1 GE Lighting Installation Guide LOP Series Lumination TM LED Luminaire BEFORE YOU BEGIN Read these instructions completely and carefully. WARNING/AVERTISSEMENT RISK OF ELECTRIC SHOCK Turn power off before inspection, installation or removal. • Properly ground electrical enclosure. RISK OF FIRE • Follow all NEC and local codes. • Use only UL approved wire for input/output connections. Only use size 18 AWG. RISQUES DE DÉCHARGES ÉLECTRIQUES • Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire. • Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique. RISQUES D’INCENDIE • Respectez tous les codes NEC et codes locaux. • N’utilisez que des fils approuvés par UL pour les entrées/sorties de connexion. Utilisez taille 18 AWG. Save These Instructions Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer. Components Supplied Prepare Electrical Wiring Tools and Components Required Electrical Requirements The LED driver must be supplied with 120-277 VAC, 50/60 Hz or 347V, 50/60Hz and connected to an individual properly grounded branch circuit, protected by a circuit breaker. Use min. 75°C supply conductor. Grounding Instructions The grounding and bonding of the overall system shall be done in accordance with National Electric Code (NEC) Article 600 and local codes. UL Listed conduit connections per NEC/CEC for nominal conduit trade size ½” UL Listed wire connectors Phillips screw driver #2 LOP Series Luminaire Mounting Kit Power feed cord kit (ordered separately) Important • Maximum length of electrical run per table below: Input voltage Lumen per 4ft. Total Number of Fixtures (4’) Total Number of Fixtures (8’) 120V 3000 20 10 4800 12 6 277 3000 45 22 4800 26 13 347 3000 56 28 4800 33 16 Please see technical data sheet for electrical properties to ensure safe installation. Under any circumstance, maximum current through connected fixtures shall not exceed 5A. Minimum distance between the fixture and the ceiling of 8”
Transcript
Page 1: LuminationTM LED Luminaire - Current by GE Electrical Wiring ... LOP Series luminaires come in two versions: ... The fixture will need to be positioned in a specific way for the continuous

1

GELighting

Installation Guide

LOP SeriesLuminationTM LED Luminaire

BEFORE YOU BEGINRead these instructions completely and carefully.

WARNING/AVERTISSEMENTRISK OF ELECTRIC SHOCK• Turn power off before inspection, installation or removal.• Properly ground electrical enclosure.RISK OF FIRE• Follow all NEC and local codes.• Use only UL approved wire for input/output connections. Only use size 18 AWG.

RISQUES DE DÉCHARGES ÉLECTRIQUES• Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire.• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.RISQUES D’INCENDIE• Respectez tous les codes NEC et codes locaux.• N’utilisez que des fils approuvés par UL pour les entrées/sorties de connexion. Utilisez taille 18 AWG.

Save These InstructionsUse only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.

Components Supplied

Prepare Electrical Wiring

Tools and Components Required

Electrical Requirements•The LED driver must be supplied with 120-277 VAC,

50/60 Hz or 347V, 50/60Hz and connected to an individual properly grounded branch circuit, protected by a circuit breaker. Use min. 75°C supply conductor.

Grounding Instructions•The grounding and bonding of the overall system shall

be done in accordance with National Electric Code (NEC) Article 600 and local codes.

• UL Listed conduit connections per NEC/CEC for nominal conduit trade size ½”

• UL Listed wire connectors• Phillips screw driver #2

•LOP Series Luminaire•Mounting Kit•Power feed cord kit (ordered separately)

Important• Maximum length of electrical run per table below:

Input voltage

Lumen per 4ft.

Total Number of Fixtures (4’)

Total Number of Fixtures (8’)

120V3000 20 104800 12 6

2773000 45 224800 26 13

3473000 56 284800 33 16

• Please see technical data sheet for electrical properties to ensure safe installation.

• Under any circumstance, maximum current through connected fixtures shall not exceed 5A.

• Minimum distance between the fixture and the ceiling of 8”

Page 2: LuminationTM LED Luminaire - Current by GE Electrical Wiring ... LOP Series luminaires come in two versions: ... The fixture will need to be positioned in a specific way for the continuous

Preparation

2

Carefully unpack unit from its packaging. Properly inspect for defects before installing. Wear clean work gloves to prevent dirt and oil from being transferred to the luminaire.

