+ All Categories
Home > Documents > lec5(2)(1) power system

lec5(2)(1) power system

Date post: 07-Jul-2018
Category:
Upload: parth
View: 218 times
Download: 0 times
Share this document with a friend

of 42

Transcript
  • 8/18/2019 lec5(2)(1) power system

    1/42

    POWER SYSTEMS ILecture 5

    06-88-590-68

    Electrical and Computer Engineering

    University of Windsor 

    Dr. Ali Tahmasebi

  • 8/18/2019 lec5(2)(1) power system

    2/42

    1

    Fault Analysis

    l The cause of electric power system faults is

    insulation breakdown

    l This breakdown can be due to a variety of different

    factors

     –  lightning

     –  wires blowing together in the wind 

     –  animals or plants coming in contact with the wires

     –  salt spray or pollution on insulators

  • 8/18/2019 lec5(2)(1) power system

    3/42

    2

    Fault Types

    l There are two main types of faults

     –  symmetric faults: system remains balanced; these faults

    are relatively rare, but are the easiest to analyze so we’ll

    consider them first. –  unsymmetric faults: system is no longer balanced; very

    common, but more difficult to analyze

    l The most common type of fault on a three phase

    system by far is the single line-to-ground (SLG),followed by the line-to-line faults (LL), double line-

    to-ground (DLG) faults, and balanced three phase

    faults

  • 8/18/2019 lec5(2)(1) power system

    4/42

    3

    Lightning Strike Event Sequence

    1. Lighting hits line, setting up an ionized path to

    ground 

    l 30 million lightning strikes per year in US!

    l a single typical stroke might have 25,000 amps, with arise time of 10  ms, dissipated in 200  ms.

    l multiple strokes can occur in a single flash, causing the

    lightning to appear to flicker, with the total event

    lasting up to a second.

    2. Conduction path is maintained by ionized air after 

    lightning stroke energy has dissipated, resulting in

    high fault currents (often > 25,000 amps!)

  • 8/18/2019 lec5(2)(1) power system

    5/42

    4

    Lightning Strike Sequence, cont’d

    3. Within one to two cycles (16 ms) relays at both

    ends of line detect high currents, signaling circuit

     breakers to open the line

    l nearby locations see decreased voltages

    4. Circuit breakers open to de-energize line in an

    additional one to two cycles

    l  breaking tens of thousands of amps of fault current is no

    small feat!

    l with line removed voltages usually return to near normal

    5. Circuit breakers may reclose after several seconds,

    trying to restore faulted line to service

  • 8/18/2019 lec5(2)(1) power system

    6/42

    5

    Fault Analysis

    l Fault currents cause equipment damage due to both

    thermal and mechanical processes

    l Goal of fault analysis is to determine the

    magnitudes of the currents present during the fault –  need to determine the maximum current to insure devices

    can survive the fault

     –  need to determine the maximum current the circuit

     breakers (CBs) need to interrupt to correctly size the CBs

  • 8/18/2019 lec5(2)(1) power system

    7/42

    6

    RL Circuit Analysis

    l To understand fault analysis we need to review the

     behavior of an RL circuit

    Before the switch is closed obviously i(t) = 0.When the switch is closed at t=0 the current will

    have two components: 1) a steady-state value

    2) a transient value

      = 2  sin ( + )

  • 8/18/2019 lec5(2)(1) power system

    8/42

    7

    RL Circuit Analysis, cont’d

    1. Steady-state current component (from standard 

     phasor analysis):

        =

    2 V sin ( + − )

    Where    =    +      =    +  and    = tan  

    The rms value of this sinusoidal current is:

     =

  • 8/18/2019 lec5(2)(1) power system

    9/42

    8

    RL Circuit Analysis, cont’d

    2. Exponentially decaying dc current component (offset

    current):     =

    Where T is the time constant,

      =

    [sec]

    The value of C1 is determined from the initial conditions:

      0 = 0 =     +     =2 sin ( + − )

      +

    At t = 0 we get    = −     sin ( − ) which depends on  aand it has a maximum at  = −

  • 8/18/2019 lec5(2)(1) power system

    10/42

    9

    RL Circuit Analysis, cont’d

  • 8/18/2019 lec5(2)(1) power system

    11/42

    10

    RL Circuit Analysis, cont’d

    Hence i(t) is a sinusoidal superimposed on a decaying dc

    current. The magnitude of idc(0) depends on when the switch

    is closed.

    For fault analysis we are only concerned with the worst case

    which is when the current is at its maximum.

