Introduction to 4-20mA Current Loop Transmitters TI Precision Labs Current Loop Transmitters Presented by Katlynne Jones Prepared by Katlynne Jones 1
Transcript
Page 1: Introduction to 4-20mA Current Loop Transmitters

Introduction to 4-20mA Current Loop Transmitters TI Precision Labs – Current Loop Transmitters

Presented by Katlynne Jones

Prepared by Katlynne Jones

1

Page 2: Introduction to 4-20mA Current Loop Transmitters

Current transmitter applications

2

ValveControl Station

Heater

Level

Sensor

Temp

Sensor

Ambient light, temperature,

& humidity sensors

Lighting, HVAC,

& humidity control

Control Station

Industrial automation Building automation

Page 3: Introduction to 4-20mA Current Loop Transmitters

4-20mA overview

• 4mA represents 0% input level – Allows up to 4mA to power external input circuitry

– 4mA zero level allows under-scale settings and fault detection

• 20mA represents 100% input level – Over-scale can also be used to detect fault conditions

Sensor

Receiver

250Ω

0 to 100%

Signal

4 to 20mA

Signal

Transmitter 1 to 5V0 to 150°C

3

Page 4: Introduction to 4-20mA Current Loop Transmitters

4-20mA overview

• 4mA represents 0% input level – Allows up to 4mA to power external input circuitry

– 4mA zero level allows under-scale settings and fault detection

• 20mA represents 100% input level – Over-scale can also be used to detect fault conditions

Failure OK Failure

213.60 mA

4

Page 5: Introduction to 4-20mA Current Loop Transmitters

Transmitter configurations

5

Transmitter

+

_

+

_

Receiver

Power

supply

Supply &

Signal Current

VLOOP

1

2

+

_

Power

supply

+

_

Receiver

Transmitter

Supply

Current

Signal

Current

1

2

3

4

2-wire block diagram 3-wire block diagram 4-wire block diagram

+

_

Power

supply

+

_

Receiver

Transmitter

Supply

Current

Signal

Current

1

2

3

5

Page 6: Introduction to 4-20mA Current Loop Transmitters

Field Control Station

Receiver

250Ω

Wiring

Resistance

+_

+_

4-20mA

Transmitter

Supply

24V

ADC+_

Why use current transmitters?

6

• Current transmission block diagram

– Transmitter: current

source

– Receiver: 250Ω resistor

translates current to

voltage

– ADC: translates voltage

to digital signal

Page 7: Introduction to 4-20mA Current Loop Transmitters

Field Control Station

Receiver

250Ω

Wiring

Resistance

+_

+_

4-20mA

Transmitter

Supply

24V

ADC

>1km

+_

+_

+_

Why use current transmitters?

7

• Current transmission block diagram

– Signals travel >1km

– Voltage transmission

would be attenuated

– Current loops are

essentially lossless

Page 8: Introduction to 4-20mA Current Loop Transmitters

Field Control Station

Receiver

250Ω

Wiring

Resistance

+_

+_

4-20mA

Transmitter

Supply

24V

ADC

+_

+_

+_

Current

Why use current transmitters?

8

• Current transmission block diagram

– Current in a loop is

equivalent at any point in

the loop

– Current leakage can

introduce error 8mA

8mA

Page 9: Introduction to 4-20mA Current Loop Transmitters

Field Control Station

Receiver

250Ω

+_

+_

4-20mA

Transmitter

Supply

24V

ADC+_

Current

Non-ideal

Resistance

Leakag

e

Why use current transmitters?

9

• Current transmission block diagram

– Current in a loop is

equivalent at any point in

the loop

– Current leakage can

introduce error 8mA

8mA

Page 10: Introduction to 4-20mA Current Loop Transmitters

Field Control Station

Receiver

250Ω

Wiring

Resistance

+_

+_

4-20mA

Transmitter

Supply

24V

ADC

>1km

+_

+_

+_

Environmental

Noise Source

Environmental

Noise Source

Why use current transmitters?

10

• Current transmission block diagram

– Many noise sources in

industrial environments

– Low impedance of a

current loop system

makes it much less

sensitive to induced

noise

Page 11: Introduction to 4-20mA Current Loop Transmitters

11

How are analog outputs used in industrial automation?

