Date post: | 14-Apr-2018 |
Category: |
Documents |
Upload: | muthoot2008 |
View: | 216 times |
Download: | 0 times |
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 1/34
IT 21
Candidate Code No.
For Board Use Only
Result
Date
Int
Result
Date
Int
ELECTRICAL INSPECTOR EXAMINATION
20 November 2010
QUESTION AND ANSWER BOOKLET
Time Allowed: Three hoursINSTRUCTIONS – READ CAREFULLY
You have 10 minutes to read this paper but do not start writing until you are told to doso by the supervisor.
Write your Candidate Code Number in the box provided above. Your namemust NOT appear anywhere in this paper.
Answer all questions.
The pass mark for this examination is 60 marks.
Use a pen for written answers. Do not use pencils or red pens.
Drawing instruments and pencils may be used when diagrams are required. Marks areallocated on the basis of correctness.
Do not use correcting fluid or correcting tape.
Non-programmable calculators may be used.
It is recommended that the reference source for your answers be included in thespace provided if a question can be answered from the Act, Regulations, Standard orCode of Practice. However, just stating a reference only will earn no marks.
For calculation questions all workings, including formulae, must be shown to gain fullmarks.
Warning – You could get 0 marks for any question, or part of a question, if you showanything hazardous or dangerous in your answer.
You may need to use the following documents in this examination:
Electricity Act 1992 reprint dated 2008 and The Electricity Amendment Act 2006
or The Electricity Act 1992 reprint dated 1 April 2010 Electricity (Safety) Regulations 2010 AS/NZS 3000:2007 and Amendment No 1
AS/NZS 3001:2008 Amendment A
AS/NZS 3004.1:2008 AS/NZS 3760:2003 and Amendment No 1; or AS/NZS 3760:2010
AS/NZS 3019:2007 NZECP 34; NZECP 35; and NZECP 51
PLEASE HAND THIS PAPER TO THE SUPERVISOR BEFORE LEAVING THE ROOM
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 2/34
IT21 QUESTIONS – 20 NOVEMBER 2010 2
Question 1
(a) The Electricity (Safety) Regulations sets requirements for electrical safety
when work is carried out on works, installations and appliance. Refer to the
Regulations and state what a person must ensure when doing work in an
electrical installation.(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(b) The Electricity (Safety) Regulations places requirements on a person whodesigns an electrical installation.
Refer to the Regulations and state what outcome the person’s installation
design must achieve.(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(c) While inspecting an electrical installation you discover a hazard that youconsider to be an immediate danger to life. The Electricity (Safety)
Regulations requires you to notify the Secretary of the danger.
State the other person the Electricity (Safety) Regulations requires you tonotify.
(1 mark)
____________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 3/34
IT21 QUESTIONS – 20 NOVEMBER 2010 3
Question 1 continued
(d) A person working under an employer licence has issued a Certificate of
Compliance for prescribed electrical work carried out.
Refer to the Electricity (Safety) Regulations and state:
(i) For how long must a copy of the Certificate of Compliance be retained?
(½ mark)
________________________________________________________
Ref: …………………………………………..
(ii) Who must retain the copy of the Certificate of Compliance?
(½ mark)
________________________________________________________
Ref: …………………………………………..
(e) There are certain circumstances under which a registered electricalinspector cannot inspect prescribed electrical work.
Refer to the Electricity (Safety) Regulations and state whether a registeredelectrical inspector has committed a grade A offence by inspecting work
that that inspector has certified on a certificate of compliance. State a
reason to support your answer.
(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 4/34
IT21 QUESTIONS – 20 NOVEMBER 2010 4
Question 1 continued
(f) You have carried out an inspection of a new low voltage electrical
installation.
Refer to the Electricity (Safety) Regulations and state the TWO aspects thatthe inspection is required to ensure.
(1 mark)
(1) ________________________________________________________
________________________________________________________
________________________________________________________
(2) ________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(g) A person is working on a low voltage electrical installation that is isolated
from the power supply. There is a risk of unintentional connection to the
power supply.
