LIST 1) Chief Engineer (LD), MSETCL, Kalwa.Fax-27601769/65 2) Chief Engr. (Trans O&M), MSETCL, Bandra. Fax No. 022 26598587. 3) S.E. (T&C), MSETCL, Aurangabad Fax-0240-2234220 /2346290 4) S.E (T&C), MSETCL, Pune. Fax-9520-2617532/2612342 5) S.E. (T&C), MSETCL, Nagpur. Fax-95712-2234220 6) S.E.(T&C), MSETCL, Nasik Road Fax-0253-2462422 7) S.E.(T&C), MSETCL, Vashi Fax--022-27662055 8) S.E.(Gen.Tstg), MSPGCL,Eklahre, Nasik Fax-95253-2810496/2810499 9) S.E. (Task Force), MSPGCL, Nagpur Fax- 0712-2591717. 10) Chief Engineer (Gen), GSECL, H.O. Baroda. Fax-0265-5512129/2344537 11) Addl. C.E.(Testing), GETCO, Baroda. Fax-0265-2351218 12) Chief Engineer(LD), MPPTCL, Jabalpur. Fax-0761- 2664343 /2282632. 13) E.D. (T&C),MPPTCL, Jabalpur. Fax-0761-2661696 14) Addl.C.E., MPPGCL, Jabalpur Fax- 0761-2660063/2665805 15) E.E. (SLDC), MPPTCL, Indore Fax-0731-2874515 16) Chief Engineer (LD), CSPTCL, Bhilai. Fax-0788-2282632/0788-383633 17) C.E. (T&C), CSEB, Raipur.Fax-0771-4066988/07759-226227 18) EE (T) , CSPGCL- Fax.No. 07789-226227 19) S.E.(T&C), CSPTCL, Bhilai. Fax.No.- 20) S.E.(T&C), CSPTCL, Raipur. Fax No.0771-4066988. 21) E.E.(T&C), CSPTCL, Bhilai. Fax No. -0788 2281561 22) EE, Division VIII(MRT),Elect. Dept; Goa Fax 0832-2735124. 23) Supdt.Engr., Electricity Dept., DNH, Silvasa. Fax : 0260-2642338 24) Executive Engr., Electricity Dept. DD. Fax : 0260-2250889 25) D.G.M.(O.S. ),N.T.P.C., Mumbai, Fax- 28216692 26) D.G.M.(EM), KSTPS,NTPC,KorbaFax 07759-233088/ 232440 27) DGM (EMD), VSTPS, NTPC, Vindhyachal Fax-07805-247713 28) DGM (EM-I),NTPC, SIPAT Fax-07752-246506/246691. 29) AGM(O&M), KGPP,Adityanagar, Surat Fax 0261-2861428/2861433 30) Sr.Supdt. (EM),Gandhar, NTPC Fax-02642-87402 / 87450 31) DGM (O.S.), WRLDC, Mumbai Fax-28235434 32) DGM, WRTS-I POWERGRID,Nagpur.Fax-95712-641366/2641496 33) Addl General Manager, WRTS-II,POWERGRID,Baroda Fax-0265-2480952 34) SME (E), TAPS-3&4,Tarapur Fax 02525-282001/282073 35) Maintenance Superintendant,TAPS –1 & 2,Tarapur.Fax- 02525-282121 36) SME(E), NPCIL ,Kakrapara Fax 02626-234266 37) GM(Maint.). T.Power., Ahmedabad.Fax-079-27506679 38) AGM (ET&A),TPC, Trombay. Fax –022-66687088 39) Dy.Gen. Manager,Dahanu TPS Fax- 952528-222576 40) Vice President, Reliance Energy, Mumbai Fax-30094488 41) GM (Electrical), JPL, Raigarh. Fax.No.7767-281995,281993. 42) Director (G M Division), CEA, New Delhi. Fax.No.011-26109750 43) AGM(OS), NSPCL, New Delhi . Fax.No.011 26717363/26717366 44) GM, KSK Mahanadi Power Co Ltd., Hyderabad- Fax.No.04023559930 45) Director (Tech & Projects), JSW Energy( Ratnagiri) Ltd., Fax.No. 022 67848393 46) GM, RGPPL,Anjanwel,Guhagar,Ratnagiri. Fax.No. 02359 241071
1 Minutes of 115th Protection Committee of WRPC
MINUTE OF 115th PROTECTION COMMITTEE MEETING OF WRPC HELD ON
6/7.09.2012 AT PUNE
The 115th Protection Committee Meeting of WRPC was held on 6/7.09.2012 at Pune. The list
of participants is placed at Annexure -I.
Shri A. V. Kolap, S.E.TR.(O&M), MSETCL, Pune welcomed all the members and
participants attending the meeting. Shri S. G. Kelkar, ED(Opn), MSETCL welcomed all the
members and participants and highlighted the progress of MSETCL at glance.
Shri S. D. Taksande, Member Secretary (I/C), WRPC, welcomed all the members and the
participants of the 115th Protection sub-Committee Meeting. He stated that todays meeting in
past 30th & 31st July occurrence. A committee headed by Chairperson CEA studied the
occurrences and submitted its report covering recommendations having a special time line.
Many recommendations are protection related and therefore implementation of these
recommendation in the time bound manner is the responsibility of PCM group. Also
Chairman WRPC & CMD MSETCL during the meeting held at WRPC Mumbai on 7th
Aug.2012 formulated a group consisting of Shri U.G.Zalte Chairman TCC & Dir(O)
MSETCL, Shri S D Taksande MS WRPC, & Shri P Pentayya GM WRLDC to review
defence mechanism , RGMO facility, Black start facility and communication facility in WR
so that W Region remain safe during any eventualities. In this regard special meeting was
arranged on 07.09.2012 at same venue. He requested all the participants to actively
participate in discussions.
He also informed that a presentation by CPRI B,lore on protection audit has been
arranged during the course of meeting. He thanked MSETCL for making nice arrangements
for stay and transport of the participants.
Member Secretary (I/C) then requested Shri M. M. Dhakate, SE(Protection), WRPC to take
the agenda items for discussion in seriatim.
The agenda Items were taken up for discussions.
ITEM NO.1: CONFIRMATION OF MINUTES OF 114TH PROTECTION
COMMITTEE MEETING.
SE(Protection), WRPC stated that the minutes of 114th PCM, held on 11/12.06.2012 at
WRPC Mumbai, were circulated vide WRPC letter No. Prot./114 PCM/2012/WRPC-6410
2 Minutes of 115th Protection Committee of WRPC
dated 27th June 2012 and following correction/observations have been received :
1. Rinfra vide email dated 26.07.2012 have requested to add following sentence in
ITEM NO. 6.3 : Revised islanding scheme in R-infra Mumbai transmission network
of 114th PCM :
“Committee has opined that R-Infra can proceed in implementing the Revised
Scheme as presented during the meeting.”
2. Item No. 2.4(ii) Multiple tripping of 400 KV lines at 400 kV JSWEL, Jaigad
(Ratnagiri) sub-station on 17.03.2011: It is noted and confirmed by WRLDC/JSWEL
that these trippings were occurred on 17.03.2012.
Members agreed for above modification/corrections.
The minutes of 114th Protection Committee were confirmed with above modifications.
ITEM NO.2: SYSTEM DISTURBANCES
2.1: System disturbances in CSPTCL/CSPGCL system.
2.1 (i) Occurrence at Korba East (Extn) (DSPM) Station on 1.05.2012
CSPGCL representative explained the disturbance as below:
At 10:34 Hrs on 1.05.2012, cascaded tripping of following lines, ICTs and generators
occured :
Kotmikala-Amarkantak-1 Ph to Ph fault, DPR operated
Kotmikala-Amarkantak-2 Over current
400/220 kV ICT at Korba(W) R & Y phase Overcurrent
Korba(E) Unit-3,4,5 (50 MW each) Overspeed/turbine trip
BALCO Unit-1 &2 Over frequency
DSPM unit-1 & 2(250 & 210 MW) Gen. elect. & reheater protection
220 kV Korba(E)-Mopka B-G fault, DPR operated
220 kV BALCO-Korba(E)-1&2 Alongwith generators at BALCO
220 kV DSPM-Banari S/c and 220 kV DSPM-Suhela S/c were already out of service due to
falling of tower. Also, 220 kV Korba(E)-Raigarh, 220 kV Korba(E)-Budhipadar-II & III
3 Minutes of 115th Protection Committee of WRPC
were kept out to control overloading on 220 kV DSPM-Korba(E) S/c.
Approximately, 940 MW loss of generation without any load loss has been reported.
In the 114th PCM during discussion on Item No. 2.1(i) : System disturbance at 400 kV Korba
system in CSPTCL system on 19-04-11, Committee recommended that in the absence of
SPS, the over current setting of the lines in the area can be raised to 150% so that sufficient
time margin would be available to take corrective actions in the event of loss of line in the
area thereby avoiding overloading the other lines by cutting-off the load or backing down the
generation. Committee further suggested that WRLDC would device SPS in consultation
with CSPGCL/CSPTCL on urgent basis.
WRLDC intimated that SPS is very much essential in Korba area, since the area is generation
hub (with evacuation mostly on 220kV system) and the transmission system is fragile around
Korba area. Tripping/planned outages of the two to three 220kV transmission elements in
this corridor causes overloading and tripping of other elements in this corridor leading to
further depletion of the transmission corridor as in the above incidence. Proper line outage
coordination is also required for avoiding such incidence till the SPS is put in place.
