Intelligent Energy Management Made Simple. Cooling problems. Server manufacturers specify inlet air temperatures Conventional controls don’t measure it Overcooling Inefficiency Hot spots. Cooling control is difficult. Open plan design All cooling units affect all areas - PowerPoint PPT Presentation
Popular Tags:
12
F e d e r s p i e l C o n t r o l s 701 El Cerrito Plaza, El Cerrito, CA 94530 [email protected] | www.federspielcontrols.com | 510-524-8480 Intelligent Energy Management Made Simple
Transcript
Page 1: Intelligent Energy Management  Made Simple

F e d e r s p i e l C o n t r o l s

701 El Cerrito Plaza, El Cerrito, CA 94530

[email protected] | www.federspielcontrols.com | 510-524-8480

Intelligent Energy Management Made Simple

Page 2: Intelligent Energy Management  Made Simple

Cooling problems

• Server manufacturers specify inlet air temperatures

• Conventional controls don’t measure it

• Overcooling

• Inefficiency

• Hot spots

Page 3: Intelligent Energy Management  Made Simple

Cooling control is difficult

• Open plan design

- All cooling units affect all areas

• Redundant cooling units

- Can lead to “fighting”

• Custom control software is expensive and unreliable

- Can’t have a PhD commission every datacenter

Page 4: Intelligent Energy Management  Made Simple

What we do

Insight

Analysis

Control

< 2yr ROI

Page 5: Intelligent Energy Management  Made Simple

How we do it

• Measure inlet air temps

• Supervisory control

• Learning algorithms

• Installed in days

Wireless ModuleWireless Module

Temperature Probes

Page 6: Intelligent Energy Management  Made Simple

Recommended deployment strategy

• Install controls first

- Immediate automated energy savings

- Excellent complement to IT-side best practices

• Persistent Commissioning™

- Determine where and how to improve

- Cost effective deployment of best practices

65

70

75

80

85

90

7:55AM

8:09AM

8:24AM

8:38AM

8:52AM

9:07AM

9:21AM

9:36AM

time

degF

first change

second change

Page 7: Intelligent Energy Management  Made Simple

Case Study 1 – Franchise Tax Board

• The Data center:- 10,000 SF- 12 CRAH’s (22 tons each)- 40% built out

• The solution:- 50 wireless inlet server temperature sensors- 4 VFDs installed- Re-arranged tiles- Reset setpoints of CRAHs- Automatic start-stop of CRAHs

Page 8: Intelligent Energy Management  Made Simple

Case Study 1 – Energy Savings

• Software shut off 6-8 CRAH units- All temperatures within ASHRAE recommended range

• 310,000 kWh/year saved- 245,000 kWh/year fan savings- 65,000 kWh/year chiller savings

• $27,900/year saved ($0.09/kWh)

• 58% reduction in fan energy usage

• 13.4% reduction of total datacenter energy usage

Page 9: Intelligent Energy Management  Made Simple

Case Study 2 – Bay Area

• The Data center:- 5,000 SF- 6 CRAH’s (22 tons each)- 130 racks

• The solution:- 48 inlet air temperature sensors- 6 VFDs with wireless controls- No other efficiency measures taken- One-day installation

Page 10: Intelligent Energy Management  Made Simple

Case Study 2 – Energy Savings

• 300,000 kWh/year saved- 218,000 kWh/year verified fan savings- 82,000 kWh/year estimated chiller savings

• $27,000/year saved ($0.09/kWh)

• 80% reduction in fan energy usage

• 17% reduction of total datacenter energy usage

Page 11: Intelligent Energy Management  Made Simple

Customer perspective

Page 12: Intelligent Energy Management  Made Simple

Summary

• Excellent ROI from supervisory cooling control

• Quick and non-intrusive installation

• Enables cost-effective application of best practices

• Excellent complement to IT-side best practices