+ All Categories
Home > Documents > International Site for Spirax Sarco

International Site for Spirax Sarco

Date post: 14-Apr-2018
Category:
Upload: cnghia
View: 228 times
Download: 0 times
Share this document with a friend

of 10

Transcript
  • 7/30/2019 International Site for Spirax Sarco

    1/10

    International site for Spirax Sarco Tel: (800) 575-0394Fax: (803) 714-2222

    http://www.SpiraxSarco.com/us/

    You are here: Home Resources Steam Engineering Tutorials

    Steam Engineering Principles and Heat Transfer Heating with Coils and Jackets

    Indirect heating of fluids is covered in this tutorial

    including layouts, control and drainage of coils andjackets, and heat transfer calculations.

    The printable version of this page has

    been replaced by

    The Steam and Condensate Loop Book

    View the complete collection ofSteam

    Engineering Tutorials

    Heating with Coils and Jackets

    Vessels can be heated in a number of different ways. This tutorial will deal with indirect heating. In t

    systems, the heat is transferred across a heat transfer surface. Options include:

    Submerged steam coils - A widely used form of heat transfer involves the installation inside a

    tank of a steam coil immersed in a process fluid.

    Steam jackets - Steam circulates in the annular space between a jacket and the vessel walls, a

    heat is transferred through the wall of the vessel.

    Submerged steam coilsThe use of tank coils is particularly common in marine applications where cargoes of crude oil, e

    oils, tallow and molasses are heated in deep tanks. Many of these liquids are difficult to hand

    ambient temperatures due to their viscosity. Steam heated coils are used to raise the temperatu

    these liquids, lowering their viscosity so that they become easier to pump.

    Tank coils are also extensively used in electroplating and metal treatment. Electroplating inv

    passing articles through several process tanks so that metallic coatings can be deposited on to

    surfaces. One of the first stages in this process is known as pickling, where materials such as stee

    copper are treated by dipping them in tanks of acid or caustic solution to remove any scale or oxiderust) which may have formed.

    Steam coil sizingHaving determined the energy required (in Tutorial 2.9), and with knowledge of the s

    pressure/temperature in the coil, the heat transfer surface may be determined using Equation 2.5.3:

    Equation 2.5.3

    The heat transfer area calculated is equivalent to the surface area of the coil, and will enab

    appropriate size and layout to be specified.

    Determining the 'U' value

    To calculate the heat transfer area, a value for the overall heat transfer coefficient, U, must be choThis will vary considerably with the thermal and transport properties of both fluids and a range of

    conditions.

    On the product side of the coil a thermal boundary layer will exist in which there is a tempera

    gradient between the surface and the bulk fluid. If this temperature difference is relatively large, the

    natural convective currents will be significant and the heat transfer coefficient will be high.

    Assisted circulation (such as stirring) that will induce forced convection, will also result in h

    coefficients. As convection is partially dependent on the bulk motion of the fluid, the viscosity (w

    varies with temperature) also has an important bearing on the thermal boundary layer.

    Additional variations can also occur on the steam side of the coil, especially with long lengths of

    The coil inlet may have a high steam velocity and may be relatively free from water. However, fu

    along the length of the coil the steam velocity may be lower, and the coil may be running partially fwater. In very long coils, such as those sometimes found in seagoing tankers or in large bulk sto

    eam Engineering

    inciples and Heat

    ansfer

    ngineering Units

    hat is Steam?

    uperheated Steam

    eam Quality

    eat Transfer

    ethods of Estimating Steam

    onsumption

    easurement of Steam

    onsumption

    hermal Rating

    nergy Consumption of Tanksnd Vats

    eating with Coils and

    ackets

    eating Vats and Tanks by

    eam Injection

    eam Consumption of Pipes

    nd Air Heaters

    eam Consumption of Heat

    xchangers

    eam Consumption of Plant

    emsntropy - A Basic

    nderstanding

    ntropy - Its Practical Use

    elated Content

    ank Coil Heating

    rowse a drawing and

    omponent sheet for a

    pical tank coil

    pplication.

    team Tables

    comprehensive set of

    eam tables is available

    ere.

    anks & Vats

    etermine the size of

    eam coil required to

    eat your tank.

