NOTE: NOT ALL ABBREVIATIONS MAY BE USED.
ABBREVIATION SCHEDULE
ABOVE COUNTERAMP OR AMPSADJACENTABOVE FINISHED FLOOR AUTHORITY HAVING JURISDICTIONALUMINUMCONDUITCIRCUIT BREAKERCIRCUITCONVENIENCE OUTLETSCOPPEREACHELECTRICALEMERGENCYELECTRIC METALLIC TUBING ELECTRIC NONMETALLIC TUBING EQUIPMENTELECTRIC WATER COOLER EXISTINGEXPLOSION PROOFFIRE ALARMFIRE ALARM CONTROL PANEL FULL LOAD AMPSFLEXIBLE METAL CONDUIT FREIGHT ON BOARDGROUND CONDUCTOR HAND-OFF-AUTOHORSE POWERISOLATED GROUND INTERMEDIATE METAL CONDUIT INSULATED
ISOLATEDKILO VOLT AMPERESKILOWATTSLIQUID-TIGHT METAL CONDUIT LIQUID-TIGHT NONMETAL CONDUIT MINIMUM CIRCUIT AMPSMAIN LUGS ONLYNORMALLY CLOSEDNOT IN CONTRACTNIGHT LIGHTNORMALLY OPENON CENTER(S)OVER CURRENT PROTECTIONQUANTITYREMOVEREQUIREMENTSRIGID METAL CONDUITRIGID NONMETALLIC CONDUITREMOVE AND RELOCATESURGE SUPPRESSIONSECURITY CONTROL PANELTAMPER RESISTANTTYPICALTRANSIENT VOLTAGE SURGE SUPPRESSORUNDER FLOORUNDERGROUNDUNLESS NOTED OTHERWISEWITHWEATHER PROOFTRANSFORMER
AA ADJAFFAHJALCCBCKTC.O.'SCU EAELECEMEMTENTEQUIPEWCE, EXEXPFAFACPFLAFMCFOBGNDHOAHPIGIMCINS
ISOKVAKWLFMC LFNCMCAMLON.C.N.I.C.N.L.N.O.O.C.OCPQTYRREQ.RMCRNCRRSSSCPTRTYPTVSSUFUGU.N.O.W/ WPXFMR
1 CIRCUIT, 2 WIRE BRANCH CIRCUIT HOME RUN TO PANEL
BRANCH CIRCUITING SYMBOLS
2 CIRCUIT, 4 WIRE BRANCH CIRCUIT HOME RUN TO PANEL
3 CIRCUIT, 6 WIRE BRANCH CIRCUIT HOME RUN TO PANEL
MULTIPLE WIRE BRANCH CIRCUITING BETWEEN FIXTURES,SWITCHES, DEVICES, ETC.
BRANCH CIRCUITING (U.N.O.) TURNED UP OR TOWARDS OBSERVER.
BRANCH CIRCUITING (U.N.O.) TURNED DOWN OR AWAY FROM OBSEVER.
BRANCH CIRCUITING (U.N.O.) CONTINUATION
CONDUIT STUB-IN
INCOMING SERVICE
CAP AND MARK
JUNCTION BOX MOUNT AS NOTED.SUBSCRIPT 'F' INDICATES TO PROVIDE A FLOOR
BOX WITH BLANK COVERPLATE
DESCRIPTIONSYMBOL REMARKS
ARROWS: NUMBER OF ARROWS INDICATESNUMBER OF CIRCUITS REQUIRED.
SHORT CROSS LINES: NUMBER OF SHORTCROSS LINES INDICATES NUMBER OF PHASE,TRAVELER, AND/OR SWITCHEDCONDUCTORS REQUIRED IF GREATER THAN 1(ONE).
LONG CROSS LINES: NUMBER OF LONGCROSS LINES INDICATES NUMBER OFNEUTRAL CONDUCTORS REQUIRED FORMULTI-WIRE HOME RUNS.
EQUIPMENT GROUND AND ISOLATEDGROUND CONDUCTORS: EQUIPMENTGROUND AND ISOLATED GROUNDCONDUCTORS ARE NOT SHOWN, BUT AREREQUIRED AS NOTED ON THE DRAWINGS ORIN THE SPECIFICATIONS.
J
ELECTRONIC SYSTEM GENERAL SYMBOLS
MOUNTING REMARKSDESCRIPTIONSYMBOL
ELECTRONIC SYSTEM PANELBOARD(SURFACE MOUNT)
ELECTRONIC SYSTEM TERMINAL BOARD TOP AT 72"
ELECTRONIC SYSTEM PANELBOARD(FLUSH MOUNT)
TOP AT 72"
TOP AT 72"NAMEPANEL
NAMEPANEL ELECTRONIC SYSTEMS MAY
INCLUDE BUT ARE NOT SPECIFICALLY LIMITED TO,
TELEPHONE, DATA, TELEVISION, LIGHTING CONTROL, CLOCKS, FIRE
ALARM, ACCESS CONTROL, SECURITY, CCTV, SOUND SYSTEM,
NURSE CALL, OR INTERCOM.
FIRE/SMOKE DAMPER
BEAM DETECTOR - TRANSMITTER
FIRE ALARM SYMBOLS
AUDIO HORN
FIRE ALARM VISUAL STROBE
FIRE ALARM AUDIO/VISUAL HORN/STROBE
FIRE ALARM AUDIO SPEAKER
FIRE ALARM AUDIO/VISUAL SPEAKER/STROBE
DUCT SMOKE DETECTOR SIDE OF DUCT
MAGNETIC DOOR HOLDERDOOR INSTALLER
COORDINATE WITH
FIRE ALARM MANUAL STATION
TAMPER SWITCH
WATER FLOW INDICATOR
CONTROL MODULE
MONITOR MODULE
FAN SHUTDOWN RELAY
WATER FLOOD INDICATOR
BEAM DETECTOR - RECEIVER
ON FIRE RISER
AT VALVE
TOP AT 72"
SMOKE DETECTOR
HEAT DETECTOR CEILING
CEILING
+48"
AT DEVICE(S) TO BECONTROLLED
AT DEVICE(S) TO
MONITOR
AT FAN CONTROL
PANEL
COORDINATE WITH DOOR INSTALLER; SUBSCRIPT
'F' INDICATES TO MOUNT AT FLOOR LEVEL
FLOOR
FIRE PROTECTION SPRINKLER RISER BELL +90"
SUBSCRIPT 'WP' INDICATES THAT AWEATHER PROOF BACK BOX IS REQ.
SUBSCRIPT 'C' INDICATESCEILING MOUNTING.
NUMERIC SUBSCRIPT INDICATES CANDELLARATING OF STROBE (I.E. - 15, 75, 110)
FURNISHED BY FIRE PROTECTION CONTRACTORAND INSTALLED AND CONNECTED BY DIV. 26
4" BELOW CEILING TOTOP OF DETECTOR
4" BELOW CEILING TOTOP OF DETECTOR
INDOOR - 96" FROM FINISH FLOOR TO TOP
OF DEVICE.OUTDOOR - 120" FROM FINISHED GRADE TO
TOP OF DEVICE
DESCRIPTIONSYMBOL MOUNTING REMARKS
END OF LINE DEVICEPER MANUFACTURER
RECOMMENDATIONS
FFIRE FIGHTERS TELEPHONE JACK +48"
EOL
S
H
WF
D
R
I
Z
F
W
T
FSD
T
D
R
FIRE ALARM CONTROL PANELFACP
CEILINGCARBON MONOXIDE DETECTORCO
ELECTRIC MOTOR
MANUAL STARTER WITH THERMAL OVERLOAD(S)
GEAR AND CONTROL SYMBOLS
AT EQUIPMENT
+60"
NON-FUSED DISCONNECT SWITCH +60"
FUSED DISCONNECT SWITCH
CIRCUIT BREAKER AND ENCLOSURE +60"
MAGNETIC STARTER +60"
COMBINATION MAGNETIC STARTER / NON-FUSED DISCONNECT +60"
COMBINATION MAGNETIC STARTER / FUSED DISCONNECT +60"
COMB. MAGNETIC STARTER / MOTOR CIRCUIT PROTECTOR (MCP) +60"
COMB. VARIABLE FREQUENCY DRIVE / MOTOR CIRCUIT PROTECTOR (MCP)FLOOR OR WALL
AS SPECIFIEDTOP AT +72" IF
WALL MOUNTED
LIGHTING AND APPLIANCE PANELBOARD (SURFACE-MOUNTED) TOP AT +72"
LIGHTING AND APPLIANCE PANELBOARD (FLUSH-MOUNTED)
20"W X 6"D
20"W X 6"DTOP AT +72"
14"W X 3"DTOP AT +72"LOAD CENTER (FLUSH-MOUNTED)
LOAD CENTER (SURFACE-MOUNTED) TOP AT +72" 14"W X 3"D
POWER DISTRIBUTION PANELBOARD WALL
THESE SYMBOLS ARE
SWITCHBOARD FLOOR
GENERAL IN NATURE ANDMAY VARY IN SIZE AND
SHAPE TO SUIT APPLICATION.CROSS HATCHING INDICATES
"MAIN PANELBOARD ORSWITCHBOARD"
METER BASE TOP AT +72"
NAME IS INDICATED INSEMI-QUOTES (I.E. 'L2A', 'MDP')
OPEN - STOP - CLOSE SWITCH +60"
HVAC THERMOSTAT +60"
HAND - OFF - AUTO SWITCH +60"
23PROVIDED BY DIVISION
FURNISHED BY ANOTHERFURNISH SWITCH UNLESS
DIVISION. INSTALL ANDCONNECT COMPLETE. REFERTO RELATED SPECIFICATION
SECTIONS.
DESCRIPTIONSYMBOL MOUNTING REMARKS
GROUND FAULT PROTECTION
VFD
F
T
GF
T
ELECTRICAL SYMBOL SCHEDULE GENERAL NOTES
1.
2.
3.
4.
MOUNT ALL OUTLETS, DEVICES, AND EQUIPMENT AT HEIGHTS INDICATED BELOW, UNLESS NOTED OTHERWISE ON THE
DRAWINGS. UNLESS NOTED OTHERWISE, HEIGHTS ARE GIVEN FROM FINISHED FLOOR TO CENTER OF OUTLET BOX.
WHERE OUTLETS, DEVICES, AND EQUIPMENT ARE NOTED BY SUBSCRIPTS, REFER TO ABBREVIATION SCHEDULE FOR
DEFINED REQUIREMENTS.
WHERE OUTLETS, DEVICES AND EQUIPMENT ARE NOTED BY THE SUBSCRIPT 'A', MOUNT AT 4" ABOVE COUNTER. IF
COUNTER HAS A BACK SPLASH, MOUNT AT 4" ABOVE BACK SPLASH. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS
AND COORDINATE WITH CASEWORK SUPPLIER.
NOT ALL ELECTRICAL SYMBOLS MAY BE USED.
KEYED NOTE
GENERAL SYMBOLS
DETAIL REFERENCE
TOP NUMBER INDICATES DETAIL NUMBER; BOTTOMLETTER-NUMBER INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN; WHERE NOT SPECIFICALLY REFERENCED, DETAIL IS GENERAL IN NATURE AND SHALL APPLY WHERE APPLICABLE.
ELEVATION REFERENCE
TOP NUMBER INDICATES ELEVATION NUMBER; BOTTOM LETTER-NUMBER INDICATES WHERE ELEVATION IS SHOWN.
SECTION REFERENCE
TOP NUMBER INDICATES SECTION NUMBER; BOTTOM LETTER NUMBER INDICATES WHERE SECTION IS SHOWN.
ARCHITECTURAL ROOM NUMBER
EQUIPMENT NAME / NUMBERTOP NUMBER ABBREVIATES EQUIPMENT NAME OR TYPE; BOTTOM NUMBER INDICATES EQUIPMENT NUMBER. REFER TO EQUIPMENT SCHEDULE.
REVISION NUMBERUSED TO DENOTE CHANGES EITHER ISSUED BY ADDENDUM OR DURING CONSTRUCTION AND TO DENOTE RECORD DRAWING CHANGES.
BREAKLINE USED TO BREAK DRAWINGS.
DESCRIPTIONSYMBOL REMARKS
2
E-2
1
AHU
1
100
XX
1
E-1
3
E-2
WALL-MOUNTED FIXTURE
ARM-MOUNTED SINGLE-HEAD LIGHT FIXTURE AND POLEAS SPECIFIED
LIGHTING SYMBOLS
POST-TOP SINGLE-HEAD, LIGHT FIXTURE AND POLE
ARM-MOUNTED DOUBLE-HEAD LIGHT FIXTURE AND POLE
OR DETAILED
AS SPECIFIEDOR DETAILED
AS SPECIFIEDOR DETAILED
REFER TO ARCHITECTURAL EXTERIORELEVATIONS FOR MOUNTING HEIGHT
AS SPECIFIEDOR DETAILED
WALL-MOUNTED LINEAR FLUORESCENT LIGHT FIXTURE OR DETAILEDAS SPECIFIED
FLUORESCENT LINEAR WALL WASHERAS SPECIFIEDOR DETAILED
RECESSED DOWN LIGHT
RECESSED WALL-WASHER OR DIRECTIONAL DOWNLIGHT
AS SPECIFIEDOR DETAILED
AS SPECIFIEDOR DETAILED
AS SPECIFIEDOR DETAILEDSURFACE OR PENDANT-MOUNTED LIGHT FIXTURE
AS SPECIFIEDOR DETAILEDTRACK OR MONO-POINT LIGHT FIXTURE
WALL SCONCEAS SPECIFIEDOR DETAILED
FLUORESCENT EGRESS LIGHT FIXTUREAS SPECIFIEDOR DETAILED
FLUORESCENT EMERGENCY (NON-EGRESS) LIGHT FIXTUREAS SPECIFIEDOR DETAILED
THIS IS AN EXAMPLE OF AN EGRESSLIGHT FIXTURE. EGRESS LIGHT FIXTURESARE HALF-SHADED DIAGONALLY.
THIS IN AN EXAMPLE OF ANEMERGENCY (NON-EGRESS) LIGHT FIXTURE.EMERGENCY FIXTURES ARE FULLY-SHADED.
