+ All Categories
Home > Documents > Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials –...

Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials –...

Date post: 24-Sep-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
42
Heating with Heat Pumps Lessons from EST Field Trials & Electricity Network Studies 27 th September 2010 Dave A Roberts
Transcript
Page 1: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Heating with Heat PumpsLessons from EST Field Trials &

Electricity Network Studies

27th September 2010Dave A Roberts

Page 2: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

22

1. Why Heat Pumps?2. What is a Heat Pump? 3. Heat Pump Characteristics4. EST Field Trials – some practical issues5. MCS Guidance6. Network Impacts7. Future studies8. Conclusions

Heating with Heat Pumps

Page 3: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

1. Why Heat Pumps

• Decarbonising domestic heating – One of major challenges in meeting CO2 targets

• Heat Pumps a promising option– Assuming low carbon electricity supply

• DECC estimates of 60 – 90% houses by 2050– Planning to introduce incentives (RHI)

• But currently only limited one-off “Premium Payments”

• Rapid growth required

3

Page 4: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

4

Growth Scenarios

Page 5: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

2. What is a Heat Pump

5

Presenter
Presentation Notes
Take in low temperature heat at the evaporator Add some electricity (to drive the heat pump compressor) Reject heat at the condenser to provide Central Heating and Direct Hot Water (DHW)
Page 6: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

6

Heat Pump performance

• Measured as Coefficient of Performance

• Dimensionless– kWthermal / kWelectrical - instantaneous– kWhthermal / kWhelectrical - more usual & more useful

• Often called System Efficiency – includes pumps & fans etc.

Presenter
Presentation Notes
Strictly speaking COP is an instantaneous kW/kW value – but its commonly used for kWh/kWh over a period System Efficiency (SE) takes account of the electricity used by fans and pumps and in some definitions uses the heat delivered (so CH and DHW used) rather than the heat output of the heat pump. Seasonal Performance Factor (SPF) is another term you may hear – basically SE but over a whole season
Page 7: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Types of Heat Pump

• Ground-source• Air-source• Water source

• Air to air • air-conditioning

hydronicRadiators

Under-floorheating

• Ventilation• Mainly exhaust air

7

Presenter
Presentation Notes
Hydronic = water distributed CH Air-to-air is widely used in commercial air-con. Some domestic. Could have a big market in houses, but are alien to the UK plumber (require refrigeration skills) and can easily be used for cooling (so is not encouraged from an energy use perspective). Very cheap options now available (L&G ~ £400 for 4kW) – mass market. No reason long term why ASHP (hydronic) should not be this price Try and avoid talking about exhaust air heat pumps – they are currently getting a bad press. They are difficult to get right because they really on the heat available from the ventilation air being enough to heat the house (when heat pumped up to a higher temperature). Danger of over ventilating the house or using loads of back-up direct electric heat
Page 8: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Under-floorheating coils

Heat pump

Ground loop

Ground Source

Ice Energy

Ice Energy

8

Presenter
Presentation Notes
3 typical ground loop collectors – bore hole, slinky and panel Bore hole 60 to 100m deep – usually more than one (test house 40 & 60m for a 4 bed detached ~ 5kW design load) Slinkies & “panels” 1.5 to 2.5m deep trenches – lots of garden space required
Page 9: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Air-source

9

Presenter
Presentation Notes
From one of our field trial sites – small semi-detached/terraced bungalows
Page 10: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

10

Air Source or Ground Source

+ Lower capital cost+ Simpler to install- Appearance - Some external noise- Performance sensitive to ..outside temperature

- Higher capital cost- Disruption during installation++ Visually unobtrusive+ Quiet++ Performance less (not) sensitive…..to outside temperature

Air Source Ground Source

Presenter
Presentation Notes
Appearance – some very ugly ASHP, though some more aesthetically pleasing GSHP & ambient temperature – bore holes not sensitive to To, horizontal are but much less so than ASHP
Page 11: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