Committee opined that the recommendation of 114th PCM as mentioned above may be
implemented at the earliest. It is also felt that inview of complex network in
Chhattisgarh , a small group could be formed to finalize the SPS scheme and be put up
to PCM.
2.1 (ii) Occurrence at Sipat on 15.06.12 and 19.06.12
NTPC representative explained the occurrence as below :
On 15.06.2012 and 19.06.2012 at NTPC Sipat there was a grid disturbance resulting in a total loss of
generation of the order of 2100-2300 MW at Sipat.
A group comprising of representatives from WRPC, WRLDC, POWERGRID and NTPC met at
NTPC-Sipat on 29.06.2012 to analyze the events that led to the disturbance and suggest remedial
measures to prevent recurrence of the same. A report analyzing the grid disturbance at Sipat STPS on
15.06.2012 and 19.06.2012 is available on WRPC website.
Brief descriptions of occurrences as explained by NTPC Sipat representative is given below:
Incident on 15.06.2012 at NTPC Sipat:
4 Minutes of 115th Protection Committee of WRPC
On 15.06.2012 at 1832 hrs at NTPC-Sipat units # 1,2,4,5 were on bar generating 2347MW. At
18:34:51 hrs B Phase of 400kV tie CT of IBT1 (400/132 kV) to ICT1 (765/400 kV) at Bay 14 at
NTPC Sipat burst and led to the tripping of IBT1 and ICT1 on Tee Differential protection. During the
explosion one broken insulator piece flew and damaged moose conductor clamp of LA of
IBT2(400/132 kV). This caused the conductor to snap and resulted in tripping of IBT2 on transformer
differential protection at 18:34:53hrs.
The Explosion of B phase CT of 14CT-B and splashing of hot oil caused following damages:
a. B phase CT of 14CT-B failed and completely damaged.
b. R & Y phase CT of 14CT-B and Y Phase CT of 14CT-A insulator got damaged.
c. 7 nos. Isolator stacks of Bay 13, 14 & 15 got damaged.
d. B-phase Circuit Breaker pole of 1452 breaker damaged beyond repair.
e. 1 no. IPS to twin Moose connector damaged in R-phase of IBT-2.
Approx. 20 meters of length of all 240 nos of control and power cables running in the main trench in
the vicinity of failed CT caught fire due to spillage of oil from CT and got damaged. These damaged
cables pertain to bay No 13 (IBT #1 main bay), 14 IBT#1 & ICT # 1 tie bay), 15 (ICT # 1 main bay),
16 (Raipur # 2 main bay), 17 Raipur # 2 and Ranchi # 1 tie bay) & 18 (Ranchi #1 main bay).
The tripping of the IBTs resulted in loss of station auxiliaries supply and the running units at Sipat
tripped as follows:
1) The Unit 2 tripped on low vacuum at 1836 hrs.
2) Unit 1 tripped at 1853 hrs, unit 4 at 1900 hrs and unit 5 at 1933 hrs.
The generation loss was around 2347 MW. The NTPC Sipat Engineers and staff quickly acted and
controlled the fire. Due to the above disturbance 400 kV Sipat-Raipur ckt 2 tripped at 18:40:44 hrs
and 400 kV Sipat-Ranchi tripped at 18:37:33 hrs. Further the tripping also led to high voltage in 765
kV and 400 kV networks and following elements tripped on High voltage.
1) 765 kV Seoni-Wardha 2 at 1900 hrs
2) 400 kV Seoni-Bhilai at 1853 hrs
3) 400 kV Seoni-Khandwa 1 at 1853 hrs
4) 400 kV Seoni-Bina at 1853 hrs
5) 400 kV Seoni-Khandwa 2 at 1900 hrs
6) 400 kV Seoni-Satpura at 1900 hrs
7) 765 kV Seoni-Bilaspur 1 at 1910 hrs
Restoration activities were taken up by Sipat and on 16.06.2012 by 1200 hrs around 2000 MW
generation was on bar. The ICT2(765/400 kV) and IBT2(400/132 kV) were charged. ICT1 and IBT1
5 Minutes of 115th Protection Committee of WRPC
remained out. While cable restoration work was in progress, another incident took place on
19.06.2012.
Incident on 19.06.2012 at NTPC Sipat:
On 19.06.2012 at 1615 hrs at NTPC-Sipat units # 1,2,3,4,5 were on bar generating 2150MW. At
16.16 Hrs on 19.06.2012 IBT-2 got tripped, which was the only source in service for 132KV
switchyard and in turn all station transformers got dead. On inspection it was found that LBB of 1552
(IBT-1) breaker operated leading to actuation of Bus Bar protection of 400 KV Bus-1. 400Kv Bus-1
became dead. All Bus #1 breaker 952, 1252, 2052 and 2452 got tripped. 400KV Bus-II was live
through Raipur # 1, Ranchi #2 and ICT#2. As IBT # 2 was charged from Bus#1 Main CB 1252 and its
dia i.e bay 10 & 11 were not commissioned, tripping of Bus #1 caused tripping of IBT #2.
This caused tripping of all running units at Sipat as follows:
Unit -2 at Sipat tripped immediately followed by tripping of unit-5 at 1623 hrs, unit- 4 at
1643 hrs and finally unit-1 at 1651 hrs. The generation loss was around 2150 MW and
resulted in high voltages in 765 and 400 kV networks.
Following lines tripped on high voltages.
1) 765 kV Sipat-Bilaspur 2 at 1653 hrs
2) 765 kV Seoni-Wardha 1 at 1653 hrs
3) 400 kV Raipur-Sipat 1 at 1653 hrs
4) 400 kV Seoni-Bina s/c at 1653 hrs
5) 400 kV Sipat-Ranchi 2 at 1653 hrs
6) 400 kV Bhilai-Seoni s/c at 1653 hrs
7) 400 kV Khandwa – Seoni 1 at 1653 hrs
8) 400 kV Seoni-Satpura at 1653 hrs
9) 400 kV Khandwa-Seoni 2 at 1653 hrs
There was no significant change in frequency due to incoming wind generation at that time. By 0230
hrs of 20.06.2012 all units at Sipat were synchronized.
The group recommended as following :
1) To explore the possibility of additional standby supply for auxiliaries from nearby 132 kV
system
2) The findings ( root cause analysis report of R & Y phase CTs by Areva).
3) New arrangement of sharing of shifting of loads between station and UATs
6 Minutes of 115th Protection Committee of WRPC
4) Procurement and replacement of the cables
Wrt recommendation No. 1 as above NTPC representative intimated that the matter is taken up with
Corporate office for providing 132 kV standby supply for auxiliaries as normally 33 kV standby
supply is provided.
Wrt recommendation No. 2 as above NTPC representative intimated that M/s Areva could not come
to any conclusion since the failed CT was completely damaged.DGA of 11CTs were done after the
incidence and six CTs which are Areva 2005 make and showing DGA violation were replaced. The
same will be taken back by M/s Areva for further checking and report is awaited. He further intimated
that tan delta of all 95 CTs have been carried out and the results are in order.
It was opined that the DGA oil samples in case of hermetically sealed CTs is a concern and the
frequency of carrying out the DGA analysis has to be restricted.
ED(O), MSETCL intimated that the CTs can easily be tested for tan delta, but even after showing
normal results, CTs including new CTs tend to fail. Hence DGA analysis is the only test to ascertain
the healthiness of the CTs
Wrt recommendation No. 3 as above NTPC representative intimated that
• IBT-2 Tie bay (Bay 10, 11) made ready and charged.
• Compressors control supply changed from Station board to Unit board in stage 1&2.
• Stage-2 compressor cooling water pump supply changed from station board to unit board.
• Replacement of 400KV damaged equipments completed.
• Repairing of damaged cables by 29.06.2012.
• Charging of all feeders by 11.07.2012.
Wrt recommendation No. 4 as above NTPC representative intimated that procurement and
replacement of cables is going on in opportunity outages.
Committee members discussed the matter and some additional recommendations were
suggested as below :
• The S/S layout should be such that the physical location of CT and cable trench
be at a distance to avoid fire in case of CT Bursting.
• FRS coating (even though costly) should be applied on entire length of control
7 Minutes of 115th Protection Committee of WRPC
cables so as to avoid propagation of fire and avoiding short circuiting of the
cable due to fire.
• Drain point leakage is required to be avoided.
• DGA analysis of all CTs to be done every three years.
• As new CTs are also failing and State agencies needs to procure any equipment
as per lowest bids. The procurement of inferior CTs can be avoided if stringent
specifications are given at the time of tendering. The specifications may be
firmed up/shared amongst the utilities.
2.2: System disturbances in GETCO/GSECL system.
2.2(i) Occurrence at Sachin S/s in Gujarat on 27.03.2012
GETCO representative explained the occurrence as follows:
At 00:05 hrs on 27.03.12 due to flashover of B-Phase PT of 220 kV Bus-B, bus fault
occurred leading to tripping of all feeders and ICTs at Sachin S/S on operation of Bus Bar
protection.
220 kV Sachin S/s is having double main and transfer bus switching scheme. The bus-
coupler was under planned shutdown for replacement of B-phase CT of 220 kV Bus-A.
