Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public. इंटरनेट मानक !ान $ एक न’ भारत का +नम-णSatyanarayan Gangaram Pitroda “Invent a New India Using Knowledge” प0रा1 को छोड न’ 5 तरफJawaharlal Nehru “Step Out From the Old to the New” जान1 का अ+धकार, जी1 का अ+धकारMazdoor Kisan Shakti Sangathan “The Right to Information, The Right to Live” !ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह Bharthari—Nītiśatakam “Knowledge is such a treasure which cannot be stolen” IS 14666 (1999): High-voltage Alternating Current Switch-fuse Combinations [ETD 8: High Voltage Switchgear and Controlgear]
Transcript
Page 1: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

Disclosure to Promote the Right To Information

Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public.

इंटरनेट मानक

“!ान $ एक न' भारत का +नम-ण”Satyanarayan Gangaram Pitroda

“Invent a New India Using Knowledge”

“प0रा1 को छोड न' 5 तरफ”Jawaharlal Nehru

“Step Out From the Old to the New”

“जान1 का अ+धकार, जी1 का अ+धकार”Mazdoor Kisan Shakti Sangathan

“The Right to Information, The Right to Live”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता है”Bhartṛhari—Nītiśatakam

“Knowledge is such a treasure which cannot be stolen”

“Invent a New India Using Knowledge”

है”ह”ह

IS 14666 (1999): High-voltage Alternating CurrentSwitch-fuse Combinations [ETD 8: High Voltage Switchgearand Controlgear]

Page 2: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7
Page 3: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7
Page 4: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC420 ( 1990 )

Wwifk$ V19*

m dE!xTTRTTM m fim+q-yTidrGFT

Indian Standard

HIGH-VOLTAGE ALTERNATINGSWITCH-FUSE COMBINATIONS

CURRENT

ICS 29.120.60

@ BIS 1999

BUREAU OF INDIAN STANDARDSMANAK BHAVAFI, 9 BAHADtiR SHAH ZAFAR MARG

NEW DELHI 110002

June 1999 Price Group 14

., --——.4

Page 5: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

,

High Voltage Switchgear and Controlgear Sectional Committee, ET 08

NATIONAL FOREWORD

This Indian Standard which is identical with IEC 420 ( 1990) ‘High-voltage alternating current switch-fuse combinations’, issued by the International Electrotechnical Commission ( IEC ), was adoptedby the Bureau of Indian Standards on the recommendations of the High Voltage Switchgear andControlgear Sectional Committee ( ET 08 ) and approval of the Electrotechnical Division Council.

This standard gives the requirements for three pole units for public and industrial distributionsystems which are functional assemblies of switches including switch disconnectors and currentlimiting fuses. These units are able to interrupt any load current up to the rated breaking current ofthe switch and also overcurrent up to the rated short circuit breaking current of the combination.

The text of the IEC Standard has been approved as suitable for publication as Indian Standardwithout deviations.

In the adopted standard, certain terminology and conventions are not identical to those used inIndian Standards. Attention is specially drawn to the following:

a) Wherever the words ‘International Standard’ appear referring to this standard, they should beread as’1 ndian Standard’.

b) Comma (,) has been used as a decimal marker while in Indian Standards, the currentpractice is to use a point (.) as the decimal marker.

In this adopted standard, reference appears to certain International Standards for which IndianStandards also exist. The corresponding Indian Standards which are to be substituted in their placeare listed below along with their degree of equivalence for the editions indicated:

International Standard

IEC 50 ( 151 ): 1978 InternationalElectrotechnical Vocabulary —Chapter 151 : Electrical andmagnetic devices

IEC50 (441): 1984 Chapter 441 :Switchgear, controlgear and fuses

IEC 56:1987 High-voltage alter-nating current circuit-breakers

IEC 129 : 1984 Alternatingcurrent disconnectors andearthing switches

IEC 137:1984 Bushings for alter-nating voltages above 1000 V

IEC 265-1:1983 High-voltageswitches, Part 1 : High-voltageswitches for rated voltages above1 kV and less than 52 kV

CorrespondingIndian Standard Degree ofEquivalence

lS1885( Pat142 ):1993 Identical

lS1885( Part 17):1979

1S13118 :1991

IS 9921( Parts 1 to 5 )

IS 2099:1986

IS 9920( Parts 1 to 4 )

Equivalent

Identical

Partiallyequivalent

,’,

Equivalent

Partiallyequivalent

( Continued on third cover)

Page 6: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666 :1999IEC 420( 1990)

CONTENTS

Page

Clausa

1 General .............................................................................................................................

1.1 Scope ..................................................................................................................................

1.2 Normative references ........................................................................................................

2 Normatand speciaf service conditions .......................................................................................

3 Dewtions .......................................................................................................................................

3.1 Devioes and general terms ...............................................................................................

3.2 Operation ............................................................................................................................

3.3 Characteristicquantities ...................................................................................................

4 Rating ..............................................................................................................................................

4.1

4.2

4.3

4.4

4.5

4.6

4.7

4.8

4.9

4.10

Rated voltage .....................................................................................................................

Rated insulationlevel .......................................................................................................

Rated frequency ................................................................................................................

Rated normal currentmcf temperature rise ..................................................................

Rated short-timewithstandcurrent ................................................................................

Rated peak withstandcurrent ..........................................................................................

Rated duration of shortcircuit .........................................................................................

Rated supplyvoltage of closingand opening devices and auxiliarycircuits............

Rated supplyfrequency of dosing and opening devices and auxiliarycircuits ......

Rated

4.101

4.102

4.103

4.104

4.105

pressureof mmpressed gas supplyfor operation ...........................................

Rated short-circuitbreaking current ..................................................................

Rated transient recoveryvottage........................................................................

Rated shorl-circuitmaking cuffent ....................................................................

Rated transfer current (strikeroperation) ........................................................-

Rated take-over currentfor release-operated combinations .........................

5

5

6

6

6

6

7

8

11

11

11

11

11

12

12

12

12

12

12

12

12

14

14

14

1

Page 7: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666 :1999IEC 420( 1990)

Clause

5 Design and construction................................................................................................................

5.1

5.2

5.3

5.4

5.5

5.6

5.7

5.8

5.9

Requirements for liquids in switch-fuse combinations ................................................

Requirements for gases in switch-fusecombinations .................................................

Earthingof switch-fusecombinations ............................................................................

Auxiliatyequipment ...........................................................................................................

Dependent power closing ................................................................................................

Stored energy closing .......................................................................................................

Operation of releases .......................................................................................................

Low and high pressure interlockingdevices .................................................................

Nameplates ........................................................................................................................

5.101

5.102

5.103

5.104

5.105

6 Type tests .....

6.1

6.2

6.3

6.4

6.5

Combinations ........................................................................................................

Switches used only in combinations .................................................................

Shorbcircuitmakingcurrentof the switch ........................................................

Linkages between the fuse striker(s)and the switch release ........................... .

lndiciMonof position.............................................................................................

................................................................... ...............................................................

Dielectrictests ...................................................................................................................

Radio interferencevoltage (r.i.v.) tests ..........................................................................

Temperature-rise tests .....................................................................................................

Measurement of the resistanceof the main oircuit ......................................................

Short-timewithstandcurrentand peak withstandourrenttests .................................

6.101

6.102

6.103

6.104

6.105

6.106

6.107

Making and breakingtests and performance...................................................

Making and brealdngtest quantitks ..................................................................

Making and breakingtests .................................................................................

Behaviourof the corntination duringtests ......................................................

Conditionof the apparatus after tests ..............................................................

Tests on the mechanism......................................................................................

Mechanical shock tests on fuses ......................................................................

2

14

14

14

14

14

14

14

15

15

15

16

16

16

16

17

It

17

18

18

18

18

18

22

23

30

30

31

31

,“,..

Page 8: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666 :1999IEC 420( 1990)

aause

7

8

9

10

Routine tests ...................................................................................................................................

7.1 Power-frequenoyvoltage withstanddry tests on the main circuit .............................

7.2 Voltage withstandtests on auxiliaryand mntrol cirouits ............................................

7.3 Measurement of the resistanceof the main circuit ......................................................

7.101 Mechanical operatingtests ..................................................................................

Applicationguide for the seleotionof switch-fuse combinationsfor service ........................

8.1 Objeot ...................................................................................................................................

8.2 C&ordination of switchand fuses ..................................................................................

8.3 Operation .............................................................................................................................

8.4 Interlocks ............................................................................................................................

Informationto be given with enquiries, tenders and orders ....................................................

Rules for transport, storage, ereotionand maintenance .........................................................

10.1 Conditionsduringtransport,storage and erection .......................................................

10.2 Ereotion ................................................................................................................................

10.3 Maintenance .............. ................................................................................................... ....

Appendix

A Example of the oo-ordinationof fuses, switohand transformer ........................................

B Justificationof the prooedurefor determiningtransfer ourrentand of theparametem associated with test duty 4 .............................................................................

Figures ......................................................................................................................................

Page

32

32

32

32

32

33

33

34

37

37

37

38

38 -

38

38

39

41

44

3

Page 9: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

As in the Original Standard, this Page is Intentionally Left Blank

Page 10: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

*

IS 14666:1999IEC 420(1990)

Indian Standard

HIGH-VOLTAGE ALTERNATING CURRENTSWITCH-FUSE COMBINATIONS

1 General

1.1 Scope

This standard applies to three-pole units for public and industrial distribution systemswhich are functional assemblies of switches including switch-disconnectors and current-Iimtting fuses and thus able to interrupt:

- any load current up to the rated breaking current of the switch;

any over-current up to the rated short-circuit breaking current of the combination bywhich automatic interruption is initiated.

NOTE 1- Besides by the fuse and its striker operation, automatic interruption may be caused by an over-current release and by self-protecting devices.

It does not apply to fuse-circuit-breakers, fuse-contactors, combinations for motor-circuitsor to combinations incorporating single capacitor bank switches.

NOTE -2 In this standard, the word “combination” is used in the following sense: a combination in which

the components oonatitute a functional assembly.

The fuses are incorporated in order to extend the short-circuit rating of the combinationbeyond that of the switch alone. They are fitted with strikers in order both to open automa-tically all three poles of the switch on the operation of a fuse and to achieve a correctoperation at values of fault current below the minimum breaking current of the fuses. Inaddition to the fuse strikers, the combination may be fitted with either an over-currentrelease or a shunt release.

NOTE 3- In this standard the term “fuse= is used to designate either the fuse or the fuse-link where the

general meaning of the text does not resuft in ambiguity.

This standard applies to combinations designed with rated voltages above 1 kV and below52 kV for use on three-phase alternating current systems of either 50 Hz or 60 Hz.

The individual components of the combinations shall comply, in all relevant respects, withIEC 265-1, 282-1 and 787 quoted below.

NOTE 4- Switches shall be in acoordanoe with IEC 2S5-1 except for the short-time ourrent and short-circuit making requirements where the current limiting effects of the fuses are taken into account.

NOTE 5- Earthing switches forming an integral part of a combination are covered by IEC 129. If the

earthing switch has a rated afiort-circuit making current, the making tests should be made in accordancewith the requirements of IEC 265-1.

