+ All Categories
Home > Documents > Linear recessed and surface lighting

Linear recessed and surface lighting

Date post: 11-Sep-2021
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
228
Linear recessed and surface lighting
Transcript
Page 1: Linear recessed and surface lighting

Linear recessed and surface lighting

B Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting

Page 2: Linear recessed and surface lighting

Linear recessed and surface lighting

CComprehensive lighting catalog 7th Edition

Section 4

Page 3: Linear recessed and surface lighting

Linear recessed and surface lighting

D Philips Lightolier For complete specif ication information visit www.lightolier.com

Page 4: Linear recessed and surface lighting

Linear recessed and surface lighting

4.1Comprehensive lighting catalog 7th Edition

Philips Lightolier has a rich heritage of providing innovative, high quality recessed and surface lighting solutions for commercial, industrial and institutional markets. The line encompasses a diverse range of products, each designed to answer a specific lighting need. From the most comprehensive recessed soft lighting coffer styled direct/indirect luminaires in the industry to innovative medical patient room lighting and parabolics designed for illuminating computer screens properly, Philips Lightolier features

only energy-efficient products that provide effective, glare-free illumination to achieve the highest quality visual environment possible. Philips Lightolier works constantly to develop innovative new products and ensure that each new luminaire meets the most demanding specifications. Carefully designed around the light source, Philips Lightolier recessed and surface products ensure you the best luminaire for the task at hand. Highlighted here are just some of the products that showcase our design abilities.

Recessed soft lighting > 4.2 Recessed & wall washing > 4.90 Medical luminaires > 4.135 Architectural & surface utility > 4.146 Task lighting > 4.167 Special purpose & industrial > 4.172 General utility > 4.202

Innovative specification grade fixtures utilizing today’s most energy efficient light sources.

Contents

Page 5: Linear recessed and surface lighting

Linear recessed and surface lighting

4.2 Philips Lightolier For complete specif ication information visit www.lightolier.com

Recessed soft lighting

Gain a broader perspective with Soft Lights. Soft Lights encompasses a full range of luminaires, including decorative round, low-glare, recessed, non-directional recessed, solutions for shallow plenums, and more. Every Soft Lights luminaire enhances the quality of the visual environment by embracing the principles of quality visual concepts.

Page 6: Linear recessed and surface lighting

Linear recessed and surface lighting

4.3Comprehensive lighting catalog 7th Edition

LED recessed luminaires > 4.4 HP90 family > 4.8 Paraplus II > 4.20 Opalescent family > 4.24 Skyway family > 4.30 Aletta > 4.36

Alter family > 4.38 Alter concept > 4.64 Coffaire family > 4.74 DL Day lighting system > 4.88

Contents

Page 7: Linear recessed and surface lighting

4.4 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Recessed 2' x 2' LED luminairesProviding illumination virtually indistinguishable from traditional technologies while consuming less energy.

The Philips Lightolier LED recessed luminaire , designed specifically around the led light source, sets a new standard for lighting efficiency, performance and sustainability. With our versatile offering of both contemporary and classical shielding appearances, lighting designers and architects have the ability to utilize a LED light source in any environment. Our LED product families, provide an ideal energy saving fixture for all 2' x 2’ recessed T-bar grid and drywall applications.

Construction•FieldreplaceableLEDarrayaccessible

from below.•Integratedthermalmanagement

system conducts heat away from LEDs and transfers it to the surrounding environment. Designed to keep LEDs below specif ied maximum temperatures in typical commercial installations.

•Depth=5"

Electrical system•Integral,highefficiency

driver and power supply.•Nominalpowerfactor=0.9.•Inputvoltage=120V-277V,

50/60Hz

LED FactsLEDs have no breakable glass, their solid-state design renders them impervious to shock, vibration, frequent switching and environmental extremes. With an average lifespan of more than 50,000 hours, these maintenance-free LED luminaires eliminate repeated relamping, and operate in ambient room temperatures of -22°F to +104°F [-30°C to +40°C].

•LEDscontainnotoxicmaterials, hazardous mercury, or halogen gases.

•LEDsemitnoultraviolet(UV)raysorinfrared(IR)radiation.

•LEDsdonotrequireamaterial safety data sheet (MSDS)orhazardouswaste disposal.

•LEDsdonotproduceelectro-magnetic interference.

Page 8: Linear recessed and surface lighting

4.5Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

24" (610mm)

5"(127mm)

Opalescent LED 2' x 2'Direct recessed air handling or static luminaires

Opalescent 2x2 LED’s deep curved lens combined with a regressed frame opening that appears as a cove or skylight. The opal lens subtly highlights the ceiling plenum while shielding the LED’s from direct view. Opalescent blends with any architectural environment and creates balanced brightness, illuminating both vertical and horizontal surfaces.

Features•Boldbutsimple2½"regressedframewith

contoured lens.•Highlighttransmissionfrostwhiteacryliclens.•Canprovide48initialfootcandlesat0.56wattsper

square foot.•Delivers3619lumenswithjust44.9inputwatts.•FieldreplaceableLEDarrayanddriversaccessible

from below.•Integratedthermalmanagementsystemconductsheat

away from LEDs and transfers it to the surrounding environment.

•Factorycalibratedintelligentdrivercapableofprovidingvarious lumen outputs to balance energy savings with lighting application needs.

•HighefficiencyLEDshave50,000hourratedlifeatL70.•PredictedL70lifetimeisbasedonLEDmanufacturer’s

supplied LM-80 data and in-situ laboratory testing.•Truemiteredcornerlensframe.•Doorjambfinishedblackonfoursidesforpositive

light stop.•Springloadedroosterheadlatches.•18gaugesteelhinges.•5"deepbody.•BlackbodytodissipateheatfromLEDs.•Earthquake/Hold-downclips.•Hemmedoversiderailsformaximumsafety.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.•Notforcontinuousrowmounting.•Five-yearwarrantyonluminaire,LEDboardsanddriver.

Options & accessoriesDrywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical wiring options: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C.

OPS22GPW38A40ULAG

30˚

60˚550

1100

1650

Candlepower CurveReference data

Delivered lumens 3619 Eff iciency lm/w 80.6

LED Driver

Inputwatts(120V) 44.9W

Opalescent Lens shielding Lumen 1 Color temp 1,2 Voltage Driver 2 Options LED PW=Highlight 25A=25klm 40=4000K UNV = LAG = Seepage4.5 Direct transmission frost 33A=33klm 120-277V LEDDriver Recessed white acrylic lens. 38A=38klm 42A=42klm

1.Approximatedeliveredvalues(ConsultIESf ile). 2. Consult representative for other color temperature options and driver dimming options.

PWOPS22G 40Example

Ordering information

Type Size Delivered lumens

Input watts

Lumens per watt

Avg 8'x10' initial footcandles*

8'x10' Watts per sq. foot Catalog no.

Static 2' x 2'

2553316736194140

30.438.444.952.8

84.082.580.678.4

34424855

0.380.400.560.66

OPS22GPW25A40ULAGOPS22GPW33A40ULAGOPS22GPW38A40ULAGOPS22GPW42A40ULAG

For Air handling housing models substitute OPS22 for OPA22.* 42 Recessed LED Luminaires in a 60' x 56' x 9' room with a reflectance of 80/50/20, placed 8' x 10' on center. Footcandlereadingsaretaken2½'fromfloorlevel.

U LAG

Page 9: Linear recessed and surface lighting

4.6 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

24" (610mm)

5"(127mm)

Skyway LED 2' x 2'Direct recessed air handling or static luminaires

Skyway 2x2 LED’s modern triple lens design features a clear conical prismatic center lens complemented by frosted white acrylic side lenses. Alternating lens textures creates visual interest while shielding the LEDs from direct view and preventing pixilation. The soft, balanced, uniform brightness of Skyway make it ideal for office, institution and healthcare applications.

Features•Aestheticallypleasingtriplelensdesign.•Curvedhighlighttransmissionfrostwhiteacrylic

side lenses.•Clearacrylicconicalprismaticcenterlens.•Canprovide45initialfootcandlesat0.56wattsper

square foot.•Delivers3366lumenswithjust44.9inputwatts.•FieldreplaceableLEDarrayanddriversaccessiblefrom

below.•Integratedthermalmanagementsystemconductsheat

away from LEDs and transfers it to the surrounding environment.

•Factorycalibratedintelligentdrivercapableofprovidingvarious lumen outputs to balance energy savings with lighting application needs.

•HighefficiencyLEDshave50,000hourratedlifeatL70.•PredictedL70lifetimeisbasedonLEDmanufacturer’s

supplied LM-80 data and in-situ laboratory testing.•BlackbodytodissipateheatfromLEDs.•5"deepbody.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Earthquake/Hold-downclips.•Doorjambfinishedblackonfoursidesforpositive

light stop.•Truemiteredcorneraluminumlensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.•Notforcontinuousrowmounting.•Five-yearwarrantyonluminaire,LEDboardsanddriver.

Options & accessoriesDrywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical wiring options: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C.

SKS22GPK33A40ULAG

30˚

60˚600

1200

1800

Candlepower CurveReference data

Delivered lumens 3366 Eff iciency lm/w 75.0

LED Driver

Inputwatts(120V) 44.9W

Skyway Lens shielding Lumen 1 Color temp 1,2 Voltage Driver 2 Options LED PW=Pattern 25A=25klm 40=4000K UNV = LAG = Seepage4.6 Direct 19, 0.156 virgin 33A=33klm 120-277V LEDDriver Recessed acrylic center lens 38A=38klm with frost white acrylic side lenses. PP=Frostwhite acrylic center lens with frost white acrylic side lenses.

1.Approximatedeliveredvalues(ConsultIESf ile). 2. Consult representative for other color temperature options and driver dimming options.

SKS22G 40Example

Ordering information

Type Size Delivered lumens

Input watts

Lumens per watt

Avg 8'x10' initial footcandles*

8'x10' Watts per sq. foot Catalog no.

Static 2' x 2'238133663851

30.444.952.8

78.375.072.9

324552

0.380.560.66

SKS22GPK25A40ULAGSKS22GPK33A40ULAGSKS22GPK38A40ULAG

ForAirhandlinghousingmodelssubstituteSKS22forSKA22.* 42 Recessed LED Luminaires in a 60' x 56' x 9' room with a reflectance of 80/50/20, placed 8' x 10' on center. Footcandlereadingsaretaken2½'fromfloorlevel.

U LAG

Page 10: Linear recessed and surface lighting

4.7Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

24" (610mm)

5"(127mm)

SpecPlus LED 2' x 2'Direct recessed static luminaires

Easily transition into the new era of the Green office with the SpecPlus LED 2x2 lensed troffer.SpecPlusLEDoffersa1/2"regressedextrudedaluminumframewithspringloadedlatches.The9/16"wideframetrimgivesa500squareinchaperture.Thelensisextrudedacrylic,squarebasemaleconicalprismof.156"overallthickness.Providingexcellentobscuration of the light source while controlling volumetric illumination.

Features•Prismaticacryliclens.•FlatsteelDoorframewith500squareinchlensopening.•Canprovide52initialfootcandlesat0.56wattsper

square foot.•Delivers3860lumenswithjust44.9inputwatts.•FieldreplaceableLEDarrayanddriversaccessible

from below.•Integratedthermalmanagementsystemconductsheat

away from LEDs and transfers it to the surrounding environment.

•Factorycalibratedintelligentdrivercapableofprovidingvarious lumen outputs to balance energy savings with lighting application needs.

•HighefficiencyLEDshave50,000hourratedlifeatL70.•PredictedL70lifetimeisbasedonLEDmanufacturer’s

supplied LM-80 data and in-situ laboratory testing.•BlackbodytodissipateheatfromLEDs.•5"deepbody.•Earthquake/Hold-downclips.•Hemmedoversiderailsformaximumsafety.•Springloadedroosterheadlatches.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.•Notforcontinuousrowmounting.•Five-yearwarrantyonluminaire,LEDboardsanddriver.

Options & accessoriesDrywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical wiring options: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C.

SPS22GFSKA38A40ULAG

30˚

60˚700

1400

2100

Candlepower CurveReference data

Delivered lumens 3621 Eff iciency lm/w 85.5

LED Driver

Inputwatts(120V) 44.9W

SpecPlus Lens frame Lens shielding Lumen 1 Color temp 1,2 Voltage Driver 2 Options LED FS=Flatsteelframe KA=0.156prismatic 25A=25klm 40=4000K UNV = LAG = Seepage4.7 Direct FA=Flatalum.frame acryliclens 33A=33klm 120-277V LEDdriver recessed RA=Regressed VA= 0.095prismatic 38A=38klm aluminum. frame acrylic lens 42A=42klm

1.Approximatedeliveredvalues(ConsultIESf ile). 2. Consult representative for other color temperature options and driver dimming options.

PWSPS22G 40Example

Ordering information

Type Size Delivered lumens

Input watts

Lumens per watt

Avg 8'x10' initial footcandles*

8'x10' Watts per sq. foot Catalog no.

Flat steel/aluminum Door frame with KA lens

Static 2' x 2'

2565315836214140

30.038.444.952.8

84.482.580.678.4

35435057

0.380.480.560.66

SPS22GFSKA25A40ULAGSPS22GFSKA33A40ULAGSPS22GFSKA38A40ULAGSPS22GFSKA42A40ULAG

U LAG

Flat steel/aluminum Door frame with VA lens

Static 2' x 2'

2722336238414397

30.038.444.952.8

89.587.685.583.3

36455259

0.380.480.560.66

SPS22GFSVA25A40ULAGSPS22GFSVA33A40ULAGSPS22GFSVA38A40ULAGSPS22GFSVA42A40ULAG

Regressed aluminum Door frame with KA lens

Static 2' x 2'

2598319436814199

30.038.444.952.8

85.583.482.079.5

35445058

0.380.480.560.66

SPS22GRAKA25A40ULAGSPS22GRAKA33A40ULAGSPS22GRAKA38A40ULAGSPS22GRAKA42A40ULAG

Regressed aluminum Door frame with VA lens

Static 2' x 2'

2729335838604397

30.038.444.952.8

89.887.786.083.3

37455259

0.380.480.560.66

SPS22GRAVA25A40ULAGSPS22GRAVA33A40ULAGSPS22GRAVA38A40ULAGSPS22GRAVA42A40ULAG

* 42 Recessed LED luminaires in a 60' x 56' x 9' room with a reflectance of 80/50/20, placed 8' x 10' on center. Footcandlereadingsaretaken2½'fromfloorlevel.

Page 11: Linear recessed and surface lighting

4.8 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

HP90Direct/indirect recessed luminaires

Page 12: Linear recessed and surface lighting

4.9Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

HP90Direct/indirect recessed luminaires

TheHP90familycontinuestogrow.NowofferedinT5orT8lampingaswellasairsupplyand return capabilities. It's an excellent choice when choosing an architectural designed luminaire for LEED compliant office space. HP90 combines a recessed contoured body with an enclosed linear prismatic lens to create an efficient direct/indirect luminaire. HP90 will illuminate both vertical and horizontal surfaces creating balanced brightness.

Page 13: Linear recessed and surface lighting

4.10 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

5" (127mm)

5"(127mm)

24" (610mm)

HP90 T5 2' x 4'Direct/indirect recessed static luminaires

HP90 combines a recessed contoured body with an enclosed linear prismatic lens to create a 90.4% efficient direct/indirect luminaire. HP90 has an excellent spacing ratio of 1.4 and will illuminate both vertical and horizontal surfaces creating balance brightness while consuming only .63 watts per square foot. It is available in 2' x 4', 2' x 2' and 1' x 4' sizes utilizing T5 lamps. An excellent choice when choosing an architectural designed luminaire for LEED compliant office spaces. The construction pays attention to fit and finish.

Features•Canprovide54.6maintainedfootcandlesofbalanced

brightness illumination at only .68 watts per square foot.•87.2%efficientsinglelamp28WT52'x4'luminaire.•90.4%efficienttwolamp28WT52'x4'luminaire.•84.6%efficienttwolamp54WT5HO2'x4'luminaire.•Direct/indirectappearancewithsoftcontouredinterior.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceilingtypes.•Lampshieldopensfromeitherside.•95%reflectivespecularaluminumreflector.•Ballastaccessiblefromroomside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•OptionalDALIballastiGENtechnologyacceptsdigital

dimming commands from computers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

Options & accessories page 4.130Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat white acrylic enamel. Rust preventive undercoating. Reflector – low iridescence specular aluminum 95% reflectance.

Ballast type <10THD

Electronic T5 program start PGElectronic T5 28W instant start WA*†

Electronic T5 28W bi-level step ballast VY (2lamp)DALIBallast DA

*Ballast(WA)onlyavailablein120or277volt.†56Inputwatts0.93B.F.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

H9S2GLR228120WA

30˚

60˚550

1100

1650

Candlepower CurveReference data

Efficiency 90.4% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 54.6W Ballastfactor 0.93

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.10 See page 4.10 Recessed 277=277V andpage4.130 UNV=120-277V

120H9S2GLR228 AWAExample

H9S2GLR254UNVPG

30˚

60˚800

1600

2400

Candlepower CurveReference data

Efficiency 84.6% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 112.4W Ballastfactor 1.0

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.10 See page 4.10 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S2GLR254 APGExample

H9S2GLR128UNVPG

30˚

60˚300

600

900

Candlepower CurveReference data

Efficiency 87.2% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 31.6W Ballastfactor 1.0

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.10 See page 4.10 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S2GLR128 APGExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T5 28W H9S2GLR228

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T5HO 54W H9S2GLR254

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 1-T5 1-T5HO

28W 54W

H9S2GLR128 H9S2GLR154

5" (127mm)

5"(127mm)

24" (610mm)

5" (127mm)

5"(127mm)

24" (610mm)

Page 14: Linear recessed and surface lighting

4.11Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

5" (127mm)

5"(127mm)

24" (610mm)

HP90 T5 2' x 2'Direct/indirect recessed static luminaires

HP90 combines a recessed contoured body with an enclosed linear prismatic lens to create an efficient direct/indirect luminaire.

Features•72.9%efficientsinglelamp40WtwintubeT52'x2'

luminaire.•83.2%efficientonelamp14WT52'x2'luminaire.•80.3%efficienttwolamp24WT5HO2'x2'luminaire.•Direct/indirectappearancewithsoftcontouredinterior.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceilingtypes.•Lampshieldopensfromeitherside.•95%reflectivespecularaluminumreflector.•Ballastaccessiblefromroomside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•OptionalDALIballastiGENtechnologyacceptsdigital

dimming commands from computers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

Options & accessories page 4.130Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat white acrylic enamel. Rust preventive undercoating. Reflector – low iridescence specular aluminum 95% reflectance.

Ballast type <10THD <20THD

Electronic T5 program start PG –Electronic TT5 40W PR* –Electronic TT5 40W IB SBElectronic TT5 50W BP –Electronic TT5 55W BF –Electronic T5 14W bi-level VY – stepballast(2lamp)DALIBallast DA –

* Program start.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

H9S2GLR1FTUNVPR

30˚

60˚300

600

900

Candlepower CurveReference data

Efficiency 72.9% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 37.6W Ballastfactor 1.0

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.11 See page 4.11 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S2GLR1FT AIBExample

H9S2GLR224UNVPG

30˚

60˚300

600

900

Candlepower CurveReference data

Efficiency 80.3% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 49.4W Ballastfactor 1.0

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.11 See page 4.11 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S2GLR224 APGExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 1-TT5 40W H9S2GLR1FT

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-T5 2-T5HO

14W 24W

H9S2GLR214 H9S2GLR224

5" (127mm)

5"(127mm)

24" (610mm)

Page 15: Linear recessed and surface lighting

4.12 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

5"(127mm)

11 15�16 (303mm)

5"(127mm)

11 15�16 (303mm)

HP90 T5 1' x 4'Direct/indirect recessed static luminaires

HP90 combines a recessed contoured body with an enclosed linear prismatic lens to create an efficient direct/indirect luminaire.

Features•86.9%efficientonelamp28WT51'x4'luminaire.•88.9%efficienttwolamp28WT51'x4'luminaire.•86.5%efficienttwolamp54WT5HO1'x4'luminaire.•Direct/indirectappearancewithsoftcontouredinterior.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceilingtypes.•Lampshieldopensfromeitherside.•95%reflectivespecularaluminumreflector.•Ballastaccessiblefromroomside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•OptionalDALIballastiGENtechnologyacceptsdigital

dimming commands from computers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

Options & accessories page 4.130Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat white acrylic enamel. Rust preventive undercoating. Reflector – low iridescence specular aluminum 95% reflectance.

Ballast type <10THD

Electronic T5 program start PGElectronic T5 28W instant start WA*† Electronic T5 28W bi-level step ballast VY (2lamp)DALIBallast DA

*Ballast(WA)onlyavailablein120or277volt.†56Inputwatts0.93B.F.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing)

H9S1GLR228UNVPG

30˚

60˚600

1200

1800

Candlepower CurveReference data

Efficiency 88.9% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 63.3W Ballastfactor 1.0

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.12 See page 4.12 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S1GLR228 APGExample

H9S1GLR128UNVPG

30˚

60˚250

500

750

Candlepower CurveReference data

Efficiency 86.9% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 32.6W Ballastfactor 1.0

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.12 See page 4.12 Recessed 277=277V andpage4.130 UNV=120-277V

120H9S1GLR128 APGExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4' 2-T5 2-T5HO

28W 54W

H9S1GLR228 H9S1GLR254

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4' 1-T5 1-T5HO

28W 54W

H9S1GLR128 H9S1GLR154

Page 16: Linear recessed and surface lighting

4.13Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

5" (127mm)

5"(127mm)

24" (610mm)

5" (127mm)

5"(127mm)

24" (610mm)

HP90 T8 2' x 4'Direct/indirect recessed static luminaires

HP90 T8 combines a recessed contoured body with an enclosed linear prismatic lens to create a 85.2% efficient direct/indirect luminaire. HP90 has an excellent spacing ratio of 1.4 and will illuminate both balanced vertical and horizontal surfaces creating balance brightness. It is available in 2' x 4', 2' x 2' and 1' x 4' sizes utilizing T8 lamps. An excellent choice when choosing an architectural designed luminaire for LEED compliant office spaces. The construction pays attention to fit and finish.

Features•85.2%efficientsinglelamp32WT82'x4'luminaire.•85.2%efficienttwolamp32WT82'x4'luminaire.•Direct/indirectappearancewithsoftcontouredinterior.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceilingtypes.•Lampshieldopensfromeitherside.•95%reflectivespecularaluminumreflector.•Ballastaccessiblefromroomside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•OptionalDALIballastiGENtechnologyacceptsdigital

dimming commands from computers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

Options & accessories page 4.130Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat white acrylic enamel. Rust preventive undercoating. Reflector – low iridescence specular aluminum 95% reflectance.

Ballast type <10THD <20THD

ElectronicT8(1or2lamp) HI* SO*ElectronicT8(1or2lamp) P2** –LOL Dimming T8 PS –Electronic T8 32W bi-level V2 – stepballast(2lamp)DALIBallast DA –

* Instant start. Standard.

** Program start.

DALI=digitaladdressabledimming

Other dimming options consult factory.Note: For T8 UNV, you must use HI or P2 ballast code.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing)

H9S2GLR232UNVHI

30˚

60˚550

1100

1650

Candlepower CurveReference data

Efficiency 85.2% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 59.7W Ballastfactor 0.88

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.13 See page 4.13 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S2GLR232 AHIExample

H9S2GLR132UNVHI

30˚

60˚300

600

900

Candlepower CurveReference data

Efficiency 85.2% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 31.2W Ballastfactor 0.88

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.13 See page 4.13 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S2GLR132 AHIExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T8 32W H9S2GLR232

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 1-T8 32W H9S2GLR132

Page 17: Linear recessed and surface lighting

4.14 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

5" (127mm)

5"(127mm)

24" (610mm)

5" (127mm)

5"(127mm)

24" (610mm)

HP90 T8 2' x 2'Direct/indirect recessed static luminaires

HP90 T8 combines a recessed contoured body with an enclosed linear prismatic lens to create an efficient direct/indirect luminaire.

Features•82.5%efficientonelamp17WT82'x2'luminaire.•80.3%efficienttwolamp17WT82'x2'luminaire.•Direct/indirectappearancewithsoftcontoured

interior.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceilingtypes.•Lampshieldopensfromeitherside.•95%reflectivespecularaluminumreflector.•Ballastaccessiblefromroomside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•OptionalDALIballastiGENtechnologyacceptsdigital

dimming commands from computers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

Options & accessories page 4.130Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat white acrylic enamel. Rust preventive undercoating. Reflector – low iridescence specular aluminum 95% reflectance.

Ballast type <10THD <20THD

ElectronicT8(1or2lamp) HI*, P2** SO*LOL Dimming T8 PS –DALIBallast DA –

* Instant start. Standard.

** Program start.

DALI=digitaladdressabledimming

Other dimming options consult factory.

Note: For T8 UNV, you must use HI or P2 ballast code.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing)

H9S2GLR217UNVHI

30˚

60˚250

500

750

Candlepower CurveReference data

Efficiency 80.3% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 30.6W Ballastfactor 0.88

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.14 See page 4.14 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S2GLR217 AHIExample

H9S2GLR117UNVHI

30˚

60˚120

240

360

Candlepower CurveReference data

Efficiency 82.5% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 16.7W Ballastfactor 0.88

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.14 See page 4.14 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S2GLR117 AHIExample

Emergency Pack

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-T8 17W H9S2GLR217

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 1-T8 17W H9S2GLR117

Page 18: Linear recessed and surface lighting

4.15Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

HP90 T8 1' x 4'Direct/indirect recessed static luminaires

HP90 T8 combines a recessed contoured body with an enclosed linear prismatic lens to create an efficient direct/indirect luminaire.

Features•77.8%efficientonelamp32WT81'x4'luminaire.•78.4%efficienttwolamp32WT81'x4'luminaire.•Direct/indirectappearancewithsoftcontoured

interior.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceilingtypes.•Lampshieldopensfromeitherside.•95%reflectivespecularaluminumreflector.•Ballastaccessiblefromroomside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•OptionalDALIballastiGENtechnologyacceptsdigital

dimming commands from computers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

Options & accessories page 4.130Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat white acrylic enamel. Rust preventive undercoating. Reflector – low iridescence specular aluminum 95% reflectance.

Ballast type <10THD <20THD

ElectronicT8(1or2lamp) HI*, P2** SO*LOL Dimming T8 PS –Electronic T8 32W bi-level V2 – stepballast(2lamp)DALIBallast DA –

* Instant start. Standard

** Program start.

DALI=digitaladdressabledimming

Other dimming options consult factory.

Note: For T8 UNV, you must use HI or P2 ballast code.

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing)

H9S1GLR232UNVHI

30˚

60˚550

1100

1650

Candlepower CurveReference data

Efficiency 78.4% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 59.4W Ballastfactor 0.88

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.15 See page 4.15 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S1GLR232 AHIExample

H9S1GLR132UNVHI

30˚

60˚250

500

750

Candlepower CurveReference data

Efficiency 77.8% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 29.4W Ballastfactor 0.88

HP90 Voltage Ballast Options Direct/indirect 120=120V Seepage4.15 See page 4.15 Recessed 277=277V andpage4.130 UNV=120-277V

UNVH9S1GLR132 AHIExample

5" (127mm)

12"(305mm)

5"(127mm)

5" (127mm)

12"(305mm)

5"(127mm)

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4' 2-T8 32W H9S1GLR232

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4' 1-T8 32W H9S1GLR132

Page 19: Linear recessed and surface lighting

4.16 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

5"(127mm)

24" (610mm)21½" (546mm)

5"(127mm)

24" (610mm)21½" (546mm)

HP90 Air 2' x 4'Direct/indirect recessed air handling luminaires

HP90 Air combines a recessed contoured body with an enclosed linear prismatic lens to create an efficient direct/indirect luminaire with air supply or return capabilities. HP90 Air will illuminate both vertical and horizontal surfaces creating balance brightness. It is available in 2' x 4' and 2' x 2' sizes. An excellent choice when choosing an architectural designed luminaire for LEED compliant office spaces. The construction pays attention to fit and finish.

Features•90.4%efficienttwolamp28WT52'x4'luminaire.•85.2%efficienttwolamp32WT82'x4'luminaire.•Direct/indirectappearancewithsoftcontouredinterior.•airsupplyorReturn.•AirreturnmodelmeetsUL1598,paragraph

9.2.2.5 requirements.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceilingtypes.•Lampshieldopensfromeitherside.•95%reflectivespecularaluminumreflector.•Ballastaccessiblefromroomside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•OptionalDALIballastiGENtechnologyacceptsdigital

dimming commands from computers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

Options & accessories page 4.130

Ballast type <10THD <20THD

Electronic T5 program start PG –Electronic T5 28W instant start WA*† –Electronic T5 28W bi-level VY – stepballast(2lamp)ElectronicT8(1or2lamp) HI*, P2** SO*LOL Dimming T8 PS –Electronic T8 32W bi-level V2 – stepballast(2lamp)DALIBallast DA –

* Instant start. Standard (WABallastonlyavailablein120or277volt)

** Program start.†56Inputwatts0.93B.F.

DALI=digitaladdressabledimming

Other dimming options consult factory.

Note: For T8 UNV, you must use HI or P2 ballast code.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

H9A2GLR128UNVPG H9A2GLR228120WA

5"(127mm)

24" (610mm)21½" (546mm)

5"(127mm)

24" (610mm)21½" (546mm)

HP90 Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.16 See page 4.16 air supply and return 277=277V andpage4.130 UNV=120-277V

UNVH9A2GLR228 APGExample

30˚

60˚300

600

900

Candlepower Curve

30˚

60˚550

1100

1650

Candlepower CurveReference data

Efficiency 87.2% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 31.6W Ballastfactor 1.0

Reference data

Efficiency 90.4% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 54.6W Ballastfactor 0.93

5"(127mm)

24" (610mm)21½" (546mm)

5"(127mm)

24" (610mm)21½" (546mm)

H9A2GLR132UNVHI H9A2GLR232UNVHI

5"(127mm)

24" (610mm)21½" (546mm)

5"(127mm)

24" (610mm)21½" (546mm)

HP90 Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.16 See page 4.16 air supply and return 277=277V andpage4.130 UNV=120-277V

UNVH9A2GLR232 AHIExample

30˚

60˚300

600

900

Candlepower Curve

30˚

60˚550

1100

1650

Candlepower CurveReference data

Efficiency 85.2% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 31.2W Ballastfactor 0.88

Reference data

Efficiency 85.2% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 59.7W Ballastfactor 0.88

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Air supply and return 2' x 4'

1-T51-T5HO2-T52-T5HO

28W54W28W54W

H9A2GLR128 H9A2GLR154 H9A2GLR228 H9A2GLR254

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Air supply and return 2' x 4' 1-T8

2-T8 32W H9A2GLR132 H9A2GLR232

Page 20: Linear recessed and surface lighting

4.17Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

5"(127mm)

24" (610mm)21½" (546mm)

5"(127mm)

24" (610mm)21½" (546mm)

HP90 Air 2' x 2'Direct/indirect recessed air handling luminaires

HP90 Air combines a recessed contoured body with an enclosed linear prismatic lens to create an efficient direct/indirect luminaire with air supply or return capabilities. HP90 Air will illuminate both vertical and horizontal surfaces creating balance brightness. It is available in 2' x 4' and 2' x 2' sizes. An excellent choice when choosing an architectural designed luminaire for LEED compliant office spaces. The construction pays attention to fit and finish.

Features•72.9%efficientsinglelamp40WTwintubeT52'x2'

luminaire.•83.2%efficientonelamp14WT52'x2'luminaire.•80.3%efficienttwolamp24WT5HO2'x2'luminaire.•Direct/indirectappearancewithsoftcontouredinterior.•airsupplyorReturn.•AirreturnmodelmeetsUL1598,paragraph.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceilingtypes.•Lampshieldopensfromeitherside.•95%reflectivespecularaluminumreflector.•Ballastaccessiblefromroomside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•OptionalDALIballastiGENtechnologyacceptsdigital

dimming commands from computers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

Options & accessories page 4.130

Ballast type <10THD <20THD

Electronic T5 program start PG –Electronic TT5 40W IB SBElectronic TT5 50W BP –Electronic TT5 55W BF –Electronic T5 14W bi-level VY – stepballast(2lamp)ElectronicT8(1or2lamp) HI*, P2** SO*LOL Dimming T8 PS –DALIBallast DA –

* Instant start. Standard

** Program start.

DALI=digitaladdressabledimming

Other dimming options consult factory.

Note: For T8 UNV, you must use HI or P2 ballast code.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

H9A2GLR1FTUNVPR H9A2GLR224UNVPG

5"(127mm)

24" (610mm)21½" (546mm)

5"(127mm)

24" (610mm)21½" (546mm)

HP90 Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.17 See page 4.17 air supply and return 277=277V andpage4.130 UNV=120-277V

UNVH9A2GLR214 APGExample

30˚

60˚300

600

900

Candlepower Curve

30˚

60˚300

600

900

Candlepower CurveReference data

Efficiency 72.9% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 37.6W Ballastfactor 1.0

Reference data

Efficiency 80.3% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 49.4W Ballastfactor 1.0

5"(127mm)

24" (610mm)21½" (546mm)

5"(127mm)

24" (610mm)21½" (546mm)

H9A2GLR117UNVHI H9A2GLR217UNVHI

5"(127mm)

24" (610mm)21½" (546mm)

5"(127mm)

24" (610mm)21½" (546mm)

HP90 Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.17 See page 4.17 air supply and return 277=277V andpage4.130 UNV=120-277V

UNVH9A2GLR232 AHIExample

30˚

60˚120

240

360

Candlepower Curve

30˚

60˚250

500

750

Candlepower CurveReference data

Efficiency 82.5% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 16.7W Ballastfactor 0.88

Reference data

Efficiency 80.3% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 30.6W Ballastfactor 0.88

Emergency Pack Emergency Pack

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Air supply and return 2' x 2'

1-TT52-T52-T5HO

40W14W24W

H9A2GLR1FT H9A2GLR214 H9A2GLR224

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Air supply and return 2' x 2' 1-T8

2-T8 17W H9A2GLR117 H9A2GLR217

Page 21: Linear recessed and surface lighting

4.18 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

HP90 2' x 4' & 2' x 2'Direct/indirect semi-recessed static luminaires

HP90DropLens~SemiRecessedoffersT5lampoptionsinabodythatisonlyrecessed2¼".The translucent linear prismatic lens and softly contoured body, create a pleasing architectural statement that is evenly illuminated. Its broad light distribution illuminates both horizontal and vertical surfaces, creating a soft balanced brightness in any space that enhances visual acuity.

Features•Only2-1/4"plenumdepth.•87.0%efficientsinglelamp28WT52'x4'luminaire.•88.5%efficienttwolamp28WT52'x4'luminaire.•78.2%efficientsinglelamp40WTwintubeT52'x2'

luminaire.•77.1%efficienttwolamp24wattT52'x2'luminaire.•Direct/indirectappearancewithsoftcontouredinterior.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceiling.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•Lampshieldopensfromeitherside.•Ballastaccessiblefromroomside.•Wiringaccessplatestandard.•OptionalDALIballastiGENTechnologyacceptsdigital

dimming controllers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

Options & accessories page 4.130Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat white acrylic enamel. Rust preventive undercoating. Reflector – low iridescence specular aluminum 95% reflectance.

Ballast type <10THD

40W TT5 PRElectronic T5 program start PGElectronic T5 28W instant start WA*†

Electronic T5 14W/28W bi-level VY stepballast(2lamp)DALIBallast DA

*Ballast(WA)onlyavailablein120or277volt.†56Inputwatts0.93B.F.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4. Conversion kit for 2' x 2' unit: FK92X2 .

Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚500

1000

1500

Candlepower CurveHDS2GLW228120WA

4 9�16"(116mm)

21½" (546mm)

4 9�16"(116mm)

21½" (546mm)

2 1/4 (57mm)

2 5/16 (59mm)

24 (610mm)

2 1/4 (57mm)

2 5/16 (59mm)

24 (610mm)

2 1/4 (57mm)

2 5/16 (59mm)

24 (610mm)

2 1/4 (57mm)

2 5/16 (59mm)

24 (610mm)

1 9/16 X 2 13/16 ACCESS PLATE W/ 2-7/8 DIA KO

24" (610mm)

2 1/4 (57.15mm)

48" (1219mm)

1 9/16 X 2 13/16 ACCESS PLATE W/ 2-7/8 DIA KO

24"(610mm)

24" (1219mm)

2 1/4 (57.15mm)

1 9/16 X 2 13/16 ACCESS PLATE W/ 2-7/8 DIA KO

24"(610mm)

24" (1219mm)

2 1/4 (57.15mm)

Reference data

Efficiency 88.5% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 54.1W Ballastfactor 0.93

30˚

60˚250

500

750

Candlepower CurveHDS2GLW1FTUNVPR

Reference data

Efficiency 78.2% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 38.4W Ballastfactor 1

4 9�16"(116mm)

21½" (546mm)

4 9�16"(116mm)

21½" (546mm)

2 1/4 (57mm)

2 5/16 (59mm)

24 (610mm)

2 1/4 (57mm)

2 5/16 (59mm)

24 (610mm)

2 1/4 (57mm)

2 5/16 (59mm)

24 (610mm)

2 1/4 (57mm)

2 5/16 (59mm)

24 (610mm)

1 9/16 X 2 13/16 ACCESS PLATE W/ 2-7/8 DIA KO

24" (610mm)

2 1/4 (57.15mm)

48" (1219mm)

1 9/16 X 2 13/16 ACCESS PLATE W/ 2-7/8 DIA KO

24"(610mm)

24" (1219mm)

2 1/4 (57.15mm)

1 9/16 X 2 13/16 ACCESS PLATE W/ 2-7/8 DIA KO

24"(610mm)

24" (1219mm)

2 1/4 (57.15mm)

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

1-T52-T51-T5HO2-T5HO

28W28W54W54W

HDS2GLW128 HDS2GLW228 HDS2GLW154 HDS2GLW254

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'2-T52-T5HO1-Twin tube T5

14W24W40W

HDS2GLW214 HDS2GLW224 HDS2GLW1FT

HP90 Semi-recessed Voltage Ballast Options Direct/indirect 120=120V Seepage4.18 See page 4.18 recessed static 277=277V andpage4.130 UNV=120-277V

120HDS2GLW228 AWAExample

HP90 Semi-recessed Voltage Ballast Options Direct/indirect 120=120V Seepage4.18 See page 4.18 recessed static 277=277V andpage4.130 UNV=120-277V

UNVHDS2GLW1FT APRExample

Page 22: Linear recessed and surface lighting

4.19Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

HP90 2' x 4' & 2' x 2'Direct/indirect surface-mounted static luminaires

HP90DropLens~SurfaceMountedoffersT5lampoptionsinabodythatisonly2-17/32"deep. The translucent linear prismatic lens and softly contoured body, create a pleasing architectural statement that is evenly illuminated. Its broad light distribution illuminates both horizontal and vertical surfaces, creating a soft balanced brightness in any space that enhances visual acuity.

Features•88.5%efficienttwolamp28W2'x4'luminaire.•87.0%efficientsinglelamp28W2'x4'luminaire.•77.1%efficienttwolamp24WT5HO2'x2'luminaire.•78.2%efficientsinglelamp40WtwintubeT52'x2'

luminaire.•Direct/indirectappearancewithsoftcontouredinterior.•Lensencloseslampcompartment.•TranslucentDRacryliclinearprismaticlens.•Tensionscrewssecureendstobody.•Lampshieldopensfromeitherside.•Ballastaccessiblefromroomside.•Built-inearthquakeclips.•OptionalDALIballastiGENTechnologyacceptsdigital

dimming controllers, scene controllers and automatic control devices.

•ConstructiontomeetNYCCodeorChicagoPlenumrequirement available.

•Notforcontinuousrowmounting.

Options & accessories page 4.130Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat white acrylic enamel. Rust preventive undercoating. Reflector – low iridescence specular aluminum 95% reflectance.

Ballast type <10THD

40 W TT5 PRElectronic T5 program start PGElectronic T5 28W instant start WA*†

Electronic T5 14W/28W bi-level VY stepballast(2lamp)DALIBallast DA

*Ballast(WA)onlyavailablein120or277volt.†56Inputwatts0.93B.F.

DALI=digitaladdressabledimming

Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚500

1000

1500

Candlepower CurveHDB2SLW228120WA

24 1/8" (613mm)

48" (1219mm)

2-7/8 DIA KO

3 5/8" (92mm)

2 15/16" (75mm)

1 5/8" (41mm)

3 5/8" (92mm)

2-1/4 MOUNTING HOLES

39 3/4" (1010mm)

42 1/2" (1080mm)

3 5/8" (92mm)

2 15/16" (75mm)

24 1/8" (613mm)

15 3/4" (400mm)

2-1/4 MOUNTING HOLES

1 5/8" (41mm)3 5/8" (92mm)

18 7/16" (468mm)

2-7/8 DIA KO

24" (1219mm)

3 5/8" (92mm)

2 15/16" (75mm)

24 1/8" (613mm)

15 3/4" (400mm)

2-1/4 MOUNTING HOLES

1 5/8" (41mm)3 5/8" (92mm)

18 7/16" (468mm)

2-7/8 DIA KO

24" (1219mm)

2 17/32 (64mm)

2 5/16 (59mm)

24 1/8 (613mm)

24 1/8 (613mm)

2 5/16 (59mm)

2 17/32 (64mm)

24 1/8 (613mm)

2 5/16 (59mm)

2 17/32 (64mm)

24 1/8 (613mm)

2 5/16 (59mm)

2 17/32 (64mm)

4 ⅞"(123mm)

21½" (546mm)

4 ⅞"(123mm)

21½" (546mm)

Reference data

Efficiency 88.5% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 54.1W Ballastfactor 0.93

30˚

60˚250

500

750

Candlepower CurveHDB2SLW1FTUNVPR

Reference data

Efficiency 78.2% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 38.4W Ballastfactor 1

24 1/8" (613mm)

48" (1219mm)

2-7/8 DIA KO

3 5/8" (92mm)

2 15/16" (75mm)

1 5/8" (41mm)

3 5/8" (92mm)

2-1/4 MOUNTING HOLES

39 3/4" (1010mm)

42 1/2" (1080mm)

3 5/8" (92mm)

2 15/16" (75mm)

24 1/8" (613mm)

15 3/4" (400mm)

2-1/4 MOUNTING HOLES

1 5/8" (41mm)3 5/8" (92mm)

18 7/16" (468mm)

2-7/8 DIA KO

24" (1219mm)

3 5/8" (92mm)

2 15/16" (75mm)

24 1/8" (613mm)

15 3/4" (400mm)

2-1/4 MOUNTING HOLES

1 5/8" (41mm)3 5/8" (92mm)

18 7/16" (468mm)

2-7/8 DIA KO

24" (1219mm)

2 17/32 (64mm)

2 5/16 (59mm)

24 1/8 (613mm)

24 1/8 (613mm)

2 5/16 (59mm)

2 17/32 (64mm)

24 1/8 (613mm)

2 5/16 (59mm)

2 17/32 (64mm)

24 1/8 (613mm)

2 5/16 (59mm)

2 17/32 (64mm)

4 ⅞"(123mm)

21½" (546mm)

4 ⅞"(123mm)

21½" (546mm)

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

1-T52-T51-T5HO2-T5HO

28W28W54W54W

HDB2SLW128 HDB2SLW228 HDB2SLW154 HDB2SLW254

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'2-T52-T5HO1-Twin tube T5

14W24W40W

HDB2SLW214 HDB2SLW224 HDB2SLW1FT

HP90 Surface mounted Voltage Ballast Options Direct/indirect 120=120V Seepage4.19 See page 4.19 recessed static 277=277V andpage4.130 UNV=120-277V

120HDB2SLW228 AWAExample

HP90 Surface mounted Voltage Ballast Options Direct/indirect 120=120V Seepage4.19 See page 4.19 recessed static 277=277V andpage4.130 UNV=120-277V

UNVHDB2SLW1FT APRExample

Page 23: Linear recessed and surface lighting

4.20 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•Direct/indirectlouverappearancewithsoft

contoured interior.•12cellf latwhitelouverwithprismaticlensoverlay.•67.8%efficientthreelampT82'x4'luminaire.•82.0%efficienttwolampT52'x4'luminaire.•72.1%efficienttwolampT82'x4'luminaire.•Only5"deep.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceiling.•Airreturnstandard(meetsULrequirements).•Staticoptional.•Louverhingesfromeitherside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•Builtinearthquakeclips.•Housingisavailablein20gaugesteelthatmeets NYCrequirements.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Paraplus II 2' x 4'Direct/indirect louver air return or static recessed luminaires

Paraplus II is an architecturally styled recessed luminaire that combines the features of a parabolic louver and an indirect cove to create an aesthetically pleasing direct/indirect appearance.

30˚

60˚850

1700

2550

Candlepower CurvePPH2G12FW332UNVH3

5"(127mm)

24" (610mm)

Reference data

Efficiency 67.8% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 85W

Paraplus Voltage Ballast Options Recessed direct/indirect 120,277orUNV(120-277) Seepage4.20 See page 4.20 and page 4.130

UNVPPH2G12FW332 AH3Example

30˚

60˚650

1300

1950

Candlepower CurvePPH2G12FW232UNVHI

5"(127mm)

24" (610mm)

Reference data

Efficiency 72.1% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 62W

30˚

60˚650

1300

1950

Candlepower CurvePPS2G12FW254UNVPG

5"(127mm)

24" (610mm)

Reference data

Efficiency 82.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 120W

Paraplus Voltage Ballast Options Recessed direct/indirect 120,277orUNV(120-277) Seepage4.20 See page 4.20 and page 4.130

UNVPPH2G12FW232 AHIExample

Paraplus Voltage Ballast Options Recessed direct/indirect 120,277orUNV(120-277) Seepage4.20 See page 4.20 and page 4.130

UNVPPS2G12FW254 APGExample

Ordering informationType Size Lamp qty –type Louver overlay Catalog no.

Air return 2' x 4' 3-T8P20P20 & white overlayMatte white lens

PPH2G12FW332 PPH2G12FO332 PPH2G12FM332

Static 2' x 4' 3-T8P20P20 & white overlayMatte white lens

PPS2G12FW332 PPS2G12FO332 PPS2G12FM332

Ordering informationType Size Lamp qty –type Louver overlay Catalog no.

Air return 2' x 4' 2-T8P20P20 & white overlayMatte white lens

PPH2G12FW232 PPH2G12FM232 PPH2G12FO232

Static 2' x 4' 2-T8P20P20 & white overlayMatte white lens

PPS2G12FW232 PPS2G12FO232 PPS2G12FM232

Ordering informationType Size Lamp qty –type Louver overlay Catalog no.

Air return 2' x 4' 2-T5HOP20P20 & white overlayMatte white lens

PPS2G12FW254 PPS2G12FO254 PPS2G12FM254

Static 2' x 4' 2-T5P20P20 & white overlayMatte white lens

PPS2G12FW228 PPS2G12FO228 PPS2G12FM228

Page 24: Linear recessed and surface lighting

4.21Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Direct/indirectlouverappearancewithsoft

contoured interior.•8cellf latwhitelouverwithprismaticlensoverlay.•72.0%efficienttwolampTT52'x2'luminaire.•71.4%efficienttwolampT5HO2'x2'luminaire.•Only5"deep.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceiling.•Airreturnstandard(meetsULrequirements).•Staticoptional.•Louverhingesfromeitherside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•Builtinearthquakeclips.•Housingisavailablein20gaugesteelthatmeets NYCrequirements.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic TT5 IB* SB*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Paraplus II 2' x 2'Direct/indirect louver air return or static recessed luminaires

Paraplus II is an architecturally styled recessed luminaire that combines the features of a parabolic louver and an indirect cove to create an aesthetically pleasing direct/indirect appearance.

30˚

60˚700

1400

2100

Candlepower CurvePPH2G8FW2FT120SB

5"(127mm)

24" (610mm)

Reference data

Efficiency 72.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 72.6W

Paraplus Voltage Ballast Options Recessed direct/indirect 120,277orUNV(120-277) Seepage4.21 See page 4.21 and page 4.130

120PPH2G8FW2FT ASBExample

30˚

60˚450

900

1350

Candlepower CurvePPS2G8FW224UNVPG

5"(127mm)

24" (610mm)

Reference data

Efficiency 71.4% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 56.9W

Paraplus Voltage Ballast Options Recessed direct/indirect 120,277orUNV(120-277) Seepage4.21 See page 4.21 and page 4.130

UNVPPS2G8FW224 APGExample

Ordering informationType Size Lamp qty –type Louver overlay Catalog no.

Air return 2' x 2' 2-TT5P20P20 & white overlayMatte white lens

PPH2G8FW2FT PPH2G8FO2FT PPH2G8FM2FT

Static 2' x 2' 2-TT5P20P20 & white overlayMatte white lens

PPS2G8FW2FT PPS2G8FO2FT PPS2G8FM2FT

Ordering informationType Size Lamp qty –type Louver overlay Catalog no.

Static 2' x 2'

2-T5P20P20 & white overlayMatte white lens

PPS2G8FW214 PPS2G8FO214 PPS2G8FM214

2-T5HOP20P20 & white overlayMatte white lens

PPS2G8FW224 PPS2G8FO224 PPS2G8FM224

2-T8P20P20 & white overlayMatte white lens

PPS2G8FW217 PPS2G8FO217 PPS2G8FM217

3-T8P20P20 & white overlayMatte white lens

PPS2G8FW317 PPS2G8FO317 PPS2G8FM317

Page 25: Linear recessed and surface lighting

4.22 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•Direct/indirectlouverappearancewithsoft

contoured interior.•6cellf latwhitelouverwithprismaticlensoverlay.•60.2%efficienttwolampT81'x4'luminaire.•67.5%efficientsinglelampT5HO1'x4'luminaire.•71.4%efficienttwolampT5HO1'x4'luminaire.•Only5"deep.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceiling.•Airreturnstandard(meetsULrequirements).•Staticoptional.•Louverhingesfromeitherside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•4earthquakeclipsstandard.•Housingis20gaugesteel,meetsNYCrequirements.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Paraplus II 1' x 4'Direct/indirect louver air return or static recessed luminaires

Paraplus II is an architecturally styled recessed luminaire that combines the features of a parabolic louver and an indirect cove to create an aesthetically pleasing direct/indirect appearance.

PPH1G6FW232UNVHI

30˚

60˚600

1200

1800

Candlepower CurveReference data

Efficiency 60.2% Spacing ratio 1.1

Electronic ballast

Inputwatts(120V) 64.1W

UNVPPH1G6FW232 AHIExample

PPS1G6FW154UNVPG

30˚

60˚550

1100

1650

Candlepower CurveReference data

Efficiency 67.5% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 60.7W

UNVPPS1G6FW154 APGExample

5"(127mm)

12" (305mm)

5"(127mm)

12" (305mm)

Ordering informationType Size Lamp qty –type Louver overlay Catalog no.

Static 1' x 4'

2-T5HOP20P20 & white overlayMatte white lens

PPS1G6FW254 PPS1G6FO254 PPS1G6FM254

1-T5HOP20P20 & white overlayMatte white lens

PPS1G6FW154 PPS1G6FO154 PPS1G6FM154

2-T5P20P20 & white overlayMatte white lens

PPS1G6FW228 PPS1G6FO228 PPS1G6FM228

Ordering informationType Size Lamp qty –type Louver overlay Catalog no.

Air return 1' x 4' 2-T8P20P20 & white overlayMatte white lens

PPH1G6FW232 PPH1G6FO232 PPH1G6FM232

Paraplus Voltage Ballast Options Recessed direct/indirect 120=120V Seepage4.22 See page 4.22 277=277V andpage4.130 UNV=120-277V

Paraplus Voltage Ballast Options Recessed direct/indirect 120=120V Seepage4.22 See page 4.22 277=277V andpage4.130 UNV=120-277V

Page 26: Linear recessed and surface lighting

4.23Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Paraplus IIDirect/indirect louver air return or static recessed luminaires

Page 27: Linear recessed and surface lighting

4.24 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

OpalescentPremium specification recessed air handling or static luminaires

Opalescent’s2½"regressedframewithcontouredlens,madeofahighlighttransmissionfrost white acrylic, creates a bold but simple appearance that will blend with any architectural environment. The Opalescent lens frame assembly, designed with precision mitered side rails and integrated spring loaded latches, allows for simple installation and maintenance of the lamps and ballast.

The exterior of the Opalescent housing is black and incorporates eyeleted heat removal vents on the end caps, creating an environment for a cooler ballast operating temperature. The internal reflector system is powder coated with our 95% reflective white paint. When matched with the high light transmission frost white acrylic lens it gives the Opalescent efficiencies that qualify for many rebate programs, making it a true energy and cost saving choice.

Page 28: Linear recessed and surface lighting

4.25Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Boldbutsimple2-1/2"regressedframe

with contoured lens.•Highlighttransmissionfrostwhiteacryliclens.•Truemiteredcornerlensframe.•86.8%efficienttwolamp28WT52'x4'luminaire.•79.5%efficienttwolamp54WT5HO2'x4'luminaire.•Internalreflectorcoatedwith95%reflectivewhitepaint.•5"deepbody.•Blackhousingexteriorforcoolerballastoperating

temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursidesforpositive

light stop.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.

Options & accessories page 4.130

Ballast type <10THD

Electronic T5 program start PGElectronic T5 28W instant start WA*†

Electronic T5 28W bi-level step ballast VY (2lamp)DALIBallast DA

*Ballast(WA)onlyavailablein120or277volt.†56Inputwatts0.93B.F.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Opalescent T5 2' x 4'Premium specification recessed air handling or static luminaires

Opalescent’s2½"regressedframewithcontouredlens,madeofahighlighttransmissionfrost white acrylic, creates a bold but simple appearance that will blend with any architectural environment. The Opalescent lens frame assembly, designed with precision mitered side rails and integrated spring loaded latches, allows for simple installation and maintenance of the lamps and ballast. The exterior of the Opalescent housing is black and incorporates eyeleted heat removal vents on the end caps, creating an environment for a cooler ballast operating temperature. The internal reflector system is powder coated with our 95% reflective white paint. When matched with the high light transmission frost white acrylic lens it gives the Opalescent efficiencies that qualify for many rebate programs, making it a true energy and cost saving choice.

30˚

60˚650

1300

1950

Candlepower CurveOPA2GPW228UNVPG

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 86.8% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 62.7W Ballastfactor 1

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T5 28W OPS2GPW228

Air handling 2' x 4' 2-T5 28W OPA2GPW228

30˚

60˚950

1900

2850

Candlepower CurveOPA2GPW254UNVPG

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 79.5% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 115.0W Ballastfactor 1

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T5HO 54W OPS2GPW254

Air handling 2' x 4' 2-T5HO 54W OPA2GPW254

Opalescent Voltage Ballast Options Frost white contoured lens design 120=120V Seepage4.25 See page 4.25 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVOPA2GPW228 APGExample

Opalescent Voltage Ballast Options Frost white contoured lens design 120=120V Seepage4.25 See page 4.25 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVOPA2GPW254 APGExample

Page 29: Linear recessed and surface lighting

4.26 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•Aestheticallypleasingtriplelensdesign.•Curvedhighlighttransmissionfrostwhiteacrylic

side lenses.•Clearacrylicconicalprismaticcenterlens.•Internalreflectorcoatedwith95%reflective

white paint.•82.8%efficienttwolamp40WTT52'x2'luminaire.•75.6%efficienttwolamp14WT52'x2'luminaire.•76.1%efficienttwolamp24WT5HO2'x2'luminaire.•5"deepbody.•Blackhousingexteriorforcoolerballastoperating

temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursidesforpositive

light stop.•Truemiteredcorneraluminumlensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.

Options & accessories page 4.130

Ballast type <10THD <20THD

Electronic T5 program start PG –Electronic TT5 40W PR* –Electronic TT5 40W IB SBElectronic TT5 50W BP –Electronic TT5 55W BF –Electronic T5 14W bi-level VY – stepballast(2lamp)DALIBallast DA –

* Program start.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Opalescent T5 2' x 2'Premium specification recessed air handling or static luminaires

Opalescent’s2½"regressedframewithcontouredlens,madeofahighlighttransmissionfrost white acrylic, creates a bold but simple appearance that will blend with any architectural environment. The Opalescent lens frame assembly, designed with precision mitered side rails and integrated spring loaded latches, allows for simple installation and maintenance of the lamps and ballast. The exterior of the Opalescent housing is black and incorporates eyeleted heat removal vents on the end caps, creating an environment for a cooler ballast operating temperature. The internal reflector system is powder coated with our 95% reflective white paint. When matched with the high light transmission frost white acrylic lens it gives the Opalescent efficiencies that qualify for many rebate programs, making it a true energy and cost saving choice.

30˚

60˚650

1300

1950

Candlepower CurveOPS2GPW2FTUNVPR

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 82.8% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 67.4W Ballastfactor 0.88

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-Twin tube T5 40W OPS2GPW2FT

Air handling 2' x 2' 2-Twin tube T5 40W OPA2GPW2FT

30˚

60˚400

800

1200

Candlepower CurveOPA2GPW224UNVPG

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 76.1% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 51.1W Ballastfactor 1

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-T52-T5HO

14W24W

OPS2GPW214 OPS2GPW224

Air handling 2' x 2' 2-T52-T5HO

14W24W

OPA2GPW214 OPA2GPW224

Opalescent Voltage Ballast Options Frost white contoured lens design 120=120V Seepage4.26 See page 4.26 Air handling or static 277=277v andpage4.130 UNV=120-277V

UNVOPS2GPW2FT APRExample

Opalescent Voltage Ballast Options Frost white contoured lens design 120=120V Seepage4.26 See page 4.26 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVOPA2GPW224 APGExample

Page 30: Linear recessed and surface lighting

4.27Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Boldbutsimple2½"regressedframewith

contoured lens.•Highlighttransmissionfrostwhiteacryliclens.•Truemiteredcornerlensframe.•80.8%efficienttwolamp32WT82'x4'luminaire.•80.0%efficientthreelamp25WT82'x4'luminaire.•Internalreflectorcoatedwith95%reflective

white paint.•5"deepbody.•Blackhousingexteriorforcoolerballastoperating

temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursidesforpositive

light stop.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeand add as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Advance Optanium C5* – Low Watt.77 Electronic T8

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Opalescent T8 2' x 4'Premium specification recessed air handling or static luminaires

Opalescent’s2½"regressedframewithcontouredlens,madeofahighlighttransmissionfrost white acrylic, creates a bold but simple appearance that will blend with any architectural environment. The Opalescent lens frame assembly, designed with precision mitered side rails and integrated spring loaded latches, allows for simple installation and maintenance of the lamps and ballast. The exterior of the Opalescent housing is black and incorporates eyeleted heat removal vents on the end caps, creating an environment for a cooler ballast operating temperature. The internal reflector system is powder coated with our 95% reflective white paint. When matched with the high light transmission frost white acrylic lens it gives the Opalescent efficiencies that qualify for many rebate programs, making it a true energy and cost saving choice.

30˚

60˚650

1300

1950

Candlepower CurveOPA2GPW232UNVC5

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 80.8% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 53.5W Ballastfactor 0.77

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T8 32W OPS2GPW232

Air handling 2' x 4' 2-T8 32W OPA2GPW232

30˚

60˚950

1900

2850

Candlepower CurveOPA2GPW332UNVH3

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data – 25W

Efficiency 80.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 71.1W Ballastfactor 0.88

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 3-T8 32W OPS2GPW332

Air handling 2' x 4' 3-T8 32W OPA2GPW332

Opalescent Voltage Ballast Options Frost white contoured lens design 120=120V Seepage4.27 See page 4.27 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVOPA2GPW232 AC5Example

Opalescent Voltage Ballast Options Frost white contoured lens design 120=120V Seepage4.27 See page 4.27 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVOPA2GPW332 AH3Example

Page 31: Linear recessed and surface lighting

4.28 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Opalescent T8 2' x 2'Premium specification recessed air handling or static luminaires

Opalescent’s2½"regressedframewithcontouredlens,madeofahighlighttransmissionfrost white acrylic, creates a bold but simple appearance that will blend with any architectural environment. The Opalescent lens frame assembly, designed with precision mitered side rails and integrated spring loaded latches, allows for simple installation and maintenance of the lamps and ballast. The exterior of the Opalescent housing is black and incorporates eyeleted heat removal vents on the end caps, creating an environment for a cooler ballast operating temperature. The internal reflector system is powder coated with our 95% reflective white paint. When matched with the high light transmission frost white acrylic lens it gives the Opalescent efficiencies that qualify for many rebate programs, making it a true energy and cost saving choice.

30˚

60˚300

600

900

Candlepower CurveOPA2GPW217UNVHI

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 74.5% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 30.2W Ballastfactor 0.90

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-T8 2-6"UT8

17W32W

OPS2GPW217 OPS2GPW26U

Air handling 2' x 2' 2-T8 2-6"UT8

17W32W

OPA2GPW217 OPA2GPW26U

30˚

60˚450

900

1350

Candlepower CurveOPA2GPW317UNVH3

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 70.1% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 45.5W Ballastfactor 0.92

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 3-T8 17W OPS2GPW317

Air handling 2' x 2' 3-T8 17W OPA2GPW317

Features•Aestheticallypleasingtriplelensdesign.•Curvedhighlighttransmissionfrostwhiteacrylic

side lenses.•Clearacrylicconicalprismaticcenterlens.•Internalreflectorcoatedwith95%reflective

white paint.•74.5%efficienttwolamp17WT82'x2'luminaire.•70.1%efficientthreelamp17WT82'x2'luminaire.•5"deepbody.•Blackhousingexteriorforcoolerballastoperating

temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursidesforpositive

light stop.•Truemiteredcorneraluminumlensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirements

or Chicago Plenum is available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeand add as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Opalescent Voltage Ballast Options Frost white contoured lens design 120=120V Seepage4.28 See page 4.28 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVOPA2GPW217 AHIExample

Opalescent Voltage Ballast Options Frost white contoured lens design 120=120V Seepage4.28 See page 4.28 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVOPA2GPW317 AH3Example

Page 32: Linear recessed and surface lighting

4.29Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Opalescent Twin 2' x 4' & 2' x 2'Premium specification recessed luminaires

Dual sculptured ends and curved opal prismatic lens, presented in a shallow regressed Door frame the Opalescent Twin provides a broad distribution that illuminates the vertical and horizontal surfaces in the work space. This creates a soft, balanced brightness that enhances the ability to see and work.

OTS2GPW232UNVHI

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'2-T8 2-T52-T5HO

32W28W54W

OTS2GPW232UNVHIOTS2GPW228UNVPGOTS2GPW254UNVPG

Static 2' x 2'

2-T5 2-T82-T5HO2-TT5

14W17W24W40W

OTS2GPW214UNVPGOTS2GPW217UNVHIOTS2GPW224UNVPGOTS2GPW2FTUNVPR

The Opalescent Twin provides illumination at power levels below LEED requirements and yet is a highly efficient luminaire. With ashallowdepthofonly3½",accesstotheballast from below, the Opalescent Twin is an excellent choice for any commercial application and a welcome part of the Opalescent family.

The Opalescent Twin will be available with two high performance T8 lamps, as well as T5 and T5HO fluorescent lamps in the 2' x 4', and T8, T5, T5HO or TT5 fluorescent lamps in the 2' x 2', both sizes will also be offered with LED options. Opalescent Twin will fit standard grid and dry wall ceilings withuseofoptionalFKDrywallkit.

Available 4th quarter 2011

Page 33: Linear recessed and surface lighting

4.30 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Skyway T5 2' x 4'Premium specification recessed air handling or static luminaires

Skyway’s aesthetically pleasing triple lens design features a clear conical prismatic center lens, enhanced by softly curved frost white acrylic lenses on each side, mounted in a regressed extruded aluminum frame with spring loaded latches. These 85% light transmission lenses, coupled with an internal reflector system coated with our 95% reflective white paint, creates our new, energy efficient Skyway.

Features•Aestheticallypleasingtriplelensdesign.•Curvedhighlighttransmissionfrostwhite

acrylic side lenses.•Clearacrylicconicalprismaticcenterlens.•Internalreflectorcoatedwith95%reflective

white paint.•73%efficienttwolamp28WT52'x4'luminaire.•72.7%efficienttwolamp54WT5HO2'x4'luminaire.•5"deepbody.•Blackhousingexteriorforcoolerballast

operating temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursides

for positive light stop.•Truemiteredcorneraluminumlensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.

Options & accessories page 4.130

Ballast type <10THD

Electronic T5 program start PGElectronic T5 28W instant start WA*†

Electronic T5 28W bi-level step ballast VY (2lamp)DALIBallast DA

*Ballast(WA)onlyavailablein120or277volt.†56Inputwatts0.93B.F.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚650

1300

1950

Candlepower CurveSKS2GPK228120WA

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 73.0% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 54.5W Ballastfactor 0.93

30˚

60˚950

1900

2850

Candlepower CurveSKS2GPK254UNVPG

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 72.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 114.9W Ballastfactor 1.0

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T5HO3-T5HO 54W SKS2GPK254

SKS2GPK354

Air handling 2' x 4' 2-T5HO3-T5HO 54W SKA2GPK254

SKA2GPK354

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T53-T5 28W SKS2GPK228

SKS2GPK328

Air handling 2' x 4' 2-T53-T5 28W SKA2GPK228

SKA2GPK328

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.30 See page 4.30 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVSKS2GPK254 APGExample

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.30 See page 4.30 Air handling or static 277=277V andpage4.130 UNV=120-277V

120SKS2GPK228 AWAExample

Page 34: Linear recessed and surface lighting

4.31Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Aestheticallypleasingtriplelensdesign.•Curvedhighlighttransmissionfrostwhite

acrylic side lenses.•Clearacrylicconicalprismaticcenterlens.•Internalreflectorcoatedwith95%reflective

white paint.•76.5%efficienttwolamp40WTwintubeT52'x2'

luminaire.•72.8%efficienttwolamp14WT52'x2'luminaire.•74.6%efficienttwolamp24WT5HO2'x2'luminaire.•5"deepbody.•Blackhousingexteriorforcoolerballast

operating temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursides

for positive light stop.•Truemiteredcorneraluminumlensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.

Options & accessories page 4.130

Ballast type <10THD <20THD

Electronic T5 program start PG –Electronic TT5 40W PR* –Electronic TT5 40W IB SBElectronic TT5 50W BP –Electronic TT5 55W BF –Electronic T5 14W bi-level VY – stepballast(2lamp)DALIBallast DA –

* Program start.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Skyway T5 2' x 2'Premium specification recessed air handling or static luminaires

Skyway’s aesthetically pleasing triple lens design features a clear conical prismatic center lens, enhanced by softly curved frost white acrylic lenses on each side, mounted in a regressed extruded aluminum frame with spring loaded latches. These 85% light transmission lenses, coupled with an internal reflector system coated with our 95% reflective white paint, creates our new, energy efficient Skyway.

30˚

60˚700

1400

2100

Candlepower CurveSKS2GPK2FTUNVIB

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 76.5% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 69.1W Ballastfactor 0.88

30˚

60˚400

800

1200

Candlepower CurveSKS2GPK224UNVPG

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 74.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 51.3W Ballastfactor 1.0

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-Twin tube T5 40W SKS2GPK2FT

Air handling 2' x 2' 2-Twin tube T5 40W SKA2GPK2FT

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'2-T52-T5HO3-T5HO

14W24W24W

SKS2GPK214 SKS2GPK224 SKS2GPK324

Air handling 2' x 2'2-T52-T5HO3-T5HO

14W24W24W

SKA2GPK214 SKA2GPK224 SKA2GPK324

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.31 See page 4.31 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVSKS2GPK224 APGExample

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.31 See page 4.31 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVSKS2GPK2FT AIBExample

Page 35: Linear recessed and surface lighting

4.32 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Skyway T5 1' x 4'Premium specification recessed air handling or static luminaires

Skyway’s aesthetically pleasing triple lens design features a clear conical prismatic center lens, enhanced by softly curved frost white acrylic lenses on each side, mounted in a regressed extruded aluminum frame with spring loaded latches. These 85% light transmission lenses, coupled with an internal reflector system coated with our 95% reflective white paint, creates our new, energy efficient Skyway.

Features•Aestheticallypleasingtriplelensdesign.•Curvedhighlighttransmissionfrostwhiteacrylic

side lenses.•Clearacrylicconicalprismaticcenterlens.•Internalreflectorcoatedwith95%reflective

white paint.•64.7%efficienttwolamp28WT51'x4'luminaire.•4"deepbody.•Blackhousingexteriorforcoolerballastoperating

temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursidesforpositive

light stop.•Truemiteredcorneraluminumlensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirements

or Chicago Plenum is available.

Options & accessories page 4.130

Ballast type <10THD

Electronic T5 program start PGElectronic T5 28W instant start WA*†

Electronic T5 28W bi-level step ballast VY (2lamp)DALIBallast DA

*Ballast(WA)onlyavailablein120or277volt.†56Inputwatts0.93B.F.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

SKS1GPK228UNVPG

4"(102mm)

11⅞" (302mm)

4"(102mm)

11⅞" (302mm)

Reference data

Efficiency 64.7% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 59.0W Ballastfactor 1

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4'

1-T52-T51-T5HO2-T5HO

28W28W54W54W

SKS1GPK128 SKS1GPK228 SKS1GPK154 SKS1GPK254

Air handling 1' x 4'

1-T52-T51-T5HO2-T5HO

28W28W54W54W

SKA1GPK128 SKA1GPK228 SKA1GPK154 SKA1GPK254

30˚

60˚550

1100

1650

Candlepower Curve

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.32 See page 4.32 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVSKS1GPK228 APGExample

Page 36: Linear recessed and surface lighting

4.33Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Aestheticallypleasingtriplelensdesign.•Curvedhighlighttransmissionfrostwhite

acrylic side lenses.•Clearacrylicconicalprismaticcenterlens.•Internalreflectorcoatedwith95%reflective

white paint.•75.3%efficienttwolamp32WT82'x4'luminaire.•75.4%efficientthreelamp32WT82'x4'luminaire.•5"deepbody.•Blackhousingexteriorforcoolerballast

operating temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursides

for positive light stop.•Truemiteredcorneraluminumlensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirements

or Chicago Plenum is available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeand add as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic T5 PG –Advance Optanium C5* – low watt.77 Electronic T8

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Skyway T8 2' x 4'Premium specification recessed air handling or static luminaires

Skyway’s aesthetically pleasing triple lens design features a clear conical prismatic center lens, enhanced by softly curved frost white acrylic lenses on each side, mounted in a regressed extruded aluminum frame with spring loaded latches. These 85% light transmission lenses, coupled with an internal reflector system coated with our 95% reflective white paint, creates our new, energy efficient Skyway.

30˚

60˚700

1400

2100

Candlepower CurveSKS2GPK232UNVC5

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 75.3% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 51.9W Ballastfactor 0.77

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T8 32W SKS2GPK232

Air handling 2' x 4' 2-T8 32W SKA2GPK232

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 3-T8 32W SKS2GPK332

Air handling 2' x 4' 3-T8 32W SKA2GPK332

30˚

60˚1050

2100

3150

Candlepower CurveSKS2GPK332UNVH3

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 75.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 87W Ballastfactor 0.88

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.33 See page 4.33 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVSKS2GPK232 AC5Example

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.33 See page 4.33 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVSKS2GPK332 AH3Example

Page 37: Linear recessed and surface lighting

4.34 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•Aestheticallypleasingtriplelensdesign.•Curvedhighlighttransmissionfrostwhiteacrylic

side lenses.•Clearacrylicconicalprismaticcenterlens.•Internalreflectorcoatedwith95%reflective

white paint.•70.7%efficienttwoLamp17WT82'x2'luminaire.•72.9%efficientthreeLamp17WT82'x2'luminaire.•5"deepbody.•Blackhousingexteriorforcoolerballast

operating temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursides

for positive light stop.•Truemiteredcorneraluminumlensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeand add as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Skyway T8 2' x 2'Premium specification recessed air handling or static luminaires

Skyway’s aesthetically pleasing triple lens design features a clear conical prismatic center lens, enhanced by softly curved frost white acrylic lenses on each side, mounted in a regressed extruded aluminum frame with spring loaded latches. These 85% light transmission lenses, coupled with an internal reflector system coated with our 95% reflective white paint, creates our new, energy efficient Skyway.

30˚

60˚300

600

900

Candlepower CurveSKS2GPK217UNVHI

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 70.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 31.7W Ballastfactor 0.83

30˚

60˚500

1000

1500

Candlepower CurveSKS2GPK317UNVH3

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Reference data

Efficiency 72.9% Spacing ratio 1.1

Electronic ballast

Inputwatts(120V) 46.6W Ballastfactor 1.0

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-T8 17W SKS2GPK217

Air handling 2' x 2' 2-T8 17W SKA2GPK217

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 3-T8 17W SKS2GPK317

Air handling 2' x 2' 3-T8 17W SKA2GPK317

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.34 See page 4.34 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVSKS2GPK217 AHIExample

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.34 See page 4.34 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVSKS2GPK317 AH3Example

Page 38: Linear recessed and surface lighting

4.35Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Aestheticallypleasingtriplelensdesign.•Curvedhighlighttransmissionfrostwhite

acrylic side lenses.•Clearacrylicconicalprismaticcenterlens.•Internalreflectorcoatedwith95%reflective

white paint.•66.4%efficienttwolamp32WT81'x4'luminaire.•4"deepbody.•Blackhousingexteriorforcoolerballast

operating temperature.•Eyeletedheatremovalventsinfixtureends.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Doorjambfinishedblackonfoursides

for positive light stop.•Truemiteredcorneraluminumlensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeRequirementsor

Chicago Plenum is available.

Options & accessories page 4.130

Ballast type <10THD <20THD

ElectronicT8(1or2lamp) HI* SO*ElectronicT8(1or2lamp) P2** –LOL Dimming T8 PS –Electronic T8 32W bi-level V2 – stepballast(2lamp)DALIBallast DA –

* Instant start. Standard

** Program start.

DALI=digitaladdressabledimming

Other dimming options consult factory.

Note: For T8 UNV, you must use HIBallastCode.

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Electrical wiring options: Consult factory. For motion or light sensor see folio OA20-10.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Skyway T8 1' x 4'Premium specification recessed air handling or static luminaires

Skyway’s aesthetically pleasing triple lens design features a clear conical prismatic center lens, enhanced by softly curved frost white acrylic lenses on each side, mounted in a regressed extruded aluminum frame with spring loaded latches. These 85% light transmission lenses, coupled with an internal reflector system coated with our 95% reflective white paint, creates our new, energy efficient Skyway.

30˚

60˚700

1400

2100

Candlepower CurveSKS1GPK232UNVHI

4"(102mm)

11 ⅞" (302mm)

4"(102mm)

11 ⅞" (302mm)

Reference data

Efficiency 66.4% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 49.6W Ballastfactor 0.77

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4' 1-T82-T8 32W SKS1GPK132

SKS1GPK232

Air handling 1' x 4' 1-T82-T8 32W SKA1GPK132

SKA1GPK232

Skyway Voltage Ballast Options Triple lens design 120=120V Seepage4.35 See page 4.35 Air handling or static 277=277V andpage4.130 UNV=120-277V

UNVSKS1GPK232 AHIExample

Page 39: Linear recessed and surface lighting

4.36 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Aletta louver shield T8 & T5 2' x 4' & 2' x 2'Direct/indirect recessed static luminaires

This family of recessed luminaires features a gently concaved diffuser that provides balanced luminosity, combined with distinctive and elegant architectural detailing.

Features•66.2%efficienttwolamp32WT82'x4'luminaire.•68.6%efficienttwolamp28WT52'x4'luminaire.•63.7%efficienttwolamp17WT82'x2'luminaire.•62.1%efficienttwolamp24WT5HO2'x2'luminaire.•Housingisblackbakedpolyesterenameldie-formedcodegaugecoldrolledsteel.20gaugeavailableforNYC.

•Thelensassemblyismadefromextruded100%DRFrost acrylic. Spring latch lens hinges, left and right sides independently, downward into the room cavity.

•ThecenterpanellouverishighpuritySemi-Specular,2-3/4"(6.99cm)openingx1-3/8"(3.49cm)deepon2"(5.08cm)centerswithmicro-prismaticsideoverlays.

•95%reflectivewhitepowderpaintedperformancekickreflector.

•Extrudedaluminumtrim,paintedwhite,interfaceswith ceilinggridorplasterframe(byothers).

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4. Conversion kit for 2' x 2' unit: FK92X2 .

Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

30˚

60˚975

1950

Candlepower Curve

ALS2GUL232UNVHI

5 ⅜"(137mm)

24" (610mm)

Reference data

Efficiency 66.2% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 59.0W Ballastfactor 0.88

30˚

60˚900

1800

Candlepower Curve

ALS2GUL228UNVPG

5 ⅜"(137mm)

24" (610mm)

5 ⅜"(137mm)

24" (610mm)

Reference data

Efficiency 68.6% Spacing ratio 1.1

Electronic ballast

Inputwatts(120V) 61.6W Ballastfactor 1.03

30˚

60˚450

900

Candlepower Curve

ALS2GUL217UNVHI

5 ⅜"(137mm)

24" (610mm)

Reference data

Efficiency 63.7% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 31.4W Ballastfactor 0.93

30˚

60˚600

1200

Candlepower Curve

ALS2GUL224UNVPG

5 ⅜"(137mm)

24" (610mm)

5 ⅜"(137mm)

24" (610mm)

Reference data

Efficiency 62.1% Spacing ratio 1.1

Electronic ballast

Inputwatts(120V) 47.7W Ballastfactor 1.0

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T83-T82-T53-T52-T5HO1-T5HO

32W32W28W28W54W54W

ALS2GUL232ALS2GUL332ALS2GUL228ALS2GUL328ALS2GUL254ALS2GUL154

Aletta Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.36 See page 4.36 Static panel w/elongated lens 277=277V andpage4.130 UNV=120-277V

UNV

2X2

ALS2GUL232 AHIExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'

2-T53-T52-T83-T82-T5HO3-T5HO

14W14W17W17W24W24W

ALS2GUL214ALS2GUL314ALS2GUL217ALS2GUL317ALS2GUL224ALS2GUL324

Aletta Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.36 See page 4.36 Static panel w/elongated lens 277=277V andpage4.130 UNV=120-277V

UNVALS2GUL224 APGExample

Whether used in office, conference, classroom or public areas, Aletta is truly easy on the eyes: comfortable lighting to see by and beautiful lighting to look at.

