Kidde AEGIS Kidde’s New Conventional Control Panel is Everything But Conventional! Kidde AEGIS™ Kidde Fire Systems—We Are the Right Protection... Every Time, Everywhere, Every Application. www.kiddefiresystems.com The Kidde AEGIS TM is a fully featured single hazard conventional control panel that is ideal for small- to mid-sized special hazard suppression environments. The AEGIS can be used to control Kidde’s full line of suppression systems—FM-200 ® , Carbon Dioxide, 3M TM Novec TM 1230 Fire Protection Fluid, Argonite TM , FE-13 TM , Halon 1301, WHDR TM Wet Chemical and IND TM Dry Chemical, as well as sprinkler supervisory, deluge/pre-action, foam and foam/water systems. This new sleek panel easily fits between studs of a 16-inch standard wall, yet it is large enough to house two 12 VDC, 12 AH batteries with two-inches of wiring and finger space between the circuit board and cabinet wall access. The AEGIS also works well with in-cabinet applications and can be used in conjunction with the Kidde In-Cabinet Suppression System. The AEGIS was engineered to be easy to install, fully robust, yet economical as well. Manual Releases and Abort Switches can be mounted directly onto the panel, avoiding the additional expense of wall mounting these items. A range of circuits has been incorporated to allow programming flexibility to handle all types of special hazard extinguishing systems. These features, as well as the many others packed into this control panel, make the AEGIS the most advanced conventional control panel available to the suppression industry today. All backed with a full five-year warranty from Kidde-the most recognized name in fire protection. Kidde AEGIS™ Agency Approvals: • cFMus to NFPA 72, ANSI/UL 864, 9 th edition and ULC-S527-99 • CSFM Approved • MEA Approved • cULus to ANSI/UL 864, 9 th edition and ULC-S527-99
Transcript
Page 1: Kidde FM-200

Kidde AEGIS™

Kidde’s New Conventional Control Panelis Everything But Conventional!

Kidde AEGIS™

Kidde Fire Systems—We Are the Right Protection...Every Time, Everywhere, Every Application. www.kiddefiresystems.com

The Kidde AEGISTM is a fully featured single hazard conventional control panel that is ideal for small- to mid-sized special hazard suppression environments. The AEGIS can be used to control Kidde’s full line of suppression systems—FM-200®, Carbon Dioxide, 3MTM NovecTM 1230 Fire Protection Fluid, ArgoniteTM, FE-13TM, Halon 1301, WHDRTM Wet Chemical and INDTM Dry Chemical, as well as sprinkler supervisory, deluge/pre-action, foam and foam/water systems.

This new sleek panel easily fits between studs of a 16-inch standard wall, yet it is large enough to house two 12 VDC, 12 AH batteries with two-inches of wiring and finger space between the circuit board and cabinet wall access. The AEGIS also works well with in-cabinet applications and can be used in conjunction with the Kidde In-Cabinet Suppression System.

The AEGIS was engineered to be easy to install, fully robust, yet economical as well. Manual Releases and Abort Switches can be mounted directly onto the panel, avoiding the additional expense of wall mounting these items. A range of circuits has been incorporated to allow programming flexibility to handle all types of special hazard extinguishing systems. These features, as well as the many others packed into this control panel, make the AEGIS the most advanced conventional control panel available to the suppression industry today. All backed with a full five-year warranty from Kidde-the most recognized name in fire protection.

Kidde AEGIS™ Agency Approvals:

• cFMus to NFPA 72, ANSI/UL 864, 9th edition and ULC-S527-99 • CSFM Approved • MEA Approved • cULus to ANSI/UL 864, 9th edition and ULC-S527-99

Page 2: Kidde FM-200

Kidde is registered trademark of Kidde-Fenwal, Inc.AEGIS is a trademark of Kidde-Fenwal, Inc.SS K-012 November 2007 ©Kidde-Fenwal, Inc.All Rights Reserved.

Kidde AEGIS Features:Programming FlexibilityThe range of circuits on the AEGIS allow to program special cases: – Combination Clean Agent plus Double-Interlocked Deluge/Pre-Action Systems – Third Detection Circuit is programmable for either Water flow Input or as a suppression independent detection circuit

A Robust Power Supply Unit (PSU)A 5.4 Amp PSU! The battery charger is able to charge upto a 68 AH battery thereby allowing for 90-hours of standby supervision plus 10-minutes of alarm—as required by some authorities. This ensures continuous fire protection in the event of downtime due to a power failure.

Power Limited CircuitsAll circuits, excluding the Agent Release Circuits, are power-limited thereby allowing the installer to run all wiring through the same conduit, cutting down the cost of extra materials. Optionally, the Agent Release circuits can also be converted to power-limited when not using AH Intitators.

Independently Programmable Agent Releasing CircuitsThe two Agent Release Circuits can be programmed with independent time delays and abort modes to fire combinations of two of the following releasing devices: – 1 or 2 Control Heads (Up to 4 Control Heads with both Agent Release Circuits) – 1 FM Sprinkler Solenoid (2 FM Sprinkler Solenoids with both Agent Release Circuits) – 1 Metron Head

Triple-RTM ProtectionThis triple redundancy process safeguards the system by ensuring no inadvertent activation of the suppression can occur in case of microprocessor failure.

Class A CircuitryAs required by many applications, the AEGIS has built-in Class A supervision fo all circuits. Furthermore, Class A wiring can be achieved without any additional hardware.

Sophisticated Notification Appliance Circuits (NACs)All three NACs use a protocol that enables silenceable horns and non-silenceable strobes to be used on the same NAC, which can significantly reduce costs.

Release Countdown TimerAn easy-to-read release countdown timer lets you know exactly when the system is going to discharge.

Battery Voltage and Charging DisplayRead the open circuit battery voltage and the battery charging current on a working panel without disconnecting the batteries or using external multi-meters!

Password ProtectionSet a password when you install the panel it ensure the system isn’t tampered with before you stop back to service the panel. If a password is forgotten, simply call the factory for a temporary daily password.

A Five Year Warranty Kidde stands behind the AEGIS, which is why we’re extending a five-year warranty for this product.

