+ All Categories
Home > Documents > Kingspan tp10 insulation

Kingspan tp10 insulation

Date post: 07-Oct-2015
Category:
Upload: krivco
View: 14 times
Download: 0 times
Share this document with a friend
Description:
Kingspan tp10 insulation
17
 H i g h p er f o r m a nce ri g id ur et ha ne i nsul ati o n –ther m al conducti vi t y 0.022– 0.023 W / m .K O n a vera g e its us e cr ea t es 15% m or e us a b le w ar m roof s p ace I nsula t i o n o f p ip es and tanks i s unnecessary N o co nden s a t i on r is k U na f f ect ed b y a ir m o vem ent Re si s t a nt t o t he pass a ge of w a t er vapour Ea s y t o ha nd l e a nd i nst a ll I d ea l f or ne w b ui l d a nd r ef ur b ishm ent C FC / HC FC –free w ith zer o O zone D ep l et i o n Po t en t i al ( OD P) CI /S f b Thi r d Issue M ar ch 2003 ( 27.9) Rn7 M2 R A FT ER L EVEL IN SUL ATIO N FO R T IL ED O R SL AT ED PIT C HED W A R M R O O F SP A C ES pitch TP10 zero ODP BBA BRITISH BOARD OF AGRÉMENT CERTIFICATE 95/3126  ® BSEN ISO 9002 : 199 4 Certificate No. FM 10697 I.S. EN ISO 9001: 2000 Registration No. 19.0633
Transcript
  • High performance rigid urethaneinsulation thermal conductivity0.0220.023 W/m.K

    On average its use creates 15% moreusable warm roof space

    Insulation of pipes and tanks isunnecessary

    No condensation risk

    Unaffected by air movement

    Resistant to the passage of watervapour

    Easy to handle and install

    Ideal for newbuild and refurbishment

    CFC/HCFCfree with zero OzoneDepletion Potential (ODP)

    CI/Sfb

    Third Issue March 2003

    (27.9) Rn7 M2

    R A F T E R L E V E L I N S U L A T I O N F O R T I L E DO R S L A T E D P I T C H E D W A R M R O O F S P A C E S

    pitch TP10 zero ODP

    BBABRITISHBOARD OFAGRMENTCERTIFICATE 95/3126

    BS EN ISO 9002 : 1994Certificate No. FM 10697

    I.S. EN ISO 9001: 2000Registration No. 19.0633

  • 2Kingspan pitch TP10 zero ODP

    TYPICAL DESIGN DETAILS

    FIGURE 1 UNVENTILATEDINSULATION BETWEEN & UNDER RAFTERS(Recommended for new build or reroofing)

    Figure 1a FULLY FILLED INSULATION BETWEEN RAFTERS NO SARKING BOARD

    Figure 1b PARTIALLY FILLED INSULATION BETWEEN RAFTERS NO SARKING BOARD

    Figure 1c FULLY FILLED INSULATION BETWEEN RAFTERS 18 mm SARKING BOARD

    Figure 1d PARTIALLY FILLED INSULATION BETWEEN RAFTERS 18 mm SARKING BOARD

    Figure 2a NO SARKING BOARD Figure 2b 18 mm SARKING BOARD

    FIGURE 2 VENTILATEDINSULATION BETWEEN & UNDER RAFTERS(Recommended for loft conversion)

    Horizontal lap between runs ofbreathable sarking membranesealed (if required) with75 mm wide doublesided acrylicadhesive tape

    Rafter

    Kingspan ThermapitchTP10 zero ODP betweenrafters

    Slates****

    *Breathable sarkingmembrane eg.Kingspan nilvent

    Horizontal lap between runs of breathable sarkingmembrane. NB. The breathable sarkingmembrane could be installed verticallyunder counter battens andpulled taut in which case theair space under thebreathable sarkingmembrane isunventilated

    Rafter

    Kingspan ThermapitchTP10 zero ODPbetween rafters

    Kingspan Thermawall TW56zero ODP under rafters

    Tiles/slates

    Tiles/slate batten

    Breathable sarkingmembrane eg.Kingspan nilvent

    Horizontal lap betweenruns of sarking felt

    Rafter

    Ventilated air space(50 mm min) aboveinsulation to currentBuilding Regulations/Standards

    Sarking felt

    Tiles/slatesTile/slatebatten

    Air space (20 mm min) aboveinsulation to provide a space to drapethe breathable sarking membrane

    Timberbatten

    Timber batten

    Kingspan ThermapitchTP10 zero ODPbetween rafters

    Kingspan Thermawall TW56zero ODP under rafters

    Horizontal lap betweenruns of sarking felt

    Rafter

    Ventilated air space(50 mm min) aboveinsulation to currentBuilding Regulations/Standards

    Sarking felt

    Slates****18 mmsarking board

    Timber batten

    Kingspan ThermawallTW56 zero ODPunder rafters**/***

    Horizontal lap between runs ofbreathable sarking membranesealed (if required) with75 mm wide doublesided acrylicadhesive tape

    Rafter

    Kingspan Thermapitch TP10 zeroODP between rafters

    Tiles/slates

    Tiles/slate batten

    *Breathable sarkingmembrane eg.Kingspan nilvent

    38 x 38 mm counter batten

    Kingspan ThermawallTW56 zero ODP underrafters**/***

    18 mmsarking board

    Horizontal lap between runs ofbreathable sarking membrane sealed(if required) with 75 mm widedouble sided acrylicadhesive tape

    Rafter

    Kingspan Thermapitch TP10 zero ODPbetween rafters

    Slates****

    *Breathable sarkingmembrane eg.Kingspan nilvent

    Kingspan ThermawallTW56 zero ODPunder rafters**/***

    18 mmsarking board

    Kingspan Thermawall TW56zero ODP under rafters**/***

    Unventilatedair space

    Timberbatten

    Kingspan ThermapitchTP10 zero ODPbetween rafters

  • 3FIGURE 3 UNVENTILATEDINSULATION BETWEEN RAFTERS(Recommended for new build or reroofing)

    Figure 3a FULLY FILLED INSULATION BETWEEN RAFTERS NO SARKING BOARD

    Figure 3b PARTIALLY FILLED INSULATION BETWEEN RAFTERS NO SARKING BOARD

    Figure 3c FULLY FILLED INSULATION BETWEEN RAFTERS 18 mm SARKING BOARD

    Figure 3d PARTIALLY FILLED INSULATION BETWEEN RAFTERS 18 mm SARKING BOARD

    FIGURE 4 VENTILATEDINSULATION BETWEEN RAFTERS(Recommended for loft conversion)

