SC 500CP-10 / SC 630CP-10 / SC 720CP-10 / SC 760CP-10 / SC 800CP-10 The award-winning design of the Sunny Central CP series saves you real money. The compact and weatherproof enclosure is easy to load and transport and can be installed almost anywhere, eliminating the need for heavy, protective concrete substa- tions. The OptiCool™ cooling concept allows it to operate at full nominal power with ambient temperatures up to 50 °C (122 °F). With powerful grid management functions, operators are perfectly prepared for today’s utility requirements, as well as those still to come. Intelligent power management is the inverter’s most important feature. In continuous operation, the Sunny Central 800CP can feed 880 kVA to the grid at ambient temperatures of up to 25 °C (77 °F). That’s 10 percent more than the rated nominal power. High performance comes standard SUNNY CENTRAL 500CP / 630CP / 720CP / 760CP / 800CP SUNNY CENTRAL 500CP / 630CP / 720CP / 760CP / 800CP Reliable • Easy and safe installation due to a separate connection area • Optional extended input voltage range up to 1100 V Flexible • Powerful grid management functions (including LVRT) • DC voltage range configurable Efficient • Full nominal power at ambient temperatures up to 50 °C (122 °F) • 10% additional power for constant operation at ambient temperatures up to 25 °C (77 °F) Economic • Outdoor enclosure allows for direct field deployment • Simplified shipping without concrete substation
Transcript
Page 1: Inverter Specifications

SC 5

00

CP

-10

/ S

C 6

30

CP

-10

/ S

C 7

20

CP

-10

/ S

C 7

60

CP

-10

/ S

C 8

00

CP

-10

The award-winning design of the Sunny Central CP series saves you real money. The compact and weatherproof enclosure is easy to load and transport and can be installed almost anywhere, eliminating the need for heavy, protective concrete substa-tions. The OptiCool™ cooling concept allows it to operate at full nominal power with ambient temperatures up to 50 °C (122 °F). With powerful grid management functions, operators are perfectly prepared for today’s utility requirements, as well as those still to come. Intelligent power management is the inverter’s most important feature. In continuous operation, the Sunny Central 800CP can feed 880 kVA to the grid at ambient temperatures of up to 25 °C (77 °F). That’s 10 percent more than the rated nominal power.

High performance comes standard

SUNNY CENTRAL 500CP / 630CP / 720CP / 760CP / 800CP

SUNNY CENTRAL 500CP / 630CP / 720CP / 760CP / 800CP

Reliable• Easy and safe installation due to

a separate connection area• Optional extended input voltage

range up to 1100 V

Flexible• Powerful grid management

functions (including LVRT)• DC voltage range configurable

Efficient• Full nominal power at ambient

temperatures up to 50 °C (122 °F)• 10% additional power for constant

operation at ambient temperatures up to 25 °C (77 °F)

Economic• Outdoor enclosure allows for

direct field deployment • Simplified shipping without

concrete substation

DS_Master_092810.indd 19DS_Master_092810.indd 19 9/28/10 2:34 PM9/28/10 2:34 PM

Page 2: Inverter Specifications

Technical data Sunny Central 720CP

Sunny Central 760CP

Sunny Central 800CP

Input DataMPP voltage range 515 V – 820 V 3) 5) 545 V – 820 V 3) 5) 570 V – 820 V 3) 5)

Max. DC voltage 1000 V / 1100 V 1) OptionalMax. DC current 1400 A 1400 A 1400 ANumber of DC inputs 9 fused inputsOutput ValuesNominal AC output @ 50 °C (122 °F) 720 kVA 760 kVA 800 kVAContinuous AC power @ 25 °C (77 °F) 792 kVA 836 kVA 880 kVAMax. AC current 1411 A 1411 A 1411 ANominal AC current 1283 A 1283 A 1283 ANominal AC voltage ±10% 324 V 342 V 360 VAC grid frequency 50 Hz ● ● ●AC grid frequency 60 Hz ● ● ●Power factor (cos ϕ) 0.9 leading ... 0.9 laggingMax. THD < 3% < 3% < 3%Power consumptionInternal consumption in operation < 1500 W 4) < 1500 W 4) < 1500 W 4)

Standby consumption < 100 W < 100 W < 100 W External auxiliary voltage 3 x 230 V, 50 / 60 Hz 3 x 230 V, 50 / 60 Hz 3 x 230 V, 50 / 60 HzDimensions and Weight Dimensions (W / H / D) in mm (in) 2562 / 2279 / 956 (101 / 90 / 116)Weight 1800 kg (3968 lb)Effi ciency 2)