CEILING MOUNTED EXIT SIGN CEILING
WALL-MOUNTED EXIT SIGNWALL ABOVE
DOOR
WALL-MOUNTED EXIT SIGN W/ EMERGENCY LIGHT FIXTUREDOOR
WALL ABOVE
DARKENED PORTION OF SIGN INDICATES
FACE(S); ARROW(S) INDICATE CHEVRON
DIRECTION(S)
TIME CLOCK
EMERGENCY LIGHT FIXTURE AS NOTED
ELECTRIC PHOTOCELL N/A MOUNT ON ROOF FACING NORTH SKY
LIGHT FIXTURE CALLOUT (LETTER DENOTES FIXTURE TYPE)
IF SHOWN, ARROW INDICATES
AIMING DIRECTION
IF SHOWN, ARROW INDICATES
AIMING DIRECTION
DESCRIPTIONSYMBOL MOUNTING REMARKS
LIGHT FIXTURE SYMBOLS ARE GENERAL IN NATURE AND MAY BE SHOWN ON THE DRAWINGS IN VARIOUS SIZES AND SHAPES. REFER TO THE LIGHT FIXTURE SCHEDULE FOR SPECIFICATION INFORMATION.
ARROWS INDICATE AIMING DIRECTION.2.
1.
RECESSED INDIRECT FLUORESCENT LIGHT FIXTURESAS SPECIFIEDOR DETAILED
XX
P
TC
LINEAR PENDANT LIGHT FIXTURE CEILING
SYMBOL
OCCUPANCY SENSOR LEGEND
MOUNTING
CEILING
REFER TO OCCUPANCY SENSOR SCHEDULE ON SHEET EL701
REMARKS
OCCUPANCY SENSOR
WALLOCCUPANCY SENSOR
+48"OCCUPANCY SENSOR/SWITCHOSX
X
WX
1. ALL DIGITAL OCCUPANCY SENSORS MUST BE PROGRAMED TO AUTOMATICALLY TURN ON LIGHTING TO 50% LIGHT LEVEL.
2. TIE DIGITAL OCCUPANCY SENSORS TO THE ENLOSED REGION'S ROOM CONTROLLER WITH CAT5 CABLE.
3. REFER TO WIRING DIAGRAMS AND SCHEDULES ON SHEET EL701 FOR MORE INFORMATION.
COMBINATION TELEPHONE/DATA OUTLET
DATA OUTLET
TELEPHONE OUTLET
+18"
+18"
+18"
TELEPHONE / DATA SYMBOLS
DESCRIPTIONSYMBOL MOUNTING REMARKS
TELEPHONE TERMINAL BOARD TOP AT 72"
ACCESS POINT CEILING
DIMMER SWITCH
SINGLE-POLE TOGGLE SWITCH WITH PILOT LIGHT
KEY-OPERATED SINGLE-POLE TOGGLE SWITCH
FOUR-WAY TOGGLE SWITCH
THREE-WAY TOGGLE SWITCH
SINGLE-POLE TOGGLE SWITCH
+48"
+48"
+48"
+48"
+48"
WIRING DEVICE SYMBOLS
TIMER SWITCH
+48"
+48"
RATE DIMMER SWITCH FOR
MAXIMUM POSSIBLE WATTAGE
DOUBLE-POLE TOGGLE SWITCH +48"
SPLIT-WIRED DUPLEX RECEPTACLE +18"
SIMPLEX RECEPTACLE +18"
DUPLEX RECEPTACLE +18"
FOURPLEX RECEPTACLE +18"
GROUND FAULT CIRCUIT INTERRUPTER DUPLEX RECEPTACLE +18"
+18"
EMERGENCY DUPLEX RECEPTACLE +18"
EMERGENCY FOURPLEX RECEPTACLE +18"
FLOOR/CEILING
SPECIAL PURPOSE OUTLET +18"
CORD DROP WITH DUPLEX RECEPTACLE +18"
SINGLE-POLE TOGGLE SWITCH +48" SUBSCRIPT KEYS SWITCH TOFIXTURES CONTROLLED.
(2) SINGLE-POLE TOGGLE SWITCH DUAL LEVEL SWITCH OUTBOARD LAMPS
SEPARATELY FROM INBOARD LAMPS.+48"
LOW VOLTAGE MOMENTARY CONTACT SWITCH +48"
3-POSITION MOMENTARY CONTACT SWITCH +48" REFER TO DETAILUP-ON; CENTER-NEUTRAL; DOWN-OFF
3-POSITION MAINTAINED CONTACT SWITCH +48" UP-ON; CENTER-OFF; DOWN-ON
GROUND FAULT CIRCUIT INTERRUPTER FOURPLEX RECEPTACLE
POWER / TELEPHONE POLE
(5-20R)
MULTI-OUTLET ASSEMBLY 4" ABOVE
SUBSCRIPT IN PARENTHESIS INDICATES NEMA CONFIGURATION IF SHOWN. REFER TO DRAWINGS AND/OR EQUIPMENT SCHEDULES. CONFIRM EXACT CONFIGURATION WITH OWNER PRIOR TO INSTALLATION.
REFER TO DETAIL
125/250V RECEPTACLE +18"DRYER -- NEMA 14-30RRANGE -- NEMA 14-50R
BACKSPLASH
DESCRIPTIONSYMBOL MOUNTING REMARKS
J
3PN
3PM
TIM
DIM
P
K
4
3
2
a
LIGHT LEVEL SENSOR CEILING
LVX REFER TO LOW VOLTAGE SCHEDULE ON SHEET
EL701
CLOSED CIRCUIT TELEVISION SYMBOLS
MATRIX SWITCHER
CLOSED CIRCUIT TELEVISION CAMERA
CLOSED CIRCUIT TELEVISION CAMERA (FIXED)
CLOSED CIRCUIT TELEVISION MONITOR
CEILING
CEILING
CEILING
DESK
DESK
FIBER JUNCTION BOX72" TO TOP OF
BOX
CLOSED CIRCUIT TELEVISION CAMERA (PAN/TILT/ZOOM)
(HIGH SPEED DOME WITH PAN / TILT / ZOOM HEAD)
DESCRIPTIONSYMBOL MOUNTING REMARKS
FX
PTZ
TV
MATRIX
FJ
GENERAL PROJECT NOTES
1.
2.
3.
4.
5.
6.
7.
DIVISION 26000 CONTRACTOR IS RESPONSIBLE FOR READING AND APPLYINGWHAT IS IN THE SPECIFICATIONS TO THIS PROJECT. ANYTHING THAT IS NOT INCLUDED ON THE PROJECT THAT IS CALLED OUT IN THE SPECIFICATION SHALLBE LISTED ON THE SUBSTANTIAL COMPLETION PUNCHLIST. THE CONTRACTOR WILL BE REQUIRED TO REMEDY THESE DEFICIENCIES WITHOUT ADDITIONAL COSTS TO OWNER. THERE WILL BE NO EXCEPTIONS.
THE CONTRACTOR MAY SCHEDULE A PRE-CONSTRUCTION MEETING. AT THEIR DISCRETION, WITH THE ELECTRICAL ENGINEER TO REVIEW THE DRAWINGS AND SPECIFICATIONS. THE MEETING SHALL BE A MAXIMUM OF ONE HOUR AND SHALL TAKE PLACE AT THE ENGINEER'S OFFICE.
THE FOLLOWING ITEMS ARE SOME OF THE REQUIREMENTS THAT ARE LISTED IN THE SPECIFICATIONS. THESE ITEMS ARE NOT ALL INCLUSIVE AND THE CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE TO ALL REQUIREMENTS OF THE SPECIFICATIONS:
A INSULATED THROAT CONNECTORS OR PLASTIC BUSHINGS SHALL BE UTILIZED FOR ALL CONDUIT SIZED USED ON THIS PROJECT.
B THE CONTRACTOR IS RESPONSIBLE FOR UPSIZING CONDUCTORS FOR VOLTAGE DROP PER THE NEC REGARDLESS OF WHETHER IT IS SHOWN ON THE PLANS OR NOT.
C THE CONTRACTOR SHALL LABEL ALL ELECTRICAL EQUIPMENT AS IT IS CALLED OUT IN THE SPECIFICATIONS.
D THE CONTRACTOR SHALL PROVIDE SEISMIC SUPPORT AND BRACING FOR ALL LIGHT FIXTURES AND ELECTRICAL EQUIPMENT AS REQUIRED BY APPLICABLE LOCAL AND NATIONAL CODES.
THE CONTRACTOR SHALL FOLLOW THE PANELBOARD SCHEDULES AS INDICATED IN THE DRAWINGS. EACH CIRCUIT BREAKER HAS BEEN ASSIGNED TO SPECIFIC AREA OF THE BUILDING. NO DEVIATION WILL BE ALLOWED WITHOUT WRITTEN APPROVAL FROM THE ELECTRICAL ENGINEER.
AT A MINIMUM THE CONTRACTOR SHALL INSTALL THE WIRE SIZE AS CALLED OUT ON THE ONE-LINE DIAGRAM. HOWEVER, THE CONTRACTOR IS RESPONSIBLE TO ENSURE THE WIRE IS SIZED LARGE ENOUGH TO ALLOW FOR VOLTAGE DROP.
THE CONTRACTOR SHALL VERIFY ALL MECHANICAL OVERCURRENT DEVICES FOR THE ACTUAL MECHANICAL EQUIPMENT SUPPLIED ON THE JOB, PRIOR TORELEASE OF ANY ELECTRICAL DISTRIBUTION EQUIPMENT. CONTACT THEELECTRICAL ENGINEER WITH ANY DISCREPANCIES.
THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING THE BID, AND SHALL EXAMINE ALL PHYSICAL CONDITIONS WHICH MAY BE MATERIAL TO THE PERFORMANCE OF HIS WORK. NO ADDITIONAL PAYMENTS WILL BE ALLOWED TO THE CONTRACTOR AS A RESULT OF EXTRA WORK MADE NECESSARY BY HIS FAILURE TO DO SO. ANY CASE OF DISCREPANCY OR LACK OF CLARITY SHALL BE PROMPTLY IDENTIFIED TO THE OWNER'S REPRESENTATIVE AND THE ENGINEERFOR CLARIFICATION.
AUDIO/VISUAL SYSTEM SYMBOLS
DESCRIPTIONSYMBOL MOUNTING REMARKS
PROJECTOR SCREEN - SURFACE MOUNTED SURFACESUBSCRIPT INDICATES SCREEN
DIMENSIONS
KEY PAD +48"
TV OUTLET +18"
KP1
ACCESS CONTROL SYMBOLS
PROXIMITY CARD READER / KEYPAD
MAGNETIC LOCK
ELECTROMAGNETIC DOOR STRIKE
REQUEST-TO-EXIT MOTION DETECTOR
KEYPAD
MAGNETIC STRIP CARD READER / KEYPAD
PROXIMITY CARD READER
MAGNETIC STRIP CARD READER
MOUNTING REMARKSDESCRIPTIONSYMBOL
MAGNETIC DOOR CONTACT SWITCH
CEILING
DOOR
DOOR
DOOR
+48"
+48"
+48"
+48"
+48"
REX
S
D
M
KP
PK
MK
PR
MR
DURESS PUSH-BUTTON
MOTION DETECTOR
SECURITY SYMBOLS
CEILING
BELOW DESK
DOOR
SUBSCRIPT DENOTES DEGREES OFMONITORED AREA
DESCRIPTIONSYMBOL MOUNTING REMARKS
D
MD
REQUEST FOR EXIT DOORREX
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:40:5
2 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
DR
ACE
EG001
GENERAL NOTES AND SYMBOLS LIST
SHEET INDEX
EG001 GENERAL NOTES AND SYMBOLS LIST
ES101 SITE PLAN - ELECTRICAL
ES501 SITE DETAILS
ES502 SITE DETAILS
EL101 CEILING PLAN LEVEL 1 - LIGHTING
EL102 CEILING PLAN MEZZ - LIGHTING
EL601 LIGHT FIXTURE SCHEDULE
EL701 WIRING DIAGRAMS
EP101 FLOOR PLAN LEVEL 1 - POWER
EP501 POWER DETAILS
EP502 DOOR SECURITY DETAILS
EP503 DOOR SECURITY DETAILS
EP601 EQUIPMENT SCHEDULES
EP701 POWER ONE-LINE DIAGRAM
EP702 RISER DIAGRAMS - POWER
EP703 RISERS AND DETAILS - POWER
EP801 PANEL SCHEDULES
EP802 PANEL SCHEDULES
KP
P
UTILITY COORDINATION REQUIREMENTS:
THE ELECTRICAL CONTRACTOR SHALL COORDINATE AND VERIFY ALL
REQUIREMENTS AND LOCATIONS TO EXTEND CONDUITS FOR UTILITY
USE WITHIN 2 WEEKS OF THE CONTRACT AWARD. THE CONTRACTOR
SHALL NOT ROUGH-IN ANY CONDUITS UNTIL THE UTILITY
COORDINATION IS COMPLETE AND ALL LOCATIONS ARE KNOWN. THE
CONTRACTOR SHALL PROVIDE TO THE ARCHITECT AND ENGINEER A
WRITTEN, SIGNED STATEMENT, INCLUDING A SKETCH OF LOCATIONS,
FROM THE UTILITY COMPANY NOTIFYING THEM THAT THEY HAVE
COORDINATED AND VERIFIED ALL REQUIREMENTS. IF THE
CONTRACTOR DOES NOT COORDINATE AND VERIFY THE
REQUIREMENTS WITH THE UTILITIES OR PROVIDE A WRITTEN
STATEMENT FROM THE UTILITY COMPANY TO THE ARCHITECT AND
ENGINEER ALL CHANGES DUE TO LACK OF COORDINATION WILL BE
DONE AT NO ADDITIONAL EXPENSE TO THE OWNER.
PROVO POWER REPRESENTATIVE;
CENTURY LINK REPRESENTATIVE;
RANDY BARNEY801-623-3125
RYAN WARNER385-312-6532
GOOGLE FIBER REPRESENTATIVE;
KENT STEINBACH801-477-5104
1.
2.
3.
UTILITY REQUIREMENTS:
BURY CONDUITS PER UTILITY REQUIREMENTS. REFER TO SHEET
ES501 FOR TRENCHING REQUIREMENTS.
