+ All Categories
Home > Documents > KAPPA V SR - SKLEP-KLIMATYZACJAsklep-klimatyzacja.pl/dokumentacje/CHILLERY_dok... ·...

KAPPA V SR - SKLEP-KLIMATYZACJAsklep-klimatyzacja.pl/dokumentacje/CHILLERY_dok... ·...

Date post: 07-Mar-2018
Category:
Upload: vuongquynh
View: 217 times
Download: 2 times
Share this document with a friend
82
Manual 101070B02 Issue 02.03 Replaces 06.02 KAPPA V SR 635 ÷ 1065 kW 0062 Installation, operating, and maintenance manual Water chillers Air/water Axial fans and self-contained screw compressors ISO 9001 - Cert. n. 0201
Transcript

Manual 101070B02Issue 02.03Replaces 06.02

KAPPA V SR635 ÷ 1065 kW

0062

Installation, operating,and maintenancemanual

Water chillers Air/water Axial fans andself-contained screw compressors

ISO 9001 - Cert. n. 0201

INDEX Page

KAPPA V SR water chiller 1UNIT FRAME 1COMPRESSORS 1CONDENSER FANS 1REFRIGERANT CIRCUIT 1ELECTRICAL PANEL 1CONTROLS AND SAFETY DEVICES 1TESTING 2KAPPA V SR UNIT VERSIONS 2HYDRAULIC MODULE OPTIONS 2ACCESSORY VERSIONS 2REFRIGERANT CIRCUIT ACCESSORIES 2HYDRAULIC CIRCUIT ACCESSORIES 3ELECTRICAL ACCESSORIES 3VARIOUS ACCESSORIES 3

SERIES 4TYPE DESIGNATION 4TECHNICAL DATA 5ELECTRICAL CHARACTERISTICS AND COMPONENTS 7TECHNICAL DATA - KAPPA V SR /ST 2PS 8SOUND PRESSURE LEVELS 9

1. FIELD OF APPLICATION 101.1 INTRODUCTION 10

2. INSPECTION, TRANSPORT, SITE HANDLING 102.1 INSPECTION 102.2 LIFTING AND SITE HANDLING 10

3. SAFETY PRECAUTIONS 123.1 DEFINITION OF DANGER ZONE 123.2 SAFETY PRESCRIPTIONS 12

MECHANICAL HAZARDS 13THERMAL HAZARDS 14NOISE-RELATED HAZARDS 14ELECTRICAL HAZARDS 14REFRIGERANT SAFETY DATA - R407C 15

3.3 POSITIONING 17

4. INSTALLATION 194.1 INSTALLATION CLEARANCES 194.2 ANTI-VIBRATION ISOLATORS (option) 204.2.1 Rubber Anti-Vibration Isolators 204.2.2 Spring Anti-Vibration Isolators 204.3 WATER PIPING CONNECTIONS 21

RECOMMENDED HYDRAULIC CIRCUIT DIAGRAM FOR KAPPA V SR 22HYDRAULIC CIRCUIT DIAGRAM VERSION KAPPA V SR /ST 2PS 23

4.4 EVAPORATOR WATER PIPE CONNECTIONS 244.5 FLEXIBLE JOINTS 254.6 DESUPERHEATER HYDRAULIC CONNECTION (optional) 264.7 HEAT RECOVERY EXCHANGER HYDRAULIC CONNECTIONS (OPTIONAL) 27

DIAGRAM WITH 3-WAY VALVE 274.8 PRESSURE RELIEF VALVES 28

DIAGRAM WITH CONDENSING PRESSURE CONTROL VALVE 28

4.9 WATER FLOW RATE TO EVAPORATOR 294.10 CHILLER WATER TEMPERATURE (SUMMER CYCLE) 294.11 HOT WATER TEMPERATURE (winter cycle) 294.12 AMBIENT AIR TEMPERATURE 294.13 FAN SPEED CONTROL (optional) 294.14 OPERATION WITH LOW TEMPERATURE CHILLED WATER AT EVAPORATOR 30

TABLE 1 - FREEZING POINT FOR WATER-ANTIFREEZE MIXTURES 30OPERATING LIMITS 31EVAPORATOR PRESSURE DROP 32PUMPS AVAILABLE PRESSURE - MODEL KAPPA V SR /ST 2PS 33ELECTRICAL PANEL LAY OUT 34

4.15 ELECTRICAL CONNECTIONS 374.15.1 General 374.15.2 Power supply to crankcase heaters 374.15.3 Potential free contacts 384.15.4 Circulating pump electrical connections 384.15.5 Microprocessor controllers 384.15.6 RS485 serial interface (optional) 384.15.7 User interface - Microprocessor pCO2 39

5. START-UP 415.1 PRELIMINARY CHECKS 415.2 OPERATING DESCRIPTION 415.2.1 Introduction 415.2.2 Unit in stand-by mode 415.2.3 Enabling the unit 425.2.4 Pump management (ST units only) 425.2.5 Compressor start-up 425.2.6 Chiller mode operation 425.2.7 Heat pump mode operation 425.2.8 Evaporator low temperature chilled water protection 425.2.9 Evaporator anti-freeze protection electric heater (optional) 425.2.10 Compressor operation 435.2.11 Compressors and capacity steps management 435.2.12 High and low pressure alarms 445.2.13 Low ambient temperature kit (option - condens. control with fan speed regulator) 445.2.14 Changeover from chiller to heat pump and vice versa 445.2.15 Defrosting (heat pump units only) 445.2.16 Total heat recovery (option) 455.2.17 Dual set-point (option) 455.2.18 Operation leaving water temperature control (option) 465.3 STARTING THE UNIT 465.4 STOPPING THE UNIT 475.4.1 Temporary stop: 475.4.2 Seasonal stop: 475.5 EMERGENCY STOP 47

6 CHECKS DURING OPERATION 486.1 INTRODUCTION 486.1.1 Checking the refrigerant charge 48

7. CALIBRATION OF CONTROL EQUIPMENT 497.1 INTRODUCTION 49

TABLE 2 - CALIBRATION OF CONTROL EQUIPMENT 49TABLE 3 - CALIBRATION OF SAFETY DEVICES 49

8. MAINTENANCE AND PERIODIC CHECKS 508.1 WARNINGS 50

8.2 INTRODUCTION 508.3 REPAIRING THE REFRIGERANT CIRCUIT 518.3.1 Leak test 518.3.2 High vacuum and dehydration of the refrigerant circuit 518.3.3 Refrigerant charge 528.4 ENVIRONMENTAL CONSIDERATIONS 52

9. TROUBLESHOOTING 53

10. DECOMMISSIONING THE UNIT 62

REFRIGERANT CIRCUIT 63

OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS 66

Blue Box 1

KAPPA V SR water chiller

UNIT FRAMESelf supporting frame with removable panels, internally coated with expanded polyurethane sound-absorbingmaterial; constructed from galvanized sheet steel with RAL 5014 powder paint baked at 180°C to provide adurable weatherproof finish. Threaded fasteners in stainless steel.

COMPRESSORSDirect drive semihermetic screw compressors. Crankcase heater and lubrication through pressure differencebetween suction and discharge pressure.Optional continuous capacity control available, to maximize the efficiency of the unit in all working conditions.Electronic motor protection via thermal sensors embedded in the windings. Star-Delta start and capacity step asstandard.

CONDENSERComposed of a high efficiency coil manufactured from copper tubes and aluminium fins. Mesh guard to protectthe coil supplied as standard.

CONDENSER FANSAxial fans, with sickle shaped blades and special bell mouth designed to reduce noise, directly coupled toa 6 polemotor with internal Klixon overload protection. Motor protection category is IP 54. The fan is equipped with asafety grille to UNI EN 294.

EVAPORATORShell and tube direct expansion evaporator. The evaporator is thermally insulated with closed cell expandedmaterial. Each evaporator is equipped with a low water temperature probe for freeze protection.

REFRIGERANT CIRCUITComprising: compressor discharge shut-off valve, liquid valve, charge connection, liquid line sight-glass, filter/dryer with interchangeable solid cartridge, thermostatic expansion valve with external pressure equalisation, highand low pressure values and relative condensation and evaporation temperatures are measured by pressuretransducers that relay signals that are displayed on the controller.

ELECTRICAL PANELThe electrical panel includes:

- main switch- fuses to protect auxiliary and power circuits- compressor contactors- fan contactors

The microprocessor controls the following functions:- water temperature regulation- freeze protection- compressor time intervals- compressor start sequence and automatic lead/lag selection- alarm signalling- alarm reset- common alarm contact for remote signalling

LCD display of the following information:- water inlet and outlet temperature- programmed temperature set-point and differential- alarm descriptions- compressor hours run meter, number of unit and compressor starts and pumps (if installed)- high and low pressure values and relative condensation and evaporation temperature values.

CONTROLS AND SAFETY DEVICES- safety high pressure switch with manual reset- high/low pressure safety with manual reset controlled by the microprocessor control- high pressure relief valve

Blue Box 2

- compressors over-temperature protection on discharge gas with liquid injection- chilled water temperature probe (at evaporator inlet)- freeze protection probe at the evaporator outlet- compressor over-temperature protection- fan over-temperature protection

TESTINGThe units are subjected to a dry run in the factory and supplied complete with oil and refrigerant.

KAPPA V SR UNIT VERSIONS

KAPPA V SR /HP: reverse cycle heat pumpIn addition to the components of version KAPPA V SR, this unit includes:- Refrigerant circuit: 4-way reversing valve, suction separator, liquid receiver, second thermostatic expansion

valve.- Electrical panel: Microprocessor enabled for summer/winter changeover and automatic defrost,

HYDRAULIC MODULE OPTIONS

KAPPA V SR 2PS: unit with storage tank and pumps.In addition to the components of version KAPPA V SR this unit includes:insulated storage tank; run and standby circulating pumps, with automatic changeover by time or fault.Expansion tank, check valves and gate valves.Version ST is available in the following additional four configurations:- ST 1PS : with 1 pump and a tank;- ST 2P : with 2 pumps without a tank;- ST S : with tank without pumps;- ST 1P : with 1 pump without a tank.

ACCESSORY VERSIONS

KAPPA V SR /DC: unit with heat recovery condenser.In addition to the components of version KAPPA V SR this unit includes for each compressor a 100% heatrecovery condenser for the production of hot water. The microprocessor automatically controls the water tempe-rature and the heat recovery safety switch.

KAPPA V SR /LN: low noise unitIn addition to the components of version KAPPA V SR this unit includes:compressors located in a sound absorbing enclosure of painted galvanized steel, internally lined with soundabsorption material having an intermediate layer of high acoustic impedance material.

REFRIGERANT CIRCUIT ACCESSORIES:

- DesuperheatersThe desuperheater heat exchanger is arranged in series with the condensing coil. It is also available in aheat pump configuration. In this case a shut-off valve must be fitted on the water recovery circuit, to beclosed during heat pump mode operation, as described in the manual.

- Pressure gauges.Available on all models. Suction and discharge pressure values, read by transducers that relay the results tothe controller display, are already displayed as standard on all models.

Blue Box 3

HYDRAULIC CIRCUIT ACCESSORIES- Anti-freeze evaporator heater- Water side relief valve (version ST only). The value is set at 6 bar, corresponding to the maximum permissible

working pressure.- Leaving water temperature control (Not available on HP version).- Mechanical flow switch

ELECTRICAL ACCESSORIES- Serial interface RS 485 with protocol Modbus; the following optional protocols are also available: Carel; Echelon

version RS485 or version FTT10- Power factor correction cos f ≥ 0.9 at nominal operating conditions- Single voltage-free contacts for machine status signals- Remote user terminal panel (in addition to the standard terminal)- Set-point variable with remote signal (0-1 V, 0-10 V, 0-4 mA, 0-20 ma)

- Dual set-pointWith double thermostatic valves + solenoid valves. Two set-points can be programmed and switchedbetween each other from the keypad or using a digital input. The type of selection must be specified at thetime of order. In all cases the thermostatic valves switch automatically on the basis of the water temperature.

- Step type condensing pressure control (ambient air minimum temperature 0 °C) The control is managed in On/Off mode by the microprocessor by means of the pressure transducers.

- Condensing pressure control by fan speed regulator (ambient air minimum temperature -20 °C).Fan speed is regulated in accordance with the condensation pressure read by the pressure transducers.

- Additional compressor capacity step- Compressor continuous capacity step control- Electronic expansion valve- Liquid line solenoid valve- Liquid receivers (standard on version /HP)- Compressor suction valves

VARIOUS ACCESSORIES- Rubber or spring type anti-vibration mounts- Anti-corrosion treatment of coils for use in aggressive environments- Timber crate packing- Pallet/skid for container shipment- Non-standard RAL paint colours

Blue Box 4

SERIES

The KAPPA V SR series of water cooled chillers and heat pumps, are available in various sizes with capacitiesfrom 635 to 1.065 kW (capacities refer to water entering/leaving 12/7 °C, ambient air 35 °C) in the followingbasic versions:- KAPPA V SR cooling only- KAPPA V SR/HP heat pump

The model, serial number, characteristics, power supply, etc. are shown by means of decals on the unit.

