NOTE: NOT ALL ABBREVIATIONS MAY BE USED. ABBREVIATION SCHEDULE ABOVE COUNTER AMP OR AMPS ADJACENT ABOVE FINISHED FLOOR AUTHORITY HAVING JURISDICTION ALUMINUM CONDUIT CIRCUIT BREAKER CIRCUIT CONVENIENCE OUTLETS COPPER EACH ELECTRICAL EMERGENCY ELECTRIC METALLIC TUBING ELECTRIC NONMETALLIC TUBING EQUIPMENT ELECTRIC WATER COOLER EXISTING EXPLOSION PROOF FIRE ALARM FIRE ALARM CONTROL PANEL FULL LOAD AMPS FLEXIBLE METAL CONDUIT FREIGHT ON BOARD GROUND CONDUCTOR HAND-OFF-AUTO HORSE POWER ISOLATED GROUND INTERMEDIATE METAL CONDUIT INSULATED ISOLATED KILO VOLT AMPERES KILOWATTS LIQUID-TIGHT METAL CONDUIT LIQUID-TIGHT NONMETAL CONDUIT MINIMUM CIRCUIT AMPS MAIN LUGS ONLY NORMALLY CLOSED NOT IN CONTRACT NIGHT LIGHT NORMALLY OPEN ON CENTER(S) OVER CURRENT PROTECTION QUANTITY REMOVE REQUIREMENTS RIGID METAL CONDUIT RIGID NONMETALLIC CONDUIT REMOVE AND RELOCATE SURGE SUPPRESSION SECURITY CONTROL PANEL TAMPER RESISTANT TYPICAL TRANSIENT VOLTAGE SURGE SUPPRESSOR UNDER FLOOR UNDERGROUND UNLESS NOTED OTHERWISE WITH WEATHER PROOF TRANSFORMER A A ADJ AFF AHJ AL C CB CKT C.O.'S CU EA ELEC EM EMT ENT EQUIP EWC E, EX EXP FA FACP FLA FMC FOB GND HOA HP IG IMC INS ISO KVA KW LFMC LFNC MCA MLO N.C. N.I.C. N.L. N.O. O.C. OCP QTY R REQ. RMC RNC RR SS SCP TR TYP TVSS UF UG U.N.O. W/ WP XFMR 1 CIRCUIT, 2 WIRE BRANCH CIRCUIT HOME RUN TO PANEL BRANCH CIRCUITING SYMBOLS 2 CIRCUIT, 4 WIRE BRANCH CIRCUIT HOME RUN TO PANEL 3 CIRCUIT, 6 WIRE BRANCH CIRCUIT HOME RUN TO PANEL MULTIPLE WIRE BRANCH CIRCUITING BETWEEN FIXTURES, SWITCHES, DEVICES, ETC. BRANCH CIRCUITING (U.N.O.) TURNED UP OR TOWARDS OBSERVER. BRANCH CIRCUITING (U.N.O.) TURNED DOWN OR AWAY FROM OBSEVER. BRANCH CIRCUITING (U.N.O.) CONTINUATION CONDUIT STUB-IN INCOMING SERVICE CAP AND MARK JUNCTION BOX MOUNT AS NOTED. SUBSCRIPT 'F' INDICATES TO PROVIDE A FLOOR BOX WITH BLANK COVERPLATE DESCRIPTION SYMBOL REMARKS ARROWS: NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS REQUIRED. SHORT CROSS LINES: NUMBER OF SHORT CROSS LINES INDICATES NUMBER OF PHASE, TRAVELER, AND/OR SWITCHED CONDUCTORS REQUIRED IF GREATER THAN 1 (ONE). LONG CROSS LINES: NUMBER OF LONG CROSS LINES INDICATES NUMBER OF NEUTRAL CONDUCTORS REQUIRED FOR MULTI-WIRE HOME RUNS. EQUIPMENT GROUND AND ISOLATED GROUND CONDUCTORS: EQUIPMENT GROUND AND ISOLATED GROUND CONDUCTORS ARE NOT SHOWN, BUT ARE REQUIRED AS NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS. J ELECTRONIC SYSTEM GENERAL SYMBOLS MOUNTING REMARKS DESCRIPTION SYMBOL ELECTRONIC SYSTEM PANELBOARD (SURFACE MOUNT) ELECTRONIC SYSTEM TERMINAL BOARD TOP AT 72" ELECTRONIC SYSTEM PANELBOARD (FLUSH MOUNT) TOP AT 72" TOP AT 72" NAME PANEL NAME PANEL ELECTRONIC SYSTEMS MAY INCLUDE BUT ARE NOT SPECIFICALLY LIMITED TO, TELEPHONE, DATA, TELEVISION, LIGHTING CONTROL, CLOCKS, FIRE ALARM, ACCESS CONTROL, SECURITY, CCTV, SOUND SYSTEM, NURSE CALL, OR INTERCOM. FIRE/SMOKE DAMPER BEAM DETECTOR - TRANSMITTER FIRE ALARM SYMBOLS AUDIO HORN FIRE ALARM VISUAL STROBE FIRE ALARM AUDIO/VISUAL HORN/STROBE FIRE ALARM AUDIO SPEAKER FIRE ALARM AUDIO/VISUAL SPEAKER/STROBE DUCT SMOKE DETECTOR SIDE OF DUCT MAGNETIC DOOR HOLDER DOOR INSTALLER COORDINATE WITH FIRE ALARM MANUAL STATION TAMPER SWITCH WATER FLOW INDICATOR CONTROL MODULE MONITOR MODULE FAN SHUTDOWN RELAY WATER FLOOD INDICATOR BEAM DETECTOR - RECEIVER ON FIRE RISER AT VALVE TOP AT 72" SMOKE DETECTOR HEAT DETECTOR CEILING CEILING +48" AT DEVICE(S) TO BE CONTROLLED AT DEVICE(S) TO MONITOR AT FAN CONTROL PANEL COORDINATE WITH DOOR INSTALLER; SUBSCRIPT 'F' INDICATES TO MOUNT AT FLOOR LEVEL FLOOR FIRE PROTECTION SPRINKLER RISER BELL +90" SUBSCRIPT 'WP' INDICATES THAT A WEATHER PROOF BACK BOX IS REQ. SUBSCRIPT 'C' INDICATES CEILING MOUNTING. NUMERIC SUBSCRIPT INDICATES CANDELLA RATING OF STROBE (I.E. - 15, 75, 110) FURNISHED BY FIRE PROTECTION CONTRACTOR AND INSTALLED AND CONNECTED BY DIV. 26 4" BELOW CEILING TO TOP OF DETECTOR 4" BELOW CEILING TO TOP OF DETECTOR INDOOR - 96" FROM FINISH FLOOR TO TOP OF DEVICE. OUTDOOR - 120" FROM FINISHED GRADE TO TOP OF DEVICE DESCRIPTION SYMBOL MOUNTING REMARKS END OF LINE DEVICE PER MANUFACTURER RECOMMENDATIONS F FIRE FIGHTERS TELEPHONE JACK +48" EOL S H WF D R I Z F W T FSD T D R FIRE ALARM CONTROL PANEL FACP CEILING CARBON MONOXIDE DETECTOR CO ELECTRIC MOTOR MANUAL STARTER WITH THERMAL OVERLOAD(S) GEAR AND CONTROL SYMBOLS AT EQUIPMENT +60" NON-FUSED DISCONNECT SWITCH +60" FUSED DISCONNECT SWITCH CIRCUIT BREAKER AND ENCLOSURE +60" MAGNETIC STARTER +60" COMBINATION MAGNETIC STARTER / NON-FUSED DISCONNECT +60" COMBINATION MAGNETIC STARTER / FUSED DISCONNECT +60" COMB. MAGNETIC STARTER / MOTOR CIRCUIT PROTECTOR (MCP) +60" COMB. VARIABLE FREQUENCY DRIVE / MOTOR CIRCUIT PROTECTOR (MCP) FLOOR OR WALL AS SPECIFIED TOP AT +72" IF WALL MOUNTED LIGHTING AND APPLIANCE PANELBOARD (SURFACE-MOUNTED) TOP AT +72" LIGHTING AND APPLIANCE PANELBOARD (FLUSH-MOUNTED) 20"W X 6"D 20"W X 6"D TOP AT +72" 14"W X 3"D TOP AT +72" LOAD CENTER (FLUSH-MOUNTED) LOAD CENTER (SURFACE-MOUNTED) TOP AT +72" 14"W X 3"D POWER DISTRIBUTION PANELBOARD WALL THESE SYMBOLS ARE SWITCHBOARD FLOOR GENERAL IN NATURE AND MAY VARY IN SIZE AND SHAPE TO SUIT APPLICATION. CROSS HATCHING INDICATES "MAIN PANELBOARD OR SWITCHBOARD" METER BASE TOP AT +72" NAME IS INDICATED IN SEMI-QUOTES (I.E. 'L2A', 'MDP') OPEN - STOP - CLOSE SWITCH +60" HVAC THERMOSTAT +60" HAND - OFF - AUTO SWITCH +60" 23 PROVIDED BY DIVISION FURNISHED BY ANOTHER FURNISH SWITCH UNLESS DIVISION. INSTALL AND CONNECT COMPLETE. REFER TO RELATED SPECIFICATION SECTIONS. DESCRIPTION SYMBOL MOUNTING REMARKS GROUND FAULT PROTECTION VFD F T GF T ELECTRICAL SYMBOL SCHEDULE GENERAL NOTES 1. 2. 3. 4. MOUNT ALL OUTLETS, DEVICES, AND EQUIPMENT AT HEIGHTS INDICATED BELOW, UNLESS NOTED OTHERWISE ON THE DRAWINGS. UNLESS NOTED OTHERWISE, HEIGHTS ARE GIVEN FROM FINISHED FLOOR TO CENTER OF OUTLET BOX. WHERE OUTLETS, DEVICES, AND EQUIPMENT ARE NOTED BY SUBSCRIPTS, REFER TO ABBREVIATION SCHEDULE FOR DEFINED REQUIREMENTS. WHERE OUTLETS, DEVICES AND EQUIPMENT ARE NOTED BY THE SUBSCRIPT 'A', MOUNT AT 4" ABOVE COUNTER. IF COUNTER HAS A BACK SPLASH, MOUNT AT 4" ABOVE BACK SPLASH. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS AND COORDINATE WITH CASEWORK SUPPLIER. NOT ALL ELECTRICAL SYMBOLS MAY BE USED. KEYED NOTE GENERAL SYMBOLS DETAIL REFERENCE TOP NUMBER INDICATES DETAIL NUMBER; BOTTOM LETTER-NUMBER INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN; WHERE NOT SPECIFICALLY REFERENCED, DETAIL IS GENERAL IN NATURE AND SHALL APPLY WHERE APPLICABLE. ELEVATION REFERENCE TOP NUMBER INDICATES ELEVATION NUMBER; BOTTOM LETTER-NUMBER INDICATES WHERE ELEVATION IS SHOWN. SECTION REFERENCE TOP NUMBER INDICATES SECTION NUMBER; BOTTOM LETTER NUMBER INDICATES WHERE SECTION IS SHOWN. ARCHITECTURAL ROOM NUMBER EQUIPMENT NAME / NUMBER TOP NUMBER ABBREVIATES EQUIPMENT NAME OR TYPE; BOTTOM NUMBER INDICATES EQUIPMENT NUMBER. REFER TO EQUIPMENT SCHEDULE. REVISION NUMBER USED TO DENOTE CHANGES EITHER ISSUED BY ADDENDUM OR DURING CONSTRUCTION AND TO DENOTE RECORD DRAWING CHANGES. BREAKLINE USED TO BREAK DRAWINGS. DESCRIPTION SYMBOL REMARKS 2 E-2 1 AHU 1 100 XX 1 E-1 3 E-2 WALL-MOUNTED FIXTURE ARM-MOUNTED SINGLE-HEAD LIGHT FIXTURE AND POLE AS SPECIFIED LIGHTING SYMBOLS POST-TOP SINGLE-HEAD, LIGHT FIXTURE AND POLE ARM-MOUNTED DOUBLE-HEAD LIGHT FIXTURE AND POLE OR DETAILED AS SPECIFIED OR DETAILED AS SPECIFIED OR DETAILED REFER TO ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHT AS SPECIFIED OR DETAILED WALL-MOUNTED LINEAR FLUORESCENT LIGHT FIXTURE OR DETAILED AS SPECIFIED FLUORESCENT LINEAR WALL WASHER AS SPECIFIED OR DETAILED RECESSED DOWN LIGHT RECESSED WALL-WASHER OR DIRECTIONAL DOWNLIGHT AS SPECIFIED OR DETAILED AS SPECIFIED OR DETAILED AS SPECIFIED OR DETAILED SURFACE OR PENDANT-MOUNTED LIGHT FIXTURE AS SPECIFIED OR DETAILED TRACK OR MONO-POINT LIGHT FIXTURE WALL SCONCE AS SPECIFIED OR DETAILED FLUORESCENT EGRESS LIGHT FIXTURE AS SPECIFIED OR DETAILED FLUORESCENT EMERGENCY (NON-EGRESS) LIGHT FIXTURE AS SPECIFIED OR DETAILED THIS IS AN EXAMPLE OF AN EGRESS LIGHT FIXTURE. EGRESS LIGHT FIXTURES ARE HALF-SHADED DIAGONALLY. THIS IN AN EXAMPLE OF AN EMERGENCY (NON-EGRESS) LIGHT FIXTURE. EMERGENCY FIXTURES ARE FULLY-SHADED. CEILING MOUNTED EXIT SIGN CEILING WALL-MOUNTED EXIT SIGN WALL ABOVE DOOR WALL-MOUNTED EXIT SIGN W/ EMERGENCY LIGHT FIXTURE DOOR WALL ABOVE DARKENED PORTION OF SIGN INDICATES FACE(S); ARROW(S) INDICATE CHEVRON DIRECTION(S) TIME CLOCK EMERGENCY LIGHT FIXTURE AS NOTED ELECTRIC PHOTOCELL N/A MOUNT ON ROOF FACING NORTH SKY LIGHT FIXTURE CALLOUT (LETTER DENOTES FIXTURE TYPE) IF SHOWN, ARROW INDICATES AIMING DIRECTION IF SHOWN, ARROW INDICATES AIMING DIRECTION DESCRIPTION SYMBOL MOUNTING REMARKS LIGHT FIXTURE SYMBOLS ARE GENERAL IN NATURE AND MAY BE SHOWN ON THE DRAWINGS IN VARIOUS SIZES AND SHAPES. REFER TO THE LIGHT FIXTURE SCHEDULE FOR SPECIFICATION INFORMATION. ARROWS INDICATE AIMING DIRECTION. 2. 1. RECESSED INDIRECT FLUORESCENT LIGHT FIXTURES AS SPECIFIED OR DETAILED XX P TC LINEAR PENDANT LIGHT FIXTURE CEILING SYMBOL OCCUPANCY SENSOR LEGEND MOUNTING CEILING REFER TO OCCUPANCY SENSOR SCHEDULE ON SHEET EL701 REMARKS OCCUPANCY SENSOR WALL OCCUPANCY SENSOR +48" OCCUPANCY SENSOR/SWITCH OS X X W X 1. ALL DIGITAL OCCUPANCY SENSORS MUST BE PROGRAMED TO AUTOMATICALLY TURN ON LIGHTING TO 50% LIGHT LEVEL. 2. TIE DIGITAL OCCUPANCY SENSORS TO THE ENLOSED REGION'S ROOM CONTROLLER WITH CAT5 CABLE. 3. REFER TO WIRING DIAGRAMS AND SCHEDULES ON SHEET EL701 FOR MORE INFORMATION. COMBINATION TELEPHONE/DATA OUTLET DATA OUTLET TELEPHONE OUTLET +18" +18" +18" TELEPHONE / DATA SYMBOLS DESCRIPTION SYMBOL MOUNTING REMARKS TELEPHONE TERMINAL BOARD TOP AT 72" ACCESS POINT CEILING DIMMER SWITCH SINGLE-POLE TOGGLE SWITCH WITH PILOT LIGHT KEY-OPERATED SINGLE-POLE TOGGLE SWITCH FOUR-WAY TOGGLE SWITCH THREE-WAY TOGGLE SWITCH SINGLE-POLE TOGGLE SWITCH +48" +48" +48" +48" +48" WIRING DEVICE SYMBOLS TIMER SWITCH +48" +48" RATE DIMMER SWITCH FOR MAXIMUM POSSIBLE WATTAGE DOUBLE-POLE TOGGLE SWITCH +48" SPLIT-WIRED DUPLEX RECEPTACLE +18" SIMPLEX RECEPTACLE +18" DUPLEX RECEPTACLE +18" FOURPLEX RECEPTACLE +18" GROUND FAULT CIRCUIT INTERRUPTER DUPLEX RECEPTACLE +18" +18" EMERGENCY DUPLEX RECEPTACLE +18" EMERGENCY FOURPLEX RECEPTACLE +18" FLOOR/CEILING SPECIAL PURPOSE OUTLET +18" CORD DROP WITH DUPLEX RECEPTACLE +18" SINGLE-POLE TOGGLE SWITCH +48" SUBSCRIPT KEYS SWITCH TO FIXTURES CONTROLLED. (2) SINGLE-POLE TOGGLE SWITCH DUAL LEVEL SWITCH OUTBOARD LAMPS SEPARATELY FROM INBOARD LAMPS. +48" LOW VOLTAGE MOMENTARY CONTACT SWITCH +48" 3-POSITION MOMENTARY CONTACT SWITCH +48" REFER TO DETAIL UP-ON; CENTER-NEUTRAL; DOWN-OFF 3-POSITION MAINTAINED CONTACT SWITCH +48" UP-ON; CENTER-OFF; DOWN-ON GROUND FAULT CIRCUIT INTERRUPTER FOURPLEX RECEPTACLE POWER / TELEPHONE POLE (5-20R) MULTI-OUTLET ASSEMBLY 4" ABOVE SUBSCRIPT IN PARENTHESIS INDICATES NEMA CONFIGURATION IF SHOWN. REFER TO DRAWINGS AND/OR EQUIPMENT SCHEDULES. CONFIRM EXACT CONFIGURATION WITH OWNER PRIOR TO INSTALLATION. REFER TO DETAIL 125/250V RECEPTACLE +18" DRYER -- NEMA 14-30R RANGE -- NEMA 14-50R BACKSPLASH DESCRIPTION SYMBOL MOUNTING REMARKS J 3PN 3PM TIM DIM P K 4 3 2 a LIGHT LEVEL SENSOR CEILING LV X REFER TO LOW VOLTAGE SCHEDULE ON SHEET EL701 CLOSED CIRCUIT TELEVISION SYMBOLS MATRIX SWITCHER CLOSED CIRCUIT TELEVISION CAMERA CLOSED CIRCUIT TELEVISION CAMERA (FIXED) CLOSED CIRCUIT TELEVISION MONITOR CEILING CEILING CEILING DESK DESK FIBER JUNCTION BOX 72" TO TOP OF BOX CLOSED CIRCUIT TELEVISION CAMERA (PAN/TILT/ZOOM) (HIGH SPEED DOME WITH PAN / TILT / ZOOM HEAD) DESCRIPTION SYMBOL MOUNTING REMARKS FX PTZ TV MATRIX FJ GENERAL PROJECT NOTES 1. 2. 3. 4. 5. 6. 7. DIVISION 26000 CONTRACTOR IS RESPONSIBLE FOR READING AND APPLYING WHAT IS IN THE SPECIFICATIONS TO THIS PROJECT. ANYTHING THAT IS NOT INCLUDED ON THE PROJECT THAT IS CALLED OUT IN THE SPECIFICATION SHALL BE LISTED ON THE SUBSTANTIAL COMPLETION PUNCHLIST. THE CONTRACTOR WILL BE REQUIRED TO REMEDY THESE DEFICIENCIES WITHOUT ADDITIONAL COSTS TO OWNER. THERE WILL BE NO EXCEPTIONS. THE CONTRACTOR MAY SCHEDULE A PRE-CONSTRUCTION MEETING. AT THEIR DISCRETION, WITH THE ELECTRICAL ENGINEER TO REVIEW THE DRAWINGS AND SPECIFICATIONS. THE MEETING SHALL BE A MAXIMUM OF ONE HOUR AND SHALL TAKE PLACE AT THE ENGINEER'S OFFICE. THE FOLLOWING ITEMS ARE SOME OF THE REQUIREMENTS THAT ARE LISTED IN THE SPECIFICATIONS. THESE ITEMS ARE NOT ALL INCLUSIVE AND THE CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE TO ALL REQUIREMENTS OF THE SPECIFICATIONS: A INSULATED THROAT CONNECTORS OR PLASTIC BUSHINGS SHALL BE UTILIZED FOR ALL CONDUIT SIZED USED ON THIS PROJECT. B THE CONTRACTOR IS RESPONSIBLE FOR UPSIZING CONDUCTORS FOR VOLTAGE DROP PER THE NEC REGARDLESS OF WHETHER IT IS SHOWN ON THE PLANS OR NOT. C THE CONTRACTOR SHALL LABEL ALL ELECTRICAL EQUIPMENT AS IT IS CALLED OUT IN THE SPECIFICATIONS. D THE CONTRACTOR SHALL PROVIDE SEISMIC SUPPORT AND BRACING FOR ALL LIGHT FIXTURES AND ELECTRICAL EQUIPMENT AS REQUIRED BY APPLICABLE LOCAL AND NATIONAL CODES. THE CONTRACTOR SHALL FOLLOW THE PANELBOARD SCHEDULES AS INDICATED IN THE DRAWINGS. EACH CIRCUIT BREAKER HAS BEEN ASSIGNED TO SPECIFIC AREA OF THE BUILDING. NO DEVIATION WILL BE ALLOWED WITHOUT WRITTEN APPROVAL FROM THE ELECTRICAL ENGINEER. AT A MINIMUM THE CONTRACTOR SHALL INSTALL THE WIRE SIZE AS CALLED OUT ON THE ONE-LINE DIAGRAM. HOWEVER, THE CONTRACTOR IS RESPONSIBLE TO ENSURE THE WIRE IS SIZED LARGE ENOUGH TO ALLOW FOR VOLTAGE DROP. THE CONTRACTOR SHALL VERIFY ALL MECHANICAL OVERCURRENT DEVICES FOR THE ACTUAL MECHANICAL EQUIPMENT SUPPLIED ON THE JOB, PRIOR TO RELEASE OF ANY ELECTRICAL DISTRIBUTION EQUIPMENT. CONTACT THE ELECTRICAL ENGINEER WITH ANY DISCREPANCIES. THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING THE BID, AND SHALL EXAMINE ALL PHYSICAL CONDITIONS WHICH MAY BE MATERIAL TO THE PERFORMANCE OF HIS WORK. NO ADDITIONAL PAYMENTS WILL BE ALLOWED TO THE CONTRACTOR AS A RESULT OF EXTRA WORK MADE NECESSARY BY HIS FAILURE TO DO SO. ANY CASE OF DISCREPANCY OR LACK OF CLARITY SHALL BE PROMPTLY IDENTIFIED TO THE OWNER'S REPRESENTATIVE AND THE ENGINEER FOR CLARIFICATION. AUDIO/VISUAL SYSTEM SYMBOLS DESCRIPTION SYMBOL MOUNTING REMARKS PROJECTOR SCREEN - SURFACE MOUNTED SURFACE SUBSCRIPT INDICATES SCREEN DIMENSIONS KEY PAD +48" TV OUTLET +18" KP1 ACCESS CONTROL SYMBOLS PROXIMITY CARD READER / KEYPAD MAGNETIC LOCK ELECTROMAGNETIC DOOR STRIKE REQUEST-TO-EXIT MOTION DETECTOR KEYPAD MAGNETIC STRIP CARD READER / KEYPAD PROXIMITY CARD READER MAGNETIC STRIP CARD READER MOUNTING REMARKS DESCRIPTION SYMBOL MAGNETIC DOOR CONTACT SWITCH CEILING DOOR DOOR DOOR +48" +48" +48" +48" +48" REX S D M KP PK MK PR MR DURESS PUSH-BUTTON MOTION DETECTOR SECURITY SYMBOLS CEILING BELOW DESK DOOR SUBSCRIPT DENOTES DEGREES OF MONITORED AREA DESCRIPTION SYMBOL MOUNTING REMARKS D MD REQUEST FOR EXIT DOOR REX 845 South 220 East Orem, UT 84058 Phone: 801.229.0088 Fax: 801.229.0089 www.sandstromarchitecture.com DRAWN BY CHECKED BY DATE PROJECT NO. SHEET NUMBER SHEET DESCRIPTION DATE REVISION/ISSUE 2/23/2017 5:40:52 PM C:\Revit 2017 Local Files\2016-201_ELEC-CENTRAL_17V_AlexEcton.rvt NEW PROVO TRANSPORTATION FACILITY PROVO SCHOOL DISTRICT 1100 EAST 1320 SOUTH PROVO, UT 84606 SA-1610 02/23/2016 DR ACE EG001 GENERAL NOTES AND SYMBOLS LIST SHEET INDEX EG001 GENERAL NOTES AND SYMBOLS LIST ES101 SITE PLAN - ELECTRICAL ES501 SITE DETAILS ES502 SITE DETAILS EL101 CEILING PLAN LEVEL 1 - LIGHTING EL102 CEILING PLAN MEZZ - LIGHTING EL601 LIGHT FIXTURE SCHEDULE EL701 WIRING DIAGRAMS EP101 FLOOR PLAN LEVEL 1 - POWER EP501 POWER DETAILS EP502 DOOR SECURITY DETAILS EP503 DOOR SECURITY DETAILS EP601 EQUIPMENT SCHEDULES EP701 POWER ONE-LINE DIAGRAM EP702 RISER DIAGRAMS - POWER EP703 RISERS AND DETAILS - POWER EP801 PANEL SCHEDULES EP802 PANEL SCHEDULES
Transcript
  • NOTE: NOT ALL ABBREVIATIONS MAY BE USED.

