Date post: | 22-Jan-2018 |
Category: |
Education |
Upload: | yvonne-chin |
View: | 1,141 times |
Download: | 0 times |
SCHOOL OF ARCHITECTURE, BUILDING AND DESIGN
BUILDING SERVICES (BLD 61403)
PROJECT 2 – CASE STUDY AND DOCUMENTATION OF BUILDING
SERVICES SYSTEMS
KUALA LUMPUR PERFORMANCE ART CENTRE
JASON LIM CHEE SHEN 0316791
LEE KA HOE 0315908
LIEW HONG ZHI 0315836
NICHOLAS LEE NGANG KIM 0320504
WONG YAN CE 0320906
YVONNE CHIN YUN MIIN 0315662
AR. SATEERAH HASSAN
TABLE OF CONTENTS
ACKNOWLEDGEMENT
ABSTRACT
RESEARCH METHODOLOGY
1.0 INTRODUCTION OF KUALA LUMPUR PERFORMANCE ART CENTRE
2.0 MECHANICAL VENTILATION SYSTEM
2.1 Introduction
2.2 Literature Review
2.3 Case Study
2.4 Components of Mechanical Ventilation System
2.4.1 Supply Air Diffusers / Grille
2.4.2 Return / Exhaust Air Grille
2.4.3 Fire Exhaust Fan
2.5 Conclusion
3.0 AIR-CONDITIONING SYSTEM
3.1 Introduction
3.2 Literature Review
3.3 Case Study
3.4 Centralized Air-Conditioning System
3.4.1 Air Handling Unit (AHU)
3.4.1.1 Air Filter in Air Handling Unit (AHU)
3.4.1.2 Centrifugal Fan in Air Handling Unit (AHU)
3.4.1.3 Heating & Cooling Coils in Air Handling Unit (AHU)
3.4.2 Fan Coil Unit (FCU)
3.4.3 Ductwork
3.5 Air-cooled Chilled Water System
3.5.1 Air-cooled Chiller
3.5.2 Component of Air-cooled Chilled System
3.5.2.1 Evaporator
3.5.2.2 Compressor
3.5.2.3 Condenser
3.5.2.4 Expansion Valve
3.5.2.5 Chilled Water Pump
3.5.2.6 Piping System
3.6 Conclusion
4.0 FIRE PROTECTION SYSTEM
4.1 Introduction
4.2 Literature Review
4.3 Case Study
4.4 Active Fire Protection
4.4.1 Heat Detector
4.4.2 Smoke Detector
4.4.3 Call Point
4.4.4 Fire Alarm Bell
4.4.5 Central Command Center
4.4.6 Fire Hydrant
4.4.7 Wet Riser & Hose Reel System
4.4.8 Sprinkler System
4.4.9 Carbon Dioxide (CO2) Suppression System
4.4.10 Fire Extinguisher
4.5 Passive Fire Protection System
4.5.1 Fire Rated Door
4.5.2 Emergency Exit Signage
4.5.3 Fire Emergency Staircase
4.5.4 Separation of Fire Risk Area
4.5.5 Smoke Curtain
4.5.6 Fire Wall
4.6 Conclusion
5.0 MECHANICAL TRANSPORTATION SYSTEM
5.1 Introduction
5.2 Literature Review
5.2.1 Types of Elevators
5.3 Case Study
5.4 Drawings – Plans
5.5 Elevator Components
5.6 Function of the Elevator
5.7 Service Lifts
5.8 Geared Machine
5.9 Control System of Elevator
5.9.1 Types of Elevator Control System
5.9.2 Types of Elevator Controllers
5.9.3 Elevator Control System Sequence System
5.10 Analysis
5.11 Conclusion
6.0 REFERENCES
ACKNOWLEDGEMENT
We owe our deepest gratitude towards the staff members of the Kuala Lumpur Performance Art
Centre (KLPAC), especially Ms. Zeenee, who arranged the visitation for us out of their busy schedule, which
given us the chance to further understand the building services system of the building KLPAC while we
experienced and observed the site with our own sights, likewise, they continued giving us support in every
way even after the visitation. Next, we sincerely appreciate the humorous Mr. Selva to bring us around
and explained to us about the building services systems used in KLPAC. Furthermore, we are deeply
grateful to our tutor, Ar. Sateerah Hassan, who guided us throughout the whole assignment, leading us
and giving us advices to improve our report in order to produce an informative piece of work. Lastly, we
would like to thank everyone who was involved in this assignment so that this assigned documentation
report could be finished smoothly.
ABSTRACT
This assignment is aimed to determine the significant information in details in the building
services system of Kuala Lumpur Performance Art Centre (KLPAC). The building services systems discussed
in this research paper is divided into four parts, which are mechanical ventilation, air-conditioning system,
active and passive fire protection system, and mechanical transportation. Components of each system are
divided into different parts for further identification and analysis to ensure the building systems
installation meet the building code requirements of the Uniform Building by-Laws 1984 (UBBL) and
Malaysian Standards Requirements (MS 1525), where the documentation shows the understanding on
how each building services functions including the connections and position of different part equipment.
Besides that, it also shows the understanding and explanation of the principles and systems, as well as
space implications and regulations related to different building services.
RESEARCH METHODOLOGY
In this report, different types of research methodology were used to produce relevant information
about the building services systems used in the KLPAC. Visitation to the selected building KLPAC was made
with a group of six members, where documenting and analysis was conducted during the visitation. We
jotted down the information and recorded the explanations that were made by the supervisor, Mr. Selva,
also asking furthered questions for the report. Photos were taken as well for the documentation of the
report.
Discussions were made after the visitation where we divided our tasks among our members.
Identification of the photos taken during the visitation was made and categorized into the four parts:
mechanical ventilation, air-conditioning system, active and passive fire protection system, and mechanical
transportation. Researches were done using resources from book references and internet resources. We
also did researches using the Uniform Building by-Laws 1984 (UBBL) and Malaysian Building Requirements
(MS 1525) to identify whether the building services installation were accurate. Other than that,
discussions were performed with the tutor, Ar. Sateerah Hassan during the tutorial session, to ensure our
report was on the right track.
INTRODUCTION OF KUALA
LUMPUR PERFORMANCE ART
CENTRE
1
2
1.0 INTRODUCTION OF KUALA LUMPUR PERFORMANCE ART CENTRE
Figure 1.1 Panoramic view of KLPAC building
Source: Photo credited to KLPAC
Kuala Lumpur Performance Art Centre (KLPAC), is a place that cultivates the love for various types
of art and cultural attributes among the people, spreading their passion for performing arts to the
younger generations along the way as well. The founders of this community were two unique
individuals known as Faridah Merican and Joe Hasham, who both created history in 1995 by owning
and operating a private theatre in Malaysia below Dataran Merdeka, called The Actors Studio
located at Plaza Putra. Unfortunately, due to a tragic event of flooding back in 2003, the
underground complex of the studio was destroyed entirely, nevertheless, KLPAC was born. The
Actors Studio, YTL Corporation and Yayasan Budi Penyayang, have partnered-up together to form
Malaysia’s first fully-integrated art center, a non-profit organization where it was officially opened
in May 2005.
KLPAC is always full of life, where there are many performances scheduled throughout the years,
mostly self-directed and self-organized events. The KLPAC building was designed with numerous
spaces, like studios, theatres, an academy that carries out seminars and workshops, cafes,
restaurants, and also a small performing arts library.
3
Figure 1.2 Programs organized by KLPAC for the younger generations
Source: http://www.klpac.org/about-klpac/our-services/
Numerous programs were organized for the young ones, so that they could develop their interaction
skills with each other, self-expression and self-discovery of their artistic talents. Teenagers were
warmly welcomed to participate in these programs too. Without a doubt, KLPAC has not hesitated
to keep the cultural life in Malaysia from growing. It is one of the iconic and historical landmark,
along with award-winning architectural design in the country. Most importantly, it became a home,
for both the local and foreign art community.
Figure 1.3 Timeline of KLPAC
4
MECHANICAL VENTILATION
SYSTEM
2
5
2.0 MECHANICAL VENTILATION SYSTEM
2.1 Introduction
Mechanical ventilation system is a process whereby it exchanges air inside an enclosed space.
The indoor air is withdrawn and replaced by fresh air continuously which is supplied by clean
external sources. By comparing this to the natural ventilation, it is relatively easier to control
or adjust. The main objective of installing this system is to maintain thermal comfort and
reaching a more satisfied air quality. Throughout the process of altering the properties of air,
by controlling the level of temperature and humidity into a standardized condition inside an
air conditioned space in order to provide a comfortable space. Fans, filters, blowers and ducts
are the components that are used for transporting and removing air from a space. All sort of
these can be found in kitchen, bathroom or working room which required exhaust fan.
In this chapter, mechanical ventilation system in the KLPAC building is documented and
recorded along with researches and analysis. The objective of this chapter is to show the
understanding of mechanical ventilation system used in the building to regulate fresh air and
maintain thermal comfort in the indoor spaces. The findings and analysis are to conclude
whether the mechanical ventilation system of the building meets the requirement of the
building by law.
6
2.2 Literature Review
Ventilation is the process which is required to exchange the stale air with fresh air from
external continuously within an enclosed space in order to maintain a better indoor air quality
inside a building. It can be achieved by the mechanical ventilation so that fresh air is well
ventilated inside the building while stale air can be withdrawn. The example of stale air are
indoor pollutants, carbon dioxide, moisture, odor, and airborne chemical. It is also helping in
circulating the air around and throughout the house. Moreover, it is easier to controlled due
to the level of comfortable can be adjust into certain level of satisfaction through filtration,
dehumidification and also conditioning of incoming outdoor air. It is signification to install a
proper mechanical ventilation as:
(I) It preserves oxygen (O2) content while removing Carbon Dioxide (CO2)
(II) It reduces excess condensation.
