Circuit Reliability Review La Verne January 2018
Transcript
Page 1: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

Circuit Reliability Review La Verne

January 2018

Page 2: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

Building a Smarter Grid for Southern California

• Southern California Edison is developing an electric grid to support California’s transition to a clean and sustainable future that meets the needs and expectations of our customers.

• We are investing more than $13 billion in the power distribution grid over three years (2017-19). Our main investment goal is to increase power reliability through significant upgrades. The investments include:

• Upgrading cables, poles, switches and transformers

• Updating the grid so it can accommodate new technologies, such as smart inverters that will allow for the two-way flow of solar energy

• Adapting the power system to accommodate future California policy related to energy storage, electric transportation and renewable energy

• Providing enhanced automation and monitoring devices to allow us to better respond to changes on the grid

• Our investments in local communities will help ensure that customers receive safe, reliable, and affordable electricity now and in the future.

• Learn more at edison.com/innovation

2

Page 3: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

Understanding Your Reliability Report

• As your electric utility, we want you to always have power when you need it. To

get there, we constantly track and monitor electric outages across our service

territory, and we measure our “system reliability” from this data.

• The two metrics we rely on are common in the electric utility industry: the

System Average Interruption Duration Index (SAIDI) and the System Average

Interruption Frequency Index (SAIFI). Both are described in more detail on the

next page.

• Replacing and upgrading our infrastructure will help SCE maintain or improve

SAIDI and SAIFI measurements.

• This report provides historical reliability data for the circuits that serve your

jurisdiction and our proposed infrastructure upgrades for the current year.

• To view other reliability reports, visit sce.com>Outage Center>Maintaining

Reliable Service

3

Page 4: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

Reliability Metrics

MOMENTARY OUTAGES:

OUTAGES LASTING 5 MINUTES OR LESS

MAIFI:

o The number of times the average customer is interrupted by Momentary outages each year.

SUSTAINED OUTAGES:

OUTAGES LASTING LONGER THAN 5 MINUTES

SAIFI:

o The number of times the average customer is interrupted by Sustained outages each year.

SAIDI:

o The cumulative amount of time the average customer is interrupted by Sustained outages each year.

4

Page 5: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

CityList1Cities in the COVINA District

LA VERNE

POMONA

WEST COVINA

WEST PUENTE VALLEY

ROWLAND HEIGHTS

SAN DIMAS

AZUSA

CHARTER OAK

CITRUS

CLAREMONT

COVINA

DIAMOND BAR

AVOCADO HEIGHTS

SOUTH SAN JOSE HILLS

VALINDA

VINCENT

WALNUT

GLENDORA

HACIENDA HEIGHTS

INDUSTRY

LA PUENTE

5

Page 6: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

*”Exclusions” are days which utilities are allowed to remove from their metrics because the outages on those days were caused by a severe acts of nature.**In the columns showing “Rank,” lower numbers indicate poorer performance.

6

Page 7: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

CircuitList1Overview of La VerneThere are 19 circuits that serve La Verne 1

Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type Customers

AVENIDA(12KV) 1,536 - - -

BILL(12KV) 999 - - -

BOYALTA(12KV) 1,378 - - -

BRACKETT(12KV) 1,524 - - -

BRYDON(12KV) 1,536 - - -

CAL POLY(12KV) 1,006 - - -

DURWARD(12KV) 202 - - -

FOOTHILL(12KV) 1,314 - - -

KRANZER(12KV) 1,403 - - -

LIMBER(12KV) 1,145 - - -

LIMING(12KV) 1,365 - - -

MORAN(12KV) 1,349 - - -

NEMAHA(4.16KV) 393 - - -

PALMER(12KV) 1,561 - - -

PUDDINGSTONE(12KV) 887 - - -

QUAKER(4.16KV) 472 - - -

RHOADS(12KV) 2,365 - - -

SAM(12KV) 1,329 - - -

WINTHROP(12KV) 1,839 - - -

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

Grand Total 23,603

7

Page 8: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

BarChart

SCE SYSTEMWIDE

**Data is as of 02/20/2018, data

can be slightly different due to

outage data validation process

La Verne

Reliability History of Circuits Serving La Verne (No Exclusions)

**“Exclusions” are days which

utilities are allowed to

remove from their metrics

because the outages on

those days were caused by

acts of nature.