Max. effi ciency 98.6% 98.6% 98.6%Euro ETA 98.4% 98.4% 98.4%CEC-eta 98.4% 98.4% 98.4%Protection Rating and Ambient ConditionsProtection rating (as per EN 60529) IP54 IP54 IP54Protection rating (as per IEC 60721-3-3) Ambient conditions: fi xed location, with protection against wind and weather

• Classification of chemically active substances: 3C2• Classification of mechanically active substances: 3S2

Operation temperature range –20 °C ... +50 °C (–4 °F ... +122 °F)Rel. humidity 15% ... 95% 15% ... 95% 15% ... 95%Fresh air consumption 3000 m3/h 3000 m3/h 3000 m3/hMax. altitude above sea level 2000 m (6562 ft) 2000 m (6562 ft) 2000 m (6562 ft)FeaturesSunny WebBox ● ● ●Communication Ethernet

(optical fi ber optional)Ethernet

(optical fi ber optional)Ethernet

(optical fi ber optional)Communication with Sunny String-Monitor RS485 RS485 RS485LCD graphic display ● ● ●

SUNNY CENTRAL 720CP / 760CP / 800CP

DS_Master_092810.indd 20DS_Master_092810.indd 20 9/28/10 2:34 PM9/28/10 2:34 PM

Page 3: Inverter Specifications

Sunny Central 720CP

Sunny Central 760CP

Sunny Central 800CP

1) Startup at DC voltage < 1000 V2) Efficiency measured without internal power supply3) Further AC voltages, DC voltages and power classes can be configured4) Internal consumption at nominal power5) At 1.05 UAC,nom and cos ϕ= 16) With complete dynamic grid support

Enclosure color RAL 9016 RAL 9016 RAL 9016Color of base RAL 7005 RAL 7005 RAL 7005Color of roof RAL 7004 RAL 7004 RAL 7004Ground fault monitoring / insulation monitoring ● ● ●Circuit breaker AC side ● ● ●Motor driven load disconnect switch on DC side ● ● ●AC overvoltage protector ● ● ●DC overvoltage protector ● ● ●Overvoltage protectors for auxiliary supply ● ● ●Certifi cates / ListingsEMC EN 61000-6-2 EN 61000-6-4CE conformity ● ● ●BDEW-MSRL / FGW / TR8 6) ● ● ●RD 1633 / 2000 ● ● ●

● Standard features ○ Optional features — Not availableType designation SC 720CP-10 SC 760CP-10 SC 800CP-10

DS_Master_092810.indd 21DS_Master_092810.indd 21 9/28/10 2:34 PM9/28/10 2:34 PM

Page 4: Inverter Specifications

Technical data Sunny Central 500CP

Sunny Central 630CP

Input DataMPP voltage range 430 V – 820 V 5) 500 V – 820 V 5)

Max. DC voltage 1000 V / 1100 V 1) OptionalMax. DC current 1250 A 1350 ANumber of DC inputs 9 fused inputsOutput ValuesNominal AC output @ 50 °C (122 °F) 500 kVA 630 kVAContinuous AC power @ 25 °C (77 °F) 550 kVA 700 kVAMax. AC current 1167 A 1271 ANominal AC current 1069 A 1155 ANominal AC voltage ±10% 270 V 315 VAC grid frequency 50 Hz ● ●AC grid frequency 60 Hz ● ●Power factor (cos ϕ) 0.9 leading ... 0.9 laggingMax. THD < 3% < 3%Power consumptionInternal consumption in operation < 1500 W 4) < 1500 W 4)

Standby consumption < 100 W < 100 W External auxiliary voltage 3 x 230 V, 50 / 60 Hz 3 x 230 V, 50 / 60 HzDimensions and Weight Dimensions (W / H / D) in mm 2562 / 2279 / 956 (101 / 90 / 116)Weight 1800 kg ( 3968 lb) 1800 kg (3968 lb)Effi ciency 2)

Max. effi ciency 98.6% 98.7%Euro ETA 98.4% 98.5%CEC-eta 98.5% 98.5%Protection Rating and Ambient ConditionsProtection rating (as per EN 60529) IP54 IP54Protection rating (as per IEC 60721-3-3) Ambient conditions: fi xed location, with protection against wind and weather

• Classification of chemically active substances: 3C2• Classification of mechanically active substances: 3S2

