Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public. इंटरनेट मानक !ान $ एक न’ भारत का +नम-णSatyanarayan Gangaram Pitroda “Invent a New India Using Knowledge” प0रा1 को छोड न’ 5 तरफJawaharlal Nehru “Step Out From the Old to the New” जान1 का अ+धकार, जी1 का अ+धकारMazdoor Kisan Shakti Sangathan “The Right to Information, The Right to Live” !ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह Bharthari—Nītiśatakam “Knowledge is such a treasure which cannot be stolen” IS 10658 (1999): Specification for Higher Capacity Dry Powder Fire Extinguisher (Trolley Mounted) [CED 22: Fire Fighting]
Transcript
Page 1: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

Disclosure to Promote the Right To Information

Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public.

इंटरनेट मानक

“!ान $ एक न' भारत का +नम-ण”Satyanarayan Gangaram Pitroda

“Invent a New India Using Knowledge”

“प0रा1 को छोड न' 5 तरफ”Jawaharlal Nehru

“Step Out From the Old to the New”

“जान1 का अ+धकार, जी1 का अ+धकार”Mazdoor Kisan Shakti Sangathan

“The Right to Information, The Right to Live”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता है”Bhartṛhari—Nītiśatakam

“Knowledge is such a treasure which cannot be stolen”

“Invent a New India Using Knowledge”

है”ह”ह

IS 10658 (1999): Specification for Higher Capacity DryPowder Fire Extinguisher (Trolley Mounted) [CED 22: FireFighting]

Page 2: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page
Page 3: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page
Page 4: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

IS 10658 : 1999Reaffirmed 2010

Indian Standard

SPECIFICATION FOR HIGHER CAPACITY DRYPOWDER FIRE EXTINGUISHER

(TROLLEY MOUNTED)

( First Revision)

ICS 13.220.10

1999

BUREAU OF INDIAN STANDARDSMANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG

NEW DELHI 110002

December 1999

© BIS

Price Group 4

Page 5: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

AMENDMENT NO.1 MARCH 2002TO

IS 10658: 1999 SPECIFICATION FOR HIGHERCAPACITY DRY POWDER FIRE EXTINGUISHER

( TROLLEY MOUNTED)( FirstRevision)

( Foreword) - Insert the following before the last para:

'A scheme for labelling environment friendly products known as ECO Mark hasbeen introduced at the instance of the Ministry of Environment and Forests(MEF), Government of India. The ECO Mark would be administered by theBureau of Indian Standards (BIS) under the SIS Act, 1986 as per the ResolutionNo. 71 dated 21 February 1991 and No. 42S dated 28 October 1992 published inthe Gazette of the Government of India. For a product to be eligible for markingwith ECO logo, it shall also carry the lSI Mark of BIS besides meeting additionaloptional environment friendly requirements. For this purpose, the StandardMark of BIS would be single mark being a combination of the lSI Mark and theECO logo. Requirements to be satisfied for a product to qualify for the BISStandard Mark for BCO friendliness being included in the relevant publishedstandards through an amendment. These requirements are optional;manufactwing units are free to opt for the lSI Mark alone also.

The amendment is based on the Gazette Notification No. 160 dated 1 April 1999for Fire Extinguishers as environment friendly products published in the Gazetteof the Government of India.'

( Page 4, clause 10 ) - Insert the following new clauses after 10 andrenumber the subsequent clauses:

'11 OPTIONAL REQUIREMENTS FOR ECO MARK

11.1 General Requirements

11.1.1 Any fire extinguisher having BIS Standard Mark qualifies forconsideration ofECO Mark.

11..1.2 The products manufacturer must produce the consent clearance as perprovision of the Water (Prevention &: Control of Pollution) Act, 1974, Water(Prevention &: Control of Pollution) Cess Act, 1977 and Air (Prevention &:

Page 6: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

Amend No.1 to IS 10658 : 1999

ControlofPollution) Act, 1981 respectively, alongwith authorization if requiredunder Environment (Protection) Act, 1986,and the Rulesmade thereunder to theBureau of Indian Standards while applying for EeO Mark.

11.1.3 The products may display in brief thecriteria based on which the producthasbeenawarded BeO Mark.

11.1.4 The product may carry along with instructions for proper use so as tomaximize product performance with statutory warning, if any, minimize wasteand method of safe disposal.

11.1.5 The material used for product packaging ( excluding refills) shall berecyclable, reusable or biodegradable.

11.1.6 The product must display a list of critical ingredients in descendinsorderof quantity present in percent by weight The list of such critical ingredientsshall be identified by the Bureau of Indian Standards.

11.2 Spedftc Requirements

11.2.1 The fire extinguisher shall not contain any Ozone Depleting Substance(ODS) relevant to fire extinguishers industry as identified under the MontrealProtocol (Annex D).

11.2.2 Oas based extinguishing media once discharged in the atmosphere shouldnot have atmospheric life time of more than a year (Annex E).

