+ All Categories
Home > Documents > Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for...

Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for...

Date post: 09-Jun-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
69
Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063 1/11/2012 Version 1.1
Transcript
Page 1: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and

Trending and Re-Tuning

PNNL-SA-85063 1/11/2012 Version 1.1

Page 2: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Data Analysis Pre-Re-Tuning Phase:

Air-Handling Units: Trend-data collection and analysis Re-tuning Phase:

Air-Handling Units: Occupied and Unoccupied Schedule

2 Chapter 5

Page 3: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Data Analysis

Key conditions to look for while analyzing the charts: Is there any unoccupied operation or 24/7 operation Is there a set back during unoccupied period Lower/higher than expected discharge-air temperature Excessive outdoor-air intake

During occupied periods During pre-heating/pre-cooling periods

Significant reheat during summer/cooling season Is the supply fan modulating (if VAV) Higher than normal static pressure Set point and static pressure resets Economizer is not utilized or not working properly

3 Chapter 5

Page 4: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Data Analysis

Enable unoccupied mode and night set back control Shut off units at night and weekend Turn off heating systems (for reheat only) during summer

When reheat system is shut off, room comfort may be maintained by increasing supply-air temperature – for constant volume units Do not turn heating off too early in the summer to avoid having to turn the system on and off repeatedly

Turn off systems during unoccupied hours Slow down systems during unoccupied/lightly and occupied hours

4 Chapter 5

Page 5: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Occupancy Scheduling

Shut off systems whenever possible Night unoccupied schedules Weekend unoccupied schedules Daytime no or low use unoccupied schedules

Auditorium, class rooms, conference rooms Includes lighting Includes specialized exhaust Do not restart too early

Use a startup schedule based on building needs Do not use fresh air during warm-up except last 30 minutes before occupancy, for flushing building

5 Chapter 5

Page 6: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Occupancy Scheduling (continued)

Shut off systems whenever possible Refrain from starting up system for the occasional nighttime user or weekend user Use bypass buttons

Unoccupied mode is a major cost saver Simple to implement Simple to track Simple to administer

Sometimes the least paid employee is the most costly Janitors working at night with all HVAC systems running, fresh at full design conditions and all lights on Is this required?

6 Chapter 5

Page 7: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Occupancy Scheduling (continued)

During unoccupied and lightly-occupied periods, run fan static pressure at ½ of normal set points, if it does not affect reheat controls

Check to make sure heated areas get full air in unoccupied modes Push unoccupied mode air to where it is needed

Set VAV boxes in interior zones to unoccupied with 0 air flow Set VAV boxes with reheat (typically on the perimeter) to a high air flow in unoccupied mode, so box will be 100% open during night cycling

Air gets to zones needing heat

7 Chapter 5

Page 8: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Occupancy Scheduling (continued)

Building electric consumption should show significant energy drop for nights/weekends

If set backs are active on all HVAC systems Base load versus peak loads should be at least 50% difference and as much as 70% with aggressive set backs

Trended data for zone temps should show 5-10oF deviations from occupied period set points when set backs are active during non-shoulder months

Winter zone temperatures should drop to 60-65oF and summer zone temperatures should rise to 80-85oF

8 Chapter 5

Page 9: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Occupancy Schedule (continued)

Trended data for discharge static pressures should show readings of 0 in. or at least 50% (half) of normal (occupied) static pressure readings If static pressure trend is not available, trended data for main supply/return fan status should indicate “OFF” during unoccupied periods Trended data for VAV boxes “occupied/unoccupied” status should indicate “unoccupied” during unoccupied periods Trended data for support systems (reheat pumps, reheat converters, reheat hot water boilers, chillers, towers, pumps, etc.) should indicate they are turning off at night, if all areas of the building are also shut down

9 Chapter 5

Page 10: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Occupancy Schedule (continued)

Unoccupied periods should include weekends, holidays and night hours during work week periods

If facility has sporadic use periods, this may require additional efforts to succeed at implementing set backs

Make sure the “tail” is not “wagging the dog” – janitors, special events, extreme weather events, overrides, etc. How does your organization respond to trouble calls (occupant complaints)? How do you respond? Is the response a “band-aid” or a long-term solution? Overrides on schedules are not long-term solutions

10 Chapter 5

Page 11: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Occupancy Schedule (continued)

Empower occupants to control their ventilation when they need it Most building designs provide occupants with local light switches for local lighting control Does your DDC system provide similar capabilities for ventilation so occupants can obtain ventilation automatically when they need it (motion sensors, timed overrides, Outlook scheduling of conference rooms or other “special” spaces)?

