    Intesis Software SL 1

    Functional SpecificationsGateway

    IntesisBox-BACnet-Lonworks V43

    1. BACnet Protocol Implementation Conformance Statement (PICS) ......................... 21.1BACnet Standardized Device Profile (Annex L): .............................................. 21.2 Segmentation Capability: ............................................................................ 21.3 Data Link Layer Options: ............................................................................. 31.4 Device Address Binding:.............................................................................. 31.5 Networking Options: ................................................................................... 31.6 Character Sets Supported ........................................................................... 31.7 Gateway ................................................................................................... 3

    2. BACnet Interoperability Building Blocks Supported (BIBBs) .................................. 42.1 Data Sharing BIBBs .................................................................................... 42.2 Alarm and Event Management BIBBs ............................................................ 42.3 Scheduling BIBBs ....................................................................................... 52.4 Trending BIBBs .......................................................................................... 52.5 Network Management BIBBs ........................................................................ 52.6 Device Management BIBBs .......................................................................... 6

    3. Objects .......................................................................................................... 73.1 Supported Object Types .............................................................................. 73.2 Device Object Type .................................................................................... 83.3 Analog Input Object Type ............................................................................ 93.4 Analog Output Object Type ........................................................................ 10

    3.5 Analog Value Object Type.......................................................................... 103.6 Binary Input Object Type .......................................................................... 123.7 Binary Output Object Type ........................................................................ 133.8 Binary Value Object Type .......................................................................... 133.9 Multistate Input Object Type ...................................................................... 153.10 Multistate Output Object Type .................................................................. 163.11 Multistate Value Object Type .................................................................... 17

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    2/17

    Intesis Software SL 2

    1. BACnet Protocol Implementation Conformance Statement (PICS)

    Date: 2011-02-07Vendor Name: Intesis Software SLProduct Name: IntesisBox-Bacnet-LonProduct Model Number: IntesisBox-Bacnet-LonApplication Software Version: 43.0.3Firmware Revision: 43.0.3BACnet Protocol Revision: 2

    Product Description:

    Lonworks (FT-10) to BACnet/IP Gateway

    Mapping of network variables as Bacnet Objects to enable read and write Lonworks data points.

    1.1 BACnet Standardized Device Profile (Annex L):

    BACnet Operator Workstation (B-OWS)

    BACnet Building Controller (B-BC)

    BACnet Advanced Application Controller (B-AAC)

    BACnet Application Specific Controller (B-ASC)

    BACnet Smart Sensor (B-SS)

    BACnet Smart Actuator (B-SA)

    Additional BACnet Interoperability Building Blocks Supported (Annex K):Reference of BIBBs List .

    .

    1.2 Segmentation Capability:

    Segmented request supported No Yes Window Size Segmented responses supported No Yes Window Size

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    3/17

    Intesis Software SL 3

    1.3 Data Link Layer Options:

    BACnet IP, (Annex J)BACnet IP, (Annex J), Foreign DeviceISO 8802-3, Ethernet (Clause 7)

    ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____MS/TP master (Clause 9), baud rate(s):MS/TP slave (Clause 9), baud rate(s):Point-To-Point, EIA 232 (Clause 10), baud rate(s):Point-To-Point, modem, (Clause 10), baud rate(s):LonTalk, (Clause 11), medium: _____Other:

    1.4 Device Address Binding:

    Is static device binding supported? (This is currently necessary for two-way communication withMS/TP slaves and certain other devices.) Yes No

    1.5 Networking Options:

    Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.Annex H, BACnet Tunneling Router over IPBACnet/IP Broadcast Management Device (BBMD)

    Does the BBMD support registrations by Foreign Devices? Yes No

    1.6 Character Sets Supported

    Indicating support for multiple character sets does not imply that they can all be supportedsimultaneously.

    ANSI X3.4IBM/Microsoft DBCSJIS C 6226ISO 10646 (UCS-4)ISO 10646 (UCS-2)ISO 8859-1

    1.7 Gateway

    If this product is a communication gateway, describe the types of non-BACnet equipment/network(s)that the gateway supports:

    Cable pair Lonworks (FT-10) bus and all devices in the bus.