NOTE 6- This standard also applies to switch-fuse combinations when included in ring main unit format.

5

Page 11: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

A_L!-

1S 14666:1999IEC 420( 1990)

1.2 Normative references

This standard refers to IEC 694 which is applicable unless otherwise specified in thisstandard. In order to simplify the Indication of corresponding requirements, the samenumbering of clauses and sub-clauses is used as in IEC 694. Amendments to theseclauses and sub-clauses are given under the same references whilst additional sub-clauses are numbered from 101.

{EC Publications. quoted in this standard:

IEC 50(151): (1978), /nternationa/ E/ectrotechnica/ Vocabulary (IEV), Chapter 151: Elec-trical and magnetic devices.

IEC 50(441): (1984), Chapter441: Switchgear, contro/gear and fuses.

IEC 56: (1987), High-vo/tage alternating current ciW&breake~.

IEC 129: (1984), Alternating current disconnectors @o/ators) and earthing switches.

IEC 137: (1984), Bushings for alternating voltages above 1000 V.

IEC 265-1: (1983), High-voitage switches, Part 1: High-voitage switches for rated voltagesabove 1 kV and less than 52 kV.

IEC 282-1: (1985), High-vo/tage fuses, Part 1: Current-limiting fuses.

IEC 298: (1981),A. C. Metal-enclosed switchgear and controlgear for rated voitages above1 kV and up to and including 72.5 kV.

IEC 466: (1987), A. C. insulation-enciosed switchgear and controigear for rated voitagesabove 1 kV and up to and inciuding 38 kV.

IEC 694: (1980), Common c/auses for high-voitage switchgear and controigear standards.

IEC 787: (1983),Application guide for the seiection of fuse-iinks of high-voltage fuses fortransformer circuit applications.

2 Normal and special service conditions

IEC 694 applies.

3 Definitions

For the purpose of this standard, the following definitions shall apply.

3.1 Devices and general terms

3.1.1 Switch-fuse combinations (inciudes fuse-switch combinations)

J,,. ,*

A combination of a three-pole switch with three fuses provided with strikers, the operationof any striker causing all three poles of the switch to open automatically.

Page 12: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

3.1.2 Switch-fuse

A switch in which one or more poles have a fuse in series in a composite unit.

3.1.3 Fuse-switch

A switch in which a fuse or a fuse-carrier with a fuse forms the moving contact.

3.1.4 Switch-disconnector

IEV 441-14-12.

3.1.5 Fuse-base fuse-mount

IEV 441-18-02.

3.1.6 Striker

IEV 441-18-18.

3.1.7 Release-operated combination

A combination in which automatic opening of the switch can also be initiated by either anover-current release or a shunt release.

NOTE - The release may be operated by either an over-current or an earth-fault relay.

3.1.8 Release

IEV 441-15-17.

3.1.9 Over-current release

IEV 441-16-33.

3.1.10 Shunt reiease

IEV 441-16-41.

3.1.11 Ambient air temperature

IEV 441-11-13.

3.2 Operation

3.2.1 Independent manual operation (of the switch)

IEV 441-16-16.

3.2.2 Dependent power operation (of the switch)

IEV 441-16-14.

7

Page 13: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

Is 14666:1999IEC 420( 1990)

3.2,3 Stored energy operation (of the switch)

IEV 441-16-15.

3.3 Characteristic quantifies

3.3.1 Rated value

IEV 151-04-03.

NOTE - See Clause 4 for individual rated values.

3.3.2 Prospective current (of a circuit and with respect to a combination situated therein)

The current that would flow in the circuit if each pole of the combination were replaced bya conductor of negligible impedance.

IEV441-17-01.

3,3.3 Prospective peak current

IEV 441-17-02.

3.3.4 Maximum prospective peak current

IEV 441-17-04.

3.3.5 Prospective breaking current

IEV 441-17-06.

3.3.6 Breaking current

IEV 441-17-07.

3.3.7 Minimum breaking current

IEV 441-18-29.

3.3.8 Short-circuit making capacity>

IEV 441-17-10.

3.3.9 Cut-off currentiiet-through current (of a fuse)

IEV 441-17-12.

3.3.10 Transfer current (striker operation)

The value of the three-phase symmetrical current at whioh the fuses and the switchexchange breaking duties: immediately below this value the current in the first pole toclear is interrupted by the fuse and the current in the other two poles by the switch; abovethis value the three-phase current is interrupted by the fuses only (see also 8.2.4).

8

Page 14: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420(1990)

3.3.11 Take-over current (of a release-operated combination)

The current co-ordinate of the intersection between the time-current characteristics of twoovercurrent protective devices (IEV 441-17-16) (see also 8.2.5).

3.3.12 Minimum take-over current (of a reiease-operated combination)

See Figure 12.

The current determined by the point of intersection of the time-current characteristics ofthe fuse and the switch corresponding to:

a) the maximum break time plus, where applicable, the maximum operating time of anexternal over-current or earth-fault relay;

b) the minimum pre-arcing time of the fuse.

3.3.13 Maximum take-over current (of a reiease-operated combination)

See Figure 12.

The current determined by the point of intersection of the time-current characteristics ofthe fuse and the switch corresponding to:

a) the minimum release-initiated opening time of the switch plus, where applicable,0,02 s to represent the minimum operating time of an external over-current or an earth-fault relay;

b) the maximum operating time of the fuses of highest rated current.

3.3.14 Maximum acceptable power dissipation

The power which is dissipated by the combination when fitted with fuses of maximumpower dissipation as determined by the temperature-rise tests (see Appendix A).

3.3.15 Fused short-circuit current

IEV 441-17-21..

3.3.16 Appiied voitage

IEV 441-17-24.

3.3.17 Recovery voitage

IEV 441-17-25.

3.3.18 Transient recovery voifage (abbreviation: TRV)

IEV 441-17-26.

3.3.19 Power frequency recovery voitage

IEV 441-17-27.

NOTE - This voltage is measured after the switch has opened.

9

Page 15: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

3.3.20 Prospective transient recovery voltage

IEV 441-17-29.

3.3.21 Fuse-initiated opening time (of the switch)

The time taken from the instant at which arcing in the fuse commences to the instant whenthe arcing contacts have separated in all poles.

3.3.22 Release-initiated opening time (of the switch)

The release-initiated opening time is defined according to the tripping method as statedbelow with any time-delay device forming an integral part of the switch adjusted to aspecified setting:

a) For a switch tripped by any form of auxiliary power, the release-initiated openingtime is the interval of time between the instant of energizing the opening release, theswitch being in the closed position, and the instant when the arcing contacts haveseparated in all poles.

b) For a switch tripped (other than by the striker) by a current in the main circuitwithout the aid of any form of auxiliary power, the release-initiated opening time is theinterval of time between the instant at which, the switch being in the closed position,the current in the main circuit reaches the operating value of the over-current releaseand the instant when the arcing contacts have separated in all poles.

3.3.23 Minimum release-initiated opening time (of the switch)

The release-initiated opening time when the specified setting of any time-delay device for-ming an integral part of the switch is its minimum setting.

3.3.24 Maximum release-initiated opening time (of the switch)

The release-initiated opening time when the specified setting of any time-delay device for-ming an integral part of the switch is its maxi~um setting.

3.3.25 Pre-arcing time, melting time (of a fuse)”

IEV 441-18-21.

3.3.26 Arcing time (of a fuse)”

IEV 441-17-37.

3.3.27 Operating time (of a fuse) ●

IEV 441-18-22.

“ The terms may be qualified by prefixing them with “minimum”, “mean” or “maximum” depending upon

whether the lower, mean or upper limits, allowing for maximum tolerances, are intended.

10

Page 16: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

3.3.28 Break-time (of the switch in a release operated combination)

The intervai of time between the beginning of the reiease initiated opening time of theswitch and the instant of finai arc extinction in ali poies.

NOTE - The term may be qualified by prefixing it with ‘minimum” or “maximum= depending upon the

opening time and the arcing time usad.

3.3.29 /zt - Joule integral

iEV 441-18-23.

4 Rating

in addition to the ratings iisted in iEC 694 the foiiowing ratings appiy:

k) Rated shod-circuit breaking current.

i) Rated transient recovWy voitage.

m) Rated short-circuit making current.

n) Rated transfer current for striker operation.

o) Rated take-over current for a release-operated combination.

4.1 Rated ~oltage

iEC 694 for rated voitages beiow 52 kV appiies.

4.2 Rated insulation level

iEC 694 for rated voitages beiow 52 kV appiies.

4.3 Rated frequency

iEC 694 appiies.

4.4 Rated normal current and temperature rise

4.4.1 Rated normal current

iEC 694 applies.

NOTE - The rated normal current applies to the complete combination of switch and fuses selected./“

it is recognized that a combination may be fitted with types and ratings of fuses other thanthose utiiized in the temperature-rise tests and this may change the normai current ratingof the combination. For any particular case, the rated normai current of the combinationshaii be assigned by the switch-fuse manufacturer. For further information see the appli-cation guide (see Ciause 8).

4.4.2 Temperature rise

IEC 694 applies and, as far as fuses are concerned, iEC 282-1.

11

Page 17: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666 :lgggIEC 420(19go)

4.5 Rated short-time withstand current

This sub-clause in IEC 694 does not apply to this standard.

4.6 Rated peak withstand current

This sub-clause in IEC 694 does not apply to this standard.

4.7 Rated duration of short circuit

This sub-clause in IEC 694 does not apply to this standard.

4.8 Rated supply voltage of closing and opening devices and auxiliary circuits

IEC 694 applies.

4.9 Rated supply frequency of closing and opening devices and auxiliary circuits

IEC 694 applies.

4.10 Rated pressure of compressed gas supply for operation

IEC 694 applies.

4.101 Rated short-circuit breaking current

The rated short-circuit breaking current is the highest prospective short-circuit currentwhich the combination shall be capable of breaking under the conditions of use andbehaviour prescribed in this standard in a circuit having a power-frequency recoveryvoltage corresponding to the rated voltage of the combination and having a prospectivetransient recovery voltage equal to the rated value specified in 4.102.

See also the note under 4.103.

The rated short-circuit breaking current is expressed by the r.m.s. value of its a.c.component.

The rated short-circuit breaking currents shall be selected from the R1O series as follows:

8- 10-12,5-16-20-25-31,5-40-50-63-80- 100kA

4.102 Rated transient recovery voltage

The rated transient recovery voltage related to the rated short-circuit breaking cu~ent (inaccordance with 4.101 ) is the reference voltage which constitutes the upper limit of theprospective transient recovery voltage of circuits which the combination shall be capableof breaking in the event of a short circuit.

\

For systems with voltages in the range given in Tables I and 1A, the prospective transientrecovery voltage usually has the form of a damped. single frequency oscillation, or an

12

Page 18: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420(1990)

approximation to such a form. This wave-form is adequately described by an envelope

consisting of two line segments defined by two parameters (see Figure 2).

