+ All Categories
Home > Documents > is.2527.1984

is.2527.1984

Date post: 03-Jun-2018
Category:
Upload: pradeepq
View: 212 times
Download: 0 times
Share this document with a friend

of 21

Transcript
  • 8/12/2019 is.2527.1984

    1/21

    Disclosure to Promote the Right To Information

    Whereas the Parliament of India has set out to provide a practical regime of right to

    information for citizens to secure access to information under the control of public authorities,in order to promote transparency and accountability in the working of every public authority,and whereas the attached publication of the Bureau of Indian Standards is of particular interestto the public, particularly disadvantaged communities and those engaged in the pursuit ofeducation and knowledge, the attached public safety standard is made available to promote thetimely dissemination of this information in an accurate manner to the public.

    !"#$% '(%)

    !"# $ %& #' (")* &" +#,-. Satyanarayan Gangaram Pitroda

    Invent a New India Using Knowledge

    /0 )"1 &2 324 #' 5 *)6 Jawaharlal Nehru

    Step Out From the Old to the New

    7"#1 &" 8+9&") , 7:1 &" 8+9&") Mazdoor Kisan Shakti Sangathan

    The Right to Information, The Right to Live

    !"# %& ;

  • 8/12/2019 is.2527.1984

    2/21

  • 8/12/2019 is.2527.1984

    3/21

  • 8/12/2019 is.2527.1984

    4/21

  • 8/12/2019 is.2527.1984

    5/21

    IS:25 7-1984

    I ndi an St andard

    CODE OF PRACTICE FORFIXING RAINWATER GUTTERS ANDDOWNPIPES FOR ROOF DRAINAGE

    Fi rst Rev i si on

    Building Construction Practices Sectional Committee, BDC 13

    Ch&ialZaSHRI. C. P. MALIK

    C-4/38, Safdarjung Development Area,New Delhi-118616

    luembsrs Reprew xt i ngSHRI. P. D. AOARWAL Public Works Department, Government of Uttar

    SHXI R. K. MATHUR ( Alternate ) Pradesh, Lucknow

    SHBID.R. BATLIVALASHBX B. K. C~AKBABOBTY

    8habha Atomic Research Ccntre, BombayHourin

    Lt tfand Urban Development Corporation

    , New Delhi

    CHIEFSER;~~.~~~EL ( Alternufe )

    ( BLOUS ) Public Works Department, Government ofTamil Nadu, Madras

    SUPERI~~TEDTDINQ ENOINEER( SPECIAL UILDING CIRCI.E) ( Altrrnute )

    CHIEF ENQIN~~H-CUM-ADDITIONAL Public Works Department, Government ofSECRETARY ( Band R )

    EXECUTIVE ENUINEER Alternate )Rajasthau, J aipur

    CEIEF ENQINEER ( TRAININO )SUPEBI~~TEI~DINO ENGINEER

    Central Public Works Department, New Delhi

    SaRI d T;;;~y~g Aftmde )Engineer-in-Chiefs Branch, Army Headquarters,

    New DelhiSEBI A. V. GOPALKBI~HNA ( Altermfc )

    DIRSOTOB, AROHITEOTWE Research, Desigus and Standards Organization

    J OMT DIREOTOR,AF.CJEITEC-( Wit&try of Railways ), Luckuow

    TUB= (Altsmalr )

    (_npap2)

    INDIAN STANDARDS INSTITUTIONThis publication is protected under the Irafiaa @yrf@ Aci ( XIV of 1957 ) andigoduadoa-& whole or in part by any means acept with writteu permission of tbcpublisher shall be deemed to be au iufringement of copyright uudv the said Act.