Consider adding outdoor-air temperature interlocks that “override” the occupied schedule, anytime the outdoor-air temperature exceeds the design parameters

This will eliminate overrides that are left in place and should only be active 2-4 weeks/year

Does your DDC system have “scheduling” capability? Do you know how it works?

Does your DDC system have “optimal start/stop” scheduling capability?

Are you using it? 11 Chapter 5

Page 12: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Night and Weekend Temperature Set back and Supply-Fan Cycling

Purpose: Determine whether night and weekend temperature set back is being used effectively Check for unusually frequent supply-fan cycling

Approach: For each monitored air-handler, plot supply fan status vs. time Look for off status during scheduled off times, for the served zones to be unoccupied (nights and weekends)

Potential issues to identify No night set back for heating or cooling No weekend set back for heating and cooling Excessive supply fan cycling

12 Chapter 5

Page 13: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Duct static pressure can be used to identify the system operation

13

Bad Operation Good Operation

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

5/28 6/2 6/7

Duc

t Sta

tic P

ress

ure

(in. w

.g.)

Time

Duct Static Pressure

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

11/25 11/26 11/27 11/28 11/29 11/30

Duc

t Sta

tic P

ress

ure

(in. w

.g.g

)

Time

Duct Static Pressure

Night and Weekend Temperature Set back and Supply- Fan Cycling (continued): Example use of Graphs

Chapter 5

Page 14: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Night and Weekend Temperature Set back and Supply-Fan Cycling (continued): Bad Example

Supply fan status vs. time – AHU runs 24/7(Example of bad operation) Supply fan status vs. time – Possibly OK but no weekend set back

14

0

0.2

0.4

0.6

0.8

1

1.2Su

pply

Fan

Sta

tus

(0=O

FF,1

=ON

) Supply Fan…

On

Off

0

0.2

0.4

0.6

0.8

1

1.2

Supp

ly F

an S

tatu

s (0

=OFF

,1=O

N) supply Fan…

On

Off

Chapter 5

Page 15: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Night and Weekend Temperature Set back and Supply-Fan Cycling (continued): Example use of Graphs

Supply fan status vs. time – Better – Longer night set back and weekend set back

15

0

0.2

0.4

0.6

0.8

1

1.2

Supp

ly F

an S

tatu

s (0

=OFF

,1=O

N) Supply Fan…

On

Off

Chapter 5

Page 16: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Checking Schedule with Supply Fan Static Pressure

16

-0.20

0.00

0.20

0.40

0.60

0.80

1.00

1.20

1.40

1.60Tu

e, 4

/5/2

011

Wed

, 4/6

/201

1

Thu,

4/7

/201

1

Fri,

4/8/

2011

Sat,

4/9/

2011

Sun,

4/1

0/20

11

Mon

, 4/1

1/20

11

Tue,

4/1

2/20

11

Wed

, 4/1

3/20

11

Thu,

4/1

4/20

11

Avg

AHU

1_D

uctS

tcPr

es

Avg AHU1_DuctStcPres Avg AHU1_DuctStcPresSp

Example of Good Operation

Chapter 5

Page 17: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Checking Schedule with Supply Fan Static Pressure

0.00

0.20

0.40

0.60

0.80

1.00

1.20

1.40

1.60Tu

e, 4

/5/2

011

Wed

, 4/6

/201

1

Thu,

4/7

/201

1

Fri,

4/8/

2011

Sat,

4/9/

2011

Sun,

4/1

0/20

11

Mon

, 4/1

1/20

11

Tue,

4/1

2/20

11

Wed

, 4/1

3/20

11

Thu,

4/1

4/20

11

Avg

AHU

3_D

uctS

tcPr

es

Avg AHU3_DuctStcPres Avg AHU3_DuctStcPresSp

17

Example of Good Operation

Chapter 5

Page 18: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Checking Schedule with Supply Fan Static Pressure

18

0.00

0.50

1.00

1.50

2.00

2.50Tu

e, 4

/5/2

011

Wed

, 4/6

/201

1

Thu,

4/7

/201

1

Fri,

4/8/

2011

Sat,

4/9/

2011

Sun,

4/1

0/20

11

Mon

, 4/1

1/20

11

Tue,

4/1

2/20

11

Wed

, 4/1

3/20

11

Thu,

4/1

4/20

11

Avg

AHU

4_D

uctS

tcPr

es

Avg AHU4_DuctStcPres Avg AHU4_DuctStcPresSp

Opportunities?