  • 8/18/2019 lec5(2)(1) power system

    12/42

    11

    RL Circuit Analysis, cont’d

    Maximum value of the offset current idc is at   = − :

    max  =  =2   

      = 2 

    Then the fault current with largest dc offset is:

      = 2    sin   −   +   [A]

  • 8/18/2019 lec5(2)(1) power system

    13/42

    12

    RL Circuit Analysis, cont’d

    This current is not a periodic function so we can’t formally

    define an rms value. However, as an approximation define:

        =      +      =      + 2  

    =

      1 + 2

     [A]

  • 8/18/2019 lec5(2)(1) power system

    14/42

    13

    If    =  =  , and    =

    where  t is time in cycles, then:

        =

    RL Circuit Analysis, cont’d

    Where K (t) is the asymmetry factor and     = 1 + 2 

    Then   max     = 3 which is at  t = 0.

  • 8/18/2019 lec5(2)(1) power system

    15/42

    14

    Generator Modeling During Faults

    l During a fault the only devices that can contribute

    fault current are those with energy storage

    l Thus the models of generators (and other rotating

    machines) are very important since they contributethe bulk of the fault current.

    l General model of one phase of a 3-phase

    synchronous machine for fault analysis:

      = 2  sin ( + )

  • 8/18/2019 lec5(2)(1) power system

    16/42

    15

    Generator Modeling, cont’d

    "d 

    'd 

    The time varying reactance is typically approximated 

    using three different values, each valid for a different

    time period:

    X direct-axis subtransient reactance

    X direct-axis transient reactance

    X dire

    =

    =

    = ct-axis synchronous reactance

  • 8/18/2019 lec5(2)(1) power system

    17/42

    16

    Generator Modeling, cont’d

    Instantaneous ac fault current for balanced 3-phase fault on

    the generator terminal:

      = 2 1  −

      1   

    + 1   −  1   

    + 1    sin ( + − 2) 

    Where Eg is the rms, line-to-neutral terminal voltage of 

    unloaded generator before fault.

  • 8/18/2019 lec5(2)(1) power system

    18/42

    17

    Generator Modeling, cont’d

    • At t = 0 (fault moment):     0 =   = which is

    called subtransient fault current and its duration depends

    on  (direct-axis subtransient time constant which isusually around 0.035 seconds)

    • As time passes (t >> ):   decays and the rms faultcurrent is:    = which is called transient fault currentand its duration depends on 

    (direct-axis transient timeconstant which is usually around 1 to 2 seconds)

    • As time passes even more (t >> ): steady-state acfault current becomes:     ∞   =   =

  • 8/18/2019 lec5(2)(1) power system

    19/42

    18

    Generator Modeling, cont’d

    • Maximum dc offset current for each phase (this max.

    happens at a = 0):

    ,     =

    2   

     

      = 2

     

     

    Where TA is the armature time constant and is usually

    around 0.2 seconds.

     NOTE: ,  , ,,  and  are provided by thegenerator manufacturer.

    • Total short circuit current will be   =     + ()

  • 8/18/2019 lec5(2)(1) power system

    20/42

    19

    Generator Short Circuit ac Current

    22

    2

  • 8/18/2019 lec5(2)(1) power system

    21/42

    20

    Generator Short Circuit Example

    l A 500 MVA, 20 kV, 3f  is operated with an internal

    voltage of 1.05 pu. Assume a solid 3f  fault occurs

    on the generator's terminal and that the circuit

     breaker operates after three cycles. Determine thefault current. Assume

    " '

    " '

    A

    0.15, 0.24, 1.1 (all per unit)

    0.035 seconds, 2.0 seconds

    T 0.2 seconds

    d d d 

    d d 

     X X X 

    T T 

    = = =

    = =

    =

  • 8/18/2019 lec5(2)(1) power system

    22/42

    21

    Generator S.C. Example, cont'd

    2.0

    ac

    0.035

    ac

    6 base ac3

    0.2DC

    Substituting in the values

    1 1 1

    1.1 0.24 1.1( ) 1.05

    1 10.15 0.24

    1.05(0) 7 p.u.0.15

    500 10I 14,433 A (0) 101,000 A3 20 10

    I (0) 101 kA 2 143 k  

    e

     I t 

    e

     I 

     I 

    e

    -

    -

    é ùæ ö+ - +ç ÷ê úè ø

    =   ê ú

    æ öê ú-ç ÷ê úè øë û

    = =

    ´= = =´

    = ´ = RMSA I (0) 175 kA=

    157

  • 8/18/2019 lec5(2)(1) power system

    23/42

    22

    Generator S.C. Example, cont'd

    0.052.0

    ac0.050.035

    ac

    0.05

    0.2DC

    RMS

    Evaluating at t = 0.05 seconds for breaker opening

    1 1 1

    1.1 0.24 1.1(0.05) 1.05

    1 10.15 0.24

    (0.05) 70.8 kA

    I (0.05) 143 kA 111 k A

    I (0.05

    e

     I 

    e

     I 

    e

    -

    -

    -

    é ùæ ö+ - +ç ÷ê úè ø

    =   ê ú

    æ öê ú-ç ÷ê úè ø   û

    =

    = ´ =2 2

    ) 70.8 111 132 kA= + =

    = 4.92 p.u.

