Lumination LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution for traditional downlight fixtures. They install in just minutes into most 6-inch and 8-inch rough-in frames and bring a fresh look to the space. Unlike plug-in LED lamps, the LRX downlight gives you a new power supply and 50,000 hour life rating, so that you won’t have to worry about compatibility or maintenance issues with the original ballasts. All downlights in the LRX family have 120-277V input and a uniform lit appearance, delivering premium performance in an economical package. Product Description: Project name _________________ Date ________________________ Type ________________________ Ordering Information: Product Dimensions: Input Voltage: 120 - 277V Standard Dimming Controls: 0-10V down to 10% CCT: 3000K, 3500K, 4000K CRI: 82 Lifetime Rating: L70 @ 50,000 Hours Input Frequency (Hz): 50/60Hz Power Factor: >0.9 Mounting Options: Spring clips clamp on to existing frame or directly to ceiling Weight: 0.6 lb IC Rating: Non-IC Rated Limited Warranty: 5 years system Files Available: LM79, LM80, IES Performance Summary: Listings: • UL and cUL Listed. • Suitable for wet locations 6-inch A = 7.75” (196.8 mm B = 4.5” (114.2 mm) C = 24.0” (609.6 mm D = 6” (152.4 mm) Ceiling Cutout Min: 5.7” 8-inch A = 9.75” (247.6 mm B = 5.1” (129.4 mm) C = 24.0” (609.6 mm D = 6” (152.4 mm) Ceiling Cutout Min: 7.7” L R X R 6 8 M D _ _ _ _ _ _ _ _ _ _ _ _ L R X R 8 8 M D _ _ _ _ _ _ _ _ _ _ _ _ FAMILY FAMILY LRX = Indoor LRX = Indoor SHAPE/SIZE SHAPE/SIZE R6 = Retrofit Downlight 6” Round Rated for New Construction R8 = Retrofit Downlight 8” Round Rated for New Construction CRI CRI CCT CCT DIMMING DIMMING 8 = 80 CRI 8 = 80 CRI MD = 0-10V Dimming MD = 0-10V Dimming LUMENS LUMENS 10 = 1000 lm/650 lm 1. 18 = 1800 lm 10 = 1000 lm/650 lm 1. 18 = 1800 lm 30 = 3000 lm 30 = 3000K 35 = 3500K 40 = 4000K 30 = 3000K 35 = 3500K 40 = 4000K SKU’S CATALOG # DESCRIPTION 93018829 GRRC6RPTWT RC 6” White Paint Goof Ring 93018831 GRRC8RPTWT RC 8” White Paint Goof Ring 93025091 FRAME6R 6” New Construction Frame Kit 93025092 FRAME8R 8” New Construction Frame Kit A B C D Nominal Lumens 650 1000 1800 3000 Delivered Lumens (8” Shown - 6” reduce 5%) 750 1200 2000 3300 System Input Power 8.5 13 22 35 System Efficacy (LPW) 88 92 91 94 Notes: 1. 1000lm models feature a selectable lumen package to allow field adjustments to light output . See page 2 for further info.
Transcript
Page 1: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

Lumination™ LED LuminairesLRX Round SeriesLED Downlights

The Lumination RX Series LED downlights are the ideal retrofit solution for traditional downlight fixtures. They install in just minutes into most6-inch and 8-inch rough-in frames and bring a fresh look to the space.Unlike plug-in LED lamps, the LRX downlight gives you a new power supply and 50,000 hour life rating, so that you won’t have to worry about compatibility or maintenance issues with the original ballasts.All downlights in the LRX family have 120-277V input and a uniform lit appearance, delivering premium performance in an economical package.

Product Description:

Project name _________________

Date ________________________

Type ________________________

Ordering Information:

Product Dimensions:

Input Voltage: 120 - 277VStandard Dimming Controls: 0-10V down to 10%CCT: 3000K, 3500K, 4000KCRI: 82Lifetime Rating: L70 @ 50,000 HoursInput Frequency (Hz): 50/60HzPower Factor: >0.9Mounting Options: Spring clips clamp on to existing frame or directly to ceilingWeight: 0.6 lbIC Rating: Non-IC RatedLimited Warranty: 5 years systemFiles Available: LM79, LM80, IES

Performance Summary:

Listings: • UL and cUL Listed.• Suitable for wet locations

6-inchA = 7.75” (196.8 mm B = 4.5” (114.2 mm) C = 24.0” (609.6 mm D = 6” (152.4 mm) Ceiling Cutout Min: 5.7”

