Liebert® Mini-Mate2™ Thermal Management System Installer/User Guide 1-ton and 1.5-ton Capacity, 50 and 60 Hz
Transcript
Page 1: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Liebert®Mini-Mate2™ Thermal Management System

Installer/User Guide1-ton and 1.5-ton Capacity, 50 and 60 Hz

Page 2: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide

Technical Support Site

If you encounter any installation or operational issues with your product, check the pertinentsection of this manual to see if the issue can be resolved by following outlined procedures.Visit https://www.Vertiv.com/en-us/support/ for additional assistance.

The information contained in this document is subject to changewithout notice and may not be suitable for all applications. Whileevery precaution has been taken to ensure the accuracy andcompleteness of this document, Vertiv assumes no responsibilityand disclaims all liability for damages resulting from use of thisinformation or for any errors or omissions. Refer to other localpractices or building codes as applicable for the correct methods,tools, and materials to be used in performing procedures notspecifically described in this document.

The products covered by this instruction manual are manufacturedand/or sold by Vertiv. This document is the property of Vertiv andcontains confidential and proprietary information owned by Vertiv.Any copying, use or disclosure of it without the written permissionof Vertiv is strictly prohibited.

Names of companies and products are trademarks or registeredtrademarks of the respective companies. Any questions regardingusage of trademark names should be directed to the originalmanufacturer.

Page 3: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

TABLE OF CONTENTS

1 Important Safety Instructions 1

1.1 Agency Listed 7

2 Nomenclature 9

2.1 Nomenclature for Self-contained Air-cooled and Water/Glycol Units 9

2.2 Nomenclature for Split-system Air-cooled and Chilled-water Units 11

2.2.1 Outdoor Prop-fan Condensing Units for Air-cooled Split Systems 13

2.3 System Configurations 14

3 Site Preparation and Equipment Handling 17

3.1 Planning Dimensions 17

3.2 Room Preparation 17

3.3 Application Limits 17

3.4 Location Considerations 18

3.4.1 Location Considerations for an Outdoor Condensing Unit 19

3.5 Indoor Unit Weights 19

3.6 Equipment Inspection and Handling 20

4 Installation 21

4.1 Installing Ceiling-mounted Units 21

4.1.1 Installing Suspension Rods and Mounting Ceiling Units 21

4.2 Installing Air-distribution Components for Evaporators 22

4.2.1 Installing a Filter Box 23

4.2.2 Guidelines for Ducted Systems 24

4.3 Installing Condensing-fan Module on Self-contained Air-cooled Systems 25

5 Piping and Refrigerant Requirements 27

5.1 Fluid Piping Required 28

5.1.1 Drain Line Installation Requirements 28

5.1.2 Condensate-drain Pump Kit 30

5.1.3 Water-supply line to the Humidifier 31

5.1.4 Chilled-water Loop Piping 31

5.1.5 Water/Glycol Loop Piping 32

5.1.6 Free-cooling Coil Piping 33

5.1.7 Hot-water Reheat Coil Piping 33

5.2 Refrigerant Piping 34

5.2.1 Piping when Condensing Unit is Above or Below Evaporator 35

5.2.2 Refrigerant-line Sizes and Equivalent Lengths 36

5.2.3 Refrigerant Charge Requirements 37

5.2.4 Field-fabricated Refrigeration Piping 38

5.2.5 Evacuation and Leak-testing Air-cooled Systems 38

5.2.6 Charging Air-cooled Systems 40

i

Page 4: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

5.2.7 Field Charge Verification for Air-cooled Systems 41

5.2.8 Documenting Refrigerant Charge on Air-cooled Units 41

5.2.9 Optimizing Refrigerant Charge on Water/Glycol Units 41

6 Electrical Connection Requirements 43

6.1 Input-power Connection Requirements 44

6.2 Control-wiring Connection Requirements 45

6.2.1 Wall-box Controller Control Connections 45

6.2.2 Split-system Condensing-unit Control Connections 45

6.2.3 Water/Glycol-cooled Unit Control Connections 45

6.2.4 Additional Control Connections 45

6.3 Condensing-fan Blower Electrical, Control and Power Connections 46

7 Checklist for Completed Installation 47

8 Initial Start-up Checks and Commissioning Procedure for Warranty Inspection 49

9 Microprocessor Control 51

9.1 Controller Operation 51

9.1.1 Powering On/Off with Wall-mounted Display 52

9.1.2 Silencing an Audible Alarm 52

9.2 Main Menu <MENU> 53

9.2.1 Editing Setpoints 56

9.2.2 Viewing Unit Status 56

9.2.3 Viewing Active Alarms 57

9.2.4 Viewing Alarm History 57

9.2.5 Setting Controller Time 57

9.2.6 Setting Controller Date 57

9.2.7 Programming Setback 58

9.2.8 Editing Setup Operation 58

9.2.9 Changing Setpoint and Setup Passwords 60

9.2.10 Calibrating Sensors and Setting Sensor-response Delay 60

9.2.11 Enabling/Disabling Alarms 61

9.2.12 Setting Alarm Delays 62

9.2.13 Activating the Common Alarm Relay 63

9.2.14 Configuring Custom Alarms 63

9.2.15 LCD Display Contrast 63

9.2.16 Non-volatile Memory 63

9.2.17 Equipment Options DIP Switches 64

9.2.18 Customizing Alarm-message Text 65

9.3 Running Diagnostics 65

9.3.1 Showing Test Inputs 65

9.3.2 Testing Outputs 66

9.3.3 Testing the Microcontroller 67

Vertiv | Liebert® Mini-Mate2™ Installer/User Guideii

Page 5: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.4 System Control and Performance 70

9.4.1 Temperature Control 70

9.4.2 Reheat 70

9.4.3 Humidity Control 72

9.4.4 Load Control 72

9.4.5 Monitoring 72

9.5 Alarm Notification, Acknowledgment and Descriptions 73

9.5.1 Custom Alarms 74

9.5.2 High Head-Pressure Alarm 74

9.5.3 Humidity-level Alarms 75

9.5.4 Temperature-level Alarms 75

9.5.5 Humidifier-problem Alarm 75

9.5.6 High-water Alarm 75

9.5.7 Loss-of-Power Alarm 76

9.5.8 Short Cycle Alarm 76

9.5.9 Loss of Water Flow Alarm 76

9.5.10 Change-filter Alarm 76

9.5.11 High-temperature Alarm 76

9.5.12 Smoke Alarm 76

10 Maintenance 77

10.1 System Testing 78

10.1.1 Environmental-control Function Tests 78

10.1.2 Cooling Test 78

10.1.3 Heating Test 78

10.1.4 Humidification Test 78

10.1.5 Dehumidification Test 78

10.1.6 Smoke Sensor Test 79

10.1.7 Remote Shutdown Test 79

10.2 Filter Maintenance 79

10.3 Electric Panel Maintenance 79

10.4 Direct-drive Blower Package Maintenance 79

10.4.1 Fan Impeller and Motor Bearing Maintenance 79

10.4.2 Air Distribution Inspection 79

10.4.3 Motor Replacement 79

10.5 Electric Reheat Maintenance 79

10.6 Refrigeration System Maintenance 80

10.6.1 Refrigeration Suction Pressure 80

10.6.2 Refrigeration Discharge Pressure 80

10.6.3 Thermostatic Expansion Valve (TXV) Maintenance 80

10.6.4 Air-Cooled Condensing Unit Maintenance 80

iii

Page 6: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10.6.5 Hot Gas Bypass Operation and Maintenance 81

10.6.6 Coaxial Condenser Maintenance (Water/Glycol-cooled Condensers Only) 83

10.6.7 Regulating Valve Maintenance (Water/Glycol-cooled Condensers Only) 83

10.6.8 Glycol Solution Maintenance 83

10.7 Compressor Maintenance 84

10.7.1 Mechanical Failure of the Compressor 84

10.7.2 Electrical Failure of the Compressor 85

10.7.3 Replacement Compressors 85

10.7.4 Replacing a Failed Compressor 85

10.8 Steam-generating Humidifier Maintenance 86

10.8.1 Operating the Humidifier 87

10.8.2 Replacing the Canister 87

10.8.3 Circuit Board Adjustments 88

11 Preventive Maintenance Checklist 89

12 Troubleshooting 95

Appendices 99

Appendix A: Technical Support and Contacts 99

Appendix B: Submittal Drawings 101

Vertiv | Liebert® Mini-Mate2™ Installer/User Guideiv

Page 7: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

1 IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONS

This manual contains important safety instructions that should be followed during the installation andmaintenance of the Liebert® Mini-Mate2. Read this manual thoroughly before attempting to install oroperate this unit.

Only qualified personnel should move, install or service this equipment.

Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unitand in this manual. Follow all installation, operation and maintenance instructions and all applicablenational and local building, electrical and plumbing codes.

WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supplydisconnect switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective equipment (PPE) per NFPA 70E before working within theelectric control enclosure. Failure to comply can cause serious injury or death. Customer mustprovide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceedingwith installation, read all instructions, verify that all the parts are included and check thenameplate to be sure the voltage matches available utility power. The Liebert® controller doesnot isolate power from the unit, even in the “Unit Off” mode. Some internal components requireand receive power even during the “Unit Off” mode of the controller. The only way to ensurethat there is NO voltage inside the unit is to install and open a remote disconnect switch. Referto unit electrical schematic. Follow all local codes.

WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all localand remote electric power supply disconnect switches and verify with a voltmeter that power isoff before working within any electric connection enclosures. Service and maintenance workmust be performed only by properly trained and qualified personnel and in accordance withapplicable regulations and manufacturers’ specifications. Opening or removing the covers toany equipment may expose personnel to lethal voltages within the unit even when it isapparently not operating and the input wiring is disconnected from the electrical source.

1 Important Safety Instructions 1

Page 8: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

WARNING! Risk of over-pressurization of the refrigeration system. Can cause piping rupture,explosive discharge of high-pressure refrigerant, loss of refrigerant, environmental pollution,equipment damage, injury, or death. This unit contains fluids and gases under high pressure.Use extreme caution when charging the refrigerant system. Do not pressurize the systemhigher than the design pressure marked on the unit's nameplate. Relieve pressure beforecutting into or making connections/disconnections to the piping system. Local building orplumbing codes may require installing a pressure-relief device in the system.

Consult local building and plumbing codes for installation requirements of additional pressure-relief devices when isolation valves are field installed. Do not isolate any refrigerant circuitsfrom over pressurization protection. The PFH condensing units include a factory-installedpressure-relief valve mounted on top of the receiver. The valve is rated for a maximum workingpressure of 475 psig.

WARNING! Risk of contact with high-speed, rotating fan blades. Can cause injury or death.Open all local and remote electric power-supply disconnect switches, verify with a voltmeterthat power is off, and verify that all fan blades have stopped rotating before working in the unitcabinet.

WARNING! Risk of electric shock. Can cause serious injury or death. The microprocessor doesnot isolate power from the unit, even in the "Unit Off" mode. Some internal components requireand receive power even during the "unit off" mode of the control. Open all local and remoteelectric power disconnect switches and verify with a voltmeter that power is Off before workingon any component of the system.

WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipmentdamage, serious injury or death. Installation and service of this equipment should be done onlyby qualified personnel, wearing appropriate, OSHA-approved PPE, who have been specially-trained in the installation of air-conditioning equipment.

WARNING! Risk of improper wire and loose electrical connections. Can cause overheated wireand electrical connection terminals resulting in smoke, fire, equipment and building damage,injury or death. Use correctly sized copper wire only and verify that all electrical connections aretight before turning power On. Check all electrical connections periodically and tighten asnecessary.

WARNING! Risk of ceiling collapse and heavy unit falling. Can cause building and equipmentdamage, serious injury or death. Verify that the supporting roof structure is capable ofsupporting the weight of the unit(s) and the accessories. See Table 3.5  on page 19, for the unitweights. Securely anchor the top ends of the suspension rods and verify that all nuts are tight.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide2

Page 9: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

WARNING! Risk of smoke and fire. Can cause activation of fire suppression systems, buildingevacuation, dispatching of fire/rescue equipment and personnel and catastrophic canisterfailure resulting in water leaks, equipment damage, injury or death. Using a humidifier canisterthat has reached the end of it’s service life can be extremely hazardous. If the canister cannotbe replaced immediately at the end of life condition, turn Off the power and water supply to thehumidifier and remove the canister until a replacement canister can be installed. Do not ignorehumidifier problem alarms. Resetting humidifier without addressing cause may result in fire ordamage due to leaking water.

CAUTION: Risk of excessive refrigerant line pressure. Can cause tubing and componentrupture resulting in equipment damage and personal injury. Do not close off any field-installedrefrigerant-line isolation valve for repairs unless a pressure-relief valve is field- installed in theline between the isolation valve and the check valve. The pressure-relief valve must be rated 5%to 10% higher than the system-design pressure. An increase in ambient temperature can causethe pressure of the isolated refrigerant to rise and exceed the system-design pressure rating(marked on the unit nameplate).

CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can causeinjury. Only properly trained and qualified personnel wearing appropriate, OSHA-approved PPEshould attempt to move, lift, remove packaging from or prepare the unit for installation.

CAUTION: Risk of contact with hot surfaces. Can cause injury. The compressor, refrigerantdischarge lines, fan motor, and some electrical components are extremely hot during unitoperation. Allow sufficient time for them to cool to a touch-safe temperature before workingwithin the unit cabinet. Use extreme caution and wear appropriate, OSHA-approved PPE whenworking on or near hot components.

CAUTION: Risk of contact with hot surfaces. Can cause burn injury. The humidifier canisterand steam discharge lines are extremely hot during operation. Allow sufficient time for them tocool to a touch-safe temperature before handling. Use extreme caution and wear appropriate,OSHA-approved PPE when performing maintenance on the humidifier.

CAUTION: Risk of contacting caustic substances. Can cause injury. Avoid touching orcontacting the gas and oils with exposed skin. Severe burns will result. Wear appropriate,OSHA-approved PPE when handling contaminated parts.

1 Important Safety Instructions 3

Page 10: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

CAUTION: Risk of the grille falling. Can cause equipment damage or injury. Do not allow theweight of the unit to rest on the grilles.

NOTICE

Risk of oil contamination with water. Can cause equipment damage.

Liebert®  Mini-Mate2 DX systems require the use of POE (polyolester) oil. POE oil absorbs waterat a much faster rate when exposed to air than previously used oils. Because water is theenemy of a reliable refrigeration system, extreme care must be used when opening systemsduring installation or service. If water is absorbed into the POE oil, it will not be easily removedand will not be removed through the normal evacuation process. If the oil is too wet, it mayrequire an oil change. POE oils also have a property that makes them act as a solvent in arefrigeration system. Maintaining system cleanliness is extremely important because the oil willtend to bring any foreign matter back to the compressor.

NOTICE

Risk of clogged or leaking drain lines and leaking water-supply lines. Can cause equipment andbuilding damage.

This unit requires a water drain connection. Drain lines must be inspected at start-up andperiodically, and maintenance must be performed to ensure that drain water runs freelythrough the drain system and that lines are clear and free of obstructions and in goodcondition with no visible sign of damage or leaks. This unit may also require an external watersupply to operate.

Improper installation, application and service practices can result in water leakage from theunit. Water leakage can result in catastrophic and expensive building and equipment damageand loss of critical data center equipment.

Do not locate unit directly above any equipment that could sustain water damage.

We recommend installing a monitored fluid-detection system to immediately discover andreport coolant-fluid system and condensate drain-line leaks.

NOTICE

Risk of leaking water/glycol. Can cause equipment and building damage.

Improper installation, application, and service practices can result in water leakage from theunit. Do not mount this unit over equipment and furniture that can be damaged by leakingwater. Install a water-tight drain pan with a drain connection under the cooling unit and theceiling mounted water/glycol condensing unit. Route the drain line to a frequently-usedmaintenance sink so that running water can be observed and reported in a timely manner.Post a sign to alert people to report water flowing from the secondary drain pan. Werecommend installing monitored leak detection equipment for the unit and supply lines and inthe secondary drain pan. Check drain lines periodically for leaks, sediment buildup,obstructions, kinks and/or damage and verify that they are free running.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide4

Page 11: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

NOTICE

Risk of piping-system corrosion and freezing fluids. Can cause leaks resulting in equipmentand very expensive building damage. Cooling coils and piping systems are at high risk offreezing and premature corrosion. Fluids in these systems must contain the proper antifreezeand inhibitors to prevent freezing and premature coil and piping corrosion. The water orwater/glycol solution must be analyzed by a competent local water treatment specialist beforestart up to establish the inhibitor and antifreeze solution requirement and at regularlyscheduled intervals throughout the life of the system to determine the pattern of inhibitordepletion.

The complexity of water/glycol solution condition problems and the variations of requiredtreatment programs make it extremely important to obtain the advice of a competent andexperienced water treatment specialist and follow a regularly scheduled coolant fluid systemmaintenance program.

Water chemistry varies greatly by location, as do the required additives, called inhibitors, thatreduce the corrosive effect of the fluids on the piping systems and components. The chemistryof the water used must be considered, because water from some sources may contain corrosiveelements that reduce the effectiveness of the inhibited formulation. Sediment deposits preventthe formation of a protective oxide layer on the inside of the coolant system components andpiping. The water/coolant fluid must be treated and circulating through the systemcontinuously to prevent the buildup of sediment deposits and or growth of sulfate reducingbacteria.

Proper inhibitor maintenance must be performed in order to prevent corrosion of the system.Consult glycol manufacturer for testing and maintenance of inhibitors.

Commercial ethylene glycol, when pure, is generally less corrosive to the common metals ofconstruction than water itself. It will, however, assume the corrosivity of the water from which itis prepared and may become increasingly corrosive with use if not properly inhibited.

We recommend installing a monitored fluid-detection system that is wired to activate theautomatic-closure of field-installed coolant-fluid supply and return shut-off valves to reducethe amount of coolant-fluid leakage and consequential equipment and building damage. Theshut-off valves must be sized to close-off against the maximum coolant-fluid system pressurein case of a catastrophic fluid leak.

NOTICE

Risk of frozen pipes and corrosion from improper coolant mixture. Can cause water leaksresulting in equipment and building damage.

When piping or the cooling unit may be exposed to freezing temperatures, charge the systemwith the proper percentage of glycol and water for the coldest design ambient temperature.Automotive antifreeze is unacceptable and must NOT be used in any glycol fluid system. Useonly HVAC glycol solution that meets the requirements of recommended industry practices.

1 Important Safety Instructions 5

Page 12: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

NOTICE

Risk of no-flow condition. Can cause equipment damage. Do not leave the water/coolant fluid-supply circuit in a no-flow condition. Idle fluid allows the collection of sediment that preventsthe formation of a protective oxide layer on the inside of tubes. Keep unit switched On andwater/coolant fluid-supply circuit system operating continuously.

NOTICE

Risk of improper water supply. Can reduce humidifier efficiency or obstruct humidifierplumbing.

Do not use completely demineralized water with this unit. The water must contain minerals forthe electrode principle to work.

Do not use a hot water source. It will cause deposits that will eventually block the fill-valveopening.

NOTICE

Risk of water backing up in the drain line. Leaking and overflowing water can cause equipmentand building damage.

Do not install an external trap in the drain line. This line already has a factory-installed trapinside the cabinet. Installation of a second trap will prevent drain-water flow and will cause thewater to overflow the drain pan.

This line may contain boiling water. Use copper or other material that is rated for handlingboiling water for the drain line. Sagging condensate drain lines may inadvertently create anexternal trap.

NOTICE

Risk of doorway/hallway interference. Can cause unit and/or structure damage. The unit maybe too large to fit through a doorway or hallway while on the skid. Measure the unit andpassageway dimensions, and refer to the installation plans prior to moving the unit to verifyclearances.

NOTICE

Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at aheight suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.

NOTICE

Risk of improper storage. Can cause unit damage.

Keep the unit upright, indoors and protected from dampness, freezing temperatures andcontact damage.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide6

Page 13: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

1.1 Agency Listed

Standard 60-Hz units are CSA Certified to the harmonized U.S. and Canadian product safety standardCSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and are marked with the CSA c-us logo.

1 Important Safety Instructions 7

Page 14: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide8

This page intentionally left blank

Page 15: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

2 NOMENCLATUREThis section describes the model-number configuration for Liebert® Mini-Mate2 units and components.

2.1 Nomenclature for Self-contained Air-cooled and Water/Glycol Units

Table 2.2  below describes each digit of the model number.

1 2 3 4 5 6 7 8 9 10 11 12

M M D 1 8 A — P R E 7 5

Table 2.1 Nomenclature Example

Digit Description

Digits 1 and 2 = the base unit

MM= Mini-Mate2

Digit 3 = Disconnect

D = Disconnect switch

Digit 4 and 5 = NominalCapacity

12 = 12 kBtuh, 1 ton, 60 Hz (air-cooled)

18 = 18 kBtuh, 1.5 ton, 60 Hz (air-cooled)

14= 14 kBtuh, 1 ton, 60 Hz (water/glycol-cooled)

20 = 20 kBtuh, 1.5 ton, 60 Hz (water/glycol-cooled)

Digit 6 = Cooling type

A= Air-cooled

F = Air-cooledwith free-cooling unit

G= Water/Glycol-cooledwith free-cooling coil

W= Water/Glycol-cooled

Digit 7= Valve type

— = Placeholder for air-cooled units

2 = 2-way standard-pressure fluid-regulating valve

3 = 3-way standard-pressure fluid-regulating valve

D = 2-wayhigh-pressure fluid-regulating valve

T = 3-wayhigh-pressure fluid-regulating valve

Digit 8 = Supplypower

P = 208/230 V / 1 ph / 60 Hz

X = 277 V / 1 ph / 60 Hz

Table 2.2 Nomenclature Digit Definitions for Self-contained Units

2 Nomenclature 9

Page 16: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Digit Description

Digit 9 = Humidification

R = Remote humidifier contact (without canister humidifier)

J = Canister humidifier and remote humidifier contact

Digit 10 = Reheat

0 = No reheat

E= Electric reheat

S= SCR reheat(not available on water/glycol-cooledwith free-cooling option)

G= Hot-gas reheat (not available with free-cooling option)

Digit 11 = Refrigerant andHot-gas bypass

7= R-407C (factory charged) andHot-gas bypass

Digit 12 = Sensor packages

N = Base package of filter-clog and high-temperature sensor

1 = iCOMCMS (Mobile Cloud) +Base package

2 = Smoke sensor +Base package

3 = iCOM CMS (Mobile Cloud) +smoke sensor +Base package

4= IS-UNITY-DP (BMS) +Base Package

5 = IS-UNITY-DP (BMS) +Smoke sensor +Base package

Table 2.2 Nomenclature Digit Definitions for Self-contained Units (continued)

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide10

Page 17: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

2.2 Nomenclature for Split-system Air-cooled and Chilled-water Units

Table 2.4  below describes each digit of the model number.