Aletta is a unique soft lighting coffer

Page 40: Linear recessed and surface lighting

4.37Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•69.8%efficienttwolamp32WT82'x4'luminaire.•73.6%efficienttwolamp28WT52'x4'luminaire.•68.4%efficienttwolamp17WT82'x2'luminaire.•66.8%efficienttwolamp24WT5HO2'x2'luminaire.•Housingisblackbakedpolyesterenameldie-formedcodegaugecoldrolledsteel.20gaugeavailableforNYC.

•Thelensassemblyismadefromextruded100%DRFrost acrylic. Spring latch lens hinges, left and right sides independently, downward into the room cavity.

•CenterPanelisconstructedwith24gaugepowderpainted CRS with linear micro-prismatic lens overlays. Elongatedlensopeningsare21-1/2"(54.61cm)windows.

•95%reflectivewhitepowderpaintedperformancekickreflector.

•Extrudedaluminumtrim,paintedwhite,interfaceswith ceilinggridorplasterframe(byothers).

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4. Conversion kit for 2' x 2' unit: FK92X2 .

Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Aletta panel shield T8 & T5 2' x 4' & 2' x 2'Direct/indirect recessed static luminaires

This family of recessed luminaires features a gently concaved diffuser that provides balanced luminosity, combined with distinctive and elegant architectural detailing.

2X2

30˚

60˚825

1650

Candlepower Curve

ALS2GUP232UNVHI

5 ⅜"(137mm)

24" (610mm)

Reference data

Efficiency 69.8% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 59.0W Ballastfactor 0.88

30˚

60˚750

1500

Candlepower Curve

ALS2GUP228UNVPG

5 ⅜"(137mm)

24" (610mm)

5 ⅜"(137mm)

24" (610mm)

Reference data

Efficiency 73.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 61.7W Ballastfactor 1.0

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T83-T82-T53-T52-T5HO1-T5HO

32W32W28W28W54W54W

ALS2GUP232ALS2GUP332ALS2GUP228ALS2GUP328ALS2GUP254ALS2GUP154

Aletta Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.37 See page 4.37 Static panel w/elongated lens 277=277V andpage4.130 UNV=120-277V

UNVALS2GUP232 AHIExample

30˚

60˚450

900

Candlepower Curve

ALS2GUP217UNVHI

5 ⅜"(137mm)

24" (610mm)

Reference data

Efficiency 68.4% Spacing ratio 1.1

Electronic ballast

Inputwatts(120V) 31.2W Ballastfactor 0.93

30˚

60˚525

1050

Candlepower Curve

ALS2GUP224UNVPG

5 ⅜"(137mm)

24" (610mm)

5 ⅜"(137mm)

24" (610mm)

Reference data

Efficiency 66.8% Spacing ratio 1.1

Electronic ballast

Inputwatts(120V) 47.5W Ballastfactor 1.0

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'

2-T53-T52-T83-T82-T5HO3-T5HO

14W14W17W17W24W24W

ALS2GUP214ALS2GUP314ALS2GUP217ALS2GUP317ALS2GUP224ALS2GUP324

Aletta Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.37 See page 4.37 Static panel w/elongated lens 277=277V andpage4.130 UNV=120-277V

UNVALS2GUP217 AHIExample Whether used in office, conference, classroom or public areas, Aletta is truly easy on the eyes: comfortable lighting to see by and beautiful lighting to look at.

Aletta is a unique soft lighting coffer

Page 41: Linear recessed and surface lighting

4.38 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•75.7%efficienttwolamp28WT52'x4'luminaire.•AltersoftwhitefilmoninsideofmicroperforatedMesh

Lamp Shields conceal lamp image providing balance between reflected and direct light.

•Seamlessweldedform:curvedtopandsidereflectorsare formed together without any gaps or visual barriers.

•Novisiblewelding,screws,latches,springs,hooks,rivetsor plastic supports.

•95%reflectiveAltersoftwhitepaintf inishandspecularinterior reflector.

•5½"deepone-piecebodyforeasyinstallation.•Swing-downmicroperforatedlampshieldsfor

easy relamping.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-grid,exposedslotT-gridand

drywall ceilings.•Luminairecanberowmounted

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PFT8 HI T8 PS3LPBT8 H3 T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚500

1000

1500

Candlepower Curve

1378

QHE2GPFOP232UNVHI 2' x 4' Microperforated mesh lamp shields, 2-lamp 32W T8

5½"(140mm)

23 13�16" (605mm)

47 13�16" (1214mm)

Reference data

Efficiency 70.3% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 62.0W Ballastfactor 0.88

RCR C.U.

1 74 3 57 5 45 7 36 9 29

30˚

60˚700

1400

2100

Candlepower Curve

1916

QHE2GPFOP332UNVH3 2' x 4' Microperforated mesh lamp shields, 3-lamp 32W T8

5½"(140mm)

24" (610mm)

47 13�16" (1214mm)

Reference data

Efficiency 64.3% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 85.0W Ballastfactor 0.88

RCR C.U.

1 67 3 52 5 41 7 33 9 27

30˚

60˚500

1000

1500

Candlepower Curve

1311

QHE2GPFOP228UNVPG 2' x 4' Microperforated mesh lamp shields, 2-lamp 28W T5

5½"(140mm)

47 13�16" (1214mm)

23 13�16" (605mm)

Reference data

Efficiency 75.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 65.0W Ballastfactor 0.88

RCR C.U.

1 79 3 61 5 48 7 38 9 31

Alter High Efficiency Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.38 See page 4.38 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQHE2GPFOP232 HIExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T52-T5HO3-T53-T5HO2-T83-T84-TT5

28W54W28W54W32W32W40, 50, 55W

QHE2GPFOP228 QHE2GPFOP254 QHE2GPFOP328 QHE2GPFOP354 QHE2GPFOP232 QHE2GPFOP332 QHE2GPFOP4FT

Alter high efficiency 2' x 4'Direct/indirect recessed static luminaires

With its balanced brightness and high-lumen package capable of accommodating up to 3 linear T8, T5 or 4 TT5 lamps, the Alter High Efficiency 2' x 4' delivers superior luminous efficacy that is perfect for wide open spaces, including workplaces with no or low partitions. This common-dimension luminaire is optically designed to create cost-effective specification-ready soft lighting for popular ceiling grids.

Page 42: Linear recessed and surface lighting

4.39Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Alter high efficiency 2' x 2'Direct/indirect recessed static luminaires

The compact architectural styling of Alter High Efficiency 2' x 2' provides shadowless balanced brightness combined with increased light efficacy in keeping with specification requirements. Designed for popular 2' x 2' grids, this luminaire allows more flexible, more symmetrical luminaire arrangements. It is suited to most environments, especially private offices where wide distribution, uniformly lit walls and low power densities are important considerations.

30˚

60˚500

1000

1500

Candlepower Curve

1444

QHE2GPFOP2FTUNVIB 2' x 2' Microperforated mesh lamp shields, 2-lamp 40W TT5

5½"(140mm)

23 13�16" (605mm)

23 13�16" (605mm)

5½"(140mm)

23 13�16" (605mm)

23 13�16" (605mm)

5½"(140mm)

23 13�16" (605mm)

23 13�16" (605mm)

Reference data

Efficiency 66.3% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 65.2W Ballastfactor 0.88

RCR C.U.

1 70 3 54 5 44 7 35 9 26

30˚

60˚250

500

750

Candlepower Curve

606

QHE2GPFOP217UNVHI 2' x 2' Microperforated mesh lamp shields, 2-lamp 17W T8

Reference data

Efficiency 64.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 74.0W Ballastfactor 0.88

RCR C.U.

1 68 3 53 5 41 7 33 9 27

30˚

60˚300

600

900

Candlepower Curve

820

QHE2GPFOP224UNVPG 2' x 2' Microperforated mesh lamp shields, 2-lamp 24W T5

Reference data

Efficiency 68.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 51.0W Ballastfactor 0.88

RCR C.U.

1 72 3 56 5 44 7 35 9 28

Alter High Efficiency Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.39 See page 4.39 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQHE2GPFOP232 IBExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'

1-TT52-TT52-T83-T82-T5HO3-T5HO

40, 50, 55W40, 50, 55W17W17W24W24W

QHE2GPFOP1FT QHE2GPFOP2FT QHE2GPFOP217 QHE2GPFOP317 QHE2GPFOP224 QHE2GPFOP324

Features•69%efficienttwolamp24WT5HO2'x2'luminaire.•AltersoftwhitefilmoninsideofmicroperforatedMesh

Lamp Shields conceal lamp and provides a balance between reflected and direct light.

•Seamlessweldedform:curvedtopandsidereflectorsare formed together without any gaps or visual barriers.

•Novisiblewelding,screws,latches,springs,hooks,rivetsor plastic supports.

•95%reflectiveAltersoftwhitepaintf inish.•5½"deep,one-piecebodyforeasyinstallation.•Swing-downlampshieldforeasyrelamping.•Easyaccesstoballastthroughlampcompartment.•Luminairecanberowmounted

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BF T8 PST8 HI 3LPBT8 H3 T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Page 43: Linear recessed and surface lighting

4.40 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•65%efficienttwolamp28WT51'x4'luminaire.•Even,shadowlesslightingreducesveilingreflections.•AltersoftwhitefilmoninsideofmicroperforatedMesh

Lamp Shields conceal lamp image providing a balance between reflected and direct light.

•95%reflectiveAltersoftwhitepaintf inish.•Swing-downlampshieldsforeasyrelamping.Easy

access to ballast through removable back reflector compartment.

•Novisiblewelding,screws,latches,springs,hooks,rivetsor plastic supports.

•Canberowmounted

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

T8 HI T5 PFT5 PG T8 PS

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter high efficiency 1' x 4'Direct/indirect recessed static luminaires

The Alter High Efficiency 1' x 4' brings together excellent power-density value, architectural styling and Alter’s characteristic low, balanced brightness glow producing a soft awareness of the lighting element. Its linear appearance suggests movement, making it ideally suited for specification in corridors and circulation areas.

30˚

60˚500

1000

1500

Candlepower Curve

1372

QHE1GPFOP232UNVHI 1' x 4' Microperforated mesh lamp shields, 2-lamp 32W T8

5"(127mm)

12" (305mm)

11 13�16"(300mm)

1 11�16"(43mm)

47 13�16" (1214mm)

9 ¾"(248mm)

Reference data

Efficiency 62.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 56.5W Ballastfactor 0.88

RCR C.U.

1 66 3 52 5 41 7 33 9 25

30˚

60˚500

1000

1500

Candlepower Curve

1375

QHE1GPFOP228UNVPG 1' x 4' Microperforated mesh lamp shields, 2-lamp 28W T5

5"(127mm)

12" (305mm)

11 13�16"(300mm)

1 11�16"(43mm)

47 13�16" (1214mm)

9 ¾"(248mm)

Reference data

Efficiency 65.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 65.0W Ballastfactor 0.88

RCR C.U.

1 68 3 54 5 43 7 35 9 27

Alter High Efficiency Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.40 See page 4.40 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQHE1GPFOP232 HIExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4'

1-T51-T5HO2-T52-T5HO2-T8

28W54W28W54W32W

QHE1GPFOP128 QHE1GPFOP154 QHE1GPFOP228 QHE1GPFOP254 QHE1GPFOP232

Page 44: Linear recessed and surface lighting

4.41Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•AltersoftwhitefilmoninsideofmicroperforatedMesh

Lamp Shields conceal lamp image providing balance between reflected and direct light.

•Seamlessweldedform:curvedtopandsidereflectorsare formed together without any gaps or visual barriers.

•Novisiblewelding,screws,latches,springs,hooks,rivetsor plastic supports.

•95%reflectiveAltersoftwhitepaintf inishandspecularinterior reflector.

•5½"deepone-piecebodyforeasyinstallation.•Swing-downmicroperforatedlampshields

for easy relamping.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-grid,exposedslotT-gridand

drywall ceilings.•Fullyrecessedluminaireandlampcompartment.•Luminairecanberowmounted (notapplicablewiththeairhandlingoption)

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PFT8 HI T8 PS3LPBT8 H3 Program start T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚400

800

12001135

Candlepower Curve

QVS2GPFOS232UNVHI 2'x4'Microperforatedmeshlampshields(static),2-lamp32WT8

5½"(140mm)

23 13�16" (605mm)

47 13�16" (1214mm)

Reference data

Efficiency 56.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 62.0W Ballastfactor 0.88

RCR C.U.

1 60 3 46 5 37 7 29 9 24

30˚

60˚700

1400

2100

1751

Candlepower Curve

QVA2GPFOP232UNVHI 2'x4'Microperforatedmeshlampshields(airhandling),2-lamp32WT8

5⅛"(130mm)

23 13�16" (605mm)

40" (1016mm)48" (1120mm)

Reference data

Efficiency 49.2% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 62.0W Ballastfactor 0.88

RCR C.U.

1 52 3 41 5 32 7 26 9 19

Alter Classic Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.41 See page 4.41 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQVS2GPFOS232 HIExample

One-piece lamp shieldReplace OS in the ordering info by OP. OS Static only.

Air handling Replace QVS in the ordering info by QVA and OS to OP. N/Afor1'x4'.

Clear Acrylic Plate Drop Down Element

Clear polished acrylic drop-down visual element with projected color face. Substitute acrylic color suffix in place of open slot only.Suffix: GC(clear) GB(blue)

GG(green) GR(red)e.g.QVS2GPFOS (OS=OpenSlot) e.g.QVS2GPFGB (GB=BlueAcrylic)For other colors or special orders, consult your Philips Lightolier representative.

Ordering information For QVA see below for ordering instructions

Type Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T52-T5HO3-T53-T5HO2-T83-T84-TT5

28W54W28W54W32W32W40, 50, 55W

QVS2GPFOS228 QVS2GPFOS254 QVS2GPFOS328 QVS2GPFOS354 QVS2GPFOS232 QVS2GPFOS332 QVS2GPFOS4FT

Alter classic 2' x 4'Direct/indirect air handling or static recessed luminaires

Functionality with crisp clean lines describes the 2' x 4' Alter luminaire. Using very popular T5, T8 and TT5 lamp technology, it offers the perfect lighting solution for spaces where larger ceiling grids are used. This luminaire provides visual interest, soft balanced brightness and is well suited for larger open spaces. When installed in continuous rows this luminaire can also create a very clean cove-like appearance.

Page 45: Linear recessed and surface lighting

4.42 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•AltersoftwhitefilmoninsideofmicroperforatedMesh

Lamp Shields conceal lamp and provides a balance between reflected and direct light.

•Seamlessweldedform:curvedtopandsidereflectorsare formed together without any gaps or visual barriers.

•Novisiblewelding.Specularinteriorreflectorwithsolidlamp shield only.

•95%reflectiveAltersoftwhitepaintf inish.•5½"deep,one-piecebodyforeasyinstallation (QVSonly).

•Swing-downlampshieldforeasyrelamping.•Easyaccesstoballastthroughlampcompartment.•Luminairecanberowmounted (notapplicablewiththeairhandlingoption)

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP 55W TT5 BF T8 HI 3LPBT8 H3Program start T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter classic 2' x 2'Direct/indirect air handling or static recessed luminaires

Architectural styling combined with visually exciting elements can provide shadowless balanced brightness. Low brightness glow provides the occupant with a soft awareness of the lighting element, while increasing depth perception and sense of orientation within the space. These luminaires offer a good lighting solution for open circulation for a distinctive appearance.

30˚

60˚500

1000

1500

1227

Candlepower Curve

QVS2GPFOS2FTUNVIB 2'x2'Microperforatedmeshlampshields(static),2-lamp40WTT5

5½"(140mm)

23 13�16" (605mm)

23 13�16" (605mm)

Reference data

Efficiency 58.5% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 74.0W Ballastfactor 0.88

RCR C.U.

1 61 3 48 5 38 7 30 9 25

30˚

60˚200

400

600590

Candlepower Curve

QVA2GPFOP2FTUNVIB 2'x2'Microperforatedmeshlampshields(airhandling),2-lamp40WTT5

5⅛"(130mm)

24" (610mm)

20" (508mm)24" (610mm)

Reference data

Efficiency 50.8% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 74.0W Ballastfactor 0.88

RCR C.U.

1 49 3 38 5 31 7 25 9 18

Alter Classic Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.42 See page 4.42 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQVS2GPFOS2FT IBExample

One-piece lamp shieldReplace OS in the ordering info by OP. OS Static only.

Air handling Replace QVS in the ordering info by QVA and OS to OP. N/Afor1'x4'.

Clear acrylic plate drop down element

Clear polished acrylic drop-down visual element with projected color face. Substitute acrylic color suffix in place of open slot only.Suffix: GC(clear) GB(blue)

GG(green) GR(red)e.g.QVS2GPFOS (OS=OpenSlot) e.g.QVS2GPFGB (GB=BlueAcrylic)For other colors or special orders, consult your Philips Lightolier representative.

Ordering information For QVA see below for ordering instructions

Type Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'

1-TT52-TT52-T83-T82-T5HO3-T5HO

40, 50, 55W40, 50, 55W17W17W24W24W

QVS2GPFOS1FT QVS2GPFOS2FT QVS2GPFOS217 QVS2GPFOS317 QVS2GPFOS224 QVS2GPFOS324

Page 46: Linear recessed and surface lighting

4.43Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Alter classic 1' x 4'Direct/indirect static recessed luminaires

The Alter 1' x 4' combines architectural styling with visually exciting elements to provide a shadowless balanced brightness. Linear appearance makes this luminaire ideally suited for corridors and circulation areas.

Features•Even,shadowlesslightingreducesveilingreflections.•AltersoftwhitefilmoninsideofmicroperforatedMesh

Lamp Shields conceal lamp image providing a balance betweenreflectedanddirectlight.Notavailableinair handling.

•95%reflectiveAltersoftwhitepaintf inish.•Swing-downlampshieldsforeasyrelamping.Easy

access to ballast through removable back reflector compartment.

•Novisiblewelding,screws,latches,springs,hooks,rivetsor plastic supports.

•Canberowmounted

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BF T8 PST8 HI T5 PG

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Air handling:N/Afor1'x4'model.Available for Standards, Slot and Concealed.

30˚

60˚400

800

12001145

Candlepower Curve

QVS1GPFOS232UNVHI 1' x 4' Microperforated mesh lamp shields, 2-lamp 32W T8

5"(127mm)

12" (305mm)

47 13�16" (1214mm)

Reference data

Efficiency 50.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 62.0W Ballastfactor 0.88

RCR C.U.

1 53 3 42 5 33 7 27 9 22

30˚

60˚400

800

1200

1053

Candlepower Curve

QVS1GPFOS2FTUNVIB 1' x 4' Microperforated mesh lamp shields, 2-lamp 40W TT5

47 13�16" (1214mm)

5"(127mm)

12" (305mm)

Reference data

Efficiency 47.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 74.0W Ballastfactor 0.88

RCR C.U.

1 52 3 41 5 32 7 26 9 19

Alter Classic Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.43 See page 4.43 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQVS1GPFOS232 HIExample

One-piece lamp shieldReplace OS in the ordering info by OP.

Clear acrylic plate drop down element

Clear polished acrylic drop-down visual element with projected color face. Substitute acrylic color suffix in place of open slot only.Suffix: GC(clear) GB(blue)

GG(green) GR(red)e.g.QVS1GPFOS (OS=OpenSlot) e.g.QVS1GPFGB (GB=BlueAcrylic)For other colors or special orders, consult your Philips Lightolier representative.

Ordering informationType Size Lamp qty –type Lamp watts Cat. no. Exposed T-grid Cat. no. Slot or Concealed T

Static 1' x 4'

1-T51-T5HO2-T52-T5HO2-T82-TT5

28W54W28W54W32W40, 50, 55W

QVS1GPFOS128 QVS1GPFOS154 QVS1GPFOS228 QVS1GPFOS254 QVS1GPFOS232 QVS1GPFOS2FT

QVS1TPFOS128 QVS1TPFOS154 QVS1TPFOS228 QVS1TPFOS254 QVS1TPFOS232 QVS1TPFOS2FT

Page 47: Linear recessed and surface lighting

4.44 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•AltersoftwhitefilmoninsideofmicroperforatedMesh

Lamp Shields conceal lamp image providing balance between reflected and direct light.

•Novisiblewelding,screws,latches,springs,hooks,rivetsor plastic supports.

•Airhandlingversionavailable.•95%reflectiveAltersoftwhitepaintf inishandspecular

interior reflector.•5½"deepone-piecebodyforeasyinstallation.•Swing-downmicroperforatedlampshieldsforeasy

relamping.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-grid,exposedslotT-gridand

drywall ceilings.•Fullyrecessedluminaireandlampcompartment.•Onlyluminairesofsamesizecanberowmounted

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB T5 PF50W TT5 BP T8 PS55W TT5 BFT8 HI3LPBT8 H3T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 20x40 unit: FK920X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Filler Plate: Sold separately. For20"x60"openingwith20"x48" luminaire: FPQVS2060.

Alter classic 20"x48"&500mmx48"Direct/indirect static recessed luminaires

20"x48"luminairesfor5-footmoduleceilinggrid(3-part20"x60"modules)andmetric luminaires.

30˚

60˚400

800

12001089

Candlepower Curve

QVS5GPFOS232UNVHI 20"x48"Microperforatedmeshlampshields2-lamp32WT8

5 3�16"(148mm)

19 13�16"(503mm)

9 ⅞"(251mm)

20" (508mm)

47 13�16" (1214mm)23 15�16" (608mm)

Reference data

Efficiency 53.4% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 56.0W Ballastfactor 0.9

RCR C.U.

1 59 3 49 5 41 7 35 9 30

Alter Classic Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.44 See page 4.44 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQVS5GPFOS232 HIExample

One-piece lamp shieldReplace OS in the ordering info by OP. OS Static only.

Ordering informationType Size Lamp qty –type Lamp watts Cat. no. Static Cat. no. Air handling*

Static 20"x48"

2-T52-T5HO3-T53-T5HO2-T83-T8

28W54W28W54W32W32W

QVS5GPFOS228 QVS5GPFOS254 QVS5GPFOS328 QVS5GPFOS354 QVS5GPFOS232 QVS5GPFOS332

QVA5GPFOP228 QVA5GPFOP254 QVA5GPFOP232

Static 500mmx48"

2-T52-T5HO3-T53-T5HO2-T83-T8

28W54W28W54W32W32W

QVS5MPFOS228 QVS5MPFOS254 QVS5MPFOS328 QVS5MPFOS354 QVS5MPFOS232 QVS5MPFOS332

* Only luminaires with one piece lamp shield, shown here, are available for air handling.

Page 48: Linear recessed and surface lighting

4.45Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Alter classic air 2' x 4' & 2' x 2'Direct/indirect recessed luminaires

The compact architectural styling of Alter Classic 2' x 2' provides shadowless balanced brightness. Designed for popular 2' x 2' grids, this luminaire allows more flexible, more symmetrical luminaire arrangements. It is suited to most environments, especially private offices where wide distribution and uniformly light walls are important considerations.

Features•Full-lengthairslotwithrightanglestiffenerformaximum

rigidity and no slot interference.•Dualswingdownsolidlampshieldsseparatedby

luminous strip for easy relamping and maintenance.•Fullyrecessedluminaireandwithtwoseparate

lamp compartments.•95%ReflectiveAltersoftwhitepaintf inish.•Specularinteriorreflector.•Onepiecebodyforeasyinstallation.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-Gridceilings.•Optionalacrylicdrop-downvisualelement.

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)

add as suffix, e.g. 120SB.

Bal. Type <10THD <20THD PowerSpecElectronic HDF Dimming

T5 Linear PG – –40W TT5 IB SB PB50W TT5 – BP –55W TT5 BF – –T8 HI SO PS3LPBT8 H3 03 –DALIBallast DA – –

LPB=Numberoflampsperballast.

DALI=digitaladdressabledimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4. Conversion kit for 2' x 2' unit: FK92X2 .

Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚350

700

1050

Candlepower Curve

QVA2GPFOP332UNVH3 2' x 4' Solid lamp shields, 3-lamp 32W T8

5⅛"(130mm)

24" (610mm)

24"(610mm)

20"(508mm)

Reference data

Efficiency 52.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 84.3W Ballastfactor 0.88

Coefficients of utilization

RF 20% RC 80% RW 70 50 30 RCR

1 58 56 54 3 49 44 40 5 41 35 30 7 35 28 23 10 27 20 16

30˚

60˚400

800

1200

950

Candlepower Curve

QVA2GPFOP2FT120SB 2' x 2' Solid lamp shields, 2-lamp 40W TT5

5⅛"(130mm)

24" (610mm)

48"(1220mm)

40"(1016mm)

Reference data

Efficiency 50.8% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 64.8W Ballastfactor 0.88

Coefficients of utilization

RF 20% RC 80% RW 70 50 30 RCR

1 56 54 52 3 47 42 39 5 40 34 30 7 34 27 23 10 27 21 16

Alter Classic Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.45 See page 4.45 w/one piece lamp shield 277=277V andpage4.72 UNV=120-277V

120QVA2GPFOP2FT SBExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static Air supply or Air return

2' x 4'

2-T83-T82-T53-T52-T53-T54-TT5

32W32W28W28W54W54W40, 50, 55W

QVA2GPFOP232 QVA2GPFOP332 QVA2GPFOP228 QVA2GPFOP328 QVA2GPFOP254 QVA2GPFOP354 QVA2GPFOP4FT

Static Air supply or Air return

2' x 2'

1-TT52-TT52-T83-T82-T53-T5

40, 50W40, 50W17W17W24W24W

QVA2GPFOP1FT QVA2GPFOP2FT QVA2GPFOP217 QVA2GPFOP317 QVA2GPFOP224 QVA2GPFOP324

Page 49: Linear recessed and surface lighting

4.46 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•MicroperforatedMeshLampShieldsprovideasoft

awareness of the light source.•AltersoftwhitefilmoninsideofmicroperforatedMesh

Lamp Shields conceal lamp image providing balance between reflected and direct light.

•4"deep,meetsADAwhenwallmounted.•Allluminairesurfaceshavethesamevisualappearance.•95%reflectiveAltersoftwhitepaintf inish.•One-piecebodyforeasyinstallation.•Swingopenlampshieldsforeasyrelamping.•Novisiblewelding,screws,latches,springs,hooks,

rivets or plastic supports

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVIB.

Ballast type

Electronic PowerSpec HDF dimming

18W TT5 BA 40W TT5 PB40W TT5 IB T8 PS50W TT5 BP55W TT5 BFT8 HI

Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter classic wall 9"x12",9"x24"&9"x48"Direct/indirect sconce luminaires

This simple and clean design can create beautiful slim rows of perforated soft light or add asplashoflightinasmallspace.TwohighlumenTT5Bi-Tubeor2T8lampscanprovidehigh illuminationlevelswhenusedinpublicspaces.(Luminairenotforthroughwiring).

120˚

150˚

1200

600

0

Candlepower Curve

228

QVW8SPFOS2FTUNVIB Surface sconce microperforated mesh lamp shields, 2-lamp 40W TT5

Reference data

Efficiency 69.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 68.4W Ballastfactor 0.88

4"(102mm)

9" (229mm)

12" (305mm) - 24" (610mm) - 48" (1220mm)

RCR C.U.

1 60 3 46 5 36 7 29 10 21

Alter Classic Wall Voltage Ballast Options Direct/indirect Sconce 120=120V Seepage4.46 See page 4.46 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQVW8SPFOS2FT IBExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static9"x12"9"x24"9"x48"

2-TT52-TT52-T8

18W40, 50, 55W32W

QVW8SPFOS218 QVW8SPFOS2FT QVW8SPFOS232

Page 50: Linear recessed and surface lighting

4.47Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Alter Wal-Lyter 1' x 2' & 1' x 4'Direct/indirect luminaires

This recessed wall washer features smooth-flowing curves and a unique design that incorporates a single lateral lamp and reflector. The result is an asymmetrical light distribution that creates a soft glow and projects additional uniform light onto the wall. Style-matched with Alter full basket design.

Features•MicroperforatedMeshLampShieldsprovidessoft

awareness of the light source.•Swing-downlampshieldforeasyrelamping.•Asymmetricalopticalsystemprovidesasoftuniform

wall wash

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BF T8 PST8 HI T5 PG

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚400

800

1200

Candlepower Curve

1056

QVS1GPFAD232UNVHI 1' x 4' Asymmetrical distribution microperforated mesh lamp shields, 2-lamp 32W T8

5"(127mm)

12" (305mm)

48" (1220mm)

Reference data

Efficiency 56.1%

Electronic ballast

Inputwatts(120V) 56.7W Ballastfactor 0.88

RCR C.U.

1 58 3 44 5 34 7 28 10 21

Alter Wal-Lyter Voltage Ballast Options Direct/indirect asymmetrical 120=120V Seepage4.47 See page 4.47 distribution w/microperforated 277=277V andpage4.72 mesh lamp shields UNV=120-277V

UNVQVS1GPFAD232 HIExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 2' 2-T8 17W QVS1GPFAD217

Static 1' x 4'

2-TT51-T51-T5HO2-T52-T5HO1-T82-T8

40, 50, 55W28W54W28W54W32W32W

QVS1GPFAD2FT QVS1GPFAD128 QVS1GPFAD154 QVS1GPFAD228 QVS1GPFAD254 QVS1GPFAD132 QVS1GPFAD232

Page 51: Linear recessed and surface lighting

4.48 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter louver 2' x 4' & 2' x 2'Direct/indirect recessed static luminaires

The Alter Louver luminaire is designed for areas requiring higher light levels. The flat blade perforated louver provides a soft glow shielding. A lens overlay prevents direct view of the lamp source.

Features•Flatbladelouverlensoverlaylampshieldandperforated

curved side lamp shield.•Seamlessweldedform:curvedtopandsidereflectors

are formed together without any gaps or visual barriers.•Novisiblewelding,screws,latches,springs,hooks,rivets

or plastic supports.•95%reflectiveAltersoftwhitepaintf inish.•5½"deep,one-piecebodyforeasyinstallation.•Swing-downlampshieldforeasyrelamping.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-grid,exposedslotT-gridceilingsanddrywallceilings(seepage4.218).

•Luminairecanberowmounted

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BF T8 PS3LPB40WTT5 I3T8 HI 3LPBT8 H3 Program start T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 . Conversion kit for 2' x 4' unit: FK92X4.

Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚600

1200

1800

Candlepower Curve

1599

QVS2GPFLW332UNVH3 2' x 4' Microperforated mesh white lamp shields /white solid blades, 3-lamp 32W T8

5½"(140mm)

23 13�16" (605mm)

47 13�16" (1214mm)

Reference data

Efficiency 56.7% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 88.6W Ballastfactor 0.88

RCR C.U.

1 60 3 47 5 37 7 29 10 21

5½"(140mm)

23 13�16" (605mm)

23 13�16" (605mm)

30˚

60˚300

600

900

Candlepower Curve

782

QVS2GPFLW317UNVH3 2' x 2' Microperforated mesh white lamp shields/white solid blades, 3-lamp 17W T8

Reference data

Efficiency 55.4% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 50.1W Ballastfactor 0.88

RCR C.U.

1 59 3 46 5 36 7 29 10 21

Alter Louver Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.48 See page 4.48 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQVS2GPFLW332 H3Example

White solid blade

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T83-T82-T53-T52-T5HO3-T5HO

32W32W28W28W54W54W

QVS2GPFLW232 QVS2GPFLW332 QVS2GPFLW228 QVS2GPFLW328 QVS2GPFLW254 QVS2GPFLW354

Static 2' x 2'

2-TT53-TT52-T83-T82-T5HO3-T5HO

40, 50, 55W40, 50, 55W17W17W24W24W

QVS2GPFLW2FT QVS2GPFLW3FT QVS2GPFLW217 QVS2GPFLW317 QVS2GPFLW224 QVS2GPFLW324

Page 52: Linear recessed and surface lighting

4.49Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Flatbladelouverlensoverlaylampshieldandperforated

curved side lamp shield.•Seamlessweldedform:curvedtopandsidereflectors

are formed together without any gaps or visual barriers.•Novisiblewelding,screws,latches,springs,hooks,rivets

or plastic supports.•95%reflectiveAltersoftwhitepaintf inish.•5½"deep,one-piecebodyforeasyinstallation.•Swing-downlampshieldforeasyrelamping.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-grid,exposedslotT-gridceilingsanddrywallceilings(seepage4.218).

•Luminairecanberowmounted

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

T8 HI T5 PF3LPBT8 H3 T8 PSProgram start T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter louver 1' x 4'Direct/indirect recessed static luminaires

The Alter Louver luminaire is designed for areas requiring higher light levels. The flat blade perforated louver provides a soft glow shielding. A lens overlay prevents direct view of the lamp source.

30˚

60˚600

1200

1800

1465

Candlepower Curve

QVS1GPFLG232UNVHI 1' x 4' Microperforated mesh white lamp shields/grey solid louver blades, 2-lamp 32W T8

5"(127mm)

12" (305mm)

48" (1220mm)

Reference data

Efficiency 59.8% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 50.1W Ballastfactor 0.88

RCR C.U.

1 64 3 51 5 41 7 33 10 24

Alter Louver Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.49 See page 4.49 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQVS2GPFLV332 H3Example

Ordering information

Type Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4'2-T82-T52-T5HO

32W28W54W

QVS1GPFLW232 QVS1GPFLW228 QVS1GPFLW254

White solid blade

Page 53: Linear recessed and surface lighting

4.50 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter Metalyte 2' x 4' & 2' x 2'Direct/indirect recessed static luminaires

Sporting a modern look for modern decors, Alter Metalyte emit surprisingly soft light and a uniform, low-level luminance. Once illuminated the reflector and mesh lamp shields appear bathed in the same uniform brightness. The mixture of direct lighting and backlighting provides a mitigated yet stunning effect. These luminaires blend in particularly well with interiors featuring metallic elements.

Features•Seamlesssemi-specularmetallicreflectorwith

lengthwise ridges.•Availableone-piecemeshlampshieldswithnoslot.•Optionaldrop-downvisualelementcomes invariouscolors(seepage4.72).

•Suitedtorowmountingforacontinuouscoveeffect

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T8(32Wonly) PS55W TT5 BF IGENDALI DAT8 HI 3LPBT8 H3 T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4. Conversion kit for 2' x 2' unit: FK92X2 .

30˚

60˚400

800

1200

Candlepower Curve

907

QVS2GPTOS232UNVHI 2' x 4' Microperforated mesh lamp shields, 2-lamp 32W T8

5½"(140mm)

24" (610mm)

48" (1220mm)

Reference data

Efficiency 44.8% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 57.1W Ballastfactor 0.88

RCR C.U.

1 47 3 37 5 29 7 23 9 17

30˚

60˚500

1000

1500

Candlepower Curve

1273

QVS2GPTOS332UNVH3 2' x 4' Microperforated mesh lamp shields, 3-lamp 32W T8

5½"(140mm)

24" (610mm)

48" (1220mm)

Reference data

Efficiency 39.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 80.4W Ballastfactor 0.88

RCR C.U.

1 42 3 33 5 26 7 21 9 19

30˚

60˚400

800

1200

Candlepower Curve

939

QVS2GPTOS2FTUNVIB 2' x 2' Microperforated mesh lamp shields, 2-lamp 40W TT5

5½"(140mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 39.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 80.4W Ballastfactor 0.88

RCR C.U.

1 42 3 33 5 26 7 21 9 19

Alter Metalyte Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.50 See page 4.50 w/mesh lamp shields 277=277V andpage4.72 UNV=120-277V

UNVQVS2GPTOS2FT IB

Example

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static* 2' x 4'

2-T83-T82-T53-T52-T5HO3-T5HO4-TT5

32W32W28W28W54W54W40, 50, 55W

QVS2GPTOS232 QVS2GPTOS332 QVS2GPTOS228 QVS2GPTOS328 QVS2GPTOS254 QVS2GPTOS354 QVS2GPTOS4FT

Static* 2' x 2'

1-TT52-TT52-T83-T82-T5HO3-T5HO

40, 50, 55W40, 50, 55W17W17W24W24W

QVS2GPTOS1FT QVS2GPTOS2FT QVS2GPTOS217 QVS2GPTOS317 QVS2GPTOS224 QVS2GPTOS324

* For optional one-piece lamp shield, replace OS by OP.

Page 54: Linear recessed and surface lighting

4.51Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Alter Metalyte louver 2' x 4' & 2' x 2'Direct/indirect recessed static luminaires

Sporting a modern look for modern decors, Alter Metalyte louver emit surprisingly soft light and a uniform, low-level luminance. This luminaire allows up to 3 TT5 lamps for a higher lumen package. Once illuminated the reflector and mesh lamp shield appear bathed in the same uniform brightness. The mixture of direct lighting, backlighting and the choice of louver and blades finishes indeed provides a mitigated yet stunning effect. These luminaires blend in particularly well with interiors featuring metallic elements.

30˚

60˚300

600

900

Candlepower Curve

QVS2GPTLG232UNVHI 2' x 4' Microperforated mesh white lamp shields /grey solid louver blades, 2-lamp 32W T8

5½"(140mm)

24" (610mm)

48" (1220mm)

Reference data

Efficiency 41.1% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 62.0W Ballastfactor 0.88

RCR C.U.

1 43 3 34 5 27 7 21 9 16

30˚

60˚600

1200

1800

Candlepower Curve

1441

QVS2GPTLG332UNVH3 2' x 4' Microperforated mesh white lamp shields /grey solid louver blades, 3-lamp 32W T8

5½"(140mm)

24" (610mm)

48" (1220mm)

Reference data

Efficiency 40.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 85.0W Ballastfactor 0.88

RCR C.U.

1 47 3 37 5 29 7 23 9 19

Features•Seamlesssemi-specularmetallicreflectorwith

lengthwise ridges.•Lensoverlaypreventingdirectviewofthelampsource.•Choiceofthreeflatbladelouvers. (Seebottomofpagefororderinginformation).

•Suitedtorowmountingforacontinuouscoveeffect.

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BF T8(32Wonly) PS3LPB40WTT5 I3 IGENDALI DAT8 HI 3LPBT8 H3 T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4. Conversion kit for 2' x 2' unit: FK92X2 .

Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚400

800

1200

Candlepower Curve

939

QVS2GPTLG2FTUNVIB 2' x 2' Microperforated mesh white lamp shields /grey solid louver blades, 2-lamp 40W TT5

5½"(140mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 40.7% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 74.0W Ballastfactor 0.88

RCR C.U.

1 43 3 34 5 27 7 22 9 17

Example

Alter Metalyte Louver Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.51 See page 4.51 w/mesh white lamp 277=277V andpage4.72 shields/grey solid UNV=120-277V louver blades

UNVQVS2GPTLG2FT IB

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static* 2' x 4'

2-T83-T82-T53-T52-T5HO3-T5HO

32W32W28W28W54W54W

QVS2GPTLG232 QVS2GPTLG332 QVS2GPTLG228 QVS2GPTLG328 QVS2GPTLG254 QVS2GPTLG354

Static* 2' x 2'

2-TT53-TT52-T83-T82-T5HO3-T5HO

40, 50, 55W40, 50, 55W17W17W24W24W

QVS2GPTLG2FT QVS2GPTLG3FT QVS2GPTLG217 QVS2GPTLG317 QVS2GPTLG224 QVS2GPTLG324

Page 55: Linear recessed and surface lighting

4.52 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter OPL 2' x 4'Direct/indirect static curved opal lens recessed luminaires

Sober design, high performance and Alter’s trademark balanced brightness come together beautifully in Alter OPL 2' x 4'. Exhibiting pure form, the one-piece opal acrylic lens produces soft glowing illumination that uniformly lights all surfaces, while creating a feeling of spaciousness. Exceptional value for lighting efficiency provides increased specification opportunities. Models with up to 3 high-output lamps ensure extra-wide lighting distribution in larger open spaces, including workplaces with no or low partitions. Also, this luminaire is well-suited to continuous rows, creat ing a continuous cove effect that enhances architectural perspectives.

Features•80.2%efficientthreelamp32WT82'x4'luminaire.•Altersoftwhitefilminsideofopalacryliclampshield

conceals lamp image, providing balance between reflected and direct light.

•Seamlessweldedform:curvedtopandsidereflectorsare formed together without any gaps or visual barriers.

•Novisiblewelding,screws,latches,springs,hooks,rivetsor plastic supports.

•95%reflectiveAltersoftwhitepaintf inishandspecularinterior reflector.

•5½"deepone-piecebodyforeasyinstallation.•Swing-downlampshieldforeasyrelamping.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-grid,exposedslotT-gridand

drywall ceilings.•Fullyrecessedluminaireandlampcompartment.•Luminairecanberowmounted.•Airhandlingversionunavailable

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

T8 HI T5 PF3LPBT8 H3 T5 PST5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚800

1600

2400

Candlepower Curve

2283

QVS2GOLOP332UNVH3 2' x 4' One-piece opal acrylic lamp shields, 3-lamp 32W T8

5½"(140mm)

24" (610mm)

48" (1220mm)

Reference data

Efficiency 80.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 86.9W Ballastfactor 0.9

RCR C.U.

1 78 3 65 5 55 7 47 9 40

Alter OPL Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.52 See page 4.52 w/one-piece opal lens 277=277V (347VN/A) andpage4.72 UNV=120-277V

UNVQVS2GOLOP232 HIExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T83-T82-T53-T52-T5HO3-T5HO

32W32W28W28W54W54W

QVS2GOLOP232 QVS2GOLOP332 QVS2GOLOP228 QVS2GOLOP328 QVS2GOLOP254 QVS2GOLOP354

Page 56: Linear recessed and surface lighting

4.53Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Altersoftwhitefilminsideofopalacryliclampshield

conceals lamp image, providing balance between reflected and direct light.

•Seamlessweldedform:curvedtopandsidereflectorsare formed together without any gaps or visual barriers.

•Novisiblewelding,screws,latches,springs,hooks,rivetsor plastic supports.

•95%reflectiveAltersoftwhitepaintf inishandspecularinterior reflector.

•5½"deepone-piecebodyforeasyinstallation.•Swing-downlampshieldforeasyrelamping.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-grid,exposedslotT-gridand

drywall ceilings.•Fullyrecessedluminaireandlampcompartment.•Optionalhold-downclipsavailable.•Luminairecanberowmounted.•Airhandlingversionnotavailable

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVIB.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BF T8 PS3LPB40WTT5 I3T8 HI 3LPBT8 H3 Program start T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter OPL 2' x 2'Direct/indirect static curved opal lens recessed luminaires

The one-piece opal acrylic lens features an attractive, uncluttered, flush-ceiling, shadowless look that adds elegance to modern interiors. What’s more, Alter OPL offers excellent value, while providing superior efficiency. Alter OPL is ideal for open-plan environments, private offices, entrance halls and public spaces.

30˚

60˚600

1200

1800

Candlepower Curve

1611

QVS2GOLOP2FTUNVIB 2' x 2' One-piece opal acrylic lamp shields, 2-lamp 40W TT5

5½"(140mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 71.8% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 64.6W Ballastfactor 0.88

RCR C.U.

1 81 3 63 5 50 7 40 9 30

Alter OPL Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.53 See page 4.53 w/one-piece opal lens 277=277V andpage4.72 UNV=120-277V

UNVQVS2GOLOP2FT IBExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'

1-TT52-TT53-TT52-T83-T82-T5HO3-T5HO

40, 50, 55W40, 50, 55W40, 50, 55W17W17W24W24W

QVS2GOLOP1FT QVS2GOLOP2FT QVS2GOLOP3FT QVS2GOLOP217 QVS2GOLOP317 QVS2GOLOP224 QVS2GOLOP324

Page 57: Linear recessed and surface lighting

4.54 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter Waves 2' x 4' & 2' x 2'Direct/indirect static side basket recessed luminaires

Architectural styling and curved door elements come together in this unique luminaire that provides balanced lighting environment. Dual-door light effect offers visual interest and soft awareness of the lighting element. Twin lateral opposing curved door lamp shields and Alter Soft Light reflector create soft light to enhance any decor.

Features•Microperforatedmeshlampshieldsprovidesoft

awareness of light source.•Curveddoorlaterallampshieldsprojectlightupwards

to reflector and provide indirect light.•95%reflectiveAltersoftwhitepaintf inish.•Fullyrecessedlampshieldsandreflector.•Curvedtopandsidesofreflectorareformedtogether

without any gaps or visual barriers.•Novisiblewelding,screws,latches,springs,holes,rivets

or plastic supports.•Optionalsolidorcurvedlampshields.•Altersoftwhitefilminsideofmicroperforatedmesh

lamp shield conceals lamp image, providing balance between reflected and direct light.

•Swing-downlampshieldforeasyrelamping.•Easyaccesstoballast.•FitsstandardT-grid,exposedslot-T-gridanddrywallceilings(seepage4.218).

•Notsuitableforrowmounting

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BF T8 PST8 HI 3LPBT8 H3 4LPBT8 H4Program start T5 PG

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4. Conversion kit for 2' x 2' unit: FK92X2 .

Hold down clips:StandardT15/16"only:QVS-HD.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚400

800

1200

Candlepower Curve

1066

QVL2GPFSS232UNVHI 2' x 4' Microperforated mesh dual lateral side lamp shields, 2-lamp 32W T8

5½"(140mm)

24" (610mm)

48" (1220mm)

Reference data

Efficiency 64.7% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 62.0W Ballastfactor 0.88

RCR C.U.

1 66 3 48 5 37 7 30 10 23

30˚

60˚800

1600

2400

Candlepower Curve

1993

QVL2GPFSS432UNVH4 2’ x 4’ Microperforated mesh dual lateral side lamp shields, 4-lamp 32W T8

5½"(140mm)

24" (610mm)

48" (1220mm)

Reference data

Efficiency 58.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 112.0W Ballastfactor 0.88

RCR C.U.

1 60 3 45 5 35 7 28 10 20

30˚

60˚300

600

900

Candlepower Curve

851

QVL2GPFSS2FTUNVIB 2' x 2' Microperforated mesh dual lateral side lamp shields, 2-lamp 40W TT5

5½"(140mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 45.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 74.0W Ballastfactor 0.88

RCR C.U.

1 47 3 36 5 28 7 22 10 178

Alter Waves Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.54 See page 4.54 w/microperforated mesh 277=277V andpage4.72 dual lateral lamp shields UNV=120-277V

UNVQVL2GPFSS2FT IBExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T82-T5HO4-T54-T5HO2-T84-T8

28W54W28W54W32W32W

QVL2GPFSS228 QVL2GPFSS254 QVL2GPFSS428 QVL2GPFSS454 QVL2GPFSS232 QVL2GPFSS432

Static 2' x 2' 2-TT52-T5HO

40, 50, 55W24W

QVL2GPFSS2FT QVL2GPFSS224

* For optional curved lamp shield replace Wave lamp shield SS with SR .

Page 58: Linear recessed and surface lighting

4.55Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Utilizesonehigh-lumenTT5compactfluorescentlamp.•Microperforatedmeshlampshieldprovidessoft

awareness of the light source.•Swing-downlampshieldforeasyrelamping.•Altersoftwhitefilmoninsideofmicroperforatedmesh

lamp shield conceals lamp image providing balance between reflected and direct light.

•95%reflectiveAltersoftwhitepaintf inishandspecularinterior reflector

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type

Electronic

40W TT5 IB 50W TT5 BP 55W TT5 BF

LPB=Numberoflampsperballast.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:Standard15/16"only:QVS-HD.Emergency pack:Notavailable.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter Dome 2' x 2'Direct/indirect static round recessed luminaires

Architectural luminaire with uniquely styled optic features “circle in square” form. The open look, elegant appearance and balanced soft light provide a distinctive touch. Rotating luminaires create patterns of light that add variety to the decor.

30˚

60˚300

600

900

Candlepower Curve

669

QVC2GPFOS1FTUNVBP 2' x 2' Microperforated mesh lamp shields, 1-lamp 50W TT5

24" (610mm)

23 ¹³�¹6" (605mm)

5 ½"(140mm)

6 ½"(165mm)

2 ⅛"(54mm)

24" (610mm)

23 ¹³�¹6" (605mm)

5 ½"(140mm)

6 ½"(165mm)

2 ⅛"(54mm)

Reference data

Efficiency 53.9% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 53.7W Ballastfactor 0.88

RCR C.U.

1 56 3 42 5 33 7 27 10 21

Alter Dome Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.55 See page 4.55 w/microperforated mesh 277=277V andpage4.72 lamp shields UNV=120-277V

UNVQVC2GPFOS1FT BPExample

30˚

60˚200

400

600

Candlepower Curve

554

QVC2GPFOS1FTUNVIB 2' x 2' Microperforated mesh lamp shields, 1-lamp 40W TT5

24" (610mm)

23 ¹³�¹6" (605mm)

5 ½"(140mm)

6 ½"(165mm)

2 ⅛"(54mm)

24" (610mm)

23 ¹³�¹6" (605mm)

5 ½"(140mm)

6 ½"(165mm)

2 ⅛"(54mm)

Reference data

Efficiency 58.3% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 47.3W Ballastfactor 0.88

RCR C.U.

1 60 3 45 5 36 7 29 10 22

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 1-TT5 40, 50, 55W QVC2GPFOS1FT

Page 59: Linear recessed and surface lighting

4.56 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter Windows 2' x 2'Direct/indirect static symmetrical recessed luminaires

The gradations of light and gently curved square lamp shields of Alter Windows make a bold design statement. The non-directional design of the Alter Windows shield helps maintain the architectural look of a space. The multi-textured lamp shield and Alter Soft White reflector combine to create visual interest and gradations of light within a single lighting element.

Features•Utilizestwotripletube(TTT)lamps.•Altersoftwhitefilminsideofmicroperforated

lamp shield conceals lamp image and provides balance between reflected and direct light.

•Opaquelensprovidesagradationoflight effect that creates visual interest and architectural detail.

•Uniquesymmetricaldesignelements.•FitsstandardT-grid,exposedslot-T-grid anddrywallceilings(seepage4.218).

•Swing-downdesignforeasyrelamping.•Novisiblewelding,screws,latches,springs,holes,rivets

or plastic supports.•Forwallversion(seenextpage).

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVTD.

Ballast type

Electronic PowerSpec HDF dimming

26W TTT TB 40W TTT PD32W TTT TC 42W TTT TD

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:StandardT15/16"only:QVS-HD.Emergency pack:Notavailable.

30˚

60˚300

600

900

Candlepower Curve

732

QVS2GPASQ2TTUNVTD 2' x 2' Recessed microperforated mesh square lamp shield, 2-lamp 42W TTT

5 ½"(140mm)

24" (610mm)

23 ¹3�¹6" (605mm)

23 ¹3�¹6" (605mm)

8 "(203mm)

Reference data

Efficiency 46.7% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 71.6W Ballastfactor 1

RCR C.U.

1 49 3 39 5 31 7 24 10 18

Alter Waves Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.56 See page 4.56 w/solid white perimeter 277=277V andpage4.72 lamp shield / white UNV=120-277V mesh center

UNVQVS2GPASQ2TT TDExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-TTT 26, 32, 42W QVS2GPASQ2TT

Page 60: Linear recessed and surface lighting

4.57Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Utilizestwoquadtube(QT)lampsforsurfacewall.•Altersoftwhitefilminsideofmicroperforatedlamp

shield conceals lamp image and provides balance between reflected and direct light.

•Opaquelensprovidesagradationoflighteffectthatcreates visual interest and architectural detail.

•Uniquesymmetricaldesignelements.•Novisiblewelding,screws,latches,springs,holes,rivets

or plastic supports.•CompactADAcompliantwallsconceform(4"deep)

makes it ideal for mounting on columns and for use where wall space is limited

Options & accessoriesBallast:Specifyvoltage(120,277orUNV)andtypeand add as suffix, e.g. UNVF4.

F4: Electronic P.S., 1 or 2 lamps per ballast 18W Quad Tube.

QD: 18W QT PowerSpec HDF dimming. (Notavailablein347V)

Emergency pack:Notavailable.

AlterWindowsWall13½"x13½"Direct/indirect recessed luminaires

Matches ceiling luminaire styling. Protruding design pro jects light backwards to wall, creating a splash of light that surrounds the luminaire. Attention is focused on the gradations of light that frame the translucid center.

45˚

135˚

0

50

150

200

Candlepower Curve

QVW1SPASQ2QTUNVF4 13½"x13½"Surfacewallmicroperforatedmeshsquarelampshield,2-lamp18WQT

4 "(102mm)

13 ½ " (343mm)

13 ½ " (343mm)

Reference data

Efficiency 40.2%

Electronic ballast

Inputwatts(120V) 38.3W Ballastfactor 1

RCR C.U.

1 35 3 24 5 18 7 14 10 10

Alter Windows Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.57 See page 4.57 w/solid white perimeter 277=277V andpage4.72 lamp shield/white UNV=120-277V mesh center

UNVQVW1SPASQ2QT F4Example

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 13 ½"x13½" 2-QT 18W QVW1SPASQ2QT

4 "(102mm)

13 ½ " (343mm)

13 ½ " (343mm)

Page 61: Linear recessed and surface lighting

4.58 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter TileLyte 2' x 2'Direct/indirect recessed static luminaires with glass lens

Alter TileLyte comprises a recessed 2' x 2' square of radiant light, softened by an interior opal film. It installs flush with the ceiling using decorative hardware, while concealing T-bars. This textured lighting element features glass with chamfered edges, bringing pure sophistication to modern interiors.

Easy Maintenance•Easy-to-removethumbscrewsfacilitateloweringof

glass shield.•Aircraft-cablesafetychainattachesbehindeach

thumbscrew to hold glass shield when open.•Safetychainscanberemovedforeasycleaning,ballast

access and lamp replacement

Elegant Compatibility•Fitsallceilinggridtypes(standardT,slim-Tandslot-T).•Blendsinwithregularf lat-edgeandaestheticrecessed-

edge ceiling tiles.•Fourdecorativestainless-steelthumbscrewscreating

discreet visual interest at the ceiling line

Endless Possibilities•Unlimitedabilitytocreateluminousceilingpatterns.•Configurationversatilitycomplementsceilingdesigns,

adapts well to architectural interiors.•Creativeside-by-sideinstallationscangeneraterows,squares,rectangles,"L"shapes,"T"shapesandothergeometric f igures

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVPG.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BF T5 PG 3LPB40WTT5 I3

LPB=Numberoflampsperballast.

Dimming ballast recommended with certain configurations.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:StandardT15/16"only:QVS-HD.Lens replacement: Available as a complete assembly. Order cat. no.: QVD22GLOP.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚800

1600

2400

Candlepower Curve

1865

QVD2GGLOP3FTUNVI3 2' x 2' Glass with opal f ilm, 3-lamp 40W TT5

5 "(127mm)

24" (610mm)

5 "(127mm)

24" (610mm)

24 " (610mm)

24" (610mm)

5 "(127mm)

24" (610mm)

5 "(127mm)

24" (610mm)

24 " (610mm)

24" (610mm)

Reference data

Efficiency 48.9% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 99.8W Ballastfactor 0.88

RCR C.U.

1 52 3 41 5 33 7 27 9 20

Alter TileLyte Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.58 See page 4.58 glass with opal f ilm 277=277V andpage4.72 UNV=120-277V

UNVQVD2GGLOP3FT I3Example

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'

3-TT53-T53-T54-T54-T5

40, 50, 55W14W24W14W24W

QVD2GGL0P3FT QVD2GGL0P314 QVD2GGL0P324 QVD2GGL0P414 QVD2GGL0P424

Page 62: Linear recessed and surface lighting

4.59Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Alter TileLyte 2' x 2'Direct/indirect recessed static luminaires with glass lens

Page 63: Linear recessed and surface lighting

4.60 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter Slim Semi-recessed 2' x 4' & 2' x 2'Direct/indirect recessed static luminaires

This slimly profiled luminaire adds beauty and visual interest to the ceiling. With their gently curved fluid architectural details, they blend into the ceiling perspective. For applications where plenum depth is limited. The combined use of style matched Slim Semi-recessed and Slim Surface luminaires can provide the perfect solution.

Features•Microperforatedmeshlampshieldsprovideasoft

awareness of the light source.•Altersoftwhitefilmoninsideofmicroperforatedmesh

lamp shields conceal lamp image providing balance between reflected and direct light.

•Luminaireis2-3/16"totaldepthforeasyinstallationintoshallow plenum.

•Swing-downlampshieldsforeasyrelamping.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-grid,exposedslotT-gridand

drywall ceilings.•Optionaldrop-downvisualelement.•Canberowmounted.•T8notavailable

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVIB.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BFT5 PG

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:StandardT15/16"only:QVS-HD. Add appropriate Suffix: PF(Perforated)orSD (Solid) (e.g.QVH2GPF/QVH2GSD).Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚300

600

900

Candlepower Curve

853

QVH2GPFOS2FTUNVIB 2' x 2' Slim semi-recessed microperforated mesh lamp shields, 2-lamp 40W TT5

2 3�¹6"(56mm)

24" (610mm)

23 ¹3�¹6"(605mm)

11 ¹5�¹6" (303mm)

23 ¹3�¹6"(605mm)

Reference data

Efficiency 52.6% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 67.0W Ballastfactor 0.88

RCR C.U.

1 53 3 39 5 30 7 25 9 21

Alter Slim Semi-recessed Voltage Ballast Options Direct/indirect recessed with 120=120V Seepage4.60 See page 4.60 microperforated mesh lamp shields 277=277V andpage4.72 UNV=120-277V

UNVQVH2GPFOS2FT IBExample

Ordering information

Type Size Recessed ceiling depth Lamp qty –type Lamp watts Catalog no.

Static microperforated mesh lamp shields

2' x 4' 2 ¼"

2-TT54-TT52-T52-T5HO3-T53-T5HO

40, 50, 55W40, 50, 55W28W54W28W54W

QVH2GPFOS2FL QVH2GPFOS4FT QVH2GPFOS228 QVH2GPFOS254 QVH2GPFOS328 QVH2GPFOS354

Static microperforated mesh lamp shields

2' x 2' 2 ¼"

2-T5HO3-T5HO1-TT52-TT5

24W24W40, 50, 55W40, 50, 55W

QVH2GPFOS224 QVH2GPFOS324 QVH2GPFOS1FT QVH2GPFOS2FT

Clear acrylic plate drop down element

Clear polished acrylic drop-down visual element with projected color face. Substitute acrylic color suffix in place of open slot only.Suffix: GC(clear) GB(blue)

GG(green) GR(red)e.g.QVH2GPFOS (OS=OpenSlot) e.g.QVH2GPFGB (GB=BlueAcrylic)For other colors or special orders, consult your Philips Lightolier representative.

30˚

60˚700

1400

2100

Candlepower Curve

1706

QVH2GPFOS4FTUNVIB 2' x 4' Slim semi-recessed microperforated mesh lamp shields, 4-lamp 40W TT5

24" (610mm)

2 3�¹6

(56mm)

23 ¹5�¹6" (608mm)

11 ¹5�¹6" (303mm)

47 ¹3�¹6" (1214mm)

23 ¹5�¹6 (608mm)

Reference data

Efficiency 52.6% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 142.0W Ballastfactor 0.88

RCR C.U.

1 53 3 40 5 32 7 25 9 21

Page 64: Linear recessed and surface lighting

4.61Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Microperforatedmeshlampshieldsprovideasoft

awareness of the light source.•Altersoftwhitefilmoninsideofmicroperforatedmesh

lamp shields conceal lamp image providing balance between reflected and direct light.

•Luminaireis3-9/16"totaldepthforeasyinstallationintoshallow plenum.

•Swing-downlampshieldsforeasyrelamping.•Easyaccesstoballastthroughlampcompartment.•FitsstandardT-grid,exposedslotT-gridand

drywall ceilings.•Optionaldrop-downvisualelement.•Canberowmounted

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVIB.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T8 PS55W TT5 BFT5 PG

Drywall kit: Conversion kit for 2' x 2' unit: FK91X4.Hold down clips:StandardT15/16"only:QVS-HD. Add appropriate Suffix: PF(Perforated)orSD (Solid) (e.g.QVH1GPF/QVH1GSD).Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter Slim Semi-recessed 1' x 4'Direct/indirect recessed static luminaires

This slimly profiled luminaire adds beauty and visual interest to the ceiling. With their gently curved fluid architectural details, they blend into the ceiling perspective. For applications where plenum depth is limited. The combined use of style matched Slim Semi-recessed and Slim Surface luminaires can provide the perfect solution.

30˚

60˚300

600

900

Candlepower Curve

800

QVH1GPFOS2FTUNVIB 1' x 4' Slim semi-recessed microperforated mesh lamp shields, 2-lamp 40W TT5

3 9�¹6"(90mm)

12" (305mm)

11 ¹3�¹6" (300mm)

5 ¹5�¹6" (150mm)

47 ¹3�¹6" (1215mm)

23 ¹5�¹6" (608mm)

3 9�¹6"(90mm)

12" (305mm)

11 ¹3�¹6" (300mm)

5 ¹5�¹6" (150mm)

47 ¹3�¹6" (1215mm)

23 ¹5�¹6" (608mm)

Reference data

Efficiency 47.5% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 68.0W Ballastfactor 0.9

RCR C.U.

1 50 3 38 5 30 7 24 10 18

Clear acrylic plate drop down element

Clear polished acrylic drop-down visual element with projected color face. Substitute acrylic color suffix in place of open slot only.Suffix: GC(clear) GB(blue)

GG(green) GR(red)e.g.QVH2GPFOS (OS=OpenSlot) e.g.QVH2GPFGB (GB=BlueAcrylic)For other colors or special orders, consult your Philips Lightolier representative.

Ordering information

Type Size Recessed ceiling depth Lamp qty –type Lamp watts Catalog no.

Static microperforated mesh lamp shields

1' x 4' 3-9/16"2-TT52-T52-T5HO

40, 50, 55W28W54W

QVH1GPFOS2FT QVH1GPFOS228 QVH1GPFOS254

Alter Slim Semi-recessed Voltage Ballast Options Direct/indirect recessed with 120=120V Seepage4.61 See page 4.61 microperforated mesh lamp shields 277=277V andpage4.72 UNV=120-277V

UNVQVH1GPFOS2FT IBExample

Page 65: Linear recessed and surface lighting

4.62 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter Slim Surface 2' x 4' & 2' x 2'Direct/indirect recessed luminaires

These slimly profiled luminaires add beauty and visual interest to the ceiling. With their gently curved fluid architectural details, they blend into the ceiling perspective. For applications where plenum depth is limited. The combined use of style matched slim semi-recessed and slim surface luminaires can provide the perfect solution.

Features•Altersoftwhitefilmoninsideofmicroperforatedmesh

lamp shields conceal lamp image providing balance between reflected and direct light.

•UtilizethesamereflectorandopticsdesignasSlimSemi-recessed model providing the same lighting performance. Luminaire with its contoured housing gives the visual perception of a very low-profile luminaire.

•Contouredhousingdepthonly2 1/4".Totaldepth3 15/16".

•95%reflectiveAltersoftwhitepaintf inishandspecularinterior reflector.

•Swing-downlampshieldsforeasyrelamping. Easy access to ballast through lamp compartment.

•FitsstandardT-grid,exposedslotT-gridanddrywall ceilings.

•Novisiblewelding,screws,latches,springs,hooks,rivets or plastic supports.

•T8notavailable.

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVIB.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP T5 PF55W TT5 BFT5 PG

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.

Conversion kit for 2' x 2' unit: FK92X2 .Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚300

600

900

Candlepower Curve

853

QVF2SPFOS2FTUNVIB 2' x 2' Slim surface microperforated mesh lamp shields, 2-lamp 40W TT5

Ceiling

25 9�¹6" (650mm)

2 ¼"(57mm)

24" (610mm)

Reference data

Efficiency 52.6% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 67.0W Ballastfactor 0.88

RCR C.U.

1 53 3 39 5 30 7 25 10 19

30˚

60˚700

1400

2100

Candlepower Curve

1854

QVF2SPFOS4FTUNVIB 2' x 4' Surface wall microperforated mesh lamp shields, 4-lamp 40W TT5

Ceiling

25 9�¹6" (650mm)

48" (1220mm)

2 ¼"(57mm)

Reference data

Efficiency 51.0% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 130.0W Ballastfactor 0.88

RCR C.U.

1 52 3 39 5 31 7 25 10 19

Clear acrylic plate drop down element

Clear polished acrylic drop-down visual element with projected color face. Substitute acrylic color suffix in place of open slot only.Suffix: GC(clear) GB(blue)

GG(green) GR(red)e.g.QVH2GPFOS (OS=OpenSlot) e.g.QVH2GPFGB (GB=BlueAcrylic)For other colors or special orders, consult your Philips Lightolier representative.

Alter Slim Surface: added profile dimensions1-11/16"=Depthofbasketfrombottomofsurfaceframe 2-1/4"=Fulldepthoff ixturefromceilingsurface

Ceiling

2 ¼"(57mm)

1 ¹�¹6"(43mm)

3 ¹5�¹6"(100mm)

Ordering information

Type Size Recessed ceiling depth Lamp qty –type Lamp watts Catalog no.

Static Microperforated Mesh Lamp Shields

2' x 4' 3 15 ⁄16"

2-TT54-TT52-T52-T5HO3-T53-T5HO

40, 50, 55W40, 50, 55W28W54W28W54W

QVF2SPFOS2FT QVF2SPFOS4FT QVF2SPFOS228 QVF2SPFOS254 QVF2SPFOS328 QVF2SPFOS354

Static Microperforated Mesh Lamp Shields

2' x 2' 3 15 ⁄16"

1-TT52-TT52-T5HO3-T5HO

40, 50, 55W40, 50, 55W24W24W

QVF2SPFOS1FT QVF2SPFOS2FT QVF2SPFOS224 QVF2SPFOS324

Allow3"forrecessedT-barmounting Actualrecessedluminairedepth⅝"

Alter Slim Surface Voltage Ballast Options Direct/indirect recessed with 120=120V Seepage4.62 See page 4.62 microperforated mesh lamp shields 277=277V andpage4.72 UNV=120-277V

UNVQVF2SPFOS2FT IBExample

Page 66: Linear recessed and surface lighting

4.63Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Microperforatedmeshlampshield.•Availableeitherinwhiteortitaniumpaintedfinish.•Economicalconstructionprovidingexcellentvalue.

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVIB.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP 55W TT5 BF

Alter Slim Square 2' x 2'Direct/indirect recessed luminaires

Featuring an attractive inset frame, Alter Slim Square produces a floating effect while hugging the ceiling line. This surface-mount fluorescent lumi naire displays a sleek profile with architectural detailing that blends into most environments. For balanced brightness applications where plenum depth is very limited.

30˚

60˚300

600

900

Candlepower Curve

876

QVB2SPGOS2FTUNVIB 2' x 2' Microperforated mesh lamp shields, 2-lamp 40W TT5

Ceiling

28 ¹�¹6" (713mm)

2 5�¹6"(59mm)¾"

(19mm)

24" (610mm)

Reference data

Efficiency 50.5% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 64.5W Ballastfactor 0.88

RCR C.U.

1 52 3 39 5 31 7 25 10 20

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static with white body microperforated mesh white lamp shields

2' x 2' 1-TT52-TT5

40, 50, 55W40, 50, 55W

QVB2SPWOS1FT QVB2SPWOS2FT

Static with titanium body microperforated mesh white lamp shields

2' x 2' 1-TT52-TT5

40, 50, 55W40, 50, 55W

QVB2SPGOS1FT QVB2SPGOS2FT

For Solid Lamp Shield replace PW or PG by SW or SG.

Alter Slim Semi-recessed Voltage Ballast Options Direct/indirect recessed with 120=120V Seepage4.63 See page 4.63 microperforated mesh lamp shields 277=277V andpage4.72 UNV=120-277V

UNVQVB2SPGOS2FT IBExample

3/4"(9mm)

1-11/16"(43mm)

1-9/16"(40mm)

SlimSquare3/4"contouredframegivestheluminaireaverylowprofilevisualperception.

Page 67: Linear recessed and surface lighting

4.64 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter ConceptDirect/indirect recessed luminaires

Page 68: Linear recessed and surface lighting

4.65Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Alter ConceptDirect/indirect recessed luminaires

Less bulk. Less weight. More performance – up to 92.7% efficient. More sustainable lighting opportunities, especially in shallow and cluttered plenums. And more lighting value for today’s modern interiors.

Alter Concept EleganceAvailable in glass and perforated steel shielding models, and in a lens version with fully enclosed dust-free lamp compartment ideal for food preparation areas and hospital applications.

Alter Concept SRSemi-recessed T5 and T8 versions with microperforated mesh lamp shield.

Decorative elementsGlass versions of Alter Concept Elegance, including style-matched Alter Elegance Glass Wall, integrate richly textured architectural materials, such as frosted ridged glass and natural satin-finished metal.

Increased maintenance convenience Tool-free access from below facilitates lamp and ballast replacements.

Less is moreIntroducing a combination of functionalities so practical, they could change the way architects design energy efficient buildings. Alter Concept features a generation of low profile luminaires. In addition to offering Alter hallmark aesthetics in a greener, more compact and more affordable lighting package, these luminaires deliver superior lighting output well suited to meeting sustainability objectives and LEED requirements.

•Suitedtosustainablebuilding trend favouring less materials and shallower plenums with 3⅝"depthidealforrestricted ceiling space (standard Alter Classic housingis5½").

•Streamlinedlightweightconstruction Alter Concept luminaires are about 30% lighter than regular Alter models with5½"housings.

•Material-savingapproachThese products feature less fuel consumption for transportation. Also, they use considerably less steel and less packaging than standard luminaires.

•Architecturalf lexibilityAlter Concept luminaires can help reduce floor-to-floor heights and overall building elevation, while minimizing the use of energy and resources

Lowerprofile:3⅝"vs.5½"

Solid edge lamp shield Most Alter Concept models with microperforated mesh lamp shield include signature Solid Edge finish for aesthetic visual appearance where shield and reflector meet.

Old version Improved version with Solid-Edge technology and seamless design

Page 69: Linear recessed and surface lighting

4.66 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Alter Concept Elegance Perforated 2' x 4', 2' x 2' & 1' x 4' Direct/indirect static shallow T5 recessed luminaires

Attractive Concept Elegance provides outstanding lighting design statements in offices and public spaces. This luminaire features seamless construction along with the clean look of solid-edge microperforated mesh lamp shields. It belongs to the Alter Concept collection of sustainable lighting elements, offering cost-effective lighting in a lightweight, low-profile design ideal for shallow plenums, modern interiors and green buildings.Features

•Efficienciesupto67.9%.•Seamlessweldedformfor2'x2'and2'x4'models:

curved top and side reflectors are formed together without any gaps or visual barriers.

•Shallowdesign,only3⅝"deepforeasyinstallation in shallow plenum.

•Post-paintedluminaire.•Solid-Edgeswing-downmicroperforatedlampshield

for easy relamping and maintenance.•Altersoftwhitefilmoninsideofmeshconcealslamp

image providing balance between reflected and direct light.

•Fullyrecessedluminaireandlampcompartment.•95%ReflectiveAltersoftwhitepaintf inish.•One-piecebodyforeasyinstallation.•Easyaccesstoballastthroughlampcompartment.•Canberowmounted.•Fitsstandard15/16"T-Grid,SlotT-Grid

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVPG.

Ballast type <10THD

Electronic T5/T5HO Program start PGElectronic TT5 40W Instant start IBElectronic TT5 40W Program rapid start PRElectronic TT5 50W Rapid start BPElectronic TT5 55W Rapid start BFElectronic(2)T528WStep-dim AY ProgramedRapidStart(B.F.=0.95/0.35)Electronic TT5/T5/T5HO Program start DA DALI Digital addressable dimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.

Conversion kit for 2' x 2' unit: FK92X2 . Conversion kit for 1' x 4' unit: FK91X4.

Hold down clips:StandardT15/16"only:QVS-HD.Emergency Lighting: Consult factory for options.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚400

800

1200

Candlepower Curve

QCE2GPFOS2FTUNVPR 2' x 2' Alter Concept Elegance Perf, 2-Lamp 40W TT5

3 ⅝"(92mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 56.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 68.5W Ballastfactor 0.9

RCR C.U.

1 59 3 46 5 36 7 29 10 22

30˚

60˚400

800

1200

Candlepower Curve

QCE2GPFOS228UNVPG 2' x 4' Alter Concept Elegance Perf, 2-Lamp 28W T5

48" (1220mm)

3 ⅝"(92mm)

24" (610mm)

Reference data

Efficiency 67.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 65.0W Ballastfactor 1.0

RCR C.U.

1 71 3 55 5 43 7 34 10 25

Alter Concept Elegance Perf Voltage Ballast Options Direct/indirect recessed UNV=120-277V Seepage4.66 See page 4.66 and page 4.72

UNVQCE2GPFOS2FT IBExample

Ordering information

Type Size Recessed ceiling depth Lamp qty –type Lamp watts Catalog no.

Static microperforated mesh lamp shields

2' x 4' 3 ⅝"2-T53-T52-T5HO

28W28W54W

QCE2GPFOS228 QCE2GPFOP328* QCE2GPFOS254

Static microperforated mesh lamp shields

2' x 2' 3 ⅝" 2-TT52-T5HO

40, 50, 55W24W

QCE2GPFOS2FT QCE2GPFOS224

Static microperforated mesh lamp shields

1' x 4' 3 ⅝"1-T5HO2-T52-T5HO

54W28W54W

QCE1GPFOS154 QCE1GPFOS228 QCE1GPFOS254

Replace OS(openslot)byOP for one piece lamp shield (e.g. QCE2GPFOP2FTUNVIB). * 3-lamp combination only available with one-piece lamp shield.

Page 70: Linear recessed and surface lighting

4.67Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Efficienciesupto92.7%.•Seamlessweldedformfor2'x2'and2'x4'models:

curved top and side reflectors are formed together without any gaps or visual barriers.

•Shallowdesign,only3⅝"deepforeasyinstallationinshallow plenum.

•Post-paintedluminaire.•Highperformancecontouredlensconcealslampimage

providing balance between reflected and direct light.•Notoolsrequiredtoremovelensforeasyrelamping

and maintenance.•Fullyrecessedluminaireandlampcompartment.•95%ReflectiveAltersoftwhitepaintf inish.•One-piecebodyforeasyinstallation.•Easyaccesstoballastthroughlampcompartment.•Canberowmounted.•Fitsstandard15/16"T-Grid,SlotT-Gridordrywall

ceilings

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVPG.

Ballast type <10THD

Electronic T5/T5HO Program start PGElectronic TT5 40W Instant start IBElectronic TT5 40W Program rapid start PRElectronic TT5 50W Rapid start BPElectronic TT5 55W Rapid start BFElectronic(2)T528WStep-dim AY ProgramedRapidStart(B.F.=0.95/0.35)Electronic TT5/T5/T5HO Program start DA DALI Digital addressable dimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.

Conversion kit for 2' x 2' unit: FK92X2 . Conversion kit for 1' x 4' unit: FK91X4.

Hold down clips:StandardT15/16"only:QVS-HD.Emergency Lighting: Consult factory for options.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter Concept Elegance Lens 2' x 4', 2' x 2' & 1' x 4' Direct/indirect static shallow T5 recessed luminaires

The Concept Elegance Lens model takes lighting performance to new levels while delivering Alter’s signature soft lighting effect. It features superior efficiency and seamless construction. It belongs to the Alter Concept collection of sustainable lighting elements, offering cost-effective lighting in a lightweight, low-profile design ideal for shallow plenums, modern interiors and green buildings.

30˚

60˚250

500

750

Candlepower Curve

QCE2GOLOP214UNVPG 2' x 2' Alter Concept Elegance Lens, 2-Lamp 14W T5

3 ⅝"(92mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 87.6% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 32.6W Ballastfactor 1.0

RCR C.U.

1 83 3 56 5 41 7 32 10 23

Alter Concept Elegance Lens Voltage Ballast Options Direct/indirect recessed UNV=120-277V Seepage4.67 See page 4.67 and page 4.72

UNVQCE2GOLOP214 PGExample

Ordering information

Type Size Recessed ceiling depth Lamp qty –type Lamp watts Catalog no.

Static Etched lens lamp shields

2' x 4' 3 ⅝" 2-T52-T5HO

28W54W

QCE2GOLOP228 QCE2GOLOP254

Static etched lens lamp shields

2' x 2' 3 ⅝"1-TT52-T52-T5HO

40, 50, 55W14W24W

QCE2GOLOP1FT QCE2GOLOP214 QCE2GOLOP224

Static etched lens lamp shields

1' x 4' 3 ⅝"1-T5HO2-T52-T5HO

54W28W54W

QCE1GOLOP154 QCE1GOLOP228 QCE1GOLOP254

30˚

60˚500

1000

Candlepower Curve

1438

QCE2GOLOP228UNVPG 2' x 4' Alter Concept Elegance Lens, 2-Lamp 28W T5

48" (1220mm)

3 ⅝"(92mm)

24" (610mm)

Reference data

Efficiency 92.7% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 61.5W Ballastfactor 1.0

RCR C.U.

1 96 3 72 5 56 7 45 10 33

Page 71: Linear recessed and surface lighting

4.68 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•Efficienciesupto70.7%.•Seamlessweldedform:curvedtopandsidereflectors

are formed together without any gaps or visual barriers.•Shallowdesign,only3⅝"deepforeasyinstallation

in shallow plenum.•Post-paintedluminaire.•Elegantridgedglasslampshieldsonhingedaluminium

extrusions swing down for easy relamping and maintenance.

•Altersoftwhitefilmoninsideofridgedglassconcealslamp image providing balance between reflected and direct light.

•Fullyrecessedluminaireandlampcompartment.•95%ReflectiveAltersoftwhitepaintf inish.•One-piecebodyforeasyinstallation.•Easyaccesstoballastthroughlampcompartment.•Canberowmounted.•Fitsstandard15/16"T-Grid,SlotT-Grid

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVPG.