8-inchA = 9.75” (247.6 mm B = 5.1” (129.4 mm) C = 24.0” (609.6 mm D = 6” (152.4 mm) Ceiling Cutout Min: 7.7”

L R X R 6 8 M D_ _ _ _ _ _ _ _ _ _ _ _

L R X R 8 8 M D_ _ _ _ _ _ _ _ _ _ _ _

FAMILY

FAMILY

LRX = Indoor

LRX = Indoor

SHAPE/SIZE

SHAPE/SIZE

R6 = Retrofit Downlight6” RoundRated for New

Construction

R8 = Retrofit Downlight8” RoundRated for New

Construction

CRI

CRI

CCT

CCT

DIMMING

DIMMING

8 = 80 CRI

8 = 80 CRI

MD = 0-10V Dimming

MD = 0-10V Dimming

LUMENS

LUMENS

10 = 1000 lm/650 lm1.

18 = 1800 lm

10 = 1000 lm/650 lm1.

18 = 1800 lm30 = 3000 lm

30 = 3000K35 = 3500K40 = 4000K

30 = 3000K35 = 3500K40 = 4000K

SKU’S CATALOG # DESCRIPTION

93018829 GRRC6RPTWT RC 6” White Paint Goof Ring 93018831 GRRC8RPTWT RC 8” White Paint Goof Ring 93025091 FRAME6R 6” New Construction Frame Kit 93025092 FRAME8R 8” New Construction Frame Kit

A

B

C

D

Nominal Lumens 650 1000 1800 3000Delivered Lumens (8” Shown - 6” reduce 5%) 750 1200 2000 3300

System Input Power 8.5 13 22 35System Efficacy (LPW) 88 92 91 94

Notes:1. 1000lm models feature a selectable lumen package to allow field adjustments to light output.See page 2 for further info.

Page 2: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

LuminationTM LRX Series DownlightsPhotometric Data:

ACCESSORY CATALOG # SKU NOTES

347V Kit LRX347V120 93036250 347V Transformer Kit 6” FRAME FRAME6R 93025091 Recommended for new construction applications 8” FRAME FRAME8R 93025092 Recommended for new construction applications Daintree LCACBAVQTUNGALV 93038296 See Daintree Accessory Kit Literature & Install Manual OR Controls LCACBAVQRUNGALV 93029452 See Organic Response Accessory Kit Literature & Install Manual EN Controls LCACBAVQNUNGALV 93029451 See Enlighted Accessory Kit Literature & Install Manual

The LRX Series comes with a new Selectable Driver Package which allows customers to manually switch from full power (1000lm)to lower power (650lm) with just the switch of a button. This affords unprecedented flexibility for distributors to stock fewer SKUs. Reduces install risk by effectively having 2 lumen levels in 1 simple package.

Accessories:

Selectable Driver Package:

*This feature is only available in the 1000/650lm package.

For more information and access to all of our resources, including our design tool visit: www.gelighting.com

Installation:• Fixture mounting to an existing metal frame • Conduit connect to quick-disconnect for easy installation

Construction: • 16 gauge Aluminum spinning reflector housing, powder coating• Custom engineered heat sink flange for passive cooling on all lumen options

Optical System:• Custom engineered reflectors for wide distributions.• Semi-diffuse diffuser for ideal combination of optical efficiency and uniformity

Electrical System:• High Efficiency, integrated driver with 0-10V dimming• Selectable Lumen Driver available in the 1000/650lm package.

Product Specifications:

Page 3: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

www.currentbyge.comAll trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratoryconditions. Current, powered by GE is a business of the General Electric Company. © 2016 GE.

IND288 (Rev 08/30/16)

LuminationTM LRX Series DownlightsPhotometric Data:

LRXR610830MD

LRXR818830MD

COEFFICIENTS OF UTILIZATION

COEFFICIENTS OF UTILIZATION

NOTE: Floor Cavity Reflectance : 20%

NOTE: Floor Cavity Reflectance : 20%

Gamma 0° 45° 90°

45° 17519 17519 17519 55° 11682 11682 11682 65° 6286 6286 6286 75° 4723 4723 4723 85° 4000 4000 4000

LUMINANCE DATA (CANDELA/m2)

Gamma 0° 45° 90°

45° 8251 8251 8251 55° 4433 4433 4433 65° 1645 1645 1645 75° 827 827 827 85° 263 263 263

LUMINANCE DATA (CANDELA/m2)

ZONAL LUMEN SUMMARY

Zone Lumens % of Fixture0-20° 184.25 18.400-30° 383.39 38.300-40° 605.34 60.500-60° 912.41 91.200-80° 991.92 99.200-90° 999.70 100.00