TYPE DESIGNATIONunit type series /version /option hydraulic modul /accessory version size

KAPPA V SR 65.2/ST 1P 73.2

/HP /ST 2P /LN 80.2/ST 1PS /DS 84.2/ST 2PS /DC 88.2

/ST S /LN/DS 93.2/LN/DC 100.2

106.3

Type designation example: KAPPA.V SR /HP/DS 100.2

Meaning of values 100 . 2

Number to identify the indicative Number of compressorscooling capacity (in this case 100 kW)

Corrente massima di spuntoMax starting currentMax. AnlaufstromCourant maxi démarrage

Tipo refrigeranteRefrigerant typeKältemittel TypType de refrigerant

Numero circuiti refrigeranteRefrigerant circuit numberAnzahl des KältemittelkreislaufesNumero circuits refrigerant

Press. massima circuito idraulicoMax. Hydraultic circuit pressureMax. Druck im Hydraul. KreislaufPression maxi circuit hydraulique

Data di produzioneManufacturing dateErstellungsdatumDate de fabrication

Press. massima circuito refriger.Max. Refrigerant circuit pressureMax. Druck KältekreislaufPression maxi circuit refrigerant

IP quadro elettricoIP electrical boardIP E-SchrankIP tableau electrique

Tensione circuiti ausiliariAuxiliary circuit voltageSteuerspannungTension circuits auxiliares

Matricola/Serial number(BBOX) Matrikel/Matricule

Corrente massima assorbitaMax absorbed currentMaximalstromverbrauchCourant maxi absorbée

Modello/ModelModell/Modèle

Tensione-Fasi-FrequenzaVoltage-Phasses-FrequencySpannung-Phasses-FrequenzTension-Phasses-Fréquence

A A

kPa

kPa

Carica refrigerante per circuito(kg)/Refrigerant charge per circuitKältemittelfüllung Kreislauf Charge de refigerant chaque circuit

(kg)/ (kg)/ (kg)

C2C1 C3 C4

bar

bar

0062

Via Enrico Mattei, 2035028 Piove di Sacco (PD)ITALYTel. +039.049.9716300

Corrente massima di spuntoREFRIGERANTE - REFRIGERANT - KÄLTEMITTEL - REFRIGERANT

MATRICOLA - MATRICULE - SERIAL NO. - SERIENUMMER

MODELLO - MODELE - MODEL - TYP

0062

Via Enrico Mattei, 2035028 Piove di Sacco (PD)

Via Enrico Mattei, 2035028 Piove di Sacco (PD)ITALYTel. +039.049.9716300

Blue Box 5

TECHNICAL DATA

Refrigerant R407C

(1) total water flow(*) ambient air temperature 35 °C; evaporator entering/leaving water temperature 12-7 °C;.(**) ambient air temperature 8 °C DB, 50%RH; condenser entering/leaving water temperature 40-45 °C.

MODEL KAPPA V SR 65.2 73.2 80.2 84.2Cool ing (*)Nominal capacity kW 635,6 710,2 769,3 813,7Evaporator water flow (1) l/s 30,37 33,93 36,76 38,88

l/h 109.316 122.150 132.323 139.963Evaporator pressure drop kPa 53 60,2 61,8 28,6Heating (**)Nominal capacity kW 610,1 679,6 736,7 785,5Condenser water flow (1) l/s 29,15 32,47 35,20 37,53

l/h 104.929 116.889 126.707 135.108Condenser pressure drop kPa 49 55,4 56,9 26,8Compressors typeQuantity n 2 2 2 2Refrigerant circuits n 2 2 2 2Absorbed power cooling (*) kW 224,1 248,1 269,3 291Absorbed power heating (**) kW 217,3 240,7 261,2 282,2Capacity steps % 0-25-50-75-100 0-25-50-75-100 0-25-50-75-100 0-25-50-75-100Condenser cool ing fans typeTotal air flow m3/s 61,33 58,67 71,56 69,60

m3/h 220.800 211.200 257.600 250.560Fan motor power n x kW 12 x 2,0 12 x 2,0 14 x 2,0 14 x 2,0Nominal revolution speed RPMElectric motor supply V/Ph/HzRefr igerant chargeChiller version kg 2 x 89 2 x 109 2 x 106 1x106 + 1x127

Heat pump version kg 2 x 110 2 x 135 2 x 130 1x130 + 1x155

Oi lOil charge l 2 x 15 2 x 15 2 x 18 2 x 18Oil producerOil typeEvaporator typeHeat exchanger water volume l 184,4 225 403 403,0Max operating pressure water side barDimension and weightLength mm 8.190 8.190 9.240 9.240Width mm 2.390 2.390 2.390 2.390Heigth mm 2.432 2.432 2.432 2.432Shipping weight kg 5.901 6.111 7.225 7.536

screw semihermetic

880

DEA

axial

400/3~/50

shell and tube

10

SE 170

Blue Box 6

TECHNICAL DATA

Refrigerant R407C

(1) total water flow(*) ambient air temperature 35 °C; evaporator entering/leaving water temperature 12-7 °C;.(**) ambient air temperature 8 °C DB, 50%RH; condenser entering/leaving water temperature 40-45 °C.

MODEL KAPPA V SR 88.2 93.2 100.2 106.3Cool ing (*)Nominal capacity kW 858,2 907,1 956 1065,3Evaporator water flow (1) l/s 41,00 43,34 45,68 50,90

l/h 147.603 156.017 164.431 183.224Evaporator pressure drop kPa 31,6 35,1 74 70Heating (**)Nominal capacity kW 834,4 881,1 927,9 1019,4Condenser water flow (1) l/s 39,86 42,10 44,34 48,70

l/h 143.510 151.557 159.604 175.334Condenser pressure drop kPa 30 33,3 70 64,5Compressors typeQuantity n 2 2 2 3Refrigerant circuits n 2 2 2 3Absorbed power cooling (*) kW 312,7 330,4 348,1 372,2Absorbed power heating (**) kW 303,1 320,3 337,5 361Capacity steps % 0-25-50-75-100 0-25-50-75-100 0-25-50-75-100 0-16.7-33.5-50-

66.7-83.3-100Condenser cool ing fans typeTotal air flow m3/s 68,33 81,26 81,26 85,78

m3/h 246.000 292.528 292.528 308.800Fan motor power n x kW 14 x 2,0 16 x 2,0 16 x 2,0 16 x 2,0Nominal revolution speed RPMElectric motor supply V/Ph/HzRefr igerant chargeChiller version kg 2 x 127 2 x 123 2 x 123 3 x 92

Heat pump version kg 2 x 155 2 x 150 2 x 150 3 x 115

Oi lOil charge l 2 x 18 2 x 18 2 x 18 3 x 15Oil producerOil typeEvaporator typeHeat exchanger water volume l 403,0 378,0 378,0 442,0Max operating pressure water side barDimension and weightLength mm 9.240 10.290 10.290 12.110Width mm 2.390 2.390 2.390 2.390Heigth mm 2.432 2.432 2.432 2.432Shipping weight kg 7.681 7.632 7.816 8.576

10

screw semihermetic

880

axial

400/3~/50

DEASE 170

shell and tube

Blue Box 7

ELECTRICAL CHARACTERISTICS AND COMPONENTS

Refrigerant R407C

(1) mains power supply to allow unit operation.(2) maximum current before safety cut-outs stop the unit. This value is never exceeded and must be used to size the electrical supply

cables and relevant safety devices (refer to electrical wiring diagram supplied with the unit).

All values in brackets are refer to /ST version (units with storage tank) or units with pump.

MODEL KAPPA V SR 65.2 73.2 80.2 84.2Maximum absorbed power (1) Kw 285,8 314 342,6 360,4

Kw (296,8) (325) (357,6) (375,4)Maximum starting current A 596 667 779 869

A (619) (690) (809) (899)Full load current (2) A 498 538 596 626

A (521) (561) (626) (656)Fan motor nominal power n x kW 12 x 2,0 12 x 2,0 14 x 2,0 14 x 2,0Fan motor nominal absorbed current n x A 12 x 4,0 12 x 4,0 14 x 4,0 14 x 4,0Pump motor nominal power kW (1 x 11,0) (1 x 11,0) (1 x 15,0) (1 x 15,0)Pump motor nominal absorbed power A (1 x 23,0) (1 x 23,0) (1 x 30,0) (1 x 30,0)Power supply V/Ph/HzControl power supply V/Ph/HzControl board supply V/Ph/HzCondenser fans supply V/Ph/HzST Hydraulic module pumps suppy V/Ph/Hz

400V 3N ~ 50Hz ±5% V230V/ ~/50Hz24V/~/50Hz400V/3~/50400V/3~/50

MODEL KAPPA V SR 88.2 93.2 100.2 106.3Maximum absorbed power (1) Kw 378,2 402,1 422 467

Kw (393,2) (424,1) (444) (489)Maximum starting current A 899 959 993 928

A (929) (1001) (1035) (970)Full load current (2) A 656 698 732 799

A (686) (740) (774) (841)Fan motor nominal power n x kW 14 x 2,0 16 x 2,0 16 x 2,0 16 x 2,0Fan motor nominal absorbed current n x A 14 x 4,0 16 x 4,0 16 x 4,0 16 x 4,0Pump motor nominal power kW (1 x 15,0) (1 x 22,0) (1 x 22,0) (1 x 22,0)Pump motor nominal absorbed power A (1 x 30,0) (1 x 42,0) (1 x 42,0) (1 x 42,0)Power supply V/Ph/HzControl power supply V/Ph/HzControl board supply V/Ph/HzCondenser fans supply V/Ph/HzST Hydraulic module pumps suppy V/Ph/Hz

400V/3~/50400V/3~/50

400V 3N ~ 50Hz ±5% V230V/ ~/50Hz24V/~/50Hz

Blue Box 8

TECHNICAL DATA - KAPPA V SR /ST 2PS

Refrigerant R407C

MODEL KAPPA V SR 65.2 73.2 80.2 84.2Pump sect ionEvaporator water flow l/s 30,37 33,93 36,76 38,88

l/h 109.316 122.150 132.323 139.963Pump nominal power kW 11 11 15 15External available pressure kPa 168 140 197 216Storage tank water volume l 1000 1000 1000 1000Dimension and weightLength mm 8.190 8.190 9.240 9.240Width mm 2.390 2.390 2.390 2.390Heigth mm 2.432 2.432 2.432 2.432Shipping weight kg 6.416 6.626 7.882 8.027

MODEL KAPPA V SR 88.2 93.2 100.2 106.3Pump sect ionEvaporator water flow l/s 41,00 43,34 45,68 50,90

l/h 147.603 156.017 164.431 183.224Pump nominal power kW 15 22 22 22External available pressure kPa 195 279 216 154Storage tank water volume l 1000 1000 1000 1000Dimension and weightLength mm 9.240 10.290 10.290 12.110Width mm 2.390 2.390 2.390 2.390Heigth mm 2.432 2.432 2.432 2.432Shipping weight kg 8.172 8.660 8.844 9.468

Blue Box 9

SOUND PRESSURE LEVELS

STANDARD UNITS

LOW NOISE UNITS

Lcc: sound pressure values measured in free field conditions with phonometer at 1 m from the unit and 1,5 m from ground levelon thecondensing coil side.