Page 3: Kidde FM-200

Effective: November 2007K-84-100

A UTC Fire & Security Company

AEGIS™Conventional Fire Alarm-Suppression Control Unit

FEATURES• Agency Approvals

• cFMus Approved to NFPA 72, ANSI 864, 9th edition and ULC-S527-99

• CSFM Approved• MEA Approved• cULus Listed to ANSI 864, 9th edition and

ULC-S527-99• Suppression focused Control Unit• Listed for a Wide Range of Suppression Systems

• Kidde FM-200®, FE13TM, CO2, 3MTM Novec 1230TM Fire Protection Fluid, ArgoniteTM, and Halon Clean Agents

• Kidde INDTM Dry Chemical & WHDRTM Wet Chemical Systems

• Sprinkler Supervisory Service• Deluge, Preaction, Foam, Foam-Water Systems

• Combination Clean Agent plus Pre-Action System• Built-in Class-A and Class-B Circuitry• Sophisticated Programmable Notification Appliance

Circuits• Independently Programmable Agent Releasing Circuits

with Triple-R Protection

• Input and Output • 3 Detection Circuits• 2 Supervisory Circuits• 1 Manual Release Circuit• 1 Abort Input Circuit• 3 Notification Appliance Circuits• 2 Release Circuits• 4 Form-C Relays

• Programmable Relays• Robust Power Supply• Elegant User-Interface• Simple Configuration• Password Protected• Digital Release Countdown• Battery Voltage and Charging Current Display• Extensive Diagnostics• Backwards Compatible• Improved and Enlarged Cabinet Design• 5-Year Warranty

DESCRIPTIONThe Kidde AEGIS is the technologically most advancedConventional Single Hazard Agent Releasing Unitavailable to the Fire-Alarm Suppression industry today. Itcombines the high quality, system reliability, and flexibilityrequired by modern commercial, high-tech and industrialapplications in an aesthetically pleasing and physicallyrobust package.The AEGIS is well equipped to handle all special hazardextinguishing systems due to the high degree ofprogramming flexibility provided and the following fullcomplement of input and output circuits:• Three (3) Class A or Class B Detection Circuits• Two (2) Class A or Class B Supervisory Circuits• One (1) Class A or Class B Manual Release Circuit• One (1) Class A or Class B Abort Input Circuit• Three (3) Class A or Class B Notification Appliance

Circuits• Two (2) Class B Agent Release Circuits• Four (4) Form-C Relays

Page 4: Kidde FM-200

DETECTION CIRCUITSThe Detection Circuits can support up to 25 ConventionalCPD-705x Ionization Smoke, PSD-715x PhotoelectricSmoke, or THD-705x Heat Detectors each as well asNormally Open contact closure type devices. Two circuitsare dedicated to the main suppression function and canbe programmed to activate the release circuits by eithersingle-shot or cross-zone input. The user-configurationallows automatic release via detection to be delayed from0 to 60 seconds in 10-second intervals and also allows achoice of which of the two Agent Release Circuits toactivate.The third Detection Circuit is programmable for eitherWaterflow or as an independent Detection circuit. Whenprogrammed for Waterflow, Notification ApplianceCircuits can be programmed as Non-Silenceable asrequired by certain jurisdictions.SUPERVISORY CIRCUITSThe Supervisory Circuits accept Normally Open contactclosure type devices such as pressure switches on theagent cylinders or on the water or air pipe network. Thesystem configuration enables the supervisory input to bea participant in the suppression function. For example,low air supervisory can be included with detection forrelease of pre-action systems as required by certainjurisdictions.

MANUAL RELEASE AND ABORT CIRCUITSBoth the Manual Release and Abort Circuits acceptNormally Open contact closure type devices. Activationof the Agent Release Circuits can either beinstantaneous or delayed up to 30 seconds (maximum)upon receipt of Manual Release input. Agent release canbe temporarily delayed by activating the Abort Circuit.The Abort input can be programmed for 5 modes ofoperation. These include the UL 10-second mode, thefull-delay mode, the IRI mode, the NYC mode, or theabort can be disabled. Aborts can also be programmed tobe applicable for either one or both Agent ReleaseCircuits thereby allowing use with Deluge/Pre-Actionsystems.NOTIFICATION APPLIANCE CIRCUITS (NAC)The three Notification Appliance Circuits are rated 1.5Amps each and accept polarized 24 Vdc NotificationAppliances. Each circuit is driven independently and isuser configurable for First Alarm, Pre-Release, andReleasing as well as for 60 BPM, 120 BPM, Temporal, orContinuous pattern.The MT and NS series appliances provide the option touse silenceable horns and non-silenceable strobes onthe same NAC. Multiple NAC circuits (connected toaudible devices only) programmed with the same mastercode pattern are synchronized, regardless of anydiffering starting times that preceded their concurrentoperation. The NACs configuration includes a user-selectable intelligent synchronization feature whichallows a silenceable horn to be shut off while the strobecontinues to flash in synchronized fashion.

TB1

TB2TB3TB4TB5TB6TB7

TB8

TB9

TB10

TB11

TB12

TB17TB16TB15TB14

TB19

TB18

TB13

DETECTOR 1

DETECTOR 2WATERFLOW/DETECTOR 3

MANUALRELEASEABORT

SUPERVISORY1

SUPERVISORY2

TROUBLE

RELAY 3

RELAY 2

RELAY 1

BATT OUT

AC IN

RELEASE 1ARC 1

RELEASE 2ARC 2

AUX24 VDC

NAC 3

NAC 2

NAC 1AC SUPPLY SELECT SWITCH (S6)

Figure 1. Printed Circuit Board (PCB)

- 2 -

Page 5: Kidde FM-200

BUILT-IN CLASS A AND B CIRCUITRYFor the input and NAC circuits, the choice of Class A orClass B supervision is made at site on the board itself byselecting the terminals used for wiring. Neitherconversion boards nor additional hardware nor jumperselection is required for this purpose.AGENT RELEASE CIRCUITS (ARC)The two circuits can be programmed for activation bydifferent inputs, with independent time delays and abortmodes to fire combinations of two of the followingreleasing devices:• 1 or 2 Kidde Continuous and Momentary Solenoid

Control Heads

• 1 Kidde Initiator

• 1 Factory Mutual Group A, B, D, E, F, G, I, J, or K Solenoid

In other words, operating in tandem, the two circuits canrelease:• 1 or 2 Control Heads on ARC1 and 1 or 2 Control

Heads on ARC2• 1 or 2 Control Heads on ARC1 and 1 Initiator on

ARC2 or vice-versa• 1 or 2 Control Heads on ARC1 and 1 FM Sprinkler

Solenoid on ARC2 or vice-versa• 1 Initiator on ARC1 and 1 Initiator on ARC2 • 1 FM Solenoid on ARC1 and 1 FM Solenoid on