ZONAL LUMEN SUMMARY

Zone Lumens % of Fixture0-20° 332.00 18.400-30° 689.94 38.300-40° 1095.66 60.900-60° 1664.57 92.500-80° 1786.51 99.200-90° 1797.12 99.80

ZONAL LUMEN SUMMARY

ZONAL LUMEN SUMMARY

RC 80% 70% 50% 30% 10% 0%RW 70% 50% 30% 10% 70% 50% 30% 10% 50% 30% 10% 50% 30% 10% 50% 30% 10% 0% 0 119 119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 1001 111 107 104 100 108 105 102 99 101 98 96 97 95 93 93 92 90 882 103 96 90 85 100 94 89 85 91 86 83 87 84 81 85 82 79 773 95 86 79 74 93 85 78 73 82 76 72 79 75 71 77 73 69 684 88 78 70 64 86 76 69 64 74 68 63 72 67 62 70 65 62 605 82 70 63 57 80 69 62 57 67 61 56 66 60 55 64 59 55 536 76 64 56 51 74 63 56 50 62 55 50 60 54 50 59 53 49 477 71 59 51 45 69 58 51 45 57 50 45 55 49 45 54 48 44 438 66 54 46 41 65 53 46 41 52 45 41 51 45 40 50 44 40 399 62 50 42 37 61 49 42 37 48 42 37 47 41 37 46 41 37 3510 59 46 39 34 57 46 39 34 45 38 34 44 38 34 43 38 34 32

RC 80% 70% 50% 30% 10% 0%RW 70% 50% 30% 10% 70% 50% 30% 10% 50% 30% 10% 50% 30% 10% 50% 30% 10% 0% 0 119 119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 1001 111 107 104 101 108 105 102 99 101 98 96 97 95 93 94 92 90 882 103 96 91 86 101 94 89 85 91 87 83 88 84 81 85 82 79 783 95 87 80 74 93 85 79 74 82 77 72 80 75 71 77 73 70 684 88 78 71 65 86 77 70 65 75 68 64 72 67 63 70 66 62 605 82 71 63 57 80 70 63 57 68 61 56 66 60 56 64 59 55 536 76 65 57 51 75 64 56 51 62 55 50 60 54 50 59 54 50 487 71 59 51 46 70 58 51 46 57 50 45 56 50 45 54 49 45 438 67 54 47 41 65 54 46 41 52 46 41 51 45 41 50 45 41 399 62 50 43 38 61 50 42 38 49 42 37 47 41 37 47 41 37 3510 59 47 39 34 57 46 39 34 45 39 34 44 38 34 43 38 34 32

POLAR GRAPH

POLAR GRAPH

512

923

384

692

256

462

128

231

Zone Lumens 0-10° 48.2610-20° 135.9920-30° 199.1430-40° 221.9640-50° 188.1250-60° 118.9560-70° 54.0470-80° 25.4780-90° 7.7890-100° 0.06100-110° 0.02110-120° 0.03120-130° 0.03130-140° 0.04140-150° 0.05150-160° 0.05160-170° 0.03170-180° 0.01

Zone Lumens 0-10° 87.0010-20° 245.0020-30° 357.9430-40° 405.7240-50° 355.7250-60° 213.1960-70° 84.3570-80° 37.5880-90° 10.6190-100° 0.07100-110° 0.14110-120° 0.29120-130° 0.44130-140° 0.54140-150° 0.55150-160° 0.48160-170° 0.31170-180° 0.10

1

1

2

2

Page 4: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

1

2 3 4 5

GELighting

imagination at work

(RC/RX/LRX Series - New Construction Frame)LuminationTM LED Luminaire

Installation Guide

BEFORE YOU BEGINRead these instructions completely and carefully.

NOTICELamp Housings RC6, RC8 or RX6, RX8 or LRX6, LRX8 may be assembled with part FRAMExR. When Lamp Housings RC6, RC8 or RX6, RX8 or LRX6, LRX8 is assembled with Part FRAMExR the final assembly complies with UL 1598 category IFAO recessed luminaire requirements.

Save These InstructionsUse only in the manner intended by the manufacturer.If you have any questions, contact the manufacturer.

Prepare Electrical WiringElectrical Requirements• The LED luminaire must be connected

to the mains supply according to itsratings on the product label.

Grounding Instructions• The grounding and bonding of the overall

system shall be done in accordance tolocal electric code of the country where theluminaire is installed.

WARNING/AVERTISSEMENTRISK OF ELECTRIC SHOCK• Turn power off before inspection, installation or removal.• Properly ground electrical enclosure.RISK OF FIRE• Follow all NEC and local codes.• Use only UL approved wire for input/output connections.Minimum size 18 AWG or 14 AWG for continuous runs.