    Home About Us Products & Services Industries & Applications Training Resources Contact

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial

    0 8/13/2013 1

  • 7/30/2019 International Site for Spirax Sarco

    2/10

    tanks, a significant pressure drop occurs along the length of the coil. To acheive the mean

    temperature, an average steam pressure of approximately 75% of the inlet pressure may be use

    extreme cases the average pressure used may be as low as 40% of the inlet pressure.

    Another variable is the coil material itself. The thermal conductivity of the coil material may

    considerably. However, overall heat transfer is governed to a large extent by the heat resistant films

    the thermal conductivity of the coil material is not as significant as their combined effect. Table 2

    provides typical overall heat transfer coefficients for various conditions of submerged steam

    application. 'U' values for steam pressures between 2 bar g and 6 bar g should be found by interpol

    of the data in the table.

    The range of figures shown in Table 2.10.1 demonstrates the difficulty in providing definitive 'U' va

    Customary figures at the higher end of the scale will apply to installations that are supplied with c

    dry steam, small coils and good condensate drainage. The lower end is more applicable to poor qusteam, long coils and poor condensate drainage.

    The recommended overall heat transfer coefficients will apply to typical conditions and installat

    These recommended rates are empirically derived, and will generally ensure that a generous s

    margin applies to the coil sizing.

    In the case of fluids other than water, the heat transfer coefficient will vary even more widely due t

    way in which viscosity varies with temperature. However, the values shown in Table 2.10.2 will serve

    guide for some commonly encountered substances, while Table 2.10.3 gives typical surface are

    pipes per metre length.

    Example 2.10.1Continuing from Example 2.9.1 determine:

    Part 1. The average steam mass flowrate during start-up. (Mean heat load = 367 kW)

    he Steam and

    ondensate Loop Book

    comprehensive best

    actice guide to saving

    nergy and optimising

    ant performance, this

    ook covers all aspects

    steam and condensate

    ystems.

    rder your copy today

    eature

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial

    0 8/13/2013 1

  • 7/30/2019 International Site for Spirax Sarco

    3/10

    Part 2. The heat transfer area required.

    Part 3. A recommended coil surface area.

    Part 4. The maximum steam mass flowrate with the recommended heat transfer area.

    Part 5. A recommendation for installation, including coil diameter and layout.

    The following additional information has been provided:

    Steam pressure onto the control valve = 2.6 bar g (3.6 bar a).

    A stainless steel steam coil provides heat.

    Heat transfer coefficient from steam/coil/liquid, U = 650 W/mC

    Part 1 Calculate the average steam mass flowrate during start-up

    Steam pressure onto the control valve = 2.6 bar g (3.6 bar a)

    Critical pressure drop (CPD) will occur across the control valve during start-up, therefore the mini

    steam pressure in the heating coil should be taken as 58% of upstream absolute pressure

    explanation of this is given in Block 5.

    Part 2 Calculate the heat transfer area required.

    Part 3 A recommendation for coil surface area

    Because of the difficulties in providing accurate 'U' values, and to allow for future fouling of the

    exchange surface, it is usual to add 10% to the calculated heat transfer area.

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial

    0 8/13/2013 1

  • 7/30/2019 International Site for Spirax Sarco

    4/10

    Part 4 The maximum steam mass flowrate with the recommended heat transfer area

    Maximum heat transfer (and hence steam demand) will occur when the temperature difference bet

    the steam and the process fluid is at its maximum, and should take into consideration the extra pipe

    allowed for fouling.

    (a) Consider the maximum heating capacity of the coil(coil)

    Using Equation 2.5.3: = UAT

    (b) Steam flowrate to deliver 519 kW

    Part 5 A recommendation for installation, including coil diameter and layout

    (a) Determine coil diameter and length

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial

    0 8/13/2013 1

  • 7/30/2019 International Site for Spirax Sarco

    5/10

    From Table 2.10.3, a 100 mm pipe has a surface area of 0.358 m/m run. This application will require:

    It may be difficult to accommodate this length of large bore heating pipe to install in a 3 m 3 m tank

    One solution would be to run a bank of parallel pipes between steam and condensate manifolds, s

    different heights to encourage condensate to run to the lower (condensate) manifold. The drain line

    fall from the bottom of the condensate manifold down to the steam trap (or pump-trap). See Figure 2

    for a suggested layout.