ARC2

This configurability is useful for those jurisdictions wherethe gaseous suppression agent is required to besupplemented with a pre-action system.TRIPLE-R PROTECTION FOR AGENT RELEASING CIRCUITS (ARC)The two ARCs feature a triple failure redundancysafeguard system to protect them from inadvertentactivation by the main microprocessor. The Triple-Rsystem requires that in order to activate an ARC, themain microprocessor issues two release commands ofopposing polarity via separate channels and that thesecommands be combined with a third signal from thepanel watchdog timer to confirm the microprocessoroperation. The Triple-R system ensures that electricaltransients or disturbances such as power surges thatcould interfere with the operation of the mainmicroprocessor will not inadvertently activate theconnected suppression system. The result is a morerobust and reliable suppression-focused panel.PROGRAMMABLE RELAYSOf the 4 relays, three are user-programmable for avariety of alarm related conditions and the fourth is adedicated trouble relay. All relay contacts are rated 3.0Amps at 30 Vdc/120 Vac (resistive).

POWER-LIMITED CIRCUITRYAll circuits, excluding ARCs are inherently power-limited.Agent Release Circuits, except when firing Initiators, canalso be made power-limited by a field located inlinereleasing diode device thereby allowing cost effectiveinstallation with all wiring in the same conduit.ROBUST POWER SUPPLY UNIT (PSU)The AEGIS features a universal 120/240 V, 50/60 Hz ACPower Supply Unit with a robust 5.4 Amps of 24 Vdcpower. Input voltage selection is via a slider switch withno jumper cutting required. The on-board battery chargeris able to charge 24 Vdc (2 x 12) batteries of capacity upto 68 Ah thereby allowing from 24 hours of supervisionplus 5 minutes of alarm to 90 hours of supervision plus10 minutes of alarm required by some jurisdictions.AUXILIARY POWER SUPPLYUp to 1 Amp of auxiliary power at 24 Vdc is available topower external 4-wire devices such as Flame Detectors,AlarmLine modules, Duct Detectors, etc.ELEGANT USER-INTERFACE The user-interface consists of an array of LED Indicators,Control Switches, a Digital Display, and Buzzer. Over andabove the System, Power Supply status, Input circuit Fireand Trouble and Output circuit Trouble LEDs, the AEGISannunciates its suppression state-of-alarm via threeadditional Pre-Release, Releasing and Post ReleaseLEDs. Four switches are provided, one each forAcknowledge, Signal Silence, System Reset and OutputDisable. The 3-digit display provides a countdown ofimpending agent release. On command from the user-interface switches, it also indicates the battery opencircuit voltage and charging current. SIMPLE SITE-SPECIFIC CONFIGURATION Accessed via the digital display and user-interfaceswitches, site-specific configuration is simple, yetdetailed and can typically be performed in a matter ofminutes. To prevent unauthorized use, the configurationmenu is protected by a user-changeable password.Factory technical support can provide assistance withlost or forgotten passwords. Apart from the input voltage selection performed on boththe PSU and main board via a slider switch, no other on-board settings or jumper cuttings are required.EXTENSIVE DIAGNOSTICS Also initiated via the digital display and user-interfaceswitches, the troubleshooting function displays diagnosticcodes that assist in determining causes of trouble. Acomplete list of diagnostic codes and their meaning shipsfactory installed on the inside of the enclosure door foreasy reference.

- 3 -

Page 6: Kidde FM-200

BACKWARDS COMPATIBILITYConsistent with previous generation Kidde controlequipment, the AEGIS is listed to be backwardscompatible with the full range of Kidde-Fenwalconventional detectors, alarm devices and suppressionaccessories. Going forward, this will allow oldergeneration panels to be replaced with relative ease.IMPROVED AND ENLARGED CABINET DESIGNThe cabinet design allows for easy installation by fittingbetween the studs of a standard 16 inch studded wall. Itis large enough to house two 12 Vdc, 12 Ah Batteries andprovides up to 2 inches (51 mm) of wiring and fingerspace between the circuit board and the cabinet wall. An optional door design features a Manual Release andAbort switch for applications with space constraints. Bothswitches incorporate guards that prevent theirinadvertent activation. Other cabinet options include a flush mounting trim-ringand a dead-front plate required for Canadianapplications.TECHNICAL SPECIFICATIONS• Hazards Protected

- One• Power Supply

- 120/240 Vac, 50/60 Hz (90 to 264 Vrms, 47 to 63 Hz) AC Main Input

- 5.4 Amps at 27 Vdc Output- Battery capacity up to 68 Ah @ 24 Vdc- Auxiliary power output rated at 1 Amp at 18.8 - 27.6

Vdc (resettable)• Three (3) Detection Circuits

- Compatible with up to 25 CPD-705x, PSD-715x, and THD-705x detectors and normally open contact-closure type devices

- Configurable as Class A/Style D or Class B/Style B- Supervised for ground faults and open circuits- Power limited- DET 1 and DET 2 used for suppression- DET3/WF configurable for detection or waterflow

• One (1) Manual Release Circuit- Compatible with normally open contact-closure type

devices- Configurable as Class A/Style D or Class B/Style B- Supervised for ground faults and open circuits- Power limited

TECHNICAL SPECIFICATIONS (cont’d)• One (1) Abort Circuit

- Compatible with normally open contact-closure type devices

- Configurable as Class A/Style D or Class B/Style B- Supervised for ground faults and open circuits- Power-limited

• Two (2) Supervisory Circuits

- Compatible with normally open contact-closure type devices

- Configurable as Class A/Style D or Class B/Style B- Supervised for ground faults and open circuits- Power-limited

• Three (3) Notification Appliance Circuits (NACs)

- Compatible with polarized 24 VDC Audio-Visual devices

- Rated at 1.5 Amps each- Configurable as Class A/Style Z or Class B/Style Y- Supervised for ground faults, shorts, and open

circuits- Power-limited- Common NAC/ARC output disconnect switch

• Two (2) Agent Release Circuits

- Each compatible with 1 or 2 control heads, or 1 initiator, or 1 FM sprinkler solenoid

- Circuits electrically capable of simultaneously releasing any combination of two of the above devices

- Factory configured as Class B/Style Y- Supervised for ground faults and open circuits- Non-power-limited. May be power-limited (except

with initiators) and supervised for short circuit using inline releasing resistor-diode device