  • 8/12/2019 is.2527.1984

    6/21

    IS t 2527 - 1984

    Continued m page 1 )

    M embers Reprwnti ng

    SHRI s. s. GILL Public Works Department, Government ofPunjab, Chandigarh

    SHRI M. KARTIKAYAN Builders Association of India, BombaySHIXI R. L. KUMAR Institution of Surveyors, New Delhi

    SHRI V. G. PAT~ARDEAN ( AItcmutc )SHRI M. Z. KIJRIGN Tata Consulring Engineers, BombaySHRI G. K. MAJUMDAR Hindustan Prefab Ltd, New Delhi

    SHRI H. S. PASRICBA ( Altcrnalc )SHRI R. C. MANQAL Cent;~or~;~lding Research Institute ( CSIR ),

    SHRI J. S. SHARM_4 (Alternate)SHRI B. V. B. PA1 Concrete Association of India, Bombay

    SRRI P. SRINIVASAN ( Altcrnata)SHRI P. K. PANDARESHRI K. S. PR~THI

    State Bank of India, BombayFore;)tutesearch Institute and College+ Dehra

    SHRI S. G. RANADIVE Indian Institute of Architects, BombaySH I ~I RUM M Y SH ROFF ( Alternate )

    Bureau of Public Enterprises, Mmistry ofEPRESENTATIVEFinance

    Central Road Research Institute, New DelhiLife Insurance Corporationof India, BombayNational Buildings Organization, New Delhi

    National Buildings Construction Corporation Ltd.New Delhi

    REPRESENTATIVEREPRESENTATIVE

    &RI K. S. SRINIVASANDEPUTY DIRECTOR ( Alternate )

    SHHI SUSHIL KUMNR

    SHRI S. R. TAMBESHRI B. T. UNWALLASHRI G. VENKATESULU

    Public Works Housing Department, Bombay

    The Institution of Engineers ( India), CalcuttaMinistry of Shipping and Transport ( Roads

    Wing ), New Delhi1SHRI M. V, SASYRY ( Alternate,

    SARI G. RAMAN, Director General, IS1 (Ex-ofi Membn)Director ( Civ Engg )

    SERI A. K. SAINIAssistant Director ( Civ Engg), IS1

    Covering, Veneering and Glazing Subcommittee, BDC 13 : 10

    Convenrr

    SER; ,J. R. BHALLA Indian Institute of Architecta, Bombay

    M embers

    ARCHITECT, WD Public Works and Housing Department, Govem-ment of Maharashtra, Bombay

    SHRI S. R. VAIDYA ( Altrrnatr )

    ( Continued on page 15 )

    2

  • 8/12/2019 is.2527.1984

    7/21

    XS : 2527 - 1984

    I ndi an St andard

    CODE OF PRACTICE FOR

    FIXING RAINWATER GUTTERS ANDDOWNPIPES FOR ROOF DRAINAGE

    Fi r st Rev i si on

    0. FOREWORD

    0.1 This Indian Standard ( First Revision ) was adopted by the IndianStandards Institution on 14 March 1984, after the draft finalized bythe Building Construction Practices Sectional Committee had beenapproved by the Civil Engineering Division Council.

    0.2 Rainwater gutters and ,downpipes are essential for prompt removal ofincident rainfall on the roof. Efficient roof drainage is an important pre-requisite for the economic maintenance of a building. Installation ofrainwaterposition an dg

    utters and pipes require careful attention to their capacity,alignment, water-tightness,

    firmness of support, etc.

    accommodation for expansion,

    This standard is intended to give guidance withregard to these details of work.

    0.2.1 This standard was first published in 1963. This is being revisedto update the methods being followed for installation and efficient func-tioning of rainwater gutters and pipes. In this revision the use of in situconcrete gutters has been discontinued since they are normally not used.Further the fixing details of different types of gutters and pipes has beendealt in detail. The sizing of rainwater pipes has been modified.

    9.3 For the purpose of deciding whether a particular requirement ofthis standard is complied \yith, the final value, observed or calculated,expressing the result of a test or analysis, shall be rounded off in accordancewith IS : 2-1960*. The number of significant places retained in therounded off value should be the same as that of the specified value inthis standard.

    1. SCOPE

    1.1 This standard covers the constructional details of rainwater gutter8and downpipes and their fittings for roof drainage.

    Rula fbr rounding off numerical valua ( mu d).

    3

  • 8/12/2019 is.2527.1984

    8/21

    IS : 2527 - 1984

    2. MATERlALS

    2.1 Rain-WaterIS. 1270-1379 or.

    Pipes and Fittings-These shall conform toIS : 1626 ( Part 1 )-196Ot or IS : 1239 ( Part 1 )-1979:.