Ballast type <10THD

Electronic T5/T5HO Program start PGElectronic TT5 40W Instant start IBElectronic TT5 40W Program rapid start PRElectronic TT5 50W Rapid start BPElectronic TT5 55W Rapid start BFElectronic(2)T528WStep-dim AY Programedrapidstart(B.F.=0.95/0.35)Electronic TT5/T5/T5HO Program start DA DALI Digital addressable dimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.

Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:StandardT15/16"only:QVS-HD.Emergency Lighting: Consult factory for options.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter Concept Elegance Glass 2' x 4' & 2' x 2'Direct/indirect static shallow T5 recessed luminaires

Concept Elegance Glass exudes soft lighting presence to bring an air of distinction to architectural decors. This luminaire family features beautifully textured glass panels, seamless construction and includes a 2' x 4' version. It belongs to the Alter Concept collection of sustainable lighting elements, offering cost-effective lighting in a lightweight, low-profile design ideal for shallow plenums, modern interiors and green buildings.

30˚

60˚400

800

1200

Candlepower Curve

QCE2GGLOS2FTUNVPR 2' x 2' Alter Concept Elegance Perf, 2-Lamp 40W TT5

3 ⅝"(92mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 58.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 68.9W Ballastfactor 0.9

RCR C.U.

1 61 3 43 5 33 7 26 10 18

30˚

60˚400

800

1200

Candlepower Curve

QCE2GGLOS228UNVPG 2' x 4' Alter Concept Elegance Perf, 2-Lamp 28W T5

48" (1220mm)

3 ⅝"(92mm)

24" (610mm)

Reference data

Efficiency 70.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 63.0W Ballastfactor 1.0

RCR C.U.

1 74 3 58 5 45 7 36 10 27

Alter Concept Elegance Perf Voltage Ballast Options Direct/indirect recessed UNV=120-277V Seepage4.68 See page 4.68 and page 4.72

UNVQCE2GGLOS2FT IBExample

Ordering information

Type Size Recessed ceiling depth Lamp qty –type Lamp watts Catalog no.

Static Concept Elegance Glass double glass lamp shields

2' x 4' 3 ⅝" 2-T52-T5HO

28W54W

QCE2GGLOS228 QCE2GGLOS254

Static Concept Elegance Glass double glass lamp shields

2' x 2' 3 ⅝" 2-TT52-T5HO

40, 50, 55W24W

QCE2GGLOS2FT QCE2GGLOS224

Page 72: Linear recessed and surface lighting

4.69Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Alter Concept Elegance Perf Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.69 See page 4.69 277=277V andpage4.72 UNV=120-277V

UNVQVW8SGLOS2FT BAExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static Elegance Wall

9"x12"9"x24" 2-TT5 18W

40WQVW8SGLOS218 QVW8SGLOS2FT

Features•Efficiency60.9%.•Usesmountingsurfaceaspartofopticalsystem.•Availablein12"and24"options.•Installsverticallyorhorizontallyonwall/ceiling.•Providingbalancebetweenreflectedanddirectlight.•0degreelampcut-off.•Onepiecebodyforeasyinstallation.•Lampshieldconstructedofdecorativefrostedrigidglass

and natural satin-finished metal

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVIB.

Ballast type

Electronic PowerSpec HDF dimming

40W TT5 IB 40W TT5 PB50W TT5 BP 55W TT5 BF18W TT5 BA

Fusing: Suffix: A (Internalfusing).

Alter Elegance Wall 9"x12"&9"x24"Direct/indirect static ceiling & wall luminaires

Alter Elegance Wall employs decorative elements in its design such as frosted, ridged glass lenses with natural satin finished trim accents made of satin finished metal. This design brings a unique level of refinement to the world of balanced brightness. Whether installed on walls, columns, partitions or even in alcoves, these luminaires create visual interest in combination with Alter Elegance for example. The utilization of these two products provides opportunities in any space for design consistency.

45˚

135˚1000

750

500

250

Candlepower Curve

QVW8SGLOS218UNVBA Alter Elegance Wall, 2-Lamp 18W TT5

24" (610mm)

9 ¾" (248mm)

4"(101mm)

9 ¾" (248mm)

4"(101mm)

12 ¼" (311mm)

Reference data

Efficiency 60.9%

Electronic ballast

Inputwatts(120V) 65.6W Ballastfactor 0.88

RCR C.U.

1 52 3 37 5 28 7 22 10 16

Page 73: Linear recessed and surface lighting

4.70 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•Efficienciesupto77.5%.•Seamlessweldedform:curvedtopandsidereflectors

are formed together without any gaps or visual barriers.•Shallowdesign,only3⅝"deepforeasyinstallationin

shallow plenum.•Post-paintedluminaire.•Solid-edgeswing-downmicroperforatedlampshield

for easy relamping and maintenance.•Altersoftwhitefilmoninsideofmeshconcealslamp

image providing balance between reflected and direct light.

•Semi-recessedluminaireandlampcompartment.•95%ReflectiveAltersoftwhitepaintf inish.•One-piecebodyforeasyinstallation.•Easyaccesstoballastthroughlampcompartment.•Canberowmounted.•Fitsstandard15/16"T-Grid,SlotT-Grid

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. UNVIB.

Ballast type <10THD

Electronic T5/T5HO Program start PGElectronic TT5 40W Instant start IBElectronic TT5 40W Program rapid start PRElectronic TT5 50W Rapid start BPElectronic TT5 55W Rapid start BFElectronic(2)T528WStep-Dim AY Programedrapidstart(B.F.=0.95/0.35)Electronic TT5/T5/T5HO Program start DA DALI Digital addressable dimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.

Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:StandardT15/16"only:QVS-HD.Emergency Lighting: Consult factory for options.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter Concept SR T5 2' x 4' & 2' x 2'Direct/indirect static T5 semi recessed luminaires

Subtle presence at the ceiling line and classy styling make Concept SR T5 a visually pleasing option for halls, corridors and other spaces. This semi-recessed luminaire features seamless construction along with the clean look of solid-edge microperforated mesh lamp shields. It belongs to the Alter Concept collection of sustainable lighting elements, offering cost-effective lighting in a lightweight, low-profile design ideal for shallow plenums, modern interiors and green buildings.

30˚

60˚400

800

1200

Candlepower Curve

QCH2GPFOS2FTUNVPR 2' x 2' Alter Concept SR T5, 2-Lamp 40W TT5

3 ⅝"(92mm)

24" (610mm)

24" (610mm)

4 ¹5�¹6"(126mm)

Reference data

Efficiency 58.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 70.7W Ballastfactor 0.9

RCR C.U.

1 61 3 47 5 37 7 30 10 22

Alter Concept Elegance Perf Voltage Ballast Options Direct/indirect recessed UNV=120-277V Seepage4.70 See page 4.70 and page 4.72

UNVQCH2GPFOS2FT IBExample

Ordering information

Type Size Recessed ceiling depth Lamp qty –type Lamp watts Catalog no.

Static Microperforated mesh lamp shields

2' x 4' 3 ⅝"2-T52-T5HO3-T5HO

28W54W28W

QCH2GPFOS228 QCH2GPFOS254 QCH2GPFOP328*

Static microperforated mesh lamp shields

2' x 2' 3 ⅝"2-T52-T5HO3-T5HO

40, 50, 55W24W24W

QCH2GPFOS2FT QCH2GPFOS224 QCH2GPFOP324*

* 3-lamp combination only available with one-piece lamp shield.

30˚

60˚400

800

Candlepower Curve

1172

QCH2GPFOS228UNVPG 2' x 4' Alter Concept SR T5, 2-Lamp 28W T5

3 ⅝"(92mm)

24" (610mm)

48" (1220mm)

4 ¹5�¹6"(126mm)

Reference data

Efficiency 71.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 67.5W Ballastfactor 1.0

RCR C.U.

1 75 3 57 5 45 7 36 10 26

Page 74: Linear recessed and surface lighting

4.71Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Efficienciesupto70.5%.•Seamlessweldedform:curvedtopandsidereflectors

are formed together without any gaps or visual barriers.•Post-paintedluminaire.•Cost-effectiveT8solutionwithshallowdesign,only3⅝"

deep for easy installation in shallow plenum.•One-pieceswing-downmicroperforatedlampshieldfor

easy relamping and maintenance.•Altersoftwhitefilmoninsideofmeshconcealslamp

image providing balance between reflected and direct light.

•Semi-recessedluminaireandlampcompartment.•95%ReflectiveAltersoftwhitepaintf inish.•One-piecebodyforeasyinstallation.•Easyaccesstoballastthroughlampcompartment.•Notsuitableforrowmounting.•Fitsstandard15/16"T-Grid,SlotT-Grid

Options & accessories page 4.72 + 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD

Electronic T8 Program start P2Electronic T8 Instant start HIElectronic T8 3-lamp instant start H3Electronic T8 Program start DA

DALI Digital addressable dimming

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.

Conversion kit for 2' x 2' unit: FK92X2 .Hold down clips:StandardT15/16"only:QVS-HD.Emergency Lighting: Consult factory for options.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Alter Concept SR T8 2' x 4' & 2' x 2'Direct/indirect static T8 semi recessed luminaires

Subtle presence at the ceiling line and classy styling make Concept SR T8 a visually pleasing option for halls, corridors and other spaces. This semi-recessed luminaire features T8 affordability and seamless construction, along with the clean look of microperforated mesh lamp shields. It belongs to the Alter Concept collection of sustainable lighting elements, offering cost-effective lighting in a lightweight, low-profile design ideal for shallow plenums, modern interiors and green buildings.

Alter Concept Elegance Perf Voltage Ballast Options Direct/indirect recessed UNV=120-277V Seepage4.71 See page 4.71 and page 4.72

UNVQCJ2GPFOP217 HIExample

Ordering information

Type Size Recessed ceiling depth Lamp qty –type Lamp watts Catalog no.

Static microperforated mesh lamp shields

2' x 4' 3 ⅝" 2-T83-T8

32W32W

QCJ2GPFOP232 QCJ2GPFOP332

Static microperforated mesh lamp shields

2' x 2' 3 ⅝" 2-T8 17W QCJ2GPFOP217

30˚

60˚200

400

607

Candlepower Curve

QCJ2GPFOP217UNVHI 2' x 2' Alter Concept SR T8, 2-Lamp 17W T8

3 ⅝"(92mm)

24" (610mm)

24" (610mm)

4 ¹5�¹6"(126mm)

Reference data

Efficiency 68.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 31.2W Ballastfactor 0.91

RCR C.U.

1 71 3 55 5 43 7 34 10 25

30˚

60˚600

1200

Candlepower Curve

1944

QCJ2GPFOP332UNVH3 2' x 4' Alter Concept SR T8, 3-Lamp 32W T8

24" (610mm)

48" (1220mm)

4 ¹5�¹6"(126mm)

3 ⅝"(92mm)

Reference data

Efficiency 70.5% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 90.7W Ballastfactor 0.88

RCR C.U.

1 73 3 56 5 44 7 35 10 25

Page 75: Linear recessed and surface lighting

4.72 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

AlterOptions & accessories

Clear Acrylic LensGI=⅛"nominal

thickness

Clear Polycarb-onate LensPX=⅛"nominal

thickness

Available for: Alter Classic Recessed 2' x 2' . . . . . . . (notavail.withairhandling) Alter Classic Recessed 2' x 4' . . . . . . . (notavail.withairhandling) Alter Classic Recessed 1' x 4' . . . . . . . (notavail.for1lamp) Alter Slim Semi-recessed 2' x 2' . . . . . (notavail.for1lamp) Alter Slim Semi-recessed 2’ x 4’ . . . . . (notavail.for2-lampTT5) Alter Slim Square 2' x 2' . . . . . . . . . . . . (notavail.for1lamp) Alter Slim Surface 2' x 2', 2’ x 4’ . . . . . (notavail.for2-TT5)

Liteguard

Liteguard is a lens for recessed luminaires adding protection against pathogens, dust and bugs and makes cleaning easy. It fits on almost all 2' x 2', 2' x 4' and 1' x 4' fully recessed luminaires including troffers, parabolics and Alter-types. Post-painted matte white aluminum frame fits Alter paint.See Liteguard brochure for more details.

Luminaire Family Nominal size Lens LG=Liteguard 2X2=2'x2' GI=ClearAcrylic 2X4 =2'x4' PX=ClearPolycarbonate 1X4 =1'x4'

2X2LG GI

Example

Optional clear polished acrylic drop-down visual element with projected color faceSubstitute acrylic suffix in place of open slot (OS)only. (e.g.replaceQVS2GPFOSbyQVS2GPFGR(Red)

Suffix: GC(Clear) GG (GreenAcrylic) GB (Blue) GR(RedAcrylic)

For other colors, consult your Philips Lightolier representative.

Hold down clips

Four clips required per luminaire. Suited to standard15/16"andslotT grid ceilings. Can also be used for row-mounting applications.

Order separately: catalog no. QVS-HD.

(Kitbagcontains4clips)

Emergency power battery pack

Add appropriate suffix in option box: T8/T5/T5HO models. Suffix: E

Internal fusing

Suffix: A(Internalfast-blowfusing). Suffix: C(Internalslow-blowfusing).

Radio interference filter

Suffix: R(inOptionbox)

Inductive capacitor circuit designed to minimize interference from line radiation or feedback.

(Onepercircuitrequired)

Factory installed emergency power battery pack with charger and inverter, concealed in luminaire channel. Upon loss of AC power, operates one fluorescent lamp at15%lightoutputfor90minutes.120Vand277Vversions available.

Note: 2' x 2' Alter Concept luminaires equipped with Emergency Lightingare5-1/4"deep.2'x4'versionswithdouble-switchingare5-1/4"deepwhileregular2'x4'versions(1ballast)are3-5/8" deep.

To get a lens separately, order Catalog no.Size Example Description Catalog no.

1' x 4'2' x 2'2' x 4'

LNQVS14LNQVS22LNQVS24

(ColorSuffix)(ColorSuffix)(ColorSuffix)

LNQVS14 - GB LNQVS22 - GR LNQVS24 - GG

Page 76: Linear recessed and surface lighting
Page 77: Linear recessed and surface lighting

4.74 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampbasketwithunique

TransOptix lens.•Body95%reflectiveflatwhitepowdercoated.•95%InternalMiro® reflector.•73.4%efficienttwolamp32WT82'x4'luminaire.•66.9%efficientthreelamp32WT82'x4'luminaire.•80.2%efficienttwolamp28WT52'x4'luminaire.•80.7%efficienttwolamp54WT5HO2'x4'luminaire.•Only5"deep.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceiling.•Fitsf lushtofaceofslotgrid(T)ceiling.•Injectionmoldedlightstopatbasketends.•Perforatedlampshieldhingesfromeitherside.•Ballastaccessiblethrulampcompartment

from room side.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•ConstructiontomeetNYCCode

or Chicago Plenum requirement available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic T5 PG –LOL Dimming T8 PS –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Coffaire HP 2' x 4'Direct/indirect recessed static luminaires

Our new high-performance Coffaire HP luminaire features a high 95% reflectance white powder painted body, our new Transoptix lens and a 95% reflectance Miro® aluminum reflector. Achieving efficiencies 20% greater than comparable luminaires currently available in the market.

30˚

60˚800

1600

2400

Candlepower Curve

30˚

60˚500

1000

1500

Candlepower CurveCFS2GHP228120WA

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP254UNVPG

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP232UNVHI

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP228120WA

Reference data

Efficiency 80.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 56.6W Ballastfactor 0.93

CFS2GHP254UNVPGReference data

Efficiency 80.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 121.1W Ballastfactor 1

CFS2GHP232UNVHI

30˚

60˚550

1100

1650

Candlepower CurveReference data

Efficiency 73.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 58.7W Ballastfactor 0.88

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP254UNVPG

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP232UNVHI

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP228120WA

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP254UNVPG

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP232UNVHI

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP228120WA

Coffaire HP Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.74 See page 4.74 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

120CFS2GHP228 AWAExample

Coffaire HP Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.74 See page 4.74 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCFS2GHP254 APGExample

Coffaire HP Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.74 See page 4.74 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCFS2GHP232 AHIExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T53-T5 28W CFS2GHP228

CFS2GHP328

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 1-T5HO2-T5HO 54W CFS2GHP154

CFS2GHP254

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T83-T8 32W CFS2GHP232

CFS2GHP332

Page 78: Linear recessed and surface lighting

4.75Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Coffaire HP 2' x 2'Direct/indirect recessed static luminaires

Our new high-performance Coffaire HP luminaire features a high 95% reflectance white powder painted body, our new Transoptix lens and a 95% reflectance Miro® aluminum reflector. Achieving efficiencies 20% greater than comparable luminaires currently available in the market. The 2' x 2' model, with Philips ballast and 25 watt PL-L lamps, is over 85% efficient. This unique combination of the Coffaire HP, lamps and ballast provides 46 maintained foot candles at 0.71 watts per square foot.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampbasketwithunique

TransOptix lens.•Body95%reflectiveflatwhitepowdercoated.•95%InternalMiro® reflector.•76.6%efficienttwolamp24WT5HO2'x2'luminaire.•85.4%efficienttwolamp25WTT52'x2'luminaire.•71.5%efficienttwolamp40WTT52'x2'luminaire.•72.5%efficienttwolamp17WT82'x2'luminaire.•Only5"deep.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceiling.•Fitsf lushtofaceofslotgrid(T)ceiling.•Injectionmoldedlightstopatbasketends.•Perforatedlampshieldhingesfromeitherside.•Ballastaccessiblethrulampcompartment

from room side.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•ConstructiontomeetNYCCode

or Chicago Plenum requirement available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic TT5 40W IB*, PR** SB*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

30˚

60˚550

1100

1650

Candlepower Curve

30˚

60˚300

600

900

Candlepower CurveCFS2GHP224UNVPG

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP2FTUNVIB ~ 25 Watt Lamps

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GPF217UNVHI

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GPF224UNVPG

Reference data

Efficiency 76.6% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 52.8W Ballastfactor 1

CFS2GHP2FTUNVIBReference data - 25W

Efficiency 85.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 57.3W Ballastfactor 0.88

CFS2GHP217UNVHI

30˚

60˚250

500

750

Candlepower CurveReference data

Efficiency 72.5% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 30.1W Ballastfactor 0.91

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP2FTUNVIB ~ 25 Watt Lamps

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GPF217UNVHI

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GPF224UNVPG

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GHP2FTUNVIB ~ 25 Watt Lamps

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GPF217UNVHI

5"(127mm)

24" (610mm)

Spotlight Fixture: CFS2GPF224UNVPG

Coffaire HP Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.75 See page 4.75 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVCFS2GHP224 APGExample

Coffaire HP Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.75 See page 4.75 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVCFS2GHP2FT AIBExample

Coffaire HP Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.75 See page 4.75 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVCFS2GHP217 AHIExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'2-T52-T5HO3-T5HO

14W24W24W

CFS2GHP214 CFS2GHP224 CFS2GHP324

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-Twin tube T5 40W25W

CFS2GHP2FT CFS2GHP2FT

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-T83-T8 17W CFS2GHP217

CFS2GHP317

Page 79: Linear recessed and surface lighting

4.76 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampbasketwithunique

TransOptix lens.•Body95%reflectiveflatwhitepowdercoated.•95%InternalMiro® reflector.•69.1%efficienttwolamp32WT81'x4'luminaire.•77.4%efficienttwolamp28WT51'x4'luminaire.•Only5"deep.•Tensionscrewssecureendstobody.•SamefixturefitsbothGandTceiling.•Fitsf lushtofaceofslotgrid(T)ceiling.•Injectionmoldedlightstopatbasketends.•Perforatedlampshieldhingesfromeitherside.•Ballastaccessiblethrulampcompartment

from room side.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•ConstructiontomeetNYCCode

or Chicago Plenum requirement available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 P2** –ElectronicT8(1&2Lamp) HI* SO*ElectronicT528W(1-2Lamp) PG** –ElectronicT554W(1-2Lamp) PG** –Electronic T5 28W instant start WA*† –LOL Dimming T8 † PS –

* Instant start. Standard (WABallastonlyavailableineither120or277.)

** Program rapid start (UNVonly)†57.5Inputwatts0.93B.F.

Other dimming options. Consult factory.

Note: For T8 UNV, you must use HI or P2 ballast code.

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Coffaire HP 1' x 4'Direct/indirect recessed static luminaires

Our new high-performance Coffaire HP luminaire features a high 95% reflectance white powder painted body, our new Transoptix lens and a 95% reflectance Miro® aluminum reflector. Achieving efficiencies 20% greater than comparable luminaires currently available in the market.

CFS1GHP232UNVHIReference data

Efficiency 69.1% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 57.4W Ballastfactor .88

CFS1GHP228120WAReference data

Efficiency 77.4% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 55.4W Ballastfactor .93

Spotlight Fixture: CFS1GHP232UNVHI

4 15�16"(125mm)

11⅞" (302mm)

Spotlight Fixture: CFS1GHP228120WA

4 15�16"(125mm)

11⅞" (302mm)

Spotlight Fixture: CFS1GHP232UNVHI

4 15�16"(125mm)

11⅞" (302mm)

Spotlight Fixture: CFS1GHP228120WA

4 15�16"(125mm)

11⅞" (302mm)

30˚

60˚550

1100

1650

Candlepower Curve

30˚

60˚550

1100

1650

Candlepower Curve

Coffaire HP Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.76 See page 4.76 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVCFS1GHP232 AHIExample

Coffaire HP Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.76 See page 4.76 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

120CFS1GHP228 AWAExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4' 1-T82-T8 32W CFS1GHP132

CFS1GHP232

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4'

1-T52-T51-T5HO2-T5HO

28W28W54W54W

CFS1GHP128 CFS1GHP228 CFS1GHP154 CFS1GHP254

Page 80: Linear recessed and surface lighting

4.77Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

30˚

60˚350

700

1050

Candlepower Curve

30˚

60˚550

1100

1650

Candlepower Curve

Coffaire II 2' x 4'Direct/indirect recessed air return or static luminaires

Coffaire II combines a perforated mesh lamp shields and an indirect cove to create an aesthetically pleasing direct/indirect luminaire that has provision for air return or static operation.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior one piece body.•PerforatedMeshLampShieldswithwhiteacrylic

overlay.•60.2%efficientthreelampT82'x4'luminaire.•63.8%efficienttwolampT82'x4'luminaire.•70.8%efficienttwolampT52'x4'luminaire.•Only5"deep.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgridTceiling.•Endsecuringtensionbars.•Airreturnstandard(meetsULrequirements).•Lighttrapsbetweenbasketandfixtureend (staticmodels).

•Lampshieldhingesfromeitherside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•Builtinearthquakeclipsstandard.•Housingisavailablein20gaugesteelthatmeets NYCrequirements.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

CFH2GPF332UNVH3

5"(127mm)

24" (610mm)

Reference data

Efficiency 60.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 89W Ballastfactor 0.90

Coffaire Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.77 See page 4.77 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCFH2GPF332 AH3Example

CFH2GPF232UNVHIReference data

Efficiency 63.8% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 58W Ballastfactor 0.88

CFS2GPF254UNVPG

30˚

60˚700

1400

2100

Candlepower CurveReference data

Efficiency 70.8% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 123.2W Ballastfactor 1.0

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Coffaire Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.77 See page 4.77 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCFH2GPF232 AHIExample

Coffaire Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.77 See page 4.77 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCFS2GPF254 APGExample

Ordering informationType Size Lamp qty –type Catalog no.

Static 2' x 4' 3-T8 CFS2GPF332

Air return 2' x 4' 3-T8 CFH2GPF332

Ordering informationType Size Lamp qty –type Catalog no.

Static 2' x 4' 2-T8 CFS2GPF232

Air return 2' x 4' 2-T8 CFH2GPF232

Ordering informationType Size Lamp qty –type Catalog no.

Static 2' x 4'1-T5HO2-T5HO2-T5

CFS2GPF154 CFS2GPF254 CFS2GPF228

Page 81: Linear recessed and surface lighting

4.78 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Meets f ire test requirement of UL 1598

30˚

60˚300

600

900

Candlepower Curve

30˚

60˚400

800

1200

Candlepower Curve

Coffaire II 2' x 2'Direct/indirect recessed air return or static luminaires

Coffaire II combines a perforated mesh lamp shields and an indirect cove to create an aesthetically pleasing direct/indirect luminaire that has provision for air return or static operation.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior one piece body.•Perforatedmeshlampshieldswithwhiteacrylic overlay.•68.10%efficienttwolampTT52'x2'luminaire.•56.7%efficienttwolampT5HO2'x2'luminaire.•Only5"deep.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgridTceiling.•Endsecuringtensionbars.•Airreturnstandard(meetsULrequirements).•Lighttrapsbetweenbasketandfixtureend (staticmodels).

•Lampshieldhingesfromeitherside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•Builtinearthquakeclipsstandard.•Housingisavailablein20gaugesteelthatmeets NYCrequirements.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic TT5 40W IB*, PR** SB*Electronic T5 PG –

* Instant start.** Program start.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

5"(127mm)

24" (610mm)

Coffaire Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.78 See page 4.78 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V (Elec.TT5Ballastonly)

120CFH2GPF2FT ASBExample

CFH2GPF2FT120SBReference data

Efficiency 68.1% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 65.5W Ballastfactor 0.90

CFS2GPF224UNVPGReference data

Efficiency 56.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 56.1W Ballastfactor

5"(127mm)

24" (610mm)

Coffaire Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.78 See page 4.78 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCFS2GPF224 APGExample

Mounting methods

Exposed T-grid ceiling Exposed slot T-grid ceiling

Exposed T-bar by others

Acoustical material by others

1 ½"max.

15/16"

24"

Exposed T-bar by others

1 ½"max.

Acoustical material by others

9/16"

24"

Ordering informationType Size Lamp qty –type Catalog no.

Static 2' x 2' 2-TT5 CFS2GPF2FT

Air return 2' x 2' 2-TT5 CFH2GPF2FT

Ordering informationType Size Lamp qty –type Catalog no.

Static 2' x 2'

2-T83-T82-T52-T5HO

CFS2GPF217 CFS2GPF317 CFS2GPF214 CFS2GPF224

Air return 2' x 2' 2-T83-T8

CFH2GPF217 CFH2GPF317

Page 82: Linear recessed and surface lighting

4.79Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Coffaire II 1' x 4'Direct/indirect recessed air return or static luminaires

Coffaire II combines a perforated mesh lamp shields and an indirect cove to create an aesthetically pleasing direct/indirect luminaire that has provision for air return or static operation.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampshieldswithwhiteacrylicoverlay.•52.1%efficienttwolampT81'x4'luminaire.•55.7%efficienttwolampT51'x4'luminaire.•Only5"deep.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgridTceiling.•Airreturnstandard(meetsULrequirements).•Lampshieldhingesfromeitherside.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•2earthquakeclipsstandard.•Housingisavailablein20gaugesteelthatmeets NYCrequirements.

•ConstructiontomeetChicagoPlenumrequirementsis available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 P2** –ElectronicT8(1&2Lamp) HI* SO*ElectronicT528W(1-2Lamp) PG** –ElectronicT554W(1-2Lamp) PG** –Electronic T5 28W instant start WA*† –LOL Dimming T8 PS –

* Instant start. Standard (WABallastonlyavailableineither120or277.)

** Program rapid start (UNVonly)†57.5Inputwatts0.93B.F.

Other dimming options. Consult factory.

Note: For T8 UNV, you must use HI or P2 ballast code.

Drywall kit: Conversion kit for 1' x 4' unit: FK91X4.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

CFH1GPF232UNVHI

5"(127mm)

12" (305mm)

Coffaire Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.79 See page 4.79 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVCFH1GPF232 AHIExample

CFH1GPF228120WA

5"(127mm)

12" (305mm)

Coffaire Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.79 See page 4.79 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

120CFH1GPF228 AWAExample

30˚

60˚400

800

1200

Candlepower Curve

30˚

60˚400

800

1200

Candlepower Curve

Reference data

Efficiency 52.1% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 67.7W Ballastfactor 0.87

Reference data

Efficiency 55.7% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 57.0W Ballastfactor 0.93

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Air return 1' x 4'

1-T52-T51-T5HO2-T5HO

28W28W54W54W

CFH1GPF128 CFH1GPF228 CFH1GPF154 CFH1GPF254

Static 1' x 4'

1-T52-T51-T5HO2-T5HO

28W28W54W54W

CFS1GPF128 CFS1GPF228 CFS1GPF154 CFS1GPF254

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Air return 1' x 4' 1-T82-T8 32W CFH1GPF132

CFH1GPF232

Static 1' x 4' 1-T82-T8 32W CFS1GPF132

CFS1GPF232

Page 83: Linear recessed and surface lighting

4.80 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Coffaire II Air 2' x 4'Direct/indirect recessed air supply and return luminaires

Coffaire II Air combines our traditional soft light perforated basket appearance with air supply/return functions for installations that demand both features.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampshieldswithwhiteacrylicoverlay.•Contouredbodyandends.•airsupplyandreturn.•Airreturnslotslocatedabovelampshield.•AirreturnmodelsmeetUL1598,Paragraph9.2.2.5

requirements.•65.0%efficienttwolamp28WT52'x4'luminaire.•70.8%efficienttwolamp54WT52'x4'luminaire.•63.8%efficienttwolampT82'x4'luminaire.•60.2%efficientthreelampT82'x4'luminaire.•Only5"deep.•Tensionscrewssecureendstobody.•Perforatedlampshieldhingesfromeitherside.•Canbecontinuousrowmounted.•Built-inearthquakeclips.•Ballastaccessiblefromroomside.•Optionalsupplyairslotcover.•MeetsNYCCode.•ConstructiontomeetChicagoPlenumrequirements

is available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Electrical wiring options: Consult factory.Dust Shield: See folio number: OA50-20.

Optional supply air slot cover:OrderCatNo:CACS-4 CSP.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Chicago Plenum: Suffix: C.

30˚

60˚700

1400

2100

Candlepower CurveCFA2GPF254UNVPG

5"(127mm)

24" (610mm)

Reference data

Efficiency 70.8% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 123W Ballastfactor 1.0

Coffaire II Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.80 See page 4.80 air supply and return 277=277V andpage4.130 w/perforated mesh shield UNV=120-277V

UNVCFA2GPF254 APGExample

30˚

60˚400

800

1200

Candlepower CurveCFA2GPF232UNVHI

5"(127mm)

24" (610mm)

Reference data

Efficiency 63.8% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 58W Ballastfactor .87

Coffaire II Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.80 See page 4.80 air supply and return 277=277V andpage4.130 w/perforated mesh shield UNV=120-277V

UNVCFA2GPF232 AHIExample

30˚

60˚600

1200

1800

Candlepower CurveCFA2GPF332UNVH3

5"(127mm)

24" (610mm)

Reference data

Efficiency 60.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 85W Ballastfactor .88

Coffaire II Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.80 See page 4.80 air supply and return 277=277V andpage4.130 w/perforated mesh shield UNV=120-277V

UNVCFA2GPF332 AH3Example

Ordering informationType Size Lamp qty –type Catalog no.

Air supply and return 2' x 4' 2-T5 CFA2GPF254 CFA2GPF228

Ordering informationType Size Lamp qty –type Catalog no.

Air supply and return 2' x 4' 2-T8 CFA2GPF232

Ordering informationType Size Lamp qty –type Catalog no.

Air supply and return 2' x 4' 3-T8 CFA2GPF332

Page 84: Linear recessed and surface lighting

4.81Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Coffaire II Air 2' x 2'Direct/indirect recessed air supply and return luminaires

Coffaire II Air combines our traditional soft light perforated basket appearance with air supply/return functions for installations that demand both features.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampshieldswithwhiteacrylicoverlay.•Contouredbodyandends.•airsupplyandreturn.•Airreturnslotslocatedabovelampshield.•AirreturnmodelsmeetUL1598,Paragraph9.2.2.5

requirements.•68.1%efficienttwolampTT52'x2'luminaire.•55.2%efficienttwolampTT52'x2'luminaire.•61.7%efficienttwolampT82'x2'luminaire.•55.9%efficientthreelampT82'x2'luminaire.•Only5"deep.•Tensionscrewssecureendstobody.•Perforatedlampshieldhingesfromeitherside.•Canbecontinuousrowmounted.•Built-inearthquakeclips.•Ballastaccessiblefromroomside.•Optionalsupplyairslotcover.•MeetsNYCCode.•ConstructiontomeetChicagoPlenumrequirements

is available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic TT5 40W IB*, PR** SB*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical wiring options: Consult factory.Dust Shield: See folio number: OA50-20.

Optional supply air slot cover:OrderCatNo:CACS-2 CSP.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Chicago Plenum: Suffix: C.

30˚

60˚500

1000

1500

Candlepower CurveCFA2GPF2FT120SB

5"(127mm)

24" (610mm)

Reference data

Efficiency 68.1% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 65W Ballastfactor .86

Coffaire II Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.81 See page 4.81 air supply and return 277=277V andpage4.130 w/perforated mesh shield UNV=120-277V

120CFA2GPF2FT ASBExample

30˚

60˚200

400

600

Candlepower CurveCFA2GPF217UNVHI

5"(127mm)

24" (610mm)

Reference data

Efficiency 61.7% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 30W Ballastfactor .93

Coffaire II Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.81 See page 4.81 air supply and return 277=277V andpage4.130 w/perforated mesh shield UNV=120-277V

UNVCFA2GPF217 AHIExample

30˚

60˚300

600

900

Candlepower CurveCFA2GPF317UNVH3

5"(127mm)

24" (610mm)

Reference data

Efficiency 55.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 46W Ballastfactor 1.0

Coffaire II Air Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.81 See page 4.81 air supply and return 277=277V andpage4.130 w/perforated mesh shield UNV=120-277V

UNVCFA2GPF317 AH3Example

Ordering informationType Size Lamp qty –type Catalog no.

Air supply and return 2' x 2' 2-TT53-TT5

CFA2GPF2FT CFA2GPF3FT

Ordering informationType Size Lamp qty –type Catalog no.

Air supply and return 2' x 4' 3-T8 CFA2GPF317

Ordering informationType Size Lamp qty –type Catalog no.

Air supply and return 2' x 2'2-T82-T52-T5HO

CFA2GPF217 CFA2GPF214 CFA2GPF224

Page 85: Linear recessed and surface lighting

4.82 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

CoffaireDropBasket2'x4'Direct/indirect recessed static luminaires

CoffaireDropBasketoffersT8andT5lampoptionsinabodythatisonlyrecessed2-1/4".The2-7/16"deepperforatedbasketcreatesuniformlightdistributionthatbrightenswallsand ceilings. Evenly illuminating both horizontal and vertical surfaces, creating a soft, balanced brightness that enhances visual acuity while creating a visual statement on the ceiling line.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampshieldswithwhiteacrylicoverlay.•60.8%efficienttwolampT82'x4'luminaire.•66.0%efficientthreelampT82'x4'luminaire.•69.9%efficienttwolamp28WT52'x4'luminaire.•66.4%efficienttwolamp54WT5HO2'x4'luminaire.•Only2-1/4"plenumdepth.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceiling.•Lampshieldhingesfromeitherside.•Wiringaccessplatestandard.•OptionalDALIballastiGENTechnologyacceptsdigital

dimming controllers, scene controllers and automatic control devices.

•ConstructiontomeetChicagoPlenumavailable.•MeetsNYCCoderequirements.•Notforcontinuousrowmounting.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Electrical wiring options: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Only 2 ¼" Deep

30˚

60˚450

900

1350

Candlepower CurveCDS2GPF228UNVPG

4 11�16"(119mm)

24" (610mm)

Reference data

Efficiency 69.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 122W Ballastfactor 1.0

Coffaire Drop Basket Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.82 See page 4.82 277=277V andpage4.130 UNV=120-277V

UNVCDS2GPF228 APGExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T53-T52-T83-T81-T5HO2-T5HO

28W28W32W32W54W54W

CDS2GPF228 CDS2GPF328 CDS2GPF232 CDS2GPF332 CDS2GPF154 CDS2GPF254

Page 86: Linear recessed and surface lighting

4.83Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

CoffaireDropBasket2'x2'Direct/indirect recessed static luminaires

CoffaireDropBasketoffersT8andT5lampoptionsinabodythatisonlyrecessed2-1/4".The2-7/16"deepperforatedbasketcreatesuniformlightdistributionthatbrightenswallsand ceilings. Evenly illuminating both horizontal and vertical surfaces, creating a soft, balanced brightness that enhances visual acuity while creating a visual statement on the ceiling line.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampshieldswithwhite acrylic overlay.•59.4%efficienttwolampT82'x2'luminaire.•55.5%efficientthreelampT82'x2'luminaire.•62.9%efficienttwolampT52'x2'luminaire.•62.6%efficienttwolampT5HO2'x2'luminaire.•55.0%efficienttwolampTT52'x2'luminaire.•Only2-1/4"plenumdepth.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceiling.•Lampshieldhingesfromeitherside.•Wiringaccessplatestandard.•OptionalDALIballastiGENTechnologyacceptsdigital

dimming controllers, scene controllers and automatic control devices.

•ConstructiontomeetChicagoPlenumavailable.•MeetsNYCCoderequirements.•Notforcontinuousrowmounting.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic TT5 40W IB*, PR** SB*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical wiring options: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚180

360

540

Candlepower CurveCDS2GPF214UNVPG

4 11�16"(119mm)

24" (610mm)

Reference data

Efficiency 62.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 33W Ballastfactor 1.0

Coffaire Drop Basket Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.83 See page 4.83 277=277V andpage4.130 UNV=120-277V

UNVCDS2GPF214 APGExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'

2-T52-T5HO2-TT52-T83-T8

14W24W40W17W17W

CDS2GPF214 CDS2GPF224 CDS2GPF2FT CDS2GPF217 CDS2GPF317

Page 87: Linear recessed and surface lighting

4.84 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

CoffaireDropBasket2'x4'Direct/indirect surface mounted static luminaires

CoffaireDropBasket~SurfaceMountedoffersT8andT5lampoptionsinabodythatisonly2-17/32"deep.The2-7/16"deepperforatedbasketcreatesuniformlightdistributionthat brightens walls and ceilings. Evenly illuminating both horizontal and vertical surfaces, creating a soft, balanced brightness that enhances visual acuity while creating a visual statement on the ceiling line.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampshieldswithwhiteacrylicoverlay.•68.0%efficienttwolamp32WT82'x4'luminaire.•69.9%efficienttwolamp28WT52'x4'luminaire.•Lampshieldhingesfromeitherside.•OptionalDALIballastiGENTechnologyacceptsdigital

dimming controllers, scene controllers and automatic control devices.

•MeetsNYCCoderequirements.•Notforcontinuousrowmounting.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic T5 PG –

* Instant start.

** Program start.

Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

30˚

60˚400

800

1200

Candlepower CurveCDB2SPF232UNVHI

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

Spotlight Fixture: CFS2GPF224UNVPG Spotlight Fixture: CDB2SPF228UNVPG

Spotlight Fixture: CDB2SPF217UNVHI Spotlight Fixture: CDB2SPF214UNVPG

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

4 11�16"(119mm)

24" (610mm)

4 11�16"(119mm)

24" (610mm)

4 11�16"(119mm)

24" (610mm)

Reference data

Efficiency 68.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 50.4W Ballastfactor 0.88

30˚

60˚450

900

1350

Candlepower CurveCDB2SPF228UNVPG

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

Spotlight Fixture: CFS2GPF224UNVPG Spotlight Fixture: CDB2SPF228UNVPG

Spotlight Fixture: CDB2SPF217UNVHI Spotlight Fixture: CDB2SPF214UNVPG

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

4 11�16"(119mm)

24" (610mm)

4 11�16"(119mm)

24" (610mm)

4 11�16"(119mm)

24" (610mm)

Reference data

Efficiency 69.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 122.1W Ballastfactor 1

Coffaire Drop Basket Voltage Ballast Options Direct/indirect Surface 120=120V Seepage4.84 See page 4.84 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCDB2SPF232 AHIExample

Coffaire Drop Basket Voltage Ballast Options Direct/indirect Surface 120=120V Seepage4.84 See page 4.84 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCDB2SPF228 APGExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4' 2-T83-T8 32W CDB2SPF232

CDB2SPF332

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T53-T51-T5HO2-T5HO

28W28W54W54W

CDB2SPF228 CDB2SPF328 CDB2SPF154 CDB2SPF254

Page 88: Linear recessed and surface lighting

4.85Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

CoffaireDropBasket2'x2'Direct/indirect surface mounted static luminaires

CoffaireDropBasket~SurfaceMountedoffersT8andT5lampoptionsinabodythatisonly2-17/32"deep.The2-7/16"deepperforatedbasketcreatesuniformlightdistributionthat brightens walls and ceilings. Evenly illuminating both horizontal and vertical surfaces, creating a soft, balanced brightness that enhances visual acuity while creating a visual statement on the ceiling line.

Features•Direct/indirectlampshieldappearancewithsoft

contoured interior.•Perforatedmeshlampshieldswithwhiteacrylicoverlay.•59.4%efficienttwolampT82'x2'luminaire.•62.9%efficienttwolampT52'x2'luminaire.•Lampshieldhingesfromeitherside.•OptionalDALIballastiGENTechnologyacceptsdigital

dimming controllers, scene controllers and automatic control devices.

•MeetsNYCCoderequirements.•Notforcontinuousrowmounting.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic TT5 40W IB*, PR** SB*Electronic T5 PG –

* Instant start.

** Program start.

Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

30˚

60˚170

340

510

Candlepower CurveCDB2SPF217UNVHI

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

Spotlight Fixture: CFS2GPF224UNVPG Spotlight Fixture: CDB2SPF228UNVPG

Spotlight Fixture: CDB2SPF217UNVHI Spotlight Fixture: CDB2SPF214UNVPG

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

4 11�16"(119mm)

24" (610mm)

4 11�16"(119mm)

24" (610mm)

4 11�16"(119mm)

24" (610mm)

Reference data

Efficiency 59.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 30.8W Ballastfactor 0.88

30˚

60˚180

360

540

Candlepower CurveCDB2SPF214UNVPG

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

Spotlight Fixture: CFS2GPF224UNVPG Spotlight Fixture: CDB2SPF228UNVPG

Spotlight Fixture: CDB2SPF217UNVHI Spotlight Fixture: CDB2SPF214UNVPG

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

24" (610mm)

2 7/16 (61.91mm)

2 1/4 (57.15mm)

4 11�16"(119mm)

24" (610mm)

4 11�16"(119mm)

24" (610mm)

4 11�16"(119mm)

24" (610mm)

Reference data

Efficiency 62.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 33.2W Ballastfactor 1.06

Coffaire Drop Basket Voltage Ballast Options Direct/indirect Surface 120=120V Seepage4.85 See page 4.85 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCDB2SPF217 AHIExample

Coffaire Drop Basket Voltage Ballast Options Direct/indirect Surface 120=120V Seepage4.85 See page 4.85 w/perforated mesh shield 277=277V andpage4.130 UNV=120-277V

UNVCDB2SPF214 APGExample

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-T83-T8 17W CDB2SPF217

CDB2SPF317

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'2-T52-T5HO2-Twin tube T5

14W24W40W

CDB2SPF214 CDB2SPF224 CDB2SPF2FT

Page 89: Linear recessed and surface lighting

4.86 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Coffaire SQ 2' x 2'Direct/indirect recessed static luminaires

Coffaire SQ offers a white translucent acrylic lens that blends into the reflector paint finish toprovideauniquefreefloatingappearancetotheattached10"squareperforatedmeshsteel center panel in an aesthetically pleasing direct/indirect luminaire.

30˚

60˚350

700

1050

Candlepower CurveCFS2GSQ224UNVPG

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 75.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 49.8W Ballastfactor 1

Features•75.6%efficienttwolamp24WT5HO2'x2'luminaire.•75.2%efficienttwolamp14WT52'x2'luminaire.•72.7%efficienttwolamp17WT82'x2'luminaire.•Direct/indirectf ixturewithasoftlycontouredinterior.•Lenshingesfromeithersideoff ixture.•Only5"deep.•SamefixturefitsbothGandTceilingtypes.•Fitsf lushtofaceofslotgrid(T)ceiling.•Built-inearthquakeclips.•Canbecontinuousrowmounted.•Wiringaccessplatestandard.•MeetsNYCCoderequirements.•ConstructiontomeetChicagoPlenumrequirement

is available.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp T8 H3*, P3** O3*Electronic TT5 40W IB*, PR** SB*Electronic T5 PG –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Packaging: Individual carton is standard.

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'

2-T53-T52-T5HO3-T5HO

14W14W24W24W

CFS2GSQ214 CFS2GSQ314 CFS2GSQ224 CFS2GSQ324

Coffaire SQ Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.86 See page 4.86 w/acrylic lens and perforated 277=277V andpage4.130 steel center panel UNV=120-277V

UNVCFS2GSQ224 APGExample

30˚

60˚250

500

750

Candlepower CurveCFS2GSQ217UNVHI

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 72.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 30.3W Ballastfactor 0.91

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-T83-T8 17W CFS2GSQ217

CFS2GSQ317

Coffaire SQ Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.86 See page 4.86 W/acrylic lens and perforated 277=277V andpage4.130 steel center panel UNV=120-277V

UNVCFS2GSQ217 AHIExample

30˚

60˚550

1100

1650

Candlepower CurveCFS2GSQ2FT120SB

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

Reference data

Efficiency 71.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 67.0W Ballastfactor 0.88

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2' 2-Twin tube T53-Twin tube T5 40W CFS2GSQ2FT

CFS2GSQ3FT

Coffaire SQ Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.86 See page 4.86 w/acrylic lens and perforated 277=277V andpage4.130 steel center panel UNV=120-277V

UNVCFS2GSQ2FT APRExample

Page 90: Linear recessed and surface lighting

4.87Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Features•Masksunsightlyinsectsanddebrisfromappearingon

the perforated basket.•ForusewithCoffaireSeries.•.040Translucentwhiteacrylicsecondaryliner

Features•Minimizespenetrationofdust,insectsandotherdebris

into the lamp compartment.•Encloseslampcompartment.•Impactresistantclearacryliclens.•Hingesatendcaps.•Doesnotinterferewithbasketremovalandrelamping

Coffaire Dust/Insect Shield DFor Coffaire series

1x4 Dust ShieldDust Shield Liner

2x2 & 2x4 Dust ShieldDust Shield Liner

PlasticStand off

PerforatedBasket

PerforatedBasket

6 ⅜"(161mm)

8 ⅛"(206mm)

11�16"(23mm)

11�16"(23mm)

45 11�16" (1167mm)

45 15�16" (1167mm)21 15�16" (557mm)

PlasticStand off

1x4 Dust ShieldDust Shield Liner

2x2 & 2x4 Dust ShieldDust Shield Liner

PlasticStand off

PerforatedBasket

PerforatedBasket

6 ⅜"(161mm)

8 ⅛"(206mm)

11�16"(23mm)

11�16"(23mm)

45 11�16" (1167mm)

45 15�16" (1167mm)21 15�16" (557mm)

PlasticStand off

Ordering information

Ordering information

Standard With dust/insect sheildCFS2G PF 2FTUNVIB CFS2G PF 232UNVHI

CFS2G PD 2FTUNVIB CFS2G PD 232UNVHI

Standard With dust/insect sheildCFS2G PF 2FTUNVIB CFS2G PF 232UNVHI

CFS2G PG 2FTUNVIB CFS2G PG 232UNVHI

To specif iy dust/insect shield change PF in the catalog no. to PD

To specif iy dust/insect shield change PF in the Catalog no. to PG

Compatible with Coffaire SeriesPrefix CFS, CFH, CFA 1X4, 2X2 and 2X4 Sizes

Photometry: Use standard photometric tests and multiply light loss factor by 0.98

Compatible with Coffaire SeriesPrefix CFS, 2X2 and 2X4 Sizes

Photometry: Use standard photometric tests and multiply light loss factor by 0.98

Coffaire Dust Guard GFor static Coffaire series

ClearLens

Example

Example

Page 91: Linear recessed and surface lighting

4.88 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

ULM-EZR Module can be relocated at any time with out use of tools. ULM-EZR Module blends in with the ceiling system. With a low profile and visible f latdimensionof3"X3.2"theULM-EZR causes a minimal interruption to the ceiling plane.

DL Daylighting SystemDirect/indirect recessed luminaires

Even when you have selected the most energy efficient luminaire/ballast/lamp combination for your space, additional energy savings can be made by utilizing natural daylight through use of

controls. In the past, many have felt “Daylighting” was too complicated because of the wiring required for the interface of the fixtures to the control sensors, the adjustability

of the sensors and the inflexibility if you relocated furniture or it did not quite work to your satisfaction.

Page 92: Linear recessed and surface lighting

4.89Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

DL Daylighting SystemDirect/indirect recessed luminaires

Now,PhilipsLightoliermakesdaylightingaseasyas1-2-3.

Step 1Install Philips Lightolier recessed luminaires* which include a 0-10 volt dimming ballast and the #EZR option per your Lighting Layout and connect to AC power as you normally would any recessed luminaire.

Step 2

Step 3

Install a ULM-EZR module in the ceiling, positioning it 6 to 10 feet from windows and over a work surface (itmustbewithin10ftofaluminaire).

The DL System is the combination of the ULM-EZR Module (UF2F-EZR)anda Philips Lightolier recessed fluorescent fixture* with a 0-10 volt dimming ballast and the #EZR option. This option includes integrated RJ45 receptacles and a 12' long CAT5 cable.

Using the low voltage plug-in 12' long CAT5 cables provided with the luminaires*, connect the luminaire and ULM-EZR module.

An additional CAT5 cable will be provided with each luminaire* to plug in additional luminaires* as in a daisy chain. Up to 20 luminaires* can be connected to a single ULM-EZR module.

When there is no daylight, place a lightmeter on the work surface and take a footcandle reading.

Adjust to desired footcandle level by rotating the sensor in the face of the ULM-EZR Module.

To get MORE light on desk from the luminaire, close aperture by rotating it counter-clockwise. The lamps will get brighter.

To get LESS light on desk from the luminaire, open aperture by rotating it clockwise. The lamps will dim down.

The sensors are factory pre-calibrated to 45fc on the horizontal, assuming standardreflectances(80/50/20),ceilingheights(8-10’)andworksurfaces(2.5’).To return to the default setting, rotate the aperture until it ‘clicks’ back into place at the mid-point.

ULM-EZR modules can be moved or added at any time merely by plugging or unplugging the CAT5 cables.

BothULM-EZR modules and fixtures have RJ45 dual receptacles for the CAT5 cable with RJ45 plugs.

ULM-EZR module sensor placement guidelinesBeforeadjustingsensorsettings,checktomakesurethey have been installed in accordance with the following guidelines:

Sensor SHOULD be located. •Between6-10’awayfromwindow. •Overworksurfaces.Sensor should NOT be located. •Oververydarksurfaces(e.g.darkcarpetorfurniture). •Overhighlyreflectivesurfaces(e.g.polishedfloorortable). •Outsidethedaylitzone(typicallybeyond15’fromwindow)

Ordering informationThe module and luminaire need to be ordered separately.

ULM-EZR Module: UL2F-EZR

DL System fixture: Specify a Philips Lightolier recessed fluorescent fixture* with a 0-10 volt, 2 wire, dimming ballast and then add suffix #EZR . (e.g. CFS2GPF232UNVM7-#EZR)

M7DenotesAdvanceMarkVIIdimmingballastforthislampingconfiguration.Otherlampingconfigurationsanddimmingballast manufacturers available. *Consult your Philips Lightolier representative for list of DL System compatible 1' x 4', 2' x2'and2'x4'recessedfluorescentf ixtures(Alterexempt).

Page 93: Linear recessed and surface lighting

Linear recessed and surface lighting

4.90 Philips Lightolier For complete specif ication information visit www.lightolier.com

Recessed & wall washing

Recessed fluorescent luminaires represent just slightly less than 50% of all commercial and industrial fluorescents sold in the United States. They are usually the “A” fixture on a project. Their use has become popular over the years because the use of low ceiling heights dictates putting the fixture behind the ceiling instead of on it, and mechanical ceiling lay-in systems made the fixture less costly to install than surface or pendant luminaires.

Our recessed line consists of many different body sizes and shielding media, such as large or small cell aluminum parabolic louvers, plastic parabolic louvers, and a variety of lenses, all to meet a designer’s application needs. Our vast product offering allows today’s designer to carefully select luminaires that will enhance any space and perform to exceptional standards.

Page 94: Linear recessed and surface lighting

Linear recessed and surface lighting

4.91Comprehensive lighting catalog 7th Edition

Lytecel 6 > 4.94 CTS3 > 4.100 PTS family > 4.102 GO2 family > 4.106 VisionSmart > 4.110 Stacklyte > 4.117 Deepcel Plus > 4.118

Prismalyte Plus > 4.122 Specplus > 4.124 XP&XP/XA > 4.126 FRX > 4.128 Options & accessories > 4.130 Quick-connect interties > 4.131 Wall washer & accent > 4.132

Contents

Page 95: Linear recessed and surface lighting

Linear recessed and surface lighting

4.92 Philips Lightolier For complete specif ication information visit www.lightolier.com

LightingforVDTareasANSI/IES RP-1, 2004 requirements for lighting VDT areas

The near-universal use of computers in office areas today is a major change in the workplace. Whereas office lighting was formerly designed to suit visual conditions for paper tasks in the horizontal plane, it must now take into consideration visual tasks comprised of a reflectivevisualdisplayterminal(VDT)intheverticalplaneandpapertasksinthehorizontalor vertical plane. This means that a new set of parameters must be considered both to limit distractingreflectionsinthevisualdisplayterminal(VDT)andbecauseofthepotentialforeye adaption problems; otherwise, a loss of visual performance will occur, with attendant problems of eyestrain, fatigue and loss of productivity.

A number of authorities have concerned themselves with this issue, most notably the Illuminating Engineering Society, who in 1989 issued a recommended practice for lighting office areas containing visual display terminals, RP-24. This was replaced in 1993 and then in 2004bytheAmericanNationalStandardforOfficeLightingANSI/IESRP-12004,whichisaccepted as the quality standard for the lighting of today’s office.

ToreducecontrastbetweentheVDTscreenandthesurroundingareaandtasks

Illuminance: Average maintained illuminance levels should not exceed 50 footcandles on the horizontal plane. If a higher level is required because of older eyes or very demanding tasks, it should be provided by supplemental task lighting. In office work that requires constant viewing of the visual display (e.g.: telephone reservations or scientif ic and engineeringdialogueswiththecomputer)where paper based visual tasks are not important, illuminance should be kept as low as possible while still achieving good visual performance.Luminance ratios: Notmorethan3:1between the task and adjacent surfaces; not more than 10:1 between the task and remote surfaces.

24 Horizontal footcandlesPhilipsLightolierVP1Lamp

49 Horizontal footcandlesPhilipsLightolierVP2Lamp

VDTscreeninaspacewithfixtures that do not meet RP-1, 2004.

VDTscreeninaspacewithfixtures that meet RP-1, 2004.

70 Horizontal footcandlesTypical 3 Lamp. Does not meet IES RP-1 2004 requirements.

1.3:1Brightnessratio 3:1Maximum(RP-1-04)

2.1:1Brightnessratio 3:1Maximum(RP-1-04)

3.4:1Brightnessratio 3:1Maximum(RP-1-04)

To reduce direct glare from the lighting fixtures at normal viewing angles: Visual Comfort Probability (VCP): 80, minimum.To minimize reflections of the lighting fixtures in the VDT screen.

Angle from VDT VDT Vertical Intensive Normal 55° 300 cd — 65° 220 cd 300 cd 75° 135 cd 185 cd 85° 45 cd 60 cdNote: This table shows candlepower values, not luminance values as in previous recommendations.

Page 96: Linear recessed and surface lighting

Linear recessed and surface lighting

4.93Comprehensive lighting catalog 7th Edition

Philips Lightolier suggested LEED luminairesComparisons in office space

Direct/indirect recessed 90.1 1999 90.1 2004

Philips Lightolier catalog no. Family Lamp Lamp

lumens Watts BF Luminaire spacing fc* w/sq ft % LEED % LEED

H9S2GPR228120WA HP90 T5 28W 2600 54.6 0.93 8X10 55.2 0.683 47.47% 31.70%

H9S2GPR232(28)UNV HP90 T5 28W 2725 51.1 0.88 8X10 50.6 0.639 50.85% 36.10%

PPH2G12FW228120WA Paraplus T5 28W 2600 55.4 0.93 8X10 48.9 0.693 46.69% 30.70%

H9S2GPR228120WA HP90 T5 28W 2600 54.6 0.93 8X10 48.0 0.630 51.54% 37.00%

H9S2GPR232(28)UNV HP90 T5 28W 2725 51.1 0.88 8X10 41.5 0.590 54.62% 41.00%

PPH2G12FW228120WA Paraplus T5 28W 2600 56 0.93 8X10 44.0 0.646 50.31% 35.40%

H9S2GPR228120WA HP90 T5 28W 2600 54.6 0.93 8 44.2 0.910 30.00% 9.00%

H9S2GPR232(28)UNV HP90 T5 28W 2725 51.1 0.88 8 37.9 0.852 34.46% 14.80%

PPH2G12FW228120WA Paraplus T5 28W 2600 56 0.98 8 42.3 0.933 28.23% 6.70%

Recessed direct 90.1 1999 90.1 2004

Philips Lightolier catalog no. Family Lamp Lamp

lumens Watts BF Luminaire spacing fc* w/sq ft % LEED % LEED

DPA2G12LS232120WO Deepcel T8 30W 2900 52 0.88 8X10 50.9 0.650 50.00% 35.00%

DPA2G12LS232120DG Deepcel T8 32W 2950 77 1.20 8X10 70.6 0.963 25.92% 3.70%

SPS2GFSVA232120WO Specline T8 30W 2900 52 0.88 8X10 52.3 0.650 50.00% 35.00%

SPS2GFSVA232120DG Specline T8 32W 2950 77 1.20 8X10 72.6 0.963 25.92% 3.70%

DPA2G12LS232120WO Deepcel T8 30W 2900 52 0.88 8X10 46.1 0.600 53.85% 40.00%

DPA2G12LS232120DG Deepcel T8 32W 2950 77 1.20 8X10 62.9 0.888 31.69% 11.20%

SPS2GFSVA232120WO Specline T8 30W 2900 52 0.88 8X10 48.6 0.600 53.85% 40.00%

SPS2GFSVA232120DG Specline T8 32W 2950 77 1.20 8X10 64.7 0.888 31.69% 11.20%

DPA2G12LS232120WO Deepcel T8 30W 2900 52 0.88 8 46.8 0.867 33.31% 13.30%

SPS2GFSVA232120WO Specline T8 30W 2900 52 0.88 8 46.9 0.867 33.31% 13.30%

60' x 56' Room 30' x 26' Room 12' x 10' Room

Page 97: Linear recessed and surface lighting

4.94 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Lytecel6LensLED6"x48"Direct recessed air return or static luminaires

The Lytecel 6 LED recessed lens brings both flexibility and unity to lighting. Create continuous lines of light with the recessed Lytecel 6 Lens LED. Its crisp, clean lines and minimalist design is sure to bring style, freshness and subtle distinction to modern office and retail interiors. A unique non-visible return air opening allows this product to have air return capabilitiesifneeded.Itfitsmoststandard6"X48"layinsystemsandisdesignedspecificallyfor the Armstrong TechZone® ceiling systems.

Features•Non-visiblereturnairopenings.•Airreturnlensregressed1-9/16",staticregressed1-3/16".

•AirreturnmodelsmeetUL1598,Paragraph9.2.2.5requirements.

•Extrudedaluminumfixturetrimflatwhitepolyesterpowder coated.

•Extruded.080whiteopalescentacryliclens.•Only6"deepbody.•Canprovide34initialfootcandlesat0.53wattsper

square foot.•Delivers2864lumenswithjust44.9inputwatts.•FieldreplaceableLEDarrayanddriversaccessiblefrom

below.•Integratedthermalmanagementsystemconductsheat

away from LEDs and transfers it to the surrounding environment.

•HighefficiencyLEDshave50,000hourratedlifeatL70.•PredictedL70lifetimeisbasedonLEDmanufacturer’s

supplied LM-80 data and in-situ laboratory testing.•20gaugesteelhousing.•UL-Listedtwinknockoutaccessplate.•2hold-downclipsstandard.•MeetsNYCCoderequirements.•CompatiblewithArmstrongTechZoneceilingsystems.•Five-yearwarrantyonluminaire,LEDboardsanddriver.

Options & accessoriesDrywall kit: For individual mounts only: FK906X4.Access plate: Top wiring access plate is shipped with fixture as standard. When access plates are required in advance for wiring convenience, specify separately. Order catalog no.: ACP5 CSP.EM Pack or dimming ballast: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

LIA64GPN28A40ULAG

5" (126mm)

6" (152mm)

6" (152mm)

1 ⅛" (30mm)

1 9�16" (40mm)

Air Return Static

5 ¾" (146mm)

5 ¾" (146mm)

5" (126mm)

6" (152mm)

6" (152mm)

2 ⅞" K.O. (22mm)

LED Driver

Lens

⅞" K.O. (22mm)

4 ¼" (108mm)

48" (1,219mm)

Ordering information

Type Delivered lumens

Input watts

Lumens per watt

8'x10½" initial footcandles*

8'x10½' watts per sq. foot Catalog no.

Air return and Static

2011250028643174

30.038.444.950.8

67.065.163.862.5

24303438

0.360.460.530.60

LIA64GPN20A40ULAGLIA64GPN25A40ULAGLIA64GPN28A40ULAGLIA64GPN31A40ULAG

For Static Handling housing models substitute LIS64 for LIA64.* 42 Recessed LED Luminaires in a 60' x 56' x 9' room with a reflectance of 80/50/20, placed 8' x 10' on center. Footcandlereadingsaretaken2½'fromfloorlevel.

Lytecel 6 Lens shielding Lumen 1 Color temp 1,2 Voltage Driver 2 Options LED PN=.08White 20A=20klm 40=4000K UNV = LAG = Seepage4.94 Direct Acrylic 25A=25klm 120-277V LEDDriver Recessed 28A=28klm 31A=31klm

1.Approximatedeliveredvalues(ConsultIESf ile). 2. Consult representative for other color temperature options and driver dimming options.

LIA64G 40Example U LAG

Page 98: Linear recessed and surface lighting

4.95Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Lytecel6Lens6"x48"Direct recessed air return or static luminaires

Lytecel 6 Lens is an extension of our popular Lytecel 6 parabolic product line. Lytecel 6 Lens offers a low in brightness extruded white opalescent acrylic lens, allowing the right amount of light to be delivered to walls and work surfaces in an office environment. A unique non-visible return air opening allows this product to have air return capabilities if needed. Itfitsmoststandard6"X48"layinsystemsandisdesignedspecificallyfortheArmstrongTechZone® ceiling systems.

Features•Non-visiblereturnairopenings.•Lensregressed19/16".•Fixturetrimflatwhitepolyesterpowdercoated.•Extruded.080whiteopalesentacryliclens.•Only6"deepbody.•64.3%efficient1lamp54WattT5HOwithlens.•1.2spacingmountingratio.•20gaugesteelhousing.•Blackhousingexteriorforcoolerballastoperating

temperature.•UL-Listedtwinknockoutaccessplate.•Canbemountedincontinuousrows.•2hold-downclipsstandard.•CompatiblewithArmstrongTechZone® ceiling systems.•MeetsNYCCoderequirements.•OptionalDALIballastacceptsdigitaldimmingcommands

from computers, scene controllers and automatic control devices.

Options & accessories page 4.130

Ballast type <10THD <20THD

Electronic T8 HI* SO*Elec.PST832W(1or2Lamp) P2 –Elec. T5 P.S. 28W or 54W PG –

* Instant start

Drywall kit: For individual mounts only: FK906X4.Access plate: Top wiring access plate is shipped with fixture as standard. When access plates are required in advance for wiring convenience, specify separately. Order catalog no.: ACP5 CSP.Electrical/wiring options: Consult factory.EM Pack or dimming ballast: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

LIA6GPNXR254UNVPG

4 15�16" (126mm)

6" (152mm)

6" (152mm)

1 ⅛" (30mm)

1 9�16" (40mm)

2 ⅞" K.O. (22mm)

Air Return Static

5 ¾" (146mm)

5 ¾" (146mm)

⅞" K.O. (22mm)

4 ¼" (108mm)

48" (1,219mm)

4 15�16" (126mm)

6" (152mm)

6" (152mm)

Lytecel 6 Voltage Ballast Options 6"x48"RecessedLens 120=120V Seepage4.95 See page 4.95 277=277V andpage4.130 UNV=120-277V (ElectT5orT8)

UNVLIA6GPNXR154 APGExample

Ordering informationType Lamp qty –type Lamp watts Standard grid ceiling = G Slot grid ceiling = T

Air return

2-T5HO1-T5HO2-T51-T52-T81-T8

54W54W28W28W32W32W

LIA6GPNXR254 LIA6GPNXR154 LIA6GPNXR228 LIA6GPNXR128 LIA6GPNXR232 LIA6GPNXR132

LIA6TPNXR254 LIA6TPNXR154 LIA6TPNXR228 LIA6TPNXR128 LIA6TPNXR232 LIA6TPNXR132

Static

2-T5HO1-T5HO2-T51-T52-T81-T8

54W54W28W28W32W32W

LIS6GPNXR254 LIS6GPNXR154 LIS6GPNXR228 LIS6GPNXR128 LIS6GPNXR232 LIS6GPNXR132

LIS6TPNXR254 LIS6TPNXR154 LIS6TPNXR228 LIS6TPNXR128 LIS6TPNXR232 LIS6TPNXR132

* For any additional ceiling systems not shown please consult factory.

Page 99: Linear recessed and surface lighting

4.96 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Lytecel6individualT56"x48"Recessed parabolic luminaires

Featuresalowbrightness20cellparaboliclouverthathasanopeningthatisonly4¼"wide.The precise contours provide photometrics that meet the IES requirements for lighting VDTareas.Itfitsmoststandard6"X48"lay-inceilingsystemsplusArmstrongTechZone® ceiling systems.

Features•Semi-specularorspecular,lowiridescence,pre-anodized

aluminum louver.•Verticalgrainoncrossbladeseliminatesreflected

lamp image.•Springloadedlatches(selfcentering).•Louverhasprotectivedustguard.•Only5-1/2"deepbody.•Blackhousingexteriorforcoolerballastoperating

temperature.•UL-Listedtwinknockoutaccessplate.•Canbemountedincontinuousrows.•2hold-downclipsstandard.•CompatiblewithArmstrongTechZone® ceiling systems.•MeetsNYCCoderequirements.•OptionalDALIballastacceptsdigitaldimming

commands from computers, scene controllers and automatic control devices.

Options & accessories page 4.130Louver: LI is available in either specular (P)or semi-specular (L)louvers. (e.g. LIS6G20PW228 or LISG20LW228)

Ballast type <10THD <20THD

ElectronicPST5(1or2Lamp) PG – (28Wor54W)

Drywall kit: For individual mounts only: FK906X4.Access plate: Top wiring access plate is shipped with fixture as standard. When access plates are required in advance for wiring convenience, specify separately. Order Catalog no.: ACP5 CSP.Electrical/wiring options: Consult factory.EM Pack or dimming ballast: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

30˚

60˚500

1000

1500

Candlepower CurveLIS6G20PW154UNVPG

Standard T-Grid ceiling

Slot Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

Standard T-Grid ceiling

Slot Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

1 Lamp T5 specular louver reference data

Efficiency 58.2% Spacing ratio 1.6

Electronic ballast

Inputwatts(120V) 59.0W Ballastfactor 1.0

30˚

60˚550

1100

1650

Candlepower Curve2 Lamp T5 specular louver reference data

Efficiency 55.3% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 66.0W Ballastfactor 1.0

Ordering informationType Lamp qty –type Lamp watts Standard grid ceiling = G Slot grid ceiling = T Tegular 9/16" ceiling = D Tegular 15/16" ceiling = A

Static

1-T52-T51-T52-T5

28W28W54W54W

LIS6G20PW128UNVPG LIS6G20PW228UNVPG LIS6G20PW154UNVPG LIS6G20PW254UNVPG

LIS6T20PW128UNVPG LIS6T20PW228UNVPG LIS6T20PW154UNVPG LIS6T20PW254UNVPG

LIS6D20PW128UNVPG LIS6D20PW228UNVPG LIS6D20PW154UNVPG LIS6D20PW254UNVPG

LIS6A20PW128UNVPG LIS6A20PW228UNVPG LIS6A20PW154UNVPG LIS6A20PW254UNVPG

Air handling

1-T52-T51-T52-T5

28W28W54W54W

LIA6G20PW128UNVPG LIA6G20PW228UNVPG LIA6G20PW154UNVPG LIA6G20PW254UNVPG

LIA6T20PW128UNVPG LIA6T20PW228UNVPG LIA6T20PW154UNVPG LIA6T20PW254UNVPG

LIA6D20PW128UNVPG LIA6D20PW228UNVPG LIA6D20PW154UNVPG LIA6D20PW254UNVPG

LIA6A20PW128UNVPG LIA6A20PW228UNVPG LIA6A20PW154UNVPG LIA6A20PW254UNVPG

Lytecel 6 Voltage Ballast Options 6"x48"Recessedparabolic 120=120V Seepage4.96 See page 4.96 277=277V andpage4.130 UNV=120-277V (ElectT5)

UNVLIS6G20PW154 PGExample

LIS6G20PW228UNVPG

Page 100: Linear recessed and surface lighting

4.97Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•Semi-specularorspecular,lowiridescence,pre-anodized

aluminum louver.•Verticalgrainoncrossbladeseliminatesreflected

lamp image.•Springloadedlatches(selfcentering).•Louverhasprotectivedustguard.•Only5-1/2"deepbody.•Blackhousingexteriorforcoolerballastoperating

temperature.•UL-Listedtwinknockoutaccessplate.•Canbemountedincontinuousrows.•2hold-downclipsstandard.•CompatiblewithArmstrongTechZone® ceiling systems.•MeetsNYCCoderequirements.•OptionalDALIballastacceptsdigitaldimming

commands from computers, scene controllers and automatic control devices.

Options & accessories page 4.130Louver: LI is available in either specular (P)or semi-specular (L)louvers. (e.g. LIS6G20PW228 or LISG20LW228)

Ballast type <10THD <20THD

Elec.IST832W(1or2Lamp) HI SOElec.PST832W(1or2Lamp) P2 –

Drywall kit: For individual mounts only: FK906X4.Access plate: Top wiring access plate is shipped with fixture as standard. When access plates are required in advance for wiring convenience, specify separately. Order Catalog no.: ACP5 CSP.Electrical/wiring options: Consult factory.EM Pack or dimming ballast: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

Lytecel6individualT86"x48"Recessed parabolic luminaires

Featuresalowbrightness20cellparaboliclouverthathasanopeningthatisonly4¼"wide. The precise contours provide photometrics that meet the IES requirements for lightingVDTareas.Itfitsmoststandard6"X48"lay-inceilingsystemsplusArmstrongTechZone® ceiling systems.

30˚

60˚250

500

750

Candlepower CurveLIS6G20PW132UNVHI

Standard T-Grid ceiling

Slot Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

Standard T-Grid ceiling

Slot Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

1 Lamp T8 specular louver reference data

Efficiency 57.6% Spacing ratio 1.7

Electronic ballast

Inputwatts(120V) 39.0W Ballastfactor 1.1

30˚

60˚500

1000

1500

Candlepower Curve2 Lamp T8 specular louver reference data

Efficiency 51.6% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 78.0W Ballastfactor 1.1

Ordering informationType Lamp qty –type Lamp watts Standard grid ceiling = G Slot grid ceiling = T Tegular 9/16" ceiling = D Tegular 15/16" ceiling = A

Static 1-T82-T8 32W LIS6G20PW132UNVHI

LIS6G20PW232UNVHILIS6T20PW132UNVHI LIS6T20PW232UNVHI

LIS6D20PW132UNVHI LIS6D20PW232UNVHI

LIS6A20PW132UNVHI LIS6A20PW232UNVHI

Air handling 1-T82-T8 32W LIA6G20PW132UNVHI

LIA6G20PW232UNVHILIA6T20PW132UNVHI LIA6T20PW232UNVHI

LIA6D20PW132UNVHI LIA6D20PW232UNVHI

LIA6A20PW132UNVHI LIA6A20PW232UNVHI

Lytecel 6 Voltage Ballast Options 6"x48"Recessedparabolic 120=120V Seepage4.97 See page 4.97 277=277V andpage4.130 UNV=120-277V (ElectT8)

UNVLIS6G20PW132 HIExample

LIS6G20PW232UNVHI

Page 101: Linear recessed and surface lighting

4.98 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Lytecel6continuousT56"x48"Recessed parabolic luminaires

Featuresalowbrightness20cellparaboliclouverthathasanopeningthatisonly4¼"wideandalengthof48".Whenmountedincontinuousrowsitcreatesanuninterruptedcontinuouslouverappearance.Itwillfitmost6"widelay-inorslotgridceilingsystemsandhas unique aligning and clamping hardware that creates the proper fit of the fixture into the ceiling system.

Features•48"longlouvergivesanuninterruptedlouver

appearance when row mounted. Ideal for continuous row applications.

•Semi-specularorspecular,lowiridescence,pre-anodized aluminum louver.

•Verticalgrainoncrossbladeseliminatesreflectedlamp image.

•Springloadedlatches(selfcentering).•Louverhasprotectivedustguard.•Only5-1/2"deepbody.•Blackhousingexteriorforcoolerballastoperating

temperature.•UL-Listedtwinknockoutaccessplate.•Canbemountedincontinuousrows.•2hold-downclipsstandard.•MeetsNYCCoderequirements.•OptionalDALIballastacceptsdigitaldimming

commands from computers, scene controllers and automatic control devices.

Options & accessories page 4.130Louver: LC is available in either specular (P)or semi-specular (L)louvers. (e.g. LCS6G20PW228 or LCS6G20LW228)

Ballast type <10THD <20THD

Elec.IST528W(1or2Lamp) PI SOElec. PS T5 28W or 54W PG – (1or2Lamp)ElecIST832W(1or2Lamp) HI –

Access plate: Top wiring access plate is shipped with fixture as standard. When access plates are required in advance for wiring convenience, specify separately. Order Catalog no.: ACP5 CSP.Electrical/wiring options: Consult factory.EM Pack or dimming ballast: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

30˚

60˚500

1000

1500

Candlepower CurveLCS6G20PW154UNVPG

Standard T-Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

Slot Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

Standard T-Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

Slot Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

1 Lamp T5 specular louver reference data

Efficiency 58.2% Spacing ratio 1.6

Electronic ballast

Inputwatts(120V) 59.0W Ballastfactor 1.0

30˚

60˚550

1100

1650

Candlepower Curve2 Lamp T5 specular louver reference data

Efficiency 55.3% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 66.0W Ballastfactor 1.0

Lytecel 6 Voltage Ballast Options 6"x48"Recessedparabolic 120=120V Seepage4.98 See page 4.98 277=277V andpage4.130 UNV=120-277V (ElectT5orT8)

UNVLCS6G20PW154 PGExample

Ordering informationType Lamp qty –type Lamp watts Standard grid ceiling = G Slot grid ceiling = T

Static

1-T52-T51-T52-T5

28W28W54W54W

LCS6G20PW128UNVPG LCS6G20PW228UNVPG LCS6G20PW154UNVPG LCS6G20PW254UNVPG

LCS6T20PW128UNVPG LCS6T20PW228UNVPG LCS6T20PW154UNVPG LCS6T20PW254UNVPG

Air handling

1-T52-T51-T52-T5

28W28W54W54W

LCA6G20PW128UNVPG LCA6G20PW228UNVPG LCA6G20PW154UNVPG LCA6G20PW254UNVPG

LCA6T20PW128UNVPG LCA6T20PW228UNVPG LCA6T20PW154UNVPG LCA6T20PW254UNVPG

End trim required for beginning and end of row.Order catalog no.: LC6 End trim

Continuous row coupler locks fixtures together for a continuous line of light without cell configuration interruption,supplied with fixture.(For end of row order LC85 CLAMP)

LCS6G20PW228UNVPG

Page 102: Linear recessed and surface lighting

4.99Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•48"longlouvergivesanuninterruptedlouver

appearance when row mounted. Ideal for continuous row applications.

•Semi-specularorspecular,lowiridescence,pre-anodized aluminum louver.

•Verticalgrainoncrossbladeseliminatesreflectedlamp image.

•Springloadedlatches(selfcentering).•Louverhasprotectivedustguard.•Only5-1/2"deepbody.•Blackhousingexteriorforcoolerballastoperating

temperature.•UL-Listedtwinknockoutaccessplate.•Canbemountedincontinuousrows.•2hold-downclipsstandard.•MeetsNYCCoderequirements.•OptionalDALIballastacceptsdigitaldimming

commands from computers, scene controllers and automatic control devices.

Options & accessories page 4.130Louver: LC is available in either specular (P)or semi-specular (L)louvers. (e.g. LCS6G20PW232 or LCS6G20LW232)

Ballast type <10THD <20THD

Elec.IST832W(1or2Lamp) HI SOElec.PST832W(1or2Lamp) P2 –

Access plate: Top wiring access plate is shipped with fixture as standard. When access plates are required in advance for wiring convenience, specify separately. Order catalog no.: ACP5 CSP.Electrical/wiring options: Consult factory.EM Pack or dimming ballast: Consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

Lytecel6continuousT86"x48"Recessed parabolic luminaires

Featuresalowbrightness20cellparaboliclouverthathasanopeningthatisonly4¼"wideandalengthof48".Whenmountedincontinuousrowsitcreatesanuninterruptedcontinuouslouverappearance.Itwillfitmost6"widelay-inorslotgridceilingsystemsandhas unique aligning and clamping hardware that creates the proper fit of the fixture into the ceiling system.