GETCO representative further stated that the two bus arrangement was converted to single
bus arrangement through isolator, since the Bus Coupler was under outage.
Load loss of 204 MW was reported due to above without any generation loss.
Committee felt that Bus Bar operated correctly but healthiness of PT should be
monitored regularly.
2.2(ii) Occurrence at Kim S/s in Gujarat on 27.03.2012
At 14:15 hrs on 27.03.2012 GSEG-Mora-Kim and GSEG-Kim which were evacuation lines
for GSEG tripped on Y –phase distance protection. GSEG GT-1(52 MW) and GSEG
STG(52.1 MW) tripped due to loss of evacuation lines. Gujarat has reported that on
patrolling sugar cane wastes were found burnt below the locations 91 & 92. (distance 17.7
Km from Kim).
8 Minutes of 115th Protection Committee of WRPC
Committee felt that the tripping was in order. For the fault however more awareness
may be spread among farmers.
2.2(iii) Occurrence at Kakrapar APS on 4.05.2012
Rrepresentative from KAPS explained the occurrence as below:
On 4.05.2012 at 17:50 Hrs CB of Kakrapar-Haldarwa-2 at KAPS end tripped on pole
discrepancy protection with C10x relay flag while normalizing the line. NPCIL have
intimated that on investigation ‘B’ pole closing circuit anti pumping relay NC contact found
resistive. The same was attended through spare contact of anti pumping relay (52 yC) and
closing loop made healthy.
Committee felt that the tripping was in order.
2.2(iv) Occurrence at Nakhatrana S/s on 27.05.2012
Rrepresentative from GETCO explained the occurrence as below:
At 10:50 hrs on 25.05.2012 backup protection operated at 220 kV Nakhatrana-Nanikhakhar-
II leading to tripping of KLTPS and ALTPS units and subsequently Nakhatrana s/s
experienced zero power. Planned shutdown of 220kV Nakhatrana-Nanikhakhar-I was
availed at 25.05.2012 for earth wire replacement work. Panandro –Kukma-II was under
outage due to permanent fault from 24.05.12 for repairing broken conductor. Due to heavy
loading on Panandro –Kukma-I and heavy wind in reverse direction, the induction effect
made it very difficult and dangerous to work on Panandro –Kukma-II and hence Panandro –
Kukma-I was switched off at 10:50 hrs to enable to carry out work on Panandro –Kukma-II.
This led to tripping of Nakhatrana-Nanikhakhar-II on back up protection due to overload and
other lines also tripping of KLTPS unit 1 & 2(unit 3 &4 were under forced shutdown) and
ALTPS unit 1(unit-2 was under forced shutdown) due to lack of evacuation.
Committee discussed the matter and concluded that this incidence could have been
averted if proper outage coordination had been there.
9 Minutes of 115th Protection Committee of WRPC
2.2(v) Occurrence at Ichhapore S/s on 2.06.2012
Rrepresentative from GETCO explained the occurrence as below:
220 kV Kawas-Haldarwa-I & II lines were switched off for controlling line loading of 220
kV Kawas-Ichhapore line. Also, planned shutdown for 220 kV Navsari-Sachin line was
availed on 2.06.12. Load on Essar complex (200 MW), Sachin S/s(200 MW),
Ichhapore(70MW) was catered by 3 lines namely 220 kV Kawas-Ichhapore, 220 kV Vav-
Ichhapore and 220 kV Vav-Sachin. At 16:15 hrs on 2.06.2012 a direct trip command from
Kawas end received during PLCC testing carried out at Kawas 220 kV Kawas-Ichhapore
line. Tripping of Kawas-Ichhapore line led to overloading of 220kV other two lines and
eventually tripped on over current protection causing zero power at Ichhapore and Sachin s/s.
Load loss of 47 MW was reported during above incidence.
It was opined that there is plug system which has to be removed if any PLCC testing is to be
carried out for avoiding extension of direct trip command. The test plug might not have been
removed while carrying out the above test. GETCO representative stated that plug system is
available at Kawas end and same was not removed due to human error.
Committee felt that checklist for testing should be well documented and available at
each substation.
2.3: System disturbances in MPPTCL/MPPGCL system.
2.3(i) Occurrence at 220 kV Jabalpur S/S and Bargi HPS on 27.05.2012.
MPPTCL representative explained the occurrence as below :
On 27.05.2012 at around 21:45 hrs 132 kV B-Phase CT of bus-coupler bay at Bargi HPS got
burst which caused bus fault at Bargi. Bargi line -1 at Jabalpur tripped on zone -2 but due to
delayed opening of 132 kV breaker of Bargi-Jabalpur-II at 220 kV Jabalpur s/s, its “B”
phase pole got burst and created bus fault on 132 kV bus resulting into tripping three
transformers(220/132 kV) and all outgoing feeders from remote end including 45 MW Unit-
1. There was load loss of around 260 MW and generation loss at Bargi HPS at 31 MW.
Relay indications at Jabalpur 220 kV Jabalpur s/s - 132KV Bargi 1 – ABC G- Z2
10 Minutes of 115th Protection Committee of WRPC
132KV Bargi 2- C-N, Z3 3x40 MVA MTSB- DTOC-2 Trip both side 3x40MVA BHEL DTOC-2 Trip both side 1x160 MVA GEC- E/F 132 kV Marhotal s/s -Jabalpur - C ph. Z2, At 132 Narsinghpur S/s - On Shrinagar line- Forward Power Relay operated. MPPTCL representative intimated that the breaker was 23 year old BHEL make and failed
breaker was replaced on 31.05.12 with ABB make SF6 CB. He further intimated that SHPM
Quadramho Relay of 132 Bargi 2 feeder at Jabalpur Replaced on 16.06.12.
Committee felt that the tripping was in order. It was also felt that replacement of any
electrical equipment solely on age could not be recommended. The overall history of
equipment is to be considered before any replacement.
2.3(ii) Occurence at Satpura S/s on 5.04.2012
MPPGCL represtnative explained the occurrence as below :
On 5.04.2012 at 00:30 hrs at Satpura TPS, 220 kV main Bus-I PT ‘B’ phase (SCT make) got
burst. Consequently busbar differential zone-I(R&B) phase and zone –II(R phase) operated
resulting into tripping of all lines and generators connected on Bus-I and Bus-II. Generation
loss of 470 MW has been reported. In the instant incident “B” phase P.T. of Bus-I failed
very badly due to internal problem in PT and burst into pieces causing heavy splash of oil in
the surrounding area.
To avoid such recurrence the location of existing PTs of 220 kV Bus-I have been shifted.
The failed “B” phase P.T. was replaced with available SCT make P.T. in order to normalize/
charge 220KV Bus-I. However, these SCT make P.T.s are proposed to be replaced with
BHEL make P.Ts ordered recently by the site.
MPPGCL representative intimated that Westinghouse PTs which served for over 50 years
were replaced with SCT make PTs which are bursting quite often. Also, busbar protection
(Asia RADSS) again operated on 5.9.12 for which the detail report is not unavailable right
now.
MPPGCL was requested to submit the report.
Committee felt that the tripping was in order. It was also felt that replacement of any
11 Minutes of 115th Protection Committee of WRPC
electrical equipment solely on age could not be recommended. The overall history of
equipment is to be considered before any replacement.
2.3(iii) Occurrence at 132 kV Bina S/s on 4.05.2012
MPPTCL representative explained the occurrence as below :
On 4.05.2012 at 07:45 hrs one tower of 132 kV Bina-Rajghat line at location no. 256
collapsed and 132 kV Bina-Rajghat tripped on DPR on AN phase and current fed was of the
order of 1592 A. Simultaneously 132 kV Bina-Chanderi line (which was on the same tower)
DPS operated on C-phase zone-I but A phase did not trip ( later CB trip coil found burnt).
After collapsing and tilting of the tower the fault came on A phase and started feeding current
approx 780 A in Chanderi feeder. Due to continuous feeding of fault current in A phase of
132 kV Chanderi feeder the 160MVA and 3x40 MVA transformers at Bina S/S tripped at on
E/F alongwith 132 kV Sagar, 132 kV Ashoknagar at Bina end on E/F. 132 kV Sironj and
Basoda feeders tripped from other end. Also, BORL 1&2 tripped from BORL end.
MPPTCL representative intimated that the breakers are MOCB type and over 35 years old.
The work of replacement of breakers is going on and already 90 % of these breakers have
been replaced.
ED(O), MSETCL intimated that many a places breakers were procured and installed as per
fault level at that time. But fault levels have changed a lot over the years and hence
CT/PT/Breakers needs to be upgraded as the fault levels are increasing.
Committee felt that the tripping was in order.
As regards to failure of new CT/PTs, Committee opined that the specifications
prepared at the time of procurement should be very stringent and also
warranty/guarantee for more than 5 years should be called for. Stage inspections
should be carried out strictly as per specifications.
2.3(iv) Occurrence at 220/132 kV Ujjain S/s on 7.05.2012
12 Minutes of 115th Protection Committee of WRPC
MPPTCL have intimated that on 7.05.2012 at 15:16 hrs 132 kV Ujjain-Ghosla line
attempted to trip on C phase zone –I indication at Ujjain end and tripped on over current E/F
from remote end. At Ujjain end B phase pole of MOCB got stuck up which continued to
feed heavy fault current and all the elements tripped from remote ends to stop feeding of
fault. Hence there was a total supply failure at 220 kV/132 kV Ujjain s/s. Ther is no bus bar
protection generally provided on 131 kV bus bar.
