I ~~UDWIG & ASSOCIATES LTD. ,.. · - -- - u u u n 1 """'''''''''ON ~ BUREAu LABORATORY TEST REPORT :,~~~~~o~:e;~~ITED CUSTOMER: Harbert's Products Inc. P.O. Box418,501 South Cedar Lane Greencastle; PA 17225 - 0418 Laboratory Test No.: C04-766.1 Date: July 15, 2004 Attention: Harvey Beck WPS Number: Material: Thickness: Electrode Class: Flux Type: Electrode/Flux Class: SAW-1 SA 36 (Ht. No.: 138844) 25.4 mm (1.00 in.) EM13K Electrode (Lincoln L-50) Crushed 781 FS7AO - EM13K F48AO- EM13K Thermal Condition: As Welded Batch/Lot No.: 1070104 SPECIMEN NUMBER DIAMETER mm (in.) AREA sq. mm (sq. in.) GAUGE LENGTH mm (in.) YIELD STRENGTH METHOD LOAD AT YIELD N (Ibs) YIELD STRENGTH MPa (psi) ULTIMATE LOAD N (Ibs) ULTIMATE STRESS MPa (psi) FINAL AREA sq. mm (sq. in.) % REDUCTION IN AREA % ELONGATION TYPE OF FRACTURE TENSILE TEST T1 12.6 (0.496) 125 (0.193) 50.8 (2.00) 0.2% Offset 66 100 530 77 200 619 48.2 61 24 PartialCup& Cone (14,900) (76,900) (17,400) (89,800) (0.075) FS7AO-EM13K / F48AO-EM13K Reauirements 400 (58,000) minimum 480/660 (70,000/95,000) 22 minimum We certify the test results in this report and that the specimen(s) were prepared and tested in accordance with the requirements of AWS A5.17/A5.17M - 97/ CSA W48.6 - 99 & AWS B4.0 - 98. The information regarding material identification (i.e. size, thickness, heat number, etc.) has been provided by the customer whose name appears on this report. Laboratory Test Conducted By: ve Rieberger, C.E.T. 4027 - 74 StreetS.£., O\LGARY, ALBERTA T2G 3K6 PHONE: (403) 262-7072 FAX: (403) 266-3769 Paae 1 of 1
Transcript

I ~~UDWIG & ASSOCIATES LTD.,..· - - - - u u u n 1 """'''''''''ON~ BUREAu

LABORATORY TEST REPORT :,~~~~~o~:e;~~ITED

CUSTOMER: Harbert's Products Inc.P.O. Box418,501 South Cedar LaneGreencastle; PA17225 - 0418

Laboratory Test No.: C04-766.1Date: July 15, 2004

Attention: Harvey Beck

WPS Number:

Material:

Thickness:

Electrode Class:

Flux Type:Electrode/Flux Class:

SAW-1

SA 36 (Ht. No.: 138844)

25.4 mm (1.00 in.)

EM13K Electrode (Lincoln L-50)Crushed 781

FS7AO - EM13KF48AO- EM13K

Thermal Condition: As Welded

Batch/Lot No.: 1070104

SPECIMEN NUMBER

DIAMETER mm (in.)

AREA sq. mm (sq. in.)

GAUGE LENGTH mm (in.)YIELD STRENGTH METHOD

LOAD AT YIELD N (Ibs)

YIELD STRENGTH MPa (psi)

ULTIMATE LOAD N (Ibs)

ULTIMATE STRESS MPa (psi)

FINAL AREA sq. mm (sq. in.)% REDUCTION IN AREA

% ELONGATION

TYPE OF FRACTURE

TENSILE TEST

T1

12.6 (0.496)

125 (0.193)

50.8 (2.00)0.2% Offset

66 100

530

77 200

619

48.2

61

24

PartialCup& Cone

(14,900)

(76,900)

(17,400)

(89,800)

(0.075)

FS7AO-EM13K /

F48AO-EM13K

Reauirements

400 (58,000) minimum

480/660 (70,000/95,000)

22 minimum

We certify the test results in this report and that the specimen(s) were prepared and tested in accordance with therequirements of AWS A5.17/A5.17M - 97/ CSA W48.6 - 99 & AWS B4.0 - 98. The information regarding materialidentification (i.e. size, thickness, heat number, etc.) has been provided by the customer whose name appears onthis report.

