24 kV / 25.8 kV Load Break Switch / Auto Section Switch
Transcript
Page 1: Load Break Switch / Auto Section Switch

24 kV / 25.8 kV

Load Break Switch / Auto Section Switch

Page 2: Load Break Switch / Auto Section Switch

2 I

Contents

Feature

Structure and Function

LBS Rating

ASS Rating

LBS control circuit

ASS control operation and performance

LBS fuse selected list

LBS installation method

LBS Dimensions

ASS installation method

ASS Dimensions

04

05

08

09

10

11

12

13

14

15

16

LB

S/A

SS

Page 3: Load Break Switch / Auto Section Switch

I 3

As the leader in power and automation industries, LSIS provides Total - Solution that creates pleasant and productive industrial society.

24kV Load Break Switch

25.8kV Auto Section Switch

Page 4: Load Break Switch / Auto Section Switch

4 I

Load Break Switch / Auto Section Switch

High technology• Realization of compact and lightweight for user convenience

• Lightning Impulse type with puffer structure that has excellent blocking performance

• Easy maintenance • Fuses up to 100A can be applied

Safety• Safe operation in hot-line status• Obvious visual check for ON-OFF status• Perfect fuse striker structure

High reliability and convenience• Maximizing arc extinguishing capability by compressed air

• Vertical and horizontal installation features• Manual cable with distance adjustment • Remote operation function. • Provide an alarm contact in case of fuse cut-off

Grounding switch function • 25kA/1 second short time capability• Maximize safety through interlock device for main circuit and ground switch

Load Break Switch

[Feature]

Basic type Fuse adhesive type

24kV Power FUSE

Page 5: Load Break Switch / Auto Section Switch

I 5

Manually operated cable• Standard length is 2m and 2.6m. Custom-made, 1.2m, 5m should be discussed separately.

• Turn the the hand wheel to the right for 50 times and manual input is completed, while turn it to the same direction for 8 times, the opening operation is completed.

Load Break Switch

[Structure]

➊ ➋ ➌ ➍ ➎

➊ Arc blade➋ Main movable part➌ Arc extinguish part

➍ Primary terminal➎ Operation mechanism➏ Fuse holder

➐ Fuse➑ Secondary terminal➒ Insulation support

LBS structure

Page 6: Load Break Switch / Auto Section Switch

6 I

inrush current suppression• When ASS operates normally (if current is 10% 100% current correction tab), blocks opening operation and it is put into operation again, this function suppresses malfunction of which ASS mistakes the current as a fault current due to inrush current of backup protective equipment of ASS.

Overload protection • It is operate according to the inverse characteristic curve in less than an overcurrent lock of 800A.

Stored energy Trip• Although blocking is operated according to the T-C curve due to overload or ASS is not blocked since the overload is removed, if backup protective equipment is operated so that no voltage is generated, the ASS will be instantaneously released and disconnects line of back of the ASS.

Overcurrent lock• While ASS protects the switching when failure of rated breaking current (900A) occurs, if the current is greater than the lock current (800A ± 10%), the switch will be LOCK status. The fault current will be removed by the backup protective equipment and ASS will be blocked in the non-voltage status.

➎ ➍

➑ ➒ ➓➐

[Structure]

[Feature]

