Lab Project No.2 (Heat Exchangers) Dr. Ho Sung Lee
Transcript

Lab Project No.2

(Heat Exchangers)

Dr. Ho Sung Lee

Parallel Flow

Counter Flow

Surface Temperature for Parallel Flow

Double Pipe Surface temperature

0

20

40

60

80

100

120

0 10 20 30 40 50 60

Tube Length (in)

Te

mp

era

ture

(F

)

Fluent simulation

Experiments

Velocity Profiles for the Entry region

Parallel flow

Experiment MathCad Fluent Experiment MathCad Fluent MathCad Fluent

°K °K °K T T T %error %error

Inner inlet 290.9 290.9 290.9 T 5.06 4.83 5.00 4.40% 1.10%

Inner outlet 295.9 295.7 295.9

outer inlet 316.3 316.3 316.3 T 4.89 4.89 5.10 0.00% -4.32%

outer outlet 311.4 311.4 311.2

Effectiveness 0.191 Tlm 4.97 4.86 5.05 2.23% -1.57%

q (Watts) 2762 2543 2637 q (% error) 7.93% 4.53%

Counter flow

Experiment MathCad Fluent Experiment MathCad Fluent MathCad Fluent

°K °K °K T T T %error %error

Inner inlet 288.3 288.3 288.3 T 5.33 5.11 5.30 4.17% 0.62%

Inner outlet 293.6 293.4 293.6

outer inlet 314.8 314.8 314.8 T 4.89 5.11 5.40 -4.55% -

10.45%

outer outlet 309.9 309.7 309.4

Effectiveness 0.194 Tlm 5.11 5.12 5.35 -0.24% -4.74%

q (Watts) 2570 2655 2806 q (% error) -3.31% -9.18%

Shell and tube

Experiment MathCad Experiment MathCad MathCad

°K °K T T %error

Inner inlet 287.4 287.4 T 5.67 5.11 9.80%

Inner outlet 293.1 292.6

outer inlet 318.6 318.6 T 5.56 5.17 7.00%

outer outlet 313.0 313.4

Effectiveness 0.166 Tlm 5.61 5.14 8.41%

Correction factor 0.993

q (Watts) 2937 2705 q (% error) 7.90%

Results for Double Pipe and Shell and Tube heat exchangers