LOCAL GOVERNMENT ENERGY AUDIT PROGRAM: ENERGY AUDIT REPORT PREPARED FOR: ATLANTIC COUNTY SPECIAL SERVICES SCHOOL DISTRICT 4805 NAWAKWA BOULEVARD MAYS LANDING, NJ 08330 ATTN: MS. LISA MOONEY BOARD SECRETARY/ADMINISTRATOR PREPARED BY: CONCORD ENGINEERING GROUP 520 S. BURNT MILL ROAD VOORHEES, NJ 08043 TELEPHONE: (856) 427-0200 FACSIMILE: (856) 427-6529 WWW.CEG-INC.NET CEG CONTACT: KEVIN BLANKENBUEHLER ME, DIRECTOR OF ENERGY SERVICES EMAIL: KBLANK@CONCORD- ENGINEERING.COM REPORT ISSUANCE: FINAL, NOVEMBER 4, 2011 PROJECT NO: 9C11036
Transcript
Page 1: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

LOCAL GOVERNMENT ENERGY AUDIT PROGRAM: ENERGY AUDIT REPORT

PREPARED FOR: ATLANTIC COUNTY SPECIAL

SERVICES SCHOOL DISTRICT 4805 NAWAKWA BOULEVARD MAYS LANDING, NJ 08330 ATTN: MS. LISA MOONEY BOARD SECRETARY/ADMINISTRATOR

PREPARED BY: CONCORD ENGINEERING GROUP

520 S. BURNT MILL ROAD VOORHEES, NJ 08043 TELEPHONE: (856) 427-0200 FACSIMILE: (856) 427-6529

WWW.CEG-INC.NET

CEG CONTACT: KEVIN BLANKENBUEHLER

ME, DIRECTOR OF ENERGY SERVICES EMAIL: [email protected]

REPORT ISSUANCE: FINAL, NOVEMBER 4, 2011

PROJECT NO: 9C11036

Page 2: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 1 of 60

TABLE OF CONTENTS

I.  EXECUTIVE SUMMARY ................................................................................................. 3 

II.  INTRODUCTION ............................................................................................................... 7 

III.  METHOD OF ANALYSIS.................................................................................................. 8 

IV.  HISTORIC ENERGY CONSUMPTION/COST ............................................................... 10 

A. ENERGY USAGE / TARIFFS .................................................................................................. 10

B. ENERGY USE INDEX (EUI) .................................................................................................. 15

C. EPA ENERGY BENCHMARKING SYSTEM ............................................................................. 17

V.  FACILITY DESCRIPTION .............................................................................................. 18 

VI.  MAJOR EQUIPMENT LIST ............................................................................................ 21 

VII.  ENERGY CONSERVATION MEASURES ..................................................................... 22 

VIII.  RENEWABLE/DISTRIBUTED ENERGY MEASURES ................................................ 48 

IX.  ENERGY PURCHASING AND PROCUREMENT STRATEGY .................................. 51 

X.  INSTALLATION FUNDING OPTIONS.......................................................................... 56 

XI.  ADDITIONAL RECOMMENDATIONS ......................................................................... 59 

Appendix A – ECM Cost & Savings Breakdown

Appendix B – New Jersey Smart Start® Program Incentives

Appendix C – Portfolio Manager “Statement of Energy Performance”

Appendix D – Major Equipment List

Appendix E – Investment Grade Lighting Audit

Appendix F – Renewable / Distributed Energy Measures Calculations

Appendix G – Duct Insulation Calculations

Page 3: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 2 of 60

REPORT DISCLAIMER

The information contained within this report, including any attachment(s), is intended solely for use by the named addressee(s). If you are not the intended recipient, or a person designated as responsible for delivering such messages to the intended recipient, you are not authorized to disclose, copy, distribute or retain this report, in whole or in part, without written authorization from Concord Engineering Group, Inc., 520 S. Burnt Mill Road, Voorhees, NJ 08043.

This report may contain proprietary, confidential or privileged information. If you have received this report in error, please notify the sender immediately. Thank you for your anticipated cooperation.

Page 4: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 3 of 60

I. EXECUTIVE SUMMARY

This report presents the findings of the energy audit conducted for:

Atlantic County Special Services School District Atlantic County Special Services School 4805 Nawakwa Boulevard Mays Landing, NJ 08330 Municipal Contact Person: Lisa Mooney

Facility Contact Person: Mike Alvare This audit is performed in connection with the New Jersey Clean Energy - Local Government Energy Audit Program for the Atlantic County Special Services School. The purpose of this analysis is to provide the owner insight into the energy savings potential that exists within the facility at the Atlantic County Special Services School. Energy Efficiency changes and upgrades requires support from the building occupants, operations personnel and the administrators of the building in order to maximize the savings and overall benefit. The efficiency improvement of public buildings provides a benefit for the environment and the residence of New Jersey. Through this report it has been demonstrated that there is a great potential for energy savings and infrastructure improvements at Atlantic County Special Services School. The Energy Conservation Measures (ECMs) identified within the report represent the potential annual savings at the facility. It is recommended to consider all ECMs as part of the District’s initiative to save energy, reduce emissions, and lower operating costs. Concord Engineering Group (CEG) recommends proceeding with the implementation of all ECM’s that provide a calculated simple payback at or under ten (10) years. The annual energy costs at this facility are as follows: The potential annual energy cost savings for each energy conservation measure (ECM) and renewable energy measure (REM) are shown below in Table 1. Be aware that the ECM’s and REM’s are not additive because of the interrelation of some of the measures. This audit is consistent with an ASHRAE level 2 audit. The cost and savings for each measure is ± 20%. The evaluations are based on engineering estimations and industry standard calculation methods. More detailed analyses would require engineering simulation models, hard equipment specifications, and contractor bid pricing.

Electricity $ 348,274

Natural Gas $ 37,074

Total $ 385,348

Page 5: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 4 of 60

Table 1 Financial Summary Table

ECM #1 Lighting Controls Upgrade $35,275 $4,169 8.5 77.3%

ECM #2 Condensing Boiler Upgrade $154,978 $4,611 33.6 -28.6%

ECM #3VFD on Chilled Water

Pumps$112,860 $2,740 41.2 -63.6%

ECM #4 Vending Miser Controls $358 $548 0.7 2194.2%

ECM #5 Demand Control Ventilation $41,364 $2,073 20.0 -24.8%

ECM #6 Refrigeration Controls $3,707 $770 4.8 211.4%

ECM #7Boiler Fuel Economizer

Controls$8,000 $1,090 7.3 104.4%

ECM #8 Geothermal Bore Field $4,243,000 $24,562 172.7 -85.5%

ECM #9 Duct Insulation $35,000 $649 53.9 -72.2%

Notes: A. Cost takes into consideration applicable NJ Smart StartTM incentives.B. Savings takes into consideration applicable maintenance savings.

ANNUAL

SAVINGSB

NET INSTALLATION

COSTA

ECM NO.

ECM NO.

DESCRIPTIONSIMPLE

PAYBACK (Yrs)

SIMPLE LIFETIME

ROI

ENERGY CONSERVATION MEASURES (ECM's)

The estimated demand and energy savings for each ECM and REM is shown below in Table 2. The descriptions in this table correspond to the ECM’s and REM’s listed in Table 1.

Page 6: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 5 of 60

Table 2 Estimated Energy Savings Summary Table

ECM #1 Lighting Controls Upgrade 16.7 30,432 0

ECM #2 Condensing Boiler Upgrade 0 0 1,249

ECM #3VFD on Chilled Water

Pumps0.0 20,000 0

ECM #4 Vending Miser Controls 0.0 3,997 0

ECM #5 Demand Control Ventilation 0.0 9,990 546

ECM #6 Refrigeration Controls 0.0 5,618 0

ECM #7Boiler Fuel Economizer

Controls0.0 0 845

ECM #8 Geothermal Bore Field 0.0 47,820 13,934

ECM #9 Duct Insulation 0.0 1,252 370

NATURAL GAS (THERMS)

ECM NO.

DESCRIPTION

ANNUAL UTILITY REDUCTION

ENERGY CONSERVATION MEASURES (ECM's)ENERGY CONSERVATION MEASURES (ECM's)

ELECTRIC DEMAND

(KW)

ELECTRIC CONSUMPTION

(KWH)

Renewable Energy Conservation Measures: The Atlantic County Special Services School has a total estimated solar system potential of 615.94 kW DC that could generate 710,235 kilowatt-hours annually offsetting 28% of the total energy purchased from the grid. Solar is an economically viable option for the District to pursue, using either existing financing methods or alternative routes, such as a Power Purchase. The District is in fact currently pursuing a Power Purchase option for solar at its facility. Energy Procurement Recommendations: CEG recommends that the Atlantic County Special Services School utilize the advisement of 3rd party unbiased Energy Consulting Firm experienced in the procurement of retail natural gas and electricity commodity and negotiation of contract terms and conditions. Further recommendations are outlined in the Energy Procurement Section of this report that could assist the District in finding additional savings through their utility bills.

Page 7: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 6 of 60

Maintenance and Operational Recommendations: In addition to the ECMs and REMs, there are maintenance and operational measures that can provide significant energy savings and provide immediate benefit. The ECMs listed above represent investments that can be made to the facility which are justified by the savings seen overtime. However, the maintenance items and small operational improvements below are typically achievable with on site staff or maintenance contractors and in turn have the potential to provide substantial operational savings compared to the costs associated. The following are recommendations which should be considered a priority in achieving an energy efficient building and further recommendations for the building are provided in the building reports:

1. Chemically clean the condenser and evaporator coils periodically to optimize efficiency. Poorly maintained heat transfer surfaces can reduce efficiency 5-10%.

2. Maintain all weather stripping on windows and doors. 3. Clean all light fixtures to maximize light output. 4. Provide more frequent air filter changes to decrease overall system power usage and

maintain better IAQ. 5. Verify all thermostats are utilizing setback and scheduling capabilities. 6. Confirm that outside air economizers on the rooftop units are functioning properly to

take advantage of free cooling and avoid excess outside air during occupied periods. 7. Educate staff and students on awareness of wasteful energy practices such as leaving

lights on unnecessarily, leaving on of non-essential computer and/or equipment at the end of the day, leaving of outside doors/windows open as a means to control room temperature, etc.

Implementation Strategy Moving Forward: It is recommended the District strongly consider all projects with a simple payback of ten years and under for implementation. However consideration should be taken on projects over ten years as they may be necessary capital improvements. The District should also consider pursuing any and all additional NJ Clean Energy Programs in order to receive the maximum incentives available. Furthermore, although individual projects with a simple payback of 10 years and less are considered financially self sustaining, it is important to consider how multiple projects can be combined together. When ECMs are aggregated into a single project, the lower cost ECMs provides valuable savings to offset the higher cost ECMs. Likewise when multiple facilities are aggregated together into a single entity energy efficiency project, the same benefits are seen on a larger scale. Overall Assessment: Overall, the Atlantic County Special Services School is well maintained and operated efficiently. Through the implementation of measures outlined in this study and improving overall operational efficiency it is likely the District has potential to further reduce its total energy cost of $385,348 by approximately 2.2%.

Page 8: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 7 of 60

II. INTRODUCTION

The comprehensive energy audit covers the 177,000 square foot Atlantic County Special Services School, which includes the following spaces: classrooms, multi-purpose rooms, specialized learning rooms, gymnasiums and offices. Electrical and natural gas utility information is collected and analyzed for one full year’s energy use of the building. The utility information allows for analysis of the building’s operational characteristics; calculate energy benchmarks for comparison to industry averages, estimated savings potential, and baseline usage/cost to monitor the effectiveness of implemented measures. A computer spreadsheet is used to calculate benchmarks and to graph utility information (see the utility profiles below). The Energy Use Index (EUI) is established for the building. Energy Use Index (EUI) is expressed in British Thermal Units/square foot/year (BTU/ft2/yr), which is used to compare energy consumption to similar building types or to track consumption from year to year in the same building. The EUI is calculated by converting the annual consumption of all energy sources to BTU’s and dividing by the area (gross square footage) of the building. Blueprints (where available) are utilized to verify the gross area of the facility. The EUI is a good indicator of the relative potential for energy savings. A low EUI indicates less potential for energy savings, while a high EUI indicates poor building performance therefore a high potential for energy savings. Existing building architectural and engineering drawings (where available) are utilized for additional background information. The building envelope, lighting systems, HVAC equipment, and controls information gathered from building drawings allow for a more accurate and detailed review of the building. The information is compared to the energy usage profiles developed from utility data. Through the review of the architectural and engineering drawings a building profile can be defined that documents building age, type, usage, major energy consuming equipment or systems, etc. The preliminary audit information is gathered in preparation for the site survey. The site survey provides critical information in deciphering where energy is spent and opportunities exist within a facility. The entire site is surveyed to inventory the following to gain an understanding of how each facility operates:

Building envelope (roof, windows, etc.) Heating, ventilation, and air conditioning equipment (HVAC) Lighting systems and controls Facility-specific equipment

The building site visit is performed to survey all major building components and systems. The site visit includes detailed inspection of energy consuming components. Summary of building occupancy schedules, operating and maintenance practices, and energy management programs provided by the building manager are collected along with the system and components to determine a more accurate impact on energy consumption.

Page 9: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 8 of 60

III. METHOD OF ANALYSIS

Post site visit work includes evaluation of the information gathered, researching possible conservation opportunities, organizing the audit into a comprehensive report, and making recommendations on HVAC, lighting and building envelope improvements. Data collected is processed using energy engineering calculations to anticipate energy usage for each of the proposed energy conservation measures (ECMs). The actual building’s energy usage is entered directly from the utility bills provided by the District. The anticipated energy usage is compared to the historical data to determine energy savings for the proposed ECMs. It is pertinent to note, that the savings noted in this report are not additive. The savings for each recommendation is calculated as standalone energy conservation measures. Implementation of more than one ECM may in some cases affect the savings of each ECM. The savings may in some cases be relatively higher if an individual ECM is implemented in lieu of multiple recommended ECMs. For example implementing reduced operating schedules for inefficient lighting will result in a greater relative savings. Implementing reduced operating schedules for newly installed efficient lighting will result in a lower relative savings, because there is less energy to be saved. If multiple ECM’s are recommended to be implemented, the combined savings is calculated and identified appropriately. ECMs are determined by identifying the building’s unique properties and deciphering the most beneficial energy saving measures available that meet the specific needs of the facility. The building construction type, function, operational schedule, existing conditions, and foreseen future plans are critical in the evaluation and final recommendations. Energy savings are calculated base on industry standard methods and engineering estimations. Energy consumption is calculated based on manufacturer’s cataloged information when new equipment is proposed. Cost savings are calculated based on the actual historical energy costs for the facility. Installation costs include labor and equipment costs to estimate the full up-front investment required to implement a change. Costs are derived from Means Cost Data, industry publications, and local contractors and equipment suppliers. The NJ Smart Start Building® program incentives savings (where applicable) are included for the appropriate ECM’s and subtracted from the installed cost. Maintenance savings are calculated where applicable and added to the energy savings for each ECM. The life-time for each ECM is estimated based on the typical life of the equipment being replaced or altered. The costs and savings are applied and a simple payback, simple lifetime savings, and simple return on investment are calculated. See below for calculation methods:

Page 10: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 9 of 60

ECM Calculation Equations:

SavingsYearly

CostNetPaybackSimple

LifetimeECMSavingsYearlySavingsLifetimeSimple

CostNet

CostNetSavingsLifetimeSimpleROILifetimeSimple

)(

LifetimeECMSavingseMaintenancYearlySavingseMaintenancLifetime

N

0nnIRR1

PeriodofFlowCashReturnofRateInternal

N

0nnDR1

PeriodofFlowCashValuePresentNet

Net Present Value calculations based on Interest Rate of 3%.

Page 11: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 10 of 60

IV. HISTORIC ENERGY CONSUMPTION/COST A. Energy Usage / Tariffs The energy usage for the facility has been tabulated and plotted in graph form as depicted within this section. Each energy source has been identified and monthly consumption and cost noted per the information provided by the District. The electric usage profile represents the actual electrical usage for the facility. Atlantic City Electric (ACE) provides electricity to the facility under their Annual General Service rate structure. A Third Part Supplier (TPS) has not been contracted. The electric utility measures consumption in kilowatt-hours (KWH) and maximum demand in kilowatts (KW). One KWH usage is equivalent to 1000 watts running for one hour. One KW of electric demand is equivalent to 1000 watts running at any given time. The basic usage charges are shown as generation service and delivery charges along with several non-utility generation charges. Rates used in this report reflect the historical data received for the facility. The gas usage profile shows the actual natural gas energy usage for the facility. South Jersey Natural Gas (SJG) provides natural gas to the facility under the General Service Gas (GSG) rate structure. A Third Part Supplier (TPS) has not been contracted. The gas utility measures consumption in cubic feet x 100 (CCF), and converts the quantity into Therms of energy. One Therm is equivalent to 100,000 BTUs of energy. The overall cost for utilities is calculated by dividing the total cost by the total usage. Based on the utility history provided, the average cost for utilities at this facility is as follows: Description Average

Electricity 13.7¢ / kWh Natural Gas $1.29 / Therm

Page 12: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 11 of 60

Table 3 Electricity Billing Data

Utility Provider: Atlantic City ElectricRate: AGS

Meter No: 86422434Account # 1134808-9996-3

Third Party Utility N/ATPS Meter / Acct No: N/A

MONTH OF USECONSUMPTION

KWHTOTAL BILL

Jan-11 169,897 $25,355

Dec-10 176,431 $24,733

Nov-10 202,925 $28,569

Oct-10 219,601 $30,306

Sep-10 286,197 $38,217

Aug-10 271,613 $36,066

Jul-10 283,265 $37,896

Jun-10 254,053 $34,436

May-10 198,894 $27,048

Apr-10 148,579 $20,522

Mar-10 166,140 $22,672

Feb-10 166,066 $22,456

Totals 2,543,661 746.7 Max $348,274

AVERAGE DEMAND 606.0 KW average

AVERAGE RATE $0.137 $/kWh

470.0

467.4

675.9

746.7

716.6

694.1

556.6

619.4

672.7

670.3

ELECTRIC USAGE SUMMARY

DEMAND KW

494.0

488.9

Page 13: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 12 of 60

Figure 1 Electricity Usage Profile

Page 14: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 13 of 60

Table 4 Natural Gas Billing Data

Utility Provider: South Jersey GasRate: GSG

Meter No: N/AAccount Number: 1-18-38-0353-1-6

Third Party Utility Provider: N/ATPS Meter No:

MONTH OF USECONSUMPTION

(THERMS)TOTAL BILL

Jan-11 7,327.00 $8,424.54

Dec-10 3,398.00 $7,383.90

Nov-10 1,354.00 $1,509.17

Oct-10 238.00 $265.53

Sep-10 21.00 $41.00

Aug-10 92.00 $135.52

Jul-10 104.00 $128.11

Jun-10 558.00 $602.66

May-10 933.00 $955.66

Apr-10 2,400.00 $2,634.29

Mar-10 3,318.00 $3,829.95

Feb-10 9,019.00 $11,163.98

TOTALS 28,762.00 $37,074.31

AVERAGE RATE: $1.29 $/THERM

N/A

NATURAL GAS USAGE SUMMARY

Page 15: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 14 of 60

Figure 2 Natural Gas Usage Profile

Page 16: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 15 of 60

B. Energy Use Index (EUI) Energy Use Index (EUI) is a measure of a building’s annual energy utilization per square foot of building. This calculation is completed by converting all utility usage consumed by a building for one year, to British Thermal Units (BTU) and dividing this number by the building square footage. EUI is a good measure of a building’s energy use and is utilized regularly for comparison of energy performance for similar building types. The Oak Ridge National Laboratory (ORNL) Buildings Technology Center under a contract with the U.S. Department of Energy maintains a Benchmarking Building Energy Performance Program. The ORNL website determines how a building’s energy use compares with similar facilities throughout the U.S. and in a specific region or state. Source use differs from site usage when comparing a building’s energy consumption with the national average. Site energy use is the energy consumed by the building at the building site only. Source energy use includes the site energy use as well as all of the losses to create and distribute the energy to the building. Source energy represents the total amount of raw fuel that is required to operate the building. It incorporates all transmission, delivery, and production losses, which allows for a complete assessment of energy efficiency in a building. The type of utility purchased has a substantial impact on the source energy use of a building. The EPA has determined that source energy is the most comparable unit for evaluation purposes and overall global impact. Both the site and source EUI ratings for the building are provided to understand and compare the differences in energy use. The site and source EUI for this facility is calculated as follows:

FootageSquareBuilding

kBtuinUsageGaskBtuinUsageElectricEUISiteBuilding

)(

FootageSquareBuilding

RatioSSXkBtuinUsageGasRatioSSXkBtuinUsageElectricEUISourceBuilding

)(

Page 17: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 16 of 60

Table 5

Facility Energy Use Index (EUI) Calculation

kWh Therms Gallons kBtu kBtu

ELECTRIC 2,543,661.0 8,684,059 3.340 29,004,756

NATURAL GAS 28,762.0 2,876,200 1.047 3,011,381

TOTAL 11,560,259 32,016,137

BUILDING AREA 177,000 SQUARE FEET

BUILDING SITE EUI 65.31 kBtu/SF/YR

BUILDING SOURCE EUI 180.88 kBtu/SF/YR

ENERGY USE INTENSITY CALCULATION

ENERGY TYPESITE-

SOURCE RATIO

BUILDING USESITE

ENERGYSOURCE ENERGY

*Site - Source Ratio data is provided by the Energy Star Performance Rating Methodology for Incorporating Source Energy Use document issued Dec 2007.

Figure 3 below depicts a national EUI grading for the source use of Elemntary Schools.

Figure 3 Source Energy Use Intensity Distributions: Elementary Schools

SOURCE EUI = 180.9

Page 18: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 17 of 60

C. EPA Energy Benchmarking System The United States Environmental Protection Agency (EPA) in an effort to promote energy management has created a system for benchmarking energy use amongst various end users. The benchmarking tool utilized for this analysis is entitled Portfolio Manager. The Portfolio Manager tool allows tracking and assessment of energy consumption via the template forms located on the ENERGY STAR website (www.energystar.gov). The importance of benchmarking for local government municipalities is becoming more important as utility costs continue to increase and emphasis is being placed on carbon reduction, greenhouse gas emissions and other environmental impacts. Based on information gathered from the ENERGY STAR website, Government agencies spend more than $10 billion a year on energy to provide public services and meet constituent needs. Furthermore, energy use in commercial buildings and industrial facilities is responsible for more than 50 percent of U.S. carbon dioxide emissions. It is vital that local government municipalities assess facility energy usage, benchmark energy usage utilizing Portfolio Manager, set priorities and goals to lessen energy usage and move forward with priorities and goals. In accordance with the Local Government Energy Audit Program, CEG has created an ENERGY STAR account for the municipality to access and monitoring the facility’s yearly energy usage as it compares to facilities of similar type. The login page for the account can be accessed at the following web address; the username and password are also listed below:

https://www.energystar.gov/istar/pmpam/index.cfm?fuseaction=login.login User Name: Atlanticcountyss Password: lgeaceg2011 Security Question: What city were you born in? Security Answer: “atlantic county” The utility bills and other information gathered during the energy audit process are entered into the Portfolio Manager. The following is a summary of the results for the facility:

Table 6 ENERGY STAR Performance Rating

FACILITY DESCRIPTION

ENERGY PERFORMANCE

RATING

NATIONAL AVERAGE

ENERGY STAR PERFORMANCE RATING

Atlantic County Special Service School

22 50

Refer to Statement of Energy Performance Appendix for the detailed energy summary.

Page 19: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 18 of 60

V. FACILITY DESCRIPTION

The Atlantic County Special Services School is located on 4805 Nawakwa Boulevard in Mays Landing, New Jersey. The 177,000 SF school was built in 2003 with no recent renovations. The building is a single story facility comprised of classrooms, multi-purpose rooms, specialized learning rooms, gymnasiums and offices.