Control box

Auto Section Switch

➊ Arc extinguish part➋ Primary terminal➌ Main movable part➍ Arc contact

➎ Fuse holder➏ Fuse➐ Secondary terminal➑ Insulation support

➒ Arrester LA➓ C.T

Operator

ASS structure

Page 7: Load Break Switch / Auto Section Switch

I 7

LS switch

LSJ

Type method

J ASS

L

Operation

M Electric-operated

M

Ratedvoltage

25 25.8kV

25

Ratedcurrent

2 200A

2

Operating power

D3 DC 24V

D3

Auxiliary contacts

1 2a2b

1

Groundswitch

Sstand

alone type

F1Fuse tilted

type

F2Fuse

vertical type

S

Length Product Name

1.0m MANUAL, OPERATOR 1.0m

1.2m MANUAL, OPERATOR 1.2m

1.5m MANUAL, OPERATOR 1.3m

1.8m MANUAL, OPERATOR 1.8m

2.0m MANUAL, OPERATOR 2.0m

2.6m MANUAL, OPERATOR 2.6m

3.0m MANUAL, OPERATOR 3.0m

Manually operated cable

Auto Section Switch

Type method

L LBS

LS switch Operation

MElectric-operated

Ratedvoltage

24 24kV

Ratedcurrent

6 630A

Operating power

D1 DC 110V

D2 DC 220V

A1 A1 110V

A2 A2 220V

00 hand-operated

Auxiliary contacts

1 2a2b

2 4a4b

Configuration Type

S stand-alone

FFuse-linked

type

Groundswitch

O ×

LSJ L M 24 6 D1 1 S O

Load Break Switch

LBS / ASS Type Numbering System

Page 8: Load Break Switch / Auto Section Switch

8 I

Load Break Switch / Auto Section Switch

Rating

Type24kV

Non-Fused type Fuse type

Type Name LSJ-L-M-24-6-S-O LSJ-L-M-24-6-F-O

Phase No. 3phase

Rated voltage 24kV

Rated frequency 60Hz

Rated current 630A

RatingMechanical durability 1,000 times

Electricaldurability E1

Rating Short time current

Virtual value 20kA

Peak 52kA

Time 1sec

Ratedmaking current

Virtual value 20kA

Peak 52kA

Rated switching capacity

Load break current 630A

Loop breaking current 630A

breaking current 16A

charging breaking current 1.5A

Frequency withstand voltage

Between earth 50kV (1min)

Between pole 60kV (1min)

Impulse withstand voltage

Between earth 125kV (1min)

Between pole 145kV (1min)

Operation method Manual / Auto

Rated control voltage AC/DC 110V / 220V

Weight 55kg 75kg

Distance between phases 300

LBS Rating

Page 9: Load Break Switch / Auto Section Switch

I 9

Service condition• Ambient temperature: up to 40 ℃ / lowest -20 ℃• Altitude: 1,000m or below• Installation location: Indoor• Installation method: vertical and horizontal

Rating

TypeLSJ-J-M-25-2-S LSJ-J-M-25-2-F

Standard type Fuse type

Phase No. 25.8kV

Rated frequency 60Hz

Rated current 200A

Frequency withstand voltage

Between conducting part & earth (1min) 50kv

Between fault conducting parts (1min) 50kv

Between in-phase terminals (1min) 60kv

Rating Short time current

Between conducting part& earth (1min) 125kA

Between fault conducting parts (1min) 125kA

Between in-phase terminals (1min) 145kA.

Ratedmaking current

Instantaneous (Asym) 15kA

1sec (sym) 10kA

10sec (sym) 3.5kA

Rated making current (Asym) 15ka(kAp)

Loop breaking current 900a

Minimum operating current

Phase (A) 10/20/30/50/70/100/140/200/BLOCK

Ground (A) 5/10/15/25/35/50/70/100/BY-PASS

Lock current of maximum overcurrent 800a

Insulating medium Standard

Operating voltageClose DC 24V

Open DC 24V

Weight 78kg(Standard type).

97kg(Fuse tilted type).

106kg(Fuse vertical type) 3kg (Control box)

Input voltage AC 220V (for battery charging)

Operating method Electric or manual

Applicable standard KEMC 1126(2007.8.22)

ASS Rating

Page 10: Load Break Switch / Auto Section Switch

10 I

Load Break Switch / Auto Section SwitchLBS control circuit

▶ For control voltage, AC/DC 110V is standard. AC/DC 220V is also available by your order.