1 2 3 4 5 6 7 8 9 10 11 12

M M D 1 8 E N P R E 0 5

Table 2.3 Nomenclature Example

Digit Description

Digits 1 and 2 = the base unit

MM= Mini-Mate2

Digit 3 = Disconnect

D = Disconnect switch

Digit 4 and 5 = NominalCapacity

12 = 12 kBtuh, 1 ton, 60 Hz (air-cooled)

18 = 18 kBtuh, 1.5 ton, 60 Hz (air-cooled)

22 = 22 kBtuh, 1 ton, 50 Hz (chilled-water cooled)

23 = 23 kBtuh, 1.5 ton, 60 Hz (chilled-water cooled)

Digit 6 = Cooling type

C= Chilled-water cooled

E= Air-cooled, split evaporator (See Outdoor Prop-fan CondensingUnits for Air-cooled Split Systems on page 13.)

K = Air-cooled, split evaporator with free-cooling (See Outdoor Prop-fan CondensingUnits for Air-cooled Split Systemson page 13.)

Digit 7= Refrigerant/Valve

N = R-407C field-supplied (evaporator units)

2 = 2-way standard close-off pressure valve (chilled-water units)

D = 2-wayhigh close-off pressure valve (chilled-water units)

Digit 8 = Supplypower

P = 208/230 V / 1 ph / 60 Hz

X = 277 V / 1 ph / 60 Hz

S= 220 V / 1 ph / 50 Hz (chilled-water units only)

Table 2.4 Nomenclature Digit Definitions for Split-system and Chilled-water Units

2 Nomenclature 11

Page 18: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Digit Description

Digit 9 = Humidification

R = Remote humidifier contact (without canister humidifier)

J = Canister humidifier and remote humidifier contact

Digit 10 = Reheat

0 = No reheat

E= Electric reheat

S= SCR reheat (available onlywith Ecooling type, not available with chilled-water units)

H= Hot-water reheat (chilled-water units only)

Digit 11 = Hot-gas bypass

0 = Not in unit

Digit 12 = Sensor packages

N = Base package of filter-clog and high-temperature sensor

1 = iCOMCMS (Mobile Cloud) +Base package

2 = Smoke sensor +Base package

3 = iCOM CMS (Mobile Cloud) +smoke sensor +Base package

4= IS-UNITY-DP (BMS) +Base Package

5 = IS-UNITY-DP (BMS) +Smoke sensor +Base package

Table 2.4 Nomenclature Digit Definitions for Split-system and Chilled-water Units (continued)

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide12

Page 19: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

2.2.1 Outdoor Prop-fan Condensing Units for Air-cooled Split Systems

Table 2.6  below describes each digit of the model number.

1 2 3 4 5 6 7 8 9 10 11

P F H 0 2 0 A — P L N

Table 2.5 Prop-fan Condensing Unit Nomenclature Example

Digit Description

Digits 1 to 3 = the base unit

PFH= Prop-fan condensing unit with hot-gas bypass

Digit 4 = Sound level

0 = Standard

Digit 5 and 6= NominalCapacity

14= 14 kBtuh

20 = 20 kBtuh

Digit 7= Cooling type

A= Air-cooled

Digit 8 = Coil type

— = Standard coil

C = Coated coil (epoxywith UV topcoat)

Digit 9 = Supplypower

P = 208/230 V / 1 ph / 60 Hz

Digit 10 = Ambient rating/Control

L= 95°F Ambient, Liebert® Lee-Temp™

Digit 11 = Refrigerant

N = R-407C field-charged

Table 2.6 Nomenclature Digit Definitions for Outdoor, Prop-fan Condensing Units

2 Nomenclature 13

Page 20: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

2.3 System Configurations

The following figures show the available capacity and cooling options for the Liebert® Mini-Mate2.

Figure 2.1 Air-cooled Units

Item Description

1 Self-containedwith grille

2 Self-containedwith optional filter box

3 Split system with grille and outdoor condensing unit

4 Split system ductedwith outdoor condensing unit

5 Outdoor condensing unit

6 Evaporator

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide14

Page 21: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Figure 2.2 Water/Glycol-cooled Units

Item Description

1 Glycol-cooledwith grille

2 Glycol-cooledwith ducted supply/return air

3 Water-cooledwith grille

4 Water-cooledwith ducted supply/return air

5 Drycooler

6 Expansion tank

7 Pump

8 Cooling tower

2 Nomenclature 15

Page 22: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Figure 2.3 Chilled-water Units

Item Description

1 Chilled-water with grille

2 Chilled-water with ducted supply/return air

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide16

Page 23: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

3 SITE PREPARATION AND EQUIPMENT HANDLINGNOTE: Before installing unit, determine whether any building alterations are required to run piping,wiring and ductwork. Follow all unit dimensional drawings and refer to the submittal engineeringdimensional drawings of individual units for proper clearances.

3.1 Planning Dimensions

The unit dimensions are described in the submittal documents included in the Submittal Drawings onpage 101.

The following table lists the relevant documents by number and title.

Document Number Title

Self-containedUnits and Split-system Evaporators/Chilled-water Units

DPN000172 Cabinet Dimensions

DPN000173 Filter-boxandGrille Option Dimensions

DPN000177 Condenser-fan Module Dimensions

Table 3.1 Dimension Planning Drawings

3.2 Room Preparation

The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceilingand walls can be a polyethylene film. Paint on concrete walls and floors should be vapor resistant.

NOTE: The vapor barrier is the single most important requirement for maintaining environmentalcontrol in the conditioned area.

Outside or fresh air should be kept to a minimum when tight temperature and humidity control isrequired. Outside air adds to the site’s cooling, heating, dehumidifying and humidifying loads. Doorsshould be properly sealed to minimize leaks and should not contain ventilation grilles.

NOTE: Temperature and humidity sensors are located in the wall box. Proper and efficient coolingrequires placing the wall box where discharge air does not directly blow on the sensors.

3.3 Application Limits

Input voltage Range of return-air conditions to the unit*

Minimum Maximum Dry-bulb temperature Relative humidity

–5% +10% 65 to 85°F (18 to 29°C) 20 to 80%

*The unit will operate at these conditions, but it will not control to these condition extremes.

Table 3.2 Application Limits for Self-contained, Evaporator and Chilled-water Units

3 Site Preparation and Equipment Handling 17

Page 24: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Input voltage Entering dry-bulb air temperature

Minimum Maximum Minimum Maximum

–5% +10%–30°F (–34°C)

(units with Lee-Temp™ receiver)115°F (48°C)

Table 3.3 Application Limits for Outdoor Air-cooled Condensing Unit

Input voltage Entering fluid temperature

Minimum Maximum Minimum* Maximum

–5% +10% 45°F (7°C) 115°F (46°C)

*Operation below 65°F (18°C)may result in fluid noise and reduced valve life.

Table 3.4 Application Limits forWater/Glycol-cooled Self-contained Unit

3.4 Location Considerations

When determining installation locations, consider that these units contain water and that water leaks cancause damage to sensitive equipment and furniture below.

NOTICE

Risk of leaking water/glycol. Can cause equipment and building damage.

Improper installation, application, and service practices can result in water leakage from theunit. Do not mount this unit over equipment and furniture that can be damaged by leakingwater. Install a water-tight drain pan with a drain connection under the cooling unit and theceiling mounted water/glycol condensing unit. Route the drain line to a frequently-usedmaintenance sink so that running water can be observed and reported in a timely manner.Post a sign to alert people to report water flowing from the secondary drain pan. Werecommend installing monitored leak detection equipment for the unit and supply lines and inthe secondary drain pan. Check drain lines periodically for leaks, sediment buildup,obstructions, kinks and/or damage and verify that they are free running.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide18

Page 25: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

3.4.1 Location Considerations for an Outdoor Condensing Unit

For a split system with an air-cooled, outdoor condensing unit, the condensing unit may be mounted onthe roof or remotely in any outdoor area.

Observe the following when planning the installation of the outdoor unit:

• To ensure a satisfactory air supply, locate air-cooled condensing units in an environment withclear air, away from loose dirt and foreign matter that may clog the coil.

• Condensing units must not be located in the vicinity of steam, hot air or fume exhausts orcloser than 18 inches from a wall, obstruction or adjacent unit.

• Avoid areas where heavy snow will accumulate at air inlet and discharge locations.

• The condensing unit should be located for maximum security and maintenance accessibility.Avoid ground-level sites with public access. Install a solid base, capable of supporting theweight of the condensing unit.

• The base should be at least 2 in. (51 mm) higher than the surrounding grade and 2 in. (51 mm)larger than the dimensions of the condensing-unit base. For snowy areas, a base of sufficientheight to clear snow accumulation must be installed.

• Securely attach the unit to the base using the holes provided in the unit mounting rails toprevent unit movement that might stress refrigerant piping and electrical wiring.

Before beginning, refer to Piping and Refrigerant Requirements on page 27 for unit placement, pipingguidelines, and refrigerant-charge requirements for your system.

The condensing unit must be located within the maximum distance from evaporator guidelines listed inTable 5.6  on page 35.

3.5 Indoor Unit Weights

Model# Weights, lb (kg)

MMD12A 265 (120)

MMD12E 220 (100)

MMD14W 260 (118)

MMD18A 295 (134)

MMD18E 225 (102)

MMD20W 300 (136)

MMD22C 220 (100)

MMD23C 220 (100)

MM2CF 63 (29)

*Add 40 lb. (20 kg.) to units with free-cooling or hot water reheat coils.Weights assume reheat and humidifier package is included.

Table 3.5 Indoor unit weights

3 Site Preparation and Equipment Handling 19

Page 26: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

3.6 Equipment Inspection and Handling

CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can causeinjury. Only properly trained and qualified personnel wearing appropriate, OSHA-approved PPEshould attempt to move, lift, remove packaging from or prepare the unit for installation.

Do not un-crate the equipment until it is close to its final location. All required assemblies are banded andshipped in corrugated containers. If any damage is discovered when the unit is un-crated, report it to theshipper immediately. If any concealed damage is later discovered, report it to the shipper and to yourVertiv representative.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide20

Page 27: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

4 INSTALLATIONRefer to the appropriate installation procedures depending the configuration and options of yourLiebert® Mini-Mate2 Thermal Management System.

4.1 Installing Ceiling-mounted Units

WARNING! Risk of ceiling collapse and heavy unit falling. Can cause building and equipmentdamage, serious injury or death. Verify that the supporting roof structure is capable ofsupporting the weight of the unit(s) and the accessories. See Table 3.5  on page 19, for the unitweights. Securely anchor the top ends of the suspension rods and verify that all nuts are tight.

NOTICE

Risk of leaking water/glycol. Can cause equipment and building damage.

Improper installation, application, and service practices can result in water leakage from theunit. Do not mount this unit over equipment and furniture that can be damaged by leakingwater. Install a water-tight drain pan with a drain connection under the cooling unit and theceiling mounted water/glycol condensing unit. Route the drain line to a frequently-usedmaintenance sink so that running water can be observed and reported in a timely manner.Post a sign to alert people to report water flowing from the secondary drain pan. Werecommend installing monitored leak detection equipment for the unit and supply lines and inthe secondary drain pan. Check drain lines periodically for leaks, sediment buildup,obstructions, kinks and/or damage and verify that they are free running.

4.1.1 Installing Suspension Rods and Mounting Ceiling Units

Refer to the Location Considerations on page 18 before beginning installation. These instructions apply toevaporators, indoor air-cooled condensing units, and indoor water/glycol-cooled condensing units.

NOTE: Follow all national and local building, electrical and plumbing codes.

• The ceiling and ceiling supports of existing buildings may require reinforcements.

• Four 3/8-in.-16 TPI threaded suspension rods are required and field supplied.

• The factory-supplied 3/8-in.-16 TPI hardware kit includes the remaining installation hardware.

• Recommended clearance between ceiling grids and building structural members is the unit’sheight plus 3 in. (76 mm).

To install the suspension rods:

1. Install the 4 field-supplied 3/8-in.-16 TPI threaded rods by suspending them from suitablebuilding structural members so that they will align with the 4 mounting locations on the unitbase.

2. Securely anchor the top ends of the suspension rods with field-supplied nuts.

3. Make sure all nuts are tight and locked.

4 Installation 21

Page 28: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

To lift and install the unit on the rods:

1. Using a suitable lifting device that is rated for the weight of the unit (see Indoor Unit Weightson page 19), raise the unit and pass the threaded rods through the 4 mounting locations in theunit base.

2. Attach the threaded rods to the flanges using the plain nuts to hold the unit in place as shownin Figure 4.1  below.

3. Slowly lower the lifting device, making sure that the rods securely hold the weight of the unit.

4. Adjust the plain nuts to distribute the weight of the unit evenly by the rods, making sure thatthe unit does not rest on the ceiling grid and that the unit is level.

NOTE: Evaporator units must be level to properly drain condensate. This does not apply to condensingunits.

5. Use the Nylock nuts to "jam" the plain nuts in place as shown in Figure 4.1  below.

Figure 4.1 Installing threaded rods and hardware of ceiling-mounted units

Item Description Item Description

1 3/8-in. threaded rod, field-supplied 7 3/8-in. fender washer

2 3/8-in. hexnut 8 3/8-in. hexnut

3 3/8-in. washer 9 3/8-in. Nylock locking nut

4 Sleeve 10 Unit base pan (reference)

5 Bracket on unit

6 Isolator

4.2 Installing Air-distribution Components for Evaporators

Your indoor units may include a filter box, ducting, plenums, and grilles. Refer to the appropriateinstallation procedures for each.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide22

Page 29: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

4.2.1 Installing a Filter Box

The optional filter box attaches directly to the return-air opening of the evaporator. The filter boxincludes 1 filter, 16 in. x 20 in. x 4 in. (406 mm x 508 mm x 102 mm).

NOTE: Do not operate the unit without filters installed in return air system.

Grille Installation

CAUTION: Risk of the grille falling. Can cause equipment damage or injury. Do not allow theweight of the unit to rest on the grilles.

The airflow grilles are directional devices and MUST be installed with the louvers properly aligned for unitto operate properly. An air baffle is included with the grille kit and must be installed to ensure proper airdistribution.

To install the grilles:

1. Refer to the instructions included with the kit, and locate the return and discharge grilles.

2. Lower the grilles into place with the louvers in the proper direction. If required, grilles may bescrewed directly to the sub-base.

3. Install a field-supplied T-bar between the two grilles.

4. Install the disposable filter (20 in. x 20 in. x 1 in.) in the return grille.

5. Lower the evaporator unit until the gasket material is compressed 1/4 in. (6 mm).

NOTE: Do not operate the unit without the filter installed in the return air grille.

4 Installation 23

Page 30: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

4.2.2 Guidelines for Ducted Systems

Observe the following for all ductwork:

• Duct work should be fabricated and installed in accordance with local and national codes

• Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit and tocontrol vibration transmission to the building.

• Attach the ductwork to the unit using the flanges provided.

• Locate the unit and ductwork so that the discharge air does not short-circuit to the return-airinlet.

• Duct work that runs through a conditioned space or is exposed to areas where condensationmay occur must be insulated. Insulation of ductwork is vital to prevent condensation duringthe cooling cycle.

• The use of a vapor barrier is required to prevent absorption of moisture from the surroundingair into the insulation.

• If the return-air duct is short or if noise is likely to be a problem, sound-absorbing insulationshould be used inside the duct.

• Duct work should be suspended using flexible hangers. Duct work should not be fasteneddirectly to the building structure.

• For multiple-unit installations, space the units so that the hot condensing unit exhaust air isnot directed toward the air inlet of an adjacent unit.

Consider the following in specific applications of ductwork to evaporator or chilled-water units:

• The total external static pressure for the inlet and outlet ducts, including grille, must notexceed 0.5 in. of water.

Consider the following in specific applications of ductwork to condensing units:

• In applications where the ceiling plenum is used as the heat rejection domain, the discharge airmust be directed away from the condensing unit air inlet and a screen must be added to theend of the discharge duct to protect service personnel. Locate the air discharge a minimum of4 ft from an adjacent wall. Failure to do so may result in reduced air flow and poor systemperformance.

• If the condensing unit draws air from the outside of the building, rain hoods must be installed.Hood intake and duct-work cross-sectional area dimensions should be equal-to or greater-than the area of the condensing unit intake flange. In addition, install a triple-layer bird screenover rain hood openings to eliminate the possibility of insects, birds, water, or debris enteringthe unit. Avoid directing the hot exhaust air toward adjacent doors or windows.

• Duct work should be designed for 950 CFM (1614 CMH).

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide24

Page 31: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

4.3 Installing Condensing-fan Module on Self-contained Air-cooled Systems

1-ton and 1.5-ton capacity, self-contained, air-cooled units use a centrifugal blower in a housing attacheddirectly to the right end of the ceiling-mounted unit.

• Mounting holes are pre-cut at the factory and fasteners are provided.

• A wiring harness is included for the power and control connections between unit blower.

• A capillary tube is included for fan-speed control.

Read all instructions before installing the blower.

NOTICE

Risk of punctured refrigerant lines. Can cause sudden loss of refrigerant and cooling.

During mounting of external disconnect switch, take special care that no refrigerant lines arepunctured or damaged.

To mount the blower on the unit:

1. Before you begin, make sure that the model number of the kit matches the voltage on the unitnameplate because an improper voltage will damage the blower.

2. On the unit, remove the knockouts for the blower wire harness and fan-speed-control capillarytube.

3. Referring to Figure 4.2  on the next page, remove the following screws, but do not remove thetwo screws (item 7) , from either side:

• The three screws (item 2) along the top cover of the unit.

• The two screws from the upper-right and upper-left side of the condenser-coil opening.

4. With the flanges on the top and sides of the blower and the access door toward the front of theunit, place the top flange under the top cover and align the holes in the flange with the holesand threaded studs in the unit.

5. Secure the blower to the unit with 4 screws and flange nuts (item 6) on the sides (2screws/flange nuts each side), and 3 screws (item 2) along the top of the blower.

NOTE: Do not use a drill to install the screws. The drill bit will damage the coil.

6. Install the bushing (item 4) for the capillary tube, route the capillary tube through the bushingand through the knockout (item 8) to the Schrader access valve on the discharge line insidethe unit, and screw the end of the capillary tube onto the valve making sure that there are noleaks.

7. Refer to Condensing-fan Blower Electrical, Control and Power Connections on page 46, andDPN000177, included in the Submittal Drawings on page 101 to connect the blower wireharness (item 3) to the unit.

4 Installation 25

Page 32: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Figure 4.2 Condensing-unit fan installation

Item Description Item Description

1 Knockout for blower-wire harness 524-in. (610-mm) recommended clearance for componentaccess

2 Top screws 6 Side screws/flange nuts (2 each side, 4 sets total)

3 High/Low-voltage wire harness 7 Side screws, do not remove either side.

4Bushing for capillary tube from fan-speedcontroller

8 Knockout for capillary tube from fan-speed controller

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide26

Page 33: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

5 PIPING AND REFRIGERANT REQUIREMENTSAll field-supplied refrigeration piping to the unit must be sweat copper. Use prevailing good pipingpractices for all connections which include brazing copper pipes using a brazing alloy of minimumtemperature of 1350 °F (732 °C) and adhering to all local codes. All other fluid connections to units, withthe exception of the condensate drain, are sweat copper. Factory-installed piping brackets must not beremoved. Field-installed piping must be installed in accordance with local codes and must be properlyassembled, supported, isolated and insulated. Avoid piping runs through noise-sensitive areas, such asoffice walls and conference rooms.

The following pipe connections are required:

• A drain line from the evaporator coil drain pan.

• A drain line from the secondary drain pan (if applicable).

• A water-supply line to the optional humidifier (if applicable).

• On split-systems systems: refrigerant piping connections between the evaporator unit and thecondensing unit.

• On chilled-water systems: connections to the building chilled-water source. See Chilled-waterLoop Piping on page 31, for additional requirements.

• On water/glycol systems: connections to a water or glycol loop. See Water/Glycol Loop Pipingon page 32, for additional requirements.

Refer to specific text and detailed diagrams in this manual for other unit-specific piping requirements.

The pipe connection locations, piping general arrangement and schematics are described in thesubmittal documents included in the Submittal Drawings on page 101.

The following tables list the relevant documents by number and title.

Document Number Title

DPN004408 GeneralArrangement, Split system, Air-cooled

DPN000168 GeneralArrangement, Self-contained , Air-cooled

DPN000166 GeneralArrangement, Self-contained, Water/Glycol-cooled

DPN000169 GeneralArrangement, Water/Glycol-cooledwith freecooling and hot-water reheat options

DPN000167 GeneralArrangement, Self-contained, Chilled-water

Table 5.1 Piping General-arrangement Drawings

Document Number Title

Evaporator andChilled-water Units

DPN004302 PipingConnections

Table 5.2 Piping Connection Drawings

5 Piping andRefrigerant Requirements 27

Page 34: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

5.1 Fluid Piping Required

5.1.1 Drain Line Installation Requirements

NOTICE

Risk of water backing up in the drain line. Leaking and overflowing water can cause equipmentand building damage.

Do not install an external trap in the drain line. This line already has a factory-installed trapinside the cabinet. Installation of a second trap will prevent drain-water flow and will cause thewater to overflow the drain pan.

This line may contain boiling water. Use copper or other material that is rated for handlingboiling water for the drain line. Sagging condensate drain lines may inadvertently create anexternal trap.

A 3/4 in. (19.1 mm) NPT-female connection is provided for the evaporator-unit condensate drain. Thisconnection also drains the humidifier if applicable. The evaporator drain pan includes a float switch toprevent unit operation if the drain becomes blocked.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide28

Page 35: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Observe the following requirements and refer to Figure 5.1  below, when installing and routing the drainline:

• The drain line must be sized for 2 gpm (7.6 l/m) flow.

• The drain line must be located so it will not be exposed to freezing temperatures.

• The drain should be the full size of the drain connection.

• The drain line must slope continuously away from the unit.

• Do not externally-trap the drain line.

• The drain line must be rigid enough that it does not sag between supports, whichunintentionally creates traps.

• Use copper or other material suitable for draining water that can reach temperatures up to212°F (100°C).

• When the evaporator is installed below the level of the gravity-fed drain line, the optionalcondensate pump kit is required. See Condensate-drain Pump Kit on the next page.

NOTE: Remove the shipping band from the float switch in the evaporator pan before operating theunit.

Figure 5.1 Correct and Incorrect gravity drains

Item Description

1 Correct drain installation.

2 Incorrect. Do not trap externally.

3 Incorrect. Sagging between supports and bowed line causes unintentional external traps.

4 Continuous downward slope away from the unit.

5 Unit

6 External trap

7 Unintentional traps from bowing of line. Lines must be rigid enough not to bow or sag between supports, creating a trap.

Table 5.3 Gravity-fed Drain Line Figure Descriptions

5 Piping andRefrigerant Requirements 29

Page 36: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

5.1.2 Condensate-drain Pump Kit

WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all localand remote electric power supply disconnect switches and verify with a voltmeter that power isoff before working within any electric connection enclosures. Service and maintenance workmust be performed only by properly trained and qualified personnel and in accordance withapplicable regulations and manufacturers’ specifications. Opening or removing the covers toany equipment may expose personnel to lethal voltages within the unit even when it isapparently not operating and the input wiring is disconnected from the electrical source.

The optional condensate pump kit is required when the evaporator is installed below the level of thegravity-fed drain line. The condensate pump is field-installed alongside the evaporator unit.

Document Number Title

DPN000174 Field-installed pump connection

Table 5.4 Condensate-drain Pump Drawings

To install the condensate-drain pump:

1. Refer to the instructions and drawings supplied with the pump. The preferred mountingmethod is to attach the pump to the unit with the mounting-bracket kit instead of mountingthe pump to duct work.