Chapter 5

Page 19: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Data Analysis

Pre-Re-Tuning Phase: Air-Handling Units: Trend-data collection and analysis of discharge-air temperature

Re-tuning Phase:

Air-Handling Units: Discharge-air temperature set point

Chapter 5 19

Page 20: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Data Analysis: Discharge-Air Temperature Set Point

Purpose Review discharge-air temperatures for the air-handlers Determine whether discharge-air temperatures are maintained relatively stable Determine whether the discharge-air temperatures are too cool or too warm

Approach For each air handler monitored, review plots of discharge-air temperature and discharge-air temperature set point vs. time and discharge-air temperature vs. discharge-air temperature set point Look for deviations between discharge-air temperatures and set points Look for unusually high (>70°F) or low (<55°F) discharge-air temperatures

20 Chapter 5

Page 21: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Data Analysis: Discharge-Air Temperature Set Point

Potential issues to identify Discharge-air temperature not meeting discharge-air temperature set point Unusually unsteady discharge-air temperatures Reset not being used for discharge-air temperature set point Discharge-air temperature set point too high or too low

21 Chapter 5

Page 22: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control

One of the most important variables in a HVAC system: Low discharge-air temperature will cause:

Overcooling Reheating in cooler zones Portable heaters in offices Drafts and cold complaints Extra load on the cooling plant Excess discharge-air pressure Excess energy in reheating the overcooled zones

22 Chapter 5

Page 23: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control (continued)

Discharge-air temperature needs to be set low enough to handle the peak cooling load

Summer weather peak Interior load peak Staffing peak Maybe 1% to 2% of the operating hours are at this condition, yet most systems run 100% of the time at this set point

Reheat makes up for all areas that are too cold from a lower than needed discharge-air temperature

23 Chapter 5

Page 24: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control (continued)

Discharge-air temperature can run as high as possible and still meet the cooling needs

VAV boxes can run at higher air flows Return-air can be warmer and help heat building Reheats will run a lot less Staff complaints go down due to less cold drafts Building is ventilated better

Reheat has to make up for all areas that are too cold from a lower than needed discharge-air temperature

24 Chapter 5

Page 25: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control (continued)

What is driving the current discharge-air temperature set point? Why is it set where it is?

Engineered setting per drawings before building was built Field engineer Building/facility manager Technician best guess Current weather conditions Loudest customer complaint Because that is where its always been, so it must be right ???????? ENERGY COST ???????

25 Chapter 5

Page 26: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control (continued)

Does the discharge-air set point vary with some input signals? > 55oF – < 70oF Set up a discharge-air temperature set point reset schedule based on the personality of the zones it feeds Examples:

Warmest 3 zones averaged For example reset, if average zone temperature is 76oF, then discharge-air temperature should be 55oF If average zone temperature is 72oF, discharge-air temperature can be as high as 65oF

Number of reheats running 10 out of 15 zones in heat, then the discharge-air temperature can be as high as 70oF 2 out of 15 zones in heat, then discharge-air can be as low as 55oF

Coolest perimeter zone Outdoor-air temperature

If outdoor-air temperature is 50oF, then the discharge-air is 70oF If outdoor-air temperature is 75oF, then the discharge-air is 55oF

26 Chapter 5

Page 27: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control (continued)

Occupant complaints (if many) could be a precursor to an improperly working (or non-functioning) discharge-air temperature control scheme Trended data for discharge-air temperatures that is “flat” or rarely varies is a strong indicator of a non-functioning discharge-air temperature “reset” control Trended data for discharge-air temperatures that show sharply falling temperatures well below set point that are coincidental to the chiller system starting and remain well below set point are indicative of a failed (leaking) cooling control valve Trended data for discharge-air temperatures that show sharply rising temperatures well above set point that are coincidental to the boiler/reheat system starting and remain well above set point are indicative of a failed (leaking) heating control valve

27 Chapter 5

Page 28: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control

Trended data for discharge-air temperature “reset” control that is working should show temperature set points that vary as the building “wakes up” in the morning hours and then changes as the building becomes occupied and continues to change during the late morning and early afternoon hours and continues to see changes due to changing outdoor ambient temperatures and solar loading. This can vary as much as 10 to 15oF over the course of the day Does your DDC system already calculate: warmest zone temperature, lowest zone temperature, average zone temperature?

