Power Protection for Business Critical Continuity Liebert GXT-MT +
Transcript
Page 1: Liebert GXT-MT - Gayatrigroup.ingayatrigroup.in/wp-content/uploads/2013/12/GXTmt.pdf · 2014. 9. 1. · Liebert GXT-MT + features a comprehensive specification, satisfies safety criteria

Power Protection for Business Critical Continuity

Liebert GXT-MT +

Page 2: Liebert GXT-MT - Gayatrigroup.ingayatrigroup.in/wp-content/uploads/2013/12/GXTmt.pdf · 2014. 9. 1. · Liebert GXT-MT + features a comprehensive specification, satisfies safety criteria

Trouble is Coming Down The Line And You Must Be Prepared

Every operation in your business depends upon the instant, around-the clock availability of computers, servers and other electronic systems. If they aren’t working, neither is your company. Every piece of this equipment your company possesses is subject to the whims of the electricity that powers it.

The first step in taking control of this situation is to understand the threats to your system reliability — and exactly what you can

do about them.

The Liebert GXT-MT + True Online Double Conversion UPS With Extended Runtime Capabilities

Liebert GXT-MT + features a comprehensive specification, satisfies safety criteria and electromagnetic compatibility standards, and offers intelligent monitoring and network management functions.

Liebert GXT-MT + satisfies your requirements for high reliability and high availability of the AC

power supply.

Liebert GXT-MT + is available in a compact Tower configuration making it easily deployed in an office or a light industrial application.

Liebert GXT-MT + long run model (L) deploys adaptive battery architecture to maximise your valuable rack space utilisation. Application specific battery configuration and placement ensures optimal performance.

NOTE:- Liebert GXT-MT + standard model is provided complete with internal battery.

Liebert GXTL-MT + (long back up model) application specific battery and cabinet available through your local Emerson

Network Power representative.

Page 3: Liebert GXT-MT - Gayatrigroup.ingayatrigroup.in/wp-content/uploads/2013/12/GXTmt.pdf · 2014. 9. 1. · Liebert GXT-MT + features a comprehensive specification, satisfies safety criteria

Applications

Small Size Data Center Telecommunication, VoIP Small Office Network Data Warehouses Medical Diagnostics Process Automation Equipments

Features

0.8 o/p p.f with LCD Display Option Extended Runtime Capabilities Flexible (Site Specific) Battery Configuration Compact Tower design. Generator Compatible Class B Electromagnetic interference (EMC) compatible Ultra wide input voltage range High capacity Battery Charger for GXTL High input power factor & low THDi

Liebert GXT - MT +

Page 4: Liebert GXT-MT - Gayatrigroup.ingayatrigroup.in/wp-content/uploads/2013/12/GXTmt.pdf · 2014. 9. 1. · Liebert GXT-MT + features a comprehensive specification, satisfies safety criteria

True Online Double Conversion

Flexible Configuration

Extended Run Time ready facilitated through a simple process of building up additional battery resources.

Multiple AC output interfaces via IEC standard sockets

Convenient maintenance

Fault type is clearly displayed for fast troubleshooting.

LCD display provides maximum operational convenience when managing the UPS.

Intelligent Management functions

Stronger Battery charger on the GXT L model for quick recharge

Remote Monitoring is available through RS232, and optional via dry contacts and SNMP. The monitoring option software supports TCP/IP with event log and analysis function.

Self-diagnosis and protection enable the auto shutdown of the client terminal or server under abnormal mains supply or when battery is over discharged.

