Date post: | 05-Apr-2018 |
Category: |
Documents |
Upload: | duy-nguyen-duc |
View: | 280 times |
Download: | 2 times |
of 25
8/2/2019 Liebert NXa UPS Battery Management
1/25
Liebert NXa 1
Battery Management
ENPC Engineering Team
Sep. 2003
8/2/2019 Liebert NXa UPS Battery Management
2/25
Liebert NXa 2
Contents
1.Overview
2.Basic Settings
3.Charging
4.Discharging
5.Maintenance6.Battery Curve
8/2/2019 Liebert NXa UPS Battery Management
3/25
Liebert NXa 3
1.Overview
1.1 Typical Charge & Discharge ProcessVoltage Current
Identify: Equalize Charge (Current Limiting or Constant Voltage ), Floating charge,Dishcharge process
40Ah
8/2/2019 Liebert NXa UPS Battery Management
4/25
Liebert NXa 4
(1) Charging Management
(2) Discharging Management
(3) Maintenance
(4)Battery Curve Customization
1.2 Scope
8/2/2019 Liebert NXa UPS Battery Management
5/25
Liebert NXa 5
2.Basic Settings
(1) Single Group Battery Capacity : 7-2500Ah(26Ah) C
(2) Number of Battery Groups: 1-10 (1)
(3) Battery cells number: 200-360 (240)(4) Battery Type Configuration: 1-20 (1)
1:VRLA 2:High discharge rate VRLA
(5) Battery Life Configuration: 12-120month (70month)
(6) Battery Curve(Characteristic): load from text file
8/2/2019 Liebert NXa UPS Battery Management
6/25
Liebert NXa 6
3.Charging
Typical process: current-limit equalize charge --->const-voltage equalize
charge --->float charge (Q: charging rate increase)
(1) Equalize charge/float charge auto transfer:
based on charging current, thresholds settable.
(2) Equalize charge maximum current limiting:settable, auto implemented by charger
(3) Equalize charge time protection:
settable, continuous equalize charging time limit.(4) Float charge voltage temperature compensation:
settable, negative coefficient
3.1 Functions
8/2/2019 Liebert NXa UPS Battery Management
7/25
Liebert NXa 7
3.2 Related Settings (1)
(1) Equalize Charge Allowed: 1/2 (1)
1:Enable 2:Disable
(2) Battery Float Charge Voltage: 2.20V~2.30V (2.25)
(3) Battery Equalize Charge Voltage: 2.30V~2.40V (2.35)
(4) Battery Charge Current Limit: 0.02~0.25C (0.2C)
for High discharge rate VRLA 0.02~0.10C (0.1C)
(5) Threshold for Equalize charge to Float charge: 0.005~0.025C(0.01C)
(6) Threshold for Float charge to Equalize charge: 0.03~0.07C(0.05C)
Note: Actual Current = above set pointSingle Group Battery CapacityNumber of Battery Groups
8/2/2019 Liebert NXa UPS Battery Management
8/25
Liebert NXa 8
(7) Temperature Compensation Allowed: 1/2 (1)
(8) Temperature Compensation Central Point: 2030 (25)
(9) Temperature Compensation Factor: 0.003~0.005
(Vf is limited to [ 2.2, 2.3])
(10) Equalize Charge Protect Time Limit: 960~1800 min(1440)
3.2 Related Settings(2)
8/2/2019 Liebert NXa UPS Battery Management
9/25
Liebert NXa 9
4.Discharging
Typical process: discharging --->pre-warning --->EOD shutdown
(Q: charging rate decrease)
(1) Backup time forecast:
based on Q, Tpb and Kc. (Tpb--basic backup time at P, Kc---Capacity Factor)
(2) Under-voltage pre-warning:
interpolation using 3-min and 6-min (P, U) curve, also refined by user desiredEOD
(3) End of discharging (EOD) protection:
lowest protection point settable, real shutdown point is regulated according topre-warning voltage.
(4) Small current discharge protection:
settable, continuous discharging time limit.
4.1 Functions
8/2/2019 Liebert NXa UPS Battery Management
10/25
Liebert NXa 10
4.2 Related Settings
(1) Battery Low Warning Time 3~60 min (5)
(2) EOD (End of discharge) Voltage 1.20~1.90V (1.70)
(3) Small Current Discharge Protection 1200~1800min(1440)
8/2/2019 Liebert NXa UPS Battery Management
11/25
Liebert NXa 11
5.Maintenance
5.1 Maintenance Test
Usage:
Periodic reactivation, discharging 20% rated capacity with set power.Conditions:
Battery fully charged, load 20~80%.