VERIFY AND COMPLY WITH ALL PROVO POWER, CENTURYLINK
AND GOOGLE FIBER REQUIREMENTS.
INCLUDE IN BID ALL LINE EXTENSION FEES, UNDERGROUND
FEES, AND ALL MISC. FEES CHARGED BY PROVO POWER,
CENTURYLINK AND GOOGLE FIBER .
GENERAL NOTES:
1. PROVIDE ALL REQUIRED BACKFILLING, ETC. FOR ALL CONDUITS. PROVIDE REQUIRED BACKFILL MATERIAL AS DIRECTED BY EACH UTILITY.
2. COORDINATE ALL LOCATIONS AND ROUTING WORK IN THE FIELD.
3. ROUTE CONDIUTS A MINIMUM OF 2' BELOW THE BUILDING FLOOR SLAB.
4. MINIMUM CONDUIT FOR SITE WORK SHALL BE 1".
5. CONDUIT ROUTING SHOWN IS SCHEMATIC AND FOR CLARIFICATION. COORDINATE LOCATION WITH ALL AFFECTED TRADES.
6. PROVIDE A MINIMUM OF 12" SEPARATION BETWEEN POWER AND COMMUNICATIONS CONDUITS.
7. ALL CONDUITS THAT EXTEND THROUGH CONCRETE SHALL BE GALVANIZED RIGID CONDUIT AND WRAPPED WITH TWO (2) LAYERS OF PVC TAPE.
8. ALL ELBOWS THAT ARE UNDER THE FINISHED GRADE SHALL BE GALVANIZED RIGID CONDUIT AND WRAPPED WITH TWO (2) LAYERS OF PVC TAPE.
PROVO POWER TRANSFORMER
'MS'
ELEC/TELECOMROOM
S1
1" CONDUIT2 # 10 AWG1 # 10 AWG GND
MOTORIZEDGATE
F10
F10F10
F10
F10
F10 F10 F10
F13
F13
F13
F11F11
F11
F8
F8
F8
F8
F9
F9
F9
F9
ES501
4
ES501
3
(TYP.)
(TYP.)
S9
ES501
2
ES501
2
ES501
2
ES501
2
ES501
2
ES501
2
ES501
2
ES501
2ES501
2
ES501
2
ES501
2
S4S5
S2 S3ES501
7
S4S5
S2 S3ES501
7
ES501
1
ES501
1
S2S3ES501
7
S8
S6
S7
L- 23(LCP-2)
L- 23(LCP-2)
L- 23(LCP-2)
L- 23(LCP-2)
L- 23(LCP-2)
L- 23(LCP-2)
L- 23(LCP-2)
L- 23(LCP-2)
L- 23(LCP-2)
L- 23(LCP-2)
L- 23(LCP-2)
ADD ALT #1
M-12
WP
WP
S11
1"C.(3) #6 AWG
#6 AWG GND
WP WP
S11
WP WP WP WPWP
WP WPWP
WP
WP
WP
WP
WP
WP
WP
WP
WP
WP
WP
WP
WP
WP
WP WP
WPWP
WP
WP
WP
S12
L- 1,3(LCP-3)
S13
(TYP)
(TYP)
S14
ES501
1
S14
S14
P-4,6
S15
F8
L- 23(LCP-2)
(2) 1" CONDUITSTO TELECOM ROOM
PT
1
S15
S4 S5
'B'
(4) PROTECTIVE BOLLARDS1' FROM ENCLOSURE CORNERS
S16
B-62
B-64
B-66
B-25,27
WP2527
WPB-29,31
2931
B-17,19
WP
WPB-21,23
17192123
WP
WP
B-9,11
119
B-13,15
15 13
B-1,3
B-5,7
WP
WP
13
57
B-33,35
B-37,39
WP
3335
3739
WP
B-41,43
B-45,47
WP
WP43
47 45
41
B-49,51
WP
B-53,55
WP
49515355
B-57,59
B-61,63
WP
WP
57596163
B-2,4
B-6,8
WP
WP
68
24
B-10,12
WP
WP
B-14,16
1012
16 14
B-58,60
60 58
WP
B-54,56
5654
WP
B-50,52
52 50WP
B-46,48
48 46 44 42 3634
40 38 32 30 28 2624
22
20 18
WP
B-42,44
WP
B-34,36
WP
B-38,40
WP
B-30,32
WP
B-26,28
WP
B-22,24
WP
B-18,20
ES501
5
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:41:0
0 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
ES101
SITE PLAN - ELECTRICAL
KEYED NOTES
S1 PROVIDE EMERGENCY OFF PUSH BUTTON WITH WATER PROOF PROTECTIVE COVER.TIE TO SHUNT-TRIP BREAKER INDICATED ON SHEET EP801.
S2 CCTV CAMERA IS PROVIDED BY THE OWNER. ELECTRICAL CONTRACTOR TO PROVIDEALL REQUIRED CABLING FROM DATA RACK TO CAMERA. TERMINATE CABLE ASDIRECTED BY THE OWNER. CONFIRM EXACT MOUNTING HEIGHT WITH THE OWNER.EXTEND CABLE OUTSIDE POLE FOR OWNER CONNECTIONS TO CAMERA.
S3 EXTEND A 1" CONDUIT WITH A 2-STRAND SINGLE MODE FIBER OPTIC CABLE FROMCAMERA TO MDF. CONFIRM TERMINATION TYPE AND LOCATION IN MDF ROOM WITHTHE OWNER.
S4 PROVIDE VIBRATION DAMPENER IN LIGHT POLE.
S5 PROVIDE SEPERATE RACEWAYS IN LIGHT POLE FOR 277V POWER, CAMERA CABLINGOR PROVIDE 600 VOLT RATED CABLING
S6 PROVIDE (1) 6" CONDUIT PER ALL PROVO POWER REQUIREMENTS. COORDINATEWITH PROVO POWER PRIOR TO ANY ROUGH-IN.
S7 NEW PROVO POWER SECTIONALIZER. CONFIRM EXACT LOCATION WITH PROVOPOWER PRIOR TO ANY WORK BEING DONE.
S8 EXTEND (3) 4" CONDUITS TO LOCATION SHOWN. PROVIDE(3) 1" INNERDUCTS IN EACHCONDUIT. (1) CONDUIT FOR CENTURYLINK, (1) CONDUIT FOR GOOGLE FIBER AND (1)CONDUIT FOR OWNER USE. COORDINATE EXACT STUB LOCATIONS WITH UTILITY ANDOWNER.
S9 NEW APPROXIMATE LOCATIONS OF CENTURYLINK AND GOOGLE FIBER PEDESTALBOXES. COORDINATE WITH UTILITY PROVIDERS FOR EXACT LOCATION PRIOR TOROUGH-IN.
S11 TIE OUTLETS TO CIRCUIT SHOWN. SIZE WIRES ACCORDINGLY FOR VOLTAGE DROP.REFER TO DETAIL 9/EP501.
S12 PROVIDE PHOTOCELL 1� BELOW PARAPET WALL.
S13 PROVIDE UNISTRUT AND SUPPORT AS REQUIRED TO MOUNT DISCONNECT AND EPOPUSH BUTTON NEXT TO PROPANE TANK.
S14 WIRELESS ACCESS POINT PROVIDED BY OWNER. MOUNT TO POLE. PROVIDE CAT6ATO TIE INTO FIBER CONVERTERS LOCATED ON THE POLE. COORDINATE ALLREQUIREMENTS WITH PROVE SCHOOL DISTRICT.
S15 OUTLETS SHALL BE SPLIT WIRED WITH EACH SINGLE RECEPTACLE CIRCUITED ASSHOWN.
S16 REFER TO ONE-LINE DIAGRAM FOR FEEDER SIZE.
#
SCALE: 1" = 30'-0"
SITE PLAN - ELECTRICAL1
6"
DEPTH
24" MIN.
SECTION A-A
(3) TIES IN TOP 6" OF PIER
#3 TIES AT 6" O.C.
(8) #5 VERTICAL BARS
EXTERIOR SLABOR GRADE
AA
BASE PLATE AND ANCHOR BOLTSBY LIGHT POLE MANUFACTURER
GROUND LUG WITH #8 AWG SOLIDCU TO REBAR IN FOOTING
2'-0"
GROUND LUG
POLEHEIGHT
FTGDEPTH
FTGDEPTH
V ult =115 MPH
V ult =150 MPH
8'-0" 4'-0" 4'-0"
12'-0" 4'-0" 5'-0"
20'-0" 5'-0" 6'-0"
30'-0" 6'-0" 7'-0"
40'-0" 6'-0" 8'-0"
DESIGN CRITERIA:
2012 IBC
SS = 2.0, SOIL SITE CLASS D
LATERAL SOIL BRG = 100 PSF/FT
ASSUMED 4.0 FT² AT TOP POLECONCRETE:
F'c =4000 PSI
TYPE I/II CEMENT
GROUT ENTIRE AREA UNDERPLATE PROVIDE A MINIMUMONE WEAP HOLE PER SIDE
DOUBLE NUT LEVELING SYSTEM
PVC SCH 40 CONDUITSEE DRAWINGS FOR SIZE
ANCHOR BOLT
GRC ELBOW (TYP.)
HAND RUB FINISHED
3/4" CHAMFER
PROVIDE IN-LINE WATERPROOFFUSE HOLDER WITH BREAKAWAY
RECEPTACLE AND FUSE
CAP SPARECONDUIT AT EACH
DEAD END POLE
20'
1" FIBER OPTIC CONDUIT.SEE SITE PLAN
HAND HOLE
WELDED IN PLACE 3/4"COUPLING BY POLE
MANUFACTURER, FORRECEPTACLE
2" CHASE NIPPLE THREADEDINTO COUPLING
POLE BASE. SEE POLE BASEDETAILS
BASE COVER. SEE POLEBASE DETAILS
ATTACHMENT. SEE POLEBASE DETAILS
1" 277 VOLT POWER CONDUIT
1" 120 VOLT POWER CONDUIT
HOFFMAN # A-24H1608SSSTAINLESS STEEL, NEMA 4XENCLOSURE WITH BACK PANEL# A-24P16. CONFIRM SIZE WITHOWNER FURNISHED EQUIPMENTPRIOR TO ORDERING BOX.
LIGHT POLE . SEE POLEBASE DETAILS AND LIGHT
FIXTURE SCHEDULE.
ENCLOSURE SUPPORTSUNISTRUT - P4001 CHANNELS
U-BOLT SIZED TO FITLIGHT POLE.
FIBER TO UTP MEDIA CONVERTER FURNISHEDBY PROVO SCHOOL DISTRICT AND INSTALLEDAND CONNECTED BY THE ELECTRICALCONTRACTOR.
GFI 4-PLEX RECEPTACLFOR MEDIA CONVERTERS
AND 24VDC CCTV CAMERATRANSFORMERS.
24VDC TRANSFORMER AND CORDTO CCTV CAMERA ARE FURNISHEDBY PROVO SCHOOL DISTRICT ANDINSTALLED AND CONNECTED BYTHE ELECTRICLA CONTRACTOR.
ROUTE FIBER, UTP AND 24VDC THROUGHCOUPLING. TYP.
WELDED IN PLACE 2"COUPLING BY POLE
MANUFACTURER, FORUTP AND 24VDC CABLE
CAT 6 UTP AND 24VDCCABLING UP TO CAMERAS.UTP AND 24VDC CABLINGSHALL 600 VOLT RATED ORINSTALLED IN CONDUIT.
FIBER OPTIC CABLING
120 VOLT CONDUCTORS
277 VOLT CONDUCTORSUP TO LIGHT FIXTURE.
24" MIN.
SECTION A-A
(3) TIES IN TOP 6" OF PIER
#3 TIES AT 6" O.C.
(8) #5 VERTICAL BARS
EXTERIOR SLABOR GRADE
2'-6"
DEPTH
AA
BASE PLATE AND ANCHOR BOLTS
BY LIGHT POLE MANUFACTURER
GROUND LUG WITH #8 AWGSOLID CU TO REBAR IN FOOTING
2'-0"
GROUND LUGPOLEHEIGHT
FTGDEPTH
FTGDEPTH
V ult =115 MPH
V ult =150 MPH
8'-0" 4'-0" 4'-0"
12'-0" 4'-0" 5'-0"
20'-0" 5'-0" 6'-0"
30'-0" 6'-0" 7'-0"
40'-0" 6'-0" 8'-0"
DESIGN CRITERIA:
2012 IBC
SS = 2.0, SOIL SITE CLASS D
LATERAL SOIL BRG = 100 PSF/FT
ASSUMED 4.0 FT² AT TOP POLECONCRETE:
F'c =4000 PSI
TYPE I/II CEMENT
GROUT ENTIRE AREA UNDERPLATE PROVIDE A MINIMUM ONEWEAP HOLE PER SIDEDOUBLE NUT LEVELING SYSTEM
PVC SCH 40 CONDUITSEE DRAWINGS FOR SIZE
ANCHOR BOLT
GRC ELBOW (TYP.)
CAP SPARECONDUIT AT
EACHDEAD END POLE
HAND RUB FINISHED
3/4" CHAMFER
PROVIDE IN-LINE WATERPROOFFUSE HOLDER WITH
BREAKAWAYRECEPTACLE AND FUSE
20'
SECTION A-A
EXTERIOR SLABOR GRADE
3'-6"
AA
ANCHORS PER BOLLARD
MANUFACTURER
(3) TIES IN TOP 6"OF PIER
#3 TIES AT 8" O.C.
(3) #4 VERTICAL BARS
10"
DESIGN ASSUMES:
200 # POINT LOAD AT TOP OF
BOLLARD (42" TALL BOLLARD)
CONCRETE:
F'c =3000 PSI
TYPE I/II CEMENT
PVC SCH 40 CONDUITSEE DRAWINGS FOR SIZE
NOTE:
CIVIL ENGINEER TO VERIFY BASE
DETAIL.
ELECTRICALHOOKS
42"
MIN
2 GANG STEEL BOX WITH WATER PROOF COVER FOR (2) SIMPLEX OUTLETS. SPOT WELD BOX TO BOLLARD
2 GANG STEEL BOX WITH GASKETED STEEL COVER PLATE TO BE USED FOR PULLING WIRES AND SPLICING AS REQUIRED. SPOT WELD BOX TO BOLLARD.