RISQUES DE DÉCHARGES ÉLECTRIQUES• Coupez l’alimentation avant d’’inspecter, installer ou déplacer le luminaire.• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.RISQUES D’INCENDIE• Respectez tous les codes NEC et codes locaux.• N’utilisez que des fils approuvés par UL pour les entrées/sorties de

connexion. Taille minimum 18 AWG ou 14 AWG pour les rangées continues.

Components

Provided Item Qty.1 Frame (6-inch or 8-inch) 12 Mounting brackets 23 L-Bracket 34 U-Bracket (used only with RC Series Installs) 15 Wing nut 3

NOTE: Part 4 and 5 are only for RC product.

Page 5: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

1 2Cut the appropriate size hole into ceiling tile.

Place side L-brackets on existing frame screws and tighten with screwdriver on both sides of the frame. Then attach mounting brackets to both L-brackets with wing nuts (provided).

Fixture Diameter

Hole Diameter

RC6 6.4–7.2 in.

RX6/LRX6 5.91–6.60 in.

RC8 7.5–8.9 in.

RX8/LRX8 7.68–8.27 in.

Frame Installation

L-brackets

Mounting brackets

3 Slide hanger bars through adjustable mounting brackets.

4 Option A: Mount fixture by attaching hanger bars to T-Grid ceiling (BH3 SKU 94890).

Option B: Mount fixture with ½” EMT conduit. Note: Supplied by 3rd party.

Bars Conduit

A B

Adjust height and tighten wing nut

5 Adjust fixture height to be flush with ceiling and tighten both mounting bracket wing nuts.

Through Wiring for 15A Circuit

Lumen Level

Maximum Number of Fixtures(120V Input / 277V Input)

1000 84 / 1951500 77 / 1792000 59 / 1383000 38 / 894000 24 / 57

Minimum Spacing Requirements for all Fixture Configurations

Center to center of adjacent luminaires 24”

Top of Luminaire to overhead building member 3”

Luminaire center to side building member 12”

(For any other information refer to RC-series Installation Guide)

RC-Series Mounting(RX-Series Mounting skip to step 15. LRX-Series Mounting skip to step 18)

Page 6: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

6 Open RC PSU box cover, disconnect AC conduit. Remove AC conduit wire from PSU box knockout hole using flat head screw driver.

Screwdriver tipRemove cover

AC conduit

Remove AC wires

Wiring Diagram

7 Insert AC line wires into the PSU box through the knockout hole and connect wires (see wiring diagram).

AC line (Line, Neutral and Ground)

DRIVER

TPC

Black (+) Lead

White (-) Lead White (-) Lead

Black (+) Lead

L N GPSU Enclosure

*Blue Lead / Red Lead

(0-10V) Purple (+) Dimming Lead

(0-10V) Grey (-) Dimming LeadBlue Lead - 120V ONLYRed Lead - 277V ONLY

*NOTE:

DRIVERTPC

Black (+) Lead

White (-) Lead White (-) Lead

See Note 2

Black (+) Lead

L N G

PSU EnclosureEcoSystem Wiring Diagram

Lutron Controller (optional)

*Blue Lead / Red Lead

EcoSystem (purple)E1

L

N

DL

E2EcoSystem (purple)Blue Lead - 120V ONLY

Red Lead - 277V ONLY

NOTE 2: DL, for use with 3-wire fluorescent control (Lutron system)

*NOTE 1:

Page 7: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

8 9Place PSU box onto frame next to unused junction box and secure with U-bracket by tightening wing nut.

Wing nutU-bracket

Take the provided safety tether and loop one end of the tether around the L-bracket.

Loop around L-bracket

1110 Attach the other end of the safety tether to the fixture using one of the three holes located on the fixture brackets. Feed the button stop and toggle through the hole and slide into the hole in the bracket. Allow the fixture to hang freely .

Plug together the light fixture to the driver enclosure with the supplied quick connects and assemble the connector housing when finished.

Feed button stop and toggle through

hole in bracket

Safety tether

Button stop

Toggle

Assembled connector housing

Connect two quick connects

Cut cable tie on light fixture.

Position fixture so L-bracket does not

interfere with springs

Align the fixture so that two of the three springs are on each side of the L-bracket. This is necessary in order to make sure that when the springs release, the L-bracket does not interfere and prevent the springs from making contact with the top of the ceiling for proper support.

12 13

Page 8: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

Connect AC line to existing junction box. Connect conduit fitting to the existing junction box. Connect the black, white and green/yellow wires of the input leads to the black, white and green AC line wires using UL Listed twist-on wire connectors and close the junction box (see wiring diagram).