    ABBREVIATION SCHEDULE

    ABOVE COUNTERAMP OR AMPSADJACENTABOVE FINISHED FLOOR AUTHORITY HAVING JURISDICTIONALUMINUMCONDUITCIRCUIT BREAKERCIRCUITCONVENIENCE OUTLETSCOPPEREACHELECTRICALEMERGENCYELECTRIC METALLIC TUBING ELECTRIC NONMETALLIC TUBING EQUIPMENTELECTRIC WATER COOLER EXISTINGEXPLOSION PROOFFIRE ALARMFIRE ALARM CONTROL PANEL FULL LOAD AMPSFLEXIBLE METAL CONDUIT FREIGHT ON BOARDGROUND CONDUCTOR HAND-OFF-AUTOHORSE POWERISOLATED GROUND INTERMEDIATE METAL CONDUIT INSULATED

    ISOLATEDKILO VOLT AMPERESKILOWATTSLIQUID-TIGHT METAL CONDUIT LIQUID-TIGHT NONMETAL CONDUIT MINIMUM CIRCUIT AMPSMAIN LUGS ONLYNORMALLY CLOSEDNOT IN CONTRACTNIGHT LIGHTNORMALLY OPENON CENTER(S)OVER CURRENT PROTECTIONQUANTITYREMOVEREQUIREMENTSRIGID METAL CONDUITRIGID NONMETALLIC CONDUITREMOVE AND RELOCATESURGE SUPPRESSIONSECURITY CONTROL PANELTAMPER RESISTANTTYPICALTRANSIENT VOLTAGE SURGE SUPPRESSORUNDER FLOORUNDERGROUNDUNLESS NOTED OTHERWISEWITHWEATHER PROOFTRANSFORMER

    AA ADJAFFAHJALCCBCKTC.O.'SCU EAELECEMEMTENTEQUIPEWCE, EXEXPFAFACPFLAFMCFOBGNDHOAHPIGIMCINS

    ISOKVAKWLFMC LFNCMCAMLON.C.N.I.C.N.L.N.O.O.C.OCPQTYRREQ.RMCRNCRRSSSCPTRTYPTVSSUFUGU.N.O.W/ WPXFMR

    1 CIRCUIT, 2 WIRE BRANCH CIRCUIT HOME RUN TO PANEL

    BRANCH CIRCUITING SYMBOLS

    2 CIRCUIT, 4 WIRE BRANCH CIRCUIT HOME RUN TO PANEL

    3 CIRCUIT, 6 WIRE BRANCH CIRCUIT HOME RUN TO PANEL

    MULTIPLE WIRE BRANCH CIRCUITING BETWEEN FIXTURES,SWITCHES, DEVICES, ETC.

    BRANCH CIRCUITING (U.N.O.) TURNED UP OR TOWARDS OBSERVER.

    BRANCH CIRCUITING (U.N.O.) TURNED DOWN OR AWAY FROM OBSEVER.

    BRANCH CIRCUITING (U.N.O.) CONTINUATION

    CONDUIT STUB-IN

    INCOMING SERVICE

    CAP AND MARK

    JUNCTION BOX MOUNT AS NOTED.SUBSCRIPT 'F' INDICATES TO PROVIDE A FLOOR

    BOX WITH BLANK COVERPLATE

    DESCRIPTIONSYMBOL REMARKS

    ARROWS: NUMBER OF ARROWS INDICATESNUMBER OF CIRCUITS REQUIRED.

    SHORT CROSS LINES: NUMBER OF SHORTCROSS LINES INDICATES NUMBER OF PHASE,TRAVELER, AND/OR SWITCHEDCONDUCTORS REQUIRED IF GREATER THAN 1(ONE).

    LONG CROSS LINES: NUMBER OF LONGCROSS LINES INDICATES NUMBER OFNEUTRAL CONDUCTORS REQUIRED FORMULTI-WIRE HOME RUNS.

    EQUIPMENT GROUND AND ISOLATEDGROUND CONDUCTORS: EQUIPMENTGROUND AND ISOLATED GROUNDCONDUCTORS ARE NOT SHOWN, BUT AREREQUIRED AS NOTED ON THE DRAWINGS ORIN THE SPECIFICATIONS.

    J

    ELECTRONIC SYSTEM GENERAL SYMBOLS

    MOUNTING REMARKSDESCRIPTIONSYMBOL

    ELECTRONIC SYSTEM PANELBOARD(SURFACE MOUNT)

    ELECTRONIC SYSTEM TERMINAL BOARD TOP AT 72"

    ELECTRONIC SYSTEM PANELBOARD(FLUSH MOUNT)

    TOP AT 72"

    TOP AT 72"NAMEPANEL

    NAMEPANEL ELECTRONIC SYSTEMS MAY

    INCLUDE BUT ARE NOT SPECIFICALLY LIMITED TO,

    TELEPHONE, DATA, TELEVISION, LIGHTING CONTROL, CLOCKS, FIRE

    ALARM, ACCESS CONTROL, SECURITY, CCTV, SOUND SYSTEM,

    NURSE CALL, OR INTERCOM.

    FIRE/SMOKE DAMPER

    BEAM DETECTOR - TRANSMITTER

    FIRE ALARM SYMBOLS

    AUDIO HORN

    FIRE ALARM VISUAL STROBE

    FIRE ALARM AUDIO/VISUAL HORN/STROBE

    FIRE ALARM AUDIO SPEAKER

    FIRE ALARM AUDIO/VISUAL SPEAKER/STROBE

    DUCT SMOKE DETECTOR SIDE OF DUCT

    MAGNETIC DOOR HOLDERDOOR INSTALLER

    COORDINATE WITH

    FIRE ALARM MANUAL STATION

    TAMPER SWITCH

    WATER FLOW INDICATOR

    CONTROL MODULE

    MONITOR MODULE

    FAN SHUTDOWN RELAY

    WATER FLOOD INDICATOR

    BEAM DETECTOR - RECEIVER

    ON FIRE RISER

    AT VALVE

    TOP AT 72"

    SMOKE DETECTOR

    HEAT DETECTOR CEILING

    CEILING

    +48"

    AT DEVICE(S) TO BECONTROLLED

    AT DEVICE(S) TO

    MONITOR

    AT FAN CONTROL

    PANEL

    COORDINATE WITH DOOR INSTALLER; SUBSCRIPT

    'F' INDICATES TO MOUNT AT FLOOR LEVEL

    FLOOR

    FIRE PROTECTION SPRINKLER RISER BELL +90"

    SUBSCRIPT 'WP' INDICATES THAT AWEATHER PROOF BACK BOX IS REQ.

    SUBSCRIPT 'C' INDICATESCEILING MOUNTING.

    NUMERIC SUBSCRIPT INDICATES CANDELLARATING OF STROBE (I.E. - 15, 75, 110)

    FURNISHED BY FIRE PROTECTION CONTRACTORAND INSTALLED AND CONNECTED BY DIV. 26

    4" BELOW CEILING TOTOP OF DETECTOR

    4" BELOW CEILING TOTOP OF DETECTOR

    INDOOR - 96" FROM FINISH FLOOR TO TOP

    OF DEVICE.OUTDOOR - 120" FROM FINISHED GRADE TO

    TOP OF DEVICE

    DESCRIPTIONSYMBOL MOUNTING REMARKS

    END OF LINE DEVICEPER MANUFACTURER

    RECOMMENDATIONS

    FFIRE FIGHTERS TELEPHONE JACK +48"

    EOL

    S

    H

    WF

    D

    R

    I

    Z

    F

    W

    T

    FSD

    T

    D

    R

    FIRE ALARM CONTROL PANELFACP

    CEILINGCARBON MONOXIDE DETECTORCO

    ELECTRIC MOTOR

    MANUAL STARTER WITH THERMAL OVERLOAD(S)

    GEAR AND CONTROL SYMBOLS

    AT EQUIPMENT

    +60"

    NON-FUSED DISCONNECT SWITCH +60"

    FUSED DISCONNECT SWITCH

    CIRCUIT BREAKER AND ENCLOSURE +60"

    MAGNETIC STARTER +60"

    COMBINATION MAGNETIC STARTER / NON-FUSED DISCONNECT +60"

    COMBINATION MAGNETIC STARTER / FUSED DISCONNECT +60"

    COMB. MAGNETIC STARTER / MOTOR CIRCUIT PROTECTOR (MCP) +60"

    COMB. VARIABLE FREQUENCY DRIVE / MOTOR CIRCUIT PROTECTOR (MCP)FLOOR OR WALL

    AS SPECIFIEDTOP AT +72" IF

    WALL MOUNTED

    LIGHTING AND APPLIANCE PANELBOARD (SURFACE-MOUNTED) TOP AT +72"

    LIGHTING AND APPLIANCE PANELBOARD (FLUSH-MOUNTED)

    20"W X 6"D

    20"W X 6"DTOP AT +72"

    14"W X 3"DTOP AT +72"LOAD CENTER (FLUSH-MOUNTED)

    LOAD CENTER (SURFACE-MOUNTED) TOP AT +72" 14"W X 3"D

    POWER DISTRIBUTION PANELBOARD WALL

    THESE SYMBOLS ARE

    SWITCHBOARD FLOOR

    GENERAL IN NATURE ANDMAY VARY IN SIZE AND

    SHAPE TO SUIT APPLICATION.CROSS HATCHING INDICATES

    "MAIN PANELBOARD ORSWITCHBOARD"

    METER BASE TOP AT +72"

    NAME IS INDICATED INSEMI-QUOTES (I.E. 'L2A', 'MDP')

    OPEN - STOP - CLOSE SWITCH +60"

    HVAC THERMOSTAT +60"

    HAND - OFF - AUTO SWITCH +60"

    23PROVIDED BY DIVISION

    FURNISHED BY ANOTHERFURNISH SWITCH UNLESS

    DIVISION. INSTALL ANDCONNECT COMPLETE. REFERTO RELATED SPECIFICATION

    SECTIONS.

    DESCRIPTIONSYMBOL MOUNTING REMARKS

    GROUND FAULT PROTECTION

    VFD

    F

    T

    GF

    T

    ELECTRICAL SYMBOL SCHEDULE GENERAL NOTES

    1.

    2.

    3.

    4.

    MOUNT ALL OUTLETS, DEVICES, AND EQUIPMENT AT HEIGHTS INDICATED BELOW, UNLESS NOTED OTHERWISE ON THE

    DRAWINGS. UNLESS NOTED OTHERWISE, HEIGHTS ARE GIVEN FROM FINISHED FLOOR TO CENTER OF OUTLET BOX.