6" SQUARE BOLLARD
SIMPLEX OUTLETS
EXTERIOR SLABOR GRADE
3'-6"
AA
ANCHORS PER BOLLARD
MANUFACTURER
(3) TIES IN TOP 6"OF PIER
#3 TIES AT 8" O.C.
(3) #4 VERTICAL BARS
10"
DESIGN ASSUMES:
200 # POINT LOAD AT TOP OF
BOLLARD (42" TALL BOLLARD)
CONCRETE:
F'c =3000 PSI
TYPE I/II CEMENT
PVC SCH 40 CONDUITSEE DRAWINGS FOR SIZE
NOTE:
CIVIL ENGINEER TO VERIFY BASE
DETAIL.
SECTION A-A
42"
MIN
ELECTRICALHOOK
2 GANG STEEL BOX WITH WATER PROOF COVER FOR (2) SIMPLEX OUTLETS. SPOT WELD BOX TO BOLLARD
2 GANG STEEL BOX WITH GASKETED STEEL COVER PLATE TO BE USED FOR PULLING WIRES AND SPLICING AS REQUIRED. SPOT WELD BOX TO BOLLARD.
6" SQUARE BOLLARD
SIMPLEX OUTLETS
HOT DIP GALVANIZEDC CHANNEL UNISTRUT
NEMA 3RPANELBOARD
CONCRETE PAD
90"MAX
HEIGHT
2" RMC PIPE
GRADE
24"MIN.
6"
PVC SCH 40 CONDUITTO MCC IN CIC
PROCESS ELECTRICAL
ROOM
PVC SCH 40 CONDUITTO EQUIPMENT
48" MIN.
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:41:0
6 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
DR
ACE
ES501
SITE DETAILS
SCALE: NTS
POLE BASE DETAIL1
SCALE: NTS
POLE BASE DETAIL FLUSH2
SCALE: NTS
BOLTED BUS CHARGER DOUBLE OUTLET BOLLARD BASE DETIAL3
SCALE: NTS
BOLTED BUS CHARGER SINGLE OUTLET BOLLARD BASE DETIAL4
SCALE: NTS
LIGHT POLE CAMERA JUNCTION BOX DETAIL7
SCALE: NTS
EXTERIOR PANELBOARD MOUNTING DETAIL5
5'-0"
6'-0"
7'-0"
4'-0"
3'-6
"
4'-0
"
HOLD DOWN CLEAT
DETAIL 11 1/4" X 2 1/2" STAINLESS STEEL HOLD-DOWN CLEAT - 2 REQ'D.
3/8" X 1 1/4" STAINLESS STEEL BOLT - 2 REQ'D.
3/8" STAINLESS STEEL BELLVILLE WASHER - 2 REQ'D.
-STOCK ITEM 1790023
-STOCK ITEM 1790024
-STOCK ITEM 1008977
-STOCK ITEM 1008975
3/8" DIA. INSERTS W/
HOLD DOWN CLEATS
2 EA. REQ'D.
(SEE DETAIL 1)
2.4 - 25kV, 3-PHASE TRANSFORMER PADVAULT WITH ACCESS, STOCK ITEM 79926002.4 - 25kV, 3-PHASE TRANSFORMER PADVAULT WITHOUT ACCESS, STOCK ITEM 79926012.4 - 25kV, 3-PHASE TRANSFORMER PAD, STOCK ITEM 179002135kV, 3-PHASE TRANSFORMER PADVAULT WITH ACCESS, STOCK ITEM 799260235kV, 3-PHASE TRANSFORMER PADVAULT WITHOUT ACCESS, STOCK ITEM 799260335kV, 3-PHASE TRANSFORMER PAD, STOCK ITEM 1008958
2.38" DIA. TERM-A-DUCTS
2 EA. REQ'D.
(1 EA. NEAR WALL
1 EA. FAR WALL)
1/2" DIA. GROUNDING INSERTS
4 EA. REQ'D.
(2 EA. OUTSIDE WALLS
2 EA. INSIDE WALLS)
16" X 60" BLOCKOUT
5'-8" LONG GALV. "C" CHANNEL
2 EA. REQ'D.
(1 EA. NEAR & FAR WALLS)
7'-0"
5.57" DIA. TERM-A-DUCTS
8 EA. REQ'D.
(4 EA. NEAR WALL
4 EA. FAR WALL)
8,081 LBS.
2'-0" LONG GALV. "C" CHANNEL
4 EA. REQ'D.
(1 EA. WALL)
3.51" DIA. TERM-A-DUCT
1 EA. REQ'D.
4.5" DIA. TERM-A-DUCTS
14 EA. REQ'D.
(7 EA. NEAR WALL
7 EA. FAR WALL)
9'-4"
GALV. PULL IRON
4 EA. REQ'D.
(1 EA. CORNER)
PCORP #7992600 - SI #1790023
3,650 LBS.
12" DIA. HDPE SUMP
FULL 180° OPEN
(TYPICAL)
2.4 - 25kV, 3-PHASE TRANSFORMER PADVAULT WITHOUT ACCESS
PCORP #7992601 - SI #1790024
2.4 - 25kV, 3-PHASE TRANSFORMER PAD ONLY (NO BASE)
PCORP #1790021
3,090 LBS.
6"
4'-6
"
6'-10"
16" X 60" BLOCKOUT
7'-0"
1'-0"11"
NO. 25P GALV. DIAMONDPLATE DOORS W/ LOCKINGBOLTS
STAINLESS STEEL
HOLD DOWN CLEAT
STAINLESS STEEL
BELLVILLE WASHER
STAINLESS STEEL
BOLT
BASE
TOP
OPTIONAL TOPS
10'
10'
WINDOW
Door
10'
20'
AREA
NO PAD
IN THIS
3'3'
KEEP THISAREA
CLEAR10'-0"
10'-0"
3'-0"
3'-0"
3'-0"
KEEP
CLEAR
THIS AREA
10'-0"
SCALE:
SCALE:
SCALE:
TRENCH DETAIL
TRENCH DETAIL
TRENCH DETAIL
MARKER TAPE WITH TRACER WIRE LABELED,
"CAUTION BURIED ELECTRIC CONDUITS BELOW"
DIRECTLY OVER POWER CONDUITS 6" MINIMUM
BELOW GRADE.
CLEAN BACKFILL CONTAINING NO ROCKS
LARGER THAN 4" DIA.
BACKFILL MATERIAL WITHIN 4" TO 6" OF
CONDUIT SHALL PASS THROUGH A 3/4" SIEVE
FRAME OR SAND WITHOUT ANY SHARP OR
FOREIGN OBJECTS.
ALL CONDUITS SHOWN SHALL BE SCHEDULE 40
PVC.
UNDISTURBED EARTH.
MARKER TAPE WITH TRACER WRITE LABELED,
"CAUTION BURIED DATA/COMMUNICATION
CONDUIT BELOW" DIRECTLY OVER DATA/COMM
CONDUITS.
TRENCHES SHALL BE A UNIFORM DEPTH FOR
ENTIRE LENGTH OF TRENCH SO CONDUITS CAN
SIT FLAT (HORIZONTAL) WITH THE GROUND.
FINISHED GRADE.
TRENCHING KEYED NOTES:
TRENCHING KEYED NOTES:
PROVIDE 1/4" NYLON ROPES IN ALL CONDUITS.
HORIZONTAL AND VERTICAL SEPARATION BETWEEN
CONDUIT SHALL BE MAINTAINED BY INSTALLING HIGH
IMPACT SPACERS WITH HORIZONTAL INTERVALS OF
EIGHT FEET.
ALL MARKER TAPE SHALL CONTAIN #10 TRACER WIRE.
REFER TO THE ROCKY MOUNTAIN POWER SIX STATE
ESR FOR ADDITIONAL INFORMATION.
VERIFY ALL REQUIREMENTS WITH UTILITIES PRIOR TO
TRENCHING.
1.
2.
3.
4.
5.
T2
T3
T5
T8
T7
NONE CENTURYLINK / GOOGLE FIBER
T4
NONE PROVO POWER
T5
T7
T8
T5
T7
T8
T2
T3
T4
T1
T2
T3
T4
T1
2
4(PRIMARY POWER)
12"MIN.
NONE PROVO POWER3
(SECONDARY POWER)
24"MIN.48"
MAX.
30"MIN.48"
MAX.
12"MIN.
12"MIN.
24"MIN.
T6
T1
T2
T3
T4
T5
T6
T7
T8
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:41:1
3 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
ES502
SITE DETAILS
SCALE: NTS
PROVO POWER TRANSFORMER PAD VAULT DETAIL1
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:41:2
0 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
EL001
COMCHECK
OSa
OSa
OS a
OSa
OSa
OS a
OS
a
LV
2
LV
2
OS
a
OSa
OS
a
OSa
LV1
OSa
LV
1
OSa
OSa
OSa
aa
PP PP
PP
b
bb
b
LV1
cc
c c
RC
RC
3b
3a
4b
4a
3
a
3
b
g
4
a
4
b
4
c
4
d
4
e
4
f
3a
3b
3c
3d
3e
3f
3a
3b
3c
3d
3e
3f
GFEDCBA
1
2
4
5
3
OFFICE81
OFFICE82
VEST.95
CUST.83
HALL121 STORAGE
77
STORAGE94
DATA/ELEC79
OFFICE80
CORRIDOR124
TRAINING ROOM75
TRAINING ROOM75
OIL89
VEST122
Wmns96
HC / Uni97
Mns98
Emp. Tlt26
LOCKER91
S.92
Cust.99
TOOLS90
OFFICE52
OPEN SHOP93
STORAGE/PARTS55
STORAGE126
WASH BAY8
UPHOLSTERY56
WASH EQUIP /MECH12
Room123
AIR11
TIRES9
RECEPTION86
Hall120
ADD ALT # 1
F5
F2
F5
F5
F5
F5
F5
F4
F4
F3F3F4F4
F3
F3
F2
F12
F12
F1
F1
F1 F1F1
F1 F1
F1 F1
F1
F1
F1
F1
F1
F2
F2
F2
F2
F2
F1
F2E
F3
F3
F5
F5
F1
F3
bb
b b
a a
aa
a a bb
AV ZONE
AV ZONE
F3
E E
E
E
L1
L1
L- 5L- 5L- 5
L- 5L- 5 L- 5
L- 5
L- 5
L-5
L-5
L- 5
L- 5 L- 5 L- 5
L- 5(LCP-1)
L- 5
L- 5(LCP-1)
L- 5 L- 5 L- 5 L- 5
L- 5
L- 7 L- 7L- 7
L- 7
L- 7
L- 21
L- 7
L- 7
L- 7 L- 7 L- 7 L- 7 L- 7 L- 7 L- 7 L- 7
L- 7
L- 7
L- 7
L- 7
L- 7
L- 7
L- 7
L- 7
L- 5
L-5 L-5
L-7
L- 5(LCP-1)
L- 5(LCP-1)
L- 5(LCP-1)
L- 5(LCP-1)
L- 5(LCP-1)
L- 5(LCP-1)
L- 5(LCP-1)
L- 5(LCP-1)
L- 5L- 5L- 5L- 5
L- 5
L- 5
L- 5(LCP-1)
L- 5(LCP-1)
L- 5
L- 5(LCP-1)
L- 7L- 7
L- 7
F2
L- 23(LCP-2)
L- 23(LCP-2)
L4
L3
WP
WP
WP
WP
WPX1
WP WP
XE1
XE1
XE1
X1X1
X1
XE1
L- 5
L- 7 L- 7 L- 7
F3
L- 23(LCP-2)
b
b
b
f
1
EL102
X1
GENERAL LIGHTING NOTES:
1. REFER TO EL701 FOR TYPICAL LIGHTING CONTROL WIRING DIAGRAMS. PROVIDE COMPLETE SYSTEM WITH ALL REQUIRED CONDUIT SYSTEM WITH ALL REQUIRED CONDUIT, WIRING, SWITCHES, SENSORS, POWER PACKS, ETC. AS REQUIRED.
2. LOCATE POWER PACKS ABOVE ACCESSIBLE CEILING NEAR ROOM ENTRANCES.
3. CONFIRM ALL LOCATIONS OF LIGHT FIXTURE WITH ARCHITECT PRIOR TO INSTALLATION.
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:41:2
7 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
EL101
CEILING PLAN LEVEL 1 - LIGHTING
SCALE: 1/8" = 1'-0"
CEILING PLAN LEVEL1 - LIGHTING1
KEYED NOTES
L1 PROVIDE CAT 5 CABLE AND TIE TOGETHER ROOM CONTROLLERS IN TRAININGROOMS SO THE LIGHTING CAN BE CONTROLLED TOGETHER WHEN DESIRED.
L3 TIE SWITCH TO OCCUPANCY SENSOR SHOWN ON SHEET EL102.
L4 IF ADD ALT # IS NOT ACCEPTED. LOCATE F12 FIXTURE ABOVE DOOR 154.
#
bdd
d
PP
GFEDCBA
1
2
4
5
3
F2EF2F2F2E
F6 F6 F6
F6F6
F6
F6F6
F6
F7
F7
F2
F2E
g g g g g
e
e
e
ed
d
d
d
c
c
c
cb
b
b
b
a
a
a
a
f f f f
b
b
b
b
b
c
c
c
c
c
d
d
d
d
d
e
e
e
e
e
L- 9
L- 9
L- 9
L- 9
L- 9
L- 9
L- 9
L- 11
L- 11
L- 11
L- 11
L- 11
L- 11
L- 11
L- 13
L- 13
L- 13
L- 13
L- 13
L- 13
L- 13
L- 21 L- 21 L- 21 L- 21
L- 15
L- 15
L- 15
L- 15
L- 15
L- 15
L- 15
L- 17
L- 17
L- 17
L- 17
L- 17
L- 17
L- 17
a
a
a
a
a
L- 19
L- 19 L- 19
L- 19
L- 19L- 19
L- 19L- 19
L- 19 L- 19
L- 19L- 19L- 21L- 21L- 21
L- 9
L- 9
L- 11
L- 11
L- 13
L- 13
L- 17
L- 15
L- 17
L- 15
L- 21
L- 21L- 21
a
a
a
a
a
b
b
b
b
b
L2
L2
L2 L2 L2 L2
L2
L2 L2 L2
L2
L2
L2
L2
L2
L2
ADD ALT # 1
g
L-21
GENERAL LIGHTING NOTES:
1. REFER TO EL701 FOR TYPICAL LIGHTING CONTROL WIRING DIAGRAMS. PROVIDE COMPLETE SYSTEM WITH ALL REQUIRED CONDUIT SYSTEM WITH ALL REQUIRED CONDUIT, WIRING, SWITCHES, SENSORS, POWER PACKS, ETC. AS REQUIRED.