2. Disconnect all power to the unit.

3. Remove the access panels.

NOTE: Remove the shipping band from the float switch in the evaporator pan.

4. Use mounting brackets if the pump is not attached to ductwork.

5. The pump inlet must be at least 1/2 in. (13 mm) below the evaporator drain. Mount the pump tothe unit exterior as shown the piping-connection diagram for your unit, see Table 5.4  above.

6. Connect 3/4 in. flexible rubber tubing with a hose clamp (both supplied with pump kit) to the3/4 in. hose barb fitting on the pump.

7. Connect the evaporator drain to 3/4 in. NPT female hose assembly on the pump inlet using 3/4in. hard pipe. Do not install a trap in the line. Provide at least 1 in. (25 mm) clearance betweenthe access panel and the drain line. Support the piping as required.

8. Connect a drain line to the pump discharge 3/8 in. O.D. Cu (compression fitting provided).

9. Connect electric leads L1 and L2 to the unit line-voltage terminal block. Connect the groundlead to the lug near the terminal block.

10. Connect wires from the auxiliary pump contacts to unit terminals TB1-8 and TB1-9 to enableunit shut down upon high-water condition in the pump.

11. Reinstall the access panels.

12. Reconnect power to the unit.

13. Run the unit to make sure the pump works properly. Operate the pump and check the drainline and discharge line for leaks. Correct as needed.

NOTE: 3/4-in. flexible rubber tubing assembly (supplied with pump kit) must be installed on pump endof rigid piping (field-provided and supported as required).

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide30

Page 37: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

5.1.3 Water-supply line to the Humidifier

Units supplied with the optional humidifier package have a 1/4-in. (6.2-mm) OD copper compressionfitting with ferrule at the water-supply connection.

• The supply pressure range is 10 psig to 150 psig (69 to 1034 kPag).

• The required flow rate is 1 gpm (3.8 lpm).

• Install a shut-off valve in the supply line to isolate the humidifier for maintenance.

NOTE: Do not route humidifier water-supply line in front of the filter-box access panel.

To install the water supply:

1. Cut the tube square and remove any burrs.

2. Slide nut, then the sleeve on tube. The threaded end of the nut faces the end of the tube.

3. Insert the tube into the fitting, seating it against the stop shoulder and tighten the nut hand-tight to the body.

4. Use a wrench to tighten the nut 1-1/4 to 2-1/4 turns.

NOTICE

Risk of improper tightening of the piping fittings. Can damage fittings and cause leaks.

Use caution not to over-tighten or under-tighten the piping fittings.

5.1.4 Chilled-water Loop Piping

NOTICE

Risk of piping-system corrosion and freezing fluids. Can cause leaks resulting in equipmentand very expensive building damage. Cooling coils and piping systems are at high risk offreezing and premature corrosion. Fluids in these systems must contain the proper antifreezeand inhibitors to prevent freezing and premature coil and piping corrosion. The water orwater/glycol solution must be analyzed by a competent local water treatment specialist beforestart up to establish the inhibitor and antifreeze solution requirement and at regularlyscheduled intervals throughout the life of the system to determine the pattern of inhibitordepletion.

The complexity of water/glycol solution condition problems and the variations of requiredtreatment programs make it extremely important to obtain the advice of a competent andexperienced water treatment specialist and follow a regularly scheduled coolant fluid systemmaintenance program.

Water chemistry varies greatly by location, as do the required additives, called inhibitors, thatreduce the corrosive effect of the fluids on the piping systems and components. The chemistryof the water used must be considered, because water from some sources may contain corrosiveelements that reduce the effectiveness of the inhibited formulation. Sediment deposits preventthe formation of a protective oxide layer on the inside of the coolant system components andpiping. The water/coolant fluid must be treated and circulating through the systemcontinuously to prevent the buildup of sediment deposits and or growth of sulfate reducingbacteria.

5 Piping andRefrigerant Requirements 31

Page 38: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Proper inhibitor maintenance must be performed in order to prevent corrosion of the system.Consult glycol manufacturer for testing and maintenance of inhibitors.

Commercial ethylene glycol, when pure, is generally less corrosive to the common metals ofconstruction than water itself. It will, however, assume the corrosivity of the water from which itis prepared and may become increasingly corrosive with use if not properly inhibited.

We recommend installing a monitored fluid-detection system that is wired to activate theautomatic-closure of field-installed coolant-fluid supply and return shut-off valves to reducethe amount of coolant-fluid leakage and consequential equipment and building damage. Theshut-off valves must be sized to close-off against the maximum coolant-fluid system pressurein case of a catastrophic fluid leak.

NOTICE

Risk of no-flow condition. Can cause equipment damage.

Do not leave the water/coolant fluid-supply circuit in a no-flow condition. Idle fluid allows thecollection of sediment that prevents the formation of a protective oxide layer on the inside oftubes. Keep unit switched On and water/coolant fluid-supply circuit system operatingcontinuously.

See Table 5.5  below, for the chilled-water loop requirements.

Install manual service shutoff valves at the supply and return lines of each unit. These shutoff valves areused for routine service and for emergency isolation of the unit.

Refer to the appropriate piping general-arrangement schematics for your system for the recommended,field-installed hardware such as shut-off valves and hose bibs. See Table 5.1  on page 27.

NOTE: Chilled-water supply and return lines must be insulated to prevent condensation of the lines.

Minimum Recommendedwater temperature, °F (°C)

Standard-pressure valvedesign pressure, Psig (Kpag)

Supply/ReturnConnection Sizes,

in.

42 (5.5) 300 (2068) 5/8 O.D. Cu

Table 5.5 Requirements for chilled-water loop installation

5.1.5 Water/Glycol Loop Piping

NOTICE

Risk of frozen pipes and corrosion from improper coolant mixture. Can cause water leaksresulting in equipment and building damage.

When piping or the cooling unit may be exposed to freezing temperatures, charge the systemwith the proper percentage of glycol and water for the coldest design ambient temperature.Automotive antifreeze is unacceptable and must NOT be used in any glycol fluid system. Useonly HVAC glycol solution that meets the requirements of recommended industry practices.

Do not use galvanized pipe.

Install manual service shut-off valves at the supply and return line to each unit. This permits routineservice and emergency isolation of the unit. Refer to the appropriate submittal drawing for the piping-connection sizes of your unit, see Table 5.2  on page 27.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide32

Page 39: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Refer to the appropriate piping general-arrangement schematics for your system for the recommended,field-installed hardware such as shut-off valves. See Table 5.1  on page 27.

When the fluid quality is poor, we recommend installing a 16-20# mesh Y-strainer filter in the supply lineto extend the service life of the coaxial condensers. These filters must be easily replaced or cleaned.

The standard maximum fluid pressure is 150 psig (1034 kPa) and 350 psig (2413 kPa) for high-pressuresystems. For applications above this pressure, contact a Vertiv representative.

The water/glycol-cooled system will operate in conjunction with a cooling tower, city water or drycooler.

NOTE: HVAC-grade ethylene or propylene glycol should be used on glycol systems. Automotiveantifreeze must not be used.

Water/Glycol-coolant Regulating Valve

Water/glycol-cooled units include a coolant-flow regulating valve that is factory-adjusted and should notneed field adjustment.

Standard-pressure and high-pressure valves are adjusted differently. Contact Vertiv technical supportbefore making any adjustments.

5.1.6 Free-cooling Coil Piping

An optional, free-cooling coil outlet can be field-piped to the condensing-unit inlet on water-cooledsystems if a 3-way regulating valve is installed inside the water/glycol condensing unit.

Refer to the appropriate piping general-arrangement schematics for your system for the details of a free-cooling coil installation. See Table 5.1  on page 27.

NOTE: If the free-cooling coil is piped to an open water tower, a CU/NI (copper-nickel) type coil mustbe ordered to prevent corrosion of the copper tubes, or a heat exchanger must separate the towerwater from the free-cooling loop.

5.1.7 Hot-water Reheat Coil Piping

On chilled-water systems, building hot water can be piped to a factory-installed hot water reheat coil,located downstream of the cooling coil. A factory-installed solenoid valve opens upon a call for reheat.

Refer to the appropriate piping general-arrangement schematics for your system for the details of a hot-water reheat coil installation. See Piping General-arrangement Drawings on page 27.

5 Piping andRefrigerant Requirements 33

Page 40: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

5.2 Refrigerant Piping

WARNING! Risk of over-pressurization of the refrigeration system. Can cause piping rupture,explosive discharge of high-pressure refrigerant, loss of refrigerant, environmental pollution,equipment damage, injury, or death. This unit contains fluids and gases under high pressure.Use extreme caution when charging the refrigerant system. Do not pressurize the systemhigher than the design pressure marked on the unit's nameplate. Relieve pressure beforecutting into or making connections/disconnections to the piping system. Local building orplumbing codes may require installing a pressure-relief device in the system.

Consult local building and plumbing codes for installation requirements of additional pressure-relief devices when isolation valves are field installed. Do not isolate any refrigerant circuitsfrom over pressurization protection. The PFH condensing units include a factory-installedpressure-relief valve mounted on top of the receiver. The valve is rated for a maximum workingpressure of 475 psig.

NOTICE

Risk of oil contamination with water. Can cause equipment damage.

Liebert®  Mini-Mate2 DX systems require the use of POE (polyolester) oil. POE oil absorbs waterat a much faster rate when exposed to air than previously used oils. Because water is theenemy of a reliable refrigeration system, extreme care must be used when opening systemsduring installation or service. If water is absorbed into the POE oil, it will not be easily removedand will not be removed through the normal evacuation process. If the oil is too wet, it mayrequire an oil change. POE oils also have a property that makes them act as a solvent in arefrigeration system. Maintaining system cleanliness is extremely important because the oil willtend to bring any foreign matter back to the compressor.

NOTICE

Risk of improper refrigerant charging. Can cause equipment damage.

Refrigerant charge must be weighed into compressorized split systems before they are started.

Self-contained systems are factory-charged. To optimize the refrigerant charge on water/glycol units, seeOptimizing Refrigerant Charge on Water/Glycol Units on page 41.

Split systems require 2 refrigerant lines between the evaporator and the condensing unit:

• 1 insulated copper suction line

• 1 copper liquid line

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide34

Page 41: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Observe the following requirements for all field-supplied refrigeration piping:

• All piping must be ACR-type copper.

• For all piping connections, use prevailing good piping practices, which includes brazing copperpipes using a brazing alloy of a minimum temperature of 1350°F (732°C) and adhere to localcodes.

• Factory-installed piping brackets must not be removed.

• Piping must be installed in accordance with local codes, and must be properly assembled,supported, isolated, and insulated.

• Use prevailing good refrigeration practices such as piping supports, leak testing, evacuation,dehydration and charging of the refrigeration circuits.

• Isolate the refrigeration piping from the building with vibration-isolating supports.

• Avoid piping runs through noise-sensitive areas such as office walls and conference rooms.

• When sealing openings in walls and to reduce vibration transmission, use a soft, flexiblematerial to pack around the tubes to prevent tube damage.

• When installing remote condensing units above the evaporator, the suction gas lines should betrapped at the evaporator. These traps will retain refrigerant oil in the off cycle. When the unitstarts, oil in the traps is carried up the vertical risers and returns to the compressors.

5.2.1 Piping when Condensing Unit is Above or Below Evaporator

Refer to Table 5.6  below, for the maximum vertical rise/fall between condensing unit and evaporator.

When installing remote condensing units above the evaporator, trap the suction gas line at theevaporator as shown in Figure 5.2  on the next page. This trap will retain refrigerant oil during the "Off"cycle. When the unit starts, oil in the trap is carried up the vertical riser and returns to the compressor. Forrises over 25 ft (7.6 m), trap every 20 ft (6 m) or evenly divided.

When installing remote condensing units below the evaporator, trap the suction gas line with an invertedtrap the height of the evaporator as shown Figure 5.2  on the next page. This prevents refrigerantmigration to the compressor during "Off" cycles. The maximum recommended vertical-level drop tocondensing unit is 15 ft (4.6 m).

Maximum Equivalent Pipe Length,ft (m)

Maximum Condensing Unit LevelAbove Evaporator, ft (m)

Maximum Condensing Unit LevelBelow Evaporator, ft (m)

150 (45) 40 (12) 15 (4.6)

Maximum recommended total equivalent pipe length is 150 ft (46 m). Suction and liquid lines may requireadditional specialty items when vertical lines exceed 20 ft. (6 m) and/or condensing unit installationis more than 15 ft. (4.6 m) below the evaporator. Contact VertivTechnical Support for assistance.

Table 5.6 Pipe length and condensing unit elevation relative to evaporator

5 Piping andRefrigerant Requirements 35

Page 42: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Figure 5.2 Refrigerant piping diagram when condenser is above or below evaporator

NOTE: Any horizontal pipe must be pitched down toward the condensing unit at a minimum rate of1/2 in. (13 mm) per 10 ft (3 m) to assure oil return to compressor.

Item Description

1 Condensing unit above evaporator

2 Condensing unit below evaporator

3 Evaporator

4 Condensing unit

5.2.2 Refrigerant-line Sizes and Equivalent Lengths

The following tables list information required to field-install the refrigerant piping for the system.

The pipe connection sizes for your equipment are included in the appropriate submittal documentsincluded in the Submittal Drawings on page 101.

Equivalent Length,ft(m)

1 Ton 1.5 Ton

Suction Liquid Suction Liquid

50 (15) 5/8” 3/8” 5/8” 3/8”

75 (23) 5/8” 3/8” 7/8” 3/8”

100 (30) 7/8” 3/8” 7/8” 3/8”

125 (38) 7/8” 3/8” 7/8” 1/2”

150 (45) 7/8” 3/8” 7/8” 1/2”

1. Consult factory for proper line sizing for runs longer than 150 ft (45 m).

2. Suction-line and liquid-line sizing based on < 3-psi pressure drop in each and on suction-line refrigerant velocities>700 FPM(3.6 m/s), horizontal and 1000 FPM (5.1 m/s) vertical.

Source: DPN000788 Rev. 13

Table 5.7  Recommended refrigerant line sizes, O.D. cu by equivalent length

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide36

Page 43: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Copper PipeOD, in.

90 DegreeElbow Copper

90 DegreeElbow Cast

45 DegreeElbow

TeeGateValve

GlobeValve

AngleValve

1/2 0.8 (0.24) 1.3 (0.39) 0.4 (0.12) 2.5 (0.76) 0.26 (0.07) 7.0 (2.13) 4.0 (1.21)

5/8 0.9 (0.27) 1.4 (0.42) 0.5 (0.15) 2.5 (0.76) 0.28 (0.08) 9.5 (2.89) 5.0 (1.52)

3/4 1.0 (0.3) 1.5 (0.45) 0.6 (0.18) 2.5 (0.76) 0.3 (0.09) 12.0 (3.65) 6.5 (1.98)

7/8 1.45 (0.44) 1.8 (0.54) 0.8 (0.24) 3.6 (1.09) 0.36 (0.1) 17.2 (5.24) 9.5 (2.89)

1-1/8 1.85 (0.56) 2.2 (0.67) 1.0 (0.3) 4.6 (1.4) 0.48 (0.14) 22.5 (6.85) 12.0 (3.65)

1-3/8 2.4 (0.73) 2.9 (0.88) 1.3 (0.39) 6.4 (1.95) 0.65 (0.19) 32.0 (9.75) 16.0 (4.87)

1-5/8 2.9 (0.88) 3.5 (1.06) 1.6 (0.48) 7.2 (2.19) 0.72 (0.21) 36.0 (10.97) 19.5 (5.94)

Refrigerant trap = Four times equivalent length of pipe per this table

Table 5.8 Equivalent lengths for various pipe fittings, ft (m)

5.2.3 Refrigerant Charge Requirements

Model#

Charge R-407C, oz (kg)

60 Hz Unit Type

MMD12A/F Self-contained, air-cooled 42 (1.19)

MMD14W/GSelf-contained, water/glycol-

cooled27 (0.77)

MMD12E/KSplit-system evaporator, air-

cooled3 (0.085)

MMD18A/F Self-contained, air-cooled 49 (1.39)

MMD20W/GSelf-contained, water/glycol-

cooled28 (0.79)

MMD18E/KSplit-system evaporator, air-

cooled4 (0.11)

PFH014A-_LN Split-system condensing unit 134 (3.80)

PFH020A-_LN Split-system condensing unit 134 (3.80)

1. Self-containedDX units are pre-chargedwith R-407C refrigerant.

2. Split-system units must be field-charged. Use Table 5.10  on the next page to determine the charge to be added forfield-fabricated refrigerant lines.

3. For units with Hot Gas Reheat coil, add 18-oz (0.51 kg) refrigerant to listed values.

Table 5.9 R-407C refrigerant unit charge1

5 Piping andRefrigerant Requirements 37

Page 44: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Line Size, OD, in. Liquid Line, lb/100 ft (kg/30 m) Suction Line, lb/100 ft (kg/30 m)

3/8 3.6 (1.6) —

1/2 6.7 (3.0) 0.2 (0.1)

5/8 10.8 (4.8) 0.3 (0.1)

3/4 16.1 (7.2) 0.4 (0.2)

7/8 22.3 (10.0) 0.5 (0.3)

1-1/8 38.0 (17.0) 0.9 (0.4)

1-3/8 57.9 (25.9) 1.4 (0.7)

Source: DPN003099Rev. 1

Table 5.10 Line charges of R-407C refrigerant using Type-L copper tube

5.2.4 Field-fabricated Refrigeration Piping

Use copper pipe with high-temperature brazed joints for all field-fabricated refrigeration piping. Use abrazing alloy with a minimum temperature of 1350°F (732°C), such as Sil-Fos. Avoid soft solders such as50/50 or 95/5.

1. Measure pipe runs and calculate pipe size and equivalent feet of suction and liquid lines perthe tables in Refrigerant-line Sizes and Equivalent Lengths on page 36.

2. Determine the type of trap to use on the suction line next to the evaporator based on theposition of the condensing unit per Pipe length and condensing unit elevation relative toevaporator on page 35.

3. Determine the number and placement of traps on vertical rises, and install traps on thesuction-line piping at the base of a rise over 5-ft (1.5-m) and every 20-ft (6-m) of vertical rise.

4. The evaporator and condensing units come with an inert-gas holding charge. Releasepressure before cutting the spun-closed end of the piping.

NOTE: You can only evacuate the system properly if you open the hot-gas by-pass and liquid-linesolenoid valves (if equipped) inside the condensing unit and you account for all check valves, seeFigure 5.3  on the facing page. Connect manifold-gauge hoses to the discharge- and suction-lineSchrader ports, remove the solenoid-valve holding coils from the hot-gas by-pass and liquid-linesolenoid valves (if equipped), and apply a solenoid-valve service magnet to the valves to obtain aproper vacuum.

5. Use a flow of dry nitrogen through the piping during brazing to prevent formation of copper-oxide scale inside the piping. A pure dry-nitrogen flow of 1 to 3 ft3/min (0.5 to 1.5 l/s) inside thepipe during brazing is sufficient to displace the air. Control the flow using a suitable meteringdevice.

NOTE: Copper oxide forms when copper is heated in the presence of air. POE oil will dissolve theseoxides from inside the copper pipes and deposit them throughout the system, clogging filter driers andaffecting other system components.

5.2.5 Evacuation and Leak-testing Air-cooled Systems

For proper leak-check and evacuation, you must open all system valves and account for all check valves,see Figure 5.3  on the facing page.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide38

Page 45: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Figure 5.3 Valves and Connections

Item Description

1 Apply amanifold gauge hose on the suction-line Schrader port.

2 Apply amanifold gauge hose on the discharge-line Schrader port.

3 Unplug the wires and remove the solenoid-valve holding coils, then apply solenoid-valve service magnets to the valves.

4 Suction line

5 Liquid injection-valve bulb

6

Schrader port with valve core

NOTE: The system includes a factory-installed Schrader valve with core in the liquid line downstream of thereceiver. Proper evacuation of the condenser side of the system can be accomplished only using the downstreamSchrader valve. See the appropriate piping schematic for your system in Submittal Drawings on page 101.

7 Scroll compressor

8 High-pressure switch

9 Condenser coil

10 Hot-gas bypass solenoid valve

5 Piping andRefrigerant Requirements 39

Page 46: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Item Description

11 Hot-gas bypass control valve

12 Liquid injection

13 3-wayhead-pressure control valve

14 Check valve

15 Pressure-balancing valve

16 Sight glass

17 Pressure-relief valve

18 Lee-Temp receiver

19 Receiver-heater pressure-limiting switch

20 Liquid-line solenoid valve

21 Liquid line

To evacuate and leak-test the system:

1. Open the liquid-line solenoid valve and hot-gas by-pass solenoid valve by removing theholding coils, and apply a solenoid-valve service magnet to the valves.

2. Connect manifold-gauge hoses on the discharge- and suction-line Schrader ports, open theservice valves, and place a 150 Psig (1034 kPa) charge of dry nitrogen with a tracer ofrefrigerant, then check the system for leaks with a suitable leak detector.

3. After completion of leak testing, release the test pressure, (observe local code) and pull aninitial deep vacuum of 500 microns on the system with a suitable pump.

4. After 4 hours, check the pressure readings and, if they have not changed, break vacuum withdry nitrogen. Pull a second and third vacuum to 500 microns or less. Re-check the pressureafter 2 hours.When the 3 checks are complete, proceed to Charging Air-cooled Systems below.

5.2.6 Charging Air-cooled Systems

NOTICE

Risk of improper refrigerant charging. Can cause equipment damage.

R-407C is a blended refrigerant and must be introduced and charged from the cylinder only asa liquid.

When adding liquid refrigerant to an operating system, it may be necessary to add therefrigerant through the valve in the compressor suction line. Care must be exercised to avoiddamage to the compressor. We recommend connecting a sight glass between the charginghose and the compressor suction service valve. This will permit adjustment of the cylinderhand valve so that liquid can leave the cylinder while allowing vapor to enter the compressor.

To calculate the charge for the system:

1. Check the nameplate on the indoor unit for refrigerant type to use.

2. Refer to Table 5.9  on page 37, and Table 5.10  on page 38, and calculate the amount ofcharge for the system including the evaporator, condensing unit, and interconnecting piping.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide40

Page 47: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

3. Accurately weigh-in as much of the system charge as possible before re-installing coils onliquid-line solenoid valve and hot-gas by-pass solenoid valve, and starting the unit.

5.2.7 Field Charge Verification for Air-cooled Systems

An integral sight glass is provided with the receiver to assist in field-charge verification. During chargeverification, set the control temperature down to keep the system running. If the system is equipped withhot-gas bypass, de-energize it by removing power from the hot-gas solenoid valve coil. To remove power,disconnect the solenoid leads from the unit contactor in the electric box, see Figure 5.3  on page 39.When charge verification is complete, replace and secure all wire connections and covers.During operation at design ambient temperatures, (95 or 105°F; 35 or 41°C) the charge level is above thesight glass in the receiver. If levels are below the sight glass, an under-charge condition is likely. If levelsare above the sight glass and higher discharge pressures than normal are observed, an overchargecondition may be likely. However, verify that other high-discharge pressure causes such as dirty coil andrestricted air flow are not responsible before removing charge.

