24
Linear Heat Detection
Transcript
Page 1: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Linear Heat Detection

Page 2: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Temperature Related Risk Protection

• Data supplied by fire insurance companies indicates that most industrial fires are caused by

- Friction heat & sparks- Overheating of equipment

- Spontaneous combustion- Oil & oil fired equipment

Page 3: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

What is Linear Heat Detection?

• Continuous heat detector in the form of a cable

- Alarmline Analogue: averaging heat detector- Alarmline Digital: fixed temperature heat detector

Page 4: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Analogue LHD Cable

• Definition:- Multi-conductor cable containing insulators whose

resistance varies proportionately to changes in temperature

- Re-settable provided temperature does not exceed burn-off point of PVC coating

- Alarm level adjusted via controller

Page 5: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Alarmline Analogue LHD Cables

• High resistance - standard applications

• Nylon extruded - chemical resistance

• Bronze braided - increased mechanical protection over standard blue

• Stainless Steel braided over nylonextrusion - offshore applications

Page 6: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

LHD 4 Controller

K82012 K82194

Page 7: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

LHD 4 Controller

• Features- Alarm level adjusted via moveable link- Open circuit and closed circuit fault monitoring- Fire and fault output to conventional fire alarm panels- Volt-free relay option for analogue addressable fire

alarm panels- Eurocard 19” rack option

Page 8: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

AlarmlineNomogram

- Select the sensor cable length being used (D)100m

- Mark the Max Temperature where an alarm must not be given (B) 45 degrees

- Draw a line from point on “D” through point on “B” to the switch setting line (A). This is the switch setting that will not give a false alarm at the Max ambient temperature

Page 9: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

AlarmlineNomogram

-In the event of a hot spot occuring, it can be shown how hot this would need to be to give an alarm for a given length

- 10 metre length = 83 degrees

- 1 metre length =120 degrees

Page 10: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Digital LHD Cable

• Definition:- A cable which contains an insulator which melts at a

specific temperature- Switch output provided once alarm temperature

reached- Not re-settable

Page 11: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Alarmline Digital LHD Cables• Polythene braid 70º C

• Nylon over sheath 70º C

• Polythene braid 90º C

• Nylon over sheath 90º C

• PVC 113º C

• PVC 180º C

• Fluoropolymer 238º C

Page 12: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Alarmline Digital Control Units

• Firebeta 2 to 12 zone conventional panel with optional extinguishant release module

• Any other conventional fire alarm panel and/or extinguishant release module (retrofit)

Page 13: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Alarmline LHD - Advantages

• Flexible- Mechanically- Electrically

• Durable- Wide range of casings / braiding- Operating range -65º to +200º C- Unaffected by operating environment

Page 14: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Analogue & Digital Properties

Alarmline Analogue Alarmline DigitalAnalogueRecoverableOpen & short circuit fault detectionMin Operating Temp -65° CMin Alarm Temp 35° CMax Alarm Temp 105° CMax recoverable Alarm Temp 150° CMax length 1000m

DigitalNon-recoverableOpen circuit fault detection

Min Operating Temp -65° CMin Alarm temp 61° CMax Alarm Temp 238° CN/A

Max length 10,000m

Page 15: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Sensor Clips

Edge clip

Sensor cable

Neoprene sleeveCable tie

‘V’ Clip

Sensorcable

Neoprenesleeve

Page 16: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Applications

• Heavy industry

• Warehousing / storage tanks

• Conveyors and escalators

• Cable trays

• Floor & ceiling voids

• Tunnels

• Car parks

Page 17: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Applications - Case Study 1

• Electricity generation

- Cable trays and risers- Boiler fronts- Conveyors- Cooling towers- Transformers

Page 18: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Applications - Case Study 2

• Warehousing and bulk storage

- Alarmline Digital cable with conventional control unit or- Alarmline Analogue high resistance / Nylon extruded

cable with LHD 4 controller- Fixing clips as required

- “T” Clips- Edge connectors- Cable tray fixings

Page 19: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Racking

Sensor Cable

Page 20: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Trays

Traywork width 600mm maximum

Sensor cable

Powercables

Sensorsupports

Page 21: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Applications - Case Study 3

• Conveyors and escalators- Alarmline Analogue bronze braided cable- Sensor Pads Bronze Braided- Series 4 LHD Control Unit- Alarmline Digital Cable- Conventional control unit- Clips & Brackets to match site requirements

Page 22: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Conveyor

Heat sensingcable Idle rollers

Conveyor Belt

Conveyor return

Page 23: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

Escalators

Sensor Pad

LHD Bronze Braided sensor cable

Page 24: Linear Heat Detection. Temperature Related Risk Protection Data supplied by fire insurance companies indicates that most industrial fires are caused by.

International Approvals

Alarmline (Analogue) Alarmline (Digital)

UK power generation- 5117 P 11- EPA 022/215

Factory Mutual- OB 9A2.AY- OR 5A4.AY

Chinese Fire Officers- MAAL 96652

Chinese Power Generation- NSTCFEPQ (Appr) 92005

German VdS (1995)

UK power Generation- EPA 019-021- EPA 206/220

Factory Mutual- OD 6A9.AY- 300 5155- 300 3834

Chinese Fire Officers- MAAL 96652- 300 8312- 300 8933