    WHERE OUTLETS, DEVICES, AND EQUIPMENT ARE NOTED BY SUBSCRIPTS, REFER TO ABBREVIATION SCHEDULE FOR

    DEFINED REQUIREMENTS.

    WHERE OUTLETS, DEVICES AND EQUIPMENT ARE NOTED BY THE SUBSCRIPT 'A', MOUNT AT 4" ABOVE COUNTER. IF

    COUNTER HAS A BACK SPLASH, MOUNT AT 4" ABOVE BACK SPLASH. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS

    AND COORDINATE WITH CASEWORK SUPPLIER.

    NOT ALL ELECTRICAL SYMBOLS MAY BE USED.

    KEYED NOTE

    GENERAL SYMBOLS

    DETAIL REFERENCE

    TOP NUMBER INDICATES DETAIL NUMBER; BOTTOMLETTER-NUMBER INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN; WHERE NOT SPECIFICALLY REFERENCED, DETAIL IS GENERAL IN NATURE AND SHALL APPLY WHERE APPLICABLE.

    ELEVATION REFERENCE

    TOP NUMBER INDICATES ELEVATION NUMBER; BOTTOM LETTER-NUMBER INDICATES WHERE ELEVATION IS SHOWN.

    SECTION REFERENCE

    TOP NUMBER INDICATES SECTION NUMBER; BOTTOM LETTER NUMBER INDICATES WHERE SECTION IS SHOWN.

    ARCHITECTURAL ROOM NUMBER

    EQUIPMENT NAME / NUMBERTOP NUMBER ABBREVIATES EQUIPMENT NAME OR TYPE; BOTTOM NUMBER INDICATES EQUIPMENT NUMBER. REFER TO EQUIPMENT SCHEDULE.

    REVISION NUMBERUSED TO DENOTE CHANGES EITHER ISSUED BY ADDENDUM OR DURING CONSTRUCTION AND TO DENOTE RECORD DRAWING CHANGES.

    BREAKLINE USED TO BREAK DRAWINGS.

    DESCRIPTIONSYMBOL REMARKS

    2

    E-2

    1

    AHU

    1

    100

    XX

    1

    E-1

    3

    E-2

    WALL-MOUNTED FIXTURE

    ARM-MOUNTED SINGLE-HEAD LIGHT FIXTURE AND POLEAS SPECIFIED

    LIGHTING SYMBOLS

    POST-TOP SINGLE-HEAD, LIGHT FIXTURE AND POLE

    ARM-MOUNTED DOUBLE-HEAD LIGHT FIXTURE AND POLE

    OR DETAILED

    AS SPECIFIEDOR DETAILED

    AS SPECIFIEDOR DETAILED

    REFER TO ARCHITECTURAL EXTERIORELEVATIONS FOR MOUNTING HEIGHT

    AS SPECIFIEDOR DETAILED

    WALL-MOUNTED LINEAR FLUORESCENT LIGHT FIXTURE OR DETAILEDAS SPECIFIED

    FLUORESCENT LINEAR WALL WASHERAS SPECIFIEDOR DETAILED

    RECESSED DOWN LIGHT

    RECESSED WALL-WASHER OR DIRECTIONAL DOWNLIGHT

    AS SPECIFIEDOR DETAILED

    AS SPECIFIEDOR DETAILED

    AS SPECIFIEDOR DETAILEDSURFACE OR PENDANT-MOUNTED LIGHT FIXTURE

    AS SPECIFIEDOR DETAILEDTRACK OR MONO-POINT LIGHT FIXTURE

    WALL SCONCEAS SPECIFIEDOR DETAILED

    FLUORESCENT EGRESS LIGHT FIXTUREAS SPECIFIEDOR DETAILED

    FLUORESCENT EMERGENCY (NON-EGRESS) LIGHT FIXTUREAS SPECIFIEDOR DETAILED

    THIS IS AN EXAMPLE OF AN EGRESSLIGHT FIXTURE. EGRESS LIGHT FIXTURESARE HALF-SHADED DIAGONALLY.

    THIS IN AN EXAMPLE OF ANEMERGENCY (NON-EGRESS) LIGHT FIXTURE.EMERGENCY FIXTURES ARE FULLY-SHADED.

    CEILING MOUNTED EXIT SIGN CEILING

    WALL-MOUNTED EXIT SIGNWALL ABOVE

    DOOR

    WALL-MOUNTED EXIT SIGN W/ EMERGENCY LIGHT FIXTUREDOOR

    WALL ABOVE

    DARKENED PORTION OF SIGN INDICATES

    FACE(S); ARROW(S) INDICATE CHEVRON

    DIRECTION(S)

    TIME CLOCK

    EMERGENCY LIGHT FIXTURE AS NOTED

    ELECTRIC PHOTOCELL N/A MOUNT ON ROOF FACING NORTH SKY

    LIGHT FIXTURE CALLOUT (LETTER DENOTES FIXTURE TYPE)

    IF SHOWN, ARROW INDICATES

    AIMING DIRECTION

    IF SHOWN, ARROW INDICATES

    AIMING DIRECTION

    DESCRIPTIONSYMBOL MOUNTING REMARKS

    LIGHT FIXTURE SYMBOLS ARE GENERAL IN NATURE AND MAY BE SHOWN ON THE DRAWINGS IN VARIOUS SIZES AND SHAPES. REFER TO THE LIGHT FIXTURE SCHEDULE FOR SPECIFICATION INFORMATION.

    ARROWS INDICATE AIMING DIRECTION.2.

    1.

    RECESSED INDIRECT FLUORESCENT LIGHT FIXTURESAS SPECIFIEDOR DETAILED

    XX

    P

    TC

    LINEAR PENDANT LIGHT FIXTURE CEILING

    SYMBOL

    OCCUPANCY SENSOR LEGEND

    MOUNTING

    CEILING

    REFER TO OCCUPANCY SENSOR SCHEDULE ON SHEET EL701

    REMARKS

    OCCUPANCY SENSOR

    WALLOCCUPANCY SENSOR

    +48"OCCUPANCY SENSOR/SWITCHOSX

    X

    WX

    1. ALL DIGITAL OCCUPANCY SENSORS MUST BE PROGRAMED TO AUTOMATICALLY TURN ON LIGHTING TO 50% LIGHT LEVEL.

    2. TIE DIGITAL OCCUPANCY SENSORS TO THE ENLOSED REGION'S ROOM CONTROLLER WITH CAT5 CABLE.

    3. REFER TO WIRING DIAGRAMS AND SCHEDULES ON SHEET EL701 FOR MORE INFORMATION.

    COMBINATION TELEPHONE/DATA OUTLET

    DATA OUTLET

    TELEPHONE OUTLET

    +18"

    +18"

    +18"

    TELEPHONE / DATA SYMBOLS

    DESCRIPTIONSYMBOL MOUNTING REMARKS

    TELEPHONE TERMINAL BOARD TOP AT 72"

    ACCESS POINT CEILING

    DIMMER SWITCH

    SINGLE-POLE TOGGLE SWITCH WITH PILOT LIGHT

    KEY-OPERATED SINGLE-POLE TOGGLE SWITCH

    FOUR-WAY TOGGLE SWITCH

    THREE-WAY TOGGLE SWITCH

    SINGLE-POLE TOGGLE SWITCH

    +48"

    +48"

    +48"

    +48"

    +48"

    WIRING DEVICE SYMBOLS

    TIMER SWITCH

    +48"

    +48"

    RATE DIMMER SWITCH FOR

    MAXIMUM POSSIBLE WATTAGE

    DOUBLE-POLE TOGGLE SWITCH +48"

    SPLIT-WIRED DUPLEX RECEPTACLE +18"

    SIMPLEX RECEPTACLE +18"

    DUPLEX RECEPTACLE +18"

    FOURPLEX RECEPTACLE +18"

    GROUND FAULT CIRCUIT INTERRUPTER DUPLEX RECEPTACLE +18"

    +18"

    EMERGENCY DUPLEX RECEPTACLE +18"

    EMERGENCY FOURPLEX RECEPTACLE +18"

    FLOOR/CEILING

    SPECIAL PURPOSE OUTLET +18"

    CORD DROP WITH DUPLEX RECEPTACLE +18"

    SINGLE-POLE TOGGLE SWITCH +48" SUBSCRIPT KEYS SWITCH TOFIXTURES CONTROLLED.

    (2) SINGLE-POLE TOGGLE SWITCH DUAL LEVEL SWITCH OUTBOARD LAMPS

    SEPARATELY FROM INBOARD LAMPS.+48"

    LOW VOLTAGE MOMENTARY CONTACT SWITCH +48"

    3-POSITION MOMENTARY CONTACT SWITCH +48" REFER TO DETAILUP-ON; CENTER-NEUTRAL; DOWN-OFF

    3-POSITION MAINTAINED CONTACT SWITCH +48" UP-ON; CENTER-OFF; DOWN-ON

    GROUND FAULT CIRCUIT INTERRUPTER FOURPLEX RECEPTACLE

    POWER / TELEPHONE POLE

    (5-20R)

    MULTI-OUTLET ASSEMBLY 4" ABOVE

    SUBSCRIPT IN PARENTHESIS INDICATES NEMA CONFIGURATION IF SHOWN. REFER TO DRAWINGS AND/OR EQUIPMENT SCHEDULES. CONFIRM EXACT CONFIGURATION WITH OWNER PRIOR TO INSTALLATION.

    REFER TO DETAIL

    125/250V RECEPTACLE +18"DRYER -- NEMA 14-30RRANGE -- NEMA 14-50R

    BACKSPLASH

    DESCRIPTIONSYMBOL MOUNTING REMARKS

    J

    3PN

    3PM

    TIM

    DIM

    P

    K

    4

    3

    2

    a

    LIGHT LEVEL SENSOR CEILING

    LVX REFER TO LOW VOLTAGE SCHEDULE ON SHEET

    EL701

    CLOSED CIRCUIT TELEVISION SYMBOLS

    MATRIX SWITCHER

    CLOSED CIRCUIT TELEVISION CAMERA

    CLOSED CIRCUIT TELEVISION CAMERA (FIXED)

    CLOSED CIRCUIT TELEVISION MONITOR

    CEILING

    CEILING

    CEILING

    DESK

    DESK

    FIBER JUNCTION BOX72" TO TOP OF

    BOX

    CLOSED CIRCUIT TELEVISION CAMERA (PAN/TILT/ZOOM)

    (HIGH SPEED DOME WITH PAN / TILT / ZOOM HEAD)

    DESCRIPTIONSYMBOL MOUNTING REMARKS

    FX

    PTZ

    TV

    MATRIX

    FJ

    GENERAL PROJECT NOTES

    1.

    2.

    3.

    4.

    5.

    6.

    7.

    DIVISION 26000 CONTRACTOR IS RESPONSIBLE FOR READING AND APPLYINGWHAT IS IN THE SPECIFICATIONS TO THIS PROJECT. ANYTHING THAT IS NOT INCLUDED ON THE PROJECT THAT IS CALLED OUT IN THE SPECIFICATION SHALLBE LISTED ON THE SUBSTANTIAL COMPLETION PUNCHLIST. THE CONTRACTOR WILL BE REQUIRED TO REMEDY THESE DEFICIENCIES WITHOUT ADDITIONAL COSTS TO OWNER. THERE WILL BE NO EXCEPTIONS.

    THE CONTRACTOR MAY SCHEDULE A PRE-CONSTRUCTION MEETING. AT THEIR DISCRETION, WITH THE ELECTRICAL ENGINEER TO REVIEW THE DRAWINGS AND SPECIFICATIONS. THE MEETING SHALL BE A MAXIMUM OF ONE HOUR AND SHALL TAKE PLACE AT THE ENGINEER'S OFFICE.

    THE FOLLOWING ITEMS ARE SOME OF THE REQUIREMENTS THAT ARE LISTED IN THE SPECIFICATIONS. THESE ITEMS ARE NOT ALL INCLUSIVE AND THE CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE TO ALL REQUIREMENTS OF THE SPECIFICATIONS:

    A INSULATED THROAT CONNECTORS OR PLASTIC BUSHINGS SHALL BE UTILIZED FOR ALL CONDUIT SIZED USED ON THIS PROJECT.

    B THE CONTRACTOR IS RESPONSIBLE FOR UPSIZING CONDUCTORS FOR VOLTAGE DROP PER THE NEC REGARDLESS OF WHETHER IT IS SHOWN ON THE PLANS OR NOT.

    C THE CONTRACTOR SHALL LABEL ALL ELECTRICAL EQUIPMENT AS IT IS CALLED OUT IN THE SPECIFICATIONS.

    D THE CONTRACTOR SHALL PROVIDE SEISMIC SUPPORT AND BRACING FOR ALL LIGHT FIXTURES AND ELECTRICAL EQUIPMENT AS REQUIRED BY APPLICABLE LOCAL AND NATIONAL CODES.

    THE CONTRACTOR SHALL FOLLOW THE PANELBOARD SCHEDULES AS INDICATED IN THE DRAWINGS. EACH CIRCUIT BREAKER HAS BEEN ASSIGNED TO SPECIFIC AREA OF THE BUILDING. NO DEVIATION WILL BE ALLOWED WITHOUT WRITTEN APPROVAL FROM THE ELECTRICAL ENGINEER.

    AT A MINIMUM THE CONTRACTOR SHALL INSTALL THE WIRE SIZE AS CALLED OUT ON THE ONE-LINE DIAGRAM. HOWEVER, THE CONTRACTOR IS RESPONSIBLE TO ENSURE THE WIRE IS SIZED LARGE ENOUGH TO ALLOW FOR VOLTAGE DROP.

    THE CONTRACTOR SHALL VERIFY ALL MECHANICAL OVERCURRENT DEVICES FOR THE ACTUAL MECHANICAL EQUIPMENT SUPPLIED ON THE JOB, PRIOR TORELEASE OF ANY ELECTRICAL DISTRIBUTION EQUIPMENT. CONTACT THEELECTRICAL ENGINEER WITH ANY DISCREPANCIES.

    THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING THE BID, AND SHALL EXAMINE ALL PHYSICAL CONDITIONS WHICH MAY BE MATERIAL TO THE PERFORMANCE OF HIS WORK. NO ADDITIONAL PAYMENTS WILL BE ALLOWED TO THE CONTRACTOR AS A RESULT OF EXTRA WORK MADE NECESSARY BY HIS FAILURE TO DO SO. ANY CASE OF DISCREPANCY OR LACK OF CLARITY SHALL BE PROMPTLY IDENTIFIED TO THE OWNER'S REPRESENTATIVE AND THE ENGINEERFOR CLARIFICATION.

    AUDIO/VISUAL SYSTEM SYMBOLS

    DESCRIPTIONSYMBOL MOUNTING REMARKS

    PROJECTOR SCREEN - SURFACE MOUNTED SURFACESUBSCRIPT INDICATES SCREEN

    DIMENSIONS

    KEY PAD +48"

    TV OUTLET +18"

    KP1

    ACCESS CONTROL SYMBOLS

    PROXIMITY CARD READER / KEYPAD

    MAGNETIC LOCK

    ELECTROMAGNETIC DOOR STRIKE

    REQUEST-TO-EXIT MOTION DETECTOR

    KEYPAD

    MAGNETIC STRIP CARD READER / KEYPAD

    PROXIMITY CARD READER

    MAGNETIC STRIP CARD READER

    MOUNTING REMARKSDESCRIPTIONSYMBOL

    MAGNETIC DOOR CONTACT SWITCH

    CEILING

    DOOR

    DOOR

    DOOR

    +48"

    +48"

    +48"

    +48"

    +48"

    REX

    S

    D

    M

    KP

    PK

    MK

    PR

    MR

    DURESS PUSH-BUTTON

    MOTION DETECTOR

    SECURITY SYMBOLS

    CEILING

    BELOW DESK

    DOOR

    SUBSCRIPT DENOTES DEGREES OFMONITORED AREA

    DESCRIPTIONSYMBOL MOUNTING REMARKS

    D

    MD

    REQUEST FOR EXIT DOORREX

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :40:5

    2 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    DR

    ACE

    EG001

    GENERAL NOTES AND SYMBOLS LIST

    SHEET INDEX

    EG001 GENERAL NOTES AND SYMBOLS LIST

    ES101 SITE PLAN - ELECTRICAL

    ES501 SITE DETAILS

    ES502 SITE DETAILS

    EL101 CEILING PLAN LEVEL 1 - LIGHTING

    EL102 CEILING PLAN MEZZ - LIGHTING

    EL601 LIGHT FIXTURE SCHEDULE

    EL701 WIRING DIAGRAMS

    EP101 FLOOR PLAN LEVEL 1 - POWER

    EP501 POWER DETAILS

    EP502 DOOR SECURITY DETAILS

    EP503 DOOR SECURITY DETAILS

    EP601 EQUIPMENT SCHEDULES

    EP701 POWER ONE-LINE DIAGRAM

    EP702 RISER DIAGRAMS - POWER

    EP703 RISERS AND DETAILS - POWER

    EP801 PANEL SCHEDULES

    EP802 PANEL SCHEDULES

  • KP

    P

    UTILITY COORDINATION REQUIREMENTS:

    THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND VERIFY ALL

    REQUIREMENTS AND LOCATIONS TO EXTEND CONDUITS FOR UTILITY

    USE WITHIN 2 WEEKS OF THE CONTRACT AWARD. THE CONTRACTOR

    SHALL NOT ROUGH-IN ANY CONDUITS UNTIL THE UTILITY

    COORDINATION IS COMPLETE AND ALL LOCATIONS ARE KNOWN. THE

    CONTRACTOR SHALL PROVIDE TO THE ARCHITECT AND ENGINEER A

    WRITTEN, SIGNED STATEMENT, INCLUDING A SKETCH OF LOCATIONS,

    FROM THE UTILITY COMPANY NOTIFYING THEM THAT THEY HAVE

    COORDINATED AND VERIFIED ALL REQUIREMENTS. IF THE

    CONTRACTOR DOES NOT COORDINATE AND VERIFY THE

    REQUIREMENTS WITH THE UTILITIES OR PROVIDE A WRITTEN

    STATEMENT FROM THE UTILITY COMPANY TO THE ARCHITECT AND

    ENGINEER ALL CHANGES DUE TO LACK OF COORDINATION WILL BE

    DONE AT NO ADDITIONAL EXPENSE TO THE OWNER.