    Figure 4a NO SARKING BOARD Figure 4b 18 mm SARKING BOARD

    Horizontal lap between runs ofbreathable sarking membranesealed (if required) with75 mm wide doublesided acrylicadhesivetape

    Rafters

    Kingspan Thermapitch TP10zero ODP between rafters12.5 mm plasterboard**

    Tiles/slates

    Tiles/slate batten

    38 x 38 mmcounter batten

    *Breathable sarkingmembrane eg.Kingspan nilvent

    Tiles/slates Tiles/slatebatten

    Horizontal lap between runs ofbreathable sarking membranesealed (if required) with75 mm wide doublesided acrylicadhesivetape

    Rafter

    Kingspan Thermapitch TP10zero ODP between rafters12.5 mm plasterboard**

    Slates****18 mmsarking board

    *Breathablesarking membraneeg. Kingspan nilvent

    Kingspan ThermapitchTP10 zero ODPbetween rafters

    Horizontal lap betweenruns of sarking felt

    Timberbatten

    Rafter

    Ventilated air space(50 mm min) aboveinsulation to currentBuilding Regulations/Standards

    12.5 mmplasterboard**

    Sarking felt

    Tiles/slates Tile/slatebatten

    Kingspan ThermapitchTP10 zero ODPbetween rafters

    12.5 mmplasterboard**

    Horizontal lap betweenruns of sarking felt

    Rafter

    Ventilated air space(50 mm min) aboveinsulation to currentBuilding Regulations/Standards

    Sarking felt

    Slates**** 18 mmsarking board

    Timberbatten

    Rafter

    Kingspan ThermapitchTP10 zero ODP between rafters

    12.5 mmplasterboard**

    Breathable sarkingmembrane eg.Kingspan nilvent

    Air space (25 mm min) aboveinsulation to provide a space to drapethe breathable sarking membrane

    Timberbatten

    Horizontal lap between runs of breathable sarking membrane.NB. The breathable sarking membranecould be installed vertically undercounter battens and pulled tautin which case the air spaceunder the breathablesarking membrane isunventilated

    Horizontal lap between runs ofbreathable sarking membranesealed (if required) with75 mm wide doublesided acrylicadhesivetape

    Rafters

    Kingspan ThermapitchTP10 zero ODPbetween rafters

    12.5 mmplasterboard**

    Timberbatten

    Slates****18 mmsarking board

    *Breathablesarkingmembraneeg. Kingspannilvent

    Unventilated airspace

    Air barriere.g. Kingspan nilvent

    Air barriere.g. Kingspan nilvent

  • 4SPECIFICATION CLAUSE

    Kingspan Thermapitch TP10 zero ODP should bedescribed in specifications as:

    The rafter level insulation shall be KingspanThermapitch TP10 zero ODP ____mm thickcomprising a CFC/HCFCfree rigid urethaneinsulation core with low emissivity composite foilfacings on both sides manufactured to BS EN ISO9002: 1994/I.S. EN ISO 9001: 2000 byKingspan Insulation Limited and shall be applied inaccordance with the instructions issued by them.

    Details also available in NBS PLUS.NBS users should refer to clauseK11 695.

    NBS

    P

    L US

    P

    LU

    S

    * The breathable sarking membrane can be placed over thecounter battens, draped to provide for drainage and overlainwith tile/slate battens. This will yield a marginally betterUvalue but it will be more difficult to seal the breathablesarking membrane effectively.

    ** The requirement for a vapour control layer and/or under tileventilation should be assessed to BS 5250: 1989 (1995).Vapour check plasterboard or a separate vapour control layercan be used as preferred.

    *** Kingspan Thermawall TW56 zero ODP contains an integralvapour control layer.

    **** If tiles are to be used then this normally necessitates the use ofcounter battens and tiling battens over the breathable sarkingmembrane to allow for water drainage and attachment of thetiles.

    Kingspan pitch TP10 zero ODP

    FIGURE 6 UNVENTILATEDINSULATION OVER RAFTERS(Recommended for new build or reroofing)

    Figure 6a NO SARKING BOARD Figure 6b 18 mm SARKING BOARD

    FIGURE 5 UNVENTILATEDINSULATION BETWEEN & OVER RAFTERS(Recommended for new build or reroofing)

    Figure 5a NO SARKING BOARD Figure 5b 18 mm SARKING BOARD

    Horizontal lap between runs of breathablesarking membrane sealed(if required) with75 mm wide doublesided acrylicadhesivetape

    Rafter

    Kingspan ThermapitchTP10 zero ODP betweenand over rafters

    12.5 mmPlasterboard**

    Tiles/slates

    Tiles/slate batten

    *Breathable sarkingmembrane eg.Kingspan nilvent

    Nailablesarking clips

    38 x 38 mmcounter batten

    Horizontal lap between runs of breathablesarking membrane sealed(if required) with75 mm wide doublesided acrylicadhesivetape

    Rafter

    Kingspan Thermapitch TP10zero ODP over rafters12.5 mm Plasterboard**

    Tiles/slates

    Tiles/slate batten

    *Breathable sarkingmembrane eg.Kingspan nilvent

    38 x 38 mmcounter batten

    Horizontal lap between runs ofbreathable sarking membranesealed (if required) with75 mm wide doublesided acrylicadhesivetape

    Rafter

    Kingspan ThermapitchTP10 zero ODP betweenand over rafters

    Nailable sarking clipsTimber battens

    Slates****18 mmsarking board

    *Breathable sarkingmembrane eg.Kingspan nilvent

    12.5 mmPlasterboard**

    Horizontal lap between runs ofbreathable sarking membranesealed (if required) with75 mm wide doublesided acrylicadhesivetape

    Rafter

    Kingspan Thermapitch TP10zero ODP over raftersTimber

    battensUnventilatedair space

    Slates****18 mmsarking board

    *Breathable sarkingmembrane eg.Kingspan nilvent

    12.5 mmplasterboard**

    Unventilated air space

    Unventilated air space

    Unventilated air space

  • 5An additional benefit of two layer systems and theInsulation Over Rafter approach (see Figure 1, 2, 5 & 6)is that thermal bridging caused by the rafter is preventedand the potential for pattern staining in the position of therafters is completely avoided. The choice maybeinfluenced by the available headroom and concerns overthe depth of bargeboards.

    Approaches with a layer of insulation over rafter arelikely to yield very large fascia boards and sogenerally, between and under rafter insulationapproaches are probably more desirable e.g. (Figures 1 and 2).