92.1 89.6 92.6106.4

112.1 114.8

134.5 139.7

0.0

20.0

40.0

60.0

80.0

100.0

120.0

140.0

160.0

2014 2015 2016 2017

SAIDI

(average

minutes of

sustained

interruptions)

0.9

0.70.8

1.01.0 0.9

1.11.2

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

SAIFI

(average

frequency of

sustained

interruptions)

1.21.4

2.5

1.7

1.4 1.41.6

1.8

0.0

0.5

1.0

1.5

2.0

2.5

3.0

MAIFI

(average

frequency of

momentary

interruptions)

8

Page 9: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

SAIDIChart

SAIDI = the cumulative amount of time the average customer is interrupted by “sustained” outages each year.

Causes of Repair Outages in La Verne

2017

3rd Party

24.3%

Equipment Failure

39.5%

Operation

13.2%

Other

0.4%

Vegetation

/Animal

5.5%

Weather /Fire

/Earthquake

17.2%

Contributions to SAIDI by Outage Cause

3rd Party

Equipment Failure

Operation

Other

Vegetation /Animal

Weather /Fire /Earthquake

Equipment Failure

e.g., in-service failure of transformer, switch, or conductors

Vegetation/Animale.g., tree branch, rodent, or bird

causing a short circuit between conductors

Othere.g., patrolled but no cause found

Operationse.g., urgent maintenance w/o 3-day

notice 3rd Party

e.g., balloon, car hit pole, dig-in

9

Page 10: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

SAIFIChart

SAIFI = the number of times the average customer is interrupted by “sustained” outages each year

Causes of Repair Outages in La Verne

2017

3rd Party

18.1%

Equipment Failure

29.0%

Operation

29.3%

Other

4.8%

Vegetation /Animal

4.6%

Weather /Fire

/Earthquake

14.2%

Contributions to SAIFI by Outage Cause

3rd Party

Equipment Failure

Operation

Other

Vegetation /Animal

Weather /Fire /Earthquake

Equipment Failure

e.g., in-service failure of transformer, switch, or conductors

Vegetation/Animale.g., tree branch, rodent, or bird

causing a short circuit between conductors

Othere.g., patrolled but no cause found

Operationse.g., urgent maintenance w/o 3-day

notice 3rd Party

e.g., balloon, car hit pole, dig-in

10

Page 11: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

11

Page 12: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

12

Page 13: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

Back-up Slides

Reliability Histories of Circuits Serving La Verne

Updated through Dec 2017

Page 14: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

CitySummary

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

92.1 0.9 1.2 89.6 0.7 1.4 92.6 0.8 2.5 24.0 0.2 0.3 3.4 0.2 0.3 24.3 0.3 0.6 54.6 0.4 0.6 106.4 1.0 1.7

3rd Party 17% 1% 9% 8% 2% 14% 35% 16% 13% 6% 33% 22% - - 56% - - - 45% 32% 16% 24% 18% 18%

Equipment Failure 52% 35% 1% 50% 45% 11% 44% 41% 8% 79% 47% 0% 49% 4% - 33% 37% 24% 25% 27% 11% 39% 29% 12%

Operation 9% 24% 15% 11% 14% - 6% 9% 0% 7% 14% 6% 36% 67% - 26% 28% 3% 9% 21% - 13% 29% 2%

Other 3% 5% 25% 10% 18% 52% 1% 1% 37% - - 33% 10% 28% 20% - - 55% 0% 0% 9% 0% 5% 30%

Vegetation/Animal 14% 31% 41% 20% 20% 18% 5% 20% 31% 2% 1% 24% 0% 0% 23% 0% 0% 8% 10% 11% 55% 5% 5% 30%