    Fig. 2.10.1

    Possible layout of coils in a rectangular tank

    Note the steam supply is situated at one end of its manifold, whilst the trap set is at the other end.

    will help steam to flow and push condensate through the coils.

    In the application, the steam and condensate headers would each be 2.8 m long. As the condenmanifold is holding condensate, the heat from it will be small compared to the steam manifold and

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial

    0 8/13/2013 1

  • 7/30/2019 International Site for Spirax Sarco

    6/10

    can be ignored in the calculation.

    The steam manifold should be 100 mm diameter as determined by the previous velocity calculation.

    will provide a heating area of:

    2.8 m x 0.358 m/m = 1.0 m

    Consequently 7 m - 1 m = 6 m of heat transfer area is still required, and must be provided by

    connecting pipes.

    Arbitrarily selecting 32 mm pipe as a good compromise between robustness and workability:

    The lengths of the connecting pipes are 2.5 m.

    CHECK

    It is necessary to confirm the steam velocity through the connecting tubes:

    On the basis of proportionality of heat transfer area, the steam header will condense:

    This leaves 86% of the 850 kg/h = 731 kg/h of steam which must pass through the 18 connecting p

    and also into the lower (condensate) manifold.

    Other steam coil layoutsThe design and layout of the steam coil will depend on the process fluid being heated. When the pro

    fluid to be heated is a corrosive solution, it is normally recommended that the coil inlet and o

    connections are taken over the lip of the tank, as it is not normally advisable to drill through

    corrosion resistant linings of the tank side. This will ensure that there are no weak points in the

    lining, where there is a risk of leakage of corrosive liquids. In these cases the coil itself may als

    made of corrosion resistant material such as lead covered steel or copper, or alloys such as titanium

    However, where there is no danger of corrosion, lifts over the tank structure should be avoided, an

    steam inlet and outlet connections may be taken through the tank side. The presence of any lif

    result in waterlogging of a proportion of the coil length, and possibly waterhammer, noise and lea

    pipework.

    Steam heating coils should generally have a gradual fall from the inlet to the outlet to ensure

    condensate runs toward the outlet and does not collect in the bottom of the coil.

    Where a lift is unavoidable, it should be designed to include a seal arrangement at the bottom of th

    and a small bore dip pipe, as shown in Figure 2.10.2.

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial

    0 8/13/2013 1

  • 7/30/2019 International Site for Spirax Sarco

    7/10

    Fig. 2.10.2

    Tank with a rising discharge pipe

    The seal arrangement allows a small amount of condensate to collect to act as a water seal, and prev

    the occurrence of steam locking. Without this seal, steam can pass over any condensate collecting ibottom of the pipe, and close the steam trap at the top of the riser.

    The condensate level would then rise and form a temporary water seal, locking the steam between

    bottom of the riser and the steam trap. The steam trap remains closed until the locked steam conden

    during which time the coil continues to waterlog.

    When the locked steam condenses and the steam trap opens, a slug of water is discharged up the

    As soon as the water seal is broken, steam will enter the rising pipe and close the trap, while the br

    column of water falls back to lie at the bottom of the heating coil.

    The small bore dip pipe will only allow a very small volume of steam to become locked in the ris

    enables the water column to be easily maintained without steam bubbling through it, ensuring there

    steady and continuous condensate flow to the outlet.

    When the seal is ultimately broken, a smaller volume of water will return to the heating coil than wi

    unrestricted large bore riser, but as the water seal arrangement requires a smaller volume of conden

    to form a water seal, it will immediately re-form.

    If the process involves articles being dipped into the liquid, it may not be convenient to install the c

    the bottom of the tank - it may be damaged by the objects being immersed in the solution. Also, du

    certain processes, heavy deposits will settle at the bottom of the tank and can quickly cover the he

    surface, inhibiting heat transfer.