(III) It avoids from heating concentration from machinery, lighting and people.
(IV) Dispersal of concentrations of bacteria.
(V) Providing consistent freshness
(VI) Dilute and remove contaminants such as smoke, dust, gases and body odors.
(VII) A good alternative in case of unreliable natural ventilation system.
There are a few types of ventilation system that would be found such as supply ventilation
system, exhaust ventilation system, and also the balanced ventilation system. All of these
system achieve with spot ventilation which required the use of localized exhaust fans. However,
it is mainly suggested to install in a more enclosed area such as kitchen and bathroom. Spot
ventilation fans work as to reduce concentrations of pollutants in a living space. In addition,
the exhaust fans should be placed nearer to the sources of moisture or pollutants.
7
2.3 CASE STUDY
Regarding to the analysis on KLPAC, several components had been found for building up the
system. Supply Air Diffusers, Return Air Grille, and Fire Exhaust Fan. The supply and exhaust
grilles behind the celling are used as the method for cooling down the temperature within the
building as to achieve thermal comfort since no much passive design found for natural
ventilation. The low air quality within the building due to not so much opening for passive
ventilation had led to the dependence on mechanical ventilation. The whole system is being
well planned to adjust the indoor temperature. However, this situation has brought to a higher
maintenance cost for the building due to it tropical climatic issues.
8
2.4 Components of Mechanical Ventilation System
2.4.1 Supply Air Diffuser/Grille
Figure 2.1 Vertical supply Air Diffuser located in the Main Foyer of KLPAC
Figure 2.2 Section Drawing of the vertical Supply Air Diffuser which located in the Main Foyer of
KLPAC
At least 2-3 connected vertical supply air diffuser had been found at the main lobby.
Different type of air diffuser can be found in a range from cost efficient type to complex
and efficient air distributors regarding to the requirements. It is a contemporary design
comparing to the typical supply air diffuser while still work as its origin function. They
9
are located at the edge of ductwork where the air can pass through it to the interior part
of the building. The system does not require any power generation and it somehow
created low-velocity air movement in occupied rooms with just a little amount of noise.
The air within the building is well regulated even though then there is no much natural
ventilation across the building. Air diffusers found were assigned to different spaces
according to the requirements. The one installed at the main lobby are more abstract
are installed 6meters above the lobby and all of them consists of openings to reduce the
plum effect, allowing air entering to distribute through eventually. It enhances the
airflow and help to achieve thermal comfort.
UBBL Section 41- Mechanical Ventilation & Air-Conditioning
Windows and opening allowing uninterrupted air passage is not necessary if the rooms
are equipped with mechanical ventilation or air-conditional.
Figure 2.3 Different shape of Air Diffuser Concealed by the ceiling
According to the analysis, there is either circular or rectangular air diffusers and is
concealed by the ceilings. The air supply is so well-distributed throughout the entire
building due to the well-planned location of these air diffusers.
10
Figure 2.4 Plan Drawing of how Air Diffuser are connected through ductwork
Figure 2.5 Details sectional drawing of the supply air grille behind the seat which is located at the
main performance stage
11
Figure 2.6 Detailed Plan Drawing for Supply Air Grille Location
At the performing stage, the supply air grilles were installed behinds the seat which allow
air distributed equally within the space. Same theory of no power generation needed as
the result of low air velocity air movement created for the enclosed space.
2.4.2 Return/Exhaust Air Grille
Figure 2.7 Return Air Griller located at the Ground Floor Corridor and the celling of the toilet
The function of the installation of exhaust air griller is to expel the foul air which is inside
the building. It helps to carry the air back to the designated AHU rooms. The duct behinds
often being covered up by a series of grillwork in order to avoid obstacles entering or
damaging the system. In addition, filters are included into the installation to trap
12
pollutants and allow better airflow accessing the building. It can require the maintenance
cost by reduce the frequent of components break down.
Moreover, it is also used like a pump while installed all over the warm spaces which
contain equipment that giving heat towards the spaces. For example, the fire pump
room and the lift control room. The air grilles or fan placed underneath the timer to
collect and suck out the warm air in between hours to prevent overheating.
Figure 2.8 Plan drawing and Sectional drawing of exhaust air in the toilet beside the main stage
Figure 2.9 Plan drawing of Exhaust Air Grille Used in the Public Toilet of KLPAC
13
Figure 2.10 Exhaust fan at the lift control room
According to MS 1525 code 8.4.5, Mechanical ventilation control
‘Each mechanical ventilation system (supply and/or exhaust) should be equipped with
a readily accessible switch or other means for shut-down or volume reduction when
ventilation is not required. Examples of such devices would include timer switch
control, thermostat control, duty cycle programming and CO/CO2 sensor control.’
14
Figure 2.11 Detailed drawing of one part of Exhaust Ventilation System in KLPAC
Figure 2.12 Sectional drawing for toilet Exhaust Dust of KLPAC and Smoke Extract Duct of KLPAC
The air ducts are connected to a ductwork which connected to the toilet and throughout
the building. The purpose of these components is to expel the foul air and pollutants
from the interiors space while keeping the air quality fresh and acceptable, and ensure
the air circulation is well ventilating the interior.
15
2.4.3 Fire Exhaust Fan
Figure 2.13 Fire Exhaust Fan located outside of KLPAC
The fire exhaust fan acts as a component for fire hazard. The automatic fire exhaust vent
was installed to expel smoke, gas and heat automatically during fire emergency case at
the main performing stage. Those exhaust fans were connected to the smoke exhaust
ductwork in order to remove the gas from the building which can be more effective
emergency evacuation. The fundamental idea of the fire ventilation is to change the
pressure conditions prevailing when the building is in a burning condition with a
direction and opening to release the fire gases, cut down the harmful substances like the
poison gases inside the building. However, the materials of the exhaust must be fire
proof and durable to resist fire. The arranged which separated these vents from the
building is to efficiently suck out the gas and smoke from the building.
Figure 2.14 Air Riser which located outside the building of KLPAC
16
2.5 Conclusion
As the conclusion, it is necessary to install mechanical ventilation when passive design didn’t
run through the building. It is difficult to withdraw the heat from the building toward outside
naturally. So, mechanical ventilation has to be installed accordingly to improve the air
circulation which access through the entire building. Although the installation may increase
the maintenance cost and the building cost of the building, it is the only solution to cool down
the spaces within itself while helping to achieve user thermal comfort, which play as a role of
cannot be compromised. The mechanical ventilation is also used to compensate and improve
the air quality within the entirely sealed space.
Moreover, KLPAC is doing well in scheduling the ventilation system. The components are well
installed at the appropriate way and location to allow it work at its max potential.
17
AIR-CONDITIONING SYSTEM
3
18
3.0 AIR-CONDITIONING SYSTEM
3.1 Introduction
Heating, Ventilating and Air-conditioning also known as HVAC is a mechanical technology of
indoor and vehicular environmental comfort. The intention is to provide adequate thermal
comfort and acceptable indoor air quality. HVAC system design is a sub discipline of mechanical
engineering, based on the principles of thermodynamics, fluid mechanics and heat transfer to
a particular space. These systems require the use of obtained energy and involve some of the
single-purpose components. Heating are appliances which serves the purpose to generate heat
for the building. Ventilation is the process of changing or replacing the air in a space to control
the temperature or to remove any combination of gases. Air conditioning runs cooling and
humidity control for a space in a building. Among of all, air conditioning system are the most
used system in mechanical system.
Kuala Lumpur Performing Art Centre (KLPAC) is the chosen building for this mechanical system
research. KLPAC is ventilated by mechanical ventilation and air-conditioning system. These
system comforts the space by controlling the internal air temperature in terms to achieve
thermal comfort. With the support of these systems, the user in KLPAC will have a comfortable
and cooling space to stay at. The air conditioning system that used in KLPAC is unit air-
conditioning system.
19
3.2 Literature Review
Air-Conditioning System
In HVAC, the terms “AC” stands for air-conditioning. It is the process of changing the air
temperature and humidity to reach thermal comfort at the same time to enrich the indoor air
quality. Other than that, air-conditioning system is often used to control temperature,
humidity, air cleanliness and air movement as well as heat radiation to achieve thermal
comfort in the building. Basically it works by bringing the indoor heat air to the outdoor.
The four types of air-conditioning system which are:
1. Split unit air-conditioning system
2. Room air conditioner (window unit)
3. Packaged unit air-conditioning system
4. Centralized/plant air-conditioning system
Split Unit Air-Conditioning System
Split unit air-conditioning system is divided by two different parts, which are indoor and
outdoor unit. The indoor unit houses evaporator, cooling coil, blower fan and air filter. Warm
air will be carried and cooled into the filter and evaporator by blower. While the outdoor unit
is usually installed on the wall in that particular space. The unit houses compressor, condenser
and expansion valve. The heat will be removed through compressor and condenser that
covered with aluminum fins which is used to fasten the heat to be removed from the
refrigerant.
Room Air Conditioner (Window Unit)
Room window air conditioner is the simplest in terms of air-conditioning system which is used
for a space rather than a whole building. This system is usually installed at window openings
or on the wall. By this way, the air of that space will be cooled down when the fans blow over
20
the evaporator. The heat will then transfer from the inside to outside by the condenser. There
are 3 different subsystems of room air temperature are presented.
3 subsystems of the room air conditioner are:
a) Refrigeration components
b) Control system components
c) Air circulation and ventilation components
Packaged Unit Air-Conditioning System
Packaged unit air-conditioning system is also known as wall-split air conditioning system. It is
a ductless system and often found in larger scale building. The system is separated into two
parts which are condensing unit and evaporative unit. Condensing unit which is located at the
interior while evaporative unit is located at the exterior that gives heat on a cold climate by
reversing the refrigerant flow to heat the interior and transfer hear from the exterior.
