LumaSMART Fluoroptic-Based Winding Hot Spot Temperature Sensor for Generation, Transmission and Distribution Transformers LumaSMART is the fifth generation Fluoroptic®-based thermometry system from LumaSense. By providing direct and real-time winding hotspot measurements, utilities can: • Implement Dynamic Loading • Extend the Life of Transformers • Reduce Costly Failures • Maximize Safe Performance
Transcript
Page 1: LumaSMART - ATECorp.com...LumaSense Technologies’ LumaSMART winding hot spot temperature system is the most advanced and reliable real-time monitoring solution available today. LumaSense

LumaSMART

Fluoroptic-Based Winding Hot Spot Temperature Sensor for Generation, Transmission and Distribution Transformers

LumaSMART is the fifth generation Fluoroptic®-based thermometry system from LumaSense. By providing direct and real-time winding hotspot measurements, utilities can:

• ImplementDynamicLoading

• ExtendtheLifeofTransformers

• ReduceCostlyFailures

• MaximizeSafePerformance

Page 2: LumaSMART - ATECorp.com...LumaSense Technologies’ LumaSMART winding hot spot temperature system is the most advanced and reliable real-time monitoring solution available today. LumaSense

LumaSenseTechnologies’LumaSMARTwindinghotspottemperaturesystemisthemostadvancedandreliablereal-timemonitoringsolutionavailabletoday.LumaSenseistheleaderinFluoroptic®(FOT)Technology,withdecadesofprovenexpertise.TheLumaSMARTFOThotspotmonitoringsystemsprovideaccurate,real-timetemperaturereadingsforprotectionandcontrolofyourcriticalpowertransformerassets.

LumaSense’sPFAteflon-jacketedFluoroptic probesareconsideredthestandardintheindustry. Featuring five-layer protection in their fiber optic encapsulation for 99% installation success,theyarespeciallydesignedtowithstandharshenvironmentswithoutdeterioratingphysicallyoraffectingtheaccuracyofthetemperaturemeasurement.

LumaSenseTechnologies’LUXTRONbrandistheworldleaderinfiberoptictemperaturemeasurementintrans-formers.Withmorethan30yearsoffiberopticexperi-

ence,LumaSensecontinuestoleadthewayininnovationofnew,robusttechnology.

Measuring Hot Spot Winding Temperature Transformersoftentakethebruntofanoverloadcondi-tion.Monitoring the transformer winding hot spot is critical to safeguard your transformer from damage and extend its usage.Transformerlifeisdirectlyrelatedtothelifeoftheinternalpaperinsulation.Theinsulatingpaper’slifeisdirectlyaffectedbyitsexposuretohightemperature.ThehighesttemperatureonthewindingsistheWindingHotSpot,wheretheinsulatingpaperwilldeterioratefirst.Conventionalmethodssimulateorcalcu-latethistemperature,butdonotaccuratelymeasureit.Theonlytruewayofknowingtheactualtemperatureisthroughreal-timefiberopticmeasurement.Ourreliable,accuratemonitorsquicklydetectandrespondtohotspotconditions,triggeringalarmsandrelaystoprotectyourmostvaluableassets.

ExceptionalReliabilityandAccuracyinWindingHotSpotsTemperatureMonitoring

SmartGridPowerTransformerHotSpotsTemperatureMonitoring

Page 3: LumaSMART - ATECorp.com...LumaSense Technologies’ LumaSMART winding hot spot temperature system is the most advanced and reliable real-time monitoring solution available today. LumaSense

TheLumaSMARTController

LumaSenseTechnologies’LumaSMARTcontrolleristhenewestinnovationfromtheleaderinFOTtechnology.BuildingontheprovenperformanceoftheThermAsset2,thismonitorprovidesallofthecapabilitiesofitsprede-cessorwhileaddingsmartgridcapabilities,aninnovativetouchscreenandextendedchannelandrelaycapabilities.

• Easilyadaptabletouser-specificneedswith4to16channelsand0,8or16Form-Cprogrammablerelays

• ±2°Caccuracyovertheentiretemperaturerangeforthelifeoftransformerwithnocalibration

• Nodrift,nocalibrationrequired

• AnalogoutputsandModbus,DNP3,ASCIIandIEC61850communicationcapabilitystandard

• RS-232CandRS-485,EthernetandUSBserialoutputs

• Lightsourcelaststhelifeofthetransformer

• Interactivetouchscreendisplayforalarms,notificationsandset-up

• Equippedwith2GBstandarddatastoragefortrans-formerlifetimememorystorage

• On-boarddiagnosticstroubleshootingguidance

FluoropticProbesThemeasurementperfor-manceofLUXTRONprobesexceedscommontempera-turesensorsinenvironmentswithhighvoltage,radiofrequencyinterference(RFI),electromagneticinterference(EMI)orcorrosiveandaboveboilingpointliquids.Ourrobustprobesaredesignedforeaseofinstallationandhaveagreaterthan99%installationsuccessrate.