Weather/Fire/Earthquake 4% 3% 9% 0% 2% 5% 10% 13% 10% 7% 5% 15% 4% 1% - 41% 35% 10% 12% 9% 9% 17% 14% 9%

SCE SYSTEMWIDE 112.1 1.0 1.4 114.8 0.9 1.4 134.5 1.1 1.6 42.6 0.3 0.5 23.6 0.2 0.4 29.2 0.2 0.4 44.3 0.4 0.5 139.7 1.2 1.8

2nd Qtr 2017 3rd Qtr 2017

19 Circuits Serving La Verne -- Total Customers:

23,603

Average Reliability of 19 Circuits Serving La Verne

4th Qtr 2017 20172014 2015 2016 1st Qtr 2017

Notes:

No outages are excluded from the metrics.

Outage Causes: Other: e.g., patrolled but no cause could be foundOperations: e.g., urgent maintenance w/o 3-day notice to customers3rd Party: e.g., balloons, car hit pole, dig-inVegetation/Animal: e.g., tree branch, rodent, or bird causing short circuit across conductors

SAIDI (minutes) = the cumulative amount of time the average customer is interrupted by “sustained” (longer than 5 minutes) outages.

SAIFI (interruptions) = the number of times the average customer is interrupted by “sustained” outages.

MAIFI (interruptions) = the number of times the average customer is interrupted by “momentary " (lasting 5 minutes or less) outages.

14

Page 15: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

CircuitHistory1

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

AVENIDA(12KV) - Customers: 1,536 348.4 4.0 3.0 345.9 1.4 0.6 76.4 1.1 5.5 - - - - - - 1.4 0.0 1.0 162.7 1.2 1.0 164.0 1.2 2.0

3rd Party - - - 26% 8% - - - 36% - - - - - - - - - 7% 4% - 7% 4% -

Equipment Failure 41% 25% - 70% 86% - - - - - - - - - - - - - 89% 86% 100% 89% 86% 50%

Operation 1% 1% 33% 3% 5% - 4% 7% - - - - - - - 31% 25% - 4% 10% - 4% 10% -

Other - - - - - 100% - - 27% - - - - - - - - 100% - - - - - 50%

Vegetation/Animal 58% 75% 67% 1% 1% - - - 36% - - - - - - 69% 75% - - - - 1% 0% -

Weather/Fire/Earthquake - - - - - - 96% 93% - - - - - - - - - - - - - - - -

BILL(12KV) - Customers: 999 107.1 2.8 0.4 0.7 0.0 - 0.2 0.0 - - - 1.0 - - - 31.1 2.1 0.9 89.2 1.0 - 120.4 3.1 1.9

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - 100% 100% - - - - - - - 100% 100% 100% 100% 99% - 100% 100% 48%

Operation - - - 100% 100% - - - - - - - - - - - - - 0% 1% - 0% 0% -

Other 45% 40% - - - - - - - - - 100% - - - - - - - - - - - 52%

Vegetation/Animal 55% 60% 100% - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

BOYALTA(12KV) - Customers: 1,378 15.9 0.1 - 49.3 1.0 - 41.8 1.0 - 0.2 0.0 - 5.2 0.0 - 49.9 0.1 - - - 1.0 55.4 0.2 1.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 9% 2% - - - - 2% 1% - - - - 100% 100% - 94% 50% - - - - 94% 63% -

Operation - - - 100% 100% - - - - 100% 100% - - - - 6% 50% - - - - 6% 37% -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal 91% 98% - - - - 98% 99% - - - - - - - - - - - - 100% - - 100%

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

BRACKETT(12KV) - Customers: 1,524 - - 2.0 207.2 2.1 3.8 124.5 1.1 3.8 - - - - - 1.0 - - - - - - - - 1.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - 98% 87% 21% 89% 89% 47% - - - - - - - - - - - - - - -