    PROVO POWER REPRESENTATIVE;

    CENTURY LINK REPRESENTATIVE;

    RANDY BARNEY801-623-3125

    RYAN WARNER385-312-6532

    GOOGLE FIBER REPRESENTATIVE;

    KENT STEINBACH801-477-5104

    1.

    2.

    3.

    UTILITY REQUIREMENTS:

    BURY CONDUITS PER UTILITY REQUIREMENTS. REFER TO SHEET

    ES501 FOR TRENCHING REQUIREMENTS.

    VERIFY AND COMPLY WITH ALL PROVO POWER, CENTURYLINK

    AND GOOGLE FIBER REQUIREMENTS.

    INCLUDE IN BID ALL LINE EXTENSION FEES, UNDERGROUND

    FEES, AND ALL MISC. FEES CHARGED BY PROVO POWER,

    CENTURYLINK AND GOOGLE FIBER .

    GENERAL NOTES:

    1. PROVIDE ALL REQUIRED BACKFILLING, ETC. FOR ALL CONDUITS. PROVIDE REQUIRED BACKFILL MATERIAL AS DIRECTED BY EACH UTILITY.

    2. COORDINATE ALL LOCATIONS AND ROUTING WORK IN THE FIELD.

    3. ROUTE CONDIUTS A MINIMUM OF 2' BELOW THE BUILDING FLOOR SLAB.

    4. MINIMUM CONDUIT FOR SITE WORK SHALL BE 1".

    5. CONDUIT ROUTING SHOWN IS SCHEMATIC AND FOR CLARIFICATION. COORDINATE LOCATION WITH ALL AFFECTED TRADES.

    6. PROVIDE A MINIMUM OF 12" SEPARATION BETWEEN POWER AND COMMUNICATIONS CONDUITS.

    7. ALL CONDUITS THAT EXTEND THROUGH CONCRETE SHALL BE GALVANIZED RIGID CONDUIT AND WRAPPED WITH TWO (2) LAYERS OF PVC TAPE.

    8. ALL ELBOWS THAT ARE UNDER THE FINISHED GRADE SHALL BE GALVANIZED RIGID CONDUIT AND WRAPPED WITH TWO (2) LAYERS OF PVC TAPE.

    PROVO POWER TRANSFORMER

    'MS'

    ELEC/TELECOMROOM

    S1

    1" CONDUIT2 # 10 AWG1 # 10 AWG GND

    MOTORIZEDGATE

    F10

    F10F10

    F10

    F10

    F10 F10 F10

    F13

    F13

    F13

    F11F11

    F11

    F8

    F8

    F8

    F8

    F9

    F9

    F9

    F9

    ES501

    4

    ES501

    3

    (TYP.)

    (TYP.)

    S9

    ES501

    2

    ES501

    2

    ES501

    2

    ES501

    2

    ES501

    2

    ES501

    2

    ES501

    2

    ES501

    2ES501

    2

    ES501

    2

    ES501

    2

    S4S5

    S2 S3ES501

    7

    S4S5

    S2 S3ES501

    7

    ES501

    1

    ES501

    1

    S2S3ES501

    7

    S8

    S6

    S7

    L- 23(LCP-2)

    L- 23(LCP-2)

    L- 23(LCP-2)

    L- 23(LCP-2)

    L- 23(LCP-2)

    L- 23(LCP-2)

    L- 23(LCP-2)

    L- 23(LCP-2)

    L- 23(LCP-2)

    L- 23(LCP-2)

    L- 23(LCP-2)

    ADD ALT #1

    M-12

    WP

    WP

    S11

    1"C.(3) #6 AWG

    #6 AWG GND

    WP WP

    S11

    WP WP WP WPWP

    WP WPWP

    WP

    WP

    WP

    WP

    WP

    WP

    WP

    WP

    WP

    WP

    WP

    WP

    WP

    WP

    WP WP

    WPWP

    WP

    WP

    WP

    S12

    L- 1,3(LCP-3)

    S13

    (TYP)

    (TYP)

    S14

    ES501

    1

    S14

    S14

    P-4,6

    S15

    F8

    L- 23(LCP-2)

    (2) 1" CONDUITSTO TELECOM ROOM

    PT

    1

    S15

    S4 S5

    'B'

    (4) PROTECTIVE BOLLARDS1' FROM ENCLOSURE CORNERS

    S16

    B-62

    B-64

    B-66

    B-25,27

    WP2527

    WPB-29,31

    2931

    B-17,19

    WP

    WPB-21,23

    17192123

    WP

    WP

    B-9,11

    119

    B-13,15

    15 13

    B-1,3

    B-5,7

    WP

    WP

    13

    57

    B-33,35

    B-37,39

    WP

    3335

    3739

    WP

    B-41,43

    B-45,47

    WP

    WP43

    47 45

    41

    B-49,51

    WP

    B-53,55

    WP

    49515355

    B-57,59

    B-61,63

    WP

    WP

    57596163

    B-2,4

    B-6,8

    WP

    WP

    68

    24

    B-10,12

    WP

    WP

    B-14,16

    1012

    16 14

    B-58,60

    60 58

    WP

    B-54,56

    5654

    WP

    B-50,52

    52 50WP

    B-46,48

    48 46 44 42 3634

    40 38 32 30 28 2624

    22

    20 18

    WP

    B-42,44

    WP

    B-34,36

    WP

    B-38,40

    WP

    B-30,32

    WP

    B-26,28

    WP

    B-22,24

    WP

    B-18,20

    ES501

    5

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :41:0

    0 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    ES101

    SITE PLAN - ELECTRICAL

    KEYED NOTES

    S1 PROVIDE EMERGENCY OFF PUSH BUTTON WITH WATER PROOF PROTECTIVE COVER.TIE TO SHUNT-TRIP BREAKER INDICATED ON SHEET EP801.

    S2 CCTV CAMERA IS PROVIDED BY THE OWNER. ELECTRICAL CONTRACTOR TO PROVIDEALL REQUIRED CABLING FROM DATA RACK TO CAMERA. TERMINATE CABLE ASDIRECTED BY THE OWNER. CONFIRM EXACT MOUNTING HEIGHT WITH THE OWNER.EXTEND CABLE OUTSIDE POLE FOR OWNER CONNECTIONS TO CAMERA.

    S3 EXTEND A 1" CONDUIT WITH A 2-STRAND SINGLE MODE FIBER OPTIC CABLE FROMCAMERA TO MDF. CONFIRM TERMINATION TYPE AND LOCATION IN MDF ROOM WITHTHE OWNER.

    S4 PROVIDE VIBRATION DAMPENER IN LIGHT POLE.

    S5 PROVIDE SEPERATE RACEWAYS IN LIGHT POLE FOR 277V POWER, CAMERA CABLINGOR PROVIDE 600 VOLT RATED CABLING

    S6 PROVIDE (1) 6" CONDUIT PER ALL PROVO POWER REQUIREMENTS. COORDINATEWITH PROVO POWER PRIOR TO ANY ROUGH-IN.

    S7 NEW PROVO POWER SECTIONALIZER. CONFIRM EXACT LOCATION WITH PROVOPOWER PRIOR TO ANY WORK BEING DONE.

    S8 EXTEND (3) 4" CONDUITS TO LOCATION SHOWN. PROVIDE(3) 1" INNERDUCTS IN EACHCONDUIT. (1) CONDUIT FOR CENTURYLINK, (1) CONDUIT FOR GOOGLE FIBER AND (1)CONDUIT FOR OWNER USE. COORDINATE EXACT STUB LOCATIONS WITH UTILITY ANDOWNER.

    S9 NEW APPROXIMATE LOCATIONS OF CENTURYLINK AND GOOGLE FIBER PEDESTALBOXES. COORDINATE WITH UTILITY PROVIDERS FOR EXACT LOCATION PRIOR TOROUGH-IN.

    S11 TIE OUTLETS TO CIRCUIT SHOWN. SIZE WIRES ACCORDINGLY FOR VOLTAGE DROP.REFER TO DETAIL 9/EP501.

    S12 PROVIDE PHOTOCELL 1� BELOW PARAPET WALL.

    S13 PROVIDE UNISTRUT AND SUPPORT AS REQUIRED TO MOUNT DISCONNECT AND EPOPUSH BUTTON NEXT TO PROPANE TANK.

    S14 WIRELESS ACCESS POINT PROVIDED BY OWNER. MOUNT TO POLE. PROVIDE CAT6ATO TIE INTO FIBER CONVERTERS LOCATED ON THE POLE. COORDINATE ALLREQUIREMENTS WITH PROVE SCHOOL DISTRICT.

    S15 OUTLETS SHALL BE SPLIT WIRED WITH EACH SINGLE RECEPTACLE CIRCUITED ASSHOWN.

    S16 REFER TO ONE-LINE DIAGRAM FOR FEEDER SIZE.

    #

    SCALE: 1" = 30'-0"

    SITE PLAN - ELECTRICAL1

  • 6"

    DEPTH

    24" MIN.

    SECTION A-A

    (3) TIES IN TOP 6" OF PIER

    #3 TIES AT 6" O.C.

    (8) #5 VERTICAL BARS

    EXTERIOR SLABOR GRADE

    AA

    BASE PLATE AND ANCHOR BOLTSBY LIGHT POLE MANUFACTURER

    GROUND LUG WITH #8 AWG SOLIDCU TO REBAR IN FOOTING

    2'-0"

    GROUND LUG

    POLEHEIGHT

    FTGDEPTH

    FTGDEPTH

    V ult =115 MPH

    V ult =150 MPH

    8'-0" 4'-0" 4'-0"

    12'-0" 4'-0" 5'-0"

    20'-0" 5'-0" 6'-0"

    30'-0" 6'-0" 7'-0"

    40'-0" 6'-0" 8'-0"

    DESIGN CRITERIA:

    2012 IBC

    SS = 2.0, SOIL SITE CLASS D

    LATERAL SOIL BRG = 100 PSF/FT

    ASSUMED 4.0 FT² AT TOP POLECONCRETE:

    F'c =4000 PSI

    TYPE I/II CEMENT

    GROUT ENTIRE AREA UNDERPLATE PROVIDE A MINIMUMONE WEAP HOLE PER SIDE

    DOUBLE NUT LEVELING SYSTEM

    PVC SCH 40 CONDUITSEE DRAWINGS FOR SIZE

    ANCHOR BOLT

    GRC ELBOW (TYP.)

    HAND RUB FINISHED

    3/4" CHAMFER

    PROVIDE IN-LINE WATERPROOFFUSE HOLDER WITH BREAKAWAY

    RECEPTACLE AND FUSE

    CAP SPARECONDUIT AT EACH

    DEAD END POLE

    20'

    1" FIBER OPTIC CONDUIT.SEE SITE PLAN

    HAND HOLE

    WELDED IN PLACE 3/4"COUPLING BY POLE

    MANUFACTURER, FORRECEPTACLE

    2" CHASE NIPPLE THREADEDINTO COUPLING

    POLE BASE. SEE POLE BASEDETAILS

    BASE COVER. SEE POLEBASE DETAILS

    ATTACHMENT. SEE POLEBASE DETAILS

    1" 277 VOLT POWER CONDUIT

    1" 120 VOLT POWER CONDUIT

    HOFFMAN # A-24H1608SSSTAINLESS STEEL, NEMA 4XENCLOSURE WITH BACK PANEL# A-24P16. CONFIRM SIZE WITHOWNER FURNISHED EQUIPMENTPRIOR TO ORDERING BOX.

    LIGHT POLE . SEE POLEBASE DETAILS AND LIGHT

    FIXTURE SCHEDULE.

    ENCLOSURE SUPPORTSUNISTRUT - P4001 CHANNELS

    U-BOLT SIZED TO FITLIGHT POLE.

    FIBER TO UTP MEDIA CONVERTER FURNISHEDBY PROVO SCHOOL DISTRICT AND INSTALLEDAND CONNECTED BY THE ELECTRICALCONTRACTOR.

    GFI 4-PLEX RECEPTACLFOR MEDIA CONVERTERS

    AND 24VDC CCTV CAMERATRANSFORMERS.

    24VDC TRANSFORMER AND CORDTO CCTV CAMERA ARE FURNISHEDBY PROVO SCHOOL DISTRICT ANDINSTALLED AND CONNECTED BYTHE ELECTRICLA CONTRACTOR.

    ROUTE FIBER, UTP AND 24VDC THROUGHCOUPLING. TYP.

    WELDED IN PLACE 2"COUPLING BY POLE

    MANUFACTURER, FORUTP AND 24VDC CABLE

    CAT 6 UTP AND 24VDCCABLING UP TO CAMERAS.UTP AND 24VDC CABLINGSHALL 600 VOLT RATED ORINSTALLED IN CONDUIT.

    FIBER OPTIC CABLING

    120 VOLT CONDUCTORS

    277 VOLT CONDUCTORSUP TO LIGHT FIXTURE.

    24" MIN.

    SECTION A-A

    (3) TIES IN TOP 6" OF PIER

    #3 TIES AT 6" O.C.

    (8) #5 VERTICAL BARS

    EXTERIOR SLABOR GRADE

    2'-6"

    DEPTH

    AA

    BASE PLATE AND ANCHOR BOLTS

    BY LIGHT POLE MANUFACTURER

    GROUND LUG WITH #8 AWGSOLID CU TO REBAR IN FOOTING

    2'-0"

    GROUND LUGPOLEHEIGHT

    FTGDEPTH

    FTGDEPTH

    V ult =115 MPH

    V ult =150 MPH

    8'-0" 4'-0" 4'-0"

    12'-0" 4'-0" 5'-0"

    20'-0" 5'-0" 6'-0"

    30'-0" 6'-0" 7'-0"

    40'-0" 6'-0" 8'-0"

    DESIGN CRITERIA:

    2012 IBC

    SS = 2.0, SOIL SITE CLASS D

    LATERAL SOIL BRG = 100 PSF/FT

    ASSUMED 4.0 FT² AT TOP POLECONCRETE:

    F'c =4000 PSI

    TYPE I/II CEMENT

    GROUT ENTIRE AREA UNDERPLATE PROVIDE A MINIMUM ONEWEAP HOLE PER SIDEDOUBLE NUT LEVELING SYSTEM

    PVC SCH 40 CONDUITSEE DRAWINGS FOR SIZE

    ANCHOR BOLT

    GRC ELBOW (TYP.)

    CAP SPARECONDUIT AT

    EACHDEAD END POLE

    HAND RUB FINISHED

    3/4" CHAMFER

    PROVIDE IN-LINE WATERPROOFFUSE HOLDER WITH

    BREAKAWAYRECEPTACLE AND FUSE

    20'

    SECTION A-A

    EXTERIOR SLABOR GRADE

    3'-6"

    AA

    ANCHORS PER BOLLARD

    MANUFACTURER

    (3) TIES IN TOP 6"OF PIER

    #3 TIES AT 8" O.C.

    (3) #4 VERTICAL BARS

    10"

    DESIGN ASSUMES:

    200 # POINT LOAD AT TOP OF

    BOLLARD (42" TALL BOLLARD)

    CONCRETE:

    F'c =3000 PSI

    TYPE I/II CEMENT

    PVC SCH 40 CONDUITSEE DRAWINGS FOR SIZE

    NOTE:

    CIVIL ENGINEER TO VERIFY BASE

    DETAIL.

    ELECTRICALHOOKS

    42"

    MIN

    2 GANG STEEL BOX WITH WATER PROOF COVER FOR (2) SIMPLEX OUTLETS. SPOT WELD BOX TO BOLLARD

    2 GANG STEEL BOX WITH GASKETED STEEL COVER PLATE TO BE USED FOR PULLING WIRES AND SPLICING AS REQUIRED. SPOT WELD BOX TO BOLLARD.

    6" SQUARE BOLLARD

    SIMPLEX OUTLETS

    EXTERIOR SLABOR GRADE

    3'-6"

    AA

    ANCHORS PER BOLLARD

    MANUFACTURER

    (3) TIES IN TOP 6"OF PIER

    #3 TIES AT 8" O.C.

    (3) #4 VERTICAL BARS

    10"

    DESIGN ASSUMES:

    200 # POINT LOAD AT TOP OF

    BOLLARD (42" TALL BOLLARD)

    CONCRETE:

    F'c =3000 PSI

    TYPE I/II CEMENT

    PVC SCH 40 CONDUITSEE DRAWINGS FOR SIZE

    NOTE:

    CIVIL ENGINEER TO VERIFY BASE

    DETAIL.

    SECTION A-A

    42"

    MIN

    ELECTRICALHOOK

    2 GANG STEEL BOX WITH WATER PROOF COVER FOR (2) SIMPLEX OUTLETS. SPOT WELD BOX TO BOLLARD

    2 GANG STEEL BOX WITH GASKETED STEEL COVER PLATE TO BE USED FOR PULLING WIRES AND SPLICING AS REQUIRED. SPOT WELD BOX TO BOLLARD.

    6" SQUARE BOLLARD

    SIMPLEX OUTLETS

    HOT DIP GALVANIZEDC CHANNEL UNISTRUT

    NEMA 3RPANELBOARD

    CONCRETE PAD

    90"MAX

    HEIGHT

    2" RMC PIPE

    GRADE

    24"MIN.

    6"

    PVC SCH 40 CONDUITTO MCC IN CIC

    PROCESS ELECTRICAL

    ROOM

    PVC SCH 40 CONDUITTO EQUIPMENT

    48" MIN.

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :41:0

    6 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    DR

    ACE

    ES501

    SITE DETAILS

    SCALE: NTS

    POLE BASE DETAIL1

    SCALE: NTS

    POLE BASE DETAIL FLUSH2

    SCALE: NTS

    BOLTED BUS CHARGER DOUBLE OUTLET BOLLARD BASE DETIAL3

    SCALE: NTS

    BOLTED BUS CHARGER SINGLE OUTLET BOLLARD BASE DETIAL4

    SCALE: NTS

    LIGHT POLE CAMERA JUNCTION BOX DETAIL7

    SCALE: NTS

    EXTERIOR PANELBOARD MOUNTING DETAIL5

  • 5'-0"

    6'-0"

    7'-0"

    4'-0"

    3'-6

    "

    4'-0

    "

    HOLD DOWN CLEAT

    DETAIL 11 1/4" X 2 1/2" STAINLESS STEEL HOLD-DOWN CLEAT - 2 REQ'D.