Table I - Standard values of rated TR

(Based on practice in Europe)

I I IRated TRV

voltage peak value

Time Time voltage

*ordinate delay co-ordhate

Time

co-ordinate

Rate

of rise

u= I t3I uI

Uc t3 I td I u’ t’

kV W 1=I

w I kV kVlpa

40 6 2,1

52 8 4,1

60 9 6,9

72 11 10as 13 14

108 16 21

3,6

7,212

17,524

36

6,2

12,3

20,63041

62

19

25

29

3542

52

0,15

0,24

0,34

0,420,47

0,57

I uc=l,4xl,5x@3u; U’$=113 UC; td=o,15t3

Table 1A- Standard values of rated TRV

(Based on practice in the United States of America and Canada)

Rated TRVvoltage peak value

Time Time Voltage Tmeeon%nate delay co-ordinate oo-ordkmte

Rate

of rise

1

u I u= 6 ‘d u’ t’

T w I PaI

kV I 1=1

5,6 1,6 17,96,9 3,1 22;28,1 4,7 26,19,9 8,6 31,9

10,1 8,9 32,414,0 15,4 44,9

16,7 21,7 53,6

2,85,58,3

15

15,5

27

38

4,89,4

14.2

25,7

26,6

46,3

65,2

3746E4

66

67

93

111

0,13002050,264

0,390

0,397

0,49s

0,587

1 I I

Uc = 1,4X1,5X-U; U’=lfs u=; td=o,15t3

NOTE - The following parameters are used for the representation of rated TRV by two-parameter reference

lines (see Figure 1):

u= = reference voltage (TRV peak value) in kV;

t3= time in ps to voltage u=

13

Page 19: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420(1990)

4.103 Rated short-circuit making current

The rated short-circuit making current is the highest prospective peak current which thecombination shall be capable of making under the conditions of use and behaviour definedin this standard in a circuit having a power-frequency voltage corresponding to the ratedvoltage of the combination. It shall be 2,5 times the value of the rated short-circuitbreaking current.

NOTE - It is recognized that the series impedance of the combination or rapid operation of the fuses or

switch may cause one or both of the following effects:

a) A reduction of short-circuit current to a value appreciably below that which woufd otherwise be reached.

b) Such rapid operation that the short-circuit current wave ia distorted from its normal form.

This is why the term ‘prospective current” is used when assessing breaking and making performances.

4.104 Rated transfer current (striker operation)

The value of the three-phase symmetrical current in the test circuit used for test duty 4.

NOTE - The actual current broken by the switch during teat duty 4 is two-phase and at least equal to -,i.e. 87 % of the rated tranafer current, because one pole is either fitted with a fuse which clears this pole oropen-circuited.

4.105 Rated take-over current for reiease-operated combinations

The value of the three-phase symmetrical current used for test duty 5.

5 Design and construction

5.1 Requirements for iiquids in switch-fuse combinations

IEC 694 applies.

5.2 Requirements for gases ins witch-fuse combinations

IEC 694 applies.

5.3 Earthing of switch-fuse combinations

IEC 694 applies.

5.4 Auxiiiary equipment

IEC 694 applies.

5.5 Dependent power ciosing

Closing mechanisms for dependent manual closing are not allowed.

5.6 Stored energy closing

IEC 694 applies.

14

Page 20: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

5.7 Operation of releases

IEC 694 applies.

5.8 Low and high pressure interlocking devices

IEC 694 applies.

5.9 Nameplates

IEC 694 applies with the following addition:

The nameplate of a switch-fuse combination shall containTable II.

Table II - Nameplate markings

information according to

Condii: marking required

Abbreviationswitch-fuseOperating

Unitonly if not integral wfth

combination device the combinationarrdlor

(1)

manufacturers are different

(2) (3) (4) (5) (6)

Manufacturer x Y

Type deaignatkm x Y

Serialnumber x (w

Number and edition of xUliistandard x

Ratedvoltage u kV x

Ratedfi@ningimpulsewithstand voUage

u. kV x

Ratadfraquenoy f Hz Y Dtierent from 50 Hz and 60 Hz

Maxknum ratad normal

Ourrent with fuses I A xn, max

Type.. . . . . . . . . . . . . . .Manufacturer . . . . . . . . .

Type of fuse strikerMadiim x

(energyoutput) orHeavy

Rated gas pressurefor operation

MPa YPw

ApfNiile

Ratad SUf@y voltage of

auxilii circuitsUa v Y Applicabkl

Year of manufacture x

Diierent from

Temperature daas Y -5 *C indoor-25 “C outdoor

15

Page 21: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420(1990)

X The marking of these values is mandatory; blank spaces indicate zero values.

Y The marking of these values is mandatory, subject to the conditions in column (6).

(Y) The marking of these values is optional and subject to the conditions in column (6).

NOTE - The abbreviations in column (2) may be used instead of the terms in column (1). When the terms

in column (1) are used, the word “rated” need not appear.

5.101 Combinations

Switch-fuse combinations shall be designed so as to be capable. of breaking, at theassigned recovery voltage, any current up to and including the rated short-circuit breakingcurrent.

Switch-fuse combinations shall be designed so as to be capable of making, at the ratedvoltage, circuits to which the rated short-circuit breaking current applies.

5.102 Switches used only in combinations

A switch intended only for use in a combination shall meet the following test requirements:

- Mechanical endurance test according to 6.102 of IEC 265-1.

- Breaking test duties 1, 3 and 4 according to 6.101 of IEC 265-1.

- Short-circuit current making tests according to 5.103 of this standard.

The mainly active load breaking capacity shall be greater than, or equal to, the maximumrated normal current for the combination.

NOTE - Compliance with short-time withstand current requirements is not needed.

5.103 Short-circuit making current of the switch

The switch shall be capable of making the highest cut-off current of the fuses intended foruse in the combination.

5.104 Linkages between the fuse striker(s) and the switch release

The linkages between the fuse striker(s) and the switch release shall be such that theswitch operates satisfactorily under both three-phase and single-phase conditions at theminimum and maximum requirements of a given type of striker (medium or heavy) irrespec-tive of the method of striker operation (spring or explosive). The requirements for strikersare given in 18.13 of IEC 282-1.

16

Page 22: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420(1990)

5.105 Indication of position

,.

When an indication device is @ted, it shall. always correctly indicate the position of theswitch.

NOTE - See 5.104.2 of IEC 265-1.

6 Type tests

IEC 694 applies with the following additions:

- making and breaking tests (see 6.103 of this standard);

- tests on the mechanism (see 6.106 of this standard),

It is understood that the switch in the combination will have been tested as an individualcomponent for compliance with IEC 265-1 (see 5.102 of this standard). Further, it isunderstood that the fuses will have been tested to the requirements of IEC 282-1.

Thus, for combinations, three groups of tests are involved:*

a) Tests on the switch in accordance with IEC 265-1; these tests may be done on acombination other than that used for tests c).

b) Tests on the fuse in accordance with IEC 282-1.

c) Tests on the combination in accordance with this standard.

[n the case of a fuse-switch, the tests of IEC 265-1 (see 5.102 of this standard) and thetests of 6.103.4 and 6.103.5 of this standard shall be carried out after replacing, asspecified, the fuses with solid links of the same shape, dimension and mass as that of thefuses.

The combination submitted for test shall:

1) conform in all essential details to drawings of Its type;

2) be in new condition with clean contact parts and fitted with the appropriate fuses;

3) when release-operated, be equipped with over-current relays or relea~es of thelowest normal current rating associated with the fuses.

The responsibility of the manufacturer is limited to the specified values and not by thevalues obtained during the type tests.

6.1 Dielectric tests

IEC 694 applies with the following additions:

The dielectric tests shall be made with fuses giving the most onerous dielectric conditionsfitted. Partial discharge tests according to 6.1.9 of IEC 694 are normally not required.However, in the case of combinations using components for which a relevant IEC standardexists including partial discharge measurements (e.g. bushings, see I.EC 137), evidenceshall be produced by the manufacturer showing that these components have passed thepartial discharge tests as specified by the relevant IEC standard.

17

Page 23: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

6.2 Radio interference voitage (r.i. v.) tests

Radio interference voltage tests are not required.

6.3 Temperature-rise tests

IEC 694 applies.

The test shall be carried out at the rated normal current of the combination when fittedwith fuses of the highest current rating and/or power dissipation. The temperature rises ofthe various parts of the combination shall not exceed the values specified in IEC 282-1 forthe fuses and IEC 694 for the other parts of the combination.

The following characteristics of the fuses used for the test shall be recorded:

a) manufacturer and type;

b) rated voltage and rated current;

c) internal resistance;

d) power dissipation (measured according to the prescriptions of IEC 282-1).

If the fuses are in an enclosure, the power dissipation at the end of the temperature-risetest is the maximum acceptable power dissipation of the combination and shall berecorded.

6.4 Measurement of the resistance of the main circuit

IEC 694 applies.

NOTE - Solid links of negligible resistance may be used instead of fuses but the resistance of the links

shall be recorded.

6.5 Shod-time withstand current and peak withstand current tests

This sub-clause in IEC 694 does not apply to this standard.

6.101 Making and breaking tests and performance

6.101.0 Generai

In principle, the tests detailed in 6.103 (making and breaking tests) verify only theperformance of the particular combination of switch and fuses actually tested. However, itis recognized that it may well be impractical to:

a) test a given switch-fuse combination with every type of fuse;

b) repeat combination tests whenever alterations are made in the design of theoriginally tested fuses.

Therefore, compliance with this standard may also be deemed to apply for alternativeuntested or partially tested combinations of switch and fuses provided that the followingconditions are met (see the application guide (Clause 8)):

{

1) any switch and fuse considered shall comply with their r~spective standards as faras applicable (IEC 265-1 and IEC 282-1 respectively);

18

Page 24: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

2) the same type of striker must be fitted i.e. medium or heavy in accordance withIEC 282-1;

3) requirements for linkages between fuse-strikers and switch release, as statedin 5.104, are met;

4) ttie requirements for the alternative type of fuse stated in 6.101.0.1, 6.101 .0.2and 6.101 .0.3 are met.

6.101 .0.1 Additional conditions for test duty 1 only

Tests to this standard on a switch-fuse combination fitted with fuses of a pafiicular typeare deemed valid if fuses of an alternative type are fitted provided that the cut-off currentand operating /zt of the alternative type, as established by test duty 1“of IEC 282-1, arenot greater than those of the tested type similarfy established.

6.101 .0.2 Actditiona/ condition for test duty 2 only

Tests to this standard on a switch-fuse combination fitted with fuses of a particular typeare deemed valid if fuses of an alternative type are fitted provided that the operating F f ofthe alternative type, as established by test duty 2 of IEC 282-1, is not greater than that ofthe tested type similarly established.

Where the fuse or fuses tested in the combination to test duty 1 of this standard have ahigher published value of Pf under test duty 1 of IEC 282-1 than under test duty 2, thentest duty 2 of this standard may be omitted.

Exempted from test duty 2 of this standard are combinations in which the switch closesfully home before opening under the action of the fuse striker and has been subjected,under IEC 265-1 conditions, to two make tests at a peak current of a value not lessthan 2,5 times /2 and a short-time test for a duration of not less than 0,1 s at a currentof a value not less than /2 (i.e. the prospective short-circuit current for test duty 2 ofIEC 282-l).