30˚

60˚250

500

750

Candlepower CurveLCS6G20PW132UNVHI

Standard T-Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

Slot Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

Standard T-Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

Slot Grid ceiling

5 ½" (139mm)

4 ¼"(108mm)

6" (152mm)

1 Lamp T8 specular louver reference data

Efficiency 57.6% Spacing ratio 1.7

Electronic ballast

Inputwatts(120V) 39.0W Ballastfactor 1.1

30˚

60˚500

1000

1500

Candlepower Curve2 Lamp T8 specular louver reference data

Efficiency 51.6% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 78.0W Ballastfactor 1.1

Lytecel 6 Voltage Ballast Options 6"x48"Recessedparabolic 120=120V Seepage4.99 See page 4.99 277=277V andpage4.130 UNV=120-277V (ElectT8)

UNVLCS6G20PW132 HIExample

Ordering informationType Lamp qty –type Lamp watts Standard grid ceiling = G Slot grid ceiling = T

Static 1-T82-T8 32W LCS6G20PW132UNVHI

LCS6G20PW232UNVHILCS6T20PW132UNVHI LCS6T20PW232UNVHI

Air handling 1-T82-T8 32W LCA6G20PW132UNVHI

LCA6G20PW232UNVHILCA6T20PW132UNVHI LCA6T20PW232UNVHI

End trim required for beginning and end of row.Order catalog no.: LC6 ENd trim

Continuous row coupler locks fixtures together for a continuous line of light without cell configuration interruption,supplied with fixture.(For end of row order LC85 CLAMP)

LCS6G20PW232UNVHI

Page 103: Linear recessed and surface lighting

4.100 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

CTS3 2', 4' & 8'1 lamp recessed luminaires

FeaturesHousing: 20 gauge pre-painted steel.

Bulkhead: 18 gauge galvanized steel

Reflector: Semi-specular aluminum.

Trim:Flangehasanaluminumextrudedwidthof3/4".Flangeless and grid mount has no trim visible. Grid mount fixture drops into grid system by others.

Lamping: T5 or T5 HO fluorescent.

Lens: Extruded frosted acrylic.

Louver:ExtrudedSemispecularparabolic,2"nominalblade spacing.

Electronic ballast: Extruded Programmed start, 3 conductors, 12 gauge wire. Color-coded quick connectors allow easy connection for modular fixture.

Emergency battery pack: 450 Lumens @ 90 minimum.

Labels included:UL,cUL,andIBEW

Ordering instructionsContinuous rows:

1. Determine run length. 2. Order starter fixture. . 3. Order one telescoping fixture*. 4. Order remainder of joiner fixtures.

Individual Fixtures:

1.OrdernumberofINDIVIDUALUNITSrequired

* For best one lamp effect, use telescoping f ixture at longest length possible.

30˚

60˚300

600

900

Candlepower Curve

30˚

60˚300

600

900

Candlepower Curve

Flush Lens3 ¾"

(95mm)

5 ¼"(133mm)

3" (76mm)

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

Flange

Flange

Flange

Grid Mount

Grid Mount

Grid Mount

Distribution

Zone Lumens %Lamp %Luminaire0-90 1854 37.8 100.0 90-180 0 0.0 0 0-180 1854 37.8 100.0

Distribution

Zone Lumens %Lamp %Luminaire0-90 1815 37.1 100.0 90-180 0 0.0 0 0-180 1815 37.1 100.0

Family Mounting Shielding Configuration Output Length (nom.) Housing Voltage OptionsCT3=CTS3 F=Flange

L=FlangelessG=GridMount

L=FlushLensR=RecessedLensP=ParabolicLouver

A=1Lamp 1 H=HighOutputS =Standard

2=2Foot4=4Foot8=8Foot

U=Indiv.UnitS=Starter 2 J=JoinerT=Telescoping 3

1=120V2=277V

4 =4throughwires5 =5throughwiresT=TandemSwitchE=EmergencyPack 4

1Lampismounteddiagonallyandextendsintoadjacentf ixtureby21/2"instarter,joinerandtelescopingf ixtures2 Starter available as 4' and 8' only3Telescopingf ixtureships853/8",adjustabledownto493/8"4 EM pack not available in 2' or telescoping f ixtures

CT3 A

Regressed Lens

30˚

60˚300

600

900

Candlepower Curve

Distribution

Zone Lumens %Lamp %Luminaire0-90 1880 38.4 100.0 90-180 0 0.0 0 0-180 1880 38.4 100.0

Parabolic Louver

Ordering information

CTS3-1

CTS3-3

CTS3-5

CTS3-13

CTS3-15

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

CTS3-7

CTS3-9

CTS3-11

3 ¾" (95mm)

5 ⅛"(130mm)

3" (76mm)

3 ¾" (95mm)

5 ⅛"(130mm)

3" (76mm)

3 ¾" (95mm)

5 ⅛"(130mm)

3" (76mm)

Flangeless

Flangeless

Flangeless

CTS3-17

Page 104: Linear recessed and surface lighting

4.101Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

Flange

Flange

Flange

Grid Mount

Grid Mount

Grid Mount

CTS3 2', 4' & 8'2 lamp recessed luminaires

FeaturesHousing: 20 gauge pre-painted steel.

Bulkhead: 18 gauge galvanized steel

Reflector: Semi-specular aluminum.

Trim:Flangehasanaluminumextrudedwidthof3/4".Flangeless and grid mount has no trim visible. Grid mount fixture drops into grid system by others.

Lamping: T5 or T5 HO fluorescent.

Lens: Extruded frosted acrylic.

Louver:ExtrudedSemispecularparabolic,2"nominalblade spacing.

Electronic ballast: Extruded programmed start, 3 conductors, 12 gauge wire. Color-coded quick connectors allow easy connection for modular fixture.

Emergency battery pack: 450 Lumens @ 90 minimum.

Labels included:UL,cUL,andIBEW

Ordering instructionsContinuous rows:

1. Determine run length. 2. Order starter fixture. . 3. Order one telescoping fixture*. 4. Order remainder of joiner fixtures.

Individual fixtures:

1.OrdernumberofINDIVIDUALUNITSrequired

* For best one lamp effect, use telescoping f ixture at longest length possible.

30˚

60˚300

600

900

Candlepower CurveFlush Lens

Distribution

Zone Lumens %Lamp %Luminaire0-90 3429 35.0 100.0 90-180 0 0.0 0 0-180 3429 35.0 100.0

Family Mounting Shielding Configuration Output Length (nom.) Housing Voltage OptionsCT3=CTS3 F=Flange

L=FlangelessG=GridMount

L=FlushLensR=RecessedLensP=ParabolicLouver

C=2Lamp 1 H=HighOutputS =Standard

2=2Foot4=4Foot8=8Foot

U=Indiv.UnitS=Starter 2 J=JoinerT=Telescoping 3

1=120V2=277V

4 =4throughwires5 =5throughwiresT=TandemSwitchE=EmergencyPack 4

1Lampismounteddiagonallyandextendsintoadjacentf ixtureby21/2"instarter,joinerandtelescopingf ixtures2 Starter available as 4' and 8' only3Telescopingf ixtureships853/8",adjustabledownto493/8"4 EM pack not available in 2' or telescoping f ixtures

CT3 C

Ordering information

30˚

60˚500

1000

1500

Candlepower CurveRegressed Lens

Distribution

Zone Lumens %Lamp %Luminaire0-90 3158 32.2 100.0 90-180 0 0.0 0 0-180 3158 32.2 100.0

30˚

60˚650

1300

1950

Candlepower CurveParabolic Louver

Distribution

Zone Lumens %Lamp %Luminaire0-90 3483 35.5 100.0 90-180 0 0.0 0 0-180 3483 35.5 100.0

CTS3-2

CTS3-4

CTS3-6

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

3 ¾" (95mm)

5 ¼"(133mm)

3" (76mm)

CTS3-8

CTS3-10

CTS3-12

3 ¾" (95mm)

5 ⅛"(130mm)

3" (76mm)

3 ¾" (95mm)

5 ⅛"(130mm)

3" (76mm)

3 ¾" (95mm)

5 ⅛"(130mm)

3" (76mm)

Flangeless

Flangeless

Flangeless

CTS3-18

CTS3-14

CTS3-16

Page 105: Linear recessed and surface lighting

4.102 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

PTS7 2', 3', 4', 5' & 7'Perimeter trough system

FeaturesHousing: Die-formed steel. Integral f langes at each end strengthen the housing and permit housings to be bolted together in continuous runs and facilitate suspension of f ixture. Concealed openings for heat extraction.

Lamping: One or two T8 fluorescent lamps, as specif ied. Provided by others.

Reflector: Die-formed semi-specular aluminum.

Louver: Semi-specular anodized aluminum, 40 degrees lengthwise by 30 degrees minimum crosswise shielding. Supported along both edges by concealed frame of extruded aluminum.

Socket Channels: Die-formed, prepainted steel held bysupportbracketsandallowsforupto6"lampoverlap.

Ceiling Trim: Extruded aluminum with integral aligner splines.

Electrical: Specify 120 volt or 277 volt. 3 conductor, 12 gauge wire. Color-coded quick connectors allow ease of connection for joiner modules. For special circuiting, consult factory. Rapid start, HPF, class “P” thermally protected.

Emergency battery pack: 450 Lumens @ 90 minimum.4'f ixtureandlongeronly.Notavailableintelescoping fixtures.

Mountings: Wall adjustment bracket - allows for inconsistencies in wall straightness. Die-formed steel used to mount system to the wall.

Finish: Ceiling trim painted baked enamel semi-gloss white.

Options and Accessories90 degree inside, 90 degree outside, 135 degree inside, and 135 outside corners available.

Labels

UL,cULandI.B.E.W.

PTS7-1 1LightT8,paraboliclouver,81/4"aperture

11 ¼"(286mm)

8 ¼"(210mm)

7 1�16"(179mm)

300

600

900

Candlepower Curve

30˚

60˚

Family Style Lamps Length Ballast OptionsPTS7=PTS7 T=Telescoping *

Blank=Non-telescoping1=1Lamp 24 =24"

36 =36"48 =48" *60 =60"84 =84"

E81=ELET8120VE82=ELET8277V

X4=4throughwiresX5=5throughwiresX6=6throughwiresT=Tandemswitch

PTS7 1

Ordering information

* PTS7-1 lamp telescoping available in48"withadjustmentof27"to48".

End plate and corner block accessories

135° InsidePTS7C1351 Standard

135° OutsidePTS7C1350 Standard

End cap setPTS7EP Standard

90° InsidePTS7C901 Standard

90° OutsidePTS7C900 Standard

Each run must be closed up by one End cap set

Distribution

Zone Lumens %Lamp %Luminaire0-90 2644 45.6 100.0 90-180 0 0.0 0.0 0-180 2644 45.6 100.0

Reference data

Report no: LRL 499-5D Eff iciency: 46.7% Lamps: 1-FO32T8

90 Inside

14''(356mm)

90 Outside

1 ½''(38mm)

135 Inside

8 ½''(213mm)

4 ¾"(12mm)

Page 106: Linear recessed and surface lighting

4.103Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

30˚

60˚500

1000

1500

Candlepower Curve

PTS7-2 2LightT8,paraboliclouver,81/4"aperture

11 ¼"(286mm)

8 ¼"(210mm)

7 1�16"(179mm)

Family Style Lamps Length Ballast OptionsPTS7=PTS7 T=Telescoping *

Blank=Non-telescoping2=2Lamp 24 =24" 60 =60"

36 =36" 96 =96"48 =48" 54 =54" *42 =42" *

E81=ELET8120VE82=ELET8277V

X4=4throughwiresX5=5throughwiresX6=6throughwiresT=Tandemswitch

PTS7 2

Ordering information

*PTS7-2lamptelescopingavailablein42"withadjustment of27"to42".Alsoavailablein54"withadjustmentof39"to54".

PTS72',3',3½',4½',5'&8'Perimeter trough system

Sample run accessories

Example of a 21' 10 ¾" run of 1 light 277v PTS7

Lightedtelescoping

unit

Example of a 1 light pattern using IS and OS corners

Telescoping unit (3 places)

90º Inside corner

90º Outside corner1 ½"

(4cm)

1 ½"(4cm)

21' 10 ¾"(667cm)

10' 2 ¼"(311cm)

9' 0"(274cm)

14"(36cm)

14"(36cm)

8' ½"(245cm)

8' ½"(245cm)

48"(122cm)

48"(122cm)

60"(152cm)

84"(213cm)

84"(213cm)

60"(152cm)

Example of a 21' 10 ¾" run of 2 light 277v PTS7

Lightedtelescoping

unit

Example of a 2 light pattern using IS and OS corners

Telescopingunit (3 places)

90º Inside corner

90º Outside corner1 ½"

(4cm)

1 ½"(4cm)

21' 10 ¾"(667cm)

9' 2 ¼"(280cm)

8' 0"(244cm)

14"(36cm)

14"(36cm)

8' ½"(245cm)

8' ½"(245cm)

48"(122cm)

48"(122cm)

48"(122cm)

96"(244cm)

36"(91cm)

48"(122cm)

24"(61cm)

Example of a 21' 10 ¾" run of 1 light 277v PTS7

Lightedtelescoping

unit

Example of a 1 light pattern using IS and OS corners

Telescoping unit (3 places)

90º Inside corner

90º Outside corner1 ½"

(4cm)

1 ½"(4cm)

21' 10 ¾"(667cm)

10' 2 ¼"(311cm)

9' 0"(274cm)

14"(36cm)

14"(36cm)

8' ½"(245cm)

8' ½"(245cm)

48"(122cm)

48"(122cm)

60"(152cm)

84"(213cm)

84"(213cm)

60"(152cm)

Example of a 21' 10 ¾" run of 2 light 277v PTS7

Lightedtelescoping

unit

Example of a 2 light pattern using IS and OS corners

Telescopingunit (3 places)

90º Inside corner

90º Outside corner1 ½"

(4cm)

1 ½"(4cm)

21' 10 ¾"(667cm)

9' 2 ¼"(280cm)

8' 0"(244cm)

14"(36cm)

14"(36cm)

8' ½"(245cm)

8' ½"(245cm)

48"(122cm)

48"(122cm)

48"(122cm)

96"(244cm)

36"(91cm)

48"(122cm)

24"(61cm)

Qty Catalog number

1 PTS7T148E82 2 PTS7184E82 1 PTS7160E82 1 PTS7EP

TopQty Catalog number

1 PTS7C901 IS Corner 1 PTS7T148E82 Tele 1 PTS7160E82 Fixture

TopQty Catalog number

1 PTS7C901 IS Corner 1 PTS7T254E82 Tele 1 PTS7248E82 Fixture

SideQty Catalog number

1 PTS7T148E82 Tele 1 PTS7148E82 Fixture 1 PTS7C900 OS Corner

SideQty Catalog number

1 PTS7T254E82 Tele 1 PTS7248E82 Fixture 1 PTS7C900 OS Corner

BottomQty Catalog number

1 PTS7T148E82 Tele 1 PTS7148E82 Fixture 1 PTS7EP End set

BottomQty Catalog number

1 PTS7T254E82 Tele 1 PTS7248E82 Fixture 1 PTS7EP End set

Qty Catalog number

1 PTS7T254E82 1 PTS7296E82 1 PTS7248E82 1 PTS7236E82 1 PTS7224E82 1 PTS7EP

Distribution

Zone Lumens %Lamp %Luminaire0-90 2644 45.6 100.0 90-180 0 0.0 0.0 0-180 2644 45.6 100.0

Reference data

Report no: LRL 499-5E Lamps: 2-32WT8 Lumens: 2900 Eff iciency: 45.6%

Page 107: Linear recessed and surface lighting

4.104 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Family Lamps Type Shielding Voltage Length OptionsPTS5=PTS5 2=2Lamp S=Standard

H=HOO=OpenS= Straight

blade louver

L=Lens

1=120V2=277V3=347VD1=Dimming120VD2=Dimming277VD3=Dimming347VE1=Emergency120VE2=Emergency277V

2 =2'3 =3'4 =4' 6 =6'8 =8'

Blank=NooptionsA =AdjustableAS= Adjustable

StaggeredS =StaggeredX4=4throughwiresX5=5throughwiresA4= Ajustable 4

through wiresA5= Ajustable 5

through wiresS5= Staggered 4

through wiresS5= Staggered 5

through wiresB4= Adjustable

Staggered 4 through wires

B5= Adjustable Staggered 5 through wires

9 ⅜"(238mm)

7"(178mm)

5 ½"(140mm)

FeaturesHousing: Die formed 20 gauge pre-painted steel. Integral heavy gauge bulk-heads support housing and trim, permitting modules to be bolted together in continuous runs and to facilitate suspension.

Lamping: Cross sectional one or two linear T5 fluorescent lamps. Provided by others.

Reflector: Precision parabolic roll-formed semi-specular aluminum or precision die-formed CRS finished in a high reflective baked white powder coat.

Louver: Lift and shift straight blade louver constructed from die-formed aluminum and painted to match housing.Louverbladesare1"highon11/8"centers(optional).

Mounting: “J” Rail is f irst mounted to the wall and the modulesconnecttotherailfor1/4"walladjustment.Modules are hung from suspension wires attached to the fixture bulkheads and the structure above.

ElectricalElectronic ballast: Programmed start, 3 conductor, 12 gauge wire. Color-coded quick connectors allow easy connection for modular fixtures.

Dimming:AdvanceMarkX,useAdvancecompatibletwo-wirecontrol(noextraleadrequired).

Emergency battery pack: 450 Lumens @ 90 minimum.4'f ixtureandlongeronly.Notavailable in adjustable fixtures.

PTS5 T5 lamps 2', 3', 4', 6' & 8'Architectural profiles

PTS5-1 1 Light T5, high eff iciency reflector

PTS5-2 2 Light T5, high eff iciency reflector

Reference data

Report no: ITL53559 Lumens: 5000

Cat no: PTS51HS14 Eff iciency: 37.2%

Lamps: 1-F54T5

Distribution

Zone Lumens %Lamp %Luminaire0-90 3026 30.3 100.0

90-180 0.0 0.0 0.0

0-180 3026 30.3 100.0

Distribution

Zone Lumens %Lamp %Luminaire0-90 1861 37.2 100.0

90-180 0.0 0.0 0.0

0-180 1861 37.2 100.0

Reference data

Report no: ITL53560 Lumens: 5000

Cat no: PTS52HS14 Eff iciency: 30.3%

Lamps: 2-F54T5

30˚

60˚900

1800

2700

Candlepower Curve

Family Lamps Type Shielding Voltage Length OptionsPTS5=PTS5 1=1Lamp S=Standard

H=HOO=OpenS= Straight

blade louver

L=Lens

1=120V2=277V3=347VD1=Dimming120VD2=Dimming277VD3=Dimming347VE1=Emergency120VE2=Emergency277V

2 =2'3 =3'4 =4' 6 =6'8 =8'

Blank=NooptionsA =AdjustableX4=4throughwiresX5=5throughwiresA4= Ajustable 4

through wiresA5= Ajustable 5

through wires

PTS5

PTS5

1

2

Module ordering information

Module ordering information30˚

60˚1000

2000

3000

Candlepower Curve

Sample Run

6' (183cm)

4' (122cm)

Three-Foot A¹ 8' (244cm)

3’ - 10 ¾"(119cm)

21'-10 ¾" (667cm)Fixture used at

For fixture using non-staggered lampsThefour-footadjustablefixturehasarangeof48.75”(123.83cm)-60”(152.40cm).Thethree-footadjustablefixturehasarangeof36.75”(93.35cm)-48”(121.92cm).Thetwo-footadjustablefixturehasarangeof24.75”(62.87cm)-36”(91.44cm).

For fixture using staggered lampsThefour-footadjustablestaggeredfixturehasarangeof51”(129.54cm)-60”(152.40cm).Thethree-footadjustablestaggeredfixturehasarangeof39”(99.06cm)-48”(121.92cm).Thetwo-footadjustablestaggeredfixturehasarangeof27”(68.58cm)-36”(91.44cm).

Three-Foot A¹ 6' (183cm)

Three-Foot A¹

Three-Foot A¹

4' (122cm)

1¾"(4cm)

1¾"(4cm)

9'-3¼" (283cm)

7'-10½"(240cm)

1' (30cm)Fixture used at

3'-3¼" (100cm)

Fixture used at3'-10½"(118cm)

Fixture used at3'-10½"(118cm)

3' (91cm)

7'-10½"(240cm)

9 ⅜"(238mm)

7"(178mm)

5 ½"(140mm)

Page 108: Linear recessed and surface lighting

4.105Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Family Lamps Shielding Voltage Length OptionsPTS8=PTS8 1=1Light O=Open

S= Straight blade louver

L=Lens

1=120V2=277V3=347VD1=Dimming120VD2=Dimming277VD3=Dimming347VE1=Emergency120VE2=Emergency277V

2 =2'3 =3'4 =4' 6 =6'8 =8'

Blank=NooptionsA =AdjustableX4=4throughwiresX5=5throughwiresA4= Ajustable 4 through wiresA5= Ajustable 5 through wires

Family Lamps Shielding Voltage Length OptionsPTS8=PTS8 2=2Light O=Open

S= Straight blade louver

L=Lens

1=120V2=277V3=347VD1=Dimming120VD2=Dimming277VD3=Dimming347VE1=Emergency120VE2=Emergency277V

2 =2'3 =3'4 =4' 6 =6'8 =8'

Blank=NooptionsA =AdjustableAS= Adjustable staggeredS =StaggeredX4=4throughwiresX5=5throughwiresA4= Ajustable 4 through wiresA5= Ajustable 5 through wires

S4= Staggered 4 through wiresS5= Staggered 5 through wiresB4= Adjustable Staggered 4 through wiresB5= Ajustable Staggered 5 through wires

90° Inside corner:PTS135INCL=LensPTS135INCO=OpenPTS135INCS =Straightblade

90° Outside corner:PTS90OTCL=LensPTS90OTCO=OpenPTS90OTCS=Straightblade

135° Inside corner:PTS90INCL=LensPTS90INCO=OpenPTS90INCS=Straightblade

135° Outside corner:PTS135OTCL=LensPTS135OTCO=OpenPTS135OTCS=Straightblade

FeaturesHousing: Die formed 20 gauge pre-painted steel. Integral heavy gauge bulk-heads support housing and trim, permitting modules to be bolted together in continuous runs and to facilitate suspension.

Lamping: Cross sectional one or two linear T8 fluorescent lamps. Provided by others.

Reflector: Precision parabolic roll-formed semi-specular aluminum.

Louver: Lift and shift straight blade louver constructed from die-formed aluminum and painted to match housing.Louverbladesare1"highon11/8"centers(optional).

Mounting: “J” Rail is f irst mounted to the wall and the modulesconnecttotherailfor1/4"walladjustment.Modules are hung from suspension wires attached to the fixture bulkheads and the structure above.

ElectricalElectronic ballast: Programmed start, 3 conductor, 12 gauge wire. Color-coded quick connectors allow easy connection for modular fixtures.

Dimming:AdvanceMarkX,useAdvancecompatibletwo-wirecontrol(noextraleadrequired).

Emergency battery pack: 450 Lumens @ 90 minimum. 4' f ixture and longer only. Notavailableinadjustablefixtures.

Ordering instructions1. Order number of f ixtures necessary

to complete the run.2. Order one end set per run. Runs with staggered lamp

fixtures must end in adjustable staggered module.

Contact factory for details.Adjustable f ixtures in 2', 3' and 4's length only. Fixture will ship one foot longer than posted length. Staggered lamp fixtures willadjustdownto3"pastpostedlength.Non-staggeredlampfixtureswilladjustdownto1"pastpostedlength.Areaofadjustability is not lamped.

PTS8 T8 lamps 2', 3', 4', 6' & 8'Architectural profiles

PTS8-1 1 Light T8, high eff iciency reflector

PTS8-2 2 Light T8, high eff iciency reflector

Mounting accessories

Reference data

Report no: ITL53557 Lumens: 2900

Cat no: PTS81S14 Eff iciency: 39.4%

Lamps: 1-F32T8

Distribution

Zone Lumens %Lamp %Luminaire0-90 1162 39.4 100.0

90-180 0 0.0 0.0

0-180 1162 39.4 100.0

Reference data

Report no: ITL53558 Lumens: 2950

Cat no: PTS82S14 Eff iciency: 31.8%

Lamps: 2-F32T8

Distribution

Zone Lumens %Lamp %Luminaire0-90 1878 31.8 100.0

90-180 0 0.0 0.0

0-180 1878 31.8 100.0

PTS8

PTS8

1

2

Module ordering information

Module ordering information

30˚

60˚450

900

1350

Candlepower Curve9 ⅜"(238mm)

7"(178mm)

5 ½"(140mm)

30˚

60˚650

1300

1950

Candlepower Curve9 ⅜"

(238mm)

7"(178mm)

5 ½"(140mm)

12"(305mm) 1 ¾" (45mm) 6 ¼" (159mm) 2" (51mm)

End cap set:PTSEP

Page 109: Linear recessed and surface lighting

4.106 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

GO2Recessed high performance louver luminaires

GO2 features a high reflectance flat white louver, and aluminum reflector system that are entirely fabricated with recyclable materials, finished with emission free powder coating, and packaged in recycled corrugated containers. Add to that, it is made in the USA, saving fuel from the factory to the job site, and it makes GO2 an environmentally friendly product.

The sharp cut-off of a traditional parabolic f ixture casts dark shadows on the wall creating a cave effect.

The flat white louver makes the luminaire low in brightness yet gives a broad light distribution that evenly illuminates all surfaces in the space, which creates a comfortable balanced brightness for the occupants.

InadditionitcanprovideilluminationlevelsequaltotheIESNArequirements,withaVisualComfortProbability(VCP)thatexceeds70 at less than .6 watts per square foot.

Replacing a typical 3 lamp parabolic with GO2 can save as much as 44% on your energy bill. The GO2 will not only meet your lighting level requirements, but also your LEED goals.

Page 110: Linear recessed and surface lighting

4.107Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

GO2 2' x 4', 2' x 2' & 1' x 4'Recessed high performance louver luminaires

Features•GO2evenlyilluminateshorizontalandverticalsurfaces

and is low in brightness.•GO22X4canprovide51maintainedfootcandlesatonly

.58 watts per square foot.•85.9%efficienttwolamp32wattT82'x4'luminaire.•80.5%efficienttwolamp17wattT82'x2'luminaire.•80.7%efficientsinglelamp32wattT81'x4'luminaire.•94%reflectiveflatwhitepowdercoatedlouver.•94%reflectanceMiro® reflector system.•5"deepbody.•Onepiecehousing.•Blackexteriorforcoolerballastoperatingtemperature.•Built-inearthquakeclips.•Springloadedlatches.•18gaugesteelhinges.•ConstructiontomeetNYCCodeorChicagoPlenum

requirements is available.•ManufacturedinUSA

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandadd as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SOElectronic T5 PG –Electronic TT5 40W IB*, PR** SBBilevelstepdimT8 V2 –BilevelstepdimT514W/28W VY –Adv. Optainum low watt T8 C5 –Adv. Optainum stand. Watt T8 C2 –

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4. Conversion kit for 2' x 2' unit: FK92X2 . Conversion kit for 1' x 4' unit: FK91X4. For drywall or plaster ceilings.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚800

1600

2400

Candlepower CurveGOS2G232UNVC5

5"(127mm)

24" (610mm)

6" (152mm)

Air supply slots (GOA Only)

2" X 2-1/2" access plate with two K.O.s (7/8" dia.)

39-1/4" (997mm)

48" (1219mm)

Reference data

Efficiency 85.9% Spacing ratio 1.7

Electronic ballast

Inputwatts(120V) 51.0W Ballastfactor 0.78

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 4'

2-T52-T52-T5HO2-T82-T82-T8

28W28W54W32W32W32W

GOS2G228UNVPGGOS2G228UNVVYGOS2G254UNVPGGOS2G232UNVC5GOS2G232UNVHIGOS2G232UNVV2

GO2 Series Voltage Ballast Options Direct/indirect 120=120V Seepage4.107 See page 4.107 recessed static 277=277V andpage4.130 or air supply/return UNV=120-277V

UNVGOS2G232 C5Example

For air handling type fixture change S to A . (e.g.: GOA2G232UNVHI)

For slot grid ceiling change G to T. (e.g.: GOS2T232UNVH)

30˚

60˚350

700

1050

Candlepower CurveGOS2G217UNVC2

5"(127mm)

24" (610mm)

23-7/8" (606mm)

15-11/16" (398mm)

5" (127mm)

Air supply slots (GOA Only)

2" X 2-1/2" access plate with two K.O.s (7/8" dia.)

5"(127mm)

24" (610mm)

Reference data

Efficiency 80.5% Spacing ratio 1.7

Electronic ballast

Inputwatts(120V) 30.2W Ballastfactor 0.88

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 2' x 2'

2-T52-T5HO2-TT52-T82-T8U 1 ⅝"

14W24W40W17W32W

GOS2G214UNVPGGOS2G224UNVPGGOS2G2FTUNVPRGOS2G217UNVHIGOS2G22UUNVHI

GO2 Series Voltage Ballast Options Direct/indirect 120=120V Seepage4.107 See page 4.107 recessed static 277=277V andpage4.130 or air supply/return UNV=120-277V

UNVGOS2G217 C2Example

For air handling type fixture change S to A . (e.g.: GOA2G217UNVHI)

For slot grid ceiling change G to T. (e.g.: GOS2T217UNVHI)

30˚

60˚400

800

1200

Candlepower CurveGOS1G132UNVC2

5 ¾"(146mm)

12" (305mm)

11-1/2" (292mm)

48" (1219mm)

4-1/2" (114mm)2-3/4" (70mm)

Air supply slots (GOA Only)

Reference data

Efficiency 80.7% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 30.2W Ballastfactor 0.87

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Static 1' x 4'

2-T52-T51-T5HO2-T82-T8

28W28W54W32W32W

GOS1G228UNVPGGOS1G228UNVVYGOS1G154UNVPGGOS1G232UNVHIGOS1G232UNVV2

GO2 Series Voltage Ballast Options Direct/indirect 120=120V Seepage4.107 See page 4.107 recessed static 277=277V andpage4.130 or air supply/return UNV=120-277V

UNVGOS1G132 C2Example

For air handling type fixture change S to A . (e.g.: GOA1G232UNVHI)

For slot grid ceiling change G to T. (e.g.: GOS1T232UNVHI)

Page 111: Linear recessed and surface lighting

4.108 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

GO2 Retro 2' x 4' & 2' x 2'Retro fit recessed luminaires

GO2 Retro features a flat white louver and a unique power tray that can be used to convert most installations of 2' x 4' or 2' x 2' parabolic or specification grade lens troffers, that are at least43/8"deep,tostateoftheart,energysavingGREENFIXTURES.GO2Retroisover80% efficient with a broad light distribution that will illuminate both horizontal and vertical surfaces, creating a comfortable balanced brightness.

Features•GO2Retrocanbeusedtoconvertmost2'x4'

and 2' x 2' parabolic or specif ication grade lens troffers into energy saving luminaires.

•GO2Retroevenlyilluminateshorizontalandverticalsurfaces and is low in brightness.

•GO2Retroisidealforthoseareaswhereyouwouldliketo have a minimum of down time such as retail spaces and schools.

•ManufacturedinUSA

30˚

60˚650

1300

1950

Candlepower CurveGOR2G232UNVC5

Reference data

Efficiency 84.5% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 53.0W Ballastfactor 0.77

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Retro fit 2' x 4'2-T52-T5HO2-T8

28W54W32W

GOR2G228UNVPGGOR2G254UNVPGGOR2G232UNVHI

Available with EM Pack Consult factory

GO2 Retro Voltage Ballast Options Direct/indirect 120=120V Seepage4.108 See page 4.108 Retro fit recessed 277=277V andpage4.130 UNV=120-277V

UNVGOR2G232 AHIExample

30˚

60˚300

600

900

Candlepower CurveGOR2G217UNVC2

Reference data

Efficiency 80.6% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 30.8W Ballastfactor 0.88

Ordering informationType Size Lamp qty –type Lamp watts Catalog no.

Retro fit 2' x 2'2-T52-T5HO2-T8

14W24W17W

GOR2G214UNVPGGOR2G224UNVPGGOR2G217UNVHI

2x2NotAvailablewithEmergencyPack

GO2 Retro Voltage Ballast Options Direct/indirect 120=120V Seepage4.108 See page 4.108 Retro Fit Recessed 277=277V andpage4.130 UNV=120-277V

UNVGOR2G217 AHIExample

3"(76mm)

20 ⅞" (530mm) min.

¾" (19mm)

¾" (19mm) min.

22 ¾" (578mm) min.

46 ¼" (1175mm) 2 x 422 ¼" (565mm) 2 x 2

20 5�¹6" (516mm) min.

4 ⅜"(111mm)

Dimensions are clearance required in fixture for GO2 Retro to fit

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeand add as suffix, e.g. UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SOElectronic T5 PG –BilevelstepdimT8 V2 –BilevelstepdimT514W/28W VY –Adv. Optainum low watt T8 C5 –Adv. Optainum stand. Watt T8 C2 –

* Instant start.

** Program start.

GO2 Retro 2' x 4'

•12Cell95%reflectivef lat white powder coated louver.

•84.5%efficient32WT8.•1.5spacemountingratio.

GO2 Retro 2' x 2'

•6Cell95%reflectivef lat white powder coated louver.

•80.6%efficient17WT8.•1.5spacemountingratio.

Page 112: Linear recessed and surface lighting

4.109Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

GO2 easy installationRetro fit recessed luminaires

Retrofitting with GO2 Retro as opposed to installing new fixtures is ideal for those areas where you would like to have a minimum of down time such as retail spaces or schools.

Step 1

The first step in installation, after making sure power to fixture is disconnected, is to remove all existing components of the previous fixture, leaving only the body. Place the GO2 Retro end adaptors between the base of the f ixtureandtheT-Bar.Secure the GO2 Retro End Adaptors in place with the suppliedtechscrews(4).

Step 3

Lift GO2 Retro power tray into position. Slide GO2 Retro power tray into brackets on end adaptors.

Step 5

Insert the GO2 Retro louver pins into the louver slots of the GO2 Retro end adaptors and close.

Step 4

Slide the telescoping end of the GO2 Retro power tray into place, resting on the end adaptors. Tighten the integrated white thumb screws of the GO2 Retro power tray securing it in place.

The installation of the GO2 Retro is complete.

Step 2

Hang GO2 Retro power tray on tab and slot as shown above. Using the ballast disconnect supplied (accepts up to 12 gaugewire),makepowerconnections and ground connection to body.

Page 113: Linear recessed and surface lighting

4.110 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

VisionSmart2'x4'4" Parabolic louver recessed air handling luminaires

VisionSmart2'x4'ParabolicsmeetcriteriaofIESRP-1andRP-24.

Features•VRunitmeetsIESRP24andRP1recommended(basic)criteriaforlightingVDTareas.

•CandelasatNadir(0°),1510on2-lampVR.•Semi-specularlowiridescencepre-anodizedlouverinVRmodel.

•Concealedspring-loadedlatch/hingecanbeopened either side.

•Only6"deep.•Earthquakeclipsincluded.•Protectivefilmdustguard.•UL-Listedtwinknockoutaccessplate.•Metalgauge/constructiontomeetNYCCode

or Chicago Plenum is available.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start.

** Program start.

Consult factory for other wattages.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Air closure strips: ACS4(factoryinstalled).

ACS4 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Note: For concealed spline, plaster or drywall ceiling, use “G” type fixtures with either S2X4FKit(seeFolioOA-30-30),orDrywallkit, FK92X4(seeFolioOA30-10).

30˚

60˚800

1600

2400

Candlepower CurveVRA2G12LS232UNVHI

Reference data

Efficiency 70.9% Spacing ratio 1.8

Electronic ballast

Inputwatts(120V) 62.0W LER 60.4

Max average brightness

55° 1701cd/m2 65° 345cd/m2 75° 61cd/m2 85° 36cd/m2

6"(152mm)

24" (610mm)

Vision Smart Voltage Ballast Options 4"Precisioncontoured 120=120V Seepage4.110 See page 4.110 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8ballastonly)

UNVVRA2G12LS232 ACS4HIExample

Ordering information

Type Size Cells Lamp qty –Type Exposed T-Grid Exposed Slot-T or

concealed T-Grid

Air handling 2' x 4' 12 2-T8 VRA2G12LS232 VRA2T12LS232

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 114: Linear recessed and surface lighting

4.111Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

VisionSmart2'x4'4" Parabolic louver recessed air handling luminaires

VisionSmart2'x4'ParabolicsmeetthecriteriaofIESRP-1andRP-24.

Features•VRunitmeetsIESRP24andRP1recommended(basic)criteriaforlightingVDTareas.

•CandelasatNadir(0°),1510on2-lampVR.•Semi-specularlowiridescencepre-anodizedlouverinVRmodel.

•Concealedspring-loadedlatch/hingecanbeopened either side.

•Only6"deep.•Earthquakeclipsincluded.•Protectivefilmdustguard.•UL-Listedtwinknockoutaccessplate.•Metalgauge/constructiontomeetNYCCode

or Chicago Plenum is available.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Elec. T8 H3*, P3** O3*LOL T8 Dimming – PS

* Instant start.

** Program start.

Consult factory for other wattages.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Air closure strips: ACS4(factoryinstalled).

ACS4 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Note: For concealed spline, plaster or drywall ceiling, use “G” type fixtures with either S2X4FKit(seeFolioOA-30-30),orDrywallkit, FK92X4(seeFolioOA30-10).

30˚

60˚1000

2000

3000

Candlepower CurveVRA2G18LP332UNVH3

Reference data

Efficiency 64.5% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 85.0W LER 60.1

Max average brightness

55° 2681cd/m2 65° 304cd/m2 75° 147cd/m2 85° 0cd/m2

6"(152mm)

24" (610mm)

Vision Smart Voltage Ballast Options 4"Precisioncontoured 120=120V Seepage4.111 See page 4.111 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8ballastonly)

UNVVRA2G18LP332 ACS4H3Example

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Exposed Slot-T or

concealed T-Grid

Air handling 2' x 4' 18 3-T8 VRA2G18LP332 VRA2T18LP332

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 115: Linear recessed and surface lighting

4.112 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

VisionSmart2'x2'4" Parabolic louver recessed air handling luminaires

VisionSmartVRarchitecturallysymmetrical2'x2'ParabolicsmeetthecriteriaofIESRP-1and RP-24.

Features•CandelasatNadir(0°),1224on2-lampVR.•Semi-specularlowiridescencepre-anodizedlouverinVRmodels.

•Concealedspring-loadedlatch/hingecanbeopened either side.

•Only6"deep.•Louverframewithintegralpositivelightstop.•Earthquakeclipsincluded.•Protectivefilmdustguard.•UL-Listedtwinknockoutaccessplate.•Metalgauge/constructiontomeetNYCCode

or Chicago Plenum is available.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)

and type and add as suffix, e.g. UNVPR .

Ballast type <10THD <20THD

1 - 2 Lamp Elec. TT5 40W IB*, PR** SB*LOL TT5 Dimming – PB

* Instant start.

** Program start.

Consult factory for other wattages.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Air closure strips: ACS2(factoryinstalled).

ACS2 CSP(f ieldinstalled).Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

Note: For concealed spline, plaster or drywall ceiling, use “G” type fixtures with either S2X2FKit(seeFolioOA-30-30),orDrywallkit, FK92X2(seeFolioOA30-10).

30˚

60˚800

1600

2400

Candlepower Curve

30˚

60˚600

1200

1800

Candlepower Curve

VRA2G16LV2FT120SBReference data

Efficiency 52.2% Spacing ratio 1.8

Electronic ballast

Inputwatts(120V) 74.0W LER 39.9

Max average brightness

55° 1130cd/m2 65° 267cd/m2 75° 121cd/m2 85° 72cd/m2

6"(152mm)

24" (610mm)

Vision Smart Voltage Ballast Options 4"Precisioncontoured 120=120V Seepage4.112 See page 4.112 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8orTT5ballastonly)

120VRA2G16LV2FT ACS2SBExample

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Exposed Slot-T or

concealed T-Grid

Air handling 2' x 2' 16 2-TT5 VRA2G16LV2FT VRA2T16LV2FT

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 116: Linear recessed and surface lighting

4.113Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

VisionSmart2'x2'4" Parabolic louver recessed air handling luminaires

VisionSmartVRarchitecturallysymmetrical2'x2'ParabolicsmeetthecriteriaofIESRP-1and RP-24.

Features•VR9cellunitmeetsIESRP24andRP1recommended(basic)criteriaforlightingVDTareas.

•Semi-specularlowiridescencepre-anodizedlouverinVRmodels.

•Concealedspring-loadedlatch/hingecanbeopened either side.

•Only6"deep.•Louverframewithintegralpositivelightstop.•Earthquakeclipsincluded.•Protectivefilmdustguard.•UL-Listedtwinknockoutaccessplate.•Metalgauge/constructiontomeetNYCCode

or Chicago Plenum is available.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Elec. T8 H3*, P3** O3*LOL T8 Dimming – PS

* Instant start.

** Program start.

Consult factory for other wattages.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Air closure strips: ACS4(factoryinstalled).

ACS4 CSP(f ieldinstalled).Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

Note: For concealed spline, plaster or drywall ceiling, use “G” type fixtures with either S2X2FKIT(seeFolioOA-30-30),orDRYWALLKIT,FK92X2(seeFolioOA30-10).

30˚

60˚800

1600

2400

Candlepower Curve

30˚

60˚600

1200

1800

Candlepower CurveVRA2G9LP317UNVH3

Reference data

Efficiency 62.7% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 47.0W LER 50.4

Max average brightness

55° 2203cd/m2 65° 238cd/m2 75° 91cd/m2 85° 0cd/m2

6"(152mm)

24" (610mm)

Vision Smart Voltage Ballast Options 4"Precisioncontoured 120=120V Seepage4.113 See page 4.113 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8ballastonly)

UNVVRA2G9LP317 ACS2H3Example

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Exposed Slot-T or

concealed T-Grid

Air handling 2' x 2' 9 3-T8 VRA2G9LP317 VRA2T9LP317

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 117: Linear recessed and surface lighting

4.114 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

VisionSmart2'x2'4" Parabolic louver recessed air handling luminaires

VisionSmartarchitecturallysymmetrical2'x2'VRParabolicsmeetthecriteriaofIESRP-1andRP-24.TheVRSeriesisbestsuitedwhereveruseofVDT’sisoccasionalornonintensive.

Features•VRunitsmeetIESRP24andRP1recommended(basic)criteriaforlightingVDTareas.

•Only6"deep.•Semi-specularlowiridescencepre-anodizedlouverisstandardonVRmodels.

•Concealedspring-loadedlatch/hingecanbeopened either side.

•Louverframewithintegralpositivelightstop.•Earthquakeclipsincluded.•ProtectiveFilmdustguard.•UL-Listedtwinknockoutaccessplate.•Metalgauge/constructiontomeetNYCCode

or Chicago Plenum is available.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start.

** Program start.

Consult factory for other wattages.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Air closure strips: ACS2(factoryinstalled).

ACS2 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

Note: For concealed spline, plaster or drywall ceiling, use “G” type fixtures with either S2X2FKit(seeFolioOA-30-30),orDrywallkit, FK92X2(seeFolioOA30-10).

30˚

60˚550

1100

1650

Candlepower CurveVRA2G9LS26UUNVHI

Reference data

Efficiency 57.1% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 60.0W LER 50.0

Max average brightness

55° 3272cd/m2 65° 357cd/m2 75° 130cd/m2 85° 38cd/m2

6"(152mm)

24" (610mm)

Vision Smart Voltage Ballast Options 4"Precisioncontoured 120=120V Seepage4.114 See page 4.114 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elect.Ballastonly)

UNVVRA2G9LS26U ACS2HIExample

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Exposed Slot-T or

concealed T-Grid

Air handling 2' x 2' 9 2-T8U6 VRA2G9LS26U VRA2T9LS26U

30˚

60˚650

1300

1950

Candlepower CurveVRA2G16LS26UUNVHI

Reference data

Efficiency 51.7% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 60.0W LER 45.4

Max average brightness

55° 1619cd/m2 65° 293cd/m2 75° 104cd/m2 85° 77cd/m2

6"(152mm)

24" (610mm)

Vision Smart Voltage Ballast Options 4"Precisioncontoured 120=120V Seepage4.114 See page 4.114 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elect.Ballastonly)

UNVVRA2G9LS26U ACS2HIExample

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Exposed Slot-T or

concealed T-Grid

Air handling 2' x 2' 16 2-T8U6 VRA2G16LS26U VRA2T16LS26U

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 118: Linear recessed and surface lighting

4.115Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

VisionSmart2'x2'4" Parabolic louver recessed air handling luminaires

VisionSmartarchitecturallysymmetrical2'x2'VRParabolicsmeetthecriteriaofIESRP-1andRP-24.TheVRSeriesisbestsuitedwhereveruseofVDT’sisoccasionalornonintensive.

Features•VRunitsmeetIESRP24andRP1recommended(basic)criteriaforlightingVDTareas.

•Only6"deep.•Semi-specularlowiridescencepre-anodizedlouverisstandardonVRmodels.

•Concealedspring-loadedlatch/hingecanbeopened either side.

•Louverframewithintegralpositivelightstop.•Earthquakeclipsincluded.•ProtectiveFilmdustguard.•UL-Listedtwinknockoutaccessplate.•Metalgauge/constructiontomeetNYCCode

or Chicago Plenum is available.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp elec. T8 H3*, P3** O3*1 & 2 Lamp elec. TT5 40W IB*, PR** SB*1 - 3 Lamp elec. TT5 40W I3* X3*LOL T8 Dimming – PSLOL TT5 Dimming – PB

* Instant start.

** Program start.

Consult factory for other wattages.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Air closure strips: ACS4(factoryinstalled).

ACS4 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

Note: For concealed spline, plaster or drywall ceiling, use “G” type fixtures with either S2X2FKIT(seeFolioOA-30-30),orDRYWALLKIT,FK92X2(seeFolioOA30-10).

Louver finish is low iridescence semi-specular.

30˚

60˚1400

2800

4200

Candlepower CurveVRA2G9LP32UUNVH3

Reference data

Efficiency 56.7% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 83.0W LER 57.0

Max average brightness

55° 4605cd/m2 65° 484cd/m2 75° 181cd/m2 85° 115cd/m2

24" (610mm)

6" (152mm)

9 Cells

Vision Smart Voltage Ballast Options 4"Precisioncontoured 120=120V Seepage4.115 See page 4.115 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elect.Ballastonly)

UNVVRA2G9LP32U ACS2H3Example

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Exposed Slot-T or

concealed T-Grid

Air handling 2' x 2' 9 3-T8U1.6 3-TT5

VRA2G9LP32U VRA2G9LP3FT

VRA2T9LP32U VRA2T9LP3FT

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

30˚

60˚1500

3000

4500

Candlepower CurveVRA2G12PP32UUNVH3

Reference data

Efficiency 55.5% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 83.0W LER 53.0

Max average brightness

55° 1151cd/m2 65° 71cd/m2 75° 52cd/m2 85° 38cd/m2

24" (610mm)

6" (152mm)

12 Cells

Vision Smart Voltage Ballast Options 4"Precisioncontoured 120=120V Seepage4.115 See page 4.115 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elect.Ballastonly)

120VRA2G12PP3FT ACS2X3Example

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Exposed Slot-T or

concealed T-Grid

Air handling 2' x 2' 12 3-T8U1.6 3-TT5

VRA2G12PP32U VRA2G12PP3FT

VRA2T12PP32U VRA2T12PP3FT

Louver finish is low iridescence specular.

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 119: Linear recessed and surface lighting

4.116 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

VisionSmart1'x4'3" Parabolic louver recessed air supply/return/static luminaires

VisionSmart(VR)luminaires1lamp8cell,2lamp12cellcomplywiththeBasicCriteriaofRP-1(formerlyRP-24).

Features•MeetsIESRP-1recommended(minimumrequirements)forlightingVDTareas(VR1lamp 8and12cell).

•Semi-specularlowiridescencepre-anodizedlouver.•Verticalgrainonlouvereliminatesreflectedlamp

images on cross baffle.•Louverframewithpositivelightstop.•Spring-loadedlatches(selfcentering).•Blackhousingexteriorforcoolerballast

operating temperature.•Built-inearthquakeclip•UL-Listedtwinknockoutaccessplate.•Metalgauge/constructiontomeetNYCCode

or Chicago Plenum is available.•Turned-inedgesforsafehandling.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start.

** Program start.

Consult factory for other wattages.

Drywall kit: Catalog no. FK91X4 with “G” type fixtures for drywall or plaster ceilings.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF14 for 1' x 4' troffer.Continuous row installation: For “F” type fixtures, half-width flanges are required between fixtures. Catalog no. 1FCTRIM(eachjoint).Air closure strips: ACS4(factoryinstalled).

ACS4 CSP(f ieldinstalled).Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

30˚

60˚200

400

800

Candlepower CurveVRA1G8LW132UNVHI

Reference data

Efficiency 67.9% Spacing ratio 1.9

Electronic ballast

Inputwatts(120V) 30.0W

Max average brightness

65° 837cd/m2 75° 82cd/m2 85° 0cd/m2

5 ¾" (146mm)

12" (305mm)

Vision Smart Voltage Ballast Options 3"Parabolic 120=120V Seepage4.116 See page 4.116 277=277V andpage4.130 UNV=120-277V (Elect.Ballastonly)

UNVVRA1G8LW132 HIExample

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 1' x 4'

812812

1-T81-T82-T82-T8

VRA1G8LW132 VRA1G12LW132 VRA1G8LW232 VRA1G12LW232

VRA1F8LW132 VRA1F12LW132 VRA1F8LW232 VRA1F12LW232

VRA1T8LW132 VRA1T12LW132 VRA1T8LW232 VRA1T12LW232

Static 1' x 4'

812812

1-T81-T82-T82-T8

VRS1G8LW132 VRS1G12LW132 VRS1G8LW232 VRS1G12LW232

VRS1F8LW132 VRS1F12LW132 VRS1F8LW232 VRS1F12LW232

VRS1T8LW132 VRS1T12LW132 VRS1T8LW232 VRS1T12LW232

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 120: Linear recessed and surface lighting

4.117Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Stacklyte 1' x 4'3" Parabolic louver recessed air supply/return/static luminaires

Stacklyte(STA)isexcellentforlightinglibrarybookshelveswith97.5%ofthefixturedistribution in the 90° zone.

Features•Semi-specularlowiridescencepre-anodizedlouver.•Verticalgrainonlouvereliminatesreflectedlamp

images on cross baffle.•Louverframewithpositivelightstop.•Spring-loadedlatches(selfcentering).•Blackhousingexteriorforcoolerballast

operating temperature.•Built-inearthquakeclip•UL-Listedtwinknockoutaccessplate.•Metalgauge/constructiontomeetNYCCode

or Chicago Plenum is available.•Turned-inedgesforsafehandling.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start.

** Program start.

Consult factory for other wattages.

Drywall kit: Catalog no. FK91X4 with “G” type fixtures for drywall or plaster ceilings.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF14 for 1' x 4' troffer.Continuous row installation: For “F” type fixtures, half-width flanges are required between fixtures. Catalog no. 1FCTRIM(eachjoint).Air closure strips: ACS4(factoryinstalled).

ACS4 CSP(f ieldinstalled).Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

30˚

60˚400

800

1200

Candlepower CurveSTA1G8LR132UNVHI

5 ¾" (146mm)

12" (305mm)

Stacklyte Voltage Ballast Options 3"Parabolic 120=120V Seepage4.117 See page 4.117 277=277V andpage4.130 UNV=120-277V (Elect.Ballastonly)

UNVSTA1G8LR132 HIExample

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 1' x 4'

812812

1-T81-T82-T82-T8

STA1G8LR132 STA1G12LR132 STA1G8LR232 STA1G12LR232

STA1F8LR132 STA1F12LR132 STA1F8LR232 STA1F12LR232

STA1T8LR132 STA1T12LR132 STA1T8LR232 STA1T12LR232

Static 1' x 4'

812812

1-T81-T82-T82-T8

STS1G8LR132 STS1G12LR132 STS1G8LR232 STS1G12LR232

STS1F8LR132 STS1F12LR132 STS1F8LR232 STS1F12LR232

STS1T8LR132 STS1T12LR132 STS1T8LR232 STS1T12LR232

5 ¾" (146mm)

12" (305mm)

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Verticalfootcandlesonbookshelves 1' 2' 3' 4' Ceiling 1 48 48 49 48 48 48 49 48 48 2 36 36 36 36 36 36 36 36 36 3 28 28 28 28 28 28 28 28 28 4 24 24 24 24 24 24 24 24 24 5 21 21 21 21 21 21 21 21 21 6 18 18 18 18 18 18 18 18 18 7 16 16 16 16 16 16 16 16 16 8 16 16 16 16 16 16 16 16 16 9 15 15 15 15 15 15 15 15 15 10 14 14 14 14 14 14 14 14 14 11 12 12 12 12 12 12 12 12 12 12 10 10 10 10 10 10 10 10 10 Floor

36"bookshelfaislewidth

Page 121: Linear recessed and surface lighting

4.118 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Deepcel Plus 2' x 4'3" Parabolic louver recessed air return/static luminaires

PhilipsLightolierDeepcelPlusistheindustrystandard3"paraboliclouvertrofferwithfeatures that offer value above the industry standard.

Features•5"deepbody.•Individuallampcompartments.•77.7%efficient,3lamp18cell.•Cleancontouredinterior.•Eyeletedheatremovalventsinfixtureends.•Onepiecehousing.•Blackexteriorforcoolerballastoperatingtemperature.•Hemmedoversiderailsforsafehandling.•Built-inearthquakeclips.•Pre-anodizedaluminumparaboliclouver.•Verticalgrainlouvereliminatesreflectedlampimageson

cross baffle.•Spring-loadedroosterheadlatches.•18gaugesteelhinges.•Louverframewithintegralpositivelightstop.•Louverhasprotectivefilmdustguard.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp elec. T8 H3*, P3** O3*1 - 4 Lamp elec. T8 H4*, P4** O4*LOL T8 Dimming – PS

* Instant start.

** Program start.

Consult factory for other wattages.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF24 for 2' x 4' troffer.Continuous row installation: For “F” type fixtures, half-width flanges are required between fixtures. Catalog no. 2FCTRIM(eachjoint).Air closure strips: ACS4(factoryinstalled).

ACS4 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.NYC code: Change DP to DY.

30˚

60˚900

1800

2700

Candlepower CurveDPA2G18LP332UNVH3

Reference data

Efficiency 77.7% Spacing ratio 1.6

Electronic ballast

Inputwatts(120V) 85.9W Luminaireeff.(LER) 68.6

5"(127mm)

24" (610mm)

Deepcel Plus Voltage Ballast Options 3"Precisioncontoured 120=120V Seepage4.118 See page 4.118 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8ballastonly)

UNVDPA2G18LP332 ACS4H3Example

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 2' x 4' 1824 3-T8 DPA2G18LP332

DPA2G24LP332DPA2F18LP332 DPA2F24LP332

DPA2T18LP332 DPA2T24LP332

Static 2' x 4' 1824 3-T8 DPS2G18LP332

DPS2G24LP332DPS2F18LP332 DPS2F24LP332

DPS2T18LP332 DPS2T24LP332

30˚

60˚850

1700

2550

Candlepower CurveDPA2G18LS332UNVH3

Reference data

Efficiency 77.6% Spacing ratio 1.6

Electronic ballast

Inputwatts(120V) 85.8W Luminaireeff.(LER) 68.6

5"(127mm)

24" (610mm)

Deepcel Plus Voltage Ballast Options 3"Precisioncontoured 120=120V Seepage4.118 See page 4.118 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8ballastonly)

UNVDPA2G18LS332 ACS4H3Example

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 2' x 4' 18 3-T84-T8

DPA2G18LS332 DPA2F18LS432

DPA2F18LS332 DPA2F18LS432

DPA2T18LS332 DPA2T18LS432

Static 2' x 4' 18 3-T84-T8

DPS2G18LS332 DPS2G18LS432

DPS2F18LS332 DPS2F18LS432

DPS2T18LS332 DPS2T18LS432

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 122: Linear recessed and surface lighting

4.119Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Features•5"deepbody.•80%efficient,2lamp12cell.•Cleancontouredinterior.•Eyeletedheatremovalventsinfixtureends.•Onepiecehousing.•Blackexteriorforcoolerballastoperatingtemperature.•Hemmedoversiderailsforsafehandling.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Pre-anodizedaluminumparaboliclouver.•Verticalgrainlouvereliminatesreflectedlampimageson

cross baffle.•Spring-loadedroosterheadlatches.•18gaugesteelhinges.•1.6spacingtomountingheightratio.•Snap-inballastcover.•Louverframewithintegralpositivelightstop.•Louverhasprotectivefilmdustguard.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 4 Lamp elec. T8 H4*, P4** O4*LOL T8 Dimming – PS

* Instant start.

** Program start.

Consult factory for other wattages.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF24 for 2' x 4' troffer.Continuous row installation: For “F” type fixtures, half-width flanges are required between fixtures. Catalog no. 2FCTRIM(eachjoint).Air closure strips: ACS4(factoryinstalled).

ACS4 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.NYC code: Change DP to DY.

Deepcel Plus 2' x 4'3" Parabolic louver recessed air return/static luminaires

PhilipsLightolierDeepcelPlusistheindustrystandard3"paraboliclouvertrofferwithfeatures that offer value above the industry standard.

30˚

60˚650

1300

1950

Candlepower CurveDPA2G12LS232UNVHI

24" (610mm)

5"(127mm)

Deepcel Plus Voltage Ballast Options 3"Precisioncontoured 120=120V Seepage4.119 See page 4.119 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8ballastonly)

UNVDPA2G12LS232 ACS4HIExample

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 2' x 4' 12 2-T8 4-T8

DPA2G12LS232 DPA2G12LS432

DPA2F12LS232 DPA2F12LS432

DPA2T12LS232 DPA2T12LS232

Static 2' x 4' 12 2-T8 4-T8

DPS2G12LS232 DPS2G12LS432

DPS2F12LS232 DPS2F12LS432

DPS2T12LS232 DPS2T12LS432

30˚

60˚1100

2200

3300

Candlepower CurveDPA2G32LS432UNVH4

Reference data

Efficiency 64.1% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 110.9W LuminaireEff.(LER) 56.7

5"(127mm)

24" (610mm)

Deepcel Plus Voltage Ballast Options 3"Precisioncontoured 120=120V Seepage4.119 See page 4.119 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8ballastonly)

UNVDPA2G32LS432 ACS4H4Example

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 2' x 4' 32 4-T8 DPA2G32LS432 DPA2F32LS432 DPAT32LS432

Static 2' x 4' 32 4-T8 DPS2G32LS432 DPS2F32LS432 DPS2T32LS432

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Reference data

Efficiency 80.0% Spacing ratio 1.6

Electronic ballast

Inputwatts(120V) 61.6W LuminaireEff.(LER) 64.4

Page 123: Linear recessed and surface lighting

4.120 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Deepcel Plus 2' x 2'3" Parabolic louver recessed air handling/static luminaires

Deepcel Plus 2' x 2' parabolic troffers feature all of the design benefits of the 2' x 4' product. AvailablewithT8andBiaxtypelampsin9,12or16cellconfigurations.Forgeneralofficelighting Deepcel Plus 2' x 2' is the preferred choice.

Features•5"deepbody,cleancontouredinterior.•66.2%efficient,2lamp9cellU6T8.•63.4%efficient,3lamp9cellT81.6.•Eyeletedheatremovalventsinfixtureends.•Onepiecehousing.•Blackexteriorforcoolerballastoperatingtemperature.•Hemmedoversiderailsforsafehandling.•Fixturesendsturned-inforsafehandling.•Built-inearthquakeclips.•Pre-anodizedaluminumparaboliclouver.•Verticalgrainlouvereliminatesreflectedlampimages

on cross baffle.•Spring-loadedroosterheadlatches.•18gaugesteelhinges.•Louverframewithintegralpositivelightstop.•Louverhasprotectivefilmdustguard.•AvailableforU-shapeOctronCurvalumeorBiax

lamp types.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp elec. T8 H3*, P3** O3*LOL T8 Dimming – PS

* Instant start.

** Program start.

Consult factory for other wattages.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF22 for 2' x 2' troffer.Continuous row installation: For “F” type fixtures, half-width flanges are required between fixtures. Catalog no. 2FCTRIM(eachjoint).Air closure strips: ACS2(factoryinstalled).

ACS2 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.NYC code: Change DP to DY.

30˚

60˚550

1100

1650

Candlepower CurveDPA2G9LS26UUNVHI

Reference data

Efficiency 66.2% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 57.2W Luminaireeff.(LER) 53.4

5"(127mm)

24" (610mm)

Deepcel Plus Voltage Ballast Options 3"Precisioncontoured 120=120V Seepage4.120 See page 4.120 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8orTT5ballastonly)

UNVDPA2G9LS26U ACS2HIExample

Ordering information For 17W T8 substitute 6U with 17 in Catalog number.

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 2' x 2' 912 2-T8U6 DPA2G9LS26U

DPA2G12LS26UDPA2F9LS26U DPA2F12LS26U

DPA2T9LS26U DPA2T12LS26U

Static 2' x 2' 912 2-T8U6 DPS2G9LS26U

DPS2G12LS26UDPS2F9LS26U DPS2F12LS26U

DPS2G9LS26U DPS2T12LS26U

30˚

60˚800

1600

2400

Candlepower CurveDPA2G9LP32UUNVH3

Reference data

Efficiency 63.4% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 57.2W Luminaireeff.(LER) 56.2

5"(127mm)

24" (610mm)

Deepcel Plus Voltage Ballast Options 3"Precisioncontoured 120=120V Seepage4.120 See page 4.120 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8orTT5ballastonly)

UNVDPA2G9LP32U ACS2H3Example

Ordering information For 17W T8 substitute 2U with 17 in Catalog number.

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 2' x 2' 912 3-T8U1.6 DPA2G9LP32U

DPA2G12LP32UDPA2F9LP32U DPA2F12LP32U

DPA2T9LP32U DPA2T12LP32U

Static 2' x 2' 912 3-T8U1.6 DPS2G9LP32U

DPS2G12LP32UDPS2F9LP32U DPS2F12LP32U

DPS2T9LP32U DPS2T12LP32U

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 124: Linear recessed and surface lighting

4.121Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Features•5"deepbody,cleancontouredinterior.•61.6%efficient,2lamp9cellU6T8.•72.0%efficient,3lamp9cellTT5.•Eyeletedheatremovalventsinfixtureends.•Onepiecehousing.•Blackexteriorforcoolerballastoperatingtemperature.•Hemmedoversiderailsforsafehandling.•Fixturesendsturned-inforsafehandling.•Built-inearthquakeclips.•Pre-anodizedaluminumparaboliclouver.•Verticalgrainlouvereliminatesreflectedlampimages

on cross baffle.•Spring-loadedroosterheadlatches.•18gaugesteelhinges.•Louverframewithintegralpositivelightstop.•Louverhasprotectivefilmdustguard.•AvailableforU-shapeOctronCurvalumeorBiaxtype.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp elec. TT5 40W I3* X3*Electronic TT5 40W IB*, PR** SB*LOL T8 Dimming – PSLOL TT5 Dimming – PB

* Instant start.

** Program start.

Consult factory for other wattages.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 .Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF22 for 2' x 2' troffer.Continuous row installation: For “F” type fixtures, half-width flanges are required between fixtures. Catalog no. 2FCTRIM(eachjoint).Air closure strips: ACS2(factoryinstalled).

ACS2 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.NYC code: Change DP to DY.

Deepcel Plus 2' x 2'3" Parabolic louver recessed air handling/static luminaires

Deepcel Plus 2' x 2' parabolic troffers feature all of the design benefits of the 2' x 4' product. AvailablewithT8andBiaxtypelampsin9,12or16cellconfigurations.Forgeneralofficelighting Deepcel Plus 2' x 2' is the preferred choice.

30˚

60˚550

1100

1650

Candlepower CurveDPA2G16LS26UUNVHI

24" (610mm)

5"(127mm)

Deepcel Plus Voltage Ballast Options 3"Precisioncontoured 120=120V Seepage4.121 See page 4.121 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8orTT5ballastonly)

UNVDPA2G16LS26U ACS2HIExample

Ordering information For 17W T8 substitute 6U with 17 in Catalog number.

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 2' x 2' 16 2-T8U6 DPA2G16LS26U DPA2G16LS26U DPA2T16LS26U

Static 2' x 2' 16 2-T8U6 DPS2G16LS26U DPS2F16LS26U DPS2T16LS26U

30˚

60˚1050

2100

3150

Candlepower CurveDPA2G9LP3FT120SB&DPA2G12LP3FT120SB

Reference data

Efficiency 72.0% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 100.0W Luminaireeff.(LER) 59.9

5"(127mm)

24" (610mm)

Deepcel Plus Voltage Ballast Options 3"Precisioncontoured 120=120V Seepage4.121 See page 4.121 pre-anodized aluminum 277=277V andpage4.130 parabolic louver UNV=120-277V (Elec.T8orTT5ballastonly)

120DPA2G9LP3FT ACS2X3Example

Ordering information

Type Size Cells Lamp qty –type Exposed T-Grid Flanged for

dry or plasterSlot-T or Concealed T

Air handling 2' x 2' 9 12 3-TT5 DPA2G9LP3FT

DPA2G12LP3FTDPA2F9LP3FT DPA2F12LP3FT

DPA2T9LP3FT DPA2T12LP3FT

Static 2' x 2' 9 12 3-TT5 DPS2G9LP3FT

DPS2G12LP3FTDPS2F9LP3FT DPS2G12LP3FT

DPS2T9LP3FT DPS2T12LP3FT

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Reference data

Efficiency 61.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 51.5W Luminaireeff.(LER) 49.4

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 125: Linear recessed and surface lighting

4.122 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Prismalyte Plus 2' x 4'Premium specification lensed recessed air handling luminaires

Prismalyte Plus luminaires are top of the line air handling lensed fluorescent luminaires with floating door appearance, regressed, aluminum doors and black painted housing for optimum lamp and ballast operations. Door frames are interchangeable with Deepcel Plus 2' x 4' louvers.

Features•5"deepbody(2'x4').•Blackhousingexteriorforcoolerballastoperating

temperature.•Built-inearthquakeclipson2'x4'.•Hemmedoversiderailsforsafety.•Fixtureendsturnedinforsafehandling.•Doorjambfinishedblackonfoursidesfor

positive light stop.•Truemiteredcorneraluminumlensframe.•InterchangeablewithDeepcelandParabafflelouvers.•Springloadedroosterheadlatches.

Options & accessories page 4.130Special lenses:VAlenspattern12prismaticvirginacrylic is standard. For other available lenses, see options and accessories page.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Elec. T8 H3*, P3** O3*1 - 4 Lamp Elec. T8 H4*, P4** O4*

* Instant start.

** Program start.

Consult factory for other wattages.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF24 for 2' x 4' troffer.Air closure strips: ACS4(factoryinstalled).

ACS4 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.For NYC code consult factory

30˚

60˚1250

2500

3750

Candlepower CurvePRA2GRFVA432UNVH4

Reference data

Efficiency 76.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 109.5W Luminaireeff.(LER) 68.7

24" (610mm)

24" (610mm)

24" (610mm)

5"(127mm)

5"(127mm)

5"(127mm)

Prismalyte Plus Voltage Ballast Options Floating lens frame 120=120V Seepage4.122 See page 4.122 recessed fluorescent 277=277V andpage4.130 troffer UNV=120-277V (Elec.T8orTT5Ballastonly)

UNVPRA2GRFVA432 CH4Example

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

Air handling 2' x 4'2-T8 3-T8 4-T8

PRA2GRFVA232 PRA2GRFVA332 PRA2FRFVA432

PRA2FRFVA232 PRA2GRFVA332 PRA2FRFVA432

Static 2' x 4'2-T8 3-T8 4-T8

PRS2GRFVA232 PRS2FRFVA332 PRS2GRFVA432

PRS2FRFVA232 PRS2FRFVA332 PRS2GRFVA432

Page 126: Linear recessed and surface lighting

4.123Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Features•5"deepbody(2'x2').•4"deep(1'x4'GType).•Blackhousingexteriorforcoolerballastoperating

temperature.•Built-inearthquakeclipson2'x2'.•Hemmedoversiderailsforsafety.•Fixtureendsturnedinforsafehandling.•Doorjambfinishedblackonfoursidesfor

positive light stop.•Truemiteredcorneraluminumlensframe.•InterchangeablewithDeepcelandParabafflelouvers.•Springloadedroosterheadlatches.

Options & accessories page 4.130Special lenses:VAlenspattern12prismaticvirginacrylic is standard. For other available lenses, see options and accessories page.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Elec. T8 H3*, P3** O3*1 - 3 Lamp Elec. TT5 40W IB*, PR** X3*Electronic TT5 40W IB* SB

* Instant start.

** Program start.

Consult factory for other wattages.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 . Conversion kit for 1' x 4' unit: FK91X4.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF22 for 2' x 2' troffer. Catalog no. PF14 for 1' x 4' troffer.Air closure strips: ACS2(factoryinstalled).

ACS2 CSP(f ieldinstalled).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.For NYC code consult factory

Prismalyte Plus 2' x 2' & 1' x 4'Premium specification lensed recessed air handling luminaires

Prismalyte Plus luminaires are top of the line air handling lensed fluorescent luminaires with floating door appearance, regressed, aluminum doors and black painted housing for optimum lamp and ballast operations. Door frames are interchangeable with Deepcel Plus 2' x 2' louvers.

30˚

60˚600

1200

1800

Candlepower CurvePRA2GRFVA26UUNVHI&PRA2GRFVA32UUNVH3

Reference data

Efficiency 71.6% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 60.0W Luminaireeff.(LER) 58.0

PRA26U5"

(127mm)

24" (610mm)

Prismalyte Plus Voltage Ballast Options Floating lens frame 120=120V Seepage4.123 See page 4.123 recessed fluorescent 277=277V andpage4.130 troffer UNV=120-277V (Elec.T8orTT5Ballastonly)

UNVPRA2GRFVA26U CHIExample

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

Air handling 2' x 2'2-T8U6 3-T8U1.6/ 3-TT5

PRA2GRFVA26U PRA2GRFVA32U PRA2GRFVA3FT

PRA2FRFVA26U PRA2FRFVA32U PRA2FRFVA3FT

Static 2' x 2'2-T8U6 3-T8U1.6/ 3-TT5

PRS2GRFVA26U PRS2GRFVA32U PRS2GRFVA3FT

PRS2FRFVA26U PRS2FRFVA32U PRS2FRFVA3FT

24" (610mm)

PRA32U5"

(127mm)

30˚

60˚800

1600

2400

Candlepower Curve

Reference data

Efficiency 67.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 76.0W Luminaireeff.(LER) 63.4

30˚

60˚600

1200

1800

Candlepower CurvePRA1GFVA232UNVHI

Reference data

Efficiency 65.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 56.6W Luminaireeff.(LER) 58.0

12" (305mm)

4"(101mm)

Prismalyte Plus Voltage Ballast Options Floating lens frame 120=120V Seepage4.123 See page 4.123 recessed fluorescent 277=277V andpage4.130 troffer UNV=120-277V (Elec.T8orTT5Ballastonly)

UNVPRA1GRFVA232 CHIExample

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

Air handling 1' x 4' 1-T8 2-T8

PRA1GRFVA132 PRA1GRFVA232

PRA1FRFVA132 PRA1FRFVA232

Static 1' x 4' 1-T8 2-T8

PRS1GRFVA132 PRS1GRFVA232

PRS1FRFVA132 PRS1FRFVA232

Page 127: Linear recessed and surface lighting

4.124 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Specplus 2' x 4'Specification grade lensed recessed static luminaires

SpecplushasallthefeaturesyoulookforinaTRUEspecificationgradelenstroffer.Our5"depth reverses the industry trend of making fixtures shallower thus putting the lamps closer to the lens. And there is more.

Features•5"deepbody(2'x4').•31/16"lamptolensforbetterlampobscuration(2'x4').•81.2%efficient(4light).•Cleancontouredinterior,noholes.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips(2'x4').•SlimlineDoorframewith475and1000squareinchlensopenings(2'x4').

•Doorjambfinishedblackonfoursidesforpositivelight stop.

•TrueMiteredcornersteellensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•Flatandregressedaluminumdoorsavailable.•ConstructiontomeetChicagoPlenum

requirements is available.

Options & accessories page 4.130Special lenses:VAlenspattern12prismaticvirginacrylic is standard. For other available lenses, see options and accessories page.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Elec. T8 H3*, P3** O3*1 - 4 Lamp Elec. T8 H4*, P4** O4*

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 4' unit: FK92X4.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF24 for 2' x 4' troffer.Continuous row installation: For “F” type fixtures, half-width flanges are required between fixtures. Catalog no. 2FCTRIM(eachjoint).Door frames: SPS2GFS (Flatsteeldoor).

SPS2GFA (Flataluminumdoor). SPS2GRA(Regressedaluminumdoor).

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

30˚

60˚1250

2500

3750

Candlepower Curve

SPS2GFSVA432UNVH4Reference data

Efficiency 81.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 108.7W LuminaireEff.(LER) 73.2

5"(127mm)

24" (610mm)

Specplus Voltage Ballast Options Lens Frame Recessed 120=120V Seepage4.124 See page 4.124 Fluorescent Troffer 277=277V andpage4.130 UNV=120-277V (Elec.T8orTT5Ballastonly)

UNVSPS2GFSVA432 AH4Example

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

Static 2' x 4'2-T8 3-T8 4-T8

SPS2GFSVA232 SPS2GFSVA332 SPS2GFSVA432

SPS2FFSVA232 SPS2FFSVA332 SPS2FFSVA432

5"(127mm)

24" (610mm)

24" (610mm)

5"(127mm)

Sky lens The Sky lens offers an aesthetically pleasing lens option for any environment giving you the ability to customize your space. The Sky lens exudes a soothing alternative to conventional lenses when used in areas such as health care waiting or examination rooms, assisted living common areas or child care faculties.

These options are available on the Philips Lightolier SpecPlus Recessed Fluorescent 2' x 2' and 2' x 4' models. To order the Sky Lens simply insert your choice of Sky lenses, S1 or S2 ,intothestandardSpecPlus(SPS)Catalog number.Sky lens 2' x 4' S1

Sky lens 2' x 4' S2 Sky lens 2' x 2' S2

Sky lens 2' x 2' S1

Example

Standard: SPS2GFS VA 232UNVHI

Sky Lens: SPS2GFS S1 232UNVHI

Page 128: Linear recessed and surface lighting

4.125Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Features•5"deepbody(2'x2').•31/16"lamptolensforbetterlampobscuration(2'x2').•71.6%efficient(2-6UT8).•Cleancontouredinterior,noholes.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips(2'x2').•SlimlineDoorframewith475and1000squareinchlensopenings(2'x2').

•Doorjambfinishedblackonfoursidesforpositivelight stop.

•TrueMiteredcornersteellensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•Flatandregressedaluminumdoorsavailable.•ConstructiontomeetChicagoPlenumrequirements

is available.

Options & accessories page 4.130Special lenses:VAlenspattern12prismaticvirginacrylic is standard. For other available lenses, see options and accessories page.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Elec. T8 H3*, P3** O3*1 - 3 Lamp Elec. TT5 40W I3* X3*Electronic TT5 40W IB*, PR** SB*

* Instant start.

** Program start.

Drywall kit: Conversion kit for 2' x 2' unit: FK92X2 . Conversion kit for 1' x 4' unit: FK91X4.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF22 for 2' x 2' troffer. Catalog no. PF14 for 1' x 4' troffer.Continuous row installation: For “F” type fixtures, half-width flanges are required between fixtures. Catalog no. 2FCTRIM(eachjoint-2'x2'). Catalog no. 1FCTRIM(eachjoint-1'x4').Door frames: SPS2GFS (Flatsteeldoor).

SPS2GFA (Flataluminumdoor). SPS2GRA(Regressedaluminumdoor).

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.

Specplus 2' x 2' & 1' x 4'Specification grade lensed recessed static luminaires

SpecplushasallthefeaturesyoulookforinaTRUEspecificationgradelenstroffer.Our5"depth reverses the industry trend of making fixtures shallower thus putting the lamps closer to the lens. And there is more.

30˚

60˚600

1200

1800

Candlepower Curve

SPS2GFSVA26UUNVHI&SPS2GFSVA32UUNVH3Reference data

Efficiency 71.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 56.3W LuminaireEff.(LER) 63.1

5"(127mm)

24" (610mm)

Prismalyte Plus Voltage Ballast Options Floating Lens Frame 120=120V Seepage4.125 See page 4.125 Recessed Fluorescent 277=277V andpage4.130 Troffer UNV=120-277V (Elec.T8orTT5Ballastonly)

UNVSPS2GFSVA26U AHIExample

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

Static 2' x 2'

2-T8U63-TT5 3-T8U1.6/ 3-T8F17

SPS2GFSVA26U SPS2GFSVA3FT SPS2GFSVA32U SPS2GFSVA317

SPS2FFSVA26U SPS2FFSVA3FT SPS2FFSVA32U SPS2FFSVA317

5"(127mm)

5"(127mm)

24" (610mm)

24" (610mm)

30˚

60˚800

1600

2400

Candlepower Curve

Reference data

Efficiency 67.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 76.2W LuminaireEff.(LER) 64.1

30˚

60˚800

1200

1800

Candlepower Curve

SPS1GFSVA232UNVHIReference data

Efficiency 69.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 55.8W LuminaireEff.(LER) 62.0

4"(101mm)

12" (305mm)

Specplus Voltage Ballast Options Lens Frame Recessed 120=120V Seepage4.125 See page 4.125 Fluorescent Troffer 277=277V andpage4.130 UNV=120-277V (Elec.T8orTT5Ballastonly)

UNVSPS1GFSVA232 AHIExample

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

Static 1' x 4' 1-T8 2-T8

SPS1GFSVA132 SPS1GFSVA232

SPS1FFSVA132 SPS1FFSVA232

Page 129: Linear recessed and surface lighting

4.126 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Standard

XPseries2'x4'High perform lensed recessed static luminaires

PhilipsLightolier’sXPtrofferoffershighefficienciesanduniquefeaturesatanaffordable price.

Features•Efficiency:83.0%(4lamp),85.0%(3lamp),87.0%(2 lamp).

•Shallow3"deephousing.•Ribbedhousingforstrengthandstability.•Endsofhousingformedinwardforsafehandling.•Built-inearthquakeclips.•Hemmed-oversiderailsforsafehandling.•EndshavescrewdimplesforinstallationtoT-bar (nofixtureorceilingdistortion).

•Flatsteelorregressedaluminumlensframewith mitered corners.