CONNECTOR (FIXED-LBS BODY)

“A”(AUX. S/W CONTACT : 2A2B)

“B”(AUX. S/W CONTACT : 4A4B-OPTION)

21 20

11 10 9 8 7 6 5 4 3 2 1

19 18

40 39 38

17

37

30 29 28 27

16 15 14 13 12

CIRCUIT DIAGRAMAUXILIARY SWITCH

SHUNTCOIL RELAY MOTOR

11

F1 B7 B5 B3 B1 A7 A5 A3

OFF ON

A1

F2 B8 B6 B4 B2 A8 A6 A4 A2

21

30

40 39 20 19 38 37 18 17 2

29 10 28 13 12279 8 7 1

T

N

C P

P ① : DC+, AC 110/220V

N ② : DC-, AC 110/220V

C ⑫ : DC+, CLOSING

T ⑬ : DC+, OPENING

A1⑦-A2⑰, A3⑥-A4⑱, A5-A6, A7-A8 : AUX S/W "A" CONTACT

B1⑨-B2⑲, B2⑩-B4⑳, B5-B6 , B7-B8 : AUX S/W "B" CONTACT

F1⑪-F2 : FUSE TRIP CONTACT

Page 11: Load Break Switch / Auto Section Switch

I 11

Time-Current Curve

Phase current and ground current setting table

▶ Phase current = (contract capacity/(√3×22.9kV))×(2~3) ▶ Ground current is set to 1/2 of the phase current.

9.0

GROUND

PHASE

8.07.06.05.04.0

3.0

2.0

1.00.90.8

0.60.50.4

0.3

0.2

0.1

100

110

150

200

300

400

450

500

600

700

800

900

1000

2000

Tim

e (s

ec)

Rated Current (%)

Controller

Operation display lamp

RESET button

RESET buttonInput PUSH button

Phase current correction button

Lamp indicator button

Ground fault selection correction button

External powerdisplay light

Inrush current limit time correction tab

Power button

ASS control operation and performance

Transformer capacity Phase current tap (A) Ground fault current Phase current Ground fault current0-10 10 5 0-7.5 0-3.8

10-250 20 10 7.5-18.75 3.8-9.4251-350 30 15 18.75-26.25 9.4-13.2351-600 50 25 26.25-45 13.2-22.5601-900 70 35 45-68 22.5-34901-1000 100 50 68-75 34-37.5

1001-1500 140 70 75-113 37.5-56.51501-2000 200 100 113-150 56.5-75

Remarks • BLOCL : Open suppression tap by phase current.• BYPASS : Open suppression tap by ground fault current.

Page 12: Load Break Switch / Auto Section Switch

12 I

Load Break Switch / Auto Section Switch

Ø45

Ø7

B

33 33 30A

Fuse selection table

LBS fuse selected list

Fuse Link Fuse Holder

TypeRated voltage

(kV)

Rated current

(A)

Dimensions(mm) Weight

(kg)

Loop breaking current(kArms)

Minimum breaking current

(In)

TypeRated

voltage(kV)

Rated current

(A)

Insulation class(BIL)A B

LFL-20G-5B

24

5

442

55 2

405

LFH-20G-D2HB 24 200 125

LFL-20G-10B 10

LFL-20G-16B 16

LFL-20G-20B 20

LFL-20G-25B 25

77 4.2

LFL-20G-30B 30

LFL-20G-40B 40

LFL-20G-50B 50

LFL-20G-60B 63

LFL-20G-75C 7587 5.1 25

LFL-20G-100C 100 6

Page 13: Load Break Switch / Auto Section Switch

I 13

ø35

4-ø8

P.C.D 52

200 14

3

FLEXIBLE CABLE

MANUAL HANDLEOPERATING TURN RIGHT

FIXED FRAME

FREE ANGLE

MOUNTING HOLE(MANUAL HANDLE)

P.C.D 52

FLEXIBLE CABLEMANUAL HANDLEOPERATING TURN RIGHT

FIXED FRAME

(MANUAL HANDLE)

ADJUSTABLE DIMENSION

MOUNTING HOLE

2�� ���

VertManual operating device

HorizontalManual operating device

LBS installation method

Page 14: Load Break Switch / Auto Section Switch

14 I

Load Break Switch / Auto Section Switch

Unit:(mm)

P.C.D 52

20

118.5

10

8A

300300

750 160

910

(402)

(609)

2020

590

580

R14

3

257

PANNEL CUTTING DETAIL "A" SIZE TOLERANCE :

700(CUBICLE MOUNTING HOLES)53

0(C

UB

ICLE

MO

UN

TIN

G H

OLE

S)

700(CUBICLE MOUNTING HOLES)

HANDLE OPERATION ASS'Y

(530

)BU

SBAR

MO

UN

TIN

G H

OLE

S

40

P.C.D 52

20

B

A300

750 160

910

300

40

R143

22.5

27.5

1137

.5

20

(110

5)

20

35

20

MIN. R150

10

8

(605)

(402)

(258)

PANNEL CUTTING DETAIL "A" DETAIL "B" SIZE TOLERANCE :

700(CUBICLE MOUNTING HOLES)

530(

CUBI

CLE

MOU

NTIN

G HO

LES)

557.