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    4/17

    Intesis Software SL 4

    2. BACnet Interoperability Building Blocks Supported (BIBBs)

    2.1 Data Sharing BIBBs

    BIBB Type Active BACnet Service Initiate Execute

    DS-RP-A Data Sharing-ReadPropertyA ReadPropertyDS-RP-B Data Sharing-ReadPropertyB ReadProperty

    DS-RPM-A Data Sharing-ReadPropertyMultipleA ReadPropertyMultiple

    DS-RPM-B Data Sharing-ReadPropertyMultipleB ReadPropertyMultiple

    DS-RPC-A Data Sharing-ReadPropertyConditionaA ReadPropertyConditional

    DS-RPC-B Data Sharing-ReadPropertyConditionalB ReadPropertyConditional

    DS-WP-A Data Sharing-WritePropertyA WriteProperty

    DS-WP-B Data Sharing-WritePropertyB WriteProperty

    DS-WPM-A Data Sharing-WritePropertyMultipleA WritePropertyMultiple

    DS-WPM-B Data Sharing-WritePropertyMultipleB WritePropertyMultiple

    DS-COV-A Data Sharing-COVA

    SubscribeCOV

    ConfirmedCOVNotification

    UnconfirmedCOVNotification

    DS-COV-B Data Sharing-COVB

    SubscribeCOV

    ConfirmedCOVNotification

    UnconfirmedCOVNotification

    DS-COVP-A Data Sharing-COVPA

    SubscribeCOV

    ConfirmedCOVNotification

    UnconfirmedCOVNotification

    DS-COVP-B Data Sharing-COVPB SubscribeCOV

    ConfirmedCOVNotification

    UnconfirmedCOVNotification

    DS-COVU-A Data Sharing-COV-UnsolicitedA UncofirmedCOVNotification

    DS-COVU-B Data Sharing-COV-Unsolicited-B UncofirmedCOVNotification

    2.2 Alarm and Event Management BIBBs

    BIBB Type Active BACnet Service Initiate Execute

    AE-N-A Alarm and Event-NotificationAConfirmedEventNotification

    UnconfirmedEventNotification

    AE-N-I-B Alarm and Event-Notification InternalBConfirmedEventNotification

    UnconfirmedEventNotification

    AE-N-E-B Alarm and Event-Notification ExternalBConfirmedEventNotification

    UnconfirmedEventNotification

    AE-ACK-A Alarm and Event-ACKA AcknowledgeAlarm

    AE-ACK-B Alarm and Event-ACKB AcknowledgeAlarm

    AE-ASUM-A Alarm and Event-SummaryA GetAlarmSummary

    AE-ASUM-B Alarm and Event-Summary

    B GetAlarmSummaryAE-ESUM-A Event-SummaryA GetEnrollmentSummary

    AE-ESUM-B Event-SummaryB GetEnrollmentSummary

    AE-INFO-A Alarm and Event-InformationA GetEventInformation

    AE-INFO-B Alarm and Event-InformationB GetEventInformation

    AE-LS-A Alarm and Event-LifeSafetyA LifeSafetyOperation

    AE-LS-B Alarm and Event-LifeSafetyB LifeSafetyOperation

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    5/17

    Intesis Software SL 5

    2.3 Scheduling BIBBs

    2.4 Trending BIBBs

    2.5 Network Management BIBBs

    BIBB Type Active BACnet Service Initiate Execute

    SCHED-ASchedulingA(must support DS-RP-A and DS-WP-A)

    SCHED-I-BScheduling-InternalB(shall support DS-RP-B and DS-WP-B)(shall also support ether DM-TS-B or DS-UTC-B)

    SCHED-E-BScheduling-ExternalB(shall support SCHED-I-B and DS-WP-A)