2. LOCATE POWER PACKS ABOVE ACCESSIBLE CEILING NEAR ROOM ENTRANCES.
3. CONFIRM ALL LOCATIONS OF LIGHT FIXTURE WITH ARCHITECT PRIOR TO INSTALLATION.
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:41:3
5 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
EL102
CEILING PLAN MEZZ - LIGHTINGSCALE: 1/8" = 1'-0"
FLOOR PLAN MEZZ - LIGHTING1
KEYED NOTES
L2 TIE CIRCUIT THROUGH SWITCHES SHOWN ON SHEET EL101.
#
4VT2-LD4-6-DR-UNV-L835-CD1-WL-VT2-CHAIN/SET-U
INT-4-50-L35-UNV-DIM
GLEON-AF-05-LED-E1-T4FT-SFBA-FF-208
(2)GLEON-AF-04-LED-E1-T4W-SCBA-FF-208
IST-F01-LED-E1-BL4-SCBA
GLEON-FA-02-LED-E1-T4W-SCBA-600
REFER TO FLOOR PLANS FORMOUNTING.
SOV-EM-G-1C-SFBA-XX-UC
REFER TO FLOOR PLANS FORMOUNTING.
CCDS-EM-G-1-SCBA-XX
24-FR-LD4-50-UNV-L835-CD-1-U
*-SNLED-LD4-50SL-FW-UNV-L835-CD-1-U
LD6B-15-D010-EU6B-1020-80-35-6LB-M-1-H-HB26
METALUX 4-WNLED-LD4-40SL-F-UNV-L835-CD-1-U
LIGHT FIXTURE SCHEDULE
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION SOURCE LOAD APPROVED MANUFACTURERS CATALOG NUMBER / SERIES COMMENTS / NOTES
54" PENDANT MOUNTED LINEAR HIGH-BAY LIGHTFIXTURE. IMPACT RESISTANT, CLOSED-CELL GASKET,20-GAUGE STEEL CHANNEL HOUSING. 36" CHAINHANGER KIT. WIDE DISTRIBUTION.
LED6000 LUMENS0-10V DIMMING3500K
120V62W
LITHONIA VAP-6000LM-FST-WD-GZ10-35K-80CRI-VAPCM13-HC36
H.E. WILLIAMS LIGHTING 96-4-L60/835-HIAFR-DIM-UNV
METALUX
SURFACE MOUNTED 4' LINEAR LIGHT FIXTURE.WATER PROOF GASKETED. ONE-PIECE FIBERGLASSHOUSING WITH POURED IN PLACE NEMA 4X GASKET.
LED6000 LUMENSON/OFF3500 K
120V45W
LITHONIA FEM-L48-6000LM-IMAFL-WD-120-GZ10-35K-80CRI-WLFEND2
NULITE
EXTERIOR WALL PACK LIGHT FIXTURE. TWO-PIECEDIE-CAST ALUMINUM HOUSING WITH ZINC-INFUSEDTGIC POWDER COAT PARTS. TYPE 3 MEDIUMDISTRIBUTION.
LED2700 LUMENS10 LEDSAT 700mAON/OFF4000K
120V27W
LITHONIA DSXW1-LED-10C-700-40K-T3M-120-BBW
H.E. WILLIAMS LIGHTING VWPH-L30/740-T3-SCBA-SDGL-DIM-UNV
EXTERIOR WALL PACK LIGHT FIXTURE. TWO-PIECEDIE-CAST ALUMINUM HOUSING WITH ZINC-INFUSEDTGIC POWDER COAT PARTS. TYPE FORWARD THROWMEDIUM DISTRIBUTION.
LED2100 LUMENS10 LED'SAT 530mAON/OFF4000K
120V20W
LITHONIA DSXW1-LED-10C-530-40K-TFTM-120-BBW
H.E. WILLIAMS LIGHTING VWMH-L20/740-TFT-SCBA-SDGL-DIM-UNV
ZERO UPLIGHT NIGHTTIME FRIENDLY POLE LIGHTDIE-CAST ALUMINUM HOUSING WITH INTEGRAL HEATSINK. FORWARD THROW DISTRIBUTION. WITH 25'SQUARE ALUMINUM POLE. POLE MUST BE WIDEENOUGH TO FIT (4) 1" CONDUITS.
LED29,000 LUMENS80 LED'S AT1000mAON/OFF4000K
208V282W
LITHONIA DSX2-LED-80C-1000-40K-TFTM-208-SPA-DF-SFBA REFER TO NOTES 'S4' AND 'S5' ONSHEET ES101.
CREE
MCGRAW-EDISON
ZERO UPLIGHT NIGHTTIME FRIENDLY POLE LIGHTDIE-CAST ALUMINUM HOUSING WITH INTEGRAL HEATSINK. TYPE 4 MEDIUM DISTRIBUTION. (2) HEADSMOUNTED AT 180 DEGREES. WITH SQUARE ALUMINUM25' POLE.
LED21500 LUMENS80 LED'S AT700mAON/OFF4000K
208V(2) 188W
LITHONIA DSX2-LED-80C-700-40K-T4M-208-SPUMBA-OF-SCBA REFER TO NOTES 'S4' AND 'S5' ONSHEET ES101.
CREE
MCGRAW-EDISON
EXTERIOR TRAPAZOIDAL WALL PACK LIGHT FIXTURE.SINGLE PIECE DIE-CAST ALUMINUM HOUSING.
LED700 LUMENSON/OFF4000K
120V9W
LITHONIA WSTM-LED-1A-40K-120-SFBA
H.E. WILLIAMS LIGHTING VWM-H-L10/740-T3-SCBA-SDGL-DIM-UNV
MCGRAW-EDISON
ZERO UPLIGHT NIGHTTIME FRIENDLY POLE LIGHTDIE-CAST ALUMINUM HOUSING WITH INTEGRAL HEATSINK. TYPE 4 MEDIUM DISTRIBUTION. WITH SQUAREALUMINUM POLE.
LED6573 LUMENS60 LED'S AT530 mAON/OFF
120V99 WATTS
LITHONIA DSX1-LED-60C-530-40K-T4M-120-SPA-SCBA
CREE ARE-EDG-4M-DA-06-E-UL-SCBA-525MA-40K
MCGRAW-EDISON
DIE-CAST ALUMINUM EDGE-LIT, LED EXIT SIGN SINGLEFACE. GREEN LETTERS, CLEAR BACKGROUNDBRUSHED ALUMINUM FINISH CEILING/BACKMOUNTING. REFER TO DRAWING FOR ARROWS.PROVIDE WITH NICKEL CADMIUM BATTERY.
LED LITHONIA LRP 1 GC 120/277 EL N (OR APPROVED EQUIVALENT).
EVENLITE
DIE-CAST ALUMINUM, LED EXIT LIGHT SINGLE FACE,GREEN LETTERS WHITE FINISH, REFER TO DRAWINGFOR ARROWS. PROVIDE WITH NICKEL CADMIUMBATTERY.
LED LITHONIA LE S W 1 G 120/277 EL N (OR APPROVED EQUIVALENT).
EVENLITE
LIGHT FIXTURE GENERAL NOTES1. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATIONS OF LIGHT FIXTURES. BRING ALL DISCREPANCIES OF LOCATIONS AND QUANTITIES TO THE ATTENTION OF THE ARCHITECT
PRIOR TO BIDDING.
2. CONFIRM MOUNTING HEIGHTS AND LOCATIONS OF ALL LIGHT FIXTURES WITH ARCHITECTURAL ELEVATIONS AND / OR ARCHITECT.
3. REFER TO THE SPECIFICATIONS FOR OTHER LIGHT FIXTURE REQUIREMENTS.
4. CONFIRM AVAILABLE MOUNTING DEPTHS OF ALL LIGHT FIXTURES AND COMPARE WITH DEPTHS SHOWN ON SHOP DRAWINGS. BRING ALL POTENTIAL CONFLICT AREAS TO THE ATTENTION OF THE
ARCHITECT AND ELECTRICAL ENGINEER PRIOR TO RELEASE.
5. ALL LIGHT FIXTURES ARE TO BE 3500K FOR INTERIOR APPLICATIONS AND AND 4000K FOR EXTERIOR APPLICATIONS, UNLESS OTHERWISE NOTED IN THE FIXTURE DESCRIPTION.
6. ALL LIGHT FIXTURES ARE TO BE A MINIMUM OF 80 CRI UNLESS OTHERWISE NOTED IN THE FIXTURE DESCRIPTION.
7. ALL LED SOURCES MUST MEET L80 AT 50,000 HRS MINIMUM UNLESS OTHERWISE NOTED.
8. CONFIRM ALL MOUNTING REQUIREMENTS WITH ARCHITECT PRIOR TO RELEASE.
BIDDING REQUIREMENTS1. BID ONLY PRODUCTS THAT ARE SPECIFIED OR APPROVED BY ADDENDUM.
2. PACKAGING OF LIGHT FIXTURES WITH OTHER SYSTEMS IS NOT ALLOWED AND MUST BE BID SEPARATELY. I.E. LIGHT FIXTURES, THEATRICAL LIGHTING, SPORTS LIGHTING AND ALL LIGHTING CONTROLS.
3. WHEN ONLY ONE OR TWO PRODUCTS ARE APPROVED FOR BIDDING, THE PRICE FOR THOSE FIXTURE TYPES SHALL BE BROKEN OUT SEPARATELY WHEN SUBMITTING PRICING TO VARIOUS DISTRIBUTORS AND / OR CONTRACTOR.
4. WHEN A CONTRADICTION EXISTS BETWEEN A SPECIFIC MODEL NUMBER AND THE DESCRIPTION, THE DESCRIPTION SHALL GOVERN.
LIGHT FIXTURE PRIOR APPROVAL REQUIREMENTS1. PRIOR APPROVAL IS REQUIRED BEFORE BIDDING THIS PROJECT.
2. PRIOR APPROVALS SHALL BE SUBMITTED TO THE ELECTRICAL ENGINEER'S OFFICE AT LEAST (8) WORKING DAYS BEFORE BID TIME. PRIOR APPROVALS RECEIVED AFTER THIS TIME PERIOD SHALL BE
REJECTED.
3. ITEMS THAT ARE SUBMITTED AND HAVE BEEN APPROVED WILL BE LISTED IN THE ADDENDUM(S). VERBAL APPROVALS WILL NOT BE GIVEN ON ANY ITEM.
4. IT IS NOT THE RESPONSIBILITY OF THE ELECTRICAL ENGINEER TO NOTIFY THE SUBMITTING PARTY OF ERRORS IN THE SUBMITTAL. NOTIFICATION OF ERRORS BY THE ELECTRICAL ENGINEER PRIOR TO
ISSUANCE OF THE ADDENDUM(S) MAY NOT BE GIVEN.
5. PRIOR APPROVALS SHALL CONSIST OF CUT SHEETS DESCRIBING THE PRODUCTS BEING SUBMITTED AS EQUIVALENTS. ALL SPECIFICATION INFORMATION SHALL BE CLEARLY MARKED. PRODUCTS
WITHOUT PHOTOMETRIC DATA WILL NOT BE APPROVED.
6. LIGHTING PACKAGES WILL BE REVIEWED FOR GENERAL PROJECT COMPLIANCE ONLY. AN IN-DEPTH REVIEW OF ANY ALTERNATE FIXTURES WILL BE DONE DURING THE SUBMITTAL REVIEW PROCESS.
ANY FIXTURES THAT ARE NOT TRULY EQUAL, AND / OR DO NOT COMPLY WITH ALL OF THE REQUIREMENTS CONTAINED IN THE CONTRACT DOCUMENTS, WILL NOT BE APPROVED.
F6
F7
F8
F9
F10
F11
F12
F13
XE1
X1
TYPE DESCRIPTION SOURCE LOAD APPROVED MANUFACTURERS CATALOG NUMBER / SERIES COMMENTS / NOTES
DECORATIVE 2'X4' LED LAY-IN TROFFER LIGHTFIXTURE. DIE-FORMED FABRICATED WITH POWDERPAINT WITH CURVED LINEAR PRISMS ACRYLIC LENS.INTEGRAL T-BAR CLIPS ON END PLATES AND LAY-INGRID MOUNTING.
LED4800 LUMENS0-10V DIMMING3500K
120V38W
LITHONIA 2BLT4-48L-ADSM-EZ1-LP835
H.E. WILLIAMS LIGHTING LT24-L48/835-AF-DIM-UNV
METALUX
PENDANT MOUNTED STRIP LIGHT FIXTURE.COLD-ROLLED STEEL BODY WITH FIVE-STAGE IRONPHOSPHATE PRE-TREATMENT PAINT. 36" CHAINHANGER KIT.
LED5000 LUMENSDIMMING3500K
120V42W PER 4'
LITHONIA ZL1D-L**-*000LM-FST-120-35K-HC36
REFER TO FLOOR PLANS FOR LENGTHOF FIXTURES.
CREE LS*-50L-35K-10V-AC5-12/3-48-Q14B-JB
MATALUX
OPEN REFLECTOR RECESSED LOW PROFILE
ROUND DOWNLIGHT WITH 6" APERTURE PARABOLIC
SEMI-SPECULAR REFLECTOR AND FROSTED
CONVEXED LENS. CONCEALED LED ARRAY
LOOK.
LED1500 LUMENS0-10V DIMMING3500K
120V34.6W
JUNO L6-15-351-G3-L600P-C-Q-WH
H.E. WILLIAMS LIGHTING L60-L15/835-CS/LAD-DIM-UNV
PORTFOLIO
2' DECORATIVE SQUARE LINEAR WALL MOUNTEDVANITY LIGHT FIXTURE.