5(CU

BICL

E M

OUNT

ING

HOLE

S)

700(CUBICLE MOUNTING HOLES)

(106

5)BU

SBAR

MO

UN

TIN

G H

OLE

S

HANDLE OPERATION ASS'Y

LSJ-L-M-24-6-F-0

LSJ-L-M-24-6-S-0

LBS Dimensions

Page 15: Load Break Switch / Auto Section Switch

I 15

PCDø52

100±2

Panel processing dimension (Controller)

Upper termial Lower termial

Panel processingdimension (Cable)

700(CUBICLE MOUNTING HOLES)

910

700

MAIN BODY

580

530(C

UBIC

LE M

OUNT

ING

HOL

ES)

27.5

530

20 15

22.5

178

190±

2

750 160

75

FRAME

300 300

25

150

118.5

75

40

200

R143

HANDLE

50

25

3-ø10

4-ø15

4-ø8

ø35

ø14 ø13

4-ø13

3-ø13

4-ø6.5

t=8 t=8

4-ø8

PCDø52

ø35

20 20

ø13ø14

6-ø13

3-ø1475

118.5

40 35

MAIN BODY

257525

FRAME200

R143

HANDLE

4-ø6.5

3-ø13

6-ø15

100±2

190±

217

8

700(CUBICLE MOUNTING HOLES)

530

(CUB

ICLE

MOU

NTIN

G H

OLES

)

358(

MOU

NTIN

G H

OLES

)

150

910

700

940

27.5

530

358

24.5

300 300

750 160

t=8 t=6

Panel processing dimension (Controller)

Upper termial Lower termial

Panel processingdimension (Cable)

4-ø6.5 FRAME100±2

2575

2575

4-ø8 PCDø52

ø35

6-ø15

3-ø13

6-ø13

ø14 ø13

MAIN BODY

HANDLE

700(CUBICLE MOUNTING HOLES)

530

(CUB

ICLE

MOU

NTIN

G H

OLES

)

177.

5(M

OUNT

ING

HOL

ES)

200

150R143

t=8

40

700

118.5

910750

300 300

160

20 1553

0

27.5

75

810

178

35

t=6

190±

217

8

Panel processing dimension (Controller)

Upper termial Lower termial

Panel processingdimension (Cable)

Unit:(mm)

Standard typeLSJ-J-M-25-2-S

Fuse type (Vertical)LSJ-J-M-25-2-F1

Fuse type (Tilted)LSJ-J-M-25-2-F2

ASS installation method

Page 16: Load Break Switch / Auto Section Switch

16 I

Load Break Switch / Auto Section Switch

(603)

257

402

910

750 160

(485)

8

(588

)

580

27.5

22.5

580

1520

8118.5

300 300 25

75 75

25

4-ø153-ø13

3-ø14

700(CUBICLE MOUNTING HOLES)

530(

CU

BIC

LE M

OU

NTI

NG

HO

LES)

(553

(BU

S BA

R M

OU

NTI

NG

HO

LES)

)

910

300 300

750

27.5

(104

6)

(111

3)

24.5

1520

940

160

25

75

215

402

(693)

(756)

8

6

118.5

25

753-ø14

6-ø15

3-ø13

530

(CUB

ICLE

MO

UNTI

NG H

OLE

S)

358(

MO

UNTI

NG H

OLE

S)

(101

1(BU

S BA

R M

OU

NTI

NG

HO

LES)

)

700(CUBICLE MOUNTING HOLES)

910

(701)

402

806

8

(650)

810

(107

1)

(113

8)

27.5

20

75

750

300 300

160

25

75

118.5

25

75

6-ø15

3-ø13

530

(CUB

ICLE

MO

UNTI

NG H

OLE

S)

177.