    T-VMT-A Trending - Viewing and Modifying TrendsA ReadRange

    T-VMT-I-B Trending - Viewing and Modifying Trends InernalB ReadRange

    T-VMT-E-B Trending - Viewing and Modifying Trends ExternalB ReadRange

    T-ATR-A Trending - Automated Trend RetrievalAConfirmedEventNotification

    ReadRange

    T-ATR-B Trending - Automated Trend RetrievalBConfirmedEventNotification

    ReadRange

    BIBB Type Active BACnet Service Initiate Execute

    T-VMT-A Trending - Viewing and Modifying TrendsA ReadRange

    T-VMT-I-B Trending - Viewing and Modifying Trends InernalB ReadRange

    T-VMT-E-B Trending - Viewing and Modifying Trends ExternalB ReadRange

    T-ATR-A Trending - Automated Trend RetrievalAConfirmedEventNotification

    ReadRange

    T-ATR-B Trending - Automated Trend RetrievalBConfirmedEventNotification

    ReadRange

    BIBB Type Active BACnet Service Initiate Execute

    NM-CE-A Network Management - Connection EstablishmentA

    Establish-Connection-To-Network

    Disconnect-Connection-To-Network

    NM-CE-B Network Management - Connection Establishment B

    Establish-Connection-To-NetworkDisconnect-Connection-To-Network

    NM-RC-A Network Management - Router ConfigurationA

    Who-Is-Router-To-Network

    I-Am-Router-To-NetworkI-Could-Be-Router-To-Network

    Initialize-Routing-Table

    Initialize-Routing-Table-Ack

    NM-RC-B Network Management - Router ConfigurationB

    Who-Is-Router-To-Network

    I-Am-Router-To-Network

    Initialize-Routing-Table

    Initialize-Routing-Table-Ack

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    6/17

    Intesis Software SL 6

    2.6 Device Management BIBBs

    BIBB Type Active BACnet Service Initiate Execute

    DM-DDB-A Device Management - Dynamic Device BindingAWho-Is

    I-Am

    DM-DDB-B Device Management - Dynamic Device BindingB Who-IsI-Am

    DM-DOB-A Device Management - Dynamic Object BindingAWho-Has

    I-Have

    DM-DOB-B Device Management - Dynamic Object BindingBWho-Has

    I-Have

    DM-DCC-A Device Management - DeviceCommunicationControlA DeviceCommunicationControl

    DM-DCC-B Device Management - DeviceCommunicationControlB DeviceCommunicationControl

    DM-PT-A Device Management - PrivateTransferAConfirmedPrivateTransfer

    UnconfirmedPrivateTransfer

    DM-PT-B Device Management - PrivateTransferBConfirmedPrivateTransfer

    UnconfirmedPrivateTransfer

    DM-TM-A Device Management - Text Message

    A

    ConfirmedTextMessage

    UnconfirmedTextMessage

    DM-TM-B Device Management - Text MessageBConfirmedTextMessage

    UnconfirmedTextMessage

    DM-TS-A Device Management - TimeSynchronizationA TimeSynchronization

    DM-TS-B Device Management - TimeSynchronizationB TimeSynchronization

    DM-UTC-A Device Management - UTCTimeSynchronizationA UTCTimeSynchronization

    DM-UTC-B Device Management - UTCTimeSynchronizationB UTCTimeSynchronization

    DM-RD-A Device Management - ReinitializeDeviceA ReinitializeDevice

    DM-RD-B Device Management - ReinitializeDeviceB ReinitializeDevice

    DM-BR-A Device Management - Backup and RestoreA

    AtomicReadFile

    AtomicWriteFile

    CreateObject

    ReinitializeDevice

    DM-BR-B Device Management - Backup and RestoreB

    AtomicReadFile

    AtomicWriteFile

    ReinitializeDevice

    DM-R-A Device Management - RestartA UnconfimedCOVNotification

    DM-R-B Device Management - RestartB UnconfimedCOVNotification

    DM-LM-A Device Management - List ManipulationAAddListElement

    RemoveListElement

    DM-LM-B Device Management - List ManipulationBAddListElement

    RemoveListElement

    DM-OCD-A Device Management - Object Creation and DeletionACreateObject

    DeleteObject

    DM-OCD-B Device Management - Object Creation and DeletionBCreateObject

    DeleteObject

    DM-VT-A Device Management - Virtual TerminalA

    VT-Open

    VT-Close

    VT-Data

    DM-VT-B Device Management - Virtual TerminalB

    VT-Open

    VT-Close

    VT-Data

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    7/17

    Intesis Software SL 7

    3. Objects

    3.1 Supported Object Types

    To monitoring and controlling items of Lonworks networks variables, they are assigned with general objecttypes specified by BACnet. The objects type supported is shown in the table below.