Centralized/Plant Air-Conditioning System
Plant air-conditioning system is one of the most effective systems that used to allocate cool air
circulation and to make sure the appropriate air is given to the whole building. This system
contains of a central plant, water system and air system. Cool air is spread through a system
of supply and return pipes that work as bring cool airs from air conditioner to the building.
There are grill covers installed along with the supply pipes and register that usually located at
the openings on the walls, floors and ceilings. The air temperature gets warmer when the
cooled air flows back through the return pipes and register system.
The 3 subsystems of centralized air-conditioning system are:
a) Air delivery system
b) Chilled water system
c) Heat rejection system
21
3.3 Case study
KLPAC is a large multiple spaces area with different function that serves different facilities
that operates a centralized air-conditioning system for reaching a comfortable temperature
which allows users to stay longer period in the building. Because of KLPAC is serving by multiple
spaces, the system is used for vary spaces such as lobby, cafeteria, office, studios and
performing theatres. Centralized air-conditioning system using chilled water for the cooling
medium and extensive ductwork to allocate air to air-handling units (AHU) or fan-coil units
(FCU) along the building. Different sizes of a space will use different kind of system for both
AHU and FCU. AHU is a compound system that channels air through ducts which usually used
in bigger space area whilst FCU that don’t connect to duct is often used in smaller space in
KLPAC.
In the building KLPAC does consists of 5 AHUs and several FCUs. There is one AHU is fitted
at the secondary performing theatre which is a smaller space compared to where the other 4
AHU are installed. The other 4 AHU can be found at the main performing theatres because of
the function which contain bigger amount of users. Other than that, there are some FCU are
installed in the smaller spaces in the building such as offices, studios and cafeteria.
The air was cooled in the air-cooled chiller system through the refrigerant cycle before
the air was being circulated to the AHU or FCU in the building. It’s the process that
demonstrates how the refrigerant vapor is absorbed and released by the compressor to the
condenser. Air-cooled chiller system is used in the building rather than using cooling tower
because it absorbs heat from the indoor space and discards it to the surrounding.
22
3.4 Centralized air-conditioning system
Air-conditioning system have two types which are centralized and decentralized air-
conditioning system. Centralized air-conditioning system serves multiple spaces of a space in
that building from a base location. It is known as a chiller generates the chilled water at the
base location and allocate it to air-handling units (AHU) or fan-coil unit (FCU) that were often
used along the building. Besides that, the air is cooled with secondary media and is transmitted
through air distribution ducts to separate spaces. In fact, of the higher energy efficiency of
centralized air-conditioning system, these systems are often used in large buildings. The
system is mainly focus on conditioning the outdoor air and achieving the indoor temperature
needs by the allocation of conditioned air to the particular space.
Advantages and disadvantages of centralized air-conditioning system:
Advantages
Higher energy efficient
Better control of comfort levels
Greater load management potential
Disadvantages
High installment cost
Complexity maintenance
23
3.4.1 Air-handling unit (AHU)
Air-handling unit (AHU) is a central air-conditioner station which deal with the air and
provide the cooled air to the specific room of the building through air ducts. Air-handling
is the process of air that brings into the spaces with some treatments. The treatments
that were applied to the air are filtering, heating, cooling, humidifying, dehumidifying,
air distributing and recycling part of the air from the particular room. AHU has a case
which also known as a box that stored in a surround room to make sure the solidness
and no external force or pressure is applying on itself. In the building KLPAC, there is
respective switch for manual control for AHU to save energy during the time that AHU is
not needed. Other than that, air-handling unit includes a few part which are humidifier,
air filter, blower fan and cooling & heating coils.
24
Analysis:
Air-handling unit (AHU) room in the building KLPAC have reach the requirement of
Malaysian Standard Code of Practice on Energy Efficiency and Use of Renewable Energy
(MS 1525). It was located at the rear end of the building that gives control panel to the
person in charge. This allows that person to shut or reduce the energy to any space that
not required in the building.
According to MS1525, Code 8.4.2.1, control setback and shut-off states that each system
should be equipped with a readily accessible means of shutting off or reducing the
energy used during periods of non-use or alternate uses of the building spaces or zones
served by the system.
25
3.4.1.1 Air filter in air-handling unit (AHU)
Air filter is one of the important parts in AHU to maintain the blower to be clean
and avoiding dust and dirt off the heating and cooling coils. It serves good air
filtration to protect heating and cooling systems equipment without giving more
in static pressure or pressure drop not like any other air moving devices. Other
than that, it provides clean air for the building users. The supply and return
ductwork as well as filter, cooling and heating coils and the dampening system
will influence the static pressure or pressure drop of the AHU.
3.4.1.2 Centrifugal fan in air-handling unit (AHU)
Centrifugal return fan in AHU was meant to absorb air from a particular space of
the building through return air ducts. The return fan has an airfoil type of blades
that gives the most efficient effect compared to the other centrifugal blades.
Some of the air was drained out through exhaust air damper, where a minor
quantity of the air continues to pass through the AHU to mix with air drawn from
the outdoor. This procedure is called mixed air when it mixed the outdoor and
return air before extra heating and cooling.
3.4.1.3 Heating and cooling coils in air-handling unit (AHU)
The function of heating and cooling coils in AHU is to change the supply air
temperature and humidity level based on the place and application. The cooling
coil is to chilled water or refrigerant as direct expansion system and it was joined
to the chilled water pipe (CHWS) that links the chiller plant through a blue pipe
to remove heat and cools down the air. On the other hand, the heating coil heats
up the AHU and starts to send warm air to the separate spaces in the building.
The coil contains of copper header which supply steam to a copper tube that
goes through a continuous aluminum fin for additional heat transfer surface area.
26
3.4.2 Fan-coil unit (FCU)
Fan-coil unit is a device that contains a fan, heating and cooling coil that controls the
temperature in the particular space inside a building. It is installed and operated
manually most of the time. FCU is quite similar like that AHU where it can be served for
many spaces in a building. FCU is often found in residential, commercial and industrial
buildings which doesn’t connect to any ductwork and it serves to recycle the air at the
same time. In the building KLPAC, FCUs can be found in studios, cafeteria and offices.
Analysis:
Control panels can be found around the space where FCU were installed to reduce the
energy during the time where the space is not used. The air conditioning and mechanical
ventilation system in KLPAC was installed to reach the requirement stated by Malaysian
Standard Code of Practice on Energy Efficiency and Use of Renewable Energy (MS1525).
Whereby according to MS1525, Code 8.4.4.1, Off-hour control states that ACMV system
should be equipped with automatic controls capable of accomplishing a reduction of
energy use for example through equipment shutdown during periods of non-use or
alternative use of the spaces served.
27
3.4.3 Ductwork
In air-conditioning system, ductwork is typically connected to the AHU. Air duct system
is required to bring the warm or cold air of the particular space of the building back to
the AHU through the return air ducts. It has to be cooled or heated in terms to transfer
the air through the spaces in the most effective ways. Moreover, it requires system of
supply ducts to bring the cooled or heated air back to the specific space in the building.
These return and supply ducts are advisable for appropriate conditioning occupied space.
Analysis:
The ducting system in the building KLPAC were fully insulated and installed to prevent
any loss of energy that meets the requirement of Malaysian Standard Code of Practice
on Energy Efficiency and Use of Renewable Energy (MS1525).
According to MS1525, Code 8.6, Air handling duct system insulation states that all ducts,
plenums and enclosures installed in or on buildings should be adequately insulated to
prevent excessive energy loses. Additional insulation with vapor barriers may be requires
to prevent condensation under some conditions.
Single Duct
28
3.5 Air-cooled chilled water system
3.5.1 Air-cooled chiller
Air-cooled chiller is a refrigerant system which removes heat from water through a
vapor-compression or absorption refrigeration cycle. This system contains an evaporator,
condenser, compressor and an expansion valve which are assembled in a mechanical
framework known as chiller package. The piping systems that connected to the chiller
package are enclosed to the unit to serve a compact central air conditioning plant. With
this system, the surrounding of the air will create a process of evaporation and
condensation. This system is often used for larger scale building because of its capability
of serving more energy efficient.
KLPAC has 2 air-cooled chillers because of the requirement needed to provide cooling
more than a space. Both of them were installed at the rear of the building to avoid any
noise pollution that might disturb the users. The chillers are connected to the AHU to
circulate the chilled water and it is manually adjusted by control panels. Only one of the
AHU used the most in order to achieve the purpose of less energy consumption. Both of
29
the AHUs will be used whenever there is a need for high cooling load. The process begins
with the evaporator tube is installed to allow the liquid refrigerant flows. Heat will be
absorbed and evaporates from the chilled water and mixes through bundle. Compressor
will release the refrigerant vapor from the evaporator before pumping it to the
condenser with high pressure and temperature. The hot gases will transform into liquid
in the air-cooled condenser coil when it gives up heat to cooler outdoor air being drawn
across the condenser coil by the condenser fans. The pressure and temperature of the
liquid refrigerant will be reduced when entering the evaporator after it goes through the
expansion device. The refrigerant will route back to the chilled water coil and the process
is repeated throughout the time.
Analysis:
The centralized chilled water air conditioning system in the building that reach the
requirement by Malaysian Standard Code of Practice on Energy Efficiency and Use of
Renewable Energy (MS1525) by installing two chillers at the rear of KLPAC. One is used
during the daytime operating hours to reduce energy consumption whilst the other one
is installed to avoid any emergency like breakdown or maintenance. Both of the chillers
will be function when there is a need for high cooling load.
According to MS1525, Code 8 (2.2) under System and Equipment Sizing states that
minimum of 2 chiller or a single multi-compressor chiller should be provided to meet the
required load if the design load where the chillers are used exceeded 1000kWr (285 tons).