Refer to the Electricity (Safety) Regulations and state the TWO courses of
action the person must take to prevent an unintentional connection of thepower supply.
(1 mark)
(1) ________________________________________________________
________________________________________________________
(2) ________________________________________________________
________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 5/34
IT21 QUESTIONS – 20 NOVEMBER 2010 5
Question 1 continued
(h) Refer to the Electricity (Safety) Regulations and state who the Secretary
may appoint to provide opinions on disputes over whether or not the
technical requirements of the regulations have been complied with.
(1 mark)
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(i) Refer to AS/NZS 3000 and state whether a combined protective earthing
and neutral (PEN) conductor can be switched. Include a reference to
support your answer.
(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(j) Refer to AS/NZS 3000 and state the prohibition relating to installing
systems under wall linings or roofing material.(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 6/34
IT21 QUESTIONS – 20 NOVEMBER 2010 6
Question 1 continued
(k) A 230V isolated supply feeds three 10A socket outlets.
Refer to AS/NZS 3000 and state TWO requirements relating to the earthing
terminal of the socket outlets.(1 mark)
(1) ________________________________________________________
________________________________________________________
________________________________________________________
(2) ________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(l) Refer to AS/NZS 3000 and state the requirement for overcurrent protectionin an extra-low voltage electrical installation where the supply is earthed at
the point of supply.
(1 mark)
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(m) Refer to AS/NZS 3000 and state the requirements relating to the minimum
resistance of the protective earthing conductor of a final subcircuit in a
low voltage electrical installation.(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 7/34
IT21 QUESTIONS – 20 NOVEMBER 2010 7
Question 1 continued
(n) State the main reason for testing the three-phase socket outlets in a new
electrical installation with a phase sequence indicator?
(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
(o) (i) What typical applications are “gG” type HRC fuse cartridges used for?
(½ mark)
________________________________________________________
(ii) What is a typical fusing factor (utilisation category) of a “gG” HRC fuse
cartridge?
(½ mark)
________________________________________________________
(p) (i) What typical applications are “gM” type HRC fuse cartridges used for?
(½ mark)
________________________________________________________
(ii) What is a typical fusing factor (utilisation category) of a “gM” HRC fuse
cartridge?(½ mark)
________________________________________________________
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 8/34
IT21 QUESTIONS – 20 NOVEMBER 2010 8
Question 1 continued
(q) An earth loop impedance test on a single phase 230V 10A socket outlet is
measured at 0.45Ω in a commercial office. A Class I electrical appliance
plugged into the socket outlet has a protective earthing conductor
resistance of 0.76Ω.
A short circuit of negligible impedance has occurred between the phase and
frame of the appliance. Calculate the prospective short circuit current
flowing in the protective earthing conductor.(1 mark)
(r) Briefly explain the basic principle of operation of an RCD tester.
(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
(s) A 100kVA, 400V, three-phase transformer has a 5% impedance and
develops a fault current level of 2MVA.
Determine the prospective short circuit current that would flow if a short
circuit of negligible impedance occurs across the transformer output
terminals.(1 mark)
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 9/34
IT21 QUESTIONS – 20 NOVEMBER 2010 9
Question 1 continued
(t) (i) If an RCD is being used for personal protection, what is the
permitted:
Type?
Maximum a.c. rated residual current?(½ mark)
________________________________________________________
(ii) If an RCD is being used for the protection of property, what is the
permitted:
Type? Maximum a.c. rated residual current?
(½ mark)
________________________________________________________
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 10/34
IT21 QUESTIONS – 20 NOVEMBER 2010 10
Question 2
A homeowner has installed the wiring for a new extension to their existing home.
The homeowner has requested that you test, inspect, certify and connect all of
the work in accordance with the Electricity (Safety) Regulations.
(a) (i) In accordance with which document must the homeowner have carriedout this work?
(1 mark)
________________________________________________________
Ref: …………………………………………..