Occupancy Profile

The typical hours of operation for the school students and teachers are between 7:00 AM and 3:00 PM on the weekdays. The facility remains occupied until 10:00 PM for afterschool activities as well as the custodial services. The student enrollment at the Atlantic County Special Services School is approximately 459.

Building Envelope

Exterior walls for the Atlantic County Special Services School are brick faced with a concrete block construction. The amount of insulation within the walls is approximately 1½” rigid insulation.

The windows throughout the school are in good condition and appear to be maintained. Typical windows throughout the school are double pane, operable, ¼” tinted glass with aluminum frames. Blinds are utilized in the building for occupant comfort, and provide a minimal amount of solar heat gain in the summer months.

The roof is a flat, built up rubber roof where the HVAC equipment resides. The amount of insulation below the roofing ranges from 2” to 5” depending on the location and slope of the roof.

HVAC Systems

Heating Plant:

The heating plant is located in a penthouse mechanical room. The main boiler room consists of two Burnham PV1122 natural gas sectional boilers. These boilers provide all of the heating hot water for the school with an input of 5,485 MBH per boiler and an efficiency of 79%. The boilers there are in good condition and have approximately 5 years until the end of their useful service life.

The boiler room houses four Sterling Peerless end suction pumps. Two pumps designated to supplying sections A, B and C operate with a constant 10 HP motor with a flow rate of 223 GPM @ 100 ft head. The remaining two pumps are designated to supply sections D, E, F and G and operate with a constant 20 HP motor with a flow rate of 493 GPM @ 110 ft head. The pumps range in efficiency from 68% to 80% and have NEMA efficient rated motors. These pumps are 10 years old and are in good condition.

Page 20: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 19 of 60

Atlantic County Special Services School contains eight packaged rooftop units and split systems that provide both heating and cooling to the areas. Those systems and the areas that they serve are briefly summarized below.

Packaged Rooftop Units:

Trane Voyager units provide heating and cooling for the large spaces such as the gymnasiums, multi-purpose rooms, cafeteria and some of the nearby surrounding spaces. These rooftop units have cooling capacities that range from 5 tons to 15 tons and heating capacities that range from 130 MBH to 250 MBH. Most of the packaged rooftop units have an average EER of 11. These units are ten years old and within their useful service life.

Split Systems:

Mitsubishi Mr. Slim products are utilized in certain areas of the school that require a dedicated cooling system. Areas such as electrical closets with computer equipment or transformers will need a dedicated system when the chiller is offline during the winter months.

Cooling for the building is provided by a chilled water loop. A brief description of these units is provided below.

Chiller Plant:

A 410 ton Water Cooled Liquid Trane Chiller provides chilled water throughout the 4-pipe air system. The chiller has an efficiency of .52 KW/Ton. Providing condenser water to the liquid cooled chiller are three Marley cooling towers located on the roof above the chiller room. These cooling towers have a flow rate of 450 GPM and have 7.5 HP fan motors. The chiller and cooler tower are approximately ten years old and within their useful service life.

Airside Equipment:

Cooling for the entire building is provided by air handling units with chilled water and hot water coils. These Trane air handling units have a capacity ranging from 1.5 tons to 12 tons. These units are ten years old and within their useful service life.

Exhaust System

Air is exhausted from the toilet rooms through the roof exhausters. Roof exhaust systems operate 24 hours a day, 7 days a week.

Kitchen exhaust is provided by several Cook Company exhaust fans. Make-up air for the kitchen exhaust and hoods is provided by two gas fired Trane make-up air rooftop units. These units provide 600 to 800 MBH heating and have a supply CFM range of 4,000 to 13,500. The kitchen exhaust hoods are controlled via switches which are manually operated.

Page 21: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 20 of 60

HVAC System Controls

The building HVAC is controlled by a TRANE Tracer Summit™ Building Automation System which provides building control through a single, integrated system. The building's climate, energy consumption, scheduling, and other controllable features can all be programmed and managed by Tracer Summit building control units. Each area of the school is operated on a strict operating schedule from 3 AM to 11 PM. Summer operation temperature set-points are 71°F during occupied hours and 73°F during unoccupied hours. Winter operation temperature set-points are 72°F during occupied hours and 69°F during unoccupied hours.

Domestic Hot Water

Domestic hot water for the restrooms is provided by two 100 gallon A.O. Smith Cyclone XHE gas fired hot water heaters, capacity of 240 MBH. These hot water heaters have a thermal efficiency of 96% and are ten years old and within their useful life.

Domestic hot water for the kitchen areas is provided by one A.O. Smith Burkay Legend 2000 condensing gas fired hot water heater, capacity of 750 MBH. This hot water heater has a thermal efficiency of 90% and is only used during operating hours of the kitchen. The hot water boiler also has two AO Smith storage tanks rated at 200 gallons each.

Lighting Refer to the Investment Grade lighting Audit Appendix for a detailed list of the lighting throughout the facility and estimated operating hours per space.

Page 22: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 21 of 60

VI. MAJOR EQUIPMENT LIST

The equipment list contains major energy consuming equipment that through implementation of energy conservation measures could yield substantial energy savings. The list shows the major equipment in the facility and all pertinent information utilized in energy savings calculations. An approximate age was assigned to the equipment in some cases if a manufactures date was not shown on the equipment’s nameplate. The ASHRAE service life for the equipment along with the remaining useful life is also shown in the Appendix.

Refer to the Major Equipment List Appendix for this facility.

Page 23: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 22 of 60

VII. ENERGY CONSERVATION MEASURES ECM #1: Lighting Controls Upgrade – Occupancy Sensors Description: Some of the lights in the Atlantic County Special Services School are left on unnecessarily. In many cases the lights are left on because of the inconvenience to manually switch lights off when a room is left or on when a room is first occupied. This is common in rooms that are occupied for only short periods and only a few times per day. In some instances lights are left on due to the misconception that it is better to keep the lights on rather than to continuously switch lights on and off. Although increased switching reduces lamp life, the energy savings outweigh the lamp replacement costs. The payback timeframe for when to turn the lights off is approximately two minutes. If the lights are expected to be off for at least a two minute interval, then it pays to shut them off.

Lighting controls come in many forms. Sometimes an additional switch is adequate to provide reduced lighting levels when full light output is not needed. Occupancy sensors detect motion and will switch the lights on when the room is occupied. Occupancy sensors can either be mounted in place of a current wall switch, or on the ceiling to cover large areas. The U.S. Department of Energy sponsored a study to analyze energy savings achieved through various types of building system controls. The referenced savings is based on the “Advanced Sensors and Controls for Building Applications: Market Assessment and Potential R&D Pathways,” document posted for public use April 2005. The study has found that commercial buildings have the potential to achieve significant energy savings through the use of building controls. The average energy savings are as follows based on the report:

Occupancy Sensors for Lighting Control 20% - 28% energy savings.

Savings resulting from the implementation of this ECM for energy management controls are estimated to be 20% of the total light energy controlled by occupancy sensors and daylight sensors (The majority of the savings is expected to be after school hours when rooms are left with lights on) This ECM includes installation of ceiling or switch mount sensors for individual offices, classrooms, large bathrooms, and libraries. Sensors shall be manufactured by Sensorswitch, Watt Stopper or equivalent. The Investment Grade Lighting Audit Appendix of this report includes the summary of lighting controls implemented in this ECM and outlines the proposed controls, costs, savings, and payback periods. The calculations adjust the lighting power usage by the applicable percent savings for each area that includes lighting controls. Energy Savings Calculations:

kWh/YrEnergyLightControlledSavings%SavingsEnergy

Page 24: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 23 of 60

kWh

$CostElecAvekWhSavingsEnergySavings.

Cost and Incentives:

Installation cost per dual-technology sensors (Basis: Sensor switch or equivalent) are as follows:

Dual Tech.Occupancy Sensor w/ (1) 2 Pole Powerpack - Remote Mnt. $450 per installation Cost includes material and labor. From the NJ Smart Start® Program Incentives Appendix, the installation of a lighting control device warrants the following incentive: Occupancy Sensor Fixture Mounted (existing facility only) = $20 per sensor Occupancy Sensor Remote Mounted (existing facility only) = $35 per sensor Energy Savings Summary:

Installation Cost ($): $38,250

NJ Smart Start Equipment Incentive ($): $2,975

Net Installation Cost ($): $35,275

Maintenance Savings ($/Yr): $0

Energy Savings ($/Yr): $4,169

Total Yearly Savings ($/Yr): $4,169

Estimated ECM Lifetime (Yr): 15

Simple Payback 8.5

Simple Lifetime ROI 77.3%

Simple Lifetime Maintenance Savings $0

Simple Lifetime Savings $62,535

Internal Rate of Return (IRR) 8%

Net Present Value (NPV) $14,494.25

ECM #1 - ENERGY SAVINGS SUMMARY

Page 25: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 24 of 60

ECM #2: Condensing Boiler Installation Description: The existing sectional boilers are used as the primary source of heat for the Atlantic County Special Services School. The existing boilers are approximately ten years old which is almost half the life expectancy for a typical sectional boiler, however the equipment appears to be maintained in good operating condition. Even for boilers that are close to the end of its life it is difficult to predict the point at which the boiler becomes inoperable. With the increased efficiency of the condensing boilers, the savings can be substantial. New condensing boilers could substantially improve the operating efficiency of the heating system of the building. Condensing boiler’s peak efficiency tops out at 99% depending on return water temperature. Due to the operating conditions of the building, the annual average operating efficiency of the proposed condensing boiler is expected to be 88%. The existing boiler’s efficiency is approximately 75%, which makes the condensing boilers 13% more efficient. This ECM is based on variable supply water temperature adjusted based on outdoor temperature. This ECM includes installation of two condensing gas fired boilers to replace the existing sectional boilers. The basis for this ECM is Aerco condensing boilers model number BMK 2.0LN-2. The boiler installation is based on a one for one replacement based on capacity of the existing boilers. The installed boilers will handle the load, but one existing sectional boiler will remain as an emergency back-up. Energy Savings Calculations: Total Gas Usage: 28,762 Therms Gas Rooftop Usage: 10,309 Therms Baseline Hot Water Gas Use: 10,000 Therms Existing Heating Natural Gas: 28,762 – (10,309 + 10,000) = 8,453 Therms (estimated)

Therm

BTUHeatValueFuelEffHeatingThermsGasNatExistingquiredHeatBldg %.Re

Therm

BTUValueHeatFuelEffHeating

BTUquiredHeatBldgUsageGasHeatingoposed

%.

RePr

Page 26: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 25 of 60

ThermCostFuelAveThermsUsageGasHeatingCostEnergy

$

From the NJ Smart Start Appendix, the installation of new condensing boilers warrants the following incentive: $1.00 per MBH. Additional maintenance savings for this ECM are estimated at $3,000/year. The facility replaced sections of the existing boiler for $15,000. The existing boilers have 15 years left on their useful service life therefore maintenance costs for replacing further sections on the two existing boilers is approximated at $3,000/year.

ECM INPUTS EXISTING PROPOSED SAVINGS

ECM INPUTSExisting Cast Iron

BoilersNew Condensing

Boilers

Existing Nat Gas (Therms) 8,453 0

Boiler Efficiency (%) 75% 88% 13%

Nat Gas Heat Value (BTU/Therm)

100,000 100,000

Equivalent Building Heat Usage (MMBTUs)

634 634

Gas Cost ($/Therm) 1.29 1.29

ECM RESULTS EXISTING PROPOSED SAVINGS

Natural Gas Usage (Therms) 8,453 7,204 1,249

Energy Cost ($) $10,904 $9,293 $1,611

COMMENTS:

CONDENSING BOILER CALCULATIONS

ENERGY SAVINGS CALCULATIONS

Page 27: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 26 of 60

Energy Savings Summary:

Installation Cost ($): $158,978

NJ Smart Start Equipment Incentive ($): $4,000

Net Installation Cost ($): $154,978

Maintenance Savings ($/Yr): $3,000

Energy Savings ($/Yr): $1,611

Total Yearly Savings ($/Yr): $4,611

Estimated ECM Lifetime (Yr): 24

Simple Payback 33.6

Simple Lifetime ROI -28.6%

Simple Lifetime Maintenance Savings $72,000

Simple Lifetime Savings $110,664

Internal Rate of Return (IRR) -3%

Net Present Value (NPV) ($76,888.22)

ECM #2 - ENERGY SAVINGS SUMMARY

Page 28: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 27 of 60

ECM #3: Install VFDs and Premium Efficiency Motors for Pumps Description: The cooling system at Atlantic County Special Services School utilizes constant speed pumps to circulate chilled water throughout the building. Based on the survey of the existing equipment it appears that all of the existing air handling units utilize 3-way control valves for flow control. 3-way control valves require full pumping energy continuously, while 2-way control valves allow the system to reduce flow when there is only a call for heating or cooling. This ECM includes the installation of Variable Frequency Drives on the existing chilled water pumps with modifications to the piping in order to cap 3-way valves and make them 2-way valves. The VFD’s would be controlled by a differential pressure sensor in each water loop to measure demand for water. The furthest air handling unit from the loop pumps would remain as a 3-way control valve (constant flow) to eliminate dead heading potential. This ECM also includes replacement of the existing pump motors with inverter duty motors that meet NEMA Premium Efficiency Standard, which also helps to reduce energy consumption. Energy Savings Calculations: Energy and cost savings calculations are based on calculation software “PumpSave v4.2,” provided by ABB. The PumpSave calculation software is used to estimate the pumping energy for variable speed pump systems. The chilled water loop pump operations are estimated to be 1,950 Hrs per year since the system is used for about 6 months total. The pump flow, HD, and resultant energy are calculated based on the existing pump horse power installed.

% EfficiencyMotor% EfficiencyPump3960

Ft Headmin

GalRateFlowGravitySpecific

HPPower VolumeCons.

Hrs.Operation HP

KW 0.746HPPower kWhCons.Energy

kWh

$CostElectricAvekWh UsageEnergyCostEnergy

Page 29: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 28 of 60

Chilled Water VFD Pumping Energy 10 HP Pumps:

4.2

En

erg

y s

avin

g c

alc

ula

tor

for

pu

mp

s

Liq

uid

de

nsi

ty62

lb/ft

³S

tati

c h

ea

d1

ft

Cal

cula

ted

by:

No

min

al

volu

me

flo

w31

0gp

mE

ffic

ien

cy

75%

Cal

cula

ted

fo

r:C

hille

d w

ater

pum

psP

um

p ID

:#1

, 2

No

min

al

he

ad

80ft

Ma

x h

ea

d

80ft

S

up

ply

vo

lta

ge

200/

208/

230/

240

V 3

-ph

Req

uire

d m

otor

pow

er:

M

oto

r p

ow

er

10H

p9.

2 H

pR

es

ult

sin

clud

ing

10%

saf

ety

mar

gin

M

oto

r e

ffic

ien

cy89

.5 %

Sa

vin

g p

erc

en

tag

e39

.1 %

An

nu

al e

ne

rgy

co

ns

um

pti

on

:

with

exi

stin

g co

ntro

l met

hod

15M

Wh

A

nn

ua

l ru

nn

ing

tim

e

2,90

0h

with

impr

oved

con

trol

met

hod

9M

Wh

An

nu

al

en

erg

y sa

vin

g6

MW

h

5%

=

145

h a

t no

m.

flow

An

nu

al

CO

2 re

du

ctio

n3

t

15%

=

435

h a

t 90

% fl

owC

O2 e

mis

sio

n/u

nit

0.5

lb/k

Wh

20%

=

580

h a

t 80

% fl

ow

30%

=

870

h a

t 70

% fl

owC

urr

en

cy u

nit

$

20%

=

580

h a

t 60

% fl

owE

ne

rgy

pri

ce0

$/kW

h

10%

=

290

h a

t ha

lf flo

wIn

vest

me

nt

cost

0$

An

nu

al

savi

ng

0$

0%

=

0 h

at

40%

flow

Inte

rest

ra

te4%

Pa

yba

ck p

eri

od

0.0

year

s

0%

=

0 h

at

30%

flow

Se

rvic

e l

ife

10ye

ars

Ne

t p

rese

nt

valu

e0

$

0%

=

0 h

at

20%

flow

100

0

AC

S55

0-U

1-03

1A-2

0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

2030

4050

6070

8090

100

Flo

w ra

te

Po

wer

(kW

)

Th

rott

ling

020

40

0

2,0

00

4,0

00

6,0

00

8,0

00

10

,00

0

12

,00

0

14

,00

0

16

,00

0

Th

rott

lin

gV

SD

En

erg

y C

on

su

me

d (

kW

h)

FLOW (gpm)

Ope

ratin

g Pr

ofile

Econ

omic

Dat

a

Impr

oved

Con

trol

by

ABB

Driv

e :

Mot

or a

nd S

uppl

y D

ata

Sen

d to

de

faul

t pr

inte

r

D E F A U L T

Pum

p D

ata

Syst

em D

ata

Thro

ttlin

g co

ntro

l

Aut

o-ad

just

sc

reen

siz

eC

lose

pro

gram

US

Me

tric

Mea

sure

men

t un

its

230

V (

3-ph

)

AC

S550

Co

py

toc

lipb

oa

rd

Exis

ting

flow

con

trol

met

hod

Sav

e ca

lcul

atio

n

?

?

Sys

tem

Dat

a

Pu

mp

Dat

a

Mo

tor

and

Su

pp

ly D

ata

Op

erat

ing

Pro

file

Eco

no

mic

Dat

a

Mea

sure

men

t U

nit

s

Eco

no

mic

Res

ult

s

En

erg

y C

on

sum

pti

on

Exi

stin

g F

low

Co

ntr

ol

Page 30: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 29 of 60

ECM INPUTS EXISTING PROPOSED SAVINGS

ECM INPUTS CV Pumps VFD Pumps

Flow ControlThrottling

Valves-2WayVFD -

Flow (GPM) 310 310 -

Head (Ft) 80 80 -

Pump Efficiency (%) 75% 75% -

Motor Efficiency (%) 89.5% 91.7% 2.2%

Operating Hrs 2900 2900 -

Estimated Power (HP) 9.3 9.1 0.22

Elec Cost ($/kWh) 0.137 0.137 -

ECM RESULTS EXISTING PROPOSED SAVINGS

Electric Energy (kWh) 15,000 9,000 6,000

Electric Energy Cost ($) $2,055 $1,233 $822

10 HP CHILLED WATER PUMPS VFD CALULATION

ENERGY SAVINGS CALCULATIONS

COMMENTS: - VFD pump energy is based on ABB energy savings calculator for pumps, "Pump Save," version 4.2. Flow rate for VFD Pump calculation is summarized in the operating profile shown in the Pump Save output.

Page 31: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 30 of 60

Chilled Water VFD Pumping Energy 25 HP Pumps:

4.2

En

erg

y s

avin

g c

alc

ula

tor

for

pum

ps

Liq

uid

de

nsi

ty62

lb/ft

³S

tati

c h

ea

d1

ft

Cal

cula

ted

by:

No

min

al

volu

me

flo

w70

0gp

mE

ffic

ien

cy

75%

Cal

cula

ted

fo

r:C

hille

d w

ater

pum

psP

um

p ID

:#3

, 4

No

min

al

he

ad

80ft

Ma

x h

ea

d

80ft

S

up

ply

vo

lta

ge

200/

208/

230/

240

V 3

-ph

Req

uire

d m

otor

pow

er:

M

oto

r p

ow

er

25H

p20

.8 H

pR

es

ult

sin

clud

ing

10%

saf

ety

mar

gin

M

oto

r e

ffic

ien

cy91

.7 %

Sa

vin

g p

erc

en

tag

e39

.1 %

An

nu

al e

ne

rgy

co

ns

um

pti

on

:

with

exi

stin

g co

ntro

l met

hod

33M

Wh

A

nn

ua

l ru

nn

ing

tim

e

2,90

0h

with

impr

oved

con

trol

met

hod

20M

Wh

An

nu

al

en

erg

y sa

vin

g13

MW

h

5%

=

145

h a

t no

m.

flow

An

nu

al

CO

2 re

du

ctio

n7

t

15%

=

435

h a

t 90

% fl

owC

O2 e

mis

sio

n/u

nit

0.5

lb/k

Wh

20%

=

580

h a

t 80

% fl

ow

30%

=

870

h a

t 70

% fl

owC

urr

en

cy u

nit

$

20%

=

580

h a

t 60

% fl

owE

ne

rgy

pri

ce0

$/kW

h

10%

=

290

h a

t ha

lf flo

wIn

vest

me

nt

cost

0$

An

nu

al

savi

ng

0$

0%

=

0 h

at

40%

flow

Inte

rest

ra

te4%

Pa

yba

ck p

eri

od

0.0

year

s

0%

=

0 h

at

30%

flow

Se

rvic

e l

ife

10ye

ars

Ne

t p

rese

nt

valu

e0

$

0%

=

0 h

at

20%

flow

100

0

AC

S55

0-U

1-08

8A-2

0.0

2.0

4.0

6.0

8.0

10.0

12.0

14.0

16.0

18.0

2030

4050

6070

8090

100

Flo

w ra

te

Po

wer

(kW

)

Th

rott

ling

020

40

0

5,0

00

10

,00

0

15

,00

0

20

,00

0

25

,00

0

30

,00

0

35

,00

0

40

,00

0

Th

rott

lin

gV

SD

En

erg

y C

on

su

me

d (

kW

h)

FLOW (gpm)

Ope

ratin

g Pr

ofile

Econ

omic

Dat

a

Impr

oved

Con

trol

by

ABB

Driv

e :

Mot

or a

nd S

uppl

y D

ata

Sen

d to

de

faul

t pr

inte

r

D E F A U L T

Pum

p D

ata

Syst

em D

ata

Thro

ttlin

g co

ntro

l

Aut

o-ad

just

sc

reen

siz

eC

lose

pro

gram

US

Me

tric

Mea

sure

men

t un

its

230

V (

3-ph

)

AC

S550

Co

py

toc

lipb

oa

rd

Exis

ting

flow

con

trol

met

hod

Sav

e ca

lcul

atio

n

?

?

Sys

tem

Dat

a

Pu

mp

Dat

a

Mo

tor

and

Su

pp

ly D

ata

Op

erat

ing

Pro

file

Eco

no

mic

Dat

a

Mea

sure

men

t U

nit

s

Eco

no

mic

Res

ult

s

En

erg

y C

on

sum

pti

on

Exi

stin

g F

low

Co

ntr

ol

Page 32: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 31 of 60

ECM INPUTS EXISTING PROPOSED SAVINGS

ECM INPUTS CV Pumps VFD Pumps

Flow ControlThrottling

Valves-2WayVFD -

Flow (GPM) 700 700 -

Head (Ft) 80 80 -

Pump Efficiency (%) 75% 75% -

Motor Efficiency (%) 91.7% 93.6% 1.9%

Operating Hrs 2900 2900 -

Estimated Power (HP) 20.6 20.1 0.42

Elec Cost ($/kWh) 0.137 0.137 -

ECM RESULTS EXISTING PROPOSED SAVINGS

Electric Energy (kWh) 34,000 20,000 14,000

Electric Energy Cost ($) $4,658 $2,740 $1,918

25 HP CHILLED WATER PUMPS VFD CALULATION

ENERGY SAVINGS CALCULATIONS

COMMENTS: - VFD pump energy is based on ABB energy savings calculator for pumps, "Pump Save," version 4.2. Flow rate for VFD Pump calculation is summarized in the operating profile shown in the Pump Save output.

Currently the incentives through NJ Smart Start® Program Incentives for chilled water pump Frequency Drives over 20HP and above are $60 per VFD rated horsepower. In addition through NJ Smart Start® Program Incentives premium efficiency motors for the chilled water pumps are as follows: $90 for 10 HP motors with 91.7% NEMA efficiency and $117 for 25 HP motors with 93% NEMA efficiency.