30
3.5.2 Components of Air-cooled chilled system
3.5.2.1 Evaporator
Evaporator is mainly used in changing the state from liquid to vapor and
removing the water or any other liquids from the combination while absorbing
the heat in the process.
3.5.2.2 Compressor
The refrigerant liquid is being squeezed in a compressor. Its function is to
stabilize the molecules of the liquid and the sizes of the gases will be decreased.
This makes the energy and the temperature increased at the same time. It was
often motivated by a motor or belt through pulley arrangement.
3.5.2.3 Condenser
Condenser is known as a ‘heater’ in this system which always in a high
temperature and pressure state. Its purpose is to transform the refrigerant gas
that discharge by the compressor back into liquid form by cooling down the
temperature of the molecules.
3.5.2.4 Expansion valve
Expansion valve is used to remove high pressure of the liquid refrigerant. The
purpose is to make sure the change of state from liquid to vapor is capable to
happen in the evaporator. It is also able to control the amount of refrigerant
flow into the evaporator. Heat should be evaded from overheating at the outlet
of the evaporator.
3.5.2.5 Chilled water pump
Chilled water was pumped to every air-handling unit by the pump machine and
return the warm water to the chiller.
31
3.5.2.6 Piping system
Pipes from air-cooled chiller are actually connected to the cooling coil in air-
handling unit which is located in a particular room. Two different pipes were
divided from the system which are the chiller water supply pipe (CHWS) and
chiller water return pipe (CHWR). Chiller water supply is to transfer the cool
water from the chiller to the AHU and the air will be cooled at the same time
when it passes through those pipes. While chiller water return pipe is to return
the warm water from AHU to the chiller.
Analysis:
The piping system of centralized chilled water air conditioning system in KLPAC met the
requirement of Malaysian Standard Code of Practice on Energy Efficiency and Use of
Renewable Energy (MS1525) by installing the piping insulation with extra barriers to the
system without happening any energy losses of the building.
According to MS1525, Code 8.5 Piping insulation states that “all piping installed to serve
building and within building should be adequately insulated to prevent excessive energy
losses. Additional insulation with barriers may be required to prevent condensation
under some conditions.”
32
3.6 Conclusion
To conclude, the air-conditioning system in KLPAC is well equipped and installed while meeting
the requirements and regulations of Uniform Building by Law. Even though KLPAC is not a large
commercial center, the function of its space serves it to contain a large amount of users. In
addition, the function of centralized air-conditioning system is to provide a comfortable
surrounding for the users. KLPAC did placed wisely the location of centralized air-condition at
the rear of the building to reduce the noise affection to the building to let those users to have
a quiet and relaxed environment to stay.
33
FIRE PROTECTION SYSTEM
4
34
4.0 FIRE PROTECTION SYSTEM
4.1 Introduction
The purpose of fire protection system is to increase the safety of emergency
responders and building occupants by providing some useful and important
information about the firefighters normally interact with the building features and fire
protection systems during fire disaster and similar emergencies. By better
understanding the needs of the fire services, designers and code officials can work
together to streamline fire service emergency operations within the built environment.
Designers in this manual can include architects, engineers, planners, and design
technicians. Code officials can include fire marshals, fire inspectors, fire prevention
officers, building inspectors, and plan reviewers. Other stakeholders include building
owners and developers, security professionals, and construction professionals. The
faster the fire service can respond, enter, locate the emergency incident, and safely
operate in or near a building, the sooner they can usually resolve the incident in a safe
manner. This, in turn, will likely increase the safety of building occupants (workers,
residents, and visitors), reduce property damage, and limit related indirect losses.
Therefore, both building occupants as well as fire service employees will realize the
benefits of the fire protection system.
35
4.2 Literature Review
In the event of a fire in a building, the safety of the occupant and first responders and
the protection of property is accomplished through a combination of how well the
active and passive fire protection works. Firstly, a good active fire protection systems
are designed to come into play only when a fire is present and require activation
through a combination of sensors or mechanical means. The active fire protection
systems designed in KLPAC consisted of fire alarms, sprinklers, water supplies and
some smoke management systems. On the other hand, a passive fire protection
system is one which is an integral part of the building layout and materials of the
construction, such as partitions to confine the fire, a stairway to assist rapid evacuation,
or sprayed fire-resistive material to increase the fire resistance of a load-bearing steel
structure. When the active and passive fire protection systems work together to
control the spread of the fire and maintain the integrity of the structure; however, the
fire department is always relied upon to fully extinguish the fire and rescue occupants
who may be immobilized.
36
4.3 Case Study – Diagram
ACTIVE FIRE PROTECTION
SYSTEM
FIRE DETECTION
PUMP ROOM
WET RISER
SPRINKLER HOSE REEL SYSTEM
SMOKE/ HEAT
DETECTIONS
CALL POINT FIRE
EXTINGUISHER
R
ALARM BELL
CENTRAL COMMAND CENTER
ACTIVATE FIRE MECHANICAL SYSTEM
37
4.4 Active Fire Protection
4.4.1 Heat Detector
Figure 4.1 Heat detector and it location at Ground Floor
UBBL -SECTION 225
Every building shall be provided with means of detecting and extinguisher fire
and alarms together with illuminated exit signs in accordance with the
requirements as specified in Tenth Schedule to these by-Laws.
Fire detectors are recognized as the most common method of fire protection for safety
These fire detectors are located on the ceiling of every floor. The purpose is to detect
and respond to the presence of fire.
38
4.4.2 Smoke Detector
Figure 4.2 Smoke detector and its location at Ground Floor
UBBL-SECTION 225
Every building shall be provided with means of detecting and extinguisher fire
and alarms together with illuminated exit signs in accordance with the
requirements as specified in the Tenth Schedule to these By-Laws.
Smoke detector located on the ceiling of every floor, it’s will detect most fires more
rapidly than heat detectors. They detect fire smoke very well and detect emit a loud and
distinctive sound to alert occupants would and provide critical seconds to implement
actions to save life and property.
39
4.4.3 Call Point
Figure 4.3 Call point found below a fire alarm
The manual alarm call points also named as manual fire alarm activation are designed
for the purpose of raising an alarm manually once verification of a fire or emergency
condition exists, by operating the push button or break glass the alarm signal can be
raised.
40
4.4.4 Alarm Bell
Figure 4.4 Fire alarm and its location at Ground Floor
UBBL - SECTION 237
Alarm bell must provide a minimum sound level of 65db (A) or +5db (A) above
any background noises, which is likely to persist for more than 30 seconds.
The fire alarm bell remains the most commonly used alarm for fire evacuation systems.
system sensor alarm bells deliver high sound pressure output for fire signaling needs
while matched with extremely low power consumption.
41
4.4.5 Central Command Center
Figure 4.5 Central Command Center and LED Fire Indicator
Figure 4.6 Location of Central Command Center
UBBL - SECTION 238
Every large premises or building exceeding 30.5 meters in height shall be
provided with a command and control center located on the designated floor
and shall contain a panel to monitor the public address, fire brigade
communication, sprinkler, water flow detectors fire detection and alarm
systems and a direct telephone connection to the appropriate fire-station by-
passing the switch board.
42
4.4.6 Fire Hydrant
Figure 4.7 Fire Hydrant Around KLPAC
UBBL - SECTION 225 (2)
Every building shall be served by at least one fire hydrant located not more than
91.5 meters from the nearest point of fire brigade access.
UBBL - SECTION 225 (3)
Depending on the site and location of the building and the provision of access
for fire appliances, additional fire hydrant shall be provided as may be required
by the Fire Authority.
Fire hydrant system is a safety measure of emergency equipment required in some
buildings that comprises a series of components that when assembled together provide
a source of water to assist fire authorities in a fire.
43
4.4.7 Wet Riser & Hose Reel System
Figure 4.8 Hose Reel at Ground Floor
UBBL – SECTION 231
Wet rising system shall be provided in every building in which the top most floor
is more than 30.5 meters above the fire appliance access level.
A hose connection shall be provided in each firefighting access lobby.
Hose reel system is the active fire protection devices used to extinguish and
control fire while in emergency situations. When the hose reel is brought into use
the pressure in the pipe immediately downstream of the pump check valves will
drop below the field adjusted pressure setting of the pressure switch thereby
triggering the pump to comes into operation automatically to feed a steady
supply of water to discharge through the hose.
44
Figure 4.9 Layout Drawing for Hose Reel System
45
4.4.8 Sprinklers
UBBL – SECTION 228
Sprinkler valves shall be located in a safe and enclosed position on the exterior
wall and shall be readily accessible to the Fire Authority.
All sprinkler systems shall be electricity connected to the nearest fire station to
provide immediate and automatic relay of the alarm when activated
Fire sprinkler systems provide early fire control or extinguishment. If properly designed,
approved, installed, and maintained, sprinkler systems help to mitigate the fire hazard
to both occupants and firefighters. The importance and effectiveness of sprinkler
systems has been demonstrated for many years. The sprinkler piping arrangement will
determine how specific a fire alarm annunciator is able to indicate water flow signals.
46
Figure 4.9 Layout Drawing for the Sprinkler System and Improvised Sprinkler System
47
4.4.9 Carbon Dioxide (CO2) Suppression System
Figure 4.10 Carbon Dioxide (CO2) Suppression System
Carbon dioxide (CO2) is a colorless, odorless, and chemically inert gas that is both readily
available and electrically non-conductive. It extinguishes fire primarily by lowering the
level of oxygen that supports combustion in a protected area. This mechanism of fire
suppression makes CO2 suppression systems highly effective, requiring minimal clean-
up, but should be used in normally unoccupied hazard locations or otherwise avoided by
personnel when discharged. CO2 suppression systems may utilize the gas through a total
flooding approach but carbon dioxide is also the only gaseous agent that may be utilized
through local application. Carbon dioxide may be stored in either high pressure spun
steel cylinders (HPCO2 suppression systems) or low pressure light wall refrigerated tanks
(LPCO2 suppression systems).