(ii) The homeowner has run new TPS twin and earth final subcircuits (but
not connected them) back to the existing switchboard position.
What is the minimum size cable must the home owner use for:
(2 marks)
The lighting circuits. _______________________
The socket outlet circuits _______________________
The permanently connected 3kW hot water cylinder _____________
The permanently connected room heater __________________
Ref: …………………………………………..
(iii) The homeowner has installed light fittings that are connected to the
fixed wiring by ceiling roses in the new bedrooms.
What is the minimum size and type of flexible cord the homeowner
must use between a ceiling rose and a light fitting?
(1 mark)
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 11/34
IT21 QUESTIONS – 20 NOVEMBER 2010 11
Question 2 continued
(iv) The homeowner has installed an isolating switch to control the new hotwater cylinder.
What is the minimum rating for the isolating switch the homeownermust install?(½ mark)
________________________________________________________
Ref: …………………………………………..
(b) (i) Refer to the Electricity (Safety) Regulations and state the documentthat details the checking and testing you are required to carry out onthe homeowners work.
(1 mark)
________________________________________________________
Ref: …………………………………………..
(ii) Refer to the document you have stated for (b)(i) and stateTHREE tests using test instruments you will carry out on the finalsubcircuits installed by the homeowner before they are connected atthe switchboard.
(1½ marks)
(1) ____________________________________________________
(2) ____________________________________________________
(3) ____________________________________________________
Ref: …………………………………………..
(c) The switchboard has the necessary RCCBs and MCBs to which the new
circuits can be connected.
State the minimum electrical protection that is required for:(3 marks)
The lighting circuits. _______________________
The socket outlet circuits _______________________
The permanently connected hot water cylinder __________________
The permanently connected room heater __________________
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 12/34
IT21 QUESTIONS – 20 NOVEMBER 2010 12
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 13/34
IT21 QUESTIONS – 20 NOVEMBER 2010 13
Question 3
A small commercial factory is to be connected to a three-phase 400V MEN power
supply and has the following loads:
10kW of electric heating 12 - 250W metal halide light fittings with a power factor of 0.8 lag.
Several lightly loaded machines with a total load of 20kW and an overall
power factor of 0.5 lag
You have been requested to recommend a suitable size transformer that can
supply this installation. You need to allow for a one-third increase in load.
Determine by calculation the most suitable size transformer.
(10 marks)
(There is additional room for your calculations over the page)
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 14/34
IT21 QUESTIONS – 20 NOVEMBER 2010 14
Question 3 continued
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 15/34
IT21 QUESTIONS – 20 NOVEMBER 2010 15
Question 4
As an electrical inspector you have been asked to provide advice relating to theinstallation of apparatus and accessories in an existing commercial building thatoperates at standard low voltage.
Most of the apparatus and accessories will be supplied at 230V, single-phase.However some apparatus and accessories will be supplied at 12V, SELV.
(a) (i) Refer to the Electricity (Safety) Regulations and state the standard to
which the 230V socket outlets must comply.(½ mark)
________________________________________________________
Ref: …………………………………………..
(ii) State the main reason why it is only the 230V socket outlets in this
installation that can comply with the standard pin arrangementdetailed in the Standard you have stated in (a)(i).
(1½ marks)
________________________________________________________
________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(b) A 230V motor driven machine is supplied by a multi-core flexible cable that incorporates 12V conductors. The 12V conductors are part of a control
circuit that allows the machine to be controlled remotely.
Refer to AS/NZS 3000 and state the requirement relating to the insulationof the conductors of the multi-core flexible cable.
(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 16/34
IT21 QUESTIONS – 20 NOVEMBER 2010 16
Question 4 continued
(c) Within the installation some SELV cables will be installed in a trunking
system with 230V cables.
Refer to AS/NZS 3000 and state TWO methods, either of which that willpermit SELV cables and 230V to be enclosed in the same wiring system.
(2 marks)
(1) ________________________________________________________
________________________________________________________
(2) ________________________________________________________
________________________________________________________
Ref: …………………………………………..