    2.1.1 Jjownpipes shall be of cylindrical shape, unless otherwise specified.

    2.1.2 Rainwater gutters may also I)e constructed in concrete which islined usually wifh bituminous material or with burnt clay products.Gutters may also be made of galvanized iron sheets fiat less than 1.25 mmin thickness and shall conform to IS : 277-19773. The gutters shall beseqlicircular in section with a width at top about twice the diameter ofthe do\vnpipe ( see Fig. 1 ).

    rMAIN RAFTER

    OOF COVERING

    CONCRETE GUTTER

    Fro. I TYPICAL DETAILS OF COUCRETE UTTER FOR SLOPBD ROOF

    ----*Specification for CM iron rainwater pipes and fiittings (rrcendrmiria~ ).tSpvification Ew asbestos cement building pipes and pipe fittings, gutters and gutter

    fittings and roofing fittings: Part 1 Piper and pipe fittings (J rst revision ).:Speciiication for mild steel tubes, tubular atxl other wrought rtcel fittingx Part 1

    Mild stl.el tubes fjourfh rrr ir ion .

    fi.Spccificatioo [or galvanirrd steel rheets ( plain and conugatad ) ( ~k~rrotfon ).

  • 8/12/2019 is.2527.1984

    9/21

    IS t 2527 - 1984

    2.2 Stays for Sheet Metal Gutters

    22.1 Stays shall consist of metal tubes or other equivalent distance-pieces or may be an integral part of the supporting bracket, provided thatthe gutters is adequately reinforced to withstand all normal conditionsof use. The size of stays shall not be less than the follqwing values, andalternative designs shall be of equivalent strength:

    a) For nominal size of gutter 12 mm diameter tube of thicknessless than 120 mm not less than that of the gutter

    b) For nominal size of gutter 16 mm diameter tube of thicknessabove 120 mm not less than that of the gutter

    2.2.2 Stays forming part of the supporting bracket shall be of suchdesign that the assembly of bracket and stay is securely fixed in posit-ion.In all cases, the position of the stay shall be such as to interfere as littleas practicable with the effective capacity of the gutter.

    3. NECESSARY INFORMATION

    3.1 Forgutters,

    a)

    b)

    3.2 All

    the efficient planning and installation of rainwater pipes anddetailed information with regard to the following is necessary:

    The maxiurn intensity of rainfall for which the roof drainagesystem is to be designed; and

    Local bye-laws, if any, governing house drainage, which willaffect the design and installations of rainwater pipes and guttersi

    information as in 3.1 shall be made available to those who are._ ^ ^ .responsible br tixing rainwater pipes and gutters.and instrtictions shall also be fur.nished.

    Necessary drawingr

    4. STORAGE AND HANDLING OF MATERIALS

    4.1 The storage and handling of gutters and pipes shall be done inaccordance with IS : 4082- 1977

    5. DESIGN CONSIDERATIONS

    5.1 Gened- The roof of a building shall be so designed, censtrtlctedand framed aa to permit effectual drainage of the rahwatkr by sufficient:number of pipes and gutters of adequate size, so arranged, jointed and

    Sxed a to ensure quick carriage of iainwater away from the roofwithout causing damMa.

    uomme8d8tbu 08 rtackitbg aid atomga of comtruction m tcrhlr at rite (Jatrairiir ).

    5

  • 8/12/2019 is.2527.1984

    10/21

    IS t 2527 - 1984

    5.X.1 Capacity- The gutters of downpipes shall have sufficient cross-sectional area and slope to ensure collection and removal of water even inthe case of the heaviest rainfall without risk of dangerous accumulation.The orientation of the building and the exposure of the site may also

    affect the quantity of rainfall which the roof receives and so attentionshould also be paid to such factors.

    5.2 Rainwater Gutters

    5.2.1 Slope The slope for the roof gutters shall normally be not lessthan 1 in 150.

    5.2.2 Flow Capacity - The flow capacities for gutters with the minimumslope stated in 5.2.1 and with outlet at one end will be as given in

    Table 1.

