Submitted By:-
Anirudh SharmaRam Pratap Singh
SUMMER TRAINING REPORT ONKOTSONS TRANSFORMERS
7/30/2019 Kot Sons
2/36
7/30/2019 Kot Sons
3/36
ISO 9001 :2000 Certified Company
Recognized Export House
Manufacturing Transformer Since 1979
25 years of Excellence
7/30/2019 Kot Sons
4/36
ALWAR Established in 1979
AGRA Established in 1991
7/30/2019 Kot Sons
5/36
Single phase transformer
Auto Transformer
Three Phase Transformer
Rectifying Transformer
Dry Type Transformer
Special Purpose Transformer
7/30/2019 Kot Sons
6/36
7/30/2019 Kot Sons
7/36
Bangladesh Oman
Iraq Syria
Ireland UAEJordan United Kingdom
Mauritius Yemen
NepalNigeria
7/30/2019 Kot Sons
8/36
NDPL, New Delhi
BSES, New Delhi Vestas RRB India Ltd. , New Delhi
NEPC Micon Ltd. , Chennai
ABB , Mumbai
Various State Electricity Board in INDIA
7/30/2019 Kot Sons
9/36
LAND MARKS
7/30/2019 Kot Sons
10/36
KOTSONS Firmly Pledge Allegiance
Towards the Betterment of
Product & customer Satisfaction
7/30/2019 Kot Sons
11/36
7/30/2019 Kot Sons
12/36
7/30/2019 Kot Sons
13/36
7/30/2019 Kot Sons
14/36
7/30/2019 Kot Sons
15/36
1-Transformer core 2-Transformer Windings
3-Transformer Tank and Radiators.
7/30/2019 Kot Sons
16/36
7/30/2019 Kot Sons
17/36
Cross over Type
Helical Type
Continuous Disc Type
7/30/2019 Kot Sons
18/36
1. Plain sheet steel tank.
2. Sheet steel tank with external cooling tubes.
3. Radiator tanks.
4. Tanks with corrugated wall panels.
7/30/2019 Kot Sons
19/36
1. Rating and terminal marking plate.
2. Tap Changing arrangement
(a) Off
circuit tap changing switch(b) Offcircuit tap changing link
(c) On Load tap changer
3. Two earthing terminals
4. Lifting Lugs
5. Draincum filter valve
6. Pressure Relief Device
7. Silicagel dehydrating breather.
Standard Fittings
7/30/2019 Kot Sons
20/36
8. Oil Level Indicator.9. Thermometer Pocket.
10. Conservator with drain plug and filling
hole.
11. Air Release plug.
12. Jacking lugs (above 1600 KVA)
13. Filter valve (top tank)
14. Under base unidirectional flat rollers
7/30/2019 Kot Sons
21/36
Bare Bushings
Or
Cable box.
i) Compound filled for PLC cables (upto 33000 Volts)or
ii) Air filled for PVC cable s (Upto 11000 Volts)
or
Bus Duct (Bare bushing enclosed in housing upto 600Volts)
Disconnection chamber between cable box andtransformer tank.
Additional bare neutral terminal.
7/30/2019 Kot Sons
22/36
Winding temperature indicator
Oil temperature indicator
Gas and oil actuated (Buchholz)relay
Conservator drain valve Shut off valve between conservator and tank.
Magnetic oil level gauge
Explosion vent
Filter valve (Bottom of tank)
Skid under base with haulage holes
Junction box.
7/30/2019 Kot Sons
23/36
Rating and Terminal marking plate
Tap changing arrangementi) Off - circuit tap changing switchII)On Load tap changer
Earthing Terminals Lifting Lugs
Valves and drain plugs
Silicagel dehydrating breather
Oil Level indicator
Thermometer Pockets Conservator with drain plug and filling hole
Jacking lugs
Air release plug
7/30/2019 Kot Sons
24/36
a) Bare bushing
i) Draw through bushing (oil flood type)
ii) Solid Bushing (through stem type)
a) Outdoor through stem type porcelain bushings
b) Cable box type porcelain
bushings
7/30/2019 Kot Sons
25/36
B) Cable sealing boxes
C) Bus Duct
c) Cable box type epoxy bushings.
7/30/2019 Kot Sons
26/36
a) Winding temperatureIndicator
b) Oil Temperature Indicator
7/30/2019 Kot Sons
27/36
c) Gas and oil actuated Buchholz relay
Magnetic Oil Gauge
7/30/2019 Kot Sons
28/36
Explosion Vent
7/30/2019 Kot Sons
29/36
PRE TEST INSPECTION
Sample of oil taken from the transformer and subjected to
electric test (break down value) of 50KV (RMS) as specified in
IS : 335.
Release trapped air through air release plugs and valve fittedfor the purpose on various fittings like radiators, bushing caps,
tank cover, Bushing turrets etc.
Check whether gas operated really (if provided) is mounted at
angle by placing a spirit level on the top of the relay. See thatthe conservator is filled upto the filling oil level marked on
plain oil gauge side and corresponding to the pointer reading in
MOG side. The air should be released after the tests. Make sure
that transformer oil runs through pert cock of Buchholz relay.
7/30/2019 Kot Sons
30/36
Check the condition of silicagel in the breather toensure that silicagel in the
breather is active and colour is blue. Also check that
the transformer oil is filled in the silicagel breather upto the level indicated.
For transformer furnished with thermometers for bothoil and winding
temperature, the signaling contacts are recommendedto be set to operate at the following temperatures.
Alarm Trip
Oil Temperature 85 deg.C +/- 2deg.c 95 Deg.C +/-
2deg.CWinding Temp. 100Deg.C +/- 2 Deg.C 110Deg.C+/- 2 deg.C
Check all the gasketed joints to ensure that there is noleakage of transformer
7/30/2019 Kot Sons
31/36
Ratio, Polarity and phase relationship
Alarm Circuits Tests
Alarm & trip circuitsa)a)Buchholz relayair injection test
b) Oil temperature indicator
alarm & trip circuits
c) Magnetic oil level gaugealarm circuits
d) Winding temperature indicatoralarm & trip circuits
Oil Sampling Test
Magnetic balance test
Magnetizing Current
Insulation Resistance
7/30/2019 Kot Sons
32/36
Quality
Long life
Reliability
Manufacturing Tolerance
Design Verification
R & D
7/30/2019 Kot Sons
33/36
1. Measurement of winding resistance.
2. Verification of voltage ratio.
3. Verification of vector Group.4. Measurement of no load current and losses.
5. Measurement of impedance and load losses.
6. Measurement of insulation resistance.
7. Power frequency withstand Voltage.
8. Induced over voltage test.
7/30/2019 Kot Sons
34/36
1. Impulse Voltage withstand test.
2. Temperature rise test.
7/30/2019 Kot Sons
35/36
Transformers are type tested at KEMA, the
Netherlands.
Manufacturing capacity upto 25 MVA, 33 KV
Manufacturing standards: IEC, BS, ANSI, IS &
DIN
Providing technical collaboration to foreign
companies.