Page 33: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 32 of 60

Energy Savings Summary:

Installation Cost ($): $114,774

NJ Smart Start Equipment Incentive ($): $1,914

Net Installation Cost ($): $112,860

Maintenance Savings ($/Yr): $0

Energy Savings ($/Yr): $2,740

Total Yearly Savings ($/Yr): $2,740

Estimated ECM Lifetime (Yr): 15

Simple Payback 41.2

Simple Lifetime ROI -63.6%

Simple Lifetime Maintenance Savings $0

Simple Lifetime Savings $41,100

Internal Rate of Return (IRR) -11%

Net Present Value (NPV) ($80,150.06)

ECM #3 - ENERGY SAVINGS SUMMARY

Page 34: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 33 of 60

ECM #4: Vending Miser Controls Description: The Atlantic County Special Services School currently utilizes vending machines in select areas within the building. Vending machines are common within cafeteria’s and faculty rooms which can be in use for a limited time during the day. The installation of the Vending Miser system will help reduce the operating hours of vending machines. Cold beverage machines regularly operate inefficiently trying to maintain a constant cool temperature within the machine. The VendingMiser® system incorporates innovative energy-saving technology into a small plug-and-play device that in conjunction with a passive infrared sensor regulate the operation of the cold beverage machines based on occupancy and room temperature. This ECM approximates the installation of two (2) of these control systems for the cold beverage machines. Energy Savings Calculations: See Vending Miser Appendix for calculation methods and analysis. Energy Savings Summary:

Installation Cost ($): $358

NJ Smart Start Equipment Incentive ($): $0

Net Installation Cost ($): $358

Maintenance Savings ($/Yr): $0

Energy Savings ($/Yr): $548

Total Yearly Savings ($/Yr): $548

Estimated ECM Lifetime (Yr): 15

Simple Payback 0.7

Simple Lifetime ROI 2194.2%

Simple Lifetime Maintenance Savings $0

Simple Lifetime Savings $8,213

Internal Rate of Return (IRR) 153%

Net Present Value (NPV) $6,178.62

ECM #4 - ENERGY SAVINGS SUMMARY

Page 35: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 34 of 60

ECM #5: Demand Controlled Ventilation Demand Controlled Ventilation (DCV) is a means to provide active, zone level control of ventilation for spaces within a facility. The basic premise behind DCV is monitoring indoor CO2 levels versus outdoor CO2 levels in order to provide proper ventilation to the spaces within the facility as well as saving costly dollars treating unconditioned ventilation air. Carbon dioxide ventilation control or demand controlled ventilation (DCV) allows for the measurement and control of outside air ventilation levels to a target cfm/person ventilation rate in the space (i.e., 15 cfm/person) based on the number of people in the space. It is a direct measure of ventilation effectiveness and is a method whereby buildings can regain active and automatic zone level ventilation control, without having to open windows. The fixed ventilation approach depends on a set-it-and-forget-it methodology that is completely unresponsive to changes in the way spaces are utilized/occupied or how equipment is maintained. A DCV system utilizes various control algorithms to maintain a base ventilation rate. The system monitors space CO2 levels and the algorithm automatically adjusts the outdoor and return air dampers to provide the quantity of outdoor air to maintain the required CO2 level in the space. System designs are normally designed for maximum occupancy and the ventilation rates are designed for this (maximum) occupancy. In areas where occupancy swings are prevalent there is ample opportunity to reduce outdoor air quantity to satisfy the needs of the actual number of occupants present. By installing the DCV controls, energy savings are realized by the reduced quantities of outdoor air that do not require heating and cooling energy. Packaged rooftop units RTU – 1 through 8 provide heating and air conditioning to several areas of the facility which include offices, auditoriums, cafeteria and multi-purpose rooms. When operating, these units provide minimum amount of outside air to the space. The outside air volume is typically based on the maximum occupancy of the space conditioned. When a given space is not fully occupied the outside air quantity delivered to the space is greater than the amount needed for adequate ventilation. This ECM includes the installation of CO2 sensors integrated into a demand control ventilation system, for the units mentioned above. This system allows the air handling unit to respond to changes in occupancy and therefore reduce the amount of outside air that has to be conditioned. Outside air accounts for a large portion of the energy consumption in the HVAC system, especially in high occupancy spaces. The U.S. Department of Energy sponsored a study to analyze energy savings achieved through various types of building system controls. The referenced savings is based on the “Advanced Sensors and Controls for Building Applications: Market Assessment and Potential R&D Pathways,” document posted for public use April 2005. The study has found that commercial buildings have the potential to achieve significant energy savings through the use of building controls. The average energy savings are as follows based on the report:

Demand Control Ventilation - 10% - 15%. Energy savings achieved through “Demand Control Ventilation” average 10%-15%. Savings resulting from the implementation of this ECM for energy management controls vary depending on the room type.

Page 36: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 35 of 60

The components required for the demand control ventilation system installation include CO2 sensors, control wiring, electrical wiring, and programming. Each occupied zone would require a minimum of one CO2 sensor installed to monitor occupancy levels.

IMPLEMENTATION SUMMARY

INPUTS ServiceMin # of CO2

SENSORSHVAC

Unit

Cooling Capaity,

Tons

Heating Capacity,

MBHDCV-1 MP 330 1 PRTU-1 15 250DCV-2 MP 330 1 PRTU-2 12.5 250DCV-3 MP 435 1 PRTU-3 8.5 135DCV-4 MP 435 1 PRTU-4 8.5 200DCV-5 MP 618 1 PRTU-5 12.5 250DCV-6 MP 618 1 PRTU-6 7.5 205DCV-7 Stage 619 1 PRTU-7 5 130Total 70 1,420

Energy Savings Calculations:

Wh

BtuEER

kWh

Wh1000

Hrs.Cooling Load Full AnnualhrTon

Btu12,000TonsCooling

eEnergyUsag Cooling

%10kwhEnergy CoolingSavingsEnergy

kWh

$CostElectricAvekWhUsageEnergyCostCooling

%EfficiencyHeatingTherms

BtuValueHeatFuelF65

Day

Hr.21FDayHDD

Hr.

BtuCapacity Heating

ThermsEnergy Heating

Therms

$CostFuelAveThermsEnergyHeatingCost Heating

The following tables represent the rooftop units which will be used to install demand control ventilation.

%10SavingsEnergy

Page 37: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 36 of 60

ECM INPUTS DCV-1Equipment PRTU-1Total Cooling Capacity, Tons 15.0Efficiency (EER) 11.5Annual Full Load Cooling Hours 1200Total Heating Capacity, MBh 250Heating Efficiency (Gas) 80%Heating Degree Days (65°F) 4827Energy Savings 10.0%Elec Cost ($/kWh) $0.137Natural Gas Cost ($/Therm) $1.29

ECM RESULTS DCV-1Cooling Energy Cnsmption, kWh 18,783 Heating Energy (Therms) 1,052Cooling Energy Savings kWh 1,878 Heating Energy Savings (Therms) 105Electric Energy Cost Savings ($) $257Total Gas Cost Savings ($) $136Total Cost Savings ($) $393

DEMAND CONTROLLED VENTILATION

ENERGY SAVINGS

COMMENTS:HDD estimated based on Atlantic City,NJ.

ECM INPUTS DCV-2,5Equipment PRTU-2,5Total Cooling Capacity, Tons 25Efficiency (EER) 11.3Annual Full Load Cooling Hours 1200Total Heating Capacity, MBh 500Heating Efficiency (Gas) 80%Heating Degree Days (65°F) 4827Energy Savings 10.0%

Elec Cost ($/kWh) $0.137

Natural Gas Cost ($/Therm) $1.29

ECM RESULTS DCV-2,5Cooling Energy Cnsmption, kWh 31,858 Heating Energy (Therms) 1,239Cooling Energy Savings kWh 3,186 Heating Energy Savings (Therms) 124Electric Energy Cost Savings ($) $436Total Gas Cost Savings ($) $160Total Cost Savings ($) $596

DEMAND CONTROLLED VENTILATION

ENERGY SAVINGS

COMMENTS:HDD estimated based on Atlantic City,NJ.

Page 38: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 37 of 60

ECM INPUTS DCV-3Equipment PRTU-3Total Cooling Capacity, Tons 9Efficiency (EER) 11.0Annual Full Load Cooling Hours 1200Total Heating Capacity, MBh 135Heating Efficiency (Gas) 80%Heating Degree Days (65°F) 4827Energy Savings 10.0%Elec Cost ($/kWh) $0.137Natural Gas Cost ($/Therm) $1.29

ECM RESULTS DCV-3Cooling Energy Cnsmption, kWh 11,127 Heating Energy (Therms) 895Cooling Energy Savings kWh 1,113 Heating Energy Savings (Therms) 90Electric Energy Cost Savings ($) $152Total Gas Cost Savings ($) $116Total Cost Savings ($) $268COMMENTS:

HDD estimated based on Atlantic City,NJ.

DEMAND CONTROLLED VENTILATION

ENERGY SAVINGS

ECM INPUTS DCV-4Equipment PRTU-4Total Cooling Capacity, Tons 9Efficiency (EER) 11.0Annual Full Load Cooling Hours 1200Total Heating Capacity, MBh 200Heating Efficiency (Gas) 80%Heating Degree Days (65°F) 4827Energy Savings 10.0%Elec Cost ($/kWh) $0.137Natural Gas Cost ($/Therm) $1.29

ECM RESULTS DCV-4Cooling Energy Cnsmption, kWh 11,127 Heating Energy (Therms) 1,005Cooling Energy Savings kWh 1,113 Heating Energy Savings (Therms) 100Electric Energy Cost Savings ($) $152Total Gas Cost Savings ($) $130Total Cost Savings ($) $282

DEMAND CONTROLLED VENTILATION

ENERGY SAVINGS

COMMENTS:HDD estimated based on Atlantic City,NJ.

Page 39: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 38 of 60

ECM INPUTS DCV-6Equipment PRTU-6Total Cooling Capacity, Tons 13Efficiency (EER) 10.0Annual Full Load Cooling Hours 1200Total Heating Capacity, MBh 205Heating Efficiency (Gas) 80%Heating Degree Days (65°F) 4827Energy Savings 10.0%Elec Cost ($/kWh) $0.137Natural Gas Cost ($/Therm) $1.29

ECM RESULTS DCV-6Cooling Energy Cnsmption, kWh 18,000 Heating Energy (Therms) 821Cooling Energy Savings kWh 1,800 Heating Energy Savings (Therms) 82Electric Energy Cost Savings ($) $247Total Gas Cost Savings ($) $106Total Cost Savings ($) $353

ENERGY SAVINGS

COMMENTS:HDD estimated based on Atlantic City,NJ.

DEMAND CONTROLLED VENTILATION

ECM INPUTS DCV-7Equipment PRTU-7Total Cooling Capacity, Tons 8Efficiency (EER) 12.0Annual Full Load Cooling Hours 1200Total Heating Capacity, MBh 130Heating Efficiency (Gas) 80%Heating Degree Days (65°F) 4827Energy Savings 10.0%Elec Cost ($/kWh) $0.137Natural Gas Cost ($/Therm) $1.29

ECM RESULTS DCV-7Cooling Energy Cnsmption, kWh 9,000 Heating Energy (Therms) 446Cooling Energy Savings kWh 900 Heating Energy Savings (Therms) 45Electric Energy Cost Savings ($) $123Total Gas Cost Savings ($) $57Total Cost Savings ($) $181COMMENTS:

HDD estimated based on Atlantic City,NJ.

DEMAND CONTROLLED VENTILATION

ENERGY SAVINGS

Page 40: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 39 of 60

Incentives: There are currently no Smart Start ® incentives available for a Demand Control Ventilation System. Energy Savings Summary:

Installation Cost ($): $41,364

NJ Smart Start Equipment Incentive ($): $0

Net Installation Cost ($): $41,364

Maintenance Savings ($/Yr): $0

Energy Savings ($/Yr): $2,073

Total Yearly Savings ($/Yr): $2,073

Estimated ECM Lifetime (Yr): 15

Simple Payback 20.0

Simple Lifetime ROI -24.8%

Simple Lifetime Maintenance Savings $0

Simple Lifetime Savings $31,095

Internal Rate of Return (IRR) -3%

Net Present Value (NPV) ($16,616.66)

ECM #5 - ENERGY SAVINGS SUMMARY

Page 41: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 40 of 60

ECM #6: Walk-in Cooler/Freezer Controls Description: The three refrigerated walk-in cooler/freezers have a bank of evaporator fans that circulate the cold air over and under the food. These banks of evaporator fans (1/20 HP motors) run continuously and give off heat that must be removed by the refrigeration. This measure would install an evaporator fan controller that features two-speed operation of the evaporator fans – high speed during cooling, and low speed when not cooling manufactured by Frigitek or equivalent. The estimated energy savings assumes that the cooler is not opened for 10 hours per day. Energy Savings Calculations: Installing controllers on each of the three evaporator fan motors in the three walk-in cooler/freezers would save approximately 468.2 kWh/month x 12 months = 5618 kWh/Year. Annual Energy Cost Savings = 5,107.2 kWh x $0.137/kWh = $769/Year Energy Savings Summary:

Installation Cost ($): $3,707

NJ Smart Start Equipment Incentive ($): $0

Net Installation Cost ($): $3,707

Maintenance Savings ($/Yr): $0

Energy Savings ($/Yr): $770

Total Yearly Savings ($/Yr): $770

Estimated ECM Lifetime (Yr): 15

Simple Payback 4.8

Simple Lifetime ROI 211.4%

Simple Lifetime Maintenance Savings 0

Simple Lifetime Savings $11,545

Internal Rate of Return (IRR) 19%

Net Present Value (NPV) $5,481.15

ECM #6 - ENERGY SAVINGS SUMMARY

Page 42: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 41 of 60

ECM #7: Boiler Controls Upgrade – Fuel Economizer Description: The space heating for the Atlantic County Special Services School is provided from a central boiler plant. The boiler plant houses two gas-fired boilers. The boilers are controlled via Trace Summit Controls building management system. These boiler controls are capable of various energy saving features such as space temperature compensation, night set back and temperature reset based on outside air. Heating energy consumption of the facility can be reduced by approximately 10% by installing an Intellicon Commercial Hot Water Heating System Fuel Economizer. Intellicon-CWH uses Dynamic Cycle Management (DCM) technology to save energy by adjusting the burner run pattern to match the system’s heat load. This technology helps reduce fuel consumption, wear on parts, flue emissions and electrical usage when installed on the gas-fired burner. This energy conservation measure will install two Intellicon CWH fuel economizer controls to both boiler burners. This will allow the controller to program the burner and maximize the system’s efficiency. Energy Savings Calculations: The Intellicon-CWH fuel economizer is guaranteed by the manufacturer (Intellidyne) to reduce fuel consumption by 10%. The annual fuel usage for the two gas-fired boilers has been approximated by subtracting the gas fired rooftop units and domestic load from the annual gas bills which are provided. Total Annual Fuel Usage: 28,762 Therms Approximate Domestic/ Rooftop Fuel Usage: 20,309 Therms Annual Boiler Fuel Usage: 8453 Therms

Boiler Savings with Intellicon CWH: 8,453 Therms x 10% = 845.3 Therms Saved

Page 43: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 42 of 60

Energy Savings Summary:

Installation Cost ($): $8,000

NJ Smart Start Equipment Incentive ($): $0

Net Installation Cost ($): $8,000

Maintenance Savings ($/Yr): $0

Energy Savings ($/Yr): $1,090

Total Yearly Savings ($/Yr): $1,090

Estimated ECM Lifetime (Yr): 15

Simple Payback 7.3

Simple Lifetime ROI 104.4%

Simple Lifetime Maintenance Savings $0

Simple Lifetime Savings $16,350

Internal Rate of Return (IRR) 11%

Net Present Value (NPV) $5,012.35

ECM #7 - ENERGY SAVINGS SUMMARY

Page 44: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 43 of 60

ECM #8: Geothermal Heat Pump System Installation Description: The existing heating system for Atlantic County Special Services School consists of two boilers that provide hot water to air handling units. The cooling system of the building consists of a chiller which provides chilled water to the air handling units. The existing heating system for the whole building utilizes natural gas as the fuel source. A geothermal heat pump system utilizes the ground as a heat sink to extract and reject heat to depending on the season. Due to the large thermal mass provided by the ground, the HVAC equipment is able to take advantage of cooler temperatures in the summer and warmer temperatures in the winter compared to the ambient air. The benefits include substantial energy efficiency increase with respect to air source systems. In addition, no electrical resistance heat is required in the heating season also reducing electric usage. A geothermal system sized properly requires no additional heat production equipment (such as a boiler) or heat rejection equipment (such as a cooling tower). All loads are handled by the heat pumps and the geothermal water loop. Due to the inefficiency of the boiler and poor operational characteristics of the air to air heat pumps, a geothermal system energy costs become very appealing. This ECM includes the installation of vertical ground source heat pumps installed within the mechanical room. In order for this hybrid system to be viable, the chiller and one of the boilers will be removed and the heat pumps will need to be tied into the chilled water loop. The heat pumps will serve as a bypass for the one existing boiler which will also be tied into this chilled water loop to provide emergency injection for the system if the load cannot be met by the heat pumps. All existing air handling units within the ceiling will remain but hot water coils will be removed. This ECM also includes installation of new ground loop water pumps with VFD drives. The pumping system is included to pump transfer fluid from the building to the well field and back. The geothermal system would require (not limited to) the following major components:

1. 500-Ton bore field. (Approximately 200 bores, 500 ft deep each). Bore field sizing is based on 200 linear feet of bore per ton of cooling. A complete geotechnical analysis will have to be performed in order to confirm the actual soil thermal conductivity at the site.

2. (2) Loop condenser water pumps. 3. Condenser water piping distribution system from the well field to the indoor heat

pumps. 4. Installation of high-efficiency (18.5 EER) vertical geothermal indoor heat pumps. 5. Removal of chiller and one boiler as well as piping modifications.

This ECM is based on Climate Master Tranquility Series vertical ground source heat pumps model TMW for the geothermal indoor or equal. District should have a Professional Engineer verify heating and cooling loads prior to moving forward with this ECM.

Page 45: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 44 of 60

Energy Savings Calculations: The energy savings calculations are based on the energy analysis performed on the energy modeling software by Trane (Trace 700 ver. 6.2.4). The energy consumption of the baseline is compared to the proposed model to determine energy savings for each utility. The savings are applied to the average energy costs based on the facilities actual usage. Note: Heating and cooling is only provided for the chilled water/ boiler loop system air handling units for geothermal system model.

ECM INPUTS EXISTING PROPOSED SAVINGS

ECM INPUTSExisting Energy Consumption

Proposed Energy Consumption

Elec Usage (KWH) 2,512,808 2,464,988 47,820

Natural Gas Usage (Therms)* 36,044 22,110 13,934

Electric Cost ($/KWH) $0.137 $0.137

Natural Gas Cost ($/Therm) $1.29 $1.29

ECM RESULTS EXISTING PROPOSED SAVINGS

Electric Energy Cost ($) $344,255 $337,703 $6,551

Natural Gas Energy Cost ($) $46,497 $28,522 $17,975

Total Energy Cost ($) $390,751 $366,225 $24,526

ECM #8 GEOTHERMAL SYSTEM CALCULATIONS

ENERGY SAVINGS CALCULATIONS

This ECM is based on energy models performed on energy analysis software by Trane (Trace 700).

*Natural gas usage for existing and proposed systems includes gas fired domestic hot water heating equipment

COMMENTS:

Page 46: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 45 of 60

Energy Savings Summary:

Installation Cost ($): $4,543,000

NJ Smart Start Equipment Incentive ($): $300,000

Net Installation Cost ($): $4,243,000

Maintenance Savings ($/Yr): $0

Energy Savings ($/Yr): $24,562

Total Yearly Savings ($/Yr): $24,562

Estimated ECM Lifetime (Yr): 25

Simple Payback 172.7

Simple Lifetime ROI -85.5%

Simple Lifetime Maintenance Savings $0

Simple Lifetime Savings $614,050

Internal Rate of Return (IRR) -11%

Net Present Value (NPV) ($3,815,298.27)

ECM #8 - ENERGY SAVINGS SUMMARY

Page 47: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 46 of 60

ECM #9: Duct Insulation for Multi-Purpose Room Air Handlers Description: There are six rooftop units which serve multi-purpose rooms 330, 435 and 618. The duct work providing the conditioning to these spaces is completely uninsulated. The duct work in the space is not only losing energy to the surrounding space but Concord Engineering has been advised that the areas which the duct work resides have been subject to condensation which leaves water on the floor below. This ECM includes the exterior insulation of all the duct work which resides within the multi-purpose rooms. Insulating the duct work will not only save energy by reducing the amount of heat loss/gain from the surrounding area, but it will also alleviate the buildup of condensation on the duct work which results in water on the floor below. Energy Savings Calculations: The following equation represents the method for calculating heat loss/gain in a duct:

12 2

Where:

q = heat loss/gain through duct walls U = overall heat transfer coefficient of duct wall P = Perimeter of bare or insulated duct L = duct length te = temperature of air entering tl = temperature of air leaving ta = surrounding area temperature

For further calculations refer to Appendix G Duct Insulation.

Page 48: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 47 of 60

Energy Savings Summary:

Installation Cost ($): $35,000

NJ Smart Start Equipment Incentive ($): $0

Net Installation Cost ($): $35,000

Maintenance Savings ($/Yr): $0

Energy Savings ($/Yr): $649

Total Yearly Savings ($/Yr): $649

Estimated ECM Lifetime (Yr): 15

Simple Payback 53.9

Simple Lifetime ROI -72.2%

Simple Lifetime Maintenance Savings $0

Simple Lifetime Savings $9,735

Internal Rate of Return (IRR) -13%

Net Present Value (NPV) ($27,252.28)

ECM #9 - ENERGY SAVINGS SUMMARY

Page 49: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 48 of 60

VIII. RENEWABLE/DISTRIBUTED ENERGY MEASURES Globally, renewable energy has become a priority affecting international and domestic energy policy. The State of New Jersey has taken a proactive approach, and has recently adopted in its Energy Master Plan a goal of 30% renewable energy by 2020. To help reach this goal New Jersey created the Office of Clean Energy under the direction of the Board of Public Utilities and instituted a Renewable Energy Incentive Program to provide additional funding to private and public entities for installing qualified renewable technologies. A renewable energy source can greatly reduce a building’s operating expenses while producing clean environmentally friendly energy. CEG has assessed the feasibility of installing renewable energy measures (REM) for the school district utilizing renewable technologies and concluded that there is potential for solar energy generation. Solar Generation Solar energy produces clean energy and reduces a building’s carbon footprint. This is accomplished via photovoltaic panels which are mounted on all south and southwestern facades of the building. Flat roof, as well as sloped areas can be utilized; flat areas will have the panels turned to an optimum solar absorbing angle. (A structural survey of the roof would be necessary before the installation of PV panels is considered). Parking lots can also be utilized for the installation of a solar array. A truss system can be installed that is high enough to park vehicles under the array and no parking lot area is lost. The state of NJ has instituted a program in which one Solar Renewable Energy Certificate (SREC) is given to the District for every 1000 kWh of generation. SREC’s can be sold anytime on the market at their current market value. The value of the credit varies upon the current need of the power companies. The credit value used in our financial calculations varies over the fifteen year outlook from an initial value of $550 per MWH down to $200 per MWH at year fifteen. This equates to an average value of $383 per MWH, or $0.383 per kWh generated. CE has reviewed Atlantic County Special Services School for the purposes of determining the potential for roof mounted and ground mounted photovoltaic system. It was determined that a total system size of 615.94 KW can be utilized for a roof mounted PV systems. A depiction of the area utilized is shown in Renewable / Distributed Energy Measures Calculation Appendix. A system size of 615.94 kilowatts could be installed. A system of this size has an estimated kilowatt hour production of 710,235 KWh annually, reducing the overall utility bill by approximately 28% percent. A detailed financial analysis can be found in the Renewable / Distributed Energy Measures Calculation Appendix. This analysis illustrates the payback of the system over a 15 year period. The eventual degradation of the solar panels and the price of accumulated SREC’s are factored into the payback. The proposed photovoltaic array layout is designed based on the specifications for the Trina TSM-PA05 230 panel. This panel has a “DC” rated full load output of 230 watts. Although panels rated at higher wattages are available through other various manufacturers, in general most manufacturers who produce commercially available solar panels produce a similar panel in

Page 50: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 49 of 60

the 200 to 250 watt range. This provides more manufacturer options to the public entity if they wish to pursue the proposed solar recommendation without losing significant system capacity. The array system capacity was sized based on available roof space area available at the existing facility. Estimated solar array generation is calculated based on the National Renewable Energy Laboratory PVWatts Version 1.0 Calculator. In order to calculate the array generation an appropriate location with solar data on file must be selected. In addition the system DC rated kilowatt (kW) capacity must be inputted, a DC to AC de-rate factor, panel tilt angle, and array azimuth angle. The DC to AC de-rate factor is based on the panel nameplate DC rating, inverter and transformer efficiencies (95%), mismatch factor (98%), diodes and connections (100%), dc and ac wiring(98%, 99%), soiling, (95%), system availability (95%), shading (if applicable), and age(new/100%). The overall DC to AC de-rate factor has been calculated at an overall rating of 81%. The PVWatts Calculator program then calculates estimated system generation based on average monthly solar irradiance and user provided inputs. The monthly energy generation and offset electric costs from the PVWatts calculator is shown in the Renewable/Distributed Energy Measures Calculation Appendix. The proposed solar array for the facility is qualified by the New Jersey Board of Public Utilities Net Metering Guidelines as a Class I Renewable Energy Source. These guidelines allow onsite customer generation using renewable energy sources such as solar and wind with a capacity of 2 megawatts (MW) or less. This limits a customer system design capacity to being a net user and not a net generator of electricity on an annual basis. Although these guidelines state that if a customer does net generate (produce more electricity than they use), the customer will be credited those kilowatt-hours generated to be carried over for future usage on a month to month basis. Then, on an annual basis if the customer is a net generator the customer will then be compensated by the utility the average annual PJM Grid LMP price per kilowatt-hour for the over generation. Due to the aforementioned legislation, the customer is at limited risk if they generate more than they use at times throughout the year. With the inefficiency of today’s energy storage systems, such as batteries, the added cost of storage systems is not warranted and was not considered in the proposed design. Direct purchase involves the district paying for 100% of the total project cost upfront via one of the methods noted in the Installation Funding Options section below. Calculations include a utility inflation rate as well as the degradation of the solar panels over time. Based on our calculations the following is the payback period:

Table 7 Renewable Financial Summary

FINANCIAL SUMMARY - PHOTOVOLTAIC SYSTEM

PAYMENT TYPESIMPLE PAYBACK,

YRS.NET PRESENT

VALUE

Finance 100% - 15 yrs 6.28 1,714,558

Page 51: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 50 of 60

Given the large amount of capital required by the School District to invest in a solar system through a Direct Purchase Concord does not recommend pursuing this route. It would be more advantageous for the School District to solicit Power Purchase Agreement (PPA) Providers who will own, operate, and maintain the system for a period of 15 years. During this time the PPA Provider would sell all of the electric generated by the Solar Arrays to the District at a reduced rate compared to their existing electric rate. Concord has performed a preliminary analysis that shows the potential benefits to the School District in reduced electric pricing over the life of the agreement. It is estimated that the School District could potentially see a reduction in electric rate from 10% to 30% and thus the analysis performed shows three alternative pricing elements based on a 2 cent, 4 cent, and 5 cent rate reduction. The following table shows the potential year 1 and total 15 year electric cost savings for each of these alternative prices.