    TABLE 1 FLOW CAPACITIES FOR LEVEL GUTTBRSWITH OUTLET AT ONE END

    SIZE FLOW N Lrralrs PEB MINUTE N VARXOUS TYPES or GUTTESS

    Sheet Steel Cast I;oioz Half Sheet Steel cast Iron _Tor Asbestos or Asbestos

    Cement -Half

    Round

    Cement - QgeeOgee

    (1) (2) (3) (4) (5)mm75 35 25 -

    loo 70 55 90 75

    115 95 70 125 115

    125 125 90 150 145

    150 195 150 240 220

    5.2.21 Efect ofbsndswill be reduced.

    Where gutters have bends, tbt flow capacityIn the case of right-angled bend the reduction of flow

    capacity will be about 25 percent.

    5.222 Ef fect of out and down pez The shape, size and position ofthe outlet and downpipe will .a tFect the flow capacity of the gutter.

    Round-cornered outlet will give a smoother flow than sharp-cornered ones.The position of the outlet will also affect the flow capacity of the gutterbut in deciding the location of-the outlet, several factors, such as ease ofconnection to the disposal ryatem and the appearance, have a+ to beconsidered. When the outlet. is placed centrally in the length of a gutter,capacity required will be one-half of that needed for an end-outlet.

    6

  • 8/12/2019 is.2527.1984

    11/21

    IS : 2527 1984

    5.2.23 Ef ict of roof dgc in dticharging the water in to the gutter- Themanner in which the water leaves the edge of a roof varies with the kindof roof covering used, and this will influence the location at which thegutters shall be fixed. Where, as for instance in a slate roof, the waterleaves the edge with very little spread to front or rear, the position of the

    gutter may be centrally under the edge, on the other hand where thewater leaves the edge with a wide spread; such as in the case of claypantiles ( with sharp upper corner to the edge ), the gutter shall be closeto the edgewith its centre slightly forward to the under edge of the roof.Where the lower corner of the roof edge is rounded, the water may bedeflected more to the rear, and the centre of the gutter may preferablyalso than be placed slightly to the rear. The most satisfactory roofwill be one with the upper corner round and the lower corner sharp.

    edge

    5.3 Size8 of Rainwater Pipe85.3.1 The sizes of downpipes suitable for variable gutters shall be as

    given in Table 2 with a variation off 5 mm.

    TABLE 2 SIZES OF DOWNPIPES SUITABLE FOB VARIOUSSIZES OR HALF-ROUND GUTTERS

    SIZX or PIPEr--- ---A---_

    For Sharp Cornered Outlet-----7

    For Round Cornered Outlet~-----~---)

    With outlet With outletr_---_*-_-_-~With outlet With outlet

    at one end at any inter- at one endmediate po-

    at any inter.

    sition in themediate po-sition in the

    length ofpipe

    length ofpipe

    mm mm mm mm mm

    75 50 50 50 50100 65 65 50 50115 65 75 50 65125 75 90 65 75150 90 100 75 100

    NOTIE Sizes other than those specified in the table may be adopted, if specificcalculations for flow prove their suitability.

    5.3.2 Rainwater Pi@-with Table 3.

    Sizes of rainwater pipes shall be in accordance

    5.5.5 The pipes shall be so designed as to give a velocity of flow notless than 1 m/a where running half full. The maximum velocity shall notexceed 25 m/s.

    7

  • 8/12/2019 is.2527.1984

    12/21

    IS I 2527 - 1984

    TABLE 3 SIZES OF RAINWATER PIPES FOR ROOF DRAINAGE

    lz.DTA CJP I'IPE AVERAOERATEO~RAIN~ALLI~ mm/h

    ----------- ~---_-____-__I)ml11 50 55 100 125 150 200

    Roof Areaa, m*

    i) 50 13.4 8.7 6.6 5.3 4.4 3.3ii) 65 24.1 160 120 96 8.0 6.0

    iii) 75 40.8 27.0 20.4 ,I@3 13.6 IO.2iv) 100 85.4 57.0 42.7 34.2 28.5 21.3v) 125 - 80.5 64.3 53.5 40.0

    vi) 150 - - - - 83.6 62.7

    5.3.4 A bell mouth inlet at the roof surface is found to giver betterdrainage effect provided proper slopes are given to the roof surface. Thespacing of pipes depends on the position of windows and openings but6 m apart is a reasonable distance.