    Object Type ID Supported Management Point

    Analog-Input 0 User defined

    Analog-Output 1 User defined

    Analog-Value 2 User defined

    Averaging 18

    Binary-Input 3 User defined

    Binary-Output 4 User defined

    Binary-Value 5 User defined

    Calendar 6

    Command 7

    Device 8

    Event-Enrollment 9

    File 10

    Group 11

    Life-Safety-Point 21

    Life-Safety-Zone 22

    Loop 12

    Multistate-Input 13 User defined

    Multistate-Output 14 User defined

    Multistate-Value 19 User defined

    Notification-Class 15

    Program 16

    Schedule 17

    Trend-Log 20

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    8/17

    Intesis Software SL 8

    3.2 Device Object Type

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R User defined

    Object_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R DEVICE

    System_Status BACnetDeviceStatus R R

    Vendor_Name CharacterString R R Intesis Software SL

    Vendor_Identifier Unsigned R R 246

    Model_Name CharacterString R R IntesisBox_BACNET_LON

    Firmware_Revision CharacterString R R 43.0.1

    Application_Software_Version CharacterString R R 43.0.1

    Location CharacterString O -

    Description CharacterString O -

    Protocol_Version Unsigned R R 1

    Protocol_Conformance_Class Unsigned R R 3

    Protocol_Services_SupportedBACnetServiceSupported

    R R

    Protocol_Object_Types_SupportedBACnetObjectTypesSupported

    R R

    Object_ListBACnetARRAY[N] ofBACnetObjectIdentifir

    R -

    Max_APDU_Length_Accepted Unsigned R R

    Segmentation_Supported BACnetSegmentation R R

    VT_Class_Supported List of ACnetVTClass O1 -

    Active_VT_SessionsList of

    BACnetVTSession

    O2 -

    Local_Time Time O3,4 -

    Local_Date Date O3,4 -

    UTC_Offset Signed O4 -

    Daylight_Saving_Status Boolean O4 -

    APDU_Segment_Timeout Unsigned O1 -

    APDU_Timeout Unsigned R R 3000

    Number_Of_APDU_Retries Unsigned R R 3

    List_Of_Session_KeysList ofBACnetSessionKey

    O -

    Time_Synchronization_RecipientsList ofBACnetRecipient

    O5 -

    Max_Master Unsigned O6 -

    Max_Info_Frames Unsigned O6 -

    Device_Adress_BindingList of BACnetAddressBinding

    R R .

    Database_Revision Unsigned R R .

    Configuration_FilesBACnetARRAY[N] ofBACnetObjectIdentifir

    O7 -

    Last_Restore_Time BACnetDateTime O7 -

    Backup_Failure_Timeout Unsigned O8 -

    Active_COV_SubscriptionsList of BACnetCOVSubscription

    O9 -

    Profile_Name CharacterString O -

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    9/17

    Intesis Software SL 9

    3.3 Analog Input Object Type

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R User definedObject_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R ANALOG INPUT

    Present_Value Real R1 R

    Description CharacterString O - Same the object name

    Device_Type CharacterString O -

    Status_Flags BACnetStatusFlags R R All bits: FALSE always.

    Event_State BACnetEventState R R NORMAL: NORMAL (0)

    Reliability BACnetReliability O R NO_FAULT_DETECTED always.

    Out_Of_Service Boolean R R Always FALSE.