11.2.3 Chemical used should not have global wanning potential (Annex F).

11.2.4 The metallic body and other meta) parts of the rue extinguishers shall befreeof lead or lead alloys.

11.2.5 The coating used for the metallic part shall not be fonnulated withmercury and mercury compounds or be tinted with pigments of lead, cadmium,chromium VI and their oxides. Excluded are natural impwitics entailed by theproduction process up to the amount 0.1 percent by weight whicti are containedin the raw material.

NOTE - ~ extiDpishcrs may bepennitted till suitable substitutes are available.

2

Page 7: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

Amend No. I to IS 10658 : 1999

ANNEX 0( Clause11.2.1 )

LIST OF OZONE DEPLETING SUBSTANCES (ODS) CONTROLLEDBY MONTREAL PROTOCOL

TradeName

Halon 1211Halon 1301Halon 2402CFC-llCFC-12CFC-113CFC-114CFC-llSCCLtC2H3C13CFC-13CFC-lllCFC-112CFC..211CFC..212CFC-213CFC-214CFC-215CFC..216CFC-217Methyl Bromide

ODP

3.010.06.01.0

1.00.81.00.61.10.11.01.01.01.01.01.01.01.01.01.00.6

Nom- ODP valuesarerelative to CFC-II whichhas been assignedarbitraIyvalueof 1.0.

3

Page 8: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

Amend No.1 to IS 10658 : 1999

ANNEX E( ClalU~ 11.2.2 )

LIST OF ATMOSPHERIC LIFE TIME OF GAS-BASED AGENTS

Trade Name Designanon AtmosphericLife Time (Year)

Halon-1300 1 (CF 31) <1 dayNAPS III HCFC (Blend A) 12FE 25 HCFC-125 36FE 241 FCFC-I24 6FE 36 HFC-227 fa 2S0FE 13 HFC-23 250FM200 HFC-227EA 41CEA410 FC-3-1-10 2600Halon 1301 Halon 1301 65Inergen 10541Argonlte 1055Argon 1001

ANNEX F( Clause 13.2.3 )

LIST OF SUBSTANCE SHAVING GLOBALWARMING POTENTIAL (GWP)

Trade Name GWP(}OOyear)VsC02

Halon 1301InergenArgoniteArgonCEA410FM200FE 13FE 36FE 241FE2SNAFS IIICF31

(CEO 22)

4

5600

55003300

121008000

48032001450

<5

RcprographyUmt,BIS.NewDeihl, India

Page 9: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

AMENDMENT NO.2 SEPTEMBER 2002TO .

IS 10658: 1999 SPECIFICATION FOR HIGHERCAPACITY DRY POWDER FIRE EXTINGUISHER

( TROLLEY MOUNTED)

( First Revision)

( Page 2, clause 6.6, lines 3 and 4 ) - Delete the words 'and 8 m in case of100kg'.

( Page 2, clause 6.8) - Substitute the following for the existing:

".8 Copper Tubing or High Pressure Hose - Copper tubing shall conformto bursting pressure of 275 kgf/cm2 or wire braided high pressure hose as perIS 14933:2001.'

[ Page 2, Table 1, Sl No. (i), col 4 ] - Insert 'or IS 2002'.

[ Page 2, Table 1, Sl No. (viii), col 3 ] - Delete the word •Seamless, .

( Page 4, clause 9.1, line 4) - Delete 'in still weather condition' and addthe following new sentence:

'prior to performance test, sample shall be conditioned for 2 h and test shall becarried out in still weather condition where air flow is 3 kmlh maximum.'

( Page 4, clause 10, line 5 ) - Delete the words 'and 100 kg'.

[ Page 4, clause 11.I(a), renumbered 12.1(a) ] - Substitute the followingfor the existing:

'a) Manufacturer's name or trade-mark, serial number and year of manufactureshall be embossed at the bottom ring. •

(CED22 )

Reprography Unit. 81S, New Deltu,lndia

Page 10: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

AMENDMENT No. 3 SEPTEMBER 2003TO

IS 10658: 1999 SPECIFICATION FOR HIGHERCAPACITY DRY POWDER FIRE EXTINGUISHER

( TROLLEY MOUNTED)( First Revision)

(Page ~t clause 6.3, line 1 ) - Substitute '(not more than 20 kgf/cm2)' for'(25 kgf/cm )'.

(CED22)

ReprographyUnit.8rS. New Delhi. India

Page 11: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

AMENDMENT NO. 4 APRIL 200STO

IS 10658: 1999 SPECIFICATION FOR HIGHERCAPACITY DRY POWDER FIRE EXTINGUISHER

(TROLLEY MOUNTED)( Fint R.,,,lo,, )

(Page 1, clauses 6.1and 6.2) - Substitute the following for the existing:

66.1 The cylinder shall be of welded construction having cold or hot drawncylindrical portion with hemispherical elliproidal or torispherical endswelded toit or two halves (upper half shorter) cold or hot drawn having dome and bottomdish of hemispherical or ellipsoidal or torispherical and circumferentially weldedtogether. A cylindrical skirt having minimum 2S mm height shall be welded tothe bottom dish.

