16
FACP FSCU VS WF FAA DH 2 E4.2 F FIRE ALARM PULL STATION. WALL MOUNTED 3 FT.-6 IN. ABOVE FLOOR. FIRE ALARM SIGNAL, SPEAKER AND FLASHING LIGHT, 6'-8" AFF. FIRE ALARM STROBE LIGHT, 6'-8" IN. MOUNTING HEIGHT. FIRE ALARM CONNECTION, HOOD EXTINGUISHING SYSTEM, SEE MECHANICAL DRAWINGS FOR LOCATION. INTERLOCK WITH SHUNT TRIP BREAKERS FOR EQUIPMENT UNDER HOOD. FIRE ALARM REMOTE LCD ANNUNCIATOR PANEL. FLUSH RECESSED WALL MOUNTED. FIRE ALARM DOOR HOLDER, WALL MOUNTED, CONSULT ARCHITECTURAL DRAWINGS TO DETERMINE TYPE REQUIRED. PROVIDE POWER FROM NEAREST RECEPTACLE CIRCUIT AND CONNECT TO FIRE ALARM SYSTEM. TAMPER SWITCH, FURNISHED AND INSTALLED WITH SPRINKLER SYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL. FLOW SWITCH, FURNISHED AND INSTALLED WITH SPRINKLER SYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL. FIRE ALARM SMOKE DETECTOR, CEILING MOUNTED. FIRE ALARM DUCT SMOKE DETECTOR LOCATED IN HVAC DUCT. FIRE ALARM CONTROL PANEL, SURFACE WALL MOUNTED. FIRE ALARM SIGNAL, HORN. 6 FT.-8 IN. MOUNTING HEIGHT. FIRE ALARM HEAT DETECTOR, 135 DEG, OPERATION. P WEATHER PROOF. FIRE ALARM STROBE LIGHT, CEILING MOUNTED. S M FIRE ALARM: H S WP IC AD AC S 2. COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROL REQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER. INTRUSION DETECTION SYSTEM: CONDUIT SLEEVE: NUMBER & SIZE, (2)-2" FOR ALL CLASSROOMS, (1)-2" FOR ALL OFFICES, UNO CABLE TRAY: SIZE AS INDICATED, 18"W x 4"H TYP. INTERCOM SPEAKER: WEATHERPROOF WALL MOUNTED AT 96"AFF. MICROPHONE JACK: WALL MOUNTED AT 18" AFF, UNO. ENHANCED STAFF PHONE: WALL MOUNTED 48" AFF ADMINISTRATIVE DISPLAY PHONE: WALL MOUNT AT 48" AFF INTRUSION SYSTEM: KEY-PAD, MOUNT 48"AFF SECURITY ACCESS: MOUNT ABOVE CEILING AT ENTRY WAY INTRUSION DETECTION DEVICE: WALL MTD. ACCESS CONTROL SYSTEMS SEE DETAIL 1/T0.01 FOR POWER, POWER DISCONNECT, LOW VOLTAGE CABLING, BOXES AND CONDUIT REQUIREMENTS. REFER TO ARCHITECTURAL PLANS AND DOOR SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. INTERCOM SPEAKER: 2' X 2' SQUARE CEILING MOUNTED COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROL REQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER. SPEAKER SYSTEM: CABLING COMPONENTS: THE CONTRACTOR SHALL PROVIDE ROUGH-IN FOR ALL DEVICES AND WIRING. ROUGH-IN REQUIREMENTS ARE SPECIFIED IN SECTION 261010. VERIFY ADJACENCY TO CORRESPONDING POWER RECEPTACLES. OTHER DEVICES WHOSE LOCATIONS ARE NOT DEPENDENT ON RECEPTACLE PLACEMENT SHALL BE COORDINATED WITH SYSTEM INSTALLER. WALL MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CEILING MTD. TELECOMMUNICATION JUNCTION BOX WALL MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CEILING MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CEILING OR WALL MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING ROUGH-IN FOR LOW VOLTAGE SYSTEMS: SA K P J J O S O S OS W HD C PC XX-1 T M ABBREVIATIONS: LEGEND: LIGHTING FIXTURES: UPPERCASE LETTER ADJACENT TO FIXTURE DENOTES DESIGNATION PER THE LIGHTING FIXTURE SCHEDULE. LOWERCASE LETTER DENOTES SWITCHLEG. THE RESPECTIVE SWITCH WILL HAVE THE SAME DESTINATIONS. NUMERAL DENOTES BRANCH CIRCUIT CONNECTION. REFER TO THE FIXTURE SCHEDULE FOR THE SPECIFIC FIXTURE INFORMATION. EMERGENCY FIXTURES SHALL HAVE FACTORY INSTALLED INTERNAL BATTERIES, PER SPECIFICATIONS. NL SUFFIX ADJACENT TO FIXTURE TYPE DENOTES NIGHT LIGHT. DO NOT SWITCH THESE FIXTURES. NON- EMERGENCY EMERGENCY/ BATTERY BACKUP LIGHTING FIXTURE: LINEAR FLUORESCENT ELECTRICAL EQUIPMENT: REFER TO ONE-LINE DIAGRAM AND EQUIPMENT CONNECTION SCHEDULE FOR LOAD DATA USED AS THE BASIS OF DESIGN AND REQUIRED CONNECTIONS. VERIFY LOAD AND LOCATION WITH EQUIPMENT CUT-SHEETS AND INSTALLER. GENERAL NOTES: DEVICE IDENTIFIER TAGS: NUMERAL ADJACENT TO DEVICE DENOTES BRANCH CIRCUIT CONNECTION. IDENTIFIER TAGS ADJACENT TO DEVICES INDICATE: WIRING DEVICES: RECEPTACLES: NOMINAL MOUNTING HEIGHT OF RECEPTACLES SHALL BE 18" TO CENTER, UNO. IF APPLICABLE, ADJUST SO DEVICE COVER IS IN THE CENTER OF MASONRY COURSE NEAREST THAT HEIGHT. THE HEIGHT ESTABLISHED SHALL GOVERN FOR ALL BOX INSTALLATIONS, WHERE INSTALLED IN MASONRY OR FRAMED WALLS. SWITCHES: MOUNTING HEIGHT OF SWITCHES SHALL BE 48" NOMINAL, ADJUSTED IN THE SAME MANNER AS SPECIFIED ABOVE, FOR RECEPTACLES. LOWERCASE LETTER INDICATES SWITCHLEG CONNECTION. THE RESPECTIVE FIXTURE(S) WILL HAVE THE SAME DESIGNATION. BRANCH CIRCUITS: CONDUCTOR COUNTS ARE SHOWN ON THE HOMERUNS ONLY. CONTRACTOR SHALL DETERMINE COUNTS FOR INTERMEDIATE RUNS BASED ON THE MANNER IN WHICH THE CIRCUIT ELEMENTS ARE CONNECTED. REFER TO THE SPECIFICATION SECTIONS 262010, 262080, & 26030 FOR SPECIAL REQUIREMENTS. LA-1,3,5 MISCELLANEOUS COMPONENTS: 3 4 a K O LIGHTING FIXTURE: LINEAR FLUORESCENT LIGHTING FIXTURE: LINEAR FLUORESCENT LIGHTING FIXTURE: FLUORESCENT STRIP LIGHTING FIXTURE: FLUORESCENT, WALL MTD. DOWNLIGHT/SCONCE FIXTURE EXIT: UNIVERSAL MTD. DIRECTIONAL FIXTURES: EMERGENCY TYPE LIGHT TRACK: LENGTH AS SHOWN MOUNT ABOVE COUNTERTOP OR BACKSPLASH, 9" ABOVE WORK SURFACE TO CENTER MOUNT DEVICE AT HEIGHT INDICATED PROVIDE WEATHER-PROOF COVER RECEPTACLE: SIMPLEX RECEPTACLE: DUPLEX, TAMPER RESISTANT TYPE. RECEPTACLE: GROUND-FAULT-INTERRUPTING, TAMPER RESISTANT TYPE IN-SLAB FLOOR BOX: SEE SPECIFICATIONS RECEPTACLE: DRYER, 30 AMP, 120/250 VOLT RECEPTACLE: SPECIAL PURPOSE , COORDINATE NEMA RATING WITH SPECIFIED EQUIPMENT ELECTRIC WATER COOLER POWER CONNECTION, GFI OUTLET HAND DRYER POWER CONNECTION: COORDINATE MOUNTING HEIGHT W/ ARCHITECTURAL ELEVATIONS SEE HAND DRYER INSTALLATION DETAIL 1/E7.01. RECEPTACLE FOR CLOCK (RECESSED) WITH CLOCK HANGER AND CLOCK. COORDINATE MOUNTING HEIGHT & LOCATION WITH ARCHITECTURAL FLOOR PLAN AND ELEVATIONS RECEPTACLE: CEILING MOUNTED SWITCH: SINGLE-POLE SWITCH: THREE-WAY TYPE SWITCH: FOUR-WAY TYPE SWITCH: SUBSCRIPT THAT INDICATES CORRESPONDING FIXTURES THAT SWITCH CONTROLS SWITCH: KEY-OPERATED SWITCH: OVERRIDE OCCUPANCY SENSOR, CEILING MOUNTED OCCUPANCY SENSOR, CORNER MOUNTED OCCUPANCY SENSOR, WALL MOUNTED SWITCH: MOTOR RATED, WITHOUT OVERLOAD PROTECTION DISCONNECT SWITCH DRY-TYPE TRANSFORMER PANELBOARD: SURFACE MOUNTED EQUIPMENT AS NOTED, SEE ABBREVIATIONS, THIS SHEET PHOTOCELL: LOCATE UNDER EAVES, FACING NORTH, AVOID ANY OTHER OUTSIDE LIGHT SOURCE BRANCH CIRCUIT: CONCEALED BRANCH CIRCUIT: CONCEALED IN FLOOR SLAB BRANCH CIRCUIT: EXPOSED 'HOMERUN' TO PANEL: NUMBER OF HASH MARKS INDICATES QUANTITY OF No. 12 AWG UNGROUNDED CONDUCTORS IN 3/4" RACEWAY. GROUNDED CONDUCTORS (NEUTRALS) ARE NOT SHOWN - ONE DEDICATED NEUTRAL IS REQUIRED FOR EACH UNGROUNDED CONDUCTOR INSTALLED, SEE SPECIFICATIONS. EACH CONDUCTOR SHALL BE MIN. No. 12 AWG UNLESS NOTED OTHERWISE. JUNCTION BOX: MTD. ABOVE CEILING JUNCTION BOX: WALL MTD. 7. WHERE COMPLETE BRANCH CIRCUIT WIRING IS NOT SHOWN, PROVIDE ACCORDING TO HOMERUNS SHOWN AND CORRESPONDING CIRCUIT NUMBERS ADJACENT TO THE DEVICE OR FIXTURE. REFER TO THE SPECIFICATIONS FOR THE WIRING METHODS. BRANCH CIRCUIT RATINGS SHALL BE BASED ON OVERCURRENT DEVICE RATINGS SHOWN IN THE PANEL SCHEDULES. 8. REFER TO THE ELECTRICAL PANELBOARD SCHEDULES AND EQUIPMENT RATINGS & CONNECTIONS SCHEDULE FOR VOLTAGE, BRANCH CIRCUITS REQUIREMENTS, BREAKERS SIZES AND OTHER RELATED ELECTRICAL EQUIPMENT TO BE PROVIDED AND/OR INSTALLED BY THE ELECTRICAL CONTRACTOR. C XX" WP A AMPERES AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AH AIR HANDLER AIC AMPERAGE INTERRUPT CAPABILITY ATU AIR TERMINAL UNIT A/V AUDIO/VISUAL AWG AMERICAN WIRE GAUGE BFG BELOW FINISHED GRADE B.E. BOTTOM EDGE C. CONDUIT CU CONDENSING UNIT DAH DUCTLESS AIR HANDLER DHP DUCTLESS HEAT PUMP DIA. DIAMETER V S V S VS VACANCY SENSOR, CEILING MOUNTED VACANCY SENSOR, CORNER MOUNTED VACANCY SENSOR, WALL MOUNTED THE ELECTRICAL DRAWINGS ARE ONLY PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL REVIEW ALL OF THE DRAWINGS AND SPECIFICATIONS FOR THEIR INTERRELATIONSHIP AND REQUIRED COORDINATION BETWEEN DISCIPLINES. SYMBOL WHERE SHOWN AT OR NEAR A ROOM INDICATES THAT ROOM IS SHOWN AS A TYPICAL LARGE SCALE. (2) INDICATES THE DETAIL NUMBER AND (E4.2) INDICATES THE SHEET NUMBER. ALL CONDUCTORS SHALL BE COPPER UNLESS NOTED WITH THE WORD "ALUMINUM" IN THE DESCRIPTION. EACH DOOR SHALL HAVE ONE 3/4"C. FROM DOOR FRAME TO DOOR CONTROLLER ENCLOSURE (ASSUME WITHIN 50' OF DOOR), ONE DEDICATED 20A, 120 VOLT CIRCUIT TO SAME CONTROLLER ENCLOSURE. PRIOR TO RUNNING ANY CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTED DEVICES WITH WALL MOUNTED ACOUSTICAL PANELS. SEE ARCHITECTURAL DRAWINGS FOR SPACES IN WHICH WALL PANELS ARE INSTALLED. PRIOR TO RUNNING CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTED DEVICES WITH WALL MOUNTED SAFETY PADS IN GYMNASIUM. 1. 3. 4. 5. 