- Common NAC/ARC output disconnect switch• Four (4) Relays

- 3 independently programmable, normally de-energized Form-C

- 1 dedicated normally energized Form-C Trouble Relay

- Relay contacts rated 3 Amps at 30 Vdc/120 Vac (resistive)

- 4 -

Page 7: Kidde FM-200

TECHNICAL SPECIFICATIONS (cont’d)• Enclosure

- NEMA 1 rated 18 gauge sheet steel with door- Red color- Suitable for wall and surface mounting- Optional Trim Ring- Optional Dead-Front Panel- Optional door with Manual Release and Abort

switches- Dimensions: - with Standard Door: 14-1/4 in. W x 5 in. D x 19 in. H (362 mm x 127 mm x 483 mm) - with Switch Door: 14-1/4 in. W x 6 in. D x 19 in. H (362 mm x 152 mm x 483 mm)

• Environmental Criteria

- Indoor/Dry use only- Operating temperature range: 32°F to 120°F

(0°C to 49°C)- Humidity: 93 ± 2% RH at 90 ± 3°F (32 ± 2°C)

• Packaging/Shipping

- Enclosure, PCB, and PSU packaged in individual cartons

- Accessories shipped include mounting hardware, battery leads, IOM manual on CD-ROM, operating instruction sheet, and EOL resistor kit

- Order inline releasing resistor-diode device (if required) and batteries separately

ORDERING INFORMATION

Description Part Number

Kidde AEGIS Control Panel 84-732001-001

Kidde AEGIS Control Unit with Switches

84-732001-201

In-Line Releasing Diode (10K) Kit 06-220023-001

Trim Ring 76-600000-007

Dead-Front Panel* 06-220175-001

Battery Enclosure 76-100010-001

Kidde AEGIS Conventional Fire Alarm-Suppression Control Unit IOM Manual

06-236716-001

Kidde AEGIS User’s CD 06-236727-001

Installation/Configuration Kit 06-220148-002

Operating Instructions 06-236719-002

Replacement Hardware Installation Kit 06-220149-001

Replacement Enclosure Assembly 06-220172-002

Replacement Enclosure Assembly (with Switches)

06-220174-002

Replacement Switch Kit 06-220176-001

Replacement PCB Assembly 06-220150-001

Replacement Power Supply 06-118394-002

Replacement Bezel Assembly 06-220151-001

Spare Key 06-118013-001

Spare Keylock with Keys 06-129924-001

EOL Backbox (Canadian applications only)

06-129963-002

Battery Harness 06-129925-002

*For Canadian applications, order Control Unit and Dead-Front Panel separately.

- 5 -

Page 8: Kidde FM-200

Kidde is a registered trademark of Kidde-Fenwal, Inc.AEGIS and Gemini are trademarks of Kidde-Fenwal, Inc.FM-200 is a registered trademark of Chemtura.FE-13 is a registered trademark of DuPont.3MTM NovecTM 1230 Fire Protection Fluid is a trademark of 3M.ArgoniteTM is a registered trademark of Ginge Kerr.

For detailed installation, operation, and configuration information, refer to the Kidde AEGIS Conventional Fire Alarm-Suppression Conventional Unit Installation, Operation, and Maintenance Manual P/N 06-236716-001.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or ques-tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.

K-84-100 Rev AC © 2007 Kidde-Fenwal Inc. Printed in USA

A UTC Fire & Security Company400 Main StreetAshland, MA 01721Ph: 508.881.2000Fax: 508.881.8920www.kiddefiresystems.com

Page 9: Kidde FM-200

Advanced Ionization SmokeDetectors

Models CPD-7054 and CPD-7054D

A UTC Fire & Security Company

Effective: September 200870-01

DESCRIPTIONThe Advance Models CPD-7054 & CPD-7054D are dualchamber Ionization Smoke Detectors designed to senseboth visible and invisible products of combustion. TheDetectors have advanced solid-state, low-voltage,surface-mount circuitry and are designed for 2-Wire and4-Wire installation using the appropriate Detector base.The characteristic 360-degree detector design permitssmoke entry from any direction. A unique sensingchamber design permits the operation of the ModelsCPD-7054 and CPD-7054D in open areas with airvelocities from 0 to 300 fpm and 0 to 500 fpm,respectively. The Model CPD-7054D is also suitable forduct housing applications in air velocities from 500 to4000 fpm. The Detectors are designed for open area/duct housing applications per UL268/UL268A and maybe installed in systems intended for Releasing DeviceService through use of compatible Fire Alarm ControlPanels.

Two red Light Emitting Diodes (LEDs) are locateddiametrically opposite each other so as to allow 360-degree viewing. Both LEDs continuously indicate theoperating condition of the Detector. During standby, theLEDs flash once every six seconds. During alarm, bothLEDs light steady at full brilliance. A double flash everysix seconds indicates a detector with a sensitivitythreshold outside acceptable limits. A unique gatedoutput circuit design provides improved stability andtransient suppression. Special signal processingtechniques verify the presence of smoke before thedetector will alarm. A fine mesh insect screen protectsthe chamber area and is used to avoid potential nuisancealarms. The detector head is installed into its mountingbase with a simple twist-lock action. A locking feature isprovided for vandal resistant security.

Table 1 lists the Technical Specifications for Models CPD-7054 and CPD-7054D Ionization Smoke Detectors.

CONTROL UNITSThe Models CPD-7054 and CPD-7054D Detectors aredesigned to operate with control units and releasingdevices having specific voltage and currentcharacteristics that are compatible with the detectorcircuitry. Both models are compatible with the Fenwal732 control unit. The Fenwal 732 has three detectioncircuits which can support up to 25 detectors per circuit.