    For these reasons side hung coils are often used in the electroplating industry. In such cases serpe

    or plate-type coils are arranged down the side of a tank, as shown in Figure 2.10.3. These coils sh

    also have a fall to the bottom with a water seal and a small bore dip-pipe. This arrangement has

    advantage that it is often easier to install, and also easier to remove for periodic cleaning if required.

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial

    0 8/13/2013 1

  • 7/30/2019 International Site for Spirax Sarco

    8/10

    Fig. 2.10.3

    Side hung coils

    If articles are to be dipped into the tank, it may not be possible to use any sort of agitator to in

    forced convection and prevent temperature gradients occurring throughout the tank. Whether botto

    side coils are used, it is essential that they are arranged with adequate coverage so that the hedistributed evenly throughout the bulk of the liquid.

    The diameter of the coil should provide sufficient length of coil for good distribution. A short leng

    coil with a large diameter may not provide adequate temperature distribution. However a very

    continuous length of coil may experience a temperature gradient due to the pressure drop from e

    end, resulting in uneven heating of the liquid.

    Whilst the next two headings, 'Sizing the control valve' and 'The condensate removal device' are incl

    in this Tutorial, the new reader should refer to later Tutorials for full and comprehensive informa

    before attempting sizing and selection of equipment.

    Control valve arrangementThe control valve set may be either one or two valves in parallel. A single control valve, large enou

    cope with the maximum flowrate encountered at start-up, may be unable to control flow accurately aminimum expected flowrate. This could cause erratic temperature control. An alternative is to fit

    temperature control valves in parallel:

    One valve (running valve) sized to control at the lower flowrate.

    A second valve (starting valve) to pass the difference between the capacity of the first valve, a

    the maximum flowrate.

    The starting valve would have a set-point slightly lower than the running valve, so it would close

    leaving the running valve to control at low loads.

    Sizing the control valveThe control valve set (either one valve or two valves in parallel).

    The coil has been sized on mean heat transfer values. However, it may be better to size the control vto supply the maximum (start-up) load. With large coils in tanks, this will help to maintain a degre

    steam pressure throughout the length of the coil when the steam is turned on, helping to

    condensate through the coil to the steam trapping device. If the control valve were sized on mean va

    steam pressure in the coil at start-up will tend to be lower and the coil may flood.

    Using one valveContinuing with Example 2.10.1 the maximum steam load is 850 kg/h and the coil is designed to de

    this at a pressure of 1.1 bar g. A steam valve sizing chart would show that a Kv

    of about 20 is requir

    pass 850 kg/h of steam with a pressure of 2.6 bar g at the inlet of the control valve, and Critical Pres

    Drop (CPD) across the valve. (Tutorial 6.4 will show how the valve size can be determined by calcula

    A DN40 control valve with a larger Kvs

    of 25 would therefore need to be selected for the application.

    If one valve is to be used, this valve must ensure the maximum heat load is catered for, while mainta

    the required steam pressure in the coil to assist the drainage of condensate from it at start-up. How

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial

    0 8/13/2013 1

  • 7/30/2019 International Site for Spirax Sarco

    9/10

    for reasons previously explained, two valves may be better.

    The running load is 52 kW and with the coil running at 1.1 bar g, the running steam load:

    The steam valve sizing chart shows a Kv

    of 2 is required to pass 85 kg/h with 3.6 bar upstream, oper

    at critical pressure drop.

    A DN15 KE type valve (Kvs

    = 4) and a DN25 piston actuated valve (Kvs

    = 18.6) operating togethe

    cater for the start-up load. When approaching the control temperature, the larger valve would be s

    shut down, allowing the smaller valve to give good control.

    The condensate removal deviceThe selection and sizing of the condensate removal device will be very much influenced by

    condensate backpressure. For the purpose of this example, it is assumed the backpressu

    atmospheric pressure. The device should be sized so it is able to satisfy both of the follo

    conditions:

    Pass 850 kg/h of condensate with 1.1 bar g in the coil, i.e. the full-load condition.