6. E.C.B. ENCLOSED CIRCUIT BREAKER EF EXHAUST FAN EH ELECTRIC HEATER EMCS ENERGY MANAGEMENT CONTROL UNIT FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL G GROUND GFI GROUND-FAULT INTERRUPTING HP HORSE POWER HRVU HEAT RECOVERY VENTILATING UNIT HWCP HOT WATER CIRCULATING PUMP KCMIL KILO CIRCULAR MIL MAH MAKEUP AIR HEATER MB MAIN BREAKER MCA MINIMUM CIRCUIT AMPS MIN MINIMUM MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED No. NUMBER NEC NATIONAL ELECTRIC CODE NTS NOT TO SCALE PIV POST INDICATOR VALVE RGS RIGID GALVANIZED STEEL RTU ROOFTOP UNIT SF SUPPLY FAN SPD SURGE PROTECTION DEVICE SWBD SWITCHBOARD TGB TELECOMMUNICATIONS GROUND BUS TMGB TELECOMMUNICATIONS MAIN GROUND BUS TTW THROUGH-THE-WALL HEAT PUMP TYP TYPICAL UH UNIT HEATER UNO UNLESS NOTED OTHERWISE V VOLTAGE W WATTAGE W/ WITH WH WATER HEATER WHP WALL-MOUNTED HEAT PUMP WP WEATHER PROOF XFMR TANSFORMER SMOKE DAMPER, 120V, PROVIDE POWER CONNECTION AND ALL NEEDED SMOKE DETECTION AND CONTROL MODULES AS REQUIRED BY NFPA 72 FOR PROPER OPERATION. SD FIRE ALARM REMOTE VOICE EVACUATION MICROPHONE FLUSH RECESSED WALL MOUNTED. MIC "C" DESIGNATION INDICATES CEILING MOUNTED. S SPEAKER - SEE DRAWINGS AND SPECIFICATIONS FOR TYPE. LA-1,3,5 'HOMERUN' TO PANEL FOR EQUIPMENT: SEE EQUIPMENT CONNECTION SCHEDULES FOR SIZE OF FEEDER AND NUMBER OF CONDUCTORS. V SWITCH: LOW VOLTAGE OVERRIDE SWITCH FOR VACANCY SENSOR. WHERE MULTIPLE SUBSCRIPTS ARE INDICATED ("ab" FOR EXAMPLE) PROVIDE A PUSHBUTTON FOR EACH CORRESPONDING GROUP OF FIXTURES TO BE CONTROLLED (2 BUTTON SWITCH FOR "ab" FOR EXAMPLE). THE PUSHBUTTONS SHALL BE MOUNTED UNDER A SINGLE GANG FACEPLATE. D SWITCH: DIMMER TYPE. DIMMER SHALL BE COMPATIBLE WITH BALLAST INSTALLED. PROVIDE ALL LOW VOLTAGE CABLING AND CONNECTIONS FOR 0 TO 10 VOLT DIMMING. FIRE ALARM CARBON MONOXIDE DETECTOR. O S HB OCCUPANCY SENSOR, CEILING MOUNTED HIGHBAY TYPE SCENE CONTROLLER STARTER/DISCONNECT SWITCH. SEE PLAN FOR SIZE, SEE SPECIFICATIONS FOR TYPE. 6 6 6 6 6 6 T PROFESSIONAL N E E R I G N E S I G E R E R E D No. 26308 I G R O E G A A W R. L N E R R A W NORTH 517 EAST CONGRESS STREET SAVANNAH, GEORGIA 31401 tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com PROJECT CONSULTANTS: SEAL: SHEET TITLE: ARCH. PROJECT NO: DRAWN BY: DATE: SCALE: SHEET: KEY PLAN: COGDELL & MENDRALA ARCHITECTS, PC STRUCTURAL ENGINEER: MECHANICAL & PLUMBING ENGINEER: DULOHERY WEEKS, INC. 333 COMMERICAL DRIVE SAVANNAH, GA. 31406 SAUSSY ENGINEERING 400 E. JOHNNY MERCER BOULEVARD SAVANNAH, GA 31410 CIVIL ENGINEERS: COASTLINE CONSULTING SERVICES 138 CANAL STREET POOLER, GA 31322 FTE: 750 / 900 CORE 1500 Cogdell MendralaArchitects WOLVERTON & ASSOCIATES, INC. 7 CONGRESS STREET SAVANNAH, GA 31401 ELECTRICAL & COMMUNICATIONS ENGINEER: SUSTAINABLE DESIGN CONSULTANTS 415 BONAVENTURE DRIVE THUNDERBOLT, GA. 31404 1400 1600 1100 1300 1200 1000 FACILITY CODE: 625-0122 12" = 1'-0" 9/18/2015 9:23:31 AM C:\Users\gclark\Desktop\GREG'S JOBS\20141017 ELEC-GClark - 9-9-2015.rvt E0.01 ELECTRICAL LEGEND & LIGHT FIXTURE SCHEDULE GJC AUGUST 2015 1402 MAY HOWARD ELEMENTARY REPLACEMENT SCHOOL 115 WILMINGTON ISLAND ROAD SAVANNAH, GEORGIA 31410 LIGHT FIXTURE SCHEDULE TYPE DESCRIPTION LAMPS MANUFACTURER / SERIES FINISH MOUNTING NOTES A1 2'X4' TROFFER WITH 0.125" THICK #A12 ACRYLIC LENS 2-32 T8, 2950 LUMEN, 4100K METALUX "GR8" SERIES, LITHONIA, COLUMBIA, H.E. WILLIAMS WHITE GRID A1L 2'X4' TROFFER WITH 0.125" THICK #A12 ACRYLIC LENS LED: 4800 LUMEN, 4000K METALUX "GRLED" SERIES, LITHONIA, COLUMBIA, H.E. WILLIAMS WHITE GRID A2 2'X4' TROFFER WITH 0.125" THICK #A12 ACRYLIC LENS 3-32 T8, 2950 LUMEN, 4100K METALUX "GR8" SERIES, LITHONIA, COLUMBIA, H.E. WILLIAMS WHITE GRID A3 2'X4' TROFFER WITH 0.125" THICK #A12 ACRYLIC LENS 4-32 T8, 2950 LUMEN, 4100K METALUX "GR8" SERIES, LITHONIA, COLUMBIA, H.E. WILLIAMS WHITE GRID B2 VOLUMETRIC RECESSED 2'X4' TROFFER, LINEAR FACETED REFLECTOR, AND REGRESSED REFRACTIVE SYSTEM 2-32 T8, 2900 LUMEN, 4100K METALUX "ARCLINE" SERIES, LITHONIA, COLUMBIA, H.E. WILLIAMS WHITE GRID C FULL-BODY LED HIGHBAY WITH WIDE DISTRIBUTION AND 0.125" THICK ACRYLIC LENS AND WIREGUARD IN DOOR FRAME, INTEGRATED DIMMABLE DRIVER. LED: 24000 LUMEN, 4000K METALUX "HBLED" SERIES, LITHONIA, COLUMBIA, H.E. WILLIAMS WHITE CHAIN E STRIP FIXTURE, 4 FOOT LENGTH, WITH 14 GUAGE WIRE GUARD 2-32 T8, 2950 LUMEN, 4100K LITHONIA "C" SERIES, METALUX, COLUMBIA, HE WILLIAMS WHITE SURFACE/CHAIN F SEALED GASKETED 2'X4' TROFFER WITH ,ACRYLIC PRISMATIC LENS .125 THICK 3-32 WATT, T8, 4100 K FAILSAFE "CFDFA" SERIES, DAYBRITE, LITHONIA, METALUX, COLUMBIA WHITE GRID PROVIDE GASKET SETWEEN LENS AND DOOR FRAME G1 1'X4' FIXTURE, SURFACE MOUNT, LOW PROFILE, VANDLE RESISTANT. FIXTURE SHALL BE EQUIPPED WITH MOTION SENSOR. 2-32 T8, 2900 LUMEN, 4100K FAILSAFE "HVSL" SERIES, LUMINAIRE, LITHONIA, METALUX, HUBBELL WHITE SURFACE-CEILING G2 1'X4' FIXTURE, SURFACE MOUNT, LOW PROFILE, VANDLE RESISTANT. 2-32 T8, 2900 LUMEN, 4100K FAILSAFE "HVSL" SERIES, LUMINAIRE, LITHONIA, METALUX, HUBBELL WHITE SURFACE GW 1'X4' FIXTURE, SURFACE MOUNT, LOW PROFILE, VANDLE RESISTANT. FIXTURE SHALL BE EQUIPPED WITH MOTION SENSOR. 2-32 T8, 2900 LUMEN, 4100K FAILSAFE "HVSL" SERIES, LUMINAIRE, LITHONIA, METALUX, HUBBELL WHITE SURFACE-WALL K ELEVATOR PIT LIGHT, CLEAR GLASS GLOBE WITH DIE CAST ALUMINUM GUARD 1-42 WATT TTT, 4100K HUBBELL "NV2" SERIES, RIG-A-LITE, STONECO, EXCELINE, DAYBRITE, BASELITE EXPOSED PARTS CORROSION RESISTANT WALL - IN PIT L NARROW (4" MAX) EXTRUDED ALUMINUM SLOT FIXTURE, CONTINUOUS FROSTED ACRYLIC LENSE PROVIDE END PLATES AND CORNER COMPANIONS FOR COMPLETE SEAMLESS INSTALLATION FOR LENGTH INDICATED, INCLUDING CORNERS. LED: 1500 LUMENS, 4000K FOCAL POINT "SEEM 4", LEADALITE, MARK, NEORAY WHITE FLANGE - CONTINUOUS LP1 STAIRWELL LIGHT, RADIAL LOUVEROR ACRYLIC RIBBED LENS SHIELDING, DIE-CAST ALUMINUM END CAPS, VANDAL RESISTANT 1-F32T8 UP / 2-F32T8 DOWN NEORAY CIRQUE 6-DIP, LEDALITE, COLUMBIA, PAL HOUSING AND EXPOSED PARTS - WHITE AIRCRAFT CABLE PENDANT LENGTH: STAIRWELL 2'-0" LP2 NARROW (4" MAX) EXTRUDED ALUMINUM PENDANT FIXTURE, CONTINUOUS FROSTED ACRYLIC LENS, BI-DIRECTIONAL, DIMMABLE. SEE PLAN FOR LENGTH OF FIXTURE. LED: 580 LUMENS/FT DOWN, 400 LUMENS/FT UP, 4000K FOCAL POINT "SEEM 4", NULITE, PEERLESS, NEORAY FINISHES TO BE SELECTED BY ARCHITECT, MULTIPLE FINISHES AIRCRAFT CABLE PENDANT HEIGHT: BOTTOM OF FIXTURE AT 10'-0" A.F.F. CUSTOM LENGTH CORD AND CABLE REQUIRED LP3 1 1/2" LINEAR PENDANT, MATT WHITE ACRYLIC DIFFUSER. FIXTURES SHALL BE MOUNTED AT VARIOUS ANGLES (HORIZONTALLY AND VERTICALLY) TO BE DETERMINED BY THE ARCHITECT WITH MOUNTING HEIGHTS BETWEEN 18' AND 26'AFF. LED: 32 WATT, 4000K OCL "DASH" PENDANT, SPI, OR APPROVED EQUAL. MULTIPLE TO BE SELECTED BY ARCHITECT AIRCRAFT CABLE 277 VOLT M SLOT LED, TRIM FLANGE, CONTINUOUS FROSTED ACRYLIC LENS. PROVIDE END PLATES AND CORNER COMPANIONS FOR COMPLETE SEAMLESS INSTALLATION FOR LENGTH INDICATED, INCLUDING CORNERS. FIXTURE SHALL BE MOUNTED AT 12'-0", IN LINE WITH WINDOW MULLION, COORDINATE EXACT MOUNTING AND FLANGE REQUIREMENT WITH ARCHITECT PRIOR TO ROUGH IN. FIXTURE LENGTH AS INDICATED ON THE PLAN. 625 LUMENS PER FOOT, 4000K FOCAL POINT "SEEM 4 LED RECESSED", MARK, NULITE, NEORAY WHITE RECESSED OA ROUND, CANOPY CEILING MOUNTED LED LIGHT, RING STYLE, OPAL LENS LED: 1125 LUMEN, 20 WATT, 4000K McGRAW EDISON "TT" SERIES, FAILSAFE, LUMINAIRE, LITHONIA, HUBBELL, McGRAW EDISON TO BE SELECTED BY ARCHITECT SURFACE SEE ARCHITECTURAL CANOPY DETAILS FOR MOUNTING OB ROUND, WALL MOUNTED LED LIGHT, EYELID STYLE, OPAL LENS LED: 865 LUMEN, 40 WATT, 4000K FAILSAFE "TRE15 LED", LUMINAIRE, LITHONIA, HUBBELL, McGRAW EDISON TO BE SELECTED BY ARCHITECT SURFACE PROVIDE BATTERY WHERE INDICATED OC SEALED IN-GRADE FLOOD LIGHT, 7 INCH APERTURE SIZE, VERY WIDE FLOOD, UNIT SHALL BE SUITABLE FOR CONCRETE MOUNTING - PROVIDE CONCRETE BASE, INSTALL PER MANUFACTURERS RECOMENDATIONS, THERE SHALL BE NO CONDENSATION WITHIN UNIT, ADJUSTABLE IN GROUND. LED: 700 LUMEN, 14 WATT, 4100K LUMIERE "MONACO 3002A" SERIES, HYDREL, KIM, HUBBELL, LUMIERE BRUSHED STAINLESS IN GRADE P CYLINDRICAL 26" PENDANT, 5" DEPTH, SINGLE POINT QUADPOD SUSPENSION, 10% UPLIGHT, DIMMABLE LED: 4200 LUMENS, 59 WATT, 4000K IMPACT "WAF.R", BETA CALCO, SOLERA TO BE SELECTED BY ARCHITECT PENDANT PENDANT HEIGHT: 8'-0" A.F.F. P2 CYLINDRICAL 48" PENDANT, 5" DEPTH, SINGLE POINT QUADPOD SUSPENSION, 10% UPLIGHT, DIMMABLE LED: 10000 LUMENS, 141 WATT, 4000K IMPACT "WAF.R", BETA CALCO, SOLERA MULTIPLE TO BE SELECTED BY ARCHITECT PENDANT HEIGHT: FIXTURE B.E. AT 9'-0" A.F.F. S1 SURFACE MOUNT ADJUSTABLE DOWNLIGHT, DIE-CAST ALUMINUM BODY, 45 DEGREE TILT, 361 DEGREE ROTATION, INTEGRATED DIMMABLE DRIVER LED: 1300 LUMEN, 14 WATT, 4000K LUCIFER "CY1-AD-LED", BRUCK, OR APPROVED EQUAL BRUSHED ALUMINUM SURFACE - CEILING S2 WALL MOUNT, ROUND SCONCE, DIE-CAST ALUMINUM HOUSING 2-18 QE TERON "THORPE", DESIGNPLAN, FAIL-SAFE, LITHONIA TO BE SELECTED BY ARCHITECT SURFACE T1 7/8" METAL SNOOT, 12V, TRACK LIGHT HEAD WITH STRAIGHT TRACK. DIRECT FEED TRANSFORMER. TRACK SHALL BE MOUNTED VERTICALLY, SEE ARCHITECTURAL DETAILS 6 WATT DIMMABLE LED MR16 BRUCK "CLAREO SPOT" / VIA STRAIGHT TRACK, HALO, ARCHITRAK MATTE CHROME SURFACE PROVIDE CURVED TRACK WHERE INDICATED T2 TRACK LIGHT. SEE DETAIL 4/E0.02 W STAIRWELL LIGHT, RADIAL LOUVEROR ACRYLIC RIBBED LENS SHIELDING, DIE-CAST ALUMINUM END CAPS, VANDAL RESISTANT 1-F32T8 UP / 2-F32T8 DOWN NEORAY CIRQUE 6-DIW, LEDALITE, COLUMBIA, PAL HOUSING AND EXPOSED PARTS - WHITE WALL XA SINGLE FACE EXIT LIGHT, DIE CAST ALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED. LED LITHONIA "LE" SERIES, BEGHELLI "LC1E" SERIES, DUAL LITE "CVD" SERIES, SURE-LITE "CX" SERIES BRUSHED STAINLESS UNIVERSAL 90 MINUTE BATTERY XB DOUBLE FACE EXIT LIGHT, DIE CAST ALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED. LED LITHONIA "LE" SERIES, BEGHELLI "LC1E" SERIES, DUAL LITE "CVD" SERIES, SURE-LITE "CX" SERIES BRUSHED STAINLESS UNIVERSAL 90 MINUTE BATTERY XC SINGLE FACE EXIT LIGHT, EDGE LIT, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED. LED LITHONIA "EDGR" SERIES, BEGHELLI "OL2" SERIES, HUBBELL "LE" SERIES, SURE-LITE "EUX" SERIES CLEAR UNIVERSAL CONCEALED BATTERY XD DOUBLE FACE EXIT LIGHT, EDGE LIT, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED. LED LITHONIA "EDGR" SERIES, BEGHELLI "OL2" SERIES, HUBBELL "LE" SERIES, SURE-LITE "EUX" SERIES CLEAR UNIVERSAL CONCEALED BATTERY XEM 2 HEAD, WALL MOUNT EMERGENCY BATTERY WITH FIXTURE LITHONIA "ELM" SERIES, BEGHELLI, HUBBELL, SURE-LITE CHLORIDE, SURELITE, DUALITE BLACK SURFACE 90 MINUTE BATTERY 1 GENERAL: REFER TO LIGHTING PLANS FOR BALLAST VOLTAGES AND CONFIGURATION OF FIXTURES. FIXTURES CONTROLLED BY MULTIPLE SWITCHES SHALL HAVE CORRESPONDING QUANTITY OF BALLASTS. 2 FIXTURES SHALL BE MOUNTED SUSPENDED OR SURFACE, GIVING RIGHT OF WAY TO HVAC DUCT WORK AND/OR EQUIPMENT. 3 PROVIDE BACKBOX ON ALL FIXTURES OF THIS TYPE SO THAT FIXTURES WITH AND WITHOUT EMERGENCY BALLAST ARE AT THE SAME DEPTH. 4 GENERAL: COORINATE ALL MOUNTING OF FIXTURES (GRID/FLANGE) WITH ARCHITECTURAL RCP. 5 FIXTURES SHALL BE SELECTED FROM THE FIXTURE SCHEDULE NOT ONLY BY CATALOG NUMBER BUT WITH CONSIDERATION TO MOUNTING, NUMBER AND TYPE OF LAMPS, AND REFERENCED NOTES. THE FIRST FIXTURE INDICATED FOR EACH TYPE WITH CATALOG NUMBER IS THE BASIS OF DESIGN FIXTURE, OTHER LISTED MANUFACTURES PRODUCE EQUAL FIXTURE TO THE BASIS OF DESIGN FIXTURE. . LIGHT FIXTURE SCHEDULE NOTES: REVISION SCHEDULE DATE DESCRIPTION 9-04-2015 Addendum No. 1 9-09-2015 Addendum No. 2 9-18-2015 Addendum No. 6
Transcript