(d) The installation will also incorporate switched standard socket outlets,
switched pendant socket outlets and switched floor socket outlets.
(i) Refer to AS/NZS 3000 and state the requirement relating to the
polarity (polarisation) of the standard socket outlets.(1 mark)
________________________________________________________
________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(ii) The switched pendant socket outlets will be supplied via a flexible
cord.
Refer to AS/NZS 3000 and state the requirements relating to the
switch in the pendant socket outlet.(1 mark)
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 17/34
IT21 QUESTIONS – 20 NOVEMBER 2010 17
Question 4 continued
(e) The installation will incorporate SELV socket outlets.
Refer to AS/NZS 3000 and state:
(i) The requirements relating to the marking of the SELV socket outlets.(1 mark)
________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(ii) The requirements relating to the plugs for the SELV apparatus.(1 mark)
________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(f) The installation incorporates recessed luminaires, for which there are no
manufacturer’s instructions.
Refer to AS/NZS 3000 and state ONE method that can used to install the
recessed luminaries.
(1 mark)
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 18/34
IT21 QUESTIONS – 20 NOVEMBER 2010 18
Question 5
A small three-phase 400V/230V low rise development comprises six 230Vdomestic electrical installations combined with communal areas. The intention isthat the load be spread evenly, as much as is possible, over the three phases.
The installation comprises:
Domestic installation Group 1. Three single-phase installations.
Domestic installation Group 2. Three single-phase installations.
Communal Group.
Refer to AS/NZS 3000 calculate the maximum demand in amps of the highestloaded phase.
(10 marks)
(a) Domestic installation Group 1. Three single-phase installations have the
following loads:
15 Lighting points 1 Electric oven – 2.5kW4 Double socket outlets (10A) 1 Storage water heater – 2kW6 Single socket outlets (10A) 1 Air-conditioning unit – 3kW
Load Group Calculation Load (A)
Group
Group
Group
Group
Group
Maximum demand
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 19/34
IT21 QUESTIONS – 20 NOVEMBER 2010 19
Question 5 continued
(b) Domestic installation Group 2. Three single-phase installations have the
following loads:
15 Lighting points 1 Electric range – 5kW4 Double socket outlets (10A) 1 Instantaneous water heater –
3kW
6 Single socket outlets (10A) 1 Sauna – 6kW
Load Group Calculation Load (A)
Group
Group
Group
Group
Group
Maximum demand
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 20/34
IT21 QUESTIONS – 20 NOVEMBER 2010 20
Question 5 continued
(c) Communal Group. The communal areas incorporate the following single
phase loads:
30 Lights – 100W each3 Clothes dryers – 4 kW each
3 Air-conditioning unit, each rated at:
6kW – winter setting3kW – summer setting
Load Group Calculation Load (A)
Group
Group
Group
Maximum demand
(d) Maximum demand of the heaviest loaded phase.
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 21/34
IT21 QUESTIONS – 20 NOVEMBER 2010 21
Question 6
(a) You have been requested to connect a new three-phase low voltage
electrical installation to the electricity supply.
You have not been involved in any way with doing prescribed electricalwork on the installation.
You have sighted a Certificate of Compliance that has been completed and
signed by the electrician who certified the work and the electrical inspectorwho inspected the work.
Refer to the Electricity (Safety) Regulations and state:
(i) The connection of the installation can only proceed if the Certificate of
Compliance has been issued within a specific time-frame. What is that
time-frame?
(½ mark)
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(ii) FOUR matters any or all of which could be confirmed on the Certificate
of Compliance you have sighted.(2 marks)
(1) ____________________________________________________
____________________________________________________
(2) ____________________________________________________
____________________________________________________
(3) ____________________________________________________
____________________________________________________
(4) ____________________________________________________
____________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 22/34
IT21 QUESTIONS – 20 NOVEMBER 2010 22
Question 6 continued
(iii) State the action you must take in relation to the new meters.