FEATURES• Approvals/Listing

• US and Canadian UL Listed (cULus)• FM Approved• CSFM Approved • NYC MEA Accepted

• Dual Ionization Chamber Technology• Nominal Sensitivity

• CPD-7054: 1.30% per ft. Obscuration• CPD-7054D: 1.00% per ft. Obscuration

• Sensitivity Measurement/Testing• Wireless Measurement in %/ft. Obscuration• Remote and Local Functional Test Capability

• Wide Range of Input Voltage 10.2 to 36.8 Vdc• Low Current Design• Dual Response LEDs Allow 360-degree Viewing• Trouble Indication• Low Profile Appearance Using Surface Mount Tech-

nology• Electrically and Mechanically Compatible with all

Fenwal Smoke and Electronic Heat Detectors and Bases

• Interchangeable 2-Wire and 4-Wire Bases• Universal Relay Modules• Non Polarized• Locking Feature for Vandal Resistance• Fine Mesh Insect Screen• EMI and RFI Resistant

Page 10: Kidde FM-200

Table 1: Technical Specification

Model Number CPD-7054 CPD-7054D

Part Number 70-540000-001 70-540000-002

Detection Dual Ionization Chamber Dual Ionization Chamber

Approvals cULus, FM, CSFM, MEA-NYC, USNRC, CNSC cULus, FM, CSFM, MEA-NYC, USNRC, CNSC

UL Compatibility I.D. I51FE1 I51FE1

Listed Spacing 30 ft. (9.1 m) centers or 900 ft.2 (83.6 m2) 30 ft. (9.1 m) centers or 900 ft.2 (83.6 m2)

Radioactive Source Material Activity

Americium 241 (sealed) 0.8 µCi (29.6 kBq) Americium 241 (sealed) 0.8 µCi (29.6 kBq

Nominal Sensitivity 1.30% + 0.25% - 0.42% per foot Obscuration

1.00% + 0.10% - 0.12% per foot Obscuration

Standby Voltage (Vdc)Using 2WB:

Using 4WRB:10.2 to 36.816.8 to 36.8

10.2 to 36.816.8 to 36.8

Maximum CurrentStandby:

Alarm:70 µA

100 mA70 µA

100 mA

Response IndicatorsQuantity:

Standby Condition:Thermistor Trouble:

Alarm Condition:

2 external LEDsOne flash every 9 seconds

Double flash every 9 secondsSteady at full brilliance

2 external LEDsOne flash every 9 seconds

Double flash every 9 secondsSteady at full brilliance

Operating EnvironmentOperating Temperature:

Storage Temperature:Relative Humidity:

32° to 120°F (0° to 49°C)-20° to 180°F (-29° to 82°C)0 to 93% Non-condensing

32° to 120°F (0° to 49°C)-20° to 180°F (-29° to 82°C)0 to 93% Non-condensing

Air VelocityOpen Area:

Duct Housing:Altitude:

0 to 300 fpm (0 to 1.5 m/s)N/A

Up to 7,500 feet (2,286 m)

0 to 500 fpm (0 to 2.5 m/s)500 to 4000 fpm (2.5 to 20 m/s)

Up to 7,500 feet (2,286 m)

Physical CharacteristicsMaterial and Finish:

Weight:

High-impact, flame-retardant plastic, off white

35.3 oz. (110g) w/o base

High-impact, flame-retardant plastic, off white

35.3 oz. (110g) w/o base

DimensionsDetector Height:

Detector Diameter:Base Height:

Base Diameter:

1-3/8 in. (35 mm)3-29/32 in. (99 mm)

3/64 in. (11 mm)5-29/32 in. (150 mm)

1-3/8 in. (35 mm)3-29/32 in. (99 mm)

3/64 in. (11 mm)5-29/32 in. (150 mm)

- 2 -

Page 11: Kidde FM-200

DETECTOR BASE OPTIONSThe Models CPD-7054 and CPD-7054D can be usedwith the detector base options and accessories in Table2. Various base options are available to provide auxiliaryrelay and/or remote indication and remote test feature.The Model CPD-7054 and CPD-7054D Ionization SmokeDetectors may be interchanged with other Fenwal SeriesTHD-705X Electronic Heat Detector and Series PSD-715X Photoelectric Smoke Detectors when usingmultifunction base configuration.

SPACING (OPEN AREA LOCATION)The Models CPD-7054 and CPD-7054D Detectors arelisted to be installed on maximum 30 ft. (9.1 m) centers,typically on smooth ceilings up to 15 ft. (4.6 m) high andwill operate with minimum air circulation.

Resultant maximum 900 square foot (83.6 m2) spacingmay be used as a reasonable guide for comparableapplications. Where special conditions exist (ceilingobstructions, high air exchange rates, etc.), reducedspacing must be used to achieve adequate protection.Computer rooms and other such installations may requirespacing with a maximum of 200 ft.2 (18.6 m2) due to highair exchange rates.

Detectors should not be located in areas with excessiveexhaust fumes, kitchen areas, near fireplaces or furnacerooms and within three (3) ft. (0.9 m) of air supply ductsor air diffusers.

For additional information, consult the Fenwal AutomaticFire Detection Application Engineering Manual MC-402,NFPA-72 and the local Authority Having Jurisdiction.

WIRING DIAGRAMSFor detailed wiring diagrams with Fenwal 2- and 4-wirebases, please refer Fenwal Document 06-235056-001.

INSTALLATION Detector bases are directly mounted on the electricaljunction boxes (3-inch, 3-1/2-inch and 4-inch octagonal,3-inch round or 4-inch2) (76 mm, 89 mm, 102 mmoctagonal, 76 mm round or 102 mm2) without the needfor any mechanical adapter required. Refer FenwalDocument 06-235056-001 for additional details.

TESTING AND MAINTENANCETesting shall be performed upon installation of thedetector and once a year thereafter as stated in NFPA-72latest edition. Detector sensitivity shall be checked withinone year of installation and every alternative yearthereafter as stated in NFPA 72. Refer FenwalDocuments 06-236514-001 and 06-235056-001 fordetails on using the Infrared Wireless Sensitivity TesterModel DST-003. The tester provides direct readout inpercent per foot obscuration from a distance of 15 ft.

without removing the detector from its base. A go/no-gotest can be performed using a test magnet.

The recommended requirement for detector maintenanceconsists of an annual cleaning of dust from the detectorhead by using the suction of a vacuum cleaner. Cleaningprograms should be geared to the individual environmentin conformance with NFPA 72.

SPARE PARTSThe Models CPD-7054 and CPD-7054D Detectors arefactory repairable only and have no field serviceablespare parts. No field repair should therefore beattempted. For service, return detector head intact toFenwal.

RADIOACTIVE MATERIAL/DISPOSALThe Americium 241 radioactive material used is shieldedby a stainless steel housing and has a maximum activityof 0.8 microcuries (29.6 kBq).