6.1.1 Where carrying handle and/or supporting fittings an: fitted to the body.these shall be either welded or brazed. The carrying handle shall be made ofmild steel or stainless steel rod J10l less than 6 mm in diameter or fabricated outof mild steel or stainless steel sheets of same thickness as thebody and the clampshall be of mild steel or stainless steel thickness of 2 mm, minimum.

6.2 Body

The material used in the construction of extinguisher bodies shall be weldable.The filler materials shall be compatible to the body steel to given good welds. Acylindrical ring shall be fitted/welded to the bottom dish. Minimum wallthickness of the body shall be calculated using the formula:

c) For carbon steel bodies,

Dt =-- + 0.7

300

b) For austenitic stainless steel bodies,

Dt =-- + 0.3

600

Page 12: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

Amend No. 4 to IS 10658 : 1999

where

t =minimum thickness. in mm; and

D = externaldiameter of the body.in mm.

( Page 3, clause 7.1 ) - Substitute the following for the existing:

'7.1 All internal and external surfaces of the body shall be completely epoxypowder coated to minimum 0.050 mm thickness. The thickness of the coatingshall be measured as given in IS 3203. The internalsurfaceof the body shall beplastic/rubber coatedandlining shall be of a minimum thickness of 0.5 mmas analternative to powder coating.

7.1.1 Test for Adh~sion of Plastic fning (Type Test) - Subject the unfilledextinguisher to a pressure15kgf/em and store for 120+ 4 h at 27 ±SoC.

-0

Release the pressure and examine the extinguisher internally for erackin&,separation from the wall of the bodyor lifting of the lining, and bubbles betweenthe lining and the body. '

(Page 3, clause 7.2) - Delete 'to zinc or lead-tin alloy coating'.

( Page 3, clause 7.3 ) - Delete.

( Page 3. clause 8.1 ) - Insert 'or Post Office Red' after 'fire red' and 'orNo. 538' after 'No. 536'.

(CED22 )Reprography Unit.BIS.New Delhi.India

2

Page 13: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

AMENDMENT NO. 5 MAY 2006TO

IS 10658: 1999 SPECIFICATION FOR HIGHERCAPACITY DRY POWDER FIRE EXTINGUISHER

(TROLLEY MOUNTED)

( Tint Revision)

[Page I, clause 6.1.1 (see also Amendment No.4) ] - Substitute '20 rom'for '6 nun' andinsert 'tube'afta' 'mild &ted' in line3.

(CED22 )

Reprography Unit, BIS, New Delhi, India

Page 14: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

AMENDMENT NO.6 SEPTEMBER 2006TO

IS 10658: 1999 SPECIFICATION FOR HIGHERCAPACITY DRY POWDER FIRE EXTINGUISHER

(TROLLEY MOUNTED)

( Flnt Revision)

[Page 4, clause 11 (see also Amendment No. I)] - Substitute'ADDITIONAL' for 'OPTIONAL'.

(CEO 22 )ReprographyUnit, BIS, New Deihl, Ind.1

Page 15: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

AMENDMENT NO.7 JANUARY 2009TO

IS 10658 : 1999 SPECIFICATION FOR HIGHERCAPACITY DRY POWDER FIRE EXTINGUISHER

(TROLLEY MOUNTED)

( First Revision)

[Page I, clause 6.2 (see a/so Amendment No.4)] - Substitute thefollowing for the existing:

'6.2 Body - The wall thickness of the body shall be not less than the wallthickness given by the formula below:

DxPTS = --- for the wall thickness ofthe body

20 x R

where

S = wall thickness, in millimetres;

D = external diameter of the body, in millimetres;

PT == test pressure, being 1.43 )( PS, in MPa;

R = 80 percent of the minimum yield strength of the materialspecified by the manufacturer, in N/mm2

•'

(CED 22)

Reprography Unit, BIS. New Deihl. India

Page 16: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

FireFightingSectionalCommittee, CEO22

FOREWORD

This IndianStandard(FirstRevision)wasadoptedbythe Bureauof Indian Standards,afterthedraftfmalizedbythe FireFightingSectionalCommittee had beenapprovedby the Civil Engineering DivisionCouncil.

Dry powder flre extinguishers (trolley mounted)are largerversion of theportabledrypowderfireextinguishersand likethe latter they maybeusedfordealingwithclassA, 8 and C fires which may be beyondthe capacityof the portable fire extinguishers but which can still be controlled without the aid of fife engines/crashtenders. In principle,the operation of such fire extinguishers and portable fire extinguishers are similar; butbecauseoflarger capacity,bulkandmass of the former, thesehaveto bemountedon a wheeled carnage trolleyand the design of the fittingshave to be modifiedto suit the mode of operationand their capacity. The detailsin regard to the maintenanceare given in IS2190 : 1992'Selection installationand maintenanceof'first-aidflreextinguishers-Code of practice (second revision)'.