5 (M

OUN

TING

HO

LES)

(103

6(BU

S BA

R M

OU

NTI

NG

HO

LES)

)

700(CUBICLE MOUNTING HOLES)

Unit:(mm)

Standard typeLSJ-J-M-25-2-S

Fuse type (Vertical)LSJ-J-M-25-2-F1

Fuse type (Tilted)LSJ-J-M-25-2-F2

ASS Dimensions

Page 17: Load Break Switch / Auto Section Switch
Page 18: Load Break Switch / Auto Section Switch
Page 19: Load Break Switch / Auto Section Switch
Page 20: Load Break Switch / Auto Section Switch
Page 21: Load Break Switch / Auto Section Switch

I 21

Memo

Page 22: Load Break Switch / Auto Section Switch

22 I

Load Break Switch / Auto Section SwitchMemo

Page 23: Load Break Switch / Auto Section Switch

I 23

Memo

Page 24: Load Break Switch / Auto Section Switch

•For your safety, please read user's manual thoroughly before operating.

•Contact the nearest authorized service facility for examination, repair, or adjustment.

•�Please contact qualified service technician when you need maintenance. Do not disassemble or repair by yourself!

•Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions

Specifications in this catalog are subject to change without notice due to continuous product development and improvement.

Overseas Branches

•LSIS Co., Ltd. Rep. Office, VietnamGema Dept Tower 18F, 6 Le Thanh Ton, District 1, HCM, VietnamTel: 84-8-3823-7890 E-mail: [email protected]

•LSIS Moscow Office, Russia123610, Krasnopresnenskaya, nab, 12, building1, office No.1005, Moscow, RussiaTel: 7-495-258-1466, 1467 Fax: 7-495-258-1466, 1467 E-mail: [email protected]

■ HEAD OFFICE

LS-ro 127 (Hogye-dong) Dongan-gu, Anyang-si, Gyeonggi-Do KoreaTel. 82-2-2034-4902, 4684, 4429Fax. 82-2-2034-4555

Overseas Subsidiaries

•LSIS USA Inc. ≫ Chicago, America2000 Millbrook Drive, Lincolnshire, Chicago, IL 60069, United States of AmericaTel: 1-847-941-8240 Fax: 1-847-941-8259 E-mail: [email protected]

•LSIS (Middle East) FZE ≫ Dubai, U.A.E.LOB 19-205, JAFZA View Tower, Jebel Ali Free Zone, Dubai, United Arab EmiratesTel: 971-4-886-5360 Fax: 971-4-886-5361 E-mail: [email protected]

•LSIS Europe B.V. ≫ Schiphol-Rijk, Netherlands1st Floor, Tupoleviaan 48, 1119NZ, Schiphol-Rijk, The NetherlandsTel: 31-20-654-1420 Fax: 31-20-654-1429 E-mail: [email protected]

•LSIS Japan Co., Ltd. ≫ Tokyo, JapanTokyo Club Building 13F, 2-6, Kasumigaseki 3-chome, Chiyoda-ku, Tokyo, 100-0013Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-mail: [email protected]

•LSIS(Dalian) Co., Ltd. ≫ Dalian, ChinaNo. 15, Liaohexi 3-Road, Economic and Technical Development Zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 E-mail: [email protected]

• LS IS(Wuxi) Co., Ltd. ≫ WUxi, China102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 E-mail: [email protected]

•LS-Vina Co., Ltd. ≫ Hanoi, VietnamNguyen Khe, Dong Anh, Hanoi, VietnamTel: 84-4-6275-8055 Fax: 84-4-3882-0220 E-mail: [email protected]

■ GLOBAL NETWORK

LOAD BREAK SWITCH / AUTO SECTION SWITCH (E) 2016. 08/(01) 2016. 11 Printed in Korea STAFF2016. 11

www.lsis.comⓒ 2016. 08 LSIS Co.,Ltd. All rights reserved.


Recommended