•EdgesofsteelorregressedDoorframehemmed-over for safe handling.

•Nolightleak.•Internal“T”hinges-easyinstallationandmaintenance.•Roosterheadspringlatches.•Meetscode30requirementsinNewEngland.

Options & accessories page 4.130Special lenses:VAlenspattern12prismaticvirginacrylic is standard. For other available lenses, see options and accessories page.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Elec. T8 H3*, P3** O3*1 - 4 Lamp Elec. T8 H4*, P4** O4*

* Instant start.

** Program start.

Drywall kit: Catalog no. FK92X4 with fixtures for drywall or plaster ceilings.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF24 for 2' x 4' troffer.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚1200

2400

3600

Candlepower CurveXP2GVA432UNVH4

Reference data

Efficiency 83.0% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 112.0W LuminaireEff.(LER) FL-74.3

3"(76mm)

24" (610mm)

XP Voltage Ballast Options Flat Steel Lens Frame 120=120V Seepage4.126 See page 4.126 Recessed Fluorescent Troffer 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVXP2GVA432 AH4Example

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

XP Static 2' x 4' 4-T8 XP2GVA432 XP2FVA432

30˚

60˚950

1900

2850

Candlepower CurveXP2GVA332UNVH3

Reference data

Efficiency 85.0% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 85.0W LuminaireEff.(LER) FL-75.2

24" (610mm)

3"(76mm)

24" (610mm)

XP Voltage Ballast Options Flat Steel Lens Frame 120=120V Seepage4.126 See page 4.126 Recessed Fluorescent Troffer 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVXP2GVA332 AH3Example

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

XP Static 2' x 4' 3-T8 XP2GVA332 XP2FVA332

30˚

60˚650

1300

1950

Candlepower CurveXP2GVA232UNVHI

Reference data

Efficiency 87.0% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 58.0W LuminaireEff.(LER) FL-74.3

24" (610mm)

3"(76mm)

24" (610mm)

XP Voltage Ballast Options Flat Steel Lens Frame 120=120V Seepage4.126 See page 4.126 Recessed Fluorescent Troffer 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVXP2GVA232 AHIExample

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

XP Static 2' x 4' 2-T8 XP2GVA232 XP2FVA232

Page 130: Linear recessed and surface lighting

4.127Comprehensive lighting catalog 7th Edition

Standard – Linear recessed and surface lighting

XP/XAseries2'x2'&1'x4'High perform lensed recessed static luminaires

PhilipsLightolier’shighperformanceXP/XAseriesoflensedtroffersoffersuniquefeaturesthatoutperform and extend more value for money than any other comparable fluorescent troffer.

Features•4"deep(1'x4').31/2"deep(2'x2').•Fixturesiderailshaverolled-overedgesfor

maximum safety.•Built-inearthquakeclips.•Flushsteelfull-sizedDoorframewithmitered

corner detailing.•Angleregressedextrudedaluminumdooroption.•Endcaphassingleformconfigurationandformededges

for easy lamping and safety.•Doorframeoverlapsendcapforpositivelightstop.•UL-Listedtwinknock-outaccessplateforeasyclosed-

door wiring.•Fitsnewnarrowslotgridceilingsystems.

Options & accessories page 4.130Special lenses:VAlenspattern12prismaticvirginacrylic is standard. For other available lenses, see options and accessories page.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Elec. T8 H3*, P3** O3*Electronic TT5 40W IB*, PR** SB*

* Instant start.

** Program start.

Drywall kit: Catalog no. FK91X4 or FK92X2 with fixtures for drywall or plaster ceilings.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Seismic Hold-Down Clip: Suffix: 2HD. For 1' x 4', type G, factory installed.Plaster frame: For type F troffers, order plaster frames separately. Catalog no. PF14 for 1' x 4' troffer.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Suffix: C. For products that meet Chicago Plenum requirements.For NYC code consult factory

30˚

60˚600

1200

1800

Candlepower CurveXP1GVA232UNVHI

Reference data

Efficiency 69.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 55.8W LuminaireEff.(LER) 62.0

4"(101mm)

12" (305mm)

XP Voltage Ballast Options Flat Steel Lens Frame 120=120V Seepage4.127 See page 4.127 Recessed Fluorescent Troffer 277=277V andpage4.130 UNV=120-277V XA (Elec.T8Ballastonly) Regressed Aluminum Lens Frame Recessed Fluorescent Troffer

UNVXP1GVA232 AHIExample

Ordering information

Type Size Lamps qty –type Exposed T-Grid Flanged for

dry or plaster

XP Static 1' x 4' 2-T8/T12 XP1GVA232 XP1FVA232

XA Static 1' x 4' 2-T8/T12 XA1GVA232 XA1FVA232

30˚

60˚600

1200

1800

Candlepower CurveXP2GVA26UUNVHI

Reference data (SO)

Efficiency 71.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 55.3W LuminaireEff.(LER) 62.3

24" (610mm)

3"(76mm)

XP Voltage Ballast Options Flat Steel Lens Frame 120=120V Seepage4.127 See page 4.127 Recessed Fluorescent Troffer 277=277V andpage4.130 UNV=120-277V XA (Elec.T8Ballastonly) Regressed Aluminum Lens Frame Recessed Fluorescent Troffer

UNVXP2GVA26U AHIExample

Reference data (SB)

Efficiency 84.1% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 58.0W LuminaireEff.(LER) 74.3

Ordering information

Type Size Lamps qty –type Exposed T-Grid

XP Static 2' x 2' 2-TT5

2-T8U6XP2GVA2FT XP2GVA26U

XA Static 2' x 2' 2-TT5

2-T8U6XA2GVA2FT XA2GVA26U

Page 131: Linear recessed and surface lighting

4.128 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Standard

FRX2'x2'Recessed luminaires

TheFRXSeriesoffersanarchitecturallydecorativelightingelementthatwillenhanceyourboardrooms, entrances or executive offices. The 2' x 2' frost white acrylic lens with softly rounded edges provides a luminescent glow of light.

Features•Creativeside-by-sideinstallationscangeneraterows,squares,rectangles,"+"shapes,"T"shapesandothergeometric f igures.

•Illuminatesbothhorizontalandverticalsurfaces.•Lensopensfromeitherside.•Lensutilizesspringloadedlatches/hinge.•5"deepbody.•FixturefitsaStandard15/16"or9/16"T-gridceiling.

Options & accessories page 4.130

Ballast type <10THD <20THD

2 Lamp Elec. T5HO 14/24W PG –2 Lamp Elec. TT5 25/40W IB* SB*2 Lamp Elec. TT5 40W PR** –2 Lamp Elec. TT5 50W – BP2 Lamp Elec. TT5 55W BF –LOL Dimming TT5 – PB1-2 Lamp Elec. T8 HI SOLOL T8 Dimming – PS

* Instant start.

** Program start.

Ordering information

Cat. no. Fixtureefficiency

Lamps type

Lamp watts

FRS2GFW2FTUNVIB FRS2GFW26UUNVHI FRS2GFW224UNVPG FRS2GFW324UNVPG

74.0% 62.2% 66.0% 70.0%

2-TT5 2-6"UT8 2-T5HO 3-T5H0

25W

24W 24W

Family Body style Width Ceiling type Lens style Reflector Lamp qty Lamps Voltage Ballast OptionsFR=FRX S=Static 2 =2Foot G=StandardGrid

15/16"or9/16"ceiling type

F=FrostWhiteAcrylic

W=White 2=2Lamp3=3Lamp

FT=TT56U=6"UT814 =14WT5HO24 =24WT5HO

(Nominal24")

120=120V277=277VUNV=120-277V

See page 4.128 See page 4.128and page 4.130

FR S 2 G F W

Ordering information

24" (610mm)

13�16"(21mm)

5"(127mm)

23-7/8" (606mm) Square Lens

Page 132: Linear recessed and surface lighting

4.129Comprehensive lighting catalog 7th Edition

Standard – Linear recessed and surface lighting

FRX2'x2'Recessed luminaires

Page 133: Linear recessed and surface lighting

Linear recessed and surface lighting

4.130 Philips Lightolier For complete specif ication information visit www.lightolier.com

Options & accessoriesFluorescent lenses, diffusers, louvers and recessed luminaire options

Philips Lightolier Standard Shielding. Extruded virgin acrylic, 3/16"squarebasedfemalecones,running45°tothepaneledge..095"nominalthickness(similartopattern12).

Catalog no. Substitute: SPS2GFS VA 332UNVH3.

Excellentobscurationandcontrol(similartoK12)..125"nominal thickness, extruded virgin acrylic lens, (average weightpersquarefootis7.8ounces).

Catalog no. Substitute: SPS2GFS VY 332UNVH3.

Economy with more rigidity. .125"nominalthickness,extrudedvirginacryliclens, (averageweightpersquarefootis6.8ounces).

Catalog no. Substitute: SPS2GFS VI 332UNVH3.

VA VY VI

Extruded acrylic, square base male conical prism. .156"overallthickness(similartoK19pattern).

Catalog no. Substitute: SPS2GFS KA 332UNVH3.

Injectionmoldedacrylicparaboliclouver,1½"x1½"x1"cell size, with silver specular protected by a clear acrylic.

Catalog no. Substitute: SPS2GFS MC 332UNVH3.

Injection molded polystyrene plastic, parabolic louver. ½"x½"x½"cellsize,withmetallizedspecularf inish.

Catalog no. Substitute: SPS2GFS BP 332UNVH3.

KA MC BP

For additional shieldings, consult your local Philips Lightolier Representative.

PrewiringFF6; FF143/8"factoryprewiredcablewired into fixture. Configurations available in various wire gauges, numbers of wires and lengths up to 6'.

e.g: DPA2G18LS332UNVH3 FF6 (3#18AWGleads,6'long);

e.g: e.g: DPA2G18LS332INVHI FF14 (4#18AWGleads,6'long).

e.g: DPA2G18LS332120SOEM FF92 (5#18AWGleads,6'long).

Job-packedJ =Uncartonedfixturesonpallets are secured by heavy-duty corrugated protectors.

31"x50"x78"

e.g: DPA2G18LS332UNVH3 J

* Consult factory for quantities

Internal fusingA=Internalfast-blowfusing. C =Internalslow-blowfusing.

e.g: SPS2GFSVA332UNVH3 A

Radio frequency shieldingForhospitals,TVstationsorwhereversensitive electronic equipment is in use. Consult factory.

Flange kitAttaches to Philips Lightolier recessed bodies, except XP and XA .

2x4=S2X4FKit 2x2=S2X2FKit 1x4=S1X4FKit see folio OA30-30

For continuous rows, half-width flanges are required between fixtures.

2'=2FCTrim 1'=1FCTrim

Radio interference filterR =Inductivecapacitorcircuitdesigned to minimize interference from line radiation or feedback.

120 or 277 volt at 50 or 60Hz.

e.g: DPA2G18LS332120O3 R (one per fixture R)

e.g: DPA2G18LS332120SO B (one per ballast B)

Fluorescent emergency lighting systemEM =EMFactory-installedemergencypower battery pack with charger and inverter,B100orequal,120Vor277V.

e.g: SPS2GFSVA332120O3 EM

Lamps installedConsult factory after ascertaining wattage, diameter, color rendering, color temperature.

Page 134: Linear recessed and surface lighting

Linear recessed and surface lighting

4.131Comprehensive lighting catalog 7th Edition

M/S intertiesQuick connect interties for master/satellite troffers

Master/satellite troffers are quoted as a single line item, but are shipped as 3 line items to a job, the Master Troffer, the Satellite Troffer and the Intertie. All are bulk packed. This requires writing 3 separate line items. The following is the method for the proper Catalog number.

(1' x 4' 1-LampTroffers)1-2 Lamp BallastXX=All Lamps On

(1' x 4' 2-Lamp Troffers)1-4 Lamp BallastXX=All Lamps On

(2' x 4' 2-Lamp Troffers)1-4 Lamp BallastXX=All Lamps On

(2' x 4' 2-Lamp Troffers)1-2 Lamp Ballast (A)1-2 Lamp Ballast (B)TI =Tandem inline

(2' x 4' 3-Lamp Troffers)1-2 Lamp Ballast (B)1-4 Lamp Ballast (A)IO=Inboard/Outboard Lamps On

(2' x 4' 4-Lamp Troffers)1-4 Lamp Ballast (A)1-4 Lamp Ballast (B)IO=Inboard/Outboard Lamps On

(2' x 2' 3-Lamp Troffers)1-2 Lamp Ballast (B)1-4 Lamp Ballast (A)IO=Inboard/Outboard Lamps On

(2' x 2' 2-Lamp Troffers)1-4 Lamp BallastXX=All Lamps On

ABABABB A AAAAAA B BBB

BB AAAA

Features•Quickconnectplug-in.•Snap-inaccessplateforeasyconnection.•Polarizednylonplugsforpositiveerrorfreeconnections.•90°connectorsfitshallowplenums.•Reducedinstallationlaborcosts.•FitsCF,DP,SP,MP,LC,LI,MB,PP,PR,VP,XP,XAandVRtrofferfamilies.

•Master/satelliterequiresfewerballastsreducingenergy costs.

(1' x 4' 1-LampTroffers)1-2 Lamp BallastXX=All Lamps On

(1' x 4' 2-Lamp Troffers)1-4 Lamp BallastXX=All Lamps On

(2' x 4' 2-Lamp Troffers)1-4 Lamp BallastXX=All Lamps On

(2' x 4' 2-Lamp Troffers)1-2 Lamp Ballast (A)1-2 Lamp Ballast (B)TI =Tandem inline

(2' x 4' 3-Lamp Troffers)1-2 Lamp Ballast (B)1-4 Lamp Ballast (A)IO=Inboard/Outboard Lamps On

(2' x 4' 4-Lamp Troffers)1-4 Lamp Ballast (A)1-4 Lamp Ballast (B)IO=Inboard/Outboard Lamps On

(2' x 2' 3-Lamp Troffers)1-2 Lamp Ballast (B)1-4 Lamp Ballast (A)IO=Inboard/Outboard Lamps On

(2' x 2' 2-Lamp Troffers)1-4 Lamp BallastXX=All Lamps On

ABABABB A AAAAAA B BBB

BB AAAA

(1' x 4' 1-LampTroffers)1-2 Lamp BallastXX=All Lamps On

(1' x 4' 2-Lamp Troffers)1-4 Lamp BallastXX=All Lamps On

(2' x 4' 2-Lamp Troffers)1-4 Lamp BallastXX=All Lamps On

(2' x 4' 2-Lamp Troffers)1-2 Lamp Ballast (A)1-2 Lamp Ballast (B)TI =Tandem inline

(2' x 4' 3-Lamp Troffers)1-2 Lamp Ballast (B)1-4 Lamp Ballast (A)IO=Inboard/Outboard Lamps On

(2' x 4' 4-Lamp Troffers)1-4 Lamp Ballast (A)1-4 Lamp Ballast (B)IO=Inboard/Outboard Lamps On

(2' x 2' 3-Lamp Troffers)1-2 Lamp Ballast (B)1-4 Lamp Ballast (A)IO=Inboard/Outboard Lamps On

(2' x 2' 2-Lamp Troffers)1-4 Lamp BallastXX=All Lamps On

A B A B A B BAA A A A A ABB B B

B BA A A A

M/S IntertiesMaster Satellite for: CF, DP, SP, MP, LC, LI, PP, PR , VP, XP, XA and VR Series

Instant start (1) 2 lamp electronic ballast INT09I2XXXX 2-1LampsUnits 9'length INT11I2XXXX 2-1LampsUnits 11'length

Instant start (1) 4 lamp electronic ballast INT09I4XXXX 2-2LampsUnits 9'length INT11I4XXXX 2-2LampsUnits 11'length

Instant start (1) 4 lamp and 2 lamp electronic ballast INT09I42XIO 2-3LampsUnits 9'length INT11I42XIO 2-3LampsUnits 11'length

Program start (1) 2 lamp electronic ballast INT09P2XXXX 2-1LampsUnits 9'length INT11P2XXXX 2-1LampsUnits 11'length

Program start (1) 4 lamp electronic ballast INT09P4XXXX 2-2LampsUnits 9'length INT11P4XXXX 2-2LampsUnits 11'length

Instant start (2) 2 lamp electronic ballast for tandem Inline INT09I22XTI 2-2LampsUnits 9'length INT11I22XTI 2-2LampsUnits 11'length

Program start also available in tandem inline replace I with P (e.g: INTO9P22XT I ).

Typical Master Troffer Catalog no. (e.g:DeepcelFamily=DPA2G18LS332120SO2XX)

Master/Satellite troffer layouts

Lamp Lamp Ballast Ballast Qty Type Voltage Type Qty (1'x4'only) 2=2Lamp 32=T8 120=120V SO=20THD 2X=1-2Lamp(2'x2'/2'x4') 3=3Lamp 277=277V HI=10THD 22=2-2Lamp 4=4Lamp 4X=1-4Lamp 42=1-2Lamp&1-4Lamp (ISonly) 44=2-4Lamp (ISonly)

DPA2G18LS

Typical Satellite catalog no. (e.g:DeepcelFamily=DPA2G18LS332XXXSO42X)

No Ballast in Must match ballast quantity Ballast master troffer code in master troffer SO=20THD Catalog number HI=10THD

DPA2G18LS

Page 135: Linear recessed and surface lighting

4.132 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Wal-Lyter high performance 2' & 4'Recessed wall washer/accent luminaires

Wal-Lyter is a high performance wall-washer that delivers an exceptionally even wash of light fromtheceilinglinetothefloorlineutilizingTT5(BiaxType)compactfluorescentlamps.Itismuch more efficient and more cost effective than most incandescent units producing equivalent illumination. Wal-Lyter is ideal for highlighting merchandise displays, brightening the walls in offices illuminating with sharp cut-off parabolics and for many other wall lighting applications.

Features•Lowiridescentspecularreflectorsystemforprecise

controlled light output.•Evenlylightsverticalsurfacesordisplays.•87%energysavingsvs.incandescent.•1,250lumen(18watt),3150lumen(40watt)Biaxtype

lamp requires fewer fixtures to provide the same wall illumination as a 60 watt incandescent wallwasher.

•20,000hourslampliferequireslessmaintenancethanincandescent wallwasher.

•Fitsalllay-ingridceilingsystems.•One-piecebodyandintegralhangerforeasy,

quick installation.•UL-Listedaccessplate.•MeetsNYCCoderequirements.•WLRKlens,extrudedacrylic(similartoK19pattern),

see page 4.130.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)

and type and add as suffix, e.g. 120SB.

Ballast type

Electronic PowerSpec HDF dimming

18W TT5 BA 40W TT5 PB24W TT5 BB40W TT5 IB*, PR**50W TT5 BE 55W TT5 BF

* Instant start.

** Program start.Drywall kit: Catalog no. WL2DF/UNV with 2' f ixtures and WL4DF/UNV with 4' f ixtures.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Radio interference filter: Suffix: R . 120 or 277 volt at 50 or 60Hz. Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Chicago Plenum: Consult factory.

WLRN124UNVPR 2' fixture, 1 lamp 40 watt TT5

10 13�16" (275mm)

10 13�16" (275mm)

7 13�16" (183mm) Opening

7 13�16" (183mm) Opening

4 7�16"(113mm)

4 7�16"(113mm)Lens

Footcandles on wall: Fixtures3feetfromwalltooutsidetrimonlampsideoff ixture(withoutlens)

Individual Wal-Lyter Multiple Units 0' 1' 2' 3' 4' 5' 6' 7' 8' 4' 6' Ceiling 8' 76 67 46 25 14 8 5 4 3 107 104 102 104 107 86 79 63 50 63 79 86 7' 64 60 46 29 17 10 7 5 4 102 104 106 104 102 78 75 67 58 67 75 78 6' 47 44 36 24 17 12 8 6 4 85 86 88 86 85 63 62 57 48 57 62 63 5' 33 34 29 24 14 10 8 6 5 66 74 74 74 66 49 50 48 48 48 50 49 4' 26 28 23 20 14 11 8 6 5 59 65 62 65 59 42 45 42 40 42 45 42 3' 19 21 20 17 12 9 8 6 5 48 53 56 53 48 35 36 37 34 37 36 35 2' 15 16 15 13 11 9 8 6 5 42 44 46 44 42 31 31 31 26 31 31 31 1' 13 12 11 11 10 8 7 6 5 38 37 36 37 38 28 26 26 22 26 26 27 Floor

Ordering informationLamps

qty –typeLamp watts

No lens cat. no.

With lens cat. no.

1-TT5

18W24W40W50W55W

WLRN121 WLRN122 WLRN124 WLRN125 WLRN126

WLRK121 WLRK122 WLRK124 WLRK125 WLRK126

NominalLength24"Units

WLRN244UNVPR 4' fixture, 2 lamp 40 watt TT5

10 13�16" (275mm)

10 13�16" (275mm)

7 13�16" (183mm) Opening

7 13�16" (183mm) Opening

4 7�16"(113mm)

4 7�16"(113mm)Lens

Footcandles on wall fixtures: 3 feet from wall tooutsidetrimonlampsideoff ixture(withoutlens)

Individual Wal-Lyter 0' 1' 2' 3' 4' 5' 6' 7' 8' Ceiling 8' 111 101 75.5 47.8 28.3 18.1 13.2 10.4 8.7 7' 113 104 81.7 55.7 35.5 23.5 16.6 12.5 9.8 6' 86.4 81.0 66.9 49.8 34.8 24.6 17.7 13.4 10.4 5' 62.5 59.1 51.4 41.6 31.9 24.3 18.4 13.9 10.7 4' 50.5 48.6 42.9 35.6 28.7 22.6 18.0 14.3 11.1 3' 39.7 38.5 34.9 30.0 25.1 20.6 16.9 14.1 11.4 2' 31.1 30.3 28.1 25.0 21.7 18.5 15.7 13.4 11.1 1' 24.2 23.6 22.5 20.8 18.7 16.6 14.6 12.8 11.0 Floor

Ordering informationLamps

qty –typeLamp watts

No lens cat. no.

With lens cat. no.

2-TT5

18W24W40W50W55W

WLRN241 WLRN242 WLRN244 WLRN245 WLRN246

WLRK241 WLRK242 WLRK244 WLRK245 WLRK246

NominalLength48"Units

Wal-Lyter Voltage Ballast Options High Performance 120=120V Seepage4.132 See page 4.132 Wall Washer 277=277V andpage4.130 UNV=120-277V

UNVWLRN124 APRExample

Integral hanger fixture: installs easily with adjustable integral hanger that clamps to T bar. Wire fixture through access plate without opening lamp compartment.

WLRN241UNVPR10 13�16" (275mm)

10 13�16" (275mm)

7 13�16" (183mm) Opening

7 13�16" (183mm) Opening

4 7�16"(113mm)

4 7�16"(113mm)Lens

Ordering informationLamps

qty –typeLamp watts

No lens cat. no.

With lens cat. no.

2-TT5Twin tube 18W

WLRN241 –

– WLRK241

NominalLength48"Units

30˚

60˚600

1200

1800

Candlepower Curve

30˚

60˚1200

2400

3600

Candlepower Curve

30˚

60˚1200

2400

3600

Candlepower Curve

Page 136: Linear recessed and surface lighting

4.133Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Individual Wal-Lyter 0' 1' 2' 3' 4' 5' 6' 7' Ceiling 8' 49 38 21 12 8 5 4 3 7' 49 42 29 18 12 8 6 4 6' 36 33 25 18 12 8 6 5 5' 27 25 21 16 12 9 7 5 4' 21 20 17 14 11 8 7 5 3' 16 16 14 12 9 8 6 5 2' 13 13 12 10 9 7 6 5 1' 11 10 10 9 8 6 6 5 Floor

WMRL124UNVPR 2' fixture, 1 lamp 40 watt TT5

Ordering informationLamps

qty –typeLamp watts

Catalog number

1-TT5

18W24W40W50W55W

WMRL121 WMRL122 WMRL124 WMRL125 WMRL126

NominalLength24"Units

Walmaster 2' & 4'Recessed wall washer/accent luminaires

Walmaster is a high performance luminaire with low-iridescence semi-specular reflectors that do not protrude below the ceiling line. This provides a clean appearance whilecontrollingthelightoutputofaT8orTT5(twintube)lamptoilluminateverticalsurfaces uniformly.

Features•Lowiridescentspecularreflectorsystemfor

precise controlled light output.•Evenlylightsverticalsurfacesordisplays(noscallops).•87%energysavingsvs.incandescent.•Lessthan3:1maximumtominimumwallillumination

when installed 6 feet on center.•20,000hourslampliferequireslessmaintenancethan

incandescent.•Noedgesprotrudebelowceilingline.•Canbeinstalledonly2feetfromwalltofarthestedgeof f ixture(3'maximum).

•Fitsallstandardandnarrowgridceilingsystems.•One-piecebodyandintegralhangerforeasy,

quick installation.•Sidesoff ixturecansupporttileorsitonT-bar.•ULListedaccessplate.•MeetsNYCCoderequirements.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)

and type and add as suffix, e.g. 120SB.

Ballast type

Electronic PowerSpec HDF dimming

18W TT5 BA 40W TT5 PB24W TT5 BB T8 PS†

40W TT5 IB*, PR** 50W TT5 BP55W TT5 BFT8 HI*

* Instant start. † 4' unit only

** Program start.

Drywall kit: Catalog no. WL2DF/UNV with 2' f ixtures and WL4DF/UNV with 4' f ixtures.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

24" (610mm) 7 ⅞"(178mm)

4 7�16"(113mm)

24" (610mm) 7 ⅞"(178mm)

4 7�16"(113mm)

WMRL244UNVPR 4' fixture, 2 lamp 40 watt TT5

48" (1220mm)7 ⅞" (178mm)

4 7�16"(113mm)

48" (1220mm) 48" (1220mm)7 ⅞" (178mm)

4 7�16"(113mm)

48" (1220mm)

Ordering informationLamps

qty –typeLamp watts

Catalog number

2-TT5

18W24W40W50W55W

WMRL241 WMRL242 WMRL244 WMRL245 WMRL246

NominalLength48"Units

Individual Wal-Lyter 0' 1' 2' 3' 4' 5' 6' 7' 8' Ceiling 8' 116 88 51 30 19 13 13 10 8 7' 119 102 71 45 29 19 19 14 11 6' 92 83 64 45 31 22 22 16 12 5' 69 64 53 40 30 22 22 16 13 4' 52 50 43 35 27 21 21 17 13 3' 40 39 35 30 24 19 19 16 13 2' 32 31 29 25 21 17 17 15 12 1' 26 25 23 21 18 15 15 13 12 Floor

WMRL143UNVHI 4' fixture, 1 lamp 32 watt T8

48" (1220mm) 7 ⅞" (178mm)

4 7�16"(113mm)

48" (1220mm) 48" (1220mm) 7 ⅞" (178mm)

4 7�16"(113mm)

48" (1220mm)

Ordering informationLamps

qty –typeLamp watts

Catalog number

1-T8 32W WMRL143

NominalLength48"Units

Drywall kit:

WL2DF/UNV with 2' f ixtures

WL4DF/UNV with 4' f ixtures

Integral Hanger Fixture: installs easily with adjustable integral hanger that clamps to T bar. Wire fixture through access plate without opening lamp compartment.

Walmaster Voltage Ballast Options High Performance 120=120V Seepage4.133 See page 4.133 Wall Washer 277=277V andpage4.130 UNV=120-277V

UNVWMRL124 APRExample

30˚

60˚600

1200

1800

Candlepower Curve

30˚

60˚1200

2400

3600

Candlepower Curve

30˚

60˚550

1100

1650

Candlepower Curve

Page 137: Linear recessed and surface lighting

4.134 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Bi-lyter2'&4'Surface wall washer or indirect wall mount luminaires

Features•Samefixturecanbeusedasawallwasherwhenceiling

mounted, or for indirect lighting when wall mounting.•Only4"deep.•MeetsADAwhenwallmounted.•Softroundedcornersandedgescreatean

elegant appearance.•20gaugecoldrolledsteelbody.•Specularreflector.•Novisiblehardware.•4'unit2-TT5or1-T8lamp.•2'unitTT5lamp.•Flatwhitebakedacrylicf inish(standard).•Canbeusedincontinuousrows.Consult factory.•MeetsNYCCoderequirements.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

TT5 IB* SBT8 HI* SO*

* 4' unit only

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Wall mount spacer: Order BL spacer. For uneven walls or a floating visual effect. Continuous row coupler: Order BL coupler.T-Grid mounting: Order BL mount.

BLSF124120SB

4 "(102mm)

4 ⅜" (111mm)

Ceiling Ordering information

Length Lamps qty –type

Lamp watts

Catalog number

24" 1-TT5

18W24W40W50W55W

BLSF121 BLSF122 BLSF124 BLSF125 BLSF126

48" 2-TT5

18W24W40W50W55W

BLSF241 BLSF242 BLSF244 BLSF245 BLSF246

48" 1-T8 32W BLSF143

30˚

60˚400

800

Candlepower Curve

Bi-lyter Voltage Ballast Options Surface Wall or 120=120V Seepage4.134 See page 4.134 Ceiling Mounted 277=277V andpage4.130 UNV=120-277V

120BLSF124 ASBExample

For f lat white f inish order BLSF. (e.g: BLSF126120SB)

Wall washer

Indirect wall mount

4 "

(102mm)

4 ⅜" (111mm)

4"(102mm)

4 ⅜"(111mm)

Wall

Footcandles on wall: Fixtures3feetfromwalltooutsidetrimonlampsideoff ixture(WallWasher)

Individual Wal-Lyter Multiple Units Continuous Row 0' 1' 2' 3' 4' 5' 6' 7' 8' 4' 6' 0' 1' 2' 3' 4' 5' 6' 7' 8' Ceiling 8' 4 5 6 9 14 25 46 72 86 100 98 92 98 100 93 82 60 50 60 82 93 157 184 199 204 207 204 199 184 157 7' 4 5 6 9 14 24 40 60 70 83 84 81 84 83 76 69 54 47 54 69 76 134 158 170 176 178 176 170 158 134 6' 4 5 6 9 13 20 31 42 47 59 63 63 63 59 53 51 44 41 44 51 53 101 118 128 134 135 134 128 118 101 5' 4 5 6 7 10 16 22 27 30 40 43 43 43 40 35 35 32 31 32 35 35 71 82 89 93 94 93 89 82 71 4' 3 4 5 6 8 10 13 15 17 24 26 26 26 24 21 21 21 21 21 21 21 45 51 55 57 58 57 55 51 45 3' 3 3 4 5 6 7 8 9 9 15 16 16 16 15 13 14 14 14 14 14 13 30 33 35 36 36 36 35 33 30 2' 3 3 3 4 4 5 5 6 6 10 10 11 10 10 9 9 9 9 9 9 9 21 23 24 25 25 25 24 23 21 1' 2 3 3 3 3 4 4 4 4 8 8 8 8 8 7 7 7 7 7 7 7 17 17 18 18 19 18 18 17 17 Floor

Small office application

OnlyfourBy-Lyters55wattlampare required to illuminate a 12' x 12' (80/80/50)officespaceto50maintainedfootcandles with only 1.68 watts per square foot.

Luminaire:mounted18"from ceiling 12' x 12' Office Space with a 9' Ceiling Height

Reflectance: 80% Ceiling, 80% Wall, 50% Floor.

Reported numbers are maintained footcandles at desk top level with 55 watt lamp. Footcandle readings will vary depending on room reflectance.

6 11�16"(170mm) 8 ¾" (222mm)

⅞" (22mm) Dia K.O.

9�32" (7mm) Mounting Hole

25 15�16" (659mm)

4 ⅜"(111mm)

⅞" (22mm) Dia K.O. 9 15�16" (252mm) Mounting Holes

22 13�16" (579mm)49 15�16" (1268mm)

10" (254mm)20 ⅛" (511mm)

4 ⅜"(111mm)

2" Unit

4" Unit

Page 138: Linear recessed and surface lighting

4.135Comprehensive Lighting Catalog 7th Edition

MD*4 & MD*2 > 4.138 MD* Coffer > 4.140 MD*A Assymetric > 4.142 OBL&SUS432/632 > 4.144

Contents

Medical luminaires

Page 139: Linear recessed and surface lighting

4.136 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Medical luminairesHospital patient room lighting

Philips Lightolier’s MD* series luminaires combine all of the lighting functions in a patient’s room into a single, ceiling-mounted luminaire. Removing lighting from walls and other locations where it may be interfering with equipment and prone to damage. It supports a friendly and more residential design for the entire room.

MD*4 installs at the edge of the ceiling and provides ambient, reading, examination, and night lighting – all from carefully shielded sources. MD*Coffer installs12-18"fromthewallandprovidesthe same lighting functions, using an indirect coffer for the ambient and reading light.

Page 140: Linear recessed and surface lighting

4.137Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Medical luminairesHospital patient room lighting

•Indirectambientlightwithperforatedmesh shield.

•Fourintegrallightingfunctions:indirectambient, direct reading, examination and optional night light.

•Installsasaone-pieceunit.

•Preciselightcontrolforglare-freepatient environment.

•Recessedorsurfacemountedtoceilingwhich eliminates damage to fixture from hospital equipment attached to patient's bed.

•Optionallowvoltageelectronicsequential switch mounted in fixture for ambient and reading light controlled withpillowspeaker(optionalbyothers).

•MeetsNYCCoderequirements.Chicago Plenum requirements available.

.•6⅞"deep.•Alllampsareshielded.•AlltwintubeT5lampsareaccessible

for relamping without tools.

•Fourlightingfunctionswithintegralambient, reading, examination and optional night light.

•Installsasaone-pieceunit.•Preciselightcontrolforglarefree

patient environment.•Recessedorsurfacemountedtoceiling

against wall directly behind patient which eliminates damage to fixture from hospital equipment attached to patients bed.

•Optionallowvoltageelectronicsequential switch mounted in fixture for ambient and reading light controlled withpillowspeaker(optionalbyothers).

•MeetsNYCCoderequirements. Chicago Plenum requirements available.

•6⅞"deep.•Alllampsareenclosed.•AlltwintubeT5lampsareaccessible

for relamping without tools.

MD*4 Series

MD* Coffer

MD*4 Style 3 (AWoption)

All components whiteFor single patient room

MD* Coffer style

MD*4 Style 2(FFoption)

White louver and horizontal surfaces to blend with ceilingFor multiple patient room

LightedZone

LightedZone

LightedZone

LightedZone

Optional LED Night LightNight Light:120Vor277V,3watt,coolwhiteLED(50,000hourslife-suppliedwithfixture).

Suffix: LD (available on MD*4only).

LightedZone

ShieldedZoneLighted

Zone

ShieldedZone

Page 141: Linear recessed and surface lighting

4.138 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•2x4Unithasfourlightingfunctionswithintegral

ambient, reading, examination and optional nurse’s night light.

•Specularaluminumreflectorsforpreciselightcontroland glare free patient environment.

•Installsasaone-pieceunit.Recessedorsurfacemounted to ceiling against wall directly behind patient.

•Eliminatesdamagetoluminairefromhospitalequipmentattached to patient bed.

•6⅞"deep.•Topwiringaccessplateisstandard.•Alllampsareenclosed.•AllTT5typelamps(notincluded)areaccessiblefor

relamping without tools.•Rugged20gaugesteelhousing.•Optionallowvoltage(1-3volts)electronicsequential

switch mounted in luminaire for ambient and reading lightcontrolledwithpillowswitch(byothers).

•ExaminationLightin2x4has36cellspecularaluminumparabolic louver with pattern 12 lens overlay.

Options & accessories Electronic (low voltage) sequential switch: Switch factory mounted in luminaire for ambient and reading light convenience (controlled by pillow switch, by others).Suffix:SW.

Nurse night light:120Vmediumbase,narrowspot,50W PAR 20 reflector lamp included with specular anodized mirror, f ield adjustable to right or left side of patients bed. Suffix: NL .TheLEDNightLight120Volt,3W, cool white LED (50,000 hours life - supplied with f ixture).Suffix:LD

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Fusing: Suffix: A (Internalfast-blowfusing).Tamper proof: Order Germ Shield.Germ shield: Order Cat. no., MD4CLGS24(2x4). Germshield can only be used with recessed MD*4.

48" (1220mm)

Wall angleor T-barby others

Acoustical tile by others

Secure Luminaire(4 Places)

Ceiling

Wall

Wall

48" (1220mm)

6 ⅞"(175mm)

MD*4 2' x 4'

Sequential switch (SW)

Ordering information

Type Cells Examination light shielding

Lamps qty –type* Ballast type Grid ceiling

MD*4 2x4 Ambient, Reading and Examination Light

36 Traditional Specular Louver 6-TT5 5-TT5 40W Electronic MD4GPSVA2SB4SB

MD4GPSVA2SB3SB

36 Louver with all White Components

6-TT5 5-TT5 40W Electronic MD4GAWVA2SB4SB

MD4GAWVA2SB3SB

36 White Louver with White Horizontal Surface

6-TT5 5-TT5 40W Electronic MD4GFFVA2SB4SB

MD4GFFVA2SB3SB

* Include 2-TT5 for ambient / reading section.

MD*4 Voltage Options Options Options Multi-function 120=120V SW=Electronic LD=3WLED Seepage4.138 Examination Luminaire 277=277V SequentialSwitch NursesNightLight

120MD4GPSVA2SB4SB SWExample A

•Excellentcolorrendition. (82 CRI TT5 Type lamp).

•Wiredforindependent switching (1or2circuit).

Numbersinparenthesis()aretotalfootcandle level of ambient and reading lights only.

FootcandlesonBed(withSpecularLouver)(TotalsofAmbient,Reading&Examinationlights)

Reading light•Eliminatesreflectedglarefrom readingmaterial(overthe shoulderillumination).

•Nodirectglaretopatientorvisitors. (7 footcandles maximum at head of bed. 15footcandlesmaximumat footofbed.).

•Controlslightdirectlyontopatients bed.•Noreadinglightspill-overtoadjacent

beds. (1 footcandle maximum at head of adjacentpatient’sbed.)

2 2 2 2 2 2 1 1 1 1 1 1

3 3 3 3 3 2 2 2 1 1 1 1

6 7 7 7 6 4 3 3 2 2 1 1

33 38 39 38 33 23 16 12 9 5 3 2

30 38 38 38 30 23 15 12 8 6 3 2

14 15 15 15 14 11 9 7 5 4 2 2

5 5 5 5 5 5 4 4 2 2 1 1

BED

WALLReading Light/On3"

6"

Adjacent MD*4 Off

BED12"

3"

6"

12"

FootcandlesonBeds(Horizontal)

Illumination at the reading task ranges 50-80 footcandles.

Examination light

MD*4 series 2' x 4'Multi-function patient room luminaire (ambient/reading/examination/nurse’s night light)

MD*4 combines all of the lighting functions in a patient’s room in a single luminaire that is ceiling mounted to permit clean headwalls. This enables architects and interior designers to create a more home-like environment and moves the light luminaire off the wall, a location where it can be damaged easily or interfere with medical equipment. MD*4 is more efficient and more economical than all other patient lighting systems.

Page 142: Linear recessed and surface lighting

4.139Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

MD*2 series 2' x 2'Multi-function patient room luminaire (ambient/reading/nurse’s night light)

MD*4 combines all of the lighting functions in a patient’s room in a single luminaire that is ceiling mounted to permit clean headwalls. This enables architects and interior designers to create a more home-like environment and moves the light luminaire off the wall, a location where it can be damaged easily or interfere with medical equipment. MD*4 is more efficient and more economical than all other patient lighting systems.

Features•2x2Unithasthreelightingfunctionswithintegral

ambient, reading, and optional nurse’s night light.•Specularaluminumreflectorsforpreciselightcontrol

and glare free patient environment.•Installsasaone-pieceunit.Recessedorsurface

mounted to ceiling against wall directly behind patient.•Eliminatesdamagetoluminairefromhospitalequipment

attached to patient bed.•6⅞"deep.•Topwiringaccessplateisstandard.•Alllampsareenclosed.•AllTT5typelamps(notincluded)areaccessiblefor

relamping without tools.•Rugged20gaugesteelhousing.•Optionallowvoltage(1-3volts)electronicsequential

switch mounted in luminaire for ambient and reading lightcontrolledwithpillowswitch(byothers).

Options & accessories Electronic (low voltage) sequential switch: Switch factory mounted in luminaire for ambient and reading light convenience (controlled by pillow switch, by others).Suffix:SW.

Nurse night light:120Vmediumbase,narrowspot,50W PAR 20 reflector lamp included with specular anodized mirror, f ield adjustable to right or left side of patients bed. Suffix: NL .TheLEDNightLight120Volt,3W, cool white LED (50,000 hours life - supplied with f ixture).Suffix:LD

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Fusing: Suffix: A (Internalfast-blowfusing).Tamper proof: Order Germ Shield.Germ shield: Order Cat. no., MD4CLGS22(2x2). Germshield can only be used with recessed MD*2 .

Sequential switch (SW)

Ordering information

Type Lamps qty –type Ballast type Grid ceiling

MD*2 2x2 Ambient and Reading Light

2-TT5 40W Electronic MD2G2SB

Reading light•Eliminatesreflectedglarefromreadingmaterial(overthe shoulder illumination).

•Nodirectglaretopatientorvisitors. (7 footcandles maximum at head of bed. 15footcandlesmaximumat footofbed.).

•Controlslightdirectlyontopatients bed.•Noreadinglightspill-overtoadjacent

beds. (1 footcandle maximum at head of adjacentpatient’sbed.)

2 2 2 2 2 2 1 1 1 1 1 1

3 3 3 3 3 2 2 2 1 1 1 1

6 7 7 7 6 4 3 3 2 2 1 1

33 38 39 38 33 23 16 12 9 5 3 2

30 38 38 38 30 23 15 12 8 6 3 2

14 15 15 15 14 11 9 7 5 4 2 2

5 5 5 5 5 5 4 4 2 2 1 1

BEDIlluminating at the reading task ranges 50-60 footcandles

WALLReading Light/On3"

6"

Adjacent MD*4 Off

BED12"

3"

6"

12"

FootcandlesonBeds(Horizontal)

Ambient light•Indirectilluminationfromwall

directly behind patient provides glare-free lighting.

•Nodirectglaretopatient(Lightisdirectedtowardswall).

•Nodirectglaretopatientsvisitor.•Nodirectglaretoadjacentpatients.

(3 footcandles maximum on wall behindadjacentpatient’sbed.)

Ambient Light/On Adjacent MD*4/Off

Reading Light/On Adjacent MD*4/Off

MD*2 Voltage Options Options Options Multi-function 120=120V SW=Electronic LD=3WLED Seepage4.139 Patient Luminaire 277=277V SequentialSwitch NursesNightLight

120MD2G2SB SWExample A

6 ⅞"(175mm)

24" (610mm)24" (610mm)

Wall angleor T-barby others

Acoustical tileby others

Ceiling

Wall

Wall

Secure Luminaire(4 Places)

MD*2 2' x 2' 2 types of lighting: ambient & reading

Illumination at the reading task ranges 50-80 footcandles.

Page 143: Linear recessed and surface lighting

4.140 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•2x4Unithasfourlightingfunctionswithintegral

ambient, reading, examination and optional nurse’s night light.

•Specularaluminumreflectorsforpreciselightcontroland glare free patient environment.

•Installsasaone-pieceunit.Recessedorsurfacemounted to ceiling against wall directly behind patient.

•Eliminatesdamagetoluminairefromhospitalequipmentattached to patient bed.

•Topwiringaccessplateisstandard.•AllTT5typelamps(notincluded)areaccessiblefor

relamping without tools. All lamps are enclosed.•Rugged20gaugesteelhousing.•Optionallowvoltage(1-3volts)electronicsequential

switch mounted in luminaire for ambient and reading lightcontrolledwithpillowswitch(byothers).

•ExaminationLightin2x4has36cellf latwhitebakedenamel louver with pattern 12 lens overlay.

•Perforatedmeshshieldforambient/readingsection.

Options & accessories 277V:Change120to277(e.g.MDCGWSVA2SB4SB120, changestoMDCGWSVA2SB4SB277).

Electronic (low voltage) sequential switch: Switch factory mounted in luminaire for ambient and reading light convenience (controlled by pillow switch, by others).Suffix:SW.

9/7 Watt night light: Suffix: PL(Lampnotincluded).

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Fusing: Suffix: A (Internalfast-blowfusing).Tamper proof: Order Germ Shield.Germ shield: Order Cat. no., MD4CLGS24(2x4). Germshield can only be used with recessed MD* Coffer.

MD*Coffer 2' x 4'

Sequential switch (SW)

Ambient light•IndirectilluminationfromTT5shielded

by perforated mesh shield with white acrylic overlay.

•Nodirectglaretopatient.•Nodirectglaretopatientsvisitor.•Nodirectglaretoadjacentpatients.

LightedZone

14 15 15 14 12 12 7

14 16 16 14 12 12 8

14 15 15 14 12 12 7

12"

6" 12"

3"from

Wall

FootcandlesonBed

Bed

17 21 23 28 33 6 5

18 22 24 29 35 6 5

17 21 23 28 33 6 5

12"

6" 12"3"from

Wall

FootcandlesonBed

Bed

Illumination at the reading task ranges 45-50 footcandles.

Ordering information

Type Cells Examination light shielding

Lamps qty –type* Ballast type Grid ceiling

MD* Coffer 2x4 Ambient, Reading and Examination Light

36 White Louver with Prismatic Overlay

6-TT5 5-TT5 40W Electronic MDCGWSVA2SB4SB

MDCGWSVA2SB3SB

* Include 2-TT5 for ambient / reading section.

MD* Coffer 2x4 Voltage Options Options Options Multi-function 120=120V SW=Electronic PL =Nurses Seepage4.140 Examination Luminaire 277=277V SequentialSwitch NightLight

120MDCGWSVA2SB4SB PLSWExample A

Reading light•Eliminatesreflectedglarefromreadingmaterial(overshoulderillumination).

•Nodirectglaretopatientorvisitors.•Controlslightdirectlyontopatient’sbed.

LightedZone

Examination light•Excellentcolorrendition.Wiredforindependentswitching(1or2circuit).

•Optionallouverorlensframe.•Concealedhingingand latching.

LightedZone 68 85 93 99 100 65 49

(31)(36)(38)(42)(45)(18)(12)

73 89 99 104 106 68 53 (32)(38)(40)(43)(47)(18) (13)

68 85 93 99 100 65 49 (31)(36)(38)(42)(45)(18)(12)

12"

6" 12"

3"from

Wall

FootcandlesonBed

Bed

Numbersinparenthesis()aretotalfootcandle level of ambient and reading lights only.

48" (1220mm)

6 ⅞"(175mm)

Wall

Mount12" - 18"from wall

Mount12" - 18"from wall

9'6" max.mounting height

Ceiling

Wall angleor T-barby others

Acoustical tile by others

48" (1220mm)Wall

Secure Luminaire(4 Places)

MD* Coffer 2' x 4'Multi-function patient room luminaire (ambient/reading /examination /nurse’s night light)

MD* Coffer combines all of the lighting functions in a patient’s room in a single luminaire that is ceiling mounted to permit clean headwalls. This enables architects and interior designers to create a more home like environment and moves the light luminaire off the wall, a location where it can be damaged easily or interfere with medical equipment. MD*Coffer is more efficient and more economical than all other patient lighting systems.

Page 144: Linear recessed and surface lighting

4.141Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

MD* Coffer 2' x 2'Multi-function patient room luminaire (ambient/reading /nurse’s night light)

MD* Coffer combines all of the lighting functions in a patient’s room in a single luminaire that is ceiling mounted to permit clean headwalls. This enables architects and interior designers to create a more home like environment and moves the light luminaire off the wall, a location where it can be damaged easily or interfere with medical equipment. MD*Coffer is more efficient and more economical than all other patient lighting systems.

MD*Coffer 2' x 2' 2 types of lighting: ambient & reading

Nightlight(optional)•Indirect9or7wattPLlampshielded

by perforated mesh with internal white acrylic overlay.

•Noglaretoanypatient.•Wiredforindependentswitching.

Ambient light

Reading light•Eliminatesreflectedglarefromreadingmaterial(overshoulderillumination).

•Nodirectglaretopatientorvisitors.•Controlslightdirectlyontopatient’sbed.

•IndirectilluminationfromTT5shieldedby perforated mesh shield with white acrylic overlay.

•Nodirectglaretopatient.•Nodirectglaretopatientsvisitor.•Nodirectglaretoadjacentpatients.

LightedZone

LightedZone

14 15 15 14 12 12 7

14 16 16 14 12 12 8

14 15 15 14 12 12 7

12"

6" 12"

3"from

Wall

FootcandlesonBed

Bed

17 21 23 28 33 6 5

18 22 24 29 35 6 5

17 21 23 28 33 6 5

12"

6" 12"

3"from

Wall

FootcandlesonBed

Bed

Illumination at the reading task ranges 45-50 footcandles.

3 4 3 3 2 2 1

3 4 3 3 2 2 1

3 4 3 3 2 2 1

12"

6" 12"

3"from

Wall

FootcandlesonBed

Bed

Features•2x2Unithasthreelightingfunctionswithintegral

ambient, reading, and optional nurse’s night light with perforated mesh shield.

•Specularaluminumreflectorsforpreciselightcontroland glare free patient environment.

•Installsasaone-pieceunit.Recessedorsurfacemounted to ceiling against wall directly behind patient.

•Eliminatesdamagetoluminairefromhospitalequipmentattached to patient bed.

•Topwiringaccessplateisstandard.•AllTT5typelamps(notincluded)areaccessiblefor

relamping without tools. All lamps are enclosed.•Rugged20gaugesteelhousing.•Optionallowvoltage(1-3volts)electronicsequential

switch mounted in luminaire for ambient and reading lightcontrolledwithpillowswitch(byothers).

•Perforatedmeshshieldforambient/readingsection.

Options & accessories 277V:Change120to277(e.g.MDCGWSVA2SB4SB120, changestoMDCGWSVA2SB4SB277).

Electronic (low voltage) sequential switch: Switch factory mounted in luminaire for ambient and reading light convenience (controlled by pillow switch, by others).Suffix:SW.

9/7 Watt night light: Suffix: PL(Lampnotincluded).

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Fusing: Suffix: A (Internalfast-blowfusing).Tamper proof: Order Germ Shield.Germ shield: Order Cat. no., MD4CLGS22(2x2). Germshield can only be used with recessed MD* Coffer.

Sequential switch (SW)

6 ⅞"(175mm)

24" (610mm)

Wall angleor T-barby others

Wall Ceiling

Mount12" - 18"from wall

Mount12" - 18"from wall

9'6" max.mounting height

Secure Luminaire(4 Places)

Acoustical tileby others

24" (610mm)Wall

Ordering information

Type Lamps qty –type* Ballast type Grid ceiling

MD* Coffer 2x2 Ambient, Reading 2-TT5 40W Electronic MDCG2SB

MD* Coffer 2x2 Voltage Options Options Options Multi-function 120=120V SW=Electronic NL =Nurses Seepage4.141 Patient Luminaire 277=277V SequentialSwitch NightLight

120MDCG2SB PLSWExample A

Page 145: Linear recessed and surface lighting

4.142 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

MD*A6"x48"Recessed fluorescent multi-function patient luminaire asymmetric examination and ambient lighting

With the ever-increasing amounts of medical equipment needing headwall space and an overall desire to create a comforting, home-like environment, the Philips Lightolier MD*A meets these challenges.

The Philips Lightolier MD*A offers three integral lighting functions: ambient light, examination light and an optional wall switch controlled night light. The ambient light provides a soft level of light that is perfect for general illumination. The examination light produces shadow-free illumination over the entire bed. When these two modes are switched on simultaneously, very high light levels are achieved, up to 120 footcandles.

Ideally installed in opposing pairs over the bed. The Philips Lightolier MD*A can be ordered as two individual luminaires for wall switch operation. Or as Master and Satellite luminaires utilizing our optional sequential switch, giving the patient the ability to control the aforementioned functions from a pillow switch.

Ordering informationExplanation of Individual MD*A luminaire Catalog number. Example: MDA6G254117120PGP2

MD*Asymmetric Fixture width Ceiling type Exam lamp Ambient lamp Voltage Exam ballast Ambient ballast

MDA 6 G 254 117 120 PG P2

Explanation of Master MD*A luminaire Catalog number with sequential switch. Example: MDA6G254117120PGP2-SW

MD*Asymmetric Fixture width Ceiling type Exam lamp Ambient lamp Voltage Exam ballast Ambient ballast Sequence switch

MDA 6 G 254 117 120 PG P2 SW

Explanation of Satellite MD*A luminaire Catalog number with sequential switch. Example: MDA6G254117120PGXX-SW

MD*Asymmetric Fixture width Ceiling type Exam lamp Ambient lamp Voltage Exam ballast Ambient ballast Satellite Sequence switch

MDA 6 G 254 117 120 PG P2 XX SW

Page 146: Linear recessed and surface lighting

4.143Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Only available in the Individual or Satellite luminaire. Suffix: NL .

MD*A6"x48"Recessed fluorescent multi-function patient luminaire asymmetric examination and ambient lighting

Ambient lightIndirect illumination from either two 17W T8 or two 24 watt T5HO two foot lamps.

•Nodirectglaretopatient.•Nodirectglaretopatient'svisitor.•Lowlevelofilluminationcomfortable

for visitors or viewing television.

Examination lightExcellent color rendition given by four 54 watt T5HO lamps.

•Wiredfortandemswitching.

Ambient and examination lightFull light level output.

•Lensencloseslampswithinluminaire.

Two 17W T8 Lampsfootcandle levels*

Four 54W T5HO Lampsfootcandle levels*

Two 17W T8 Lamps and Four 54 Watt T5HO Lamps, footcandle levels*

7

9

10

10

8

8

10

10

9

7

8

10

11

10

8

79

100

106

99

79

79

99

106

100

79

84

106

114

106

84

82

101

108

101

80

80

101

108

101

82

89

108

117

108

88

Two 24W T5HO Lampsfootcandle levels*

Four 54W T5HO Lampsfootcandle levels*

Two 24W T5HO Lamps and Four 54 Watt T5HO Lamps, footcandle levels*

10

13

15

15

12

12

15

15

13

10

11

15

16

15

11

79

100

106

99

79

79

99

106

100

79

84

106

114

106

84

85

104

111

106

86

86

106

111

104

85

92

111

120

110

92

Two 17W T8 Lampsfootcandle levels*

Four 54W T5HO Lampsfootcandle levels*

Two 17W T8 Lamps and Four 54 Watt T5HO Lamps, footcandle levels*

7

9

10

10

8

8

10

10

9

7

8

10

11

10

8

79

100

106

99

79

79

99

106

100

79

84

106

114

106

84

82

101

108

101

80

80

101

108

101

82

89

108

117

108

88

Two 24W T5HO Lampsfootcandle levels*

Four 54W T5HO Lampsfootcandle levels*

Two 24W T5HO Lamps and Four 54 Watt T5HO Lamps, footcandle levels*

10

13

15

15

12

12

15

15

13

10

11

15

16

15

11

79

100

106

99

79

79

99

106

100

79

84

106

114

106

84

85

104

111

106

86

86

106

111

104

85

92

111

120

110

92

Two 17W T8 Lampsfootcandle levels*

Four 54W T5HO Lampsfootcandle levels*

Two 17W T8 Lamps and Four 54 Watt T5HO Lamps, footcandle levels*

7

9

10

10

8

8

10

10

9

7

8

10

11

10

8

79

100

106

99

79

79

99

106

100

79

84

106

114

106

84

82

101

108

101

80

80

101

108

101

82

89

108

117

108

88

Two 24W T5HO Lampsfootcandle levels*

Four 54W T5HO Lampsfootcandle levels*

Two 24W T5HO Lamps and Four 54 Watt T5HO Lamps, footcandle levels*

10

13

15

15

12

12

15

15

13

10

11

15

16

15

11

79

100

106

99

79

79

99

106

100

79

84

106

114

106

84

85

104

111

106

86

86

106

111

104

85

92

111

120

110

92

Optional 3 watt LED night light

*Footcandle levels based on an opposing pair of MD*A luminaries.

36"

72"

42"

Ambient

Exam

Exam & Ambient

4 15�16" (126mm)

6" (152mm)

6" (152mm)

5 ¾" (146mm)

20 Gauge steel housing Exam light (2) 54w T5HO

lamps (by others)

Ambient light (1) 17W T8 or 24W T5HO (by others)

Miro 4 reflector

Lens hold down latch

Asymmetric prismatic lens

36"

72"

42"

Ambient

Exam

Exam & Ambient

4 15�16" (126mm)

6" (152mm)

6" (152mm)

5 ¾" (146mm)

20 Gauge steel housing Exam light (2) 54w T5HO

lamps (by others)

Ambient light (1) 17W T8 or 24W T5HO (by others)

Miro 4 reflector

Lens hold down latch

Asymmetric prismatic lens

Page 147: Linear recessed and surface lighting

4.144 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•Fornursinghomes,hospitalsandotherhealth

care facilities.•Separatelampcompartmentsforcontrolled

uplight and downlight.•Four-waypullswitch,standard(120voltonly).•.125thickDRacryliclinearprismaticrefractor. (impactresistant).

•Flatwhitefasciastandard.•Coldrolledsteelbodywithdie-castaluminumends.•Concealedpull-actionspring-loadedlatches

to retain lens.•Optionaloakfasciainsert.•Optionallowvoltageelectronicsequentialswitch

for push button control of up/down lighting. UL 544 listed. Includes phone jack type receptacle.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. 277SO.

Ballast type <10THD <20THD

T8 HI PS

6 1�16"(154mm)

5 9�16" (141mm)Pull Switch

Switching

4Lamps=1,2,3,4 3Lamps=1,2,4 2Lamps=2,4

30˚60˚

120˚

150˚1000

500

0

500

Candlepower Curve

6'

3'side view

50 FC reading plane(60˚ from horizontal)

3-6' readingplane

Reading Position

Over-Bed Wall Mounted Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.144 See page 4.144 277=277V andpage4.216

120OBL332 RSOExample

Ordering informationLamp Configuration Size Lamp qty –type Catalog no.

2 Up/1 Down2 Up/2 Down1 Up/1 Down

48"3-T84-T82-T8

OBL332OBL432OBL232

Optional fascia insert: Oak—to order substitute K for L in Catalog no. (e.g. OBL332 to OBK332).

Momentary button cordset: Traditional “Winged” Pendant Design ESD protection to 15000 volts. Heavy duty7"cable.Consult factory.

Nite light: Consult factory.

Radio interference filter: Suffix: R . 120 or 277 volt at 50 or 60Hz. Electronic (low voltage) sequential switch: Switch factory mounted in fixture for Up and Down Light Operation from pillow switch, UL544 listed. Includes phone jack type receptacle. Consult factory. (120Vor277V).

OBLOver-bedlight

Features•2unitsprovide123averagefootcandlesonpatientsbed

when installed over each end of bed.•Utilizes2-2lampelectronicballast.•Utilizes4-40wattBiaxtypelampswithexcellentcolorrendition(82CRI).

•31/2"x31/2"cellsize.•Doorjambwithintegralpositivelightstop.•Spring-loadedlatches.•Integralearthquakeclip.

Options & accessories page 4.130Ballast: Electronic 120 volt standard. For 277 volt, change 120 to 277 (e.g. MDS2G36PS4FT277SB).

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Radio interference filter: Suffix: R . 120 or 277 volt at 50 or 60Hz. One per fixture standard.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.

Note: For concealed spline, plaster or drywall ceiling, use “G” type fixtures with either: S2X2FKIT,orDrywallkit,FK92X2 .

MDS2G36PS4FT120SB

MD*4 2' x 2'Recessed 36 cell with prismatic overlay examination luminaire

5" (127mm)

24" (610mm)

Reference data

Efficiency 55.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 132.0W LuminaireEff.(LER) 31.3

WALL 3"

6"12"

12"12"12"12"

C L C L

52.5 54.8 52.7 106 111 107

63.9 66.8 64.1 119 125 120

74.5 78.0 74.7 128 134 129

77.9 81.6 78.1 133 139 133

75.6 79.1 75.8 132 138 133

68.6 71.8 68.8 123 129 123

57.6 60.3 57.9 109 114 110

InitialFootcandlesonBed

1 Fixture 2 Fixture

Ordering information

Type Cells Examination light shielding T-Grid Slot-T or Concealed-T

MD*4 2x2 Recessed Examination Light

36 Low iridescence specular louver w/prismatic overlay MDS2G36PS4FT120SB MDS2T36PS4FT120SB

36Low iridescence semi-specular louver w/prismatic overlay

MDS2G36LS4FT120SB MDS2T36LS4FT120SB

Examination Light Voltage Ballast Options Direct/indirect recessed 120=120V Seepage4.144 See page 4.144 277=277V andpage4.130

120MDS2G36PS4FT ASBExample

30˚

60˚1800

3600

Candlepower Curve

OBLseriesOver-bed, wall mounted luminaire

Page 148: Linear recessed and surface lighting

4.145Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

SUS 432/632Over-bed, wall mounted luminaire

30˚

60˚2400

3400

4400

Candlepower Curve

Ordering informationLamp

qty –typeExposed T-Grid

Flanged fordry or plaster

6-T8 SUS2GFSMA632 SUS2FFSMA632

SUS2GFSMA632UNVH6

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

Features•Asymmetric/symmetricdistribution

provides:Supplemental illumination to operating tables.•Minimizescontrastbetweensurgicalandsurrounding

areas.•Meetsgovernmentspecif icationforRadioFrequencyInterference(RFI),MIL-STD461-A,MIL-STD463.

•Oneradiosuppressorperfixture(standard).•Highefficiency60.9%(6light),61.2%(4light).•One-piecehousing.•Built-inearthquakeclips.•Flatfull-sizesteellensframeisgasketed.•21/4"lamptointegrallightstopforeasylampremoval.•Blackhousingexteriorforcoolerballast

operating temperature.•Hemmedoversiderailsforsafety.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV) and type and add as suffix, e.g. 277SO.

Ballast type <10THD <20THD

2 - 2 Lamp Elec. T8 SO* HI*3 - 2 Lamp Elec. T8 SO* HI*1 - 4 Lamp Elec. T8 O4* H4*2 - 3 Lamp Elec. T8 O6* H6*LOL Dimming T8 PS

* Instant start Standard.

Continuous row installation: For “F” type fixtures, half-width flanges are required between fixtures. Catalog no. 2FC Trim(eachjoint).

Plaster frames: “F” type fixtures do not include plaster frames. For individual or continuous mounting, specify PF24 universal frame per fixture.

Electrical/wiring: Options consult factory.

Seismic hold-down clips:For"G"typetroffers. Suffix:4HD(forNYConly).

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

Radio interference filter: Suffix: R . If one per ballast is required. 120 or 277 volt at 50 or 60Hz. Note:Onlyoneradiointerferencefilter(RF)forf ixtureif3 ballasts are used.

The footcandle readings of a typical 8' x 12' pat-tern layout of 8, 6 lamp units, illustrates that the asymmetric distribution adds 35% more light to the operating area (room size12'x16'x9'ceiling).

Fully gasketedlens frame

Hemmed over side-rails forsafe handling

Blackhousingexteriorfor cooler ballast

operating temperature

Blackstripedinterior perimeter of body

eliminates light leakSymmetrical distribution Asymmetrical distribution

One-piece housing

SUS 632 Voltage Ballast Options Surgical Perimeter 120=120V Seepage4.145 See page 4.145 Static Luminaire 277=277V andpage4.130 UNV=120-277V

UNVSUS2GFSMA632 AH6Example

30˚

60˚1200

2200

3200

Candlepower Curve

Ordering informationLamp

qty –typeExposed T-Grid

Flanged fordry or plaster

4-T8 SUS2GFSMA432 SUS2FFSMA432

SUS2GFSMA432UNVH4

The footcandle readings of a typical 8' x 12' pat-tern layout of 8, 4 lamp units, illustrates that the asymmetric distribution adds 35% more light to the operating area (room size12'x16'x9'ceiling).

Fully gasketedlens frame

Hemmed over side-rails forsafe handling

Blackhousingexteriorfor cooler ballast

operating temperature

Blackstripedinterior perimeter of body

eliminates light leakSymmetrical distribution Asymmetrical distribution

One-piece housing

SUS 432 Voltage Ballast Options Surgical Perimeter 120=120V Seepage4.145 See page 4.145 Static Luminaire 277=277V andpage4.130 UNV=120-277V

UNVSUS2GFSMA432 AH4Example

Earthquake Clip installed (lay-ingrid)

Built-inEarthquakeClip before installation

Page 149: Linear recessed and surface lighting

Linear recessed and surface lighting

4.146 Philips Lightolier For complete specif ication information visit www.lightolier.com

Architectural & surface utility

Surface mounted luminaires are most often used in situations where it is not feasible to install recessed lighting: where there is no suspended ceiling, where there are obstructions above the ceiling, or where it is costly and troublesome to penetrate but surface-mounted luminaires are also extensively used because they serve as elements of distinctive style, providing an identity or signature; they add character to a space. Becauseasurfacemountedfluorescentissubjecttocloser visual scrutiny than a recessed, standards of detailing craftsmanship are necessarily higher. The high quality of Philips Lightolier’s production is seen in this product offering.

Page 150: Linear recessed and surface lighting

Linear recessed and surface lighting

4.147Comprehensive lighting catalog 7th Edition

Stairwell > 4.148 Celebrity > 4.150 Belmont > 4.153 Dorm Lyte > 4.158 Dominaire Surface > 4.159

LWBUandLSW > 4.160 Deepcel Surface > 4.162 Prismalyte Surface > 4.163 VisionSmartSurface > 4.164 SLB > 4.165

Contents

Page 151: Linear recessed and surface lighting

4.148 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Philips Lightolier stairwell luminaireWall/ceiling mounted fluorescent

Conserving energy while maintaining safety.Stairwell lighting typically operates continuously at full output despite very low, intermittent use. The solution to this unique application is bi-level lighting which maintains minimum illumination requirementswhenthestairwellsareempty,therebymaximizingenergysavings.Bi-levellightingincorporates a sensor integrated into the fixture that dims the lighting down to minimum standards, when no one is present. When the fixture detects someone in the area, the lighting is restored to full brightness. This can result in 50 to 80 percent energy savings per fixture.

The Philips Lightolier stairwell luminaire incorporates an internal motion sensor and a bi-level ballast. It provides a standby low-light level, and upon detection of motion in a space, immediately increases the lighting to full brightness. After occupancy is no longer detected, the fixture reverts back to the low, standby level. The automatic bi-level lighting control saves energy and ensures full light output when the space is occupied. The Philips Lightolier stairwell luminaire can be mounted on the wall or installed on a ceiling and is available in one or two lamp T8 and two lamp T5 linear fluorescent.

Prismatic lens option

Philips Lightolier stairwell luminaire

Ideal for Stairwells, restrooms, laundry rooms and other areas where maximum light levels are not required on a constant basis.

Lens options

•Uniquecomposite,1/8"thickDR(impactresistant)acryliclenswithawhiteopaquecenterandlinearprisms to spread up/down light.

•Classic1/8"thicklinearprismaticvirginacryliclensthatislowinbrightness•ALinearprismaticlensof50%DR(impactresistant)and50%standardacrylicwithanominalthicknessof1/8"thatwillwithstand70foot-poundsofimpactwithoutbreaking.

Sensor options

Ultrasonic Occupancy Sensor •Ultrasonictechnology(40Khz)

Ultrasonic detection operates by transmitting sound waves throughout an area and measuring the speed at which they return.

Infrared Occupancy Sensor • Adjustable time delay from 30 seconds to 30 minutes. • Fixed sensitivity optimized for FS-LxW lens coverages. • RoHS compliant. • Light level daylighting feature from 10-120 fc.

Tamper proof option Secondary endcaps, secured with Holt head screws, can be added to the luminaire for tamper proofing

Example catalogSF4C232UNVV2-US, two 32 watt T8 lamps, bi-level dimming ballast and integrated Ultrasonic sensorSF4C232UNVV2-OC, two 32 watt T8 lamps, bi-level dimming ballast and integrated Infrared sensorFor complete listing of available fixtures and specification sheets search Stairwell at www.lightolier.com

Page 152: Linear recessed and surface lighting

4.149Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Philips Lightolier stairwell luminaireWall/ceiling mounted fluorescent

Recessed and Surface lighting Recessed and Surface lighting

1000 1001Comprehensive Lighting Catalog 7th EditionPhilips Lightolier For complete specif ication information visit www.lightolier.com

Lightolier Stairwell LuminaireWall/Ceiling Mounted Fluorescent

Conserving energy while maintaning safety.

Lighting in motion.

Lightolier Stairwell LuminaireWall/Ceiling Mounted Fluorescent

Composite lens option

Prismatic lens option

Fast Facts• Integrated occupancy sensor, Ultrasonic or Infrared motion• Available in T8, T5 and T5HO lamping• Three unique lens options• Only 3 ⅞" deep, meeting the Americans with Disabilities Act

requirements for wall mounted fixtures• Additional proprietary dimmer available for GSA requirements

(Consult Factory)

Lightolier Stairwell Luminaire

Ideal for

Lens Options

Sensor Options

Ultrasonic Occupancy Sensor •

Infrared Occupancy Sensor • Adjustable time delay from 30 seconds to 30 minutes. • Fixed sensitivity optimized for FS-LxW lens coverages. • RoHS compliant. • Light level daylighting feature from 10-120 fc.

Tamper Proof Option Secondary endcaps, secured with Holt head screws, can be add to the luminaire for tamper proofing

Example CatalogSF4C232UNVV2-US, two 32 watt T8 lamps, bi-level dimming ballast and integrated Ultrasonic sensorSF4C232UNVV2-OC, two 32 watt T8 lamps, bi-level dimming ballast and integrated Infrared sensorFor complete listing of available fixtures and specification sheets search Stairwell at www.lightolier.com

Stairwell lighting typically operates continuously at full output despite very low, intermittent use. The solution to this unique application is bi-level lighting which maintains minimum illumination requirements when the stairwells are empty, thereby maximizing energy savings. Bi-level lighting incorporates a sensor integrated into the fixture that dims the lighting down to minimum standards, when no one is present. When the fixture detects someone in the area, the lighting is restored to full brightness. This can result in 50 to 80 percent energy savings per fixture.

The Lightolier Stairwell luminaire incorporates an internal motion sensor and a bi-level ballast. It provides a standby low-light level, and upon detection of motion in a space, immediately increases the lighting to full brightness. After occupancy is no longer detected, the fixture reverts back to the low, standby level. The automatic bi-level lighting control saves energy and ensures full light output when the space is occupied. The Lightolier Stairwell luminaire can be mounted on the wall or installed on a ceiling and is available in one or two lamp T8 and two lamp T5 linear fluorescent.

Stairwells, restrooms, laundry rooms and other areas where maximum light levels are not required on a constant basis.

• Unique composite, 1/8" thick DR (impact resistant) acrylic lens with a white opaque center and linear prisms to spread up/down light.• Classic 1/8" thick linear prismatic virgin acrylic lens that is low in brightness• A Linear prismatic lens of 50% DR (impact resistant) and 50% standard acrylic with a nominal thickness of 1/8" that will withstand 70 foot-pounds of impact without breaking.

Ultrasonic technology (40Khz)Ultrasonic detection operates bytransmitting sound waves throughoutan area and measuring the speed atwhich they return.

Ordering Information T5 or T5HO

Ordering Information T8

Note: Consult local code authority for applications where Stairwell luminaire will be used as emergency lighting.

Stairwell:Wall MountedFluorescent

SFFixtureLength:4=48"(Nominal 48")

4Lens Type:C =White Composite Acrylic LensR = Linear Prismatic Virgin Acrylic LensV = Vandal Proof ~ A High impact, 50% DR Acrylic Linear Prismatic Lens with Additional Secondary Vandal proof end-caps secured with holt head screws. (Factory Installed Only)

CLampQuantity:2=2 Lamp

2Lamp Type:(By Others)28=T5 28W54=T5HO 54W(Nominal 48")

28Voltage‡:120, 277 orUNV = 120-277

UNVBallast Type: <10THD 2 Lamp 28W Elec. T5 VY (.95BF)100% / 50% Bi-level2 Lamp 28W Elec. T5 PG ††2 Lamp 54W Elec. T5HO NQ (.80BF)100% / 50% Bi-level2 Lamp 54W Elec. T5HO PG ††

Dimming 0-10 Volt2 Lamp 28W Elec. T5 EQ‡2 Lamp 54W Elec. T5HO MW‡

‡ Specific 120 or 277 voltage must be specified with use of a 0-10 volt dimming ballast.††Program Rapid Start (UNV only)

Note: UNV PG combination will result in lamps controlled by occupancy sensor in a ON or OFF capacity.

Sensor Type:US=UltraSonicOC=Infrared

USOptions:DL=Optional GSA ballast low level controller.

Note: DL option requires the use of a 0-10 volt dimming ballast.

Options:Emergency Pack(Consult Factory for applicable code)

Optional Fusing:A=Internal fast blowingC=Internal slow blowing

Note: Consult local code authority for applications where Stairwell luminaire will be used as emergency lighting.

Stairwell:Wall MountedFluorescent

SFFixtureLength:2=24"4=48"

4Lens Type:C =White Composite Acrylic LensR = Linear Prismatic Virgin Acrylic LensV = Vandal Proof ~ A High impact, 50% DR Acrylic Linear Prismatic Lens with Additional Secondary Vandal proof end-caps secured with holt head screws. (Factory Installed Only)

CLampQuantity:1=1 Lamp2=2 Lamps

2Lamp Type:(By Others)17=17W T8(Nominal 24")32=32W T8(Nominal 48")

32Voltage‡:120, 277 orUNV=120-277UN2 = 2, one lamp universal voltage ballasts (SF4 ONLY)

UNVBallast Type: <10THD 1 or 2 Lamp 17W or 32W Elec. T8 V2 100% / 50% Bi-level1 or 2 Lamp 17W or 32W Elec. T8 P2*

Dimming 0-10 Volt1 or 2 Lamp 17W or 32W Elec. T8 M7‡

‡ Specific 120 or 277 voltage must be specified with use of a 0-10 volt dimming ballast.*Program Start Standard

Note: UN2 P2 combination will result in one lamp always ON with second lamp controlled by occupancy sensor.UNV P2 combination will result in lamp/lamps controlled by occupancy sensor in a ON or OFF capacity.

Sensor Type:US=UltraSonicOC=Infrared

USOptions:DL=Optional GSA ballast low level controller.

Note: DL option requires the use of a 0-10 volt dimming ballast.

Options:Emergency Pack(Consult Factory for applicable code)

Optional Fusing:A=Internal fast blowingC=Internal slow blowing

-

-

VY

V2

Recessed and Surface lighting Recessed and Surface lighting

1000 1001Comprehensive Lighting Catalog 7th EditionPhilips Lightolier For complete specif ication information visit www.lightolier.com

Lightolier Stairwell LuminaireWall/Ceiling Mounted Fluorescent

Conserving energy while maintaning safety.

Lighting in motion.

Lightolier Stairwell LuminaireWall/Ceiling Mounted Fluorescent

Composite lens option

Prismatic lens option

Fast Facts• Integrated occupancy sensor, Ultrasonic or Infrared motion• Available in T8, T5 and T5HO lamping• Three unique lens options• Only 3 ⅞" deep, meeting the Americans with Disabilities Act

requirements for wall mounted fixtures• Additional proprietary dimmer available for GSA requirements

(Consult Factory)

Lightolier Stairwell Luminaire

Ideal for

Lens Options

Sensor Options

Ultrasonic Occupancy Sensor •

Infrared Occupancy Sensor • Adjustable time delay from 30 seconds to 30 minutes. • Fixed sensitivity optimized for FS-LxW lens coverages. • RoHS compliant. • Light level daylighting feature from 10-120 fc.

Tamper Proof Option Secondary endcaps, secured with Holt head screws, can be add to the luminaire for tamper proofing

Example CatalogSF4C232UNVV2-US, two 32 watt T8 lamps, bi-level dimming ballast and integrated Ultrasonic sensorSF4C232UNVV2-OC, two 32 watt T8 lamps, bi-level dimming ballast and integrated Infrared sensorFor complete listing of available fixtures and specification sheets search Stairwell at www.lightolier.com

Stairwell lighting typically operates continuously at full output despite very low, intermittent use. The solution to this unique application is bi-level lighting which maintains minimum illumination requirements when the stairwells are empty, thereby maximizing energy savings. Bi-level lighting incorporates a sensor integrated into the fixture that dims the lighting down to minimum standards, when no one is present. When the fixture detects someone in the area, the lighting is restored to full brightness. This can result in 50 to 80 percent energy savings per fixture.

The Lightolier Stairwell luminaire incorporates an internal motion sensor and a bi-level ballast. It provides a standby low-light level, and upon detection of motion in a space, immediately increases the lighting to full brightness. After occupancy is no longer detected, the fixture reverts back to the low, standby level. The automatic bi-level lighting control saves energy and ensures full light output when the space is occupied. The Lightolier Stairwell luminaire can be mounted on the wall or installed on a ceiling and is available in one or two lamp T8 and two lamp T5 linear fluorescent.

Stairwells, restrooms, laundry rooms and other areas where maximum light levels are not required on a constant basis.

• Unique composite, 1/8" thick DR (impact resistant) acrylic lens with a white opaque center and linear prisms to spread up/down light.• Classic 1/8" thick linear prismatic virgin acrylic lens that is low in brightness• A Linear prismatic lens of 50% DR (impact resistant) and 50% standard acrylic with a nominal thickness of 1/8" that will withstand 70 foot-pounds of impact without breaking.

Ultrasonic technology (40Khz)Ultrasonic detection operates bytransmitting sound waves throughoutan area and measuring the speed atwhich they return.

Ordering Information T5 or T5HO

Ordering Information T8

Note: Consult local code authority for applications where Stairwell luminaire will be used as emergency lighting.