Model TotalKAPPA V SR 63 [dB] 125 [dB] 250 [dB] 500 [dB] 1000 [dB] 2000 [dB] 4000 [dB] 8000 [dB] dB(A)

Lcc Lcc Lcc Lcc Lcc Lcc Lcc Lcc Lcc65.2 71,7 75,6 74,4 73,9 76,4 74,2 65,2 54,6 80,0

73.2 71,7 75,4 74,4 73,9 76,5 74,1 65,0 54,0 80,0

80.2 72,7 76,6 75,4 74,9 77,4 75,2 66,2 55,6 81,0

84.2 73,4 77,6 75,8 75,6 77,9 75,7 67,1 56,6 81,5

88.2 73,4 77,4 75,8 75,6 78,0 75,6 66,9 56,0 81,5

93.2 73,9 77,9 76,4 76,2 78,5 76,1 67,4 56,3 82,0

100.2 73,9 77,9 76,4 76,0 78,3 76,2 67,6 56,5 82,0

106.3 73,9 77,9 76,4 78,5 78,1 76,3 67,8 56,7 82,0

Octave band [Hz]

Model TotalKAPPA V SR /LN 63 [dB] 125 [dB] 250 [dB] 500 [dB] 1000 [dB] 2000 [dB] 4000 [dB] 8000 [dB] dB(A)

Lcc Lcc Lcc Lcc Lcc Lcc Lcc Lcc Lcc65.2 71,0 74,9 74,0 72,1 73,2 73,2 63,1 54,1 78,0

73.2 70,5 74,7 73,9 71,7 73,9 72,8 62,8 53,7 78,0

80.2 73,0 76,0 74,7 72,8 74,8 73,8 64,1 53,8 79,0

84.2 73,0 76,4 74,7 72,8 74,8 73,8 64,3 54,0 79,5

88.2 72,8 76,5 74,8 73,3 76,0 73,6 64,9 54,5 79,5

93.2 73,5 76,9 75,4 75,1 76,3 74,1 65,4 54,3 80,0

100.2 73,3 77,1 75,7 75,0 76,2 74,0 65,2 54,3 80,0

106.3 73,1 77,3 76,0 74,9 76,1 73,9 65,0 54,3 80,0

Octave band [Hz]

Blue Box 10

2.2 LIFTING AND SITE HANDLING

Avoid sudden movements and jolts when unloading and positioning the unit. Internal handling proceduresmust be conducted with care. The unit must be lifted using spreader bars. Do not exert leverage on thecomponents of the machine. The unit must be lifted by inserting steel tubes through the lifting attachmentsshown by the relative labels (yellow arrow). The unit must be lifted by harnessing it as shown in figure 1: useropes or straps of sufficient length. The width of the spreader bars must not be less than that of unit.

1. FIELD OF APPLICATION

The equipment is designed for cooling (chiller only versions) or cooling/heating (heat pump versions) water, whichis usually applied to air conditioning or refrigeration systems. Units must be used exclusively within the operatinglimits specified in Section 4.

1.1 INTRODUCTION

- When installing or servicing the unit, it is necessary to strictly follow the rules described in this manual, toconform to all the items detailed on the unit labels and take any necessary precaution.

- Pressure in refrigerant circuits and danger from electrical shock can be hazardous when installing or servicing theunit.

Any work on the unit must be carried out only by trained personnel.

Attention: before repairing or servicing the unit, ensure that the electricalsupply is disconnected.

The warranty will be invalid if the rules described in this manual are not observed and if any modifications aremade to the unit without prior authorisation of the manufacturer.

2. INSPECTION, TRANSPORT, SITE HANDLING

2.1 INSPECTION

After receiving the unit, immediately check its integrity. The unit will have left the factory in perfect conditiontherefore on receiving the unit any damage must be verbally described to the carrier and recorded on the DeliveryNote which must be signed by both parties. Blue Box or their Agent must be informed, as soon as possible, of theextent of the damage.The Customer should prepare a written statement and photographic evidence regarding any severe damage.

Blue Box 11

Figure 1

1

2

Caution: ensure that the method of lifting does not allow the unit to slipfrom chains and slings or turn-over or slide from lifting devices.

(1) Side panel protection (not supplied)(2) Lifting holes

Blue Box 12

3. SAFETY PRECAUTIONS

3.1 DEFINITION OF DANGER ZONE

Only authorised operators must be allowed in the vicinity of the unit.

- The external danger zone concerns a space of approximately 2 m in width around the perimeter of the machine.Access to this area must be prevented by a suitable enclosure if the unit is located in an unprotected area thatis easily accessible to unauthorised persons.

- The internal danger zone is defined as the interior of the machine. Access to the interior of the machine mustnot be permitted to unqualified personnel and never before the machines’ electrical supply has been disconnected.

3.2 SAFETY PRESCRIPTIONS

The unit is designed and built in accordance with the PED 97/23CE rules, to ensure the maximum level of safety.To avoid possible situations of risk adhere to the following rules at all times:

- All work on the unit must be performed by qualified personnel. Before working on the unit, ensure that designatedpersonnel are conversant with the documentation supplied. Always ensure there is a copy of the documentationin the immediate vicinity of the unit.

- Use appropriate personal safety equipment (gloves, helmet, safety goggles, safety footwear, etc.) for allmaintenance and control operations on the unit.

- Use only tools and equipment that are in good working order.

- The fans have protective grilles to prevent accidental contact. Use the maximum caution to avoid inserting ordropping objects through the grilles.

- The exchanger coils have sharp edges. Do not touch the coils without using suitable protection.

- The compressor compartment contains various high temperature components. Adopt maximum caution whenworking in the vicinity of the compressors and avoid touching any parts of the unit without appropriate protection.

- Do not work within the theoretical discharge trajectory of the relief valves.

Blue Box 13

MECHANICAL HAZARDS

Operating mode Analysed risk or hazard Solution adopted Normal operating regime Maintenance

Stability Because of their intrinsic characteristics, the units are not associated with problems of possible falling or tipping while in operation. Carefully read the items described in this manual concerning the methods of positioning the unit.

Handling during transport and installation.

Stability The unit's base frame has specific lifting holes; the positions of which are marked with yellow decals. Following this procedure will eliminate the risk of the unit tipping. Carefully read the items descriptions in this manual concerning the methods of handling the unit.

Normal operating regime Maintenance

Pipeline bursts. Pipes are rigidly anchored to reduce the degree of vibration.

Normal operating regime

Surfaces, sharp corners and edges.

The machine is designed and built in such a way as to minimise the presence of sharp corners and edges as far as possible.

Maintenance Surfaces, sharp corners and edges.

In the interior parts of the unit it is not possible to totally eliminate risks from the presence of surfaces, sharp corners and edges. The operating, installation, and maintenance manual specifies that maintenance operations should be carried out exclusively by qualified personnel, and provides indications of the protective equipment to be used.

Normal operating regime

Cutting or severing. The moving parts of the unit are located in clearly defined areas. Specifically, the fans are enclosed in an inaccessible compartment and are equipped with an upper protection grille to UNI EN 294. All the protections supplied to limit and enclose the fan compartments cannot be removed without the use of special tools.

Maintenance Cutting or severing. The moving parts of the unit are located in clearly defined areas. Specifically, the fans are enclosed in an inaccessible compartment and are equipped with an upper protective grille to UNI EN 294.

Normal operating regime

Cutting or severing. All units are supplied as standard with specific protection grilles designed to protect against accidental contact with the finned coils, which can cause minor cuts to the hands.

Normal operating regime

Entanglement, dragging, impact.

The moving parts of the unit are located in clearly defined areas. Specifically, the fans are enclosed in an inaccessible compartment and they are equipped with an upper protective grille to UNI EN 294. All the protections supplied to limit and enclose the fan compartments cannot be removed without the use of special tools.

Blue Box 14

Operating mode Analysed risk or hazard Solution adopted Maintenance Entanglement, dragging,

impact. The moving parts of the unit are located in clearly defined areas. Specifically, the fans are enclosed in an inaccessible compartment and they are equipped with an upper protective grille to UNI EN 294.

Normal operating regime Maintenance

Projection of high pressure jets of fluid - Explosion hazard

All units are designed and manufactured in accordance with rule EN 378-2 and are equipped with relief valves to eliminate the risk of pressure bursts. The outlet from relief valves must be piped appropriately to eliminate risks associated with the expulsion of gas at high pressure from the machine.

Operating mode Analysed risk or hazard Solution adopted Normal operating regime Maintenance

Burns caused by high temperatures.

Most of the pipelines that could cause burns, when touched, are lagged with heat insulating material.

Operating mode Analysed risk or hazard Solution adopted Normal operating regime Maintenance

Hearing damage. All units are designed and built with the aim of reducing noise emissions to the minimum.

Operating mode Analysed risk or hazard Solution adopted Contact with electrically live parts (direct contact). Elements carrying electrical current in the case of faults. Inappropriate insulation.

Normal operating regime Maintenance

Radiated heat due to short-circuits or overloads.

All units are designed and built in compliance with harmonised standard EN 60204-1.

MECHANICAL HAZARDS

THERMAL HAZARDS

NOISE-RELATED HAZARDS

ELECTRICAL HAZARDS

Blue Box 15

REFRIGERANT SAFETY DATA - R407C

Identification of the preparation:

407C

Synonyms: HFC-32lHFC-125IHFG134a Formula: Mixture

1. IDENTIFICATION OF THE SUBSTANCE

1.1

EE-No: difluoromethane (HFC-32) : 200-839-4 1-1-1-2-tetrafluoroethane UHFC-134a) : 212-377-0 pentafluoroethane (HFC-125) : 206-557-8

Chemical Name CAS-No - Wt % - Symbol(s): & phrases "R" difluoromethane 75/10/5 - 23 - F+;R12 1-2-2-2-tetrafluoroethane 811/97/2 - 52

2. COMPOSITION / INFORMATION ON INGREDIENTS

pentafluoroethane 354/33/ 6 - 25 3. HAZARDS IDENTIFICATION:

3.1 Most important hazards:

Liquefied gas: may cause frostbite. Contact with eyes may cause irritation.

Eyes Rinse immediately with plenty of water for at least 15 minutes. Keep eye wide open while rinsing. If symptoms persist, call a physician.

Skin Liquefied gas may cause frostbite. Wash frostbitten areas with plenty of water. Do not remove clothing. Wash off with warm water. if skin irritation persists, call a physician.

Inhalation Move to fresh air in case of accidental inhalation of vapours. Oxygen or artificial respiration if needed. Do not apply artificial respiration if patient is breathing; Consult a physician after significant exposure. Do not give adrenaline or similar drugs.

Ingestion Do not induce vomiting without medical advice. Call a physician immediately. Do not give drugs from adrenaline-ephedrine group.

4. FIRST-AID MEASURES:

4.1

General advice Consult a physician alter significant exposure.

5.1 Suitable extinguishing media:

The product itself does not burn. Extinguish with carbon dioxide, dry chemical, foam or water spray. Use extinguishing measures that are appropriate to the environment.

5.2 Extinguishing media which must not be used for safety reasons:

None

5.3 Specific hazards: Possibility of generating hazardous reactions during a fire due to the presence of F and/or Cl groups. Fire or intense heat may cause violent rupture of packages.

5.4 Special protective equipment for fire-fighters:

In case of fire, west a self contained breathing apparatus. Protective suit.

5. FIRE-FIGHTING MEASURES:

5.5 Specific methods: Standard procedure for chemical fires. In the event of fire, cool tanks with water spray.

6.1 Personal precautions: Use personal protective equipment. Evacuate personnel to safe areas. Do not breath vapours or spray mist. Ensure adequate ventilation.

6. ACCIDENTAL RELEASE MEASURES:

6.2 Methods for cleaning up:

Shut off leaks it without risk. Solid evaporates. Ensure adequate ventilation.

Blue Box 16

REFRIGERANT SAFETY DATA - R407C

7.1 Handling: Keep away from heat, sources of ignition. Do not puncture or drop container, Provide sufficient air exchange and / or exhaust in work rooms.

7. HANDLING AND STORAGE:

7.2 Storage: Keep containers tightly closed in a cool, well-ventilated place. Store in a cool and shaded area. Do not expose to temperatures above 50 °C. Keep tightly closed.

8.1

Engineering measures to reduce exposure:

Ensure adequate ventilation, especially in confined areas.

Personal protection equipment:

Respiratory protection: In case of insufficient ventilation wear suitable respiratory equipment, preferably a compressed airline breathing apparatus.

Hand protection: Impervious butyl rubber gloves. Eye protection: Wear as appropriate: safety glasses, gaggles, Wear face-shield

and protective suit for abnormal processing problems.

8.2

Skin and body protection:

Chemical resistant apron, long sleeved clothing, safety shoes.

8. EXPOSURE CONTROLS / PERSONAL PROTECTION:

8.3

Exposure limit(s): 1-1-1-2-tetrafluoroethane 1000 ppm (TWA); difluoromethane: 1000 ppm (TWA); pentafluoroethane: 1000 ppm (TWA)(AIHA);

9.1 Stability: Stable at normal conditions. No decomposition if stored and applied as directed. Decomposition starting from 250°C.

9.2 Conditions to avoid: Do not expose to temperatures above 50 °C. Fire or Intense heat may cause violent rupture of packages.

9.3 Materials to avoid: alkaline metals (Na, K), alkaline earth metals (Ca, Mg), finely divided aluminium, zinc.

9. STABILITY AND REACTIVITY:

9.4

Hazardous decomposition products:

halogenated compounds, hydrogen halides (HF, HCI), carbonyl halides (COCl2), carbon monoxide, carbon dioxide (C02).

10.1 Acute toxicity: LC50/inh./4 h/rat : > 500000 ppm 10.2 Irritation : Skin: slightly irritant, may cause frostbite. Eyes: slightly irritant.