    Note: However, where the choice is for two layers,the layer with the greatest effective Rvalue should beplaced uppermost in order to prevent condensationbetween the two layers.

    UNVENTILATED ROOF VENTILATIONCONSIDERATIONSUnventilated roof approaches create a warm pitchedroof space, which does not require cross ventilation.Recent research suggests that sealing an unventilatedroof, yields a more energy efficient roof as theimpacts of ventilation and incidental infiltrating coldair are negated. Therefore, if creating an unventilatedroof, it is preferable to fully seal all joints in thebreathable sarking membrane with tape. Any watervapour reaching the breathable sarking membraneescapes without condensing. There is then adequateair movement beneath the tiles to dissipate this watervapour to the outside atmosphere. Tape for sealingjoints in the breathable sarking membrane should bespecified in accordance with the recommendations ofthe breather membrane manufacturer.

    The requirement for a vapour control layer and/orundertile ventilation should be assessed to BS 5250:1989 (1995) (Code of practice for control ofcondensation in buildings). Vapour check plasterboardor a separate vapour control layer can be specified,as preferred if required.

    Note: Kingspan Thermawall TW56 zero ODP, asused in Figure 1, contains an integral vapour controllayer.

    VENTILATED ROOF VENTILATIONCONSIDERATIONSIn these cases the Building Regulations/Standards requirea 50 mm ventilation air gap between the insulation andthe sarking felt, so as to avoid condensation.

    The requirement for a vapour control layer should beassessed to BS 5250: 1989 (1995) (Code of practicefor control of condensation in buildings). Vapour checkplasterboard or a separate vapour control layer can bespecified, as preferred if required.

    Note: Kingspan Thermawall TW56 zero ODP, asused in Figure 2, contains an integral vapour control layer.

    BREATHABLE SARKING MEMBRANEBS 5250: 1989 (1995) (Code of practice for control ofcondensation in buildings) recommends that the vapourresistance of the breathable sarking membrane e.g.Kingspan nilvent TM must not exceed 0.25 MN.s/g.

    DESIGN CONSIDERATIONS

    SUSTAINABILITYIt is widely recognised that there are four main globalenvironmental sustainability issues: global warming,nonrenewable resource depletion, toxic pollution and ozone depletion, and that these global issues far outweigh any local sustainability issues in theirneed for immediate attention and potential impactfrom inaction.

    Recent studies have shown that the first three issuesare essentially one. The extraction and consumption(burning) of fossil fuels is by far the most significantcontributor to global warming, nonrenewableresource depletion and toxic pollution.

    Therefore, saving energy by specifying the lowest Uvalue possible and using zero ODP insulationmaterials are the best actions to take whenconsidering sustainability for the insulationrequirements of a building.

    Kingspan Thermapitch TP10 zero ODPis manufactured without the use ofCFCs/HCFCs and has zero OzoneDepletion Potential (ODP).

    In the past, erroneously, the relativesustainability of insulation materials has beencompared on the basis of embodied energy. It is nowknown that the embodied energy of insulationmaterials is insignificant compared with the energysaved by insulation over the lifetime of a building inwhich it is used and so is of limited importance.However, it is a matter of social responsibility to statethe environmental impact in the manufacture of aproduct, and a full Life Cycle Analysis (LCA) ratherthan embodied energy is recognised as the preferredtool to achieve this.

    An LCA, independently certified by theBRE, has been carried out for UKproduced Kingspan Thermapitch TP10zero ODP and a copy is available fromKingspan Insulation, see rear cover.Kingspan Insulation Limited is the first insulationmanufacturer to publish openly such information.

    UNVENTILATED (SEALED AND UNSEALED) ANDVENTILATED CONSTRUCTIONSThere is generally a choice between either approach,except in the case of refurbishment/loft conversions.In these instances, unless the whole roof is to bestripped, it is impossible to use an unventilated roof,because a breathable sarking membrane cannot beinstalled.

    Recent research suggests that the unventilated, sealedroof approach yields a more energy efficient roof asthe impacts of ventilation and incidental infiltratingcold air are negated.

    POSITION OF INSULATIONDependent on the designed insulation value of theconstruction and the available rafter depth and headroom,different approaches can be taken. It may be necessaryto use two layers of insulation to achieve requiredUvalues e.g. Figures 1, 2 & 5.

  • 6The Uvalue requirements as detailed in theappropriate Building Regulations/Standards can beeasily achieved utilising the appropriate thickness ofKingspan Thermapitch TP10 zero ODP. Thecalculation of Uvalues for pitched roof insulationpurposes is determined by a number of factors: will the loft space be habitable or not; does the ceiling line follow the pitch of the roof or

    is it a flat horizontal ceiling; the pitch of the roof (where a horizontal ceiling is

    to be used); and rafter centres/depth/width where insulation is

    between rafters.

    The following examples have been calculated usingboth the combined method and the proportional areamethod. The combined method is required forcompliance with Building Regulations/Standardsrevised after the year 2000. These examples arebased on the constructions shown in Figures 1 to 6with 50 mm wide rafters at 600 mm centres and12.5 mm plasterboard.* If your construction is anydifferent, please consult our Technical ServicesDepartment (see rear cover).

    Combined Method Uvalues were calculated usingthe method which has been adopted to bringNational standards in line with the EuropeanStandard calculation method, BS/I.S. EN ISO 6946:1997 (Building components and building elements.Thermal resistance and thermal transmittance.Calculation method).

    Proportional Area Method Uvalues were calculatedusing the method detailed in The Chartered Institute ofBuilding Services Engineers (CIBSE) Guide A3(Thermal Properties of Building Structures).

    NB when calculating Uvalues using the combined method asdetailed in BS/I.S. EN ISO 6946: 1997, the type of mechanicalfixing used may change the thickness of insulation required. The effectof fixings has been ignored for the purposes of these calculations.Please contact the Kingspan Insulation Technical Services Department(see rear cover) for project calculations.

    NB for the purposes of these calculations the standard ofworkmanship has been assumed good and therefore the correctionfactor for air gaps has been ignored.

    The figures in the Uvalue tables (pages 79) are for guidance only.A detailed Uvalue calculation together with a condensation riskanalysis should be completed for each individual project. Please callour Technical Services Department for assistance (see rear cover).

    *Unless otherwise stated.

    TYPICAL UVALUES

    POSITION OF BREATHABLE SARKING MEMBRANEThe taping of breathable sarking membrane joints isconsiderably easier to achieve if the membrane isinstalled on a continuous surface (Figures 1a, 1c, 1d,3a, 3c, 3d, 5a, 5b, 6a & 6b).