  • 8/18/2019 lec5(2)(1) power system

    24/42

    23

    Network Fault Analysis Simplifications

    l To simplify analysis of symmetrical fault currents

    in networks we'll make several simplifications:

    1. Transmission lines are represented by their series

    reactance

    2. Transformers are represented by their leakage

    reactances

    3. Synchronous machines are modeled as a constant

    voltage behind direct-axis subtransient reactance

    4. Induction motors are ignored if small (

  • 8/18/2019 lec5(2)(1) power system

    25/42

    24

    Network Fault Example

    For the following network assume a fault on the

    terminal of the generator; all data is per unit

    except for the transmission line reactance

    2

    19.5Convert to per unit: 0.1 per unit

    138100

    line X    = =

    generator has 1.05

    terminal voltage &

    supplies 100 MVAwith 0.95 lag pf 

  • 8/18/2019 lec5(2)(1) power system

    26/42

    25

    Network Fault Example, cont'd

    Faulted network per unit diagram

    *'a

    To determine the fault current we need to first estimate

    the internal voltages for the generator and motor For the generator 1.05, 1.0 18.2

    1.0 18.20.952 18.2 E 1.103 7.1

    1.05

    T G

    Gen

    V S 

     I 

    = = Ð °

    Ðæ ö= = Ð - ° = Ðç ÷

    è ø

  • 8/18/2019 lec5(2)(1) power system

    27/42

    26

    Network Fault Example, cont'd

    The motor's terminal voltage is then

    1.05 0 - (0.9044 - 0.2973) 0.3 1.00 15.8

    The motor's internal voltage is

    1.00 15.8 (0.9044 - 0.2973) 0.2

    1.008 26.6

    We can then solve as a linear circuit:

    1I

     j j

     j j

    Ð ´ = Ð -

    Ð - °- ´

    = Ð - °

    = .103 7.1 1.008 26.60.15 0.5

    7.353 82.9 2.016 116.6 9.09

     j j

     j

    Ð ° Ð - °+

    = Ð - °+ Ð - °=

  • 8/18/2019 lec5(2)(1) power system

    28/42

    27

    Fault Analysis Solution Techniques

    l Circuit models used during the fault allow the

    network to be represented as a linear circuit

    l There are two main methods for solving for fault

    currents:1. Direct method: Use prefault conditions to solve for the

    internal machine voltages; then apply fault and solve

    directly

    2. Superposition: Fault is represented by two opposingvoltage sources; solve system by superposition

     –  first voltage just represents the prefault operating point

     –  second system only has a single voltage source

  • 8/18/2019 lec5(2)(1) power system

    29/42

    28

    Superposition Approach

    Faulted Condition

    Exact Equivalent to Faulted Condition

    Fault is represented 

     by two equal and opposite voltage

    sources, each with

    a magnitude equal

    to the pre-fault voltage

  • 8/18/2019 lec5(2)(1) power system

    30/42

    29

    Superposition Approach, cont’d

    Since this is now a linear network, the faulted voltages

    and currents are just the sum of the pre-fault conditions

    [the (1) component] and the conditions with just a single

    voltage source at the fault location [the (2) component].

    Pre-fault (1) component equal to the pre-fault

     power flow solution, where obviously the pre-fault

    “fault current is zero:

     I g(1) = I  L = pre-

    fault generator 

    current (usually

    very small

    compared to I  f )

  • 8/18/2019 lec5(2)(1) power system

    31/42

    30

    Superposition Approach, cont’d

    Fault (2) component due to a single voltage source

    at the fault location, with a magnitude equal to the

    negative of the pre-fault voltage at the fault location.

    (1) (2) (1) (2)

    (1) (2) (2)

    I

    0

    gg g m m m

     f    f f f 

     I I I I I 

     I I I I 

    = + = +

    = + = +

  • 8/18/2019 lec5(2)(1) power system

    32/42

    31

    Two Bus Superposition Solution

    (1) (1)

    (2) f 

    (2) f 

    (2)