FACP

FSCU

VS

WF

FAA

DH

2E4.2

F FIRE ALARM PULL STATION. WALL MOUNTED 3 FT.-6 IN.ABOVE FLOOR.

FIRE ALARM SIGNAL, SPEAKER AND FLASHING LIGHT, 6'-8" AFF.

FIRE ALARM STROBE LIGHT, 6'-8" IN. MOUNTING HEIGHT.

FIRE ALARM CONNECTION, HOOD EXTINGUISHING SYSTEM, SEEMECHANICAL DRAWINGS FOR LOCATION. INTERLOCK WITH SHUNTTRIP BREAKERS FOR EQUIPMENT UNDER HOOD.

FIRE ALARM REMOTE LCD ANNUNCIATOR PANEL. FLUSH RECESSEDWALL MOUNTED.

FIRE ALARM DOOR HOLDER, WALL MOUNTED, CONSULT ARCHITECTURALDRAWINGS TO DETERMINE TYPE REQUIRED. PROVIDE POWER FROMNEAREST RECEPTACLE CIRCUIT AND CONNECT TO FIRE ALARM SYSTEM.

TAMPER SWITCH, FURNISHED AND INSTALLED WITH SPRINKLERSYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL.

FLOW SWITCH, FURNISHED AND INSTALLED WITH SPRINKLERSYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL.

FIRE ALARM SMOKE DETECTOR, CEILING MOUNTED.

FIRE ALARM DUCT SMOKE DETECTOR LOCATED IN HVAC DUCT.

FIRE ALARM CONTROL PANEL, SURFACE WALL MOUNTED.

FIRE ALARM SIGNAL, HORN. 6 FT.-8 IN. MOUNTING HEIGHT.

FIRE ALARM HEAT DETECTOR, 135 DEG, OPERATION.

P

WEATHER PROOF.

FIRE ALARM STROBE LIGHT, CEILING MOUNTED.

S

M

FIRE ALARM:

H

S WP

IC

AD

AC

S

2.

COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROLREQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER.

INTRUSION DETECTION SYSTEM:

CONDUIT SLEEVE: NUMBER & SIZE, (2)-2" FOR ALLCLASSROOMS, (1)-2" FOR ALL OFFICES, UNO

CABLE TRAY: SIZE AS INDICATED, 18"W x 4"H TYP.

INTERCOM SPEAKER: WEATHERPROOF WALL MOUNTED AT96"AFF.

MICROPHONE JACK: WALL MOUNTED AT 18" AFF, UNO.

ENHANCED STAFF PHONE: WALL MOUNTED 48" AFF

ADMINISTRATIVE DISPLAY PHONE: WALL MOUNT AT 48" AFF

INTRUSION SYSTEM: KEY-PAD, MOUNT 48"AFF

SECURITY ACCESS: MOUNT ABOVE CEILING AT ENTRY WAY

INTRUSION DETECTION DEVICE: WALL MTD.

ACCESS CONTROL SYSTEMS

SEE DETAIL 1/T0.01 FOR POWER, POWER DISCONNECT, LOW VOLTAGE CABLING,BOXES AND CONDUIT REQUIREMENTS. REFER TO ARCHITECTURAL PLANSAND DOOR SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

INTERCOM SPEAKER: 2' X 2' SQUARE CEILING MOUNTED

COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROLREQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER.

SPEAKER SYSTEM:

CABLING COMPONENTS:

THE CONTRACTOR SHALL PROVIDE ROUGH-IN FOR ALL DEVICES ANDWIRING. ROUGH-IN REQUIREMENTS ARE SPECIFIED IN SECTION 261010. VERIFY ADJACENCY TO CORRESPONDING POWER RECEPTACLES. OTHERDEVICES WHOSE LOCATIONS ARE NOT DEPENDENT ON RECEPTACLEPLACEMENT SHALL BE COORDINATED WITH SYSTEM INSTALLER.

WALL MTD. TELECOMMUNICATION JUNCTION BOX ANDCONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING

CEILING MTD. TELECOMMUNICATION JUNCTION BOX

WALL MTD. TELECOMMUNICATION JUNCTION BOX ANDCONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING

CEILING MTD. TELECOMMUNICATION JUNCTION BOX ANDCONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING

CEILING OR WALL MTD. TELECOMMUNICATION JUNCTION BOX ANDCONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING

ROUGH-IN FOR LOW VOLTAGE SYSTEMS:

SA

KP

J

J

OS

OS

OS

W

HD

C

PC

XX-1

T

M

ABBREVIATIONS:

LEGEND:

LIGHTING FIXTURES:

UPPERCASE LETTER ADJACENT TO FIXTURE DENOTES DESIGNATION PER THELIGHTING FIXTURE SCHEDULE. LOWERCASE LETTER DENOTES SWITCHLEG. THERESPECTIVE SWITCH WILL HAVE THE SAME DESTINATIONS. NUMERAL DENOTESBRANCH CIRCUIT CONNECTION.

REFER TO THE FIXTURE SCHEDULE FOR THE SPECIFIC FIXTURE INFORMATION.

EMERGENCY FIXTURES SHALL HAVE FACTORY INSTALLED INTERNAL BATTERIES,PER SPECIFICATIONS.

NL SUFFIX ADJACENT TO FIXTURE TYPE DENOTES NIGHT LIGHT. DO NOT SWITCHTHESE FIXTURES.

NON-EMERGENCY

EMERGENCY/BATTERY BACKUP

LIGHTING FIXTURE: LINEAR FLUORESCENT

ELECTRICAL EQUIPMENT:

REFER TO ONE-LINE DIAGRAM AND EQUIPMENT CONNECTION SCHEDULE FORLOAD DATA USED AS THE BASIS OF DESIGN AND REQUIRED CONNECTIONS.VERIFY LOAD AND LOCATION WITH EQUIPMENT CUT-SHEETS AND INSTALLER.

GENERAL NOTES:

DEVICE IDENTIFIER TAGS:

NUMERAL ADJACENT TO DEVICE DENOTES BRANCH CIRCUIT CONNECTION.IDENTIFIER TAGS ADJACENT TO DEVICES INDICATE:

WIRING DEVICES:

RECEPTACLES:

NOMINAL MOUNTING HEIGHT OF RECEPTACLES SHALL BE 18" TO CENTER, UNO. IFAPPLICABLE, ADJUST SO DEVICE COVER IS IN THE CENTER OF MASONRY COURSENEAREST THAT HEIGHT. THE HEIGHT ESTABLISHED SHALL GOVERN FOR ALL BOXINSTALLATIONS, WHERE INSTALLED IN MASONRY OR FRAMED WALLS.

SWITCHES:

MOUNTING HEIGHT OF SWITCHES SHALL BE 48" NOMINAL, ADJUSTED IN THE SAMEMANNER AS SPECIFIED ABOVE, FOR RECEPTACLES. LOWERCASE LETTER INDICATESSWITCHLEG CONNECTION. THE RESPECTIVE FIXTURE(S) WILL HAVE THE SAMEDESIGNATION.