Table 8 Summary – PPA Analysis

Solar System Size (kW) 615.94Annual Solar System Production (kWh) 710,235Existing Utility Electric Rate ($/kWh) $0.137Existing Electric Utility Cost $97,302

Year 1 PPA Electric Rate ($/kWh) $0.132Year 1 PPA Electric Cost $93,751Electric Cost Savings Year 1 $3,551

Year 1 PPA Electric Rate ($/kWh) $0.127Year 1 PPA Electric Cost $90,200Electric Cost Savings Year 1 $7,102

Year 1 PPA Electric Rate ($/kWh) $0.122Year 1 PPA Electric Cost $86,649Electric Cost Savings Year 1 $10,654

POWER PURCHASE AGREEMENT SUMMARY

Analysis - 1

Analysis - 2

Analysis - 3

Wind Generation In addition to the Solar Analysis, CEG also conducted a review of the applicability of wind energy for the facility. Wind energy production is another option available through the Renewable Energy Incentive Program. Wind turbines of various types can be utilized to produce clean energy on a per building basis. Cash incentives are available per kWh of electric usage. Based on CEG’s review of the applicability of wind energy for the facility, it was determined that the average wind speed of 4.6 m/s is not adequate enough to make wind an economically viable option for the school district to pursue.

Page 52: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 51 of 60

IX. ENERGY PURCHASING AND PROCUREMENT STRATEGY Load Profile: Load Profile analysis was performed to determine the seasonal energy usage of the facility. Irregularities in the load profile will indicate potential problems within the facility. Consequently based on the profile a recommendation will be made to remedy the irregularity in energy usage. For this report, the facility’s energy consumption data was gathered in table format and plotted in graph form to create the load profile. Refer to The Electric and Natural Gas Usage Profiles included within this report to reference the respective electricity and natural gas usage load profiles. Electricity: The Electric Usage Profile is a fairly steady year-long electric load with an above average load profile. The facility is currently receiving electric delivery and supply service directly from Atlantic City Electric. The historical usage profile is beneficial and will allow for more competitive energy prices when shopping for alternative suppliers mainly due to the relatively steady year-long load profile. Third Party Supplier (TPS) electric commodity contracts that offer’s a firm, fixed price for 100% of the facilities electric requirements and are lower than the Atlantic City Electric’s BGS-FP default rate are recommended. Natural Gas: The Natural Gas Usage Profile demonstrates a very typical natural gas (heat load) profile. A base-load shaping (flat) will secure more competitive energy prices when procuring through an alternative energy source. This load profile may yield more favorable natural gas pricing when shopping for alternative suppliers. Nymex commodity pricing is generally higher in the winter months of November – March and lower in the summer months of April – October. Obtaining a flat load profile, (usage is similar each month), will yield optimum natural gas pricing when shopping for alternative suppliers. Third Party Supplier (TPS) natural gas commodity contracts that offer a firm, fixed price for 100% of the facilities natural gas requirements are recommended. Tariff Analysis: Electricity: The facility receives electric distribution service through Atlantic City Electric (AECO) on rate schedule’s AGS (Annual General Service) and MGS (Monthly General Service). For the electric supply (generation) service only, the client has a choice to either use AECO’s default service rate BGS-FP or contract with a Third Party Supplier (TPS) to supply electric.

Page 53: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 52 of 60

Each year since 2002, the four New Jersey Electric Distribution Companies (EDCs) - Public Service Gas & Electric Company (PSE&G), Atlantic City Electric Company (ACE), Jersey Central Power & Light Company (JCP&L), and Rockland Electric Company (RECO) - have procured several billion dollars of electric supply to serve their Basic Generation Service (BGS) customers through a statewide auction process held in February. BGS refers to the service of customers who are not served by a third party supplier or competitive retailer. This service is sometimes known as Standard Offer Service, Default Service, or Provider of Last Resort Service. The Auction Process has consisted of two auctions that are held concurrently, one for larger customers on an hourly price plan (BGS-CIEP) and one for smaller commercial and residential customers on a fixed-price plan (BGS-FP). This facility’s rate structure is based on the fixed-price plan (BGS-FP). The current BGS-FP average price to compare for AECO’s AGS rate schedule is $0.1182/kWh. Based upon the current BGS-FP electric rate from AECO, this facility has the ability to experience savings by contracting with a Third Party Supplier (TPS) for electric supply service. Should the facility contract with a TPS, the utility, AECO will continue to be responsible for maintaining the existing network of wires, pipes and poles that make up the delivery system, which will serve all consumers, regardless of whom they choose to purchase their electricity from. AECO’s delivery service rate includes the following charges: Customer Service Charge, Distribution Charge, Market Transition, Transition Bond Charge, Non Utility Generation Charge, Societal Benefits Charge (SBC), Infrastructure Investment Charge, System Control Charge, Regulatory Assets Recovery Charge, and Regional Greenhouse Gas Initiative Charge. Natural Gas: The facility currently receives natural gas distribution service through South Jersey Gas (SJG) on rate schedule GSG (General Service Gas). The facility is also receiving natural gas commodity supply from the utility, SJG on the Basic Gas Supply Service (BGSS). SJG provides basic gas supply service (BGSS) to customers who choose not to shop from a Third Party Supplier (TPS) for natural gas commodity. The option is essential to protect the reliability of service to consumers as well as protecting consumers if a third party supplier defaults or fails to provide commodity service. Please refer to the link below for a recap of monthly natural gas BGSS charges from SJG. http://www.southjerseygas.com/108/tariff/bgssrates.pdf The utility, SJG is responsible for maintaining the existing network of underground pipes that make up the delivery system, which will serve all consumers, regardless of whom they choose to purchase their natural gas from. SJG’s delivery service rates includes the following charges: Customer Service Charge, Delivery Charge, Line Loss, and Applicable Riders that include: Societal Benefits Charge (SBC), Balancing Service Clause, Temperature Adjustment Clause, Conservation Incentive Program and Energy Efficient Tracker.

Page 54: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 53 of 60

Electric and Fossil Fuel Commodities Market Overview:

Current electricity and natural gas market pricing has remained relatively stable over the last year. Commodity pricing in 2008 marked historical highs in both natural gas and electricity commodity. Commodity pricing commencing spring of 2009 continuing through 2011, has decreased dramatically over 2008 historic highs and continues to be favorable for locking in long term (2-5 year) contracts with 3rd Party Supplier’s for both natural gas and electricity supply requirements.

It is important to note that both natural gas and electric commodity market prices are moved by supply and demand, political conditions, market technicals and trader sentiment. This market is continuously changing Energy commodity pricing is also correlated to weather forecasts. Because weather forecasts are dependable only in the short-term, prolonged temperature extremes can really cause extreme price swings.

Short Term Energy Outlook - US Energy Information Administration (9/07/2011):

U.S. Natural Gas Prices. Natural gas working inventories ended August 2011 at 3.0 trillion cubic feet (Tcf), about 5 percent, or 144 billion cubic feet (Bcf), below the 2010 end-of-August level. EIA expects that working natural gas inventories will approach last year's high levels by the end of this year's injection season. The projected Henry Hub natural gas spot price averages $4.20 per million British thermal units (MMBtu) in 2011, $0.18 per MMBtu lower than the 2010

Page 55: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 54 of 60

average. EIA expects the natural gas market to tighten moderately in 2012, with the Henry Hub spot price increasing to an average of $4.30 per MMBtu.

Uncertainty about natural gas prices is lower this year compared with last year at this time. Natural gas futures for November 2011 delivery (for the 5-day period ending September 1, 2011) averaged $4.07 per MMBtu, and the average implied volatility was 34 percent. The lower and upper bounds for the 95-percent confidence interval for November 2011 contracts are $3.16 per MMBtu and $5.26 per MMBtu. At this time last year, the November 2010 natural gas futures contract averaged $4.07 per MMBtu and implied volatility averaged 48 percent. The corresponding lower and upper limits of the 95-percent confidence interval were $2.84 per MMBtu and $5.83 per MMBtu.

U.S. Electricity Consumption. During the first half of 2010, total consumption of electricity rose an estimated 4.2 percent compared with the first half of last year. Growth during the second half is projected to be slightly higher, rising 5.2 percent compared with the same period in 2009. High temperatures during July and August have pushed up sales of electricity in the residential and commercial sectors, especially in the Midwest and Northeast. Projected electricity sales to the industrial sector increase by 6 percent in 2010, but growth slows to 0.2 percent next year as expected growth in industrial output moderates. Total forecast consumption of electricity falls slightly in 2011 since summer temperatures are forecast to return to near-normal levels.

U.S. Electricity Retail Prices. Retail prices of electricity to the residential sector during the first six months of this year were generally higher than the same period in 2010. Growth in residential electricity prices should moderate during the second half. EIA expects average U.S. residential electricity prices to increase by 2.3 percent in 2011 and by 0.6 percent in 2012.

Recommendations:

1. CEG recommends exploring TPS commodity supply procurement pricing and strategies for both electric and natural gas supply service. Energy commodities are among the most volatile of all commodities, however at this point and time, energy is extremely competitive. Atlantic County Special Services School could realize up to a 20% reduction in energy supply costs for both electricity and natural gas, if it were to take advantage of these current market prices quickly, before energy increases.

Overall, after review of the utility consumption, billing, and current commodity pricing outlook, CEG recommends that the Atlantic County Special Services School utilize the advisement of 3rd party unbiased Energy Consulting Firm experienced in the procurement of retail natural gas and electricity commodity and negotiation of contract terms and conditions. The Energy Consulting Firm should incorporate a rational, defensible strategy for purchasing commodity in volatile markets based upon the following:

Budgets that reflect sound market intelligence An understanding of historical prices and trends Awareness of seasonal opportunities (e.g. shoulder months) Negotiation of fair contractual terms An aggressive, market based price

Page 56: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 55 of 60

2. CEG recommends that the Atlantic County Special Services School explore Demand

Response Programs that may be available for its facilities. Demand response is the action of end users lowering their demand for electric (reducing consumption) in order to help balance supply and demand on the electric grid and ensure stability. The greatest need for demand response typically occurs during times of peak electricity demand, between the hours of 11 am and 6 pm, when extra strain is placed on the grid from situations such as increased air conditioning use on hot days or downed power lines resulting from a storm. Significant incentives are available for clients enrolled in demand response programs. It is strongly recommended that the school utilize an experienced 3rd party unbiased energy consulting firm prior to initiating any demand response programs. This is recommended due to the potential conflicts with existing and/or future electric supply service agreements and transparency created by the evaluation of current programs and incentives available.

The recommendations presented by CEG are based on current information provided by the client for its utility usage, any savings presented with these recommendations are estimates only based on that information as well as current commodities marketplace. It is recommended that further analysis and review of more recent utility data be performed prior to performing any of the presented recommendations.

Page 57: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 56 of 60

X. INSTALLATION FUNDING OPTIONS CEG has reviewed various funding options for the facility District to utilize in subsidizing the costs for installing the energy conservation measures noted within this report. Below are a few alternative funding methods: A. Incentive Programs: Pay For Performance The New Jersey Smart Start Pay for Performance program includes incentives based on savings resulted from implemented ECMs. The program is available for all buildings that were audited as part of the NJ Clean Energy’s Local Government Energy Audit Program. The facility’s participation in the program is assisted by an approved program partner. An “Energy Reduction Plan” is created with the facility and approved partner to shown at least 15% reduction in the building’s current energy use. Multiple energy conservation measures implemented together are applicable toward the total savings of at least 15%. No more than 50% of the total energy savings can result from lighting upgrades / changes. Total incentive is capped at 50% of the project cost. The program savings is broken down into three benchmarks; Energy Reduction Plan, Project Implementation, and Measurement and Verification. Each step provides additional incentives as the energy reduction project continues. The benchmark incentives are as follows:

1. Energy Reduction Plan – Upon completion of an energy reduction plan by an approved

program partner, the incentive will grant $0.10 per square foot between $5,000 and $50,000, and not to exceed 50% of the facility’s annual energy expense. (Benchmark #1 is not provided in addition to the local government energy audit program incentive.)

2. Project Implementation – Upon installation of the recommended measures along with the

“Substantial Completion Construction Report,” the incentive will grant savings per KWH or Therm based on the program’s rates. Minimum saving must be 15%. (Example $0.11 / kWh for 15% savings, $0.12/ kWh for 17% savings, … and $1.10 / Therm for 15% savings, $1.20 / Therm for 17% saving, …) Increased incentives result from projected savings above 15%.

3. Measurement and Verification – Upon verification 12 months after implementation of all

recommended measures, that actual savings have been achieved, based on a completed verification report, the incentive will grant additional savings per kWh or Therm based on the program’s rates. Minimum savings must be 15%. (Example $0.07 / kWh for 15% savings, $0.08/ kWh for 17% savings, … and $0.70 / Therm for 15% savings, $0.80 / Therm for 17% saving, …) Increased incentives result from verified savings above 15%.

Page 58: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 57 of 60

Direct Install Program The New Jersey Clean Energy’s Direct Install Program is a state funded program that targets small commercial and industrial facilities with peak demand of less than 100 kW. This turnkey program is aimed at providing owners a seamless, comprehensive process for analysis, equipment replacement and financial incentives to reduce consumption, lower utility costs and improve profitability. The program covers up to 60% of the cost for eligible upgrades including lighting, lighting controls, refrigeration, HVAC, motors, variable speed drives, natural gas and food service. Participating contractors (refer to www.njcleanenergy.com) conduct energy assessments in addition to your standard local government energy audit and install the cost-effective measures. The following measures are potential candidates for Direct Install: Smart Start Program

Prescriptive Measures - The New Jersey Clean Energy’s Smart Start prescriptive measures incentives include unit pricing incentives for installation of energy efficient equipment and controls. Proposed equipment and controls must meet the minimum efficiency requirements as well as other application requirements. The Smart Start prescriptive incentives applicable for new construction, renovations, remodeling and equipment replacements, for a wide range of equipment including:

Electric Chillers Gas Cooling Electric Unitary HVAC Ground Source Heat Pumps Gas Heating Variable Frequency Drives Gas Water Heating Premium Motors Prescriptive Lighting Lighting Controls Technical Studies

Custom Measures - The New Jersey Clean Energy’s Smart Start prescriptive measures incentives include all measures not identified in the prescriptive measures category or measures that must have savings verified through additional analysis such as energy model simulations. Custom measures are intended to include savings as a result of unique energy efficiency measures, which are typically facility specific such as waste heat recovery. Custom incentives are provided based on the amount of energy saved and minimum internal rate of return in order to be eligible.

CEG recommends the District review the use of the above-listed funding options in addition to utilizing their standard method of financing for facilities upgrades in order to fund the proposed energy conservation measures.

Page 59: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 58 of 60

B. Financing Options: Municipal Bonds Municipal bonds are a bond issued by a city or other local government, or their agencies. Potential issuers of municipal bonds include cities, counties, redevelopment agencies, school districts, publicly owned airports and seaports, and any other governmental entity (or group of governments) below the state level. Municipal bonds may be general obligations of the issuer or secured by specified revenues. Interest income received by holders of municipal bonds is often exempt from the federal income tax and from the income tax of the state in which they are issued, although municipal bonds issued for certain purposes may not be tax exempt. Power Purchase Agreement Public Law 2008, Chapter 3 authorizes contracts of up to fifteen (15) years for energy purchase contracts commonly known as “power purchase agreements.” These are programs where the contracting unit (Owner) procures a contract for, in most cases, a third party to install, maintain, and own a renewable energy system. These renewable energy systems are typically solar panels, windmills or other systems that create renewable energy. In exchange for the third party’s work of installing, maintaining and owning the renewable energy system, the contracting unit (Owner) agrees to purchase the power generated by the renewable energy system from the third party at agreed upon energy rates. Energy Savings Improvement Program (ESIP): Public Law 2009, Chapter 4 authorizes government entities to make energy related improvements to their facilities and pay for the costs using the value of energy savings that result from the improvements. The “Energy Savings Improvement Program (ESIP)” law provides a flexible approach that can allow all government agencies in New Jersey to improve and reduce energy usage with minimal expenditure of new financial resources. This program provides public entities to make valuable facility infrastructure improvements that are associated with energy savings. All energy savings projects are eligible as long as the financing period does not extend beyond 15 years. The financing can be utilized for all aspects of energy efficiency project implementation including, energy savings plan development, engineering, construction management, construction management, commissioning, and measurement and verification. This program provides the much needed financing for energy efficiency projects without the burden of increased debt. The program allows for procurement of financing without voter approval or extending existing debt. The program requires evaluation to ensure a positive cash-flow through the entire 15 year financing period. The first phase of implementing an ESIP is the development of an Energy Savings Plan (ESP) to verify the energy savings, construction costs, and overall financial model. The underlining program requirement is the limitation of the project term to 15 years. The ESIP project size is open for multiple buildings to be included within one project. In addition all applicable incentive programs can also be utilized to help reduce the overall construction cost.

Page 60: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 59 of 60

XI. ADDITIONAL RECOMMENDATIONS The following recommendations include no cost/low cost measures, Operation & Maintenance (O&M) items, and water conservation measures with attractive paybacks. These measures are not eligible for the Smart Start Buildings incentives from the office of Clean Energy but save energy none the less.

A. Chemically clean the condenser and evaporator coils periodically to optimize efficiency. Poorly maintained heat transfer surfaces can reduce efficiency 5-10%.

B. Maintain all weather stripping on windows and doors.

C. Clean all light fixtures to maximize light output.

D. Provide more frequent air filter changes to decrease overall system power usage and maintain better IAQ.

E. Verify all thermostats are utilizing setback and scheduling capabilities.

F. Confirm that outside air economizers on the rooftop units are functioning properly to take advantage of free cooling and avoid excess outside air during occupied periods.

G. Educate staff and students on awareness of wasteful energy practices such as leaving lights on unnecessarily, leaving on of non-essential computer and/or equipment at the end of the day, leaving of outside doors/windows open as a means to control room temperature, etc.

Page 61: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Atlantic County Special Services School District Energy Audit

Concord Engineering Group, Inc. 9C11036 November 4, 2011– FINAL Page 60 of 60

XII. ENERGY AUDIT ASSUMPTIONS The assumptions utilized in this energy audit include but are not limited to following:

A. Cost Estimates noted within this report are based on industry accepted costing data such as RS MeansTM Cost Data, contractor pricing and engineering estimates. All cost estimates for this level of auditing are +/- 20%. Prevailing wage rates for the specified region has been utilized to calculate installation costs. The cost estimates indicated within this audit should be utilized by the owner for prioritizing further project development post the energy audit. Project development would include investment grade auditing and detailed engineering.

B. Energy savings noted within this audit are calculated utilizing industry standard procedures and accepted engineering assumptions. For this level of auditing, energy savings are not guaranteed.

C. Information gathering for each facility is strongly based on interviews with operations personnel. Information dependent on verbal feedback is used for calculation assumptions including but not limited to the following:

a. operating hours b. equipment type c. control strategies d. scheduling

D. Information contained within the major equipment list is based on the existing owner documentation where available (drawings, O&M manuals, etc.). If existing owner documentation is not available, catalog information is utilized to populate the required information.

E. Equipment incentives and energy credits are based on current pricing and status of rebate programs. Rebate availability is dependent on the individual program funding and applicability.

F. Equipment (HVAC, Plumbing, Electrical, & Lighting) noted within an ECM recommendation is strictly noted as a basis for calculation of energy savings. The owner should use this equipment information as a benchmark when pursuing further investment grade project development and detailed engineering for specific energy conservation measures.

Utility bill annual averages are utilized for calculation of all energy costs unless otherwise noted. Accuracy of the utility energy usage and costs are based on the information provided. Utility information including usage and costs is estimated where incomplete data is provided.