(1 mark)
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(iv) What must be contained in the document you have sighted relating to
the testing of the installation.(2 marks)
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(v) Who must sign the documentation you have sighted in (a)(iv).
(1 mark)
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(b) You have been requested to reconnect an existing electrical installation thathas been disconnected for 10 months. No prescribed electrical work has
been carried out in the time the installation has been disconnected.
You have not been involved in any way with testing or checking the
installation.
You have sighted a certificate before reconnecting the installation. Refer tothe Electricity (Safety) Regulations and state:
(i) The Standard under which the certificate is issued.
(½ mark)
________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 23/34
IT21 QUESTIONS – 20 NOVEMBER 2010 23
Question 6 continued
(ii) The name of that certificate.
(½ mark)
________________________________________________________
Ref: …………………………………………..
(iii) The matters that must be confirmed on the certificate that you havesighted.
(1½ marks)
________________________________________________________
________________________________________________________
________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(iv) Refer to the Standard you have stated in (b)(i) and state the
requirement relating to the adequacy of the overcurrent protectivedevices in the installation.
(1 mark)
________________________________________________________
________________________________________________________
________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 24/34
IT21 QUESTIONS – 20 NOVEMBER 2010 24
Question 7
(a) Final subcircuits are generally required to have overcurrent protection.
(i) Refer to AS/NZS 3000 and state the overcurrent protection
requirements for the active conductors of a final subcircuit supplying astandard socket outlet.
(1 mark)
________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(ii) Refer to AS/NZS 3001 and state the overcurrent protectionrequirements for the active conductors of a final subcircuit supplying a
socket outlet for a caravan in a caravan park.(1 mark)
________________________________________________________
________________________________________________________
________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 25/34
IT21 QUESTIONS – 20 NOVEMBER 2010 25
Question 7 continued
(b) TWO types of single-phase socket outlets can be installed on a servicepillar in a caravan park for the supply of electricity to caravans. Eachtype is required to have specific characteristics
Refer to AS/NZS 3001 and for each type of socket outlet state:
The configuration The applicable Standard The minimum current rating.
(3 marks)
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(c) TWO types of single-phase socket outlets can be installed on a servicepillar in areas other than a caravan park for the supply of electricityconnectable installations. Each type is required to have specificcharacteristics
Refer to AS/NZS 3001 and for each type of socket outlet state:
The configuration The applicable Standard The minimum current rating.
(3 marks) ____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 26/34
IT21 QUESTIONS – 20 NOVEMBER 2010 26
Question 7 continued
(d) Refer to AS/NZS 3001 and state the overcurrent protection requirements
within a caravan for the incoming supply.
(2 marks)
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
Ref: …………………………………………..
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 27/34
IT21 QUESTIONS – 20 NOVEMBER 2010 27
Question 8
The figure below represents a new low voltage single-phase supply to a domestic
installation. The installation is live and there maybe a phase/neutral
transposition between the distribution supply system and the MEN
switchboard.
(a) You are going to carry out testing using a multi-meter that has the requiredfunctions (scales) to verify whether a mains phase/neutral transposition has
taken place.
(i) State the function (scale) you would select on the multi-meter.
(½ mark)
________________________________________________________
(ii) State the range you would select on the multi-meter.(½ mark)
________________________________________________________
(iii) State additional equipment you would use with the multi-meter.(1 mark)
________________________________________________________
________________________________________________________
(turn over)
Neutral bar
Main switch Earth bar
Single-phase consumer
Meter box
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 28/34
IT21 QUESTIONS – 20 NOVEMBER 2010 28
Question 8 continued
(b) On the figure on the previous page, use the instrument and equipment you
have stated in (a) to show how testing for a mains phase/neutraltransposition is carried out.
(2 marks)
(c) For the tests you have carried out in (b) state:
(i) The readings you would get on the multi-meter if phase/neutral
transposition has not taken place.(2 marks)
________________________________________________________
________________________________________________________
________________________________________________________
________________________________________________________
(ii) The readings you would get on the multi-meter if a phase/neutral
transposition has taken place.(2 marks)
________________________________________________________
________________________________________________________
________________________________________________________
________________________________________________________
(d) The low voltage installation is protected on the distribution supply system
by a 60A rewireable pole fuse.