6.101 .0.3 Additional condition for test duty 3 only

Test duty 3 is not mandatory provided that the manufacturers of the fuse and the switchrespectively can produce evidence to show that the combination will perform satisfactorilyunder low over-current conditions, either by a) or b) below:

a) Such evidence, which must cover the following three items, is produced by:

1) The fuse manufacturer providing a value for the maximum length of arcing timefor which the fuse can withstand a value of current just below its minimum breakingcurrent without external damage (refer to the first paragraph of 6. 105).

In principle, this value of current shall be in the range 70 % to 90 % of the calculatedtheoretical minimum breaking current. The value of the arcing withstand time ismeasured from the commencement of arcing until the instant when external damageto the fuse begins to occur.

19

Page 25: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

Alternatively, the fuse manufacturer providing a value for the maximum length ofarcing time as recorded for the given fuse type on test duty 3 of IEC 282-1, thisbeing a lower value than the fuse arcing withstand time as given above.

2) The switch-fuse manufacturer showing that the fuse-initiated opening time of theswitch is less than the fuse arcing time as given in 1) above (see 8.2.3).

3) The fuse manufacturer providing evidence to show that the given fuse will wHh-stand a low-voltage test at a current of a value giving a pre-arcing time of at least20 min duration without external damage (refer to the first paragraph of 6. 105).

b) Where the fuse manufacturer can show that the fuse has been satisfactorily provenat all values of breaking current from the rated value down to the value equivalent tothe minimum melting current of the fuse in the combination (i.e. so called full rangefuses) then the fuse-initiated opening time of the switch-fuse combination is deemednot relevant and test duty 3 may be omitted.

6.101 .0.4 Additional condition for test duty 4 only

test duty 4 may be omitted in the case of release-operated combinations if the take-overcurrent is equal to or higher than the transfer current.

6.101.1 Condition of the combination before tests

The combination under test shall be mounted complete on its own support or on an equi-valent support. Its operating device shall be operated in the manner specified and, in parti-cular, if it is electrically or pneumatically operated, it shall be operated at the minimumvoltage or gas pressure respectively as specified in 4.8 and 4.10 of IEC 694, unlesscurrent chopping influences the test results. In the latter case, the combination shall beoperated at a voltage or gas pressure within the tolerances specified for 4.8 and 4.10 ofIEC 694, chosen so as to obtain the highest contact speed at contact separation andmaximum arc extinguishing properties.

It shall be shown that the combination wi!l operate satisfactorily under the aboveconditions on no-load. The travel of the moving contacts shall be recorded if possible.

Combinations with independent manual operation may be operated by an arrangementprovided for the purpose of making remote control possible.

Due consideration shall be given to the choice of the live side connections. When thecombination is intended for power supply from either side and the physical arrangement ofone side of the break or breaks of the combination differs from that of the other side, thelive side of the test circuit shall be connected to that side of the combination which givesthe more onerous condition. In case of doubt, the test duty shall be repeated with thesupply connections reversed, but for test duties comprising identical tests, one test shallbe made with the supply connected to one side and the following test(s) with the supplyconnected to the other side.

20

Page 26: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420(1990)

The tests performed on the combination shall be made with fuses having the highest ratedcurrent and/or operating Ft value declared by the manufacturer as suitable for use in thecombination.’ For release-operated combinations, over-c’urrent relays or releases (wherefitted) shall be of the lowest normal current “ratingassociated with these fuses. The testsshall be carried out at the ambient temperature and without previous loading unless other-wise specified.

6.101.2 Test frequency

Combinations shall, in principle, be tested at rated frequency with a toleranc6 of +1 O %.However, for convenience of testing, some deviations from the above tolerance areallowable; for example, when combinations rated at 50 Hz are tested at 60 Hz and viceversa, care should be exercised in the interpretation of the results, taking into account allsignificant facts such as the type of the combination and the type of tests performed.

NOTE - In some cases, the rated characteristics of a combination when used on a 60 Hz system may beclifferent from its rated characteristics when usad on a 50. Hz system.

6.101.3 Power factor

The power factor of the test circuit shall be determined by calculation from thq. circuitconstants or by measurement and shall be taken as the average of the power faCtors in ‘each phase.

During the tests, the average value shall conform to the values given in 6.103.1, 6.103.2,6.103.3, 6.103.4 and 6.103.5.

6.101.4 Arrangement of test circuits

For test duties 1 and 2, the combination shall preferably be connected in a circuit havingthe neutral point of the supply isolated and the neutral point of the three-phase shortcircuit earthed, as shown in Figure 3 a). When the neutral point of the test supply cannotbe isolated, it shall be earthed and the three-phase short-circuit point shall be isolated asshown in Figure 3 b).

For test duty 3 the combination shall be connected in a single-phase circuit as shown inFigures 4a) and 4 b).

For test duties 4 and 5 the combination shall be connected in a circuit as shown inFigures 5 a) and 5 b).

For combinations producing an emission of flame or metallic particles, the tests shall bemade with metallic screens placed in the vicinity of the live parts, separated from them bya clearance distance which the manufacturer shall specify.

.-

The screens, frame and other normally earthed parts shall be insulated from earth butconnected thereto by a suitable device to indicate leakage current to earth.

21

Page 27: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

f ,

IS 14666:1999IEC 420(1990)

6.102 Making and bre4ing testquantities*

6.102.1 Test vo/tage for breaidng tests

The test voltage is the average of the phase-to-phase voltages measured at the combi-nation location immediately after the breaking operation.

The voltage shall be measured as close as practicable to the terminals of the combination,i.e. without appreciable impedance between the measuring point and the terminals.

The test voltage, in the case of three-phase tests, shall be, as nearly as possible, equal tothe rated voltage of the combination.

The tolerance on the test voltage is *5 % of the specified value.

6.102.2 Power-frequency recovery voltage

The power-frequency recovery voltage shall be maintained for 0,1 s, at least, after arcextinction.

The power-frequency recovery voltage of a three-phase test circuit shall be the averagevalue of the power-frequency recovery voltages in all phases measured after the openingof the switch.

The powet-frequency recovery voltage of the test circuit shall be measured between theterminals of each pole of the combination in each phase of the test circuit.

The power-frequency recovery voltage shall be measured one cycle after the opening ofthe switch in accordance with Figure 6.-.

6.102.3 Applied voltage before short-circuit making tests

The applied voltage (see 3.3. 16) before the short-circuit making tests in test duties 1and 2 is the r.m.s. value of the voltage at the pole terminals immediately before the test.

In the case of three-phase tests the average value of the applied voltages shall be not lessthan the rated voltage of the combination divided by @ and shall not exceed this value bymore than 10 % without the consent of the manufacturer.

The difference between the average value”and the applied voltages of each phase shallnot exceed 5 Y. of the average value.

.

22

Page 28: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420(1990)

6.102.4 Breaking current

For test duties 1 and 2 the r.m.s. value of the a.c. component of the prospective shorlcircuit breaking current shall be measured one half-cycle after the initiation of the shortcircuit in the prospective current test.

For test duties 3, 4 and 5 the breaking current shall be the r.m.s. value of the a.c. compo-nent measured at the initiation of arcing.

For test duties 1, 2 and 5 the r.m.s. value of the a.c. component of the breaking current inany pole shall not vary from the average by more than 10 YO of the average. For testduty 4, the r.m.s. value of the a.c. component of the breaking current in the two polesfitted with solid conducting links shall be not less than ~2, i.e. 87 Y., of that in the firstpole to clear, i.e. the pole fitted with a fuse.

.

6.102.5 Transient recovery voltage

The prospective TRV of a test circuit shall be determined by such a method as willproduce and measure the TRV wave without significantly influencing it and shall bemeasured at the terminals to which the combination will be connected with all necessarytest-measuring devices, such as voltage dividers, included. Suitable methods are des-cribed in Appendix GG of IEC 56.

For three-phase circuits, the transient recovery voltage refers to the first pole to clear, i.e.the voltage across one open pole with the other two poles closed, with the appropriate testcircuit arranged in accordance with 6.f 01.4.

The prospective transient recovery voltage curve of a test circuit is represented by itsenvelope drawn as shown in Figure 2 and by its initial portion.

The prospective transient recovery voltage wave of the test circuit shall comply with thefollowing requirements:

a) Its envelope shall at no time be below the specified reference line.

NOTE - ft is stressed that the extent by which the envelope may exceed the specified reference line

requires the consent of the manufacturer.

b) Its initial portion shall not cross the delay line where such a one is specified.

6.103 Making and breaking tests

6.103.1 Test duty 1

This test duty is performed to show that the switch is capable of withstanding and makingthe cut-off current of the fuse without damage and that the striker will open the switch atthis current. The test is carried out with fuses fitted in all three poles of the combination.

One break and then one make-break test shall be made in a three-phase circuit havingprospective symmetrical r.m.s.and peak currents equal to the rated short-circuit values ofthe combination with a tolerance of -O Y. +5 Y..

23

Page 29: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

The power factor of the test circuit shall be 0,07 to 0,15 lagging.

The applied voltage shall be in accordance with 6.102.3.

The power-frequency recovery voltage (see 6.102.2) shall be equal to the rated voltage ofthe combination divided by ~ with a tolerance of *5 ‘Yo.

The prospective transient recovery voltage shall be in accordance with 4.102 and 6.102.5.

The first operation of the test duty shall be made with the initiation of arcing in the fuse inme of the outer poles in accordance with the provisions of IEC 282-1, test duty 1, i.e. to>e within the range 65 to 90 electrical degrees after voltage zero in that pole.

6.103.2 Test duty 2

This test duty may be omitted (unless requested by the user) provided that the conditionsof 6.101 .0.2 can be met.

When carried out, its purpose is to verify the performance of the combination with aprospective current approximating to that producing the maximum Pt for the switch. Thetest is carried out with fuses fitted in all three poles of th,e combination.

One break and then one make-break test shall be made in a three-phase circuit having aprospective current “within*1 O % of that prospective current required to verify the value ofFt of IEC 282-1 for the fuse design incorporated in the combination.

The power factor of the test circuit shall be 0,07 to 0,15 lagging*.

The applied voltage shall be in accordance with 6.102.3. The first operation of this testduty shall be made with point-on-wave closure of the circuit such that current commencesbetween O and 20 electrical degrees after voltage zero on any one phase..

The power-frequency recovery voltage (see 6.102.2) shall be equal to the rated voltage ofthe combination divided by ~ with a tolerance of *5 ‘A.

The prospective transient recovery voltage shall be in accordance with 6.102.5 and thevalues specified in Table Ill Or 111Aas appropriate (see also Appendix B of IEC 282-1). Itshighest peak shall be not smaller than the parameter UCspecified. The rising segment ofits envelope shall be between the two lines specified by the tolerance of t3

NOTE - A delay line is not specified because the initial portion of the TRV wave is of no im~rtance forthe behaviour of the fuse (see Appendix B of [EC 282-1).

“ When the manufacturer agrees, the lower limit does not apply.

