I ~~UDWIG & ASSOCIATES LTD.,..· - - - - u u u n 1 """'''''''''ON~ BUREAu
LABORATORY TEST REPORT :,~~~~~o~:e;~~ITED
CUSTOMER: Harbert's Products Inc.P.O. Box418,501 South Cedar LaneGreencastle; PA17225 - 0418
Laboratory Test No.: C04-766.1Date: July 15, 2004
Attention: Harvey Beck
WPS Number:
Material:
Thickness:
Electrode Class:
Flux Type:Electrode/Flux Class:
SAW-1
SA 36 (Ht. No.: 138844)
25.4 mm (1.00 in.)
EM13K Electrode (Lincoln L-50)Crushed 781
FS7AO - EM13KF48AO- EM13K
Thermal Condition: As Welded
Batch/Lot No.: 1070104
SPECIMEN NUMBER
DIAMETER mm (in.)
AREA sq. mm (sq. in.)
GAUGE LENGTH mm (in.)YIELD STRENGTH METHOD
LOAD AT YIELD N (Ibs)
YIELD STRENGTH MPa (psi)
ULTIMATE LOAD N (Ibs)
ULTIMATE STRESS MPa (psi)
FINAL AREA sq. mm (sq. in.)% REDUCTION IN AREA
% ELONGATION
TYPE OF FRACTURE
TENSILE TEST
T1
12.6 (0.496)
125 (0.193)
50.8 (2.00)0.2% Offset
66 100
530
77 200
619
48.2
61
24
PartialCup& Cone
(14,900)
(76,900)
(17,400)
(89,800)
(0.075)
FS7AO-EM13K /
F48AO-EM13K
Reauirements
400 (58,000) minimum
480/660 (70,000/95,000)
22 minimum
We certify the test results in this report and that the specimen(s) were prepared and tested in accordance with therequirements of AWS A5.17/A5.17M - 97/ CSA W48.6 - 99 & AWS B4.0 - 98. The information regarding materialidentification (i.e. size, thickness, heat number, etc.) has been provided by the customer whose name appears onthis report.
Laboratory Test Conducted By:ve Rieberger, C.E.T.
4027 - 74StreetS.£.,O\LGARY, ALBERTAT2G3K6 PHONE: (403)262-7072 FAX: (403) 266-3769 Paae 1 of 1
I.~~UDWIG & ASSOCIATES LTD.
'iF' m (J U v n ) ACCREDITATION;;I BUREAU
LABORATORYTEST REPORT ~~~~~:~::;~~~ITED
Laboratory Test No.: C04-766.1Date: July 16,2004
CUSTOMER: Harbert's Products Inc.P.O. Box 418,501 South Cedar LaneGreencastl~: PA17225 -0418
Attention: Harvey Beck
WPS Number:
Material:
Thickness:
Electrode Class:
Flux Type:Electrode/Flux Class:
SAW-1
SA 36 (Ht. No.: 138844)
25.4 mm (1.00 in.)
EM13K Electrode (Lincoln L-50)Crushed 781
FS7AO - EM13KF48AO- EM13K
Thermal Condition: As Welded
Batch/Lot No.: 1070104
NOTCH-TOUGHNESS TEST
TYPE OF TEST: Charpy V-NotchTEST TEMPERATURE: -18°C (O°F)
SpecimenNumber
ORIENTATION:SPECIMEN SIZE:
Transverse10 x 10 mm
NotchLocation
F2.1F2.2F2.3F2.4F2.5
Weld MetalWeld MetalWeld MetalWeld MetalWeld Metal
57.066.444.758.363.7
(42.0)(49.0)(33.0)(43.0)(47.0)
Toughness test results meet the requirements of ANSI/AWS A5.17/A5.17M - 97, for FS7AO - EM13K /F48AO-EM 13K Electrode/Flux classification.
We certify the test results in this report and that the specimen(s) were prepared and tested in accordance with therequirements of AWS A5.17/A5.17M - 97 / CSA W48.6 - 99 & AWS 84.0 - 98. The information regarding materialidentification (i.e. size, thickness, heat number, etc.) has been provided by the customer whose name appears onthis report. .
Laboratory Test Conducted By:
4027 - 14 Street S.E., CALGARY, ALBERTA T2G 3K6 PHONE: (403) 262-7072 FAX: (403) 266-3169 Pace 1 of 1
WESTERN INSPECTION LTD.3231- 58thAVENUE,S.B.,CALGARYALBERTAT2COB4TBL:(403)279.4540FAX:(403)236-3043
Ludwig & Associates4027- 14St. SECalgary ABT26 3K6Tel: (403) 262-7072 Fax: (403) 266-3169
i __
Job Number: C04-766PO Number:
RADIOGRAPHIC EXAMINATION REPORT #tGV-209949
-l
Date of Exam:Job Location:Technicians:
AceCodes:Inspected:Material:Isotope:Focal spot:Curies:Degree:Processing:Units:
Wednesday,Jul 14 2004 .Customer s ShopLeo Brunet CGSBII, SHTII
AStlESee 11 Part C SFA5.17-2001Pre Heat Treatsa 36IR192
. .2x3 111150
100%Automaticin
Legend:---------. (Loading) S :: Singleo :: Double
T :: TripleACC:: AcceptREJ :: Reject
RETEST:: Retest1 :: Acceptable2 :: Slight3 :: Reject
Note: SFDDoes not include reinforcement
II (Result)
@ (Degree)
--.J1 TestInformation : FilmInformation : ResultInformation :I _. 00__ .. _II. 1__ ft_L ",." ",,,,..,, . , _ T. T" ~:... I.- A n'I'!"""""""II'lou C'rftM_
Test: .1 RT4-L 1B 20 12 19.0 1.277 S o - END D5-6EV-I4.5x17ACC
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
T.291hi S.S.O.F.D.,nominalwall thickness plus reinforcement.RT4 Longseams: T.291g) 5.0.0., upto 2" wall thickness,18",over2" wall thickness208 mi~imum.
Footage:Oty Code------------------------------------------------1 Ft L/1.0/00
~~~~-~~~~:~--~----------------------------Scott Istace C6SBLevel II SNTLevel11
Sign Here: ~-~-------------------------------
~tIPORIANT:Please.~ign AndRe~urn.the yellowCopy.to W~sternInspec~i~nLtd. ~.S.A.P~7/14/2004 10:46:47 AM.- .