LOP Series luminaires come in two versions: continuous units (LOPC Series) and independent units (LOPI Series). For mounting continuous units, a Starter Kit is required for each power drop. A continuous electrical run will consist of a number of continuous units up to a maximum current of 5A on a breaker. Additional continuous runs may be appended mechanically to the same row using additional power feeds. When installing luminaires, use clean gloves in order to avoid fouling the optical parts.

Installation for Independent Fixtures

1X

All kits shown are automatically included for independent SKUs

1X2X 1X

Power and control cord102” (1 of each)

LOPI Series

Page 3: LuminationTM LED Luminaire - Current by GE Electrical Wiring ... LOP Series luminaires come in two versions: ... The fixture will need to be positioned in a specific way for the continuous

Slightly untighten screws on the sides of the knock-out plate. Slide the knock out plate towards the end-cap to be able to unclip it (direction shown on the figure).

3

LOPI Series

54

Remove knockout plate. Attach UL Listed strain reliefs and dimming lines if needed. Connect wires based on wiring diagram below.

FIXTURE LINEGROUNDNEUTRAL

DIMMING (+)DIMMING (-)

BLACKGREENWHITEVIOLETGRAY

6

Attach knockout plate to fixture.

LOPI Series

1 32

Remove fixture from packaging. Connect fixture to applicable upper mounting kit.

Install lower mounting kit into slots on fixture housing on both ends.

Page 4: LuminationTM LED Luminaire - Current by GE Electrical Wiring ... LOP Series luminaires come in two versions: ... The fixture will need to be positioned in a specific way for the continuous

4

Power feed kits ordered separately (order one per power drop)

1 per fixture1 per fixture

Installation for Continuous Runs

1X

1XPower and control cord

102” (1 of each)

1X 2X

Voltage End cap color Kit #

120-277V White 93053095

120-277V Silver 93053297

347V White 93053296

347V Silver 93053298

LOPC Series

Page 5: LuminationTM LED Luminaire - Current by GE Electrical Wiring ... LOP Series luminaires come in two versions: ... The fixture will need to be positioned in a specific way for the continuous

Follow steps 1 and 2 from “Installation for Independent Fixtures.”

NOTE: The fixture will need to be positioned in a specific way for the continuous run. Reference the label on the fixture to determine which side faces the same direction as the fixture run.

5

1

Remove the blank knockout plate labeled with the notation “Supply Connections Underneath.”

Unconnected supply leads

Starter Kit knockout

plate

Power Feed Kit knockout plate

Dimming leads

Disconnect the grounding wire.

Connect the feed cord into the Power Feed Kit knockout plate. Remove all necessary connectors using cutters.

Connect the grounding wire from the fixture to the knockout plate provided in the starter kit.

Strip wires and connect to feed cord using UL listed connectors. Follow wiring diagram below.

Attach knockout plate to fixture. Use housing screws to secure the knockout plate in place.

2 3

5

4

6 7

CONTROL

BRANCH CIRCUIT 1

STAN

DAR

D

LINE 2LINE

NEUTRALGROUND

(0-10V) +(0-10V) –

RED BLACKWHITEGREEN/YELLOW

VIOLETGRAY

LOPC Series

Page 6: LuminationTM LED Luminaire - Current by GE Electrical Wiring ... LOP Series luminaires come in two versions: ... The fixture will need to be positioned in a specific way for the continuous

6

Swing the fixture up so that it is linear with the existing fixture. Make sure fixtures are level.

Make electrical connections.

Suspend the other end of the fixture with the applicable Suspension Kit.For Canadian installation, every fixture should be held by 2 suspen-sion cables.

Reinstall knockout plates Install end caps provided in Power Feed Kit at both ends of the run. Make sure both clips are properly engaged.

Locate the 4 screws noted in the illustration and rotate them clockwise to draw the fixtures together. Keeptightening until a proper seal is made.Do not over-torque.