10. TOXICOLOGICAL INFORMATION:

10.4 Chronic toxicity: chronic inhalation, no-observed-effect level (NOEL):> 10000pprn rat.

11.1 Waste from residues / unused products:

Offer surplus and non-recyclable solutions to an established disposal company. In accordance with local and national regulations. S59 - Refer to manufacturer/supplier for information on recovery/recycling.

11. DISPOSAL CONSIDERATIONS:

Contaminated packaging:

Do not reuse empty containers. Empty pressure vessels should be returned to supplier.

No. O.N.U. 3340 12. TRANSPORT INFORMATIQN: ADR/RID UN 3340 Refrigerant gas R407C, 2, 2° A, ADR/RID

Label: 2

Blue Box 17

3.3 POSITIONING

Read the following points carefully when choosing the most suitable site for the unit and its connections:

- dimensions and connection point of hydraulic pipelines;- location of the electrical power connection point;- accessibility for maintenance and repair work;- loading capacity and compactness of the supporting surface;- ventilation of air-cooled condenser;- orientation and exposure to sunlight; as far as possible the condenser coil should not be exposed to direct

sunlight;- direction of prevailing winds: do not position the unit in such a way that prevailing winds can cause air recirculation

at the condenser coil;- type of support surface: to limit the risk of overheating, do not install the unit on a dark coloured surface (e.g.

bitumen roofing membranes and compounds);- possible sound reverberation.

All models in the KAPPA V SR series are designed for exterior installation: to avoid the risk of air recirculationunits must not be covered by a shelter roof or located under trees (even if the unit is only partially covered).It is advisable to make a supporting plinth, perfectly levelled and horizontal, of dimensions commensurate withthe footprint of the unit. This precaution is of the greatest importance if the unit is to be located on unstableground. Picture 2 shows a typical supporting plinth structure.

Figure 2

Plinth slab

Sealant

Cork underlayment

Soil

15-20 cm

Blue Box 18

Figure 3

The floor slab should be:

- made with a proper foundation raised 15-20 cm above ground level,- with a cork underlay sealed around the perimeter,- flat, horizontal and capable of supporting 150% of the unit’s operating weight.- at least 30 cm longer and wider than the unit.

The unit transmits a low level of vibration to the supporting structure: it is recommended that a layer of rigidrubber sheeting is placed between the base of the unit and the supporting surface.If a higher level of vibration damping is required, use anti-vibration mounts (contact Bluebox for details).

When installing on roofs or intermediate floors, units and piping must be isolated from walls and ceilings.The units should not be installed next to offices, bedrooms, or other areas where low noise levels are a necessity.To avoid excess sound reverberation do not install the units in narrow or confined spaces.

Blue Box 19

4. INSTALLATION

4.1 INSTALLATION CLEARANCES

It is important that an adequate air volume is available at the intake and exhaust sides of the condenser coil. It isessential to avoid air recirculation between the intake and exhaust sides to prevent a reduction of the ratedperformance levels and unit operating problems or a possible stop of normal unit operation. The minimumclearances required for satisfactory operation of the unit is as follows (refer to figure 4):

- coils side: minimum distance 0.75 meters.- top: no impediments that obstruct the air discharge.- electrical panel side: 1 meter (see dimensional drawings)- hydraulic connection sides: 0,75 metre for pipe run location.

(*) It is recommended that sufficient space is allowed for shell and tube heat exchanger withdrawal.

High walls near the machine may interfere with correct functioning. When units are side by side the minimumdistance between them should be 3 metres (see figure 4).

Figure 4

SIDE BY SIDE UNITS

3 m min.

1.5 m

0.75 m (*) 1 m

Blue Box 20

Figure 5

Figure 6

4.2 ANTI-VIBRATION ISOLATORS (option)

It is recommended that the unit is installed on rubber or spring anti-vibration mountings, supplied as an option, toreduce vibrations transmitted to the building structure. It is advisable to use rubber isolators for units installed inthe basement, or ground floors in contact with the earth, and spring isolators for units installed on intermediatefloors.

The anti-vibration isolators must be installed before the unit is positioned.Ensure that during lifting the unit is firmly secured with straps.

4.2.1 Rubber Anti-Vibration Isolators

Rubber isolators are made of an upper metallic bell with a fixing screw to the base-frame of the unit. The isolatoris fixed at the foundation via 2 holes on the flange. On the flange there is a number (45, 60, 70 ShA) whichidentifies the hardness of the rubber isolator. The dimensional drawing, enclosed in the machine, shows the unitfootprint with the position and weight of each isolator.

Rubber/metal anti-vibrationi so la torDesigned to reduce the vibration.

4.2.2 Spring Anti-Vibration Isolators

Anti-Vibration Isolators with cylindrical springs are recommended to reduce any mechanical and sound vibration.Each isolator has a code which identifies the maximum permitted load.When installing spring Anti-Vibration Isolators, it is compulsory to carefully follow all recommendations and assemblyinstructions. The dimensional drawing, enclosed in the machine, shows the footprint with the position and weightof each isolator.

Standard spring anti-vibration isolatorsThe isolator is fixed to theunit's baseframe with a nutand two bolts and washers.

Spring anti-vibrationisolators for heavyloadsThe load of the unit issupported by the fullsurface of the isolators. Theload is not exerted on thebolt.

Blue Box 21

4.3 WATER PIPING CONNECTIONS

Unit water pipework must be installed in accordance with national and local regulation and codes.Follow the recommendations below when designing the water piping circuit (refer to the diagrams included in thismanual).- Piping should be connected to the unit with flexible joints, to avoid vibration transmission and allow for thermal

expansion (the same procedure should be adopted for the circulating pumps).

- The following devices should be located on the piping system:- Isolating/regulating valves, temperature gauges or thermometer pockets, pressure gauges or binder points

required for servicing operations.- Serviceable mesh strainer, with a filtration level no larger than 1mm, located on the unit inlet to prevent debris

from entering the heat exchangers.- Vent valves, to be installed in the upper parts of the circuit, for air bleeding.- Expansion device with accessories for circuit pressurisation, water thermal expansion compensation and system

filling.- Unload valve and if necessary drainage tank for circuit emptying during maintenance and seasonal stop.

Blue Box 22

REC

OM

MEN

DED

HY

DR

AU

LIC

CIR

CU

IT D

IAG

RA

M F

OR

KA

PPA

V S

R

1Pu

mp

2Ex

pans

ion

tank

3Re

lief

valv

e4

Che

ck v

alve

5Ba

ll va

lve

6Ta

nk7

Wat

er p

ress

ure

gaug

e

8Th

erm

omet

er9

Wat

er fi

lter

10Bl

eed

valv

e11

Flex

ible

con

nect

ion

12C

ircui

t fill

ing

unit

13W

ater

dra

in14

Flow

switc

h

LEA

VIN

G U

SER

WA

TERE

NT

ER

ING

USE

R W

ATE

R

Blue Box 23

HYDRAULIC CIRCUIT DIAGRAM VERSION KAPPA V SR /ST 2PS

Blue Box 24

If incorrectly connected the antifreeze thermostat will not operate and the evaporator may freeze.On all units the hydraulic connections are made by flexible joints and welding pipe.

EVAPORATOR WATER

The water inlet and outlet must be connected in the positions indicatedas labelled on the unit.

4.4 EVAPORATOR WATER PIPE CONNECTIONS

A constant water flow to the evaporator must be guaranteed at al loperating conditions to prevent l iquid refrigerant from entering thecompressor and causing irreparable damage.

Compressors start and stop often due to changes in cooling demand. In hydraulic circuits with low water volume,where the thermal inertia action is low, it is advisable to verify that the water volume equals or exceeds thefollowing ratio:

24 · QCOMPTOTM>= ---------------------

Nwhere:

M = system water content [kg] QCOMPTOT = unit cooling capacity [kW]

N = number of capacity steps

If the water volume does not reach the value given by the formula, it is advisable to provide the circuit with astorage vessel to increase the volume (tank + circuit) to match the result of the formula.The chilled water piping and storage vessel must be insulated to prevent condensation on the pipe surfaces andto avoid circuit performance losses.

It is mandatory to install a flow switch (supplied with the unit) on theevaporator water outlet connection identified by the following decal:

EVAPORATOR WATER

It is compulsory to install a metallic filter, on the water inlet piping. If afilter is not installed the warranty will be terminated immediately.

Blue Box 25

Figure 7

Caution: When making hydraulic connections never use naked flamesclose to or inside the unit.

4.5 FLEXIBLE JOINTS

Flexible joints allow axial movements due to thermal expansion, eliminate vibrations and allow for easy assemblyand disassembly of the jointed parts.To assemble the joint proceed as follow:

1) Disconnect bolts and open the joint .

2) Move the gasket on the heat exchanger connection towardsthe shell .

3) Weld the counter-connection to the hydraulic circuit pipe.

4) Line up the connection and the counter-connection, placethe gasket in the original position and if possible lubricate iton contact areas with a non-aggressive oil or grease.

5) Assemble the joint and tighten the nuts.

Shell

Connection

Gasket

C o u n t e rconnection

Joint

ShellConnection

Gasket

C o u n t e rconnection

Pipe Weld

Connection

Gasket

Joint

Blue Box 26

Figure 8

Desuperheater recoverywater outlet

Desuperheater recoverywater inlet

Entering/leaving chilled water

4.6 DESUPERHEATER HYDRAULIC CONNECTION (optional)

For all units equipped with desuperheaters the connections, for the relative hydraulic circuit, are steel tubes withmale threads.The water inlet and outlet must be connected in the positions indicated as labelled on the unit (see fig. 8).

Heat recovery water inlet:

Heat recovery water outlet:

On HP version units the hydraulic connection to the desuperheater mustbe isolated during heat pump operation

IN

RECOVERY WATER

OUT

RECOVERY WATER

Blue Box 27

Figure 9

3-way valve

Recoverywater outlet

Recoverywater inlet

4.7 HEAT RECOVERY EXCHANGER HYDRAULIC CONNECTIONS (OPTIONAL)

For all units equipped with a recovery condenser, the relative hydraulic circuit connections are male threadedsteel pipes (the diameter depends on the unit's size)The units are equipped with a probe that monitors the temperature of the water returning from the system. Themicroprocessor controller enables recovery when necessary, disconnecting the fans, and restarting regular operationonce the water has reached the desired temperature. If faults occur on the recovery condenser the microprocessor controller restarts the fans.The calibration values of the thermostat and pressure switches are given in the relevant controller instructionmanual.

For units equipped with a recovery condenser:

The water inlet and outlet must be connected to the recovery circuit inthe positions indicated as labelled on the unit.

IN

ACQUA RECUPERO RECOVERY WATER

OUT

It is mandatory to install a three-way modulating, valve with water tem-perature probe, on the inlet to the unit to ensure that, at steady stateconditions, the inlet water temperature is not less than 30 °C.

DIAGRAM WITH 3-WAY VALVE

Blue Box 28

Figure 10

Alternatively: a condensing pressure control valve for each refrigerantcircuit that ensures an average condensing temperature of at least 35°C.

DIAGRAM WITH CONDENSING PRESSURE CONTROL VALVE

4.8 PRESSURE RELIEF VALVES

Pressure relief valves are fitted on the high pressure side and low pressure side of the refrigerant circuit. Thevalves must be vented, to outdoors, through a vent pipe.The vent pipe must be sized no smaller than the relief valve and it must not be supported from the valve.

Caution: The relief valve must be directed into a safe zone where noinjuries can be caused to people.

Ø×

Condensing pressure control valve

Recoverywater outlet

Recoverywater inlet

To the refrigerant circuit

Blue Box 29

4.9 WATER FLOW RATE TO EVAPORATOR

The nominal water flow rate is based on a 5 °C temperature difference between inlet and outlet in relation to thesupplied cooling capacity.

The maximum permissible flow rate is that which results in a temperature difference of 3 °C: higher flow rates willlead to excessive pressure drops and could damage the evaporator.

The minimum permissible flow rate is that which results in a temperature difference of 8 °C or a pressure drop ofno less than 10 kPa: lower flow rates will lead to excessively low evaporation temperatures with consequenttripping of safety devices and shutdown of the unit.

4.10 CHILLER WATER TEMPERATURE (summer cycle)

The minimum evaporator leaving water temperature is 6 °C; for lower water temperatures at the evaporatoroutlet refer to section 6.6.The maximum water temperature at the evaporator inlet is 20 °C. In the case of higher temperatures specificsolutions are necessary (dual circuits, three-way valves, by-pass, storage tanks): consult the Bluebox EngineeringDepartment to discuss the most suitable solution for your application.

4.11 HOT WATER TEMPERATURE (winter cycle)

The minimum water temperature at the condenser inlet, once the system is operating in steady state conditions,must not be lower than 28 °C: lower values could result in operating anomalies of the compressor with theconsequent risk of compressor breakdown.The maximum water temperature at the condenser outlet must not be higher than 47 °C. In the event of highertemperatures the safety devices will trip causing the unit to shut down.