Operation - - - 2% 9% - - - - - - - - - - - - - - - - - - -

Other - - 50% 0% 4% 52% - - 53% - - - - - - - - - - - - - - -

Vegetation/Animal - - 50% - - 26% 3% 4% - - - - - - 100% - - - - - - - - 100%

Weather/Fire/Earthquake - - - - - - 7% 7% - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving La Verne - 1 of 5

2014 2015 2016 1st Qtr 2017 2nd Qtr 2017 3rd Qtr 2017 4th Qtr 2017 2017

15

Page 16: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

CircuitHistory2

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

BRYDON(12KV) - Customers: 1,536 188.7 2.3 1.1 32.7 0.1 1.0 35.6 0.1 7.4 16.4 0.1 - 3.3 0.0 - 23.2 0.0 0.0 191.4 1.0 1.0 234.3 1.2 1.0

3rd Party - - - - - - 45% 20% 29% 18% 10% - - - - - - - 98% 97% - 82% 87% -

Equipment Failure 35% 6% 5% 91% 93% - - - - - - - 36% 50% - - - - - - - 1% 1% -

Operation 19% 26% 45% 1% 1% - - - - 82% 90% - - - - 100% 100% - - - - 16% 7% -

Other 2% 1% 2% - - 97% 14% 20% 29% - - - - - - - - 100% 1% 0% - 0% 0% 3%

Vegetation/Animal 10% 44% 3% 8% 6% 3% 42% 59% 43% - - - - - - - - - 1% 3% 100% 1% 3% 97%

Weather/Fire/Earthquake 34% 23% 45% - - - - - - - - - 64% 50% - - - - - - - 1% 1% -

CAL POLY(12KV) - Customers: 1,006 342.8 0.3 1.0 6.8 0.1 2.0 28.3 1.0 0.1 383.3 1.0 1.0 - - - 200.3 1.0 2.0 125.7 1.0 1.0 709.3 3.0 4.0

3rd Party 100% 100% 100% - - - 100% 100% - - - - - - - - - - - - 100% - - 25%

Equipment Failure - - - - - - - - - 100% 100% - - - - - - - - - - 54% 33% -

Operation - - - 100% 100% - - - 100% - - - - - - - - - 6% 1% - 1% 0% -

Other - - - - - 48% - - - - - 100% - - - - - 50% - - - - - 50%

Vegetation/Animal - - - - - 52% - - - - - - - - - - - 50% 94% 99% - 17% 33% 25%

Weather/Fire/Earthquake - - - - - - - - - - - - - - - 100% 100% - - - - 28% 33% -

DURWARD(12KV) - Customers: 202 140.3 2.0 2.1 38.7 0.2 - 0.8 0.0 - - - - 1.5 0.0 - - - - - - - 1.5 0.0 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 51% 47% 7% - - - - - - - - - 100% 100% - - - - - - - 100% 100% -

Operation 26% 3% - 100% 100% - 100% 100% - - - - - - - - - - - - - - - -

Other 1% 0% 47% - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal 22% 49% 46% - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

FOOTHILL(12KV) - Customers: 1,314 18.5 0.2 2.6 0.2 0.0 2.0 27.2 0.6 3.6 7.4 0.0 - 23.8 0.1 - 0.3 0.0 - 0.3 0.0 1.0 31.7 0.1 1.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - 1% 0% - - - - 96% 85% - - - - - - - 72% 47% -

Operation 100% 100% 24% 100% 100% - 13% 8% - 100% 100% - 4% 15% - 100% 100% - 100% 100% - 28% 53% -

Other - - 38% - - 50% - - 55% - - - - - - - - - - - - - - -

Vegetation/Animal - - 38% - - 50% 22% 61% 45% - - - - - - - - - - - 100% - - 100%