Later, the defective pole’s mechanism has been replaced and further the breaker is being
replaced by SF6 breaker.
2.3(v) Occurrence at 220kV Barwaha S/s on 11.05.2012
MPPTCL representative explained the occurrence as below :
On dt. 11.05.12, at 00:58 hrs., 220 KV “Y” phase L.A. of 220 KV Barwaha – Itarsi feeder
burst at 220 KV S/s Barwaha. There was heavy lightening in the area. This feeder tripped
from both ends. It tripped from Itarsi (remote) end on DPR in Zone I, but at Barwaha end
DPR not operated due to VT fuse failure blocking, therefore, it tripped on back up E/f
protection, it has taken about 426 msec, consequently due to this delay in tripping, other 220
KV feeders on 220 KV bus Barwaha, tripped on DPR Zone II protection from remote ends,
except the 220 KV Barwaha – Handia feeder.
There were no interruption occurred due to this event, 220 KV bus & Transformers were
remain charged due to availability of 220 KV supply from 220 KV S/s Handia. Healthy 220
KV feeders normalized within 30 minutes.
The DPR (Make AREVA, Type 442) of 220 KV Barwaha Itarsi feeder was not operated at
220 KV S/s Barwaha end. It was blocked by VT fuse failure feature due to failure of “Y”
phase PT fuse in C&R panel. On checking the Fuse grip base found defective, which was
then replaced. Since fault duration was about 426 msec, it was close to Zone II operational
time therefore, due to slight delay at 220 KV Handia S/s end, fault disconnected just before
operation of DPR at 220 KV S/s Handia end.
Failed L.A. (20 years old) replaced by new L.A. on 220 KV Barwaha- Itarsi feeder at 220 KV
S/s Barwaha. The 220 KV C&R panels were checked for any discrepancy as observed above.
13 Minutes of 115th Protection Committee of WRPC
During these trippings, 05 Generators ( 5 x 50 MW ) tripped at Omkareshwar HPS, and a
generation loss of 125 MWh occurred. However line trippings at Omkareshwar HPS were in
order and other 220 KV feeders at Omkareshwar HPS connected to other 220 KV S/s were
also normal at that time.
Committee discussed the matter and opined that lightening arrestors supposed to divert
the lightening strokes and should not fail due to lightening itself. Also, Leakage current
(LCM) of LAs be monitored. Committee felt that the tripping of Omkareshwar units
were undesirable. MPPGCL may submit detailed report regarding trippings at
Omkareshwar.
This item was again slated for discussion in the next PCM after data from
Omkareshwar is made available.
2.4: System disturbances in MSETCL/MSPGCL system.
2.4(i) Occurrence at 220 kV Kalwa on 12.06.2012 at 17:05 Hrs
MSETCL representative explained the occurrence as below :
On dtd.12.06.12 at 17:06 Hrs at 400KV R.S. Kalwa , 400 KV AREVA make CT of spare single phase unit of BHEL make burst & caught fire. At this instant, the REF protection & instantaneous B/U protection operated & breaker tripped which isolated the CT fault from the system. The failed CT has rising trend of Capacitance & Tan-delta values indicating that CT failed due to insulation failure.
Date of Testing Voltage Capacitance Tan-delta
26/06/2010 10KV 1095pf 0.197%
24/11/2010 10KV 1098.3pf 0.15%
27/11/2011 10KV 1098.0pf 0.976%
01/03/2012 10KV 1099pf 1.13%
07/06/2012 10KV 1093pf 2.051%
This rising trend has developed in new CT which is just five years old & charged in the year 2010 only . The matter was immediately referred to M/s AREVA & representative visited on dtd.20.06.2012 for inspection. The final report is awaited.
14 Minutes of 115th Protection Committee of WRPC
The controls cables were found to be damaged of own bay of ICT-1 & spare ICT of BHEL & CGL make. The E/W in between s/s take off gantry & 1st tower of double circuit 220 KV Kalwa- Kharghar & Kalwa- SIEMENS snapped & broken in to pieces. The fumes & flames of busted CT found to be spread over & broken pieces of insulator part of CT hit on ICT tank, 400 KV Bushing etc.
17/05:06:10:543 hrs : ( 1204 msec)
At this instant, it is confirmed that the BB Main II operated. The failed CT was connected to Main-II Bus resulting in to tripping of all the feeder/equipments connected to the bus along with Bus coupler.
The 400KV feeders tripped at remote end also on DT received signal. The indication appeared on ABB, RADSS BB is Y, B, & U (trip). This confirms that the BB did not operate for CT failure. However, it subsequently operated due to fumes & flames spread over on the adjacent/nearby Y & B ph of 3 x 167 MVA ICT – I which were connected to Main Bus II.
17/05:06:11:395 hrs : (2056 msec)
During the above occurrence, the E/W from S/S take off gantry to 1st tower of double Circuit line 220KV Kalwa – Siemens & Kalwa – Kharghar also break down from tower end. This has caused the 3 ph – G fault initially on 220KV Kalwa – Siemens line which is cleared instantly by the distance protection at both ends in Zone – 1.
17/ 05:06:12:675 hrs : (3336 msec)
The above failure of E/W have also caused the transient fault on B ph of 220KV Kalwa –Kharghar line due to swinging whereby the line tripped at Kalwa end & reclosed successfully , However Kharghar end tripped in Zone 2.
During above occurrence, Kalwa – Mulund & Kalwa – Trombay and 220kV Interconnector found to be tripped at Kalwa end only on operation of BB trip relay ABB make (RXMVB2: Speed Relay, ABB Make).
It is also noted that the above trip relay (ABB , RXMVB 2) is found to be operated on < 50 % of rated DC voltage being fast acting devices. Therefore, it may be operating due to DC voltage spike.
To understand the phenomenon, the Additional Aux. relays are incorporated in the BB Tripping of 220KV Kalwa & Trombay and 220kV Interconnector (Drawing Enclosed).
The window and relay indication are as below: 200 MVA SPARE ICT 400/220 kV breaker tripped ( 400KV side )WI: Diff Trip; Breaker D.C fail; buchholz alarm; Fault: 400kv CT of this spare ICT 200 MVA Brust.
15 Minutes of 115th Protection Committee of WRPC
RI: 86REF E/F Relay – 1Element 67 IN Directional E/F 1 Element (INST) 86A 5 Element SLD showing the occurrence details and bus bar trip relay circuitry is enclosed at
Annexure-2.4(i).
MSETCL representative further informed that torret CTs are not used for REF
protection of the ICT and the line CTs are wired for REF protection of the ICT.
Committee observed that the tripping of ICT due to failure of line CT is in order, since
the core towards the ICT side might have initially developed the fault and BB side core
might have been wired up for REF protection. The REF protection sensed the fault
correctly and tripped the ICT on REF. It was also observed that simultaneously the BB
protection should have operated since the same CT was wired in the BB protection.
However the BB protection might not have sensed the fault initially as the BB
protection might have been wired up through the CT core towards BB and the failure
of the CT core towards the ICT developed the fault initially and this was the out of zone
fault for BB protection and before the CT blasted completely the fault was isolated by
tripping the ICT. The spread over of fumes & flames of the busted CT caused
carbonization of the adjacent/nearby Y & B ph of 3 x 167 MVA ICT – I which were
connected to Main Bus II thereby creating a bus fault. This time the BB protection
sensed the fault correctly and isolated the fault. The tripping of the 220kV lines due to
breaking of E/W and creating Ph-G faults was in order. The operation of 220kV BB
protection was undesirable due to spurious DC voltage. The performance of the
modified BB tripping scheme should be closely monitored, since an additional relay in
the scheme would introduce additional delay and additional circuitry in the BB
protection scheme. The matter may be referred to ABB.
2.4(ii) Occurrence at 220 KV S/S Khaparkheda on date 19.03.2012
MSETCL representative explained the occurrence as below :
On 19.03.12 at 20:43 hrs Bus bar protection operated due to the initiation of arc across the
R, Y & B Poles (i.e. between blades & jaws) of the 29C Isolator of GT4 bay and is attributed
to the imperfect closing of the 29C Isolator.
16 Minutes of 115th Protection Committee of WRPC
Details of trippings at Khaparkheda S No
Name of feeder / equipment
Window Indications
Relay Indications (RYB nomenclature)
1. Busbar protection for 220 KV Transfer bus (i.e. Auxiliary bus) operated and tripped the TBC breaker through its 96 busbar trip relay:
Busbar Protection Operated
Busbar scheme ABB – RADSS with TR and R, T & U flag indications.
i. 220 KV TBC BB Prot optd 96 relay optd. 2. 220 KV GT4 E/F opt. (at PCR
end); LBB operated WI on
GT4 control panel and RTU
DC SCADA IED at GCR end
O/C-E/F relay; LBB relay (B/U + LBB Alstom- KCEG 142), MTR optd.