    In these cases, the breathable sarking membrane isinstalled under the counter battens, which provide achannel for water drainage, or in situations with a sarkingboard under a slated roof, directly under the slates (asneither tile battens nor counter battens are used).

    Generally, when a continuous surface is available, itwill prove easier to install the breathable sarkingmembrane in horizontal runs, whilst still enabling easysealing between runs.

    In some cases with a continuous surface (Figure 1a,3a, 5a & 6a, and 1c, 1d, 3c, 3d, 5b & 6b whencounter battens, tiling battens and tiles replace slatesnailed directly into the sarking board) the breathablesarking membrane can be installed over the counterbattens. This yields a marginally better design Uvaluebut it may be more difficult to seal the breathablesarking membrane joints effectively, as the membranemust be draped over the counter battens in horizontalruns so as to provide a water drainage channel.The air movement allowed by the unsealed membranemay negate the benefit of putting the membraneabove the counter battens.

    In situations where there is no continuous surface(Figures 1b and 3b), the breathable sarking membranecan be draped over the rafters in horizontal runs toprovide a channel for water drainage. In this situation,sealing of the breathable sarking membrane joints willprove difficult.

    In roofs with no continuous surface, it is preferable,though more difficult, to install the breathable sarkingmembrane in vertical runs with junctions between runssealed by counterbattens placed over the laps inrafter positions. The breathable sarking membrane isinstalled taut as the counterbatten provides a spacefor water drainage.

    RECOMMENDED SOLUTIONS FOR NEW BUILD/REROOFINGThe ideal solution for new build or reroofing projects is,therefore, between and under rafter insulation with acontinuous surface for the breathable sarking membraneso that it can be installed in horizontal runs undercounterbattens with laps sealed (Figures 1a, 1c and 1d).

    The next best solution is, therefore, between andunder rafter insulation with no continuous surface forthe breathable sarking membrane, and the breathablesarking membrane installed in vertical runs with lapssealed under counterbattens (Figure 1b).

    MANSARD ROOFS/WALLSKingspan Thermapitch TP10 zero ODP can be usedfor the construction of insulated tiled or slated mansardroofs/walls. Its application on such contracts is identicalto the standard specification, which is given here.

    FIRE STOPSCurrent Building Regulations/Standards should beconsidered with regard to the requirements for and/orprovision of fire stops.

    Kingspan pitch TP10 zero ODP

  • 7PARTIALLY FILLED INSULATION BETWEEN RAFTERS 18 mm SARKING BOARD (Fig 1d)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method25 30 0.34 0.3340 0.31 0.3050 0.28 0.2760 0.26 0.2465 0.25 0.2470 0.24 0.2375 0.23 0.2280 0.22 0.2190 0.21 0.2095 0.20 0.19

    100 0.19 0.18110 0.18 0.17120 0.17 0.16125 0.17 0.16130 0.16 0.15

    NB calculations based on rafters being underlined with Kingspan ThermawallTW56 zero ODP comprising 12.5 mm plasterboard and 25 mm of insulation ofthermal conductivity 0.022 W/m.K. Thickness shown in the table above is only thebetween rafter component. Calculations assume that there is a minimum 25 mmairspace between the rafters above the insulation layer installed between them.NB the thermal resistance of the between rafter layer must be that of the underrafter layer so as to avoid condensation.

    VENTILATEDINSULATION BETWEEN & UNDER RAFTERS

    NO SARKING BOARD (Fig 2a)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method25 30 0.39 0.3340 0.35 0.3050 0.31 0.2755 0.30 0.2660 0.28 0.2570 0.26 0.2375 0.25 0.2280 0.24 0.2190 0.22 0.19

    100 0.21 0.18105 0.20 0.18110 0.19 0.17120 0.18 0.16125 0.18 0.16130 0.17 0.15140 0.16 0.15

    NB calculations based on rafters being underlined with Kingspan ThermawallTW56 zero ODP comprising 12.5 mm plasterboard and 25 mm of insulation ofthermal conductivity 0.022 W/m.K. Thickness shown in the table above is onlythe between rafter component. Calculations assume that there is a minimum 50 mm ventilated airspace between the rafters above the insulation layerinstalled between them.NB the thermal resistance of the between rafter layer must be that of the underrafter layer so as to avoid condensation.

    UNVENTILATEDINSULATION BETWEEN & UNDER RAFTERSFULLY FILLED INSULATION BETWEEN RAFTERS NO SARKING BOARD (Fig 1a)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method75 0.25 0.23

    100 0.21 0.20125 0.18 0.17150 0.15 0.15

    NB calculations based on rafters being underlined with Kingspan ThermawallTW56 zero ODP comprising 12.5 mm plasterboard and 25 mm of insulation ofthermal conductivity 0.022 W/m.K. Thickness shown in the table above is only thebetween rafter component.NB the thermal resistance of the between rafter layer must be that of the underrafter layer so as to avoid condensation.

    PARTIALLY FILLED INSULATION BETWEEN RAFTERS NO SARKING BOARD (Fig 1b)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method25 30 0.35 0.3340 0.31 0.2945 0.29 0.2850 0.28 0.2760 0.26 0.2565 0.25 0.2470 0.24 0.2375 0.23 0.2280 0.22 0.2190 0.21 0.2095 0.20 0.19

    100 0.19 0.18110 0.18 0.17120 0.17 0.16125 0.17 0.16130 0.16 0.15

    NB calculations based on rafters being underlined with Kingspan ThermawallTW56 zero ODP comprising 12.5 mm plasterboard and 25 mm of insulation ofthermal conductivity 0.022 W/m.K. Thickness shown in the table above is only thebetween rafter component. Calculations assume that there is a minimum 25 mmairspace between the rafters above the insulation layer installed between them.NB the thermal resistance of the between rafter layer must be that of the underrafter layer so as to avoid condensation.

    FULLY FILLED INSULATION BETWEEN RAFTERS 18 mm SARKING BOARD (Fig 1c)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method75 0.25 0.23

    100 0.21 0.19125 0.18 0.17150 0.15 0.15

    NB calculations based on rafters being underlined with Kingspan ThermawallTW56 zero ODP comprising 12.5 mm plasterboard and 25 mm of insulation ofthermal conductivity 0.022 W/m.K. Thickness shown in the table above is only thebetween rafter component.NB the thermal resistance of the between rafter layer must be that of the underrafter layer so as to avoid condensation.