Page 5: Liebert GXT-MT - Gayatrigroup.ingayatrigroup.in/wp-content/uploads/2013/12/GXTmt.pdf · 2014. 9. 1. · Liebert GXT-MT + features a comprehensive specification, satisfies safety criteria

True On-Line Double Conversion

Technology: When “Adequate” protection is not enough

Technical Specifications Model 1 kVA 2 kVA 3 kVA

OUTPUT PARAMETERS

Capacity 1kVA / 800W 2kVA / 1600W 3kVA / 2400W

Power Factor 0.8 0.8 0.8

Configuration 1 phase, L-N = PE 1 phase, L-N = PE 1 phase, L-N = PE

Nominal Voltage 220 / 230 / 240 Vac 220 / 230 / 240 Vac 220 / 230 / 240 Vac

Voltage Regulation + / - 3% + / - 3% + / - 3%

Voltage THD <=3% - Linear Load <=6% - Non Linear load

<=4% - Linear Load <=7% - Non Linear load

<=4% - Linear Load <=7% - Non Linear load

Frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz

Frequency Regulation - Free Run (Unsynchronised with bypass)

+ / - 0.5 Hz + / - 0.5 Hz + / - 0.5 Hz

Frequency Regulation (Synchronised with bypass)

47.5 to 52.5 HZ / 57.5 to 62.5 HZ 47.5 to 52.5 HZ / 57.5 to 62.5 HZ 47.5 to 52.5 HZ / 57.5 to 62.5 HZ

Slew Rate 1 Hz per second maximum 1 Hz per second maximum 1 Hz per second maximum

Creast Factor 3:1 max. 3:1 max. 3:1 max.

Transient response at 100% step load + / - 6% On line mode; + / - 6% On line mode; + / - 6% On line mode;

Recovery time <150ms <150ms <150ms

Over load capacity 110% - 130% - 12 sec; >130 - 1.5 sec 110% - 130% - 12 sec; >130 - 1.5 sec 110% - 130% - 12 sec; >130 - 1.5 sec

AC - AC Efficiency 88% R-Load, 87% RCD - Load 88% R-Load, 87% RCD - Load 88% R-Load, 87% RCD - Load

Transfer time - Mains to battery 0 millisec 0 millisec 0 millisec

Transfer time - Inverter to bypass - Synchronisation mode

4 msec 4 msec 4 msec

INPUT PARAMETERS

Configuration 1 phase, L-N + PE 1 phase, L-N + PE 1 phase, L-N + PE

Nominal Voltage 230 Vac 230 Vac 230 Vac

Voltage range 160V to 300V at 100% Load, At 60% Load 110V to 300 Vac

160V to 300V at 100% Load, At 60% Load 110V to 300 Vac

160V to 300V at 100% Load, At 60% Load 110V to 300 Vac

Frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz

Frequency range - Hz 40 - 70 Hz 40 - 70 Hz 40 - 70 Hz

Power Factor >=0.95 >=0.95 >=0.95

Current Distortion (I-THD) 12% linear, 13% nonlinear 12% linear, 13% nonlinear 12% linear, 13% nonlinear

BYPASS

Voltage 220 / 230 / 240 Vac 220 / 230 / 240 Vac 220 / 230 / 240 Vac

198V - 242V For 220V 198V - 242V For 220V 198V - 242V For 220V

207V - 253V For 230V 207V - 253V For 230V 207V - 253V For 230V

216V - 264V For 240V 216V - 264V For 240V 216V - 264V For 240V

Frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz

Frequency Range 47.5 to 52.5 Hz / 57.5 to 62.5 Hz 47.5 to 52.5 Hz / 57.5 to 62.5 Hz 47.5 to 52.5 Hz / 57.5 to 62.5 Hz

Page 6: Liebert GXT-MT - Gayatrigroup.ingayatrigroup.in/wp-content/uploads/2013/12/GXTmt.pdf · 2014. 9. 1. · Liebert GXT-MT + features a comprehensive specification, satisfies safety criteria

Technical Specifications Model 1 kVA 2 kVA 3 kVA

BATTERY CHARGER

Nominal Voltage - Float 41 Vdc 108 Vdc 82.1 Vdc

Maximum charging current - STD. / LB. 1A - STD and 4 / 8 A - LB 1A - STD and 4 / 8 A - LB 1A - STD and 4 / 8 A - LB