3. Consequent to operation of the LBB relay of GT4 all breakers connected to 220 KV Main Bus1 including Bus-coupler at Khaparkheda GCR tripped through respective Busbar trip relay 96 as follows:
--- ---
i. 400 KV Koradi ckt BB Prot optd. 96 relay optd. ii. 220 KV Ambazari ckt1 BB Prot optd. 96 relay optd. iii. 220 KV Kanhan ckt2 BB Prot optd 96 relay optd.iv. 220 KV Kaulewada ckt1 BB Prot optd 96 relay optd.v. 220 KV Kalmeshwar ckt BB Prot optd 96 relay optd.vi. 220 KV Wardha ckt BB Prot optd 96 relay optd.vii. 220 KV GT1 MTR Optd 96 relay optd.viii. 220 KV GT3 MTR Optd 96 relay optd.ix. 220 KV GT4 MTR Optd 96 relay optd.x. 40 MVA Stn T/F1 MTR Optd 96 relay optd.xi. 40 MVA Stn T/F3 MTR Optd 96 relay optd.xii. 40 MVA Stn T/F4 MTR Optd 96 relay optd. xiii. 220 KV Bus Coupler MTR Optd 96 relay optd. There were no trippings at Remote ends. Details : Outage was availed by construction wing on date 19.03.2012 on 220 KV Main bus2
at 220 KV S/S Khaparkheda for connecting the bus2 side jumpers for the proposed
commissioning of two new 220 KV circuits to new Khaparkheda S/S. For availing this
outage all the 9 bays that were connected to 220 KV Bus2 were shifted to 220 KV Bus1
through TBC by the S/S operating staff in the morning session. After completion of the
jumpering work by construction, operation of restoration of normalcy of bays was taken up in
hand by S/S operating staff at 17:56 hrs. Shifting operation for six 220 KV bays (viz:
17 Minutes of 115th Protection Committee of WRPC
Ambazari2, Kanhan1, Purti, Kaulewada2, GT2 & Stn T/F2) from Bus1 to Bus2 was
completed by 20:15 hrs.
Shifting operation for 7th bay (i.e. GT4 bay) were underway; at the juncture of tripping of
main breaker of GT4 heavy sparking across all the six R, Y & B pole contacts of 29C double
break isolator of GT4 bay (at 20:43 hrs) was observed by the switchyard operating staff.
Subsequently all the breakers connected to 220 KV Main Bus1 at Khaparkheda S/S tripped.
Analysis of Occurrence :
• MSETCL have intimated that they have analysed the occurrence and main cause of
occurrence is the heavy arcing that took place across all the R, Y & B pole contacts
(i.e. jaw & blade) of the double break isolator 29C (i.e. TBC side isolator) in GT4 bay
during shifting operations. Though after post occurrence, the correct closing and
opening operations of 29C isolator of GT-4 bay were confirmed in presence of the
CE, EHV CC O & M Zone, Nagpur, SE, EHV O & M Circle, Nagpur, EE,EHV O &
M Division, Nagpur and SE(TCC) Nagpur, it was felt that there must have been some
gap left between jaw and blade of 29C isolator during pre-occurrence shifting
operation. This might not have been noticed during night hours. At this instance GT4
was running at @183 MW of power. Thus the current of @500A was initially broken
across the imperfectly closed poles of the isolator which initiated arcing. The length
of arc and the magnitude of flashover current gradually increased and subsequently
attained a fault value. The estimated fault current is @10KA.
• This heavy arcing fault was in-zone fault for TBC bus (i.e. Auxiliary bus) and thus
selective operation of Busbar protection (ABB-RADSS) for transfer bus and
subsequent tripping of TBC breaker is IN ORDER.
• The occurrence took place at the very instance of hand-tripping of main breaker of
GT4 during shifting operation. Hence the GT4 remained connected to Main Bus1 (i.e.
29A isolator was in closed position) also the ‘NIT’ switch remained in ‘INTER’
position.
• While other sources connected to the bus-I fed the fault through the TBC, The GT4
directly fed the fault with its own fault contribution (estimated fault contribution by
GT4 @1KA). This caused Earth Fault relay of GT4 to operate at PCR end and issued
the trip command to TBC & Main breaker. However the fault current did not seize as
the Generating Unit-4 was directly feeding the fault. Hence, subsequently its LBB
18 Minutes of 115th Protection Committee of WRPC
protection operated and tripped all the breakers connected to Bus1. Hence the
operation of E/F & LBB protection of GT4 and consequent tripping of all breakers
connected to 220 KV Main Bus1 at Khaparkheda is IN ORDER.
• The sequence of operations for shifting of the GT4 bay was later verified and found
OK.
SE(Protection), WRPC enquired whether transfer bus is used for switching of feeders from
one bus to another. Members from Generating company viz. NTPC, CGPL, State Genco’s of
other States etc. informed that switching is done directly through isolators and transfer bus is
not used for switching over from one bus to other bus. This procedure of transferring element
from one Bus to other also takes far lesser time. Transfer bus is used only during when there
is problem with own breaker or own isolator or own CT.
Committee recommended that MSETCL may follow the same procedure that is being
followed by other generators/TRANSCOs. The operation of LBB and BB protection of
220kV transfer bus was in order, since the transfer bus isolator was not closed properly
during transfer of GT4 from Main bus 1 to Main bus 2. However the above occurrence
would have been avoided if the above procedure for transfer of element from one bus to
another bus was adopted.
2.4(iii) Occurrence at 400 KV S/S Khaparkheda on date 05.04.2012
MSETCL representative explained the occurrence as below :
At 400 kV Khaparkheda s/s at 12:41 on 5.04.2012 all breakers connected to 400 KV Bus1
(one and a half bus arrangement) tripped at 400 KV GCR Khaparkheda through respective
Busbar trip relay 96 on operation of LBB protection (50Z1) (Areva Micom make P123 type)
of GTR bay installed in MAHAGENCO GCR, for Bus-I.
Details of trippings at Khaparkheda S No
Name of feeder / equipment
Window / SCADA
Indications
Relay Indications (RYB nomenclature)
1 LBB relay of GTR bay operated at Mahagenco’s PCR end and tripped following breakers connected to 400 KV Bus1 through respective BB trip relay 96 as under:
---- LBB relay 50Z1 (Areva Micom P123) operated at PCR with trip LED indication. Fault data (Record 25): Ia = 0; Ib=1.25A; Ic=0; Faulted Phase: None; Tme: 12:41:25:22; Dt 05.04.12
19 Minutes of 115th Protection Committee of WRPC
i. 400 KV GTR 96 relay optd 96 relay (GTR was OFF) Time: 12:41:44:174 hrs)
ii. 3X167 MVA 400/220 KV ICT1
96 relay optd 96 relay (Time: 12:41:44:174 hrs)
iii 3X167 MVA 400/220 KV ICT2
96 relay optd 96 relay (Time: 12:41:44:174 hrs)
iv 400 KV Stn 5A 96 relay optd 96 relay (Time: 12:41:44:174 hrs) v 400 KV Stn 5B 96 relay optd 96 relay (Time: 12:41:44:174 hrs)
There were no trippings at Remote ends. MSETCL representative stated that on enquiry with MAHAGENCO it was intimated that
GTR was already OFF. The pre-synchronisation trials of the GTR bay were in progress and
the relay operated at the instance of switching OFF / ON the auxiliary DC to the Control &
Relay panel. This trial was a part of the routine test. However at the instance of switching of
auxiliary supply, the ‘any trip’ pulse from MTR (Master Trip Relay) was active to the LBB
relay as the MTR was not resetted.
The numerical busbar scheme Sifang CSC 150 is provided at 400 KV Khaparkheda GCR.
The in-built LBB function of this relay is used for LBB protection for all the bays except
GTR. As the control of GTR bay is with Mahagenco, the LBB relay for this bay is also under
the purview of Mahagenco and the LBB command for GTR is externally connected to the trip
bus of busbar scheme. The matter of undesired operation of the LBB relay has been taken up
with MAHAGENCO and with M/S Areva.
As one and a half breaker bus arrangement is provided at GCR, the breakers connected to
Bus-1 & Bus-2 are clearly identified; hence isolator interlock is not provided for
identification of breaker. In the present scheme the LBB command of GTR is therefore
directly connected to the trip bus without such interlock.
The matter for review of the protection scheme for introduction of Breaker or Isolator
interlock is also taken up with M/S Easun Reyrolle Ltd.
The tripping of breakers connected 400 KV Bus-1 consequent to operation of LBB did not
cause any interruption of supply, since there is a one and a half breaker bus arrangement. The
GTR was already OFF and other bays were being fed through respective Tie breaker / Main
breaker.
20 Minutes of 115th Protection Committee of WRPC
Committee opined that this is human error and this occurrence could have been
avoided if proper procedure would have been followed. Also, MSPGCL were
instructed to provide necessary interlock in the scheme at Khaparkheda Generating
station. After providing the interlock the compliance report stating details of the same
may be forwarded to WRPC.
2.4(iv) Occurrence at 220 KV S/S Warora on date 13.05.2012
MSETCL representative explained the occurrence as below :
On date 13.05.2012 at 08:58 hrs 220 kV Bus bar Protection (REB 500 ABB Make) of 220
KV WPCL bus operated and tripped following breakers through respective B/B trip relay
96 including bus sectionalizer breaker
Sr No
Name of feeder / equipment
Window Indications
Relay Indications (RYB nomenclature)
a 220 KV WPCL Ckt-1 nil 96 BB trip relay b 220 KV WPCL Ckt-2 nil 96 BB trip relay
Trippings at Remote ends :
S No
Name of S/S Name of the feeder
Window Indications Relay Indications
1 220 KV GCR Chandrapur
220 KV Warora Distance protection trip
Dist Zone-2, R-Y-N, XTF=40.6 KM, 86
2 220 KV Wani 220 KV Warora Distance protection optd.