At temperatures below design ambient temperature, refrigerant backs into the condenser coil and thelevel in the receiver drops below the sight glass. If you are trying to verify charge level at lower ambienttemperatures, block the condenser coil to maintain 240 psig (1655 kPa) discharge pressure to ensure thehead-pressure-control valve is closed. At these conditions the charge level should be above the sightglass in the receiver.

NOTE: If no level is visible in the sight glass, add charge until the level is in the middle of the sight glass.Check the discharge pressure during this procedure and adjust coil restrictions to maintain 240 psig (1655 kPa). Once the charge is in the middle of the sight glass, add additional system charge per Table5.11  below. After charging, unblock the coil and allow the unit to operate normally. After conditionshave stabilized, restrict the coil if required to maintain 240 psig (1655 kPa) discharge pressure andverify that the charge level is above the sight glass.

ModelNumbers R-407C

60Hz 50Hz oz (kg)

PFH014A-_L — 4 (0.11)

PFH020A-_L — 4 (0.11)

See Table 5.9  on page 37, for base charge amount of the condensing unit.

Table 5.11 Field verification charge addition

5.2.8 Documenting Refrigerant Charge on Air-cooled Units

When the unit is charged, you must record the total system charge value on the condensing unit's serialtag. The total system charge includes the evaporator, condensing unit, and interconnecting lines.

5.2.9 Optimizing Refrigerant Charge on Water/Glycol Units

1. Operate the unit at full heat load, normal room conditions and normal water/glycol fluidtemperatures for a minimum of 30 minutes before measuring stable unit superheat andsubcooling temperatures and adjusting charge levels.

• Condensing temperatures should be in range of 100 to 130°F (38 to 54°C) depending onfluid type and fluid temperature.

• Full heat load is required to stabilize the system.

5 Piping andRefrigerant Requirements 41

Page 48: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

2. Attach pressure and temperature instruments to the liquid line of the condensing unit. Use thefactory-installed Schrader valve located in the liquid line of the condenser. Measure the initialsubcooling.

NOTE: To determine subcooling measurement, a liquid-line pressure reading (at the factory-installedSchrader tap) must be measured along with the temperature reading on the liquid line. Convert theliquid-line pressure reading into a liquid temperature by utilizing a Pressure-temperature Guide.Subtract the measured temperature from the liquid-saturation temperature. The difference issubcooling.

3. Adjust refrigerant charge levels as needed to achieve subcooling range of 12 to 14°F(6.7 to 7.8°C) while maintaining full load conditions.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide42

Page 49: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

6 ELECTRICAL CONNECTION REQUIREMENTS

WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supplydisconnect switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective equipment (PPE) per NFPA 70E before working within theelectric control enclosure. Failure to comply can cause serious injury or death. Customer mustprovide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceedingwith installation, read all instructions, verify that all the parts are included and check thenameplate to be sure the voltage matches available utility power. The Liebert® controller doesnot isolate power from the unit, even in the “Unit Off” mode. Some internal components requireand receive power even during the “Unit Off” mode of the controller. The only way to ensurethat there is NO voltage inside the unit is to install and open a remote disconnect switch. Referto unit electrical schematic. Follow all local codes.

WARNING! Risk of improper wire and loose electrical connections. Can cause overheated wireand electrical connection terminals resulting in smoke, fire, equipment and building damage,injury or death. Use correctly sized copper wire only and verify that all electrical connections aretight before turning power On. Check all electrical connections periodically and tighten asnecessary.

NOTE: Seal openings around piping and electrical connections to prevent air leakage. Failure to do socould reduce the unit's cooling performance.

NOTICE

Risk of improper electrical supply connection. Can cause equipment damage.

See transformer label for primary tap connections. Installer will need to change transformerprimary taps if applied unit voltage is other than pre-wired tap voltage.

All power and control wiring and ground connections must be in accordance with the National ElectricalCode and local codes. Refer to the equipment serial-tag data for electrical requirements.

A manual electrical disconnect switch should be installed in accordance with local codes and distributionsystem. Consult local codes for external disconnect requirements.

Each unit is shipped from the factory with internal wiring completed. Refer to the unit's electricalschematic when making connections. Electrical connections to be supplied by the users and made at theinstallation site are:

• Power supply to each ceiling unit.

• Power supply to outdoor condensing unit, if applicable.

• Control wiring (shielded) between the evaporator unit and condensing unit, if applicable.

• Control wiring (shielded) between the control panel (wall box) and the evaporator or chilled-water unit's control board.

The electrical connections are described in the submittal documents included in the Submittal Drawingson page 101.

The following table lists the relevant documents by number and title.

6Electrical Connection Requirements 43

Page 50: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Document Number Title

Evaporator andChilled-water Units

DPN000175 ElectricalConnections, Air-cooled, Water/Glycol-cooled andChilled-water units

DPN000176 ElectricalConnections, Air-cooled, Water/Glycol-cooled andChilled-water units

DPN004850 Arrangement andDimensions, Unit-mounted IS-UNITY-DP for BMSCommunication

DPN004911 Arrangement andDimensions, Wall-mounted IS-UNITY-DP for BMSCommunication

DPN004854 ElectricalConnections, IS-UNITY-DP for BMSCommunication

DPN004947 Arrangement andDimensions, Wall-mounted iCOM™CMSenclosure

DPN003523 Arrangement andDimensions, Unit-mounted iCOM™CMSenclosure

DPN003556 ElectricalConnections, iCOM™CMS for Mobile CloudCommunication

Self-containedCondensingUnits

DPN000177 ElectricalConnections, Air-cooledCondensing unit Blower

Table 6.1 Electrical Field-connection Drawings

6.1 Input-power Connection Requirements

WARNING! Risk of loose electrical connections. Can cause overheating of wire, smoke and fireresulting in building and equipment damage, injury or death. Use copper wiring only. Verify thatall connections are tight.

NOTE: Refer to specifications for full-load amp. and wire-size amp. ratings.

Voltage supplied must agree with the voltage specified on the unit serial tag. If a field-supplied disconnectswitch is required, it may be bolted to the ceiling unit, but not to any of the removable panels. This wouldinterfere with access to the unit. Make sure that no refrigerant lines are punctured when mounting thedisconnect switch.

Route the electrical-service conduit through the hole provided in the cabinet and terminate it at theelectric box. Make connections at the factory terminal block or disconnect switch, L1, L2, L3. Connectearth ground to lug provided. See transformer label for primary tap connections. Installer will need tochange transformer primary taps if applied unit voltage is other than pre-wired tap voltage. For 208-VACapplications, the low-voltage transformer tap must be changed. Refer to the electrical schematic.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide44

Page 51: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

6.2 Control-wiring Connection Requirements

6.2.1 Wall-box Controller Control Connections

A four-conductor (thermostat type) field-supplied, shielded wire must be connected between theevaporator control board and the wall box display. Refer to the appropriate submittal drawings for yoursystem for electrical connections. See Table 6.1  on the previous page.

6.2.2 Split-system Condensing-unit Control Connections

A field-supplied, shielded, 4-wire control connection (24 VAC) is required between the evaporator and thecondensing unit.

Control wiring must be installed in accordance with the National Electrical Code (NEC) Class 1 or Class 2circuit according to wire-routing conditions chosen and local codes. Water/Glycol-cooled units require aClass 1 circuit. If installing a Glycol unit, see Water/Glycol-cooled Unit Control Connections below, forspecific requirements.

Control wiring between the evaporator and the condensing unit must be shielded and sized for a voltagedrop of less than 1 volt, see Table 6.2  below, for recommended minimum gauge by distance. Connect theshield wire to earth (ground) at the Liebert® equipment. Avoid running the low-voltage connections nearhigh-voltage lines or loads such as light ballasts.

NOTE: Do not connect additional electrical devices to the control circuit. The internal-controltransformer is only sized for factory-supplied components. Refer to the appropriate submittaldrawings for your system for electrical connections. See Table 6.1  on the previous page.

Maximum Distance,* ft (m) Minimum Wire Gauge, AWG (mm2)

50 (15) 20 (0.75)

75 (23) 18 (1.0)

100 (30) 18 (1.0)

150 (45) 16 (1.5)

* One-waycontrolwire run between outdoor condensing unit and evaporator.

Table 6.2 Recommended minimum wire size

6.2.3 Water/Glycol-cooled Unit Control Connections

Glycol-cooled units require an additional field-supplied, 2-conductor (thermostat type) wire connectionbetween the evaporator unit and the drycooler. Units with water-tower loops can be wired for circulationpump/valve requirement. A Class 1 circuit is required for Water/Glycol units. Control wiring must beinstalled in accordance with NEC and local codes. Refer to the appropriate submittal drawings for yoursystem for electrical connections. See Table 6.1  on the previous page.

6.2.4 Additional Control Connections

If your system includes other, optional monitoring and control devices, additional control wiring will berequired.

6Electrical Connection Requirements 45

Page 52: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

6.3 Condensing-fan Blower Electrical, Control and Power Connections

Field connections are required at the ceiling unit using the provided wiring harness. A 4-wire connectionis required from the condensing fan to the ceiling unit.

The ceiling unit power connections are made at the terminal block or disconnect switch in the lower left-hand corner of the electric panel (middle). The power terminal connections are labeled L1 and L2. (For208 VAC applications, change the input transformer connection as described in the electrical schematicattached to cabinet). Self-contained, air-cooled models require power connections from the evaporatorceiling unit to the condensing fan.

NOTICE

Risk of incorrect input power supply. Can cause equipment damage.

The line voltage supplied must correspond with the voltage specified on the unit’s nameplate.

The electrical connection locations and wiring is described in the DPN000177, included in the SubmittalDrawings on page 101. See Installing Condensing-fan Module on Self-contained Air-cooled Systems onpage 25, for the installation steps.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide46

Page 53: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

7 CHECKLIST FOR COMPLETED INSTALLATION1. Proper clearances for service access have been maintained around the equipment.

2. Equipment is level and mounting fasteners are tight.

3. Piping completed to refrigerant or coolant loop (if required). Refrigerant charge added.

4. Condensate pump installed (if required).

5. Drain line(s) connected and checked for leaks.

6. Water-supply line connected to humidifier (if required). Routed to allow air-filter removal.

7. All piping connections are checked for leaks. (Correct as required.)

8. Field-provided, water-tight, secondary drain pan with drain is installed under all cooling unitsand ceiling-mounted water/glycol condensing units.

9. Drain from secondary drain pan is routed to a frequently-used maintenance sink with signsposted to alert people to report water/glycol flowing from drain pan.

10. Filter box installed on ducted units.

11. Ducting completed or optional grille installed.

12. Filters installed in return air duct.

13. Line voltage to power wiring matches equipment serial tag.

14. Power wiring connections completed between disconnect switch, evaporator and condensingunit, including earth ground.

15. Power-line circuit breakers or fuses have proper ratings for equipment installed.

16. Wall-mounted control is mounted and wired to the cooling unit.

17. Shielded control wiring connections used and completed to evaporator and condensing unit (ifrequired), including wiring to wall-mounted control panel and optional controls.

18. Control-panel DIP switches set based on customer requirements.

19. All wiring connections are tight.

20. Foreign materials have been removed from inside and around all equipment installed (shippingmaterials, construction materials, tools, etc.)

21. Fans and blowers rotate freely without unusual noise.

22. Inspect all piping connections for leaks during initial operation. Correct as needed.

23. Rubber band is removed from evaporator condensate-pan float switch.

7 Checklist for Completed Installation 47

Page 54: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide48

This page intentionally left blank

Page 55: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

8 INITIAL START-UP CHECKSAND COMMISSIONING PROCEDUREFOR WARRANTY INSPECTION

WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supplydisconnect switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective equipment (PPE) per NFPA 70E before working within theelectric control enclosure. Failure to comply can cause serious injury or death. Customer mustprovide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceedingwith installation, read all instructions, verify that all the parts are included and check thenameplate to be sure the voltage matches available utility power. The Liebert® controller doesnot isolate power from the unit, even in the “Unit Off” mode. Some internal components requireand receive power even during the “Unit Off” mode of the controller. The only way to ensurethat there is NO voltage inside the unit is to install and open a remote disconnect switch. Referto unit electrical schematic. Follow all local codes.

WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipmentdamage, serious injury or death. Installation and service of this equipment should be done onlyby qualified personnel, wearing appropriate, OSHA-approved PPE, who have been specially-trained in the installation of air-conditioning equipment.

• Confirm that all items on Checklist for Completed Installation on page 47, have been done.

• Locate “Liebert® Mini-Mate2 Warranty Inspection Check Sheet” in the unit’s electric panel.(PSWI-8542-409CO).

• Complete “Liebert® Mini-Mate2 Warranty Inspection Check Sheet” during start-up.(PSWI-8542-409CO).

• Forward the completed “Liebert® Mini-Mate2 Warranty Inspection Check Sheet” to your localsales office. This information must be completed and forwarded to validate warranty.

• Contact your local sales representative or technical support if you have any questions orproblems during unit start-up and commissioning. Visit https://www.vertiv.com/en-us/support/or call 1-800-543-2778 for contacts.

8 Initial Start-upChecks and Commissioning Procedure for Warranty Inspection 49

Page 56: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide50

This page intentionally left blank

Page 57: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9 MICROPROCESSOR CONTROLThe Microprocessor Control for the Liebert® Mini-Mate2 features a menu-driven LCD. The menus, controlfeatures, and circuit board are described in this section. Detailed information concerning controls (SystemControl and Performance on page 70) and alarms (Alarm Notification, Acknowledgment and Descriptionson page 73) are provided.

9.1 Controller Operation

Setpoints, DIP switch settings and other selections were made during factory testing of your unit and arebased upon typical operating experience. Other default selections were made according to optionsincluded with your unit.

NOTE: Onlymake adjustments to the factory-default settings if they do not meet your specifications.

When adjusting setpoints and configuration, allowable ranges are displayed by pressing the help key. Ifenabled, a password is required to change setpoints, time delays, and other settings.

The default display normally shows the present room temperature, humidity, active status functions(cooling, heating, dehumidifying, humidifying), fan speed, and active alarms.

The controller includes an LCD display and 8 buttons to navigate the display.

9Microprocessor Control 51

Page 58: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Figure 9.1 Control keys on the wall-mounted display

Item Description

1 I/O (On/Off)

2 Menu, displays program menu

3 Up arrow, increases parameter value in asettings mode

4 Escape, backs-up to apreview menu

5 Enter, saves settings/changes

6 Down arrow, decreases parameter value in asettings mode

7 Alarm Silence/Help, silences active alarm(s). Displays help text when there is no alarm.

8 HI/LO, selects fans speed.

9.1.1 Powering On/Off with Wall-mounted Display

To power-on the system:

Press I/O after power is applied.

To power-off the system:

Press I/O before power is disconnected.

9.1.2 Silencing an Audible Alarm

Active alarms are displayed on the LCD screen and sound an audible beeper.

To silence an audible alarm:

Press the Alarm Silence/Help button.The alarm notification remains visible on the LCD screen.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide52

Page 59: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.2 Main Menu <MENU>

The menu options are shown in Figure 9.2  on page 55. The options differ only slightly depending on thesize of the unit. The differences are noted in the option descriptions.

To select a menu option:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight a selection, then press Enter.

Main Menu Options

SETPOINTS

See Editing Setpoints on page 56.

STATUS

See Viewing Unit Status on page 56.

ACTIVE ALARMS

See Viewing Active Alarms on page 57. and Viewing Alarm History on page 57.

TIME

See Setting Controller Time on page 57.

DATE

See Setting Controller Date on page 57.

SETBACK

See Programming Setback on page 58.

SETUP OPERATION

See Editing Setup Operation on page 58

SETPOINT PASSWORD

See Changing Setpoint and Setup Passwords on page 60

SETUP PASSWORD

See Changing Setpoint and Setup Passwords on page 60.

CALIBRATE SENSORS

See Calibrating Sensors and Setting Sensor-response Delay on page 60.

ALARM ENABLE

See Enabling/Disabling Alarms on page 61.

ALARM TIME DELAY

See Setting Alarm Delays on page 62.

COMMON ALARM ENABLE

9Microprocessor Control 53

Page 60: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

See Activating the Common Alarm Relay on page 63.

CUSTOM ALARMS

See Configuring Custom Alarms on page 63.

CUSTOM TEXT

See Customizing Alarm-message Text on page 65.

DIAGNOSTICS

See Running Diagnostics on page 65.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide54

Page 61: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Figure 9.2 Control Menu Example

9Microprocessor Control 55

Page 62: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.2.1 Editing Setpoints

Setpoints are kept in non-volatile memory. The setpoint options are:

• TEMPERATURE SETPOINT

• TEMPERATURE SENSITIVITY

• HUMIDITY SETPOINT

• HUMIDITY SENSITIVITY

• HIGH TEMPERATURE ALARM

• LOW TEMPERATURE ALARM

• HIGH HUMIDITY ALARM

• LOW HUMIDITY ALARM

Table 9.1  below, lists the default setting and allowed range for each setpoint.

Setpoint Default Range

Temperature Setpoint 72°F 40-90°F (5-32°C)

Temperature Sensitivity 2.0°F 1-9.9°F (0.6-5.6°C)

HumiditySetpoint 50% 20-80% RH

HumiditySensitivity 5% 1-30% RH

High Temperature Alarm 80°F 35-95°F (2-35°C)

Low Temperature Alarm 65°F 35-95°F (2-35°C)

HighHumidityAlarm 60% 15-85% RH

Low HumidityAlarm 40% 15-85% RH

Table 9.1 Default setpoints and allowable ranges

To adjust a setpoint:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight SETPOINTS, then press Enter.

3. Use the Up/Down arrows to highlight a setpoint option, then press Enter.

4. Use the Up/Down arrows to change the value, then press Enter to store the value.

9.2.2 Viewing Unit Status

The Status options displays percentage heating, cooling, dehumidifying and humidifying status of theunit

To view the unit status:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight STATUS, then press Enter.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide56

Page 63: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.2.3 Viewing Active Alarms

Alarms display on the LCD as “No Alarm Present” or “Alarm XX of YY”where “XX” is the number of the alarmand “YY” is the total number of active alarms.

To view active alarms:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight ACTIVE ALARMS, then press Enter.

3. If there is more than one active alarm, use the Up/Down Arrows to scroll through the alarms list.

9.2.4 Viewing Alarm History

A history of the 10 most-recent alarms is kept in non-volatile memory with the date and time ofoccurrence. The first alarm in the history is the most recent, and the 10th is the oldest. If alarm history isfull (10 alarms) and a new alarm occurs, the oldest drops off and the new alarm appears in location 1,moving the others down the list by 1.

NOTE: On new units, the alarm historymay show the results of factory testing.

To view alarm history:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight ACTIVE ALARMS, then press Enter.

3. Use the Up/Down Arrows to scroll through the alarms list.

9.2.5 Setting Controller Time

The controller time clock must be set to allow for the setback control. The clock uses the 24-hour system(that is, 12 midnight is entered as 24:00).

To set the time:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight TIME, then press Enter.

3. Use the Up/Down arrows to change the each character, pressing Enter to store it and move tothe next character.

NOTE: Date and Time features have a battery back-up.

9.2.6 Setting Controller Date

The controller date must be set to allow for the setback control.

To set the date:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight DATE, then press Enter.

3. Use the Up/Down arrows to change the each character, pressing Enter to store it and move tothe next character.

NOTE: Date and Time features have a battery back-up.

9Microprocessor Control 57

Page 64: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.2.7 Programming Setback

The microprocessor can be programmed for night and weekend setback. Two (2) events can beprogrammed for a 5-day work week and two (2) events can be programmed for a 2-day weekend. UseTable 9.2  below, to devise a setback plan.

To program a setback plan:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight SETBACK, then press Enter.

3. Use the Up/Down arrows to change the values, then press Enter to store the value.

Event Weekend Weekday

Time 1

Temperature 1

Sensitivity 1

Humidity 1

HumiditySensitivity 1

Time 2

Temperature 2

Sensitivity 2

Humidity 2

HumiditySensitivity 2

Table 9.2  Night and Weekend setback plan

9.2.8 Editing Setup Operation

System set-up parameters are kept in non-volatile memory.

To edit the set-up:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight SETUP OPERATION, then press Enter.

3. Use the Up/Down arrows to highlight a set-up option, then press Enter.

4. Use the Up/Down arrows to change the value, then press Enter to store the value.

Table 9.3  below, lists the default setting and allowed range for each function.

Function Default Range

Restart Time Delay 0.1 min0 to 9.9min

(0 = manual restart)

C/F Degrees °F °Cor °F

HumidityControl Rel Relative or Absolute

Table 9.3 Set-up functions, default values and allowable ranges

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide58

Page 65: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Set-up options

RESTART TIME DELAY

Selects a delay before restarting the unit after main power is restored to the unit.

• Delay can be set from 0.1 minutes (6 seconds) to 9.9 minutes.

• If several units are operating, set different delays for a sequential start-up.

• Setting the value to zero (0) prevents unit restart when power is restored. In this case, the unitmust be restarted manually by pressing the “On/Off” button on the keypad.

C/F DEGREES

Selects Fahrenheit (F) or Celsius (C) for display readings/setpoints.

HUMIDITY CONTROL METHOD

Selects relative (direct) or absolute (predictive) for humidity control. The LCD displays thepercentage relative humidity for both methods of control and if “absolute” is selected, the adjustedhumidity reading is also displayed.

• If “relative” is selected, the RH control is taken directly from the RH sensor.

• If “absolute” is selected, the RH control automatically adjusts when return-air temperaturedeviates from the desired temperature setpoint (i.e., predictive humidity control). Predictivehumidity control automatically adjusts the humidity level ~2% RH for each degree differencebetween the return air temperature and the temperature setpoint.

For more details about selecting the humidity-control method, see Humidity Control and Over-cooling below.

Humidity Control and Over-cooling

When using the relative (direct) humidity control method, unnecessary dehumidification can result whenover-cooling occurs during a dehumidification cycle. This happens when a higher-than-normal RHreading is caused by over-cooling the room (about 2% RH for each degree of over cooling). Thistemperature drop extends the dehumidification cycle. Later, when dehumidification ends and thetemperature rises to the setpoint, the RH reading falls to a reading lower than actually desired. If thetemperature drop significant enough, the percentage RH could be low enough to activate the humidifier.

Using the absolute (predictive) humidity method may avoid over-dehumidification. When over-coolingcauses an increase in the RH reading, the humidity-control program estimates what the RH will be whenthe dehumidification cycle ends and temperature returns to the setpoint and allows the dehumidificationcycle to end at the proper time. Predictive humidity control can greatly reduce energy consumption byminimizing compressor/reheat operation and eliminating unnecessary operation.

9Microprocessor Control 59

Page 66: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.2.9 Changing Setpoint and Setup Passwords

When you attempt to make changes, the display prompts you for a 3-digit password. The passwordsprovide system security, so that only authorized personnel may make changes. If unauthorized changesoccur, the passwords may be compromised and new ones should be set.

The system includes two passwords with the following factory-default settings:

• Default set-up password = 3 - 2 - 1

• Default setpoint password = 1 - 2 - 3

To change a password:

First enter the default password, then enter the new password.