The extinguisher and component shall be designed taking into account the working pressure required toachieve satisfactoryperformanceunderminimumambienttemperatureof 35°Canddesignpressurewhichshallbe maximumpressureachievedat 600C ambienttemperatureor maximumpressurelikelyto be developedin thesystem with stoppage of powder flow due to obstructionwhicheveris more.

This standard has been prepared with a view to guide the industries for the manufacturer and the users inobtaining the extinguisher capable of giving satisfactory performance. This standard was first publishedin 1983. The principal modificationsmade in this revisionare inrespectof (a) materials specifiedfor differentcomponentsgivenin tabularformand for somecomponents additional materials havebeen specified,(b) newclauses for actuating mechanism,bore size of syphon tube, epoxy polyesterpowder coating, and (c) updatingthe various clauses based on the use of this type of extinguisher. The amendment issued has also beenincorporatedin the revised version.

The Composition of the technical committee responsible for the formulation of this standard is given atAnnexC.

For the purposeof decidingwhethera particularrequirement of this standard is compliedwith, the fmal value,observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance withIS 2:1960'Rules forrounding offnumerical values(revised)'. Thenumberof significant placesretained intherounded otTvalue should be the same as that of the specified value in this standard.

Page 17: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

IS 10658 : 1999

Indian Standard

SPECIFICATION FOR HIGHERCAPACITY DRYPOWDERFIRE EXTINGUISHER

(TROLLEY MOUNTED)

( First Revision)

Dry PowderContent,kg, Tolerance + 5 Percent

2S

so75

I SCOPE

1.1 Thisstandard laysdownthe requirementregardingmaterial,shape, construction,chemicalcharges, anti­corrosivetreatment and tests for trolley mounteddrypowder fll'eextinguishers of capacities25 kg, 50 kgand7Skg.

2 REFERENCES

2.1 The Indian Standards listed in Annex A containprovisions which, through references in the text,constituteprovisions of this standard.At the time ofpublication, the editions indicated were valid. Allstandards are subject to revision, and parties toagreements based on this standardare encouragedtoinvestigatethe possibilityof applyingthe most recenteditionsof the standards given at Annex A.

3CAPACI1Y

3.1 ·Thetotal capacityof thedry powder extinguisherwhenfilledforthe variouscapacitiesshallbeasunder:

Nominal Size,kg

2S

~

7S

4 PRINCIPLE

4.1 Themethodofexpulsionof dry powdershanbebymeans of pressure produced from compressed orliquitied gas from gas cylinderattachedto the bodyand suitably mounted on trolley or gas cartridgeattached to the cap.

S MATERIALS

5.1 Thematerial for constructionof various parts ofthe extinguishershallbeasgiven inTable 1.

6 CONSTRUCI1ON

6.1 Body

The construction of the body shall be weldedconforming to therequirements givenin IS9595. The

shapeofthebody shall becylindricalhavingdiameternot more than 75 em, The domed ends of the bodyshall be without reverse of curvature and shall bedished outwardsto a radiusnot exceedingthe internaldiameter of the body to which these are fixed. Theminimumthickness of the body shall be calculated asunderwithanextraallowanceof0.5mm forcorrosion:

pxDot =

200f.j+p

where

p = design pressure in kgflcmZ,

Do ::: outsidediameterinmm,

f allowablestressvalue inkgflnunz, and

j weld joint factor = 0.70 for noradiographywith double welded buttjoints, 0.65 for no radiography withsingle welded butt joint with backingstrip; 0.85 for spot radiography withdoubleweldedbuttjoints and0.80 forspot radiography with single weldedbuttjoints with backingstrip.

6.1 Neck Ring

The neckringshallprovidea clearopeningof not lessthan 75 nun. It shall have parallel screw threads foreffectivelength of not lessthan 22nun. The neckringshall be firmly secured to the body by brazing orwelding.

6.3 Cap

Thecapshallbe threadedfor fixingto the neckring inthebodyfor not lessthan22mmeffectivelength. Theparallel threads shall be in accordancewith IS 2643(Part 1).At least3 holes ofnot less than3 mmdiametereach shall be drilled through the threads of the capto fonn ventsforrelease of any pressure remaininginthe bodyduringwithdrawalof thecap. The centresoftheventholesshallbe 6.5mmmaximum fromthe faceof thecap jointwasher. Theextinguishershallbefittedwith safety valve which shall releaseat a pressure of

Page 18: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

IS 10658: 1999

2.5 MN/m2 (25 kgf/cm 2) as per requirement ofIS 5903.

6.4 CapJolntWasber

The capjoint washershaU beprovidedintherecessinthe cap asshown in Fig. I.