Dist Zone-2 R-Y,86
3 220 KV Wardha 220 KV Warora Distance protection optd.
Dist Zone-2, R-Y-N, XTF=73 KM,86
4 220KV Hinganghat 220 KV Warora Distance protection optd.
Dist Zone-2 R-Y,XTF=48.76 KM,86
Details of occurrence : On date 13.05.2012 at 08:58 hrs, bursting sound was heard from the switch yard of 220 KV
S/S Warora, followed by total a. c. failure at this S/S. On Yard inspection ‘R’ ph CT (Make:
SCT Gaziabad, Sr. no.: 2009/1766, Mfg year: 2009) of 220 KV WPCL Bus-sectionalizer
found to have burst. The failure caused damage to R-ph pole of Siemens make bus-
sectionalizer breaker and R-ph insulator of incoming side and outgoing side isolators and
carbonisation of adjoining Y-ph CT. 220 KV Bus bar Protection scheme (ABB - REB 500)
provided for 220 KV WPCL bus operated alongwith the newly commissioned 220 KV Bus
bar Protection scheme (Make: NR-RCS 915 ) provided on 220 KV old Warora bus which
21 Minutes of 115th Protection Committee of WRPC
was kept on alarm mode.
Analysis of occurrence :
• The work of extension of existing 220 KV bus in the extended section of
switchyard, providing of bus-section breaker and allied work of providing
switchgear, protection and SCADA etc was carried out by M/S WPCL on turnkey
basis. On date 13.05.2012, at 08:58 Hrs the R-ph CT of 220 KV Bus-sectionalizer
burst which created bus fault in WPCL bus and consequently 220 KV Bus bar
Protection (ABB-REB 500) of 220 KV WPCL bus operated and tripped 220 KV
WPCL Ckt-I & II breakers through respective B/B trip relay 96 including Bus-
sectionalizer breaker at Warora end is in order.
• Remote end indication at Chandrapur, Wani, Wardha, Hinganghat indicate the
involvement of R & Y phases in the fault, indicating that the smoke of the burst R-
ph CT must have created a bus fault w. r. to Y phases. This fault was being fed
from existing 220 KV Warora bus. The Newly commissioned numerical 220 KV
Bus bar protection scheme (RCS 915 Make-NR) provided for 220 KV old Warora
bus operated but since the same was kept on alarm mode so as to confirm its
stability on through fault, no tripping at local end at Warora S/S occurred. Thus
220 KV bus fault on 220 KV old Warora bus caused all the sources to trip at their
respective end on distance zone-2 (R & Y phases). Tripping of all sources at
remote end caused total a.c. failure at 220 KV S/S Warora.
• The occurrence caused loss of generation @436 MW of M/S WPCL. Also the load
of Warora Railway TSS of @ 2 MW and local load of @ 43 MW was affected.
The load of @ 385 MW of Hinganghat, Wardha, GCR Chandrapur and Wani
feeders was thrown off to other lines in the grid. The 220 KV grid however
remained stable.
• The newly commissioned 220 KV Bus bar protection scheme (RCS 915 Make-NR)
which was kept on alarm mode to confirm its stability on through fault is now kept
on trip mode.
Committee observed that the tripping of lines from remote ends in zone 2 were in order
since the BB protection scheme was kept under observation(in Alarm mode).
2.4(v) Occurrence at 220 KV S/S Butibori on date 19.06.2012
22 Minutes of 115th Protection Committee of WRPC
MSETCL have informed that at 03:50 hrs on 19.06.2012 at Butibori S/S all breakers
connected to 220 KV Main Bus-1 including Bus-coupler tripped through respective 96 BB
tripped.
Details of trippings at Butibori: S No
Name of the feeder / equipment
Window Indications Relay Indications
1 LBB Protection of 220 KV Indorama feeder operated and tripped all breakers connected to 220 KV Bus 1, including Bus-coupler, through respective 96 BB trip relays, as follows:
-
2 220 KV Indorama LBB protection optd 2/50Z, 96 3 220 KV Inox i)Pilot wire prot optd.
ii)Pilot wire defective 96
4 220 KV Buscoupler Nil 96 5 50MVA 220/33 KV T/F-3 Nil 96 6 220 KV Koradi Trip relay optd. 96
There were no trippings at remote end.
Analysis of occurrence : MSETCL have analysed the incidence as below :
1. There was a fault on 11 KV bus at M/S Indorama company emanating from 220 KV
Butibori S/S. For this fault, 11/33 KV Tie 4 & 5 T/F tripped on over-current relay at
consumer end with fault current @ 1.71 KA and 1.63 KA on 33 KV side in about 232
msec.
2. The matter of operation of LBB protection of 220 KV Indorama feeder was
investigated in detail and the problem of contact of trip relay RXMS1 was detected.
It was found that the D.C logic of LBB relay on 220 KV Indorama panel at 220 KV
Butibori S/S was through via bus bar protection trip relay (96) contact which was
found stuck in make condition. The fault current was above the pick up setting of
LBB relay . Current setting of LBB relay is 0.8 A sec(CTR-400/1A) that is 320 A
primary with 200 msec timer setting. As D.C. logic of the LBB relay was already
through and fault current was above pick up setting of LBB relay resulting into
operation of LBB protection of 220 KV Indorama feeder. The problem of contact of
23 Minutes of 115th Protection Committee of WRPC
trip relay RXMS1 was later attended and confirmed that the D.C. logic of LBB relay
is not through.
3. It is to note that back up protection of 220 KV Indorama feeder did not operate for the
above fault as the fault current was just above the pick up setting of LBB relay and
Earth fault relay will take time @0.5Sec to operate. The setting of Back up O/C and
E/F relay (Make: EE, Type: CDD) are:
CTR PS TMS O/C R & B 400/1A 100% 0.08 E/F 40% 0.08
4. The total fault current shown at 33 KV level at M/S Indorama end is @3.34KA
(Ref: Annexure:2). For this fault, The fault current shown by 220 KV side relay of
220/33 KV T/F at 220 KV Butibori S/S end is @500 A. From this it appears that
@500 A fault current is fed from 220 KV bus at 220 KV Butibori S/S. For 500 Amp
fault current the time require for E/F relay to operate is calculated as under:
500A/160=3.1 means for 3 times current TOP is 6.302 and TMS setting for E/F is
0.08. Thus time requires to operate E/F relay comes out to be @504 msec.
From this it appears that before operation of E/F relay of T/F, the LBB relay of
Indorama feeder operated with pick up setting of 320 A primary with 200 msec timer
setting.
5. The occurrence caused interruption to EHV consumers M/S Indorama & M/S INOX
(Load 1MW and 2.5 MW respectively) and also local 33 KV load of @ 12 MW
was affected. The load @ 55 MW on 220 KV Koradi feeder was shared by other
feeders and the grid remained stable.
Committee discussed the incidence and opined that the operation of LBB protection of
220 KV Indorama feeder is undesirable and the operation of LBB relay of 220 KV
Indorama feeder was mainly due to contact stuck up (low contact gap) problem of trip
relay RXMS 1 (since RXMS 1 are high speed relay), which made the trip logic of LBB
relay through and the load current was higher than the LBB current setting.
Committee opined that trip through logic of LBB relay should be wired up through
RXMH relay (since these are slow speed relays) instead of RXMS 1 relay for desirable
24 Minutes of 115th Protection Committee of WRPC
operation of LBB.
ITEM NO. 3: Other points:
ITEM NO. 3.1: Implementation of SPS for Agra-Gwalior corridor. Member Secretary(I/C), WRPC, intimated that NRLDC vide letter dated 5.8.2012 requested
for discussion and finalization of setting for SPS for tripping of Agra-Gwalior lines or Bina-
Gwalior lines.
Following comments were communicated to NRPC vide letter
No.WRPC/Protection/SPS/2012/1287 Dated 16.08.2012.
1. SPS designed by NR is preemptive action to control overloading of Agra-Gwalior and Bina-
Gwalior corridor between WR and NR and therefore summated values for both the circuits
may be considered for operating load shedding in NR.
2. Proper load shedding in NR only would reduce the flow on above corridor. The effect of
backing down of generation in WR would not be so sensitive to reduce the flow on above
corridor. Therefore, Case-1 and Case-2 actions to be taken by NR constituents are in order.
3. As far as backing down of 500 MW generation in Western Region is concerned, We have
requested WRLDC to carry out sensitivity study to find the effect of backing down/tripping
of various generators on flow on Bina-Gwalior and Agra-Gwalior lines.Therfore
presupposing backingdown of generation at VSTPS or Korba may not be appreciable.
4. In case of angular separation between Gwalior and Agra beyond permissible limit planned
separation between the two grids alongwith load shedding schemes may also be planned/
incorporated.
5. Sufficient time delay and interlocks are required to be provided for backing down/tripping of
generation in WR after ascertaining that sufficient load shedding is carried out in NR and
thereafter according to flow on Agra-Gwalior and Bina-Gwalior lines backing down
quantum can be decided.