NOTE: The password function can be disabled by setting DIP switch 8 in the wall box to OFF and thencycling power to the unit.

9.2.10 Calibrating Sensors and Setting Sensor-response Delay

If you suspect that the temperature and/or humidity readings are not accurate, you can calibrate thesensors to match the display using your portable, calibrated test instrument and the CALIBRATESENSORS menu. The temperature sensor can be calibrated +5°F. The humidity sensor can be calibrated±10% RH.

If the sensors are subject to frequent wide temperature and humidity swings, it may be necessary toshorten the cycling by increasing the sensor time delay. If the sensors are located too close to the airdischarge, they will likely experience rapid swings in measurement. Another method in reducingcompressor cycling is to increase the temperature and/or humidity sensitivity.

The calibration and delay options are:

• SET TEMP CAL—calibrates the temperature sensor ±5°F (±2.8°C).

• SET HUM CAL—calibrates the humidity sensor ±10%.

• SET TEMP DELAY—sets the time-delay for sensor response 10 to 90 seconds (default setting= 50 seconds).

• SET HUMID DELAY—sets the time-delay for sensor response 10 to 90 seconds (default setting= 50 seconds).

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide60

Page 67: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

To calibrate a sensor:

1. Make sure the unit is operating and has maintained stable operating conditions for at least 15minutes.

2. Place the test instrument as close as possible to the sensors to obtain an accurate reading forcomparison.

3. At the controller, press the MENU key.

4. Use the Up/Down arrows to highlight CALIBRATE SENSORS, then press Enter.

5. Use the Up/Down arrows to highlight a calibration option, then press Enter.

6. Use the Up/Down arrows to adjust the unit's sensor reading to match the reading from the testdevice, then press Enter to store the value.

IMPORTANT! When calibrating the humidity sensor, the calibration value is always displayed in "% RH,"even when absolute humidity control is selected for the unit. If absolute humidity control is selected,the Normal Status Display displays the adjusted reading, which may not agree with the relative humidityreading that displays in calibration.

To set sensor response-time delay:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight CALIBRATE SENSORS, then press Enter.

3. Use the Up/Down arrows to highlight a set-delay option, then press Enter.

4. Use the Up/Down arrows to adjust the delay, then press Enter to store the value.

9.2.11 Enabling/Disabling Alarms

Many individual alarms may be enabled or disabled. When enabled, an alarm annunciates audibly, visibly,and communicates to a connected site-monitoring system. When disabled, the alarm is completelyignored.

The alarms available for adjustment are:

• Custom Alarm #1

• Custom Alarm #2

• High Temperature

• Low Temperature

• High Humidity

• Low Humidity

• Short Cycle

• Loss of Power

9Microprocessor Control 61

Page 68: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

To set enable or disable an alarm:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight ALARM ENABLE, then press Enter.

3. Use the Up/Down arrows to highlight an alarm option, then press Enter.

4. Use the Up/Down arrows to enable/disable, then press Enter to store the value.

NOTE: When the alarm is disabled it will not report to the wall box or the common alarm relay.

NOTE: Even when the high-water alarm is disabled, the unit automatically shuts off when a high-waterincident occurs. Also, the optional, factory-installed smoke sensor automatically shuts off theevaporator unit when smoke is detected even if the alarm is disabled.

NOTE: The standard, factory-installed high-water alarm and high-head-pressure alarms cannot bedisabled.

9.2.12 Setting Alarm Delays

For each alarm, you can set an amount of time to delay the notification after an alarm condition occurs. Ifthe alarm condition resolves before the delay elapses, there is no alarm notification and the time delayresets automatically. The delay may be set for 0 to 255 seconds, in 1-second intervals. Table 9.4  below,lists each alarm and the default delay setting.

NOTE: Software alarms such as “loss of power” and “short cycle,” should be left at the factory defaultof 0.

Alarm Default Time Delay, seconds

Hum Prob 2

HighHeadPressure 2

Custom Alarm #1 0

Custom Alarm #2 6

High Temperature 30

Low Temperature 30

HighHumidity 30

Low Humidity 30

Short Cycle 0

Loss of Power 0

Table 9.4 Default Alarm Delay Times

To set alarm-delay times:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight ALARM TIME DELAY, then press Enter.

3. Use the Up/Down arrows to highlight an alarm option, then press Enter.

4. Use the Up/Down arrows to select the delay, then press Enter to store the value.

5. Repeat steps 3 and 4 for each alarm delay to set.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide62

Page 69: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

NOTE: The delay for the standard, factory-installed high-head-pressure alarm is not adjustable.

9.2.13 Activating the Common Alarm Relay

Each alarm can be set to activate the common-alarm relay. The common-alarm relay is K5. SeeEnabling/Disabling Alarms on page 61, for the list of available alarms.

When set to YES (enabled), the relay energizes immediately when the alarm annunciates and de-energizes when the alarm is acknowledged. When set to NO (disabled), an alarm has no effect on thecommon-alarm relay.

To set an alarm to trigger the common-alarm relay:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight COMMON ALARM ENABLE, then press Enter.

3. Use the Up/Down arrows to highlight an alarm option, then press Enter.

4. Use the Up/Down arrows to select YES/NO, then press Enter to store the value.

5. Repeat steps 3 and 4 for each common alarm to activate.

9.2.14 Configuring Custom Alarms

You can select custom alarm messages from a list of standard messages or you can create up to twocustom-text messages for selection. The following are the messages available for custom alarms:

• Filter Clog

• Humidifier Problem

• Water Flow Loss

• Loss of Air Flow

• Smoke Detected

• Custom Text #1 (See Customizing Alarm-message Text on page 65. to create a custommessage.)

• Custom Text #2 (See Customizing Alarm-message Text on page 65. to create a custommessage.)

To select the message for a custom alarm:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight CUSTOM ALARMS, then press Enter.

3. Use the Up/Down arrows to highlight the alarm, then press Enter.

4. Use the Up/Down arrows to select the message, then press Enter to store the value.

9.2.15 LCD Display Contrast

You can adjust the level of contrast to help with the viewing angle of the LCD disposal using apotentiometer screw inside the wall box next to the display.

9.2.16 Non-volatile Memory

All critical information is stored in nonvolatile memory. Setpoints and set-up parameters are kept insidethe microcontroller in EEPROM.

9Microprocessor Control 63

Page 70: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.2.17 Equipment Options DIP Switches

Equipment options are selected and enabled using a set of DIP switches mounted on the control boardinside the ceiling-mounted evaporator. The switches are factory-set and should not be changed.

The switch settings on the control board are recognized by the microprocessor control and may bereviewed in the LCD display. Table 9.5  below, shows the setting options. See Editing Setup Operation onpage 58, to review the settings on the display.

Figure 9.3  on page 68 shows the DIP switches on control board in the evaporator unit. Figure 9.4  onpage 69 shows the DIP switches on control board in the wall-mounted controller.

NOTE: To update the DIP switch settings, power must be cycled Off, then On from the unit disconnectswitch.

Switch OFFPosition ON Position

1 Compressor ChillWater

2 StagedReheat SCR Reheat

3 Not Used. Must remain in OFF position.

4 Not Used. Must remain in OFF position.

5 Enable Reheat Disable Reheat

6 Enable Humidifier Disable Humidifier

7 Enable Dehumidifier Disable Dehumidifier

8 Electric Reheat Gas Reheat

Table 9.5 Equipment-option DIP-switch settings (on unit control board)

Switch OFFPosition ON Position

1 Beeper Disable Beeper Enable

2 Not Used. Must remain in OFF position.

3 Not Used. Must remain in OFF position.

4 Not Used. Must remain in OFF position.

5 Not Used. Must remain in OFF position.

6 Not Used. Must remain in OFF position.

7 Disable Setback Enable Setback

8 Enable Password Disable Password

Table 9.6 DIP-switch settings on wall-box board

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide64

Page 71: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.2.18 Customizing Alarm-message Text

IMPORTANT! If using custom text messages, notifymaintenance personnel of the alarm function andrequired action.

You can create custom messages for your custom alarms up to 20 characters in length including blankspaces or any of the following alphanumeric characters and symbols:

A, B, C, D, E, F, G, H, I, J, K, L, M, N, O, P, Q, R, S, T, U, V, W, X, Y, Z

#, %, *, -

0,1, 2, 3, 4, 5, 6, 7, 8, 9

To create custom text message:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight CUSTOM TEXT, then press Enter.

3. Use the Up/Down arrows to highlight the custom-text option, then press Enter.

4. Use the Up/Down arrows to select the character, press Enter to store the value until the entiremessage is stored.

5. To use the custom message, select it from the CUSTOM ALARMS menu. See ConfiguringCustom Alarms on page 63.

9.3 Running Diagnostics

Using the diagnostics tools, you can view system inputs and outputs and test the microcontroller withoutinterrupting normal operation of the unit. Testing system outputs temporarily suspends normal systemcontrol and operation.

9.3.1 Showing Test Inputs

You can view the input state of the devices listed in Table 9.7  on the next page, with the unit on and thefan running.

To show the test inputs:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight DIAGNOSTICS, then press Enter.

3. Use the Up/Down arrows to highlight TEST INPUTS, then press Enter.

4. Use the Up/Down arrows to scroll through the inputs list.

9Microprocessor Control 65

Page 72: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Input Circuit Normal Status

HighWater Alarm Off unless HighWater Alarm is active.

HighHeadPressure Alarm

Off unless HighHeadPressure Alarm is active.

Custom alarm #1 Off unless this special customer selectable alarm is active.

Custom alarm #2 Off unless this special customer selectable alarm is active.

PowerOn unless unit is turned off through the wall boxor anyof the following optional devices: high temperaturesensor, HighWater Alarm or Remote Shutdown.

Table 9.7 Test Inputs

9.3.2 Testing Outputs

NOTICE

Risk of overheating the compressor during the Test Output mode. Testing the compressoroutput for more than a few seconds can cause compressor damage.

Extended unit operation in the Test Outputs mode may damage the unit. Do not operate theunit in the Test Outputs mode any longer than is necessary for troubleshooting.

NOTICE

Risk of extended unit operation in the test outputs mode for troubleshooting. Can causedamage to the unit.

Do not operate unit in the test outputs mode any longer than is necessary for troubleshooting.

The outputs available are:

• Normal fan: normal-speed fan contactor

• Low Speed Fan: low-speed fan contactor (on direct-drive blower units only)

• Humidifier: steam-humidifier contact (if present)

• Cool: compressor contactor or chilled-water valve

• HGBP: hot-gas bypass valve

• Reheat: reheat contactor (if present)

• Common Alarm: common-alarm relay

When testing outputs, the unit is effectively turned off. When stepping from one load to the next, theprevious load is automatically turned off if it was on.

NOTE: Compressor is limited to 15 seconds On to prevent damage.

NOTE: When testing outputs, the fan is turned On with all loads. After 6 minutes without user input,the controller automatically exits test-output mode and returns to normal operation.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide66

Page 73: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

To test the outputs:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight DIAGNOSTICS, then press Enter.

3. Use the Up/Down arrows to highlight TEST OUTPUTS, then press Enter.

4. Use the Up/Down arrows to highlight the output to test, the press Enter to toggle the loadon/off.The output remains for 5 minutes unless toggled Off, when you step to the next load, or whenyou exit the test-outputs function.

9.3.3 Testing the Microcontroller

When selected, the microcontroller performs a self-test that lasts approximately 10 seconds. When thetest is complete, the display shows the ROM checksum, ROM part number, and the firmware revisionnumber.

To test the microcontroller:

1. Press the MENU key.

2. Use the Up/Down arrows to highlight DIAGNOSTICS, then press Enter.

3. Use the Up/Down arrows to highlight TEST MICROCONTROLLER, then press Enter.

Figure 9.3  on the next page, shows the control board in the evaporator unit. Figure 9.4  onpage 69, shows the connections on control board in the wall-mounted controller.

9Microprocessor Control 67

Page 74: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Figure 9.3 Control board inside the evaporator

Item Description

1 DIP switches 1 – 8

Connection Function Connection Function

TB2-4 Hot Gas Bypass TB1-2 Customer Alarm Connection #1

TB2-3 HighHeadAlarm Connection TB1-1 Customer Alarm Connection (Common)

TB2-2 Heat Rejection (24VAC+) TB3-4 Connection to Terminal#4Wall Box

TB2-1 Heat Rejection (24VACGND) TB3-3 Connection to Terminal#3 Wall Box

TB1-9 Condensate PumpAuxAlarm TB3-2 Connection to Terminal#2 Wall Box

TB1-8 Condensate PumpAuxAlarm TB3-1 Connection to Terminal#1Wall Box

Table 9.8  Connections/Functions of control board inside evaporator

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide68

Page 75: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Connection Function Connection Function

TB1-7 CommonAlarm Connection TB4-2 Site Monitoring Connection (-)

TB1-6 CommonAlarm Connection TB4-1 Site Monitoring Connection (+)

TB1-5 Remote Shutdown P16 Remote Sensor Connection

TB1-4 Remote Shutdown

TB1-3 Customer Alarm Connection #2

Table 9.8  Connections/Functions of control board inside evaporator (continued)

Figure 9.4 Control board inside the wall-mounted controller

Item Description

1 TB3-1

2 TB3-2

3 TB3-3

4 TB3-4

5 DIP switches 1 to 8

9Microprocessor Control 69

Page 76: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.4 System Control and Performance

This section describes how the Mini-Mate2 responds to operator input and room conditions.

9.4.1 Temperature Control

The following describes the methods of temperature control and determining cooling requirement for thevarious Mini-Mate2 cooling types.

Control-type Response Proportional Control

The percent requirement for temperature control is determined by the difference between the return-airtemperature and the temperature setpoint. As the return air temperature rises above the temperaturesetpoint, the percent cooling required increases proportionally (from 0 to 100%) over a temperature bandequal to the temperature sensitivity plus 1°F. The heating requirement is determined in a similar manneras the temperature decreases below the setpoint. With this control type, the temperature at which theroom is controlled increases as the room load increases. At full load, the room is controlled to atemperature equal to the setpoint plus the sensitivity.

Cooling Operation for Compressorized (DX) Systems

Cooling is activated when the temperature control calculates a cooling requirement of 100% anddeactivated when the cooling requirement drops below 50%. Hot-gas bypass is activates when a call forcooling occurs unless there is also a call for dehumidification.

Mode Hot-gas bypass

Cooling only ON

Dehumidification only OFF

Coolingwith Dehumidification OFF

Table 9.9 Hot-gas bypass response to cooling and dehumidification modes

Cooling Operation for Chilled-water Systems

The chilled-water control valve is adjusted by a slow-acting motor based on cooling and dehumidificationrequirements.

Cooling Operation for DX Systems with Free-cooling Coil

When free-cooling is available, the freecooling control valve is adjusted by a slow-acting motor based oncooling and dehumidification requirements.

9.4.2 Reheat

The following describes the methods of reheat control and determining reheat requirement for thevarious Mini-Mate2 cooling types.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide70

Page 77: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Ground Current Detector

A Ground Current Detector (GCD) is factory-installed on all units with reheat. The GCD detects reheatleakage current and shuts-down operation of the reheat. A steady-green LED indicates that the reheat isoperating properly. A red LED indicates that the reheat has failed and both the reheat element and GCDmust be replaced.

WARNING! Risk of ground-fault protection failure. Can cause smoke, fire, equipment andbuilding damage, injury, or death. Do not remove or disable the ground current detector.

Figure 9.5 Ground-current detector

Electric or Hot Water Reheat

The reheat stage activates when the temperature control calculates a requirement of 100%. The reheat isdeactivates when the heat requirement is 50% less than the activation point.

SCR Electric Reheat

The SCR proportionally controls the stainless-steel reheat feature to maintain the selected roomtemperature. The rapid cycling of the SCR controller provides precise temperature control, while theconstant element temperature improves heater life. During SCR operation, the compressors operatecontinuously and the heaters are modulated to provide temperature control.

The display status shows when the unit is cooling and heating. The control automatically locks thecompressor cooling in the “ON” position except when the temperature falls below the low-temperature-alarm setpoint. When temperature falls below the low-temperature setpoint, cooling is disabled until theroom temperature reaches this minimum temperature setpoint.

9Microprocessor Control 71

Page 78: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.4.3 Humidity Control

The following describes the methods of humidity control and determininghumidification/dehumidification requirement for the various Mini-Mate2 cooling types.

Humidification Operation

The humidifier activates when the humidity control calculates a 100% humidification requirement, and itis deactivates when the humidification requirement falls below 50%.

Dehumidification/Humidification Percent Required

The humidity control for the Mini-Mate2 is based on a calculated percent requirement fordehumidification or humidification. The percent requirement is calculated from the difference betweenthe sensor reading and the humidity setpoint, divided by the sensitivity. The control method is selectablebetween relative and absolute. "Relative" humidity control is the default.

Dehumidification Operation for Compressorized (DX) Systems

Dehumidification in the standard configuration operates the compressor without the hot-gas bypassactive. The fan operates at low speed unless the cooling requirement reaches 100%. At 100% coolingrequirement, the low-speed fan is disabled (unless manually overridden) until the cooling requirementdecreases to 0%. Dehumidification is also disabled if the heating requirement exceeds 125% and is re-enabled when the heating requirement reaches 50%.

Dehumidification Lockout

Dehumidification is locked out if over cooling occurs. Dehumidification is disabled at 125% (first stage) and200% (all stages) heating requirement. Dehumidification is re-enabled at 66% and 33% heatingrequirement.

9.4.4 Load Control

The control system monitors the compressor and prevents it from turning on within a 3-minute period ofbeing off. If this on-off-on cycle occurs too often (for example: 10 times in a one-hour period), a Short CycleAlarm occurs.

9.4.5 Monitoring

IS-UNITY-DP BMS Monitoring Solution - factory-installed

The IS-UNITY-DP card is a factory-installed option, providing full building-management system (BMS)access via BACnet/Modbus IP and BACnet/Modbus 485. Card provides access and supports SNMPv1/v2c/v3 and Liebert® Nform™. The card is factory-installed in a unit-mounted external enclosure andand is factory-wired for communication to and powered from the Liebert® Mini-Mate2 unit. Field wiring toother systems required to access features.

IS-UNITY-DP BMS Monitoring Solution - field-installed

The IS-UNITY-DP card provides full building-management system (BMS) access via BACnet/Modbus IPand BACnet/Modbus 485. Card provides access and supports SNMP v1/v2c/v3 and Liebert® Nform™.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide72

Page 79: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

• The unit-mount kit for field-installation includes the IS-UNITY-DP card, power/communicationinterface card, enclosure, all required power and communication wires to the Liebert® Mini-Mate2 unit, and full instructions. Field-supplied wiring to other systems required to accessfeatures.

• The wall-mount kit for field installation includes the IS-UNITY-DP card, power/communicationinterface card, painted enclosure, 120-V wall-outlet transformer with 6-ft (2-m) low-voltagepower wire, and full instructions. Field-supplied wiring for communication to Liebert® Mini-Mate2 and to other systems is required to access features.

Liebert iCOM CMS (Mobile Cloud) – factory installed

The iCOM card is a factory-installed option, providing mobile-cloud access, remote access to the unit-level display via the world-wide web, and limited building-management system (BMS) access via ModbusTCP/IP, Modbus RTU, Vertiv SiteScan access, and SNMP v1, v2c. The card is factory-installed in a unit-mounted external enclosure and is factory-wired for power and unit communication. Field wiring to Cloudor BMS is required.

Liebert iCOM CMS (Mobile Cloud) – field-installed kit

The iCOM-CMS™ Mobile Cloud Solution provides mobile cloud access, remote access to the unit-leveldisplay via the world-wide web, and limited building-management system (BMS) access via ModbusTCP/IP, Modbus RTU, Vertiv SiteScan access, and SNMP v1, v2c.

• The unit mount kit for field-installation includes the iCOM-CMS card, enclosure, all requiredpower and communication wires to the Liebert® Mini-Mate2 unit, and full instructions. Field-supplied wiring to other systems required to access features.

• The wall-mount kit for field-installation includes the iCOM-CMS card, painted enclosure, 120-Vwall-outlet transformer with 6-ft (2-m) low-voltage power wire, and full instructions. Field-supplied wiring for communication to the Liebert Mini-Mate2 and to other systems is requiredto access features.

9.5 Alarm Notification, Acknowledgment and Descriptions

The microprocessor control system audibly and visually signals all enabled alarms including customalarms. See Configuring Custom Alarms on page 63, for settings and customization options.

When a new alarm occurs, it is displayed on the screen and the audible alarm is activated. (Ifcommunicating with a Liebert® Monitoring product, the alarm is also transmitted). The message “PRESSALARM SILENCE” prompts you to silence the alarm. After the alarm is silenced, the display return to theNormal Status display. Alarms can also be silenced through communication with a Liebert® Monitoringproduct unit. See Viewing Active Alarms on page 57.

9Microprocessor Control 73

Page 80: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Many alarms reset automatically when the alarm condition is no longer represented and after it has beenacknowledged by being silenced. The exceptions are:

• Software alarms—Loss of Power alarms reset automatically 30 seconds after being silenced oracknowledged. Short Cycle alarms reset automatically 90 minutes after being silenced oracknowledged.

• Alarms that monitor overload or high-pressure switches may require a manual reset dependingupon the model.

The following sections describe and provide troubleshooting suggestions for each type of alarm. SeeTroubleshooting on page 95 for additional details. If you need further assistance, contact your Vertivrepresentative.

NOTE: Alarms are specific at the time the unit is ordered. Additional devices and wiring at the factorymay be required for some alarms.

9.5.1 Custom Alarms

Custom alarm(s) messages are programmed at the LCD display. The message displayed may be includedin a list of provided alarms or it may be customized text (for up to two alarms). See Configuring CustomAlarms on page 63.

IMPORTANT! If using custom text messages, notifymaintenance personnel of the alarm function andrequired action.

9.5.2 High Head-Pressure Alarm

Compressor head pressure is monitored with a pressure-sensor switch. (One SPDT pressure switch isused per refrigeration circuit). If head pressure exceeds 400 psig (2760 kPag), the switch turns off thecompressor contactor and sends an input signal to the control.

Acknowledge the condition by pressing the alarm silence button on the wall box, which will clear if thehigh head pressure is alleviated.

If the head pressure alarm activates 3 times, the alarm locks until the unit is serviced. After the headpressure problem is fixed, reset the control by disconnecting power to the evaporator unit.

To address a high head-pressure alarm:

• On air-cooled systems—check for power shut off to the condensing unit, condensing unit fannot working, defective head pressure control valves, dirty condenser coils or crimped lines. Also,make sure that side switch on the compressor contactors close to energize the condensing-unit control circuit.

• On water/glycol-cooled systems—Check water regulating valves. Verify water/glycol flow(pumps are operating and service valves are open). Is water tower or drycooler operating? Isthe coolant temperature entering the condensing unit at or below design conditions? Is AUXrelay (terminals 70 & 71) operating during cooling to turn on the drycooler?

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide74

Page 81: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.5.3 Humidity-level Alarms

The humidity alarm may be activated under the following conditions:

• High: The room return-air humidity exceeds the pre-set high-humidity alarm setpoint. Is theunit set up for dehumidification? Check DIP switch.