Stairwell:Wall MountedFluorescent

SFFixtureLength:4=48"(Nominal 48")

4Lens Type:C =White Composite Acrylic LensR = Linear Prismatic Virgin Acrylic LensV = Vandal Proof ~ A High impact, 50% DR Acrylic Linear Prismatic Lens with Additional Secondary Vandal proof end-caps secured with holt head screws. (Factory Installed Only)

CLampQuantity:2=2 Lamp

2Lamp Type:(By Others)28=T5 28W54=T5HO 54W(Nominal 48")

28Voltage‡:120, 277 orUNV = 120-277

UNVBallast Type: <10THD 2 Lamp 28W Elec. T5 VY (.95BF)100% / 50% Bi-level2 Lamp 28W Elec. T5 PG ††2 Lamp 54W Elec. T5HO NQ (.80BF)100% / 50% Bi-level2 Lamp 54W Elec. T5HO PG ††

Dimming 0-10 Volt2 Lamp 28W Elec. T5 EQ‡2 Lamp 54W Elec. T5HO MW‡

‡ Specific 120 or 277 voltage must be specified with use of a 0-10 volt dimming ballast.††Program Rapid Start (UNV only)

Note: UNV PG combination will result in lamps controlled by occupancy sensor in a ON or OFF capacity.

Sensor Type:US=UltraSonicOC=Infrared

USOptions:DL=Optional GSA ballast low level controller.

Note: DL option requires the use of a 0-10 volt dimming ballast.

Options:Emergency Pack(Consult Factory for applicable code)

Optional Fusing:A=Internal fast blowingC=Internal slow blowing

Note: Consult local code authority for applications where Stairwell luminaire will be used as emergency lighting.

Stairwell:Wall MountedFluorescent

SFFixtureLength:2=24"4=48"

4Lens Type:C =White Composite Acrylic LensR = Linear Prismatic Virgin Acrylic LensV = Vandal Proof ~ A High impact, 50% DR Acrylic Linear Prismatic Lens with Additional Secondary Vandal proof end-caps secured with holt head screws. (Factory Installed Only)

CLampQuantity:1=1 Lamp2=2 Lamps

2Lamp Type:(By Others)17=17W T8(Nominal 24")32=32W T8(Nominal 48")

32Voltage‡:120, 277 orUNV=120-277UN2 = 2, one lamp universal voltage ballasts (SF4 ONLY)

UNVBallast Type: <10THD 1 or 2 Lamp 17W or 32W Elec. T8 V2 100% / 50% Bi-level1 or 2 Lamp 17W or 32W Elec. T8 P2*

Dimming 0-10 Volt1 or 2 Lamp 17W or 32W Elec. T8 M7‡

‡ Specific 120 or 277 voltage must be specified with use of a 0-10 volt dimming ballast.*Program Start Standard

Note: UN2 P2 combination will result in one lamp always ON with second lamp controlled by occupancy sensor.UNV P2 combination will result in lamp/lamps controlled by occupancy sensor in a ON or OFF capacity.

Sensor Type:US=UltraSonicOC=Infrared

USOptions:DL=Optional GSA ballast low level controller.

Note: DL option requires the use of a 0-10 volt dimming ballast.

Options:Emergency Pack(Consult Factory for applicable code)

Optional Fusing:A=Internal fast blowingC=Internal slow blowing

-

-

VY

V2

Lighting in motion.

Fast facts•Integratedoccupancysensor,ultrasonicorinfraredmotion•AvailableinT8,T5andT5HOlamping•Threeuniquelensoptions•Only3⅞"deep,meetingtheAmericanswithDisabilitiesAct

requirements for wall mounted fixtures•AdditionaldimmeravailableforGSArequirements(consultfactory)

– –

– –

– –

– –

Note: Stairwell luminaire also available in LED

Page 153: Linear recessed and surface lighting

4.150 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•Universalluminairethathasuplight/downlight

or downlight capabilities on the same fixture.•Lowbrightnesscontrolleddownlightinganduplighting/

downlighting.•Injection-moldedone-piecevirginacrylicdownlightrefractor(1side,2endsandface).

•Catadioptricsideandendwalldesign(downlight).•Slim31/16"depth.•Nominal2'and4'lengths.•63%efficientT8lampsdownlight.•67.1%efficientT8lampsuplight/downlight.•Invisiblesteellatchesalignrefractortohousing.•Individualorcontinuousrows.•Forovermirror,overbed,corridor,stairwell

and bulletin board applications.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Radio interference filter: 120 or 277 volt, 50 or 60 Hz. One per fixture. Suffix: R.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Celebrity(CWBU)UniversalWall mounted downlight luminaire

The ultimate in glare-free architectural lighting. A classic rectilinear wall fixture with a jewel-like diamond faceted injection molded refractor that mirrors out brightness at critical viewing angles. Ideal for nursing homes when used as a bed-light in the uplight/downlight configuration. It is also excellent when used over mirrors, in corridors and for task lighting in the downlight only configuration.

Uplight lens cover for downlignt only

CWBU232UNVHI 2 Lamp Downlight

CWBU132UNVHI 1 Lamp Downlight

Reference data

Efficiency 63.0% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 62.0W

Reference data

Efficiency 68.4% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 30.0W

Ordering informationType Size Lamp qty –type Catalog no.

Downlight7 ⅝"x25 ½"7 ⅝"x49 ½"

2-T8 CWBU217CWBU232

Ordering informationType Size Lamp qty –type Catalog no.

Downlight7 ⅝"x25 ½"7 ⅝"x49 ½"

1-T8 CWBU117CWBU132

CWBU Voltage Ballast Options Wall Mounted 120=120V Seepage4.150 See page 4.150 Downlight 277=277V andpage4.216 Luminaire UNV=120-277V (Elec.T8Ballastonly)

CWBU Voltage Ballast Options Wall Mounted 120=120V Seepage4.150 See page 4.150 Downlight 277=277V andpage4.216 Luminaire UNV=120-277V (Elec.T8Ballastonly)

UNV

UNV

CWBU232

CWBU132

A

A

HI

HI

Example

Example

7 ⅝" (194mm)

3 1�16"(78mm)

Uplight Lens Cover

7 ⅝" (194mm)

3 1�16"(78mm)

Uplight Lens Cover

7 ⅝" (194mm)

3 1�16"(78mm)

Uplight Lens Cover

30˚

60˚

90˚

500

1000

1500

Candlepower Curve

30˚

60˚

90˚

500

1000

1500

Candlepower Curve

Page 154: Linear recessed and surface lighting

4.151Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Features•Universalluminairethathasuplight/downlight

or downlight capabilities on the same fixture.•Lowbrightnesscontrolleddownlightinganduplighting/

downlighting.•Injection-moldedone-piecevirginacrylicdownlightrefractor(1side,2endsandface).

•Catadioptricsideandendwalldesign(downlight).•Slim31/16"depth.•Nominal2'and4'lengths.•63%efficientT8lampsdownlight.•67.1%efficientT8lampsuplight/downlight.•Invisiblesteellatchesalignrefractortohousing.•Individualorcontinuousrows.•Forovermirror,overbed,corridor,stairwell

and bulletin board applications.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Radio interference filter: 120 or 277 volt, 50 or 60 Hz. One per fixture. Suffix: R.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Celebrity(CWBU)UniversalWall mounted uplight/downlight luminaire

The ultimate in glare-free architectural lighting. A classic rectilinear wall fixture with a jewel-like diamond faceted injection molded refractor that mirrors out brightness at critical viewing angles. Ideal for nursing homes when used as a bed-light in the uplight/downlight configuration. It is also excellent when used over mirrors, in corridors and for task lighting in the downlight only configuration.

Uplight lens cover removed for uplight/downlignt

CWBU232UNVHI 2 Lamp Uplight / Downlight

CWBU132UNVHI 1 Lamp Uplight / Downlight

30˚

60˚

90˚

45˚

500

500

1000

Candlepower Curve

30˚

60˚

90˚

45˚

500

500

1000

Candlepower CurveReference data

Efficiency 67.1% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 62.0W

Reference data

Efficiency 69.8% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 30.0W

Ordering informationType Size Lamp qty –type Catalog no.

Uplight / Downlight7 ⅝"x25 ½"7 ⅝"x49 ½"

2-T8 CWBU217CWBU232

Ordering informationType Size Lamp qty –type Catalog no.

Uplight /Downlight7 ⅝"x25 ½"7 ⅝"x49 ½"

1-T8 CWBU117CWBU132

CWBU Voltage Ballast Options Wall Mounted 120=120V Seepage4.151 See page 4.151 Uplight/Downlight 277=277V andpage4.216 Luminaire UNV=120-277V (Elec.T8Ballastonly)

CWBU Voltage Ballast Options Wall Mounted 120=120V Seepage4.151 See page 4.151 Uplight/Downlight 277=277V andpage4.216 Luminaire UNV=120-277V (Elec.T8Ballastonly)

UNV

UNV

CWBU232

CWBU132

A

A

HI

HI

Example

Example

7 ⅝" (194mm)

3 1�16"(78mm)

Uplight Lens Cover

7 ⅝" (194mm)

3 1�16"(78mm)

Uplight Lens Cover

7 ⅝" (194mm)

3 1�16"(78mm)

Uplight Lens Cover

Page 155: Linear recessed and surface lighting

4.152 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

30˚

60˚700

1400

2100

Candlepower Curve

SpecificationSurfaceLensCBSUnitMatchesCWBUCelebrityWallUnit

Sturdy steel chassis Four sided injection molding

Photograph illustrates action of Celebrity lens enclosure. Catadioptric prisms “mirror” out glare, refract light beams into useful areas.

Celebrity SurfaceSurface

12" (305mm)

3 ¼"(83mm)

Features•.187lensthickness.•Fivesideinjectionmoldedrefractorwithsquarebase,conicalprisms(absolutelynosag).

•Catadioptricside/endwalldesign,forlowbrightness.•Tightaligningrefractorfit.•Invisiblespringsteellatches.•Easyballastaccessibility.•Rigid,reinforcedhousing.•Individualorcontinuousrowmounting.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

1 - 2 Lamp Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Not recommended for stem mounting.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

CBS232UNVHIReference data

Efficiency 78.2% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 59.1W LuminaireEff(LER) 66.2

Ordering informationType Size Lamp qty –type Catalog no.

Surface Prismatic 12"x49 9⁄16" 2-T8 CBS232

Celebrity Voltage Ballast Options Surface Wrap 120=120V Seepage4.152 See page 4.152 Luminaire 277=277V andpage4.216 UNV=120-277V (Elec.T8Ballastonly)

UNVCBS232 AHIExample

Page 156: Linear recessed and surface lighting

4.153Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

BelmontSpillFrame

BelmontSpillFrame

BelmontSpillFrame1'x4'Architectural surface luminaire

10 ½"(267mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

9�16" Mounting Hole

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

18"(457mm)

15 ½"(394mm)

5" (127mm)

3" (76mm)

26"(660mm)

20"(508mm)

7 11�32"(187mm)

⅞" K.O.

⅞" K.O. Within 1 ⅞" K.O.

1 1�16" (27mm)

9�32" Mounting Hole

⅞" KO

⅞" KO

⅞" K.O.

⅞" KO

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole

9�32" Mounting Hole

15 ½"(394mm)

2 31�32" (75mm)

31�32"(25mm)

50"(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

⅞" K.O.10 ½"

(267mm)

2 31�32" (75mm)

31�32"(25mm)

⅞" K.O.

⅞" K.O.

9�32" Mounting Hole

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole50"

(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

1X4 BELMONT SF (2) F32 T8 2X4 BELMONT SF (4) F32 T8 2X2 BELMONT SF (4) F17 T82X4 BELMONT SF (2) F32 T8 2X2 BELMONT SF (2) F40 TT5

Features•Excellentforlightingcafeterias,smalloffices,corridors,

kitchens and family rooms.•Uniquerectangulardoubleframecreates

uninterrupted spill of light from all four sides.•Extrudedaluminumframewithmiteredcorners.•1/8”thickwhiteacryliclenscontaining25%DR.•Only3-3/4”totaldepth.•Stepbackhousingforanapparentdepthof1-1/2”.•Lensopensandhingesfromeitherside.•Zip-clipflushmountonT-gridceilings.•Off-center7/8”K.O.forflushmounttoT-gridceiling.

Ordering information

Type Lamps qty –type

Electronic ballast Finish Shielding Chassis

Belmont Spill Frame Architectural Surface Luminaire

4-T8

2 - 2 Lamp2 - 2 Lamp1 - 4 Lamp1 - 4 Lamp

BlackWhiteBlackWhite

BESF2X4BESF2X4BESF2X4BESF2X4

BE2B432UNVHIBE2W432UNVHIBE2B432UNVH4BE2W432UNVH4

Ordering information

Type Lamps qty –type

Electronic ballast Finish Shielding Chassis

Belmont Spill Frame Architectural Surface Luminaire

2-T8 1 - 2 Lamp BlackWhite

BESF1X4BESF1X4

BE1B232UNVHIBE1W232UNVHI

Note: Chassis and shielding are packed in separate cartons. When ordering, enter as separate line items.

Note: Chassis and shielding are packed in separate cartons. When ordering, enter as separate line items.

10 ½"(267mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

9�16" Mounting Hole

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

18"(457mm)

15 ½"(394mm)

5" (127mm)

3" (76mm)

26"(660mm)

20"(508mm)

7 11�32"(187mm)

⅞" K.O.

⅞" K.O. Within 1 ⅞" K.O.

1 1�16" (27mm)

9�32" Mounting Hole

⅞" KO

⅞" KO

⅞" K.O.

⅞" KO

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole

9�32" Mounting Hole

15 ½"(394mm)

2 31�32" (75mm)

31�32"(25mm)

50"(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

⅞" K.O.10 ½"

(267mm)

2 31�32" (75mm)

31�32"(25mm)

⅞" K.O.

⅞" K.O.

9�32" Mounting Hole

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole50"

(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

1X4 BELMONT SF (2) F32 T8 2X4 BELMONT SF (4) F32 T8 2X2 BELMONT SF (4) F17 T82X4 BELMONT SF (2) F32 T8 2X2 BELMONT SF (2) F40 TT5

10 ½"(267mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

9�16" Mounting Hole

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

18"(457mm)

15 ½"(394mm)

5" (127mm)

3" (76mm)

26"(660mm)

20"(508mm)

7 11�32"(187mm)

⅞" K.O.

⅞" K.O. Within 1 ⅞" K.O.

1 1�16" (27mm)

9�32" Mounting Hole

⅞" KO

⅞" KO

⅞" K.O.

⅞" KO

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole

9�32" Mounting Hole

15 ½"(394mm)

2 31�32" (75mm)

31�32"(25mm)

50"(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

⅞" K.O.10 ½"

(267mm)

2 31�32" (75mm)

31�32"(25mm)

⅞" K.O.

⅞" K.O.

9�32" Mounting Hole

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole50"

(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

1X4 BELMONT SF (2) F32 T8 2X4 BELMONT SF (4) F32 T8 2X2 BELMONT SF (4) F17 T82X4 BELMONT SF (2) F32 T8 2X2 BELMONT SF (2) F40 TT5

The intriguing appearance and ease ofmaintenancemakeBelmontSpillFrame the ideal choice for surface mounted lighting applications for cafeterias, corridors, small offices, kitchens or family rooms.

10 ½"(267mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

9�16" Mounting Hole

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

18"(457mm)

15 ½"(394mm)

5" (127mm)

3" (76mm)

26"(660mm)

20"(508mm)

7 11�32"(187mm)

⅞" K.O.

⅞" K.O. Within 1 ⅞" K.O.

1 1�16" (27mm)

9�32" Mounting Hole

⅞" KO

⅞" KO

⅞" K.O.

⅞" KO

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole

9�32" Mounting Hole

15 ½"(394mm)

2 31�32" (75mm)

31�32"(25mm)

50"(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

⅞" K.O.10 ½"

(267mm)

2 31�32" (75mm)

31�32"(25mm)

⅞" K.O.

⅞" K.O.

9�32" Mounting Hole

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole50"

(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

1X4 BELMONT SF (2) F32 T8 2X4 BELMONT SF (4) F32 T8 2X2 BELMONT SF (4) F17 T82X4 BELMONT SF (2) F32 T8 2X2 BELMONT SF (2) F40 TT5

BelmontSpillFrame2'x4'Architectural surface luminaire

BelmontSpillFramefeaturesanextrudedaluminumframewithauniqueuninterruptedspillof light on all four sides with a soft-white, impact resistant acrylic lens. The step back chassis createsafloatingframeeffectwithanapparentdepthofonly1½inches.Theframecanbeopened and/or hinged from either side without tools for easy lamp replacement.

Page 157: Linear recessed and surface lighting

4.154 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

BelmontSpillFrame2'x2'Architectural surface luminaire

BelmontSpillFramefeaturesanextrudedaluminumframewithauniqueuninterruptedspillof light on all four sides with a soft-white, impact resistant acrylic lens. The step back chassis createsafloatingframeeffectwithanapparentdepthofonly1½inches.Theframecanbeopened and/or hinged from either side without tools for easy lamp replacement.

Features•Excellentforlightingcafeterias,smalloffices,

corridors, kitchens and family rooms.•Uniquerectangulardoubleframecreates

uninterrupted spill of light from all four sides.•Extrudedaluminumframewithmiteredcorners.•1/8”thickwhiteacryliclenscontaining25%DR.•Only3-3/4”totaldepth.•Stepbackhousingforanapparentdepthof1-1/2”.•Lensopensandhingesfromeitherside.•Zip-clipflushmountonT-gridceilings.•Off-center7/8”K.O.forflushmounttoT-gridceiling.

Ordering information

Type Lamps qty –type

Electronic ballast Finish Shielding Chassis

Belmont Spill Frame Architectural Surface Lum.

4-T84-T84-T84-T82-TT5 40W2-TT5 40W

2 - 2 Lamp2 - 2 Lamp1 - 4 Lamp1 - 4 Lamp1 - 2 Lamp1 - 2 Lamp

BlackWhiteBlackWhiteBlackWhite

BESF2X2BESF2X2BESF2X2BESF2X2BESF2X2BESF2X2

BE2B417UNVHIBE2W417UNVHIBE2B417UNVH4BE2W417UNVH4BE2B2FTUNVIBBE2W2FTUNVIB

Note: Chassis and shielding are packed in separate cartons. When ordering, enter as separate line items.

10 ½"(267mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

9�16" Mounting Hole

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

18"(457mm)

15 ½"(394mm)

5" (127mm)

3" (76mm)

26"(660mm)

20"(508mm)

7 11�32"(187mm)

⅞" K.O.

⅞" K.O. Within 1 ⅞" K.O.

1 1�16" (27mm)

9�32" Mounting Hole

⅞" KO

⅞" KO

⅞" K.O.

⅞" KO

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole

9�32" Mounting Hole

15 ½"(394mm)

2 31�32" (75mm)

31�32"(25mm)

50"(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

⅞" K.O.10 ½"

(267mm)

2 31�32" (75mm)

31�32"(25mm)

⅞" K.O.

⅞" K.O.

9�32" Mounting Hole

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole50"

(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

1X4 BELMONT SF (2) F32 T8 2X4 BELMONT SF (4) F32 T8 2X2 BELMONT SF (4) F17 T82X4 BELMONT SF (2) F32 T8 2X2 BELMONT SF (2) F40 TT5

The intriguing appearance and ease ofmaintenancemakeBelmontSpillFrame the ideal choice for surface mounted lighting applications for cafeterias, corridors, small offices, kitchens or family rooms.10 ½"

(267mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

9�16" Mounting Hole

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

18"(457mm)

15 ½"(394mm)

5" (127mm)

3" (76mm)

26"(660mm)

20"(508mm)

7 11�32"(187mm)

⅞" K.O.

⅞" K.O. Within 1 ⅞" K.O.

1 1�16" (27mm)

9�32" Mounting Hole

⅞" KO

⅞" KO

⅞" K.O.

⅞" KO

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole

9�32" Mounting Hole

15 ½"(394mm)

2 31�32" (75mm)

31�32"(25mm)

50"(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

⅞" K.O.10 ½"

(267mm)

2 31�32" (75mm)

31�32"(25mm)

⅞" K.O.

⅞" K.O.

9�32" Mounting Hole

⅞" K.O. Within 1 ⅞" K.O.

9�32" Mounting Hole50"

(1270mm)

5"(127mm)

44 1�16"(1119mm)

39 ⅝"(1006mm)

5 3�16"(132mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

15 ½"(394mm)

1 ½"(38mm)

3 ¾"(95mm)

1X4 BELMONT SF (2) F32 T8 2X4 BELMONT SF (4) F32 T8 2X2 BELMONT SF (4) F17 T82X4 BELMONT SF (2) F32 T8 2X2 BELMONT SF (2) F40 TT5

BelmontSpillFrame

Page 158: Linear recessed and surface lighting

4.155Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

BelmontI&ll2'x4'&1'x4'Linear fluorescent utility luminaire

Ideally suited to circulation, utility, and workspaces, these shallow, sleek lightforms are available in the more efficient T8 Electronic lamp-ballast systems.

BelmontI

Belmontll

Wrap-around acrylic diffuser with end caps attached.Complete Iuminaire consists of Lightshield and Chassis. Specify and order each item separately.

Notsuitable for row mounting.

Linear acrylic arc with no visible trim.Complete luminaire consists of Lightshield and Chassis. Specify and order each item separately.

Notsuitable for row mounting.

* Footcandle values of illumination are initial and average and areataheightof30"abovethefloor.Theyareshownforrooms with ceiling heights ranging from 8' to 12'.

Roomfinishesaretypical:whiteceiling(80%refl.). LightWalls(50%refl.)anddarkf loor(20%refl.).

All units are: cULus listed, suitable for damp locations.

50 ¼"(1276mm)

10 ¾"(273mm)

3 ½" (89mm)

49 ½"(1257mm)

10 ⅝"(270mm)

3 ⅞" (98mm)

15 ⅝" (397mm)

49 ½"(1257mm)

3 ⅞" (98mm)

1x4

1x4

2x4

2x4

Application data for surface mountedStyle Multiple Fixtures Single Fixture

Lamp Fixture Spacing,O.C

F.C.*30' x 50'Room

F.C.*12 x 12'Room

BelmontI 6'8'10'

782828

15

(2)40WT12

(2)32WT8:F.C.x0.9

BelmontII 8'10'12'

966142

22

(4)40WT12

(4)32WT8:F.C.x0.9Ordering information

Type Size Lamps qty –type Wattage Electronic

ballast Finish Chassis Lightshield(Orderseparately)

Belmont I Utility Luminaire

1' x 4'1' x 4'

2-T82-T8 32W UNV Black

WhiteBE1B232UNVHIBE1W232UNVHI

1032410324

2' x 4'2' x 4'

4-T84-T8 32W UNV Black

WhiteBE2B432UNVHIBE2W432UNVHI

1032810328

For products that require 1-4 light ballast add suff ix H4. Example: BE2B432UNVH4

Ordering information

Type Size Lamps qty –type Wattage Electronic

ballast Finish Chassis Lightshield(Orderseparately)

Belmont II Utility Luminaire

1' x 4'1' x 4'

2-T82-T8 32W UNV Black

WhiteBE1B232UNVHIBE1W232UNVHI

1032610326

2' x 4'2' x 4'

4-T84-T8 32W UNV Black

WhiteBE2B432UNVHIBE2W432UNVHI

1033010330

For products that require 1-4 light ballast add suff ix H4. Example: BE2B432UNVH4

16" (406mm)

50 ¼"(1276mm)

3 ¾" (95mm)

Page 159: Linear recessed and surface lighting

4.156 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

BelmontCloud2'x4'&1'x4'Linear fluorescent utility luminaire

Ideally suited to circulation, utility, and workspaces, these shallow, sleek lightforms are available in the more efficient T8 Electronic lamp-ballast systems.

BelmontCloudAcrylic diffuser with softly contoured edges.Complete luminaire consists of Lightshield and Chassis. Specify and order each item separately.

Notsuitable for row mounting.

All units are: cULus listed, suitable for damp locations.

51 ½"(1308mm)

13 ¾"(349mm)

4" (102mm)

1x4 2x4

Ordering information

Type Size Lamps qty –type Wattage Electronic

ballast Finish Chassis Lightshield(Orderseparately)

Belmont Cloud Utility Luminaire

1' x 4'1' x 4'

2-T82-T8 32W UNV Black

WhiteBE1B232UNVHIBE1W232UNVHI

1032510325

2' x 4'2' x 4'

4-T84-T8 32W UNV Black

WhiteBE2B432UNVHIBE2W432UNVHI

1032710327

For products that require 1-4 light ballast add suff ix H4. Example: BE2B432UNVH4

17" (432mm)

51 ½"(1308mm)

4" (102mm)

Page 160: Linear recessed and surface lighting

4.157Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Belmont6"Cloud&VanityLightArchitectural surface

Features•6"whiteopalacryliclens(vacuumformed).•Canbehorizontallyorverticallywallmounted.•Canbeceilingmounted.•Efficiency69.0%.•Lenssecuredtobodywithscrewsatends.•Quarterturnlatchsecureschannelcoverforeasy

wireway access.•Heavydutychannelofcodegaugedieformedsteel.•Fullyenclosedwiring.•ULListedsnap-onendcaps(body).•Greengroundingscrewinstalledinchannel.

Options & accessories

Ballast type <10THD <20THD

Electronic T8 HI –

Features•Canbehorizontallyorverticallymounted.•43/4"diametersopalwhiteacryliclens.•Positivestainlesssteellensretainers.•Permanentlyinstalledmilkwhiteopaquediffuserends

with decorative trim.•Efficiency76.6%(T8).•Quarterturnlatchsecureschannelcoverforeasy

wireway access.•Heavydutychannelofcodegaugedieformedsteel.•Fullyenclosedwireway.•ULListedsnap-onendcaps(body).•Greengroundingscrewinstalledinchannel.

Options & accessories

Ballast type <10THD <20THD

Electronic T8 HI –

Belmont6"Cloud

VanityLight

26 ½" (673mm) 38 ½" (978mm)

24" (610mm) or 36" (914mm)

2' or 3' Channel4" (102mm)

K.O.

6" (152mm)4 ⅝"

(117mm)

50 ½" (1282mm)

48"

4' Channel4" (102mm)

K.O.6 ⅜" (162mm) 2" Dia. K.O. with ⅞" Dia. ⅞" Dia. K.O.

6" (152mm)4 ⅝"

(117mm)

4 ⅛"(105mm)

4 ⅛"(105mm)

6" (152mm)

2"(51mm)

24" (610mm)36" (914mm)48" (1219mm)

24" (610mm)36" (914mm)48" (1219mm)

25 ½" (648mm)37 ½" (953mm)49 ½" (1257mm)

⅞" Dia. (22mm)

4 ¾" (121mm)

4"(102mm)

2 ½"(64mm)

Ordering information When ordering, enter as separate line items.

Type Size Lamps qty –type Voltage Chassis Shielding

Belmont 6" Cloud Utility Luminaire

6"x24"6"x36"6"x48"

2-T8 UNV(120-277V)SW2S217HPFUNVHISW2S225HPFUNVHISW2S232HPFUNVHI

BCW6X24BCW6X36BCW6X48

Note: Chassis and shielding are packed in separate cartons. Chassis and shielding shown are stock items.

Ordering information When ordering, enter as separate line items.

Type Size Lamps qty –type Voltage Chassis Shielding

Vanity Light Utility Luminaire

4 ¾"x24"4 ¾"x36"4 ¾"x48"

1-T8 UNV(120-277V)SN2S117HPFUNVHISN2S125HPFUNVHISN2S132HPFUNVHI

VLW4X24VLW4X36VLW4X48

Note: Chassis and shielding are packed in separate cartons. Chassis and shielding shown are stock items.

Page 161: Linear recessed and surface lighting

4.158 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•Fordorms,nursinghomes,assistedliving,health

care facilities, or other over bed or wall mounted applications.

•Upanddownlight,1or2lamp.•Separatelampcompartmentsforcontrolleduplight

and downlight for 2 lamp models.•1/8"thickDRacryliclens.Uniqueco-extension.White

opaque center. Frosted white front sections for subtle glow. Linear prisms to spread up/downlight.

•Only3-7/8"deep,meetsAmericanWithDisabilitiesAct for wall mounted fixtures.

•Concealedpull-actionspring-loadedlatchestoretain lens.

•20gaugecoldrolledsteelpostpaintedbakedwhiteenamel end caps.

•Nominal4'length.•Four-waypullswitch,(120voltonly)optional.•Optionallowvoltageelectronicsequentialswitchfor

push button control of up/down lighting. UL 544 listed. Includes phone jack type receptacle.

Options & accessories page 4.216

Ballast type <10THD <20THD

Electronic T8 HI* SO*ElectronicT5P.S.(28Wor54W) PG –

* Instant start

Fusing: Suffix: A (Internalfast-blowfusing). Suffix: C (Internal slow-blow fusing).

3 ⅞" (95mm)

3 ⅞" (98mm)

48 ½" (1232mm)

24 ¼" (616mm)

6 ⅛" (156mm)

4 ¼"(108mm)

6" (1

52m

m)

3 ⅞" (95mm)

6" (1

52m

m)

Uplight or Downlight Up/Downlight

4" (102mm)

6"(152mm) 24" (610mm)

47 15�16" (1218mm)

Up/Down Light1 or 2 T5 or T8 Lamps

Independent Up/Down Light2 T5 or T8 Lamps

6 ⅛

" (15

5mm

)

6 ⅛

" (15

5mm

)

3 ⅞" (98mm)

Dorm Lyte

Ordering information

Type Size Lamps qty –type Wattage Catalog number

Up/Down Light 48"

1-T51-T81-T5HO2-T52-T82-T5HO

28W32W54W28W32W54W

DM4X128DM4X132DM4X154DM4X228DM4X232DM4X254

Independent Up or Down Light 48"

2-T52-T82-T5HO

28W32W54W

DM4R228DM4R232DM4R254

Dorm Lyte Voltage Ballast Options Wall Mounted 120=120V Seepage4.158 See page 4.158 Fluorescent 277=277V andpage4.216 UNV=120-277V (Elec.T8orT5Ballast)

UNVDM4X232 AHIExample

Dorm LyteWall mounted fluorescent luminaire

1' 15 35 52 35 15

3' 15 25 31 35 15

5' 12 14 16 14 12

7' 9 10 10 10 9

9' 8 8 8 8 7

11' 7 7 7 7 7

1' 3' 5' 7' 9'

35 to 40 fc reading plane(60° from horizontal)

3 ½'ReadingPlane

Reading Position 3'

5'

Reference data

Room Size: 12' x 10' x 8' Ceiling.

Reflection: 80-50-20.80LLF

Reading Area: 35-40fc

1' 15 35 52 35 15

3' 15 25 31 35 15

5' 12 14 16 14 12

7' 9 10 10 10 9

9' 8 8 8 8 7

11' 7 7 7 7 7

1' 3' 5' 7' 9'

35 to 40 fc reading plane(60° from horizontal)

3 ½'ReadingPlane

Reading Position 3'

5'

Page 162: Linear recessed and surface lighting

4.159Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

30˚

60˚600

1200

1800

Candlepower Curve

30˚

60˚1000

2000

3000

Candlepower Curve

14" (356mm)

2 ⅝"(67mm)

14" (356mm)

2 ⅝"(67mm)

9" (229mm)

2 ⅝"(67mm)

Features•Stepbackhousingforanapparentdepthof11/2".•Prismaticvirginacryliclens.•Luminouscatadioptricendcaps.•Twosideshelf-levelinglenshinging.•9"wide,4'nominallengths.•14"wide,4'nominallength.•Zip-clipflushmountonT-gridceilings.•Off-center7/8"K.O.forflushmounttoT-gridceiling.•OptionalUL-listedlowdensitymountingspacers.•Completelyassembledwithsetupendstolampholders.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1-2LampElectronicTT5(40W)SB*, PR** IB*1 - 3 Lamp Electronic T8 H3*, P3** O3*1 - 4 Lamp Electronic T8 H4*, P4** O4*LOL T8 Dimming – PS

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Canopy spacer:Suspendsfixture11/2"fromsurface.Order Catalog no. AC1 CSP.Stem and canopy sets:Suspendfixture6",12",18"or24"fromsurface.(Fourperfixtureisrecommended.)Catalog no.: ASC6 CSP(6");ASC12 CSP(12");ASC18 CSP (18"); ASC24 CSP(24").Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).Stems not available with 3 lamp unit.

WA4A232UNVHI

WB4B432UNVH4

Reference data

Efficiency 70.9% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 63.0W LuminaireEff(LER) 56.5

Reference data

Efficiency 70.1% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 84.4W LuminaireEff(LER) 71.0

Ordering informationType Size Lamp qty –type Catalog no.

Prismatic Luminaire 9"x49 9⁄16" 2-T8 WA4A232

Ordering informationType Size Lamp qty –type Catalog no.

Surface Prismatic Luminaire

14"x48 ¾"14"x48 ¾"14"x48 ¾"24"x48 ⅝"24"x48 ⅝"

2-T83-T84-T84-T82-TT5-40

WB4B232WB4B332WB4B432WB2B417WB2B2FT

Dominaire Voltage Ballast Options Surface Wrap 120=120V Seepage4.159 See page 4.159 Luminaire 277=277V andpage4.216 UNV=120-277V (Elec.T8Ballastonly)

Dominaire Voltage Ballast Options Surface Wrap 120=120V Seepage4.159 See page 4.159 Luminaire 277=277V andpage4.216 UNV=120-277V (Elec.T8Ballastonly)

UNV

UNV

WA4A232

WB4B432

A

A

HI

H4

Example

Example

Dominaire SurfaceSurface

Page 163: Linear recessed and surface lighting

4.160 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•Universalluminairethathasuplight/downlight

or downlight capabilities on the same fixture.•Lowbrightnesscontrolleddownlightinganduplighting/

downlighting.•Lowbrightnesslinearprismaticvirginacrylicrefractor.•Invisiblesteellatchesalignrefractortohousing.•Individualorcontinuousrows.•Forovermirror,overbed,corridor,stairwellandbulletin

board applications.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

LWBU232UNVHI 1 & 2 Lamp Downlight

30˚

60˚

90˚0

210

420

630

Candlepower CurveReference data

Efficiency 62.4% Spacing ratio 1.2

Ordering informationType Size Lamp qty –type Catalog no.

Downlight

7 ⅝"x25 ½"7 ⅝"x37 ½"7 ⅝"x49 ½"

1-T8LWBU117LWBU125LWBU132

7 ⅝"x25 ½"7 ⅝"x37 ½"7 ⅝"x49 ½"

2-T8LWBU217LWBU225LWBU232

LWBU Voltage Ballast Options Wall Mounted 120=120V Seepage4.160 See page 4.160 Downlight 277=277V andpage4.216 Luminaire UNV=120-277V (Elec.T8Ballastonly)

UNVLWBU132 AHIExample

7 ⅝" (194mm)

3 1�16"(78mm)

Uplight Lens Cover

LWBU232UNVHI 1 & 2 Lamp Uplight/Downlight

30˚

60˚

90˚

45˚

450

0

450

900

Candlepower CurveReference data

Efficiency 65.2% Spacing ratio 1.2

Ordering informationType Size Lamp qty –type Catalog no.

Uplight / Downlight

7 ⅝"x25 ½"7 ⅝"x37 ½"7 ⅝"x49 ½"

1-T8LWBU117LWBU125LWBU132

7 ⅝"x25 ½"7 ⅝"x37 ½"7 ⅝"x49 ½"

2-T8LWBU217LWBU225LWBU232

LWBU Voltage Ballast Options Wall Mounted 120=120V Seepage4.160 See page 4.160 Uplight/Downlight 277=277V andpage4.216 Luminaire UNV=120-277V (Elec.T8Ballastonly)

UNVLWBU132 AHIExample

7 ⅝" (194mm)

3 1�16"(78mm)

Uplight Lens Cover

7 ⅝" (194mm)

3 1�16"(78mm)

Uplight Lens Cover

Uplight lens cover for downlight only

Controlled uplight/downlight (LWBU)

Uplight lens cover removed for uplight/downlight

LWBUUniversalWall mounted downlight or uplight/downlight

Page 164: Linear recessed and surface lighting

4.161Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Features•Forceilingorwall(verticallyorhorizontally)mounted

applications.•Only37/8"deep,meetsAmericanswithDisabilitiesAct(wallmounted).

•Lowbrightness.125thicklinearprismaticvirginacrylicrefractor.

•Invisiblespringsteellatchesalignrefractortohousing.•20gaugecoldrolledsteelpostpaintedbakedwhite

enamel end caps.•Forovermirror,overbed,corridor,stairwellandbulletin

board applications.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

LS4R232UNVHI 1 Lamp Downlight

30˚

60˚

90˚0

400

800

1200

Candlepower CurveReference data

Efficiency 73.9% Spacing ratio 1.3

Ordering informationType Size Lamp qty –type Catalog no.

Prismatic Lens Luminaire6"x23 15⁄16"6"x47 15⁄16"

2-T8 LS2R217LS4R232

LSW Voltage Ballast Options Wall or Ceiling 120=120V Seepage4.161 See page 4.161 Mounted 277=277V andpage4.216 Luminaire UNV=120-277V (Elec.T8Ballastonly)

UNVLS4R232 AHIExample

LS4R232UNVHI LS4R132UNVHI

6 ⅛" (155mm)6 ⅛" (155mm)

3 ⅞"(98mm)

3 ⅞"(98mm)

LS4R232UNVHI LS4R132UNVHI

6 ⅛" (155mm)6 ⅛" (155mm)

3 ⅞"(98mm)

3 ⅞"(98mm)

LS4R132UNVHI 2 Lamp Downlight

30˚

60˚

90˚0

190

380

570

Candlepower CurveReference data

Efficiency 76.9% Spacing ratio 1.4

Ordering informationType Size Lamp qty –type Catalog no.

Prismatic Lens Luminaire6"x23 15⁄16"6"x47 15⁄16"

1-T8 LS2R117 LS4R132

LSW Voltage Ballast Options Wall or Ceiling 120=120V Seepage4.161 See page 4.161 Mounted 277=277V andpage4.216 Luminaire UNV=120-277V (Elec.T8Ballastonly)

UNVLS4R132 AHIExample

LSWWall mounted/ceiling mounted

Page 165: Linear recessed and surface lighting

4.162 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•Only51/2"deep.•Welded20gaugesteelbody.•45°miteredcorners(bodyandlouver).•Side-mountedballastforcooleroperation.•3"deepaluminumparaboliclouver.•Verticalgrainonlouvereliminatesreflectedlampimage

on cross baffle.•MatchesDeepcel2x2and2x4recessed.•Perfectlyuniformfour-sideblackreveal.•Spring-loadedlatches.•Reversiblelouverhinging.•Doorjambwithintegralpositivelightstop.•FlushendK.O.’sforsmoothsurfaceappearance (atendofroworindividual).

•Louverhaspolyethylenedustguard.•MeetsNYCCoderequirements.

Options & accessories page 4.130Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Electronic T8 H3*, P3** O3*1 - 4 Lamp Electronic T8 H4*, P4** O4*1-3LampElec.TT5(40W) I3* X3*1&2LampElec.TT5(40W) IB*, PR** SB*

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Stem and canopy sets:Suspendfixture6",12",18"or24"fromsurface.(Fourperfixtureisrecommended.)Catalog no.: ASC6 CSP(6");ASC12 CSP(12");ASC18 CSP (18"); ASC24 CSP(24").Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Deepcel Surface 2' x 4' & 2' x 2'3" parabolic louver surface fluorescent luminaires

30˚

60˚1000

2000

3000

Candlepower CurveDPB2S18LS332UNVH3

24" (610mm)

5 ½"(140mm)

24" (610mm)

5 ½"(140mm)

24" (610mm)

5 ½"(140mm)

Reference data

Efficiency 69.6% Spacing ratio 1.6

Electronic ballast

Inputwatts(120V) 85.0W

Ordering informationType Cells Size Lamp qty –type Catalog no.

SurfaceParabolic

12182432

2' x 4'

2-T83-T83-T84-T8

DPB2S12LS232DPB2S18LS332DPB2S24LS332DPB2S32LS432

Deepcel Surface Voltage Ballast Options Surface3"Parabolic 120=120V Seepage4.162 See page 4.162 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVDPB2S9LS26U AHIExample

30˚

60˚600

1200

2400

Candlepower CurveDPB2S9LS26UUNVHI

24" (610mm)

5 ½"(140mm)

24" (610mm)

5 ½"(140mm)

24" (610mm)

5 ½"(140mm)

Reference data

Efficiency 57.6% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 60.0W

Ordering informationType Cells Size Lamp qty –type Catalog no.

SurfaceParabolic

912169991212

2' x 2'

2-T8 U62-T8 U62-T8 U63-T8 17W3-TT5Biax3-T8U1.63-TT5Biax3-T8U1.6

DPB2S9LS26UDPB2S12LS26UDPB2S16LS26UDPB2S9LS317DPB2S9LS3FTDPB2S9LS32UDPB2S12LS3FTDPB2S12LS32U

Deepcel Surface Voltage Ballast Options Surface3"Parabolic 120=120V Seepage4.162 See page 4.162 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVDPB2S18LS332 AH3Example

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 166: Linear recessed and surface lighting

4.163Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

30˚

60˚600

1200

1800

Candlepower Curve

The Prismalyte Surface box Available with your choice of 3 different Door frames.

To specify which Door frame you prefer, use door name abbreviation indicated in Catalog number (PNB2SRAVA232).

30˚

60˚600

1200

2400

Candlepower Curve

12" (305mm)

5 ½"(140mm)

12" (305mm)

5 ½"(140mm)

12" (305mm)

5 ½"(140mm)

24" (610mm)

5 ½"(140mm)

24" (610mm)

5 ½"(140mm)

Features•20gaugesteelhousing.•Housingmiteredcornerdetailing.•Only51/2"deep.•Dualsidewirewaysforcooleroperation.•Quickremoveballastcovers.•Fullyenclosedwiring.•Availableinthreelensframestyles.•Doorjambwithpositivelightstop.•Positivespring-loadedorcam-actionlatches.•Availablewithfloatingorfullsizedoors.•Aluminumdoorswithmiteredcorners.•MatchesPrismalytetroffer(seepage4.122).•MeetsNYCCoderequirements.•Matches1x4,2x2,2x4PrismalyteRecessed.

Options & accessories page 4.130Special lenses:VAlensisstandardvirginacrylic. For other available lenses, see page 4.130Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Electronic T8 H3*, P3** O3*1 - 4 Lamp Electronic T8 H4*, P4** O4*1-3LampElec.TT5(40W) I3* X3*1&2LampElec.TT5(40W) IB*, PR** SB*

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Stem and canopy sets:Suspendfixture6",12",18"or24"fromsurface.(Fourperfixtureisrecommended.)Catalog no.: ASC6 CSP(6");ASC12 CSP(12");ASC18 CSP (18"); ASC24 CSP(24").Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

Prismalyte Surface 2' x 4', 2' x 2' & 1' x 4'Premium specification lensed surface fluorescent luminaires

PNB1SRAVA232UNVHI

PNB2SRAVA26UUNVHI

Reference data

Efficiency 58.4% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 62.0W

Reference data

Efficiency 57.3% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 60.0W

Ordering informationType Size Lamp qty –type Catalog no.

SurfaceParabolic 1' x 4'

1-T82-T83-T8

PNB1SRAVA132PNB1SRAVA232PNB1SRAVA332

Ordering informationType Size Lamp qty –type Catalog no.

SurfaceParabolic 2' x 2'

2-T8 U63-TT53-T8 U1.6

PNB2SRAVA26UPNB2SRAVA3FTPNB2SRAVA32U

Prismalyte Surface Voltage Ballast Options Premium Lensed 120=120V Seepage4.163 See page 4.163 Surface Luminaire 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

UNVPNB1SRAVA232 AHIExample

24" (610mm)

5 ½"(140mm)

24" (610mm)

5 ½"(140mm)

30˚

60˚1200

2400

3600

Candlepower Curve

24" (610mm)

5 ½"(140mm)

PNB2SRAVA432UNVH4Reference data

Efficiency 60.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 112W

Ordering informationType Size Lamp qty –type Catalog no.

SurfaceParabolic 2' x 4'

2-T83-T84-T8

PNB2SRAVA232PNB2SRAVA332PNB2SRAVA432

FA =Flush Aluminum Full-Size Door

RF =RegressedAluminum Floating Door

RA =Regressed Aluminum Full-Size Door

Page 167: Linear recessed and surface lighting

4.164 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

30˚

60˚300

600

900

Candlepower Curve

12" (305mm)

5 ½"(140mm)

•••

• •

Features•20gaugesteelweldedbody.•Sidemountedballastforcooleroperation.•45°miteredcorners(bodyandlouver).•3"deepcellaluminumparaboliclouver(VRB).•Spring-loadedlatches.•Perfectlyuniformfoursidereveal.•Low-iridescence,semi-specularaluminum,standard.•Louverhaspolyethylenedustguard.•MeetsNYCCoderequirements.•Louverassemblycanbereplacedwithanyof3standard

Philips Lightolier Door frames.

Options & accessories page 4.216Louver finish: Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*LOL T8 Dimming – PS

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Stem and canopy sets:Suspendfixture6",12",18"or24"fromsurface.(Fourperfixtureisrecommended.)Catalog no.: ASC6 CSP(6");ASC12 CSP(12");ASC18 CSP (18"); ASC24 CSP(24").Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

VisionSmartSurface1'x4'Surface

VRB1S8LS132UNVHIReference data

Efficiency 66.0% Spacing ratio 1.9

Electronic ballast

Inputwatts(120V) 30.0W

Ordering informationType Cells Size Lamp qty –type Catalog no.

SurfaceParabolic

812 1' x 4' 1-T8

1-T8VRB1S8LS132VRB1S12LS132

812 1' x 4' 2-T8

2-T8VRB1S8LS232VRB1S12LS232

Vision Smart Voltage Ballast Options Surface 1' x 4' 120=120V Seepage4.164 See page 4.164 277=277V andpage4.216 UNV=120-277V (Elec.T8Ballastonly)

UNVVRB1S8LS132 AHIExample

8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell8 Cell 12 Cell

9 Cell 12 Cell 16 Cell 32 Cell18 Cell 24 Cell

12 Cell

Page 168: Linear recessed and surface lighting

4.165Comprehensive lighting catalog 7th Edition

Standard – Linear recessed and surface lighting

FS =FlushSteel RA =RegressedAluminum

Features•Shallow4"deep,20gaugesteelhousing.•Positivecam-actionlatchessecureframeoneitherside.•Centermountedballastcompartment.•Snap-onwiringchannelcoverisremovedwithouttools.•Matteblacklightsealonbothendstopreventlightleaks.

Options & accessories page 4.216Special lenses:VAlensisstandardvirginacrylic. For other available lenses, see page 4.130.Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 3 Lamp Electronic T8 H3*, P3** O3*1 - 4 Lamp Electronic T8 H4*, P4** O4*

* Instant start ** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Stem and canopy sets:Suspendfixture6",12",18"or24"fromsurface.(Fourperfixtureisrecommended.)Catalog no.: ASC6 CSP(6");ASC12 CSP(12");ASC18 CSP (18"); ASC24 CSP(24").Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

30˚

60˚550

1100

1650

Candlepower CurveSLB1SFSVA232UNVHI

24" (610mm)

24" (610mm)

24" (610mm)

4"(102mm)

4"(102mm)

4"(102mm)

12"(305mm)

24" (610mm)

24" (610mm)

24" (610mm)

24" (610mm)

24" (610mm)

4"(102mm)

4"(102mm)

4"(102mm)

4"(102mm)

4"(102mm)

4"(102mm)

Reference data

Efficiency 56.2% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 62.0W

Ordering informationType Door frame Size Lamp qty –type Catalog no.

SurfaceLuminaire

Flush Steel 1' x 4' 2-T8 SLB1SFSVA232

Regressed Aluminum 1' x 4' 2-T8 SLB1SRAVA232

SLB Voltage Ballast Options High Performance 120=120V Seepage4.165 See page 4.165 Lensed Surface 277=277V andpage4.216 Luminaire UNV=120-277V (Elec.T8Ballastonly)

UNVSLB1SFSVA232 HIExample

30˚

60˚550

1100

1650

Candlepower CurveSLB2SFSVA26UUNVHI

24" (610mm)

24" (610mm)

24" (610mm)

4"(102mm)

4"(102mm)

4"(102mm)

12"(305mm)

24" (610mm)

24" (610mm)

24" (610mm)

24" (610mm)

24" (610mm)

4"(102mm)

4"(102mm)

4"(102mm)

4"(102mm)

4"(102mm)

4"(102mm)

Reference data

Efficiency 63.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 60.0W

Ordering informationType Door frame Size Lamp qty –type Catalog no.

SurfaceLuminaire

Flush Steel 2' x 2' 2-T8 U64-17W

SLB2SFSVA26USLB2SFSVA417

Regressed Aluminum 2' x 2' 2-T8 U6

4-17WSLB2SRAVA26USLB2SRAVA417

30˚

60˚1200

2400

3600

Candlepower CurveSLB2SFSVA432UNVH4

24" (610mm)

24" (610mm)

24" (610mm)

4"(102mm)

4"(102mm)

4"(102mm)

12"(305mm)

24" (610mm)

24" (610mm)

24" (610mm)

24" (610mm)

24" (610mm)

4"(102mm)

4"(102mm)

4"(102mm)

4"(102mm)

4"(102mm)

4"(102mm)

Reference data

Efficiency 67.1% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 112.0W

Ordering informationType Door frame Size Lamp qty –type Catalog no.

SurfaceLuminaire

Flush Steel 2' x 4'2-T83-T84-T8

SLB2SFSVA232SLB2SFSVA332SLB2SFSVA432

Regressed Aluminum 2' x 4'

2-T83-T84-T8

SLB2SRAVA232SLB2SRAVA332SLB2SRAVA432

The Prismalyte Surface boxAvailable with your choice of 2 different door frames.

To specify which door frame you prefer, use door name abbreviation indicated in catalog number (PNB2SRAVA232).

SLB2'x4',2'x2'&1'x4'High performance lensed surface fluorescent luminaires

Highqualitysurfaceluminaireswith4"deephousings.Doorframesareextrudedaluminumorsteel.SLBseriessurfaceluminairescanbeusedinlowplenumdepthareasthatrequire surface luminaires.

Page 169: Linear recessed and surface lighting

4.166 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Standard

Features•Idealforlowceilingheightapplicationswhererecessed

units cannot be used.•213/16"totaldepth.•Step-backhousingforanapparentdepthof13/4".•Ashallowprofileandlinearprismaticsidescombineto

reduce ceiling contrast.•Virginacryliclenswithone-pieceextrudedprismatic

pattern 12 bottom and linear prism side walls.•Shieldinghingesfromeitherside(self-leveling).•Full-lengthballastcoversnaps-in,snaps-out(notools).•Individualorcontinuousrowinstallations.•Suitableformountingonlow-densitycellulose

f iberboard surfaces.•Suitablefordamplocations.

Jet Star LensSurface

Jet Star Corridor LensSurface

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI*, P2** SO*1 - 4 Lamp Electronic T8 H4*, P4** O4*LOL T8 Dimming – PS

* Instant start ** Program start For20WT12,useBallastsuffixPL .

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts or emergency pack, consult factory.Canopy spacer:Suspendsfixture11/4"fromsurface.Order Catalog no. AC1 CSP.Stem and canopy sets:Suspendfixture6",12",18"or24"fromsurface.(Fourperfixtureisrecommended.)Catalog no.: ASC6 CSP(6");ASC12 CSP(12");ASC18 CSP (18"); ASC24 CSP(24").Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

JS4A232UNVHI

JS4C132UNVHI

Reference data

Efficiency 85.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 56.0W LER 78.2

Reference data

Efficiency 84.3% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 34.3W LER 77.7

8 ¼" (108mm)

13 ¼" (339mm)

2 ½"(61mm)

2 ½"(61mm)

Ordering informationType Size Lamp qty –type Catalog no.

Jet StarLens Luminaire

8 ¼"x24"8 ¼"x24"8 ¼"x48"8 ¼"x96"

2-T122-T82-T84-T8*

JS2A220JS2A217JS4A232JS8A232

13 ¼"x48" 4-T8 JS4B432

* 2-Lamps In Tandem - 4 Lamps Total

Ordering informationType Size Lamp qty –type Catalog no.

Jet StarLens Luminaire

5 ½"x24"5 ½"x24"5 ½"x24"5 ½"x24"5 ½"x48"5 ½"x48"5 ½"x96"5 ½"x96"

1-T121-T82-T122-T81-T82-T82-T8*4-T8**

JS2C120JS2C117JS2C220JS2C217JS4C132JS4C232JS8C132JS8C232

5 ½"(140mm)

4 ¼"(108mm)

4 ⅛"(105mm)

1 ⅞"(48mm)

Jet Star Voltage Ballast Options Corridor lens 120=120V Seepage4.166 See page 4.166 Surface 277=277V andpage4.216 UNV=120-277V (Elec.T8Ballastonly)

UNVJS4C132 AHIExample

30˚

60˚550

1100

Candlepower Curve

30˚

60˚280

560

Candlepower Curve

*1-Lamp in tandem - 2 lamps total**2-Lamps in tandem - 4 lamps totalFor T5 options consult factory

Jet Star lens Voltage Ballast Options Surface 120=120V Seepage4.166 See page 4.166 277=277V andpage4.216 UNV=120-277V (Elec.T8Ballastonly)

UNVJS4A232 AHIExample

Reference data

Efficiency 90.7% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 57.0W LER 81.6

8 ¼" (108mm)

13 ¼" (339mm)

2 ½"(61mm)

2 ½"(61mm)

30˚

60˚550

1100

Candlepower Curve

Page 170: Linear recessed and surface lighting

4.167Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Pristine > 4.168 Taskmaster I > 4.169 Taskmaster II > 4.169 Taskmaster Solid Front T8 > 4.170 Taskmaster Solid Front T5 > 4.171

Contents

Task lighting

Page 171: Linear recessed and surface lighting

4.168 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•Architecturallypleasingroundedslimprofileonly3/4"deepx4-3/4"wide.

•Providesmedianfootcandlelevelof55on2'x5'desk top.

•Prismaticacrylicspreadlens.•Flushpushbuttonswitch.•Electronicprogramstart<10THDballast.•LampT213W,CRI=80,colortemperature3500K,

lamp is included.•Ninefootstraightblackcord.•Bakedpewterpolyesterenamelfinishforcordandplug.•Bakedwhitepolyesterenamelfinishforhardwireoption.•MeetsNewYorkCityrequirementsfortasklighting.

Please consult factory for any further options.

PristineT2 Task lighting

PristineHard wire series

AluminumReflector

4 ¾" (121mm)

1 ⅜"(35mm)

¾"(19mm)

Nine FootStraight Cord

22" (559mm)

4 ¾"(121mm)

12" (305mm)5 1�16"(132mm)

AluminumReflector

4 ¾" (121mm)

1 ⅜"(35mm)

¾"(19mm)

Nine FootStraight Cord

22" (559mm)

4 ¾"(121mm)

12" (305mm)5 1�16"(132mm)

Ordering informationType Color Length Lamp qty –type Lamp watts Catalog no.

Pristine One Lamp with Cord and Plug Pewter 22” 1-T2 13W PC2P13T2120PTCPB

Pristine One Lamp with Chicago Style Plug Pewter 22” 1-T2 13W PC2P13T2120PTCPBCH

Ordering informationType Color Length Lamp qty –type Lamp watts Catalog no.

Pristine One Lamp Hardwire White 22” 1-T2 13W PC2W13T2120PTHW

AluminumReflector

4 ¾" (121mm)

1 ⅜"(35mm)

¾"(19mm)

Nine FootStraight Cord

22" (559mm)

4 ¾"(121mm)

12" (305mm)5 1�16"(132mm)

2 ~ ⅞" K.O.

2 ~ ⅞" K.O.Center Line

4 ¾"(121mm)

5 1�16"(132mm)

6" (153mm)

8"(203mm)

12" (305mm)

22" (559mm)

3" (76mm)

T2 Lamp

6 3�16" (161mm)

AluminumReflector

4 ¾" (121mm)

1 ¼"(32mm)

¾"(19mm)

1 ¼"(32mm)

2 ~ ⅞" K.O.

2 ~ ⅞" K.O.Center Line

4 ¾"(121mm)

5 1�16"(132mm)

6" (153mm)

8"(203mm)

12" (305mm)

22" (559mm)

3" (76mm)

T2 Lamp

6 3�16" (161mm)

AluminumReflector

4 ¾" (121mm)

1 ¼"(32mm)

¾"(19mm)

1 ¼"(32mm)

2 ~ ⅞" K.O.

2 ~ ⅞" K.O.Center Line

4 ¾"(121mm)

5 1�16"(132mm)

6" (153mm)

8"(203mm)

12" (305mm)

22" (559mm)

3" (76mm)

T2 Lamp

6 3�16" (161mm)

AluminumReflector

4 ¾" (121mm)

1 ¼"(32mm)

¾"(19mm)

1 ¼"(32mm)

Backwall

Desktop

Pristine

Pristine

Page 172: Linear recessed and surface lighting

4.169Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Features•11/8"shallowdepth.•Fivenominallengths:12",21",24",33",42".•Groundedconvenienceoutlet(optional).•On/offrockerswitch(includedinsupplypack).•Bakedwhiteenamelfinish.

Options & accessoriesAccessories that will ship separately order the following:

GLR-B(6packof3ampfusing)

RIF-SUPR(1-RFIsuppressor)

CONV OUTLET 10-pack (10packofoutletsandhardware)

Accessories are for f ield installation.

Features•17/8"shallowdepth.•Fournominallengths:18",24",36",48".•Groundedconvenienceoutlet(optional).•On/offrockerswitch,standard(includedinsupplypack).•Bakedwhiteenamelfinish.

Options & accessoriesAccessories that will ship separately order the following:

GLR-B(6packof3ampfusing)

RIF-SUPR(1-RFIsuppressor)

CONV OUTLET10-PACK (10packofoutletsandhardware)

Accessories are for f ield installation.

Taskmaster IIUnder shelf luminaires

Ordering informationType Length Lamp watts/Type Catalog no.

Taskmaster I (OneLamp)

12 ¼"21 ¼"33 ½"

8PH13PH8PH/13PH(1each)

TSL0018W BPRTSL0113W BPRTSL1813W BPR

Taskmaster I (TwoLamp)

24 ¼"42 ½"

8PH13PH

TSL0028W BPRTSL0213W BPR

Ordering informationType Length Lamp qty –type Lamp watts Catalog no.

Taskmaster II

18⅛"24⅛"36⅛"48⅛"24⅛"36⅛"48⅛"

TS-T12TS-T12TS-T12TS-T12T8T8T8

15W20W30W40W17W25W32W

TCU15W120P BPRTCU20W120P BPRTCU30W120P BPRTCU40W120P BPRTCU20WUNVRO BPRTCU30WUNVRO BPRTCU40WUNVRO BPR

5" (127mm)

1 ⅛"(29mm)

5¼" (134mm)

1 ⅞"(48mm)

5" (127mm)

1 ⅛"(29mm)

5¼" (134mm)

1 ⅞"(48mm)

Taskmaster I Under Shelf Luminaire

For electronic ballast, substitute TSLP for TSL , e.g: TSLP0018W BPR .

TSL0018W BPRExample

Attractive, unobtrusive lighting

Lamp/fixture Bulk pack Taskmaster II length/watts Finish Voltage Ballast rocker switch Undershelf 15=15WTST12(Nom.18") W =White 120 =120V P =Standard Warning(277BPR)Bulk Luminaire 20=20WTST12or17WT8(Nom.24") (T12Only) Magnetic T12 pack rocker switch can 30 =30WRST12or25WT8(Nom.36") UNV=120-277V RO =RapidStart notbeinstalledonfixture 40=40WRST12or32WT8(Nom.48") (Elec.T8Ballastonly) <10THDT8 if277Visbeingrun.

TCU W40Example UNV RO BPR

Taskmaster

Taskmaster

Taskmaster IUnder shelf luminaires

Page 173: Linear recessed and surface lighting

4.170 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Taskmaster Solid Front T8Specification undershelf luminaire

Features•1¾”shallowdepth.•Threenominallengths:24",36",48"•Specif icationgradeundershelfluminaire.•Solidfrontdesign.•Lensremovablewithouttoolsforeasymaintenance.•100%acryliclinearprismaticlenstoobscurelampimage

and uniformly distribute light output•LampT8,CRI=70,colortemp3500K,isstandard

and included.•Paintafterfabricationwithwhitepolyesterpaintf inish.•On/offrockerswitch(includedinsupplypack) 120 volt use only.•Universalvoltage.

Options & accessoriesAccessories that will ship separately order the following:

GLR-B(6packof3ampfusing)

RIF-SUPR(1-RFIsuppressor)

CONV OUTLET(10PACK)

LC

CL

CL

⅝"(16mm)

½" (13mm) Dia. K.O.This End Only

5 ¼" (133mm)

1 ¾"(44mm)

7�16" (11mm) Dia. K.O.Each End

⅞" (22mm) Dia. K.O.Each End

⅞" (22mm) Dia. K.O. (2)(One Top/One Back)

4 ¼"(108mm)

5 ¼"(133mm)

2 7�16"(62mm)

24 1�16" (611mm)

3�16" (5mm)Dia. Hole (4)(2 Top/2 Back)

Keyhole K.O. (2)

36 1�16" (916mm)

⅞" (22mm) Dia. K.O. (2)(One Top/One Back)

2 7�16"(62mm)

3�16" Dia. Hole (4)(2 Top/2 Back)

Keyhole K.O. (2)

⅞" (22mm) Dia. K.O. (2)(One Top/One Back)

48 1�16" (1221mm)

Keyhole K.O. (2)

3�16" Dia. Hole (4)(2 Top/2 Back)

2 7�16"(62mm)

5 ¼"(133mm)

4 ¼"(108mm)

4 ¼"(108mm)

5 ¼"(133mm)

Ordering informationType Length Lamp qty –type Lamp watts Catalog no. Electronic ballast type

Taskmaster Sold Front T8

24 1 ⁄16"36 1 ⁄16"48 1 ⁄16"

1-T817W25W32W

TCF117WUNVRO BPRTCF125WUNVRO BPRTCF132WUNVRO BPR

<10ProgramRapidStart

24 1 ⁄16"36 1 ⁄16"48 1 ⁄16"

1-T817W25W32W

TCF117WUNVHI BPRTCF125WUNVHI BPRTCF132WUNVHI BPR

<10Instantstart

Lamp/fixture Bulk pack Taskmaster Lamp length/watts Finish Voltage Ballast rocker switch Solid Front T8 Specif ication 1=Number 17 =17WT8(Nom24") W =White UNV=120-277V HI =Instantstart Canonlybeinstalled Undershelf Luminaire of Lamps 25 =25WT8(Nom36") (Elec.T8Ballastonly) <10THDT8 ina120voltapplication 32 =32WT8(Nom48") RO=RapidStart <10THDT8

1TCF W32Example UNV RO BPR

Taskmaster

Page 174: Linear recessed and surface lighting

4.171Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Taskmaster Solid Front T5Specification undershelf luminaire

Features•11/8”shallowdepth.•Threenominallengths:22”,34”,46”•Specif icationgradeundershelfluminaire.•Solidfrontdesign.•Lensremovablewithouttoolsforeasymaintenance.•100%acryliclinearprismaticlenstoobscurelampimage

and uniformly distribute light output•LampT5,CRI=80,colortemp3500K,isstandard

and included.•Paintafterfabricationwithwhitepolyesterpaintf inish.•On/offrockerswitch(includedinsupplypack)

120 volt use only.•Universalvoltage.

Options & accessoriesAccessories that will ship separately order the following:

GLR-B(6packof3ampfusing)

CONV OUTLET(10pack)

5" (127mm)

1 ⅛"(29mm)

½"(13mm)

⅝" (16mm) Dia.

22 ¾" (578mm)

1 ½"(38mm)

2 ½"(64mm)

5"(127mm)

1 ¾"(45mm)

1 ¾"(45mm)

2 ⅜"(60mm) Keyhole K.O. (2)

11 ⅜"(289mm)

3�16" (5mm)Dia. Hole (2)

.53" (13mm) Dia. K.O. (6)(3 Top/3 Back)

34 ½" (876mm)

3�16" (5mm)Dia. Hole (2)

2 ½"(64mm)

5"(127mm)

1 ¾"(45mm)2 ⅜"

(60mm) Keyhole K.O. (2)

1 ¾"(45mm)

.53" (13mm) Dia. K.O. (6)(3 Top/3 Back)

1 ½"(38mm)

17 ¼"(438mm)

.53" (13mm) Dia. K.O. (6)(3 Top/3 Back)

1 ½"(38mm)

2 ⅜"(60mm) Keyhole K.O. (2)

1 ¾"(45mm)

1 ¾"(45mm)

2 ½"(64mm)

5"(127mm)

46 ¼" (1175mm)

23 ⅛"(587mm)

3�16" (5mm)Dia. Hole (2)

1 ½"(38mm)

Ordering informationType Length Lamp qty –type Lamp watts Catalog no. Electronic ballast type

Taskmaster Sold Front T5

22 ¾”34 ½”46 ¼”

1-T514W21W28W

TSF114WUNVPG BPRTSF121WUNVPG BPRTSF128WUNVPG BPR

<10ProgramRapidStart

Lamp/fixture Bulk pack Taskmaster Lamp length/watts Finish Voltage Ballast rocker switch Solid Front T8 Specif ication 1=Number 14 =14WT5(Nom22") W =White UNV=120-277V HI=ProgramRapidStart Canonlybe Undershelf Luminaire of Lamps 21 =21WT5(Nom34") (Elec.T5Ballastonly) <10THDT5 installedina 28 =28WT5(Nom46") 120Vapplication

1TSF W28Example UNV PG BPR

Taskmaster

Page 175: Linear recessed and surface lighting

Linear recessed and surface lighting

4.172 Philips Lightolier For complete specif ication information visit www.lightolier.com

Special purpose & industrial

Special purpose luminaires that address vandal, wet and cleanroom application needs. Industrial lighting for enclosed or open luminaires where special construction is provided to meet concerns of hazardous and industrial areas for proper and safe lighting levels.

Page 176: Linear recessed and surface lighting

Linear recessed and surface lighting

4.173Comprehensive lighting catalog 7th Edition

FluorescentHigh&LowBays > 4.174 Cleanguard Class > 4.186 Hazardline > 4.188 Sealatron > 4.190 Cleanguard Wet > 4.192 Cleanlite > 4.193 GuardsmanVandalResistant > 4.194 IC Series > 4.198 TU Turret Industrial > 4.200 KD/KWIndustrial > 4.201

Contents

Page 177: Linear recessed and surface lighting

4.174 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

90° 90°

90° 90°

90° 90°

Contoured Miro IV specular reflector

Features a mirrored silver finish designed to concentrate beam spread and optimize lamp performance making it ideal to concentrate light on the racks of a warehouse or a store.

Flat white reflector

In gymnasiums, low-glare and wide light distribution which can be provided by a flat white reflector are a must.

Flat Miro IV specular reflector

For assembly plant as well as retail open area, a flat design reflector with mirrored silver finish produces very wide light distribution and optimizes efficiency.

Fluorescent high & low baysCurrent statistics reveal 65% of the energy is being consumed by the commercial and industrial markets and 22% of this energy is being utilized for lighting alone. Smart business managers have discovered the incredible energy savings of up to 50% by replacing traditional HID high bay fixtures with efficient linear fluorescent T5HO and T8 luminaires. These are the ideal green solution and have the added benefits of high Philips Lightolier, illumination uniformity and instant-on starting.

A wide variety of T5 and T8 fluorescent fixtures are offered by Philips Lightolier for high and low bay lighting, all providing exceptional features for the application they were designed for. Here are some features you may want to consider when choosing a fluorescent high bay.

Light beam

Uplight vs. downlight only Motion sensors for additional savings

1. Selecting the right reflector is just as important as choosing the right luminaire. Reflectors determine how light is distributed in a space. Each reflector design has a specif ic light distribution function that is suited to certain applications better than others.

2. A well-lit, inviting ceiling appearance contributes to a store's or working's positive ambience. Darker ceilings produce a more closed-in feeling, uncomfortable to most people. Uplight reduces the cave effect, expands the space and makes it look cleaner.

3. Byincludingoccupancysensorcontrols,theenergyreductionisevengreater,especially in areas of a facility that have limited traff ic. Unlike HID lamping, adding occupancy sensors to T5HO and T8 systems is relatively easy and inexpensive. If

the addition of a sensor makes you nervous, consider using the Smart TriLyte turnkey solution which has the technology to optimize lamp life.

Whether it is for industrial, recreational or commercial uses, you will f ind that Philips Lightolier’s f luorescent high bays deliver great lighting packages, superior energy efficiency and occupancy sensing capabilities.

Page 178: Linear recessed and surface lighting

4.175Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Trilyte Nordik

The same light output at -18°C as the regular TriLyte at 25°C, making it perfect for cold storage.

Gymlyter

Highly resistant, full body luminaire with strong wireguard.

Trilyte

The best design in its category including ballast ventilation and body strength. Most versatile high bay in regards to application, especially in industrial aisles.

Smart Trilyte

TriLyte including Philips Alto low mercury lamps, Advance electronic ballast and a sensor optimizing lamp life and energy savings. Guaranteed for 3 years.

Fluorescent high bay Selection chart

Design Lamp Distribution Reflector Application Mounting Accessories

Lam

ps

War

rant

y

Nar

row

Wid

e

T5

T8

Dow

nlig

ht/

Upl

ight

Dow

nlig

ht

Con

tour

ed M

IRO

IV

Flat

MIR

O IV

Flat

Whi

te

Indu

stri

al

Rec

reat

ive

Ret

ail

Col

d En

viro

nmen

ts*

Hot

En

viro

nmen

ts**

Surf

ace

Pend

ant

Cha

in

Ster

n

Sens

or

Doo

r

Wir

egua

rd

Trilyte 2, 3, 4, 4T

6 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●

Smart Trilyte 4 6 ● ● ● ● ● ● ● ● ● ● ● ● STD ● STD 3 years

TrilyteNordik 4 6 T5HO ● ● ● ● ● STD STD

Gymlyter 2, 3, 4, 4T

6 ● ● ● ● STD ● ● ● ● ● ● ● STD ●

STD=StandardT=Lampsintandem(e.g.4Tmeans8lampstotal)**Ratedforusefrom5°Cto55°Cambient(withoutlens).**Rated for use from -18°C to 5°C ambient.For any special solution, contact your Philips Lightolier representative.

Page 179: Linear recessed and surface lighting

4.176 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

2 ¾"(70mm)

17"(432mm)

13 ⅜"(340mm)

36"(914mm)

17 "(432mm)

8 ¾"(222mm) Narrow-Body 4'

49 ½"(1257mm)

98 ¼"(2496mm)

17 "(432mm)

8 ¾"(222mm)

36"(914mm)

36"(914mm)

Narrow-Body 8'

TriLyteNarrowNarrow-body 2, 3 & 4 lamp lowbay surface/pendant luminaire

DesignedforTrade(commercialspaces),RecreationalandIndustriallocations,TriLyteprovides much needed versatility in lowbay applications. Using the appropriate lamp, wattage and reflector options, this narrow-body version is also suitable for highbay lighting, particularlyretailoutletsandindoorsportsfacilities.Itslow-profilehousing(almost1"shallowerthanmostcompetingmodels)isperfectforareasthatplaceapremiumonluminaire appearance. Dual-circuit TriLyte equipped with optional motion sensor delivers added lighting control flexibility for industrial applications.

Features•Sturdyone-piecepost-paintedhousingprovidingclean,

smooth,installation-friendly corners.•Side-mountedballastforlow2-3/4"profile.•Mountingheightsfrom12'to45'withsuitablelamping-

reflector lens selection.•2,3and4-lampversions(cross-sectionview).•Availablein4'and8'lengths.•Choiceofcontouredspecular,f latspecularorflat

white reflector.•Contouredspecularreflectoroffersoptimum

performance and 95% reflectivity (not available on 2-lampmodel).

•Choiceofstem,surfaceorchainmounting.•Acceptsemergencybatterypacks.•Availablemotionsensorallowsfortotallightingcontrol,

added energy savings.

Options & accessoriesBallast:Specifyvoltage(120,277orUNV)

and add as suffix, e.g. 120PU.

Ballast type <10THD

Elect.I.S.T8,(1)4-Lamp H4Elect.I.S.T8,(1)4-Lamp&(1)2-Lamp H5Elect.I.S.T8,(2)4-Lamp H7 one 4-Lamp ballast to operate outside lamps one 4-lamp ballast to operate inside lamps

Elect.P.S.T5/T5HO,(1)2-Lamp PGElect.P.S.T5/T5HO,(1)3-Lamp PUElect.P.S.T5/T5HO,(1)4-Lamp PVElect.P.S.T5/T5HO,(1)4-Lamp&(1)2-Lamp P6 one 4-Lamp ballast to operate outside lamps one 2-lamp ballast to operate inside lamps

Elect.P.S.T5/T5HO,(2)3-Lamp P7 one 3-Lamp for 1, 3, & 5 and one 3-Lamp for 2, 4, & 6

Elect.P.S.T5/T5HO,(2)4-Lamp P8 one 4-Lamp for 1, 3, & 5 and one 4-Lamp for 2, 4, & 6

Consult your representative for other ballast options.

Electrical/wiring options: Consult your Philips Lightolier representative.Stem and canopy sets 4 stems required per luminaire. Order cat. no. ASC12 CSP (12"), ASC18 CSP(18"),ASC24 CSP(24"),ASC36 CSP(36"),ASC48 CSP (48").Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C (Internalslow-blowfusing).Chain hanger kit: 2 kits required per luminaire. Order catalog number EE9HC.Wireguard/lens:Varietyofshieldingoptionsavailable.Luminaire-mounted motion sensor: 360° coverage. Field installed. Only available on luminaires with contoured specular reflectors. Order catalog number FH360.Remote-mounted motion sensor:Narrowcoverage.Field installed. Order catalog number FH110.

FH4C4DXX454120PV

30˚

60˚3000

6000

9000

Candlepower CurveReference data

Efficiency 89.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 58W LER FI-T 6.0

VA =Pattern 12 prismatic lens madeofvirginacrylic(.095"nominal).Completewithhinged white wireguard.

VI = Pattern12prismaticlensmadeofvirginacrylic(.125"nominal).Completewithhinged white wireguard.XX =Versionwithoutlensshielding.

WW =Whitehingedwireguardonly(nolens),9-gaugewire adding rigidity to luminaire.

RCP C.U.

1

2

3

4

5

6

7

8

9

10

63

57

51

45

41

37

33

30

27

24

Application data*

Luminaire spacing FC W/Sq Ft

300' x 400' x 25' Space 17' on center 50 0.81

120' x 80' x 28' Space 16' on center 55 0.98

300' x 400' x 25' Space 14' on center 75 1.15

*AverageFootcandlesMaintained.TotalLLF=0.84. Reflectance: 80% Ceiling, 50% Wall, 20% Floor. 54W T5HO lamp rated at 4400 lumens at 25°C.

Page 180: Linear recessed and surface lighting

4.177Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Luminaire type

Luminaire length Body style Width Type Lens/shielding

Lamp qty in a luminaire cross-section Lamp/type Voltage Ballast Options

FH=TriLyte 4=4'

8=8'

W =FlatDesignWhite Reflector

C =ContouredSpecular Reflector

S =FlatDesignSpecular Reflector

4=17" D=Downlight VA=PrismaticLensVAwithWireguard

VI=PrismaticLensVI withWireguard

WW =Wireguard,White/NoLens

XX=NoShielding

2=2Lamps

3=3Lamps

4=4Lamps

28=T528W

32=T832W

54=T5HO54W

120=120V

277=277V

UNV=120-277V

See previous page

See previous page

TriLyteNarrowNarrow-body 2, 3 & 4 lamp lowbay surface/pendant luminaire

DesignedforTrade(commercialspaces),RecreationalandIndustriallocations,TriLyteprovides much needed versatility in lowbay applications. Using the appropriate lamp, wattage and reflector options, this narrow-body version is also suitable for highbay lighting, particularlyretailoutletsandindoorsportsfacilities.Itslow-profilehousing(almost1"shallowerthanmostcompetingmodels)isperfectforareasthatplaceapremiumonluminaire appearance. Dual-circuit TriLyte equipped with optional motion sensor delivers added lighting control flexibility for industrial applications.

Ordering information for T5

Type Lamp qty/type

Lamp/luminaire nominal length

Luminaire width Catalog no.

PrismaticLens(VI)with Wireguard

2-T5HO 3-T5HO 4-T5HO 6-T5HO 8-T5HO

48" 48" 48" 96"tandem 96"tandem

17"

FH4W4DVI254UNVPG FH4C4DVI354UNVPG FH4C4DVI454UNVPG FH8C4DVI354UNVP6 FH8C4DVI454UNVP8

White Wireguard withNoLens

2-T5HO 3-T5HO 4-T5HO 6-T5HO 8-T5HO

48" 48" 48" 96"tandem 96"tandem

17"

FH4W4DWW254UNVPG FH4C4DWW354UNVPG FH4C4DWW454UNVPG FH8C4DWW354UNVP6 FH8C4DWW454UNVP8

Ordering information for T8Type Lamp

qty/typeLamp/luminaire nominal length

Luminaire width

Catalog no.

PrismaticLens(VI)with Wireguard

2-T8 3-T8 4-T8 6-T8 8-T8

48" 48" 48" 96"tandem 96"tandem

17"

FH4W4DVI232UNVHI FH4C4DVI332UNVH3 FH4C4DVI432UNVH4 FH8C4DVI332UNVH5 FH8C4DVI432UNVH7

White Wireguard withNoLens

2-T8 3-T8 4-T8 6-T8 8-T8

48" 48" 48" 96"tandem 96"tandem

17"

FH4W4DWW232UNVHI FH4C4DWW332UNVH3 FH4C4DWW432UNVH4 FH8C4DWW332UNVH5 FH8C4DWW432UNVH7

FH 4 4W D WW 4 54 UNV PV

Basic catalog no. Voltage Ballast Options TriLyte Luminaire 120=120V Seepreviouspage Seepreviouspage 277=277V UNV=120-277V

FH4W4DWW454 UNV APVExample

Numberinglogic

Acronyms usedCU =Coefficientsofutilization FC =FootcandlesIS =InstantstartLLF =Light loss factorPS = Program start RCR =Room cavity ratio THD =Total harmonic distortion

Page 181: Linear recessed and surface lighting

4.178 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

TriLyte WideWide-body 6 lamp highbay surface/pendant luminaire

DesignedforTrade(commercialspaces),RecreationalandIndustriallocations,TriLyteprovides much needed versatility in highbay applications. Using the appropriate lamp, wattage and reflector options, this wide-body version is also suitable for lowbay lighting, particularly retailoutletsandindoorsportsfacilities.Itslow-profilehousing(almost1"shallowerthanmostcompetingmodels)isperfectforareasthatplaceapremiumonluminaireappearance.Dual-circuit TriLyte equipped with optional motion sensor delivers added lighting control flexibility for industrial applications.