Weather/Fire/Earthquake - - - - - - 64% 30% - - - - - - - - - - - - - - - -

2017

Reliability Histories for Individual Circuits Serving La Verne - 2 of 5

2014 2015 2016 1st Qtr 2017 2nd Qtr 2017 3rd Qtr 2017 4th Qtr 2017

16

Page 17: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

CircuitHistory3

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

KRANZER(12KV) - Customers: 1,403 - - 2.0 84.9 1.1 2.0 271.8 1.4 5.1 - - - - - - - - - 194.5 1.0 1.0 194.5 1.0 1.0

3rd Party - - - - - - - - - - - - - - - - - - 100% 100% - 100% 100% -

Equipment Failure - - - 75% 92% - 95% 95% - - - - - - - - - - - - - - - -

Operation - - 50% 25% 8% - - - - - - - - - - - - - - - - - - -

Other - - - - - 50% 5% 5% 50% - - - - - - - - - - - - - - -

Vegetation/Animal - - 50% - - 50% - - 50% - - - - - - - - - - - 100% - - 100%

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

LIMBER(12KV) - Customers: 1,145 392.4 3.2 2.0 79.8 1.1 2.6 236.8 2.2 1.0 - - - - - - - - - - - - - - -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 97% 96% 0% - - 33% 59% 45% - - - - - - - - - - - - - - - -

Operation 3% 4% - - - - 41% 55% - - - - - - - - - - - - - - - -

Other - - - 95% 97% 33% - - 100% - - - - - - - - - - - - - - -

Vegetation/Animal 0% 0% 100% 4% 3% - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 1% 0% 34% - - - - - - - - - - - - - - - - - -

LIMING(12KV) - Customers: 1,365 25.1 2.0 - 3.4 0.0 2.0 - - 1.0 - - - - - - 0.7 0.0 - - - 1.0 0.7 0.0 1.0

3rd Party - - - - - 100% - - - - - - - - - - - - - - 100% - - 100%

Equipment Failure 4% 1% - - - - - - 100% - - - - - - - - - - - - - - -

Operation 95% 99% - - - - - - - - - - - - - 100% 100% - - - - 100% 100% -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal 1% 0% - 100% 100% - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

MORAN(12KV) - Customers: 1,349 4.4 0.0 1.0 68.1 1.0 - 8.3 0.0 3.0 - - - - - 1.0 - - - - - - - - 1.0

3rd Party - - - - - - 22% 47% - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% - 94% 99% - 37% 24% - - - - - - - - - - - - - - - -

Operation - - - 6% 1% - - - - - - - - - - - - - - - - - - -

Other - - 100% - - - - - 34% - - - - - 100% - - - - - - - - 100%

Vegetation/Animal - - - - - - 41% 29% 66% - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving La Verne - 3 of 5

2014 2015 2016 1st Qtr 2017 2nd Qtr 2017 3rd Qtr 2017 4th Qtr 2017 2017

17

Page 18: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

CircuitHistory4

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

NEMAHA(4.16KV) - Customers: 393 - - - 150.4 1.4 3.4 11.0 1.0 2.0 101.7 1.4 - 10.0 1.0 1.0 - - - - - - 111.7 2.4 1.0

3rd Party - - - 90% 30% 41% - - - - - - - - 100% - - - - - - - - 100%

Equipment Failure - - - - - - - - - - - - - - - - - - - - - - - -

Operation - - - - - - - - - 7% 66% - 100% 100% - - - - - - - 16% 80% -

Other - - - - - 30% - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 10% 70% 30% 100% 100% 100% 93% 34% - - - - - - - - - - 84% 20% -

PALMER(12KV) - Customers: 1,561 73.6 0.1 1.0 290.1 1.8 1.3 39.7 0.1 - - - 0.2 5.2 0.7 1.0 79.2 1.1 - 4.8 0.0 - 89.2 1.8 1.2

3rd Party - - 100% - - 78% 45% 47% - - - - - - 100% - - - 2% 3% - 0% 0% 80%

Equipment Failure 100% 99% - 56% 44% 22% 51% 31% - - - - - - - 16% 2% - 71% 56% - 18% 2% -

