  • What is aMotor

    ControlCentre?

  • A Motor Control Centre isa grouping of various motor

    control & distributiondevices in one commonenclosure, fed from acommon bus system

  • A Motor Control Centreconsists of 4 basic

    components:

    -Incoming-Enclosure

    -Bus System-Units

  • Cutler-Hammer manufactures2 lines of Motor Control

    Centres

    Freedom Series 2100

    Advantage

  • IncomingMain Lugs Only

    MCC fed by upstream CB or FusibleSwitch and therefore there is no meansto disconnect power at the MCC.

    Screw or Crimp type, up to 1000 MCM6 per phase, Top or bottom entry

    Lugs are connected to Vertical Bus,which has the same rating as theHorizontal Bus (up to 1600A)

  • Incoming

    Cutler-Hammer SeriesC Circuit Breakers F (150A & 225A) Frame

    comes standard with ThermalMagnetic trips only

    K (400A) & L (600A) Frameare available with Thermal

    Magnetic or optional DigitripRMS 310 Electronic Trip

    N (800A & 1200A) & R(1600A, 2000A & 2500A)

    Frame are stnd with DigitripRMS 310 Electronic Trip

    Main Circuit Breaker

  • Incoming

    Main Fusible SwitchCutler-Hammer heavy duty Industrially rated K Switch

    Available up to 1200 Amps

    Molded Case SwitchUsing Hi-Mag CB (MCS) to provide disconnecting means at

    MCC, without short circuit protection

  • Incoming

    Bus Link to existingCutler-Hammer MCCs

    Bus Duct EntryManufactured to suit

    customers bus duct, basedupon customer supplied bus

    duct flange drawing

    Bus links & Transition cells toconnect to Cutler-Hammer,

    Westinghouse, Commander &Sylvania MCCs manufactured since

    1950

    Transition Sections10 wide cells provide

    transition to Switchgear &Transformers

  • EnclosureIndoor

    -EEMAC 1-EEMAC 1A (gasketed)EEMAC 2 (driphood)

    EEMAC 12 (dust tight)

    Outdoor-EEMAC 3R (rain, sleet proof)

    walk in or non-walk in

  • Enclosure

    Standard Section height is90, not including 1 high

    channel sill

    Standard Section width is 20

  • Wider Sections are available for largerstarters, Transfer Switches, PLCs, etc.

    20 24 28 32 44

  • Enclosure

    Side View

    16 deepSection

    V

    e

    r

    t

    i

    c

    a

    l

    B

    u

    s

    L

    o

    c

    a

    t

    i

    o

    n

    Units mounton Front Side

    only

    16 21

    Side View

    21 deepSection

    Units mounton Front Side

    Units mounton rear on

    Back to BackMCCs

    V

    e

    r

    t

    i

    c

    a

    l

    B

    u

    s

    L

    o

    c

    a

    t

    i

    o

    n

  • Cutler-Hammers standard back toback arrangement is a total of 21

    deep and employs a commonHorizontal & Vertical Bus for front

    & rear units.

    As an alternate, we can supply 16or 21 deep (front mounted sections)mounted back to back, to form a 32

    or 42 deep back to back design,with 2 sets of busses. Horizontalbusses would be cross connected

    with custom buswork

    Enclosure

  • Enclosure9 high top and bottom wireways on Front

    mounted sections

    4 5/8 vertical wireway(larger wireways available on sections over

    20 wide)

    15 top & 3 bottom wireway standard onrear sections and optional on front

    72 of unit mounting space available onFront and Rear of all sections

    Reduced height sectionsavailable in increments of 6

  • Enclosure-ASA 61 exterior finish (ASA 49 and other special colours available as an option)-White interior panels-12 gauge steel sub frame-14 gauge steel doors & covers-lifting eyes

    Optional features:-Channel sills (adds 1 to overall height)-Bottom plates (stnd on EEMAC 12)-Driphood-Space heater & thermostat-Non conductive handrails-Canopy lights-Corner sections+