    5.4 Water-Tightness - All junctions and joints shall be thoroughlywater-tight, riveted, belted and soldered. Joints between successivelength of gutters shall have an overlap of at least 50 mm. The dropin the overlap of the gutter shall always be in the direction of the fall.Ends of guttering rhall be closed with galvanized sheets not less than1.215 mm in thickness to fit the section and made water-tight.

    Junctions with downwater pipes shall be made water-tight.

    5.5 Strength and Stability

    5.5.1 Gutters if located at the exterior like the eaves and roof edgeswill be subject to high wind velocities. The effect of zones of very lowpressure for certain angles of incidence of the wind shall, therefore betaken into account in the design and reference may be made to 1s : 875-1964.. Gutters shall be fixed 25 mm below the edges of the roof supportedwith brackets aLt about 1.25 m intervals. Roof gutters if required mayalso be designed for occasional live loads which are likely to occur duringerection and other operations.

    5.6 Allowance for Expansion of Shrinkage

    5.6.1 Variations in temperature, and for materiala other than metal,differences in relative humidity, will cause linear changes resulting indisplacements of gutters and pipes in relation to the building, and vallowance shall be made for free expansion to prevent any undue stressesin them or blistering and cticking of the outer finish.

    *Code of practice for structural s&t; of build Loading aadmda (r d).

    8

  • 8/12/2019 is.2527.1984

    13/21

    5.6.1.1 Provision made for expansion of gutters (see 5.6.1.2 ) shallccommodate their linear changes. Where the expansion accommodateds less than 20 mm, the length of the gutter between the expansion jointshall not exceed 30 m for sheet steel, asbestos cement or cast iron gutters.

    5.6.1.2 The expansion devices for gutters may be provided as follows:

    a) For sheet metal gutters the expansion joints shall beprovided as in Fig. 2;

    2A FREE END :B FIXED END

    2G

    ENLARGED

    SECTION XX

    DETAIL ED VIEW OF 20

    FIG. I TYPICAL DETAILS OF EXPANSION OINT FOR Smm METALGIJ TTRR LINING

  • 8/12/2019 is.2527.1984

    14/21

    IS : 2527 - 1984

    b) For bituminous lining over wooden or similar backing,joint shall also be provided fsr lateral expansion as inFig. 3; and

    c) For concrete gutters expansion joints shall be provided in

    the same manner as for reinforced concrete slabs.

    FIG. 3 TYPICAL DETAILS FOR ACCOMMODATION OF LATERALEXPANSION IN FLEXIBLE LII~ING IN GUTTERS

    6. PROGRAMMING OF THE WORK

    6.1 The rainwater pipes shall be fixed to the outside of the external wallsof the building or in recesses. or chases cut or frame in suchexte*mal wall.Work to the extent necessary for supporting the rainwater fittingsproperly in position shall be completed before the person entrusted withthe job of fixing rainwater gutters and pipes starts his work. Any plasterfinish in building work near the location of the downpipe shall becompleted before fixing of the downpipe. Hold fasts an.d clamps for thepipes may also preferably be fixed to the wall before plastering, so as toavoid disturbing the plaster finish later.

    7. FIXING DETAIES

    7.1 Rainwater Gutters

    7.1.1 Asbestos Cement Gutters - Gutters shall be laid with a minimumfall of 1 in 150 which should be increased where possible. Gutters shall

    be true to line and slope and shall be laid with the requisite accessoriessuch as drop ends, stop ends, nozzles, angles and union clins as directed.The size of outlet of drons ends and nozzles shall bethe rainwater.pipes into-which they discharge water.

    10

    same as the size ofThe requisite slope

  • 8/12/2019 is.2527.1984

    15/21

    15 I 2527 1984

    in the gutter shall be given in the line of brackets. The brackets shallbe placed at not more than 900 mm centre.