24

Page 30: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

Table Ill - Standard values of prospective TRV for test duty

(Based on practice in Europe)

Rated TRVValtege peak voltage

u L/c

W W

3,6 6,6

72 13,2

12 2217,5 32

24 4436 88

I UC=1,5X

IS 14666:1999IEC 420( 1990)

2

TImaco-ordinate I

Rate of riseI

I U=l $ IP$

120-180

158-208

180-240216-288264-352324-432

kVlps

0,055-0,041

0,064-0,069

0,122-0,0810,148.-0,1110,167-0,125

0,203-0,152

,5X+Z3U

Table 111A- Standard values of prospective TRV for test duty 2

(Based on practice in the United States of America and Canada)

Rated TRV Timevoltage peak voltage co-adnate

u u= G

kV kV P

2,8 5,1 111-146

5,5 10,1 138-1648,3 15,2 162-216

15 27,6 186-264

15,5 26,5 201-288

27 49,6 279-37238 69,8 3s3-444

Rate of rise

u= I t3

0,046-0,034

0,073-0,055O,o%t -0,071

0,139-0,1040,142-0,106

0,178-0,1330,210-0,157

U==I,5XI,5X4ZSU

6.103.3 Test duty 3- breaking test with long pre-arcing time of fuse

This test duty may be omitted (unless requested by the user) provided that the conditionsof 6.101 .0.3 can be met.

When performed, its purpose is to demonstrate that:

a) the fuse is able to carry low over-currents withindamage during the pre-arcing period (see 1) below);

b) the fuse, having been pre-heated by a current as

the combination without external

under a), is able to withstand aninternal arcing current below the minimum breaking current without external damage fora period of time, including a certain safety margin, before the striker-operated switchinterrupts the current (see 2) below).

25

Page 31: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420(1990)

Two breaking tests shall be made in a single-phase circuit. Both of the preceding condi-tions shall be met on each test.

The tests shall be in two parts:

1) A low-voltage current shall be applied to the combination to pre-heat the fuse. Thevalue of this current shall be in the range of 75 ‘A to 85 9f0 of the value of the 20 minpre-arcing current for the fuse, as determined from the manufacturer’s mean time-current characteristic.

2) After 20 min. the value of the low-voltage test current shall be brought to within therange of 70 % to 80 YO of the value of the minimum breaking current of the fuse. Prior tomelting, the combination shall be switched over to a high-voltage source equal to therated voltage of the combination and set to the same value of current. (The method ofchange-over is given in 13.2.2.1 of IEC 282- 1.)

The time-current characteristics of certain types of fuses with low minimum breakingcurrent values may make it impossible to obtain metting of the fuse elements at 80 YO ofthe vaiue of the minimum breaking current (at least within a reasonable time). Under thiscircumstance, after 20 min. of pre-heating, the iow-voitage current shali be changed to ahigher value sufficient to melt the fuse elements within the ensuing few minutes. Whensome or ail of the fuse elements have melted but with the striker element still intact, thefuse shall be switched over to a high voltage source equal to the rated voltage of the com-bination set at 70 % to 80 ‘A of the value of the minimum breaking current.

NOTES

1 When testing station limitations prevent the maintenance of constant current, the tolerance of the

current can be exceeded in either direction during not more than 20 % of the total melting time provided

that the current at the initiation of arcing is within the tolerance specifiad for test dut y 3.

2 If, for any reason, the fuse ctears the circuit before the arcing contacts cf the switch separate, the testis invalid and should be repeated with a lower ourrent during the second part, until two valid testshavebeen obtained.

The tests shaii be made ORone of the outer poies of the combination, with a fuse fitted, inseries with one of the other poles having a soiid link of negligible impedance fitted in theplace of the fuse.

The power factor of the test circuit shall be between 0,4 and 0,6 iagging.

The power-frequency recovery voitage appearing across the two poles in series shall beequal to the rated voltage of the combination with a tolerance of *5 ‘A. TRV characteristicsare not specified (see 13.1 .2.3 of IEC 282-1).

The operation of the fuse striker shali cause the switch to open.

6.103.4 Test duty 4- breaking tests at the rated transfer current -

This test duty is mandatory (but see 6.101 .0.4) and is performed to prove the correctco-operation between the switch and fuses in the current region where the breaking dutyis transferred from the fuses to the switch (see 3.3.10).

26

Page 32: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

--.&L

1

IS 14666:1999IEC 420( 1990)

The value of the rated transfer ctment shall be determined by the switch-fusemanufacturer, taking into account the fuse-initiated opening time of the switch and thetime-current characteristic of the fuse of maximum current rating to be used, as explainedin 8.2.4.

NOTE - This current should be equal to or greater than the transfer ourrent as defined in 3.3.10 (aJso seethe application guide (ClauseS)).

Three break tests shall be made in a three-phase circuit, as shown in Figure 5a, with thefuses in two poles replaced by solid links of negligible Impedance. The pair of poles with

I. . the solid links shall be different on each of the three breaking tests. In the case of fuse-

switches the solid links shall be of the same shape, dhnension and mass as those of thefuses they replace (see also the paragraph after Item c) of Clause 6).

If this arrangement of one fuse and two solid links is not practicable for the testing labora-tory, then the fuse may be omitted and the switch tripped in some other way. In the caseof fuse-switches the fuse shall be replaced by either a dummy fuse (e.g. a blown fuse) oran insulating link of the same shape, dimension and mass as those of the fuse.

The test circuit shall consist of a three-phase supply and load circuit (see Figure 5a).

The load circuit shall be a series circuit.

The supply circuit shall have a power factor not exceeding 0,2 lagging and shail meet thefollowing requirements:

a) the symmetrical component of the short-circuit breaking current of the supply circuitshall neither exceed the rated short-circuit breaking current of the combination nor beless than 5 Ye of this current;

b) the impedance of the supply circuit shall be between 12 % and 18 % of the totalimpedance of the test circuit for test duty 4. If due to !imitations of the testing stationthis condition cannot be met, the percentage may be’ tower. But it shail be ensured thatthe resulting prospective TRV is not less severe;

c) the prospective transient recovery voitage of the supply circuit under short-circuitconditions shall be not less severe than that specified in Table I or 1A,as appropriate.

The power factor of the load circuit, determined in accordance with 6.?01 .3, shall be:

- 0,2 to 0,3 lagging if the breaking current exceeds 400A;

- 0,3 to 0,4 lagging if the tweaking cuwent is -al to or tees than 400 A.

The test voltage shall be in accordance with 6.102.1.

[

.......

The power-frequency recovery voltage (see 6.1 02.2) si@l be equal to the rated voltage ofthe combination divided by ~ with a tolerance ot *.5 %.

27

Page 33: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

d

IS 14666:1999IEC 420( 199o )

/

.: .

The prospective transient recovery voltage of the load circuit, for calibration purposes,shall be in accordance with 6.102.5 and Tables IV or IVA, as appropriate. A delay line isnot specified. %4$

::

Table IV - Standard values of prospective TRV for test duty 4

(Based on practice in Europe) \

~Rated TRV T-mm

voltage peak VoltegeRate cd b“ 1’

u Uc !3 ucl~ . . . .

kV kV w kVlps

3,6 6,2 so 0,077

7,2 12,3 104 0,115 d12 20,6 120 0,16717,5 30 144 0206

\

24 41 176 0236

36 62 216;

o#2s5

UC=1,4X1,5X4Z?3U

Table IVA - Standard values of prospective TRV for test duty 4

(Based on practice in the United States of America and Canada)

Rated TRVvoftsge ** so-odnats

Rated rise

u Uc fa U=l $

kV kV w kVlps

2,s 4,s 74 0,0s55,5 9,4 92 0,1038,3 14,2 106 0,132

15 25,7 132 0,1%15.5 26,6 1s4 0,19627 46s 1= 024938 652 2Z Om

Ue.l,sxl,sxau I

.

. .

NOTES

1 Tables IV and IVA @v. thr.e-phaso vafues ar@ refer to the fket @e to dear, i... tho pofe with the

fuse (or dummy fusdirwulati~ link).

2 The valuesshownin Teblea IV errdIVAare eppfioablato typfcalinstaffationskwofvfngtrensfercurrentsof lowervaluethan those arising from sofid short-circ~ in the transfor~ secondary terminal

zone; the latter are normally cleerad by tho fue.a. However, they may net be appropriate fw an appfiaetionrequiring the cfearing of such terminal-zone faults by the switch. SucfI a condftion of appfiition is whject

to agreement between the user and the manufacturer.

28

Page 34: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

,.,

.4

IS 14666:1999IEC 420(1990)

6.103.5 Test duty 5- breaking tests at the rated take-over current(release-operated cornbhatkms only)

This test duty is mandatofy for release-operated combinations only and is pedormed toprove the correct co-operation between the release-operated switch and fuses in thecurrent region where the breaking duty is taken over from the fuses by therelease~operated switch (see 3.3.11).

The value of the rated take-over current shall be determined by the switch-fusemanufacturer, taking into account the release-initiated opening time of the switch and thetime-current characteristic of the fuse of maximum current rating to be used, as explainedin 8.2.5.

NOTE - This current should be equal to or greater than the maximum take-over current as defined

in 3.3.13 (see also the application guide (Clause 8)).

Three break tests shall be made in a three-phase circuit,as shown in Figure 5b, with the fuses inall three poles replamd by solii tinks of negligible impedance. In the case of fuse-switches thestild links shall be of the same shape, dimension and mass as those of the fuses they replace(see also the paragraph after Item c) of Clause 6).

The test arcuit shall be the same as that for test duty 4.

6.103.6 Summary of testparameters

A summary of the parameters to be used when performingtest duties 1 to 5 is given in Table V.

Table V - Summary of test parametersfor test duties 1 to 5

Test dutyTest Teetcweratl Powsr

No. Cwuit voltage X tie “~ factor TRV

1 3-phase u Mteetdutyl o 0,07to0,15 TablealandfAfigure3 ~ IEC3S2-1 co @E@9 Ofthisstandard

2 s-phase u seeteatduty2 o 0,07 to 0,15 Tabfea Ill and 111Afigure 3 of IEC 2S2-1 co tagging d this standard

3 l-phase u 0,8 Is o 0,4 to 0,8 See 13,1,22ffgure 4 seetestduty3 o tWf9iw of IEC 2S2-1

of IEC 2S2-1

4 3-phaslY u 1,I 0,s7~ o 14>400A Tables IV and IVA2-phsse See 8,103,4 0 02 to 0,3 d t& standard

&ure 5a of thfs standard o fW9@

4s400A See 6,101,8 a)

0$ to 0,4 of IEC2S5-1@mm

5 u & o ~>400A T* IVandfVAfigure5b Sea6,103,5 0 02 to0,3 dtitird

ofthisstandard o %f@Xf&s“400A See6,101,8a)Osb 0,4 ofIEC2S61lagging

NOTE- Thepowerfactors relating to test duties 4 and 5 refer to the load circuit.

29

Page 35: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

6.104 Behaviour of the combination during tests

The combination may be inspected but not reconditioned (apart from the replacement offuses) between any of the test duties which shall all be done on the same combination.

During operation, the combination shall show neither signs of excessive distress norphenomena that might endanger an operator.