If not, then it is doubtful that your DDC is set up to reset the discharge-air temperature set point based upon a feedback that reflects true building load conditions

Does your DDC system currently reset the discharge-air temperature set point using either outside-air temperature or return-air temperature? Preferred order to reset discharge-air temperature is from zone conditions, return-air temperature and then outside-air temperature

28 Chapter 5

Page 29: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control

Summer mode (for example, outdoor-air temperature >75oF ): Set discharge-air temperature set point at 55oF Shut off heating coil valve

Winter mode (for example, outdoor-air temperature <60oF): Set discharge-air temperature set point at 65oF, if less than 40% of zones require cooling If more zones call for cooling than heating, discharge-air temperature set point can be lowered to 55oF Shut off the cooling coil valve, if the freeze protection is not enabled

Heating and cooling valves can be closed when outdoor-air temperature is in between summer mode and winter mode

Chapter 5 29

Page 30: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Discharge-Air Temperatures: Example use of Graphs

Discharge-air temperature and discharge-air temperature set point vs. time – 3 days

30

Discharge/Discharge Set Point Temperature vs. Time

50

55

60

65

70

75

4/9/07 8:00AM

4/9/07 8:00PM

4/10/07 8:00AM

4/10/07 8:00PM

4/11/07 8:00AM

4/11/07 8:00PM

Time

Tem

pera

ture

(oF)

Discharge Discharge Set Point

Example of Good Reset Operation

Chapter 5

Page 31: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

Wed, 2/16/2011 Thu, 2/17/2011 Fri, 2/18/2011 Sat, 2/19/2011

Avg

AHU

1_Te

mpS

a

Avg

AHU

1_Te

mpS

aSp

Avg AHU1_TempSaSp Avg AHU1_TempSa

Air-handler Discharge-Air Temperatures: Example use of Graphs

Discharge-air temperature and discharge-air temperature set point vs. time – 3 days

31

Example of Bad Operation - No Reset (Constant day and night)

Daytime Daytime

Discharge-Air Temperature Set Point

Discharge-air Temperature

Chapter 5

Page 32: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

20

30

40

50

60

70

80

0

20

40

60

80

100

120

11/1/10 11/2/10 11/3/10 11/4/10 11/5/10 11/6/10 11/7/10 11/8/10

OAT

(deg

ree

F)

Tota

l Num

ber o

f Ter

min

al B

ox

VAV's # in Cooling and Heating Mode, OAT vs. Time# In Clg Mode # In Htg Mode OAT

Air-handler Discharge-Air Temperatures: Example use of Graphs

Opportunity to decrease the discharge-air temperature (total VAV terminal box number is 279)

32

VAV in cooling

VAV in Heating

OAT

Example of Bad Operation - No Reset Chapter 5

Page 33: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

20

30

40

50

60

70

80

0

20

40

60

80

100

120

11/15/10 11/16/10 11/17/10 11/18/10 11/19/10 11/20/10 11/21/10 11/22/10

OAT

(deg

ree

F)

Term

inal

Box

Num

ber

VAV's # in Cooling and Heating Mode, OAT vs. Time# In Clg Mode # In Htg Mode OAT

Air-Handler Discharge-Air Temperatures: Example use of Graphs

Opportunity to increase the discharge-air temperature when outdoor-air temperature (OAT) is lower than 50ºF (total VAV terminal box number is 108)

33

VAV in Heating

VAV in cooling

OAT

Example of Bad Operation - No Reset

Chapter 5

Page 34: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control

34

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

Wed

, 4/6

/11

12:0

0 A

M

Wed

, 4/6

/11

12:0

0 PM

Thu,

4/7

/11

12:0

0 A

M

Thu,

4/7

/11

12:0

0 PM

Fri,

4/8/

11 1

2:00

AM

Fri,

4/8/

11 1

2:00

PM

Avg

AHU

2_Te

mpS

aSp

Avg AHU2_TempSaSp Avg AHU2_TempSa

Discharge-Air Temperature

Discharge-Air Temperature Set Point

Chapter 5

Page 35: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control

35

0.00

20.00

40.00

60.00

80.00

100.00

120.00

140.00

Wed

, 4/6

/11

12:0

0 A

M

Wed

, 4/6

/11

12:0

0 PM

Thu,

4/7

/11

12:0

0 A

M

Thu,

4/7

/11

12:0

0 PM

Fri,

4/8/

11 1

2:00

AM

Fri,

4/8/

11 1

2:00

PM

Avg

AHU

3_Te

mpS

aSp

Avg AHU3_TempSaSp Avg AHU3_TempSa

Discharge-Air Temperature

Discharge-Air Temperature Set

Point

Chapter 5

Page 36: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Discharge-Air Temperature Control