    3/8" X 1 1/4" STAINLESS STEEL BOLT - 2 REQ'D.

    3/8" STAINLESS STEEL BELLVILLE WASHER - 2 REQ'D.

    -STOCK ITEM 1790023

    -STOCK ITEM 1790024

    -STOCK ITEM 1008977

    -STOCK ITEM 1008975

    3/8" DIA. INSERTS W/

    HOLD DOWN CLEATS

    2 EA. REQ'D.

    (SEE DETAIL 1)

    2.4 - 25kV, 3-PHASE TRANSFORMER PADVAULT WITH ACCESS, STOCK ITEM 79926002.4 - 25kV, 3-PHASE TRANSFORMER PADVAULT WITHOUT ACCESS, STOCK ITEM 79926012.4 - 25kV, 3-PHASE TRANSFORMER PAD, STOCK ITEM 179002135kV, 3-PHASE TRANSFORMER PADVAULT WITH ACCESS, STOCK ITEM 799260235kV, 3-PHASE TRANSFORMER PADVAULT WITHOUT ACCESS, STOCK ITEM 799260335kV, 3-PHASE TRANSFORMER PAD, STOCK ITEM 1008958

    2.38" DIA. TERM-A-DUCTS

    2 EA. REQ'D.

    (1 EA. NEAR WALL

    1 EA. FAR WALL)

    1/2" DIA. GROUNDING INSERTS

    4 EA. REQ'D.

    (2 EA. OUTSIDE WALLS

    2 EA. INSIDE WALLS)

    16" X 60" BLOCKOUT

    5'-8" LONG GALV. "C" CHANNEL

    2 EA. REQ'D.

    (1 EA. NEAR & FAR WALLS)

    7'-0"

    5.57" DIA. TERM-A-DUCTS

    8 EA. REQ'D.

    (4 EA. NEAR WALL

    4 EA. FAR WALL)

    8,081 LBS.

    2'-0" LONG GALV. "C" CHANNEL

    4 EA. REQ'D.

    (1 EA. WALL)

    3.51" DIA. TERM-A-DUCT

    1 EA. REQ'D.

    4.5" DIA. TERM-A-DUCTS

    14 EA. REQ'D.

    (7 EA. NEAR WALL

    7 EA. FAR WALL)

    9'-4"

    GALV. PULL IRON

    4 EA. REQ'D.

    (1 EA. CORNER)

    PCORP #7992600 - SI #1790023

    3,650 LBS.

    12" DIA. HDPE SUMP

    FULL 180° OPEN

    (TYPICAL)

    2.4 - 25kV, 3-PHASE TRANSFORMER PADVAULT WITHOUT ACCESS

    PCORP #7992601 - SI #1790024

    2.4 - 25kV, 3-PHASE TRANSFORMER PAD ONLY (NO BASE)

    PCORP #1790021

    3,090 LBS.

    6"

    4'-6

    "

    6'-10"

    16" X 60" BLOCKOUT

    7'-0"

    1'-0"11"

    NO. 25P GALV. DIAMONDPLATE DOORS W/ LOCKINGBOLTS

    STAINLESS STEEL

    HOLD DOWN CLEAT

    STAINLESS STEEL

    BELLVILLE WASHER

    STAINLESS STEEL

    BOLT

    BASE

    TOP

    OPTIONAL TOPS

    10'

    10'

    WINDOW

    Door

    10'

    20'

    AREA

    NO PAD

    IN THIS

    3'3'

    KEEP THISAREA

    CLEAR10'-0"

    10'-0"

    3'-0"

    3'-0"

    3'-0"

    KEEP

    CLEAR

    THIS AREA

    10'-0"

    SCALE:

    SCALE:

    SCALE:

    TRENCH DETAIL

    TRENCH DETAIL

    TRENCH DETAIL

    MARKER TAPE WITH TRACER WIRE LABELED,

    "CAUTION BURIED ELECTRIC CONDUITS BELOW"

    DIRECTLY OVER POWER CONDUITS 6" MINIMUM

    BELOW GRADE.

    CLEAN BACKFILL CONTAINING NO ROCKS

    LARGER THAN 4" DIA.

    BACKFILL MATERIAL WITHIN 4" TO 6" OF

    CONDUIT SHALL PASS THROUGH A 3/4" SIEVE

    FRAME OR SAND WITHOUT ANY SHARP OR

    FOREIGN OBJECTS.

    ALL CONDUITS SHOWN SHALL BE SCHEDULE 40

    PVC.

    UNDISTURBED EARTH.

    MARKER TAPE WITH TRACER WRITE LABELED,

    "CAUTION BURIED DATA/COMMUNICATION

    CONDUIT BELOW" DIRECTLY OVER DATA/COMM

    CONDUITS.

    TRENCHES SHALL BE A UNIFORM DEPTH FOR

    ENTIRE LENGTH OF TRENCH SO CONDUITS CAN

    SIT FLAT (HORIZONTAL) WITH THE GROUND.

    FINISHED GRADE.

    TRENCHING KEYED NOTES:

    TRENCHING KEYED NOTES:

    PROVIDE 1/4" NYLON ROPES IN ALL CONDUITS.

    HORIZONTAL AND VERTICAL SEPARATION BETWEEN

    CONDUIT SHALL BE MAINTAINED BY INSTALLING HIGH

    IMPACT SPACERS WITH HORIZONTAL INTERVALS OF

    EIGHT FEET.

    ALL MARKER TAPE SHALL CONTAIN #10 TRACER WIRE.

    REFER TO THE ROCKY MOUNTAIN POWER SIX STATE

    ESR FOR ADDITIONAL INFORMATION.

    VERIFY ALL REQUIREMENTS WITH UTILITIES PRIOR TO

    TRENCHING.

    1.

    2.

    3.

    4.

    5.

    T2

    T3

    T5

    T8

    T7

    NONE CENTURYLINK / GOOGLE FIBER

    T4

    NONE PROVO POWER

    T5

    T7

    T8

    T5

    T7

    T8

    T2

    T3

    T4

    T1

    T2

    T3

    T4

    T1

    2

    4(PRIMARY POWER)

    12"MIN.

    NONE PROVO POWER3

    (SECONDARY POWER)

    24"MIN.48"

    MAX.

    30"MIN.48"

    MAX.

    12"MIN.

    12"MIN.

    24"MIN.

    T6

    T1

    T2

    T3

    T4

    T5

    T6

    T7

    T8

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :41:1

    3 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    ES502

    SITE DETAILS

    SCALE: NTS

    PROVO POWER TRANSFORMER PAD VAULT DETAIL1

  • 845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :41:2

    0 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    EL001

    COMCHECK

  • OSa

    OSa

    OS a

    OSa

    OSa

    OS a

    OS

    a

    LV

    2

    LV

    2

    OS

    a

    OSa

    OS

    a

    OSa

    LV1

    OSa

    LV

    1

    OSa

    OSa

    OSa

    aa

    PP PP

    PP

    b

    bb

    b

    LV1

    cc

    c c

    RC

    RC

    3b

    3a

    4b

    4a

    3

    a

    3

    b

    g

    4

    a

    4

    b

    4

    c

    4

    d

    4

    e

    4

    f

    3a

    3b

    3c

    3d

    3e

    3f

    3a

    3b

    3c

    3d

    3e

    3f

    GFEDCBA

    1

    2

    4

    5

    3

    OFFICE81

    OFFICE82

    VEST.95

    CUST.83

    HALL121 STORAGE

    77

    STORAGE94

    DATA/ELEC79

    OFFICE80

    CORRIDOR124

    TRAINING ROOM75

    TRAINING ROOM75

    OIL89

    VEST122

    Wmns96

    HC / Uni97

    Mns98

    Emp. Tlt26

    LOCKER91

    S.92

    Cust.99

    TOOLS90

    OFFICE52

    OPEN SHOP93

    STORAGE/PARTS55

    STORAGE126

    WASH BAY8

    UPHOLSTERY56

    WASH EQUIP /MECH12

    Room123

    AIR11

    TIRES9

    RECEPTION86

    Hall120

    ADD ALT # 1

    F5

    F2

    F5

    F5

    F5

    F5

    F5

    F4

    F4

    F3F3F4F4

    F3

    F3

    F2

    F12

    F12

    F1

    F1

    F1 F1F1

    F1 F1

    F1 F1

    F1

    F1

    F1

    F1

    F1

    F2

    F2

    F2

    F2

    F2

    F1

    F2E

    F3

    F3

    F5

    F5

    F1

    F3

    bb

    b b

    a a

    aa

    a a bb

    AV ZONE

    AV ZONE

    F3

    E E

    E

    E

    L1

    L1

    L- 5L- 5L- 5

    L- 5L- 5 L- 5

    L- 5

    L- 5

    L-5

    L-5

    L- 5

    L- 5 L- 5 L- 5

    L- 5(LCP-1)

    L- 5

    L- 5(LCP-1)

    L- 5 L- 5 L- 5 L- 5

    L- 5

    L- 7 L- 7L- 7

    L- 7

    L- 7

    L- 21

    L- 7

    L- 7

    L- 7 L- 7 L- 7 L- 7 L- 7 L- 7 L- 7 L- 7

    L- 7

    L- 7

    L- 7

    L- 7

    L- 7

    L- 7

    L- 7

    L- 7

    L- 5

    L-5 L-5

    L-7

    L- 5(LCP-1)

    L- 5(LCP-1)

    L- 5(LCP-1)

    L- 5(LCP-1)

    L- 5(LCP-1)

    L- 5(LCP-1)

    L- 5(LCP-1)

    L- 5(LCP-1)

    L- 5L- 5L- 5L- 5

    L- 5

    L- 5

    L- 5(LCP-1)

    L- 5(LCP-1)

    L- 5

    L- 5(LCP-1)

    L- 7L- 7

    L- 7

    F2

    L- 23(LCP-2)

    L- 23(LCP-2)

    L4

    L3

    WP

    WP

    WP

    WP

    WPX1

    WP WP

    XE1

    XE1

    XE1

    X1X1

    X1

    XE1

    L- 5

    L- 7 L- 7 L- 7

    F3

    L- 23(LCP-2)

    b

    b

    b

    f

    1

    EL102

    X1

    GENERAL LIGHTING NOTES:

    1. REFER TO EL701 FOR TYPICAL LIGHTING CONTROL WIRING DIAGRAMS. PROVIDE COMPLETE SYSTEM WITH ALL REQUIRED CONDUIT SYSTEM WITH ALL REQUIRED CONDUIT, WIRING, SWITCHES, SENSORS, POWER PACKS, ETC. AS REQUIRED.

    2. LOCATE POWER PACKS ABOVE ACCESSIBLE CEILING NEAR ROOM ENTRANCES.

    3. CONFIRM ALL LOCATIONS OF LIGHT FIXTURE WITH ARCHITECT PRIOR TO INSTALLATION.

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :41:2

    7 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    EL101

    CEILING PLAN LEVEL 1 - LIGHTING

    SCALE: 1/8" = 1'-0"

    CEILING PLAN LEVEL1 - LIGHTING1

    KEYED NOTES

    L1 PROVIDE CAT 5 CABLE AND TIE TOGETHER ROOM CONTROLLERS IN TRAININGROOMS SO THE LIGHTING CAN BE CONTROLLED TOGETHER WHEN DESIRED.

    L3 TIE SWITCH TO OCCUPANCY SENSOR SHOWN ON SHEET EL102.

    L4 IF ADD ALT # IS NOT ACCEPTED. LOCATE F12 FIXTURE ABOVE DOOR 154.

    #

  • bdd

    d

    PP

    GFEDCBA

    1

    2

    4

    5

    3

    F2EF2F2F2E

    F6 F6 F6

    F6F6

    F6

    F6F6

    F6

    F7

    F7

    F2

    F2E

    g g g g g

    e

    e

    e

    ed

    d

    d

    d

    c

    c

    c

    cb

    b

    b

    b

    a

    a

    a

    a

    f f f f

    b

    b

    b

    b

    b

    c

    c

    c

    c

    c

    d

    d

    d

    d

    d

    e

    e

    e

    e

    e

    L- 9

    L- 9

    L- 9

    L- 9

    L- 9

    L- 9

    L- 9

    L- 11

    L- 11

    L- 11

    L- 11

    L- 11

    L- 11

    L- 11

    L- 13

    L- 13

    L- 13

    L- 13

    L- 13

    L- 13

    L- 13

    L- 21 L- 21 L- 21 L- 21

    L- 15

    L- 15

    L- 15

    L- 15

    L- 15

    L- 15

    L- 15

    L- 17

    L- 17

    L- 17

    L- 17

    L- 17

    L- 17

    L- 17

    a

    a

    a

    a

    a

    L- 19

    L- 19 L- 19

    L- 19

    L- 19L- 19

    L- 19L- 19

    L- 19 L- 19

    L- 19L- 19L- 21L- 21L- 21

    L- 9

    L- 9

    L- 11

    L- 11

    L- 13

    L- 13

    L- 17

    L- 15

    L- 17

    L- 15

    L- 21

    L- 21L- 21

    a

    a

    a

    a

    a

    b

    b

    b

    b

    b

    L2

    L2

    L2 L2 L2 L2

    L2

    L2 L2 L2

    L2

    L2

    L2

    L2

    L2

    L2

    ADD ALT # 1

    g

    L-21

    GENERAL LIGHTING NOTES:

    1. REFER TO EL701 FOR TYPICAL LIGHTING CONTROL WIRING DIAGRAMS. PROVIDE COMPLETE SYSTEM WITH ALL REQUIRED CONDUIT SYSTEM WITH ALL REQUIRED CONDUIT, WIRING, SWITCHES, SENSORS, POWER PACKS, ETC. AS REQUIRED.

    2. LOCATE POWER PACKS ABOVE ACCESSIBLE CEILING NEAR ROOM ENTRANCES.

    3. CONFIRM ALL LOCATIONS OF LIGHT FIXTURE WITH ARCHITECT PRIOR TO INSTALLATION.

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :41:3

    5 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    EL102

    CEILING PLAN MEZZ - LIGHTINGSCALE: 1/8" = 1'-0"

    FLOOR PLAN MEZZ - LIGHTING1

    KEYED NOTES

    L2 TIE CIRCUIT THROUGH SWITCHES SHOWN ON SHEET EL101.

    #

  • 4VT2-LD4-6-DR-UNV-L835-CD1-WL-VT2-CHAIN/SET-U

    INT-4-50-L35-UNV-DIM

    GLEON-AF-05-LED-E1-T4FT-SFBA-FF-208

    (2)GLEON-AF-04-LED-E1-T4W-SCBA-FF-208

    IST-F01-LED-E1-BL4-SCBA

    GLEON-FA-02-LED-E1-T4W-SCBA-600

    REFER TO FLOOR PLANS FORMOUNTING.

    SOV-EM-G-1C-SFBA-XX-UC

    REFER TO FLOOR PLANS FORMOUNTING.

    CCDS-EM-G-1-SCBA-XX

    24-FR-LD4-50-UNV-L835-CD-1-U

    *-SNLED-LD4-50SL-FW-UNV-L835-CD-1-U

    LD6B-15-D010-EU6B-1020-80-35-6LB-M-1-H-HB26

    METALUX 4-WNLED-LD4-40SL-F-UNV-L835-CD-1-U

    LIGHT FIXTURE SCHEDULE

    LIGHT FIXTURE SCHEDULE

    TYPE DESCRIPTION SOURCE LOAD APPROVED MANUFACTURERS CATALOG NUMBER / SERIES COMMENTS / NOTES

    54" PENDANT MOUNTED LINEAR HIGH-BAY LIGHTFIXTURE. IMPACT RESISTANT, CLOSED-CELL GASKET,20-GAUGE STEEL CHANNEL HOUSING. 36" CHAINHANGER KIT. WIDE DISTRIBUTION.

    LED6000 LUMENS0-10V DIMMING3500K

    120V62W

    LITHONIA VAP-6000LM-FST-WD-GZ10-35K-80CRI-VAPCM13-HC36

    H.E. WILLIAMS LIGHTING 96-4-L60/835-HIAFR-DIM-UNV

    METALUX

    SURFACE MOUNTED 4' LINEAR LIGHT FIXTURE.WATER PROOF GASKETED. ONE-PIECE FIBERGLASSHOUSING WITH POURED IN PLACE NEMA 4X GASKET.

    LED6000 LUMENSON/OFF3500 K

    120V45W

    LITHONIA FEM-L48-6000LM-IMAFL-WD-120-GZ10-35K-80CRI-WLFEND2

    NULITE

    EXTERIOR WALL PACK LIGHT FIXTURE. TWO-PIECEDIE-CAST ALUMINUM HOUSING WITH ZINC-INFUSEDTGIC POWDER COAT PARTS. TYPE 3 MEDIUMDISTRIBUTION.

    LED2700 LUMENS10 LEDSAT 700mAON/OFF4000K

    120V27W

    LITHONIA DSXW1-LED-10C-700-40K-T3M-120-BBW

    H.E. WILLIAMS LIGHTING VWPH-L30/740-T3-SCBA-SDGL-DIM-UNV

    EXTERIOR WALL PACK LIGHT FIXTURE. TWO-PIECEDIE-CAST ALUMINUM HOUSING WITH ZINC-INFUSEDTGIC POWDER COAT PARTS. TYPE FORWARD THROWMEDIUM DISTRIBUTION.

    LED2100 LUMENS10 LED'SAT 530mAON/OFF4000K

    120V20W

    LITHONIA DSXW1-LED-10C-530-40K-TFTM-120-BBW

    H.E. WILLIAMS LIGHTING VWMH-L20/740-TFT-SCBA-SDGL-DIM-UNV

    ZERO UPLIGHT NIGHTTIME FRIENDLY POLE LIGHTDIE-CAST ALUMINUM HOUSING WITH INTEGRAL HEATSINK. FORWARD THROW DISTRIBUTION. WITH 25'SQUARE ALUMINUM POLE. POLE MUST BE WIDEENOUGH TO FIT (4) 1" CONDUITS.