BRANCH CIRCUITS:

CONDUCTOR COUNTS ARE SHOWN ON THE HOMERUNS ONLY. CONTRACTORSHALL DETERMINE COUNTS FOR INTERMEDIATE RUNS BASED ON THE MANNERIN WHICH THE CIRCUIT ELEMENTS ARE CONNECTED. REFER TO THESPECIFICATION SECTIONS 262010, 262080, & 26030 FOR SPECIALREQUIREMENTS.

LA-1,3,5

MISCELLANEOUS COMPONENTS:

3

4

a

K

O

LIGHTING FIXTURE: LINEAR FLUORESCENT

LIGHTING FIXTURE: LINEAR FLUORESCENT

LIGHTING FIXTURE: FLUORESCENT STRIP

LIGHTING FIXTURE: FLUORESCENT, WALL MTD.

DOWNLIGHT/SCONCE FIXTURE

EXIT: UNIVERSAL MTD.

DIRECTIONAL FIXTURES: EMERGENCY TYPE

LIGHT TRACK: LENGTH AS SHOWN

MOUNT ABOVE COUNTERTOP OR BACKSPLASH, 9" ABOVEWORK SURFACE TO CENTER

MOUNT DEVICE AT HEIGHT INDICATED

PROVIDE WEATHER-PROOF COVER

RECEPTACLE: SIMPLEX

RECEPTACLE: DUPLEX, TAMPER RESISTANT TYPE.

RECEPTACLE: GROUND-FAULT-INTERRUPTING, TAMPERRESISTANT TYPE

IN-SLAB FLOOR BOX: SEE SPECIFICATIONS

RECEPTACLE: DRYER, 30 AMP, 120/250 VOLT

RECEPTACLE: SPECIAL PURPOSE , COORDINATE NEMARATING WITH SPECIFIED EQUIPMENT

ELECTRIC WATER COOLER POWER CONNECTION, GFI OUTLET

HAND DRYER POWER CONNECTION: COORDINATE MOUNTINGHEIGHT W/ ARCHITECTURAL ELEVATIONSSEE HAND DRYER INSTALLATION DETAIL 1/E7.01.

RECEPTACLE FOR CLOCK (RECESSED) WITH CLOCKHANGER AND CLOCK. COORDINATE MOUNTING HEIGHT &LOCATION WITH ARCHITECTURAL FLOOR PLAN ANDELEVATIONS

RECEPTACLE: CEILING MOUNTED

SWITCH: SINGLE-POLE

SWITCH: THREE-WAY TYPE

SWITCH: FOUR-WAY TYPE

SWITCH: SUBSCRIPT THAT INDICATES CORRESPONDINGFIXTURES THAT SWITCH CONTROLS

SWITCH: KEY-OPERATED

SWITCH: OVERRIDE

OCCUPANCY SENSOR, CEILING MOUNTED

OCCUPANCY SENSOR, CORNER MOUNTED

OCCUPANCY SENSOR, WALL MOUNTED

SWITCH: MOTOR RATED, WITHOUT OVERLOAD PROTECTION

DISCONNECT SWITCH

DRY-TYPE TRANSFORMER

PANELBOARD: SURFACE MOUNTED

EQUIPMENT AS NOTED, SEE ABBREVIATIONS, THIS SHEET

PHOTOCELL: LOCATE UNDER EAVES, FACING NORTH, AVOIDANY OTHER OUTSIDE LIGHT SOURCE

BRANCH CIRCUIT: CONCEALED

BRANCH CIRCUIT: CONCEALED IN FLOOR SLAB

BRANCH CIRCUIT: EXPOSED

'HOMERUN' TO PANEL: NUMBER OF HASH MARKSINDICATES QUANTITY OF No. 12 AWG UNGROUNDEDCONDUCTORS IN 3/4" RACEWAY. GROUNDEDCONDUCTORS (NEUTRALS) ARE NOT SHOWN - ONEDEDICATED NEUTRAL IS REQUIRED FOR EACHUNGROUNDED CONDUCTOR INSTALLED, SEESPECIFICATIONS. EACH CONDUCTOR SHALL BE MIN. No.12 AWG UNLESS NOTED OTHERWISE.

JUNCTION BOX: MTD. ABOVE CEILING

JUNCTION BOX: WALL MTD. 7. WHERE COMPLETE BRANCH CIRCUIT WIRING IS NOT SHOWN, PROVIDE ACCORDINGTO HOMERUNS SHOWN AND CORRESPONDING CIRCUIT NUMBERS ADJACENT TO THEDEVICE OR FIXTURE. REFER TO THE SPECIFICATIONS FOR THE WIRING METHODS.BRANCH CIRCUIT RATINGS SHALL BE BASED ON OVERCURRENT DEVICE RATINGSSHOWN IN THE PANEL SCHEDULES.

8. REFER TO THE ELECTRICAL PANELBOARD SCHEDULES AND EQUIPMENT RATINGS &CONNECTIONS SCHEDULE FOR VOLTAGE, BRANCH CIRCUITS REQUIREMENTS,BREAKERS SIZES AND OTHER RELATED ELECTRICAL EQUIPMENT TO BE PROVIDEDAND/OR INSTALLED BY THE ELECTRICAL CONTRACTOR.

C

XX"

WP

A AMPERES

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AIR HANDLER

AIC AMPERAGE INTERRUPT CAPABILITY

ATU AIR TERMINAL UNIT

A/V AUDIO/VISUAL

AWG AMERICAN WIRE GAUGE

BFG BELOW FINISHED GRADE

B.E. BOTTOM EDGE

C. CONDUIT

CU CONDENSING UNIT

DAH DUCTLESS AIR HANDLER

DHP DUCTLESS HEAT PUMP

DIA. DIAMETER

VS

VS

VS

VACANCY SENSOR, CEILING MOUNTED

VACANCY SENSOR, CORNER MOUNTED

VACANCY SENSOR, WALL MOUNTED

THE ELECTRICAL DRAWINGS ARE ONLY PART OF THE CONTRACT DOCUMENTS.THE CONTRACTOR SHALL REVIEW ALL OF THE DRAWINGS AND SPECIFICATIONSFOR THEIR INTERRELATIONSHIP AND REQUIRED COORDINATION BETWEENDISCIPLINES.

SYMBOL WHERE SHOWN AT OR NEAR A ROOM INDICATES THATROOM IS SHOWN AS A TYPICAL LARGE SCALE. (2) INDICATESTHE DETAIL NUMBER AND (E4.2) INDICATES THE SHEET NUMBER.

ALL CONDUCTORS SHALL BE COPPER UNLESS NOTED WITH THE WORD "ALUMINUM"IN THE DESCRIPTION.

EACH DOOR SHALL HAVE ONE 3/4"C. FROM DOOR FRAME TO DOOR CONTROLLERENCLOSURE (ASSUME WITHIN 50' OF DOOR), ONE DEDICATED 20A, 120 VOLT CIRCUITTO SAME CONTROLLER ENCLOSURE.

PRIOR TO RUNNING ANY CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTEDDEVICES WITH WALL MOUNTED ACOUSTICAL PANELS. SEE ARCHITECTURAL DRAWINGSFOR SPACES IN WHICH WALL PANELS ARE INSTALLED.

PRIOR TO RUNNING CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTED DEVICESWITH WALL MOUNTED SAFETY PADS IN GYMNASIUM.

1.

3.

4.

5.

6.

E.C.B. ENCLOSED CIRCUIT BREAKER

EF EXHAUST FAN

EH ELECTRIC HEATER

EMCS ENERGY MANAGEMENT CONTROL UNIT

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

G GROUND

GFI GROUND-FAULT INTERRUPTING

HP HORSE POWER

HRVU HEAT RECOVERY VENTILATING UNIT

HWCP HOT WATER CIRCULATING PUMP

KCMIL KILO CIRCULAR MIL

MAH MAKEUP AIR HEATER

MB MAIN BREAKER

MCA MINIMUM CIRCUIT AMPS

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MTD MOUNTED

No. NUMBER

NEC NATIONAL ELECTRIC CODE

NTS NOT TO SCALE

PIV POST INDICATOR VALVE

RGS RIGID GALVANIZED STEEL

RTU ROOFTOP UNIT

SF SUPPLY FAN

SPD SURGE PROTECTION DEVICE

SWBD SWITCHBOARD

TGB TELECOMMUNICATIONS GROUND BUS

TMGB TELECOMMUNICATIONS MAIN GROUND BUS

TTW THROUGH-THE-WALL HEAT PUMP

TYP TYPICAL

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

V VOLTAGE

W WATTAGE

W/ WITH

WH WATER HEATER

WHP WALL-MOUNTED HEAT PUMP

WP WEATHER PROOF

XFMR TANSFORMER

SMOKE DAMPER, 120V, PROVIDE POWER CONNECTION AND ALLNEEDED SMOKE DETECTION AND CONTROL MODULES AS REQUIREDBY NFPA 72 FOR PROPER OPERATION.

SD

FIRE ALARM REMOTE VOICE EVACUATION MICROPHONE FLUSH RECESSEDWALL MOUNTED.

MIC

"C" DESIGNATION INDICATES CEILING MOUNTED.

S SPEAKER - SEE DRAWINGS AND SPECIFICATIONS FOR TYPE.

LA-1,3,5'HOMERUN' TO PANEL FOR EQUIPMENT: SEE EQUIPMENTCONNECTION SCHEDULES FOR SIZE OF FEEDER ANDNUMBER OF CONDUCTORS.

V SWITCH: LOW VOLTAGE OVERRIDE SWITCH FOR VACANCYSENSOR. WHERE MULTIPLE SUBSCRIPTS ARE INDICATED("ab" FOR EXAMPLE) PROVIDE A PUSHBUTTON FOR EACHCORRESPONDING GROUP OF FIXTURES TO BE CONTROLLED(2 BUTTON SWITCH FOR "ab" FOR EXAMPLE). THEPUSHBUTTONS SHALL BE MOUNTED UNDER A SINGLE GANGFACEPLATE.

DSWITCH: DIMMER TYPE. DIMMER SHALL BE COMPATIBLE WITHBALLAST INSTALLED. PROVIDE ALL LOW VOLTAGE CABLINGAND CONNECTIONS FOR 0 TO 10 VOLT DIMMING.

FIRE ALARM CARBON MONOXIDE DETECTOR.

OSHB

OCCUPANCY SENSOR, CEILING MOUNTED HIGHBAY TYPE

SCENE CONTROLLER

STARTER/DISCONNECT SWITCH. SEE PLAN FOR SIZE, SEESPECIFICATIONS FOR TYPE.

6

6

6

6

6

6

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

12" = 1'-0"9/1

8/2

015 9

:23:3

1 A

MC

:\U

sers

\gcla

rk\D

eskto

p\G

RE

G'S

JO

BS

\20141017 E

LE

C-G

Cla

rk -

9-9

-2015.r

vt

E0.01

ELECTRICALLEGEND &LIGHT FIXTURESCHEDULE

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION LAMPS

MANUFACTURER /

SERIES FINISH MOUNTING NOTES

A1 2'X4' TROFFER WITH 0.125" THICK #A12 ACRYLIC LENS 2-32 T8, 2950LUMEN, 4100K

METALUX "GR8"SERIES, LITHONIA,COLUMBIA, H.E.WILLIAMS

WHITE GRID

A1L 2'X4' TROFFER WITH 0.125" THICK #A12 ACRYLIC LENS LED: 4800LUMEN, 4000K

METALUX "GRLED"SERIES, LITHONIA,COLUMBIA, H.E.WILLIAMS

WHITE GRID

A2 2'X4' TROFFER WITH 0.125" THICK #A12 ACRYLIC LENS 3-32 T8, 2950LUMEN, 4100K

METALUX "GR8"SERIES, LITHONIA,COLUMBIA, H.E.WILLIAMS

WHITE GRID

A3 2'X4' TROFFER WITH 0.125" THICK #A12 ACRYLIC LENS 4-32 T8, 2950LUMEN, 4100K

METALUX "GR8"SERIES, LITHONIA,COLUMBIA, H.E.WILLIAMS

WHITE GRID

B2 VOLUMETRIC RECESSED 2'X4' TROFFER, LINEARFACETED REFLECTOR, AND REGRESSED REFRACTIVESYSTEM

2-32 T8, 2900LUMEN, 4100K

METALUX "ARCLINE"SERIES, LITHONIA,COLUMBIA, H.E.WILLIAMS

WHITE GRID

C FULL-BODY LED HIGHBAY WITH WIDE DISTRIBUTION AND0.125" THICK ACRYLIC LENS AND WIREGUARD IN DOORFRAME, INTEGRATED DIMMABLE DRIVER.

LED: 24000LUMEN, 4000K

METALUX "HBLED"SERIES, LITHONIA,COLUMBIA, H.E.WILLIAMS

WHITE CHAIN

E STRIP FIXTURE, 4 FOOT LENGTH, WITH 14 GUAGE WIREGUARD

2-32 T8, 2950LUMEN, 4100K

LITHONIA "C" SERIES,METALUX, COLUMBIA,HE WILLIAMS

WHITE SURFACE/CHAIN

F SEALED GASKETED 2'X4' TROFFER WITH ,ACRYLICPRISMATIC LENS .125 THICK

3-32 WATT, T8,4100 K

FAILSAFE "CFDFA"SERIES, DAYBRITE,LITHONIA, METALUX,COLUMBIA

WHITE GRID PROVIDE GASKET SETWEENLENS AND DOOR FRAME

G1 1'X4' FIXTURE, SURFACE MOUNT, LOW PROFILE, VANDLERESISTANT. FIXTURE SHALL BE EQUIPPED WITHMOTION SENSOR.