Page 62: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX A1 of 1

LIFETIME ENERGY SAVINGS

LIFETIME MAINTENANCE

SAVINGSLIFETIME ROI SIMPLE PAYBACK

INTERNAL RATE OF RETURN (IRR)

NET PRESENT VALUE (NPV)

MATERIAL LABORREBATES,

INCENTIVES

NET INSTALLATION

COSTENERGY MAINT. / SREC TOTAL (Yearly Saving * ECM Lifetime)

(Yearly Maint Svaing * ECM Lifetime)

(Lifetime Savings - Net Cost) / (Net Cost)

(Net cost / Yearly Savings)

($) ($) ($) ($) ($/Yr) ($/Yr) ($/Yr) (Yr) ($) ($) (%) (Yr) ($) ($)

ECM #1 Lighting Controls Upgrade $30,600 $7,650 $2,975 $35,275 $4,169 $0 $4,169 15 $62,535 $0 77.3% 8.5 8.19% $14,494.25

ECM #2 Condensing Boiler Upgrade $78,899 $80,079 $4,000 $154,978 $1,611 $3,000 $4,611 24 $110,664 $72,000 -28.6% 33.6 -2.54% ($76,888.22)

ECM #3 VFD on Chilled Water Pumps $29,262 $85,512 $1,914 $112,860 $2,740 $0 $2,740 15 $41,100 $0 -63.6% 41.2 -10.59% ($80,150.06)

ECM #4 Vending Miser Controls $358 $0 $0 $358 $548 $0 $548 15 $8,213 $0 2194.2% 0.7 152.95% $6,178.62

ECM #5 Demand Control Ventilation $3,150 $38,214 $0 $41,364 $2,073 $0 $2,073 15 $31,095 $0 -24.8% 20.0 -3.37% ($16,616.66)

ECM #6 Refrigeration Controls $3,707 $0 $0 $3,707 $770 $0 $770 15 $11,545 $0 211.4% 4.8 19.29% $5,481.15

ECM #7 Boiler Fuel Economizer Controls $3,200 $4,800 $0 $8,000 $1,090 $0 $1,090 15 $16,350 $0 104.4% 7.3 10.63% $5,012.35

ECM #8 Geothermal Bore Field $2,271,500 $2,271,500 $300,000 $4,243,000 $24,562 $0 $24,562 25 $614,050 $0 -85.5% 172.7 -11.42% ($3,815,298.27)

ECM #9 Duct Insulation $35,000 $0 $0 $35,000 $649 $0 $649 15 $9,735 $0 -72.2% 53.9 -12.92% ($27,252.28)

Notes: 1) The variable Cn in the formulas for Internal Rate of Return and Net Present Value stands for the cash flow during each period.2) The variable DR in the NPV equation stands for Discount Rate3) For NPV and IRR calculations: From n=0 to N periods where N is the lifetime of ECM and Cn is the cash flow during each period .

ECM COST & SAVINGS BREAKDOWN

CONCORD ENGINEERING GROUP

Atlantic County Special Services School District

INSTALLATION COST YEARLY SAVINGS

ECM LIFETIMEDESCRIPTIONECM NO.

ECM ENERGY AND FINANCIAL COSTS AND SAVINGS SUMMARY

Page 63: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix B Page 1 of 3

Concord Engineering Group, Inc. 520 BURNT MILL ROAD VOORHEES, NEW JERSEY 08043 PHONE: (856) 427-0200 FAX: (856) 427-6508

SmartStart Building Incentives The NJ SmartStart Buildings Program offers financial incentives on a wide variety of building system equipment. The incentives were developed to help offset the initial cost of energy-efficient equipment. The following tables show the current available incentives as of February, 2010:

Electric Chillers Water-Cooled Chillers $12 - $170 per ton

Air-Cooled Chillers $8 - $52 per ton Energy Efficiency must comply with ASHRAE 90.1-2004

Gas Cooling Gas Absorption Chillers $185 - $400 per ton

Gas Engine-Driven Chillers Calculated through custom measure path)

Desiccant Systems $1.00 per cfm – gas or electric

Electric Unitary HVAC Unitary AC and Split Systems $73 - $93 per ton

Air-to-Air Heat Pumps $73 - $92 per ton Water-Source Heat Pumps $81 per ton

Packaged Terminal AC & HP $65 per ton Central DX AC Systems $40- $72 per ton

Dual Enthalpy Economizer Controls $250 Occupancy Controlled Thermostat

(Hospitality & Institutional Facility) $75 per thermostat

Energy Efficiency must comply with ASHRAE 90.1-2004

Ground Source Heat Pumps

Closed Loop & Open Loop $450 per ton, EER ≥ 16 $600 per ton, EER ≥ 18 $750 per ton, EER ≥ 20

Energy Efficiency must comply with ASHRAE 90.1-2004

Page 64: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix B Page 2 of 3

Gas Heating

Gas Fired Boilers < 300 MBH $300 per unit

Gas Fired Boilers ≥ 300 - 1500 MBH $1.75 per MBH

Gas Fired Boilers ≥1500 - ≤ 4000 MBH $1.00 per MBH

Gas Fired Boilers > 4000 MBH (Calculated through Custom Measure Path)

Gas Furnaces $300 - $400 per unit, AFUE ≥ 92%

Variable Frequency Drives

Variable Air Volume $65 - $155 per hp Chilled-Water Pumps $60 per hp

Compressors $5,250 to $12,500 per drive

Natural Gas Water Heating Gas Water Heaters ≤ 50 gallons $50 per unit

Gas-Fired Water Heaters > 50 gallons $1.00 - $2.00 per MBH Gas-Fired Booster Water Heaters $17 - $35 per MBH Gas Fired Tankless Water Heaters $300 per unit

Prescriptive Lighting Retro fit of T12 to T-5 or T-8 Lamps

w/Electronic Ballast in Existing Facilities

$10 per fixture (1-4 lamps)

Replacement of T12 with new T-5 or T-8 Lamps w/Electronic Ballast in

Existing Facilities

$25 per fixture (1-2 lamps) $30 per fixture (3-4 lamps)

Replacement of incandescent with screw-in PAR 38 or PAR 30 (CFL)

bulb $7 per bulb

T-8 reduced Wattage (28w/25w 4’, 1-4 lamps)

Lamp & ballast replacement $10 per fixture

Hard-Wired Compact Fluorescent $25 - $30 per fixture

Metal Halide w/Pulse Start $25 per fixture LED Exit Signs $10 - $20 per fixture

T-5 and T-8 High Bay Fixtures $16 - $284 per fixture

HID ≥ 100w Retrofit with induction lamp, power coupler and generator

(must be 30% less watts/fixture than HID system)

$50 per fixture

HID ≥ 100w Replacement with new HID ≥ 100w $70 per fixture

LED Refrigerator/Freezer case lighting replacement of fluorescent in medium

and low temperature display case

$42 per 5 foot $65 per 6 foot

Page 65: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix B Page 3 of 3

Lighting Controls – Occupancy Sensors Wall Mounted $20 per control

Remote Mounted $35 per control Daylight Dimmers $25 per fixture

Occupancy Controlled hi-low Fluorescent Controls $25 per fixture controlled

Lighting Controls – HID or Fluorescent Hi-Bay Controls Occupancy hi-low $75 per fixture controlled Daylight Dimming $75 per fixture controlled

Daylight Dimming - office $50 per fixture controlled

Premium Motors Three-Phase Motors $45 - $700 per motor

Fractional HP Motors Electronic Communicated Motors (replacing shaded pole motors in

refrigerator/freezer cases)

$40 per electronic communicated motor

Other Equipment Incentives

Performance Lighting

$1.00 per watt per SF below program incentive threshold, currently 5% more energy efficient than ASHRAE 90.1-

2004 for New Construction and Complete Renovation

Custom Electric and Gas Equipment Incentives not prescriptive

Custom Measures

$0.16 KWh and $1.60/Therm of 1st year savings, or a buy down to a 1 year

payback on estimated savings. Minimum required savings of 75,000 KWh or 1,500 Therms and a IRR of at

least 10%. Multi Measures Bonus 15%

Page 66: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

OMB No. 2060-0347

STATEMENT OF ENERGY PERFORMANCEAtlantic County Special Services School

Building ID: 2867450 For 12-month Period Ending: January 31, 20111

Date SEP becomes ineligible: N/A Date SEP Generated: September 16, 2011

FacilityAtlantic County Special Services School4805 Nawakwa BoulevardMays Landing, NJ 08330

Facility OwnerAtlantic County Special Services School4805 Nawakwa Boulevard mays landing, NJ 08330

Primary Contact for this FacilityJames Rutala717 River Drive Linwood, NJ 08221

Year Built: 2003Gross Floor Area (ft2): 177,000

Energy Performance Rating2 (1-100) 22

Site Energy Use Summary3

Electricity - Grid Purchase(kBtu) 8,678,971 Natural Gas (kBtu)4 2,876,200 Total Energy (kBtu) 11,555,171

Energy Intensity5 Site (kBtu/ft2/yr) 65 Source (kBtu/ft2/yr) 181 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 1,382 Electric Distribution Utility Atlantic City Electric Co [Pepco Holdings Inc] National Average Comparison National Average Site EUI 51 National Average Source EUI 140 % Difference from National Average Source EUI 29% Building Type K-12

School

Stamp of Certifying Professional

Based on the conditions observed at thetime of my visit to this building, I certify that

the information contained within thisstatement is accurate.

Meets Industry Standards6 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A

Certifying ProfessionalMichael Fischette520 South Burnt Mill Road Voorhees, NJ 08043

Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Values represent energy intensity, annualized to a 12-month period.5. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.

The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, Licensed Professional facility inspection, and notarizing the SEP) andwelcomes suggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave.,NW, Washington, D.C. 20460.

EPA Form 5900-16

Appendix C Page 1 of 7

Page 67: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

ENERGY STAR®

Data Checklistfor Commercial Buildings

In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) or a Registered Architect (RA) must validate the accuracy of the data underlyingthe building's energy performance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well asits total energy consumption, to assist the PE or RA in double-checking the information that the building owner or operator has entered into Portfolio Manager.

Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Building Name Atlantic County Special

Services School Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?

Type K-12 School Is this an accurate description of the space inquestion?

Location 4805 Nawakwa Boulevard,Mays Landing, NJ 08330

Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.

Single Structure Single Facility

Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of acute care orchildren's hospitals) nor can they be submitted asrepresenting only a portion of a building

Atlantic County Special Services School (K-12 School)

CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES

Gross Floor Area 177,000 Sq. Ft.

Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.

Open Weekends? No

Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity could includeany time when the space is used for classes,performances or other school or communityactivities. If the building is open on the weekend aspart of the standard schedule during one or moreseasons, the building should select ?yes? for openweekends. The ?yes? response should applywhether the building is open for one or both of theweekend days.

Number of PCs 310 (Default) Is this the number of personal computers in theK12 School?

Number of walk-inrefrigeration/freezer

units 3

Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.

Presence ofcooking facilities Yes

Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students is onlykept warm and/or served to students, or has only agalley that is used by teachers and staff then theanswer is "no".

Percent Cooled 100 % Is this the percentage of the total floor space withinthe facility that is served by mechanical coolingequipment?

Percent Heated 100 % Is this the percentage of the total floor space withinthe facility that is served by mechanical heatingequipment?

Months 10(Optional) Is this school in operation for at least 8 months ofthe year?

Page 1 of 4

Appendix C Page 2 of 7

Page 68: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

High School? No

Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.

Page 2 of 4

Appendix C Page 3 of 7

Page 69: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

ENERGY STAR®

Data Checklistfor Commercial Buildings

Energy ConsumptionPower Generation Plant or Distribution Utility: Atlantic City Electric Co [Pepco Holdings Inc]

Fuel Type: Electricity

Meter: Electric (kWh (thousand Watt-hours))Space(s): Entire Facility

Generation Method: Grid Purchase

Start Date End Date Energy Use (kWh (thousand Watt-hours))

01/01/2011 01/31/2011 169,897.00

12/01/2010 12/31/2010 176,431.00

11/01/2010 11/30/2010 202,925.00

10/01/2010 10/31/2010 219,601.00

09/01/2010 09/30/2010 286,197.00

08/01/2010 08/31/2010 271,613.00

07/01/2010 07/31/2010 283,265.00

06/01/2010 06/30/2010 254,053.00

05/01/2010 05/31/2010 198,894.00

04/01/2010 04/30/2010 148,579.00

03/01/2010 03/31/2010 166,140.00

02/01/2010 02/28/2010 166,066.00

Electric Consumption (kWh (thousand Watt-hours)) 2,543,661.00

Electric Consumption (kBtu (thousand Btu)) 8,678,971.33

Total Electricity (Grid Purchase) Consumption (kBtu (thousand Btu)) 8,678,971.33

Is this the total Electricity (Grid Purchase) consumption at this building including allElectricity meters?

Fuel Type: Natural Gas

Meter: Gas (therms)Space(s): Entire Facility

Start Date End Date Energy Use (therms)

01/01/2011 01/31/2011 7,327.00

12/01/2010 12/31/2010 3,398.00

11/01/2010 11/30/2010 1,354.00

10/01/2010 10/31/2010 238.00

09/01/2010 09/30/2010 21.00

08/01/2010 08/31/2010 92.00

07/01/2010 07/31/2010 104.00

06/01/2010 06/30/2010 558.00

05/01/2010 05/31/2010 933.00

04/01/2010 04/30/2010 2,400.00

Page 3 of 4

Appendix C Page 4 of 7

Page 70: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

03/01/2010 03/31/2010 3,318.00

02/01/2010 02/28/2010 9,019.00

Gas Consumption (therms) 28,762.00

Gas Consumption (kBtu (thousand Btu)) 2,876,200.00

Total Natural Gas Consumption (kBtu (thousand Btu)) 2,876,200.00

Is this the total Natural Gas consumption at this building including all Natural Gas meters?

Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.

On-Site Solar and Wind EnergyDo the fuel consumption totals shown above include all on-site solar and/or wind power located atyour facility? Please confirm that no on-site solar or wind installations have been omitted from thislist. All on-site systems must be reported.

Certifying Professional (When applying for the ENERGY STAR, the Certifying Professional must be the same PE or RA that signed and stamped the SEP.)

Name: _____________________________________________ Date: _____________

Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.

Page 4 of 4

Appendix C Page 5 of 7

Page 71: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.

Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.

FacilityAtlantic County Special Services School4805 Nawakwa BoulevardMays Landing, NJ 08330

Facility OwnerAtlantic County Special Services School4805 Nawakwa Boulevard mays landing, NJ 08330

Primary Contact for this FacilityJames Rutala717 River Drive Linwood, NJ 08221

General InformationAtlantic County Special Services School

Gross Floor Area Excluding Parking: (ft2) 177,000 Year Built 2003 For 12-month Evaluation Period Ending Date: January 31, 2011

Facility Space Use SummaryAtlantic County Special Services School

Space Type K-12 School

Gross Floor Area(ft2) 177,000

Open Weekends? No

Number of PCsd 310

Number of walk-in refrigeration/freezerunits 3

Presence of cooking facilities Yes

Percent Cooled 100

Percent Heated 100

Monthso 10

High School? No

School Districto Atlantic County

Energy Performance ComparisonEvaluation Periods Comparisons

Performance Metrics Current(Ending Date 01/31/2011)

Baseline(Ending Date 01/31/2011) Rating of 75 Target National Average

Energy Performance Rating 22 22 75 N/A 50

Energy Intensity

Site (kBtu/ft2) 65 65 40 N/A 51

Source (kBtu/ft2) 181 181 110 N/A 140

Energy Cost

$/year N/A N/A N/A N/A N/A

$/ft2/year N/A N/A N/A N/A N/A

Greenhouse Gas Emissions

MtCO2e/year 1,382 1,382 839 N/A 1,072

kgCO2e/ft2/year 8 8 5 N/A 6

More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Average column presentsenergy performance data your building would have if your building had an average rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.

Appendix C Page 6 of 7

Page 72: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

2011Atlantic County Special Services School4805 Nawakwa BoulevardMays Landing, NJ 08330

Portfolio Manager Building ID: 2867450

The energy use of this building has been measured and compared to other similar buildings using theEnvironmental Protection Agency’s (EPA’s) Energy Performance Scale of 1–100, with 1 being the least energyefficient and 100 the most energy efficient. For more information, visit energystar.gov/benchmark.

This building’sscore

22

100

Most Efficient

This building uses 181 kBtu per square foot per year.*

*Based on source energy intensity for the 12 month period ending January 2011

Date of certification

Date Generated: 09/16/2011

Statement ofEnergy Performance

1

Least Efficient

50

Average

Buildings with a score of75 or higher may qualifyfor EPA’s ENERGY STAR.

I certify that the information contained within this statement is accurate and in accordance with U.S.Environmental Protection Agency’s measurement standards, found at energystar.gov

Appendix C Page 7 of 7

Page 73: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 1 of 12

AC UnitsTag PRTU-1 PRTU-2,5 PRTU-3,8

Unit Type Packaged Rooftop Packaged Rooftop Packaged Rooftop

Qty 1 2 2

Location Rooftop Rooftop Rooftop

Area ServedMulti Purpose 330 & Surrounding Rooms

Multi Purpose 330,618 & Surrounding Rooms

428-433. Multi-Purpose 435, Kitchen

Manufacturer Trane Voyager Trane Voyager Trane Voyager

Model # YCD180B4LGGA YCD150D4HGAA YCD102C4LGAC

Serial # Z46100241D Z46100275D Z38100096D

Cooling Type DX, R-22 DX, R-22 DX, R-22

Cooling Capacity (Tons) 15 Tons 12.5 Tons 8.5 Tons

Cooling Efficiency (SEER/EER)

11.5 EER 11.3 EER 11 EER

Heating Type Nat Gas HX Nat Gas HX Nat Gas HX

Heating Input (MBH) 250 MBH 250 MBH 135 MBH

Efficiency 80% 80% 80%

Fuel Nat Gas Nat Gas Nat Gas

Approx Age 10 10 10

ASHRAE Service Life 15 15 15

Remaining Life 5 5 5

Comments

Note:

MAJOR EQUIPMENT LISTConcord Engineering Group

Atlantic County Special Services School

"N/A" = Not Applicable. "-" = Info Not Available

Page 74: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 2 of 12

AC UnitsTag

Unit Type

Qty

Location

Area Served

Manufacturer

Model #

Serial #

Cooling Type

Cooling Capacity (Tons)

Cooling Efficiency (SEER/EER)

Heating Type

Heating Input (MBH)

Efficiency

Fuel

Approx Age

ASHRAE Service Life

Remaining Life

Comments

Note:

"N/A" = Not Applicable. "-" = Info Not Available

PRTU-4 PRTU-6 PRTU-7

Packaged Rooftop Packaged Rooftop Packaged Rooftop

1 1 1

Rooftop Rooftop Rooftop

Multi-Purpose 435,442-445

Multi Purpose Room 618

Stage 619

Trane Precedent Trane Voyager Trane

YHC102E4RHA0AD0C

YCD090D4HGBEYSC060A4RHA0EE00

0A100A00

103610261L Z46101328D Z46100317L

DX, R-22 DX, R-22 DX, R-22

8.5 Tons 7.5 Tons 5 Tons

11 EER 10 EER 12 EER

Nat Gas HX Nat Gas HX Nat Gas HX

200 MBH 205 MBH 130 MBH

80% 80% 80%

Nat Gas Nat Gas Nat Gas

10 10 10

15 15 15

5 5 5

Page 75: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 3 of 12

AC UnitsTag

Unit Type

Qty

Location

Area Served

Manufacturer

Model #

Serial #

Cooling Type

Cooling Capacity (Tons)

Cooling Efficiency (SEER/EER)

Heating Type

Heating Input (MBH)

Efficiency

Fuel

Approx Age

ASHRAE Service Life

Remaining Life

Comments

Note:

"N/A" = Not Applicable. "-" = Info Not Available

MUA-1 MUA-2 SS-1

Make Up Air Unit Make Up Air Unit Split Sytem

1 1 4

Rooftop Rooftop Rooftop

Kitchen Hoods Kitchen Hoods Varies

Trane Trane Mitsubishi

GRAA80GFHE0N1JU102A0JRW

GRBA60GFHE0N PU24EK

C01M67245 C01M67246 22E00646B

N/A N/A DX, R-22

N/A N/A 2 Tons

N/A N/A 9.6 EER/ 10.4 SEER

Nat Gas HX Nat Gas HX N/A

800 MBH 600 MBH N/A

80% 80% N/A

Nat Gas Nat Gas N/A

10 10 10

15 15 15

5 5 5

Page 76: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 4 of 12

AC UnitsTag

Unit Type

Qty

Location

Area Served

Manufacturer

Model #

Serial #

Cooling Type

Cooling Capacity (Tons)

Cooling Efficiency (SEER/EER)

Heating Type

Heating Input (MBH)

Efficiency

Fuel

Approx Age

ASHRAE Service Life

Remaining Life

Comments

Note:

"N/A" = Not Applicable. "-" = Info Not Available

SSHP-1Split System Heat

PumpSplit System Heat

PumpSplit Sytem

1 1 3

Rooftop Rooftop Rooftop

Varies Varies Varies

Mitsubishi Mitsubishi Mitsubishi

PUH24EK PUH30EK PU12EK

- - -

DX, R-22 DX, R-22 DX, R-22

2 Tons 2.5 Tons 1 Ton

10.2 EER/SEER 9.6 EER/ 10.6 SEER 10.3 EER/ 11.5 SEER

Heat Pump Heat Pump N/A

25 MBH 33 MBH N/A

6.8 HSPF 7.1 HSPF N/A

Heat Pump Heat Pump N/A

10 10 10

15 15 15

5 5 5

Page 77: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 5 of 12

AC UnitsTag

Unit Type

Qty

Location

Area Served

Manufacturer

Model #

Serial #

Cooling Type

Cooling Capacity (Tons)

Cooling Efficiency (SEER/EER)

Heating Type

Heating Input (MBH)

Efficiency

Fuel

Approx Age

ASHRAE Service Life

Remaining Life

Comments

Note:

"N/A" = Not Applicable. "-" = Info Not Available

Split System Refrigeration CU

1 2

Rooftop Rooftop

Varies Walk in Freezers

Mitsubishi Cold Zone

PUY-A24NHA2 OR-H10H2P-2T-E

8YUO1897A M0194349-0102

DX, R-22 DX, R-22

2 Tons 1/20 HP

13.5 SEER N/A

N/A N/A

N/A N/A

N/A N/A

N/A N/A

10 10

15 15 15

5 5 15

Page 78: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 6 of 12

AHUsTag AHU-1-57

Unit Type Air Handler

Qty 57

Location Ceiling

Area Served Varies

Manufacturer Trane

Model # BCHB

Serial # T01L088719

Cooling Type Chilled Water Coil

Cooling Capacity (MBH) 18,24,39,51,76,92, 142

Cooling Efficiency (SEER/EER)

See Chiller Efficiecny

Heating Type Hot Water Coil

Heating Input (MBH)24,28,60,62,120,146,

158

Efficiency See Boiler Efficiency

Fuel Hot Water

Approx Age 10

ASHRAE Service Life 15

Remaining Life 5

Comments

Note:

MAJOR EQUIPMENT LISTConcord Engineering Group

Atlantic County Special Services School

"N/A" = Not Applicable. "-" = Info Not Available

Page 79: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 7 of 12

BoilersTag B-1,2

Unit Type Cast Iron Section

Qty 2

Location Boiler Room

Area ServedHW coil Air Handling

Units

Manufacturer Burnham

Model # PV1122WNP

Serial # 64358157

Input Capacity (Btu/Hr) 5485 MBH

Rated Output Capacity (Btu/Hr)

4334 MBH

Approx. Efficiency % 80.0%

Fuel Nat Gas

Approx Age 10

ASHRAE Service Life 24

Remaining Life 14

Comments Power Flame Burner - MN = BCCR4-G-25 Max Input = 5480 MBH

Note:

MAJOR EQUIPMENT LIST

Concord Engineering Group

Atlantic County Special Services School

"N/A" = Not Applicable. "-" = Info Not Available

Page 80: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 8 of 12

Cooling TowerTag CH-1

Unit TypeWater Cooled Liquid

Chiller

Qty 1

Location Chiller Room

Area Served Chilled Water Loop

Manufacturer Trane

Model # CVHF 410

Serial # L01M13275

Refrigerant R-123

Cooling Capacity (Tons) 410 Tons

Cooling Efficiency (KW/Ton)

.52 KW/Ton

Volts / Phase / Hz 480/3/60

Fuel -

Chilled Water GPM / ΔT1080 GPM @ 10°F 

ΔTCondenser Water GPM / ΔT

1350 GPM @ 10°F ΔT

Approx Age 10

ASHRAE Service Life 20

Remaining Life 10

Comments

Note:

MAJOR EQUIPMENT LISTConcord Engineering Group

Atlantic County Special Services School

"N/A" = Not Applicable. "-" = Info Not Available

Page 81: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 9 of 12

Cooling TowerTag CT-1,2,3

Unit TypeDraw Thru Steel Cooling Tower

Qty 3

Location Rooftop

Area ServedCondenser Water for

Chiller

Manufacturer Marley

Model # NC1211

Serial # NC8301D1GS

Rated Flow GPM 450 GPM

EWT / LWT 95°F / 85°F

Motor HP 7.5 HP

Electrical 480/3/60

Approx Age 10

ASHRAE Service Life 20

Remaining Life 10

Comments

Note:

MAJOR EQUIPMENT LIST

Concord Engineering Group

Atlantic County Special Services School

"N/A" = Not Applicable. "-" = Info Not Available

Page 82: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 10 of 12

Domestic Water HeatersTag DHW-1 DHW-2,3

Unit Type Gas BoilerDomestic Hot Water

Heater

Qty 1 2

Location Boiler Room Boiler Room

Area Served Building Domestic Kitchen Domestic

ManufacturerAO Smith Burkay

Legend 2000AO Smith Preferred

Cyclone XHE

Model # LW 750 900 BTH 250A 966

Serial # 990 A01 60694 LJ01-1145532-966

Size (Gallons) - 100 Gallons

Input Capacity (MBH/KW)

750 MBH 240 MBH

Recovery (Gal/Hr) - 273 Gal/Hr

Efficiency % 90% 96.00%

Fuel Nat Gas Nat Gas

Approx Age 10 10

ASHRAE Service Life 12 12

Remaining Life 2 2

Comments

Note:

MAJOR EQUIPMENT LIST

Concord Engineering Group

Atlantic County Special Services School

"N/A" = Not Applicable. "-" = Info Not Available

Page 83: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 11 of 12

PumpsTag P-1,2 P-3,4

Unit TypeBoiler Inline Circ

PumpEnd Suction End Suction

Qty 2 2 2

Location Boiler Room Boiler Room Boiler Room

Area Served Boilers 1 & 2 HW to Sections A,B,CHW to Sections

D,E,F,G

Manufacturer Bell & Gossett Sterling Peerless Pump Sterling Peerless Pump

Model # Series 80 F2 1215A F2 1230A

Serial # C067927-01 569722B 569723B

Horse Power 3/4 HP 10 HP 20 HP

Flow 150 GPM223 GPM @ 100

FTHD493 GPM @ 110

FTHD

Motor Info Unknown Info US Electric Motors US Electric Motors

Electrical Power Unknown Info 208-230/460 208-230/460

RPM Unknown Info 1760 RPM 1770 RPM

Motor Efficiency % Unknown Info 89.5% 91.0%

Approx Age 10 10 10

ASHRAE Service Life 20 20 20

Remaining Life 10 16 17

Comments

Note:

MAJOR EQUIPMENT LISTConcord Engineering Group

Atlantic County Special Services School

"N/A" = Not Applicable. "-" = Info Not Available

Page 84: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Appendix D

Page 12 of 12

PumpsTag

Unit Type

Qty

Location

Area Served

Manufacturer

Model #

Serial #

Horse Power

Flow

Motor Info

Electrical Power

RPM

Motor Efficiency %

Approx Age

ASHRAE Service Life

Remaining Life

Comments

Note:

"N/A" = Not Applicable. "-" = Info Not Available

P-5,6 P-7,8 P-9,10

End Suction End Suction End Suction

2 2 2

Chiller Room Chiller Room Chiller Room

Chilled Water Chilled Water Condenser Water

Sterling Peerless Pump Sterling Peerless Pump Sterling Peerless Pump

Unknown Info Unknown Info Unknown Info

Unknown Info Unknown Info Unknown Info

10 HP 25 HP 25 HP

310 GPM @ 80 FTHD 700 GPM @ 80 FTHD1350 GPM @ 60

FTHD

US Electric Motors US Electric Motors US Electric Motors

208-230/460 208/230/460 208/230/460

1760 RPM 1775 RPM 1775 RPM

89.5% 91.7% 91.7%

10 10 10

20 20 20

16 16 16

Page 85: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E1 of 67

CEG Job #: 9C11036

Project: Atlantic County Special Services KWH COST: $0.137

4805 Nawakwa Boulevard

Mays Landing, NJ 08330

Bldg. Sq. Ft.

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 100 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 101 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 102 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 102 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.07 117.0 $16.03 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 103 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232104

Passage3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 105 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 106 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11 107 1800 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 108 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 108 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 109 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 110 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 112 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 113 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 114 500 1 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232115

Vestibule3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

177,000

ACSS School

Page 86: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E2 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 116 1800 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 223.2 $30.58 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 117 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 118 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 119 1800 3 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.20 351.0 $48.09 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 120 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 120 1800 2 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.13 234.0 $32.06 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 120 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11123

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11124

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11125

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 126 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232127

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200127

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4,032.0 $552.38 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 128 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11129

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11130

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11132

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 133 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 134 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 87: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E3 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 135 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 136 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 137 500 5 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.15 75.0 $10.28 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11 138 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 139 1800 5 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.43 774.0 $106.04 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 140 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11142

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11143

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11144

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 145 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232146

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200146

Corridor3600 18 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.44 5,184.0 $710.21 18 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 147 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11148

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11149

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11150

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 152 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 153 1800 14 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

30 0.42 756.0 $103.57 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 154 1800 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 88: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E4 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 155 1800 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232156

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200156

Corridor3600 2 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.16 576.0 $78.91 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560156

Corridor3600 8 1

Recessed Down Light, 26w CFL Lamp

26 0.21 748.8 $102.59 8 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232200

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200200

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4,032.0 $552.38 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 201 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 202 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11203

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11204

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11205

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11206

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11207

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11208

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 209 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 210 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 212 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 213 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 213 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 89: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E5 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232214

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200214

Corridor3600 10 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.80 2,880.0 $394.56 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11215

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11216

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11217

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 218 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 219 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 220 500 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 172.0 $23.56 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 222 500 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 129.0 $17.67 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 223 500 2 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.06 30.0 $4.11 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 224 500 2 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.06 30.0 $4.11 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 225 500 1 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 226 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 227 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 229 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232230

Corridor3600 9 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.77 2,786.4 $381.74 9 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200230

Corridor3600 26 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 2.08 7,488.0 $1,025.86 26 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560230

Corridor3600 8 1

Recessed Down Light, 26w CFL Lamp

26 0.21 748.8 $102.59 8 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.44230

Corridor3600 2 1

1x4, 1 Lamp, 32w T8, Elect. Ballast, Surface MNt., No

Lens32 0.06 230.4 $31.56 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 90: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E6 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11232

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11233

Toilet Room1800 1 8

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11234

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 235 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 236 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 237 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.31 238 1800 18 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

62 1.12 2,008.8 $275.21 18 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 239 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.31 240 500 11 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

62 0.68 341.0 $46.72 11 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11242

Toilet1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21243

Toilet1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 244 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 245 1800 3 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

30 0.09 162.0 $22.19 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 246 1800 4 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.12 216.0 $29.59 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 247 1800 24 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.72 1,296.0 $177.55 24 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11248

Toilet500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 249 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200251

Corridor3600 13 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.04 3,744.0 $512.93 13 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 252 1800 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 334.8 $45.87 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 91: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E7 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 253 1800 7 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.60 1,083.6 $148.45 7 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232300 & 310Corridor

3600 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200300 & 310Corridor

3600 24 21x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.92 6,912.0 $946.94 24 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 301 1800 9 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.77 1,393.2 $190.87 9 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 302 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11303

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11304

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11305

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 306 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 306 500 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.07 32.5 $4.45 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 307 1800 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 223.2 $30.58 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 308 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 309 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 312 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 313 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11314

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11315

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 317 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11317

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 92: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E8 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

211.37 318 500 3 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

30 0.09 45.0 $6.17 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 319 1800 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 223.2 $30.58 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 322 1800 4 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.25 446.4 $61.16 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 322 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.07 117.0 $16.03 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 323 1800 4 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.25 446.4 $61.16 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 323 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.07 117.0 $16.03 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 326 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 328 500 4 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

30 0.12 60.0 $8.22 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 329 1800 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 334.8 $45.87 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

564330

MPR1800 20 9

Pendant Mount Dome Light, 36w CFL

324 6.48 11,664.0 $1,597.97 20 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232330

MPR1800 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 332 1800 6 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.37 669.6 $91.74 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 334 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 337 1800 9 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.56 1,004.4 $137.60 9 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 339 500 4 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.25 124.0 $16.99 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 342 1800 13 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.12 2,012.4 $275.70 13 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.31 342 1800 3 22x2, 2 Lamp, 17w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

34 0.10 183.6 $25.15 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 343 500 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 129.0 $17.67 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 344 500 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 129.0 $17.67 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 93: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E9 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

200345

Corridor3600 11 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.88 3,168.0 $434.02 11 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232346

Commons3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.26 928.8 $127.25 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33346

Commons3600 12 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect34 0.41 1,468.8 $201.23 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560346

Commons3600 7 1

Recessed Down Light, 26w CFL Lamp

26 0.18 655.2 $89.76 7 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 347 500 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 86.0 $11.78 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 349 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200320

Corridor3600 22 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.76 6,336.0 $868.03 22 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 352 500 4 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.12 60.0 $8.22 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 353 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 354 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 355 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 355 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200356

Corridor3600 6 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.48 1,728.0 $236.74 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 357 1800 5 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.31 558.0 $76.45 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 357 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.07 117.0 $16.03 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232358

Toilet Entry3600 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 309.6 $42.42 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 359 1800 5 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.31 558.0 $76.45 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 359 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.07 117.0 $16.03 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 362 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 94: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E10 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 363 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 364 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 365 1800 14 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.20 2,167.2 $296.91 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 365 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 367 1800 15 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.29 2,322.0 $318.11 15 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232400

Corridor3600 6 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.52 1,857.6 $254.49 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200400

Corridor3600 28 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 2.24 8,064.0 $1,104.77 28 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 401 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 402 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 403 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 404 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 405 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 406 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232407

Passage3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 408 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 409 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 410 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 411 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 412 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 95: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E11 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 413 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 414 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 414 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 415 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 416 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 417 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232418

Passage3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 419 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232420

Passage3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 422 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 423 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 424 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 425 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 426 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 427 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 428 1800 2 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.13 234.0 $32.06 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 429 1800 3 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.20 351.0 $48.09 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 429 1800 6 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.37 669.6 $91.74 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 432 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 96: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E12 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 433 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 434 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

562 435 1800 8 1Recessed Down Light, (1)

42w CFL Lamp42 0.34 604.8 $82.86 8 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.11 436 500 2 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 437 1800 1 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.09 154.8 $21.21 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 438 500 3 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

30 0.09 45.0 $6.17 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 439 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232440

Corridor3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.26 928.8 $127.25 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200440

Corridor3600 12 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.96 3,456.0 $473.47 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 442 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 443 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 444 500 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.07 32.5 $4.45 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 445 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 446 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21447

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21448

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11448

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 450 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 452 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 97: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E13 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11453

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11454

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11455

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 456 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 457 500 4 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.25 124.0 $16.99 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 458 500 2 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

30 0.06 30.0 $4.11 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 459 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232460

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200460

Corridor3600 6 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.48 1,728.0 $236.74 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 463 1800 11 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.95 1,702.8 $233.28 11 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 463 1800 4 32x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.14 244.8 $33.54 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 464 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 466 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 467 500 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 129.0 $17.67 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 467 500 5 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.33 162.5 $22.26 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232469

Passage3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232470

Corridor3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.26 928.8 $127.25 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200470

Corridor3600 9 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.72 2,592.0 $355.10 9 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 473 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 98: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E14 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

227.33 473 1800 2 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.07 122.4 $16.77 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 474 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 476 1800 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 223.2 $30.58 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 477 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 478 1800 10 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1,548.0 $212.08 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 478 1800 9 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.31 550.8 $75.46 9 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 478 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11480

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21482

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 484 1800 13 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.12 2,012.4 $275.70 13 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 485 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 487 500 6 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.37 186.0 $25.48 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21488

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21489

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232490

Corridor3600 5 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.43 1,548.0 $212.08 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200490

Corridor3600 20 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.60 5,760.0 $789.12 20 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560 493 500 2 1Recessed Down Light, 26w

CFL Lamp26 0.05 26.0 $3.56 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11494

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21495

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 99: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E15 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 496 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 497 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21498

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21499

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560 500 500 2 1Recessed Down Light, 26w

CFL Lamp26 0.05 26.0 $3.56 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21503

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21504

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 505 500 6 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.37 186.0 $25.48 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 506 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 507 1800 14 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.20 2,167.2 $296.91 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21508

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21509

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 510 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11512

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 513 1800 14 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.20 2,167.2 $296.91 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 514 1800 7 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.60 1,083.6 $148.45 7 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21515

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21516

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21517

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 100: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E16 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 518 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 519 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 520 1800 3 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.10 183.6 $25.15 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 520 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 522 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232600

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200600

Corridor3600 22 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.76 6,336.0 $868.03 22 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 601 1800 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 602 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.31 603 500 2 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.31 604 500 2 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 607 1800 6 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.37 669.6 $91.74 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 608 1800 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 223.2 $30.58 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 609 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232610

Corridor3600 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 309.6 $42.42 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200610

Corridor3600 17 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.36 4,896.0 $670.75 17 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232612

Entry3600 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 309.6 $42.42 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 613 500 4 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.25 124.0 $16.99 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232614

Entry3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 101: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E17 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232615

Ramp3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

561 616 1800 2 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.10 187.2 $25.65 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.11 617 500 3 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

564 618 1800 12 9Pendant Mount Dome Light,

36w CFL324 3.89 6,998.4 $958.78 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

650 618 1800 2 1 Wall Sconce, (1) 27w Lamp 27 0.05 97.2 $13.32 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.31 619 1800 11 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

62 0.68 1,227.6 $168.18 11 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232620

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200620

Corridor3600 5 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.40 1,440.0 $197.28 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21622

Toiler Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21623

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21624

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 625 1800 7 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.60 1,083.6 $148.45 7 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 626 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232627

Corridor3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.26 928.8 $127.25 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 628 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 629 1800 15 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.29 2,322.0 $318.11 15 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 629 1800 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 334.8 $45.87 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232630

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200630

Corridor3600 10 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.80 2,880.0 $394.56 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 102: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E18 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

560630

Corridor3600 2 1

Recessed Down Light, 26w CFL Lamp

26 0.05 187.2 $25.65 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

561 631 1800 1 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.05 93.6 $12.82 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 632 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

561 633 1800 1 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.05 93.6 $12.82 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.11 634 500 1 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 635 500 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 172.0 $23.56 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 636 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 637 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.21 638 500 1 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200640

Corridor3600 5 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.40 1,440.0 $197.28 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 642 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 644 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21645

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21646

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11647

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 648 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 649 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21650

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21652

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 103: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E19 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11653

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 654 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232700

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200700

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4,032.0 $552.38 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 701 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 702 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 703 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 704 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 705 500 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 258.0 $35.35 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 706 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 708 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 709 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232710

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200710

Corridor3600 22 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.76 6,336.0 $868.03 22 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 712 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 713 1800 4 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.25 446.4 $61.16 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21714

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21715

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560716

Change Room500 2 1

Recessed Down Light, 26w CFL Lamp

26 0.05 26.0 $3.56 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 104: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E20 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21718

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21719

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200720

Corridor3600 4 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.32 1,152.0 $157.82 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 722 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21723

Change Room500 2 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560724

Change Room500 2 1

Recessed Down Light, 26w CFL Lamp

26 0.05 26.0 $3.56 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21725

Change Room500 2 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 729 500 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 172.0 $23.56 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232730

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200730

Corridor3600 22 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.76 6,336.0 $868.03 22 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 732 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 733 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 734 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 735 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232736

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232737

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232738

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 739 1800 10 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1,548.0 $212.08 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232740

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 105: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E21 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232741

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232742

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21743

Toilet Room500 1 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens65 0.07 32.5 $4.45 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21744

Toilet Room500 2 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens65 0.13 65.0 $8.91 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232745

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232746

Instruction Rm.500 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 86.0 $11.78 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232747

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 748 1800 10 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1,548.0 $212.08 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232749

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232750

Corridor3600 14 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 1.20 4,334.4 $593.81 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200750

Corridor3600 33 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 2.64 9,504.0 $1,302.05 33 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232752

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232753

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 754 1800 13 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.12 2,012.4 $275.70 13 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 755 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 756 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 757 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 758 1800 13 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.12 2,012.4 $275.70 13 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 759 1800 13 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.12 2,012.4 $275.70 13 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 106: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E22 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 760 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 762 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 763 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 764 1800 13 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.12 2,012.4 $275.70 13 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232765

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232766

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232767

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 768 1800 10 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1,548.0 $212.08 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232769

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232770

Instruction Rm.500 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 86.0 $11.78 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232772

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21773

Toilet Room1800 2 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens65 0.13 234.0 $32.06 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21774

Toilet Room1800 2 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens65 0.13 234.0 $32.06 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232775

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232776

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232777

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 778 1800 10 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1,548.0 $212.08 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 778 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232779

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 107: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E23 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232780

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232782

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 43.0 $5.89 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 783 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 784 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 785 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 786 1800 5 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.43 774.0 $106.04 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 787 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 788 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 789 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 789 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 790 500 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 86.0 $11.78 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 792 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 792 1800 2 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.07 122.4 $16.77 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 793 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11794

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21795

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21796

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 797 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232800

Corridor3600 10 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.86 3,096.0 $424.15 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 108: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E24 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

200800

Corridor3600 18 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.44 5,184.0 $710.21 18 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21800

Corridor3600 2 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.12 446.4 $61.16 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.44800

Corridor3600 2 1

1x4, 1 Lamp, 32w T8, Elect. Ballast, Surface MNt., No

Lens32 0.06 230.4 $31.56 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 801 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11 802 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 803 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 804 1800 13 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.12 2,012.4 $275.70 13 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21805

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11807

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 808 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 809 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11810

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21812

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21813

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 814 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 815 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11816

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21817

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21818

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 109: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E25 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 819 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 823 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 824 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 825 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 826 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 827 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 827 500 2 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

65 0.13 65.0 $8.91 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 828 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 829 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.11830

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21832

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21833

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Prismatic Lens62 0.06 111.6 $15.29 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 834 1800 12 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.03 1,857.6 $254.49 12 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 836 1800 8 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.69 1,238.4 $169.66 8 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 836 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 837 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 838 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 839 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 842 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 110: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E26 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 843 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232844

Passage3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 845 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 846 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 847 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 848 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 849 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 850 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 852 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232853

Passage3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 854 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 855 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 856 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 857 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 858 1800 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 309.6 $42.42 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 859 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232900

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200900

Corridor3600 16 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.28 4,608.0 $631.30 16 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 902 500 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 172.0 $23.56 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 111: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E27 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 903 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 904 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 905 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 906 500 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 172.0 $23.56 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 907 1800 5 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.43 774.0 $106.04 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.31 907 1800 1 22x2, 2 Lamp, 17w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 908 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 909 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 909 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200910

Corridor3600 10 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.80 2,880.0 $394.56 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 913 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 914 3600 2 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560 915 1800 18 1Recessed Down Light, 26w

CFL Lamp26 0.47 842.4 $115.41 18 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

221.33 915 1800 3 21x4, 2 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Direct/ Indirect

58 0.17 313.2 $42.91 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 916 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 917 1800 4 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.25 446.4 $61.16 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 918 1800 6 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.37 669.6 $91.74 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232919

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.34 1,238.4 $169.66 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200919

Corridor3600 2 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.16 576.0 $78.91 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 112: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E28 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

560919

Corridor3600 2 1

Recessed Down Light, 26w CFL Lamp

26 0.05 187.2 $25.65 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200920

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4,032.0 $552.38 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 922 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 923 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 924 1800 7 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.24 428.4 $58.69 7 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 927 1800 5 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.43 774.0 $106.04 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 928 1800 7 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.60 1,083.6 $148.45 7 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 929 1800 7 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.60 1,083.6 $148.45 7 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232930

Commons3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.17 619.2 $84.83 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560930

Commons3600 8 1

Recessed Down Light, 26w CFL Lamp

26 0.21 748.8 $102.59 8 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

650930

Commons3600 6 1 Wall Sconce, (1) 27w Lamp 27 0.16 583.2 $79.90 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

623930

Commons3600 4 8

Hanging Chandelier, (8) 39w CFL Lamp

312 1.25 4,492.8 $615.51 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 935 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 936 1800 15 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.29 2,322.0 $318.11 15 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200940

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4,032.0 $552.38 14 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 942 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 943 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 944 1800 13 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.12 2,012.4 $275.70 13 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200945

Corridor3600 5 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.40 1,440.0 $197.28 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 113: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E29 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 946 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 947 500 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 62.0 $8.49 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 948 500 2 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

30 0.06 30.0 $4.11 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 949 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200950

Corridor3600 20 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.60 5,760.0 $789.12 20 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 951 1800 6 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.52 928.8 $127.25 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 952 500 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 93.0 $12.74 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 953 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200954

Passage3600 16 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.28 4,608.0 $631.30 16 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 955 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 956 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 957 1800 2 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.12 223.2 $30.58 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 958 1800 6 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.37 669.6 $91.74 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 958 1800 1 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.03 61.2 $8.38 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 959 1800 7 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.43 781.2 $107.02 7 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232960

Corridor3600 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.09 309.6 $42.42 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

200960

Corridor3600 8 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.64 2,304.0 $315.65 8 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 962 1800 6 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Pendant Mnt., Prismatic Lens

30 0.18 324.0 $44.39 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

561 963 3600 2 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.10 374.4 $51.29 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 114: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E30 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232964

Corridor3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed Mnt.,

Direct/ Indirect86 0.26 928.8 $127.25 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 965 1800 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 334.8 $45.87 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 966 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 967 1800 3 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.19 334.8 $45.87 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 968 1800 3 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.26 464.4 $63.62 3 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 969 500 1 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.06 31.0 $4.25 1 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 970 3600 8 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.69 2,476.8 $339.32 8 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

562 970 3600 9 1Recessed Down Light, (1)

42w CFL Lamp42 0.38 1,360.8 $186.43 9 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.44 970 3600 4 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface MNt., No Lens

32 0.13 460.8 $63.13 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 972 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 973 1800 22 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 0.75 1,346.4 $184.46 22 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 974 1800 5 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.31 558.0 $76.45 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 975 1800 5 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.31 558.0 $76.45 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 976 1800 4 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.34 619.2 $84.83 4 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560977

Toilet Entry3600 2 1

Recessed Down Light, 26w CFL Lamp

26 0.05 187.2 $25.65 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

227.33978 Fast Seating,

979 Café and 982 Dinning

1800 52 22x2, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

34 1.77 3,182.4 $435.99 52 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

560978 Fast Seating,

979 Café and 982 Dinning

1800 55 1Recessed Down Light, 26w

CFL Lamp26 1.43 2,574.0 $352.64 55 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 980 1800 18 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 1.55 2,786.4 $381.74 18 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 981 500 5 22x4, 2 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Prismatic Lens

62 0.31 155.0 $21.24 5 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Page 115: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

Investment Grade Lighting Audit APPENDIX E31 of 67

EXISTING LIGHTING PROPOSED LIGHTING SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Retro-Unit Watts Total kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Lamps Description Used kW Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

211.41 984 500 6 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.18 90.0 $12.33 6 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 985 500 10 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.30 150.0 $20.55 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 987 3600 10 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.30 1,080.0 $147.96 10 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

232 991 3600 9 32x4, 3 Lamp, 32w T8, Elect.

Ballast, Recessed Mnt., Direct/ Indirect

86 0.77 2,786.4 $381.74 9 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 992 500 15 11x4, 1 Lamp, 32w T8, Elect.

Ballast, Surface Mnt., Prismatic Lens

30 0.45 225.0 $30.83 15 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

561 992 500 2 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.10 52.0 $7.12 2 0 No Change 0 0.00 0 $0.00 $0.00 $0.00 0.00 0 $0.00 0.00

Totals 2,901 1414 481,600 $65,979 2,901 0 0.0 0 $0 $0 0.0 0 $0 #DIV/0!