36

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00W

ed, 4

/6/1

1 12

:00

AM

Wed

, 4/6

/11

12:0

0 PM

Thu,

4/7

/11

12:0

0 A

M

Thu,

4/7

/11

12:0

0 PM

Fri,

4/8/

11 1

2:00

AM

Fri,

4/8/

11 1

2:00

PM

Avg

AHU

4_Te

mpS

a

Avg AHU4_TempSa Avg AHU4_TempSaSp

Discharge-Air Temperature

Discharge-Air Temperature

Set Point

Chapter 5

Page 37: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Data Analysis: Static Pressure

Pre-Re-Tuning Phase: Air-Handling Units: Trend-data collection and analysis for duct static pressure

Re-tuning Phase:

Air-Handling Units: Duct static pressure

Chapter 5 37

Page 38: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Data Analysis: Static Pressure

Purpose: Determine whether the static pressure set point is too high or too low or if static pressure is changing over time Approach:

For each air handler, review a plot of the damper positions of all VAV units vs. time Look for situations where:

Most dampers are nearly closed during cooling – static pressure too high Several VAV boxes on an air handler have dampers fully open – static pressure is too low and VAV boxes are not able to meet zone loads – starved boxes Dampers are not modulating as conditions change – VAV boxes that are not being controlled or not responding to control signals

38 Chapter 5

Page 39: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Static Pressure Control

Does the static pressure vary with some input signals? Like discharge-air temperature, static pressure should follow the real load conditions

Too high and VAV boxes have trouble controlling High noise levels in ceiling or at diffusers coming from VAV box Extra load on air handler not required

Higher CFMs More chiller load More fan wear and belt wear Higher fan energy cost. horsepower varies with the CUBE of the speed

Ideally, VAV dampers should run in the 50% to 75% range (non-design conditions)

39 Chapter 5

Page 40: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Static Pressure Control

Static pressure control specifications taken directly from a vendor’s standard specifications VAV control

STATIC PRESSURE CONTROL: THE SUPPLY FAN WILL MODULATE TO MAINTAIN THE DISCHARGE STATIC PRESSURE SET POINT

Who determines set point? Normally a computer before the building is ever built!

Control contractors are not actively coding in intelligent control functions unless an engineer asks for it Engineers are designing to basic design conditions and are not concerned about system control in shoulder conditions

40 Chapter 5

Page 41: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Static Pressure Control (continued)

Use a reset schedule based on damper position Read all damper positions Sort by descending position, highest to lowest Reset discharge static to maintain the average of the 3rd highest to the 7th highest positions to about 75% open

Do not use failed dampers or outliers in calculations

Main idea is match control point to actual need Example would be systems that run at 0.5 in. in the morning and 2 in. in the afternoon when fully loaded

41 Chapter 5

Page 42: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Static Pressure Control (continued)

Example of cause and effect Discharge pressure transmitter failed

Fan failed at full speed Building owner determined not to fix it because tenants did not complaint Utility bill went up several thousands of dollars over a 1-year period

Utility bill is passed on to tenant Tenant finally complained about increase and then helped owner determine cause Owner did the $100 repair The utility bill dropped thousands of dollars!

42 Chapter 5

Page 43: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Static Pressure Control (continued)

Occupant complaints (if many) could be a precursor to an improperly working discharge static pressure control scheme Excess static pressure can result in excess air and cold drafts as well as high noise levels in office spaces from diffuser noise Excess supply fan static pressure can result in outside-air being “drawn” into the mixing box plenum section, via the exhaust damper If this is observed in field walk-downs, verify that the return fan is operating correctly; otherwise, excess supply static pressure should be one suspect

43 Chapter 5

Page 44: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Static Pressure Control (continued)

Trended data for static pressure control that is working should show static pressure varying

Set points that vary as the building “wakes up” in the morning hours and then changes as the building becomes occupied and continues to change during the late morning and early afternoon hours and continues to see changes due to changing outdoor ambient temperatures, solar loading and internal gains

If the static pressure control is constant, then the fan speed (load) should vary as noted above

44 Chapter 5

Page 45: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Static Pressure Reset Based on Terminal Box: Example of Good Operation

0

10

20

30

40

50

60

70

80

90

100

0

0.5

1

1.5

2

2.5

3

3.5

4

5/12 5/17 5/22 5/27 6/1 6/6 6/11 6/16 6/21 6/26 7/1

Out

door

air

Tem

pera

ture

(deg

ree

F)

Stat

ic P

ress

ure

(in. w

.g.)