4.12 AMBIENT AIR TEMPERATURE

The units are designed and built to operate with ambient air temperatures within the limits shown on the operatinglimits diagrams. Contact Bluebox if the unit is required to operate at different ambient temperatures.It should be noted that the performance of heat pump units decreases significantly at lower ambient temperatures.(below 0 °C).The units can be optionally equipped with an electric element for heating the evaporator. The heater cuts in,when the machine is switched off, if the water temperature in the evaporator falls below the freeze protectioncalibration temperature.

4.13 FAN SPEED CONTROL (optional)

If the unit is required to operate at ambient air temperatures less than 15 °C a fan speed controller must beincluded. With fan speed control the unit can function correctly, at low ambient temperatures, by reducing the airflow supplied to the condenser so that it operates within acceptable parameters.This device can also be used to reduce unit sound levels as the ambient ait temperature reduces (for instanceduring the night).

This control is calibrated and factory tested.

Warning: speed control calibration settings must not be altered. If itproves necessary to alter speed calibration settings, this task must beentrusted to a skilled engineer, who should refer to the attached instructionsheet.

Blue Box 30

4.14 OPERATION WITH LOW TEMPERATURE CHILLED WATER AT EVAPORATOR

Units from the normal production range are not designed to operate withchilled water temperatures lower than 6 °C, at the evaporator outlet. Tooperate outside this limit the unit may require structural modifications. Ifthis is necessary contact Bluebox.

With temperatures lower than 6 °C, the hydraulic circuit should be filled with a suitable water and antifreezesolution. In such cases the service thermostat and the freeze protection thermostat must be reset:

These calibrations are normally factory set.

The ethylene glycol percentage must be selected in relation to the required chilled water temperature.See table 1.

TABLE 1 - FREEZING POINT FOR WATER-ANTIFREEZE MIXTURES

If ambient temperatures lower than the freezing point of water can beexpected, antifreeze mixtures in the above indicated percentage mustbe utilized.

In the case of ST versions with a glycol content greater than 30% pumpswith special seals must be specified at the time of the order.

LIQUID OUTLET TEMPERATURE

OR MINIMUM AMBIENT TEMPERATURE (°C)

FREEZING POINT (°C) -5° -10° -15° -20° -25° -30° -35° -40° -45°

ANTIFREEZE

ETHYLENE GLYCOL 6 22 30 36 41 46 50 53 56

PROPYLENE GLYCOL 15 25 33 39 44 48 51 54 57

METHANOL 8 14 20 26 30 34 38 41 45

CALCIUM CHLORIDE 9 14 18 21 24 26 27 28 30

TEMPER -20

TEMPER -40 ---

TEMPER -60

TIFOXITE 50 60 63 69 73 ---

FREEZIUM 10 20 25 30 34 37 40 43 45

PEKASOL 50 59 68 75 81 86 90 ---

-30° -35°+0° -5° -10° -15° -40°

% BY WEIGHT

40

50

T -20°C

T -40°C

T -60°C

---

-20° -25°

Blue Box 31

OPERATING LIMITS

KAPPA V SR - Refrigerant R407C

0

5

10

15

20

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

Refrigeratore / Chiller

RaffreddamentoCooling

Con dispositivi opzionali per bassetemperature dell’aria esterna.

With low ambient temperature kit.

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 500

5

10

15

20

25

30

35

40

45

50

55

Pompa di caloreHeat pump

RiscaldamentoHeating

RaffreddamentoCooling

Con dispositivi opzionali per bassetemperature dell’aria esterna.

With low ambient temperature kit.

Wat

er le

avin

g te

mpe

ratu

re [°

C]

Wat

er le

avin

g te

mpe

ratu

re [°

C]

Ambient air temperature [°C]

Ambient air temperature [°C]

The water temperature rise for all versions must be between 3 °C (min) and 8 °C (max)

Blue Box 32

EVAPORATOR PRESSURE DROP

The water temperature rise for all versions must be between 3 °C (min) and 8 °C (max)

4020

20

30

50

60

70

8090

100

40

3010

65.2

73.2 80.2

50 60

84.2-88.2-93.2

100.2 106.3

25 35 5545Portata acqua [l/s]

Water Flow

Per

dit

a d

i car

ico

[kP

a]P

ress

ure

dro

p [

kPa]

[ l / s ]

Blue Box 33

PUMPS AVAILABLE PRESSURE - MODEL KAPPA V SR /ST 2PS

PREVALENZA UTILE

0

50

100

150

200

250

300

350

400

450

500

20 30 40 50 60

Portata acqua [l/s]Water flow

Prev

alen

za u

tile

[kPa

]A

vaila

ble

pres

sure

65.2-73.2 80.2

84.2-88.2

93.2

100.2

106.3

Water flow [l/s]

Ava

ilab

le p

ress

ure

[k

Pa]

Blue Box 34

ELECTRICAL PANEL LAY OUT

MODELS 65.2 - 100.2

Blue Box 35

ELECTRICAL PANEL LAY OUT

MODEL 106.3

Remote electric panelOption - ST version

See sheet 2

Blue Box 36

KEY TO ELECTRICAL COMPONENT PART NUMBER

A2 CONTROL BOARDA3 CONTROL BOARDA5 FAN SPEED CONTROLA6 FAN SPEED CONTROLA16 SAFETY THERMOSTAT 1A17 SAFETY THERMOSTAT 2A18 SAFETY THERMOSTAT 3A27 PHASE SEQUENCE CONTROLA51 EXPANSION VALVE CONTROL CHA52 3 CIRCUITS EXPANSION VALVE CONTROLB13 OVERLOAD CUT-OUT PUMP 1B14 OVERLOAD CUT-OUT PUMP 2C1 POW. FACT. CORRECT. CONDENS. COMPR. 1C2 POW. FACT. CORRECT. CONDENS. COMPR. 2C3 POW. FACT. CORRECT. CONDENS. COMPR. 3C46 POW. FACT. CORRECT. CONDENS. PUMPSFR1 OVERLOAD CUT-OUT COMPRESSOR 1FR2 OVERLOAD CUT-OUT COMPRESSOR 2FR3 OVERLOAD CUT-OUT COMPRESSOR 3FR13 OVERLOAD CUT-OUT PUMP 1FR14 OVERLOAD CUT-OUT PUMP 2FU1 FUSES COMPRESSOR 1FU2 FUSES COMPRESSOR 2FU3 FUSES COMPRESSOR 3FU13 FUSES PUMP 1FU14 FUSES PUMP 2FU19 FUSES FAN SPEED CONTROL 1FU20 FUSES FAN SPEED CONTROL 2FU21 FUSES FAN 1FU22 FUSES FAN 2FU23 FUSES FAN 3FU24 FUSES FAN 4FU25 FUSES FAN 5FU26 FUSES FAN 6FU27 FUSES FAN 7FU28 FUSES FAN 8FU40 FUSES HEATERSFU41 FUSES CAPAC. POW. FACT. CORRECT. COMPR. 1FU42 FUSES CAPAC. POW. FACT. CORRECT. COMPR. 2FU46 FUSES CAPAC. POW. FACT. CORRECT. PUMPSFU50 FUSES AUX. TRANSFORMERFU51 AUX. CIRCUIT FUSESFU52 FUSE CONTROL

FU56 PHASE SEQ. RELAY FUSESKA1 VOLTAGE RELAYKA2 RELAIS ALARM FAN.KA5 PHASE SEQUENCE RELAYKM1 CONTACTOR LINE COMPRESSOR 1KM2 CONTACTOR LINE COMPRESSOR 2KM3 CONTACTOR LINE COMPRESSOR 3KM5 CONTACTOR DELTA COMPRESSOR 1KM6 CONTACTOR DELTA COMPRESSOR 2KM7 CONTACTOR DELTA COMPRESSOR 3KM9 CONTACTOR STAR COMPRESSOR 1KM10 CONTACTOR STAR COMPRESSOR 2KM11 CONTACTOR STAR COMPRESSOR 3KM13 CONTACTOR PUMP 1-1KM14 CONTACTOR PUMP 2-1KM15 CONTACTOR PUMP 1-2KM16 CONTACTOR PUMP 2-2KM17 CONTACTOR PUMP 1-3KM18 CONTACTOR PUMP 2-3KM21 CONTACTOR FAN 1KM22 CONTACTOR FAN 2KM23 CONTACTOR FAN 3KM24 CONTACTOR FAN 4KM25 CONTACTOR FAN 5KM26 CONTACTOR FAN 6KM27 CONTACTOR FAN 7KM28 CONTACTOR FAN 8KM40 CONTACTOR EL. HEATER EVAPORATORKM41 CONTACT. CAP. POW. FACT. CORRECT. COMPR. 1KM42 CONTACT. CAP. POW. FACT. CORRECT. COMPR. 2KM46 CONTACT. CAP. POW. FACT. CORRECT. PUMPSKT1 RELAIS 1 START D/YKT2 RELAIS 2 START D/YKT3 RELAIS 3 START D/YKT5 RELAIS START 1KT6 RELAIS START 2KT7 RELAIS START 3QS MAIN SWITCHST1 TEMPERATURE SENSORTC1 AUX. TRANSFORMER

Blue Box 37

Figure 11

4.15 ELECTRICAL CONNECTIONS

4.15.1 General

Electrical connections must be made in accordance with the information given on the electrical drawing attachedto the unit and in compliance with the applicable local regulations.

An Earth (ground) connection is compulsory. The installer must connect the earth cable with a dedicated terminalon the earth bar in the electrical board (refer to the illustration on the following page) labelled PE.

It must be verified that the electrical supply corresponds to the unit electrical nominal data (tension, phases,frequency) indicated on the label on the front panel of the unit.

Line voltage fluctuations must not be more than ±5% of the nominal value, while the voltage unbalance betweenone phase and another must not exceed 2%. If these tolerances are not possible contact Blue Box to provide thenecessary devices.

Check that the line is connected with the correct phase sequence.

The cable inlet point is created by drilling a hole in the side or base of the electrical enclosure, depending on themodel.

The control circuit is derived from the power supply through a transformer located inside the electrical panel.The control circuit is protected by fuses.

Electrical cable anchorage: anchor the electrical power cables with fixingsystems able to withstand pulling and torsional stress.

Before any operation on the electrical section, be sure that the electricsupply is disconnected.

Power cable and l ine protection must be sized according to thespecification indicated on the wiring diagram and the documents suppliedwith the unit.

The crankcase heaters must be connected at least 12 hours before startingthe unit; the heaters are automatically connected when the maindisconnect switch is set to the ON position.

The electrical supply must be within the limits shown. If this is not thecase the warranty will be terminated immediately.

4.15.2 Power supply to crankcase heaters

1) Close the main disconnect switch by turning it from position “0” to position “1”2) Check that the word “OFF” is shown on the display3) Ensure that the unit is in “OFF” status and that the external enabling contact

is open4) After a few moments, if the phase sequence is incorrect the alarm “INCORRECT

PHASE SEQUENCE” will be displayed. In this case invert the connections oftwo of the power line phase wires.

5) Leave the unit in this condition for at least 12 hours to allow the crankcaseheaters to perform their function

Blue Box 38

4.15.3 Potential free contacts

The following potential free contacts are available:- 1 potential free contact for general alarm (terminals 100 - 101 - 102)- 1 potential free contact for each compressor (option)- 1 contact for each pair of fans (option)- 1 contact for each pump (option - ST models)

4.15.4 Circulating pump electrical connections

The external interlocks of unit must close for the unit to operate. The normally open external water circulatingpump contactor terminals must be wired in series with terminals 1 and 2, on the unit control panel, to ensure thatthe chiller can only start after the pump is in operation.In ST units external enabling contacts 1-2 must be jumpered (unless they are required for system functions).

Turn on the pump before the unit starts and stop it after the unit hasstopped (recommended time delay: 60 sec.).

4.15.5 Microprocessor controllers

Chillers and heat pumps KAPPA V SR are equipped with the pCO2 microprocessor controller.

The pCO2 electronic microprocessor controller with the DBBB0*P20Z program is designed to manage chiller andheat pump units, with control of 2 compressors having 2 capacity steps each.The program configuration manages the total control of the air-cooled unit with plate exchangers includingcompressor start/stop times, safety devices and other auxiliary functions such as condensation control in coolingmode, evaporation control in heat pump mode, free-cooling, heat recovery and other functions described later inthis manual.The necessary hardware is optimised to obtain the maximum advantage from the available inputs and outputs;the connection between various circuit boards and the user interface terminal is achieved via the pLANE using thededicated RS485 serial connector for network connections.Each unit can also be connected to remote supervision and/or telediagnostics systems by means of an RS485serial line.

Detailed information on the operation of the above systems is provided in the specific controller manual suppliedwith the unit.