48
4.4.10 Fire Extinguisher
Figure 4.11 Dry Powder Fire Extinguisher
UBBL – SECTION 227
Portable extinguisher shall be provided in accordance with the relevant codes of practice
and shall be sired in prominent positions on exits routes to be visible from all directions
and similar extinguisher in a building shall be of the same method of operation.
Fire extinguisher, or extinguisher, is an active fire protection device used to extinguish or
control small fires, often in emergency situations. It is not intended for use on an out-of-
control fire, such as one which has reached the ceiling and endangers the user. Fire
extinguisher can be divided into 5 major class, each of them performs best in a specific
scenario to counter the fire emergency types.
KLPAC owns only the ‘Dry Powder’ extinguisher which are placed within the building area as
it fits with building activities.
49
Figure 4.12 Diagram of various classes of fire extinguishers
50
4.5 Passive Fire Protection System
Passive Fire Protection (PFP) is an integral component of the three components of structural fire
protection and fire safety in a building. PFP attempts to contain fires or slow the spread, through
use of fire-resistant walls, floors, and doors (amongst other examples). PFP systems must
comply with the associated Listing and approval use and compliance in order to provide the
effectiveness expected by building codes.
Figure 4.13 The schematic drawing above shows a diagrammatic flow chart of KLPAC’s passive fire protection system
PASSIVE FIRE PROTECTION SYSTEM
COMPARTMENT MEANS OF ESCAPE
FIRE WALL
EMERGENCY EXIT SIGNAGE
FIRE RATED DOOR
FIRE EMERGENCY
STAIRCASE
SMOKE CURTAIN
SEPERATION OF FIRE RISK
AREA
51
4.5.1 Fire Rated Door
Figure 4.14 Fire Rated Door
Fire rated door is an essential important fire-proofing component that need to be
concerns about when designing a building as this was a pathway to ensure the users
safety. By having the same usage as the fire wall does, fire door serves as critical
compartmentalization of building entrances or exits in order to prevent fire and smoke
spreading. There are many kinds of fire rated door staircase design and KLPAC building
has applied the 1.5-hours fire rated door were installed at the egress of fire staircase each
floor as well as office entrances.
52
UBBL – SECTION 162 (1)
Fire doors of the appropriate FRP shall be provided.
Openings in compartment walls and separating walls shall be protected by a fire
door having FRP in accordance with the requirements for that wall specified in
the Ninth Schedule to these By-Laws.
UBBL – SECTION 164 (1)
All fire doors shall be fitted with automatic door closed of the hydraulically spring
operated type in the case of swing doors and of wire rope and weight type in the
case of sliding door.
The fire door located at the side of the building, it was located there as it has been
considerate in terms of circulations that allow users of building to walk easier however
the escape routes will be protected by the fire rated door during fire event occurred in
the building. Unfortunately, the door that was made of timber and aluminum is
combustible and it will cause door failures after a long period.
The automatic door closer hinges and devices were installed to fulfil the requirements of
By-Laws Section 164(1). The main reasons for installing the device on the door are to
ensure the door was always enclosed.
53
4.5.2 Emergency Exit Signage
Figure 4.16 Emergency Exit Signage
Exit signs that are above the fire rated door are installed with neon green words on was
to indicate the escape way when fire events occurred in the building. There will be
emergency light lighten up when the main electricity supply has been cut off. Exit signage
plays important role in terms of fire escaping as when fire events occurred, building will
be full with smokes and hardly visible, also in the worst condition the electricity supply
will be cut off and blackout occurred will cause the user panic and stuck in the building.
With the design of font and mechanism applied into the signage has greatly help to reduce
the panic of the users. The letters and colors used for the signage can effectively attract
the attentions of the users when the light is out. In Malaysia, exit signage is written in
Malay and the word “KELUAR” means exit. Based on the photo, the exit sign was located
above the fire doors, which it was mainly to direct the users and occupant of the building
towards the fire escape staircases. According to UBBL, the exit signs are not able to be
block by other stuff or decorations, it should be located in specific location. It is a lone-
standing sign.
54
UBBL – SECTION 172
Story exits and access to such exits shall be marked by readily visible signs and
shall not be obscured by any decorations, furnishings or other equipment
A sign reading “KELUAR” with an arrow indicating the direction shall be placed in every
location where the direction of travel to reach the nearest exit is not immediately
apparent.
Every exit sign shall have the work “KELUAR” in plainly legible letters not less than 150mm
high with the principal strokes of the letters not less than 18mm wide. The lettering shall
be in red against a black background.
All exist signs shall be illuminated continuously during periods of occupancy.
55
4.5.3 Fire Emergency Staircase
Figure 4.17 Fire Emergency Staircase
Fire escape staircase was important as it was a pathway that leads the user or the
occupant of the building to a safer area or an assembly point whenever there was an
emergency event happens in the building. According to law, fire escape staircase that
leads to assembly point occupants of the building and keep them away from danger as
much as possible when danger or emergency occurs.
UBBL – SECTION 168
The required width of a staircase shall be maintained throughout its length
including at landings.
Except as provided for in by law 194 every upper floor shall have means of access
via at least two separate staircases.
56
The required width of staircase shall be clear width between walls but handrails
may be permitted to encroach on this width to maximum of 7.5 millimeters.
Tiles on staircases riser maximum 180 mm and thread minimum 255mm.
UBBL – SECTION 169
No exit route may reduce in width along its path of travel from story exit to the final exit.
UBBL – SECTION 178
In buildings classified as institutional or places of assembly, exits to a streets or large open
space, together with staircases, corridors and passages leading to such exits shall be
located, separated or protected as to avoid any undue danger to the occupants of the
place.
57
4.5.4 Separation of Fire Risk Area
UBBL – SECTION 139
The following area uses shall be separated from the other areas of the occupancy in which
they are located by fire resisting construction of elements of structure of a FRP to be
determined by local authority based on the degree of hazard:
Boiler rooms and associated duels storage area
Laundries
Repairs shops involving hazardous processes and materials
Storage area of materials in quantities deemed hazardous
Liquefied petroleum gas storage areas
Linen rooms
Transformer rooms and substations
Flammable liquid stores
According the laws, all fire risk area should be allocated evenly and separate ly when
architect design and doing spatial planning for the building to reduce the fire to expand
from one point to another point rapidly. From our site visit in KLPAC, spatial planning that
was done there was nicely done because according to the ground floor plan, electrical
room, mechanical room studios and stages are evenly distributed in ground floor,
basement.
With this location distribution, the risk of fire area is greatly reduced as they are far apart
from each other’s which buys more time for the user and occupants to escape when fire
occurred, it also allows to reduce damage that will be happen on the building too.
58
4.5.5 Smoke Curtains
Figure 4.18 Smoke curtain found in Gen Set Room
UBBL – SECTION 161 (1)
Any fire stop required by the provision of this part shall be so formed and positioned as
to prevent or retard the passage of flame.
Smoke curtain is a fabric that made of incombustible material which is to prevent fire
and smoke spreading rapidly. Smoke curtains were found in KLPAC building and they are
installed on top of the entrance and windows of the mechanical room and electrical
systems rooms such as transformer room as these are the room for emergency purpose
and to detect and to ensure the room are free of fire and smoke. During the event of fire,
smoke curtain will be automatically dropped down to form a barrier to prevent the fire
and smoke to spread further easily.
59
4.5.6 Fire Wall
Figure 4.20 Firewall found in KLPAC office
Generally, fire wall is a fire resistant barrier that was being designed to prevent the spread
of fire in a period of time. They are an assembly of materials that not only act as a wall
that separate spaces but also separate those high fire risk areas such as transformer room,
electrical room and mechanical room. It was being designed to provide more time to
escape when fire occurred to the building. It buys sufficient times for the occupant and
the users to escape.
After investigating KLPAC, the architect has fully fulfilled the requirement that was being
set in UBBL, the design and the placement of the fire wall are well considerate and it was
able to ensure the safety of the occupants by being harmed from the fire.
60
UBBL – SECTION 138 (C)
Any wall or floor separating part of a building from any other part of the same
building, which is used or intended to be used mainly for a purpose failing within
a different purpose group as, set out in the Fifth Schedule to these by laws.
UBBL – SECTION 148 (6)
Any compartment walls or compartment floor which is required by these By-Laws
to have FRP of one hour or more shall be constructed wholly of non-combustible
materials and apart from any ceiling, the required FRP of wall or floor shall be
obtained without assistance from any noncombustible materials.
61
4.6 Conclusion
Through investigation, it is safe to say that the Kuala Lumpur Performing Art Center (KLPAC) has
an effective and efficient fire protection system. The building obeys the Universal Building By-
Law with strict detail for maximum protection, and it is built and installed with minimum
occupant disturbances. KLPAC also follows and conforms any updates by the BOMBA for
additional state-of-the-art protection system for time to come. In conclusion, KLPAC is an
outstanding example of fire protection case studied for students to get exposed and understand
without going to hard-to-reach locations.
62
MECHANICAL
TRANSPORTATION SYSTEM
5
63
5.0 MECHANICAL TRANSPORTATION SYSTEM
5.1 Introduction
Mechanical transportation has become the
necessity in the most of the high rise flats,
apartments and commercial buildings in
Malaysia and even the world. Vertical
transportation is a phrase used to describe
the various means of travelling between
floors in a building. All buildings with more
than one storey of course have at least one
set of stairs and the provision of stairs is a
very important consideration when
designing buildings in order to ensure all the
occupants of the building can escape safely
in the event of a fire.