Operation temperature range –20 °C ... +50 °C (–4 °F ... +122 °F) –20 °C ... +50 °C (–4 °F ... +122 °F)Rel. humidity 15% ... 95% 15% ... 95%Fresh air consumption 3000 m3/h 3000 m3/hMax. altitude above sea level 2000 m (6562 ft) 2000 m (6562 ft)FeaturesSunny WebBox ● ●Communication Ethernet (optical fi ber optional) Ethernet (optical fi ber optional)Communication with Sunny String-Monitor RS485 RS485LCD graphic display ● ●Enclosure color RAL 9016 RAL 9016

SUNNY CENTRAL 500CP / 630CP

DS_Master_092810.indd 22DS_Master_092810.indd 22 9/28/10 2:34 PM9/28/10 2:34 PM

Page 5: Inverter Specifications

Sunny Central 500CP

Sunny Central 630CP

1) Startup at DC voltage < 1000 V2) Efficiency measured without internal power supply3) Further AC voltages, DC voltages and power classes can be configured4) Internal consumption at nominal power5) At 1.05 UAC,nom and cos ϕ= 16) With complete dynamic grid support

Color of base RAL 7005 RAL 7005Color of roof RAL 7004 RAL 7004Ground fault monitoring / insulation monitoring ● ●Circuit breaker AC side ● ●Motor driven load disconnect switch on DC side ● ●AC overvoltage protector ● ●DC overvoltage protector ● ●Overvoltage protectors for auxiliary supply ● ●Certifi cates / ListingsEMC EN 61000-6-2 EN 61000-6-4CE conformity ● ●BDEW-MSRL / FGW / TR8 6) ● ●RD 1633 / 2000 ● ●

● Standard features ○ Optional features — Not availableType designation SC 500CP-10 SC 630CP-10

DS_Master_092810.indd 23DS_Master_092810.indd 23 9/28/10 2:34 PM9/28/10 2:34 PM

Page 6: Inverter Specifications

SMA central inverters in the new Sunny Central MV stations fulfill the following specifications typically required with utility-scale applications:

SMART GRID MANAGMENT INCLUDED

Grid support through reactive powerIn order to keep the grid voltage constant, Sunny Central HE inverters supply leading or lag-ging reactive power to the grid. For this, there are three options:

a) Fixed presetting of the reactive power by the grid operatorThe grid operator presets a fixed reactive power value or a fixed phase shift between cos(ϕ)leading= 0.9 and cos(ϕ)lagging= 0.9.

b) Dynamic presetting of the reactive power by the grid operatorThe grid operator presets a dynamic phase shift - any value between cos(ϕ)leading= 0.9 and cos(ϕ)clagging= 0.9. It is transmitted either through a communication unit or via a standardized current signal (I=4...20 mA) in accordance with DIN IEC.

c) Control of the reactive power through a characteristic curveEither the reactive power or the phase shift is controlled by a pre-defined characteristic curve - depending on the fed-in active power or grid voltage.

Frequency-dependent control of active powerStarting at a defined grid frequency, the inverter will automatically reduce the fed-in active power along a preset characteristic curve and thereby contribute to the stabilization of the grid frequency.

Power limitation peak shaving / grid safety managementIn order to avoid short-term grid overload, the grid operator presets a nominal active power value which the inverter will implement within 60 seconds. The nominal value is transmitted to the inverters via a ripple control receiver in combination with the SMA Power Reducer Box. Typical limit values are 100, 60, 30, or 0 percent of the nominal power.

Monitored dynamic grid support LVRT (Low Voltage Ride Through)Until now, PV systems have had to disconnect from the grid immediately even during short grid voltage losses. The result is that, if there are grid disturbances, basically all feed-in systems shut down in cascades and further increase the imbalance of the grid. Using the monitored dyna-mic grid support, the new Sunny Central HE devices can feed in immediately after short-term voltage losses—as long as the nominal voltage exceeds fixed values. (Optional)

SMA America, LLCToll Free +1 888 4 SMA USAwww.SMA-America.com

SCCP

ALL-D

US10

3911

SM

A and

Sunn

y Cen

tral a

re reg

istered

trade

marks

of SM

A Sola

r Tec

hnolo

gy AG

. Tex

t and

illustra

tions

confo

rm to

tech

nical

stand

ards o

n prin

ting. T

echn

ical m

odific

ation

s rese

rved.

No lia

bility

for pr

inting

error

s. Prin

ted on

chlor

ine-fre

e pap

er.

DS_Master_092810.indd 24DS_Master_092810.indd 24 9/28/10 2:34 PM9/28/10 2:34 PM


Recommended