3. Heat Pump Characteristics

• Very different from a boiler• Performance very sensitive to source and sink

temperatures• the Air or Ground temperature (source)• the Heat Emitter temperatures (sink)

• Installers & Users need to understand this

11

Presenter
Presentation Notes
Boilers are robust in that you can get good performance with a less than ideal Central heating system. The effect of flow temperature on boiler efficiency is small (relative to that for heat pumps)
Page 12: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

12

COP curve*

Illustrative example: GSHP brine at 0oC

* COP of installed system

Presenter
Presentation Notes
Flow temperature = temperature of heat leaving the heat pump (and going to the Central Heating or to produce DHW) Data used is a manufacturer’s 5kWthermal GSHP data, with an additional 100W added for the ground loop pump EU definition of HP & renewable energy COP > ~ 2.8 DECC will use this for RHI
Page 13: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

13

Energy Use Curve

Illustrative example: GSHP brine at 0oC

Electricity units to deliver 100 units of heat

Presenter
Presentation Notes
Perhaps more powerful to use electrical energy required to deliver a given quantity of heat (reciprocal of the COP). Makes it very clear that as the flow temperature increase, so does the electricity use – and by large amounts (nearly doubles between 35 and 60) e.g. to deliver 100 kWh of heat, at 45oC, the heat pump input is 31 kWh electric
Page 14: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

14

Air Source

Illustrative example

Electricity units to deliver 100 units of heat

Presenter
Presentation Notes
Air source is sensitive to outside air temperature – both in terms of energy use and capacity (next slide). Slide show curves for air temperatures of -10, 0 and +10oC
Page 15: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

15

Air Source - capacity

Illustrative example

Presenter
Presentation Notes
Most manufacturers quote a nominal capacity at 7oC air on and 35oC water flow. That’s the 100% point on the graph. Big fall in capacity as the ambient air cools (just when you need the capacity!) Increasingly, ASHPs are using variable speed drives which can over come this problem to some extent (over-speeding as well as reducing speed) Thus, a heat pump in Scotland will be bigger than one in Cornwall for the same house
Page 16: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

4. EST Field Trials

• Phase 1 ~ 80 houses– Mix of ASHP & GSHP – Results generally disappointing but explainable

• Phase 2 ~ 50 houses– Improvements to:

• Systems (including replacing heat pump)• Instrumentation

– Monitoring now finished• Results to be discussed with manufacturers next month• Public report ~ April 2013

16

Presenter
Presentation Notes
Most of the 50 Phase 2 sites were in Phase 1 (5 new sites) Semi clusters – Aberdeen, Yorkshire, Cheshire, Staffs, Cornwall, Gloucester
Page 17: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

17

Some learning points from Phase 1• Heat emitter temperatures

– Generally too high for good performance• A few low ones (usually under-floor heating)

– Scope for improvement• “Over-sized” radiators• Fanned radiators

• Parasitic loads (pumps, fans) – Significant impact on overall performance– Scope for reduction

• High efficiency pumps• Avoid unnecessary use

• Overly complex controls– Users need to understand them

Presenter
Presentation Notes
I haven’t included the radiator sizing figure – but typically a flow temperature or 45 would require 3 times the area of radiator (so double ganged instead of single and longer as well) than a standard 75oC flow rad.
Page 18: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

5. MCS Guidance

• Microgeneration Certification Scheme• Outcome of EST field trial

– Updates to installer guidance MIS 3005

• Three key areas– Sizing– Ground loop design new supplementary documents– Heat emitter guide on MCS web site

• DECC road-show to publicise changes & train installers– Social Housing road-show soon (Glasgow 1st November 2012*)

18

* http://www.decc.gov.uk/en/content/cms/news/heat_pump_road/heat_pump_road.aspx

Presenter
Presentation Notes
MCS – both products and installers have registration schemes. Will be a requirement for RHI payments (cf FiTs) The heat emitter guide relates heat loss of “worst” room to flow temperature achievable by the type of heat emitter chosen and provides an indication of the annual energy performance – a good source of information
Page 19: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