Better Connector 5 pin Wago 770-750 5 pin Wago 770-750 5 pin Wago 770-750

BATTERY PARAMETERS

Type SMF SMF SMF

No. of battery blocks 3 8 8

Battery Voltage 36 VDC 96 V 96V

Maximum Back up time at full load STD. 7 minutes / 7 AH STD. 6.5 minutes / 7 AH STD. 5 minutes / 7 AH

ENVIRONMENTAL PARAMETERS

Operating temperature 0 to 40 deg. centigrade 0 to 40 deg. centigrade 0 to 40 deg. centigrade

Storage temperature -20 to 50 deg. centigrade -20 to 50 deg. centigrade -20 to 50 deg. centigrade

Relative Humidity 90% RH 90% RH 90% RH

Altitude

Noise level <45db <45db <45db

MECHANICAL PARAMETERS

Height X Width X Depth (MM) 220 X 145 X 388.5 318 X 190 X 387 318 X 190 X 387

Weight 13 kg. - STD., 7 kg. - LB 26 kg. - STD., 13 kg. - LB 28 kg. - STD., 13 kg. - LB

Ventilation Forced - Air cooled Forced - Air cooled Forced - Air cooled

Cable Entry Backside Backside Backside

Colour / Panel finish RAL 7016 dark grey RAL 7016 dark grey RAL 7016 dark grey

Protection IP20 IP20 IP20

Communication Port RS232, USB RS232, USB RS232, USB

EPO Yes Yes Yes

MONITORING SOFTWARE SNMP, dry contact card, UPSilon 2000

SNMP, dry contact card, UPSilon 2000

SNMP, dry contact card, UPSilon 2000

STANDARDS

EMI EN 62040-2: 2006 EN 62040-2: 2006 EN 62040-2: 2006

SAFETY EN 62040-1-1: 2003 EN 62040-1-1: 2003 EN 62040-1-1: 2003

PERFORMANCE (technical feature) IEC / EN 62040 - 3 IEC / EN 62040 - 3 IEC / EN 62040 - 3

Transportation IEC 600068-2-32 - DROP TEST IEC 600068-2-32 - DROP TEST IEC 600068-2-32 - DROP TEST

IEC 60068-2-64 - VIBRATION TEST IEC 60068-2-64 - VIBRATION TEST IEC 60068-2-64 - VIBRATION TEST

IEC 60068-2-27 - SHOCK TEST IEC 60068-2-27 - SHOCK TEST IEC 60068-2-27 - SHOCK TEST

Miscellaneous EN 50272 - VOLUME / AIR FLOW / DEGASSING STANDARD

EN 50272 - VOLUME / AIR FLOW / DEGASSING STANDARD

EN 50272 - VOLUME / AIR FLOW / DEGASSING STANDARD

CE MARK CE MARK CE MARK

Page 7: Liebert GXT-MT - Gayatrigroup.ingayatrigroup.in/wp-content/uploads/2013/12/GXTmt.pdf · 2014. 9. 1. · Liebert GXT-MT + features a comprehensive specification, satisfies safety criteria

Country Office

Emerson Network Power (India) Private Ltd.

Plot No. C-20, Road No. 19, Wagle Estate,

Thane (w), Maharashtra - 400 604. India.

Tel.: 91-22-67208000

Fax: 91-22-25828358

Toll Free No 18002096070

Email: [email protected]

Voice of Customers UPS Awards 2004-05 for Product Line

& Customer Service Awards in IT, Telecom, Large Enterprise & Hospitals and

Customer Service Leadership Award in BFSI

2007 R

Best IT Hardware Company Maharashtra IT Award 2006-07

www.emersonnetworkpower.co.in

Emerson Network Power.

The global leader in enabling Business-Critical Continuit yTM.

AC Power

Connectivity

DC Power

Embedded Computing

Embedded Power

Monitoring

Outside Plant

Power Switching & Controls

Precision Cooling

Racks & Integrated Cabinets

Services