6.5 Expansion Space

A space shall be providedabove dry powderlevel inthe body of the extinguisher. It shall be of sufficientvolume to ensure that when discharge nozzle istemporarilyclosedand the extinguisher isoperatedata temperatureof 27 ± 5°C, the internalpressureshallnotexceed1.5MN/m2 (I Skgf/cm2

) and thebodyshallnot show any sign of leakage.

NOTE - For testing this requirement the adapter with

pressure gauge be titted in place of cap.

6.6 Discharge Hose

Discharge hose shall be of braidedrubber or PVCofnominal bore 19mm diameterfittedwithnot lessthan3 m incaseof2S kg;'Sm incaseof SO kgand7Skg,and

8 m in caseof 100 kg lengthof hose. Thehoseshallhaveburstingpressureof not less thanSO kgflcm2

6.7 Cylinder

The CO2

gascylindershall conform to IS 7285 andshall be ofcapacity I.Slitresfor25kgsizeand3 litresfor SO and7S kg size and shall be filled with carbondioxide (seeIS307) havingmaximum filling ratioof0.667 which is the ratio of mass of carbon dioxidechargedintheCOJ1tainer to the- mass of waterrequiredto fill thecontainerat 27°C.

6.8 CopperTubing(RequiredIfGasCylinder is Used)

It shallconformto burstingpressureof275 kgf/cm2•

6.9 Nozzle and Other Discharge Fittings

The nozzle shall be trigger controlled and shall becapable ofdischargingdry powderas in 9.1, and shallbeso designedas to eximinatemoisturepenetration.

6.10 Actuation Mechanism

The CO2 cylindershallhavewheelvalveas shown inFig. I to operateand dischargegas.

Table 1 Materials for Construction of Various Parts of Fin Extinguisher

(Clause 5.1)

RtlevaDt IDdlaDStaDdard

(4)

Grade 2 of IS 291 orType I of IS 319Grade LTB2 of IS 318IS 7328Grade 44S0 of IS 617

GradeLTB2 of IS 318Type I of IS 319

IS 1079 orIS 2041 orIS 2062

Grade LT82 ofIS 318IS 1239 (Part 1)IS 6912

seamless mild steel tube

Material

(3)

Mild steel sheets

i) Leaded tin bronze

ii) Seamless mild steel tubeiii) Copper

i) Brass

ii) Leaded tin bronzeiii) Plasticiv) Aluminium alloy

i) Leadedtin bronzeii) Brass

i) Leaded tin bronzeii) Brass

Rubber

GradeLTB2 of IS 318Type I of IS 319

Conforming to requirement ofhardness as applicable to Type 3ofiS 5382 and also acictand alkaliresistant (8ee Note)

IS 3224

IS 1239 (Part I)IS 3601

NOTE-When a piece of 25 mm cut from any portion is dipped in 20 percent sulphuric acidlS percent sodium hydroxidesolution for 30 min, there shall be no siln of corrosion/damage.

v) Drain plug

vi) Washer

ii) Neck ring

iv) Cap

iii) Nozzle

vii) Discharge valve

SI CompODtDtNo.

(I) (2)

i) Body

viii) Syphon tube

2

Page 19: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

IS 10658: 1999

SAP_TYVA LVI!WITHCA~

BODY

O'SCH "ROE VALVa

C Oz CVLlNDeR

M 8 TUBE. 2.......FITTED IN STANDARD

BEARING

WHeeL WrJH SOLID RU881!RTYRE ... zoo·. 10 .,,,.. FOR 21 &50 kg AND'" 100.7' """ prOR70 kg

NOTESI For 25 kg capacity gas cartridge outside or inside may be used.2 For 25 kg capacity drain plug is not necessary.

FIG. 1 TYPICAL DETAILS OF DRY POWDER FIRE EXTINGUISHER (TROLLEY MOUNTED)

6.11 Drain Plug

The drain plug ofnot less than 25 mm diameter shall beprovided on the body except in case of25 kg capacityand the washer shall be provided to make the jointwatertight.

6.12 The dry powder used in the extinguisher shallconformto IS 4308 or IS 14609.

6.13 The bore of syphon tube shall not be less than19mm.

6.14 Provision shall be made for an internal pressuretest on the body. For this purpose, the union towhich the discharge hose is connected shall bescrewed with threads which shall be in accordance withG 1/2 or G 3/4 ofIS 2643 (Part I) so that a test pipe maybe connected at this point.

7 ANTI-CORROSIVETREATMENT

7.1 All internal and external surfaces of the body andinternal parts shall be completely coated with zinc orlead-tin alloy (tin 10 percent minimum) applied byhot-dipping or electrolytic process to a thickness of

3

not less than 0.025 mm. The thickness ofthe coatingshall be measured as given in IS 3203. There shall beno visible uncoated area both internally and externally.

7.2 Phosphating (see IS 36 I 8) may be applied on theexternal surface ofthe body as an alternative to zinc orlead-tin alloy coating.