    Handrail

    Driphood

  • MCC Bus System

    Horizontal Bus

    Vertical Bus

    Horizontal Ground Bus

    Option Vertical Ground

    Neutral Bus

    Horizontal Ground Bus can be mounted at bottomif no Neutral bus is being used

  • Horizontal BusCopper or AluminumTin or Silver plated

    -600 Amp-800 Amp

    -1200 Amp-1600 Amp-2000 Amp-2500 Amp-3200 Amp

    CSA rated for 65 degree C rise

  • Vertical BusCopper or AluminumTin or Silver plated

    -400 Amp (standard on Frontmounted sections

    -600 Amp (standard on Back toBack Sections, optional on front)

    -800 Amp-1200 Amp-1600 Amp

    In the incoming section, the Vertical bus hasthe same rating as the Horizontal bus (up to

    1600A)

  • Ground BusHorizontal Ground Bus (stnd locationat top of section, also may be mounted

    at bottom of section)

    Standard horizontal ground is 300Amp (1/4 x 1). Optional 600 Amp

    (1/4 x 2) is available

    Optional Vertical Ground Bus (1/4 x 1)mounted in the vertical wireway

    Neutral Bus On 4 wire systems, mounted atbottom of section, available at 300A,600A and 800A

  • Bus Bracing

    Bus braces mechanically holdthe bus in place and prevent bus

    deflection caused by a shortcircuit

    Standard Horizontal and VerticalBus bracings are 42,000 Amps

    65,000 & 100,000 Amp bracingare available as options

  • Bus IsolationAll MCC power busses are

    isolated to prevent accidentalcontact

    Horizontal bus is mountedbehind steel barriers the top

    wireway

    Vertical bus comes with glasspolyester barriers with

    removeable stab hole covers

    Glass Polyestor Barrierswith stab covers

  • Bus Insulation

    Horizontal bus is available withoptional Insulating boots, up to

    2500 amp

    An optional Labyrinth Insulatingbarrier is available on the

    Vertical bus. Optional automaticshutters are available.

    Bus boots on the Horizontal bus

    Labyrinth barriers on Vertical bus

  • MCC Bus SystemHorizontal Bus600 Amp to 3200 Amp

    Vertical Bus400 Amp to 1600 Amp

    Horizontal Ground Bus300 Amp (1/4 x 1)or 600 Amp (1/4 x 2)

    Option Vertical Ground300 Amp (1/4 x 1)