Page 116: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E32 of 67

CEG Job #: 9C11036

Project: Atlantic County Special Services KWH COST: $0.137

Address: 1000 Holy Oak Drive

Mays Landing, NJ 08330Building SF: FALSE

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 100 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 101 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 102 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 102 1800 1 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.065 117 $16.03 1 No Change 65 0.07 0% 117 $16.03 $0.00 $0.00 0.00 0 $0.00 0.00

232 103 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232104

Passage3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 105 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 106 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

222.11 107 1800 1 22x4, 2 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

62 0.062 111.6 $15.29 1 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 108 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 108 1800 1 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.034 61.2 $8.38 1 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

232 109 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 110 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 112 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 113 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

198,270

Page 117: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E33 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 114 500 1 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232115

Vestibule3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 116 1800 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 223.2 $30.58 2 0 No Change 62 0.12 0% 223.2 $30.58 $0.00 $0.00 0.00 0 $0.00 0.00

232 117 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 118 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 119 1800 3 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.195 351 $48.09 3 0 No Change 65 0.20 0% 351 $48.09 $0.00 $0.00 0.00 0 $0.00 0.00

232 120 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 120 1800 2 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.13 234 $32.06 2 0 No Change 65 0.13 0% 234 $32.06 $0.00 $0.00 0.00 0 $0.00 0.00

232 120 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.11123

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11124

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11125

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 126 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232127

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

200127

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4032 $552.38 14 0 No Change 80 1.12 0% 4032 $552.38 $0.00 $0.00 0.00 0 $0.00 0.00

232 128 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

Page 118: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E34 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11129

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.11130

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11132

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 133 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 134 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 135 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 136 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 137 500 5 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.15 75 $10.28 5 0 No Change 30 0.15 0% 75 $10.28 $0.00 $0.00 0.00 0 $0.00 0.00

222.11 138 500 1 22x4, 2 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 139 1800 5 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.43 774 $106.04 5 0 No Change 86 0.43 0% 774 $106.04 $0.00 $0.00 0.00 0 $0.00 0.00

232 140 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.11142

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11143

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11144

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 145 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232146

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

Page 119: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E35 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

200146

Corridor3600 18 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.44 5184 $710.21 18 0 No Change 80 1.44 0% 5184 $710.21 $0.00 $0.00 0.00 0 $0.00 0.00

232 147 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.11148

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.11149

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11150

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 152 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

211.37 153 1800 14 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

30 0.42 756 $103.57 14 0 No Change 30 0.42 0% 756 $103.57 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 154 1800 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 155 1800 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232156

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

200156

Corridor3600 2 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.16 576 $78.91 2 0 No Change 80 0.16 0% 576 $78.91 $0.00 $0.00 0.00 0 $0.00 0.00

560156

Corridor3600 8 1

Recessed Down Light, 26w CFL Lamp

26 0.208 748.8 $102.59 8 0 No Change 26 0.21 0% 748.8 $102.59 $0.00 $0.00 0.00 0 $0.00 0.00

232200

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

200200

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4032 $552.38 14 0 No Change 80 1.12 0% 4032 $552.38 $0.00 $0.00 0.00 0 $0.00 0.00

232 201 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 202 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

Page 120: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E36 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11203

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.11204

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.11205

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.11206

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.11207

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11208

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 209 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 210 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 212 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 213 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

227.33 213 1800 1 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.034 61.2 $8.38 1 0 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

232214

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

200214

Corridor3600 10 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.8 2880 $394.56 10 0 No Change 80 0.80 0% 2880 $394.56 $0.00 $0.00 0.00 0 $0.00 0.00

222.11215

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.11216

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11217

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

Page 121: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E37 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 218 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 219 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 220 500 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 172 $23.56 4 0 No Change 86 0.34 0% 172 $23.56 $0.00 $0.00 0.00 0 $0.00 0.00

232 222 500 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 129 $17.67 3 0 No Change 86 0.26 0% 129 $17.67 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 223 500 2 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.06 30 $4.11 2 0 No Change 30 0.06 0% 30 $4.11 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 224 500 2 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.06 30 $4.11 2 0 No Change 30 0.06 0% 30 $4.11 $0.00 $0.00 0.00 0 $0.00 0.00

232 225 500 1 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232 226 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 227 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 229 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232230

Corridor3600 9 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.774 2786.4 $381.74 9 0 No Change 86 0.77 0% 2786.4 $381.74 $0.00 $0.00 0.00 0 $0.00 0.00

200230

Corridor3600 26 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 2.08 7488 $1,025.86 26 0 No Change 80 2.08 0% 7488 $1,025.86 $0.00 $0.00 0.00 0 $0.00 0.00

560230

Corridor3600 8 1

Recessed Down Light, 26w CFL Lamp

26 0.208 748.8 $102.59 8 0 No Change 26 0.21 0% 748.8 $102.59 $0.00 $0.00 0.00 0 $0.00 0.00

211.44230

Corridor3600 2 1

1x4, 1 Lamp, 32w T8, Elect. Ballast, Surface

MNt., No Lens32 0.064 230.4 $31.56 2 0 No Change 32 0.06 0% 230.4 $31.56 $0.00 $0.00 0.00 0 $0.00 0.00

222.11232

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.11233

Toilet Room1800 1 8

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

Page 122: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E38 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11234

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 235 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 236 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 237 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

221.31 238 1800 18 21x4, 2 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

62 1.116 2008.8 $275.21 18 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

62 0.89 20% 1607.04 $220.16 $450.00 $450.00 0.22 401.76 $55.04 8.18

232 239 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

221.31 240 500 11 21x4, 2 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

62 0.682 341 $46.72 11 0 No Change 62 0.68 0% 341 $46.72 $0.00 $0.00 0.00 0 $0.00 0.00

222.11242

Toilet1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21243

Toilet1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 244 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 245 1800 3 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

30 0.09 162 $22.19 3 0 No Change 30 0.09 0% 162 $22.19 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 246 1800 4 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.12 216 $29.59 4 0 No Change 30 0.12 0% 216 $29.59 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 247 1800 24 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.72 1296 $177.55 24 0 No Change 30 0.72 0% 1296 $177.55 $0.00 $0.00 0.00 0 $0.00 0.00

222.11248

Toilet500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 249 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

200251

Corridor3600 13 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.04 3744 $512.93 13 0 No Change 80 1.04 0% 3744 $512.93 $0.00 $0.00 0.00 0 $0.00 0.00

Page 123: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E39 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 252 1800 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 334.8 $45.87 3 0 No Change 62 0.19 0% 334.8 $45.87 $0.00 $0.00 0.00 0 $0.00 0.00

232 253 1800 7 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.602 1083.6 $148.45 7 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.48 20% 866.88 $118.76 $450.00 $450.00 0.12 216.72 $29.69 15.16

232300 & 310Corridor

3600 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

200300 & 310Corridor

3600 24 21x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.92 6912 $946.94 24 0 No Change 80 1.92 0% 6912 $946.94 $0.00 $0.00 0.00 0 $0.00 0.00

232 301 1800 9 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.774 1393.2 $190.87 9 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.62 20% 1114.56 $152.69 $450.00 $450.00 0.15 278.64 $38.17 11.79

232 302 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.11303

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11304

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11305

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 306 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 306 500 1 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.065 32.5 $4.45 1 0 No Change 65 0.07 0% 32.5 $4.45 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 307 1800 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 223.2 $30.58 2 0 No Change 62 0.12 0% 223.2 $30.58 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 308 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

232 309 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 312 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 313 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

Page 124: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E40 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11314

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11315

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 317 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.11317

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 318 500 3 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

30 0.09 45 $6.17 3 0 No Change 30 0.09 0% 45 $6.17 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 319 1800 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 223.2 $30.58 2 0 No Change 62 0.12 0% 223.2 $30.58 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 322 1800 4 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.248 446.4 $61.16 4 0 No Change 62 0.25 0% 446.4 $61.16 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 322 1800 1 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.065 117 $16.03 1 0 No Change 65 0.07 0% 117 $16.03 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 323 1800 4 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.248 446.4 $61.16 4 0 No Change 62 0.25 0% 446.4 $61.16 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 323 1800 1 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.065 117 $16.03 1 0 No Change 65 0.07 0% 117 $16.03 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 326 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 328 500 4 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

30 0.12 60 $8.22 4 0 No Change 30 0.12 0% 60 $8.22 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 329 1800 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 334.8 $45.87 3 0 No Change 62 0.19 0% 334.8 $45.87 $0.00 $0.00 0.00 0 $0.00 0.00

564330

MPR1800 20 9

Pendant Mount Dome Light,36w CFL

324 6.48 11664 $1,597.97 20 0 No Change 324 6.48 0% 11664 $1,597.97 $0.00 $0.00 0.00 0 $0.00 0.00

232330

MPR1800 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 332 1800 6 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.372 669.6 $91.74 6 0 No Change 62 0.37 0% 669.6 $91.74 $0.00 $0.00 0.00 0 $0.00 0.00

Page 125: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E41 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 334 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 337 1800 9 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.558 1004.4 $137.60 9 0 No Change 62 0.56 0% 1004.4 $137.60 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 339 500 4 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.248 124 $16.99 4 0 No Change 62 0.25 0% 124 $16.99 $0.00 $0.00 0.00 0 $0.00 0.00

232 342 1800 13 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.118 2012.4 $275.70 13 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.89 20% 1609.92 $220.56 $450.00 $450.00 0.22 402.48 $55.14 8.16

227.31 342 1800 3 22x2, 2 Lamp, 17w T8,

Elect. Ballast, Recessed Mnt., Prismatic Lens

34 0.102 183.6 $25.15 3 0 No Change 34 0.10 0% 183.6 $25.15 $0.00 $0.00 0.00 0 $0.00 0.00

232 343 500 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 129 $17.67 3 0 No Change 86 0.26 0% 129 $17.67 $0.00 $0.00 0.00 0 $0.00 0.00

232 344 500 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 129 $17.67 3 0 No Change 86 0.26 0% 129 $17.67 $0.00 $0.00 0.00 0 $0.00 0.00

200345

Corridor3600 11 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.88 3168 $434.02 11 0 No Change 80 0.88 0% 3168 $434.02 $0.00 $0.00 0.00 0 $0.00 0.00

232346

Commons3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.258 928.8 $127.25 3 0 No Change 86 0.26 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

227.33346

Commons3600 12 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect34 0.408 1468.8 $201.23 12 1

Dual Tech. Occupancy Sensor w/ (1) 2 Pole Powerpack -

Remote Mnt.34 0.33 20% 1175.04 $160.98 $450.00 $450.00 0.08 293.76 $40.25 11.18

560346

Commons3600 7 1

Recessed Down Light, 26w CFL Lamp

26 0.182 655.2 $89.76 7 0 No Change 26 0.18 0% 655.2 $89.76 $0.00 $0.00 0.00 0 $0.00 0.00

232 347 500 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 86 $11.78 2 0 No Change 86 0.17 0% 86 $11.78 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 349 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

200320

Corridor3600 22 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.76 6336 $868.03 22 0 No Change 80 1.76 0% 6336 $868.03 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 352 500 4 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.12 60 $8.22 4 0 No Change 30 0.12 0% 60 $8.22 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 353 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

Page 126: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E42 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 354 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 355 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 355 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

200356

Corridor3600 6 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.48 1728 $236.74 6 0 No Change 80 0.48 0% 1728 $236.74 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 357 1800 5 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.31 558 $76.45 5 0 No Change 62 0.31 0% 558 $76.45 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 357 1800 1 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.065 117 $16.03 1 0 No Change 65 0.07 0% 117 $16.03 $0.00 $0.00 0.00 0 $0.00 0.00

232358

Toilet Entry3600 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 309.6 $42.42 1 0 No Change 86 0.09 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 359 1800 5 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.31 558 $76.45 5 0 No Change 62 0.31 0% 558 $76.45 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 359 1800 1 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.065 117 $16.03 1 0 No Change 65 0.07 0% 117 $16.03 $0.00 $0.00 0.00 0 $0.00 0.00

232 362 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 363 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 364 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 365 1800 14 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.204 2167.2 $296.91 14 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.96 20% 1733.76 $237.53 $450.00 $450.00 0.24 433.44 $59.38 7.58

227.33 365 1800 1 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.034 61.2 $8.38 1 0 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

232 367 1800 15 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.29 2322 $318.11 15 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 1.03 20% 1857.6 $254.49 $450.00 $450.00 0.26 464.4 $63.62 7.07

232400

Corridor3600 6 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.516 1857.6 $254.49 6 0 No Change 86 0.52 0% 1857.6 $254.49 $0.00 $0.00 0.00 0 $0.00 0.00

Page 127: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E43 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

200400

Corridor3600 28 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 2.24 8064 $1,104.77 28 0 No Change 80 2.24 0% 8064 $1,104.77 $0.00 $0.00 0.00 0 $0.00 0.00

232 401 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 402 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 403 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 404 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 405 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 406 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232407

Passage3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

232 408 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 409 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 410 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 411 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 412 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 413 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 414 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 414 1800 1 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.034 61.2 $8.38 1 0 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

Page 128: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E44 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 415 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 416 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 417 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232418

Passage3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 419 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232420

Passage3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

232 422 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 423 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 424 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 425 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 426 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 427 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 428 1800 2 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.13 234 $32.06 2 0 No Change 65 0.13 0% 234 $32.06 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 429 1800 3 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.195 351 $48.09 3 0 No Change 65 0.20 0% 351 $48.09 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 429 1800 6 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.372 669.6 $91.74 6 0 No Change 62 0.37 0% 669.6 $91.74 $0.00 $0.00 0.00 0 $0.00 0.00

232 432 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

Page 129: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E45 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 433 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

232 434 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

562 435 1800 8 1Recessed Down Light, (1)

42w CFL Lamp42 0.336 604.8 $82.86 8 0 No Change 42 0.34 0% 604.8 $82.86 $0.00 $0.00 0.00 0 $0.00 0.00

221.11 436 500 2 21x4, 2 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

232 437 1800 1 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.086 154.8 $21.21 1 0 No Change 86 0.09 0% 154.8 $21.21 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 438 500 3 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

30 0.09 45 $6.17 3 0 No Change 30 0.09 0% 45 $6.17 $0.00 $0.00 0.00 0 $0.00 0.00

232 439 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232440

Corridor3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.258 928.8 $127.25 3 0 No Change 86 0.26 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

200440

Corridor3600 12 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.96 3456 $473.47 12 0 No Change 80 0.96 0% 3456 $473.47 $0.00 $0.00 0.00 0 $0.00 0.00

232 442 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 443 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 444 500 1 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.065 32.5 $4.45 1 0 No Change 65 0.07 0% 32.5 $4.45 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 445 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

232 446 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.21447

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21448

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

Page 130: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E46 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11448

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 450 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 452 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.11453

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11454

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11455

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 456 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.21 457 500 4 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.248 124 $16.99 4 0 No Change 62 0.25 0% 124 $16.99 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 458 500 2 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

30 0.06 30 $4.11 2 0 No Change 30 0.06 0% 30 $4.11 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 459 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232460

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

200460

Corridor3600 6 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.48 1728 $236.74 6 0 No Change 80 0.48 0% 1728 $236.74 $0.00 $0.00 0.00 0 $0.00 0.00

232 463 1800 11 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.946 1702.8 $233.28 11 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.76 20% 1362.24 $186.63 $450.00 $450.00 0.19 340.56 $46.66 9.64

227.33 463 1800 4 32x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.136 244.8 $33.54 4 0 No Change 34 0.14 0% 244.8 $33.54 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 464 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

232 466 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

Page 131: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E47 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 467 500 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 129 $17.67 3 0 No Change 86 0.26 0% 129 $17.67 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 467 500 5 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.325 162.5 $22.26 5 0 No Change 65 0.33 0% 162.5 $22.26 $0.00 $0.00 0.00 0 $0.00 0.00

232469

Passage3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

232470

Corridor3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.258 928.8 $127.25 3 0 No Change 86 0.26 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

200470

Corridor3600 9 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.72 2592 $355.10 9 0 No Change 80 0.72 0% 2592 $355.10 $0.00 $0.00 0.00 0 $0.00 0.00

232 473 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 473 1800 2 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.068 122.4 $16.77 2 0 No Change 34 0.07 0% 122.4 $16.77 $0.00 $0.00 0.00 0 $0.00 0.00

232 474 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 476 1800 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 223.2 $30.58 2 0 No Change 62 0.12 0% 223.2 $30.58 $0.00 $0.00 0.00 0 $0.00 0.00

232 477 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 478 1800 10 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1548 $212.08 10 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.69 20% 1238.4 $169.66 $450.00 $450.00 0.17 309.6 $42.42 10.61

227.33 478 1800 9 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.306 550.8 $75.46 9 0 No Change 34 0.31 0% 550.8 $75.46 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 478 1800 1 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.034 61.2 $8.38 1 0 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

222.11480

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21482

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 484 1800 13 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.118 2012.4 $275.70 13 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.89 20% 1609.92 $220.56 $450.00 $450.00 0.22 402.48 $55.14 8.16

Page 132: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E48 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 485 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.21 487 500 6 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.372 186 $25.48 6 0 No Change 62 0.37 0% 186 $25.48 $0.00 $0.00 0.00 0 $0.00 0.00

222.21488

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21489

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232490

Corridor3600 5 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.43 1548 $212.08 5 0 No Change 86 0.43 0% 1548 $212.08 $0.00 $0.00 0.00 0 $0.00 0.00

200490

Corridor3600 20 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.6 5760 $789.12 20 0 No Change 80 1.60 0% 5760 $789.12 $0.00 $0.00 0.00 0 $0.00 0.00

560 493 500 2 1Recessed Down Light, 26w

CFL Lamp26 0.052 26 $3.56 2 0 No Change 26 0.05 0% 26 $3.56 $0.00 $0.00 0.00 0 $0.00 0.00

222.11494

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21495

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 496 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 497 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.21498

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21499

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

560 500 500 2 1Recessed Down Light, 26w

CFL Lamp26 0.052 26 $3.56 2 0 No Change 26 0.05 0% 26 $3.56 $0.00 $0.00 0.00 0 $0.00 0.00

222.21503

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21504

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

Page 133: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E49 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 505 500 6 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.372 186 $25.48 6 0 No Change 62 0.37 0% 186 $25.48 $0.00 $0.00 0.00 0 $0.00 0.00

232 506 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 507 1800 14 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.204 2167.2 $296.91 14 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.96 20% 1733.76 $237.53 $450.00 $450.00 0.24 433.44 $59.38 7.58

222.21508

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21509

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 510 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.11512

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 513 1800 14 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.204 2167.2 $296.91 14 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.96 20% 1733.76 $237.53 $450.00 $450.00 0.24 433.44 $59.38 7.58

232 514 1800 7 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.602 1083.6 $148.45 7 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.48 20% 866.88 $118.76 $450.00 $450.00 0.12 216.72 $29.69 15.16

222.21515

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21516

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21517

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 518 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 519 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 520 1800 3 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.102 183.6 $25.15 3 0 No Change 34 0.10 0% 183.6 $25.15 $0.00 $0.00 0.00 0 $0.00 0.00

232 520 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

Page 134: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E50 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

227.33 522 1800 1 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.034 61.2 $8.38 1 0 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

232600

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

200600

Corridor3600 22 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.76 6336 $868.03 22 0 No Change 80 1.76 0% 6336 $868.03 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 601 1800 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 602 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

221.31 603 500 2 21x4, 2 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

221.31 604 500 2 21x4, 2 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 607 1800 6 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.372 669.6 $91.74 6 0 No Change 62 0.37 0% 669.6 $91.74 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 608 1800 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 223.2 $30.58 2 0 No Change 62 0.12 0% 223.2 $30.58 $0.00 $0.00 0.00 0 $0.00 0.00

232 609 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232610

Corridor3600 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 309.6 $42.42 1 0 No Change 86 0.09 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

200610

Corridor3600 17 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.36 4896 $670.75 17 0 No Change 80 1.36 0% 4896 $670.75 $0.00 $0.00 0.00 0 $0.00 0.00

232612

Entry3600 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 309.6 $42.42 1 0 No Change 86 0.09 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 613 500 4 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.248 124 $16.99 4 0 No Change 62 0.25 0% 124 $16.99 $0.00 $0.00 0.00 0 $0.00 0.00

232614

Entry3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232615

Ramp3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

Page 135: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E51 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

561 616 1800 2 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.104 187.2 $25.65 2 0 No Change 52 0.10 0% 187.2 $25.65 $0.00 $0.00 0.00 0 $0.00 0.00

221.11 617 500 3 21x4, 2 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

564 618 1800 12 9Pendant Mount Dome Light,

36w CFL324 3.888 6998.4 $958.78 12 0 No Change 324 3.89 0% 6998.4 $958.78 $0.00 $0.00 0.00 0 $0.00 0.00

650 618 1800 2 1 Wall Sconce, (1) 27w Lamp 27 0.054 97.2 $13.32 2 0 No Change 27 0.05 0% 97.2 $13.32 $0.00 $0.00 0.00 0 $0.00 0.00

221.31 619 1800 11 21x4, 2 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

62 0.682 1227.6 $168.18 11 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

62 0.55 20% 982.08 $134.54 $450.00 $450.00 0.14 245.52 $33.64 13.38

232620

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

200620

Corridor3600 5 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.4 1440 $197.28 5 0 No Change 80 0.40 0% 1440 $197.28 $0.00 $0.00 0.00 0 $0.00 0.00

222.21622

Toiler Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21623

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21624

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 625 1800 7 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.602 1083.6 $148.45 7 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.48 20% 866.88 $118.76 $450.00 $450.00 0.12 216.72 $29.69 15.16

232 626 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

232627

Corridor3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.258 928.8 $127.25 3 0 No Change 86 0.26 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 628 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 629 1800 15 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.29 2322 $318.11 15 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 1.03 20% 1857.6 $254.49 $450.00 $450.00 0.26 464.4 $63.62 7.07

222.21 629 1800 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 334.8 $45.87 3 0 No Change 62 0.19 0% 334.8 $45.87 $0.00 $0.00 0.00 0 $0.00 0.00

Page 136: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E52 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232630

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

200630

Corridor3600 10 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.8 2880 $394.56 10 0 No Change 80 0.80 0% 2880 $394.56 $0.00 $0.00 0.00 0 $0.00 0.00

560630

Corridor3600 2 1

Recessed Down Light, 26w CFL Lamp

26 0.052 187.2 $25.65 2 0 No Change 26 0.05 0% 187.2 $25.65 $0.00 $0.00 0.00 0 $0.00 0.00

561 631 1800 1 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.052 93.6 $12.82 1 0 No Change 52 0.05 0% 93.6 $12.82 $0.00 $0.00 0.00 0 $0.00 0.00

232 632 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

561 633 1800 1 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.052 93.6 $12.82 1 0 No Change 52 0.05 0% 93.6 $12.82 $0.00 $0.00 0.00 0 $0.00 0.00

221.11 634 500 1 21x4, 2 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 635 500 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 172 $23.56 4 0 No Change 86 0.34 0% 172 $23.56 $0.00 $0.00 0.00 0 $0.00 0.00

232 636 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 637 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

221.21 638 500 1 21x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

200640

Corridor3600 5 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.4 1440 $197.28 5 0 No Change 80 0.40 0% 1440 $197.28 $0.00 $0.00 0.00 0 $0.00 0.00

232 642 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 644 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.21645

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21646

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

Page 137: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E53 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11647

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 648 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 649 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.21650

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21652

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11653

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 654 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232700

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

200700

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4032 $552.38 14 0 No Change 80 1.12 0% 4032 $552.38 $0.00 $0.00 0.00 0 $0.00 0.00

232 701 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 702 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 703 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 704 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 705 500 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 258 $35.35 6 0 No Change 86 0.52 0% 258 $35.35 $0.00 $0.00 0.00 0 $0.00 0.00

232 706 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.21 708 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

Page 138: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E54 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 709 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

232710

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

200710

Corridor3600 22 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.76 6336 $868.03 22 0 No Change 80 1.76 0% 6336 $868.03 $0.00 $0.00 0.00 0 $0.00 0.00

232 712 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.21 713 1800 4 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.248 446.4 $61.16 4 0 No Change 62 0.25 0% 446.4 $61.16 $0.00 $0.00 0.00 0 $0.00 0.00