7.3 Epoxy polyester powder coating of 50 micronthickness may beapplied on both surfaces ofthe bodyas an alternative to lead-tin alloy coating.

8 PAINTING

8.1 Each extinguisher shall be painted fire redconforming to shade No. 536 of IS 5. All componentsoftrolley andother items other than the fire extinguishershall be painted with the primer and finishing paintsof two coats each. The paint shall conform toIS 2932.

9 TFSTREQUIREMENfS

9.1 PerformaDceTest

The extinguisher shall be capable of dischargingminimum of 85 percent by mass of the actual rated

Page 20: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

IS 10658: 1999

capacity of dry powder when the extinguisher isoperated at a temperature of27 ± SoC in still weathercondition. The contents shall be expelled in the formofa continuous discharge which shall comply with thefollowing requirements:

Capacity of Duration Range ofJet ThrowExttngutsher S (Minimum Throw)

kg m

25 2St030 6

50 40 to 50 8

75 50 to 60 10

9.2 Hydraulic Test

The extinguisher shall be tested to an internal hydraulicpressure of3.0 MN/m2 (30 kgf/cm'). The test pressureshall be held for a minimum period of two and a halfminutes. During the test, it shall not show any sign ofleakage.

9.3 Bunting Test

In case ofhydraulic burst test, failure shall not occurat a pressure of less than 4.5 MN/m 2 (45 kgf/cm").

10 WHEELED CARRIAGE

The fire extinguisher shall be provided with wheeledcarriage according to details given in Fig. 1. The fittingshall ensure that the lowest part of the body remainsnot lessthan 10em for 25 kg and 20 em for 50 kg, 75 kgand 100 kg above the ground when it is in the verticalposition.

11 MARKING

11.1 Each extinguisher shallbeclearlyand permanentlymarked with the following information:

a) Name of the manufacturer or trade-mark, ifany;

b) Method ofoperation in prominent letter;

c) Words 'Dry Powder Extinguisher';

d) Capacity ofthe extinguisher in kg;

e) Words'Recharge After Use';

f) A declaration to the effect that the body ofthe extinguisher has been tested to a pressureof3.0 MN/m2 (30 kgflcm2

) ;

g) Letters indicating the various classes of firesfor which the extinguisher is suitable;

h) Year ofmanufacture;

J) Working and design pressure;

k) Capacity of gas cartridge; and

m) Capacity ofgas cylinder with filling ratio.

11.2 DIS Certification Marking

The product may also be marked with the StandardMark.

11.2.1 The use of the Standard Mark is governed bythe provisions ofBureau ofIndian Standards Act, 1986and the Rules and Regulations made thereunder. Thedetails ofconditions under which the licence for theuse ofStandard Mark may begranted to manufacturersor producers may be obtained from the Bureau ofIndian Standards.

12 SAMPLING AND CRITERIA FORCONFORMITY

The details ofsampling and criteria for conformity aregiven in Annex B.

ANNEX A

(Clause 2.1)

LISf OF REFERRED INDIAN STANDARDS

IS No. Title IS No. Title

S: 1994 Colours for ready mixed paints and 617: 1994 Aluminium and aluminium alloyenamels (fOk, th revision) ingots and castings for general engi-

291: 1989 Naval brass rods and sections for neering purposes (third revision)

machining purposes (third revision) 1079: 1994 Hot rolled carbon steel sheets and307: 1966 Carbon dioxide (secondrevision) strips (fifth revision)

318: 1981 Leaded tin bronze ingots and castings 1239 Mild steel tubes, tubulars and other(second revision) (Part I): 1990 wrought steel fittings: Part 1 Mild

319: 1989 Free cutting brass bars, rods andsteel tubes (fifth revision)

sections (fourth revision) 2041: 1995 Steel plates for pressure vessels used

4

Page 21: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

IS No.

2062: 1992

~190: 1992

2643 (Part 1):1975

2932: 1993

3203: 1982

3224: 1979

3601: 1984

Title

at moderate and low temperature(second revisiony

Steel for general structural purposes(fourth revision)

Selection, installation and main­tenance of first-aid fire extinguishers

- Code of practice (second revisions

Dimensions for pipe threads forfastening purposes: Part 1 Basicprofile and dimensions (first revision)

Enamel, synthetic, exterior (a)undercoating, (b) finishing (secondrevision)

Methods oftesting local thickness ofelectroplated coatings (first revision)

Valve fittings for compressed gascylinders excluding liquefied petro­leum gas (LPG) cylinders (secondrevision)

Steel tubes for mechanical andgeneral engineering purposes (firstrevision)

IS No.