    Neutral Bus300 Amp, 600 Ampor 800 Amp

    Horizontal Ground Bus can be mounted at bottomif no Neutral bus is being used

  • Incoming Cables

    Main CircuitBreaker Open

    MCC bus notEnergized

  • Main CircuitBreaker Closed

    MCC busEnergized

    Incoming Cables

  • PLU

    G O

    NTO

    MC

    CV

    ERTI

    CA

    L B

    US

    TO M

    OTO

    R

    M

    R

    OL

    TO M

    OTO

    R

    STA

    RTE

    R

    STOPSTART

    M

    M

    Main CB ClosedMCC Bus Energized

    Starter CB Open

  • Main CB ClosedMCC Bus Energized

    Starter CB Closed

    PLU

    G O

    NTO

    MC

    CV

    ERTI

    CA

    L B

    US

    TO M

    OTO

    R

    M

    R

    OL

    TO M

    OTO

    R

    STA

    RTE

    R

    STOPSTART

    M

    M

    Main CB ClosedMCC Bus Energized

    Starter CB ClosedStarter coil not energized

  • PLU

    G O

    NTO

    MC

    CV

    ERTI

    CA

    L B

    US

    TO M

    OTO

    R

    M

    OL

    TO M

    OTO

    R

    STA

    RTE

    R

    STOP START

    M

    M

    Main CB ClosedMCC Bus Energized

    Starter CB ClosedMomentary Start PB depressed

    Starter Coil energizedMotor Starts

  • PLU

    G O

    NTO

    MC

    CV

    ERTI

    CA

    L B

    US

    TO M

    OTO

    R

    M

    OL

    TO M

    OTO

    R

    STA

    RTE

    R

    STOPSTART

    M

    M

    Main CB ClosedMCC Bus Energized

    Starter CB ClosedSeal in Contact closes

    Momentary Start PB releasedStarter Coil energized

    Motor Runs

  • PLU

    G O

    NTO

    MC

    CV

    ERTI

    CA

    L B

    US

    TO M

    OTO

    R

    M

    OL

    TO M

    OTO

    R

    STA

    RTE

    R

    STOP

    START

    M

    M

    Main CB ClosedMCC Bus Energized

    Starter CB ClosedStop Pushbutton depressedStarter Coil De-energiaed

    Motor Stops

  • UnitsCommon MCC Units

    -Combination Motor Starters-Fusible & CB type Feeders

    -Panelboards-Distribution Transformers

    -PLCs-Metering

    -Hydro Metering Compartment-Transfer Switches

    -Clipper TVSS units

  • Motor Starters

    Motor Starter units are CombinationStarters, consisting of a Starter and a

    disconnect device, either a CircuitBreaker (HMCP or Thermal Mag)

    or Fusible Switch

  • Freedom Starters

    Size 1 to 6 EEMAC rated,or optional IEC starters,c/w adjustable bimetallic

    overload relay

    Compact 6 size 1 (IEC size F) and18 Size 3 & 4 (CB type) are available

  • Advantage Starters

    Size 1 to 6 EEMAC Starter c/wElectronic Overload Relay

    Various control, metering & groundfault modules are available as well as

    PONI communications modules

    Compact 6 size 1-2 and 18 Size 3-4(CB type) are available

  • 6 Compact Starters

    -Provides space savings, 12 unitsin a Front mounted Section & 23

    in a Back to Back-Available with Freedom NEMA,

    Freedom IEC or Advantage-HMCP or Fusible Switch

    -Up to 25 HP in someconfigurations

  • Optional Units

    Developed based on feedbackfrom various MCC users

    -Slider operator mounted on RHside (mandatory in many

    industries for safety)-Rugged Industrially rated KSwitch with visible contact

    blades-Full accessibility to Power

    Fuses

  • SV9000 Drives

    Currently available in MCCs upto 250 HP at 690Volts, withlarger sizes in development.

    Simple programming with astandard or graphic keypad or

    through a PC50 HP VFDs

    mounted two high inan MCC

  • IT Solid State Starter

    Intelligent Technology (IT), theindustries most compact MCC

    Solid State Starter design,requiring 30-63% less space

    Up to 900 HP at 690V

    Compact, easy to program andadvanced functionality

    125 HP IT Starter in18 high MCC unit

  • Vacuum Contactors

    Available in 135, 270 & 540Amp ratings.

    Used in conjunction with C306Freedom Overload in MCCs

    Provides long service life andlow maintenance requirements

  • FeedersThermal Magnetic CB type Feeders from

    HFD to RD Frame

    Available in 6 compact and Dualconfigurations (maximum 150A)

    Fusible Feeders using K-Switch, up to 1200Amps

    Available in 6 compact (up to 60A) andDual (up to 100A) configurations

    Dual MountedCB typeFeeder

  • PanelboardsPow-R-Line panelboards,

    up to 42 Circuitsthru 600 Volts

    Distribution TransformersSingle Phase up to 50 KVAThree Phase up to 45 KVA

  • TVSS

    Clipper TransientVoltage SurgeSuppression

    (TVSS)

    Surge ratings100kA to 500kA

  • PLCs

    Wide rangingexperience in

    mounting & wiringCutler Hammer PLCs

    as well as allcompetitive PLCs

  • OEM

    Basic Class 1 Type ASections & Units supplied to

    OEMs c/w-Blank panel (with or without Circuit

    Breaker & operating mechanism-Devices (PLC, VFDs, etc) mounted

    & wired by the OEM-Special heights available

  • Digital Metering

    Cutler Hammer PowerManagement Products

    -IQ Analyser-IQ DP-4000-IQ Generator

    -IQ Data-IQ 200

    IQ DP-4130Digital Meter

  • Metering

    Standard AnalogueMeters

    Service EntranceSections c/w Utility

    MeteringCompartments

  • Transfer Switch

    Designed to control Emergency &Standby Power Systems

    Available as type A (not intended toprovide short circuit & overloadprotection) or type B (c/w shortcircuit & overload protection)