    18 mm SARKING BOARD (Fig 2b)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method25 30 0.39 0.3340 0.35 0.3050 0.31 0.2755 0.30 0.2660 0.28 0.2570 0.26 0.2375 0.25 0.2280 0.24 0.2190 0.22 0.19

    100 0.21 0.18105 0.20 0.18110 0.19 0.17120 0.18 0.16125 0.18 0.16130 0.17 0.15140 0.16 0.15

    NB calculations based on rafters being underlined with Kingspan ThermawallTW56 zero ODP comprising 12.5 mm plasterboard and 25 mm of insulation ofthermal conductivity 0.022 W/m.K. Thickness shown in the table above is onlythe between rafter component. Calculations assume that there is a minimum 50 mm ventilated airspace between the rafters above the insulation layerinstalled between them.NB the thermal resistance of the between rafter layer must be that of the underrafter layer so as to avoid condensation.

    Although 20 and 25 mm Kingspan Thermapitch TP10 zero ODP is available, its effective Rvalue is that of the insulated plasterboard under the rafters. This carries apotential condensation risk.

  • UNVENTILATEDINSULATION BETWEEN RAFTERSFULLY FILLED INSULATION BETWEEN RAFTERS NO SARKING BOARD (Fig 3a)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method75 0.36 0.35

    100 0.28 0.27125 0.23 0.22150 0.19 0.19175 0.17 0.16200 0.15 0.15

    8

    PARTIALLY FILLED INSULATION BETWEEN RAFTERS NO SARKING BOARD (Fig 3b)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method45 0.45 0.4350 0.42 0.4060 0.37 0.3565 0.35 0.3370 0.33 0.3175 0.32 0.3080 0.30 0.2890 0.28 0.26

    100 0.26 0.24110 0.24 0.22115 0.23 0.22120 0.22 0.21125 0.21 0.20130 0.21 0.19135 0.20 0.19140 0.19 0.18150 0.18 0.17160 0.17 0.16170 0.16 0.16

    NB calculations assume that there is a minimum 25 mm airspace between therafters above the insulation layer installed between them.

    FULLY FILLED INSULATION BETWEEN RAFTERS 18 mm SARKING BOARD (Fig 3c)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method75 0.36 0.34

    100 0.28 0.27125 0.23 0.22150 0.19 0.19175 0.17 0.16200 0.15 0.15

    PARTIALLY FILLED INSULATION BETWEEN RAFTERS 18 mm SARKING BOARD (Fig 3d)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method45 0.45 0.4250 0.42 0.4060 0.37 0.3565 0.35 0.3470 0.33 0.3275 0.32 0.3180 0.30 0.2990 0.28 0.27

    100 0.25 0.25110 0.24 0.23120 0.22 0.21125 0.21 0.21130 0.20 0.20140 0.19 0.19145 0.19 0.18150 0.18 0.18160 0.17 0.17165 0.17 0.16

    NB calculations assume that there is a minimum 25 mm airspace between therafters above the insulation layer installed between them.

    VENTILATEDINSULATION BETWEEN RAFTERSNO SARKING BOARD (Fig 4a)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method60 0.43 0.3670 0.38 0.3275 0.36 0.3080 0.34 0.2990 0.31 0.2695 0.29 0.25

    100 0.28 0.24110 0.26 0.22115 0.25 0.22120 0.24 0.21125 0.23 0.20130 0.22 0.20140 0.21 0.18145 0.20 0.18150 0.19 0.17160 0.18 0.16170 0.17 0.16175 0.17 0.17180 0.16 0.15

    NB calculations assume that there is a minimum 50 mm ventilated airspace betweenthe rafters above the insulation layer installed between them.

    18 mm SARKING BOARD (Fig 4b)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method60 0.43 0.3670 0.38 0.3275 0.36 0.3080 0.34 0.2990 0.31 0.2695 0.29 0.25

    100 0.28 0.24110 0.26 0.22115 0.25 0.22120 0.24 0.21125 0.23 0.20130 0.22 0.20140 0.21 0.18145 0.20 0.18150 0.19 0.17160 0.18 0.17170 0.17 0.16175 0.17 0.17180 0.16 0.15

    NB calculations assume that there is a minimum 50 mm ventilated airspacebetween the rafters above the insulation layer installed between them.

    Kingspan pitch TP10 zero ODP

  • 9UNVENTILATEDINSULATION BETWEEN & OVER RAFTERS

    NO SARKING BOARD (Fig 5a)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method20+20 0.43 0.4325+25 0.36 0.3625+30 0.34 0.3430+30 0.32 0.3240+40 0.26 0.2540+45 0.25 0.2450+50 0.22 0.2155+55 0.20 0.1960+60 0.19 0.1860+65 0.18 0.1770+70 0.17 0.1670+75 0.16 0.15

    NB first thickness refers to thickness between rafters, second thicknessover rafters. The thermal resistance of the over rafter layer must be that of the between rafter layer so as to avoid condensation.NB combined method calculation accounts for the effect of using astainless steel fixing of 6.0 mm diameter, giving a cross sectionalarea of 7.45 mm2.

    18 mm SARKING BOARD (Fig 5b)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method20+20 0.42 0.4325+25 0.36 0.3625+30 0.33 0.3430+30 0.32 0.3140+40 0.26 0.2540+45 0.25 0.2450+50 0.22 0.2155+55 0.20 0.1960+60 0.19 0.1860+65 0.18 0.1770+70 0.17 0.1570+75 0.16 0.15

    NB first thickness refers to thickness between rafters, second thicknessover rafters. The thermal resistance of the over rafter layer must be that of the between rafter layer so as to avoid condensation.NB combined method calculation accounts for the effect of using astainless steel fixing of 6.0 mm diameter, giving a cross sectionalarea of 7.45 mm2.

    UNVENTILATEDINSULATION OVER RAFTERS

    NO SARKING BOARD (Fig 6a)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method40 0.41 0.4150 0.35 0.3560 0.30 0.3070 0.27 0.2775 0.25 0.2580 0.24 0.2490 0.22 0.22

    100 0.20 0.20110 0.19 0.18120 0.18 0.17125 0.17 0.16130 0.16 0.16

    NB combined method calculation accounts for the effect of using astainless steel fixing of 6.0 mm diameter, giving a cross sectionalarea of 7.45 mm2.