From liquid-filled combinations there shall be no outward emission of flame, and the gasesproduced together with the liquid carried with the gases shall be allowed to escape in sucha way as not to cause electrical breakdown.

For other types of combinations, flame or metallic particles such as might impair theinsulation level of the combination shall not be projected beyond the boundaries specifiedby the manufacturer.

There shall be no indication of significant leakage current to the earthed structure orscreens, when fitted, during the tests. In case of doubt, the normally earthed parts shouldbe connected to earth through a fuse consisting of a copper wire of 0,1 mm diameter and50 mm long.

No significant leakage current is assumed to have flowed if the fuse wire is intact after thetest.

In certain circumstances it may be necessary to maintain a permanent electrical connec-tion between the frame of the combination and earth. In such cases it is permissible toearth the frame through the primary winding of a suitable transformer having a 1:1 ratiowith the fuse connected across the secondary winding of the transformer and with thesecondary terminals protected by a spark gap.

During test duties 1, 2 and 3, the switch shall open following the action of the fuse strikers.

NOTES

1 All three fuses should be replaced regardless of whether, during the test, they have operated or not.

2 In three-phase operations, one fuse and/or its striker may not have operated during tests. This is a

normal and not unusual condition which will not invalidate acceptance of the test provided that the fuseshall not have received external damage in any way.

6.105 Condition of the apparatus after tests

After tests, fuses shall comply with the requirements of 7.2.3 of IEC 282-1. After testduty 3, external signs of damage or deterioration are acceptable provided they are notsuch as to prevent compliance: minor cracks and/or discoloration are permitted (referto 7.2.3 ~f IEC 282-1).

After performing each test duty:

a) The mechanical function and the insulators of the combination shall be practically inthe same condition as before the tests. There may be deposits on the insulators causedby the decomposition of the arc-extinguishing medium.

--k

.. 4,

!.f.+

,.

30

Page 36: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

~’ ,

.-— —

. . .d

IS 14666:1999IEC 420{ 1990)

b) The combination shall, without reconditioning, be capable of withstanding its ratedvoltage without dielectric failure.

c) For those combinations which incorporate a switch-disconnector, the isolatingproperties of the switch-disconnector in the open position shall not be reduced belowthose specified (see 4.2) by deterioration of insulating parts in the neighborhood of, orparallel to, the isolating distance. The requirements for disconnectors in IEC 129 shallbe fulfilled.

d) The combination shall beafter renewal of fuses.

Visual inspection and no-loadsufficient for checking the above

capable of carrying its rated normal current continuously

operation of the combination after tests are usuallyrequirements.

In case of doubt as to the ability of the combination to meet the conditions of the foregoing6.105 b), it shall be subjected to the relevant power-frequency voltage withstand tests inaccordance with 7.1 but using 80 Y. of the prescribed test voltage.

In case of doubt as to the ability of the combination, where applicable, to meet theconditions of the foregoing 6.105 c), it shall be subjected to the relevant power-frequencyvoltage withstand tests in accordance with 7.1.

In case of doubt as to the ability of the combination to carry the rated normal current, atemperature-rise test shall be made, after renewal of the fuses, to check that thetemperature-rise values specified (see 4.4) are not exceeded by more than 10 K. An over-haul of the combination is authorized after the temperature-rise test.

6.106 Tests on the mechanism

6.106.1 General test conditions.

Unless otherwise specified, the tests shall be made at the ambient air temperature of thetest location.

6.106.2 Test of the trip linkages (&/so refer to 6. 107)

1) To test the mechanical reliability of the linkages between the fuse striker(s) and theswitch release, a total of 100 operations shall be made with the appropriate type ofstriker, of which 90 shall be made (30 in each pole) with one striker of minimum energyand 10 with three strikers of maximum energy operating simultaneously.

After performing this test duty, the mechanical functioning of the trip linkages shall bepractically the same as before the tests.

2) Using a dummy fuse-link with extended striker, set to the minimum actual travelwithin the tolerance specified in 18.13 of IEC 282-1, for each pole in turn it shall beshown that the switch either cannot be closed or cannot remain closed according to itsdesign.

NOTE - For the purpose of these tests, a device simulating fuse striker operation maybe used.

6.107 Mechanica/ shock tests on fuses

During the test of the trip linkages given in 6.106.2 two fuses of different manufactureshall be fitted in the two poles of the combination not fitted with the fuse striker simulating

31

Page 37: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

device for the three sets of 30 operations involved. Each of the two fuses used shall bethe mechanically least robust of their respective series as advised by the fuse manu-facturer.

Additionally, in the case of fuse-switches only, 90 close-open operations shall beperformed manually with three fuses of different manufacture fitted. Each of the threefuses used shall be the mechanically least robust of their respective series as advised bythe fuse manufacturer.

After performing this (these) test duty(ies), the fuses shall show neither signs of mecha-nical damage nor change in resistance. They shall not have become displaced in theircontacts.

The satisfactory performance of the above test duty(ies) can be deemed to be sufficientevidence for justifying the use of makes of fuses other than those tested without furthermechanical shock testing.

7 Routine tests

[EC 694 applies.

7.1 Power-frequency vo/tage withstand dry tests on the main circuit

IEC 694 applies.

7.2 Voltage withstand tests on auxiiiary and controi circuits

IEC 694 applies.

7.3 Measurement of the resistance of the main circuit

IEC 694 applies; also see note under 6.4.

7.101 Mechanical operating tests

Operating tests shall be carried out to ensure that combinations’ comply with the pres-cribed operating conditions within the specified voltage and supply pressure limits of theiroperating devices.

During these tests, it shall be verified, in particular, that the combinations open and closecorrectly when their operating devices are energized or under pressure. It shall also beverified that operation will not cause any damage to the combinations. Fuses of maximummass and dimensions shall be fitted.

For all switch-fuse combinations the following test shall be done:

a) under the conditions of 6.106.2 with the action of on-e fuse striker of minimumenergy, simulated: five opening operations.

32 .

Page 38: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

Additionally, the following tests shall be done where applicable:

b) at the specified maximum supply voltage and/or the maximum pressure of thecompressed gas supply: five operating cycles;

c) at the specified minimum supply voltage and/or the minimum pressure of thecompressed gas supply: five operating cycles; I

d) If a combination can be operated by hand as well as by its normal electric orpneumatic operating device: five manually operated cycles;

e) for manually operated combinations only: ten operating cycles;

f) for release-operated combinations only, at rated supply voltage and/or ratedpressure of the compressed gas supply: five operating cycles with a tripping circuit

~ energized by the closing of the main contacts.

The tests a), b), c), d) and e) shall be made without current passing through the maincircuit.

For combinations fitted with over-current releases, the releases shall be set at theminimum calibration mark on the over-current scale.

During test f), it shall be shown that the over-current releases operate correctly with acurrent passing through the main circuit not exceeding 110 YO of the setting value on theover-current scale.

This current may be supplied from a suitable low-voltage source.

During all the foregoing routine tests, no adjustments shall be made and the operationshall be faultless. The closed and open positions shall be attained during each operatingcycle on tests a), b), c), d) and e).

After the tests, the combination shall be examined to determine that no parts havesustained damage and that all parts are in a satisfactory condition.

8 Application guide for the selection of switch-fuse combinations for service

8.1 Objecf

The object of this application guide, taken In conjunction with that for switches (seeCiause 8 of IEC 265-1) and that for fuses (IEC 787) is to specify criteria for the selectionof a combination of switch and fuses which will assure safe operation, using the parametervalues established by tests in accordance with IEC 265-1, IEC 282-1 and this standard.

.

Criteria for the co-ordination of high-voltage fuses with other drcuit components in trans-former applications and guidance for the selection of such fuses with particular referenceto their time-current characteristics and ratings are given in IEC 787.

33

Page 39: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

Guidance for the selection of switches will be given in the pending application guide forIEC 265-1.

The test duties specified in this standard together with the associated guidance as to theapplication of these tests to other combinations cover most users’ requirements. However,some cases, for example to support the use of a back-up fuse by type tests done on thecombination using so called full range fuses from another manufacturer, may requireadditional combination testing. Such testing should be subject to agreement between themanufacturer and user.

8.2 Co-ordination ofs witch and fuses

8.2.1 Rated short-circuit breaking current

The rated short-circuit breaking current of a combination is largely determined by that ofthe fuses and shall be equal to or greater than the maximum expected fault current levelof the point in the distribution system at which the combination is to be located.

8.2.2 Rated normal current

Reference should be made to 22.2 of IEC 282-1 where comment is made on the ratednormal current of fuses and its selection and on how it may be affected by the mounting ofthe fuses in an enclosure.

The rated normal current of a switch-fuse combination is assigned by the switch-fusemanufacturer on the basis of information gained from temperature-rise tests and willdepend on the type and ratings of the switch and the fuses. It may have to be reducedwhere the ambient temperature in service exceeds the prescribed ambient temperature(see 2.1 and 2.2 of IEC 694).

NOTE - The rated normal current of a combination is generally less than, but should not be in excess of,

the rated current of the fuses as assigned by the fuse manufacturer.

8.2.3 Low over-current peflormance

At values of fault current below the minimum breaking current of the fuses fitted in thecombination correct operation is assured by the ejection of one or more fuse strikers oper-ating the switch tripping mechanism (and hence causing the switch to open) before thefuse has had time to be damaged by internal arcing.

In 6.101 .0.3 are laid down criteria which have to be observed for correct operation to beassured. Whilst, in the case of the first alternative under 6.101.0.3. a) 1), there is no valuespecified for the margin between the fuse-initiated opening time of the switch and theno-damage withstand time of the fuses, practical considerations suggest a no-damagewithstand time of the fuses at least 50 % longer than the fuse-initiated opening time of theswitch. In this way, due ‘allowance with a reasonable safety margin will be made for manu-facturing tolerances and variations in service conditions.

,.,,

34

Page 40: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

.. ‘

IS 14666:1999IEC 420( 1990)

The second alternative under 6.101 .0.3 a) 1) is based on the proven concept that thenumber of cycles of arcing in a fuse at a current just below the true minimum breakingcurrent will always be greater than the number of cycles of arcing at a value of current justabove the true minimum breaking current. Using this concept, it is only necessary to exa-mine the oscillographic records of existing test duty 3 in IEC 262-1 on given fuses andmeasure the arcing time: if it is greater than the fuse-initiated opening time of theassociated switch-fuse, then the conditions of the second alternative may be deemed tobe satisfied.

The preceding paragraphs, to be strictly correct, should refer to the break-time not theopening time of the switch. However, the opening time is usually more readily availableand is accurate enough for the purpose.

8.2.4 Transfer current

The transfer current of a combination is dependent upon both the fuse-initiated openingtime of the switch and the time-current characteristic of the fuse.

Near the transfer point, under a three-phase fault, the fastest fuse to melt clears the firstpole and its striker starts to trip the switch.

The other two poles then see a reduced current (87 Y.) which will be interrupted by eitherthe switch or the remaining fuses. The transfer point is when the switch opens and thefuse elements melt simultaneously.