LED1300 LUMENSON/OFF
120V18W
LITHONIA FMVCSL-24IN-MVOLT-35K-90CRI-SFBA
STONE LIGHTING BB415-24-T5LED
4' LONG NARROW HOUSING SURFACE WRAPAROUNDLIGHT WITH DIE-FORMED CODE-GUAGE STEEL.CURVED PRISMATIC DIFFUSER WITH HIGH-ANGLEBRIGHTNESS CONTROL.
LED4000 LUMENSON/OFF3500 K
120V41W
LITHONIA LBL4-40L-EZ1-LP835
H.E. WILLIAMS LIGHTING 17-4-L40/835-A-DIM-UNV
F1
F2
F3
F4
F5
JACK CHAIN TO STRUCTUREFOR LATERAL BRACING(TYP. 2X)
CHAIN SETSTEEL JOIST
BRANCH CIRCUITING SEE PLAN
LIGHT FIXTURE
KEYED NOTES:
1. MOUNTING HEIGHT. SEE LIGHTING PLANS FOR REQUIREMENTS.
#1
a14L-4/LC14-2
14EL-3
F# LETTER DESIGNATESFIXTURE TYPE.
LOWERCASE LETTER DESIGNATESSWITCHING OR CIRCUIT ASSIGNMENT.ASSIGNMENTS, SUCH AS a/b, INDICATEDUAL LEVEL SWITCHING.
CIRCUIT DESIGNATION (FIRST)/RELAY DESIGNATION (SECOND)
CIRCUIT DESIGNATION
F#E LETTER DESIGNATESFIXTURE TYPE.
SHADING INDICATES EGRESS LIGHTFIXTURE. PROVIDE A 1400 LUMEN,90 MINUTE EMERGENCY BATTERY PACK (BODINE B50, OR APPROVED EQUAL).
EXIT SIGNS. CONNECTTO UNSWITCHED HOTEMERGENCY LIGHTINGCIRCUIT.
SUPPORT CLIP ARRANGEMENT DIAGRAMS
2' x 4' OR 1' x 4'
LAY-IN TROFFER
#12 STEEL WIRE
2' X 2'
WIRE HANGER AT EACHOF FOUR CORNERSINDEPENDENT OFCEILING SUPPORT SYSTEM
ANCHOR TO CONCRETE CEILING USING 3/4" PIN & ANGLE CLIP
LAY-IN TILE
CEILING
LAY-IN AND TROFFER LIGHTFIXTURE SUPPORT CLIP(CADDY 515 OR 515A TO SUITAPPLICATION OR EQUIVALENT).PROVIDE 4 CLIPS PER FIXTURE.
LV
#1
WHERE A SINGLE-POLE TOGGLE SWITCH ANDOCCUPANCY SENSOR ARE SHOWN IN THESAME ROOM, THE SWITCH SHALL BE WIREDTO THE OCCUPANCY SENSOR AND FUNCTIONAS A MANUAL OVERIDE.
C
LOWERCASE LETTER DESIGNATESSWITCHING OR CIRCUIT ASSIGNMENTWITHIN ROOM.
INDICATES DUAL LEVEL SWITCHING.INBOARD LAMPS ARE TO BE SWITCHEDSEPARATELY FROM OUTBOARD LAMPS.
X
SUBSCRIPT DESIGNATES TYPE OFOCCUPANCY SENSOR. REFER TOOCCUPANCY SENSOR SCHEDULE
ab
LOW VOLTAGE OVERRIDE SWITCH. NUMBERREFERS TO SWITCH PROGRAMMING DETAILSLISTED IN PUSHBUTTON SCHEDULE.
c
LOWERCASE LETTER DESIGNATESSWITCHING OR ZONEWITHIN ROOM.
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:41:4
1 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
EL601
LIGHT FIXTURE SCHEDULE
SCALE: NTS
TYPICAL CHAIN HUNG LIGHT FIXTURE DETAIL1SCALE: NTS
TYPICAL LIGHT FIXTURE CONVENTION2
SCALE: NTS
RECESSED GRID LIGHT FIXTURE SUPPORT DETAIL3
SCALE: NTS
TYPICAL SWITCHING CONVENTION4
NOTE:1.) PROVIDE WATTSTOPPER DLM LIGHTING CONTROL SYSTEM (OR APPROVED EQUIVALENT).2.) DIAGRAM SHOWS TYPICAL DEVICE WIRING. REFER TO FLOOR PLANS FOR EXACT NUMBER AND TYPEOF DEVICES FOR EACH ROOM / SPACE3.) MAX 3 RELAYS PER ROOM CONTROLLER. PROVIDE ADDITIONAL ROOM CONTROLLERS AS REQUIREDFOR ADDITIONAL RELAYS AND TIE TOGETHER WITH CAT5E CABLE. REFER TO FLOOR PLANS.4.) LMLS-500 PHOTOSENSOR IS USED TO MONITOR DAYLIGHT FOR AUTOMATIC 0-10V DIMMING LIGHTADJUSTMENT FOR CORRECT LEVELS.
*DLM OccupancySensor
*NOTE:Corner mount Sensor shown with pigtail &supplied coupler. Ceiling mount Sensor hastwo RJ45 ports.
LMRJ-C8
Coupler
RJ45
(Typical)
Red
Yel
Lighting
Load
(c)
Blu
Lighting
Load
(a)
Lighting
Load
(b)
Vio
Gry
VioGry
VioGry
VioGry
Vio
Gry V
ioG
ry
Class 2 0-10 VoltControl Wiring
0-10VDC DimmingDriver required.
LMRJ Series Pre-TerminatedCables or CAT5e. Free Topology& Splitter Acceptable
120/230/277
Hot Blk
Neutral WhtLMRC-213
Dimming RoomController
RJ45 Port(Typical)
LMDM-101 Dimming Switcheswith LMSW-103 Scene Switch
All loads auto-onat 50% light levels.
Neutral
Red
daL o
(Load)
Single Low Voltage Switch
LINE BLACK
NEUTRAL WHITE
GROUND GREEN
FOR USE WITH DW-100-24,PW-100-24, AND UW-100-24.
OPERATION :
Occupancy Sensor switches
Lights ON/OFF. When occupied, the
LS-301 dims the lights as daylight
increases.
RED
BLACK
RED
RED
BLU
BLU
RED
REDYLW
YLW
GRY(-)
VIO(+)
COMMON
CONTROL OUTPUT
RE
D
BLK
BLU
WHT
BLKHOT
NEUTRAL
WIRING WITH OCCUPANCY SENSOR
ANY
CEILING/WALL
OCCUPANCY
SENSOR
LS-301
ELECTRONIC
DIMMING
DRIVER
(0-10 VDC)
LAMP
LAMP
POWER
PACK
VIOLET
GREY
+24VDC
LS-301 WIRING SCHEMATIC
LOCALOVERRIDESWITCH
P
LV#
TO BUILDING AUTOMATION SYSTEM
PANEL
'LCPB'
PHOTOCELL
BASEMENT
LOW VOLTAGE
OVERRIDE SWITCH(TYPICAL)
PROVIDE ASTRONOMICAL TIME CLOCKFUNCTIONS AND CPU IN THIS PANEL.REFER TO RELAY PANEL SCHEDULE ANDPUSH BUTTON SCHEDULE FOR ADDITIONALINFORMATION.
1
1
1
ROOF
TO OTHER SWITCHES, DAISY CHAIN WIRING CONFIGURATION
24 RELAY
2
LMDC-100
DW-100
DT-355
DT-300
CATALOG NUMBERTECHNOLOGY
DUAL TECHa
c
b
SYMBOL
OCCUPANCY SENSOR SCHEDULE
WATTSTOPPERVOLTAGE
DIGITAL
LINE
LINE
LOW
OSa
MOUNTING
CEILING
WALL
CEILING
CEILING
VACANCY TYPE
VACANCY
VACANCY
VACANCY
OCCUPANCY
DUAL TECH
DUAL TECH
DUAL TECH 3/EL701
2/EL701
1/EL701
DIAGRAMWIRING
d DUAL TECH VACANCY LOW CEILING DT-300
4/EL701
5/EL701
BLK
POWER PACK
HOT
RE
D
+24VDC
CONTROL OUTPUT
COMMON
BLU
24VDCOCCUPANCYSENSOR
NEUTRAL
LOCALOVERRIDESWITCH
LIGHTINGLOAD
+24VDC
COMMON24VDCOCCUPANCYSENSOR
CONT. OUTPUT
(QTY AS INDICATEDON DRAWINGS)
GENERAL NOTES:
1. PROVIDE ADDITIONAL POWER PACKS AND OCCUPANCY SENSORS AS REQUIRED.
NEUTRALLOAD
SWITCH LOAD HOT
NEUTRALGROUND
(OPTIONAL)
NOTES:1.) PROVIDE WATTSTOPPER DLM LIGHTING CONTROL SYSTEM (OR APPROVED EQUIVALENT). 2.)DIAGRAM SHOWS TYPICAL DEVICE WIRING. REFER TO FLOOR PLANS FOR EXACT NUMBER AND TYPE OF DEVICES FOR EACH ROOM/SPACE.3.) MAX 3 RELAYS PER ROOM CONTROLLER. PROVIDE ADDITIONAL ROOM CONTROLLERS AS REQUIRED FOR ADDITIONAL RELAYS AND TIE TOGETHER WITH CAT5E CABLE. REFER TO FLOOR PLANS. 4.) LMLS-500 PHOTOSENSOR IS USED TO MONITOR DAYLIGHT FOR AUTOMATIC 0-10V DIMMING LIGHT ADJUSTMENT FOR CORRECT LEVELS.
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:44:4
1 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
EL701
WIRING DIAGRAMS
SCALE: NTS
LIGHTING CONTROL DETAIL - SINGLE LOAD1
SCALE: NTS
LINE VOLTAGE OCCUPANCT SENSOR WIRING DIAGRAM2
LOW VOLTAGE PUSHBUTTON SCHEDULE
SWITCHID
WATTSTOPPER CATALOG #
(ORAPPROVED
EQUAL)
WIRINGDETAIL
REFERENCE
BUTTONS - AREA/LOAD CONTROLLED
B-1 B-2 B-3 B-4 B-5 B-6
1 LVSW-102 6/EL701 LCP-1 ON LCP-1 OFF - - - -
2 LMSW-105 3/EL701 DIM UP/DOWN 'a' OFF, 'b' 50% 'a' ON/OFF 'b' ON/OFF ALL ON/OFF -
LIGHTING CONTROL PANEL RCPRELAY
ELECTRICAL INFO
LOCATIONSWITCH
O/S
CHANNEL
PANEL CKT LOAD A B C D E F G H
LCP-1 L 5 754 W CORRIDOR LTG LV1 X
LCP-2 L 23 942 W EXTERIOR LTG - X
LCP-3 L 1,3 2068 W BUS PARKING LIGHTING CONTACTOR - X
LCP-4 0 W SPARE
LCP-5 0 W SPARE
LCP-6 0 W SPARE
LCP-7 0 W SPARE
LCP-8 0 W SPARE
SCALE: NTS
LC-PHOTOSENSOR DIMMING WIRING DIAGRAM3
CHANNEL LOAD DESCRIPTION PROGRAM REQUIREMENTS
A
B
CDE
GENERAL NOTES:1. PROGRAM SYSTEM TO MEET REQUIREMENTS OF 2015 IBC & 2015 IECC.2. CONFIRM SWITCHING SCHEME WITH OWNER PRIOR TO PROGRAMMING SYSTEM.3. INCLUDE A FINE TUNING VISIT WITHIN 3 MONTHS OF BUILDING OCCUPANCY AT OWNER'S REQUEST TO
MAKE MINOR ADJUSTMENTS.4. REFER TO SHEET ES101 FOR PHOTOCELL LOCATION.
INTERIOR LTG
EXTERIOR LTG
TIME CLOCK CONTROLLED. CORRDINATEWITH OWNER FOR SCHEDULE.TIME CLOCK AND PHOTOCELLCONTROLLED CORRDINATE WITH OWNERFOR SCHEDULE AND SETTINGS.
SCALE: NTS
WALL OCCUPANCY SENSOR SWITCH WIRING DIAGRAM4
SCALE: NTS
ANALOG DAYLIGHT SENSOR WIRING DIAGRAM5
SCALE: NTS
RELAY PANEL RISER DIAGRAM6
WH
F
F
FF
T T T T
F
PR
MDMD
D
MD
MD
MD
D
D D D D
F F
F
TT
TT
T
T
T
F
F
F
T
J
J
J
T
T
FF
F
F F
F
F
F
AN
N
JJ
J
ED
D
D
D
D
D
D
T
LC
F
F
F
J
F
J
D
D
Z
Z
GFEDCBA
1
2
4
5
3
DATA/ELEC79
OFFICE80
CUST.83
OFFICE82
OFFICE81
STORAGE77
RECEPTION86
OFFICE52
Emp. Tlt26
TRAINING ROOM75
Mns98
HC / Uni97
HALL121
STORAGE94
Cust.99
TOOLS90
Hall120
Wmns96
VEST.95
UPHOLSTERY56
WASH EQUIP /MECH12
Room123
AIR11
TIRES9
LOCKER91
S.92
STORAGE/PARTS55
OPEN SHOP93
OIL89
STORAGE126
WASH BAY8
CORRIDOR124
VEST122
A A A A
AA
AA
A
2
EP101
WP
+42" +42"
+42"
+42"
+42"
WP
WP
ADD ALT # 1
P2
P1
WP
3
EP101
'G'
G
1
D
1
A
1
G
2
P2 P2 P2
P2
360º
A
WP
WP
WP
WP
WP
WP
P3
CLGCLG
CLG
CLGCLG
CLG
WP
WPWP
P5
P4
P-1
P-1
P-1P-1
P-1
P-1P-3
P-3P-3
P-3
P-3
P-3
P-5
P-5 P-5
P-5
G-1
P-7
P-7P-7
P-7
P-7
P-7
P-17 P-19
P-19P-20
P-19
P-20
P-21P-21P-21
P-21P-21
P-21
P-23
P-25
P-27
P-14
P-14
P-14
P-14
P-16
P-18
P-20
P-20
P-14
P-5
P-20
P-5P-20G-1
G-1G-1 G-1
G-3
G-3G-3
G-3
G-3
G-5
G-5G-5
G-5 G-5
G-7
G-7
G-7G-9
G-9
G-9
G-9
G-11
G-11
G-11
G-13
G-15
G-15
G-15G-15G-17G-17
G-17
G-17
G-19 G-19 G-19G-19
G-23 G-25 G-27 G-29
G-32,34,36
G-2,4,6G-8,10,12
G-14,16,18
G-31
FF
1
EF
1
EF
2
EF
3
EF
4
EF
5
EF
6
EF
7
EF
9
PW
1
FF
2
M-13,15,17
M-1,3,5 L-7L-7
L-7
L-7
L-7
2
2
L-7
M-7,9,11
L-7
M-2,4,6
2
2
2
2
2
2
2
22
2
2
2
2
222
1
1
2
22
2
2
2
2
22
1
WP
WP
WP
RTH
2
G-11
M-8
M-14
P7
M-14 P7
G-38,40
P6 G-20,22,24 G-26,28,30
BATTERY CHARGER
G-33 G-35
BATTERY CHARGER
BL
1
BL
1
DWH
2
M-18
P
2
M-20
P8 P8 P8P8 P8 P8
WP
WP
75cd
15cd
75cd
15cd
75cd
75cd
15cd30cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd 15cd
15cd
P-22
P-24
EP502
2
100
EP502
3
101
15cd
EP502
1
112
EP503
3
115
EP503
2
142
EP503
1
(TYP)
EP503
2
137
EP503
2
133
EP503
2
128
P10P11P12
OHD
1(TYP)
LEVEL 10' - 0"
TOW9' - 0"
SINK DISPOSAL
REFRIGERATOR SWITCH
2' -
6"
GFCI GFCI
P-29
P-33
P-31 P-31
DATA/ELEC79
'MDP'
'L'
'P'
'LCP'
P-9 P-11
P-13
P-15
EF
8
M-10'M'
'TC1'
'TC2'
L5
'FACP'
'NAC'
P-8
P-10
P-12
GENERAL POWER NOTES:
1. ALL 120V, 20AMP OUTLETS THAT ARE WITHIN 6' OF ANY SINK SHALL BE GFCI.
2. THE DISION 26 CONTRACTOR SHALL DETERMINE THE EXACT ROUTING OF ALL CONDUITS IN THE FIELD. THIS PLAN REPRESNTS A SCHEDMATIC REPRESENTATION OF DEVICE LOCATION AND CONDUIT RUNS.
GFEDCBA
1
CU
1
RTU
1
HRV
1
G-21
G-21 G-21
M-19,21,23
M-25,27,29
M-31,33,35
M-16
P7
AHU
1
M-16
P7
M-37,39,41
30cd
P9
P9
WP
WPG-21
WP
WPG-21
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:41:5
8 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
EP101
FLOOR PLAN LEVEL 1 - POWER
SCALE: NTS
FLOOR PLAN LEVEL 1 - POWER1
KEYED NOTES
L5 PROVIDE A MULTI-POLE CONTACTOR (WATTSTOPPER CAT. #C115CO, OR APPROVEDEQUIVALENT). RUN 208V, 2 POLE SITE LIGHTING CIRCUIT THROUGH LIGHTINGCONTRACT. TIE THE 120V COIL FOR THE CONTACTOR THROUGH A RELAY IN THE'LCP' PANEL.
P1 COORDINATE EXACT HEIGHT AND LOCATION OF OUTLETS FOR TV WITH OWNER.
P2 COORDINATE WITH GARAGE DOOR INSTALLER AND ARCHITECT FOR MOTORPLACEMENT AND INSTALLATION .
P4 COORDINATE WITH WHITE BOARD SUPPLIER FOR EXACT LOCATION REQUIRED FORPOWER AND DATA OUTLETS FOR SHORT THROW PROJECTOR.
P6 TERMINATE CIRCUIT AT J-BOX FOR FUTURE USE.
P7 PROVIDE POWER INDICATED FOR MECHANICAL DAMPERS. COORDINATE WITHMECHANICAL.
P8 CIRCUIT EF TO LIGHTING IN ROOM SO EF CAN BE CONTROLLED WITH LIGHTING.REFER TO SHEET EL101.
P9 PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR DUCT OF THE ROOF TOPUNIT AS SHOWN. TIE TO THE FIRE ALARM CONTROL PANEL AND TO THE ROOT TOPUNIT FOR AUTOMATIC SHUT DOWN.
P10 ALL RECEPTACLES IN THE SHOP SHALL BE MOUNTED AT 48" AFF. ELECTRICALINSTALLATION FROM FINISHED FLOOR TO +18" AFF SHALL COMPLY WITH CLASS 1 DIV2 PER ALL NEC REQUIREMENTS.
P11 ALL CONDUIT THAT IS RUN BELOW THE FLOOR SLAB AND UP INTO EQUIPMENT,DEVICES, JUNCTION BOXES, PANELS, ETC SHALL BE CONTINUOUS FROM THE ELBOWBELOW GRADE TO THE EQUIPMENT, DEVICE, JUNCTION BOX, PANEL, ETC. IF ANYCONDUIT COUPLINGS ARE INSTALLED BETWEEN THE FLOOR SLAB AND 48" AFF THECONTRACTOR SHALL CONCRETE INCASE CONDUIT FROM THE FLOOR SLAB TO 48"AFF TO COMPLY WITH HAZARDOUS LOCATION REQUIREMENTS.
P12 ALL OWNER EQUIPMENT ROUGH-IN REQUIREMENTS SHALL COORDINATE WITH THEOWNER PRIOR TO ANY ROUGH-IN.
#
SCALE: 1/4" = 1'-0"
KITCHEN SECTION2
SCALE: 1/4" = 1'-0"
ENLARGED ELECTRICAL ROOM3
SCALE: NTS
FLOOR PLAN MEZZANIENE-POWER4
20 A.
20 A.
GROUPOF LIGHTFIXTURES
GROUPOF LIGHTFIXTURES
LASTGROUP
OF LIGHTFIXTURES
TOTAL CIRCUIT LENGTH
BRANCH PANEL
BRANCH PANEL
120 VOLTS 277 VOLTS
a - USING #12 AWG 90 FT. 180 FT.
b - USING #10 AWG 150 FT. 300 FT.
c - USING #8 AWG 250 FT. 450 FT.
d - USING #6 AWG 380 FT. 700 FT.
IF PANEL BOARD IS FEED FROM A TRANSFORMER LOCATED IN THE SAME ROOM AS THE PANEL.THE TOTAL LENGTH OF BRANCH CIRCUITS SHALL NOT EXCEED THE FOLLOWING:
THE ABOVE CIRCUIT LENGTHS ARE BASED ON 4% VOLTAGE DROP AT 16 AMPS LOAD AT THEEND OF THE CIRCUIT. SAME WIRE SIZE SHALL BE USED FOR THE ENTIRE CIRCUIT.
120 VOLTS 277 VOLTS
a - USING #12 AWG 75 FT. 180 FT.
b - USING #10 AWG 125 FT. 260 FT.
c - USING #8 AWG 205 FT. 420 FT.
d - USING #6 AWG 325 FT. 660 FT.
IF PANELBOARD IS FEED FROM A TRANSFORMER LOCATED REMOTELY FROM THE PANEL. THETOTAL LENGTH OF BRANCH CIRCUITS SHALL NOT EXCEED THE FOLLOWING:
THE ABOVE CIRCUIT LENGTHS ARE BASED ON 3% VOLTAGE DROP AT 16 AMPS LOAD AT THEEND OF THE CIRCUIT. SAME WIRE SIZE SHALL BE USED FOR THE ENTIRE CIRCUIT.
BRANCH CIRCUIT DEFINITION:CIRCUIT ORIGINATING FROM A 20 AMP CIRCUIT BREAKER IN A BRANCH PANEL AND ENDING ATTHE LAST DUPLEX OUTLET ON THE CIRCUIT OR ENDS AT THE LAST LIGHT FIXTURE.
GENERAL NOTES:
FIRE ALARM ANDGENERATOR
ANNUNCIATOR
COUNTERTOP ONLY
COUNTERTOP WITH BACKSPLASH
FIRE ALARM STROBE
AND HORN/STROBEDISCONNECT SWITCH (TYP)
ELECTRICAL PANELBOARD,FACP PANEL AND SECURITY
PANEL
48"-72"TO TOP
80" BOTTOM MIN.
96" TOP MAX.(MEASUREDFROM LENS)
18" MIN.
48" MAX.
ADA PUSH BUTTONS, LIGHTING
CONTROLS, FIRE ALARM PULLSTATIONS, AND CARD
ACCESS
60" DATA, PHONE, ANDELECTRICAL OUTLETS
4"
CASEWORK;BY OTHERS
LAY-IN OR HARD LID CEILING
4"
4"
FIRE ALARM BEAM DETECTOR
SMOKE AND HEATDETECTORS
SURFACE MOUNT CONDUITS ONSTRUCTURE. DO NOT PENDANT
MOUNTCONDUITS
DECK STRUCTURALJOIST OR BEAM
72" MAXTO TOP
30'-0" MAX
CEILING MOUNTEDFIRE ALARM STROBEAND HORN/STROBE
6" MAX (IF CLG ISLESS THAN 80")
1. MOUNT ALL OUTLETS, DEVICES, AND EQUIPMENT AT HEIGHTS INDICATED BELOW, UNLESS NOTED
OTHERWISE ON THE DRAWINGS. UNLESS NOTED OTHERWISE, HEIGHTS ARE GIVEN FROM FINISHED
FLOOR TO CENTER OF OUTLET BOX.
2. WHERE OUTLETS, DEVICES AND EQUIPMENT ARE NOTED BY THE SUBSCRIPT 'A', MOUNT AT 4" ABOVE
COUNTER. IF COUNTER HAS A BACK SPLASH, MOUNT AT 4" ABOVE BACK SPLASH. REFER TO
ARCHITECTURAL INTERIOR ELEVATIONS AND COORDINATE WITH CASEWORK SUPPLIER.
BEAM CLAMP, HANGER CLAMPOR APPROVED SUPPORT, AS REQUIRED
BY WEIGHT SUPPORTED
2 PIECE CHANNELCONDUIT CLAMP
UNISTRUT CHANNEL - SIZE ASREQUIRED BY WEIGHT SUPPORTED
ALL THREAD ROD-SIZE AS REQUIRED
RACEWAY 3/4" TO 6"(TYPICAL)
STRUCTURAL UNIT-(BEAM, JOIST, SLAB, ETC.)
NOTE:
TIE WIRE SHALL NOTBE USED AS A COMPONENTOF ANY RACEWAY HANGERSYSTEM.
RACEWAY, 3/4" THRU 6"
CONDUIT HANGER
STRUCTURAL UNIT
RACEWAY - 3/4" THRU 1"
STRUCTURAL UNIT
BEAM CLAMP OR HANGERCLAMP AS REQUIREDWEIGHT SUPPORTED
ALL THREAD-SIZEAS REQUIRED
BEAM CLAMP OR HANGERCLAMP AS REQUIRED BY
WEIGHT SUPPORTED
PROVIDE CONDUIT SUPPORTS INACCORDANCE WITH NEC SPACINGREQUIREMENTS FOR TYPE OFRACEWAY REQUIRED.
STEEL CITYNO. 7501BOX SUPPORT
AS REQUIRED FOR TYPEOF CONSTRUCTION
TYPICALOUTLET BOX
BARSTRAPS
BARSTRAPS
TYPICAL WALLOUTLET
BARSTRAPS
NOTES:
TYPICALOUTLET BOX
TYPICAL FOR WOOD AND METAL STUD ROUGH-IN.
PLASTER RINGS NOT SHOWN.
LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCHITECTURAL AND MECHANICAL DRAWINGS, AND
WITH ALL APPLICABLE SHOP DRAWINGS.
IN ACCORDANCE WITH UBC 4303 OUTLETS ON OPPOSITE SIDES OF WALLS OR PARTITIONS IN THE SAME
STUD SPACE MUST BE SEPARATED BY A MINIMUM OF 24" HORIZONTAL DISTANCE.
1.
2.
3.
4.
A1-40
A1-40/IG
PROVIDE 4"x4"x2-1/8" DEEP JUNCTION BOXWITH SINGLE GANG PLASTER RING ANDEXTEND 3/4" CONDUIT WITH NYLON PULLROPE TO ACCESSIBLE CEILING.TERMINATE CONDUIT IN CEILING SPACEWITH A NYLON BUSHING. CABLE TO BEPROVIDED BY OWNER.
ISOLATED GROUND CIRCUIT.
DESIGNATION OF CIRCUIT. WIRECOMPLETE.
NOTES:
1. SUPPORT FROM WALL 12 INCHES ABOVE FINISHED GRADE,
UNLESS NOTED OTHERWISE.
2. PROVIDE IN EACH NEW ELECTRICAL AND IT ROOM.
3. EXTEND ALL BUILDING MAIN GROUNDING CONDUCTOR TO
THE MAIN BUILDING GROUNDING BUS.
4. SEE SPECIFICATION SECTION 260452 FOR DETAILS.
1-1/2"
PLATESIDE VIEW
1"
1"
4"
2"
2"
1/4"
1"
2" TYP 8 PLCS
HOLE SIZE3/8"-16 TAPPED
STAMPED DESCRIPTION
XXXXXXXX GROUND SYSTEM
TO FLOOR/RACK GROUNDING
CAD-WELD CONNECTION (TYP.)
DI-ELECTRIC INSULATOR BOTH ENDS TOPANEL GROUND
COMPRESSIONLUG CONNECTED
PLATE SIZE4"x1/4"x18" COPPER
7/16 DIA. HOLEBOTH ENDS
CP 25WB CAULK ONBOTH SIDES OF WALL
DAMMING MATERIAL(BACKER ROD, FIBER-GLASS OR
MINERAL WOOL).
