Low Expansion Foam • NFPA 11 • class B – flammable liquids, FP < 100 0 F – combustible liquids FP > 100 0 F • forms blanket • 2-D horizontal surface • tank farms, airports etc.
Transcript
Page 1: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Low Expansion Foam

• NFPA 11

• class B– flammable liquids, FP < 1000F– combustible liquids FP > 1000F

• forms blanket

• 2-D horizontal surface

• tank farms, airports etc.

Page 2: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Expansion Ratio

Classification Range

Low expansion up to 20:1

Medium 20:1 to 100:1

High 200:1 to 1000:1

Page 3: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Components of Foam

Air– within bubbles– most of volume

Concentrate– to be mixed with water– final concentration 3% or 6%

Water– water + concentrate = solution

Page 4: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Types of Foam

Protein– older type– no film– from animal protein– little in use now

Page 5: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Types of Foam

Fluoroprotein– better than protein– forms film

Page 6: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Types of Foam

Aqueous Film Forming Foam– AFFF– most common for fuels– thin film– not for alcohols

Page 7: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Types of Foam

Alcohol Resistant– also “Alcohol type”– for small alcohols– methanol, ethanol etc– from membrane bewteen water and foam

Page 8: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Types of Foam

Chemical– chemically generated foam– obsolete

Page 9: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Proportioning Methods

• To mix concentrate with water

• either 3% or 6% concentrate in water

• 3 mechanisms– Venturi proportioner– Pressure proportioner– Balanced pressure proportioner– skip details

Page 10: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Types of Systems

Mobile– fire dept. trucks

Semi-Fixed– permanent piping, foam makers– mobile concentrate and pump

Page 11: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Types of Systems

Fixed– Subsurface injection– Surface application– seal protection for floating roofs– dike protection

Page 12: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Sub-Surface Injection

• Fixed roof storage tank

• foam applied below surface

• floats to surface

• gentle, uniform application

• fluoroprotein foam

• has good fuel-shedding properties

Page 13: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Sub-Surface Injection-design

1. Calculate fuel surface area

A =( )( r)2

2. Determine application rate (R) and discharge time (T)

• see 3.8

Page 14: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Sub-Surface Injection-design

3. Calculate discharge rate (D) and foam concentrate quantity (Q)

D = (A) x (R)

Q = (A) x (R) x (T) x (%)

4. Determine the number of subsurface application outlets

• see 3.9

Page 15: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Sub-Surface Injection-design

5. Determine supplementary requirements– number of hoses (see 3-10)– discharge time (see 3-11)

6. Calculate supplementary discharge rate (Ds) and foam quantity (Qs)

Ds = (N) x (50 gpm)

Qs = (N) x (50 gpm) x (Ts) x (%)

Page 16: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Sub-Surface Injection-design

Total requirement for concentrate

Qtotal = Q + Qs

see example 3.1

Page 17: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Surface Application

• Fixed discharge units

• on rim of tank

Page 18: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Surface Injection-design

1. Calculate fuel surface area

A =( )( r)2

2. Determine application rate (R) and discharge time (T)

• see 3.14

• note difference between types I and II

Page 19: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Surface Injection-design

3. Calculate discharge rate (D) and foam concentrate quantity (Q)

D = (A) x (R)

Q = (A) x (R) x (T) x (%)

4. Determine the number of surface application outlets

• see 3.15

Page 20: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Surface Injection-design

5. Determine supplementary requirements– number of hoses (see 3-10)– discharge time (see 3-11)

6. Calculate supplementary discharge rate (Ds) and foam quantity (Qs)

Ds = (N) x (50 gpm)

Qs = (N) x (50 gpm) x (Ts) x (%)

Page 21: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Surface Injection-design

Total requirement for concentrate

Qtotal = Q + Qs

see example 3.2

Page 22: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Seal ProtectionFloating Roof Tanks

• No vapour space

• gap at edge of roof a problem

• seal spans gap

Page 23: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Floating Roof Tanks-design

1. Calculate fuel surface area

A = total roof area - unprotected roof area

A =( )( r1)2 - ( )( r2)2

2. Determine application rate (R) and discharge time (T)

• R = .30 gpm/ft2

• T = 20 min.

Page 24: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Floating Roof Tanks-design

3. Calculate discharge rate (D) and foam concentrate quantity (Q)

D = (A) x (R)

Q = (A) x (R) x (T) x (%)

4. Determine the spacing of outlets

• see text

Page 25: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Floating Roof Tanks-design

5. Determine number of discharge devices

N = C/S

N = number

C = circumference ( x diameter)

S = maximum spacing

Page 26: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Floating Roof Tanks-design

6. Determine supplementary requirements– number of hoses (see 3-10)– discharge time (see 3-11)

7. Calculate supplementary discharge rate (Ds) and foam quantity (Qs)

Ds = (N) x (50 gpm)

Qs = (N) x (50 gpm) x (Ts) x (%)

Page 27: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Floating Roof Tanks-design

Total requirement for concentrate

Qtotal = Q + Qs

see example 3.3

Page 28: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Dike Protection

• To contain tank farm

Page 29: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Dike Protection- Design

1. Calculate dike surface area

A = dike length x dike width

2. Determine application rate (R) and discharge time (T)

R = .10 gpm/ft2 fixed outlets

R = .16 gpm/ft2 monitors

T = 30 min., flamm. liquids

T = 20 min., comb. liquids

Page 30: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Dike Protection- Design

3. Calculate discharge rate (D) and foam concentrate quantity (Q)

D = (A) x (R)

Q = (A) x (R) x (T) x (%)

4. Determine the number of discharge devices

• every 30 ft

N = (2L + 2W)/30

see 3.4

Page 31: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Aircraft Hangers

• omit

Page 32: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Truck Loading Rack

Page 33: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Truck Loading Rack

Hazards

Page 34: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Truck Loading Rack

Strategy

Page 35: Low Expansion Foam NFPA 11 class B –flammable liquids, FP < 100 0 F –combustible liquids FP > 100 0 F forms blanket 2-D horizontal surface tank farms,

Truck Loading Rack

Design


Recommended