2-32 T8, 2900LUMEN, 4100K

FAILSAFE "HVSL"SERIES, LUMINAIRE,LITHONIA, METALUX,HUBBELL

WHITE SURFACE-CEILING

G2 1'X4' FIXTURE, SURFACE MOUNT, LOW PROFILE, VANDLERESISTANT.

2-32 T8, 2900LUMEN, 4100K

FAILSAFE "HVSL"SERIES, LUMINAIRE,LITHONIA, METALUX,HUBBELL

WHITE SURFACE

GW 1'X4' FIXTURE, SURFACE MOUNT, LOW PROFILE, VANDLERESISTANT. FIXTURE SHALL BE EQUIPPED WITHMOTION SENSOR.

2-32 T8, 2900LUMEN, 4100K

FAILSAFE "HVSL"SERIES, LUMINAIRE,LITHONIA, METALUX,HUBBELL

WHITE SURFACE-WALL

K ELEVATOR PIT LIGHT, CLEAR GLASS GLOBE WITH DIECAST ALUMINUM GUARD

1-42 WATT TTT,4100K

HUBBELL "NV2"SERIES, RIG-A-LITE,STONECO, EXCELINE,DAYBRITE, BASELITE

EXPOSEDPARTS

CORROSIONRESISTANT

WALL - IN PIT

L NARROW (4" MAX) EXTRUDED ALUMINUM SLOTFIXTURE, CONTINUOUS FROSTED ACRYLIC LENSEPROVIDE END PLATES AND CORNER COMPANIONS FORCOMPLETE SEAMLESS INSTALLATION FOR LENGTHINDICATED, INCLUDING CORNERS.

LED: 1500LUMENS, 4000K

FOCAL POINT "SEEM4", LEADALITE, MARK,NEORAY

WHITE FLANGE -CONTINUOUS

LP1 STAIRWELL LIGHT, RADIAL LOUVEROR ACRYLIC RIBBEDLENS SHIELDING, DIE-CAST ALUMINUM END CAPS,VANDAL RESISTANT

1-F32T8 UP /2-F32T8 DOWN

NEORAY CIRQUE6-DIP, LEDALITE,COLUMBIA, PAL

HOUSINGAND

EXPOSEDPARTS -WHITE

AIRCRAFT CABLE PENDANT LENGTH:STAIRWELL 2'-0"

LP2 NARROW (4" MAX) EXTRUDED ALUMINUM PENDANTFIXTURE, CONTINUOUS FROSTED ACRYLIC LENS,BI-DIRECTIONAL, DIMMABLE. SEE PLAN FOR LENGTH OFFIXTURE.

LED: 580LUMENS/FTDOWN, 400

LUMENS/FT UP,4000K

FOCAL POINT "SEEM4", NULITE, PEERLESS,NEORAY

FINISHES TOBE SELECTED

BYARCHITECT,MULTIPLEFINISHES

AIRCRAFT CABLE PENDANT HEIGHT: BOTTOMOF FIXTURE AT 10'-0" A.F.F.CUSTOM LENGTH CORD ANDCABLE REQUIRED

LP3 1 1/2" LINEAR PENDANT, MATT WHITE ACRYLICDIFFUSER. FIXTURES SHALL BE MOUNTED AT VARIOUSANGLES (HORIZONTALLY AND VERTICALLY) TO BEDETERMINED BY THE ARCHITECT WITH MOUNTINGHEIGHTS BETWEEN 18' AND 26'AFF.

LED: 32 WATT,4000K

OCL "DASH" PENDANT,SPI, OR APPROVEDEQUAL.

MULTIPLE TOBE SELECTED

BYARCHITECT

AIRCRAFT CABLE 277 VOLT

M SLOT LED, TRIM FLANGE, CONTINUOUS FROSTEDACRYLIC LENS. PROVIDE END PLATES AND CORNERCOMPANIONS FOR COMPLETE SEAMLESS INSTALLATIONFOR LENGTH INDICATED, INCLUDING CORNERS.FIXTURE SHALL BE MOUNTED AT 12'-0", IN LINE WITHWINDOW MULLION, COORDINATE EXACT MOUNTING ANDFLANGE REQUIREMENT WITH ARCHITECT PRIOR TOROUGH IN. FIXTURE LENGTH AS INDICATED ON THEPLAN.

625 LUMENSPER FOOT,

4000K

FOCAL POINT "SEEM 4LED RECESSED",MARK, NULITE,NEORAY

WHITE RECESSED

OA ROUND, CANOPY CEILING MOUNTED LED LIGHT, RINGSTYLE, OPAL LENS

LED: 1125LUMEN, 20

WATT, 4000K

McGRAW EDISON "TT"SERIES, FAILSAFE,LUMINAIRE, LITHONIA,HUBBELL, McGRAWEDISON

TO BESELECTED BY

ARCHITECT

SURFACE SEE ARCHITECTURALCANOPY DETAILS FORMOUNTING

OB ROUND, WALL MOUNTED LED LIGHT, EYELID STYLE,OPAL LENS

LED: 865 LUMEN,40 WATT, 4000K

FAILSAFE "TRE15LED", LUMINAIRE,LITHONIA, HUBBELL,McGRAW EDISON

TO BESELECTED BY

ARCHITECT

SURFACE PROVIDE BATTERY WHEREINDICATED

OC SEALED IN-GRADE FLOOD LIGHT, 7 INCH APERTURESIZE, VERY WIDE FLOOD, UNIT SHALL BE SUITABLE FORCONCRETE MOUNTING - PROVIDE CONCRETE BASE,INSTALL PER MANUFACTURERS RECOMENDATIONS,THERE SHALL BE NO CONDENSATION WITHIN UNIT,ADJUSTABLE IN GROUND.

LED: 700 LUMEN,14 WATT, 4100K

LUMIERE "MONACO3002A" SERIES,HYDREL, KIM,HUBBELL, LUMIERE

BRUSHEDSTAINLESS

IN GRADE

P CYLINDRICAL 26" PENDANT, 5" DEPTH, SINGLE POINTQUADPOD SUSPENSION, 10% UPLIGHT, DIMMABLE

LED: 4200LUMENS, 59WATT, 4000K

IMPACT "WAF.R", BETACALCO, SOLERA

TO BESELECTED BY

ARCHITECT

PENDANT PENDANT HEIGHT: 8'-0" A.F.F.

P2 CYLINDRICAL 48" PENDANT, 5" DEPTH, SINGLE POINTQUADPOD SUSPENSION, 10% UPLIGHT, DIMMABLE

LED: 10000LUMENS, 141WATT, 4000K

IMPACT "WAF.R", BETACALCO, SOLERA

MULTIPLE TOBE SELECTED

BYARCHITECT

PENDANT HEIGHT:FIXTURE B.E. AT 9'-0"

A.F.F.

S1 SURFACE MOUNT ADJUSTABLE DOWNLIGHT, DIE-CASTALUMINUM BODY, 45 DEGREE TILT, 361 DEGREEROTATION, INTEGRATED DIMMABLE DRIVER

LED: 1300LUMEN, 14

WATT, 4000K

LUCIFER"CY1-AD-LED", BRUCK,OR APPROVED EQUAL

BRUSHEDALUMINUM

SURFACE - CEILING

S2 WALL MOUNT, ROUND SCONCE, DIE-CAST ALUMINUMHOUSING

2-18 QE TERON "THORPE",DESIGNPLAN,FAIL-SAFE, LITHONIA

TO BESELECTED BY

ARCHITECT

SURFACE

T1 7/8" METAL SNOOT, 12V, TRACK LIGHT HEAD WITHSTRAIGHT TRACK. DIRECT FEED TRANSFORMER.TRACK SHALL BE MOUNTED VERTICALLY, SEEARCHITECTURAL DETAILS

6 WATTDIMMABLE LED

MR16

BRUCK "CLAREOSPOT" / VIA STRAIGHTTRACK, HALO,ARCHITRAK

MATTECHROME

SURFACE PROVIDE CURVED TRACKWHERE INDICATED

T2 TRACK LIGHT. SEE DETAIL 4/E0.02

W STAIRWELL LIGHT, RADIAL LOUVEROR ACRYLIC RIBBEDLENS SHIELDING, DIE-CAST ALUMINUM END CAPS,VANDAL RESISTANT

1-F32T8 UP /2-F32T8 DOWN

NEORAY CIRQUE6-DIW, LEDALITE,COLUMBIA, PAL

HOUSINGAND

EXPOSEDPARTS -WHITE

WALL

XA SINGLE FACE EXIT LIGHT, DIE CAST ALUMINUM,UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTIONOF ARROWS AS INDICATED.

LED LITHONIA "LE" SERIES,BEGHELLI "LC1E"SERIES, DUAL LITE"CVD" SERIES,SURE-LITE "CX"SERIES

BRUSHEDSTAINLESS

UNIVERSAL 90 MINUTE BATTERY

XB DOUBLE FACE EXIT LIGHT, DIE CAST ALUMINUM,UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTIONOF ARROWS AS INDICATED.

LED LITHONIA "LE" SERIES,BEGHELLI "LC1E"SERIES, DUAL LITE"CVD" SERIES,SURE-LITE "CX"SERIES

BRUSHEDSTAINLESS

UNIVERSAL 90 MINUTE BATTERY

XC SINGLE FACE EXIT LIGHT, EDGE LIT, UNIVERSALMOUNTING, GREEN LETTERS - DIRECTION OF ARROWSAS INDICATED.

LED LITHONIA "EDGR"SERIES, BEGHELLI"OL2" SERIES,HUBBELL "LE" SERIES,SURE-LITE "EUX"SERIES

CLEAR UNIVERSAL CONCEALED BATTERY

XD DOUBLE FACE EXIT LIGHT, EDGE LIT, UNIVERSALMOUNTING, GREEN LETTERS - DIRECTION OF ARROWSAS INDICATED.

LED LITHONIA "EDGR"SERIES, BEGHELLI"OL2" SERIES,HUBBELL "LE" SERIES,SURE-LITE "EUX"SERIES

CLEAR UNIVERSAL CONCEALED BATTERY

XEM 2 HEAD, WALL MOUNT EMERGENCYBATTERY

WITH FIXTURE LITHONIA "ELM"SERIES, BEGHELLI,HUBBELL, SURE-LITECHLORIDE, SURELITE,DUALITE

BLACK SURFACE 90 MINUTE BATTERY

1 GENERAL: REFER TO LIGHTING PLANS FOR BALLAST VOLTAGES AND CONFIGURATION OF FIXTURES. FIXTURES CONTROLLED BYMULTIPLE SWITCHES SHALL HAVE CORRESPONDING QUANTITY OF BALLASTS.

2 FIXTURES SHALL BE MOUNTED SUSPENDED OR SURFACE, GIVING RIGHT OF WAY TO HVAC DUCT WORK AND/OR EQUIPMENT.

3 PROVIDE BACKBOX ON ALL FIXTURES OF THIS TYPE SO THAT FIXTURES WITH AND WITHOUT EMERGENCY BALLAST ARE AT THE SAMEDEPTH.

4 GENERAL: COORINATE ALL MOUNTING OF FIXTURES (GRID/FLANGE) WITH ARCHITECTURAL RCP.

5 FIXTURES SHALL BE SELECTED FROM THE FIXTURE SCHEDULE NOT ONLY BY CATALOG NUMBER BUT WITH CONSIDERATION TOMOUNTING, NUMBER AND TYPE OF LAMPS, AND REFERENCED NOTES. THE FIRST FIXTURE INDICATED FOR EACH TYPE WITH CATALOGNUMBER IS THE BASIS OF DESIGN FIXTURE, OTHER LISTED MANUFACTURES PRODUCE EQUAL FIXTURE TO THE BASIS OF DESIGNFIXTURE. .