The United States Nuclear Regulatory Commission(USNRC) allows the user of Americium 241 filled smokedetectors to dispose of them without obtaining a license.Under the Code of Federal Regulations, Part 10(10CFR), Paragraph 30.20, any person receiving, using,owning, etc., by-product material in detectors designed toprotect life or property from fires or airborne hazards isautomatically granted a general license which,conversely, exempts them from a specific license,thereby allowing them to both receive and dispose ofsmoke detectors without returning to the manufacturer.

ARCHITECT/ENGINEER SPECIFICATIONSThe contractor shall furnish and install where indicatedon the plans, UL268/UL268A listed dual-chamber,Ionization Smoke Detectors, Fenwal Models CPD-7054and CPD-7054D. Ionization Smoke Detectors containinga radioactive source of strength greater than 0.8microcuries (29.6 kBq) shall not be acceptable. Thecombination detector head and twist-lock base shall beUL Listed compatible with a UL Listed fire alarm controlunit. The Models CPD-7054 and CPD-7054D IonizationSmoke Detectors shall share interchangeable bases withthe PSD-7157 and PSD-7157D Photoelectric SmokeDetectors and the THD-7052 and THD-7053 HeatDetectors.The Fenwal Models CPD-7054 and CPD-7054D Ionization Smoke Detectors shall have two RedLEDs located diametrically opposite each other so as to

CAUTION

Do not attempt disassembly of the fac-tory sealed smoke detector. This assembly is sealed for your protection and should not be opened for servic-ing. Opening of the detector will void its warranty.

- 3 -

Page 12: Kidde FM-200

allow 360-degree viewing. The LEDs shall continuouslyindicate the operating condition of the Detector. Duringstandby, the LEDs shall flash once every six seconds.During alarm, both LEDs shall light steady at fullbrilliance. If the sensitivity of the detector drifts outsideacceptable limits, the LEDs shall double flash every sixseconds. The detector may be reset by actuating thecontrol panel reset switch. The vandal-resistant securitylocking feature shall be used in those areas as indicatedon the drawings. The locking feature shall be fieldremovable when not required.

It shall be possible to measure the sensitivity of theFenwal Models CPD-7054 and CPD-7054D IonizationSmoke Detectors from a distance of up to 15 ft. (4.6 m)without removal from the base. Measurement shall beaccomplished with a wireless infrared Fenwal SensitivityTester (DST-003) allowing direct measurement in percentper foot obscuration. Sensitivity measurementtechniques requiring wiring between the Detector-Basecombination and the Tester shall not be acceptable. Itshall also be possible to perform a functional test of thedetector without the need for generating smoke.

The Fenwal Models CPD-7054 and CPD-7054DIonization Smoke Detectors shall operate over an inputvoltage range from 10.2 to 36.8 Vdc. Voltage and RFtransient suppression techniques to withstand up to 20volt/meter shall be employed to minimize susceptibility tofalse alarms.

Supplementary SPDT relays, remote test, and/or remoteLED alarm indicators shall be installed where indicated.

- 4 -

Page 13: Kidde FM-200

Table 2: Ordering Information

Part Number Model Description

Detector Heads - Ionization Smoke

70-540000-001 CPD-7054 Ionization Advanced Smoke Detector (cULus)

70-540000-002 CPD-7054D Ionization Advanced Smoke Detector (cULus)

Detector Heads - Photoelectric Smoke

71-570000-001 PSD-7157 Photoelectric Advanced Smoke Detector (cULus)

71-570000-002 PSD-7157D Photoelectric Advanced Smoke Detector (cULus)

Detector Heads - Heat

70-520000-001 THD-7052 135°F (57°C) Fixed Heat Detector, 15°F (-9°C) Rate of Rise (cULus)

70-530000-001 THD-7053 135°F (57°C) Fixed Heat Detector (cULus)

Detector Bases

70-501000-001 2-Wire 2-Wire Standard Base. Connects to circuit via screw terminals. (CID = FE51A)

70-501000-002 2WRLT 2-Wire Base w/ Remote LED & Test capabilities. Connects to circuit via screw terminals. Minimum Alarm Current 15 mA @ 24 Vdc. (CID = FE52A)

70-501000-005 2WRB 2-Wire Base w/ 2WRM, Remote LED & Test capabilities. Connects to cir-cuit via pigtail leads. Minimum Alarm Current 19 mA @ 24 Vdc. (CID = FE55A)

70-501000-101 4WRB 4-Wire Base w/ 4WRM, Remote LED & Test capabilities. Connects to cir-cuit via pigtail leads. Minimum Alarm Current 35mA @ 24 Vdc.

70-500000-004 2WRM Spare SPDT Relay for 2WRB Bases. Contacts rated 1.0 A, 30 Vdc/0.5 A, 125 Vac.

Detector Accessories

06-117883-001 Test Magnet

29-116788-001 EOL Supervisory Relay

70-200000-911 RA-911 Remote Alarm Indicator

70-200000-914 RA-914 Remote Alarm Indicator with Smoke Detector Switch

70-500000-003 DST-003 Advanced Handheld Wireless Smoke Detector Sensitivity Tester

70-501000-003 MA-001 Mechanical Retrofit Adapter. Allows CPD-705X and PSD-715X Detectors to physically connect to Base P/Ns 70-201000-001, -002, -003,-005 & DH-22. (CID = MAFE1)

- 5 -

Page 14: Kidde FM-200

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or ques-tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.

70-01 Rev AD © 2008 Kidde-Fenwal Inc. Printed in USA

A UTC Fire & Security Company400 Main StreetAshland, MA 01721Ph: 508.881.2000Fax: 508.881.8920www.kiddefiresystems.com

Page 15: Kidde FM-200

Advanced Photoelectric Smoke Detectors

Models PSD-7157 and PSD-7157D

A UTC Fire & Security Company

Effective: September 200870-02

DESCRIPTION

Photoelectric Smoke Detectors respond to a broadspectrum of both flaming and smoldering fire conditions.The Detectors have advanced solid-state, low-voltage,surface-mount circuitry and are designed for 2-Wire and4-Wire installation using the appropriate Detector base.The characteristic 360-degree detector design permitssmoke entry from any direction. A unique sensingchamber design permits the operation of the ModelsPSD-7157 and PSD-7157D in open areas with airvelocities from 0 to 300 fpm and 0 to 4000 fpmrespectively. The Model PSD-7157D is also suitable forduct housing applications in air velocities from 500 to4000 fpm. The Detectors are designed for open area/duct housing applications per UL268/UL268A and maybe installed in systems intended for Releasing DeviceService through use of compatible Fire Alarm ControlPanels.