    18 mm SARKING BOARD (Fig 6b)

    Insulant Thickness Uvalue (W/m2.K)(mm) Combined Method Proportional

    Area Method35 0.43 0.4540 0.39 0.4150 0.34 0.3560 0.29 0.3070 0.26 0.2775 0.25 0.2580 0.23 0.2490 0.21 0.22

    100 0.20 0.20110 0.19 0.18115 0.18 0.18120 0.17 0.17125 0.17 0.16130 0.16 0.16

    NB combined method calculation accounts for the effect of using astainless steel fixing of 6.0 mm diameter, giving a cross sectionalarea of 7.45 mm2.

  • 10

    OVER RAFTER LAYER OF INSULATIONOver rafter insulation without a sarking board (Figures5a & 6a), is simply fixed by placing the KingspanThermapitch TP10 zero ODP boards over therafters and under 38 x 38 mm treated softwoodcounterbattens in line with the rafters. Secure thecounterbattens to the rafters by fixing through boththe counterbattens and the Kingspan ThermapitchTP10 zero ODP.

    Over rafter insulation with slates fixed directly into asarking board (Figures 5b & 6b), is simply fixed byplacing the Kingspan Thermapitch TP10 zero ODPboards over the rafters with the sarking boardoverlaid. Secure the sarking board and KingspanThermapitch TP10 zero ODP to the rafters by fixingthrough both the sarking board and the KingspanThermapitch TP10 zero ODP.

    Over rafter insulation with a sarking board and tileson tiling battens and counter battens, is simply fixedby placing the Kingspan Thermapitch TP10 zeroODP boards over the rafters with the sarking boardoverlaid, and with 38 x 38 mm softwood treatedcounterbattens in line with the rafters. Secure thecounterbattens to the rafters by fixing through thecounterbatten, the sarking board and the KingspanThermapitch TP10 zero ODP.

    Boards of Kingspan Thermapitch TP10 zero ODPshould be tightly butted, they may be laid eitheracross or down the line of the rafters and shouldpreferably be laid break bonded. All board jointsrunning from eaves to ridge must occur over rafters.There is no necessity to tape board joints. Apreservative treated stop rail should be secured to therafters close to the eaves (see Figures 9a & 9b).

    BETWEEN RAFTER LAYER OF INSULATIONBetween rafter insulation can be installed by threemethods.

    In cases where the insulation between rafters is to beflush with the top of the rafters but does not fill the fullrafter depth (Figure 5), install the insulation by the useof nailable sarking clips. The nailable sarking clipsare driven into the upper surface of each rafter atonemetre intervals up the roof slope. The nailablesarking clips then support lengths of KingspanThermapitch TP10 zero ODP suitably trimmed tosize and placed between the rafters.

    In cases where the insulation between rafters is to beflush with the bottom of the rafters but does not fill thefull rafter depth (Figures 1b, 1d, 2a, 2b, 3b, 3d, 4a& 4b), install the insulation with the aid of battensnailed to the side of the rafters. The battens should bein the appropriate position to ensure the insulation isflush with the bottom of the rafters.

    SITEWORK

    In cases where the insulation between rafters fully fillsthe rafter depth (Figures 1a ,1c, 3a & 3c), simplyinstall the correct thickness of insulation in such amanner that it is flush with the bottom of the rafters.

    In all cases, ensure that insulation boards are tightlybutted and that there is a tight fit between theinsulation and the rafters. Fill all gaps with expandingurethane sealant.

    UNDER RAFTER LAYER OF INSULATIONPlease refer to literature for Kingspan ThermawallTW56 zero ODP.

    BREATHABLE SARKING MEMBRANEThe specified breathable sarking membrane(e.g. Kingspan nilvent TM) is applied as specified.Application advice should be sought from theappropriate membrane manufacturer.

    SARKING FELTIn cases without a sarking board, the sarking felt isdraped over the rafters to provide a channel for waterdrainage and held in place by the slate/tile battens,which are nailed through the felt to the rafters.

    In cases with a sarking board, the sarking felt isapplied over the sarking board and held in place bythe slates or counter battens which are nailed throughthe felt to the sarking board.

    SLATING AND TILINGSlating and tiling over Kingspan Thermapitch TP10zero ODP is exactly the same as on any otherpitched roof except that in some instances the slate/tile battens are fixed to the previously appliedcounterbattens. It is, however, essential that slate ortiling rubble does not lay in contact with thebreathable sarking membrane (if used) as this mayallow wind driven rain or melted snow to penetratethe breathable sarking membrane.

    SURFACE TREATMENTThe boards of Kingspan Thermapitch TP10 zeroODP have a foil faced durable surface and no furthertreatment is necessary. Kingspan Thermapitch TP10zero ODP is not intended to provide an internal finishand should be underlined with a suitable buildingboard.

    CUTTINGCutting should be carried out using a fine toothedsaw or by scoring with a knife and snapping theboard over a straight edge and cutting the facing onthe other side. Ensure accurate trimming to achieveclose butting joints and continuity of insulation.

    Kingspan pitch TP10 zero ODP

  • 11

    UNVENTILATEDINSULATION BETWEEN & UNDER RAFTERS OR JUST BETWEEN RAFTERS(Recommended for new build or reroofing)

    DAILY WORKING PRACTICEInstalled Kingspan Thermapitch TP10 zero ODPboards should be protected against inclementweather.

    FIXINGS FOR OVER RAFTER INSULATIONHelifix InSkew, Target Skewfast, WallfastTimfix or similar approved fixings should be appliedat centres appropriate to the design of the roof andlocation of the building.Refer to:Helifix Limited +44 (0) 20 8735 5222;Target Fixings Limited +44 (0) 1344 777 189; orWallfast Limited +44 (0) 23 9265 3330.

    AVAILABILITYKingspan Thermapitch TP10 zero ODP is availablethrough specialist insulation distributors and selectedbuilders and roofing merchants throughout the UK,Ireland and Europe.

    PACKAGINGAccording to quantity, the boards are supplied inpacks or on pallets, labelled and shrinkwrapped inpolythene.

    STORAGEThe packaging of Kingspan Thermapitch TP10zero ODP should not be considered adequate forlong term outside protection. Ideally boards should bestored inside a building. If however, outside storagecannot be avoided the boards should be stackedclear of the ground and covered with a polythenesheet or weatherproof tarpaulin. Boards that havebeen allowed to get wet should not be used.

    HEALTH AND SAFETYKingspan Insulation products are chemically inert andsafe to use. A leaflet on this topic which satisfies therequirements set out in the Control of SubstancesHazardous to Health Regulations 1988 (COSHH) isavailable from our Technical Services Department (seerear cover).