LIGHT FIXTURE SCHEDULE NOTES: REVISION SCHEDULE

DATE DESCRIPTION

9-04-2015 Addendum No. 1

9-09-2015 Addendum No. 2

9-18-2015 Addendum No. 6

HD HD

HD HD

WW

WP

WP

WP

C

C

AV

WP

J

J

C

J

C

C C

C

C

WP

WP

CC

C

WP WP

WP WP

J J J

J J J

C

C

C

CHASE

1022.1

JAN

1022

MEN

1021

WOMEN

1023

CORRIDOR

1004

CORRIDOR

1001.1

CORRIDOR

1001.2

VESTIBULE

1000

RECORDS

1011

STORAGE

1020

MAILROOM

1005

CORRIDOR

1001

CLOS

1012.2

LEAD TEACHER

1016ASSIST. PRINCIPAL

1018

TESTING

1014

CLOSET

1014.1

JAN

1015

TLT

1017

SITTING AREA

1004.1SUPPLY

1007

CLINIC

1019

COTS

1019.1

CORR

1004.2

CLOSET

1004.4

CORR

1004.3

TLT

1012.1

CONFERENCE

1010

PRINCIPAL

1012

TLT

1019.2TLT

1013

WORKROOM

1006

OFFICE

1009

DATA CLERK

1008

CLERICAL

1003

RECEPTION

1002

THIS AREA SERVED BYPANEL: L1A

THIS AREA SERVED BYPANEL: L1B

/1 E2.13

/1 E2.13

/1

E2.1

1/

1E

2.1

1

/1 E2.12

C

C

C

C

C

NOTE 3

CC

C

C

C C

NOTE 1

C C

C

C

C

C

NOTE 4

C

CNOTE 2

NOTE 6

NOTE 7

NOTE 2

NOTE 9

NOTE 8

NOTE 10

NOTE 11

NOTE 11

NOTE 12

6060

60

60

58 58 2 4

5858

58

56

56 56

6 8

56

L1B- 5658 60

60

56

L1B- 24

L1B- 68

7 7

5

5

9

9

5

3

3

3

3

1

1

1

35

1

35

5

57

9

53

53

55

57

53

53

51

51

51

51 51 49

49

49

49

49

4545

45

45

43

43

43

43

41

41 41

39

41

3939

47

1947

47

47

47

21 21 21

21

19

35

191919

21

2123 25,27 33

31

23

23

29

17

17

17

17

39 3737

3739

35

35

13

13

13151515

15 15

9

11

11

11

3

L1A- 25,27

L1A- 13 5

911

L1A- 1315 17

L1A- 19

21 23L1A- 29

3331

L1A- 3537 39

41

L1A- 4143 45

L1A- 4749 51

L1A- 5355 57

60" AFF

60" AFF

60" AFF

59

45

L1A- 7

NOTE 2

EQUIPMENT

1103

LEARNING CENTER

1111

LEARNING CENTER

1112

WORKROOM

1104

BROADCAST

1109

OFFICE

1105

CIRCULATION

1101.1

STORAGE

1106

TLT

1104.1

TLT

1107

TLT

1108

STAFF

1110

COMPUTER LAB

1102

MEDIA CENTER-2

1101-2

THIS AREA SERVED BYPANEL: L1B

/1 E2.13

/1 E2.13

/2

E2.1

1

/1

E2.1

4

/1 E2.12

/2 E2.11

/1 E2.12

4E5.02

1E5.03

NOTE 3

NOTE 3

C C C

C C

NOTE 2

NOTE 2

NOTE 5

NOTE 2

C

C C C

C

NOTE 13

1

1

13

13

3

3

5

5

7

7

L1B- 13

L1B- 57

23

23

23

15 15

17

17

17

17

17

17

17

15

21

21

55

1111

13

11

25

25

25

25

57

19

19

1927

31 31 31

29

29

29

29

29

27

27 27

39

33

33

35 35

37

39

37

41

41 41

41

53

53

53

23

55

55

55

55

11

9 9

11

47

47

47 4749

49

49

45

45

45 43 43 43

43

48" AFF FOR WALLMOUNTED PHONE

47

43

23

L1B- 913

L1B- 1517 19

L1B- 2123 25

L1B- 2729 31

L1B- 3335 37

L1B- 39

51 51

51

5151

L1B- 4143 45

L1B- 4749 51

L1B- 5355

L1B- 616563

L1B- 737775

L1B- 798381 87 89

L1B- 859593

7169L1B- 67

L1B- 91

NOTE 4

49

45

57

5959

L1B- 5759

NOTE 2

FINISHED CEILING3#12,1/2IN. FLEX

3#12, 1 / 2 IN. C

INTERIOR VIEW

1 IN. C.

1 IN. C.

MAKE ALL CONNECTIONS AND PROVIDE ALL ITEMS REQUIRED FORCOMPLETE OPERATING SYSTEM AS REQUIRED BY MANUFACTURER

ELECTRICDOORSTRIKE

INTERIOR VIEW

ELECTRICDOORSTRIKE

PUSH TOEXITBUTTONS

REQUESTTO EXITDETECTOR

REQUESTTO EXITDETECTOR

DOORS WITH ELECTRIC DOOR STRIKE

POWER SUPPLYAND CONTROLLER

(TYPICAL)

LOCATE AT RECEPTIONDESK COORDINATEEXACT LOCATION WITHARCHITECT

MOTOR RATEDSWITCH

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

NOT TO SCALE8/7

/2015 3

:27:4

3 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

E2.11

FIRST FLOORPOWER PLAN -BUILDING 1000& 1100

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/8" = 1'-0"E2.11

POWER PLAN - 10002 1/8" = 1'-0"E2.11

POWER PLAN - 11001

(THIS SHEET ONLY)NOTES:8 PROVIDE DOOR INTERCOM SYSTEM AIPHONE JK-1MED MASTER

STATION WITH WIDE ANGLE VIEW, PAN/TILT/ZOOM CONTROL,COLOR MONITOR AND BUILT IN PICTURE MEMORY-PROVIDE WITHMCW-S/A DESK STAND. MASTER STATION SHALL PROVIDE DOORRELEASE, INTERFACE WITH DOOR LOCKING SYSTEM.

9 PROVIDE WEATHER PROOF DOOR SUBSTATION JK-DVF (FLUSHMOUNT) OR JK-DV (SURFACE MOUNT) OUTSIDE OF ENTRY.

10 MAKE CONNECTION TO NEAREST RECEPTACLE CIRCUIT FORPOWER, PROVIDE ALL TRANSFORMERS RACEWAY AND CABLINGREQUIRED FOR COMPLETE OPERATIONAL SYSTEM.

11 MAKE FINAL CONNECTION TO DOOR LOCK ACCORDING TO THEMANUFACTURERS INSTRUCTIONS.THE DOOR IS TO UNLOCKWHEN PUSH BUTTON IS PRESSED SEE DOOR LOCK CONNECTIONDETAIL.

12 PUSH TO EXIT BUTTONS, SEE DOOR LOCK CONNECTIONSDETAIL, THIS SHEET.

13 COORDINATE OUTLET LOCATION ON COLUMN AND CONDUITROUTING WITH ARCHITECTPRIOR TO ROUGH IN.

1 MOUNT IN CABINET FOR MICROWAVE, COORDINATE EXACTOUTLET MOUNTING HEIGHT PRIOR TO ROUGH IN. PROVIDERECESSED SIMPLEX OUTLET.

2 PROVIDE RECESS OUTLET BOXES MOUNTED AT 60" A.F.F. FORCABLING AND POWER FOR WALL MOUNT TELEVISION.

3 MOUNT OUTLETS IN KNEE SPACE OF CABINET, CONCEAL ALLCONDUIT. ROUTE DATA CONDUITS UNDER GROUND TONEAREST WALL, THEN TURN OUT ABOVE ACCESSIBLE CEILING.

4 PROVIDE RECEPTACLE AND DATA OUTLET AT 52" A.F.F. FORKRONOS TIMECLOCK. COORDINATE EXACT MOUNTING LOCATIONWITH ARCHITECT PRIOR TO ROUGH IN.

5 WHERE OUTLET IS LOCATED AT BOOK STACK, OUTLET SHALL BEINSTALLED IN BASE OF BOOK STACK, MOUNTED HORIZONTALLY.COORDINATE STACK LOCATIONS WITH ARCHITECT.

6 PROVIDE OUTLET FOR COUNTERTOP ICE DISPENSER.

7 PROVIDE 4#10, 3/4"C HOMERUN

NOT TO SCALEE2.11

DOOR LOCK CONNECTIONS3

A COORDINATE LOCATIONS OF OUTLETS WITH ARCHITECT, SEEDETAIL. 2/E7.01.

(THIS SHEET ONLY)GENERAL NOTES:

REVISION SCHEDULE

DATE DESCRIPTION

x1

4 4 4 4

4 4 4 4

1

4

4

4

4

x1

x1x1

x1

x1

x1

x4

x4

x4

x4

x1

x1

x1

x1

x1

x1x1

x1

WP

WPWP

WP

HD HD

WW

W

AV

J

SM

M

AV

C

HDHD

C

MSM

SM

SM

ELEC

1208

STOR

1211

STOR

1210

STORAGE

1204

STORAGE

1205

CHASE

1213.1

GYM

1201

OFFICE

1207

STOR

1206

LOBBY

1200

JAN

1213

MEN

1212

MUSIC

1209

CORR

1200.1

WOMEN

1214

T-1A

L1A L1AL1A

H1A

/1 E2.11

/2 E2.11

/1

E2.1

1 /2 E2.11

NOTE 1

NOTE 2

NOTE 4

NOTE 3

NOTE 1

NOTE 5

59

59

59

59

59

59

79

81

8365

65

63

61

61

61 61

63

63

6365

6563

67676767

69

6969

69 75 77

71 73

8585

85

858787

8989

87

89

87

91

91

91

91

93

9393

9395101

95

95

9191

97

97

97

97

97 87

87

89 L1A- 5961 63

L1A- 6567 69

L1A- 7173

L1A- 7577

L1A- 7981 83

103

L1A- 103

L1A- 8587 89

L1A- 9193 95

L1A- 97

ALL CIRCUITS SHALL BEROUTED TO PANEL: LA

NOTE 6

105

105

9999 101L1A- 97

65

PROJECTOR

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

1/8" = 1'-0"8/7

/2015 3

:27:4

7 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

E2.12

FIRST FLOORPOWER PLAN -BUILDING 1200

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/8" = 1'-0"E2.12

POWER PLAN - 12001

1 MOUNT BOX FOR AUDIO VISUAL CONNECTIONS AT 48" AFF.SEE DETAIL FOR BOX SIZE, CONFIGURATION AND CONDUITREQUIREMENTS.

2 SINGLE GANG JUNCTION BOX WITH 1" C TURNED OUTABOVE CEILING FOR PROJECTOR CONTROLLER.

3 POWER FOR PROJECTOR AT 96", COORDINATE LOCATIONWITH ARCHITECT PRIOR TO ROUGH IN.

4 PROVIDE 3 POSITION, CENTER OFF SWITCH COMPATIBLEWITH PROJECTOR SCREEN MOTOR / MOTORIZED DIVIDERCURTAIN. MAKE ALL CONNECTIONS REQUIRED FORCOMPLETE OPERABLE SYSTEM.

5 MOTORIZED DIVIDER CURTAIN HUNG FROM STRUCTURE.COORDINATE EXACT LOCATION PRIOR TO ROUGH IN.PROVIDE 3#10, 1/2"C HOMERUN.

6 PROJECTOR SCREEN MOTOR. COORDINATE EXACTLOCATION WITH OWNER. PROVIDE 3#10, 1/2"C. HOMERUN.

(THIS SHEET ONLY)NOTES:

(THIS SHEET ONLY)GENERAL NOTES:A COORDINATE LOCATIONS OF OUTLETS WITH ARCHITECT, SEE

DETAIL. 2/E7.01.

REVISION SCHEDULE

DATE DESCRIPTION

x1

x1

x1

x1x1

DN

WP

W W W

WP

WP

WP

WP

WP

C

WP

WP

CAFETERIA

1304

ELEC

1301

CORR

1300

JAN

1306

TRASH VEST

1305

OFFICE

1314

CHEM STOR

1313

SERVERY

1307

ELECTRICAL

1318

TLT

1317

DISH WASH

1308

COOLER/FREEZER

1312

RECEIVING

1315

KITCHEN

1311

DRY STORAGE

1310

TABLE/CHAIR STORAGE

1309

LOCKER

1316

SCRUBBER STORAGE

1302

MDF

1303SUPPLIES

1304.1

MECHANICAL-1

1319-1

MECHANICAL-2

1319-2

CORRIDOR-2

1100-2

MSB

H1K L1KL1KT-1K

H1M

MSB

T-1B

L1B

L1B

L1B

H1B

THIS AREA SERVED BYPANEL: L1B

THIS AREA SERVED BYPANEL: L1K

THIS AREA SERVED BYPANEL: L1B

THIS AREA SERVED BYPANEL: L1K

1E5.01

/2 E2.11

/1

E2.1

4

/1 E2.11 /2

E2.1

1

/1

E2.1

1

4E5.03

T-EM

L1K-EM

ECB L1K-EM

NLKELKWP

97

97 97 97 97 97

101

99 101 101

101

101

107105103109

109113

115

111

111

109

109

L1B- 97

107105L1B- 103

L1B- 109111

3

3

3

3

3

5

5

5

5

5

7

7

7

3

L1K- 37

5

10199

OUTLET SHALL BELOCATED AT IRRIGATIONCONTROL PANEL. VERIFYEXACT LOCATION PRIORTO ROUGH IN.

MTS

MAKE FINAL CONNECTION TO UNITACCORDING TO MANUFACTURERSINSTRUCTIONS.

L1K- 9

5

30A/2P

5

5

3#10 1/2"C

COUNTERTOP ICE DISPENSER

L1B- 117,119

L1B- 121,123

L1B- 113115

TRASHCOMPACTOR

82

L1B- 82

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

1/8" = 1'-0"8/7

/2015 3

:27:5

0 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

E2.13

FIRST FLOORPOWER PLAN -BUILDING 1300

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/8" = 1'-0"E2.13

POWER PLAN - 13001

A COORDINATE LOCATIONS OF OUTLETS WITH ARCHITECT, SEEDETAIL. 2/E7.01.