Two Red Light Emitting Diodes are located diametricallyopposite each other so as to allow 360-degree viewing.Both LEDs continuously indicate the operating conditionof the Detector. During standby, the LEDs flash onceevery six seconds. During alarm, both LEDs light steadyat full brilliance. A double flash every six secondsindicates a detector with a sensitivity threshold outsideacceptable limits. A unique gated output circuit designprovides improved stability and transient suppression.Special signal processing techniques verify the presenceof smoke before the detector will alarm. A fine meshinsect screen protects the chamber area and is used toavoid potential nuisance alarms. The detector head isinstalled into the base with a simple twist-lock action. Alocking feature is provided for vandal resistant security.

Table 1 lists the Technical Specifications for Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors.

CONTROL UNITSThe Models PSD-7157 and PSD-7157D Detectors aredesigned for operation with control units and releasingdevices having specific voltage and currentcharacteristics that are compatible with the detectorcircuitry. The Detectors are compatible with the Fenwal732 control unit. The Fenwal 732 has three detectioncircuits which can support up to 26 detectors per circuit.

FEATURES• Approvals/Listing

• US and Canadian UL Listed (cULus)• FM Approved• CSFM Approved • NYC MEA Accepted

• Nominal Sensitivity• PSD-7157: 3.25% per ft. Obscuration• PSD-7157D: 2.40% per ft. Obscuration

• Sensitivity Measurement/Testing• Wireless Measurement in %/ft. Obscuration• Remote and Local Functional Test Capability

• Wide Range of Input Voltage 10.2 to 36.8 Vdc• Low Current Design• Dual Response LEDs Allow 360-degree Viewing• Trouble Indication• Low Profile Appearance Using Surface Mount

Technology• Electrically and Mechanically Compatible with

all Fenwal Smoke and Electronic Heat Detectorsand Bases

• Interchangeable 2-Wire and 4-Wire Bases• Universal Relay Modules• Non Polarized• Locking Feature for Vandal Resistance• Fine Mesh Insect Screen• EMI and RFI Resistant

The Advance Models of PSD-7157 and PSD-7157D

Page 16: Kidde FM-200

DETECTOR BASE OPTIONSThe Models PSD-7157 and PSD-7157D can be usedwith the detector base options and accessories in Tables2. Various base options are available to provide auxiliaryrelay and/or remote indication and remote test feature.

The Models PSD-7157 and PSD-7157D PhotoelectricSmoke Detectors may be interchanged with other FenwalSeries THD-705X Electronic Heat Detectors and SeriesCPD-705X Ionization Smoke Detectors when usingmultifunction base configuration.

Table 1: Technical Specification

Model Number PSD-7157 PSD-7157D

Part Number 71-570000-001 71-570000-002

Detection Photoelectric Photoelectric

Approvals cULus, FM, CSFM, MEA-NYC cULus, FM, CSFM, MEA-NYC

UL Compatibility I.D. P55FE1 P55FE1

Listed Spacing 30 ft. (9.1 m) centers or 900 ft.2 (83.6 m2) 30 ft. (9.1 m) centers or 900 ft.2 (83.6 m2)

Nominal Sensitivity 3.25% + 0.45% - 1.78% per foot Obscuration

2.40% + 0.04% - 1.34% per foot Obscuration

Standby Voltage (Vdc)Using 2WB:

Using 4WRB:10.2 to 36.816.8 to 36.8

10.2 to 36.816.8 to 36.8

Maximum CurrentStandby:

Alarm:70 µA

100 mA70 µA

100 mA

Response IndicatorsQuantity:

Standby Condition:Thermistor Trouble:

Alarm Condition:

2 external LEDsOne flash every 11 seconds

Double flash every 11 secondsSteady at full brilliance

2 external LEDsOne flash every 11 seconds

Double flash every 11 secondsSteady at full brilliance

Operating EnvironmentOperating Temperature:

Storage Temperature:Relative Humidity:

32° to 120°F (0° to 49°C)-20° to 180°F (-29° to 82°C)0 to 93% Non-condensing

32° to 120°F (0° to 49°C)-20° to 180°F (-29° to 82°C)0 to 93% Non-condensing

Air VelocityOpen Area:

Duct Housing:Altitude:

0 to 300 fpm (0 to 1.5 m/s)N/A

Up to 7,500 feet (2,286 m)

0 to 4000 fpm (0 to 20 m/s)500 to 4000 fpm (2.5 to 20 m/s)

Up to 7,500 feet (2,286 m)

Physical CharacteristicsMaterial and Finish:

Weight:

High-impact, flame-retardant plastic, off white

35.3 oz. (110g) w/o base

High-impact, flame-retardant plastic, off white

35.3 oz. (110g) w/o base

DimensionsDetector Height:

Detector Diameter:Base Height:

Base Diameter:

1-3/8 in. (35 mm)3-29/32 in. (99 mm)

3/64 in. (11 mm)5-29/32 in. (150 mm)

1-3/8 in. (35 mm)3-29/32 in. (99 mm)

3/64 in. (11 mm)5-29/32 in. (150 mm)

- 2 -

Page 17: Kidde FM-200

SPACING (OPEN AREA LOCATION)The Models PSD-7157 and PSD-7157D Detectors arelisted to be installed on maximum 30 ft. (9.1 m) centers,typically on smooth ceilings up to 15 ft. (4.6 m) high andwill operate with minimum air circulation.

Resultant maximum 900 square foot (83.6 m2) spacingmay be used as a reasonable guide for comparableapplications. Where special conditions exist (ceilingobstructions, high air exchange rates, etc.), reducedspacing must be used to achieve adequate protection.Computer rooms and other such installations may requirespacing with a maximum of 200 ft.2 (18.6 m2) due to highair exchange rates.

Detectors should not be located in areas with excessiveexhaust fumes, kitchen areas, near fireplaces or furnacerooms and within three (3) ft. (.9 m) of air supply ducts orair diffusers.

For additional information, consult the Fenwal AutomaticFire Detection Application Engineering Manual MC-402,NFPA-72 and the local Authority Having Jurisdiction.

WIRING DIAGRAMSFor detailed wiring diagrams with Fenwal 2- and 4-wirebases, please refer Fenwal Document 70.104

INSTALLATION Detector bases are directly mounted on the electricaljunction boxes (3-inch, 3-1/2-inch and 4-inch octagonal,3-inch round or 4-inch square) (76 mm, 89 mm, 102 mmoctagonal, 76 mm round or 102 mm square) without theneed for any mechanical adapter required. Refer FenwalDocument 06-235056-001 for additional details.