Laboratory Test Conducted By:ve Rieberger, C.E.T.

4027 - 74StreetS.£.,O\LGARY, ALBERTAT2G3K6 PHONE: (403)262-7072 FAX: (403) 266-3769 Paae 1 of 1

I.~~UDWIG & ASSOCIATES LTD.

'iF' m (J U v n ) ACCREDITATION;;I BUREAU

LABORATORYTEST REPORT ~~~~~:~::;~~~ITED

Laboratory Test No.: C04-766.1Date: July 16,2004

CUSTOMER: Harbert's Products Inc.P.O. Box 418,501 South Cedar LaneGreencastl~: PA17225 -0418

Attention: Harvey Beck

WPS Number:

Material:

Thickness:

Electrode Class:

Flux Type:Electrode/Flux Class:

SAW-1

SA 36 (Ht. No.: 138844)

25.4 mm (1.00 in.)

EM13K Electrode (Lincoln L-50)Crushed 781

FS7AO - EM13KF48AO- EM13K

Thermal Condition: As Welded

Batch/Lot No.: 1070104

NOTCH-TOUGHNESS TEST

TYPE OF TEST: Charpy V-NotchTEST TEMPERATURE: -18°C (O°F)

SpecimenNumber

ORIENTATION:SPECIMEN SIZE:

Transverse10 x 10 mm

NotchLocation

F2.1F2.2F2.3F2.4F2.5

Weld MetalWeld MetalWeld MetalWeld MetalWeld Metal

57.066.444.758.363.7

(42.0)(49.0)(33.0)(43.0)(47.0)

Toughness test results meet the requirements of ANSI/AWS A5.17/A5.17M - 97, for FS7AO - EM13K /F48AO-EM 13K Electrode/Flux classification.

We certify the test results in this report and that the specimen(s) were prepared and tested in accordance with therequirements of AWS A5.17/A5.17M - 97 / CSA W48.6 - 99 & AWS 84.0 - 98. The information regarding materialidentification (i.e. size, thickness, heat number, etc.) has been provided by the customer whose name appears onthis report. .

Laboratory Test Conducted By:

4027 - 14 Street S.E., CALGARY, ALBERTA T2G 3K6 PHONE: (403) 262-7072 FAX: (403) 266-3169 Pace 1 of 1

WESTERN INSPECTION LTD.3231- 58thAVENUE,S.B.,CALGARYALBERTAT2COB4TBL:(403)279.4540FAX:(403)236-3043

Ludwig & Associates4027- 14St. SECalgary ABT26 3K6Tel: (403) 262-7072 Fax: (403) 266-3169

i __

Job Number: C04-766PO Number:

RADIOGRAPHIC EXAMINATION REPORT #tGV-209949

-l

Date of Exam:Job Location:Technicians:

AceCodes:Inspected:Material:Isotope:Focal spot:Curies:Degree:Processing:Units:

Wednesday,Jul 14 2004 .Customer s ShopLeo Brunet CGSBII, SHTII

AStlESee 11 Part C SFA5.17-2001Pre Heat Treatsa 36IR192

. .2x3 111150

100%Automaticin

Legend:---------. (Loading) S :: Singleo :: Double

T :: TripleACC:: AcceptREJ :: Reject

RETEST:: Retest1 :: Acceptable2 :: Slight3 :: Reject

Note: SFDDoes not include reinforcement

II (Result)

@ (Degree)

--.J1 TestInformation : FilmInformation : ResultInformation :I _. 00__ .. _II. 1__ ft_L ",." ",,,,..,, . , _ T. T" ~:... I.- A n'I'!"""""""II'lou C'rftM_

Test: .1 RT4-L 1B 20 12 19.0 1.277 S o - END D5-6EV-I4.5x17ACC

-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------

T.291hi S.S.O.F.D.,nominalwall thickness plus reinforcement.RT4 Longseams: T.291g) 5.0.0., upto 2" wall thickness,18",over2" wall thickness208 mi~imum.

Footage:Oty Code------------------------------------------------1 Ft L/1.0/00

~~~~-~~~~:~--~----------------------------Scott Istace C6SBLevel II SNTLevel11

Sign Here: ~-~-------------------------------

~tIPORIANT:Please.~ign AndRe~urn.the yellowCopy.to W~sternInspec~i~nLtd. ~.S.A.P~7/14/2004 10:46:47 AM.- .