• IndustrystandardLUXTRONQualityProbes™andDipTipRuggedProbes™

• VitonO-ringconnectorforprotectionagainstleaks

• PFATeflon®-jacketeddesignwithKevlar®construction

• ImmunetoRFandEMIandElectricallyNon-Conductive

• Mostrobust,well-builtfiberopticprobesonthemarket

• Insulatedwithfivelayersforsuperiorprotection

• DipTipRuggedProbesdon’trequiredoubleinstalla-tions

• Dielectricallytestedtoensuresafe,accurageperfor-mance

• Chemicallyinertandcompatiblewithmanyaggressivechemicals

• Intrinsicallysafe,stableanddrift-free

• Availableinvariouslengths(1mto16mstandard)

WEIDMANN-Certified SmartSpacers™OursensortipscanbesuppliedwithWEIDMANN-certifiedSmartSpacers.AllWEIDMANN-certifiedcompo-nentsincludingadhesivesandassembliesmeetstrictmanufac-turingprocesscontrolsandareshippedwithacertificateofcomplianceoutliningthatthecomponenthasmetthefive-partWEIDMANNcertificationprocess.AvailablewithLumaSenseDipTipRuggedProbes™.

ExtensionsLumaSenseoffersmultiplefiberopticextensionsoptionstoconnecttheprobesfromthetankwallplatetotheinstrument.

Single Fiber Extension• HardCladSilicafiberjacketedinPVCandKevlar®

• Availableinlengthsof5,10,15or20metersorcustomlengthsbyrequestupto50meters

• SMAconnectorincludesVitonO-ringforprotectionagainstleaks

Four-Fiber Extension• FourfibercablesubunitsandacentralKevlar®

strengthmemberinonePVCouterjacket

• EachsubunitfeaturesHytrel®andKevlar®overHardCladSilicafiber

• Availableinlengthsof5,10,15or20metersorcustomlengthsbyrequestupto50meters

• VitonO-ringconnectorsforprotectionagainstleaks

• Availableinlowtemperatureconstructionalso

TankWallPlateAssemblyLumaSenseprovidesweldedtankwallfeedthroughplateassemblies.Eachtankwallplatefeaturesourproprietaryweldedfeedthroughsonastainlesssteelplate,withacarbonsteelbackingringandVitonO-ringformaximumprotectionagainstleaks.

Page 4: LumaSMART - ATECorp.com...LumaSense Technologies’ LumaSMART winding hot spot temperature system is the most advanced and reliable real-time monitoring solution available today. LumaSense

[email protected] www.lumasenseinc.com©2013LumaSenseTechnologies.Allrightsreserved.LumaSenseTechnologies,Inc.,reservestherighttochange

theinformationinthispublicationatanytime.

Americas and AustraliaSales & ServiceSanta Clara, CAPh:+18006310176Fax:+14087271677

Europe, Middle East, Africa Sales & ServiceFrankfurt, GermanyPh:+4969973730Fax:+496997373167

IndiaSales & Support CenterMumbai, IndiaPh:+912267419203Fax:+912267419201

ChinaSales & Support CenterShanghai, ChinaPh:+8613311827766Fax:+862158772383

LumaSense Technologies Awakening Your 6th Sense

LumaSMARTBrochureRev.09/03/13

TechnicalData

InnovativeOn-BoardSoftwareTheLumaSMART’sinnovativeon-boardsoftwaregivesacolor-codedvisualdisplayofallconnectedprobes.UsingthetouchscreenexclusivelyofferedbyLumaSense,youcancustomizechannellabels,configurealarmsandrelaysanddownloaddatalogs.Inaddition,thediagnosticfeatureallowsyoutoeasilytestyourconfiguredrelaysettingsbysimulatingalarmconditions.Oursoftwarealsoallowsfortrendinganddataanalysisoftempera-turesmeasured.

PerformanceNumberofChannels 4to16(inincrementsof2)

TemperatureRange -30to230ºC

Accuracy ±2°Coverentiretemperaturerangeforlifeoftransformerwithoutcalibration

DisplayResponseTime 1sec

MeasurementResolution

0.1ºC

Precision ±0.5ºC

LightSourceLifeSpan Lifeofthetransformer

EMI/RFISusceptibility Completeimmunity

InterfaceDisplay 5.7-inchinteractivetouchscreen

ProbeSignalStrengthReadout

Accessibleforallchannels

Diagnostics On-boardselfdiagnosticsandtroubleshootingguide

Environmental SpecificationsOperatingTemperature -30to70°C

StorageTemperature -35to75ºC

CommunicationAnalogOutput Choiceof4-20mAor0-1mA

SerialOutput RS-232CandRS-485,Ethernet,USB

Relays 0,8or16Form-Cprogrammablerelays

SystemStatusRelay 1Form-Crelay

Communications ModbusASCII,ModbusRTU,DNP3.0,ASCIIandIEC61850Standard

Probes AcceptsLUXTRONRuggedandQualityProbes

DataStorage 2GBofdataat1minuteintervalsonallchannels,aswellaserrorcodesandrelaystatuses.Retainsapproximately40yearsofdata.

ElectricalInputPower 90to264VACor127to370VDC,47to

63Hz

SurgeProtection 4000V(IEEEC37.90.1-2002)

Consumption 108W(maximum)

PhysicalMounting Rack,panelorwallmountavailable


Recommended