11

14

12

15 16

13

LOPC Series#2

Pull out female sliders from the first fixture that is hung in the continuous run.

Pull the male sliders out of the next fixture in the run.

Hook male sliders onto the female sliders.

8 9 10

Page 7: LuminationTM LED Luminaire - Current by GE Electrical Wiring ... LOP Series luminaires come in two versions: ... The fixture will need to be positioned in a specific way for the continuous

1 2

Cable coupler

2nd cable

2-inch non-power feed canopy

7

Utilization of Kits

Power Feed KitNon-power Feed Kit

White Heyco StrainRelief Bushings

1/16” Galv. Cable

18/4 ST Cord600V 105CPrepped One End

ZF15-15Z-XCCross Cable Gripper

1/16” Galv. CrossCable w/ Toggle Ends

White Heyco StrainRelief Bushings

2” White Canopy

BB-1420Bracket Bar w/ 1/4-20Stud & Ground Screw

CC-1420-T2

Ø5” White Canopy with2 Power feed Holes

1/16” Galv. Cable

CC-18IP-SRSlip Ring Cable Coupler

ZF-15Z-XCCable gripper

18/2 SVT CordWhite with Grey & VioletConductorsPrepped One End

1/16” Galv. Cross Cable w/ Toggle Ends

Kit Installation

Attach crossbar to junction box in ceiling with two #8 screws (provided).

Pass cable through cable coupler and screw onto stud. Pass cable through canopy and slip ring (power canopy shown).

Hang second cable to a structural ceiling member capable of supporting 44 pounds and cover with non-power feed canopy.

3Dimming line

AC line

Junction box in ceiling

Crossbar

Cable coupler

Slip ring5-inch powerfeed

canopy

Stud

Page 8: LuminationTM LED Luminaire - Current by GE Electrical Wiring ... LOP Series luminaires come in two versions: ... The fixture will need to be positioned in a specific way for the continuous

4 5

8

Assemble cross cables: Remove screw from cross cable gripper and insert toggle cable into slot. Replace screw and tighten.

Insert both ends of the toggle cable into the luminaire mounting holes and adjust so that the toggles are engaged and will not come out of the holes when loaded.

To adjust height and to level a fixture, press the tip of the gripper and pull the suspension cable to the desired height. Clip the cable with cable cutters to finish the appearance.

NOTE: Gripper cannot be depressed while there is weight on mechanisms.

6

Toggle cable

Cross cable

gripper

Down cablePress tip to adjust

7 8

Connect the black (line) and white (neutral) wires from the ceiling to the matching- colored wires from the AC cord. Connect both green wires to the grounding screw. Connect the white/grey and violet wires from the luminaire to the matching- colored wires from the dimming circuit.

Push canopy up to ceiling and tighten slip ring over cable coupler. Make sure no openings are present in enclosure.

Secure feed cords to aircraft cable using provided zip ties.

9Dimming wires

Strain relief bushings

AC wires Slip ring

Zip tie

Page 9: LuminationTM LED Luminaire - Current by GE Electrical Wiring ... LOP Series luminaires come in two versions: ... The fixture will need to be positioned in a specific way for the continuous

All trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions. Current, powered by GE is a business of the General Electric Company. © 2017

www.currentbyge.com, www.gelighting.com

IND401 (Rev 05/10/17)99003635

9

Troubleshooting

Symptom Solution

Luminaire will not turn on • Check that the color of the supply side wires match the color of the wires they are connected to.

• Check that the LED driver connector is fully engaged to the LED light engine connector.

Luminaire on through wiring will not turn on

• Check that the through wiring connector form the previous fixture in the linear row is fully engaged to the malfunctioning luminaire.

Luminaires to luminaire mating in continuous run is loose

• Ensure that all 4 vertical screws are properly tightened (see page 6, step 13).

Suspension method won’t engage with luminaire

• Check that the suspension method is one of the approved types in the installation instruction.

End cap is loose • Ensure clip engagement (see page 6, step 16).

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. This Class [A] RFLD complies with the Canadian standard ICES-005. Ce DEFR de la classe [A] est conforme à la NMB-005 du Canada.

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.


Recommended