3618: 1966

4308: 1982

5382: 1985

5903: 1970

6912: 1985

7285: 1988

7328: 1992

9595: 1996

14609: 1999

IS 10658 : 1999

Title

Phosphate treatment of iron and steelfor protection against corrosion

Specification for dry powder for firefighting (first revision)

Rubber sealing rings for gas mains,water mains and sewers (first revisiom

Recommendations for safety devicesfor gas cylinders

Copper and copper alloy forgingstock and forgings (first revision)

Seamless steel cylinders for penna­nent and high pressure liquefiablegases (second revision)

High density polyethylene materialsfor moulding and extrusion (firstrevision)

Metal-arc welding of carbon andcarbon manganese steels-Recom­mendations (first revision)

Dry chemical powder for fire fightingA, B, C class fires - Specification

ANNEX B

(Clause 12)

SAMPLINGANDCRITERIA FORCONFORMITY

B-OGENERAL

B-O.I The risk involved in failure ofa fire extinguisherto work when needed is extremely large. Fire extin­guishers, therefore, ought to have a high degree ofreliability of performance during the entire period ofits service. It can be achieved only through adequatedesign and control at all stages of manufacture andassembly.

B-1 SAMPLING

8-1.1 Lot

All fire extinguishers of the same type, shape, designand capacity, produced by the same manufacturer fromsimilar materials under almost identical conditions ofmanufacture shall be grouped together to constitute a lot.

8-1.2 Each lot shall be considered individually for thepurpose of evaluation of quality in accordance withthis specification.

5

8-1.2.1 The number of samples for testing to betakenat random from a lot and the criteria for conformityshall be as given in 8-1.2.2 and 8-1.2.3.

8-1.2.2 From each lot a number ofsamples as indicatedin col 2 of Table 2 shall be selected at random.

8-1.2.3 They shall be examined visually, as far aspossible, in respect of requirements specified in 3, 5to 8, 11 and then in respect ofhydraulic pressure test(see 9).

8-1.2.3.1 All the samples tested shall pass thesetests for the lot to be declared to conform to theserequirements.

8-1.2.4 In respect ofperformance test (see 9.1), onesample shall be tested for this property. and the sampleshall pass this test for the lot to be declared to conformto this requirement.

8-1.2.5 In respect ofbursting pressure (see 9.3), one

Page 22: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

IS 10658: 1999

type test shall be done and these should conform tothe requirementslaiddown in the specification.

B-l.2.~ In the absence of a certificate from amanufacturerabout conformity of specifications forthe various components (see 5) and the charge(see 6.12) froma samplefire extinguisher, such itemsshallbe takenseparatelyandexaminedindividually inrespect of the relevantrequirements laid down in thespecification. The lot shall be consideredsatisfactoryif all the itemssatisfytherelevantrequirements of thisspecification.

SINo.

(I)

r)

II)

III)

IV)

Table2 For LotsProduced Under QualityControl System

(Clause a-I.2.2)

No. of Items Simplein the Lot Size

(2) (3)

Up to 25 J

26 to 50 5

5 I to 100 8

101 to 200 8 percent

Chalr",all

Me",be"

SHRJ D K SHAMI

DR NAVINrHANDRA JAIN

SHRI P N SEmNA

SHIU N T PANJAWANI (A/temate)

SHRJ StIv NAlH

SHIU P GANESHAN (A/temate)

S... P K CHATJEJUEESHRI H S KAPAIlWAN(Altemate)

ANNEX C

(Foreword)

COMMrrTEECOMPOSmON

FireFighting Sectional Committee, CEO22

Representing

Ministry of Home Affairs, New Deihl

Ministry of Home Affairs. New Deihl

Government ot Maharashtra, Mumbai

Kooverji Devvlu & lo (P) ltd. Murnbai

Steelage Industnes Ltd, Chennai/Delhi

Mmrstry of Defence. Deihl

SHRI K P SHARMAAssn SErumY CoMMIssIONEll (FIRE)(Alternate)

SHaI M GANGARAJUSHRI V 1'..VERMA (Altemate)

SHIU S I'. DHaISHRI S K SHARMA (A/temale)

SHRIV L N RAoLT-eOL S I'. MAIlKENDEY (A/temate)

SHRI P A DuBn

SHIllJ N VAKD..

SHIU K RAVI (A/.,.,.,.)

6

Railway Board. Deihl

Directorate General of Supplies &. Disposals. Pune

Deihl Fire Service, Deihl

Controllerate ot Quality Assurance, Pune

Design and Consultancy, CME Campus, Pune

Enganeer-an-ehlefs Branch. New Deihl

Defence Research and Development Orgenization, Delhi

Tmft" Advisory Committee, Ahmadabad

Home Department (Fire Service). Chennli

(Contmued on page 7)

Page 23: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

(Contmuedfrom page 6)

Member!