• Programmable logic controllers (PLCs) – Analog output modules that control

something placed in the field • Communication, valve position, position

of linear actuator, etc.

– Analog output module is powered by PLC back-plane • Primarily 3-wire systems

• Field elements –Analog outputs paired with sensors,

placed remotely in the field

–Comprise a majority of the market for industrial analog outputs

–Most often 2-wire, or loop-powered, 4-20mA sensor transmitters

Page 12: Introduction to 4-20mA Current Loop Transmitters

°T

3-Wire

Transmitter

2-Wire

Transmitter

RVLOOP

Typical 4-20mA applications

12

– Temperature

– 2-wire transmitter

– Valve, heater

– 3-wire transmitter

Transmit control

signals from a

control station out to

a remote device.

Report a process

variable from a

remote sensor to a

control station.

Page 13: Introduction to 4-20mA Current Loop Transmitters

Designing 4-20mA transmitters

• Discrete

– Customizable

• Partially integrated

– Reduces size while still allowing for various input types

• Fully integrated

– Further reduces size

– HART interface

13

Page 14: Introduction to 4-20mA Current Loop Transmitters

4-20mA transmitters – fully discrete

14

TIPD102

TIPD158

DACA1

R1

R2

+

R4 R3

VREG

Regulator

R5

Loop+

Loop-

Q1

VDAC

Page 15: Introduction to 4-20mA Current Loop Transmitters

U1

RIN

+

2475Ω

VREG_5V V+

IO

Q1

V+

Q1

E

B

5V

Regulator

4.096V

Reference

25Ω

VREF_4.096V

IIN

IRET RLIM

10 nF

XTR116

Loop+

Loop-

+

-

Ref

+

INA333

143kΩ

19.6kΩ

RG2.55kΩ10kΩ

12.49kΩ

OPA333

+

-

+

VREF_4.096V

VREF_4.096V

VREG_5V

VREF_0.5V

RADJUST

50Ω

RCOMP

10pF

CHF

10pF

CLF

IRET

IRET

IRET

10nF

10nF

4-20mA transmitters – partially integrated

15

TIPD190

TIPD155

Page 16: Introduction to 4-20mA Current Loop Transmitters

SCLK

SDO

SDIN

DVDDREFOUT REFIN LP_X

IRANGE

IENABLE

LDAC

DAC Input Register

SP

I S

hift R

egis

ter

Input

Co

ntr

ol Logic

DAC IAmp

VSENSEP_X

VENABLE

CCOMP_X

User Calibration

Register

Slew Rate Control

Internal Reference

X

Buck/Boost Converters

Watchdog Timer

Alarm

PVDD_X LN_X VPOS_IN_X

AGND1

AVDD

VAmp

Feedback

CHANNEL - A

CHANNEL - B

CHANNEL - C

CHANNEL - D

VNEG_IN_X

PVSS_X

DVDD_EN

Amp

Power On Reset

HARTIN_X

Current Source

CLR

SYNC

RESET

ALARM

AGND2 AGND3

Σ

HART Filters

GND

IOUT

VOUT

or

AVDD

4-20mA transmitters – fully integrated

16

TIPD119

TIPD216

Page 17: Introduction to 4-20mA Current Loop Transmitters

HART – what is it? why is it useful?

• HART – Highway Addressable Remote Transducer

– Bell 202 Frequency Shift Keying Standard at 1200 bps

• “Mark” and “Space” symbols (1mApp)

– Mark: 1200 Hz sinusoid, represents 1

– Space: 2200 Hz sinusoid, represents 0

17

4mA

20mA

Time

4-20mA “DC” signal

only communicates a

single variable, typically

sensor data

4mA

20mA

0

1

0

1

0

1

Time

4-20mA “DC” signal

communicates primary

variable, sensor data

HART FSK signals communicate auxiliary information such as

in-system calibration data, reliability information / diagnostics,

and additional sensor data

“Simple” sensor transmitter “Smart” sensor transmitter

Page 18: Introduction to 4-20mA Current Loop Transmitters

18

Thanks for your time!