    7.1.1.1 Socketed gutters shall be supported with a bracket close tothe socket and another in the centre of the gutter. Plain-ended gutters

    shall be supported with a bracket on either side of each joint; and forgutters of large size, one extra bupporting bracket in the centre of thegutter shall be fixed.

    7.1.13 Brackets shall be fabricated from mild steel flats and mildsteel rods see Fig. 4 ). All brackets shall be provided with a suitablemeans of securing the gutters in position at the back.

    MS ANGLE OR

    WOODEN PURLIN

    MS GUTTER CLAMPS

    ONEON EITHER SIDE

    4A VALLEY GUTTER

    MS ANGLE OR /

    WOODEN PURLIN

    MS FLAT GUTTER

    CLAMPi /

    48 HALF ROUND GUTTER

    FIG. 4 FIXING OF ASBESTOS CEMENT GUTTERS

    7.1.1.3 The angular space between the socket and the spigot shall befilled with a few turns of spun yarn soaked in bitumastic jointingcompound. It shall be pressed home by means of a caulking tool. More

    11

  • 8/12/2019 is.2527.1984

    16/21

    IS, t 2527 - 1984

    skeins of yarn shall be wrapped, if necessary, and well rammed home.The joint shall then be finished with bitumastic compound at an angleof 45.

    7.1.2 Shset Metal Gutters These gutters shall be fabricated fromgalvanized iron sheets not less than 1.25 mm in thickness and may bestiffened with stays where necessary. The spacing of stays should notexceqd 400 mm. Stays of the tubular pattern shall be soldered in positionin the gutter.

    7.1.2.1 Jointing All joints shall be lapped and soldered for at least40 mm in the direction of flow. In case where the joints are soldered, thejointing faces of sheet metal gutters shall be primed with solder to ensurerunning of the jointing metal. Soldering of the resulting joint throtrghout

    the full girth of the gutter and to the full extent in the lap shall beensured. Jointing may also be done by press-folding of the jointing faces.

    7.1.2.2 Fixing Gutter shall be laid with a minimum fall of 1 in150. All gutters shall be supported at centres not exceeding 750 mm andsupporting brackets or screws shall normally coincide with alternate stays.Where brackets are to be fixed to the side of rafters, they shall be bent toshape and fixed rigidly to the sides of rafter with 10 mm dia bolt.The brackets shall lap with rafter not less than 300 mm and connectingbolts shall be at 120 mm centres. Where the brackets are to be fixed tothe purlins the brackets shall be bent to shape with one end turned atright angle and fixed to the purlin face with 10 mm dia bolt, nut andwasher. The perpendicular over hung portion of the bent to shape shallbe fixed to the brackets with 2 No. 6 mm dia bolt. The requisite slope inthe gutter shall be given in the line bracket. The brackets shall be placedat not mol;e than 1 200 mm. For connection to down take pipes, a properdrop end or funnel shaped connecting piece shall be made out of sheetof the same thickness as the gutter and riveted to the gutter the otherend tailing into the socket of the rainwater pipe. The gutter when fixed

    shall be true to line and slope and shall be water-tight.

    7.2 Rainwater Pipes

    7.2.1 Cast Iron Pipes The pipes and fittings shall be fixed in verticalalignment unless otherwise specified. The pipe and fittings shall besecured to the walls. Wooden cleats shall be inserted so that the pipesand fittings are kept at a distance of not less than 30 mm from the wall tofacilitaLe cleaning, painting, etc. If not provided with lugs, the pipes

    shall be secured to the wall at all joints by means of mild steel or castiron holder bat clamp (see IS : 1230.1979* ). Pipes which are provided

    ?Spccifc*tion for cut iron rainwater piper uid fitting8 ( srcod rmisioa.

    12

  • 8/12/2019 is.2527.1984

    17/21

  • 8/12/2019 is.2527.1984

    18/21

    I S : 2527 - 1984

    The joint shall then be finished with bitumastic compound at an angleof 450.

    7.23 Sheet Metal Pipes The pipes shall be held by clamps fixed tothestructure by means of wood screw inserted into suitable wall plugs.