    Update_Interval Unsigned O -

    Units BACnetEngineeringUnits R R NULL (no units)

    Min_Pres_Value Real O -

    Max_Pres_Value Real O -

    Resolution Real O -

    COV_Increment Real O2 R Any change

    Time_Delay Unsigned O3 -

    Notification_Class Unsigned O3 -

    High_Limit Real O3 -

    Low_Limit Real O3 -

    Deadband Real O3 -

    Limit_Enable BACnetLimitEnable O3 -

    Event_Enable BACnetEventTransitionBits O3 -

    Acked_Transitions BACnetEventTransitionBits O3 -

    Notify_Type BACnetNotifyType O3 -

    Event_Time_StampsBACnetARRAY[3] ofBACnetTimeStamp

    O3 -

    Profile_Name CharacterString O -

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    10/17

    Intesis Software SL 10

    3.4 Analog Output Object Type

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R

    Object_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R ANALOG INPUT

    Present_Value Real R4 RW

    Description CharacterString O R Same the object name

    Status_Flags BACnetStatusFlags R R All bits: FALSE always.

    Event_State BACnetEventState R R NORMAL: NORMAL (0)

    Reliability BACnetReliability O R NO_FAULT_DETECTED always.

    Out_Of_Service Boolean R R Always FALSE.

    Units BACnetEngineeringUnits R R NULL (no units)

    Min_Pres_Value Real O -

    Max_Pres_Value Real O -

    Resolution Real O -

    Priority_Array BACnetPriorityArray R R Accept all writes as Priority 16

    Relinquish_Default BACnetBinaryPV R R Same Present_Value data

    COV_Increment Real O2 R Any change

    Time_Delay Unsigned O3 -

    Notification_Class Unsigned O3 -

    High_Limit Real O3 -

    Low_Limit Real O3 -

    Deadband Real O3 -

    Limit_Enable BACnetLimitEnable O3 -

    Event_Enable BACnetEventTransitionBits O3 -

    Acked_Transitions BACnetEventTransitionBits O3 -

    Notify_Type BACnetNotifyType O3 -

    Event_Time_StampsBACnetARRAY[3] ofBACnetTimeStamp

    O3 -

    Profile_Name CharacterString O -

    3.5 Analog Value Object Type

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    11/17

    Intesis Software SL 11

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R

    Object_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R ANALOG VALUE

    Present_Value Real R4 RW

    Description CharacterString O R Same the object name

    Device_Type CharacterString O -

    Status_Flags BACnetStatusFlags R R All bits: FALSE always.

    Event_State BACnetEventState R R NORMAL: NORMAL (0)

    Reliability BACnetReliability O R NO_FAULT_DETECTED always.

    Out_Of_Service Boolean R R Always FALSE.

    Units BACnetEngineeringUnits R R NULL (no units)

    Priority_Array BACnetPriorityArray R R Accept all writes as Priority 16

    Relinquish_Default BACnetBinaryPV R R Same Present_Value data

    COV_Increment Real O2 R Any change

    Time_Delay Unsigned O3 -

    Notification_Class Unsigned O3 -

    High_Limit Real O3 -

    Low_Limit Real O3 -

    Deadband Real O3 -

    Limit_Enable BACnetLimitEnable O3 -

    Event_Enable BACnetEventTransitionBits O3 -

    Acked_Transitions BACnetEventTransitionBits O3 -

    Notify_Type BACnetNotifyType O3 -

    Event_Time_StampsBACnetARRAY[3] ofBACnetTimeStamp

    O3 -

    Profile_Name CharacterString O -

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    12/17

    Intesis Software SL 12

    3.6 Binary Input Object Type

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R

    Object_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R BINARY INPUT

    Present_Value BACnetBinaryPV R1 R

    Description CharacterString O R Same the object name

    Device_Type CharacterString O -

    Status_Flags BACnetStatusFlags R R All bits: FALSE always.

    Event_State BACnetEventState R R Always NORMAL: NORMAL (0)

    Reliability BACnetReliability O R NO_FAULT_DETECTED always.

    Out_Of_Service Boolean R R Always FALSE.