Trigger:
Manually through LCD panel or Automatically.
Battery Self Test Interval 720~4320 hour (1440)
Maintenace Test Power in battery curve data (total KW)
8/2/2019 Liebert NXa UPS Battery Management
12/25
Liebert NXa 12
5.2 Capacity Test (1)
Usage:
Battery curve update, discharging to EOD with whole load.
Conditions:
Battery fully charged, load 20~80%.
Trigger:
Manually through LCD panel .
8/2/2019 Liebert NXa UPS Battery Management
13/25
Liebert NXa 13
5.2 Capacity Test (2)
L ie b e rt N X a 2 0 0 3 -0 1 -2 2 1 2 : 3 0 : 3 66 0k V A -3 X 3 U n it #1 N o rm a l
?
B y p a s sM a i n
V p h a s e V
Ip h a s e A
F re q . H z
V lin e VP . F .
A (A B )
2 2 02 0 .5
50.1
3 8 00 .9 9
B (B C )
2 2 0
2 0 .5
50 .1
3 8 00 .9 9
C (C A )
2 2 0
20.5
50 .1
3 8 00.99
F 2 F 4 F 5F 1 F 3
O u t p u t
In p u t B r e a k e r C lo s e d 0 1 -1 2 1 2 :2 8 :1 6
M a n u a l T u rn O n 0 1 -1 2 1 2:3 0 :0 6
U P S in N o rm a l M o d e 0 1-2 2 1 2 :3 0:1 6
B a t t e r y w i l l b e d e p l e t e d ,C o n f i r m o r c a n c e l
E S C
8/2/2019 Liebert NXa UPS Battery Management
14/25
Liebert NXa 14
5.3 Battery Life Forecast
8/2/2019 Liebert NXa UPS Battery Management
15/25
Liebert NXa 15
6.1 Battery Curve Content
6.Battery Curve
(1) Backup time curve: (P,Tpb)
(2) Prewarning curves: (P,U) 3min and 6min
(3) Some set points
(4) Some coefficients
8/2/2019 Liebert NXa UPS Battery Management
16/25
Liebert NXa 16
6.2 Pre-warning Curves Example
Battery Low Voltage
1.651.71.751.81.851.91.95
0.
83
1.
11
1.
5
1.
77
2.
46
3.
33
3.
74
4.
38
5.
36
W/AH
Voltage
UP3
UP6
8/2/2019 Liebert NXa UPS Battery Management
17/25
8/2/2019 Liebert NXa UPS Battery Management
18/25
Liebert NXa 18
6.4 Battery Curve Data Description(2)
(1) [battery_curve_base_num]: data number in the file
(2) [battery_curve_base_data]: curve data
Line 1: discharging power for each cell (W/cell)Line 2: corresponding backup time
Line 3: corresponding dischargable capacity percentage (1 for 10hour discharging)
Line 4: discharging power/capacity (W/Ah)
Line 5: corresponding 3-min prewarning voltage
Line 6: corresponding 6-min prewarning voltage
Line 7-9: other set points or
8/2/2019 Liebert NXa UPS Battery Management
19/25
Liebert NXa 19
6.5 Load Battery Curve from file
8/2/2019 Liebert NXa UPS Battery Management
20/25
Liebert NXa 20
6.6 Customize Battery Curve (1)
For VRLA battery, custom battery curve could be built according to batterydatasheet or experimental data.
Custom battery curve can enhance the accuracy of backup time forecast, andprovide better battery and load protection .
Generally, only the first 3 lines (backup time curve) should be customized.
8/2/2019 Liebert NXa UPS Battery Management
21/25
Liebert NXa 21
6.6 Customize Battery Curve (2)
CSB 26Ah Dtasheet and Curve
8/2/2019 Liebert NXa UPS Battery Management
22/25
Liebert NXa 22
6.6 Customize Battery Curve (3)
CSB 40Ah Dtasheet and Curve
8/2/2019 Liebert NXa UPS Battery Management
23/25
Liebert NXa 23
6.6 Customize Battery Curve (4)
To build custom battery curve without datasheet, you can specify thedischarging power in the first line by replacing the C in the followingtemplate with real battery capacity .
8/2/2019 Liebert NXa UPS Battery Management
24/25
Liebert NXa 24
6.7 Battery Parameters
8/2/2019 Liebert NXa UPS Battery Management
25/25
Liebert NXa 25
Thanks