    Where it is required to fix the pipe clear of the wall, a hardwood blockshall be used and shall be secured in place by screws inserted intosuitable wall plugs. The overall size of the block shall be the same asthat of the ears of the pipe so ag to afford full support to their entiresurface see Fig 6)

    /ROOF COVERING

    WALL

    PLATE

    /WOODEN BATTEN

    SHEET ETALGUTTER

    STEEL EIRACKETS(AT SUITQLE

    INTERVALS

    3 mm mtn I_FIG. 6 A TYPICAL DETAIL OF FIXING OF SHEET METAL

    GUTTERS AND DOWNPIPES FOR SLOPED ROOF

    8. INSPECTION AND MAINTENANCE

    8.1 All gutter pipes and sockets shall be carefully examined for defectsbefore they are installed and also on completion of the work. Each pipeshall be rung with a hammer or mallet and those that do not ring trueand clear be rejected.damage and blockage.

    Sound pipes shall be carefully stored to preventCast iron pipes shall be carefully examined for

    damage of protective coating.

    8.2 The gutters and pipe shall be inspected at regular intervals and anydefect discovered shall be made good.

    14

  • 8/12/2019 is.2527.1984

    19/21

    IS r2527 -1984

    ( Continued from page 2 I

    Mmbns RepresentingSHRI S. K. CEANDA Public Works Department, Government of West

    CHIEFARCHITECT

    Bengal, Calcutta

    Central Public Works Department, New DelhiSENIOR ARCHITICT H and TP ) II Alternate )SERI G. K. DAMANI Alumilite Pvt Ltd, Calcutta

    SHRI V. MISERA ( Alternate)SHRI S. P. GCPTA

    SHRI C. V. CHALAM Alternate )Hindustan-Pilkington Glasr Works Ltd, Calcutta

    SHRI T. N. GUPTA Cent;raoryezding Research Inatitute (CSIR ),

    SARI N. K. SAN~RARI ( Alternate )SHRI G: R. JOEHI

    SHRI P. SRINIVASAN ( Altematr )Concrete Association of India, Bombay

    SERI R. L. KUMARSEEI P. J . MEETA

    The Institution of Surveyors, New DelhiThe Imtitution of Engineers ( India ), Calcutta

    SHRI B. NATARAJ AN Kent Ceramic Tiles Co Pvt Ltd, MadrasSHRX K. S. PRUTHI Foreat Research Institute and Collegea, Dehta

    DunSHRI H. K; RAKHRA Engineer-in-Chiefs Branch, Army Headquarters,

    New DelhiSHRI J . RAMAMURTHY ( Alternets )

    SHRI K. S. SR~IVASANSERI A. K. LAL ( Alternate )

    National Building Organization, New Delhi

    SHRI SUBRATO RAY Balmer Lawrie and Co Ltd, CalcuttaSRRI K. SUBYANARAYANAN

    SERX AXJAN SEN ( Alternate )Indian Aluminium Company Lid, Calcutta

  • 8/12/2019 is.2527.1984

    20/21

    INDlAN STANDARDS

    ON

    COVERING, VENEERING AND GLAZING

    IS:

    1414-1962 Code of practice for fixing wall coverings1649-1962 Code of practice for design and construction of Rues and chimneys for

    domestic heating appliances (jrst revision1946-1961 Code of practice for use of fixing devices in walls, ceilings and floors of solid

    construction2441- 1963 Code of practice for fixing ceiling covering2527-1984 Code of practice for fixing rainwater gutters and downpipes for roof

    drainage ( f;rsr &An )3548-1966 Code of practice fot glazing in buildings4 01 ( Part l )-1967 Code of practice for external facing and veneers: Part 1 Stone

    facing1401 ( Part 2 )-1967 Code of practice for external facing and veneers: Part 2 Cement

    concrete facing4101 ( Part 3 )-1968 Code of practice for external facing and veneers: Part 3 Wall

    tiling and mosaics4407-1967 Code ofpractice for reed walling5119 ( Part l )-1968 Code of practice for laying and fixing of slopped roof coverings:

    Part 1 Slating10439-1983 Code of practice for patent glazing