Operation - - - 0% 0% - 3% 21% - - - 100% - - - 84% 98% - - - - 75% 57% 20%

Other - - - - - - - - - - - - 98% 100% - - - - - - - 6% 40% -

Vegetation/Animal 0% 1% - 44% 56% - - - - - - - 2% 0% - - - - 27% 41% - 2% 1% -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PUDDINGSTONE(12KV) - Customers: 887 - - 2.0 - - 1.0 108.6 2.0 2.0 69.3 1.0 1.0 - - - - - - 176.9 1.0 - 246.2 2.0 1.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - 100% 100% 100% 50% 100% 100% 0% - - - - - - - - - 28% 50% 0%

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - 50% - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - 100% - - - - - - - - 100% - - - - - - 100% 100% - 72% 50% 100%

QUAKER(4.16KV) - Customers: 472 2.5 0.0 - 13.8 0.1 - - - - - - - 8.9 1.0 1.0 - - 1.0 13.8 1.0 - 22.6 2.0 2.0

3rd Party - - - - - - - - - - - - - - 100% - - - - - - - - 50%

Equipment Failure 100% 100% - - - - - - - - - - - - - - - - - - - - - -

Operation - - - 100% 100% - - - - - - - 100% 100% - - - 100% 100% 100% - 100% 100% 50%

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving La Verne - 4 of 5

2014 2015 2016 1st Qtr 2017 2nd Qtr 2017 3rd Qtr 2017 4th Qtr 2017 2017

18

Page 19: La Verne January 2018 - Southern California Edison · Circuit Reliability Review La Verne January 2018. Building a Smarter Grid for Southern California • Southern California Edison

CircuitHistory5

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

RHOADS(12KV) - Customers: 2,365 - - 2.9 131.2 1.2 5.0 126.3 1.1 4.0 5.5 0.0 0.7 - - - 35.6 0.1 3.3 - - 1.1 41.2 0.2 5.1

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - 100% 100% - - - - - - - 99% 78% 33% - - - 85% 69% 21%

Operation - - 32% 26% 5% - - - - - - - - - - 1% 22% - - - - 1% 19% -

Other - - 32% 57% 87% 80% - - 50% - - - - - - - - 67% - - - - - 43%

Vegetation/Animal - - 35% 16% 9% 20% - - 50% 100% 100% 100% - - - - - - - - 100% 13% 12% 35%

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

SAM(12KV) - Customers: 1,329 19.8 0.7 - 102.8 1.0 1.0 27.0 1.3 2.3 23.7 1.0 1.0 - - 1.0 27.1 1.0 1.0 68.8 1.0 2.0 119.6 3.0 5.0

3rd Party - - - - - - - - - 94% 100% 100% - - 100% - - - - - - 19% 33% 40%

Equipment Failure 41% 4% - 1% 0% - 49% 2% - - - - - - - - - - - - - - - -

Operation 46% 92% - 1% 0% - 3% 1% - 6% 0% - - - - - - - 100% 100% - 59% 33% -

Other 13% 5% - - - 100% - - - - - - - - - - - - - - 50% - - 20%

Vegetation/Animal - - - 98% 100% - 45% 97% - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - 2% 0% 100% - - - - - - 100% 100% 100% - - 50% 23% 33% 40%

WINTHROP(12KV) - Customers: 1,839 22.5 0.0 - 6.6 0.0 - 401.3 1.1 2.8 2.1 0.0 - 10.9 1.0 - 0.3 0.0 - - - - 13.3 1.0 -

3rd Party - - - - - - 92% 94% 30% - - - - - - - - - - - - - - -

Equipment Failure 79% 74% - - - - 0% 0% - - - - - - - - - - - - - - - -

Operation 19% 25% - 14% 36% - 0% 0% - 100% 100% - 100% 100% - 100% 100% - - - - 100% 100% -

Other 2% 1% - - - - - - 35% - - - - - - - - - - - - - - -

Vegetation/Animal - - - 86% 64% - 0% 0% - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - 8% 5% 35% - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving La Verne - 5 of 5