6. Appropriate action plan may be devised in case of tripping of both Agra-Gwalior lines
7. Above points alongwith the sensitivity study results submitted by WRLDC would then be
discussed in ensuing Protection sub-Committee of WRPC and thereafter in TCC & WRPC
forum and then the outcome would be submitted to NR.
WRLDC have carried out studies to check the sensitivity of various options as below :
• As per studies, after tripping of Agra-Gwalior lines power flow over other inter-regional
25 Minutes of 115th Protection Committee of WRPC
lines between NR-WR and WR-ER would increase. Higher sensitivity has been observed
with reduction of generation at :
i) Korba, Sipat, Vindhyachal STPS to control power flow towards ER
ii) CGPL & SSP to control power flow in Zerda-Bhinmal-Kankroli lines
iii) Satpura TPS to control power flow in Bina-Mehgaon-Gwalior lines
iv) ISP and Satpura TPS to control power flow in Badod-Kota-modak lines
• The SPS shall also take signal from another SPS to be provided at Bina for loss of D/C
lines of Bina-Gwalior
• Inter-tripping scheme at Bina to control ICT loadings
• SPS had been made operational in NR since 18.08.2012 for load shedding of 500 MW in
UP and Rajasthan whenever flow on Gwalior-Agra D/C crosses 500 MW/Ckt or if flow
crosses 750 MW in case of only single ckt. Availability.
The loss of export to NR may result in high voltages at Bina & Gwalior and inter-tripping
shall be provided to trip one ckt of 400 kV Bina-Gwalior D/C (if both ckts are available) or
tripping of one ckt of Satna-Bina. (preferably 765 kV). The voltage grading for tripping of
lines at Bina may be coordinated accordingly so that 400 kV Bina-Bina D/C and 400 kV
Bina-Shujalpur D/C should not trip and positively avoided.
As per studies 500 MW relief from all the stations mentioned above are required.
In this a discussion evolved among members. The gist of discussion is given below.
CE, SLDC, MPPTCL stated that Satpura TPS normally operate on Technical minimum and
therefore Satpura TPS may not be considered for above backing down and instead JP Bina
Power Station may be considered. Further SSP and ISP being a hydro station and the
generation from this station during such occasions may not be always available. Hence
alternate generation backing down may be explored.
He further stated that similar SPS is also required to be designed for Badod-Modak and
Badod-Kota lines or alternatively load in Rajasthan/UP (near Modak & Kota) to the tune of
100 MW should be tripped.
In view of above it was decided that backing down at JP Bina instead of backing down at
Satpura TPS and backing down at CGPL instead of backing down at SPS and ISP may be
included in the scheme for controlling the flow from WR to NR.
26 Minutes of 115th Protection Committee of WRPC
Regarding commercial mechanism to compensate for UI payable due to above for the
concerned stations as above, GM, WRLDC intimated that at this stage suspension of UI for
these stations or post-facto revision of schedules (schedules as per actual) may be done by
them as done in case of transmission constraints. Detailed commercial mechanism would be
formulated by WRLDC and then it may be discussed in ensuing Commercial Committee.
Committee in-principle agreed with the above arrangement. Details would be prepared
by WRLDC and put up for approval in the next WRPC meeting. NRPC would be
intimated of having identified units for 500 MW backing down required for proposed SPS
scheme.
ITEM NO. 3.2: Repeatation of PLCC frequency for various 400 kV lines under WRSS-
II & Mundra UMP scheme
SE(Protection), WRPC stated that ACE(Transmission), GETCO during 114th PC meeting
intimated that PLCC frequencies already in use on 400 kV at GETCO s/s are repeatedly used
by PGCIL for 400 kV D/c Ranchodpura(Vadavi)-Limbdi(Chorania), 400 kV D/c
Ranchodpura-Zerda(Kansari), 400 kV Ranchodpura-Bachau and 400 kVLimbdi(chorania)-
Mundra commissioned under WRSS-II and Mundra UMPP scheme without any concurrence
fromGETCO. He further intimated that as per technical report, CE1, IEC 663:1980 clause
No. 4.1.2.C, “The same frequency maybe used for two different PLCC stubs working on
lines forming common system if two are separated by at least two line sections with
intermediate sub stations.”
PGCIL has used frequencies already used in service for GETCO without any concurrences
from GETCO for other stations and warned that the practice of utilizing repeated frequencies
for PLCC may cause mal operation of system further causing instability in the grid. He
further intimated that 8 KHz band is used for every link.
PGCIL/WRLDC representative during 114th meeting of Protection Committee intimated that
PGCIL might have used repeated frequencies due to non-availability of the bandwidth. He
further intimated that elsewhere 4 KHz band is used safely in the system and the problem of
non-availability of bandwidth can be resolved if 4 KHz band is used in GETCO. However,
he would confirm the same after consultation with WR-II. PGCIL/WRLDC were requested
to followup the matte with WRTS-II, PGCIL.
27 Minutes of 115th Protection Committee of WRPC
ACE(TR), GETCO vide letter No. CE(Tr)/SE/Telecom/PLCC/39/1012 dated 23.07.2012
addressed to PGCIL, WR-II (have intimated that despite several reminders to PGCIL
regarding repeated use of PLCC frequencies for 400 kV transmission lines under WRSS-II &
Mundra UMPP scheme, matter have not been responded/solved by PGCIL.
PGCIL, WR-II representative intimated that they have referred the matter to their
Corporate office and necessary action is being taken. SE(Protection), WRPC requested
PGCIL and GETCO to sort out the matter bilaterally for which both PGCIL and
GETCO agreed.
ITEM NO. 3.3: Review of low frequency and high frequency trip setting for generating stations in WR.
SE(Protection), WRPC stated that during recent grid disturbance in NR/ER/NER on
31.07.2012, WR grid was isolated from rest of NEW grid and WR frequency almost touched
51.5 Hz. Following units reported to have tripped in WR during isolation of WR from
NR/ER :
Station/ Unit Date/Time Reason MW Adani, Mundra-7 31.07/13:01 SPS operation 660 EPGL-2 31.07/13:02 Feed water pump tripped 600 KLTPS-2 31.07/13:02 Geenrator protection operated 70 DSPM -1 31.07/12:57 UAT HT side overcurrent relay 250 DSPM -2 31.07/12:57 Over frequency relay operated 250 Sipat STPS 31.07/13:01 Over frequency relay operated 500
Member Secretary (I/C), WRPC stated that from above it is clear that most of the units have
tripped on protection irrelevant with the above occurrence and trippings were undesirable,
however it has given relief as required at that time. It is necessary that particular relief is
received through designed tripping of units as per setting. Also, the generator trip
settings/timings required to be staggered to avoid simultaneous/excessive tripping of all
generators at given station/control area/State. In such an event total station may face
blackout and may result into low frequency in the grid in the event of tripping more than
required generation.
Committee reviewed the trip settings of various units and recommended that
generation of around 1500 MW is required to be tripped/backed down during high
frequency operation of the system at specific generating stations so as to avoid
28 Minutes of 115th Protection Committee of WRPC
transmission congestions and over voltage problems. Committee further felt that
generator over frequency trip are not meant for tripping the units as a system special
protection scheme and the over frequency trip settings suggested by the OEM of the
generators be retained. WRLDC was requested to study and identify the generating
units which are required to be tripped at system frequency above 51.5Hz. as a design
feature notwithstanding trip setting adopted by other units in grid.
ITEM NO. 3.4: Protection Auditing by CPRI
Member Secretary (I/C), WRPC stated that during the meeting held at CEA on recent grid
disturbance in NR, importance of protection auditing was discussed. All the members are
familiar with protection of power system but new to auditing of the same. In order to address
the system security concerns protection audit of substations is essential and actively being
pursued in India. The aim of the audit is to review the protection philosophy, relay
coordination and protection settings, healthiness of DC system, healthiness of
communication link with respect to protection system, healthiness of Time synchronization
of generating Units, healthiness of disturbance recorders and event loggers, protection testing
procedures and protection system technology.
Accordingly, Shri Shivkumar Aradhya, CPRI, Bengaluru made a detailed presentation on the
ins and outs of protection auditing, wherein he covered aspect like scope of audit, stages of
audit, methodology adopted for audit, facilities available at CPRI, and case studies of DTL.
The full presentation is available on WRPC website.
Member Secretary, WRPC enquired CPRI whether any license has been granted to
CPRI or CPRI is certified as statutory body for protection audit. In reply, CPRI stated
that presently there is no license or certificate granted to CPRI and CPRI is carrying
out audit of protection system of State and other utilities as per requests received from
them. Also MS enquired whether only stand alone audit is possible or whole scheme
such as bus-bar or differential scheme can be audited. CPRI representative stated that
online scheme can not be audited however instrument transformer accuracy and setting
of relays individually could be audited. The presentation has been uploaded on WRPC
site.
ITEM NO. 4: Any other issues.
30 Minutes of 115th Protection Committee of WRPC
entered NR. Further prior to closing the AC Bypass, NTPC-Vindhyachal
was running normally with WR system. It is unfortunate that some problem
of NR system bypass got ‘extended into’ Vindhyachal and tripped the units.