OR. T P SHARMA

DR A K GuPrA (Altemate)

MANA<JNo DIRBcroRTECHNICALEXECl1I1VE(Altemale)

SHRI R.C SHARMASHRJ S L NAGARKAR (Alternate)

PR!soJfNrOI!NERAL SECRETARY (A/lemate)

SHRI S N KUNDUSHIUP KHANNA

DIREcroROFEQuIrMENrSENIOR FIRE OFFICER (Alternate)

SHRIC P 00sAIN

SHRIP N GHOSH

SHRIB J SHAHSHIU A M SHAH (Allernate)

StnuV V RAoSHlUV G SAwANT(Altemate)

SHRI T YOOI!SWAIlA

~HR1 JOHN TAKEY(Alternate)

SHRISURl!SHBABUSHJU D N SINGH (Alternate)

SHIU R P SAXENASHRJ NEERAJSH.UMA (Alternale)

SHRJ SWARANJITSEN0EPuTv DIRECTOR.(.4Itemate)

SHRJ T.wr SURSHRI 0 NEOOI (Alternate)

SHRI HAIusHS.wn

SH1u RAMEsnR.OHoBLEV

SHIllS M DesAI

SHRI G B MENoN

SfIuAsHoK SHARMASHRI A K NANDI (A/temate)

SHRI P N PANCHAL

SHa1 VINODKUMAIl,Director (Civ Enlg)

IS 10658 : 1999

Repre"nttng

Central Buddmg Research Institute (CSIR), Roorkee

West Bengal Fire Service, Calcutta

Avon Services Pvt Ltd, Mumbal

Central Industnal Secunty Force,New Deihl

The Institution of Fire Engmeers(India), Deihl

Fare and Safety Appliances Co, CalcuttaJaya Shn Textiles, Deihl

National Airport Authonty, New Deihl

Central Public Works Deptt New Deihl

In personal capacity (J-1916 Chtttaranjan Park New Delh,)

Newage Industries, GUJarat

Bombay Fire Bngade, Mumbal

Steel AuthOrity of India Ltd, Rourke1a

Steel Authority of India Ltd, Dhanbad

ad and Natural Gas Commission, Dehradun

Home (Police Department) Government of Andhra Pradesh,Hyderabad

Surex Production and Sales Pvt Ltd, Calcutta

VIJay Fire Protection Systems Pvt Ltd, Mumbal

Bhabha Atomic Research Centre, Mumbal

Eureka Firetech Pvt Ltd, Mumbar

In personal capacity (16 Am,k.et Society ManJal PurG J D C Road. Vadodara)

Mather and Platt (India) Ltd, Mumbai

Loss, Prevention ASSOClalion of India, Mumbal

In personal capacity (Flat No 46 Block E-l Pocket JJSector IS Roh,m Delh,)

Director General, BIS (Ex-offiCIO Member)

Member-SeerelDrySHuSANDVCHA1UM.DI

Joant Director (CIV Engg), DIS

7

Page 24: IS 10658 (1999): Specification for Higher Capacity Dry ... · IS 10658: 1999 SPECIFICATIONFOR HIGHER CAPACITY DRY POWDERFIREEXTINGUISHER ( TROLLEY MOUNTED) ( First Revision) ( Page

Bureau of Indian Standards

DIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to 'promoteharmonious development of the activities of standardization, marking and quality certification of goodsand attending to connected matters in the country.

Copyright

DIS has the copyright of all its publications. No part of these publications may be reproduced in any formwithout the prior permission in writing of BIS. This does not preclude the free use, in the course ofimplementing the standard, of necessary details, such as symbols and sizes, type or grade designations.Enquiries relating to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are alsoreviewed periodically; a standard along with amendments is reaffirmed when such review indicates thatno changes are needed; if the review indicates that changes are needed, it is taken up for revision. Usersof Indian Standards should ascertain that they are in possession of the latest amendments or edition byreferring to the latest issue of 'BIS Handbook' and 'Standards: Monthly Additions'.

This Indian Standard has been developed from Doc: No. CED 22 (5810).

Amendments Issued Since Publication

Amend No. Date of Issue Text Affected

BUREAU OF INDIAN STANDARDS

Headquarters:

Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110 002 'Telephones: 323 01 31, 323 33 75, 323 94 02

Telegrams : Manaksanstha(Common '0 all offices)

Regional Offices : Telephone

Central : Manak Bhavan, 9 Bahadur Shah Zafar MargNEW DELHI 110 002

Eastern : 1/14 C. I.T. Scheme VII M, V. I. P. Road. KankurgachiCALCUnA 700 054

{32376 173233841

{3378499.33785613378626,33791 20

.,

{60384360 20 25

235 02 16, 235 04 42235 IS 19,23523 15{

Western : Manakalaya, E9 MIDe, Marol, Andheri (East) { 8329295, 832b8 58MUMBAI 400 093 8327891, 832 7~2

Branches: AHMADABAD. BANGALORE. BHOPAL. BHUBANESHWAR. COIMBATORE.FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUa.LUCKNOW. NAGPUR. PATNA. PUNE.RAJKOT.THIRUVANANTHAPURAM.

Southern : C. I. T. Campus. IV Cross Road, CHENNAI 600 113

Northern : SeQ 335-336. Sector 34-A, CHANDIGARH 160 022

Printed at : Plabhat Oft'set Press. New DeJhi-2