The detector bases also include a locking feature thatprevents removal of the detector without use of a tool.

TESTING AND MAINTENANCETesting shall be performed upon installation of thedetector and once a year thereafter as stated in NFPA-72latest edition.

Detector sensitivity shall be checked within one year ofinstallation and every alternative year thereafter as statedin NFPA 72. Refer Fenwal Documents 06-236524-001and 06-235056-001 for details on using the InfraredWireless Sensitivity Tester Model DST-003. The testerprovides direct readout in percent per foot obscurationfrom a distance of 15 ft. without removing the detectorfrom its base. A go/no-go test can be performed using atest magnet.

The recommended requirement for detector maintenanceconsists of an annual cleaning of dust from the detectorhead by using the suction of a vacuum cleaner. Cleaningprograms should be geared to the individual environmentin conformance with NFPA 72.

SPARE PARTSThe Models PSD-7157 and PSD-7157D Detectors arefactory repairable only and have no field serviceablespare parts. No field repair should therefore beattempted. For service, return detector head intact toFenwal.

ARCHITECT/ENGINEER SPECIFICATIONSThe contractor shall furnish and install where indicatedon the plans, UL268/UL268A listed Photoelectric SmokeDetectors, Fenwal Models PSD-7157 and PSD-7157D.The combination detector head and twist-lock base shallbe UL Listed compatible with a UL Listed fire alarmcontrol unit. The Models PSD-7157 and PSD-7157DPhotoelectric Smoke Detectors shall shareinterchangeable bases with the CPD-7054 and CPD-7054D Ionization Smoke Detectors and the THD-7052and THD-7053 Heat Detectors.

The Fenwal Models PSD-7157 and PSD-7157DPhotoelectric Smoke Detectors shall have two Red LEDslocated diametrically opposite each other so as to allow360-degree viewing. The LEDs shall continuouslyindicate the operating condition of the Detector. Duringstandby, the LEDs shall flash once every six seconds.During alarm, both LEDs shall light steady at fullbrilliance. If the sensitivity of the detector drifts outsideacceptable limits, the LEDs shall double flash every sixseconds. The detector may be reset by actuating thecontrol panel reset switch. The vandal-resistant securitylocking feature shall be used in those areas as indicatedon the drawings. The locking feature shall be fieldremovable when not required.

It shall be possible to measure the sensitivity of theFenwal Models PSD-7157 and PSD-7157D PhotoelectricSmoke Detectors from a distance of up to 15 feet (4.6 m)without removal from the base. Measurement shall beaccomplished with a wireless infrared Fenwal SensitivityTester (DST-003) allowing direct measurement in percentper foot obscuration. Sensitivity measurementtechniques requiring wiring between the Detector-Basecombination and the Tester shall not be acceptable. Itshall also be possible to perform a functional test of thedetector without the need for generating smoke.

CAUTION

Do not attempt disassembly of the fac-tory sealed smoke detector. Thisassembly is sealed for your protectionand should not be opened for servic-ing. Opening of the detector will voidits warranty.

- 3 -

Page 18: Kidde FM-200

ThasproIf ytio

7

is literature is provided for informational purposes only. KIDDE-FENWAL, INC. sumes no responsibility for the product’s suitability for a particular application. The duct must be properly applied to work correctly.ou need more information on this product, or if you have a particular problem or ques-

The Fenwal Models PSD-7157 and PSD-7157DPhotoelectric Smoke Detectors shall operate over aninput voltage range from 10.2 to 36.8 Vdc. Voltage andRF transient suppression techniques to withstand up to20 volt/meter shall be employed to minimize susceptibilityto false alarms.

Supplementary SPDT relays, remote test, and/or remoteLED alarm indicators shall be installed where indicated

.

Table 2: Ordering Information

Part Number Model Description

Detector Heads - Ionization Smoke

70-540000-001 CPD-7054 Ionization Advanced Smoke Detector (cULus)

70-540000-002 CPD-7054D Ionization Advanced Smoke Detector (cULus)

Detector Heads - Photoelectric Smoke

71-570000-001 PSD-7157 Photoelectric Advanced Smoke Detector (cULus)

71-570000-002 PSD-7157D Photoelectric Advanced Smoke Detector (cULus)

Detector Heads - Heat

70-520000-001 THD-7052 135°F (57°C) Fixed Heat Detector, 15°F (-9°C) Rate of Rise (cULus)

70-530000-001 THD-7053 135°F (57°C) Fixed Heat Detector (cULus)

Detector Bases

70-501000-001 2-Wire 2-Wire Standard Base. Connects to circuit via screw terminals. (CID = FE51A)

70-501000-002 2WRLT 2-Wire Base w/ Remote LED & Test capabilities. Connects to circuit via screw terminals. Minimum Alarm Current 15 mA @ 24 Vdc. (CID = FE52A)

70-501000-005 2WRB 2-Wire Base w/ 2WRM, Remote LED & Test capabilities. Connects to cir-cuit via pigtail leads. Minimum Alarm Current 19 mA @ 24 Vdc. (CID = FE55A)

70-501000-101 4WRB 4-Wire Base w/ 4WRM, Remote LED & Test capabilities. Connects to cir-cuit via pigtail leads. Minimum Alarm Current 35mA @ 24 Vdc.

70-500000-004 2WRM Spare SPDT Relay for 2WRB Bases. Contacts rated 1.0 A, 30 Vdc/0.5 A, 125 Vac.

Detector Accessories

06-117883-001 Test Magnet

29-116788-001 EOL Supervisory Relay

70-200000-911 RA-911 Remote Alarm Indicator

70-200000-914 RA-914 Remote Alarm Indicator with Smoke Detector Switch

70-500000-003 DST-003 Advanced Handheld Wireless Smoke Detector Sensitivity Tester

70-501000-003 MA-001 Mechanical Retrofit Adapter. Allows CPD-705X and PSD-715X Detectors to physically connect to Base P/Ns 70-201000-001, -002, -003,-005 & DH-22. (CID = MAFE1)

A UTC Fire & Security Company

n, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.

0-02 Rev AE © 2008 Kidde-Fenwal Inc. Printed in USA

400 Main StreetAshland, MA 01721Ph: 508.881.2000Fax: 508.881.8920www.kiddefiresystems.com