4.15.6 RS485 serial interface (optional)

All KAPPA V SR units can be equipped with a serial interface board for supervision or remotediagnostics functions by means of a computer.

The serial interface board plugs into a dedicated slot on the connection board.Connection to the supervision or remote diagnostics serial line is executed in compliance with standard RS485and is achieved by means of the serial interface boards.When the serial interface board is inserted the following communications protocols are available: Carel, Modbus-jbus, BacNet. If a connection is to be made with networks that utilise the Lon-Talk protocol, a dedicated boardmust be installed. In this case, a conversion gateway is not required.

Blue Box 39

Figure 12

4.15.7 User interface - Microprocessor pCO2

The back-lit LCD display comprises 4 lines and 20 columns.

In addition to the LCD display, the user interface is equipped with the following function keys (fig. 10):

“Menu” key: press this key from any menu to return to the opening menu.

Maintenance key: press this key to access the maintenance menus.

Print key: this key is currently not used.

"I/O" key: pressing this key opens the menus containing the status of the digital inputs and outputstogether with the values read on the analogue inputs and the value of the analogue outputs

“Clock” key: press this key to open the clock menus.

“Set” key: this key opens the menus in which the various operating set-points can be edited.

“Prog” key: this key opens the service menus.

Blue Box 40

"? info" key: pressing this key opens a menu in which the address of the component connected tothe terminal can be changed.

"Summer" key (blue) and "winter" key (red): in the case of chiller + heat-pump units,press these keys to select the required operating mode.

“ON/OFF” key: press this key to switch from Stand- by to ON or vice versa.

“Alarm” key: this key serves to mute the alarm buzzer, display any active alarms, and reset themin certain cases.

Arrow key: the arrow keys allow you to navigate through the menus; when an editablefield is selected, the arrow keys serve to change the current value.

“Enter” key: pressing this key allows you to access fields containing editable parameters and also toconfirm any changes you make to such parameters.

Blue Box 41

5. START-UP

5.1 PRELIMINARY CHECKS

- Check that the electrical connections have been made correctly, and that all terminals are well tightened.

- Check that the voltage on the RST terminals is 400 V ± 5% (or the unit’s rated value, in the event of unitssupplied to run on non-standard power supplies). If the mains voltage is subject to frequent fluctuations, consultour Engineering Department to discuss the necessary protection systems.

- Check that the display shows the gas pressure in the refrigerant circuit.

- Inspect the unit for refrigerant leaks using a leak detector if necessary.

- Check that the crankcase heaters are correctly supplied with power.

5.2 OPERATING DESCRIPTION

5.2.1 Introduction

The microprocessor control regulates the water temperature of the evaporator maintaining it at the set-pointvalue acting on the compressors management.As well as the compressors the controller manages the operation of other components of the chiller such as thepumps (ST version) and fans, with relative operating times and alarms, and “ancillary” functions such as condensationcontrol, etc., as described below.

Almost all the parameters referred to below (set-points, differentials, calibration, delays...) can be programmedby means of the various menus. Refer to the specific manual for the pCO2 controller.

5.2.2 Unit in stand-by mode

The unit is in stand-by mode when it is supplied with power but not actually enabled to operate.In this condition the display shows the values of the various machine parameters, but compressor is inhibited.When in stand-by mode the unit can be powered on.Power-on is obtained by pressing the “ON-OFF” button of the microprocessor control or via serial or an externalinterlock.

The heaters must be connected at least 12 hours before starting the unit;the heaters are automatically connected when the main disconnect switchis set to the ON position.

Significant leakage of R407C refrigerant in the gaseous state will alterthe percentages of the remaining mixture with consequent fall-off ofperformance.

- Verify that heaters are working correctly: after the warm up period the crankcase must be warm to the touchand must have at least a temperature 10 - 15 °C higher than ambient temperature.

- Check that all hydraulic connections are correctly installed and all indications on unit labels are observed.

- Check that the hydraulic system has been vent to eliminate any air remaining; charge it gradually and open thevent devices on the upper part, provided at the care of the installer together with an expansion tank of a propersize.

Blue Box 42

5.2.3 Enabling the unit

Start-up of the unit from stand-by mode can be achieved after closing the external enabling contact, by pressingthe “ON/OFF” button, or by means of a signal on the serial line.Activation of the controller outputs that manage the various sections of the chiller is executed in strict compliancewith the operating times. If the “ON” button is pressed before the external interlocks are closed, the displayindicates which of the external interlocks is not yet enabled.Operation of the pump has priority to the compressors, which can start only after the pump is running.

5.2.4 Pump management (ST units only)

If system pump control is included switching on the unit will automatically enable the pump.If there are two pumps (run and stand-by) they will be activated alternately when the programmed operating timelimit for each pump has elapsed.When the pumps are switched over both pumps will run in tandem, for a few seconds, to ensure a constant flowof water in the system circuit.When the unit is switched from active status to stand-by, if performed by opening an external permissive, thecurrently active pump of the ST unit will be stopped with a delay interval, after the disconnection of the lastcompressor in operation, making it possible to exploit the thermal inertia of the system.

5.2.5 Compressor start-up

The controller allows the compressors to be started if the flow switch input is closed within the compressor start-up delay time interval. If the flow switch input opens, after the compressor has started, the trip is retarded if itoccurs within the time programmed for the compressor stop.If the unit trips due to the opening of the flow switch input, the relative alarm is displayed.Starting and stopping of the compressors and capacity step control is managed by the controller in accordancewith the building cooling demands.

5.2.6 Chiller mode operation

In chiller operation, the controller lowers the water temperature value, maintaining it as close as possible to theprogrammed set-point.In the standard version, in which the control acts on the evaporator entering water, the management of compressoroperation and capacity steps is linked to the difference between the entering water temperature and the programmedset-point.

5.2.7 Heat pump mode operation

In heat pump operation, the controller increases the water temperature value, maintaining it as close as possibleto the programmed set-point.Management of compressor operation is performed in the same way as already illustrated for chiller modeoperation.

5.2.8 Evaporator low temperature chilled water protection

If the evaporator leaving water temperature is lower than the limit value programmed in the low temperaturechilled water protection set-point, the controller will stop all the compressors and activate the low temperaturewater alarm.This alarm must be reset manually and the compressor restarted only when the evaporator leaving water tempe-rature is equal to or higher than the alarm trip value, increased by the low temperature water differential.The low temperature water alarm can only be activated when the unit is switched on (in stand-by conditions thefreeze alarm is not operational).

5.2.9 Evaporator anti-freeze protection electric heater (optional)

Blue Box 43

In conditions that lead to tripping the freeze alarm, the controller energises the heater.The heater remains powered for the entire time that the conditions for the freeze alarm continue.Unlike the low water temperature alarm, which is enabled only when the unit is powered on, the anti-freezeheater can be energised when the machine is on stand-by.

5.2.10 Compressor operation

When the unit is running correctly and no general alarms are present, the microprocessor controller starts thecompressors in accordance with the water temperature reading.Compressor starts are staggered in accordance with preset delay intervals, thus avoiding excess input currentsurges.Before starting a compressor, the microprocessor checks the value of the delivery pressure by means of therelevant transducer, the status of the high pressure switch and the compressor motor windings temperature bychecking the thermal protection.

When the compressor has been started, tripping of any of the safety devices will cause the compressor to stopimmediately and an alarm will be displayed.While the compressor is running, discharge pressure and suction pressure are monitored constantly by means ofthe relevant sensors.

On unit start-up the first compressor is started with a delay, set on the microprocessor controller, after the start ofthe hydraulic system circulating pump.Once started, each compressor must run for a minimum operating period, unless a critical alarm should trip in themeantime.The critical alarms which can stop the compressor during the minimum operating time are the high pressurealarm and the compressor thermal cut-out alarm. Once stopped each compressor can be restarted only after aminimum idle time or after a minimum time interval between two consecutive starts has elapsed.The consecutive starting of two compressors or the consecutive starting of one compressor, is executed withminimum delay intervals equal to the capacity step activation time.Stopping compressors is also performed with a minimum programmed delay interval.

5.2.11 Compressors and capacity steps management

Start-up of the compressors is automatic when the reference water temperature changes with respect to theprogrammed set-point.Normally the reference water temperature is the value detected at the inlet to the chiller unit.

Two different working possibities are available as cooling demand increases:

- In the “FPM” working system the first step of the first compressor is energised, then the first step of the secondcompressor, then the first compressor operates at full load and finally the second compressor operates at fullload.

- In the “CPM” working system, the first step of first compressor is energised and than operates at full load, thanthe first step of the second compressor starts and finally the second compressors operates at full load.

As the cooling demand reduces, the capacity steps are unloaded in reverse to the load procedure: in the “FPM”system all compressors capacity steps reduce and the compressors are stopped, in the “CPM” mode for eachcompressor the capacity steps are first reduced and then the compressors are stopped.

An even distribution of operating hours over all compressors of the the unit is ensured by selecting the automaticlead/lag selection.

With the start rotation function active, the first compressor to start is the first one that previously stopped. The firstcompressor to start will be the one with the least operating hours.

The capacity control of compressors can be carried out either by steps or continuously.

Blue Box 44

With capacity step control, each solenoid valve represents one capacity power step.Upon request continous capacity step control is available.In continuous capacity step control, compressor power is adjusted by the movement of the step control cylinder,actuated by two solenoid valves; one to increase power and the other to reduce it.The cylinder moves in response to pulses by the solenoid valves; cylinder position and the degree of capacitycontrol is regulated by the controller, on the basis of the time necessary for the entire cylinder stroke.Compressor shutdown and start-up are always carried out at 25% of the compressor cooling capacity.

5.2.12 High and low pressure alarms

Discharge pressure (high pressure) and suction pressure (low pressure) are managed by the microprocessorcontroller through the relevant sensors.When a compressor is running, the controller checks that:- Discharge pressure is always lower than the safety value set for cooling or heating mode operation. If the values

are exceeded, the controller immediately stops the compressor and displays a high pressure alarm. The highpressure alarm can be reset manually on the controller only when the pressure detected by the dischargepressure sensor is lower than the value that caused the alarm to trip, less the differential value.

- The suction pressure is always higher than the safety value set for operation in cooling or heating mode. If thevalue read by the suction pressure sensor is lower than the limits set for the relative operating conditions, thecontroller will stop the compressor and generate a low pressure alarm. The low pressure alarm is not instantaneous,but operates after a preset delay interval, both in the starting phase and during the normal running of themachine. The low pressure alarm can only be deactivated manually at the controller. In all cases the lowpressure alarm can only be reset when the pressure detected by the suction sensor is higher than the value thatcaused the alarm to trip, plus the differential value. It is possible to program the number of permissible conse-cutive compressor starts before the unit shuts down in safety status.

5.2.13 Low ambient temperature kit (option - condensing control with fan speed regulator)

As the ambient air temperature decreases the necessary condensing pressure for correct operation of the chillercycle is maintained, within the machine operating range, by adjusting the cooling air flow through the condenser.Condensing pressure control is only active when the machine is operating in chiller mode.When the unit is operating in heat pump mode this function is inhibited and the fans are forced to their maximumspeed.The controller checks the condensing pressure and adjusts fan speed on the basis of the circuit with the highestpressure reading. The speed regulator adjusts fan speed with a phase control system that minimises problemsrelated to electromagnetic compatibility.Speed control is available over a 40-100% range. At the time of start-up the fans always run at 40% nominalspeed.

5.2.14 Changeover from chiller to heat pump and vice versa

The changeover from chiller to heat pump and back can be performed at any time, either by means of anexternal signal on a digital input, from the keypad, or via the serial line. The operating mode changeover must beonly seasonal and only with the unit off.After a mode changeover, the controller re-starts the unit in the new mode with a factory set minimum delaytime.The unit operates only with temperature control on the inlet (or return from the system).

5.2.15 Defrosting (heat pump units only)

During winter heat pump mode operation the finned coil of the air cooled condenser functions as an evaporator,cooling and dehumidifying ambient air.During heat pump operation, the evaporation pressure is monitored to prevent it from falling below a presetvalue. The evaporation control is active only during heating mode operation.Depending on the ambient air temperature and humidity conditions, condensate or frost will tend to form,consequently obstructing the free passage of air and causing thermal insulation. The frost that builds up on the

Blue Box 45

coil obstructs the passage of air and reduces the available heat exchange surface area (and thus the thermalefficiency) and can damage the heat exchanger.Defrosting is the procedure that eliminates the ice that has formed on the evaporator coil during heat pump modeoperation of an air/water unit.Defrosting is performed simultaneously for the entire unit.All heat pump versions are equipped with a control that activates an automatic coil defrost cycle when necessary.After starting however, the first defrost cycle will be started after a preset minimum operating time to allow theformation of sufficient thermal inertia to allow the cycle to be completed successfully.Defrost cycle activation is based on the detection of a low suction pressure value due to insufficient heat exchangebetween the evaporator and the air due to the formation of a layer of ice, which exerts a thermal insulationeffect. For a defrost cycle to be able to start a suction pressure of at least one of the currently operating compressorsmust remain below the pressure set for the defrost cycle trip signal for a preset time interval.