    LED29,000 LUMENS80 LED'S AT1000mAON/OFF4000K

    208V282W

    LITHONIA DSX2-LED-80C-1000-40K-TFTM-208-SPA-DF-SFBA REFER TO NOTES 'S4' AND 'S5' ONSHEET ES101.

    CREE

    MCGRAW-EDISON

    ZERO UPLIGHT NIGHTTIME FRIENDLY POLE LIGHTDIE-CAST ALUMINUM HOUSING WITH INTEGRAL HEATSINK. TYPE 4 MEDIUM DISTRIBUTION. (2) HEADSMOUNTED AT 180 DEGREES. WITH SQUARE ALUMINUM25' POLE.

    LED21500 LUMENS80 LED'S AT700mAON/OFF4000K

    208V(2) 188W

    LITHONIA DSX2-LED-80C-700-40K-T4M-208-SPUMBA-OF-SCBA REFER TO NOTES 'S4' AND 'S5' ONSHEET ES101.

    CREE

    MCGRAW-EDISON

    EXTERIOR TRAPAZOIDAL WALL PACK LIGHT FIXTURE.SINGLE PIECE DIE-CAST ALUMINUM HOUSING.

    LED700 LUMENSON/OFF4000K

    120V9W

    LITHONIA WSTM-LED-1A-40K-120-SFBA

    H.E. WILLIAMS LIGHTING VWM-H-L10/740-T3-SCBA-SDGL-DIM-UNV

    MCGRAW-EDISON

    ZERO UPLIGHT NIGHTTIME FRIENDLY POLE LIGHTDIE-CAST ALUMINUM HOUSING WITH INTEGRAL HEATSINK. TYPE 4 MEDIUM DISTRIBUTION. WITH SQUAREALUMINUM POLE.

    LED6573 LUMENS60 LED'S AT530 mAON/OFF

    120V99 WATTS

    LITHONIA DSX1-LED-60C-530-40K-T4M-120-SPA-SCBA

    CREE ARE-EDG-4M-DA-06-E-UL-SCBA-525MA-40K

    MCGRAW-EDISON

    DIE-CAST ALUMINUM EDGE-LIT, LED EXIT SIGN SINGLEFACE. GREEN LETTERS, CLEAR BACKGROUNDBRUSHED ALUMINUM FINISH CEILING/BACKMOUNTING. REFER TO DRAWING FOR ARROWS.PROVIDE WITH NICKEL CADMIUM BATTERY.

    LED LITHONIA LRP 1 GC 120/277 EL N (OR APPROVED EQUIVALENT).

    EVENLITE

    DIE-CAST ALUMINUM, LED EXIT LIGHT SINGLE FACE,GREEN LETTERS WHITE FINISH, REFER TO DRAWINGFOR ARROWS. PROVIDE WITH NICKEL CADMIUMBATTERY.

    LED LITHONIA LE S W 1 G 120/277 EL N (OR APPROVED EQUIVALENT).

    EVENLITE

    LIGHT FIXTURE GENERAL NOTES1. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATIONS OF LIGHT FIXTURES. BRING ALL DISCREPANCIES OF LOCATIONS AND QUANTITIES TO THE ATTENTION OF THE ARCHITECT

    PRIOR TO BIDDING.

    2. CONFIRM MOUNTING HEIGHTS AND LOCATIONS OF ALL LIGHT FIXTURES WITH ARCHITECTURAL ELEVATIONS AND / OR ARCHITECT.

    3. REFER TO THE SPECIFICATIONS FOR OTHER LIGHT FIXTURE REQUIREMENTS.

    4. CONFIRM AVAILABLE MOUNTING DEPTHS OF ALL LIGHT FIXTURES AND COMPARE WITH DEPTHS SHOWN ON SHOP DRAWINGS. BRING ALL POTENTIAL CONFLICT AREAS TO THE ATTENTION OF THE

    ARCHITECT AND ELECTRICAL ENGINEER PRIOR TO RELEASE.

    5. ALL LIGHT FIXTURES ARE TO BE 3500K FOR INTERIOR APPLICATIONS AND AND 4000K FOR EXTERIOR APPLICATIONS, UNLESS OTHERWISE NOTED IN THE FIXTURE DESCRIPTION.

    6. ALL LIGHT FIXTURES ARE TO BE A MINIMUM OF 80 CRI UNLESS OTHERWISE NOTED IN THE FIXTURE DESCRIPTION.

    7. ALL LED SOURCES MUST MEET L80 AT 50,000 HRS MINIMUM UNLESS OTHERWISE NOTED.

    8. CONFIRM ALL MOUNTING REQUIREMENTS WITH ARCHITECT PRIOR TO RELEASE.

    BIDDING REQUIREMENTS1. BID ONLY PRODUCTS THAT ARE SPECIFIED OR APPROVED BY ADDENDUM.

    2. PACKAGING OF LIGHT FIXTURES WITH OTHER SYSTEMS IS NOT ALLOWED AND MUST BE BID SEPARATELY. I.E. LIGHT FIXTURES, THEATRICAL LIGHTING, SPORTS LIGHTING AND ALL LIGHTING CONTROLS.

    3. WHEN ONLY ONE OR TWO PRODUCTS ARE APPROVED FOR BIDDING, THE PRICE FOR THOSE FIXTURE TYPES SHALL BE BROKEN OUT SEPARATELY WHEN SUBMITTING PRICING TO VARIOUS DISTRIBUTORS AND / OR CONTRACTOR.

    4. WHEN A CONTRADICTION EXISTS BETWEEN A SPECIFIC MODEL NUMBER AND THE DESCRIPTION, THE DESCRIPTION SHALL GOVERN.

    LIGHT FIXTURE PRIOR APPROVAL REQUIREMENTS1. PRIOR APPROVAL IS REQUIRED BEFORE BIDDING THIS PROJECT.

    2. PRIOR APPROVALS SHALL BE SUBMITTED TO THE ELECTRICAL ENGINEER'S OFFICE AT LEAST (8) WORKING DAYS BEFORE BID TIME. PRIOR APPROVALS RECEIVED AFTER THIS TIME PERIOD SHALL BE

    REJECTED.

    3. ITEMS THAT ARE SUBMITTED AND HAVE BEEN APPROVED WILL BE LISTED IN THE ADDENDUM(S). VERBAL APPROVALS WILL NOT BE GIVEN ON ANY ITEM.

    4. IT IS NOT THE RESPONSIBILITY OF THE ELECTRICAL ENGINEER TO NOTIFY THE SUBMITTING PARTY OF ERRORS IN THE SUBMITTAL. NOTIFICATION OF ERRORS BY THE ELECTRICAL ENGINEER PRIOR TO

    ISSUANCE OF THE ADDENDUM(S) MAY NOT BE GIVEN.

    5. PRIOR APPROVALS SHALL CONSIST OF CUT SHEETS DESCRIBING THE PRODUCTS BEING SUBMITTED AS EQUIVALENTS. ALL SPECIFICATION INFORMATION SHALL BE CLEARLY MARKED. PRODUCTS

    WITHOUT PHOTOMETRIC DATA WILL NOT BE APPROVED.

    6. LIGHTING PACKAGES WILL BE REVIEWED FOR GENERAL PROJECT COMPLIANCE ONLY. AN IN-DEPTH REVIEW OF ANY ALTERNATE FIXTURES WILL BE DONE DURING THE SUBMITTAL REVIEW PROCESS.

    ANY FIXTURES THAT ARE NOT TRULY EQUAL, AND / OR DO NOT COMPLY WITH ALL OF THE REQUIREMENTS CONTAINED IN THE CONTRACT DOCUMENTS, WILL NOT BE APPROVED.

    F6

    F7

    F8

    F9

    F10

    F11

    F12

    F13

    XE1

    X1

    TYPE DESCRIPTION SOURCE LOAD APPROVED MANUFACTURERS CATALOG NUMBER / SERIES COMMENTS / NOTES

    DECORATIVE 2'X4' LED LAY-IN TROFFER LIGHTFIXTURE. DIE-FORMED FABRICATED WITH POWDERPAINT WITH CURVED LINEAR PRISMS ACRYLIC LENS.INTEGRAL T-BAR CLIPS ON END PLATES AND LAY-INGRID MOUNTING.

    LED4800 LUMENS0-10V DIMMING3500K

    120V38W

    LITHONIA 2BLT4-48L-ADSM-EZ1-LP835

    H.E. WILLIAMS LIGHTING LT24-L48/835-AF-DIM-UNV

    METALUX

    PENDANT MOUNTED STRIP LIGHT FIXTURE.COLD-ROLLED STEEL BODY WITH FIVE-STAGE IRONPHOSPHATE PRE-TREATMENT PAINT. 36" CHAINHANGER KIT.

    LED5000 LUMENSDIMMING3500K

    120V42W PER 4'

    LITHONIA ZL1D-L**-*000LM-FST-120-35K-HC36

    REFER TO FLOOR PLANS FOR LENGTHOF FIXTURES.

    CREE LS*-50L-35K-10V-AC5-12/3-48-Q14B-JB

    MATALUX

    OPEN REFLECTOR RECESSED LOW PROFILE

    ROUND DOWNLIGHT WITH 6" APERTURE PARABOLIC

    SEMI-SPECULAR REFLECTOR AND FROSTED

    CONVEXED LENS. CONCEALED LED ARRAY

    LOOK.

    LED1500 LUMENS0-10V DIMMING3500K

    120V34.6W

    JUNO L6-15-351-G3-L600P-C-Q-WH

    H.E. WILLIAMS LIGHTING L60-L15/835-CS/LAD-DIM-UNV

    PORTFOLIO

    2' DECORATIVE SQUARE LINEAR WALL MOUNTEDVANITY LIGHT FIXTURE.

    LED1300 LUMENSON/OFF

    120V18W

    LITHONIA FMVCSL-24IN-MVOLT-35K-90CRI-SFBA

    STONE LIGHTING BB415-24-T5LED

    4' LONG NARROW HOUSING SURFACE WRAPAROUNDLIGHT WITH DIE-FORMED CODE-GUAGE STEEL.CURVED PRISMATIC DIFFUSER WITH HIGH-ANGLEBRIGHTNESS CONTROL.

    LED4000 LUMENSON/OFF3500 K

    120V41W

    LITHONIA LBL4-40L-EZ1-LP835

    H.E. WILLIAMS LIGHTING 17-4-L40/835-A-DIM-UNV

    F1

    F2

    F3

    F4

    F5

    JACK CHAIN TO STRUCTUREFOR LATERAL BRACING(TYP. 2X)

    CHAIN SETSTEEL JOIST

    BRANCH CIRCUITING SEE PLAN

    LIGHT FIXTURE

    KEYED NOTES:

    1. MOUNTING HEIGHT. SEE LIGHTING PLANS FOR REQUIREMENTS.

    #1

    a14L-4/LC14-2

    14EL-3

    F# LETTER DESIGNATESFIXTURE TYPE.

    LOWERCASE LETTER DESIGNATESSWITCHING OR CIRCUIT ASSIGNMENT.ASSIGNMENTS, SUCH AS a/b, INDICATEDUAL LEVEL SWITCHING.

    CIRCUIT DESIGNATION (FIRST)/RELAY DESIGNATION (SECOND)

    CIRCUIT DESIGNATION

    F#E LETTER DESIGNATESFIXTURE TYPE.

    SHADING INDICATES EGRESS LIGHTFIXTURE. PROVIDE A 1400 LUMEN,90 MINUTE EMERGENCY BATTERY PACK (BODINE B50, OR APPROVED EQUAL).

    EXIT SIGNS. CONNECTTO UNSWITCHED HOTEMERGENCY LIGHTINGCIRCUIT.

    SUPPORT CLIP ARRANGEMENT DIAGRAMS

    2' x 4' OR 1' x 4'

    LAY-IN TROFFER

    #12 STEEL WIRE

    2' X 2'

    WIRE HANGER AT EACHOF FOUR CORNERSINDEPENDENT OFCEILING SUPPORT SYSTEM

    ANCHOR TO CONCRETE CEILING USING 3/4" PIN & ANGLE CLIP

    LAY-IN TILE

    CEILING

    LAY-IN AND TROFFER LIGHTFIXTURE SUPPORT CLIP(CADDY 515 OR 515A TO SUITAPPLICATION OR EQUIVALENT).PROVIDE 4 CLIPS PER FIXTURE.

    LV

    #1

    WHERE A SINGLE-POLE TOGGLE SWITCH ANDOCCUPANCY SENSOR ARE SHOWN IN THESAME ROOM, THE SWITCH SHALL BE WIREDTO THE OCCUPANCY SENSOR AND FUNCTIONAS A MANUAL OVERIDE.

    C

    LOWERCASE LETTER DESIGNATESSWITCHING OR CIRCUIT ASSIGNMENTWITHIN ROOM.

    INDICATES DUAL LEVEL SWITCHING.INBOARD LAMPS ARE TO BE SWITCHEDSEPARATELY FROM OUTBOARD LAMPS.

    X

    SUBSCRIPT DESIGNATES TYPE OFOCCUPANCY SENSOR. REFER TOOCCUPANCY SENSOR SCHEDULE

    ab

    LOW VOLTAGE OVERRIDE SWITCH. NUMBERREFERS TO SWITCH PROGRAMMING DETAILSLISTED IN PUSHBUTTON SCHEDULE.

    c

    LOWERCASE LETTER DESIGNATESSWITCHING OR ZONEWITHIN ROOM.

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :41:4

    1 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    EL601

    LIGHT FIXTURE SCHEDULE

    SCALE: NTS

    TYPICAL CHAIN HUNG LIGHT FIXTURE DETAIL1SCALE: NTS

    TYPICAL LIGHT FIXTURE CONVENTION2

    SCALE: NTS

    RECESSED GRID LIGHT FIXTURE SUPPORT DETAIL3

    SCALE: NTS

    TYPICAL SWITCHING CONVENTION4

  • NOTE:1.) PROVIDE WATTSTOPPER DLM LIGHTING CONTROL SYSTEM (OR APPROVED EQUIVALENT).2.) DIAGRAM SHOWS TYPICAL DEVICE WIRING. REFER TO FLOOR PLANS FOR EXACT NUMBER AND TYPEOF DEVICES FOR EACH ROOM / SPACE3.) MAX 3 RELAYS PER ROOM CONTROLLER. PROVIDE ADDITIONAL ROOM CONTROLLERS AS REQUIREDFOR ADDITIONAL RELAYS AND TIE TOGETHER WITH CAT5E CABLE. REFER TO FLOOR PLANS.4.) LMLS-500 PHOTOSENSOR IS USED TO MONITOR DAYLIGHT FOR AUTOMATIC 0-10V DIMMING LIGHTADJUSTMENT FOR CORRECT LEVELS.

    *DLM OccupancySensor

    *NOTE:Corner mount Sensor shown with pigtail &supplied coupler. Ceiling mount Sensor hastwo RJ45 ports.

    LMRJ-C8

    Coupler

    RJ45

    (Typical)

    Red

    Yel

    Lighting

    Load

    (c)

    Blu

    Lighting

    Load

    (a)

    Lighting

    Load

    (b)

    Vio

    Gry

    VioGry

    VioGry

    VioGry

    Vio

    Gry V

    ioG

    ry

    Class 2 0-10 VoltControl Wiring

    0-10VDC DimmingDriver required.

    LMRJ Series Pre-TerminatedCables or CAT5e. Free Topology& Splitter Acceptable

    120/230/277

    Hot Blk

    Neutral WhtLMRC-213

    Dimming RoomController

    RJ45 Port(Typical)

    LMDM-101 Dimming Switcheswith LMSW-103 Scene Switch

    All loads auto-onat 50% light levels.

    Neutral

    Red

    daL o

    (Load)

    Single Low Voltage Switch

    LINE BLACK

    NEUTRAL WHITE

    GROUND GREEN

    FOR USE WITH DW-100-24,PW-100-24, AND UW-100-24.

    OPERATION :

    Occupancy Sensor switches

    Lights ON/OFF. When occupied, the

    LS-301 dims the lights as daylight

    increases.

    RED

    BLACK

    RED

    RED

    BLU

    BLU

    RED

    REDYLW

    YLW

    GRY(-)

    VIO(+)

    COMMON

    CONTROL OUTPUT

    RE

    D

    BLK

    BLU

    WHT

    BLKHOT

    NEUTRAL

    WIRING WITH OCCUPANCY SENSOR

    ANY

    CEILING/WALL

    OCCUPANCY

    SENSOR

    LS-301

    ELECTRONIC

    DIMMING

    DRIVER

    (0-10 VDC)

    LAMP

    LAMP

    POWER

    PACK

    VIOLET

    GREY

    +24VDC

    LS-301 WIRING SCHEMATIC

    LOCALOVERRIDESWITCH

    P

    LV#

    TO BUILDING AUTOMATION SYSTEM

    PANEL

    'LCPB'

    PHOTOCELL

    BASEMENT

    LOW VOLTAGE

    OVERRIDE SWITCH(TYPICAL)

    PROVIDE ASTRONOMICAL TIME CLOCKFUNCTIONS AND CPU IN THIS PANEL.REFER TO RELAY PANEL SCHEDULE ANDPUSH BUTTON SCHEDULE FOR ADDITIONALINFORMATION.