(THIS SHEET ONLY)GENERAL NOTES:

REVISION SCHEDULE

DATE DESCRIPTION

2

2

1

1

C C

C

WP

AV

CC

CC

CC

AV

WP

WP

J

J

J

J

J

W W W

C

C

AV

C

C

C

C

JSTORAGE

1429

OFFICE

1407

TLT

1404.1

OFFICE

1408OFFICE

1409

KILN

1413

STAIR

2402-14

STOR

1405.1

STORAGE

1412

JAN

1420

DATA

1418

ELEC

1416

OFFICE

1414

OFFICE

1410

CONF

1433

ELL CLASSROOM

1430

WORKROOM

1434

RESOURCE ROOM

1421ART

1411

ELEVATOR EQUIPMENT

1415

ELEV

1417

WAITING

1405

CORR

1405.2

STAIR

1401

CORRIDOR

1400

HEAD CUSTODIAN

1402

JAN

1403

TLT

1431

TLT

1432

SPANISH

1602

HALL

1424

TLT

1424.2

TLT

1424.1

1ST GRADE CLASSROOM

1426

1ST GRADE CLASSROOM

1422

HALL

1425

TLT

1425.2

TLT

1425.1

1ST GRADE CLASSROOM

1427

1ST GRADE CLASSROOM

1423

H1CL1C

L1CT-1C1

L1C

/1 E2.11

/1 E2.13

/1

E2.1

3

/1 E2.15

/1 E2.15

/2 E2.15 /2 E2.15

2E5.03

3E5.02

C

C

C

C

C

TV

NOTE 1

NOTE 2

TV

NOTE 2C

1515

15

1315

151E5.02

1E5.02

L1C- 1921 23

L1C- 3133 35

L1C- 2527 29

L1C- 3739 41

L1C- 4345 47

49 49 53

49

49

51

51

49

51

L1C- 4951

59

59

59

59

61

61

61

57

57

57L1C- 5759

63 65 67

L1C- 6365 67

NOTE 3

NOTE 3

69

69

69

71

71

71

71

73

73

73

71

71

71

L1C- 6971 73

69 69

57

75

75

75

L1C- 75

77

77

77

77

79

79

79

79

7977

83

83

8381

81

81

81

L1C- 8183 85

85

85

85 87

87

87

8789

89

89

89

89

89

87 89L1C- 85

91 93

91

93

93

91

L1C- 9193

9999

95

99 95 95

95

959795

95L1C- 9599 99

101

101

101

101

105105

105

105

103

103

103

L1C- 101

15

73

8E5.03

L1C- 13

NOTE 2

105

103

95

81

91

49

61

75

NOTE 4

C

11

11

9

7

11

L1C- 79 11

L1C- 78,80,82

97

73

53

53

T-1C2

ECB-KILN

NOTE 5

ECB-KILN- 1,3

MSB- 14

ELEV. PIT LIGHT,RECEPTACLEAND SUMP PUMPCIRCUITSSEE 6/E5.03

L1C- 108110 112

L1C- 114,116

82

L1B- 82

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

1/8" = 1'-0"8/7

/2015 3

:27:5

4 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

E2.14

FIRST FLOORPOWER PLAN -BUILDING 1400

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/8" = 1'-0"E2.14

POWER PLAN - 14001

1. MOUNT IN CABINET FOR MICROWAVE, COORDINATEEXACT OUTLET MOUNTING HEIGHT PRIOR TO ROUGH IN.PROVIDE RECESSED SIMPLEX OUTLET.

2. PROVIDE RECESS OUTLET BOXES MOUNTED AT 60" A.F.F.FOR CABLING AND POWER FOR WALL MOUNT TELEVISION.

3. MOUNT BOX FOR AUDIO VISUAL CONNECTIONS AT 48" AFF.SEE DETAIL FOR BOX SIZE AND CONFIGURATION.

4. PROVIDE NEMA 15-50 THREE-PHASE PLUG. PROVIDE4#6, #10G, 1"C.

5. PROVIDE 60A/2P DISCONNECT WITH 4#6, #10G, 1"C HOMERUNTO ECB-KILN. MAKE FINAL CONNECTION TO EXISTING RELOCATEDKILN.

(THIS SHEET ONLY)NOTES:

A COORDINATE LOCATIONS OF OUTLETS WITH ARCHITECT, SEEDETAIL. 2/E7.01.

(THIS SHEET ONLY)GENERAL NOTES:

REVISION SCHEDULE

DATE DESCRIPTION

x4

x1

x1

x1

x1

x1

x1

x1

x4

x1

WP

J

J J

J

J

J

J

J

WP

J

J

J

J

J

J

J

J J

J

CORR

1500

WORKROOM

1434

STORAGE

1514

HALL

1504

STAIR

2402-65

HALL

1510

TLT

1510.2

TLT

1510.1

KINDERGARTEN CLASSROOM

1508

KINDERGARTEN CLASSROOM

1512

HALL

1509

TLT

1509.2

TLT

1509.1

KINDERGARTEN CLASSROOM

1507

KINDERGARTEN CLASSROOM

1511

HALL

1503

TLT

1503.2

TLT

1503.1

KINDERGARTEN CLASSROOM

1501

KINDERGARTEN CLASSROOM

1505

TLT

1504.1

1ST GRADE INCLUSION CLASSROOM

1502

TLT

1504.2

KINDERGARTEN INCLUSION CLASSROOM

1506

L1C1

THIS AREA SERVED BYPANEL: L1C1

THIS AREA SERVED BYPANEL: L1C

THIS AREA SERVED BYPANEL: L1C1

THIS AREA SERVED BYPANEL: L1C

/1 E2.14

/1 E2.14

2E5.02

1E5.02

1E5.02

1E5.02

L1C- 2022 24

L1C1- 3133 35

L1C- 2628 30

L1C1- 3739 41

L1C1- 13 5

L1C1- 79 11

L1C1- 1315 17

L1C1- 1921 23

L1C1- 27

27

27

27

27

25

25

25

25

L1C1- 2527

CORR

1600

STORAGE

1614

STAIR

2402-72

HALL

1604

TLT

1604.2

TLT

1604.1

2ND GRADE CLASSROOM

1606

SPANISH

1602

HALL

1610

TLT

1610.2

TLT

1610.1

2ND GRADE CLASSROOM

1612

2ND GRADE CLASSROOM

1608

HALL

1611

TLT

1611.2

TLT

1611.1

2ND GRADE CLASSROOM

1613

2ND GRADE CLASSROOM

1609

SID/PID CLASSROOM

1607

PSI CLASSROOM

1601

TLT

1603.2STOR.

1605

TLT

1603.1

DRESSING

1603

THIS AREA SERVED BYPANEL: L1C2

THIS AREA SERVED BYPANEL: L1C

THIS AREA SERVED BYPANEL: L1C2

THIS AREA SERVED BYPANEL: L1C

L1C2

/1 E2.14 /1 E2.14

1E5.02

1E5.02

1E5.02

5E5.02

L1C- 107109 111

L1C2- 24 6

L1C- 810 12

L1C2- 810 12

L1C- 14,16 L1C- 18

L1C2- 13 5

L1C2- 79 11

L1C2- 1315 17

L1C2- 1921 23

25

25

25

25

27

27

27

27

27

L1C2- 2527

PROVIDE 4#10, 1/2"C

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

1/8" = 1'-0"8/7

/2015 3

:27:5

9 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

E2.15

FIRST FLOORPOWER PLAN -BUILDING 1500& 1600

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/8" = 1'-0"E2.15

POWER PLAN - 15001 1/8" = 1'-0"E2.15

POWER PLAN - 16002

A COORDINATE LOCATIONS OF OUTLETS WITH ARCHITECT, SEEDETAIL. 2/E7.01.

(THIS SHEET ONLY)GENERAL NOTES:

REVISION SCHEDULE

DATE DESCRIPTION

x1

x1

x1

x1

C CA

V

C C

C

C

AV

AV

JJ

JJ

W W W

C

C

C

C

C

AV

J

J

J

J

AV

C

RESOURCE ROOM-1

2405-1

RESOURCE ROOM-1

2401-1

STAIR

1120

STORAGE-1

2427-1

STORAGE-1

2407-1

STORAGE

2410

JAN-1

2420-1 DATA

2419

ELEC-1

2418-1

CONF-1

2433-1

DATA CONF ROOM-1

2429-1

WORKROOM-1

2430-1

RESOURCE ROOM-1

2417-1

STOR-1

2411-1

CORRIDOR-1

2402-1

OFFICE-1

2416-1

OFFICE-1

2414-1

STOR-1

2412-1

SCIENCE CLASSROOM

2409

GIFTED/STEM LAB

2408

CORRIDOR

2400

STAIR-1

2406-1

OFFICE-1

2415-1

ELEV-1

2413-1

TLT-1

2431-1

TLT-1

2432-1

3RD GRADE CLASSROOM

2602

HALL-1

2423-1

TLT-1

2423.2-1

3RD GRADE CLASSROOM

2421

3RD GRADE CLASSROOM-1

2425-1

TLT-1

2423.1-1

HALL-1

2424-1

TLT-1

2424.2-14TH GRADE CLASSROOM

2422

4TH GRADE CLASSROOM-1

2426-1

TLT-1

2424.1-1

4TH GRADE INCULSION CLASSROOM-1

2502-1

3RD GRADE INCLUSION CLASSROOM

2601

TLT

2403

TLT

2404

H2C

L2C

L2C

T-2C

L2C

/1 E2.22

/1 E2.22

/2 E2.22 /2 E2.22

10E5.03

9E5.03

C

C

C

C

C

TV

NOTE 1

NOTE 2

NOTE 3

NOTE 3

NOTE 3

LOCATE OUTLETABOVE GOGGLECABINET.

1E5.02

10E5.03

1E5.02

C

NOTE 2

7

7

9

11

11

11 9

11

11

11

23

23

23

17 15

1717

13

15

17

13 1721

21

21

21

21

19

1919

19

23

23

L2C- 3739 41

L2C- 4345 47

L2C- 2527 29

L2C- 3133 35

75

75 75

75

77

77

77

77

73

65

65

65

6565

61

61

61

61

61

61

7373

63

6363

63

73

57

5759

59

55

515351

49

57

57

57

73

85

8587

87

91 93 95

92 83 83

81

79

83

81

79

7981

83

L2C- 9799 101

L2C- 103105 107

89

89

89

89

87

8787

L2C- 115117 119

L2C- 109111 113

73

17

L2C- 79 11

L2C- 1315 17

L2C- 1921 23

L2C- 6163 65

L2C- 9193 95

L2C- 8587 89

L2C- 737775

8381L2C- 79

L2C- 5757 59

L2C- 4951 53

C

NOTE 369

69

69

71 71

71

71

71

676767

67

L2C- 92

L2C- 6769 71

71

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

1/8" = 1'-0"8/7

/2015 3

:28:0

3 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

E2.21

SECOND FLOORPOWER PLAN -BUILDING 2400

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/8" = 1'-0"E2.21

POWER PLAN - 24001

1. MOUNT IN CABINET FOR MICROWAVE, COORDINATEEXACT OUTLET MOUNTING HEIGHT PRIOR TO ROUGH IN.PROVIDE RECESSED SIMPLEX OUTLET.

2. PROVIDE RECESS OUTLET BOXES MOUNTED AT 60" A.F.F.FOR CABLING AND POWER FOR WALL MOUNT TELEVISION.

3. MOUNT BOX FOR AUDIO VISUAL CONNECTIONS AT 48" AFF.SEE DETAIL FOR BOX SIZE AND CONFIGURATION.

(THIS SHEET ONLY)NOTES:

A COORDINATE LOCATIONS OF OUTLETS WITH ARCHITECT, SEEDETAIL. 2/E7.01.