Time

Static Pressure OAT

45

Static Pressure

Outdoor-Air Temperature

Example for Bad and Good Operation

Static Pressure before re-tuning and After re-tuning

Before re-tuning After re-tuning

Chapter 5

Page 46: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Static Pressure Reset Based on Terminal Box: Example of Good Operation

0

10

20

30

40

50

60

70

80

90

100

0

0.5

1

1.5

2

2.5

3

3.5

4

Out

door

air

Tem

pera

ture

(deg

ree

F)

Stat

ic P

ress

ure

(in. w

.g.)

Time

Static Pressure OAT

Example of Good Operation

Static Pressure Reset (lightly occupied building at night)

Chapter 5 46

Page 47: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

0.00

0.50

1.00

1.50

2.00

2.50

11/1/10 11/8/10 11/15/10 11/22/10

Duc

t Sta

tic P

ress

ure

(in. w

.c.)

Avg AHU1_DuctStcPresSp Avg AHU1_DuctStcPres

No Static Pressure Reset: Example of Bad Operation - Constant Day and Night

Duct static pressure and set point vs. time

47

Example of Bad Operation - No Reset

Static Pressure Static Pressure Set Point

Chapter 5

Page 48: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

No Static Pressure Reset: Example of Bad Operation

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

0

10

20

30

40

50

60

70

80

90

100

5/28 5/30 6/1 6/3 6/5 6/7 6/9 6/11

Duc

t Sta

tic P

ress

ure

(in. w

.g.g

)

Out

door

Air

Tem

prat

ure

(deg

ree

F)

Time

OAT Static Pressure Set Point Duct Static Pressure

48

Example of Bad Operation - No Reset

Outdoor Air Temperature

Static Pressure

Static Pressure Set Point

Duct static pressure and set point, and outdoor-air temperature vs. time

No night-time

setback

Chapter 5

Page 49: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler Data Analysis: Heating and Cooling

Pre-Re-Tuning Phase: Air-Handling Units: Trend-data collection and analysis of heating and cooling

Re-tuning Phase:

Air-Handling Units: Heating and cooling

Chapter 5 49

Page 50: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler: Heating and Cooling

Are the heating and cooling coils efficient? Clean Valves not leaking through

Check (touch) coil for temperature of pipes at air-handler penetrations Should be room temperature, if not active

Loops locked out at some outdoor-air temperature preventing heating and cooling at same time

Heating locked out above 50oF or lowest temperature building can do without heat Cooling locked out below 55oFor highest temperature building can do without cooling Critical on dual-duct and multi-zone systems

Balance point of building is critical when setting these lockouts

50 Chapter 5

Page 51: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handler: Heating and Cooling (continued)

Trended data for discharge-air temperatures that show sharply falling temperatures well below set point that are coincidental to the chiller system starting and remain well below set point are indicative of a failed (leaking) cooling control valve Trended data for discharge-air temperatures that show sharply rising temperatures well above set point that are coincidental to the boiler/reheat system starting and remain well above set point are indicative of a failed (leaking) heating control valve Trended data for discharge-air temperature that shows a heating valve open to maintain discharge-air set point with the economizer control on full re-circulation (or minimum outside air) and a mixed-air temperature that is above the discharge-air temperature, is indicative of a leaking chilled water valve (if the chiller system is active) If condensate is observed on un-insulated lines or exposed coil sections during times when mechanical cooling is not being called for by the control system or during times when outside-air temperature should be adequate for “free” cooling, then leaking cooling control valves should be suspected If heating and cooling loops come with outside-air temperature lockouts, but those lockout settings are set to abnormal values, this would indicate failed or leaking control valves that indicate simultaneous heating and cooling (energy intensive)

51 Chapter 5

Page 52: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Outdoor-air Lockouts for Heating and Cooling

Purpose: Determine whether the outdoor-air lockouts for heating and cooling are set to reasonable values Approach:

Use plots of heating and cooling set points vs. time to determine whether lockouts are set backwards – cooling lockout is lower than the heating lockout Use plots of heating and cooling valve positions to determine whether heating and cooling of the air stream are taking place at the same time

52 Chapter 5

Page 53: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Outdoor-Air Lockouts for Heating & Cooling (continued)