    Please note that the reflective surface on this product is designed toenhance its thermal performance. As such, it will reflect light as wellas heat, including ultraviolet light. Therefore, if this board is beinginstalled during very bright or sunny weather, it is advisable to wearUV protective sunglasses or goggles, and if the skin is exposed for asignificant period of time, to protect the bare skin with a UV blocksun cream.

    Warning do not stand on or otherwise support your weight on thisboard unless it is fully supported by a load bearing surface.

    Figure 7a OVERHANGING EAVES DETAIL SECTION PERPENDICULAR TO RIDGE

    Figure 7b SECTION PARALLEL TO RIDGE

    Flexible insulation materialtightly packed to blockcold bridge and retard airinfiltration.

    Cavity closer

    Breathable sarking membraneeg. Kingspan nilvent drapedover rafters in horizontal runs

    Breathablesarking membranelapped overeaves strip

    Tiles/slates

    Eaves stripKingspan Thermapitch TP10zero ODP between rafters

    Kingspan Thermawall TW56zero ODP under rafters (can bereplaced with plasterboard)

    Tiles/slate batten

    Rafter

    Seal gap between floorand sloping ceiling

    Flexible insulation material tightly packed toblock cold bridge and retard air infiltration.

    Breathable sarking membraneeg. Kingspan nilvent drapedover rafters in horizontal runs

    Breathable membrane fullycovering the undercloakTiles/slates

    KingspanThermapitchTP10 zeroODP betweenrafters

    KingspanThermawall TW56zero ODP underrafters (can bereplaced with 12.5 mmplasterboard)

    Air space 25mm (min.) toprovide spaceto drape thebreathablesarkingmembrane

    Tiles/slate batten

    Mortar infill

    Rafter Timberbatten

    Flying rafter

    Fascia board

    Cavity closer

  • 12

    Kingspan pitch TP10 zero ODP

    VENTILATEDINSULATION BETWEEN & UNDER RAFTERS OR JUST BETWEEN RAFTERS(Recommended for loft conversion)

    Figure 8a OVERHANGING EAVES DETAIL SECTION PERPENDICULAR TO RIDGE

    Figure 8b SECTION PARALLEL TO RIDGE

    Flexible insulation material tightly packed toblock cold bridge and retard air infiltration.

    Sarking felt draped over raftersin horizontal runs

    Sarking felt fully coveringthe undercloakTiles/slates

    KingspanThermapitchTP10 zero ODPbetween rafters

    KingspanThermawallTW56 zero ODPunder rafters (canbe replaced with12.5 mmplasterboard)

    Tiles/slate batten

    Mortar infill

    Rafter

    Timber battenFlying rafter

    Fascia board

    Cavity closer

    Flexible insulation material tightly packed toblock cold bridge and retard air infiltration.Cavity closer

    Sarking felt draped over raftersin horizontal runs

    Sarking felt is laidinto the gutter

    Tiles/slates

    Kingspan Thermapitch TP10zero ODP between rafters

    Kingspan Thermawall TW56zero ODP under rafters (can bereplaced with plasterboard)

    Tiles/slate batten

    Rafter

    Proprietary eaves ventilator

    Seal gap between floorand sloping ceiling

    JoistVentilation post

    Air flow path mustnot be blocked

    Ventilated airspace 50 mm(min.) to currentBuildingRegulation/Standards

  • 13

    UNVENTILATEDINSULATION BETWEEN & OVER RAFTERS OR JUST OVER RAFTERS(Recommended for new build or reroofing)

    Figure 9a OVERHANGING EAVES DETAIL SECTION PERPENDICULAR TO RIDGE

    Figure 9b RIDGE DETAIL SECTION PERPENDICULAR TO RIDGE

    Breathable sarking membraneeg. Kingspan nilvent lapped150 mm (min) over the ridge fromeach side

    Flexible insulation materialtightly packed to blockcold bridge and retardair infiltration.

    Cavity closer

    38 x 38 mm counter batten

    Tiles/slates Kingspan Thermapitch TP10 zero ODPbetween (if required) and over rafters

    Tiles/slate batten

    Breathable sarking membraneeg. Kingspan nilventdraped over rafters inhorizontal runs

    Rafters

    12.5 mm plasterboard

    Seal gap between floorand sloping ceiling

    Breathable sarkingmembrane lapped overeaves strip

    Eaves strip

    Figure 9c SECTION PARALLEL TO RIDGE

    Flexible insulation material tightly packed toblock cold bridge and retard air infiltration.

    Breathable sarking membraneeg. Kingspan nilvent drapedover rafters in horizontal runs

    Tiles/slates

    Kingspan Thermapitch TP10zero ODP between (ifrequired) and over rafters

    12.5 mm plasterboard

    Tiles/slate batten

    Mortar infill

    38 x 38 mm counter batten

    Timberbatten

    Rafter

    Flying rafter

    Breathable sarking membraneturned up by 50 mm (min.)

    Fascia board

    Cavity closer

    Undercloak

    Unventilatedairspace

  • THE FACINGSKingspan Thermapitch TP10 zero ODP is faced onboth sides with a low emissivity composite foil facingwhich is highly resistant to the transmission of watervapour. This reflective, low emissivity surfaceeffectively doubles the thermal resistance of the cavityin which the board is placed.

    THE COREThe core of Kingspan Thermapitch TP10 zero ODPis a high performance CFC/HCFCfree rigidurethane insulant of typical density 32 kg/m3.

    CFC/HCFCFREEKingspan Thermapitch TP10 zero ODPis manufactured without the use of CFCs/HCFCs and has zero Ozone DepletionPotential (ODP).

    PRODUCT DATA

    STANDARDS AND APPROVALSKingspan Thermapitch TP10 zero ODP ismanufactured to the highest standards under qualitycontrol systems approved to BS EN ISO 9002: 1994(Quality Systems. Model for quality assurance inproduction, installation and servicing)/I.S. EN ISO9001: 2000 (Quality management systems Requirements). Its use is covered by BBA Certificate95/3126.

    STANDARD DIMENSIONSKingspan Thermapitch TP10 zero ODP is availablein the following standard sizes and thicknesses:

    Nominal Dimension AvailabilityLength (m) 2.4Width (m) 1.2Insulant Thickness* (mm) 20, 25, 30, 35, 40, 45, 50,

    55, 60, 65, 70, 75, 80, 90,95, 100, 105, 110, 115, 120, 125, 130, 135, 140, 145, 150, 160, 165, 170,175, 180, 200

    * Other thicknesses are available subject to quantity.