State the main reason why a phase and neutral transposition on the mains
will not operate (“blow”) the pole fuse.(2 marks)
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 29/34
IT21 QUESTIONS – 20 NOVEMBER 2010 29
Question 9
(a) A 230V PVC insulated two-core copper TPS cable is required to be installed
to supply a 230V, single phase switchboard on a farm.
Calculate the minimum size of cable that will meet the load, voltage dropand environmental conditions by using the following information and
information in the tables on pages 30, 31 and 32.
The cable route between the point of supply and switchboard is 300
metres:
The cable will be buried direct. The only load in the switchboard is a 10A socket outlet.
The ambient temperature is that set under the Electricity (Safety)
Regulations.
The maximum conductor temperature permitted is 75 oC. The maximum allowable voltage drop is that stated in AS/NZS 3000
(6 marks)
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 30/34
IT21 QUESTIONS – 20 NOVEMBER 2010 30
Question 9 continued
(b) A PVC insulated three-core copper cable is to be used to supply a 70 kW,
three-phase, 400 V furnace in a foundry.
Calculate the minimum size of cable that will meet the load, voltage dropand environmental conditions by using the following information andinformation in the tables on pages 30, 31 and 32.
The cable is to be clipped direct (touching). The protective earthing conductor is to be run adjacent to the cable
The ambient air temperature is 35 oC.
The distance between the switchboard and the furnace is 5 metres The cable is to be protected by HRC fuses.
The maximum conductor temperature permitted is 75 oC.
. (4 marks)
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 31/34
IT21 QUESTIONS – 20 NOVEMBER 2010 31
Question 9 continued
The following are extracts from AS/NZS 3008.1.2.
Table 9
Current Carrying Capacities of Two-Core O.6/1 kV Insulated andSheathed (including Neutral Screened) Cables with or without Earth
Conductor, Armoured or Non-Armoured Cables
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Current carrying capacity A
Unenclosed Enclosed BuriedDirect
Undergroundnon-metallicwiringenclosureCon
ductorsize
Spaced Touching Non-metallicwiringenclosures
in air –roundcable
Non-metallicwiringenclosures
in air – flatcable
In non-metallicwiringenclosures
orunenclosedpartiallysurroundedby thermalinsulation
Completelysurroundedby thermalinsulation
mm2 Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
1 17 -- 16 -- 13 10 15 11 11 9 8 - 24 - 19 -1.5 22 - 21 - 16 13 19 15 15 11 10 - 31 - 24 -2.5 31 - 30 - 23 17 25 19 21 16 15 - 44 - 34 -
4 42 - 39 - 30 23 33 25 27 22 19 - 57 - 44 -6 52 - 50 - 39 30 42 32 35 27 25 - 72 - 56 -10 73 - 68 - 54 41 57 43 49 38 34 - 96 - 75 -
16 97 75 91 71 72 55 75 57 65 50 46 35 127 97 97 7525 131 100 120 95 100 76 101 76 90 71 60 47 160 127 127 9835 160 125 148 114 120 89 120 89 105 82 74 58 198 154 154 121
Note: The ratings are based on 300C ambient air temperature and 150C ambient soil temperature
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 32/34
IT21 QUESTIONS – 20 NOVEMBER 2010 32