    Pass the condensate load when steam pressure in the coil equals the condensate backpressu

    i.e. the stall load condition.

    If the steam trap is only sized on the first condition, it is possible that it may not pass the stall load

    condition where the product approaches its required temperature and the control valve modulat

    reduce steam pressure). The stall load may be considerable. With respect to non-flow type applica

    such as tanks, this may not be too serious from a thermal viewpoint because the contents of the tan

    almost be at the required temperature, and have a huge reservoir of heat.

    Any reduction in heat transfer at this part of the heating process may therefore have little imme

    effect on the tank contents.

    However, condensate will back up into the coil and waterhammer will occur, along with its assoc

    symptoms and mechanical stresses. Tank coils in large circular tanks tend to be of robust construc

    and are often able to withstand such stresses. Problems can however occur in rectangular tanks (w

    tend to be smaller), where vibration in the coil will have more of an effect on the tank structure. Here

    energy dissipated by the waterhammer causes vibration, which can be detrimental to the life of the

    the tank, and the steam trap, as well as creating unpleasant noise.

    With respect to flow-type applications such as plate heat exchangers, a failure to consider the

    condition will usually have serious implications. This is mainly due to the small volume in the

    exchanger.

    For heat exchangers, any unwanted reduction in the heating surface area, such as that cause

    condensate backing up into the steam space, can affect the flow of heat through the heating sur

    This can cause the control system to become erratic and unstable, and processes requiring stab

    accurate control can suffer with poor performance.

    If heat exchangers are oversized, sufficient heating surface may remain when condensate backs up

    the steam space, and reduction of thermal performance may not always occur. However, with

    exchangers not designed to cope with the effects of waterlogging, this can lead to corrosion o

    heating surface, inevitably reducing the service life of the exchanger. Waterlogging can, in s

    applications, be costly. Consider a waterlogging air heater frost coil. Cold air at 4C flowing at 3 m/s

    soon freeze condensate locked in the coils, resulting in premature and unwarranted failure. P

    drainage of condensate is essential to maintain the service life of any heat exchanger and air heater.

    Steam traps are devices which modulate to allow varying amounts of condensate to drain

    applications under varying conditions. Float traps are steam traps designed to modulate and rel

    condensate close to steam temperature, offering maximum plant performance, maximum plant life

    maximum return on plant investment.

    When stall conditions occur, and a steam trap cannot be used, an automatic pump-trap or pump and

    in combination will ensure correct condensate drainage at all times, thus maximising the thecapability and lifetime costs of the plant.

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial

    0 8/13/2013 1

  • 7/30/2019 International Site for Spirax Sarco

    10/10

    The printable version of this page has now been replaced by

    The Steam and Condensate Loop Book

    View the complete collection ofSteam Engineering Tutorials

    Steam jacketsThe most commonly used type of steam jacket consists simply of an outer cylinder surrounding

    vessel, as shown in Figure 2.10.4. Steam circulates in the outer jacket, and condenses on the wall o

    vessel. Jacketed vessels may also be lagged, or may contain an internal air space surrounding

    jacket. This is to ensure that as little steam as possible condenses on the outer jacket wall, and tha

    heat is transferred inwards to the vessel.

    Fig. 2.10.4

    A conventional jacketed vessel

    The heat transfer area (the vessel wall surface area), can be calculated in the same manner as w

    steam coil, using Equation 2.5.3 and the overall heat transfer coefficients provided in Table 2.10.4.

    Although steam jackets may generally be less thermally efficient than submerged coils, due to radia

    losses to the surroundings, they do allow space for the vessels to be agitated so that heat transf

    promoted. The U values listed in Table 2.10.4. are for moderate non-proximity agitation.

    Commonly the vessel walls are made from stainless steel or glass lined carbon steel. The glass l

    will offer an additional corrosion resistant layer. The size of the steam jacket space will depend on

    size of the vessel, but typically the width may be between 50 mm and 300 mm.

    What do I do now?

    ng with Coils and Jackets : International site for Spirax Sarco http://www.spiraxsarco.com/resources/steam-engineering-tutorial


Recommended