Potential issues to identify Air-handler heating and cooling coils operating simultaneously Heating and cooling lockouts possibly overlapping (need to be confirmed in control-code settings during on-site re-tuning) Unreasonable values are set for the heating and cooling lockouts

53 Chapter 5

Page 54: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Outdoor-Air Lockouts for Heating and Cooling: Example use of Graphs

Air-handler heating vs. cooling valve positions

54

Chilled Water vs Hot Water Valve Signals

0

10

20

30

40

50

60

70

80

90

100

0 10 20 30 40 50 60 70 80 90 100

Chilled Water Signal (%)

Hot

Wat

er S

igna

l (%

)

Worse

Bad

Chapter 5

Page 55: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Lockout for Cooling During Winter Season: Before and after Building Re-tuning

Heating coil valves and cooling coil valve signals vs. time

55

0

20

40

60

80

100

120

10/25 10/26 10/27

Coi

l Vla

ves

(%)

TIME

HWV CHWV

Before Building Re-tuning

Example of Good Operation Example of Bad Operation

0%

20%

40%

60%

80%

100%

120%

1/20 1/21 1/22 1/23 1/24 1/25 1/26Va

lve

Posi

tion

(%)

TIME

HWV

After Building Re-tuning

Chilled Water Valve Signal

Hot Water Valve Signal

Chapter 5

Page 56: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

0

10

20

30

40

50

60

70

80

90

100

0

10

20

30

40

50

60

70

80

90

100

Avg

AHU

_Vlv

_HeC

1_%

op

Avg

AHU

_Vlv

_CC

1_%

op

Avg AHU_Vlv_CC1_%op Avg AHU_Vlv_HeC1_%op

Example of Simultaneous Heating and Cooling: Bad Operation Heating and cooling coil valve signal vs. time

56

Example of Bad Operation

Chilled Water Valve Signal

Hot Water Valve Signal

Chapter 5

Page 57: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

20.00

30.00

40.00

50.00

60.00

70.00

80.00

0.00

20.00

40.00

60.00

80.00

100.00

120.00

OAT

(deg

ree

F)

Valv

e Po

sitio

n (%

)

Avg AHU_Vlv_CC1_%op Avg AHU_Vlv_HeC1_%op Avg Bldg1_TempOa

Example of Simultaneous Heating and Cooling: Bad Operation

Heating and cooling coil valve signal, and outdoor-air temperature vs. time

57 Example of Bad Operation

Chilled Water Valve Signal

Hot Water Valve Signal

Outdoor-Air Temperature

Chapter 5

Page 58: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

30

40

50

60

70

80

90

0

20

40

60

80

100

120

OAT

(deg

ree

F)

Valv

e Po

sitio

n (%

)

Avg AHU_Vlv_CC1_%op Avg AHU_Vlv_HeC1_%op Avg Bldg1_TempOa

Example of Simultaneous Heating and Cooling: Bad Operation

Heating and cooling coil valve signals, and outdoor-air temperature vs. time

58

Example of Bad Operation

Hot Water Valve Signal Chilled Water Valve

Signal Outdoor-Air Temperature

Chapter 5

Page 59: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Minimum Outdoor-Air

Pre-Re-Tuning Phase: Air-Handling Units: Trend-data collection and analysis of minimum outdoor air

Re-tuning Phase:

Air-Handling Units: Minimum outdoor air operations

Chapter 5 59

Page 60: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Minimum Outdoor-Air Operations

Purpose Review minimum outdoor-air operations Determine whether sufficient outdoor-air is being supplied for ventilation Determine whether more outdoor-air than needed is being brought in at times (e.g., when the outdoor-air temperature < 40°F or > 60°F or when the zones served are unoccupied) Determine whether outdoor-air dampers close during night and weekend set back and during startup mode in the morning

60 Chapter 5

Page 61: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Minimum Outdoor-Air Operations (continued)

Approach For each air-handling unit with air-side economizer, review plots:

Outdoor-air fraction (OAF) vs. time Outdoor-air damper and occupancy mode vs. time Outdoor-air fraction vs. fan speed (if available)

Determine if OAF > minimum OAF for ventilation when the system is not economizing Determine whether outdoor-air ventilation is being provided when the building is unoccupied and ventilation is not required for some other reason, especially when in the heating mode and when conditions are not favorable of economizing in cooling mode If OAF and fan speed are tracking each other, it is an indication of return-air problems 20% damper position is never 20% outdoor air

61 Chapter 5

Page 62: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Minimum Outdoor-Air Operations (continued)