AC line

15

RX-Series Mounting

Line (black)

Neutral (white)

Ground (green)

DRIVER

Black

White

Green/Yellow

Wiring Diagram

CAUTION

RISK OF PERSONAL INJURY - Operators shall ensure no appendages are in the path of the torsion springs as they are a pinch hazard when released. The springs will release when the arm is flexed downward. Be cautious that no body part is in the path of the spring when released.

17 Load springs into upright position by twisting the springs upward and carefully insert the fixture to the hole of the frame. Ensure fixture is secure.

Springs up

16 Connect the two quick connectors and reassemble the connector box.

Reassembled connector box

Connect plugs

Final installation position for

springs

Push fixture through the hole in the ceiling. This will engage the protruding arms, thus, releasing the springs. The springs will draw the fixture up into the ceiling and hold it their tightly.

14

CAUTION

RISK OF PERSONAL INJURY - Operators shall ensure no appendages are in the path of the torsion springs as they are a pinch hazard when released. The springs will release when the arm is flexed downward. Be cautious that no body part is in the path of the spring when released.

Page 9: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

LRX-Series Mounting

Connect conduit end with input leads to existing junction box and make proper connections. Connect the black, white, and green/yellow wires of the input leads to the black, white and green wires using twist-on wire connectors and close junction box.

Optional dimmer: When connecting with dimming controller, wires must be run through another separate knockout hole. Connect the violet (dimming +) and gray (dimming -) wires to the violet and gray wires of the fixture.

NOTE: Please cover dimming leads with wire nuts if you won’t connect with dimming leads.

AC line

18

0-10 Volt Dimming

Lutron EcoSystem Dimming (optional)

Gray 0-10V –

0-10V +Violet

To 0-10V Dimmer

LED Driver

Purple

PurpleEcoSystem

EcoSystem

To Lutron System

LED Driver

Wiring Diagram

L

Dimming +

N

Dimming –

Ground

LRX Fixture

Black

Violet

White

Gray

Green/Yellow

No. Dimmer Type

Maximum Fixture

Quantity1 QSN - 4T16 - S 802 GRX TV1 with Grafik Eye QS Main Unit 5203 NTFTV/NFTV/DVTV with PP - 120 404 TVM2 Module 805 TVI - LMF -2S 35

Maximum Quantity Of Fixtures That Can Be Connected With One Dimmer

Lumens Setting Switch

NOTE: For 1000/650lm product, default output lumen is 1000lm. Push switch up to activate 650lm.

Page 10: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

www.gelighting.com

GE and the GE Monogram are trademarks of the General Electric Company. All other trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions. GE Lighting is a business of the General Electric Company. © 2016 GE.

IND259 (Rev 08/26/16)

Connect the two quick connectors and reassemble the connector box.

Load springs into upright position by twisting the springs upward and carefully insert the fixture to the hole of the frame. Verify reflector trim is flush with ceiling.

Reassemble connector box

Connect plugs:3 pole to 3 pole2 pole to 2 pole

Springs up

CAUTION

RISK OF PERSONAL INJURY - Operators shall ensure no appendages are in the path of the torsion springs as they are a pinch hazard when released. The springs will release when the arm is flexed downward. Be cautious that no body part is in the path of the spring when released.

19 20

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. This Class [A] RFLD complies with the Canadian standard ICES-003. Ce DEFR de la classe [A] est conforme á la NMB-003 du Canada.

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Page 11: Lumination LED Luminaires - WESCO International · Lumination™ LED Luminaires LRX Round Series LED Downlights The Lumination RX Series LED downlights are the ideal retrofit solution

Lumination™ ControlsLRX Transformer Kit

Product Description:The LRX transformer kits provides connection to LRX fixtures. This kit is essential in Canadian commercial and industrial applications.

Projectname

Date

Type

Product Dimensions:

Performance Summary:Input Voltage: 347VOutput Voltage: 277VInput Frequency: 60HzOutput Frequency: 60HzMaximum Current: 0.27A (277V) or 0.23A (347V)Maximum Power: 70VAStorage temperature: -40C ~ +70COperating temperature: -10C ~ + 35CCompatible Fixtures: LRXWeight: 1.80kgLimited Warranty: 5YIC Rating: Non–IC

Listings:• UL and cUL Listed

www.currentbyge.comAll trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions. Current, powered by GE is a business of the General Electric Company.© 2016GE.

IND323 102416

Ordering Information

Material Description Code

93036250 LRX347V277


Recommended