In buildings with more than four floors, a lift is desirable as there is a limit to how far people are
willing to walk upstairs. The best lift systems can help transform a building’s functionality,
sustainability and occupant well-being. In addition to this, stairs are unsuitable for infirm and
mobility impaired persons so buildings with only two floors are sometimes fitted with a lift.
This research discusses about the mechanical transportation system in KLPAC and this case
study is compiled with details on mechanical transportation at KLPAC, referencing conformance
to UBBL Mechanical Transportation System Requirements. KLPAC is a low rise building with four
floors which is accessible by stairs and elevators. According to my research, there are three
elevators and no escalators in the building, which are for Passengers, Services and Loading Bay
Elevator.
64
In KLPAC, Dover Brand elevators were used. Dover Elevator (Malaysia) Sdn Bhd has the aim of
supplying, installing and maintaining high quality Dover Brand of elevators to ever increasing
demand of high rise buildings for various usages.
Dover Elevators (M) Sdn Bhd was set up in 1994 under the name of Internet Engineering Sdn
Bhd to be the sole distributor of Dover brand of elevators and escalators in Malaysia.
It has been very flexible and forward looking to allow the highly sophisticated controller and
traction machine of proprietary designs, to be manufactured in Malaysia, South Korea and China
to make the products more cost effective in order to remain competitive in the market.
65
5.2 Literature Review
Vertical transportation in buildings is a key issue for building users and tenants, breakdowns or
long waiting times for a lift lead to frustration and dissatisfaction with both the lift and the
building. Early electric lifts were controlled by an attendant and only featured controls to go up
and go down. Doors had to be opened manually as well. Nowadays, lift attendants are reserved
for only the most exclusive establishments, as the automatic passenger operated lift has all but
taken over.
An elevator or lift is a type of vertical transport equipment that efficiently moves people or
goods between floors, levels or decks of a building, vessel or other structures. Elevators are
generally powered by electric motors that either drive traction cables or counterweight systems
like a hoist, or pump hydraulic fluid to raise a cylindrical piston like a jack.
Lift is a lifting machine or appliance having a car or platform the direction of movement of which
is restricted by a guide or guides but service lift means a lift having a rated load of not more
than 250 kg and a car in which the area of the floor is not more than 1 m2 and the height of
which is not more than 1.2m.
The technology used in new installations depends on a variety of factors. Hydraulic lifts are
cheaper, but installing cylinders greater than a certain length becomes impractical for very high
lift hoist-ways. For buildings of much over seven stories, traction lifts must be employed instead.
Hydraulic lifts are usually slower than traction lifts. Elevator doors protect riders from falling
into the shaft. The most common configuration is to have two panels that meet in the middle,
and slide open laterally.
Openings shall be made at the top of a well, with a minimum area of 1% of the area of the
horizontal cross section of the well, ventilating to the open air either directly or via ducting or
the machine or pulley room, provided that in no case the ventilation openings shall be less than
0.15 m2 net free area.
66
5.2.1 Types of Elevators
Elevators will be classified according to hoist mechanism to 4 main types as follows:
i. Hydraulic Elevators
ii. Traction Elevators
iii. Climbing Elevators
iv. Pneumatic Elevators
i. Hydraulic Elevators
Hydraulic elevators are supported by a piston at the bottom of the elevator that
pushes the elevator up. They are used for low-rise applications of 2-8 stories and travel
at a maximum speed of 200 feet per minute. The machine room for hydraulic elevators
is located at the lowest level adjacent to the elevator shaft.
Hydraulic Elevators Types
Hydraulic elevators have many two main types as follows:
67
a) Holed (Conventional) Hydraulic Elevators
They have a sheave that extends below the floor of the elevator pit, which
accepts the retracting piston as the elevator descends. Some configurations
have a telescoping piston that collapses and requires a shallower hole below
the pit. Max travel distance is approximately 60 feet.
b) Hole-less Hydraulic Elevators
They have a piston on either side of the cab. It can be divided to 3 different
types as follows:
i. Telescopic Hydraulic Elevators:
In this configuration, the telescoping pistons are fixed at the base of
the pit and do not require a sheave or hole below the pit and has 2 or
3 pieces of telescoping pistons. Telescoping pistons allow up to 50 feet
of travel distance.
ii. Non-telescoping (single stage) Hydraulic Elevators:
It has one piston and only allows about 20 feet of travel distance.
iii. Roped Hydraulic Elevators:
They use a combination of ropes and a piston to move the elevator.
Maximum travel distance is about 60 feet.
68
Hydraulic Elevators Components
The hydraulic elevators will differ from the traction elevator in the following main
components:
i. Machine/drive system.
ii. Safety system.
69
Hydraulic Power Unit
The power unit shall be generously rated and shall operate with minimum noise and
vibration. The unit shall be mounted on vibration insulators above the machine room
floor. A silencer unit shall be fitted in the hydraulic system to minimize the
transmission of pulsations from the pump to the car and the elimination of airborne
noise.
The hydraulic power unit consists of the following components:
i. The Tank.
ii. Motor/Pump.
iii. Valve.
iv. Actuator.
70
The Tank
The tank shall have sufficient capacity to provide an adequate reserve to prevent the
entrance of air or other gas into the system. A sight glass tube shall be provided for
checking the oil level and the minimum level mark shall be clearly indicated. An oil
level monitoring device shall be provided, and if operated, shall maintain a visual and
audible signal in the control panel until the fault is rectified.
So, the main function of the tank is holding the liquid used in the system. This liquid is
usually oil based because:
1. Non compressible
2. Self-lubricating
71
ii. Traction Elevators
Traction elevators are the most common type of elevators. Elevator cars are pulled up
by means of rolling steel ropes over a deeply grooved pulley, commonly called a sheave
in the industry. The weight of the car is balanced by a counterweight since 1900.
Sometimes two elevators are built so that their cars always move synchronously in
opposite directions, and are each other's counterweight. Otis has a long history of
meeting new challenges with ongoing innovation.
While there is a wide range of elevators to fit every need, they fall under three basic
types:
I. Machine room-less
II. Gearless traction
III. Geared traction
72
I. Machine Room-less Elevators
This revolutionary elevator system is based on the first major breakthrough in lifting
technology in nearly 100 years. Designed for buildings between about two and 30
stories, this system employs a smaller sheave than conventional geared and gearless
elevators. The reduced sheave size, together with a redesigned machine, allows the
machine to be mounted within the hoist-way itself—eliminating the need for a bulky
machine room on the roof. Just as unique are the flat polyurethane-coated steel belts,
an Otis invention for the Gen2™ elevator system, that replace the heavy, woven steel
cables that have been the industry standard since the 1800s. The belts make the
smaller sheave possible. They are only 0.1 inch (3 mm) thick, yet they are as strong as
woven steel cables and far more durable, flexible and space-saving.
73
II. Geared Traction Elevators
As the name implies, the electric motor in this design drives a gear-type reduction unit,
which turns the hoisting sheave. While slower than a typical gearless elevator, the gear
reduction offers the advantage of requiring a less powerful motor to turn the sheave.
These elevators typically operate at speeds from 350 to 500 feet per minute (1.7 to 2.5
meters per second) and carry loads of up to 30,000 pounds (13,600 KG). An electrically
controlled brake between the motor and the reduction unit stops the elevator, holding
the car at the desired floor level.
74
III. Gearless Traction Elevators
In 1903, Otis introduced the design that would become the standard in the elevator
industry—the gearless traction elevator. These elevators typically operate at speeds
greater than 500 feet per minute (2.54 meters per second). In a gearless traction
machine, woven steel cables called hoisting ropes are attached to the top of the
elevator car and wrapped around the drive sheave in special grooves. The other ends
of the cables are attached to a counterweight that moves up and down in the hoist
way on its own guiderails. The combined weight of the elevator car and the
counterweight presses the cables into the drive sheave grooves, providing the
necessary traction as the sheave turns. Gearless technology makes the tallest buildings
in the world possible, such as Malaysia’s Petronas Towers.
75
iii. Climbing Elevators
Component of climbing elevators
They hold their own power device on them, mostly electric or combustion engine.
Climbing elevators are often used in work and construction areas.
iv. Pneumatic Elevators
A pneumatic elevator, also called pneumatic elevator is a kind of glass tube with a
cabin inside that moves up or down to the desired floor level without showing visible
means of propulsion. It moves up and down using the force of suction. The pneumatic
lifts usually fit only one or two people and can be installed more quickly and
inexpensively than regular elevators because they don’t require a shaft or a control
room to house hydraulic machinery. They are elevators for easy installation, “which
in many cases do not require civil works”, and can be installed in two, three and four
stops.
When the piston gear depressurizes the area inside the cylinder above the vacuum
elevator cab, the cab is then lifted by higher atmospheric pressure below the cab.
76
The inside of the vacuum elevator cab always remains at the atmospheric pressure. As
air pressure is lowered above the cab, the cab is lifted.
A valve regulating inflow of air in the upper part of the shaft controls the pneumatic
depression and enables descent. When the valve lets in air (at atmospheric pressure)
into the low pressure chamber, the vacuum elevator cab will safely lower to the
desired level. This valve also controls the speed of the cab.
77
5.3 Case Study
In KLPAC, there is only one type of mechanical vertical transportation. There are a few types of
elevators that can be found, like Passenger Elevator and Loading Bay Elevator. This research
focus on the mechanical transportation system in KLPAC and also conduct with analysis and
recommendations for improvements to mechanical transportation system at KLPAC in term of
safety and control of circulation.
The types of elevator system used in KLPAC is Geared Traction Elevator.