Features•Sturdyone-piecepost-paintedhousingprovidingclean,

smooth, installation-friendly corners.•Side-mountedballastforlow2-3/4"profile.•Mountingheightsupto45'.•6-lampversionsonly(cross-sectionview).•Availablein4'lengthsonly.•Choiceofcontouredspecularorflatwhitereflector.•Contouredspecularreflectoroffersoptimum

performance and 95% reflectivity.•Choiceofstem,surfaceorchainmounting.•Acceptsemergencybatterypacks.•Availablemotionsensorallowsfortotallightingcontrol,

added energy savings.

Options & accessoriesBallast:Specifyvoltage(120,277orUNV)

and add as suffix, e.g. UNVPG.

Ballast type <10THD

Elect.I.S.T8,(1)4-Lamp&(1)2-Lamp H5Elect.P.S.T5/T5HO,(1)4-Lamp&(1)2-Lamp P6 one 4-Lamp ballast to operate outside lamps one 2-lamp ballast to operate inside lamps

Elect.P.S.T5HO,(2)3-Lamp P7 one 3-Lamp for 1, 3, & 5 and one 3-Lamp for 2, 4, & 6

Consult your representative for other ballast options.

Electrical/wiring options: Consult your Philips Lightolier representative.Stem and canopy sets: 4 stems required per luminaire. Order cat. no. ASC12 CSP(12"), ASC18 CSP (18"),ASC24 CSP(24"), ASC36 CSP(36"),ASC48 CSP (48").Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C (Internalslow-blowfusing).Chain hanger kit 2 kits required per luminaire. Order catalog number EE9HC.Wireguard/lensVarietyofshieldingoptionsavailable.Luminaire-mounted motion sensor 360° coverage. Field installed. Only available on luminaires with contoured specular reflectors. Order cat. no. FH360.Remote-mounted motion sensor Narrowcoverage.Field installed. Order catalog number FH110.

FH4C5DXX654UNVP6Reference data

Efficiency 90.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 234W LER 1.00

23 ⅛"(587mm)

23 ⅛"(587mm)

2 ¾"(70mm)

19 ⅝"(498mm)

15"(381mm)

36"(914mm)

49 ½"(1257mm)

30˚

60˚3000

6000

9000

Candlepower CurveRCP C.U.

1

2

3

4

5

6

7

8

9

10

100

92

85

79

72

67

62

58

53

49

Application data*

Luminaire spacing FC W/Sq Ft

120' x 80' x 28' Space 240 sq ft per lum. 80 1.5

120' x 80' x 28' Space 20' on center 50 1.9

300' x 400' x 25' Space 18' on center 75 1.1

*Averagefootcandlesmaintained.TotalLLF=0.84. Reflectance: 80% Ceiling, 50% Wall, 20% Floor. 54W T5HO lamp rated at 4400 lumens at 25°C.

**Averagefootcandlesmaintained.TotalLLF=0.84. Reflectance: 50% Ceiling, 30% Wall, 20% Floor. 54W T5HO lamp rated at 4400 lumens at 25°C.

VA =Pattern 12 prismatic lens madeofvirginacrylic(.095"nominal).Completewithhinged white wireguard.

VI = Pattern12prismaticlensmadeofvirginacrylic(.125"nominal).Completewithhinged white wireguard.

WW =Whitehingedwireguardonly(nolens),9-gaugewireadd-ing rigidity to luminaire.

XX =Versionwithoutlensshielding.

Page 182: Linear recessed and surface lighting

4.179Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Luminaire type

Luminaire length Body style Width Type Lens/shielding

Lamp qty in a luminaire cross-section Lamp/type Voltage Ballast Options

FH=TriLyte 4=4' W =FlatDesignWhite Reflector

C =ContouredSpecular Reflector

5=23" D=Downlight VA=PrismaticLensVAwithWireguard

VI=PrismaticLensVI withWireguard

WW =Wireguard,WhitewithNoLens

XX=NoShielding

6=6Lamps 28=T528W

32=T832W

54=T5HO54W

120=120V

277=277V

UNV=120-277V

See previous page

See previous page

TriLyte WideWide-body 6 lamp highbay surface/pendant luminaire

DesignedforTrade(commercialspaces),RecreationalandIndustriallocations,TriLyteprovides much needed versatility in highbay applications. Using the appropriate lamp, wattage and reflector options, this wide-body version is also suitable for lowbay lighting, particularly retailoutletsandindoorsportsfacilities.Itslow-profilehousing(almost1"shallowerthanmostcompetingmodels)isperfectforareasthatplaceapremiumonluminaireappearance.Dual-circuit TriLyte equipped with optional motion sensor delivers added lighting control flexibility for industrial applications.

Ordering information for T5

Type Lamp qty/type

Lamp/luminaire nominal length

Luminaire width Catalog no.

PrismaticLens(VI) with Wireguard 6-T5HO 48" 23" FH4C5DVI654UNVP6

White Wireguard withNoLens 6-T5HO 48" 23" FH4C5DWW654UNVP6

Ordering information for T8Type Lamp

qty/typeLamp/luminaire nominal length

Luminaire width

Catalog no.

PrismaticLens(VI)with Wireguard 6-T8 48" 23" FH4C5DVI632UNVH5

White Wireguard withNoLens 6-T8 48" 23" FH4C5DWW632UNVH5

FH 4 5W D WW 6 54 UNV P6

Basic Catalog no. Voltage Ballast Options TriLyte Luminaire 120=120V Seepreviouspage Seepreviouspage 277=277V UNV=120-277V

FH4W5DWW654 UNV P6Example

Acronyms usedCU =Coefficientsofutilization FC =FootcandlesIS =InstantstartLLF =Light loss factorPS = Program start RCR =Room cavity ratio THD =Total harmonic distortion

Numberinglogic

Page 183: Linear recessed and surface lighting

4.180 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

2 ¾"(70mm)

17"(432mm)

13 ⅜"(340mm)

36"(914mm)

17 "(432mm)

8 ¾"(222mm) Narrow-Body 4'

49 ½"(1257mm)

98 ¼"(2496mm)

17 "(432mm)

8 ¾"(222mm)

36"(914mm)

36"(914mm)

Narrow-Body 8'

36"(914mm)

17 "(432mm)

8 ¾"(222mm) Narrow-Body 4'

49 ½"(1257mm)

98 ¼"(2496mm)

17 "(432mm)

8 ¾"(222mm)

36"(914mm)

36"(914mm)

Narrow-Body 8'

VA =Pattern 12 prismatic lens madeofvirginacrylic(.095"nominal).Completewithhinged white wireguard.

VI = Pattern12prismaticlensmadeofvirginacrylic(.125"nominal).Completewithhinged white wireguard.

White hinged 9-gauge wireguard adding rigidity to luminaire available as an accessory. (FH4WG4 for narrow luminaire and FH4WG5 for wide luminaire. Add VA or VI for a wireguardwithlens.)XX =Versionwithoutlensshielding.

Smart TriLyteLow / high bay including lamps, ballast and sensor with a 3 year warranty

The Smart TriLyte is the first and only packaged fluorescent low/high bay engineered specifically to correctly address sensor applications lamp cycling in Canada. It delivers optimal performance and is the only occupancy-sensored linear fluorescent low/high bay that carries a complete system warranty on all components including lamps, ballast,sensor and luminaire for 3 years.

Features•Completesystemintetegratingmotionsensorand

Philips lamps, ballast, and lighting fixture•Lamps: Low Mercury Philips Alto II T8 lamps (Philips F32T8/TL841/AltoII,4100K,2850initiallumens)orAltoT5HOlamps(PhilipsF54T5/841/HO/ALTO,4100K,5000initiallumens)showing95%lumenmaintenanceand reduced lamp-end blackening. For other lamp colour temperatures, consult your Philips Lightolier representative

•4models(Narrow-body)–Availablein4'and8'lengths•6models(Wide-body)–Availablein4'lengthonly.• Sensor: LampMaximizer optimizes lamp life and

energy costs while reducing maintenance costs. Circular detection with passive infrared for 30-40 ft diameter coverage. Green LED on the sensor will blink constantly for 31 days once 70% of the projected lamp life has been reached

•Ballast: Philips Advance programmed start electronic ballast.TotalHarmonicDistorsionof<10%

•Ratedforballastcasetemperatureupto90°C.Testedto operate at ambient temperatures of 55°C (6-lamp versionwithoutlens).Forlensapplications,consultyourPhilips Lightolier representative

•Guarantee: 3-year guarantee on all components including lamps, ballasts, sensor and any other component installed on the product by the factory. Properly installed product that Philips Lightolier determines to be defective will be repaired or replaced at Philips Lightolier’s discretion. (The warranty covers the repair or replacement of the product and does not extend to transportation, installation or replacement charges.Nootherwarranty,eitherexpressedorimplied, beyond this statement is included. Consult your PhilipsLightolierrepresentativeforfurtherinformation.)

•Body: One-piece post-painted housing providing clean, smooth, installation-friendly corners

•Reflector:ContouredMiroIVreflectoroffersoptimum performance and 95% reflectivity

•Mounting: Choice of stem, surface or chain mounting. 12' to 45' mounting height with suitable lamp reflector lens mix

•Bulk Pack: Sold in bulk pack only

Options & accessoriesWireguard/lens: See besides.Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C (Internalslow-blowfusing).Stem and canopy sets: 4 stems required per luminaire. Order catalog no. STKF12(12"),STKF18(18"),STKF24(24"),STKF36(36"),STKF48(48").Chain hanger kit: 2 kits per luminaire. Order catalog no. EE9HC.

FH4C4DXX454UNVSML Narrow Body, 4-Lamp T5HO

30˚

60˚3000

6000

9000

Candlepower CurveReference data

Efficiency 86.2% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 234W Ballastfactor 1.0

Ordering information T8

Type* Lamp qty/type

Lamp/luminaire nominal length

Lumin. Width

Catalog number

4-T8 6-T8

48" 48"

17" 23"

FH4C4DXX432UNVSML FH4C5DXX632UNVSML

*Noshielding(accessoriesorderedseparately).

Application data*

Luminaire spacing FC W/Sq Ft

100' x 12' x 28' Space 20' on center 17/10 0.98

100' x 12' x 28' Space 15' on center 23/14 1.37

*Averagefootcandlesmaintained.TotalLLF=0.84. Reflectance: 50% Ceiling, 30% Wall, 20% Floor. 54W T5HO lamp rated at 4400 lumens at 25°C. 4 pi x4' grid at f loor level.

**Footcandlesatthefloor(horizontal) withFootcandlesonthewalls(vertical).

RCP C.U.

1

2

3

4

5

6

7

8

9

10

96

88

82

76

70

66

60

56

52

48

Page 184: Linear recessed and surface lighting

4.181Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Smart TriLyteLow / high bay including lamps, ballast and sensor with a 3 year warranty

The Smart TriLyte is the first and only packaged fluorescent low/high bay engineered specifically to correctly address sensor applications lamp cycling in Canada. It delivers optimal performance and is the only occupancy-sensored linear fluorescent low/high bay that carries a complete system warranty on all components including lamps, ballast,sensor and luminaire for 3 years.

FH4C5DXX654UNVSML Wide Body, 6-Lamp T5HO

Reference data

Efficiency 90.0% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 358.0W Ballastfactor 1.0

Ordering information T8

Type* Lamp qty/type

Lamp/luminaire nominal length

Luminaire width

Catalog number

4-T5HO 6-T5HO

48" 48"

17" 23"

FH4C4DXX454UNVSML FH4C5DXX654UNVSML

*Noshielding(accessoriesorderedseparately).

Luminaire type

Luminaire length

Reflector type Width Type Shielding/cord

Lamp qty in a luminaire cross-section Lamp/Type Voltage Ballast

FH= TriLyte Series

4= 4' (4 & 6 Lamp

8= 8' (4Lamponly)

C= Contoured MiroIV

4=17"(4-lamponly)

5=23"(6-lamp only; 4' unitonly)

D=Downlight XX=NoShielding

X3=Noshielding,3' cord, twist lock plug(singleswitching)

X6=Noshielding,6' cord, twist lock plug (single switching for 4 lamps or less; double switching for 6lamps)

X7=Noshielding,6' cord, no plug (doubleswitching)

4=4Lamps

6=6Lamps

32=T832W

54=T5HO54W

120=120V

277=277V

UNV=120-277V

SML = Smart Lighting (Philips Alto or Alto II 841 lamps, Philips Advance elect. P.S. bal-last and LampMaximizer sensor.)BulkPack.

FH 4 4C D XX 4 32 UNV SML

2 ¾"(70mm)

23 ⅛"(587mm)

19 ⅝"(498mm)

36"(914mm)

49 ½"(1257mm)

23 ⅛"(587mm)

15"(381mm)

30˚

60˚3000

6000

9000

Candlepower Curve

Application data*

Luminaire spacing FC W/Sq Ft

100' x 12' x 28' Space 20' on center 24/16 1.49

100' x 12' x 28' Space 15' on center 32/22 2.09

*Averagefootcandlesmaintained.TotalLLF=0.84. Reflectance: 50% Ceiling, 30% Wall, 20% Floor. 54W T5HO lamp rated at 4400 lumens at 25°C. 4 pi x4' grid at f loor level.

**Footcandlesatthefloor(horizontal) withFootcandlesonthewalls(vertical).

RCP C.U.

1

2

3

4

5

6

7

8

9

10

100

92

85

79

72

67

62

58

53

49

Numberinglogic

Page 185: Linear recessed and surface lighting

4.182 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Features•TheTrilyteNordikisdesignedforrefrigerated

environments•Candlelightrelativeoutput86.2%at-18°Cwhen

ordered with Philips Lightolier supplied amalgam lamps (CRIof4100K)

•ldealfortemperaturesbetween-18°Cand5°Cwhenordered with Philips Lightolier recommended T5HO amalgam lamps.For ambient temperatures of 5°C to 55°C, use regular TriLyte

•Body: One-piece post painted steel housing for superior strength and able to withstand the harshest environments. Smooth and installation-friendly corners

•Shielding: Full gasket sealed Door frame standard withclearacryliclens(0.12"nominalthickness)andspring latch design for easy tool less access to the lamp compartment . Polycarbonate lens also available. WireguardN/A

•Reflector: ContouredMiroIVreflectoroffersoptimum performance and 95% reflectivity

•Mounting: Surface or chain

Options & accessoriesBallast:Specifyvoltage(120,277orUNV,347)

and add suffix, e.g. UNVPV.

Ballast type <10THD

Elect.P.S.T5HO,(2)2-Lamp PGElect.P.S.T5HO,(1)4-Lamp PVElect.P.S.T5HO,(1)4-Lamp&(1)2-Lamp P6 one 4-Lamp for 1, 2, 5, & 6 and one 2-Lamp for 3 & 4

Elect.P.S.T5HO,(2)3-Lamp P7 one 3-Lamp for 1, 3, & 5 and one 3-Lamp for 2, 4, & 6

Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Emergency packN/A.Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C (Internalslow-blowfusing).Chain hanger kit:24"chainsuspensionkit.2kitsrequired per luminaire. Order catalog no. EE9HC.Lamps: Philips Lightolier strongly recommends purchasing the fixture complete with special amalgam lamps to insure maximum light output. Suffix: 6.Shielding: For clear polycarbonate lens instead of clear arylic lens, replace GI by PX.

36"(914mm)

49 ⅜"(1255mm)

17" (431mm)

2 ¾"(70mm)

Spring latch design for easy, toolless access to the lamp compartment.

TriLyteNordikFluorescent high bay for cold environments

TheTriLyteNordikisdesignedtoachievethesameleveloutputat-18°Casaregularfluorescenthighbayat25°Cambienttemperature.WiththeTriLyteNordik,youbenefitofthe energy savings, high color rendering and very low lumen depreciation that were reserved to standard ambient temperature, making it perfect for applications such as cold storage.

FHC4C4DGI454UNVPV6 Narrow Body

RCP C.U.

1

2

3

4

5

6

7

8

9

10

96

88

82

76

70

66

60

56

52

48

Reference data

Efficiency 86.2% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 234W Ballastfactor 1.0

Ordering information

Type* Size Lamp qty/type Catalog no.

Clear Acrylic Lens with Lamps 17"x49⅜" 4-T5HO FHC4C4DGI454UNVPV6

*Noshielding(accessoriesorderedseparately).

30˚

60˚3000

6000

9000

Candlepower Curve

Basic catalog no. Voltage Ballast Options TriLyteNordik 120=120V Seepage4.182 See page 4.182 277=277V Addappropriatesuffix. UNV=120-277V toCatalognumber. 6=Amalgamlamps

(recommended).

FHC4C4DGI454 UNV 6PVExample

Application data*

Luminaire spacing FC W/Sq Ft

300' x 400' x 25' Space 17' on center 50 0.81

120' x 80' x 28' Space 16' on center 55 0.98

300' x 400' x 25' Space 14' on center 75 1.15

*Averagefootcandlesmaintained.TotalLLF=0.84. Reflectance: 80% Ceiling, 50% Wall, 20% Floor. Lamps rated at 4400 lumens.

Page 186: Linear recessed and surface lighting

4.183Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

TriLyteNordikFluorescent high bay for cold environments

TheTriLyteNordikisdesignedtoachievethesameleveloutputat-18°Cthanaregularfluorescenthighbayat25°Cambienttemperature.WiththeTriLyteNordik,youbenefitfrom energy savings, high color rendering and very low lumen depreciation that were reserved for standard ambient temperature, making it perfect for applications such ascold storage.

FHC4C5DGI654UNVP66 Wide Body

RCP C.U.

1

2

3

4

5

6

7

8

9

10

100

92

85

79

72

67

62

58

53

49

Reference data

Efficiency 90.0% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 358.0W Ballastfactor 1.00

Ordering information

Type* Size Lamp qty/type Catalog no.

Clear Acrylic Lens with Lamps 23"x49⅜" 6-T5HO FHC4C5DGI654UNVP66

*Noshielding(accessoriesorderedseparately).

2 ¾"(70mm)

36"(914mm)

49 ⅜"(1254mm)

23 ⅛" (588mm)

Basic catalog no. Voltage Ballast Options TriLyteNordik 120=120V Seepreviouspage Seepreviouspage 277=277V Addappropriatesuffix. UNV=120-277V toCatalognumber. 6=Amalgamlamps

(recommended).

FHC4C5DGI454 UNV 6P6Example

30˚

60˚4000

8000

12000

Candlepower Curve

Application data*

Luminaire spacing FC W/Sq Ft

120' x 80' x 28' Space 240' on center 80 1.5

120' x 80' x 28' Space 20' on center 50 1.9

300' x 400' x 25' Space 18' on center 75 1.1

300' x 400' x 25' Space** 22' on center 50 0.76

*Averagefootcandlesmaintained.TotalLLF=0.84. Reflectance: 80% Ceiling, 50% Wall, 20% Floor. Lamps rated at 4400 lumens.

**Idem with 30% wall reflectance.

Page 187: Linear recessed and surface lighting

4.184 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

17"(432mm)

2 ¾"(70mm)

13 ⅜"(340mm)

49 ½"(1257mm)

98 ¼"(2496mm)

8 ¾"(222mm)

17"(432mm)

8 ¾"(222mm)

17"(432mm)

Narrow Body 4'

Narrow Body 8'

36"(914mm)

36"(914mm)

36"(914mm)

Features•Flatwhitereflectorandwireguardasstandard. (ChoiceofMiroIVflatreflectoralsoavailalble)

•Sturdyone-piecepost-paintedhousingprovidingclean,smooth, installation-friendly corners

•Side-mountedballastforlow2-3/4"profile•2-,3-,4-and8-lamp(4-lampintandem)T8orT5HO (cross-sectionview)

•Availablein4'and8'lengths•Choiceofstem,surfaceorchainmountingwith

installation up to 45'•Acceptsemergencybatterypacks

Options & accessoriesBallast:Specifyvoltage(120,277orUNV,347)

and add suffix, e.g. UNVPV.

Ballast type <10THD

Elect.I.S.T8,4LPB H4Elect.I.S.T8,(1)4LPB&(1)2LPB H5Elect.I.S.T8,(2)4LPB H7 one for outside and one for inside lamps

Elect.P.R.S.T5/T5HO,1or2LPB PGElect.P.R.S.T5/T5HO,1or3LPB PUElect.P.R.S.T5/T5HO,1or4LPB PVElect.P.S.T5/T5HO,(1)4LPB&(1)2LPB P6 one4LPBforoutsidelampsandone2LPBforinsidelamps

Elect.P.S.T5/T5HO,(1)3LPB&(1)3LPB P7 one3LPBforlamps1,3,&5andone3LPBforlamps2,4,&6

Elect.P.S.T5/T5HO,(2)4LPB P8 one for outside and one for inside lamps

LPB=Numberoflampsperballast

Emergency/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C (Internalslow-blowfusing).Lamps: not included except upon request. For T5HO lamps(8/41K)installed,CFIchoiceofbrand,addsuffix6. Consult your Philips Lightolier representative for additional options.

GymlyterResistant high bay dedicated to gymnasiums

Gymlyter is a one-piece body made of 22-gauge steel and a strong wireguard, with or without lens, fully dedicated to gymnasiums and other recreative environments.

FH4W4DWW454UNVCV Narrow Body, 6-Lamp T5HO

RCP C.U.

1

2

3

4

5

6

7

8

9

10

96

88

82

76

70

66

60

56

52

48

Reference data

Efficiency 86.2% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 234W Ballastfactor 1.0

White hinged 9-gauge wireguard adding rigidity to luminaire available as an accessory. FH4WG4 for narrow luminaire. Add VA or VI for a wire guard with lens.

VI Pattern 12 prismatic lens made ofvirginacrylic(.125"nominal).Completewith hinged white wireguard.

30˚

60˚3000

6000

9000

Candlepower Curve

Application data*

Luminaire spacing FC W/Sq Ft

300' x 400' x 25' Space 17' on center 50 0.8

120' x 80' x 28' Space 16' on center 55 1.0

300' x 400' x 25' Space 14' on center 75 1.2

*Averagefootcandlesmaintained.TotalLLF=0.84. Reflectance=80%Ceiling,50%Wall,20%Floor. 54W T5HO lamp rated at 4400 lumens at 25°C.

Page 188: Linear recessed and surface lighting

4.185Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Lumin. Type

Lumin. Length

Reflector type Width Type Lens/shielding

Lamp qty in a luminaire cross-section Lamp/type Voltage Ballast Options

FH 4= 4'

8= 8'

W= Flat Design White Reflector

S= Flat Design Specular Reflector

4=17" D=Downlight VI=PrismaticLensVIwithWireguard

WW=Wireguard,White with NoLens

2=2Lamps

3=3Lamps

4=4Lamps

8 =4Lampsin tandem (8total)

28=T528W

32=T832W

54=T5HO54W

120=120V

277=277V

UNV=120-277V

See prev. page

See previous page

Add appropriate suffix to Catalog number

GymlyterResistant high bay dedicated to gymnasiums

Gymlyter is a one-piece body made of 22-gauge steel and a strong wireguard, with or without lens, fully dedicated to gymnasiums and other recreative environments.

Ordering information for T5

Type Length Lamp qty/type

Lamp/luminaire nominal length Catalog no.

Prismatic Lens with Wireguard 17"

4-T5HO 6-T5HO 8-T5HO

48" 96"tandem 96"tandem

FH4W4DVI454 FH8W4DVI354 FH8W4DVI454

White Wireguard withNoLens 17"

4-T5HO 6-T5HO 8-T5HO

48" 96"tandem 96"tandem

FH4W4DWW454 FH8W4DWW354 FH8W4DWW454

Ordering information for T8

Type Length Lamp qty/type

Lamp/luminaire nominal length Catalog no.

PrismaticLens(VI) with Wireguard 17"

2-T8 3-T8 4-T8 6-T8 8-T8

48" 48" 48" 96"tandem 96"tandem

FH4W4DVI232 FH4W4DVI332 FH4W4DVI432 FH8W4DVI332 FH8W4DVI432

White Wireguard withNoLens 17"

2-T8 3-T8 4-T8 6-T8 8-T8

48" 48" 48" 96"tandem 96"tandem

FH4W4DWW232 FH4W4DWW332 FH4W4DWW432 FH8W4DWW332 FH8W4DWW432

FH 4 4W D WW 4 54 UNV PV 6

Numberinglogic

Page 189: Linear recessed and surface lighting

4.186 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Cleanguard Voltage Ballast Options Wet location 120=120V Seepage4.186 See page 4.186 Class 10,000 or 277=277V andpage4.130 100,000 Clean Room UNV=120-277V (Elec.T8orTT5Ballastonly)

CXS2GFSVI26U UNV AHIExample

Cleanguard Class 10,000 CleanRoom 2' x 4' & 2' x 2'Recessed fluorescent luminaire

Features•MeetsrequirementsforFederalStandard209EClass

10,000 & 100,000 Clean Room tested by Independent Lab.•ULandULcListedforwetordamplocationsfor

covered ceiling use.•Fits15/16"to1"widefacegridceilingsystemsorflanged

for drywall type ceilings. Contractor responsible for sealing fixture to ceiling.

•Fullperimetergasketing(closedcellNeoprene)betweenDoor frame and lens, between housing and Door frame.

•Endssealedtobody.•.125pattern12lensinstalledsmoothsidedown.•Doorframeispostpainted,bakedacrylicenamel.•Hemmedoversiderailsformaximumsafety.•Springloadedroosterheadlatches.•18gaugesteelhinges.•Flatandregressedaluminumdoorsavailable.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. UNVHI

Ballast type <10THD <20THD

Electronic T8 HI*, P2** S0*1-3 Lamp Elec T8 H3*, P3** 03*1-4 Lamp Elect T8 H4*, P4** 04*1-3 Lamp TT5 40 Watt IB*, PR** SB*Electronic TT5 40 Watt I3* X3*

* Instant start** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Continuous row installation: For F type fixtures, half-width flanges are required between fixtures. Catalog no.: 2FCTrim for each joint.Plaster frame: For F type troffers, order plaster frames separately. Catalog no.: PF24 for 2'x4' troffer; PF22 for 2'x2' troffer.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

CXS2GFSVI26UUNVHI

30˚

60˚500

1000

1500

Candlepower CurveReference data

Efficiency 63.1% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 53.7W LER FL 56.0

Ordering information

Type Size Lamp qty–type

Exposed T-Grid

Flanged for dry wall or plaster

Flat Aluminum Door 2' x 2'

2-6" T8 3-TT5 3-1.6"U T8

CXS2GFAVI26U CXS2GFAVI3FT CXS2GFAVI32U

CXS2FFAVI26U CXS2FFAVI3FT CXS2FFAVI32U

Flat Steel Door 2' x 2'

2-6"T8 3-TT5 3-1.6"UT8

CXS2GFSVI26U CXS2GFSVI3FT CXS2GFSVI32U

CXS2FFSVI26U CXS2FFSVI3FT CXS2FFSVI32U

Regressed Aluminum Door

2' x 2'2-6"T8 3-TT5 3-1.6"UT8

CXS2GRAVI26U CXS2GRAVI3FT CXS2GRAVI32U

CXS2FRAVI26U CXS2FRAVI3FT CXS2FRAVI32U

CXS2GFSVI332UNVH3

Cleanguard Voltage Ballast Options Wet location 120=120V Seepage4.186 See page 4.186 Class 10,000 or 277=277V andpage4.130 100,000 Clean Room UNV=120-277V (Elec.T8Ballastonly)

CXS2GFSVI332 UNV AH3Example

Reference data

Efficiency 67.9% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 108.7W LER FL 73.2

Ordering information

Type Size Lamp qty–type

Exposed T-Grid

Flanged for dry wall or plaster

Flat Aluminum Door 2' x 4'

2 T8 3-T8 4-T8

CXS2GFAVI232 CXS2GFAVI332 CXS2GFAVI432

CXS2FFAVI232 CXS2FFAVI332 CXS2FFAVI432

Flat Steel Door 2' x 4'

2 T8 3-T8 4-T8

CXS2GFSVI232 CXS2GFSVI332 CXS2GFSVI432

CXS2FFSVI232 CXS2FFSVI332 CXS2FFSVI432

Regressed Aluminum Door

2' x 4'2 T8 3-T8 4-T8

CXS2GRAVI232 CXS2GRAVI332 CXS2GRAVI432

CXS2FRAVI232 CXS2FRAVI332 CXS2FRAVI432

5"(127mm)

24" (610mm)

30˚

60˚750

1500

2250

Candlepower Curve

5"(127mm)

24" (610mm)

Page 190: Linear recessed and surface lighting

4.187Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

5"(127mm)

24" (610mm)

Exposed T-grid ceiling, 1 ½" face, (with flat aluminum frame).

Exposed T-grid ceiling 15⁄16" to 1" face (with flat aluminum frame).

24"1 ½"

¼"max.

1 ½"max.

gasketing

Cleanguard Class 1,000/10,000 CleanRoom 2' x 4' & 2' x 2'Recessed fluorescent luminaire 2' x 2', 2' x 4' - 1½" wide T-bar

CXS2WFAVI26UUNVHI

CXS2WFAVI332UNVH3

30˚

60˚500

1000

1500

Candlepower Curve

Cleanguard Voltage Ballast Options Wet location 120=120V Seepage4.187 See page 4.187 Class 1,000, 10,000 or 277=277V andpage4.130 100,000 Clean Room UNV=120-277V (Elec.T8orTT5Ballastonly)

CXS2WFAVI26U UNV AHIExample

Cleanguard Voltage Ballast Options Wet location 120=120V Seepage4.187 See page 4.187 Class 1,000, 10,000 or 277=277V andpage4.130 100,000 Clean Room UNV=120-277V (Elec.T8Ballastonly)

CXS2WFAVI332 UNV AH3Example

Reference data

Efficiency 63.1% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 53.7W LER FL 56.0

Reference data

Efficiency 67.9% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 108.7W LER FL 73.2

Ordering information

Type Size Lamp qty–type

¹5⁄¹6" to 1 ½" Wide face T-Grid

Flat Aluminum Door 2' x 2'

2-6" T8 3-TT5 3-1.6"U T8

CXS2WFAVI26U CXS2WFAVI3FT CXS2WFAVI32U

Ordering information

Type Size Lamp qty–type

¹5⁄¹6" to 1 ½" Wide face T-Grid

Flat Aluminum Door 2' x 2'

2-T8 3-T8 4-T8

CXS2WFAVI232 CXS2WFAVI332 CXS2WFAVI432

30˚

60˚750

1500

2250

Candlepower Curve

Features•MeetsrequirementsforFederalStandard209EClass

1,000/10,000 & 100,000 Clean Room tested by Independent Lab.

•ULandULcListedforwetordamplocationsforcovered ceiling use.

•Fits15/16"to11/2"widefacegridceilingsystems.Contractor responsible for sealing fixture to ceiling.

•Fullperimetergasketing(closedcellNeoprene)between Door frame and lens, closed cell ethafoam gasketing between housing and Door frame.

•Endssealedtobody.•.125pattern12lensinstalledsmoothsidedown.•Doorframeispostpainted,bakedacrylicenamel.•Hemmedoversiderailsformaximumsafety.•Springloadedroosterheadlatches.•18gaugesteelhinges.•Flatextrudedaluminumdoor.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. UNVHI

Ballast type <10THD <20THD

Electronic T8 HI*, P2** S0*1-3 Lamp Elec T8 H3*, P3** 03*1-4 Lamp Elect T8 H4*, P4** 04*1-3 Lamp TT5 40 Watt IB*, PR** SB*Electronic TT5 40 Watt I3* X3*

* Instant start

** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

5"(127mm)

24" (610mm)

Mounting Methods

gasketing

24"

¼"max.

gasketing

gasketing

¹5⁄¹6"or1"

1 ½"max.

Page 191: Linear recessed and surface lighting

4.188 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

8 9�32"(210mm)

9 ¾" (247mm)

7 5�16"(186mm)

5 9�32"(134mm)

8 9�32"(210mm) 7 5�16"

(186mm)

5 9�32"(134mm)

9 ¾" (247mm)

Features•SamefixturemeetsClassI,II,IIIandWetLocation

requirements.•UL-ListedClassI,Division2,GroupsA,B,CandD

locations.•UL-ListedClassII,Division1and2,GroupsFandGand

Class III, Division 1 and 2 locations.•ULListedforwetlocations.•Non-corrosivefiberglassreinforcedpolyestercompositebodysuitable(T8orT12RS)for40°Cambienttemperature.

•MeetsUL844staticdischargerequirements.•MeetsUL746Cimpacttestrequirements.•MeetsUL94-5VAfirerating.•Stainlesssteel,16gaugesteeldoorwith3/16"tempered

glass lens.•Stainlessspringsteeltoggleclampstosecurelens

door frame.•One-piecesiliconegasketing.

Options & accessories page 4.217Ballast:Specifyvoltage(120,277)andtype

and add as suffix, e.g. HSCXT232UNVHI

Ballast type <10THD <20THD

1-2 Lamp Elec T8 HI* S0*1-3 Lamp Elec T8 H3* 03*

* Instant start

Electrical/wiring options: For special wiring, fusing, consult factory.

HazardlineVapor/dust/wet locations enclosed luminaire

This luminaire is suitable for indoor and outdoor application in three areas. Class I Div. 2 locations are those in which flammable gases, vapors or liquids are handled in closed containers from which any escape of hazardous materials are accidental. Class II locations are hazardous because of the presence of combustible dust. Class III locations are hazardous because of the presence of easily ignitable fibers of flyings. Hazardline, additionally has a wet location rating for use indoors.

HSCXT232120SO

30˚

60˚500

1000

1500

Candlepower CurveReference data

Efficiency 72.7% Spacing ratio 1.0

Electronic ballast

Inputwatts(120V) 62.0W Ballastfactor 0.88

Ordering information

Type Class/division Fixture length

Lamp qty/type Catalog no.

Enclosed Industrial Fluorescent

Vapor-tight Class I Division 2 Dust-tight Class II/III Division 1 Division 2 Wet-Location

53" 53"

2-T8

3-T8

HSCXT232 HSCXT332

*800 MA HO fixtures are standard with -20°F ballasts*Consult factory for HO units.

Hazardline Voltage Ballast Options Vapor/Dust/Wet 120=120V Seepage4.188 See page 4.188 Locations Enclosed 277=277V andpage4.217 Luminaire UNV=120-277V

HSCXT232 120 SOExample

Application data*

Luminaire spacing FC W/Sq Ft

50' x 70' x 12' Space 51 0.9 8'x8'(64sqft/f ixture)

12' x 16' x 8.5' Space 54 1.2 6'x8'(48sqft/f ixture)

8'x8'x8.5'Cubicle/60"Partition 54 0.9 30'x30'(64sqft/f ixture)

*AveragefootcandlesmaintainedTotalLLF=.75 Reflectance: 80% Ceiling, 50% Wall, 20% Floor RE835 lamp rated at 3000 lumens

Coefficients of utilization % wall reflectance

Room

Cav

ity R

atio

70 50 30

1 78 75 72

2 72 67 62

3 66 59 54

4 60 53 47

5 55 46 40

6 51 42 35

7 47 37 31

8 43 33 27

9 39 30 24

10 36 27 21 20% of floor and 80% of ceiling effective cavity reflectance

Page 192: Linear recessed and surface lighting

4.189Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

FeaturesThe following hazardous location definitions are excerpted fromArticle500ofthe1990NationalElectricalCode

HSCXT Series meets the following classifications

Class I, Division 2 locations (a) ClassI,Division2locationisalocation(1)inwhich

volatile f lammable liquids or flammable gases are handled, processed, or used, but in which the liquids, vapors, or gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems, or in case of abnormal operation of equipment.

Class II locationsClass II locations are those that are hazardous because of the presence of combustible dust. (a) ClassII,Division1.AClassII,Division1locationis

alocation:(1)whichcombustibledustisintheairunder normal operating conditions, in quantities sufficient to produce explosive or ignitible mixtures; or(2)wheremechanicalfailureorabnormaloperation of machinery or equipment might cause such explosive or ignitible mixtures to be produced, and might also provide a source of ignition through simultaneous failure of electric equipment, operation ofprotectiondevices,orfromothercauses;or(3)inwhich combustible dusts of an electrically conductive nature may be present in hazardous quantities.

(b)ClassII,Division2.AClassII,Division2locationisalocation where combustible dust is not normally in the air in quantities sufficient to produce explosive or ignitible mixtures, and dust accumulations are normally insufficient to interfere with the normal operation of electrical equipment or other apparatus, but combustible dust may be in suspension in the air as a result of infrequent malfunctioning of handling or processing equipment and where combustible dust accumulations on, in, or in the vicinity of the electrical equipment may be sufficient to interfere with the safe dissipation of heat from electrical equipment or may be ignitible by abnormal operation or failure of electrical equipment.

Class III locationsClass III locations are those that are hazardous because of the presence of easily ignitible fibers of f lyings, but in which such fibers or flyings are not likely to be in suspension in the air in quantities sufficient to produce ignitible mixtures.(a) ClassIII,Division1.AClassIII,Division1location

is a location in which easily ignitible fibers or materials producing combustible flyings are handled, manufactured, or used.

(b)ClassIII,Division2.AClassIII,Division2locationisa location in which easily ignitible fibers are stored or handled.

Hi-temp power channel Heavy-duty hinged stainless steel door

Top/end suspension hubs Class I/Division 2 construction

45° Adjustable quadrant brackets NKH45 Top-mount angle-bars HACM CSP

HazardlineVapor/dust/wet locations enclosed luminaire

This luminaire is suitable for indoor and outdoor application in three areas. Class I Div. 2 locations are those in which flammable gases, vapors or liquids are handled in closed containers from which any escape of hazardous materials are accidental. Class II locations are hazardous because of the presence of combustible dust. Class III locations are hazardous because of the presence of easily ignitable fibers of flyings. Hazardline, additionally has a wet location rating for use indoors.

ThermalPerformanceofHSCXTFixtures*

Features

Options

Ordering informationLamp

qty/typeAmbient temp. °C

“T” Numbers

Fixture Temp.* Catalog no.

2-T8 3-T8

40 40

T-4A T-4A

120°C(248°F) 120°C(248°F)

HSCXT232 HSCXT332

*800 MA HO fixtures are standard with -20°F ballasts*Consult factory for HO units.

Page 193: Linear recessed and surface lighting

4.190 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Professional

Sealatron Voltage Ballast Options Wet Location 120=120V Seepage4.190 See page 4.190 Enclosed Luminaire 277=277V UNV=120-277V

ST4WA232 UNV AHIExample

SealatronWet location enclosed industrial luminaire

The Sealatron is an enclosed industrial luminaire rated for wet locations with an IP67 rating

Features•WetLocation-Areasofhighhumidity,watervapor,rain,

incidental water spray, or other non-corrosive or non-f lammableliquid.(UL-Listed)

•NSFCertif iedforNon-FoodZoneinstallations.•IP67rating.•Acceptableforoutdooraswellasindoorinstallations.•One-pieceimpactresistant,non-conductive,non-

corrosive housing, reinforced polyester fiberglass housing.

•Smoothexteriorsurfaceforeasycleaning.•Lightingchannelhashighreflectancebakedwhite

enamel finish.•Twogasketedthreaded(1/2"tradesize)wetlocation

hubs installed on ends.•HighimpactDRacrylicmoldedlens.•Crepepatterninnersurfacelens.•Continuous,compressible,closed-cellneoprenegasket

bonded to housing.•ABSlock-tightplasticmoldedcam-actiontension

latches.•K.O.'sprovidedthroughoutforeasyaccess.•Canbesurface(wall/ceiling)orsuspendedmounted

unless otherwise specif ied.•Mountingbracketsavailable,Orderseparately.

Options & accessoriesBallast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. ST4WA232UNVHIElectronicT12(HOonly) SSBallast type <10THD <20THD

Electronic T8 H0 P2 SOElectronic T8 HI* SO*1-4 Lamp Electronic T8 H4* 04*ElectronicT5InstantS(28W) PI Electronic T5 Program S PG1-4LampElectronicT5(54W) PV

* Instant start Standard

Cold weather ballasts: T12 HO lamped fixtures are standard with –20°F ballasts. To specify cold weather (0°F)ballastsforRSorT8fixtures.Suffix: CW.Water tight kits: One installed each end of f ixture. For additional kits, order Catalog no.: STW-DC2.Electrical/wiring options: Consult factory.Radio interference filter: 120 or 277 volt, 50 or 60 Hz. One per fixture. Suffix: R. One per ballast. Suffix: B.Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C (Internalslow-blowfusing).Top mounting bracket: Order Catalog no.: STW TOP BRKT.

ST4WA232120SO

30˚

60˚500

1000

1500

Candlepower CurveReference data

Efficiency 85.10% Spacing ratio 1.5

Electronic ballast

I.W.(120V) 54W

Ballastfactor 0.88

Ordering information

Type Size Lamp length

Lamp qty–type Catalog no.

STW Wet Location Enclosed Industrial

7 x 25 ¹3⁄¹6" 24"24"

1-T81-T8

ST4WA117ST4WA217

7 x 49 ¹3⁄¹6"

48" 46" 46" 48" 46" 46"

1-T8 1-T5 1-T5HO 2-T8 2-T5 2-T5HO

ST4WA132 ST4WA128 ST4WA154 ST4WA232 ST4WA228 ST4WA254

7 x 97 ¹3⁄¹6"

48" 46" 46" 48" 46" 46" 96" 96" 96"

1-T8* 1-T5* 1-T5HO* 2-T8** 2-T5** 2-T5HO** 2-T8SL 2-T8HO 2-T12HO

ST8WA132 ST8WA128 ST8WA154 ST8WA232 ST8WA228 ST8WA254 ST8WA259SL ST8WA286HO ST8WA296HO

*2lampstotal,(intandem) **4lampstotal,(intandem)

Precision molded pre-formed knockouts for stem, chain or surface mounting.

Smooth virgin acrylic lens opens easily and hinges from either side for easy maintenance.

3 3�16"(81mm)

2 ⅛"(154mm)

1 ½"(38mm)

5 3�16"(132mm)

6 ⅝"(168mm)7"

(178mm)

Hole each end.88" Dia. (⅞")

3 3�16"(81mm)

3"(76mm)

1 ½"(38mm)

5 ⅞"(149mm)

6 ⅝"(168mm)7"

(178mm)

Hole each end.88" Dia. (⅞")

38 ¾" (984mm)41 ⅞" (1064mm)

Stud location (2 places)

Stud location (2 places)

Drill Point location(2 places)

49 13�16" (127mm)

5 ⅛"(130mm)

89 ⅞" (2283mm)

Stud location(4 places)

Drill PointLocation(2 places)

17 ½" (445mm)

14 ¾" (375mm)¼" - 28 Brass Studs

Drill Point location(2 places)

25 13�16" (655mm)

Two Top Mounting Brackets: STW TOP BRKT

Two Surface or Chain Mounting Brackets: STW END BRKTS

¼" - 28 Brass Studs¼" - 28 Brass Studs40 13�16" (1037mm)40 13�16" (1037mm)

97 13�16" (2484mm)

Note: Sealatron luminaire also available in LED

Page 194: Linear recessed and surface lighting

4.191Comprehensive lighting catalog 7th Edition

Professional – Linear recessed and surface lighting

Sealatron IP low profileWet location enclosed industrial luminaire

The Sealatron IP Low Profile enclosed Industrial is a wet location listed luminaire that incorporates a low profile housing design, high impact lenses and IP ratings.

Features•IP65ratingforribbedlensesandIP67ratingfor

prismatic lens.•Acceptableforoutdooraswellasindoorinstallations.•WetLocationAreasofhighhumidity,watervapor,rain,

incidental water spray, or other non-corrosive or non-flammable liquid.

•Alsosuitablefordamplocations.•Non-conductive,non-corrosivehousing.•Smoothexteriorsurfaceforeasycleaning.•Moldedfiberglass5V-Ahousing.•Choiceofribbedorinjectionmoldedprismaticdiffusers.•Continuouspouredgasket.•Polycarbonatecamactionlatchesarestandard.•Ballastisretainedbyasnap-ongeartrayinlieuof

channel, reducing weight.•Twosnap-onstainlesssteelmountingbracketsincluded,

can be installed anywhere along housing (except at latches).

Options & accessoriesBallast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. IP4WP232UNVHI

Ballast type <10THD <20THD

Electronic T8 HI* SO*1 - 3 Lamp Electronic T8 H3* 03*1 - 4 Lamp Electronic T8 H4* 04*2 - 3 Lamp Electronic T8 H6*1 - 4 Lamp or 1 - 4 Lamp Elect T8 H5* ElectronicT5(28W/54W) PG**1-3LampElectronicT5(54W) PU**

* Instant start

** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming options, consult factory.Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C (Internalslow-blowfusing).

30˚

60˚550

1100

1650

Candlepower Curve

IP4WP232UNVHI

Sealatron Fixture Fixture Lamp Lamp type/ IP low length width Lens shielding type quantity fixture length Voltage Ballast type Options profile 2=2' W=7¼" R=LinealRibbed 1=1Lamp 14=T5(2') 120=120V See page 4.191 Add appropriate 4=4' N*=4½" (IP65)Polycarbonate 2=2Lamps 17=T8(2') 277=277V suffix to catalog 8=8' A=LinealRibbedHigh 3=3Lamps 24=T5HO(2') UNV=120-277V ImpactAcrylic(IP65) (28W,32W,54W 28=T5(4') P=PrismaticInjection lamptypesonly)** 32=T8(4') Polycorbonate 54=T5SO(4')

IP W4Example

Ordering information

Size Family Lamps X section

Lamp fixture

Available lenses

Lamp type

Length in. (mm)

Width in. (mm)

Height in. (mm)

2'

4'

8'

IP

IP

IP

12

1 2 3 1 2 3

12

123

246

R, P

R, PA, R, PA, R, P

A

14, 17, 24HO

28, 32, 54HO28, 32, 54HO28, 32, 54HO

28, 32, 54HO28, 32, 54HO

28, 32

27 11/16"(703)

51 9/16"(1310)

100"(2540)

4½"(114)7¼"(184)

4½"(114)7¼"(184)7¼"(184)

7¼"(184)

4¼"(108)

4¼"(108)

4¼"(108)

UNV AHIA 322

*Narrowhousingonlyavailableinonelamp,twoandfourfootf ixturesizes.** 28W, 32W and 54W available in three lamp, four foot f ixture sizes.

28W and 32W available in three lamp, eight foot f ixture sizes.

A

Prismatic Injected Molded Lens (P)

Ribbed Lenses (R, A)

2 and 3 lamp (1 lamp 8') 1 lamp (except 8')

4 ¼"(108mm)

4 ¼"(108mm)

4 ¼"(108mm)

4 ¼"(108mm)

4 ½" (114mm)

4 ½" (114mm)7 ¼" (184mm)

7 ¼" (184mm)

Mounting Bracket(included)

A (Overall Length)2'models2711/16"(703mm)4'models519/16"(1310mm)8'models100"(2540mm)

Reference data

Efficiency 66.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 55W

Page 195: Linear recessed and surface lighting

4.192 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Cleanguard wet locationRecessed fluorescent luminaire 2' x 4', 2' x 2' & 1' x 4'

WES1GFAVA232UNVHI

WES2GFAVA26UUNVHI

Cleanguard Voltage Ballast Options Wet Location 120=120V Seepage4.192 See page 4.192 277=277V andpage4.130 UNV=120-277V

WES1GFAVA232 UNV AHIExample

Cleanguard Voltage Ballast Options Wet Location 120=120V Seepage4.192 See page 4.192 277=277V andpage4.130 UNV=120-277V

WES2GFAVA26U UNV AHIExample

Reference data

Efficiency 69.0% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 80.0W LER FL 48.3

Reference data

Efficiency 71.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 56.3W LER FL 58.6

Ordering information

Type Size Lamp qty–type

Exposed T T-Grid

Flanged for Dry Wall or Plaster

Flat Steel Door Regressed Alum. Door Flat Aluminum Door

1' x 4'2-T8 2-T8 2-T8

WES1GFSVA232 WES1GRAVA232 WES1GFAVA232

WES1FFSVA232 WES1FRAVA232 WES1FFAVA232

Features•ULandC-ULListedforwetordamplocationsfor

covered ceiling use.•Fullperimetergasketing(closedcellNeoprene)between

Door frame and lens, between housing and Door frame.•Doorframeispostpainted,bakedacrylicenamel.•5"deepbodyfor2x4and2x2.•81.2%efficient(T8),2x44lamp.•69.0%efficient(T8),2-6"U.•64.6%efficient(T8).1x42lamp.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips2x4,2x2.•SlimlineDoorframewith1000squareinchlensopening

on 2x4 door.•Miteredcornersteellensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•Flatandregressedaluminumdoorsavailable.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. UNVHI

Ballast type <10THD <20THD

Electronic T8 HI*, P2** S0*1-3 Lamp Elec T8 H3*, P3** 03*1-4 Lamp Elect T8 H4*, P4** 04*1-3 Lamp TT5 40 Watt I3* X3*Electronic TT5 40 Watt IB*, PR** SB*

* Instant start

** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Seismic Hold-Down Clip: For 1'x4' type G, Suffix: 2HD. Factory installed.Plaster frame: For F type troffers, order plaster frames separately. Catalog no.: PF24 for 2'x4' troffer; PF22 for 2'x2' troffer; PF14 for 1'x4' troffer.Fusing: Suffix: A (Internalfast-blowfusing).Suffix: C (Internalslow-blowfusing)Continuous row installation: For 1'x4' F type fixtures, trim is required between fixtures. Cat. no.: 1FCTrim For 2'x4' and 2'x2' F type fixtures, trim is required between fixture Cat. no. S2FCTrim (Oneperjointisrequired).

4"(101mm)

12" (305mm)

30˚

60˚600

1200

1800

Candlepower Curve

5"(127mm)

24" (610mm)

30˚

60˚600

1200

1800

Candlepower Curve

Ordering information

Type Size Lamp qty–type

Exposed T T-Grid

Flanged for Dry Wall or Plaster

Flat Steel Door 2' x 2'2-6" T8 3-TT5 3-1.6"U T8

WES2GFSVA26U WES2GFSVA3FT WES2GFSVA32U

WES2FFSVA26U WES2FFSVA3FT WES2FFSVA32U

Regressed Aluminum Door 2' x 2'

2-6" T8 3-TT5 3-1.6"U T8

WES2GRAVA26U WES2GRAVA3FT WES2GRAVA32U

WES2FRAVA26U WES2FRAVA3FT WES2FRAVA32U

Flat Aluminum Door 2' x 2'

2-6" T8 3-TT5 3-1.6"U T8

WES2GFAVA26U WES2GFAVA3FT WES2GFAVA32U

WES2FFAVA26U WES2FFAVA3FT WES2FFAVA32U

WES2GFAVA432UNVH4 Reference data

Efficiency 81.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 108.7W LER FL 73.2

5"(127mm)

24" (610mm)

30˚

60˚1250

2500

3750

Candlepower Curve

Cleanguard Voltage Ballast Options Wet Location 120=120V Seepage4.192 See page 4.192 277=277V andpage4.130 UNV=120-277V(Elec.T8Ballastonly)

WES2GFAVA432 UNV AH4Example

Ordering information

Type Size Lamp qty–type

Exposed T T-Grid

Flanged for Dry Wall or Plaster

Flat Steel Door 2' x 4'2-T8 3-T8 4-T8

WES2GFSVA232 WES2GFSVA332 WES2GFSVA432

WES2FFSVA232 WES2FFSVA332 WES2FFSVA432

Regressed Aluminum Door 2' x 4'

2-T8 3-T8 4-T8

WES2GRAVA232 WES2GRAVA332 WES2GRAVA432

WES2FRAVA232 WES2FRAVA332 WES2FRAVA432

Flat Aluminum Door 2' x 4'

2-T8 3-T8 4-T8

WES2GFAVA232 WES2GFAVA332 WES2GFAVA432

WES2FFAVA232 WES2FFAVA332 WES2FFAVA432

Page 196: Linear recessed and surface lighting

4.193Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

6 1�16"(27mm)

2 13�16"(71mm)

8 5�32" (207mm)

6 1�16"(27mm)

8 5�32" (207mm)

2 13�16"(71mm)

6 1�16"(27mm)

2 13�16"(71mm)

8 5�32" (207mm)

6 1�16"(27mm)

8 5�32" (207mm)

2 13�16"(71mm)

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.193 See page 4.193 Damp/Wet Locations 277=277V Enclosed Luminaire UNV=120-277V (Elec.T8Ballastonly)

SC4WC232 UNV TPHIExample

CleanliteDamp/wet locations enclosed luminaire

Features•UL-listedfordryanddamplocations.•UL-listedforwetlocations.•Siliconesealedbody(SC4W).•Forindustrialorcommercialapplications.•Crispmodulardesign.•Availablein4'onepiecebody.•Continuousclosed-cellgasketingatallsealpoints.•Smoothone-piecewater-clearacryliclens.•Lock-tightcam-actionlatches.•Water-tighthubsforelectricalfeed(SC4W).•ConstructionmeetsNYCcoderequirements.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. SC4DC232UNVHIBallast type <10THD <20THD

Electronic T8 HI* SO*1 - 3 Lamp Electronic T8 H3* 03*Electronic T5 Program S PG SO*1-3LampElectT5(54W) PU –

* Instant start Standard

Tamperproof latches: Suffix: TP.Optional lenses: Lexan lenses or DR acrylic lens. Consult factory.Water tight kits: All f ixtures are furnished with one watertight hub kit for top or end conduit entry. Additional water tight kits required for every entry. Catalog no.: GWHB CSP. For coupling kits required for continuous row mounting. Catalog no.: KWCP CSP

SC4WC232UNVHI

30˚

60˚500

1000

1500

Candlepower CurveReference data

Efficiency 79.3% Spacing ratio 1.6

Electronic ballast

Inputwatts(120V) 53.0W

Ordering information

Type Size Lamp length

Lamp qty–type Catalog no.

Damp Locations 8 3⁄16"x50 5⁄16"

48" 46" 46" 48" 46" 46" 48" 46" 46"

1-T8 1-T5 1-T5HO 2-T8 2-T5 2-T5HO 3-T8 3-T5 3-T5HO

SC4DC132 SC4DC128 SC4DC154 SC4DC232 SC4DC228 SC4DC254 SC4DC332 SC4DC328 SC4DC354

Wet Locations 8 3⁄16"x50 5⁄16"

48" 46" 46" 48" 46" 46" 48" 46" 46"

1-T8 1-T5 1-T5HO 2-T8 2-T5 2-T5HO 3-T8 3-T5 3-T5HO

SC4WC132 SC4WC128 SC4WC154 SC4WC232 SC4WC228 SC4WC254 SC4WC332 SC4WC328 SC4WC354

Water-tight hubs

Page 197: Linear recessed and surface lighting

4.194 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.194 See page 4.194 277=277V andpage4.130 UNV=120-277V

GVS1GFSVL232 UNV AHIExample

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.194 See page 4.194 277=277V andpage4.130 UNV=120-277V

GVS2GFSVL26U UNV AHIExample

GuardsmanVandalResistantRecessed fluorescent luminaire 2' x 4', 2' x 2' & 1' x 4'

Features•Excellentforlocationswherevandalresistance

is required.•Prismaticlens(VL)is3/16"thickpattern12,minimum

impact strength, 130 foot pounds.•Fullperimetergasketing(closedcellNeoprene)

between Door frame and lens.•Tamperresistantholtheadscrewssecurelens

to housing.•5"deepbody,2x2and2x4.•74.4%efficient(T8),2x44lamp.•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclipson2x2and2x4.•Springloadedroosterheadlatches.•18gaugesteelhinges.•69.3%efficient(T8),2x22-6"U.•62.2%efficient(T8),1x42lamp.•Turnedupedgesforsafehandling.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277)andtype

and add as suffix, e.g. UNVHI

Ballast type <10THD <20THD

Electronic T8 HI*, P2** S0*1-3 Lamp Elec T8 H3*, P3** 03*1-4 Lamp Elect T8 H4*, P4** 04*1-3 Lamp TT5 40 Watt I3* X3*1 & 2 Lamp TT5 40 Watt IB*, PR** SB*

* Instant start

** Program start

Lens:Foroptional9/64"thick(VK) pattern 12, minimum impact strength, 80 foot pounds, substitute VL with VK inCatalogno.i.e:GVS2GFSVK432.Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Seismic hold-down clip: For 1'x4' type G, Suffix: 2HD. Factory installed.Plaster frame: For F type troffers, order plaster frames separately. Catalog no.: PF24 for 2'x4' troffer; PF22 for 2'x2' troffer.Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C (Internalslow-blowfusing).

GVS1GFSVL232UNVHI

GVS2GFSVL26UUNVHI

Reference data

Efficiency 62.3% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 80.0W LER FL 48.3

Reference data

Efficiency 69.3% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 56.4W LER FL 58.9

Ordering information

Type Size Lamp qty–type

Exposed T-Grid

Flanged for dry wall or plaster

Flat Steel Door 1' x 4' 2-T8 GVS1GFSVL232 GVS1FFSVL232

Ordering information

Type Size Lamp qty–type

Exposed T-Grid

Flanged for dry wall or plaster

Flat Steel Door 2' x 2'2-6" T8 3-TT5 3-1.6"U T8

GVS2GFSVL26U GVS2GFSVL3FT GVS2GFSVL32U

GVS2FFSVL26U GVS2FFSVL3FT GVS2FFSVL32U

5"(127mm)

24" (610mm)

4"(101mm)

12" (305mm)

30˚

60˚500

1000

1500

Candlepower Curve

30˚

60˚600

1200

1800

Candlepower Curve

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.194 See page 4.194 277=277V andpage4.130 UNV=120-277V

GVS2GFSVL432 UNV AH4Example

GVS2GFSVL432UNVH4Reference data

Efficiency 74.4% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 105W LER FL 69.0

Ordering information

Type Size Lamp qty–type

Exposed T-Grid

Flanged for dry wall or plaster

Flat Steel Door 2' x 4'2-T8 3-T8 4-T8

GVS2GFSVL232 GVS2GFSVL332 GVS2GFSVL432

GVS2FFSVL232 GVS2FFSVL332 GVS2FFSVL432

5"(127mm)

24" (610mm)

30˚

60˚1250

2500

3750

Candlepower Curve

Page 198: Linear recessed and surface lighting

4.195Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

24" (610mm)

5 ½"(140mm)

24" (610mm)

5 ½"(140mm)

30˚

60˚450

900

1350

Candlepower Curve

30˚

60˚1050

2100

3150

Candlepower Curve

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.195 See page 4.195 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

GVB2SFSVL26U UNV AHIExample

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.195 See page 4.195 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

GVB2SFSVL432 UNV AH4Example

GuardsmanVandalResistantSurface box luminaire 2' x 4', 2' x 2' & 1' x 4'

GVB2SFSVL26UUNVHI

GVB2SFSVL432UNVH4

Reference data

Efficiency 55.5% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 60.7W

Reference data

Efficiency 65.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 13.3W

Ordering informationType Size Lamp qty–Type Surface box

Flat Steel Door 2' x 2'2-6" T8 3-TT5 3-1.6"U T8

GVB2SFSVL26U GVB2SFSVL3FT GVB2SFSVL32U

Ordering informationType Size Lamp qty–Type Surface box

Flat Steel Door 2' x 4'2-T8 3-T84-T8

GVB2SFSVL232 GVB2SFSVL332 GVB2SFSVL432

Features•Excellentforlocationswherevandalresistance

is required.•20gaugesteelbody.•Prismaticlens(VL)is3/16"thick,pattern12,minimum

impact strength, 130 foot pounds.•Fullperimetergasketing(closedcellNeoprene)between

Door frame and lens.•Tamperresistantholtheadscrewssecurelens

to housing.•45°miteredcorners(bodyandDoorframe).•Only5-1/2"deep.•54.9%efficient(2lampT8).1x4•55.5%efficient(2UlampT8).•65.2%efficient(4lampT8).•Sidemountedballastforcooleroperation.•Fullyenclosedwiring.•MeetsNYCCoderequirements.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. UNVHI

Ballast type <10THD <20THD

Electronic T8 HI*, P2** S0*1-3 Lamp T8 H3*, P3** 03*1-4 Lamp T8 H4*, P4** 04*Electronic TT5 40 Watt IB*, PR** SB*1-3 Lamp TT5 40 Watt I3* X3*

* Instant start

** Program start

Lens:Foroptional9/64"thick(VK) pattern 12, minimum impact strength 80 foot pounds, substitute VL with VKincatalogno.ieGVB2SFSVK432Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, or emergency pack, consult factory.Fusing: Suffix: A (Internalfast-blowfusing).Suffix: C (Internalslow-blowfusing)

24" (610mm)

5 ½"(140mm)

30˚

60˚500

1000

1500

Candlepower Curve

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.195 See page 4.195 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

GVB1SFSVL232 UNV AHIExample

GVB1SFSVL232UNVHIReference data

Efficiency 54.9% Spacing ratio 1.2

Electronic ballast

Inputwatts(120V) 55.6W

Ordering informationType Size Lamp qty–Type Surface box

Flat Steel Door 1' x 4' 2-T8 GVB1SFSVL232

Page 199: Linear recessed and surface lighting

4.196 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Candela Distribution

Angle End 45 Cross 0 2339 2339 2339 5 2340 2337 2331 15 2267 2302 2328 25 2110 2208 2274 35 1876 2053 2133 45 1534 1730 1757 55 866 1020 973 65 474 540 679 75 260 310 453 85 68 184 322 95 0 134 266 105 1 137 205 115 4 94 129 125 8 60 78 135 10 45 60 145 9 34 47 155 9 22 33 165 8 12 17 175 8 7 9

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.196 See page 4.196 277=277V andpage4.130 UNV=120-277V

GV4WB332 UNV AH3Example

GuardsmanVandalResistantFluorescent wraparound luminaire

Features•Excellentforlocationswherevandalresistance is required.•Prismaticlensis50%DR(impactresistant),and50%standardacrylicwithanominalthicknessof1/8",withstands 70 ft. lbs. impact without breaking.

•Tamperresistantholtheadscrewssecurelens to housing.

•UL-Listedfordirectmountingonlowdensityceilingsand damp locations.

•Steelendcaps,standard.•Self-aligningforcontinuousrowmounting.•Heavyduty,dieformedchannelofcodegaugesteel.

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. UNVHI

Ballast type <10THD <20THD

Electronic T8 HI*, P2** S0*1-3 Lamp T8 H3*, P3** 03*1-4 Lamp T8 H4*, P4** 04*

* Instant start

** Program start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A(Internalfast-blowfusing).Suffix: C (Internalslow-blowfusing).

GV4WB332UNVH3Reference data

Efficiency 79.8% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 86W LER FL 75

Ordering informationType Size Lamp qty–Type Catalog no.

Surface Wraparound 15 5 ⁄ ¹6"x48" 3-T8 GV4WB332

⅞"Dia. K.O.

SpannerHeadScrewLens RetainerBracketEnd PlateLens

³�¹6" K.O. (2)

13 ⅞" (325mm)

2 ¹³�¹6"(71mm)

12 ¹�¹6" (306mm)

⅞"Dia. K.O.Spanner Head ScrewLens RetainerBracketEnd PlateLens³�¹6" K.O. (2)

2 ¹³�¹6"(71mm)

8 ⅝" (219mm)

6 ¹³�¹6" (173mm)

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.196 See page 4.196 277=277V andpage4.130 UNV=120-277V

GV4WA232 UNV AHIExample

GV4WA232UNVHIReference data

Efficiency 77.8% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 59W LER FL 70

Ordering informationType Size Lamp qty–Type Catalog no.

Surface Wraparound 10 5 ⁄ ¹6" x 48" 10 5 ⁄ ¹6" x 96"

2-T8 2-T8inTandem(4total)

GV4WA232 GV8WA232

Candela Distribution

Angle End 45 Cross 0 1482 1482 1482 5 1482 1482 1479 15 1432 1463 1483 25 1331 1409 1458 35 1186 1313 1375 45 967 1078 1045 55 541 615 568 65 305 329 388 75 162 208 292 85 45 129 251 95 0 111 261 105 1 147 199 115 3 83 107 125 4 48 62 135 6 44 57 145 7 34 47 155 7 21 32 165 5 9 15 175 5 6 7

SpannerHeadScrewLens RetainerBracketEnd PlateLens

³�¹6" K.O. (2)

13 ⅞" (325mm)

2 ¹³�¹6"(71mm)

12 ¹�¹6" (306mm)⅞"Dia. K.O.

Candela Distribution

Angle End 45 Cross 0 3116 3116 3116 5 3123 3119 3107 15 3020 3063 3099 25 2814 2941 3020 35 2506 2716 2830 45 2040 2285 2285 55 1178 1348 1257 65 632 695 862 75 348 395 553 85 95 229 372 95 0 156 306 105 3 163 237 115 6 119 162 125 10 87 117 135 15 65 91 145 13 48 65 155 13 31 46 165 11 17 25 175 11 11 14

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.196 See page 4.196 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

GV4WB432 UNV AH4Example

GV4WB432UNVH4Reference data

Efficiency 78.2% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 108W LER FL 76

Ordering informationType Size Lamp qty–Type Catalog no.

Surface Wraparound 15 5 ⁄ ¹6"x48" 2-T8 4-T8

GV4WB232 GV4WB432

Page 200: Linear recessed and surface lighting

4.197Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Guardsman Voltage Ballast Options Vandal Resistant 120=120V Seepage4.197 See page 4.197 GSW Series 277=277V andpage4.130 UNV=120-277V (Elec.T8Ballastonly)

GS4V232 UNV AHIExample

GuardsmanVandalResistantGSW series ceiling or wall mounted luminaire

Features•Excellentforlocationswherevandalresistanceis

required, areas such as hallways, stairwells, locker rooms, parking garages and psychiatric hospitals.

•Forceilingorwallmountedapplications.•Canbeverticallyorhorizontallymountedonwall.•20gaugecoldrolledsteel,postpainted,bakedwhite

enamel housing.•18gaugecoldrolledsteelpostpaintedbakedwhite

enamel end caps, standard.•Linearprismaticlens50%DR(impactresistant)and50%standardacrylicwithnominalthicknessof1/8",withstands 70 foot pounds of impact without breaking.

•Tamperresistantholtheadscrewssecureendsto housing.

•Only3-7/8"deep,meetsAmericanswithDisabilitiesActfor wall mounted fixtures.

•Nominal2'and4'lengths.•73.9%efficient(T8lamps).

Options & accessories page 4.130Ballast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. UNVHI

Ballast type <10THD <20THD

Electronic T8 HI* S0*

* Instant start

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C (Internalslow-blowfusing).

GS4V232UNVHIReference data

Efficiency 73.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 59.1W LER 62.9

Ordering information

Type Size Lamp Length

Lamp qty–type Catalog no.

GSW VandalResistant Ceiling or Wall

6"x23¹5⁄¹6" 24" 1-T8 2-T8

GS2V117 GS2V217

6"x48" 48" 1-T8 2-T8

GS4V132 GS4V132

3 ⅞"(98mm)

6" (152mm)

4"6"

(152mm) 23 15�16"(608mm)

⅞" dia. K.O. (2)9�32" hole (2)

End Cap End Cap

Nut Nut

Nut

For continuous row mounting

Required to space fixtures apart so ends

can be removed or

installed.

Threaded Nipple

30˚

60˚400

800

1200

Candlepower Curve

⅞" dia. K.O. (3) 1 ⅞" dia. K.O. 9�32" hole (2)

4"6"

(152mm) 24"(610mm) 48"

(1219mm)

Page 201: Linear recessed and surface lighting

4.198 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

9 Cells or 12 Cells (2-T8U6)

9 Cells or 12 Cells (3-T8U1.6)

9 Cells or 12 Cells (3-TT5)

16 Cells (2-T8U6)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

5"(127mm)

5"(127mm)

5"(127mm)

24" (610mm)

9 Cells or 12 Cells (2-T8U6)

9 Cells or 12 Cells (3-T8U1.6)

9 Cells or 12 Cells (3-TT5)

16 Cells (2-T8U6)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

5"(127mm)

5"(127mm)

5"(127mm)

24" (610mm)

IC Series 2' x 4' & 2' x 2'3" parabolic recessed suitable for thermal insulation contact

Features•ULListedTypeICRecessedLuminaire(IntendedforThermalInsulatedContact).

•Constructionprovidesoptimumthermalperformance.•Idealforfireratedceilings.•Blackexteriorforcoolerballastoperatingtemperature.•5"deepbody(2x4,2x2)•77.7%efficient(3light18cell)•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•Pre-anodizedaluminumparaboliclouver.•Springloadedroosterheadlatches.•18gaugesteelhinges.•Louverhasprotectivefilmdustguard.

Options & accessories page 4.130Louver: Finish Low iridescence semi-specular is standard. Consult factory for other finishes.Ballast:Specifyvoltage(UNV)andtype

and add as suffix, e.g. UNVC4.

Ballast type <10THD

Electronic T8 C2*1-3 Lamp Elec T8 C3*1-4 Lamp Elect T8 C4*1-3LampTT5(40W) NI*ElectronicTT5(40W) NJ*

* Instant start High Eff iciency.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Continuous row installation: For F type fixtures, half-width flanges are required between fixtures. Catalog no.: 2FCTrim for each joint.Plaster frame: For F type troffers, order plaster frames separately. Catalog no.: PF24 for 2'x4' troffer; PF22 for 2'x2' troffer.Drywall kit: Catalog no.: FK92X4 for 2'x4' troffer; FK92X2 for 2'x2' trofferChicago Plenum: For products that meet Chicago Plenum requirements, add Suffix: C.

ICS2G9LS26UNVC2

Ordering information

Type Cells Lamp qty–type

Exposed T-Grid

Flanged for dry wall or plaster

Slot-T or Concealed T

Static

9 12

2-T8U6 2-T8U6

ICS2G9LS26U ICS2G12LS26U

ICS2F9LS26U ICS2F12LS26U

ICS2G9LS26U ICS2T12LS26

16 2-T8U6 ICS2G16LS26U ICS2F16LS26U ICS2T16LS26U

9 12

3-T8U1.6 3-T8U1.6

ICS2G9LP32U ICS2G12LP32U

ICS2F9LP32U ICS2F12LP32U

CS2T9LP32U ICS2T12LP32U

9 12

3-TT5 3-TT5

ICS2G9LP3FT ICS2G12LP3FT

ICS2G12LP3FT ICS2G12LP3FT

ICS2T9LP3FT ICS2T12LP3FT

IC Series Voltage Ballast Options 3"ParabolicRecessed UNV=120-277V Seepage4.198 See page 4.198 Suitable for Thermal (Elec.T8orTT5Ballastonly) and page 4.130 Insulation Contact

UNVICS2G9LS26U AC2Example

18 Cells 24 Cells (3-T8)

18 Cells 24 Cells (3-T8 or 4-T8)

32 Cells (4-T8)

12 Cells (2-T8 or 4-T8)

5"(127mm)

5"(127mm)

5"(127mm)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

24" (610mm)

18 Cells 24 Cells (3-T8)

18 Cells 24 Cells (3-T8 or 4-T8)

32 Cells (4-T8)

12 Cells (2-T8 or 4-T8)

5"(127mm)

5"(127mm)

5"(127mm)

5"(127mm)

24" (610mm)

24" (610mm)

24" (610mm)

24" (610mm)

ICS2G12LS232UNVC2

Ordering information

Type Cells Lamp qty–type

Exposed T-Grid

Flanged for dry wall or plaster

Slot-T or Concealed T

Static

1212

2-T8 4-T8

ICS2G12LS232 ICS2G12LS432

ICS2F12LS232 ICS2F12LS432

ICS2T12LS232 ICS2T12LS432

18 24

3-T83-T8

ICS2G18LP332 ICS2G24LP332

ICS2F18LP332 ICS2F24LP332

ICS2T18LP332 ICS2T24LP332

18 18

3-T8 4-T8

ICS2G18LS332 ICS2G18LS432

ICS2F18LS332 ICS2F18LS432

ICS2T18LS332 ICS2T18LS432

32 4-T8 ICS2G32LS432 ICS2F32LS432 ICS2T32LS432

IC Series Voltage Ballast Options 3"ParabolicRecessed UNV=120-277V Seepage4.198 See page 4.198 Suitable for Thermal (Elec.T8Ballastonly) and page 4.130 Insulation Contact

UNVICS2G12LS232 AC2Example

Page 202: Linear recessed and surface lighting

4.199Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

4 Lamp Data5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

5"(127mm)

24" (610mm)

IC Series 2' x 4' & 2' x 2'Recessed lensed static suitable for thermal insulation contact

Features•ULListedTypeICRecessedLuminaire(IntendedforThermalInsulatedContact).

•Constructionprovidesoptimumthermalperformance.•Idealforfireratedceilings.•Blackexteriorforcoolerballastoperatingtemperature.•5"deepbody(2x4,2x2)•81.2%efficient(4light)•Hemmedoversiderailsformaximumsafety.•Fixtureendsturned-inforsafehandling.•Built-inearthquakeclips.•TrueMiteredcornersteellensframe.•Springloadedroosterheadlatches.•18gaugesteelhinges.•Flatandregressedaluminumdoorsavailable.•ConstructiontomeetChicagoPlenumrequirements

is available.

Options & accessories page 4.130Special lenses:VIlensisstandardvirginacrylic. For other available lenses, see page 4.130.Ballast:Specifyvoltage(UNV)andtype

and add as suffix, e.g. UNVC2 .

Ballast type <10THD

Electronic T8 C2*1-3 Lamp Elec T8 C3*1-4 Lamp Elect T8 C4*1-3 Lamp TT5 40 Watt NI*Electronic TT5 40 Watt NJ*

* Instant start High Eff iciency.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory.Continuous row installation: For F type fixtures, half-width flanges are required between fixtures. Catalog no.: 2FCTrim(eachjoint,2x2,2x4).Plaster frame: For F type troffers, order plaster frames separately. Catalog no.: PF24 for 2'x4' troffer; PF22 for 2'x2' troffer.Door frames Available: ICS2GFS(f latsteeldoor), ICS2GFA(f lataluminumdoor)ICS2GRA (regressed aluminumdoor).Chicago Plenum: For products that meet Chicago Plenum requirements, add Suffix: C.Fusing: Suffix: A(Internalfast-blowfusing).

Suffix: C(Internalslow-blowfusing.)

ICS2GFSVI432UNVC4

Ordering information

Type Size Lamp qty–type

Exposed T-Grid

Flanged for dry wall or plaster

Static 2' x 4'2-T83-T84-T8

ICS2GFSVI232ICS2GFSVI332ICS2GFSVI432

ICS2FFSVI232ICS2FFSVI332ICS2FFSVI432

Reference data

Efficiency 81.2% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 108.7W Ballastfactor 73.2

IC Series Voltage Ballast Options Recessed Lensed Static UNV=120-277VSeepage4.199 See page 4.199 Suitable for Thermal (Elec.T8Ballastonly) and page 4.130 Insulation Contact

UNVICS2GFSVI432 AC4Example

2 Lamp Data 3 Lamp Data5"

(127mm)

24" (610mm)

5"(127mm)

5"(127mm)

24" (610mm)

24" (610mm)

ICS2GFSVI26UUNVC2&ICS2GFSVI32UUNVC3

Ordering information

Type Size Lamp qty–type

Exposed T-Grid

Flanged for dry wall or plaster

Static 2' x 2'

2-T8U63-TT53-T8U1.63-T8F17

ICS2GFSVI26UICS2GFSVI3FTICS2GFSVI32UICS2GFSVI317

ICS2FFSVI26UICS2FFSVI3FTICS2FFSVI32UICS2FFSVI317

IC Series Voltage Ballast Options Recessed Lensed Static UNV=120-277V Seepage4.199 See page 4.199 Suitable for Thermal (Elec.T8orTT5Ballastonly) and page 4.130 Insulation Contact

UNVICS2GFSVI26U AC2Example

Reference data

Efficiency 71.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 56.3W Ballastfactor 58.6

Reference data

Efficiency 67.9% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 76.2W Ballastfactor 64.1

Page 203: Linear recessed and surface lighting

4.200 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

4 ⅛"(105 mm)

6 ⅛"(156 mm)

11 ¾"(298 mm)

5 ⅜"(127 mm)

Turret Industrial Voltage Ballast Options Fluorescent Premium 120=120V Seepage4.200 See page 4.200 Open Industrial Luminaire 277=277V andpage4.217 UNV=120-277V (Elec.T832WBallastonly)

TU4A232 UNV AHIExample

TU Turret IndustrialFluorescent premium open industrial luminaire

Features•Ruggedtelescopingturretlampholders.•Optimum53/8"lampspacing(2lampunits).•Reflectorisembossedforrigidity.•Reflectorsidesareturnedupforrigidityand

safe handling.•12%aperturereflector,standard.•Solidtopreflector,optional.•Reflectorsecuredtohousingwitheasytouse

thumb screws.•41/8"wideclevistypehousingchannel.•Fullyenclosedwiring.•Optionalporcelainreflectors.•Optionalslidegriphangers.•Optionalheavydutycoupling,wireguardsand

reflector aligners.

page 4.217Ballast:Specifyvoltage(120,277orUNV)andtype

and add as suffix, e.g. TU4A232UNVHI

Ballast type <10THD <20THD

Electronic T12 H0 – SSStd.Mag.HO/VHO – PHElectronic T8 HI*, P2** SO*1 - 3 Lamp Electronic T8 H3*, P3** 03*1 - 4 Lamp Electronic T8 H4*, P4** 04*

* Instant start** Program start

Cold weather ballasts: T12 HO lamped fixtures are standard with –20°F ballasts. To specify cold weather (0°F)ballastsforRSorT8fixtures.Suffix: CW.Reflector Row Aligners: For continuous row installations, specify two additional bulk-packed aligners. Order Catalog no. TU - SNA .Housing row couplers: For continuous row mounting (stem/chain).Oneperjointrequired.Ordercat.no. LFL - 3.Side-grip hangers:Accepts1/2"threadstemsorrods.Slides into fixture chassis grooves. Order cat. no. LFL - 111.Chain hanger kit: Order catalog no. LFL - 123. 4' Wire guard: Order catalog no. LFL - 173.