• Low: The room return-air humidity is below the low-humidity alarm setpoint. Is the unit setupfor humidification? Check DIP switch.

• High and Low Humidity (simultaneously): The simultaneous display of two alarms results in lossof the humidity input signal, and dashes (- - -) are displayed for the humidity reading on thedisplay. If this condition occurs, the control system deactivates both humidification anddehumidification. Check for a disconnected cable or failed sensor.

NOTE: Check for proper setpoints. Does the room have a vapor barrier to seal it from outdoorhumidity? Are doors or windows open to outside air?

9.5.4 Temperature-level Alarms

The temperature-level alarm may be activated under the following conditions:

• High: Room return-air temperature increases to the high-temperature alarm setpoint. Checkfor proper setpoint value. Is the room load more than the unit can handle (unit capacity is toosmall)? Make sure cooling components are operating (compressor or valves).

• Low: The room return-air temperature decreases to the low-temperature alarm setpoint. Checkfor proper setpoint value. Make sure all heating components are operating (contactors,reheats, etc.). Are reheats drawing the proper current (refer to amp rating on nameplate)?

• High and Low Simultaneously: The simultaneous display of the two alarms results in loss of thetemperature input signal (or the humidity is out of sensor range-15 to 85% RH), and dashes(---) are displayed for the temperature reading on the display. If this condition occurs, thecontrol system initiates 100% cooling. Check for a disconnected cable or a failed sensor.

NOTE: Check for proper setpoints. Does the room have a vapor barrier to seal it from outdoorhumidity? Are doors or windows open to outside air?

9.5.5 Humidifier-problem Alarm

The Humidifier Problem alarm sounds and displays a message if any of the humidifier conditionsdescribed in Table 9.10  below, occur. The Humidifier's control-board fault-indicator LED assists indetermining the issue.

Fault Condition LED Indicator

Overcurrent detection Lit constant

Fill system fault 1-second flash

Replace tank 1/2-second flash

Table 9.10 Humidifier faults and LED indicator

9.5.6 High-water Alarm

A float switch in the evaporator pan shuts down the evaporator when a high water level occurs. Clear thedrain and reset power to the unit to clear the alarm.

9Microprocessor Control 75

Page 82: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

9.5.7 Loss-of-Power Alarm

The Loss of Power alarm activates (after power is restored to the unit) if the unit has lost power or thedisconnect switch was incorrectly turned off before the unit’s On switch was pressed. A Liebert® remotemonitoring unit (optional) will immediately indicate loss of power.

9.5.8 Short Cycle Alarm

A Short Cycle alarm occurs if the compressor system exceeds 10 cooling-start attempts in a 1-hour period.This may happen if the refrigerant level is low or if the cooling load is small compared to the unit’scapacity. Check for leaks, crimped lines and defective components. If the cooling load is low, increasesensitivity to reduce cycle.

9.5.9 Loss of Water Flow Alarm

NOTE: This alarm may not be available depending on cooling type, unit options and alarmcustomization.

The Loss of Water Flow alarm occurs if no water flow is detected in the chilled-water or condensing unitwater-supply line. An external flow switch is required for this alarm. Determine whether service valves areclosed, pumps are not working, etc.

9.5.10 Change-filter Alarm

NOTE: This alarm may not be available depending on cooling type and alarm customization.

Periodically, the return-air filters in the evaporator must be changed. The Change Filter alarm indicatesthat filter replacement is necessary. A differential air-pressure switch closes when the pressure dropacross the filters becomes excessive. The switch is adjustable using the procedure on the switch label.

9.5.11 High-temperature Alarm

NOTE: This alarm may not be available depending on cooling type and alarm customization.

The high-temperature alarm occurs when the temperature exceeds high temperature sensor setpoint of125°F (52°C). The optional high temperature sensor is a bi-metal operated sensing device with a closedswitch under normal conditions. Connected between pins 1-8 and 1-9, this device shuts down the entireunit.

9.5.12 Smoke Alarm

NOTE: This alarm may not be available depending on cooling type, unit options, and alarmcustomization.

The smoke alarm occurs when the smoke sensor detects smoke. The sensor constantly samples return-airthrough a tube. The sensor's power supply is located in the electric panel. The smoke sensor shuts downthe unit upon detecting smoke, and activates visual and audible alarms. This smoke sensor is notintended to function as or replace any room smoke-detection system that may be required by local ornational codes. Locate the source of the smoke and follow appropriate emergency procedures.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide76

Page 83: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10 MAINTENANCEUse copies of the Preventive Maintenance Checklist on page 89 to record preventive maintenanceinspections.

WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supplydisconnect switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective equipment (PPE) per NFPA 70E before working within theelectric control enclosure. Failure to comply can cause serious injury or death. Customer mustprovide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceedingwith installation, read all instructions, verify that all the parts are included and check thenameplate to be sure the voltage matches available utility power. The Liebert® controller doesnot isolate power from the unit, even in the “Unit Off” mode. Some internal components requireand receive power even during the “Unit Off” mode of the controller. The only way to ensurethat there is NO voltage inside the unit is to install and open a remote disconnect switch. Referto unit electrical schematic. Follow all local codes.

WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all localand remote electric power supply disconnect switches and verify with a voltmeter that power isoff before working within any electric connection enclosures. Service and maintenance workmust be performed only by properly trained and qualified personnel and in accordance withapplicable regulations and manufacturers’ specifications. Opening or removing the covers toany equipment may expose personnel to lethal voltages within the unit even when it isapparently not operating and the input wiring is disconnected from the electrical source.

WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipmentdamage, serious injury or death. Installation and service of this equipment should be done onlyby qualified personnel, wearing appropriate, OSHA-approved PPE, who have been specially-trained in the installation of air-conditioning equipment.

The Liebert® Mini-Mate2 units are single components in the facility heat-removal system. The systemincludes air distribution (duct systems), heat rejection (condensing units or chilled water), and indoorcooling and humidity loads (equipment load, location, outside air infiltration). Proper application andmaintenance of the entire system is critical to the life and reliability of the thermal-management units.

• Good maintenance practices are essential to minimizing operation costs and maximizingproduct life.

• Read and follow monthly and semi-annual maintenance schedules included in this manual.These MINIMUM maintenance intervals may need to be more frequent based on site-specificconditions.

• We recommend the use of trained and authorized service personnel, extended servicecontracts and factory-specified replacement parts. Contact your Vertiv sales representative.

10 Maintenance 77

Page 84: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10.1 System Testing

WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supplydisconnect switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective equipment (PPE) per NFPA 70E before working within theelectric control enclosure. Failure to comply can cause serious injury or death. Customer mustprovide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceedingwith installation, read all instructions, verify that all the parts are included and check thenameplate to be sure the voltage matches available utility power. The Liebert® controller doesnot isolate power from the unit, even in the “Unit Off” mode. Some internal components requireand receive power even during the “Unit Off” mode of the controller. The only way to ensurethat there is NO voltage inside the unit is to install and open a remote disconnect switch. Referto unit electrical schematic. Follow all local codes.

WARNING! Risk of contact with high-speed moving parts. Can cause injury or death. Open alllocal and remote electric power-supply disconnect switches, verify with a voltmeter that poweris off, and verify that all the fan blades have stopped moving before working in the unit.

10.1.1 Environmental-control Function Tests

The performance of all control circuits can be tested by changing the setpoints, which actuates each ofthe main functions.

10.1.2 Cooling Test

To test the cooling function, set the setpoint to a temperature of 10°F (5°C) below room temperature. Acall for cooling should register and prompt the equipment to begin cooling cycle. (Disregard anytemperature alarms). Upon completion of testing, return the setpoint to the desired temperature.

10.1.3 Heating Test

Test Reheat by setting the setpoint to 10°F (5°C) above room temperature. A call for heating shouldregister and prompt the equipment to begin heating cycle. (Disregard any temperature alarms). Uponcompletion of testing, return the setpoint to the desired temperature.

NOTE: Units with hot-gas reheat cannot be tested in this manner. The heating function is onlyactivated during dehumidification and is designed to offset cooling load of the unit.

10.1.4 Humidification Test

To check humidification, set the humidity setpoint at 10% RH above the room humidity reading. After ashort delay, the canister will fill with water and steam will be produced. Upon completion of testing, returnthe humidity setpoint to the desired humidity.

10.1.5 Dehumidification Test

Test dehumidification by setting the humidity setpoint at 10% RH below room relative humidity. Thecompressor should turn on and the fan should switch to low speed. Upon completion of testing, return thehumidity setpoint to the desired humidity.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide78

Page 85: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10.1.6 Smoke Sensor Test

The smoke sensor is located in the unit, and the power supply for the smoke sensor is located in theelectric panel. It constantly samples return air through a tube. No adjustments are required.

10.1.7 Remote Shutdown Test

A connection point is provided for remote shutdown devices supplied by the customer. This terminal stripis on the printed circuit board. (Terminals TB1-4 and TB1-5 are fitted with a jumper when no remoteshutdown device is installed.)

10.2 Filter Maintenance

Experience shows that filters are usually the most neglected item in an environmental control system. Inorder to maintain efficient operation, they should be checked monthly and changed as required.

NOTE: Always turn power off before removing filters.

Filters can be replaced by opening the hinged door on the return air filter box or by opening the return airgrille (grille version only). Replacement filters are commercially available in several efficiencies, contactyour Vertiv representative for appropriate filter sizes.

10.3 Electric Panel Maintenance

Inspect the electric panel on a semi-annual basis for any loose electrical connections.

10.4 Direct-drive Blower Package Maintenance

Inspect the blower package monthly including: motor mounts, fan bearings and impellers.

10.4.1 Fan Impeller and Motor Bearing Maintenance

Inspect fan impellers thoroughly and remove any debris. Check to see if the impellers are tightly mountedon the fan shaft and that they do not rub against the fan housing during rotation. Although the unit'smotor bearings are permanently sealed and self-lubricating, inspect them monthly for signs of wear.

10.4.2 Air Distribution Inspection

Because all unit models are designed for constant volume air delivery, any unusual restrictions within theair circuit must be avoided. Note that high-efficiency filters can reduce air performance and evaporatorcapacity.

10.4.3 Motor Replacement

If the evaporator motor needs to be replaced, first remove the air distribution plate on the bottom of theunit. Removing the mounting screws, allows the entire blower wheel and motor to be lifted out.

10.5 Electric Reheat Maintenance

Reheat element sheets and fins are manufactured with stainless steel. Regular inspections are necessaryto assure proper cleanliness of the reheating element. If inspection reveals corrosion particles on thereheating element or adjoining surfaces (including ducts and plenums), perform appropriate cleaning.Periodic replacement of the reheating element may be necessary to meet specific applicationrequirements.

10 Maintenance 79

Page 86: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10.6 Refrigeration System Maintenance

Inspect the components of the refrigeration system monthly for proper function and signs of wear.Because evidence of malfunction is typically present before component failure, periodic inspections aremajor factor in the prevention of most system failures. Refrigerant lines must be properly supported andnot allowed to vibrate against ceilings, floors, or unit frame. Inspect all refrigerant lines every 6 months forsigns of wear and proper support. Inspect the capillary and equalizer lines from the expansion valve.

10.6.1 Refrigeration Suction Pressure

Suction pressure will vary with load conditions. Suction pressure normally ranges from 58 psi to 75 psi(405 kPa to 517 kPa).

10.6.2 Refrigeration Discharge Pressure

The discharge pressure will vary greatly with load and ambient conditions, see Table 10.1  below. Thehigh-pressure switch shuts down the compressor at its cut-out setting.

System Design Discharge Pressure, psig (kPa)

Air-Cooled 200-300 (1380-2070)

Water-Cooled 65 to 85°F water (18 to 29.4°C) 200-250 (1380-1725)

Glycol-Cooled 250-350 (1725-2415)

High-Pressure Cut-Out 400 (2760)

Table 10.1 Typical Discharge Pressures

10.6.3 Thermostatic Expansion Valve (TXV) Maintenance

The TXV performs one function: It keeps the evaporator supplied with enough refrigerant to satisfy loadconditions. It does not affect compressor operation.

Proper valve operation can be determined by measuring superheat. The correct superheat setting isbetween 10 and 15°F (5.6 and 8.3°C). If too little refrigerant is being fed to the evaporator, the superheatwill be high. If too much refrigerant is being supplied, the superheat will be low.

10.6.4 Air-Cooled Condensing Unit Maintenance

Restricted airflow will reduce operating efficiency and could result in high compressor-head pressure andloss of cooling.

• Clear coil surface of all debris that will inhibit airflow.

• Check for bent or damaged coil fins and correct.

• Do not permit snow to accumulate around or under outdoor unit.

• Periodically consider commercial cleaning of coil surface

• Inspect fans, motors and controls for proper operation.

• Check all piping and capillaries for vibration and proper support.

• Inspect all refrigerant lines for signs of oil leaks.

• Check contactors for pitting. Replace if pitted.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide80

Page 87: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10.6.5 Hot Gas Bypass Operation and Maintenance

When applying hot-gas bypass with split system condensing units, bypassing discharge gas to thecompressor suction line offers more flexibility than conventional hot-gas bypass to the evaporator unit.

The hot-gas bypass valve is installed between the compressor discharge piping and suction piping,bypassing the condenser and evaporator coils. The discharge gas mixes with the suction gas, raising thesuction temperature and pressure and decreasing the mass flow through the evaporator. The highersuction temperatures could cause compressor overheating, therefore a separate, liquid-quenching valveis provided to mix refrigerant from the system liquid line with the discharge gas before mixing with thesuction gas entering the compressor.

During normal operation, when the evaporator is under full load, the hot-gas bypass equalizer pressurewill remain high enough to keep the valve port closed. If the evaporator load decreases, the evaporatortemperature and pressure will drop. When the suction pressure reduces below the hot-gas-bypass valvesetting the hot-gas-bypass valve opens diverting some of the refrigerant flow back to the compressorsuction. The liquid-quenching valve bulb senses this increased superheat and opens, allowing liquidrefrigerant to mix with the discharge gas, de-superheating it.

Proper mixing of the three refrigerant paths ensures stable operation and system performance. Theliquid-quenching valve bulb must be located downstream of all these connections to control superheat atthe compressor inlet. Superheat settings for the liquid-quenching valve are chosen to maintainconsistency with the system expansion valve. During hot-gas bypass operation, higher superheats,50 to 60°F (28 to 33°C), may be observed at the compressor. The liquid-quenching valve is internallyequalized and superheat is not adjustable.

10 Maintenance 81

Page 88: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Figure 10.1 Hot-gas bypass components and flow

Item Description

1 Discharge bypass valve

2 External equalizer

3 Evaporator

4 Distributor

5 TEV

6 Catch-all

7 Solenoid valve

8 Receiver

9 Condenser coil

10 Compressor

11 De-superheating TEV

12 Hot-gas solenoid valve

13 External equalizers

To adjust hot-gas bypass:

1. Install the suction and discharge pressure gauge.

2. Adjust temperature setpoint to call for cooling so that the refrigeration compressor will runcontinuously.

3. Remove the TOP adjusting nut from the valve.

4. Insert an Allen wrench in the brass hole at top of valve in adjusting port, and turn CLOCKWISEif a higher evaporator temperature is required. Adjust no more than 1/4 turn at a time. Let thesystem stabilize for 15 minutes before determining if additional adjustment are necessary.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide82

Page 89: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

5. After obtaining the suction pressure required, reinstall cap tightly making sure there are noleaks.

6. Let the evaporator operate for approximately 10 to 15 minutes to make sure the suctionpressure is within the range desired.

7. There may be a fluctuation of approximately 3 to 6 psig (21 to 41 kPa) on the evaporator due tothe differential on the hot gas bypass.

8. Return temperature setpoint to the desired setting.

10.6.6 Coaxial Condenser Maintenance (Water/Glycol-cooled Condensers Only)

Each water or glycol-cooled module has a coaxial condenser consisting of an exterior steel tube and aninterior copper tube. Clean the screen on the field-installed Y-strainer (if installed). If the water supply isclean, coaxial condensers do not normally require maintenance or replacement. If your system begins tooperate at high head pressure with reduced capacity and all other causes have been eliminated, thecondenser may be obstructed or fouled and should be cleaned or replaced.

10.6.7 Regulating Valve Maintenance (Water/Glycol-cooled Condensers Only)

The water-regulating valve automatically regulates the amount of fluid necessary to remove the heatfrom the refrigeration system, permitting more fluid to flow when load conditions are high and less fluid toflow when load conditions are low. The valve consists of a brass body, balance spring, valve seat, valve discholders, capillary tube to discharge pressure and adjusting screw.

The water regulating valve begins opening at 180 psig (1240 kPag) and is fully opened at 240 psig (1655kPag). The valve is factory-set and should not need adjustment. There is significant difference in the waystandard-pressure and high-pressure valves are adjusted. Consult Vertiv technical support.

10.6.8 Glycol Solution Maintenance

It is difficult to establish a specific schedule of inhibitor maintenance because the rate of inhibitordepletion depends upon local water conditions. Analysis of water samples at the time of installation andthrough a maintenance program should help to establish a pattern of depletion. A visual inspection of thesolution and filter residue is often helpful in judging whether active corrosion is occurring.

The complexity of water/glycol solution condition problems and the variations of required treatmentprograms make it extremely important to obtain the advice of a competent and experienced water-treatment specialist and follow a regularly-scheduled coolant-fluid system-maintenance program. It isimportant to note that improper use of water treatment chemicals can cause problems more serious thanusing none. Proper inhibitor maintenance must be performed in order to prevent corrosion of the glycolsystem. Consult the glycol manufacturer for testing and maintenance of inhibitors. Do not mix productsfrom different manufacturers.

10 Maintenance 83

Page 90: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10.7 Compressor Maintenance

WARNING! Risk of over-pressurization of the refrigeration system. Can cause piping rupture,explosive discharge of high-pressure refrigerant, loss of refrigerant, environmental pollution,equipment damage, injury, or death. This unit contains fluids and gases under high pressure.Use extreme caution when charging the refrigerant system. Do not pressurize the systemhigher than the design pressure marked on the unit's nameplate. Relieve pressure beforecutting into or making connections/disconnections to the piping system. Local building orplumbing codes may require installing a pressure-relief device in the system.

Consult local building and plumbing codes for installation requirements of additional pressure-relief devices when isolation valves are field installed. Do not isolate any refrigerant circuitsfrom over pressurization protection. The PFH condensing units include a factory-installedpressure-relief valve mounted on top of the receiver. The valve is rated for a maximum workingpressure of 475 psig.

CAUTION: Risk of contacting caustic substances. Can cause injury. Avoid touching orcontacting the gas and oils with exposed skin. Severe burns will result. Wear appropriate,OSHA-approved PPE when handling contaminated parts.

Infrequently, a fault in the motor insulation may result in a motor burnout (if system is properly installed,motor burnout rarely occurs). Primarily, this type of failure is due to mechanical or lubrication problems,where the burnout is a secondary consequence.

Early detection can prevent a large percentage of the problems that can cause compressor failures.Periodic maintenance inspections that identify abnormal operation can be a major factor in reducingmaintenance costs. It is easier and more cost-effective to implement the necessary preventative stepsthat ensure proper system operation, rather than ignore a problem until it results in compressor failureand costly replacement. When troubleshooting a compressor problem, check all electrical components forproper operation:

• Check all fuses and circuit breakers.

• Check pressure switch operation.

• If a compressor failure has occurred, determine whether its cause is an electrical or mechanicalproblem.

10.7.1 Mechanical Failure of the Compressor

If you determine that a mechanical failure has occurred, the compressor must be replaced. If a burnoutoccurs, correct the problem and clean the system. It is important to note that successive burnouts of thesame system are usually caused by improper cleaning. If a severe burnout has occurred, the oil will beblack and acidic.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide84

Page 91: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10.7.2 Electrical Failure of the Compressor

In the event of an electrical failure and subsequent burnout of the refrigeration compressor motor, properprocedures must be followed to thoroughly remove any acids that would cause a future failure. There aretwo kits that can be used with a complete compressor burnout - Sporlan System Cleaner and Alco Dri-Kleener. Follow the manufacturer's procedure.

NOTE: Damage to a replacement compressor due to improper system cleaning constitutes abuseunder the terms of the warranty, thereby voiding the warranty.

10.7.3 Replacement Compressors

Replacement compressors are available from your Vertiv supplier and are shipped to the job site in areusable crate (as required by the service contractor). If the compressor is under warranty, you mustreturn it to Vertiv, to receive proper warranty credit. Returned it in the same container in which thereplacement compressor was shipped. Record the possible cause(s) or condition(s) of the damage on theprovided return tag.

10.7.4 Replacing a Failed Compressor

1. Disconnect power

2. Attach suction and discharge gauges to access fittings.

3. Recover refrigerant using standard recovery procedures and equipment. Use a filter-drierwhen charging the system with recovered refrigerant.

NOTE: Release of refrigerant to the atmosphere is harmful to the environment and unlawful.Refrigerant must be recycled or discarded in accordance with federal, state and local regulations.

4. Remove failed compressor.

5. Install replacement compressor and make all connections.

• Use a flow of dry nitrogen through the piping during brazing to prevent formation ofcopper oxide scale inside the piping. Copper oxide forms when copper is heated in thepresence of air. POE oil will dissolve these oxides from inside the copper pipes and depositthem throughout the system, clogging filter driers and affecting other systemcomponents.

• A pure dry nitrogen flow of 1-3 ft3/min (0.5-1.5 l/s) inside the pipe during brazing issufficient to displace the air. Control the flow using a suitable metering device. Pressurizeand leak test the system at approximately 150 psig (1034 kPa) pressure.

6. Follow manufacturer's instructions for clean-out kits.

7. Evacuate the system twice to 500 microns. Break the vacuum each time with clean, drynitrogen.

8. Evacuate the system a third time to 500 microns.

9. Charge the system with refrigerant (R-407C) based on requirements of the evaporator,condensing unit, and lines. Refer to the unit nameplate.

10. Apply power and operate the system. Check for proper operation. Refer to Table 10.1  onpage 80.

10 Maintenance 85

Page 92: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10.8 Steam-generating Humidifier Maintenance

The humidifier drains and refills to maintain a current setpoint and alert the operator when the humidifiercanister needs to be replaced.

WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supplydisconnect switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective equipment (PPE) per NFPA 70E before working within theelectric control enclosure. Failure to comply can cause serious injury or death. Customer mustprovide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceedingwith installation, read all instructions, verify that all the parts are included and check thenameplate to be sure the voltage matches available utility power. The Liebert® controller doesnot isolate power from the unit, even in the “Unit Off” mode. Some internal components requireand receive power even during the “Unit Off” mode of the controller. The only way to ensurethat there is NO voltage inside the unit is to install and open a remote disconnect switch. Referto unit electrical schematic. Follow all local codes.

WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipmentdamage, serious injury or death. Installation and service of this equipment should be done onlyby qualified personnel, wearing appropriate, OSHA-approved PPE, who have been specially-trained in the installation of air-conditioning equipment.

WARNING! Risk of smoke and fire. Can cause activation of fire suppression systems, buildingevacuation, dispatching of fire/rescue equipment and personnel and catastrophic canisterfailure resulting in water leaks, equipment damage, injury or death. Using a humidifier canisterthat has reached the end of it’s service life can be extremely hazardous. If the canister cannotbe replaced immediately at the end of life condition, turn Off the power and water supply to thehumidifier and remove the canister until a replacement canister can be installed. Do not ignorehumidifier problem alarms. Resetting humidifier without addressing cause may result in fire ordamage due to leaking water.