Question 9 continued
Table 12
Current Carrying Capacities of Three-Core And Four-Core O.6/1 kV
Insulated and Sheathed (including Neutral Screened) Cables with orwithout Earth Conductor, Armoured or Non-Armoured Cables
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Current carrying capacity A
Unenclosed Enclosed BuriedDirect
Undergroundnon-metallicwiringenclosureCon
ductorsize
Spaced Touching Non-metallicwiringenclosuresin air –roundcable
Non-metallicwiringenclosuresin air – flatcable
In non-metallicwiringenclosuresorunenclosedpartiallysurroundedby thermalinsulation
Completelysurroundedby thermalinsulation
mm2 Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
1 15 -- 14 -- 11 9 14 10 11 8 7 - 21 - 17 -1.5 18 - 17 - 15 11 17 13 14 11 9 - 26 - 21 -2.5 26 - 25 - 21 16 23 17 19 15 13 - 37 - 29 -
4 35 - 33 - 27 21 30 23 25 19 17 - 48 - 37 -6 46 - 42 - 35 27 39 30 33 25 22 - 61 - 47 -10 52 - 58 - 48 38 52 40 44 34 29 - 81 - 63 -
16 82 64 78 60 64 49 68 52 59 46 39 30 106 83 81 6425 111 86 104 81 90 68 95 72 82 64 52 40 138 107 106 8335 137 106 125 99 105 80 105 80 96 74 64 49 165 127 127 100
Note: The ratings are based on 300C ambient air temperature and 150C ambient soil temperature
Table 27(1)
Rating Factors for Variations in Ambient Temperature for Cables in Air
or Heated Concrete Slabs and for Cables Buried Direct in the Ground or
in Underground Wiring Enclosures – Air And Concrete Slab
Temperatures
1 2 3 4 5 6 7 8 9 10 11
Rating Factor
Ambient temperature
Conductortemperature0
C 15 20 25 30 35 40 45 50 55 60150 1.07 1.05 1.03 1.00 0.98 0.96 0.94 0.91 0.89 0.87110 1.08 1.06 1.03 1.00 0.97 0.93 0.90 0.87 0.83 0.7990 1.15 1.09 1.05 1.00 0.95 0.91 0.85 0.80 0.74 0.66
80 1.17 1.12 1.06 1.00 0.95 0.89 0.82 0.75 0.68 0.5975 1.18 1.12 1.06 1.00 0.94 0.88 0.80 0.72 0.63 0.53
(turn over)
7/27/2019 IT_21_Questions_20_November_10.pdf
http://slidepdf.com/reader/full/it21questions20november10pdf 33/34
IT21 QUESTIONS – 20 NOVEMBER 2010 33
Question 9 continued
Table 27(2)
Rating Factors for Variations in Ambient Temperature for Cables in Air
or Heated Concrete Slabs and for Cables Buried Direct in the Ground orin Underground Wiring Enclosures – Soil Temperatures
1 2 3 4 5 6 7 8
Rating Factor
Ambient temperature
Conductortemperature0C 10 15 20 25 30 35 40
110 1.02 1.00 0.97 0.94 0.92 0.89 0.8690 1.04 1.00 0.96 0.93 0.91 0.87 0.8380 1.04 1.00 0.95 0.92 0.88 0.83 0.78
75 1.04 1.00 0.95 0.91 0.86 0.81 0.75
Table 42
Three-Phase Voltage Drop at 50Hz of Multicore Cables with Circular Copper
Conductors
Three-phase voltage drop at 50 Hz, mV/A.m
Conductor temperature, 0CConductor size 45 60 75 90 110
mm2 Max. 0.8p.f.
Max. 0.8p.f.
Max. 0.8p.f.
Max. 0.8p.f.
Max. 0.8p.f.
1 40.3 - 42.5 - 44.7 - 46.8 - 49.7 -1.5 25.9 - 27.3 - 28.6 - 30.0 - 31.9 -2.5 14.1 - 14.9 - 15.6 - 16.4 - 17.4 -
4 8.77 - 9.24 - 9.71 - 10.2 - 10.8 -6 5.86 - 6.18 - 6.49 - 6.80 - 7.22 -10 3.49 - 3.67 - 3.86 - 4.05 - 4.29 -
16 2.19 - 2.31 - 2.43 - 2.55 - 2.70 -25 1.39 - 1.47 - 1.54 - 1.61 - 1.71 -35 1.01 - 1.06 - 1.11 - 1.17 - 1.24 -
Note: To convert to single-phase values multiply the three-phase value by 1.155
(turn over)