TU4A232UNVHI

30˚

60˚1450

2900

Candlepower CurveReference data

Efficiency 91.7% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 61W LER FI 80

Ordering information

Type Fixture length

Lamp length

Lamp qty/type Catalog no.

12% Uplight

49 ½" 49 ½" 99 ⅞" 99 ⅞" 96" 96" 48" 96" 48" 96"

48" 48" 48" 48" 96" 96" 48" 96" 48" 96"

2-T8 3-T8 2-T8inTandem(4total) 3-T8inTandem(6total) 2-T8SL 2-T8HO2-T12HO 2-T12HO 2-T12VHO 2-T12VHO

TU4A232 TU4A332 TU8A232 TU8A332 TU8A259SL TU8A286HO TU4A248HO TU8A296HO TU4A248VO TU8A296VO

Solid Top NoUplight

49 ½" 49 ½" 99 ⅞" 99 ⅞" 96" 96" 48" 96" 48" 96"

48" 48" 48" 48" 96" 96" 48" 96" 48" 96"

2-T8 3-T8 2-T8inTandem(4total) 3-T8inTandem(6total) 2-T8SL 2-T8HO2-T12HO 2-T12HO 2-T12VHO 2-T12VHO

TU4S232 TU4S332 TU8S232 TU8S332 TU8S259SL TU8S286HO TU4S248HO TU8S296HO TU4S248VO TU8S296VO

Page 204: Linear recessed and surface lighting

4.201Comprehensive lighting catalog 7th Edition

Standard – Linear recessed and surface lighting

Turret Industrial Voltage Ballast Options Standard Open 120=120V Seepage4.201 See page 4.201 Industrial Luminaire 277=277V andpage4.217 UNV=120-277V (Elec.T832WBallastonly)

KW4S232 UNV AHIExample

KD/KWIndustrialStandard open industrial luminaire

Features•Reflectorisembossedforrigidity.•Reflectorsidesareturnedupforrigidityand

safe handling.•Solidtopreflector,standard.•10%aperturereflector,optional.•41/8"widehousingchannel.•U.L.Listedsnap-onendcaps.•Fullyenclosedwiring.•Combinationendcapforcontinuousrowmounting.•Optionalhangers,wireguardsandaligners.•Optionalheavydutycoupling.•ConvenienceoutletandswitchK.O.’sprovided.

Options & accessories page 4.217

Ballast:Specifyvoltage(120,277orUNV)andtypeand add as suffix, e.g. KW4S232UNVHI

Ballast type <10THD <20THD

ElectronicT12(H0&SL) – SSStd.Mag.HO/VHO – PHElectronic T8 HI*, P2** SO*1 - 3 Lamp Electronic T8 H3*, P3** 03*1 - 4 Lamp Electronic T8 H4*, P4** 04*

* Instant start

** Program start

4' Wire guard: Order two per 8' f ixture. Order catalog no. AWG4W CSP.Reflector row aligner: For continuous row installations. Order catalog no. KND CSP.Side grip hanger:Accepts1/2"threadstemsorrods.Slides into fixture chassis grooves. For KW series order NAHW CSP and for KD series order NAHD CSP.Hard surface mounting or twist tee: For KW series order NAH3 CSP and for KD series order NAH3D CSP.Chain hanger kit: Order catalog no. AH5 CSP.Heavy duty housing coupler: Order catalog no. NHDC-W CSP.

KW4S232UNVHI

Ordering information

Type Fixture length

Lamp length

Lamp qty/type Catalog no.

Solid Top NoUplite

48" 96" 96" 96" 96" 48" 96" 48" 96"

48" 48" 96" 96" 96" 48" 96" 48" 96"

2-T8 2-T8inTandem(4total) 2-T8SL 2-T8HO 2-T12SL 2-T12HO2-T12HO 2-T12VHO 2-T12VHO

KW4S232 KW8S232 KW8S259SL KD8S286HO KW8S296SL KD4S248HO KD8S296HO KD4S248VO KD8S296VO

10% Uplite

48" 96" 96" 96" 96" 48" 96" 48" 96"

48" 48" 96" 96" 96" 48" 96" 48" 96"

2-T8 2-T8inTandem(4total) 2-T8SL 2-T8HO 2-T12SL 2-T12HO2-T12HO 2-T12VHO 2-T12VHO

KW4A232 KW8A232 KW8A259SL KD8A286HO KW8A296SL KD4A248HO KD8A296HO KD4A248VO KD8A296VO

10 ½"(267mm)

4 ⅜"(103mm)

4 ⅝"(117mm)

30˚

60˚

Candlepower Curve

500

1000

1500

Reference data

Efficiency 88.4% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 62.0W LER FI 75.3

Page 205: Linear recessed and surface lighting

Linear recessed and surface lighting

4.202 Philips Lightolier For complete specif ication information visit www.lightolier.com

General utility

General utility luminaires are used in a wide variety of applications, ranging from the complex to the simple. This section highlights quality surface mounted strip lightinginallT12,T8andT5lampstyles.OurSV5Louver and Lens Series offers many combinations within ourSVT5channelfamily.Enablingdesignerstousechannels in both a stylish and practical method. Our standard, narrow, wide, deep and staggered channels meet all the requirements for today's construction needs.YouwilldiscoverthatPhilipsLightolierprovidesmany solutions for your general utility lighting needs.

Page 206: Linear recessed and surface lighting

Linear recessed and surface lighting

4.203Comprehensive lighting catalog 7th Edition

SV5 > 4.204 T5 Strips > 4.206 Symmetric & Asymmetric Reflectors > 4.208 SD Deep Strip > 4.210 SS Staggered Strip > 4.211 SM Side Mount Strip > 4.211 SNStrip > 4.212 SW Strip > 4.213

Catalog numbering logic > 4.214 Surface/wall options > 4.216 Industrial options > 4.217 Drywall kit > 4.218 The ULM Module > 4.219 Ballastcodeoptions > 4.220 Air handling data > 4.222

Contents

Page 207: Linear recessed and surface lighting

4.204 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Ordering information

Type Length (nom)

SV5 Reflector and louver*

White Perforated Reflector with White PerforatedRadialBlade

46" SV5LVW4SPER**

White Solid Reflector with Grey Solid Radial Blade

46" SV5LGW4SSLD**

*Onlyforusewith1or2-lampT5Strip(SV)** For Slotted White Reflector, replace Solid White SLD by SLT. For Perforated White Reflector, replace Solid White SLD by PER . ForWhitePerforatedRadialBladeLouver,replaceLW with LV.ForGreyPerforatedRadialBladeLouver,replaceLG with LH

30˚

60˚0

0

Candlepower Curve

0

SV5LVW4SPER Two 28W T5 Fluorescent lamps

2"(51mm)

4 1�16"(103mm)

2 9�16"(42mm)

3 11�16"(94mm)

4 ⅞"(124mm)

RCR C.U.

1 91 2 83 3 76 4 70 5 64 6 59 7 54 8 50 9 46 10 43

Features•90.6%Efficiency-basedon1-54WSVStripwith

perforated reflector and clear linear ribbed lens.•86.1%Efficiency-Basedon2-28WSVStripwith

perforated reflector and perforated radial louver.•Postpaintedwithhighefficiencywhitepowderedpaint.•Lay-indesignopticallowsforeasylampmaintenance.•Lowprofile3”11-16profilewheninstalled.•Tooledradiallouverensuresdesignconsistencyin

continuous row applications.•Retro-fittablewithCFIBrandSV4T5Strip.•Louver-solidorperforatedpatternradialblade.•Lens-frostedlinearorclearlinear

Options & accessoriesStem and canopy sets: Suspend luminaire 12",18",24",36",or48"fromsurface. (Twoperluminaireisrecommended.) Catalog no.: SV5F12 (12");SV5F18(18"); SV5F24(24");SV5F36(36");SV5F48(48").

Aircraft cable kit:CatNo:SVCC60-UNV (adj.6"-60")60"SV5PowerFeed,Cableand CanopyKit

Cable and canopy kit:CatNo:SVC60(adj.6"-60")

Chain hanging kit:CatNo:EE9HC Includes two 5' heavy duty link chains with sturdy “V” hookforfixturesuspension.

Rocker switches and convenience outlets: Certain combinationsoftheSVSeriesstripwiththenewSV5Reflector assembly will not accommodate these options. Please consult the specif ication sheets or your Philips Lightolier representative to validate the request.

Reference data

Efficiency 86.1% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 64.0W LuminaireEff(LER) 1.0

Application data*

Luminaire spacing FC W/Sq Ft

50' x 70' x 8.5' Space 8' on center 51 1.02

30' x 30' x 8.5' Space 10' on center 53 1.14

10' x 8' x 8' Space 6' on center 43 1.28

6' x 8' x 8' Space Work Cell 36 1.33

* Average foot candles maintained. Total Light Loss Factor LLF=.90Reflectances:80%Ceiling,50%Wall,20%FloorRE835T5/T5HO lamp lumens at 4400 rated at 25C.

Louver options

SV5 Louver design Reflector Light dist. Reflector style Reflector LV=White/PerforatedBlade W4=Nominal S =Symmetric SLD=Solid Accessory LW=White/SolidBlade 46”White SLT=Slotted LG=Grey/SolidBlade (Std) PER=Perforated LH=Grey/PerforatedBlade

LVSV5 SW4Example PER

+

SV4 Strip (1or2lamps)

SV5 Reflector and shielding options

Complete SV5 luminaire

CompleteSV5Luminaire

=

Dimensions are the same for 1 or 2-lamp luminaire.

SV5louverandlensseriesFor 1 and 2 lamp 46 T5 strip (SV)

Stylish, when utilizing either the radial louver or linear ribbed prismatic lens, or practical in instanceswherenoopticisrequiredandshieldedlightisrequired.TheSV5Seriesoffersmany combinations within its offering that allows combinations of either solid, slotted or peforated reflector designs to be interchanged with different radial louver or lens options. The new reflector design also offers a nice alternative to the standard straight blade reflectorwhenusedwithoutthelens/louveroption.TheSV5Seriesisretro-fittablewithSV4Seriesstrip.

Page 208: Linear recessed and surface lighting

4.205Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

SV5louverandlensseriesFor 1 and 2 lamp 46 T5 strip (SV)

Options & accessoriesStem and canopy sets: Suspend luminaire 12",18",24",36",or48"fromsurface. (Twoperluminaireisrecommended.) Catalog no.: SV5F12 (12");SV5F18(18"); SV5F24(24");SV5F36(36");SV5F48(48").

Aircraft cable kit:CatNo:SVCC60-UNV (adj.6"-60")60"SV5powerfeed,cableand canopykit

Cable and canopy kit:CatNo:SVC60(adj.6"-60")

Chain hanging kit:CatNo:EE9HC Includes two 5' heavy duty link chains with sturdy “V” hookforfixturesuspension.

Rocker switches and convenience outlets: Certain combinationsoftheSVSeriesstripwiththenewSV5Reflector assembly will not accommodate these options. Please consult the specif ication sheets or your Philips Lightolier representative to validate the request.

Features•90.6%Efficiency-Basedon1-54WSVStripwith

perforated reflector and clear linear ribbed lens.•86.1%Efficiency-Basedon2-28WSVStripwith

perforated reflector and perforated radial louver.•Postpaintedwithhighefficiencywhitepowderedpaint.•Lay-indesignopticallowsforeasylampmaintenance.•Lowprofile3”11-16profilewheninstalled.•Tooledradiallouverensuresdesignconsistencyin

continuous row applications.•Retro-fittablewithCFIBrandSV4T5Strip.•Louver-solidorperforatedpatternradialblade.•Lens-frostedlinearorclearlinear

Lens options

Ordering information

Type Length (nom)

SV5 Reflector and louver*

White Perforated Reflector with Clear Linear Lens

46" SV5CLW4SPER**

White Solid Reflector with Frosted Linear Lens 46" SV5FLW4SSLT**

*Onlyforusewith1or2-lampT5Strip(SV)** For Perforated White Reflector, replace Solid White SLT by PER

30˚

60˚0

0

Candlepower Curve

0

SV5CLW4SPER One 54W T5 HO Fluorescent lamp

2"(51mm)

4 1�16"(103mm)

2 9�16"(42mm)

3 11�16"(94mm)

4 ⅞"(124mm)

RCR C.U.

1 95 2 86 3 79 4 72 5 66 6 61 7 56 8 51 9 47 10 44

Reference data

Efficiency 90.6% Spacing ratio 1.3

Electronic ballast

Inputwatts(120V) 64.0W LuminaireEff(LER) 1.1

Application data*

Luminaire spacing FC W/Sq Ft

50' x 70' x 12' Space 8' on center 45 0.92

30' x 30' x 8.5' Space 10' on center 46 1.06

10' x 8' x 8' Space 8' on center 37 1.19

6' x 8' x 8' Space Work Cell 36 1.25

* Average foot candles maintained. Total Light Loss Factor LLF=.90Reflectances:80%Ceiling,50%Wall,20%FloorRE835T5/T5HO lamp lumens at 4400 rated at 25C.

SV5 Louver design Reflector Light dist. Reflector style Reflector CL=ClearLinearLens W4=Nominal S =Symmetric SLT=Slotted Accessory FL=FrostedLinearLens 46”White PER=Perforated (Std)

CLSV5 SW4Example PER

Ordering information

Type Length (nom)

SV5 Reflector and louver*

White Solid Reflector 46"SV5XXW4SSLD**SV5XXW4SSLD**SV5XXW4SSLD**

Lens option not available with a solid reflector*Onlyforusewith1or2-lampT5Strip(SV)** For Slotted White Reflector, replace Solid White SLD by SLT.

For Perforated White Reflector, replace Solid White SLD by PER .

30˚

60˚0

0

0

Candlepower Curve

0

SV5XXW4SSLD Two 28W T5 Fluorescent lamps

2"(51mm)

4 1�16"(103mm)

2 9�16"(42mm)

3 11�16"(94mm)

4 ⅞"(124mm)

RCR C.U.

1 96 2 88 3 80 4 74 5 67 6 62 7 57 8 52 9 48 10 44

Reference data

Efficiency 87.8% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 64.0W LuminaireEff(LER) 1.0

Application data*

Luminaire spacing FC W/Sq Ft

50' x 70' x 12' Space 8' on center 45 0.88

30' x 30' x 8.5' Space 10' on center 34 0.64

10' x 8' x 8' Space 8' on center 22 0.64

6' x 8' x 8' Space Work Cell 28 1.33

* Average foot candles maintained. Total Light Loss Factor LLF=.90Reflectances:80%Ceiling,50%Wall,20%FloorRE835T5/T5HO lamp lumens at 4400 rated at 25C.

SV5 Louver design Reflector Light dist. Reflector style Reflector XX=NoLens/Louver W4=Nominal S =Symmetric SLD=Solid(N/AwithLensoption) Accessory 46” White SLT=Slotted (Std) PER=Perforated

XXSV5 SW4Example SLD

Dimensions are the same for 1 or 2-lamp luminaire.

Dimensions are the same for 1 or 2-lamp luminaire.

Page 209: Linear recessed and surface lighting

4.206 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•Only13/8"deep.•Utilizescompact,highefficiency,T5orT5HOlamps.•Fullyenclosedwiring.•ConvenienceoutletandswitchK.O.sprovided(1 lamp only).

•Pushthroughlampholderswithrotorforsecurelamp retention.

Features•Only2"Wide.•Utilizescompact,highefficiency,T5orT5HOlamps.•Fullyenclosedwiring.•Optionalwhiteorspecular,symmetricand

assymetric reflector.•ConvenienceoutletandswitchK.O.sprovided.•Pushthroughlampholderswithrotorforsecure

lamp retention.•Optionalhangersandguards.

T5 side-mount strip series 26",38",50"Surface side-mount strips (SM)

30˚

60˚350

700

1050

Candlepower Curve

SV4S228UNVPG 2 T5 Strip

1⅜"(35mm)

2⅜"(60mm)

2" (51mm)

1⅜"(35mm)

2⅜"(60mm)

2" (51mm)

RCR C.U.

1 90 2 77 3 67 4 59 5 52 6 46 7 41 8 37 9 33 10 30

Reference data

Efficiency 93,3% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 66.0W Ballastfactor 1.0

Ordering information

Type Length (nominal)

Number of lamps T5 T5HO

Strip T5

22"22" 34"34" 46"46" 92"92"

121212

2(tandem)4(tandem)

SV2S114SV2S214SV3S121SV3S221SV4S128SV4S228SV8S128SV8S228

SV2S124SV2S224SV3S139SV3S239SV4S154SV4S254SV8S154SV8S254

30˚

60˚350

700

Candlepower Curve

SM4S228UNVPG 2 T5 Sidemount Strip

3" (76mm)2" (51mm)

1 ⅜" (35mm)

1 ⅜" (35mm)

4" (102mm)2" (51mm)

RCR C.U.

1 86 2 74 3 65 4 57 5 50 6 45 7 40 8 36 9 33 10 30

Reference data

Efficiency 94,5% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 66.0W Ballastfactor 1.0

Ordering information

Type Length (nominal)

Number of lamps T5 T5HO

Side-mount Strip T5

22"22" 34"34" 46"46"

121212

SM2S114SM2S214SM3S121SM3S221SM4S128SM4S228

SM2S124SM2S224SM3S139SM3S239SM4S154SM4S254

Strip T5 Voltage Ballast Options Surface Strips 120=120V SeenextpageSeenextpage 277=277V UNV=120-277V

Strip T5 Voltage Ballast Options Surface Strips 120=120V SeenextpageSeenextpage 277=277V UNV=120-277V

UNV

UNV

SV4S228

SM4S228

PG

PG

Example

Example

T5 strip series 22",34",46",92"Surface strips (SV)

Page 210: Linear recessed and surface lighting

4.207Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

T5 staggered strip series 26",38",50"Surface staggered strips

Application data*

Luminaire spacing FC W/Sq Ft

50' x 70' x 8.5' Space 12' on center 29 .45

30' x 30' x 8.5' Space 10' on center 36 .66

12' x 16' x 8.5' Space 8' on center 54 1.4

* Average footcandles mounted total LLF Reflectance 60% ceiling, 50%wall,20%.FloorT5ratedat2610lumens(25°C).

Features•Only2"Wide.•Utilizescompact,highefficiency,T5orT5HOlamps.•Fullyenclosedwiring.•Optionalwhiteorspecular,symmetricand

assymetric reflector.•ConvenienceoutletandswitchK.O.sprovided.•Pushthroughlampholderswithrotorforsecurelamp

retention.•Optionalhangersandguards.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)

and type and add as suffix, e.g. UNVPG.

Ballast type

ElectronicT5(1or2LPB)Programstart PGElectronicT5(1or2LPB)PowerSpecDimming PF (120/277Vonly)

LPB=Numberoflampsperballast.

Radio interference filter: Suffix: R . 120 or 277 volt at 50 or 60Hz.

Stem and canopy sets:Suspendluminaire12",18",24",36",or48"fromsurface.(Twoperluminaireisrecommended.For34"and46"SVStriponly.) Catalog no.: SV5F12(12");SV5F18(18");SV5F24 (24");SV5F36(36");SV5F48(48")

Chain hanging kit: Includes two 5' heavy duty link chains with sturdy “V”hookforfixturesuspension.(34"and46"SVStriponly.)Catalogno.:AH5 CSP

Wire guard: white wire guard. Catalog no.: For SVStripT534":SV5GXW3 For SVStripT546":SV5GXW4

Reflectors: See Page page 4.208 + 4.209

30˚

60˚

0

0

Candlepower Curve

0

SS4S228UNVPG 2 T5 Staggered Strip

3 ⅛" (79mm)

2 ⅜" (60mm)

26 ½" (673mm)

38 ¼" (972mm)

50" (1270mm)

4" (102mm)

4" (102mm)

4" (102mm)

1 7�16" (37mm)

Ordering information

Type Length (nominal)

Number of lamps T5 T5HO

26 ½"26 ½"38 ¼"38 ¼"50"50"

121212

SS2S114SS2S214SS3S121SS3S221SS4S128SS4S228

SS2S124SS2S224SS3S139SS3S239SS4S154SS4S254

Staggered Strip T5

Staggered Voltage Ballast Options Strip T5 120=120V Seepage4.207 See page 4.207 Surface Strips 277=277V andpage4.216 UNV=120-277V

UNVSS4S228 PGExample

RCR C.U.

1 88 2 76 3 66 4 58 5 50 6 45 7 40 8 36 9 32 10 29

Reference data

Efficiency 90,4% Spacing ratio 1.5

Electronic ballast

Inputwatts(120V) 66.0W Ballastfactor 1.0

Page 211: Linear recessed and surface lighting

4.208 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

30˚

60˚300

600

900

Candlepower Curve

SV5R1S4SSLD/SV4S154UNVPG 1 T5 Symmetric Silver

2 ½"(64mm)

1 ⅜"(35mm)

4 ⅛" (105mm)

2" (51mm) RCR C.U.

1 90 2 77 3 67 4 59 5 52 6 46 7 41 8 37 9 33 10 30

30˚

60˚300

600

900

Candlepower Curve

SV5R1W4SSLD/SV4S254UNVPG 2 T5 Symmetric White

4 ⅛" (105mm)

2" (51mm)

2 ½"(64mm)

1 ⅜"(35mm)

RCR C.U.

1 86 2 74 3 65 4 57 5 50 6 45 7 40 8 36 9 33 10 30

Features•Only1⅜"deep.•InstallationonregularSVT5strip,1or2lamps.•Availableinwhiteorhighreflectivityspecularf inish.•Optionalmicro-perforatedorslottedwhitereflector.

Reference data

Efficiency 87,5% Spacing ratio 1.9

Electronic ballast

Inputwatts(120V) 64.0W Ballastfactor 1.0

Application data*

Luminaire spacing FC W/Sq Ft

50' x 70' x 8.5' Space 12' on center 25 .44

30' x 30' x 8.5' Space 10' on center 31 .64

12' x 16' x 8.5' Space 8' on center 47 1.3

*AveragefootcandlesmountedtotalLLF=.90Reflectance80%ceiling,50%wall,20%FloorT5ratedat(25°C).

Lamp rated at 2610 lumens

Reference data

Efficiency 78.7% Spacing ratio 1.4

Electronic ballast

Inputwatts(120V) 121.0W Ballastfactor 1.0

Ordering information

Type Length (nominal)

Reflector for T5 Strip*

Symetric Reflector White

22" 34" 46" 92"

SV5R1W2SSLD** SV5R1W3SSLD** SV5R1W4SSLD** 2X SV5R1W4SSLD**

Symetric Reflector Silver

22" 34" 46" 92"

SV5R1S2SSLD SV5R1S3SSLD SV5R1S4SSLD 2X SV5R1S4SSLD

* Use with 1 or 2 T5 Strip (SV)** For Slotted White Reflector, replace Solid White SLD by SLT

For Microperforated White Reflector, replace Solid White SLD by PER

Application data*

Luminaire spacing FC W/Sq Ft

50' x 70' x 8.5' Space 12' on center 50 .83

30' x 30' x 8.5' Space 10' on center 51 1.2

12' x 16' x 8.5' Space 8' on center 84 2.5

*AveragefootcandlesmountedtotalLLF=.90Reflectance80%ceiling,50%wall,20%FloorT5ratedat(25°C).

Lamp rated at 4400 lumens

Ordering information

Type Length (nominal)

Reflector for T5 Strip*

Symetric Reflector White

22" 34" 46" 92"

SV5R1W2SSLD** SV5R1W3SSLD** SV5R1W4SSLD** 2X SV5R1W4SSLD**

Symetric Reflector Silver

22" 34" 46" 92"

SV5R1S2SSLD SV5R1S3SSLD SV5R1S4SSLD 2X SV5R1S4SSLD

* Use with 1 or 2 T5 Strip (SV)** For Slotted White Reflector, replace Solid White SLD by SLT

For Microperforated White Reflector, replace Solid White SLD by PER

Symmetric reflector 2', 3', 4'For 1 or 2 lamps T5 strip (SV)

Page 212: Linear recessed and surface lighting

4.209Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Asymmetric reflector 2', 3', 4'For 1 or 2 lamps T5 strip (SV)

Features•Only1⅜"deep.•InstallationonregularSVT5strip,1or2lamps.•Availableinwhiteorhighreflectivityspecularf inish.

30˚

60˚

Candlepower Curve

300

600

SV5R1W4ASLD/SV4S154UNVPG 1 T5 Asymmetric White

3 ⅛" (79mm)

2" (51mm)

2 ½"(64mm)

1 ⅜"(35mm)

RCR C.U.

1 88 2 76 3 66 4 58 5 50 6 45 7 40 8 36 9 32 10 29

30˚

60˚

300

600

Candlepower Curve

SV5R1W4ASLD/SV4S254UNVPG 2 T5 Asymmetric White

3 ⅛" (79mm)

2" (51mm)

2 ½"(64mm)

1 ⅜"(35mm)

RCR C.U.

1 86 2 75 3 65 4 57 5 50 6 45 7 40 8 36 9 32 10 29

Reference data

Efficiency 91.8% Spacing ratio -

Electronic ballast

Inputwatts(120V) 64.0W Ballastfactor 1.1

Reference data

Efficiency 85.8% Spacing ratio -

Electronic ballast

Inputwatts(120V) 121.0W Ballastfactor 1.0

Ordering information

Type Length (nominal)

Reflector for T5 Strip*

Symetric Reflector White

22" 34" 46" 92"

SV5R1W2ASLD** SV5R1W3ASLD** SV5R1W4ASLD** 2X SV5R1W4ASLD**

Symetric Reflector Silver

22" 34" 46" 92"

SV5R1S2ASLD SV5R1S3ASLD SV5R1S4ASLD 2X SV5R1S4ASLD

* Use with 1 or 2 T5 Strip (SV)** For Slotted White Reflector, replace Solid White SLD by SLT

For Microperforated White Reflector, replace Solid White SLD by PER

Ordering information

Type Length (nominal)

Reflector for T5 Strip*

Symetric Reflector White

22" 34" 46" 92"

SV5R1W2ASLD** SV5R1W3ASLD** SV5R1W4ASLD** 2X SV5R1W4ASLD**

Symetric Reflector Silver

22" 34" 46" 92"

SV5R1S2ASLD SV5R1S3ASLD SV5R1S4ASLD 2X SV5R1S4ASLD

* Use with 1 or 2 T5 Strip (SV)** For Slotted White Reflector, replace Solid White SLD by SLT

For Microperforated White Reflector, replace Solid White SLD by PER

Page 213: Linear recessed and surface lighting

4.210 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Specification

Features•Fixturessuitableforindividual,row,surface,

or suspension mounting.•Efficiency92.3%(T12).•Quarterturnlatchsecureschannelcoverforeasy

wireway access.•Heavydutychannelofcodegaugedieformedsteel.•Fullyenclosedwiring.•U.L.Listedsnap-onendcaps.•Combinationendcapforcontinuousrowmounting.•Greengroundingscrewinstalledinchannel.•Lampholdersmaybeindividuallyreplacedorrewired.•T8(380mA)andT12(800mA)standardfixturesinclude

ballasts rated for –20°F starting temperature.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)

and type and add as suffix, e.g. 120SO.

Ballast type <10THD <20THD

Electronic T8 HI* SO*Electronic P.S. T8 P2 –Electro-Magnetic – PHElcetronic T12 Standard – SS

* Instant start.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Optional hangers, wire guards & aligners, see page 4.216.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

SD8S296HO120SS

Reference data

Efficiency 92,3% Spacing ratio 1.59

Electronic ballast

Inputwatts(120V) 232W LER =FS 67.3

5 1 ⁄16"(T12) (129mm)

4 13 ⁄16"(T8) (122mm)

1 Lamp

5 1 ⁄16"(T12) (129mm)

4 13 ⁄16"(T8) (122mm)

2 Lamp

5 ⅞"(149mm)

5 ⅞"(149mm)

⅞" Dia.K.O. (4)

½" Dia.K.O. (2)Side View

2 ¾"(70mm)

4"(102mm) 6" (152mm)

⅞" Dia. K.O. (4) S HookK.O. (8)

4' Channel

4 ⅛"(105mm)

2" Dia. K.O.

4 ⅝"(117mm)

6 ⅜" (162mm)

1 ⅛" (29mm)

48" (1220mm)

30˚

60˚1400

2800

Candlepower CurveOrdering information

Fixture length

Nominal lamp

length

Lamps qty - type

Catalog no.SD 1 or 2 lamps wide

48"96"96"192"96"192"

48"48"96"96"96"96

1-T12HO1-T12VHO1-T12HO

1-T12HOinTandem(2Total)1-T12VHO

1-T12HOinTandem(2Total)

SD4S148HO SD4S148VO SD8S196HOSD8T196HOSD8S196VOSD8T196VO

48" 48"2-T8HO2-T12HO2-T12VHO

SD4S244HOSD4S248HOSD4S248VO

96" 96" 2-T12HO2-T12VHO

SD8S296HOSD8S296VO

96"192"96"

96"1-T8HO

1-T8inTandem(2Total)2-T8HO

SD8S186HOSD8T186HOSD8S286HO

ReflectorsType Size Catalog no.

Symmetrical 48" NSYMF48S CSP

Asymmetrical 48" NASYF48S CSP

Accessories

AC1 CSP=spacereach. NAH3D CSP =twisteeeach. NAHD CSP=slidegripeach. AWG3W CSP=wireguardeach4ft.All symmetric and asymmetric reflectors are shipped separately from the fixture.

SD Strip Voltage Ballast Options High Output 120=120V Seepage4.210 See page 4.210 VeryHighOutput 277=277V andpage4.216

120SD8S296HO ASSExample

72" (1829mm) or 96" (2438mm)6" (152mm)

⅞" Dia. K.O. (4)

6' & 8' Channel

4 ⅛"(105mm)

2" Dia. K.O.6 ⅜" (162mm)

S HookK.O. (8)

4 ⅝"(117mm)

24"(610mm)

4" (102mm)3 1�16"(78mm)

SD Deep StripHigh output/very high output

Page 214: Linear recessed and surface lighting

4.211Comprehensive lighting catalog 7th Edition

Specification – Linear recessed and surface lighting

Features•Full3"overlapeliminatesshadowscaused

by lampholders or lamp ends.•Housingisonly15/8"deep.•Safe-handlingmetaledges.•Fullyenclosedwireway.•Excellentforperimetercovelightingorother

applications where continuous even illumination is required.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI* SO*1-4 Lamp Electronic T8 H4* O4*LOL T8 Dimming – PS

Magnetic T12 HPF Models – PH LPF Models – PL

* Instant start.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Optional hangers, wire guards & aligners, see page 4.216.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

SS4S132HPFUNVHI SS4S232HPFUNVHI

1 Lamp Reference data

Efficiency 89,5% Spacing ratio 1.6

Ordering information

Fixture length

Nominal lamp

length

Lamps qty - type

1 LampCatalog no.

23 15 ⁄16"23 15 ⁄16"35 15 ⁄16"35 15 ⁄16"47 15 ⁄16"68 15 ⁄16"68 15 ⁄16"92 15 ⁄16"

24"24"36"36"48"36"36"48"

1-T81-T121-T81-T121-T82-T82-T122-T8

SS2S117HPF SS2S120HPF SS3S125HPFSS3S130HPFSS4S132HPFSS6T125HPFSS6T130HPFSS8T132HPF

Ordering information

Fixture length

Nominal lamp

length

Lamps qty - type

2 LampCatalog no.

26 15 ⁄16"26 15 ⁄16"38 15 ⁄16"38 15 ⁄16"50 15 ⁄16"74 15 ⁄16"74 15 ⁄16"98 15 ⁄16"

24"24"36"36"48"36"36"48"

2-T82-T122-T82-T122-T84-T84-T124-T8

SS2S217HPF SS2S220HPF SS3S225HPFSS3S230HPFSS4S232HPFSS6T225HPFSS6T230HPFSS8T232HPF

Ordering information

Fixture length

Nominal lamp

length

Lamps qty - type

1 LampCatalog no.

1 LampCatalog no.

24"24"36"36"36"48"48"

24"24"36"36"36"48"48"

T8T12T8T12T12T12T8

SM117HPF SM120LPF SM125HPFSM130LPFSM130HPFSM134LPFSM132HPF

SM217HPFSM220LPFSM225HPF–SM230HPF–SM232HPF

SS Strip Voltage Ballast OptionsNarrowWidthChannel 120=120V Seepage4.211 See page 4.211 277=277V andpage4.216 UNV=120-277V(ElectT8only)

UNVSS4S132HPF AHIExample

2lampReflectors(T8only)Type Size Catalog no.

Asymmetrical24"36"48"

ASYF24STGASYF36STGASYF48STG

1lampT8Reflectors(T8only)Type Size Catalog no.

Asymmetrical24"36"48"

ASYC20STGASYC30STGASYC40STG

Features•Only113/16"deep.•Efficiency95.8%.•Ballastcoversecuredbyquarter-turnlatches.•Fullyenclosedwiring.•Maybesurfacemountedorsuspended.•Maybecontinuousrowmounted.•Codegauge,heavyduty,dieformedsteelchannel.•Multipleknockoutsforconvenientinstallation.•Lampholdersmaybeindividuallyreplacedorrewired.•Highreflectancebakedwhiteenamelfinish.•U.L.Listedfordamplocations.

2 Lamp Reference data

Efficiency 89,5% Spacing ratio 1.6

SM132HPFUNVHI

SIDE VIEW

TOP VIEW2"(51mm)

2 ½"(66mm)

4 ⅛"(105mm)

1 13�16"(46mm)

1 13�16"(46mm)

⅞" K.O. (4)

⅞" K.O. (3) ½" K.O. (2)

1 1�16" (27mm) 1 1�16" (27mm)1 ¼"

(32mm)3 ¾"

(95mm)

SIDE VIEW

TOP VIEW2"(51mm)

2 ½"(66mm)

4 ⅛"(105mm)

1 13�16"(46mm)

1 13�16"(46mm)

⅞" K.O. (4)

⅞" K.O. (3) ½" K.O. (2)

1 1�16" (27mm) 1 1�16" (27mm)1 ¼"

(32mm)3 ¾"

(95mm)

1 Lamp

SIDE VIEW

TOP VIEW2" (51mm)

2½"(66mm)

5¹¹�¹6" (145mm)

1¹3�¹6"(46mm)

1¹3�¹6"(46mm)

⅞" K.O. (4)

⅞" K.O. (3) ½" K.O. (2)

1¹�¹6" (27mm) 1¹�¹6" (27mm)1¼"

(32mm)3¾" (95mm)

2 Lamp

DimensionsChannel length Inches (mm)

2' Channel3' Channel4' Channel

24"36"48"

(610mm)(914mm)(1219mm)

1 ⅝" (141mm)

3 ¾" (T12) (95mm)

3 ½" (T8) (89mm)

4 ¼" (110mm)

1 ⅝" (141mm)

3 ¾" (T12) (95mm)

3 ½" (T8) (89mm)

4 ¼" (110mm)

SS Staggered StripSurface strip

SM Side Mount StripSurface strip

Page 215: Linear recessed and surface lighting

4.212 Philips Lightolier For complete specif ication information visit www.lightolier.com

Linear recessed and surface lighting – Standard

Features•Fixturessuitableforindividual,row,surface,or

suspension mounting.•Efficiency94%(T8).•Quarterturnlatchsecureschannelcoverforeasy

wireway access.•Heavydutychannelofcodegaugedieformedsteel.•Only21/2"wide.•Fullyenclosedwiring.•U.L.Listedsnap-onendcaps.•Combinationendcapforcontinuousrowmounting.•Greengroundingscrewinstalledinchannel.•U.L.listedfordirectmountingonlowdensityceilings

and damp location.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI* SO*LOL T8 Dimming – PS

Magnetic T12 Standard Electro-Magnetic PL – LPF Models

Electronic T12 SS – HPFModels18",24",36"only

* Instant start.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Optional hangers, wire guards & aligners, see page 4.216.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

SN4S132HPFUNVHI

SIDE VIEW

TOP VIEW2" (51mm)

2 ½"(66mm)

2 ½"(66mm)

3 13�16"(94mm)

1 13�16"(46mm)

⅞" K.O. (4)

⅞" K.O. (3)½" K.O. (2)

1 1�16" (27mm) 1 1�16" (27mm)1 ¼"

(32mm)

3 ¾" (95mm)

30˚

60˚200

400

Candlepower CurveReference data

Efficiency 94,0% Spacing ratio 1.6

Electronic ballast

Inputwatts(120V) 36.0W LER =FS 66.7

DimensionsChannel length Inches (mm)

18"Channel2' Channel3' Channel4' Channel6' Channel8' Channel

18"24"36"48"72"96"

(457mm)(610mm)(914mm)(1219mm)(1829mm)(2438mm)

Ordering informationFixture length

Lamp length

Lamps qty - type Catalog no.

24"36"48"96"

24"36"48"48"

1-T81-T81-T8

1-T8inTandem(2Total)

SN2S117HPF SN3S125HPF SN4S132HPFSN8T132HPF

18"18"24"24"36"36"48"

18"18"24"24"36"36"48"

1-T121-T121-T121-T121-T121-T121-T12

SN1S115HPFSN1S115LPFSN2S120HPFSN2S120LPFSN3S130HPFSN3S130LPFSN4S134LPF

ReflectorsType Size Catalog no.

Symmetrical24"36"48"

NSYMC20 CSP NSYMC30 CSP NSYMC40 CSP

Asymmetrical24"36"48"

NASYC20 CSP NASYC30 CSP NASYC40 CSP

SN Strip Voltage Ballast OptionsNarrowWidthChannel 120=120V Seepage4.212 See page 4.212 277=277V andpage4.216 UNV=120-277V (ElectT8only)

UNVSN4S132HPF AHIExample

Accessories

AC1 CSP=spacereach. AWG1W CSP=wireguardeach.All symmetric and asymmetric reflectors are shipped separately from the fixture.

Symmetrical

5 ⅛"(130mm)

6"(152mm)

Asymmetrical

5 ⅛"(130mm)

5 7 ⁄16"(138mm)

SNStripNarrow width channel

Page 216: Linear recessed and surface lighting

4.213Comprehensive lighting catalog 7th Edition

Standard – Linear recessed and surface lighting

Features•Fixturessuitableforindividual,row,surface,or

suspension mounting.•Efficiency97.3%(T8).•Quarterturnlatchsecureschannelcoverforeasy

wireway access.•Heavydutychannelofcodegaugedieformedsteel.•Fullyenclosedwiring.•U.L.Listedsnap-onendcaps.•Combinationendcapforcontinuousrowmounting.•Greengroundingscrewinstalledinchannel.•Lampholdersmaybeindividuallyreplacedorrewired.•U.L.listedfordirectmountingonlowdensityceilings

and damp locations.

Options & accessories page 4.216Ballast:Specifyvoltage(120,277orUNV)andtypeandaddassuffix,e.g.UNVHI.

Ballast type <10THD <20THD

Electronic T8 HI* SO*1-4 Lamp Electronic T8 H4* O4*LOL T8 Dimming – PS

Magnetic T12 Standard Electro-Magnetic – PL LPF Models

Electronic T12 Standard Electro-Magnetic – SS HPF and SL Models

* Instant start.

Electrical/wiring options: For special wiring, fusing, electronic dimming ballasts, consult factory. Optional hangers, wire guards & aligners, see page 4.216.Fusing: Suffix: A (Internalfast-blowfusing).

Suffix: C (Internal slow-blow fusing).

SW4S232HPFUNVHI

30˚

60˚400

800

Candlepower CurveReference data

Efficiency 97,3% Spacing ratio 1.58

Electronic ballast

Inputwatts(120V) 60.3W LEF =FS 80.5

Ordering informationFixture length

Lamp length 1 Lamp -type 1 Lamp

Catalog no. 2 Lamp -type 2 LampCatalog no.

24"36"48"96"96"

24"36"48"48"96"

1-T81-T81-T8

1-T8inTandem(2Total)1-T8 SL

SW2S117HPF SW3S125HPF SW4S132HPFSW8T132HPFSW8S159SL

2-T82-T82-T8

2-T8(inTandem-2Total)2-T8 SL

SW2S217HPF SW3S225HPF SW4S232HPFSW8T232HPFSW8S259SL

24"24"36"36"48"48"72" 96"192"

24"24"36"36"48"48"72" 96"96"

1-T121-T121-T121-T121-T12

1-T12SL1-T12SL1-T12SL

1-T12inTandem(2Total)

SW2S120HPFSW2S120LPFSW3S130HPFSW3S130LPFSW4S134LPFSW4S148SLSW6S172SLSW8S196SLSW8T196SL

2-T122-T122-T122-T122-T12

2-T12SL2-T12SL2-T12SL

SW2S220HPFSW2S220LPFSW3S230HPFSW3S230LPFSW4S234LPFSW4S248SLSW6S272SLSW8S296SL–

ReflectorsType Size Catalog no.

Symmetrical24"36"48"

NSYMF24S CSP NSYMF36S CSP NSYMF48S CSP

Asymmetrical24"36"48"

NASYF24S CSP NASYF36S CSP NASYF48S CSP

SW Strip Voltage Ballast Options Standard Strip Wide 120=120V Seepage4.213 See page 4.213 277=277V andpage4.216 UNV=120-277V (ElectT8only)

UNVSW4S232HPF AHIExample

3¾"(T12) (95mm)

3½"(T8) (89mm)

1 Lamp

3¾"(T12) (95mm)

3½"(T8) (89mm)

2 Lamp

Accessories

AC1 CSP=spacereach. NAH3 CSP=twisteeeach. AWG1W CSP=wireguardeach.All symmetric and asymmetric reflectors are shipped separately from the fixture.

SW StripStandard strip wide

Page 217: Linear recessed and surface lighting

Linear recessed and surface lighting

4.214 Philips Lightolier For complete specif ication information visit www.lightolier.com

Add appropriate suffix to Cat. no.

BF=2 lamps Elec. 55W TT5

BP=2lampsElec. 50W TT5

DA=iGENDALIDS=iGENBroadCast

4Sensorw/iGENBallastF4 =Electronic18WQT4pinO3=3lampElectronicT8InstantstartO4=Electronic4LPBT8InstantstartPA=PowerSpecHDFdimming

Electronic 18W TT5PB=PowerSpecHDFdimming

Electronic 40W TT5PC=PowerSpecHDFdimming

Electronic 50/55W TT5PD=ElectronicDimming

2x42W TTT 4 pinPG=ElectronicT5ProgramstartPS=PowerSpecHDFdimming

Electronic T8SB=2lampsElectronic40WTT5SO=2lampElectronicT8InstantstartTC=Electronic2x32WTTT4pinTD=Electronic2x42WTTT4pinX3=3lamps40WElectronicTT5HI =ElectronicT8<10THDH3=1-3lampElectronicT8<10THDH4=1-4lampElectronicT8<10THD

120=120V277=277VUNV=120-277V

AD=Asymmetric Distribution

CB=Circularlamp shield

GB=Clearacrylic w/Blue projected color face

GC=ClearacrylicGG=Clearacrylic

w/Green projected color face

GR=Clearacrylic w/Red projected color face

LG=Greysolid flat blade louver

LV =Whiteperforated flat blade louver

LW=Whitesolid flat blade louver

OP =One-PiecelampshieldOB=One-piecelampshield

w/SensorOS=OpenSlot(noacrylic)SQ=SquareWindowsbasketSS =LateralWavesideshieldsSR =LateralCurvedsideshields

Catalog numbering logicCoffaire (recessed)

Please note that this ordering guide lists all coffaire luminaire numbering logic. The possible combinations and options do not apply to all luminaires. Please refer to the specific luminaire page.

FamilyLumin. width

Ceiling type

Lamp shield with luminaire finish

Lamp shield details

Lamp qty

Lamp type Voltage Ballast Options

QVS 2 G PF OS 3 32 UNV H3 A

QVC=RoundEclipseQVE =EleganceQVB=SlimSquareQMF=MetaformSRQVF =SlimSurfaceQVH=SlimSRQVS =ClassicClassic

OP Windows SmartVisionLouver Metalyte Metalyte Louver

QVW=ClassicWallEclipse Wall Windows Wall

QVL =WavesQVA=AirQHE=High-EfficiencyQVD=AlterTileLyteQCE=Concept

EleganceQCH=ConceptSRQCJ =Concept

1=12"2=24"5=20"

1=1lamp2=2lamp3=3lamp4=4lamp

G=GridS=SurfaceT=SlotT-grid

Ceiling

GL=GlassLampShieldPA=SolidWhite

Perimeter Lamp Shield w/White Mesh Center

PC=SolidWhitePerimeter Lamp Shield w/White Mesh Inner Area and Solid center

PF =MicroperforatedMesh Lamp Shield

PT=MetallicReflector w/Microperforated Mesh Lamp Shield

PG=MicroperforatedMesh Lamp Shield w/TitaniumBody

PW=MicroperforatedMesh Lamp Shield w/WhiteBody

SG=SolidTitanium Lamp Shield w/TitaniumBody

SW=SolidWhite Lamp Shield w/WhiteBody

14=2'T514W17=2'T817W24=2'T5HO24W32=4'T832WFT=TT5FL=TwoTT5in2'x4'TT=TTTTripleTube28=4'T528W54=4'T5HO54WQT=QuadQTlamp

Add appropriate suffix to Cat. no.

HI=ElectronicT8 Instant start

H3=1-3lampElec. T8 Instant start

PG=ElectronicT5 Program start

PR=ElectronicTT5(40W) Program start

BP=2lampsElec. 50W TT5

P2=ElectronicT8 Program start

P3=1-3lampElec.T8 Program startI3 =1-3lampElec.TT5(40W)

Instant start

120=120V277=277VUNV=120-277V

PF=PerforatedMesh Shield

HP=HighperformanceSQ=AcrylicLensand

Perforated Steel Center Panel

CF S 2 G PF 2 32 UNV

H3 A

HI A

1=1lamp2=2lamp3=3lamp

14=2'T514W17=2'T817W 24=2'T5HO24WFT=TT528 =4'T528W32 =4'T832W54 =4'T5HO54W

CF=Coffaire A=Airsupply and returnS=StaticH=Airreturn

1=12"2=24"

G=BothStandardGrid and Slot Grid

N=9/16"NarrowT-Grid

Family Body styleLumin. width Ceiling type Shielding

Lamp qty

Lamp type Voltage Ballast Options

Catalog numbering logicAlter

Please note that this ordering guide lists all Alter Soft Light numbering logic. The possible combinations and options do not apply to all luminaires. Please refer to the specific luminaire page.

Page 218: Linear recessed and surface lighting

Linear recessed and surface lighting

4.215Comprehensive lighting catalog 7th Edition

SO=ElectronicT8O3=1-3lamp

Electronic T8O4=1-4lamp

ElectronicT8SB=Electronic40WTT5X3=1-3lampElectronic40WTT5PS=LOLPowerSpec

T8 DimmingPB=LOLPowerSpec

40W TT5 DimmingHI=ElectronicT8<10THDH3=1-3lamp

ElectronicT8<10THDH4=1-4lamp

ElectronicT8<10THD

in a lumin. cross sec-tion1=1lamp2=2lamp3=3lamp4=4lamp

17=2'T8 20=2'T1232=4'T82U=T8U1.66U=T8U6or

T12U6FT=TT5

8 =1x8 (1'x4')9 =3x3 (2'x2')12=2x6 (2'x4')

3x4 (2'x2')1x12(1x4')

16=4x4 (2'x2')2x8 (2'x4')

18=3x6 (2'x4')20=1x20(6'x48')24=2x12(1'x4')

3x8 (2'x4')27=3x9 (2'x4')29=2x9 (2'x4')32=4x8 (2'x4')

Catalog numbering logicParabolic (recessed and surface)

Please note that this ordering guide lists all parabolic luminaire numbering logic. The possible combinations and options do not apply to all luminaires. Please refer to the specific luminaire page.

Catalog numbering logicLens (recessed and surface) except XP troffer

Please note that this ordering guide lists all lens luminaire numbering logic. The possible combinations and options do not apply to all luminaires. Please refer to the specific luminaire page.

Family Body styleLumin. width

Ceiling type

Number of cells

Louver finish

Mounting method

Lamp qty

Lamp type Voltage Ballast Options

DP A 2 G 18 L S 3 32 UNV

DP=Deepcel Plus

VR=Vision Smart Recom- mended

ST=StacklyteLI =LytecelIndividualLC=LytecelContinuous

A=Airsupplyand return

S=StaticB=Surfacebox

L=Lowiridescence Semi-specular

P=Lowiridescence Specular

1=12"2=24"6=6"

G=Grid (lay-inTbar)

T=Slotgridortwo-directional concealed T (seeoptions)

F=Flangefordrywall, plaster or concealed splice

S=Surface

for ballast cover louverS=SingleP=TwinR=Specular

reflector

H3 A

Add appropriate suffix to Cat. no.

120=120V277=277VUNV=120-277V

SO=ElectronicT8O3=1-3lamp

Electronic T8O4=1-4lamp

ElectronicT8SB=Electronic40WTT5X3=1-3lampElectronic40WTT5PS=LOLPowerSpec

T8 DimmingPB=LOLPowerSpec

40W TT5 DimmingHI=ElectronicT8<10THDH3=1-3lamp

ElectronicT8<10THDH4=1-4lamp

ElectronicT8<10THD

in a lumin. cross sec-tion1=1lamp2=2lamp3=3lamp4=4lamp6=6lamp

17=2'T8 20=2'T1232=4'T82U=T8U1.66U=T8U6or

T12U6FT=TT5

SP S 2 G FS VA 4 32 UNV

SP=SpecPlusPR=Prismalyte PlusSU=Operating Room LuminairePN=PrismalyteBoxSL=SLSurfacebox

A=AirsupplyS=StaticB=Surfacebox

FS=FlatsteelframeRA=Regressed

aluminum frame

FA=Flataluminum frame iridescence

RF=Regressedaluminum floating door

1=12"2=24"

G=Grid (lay-inTbar)

F=Flangefordrywall, plaster or concealed splice

S=Surface

VA=Standard(virgin acrylic - see options and consultfactory)

H4 A

Add appropriate suffix to Cat. no.

120=120V277=277VUNV=120-277V

Family Body styleLumin. width

Ceiling type

Lens frame

Lens/shield type

Lamp qty

Lamp type Voltage Ballast Options

Page 219: Linear recessed and surface lighting

Linear recessed and surface lighting

4.216 Philips Lightolier For complete specif ication information visit www.lightolier.com

Radio interference filterRF =Inductivecapacitorcircuitdesignedto minimize interference from line radiationorfeedback.120Vor277V,50 or 60 Hz. One per fixture.

e.g: WA4A232120SO RF

Cord and plug convenienceCPA(120V) CPB(277V) =Factorywired six foot 3-conductor cord with a heavy-duty twist-lock plug withproper NEMAconfigurationforspecif ied voltage.

e.g: WA4A232120SO CPA

Fluorescent emergency lighting systemEM =Factory-installedemergencypower battery pack with charger and inverter,B100orequal,120Vor277V.

e.g: WA4A232120SO EM

Chain hanger kitAH5 CSP (SW/SD/KW/KDfixtures)

Two5'heavydutychainswithsturdy“V”hooks that grip fixtures at four knock-out points for level suspension.

Row couplersNHDC-W CSP (SD/SWfixtures)

Required to connect, stabilize stem or chain-mounted fixtures used in continuous rows.

Wire guardsAWG1W CSP (SNstrip) AWG3W CSP (SW/SDstrip)

Hinge and latch positive-lock construction, complete with longitudinal and transverse struts for secure protection.BakedWhiteEnamel.

Heavy duty slide-grip hangerNAHD CSP (SD/KDfixtures) NAHW CSP(SW/KWfixtures)

Hinge and latch positive-lock construction, complete with longitudinal and transverse struts for secure protection.

FusingA=Internalfast-blowfusing.

C=Internalslow-blowfusing.

e.g: WA4A232120SO A

Stem and canopy setASC6 CSP(6") ASC12 CSP (12") ASC18 CSP(18") ASC24 CSP(24")

Suspendsfixture6",12",18"or24"fromsurface and can be used in conjunction with Heavy-Duty Slide Grip Hanger.

Canopy spacer (1 ½")AC1 CSP

Suspends fixture approximately 1½"fromsurface.

Twist tee hangerNAH3 CSP (SW/KWfixtures) NAH3D CSP (SD/KDfixtures)

ForSW/SD/KW/KDinstallationof4⅛"wide(channel)f ixtureonexposed “T” grid ceilings on hard surfaces.Provides1½"clearancefrom surface.

Surface/wallOptions & accessories

Page 220: Linear recessed and surface lighting

Linear recessed and surface lighting

4.217Comprehensive lighting catalog 7th Edition

Reflector row alignersKND CSP

Clear, tough, plastic aligners forKW/KDfixturereflectors.

Radio interference filterRF =Inductivecapacitorcircuitdesignedto minimize interference from line radiationorfeedback.120Vor277V,50 or 60 Hz. One per fixture standard.

e.g: TU4A232120S0 RF

FusingA=Internalfast-blowfusing.

C=Internalslow-blowfusing.

e.g: TF4A232120S0 A

Cord and plug convenienceCPA(120V) CPB(277V) =Factorywired six foot 3-conductor cord with a heavy-duty twist-lock plug withproper NEMAconfigurationforspecif ied voltage.

e.g: TU4A232120S0 CPA

Fluorescent emergency lighting systemEM =Factory-installedemergencypower battery pack with charger and inverter,B100orequal,120Vor277V.

e.g: TU4A232120SO EM

Chain hanger kitAH5 CSP (KW/KDfixtures)

Two5'heavydutychainswithsturdy“V”hooks that grip fixtures at four knock-out points for level suspension.

Wire guardsAWG4W CSP(KD/KWfixtures) LFL - 173 (TUfixtures)

Hinge and latch positive-lock construction, complete with longitudinal and transverse struts for secure protection.

Heavy duty slide-grip hangerNAHD CSP (KDfixtures) NAHW CSP(KWfixtures) LFL - 111 (TUfixtures)

Hinge and latch positive-lock construction, complete with longitudinal and transverse struts for secure protection.

Twist tee hangerNAH3 CSP (SW/KWfixtures) NAH3D CSP (SD/KDfixtures)

ForSW/SD/KW/KDinstallationof4⅛"wide(channel)f ixtureonexposed “T” grid ceilings on hard surfaces.Provides1½"clearancefrom surface.

Stem and canopy setASC6 CSP(6") ASC12 CSP (12") ASC18 CSP(18") ASC24 CSP(24")

Suspends fixture 6', 12', 18' or 24' from surface and can be used in conjunction with Heavy-Duty Slide Grip Hanger or Ice-Tong Hanger.

Row couplersNHDC-W CSP (KD/KWfixtures)

Required to connect, stabilize stem or chain-mounted fixtures used in continuous rows.

Canopy spacer (1 ½")AC1 CSP

Suspends fixture approximately 1½"fromsurface.

Reflector row alignersTU - SNA(TUfixtures)

Aluminum joiners clamp reflectors together for straight, permanent alignment. Two aligners are included with all 8' f ixtures. For continuous row installations, specify two additional bulk-packed aligners per reflector point.

Housing row couplersLFL - 3(TUfixtures)

IndustrialOptions & accessories

Page 221: Linear recessed and surface lighting

Linear recessed and surface lighting

4.218 Philips Lightolier For complete specif ication information visit www.lightolier.com

“F” Mounting Frame

A B

Ceiling Opening

Fixture

Wire Hangers(by others)

Acoustical Tile(by others)

“F” Mounting Frame

1 ⅛"

“F” Mounting Frame

“F” Mounting Frame

Screws(supplied)

Fixture

Wire Hangers(by others)

Plaster(by others)

“F” Mounting Frame

Plaster Frame

1 ⅛"

Fixture

Wire Hangers(by others)

Acoustical Tile(by others)

“F” Mounting Frame

Channel (by others)

1 ⅛"

¼" Dia. Wire Hanger Hole ⅛" Dia. Screw Assembly Hole

1 ⅛" 3�16"

1 ⅜" 1 ½"

48 ⅝"

25 5�16"

49 5�16"

25 5�16"6 ⅝" OR

12 ⅝"

Features•Designedtopermituseofgrid(NEMA G)f ixturesin

ceilings requiring flanges.•Maybeusedwithany“G” type Philips Lightolier troffer.•MaybeusedinconjunctionwithPhilipsLightolier

plaster frame.•Extrudedaluminumconstructionwithmiteredcorners.•Includesscrewsforcompleteassembly.•Notforcontinuousrowmounting.

“F” Mounting frame assembly 6"x48",1'x4',2'x2',2'x4'

For Mounting in Drywall or Ceilings Requiring Flanges

Ordering information

Catalog number

Fixture Size

Ceiling (cut out) Opening

A B

FK906X4FK91X4 FK92X2 FK92X4

6"X48"1' x 4' 2' x 2' 2' x 4'

6⅝" (168mm)12 ⅝" (321mm)24 ⅝" (626mm)24 ⅝" (626mm)

48⅝" (1235mm)48 ⅝" (1235mm)24 ⅝" (626mm)48 ⅝" (1235mm)

Mounting methods for “F” mounting frame assembly Note: Donotusewirehangers(byothers)atendoff ixture.

Note:Donotusewirerhangers(byothers)atendoff ixture.

Assemble “F”mountingframewithsuppliedscrews(4places).Install “F” mounting frame into ceiling opening. May be used withplasterframe(seereversesideformountingmethods).

Note:Donotusewirerhangers(byothers)atendoff ixture. Note:Donotusewirerhangers(byothers)atendoff ixture.

“F” Mounting frame assembly installation instructions Ceiling cut out dimensionsAssemble “F” mounting frame with screws supplied (4 places).

Install “F” mounting frame into ceiling opening.

May be used with plaster frame. Install f ixture into “F” mounting frame.

1. 2.

Drywall kitFor most recessed fixtures

Page 222: Linear recessed and surface lighting

Linear recessed and surface lighting

4.219Comprehensive lighting catalog 7th Edition

The ULM Module clamps to the ceiling “T” bar and then the fixture is dropped in place. The same ULM Module will f it either standard or slot grid ceilings. Plug-in quick connectors are used for electrical connection of module to fixture.

Housing encloses electrical connections — line or low voltage. Tile is notched and dropped in place.

4 ½"(114mm)

6 ½"(165mm)

4"(102mm)

Exposed T-Grid Ceiling Exposed Slot T-Grid Ceiling

Features•Canaccommodatemostmanufacturerslightor

occupancy sensor switch.•Lineorlowvoltage.•Fitsstandardorslotgridceilingsystems.•Plug-inconnectiontomatingfixture (orderedseparately).

•Securestoceiling"T"(standardorslotgrid).•Ceilingtilehold-down.•18gaugesteelfascia.

Fixture Sensor Manufacturer Manufacturer ULM Module width Finish code Manufacturer part number Power rating Motion or Light 2=24" F=Flat TR1=Tridonic DSISmart120V 120V Sensor Enclosure White TR2 = Tridonic DSISmart277V 120V WS1=WattStopper FS205 24VDC WS2=WattStopper FS305 24VDC WS3=WattStopper FS355 120-277VAC WS4=WattStopper FS405 24VDC LU1 =Lutron C-R-M1-WH 15VDC LU2 =Lutron C-SR-M1-WH 15VDC

2UL FExample

Mates with 2' x 2' & 2' x 4' recessed fixture products

Alter Classic (QVS)

Alter High Efficiency (QHE)

Alter Louver (QVS-LV)

Coffaire (CF)

Deepcel (DP)

HP90 (H9)

Opalescent (OP)

Paraplus (PP)

Prismalyte (PR)

Skyway (SKS)

Specplus (SP)

VisionSmart2'x2' (VR)

VisionSmart2'x4' (VR)

Specifications

Materials: 18 gauge cold rolled steel fascia.

Finish: Flat white.

Housing: 24 gauge galvanized steel.

Labels:I.B.E.W.

The ULM moduleMotion or light sensor enclosure

TheUniversalLightandMotion(ULM)Modulesensorintegrateswithrecessedlightingfixtures. The clean design allows it to blend in nicely with the ceiling system and lighting fixture. The ULM Module is an enclosure that will accommodate most manufacturers motion or daylight sensors in either line or low voltage. It is designed to interface and quick connect to most of our 2x4 and 2x2 recessed lighting fixtures. The ULM Module creates the convenienceofbeingabletobuildamotionordaylightsensor(producedbyothers)intoanyof our recessed fixtures eliminating the potential errors in how the sensors and fixtures are electrically connected. The ULM Module comes packaged complete with the appropriate sensor and can be easily installed and connected to the end of the lighting fixture.

Note: Fixtures and ULM Modules are ordered as separate items. Sensors used and wiring of f ixtures will be based on information provided by specif ier.

Page 223: Linear recessed and surface lighting

Linear recessed and surface lighting

4.220 Philips Lightolier For complete specif ication information visit www.lightolier.com

Ballastcodeoptions

Ballast code Ballast lamp capacity Type Ballast factor THD Voltage Wattage Ballast designation

B3 1 - 3 Lamp Rapid Start 1.00 <10% 120 or 277 40W Generic Electronic1

BA3 1 or 2 Lamp Rapid Start 1.00 <10% UNV 18W Generic Electronic1

BB3 1 or 2 Lamp Rapid Start 0.95 <10% UNV 24W Generic Electronic1

BF3 1 or 2 Lamp Program start 1.00 <10% UNV 55W Generic Electronic1

BP3 1 or 2 Lamp Program Rapid Start 0.98 <10% UNV 50W Generic Electronic1

CD3 1 or 2 Lamp Instant start 0.88 <10% UNV 40W Advance Electronic Centium

CE 1 - 3 Lamp Instant start 0.88 <10% UNV 40W Advance Electronic Centium

CF 1 Lamp Program start 1.00 <10% UNV 40W AdvanceElectronicCentiumIntelliVolt

CT3 1 or 2 Lamp Program start 1.10 <10% UNV 50W or 55W AdvanceElectronicCentiumIntelliVolt

CY 1 - 3 Lamp Program Rapid Start 0.90 <10% UNV 50W or 55W AdvanceElectronicCentiumIntelliVolt

CZ 1 - 4 Lamp Program Rapid Start 0.90 <10% UNV 50W or 55W AdvanceElectronicCentiumIntelliVolt

I3 1 - 3 Lamp Instant start 0.88 <10% UNV 40W Generic Electronic1

IB3 1 or 2 Lamp Instant start 0.88 <10% UNV 40W Generic Electronic1

M7 1 - 2 Lamp Program start 1.00 / 0.03 <10% UNV 40W AdvanceElectronicMarkVIIDimming

MW3 1 or 2 Lamp Program start 0.90 / 0.03 <10% 120 or 277 55W AdvanceElectronicMarkVIIDimming

MX3 1 or 2 Lamp Program start 1.00 / 0.05 <10% 120 or 277 40W AdvanceElectronicMarkXDimming

MZ3 1 or 2 Lamp Program start 0.90 / 0.05 <10% 120 or 277 55W AdvanceElectronicMarkXDimming

P93 1 or 2 Lamp Program start 1.00 <10% UNV 55W Generic Electronic1 90°C

PB3 1 or 2 Lamp Program start 0.95 <10% UNV 40W Philips Lightolier Electronic Dimming

PC3 1 or 2 Lamp Program start 0.90 <10% UNV 55W Philips Lightolier Electronic Dimming

PR3 1 or 2 Lamp Program Rapid Start 1.00 <10% UNV 40W Generic Electronic1

SB3 1 or 2 Lamp Instant start 1.00 <20% 120 or 277 40W Generic Electronic1

X3 1 - 3 Lamp Instant start 0.88 <20% 120 or 277 40W Generic Electronic1

1Genericelectronicballast(Advance,Sylvania,Universal,UltraSaveorGE)chosenbyfactorybasedonavailability.2Ballastfactorbasedon4'lengthlamps.3Ballastcodesignif iesuseofasingle1lampballastina2lampfixture,asingle1lampballastanda2lampballastina3lampfixtureandtwo2lampballastsina4lampfixture.

Voltage Ballast 120=120V 277=277V UNV=120-277V

ExampleExample of voltage and ballast code fields to be populated within fixture specif ication sheet.

Twin tube T5 ballast code options22 ½" Long

Page 224: Linear recessed and surface lighting

Linear recessed and surface lighting

4.221Comprehensive lighting catalog 7th Edition

Ballastcodeoptions

T8 ballast code options2', 3' and 4' lengths

Ballast code Ballast lamp capacity Type Ballast factor2 THD Voltage Ballast designation

A3 1 - 3 Lamp Program Rapid Start 0.71 <10% UNV Advance Electronic Optanium Low Watt

A4 1 - 4 Lamp Program Rapid Start 0.71 <10% UNV Advance Electronic Optanium Low Watt

A53 1 or 2 Lamp Instant start 0.77 <10% UNV Advance Electronic Optanium IOPA Low Watt

A6 1 - 3 Lamp Instant start 0.77 <10% UNV Advance Electronic Optanium IOPA Low Watt

A7 1 - 4 Lamp Instant start 0.77 <10% UNV Advance Electronic Optanium IOPA Low Watt

C23 1 or 2 Lamp Instant start 0.87 <10% UNV Advance Electronic Optanium

C3 1 - 3 Lamp Instant start 0.87 <10% UNV Advance Electronic Optanium

C4 1 - 4 Lamp Instant start 0.87 <10% UNV Advance Electronic Optanium

C53 1 or 2 Lamp Instant start 0.77 <10% UNV Advance Electronic Optanium Low Watt

C6 1 - 3 Lamp Instant start 0.77 <10% UNV Advance Electronic Optanium Low Watt

C7 1 - 4 Lamp Instant start 0.77 <10% UNV Advance Electronic Optanium Low Watt

C8 1 - 3 Lamp Program Rapid Start 0.88 <10% UNV Advance Electronic Optanium

C9 1 - 4 Lamp Program Rapid Start 0.88 <10% UNV Advance Electronic Optanium

CA3 1 or 2 Lamp Instant start 0.88 <10% UNV Advance Electronic Centium

CG 1 or 2 Lamp Program Rapid Start 0.88 <10% UNV Advance Electronic Optanium

CI 1 - 3 Lamp Instant start 0.88 <10% UNV Advance Electronic Centium

CJ 1 - 4 Lamp Instant start 0.88 <10% UNV Advance Electronic Centium

CK3 1 or 2 Lamp Program Rapid Start 0.71 <10% UNV Advance Electronic Optanium Low Watt

CO3 1 or 2 Lamp Instant start 1.18 <10% UNV Advance Electronic Optanium High Lite Output

H3 1 - 3 Lamp Instant start 0.88 <10% UNV Generic Electronic1

H4 1 - 4 Lamp Instant start 0.88 <10% UNV Generic Electronic1

H5 1 - 2 Lamp & 1 - 4 Lamp Instant start 0.88 <10% UNV Generic Electronic1

H6 2 - 3 Lamp Instant start 0.88 <10% UNV Generic Electronic1

HI3 1 or 2 Lamp Instant start 0.88 <10% UNV Generic Electronic1

L3 1 - 3 Lamp Instant start 0.77 <10% UNV Generic Electronic1 Low Watt

L4 1 - 4 Lamp Instant start 0.77 <10% UNV Generic Electronic1 Low Watt

LW3 1 or 2 Lamp Instant start 0.77 <10% UNV Generic Electronic1 Low Watt

M4 1-4Lamp(No17W) Program start 0.88 <10% UNV AdvanceElectronicMarkVIIDimming

M73 1 or 2 Lamp Program start 1.00 <10% UNV AdvanceElectronicMarkVIIDimming

M8 1 - 3 Lamp Program start 0.88 <10% UNV AdvanceElectronicMarkVIIDimming

MY 1 - 3 Lamp Program start 1.02 <10% 120 or 277 AdvanceElectronicMarkXDimming

P23 1 or 2 Lamp Program start 0.88 <10% UNV Generic Electronic1

P3 1 - 3 Lamp Program start 0.88 <10% UNV Generic Electronic1

P4 1 - 4 Lamp Program start 0.88 <10% UNV Generic Electronic1

PS3 1 or 2 Lamp Program start 0.98 <10% UNV Philips Lightolier Electronic Dimming

PW 1 - 3 Lamp Program start 0.98 <10% UNV Philips Lightolier Electronic Dimming

PX 1 - 4 Lamp Program start 0.98 <10% UNV Philips Lightolier Electronic Dimming

V23 1 or 2 Lamp Program Rapid Start 0.95 <10% UNV Generic Electronic Step Dimming1

1Genericelectronicballast(Advance,Sylvania,Universal,UltraSaveorGE)chosenbyfactorybasedonavailability.2Ballastfactorbasedon4'lengthlamps.3Ballastcodesignif iesuseofasingle1lampballastina2lampfixture,asingle1lampballastanda2lampballastina3lampfixtureandtwo2lampballastsina4lampfixture.

Voltage Ballast 120=120V 277=277V UNV=120-277V

ExampleExample of voltage and ballast code fields to be populated within fixture specif ication sheet.

Page 225: Linear recessed and surface lighting

Linear recessed and surface lighting

4.222 Philips Lightolier For complete specif ication information visit www.lightolier.com

Ballastcodeoptions

Deepcel 2' x 4' size

All performance data on the 2' x 4' luminaire is based onamaintainedroomtemperatureof75°F(24°C).Airperformance tests were conducted in accordance with AirDiffusionCouncil(ADC)airdiffusingtrofferheatremoval test code TC-66.

HEAT TRANSFER, ENERGY DISTRIBUTION, THREE LAMPS – FOUR LAMPS

NEGATIVESTATICPRESSURE(IN.OFH2O)

COMBINATION RETURN AIR/HEAT REMOVAL

1.Input,BTUH2.Heatremoved;BTUH3.Heattospace;BTUH

Ballast code Ballast lamp capacity Type Ballast factor THD Voltage Ballast designation

AY 2 Lamp Program start 0.95 <10% UNV AdvanceElectronicOptaniumStepDimming(28WattOnly)

CT3 1 or 2 Lamp Program start 1.00 - 1.032 <10% UNV AdvanceElectronicCentiumIntelliVolt

CY 1 - 3 Lamp Program Rapid Start 1.00 <10% UNV AdvanceElectronicCentiumIntelliVolt(54WattOnly)

CZ 1 - 4 Lamp Program Rapid Start 0.90 <10% UNV AdvanceElectronicCentiumIntelliVolt(54WattOnly)

MW3 1 or 2 Lamp Program start 1.00 / 0.03 <10% 120 or 277 AdvanceElectronicMarkVIIDimming(54WattOnly)

MZ3 1 or 2 Lamp Program start 1.00 / 0.052 <10% 120 or 277 AdvanceElectronicMarkXDimming(24or54WattOnly)

P5 1 - 3 Lamp Program start 1.00 <10% UNV Generic Electronic190°C(54WattOnly)

P93 1 or 2 Lamp Program start 1.00 <10% UNV Generic Electronic190°C(54WattOnly)

PF3 1 or 2 Lamp Program start 1.00 - 1.052 <10% UNV Philips Lightolier Electronic Dimming

PG3 1 or 2 Lamp Program start 1.00 - 1.052 <10% UNV Generic Electronic1

PU 1 - 3 Lamp Program start 1.00 <10% UNV Generic Electronic1(54WattOnly)

PV 1 - 4 Lamp Program start 1.00 <10% UNV Generic Electronic190°C(54WattOnly)

VY 2 lamp Program Rapid Start 0.95 <10% UNV Generic Electronic Step Dimming1(14or28WattOnly)

VZ 1 or 2 Lamp Program Rapid Start 1.15 <10% UNV Generic Electronic Step Dimming1(14or28WattOnly)

WA3 1 or 2 Lamp Instant start 0.93 <10% 120 or 277 Generic Electronic1(28WattOnly)

WW3 1 or 2 Lamp Program start 0.95 <10% UNV Generic Electronic1(28WattOnly)

WX3 1 or 2 Lamp Program start 1.15 <10% UNV Generic Electronic1(28WattOnly)

1Genericelectronicballast(Advance,Sylvania,Universal,UltraSaveorGE)chosenbyfactorybasedonavailability.2Ballastfactorbasedon4'lengthlamps.3Ballastcodesignif iesuseofasingle1lampballastina2lampfixture,asingle1lampballastanda2lampballastina3lampfixtureandtwo2lampballastsina4lampfixture.

Voltage Ballast 120=120V 277=277V UNV=120-277V

ExampleExample of voltage and ballast code fields to be populated within fixture specif ication sheet.

T5 ballast code options2', 3' and 4' lengths

Air handling dataAir return/heat transfer data for Deepcel

Page 226: Linear recessed and surface lighting

Linear recessed and surface lighting

4.223Comprehensive lighting catalog 7th Edition

NEGATIVESTATICPRESSURE(IN.OFH2O)

*Lytecel6"x48" Air return InformationIs only the Air return through the side slot. (Noheattransferdatatoright)

Deepcel 2' x 2' size

VR1'x4'size

All performance data on the 1' x 4' luminaire is based on a maintained roomtemperatureof75°F(24°C).Airperformance tests were conducted in accordance with Air Diffusion Council (ADC)airdiffusingtrofferheatremovaltest code TC-66.

All performance data on the 2' x 2' luminaire is based on a maintained roomtemperatureof75°F(24°C).Airperformance tests were conducted in accordance with Air Diffusion Council (ADC)airdiffusingtrofferheatremovaltest code TC-66.

Air return through side slots

Heat transfer, energy distribution, two lamps

Heat transfer, energy distribution, two F40 lamps

Heat transfer, energy distribution, two lamps

NEGATIVESTATICPRESSURE(IN.OFH2O)

1.Input,BTUH2.Heatremoved;BTUH3.Heattospace;BTUH

1.Input,BTUH2.Heatremoved;BTUH3.Heattospace;BTUH

Air handling dataAir return/heat transfer data for VR

Air handling dataAir return/heat transfer data for Deepcel & Lytecel

Page 227: Linear recessed and surface lighting

Linear recessed and surface lighting

4.224 Philips Lightolier For complete specif ication information visit www.lightolier.com

Air handling dataAir return/heat transfer data for Prismalyte Plus

2' x 4' size 2' x 4' & 2' x 2' size

2' x 2' size

All performance data on the 2' x 2' luminaire is based onamaintainedroomtemperatureof75°F(24°C).Airperformance tests were conducted in accordance with Air DiffusionCouncil(ADC)airdiffusingtrofferheatremovaltest code TC-66.

All performance data on the 1' x 4' luminaire is based onamaintainedroomtemperatureof75°F(24°C).Airperformance tests were conducted in accordance with Air DiffusionCouncil(ADC)airdiffusingtrofferheatremovaltest code TC-66.

All performance data on the 2' x 4' luminaire is based on a maintainedroomtemperatureof75°F(24°C).Airperformancetests were conducted in accordance with Air Diffusion Council (ADC)airdiffusingtrofferheatremovaltestcodeTC-66.

1' x 4' size

1.Input,BTUH2.Heatremoved;BTUH3.Heattospace;BTUH

Page 228: Linear recessed and surface lighting

Linear recessed and surface lighting

4.225Comprehensive lighting catalog 7th Edition

Air handling dataAir return/heat transfer data for Paraplus and Coffaire

2' x 4' size 2' x 2' size

CFM Through Lamp Compartment0 10 20 30 40 50 60

Stat

ic Pr

essu

re-In

. Wg.

20° Plenum to space two 54W T5HO lamps

1. Input:BTUH.2.Totaltoplenum:BTUH3.RemovedinexhaustBTUH.

1

3

2

1' x 4' size

500

400

300

200

100

0

-100

-200

Paraplus ParaplusCoffaire Coffaire

CFM Through Lamp Compartment0 10 20 30 40 50 60

Stat

ic Pr

essu

re-In

. Wg.

20° Plenum to space two 54W T5HO Lamps

1. Input:BTUH.2.Totaltoplenum:BTUH3.RemovedinexhaustBTUH.

1

2

3

500

400

300

200

100

0

-100

-20010 20 30 40 50 70 100 150 200 250

Pressure drop tested in accor-dance with ADC 1062R2

Stat

ic Pr

essu

re-In

. Wg. 1. Return air through 20 heat

slots1/2"wideeachinsidelamp compartment.

ReturnAirFlow(CFM)

.100

.010

.00110 20 30 40 50 70 100

Pressure drop tested in accordance with ADC 1062R2

Stat

ic Pr

essu

re-In

. Wg. 1. Return air

through 8 heat slots1/2"wideeach inside lamp compartment.

ReturnAirFlow(CFM)

.100

.010

.001

Air performance tests on the 1' x 4' luminaire were conducted with procedure described in I.E.S. Journal, Summer1987,Vol.16,No.2,Pages21-31byBuildingAcousticsLightingLaboratories, Inc.

CFM Through Lamp Compartment0 10 20 30 40 50 60

Stat

ic Pr

essu

re-In

. Wg.

20° Plenum to space two 54W T5HO lamps

1. Input:BTUH.2.Totaltoplenum:BTUH3.RemovedinexhaustBTUH.

500

400

300

200

100

0

-100

-20010 20 30 40 50 70 100 150 200 250

Pressure drop tested in accordance with ADC 1062R2

Stat

ic Pr

essu

re-In

. Wg. 1. Return air through 20 heat

slots1/2"wideeachinsidelamp compartment.

ReturnAirFlow(CFM)

.100

.010

.001

Air performance tests on the 2' x 4' luminaire were conducted with procedure described in I.E.S. Journal, Summer1987,Vol.16,No.2,Pages21-31byBuildingAcousticsLightingLaboratories, Inc.

Air performance tests on the 2' x 2' luminaire were conducted with procedure described in I.E.S. Journal, Summer1987,Vol.16,No.2,Pages21-31byBuildingAcousticsLightingLaboratories, Inc.

Paraplus Coffaire

Paraplus and Coffaire with air return meets the requirements of UL 1598, Paragraph 9.2.2.5, Large scale fallout tested in accordance with the fire test described in Paragraph9.2.3.2.2.,andisUL(UnderwritersLaboratories)listedunderFileR5892,Vol.1,Section4,dated11/16/2001.


Recommended