    1

    1

    1

    ROOF

    TO OTHER SWITCHES, DAISY CHAIN WIRING CONFIGURATION

    24 RELAY

    2

    LMDC-100

    DW-100

    DT-355

    DT-300

    CATALOG NUMBERTECHNOLOGY

    DUAL TECHa

    c

    b

    SYMBOL

    OCCUPANCY SENSOR SCHEDULE

    WATTSTOPPERVOLTAGE

    DIGITAL

    LINE

    LINE

    LOW

    OSa

    MOUNTING

    CEILING

    WALL

    CEILING

    CEILING

    VACANCY TYPE

    VACANCY

    VACANCY

    VACANCY

    OCCUPANCY

    DUAL TECH

    DUAL TECH

    DUAL TECH 3/EL701

    2/EL701

    1/EL701

    DIAGRAMWIRING

    d DUAL TECH VACANCY LOW CEILING DT-300

    4/EL701

    5/EL701

    BLK

    POWER PACK

    HOT

    RE

    D

    +24VDC

    CONTROL OUTPUT

    COMMON

    BLU

    24VDCOCCUPANCYSENSOR

    NEUTRAL

    LOCALOVERRIDESWITCH

    LIGHTINGLOAD

    +24VDC

    COMMON24VDCOCCUPANCYSENSOR

    CONT. OUTPUT

    (QTY AS INDICATEDON DRAWINGS)

    GENERAL NOTES:

    1. PROVIDE ADDITIONAL POWER PACKS AND OCCUPANCY SENSORS AS REQUIRED.

    NEUTRALLOAD

    SWITCH LOAD HOT

    NEUTRALGROUND

    (OPTIONAL)

    NOTES:1.) PROVIDE WATTSTOPPER DLM LIGHTING CONTROL SYSTEM (OR APPROVED EQUIVALENT). 2.)DIAGRAM SHOWS TYPICAL DEVICE WIRING. REFER TO FLOOR PLANS FOR EXACT NUMBER AND TYPE OF DEVICES FOR EACH ROOM/SPACE.3.) MAX 3 RELAYS PER ROOM CONTROLLER. PROVIDE ADDITIONAL ROOM CONTROLLERS AS REQUIRED FOR ADDITIONAL RELAYS AND TIE TOGETHER WITH CAT5E CABLE. REFER TO FLOOR PLANS. 4.) LMLS-500 PHOTOSENSOR IS USED TO MONITOR DAYLIGHT FOR AUTOMATIC 0-10V DIMMING LIGHT ADJUSTMENT FOR CORRECT LEVELS.

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :44:4

    1 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    EL701

    WIRING DIAGRAMS

    SCALE: NTS

    LIGHTING CONTROL DETAIL - SINGLE LOAD1

    SCALE: NTS

    LINE VOLTAGE OCCUPANCT SENSOR WIRING DIAGRAM2

    LOW VOLTAGE PUSHBUTTON SCHEDULE

    SWITCHID

    WATTSTOPPER CATALOG #

    (ORAPPROVED

    EQUAL)

    WIRINGDETAIL

    REFERENCE

    BUTTONS - AREA/LOAD CONTROLLED

    B-1 B-2 B-3 B-4 B-5 B-6

    1 LVSW-102 6/EL701 LCP-1 ON LCP-1 OFF - - - -

    2 LMSW-105 3/EL701 DIM UP/DOWN 'a' OFF, 'b' 50% 'a' ON/OFF 'b' ON/OFF ALL ON/OFF -

    LIGHTING CONTROL PANEL RCPRELAY

    ELECTRICAL INFO

    LOCATIONSWITCH

    O/S

    CHANNEL

    PANEL CKT LOAD A B C D E F G H

    LCP-1 L 5 754 W CORRIDOR LTG LV1 X

    LCP-2 L 23 942 W EXTERIOR LTG - X

    LCP-3 L 1,3 2068 W BUS PARKING LIGHTING CONTACTOR - X

    LCP-4 0 W SPARE

    LCP-5 0 W SPARE

    LCP-6 0 W SPARE

    LCP-7 0 W SPARE

    LCP-8 0 W SPARE

    SCALE: NTS

    LC-PHOTOSENSOR DIMMING WIRING DIAGRAM3

    CHANNEL LOAD DESCRIPTION PROGRAM REQUIREMENTS

    A

    B

    CDE

    GENERAL NOTES:1. PROGRAM SYSTEM TO MEET REQUIREMENTS OF 2015 IBC & 2015 IECC.2. CONFIRM SWITCHING SCHEME WITH OWNER PRIOR TO PROGRAMMING SYSTEM.3. INCLUDE A FINE TUNING VISIT WITHIN 3 MONTHS OF BUILDING OCCUPANCY AT OWNER'S REQUEST TO

    MAKE MINOR ADJUSTMENTS.4. REFER TO SHEET ES101 FOR PHOTOCELL LOCATION.

    INTERIOR LTG

    EXTERIOR LTG

    TIME CLOCK CONTROLLED. CORRDINATEWITH OWNER FOR SCHEDULE.TIME CLOCK AND PHOTOCELLCONTROLLED CORRDINATE WITH OWNERFOR SCHEDULE AND SETTINGS.

    SCALE: NTS

    WALL OCCUPANCY SENSOR SWITCH WIRING DIAGRAM4

    SCALE: NTS

    ANALOG DAYLIGHT SENSOR WIRING DIAGRAM5

    SCALE: NTS

    RELAY PANEL RISER DIAGRAM6

  • WH

    F

    F

    FF

    T T T T

    F

    PR

    MDMD

    D

    MD

    MD

    MD

    D

    D D D D

    F F

    F

    TT

    TT

    T

    T

    T

    F

    F

    F

    T

    J

    J

    J

    T

    T

    FF

    F

    F F

    F

    F

    F

    AN

    N

    JJ

    J

    ED

    D

    D

    D

    D

    D

    D

    T

    LC

    F

    F

    F

    J

    F

    J

    D

    D

    Z

    Z

    GFEDCBA

    1

    2

    4

    5

    3

    DATA/ELEC79

    OFFICE80

    CUST.83

    OFFICE82

    OFFICE81

    STORAGE77

    RECEPTION86

    OFFICE52

    Emp. Tlt26

    TRAINING ROOM75

    Mns98

    HC / Uni97

    HALL121

    STORAGE94

    Cust.99

    TOOLS90

    Hall120

    Wmns96

    VEST.95

    UPHOLSTERY56

    WASH EQUIP /MECH12

    Room123

    AIR11

    TIRES9

    LOCKER91

    S.92

    STORAGE/PARTS55

    OPEN SHOP93

    OIL89

    STORAGE126

    WASH BAY8

    CORRIDOR124

    VEST122

    A A A A

    AA

    AA

    A

    2

    EP101

    WP

    +42" +42"

    +42"

    +42"

    +42"

    WP

    WP

    ADD ALT # 1

    P2

    P1

    WP

    3

    EP101

    'G'

    G

    1

    D

    1

    A

    1

    G

    2

    P2 P2 P2

    P2

    360º

    A

    WP

    WP

    WP

    WP

    WP

    WP

    P3

    CLGCLG

    CLG

    CLGCLG

    CLG

    WP

    WPWP

    P5

    P4

    P-1

    P-1

    P-1P-1

    P-1

    P-1P-3

    P-3P-3

    P-3

    P-3

    P-3

    P-5

    P-5 P-5

    P-5

    G-1

    P-7

    P-7P-7

    P-7

    P-7

    P-7

    P-17 P-19

    P-19P-20

    P-19

    P-20

    P-21P-21P-21

    P-21P-21

    P-21

    P-23

    P-25

    P-27

    P-14

    P-14

    P-14

    P-14

    P-16

    P-18

    P-20

    P-20

    P-14

    P-5

    P-20

    P-5P-20G-1

    G-1G-1 G-1

    G-3

    G-3G-3

    G-3

    G-3

    G-5

    G-5G-5

    G-5 G-5

    G-7

    G-7

    G-7G-9

    G-9

    G-9

    G-9

    G-11

    G-11

    G-11

    G-13

    G-15

    G-15

    G-15G-15G-17G-17

    G-17

    G-17

    G-19 G-19 G-19G-19

    G-23 G-25 G-27 G-29

    G-32,34,36

    G-2,4,6G-8,10,12

    G-14,16,18

    G-31

    FF

    1

    EF

    1

    EF

    2

    EF

    3

    EF

    4

    EF

    5

    EF

    6

    EF

    7

    EF

    9

    PW

    1

    FF

    2

    M-13,15,17

    M-1,3,5 L-7L-7

    L-7

    L-7

    L-7

    2

    2

    L-7

    M-7,9,11

    L-7

    M-2,4,6

    2

    2

    2

    2

    2

    2

    2

    22

    2

    2

    2

    2

    222

    1

    1

    2

    22

    2

    2

    2

    2

    22

    1

    WP

    WP

    WP

    RTH

    2

    G-11

    M-8

    M-14

    P7

    M-14 P7

    G-38,40

    P6 G-20,22,24 G-26,28,30

    BATTERY CHARGER

    G-33 G-35

    BATTERY CHARGER

    BL

    1

    BL

    1

    DWH

    2

    M-18

    P

    2

    M-20

    P8 P8 P8P8 P8 P8

    WP

    WP

    75cd

    15cd

    75cd

    15cd

    75cd

    75cd

    15cd30cd

    15cd

    15cd

    15cd

    15cd

    15cd

    15cd

    15cd

    15cd 15cd

    15cd

    P-22

    P-24

    EP502

    2

    100

    EP502

    3

    101

    15cd

    EP502

    1

    112

    EP503

    3

    115

    EP503

    2

    142

    EP503

    1

    (TYP)

    EP503

    2

    137

    EP503

    2

    133

    EP503

    2

    128

    P10P11P12

    OHD

    1(TYP)

    LEVEL 10' - 0"

    TOW9' - 0"

    SINK DISPOSAL

    REFRIGERATOR SWITCH

    2' -

    6"

    GFCI GFCI

    P-29

    P-33

    P-31 P-31

    DATA/ELEC79

    'MDP'

    'L'

    'P'

    'LCP'

    P-9 P-11

    P-13

    P-15

    EF

    8

    M-10'M'

    'TC1'

    'TC2'

    L5

    'FACP'

    'NAC'

    P-8

    P-10

    P-12

    GENERAL POWER NOTES:

    1. ALL 120V, 20AMP OUTLETS THAT ARE WITHIN 6' OF ANY SINK SHALL BE GFCI.

    2. THE DISION 26 CONTRACTOR SHALL DETERMINE THE EXACT ROUTING OF ALL CONDUITS IN THE FIELD. THIS PLAN REPRESNTS A SCHEDMATIC REPRESENTATION OF DEVICE LOCATION AND CONDUIT RUNS.

    GFEDCBA

    1

    CU

    1

    RTU

    1

    HRV

    1

    G-21

    G-21 G-21

    M-19,21,23

    M-25,27,29

    M-31,33,35

    M-16

    P7

    AHU

    1

    M-16

    P7

    M-37,39,41

    30cd

    P9

    P9

    WP

    WPG-21

    WP

    WPG-21

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :41:5

    8 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    EP101

    FLOOR PLAN LEVEL 1 - POWER

    SCALE: NTS

    FLOOR PLAN LEVEL 1 - POWER1

    KEYED NOTES

    L5 PROVIDE A MULTI-POLE CONTACTOR (WATTSTOPPER CAT. #C115CO, OR APPROVEDEQUIVALENT). RUN 208V, 2 POLE SITE LIGHTING CIRCUIT THROUGH LIGHTINGCONTRACT. TIE THE 120V COIL FOR THE CONTACTOR THROUGH A RELAY IN THE'LCP' PANEL.

    P1 COORDINATE EXACT HEIGHT AND LOCATION OF OUTLETS FOR TV WITH OWNER.

    P2 COORDINATE WITH GARAGE DOOR INSTALLER AND ARCHITECT FOR MOTORPLACEMENT AND INSTALLATION .

    P4 COORDINATE WITH WHITE BOARD SUPPLIER FOR EXACT LOCATION REQUIRED FORPOWER AND DATA OUTLETS FOR SHORT THROW PROJECTOR.

    P6 TERMINATE CIRCUIT AT J-BOX FOR FUTURE USE.

    P7 PROVIDE POWER INDICATED FOR MECHANICAL DAMPERS. COORDINATE WITHMECHANICAL.

    P8 CIRCUIT EF TO LIGHTING IN ROOM SO EF CAN BE CONTROLLED WITH LIGHTING.REFER TO SHEET EL101.

    P9 PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR DUCT OF THE ROOF TOPUNIT AS SHOWN. TIE TO THE FIRE ALARM CONTROL PANEL AND TO THE ROOT TOPUNIT FOR AUTOMATIC SHUT DOWN.

    P10 ALL RECEPTACLES IN THE SHOP SHALL BE MOUNTED AT 48" AFF. ELECTRICALINSTALLATION FROM FINISHED FLOOR TO +18" AFF SHALL COMPLY WITH CLASS 1 DIV2 PER ALL NEC REQUIREMENTS.

    P11 ALL CONDUIT THAT IS RUN BELOW THE FLOOR SLAB AND UP INTO EQUIPMENT,DEVICES, JUNCTION BOXES, PANELS, ETC SHALL BE CONTINUOUS FROM THE ELBOWBELOW GRADE TO THE EQUIPMENT, DEVICE, JUNCTION BOX, PANEL, ETC. IF ANYCONDUIT COUPLINGS ARE INSTALLED BETWEEN THE FLOOR SLAB AND 48" AFF THECONTRACTOR SHALL CONCRETE INCASE CONDUIT FROM THE FLOOR SLAB TO 48"AFF TO COMPLY WITH HAZARDOUS LOCATION REQUIREMENTS.

    P12 ALL OWNER EQUIPMENT ROUGH-IN REQUIREMENTS SHALL COORDINATE WITH THEOWNER PRIOR TO ANY ROUGH-IN.

    #

    SCALE: 1/4" = 1'-0"

    KITCHEN SECTION2

    SCALE: 1/4" = 1'-0"

    ENLARGED ELECTRICAL ROOM3

    SCALE: NTS

    FLOOR PLAN MEZZANIENE-POWER4

  • 20 A.

    20 A.

    GROUPOF LIGHTFIXTURES

    GROUPOF LIGHTFIXTURES

    LASTGROUP

    OF LIGHTFIXTURES

    TOTAL CIRCUIT LENGTH

    BRANCH PANEL

    BRANCH PANEL

    120 VOLTS 277 VOLTS

    a - USING #12 AWG 90 FT. 180 FT.

    b - USING #10 AWG 150 FT. 300 FT.

    c - USING #8 AWG 250 FT. 450 FT.

    d - USING #6 AWG 380 FT. 700 FT.

    IF PANEL BOARD IS FEED FROM A TRANSFORMER LOCATED IN THE SAME ROOM AS THE PANEL.THE TOTAL LENGTH OF BRANCH CIRCUITS SHALL NOT EXCEED THE FOLLOWING:

    THE ABOVE CIRCUIT LENGTHS ARE BASED ON 4% VOLTAGE DROP AT 16 AMPS LOAD AT THEEND OF THE CIRCUIT. SAME WIRE SIZE SHALL BE USED FOR THE ENTIRE CIRCUIT.

    120 VOLTS 277 VOLTS

    a - USING #12 AWG 75 FT. 180 FT.

    b - USING #10 AWG 125 FT. 260 FT.

    c - USING #8 AWG 205 FT. 420 FT.

    d - USING #6 AWG 325 FT. 660 FT.

    IF PANELBOARD IS FEED FROM A TRANSFORMER LOCATED REMOTELY FROM THE PANEL. THETOTAL LENGTH OF BRANCH CIRCUITS SHALL NOT EXCEED THE FOLLOWING:

    THE ABOVE CIRCUIT LENGTHS ARE BASED ON 3% VOLTAGE DROP AT 16 AMPS LOAD AT THEEND OF THE CIRCUIT. SAME WIRE SIZE SHALL BE USED FOR THE ENTIRE CIRCUIT.

    BRANCH CIRCUIT DEFINITION:CIRCUIT ORIGINATING FROM A 20 AMP CIRCUIT BREAKER IN A BRANCH PANEL AND ENDING ATTHE LAST DUPLEX OUTLET ON THE CIRCUIT OR ENDS AT THE LAST LIGHT FIXTURE.

    GENERAL NOTES:

    FIRE ALARM ANDGENERATOR

    ANNUNCIATOR

    COUNTERTOP ONLY

    COUNTERTOP WITH BACKSPLASH

    FIRE ALARM STROBE

    AND HORN/STROBEDISCONNECT SWITCH (TYP)

    ELECTRICAL PANELBOARD,FACP PANEL AND SECURITY

    PANEL

    48"-72"TO TOP

    80" BOTTOM MIN.

    96" TOP MAX.(MEASUREDFROM LENS)

    18" MIN.

    48" MAX.

    ADA PUSH BUTTONS, LIGHTING

    CONTROLS, FIRE ALARM PULLSTATIONS, AND CARD

    ACCESS

    60" DATA, PHONE, ANDELECTRICAL OUTLETS

    4"

    CASEWORK;BY OTHERS

    LAY-IN OR HARD LID CEILING

    4"

    4"

    FIRE ALARM BEAM DETECTOR

    SMOKE AND HEATDETECTORS

    SURFACE MOUNT CONDUITS ONSTRUCTURE. DO NOT PENDANT

    MOUNTCONDUITS

    DECK STRUCTURALJOIST OR BEAM

    72" MAXTO TOP

    30'-0" MAX

    CEILING MOUNTEDFIRE ALARM STROBEAND HORN/STROBE

    6" MAX (IF CLG ISLESS THAN 80")

    1. MOUNT ALL OUTLETS, DEVICES, AND EQUIPMENT AT HEIGHTS INDICATED BELOW, UNLESS NOTED

    OTHERWISE ON THE DRAWINGS. UNLESS NOTED OTHERWISE, HEIGHTS ARE GIVEN FROM FINISHED

    FLOOR TO CENTER OF OUTLET BOX.

    2. WHERE OUTLETS, DEVICES AND EQUIPMENT ARE NOTED BY THE SUBSCRIPT 'A', MOUNT AT 4" ABOVE

    COUNTER. IF COUNTER HAS A BACK SPLASH, MOUNT AT 4" ABOVE BACK SPLASH. REFER TO

    ARCHITECTURAL INTERIOR ELEVATIONS AND COORDINATE WITH CASEWORK SUPPLIER.

    BEAM CLAMP, HANGER CLAMPOR APPROVED SUPPORT, AS REQUIRED

    BY WEIGHT SUPPORTED

    2 PIECE CHANNELCONDUIT CLAMP

    UNISTRUT CHANNEL - SIZE ASREQUIRED BY WEIGHT SUPPORTED

    ALL THREAD ROD-SIZE AS REQUIRED

    RACEWAY 3/4" TO 6"(TYPICAL)

    STRUCTURAL UNIT-(BEAM, JOIST, SLAB, ETC.)

    NOTE:

    TIE WIRE SHALL NOTBE USED AS A COMPONENTOF ANY RACEWAY HANGERSYSTEM.