The main components of the Geared Traction Elevators are:
1) Geared Machine
2) Wrapping for traction sheave
3) Governor
4) Door System
5) Counterweight
6) Safety Break
78
5.4 Drawings - Plans
Stairs are closely located to the elevators in case of emergency. Other than that, under
minimum standard of service, KLPAC fulfills in terms of maximum walking distance of 45m to
the elevator lobby.
79
Cross section of the haistway for the elevator in KLPAC.
80
Section schematic diagram
81
Rough elevator machine room to shaft floor plan
Front view of stretcher lift
82
5.5 Elevator components
Geared Traction Elevator detail component diagram
In KLPAC, electrical elevator is used as mechanical transportation. The type of lift is geared
traction elevator where the elevator cars computerized and controlled by control system which
is located at the roof top. The way it works Is that the control system receives signal and elevator
cars are pulled down by hoisting rope over a sheave and is powered by geared machine. This
elevator is balances by a counterweight. Other than that, an electrically controlled brake is
installed between the motor and the reduction unit stops the elevator, holding the car at the
desired floor level.
83
5.6 Function of the Elevator
The Gear Box is attached to the motor to drive the wheel and pull the rope.
This elevator typically operates at speeds from 38 to 152 meters (125-500ft) per minute and
carry loads of up to 13600 kilograms (30,000 lbs).
Geared machines use worm gears to control mechanical movement of elevator cars by “rolling”
steel hoist ropes over a drive sheave which is attached to a gearbox driven by high speed motor.
An electrically controlled brake between the motor and the reduction unit stops the elevator,
holding the car at the desired floor level.
84
5.7 Service Lift
For service lifts of a rated load of 150 kg and above, the machinery space floor area shall not be
less than 1.5 m x 1.5 m and the clear height shall not be less than 1.2 m. For service lifts of a
rated load below 150 kg, the machinery space depth shall not exceed 600 mm and the clear
height shall not be less than 800 mm.
The machinery space shall be soundly constructed, weather-proof and dry. It shall be safe for
access by maintenance personnel to all equipment. For service lifts of a rated load of 150 kg and
above, the floor of the machinery space shall be of adequate strength at every point to
withstand the load of maintenance personnel and equipment.
For service lifts of a rated load below 150 kg, either the requirements in paragraph or those
listed below shall be followed the maintenance personnel shall be able to reach every part of
the equipment inside the machinery space with his hands while standing outside the space, and
85
rigid partition or wire mesh shall be provided to prevent any object from falling down into the
lift-well from the machinery space.
For service lifts of a rated load below 150 kg, be not less than 800 mm in height and have a
width of 900 mm or the full width of the machinery space, whichever is the less. For service lifts
of a rated load of 150 kg and above, be not less than 1.0 m in height and have a width of not
less than 1.2 m, be facing the machine and its ancillary equipment to allow installation and
maintenance work.
Car operating panel, ventilation hole, key hole in the shaft
86
5.7.1 Geared Machine
Geared Machine found in Machine Room located on rooftop of KLPAC
Geared traction machine is powered by AC-DC electrical motor. It functions to turn the sheave
which then moves the lift car. Compared with gear less traction, it uses less energy to turn the
motor and help to save energy cost. This gear traction elevator is suitable for low mid-rise
buildings like KLPAC. This design utilizes a mechanical speed reduction gear set to reduce the
rpm of the drive motor (input speed) to suit the required speed of the drive sheave and elevator
(output speed). Generally, geared machines are used for speeds between 0.1 m/s and 2.5 m/s
and are suitable for loads from 5 Kg up to 50,000 Kg and above. Their sizes and shapes vary with
load, speed and manufacture but the underlying principles and components are the same.
Contemporary cheaper installations, such as those in residential buildings and low- traffic
commercial applications generally used a single or two speed AC hoist machine (abbreviation is
AC/ (speed number)). The widespread availability of cheap solid state AC drives has allowed
infinitely variable speed AC motors to be universally (for ACVV/AC-VVVF), bringing with it the
87
advantages of the older motor-generator based systems, without the penalties in terms of
efficiency and complexity.
Analysis the lift system
88
Geared Machines Components
Types of geared machine drive according to location of installation:
A- The drive machine located directly over top its hoist way or shaft is commonly referred to
as “Overhead traction” as in the below image.
Overhead Traction
B- The drive machine located at a basement is commonly referred to as “basement traction” as
in the below image.
89
Basement Traction
C- The drive machine located at the side of the hoist way is commonly referred to as an “offset
traction” as in the below image.
90
Offset Traction
Note: Basement and offset applications require additional deflector sheaves to properly lead
suspension ropes off the drive sheave and to the car top or counterweight.
91
7.9 Control system
Elevator Control System is the system responsible for coordinating all aspects of elevator
service such as travel, speed, and accelerating, decelerating, door opening speed and delay,
leveling and hall lantern signals.
Simple Elevator Control System Inputs and Outputs
92
Diagram showing how elevator system works in KLPAC.
Control System Panel found in Machine Room in KLPAC
Elevator control panel is a device that can be found at the machine room usually located at the
top. It functions as a brain to the elevator system that receives signal from user or operator and
sends out signal to different components of the elevator.
93
Overs-peed Governor
An over-speed Governor is an elevator device which act as a stop device in case the elevator
runs beyond the rated speed. This device must be installed for traction elevators.
Ventilation inside Machine Room
Vents can be found in the machine room, they serve the purpose of ventilating the interior
machine room.
94
5.9.1 Types of elevator control systems
There are 3 main types for elevator control systems as follows, single Automatic operation,
selective collective operation, and group automatic operation.
1- Single Automatic operation:
First automated system without single call button on each floor and single button for each floor
inside the car. Passenger has exclusive use of the car until rip is complete.
2- Selective collective operation:
Most common, remembers and answers calls in one direction then reverses. When trip
complete, programmed to return to a home landing.
3- Group automatic operation:
For large buildings with many elevators which are controlled with programmable
microprocessors to respond.
Note: The traffic management systems which combine visual monitoring, interactive command
control, and traffic analysis to ensure that the elevators are running properly will be discussed
in another course for planning and design of elevators traffic management systems.
5.9.2 Elevator control system components
The elevator as a control system has a number of components. These can basically be divided
into the following such as: inputs, outputs and controllers.
1- Inputs, which include sensors, buttons, key controls, and system controls.
A- Sensors
A.1 Magnetic and/or photo electric:
95
photo electric Car Position Sensor
These pick up signals regarding the location of the car. This sensor is usually placed on the car
itself and reads the position by counting the number of holes in the guide rail as they pass by in
the photo-electric sensor or in the case of the magnetic sensor, the number of magnetic pulses.
A.2 Infrared:
Infrared Sensor
This is used to detect people entering or leaving the elevator.
96
A.3 Weight sensor (Overload Device):
Weight Sensor
This is placed on the car to warn the control system if the design load is exceeded.
A.4 PVT (primary velocity transducer):
Velocity of the drive sheave is sensed with this encoder.
97
B- Buttons
B.1 Hall Buttons:
Hall Buttons
These buttons are on a button panel on the outside of the elevator shafts and are used by
potential passengers to call an elevator cab to the floor that the pressed summon button is
located on. There are two Hall buttons on each floor – one for up, another for down, except on
the top floor where there is only down and on the bottom floor where there is only up. The
controller interacts with these buttons by receiving press and release signals indicating the
requested direction and floor number. It also sends light on/off signals to indicate the status of
the buttons.
B.2 Floor Request Buttons:
Floor Request Button
98
This particular elevator controller will be controlling elevator cabs that are in a building with 6
floors. Consequently, each cab has 6 floor request buttons labeled 1 through 6 that passengers
can use to direct the elevator cabs to the floor that they would like to go to.
These buttons are located on a button panel on the interior of each elevator cab. The controller
interacts with these buttons by receiving pressed signals indicating the desired floor number
and elevator cab which they were pressed from. It also sends light on/off signals to indicate the
status of the buttons.
B.3 Open Door Button:
This button is on the interior button panel of each cab. A passenger can press this button to
open the elevator doors or keep pressing it to keep them open, but only when the elevator cab
99
is stopped at a floor. Some elevator systems also have a close door button, but this one does
not. The controller interacts with this button by receiving a signal when it is pressed and when
it is released. Both of these signals include the cab from which they came from.
B.4 Emergency Stop Button:
This button is on the interior button panel of each cab. A passenger can press this button to
stop the elevator no matter where it is in a shaft. The controller interacts with this button by
receiving a signal from it that indicates that it was pressed, as well as the cab that it came from.
B.5 Emergency Bell Button:
This button is on the interior button panel of each cab. A passenger can press this button to
sound a bell to alert people outside of the elevator shaft that someone is trapped inside the
elevator cab in case of a malfunction. The controller interacts with this button by receiving a
signal from it that indicates that it was pressed.
10
0
B.6 Registration panel
10
1
In destination control systems, the conventional hall call-buttons (Up and Down arrows) located
at the elevator lobby are replaced by the registration devices. Passengers register their
destination floor through these registration devices at the lobby instead of in the elevator. The
registration device will display the elevator that has been assigned for transporting the
passenger. As the passenger has already registered the desired destination floor, there is no
need to input the destination floor in the elevator.
C- Key Controls
Fireman's service Switches
Key controls may only be activated by the proper keys, and their use is thus restricted to repair
people, elevator operators or firemen. It is used in place of or in conjunction with a pushbutton
to restrict access to a floor. Keypads and card readers are also available. Examples for these
keys are as follows:
Fireman's service, phase II key switch.
An inspector's switch, which places the elevator in inspection mode (this may be
situated on top of the elevator).
Manual up/down controls for elevator technicians, to be used in inspection mode, for
example.
10
2
An independent service/exclusive mode Switch (also known as "Car Preference"), which
will prevent the car from answering to hall calls and only arrive at floors selected via the
panel. The door should stay open while parked on a floor. This mode may be used for
temporarily transporting goods. The controller interacts with the switch by receiving a
signal from it when it has been toggled to either AUTO or HOLD mode. AUTO is for
normal operation; HOLD is to keep the elevator cab from moving and its doors from
opening or closing.