    Before the fault we had E 1.05 0 ,

    0.952 18.2 and 0.952 18.2

    Solving for the (2) network we get

    E 1.05 07

     j0.15 j0.15

    E 1.05 02.1

     j0.5 j0.5

    7 2.1 9.1

    0.952

    g   m

    g

    m

     f 

    g

     I I 

     I j

     I j

     I j j j

     I 

    = Ð °

    = Ð - ° =- Ð -

    Ð °= = =-

    Ð °= = =-

    = - - =-

    = Ð 18.2 7 7.35 82.9 j- °- = Ð - °

    This matches

    what we

    calculated 

    earlier 

  • 8/18/2019 lec5(2)(1) power system

    33/42

    32

    Extension to Larger Systems

    Superposition can be easily extended to larger systems:

    Y bus . E = I

    WhereY bus : positive-sequence bus admittance matrix

    E : vector of bus voltages

    I : vector of current sources

    If we define:   Z bus

    = (Y bus

    )-1 then:

    Z bus . I = E

  • 8/18/2019 lec5(2)(1) power system

    34/42

    33

    Extension to Larger Systems

    General form of Y bus :

    § Diagonal elements yii = sum of all admittancesconnected to bus ‘i’ (self-admittance elements)

    § Off-diagonal elements yij = - (sum of admittancesconnected between buses ‘i’ and  ‘j’ )

    ü In large power systems,  Y bus is a sparse matrix (mostelements are zero)

  • 8/18/2019 lec5(2)(1) power system

    35/42

    34

    Extension to Larger Systems

    Assuming the fault happens at bus n then the element n of the vector I(2) is: In =  - If 

    ² (the negative sign indicates

    that the current is flowing away from bus n ).

    • Other elements of vector I(2) are all zero (since there is

    only one source at bus n ).

    • We also know that En(2) =  -Vf 

    ( Vf = voltage at the fault location before fault happened)

    This equation only needs to be solved for the fault circuit (2):

    Z bus(2) . I(2) = E(2)

  • 8/18/2019 lec5(2)(1) power system

    36/42

    35

    Calculating Fault Current

        ⋯     ⋯

    ⋮⋮

    ⋮⋮

    ⋮ ⋮…   ⋮ ⋮

    …  

    0

    0

    ⋮−⋮0

    =

    ()()

    ⋮−⋮

    ()

    So for a power system with a total of  N  buses:

    → − = −   →    =  Z nn is known as the driving point impedance.

  • 8/18/2019 lec5(2)(1) power system

    37/42

    36

    Calculating Bus Voltages

    • To calculate voltage at any bus k in circuit (2):

    () =    −   = −  

     Z kn is known as the transfer point impedance.

    If pre-faults load currents are assumed to be zero (sincethey are very small compared to I  f )  ® () = then:

     = −  +  =  1 −

     

    • To find bus voltages, use superposition:

     = () + ()

  • 8/18/2019 lec5(2)(1) power system

    38/42

    37

    3-Generator System Fault Example

    g1 2 3

    For simplicity assume the system is unloaded 

     before the fault with

    E 1.05 0

    Hence all the prefault currents are zero.

    g g E E = = = Ð °

  • 8/18/2019 lec5(2)(1) power system

    39/42

    38

    3-Generator System Fault Example

    15 10 0

    10 20 5

    0 5 9

    bus   j

    -é ùê ú= -ê ú

    -ê úû

    Y

    115 10 0

    10 20 5

    0 5 9

    0.1088 0.0632 0.0351

    0.0632 0.0947 0.0526

    0.0351 0.0526 0.1409

    bus Z j

     j

    --é ù

    ê ú= -ê ú

    -ê úë û

    é ùê ú=ê úê úû

  • 8/18/2019 lec5(2)(1) power system

    40/42

    39

    1

    (2)

    1.05For a fault at bus 1 we get I 9.6

    0.1088

    0.1088 0.0632 0.0351 9.6

    0.0632 0.0947 0.0526 0

    0.0351 0.0526 0.1409 0

    1.05 0

    0.60 00.337 0

     f  j I  j

     j

     j

    -= = =-

    -

    é ùé ù

    ê úê ú= ê úê úê úê úë ûë û

    - Ð °é ùê ú

    = - Ð °ê ú- Ð °ê úû

    V

    3-Generator System Fault Example

    ¬ Bus voltages at fault circuit (2)

  • 8/18/2019 lec5(2)(1) power system

    41/42

    40

    3-Generator System Fault Example

    1.05 0 1.05 0 0 0

    1.05 0 0.606 0 0.444 0

    1.05 0 0.337 0 0.713 0

    Ð ° - Ð ° Ð °é ù é ù é ùê ú ê ú ê ú= Ð ° + - Ð ° = Ð °ê ú ê ú ê ú

    Ð ° - Ð ° Ð °ê ú ê ú ê úû ë û ë û

    V

  • 8/18/2019 lec5(2)(1) power system

    42/42

    41

    Circuit Breaker and Fuse Selection

    Study section 7.5 of “Glover” (Posted on course website)


Recommended