Potential issues to identify Insufficient outdoor-air ventilation provided – minimum outdoor-air fraction (OAF) is too low Too much outdoor-air ventilation provided when the air-handler is not economizing Too much outdoor-air ventilation provided during unoccupied times (nights and weekends, during set back)

Use air fraction to find % of outdoor-air Works if air is mixed relatively evenly OAF = ((Return-Mixed)/(Return-Outdoor))*100 Add into code for all air handlers and track history

Especially schools and other public spaces

Use CO2 sensors whenever possible for areas with changing staff loads and larger spaces (conference rooms, auditoriums, etc)

Infiltration may satisfy ventilation needs without outdoor-air dampers being open

62 Chapter 5

Page 63: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Outdoor-Air Makeup (continued)

Does your DDC system have separate outdoor-, return- and mixed-air temperature sensors? Does your DDC system use these values to calculate outdoor-air fractions?

63 Chapter 5

Page 64: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Outdoor-Air Makeup

20% damper is never 20% air flow Pressure differential across outdoor-air damper is more important than damper position No pressure differential leads to no flow High delta leads to high flow

64 Chapter 5

Page 65: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Minimum Outdoor-Air Operations: Example use of Graphs

Outdoor-air fraction and temperature, and damper position vs. time: building occupied 24/7

65

0

20

40

60

80

100

120

4/9/0712:45 PM

4/10/0712:45 AM

4/10/0712:45 PM

4/11/0712:45 AM

4/11/0712:45 PM

4/12/0712:45 AM

4/12/0712:45 PM

Time

Dam

per P

ositi

on S

igna

l and

O

utdo

or A

ir Fr

actio

n (%

)

0.0

20.0

40.0

60.0

80.0

100.0

120.0

Out

door

-Air

Tem

pera

ture

(o F)

Damper SignalOutdoor Air FractionOutdoor-Air Temperature

Outdoor-Air Fraction/Damper Position Signal/ Outdoor Air Temperature vs. Time

Chapter 5

Page 66: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

Air-Handling Unit: Minimum Outdoor-Air Operations: Example use of Graphs

Outdoor-air fraction and temperature, and damper position vs. time: building occupied 12 h/d

66

0

20

40

60

80

100

120

4/9/07 12:45PM

4/10/0712:45 AM

4/10/0712:45 PM

4/11/0712:45 AM

4/11/0712:45 PM

4/12/0712:45 AM

4/12/0712:45 PM

Time

0.0

20.0

40.0

60.0

80.0

100.0

120.0

Out

door

-Air

Tem

pera

ture

(o F)

Damper SignalOutdoor Air FractionOccupancyOutdoor-Air Temperature

Outdoor-Air Fraction/Damper Position Signal/ Outdoor Air Temperature vs. Time

Dam

per P

ositi

on S

igna

l, O

ccup

ancy

, and

O

utdo

or-A

ir Fr

actio

n (%

)

Chapter 5

Page 67: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

10.00

20.00

30.00

40.00

50.00

60.00

70.00

0.00

20.00

40.00

60.00

80.00

100.00

120.00

OAT

(deg

ree

F)

Avg

AHU

_Dm

pr_O

A2_

%op

Avg AHU_Dmpr_OA2_%op Avg Bldg1_TempOa

Air-Handling Unit: Minimum Outdoor-Air Operations: Normal Operation

Outdoor-air damper vs. time

67

Minimum Outdoor-Air Damper Position = 15%

Outdoor-Air Temperature

Outdoor-Air Damper

Chapter 5

Minimum Outdoor-Air

Damper Position

Page 68: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

10.00

20.00

30.00

40.00

50.00

60.00

70.00

0.00

20.00

40.00

60.00

80.00

100.00

120.00

OAT

(deg

ree

F)

Avg

AHU

_Dm

pr_O

A2_

%op

Avg AHU_Dmpr_OA3_%op Avg Bldg1_TempOa

Air-Handling Unit: High Minimum Outdoor-Air Damper Position

Outdoor-air damper vs. time

68

Outdoor-Air Temperature

Outdoor-Air Damper

Chapter 5

Minimum Outdoor-Air

Damper Position

High Minimum Outdoor-Air Damper Position = 30%

Page 69: Large Commercial Buildings: Re-tuning for Efficiency · Large Commercial Buildings: Re-tuning for Efficiency Air Handling Units: Pre-Re-Tuning and Trending and Re-Tuning PNNL-SA-85063

QUESTIONS? www.pnnl.gov/buildingretuning

Chapter 5 69


Recommended