    INSULATION COMPRESSIVE STRENGTHTypically exceeds 140 kPa at 10% compression when tested to BS EN 826: 1996 (Thermal insulatingproducts for building applications. Determination ofcompression behaviour).

    WATER VAPOUR RESISTANCEModified to include board facings, the boards achievea resistance far greater than 100 MN.s/g when testedin accordance with BS 4370: Part 2: 1993.

    DURABILITYIf correctly applied, Kingspan Thermapitch TP10zero ODP has an indefinite life. Its durability dependson the supporting structure and the conditions of its use.

    RESISTANCE TO SOLVENTS, FUNGI & RODENTSThe insulation core is resistant to dilute acids, alkalis,mineral oil and petrol. It is not resistant to somesolventbased adhesive systems, particularly thosecontaining methyl ethyl ketone. Adhesives containingsuch solvents should not be used in association withKingspan Thermapitch TP10 zero ODP. Boardswhich have been in contact with harsh solvents,petrol, mineral oil or acids, or boards that have beendamaged in any way should not be used.

    The insulation core and facings used in themanufacture Kingspan Thermapitch TP10 zeroODP resist attack by mould and microbial growth anddo not provide any food value to vermin.

    FIRE PERFORMANCEKingspan Thermapitch TP10 zero ODP, whensubjected to British Standard fire tests, achieves theresults given below.

    Test Result

    BS 476: Part 3: 1975 SAA rating(External fire exposure roof test)

    BS 476: Part 7: 1997 Class 1 rating(Surface Spread of Flame Test)

    Further details of the fire performance of KingspanInsulation products may be obtained from ourTechnical Services Department (see rear cover).14

    PRODUCT DESCRIPTION

    Kingspan pitch TP10 zero ODP

    BBABRITISHBOARD OFAGRMENTCERTIFICATE 95/3126

    BS EN ISO 9002 : 1994Certificate No. FM 10697

    I.S. EN ISO 9001: 2000Registration No. 19.0633

  • 15

    THE KINGSPAN INSULATIONPRODUCT RANGE

    THE KINGSPAN KOOLTHERM KRANGE With a thermal conductivity of 0.0220.024

    W/m.K rigid phenolic insulation is the mostthermally efficient insulation product commonlyavailable.

    Utilises the thinnest possible insulation board toachieve required Uvalues.

    Fire performance can be equivalent to mineral fibre. Achieves a Class O fire rating to the Building

    Regulations. Achieves the best possible rating of 30 mm).

    THERMAL RESISTANCESThermal resistance (Rvalue) varies with thickness andis calculated by dividing the thickness of the board(expressed in metres) by its thermal conductivity.

    Insulant Thickness Thermal Resistance(mm) (m2.K/W)

    20 0.9025 1.1030 1.3540 1.7050 2.1555 2.3560 2.6065 2.8070 3.0075 3.2580 3.4590 3.9095 4.10

    100 4.30105 4.55110 4.75115 5.00120 5.20125 5.40130 5.65135 5.85140 6.05145 6.30150 6.50160 6.95165 7.15175 7.60180 7.80200 8.65

  • I N S U L A T I O N

    Kingspan InsulationPembridge, Leominster, Herefordshire HR6 9LA, UK

    Castleblayney, County Monaghan, Ireland

    Kingspan, Kooltherm, the zo Device and the Lion Device are Registered Trademarks of the Kingspan Group plcTM Styrozone and Nilvent are Trademarks of the Kingspan Group plc

    www.insulation.kingspan.com

    CUSTOMER SERVICE

    For quotations, order placement and details of despatchesplease contact our Building Fabric Insulation CustomerServices Department on the numbers below:

    UK Telephone: +44 (0) 870 850 8555 Fax: +44 (0) 870 850 8666 email: [email protected]

    Ireland Telephone: +353 (0) 42 97 95000 Fax: +353 (0) 42 97 46129 email: [email protected]

    TECHNICAL ADVICE

    Kingspan Insulation Ltd support all of their products with acomprehensive Technical Advisory Service for specifiers,stockists and contractors.

    This includes a free computeraided service designed togive fast, accurate technical advice. Simply phone our

    with your project specification and we canrun calculations to provide Uvalues, condensation/dewpoint risk, required insulation thicknesses etc Thereafter wecan run any number of permutations to help you achieveyour desired targets.

    We can also give general application advice and advice ondesign detailing and fixing etc... Site surveys are alsoundertaken as appropriate.

    Please contact our Building Fabric Insulation TechnicalServices Department on the numbers below:

    LITERATURE AND SAMPLES

    Kingspan Insulation produces a comprehensive range oftechnical literature for specifiers, contractors, stockists andend users. The literature contains clear user friendly adviceon typical design; design considerations; thermal properties;sitework and product data.

    Available as a complete Design Manual or as individualproduct brochures, Kingspan Insulation technical literature isan essential specification tool. For copies please contact ourMarketing Department on the numbers below:

    UK Telephone: +44 (0) 1544 387 210 Fax: +44 (0) 1544 387 299 email: [email protected]

    Ireland Telephone: +353 (0) 42 97 95038 Fax: +353 (0) 42 97 46129 email: [email protected]

    GENERAL ENQUIRIES

    For all other enquiries contact Kingspan Insulation on thenumbers below:

    UK Telephone: +44 (0) 870 850 8555 Fax: +44 (0) 870 850 8666 email: [email protected]

    Ireland Telephone: +353 (0) 42 97 95000 Fax: +353 (0) 42 97 46129 email: [email protected]

    UK: Telephone: +44 (0) 870 850 8555 Fax: +44 (0) 1544 387 278 email: [email protected]

    Ireland: Telephone: +353 (0) 42 97 95032 Fax: +353 (0) 42 97 46129 email: [email protected]

    Kingspan Insulation reserve the right to amend product specificationswithout prior notice. Product thicknesses shown in this documentshould not be taken as being available ex-stock and reference shouldbe made to the current Kingspan Insulation price-list or advice soughtfrom Kingspan Insulation Sales department. The information, technicaldetails and fixing instructions etc. included in this literature are givenin good faith and apply to uses described. Recommendations for useshould be verified as to the suitability and compliance with actualrequirements, specifications and any applicable laws and regulations.For other applications or conditions of use, Kingspan Insulation offersa free Technical Advisory Service (see left) whose advice should besought for uses of Kingspan Insulation products that are notspecifically described herein. Please check that your copy of theliterature is current by contacting our Marketing Department (seeabove).


Recommended