METAL PIPEOR CONDUIT
FIRE RATED CONCRETEWALL (SOLID OR BLOCK)
METALLIC CONDUIT
1/4" MINIMUM DIAMETER
BEAD OF 3M FIREBARRIER CP 25 CAULK
OR MP MOLDABLEPUTTY
1/4" MINIMUMDIAMETER BEAD OF3M FIRE BARRIER CP25 CAULK OR MPMOLDABLE PUTTY
STEEL STUD
GYPSUM BOARD
SOUND ATTENUATION INSULATION (STC WALLS)
NOTE:1. TYPICAL DETAILS SHOWING GENERAL FIRE STOPPING PROCEDURE. ACTUAL PROCEDURE DEPENDS UPON ANNULAR SPACE BETWEEN PIPE AND/OR INSULATION AND OPENING. FOLLOW MANUFACTURER'S INSTRUCTIONS.
2. FIRESTOP TESTED UP TO 4 HOURS IN ACCORDANCE WITH ASTM E 814 (UL 1479) & CAN/ULC S115.
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:42:0
6 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
EP501
POWER DETAILS
SCALE: NTS
TYPICAL DEVICE ELEVATION DETAIL1SCALE: NTS
MULTIPLE RACEWAY SUPPORT DETAIL2
SCALE: NTS
TYPICAL RACEWAY DETAIL3
SCALE: NTS
TYPICAL ROUGH-IN REQUIREMENTS4
SCALE: NTS
TYPICAL OUTLET CONVENTION5
SCALE: NTS
GROUNDING BUS DETAIL6
SCALE: NTS
TYPICAL CONCRETE WALL PENETRATION DETAIL7
SCALE: NTS
TYPICAL GYPBOARD WALL PENETRATION DETAIL8
SCALE: NTS
BRANCH CIRCUITING DETAIL9
ABBREVIATIONS:GENERAL NOTES:
1. THE DOOR DETAILS SHOWN BELOW ARE GENERAL ROUGH-IN DETAILS AND NOT ALL DEVICES SHOWN MAY BE PRESENT FOR
EACH DOOR. CONTRACTOR SHALL REFER TO THE DOOR HARDWARE SCHEDULE IN THE ARCHITECTS DRAWINGS AND SPECS
TO DETERMINE WHAT DEVICES ARE PRESENT FOR EACH DOOR REQUIRING CARD ACCESS DOOR EQUIPMENT.
2. NOT ALL DOOR STYLE DETAILS SHOWN BELOW MAY BE INCLUDED IN THE PROJECT.
3. ALL CONDUIT SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS.
4. THE DOOR ROUGH-IN INFORMATION SHOWN ON THESE DRAWINGS ARE SCHEMATIC IN NATURE AND CANNOT ACCOUNT FOR
ALL SPECIFIC VENDOR REQUIREMENTS, OR ACTUAL DOOR HARDWARE PROVIDED. COORDINATE SPECIFIC LOCATIONS WITH
SECURITY CONTRACTOR AND APPROVED DOOR HARDWARE SCHEDULES PRIOR TO ROUGH-IN. CONTRACTOR IS RESPONSIBLE
FOR A COMPLETE CONDUIT RACEWAY SYSTEM AT THE DOOR AND BACK TO LOCAL ELECTRICAL ROOM.
5. IF REX IS NOT INCLUDED IN DOOR HANDLE OR EXIT DEVICE, PROVIDE BOX FOR WALL MOUNTED REX DEVICE. VERIFY WITH
DOOR HARDWARE PRIOR TO ROUGH-IN.
6. PROVIDE CONDUIT AND DEVICE BACK BOX ROUGH-IN AT ALL CARD READER DOOR LOCATIONS. CONDUIT SHALL BE 3/4"
UNLESS OTHERWISE NOTED AND ALL BOXES SHALL BE 4 SQUARE WITH A SINGLE GANG MUD RING FOR DEVICES OR JUST A
SINGLE GANG BOX IF INSTALLED AT THE DOOR FRAME.
7. A SINGLE FIRE ALARM CONTROL MODULE MAY BE USED TO CONTROL THE POWER TO MULTIPLE DOORS IF COORDINATED
WITH THE ACCESS CONTROL SYSTEM VENDOR TO WIRE DOORS SEPARATE FROM OTHER DOORS TOGETHER ON THE SAME
POWER SUPPLY LOOP.
8. IF NO ACCESSIBLE CEILING SPACE IS NEAR THE CONTROLLED DOOR, ALL CONDUITS ARE TO BE RUN CONTINUOUS TO THE
DOOR ACCESS CONTROL PANEL UNLESS A LOCATION IS DETERMINED TO BE ACCEPTABLE TO THE ENGINEER PRIOR TO
INSTALLATION.
ACCESS CONTROL COORDINATION REQUIREMENTS:
CODE REFERENCES AND REQUIREMENTS:
2016 NFPA 101 - LIFE SAFETY CODE
• 7.2.1.5.6(5) REQUIRES THAT LOSS OF POWER WILL UNLOCK THE ELECTRICALLY CONTROLLED DOOR HARDWARE.• 7.2.1.6.2.(4) REQUIRES THAT ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM UNLOCK ALL DOORS LOCATED IN THE PATH OF EGRESS.2016 NFPA 80 - FIRE DOORS AND OTHER OPENING PROTECTIVES
• 6.1.3.4 REQUIRES THAT POWER OPERATED FIRE DOORS HAVE A RELEASING DEVICE TO AUTOMATICALLY RELEASE POWER UPON FIRE ALARM.• 6.4.4.3.3 REQUIRES THAT FIRE RATED DOORS BE POSITIVELY LATCHED TO MAINTAIN THE FIRE RATING, ALL ELECTRIC STRIKES USED IN FIRE RATED DOORS MUST BE FAIL SECURE.2012 IBC - INTERNATIONAL BUILDING CODE
• 1008.1.9.8 REQUIRES ELECTROMAGNETICALLY LOCKED DOORS HAVE A SENSOR RELEASE SWITCH EITHER AUTOMATIC OR BY A READILY ACCESSIBLE WALL MOUNTED PUSHBUTTON TO RELEASE THE LOCK.
INTEGRATION WITH FIRE ALARM
ALL MAGNETIC LOCKS SHALL BE UNLOCKED DURING A GENERAL FIRE ALARM. THIS ACTION IS NOT REQUIRED IF SYSTEM IS IN ALARM BY MEANS OF A MANUAL PULL STATION. AUTOMATIC DETECTION DEVICES SUCH AS SMOKE DETECTORS OR SPRINKLER FLOW REQUIRE UNLOCKING AND THE DOOR MUST REMAIN UNLOCKED UNTIL FIRE ALARM SYSTEM
RESET. CONTRACTOR SHALL INCLUDE ALL FIRE ALARM INTERFACE EQUIPMENT SUCH AS ADDRESSIBLE CONTROL MODULES OR BY CONTACT CLOSURE SIGNALING TO THE ACCESS CONTROL PANELS AS NECESSARY TO MEET THE CODE REQUIREMENTS. ALL DOORS IN STAIRWELLS MUST ALLOW FOR RE-ENTRY.
***TO ENSURE A COMPLETE AND OPERATING ACCESS CONTROL SYSTEM AND TO ELIMINATE DELAYS, INSUFFICIENT OR UNNECESSARY WORK BY ALL OF THE ENTITIES INVOLVED, THE FOLLOWING STEPS SHALL BE COMPLETED. THE FAILURE TO DO SO RESULTING IN ADDED COSTS AND LOST TIME WILL BE BORN SOLELY BY THE CONTRACTOR. NO
ADDITIONAL PAYMENTS WILL BE MADE BY THE OWNER TO COVER WORK DESCRIBED BELOW.***
DURING THE BIDDING PROCESS:
1. THE ELECTRICAL CONTRACTOR SHALL REVIEW THE FLOORPLAN DRAWINGS AND DETAILS ON THIS SHEET. THE FLOORPLANS WILL INDICATE WHICH DOORS HAVE ACCESS CONTROL EQUIPMENT REQUIRING ROUGH-IN. DEVICE LOCATIONS REQUIRING JUNCTION BOXES WILL BE SHOWN ON THE FLOORPLANS, BUT ALL CONDUIT AND HARDWARE
REQUIREMENTS CAN ONLY BE DETERMINED BY REFERRING TO THE SPECIFIC DOOR ROUGH-IN DETAILS AND THE ARCHITECTURAL DOOR HARDWARE SPECIFICATION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER FOR CLARIFICATION.
2. THE ELECTRICAL CONTRACTOR SHALL REVIEW THE ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE SPECIFICATIONS, AND DEFINED EGRESS PATHS. IDENTIFY ACCESS CONTROLLED DOORS LOCATED IN FIRE RATED WALLS AND IN PATHS OF EGRESS REQUIRING ADDITIONAL CONTROL DEVICES.
3. THE ELECTRICAL CONTRACTOR SHALL VERIFY WHICH DOORS USING AN ELECTRIFIED EXIT DEVICE WILL REQUIRE 120V AT THE DOOR. THIS IS MANUFACTURER SPECIFIC AND MUST BE CONFIRMED WITH THE GENERAL CONTRACTOR ACCORDING TO WHICH HARDWARE SUPPLIER BEING USED.
POST-BID, DURING THE SUBMITTAL PROCESS:
4. DURING THE SUBMITTAL PROCESS, THE ELECTRICAL CONTRACTOR SHALL REVIEW THE APPROVED DOOR HARDWARE SUBMITTAL TO CONFIRM THE THE FINAL HARDWARE SETS PRIOR TO ANY ROUGH-IN. ANY QUESTIONS SHALL BE ISSUED BY FORMAL RFI.
5. MEET WITH THE ACCESS CONTROL VENDOR TO REVIEW ALL FINAL INTEGRATION AND ROUGH-IN REQUIREMENTS. ONLY AFTER CONFIRMING THE FINAL DOOR HARDWARE AND ACCESS CONTROL SYSTEM REQUIREMENTS SHALL ANY ROUGH-IN WORK BEGINS.
AFF - ABOVE FINISHED FLOOR
AP - ACCESS CONTROL PANEL
CR - CARD READER
DHS - DOOR HARDWARE SUPPLIER
DPS - DOOR POSITION SWITCH
EPT - ELECTRIC POWER TRANSFER
ES - ELECTRIC STRIKE
MAG LOCK - MAGNETIC LOCK
RX - EXIT DEVICE
PB - DOOR RELEASE PUSH BUTTON
(MANUAL REX)
REX - REQUEST TO EXIT
RFI - REQUEST FOR INFORMATION
+42" A.F.F.
1" CONDUIT TO ACCESSIBLE CEILING
SPACE OR LOCAL COMMUNICATIONS
ROOM. REFER TO SPECIFICATIONS.
CARD READER
(EXTERIOR)
(IF PRESENT)
MAG LOCK
(IF PRESENT)
DOOR POSITION SWITCH
(IF PRESENT)
6"X6"X4" SQ JUNCTION BOX. MOUNT
JUNCTION BOX ABOVE DOOR IN THE
CEILING SPACE OF THE SECURE SIDE
(IF PRESENT)
(IF PRESENT)120V POWER
3/4" C.
3/4" C.
EPT OR POWER TRANSFER HINGE
COORDINATE MOUNTING HEIGHT
WITH DOOR/FRAME SUPPLIER
Z
FIRE ALARM CONTROL MODULE(AT FIRE RATED DOORS)
KEY PAD/
ELECTRIFIED EXIT DEVICEPOWER SUPPLY
(IF PRESENT)
ELECTRIC STRIKE(IF PRESENT)
(IF PRESENT)
+42" A.F.F.
3/4" C.
ELECTRIFIED EXIT DEVICEPOWER SUPPLY
ADA ACTIVATIOR
(INTERIOR)
6"X6"X4" SQ JUNCTION BOX. MOUNT
JUNCTION BOX ABOVE DOOR IN THE
CEILING SPACE OF THE SECURE SIDE
1" CONDUIT TO ACCESSIBLE CEILING
SPACE OR LOCAL COMMUNICATIONS
ROOM. REFER TO SPECIFICATIONS.
(IF PRESENT)
DOOR POSITION SWITCH
(IF PRESENT)
AUTO OPERATOR
120V POWER 3/4" C.
(IF PRESENT)
(IF PRESENT)
EPT OR POWER TRANSFER HINGE
COORDINATE MOUNTING HEIGHT
WITH MANUFACTURER
3/4" C.
CARD READER
(EXTERIOR)
(IF PRESENT)
ADA ACTIVATIOR
(EXTERIOR)
(IF PRESENT)
(IF PRESENT)120V POWER
Z
FIRE ALARM CONTROL MODULE(AT FIRE RATED DOORS)
Z
FIRE ALARM CONTROL MODULE(AT FIRE RATED DOORS)
KEY PAD/
MULLION
(REMOVABLE)
ELECTRIC STRIKE (IF PRESENT)
3/4" C.
+42" A.F.F.
3/4" C.
AUTO OPERATOR
ADA ACTIVATIOR
(INTERIOR)
(IF PRESENT)
ADA ACTIVATIOR
(EXTERIOR)
(IF PRESENT)
3/4" C.
120V POWER
845 South 220 EastOrem, UT 84058
Phone: 801.229.0088 Fax: 801.229.0089www.sandstromarchitecture.com
DRAWN BY
CHECKED BY
DATE
PROJECT NO.
SHEET NUMBER
SHEET DESCRIPTION
DATE REVISION/ISSUE
2/2
3/2
01
7 5
:42:1
3 P
MC
:\R
evi
t 20
17
Lo
ca
l F
iles\2
01
6-2
01
_E
LE
C-C
EN
TR
AL_1
7V
_Ale
xEcto
n.r
vt
NE
W P
RO
VO
TR
AN
SP
OR
TA
TIO
N F
AC
ILIT
YP
RO
VO
SC
HO
OL D
IST
RIC
T
11
00
EA
ST
13
20
SO
UT
HP
RO
VO
, U
T 8
46
06
SA-1610
02/23/2016
Author
Checker
EP502
DOOR SECURITY DETAILS
SCALE: 12" = 1'-0"
ELECTRIFIED EXIT DEVICE1
SCALE: 12" = 1'-0"
DOUBLE DOOR WITH ELECTRIFIED EXIT
DEVICE AND ADA AUTO OPERATOR2
SCALE: 12" = 1'-0"
BRANCH CIRCUITING DETAIL3
ABBREVIATIONS:GENERAL NOTES:
1. THE DOOR DETAILS SHOWN BELOW ARE GENERAL ROUGH-IN DETAILS AND NOT ALL DEVICES SHOWN MAY BE PRESENT FOR
EACH DOOR.