19

Sizing

• Issue was “Scandinavian” design– Under-sized heat pump + electric flow boiler “top-up”– Field trial experience

• Poor seasonal performance• High bills

• MIS 3005 addresses this– Size for 100% load at design day condition– Requires a full heat loss calc. on property

• Even with this approach..– Some days (colder than design day) where heat pump won’t cope

• Reduce some room temperatures / warmer clothing /

Presenter
Presentation Notes
Flow boilers aren’t bad when you have loads of low cost hydro Design day -1oC London, I think ~ -4oC in Scotland Even on mild days were seeing flow boiler use in some cases – customer behaviour needs to be considered (different to boilers) and education needs to be provided at time of installation. Also, currently, householders will not be aware that the flow boiler is being used
Page 20: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

6. Network Impacts

• Both sizing and penetration levels are of concern– Large additional loads c.f. other (non electric heating) domestic

loads

• Network specific (urban, rural, local constraints)– But often Networks already stretched

• Coldest day analysis– Heat demand determines the Heat Pump electricity load

• Brief example– 7kW (design day) heat demand house– Assume no diversity on coldest day

• i.e. all heat pumps will be running flat out – especially at peak times– Look at both 24/7 and “bimodal” operation

20

Presenter
Presentation Notes
7kW is equivalent to ~ 12,000 kWh per year – slightly below the UK average Bimodal refers to the typical ~3 hours in the morning and ~8 hours mid afternoon / evening heating pattern 24/7 heating requires more heat (though there may be a heat pump COP benefit which will compensate to some extent). 24/7 vs biomdal for heat pumps is one of those currently unresolved issues. Several manufacturers recommend 24/7 (at least in winter) COP ~ 3 used
Page 21: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

21

Heat Pumps 10% penetration, 24/7

Presenter
Presentation Notes
Low penetration level Even at these levels – significant increase in MD
Page 22: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

22

Heat Pumps10% penetration, 24/7, 1 hour interrupt

Presenter
Presentation Notes
Standard DSM interupts don’t help the peak problem much
Page 23: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

23

Heat Pumps10% penetration, 24/7, MD unchanged

Presenter
Presentation Notes
Better approach is, say, heat storage to run in parallel with a reduced heat pump operation across the peak periods
Page 24: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

24

Heat Pumps100% penetration, 24/7, big increase in MD

Presenter
Presentation Notes
By the time we have all houses with heat pumps on a given network, the MD is greatly increased
Page 25: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

25

Heat Pumps100% penetration, bimodal, big problem!

Presenter
Presentation Notes
Assumes all heating systems start and stop at same time. In reality there will be some diversity in start / stop times, but still likely to be several hours per day at these sorts of level
Page 26: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

26

Mitigation measures

• Network investment• More efficient heat pumps

– Typically lower flow temperatures

• Under-sizing– Counter to MCS guidance but can be a good solution with top-up

heat from:

• Storage electric

• Gas

• Other storable fuels

• direct electric

Page 27: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

27

Under-sizing• Helps with design day• Only a small top-up

Presenter
Presentation Notes
Simplistic analysis of a full heating season, with days placed in order of daily heat load. With a heat pump sized to provide 60% of the design day heat load, the heat pump provides 91% of the total annual heating, leaving the other 9% for the back-up / top-up heating. This is the basis of the Scandinavian sizing – but they go and spoil it (for the UK situation) by using direct electric for the top-up
Page 28: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

28

SGF:WS3* (Phase 2):Network Model Schematic Overview

*Smart Grid Forum: Workstream 3

Page 29: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

29

The spread of (network related) investment from the model is significant

Spread of GB network related investment (non-discounted cumulative totex showing the two most extreme scenarios) to accommodate projections in Low Carbon Technologies connecting to the electricity distribution network

Output: The potential impact of future GB energy scenarios on power networks is material

Page 30: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Output: The challenge ahead is technically demanding and of a scale not seen in 50 yearsInvestment will require step changes