Attendant service mode switch.
D- System Controls
System controls are used to turn the elevator system on or off, system controls are only
accessible from an elevator control room. They would typically be used quite infrequently –
perhaps the system would be turned on early in the morning and turned off late at night, or
turned off at the start of holidays and turned on once the next term begins.
2- Outputs, which include:
A- Actuators.
B- Bells.
C- Displays.
10
3
A- Actuators
A.1 Door Opening Device:
Door Opening Device
On top of each elevator cab is a door opening device. This device opens the inner door of the
elevator cab and the outer door of the elevator shaft simultaneously at each floor. The
controller interacts with the door opening device by sending signals to open or close the doors
and by receiving signals when the doors have been completely opened or closed. The signals
that the controller receives also indicate which cab they are coming from.
A.2 Electric motor:
The elevator motor is responsible for moving an elevator cab up and down between floors. As
this elevator system uses a roped mechanism, the elevator engine is connected to a sheave
which the ropes are looped around. The controller interacts with the elevator engine by sending
it a signal that specifies at which speed and in what direction the engine should be going in. A
stop signal is simply constructed by setting the speed parameter of the signal to zero.
A.3 Brakes:
There a few brake systems in a typical elevator system. These include the electromagnetic and
mechanical brakes. The electromagnetic brakes activate automatically if there is a sudden loss
of power or when the car is stationary. The mechanical brakes at the sheave itself also stop the
car from moving when the car is inactive.
10
4
B- Bells
B.1 Emergency Bell:
Somewhere in the elevator system is an emergency bell that is used to alert people outside of
the elevator system that someone is trapped inside an elevator cab. The controller interacts
with the emergency bell by sending it a signal to ring.
B.2 Load Bell:
Each cab has a load bell that is used to alert the passengers inside the cab that there is too much
weight in it to operate it safely. The controller interacts with the load bell be sending it a signal
to ring.
C- Displays
C.1 Car Position Display:
The interior of each elevator cab has a display that indicates to its passengers which floor the
elevator cab is currently on. Some elevator systems have this floor number display on every
floor outside of the elevator doors, but this system does not. The controller interacts with this
Car Position Display
10
5
display by sending a signal that tells it which floor number to display. Can be either analog
(individual indicators for each floor) or digital (a dot matrix or segmented LED that changes to
indicate the floor level)
C.2 Direction Display:
Direction Display
The interior of each elevator cab has a display that indicates the current direction of an elevator
cab; it is either up or down. The controller interacts with this display by sending it a signal that
tells it which direction to display.
10
6
3- Controller
The controller is a device which manages the visual monitoring, interactive command control
and traffic analysis system to ensure the elevators are functioning efficiently.
The primary function of the elevator controller. The primary function of the elevator controller
is essentially to receive and process a variety of signals from several different components of a
whole elevator system. It is able to send signals in response to the ones it receives in order to
operate all of the other components in the system. This exchange of signals is how the elevator
controller is able to keep the elevators running smoothly on a day-to-day basis.
Here are a few of the following ways the controller interacts with the other components of the
elevator system:
Controls the speed of elevator engines in order to move elevator cabs up and down their
respective shafts.
Queues and processes elevator summons and floor requests from passengers through the
signals provided to it by several buttons.
Processes information sent to it by load sensors in order to ensure that the load of a cab never
exceeds the safety limit.
Processes information sent to it by position marker sensors in order to keep track of where the
elevator cabs are at all times, as well as their speed.
Provides feedback to passengers through the lights on some of the buttons and the floor
number and direction displays in each cab.
Can sound alarm bells that are either invoked by trapped passengers or required to warn of
excess load in a cab.
Controls the operation of the elevator doors of a cab through communication with door opening
devices.
10
7
Types of elevator controllers
There are 3 primary types of controller technology used to process the logic of the controller as
follows:
1- Relay based controller (electromechanical switching)
Relay based controller (electromechanical switching)
A relay is a very dependable device consisting of an electromagnet that opens and closes
contacts, routing the logic to various circuits. A simple elevator with a few stops and manual
door operation can be served well by a relay controller. Relays can also be used for more
complex elevators, and in fact were until the 1980's. However, the number of relays required
can make it difficult to troubleshoot should there ever be a problem.
The following applications may be recommended as suitable for controllers using
electromagnetic relay technology:
Single lifts only.
Drive speed up to 1 m/s.
10
8
Passenger lifts in low traffic and usage situations in low-rise buildings, i.e. not more than
three stories (e.g. residential buildings, very small hotels, nursing homes).
Goods, bullion lifts in low-rise commercial buildings (e.g. offices, hotels, hospitals).
2- Solid-State Logic Technology
Solid-State Logic Technology
It includes both discreet transistors circuits and integrated circuit boards. It gives improved
reliability, lower power consumption and easy fault diagnosis than electromagnetic relay
technology.
The following applications are recommended as suitable for controllers using solid-state logic
technology:
Single lifts and duplex groups.
Drive speed up to 2 m/s.
Passenger lifts in low traffic situations in medium-rise buildings, i.e. up to 12 stories (e.g.
residential buildings and small hotels)
Goods, bullion lifts in low-rise commercial buildings (e.g. offices, hotels, hospitals)
10
9
3- PLC controller (computer based technology)
PLC controller (computer based technology)
The advent of personal computers has made microprocessor technology affordable for many
other fields. Elevator Concepts utilizes a special type of industrial computer called a
Programmable Logic Controller PLC to control the logic of more complex jobs. They are very
dependable, compact, and simple to troubleshoot.
Computer based controllers are suitable for the following:
All lifts types.
All drive speeds (i.e. 0.5 m/s to 10 m/s).
Lift groups of all sizes.
11
0
5.9.3 Elevator Control System Sequence Diagrams
The elevator control system may be viewed either from the point of view of an individual user
or as a system being acted on by many users and the following images show these different
point of views.
1- From the point of view of an individual user:
11
1
2- From the point of view as a system being acted on by many users:
Note: these topics about elevators in this course EE-1: Beginner's electrical design course is an
introduction only for beginners to know general basic information about elevators as a type of
Power loads. But in other levels of our electrical design courses, we will show and explain in
detail the Elevator Loads Estimation calculations.
11
2
5.10 Analysis
1.KLPAC has me the requirement of UBBL to position stairs near the elevators in case of
emergency and to install smoke detector at every lift lobbies in the building.
UBBL 1984 section 152-157, ventilation to elevator shafts:
151(1)- Every opening in an elevator shaft or elevator entrance shall open into a protected
lobby unless other suitable means of protection to the opening to the satisfaction of the local
authority is provided. These requirements shall not apply to open type industrial and other
special buildings as maybe approved by D.G.F.S.
153(1)- All elevator lobbies shall be provided with smoke detectors.
2.KLPAC has also met the requirement of UBBL 1984 to make sure the car moves to ground
floor with doors open when emergency happens.
154(1)- On failure of mains power all elevator shall return in sequence directly to the
designated floor, commencing with the fire elevators, without answering any car or landing
calls and park with doors open.
3.For mid-rise building, KLPAC has successfully provided 3 elevators to the requirement stated
by UBBL 1984 section 124, elevators:
124- For all non- residential buildings exceeding 4 storeys above or below the main access
level at least one elevator shaft be provided.
11
3
5.11 Conclusion
The selection of geared traction elevator system fits perfectly for the small or medium rise
building like KLPAC due to its volume of traffic, lower installation cost, number of floors and
lower maintenance cost. All of its mechanical transportation do bring convenience to the
users and the building complied with UBBL and fully functioning as well.
11
4
REFERENCES
6
11
5
6.0 References
Uniform Building By-Law 1984 (UBBL)
Malaysian Standard Requirements (MS 1525)
Fire Protection Association New Zealand Inc., Fire Sprinkler.
http://www.fireprotection.org.nz/sprinklers.htm
http://www.onestopfire.com/whatisfirepump.htm
What Is A Fire Pump?
One Stop Fire Products provides fire pump systems and related goods for rural, vacation and
remote properties.
onestopfire.com
http://www.fireservice.co.uk/safety/smoke-alarms
http://www.csemag.com/single-article/striking-a-balance-between-passive-and-active-fire-
protection/bd7bf18186f5b538e74862fc0c1474a1.html
Carbon dioxide suppression system
http://www.janusfiresystems.com/products/carbon-dioxide-co2
extinguisher
https://en.wikipedia.org/wiki/Fire_extinguisher
fire emergency staircase
https://en.wikipedia.org/wiki/Fire_escape
Separation of Fire Risk Area
https://www.hud.ac.uk/.../fireriskassessments/FRAc.doc
Smoke Curtain
https://en.wikipedia.org/wiki/Safety_curtain
11
6
Fire Wall
https://en.wikipedia.org/wiki/Firewall_(construction)
TRANSPORTATION SYSTEM REFERENCE ABOUT ELEVATORS. (n.d.). Retrieved June 23, 2016, from
http://www.otis.com/site/us/pages/AboutElevators.aspx…
ThyssenKrupp Elevator Americas. (n.d.). Retrieved June 23, 2016, from https://www.thyssenkruppelevator.com/modernization/gearless
Elevator Types - archtoolbox.com. (n.d.). Retrieved June 23, 2016, from https://www.archtoolbox.com/…/vertical-c…/elevatortypes.html
Elevator Control System. (n.d.). Retrieved June 23, 2016, from http://www.electrical-knowhow.com/…/elevator-control-system…
How do elevators and lifts work? (n.d.). Retrieved June 23, 2016, from http://www.explainthatstuff.com/how-elevators-work.html