    RACEWAY, 3/4" THRU 6"

    CONDUIT HANGER

    STRUCTURAL UNIT

    RACEWAY - 3/4" THRU 1"

    STRUCTURAL UNIT

    BEAM CLAMP OR HANGERCLAMP AS REQUIREDWEIGHT SUPPORTED

    ALL THREAD-SIZEAS REQUIRED

    BEAM CLAMP OR HANGERCLAMP AS REQUIRED BY

    WEIGHT SUPPORTED

    PROVIDE CONDUIT SUPPORTS INACCORDANCE WITH NEC SPACINGREQUIREMENTS FOR TYPE OFRACEWAY REQUIRED.

    STEEL CITYNO. 7501BOX SUPPORT

    AS REQUIRED FOR TYPEOF CONSTRUCTION

    TYPICALOUTLET BOX

    BARSTRAPS

    BARSTRAPS

    TYPICAL WALLOUTLET

    BARSTRAPS

    NOTES:

    TYPICALOUTLET BOX

    TYPICAL FOR WOOD AND METAL STUD ROUGH-IN.

    PLASTER RINGS NOT SHOWN.

    LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCHITECTURAL AND MECHANICAL DRAWINGS, AND

    WITH ALL APPLICABLE SHOP DRAWINGS.

    IN ACCORDANCE WITH UBC 4303 OUTLETS ON OPPOSITE SIDES OF WALLS OR PARTITIONS IN THE SAME

    STUD SPACE MUST BE SEPARATED BY A MINIMUM OF 24" HORIZONTAL DISTANCE.

    1.

    2.

    3.

    4.

    A1-40

    A1-40/IG

    PROVIDE 4"x4"x2-1/8" DEEP JUNCTION BOXWITH SINGLE GANG PLASTER RING ANDEXTEND 3/4" CONDUIT WITH NYLON PULLROPE TO ACCESSIBLE CEILING.TERMINATE CONDUIT IN CEILING SPACEWITH A NYLON BUSHING. CABLE TO BEPROVIDED BY OWNER.

    ISOLATED GROUND CIRCUIT.

    DESIGNATION OF CIRCUIT. WIRECOMPLETE.

    NOTES:

    1. SUPPORT FROM WALL 12 INCHES ABOVE FINISHED GRADE,

    UNLESS NOTED OTHERWISE.

    2. PROVIDE IN EACH NEW ELECTRICAL AND IT ROOM.

    3. EXTEND ALL BUILDING MAIN GROUNDING CONDUCTOR TO

    THE MAIN BUILDING GROUNDING BUS.

    4. SEE SPECIFICATION SECTION 260452 FOR DETAILS.

    1-1/2"

    PLATESIDE VIEW

    1"

    1"

    4"

    2"

    2"

    1/4"

    1"

    2" TYP 8 PLCS

    HOLE SIZE3/8"-16 TAPPED

    STAMPED DESCRIPTION

    XXXXXXXX GROUND SYSTEM

    TO FLOOR/RACK GROUNDING

    CAD-WELD CONNECTION (TYP.)

    DI-ELECTRIC INSULATOR BOTH ENDS TOPANEL GROUND

    COMPRESSIONLUG CONNECTED

    PLATE SIZE4"x1/4"x18" COPPER

    7/16 DIA. HOLEBOTH ENDS

    CP 25WB CAULK ONBOTH SIDES OF WALL

    DAMMING MATERIAL(BACKER ROD, FIBER-GLASS OR

    MINERAL WOOL).

    METAL PIPEOR CONDUIT

    FIRE RATED CONCRETEWALL (SOLID OR BLOCK)

    METALLIC CONDUIT

    1/4" MINIMUM DIAMETER

    BEAD OF 3M FIREBARRIER CP 25 CAULK

    OR MP MOLDABLEPUTTY

    1/4" MINIMUMDIAMETER BEAD OF3M FIRE BARRIER CP25 CAULK OR MPMOLDABLE PUTTY

    STEEL STUD

    GYPSUM BOARD

    SOUND ATTENUATION INSULATION (STC WALLS)

    NOTE:1. TYPICAL DETAILS SHOWING GENERAL FIRE STOPPING PROCEDURE. ACTUAL PROCEDURE DEPENDS UPON ANNULAR SPACE BETWEEN PIPE AND/OR INSULATION AND OPENING. FOLLOW MANUFACTURER'S INSTRUCTIONS.

    2. FIRESTOP TESTED UP TO 4 HOURS IN ACCORDANCE WITH ASTM E 814 (UL 1479) & CAN/ULC S115.

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :42:0

    6 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    EP501

    POWER DETAILS

    SCALE: NTS

    TYPICAL DEVICE ELEVATION DETAIL1SCALE: NTS

    MULTIPLE RACEWAY SUPPORT DETAIL2

    SCALE: NTS

    TYPICAL RACEWAY DETAIL3

    SCALE: NTS

    TYPICAL ROUGH-IN REQUIREMENTS4

    SCALE: NTS

    TYPICAL OUTLET CONVENTION5

    SCALE: NTS

    GROUNDING BUS DETAIL6

    SCALE: NTS

    TYPICAL CONCRETE WALL PENETRATION DETAIL7

    SCALE: NTS

    TYPICAL GYPBOARD WALL PENETRATION DETAIL8

    SCALE: NTS

    BRANCH CIRCUITING DETAIL9

  • ABBREVIATIONS:GENERAL NOTES:

    1. THE DOOR DETAILS SHOWN BELOW ARE GENERAL ROUGH-IN DETAILS AND NOT ALL DEVICES SHOWN MAY BE PRESENT FOR

    EACH DOOR. CONTRACTOR SHALL REFER TO THE DOOR HARDWARE SCHEDULE IN THE ARCHITECTS DRAWINGS AND SPECS

    TO DETERMINE WHAT DEVICES ARE PRESENT FOR EACH DOOR REQUIRING CARD ACCESS DOOR EQUIPMENT.

    2. NOT ALL DOOR STYLE DETAILS SHOWN BELOW MAY BE INCLUDED IN THE PROJECT.

    3. ALL CONDUIT SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS.

    4. THE DOOR ROUGH-IN INFORMATION SHOWN ON THESE DRAWINGS ARE SCHEMATIC IN NATURE AND CANNOT ACCOUNT FOR

    ALL SPECIFIC VENDOR REQUIREMENTS, OR ACTUAL DOOR HARDWARE PROVIDED. COORDINATE SPECIFIC LOCATIONS WITH

    SECURITY CONTRACTOR AND APPROVED DOOR HARDWARE SCHEDULES PRIOR TO ROUGH-IN. CONTRACTOR IS RESPONSIBLE

    FOR A COMPLETE CONDUIT RACEWAY SYSTEM AT THE DOOR AND BACK TO LOCAL ELECTRICAL ROOM.

    5. IF REX IS NOT INCLUDED IN DOOR HANDLE OR EXIT DEVICE, PROVIDE BOX FOR WALL MOUNTED REX DEVICE. VERIFY WITH

    DOOR HARDWARE PRIOR TO ROUGH-IN.

    6. PROVIDE CONDUIT AND DEVICE BACK BOX ROUGH-IN AT ALL CARD READER DOOR LOCATIONS. CONDUIT SHALL BE 3/4"

    UNLESS OTHERWISE NOTED AND ALL BOXES SHALL BE 4 SQUARE WITH A SINGLE GANG MUD RING FOR DEVICES OR JUST A

    SINGLE GANG BOX IF INSTALLED AT THE DOOR FRAME.

    7. A SINGLE FIRE ALARM CONTROL MODULE MAY BE USED TO CONTROL THE POWER TO MULTIPLE DOORS IF COORDINATED

    WITH THE ACCESS CONTROL SYSTEM VENDOR TO WIRE DOORS SEPARATE FROM OTHER DOORS TOGETHER ON THE SAME

    POWER SUPPLY LOOP.

    8. IF NO ACCESSIBLE CEILING SPACE IS NEAR THE CONTROLLED DOOR, ALL CONDUITS ARE TO BE RUN CONTINUOUS TO THE

    DOOR ACCESS CONTROL PANEL UNLESS A LOCATION IS DETERMINED TO BE ACCEPTABLE TO THE ENGINEER PRIOR TO

    INSTALLATION.

    ACCESS CONTROL COORDINATION REQUIREMENTS:

    CODE REFERENCES AND REQUIREMENTS:

    2016 NFPA 101 - LIFE SAFETY CODE

    • 7.2.1.5.6(5) REQUIRES THAT LOSS OF POWER WILL UNLOCK THE ELECTRICALLY CONTROLLED DOOR HARDWARE.• 7.2.1.6.2.(4) REQUIRES THAT ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM UNLOCK ALL DOORS LOCATED IN THE PATH OF EGRESS.2016 NFPA 80 - FIRE DOORS AND OTHER OPENING PROTECTIVES

    • 6.1.3.4 REQUIRES THAT POWER OPERATED FIRE DOORS HAVE A RELEASING DEVICE TO AUTOMATICALLY RELEASE POWER UPON FIRE ALARM.• 6.4.4.3.3 REQUIRES THAT FIRE RATED DOORS BE POSITIVELY LATCHED TO MAINTAIN THE FIRE RATING, ALL ELECTRIC STRIKES USED IN FIRE RATED DOORS MUST BE FAIL SECURE.2012 IBC - INTERNATIONAL BUILDING CODE

    • 1008.1.9.8 REQUIRES ELECTROMAGNETICALLY LOCKED DOORS HAVE A SENSOR RELEASE SWITCH EITHER AUTOMATIC OR BY A READILY ACCESSIBLE WALL MOUNTED PUSHBUTTON TO RELEASE THE LOCK.

    INTEGRATION WITH FIRE ALARM

    ALL MAGNETIC LOCKS SHALL BE UNLOCKED DURING A GENERAL FIRE ALARM. THIS ACTION IS NOT REQUIRED IF SYSTEM IS IN ALARM BY MEANS OF A MANUAL PULL STATION. AUTOMATIC DETECTION DEVICES SUCH AS SMOKE DETECTORS OR SPRINKLER FLOW REQUIRE UNLOCKING AND THE DOOR MUST REMAIN UNLOCKED UNTIL FIRE ALARM SYSTEM

    RESET. CONTRACTOR SHALL INCLUDE ALL FIRE ALARM INTERFACE EQUIPMENT SUCH AS ADDRESSIBLE CONTROL MODULES OR BY CONTACT CLOSURE SIGNALING TO THE ACCESS CONTROL PANELS AS NECESSARY TO MEET THE CODE REQUIREMENTS. ALL DOORS IN STAIRWELLS MUST ALLOW FOR RE-ENTRY.

    ***TO ENSURE A COMPLETE AND OPERATING ACCESS CONTROL SYSTEM AND TO ELIMINATE DELAYS, INSUFFICIENT OR UNNECESSARY WORK BY ALL OF THE ENTITIES INVOLVED, THE FOLLOWING STEPS SHALL BE COMPLETED. THE FAILURE TO DO SO RESULTING IN ADDED COSTS AND LOST TIME WILL BE BORN SOLELY BY THE CONTRACTOR. NO

    ADDITIONAL PAYMENTS WILL BE MADE BY THE OWNER TO COVER WORK DESCRIBED BELOW.***

    DURING THE BIDDING PROCESS:

    1. THE ELECTRICAL CONTRACTOR SHALL REVIEW THE FLOORPLAN DRAWINGS AND DETAILS ON THIS SHEET. THE FLOORPLANS WILL INDICATE WHICH DOORS HAVE ACCESS CONTROL EQUIPMENT REQUIRING ROUGH-IN. DEVICE LOCATIONS REQUIRING JUNCTION BOXES WILL BE SHOWN ON THE FLOORPLANS, BUT ALL CONDUIT AND HARDWARE

    REQUIREMENTS CAN ONLY BE DETERMINED BY REFERRING TO THE SPECIFIC DOOR ROUGH-IN DETAILS AND THE ARCHITECTURAL DOOR HARDWARE SPECIFICATION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER FOR CLARIFICATION.

    2. THE ELECTRICAL CONTRACTOR SHALL REVIEW THE ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE SPECIFICATIONS, AND DEFINED EGRESS PATHS. IDENTIFY ACCESS CONTROLLED DOORS LOCATED IN FIRE RATED WALLS AND IN PATHS OF EGRESS REQUIRING ADDITIONAL CONTROL DEVICES.

    3. THE ELECTRICAL CONTRACTOR SHALL VERIFY WHICH DOORS USING AN ELECTRIFIED EXIT DEVICE WILL REQUIRE 120V AT THE DOOR. THIS IS MANUFACTURER SPECIFIC AND MUST BE CONFIRMED WITH THE GENERAL CONTRACTOR ACCORDING TO WHICH HARDWARE SUPPLIER BEING USED.

    POST-BID, DURING THE SUBMITTAL PROCESS:

    4. DURING THE SUBMITTAL PROCESS, THE ELECTRICAL CONTRACTOR SHALL REVIEW THE APPROVED DOOR HARDWARE SUBMITTAL TO CONFIRM THE THE FINAL HARDWARE SETS PRIOR TO ANY ROUGH-IN. ANY QUESTIONS SHALL BE ISSUED BY FORMAL RFI.

    5. MEET WITH THE ACCESS CONTROL VENDOR TO REVIEW ALL FINAL INTEGRATION AND ROUGH-IN REQUIREMENTS. ONLY AFTER CONFIRMING THE FINAL DOOR HARDWARE AND ACCESS CONTROL SYSTEM REQUIREMENTS SHALL ANY ROUGH-IN WORK BEGINS.

    AFF - ABOVE FINISHED FLOOR

    AP - ACCESS CONTROL PANEL

    CR - CARD READER

    DHS - DOOR HARDWARE SUPPLIER

    DPS - DOOR POSITION SWITCH

    EPT - ELECTRIC POWER TRANSFER

    ES - ELECTRIC STRIKE

    MAG LOCK - MAGNETIC LOCK

    RX - EXIT DEVICE

    PB - DOOR RELEASE PUSH BUTTON

    (MANUAL REX)

    REX - REQUEST TO EXIT

    RFI - REQUEST FOR INFORMATION

    +42" A.F.F.

    1" CONDUIT TO ACCESSIBLE CEILING

    SPACE OR LOCAL COMMUNICATIONS

    ROOM. REFER TO SPECIFICATIONS.

    CARD READER

    (EXTERIOR)

    (IF PRESENT)

    MAG LOCK

    (IF PRESENT)

    DOOR POSITION SWITCH

    (IF PRESENT)

    6"X6"X4" SQ JUNCTION BOX. MOUNT

    JUNCTION BOX ABOVE DOOR IN THE

    CEILING SPACE OF THE SECURE SIDE

    (IF PRESENT)

    (IF PRESENT)120V POWER

    3/4" C.

    3/4" C.

    EPT OR POWER TRANSFER HINGE

    COORDINATE MOUNTING HEIGHT

    WITH DOOR/FRAME SUPPLIER

    Z

    FIRE ALARM CONTROL MODULE(AT FIRE RATED DOORS)

    KEY PAD/

    ELECTRIFIED EXIT DEVICEPOWER SUPPLY

    (IF PRESENT)

    ELECTRIC STRIKE(IF PRESENT)

    (IF PRESENT)

    +42" A.F.F.

    3/4" C.

    ELECTRIFIED EXIT DEVICEPOWER SUPPLY

    ADA ACTIVATIOR

    (INTERIOR)

    6"X6"X4" SQ JUNCTION BOX. MOUNT

    JUNCTION BOX ABOVE DOOR IN THE

    CEILING SPACE OF THE SECURE SIDE

    1" CONDUIT TO ACCESSIBLE CEILING

    SPACE OR LOCAL COMMUNICATIONS

    ROOM. REFER TO SPECIFICATIONS.

    (IF PRESENT)

    DOOR POSITION SWITCH

    (IF PRESENT)

    AUTO OPERATOR

    120V POWER 3/4" C.

    (IF PRESENT)

    (IF PRESENT)

    EPT OR POWER TRANSFER HINGE

    COORDINATE MOUNTING HEIGHT

    WITH MANUFACTURER

    3/4" C.

    CARD READER

    (EXTERIOR)

    (IF PRESENT)

    ADA ACTIVATIOR

    (EXTERIOR)

    (IF PRESENT)

    (IF PRESENT)120V POWER

    Z

    FIRE ALARM CONTROL MODULE(AT FIRE RATED DOORS)

    Z

    FIRE ALARM CONTROL MODULE(AT FIRE RATED DOORS)

    KEY PAD/

    MULLION

    (REMOVABLE)

    ELECTRIC STRIKE (IF PRESENT)

    3/4" C.

    +42" A.F.F.

    3/4" C.

    AUTO OPERATOR

    ADA ACTIVATIOR

    (INTERIOR)

    (IF PRESENT)

    ADA ACTIVATIOR

    (EXTERIOR)

    (IF PRESENT)

    3/4" C.

    120V POWER

    845 South 220 EastOrem, UT 84058

    Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com

    DRAWN BY

    CHECKED BY

    DATE

    PROJECT NO.

    SHEET NUMBER

    SHEET DESCRIPTION

    DATE REVISION/ISSUE

    2/2

    3/2

    01

    7 5

    :42:1

    3 P

    MC

    :\R

    evi

    t 20

    17

    Lo

    ca

    l F

    iles\2

    01

    6-2

    01

    _E

    LE

    C-C

    EN

    TR

    AL_1

    7V

    _Ale

    xEcto

    n.r

    vt

    NE

    W P

    RO

    VO

    TR

    AN

    SP

    OR

    TA

    TIO

    N F

    AC

    ILIT

    YP

    RO

    VO

    SC

    HO

    OL D

    IST

    RIC

    T

    11

    00

    EA

    ST

    13

    20

    SO

    UT

    HP

    RO

    VO

    , U

    T 8

    46

    06

    SA-1610

    02/23/2016

    Author

    Checker

    EP502

    DOOR SECURITY DETAILS

    SCALE: 12" = 1'-0"

    ELECTRIFIED EXIT DEVICE1

    SCALE: 12" = 1'-0"

    DOUBLE DOOR WITH ELECTRIFIED EXIT

    DEVICE AND ADA AUTO OPERATOR2

    SCALE: 12" = 1'-0"

    BRANCH CIRCUITING DETAIL3

  • ABBREVIATIONS:GENERAL NOTES:

    1. THE DOOR DETAILS SHOWN BELOW ARE GENERAL ROUGH-IN DETAILS AND NOT ALL DEVICES SHOWN MAY BE PRESENT FOR

    EACH DOOR.