    Polarity BACnetPolarity R R NORMAL

    Inactive_Text CharacterString O2 -

    Active_Text CharacterString O2 -

    Change_Of_State_Time BACnetDateTime O3 -

    Change_Of_State_Count Unsigned O3 -

    Elapsed_Active_Time Unsigned O4 -

    Time_Of_Active_Time_Reset BACnetDateTime O5 -

    Time_Delay Unsigned O5 -

    Notification_Class Unsigned O5 -

    Alarm_Value BACnetBinaryPV O5 -

    Event_Enable BACnetEventTransitionBits O5 -

    Acked_Transitions BACnetEventTransitionBits O5 -Notify_Type BACnetNotifyType O5 -

    Event_Time_StampsBACnetARRAY[3] ofBACnetTimeStamp

    O5 -

    Profile_Name CharacterString O -

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    13/17

    Intesis Software SL 13

    3.7 Binary Output Object Type

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R

    Object_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R BINARY INPUT

    Present_Value BACnetBinaryPV W RW

    Description CharacterString O R Same the object name

    Device_Type CharacterString O -

    Status_Flags BACnetStatusFlags R R All bits: FALSE always.

    Event_State BACnetEventState R R Always NORMAL: NORMAL (0)

    Reliability BACnetReliability O R NO_FAULT_DETECTED always.

    Out_Of_Service Boolean R R Always FALSE.

    Polarity BACnetPolarity R R NORMAL

    Inactive_Text CharacterString O1 -

    Active_Text CharacterString O1 -

    Change_Of_State_Time BACnetDateTime O2 -

    Change_Of_State_Count Unsigned O2 -

    Time_Of_State_Count_Reset BACnetDateTime O2 -

    Elapsed_Active_Time Unsigned O3 -

    Time_Of_Active_Time_Reset BACnetDateTime O3 -

    Minimum_Off_Time Unsigned O -

    Minimum_On_Time Unsigned O -

    Priority_Array BACnetPriorityArray R R Accept all writes as Priority 16

    Relinquish_Default BACnetBinaryPV Same Present_Value dataTime_Delay Unsigned O4 -

    Notification_Class Unsigned O4 -

    Feedback_Value BACnetBinaryPV O4 -

    Event_Enable BACnetEventTransitionBits O4 -

    Acked_Transitions BACnetEventTransitionBits O4 -

    Notify_Type BACnetNotifyType O4 -

    Event_Time_StampsBACnetARRAY[3] ofBACnetTimeStamp

    O4 -

    Profile_Name CharacterString O -

    3.8 Binary Value Object Type

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    14/17

    Intesis Software SL 14

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R

    Object_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R BINARY VALUE

    Present_Value BACnetBinaryPV W RW

    Description CharacterString O R Same the object name

    Status_Flags BACnetStatusFlags R R All bits: FALSE always.

    Event_State BACnetEventState R R Always NORMAL: NORMAL (0)

    Reliability BACnetReliability O R NO_FAULT_DETECTED always.

    Out_Of_Service Boolean R R Always FALSE.

    Inactive_Text CharacterString O1 -

    Active_Text CharacterString O1 -

    Change_Of_State_Time BACnetDateTime O2 -

    Change_Of_State_Count Unsigned O2 -

    Time_Of_State_Count_Reset BACnetDateTime O2 -

    Elapsed_Active_Time Unsigned O3 -

    Time_Of_Active_Time_Reset BACnetDateTime O3 -

    Minimum_Off_Time Unsigned O -

    Minimum_On_Time Unsigned O -

    Priority_Array BACnetPriorityArray R R Accept all writes as Priority 16

    Relinquish_Default BACnetBinaryPV Same Present_Value data

    Time_Delay Unsigned O4 -

    Notification_Class Unsigned O4 -

    Alarm_Value BACnetBinaryPV O4 -

    Event_Enable BACnetEventTransitionBits O4 -

    Acked_Transitions BACnetEventTransitionBits O4 -

    Notify_Type BACnetNotifyType O4 -

    Event_Time_StampsBACnetARRAY[3] ofBACnetTimeStamp

    O4 -

    Profile_Name CharacterString O -

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    15/17

    Intesis Software SL 15

    3.9 Multistate Input Object Type

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R

    Object_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R MULTISTATE INPUT

    Present_Value Unsigned R1 R

    Description CharacterString O R Same the object name

    Device_Type CharacterString O -

    Status_Flags BACnetStatusFlags R R All bits: FALSE always.