222.21714

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21715

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

560716

Change Room500 2 1

Recessed Down Light, 26w CFL Lamp

26 0.052 26 $3.56 2 0 No Change 26 0.05 0% 26 $3.56 $0.00 $0.00 0.00 0 $0.00 0.00

222.21718

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21719

Change Room500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

200720

Corridor3600 4 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.32 1152 $157.82 4 0 No Change 80 0.32 0% 1152 $157.82 $0.00 $0.00 0.00 0 $0.00 0.00

232 722 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.21723

Change Room500 2 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

560724

Change Room500 2 1

Recessed Down Light, 26w CFL Lamp

26 0.052 26 $3.56 2 0 No Change 26 0.05 0% 26 $3.56 $0.00 $0.00 0.00 0 $0.00 0.00

222.21725

Change Room500 2 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

232 729 500 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 172 $23.56 4 0 No Change 86 0.34 0% 172 $23.56 $0.00 $0.00 0.00 0 $0.00 0.00

Page 139: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E55 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232730

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

200730

Corridor3600 22 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.76 6336 $868.03 22 0 No Change 80 1.76 0% 6336 $868.03 $0.00 $0.00 0.00 0 $0.00 0.00

232 732 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 733 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 734 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 735 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232736

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232737

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232738

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232 739 1800 10 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1548 $212.08 10 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.69 20% 1238.4 $169.66 $450.00 $450.00 0.17 309.6 $42.42 10.61

232740

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232741

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232742

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

227.21743

Toilet Room500 1 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.065 32.5 $4.45 1 0 No Change 65 0.07 0% 32.5 $4.45 $0.00 $0.00 0.00 0 $0.00 0.00

227.21744

Toilet Room500 2 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.13 65 $8.91 2 0 No Change 65 0.13 0% 65 $8.91 $0.00 $0.00 0.00 0 $0.00 0.00

232745

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

Page 140: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E56 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232746

Instruction Rm.500 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 86 $11.78 2 0 No Change 86 0.17 0% 86 $11.78 $0.00 $0.00 0.00 0 $0.00 0.00

232747

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232 748 1800 10 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1548 $212.08 10 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.69 20% 1238.4 $169.66 $450.00 $450.00 0.17 309.6 $42.42 10.61

232749

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232750

Corridor3600 14 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 1.204 4334.4 $593.81 14 0 No Change 86 1.20 0% 4334.4 $593.81 $0.00 $0.00 0.00 0 $0.00 0.00

200750

Corridor3600 33 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 2.64 9504 $1,302.05 33 0 No Change 80 2.64 0% 9504 $1,302.05 $0.00 $0.00 0.00 0 $0.00 0.00

232752

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232753

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232 754 1800 13 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.118 2012.4 $275.70 13 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.89 20% 1609.92 $220.56 $450.00 $450.00 0.22 402.48 $55.14 8.16

222.21 755 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 756 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 757 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

232 758 1800 13 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.118 2012.4 $275.70 13 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.89 20% 1609.92 $220.56 $450.00 $450.00 0.22 402.48 $55.14 8.16

232 759 1800 13 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.118 2012.4 $275.70 13 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.89 20% 1609.92 $220.56 $450.00 $450.00 0.22 402.48 $55.14 8.16

222.21 760 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 762 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

Page 141: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E57 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21 763 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

232 764 1800 13 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.118 2012.4 $275.70 13 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.89 20% 1609.92 $220.56 $450.00 $450.00 0.22 402.48 $55.14 8.16

232765

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232766

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232767

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232 768 1800 10 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1548 $212.08 10 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.69 20% 1238.4 $169.66 $450.00 $450.00 0.17 309.6 $42.42 10.61

232769

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232770

Instruction Rm.500 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 86 $11.78 2 0 No Change 86 0.17 0% 86 $11.78 $0.00 $0.00 0.00 0 $0.00 0.00

232772

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

227.21773

Toilet Room1800 2 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.13 234 $32.06 2 0 No Change 65 0.13 0% 234 $32.06 $0.00 $0.00 0.00 0 $0.00 0.00

227.21774

Toilet Room1800 2 2

2x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.13 234 $32.06 2 0 No Change 65 0.13 0% 234 $32.06 $0.00 $0.00 0.00 0 $0.00 0.00

232775

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232776

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232777

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232 778 1800 10 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.86 1548 $212.08 10 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.69 20% 1238.4 $169.66 $450.00 $450.00 0.17 309.6 $42.42 10.61

227.33 778 1800 1 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.034 61.2 $8.38 1 0 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

Page 142: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E58 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232779

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232780

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

232782

Instruction Rm.500 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 43 $5.89 1 0 No Change 86 0.09 0% 43 $5.89 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 783 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 784 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

232 785 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 786 1800 5 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.43 774 $106.04 5 0 No Change 86 0.43 0% 774 $106.04 $0.00 $0.00 0.00 0 $0.00 0.00

232 787 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 788 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 789 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 789 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 790 500 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 86 $11.78 2 0 No Change 86 0.17 0% 86 $11.78 $0.00 $0.00 0.00 0 $0.00 0.00

232 792 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 792 1800 2 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.068 122.4 $16.77 2 0 No Change 34 0.07 0% 122.4 $16.77 $0.00 $0.00 0.00 0 $0.00 0.00

232 793 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.11794

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

Page 143: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E59 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21795

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21796

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 797 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232800

Corridor3600 10 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.86 3096 $424.15 10 0 No Change 86 0.86 0% 3096 $424.15 $0.00 $0.00 0.00 0 $0.00 0.00

200800

Corridor3600 18 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.44 5184 $710.21 18 0 No Change 80 1.44 0% 5184 $710.21 $0.00 $0.00 0.00 0 $0.00 0.00

222.21800

Corridor3600 2 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 446.4 $61.16 2 0 No Change 62 0.12 0% 446.4 $61.16 $0.00 $0.00 0.00 0 $0.00 0.00

211.44800

Corridor3600 2 1

1x4, 1 Lamp, 32w T8, Elect. Ballast, Surface

MNt., No Lens32 0.064 230.4 $31.56 2 0 No Change 32 0.06 0% 230.4 $31.56 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 801 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

222.11 802 500 2 22x4, 2 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

232 803 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 804 1800 13 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.118 2012.4 $275.70 13 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.89 20% 1609.92 $220.56 $450.00 $450.00 0.22 402.48 $55.14 8.16

222.21805

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.11807

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 808 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 809 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.11810

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

Page 144: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E60 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.21812

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21813

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 814 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 815 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

222.11816

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21817

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21818

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 819 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 823 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 824 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 825 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 826 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 827 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

227.21 827 500 2 22x2, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens65 0.13 65 $8.91 2 0 No Change 65 0.13 0% 65 $8.91 $0.00 $0.00 0.00 0 $0.00 0.00

232 828 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 829 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

Page 145: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E61 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

222.11830

Time Out500 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Surface Mnt.,

Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21832

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

222.21833

Toilet Room1800 1 2

2x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 111.6 $15.29 1 0 No Change 62 0.06 0% 111.6 $15.29 $0.00 $0.00 0.00 0 $0.00 0.00

232 834 1800 12 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.032 1857.6 $254.49 12 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.83 20% 1486.08 $203.59 $450.00 $450.00 0.21 371.52 $50.90 8.84

232 836 1800 8 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.688 1238.4 $169.66 8 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.55 20% 990.72 $135.73 $450.00 $450.00 0.14 247.68 $33.93 13.26

227.33 836 1800 1 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.034 61.2 $8.38 1 0 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

232 837 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 838 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 839 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 842 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 843 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232844

Passage3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 845 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 846 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 847 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 848 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

Page 146: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E62 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 849 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 850 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 852 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232853

Passage3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

232 854 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

232 855 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 856 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 857 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

232 858 1800 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 309.6 $42.42 2 0 No Change 86 0.17 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 859 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232900

Corridor3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

200900

Corridor3600 16 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.28 4608 $631.30 16 0 No Change 80 1.28 0% 4608 $631.30 $0.00 $0.00 0.00 0 $0.00 0.00

232 902 500 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 172 $23.56 4 0 No Change 86 0.34 0% 172 $23.56 $0.00 $0.00 0.00 0 $0.00 0.00

232 903 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 904 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 905 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

Page 147: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E63 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 906 500 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 172 $23.56 4 0 No Change 86 0.34 0% 172 $23.56 $0.00 $0.00 0.00 0 $0.00 0.00

232 907 1800 5 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.43 774 $106.04 5 0 No Change 86 0.43 0% 774 $106.04 $0.00 $0.00 0.00 0 $0.00 0.00

227.31 907 1800 1 22x2, 2 Lamp, 17w T8,

Elect. Ballast, Recessed Mnt., Prismatic Lens

34 0.034 61.2 $8.38 1 0 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 908 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 909 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 909 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

200910

Corridor3600 10 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.8 2880 $394.56 10 0 No Change 80 0.80 0% 2880 $394.56 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 913 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 914 3600 2 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

560 915 1800 18 1Recessed Down Light, 26w

CFL Lamp26 0.468 842.4 $115.41 18 0 No Change 26 0.47 0% 842.4 $115.41 $0.00 $0.00 0.00 0 $0.00 0.00

221.33 915 1800 3 21x4, 2 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Direct/ Indirect

58 0.174 313.2 $42.91 3 0 No Change 58 0.17 0% 313.2 $42.91 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 916 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 917 1800 4 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.248 446.4 $61.16 4 0 No Change 62 0.25 0% 446.4 $61.16 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 918 1800 6 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.372 669.6 $91.74 6 0 No Change 62 0.37 0% 669.6 $91.74 $0.00 $0.00 0.00 0 $0.00 0.00

232919

Corridor3600 4 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.344 1238.4 $169.66 4 0 No Change 86 0.34 0% 1238.4 $169.66 $0.00 $0.00 0.00 0 $0.00 0.00

200919

Corridor3600 2 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.16 576 $78.91 2 0 No Change 80 0.16 0% 576 $78.91 $0.00 $0.00 0.00 0 $0.00 0.00

Page 148: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E64 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

560919

Corridor3600 2 1

Recessed Down Light, 26w CFL Lamp

26 0.052 187.2 $25.65 2 0 No Change 26 0.05 0% 187.2 $25.65 $0.00 $0.00 0.00 0 $0.00 0.00

200920

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4032 $552.38 14 0 No Change 80 1.12 0% 4032 $552.38 $0.00 $0.00 0.00 0 $0.00 0.00

232 922 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 923 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

227.33 924 1800 7 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.238 428.4 $58.69 7 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

34 0.19 20% 342.72 $46.95 $450.00 $450.00 0.05 85.68 $11.74 38.34

232 927 1800 5 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.43 774 $106.04 5 0 No Change 86 0.43 0% 774 $106.04 $0.00 $0.00 0.00 0 $0.00 0.00

232 928 1800 7 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.602 1083.6 $148.45 7 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.48 20% 866.88 $118.76 $450.00 $450.00 0.12 216.72 $29.69 15.16

232 929 1800 7 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.602 1083.6 $148.45 7 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.48 20% 866.88 $118.76 $450.00 $450.00 0.12 216.72 $29.69 15.16

232930

Commons3600 2 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.172 619.2 $84.83 2 0 No Change 86 0.17 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

560930

Commons3600 8 1

Recessed Down Light, 26w CFL Lamp

26 0.208 748.8 $102.59 8 0 No Change 26 0.21 0% 748.8 $102.59 $0.00 $0.00 0.00 0 $0.00 0.00

650930

Commons3600 6 1 Wall Sconce, (1) 27w Lamp 27 0.162 583.2 $79.90 6 0 No Change 27 0.16 0% 583.2 $79.90 $0.00 $0.00 0.00 0 $0.00 0.00

623930

Commons3600 4 8

Hanging Chandelier, (8) 39w CFL Lamp

312 1.248 4492.8 $615.51 4 0 No Change 312 1.25 0% 4492.8 $615.51 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 935 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

232 936 1800 15 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.29 2322 $318.11 15 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 1.03 20% 1857.6 $254.49 $450.00 $450.00 0.26 464.4 $63.62 7.07

200940

Corridor3600 14 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.12 4032 $552.38 14 0 No Change 80 1.12 0% 4032 $552.38 $0.00 $0.00 0.00 0 $0.00 0.00

232 942 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

Page 149: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E65 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

232 943 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 944 1800 13 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.118 2012.4 $275.70 13 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 0.89 20% 1609.92 $220.56 $450.00 $450.00 0.22 402.48 $55.14 8.16

200945

Corridor3600 5 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.4 1440 $197.28 5 0 No Change 80 0.40 0% 1440 $197.28 $0.00 $0.00 0.00 0 $0.00 0.00

232 946 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 947 500 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 62 $8.49 2 0 No Change 62 0.12 0% 62 $8.49 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 948 500 2 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

30 0.06 30 $4.11 2 0 No Change 30 0.06 0% 30 $4.11 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 949 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

200950

Corridor3600 20 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.6 5760 $789.12 20 0 No Change 80 1.60 0% 5760 $789.12 $0.00 $0.00 0.00 0 $0.00 0.00

232 951 1800 6 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.516 928.8 $127.25 6 0 No Change 86 0.52 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 952 500 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 93 $12.74 3 0 No Change 62 0.19 0% 93 $12.74 $0.00 $0.00 0.00 0 $0.00 0.00

232 953 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

200954

Passage3600 16 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 1.28 4608 $631.30 16 0 No Change 80 1.28 0% 4608 $631.30 $0.00 $0.00 0.00 0 $0.00 0.00

232 955 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

232 956 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 957 1800 2 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.124 223.2 $30.58 2 0 No Change 62 0.12 0% 223.2 $30.58 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 958 1800 6 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.372 669.6 $91.74 6 0 No Change 62 0.37 0% 669.6 $91.74 $0.00 $0.00 0.00 0 $0.00 0.00

Page 150: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E66 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

227.33 958 1800 1 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.034 61.2 $8.38 1 0 No Change 34 0.03 0% 61.2 $8.38 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 959 1800 7 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.434 781.2 $107.02 7 0 No Change 62 0.43 0% 781.2 $107.02 $0.00 $0.00 0.00 0 $0.00 0.00

232960

Corridor3600 1 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.086 309.6 $42.42 1 0 No Change 86 0.09 0% 309.6 $42.42 $0.00 $0.00 0.00 0 $0.00 0.00

200960

Corridor3600 8 2

1x4, 2 Lamp, 40w Biax, Elect. Ballast, Recessed

Mnt., Wall Wash80 0.64 2304 $315.65 8 0 No Change 80 0.64 0% 2304 $315.65 $0.00 $0.00 0.00 0 $0.00 0.00

211.37 962 1800 6 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Pendant Mnt.,Prismatic Lens

30 0.18 324 $44.39 6 0 No Change 30 0.18 0% 324 $44.39 $0.00 $0.00 0.00 0 $0.00 0.00

561 963 3600 2 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.104 374.4 $51.29 2 0 No Change 52 0.10 0% 374.4 $51.29 $0.00 $0.00 0.00 0 $0.00 0.00

232964

Corridor3600 3 3

2x4, 3 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Direct/ Indirect86 0.258 928.8 $127.25 3 0 No Change 86 0.26 0% 928.8 $127.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 965 1800 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 334.8 $45.87 3 0 No Change 62 0.19 0% 334.8 $45.87 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 966 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 967 1800 3 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.186 334.8 $45.87 3 0 No Change 62 0.19 0% 334.8 $45.87 $0.00 $0.00 0.00 0 $0.00 0.00

232 968 1800 3 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.258 464.4 $63.62 3 0 No Change 86 0.26 0% 464.4 $63.62 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 969 500 1 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.062 31 $4.25 1 0 No Change 62 0.06 0% 31 $4.25 $0.00 $0.00 0.00 0 $0.00 0.00

232 970 3600 8 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.688 2476.8 $339.32 8 0 No Change 86 0.69 0% 2476.8 $339.32 $0.00 $0.00 0.00 0 $0.00 0.00

562 970 3600 9 1Recessed Down Light, (1)

42w CFL Lamp42 0.378 1360.8 $186.43 9 1

Dual Tech. Occupancy Sensor w/ (1) 2 Pole Powerpack -

Remote Mnt.42 0.30 20% 1088.64 $149.14 $450.00 $450.00 0.08 272.16 $37.29 12.07

211.44 970 3600 4 11x4, 1 Lamp, 32w T8, Elect. Ballast, Surface

MNt., No Lens32 0.128 460.8 $63.13 4 0 No Change 32 0.13 0% 460.8 $63.13 $0.00 $0.00 0.00 0 $0.00 0.00

232 972 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

Page 151: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX E67 of 67

ECM #2: Lighting Controls

EXISTING LIGHTING PROPOSED LIGHTING CONTROLS SAVINGSCEG Fixture Yearly No. No. Fixture Fixt Total kWh/Yr Yearly No. No. Controls Watts Total Reduction kWh/Yr Yearly Unit Cost Total kW kWh/Yr Yearly Yearly Simple

Type Location Usage Fixts Lamps Type Watts kW Fixtures $ Cost Fixts Cont. Description Used kW (%) Fixtures $ Cost (INSTALLED) Cost Savings Savings $ Savings Payback

227.33 973 1800 22 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 0.748 1346.4 $184.46 22 0 No Change 34 0.75 0% 1346.4 $184.46 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 974 1800 5 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.31 558 $76.45 5 0 No Change 62 0.31 0% 558 $76.45 $0.00 $0.00 0.00 0 $0.00 0.00

222.21 975 1800 5 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.31 558 $76.45 5 0 No Change 62 0.31 0% 558 $76.45 $0.00 $0.00 0.00 0 $0.00 0.00

232 976 1800 4 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.344 619.2 $84.83 4 0 No Change 86 0.34 0% 619.2 $84.83 $0.00 $0.00 0.00 0 $0.00 0.00

560977

Toilet Entry3600 2 1

Recessed Down Light, 26w CFL Lamp

26 0.052 187.2 $25.65 2 0 No Change 26 0.05 0% 187.2 $25.65 $0.00 $0.00 0.00 0 $0.00 0.00

227.33978 Fast Seating,

979 Café and 982 Dinning

1800 52 22x2, 2 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

34 1.768 3182.4 $435.99 52 0 No Change 34 1.77 0% 3182.4 $435.99 $0.00 $0.00 0.00 0 $0.00 0.00

560978 Fast Seating,

979 Café and 982 Dinning

1800 55 1Recessed Down Light, 26w

CFL Lamp26 1.43 2574 $352.64 55 0 No Change 26 1.43 0% 2574 $352.64 $0.00 $0.00 0.00 0 $0.00 0.00

232 980 1800 18 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 1.548 2786.4 $381.74 18 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

86 1.24 20% 2229.12 $305.39 $450.00 $450.00 0.31 557.28 $76.35 5.89

222.21 981 500 5 22x4, 2 Lamp, 32w T8, Elect. Ballast, Recessed

Mnt., Prismatic Lens62 0.31 155 $21.24 5 0 No Change 62 0.31 0% 155 $21.24 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 984 500 6 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.18 90 $12.33 6 0 No Change 30 0.18 0% 90 $12.33 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 985 500 10 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.3 150 $20.55 10 0 No Change 30 0.30 0% 150 $20.55 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 987 3600 10 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.3 1080 $147.96 10 1Dual Tech. Occupancy Sensor

w/ (1) 2 Pole Powerpack - Remote Mnt.

30 0.24 20% 864 $118.37 $450.00 $450.00 0.06 216 $29.59 15.21

232 991 3600 9 32x4, 3 Lamp, 32w T8,

Elect. Ballast, Recessed Mnt., Direct/ Indirect

86 0.774 2786.4 $381.74 9 0 No Change 86 0.77 0% 2786.4 $381.74 $0.00 $0.00 0.00 0 $0.00 0.00

211.41 992 500 15 11x4, 1 Lamp, 32w T8,

Elect. Ballast, Surface Mnt., Prismatic Lens

30 0.45 225 $30.83 15 0 No Change 30 0.45 0% 225 $30.83 $0.00 $0.00 0.00 0 $0.00 0.00

561 992 500 2 2Wall Mtd Fixture, (2) 26w

CFL Lamp52 0.104 52 $7.12 2 0 No Change 52 0.10 0% 52 $7.12 $0.00 $0.00 0.00 0 $0.00 0.00

Totals 2,901 1414 223.2 481,600.2 $65,979.23 2,901 85 206.6 451,168.7 $61,810.11 $38,250 16.69 30,432 $4,169 9.17

Page 152: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX F

1 of 2

Building Area (sq ft) Panel QtyPanel Sq

Ft

Panel Total Sq

Ft

Total KWDC

Total Annual

kWh

Panel Weight (43

lbs)W/SQFT

Atlantic County Special Services

School - Roof

Trina PA05 230W

2678 25.0 66,950 615.94 710,235 115,154 9.20

Note:1. Panel Square Feet value includes clearance allowance.

Proposed PV Layout Utilizing Solar Dock Roof Mounting System (10 deg)

Notes:

1. Estimated kWH based on the National Renewable Energy Laboratory PVWatts Version 1 Calculator Program.

Page 153: LOCAL GOVERNMENT ENERGY AUDIT PROGRAM ENERGY … · 11/4/2011  · ECM #4 Vending Miser Controls 0.0 3,997 0 ECM #5 Demand Control Ventilation 0.0 9,990 546 ECM #6 Refrigeration Controls

APPENDIX F

2 of 2

Project Name: LGEA Solar PV Project - Atlantic County Special Services School

Location: Mays Landing, NJDescription: Photovoltaic System 100% Financing - 15 year

Simple Payback Analysis

Total Construction Cost $2,329,458

Annual kWh Production 710,235

Annual Energy Cost Reduction $97,302

Average Annual SREC Revenue $273,870

Simple Payback: Years

Life Cycle Cost Analysis

Analysis Period (years): 15 Financing %: 100%

Discount Rate: 3% Maintenance Escalation Rate: 3.0%

Average Energy Cost ($/kWh) $0.137 Energy Cost Escalation Rate: 3.0%

Financing Rate: 6.00% Average SREC Value ($/kWh) $0.386

Period Additional Energy kWh Energy Cost Additional SREC Interest Loan Net Cash Cumulative

Cash Outlay Production Savings Maint Costs Revenue Expense Principal Flow Cash Flow

0 $0 0 0 0 $0 0 0 0 0

1 $0 710,235 $97,302 $0 $390,629 $137,080 $98,808 $252,044 $252,044

2 $0 706,684 $100,221 $0 $388,676 $130,985 $104,902 $253,010 $505,054

3 $0 703,150 $103,228 $0 $351,575 $124,515 $111,372 $218,916 $723,969

4 $0 699,635 $106,325 $0 $314,836 $117,646 $118,241 $185,273 $909,242

5 $0 696,136 $109,514 $7,170 $313,261 $110,353 $125,534 $179,718 $1,088,961

6 $0 692,656 $112,800 $7,134 $311,695 $102,610 $133,277 $181,473 $1,270,434

7 $0 689,193 $116,184 $7,099 $275,677 $94,390 $141,497 $148,875 $1,419,308

8 $0 685,747 $119,669 $7,063 $274,299 $85,663 $150,224 $151,017 $1,570,326

9 $0 682,318 $123,260 $7,028 $238,811 $76,397 $159,490 $119,155 $1,689,481

10 $0 678,906 $126,957 $6,993 $237,617 $66,561 $169,327 $121,694 $1,811,175

11 $0 675,512 $130,766 $6,958 $202,654 $56,117 $179,771 $90,574 $1,901,750

12 $0 672,134 $134,689 $6,923 $201,640 $45,029 $190,859 $93,519 $1,995,269

13 $0 668,773 $138,730 $6,888 $167,193 $33,257 $202,630 $63,147 $2,058,416

14 $0 665,430 $142,892 $6,854 $166,357 $20,759 $215,128 $66,508 $2,124,923

15 $0 662,102 $147,178 $6,820 $132,420 $7,491 $228,397 $36,892 $2,161,815

Totals: 10,288,611 $1,809,715 $76,930 $3,967,342 $1,208,854 $2,329,458 $2,161,815 $21,482,167

Net Present Value (NPV)

Photovoltaic System 100% Financing - 15 year

6.28

$1,714,558


Recommended