    Available up to 1200 Amp in MCCs

  • MCC unit features

    OperatingMechanism

    DevicePanel

    Bus Stabs

    GroundingClip

    TerminalBlock

    CircuitBreaker

    Contactor&

    Overload

    PivotTube

    UnitLatch

  • Operating MechanismGrey Toggle Slider

    MCC unit features

    -Indicates position of the Disconnect

    Interlocked with door so that:-When ON door cannot open and

    unit cannot be withdrawn-When door is open, operator is held

    in OFF-Unit cannot be withdrawn unless in

    OFF position-A Defeater mechanism is provided

    for Authorized personnel

    -Padlockable in OFF position

  • Unit ground clipGrounds unit to structure

    prior to engaging theMCC bus

    MCC unit featuresBus Stabs

    -Plugs units onto theVertical bus up to 400A-Fully shrouded, floating

    stab fingers-Tin plated (silver

    optional) copper/steelalloy stab

  • MCC unit features

    Unit Device PanelMounted on MCC unit

    Hinges down for unit access

    Holds up to six devices:-30mm Pilot Devices

    (Lights, PBs Selector Switches)-Mini Meters

    (Ammeter, Voltmeters, ETM)

  • MCC unit features

    Unit Latch locks unit in position

    Latches & locks in 3 positions:-Fully engaged

    -Test or detent position-Withdrawn

    Door Latch

    Heavy duty 1/4 turn latchprovides positive door closureand latch position indication

  • Unit Wiring# 16 TEW control wire as standard

    # 14 and other wire types also available

    Sleeve type or Heatshrink wiretags

    7 Point non pull-apart Terminal Block is standard(mounted on RH unit side)

    7 Point pull-apart TB also available(mounted on RH unit side)

    Other TBs are also available(mounted on elevated channel)

  • Unit WiringType A - No terminal blocks

    Type B - Control TBs in Starter unitsType C - Control TBs in Starter units which are wired

    to master control TBs at the top or bottom of eachMCC Section

    Class I - No interwiring between unitsClass II - complete control system including controldrawings showing remote devices and/or interwiring

    between units.

  • Unit WiringST

    AR

    TER

    Class IType A

    Fieldwiringdirectly

    ontoStarter

    STA

    RTE

    R

    Class IType B

    Fieldwiringonto

    controlTBs,which

    arefactorywired to

    theStarter

    STA

    RTE

    R

    Class IType C

    Fieldwiringonto

    masterTBs (attop or

    bottom)which

    arewired toTBs inStarterUnit

  • Unit Wiring

    STA

    RTE

    RST

    AR

    TER

    Class II factorywiring

    between two ormore units in

    the MCC

  • Unit Wiring

    11A

    AUTO

    HAND

    OFF2

    3M

    TRFUX1

    H1

    120VX2

    600V

    OL

    X2

    STOPREMOTE

    PLC

    FIREALARM

    Class I I wiring diagramshowing remote devices

  • DeviceNet MCC

    DeviceNet is an open communicationnetwork that connects intelligent control

    devices

    DeviceNet is built around a published, openstandard

    Specification controlled by ODVA

  • DeviceNet MCC

    DeviceNet MCCs

    -Reduces total installedcosts

    -Provides advanceddiagnostics

    -Reduces or eliminatesdowntime

  • DeviceNet MCC

    Shipping split on DeviceNet MCC

    Shipping split on standard MCC withinterwiring to a PLC

  • PANELMATE

    WPONIDNA

    WPONIDNAWPONIDNA WPONIDNA

    WPONIDNA

    WPONIDNA

    24VDC POWERSUPPLY

    MAINCB FEEDER

    FVRSize 1

    ITSolidState

    FVNRSize 4

    FVNRSize 2

    FVNRSize 1

    SV9000VFD

    DeviceNet MCCConceptual View

    Terminating Resistor

    Trunk Cable (thick)

    Tee Connector

    Crop Cable (thin)


Recommended