+ All Categories
Home > Documents > KD Relay Application: Compensator distance relay that provides a single zone of phase protection for...

KD Relay Application: Compensator distance relay that provides a single zone of phase protection for...

Date post: 30-Dec-2015
Category:
Upload: madlyn-gaines
View: 214 times
Download: 0 times
Share this document with a friend
Popular Tags:
14
KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to phase, two phase to ground and three phase faults within the reach setting and sensitivity level of the relay
Transcript
Page 1: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay

Application:• Compensator distance relay

that provides a single zone of phase protection for all three phases.

• It provides tripping for phase to phase, two phase to ground and three phase faults within the reach setting and sensitivity level of the relay

Page 2: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay Construction

Cylinder Unit:• Main function is to

operate when the angle between two signal applied is within certain range.

• Widely used as a directional unit and in impedance relays.

Page 3: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay ConstructionCylinder Unit:

• T=KI1I2SIN(Ø12-Ø)-KS

• Where K and Ø are design constants.

• Different combinations of input quantities can be used for different applications, system voltages or currents or network voltages.

Page 4: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay ConstructionCompensator:• Designated as T• Current to Voltage air

gap transformer.• Voltage side has a tap

which divides the winding in two sections.

• The output voltage angle can be changed by connecting a resistor across one of the voltage winding sections

Page 5: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay Construction

Compensator:

Page 6: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay

Page 7: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay

Operation:

Page 8: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay

Page 9: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay

C3C Capacitor

Page 10: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay

Impedance Circle

Page 11: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay

Impedance Curve

Page 12: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD Relay

Page 13: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

KD RELAY Equations needed for testing

M

STZSetting

1

•Impedance measured by 3 phase unit

L

LL

I

VZr

3Setting

LLL

Z

VI

3

Relay Setting

Used to find required test current

•Impedance measured by 2 phase unit

L

LL

I

VZr

2 Setting

LLL Z

VI

2 Used to find required test current

Page 14: KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.

Tests Required

• Main tests required are the compensator check, maximum torque angle and the impedance test for 3 phase unit and phase to phase units.


Recommended