From a practical standpoint the transfer current for a given application is determined asfollows:

Superimpose upon the minimum pre-arcing time-current characteristic (based on a currenttolerance of -6,5 Y.)” of the fuse (see Figure 7) a time equal to 0,9 times the fuse-initiatedopening time of the switch (see Appendix B for the derivation): the associated currentis the value of the three-phase transfer current, and must not be greater than the ratedtransfer current which is the three-phase current determined by the switch-fuse manufac-turer and used on test duty 4: the test-current through the two poles of the switch fittedwith solid links on test duty 4 is equal to ~2, i.e. 0,87 times this current after the currentin the pole fitted with the fuse has been interrupted.

For a mathematical justification of the above procedure, see Appendix B.

8.2.5 Take-over current

The value of the take-over current of a combination is dependent upon both the release-initiated opening time of the switch and the time-current characteristic of the fuse-. As itsname implies, it is the value of over-current above which the fuses take-over the funtilonof current interruption from the release and switch.

“ In these sub-clauses a amrant tderanse of $6,5 % is used(i.e.M?u of*1O %). Ttis isbaaedoncurrentpractice.

35

Page 41: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

A

a

IS 14666:1999IEC 420(1990)

From a practical standpoint the maximum take-over current for a given application is deter-mined as follows:

Superimpose upon the maximum pre-arcing time-current characteristic (based on acurrent tolerance of +6,5 9’o)* of the fuse (see Figure 12) a time equal to the minimumrelease-initiated opening time of the switch plus, where applicable, 0,02s to represent theminimum operating time of an external relay: the associated current is the value of thetake-over current, and shall not be greater than the rated take-over current which is thecurrent determined by the switch-fuse manufacturer and used on test duty 5.

8.2.6 Primary fault condition caused by a solid short circuit on the transformersecondary terminais

As indicated in note 2 after Tables IV and WA and in Appendix B, Clause 94, the primaryside fault condition caused by a solid short circuit on the transformer secondary terminalsgives rise to severe TRV values wh!ch the switch in a combination may not be able tocope with. The fuses, therefore, shall be so chosen that they alone will deal with such afault condition without throwing any of the breaking duty onto the switch. In practice, thisentails ensuring that the transfer current of the combination, found in the mannerdescribed in 8.2.4, is less than the foregoing primary fault current.

NOTE - In some cases, in order to achieve this, it maybe necessary to choose a fuse with a rated current

from the RIO rather than from the R6 series.

An example is given in Appendix A.

8.2.7 Extension of the vaiidity of making and breaking (ype tests

As it is recognized that it may well be Impractical to test all combinations of switch andfuses and to carry out repeat test$ on combinations whenever the fuse is altered, thisstandard specifies conditions whereby the validity of the making and breaking type testsmay be extended to cover combinations of switch and fuses other than that (those) tested.

The switch-fuse manufacturer or the user can, on their own responsibility, avail them-selves of this extension and decide which other types of fuses can validly be used in thecombination.

The principles on which the conditions for extending the validity of the making andbreaking type tests are based are as follows:

1) Any fuse or modified fuse used in a combination shall have been certified toIEC 282-1. This is necessary not only to prove the fuse but also to provide cut-offcurrent and operating Ft data.

2) The cut-off current and operating Pt of the fuse shall be no greater than those ofthe fuse tested in the combination in order to ensure that the switch contacts cannot besubjected to unproven conditions.

3) There must be evidence that, under low over-current conditions, the switch will tripbefore any unacceptable external damage to the fuse can occur.

● in these sub-clauses a current tolerance of i6,5 % is used (i.e. W a of *IO %). Thisisbased on currant practice.

36

Page 42: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999[EC 420 ( 1990)

4) The same type of fuse striker (energy output) as that fitted to the fuse tested inthe combination shall be used in order to give assurance that the switch will trip (seealso 5.1 04).

5)1 For fuse-switches only, any change in fuse-link mass shall not invalidate the mech-anical operation.

8.3 Operation

1) The three fuses fitted in a given combination shall all be of the same type andcurrent rating, otherwise the breaking performance of the combination could beadversely affected.

2) It is vital, for the correct operation of the combination, that the fuses are insertedwith the strikers the correct way round.

3) When a switch-fuse has operated as a result of a three-phase fault, it is possiblefor:

a) only two out of the three fuses to have operated;

b) all three fuses to have operated but’ for only two out of the three strikers to haveejected.

Such partial operation of one fuse can occur under three-phase service conditionsand is not to be considered abnormal.

4) Where a switch-fuse has operated without any obvious signs of a fault on thesystem, examination of the operated fuse or fuses may give an indication as to the typeof fault current and its approximate value. Such an investigation is best carried out bythe fuse manufacturer who is usually prepared to offer such a service to users.

5) It is advisable to discard and replace all three fuses when the fuse(s) in one or twopoles of a combination has operated unless it is definitely known that no over-currenthas passed through the unmelted fuse(s).

6) Before removing or replacing fuses, the operator should satisfy himself that thefuse-mount is electrically disconnected from all parts of the combination which couldstill be electrically energized. This is especially important when the fuse-mount is notvisibly isolated.

8.4 Interlocks

Sub-clause 5.105 of IEC 298 and Clause 19 of IEC 466 apply as appropriate.

9 Information to be given with enquiries, tenders and orders

The combination manufacturer shall give, apart from the rated quantities, the followinginformation:

a) The maximum acceptable power dissipation of the combination (see 6.3. d)).

b) The maximum cut-off current that the switch has been proven to be able to deal with(see 6.101.0.1: additional conditions for test duty 1). “

c) The maximum F t that the switch has been proven to be abte6.101 .0.1 and 6.101.0.2: additional conditions for test duties 1 and 2

37

to deal with (seerespectively).

.

Page 43: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

d) The fuse-initiated opening time of the switch (see 6.101.0.3 and 6.103.4); and aiso,where appiicabie, the minimum reiease-initiated opening time of the switch (see 8.2.5).

e) The types and dimensions of the fuses which can be used in the combination.

f) Type of fuse striker (medium or heavy).

g) The rated transfer current (see 6.103.4) and aiso, where appiicabie, the rated take-over current (see 6.103.5).

h) Method of operation, whether manuai or power.

j) Filiing medium (type and amount), where applicable.

Where a user wishes to use a fuse of a type different from those iisted under e) abovebut of the same dimensions, he shouid, in addition to referring to the appiicat{on guide(Ciause 8), request the foiiowing information from the fuse manufacturer in accordancewith iEC 282-1.

k) The Pt characteristic (according to iEC 282-1).

i) The cut-off current’characteristic.

m) The maximum iength of arcing time as stipulated in 6.101 .0.3 a) 1).

n) Rated short-circuit breaking current.

o) Rated minimum breaking current.

p) Power dissipation at rated current.

q) Pre-arcing time-current characteristic.

r) Type of fuse striker (medium oi heavy).

10 Rules for transport, storage, erection and maintenance

iEC 694 appiies.

High-voltage fuses, aithough robust in externai appearance, may have fuse-eiements ofrelatively fragiie construction Fuses shouid, therefore, be kept in their protectivepackaging untii ready for installation and shouid be bandied with the same degree of careas a reiay, meter or other simiiar item. Where fuses are aiready fitted in a switch-fuse unitthey shouid be temporarily removed whiie ‘the unit ismanhandled into position:

10.1 Conditions during transport, storage and erection

iEC 694 appiies.

10.2 Erection

iEC 694 appiies.

10.3 Maintenance

iEC 694 appiies.

38

Page 44: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

---Q.

. :IS 14666:1999IEC 420( 1990)

Appendix A

Example of the co-ordination

The transformer is chosen by the user for itsload current and permissible overload current.

of fuses, switch and transformer

particular duty thus fixing values of the fuil

The maximum fauit ievel of the high-voltage system is known.

For the purpose of this example take an 11system with maximum fauit ievei of 16 kA:

a) full load current is 21 A approximately;

b) permissible periodic overload is, say,former, i.e. approximately:

kV, 400 kVA transformer on a high-voltage ,

150 ?4., on the “-5 Ye” tapping of the trans-

21 Ax1,05x1,5=33A

c) magnetizing inrush current is:

21 Ax12= 252A

maximum for a duration of 0,1 s (Clause 4 a) of IEC 787).

Site ambient air temperature is 45 ‘C, i.e. 5 ‘C above standard.

Suppose the user has dedded that a 12 kV switch-fuse combination from a certain manu-facturer wiii be used to controi and protect the transformer.

The manufacturer wiii be abie to provide a iist of the fuses which can be used in thecombination and wiii be abie to advise which of these are suitabie for the application.

This iist of fuses wiii have been drawn up by the switch-fuse manufacturer on the basis ofappropriate type tests on the switch-fuse combination to this standard and by the appli-cation of its extension of vaiidity ciauses (see 8.2.7).

Suppose he advises that a 12 kV, 40A, 16 kA (at ieast) back-up fuse of a given type froma certain fuse manufacturer is suitabie. To justify this advice, the switch-fuse manufacturerwiii have ascertained that:

# 1) The fuse can withstand the 252 A magnetizing inrush current of the transformerfor 0,1 s (Ciause 4 a) of iEC 787): he wiii normaiiy do this by examining the fuse time-current characteristic and/or consulting the fuse “manufacturer.

39

Page 45: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

4,

IS 14666:1999. d

IEC 420(1990) (

2) The normal current rating of the switch-fuse combination when fitted with the fusesis adequate to allow for periodic overloading of the transformer up to 33 A in ambientair temperature conditions of 45 ‘C (see 4 b) 1) of IEC 787). x-~

1 !!,

NOTE - The normal current rating of the combination when fitted with the fuses may not be as much as40 A especially in the higher than standard ambient conditions: temperature-rise tests carried out by the

switch-f use manufacturer or calculations based on such tests may indicate a normal current rating of, say, !

35 A in ambient conditions of 45 ‘C. This would be adequate for the application.. .

3) The pr.?-arcing current of the fuse is low enough in the 10 s region of the fuse time-current characteristic to ensure satisfactory protection of the transformer (Clause 4 c)of 1EC 787): he will normally do this by examining the fuse time-current characteristicand/or consulting the fuse manufacturer.

4) The fuses alone will deal with the condition of a solid short on the transformersecondary terminals i.e. that the maximum primary short-circuit current (in this case:

400X 100= 420A

llxmx5

based on 5 % transformer reactance) is greater than the transfer current (see 3.3.9) ofthe combination when fitted with 40 A fuses: he will do this by ascertaining the transfercurrent using the method explained in 8.2.4. Reference to Figure 10 shows that thetransfer current so obtained is only 280 A, the fuse-initiated opening time of the switchbeing assumed to be 0,05s for the purpose of this example.

5) The transfer current of the combination when fitted with 40 A fuses is less than itsrated transfer current /4 (see 4.104) which we shall suppose to be 1 000 A.

The supply authority must check that the fuse discriminates with the highest rating of alow-voltage fuse used in the event of a phase-to-phase fault occurring on the low-voltagesystem.

NOTE - This is usually the worst condition for discrimination.