Before starting to defrost the coils, all the compressors are started, after which the unit reverses its operation fromheat pump to chiller mode.When the cycle is reversed the fans stop and the compressors force hot gas into the coil.A pressure switch on the high pressure circuit maintains the discharge gas pressure below the defrost end value.To maintain the pressure lower than the defrost end pressure the pressure switch activates the fans.To reduce the air flow and obtain more efficient heating of the outer part of the coil, the pressure switch signalcauses the fans to rotate in reverse.When the defrost end temperature is reached, as measured by a thermostat with a probe located in the lowerpart of the coil, the pressure switch allows the discharge pressure to reach the defrost end pressure.When the defrost end pressure has been reached, the controller reverses the unit from chiller mode to heat pumpmode, thereby terminating the defrost procedure.Even though in certain conditions the surface temperature of the coil and the condensation pressure fail to reachthe defrost values within the preset time limit, the defrost cycle is forcibly terminated as though the defrost endsignal were present. The controller restarts the fans, and when the pressure lowers again to the preset value, itreverses the unit’s operating mode again.If the defrost cycle is forcibly interrupted, with the timeout signal, a message is displayed on the controller,although no controller functions are activated.The defrost timeout alarm is automatically cleared from the active alarms menus when a defrost cycle terminatesnormally because the defrost end pressure has been reached. In any event, the alarms historical file will containa record of all defrost cycles that were terminated forcibly due to a timeout intervention.Consecutive defrost cycles must be at least 30 minutes apart. If the forced defrost signal persists, inform theService organisation.

5.2.16 Total heat recovery (option)

Heat recovery is the function where all the energy that would normally be rejected to the air cooled condenser isrecovered at a refrigerant to water condenser installed in series with the air-cooled condenser.The heat recovery process is managed by the microprocessor controller.During energy recovery the fans are stopped and the condensing coil is by-passed via solenoid valves connecteddownstream of the thermostat valve. The machine is equipped with a liquid receiver.Heat recovery can only occur when the water temperature at the recovery exchanger inlet is lower than therecovery set-point. Heat recovery is terminated when the temperature increases by the recovery differentialvalue.It is mandatory to use a condensing pressure control valve (one for each hydraulic circuit) or three-way valve,fitted by the installer, to avoid condensation values that are incompatible with operation of the machine.

5.2.17 Dual set-point (option)

Operation with a dual set-point is possible only in chiller mode.With double thermostatic valves and solenoid valves that are automatically switched according to the requiredexpansion temperature. Two set-point values can be programmed on the microprocessor controller via the keypador a digital input. Switching of the thermostatic valves is always automatic, in accordance with the water tempe-rature.The valves are sized on the basis of the temperature values specified at the time of the order. The machineoperating limits shown in the catalogue are not affected. If the hydraulic circuit contains glycol in sufficient

Blue Box 46

quantities to eliminate the risk of freezing, the lower limit is extended to a minimum of -5 °C leaving watertemperature.

5.2.18 Operation leaving water temperature control (option)

With leaving chilled water temperature control the reference sensor must be installed on the evaporator outlet or,if there is more than one evaporator, on the common outlet pipeline downstream from the relative manifold.The unit’s capacity steps are activated / deactivated with delay intervals in relation to a dead zone. When theleaving water temperature is higher than the programmed set-point compressors start is enabled.

5.3 STARTING THE UNIT

For the start-up procedure refer also to the microprocessor controller manual.

- Close the external enabling contacts- Press the "ON" button on the microprocessor controller- If all the controls are enabled the display will show the message "UNIT ON"

After having performed the above procedures the unit will start automatically after a delay of approximately 5minutes, assuming that the enabling signals of the microprocessor, the flow switches, and the water pumpscontinue to be present.

If the unit fails to start: do not change internal electrical connections onpenalty of immediate invalidation of the warranty.

Important: on heat pump versions the operating cycle must be reversedat the start and end of the season. Frequent switching from summer towinter mode, and vice versa, should be avoided at all costs because itcan lead to malfunctions and subsequent breakdown of the compressors.

During idle periods do not disconnect the unit from the power supply (thecompressor crankcase heaters must remain switched on in these intervals).Disconnect the unit from the power supply only in the event of prolongeddisuse (e.g. seasonal shutdowns). For temporary shutdown of the unitrefer to the guide lines given in paragraph 5.6.

Blue Box 47

Figure 14

Figure 13

5.4 STOPPING THE UNIT

5.4.1 Temporary stop:- To stop the unit press the "OFF" button on the front panel.

5.4.2 Seasonal stop:- Disconnect the power supply- Drain the system circuit (unless it contains a water/glycol solution)- When the unit is to be restarted repeat the initial start-up procedure

Warning: do not use the machine main power switch to stop the unit:this switch must be used to disconnect the electrical supply when nocurrent is flowing on the circuit, i.e. only when the unit is in OFF status.Note also that if power is disconnected from the unit, the crankcaseheaters will be switched off with the resulting risk of compressor damageat the time of restarting.

5.5 EMERGENCY STOP

Emergency stops are obtained by turning the red colour main disconnect switch on the electrical panel to position 0. (figure 14).

Blue Box 48

6 CHECKS DURING OPERATION

6.1 INTRODUCTION

- Check that the water temperature at the evaporator inlet is close to the set-point value of the service thermostat.

- For units equipped with pump units, if the pump runs noisily, close the relative delivery cock until the pump startsrunning smoothly again. This situation can occur when system pressure drops deviate significantly from thepump available pressure.

6.1.1 Checking the refrigerant charge

- After a few hours of unit operation check that the sight glass moisture indicator has a green coloured core. if thecore is yellow, moisture is present in the circuit. In such a situation the circuit must be dehydrated by a qualifiedtechnician.

- Check the sight glass for air bubbles. A constant passage of bubbles through the sight glass could indicate thatthe refrigerant must be replenished. Occasional bubbles are considered normal.

- A few minutes after the start of the compressors, check that the condensing temperature, equivalent to thepressure read on the pressure gauge, is approximately 18 °C higher than condenser inlet air temperature. Alsocheck that the evaporating temperature, equivalent to the pressure read on the pressure gauge, is 5 °C lowerthan the evaporator outlet temperature.

- Check that refrigerant liquid superheating is between 5 and 7 °C; to do this:

1) measure the temperature using a contact thermometer placed on the compressor suction pipeline;2) read the temperature, equivalent to the pressure read on the pressure gauge connected to the compressor

suction side (saturation temperature corresponding to suction pressure); for units charged with R407Crefrigerant, refer to the D.P. (Dew Point) pressure gauge scale.

The difference between the temperatures measured in this manner is equivalent to the superheating value.

- Check that refrigerant subcooling is between 5 and 7 °C; to do this:

1) measure the temperature using a contact thermometer placed on the compressor discharge pipeline;2) read the temperature, equivalent to the pressure read on the pressure gauge connected to the liquid

connection at the condenser outlet (saturation temperature corresponding to condenser delivery pressure);for units charged with R407C refrigerant, refer to the B.P. (Bubble Point) pressure gauge scale.

The difference between the temperature values measured in this manner is equivalent to the subcoolingvalue.

Blue Box 49

7. CALIBRATION OF CONTROL EQUIPMENT

7.1 INTRODUCTION

All the control equipment is factory calibrated before the machine is shipped. Control equipment and safetydevices should nonetheless be checked after a reasonable period of operation. Calibration values are given inTables 2 and 3.

All service operations on the control equipment must be carried out byQUALIFIED PERSONNEL ONLY; incorrect calibration values can causeserious damage to the unit and personal injury.

TABLE 2 - CALIBRATION OF CONTROL EQUIPMENT

TABLE 3 - CALIBRATION OF SAFETY DEVICES

* Chiller / heat pump

CAPACITY STEPS

CONTROL ELEMENT SET POINT DIFFERENTIALService calibration (summer) °C 9 3Service calibration (winter) °C 43 3

4 - 6

ACTIVATION DIFFERENTIAL RESETSET-POINT

No-frost setting °C 3 6 manualMaximum pressure switch setting bar 26 7 manualMinimum pressure switch setting bar 2.5 / 0.7 * 1 manual (from controller)Evaporator heater setting °C 3 6 automaticDefrost start setting bar 2 -- automaticDefrost end setting bar 18 -- automaticDefrost end thermostat setting °C 5 -- automaticDefrost pressure switch setting bar 16 2 automatic

CONTROL ELEMENT

Blue Box 50

Adopt the maximum caution when working in the vicinity of the finnedcoils because of the sharp edges of the aluminium fins.

The compressor’s oil separator and discharge l ine can reach hightemperatures. Always exert caution when working in the vicinity of thecompressor.

Make sure that the unit has been disconnected from the power supplybefore carrying out any work or accessing internal parts.

All operations described in this chapter MUST BE PERFORMEDEXCLUSIVELY BY QUALIFIED PERSONNEL.

8. MAINTENANCE AND PERIODIC CHECKS

8.1 WARNINGS

8.2 INTRODUCTION

Carry out the following periodic checks to ensure the unit is operating correctly:

CHECK PERIOD Check that safety and control devices work correctly as previously described monthly Check that all the terminals within the electric panel and compressor are tight The sliding terminals of the contactors should be periodically cleaned: if any damage is found, replace the contactors

monthly

Check the sight glass to verify the refrigerant charge. monthly Check that there is no oil leakage from the compressor monthly Check that there is no water leakage in the hydraulic system monthly If the unit is to be stopped for a long period the hydraulic circuit, including all pipes and heat exchangers, should be drained. This is compulsory if the ambient temperature is expected to fall below the freezing point of the liquid employed.

seasonal operation

Check process water levels monthly Check that the flow switch is operating correctly. monthly Check that the crankcase heater is operating correctly and there is a power supply. monthly Clean metallic filters on water piping monthly Clean the finned coil or the filter coils, if present, by means of compressed air, which should be directed in the opposite direction to the normal direction of air flow. If the coil is completely clogged clean with a jet of water.

monthly

Execute a defrost test (heat pump units only) monthly Check the condition, anchorage, and balancing of fans every 4 months Check the colour of the sight glass core (green = no moisture, yellow = moisture present): if it is yellow change the refrigerant filter

every 4 months

Check that the noise level has not increased. every 4 months

Blue Box 51

If the circuit is to be emptied, use the appropriate equipment to collectthe refrigerant.

8.3 REPAIRING THE REFRIGERANT CIRCUIT

If repairs have been made to the refrigerant circuit, perform the following steps:

- leak test;- vacuum and dehydration of refrigerant circuit;- refrigerant charge.

8.3.1 Leak test

Charge the refrigerant circuit to a pressure of 15 bar with dry nitrogen gas by means of a cylinder fitted with apressure reducer. Check the circuit for leaks with a leak detector. The formation of bubbles or foam indicates thepresence of leaks.If leaks are found during the test, empty the refrigerant circuit and then repair the point of leakage by weldingwith appropriate alloys.

Do not use oxygen instead of nitrogen: explosion hazard.

8.3.2 High vacuum and dehydration of the refrigerant circuit

To generate a high vacuum in the refrigerant circuit use a high vacuum pump able to reach 0.1 mbar of absolutepressure with a flow rate of 10 m3/h. With this type of pump, a single vacuum cycle is normally sufficient to reachan absolute pressure of 0.1 mbar.If this type of pump is not available, or in the event that the circuit has been left open for a long period of time,you are strongly advised to use the triple evacuation method. This procedure is also prescribed in the event ofmoisture in the refrigerant circuit.

Connect the vacuum pump to the charge connector.Proceed as follows:

- Evacuate the circuit to a pressure of at least 35 mbar absolute. Charge the circuit with nitrogen to a relativepressure of approx. 1 bar.

- Repeat the operation described above.

- Repeat the operation described above for the third time in order to reach the highest degree of vacuum possible.

This procedure should guarantee the elimination of up to 99% of contaminants.

Blue Box 52

8.3.3 Refrigerant charge

- Connect the refrigerant gas cylinder to the male 1/4 SAE charge connector on the liquid line and allow a smallamount of gas to escape in order to purge the connection hose of air.

- The circuit must be charged exclusively with liquid; therefore, if the cylinder is not equipped with a dip pipe itmust be turned upside-down.

Units operating with R407C must be charged exclusively with l iquidrefrigerant by way of the charge connection on the liquid line.

A unit that was originally factory charged with R407C cannot be chargedwith R22 (and vice versa)!