    Event_State BACnetEventState R R Always NORMAL: NORMAL (0)

    Reliability BACnetReliability O2 R NO_FAULT_DETECTED always.

    Out_Of_Service Boolean R R Always FALSE.

    Number_Of_States Unsigned R - Unreliable

    State_Text BACnetARRAY[N] ofCharacterString O -

    Time_Delay Unsigned O3 -

    Notification_Class Unsigned O3 -

    Alarm_Values List of Unsigned O3 -

    Event_Enable BACnetEventTransitionBits O3 -

    Acked_Transitions BACnetEventTransitionBits O3 -

    Notify_Type BACnetNotifyType O3 -

    Event_Time_StampsBACnetARRAY[3] ofBACnetTimeStamp

    O3 -

    Profile_Name CharacterString O -

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    16/17

    Intesis Software SL 16

    3.10 Multistate Output Object Type

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R

    Object_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R MULTISTATE OUTPUT

    Present_Value Unsigned R1 RW

    Description CharacterString O R Same the object name

    Device_Type CharacterString O -

    Status_Flags BACnetStatusFlags R R All bits: FALSE always.

    Event_State BACnetEventState R R Always NORMAL: NORMAL (0)

    Reliability BACnetReliability O2 R NO_FAULT_DETECTED always.

    Out_Of_Service Boolean R R Always FALSE.

    Number_Of_States Unsigned R - Unreliable

    State_TextBACnetARRAY[N] ofCharacterString

    O -

    Priority_Array BACnetPriorityArray R R Accept all writes as Priority 16

    Relinquish_Default Unsigned R R Same Present_Value data

    Time_Delay Unsigned O1 -

    Notification_Class Unsigned O1 -

    Feedback_Values Unsigned O1 -

    Event_Enable BACnetEventTransitionBits O1 -

    Acked_Transitions BACnetEventTransitionBits O1 -

    Notify_Type BACnetNotifyType O1 -

    Event_Time_StampsBACnetARRAY[3] ofBACnetTimeStamp

    O1 -

    Profile_Name CharacterString O -

  • 7/30/2019 IntesisBox BACnet IP Server LON PICS

    17/17

    Intesis Software SL 17

    3.11 Multistate Value Object Type

    Property Identifier Property Datatype BACnet IntesisBox Remarks

    Object_Identifier BACneObjectIdentifier R R

    Object_Name CharacterString R R User defined

    Object_Type BACnetObjectType R R MULTISTATE OUTPUT

    Present_Value Unsigned R1 RW

    Description CharacterString O R Same the object name

    Status_Flags BACnetStatusFlags R R All bits: FALSE always.

    Event_State BACnetEventState R R Always NORMAL: NORMAL (0)

    Reliability BACnetReliability O2 R NO_FAULT_DETECTED always.

    Out_Of_Service Boolean R R Always FALSE.

    Number_Of_States Unsigned R - Unreliable

    State_TextBACnetARRAY[N] ofCharacterString

    O -

    Priority_Array BACnetPriorityArray O3 R Accept all writes as Priority 16

    Relinquish_Default Unsigned O3 R Same Present_Value data

    Time_Delay Unsigned O4 -

    Notification_Class Unsigned O4 -

    Alarm_Values List of Unsignet O4 -

    Fault_Values List of Unsignet O4 -

    Acked_Transitions BACnetEventTransitionBits O4 -

    Notify_Type BACnetNotifyType O4 -

    Event_Time_StampsBACnetARRAY[3] ofBACnetTimeStamp

    O4 -

    Profile_Name CharacterString O -


Recommended