As explained in Clause 4 d) of IEC 787, the intersection of the time-current characteristicsof the high-voltage and low-voltage fuses shall occur at a value of current greater than

- that of the maximum fault current on the load side of the low-voltage fuse (see Figure 11).

,

40

Page 46: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

-.&

‘d

IS 14666:1999IEC 420(1990)

Appendix B

Justification of the procedure for determining transfer current andof the parameters associated with test duty 4

B.1 Background

Transfer current is defined as the current at which, under striker operation, the breakingduty is transferred from the fuses to the switch (see first paragraph of 6. 103.4).

This occurs when, after the melting of a first fuse, the switch opens under striker operationbefore or at the same time as the melting of the second fuse, there being an inevitabledifference between the melting times of fuses.

A knowledge of this difference, AT, between the melting times of fuses permits comparisonbetween it and the striker-initiated opening time of the switch.

B.2 Mathematical determination of AT

Figure 8 shows small segments of the more probable minimum and maximum fuse time-current characteristics in the transfer current region.

The time, Tml, on the minimum characteristic is the melting time of the first fuse tooperate under a three-phase fault current, /1.

The time, Tm2, is the melting time of the second fuse to operate. It should be noted thatthis time Tm2 (see Figure 8) is shorter than the value indicated for a two-phase current of0,87 /1 by the maximum time-current characteristic as this second fuse has already seenthe three-phase fault current /1 for the time Tml.

The small segments of the time-current characteristics can be regarded as straight lines toa close approximation in log-log co-ordinates, their equation being:

logTm=-slog/+logC

defining a relationship between /and Tm such that:

/a Tm=C (1)

where a is the gradient and log C the intercept with the ordinate axis of the straight line sodefined.

41

Page 47: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

.,,

.. .4IS 14666:1999IEC 420( 1990)

Applying equation (1) to the minimum time-current characteristic, the equation for themaximum time-current characteristic will be expressed by:

la Tm=C(l+x)a (2)

where x is the tolerance on the current between the two time-current characteristics anddefined as 100 x Y..

The first fuse melts under the three-phase fault current, /1, in a time Tml, according toequation (1) for the minimum time-current characteristic such that:

/~ Tml = C (3)

After having seen the current, /1, for a time Tml, the second fuse will melt under the two-phase fault current, 0,87 /1, in a time Tm2 according to equation (2) for the maximum time-current characteristic such that:

/~ Tml + (0,87 /1) a (Tm2-Tml) = C (1 + x) a (4)

combining (3) and (4):

AT=(Trn2-Tq) =Trnl [ (I+x)a-ll

(0,87) a(5)

B.3 Practical determination of transfer current

Taking a statistically realistic tolerance for the fuse time-current characteristics of *6,5 ‘/.(*26 of *1O %) then x = 0,13.

Taking also 4 for a, which is the value commonly encountered in practice, with fuse-initiated opening times lying between 0,05 s and 0,3 s, then equation 5 gives:

4-1AT=Tml [(1 ‘0’13) ](0,87) 4

The transfer point occurs when the fuse-initiated opening time, TO, of the switch is equalto AT:

TO =AT=l,l xTmlor

Tml = 0,9 TO

Thus, the transfer current can be defined as the current which gives a melting time equalto 0,9 TO for the minimum time-current characteristic of the fuse.

42

Page 48: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420( 1990)

B.4 Type of faults invoived in the transfer current region

Pr\rnary side protection devices are particularly concerned with fauits in the secondaryterminai zone of the transformer up-stream of the secondary protection devices and oniyrareiy with secondary iine fauits except in cases of faiiure of the secondary protection or ofincorrect discrimination between the primary and secondary protection.

The primary short-circuit current arising from soiid shorts in the transformer secondaryterminai zone is expressed by:

, =loo/TSC z

where

+ = rated current of the transformer

Z = short-circuit percentage impedance of the transformer

The breaking of such fauits (soiid sheds) is associated with severe TRV vaiues which theswitch in the combination may not be abie to interrupt. Thus it is necessary for this type offauit to be cieared by the fuses oniy, i.e. the transfer current shaii aiways be iower thanthe current l~c (see Figure 9).

This condition being fuifiiied, then transfer currents correspond to fauits for which arcimpedance or fauited iine impedance reduces the magnitude of both the current and theTRV vaiues and increases the power factor.

43

Page 49: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

4,

. . !.$

IS 14666 :1999IEC 420( 1990)

u

tUc -——— ———— —. —-.

tfj = 0,15 ts

Figure 1-

Voltage

u{

o td t’ ta t

Representation of a specified TRV by a W-parameter reference lineand a delay line

———————— .

L-$”“

.

0 t3Time

Figure 2- Example of a two-parameter reference line for a TRV

44

Page 50: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666:1999IEC 420(1990)

A

[1

I

[ 1

0 A

ilI

Preferred earth point

Fuse

Alternativeeerthpoint

Figure 3- Arrangement of test circuits for test duties 1 and 2

r

m“

AI

[ 1 [ 1 [ 1

0 A o

JI

Fuse

--lI

Solid link

/////////~I

r

1’\

[ 1

J o

Prefemed earth point Alternative earth pornt

Figure 4- Arrangement of test circuits for test d@ 3

45

Page 51: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666 :1999

IEC 420( 1990)

Fuse

+=-FL””Preferred earth point

Test duty No. 4Figure 5a

Preferred eetth point

Solid link

Load

A

[1

I

I I

1

1 J

Atternetwe earth point

ti”

Anern#we earth point

.

I

,

Test d@y No. 5Figure 5b

Figure 5- Arrangement of test circuits for test duties 4 and 5

46

Page 52: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

Is 14666 :1999EC 420( 1990)

c

U1— = Voltage of pole 121’2

U2— = Voltaqeofpole221 ‘3

U3— = Wltaqe of pole 321’2

—-

J

b’414]tU3- -—

1—.

Pole 1

Fuse did not operate

Pole 2

tPole 3

(J1 U2 U3—— .. 21/2+ –+21’2 21’3

3

IFirst fuse to clear

J

Average WIlrage of poles 1.2 and 3

00- Instant of opening of mechanical switching device

.

Figure 6- Determination of power-frequency recovery voltage

47

Page 53: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666 :1999IEC 420( 1990)

Time

0,9 times 0,05 s

(0,05s fuse-

initiated

opening time I

x sm In

cL- S6

I/. Current

...@-

.4

.

Figure 7- Practical determination of transfer cument

48

Page 54: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666 :1999IEC 420(1990)

Probable maximum time-current characteristic

/ Probable minimum time-current characteristic

o

0,871, /1 I

Figure 8- Probable maximum and minimumtime-current charactm”stics of fuse

,

49

Page 55: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666 :1999IEC 420( 1990)

Time

ISc Current

Figure 9- Tmnsfer ourrent in relation to the primaryfautt current /= due to a solidshort in the transformer secondary terminal

50

Page 56: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

~.,-—.—

lime ISI

0,1

0,9 times O,@s

(0,05 S fuse.

initiated

opemng time)

0,045 s

21 33

1II\\\\\\\\\\\\\\

: \0 \=

? \0 \

*~ \In \

.s’E \

~ \

\

IS 14666 :1999IEC 420( 1990)

252 280 420 1000 kfent (A)1,

Figure 10- CharaCtefi@cs retating to the protection of an 11 kV -400 kVA transformer I

51

Page 57: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

Is 14666 :1999IEC 420( 1990)

Time t.s

high-voltage fuse

Minimum timelcurrent characteristic of

Maximum operating timeof low-voltage fuse(referred to high-voltageside]

Maximum fault current on low-voltage side

(referred to hi@-vokage side)

420

Curreru (A)

Figure 11 - Characteristics fordetennining take-over mnnt

52

Page 58: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

IS 14666 :1999IEC 420( 1990)

t Fuse

;.,

L

Maxmun break time (iieased by the maximumK4ay opemtiq time if operated by external over-

\ gment I&@\

-\\

K \’

K\\

Minimum opening time (increased bv 0,02s ~operated tryexternal over-current relays.}

\

\

\

\

\\Maximum operating time for maximum

rated current

-\

Minimum pre-arcing time

*

‘ Prospective current

.J-1,.

J

Figure 12- Characteristics for determining take-over current

Page 59: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

~Gonrmueu from secorru cover J

International Standard

IEC 282-1:1985 High-voltagefuses, Part 1: Current-limitingfuses

IEC 298 : 1981 A,C. Metalenclosed switchgear and control-gear for rated voltages above 1 kVand up to and including 72.5 kV

IEC 466:1987 A.C. lnsulation-enclosed switchgear and control-gear for rated voltages above 1 kVand up to and including 38 kV

IEC 694:1980 Common clausesfor high-voltage switchgear andcontrolgear standards

IEC 787:1983 Application guidefor the selection of fuse-links ofhigh-voltage fuses for trans-former circuit applications

Corresponding Indian Standard

IS 9385 ( Part 1 ) :1979

IS 3427:1997

IS 14659:1999

IS 12729:1988

IS 12534:1988

Degree of

Equivalence

Equivalent

Identical

Identical(Under print)

Equivalent

do

Only the English language text in the International Standard has been retained while adopting it inthis Indian Standard.

For the purpose of deciding whether a particular requirement of this standard is complied with, thefinal value, observed or calculated, expressing the result of a test or analysis, shall be rounded offin accordance with IS 2:1960 ‘Rules for rounding off numerical values ( revised)’. The number ofsignificant places retained in the rounded off value should be the same as that of the specifiedvalue in this standard.

Page 60: IS 14666 (1999): High-voltage Alternating Current Switch-fuse … · 2018. 11. 15. · IEV 441-14-12. 3.1.5 Fuse-base fuse-mount IEV 441-18-02. 3.1.6 Striker IEV 441-18-18. 3.1.7

Bureau of Indian Standards

1*L

.,.*“

,.:,

BIS is a statutoxy institution established under the Bureau ofIndian StandardsAct, 1986 to promote harmoniousdevelopment of the activities of standardization, marking and quality certification of goods and attending toconnected matters in the country.

Copyright

BIS has the copyright of all its publications. NOpart of these publications maybe reproduced in any form withoutthe prior permission in writing of BIS. This does not preclude the free use, in the course of implementing thestandard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating tocopyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewedperiodically; a standard along with amendments is reaffirmed when such review indicates that no changes areneeded; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standardsshould ascertain that they are in possession of the latest amendments or edition by referring to the latest issueof ‘BIS Handbook’ and ‘Standards : Monthly Additions’.

This Indian Standard has been developed from Doc: No. ET 08 (5014).

Amendments Issued Since Publication

Amend No. Date of Issue Text Affected

BUREAU OF INDIAN STANDARDS.Headquarters:

Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telegrams: ManaksanstiiaTelephones :3230131, 3239402, 3233375 ( ,Common to,

all offices )

Regional OffIces: Telephone

Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg{

3237617NEW DELHI 110002 3233841

Eastern : 1/14 C. I. T. Scheme VII M, V. I. P, Road, Maniktola{

3378499, 3378561CALCUTTA 700054 3378626, 3378662

Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022{

603843602025

Southern : C. 1. T Campus, IV Cross Road, CHENNAI 600113{