CAUTION: Risk of contact with hot surfaces. Can cause burn injury. The humidifier canisterand steam discharge lines are extremely hot during operation. Allow sufficient time for them tocool to a touch-safe temperature before handling. Use extreme caution and wear appropriate,OSHA-approved PPE when performing maintenance on the humidifier.

After an extended period of operation, in accordance with life-expectancy information, the cylinder iscompletely used as indicated by the amber high-water sensor light illuminated on the cabinet. Then thiscondition is reached, a new replacement cylinder must be installed.

NOTE: The amber high-water sensor light may come on during initial start-up, but this instance doesnot indicate that the cylinder should be replaced.

The steam cylinder is disposable and must be replaced at the end of the cylinder's life. Cylinder life willvary according to water-supply conditions and humidifier use.

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide86

Page 93: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

10.8.1 Operating the Humidifier

1. During start-up, when the humidity control calls for humidification, the fill valve opens andallows water to enter the canister. When the water level reaches the electrodes, current flowsand the water begins to warm. The canister fills until the amperage reaches the setpoint andthe fill valve closes. As the water warms, its conductivity increases and the current flow, in turn,rises. If the current reaches 115% of the normal operating current, the drain valve opens anddrains some of the water out of the canister. This reduces electrode contact with the water andlowers the current flow to the amperage setpoint. Boiling soon commences, and the canisteroperates normally.

2. If the conductivity of the water is low, the canister fills and the water level reaches the canisterfull electrode before the current setpoint is reached. The humidifier stops filling to preventoverflow. Boiling should commence in time. As water is boiled off, the mineral concentration inthe canister increases and current flow also increases. The canister eventually reaches fulloutput and goes to normal operation. No drain is permitted until then.

3. When full output is reached the circuit board starts a time cycle which is factory-set at 60seconds. During this repeating time cycle, the fill valve will open periodically to replenish thewater being boiled off and maintain a “steady state” output at the setpoint. The amperagevariance depends on the conductivity of the water.

4. After many cycles, the mineral concentration in the canister becomes too high. When thisoccurs, the water boils too quickly. As the water quickly boils off and less of the electrode isexposed, the current flow decreases. When the current crosses the low threshold point beforethe end of the time cycle, the drain valve opens, draining the mineral-laden water out andreplacing it with fresh water. This lowers the mineral concentration and returns the canister to“steady state” operation and prolongs canister life. The frequency of drains depends on waterconductivity.

5. Over a period of time, the electrode surface becomes coated with a layer of insulating material,which causes a drop in current flow. As this happens, the water level in the canister will slowlyrise exposing new electrode surface to the water to maintain normal output. Eventually, thesteady-state water level will reach the canister-full electrode and indicate so by activating thecanister full alarm and opening the humidifier contactor. At this point, all of the electrodesurface has been used up and the canister must be replaced.

6. After the entire electrode surface has been coated, the output will slowly begin to fall off. Thisusually occurs in the last several hours of electrode life and should allow enough time toschedule maintenance. During these last hours, the mineral concentration can increase. If themineral concentration is too high, arcing can occur. If the electrodes start to arc, turn off thehumidifier immediately and replace the canister with the identical part.

10.8.2 Replacing the Canister

The humidifier RUN/DRAIN switch is located in humidifier assembly. This switch should be in the RUNposition when the humidifier is in normal operation. It should be in the DRAIN position when a manualdrain for service is required. The electronic control board for the humidifier is located in the same area asthe humidifier assembly. When the unit is energized, power is available to the humidifier circuits.

1. Turn off the humidifier by lowering the humidity setpoint below the ambient humidity level.

Record the original setpoint.

2. Place the RUN/DRAIN switch in the DRAIN position to drain the water from the canister.

3. Return the RUN/DRAIN switch to the RUN position after the canister has drained.

10 Maintenance 87

Page 94: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

4. Turn Off the power at the main unit.

5. Remove the cover from the humidifier cabinet

6. Locate the power wires to the steam canister. They are connected to the canister with 1/4-inquick connects. Make note of the wiring configuration before removing any wires. Refer to theschematic on the unit. Slide the rubber boot back to expose the connections. Remove the two(2) power wires and the canister wire. Do not loosen the screws that secure the electrodes.

7. Loosen the steam outlet hose clamps and slide the steam hose away from the canister fitting.

8. Release the canister clamp along the base of the canister.The canister is now ready to be removed.

9. Remove the canister.

10. Reverse these steps to replace the canister, taking special not of the following:

• When replacing wiring, connect the red wire from terminal #1 on the interface to the redtip terminal on the canister. Reconnect the power wires as they were formerly connected(#2 on the left and #1 on the right).

• Always check the fill and drain solenoids for proper operation after replacing the canister.

10.8.3 Circuit Board Adjustments

Humidifier operation is governed by the humidifier control board. There are three potentiometersmounted on the board. These pots can be used to adjust for extreme water conductivity conditions andcapacity.

POT2 controls the amperage at which the drain will energize. The pot is clearly marked in percentages.This adjustment is factory-set at 85%, which indicates that the unit will drain when the amperage falls offto 85% of the capacity setpoint. Raising the value increases the frequency of drain cycles. Lowering thevalue decreases the frequency of drain cycles. The frequency should be increased for highly conductivewater and decreased for less conductive water. If adjustment is necessary and a change of three to fourpercent in either direction does not permit normal operation of the unit, consult your Vertiv supplier.

POT1 controls the duration of the drain cycle. The pot is clearly marked in seconds. This adjustment isfactory-set at 60 seconds and should not be readjusted without consulting your Vertiv supplier.

POT3 is factory-set at 100%. The maximum capacity of the system is not field adjustable.

WARNING! Risk of electric shock. Can cause injury or death. The DIP switches must be setexactly as indicated in 10.8.3  above. Failure to correctly set the DIP switches may result in anelectrical or water hazard.

The DIP switch sets the capacity of the humidifier. If you replace the humidifier, set the DIP switches onthe circuit board based on the voltage and capacity of your unit shown in Table 10.2  below.

Voltage SW1 SW2 SW3 SW4 Amps

208/230 On Off On Off 4.0

220/240 Off Off On Off 3.7

277 Off On Off Off 3.1

Table 10.2 DIP switch settings for humidifier control board

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide88

Page 95: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

11 PREVENTIVE MAINTENANCE CHECKLISTSource: DPN002953, Rev 2

Inspection Date Job NameIndoor Unit Model # Indoor Unit Serial Number #Condensing Unit Model # Condensing Unit Serial #Room Temperature/Humidity °                     % Ambient Temperature °

Not all units will have all components. To determine your unit’s configuration, compare the Indoor UnitModel # above and the information in the Components and Nomenclature section.

Good maintenance practices are essential to minimizing operation cost and maximizing product life. Readand follow all applicable maintenance checks listed below. At a minimum, these checks should beperformed semi-annually. However, maintenance intervals may need to be more frequent based on site-specific conditions. Review the unit user manual for further information on unit operation. We recommendthe use of trained and authorized service personnel, extended service contracts, and factory-certifiedreplacement parts. Contact your local sales representative for more details.

Check all that apply:

Evaporator/Filters

1. Check/Replace Filters

2. Grille Area Unrestricted

3. Wipe Section Clean

4. Coil Clean

5. Clean Condensate Pan

6. Clean Trap in Condensate Drain

7. Drain Connection/Lines Open, Leak Free and in Good Condition

8. Check/Test Filter Clog Switch Operation (If equipped)

9. Check/Test Condensate Drain Pan Float Switch Operation (If equipped)

Blower Section

1. Blower Wheels Free of Debris

2. Check Motor Mount

3. Motor amp draw

L1 ___________ L2 ___________ L3 ____________

(L1 and L2 on single-phase units)

• Compare to nameplate amps

11 Preventive Maintenance Checklist 89

Page 96: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Reheat (if equipped)

1. Inspect elements and check for corrosion

2. Check/Re-torque wire connections (inside reheat box)

3. Reheat amp draw

L1 ___________ L2 ___________ L3 ___________

Steam Generating Humidifier (if equipped)

1. Check drain valve/drain lines/trap for clogs

2. Check water fill valve and all hoses for leaks

3. Check condition of steam hose

4. Check canister for mineral deposits

5. Check condition of the electrodes

6. Clean strainer

7. Replace humidifier bottle if necessary

8. Check operation of humidifier

9. Humidifier amp draw

L1 ______________ L2 ___________ L3 ______________

Condensate Pump (if equipped)

1. Check for debris in sump

2. Check operation of float(s) (free movement)

3. Check/Clean discharge check valve

4. Check drain connection/lines for leaks

Overflow Drain Pan (Ducted Units - If Equipped)

1. Drain Connection and Lines Open and Free of Debris

2. Drain line empties into a maintenance sink or condensate pump.

3. Water detection device/system installed and monitored - Check operation (If installed)

Electrical Panel

1. Check fuses

2. Check contactors for pitting (Replace if pitted)

3. Check/Re-torque wire connections

Controls

1. Check/Verify control operation (Sequence)

2. Check/Test changeover device(s) (if equipped)

3. Check/Test water-detection device(s) (if equipped)

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide90

Page 97: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Refrigeration Piping

1. Check refrigerant lines (clamps secure/no rubbing/no leaks)

2. Check for moisture (sight glass)

3. Check for restriction temperature drop across filter drier

Compressor Section

1. Check oil level

2. Check for oil leaks

3. Check compressor mounts (springs/bushings)

4. Cap tubes (not rubbing)

5. Check/Re-torque wire connections (inside compressor box)

6. Compressor operation (vibration/noise)

7. Check crank-case heater fuses/operation (if equipped)

8. Check for refrigerant leaks

9. Suction pressure ______________

10. Discharge Pressure ______________

11. Superheat ______________

12. High pressure cut out ______________

13. Compressor amp draw ______________

L1 ______________ L2 ______________ L3 ______________

(L1 and L2 on single-phase units)

Econ-O-Coil (if equipped)

1. Verify proper water/glycol maintenance/treatment is being performed

2. Verify that continuous water/glycol flow is maintained

3. Check for water/glycol leaks

4. Check valve operation

Air-Cooled Condensing Unit (if equipped)

1. Coil clean/free of debris

2. Motor mounts tight

3. Bearings in good condition

4. Refrigerant lines properly supported.

5. Motor amp draw

L1 ______________ L2 ___________ L3 ______________

(L1 and L2 on single-phase units)

11 Preventive Maintenance Checklist 91

Page 98: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Water/Glycol-cooled Condenser (if equipped)

6. Check water-regulating valve operation

7. Verify water flow/Continuous flow is maintained

8. Clean screen on Y strainer (if equipped)

9. Cap tubes (not rubbing)

10. Check for water/glycol leaks

11. Entering water temperature ________°

12. Leaving water temperature ________°

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide92

Page 99: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

MAINTENANCE NOTES

NameSignatureCompany

Make photocopies for your records. Compare readings/information to previous maintenance worksheet.

To locate your local Vertiv representative for Vertiv-engineered parts, check https://www.vertiv.com/en-us/support/ or Call 1-800-543-2778.

11 Preventive Maintenance Checklist 93

Page 100: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide94

This page intentionally left blank

Page 101: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

12 TROUBLESHOOTING

WARNING! Risk of electric shock. Can cause injury or death. Open all local and remote electricalpower disconnect switches and verify with a voltmeter that power is off before working withinelectrical enclosures. Hazardous voltage will be present at evaporator, condensing unit, reheatand humidifier even with the unit turned Off at the control panel. With power and controlsenergized, the unit could begin operating automatically without warning.

Table 12.1  below, describes the possible causes, and actions to take when troubleshooting an issue.

Symptom Possible Causes Check or Remedy

Unit will not start

No power to unit Check voltage at input terminal block.

Control voltage circuitbreaker (attransformer) open

Locate short and reset circuit breaker.

Float switch relayhasclosed due to highwater in thecondensate pan.

Has rubber band been removed from float switch?Check drain and line. Accessfrom bottom through discharge air grille. Power must be cycled at the disconnectto reset.

Jumper not in placeCheck terminalTB1-4 andTB1-5 for jumper or N/C contact. Check Pins 1-8 and 1-9for jumper or N/C optional high-temperature sensor contact. Check Pins 5-4 and5-5 for jumper or N/C smoke detector contact.

No cooling

“Cooling” is notdisplayed at thecontrol panel.

Adjust TEMP control setpoint and sensitivity to require cooling.

Short cycle preventioncontrol.

Control software delays compressor 3 minutes cooling, from stop to start

Compressor contactornotpulling in.

Check for 24VAC±2 VACat terminals P4-8 andP4-4. If voltage is detected,check contactor. If there is no voltage at P4-8 andP4-4, check at terminals P2-3andP2-8. If voltage, check freezestat.

Compressor high headpressure.

See below for cause.

Plugged filter/drier. Replace filter/drier.

Low refrigerantcharge.

Check pressure gauges. See the tables in Refrigerant Charge Requirements onpage 37 for recommended pressures. At low ambient temperatures, properrefrigerant charge is very important on units with Lee-Temp receivers.

Table 12.1 Troubleshooting

12 Troubleshooting 95

Page 102: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Symptom Possible Causes Check or Remedy

Compressor highhead pressure alarm

Insufficient air flowacross condenser coil

Remove debris from coil and air inlets.

Water/Glycol-Cooledonly: No fluid flowingthrough condenser.

Check fluid supply to regulating valve. Clean Y-strainer filter if installed. Adjust valveif necessary.

Un-shielded controlwires used betweensplit-system units.

Check for shielded controlwires used and for shieldedwire connection to earth(ground) at the Liebert® equipment. Route low-voltage wires separate from high-voltage lines and away from loads such as light ballasts.

Self-Contained, Air-Cooled only:Condensing-unit fannot operating

Check fan operation.

Reheat will notoperate

DIP switch not set toenable reheat option

See DIP switch settings 9.2.17  on page 64.

“HEAT” not displayedat the control panel

Increase temperature setpoint to require heating.

Reheat safetyopen,defective reheatcontact or defectiveboard

Check voltage at P2-1 andP1-9 on interface board for 24VAC±2 VAC. If voltage,check reheat contactor and reheat safety. If no voltage, check wiring and/orreplace board.

Element is burned out Turn off power. Check element continuitywith Ohm meter.

GCD has tripped Replace GCD and heating element.

Display freezes andcontrol pads do notrespond

Static dischargeDuring period of low humidity, static electricity can cause the control program tofreeze or display incorrect information. Although this is unlikely, the control can bereset bycycling power from the disconnect switch.

Table 12.1 Troubleshooting (continued)

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide96

Page 103: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Symptom Possible Causes Check or Remedy

Humidifier does notoperate

DIP switch not set toenable humidifieroption

See DIP switch settings 9.2.17  on page 64.

“HUMIDIFY” notdisplayed at controlpanel

Increase humidity control setpoint and sensitivity to require humidification.

Defective boardCheck voltage at P3-1 andP1-9 on interface board for 24VAC±2 VAC. If novoltage, check wiring and/or replace board. Check wiring from control panel toboard.

Failed humidity sensorHumiditydisplaywill indicate dashes. Check wiring from temperature/ humidityboard to the control board and from the wall box to the control board. Replace wallboxor temperature/humidity circuit board (if remote).

No water flowMake sure switch is in Run position. Check humidifier water supply (including filterscreen) and check nylon overflow line if canister is full.

Canister fill rate is notkeeping upwith thesteam output

Check fill valve screen opening and capillary tube for obstructions. Check watersupplypressure (minimum 10 psig [69 kPa]).

Fan will not operate atlow speedwhenselected from controlpanel.

Openwiring or failedboard

Verify “LOWFAN” is displayed at the control panel. Check for 24VAC±2 VACatterminals P3-4 andP1-9. If no voltage, check wiring and/or replace interface board.Check fan relays.

Fan will not operate atlow speed duringdehumidification

Temperaturerequirement is toohigh.

Verifywith display. Cooling requirement overrides dehumidification.

Cooling cycle tooshort

Sensor response delaytoo short

Increase sensor response delay. See Calibrating Sensors and Setting Sensor-response Delayon page 60.

Condensate pumpdoes not operate

Open or short circuit inwiring

Find open or short circuit and repair power to pump.

Continuous CoolingFailed temperaturesensor

Temperature displaywill indicate dashes. Check wiring fromtemperature/humidityboard (remote sensors) to the control board or fromcontrol board to wall box. Replace temperature/humidity circuit board (remotesensors) or wall box.

Continuous CoolingDehumidificationHumidification

Shortedwiring or failedcontrol board

Check wiring and/or replace control board.

Table 12.1 Troubleshooting (continued)

12 Troubleshooting 97

Page 104: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide98

This page intentionally left blank

Page 105: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

APPENDICES

Appendix A: Technical Support and Contacts

A.1 Technical Support/Service in the United States

Vertiv Group Corporation

24x7 dispatch of technicians for all products.

1-800-543-2378

Liebert Thermal Management Products

1-800-543-2778

Liebert Channel Products

1-800-222-5877

Liebert AC and DC Power Products

1-800-543-2378

A.2 Locations

United States

Vertiv Headquarters

1050 Dearborn Drive

Columbus, OH, 43085, USA

Europe

Via Leonardo Da Vinci 8 Zona Industriale Tognana

35028 Piove Di Sacco (PD) Italy

Asia

7/F, Dah Sing Financial Centre

3108 Gloucester Road, Wanchai

Hong Kong

99

Page 106: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide100

This page intentionally left blank

Page 107: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Appendix B: Submittal Drawings

The submittal drawings are in the order of document part number (DPN). Table 14.1  below, groups thedrawings by topic/application.

Document Number Title

PlanningDimensions - Self-containedUnits and Split-system Evaporators/Chilled-water Units

DPN000172 Cabinet Dimensions

DPN000173 Filter-boxandGrille Option Dimensions

DPN000177 Condenser-fan Module Dimensions

PipingGeneralArrangement

DPN004408 Piping Schematic, Split system, Air-cooled

DPN000168 Piping Schematic, Self-contained , Air-cooled

DPN000166 Piping Schematic, Self-contained, Water/Glycol-cooled

DPN000169 Piping Schematic, Water/Glycol-cooledwith freecooling and hot-water reheat options

DPN000167 Piping Schematic, Self-contained, Chilled-water

Piping Connections - Evaporator andChilled-water Units

DPN004302 PipingConnections

Condensate-pumpConnection

DPN000174 Field-installed pump connection

ElectricalConnections - Evaporator andChilled-water Units

DPN000175 ElectricalConnections, Air-cooled units

DPN000176 ElectricalConnections, Water/Glycol-cooled andChilled-water units

DPN004850 Arrangement andDimensions, Unit-mounted IS-UNITY-DP for BMSCommunication

DPN004911 Arrangement andDimensions, Wall-mounted IS-UNITY-DP for BMSCommunication

DPN004854 ElectricalConnections, IS-UNITY-DP for BMSCommunication

DPN004947 Arrangement andDimensions, Wall-mounted iCOM™CMSenclosure

DPN003523 Arrangement andDimensions, Unit-mounted iCOM™CMSenclosure

DPN003556 ElectricalConnections, iCOM™CMS for Mobile CloudCommunication

ElectricalConnections - Self-containedCondensingUnits

DPN000177 ElectricalConnections, Air-cooledCondenser-fan Module

Table 14.1 Submittal-drawings Contents

101

Page 108: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide102

This page intentionally left blank

Page 109: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 4REV DATE : 2/17

DPN000166Page :1 /1

1 & 1.5 TON SELF CONTAINED WATER/GLYCOL COOLED SYSTEM

For

m N

o.: D

PN

0010

40_R

EV

4

GENERAL ARRANGEMENT DIAGRAM

LIEBERT MINI-MATE2

EvaporatorCoil

Expansion Valve

Filter DrierSensingBulb

Compressor

High PressureSwitch

ExternalEqualizer

Tube in TubeCondenser

Water/GlycolReturn Line

Water/GlycolSupply Line

Fluid ReturnFrom Unit

Fluid SupplyTo Unit

Shut - OffValve

Hose Bibs

2 - Way WaterRegulating Valve

Tube in TubeCondenser

Fluid ReturnFrom Unit

Fluid SupplyTo Unit 3 - Way Water

Regulating Valve(Optional)

FIELD PIPING

FACTORY PIPING

Hot Gas BypassSolenoid Valve

Hot Gas BypassControl Valve

SHEET 1 OF 1

Notes:

1. Components are not supplied by Liebert but are required for proper circuit operation and maintenance.

1

1

Page 110: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 4REV DATE : 2/17

DPN000167Page :1 /1

1.5 TON SELF CONTAINED CHILLED WATER SYSTEM

For

m N

o.: D

PN

0010

40_R

EV

4

GENERAL ARRANGEMENT DIAGRAM

LIEBERT MINI-MATE2

Bleed Valve

Chilled WaterCoil

Chilled WaterControl Valve

ChilledWaterSupply

ChilledWaterReturn

Shut - Off Valves

Hose Bibs

FIELDPIPING

FACTORYPIPING

Notes:

1. Components are not supplied by Liebert but are required for proper operation and maintenance.

1

1

Page 111: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 2REV DATE : 2/17

DPN000168Page :1 /1

1 & 1.5 TON SELF CONTAINED AIR COOLED SYSTEM

For

m N

o.: D

PN

0010

40_R

EV

4

GENERAL ARRANGEMENT DIAGRAM

LIEBERT MINI-MATE2

Condenser Coil

High PressureSwitch

Compressor

FilterDrier

Expansion Valve

SensingBulb

ExternalEqualizer

EvaporatorCoil

Hot Gas BypassSolenoid Valve

Hot Gas BypassControl Valve

Page 112: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 6REV DATE : 10/17

DPN000169Page :1 /1

1 & 1.5 TON FREE COOLING OR HOT WATER REHEAT COIL OPTIONS

For

m N

o.: D

PN

0010

40_R

EV

4

GENERAL ARRANGEMENT DIAGRAM

LIEBERT MINI-MATE2

Solenoid ValveProvided WithOptional HotGas ReheatHigh Pressure

Switch

Check Valve

Compressor

Filter Drier

Condenser Coil(Coaxial condensernot shown)

Hot Gas Reheat Coil(Optional)

Evaporator Coil

Expansion Valve

SensingBulb

External Equalizer

Bleed Valve

Free CoolingCoil

Free CoolingControl Valve

TemperatureStat

FluidReturn

FluidSupply

Shut - OffValve

Hose Bibs

Bleed Valve

Hot Water ReheatCoil

Hot Water ReheatControl Valve

Y-Strainer

WaterSupply

WaterReturn

Shut -OffValve

Hose Bibs

OPTIONAL HOT GASREHEAT

OPTIONAL FREE COOLING COIL (3-WAY VALVE) OPTIONAL HOT WATER REHEAT (2-WAY VALVE)

OPTIONAL PIPING

FACTORY PIPING

FIELD PIPING

Hot Gas BypassSolenoid Valve

Hot Gas BypassControl Valve

Notes:1. Hot Gas Reheat is available only on self contained "DX" modules. Air Cooled piping shown, Also available on water and glycol models.2. Hot Water Reheat Coil only avaialable on Chilled Water units.3. Each module is available with only one (1) of the above listed options.