3) As such Committee recommended that Vindhyachal units tripped under
grid disturbance and appropriate commercial issues may be taken up in the
CCM forum of WRPC.
4.2 CGPL Synchronization issue.
CGPL representative intimated that on 30.07.2012 at around 06:15hrs, CGPL Mundra was
isolated from the grid and survived with house load. The loading of the generators which was
around 700MW dropped to @124MW after isolation. At around 06:19hrs unit-2 tripped on
reverse power and Unit-1 continued on house load generating about 62MW. 400 kV CGPL-
Mundra line was in service. While closing 400kV Bhacchau-Ranchodpura ckt 2 at
Ranchodpura S/S by GETCO there was a large synchronizing current of the order of 26 kA
on all three phases and the unit at CGPL Mundra tripped. There were damages to the unit and
the original manufacturer has to be called and it took around a month to bring back the unit.
He apprehended that the synchronization of 400 kV Bachau-Ranchodpure ckt 2 was
performed without using the check synchronization facility and this was due to improper
synchronization.
GETCO representative intimated that synchronizing facility is available at 400kV
Ranchodpura. Further GETCO was instructed by WRLDC to close the above line. However
it was not told to them that CGPL was on islanded mode / house load.
GM, WRLDC stated that this was the problem of communication, as CGPL intimated that
their units were islanded on house load, which was not understood by operators at at
WRLDC. He opined that CGPL could have intimated that their units were islanded from the
grid. To this CGPL pointed out that they have no way of knowing whether they are islanded
or not from the grid.
Committee discussed the occurrence and observed the following:
1) The large currents in all the three phases resulted due to improper
synchronization. It is well known that when two systems are synchronized with
large phase difference, it results in a fault like situation on all the phases, which
30 Minutes of 115th Protection Committee of WRPC
entered NR. Further prior to closing the AC Bypass, NTPC-Vindhyachal
was running normally with WR system. It is unfortunate that some problem
of NR system bypass got ‘extended into’ Vindhyachal and tripped the units.
3) As such Committee recommended that Vindhyachal units tripped under
grid disturbance and appropriate commercial issues may be taken up in the
CCM forum of WRPC.
4.2 CGPL Synchronization issue.
CGPL representative intimated that on 30.07.2012 at around 06:15hrs, CGPL Mundra was
isolated from the grid and survived with house load. The loading of the generators which was
around 700MW dropped to @124MW after isolation. At around 06:19hrs unit-2 tripped on
reverse power and Unit-1 continued on house load generating about 62MW. 400 kV CGPL-
Mundra line was in service. While closing 400kV Bhacchau-Ranchodpura ckt 2 at
Ranchodpura S/S by GETCO there was a large synchronizing current of the order of 26 kA
on all three phases and the unit at CGPL Mundra tripped. There were damages to the unit and
the original manufacturer has to be called and it took around a month to bring back the unit.
He apprehended that the synchronization of 400 kV Bachau-Ranchodpure ckt 2 was
performed without using the check synchronization facility and this was due to improper
synchronization.
GETCO representative intimated that synchronizing facility is available at 400kV
Ranchodpura. Further GETCO was instructed by WRLDC to close the above line. However
it was not told to them that CGPL was on islanded mode / house load.
GM, WRLDC stated that this was the problem of communication, as CGPL intimated that
their units were islanded on house load, which was not understood by operators at at
WRLDC. He opined that CGPL could have intimated that their units were islanded from the
grid. To this CGPL pointed out that they have no way of knowing whether they are islanded
or not from the grid.
Committee discussed the occurrence and observed the following:
1) The large currents in all the three phases resulted due to improper
synchronization. It is well known that when two systems are synchronized with
large phase difference, it results in a fault like situation on all the phases, which
31 Minutes of 115th Protection Committee of WRPC
happened in this case.
2) Prior to synchronization, the communication gaps indicates that operator at
GETCO was not aware that by closing a 400 kV Ranchodpura-Bachau line, they
were attempting to synchronize an islanded system with the rest of the grid. If
GETCO had been instructed by WRLDC that by closing the above line, two
islanded systems are being synchronized, permissible limits of synchronization
could have been made stringent ( as done for generator synchronization) and
suitably taken care of, so that the synchronization is smooth. This would have
avoided the damage to the machine at CGPL.
3) Committee recommended that in future, WRLDC, before giving codes, should
be fully aware of the situation and also make aware any intervening or
coordinating agency about the situation, particularly for lines connecting to or
near generating stations.
4) Committee recommended that flow of information and communication from
WRLDC to SLDC / intervening agency should be clear and explicit.
ITEM NO. 5: Date and Venue of the next meeting.
The next protection Committee meeting will be held during the month of December -12. The
date and venue will be intimated separately.
ANNEXURE-I
1 Shri S.A.Patel Ex. Engineer (Testing)
2 Shri. P S Kulkarni Superintending Engineer, Nagpur3 Shri. Ajit Pachori Executive Engineer, Mumbai
4 Shri S G Kelkar ED (O), Mumbai5 Shri Shinde Chief Engineer , SLDC, Kalwa6 Shri Shashank Jewalikar Superintending Engineer (T &C), Auragabad.7 Shri A M Kondawar Superintending Engineer (TCC), Nagpur8 Shri Vasant Pandey EE, SLDC, Kalwa9 Shri B L Pasarate SE(TCC), Vashi
10 Shri P M Deshpande EE(Testing), Yavatmal11 Shri P S sale SE(TCC), Karad12 Shri P R Deore CE(Trans.), Pune13 Shri R S Parulkar EE(T&T), Chandrapur
14 Shri Bende P R Chief Engineer, SLDC, Jabalpur
15 Shri R S Shrivastava Superintending Engineer, 400kV S/S, Bhopal16 Shri Sunil Yadav Superintending Engineer(T&C) , Indore.
17 Shri Prakash C. Soni Superintending Engineer (Engg.), MPPGCL,Jabalpur
18 Shri M Z Rehman Superintending Engineer (T&C), Bhilai
19 Shri S K Mehta Superintending Engineer(O&M), Raipur20 Shri P Kolay Superintending Engineer(Opn.), Korba west
21 Shri Ruchir Oza SO/E , TAPS-3&4, Tarapur 22 Shri Ashwin Yadav SO/E , TAPS-3&4, Tarapur 23 Shri V M Daptardar SME(E), TAPS 1&2 , Tarapur
LIST OF PARTICIPANTS
115th Protection Committee Meeting held on 6th & 7th September 2012 at Pune(Mah.).
GETCO (Gujarat Energy Transmission Corporation Limited)
MAHAGENCO (Maharashtra State Power Generation Company Limited)
MSETCL (Maharashtra State Electricity Transmission Company Limited)
MPPTCL (Madhya Pradesh Power Transmission Corporation Limited)
MPPGCL (Madhya Pradesh State Power Generation Co. Ltd.)
CSPTCL (Chattisgarh State Power Transmission Co. Ltd.)
CSPGCL (Chattisgarh State Power Generation Co. Ltd.)
NPCIL (Nuclear Power Corporation of India Limited)
24 Shri Jitendra Tewari AGM (EMD-I/c) Vindhyachal STPS25 Shri R K Aash AGM(Elect.), NTPC, Kawas.26 Shri Prasun Chakraborty AGM(EMD-I), NTPC, Sipat.27 Shri D Roychowdhary AGM WR-II, Raipur28 Shri Oswald Menezes DGM(OS)., NTPC,WR-I,Mumbai
29 Shri Kundan Rathod Sr. Manager( E M), RGPPL.
30 Shri M A K P Singh Member (Power), NCA31 Shri Rajesh Sharma Assist. Director, NCA
32 Shri Ravi A. Wadyalkar Manager , WRTS-I, Nagpur33 Shri Brahananda Doppani Manager (O&M), WRTS-II, Vadodara.
34 Shri Murlikrishnan Asst. Gen. Manager35 Shri A Uppal Chief Manager36 Shri Girish Jawale Manager, Mumbai
37 Shri K N Athavale GM(Electrical)
38 Shri Uday Trivedi Manager, Ahmedabad.
39 Shri Pravin Chitral Assistant Gen. Manager (O&M), Ahmedabad.40 Shri Milind Modi Manager (Trans.), Ahmedabad.
41 Shri M. R. Waigankar Sr. Manager (T&P), R-Infra, Mumbai
42 Shri S. Aradhya Addl. Director
43 Shri P Pentayya GM, POSOCO, Mumbai44 Shri V A Murty DGM, POSOCO, Mumbai45 Smt. Pushpa Seshadri Chief Manager (OS), POSOCO,Mumbai
46 Shri S D Taksande Member Secretary I/C47 Shri Satyanarayan S. Superintending Engineer (O&S)48 Shri M M Dhakate Superintending Engineer (P)49 Shri P D Lone Executive Engineer (Comml)
NTPC Ltd.
RGPPL,Ratnagiri
NARMADA CONTROL AUTHORITY
PGCIL (Power Grid Corporation of India Limited)
TPC (Tata Power Company)
Coastal Gujrat Power Ltd.,Mundra
Adani Power Ltd, Ahmedabad
Torrent Power Ahmedabad
REL (Reliance Infra Ltd.)
CPRI , Bangalore
POSOCO WRLDC (Western Regional Load Dispatch Centre)
WRPC (Western Regional Power Committee)