30

Gross GB network related investment for the next four RIIO periods

Load related expenditure (LRE) – investment driven by changes in demand, i.e. that in response to new loads or generation being connected to parts of the network (connections expenditure) and investment associated with general reinforcement. Non-load related expenditure (NLRE) – other network investment that is disassociated with load. LNRE and LRE have simply been assumed to be 8/5th of the DPCR5 values for the extended RIIO periods

Page 31: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Output: Observations

An iterative process with evidence from innovation trials will improve the evidence base – version control advisable

31

• A total of 45 separate variables in the model

• As more information comes to light, the model output will be improved

• For example:• LV network parameters• LCT profiles, e.g. electric

vehicle charging profiles• Solution costs & benefits

Refine input parameters

RunModel

Report output

Page 32: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

7. Future Studies

• Low temperature heat emitters • 24/7 vs bimodal operation• Challenge MCS guidance on sizing

– Hybrid solutions

• Electricity Supply / End Use balancing– Problem or solution?

32

Presenter
Presentation Notes
Tools required: Test Houses Labs Building modelling Network modelling Then more field trials
Page 33: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

8. Conclusions

• Heat Pumps important to the low carbon future• Designs need improving

– More the application than the Heat Pumps

• Owners & specifiers need to understand characteristics• Network capacity concerns

– Tools now available to investigate issues

33

Presenter
Presentation Notes
By application I mean the Central Heating system. There is scope for efficiency improvements in the heat pumps themselves – better compressor motors being the next one just over the horizon
Page 34: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions
Page 35: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Appendix

35

Page 36: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

WS3-Ph2: A consortium-led approach on behalf of the GB Smart Grid Forum (Work Stream 3)

36

Project Partners..

Working with..

Page 37: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

2. Disruptive technologies have scope to create significant challenge to LV networks

37

Heat Pumps

Photovoltaic

Electric VehiclesSource: SGF, WS1, DECC, Dec 2011

A

B

C

A B

C

Page 38: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Not all networks are equal: The headroom of the networks differ throughout GB

Factors include:

Build specification

Customer type and customer density

Local geography

38

Presenter
Presentation Notes
The physical electrical network infrastructure is not uniform across GB. Variations have resulted from the age profile (large city centres were electrified well before rural areas, and therefore have different network topologies, new housing estates are designed differently from pre 1950s), differing customer densities, and local geography. A graphic slide(s) to explain roughly how the model works: How have we built up the network from different feeder types. Different types of feeders have different properties; feed different number and types of customers. Then go into a bit of detail on how the model has been built
Page 39: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

The mix of customers along a feeder has a significant impact on its overall demand profile

LV feeder demand profile

39

Presenter
Presentation Notes
Detached Flat with E7 School Office Hotel Street light
Page 40: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

PV installations have clustered in different parts of GB

40

Percentage of network

Percentage of low-carbon technology installations

1% 9%

4% 17%

25% 48%

30% 22%

40% 5%

Number of domestic PV installations per 10,000 households by Local Authority, end of December 2011

Source: www.azure.eco.co.uk

Source: DECC

Presenter
Presentation Notes
Post codes in Scotland with more than 200kW installed capacity (PV) at 31st December 2011
Page 41: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Domestic Heat Pump

Point load demand profiles have a significant impact

• Winter Peak, Winter & Summer Average• Weekday• Temperature Sensitivity• Appliance Type & Efficiency• Validation

Standard Tariff Domestic Domestic E7 Storage Heaters

Temperature Sensitivity

41

Page 42: Lessons from EST Field Trials & Electricity Network Studies Sep 2012/Dave...EST Field Trials – some practical issues 5. MCS Guidance 6. Network Impacts 7. Future studies 8. Conclusions

Fixing the problem: Selecting solutions with an increasing solution set

42

ConventionalSolutions

ConventionalSolutions

‘Business-As-Usual’Investment

‘Smart’ Investment

SmartSolutions

Solution Enablers


Recommended