8.4 ENVIRONMENTAL CONSIDERATIONS

Laws governing the use of substances detrimental to the ozone layer prohibit the dispersal of refrigerant gases inthe environment, obliging users to recover refrigerants at the end of their useful life and consign them to thedealer or to specific collection centres.Refrigerant R407C is mentioned among substances subject to special monitoring regimes established by law, andas such they are subject to the prescriptions indicated above.

Use special care during maintenance work in order to limit the risk ofrefrigerant leakage as far as possible.

Blue Box 53

9. TROUBLESHOOTING

The following pages contain a list of the most common causes that can result in the shutdown or anomalousoperation of the chiller. Faults are arranged in accordance with easily identifiable symptoms.

In relation to possible corrective action, adopt the maximum attention inthe operations you intend to perform as overconfidence coupled withinsufficient attention due to lack of expertise can lead to serious accidents.We therefore recommend that Blue Box or other skilled HVAC engineersare contacted to identify and correct the problem.

Blue Box 54

SYMPTOM

OPERATION

PROBABLE CAUSE

POSSIBLE CORRECTIVE ACTION

COOLING

HEATING

A) No compressor running. Fans

⊗ ⊗ No mains power Check presence of mains power

stopped (display Off) ⊗ ⊗ Main power switch Off

(position "O") Turn main power selector to position "I"

⊗ ⊗ No power to control circuits Check fuses FU50, FU51, FU52.

Check operation of transformer ⊗ ⊗ Incorrect phase sequence

(relay KA5 with only green LED lit)

Invert two of the phase wires of the power supply line; when the unit is powered up again both the green and yellow LEDs should light

⊗ ⊗ Relay KA5 with green and

yellow LEDs off Check fuses FU56; If fuses are OK replace phase sequence relay

B) No compressor running. Display On: ”OFF from external consent”

⊗ ⊗ No external consent Check presence of external consent; if not present, bridge terminals 1 and 2

C) No compressor running. Display On: ”OFF from supervision system”

⊗ ⊗ No consent from supervision system

Activate operation from supervision system

D) No compressor running. Display On: ”OFF”

⊗ ⊗ No consent from “on/off” key of user interface

Press “on/off” key

Blue Box 55

SYMPTOM

OPERATION

PROBABLE CAUSE

POSSIBLE CORRECTIVE ACTION

COOLING

HEATING

E) No compressor running. Display On:

⊗ ⊗ 220V fuses burnt-out (FU51)

Change fuses. If fuses burn-out again, contact assistance

unit ON with alarm “High Pressure Compressor 1, 2, 3” ⊗ Fans contactor not

energised Check voltage across the contactor coil and coil continuity

⊗ Fan fuses burnt-out (FU21) Check cause of burn-out and

change fuses. ⊗ Fan motor faulty Check and replace if necessary F) No compressor running. Display On: unit ON with alarm “Fans protection”

⊗ ⊗ Fan thermal protection intervention

Check insulation between windings and from windings to earth (ground)

⊗ ⊗ Fan motor faulty Check and replace if necessary ⊗ ⊗ Faulty fan alarm relay Check and replace relay G) No compressor running. Display On: unit ON with alarm

⊗ ⊗ Drop in power feeding voltage

Check voltage stability and fit appropriate protection if necessary

“Thermal protections Compressor 1, 2, 3” ⊗ ⊗ Setting of thermal

protections Contact assistance

⊗ ⊗ Circuits partially discharged Call service to replenish charge

Blue Box 56

SYMPTOM

OPERATION

PROBABLE CAUSE

POSSIBLE CORRECTIVE ACTION

COOLING

HEATING

H) No compressor running. Display On:

⊗ Insufficient percentage of glycol in hydraulic circuit

Restore correct glycol percentage

unit ON with alarm “Low Pressure compressor 1, 2, 3” ⊗ ⊗ Both circuits have

insufficient refrigerant charge

Find possible leaks in circuit, repair, and recharge

⊗ Fans contactor not

energised Check voltage across the contactor coil and coil continuity

⊗ Fan motor faulty Check and replace if necessary ⊗ Insufficient water flow to

evaporator Check hydraulic circuit

⊗ Incorrect setting of defrost

set-point Check and correct setting if necessary

I) No compressor running. Display On: unit ON with alarm

⊗ Insufficient water flow to evaporator

Increase water flow to evaporator and check temperature rise

“Exceeded Threshold Low Temperature of leaving User Water” ⊗ ⊗ Faulty controller Contact service organisation ⊗ Defrost sensor short circuit Contact service organisation J) No compressor running. Display On: unit ON with alarm “Exceeded Threshold Low Temperature User Water Reference”

⊗ Excessive thermal load Reduce thermal load

Blue Box 57

SYMPTOM

OPERATION

PROBABLE CAUSE

POSSIBLE CORRECTIVE ACTION

COOLING

HEATING

K) No compressor running. Display On: unit ON with alarm “Exceeded Threshold High Temperature of

⊗ Excessive thermal load Wait until entering water temperature is below the alarm set point. Start hydraulic circuit of evaporator and unit. If not sufficient contact assistance.

entering User Water ⊗ Refrigerant circuits partially

discharged Call assistance

L) No compressor running. Display On: unit ON with alarm

⊗ ⊗ Power supply voltage not stable

Check power supply voltage; if not correct contact the electricity company

“No power to Control circuits” ⊗ ⊗ Fuses FU51 burnt-out Check cause of fuse burn-out

and replace fuses. M) No compressor running.

⊗ ⊗ No water flow to evaporator

Check hydraulic circuit

Display On: unit OFF with alarm “Flow Switch Alarm” ⊗ ⊗ Flow switch faulty Check flow switch contact and

replace if necessary N) No compressor running. Display On: unit OFF with alarm ”Incorrect Phase Sequence” and phase sequence relay with green LED On and orange LED Off

⊗ ⊗ Incorrect phase sequence Invert two of the phase wires of the power supply line

Blue Box 58

SYMPTOM

OPERATION

PROBABLE CAUSE

POSSIBLE CORRECTIVE ACTION

COOLING

HEATING

O) No compressor running. Display On: unit OFF with alarm ”Incorrect Phase Sequence” and phase sequence relay with green and orange LEDs On

⊗ ⊗ Faulty relay Check to ensure that relay closes contact

P) No compressor running. Display On: unit OFF with alarm

⊗ ⊗ Fuses FU56 burnt-out Check fuse FU56 and replace if necessary

”Incorrect Phase Sequence” and phase sequence relay with green and orange LEDs Off

⊗ ⊗ One of the three phases is not present

Check connection of each phase

Q) No compressor running. Display On: unit ON without alarm

⊗ ⊗ No consent from digital input to compressors

Check consent to compressors and close relative contacts

⊗ ⊗ Unit at temperature Normal operation ⊗ ⊗ Compressor fuses burnt-

out Check continuity of fuses; if burnt-out call service

⊗ ⊗ Controller faulty Call service ⊗ ⊗ Anti-recycle timer running Wait 5 minutes until the timer

generates a consent

Blue Box 59

SYMPTOM

OPERATION

PROBABLE CAUSE

POSSIBLE CORRECTIVE ACTION

COOLING

HEATING

R) One or more compressors switched off. Display On with

⊗ ⊗ Excess refrigerant charge Check refrigerant charge and call service organisation

alarm “High Pressure Compressor” ⊗ ⊗ Refrigerant circuit contains

non-condensable gas Empty circuit, apply vacuum, and recharge

⊗ ⊗ High pressure switch

incorrectly set or faulty Check pressure switch setting

⊗ Condenser coil or coil filters

(if present) clogged Clean coil and filters (if present) with compressed air

S) One or more compressors switched

⊗ ⊗ Insufficient refrigerant charge due to leak in circuit

Call service organisation

off. Display On with alarm “Low Pressure Compressors” ⊗ ⊗ Thermostatic valve faulty Call service organisation ⊗ ⊗ Solenoid valve of liquid

refrigerant line faulty (if present)

Call service organisation

⊗ Dehydrating filter clogged Call service organisation ⊗ Evaporator coil or coil filters

(if present) clogged Clean coil and filters (if supplied) with compressed air

⊗ ⊗ Liquid refrigerant valve not

completely open Check and open fully

⊗ ⊗ Pressostat faulty Check; replace if necessary T) One or more compressors switched off. Display On with alarm “Compressor Thermal Protections”

⊗ ⊗ Problems at the compressor Call service organisation

Blue Box 60

SYMPTOM

OPERATION

PROBABLE CAUSE

POSSIBLE CORRECTIVE ACTION

COOLING

HEATING

U) One or more ⊗ ⊗ Unit capacity step active Normal operation compressors Off. Display On without alarms ⊗ ⊗ Fuses burnt-out Call service organisation ⊗ ⊗ Faulty controller Call service organisation ⊗ ⊗ No external consent to

compressor Check compressor external consent

V) All compressors running. Display On with alarm “Compressor Maintenance”

⊗ ⊗ Compressors specified by alarm require maintenance

Call service for scheduled maintenance

W) All compressors running. Display On with alarm “Unit Maintenance”

⊗ ⊗ Unit maintenance required Call service for scheduled maintenance

X) All compressors ⊗ ⊗ Excessive thermal load Call service organisation running without stopping. Display On without alarm ⊗ ⊗ Refrigerant circuits partially

discharged Call service organisation

⊗ Liquid refrigerant filter

clogged Clean or replace

⊗ ⊗ Controller not working Call service organisation ⊗ 4-way reversing valve not

energised Check power supply and solenoid valve coils and replace if necessary

Blue Box 61

If the display presents alarms other than those described above, contactthe service organisation.

SYMPTOM

OPERATION

PROBABLE CAUSE

POSSIBLE CORRECTIVE ACTION

COOLING

HEATING

Y) One or more compressors start and

⊗ ⊗ Compressor contactor faulty

Check; replace if necessary

stop. Display On without alarm ⊗ ⊗ Wrong set point values Modify in accordance with values

of paragraph “Calibration of control equipment”

⊗ ⊗ Compressor faulty Check; replace if necessary Z) Anomalous noise from system

⊗ ⊗ Compressor noisy Contact service organisation for check and replacement if necessary

⊗ ⊗ Thermostatic valve noisy Contact service to check and add

refrigerant ⊗ ⊗ Vibrating pipes Contact service organisation to

secure pipes ⊗ ⊗ Casing panels vibrate Check that panels are properly

fastened; contact service organisation if necessary

⊗ ⊗ Worn fan bearings Check; replace fan if necessary

Blue Box 62

10. DECOMMISSIONING THE UNIT

When the unit has reached the end of its useful life and must therefore be removed and replaced, adhere to thefollowing rules:

- the refrigerant must be recovered by a qualified technician and sent to an authorised collection centre;- also the compressor lubrication oil must be recovered and sent to a collection centre;- the structure and components, if unusable, must be stripped down and separated according to the material

type; this is particularly important for copper and aluminium, which are fairly abundant on the machine.

This procedure is designed to assist the work of collection, disposal, and recovery specialists and to reduce theassociated environmental impact.

Blue Box 63

KAPPA V SR

≠≠

REFRIGERANT CIRCUIT

Blue Box 64

KAPPA V SR /HP

≠≠

REFRIGERANT CIRCUIT

Blue Box 65

KAPPA V SR /DC

≠≠

REFRIGERANT CIRCUIT

Blue Box 66

KAPPA V SR - KAPPA V SR/HPModels 65.2 - 73.2

OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS

Blue Box 67

KAPPA V SR - KAPPA V SR/HP - FOOTPRINTModels 65.2 - 73.2

OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS

Blue Box 68

KAPPA V SR - KAPPA V SR/HPModels 80.2 - 88.2

OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS

Blue Box 69

KAPPA V SR - KAPPA V SR/HP - FOOTPRINTModels 80.2 - 88.2

OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS

Blue Box 70

KAPPA V SR - KAPPA V SR/HPModels 93.2 - 100.2

OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS

Blue Box 71

KAPPA V SR - KAPPA V SR/HP - FOOTPRINTModels 93.2 - 100.2

OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS

Blue Box 72

KAPPA V SR - KAPPA V SR/HPModel - 106.3

OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS

Blue Box 73

KAPPA V SR - KAPPA V SR/HP - FOOTPRINTModel - 106.3

OVERALL DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS

Blue Box 74

BLUE BOX GROUP

www.blueboxgroup.it

[email protected]

BLUE BOX srl

Via E. Mattei, 2035028 Piove di Sacco PD ItalyTel. +39.049.9716300Fax +39.049.9704105

Manual 101070B02 - Issue 02.03 / Replaces 05.02All data in this manual is subject to change without prior notice

BLUE BOX srl

is an associate company of

BLUE BOX GROUP

Is a

mem

ber

of

Piov

e C

lima

Synd

acat

e


Recommended