4. Components are not supplied by Liebert but are required for proper circuit operation and maintenance.

4

4

4

4

Page 113: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 8REV DATE : 4/18

DPN000172Page :1 /1

1 & 1.5 TON AIR, WATER/GLYCOL & CHILLED WATER MODELS

For

m N

o.: D

PN

0010

40_R

EV

4

CABINET DIMENSIONAL DATA

LIEBERT MINI-MATE2

Rear of Unit

Customer supplied threaded rodsfor module support from ceiling(typ. 4)

Shaded area indicates a recommendedclearance of 30" (762mm) be provided forcomponent access and removal.

Condenser blower box location forSelf-Contained Air Cooled Unitsonly.

3/8" (10mm) holes for modulerigging. (typ. 2 each end)

Unit hanging supports.

RemovableAccessPanels

Threaded Rod Centers

Threaded RodCentersRight End

30"762mm 54"

1372mm

20"508mm

3 3/8"86mm

14 1/2"368mm

3 1/4"83mm 18"

457mm

3 1/16"78mm

7 1/2"190mm

14"355mm

15"381mm

1 7/8"47mm 4 7/8"

123mm

16 3/4"425mm

11"279mm

Condenser Inlet duct connectionfor Self-Contained Air CooledUnit only. 1" (25.4mm) flange.

Evaporator Supply(ducted only)

Evaporator Return(ducted only)

Threaded Rod Centers Left End

Access Panel for Blower/Motor located onthe bottom of the unit. Allow a minimumclearance of 9" (229mm) below unit foraccess to Blower/Motor.

60 HZ 50 HZ

MM*12E 220 (100)

MM*12A 265 (120)

MM*14W 260 (118)

MM*18E 225 (102)

MM*18A 300 (136)

MM*20W 295 (134)

MM*23C MM*22C 220 (100)

NA

UNIT NET WT

lbs. (kg)

MODEL #

Front of Unit

56"1422mm

27"686mm

58"1473mm

OVERALL

22"559mm

30"762mm

OVERALL

1"25mm

Page 114: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 3REV DATE : 2/17

DPN000173Page :1 /1

1 & 1.5 TON AIR, WATER/GLYCOL & CHILLED WATER MODELS

For

m N

o.: D

PN

0010

40_R

EV

4

UNIT OPTIONS DIMENSIONAL DATA

LIEBERT MINI-MATE2

7 5/8"194mm

20 1/4"514mm

8"203mm

1 1/4"32mm

14"356mm

18"457mm

1"25mm

2 1/4"58mm

16"406mm

Shaded area indicates a recommendedclearance of 30" (762mm) be providedfor component access and removal.

3/4" (19mm) Flange

(OPTIONAL) FILTER BOX

DIMENSIONAL DATA

Cabinet dimensionssame as DPN000172.

Front of Unit

One WayAir Returnto Unit Three Way

Unit Discharge

Removable for filteraccess and removal.

(OPTIONAL) GRILLE AIR DISTRIBUTION

2"51mm

5"127mm

1"25mm

Page 115: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 2REV DATE : 2/17

DPN000174Page :1 /1

1 & 1.5 TON MODELS

For

m N

o.: D

PN

0010

40_R

EV

4

OPTIONAL FIELD INSTALLED

LIEBERT MINI-MATE2

CONDENSATE PUMP CONNECTION

Power Supply fromElectric Service PowerBlock in Unit

(Optional)Humidifier SupllyConnection

7/8" (22mm) Dia.Electrical Entrance forCondensate Pump Connection

3/4" (19mm) N.P.T. FemaleCondensate Drain ConnectionDrain is trapped inside unitField Supplied

Rigid Tubing(support as required)

3/4" (19mm) FPTCustomer Connection

Flexible Rubber Tubing

3/4" (19mm) Hose BarbSupplied on Pump Tank

3/8" (9.5mm) Compression FittingDrain Connection

Notes:

1. 3/4" (19mm) Flexible Rubber Tubing Assembly (supplied with pump kit) must be installed on pump end of rigid piping (support as required).2. The Auxiliary Float Switch included with pump must be field interlocked with unit control to enable unit shutdown feature. Wire to evaporator terminal per unit schematic.3. Refer to DPN003401 for installation instructions.

1

Top View

Front of Unit

Back of Unit

12 1/2"318mm

6 1/2"165mm

11 1/2"292mm

Drain Line(field supplied)

CondensatePump

Condensate PumpSupport Bracket

Page 116: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 6REV DATE : 3/19

DPN000175Page :1 /1

1 & 1.5 TON AIR, WATER/GLYCOL & CHILLED WATER MODELS

For

m N

o.: D

PN

0010

40_R

EV

4

ELECTRICAL FIELD CONNECTIONS

LIEBERT MINI-MATE2

Right End

Heat Rejection Connection. Fieldsupplied 24V NEC class 2 wiring. Seenote 2. For remote air cooled units fromterminals TB2-1, 2, 3 & 4 in the Fan/Coilmodule to wires 1, 2, 3 & 4 in thecondensing module:1. 24V GND2. 24V Supply3. High Pressure Alarm (OPT)4. Hot Gas Bypass Connection

Remote Unit Shutdown. Replace existingjumper between terminals TB1-4 & TB1-5with normally closed switch having aminimum 75VA rating, use field supplied24V class 1 wire.

Common Alarm Connection. Fieldsupplied 24V class 2 wiring tocommon alarm terminal TB1-6 &TB1-7.

(Optional) Condensate Pump AuxiliaryFloat Switch Connection to terminalTB1-8 & TB1-9.

Entrance for customer lowvolt connection.

Site Monitoring Connection. TerminalsTB4-1 (+) & TB4-2 (-) are for connection of a2 wire, twisted pair, communication cable(available from Liebert or others) to optionalIS-UNITY-DP, iCOM CMS, OR SiteScan.

Remote Control Panel Connection toTB3-1,2,3,4 connected with field suppliedThermostat wire (22ga, shielded/jacketed:available from Liebert or others). Unit ControlBoard terminals marked GND, +5V, T-, T+ mustbe connected to corresponding terminals onRemote Control Wall Box.

Earth Ground Connection.Connection terminal for fieldsupplied earth grounding wire.

High Volt Power Connections.Electric service connectionterminals.

Entrance for Customer HighVolt Connection.

Factory installed disconnectswitch (optional).

Interconnecting condenser blower harness

Fan Speed Control captubepassage holes

Entrance for CustomerLow Voltage Connections

Field supplied 24V (NEC class2 wiring)to condensing module (if applicable).

Field supplied, field wiredthermostat wire to remotewall box.

Customer Remote Alarm Connection.Field supplied 24V class 2 wiring toterminals TB1-1, TB1-2 & TB1-3.

Remote Humidifier ContactField Supplied 24V class 2wiring to terminals 11 & 12,located in field wirecompartment.

Drycooler/Circulating pumpcontrol circuit TB70-71. Optionalw/Econ-O-Cycle models. Use fieldsupplied 24V class 2 wire.

NOTES:1. Refer to specification sheet for full load amp and wire size amp ratings.2. Control voltage wiring must be a minimum of 16 GA (1.3mm) for up to 75'(23m) or not to exceed 1 volt drop in control line.

Optional IS-UNITY-DP OR iCOM CMS connectionto terminals 20 and 21 on lower right outside ofelectric box. Field supplied 24V Class 2 wiring.

Page 117: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 3REV DATE : 2/17

DPN000176Page :1 /1

1 & 1.5 TON AIR, WATER/GLYCOL & CHILLED WATER MODELS

For

m N

o.: D

PN

0010

40_R

EV

4

ELECTRICAL FIELD CONNECTIONS

LIEBERT MINI-MATE2

7/8" (22mm) Dia. Entrancefor low voltage connectionto Condensing Unit(if applicable).

7/8" (22mm) Dia. Electricalentrance for CondensatePump connection.

Condenser Blower Harness Connection

Entrance for Capillary Tubefrom Fan Speed Controller(only on self-contained aircooled units).

Entrance for Customer Low VoltConnection.

Entrance for Customer HighVolt Connections.

Electric service notby Liebert.

Field supplied unit disconnectswitch when factory unitdisconnect switch is notsupplied.

FRONT OF UNIT

BACK OF UNIT

NOTE: Refer to specification sheet for full load amps. and wire size amp. ratings.

Page 118: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 3REV DATE : 2/17

DPN000177Page :1 /1

1 & 1.5 TON FSC CONDENSER FAN MODULE

For

m N

o.: D

PN

0010

40_R

EV

4

CABINET DIMENSIONAL DATA &

LIEBERT MINI-MATE2

ELECTRICAL FIELD CONNECTIONS

Front of Unit

5 1/4"133mm

12"305mm

18 5/8"473mm

4 11/16"119mm

12"305mm

17 1/4"438mm

20"508mm

High & Low VoltageWire Harness seeunit schematic forwiring.

Blower Motor & Controlleraccess cover.

Blower & Motor Assembly

Fan Speed Controller

Capillary Tube from fan speedcontroller. Screw onto accessvalve in discharge line (insideceiling unit).

Shaded area indicates a recommended clearanceof 24" (610mm) be provided for componentaccess and removal.

L2

L1

2CC T2

T11CC

CC-COIL

CC-COIL

COMPRESSORCONTACTOR

Line Side(to power block)

Load Side(to compressor)

High VoltageWire

Low VoltageWire

Low VoltageWire

High VoltageWire

MM2CF 63 (29)

ModelUnit Net Weight

lbs. (kg)

Page 119: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 6REV DATE : 2/19

DPN003523Page :1 /1

UNIT MOUNTED iCOM™ CMS ON 1 & 1.5

FOR MOBILE CLOUD CONNECTIVITY

For

m N

o.: D

PN

0010

40_R

EV

4

GENERAL ARRANGEMENT & DIMENSIONAL DATA

LIEBERT MINI-MATE2

Rear of Unit

Front of Unit

Shaded area indicatesa recommended clearanceof 30" (762 mm) forcomponent accessand removal

Shaded area indicatesa recommended clearanceof 30" (762 mm) forcomponent accessand removal

Note:

1. Connection to optional SiteLink System or Modbus RTU.

2. Communication to Liebert MiniMate2 Unit.

3. Refer to DPN003556 for field communication connections.

Front View

12"305mm

Top ViewLiebert iCOM™ CMS Enclosure

14"355mm

14 1/4"362mmLiebert iCOM™ CMS

Control Board

24VAC Power ConnectionP5

ETHERNET 1(Mobile App)

ETHERNET 2(Modbus TCP/IP orSNMP v1, v2c)

USB (Software Upgrades)

ICOM™ CMS

485-1P59

485-2P58

3"76mm

1

4"102mm

Bottom View

2

Power & Communication Knockout

Page 120: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 5REV DATE : 2/19

DPN003556Page :1 /1

LIEBERT MINI-MATE2 & LIEBERT DATAMATE

For

m N

o.: D

PN

0010

40_R

EV

4

MOBILE CLOUD COMMUNICATION CONNECTION OPTIONS

iCOM™ CMS

CMS COMMS CONNECTION TERMINAL PIN PIN

iCOM CMS 485-1 TB4 1 2

iCOM CMS 485-1 77, 78 N/A N/A

iCOM CMS 485-1 TB5 77 78

Liebert Mini-Mate2 1-5 Ton

Liebert Mini-Mate2 8 Ton

Liebert DataMate

Mobile Cloud with

SiteLink option shown

(1 Cooling Unit per card)

1. Mobile Cloud access provided via IP Connectivity2. SiteLink (Web Adapter Card not required) - 485-2 alternately can be used for Modbus RTU3. Modbus TCP/IP & SNMP v1, v2c available.4. Communication wiring is field supplied - IP use CAT5e cable or greater - 485 - use EIA 485 rated, shielded, twisted pair cable, 22-18AWG - Must be rated to meet local codes and conditions.

CoolingUnit 1

Room 1

SiteLink

iCOM CMSCOMMUNICATIONS

BOARD485-1P59

485-2P58

PowerP5 CAN USB ETHERNET 2 ETHERNET 1

- + - +

Unit to iCOM CMS Connection Points

Cloud AccessSee Note 3

Use AC4 for Team Work & Lead-Lag between Liebert Mini-Mate2 & Liebert DataMate units.

Page 121: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 0REV DATE : 8/17

DPN004302Page :1 /2

1 & 1.5 TON AIR, WATER/GLYCOL & CHILLED WATER MODELS

For

m N

o.: D

PN

0010

40_R

EV

4

PRIMARY CONNECTION LOCATIONS

LIEBERT MINI-MATE2

FRONT OF UNIT

Liquid Refrigerant Line3/8" O.D. Cu

Suction Refrigerant Line5/8" OD Cu

Chilled Water Return Line (OUT)5/8" OD Cu.

Chilled Water Supply Line (IN)5/8" (15.9mm) OD CU.

Condenser Air Outletfor Self-ContainedAir-Cooled Units.

See Detail A

1 1/16"27mm

1 1/4"32mm

2"51mm

3 3/16"81mm

2 5/16"59mm

3 5/16"84mm

2 3/8"60mm

3 3/4"95mm

4 1/8"105mm

1 3/8"35mm 4 7/8"

124mm

DETAIL "A"

10"254mm

Page 122: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 0REV DATE : 8/17

DPN004302Page :2 /2

1 & 1.5 TON AIR, WATER/GLYCOL & CHILLED WATER MODELS

For

m N

o.: D

PN

0010

40_R

EV

4

PRIMARY CONNECTION LOCATIONS

LIEBERT MINI-MATE2

2"51mm

12 1/16"306mm

1 3/8"35mm

3 3/8"86mm

7 7/8"200mm

DETAIL "B"

3 1/8"79mm

1 3/8"35mm

7 5/8"194mm

12 1/2"318mm

3 3/8"86mm

DETAIL "C"

2 3/4"70mm

7 3/16"183mm

1 1/8"29mm

2 1/8"54mm

3 1/2"89mm

DETAIL "D"

BACK OF UNIT

Optional 1/4" (6mm) O.D. CompressionFitting. Use copper lines for humidifiersupply line.NOTE: ROUTE HUMIDIFIER SUPPLY LINEAND ELECTRICAL SUPPLY TO CLEAROPTIONAL FILTER BOX ACCESS DOOR.

Evaporator Air Inlet

3/4" (19mm) NPT FemaleCondensate Drain Connection.Drain is trapped internally and mustnot be trapped outside of the module.

Evaporator Air Outlet

Condenser Air Inletfor Self-ContainedAir-Cooled Units.

1/2" (12.7mm) OD CUWater/Glycol Outlet Connection.

1/2" (12.7mm) OD CUWater/Glycol Inlet Connection.

Hot Water Reheator Free Cooling Inlet

Hot Water Reheator Free Cooling Outlet

See Detail B

See Detail C

See Detail D

9 7/8"251mm

Page 123: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 0REV DATE : 10/17

DPN004408Page :1 /1

1 & 1.5 TON SPLIT SYSTEMS W/ AIR COOLED CONDENSING UNIT

For

m N

o.: D

PN

0010

40_R

EV

4

GENERAL ARRANGEMENT DIAGRAM

LIEBERT MINI-MATE2

Condenser Coil

High PressureSwitchCompressor

Hot Gas BypassSolenoid Valve

3 Way HeadPressureControl Valve

Hot Gas BypassControl Valve

Liquid LineSolenoid Valve

Check Valve

3/8" SAE 45° Male Flare (MCD)or Atmospheric (PFH)Pressure Relief Valve

Sight Glass

Lee - TempReceiver

Liquid InjectionValve Bulb

LiquidInjection

FilterDrier

Sensing Bulb

External Equalizer

Expansion Valve

Evaporator Coil

Pressure BalancingValve

ReceiverHeaterPressureLimitingSwitch

Schrader Port w/Valve Core

SuctionLine

LiquidLine

Schrader Port w/Valve Core

Schrader Port w/Valve Core

FIELD PIPING

FACTORY PIPING

Page 124: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 1REV DATE : 2/19

DPN004850Page :1 /1

UNIT MOUNTED IS-UNITY-DP ON 1 & 1.5 TON FOR BMS CONNECTIVITY

For

m N

o.: D

PN

0010

40_R

EV

4

GENERAL ARRANGEMENT & DIMENSIONAL DATA

LIEBERT MINI-MATE2

Rear of Unit

Front of Unit

Shaded area indicatesa recommended clearanceof 30" (762mm) forcomponent accessand removal

Shaded area indicatesa recommended clearanceof 30" (762mm) forcomponent accessand removal

RS-485 port (using adaptor)

Notes:

1. Refer to DPN004854 for field communication connections.

BOTTOM VIEW

8"203mm

2 1/16"52mm

8 1/2"216mm

INTERFACE BOARD

IS-UNITY-DP CARD

ETHERNET port

NOT USED

Cover removed for clarity. Removal not required for making field communication connections.

NOT USED

Adaptor plugged into BMS 485 portwhen unit is shipped

Unity Card enclosure – see right views with details.

Page 125: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 2REV DATE : 2/19

DPN004854Page :1 /1

LIEBERT MINI-MATE2 & DATAMATE

For

m N

o.: D

PN

0010

40_R

EV

4

BMS COMMUNICATION CONNECTION OPTIONS

IS-UNITY-DP

BMS IP/485(1 Cooling Unit only)

1. Building Management System (BMS) Protocols *BACNet over IP/485 *Modbus over IP/4852. Communication wiring is field supplied - IP - use CAT5e cable or greater - 485 - use EIA 485 rated, shielded, twisted pair cable, 22-18AWG. - Must be rated to meet local codes and conditions.

BMS 485using adaptor

NOT USED

RESET BUTTON

BMS IP & SNMP v1/v2c/v3using ETHERNET PORT

NOT USED Adaptor plugged into BMS 485 portwhen unit is shipped

J3 - POWER 24V

INTERFACE

J2 - 485 port

TERMINAL/PLUG POSITION TERMINAL/PLUG POSITION TERMINAL/PLUG POSITION

COMMUNICATION (485) TB4 1 / 2 J2 2 / 1 77 / 78 N/A

POWER 24V 20, 21 N/A J3 1 / 2 J3 1 / 2

COMMUNICATION (485) 77, 78 N/A J2 2 / 1 77 / 78 N/A

POWER 24V TB1 4 / 8 J3 1 / 2 J3 1 / 2

COMMUNICATION (485) TB5 77 / 78 N/A N/A 77 / 78 N/A

POWER 24V N/A N/A N/A N/A J3 1 / 2

Liebert DataMate

WALL MOUNTED KITs**UNIT UNIT MOUNTED KITs*

Liebert Mini-Mate2 1-5 Ton

Liebert Mini-Mate2 8 Ton

NotesTerminals are presented in order of connection. For example, TB4-1 connects to J2-2.* Unit mounted kits are povided with Unit Comm & power wire harnesses; BMS Comm are field provided.** Wall mounted kits are provided with power wire harness and 120 Volt wall outlet transformer. Unit Comm & BMS Comm are field provided.

UNIT MOUNTED* Liebert Mini-Mate2 only)Factory Installed or Field Installed Kit

UNITY CARD

INTERFACE

J3 - POWER 24V77/78 TERMINALSCOMMUNICATION (485)

WALL MOUNTED KIT**Field Installed

UNIT TO INTERFACE BOARD CONNECTIONS

UNIT COMM & PWR

BMS IP

UNIT COMM

PWR

BMS IPBMS485BMS485

UNITY CARD

Field Wiring

Factory Wiring

Page 126: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 1REV DATE : 2/19

DPN004911Page :1 /1

WALL MOUNTED IS-UNITY-DP CARD FOR BMS CONNECTIVITY

For

m N

o.: D

PN

0010

40_R

EV

4

GENERAL ARRANGEMENT & DIMENSIONAL DATA

LIEBERT MINI-MATE2

Front of Unit

Field Provided Wiring

Wall

Thermostatwire to remotewall box.

Shaded area indicates a recommended clearancefor component access and removal.

Recommendeddisconnect switch

located withinsight of unit.

Not provided by Vertiv.

Typical Installation

Optional FilterBox Shown

Notes:

1. Communication to Liebert MiniMate2 unit.

2. Refer to DPN004854 for field communication connections.

3. Shaded areas indicate a recommended minimum clearance be provided for component access.

4. Locate the Unity Card Enclosure within 6' (1.8m) (length of power cord) of a 120V wall receptacle.

Liebert

MENU ESC

? ENTER

I / O

HI/LO

Wall MountedUnity Card Enclosure

4

Transformer &Power Cord(in kit)

120VACField Provided

BMS COMM

Communication Wire 1

UNITY CARD

INTERFACE

J3 - POWER 24V77/78 TERMINALSCOMMUNICATION (485)

PWR

BMS IP

UNIT COMM1 14 1/4"362mm

12"305mm

Top View3 3/8"85mm

Knockouts(Typ.)

Vertiv Provided Wiring

BMS485

Page 127: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

REV : 0REV DATE : 2/19

DPN004947Page :1 /1

WALL MOUNTED iCOM™ CMS FOR MOBILE CLOUD CONNECTIVITY

For

m N

o.: D

PN

0010

40_R

EV

4

GENERAL ARRANGEMENT & DIMENSIONAL DATA

LIEBERT MINI-MATE2

Front of Unit

Field Provided Wiring

Wall

Thermostatwire to remotewall box.

Shaded area indicates a recommended clearancefor component access and removal.

Recommendeddisconnect switch

located withinsight of unit.

Not provided by Vertiv.

Typical Installation

Optional FilterBox Shown

Notes:

1. Connection for optional SiteLink System or Modbus RTU..

2. Communication to Liebert MiniMate2 unit.

3. Refer to DPN003556 for field communication connections.

4. Locate the CMS Enclosure within 6' (1.8m) (length of power cord) of a 120V wall receptacle.

Liebert

MENU ESC

? ENTER

I / O

HI/LO

Liebert iCOM CMSEnclosure

4

Transformer &Power Cord(in kit)

120VACField Provided

WALL MOUNTED KIT

Communication Wire 2

Vertiv Provided Wiring

Front View

12"305mm

Top View

Liebert iCOM™ CMS Enclosure

14"355mm

14 1/4"362mm

Liebert iCOM™ CMSControl Board

24VAC Power ConnectionP5

ETHERNET 1(Mobile App)

ETHERNET 2(Modbus TCP/IP or SNMP v1, v2c)

USB (Software Upgrades)

ICOM™ CMS

485-1P59

485-2P58 3"

76mm

1

CommunicationKnockout

4"102mm

Bottom View

PowerKnockout

2

Page 128: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv | Liebert® Mini-Mate2™ Installer/User Guide

Page 129: Liebert® Mini-Mate2™ Installer/User Guide · 2018-08-09 · TABLEOFCONTENTS 1ImportantSafetyInstructions 1 1.1 AgencyListed 7 2Nomenclature 9 2.1 Nomenclaturefor Self-contained

Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA

© 2019VertivGroupCorp. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of VertivGroupCorp. All other names andlogos referred to are trade names, trademarks or registered trademarks of their respective owners. While everyprecaution has been taken to ensureaccuracyand completeness herein, VertivGroupCorp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this informationor for anyerrors or omissions. Specifications are subject to change without notice.