(THIS SHEET ONLY)GENERAL NOTES:

REVISION SCHEDULE

DATE DESCRIPTION

x1

x1

x4

x1x1

x1

x1

x1

x1

x1

x1

x4

x4

x1

x1

x4

J

J J

J

J

J

J

J

J

J

J

J

J

J

J

J

CORRIDOR

2500

STAIR

1131

STORAGE-1

2514-1

HALL-1

2510-1

TLT-1

2510.2-1

5TH GRADE CLASSROOM

2512

5TH GRADE CLASSROOM-1

2508-1

HALL-1

2509-1

TLT-1

2509.2-1

5TH GRADE CLASSROOM

2511

5TH GRADE CLASSROOM-1

2507-1

HALL-1

2503-1

TLT-1

2503.2-1

5TH GRADE CLASSROOM

2505

4TH GRADE CLASSROOM-1

2501-1

HALL-1

2504-1

TLT-1

2504.2-1

5TH GRADE INCLUSION CLASSROOM

2506

4TH GRADE INCULSION CLASSROOM-1

2502-1

TLT-1

2504.1-1

/1 E2.21

/1 E2.21

L2C1

TLT-2

2509.1-2

TLT-2

2510.1-2

TLT-2

2503.1-2

1E5.02

1E5.02

1E5.02

2E5.02

L2C- 5052 54

L2C- 5658 60

L2C1- 27

L2C1- 810 12

L2C1- 24 6

L2C1- 1315 17L2C1- 1

3 5

27

L2C1- 1921 23

L2C1- 79 11

25

25

25

25

2727

27

L2C1- 2527

THIS AREA SERVED BYPANEL: L2C1

THIS AREA SERVED BYPANEL: L2C

THIS AREA SERVED BYPANEL: L2C1

THIS AREA SERVED BYPANEL: L2C

STAIR

1135

CORRIDOR-1

2600-1

STORAGE

2614

HALL-1

2604-1

TLT-1

2604.2-1

3RD GRADE CLASSROOM

2602

3RD GRADE CLASSROOM-1

2606-1

TLT-1

2604.1-1

HALL-1

2610-1

TLT-1

2610.2-1

GIFTED CLASSROOM

2608

GIFTED CLASSROOM

2612

TLT-1

2610.1-1

HALL-1

2609-1

TLT-1

2609.2-1

GIFTED CLASSROOM

2607

GIFTED CLASSROOM-1

2611-1

TLT-1

2609.1-1

HALL-1

2603-1

TLT-1

2603.2-1

3RD GRADE INCLUSION CLASSROOM

2601

TLT-1

2603.1-1

ESL CLASSROOM-1

2605-1

L2C2

/1 E2.21 /1 E2.21

1E5.02

2E5.02

1E5.02

1E5.02

L2C- 4446 48

L2C- 3840 42

L2C2- 24 6 L2C2- 8

10 12

L2C2- 13 5

L2C2- 1315 17

L2C2- 79 11

L2C2- 1921 23

25

25

25

25

27

27

27

27

L2C2- 27

L2C2- 2527

THIS AREA SERVED BYPANEL: L2C2

THIS AREA SERVED BYPANEL: L2C

THIS AREA SERVED BYPANEL: L2C2

THIS AREA SERVED BYPANEL: L2C

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

1/8" = 1'-0"8/7

/2015 3

:28:0

8 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

E2.22

SECOND FLOORPOWER PLAN -BUILDING 2500& 2600

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/8" = 1'-0"E2.22

POWER PLAN - 25001 1/8" = 1'-0"E2.22

POWER PLAN - 26002

A COORDINATE LOCATIONS OF OUTLETS WITH ARCHITECT, SEEDETAIL. 2/E7.01.

(THIS SHEET ONLY)GENERAL NOTES:

REVISION SCHEDULE

DATE DESCRIPTION

x1

x1

x1

x1

W/D

X 6' - 0"21' - 4"

X 11' - 4"13' - 4"

X 22' - 8"15' - 4"

X 21' - 4"18' - 8"

X 28' - 8"38' - 0"

X 26' - 8"46' - 8"

X 24' - 8"19' - 6"

X 8' - 8"6' - 0"

X 8' - 8"12' - 0"

X 9' - 4"7' - 4"X 8' - 8"10' - 8"

X 7' - 4"8' - 0"

FE-K FEB

FEC

FEC

40°

40°

40°

40°

D

D

D

D

DD

2148

2148

RR D

R RD

21362136

2136

2136

2136

2148

21482148

2148 2148

2148

21482148

2148 2148

D

D

CH

EM

D2

FS

D1

2148

2148

2148

2148

2148

2148

2148

2148 2148

2148

2148

2148

2148

D

D

W/DE1

E15

E14b

E17

E23E23

E25

E26

E62

E26

E24

E31

E61

E27 E28

E62

E61

E19

E51

E22

E22

E21

E46E45

E14

E44

E44b

E46E45

E25

COOLER

FREEZER

EW2

E54

E55

E59

E49

E33

WP

WP

JJ

SS

J

JJ

J

JJ

J

C

CHEM STOR

1313

OFFICE

1314

RECEIVING

1315

LOCKER

1316

TLT

1317

KITCHEN

1311

SERVERY

1307

TRASH VEST

1305

TABLE/CHAIR STORAGE

1309

JAN

1306

DISH WASH

1308

DRY STORAGE

1310

COOLER/FREEZER

1312

L1K- 1

NOTE 1

NOTE 2

NOTE 4

NOTE 3

6

4

2

L1K- 24 6

L1K- 12,14

H1K- 2,4,6

8

10

L1K- 810

H1K- 8,10,12

L1K- 16L1K- 18

L1K- 20

L1K- 2420

24

26 22

26

22

@24"

@24"

@48" @48"

@48"

@48"

@48"@48"

@48"

@48"

@48"

@48"

28

28

NOTE 25

@48" @48"30 32

L1K- 3032

36

34

38

38

38

38

38

L1K- 3438

36

MSB- 13

NOTE 15

NOTE 15

NOTE 15

NOTE 15

NOTE 5

NOTE 6

NOTE 7

NOTE 10

NOTE 10

NOTE 10

NOTE 10

NOTE 9

EW5

EW2

EW7

7#12, 1"C

7#12, 1"C

TO CONDENSINGSYSTEM CONTROLPANEL EW6

EW4

NOTE 10

L1K-EM- 6

L1K-EM- 6

NOTE 9

EW1

L1K-EM- 4

L1K-EM- 1,3,5

NOTE 8

NOTE 8

NOTE 11 NOTE 12 NOTE 11 NOTE 12

NOTE 13

NOTE 14NOTE 16

NOTE 15

NOTE 15

NOTE 15

NOTE 17

L1K- 35,37,39

NOTE 18

NOTE 18L1K- 46,48 L1K- 52,54

L1K-EM- 2

L1K-EM- 7

7 9

9

L1K- 58,60 L1K- 62,64L1K- 66

68

68

66

NOTE 20

H1K- 26,28,30

H1K- 20,22,24

NOTE 2

H1K- 14,16,18

NOTE 19

NOTE 21

NOTE 22

NOTE 23

NOTE 2

NOTE 24

H1K- 32,34,36

70

7070

70 70

70

70

70

L1K- 70

76

76

76

76

72

72

72

74

74

74

74

L1K- 727674

NOTE 15

NOTE 15

NOTE 15

NOTE 15

NOTE 15

NOTE 15

NOTE 15

NOTE 15

NOTE 13

NOTE 13

NOTE 14

NOTE 14

@48" 78

L1K- 78

NOTE 26

L1K- 80,82

4#10

L1K- 84

38

H1K T-1K L1K L1K

6 6

DESIGN IS BASED ON SINGLE CIRCUIT FEED TO FREEZER AND DUAL CIRCUITFEED TO COOLER. VERIFY CONNECTIONS FOR UNITS ACTUALLY PROVIDED ANDMODIFY ACCORDINGLY.

ALL CONDUITS ENTERING REFRIGERATED SPACES SHALL BE RGS. PROVIDESEALING FITTING AT ALL ENTRY POINTS AND SEAL TO PREVENT THEENTRANCE OF MOISTURE.

PROVIDE ROUGH-IN FOR CONTROL WIRING AS REQUIRED BY EQUIPMENTINSTALLATION DRAWINGS.

PANELSERVINGFREEZER/COOLER.

LOCATE WITHIN SIGHT OFINDOOR COIL. COORDINATESWITCH LOCATION WITHEQUIPMENT INSTALLER,TYP.

FREEZER

COILCONDENSERCONTROLPANEL

CONDENSERCONTROLPANEL

COIL

COOLER

(FREEZER COOLER CONNECTIONS DETAIL )NOTES:S

SWP

S

SWP

120V CIRCUIT

KITCHEN HOOD FIRE SUPPRESSIONNORMALLY OPEN CONTACTS IN

SYSTEM THAT CLOSE UPONACTIVATION

120V CIRCUIT

KITCHEN HOOD FIRE SUPPRESSIONNORMALLY OPEN CONTACTS IN

SYSTEM THAT CLOSE UPONACTIVATION

SHUNT TRIP COILS

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

As indicated9/1

8/2

015 9

:25:0

6 A

MC

:\U

sers

\gcla

rk\D

eskto

p\G

RE

G'S

JO

BS

\20141017 E

LE

C-G

Cla

rk -

9-9

-2015.r

vt

E5.01

LARGE SCALEKITCHEN -ELECTRICAL

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/4" = 1'-0"E5.01

LARGE SCALE - KITCHEN POWER & SYSTEMS1

KITCHEN EQUIPMENT RATINGS AND CONNECTIONS

ITEM VOLT PH HP MCA MOCP DISCONNECT WIRE SIZE

ITEM E1 - FLY FAN 120 1 3/4 20 30A/2P 3#12, 1/2"C

ITEM E14 - POWER SOAK 208 1 ECB 3#12, 1/2"C

ITEM E15 - DISPOSER 480 3 2 20 ECB 3#12, 1/2"C

ITEM E19 - VCM 480 3 5 20 NEMA L21-30P (REC) 3#12, 1/2"C

ITEM E23 - HOLD/PROOF CABINET 120 1 3/4 20 MOTOR RATED SWITCH 3#10, 1/2"C

ITEM E44 - UDS 208 3 70 100A/3P 4#4, #8G, 1 1/4"C

ITEM E44B - UDS 480 3 350 400A/3P 4#500, #2G, 3 1/2"C

ITEM E49 - SINK HEATER 480 3 20 ECB 4#12, 1/2"C

ITEM E54 - BOOSTER HEATER 480 3 30 ECB 4#10, 1/2"C

ITEM E55 - DISHWASHER 480 3 40 ECB 3#8, #10G, 1"C

ITEM E59 - DISPOSER 480 3 20 ECB 4#12, 1/2"C

ITEM E61 - UTILITY WALL 208 1 125 200A/2P 3#3, #8G, 1 1/2"C

ITEM EW1 - FREEZER CONDENSER 120 1 5.4 20 30A/1P/3R 3#12, 1/2"C

ITEM EW2 - COOLER CONDENSER 120 1 5.4 20 30A/1P/3R 3#12, 1/2"C

ITEM EW4 - COOLER LTS, HTR 120 1 5.4 20 30A/1P/3R 3#12, 1/2"C

ITEM EW5 - FREEZER 120 1 5.4 20 30A/1P/3R 3#12, 1/2"C

ITEM EW7 - CONDENSING UNIT 208 3 51.7 70 100A/3P/3R 3#4, #8G, 1 1/4"C

NOT TO SCALEE5.01

2 FREEZER/COOLER CONNECTIONSNOT TO SCALEE5.01

4 HOOD FIRE SUPPRESSOIN INTERLOCKS

(THIS SHEET ONLY)NOTES:

14 CONNECT CORD AND PLUG SET OR PREWIRED FLEXIBLE CONDUIT PROVIDED WITH UDS TO EQUIPMENT TERMINALS

FOR EACH PIECE OF KITCHEN EQUIPMENT. COORDINATEWITH UDS BEING INSTALLED.

15 CONNECT UDS ELECTRICAL FIELD JOINTS BY BOLTING BUS BARS AND/OR WIRING TOGETHER. CONNECT ALL

CONTROL WIRING FIELD JOINT MOLDED CONNECTORS.

16 INSTALL 120 VOLT CIRCUIT FROM FIRE EXTINGUISHINGSYSTEM TO FUEL SHUT-OFF TERMINAL BLOCK IN UDS.COORDINATE EXACT CONNECTION POINTS WITH UDSBEING INSTALLED.

17 PROVIDE 2-WIRE CIRCUIT FROM UDS RISER TO REMOTE GAS SOLENOID VALVE. COORDINATE EXACT CONNECTION

POINTS AND WIRE SIZE WITH UDS BEING INSTALLED.

18 PROVIDE 1 IN. C. EMPTY WITH PULLSTRING FOR POINT OFSALE CABLING.

19 PROVIDE FLUSH 30A/3P ECB WITH STAINLESS STEELCOVER AND DOUBLE GASKET.

20 PROVIDE FLUSH 40A/3P ECB WITH STAINLESS STEELCOVER AND DOUBLE GASKET.

21 PROVIDE SERVICE OUT OF WALL AT 16" A.F.F. CONNECTTO TERMINALS AT 12" A.F.F.

22 PROVIDE SERVICE OUT OF WALL AT 8" A.F.F. CONNECT TOTERMINALS ON BOOSTER HEATER AT 4" A.F.F..

23 PROVIDE SERVICE OUT OF WALL AT 64" A.F.F. CONNECTTO TERMINALS ON DISSHWASHER AT 64" A.F.F..

24 PROVIDE SERVICE OUT OF WALL AT 16" A.F.F., EXTEND TOCONTROL PANEL AND SOLENOID VALVE AND CONNECT TOTERMINALS ON DISPOSER.

25 PROVIDE SERVICE OUT OF WALL AT 56" A.F.F., CONNECTTO TERMINALS ON ICE MAKER AT 74" A.F.F...

26 PROVIDE RECEPTACLE AND DATA OUTLET AT 52" A.F.F.FOR KRONOS TIMECLOCK.

1 PROVIDE FLUSH 30A/2P ECB WITH STAINLESS STEELCOVER AND DOUBLE GASKET.

2 PROVIDE FLUSH 20A/3P ECB WITH STAINLESS STEELCOVER AND DOUBLE GASKET.

3 PROVIDE SERVICE AT 16" A.F.F. FOR POWER SOAKER.MAKE FINAL CONNECECTION ACCORDING TOMANUFACTURERS REQUIREMENT.

4 MAKE ALL CONNECTIONS AS REQUIRED TO DISPOSERCONTROL PANEL, DISPOSER, AND SOLENOID VALVE.MOUNT CONTROL PANEL UNDERNEATH FRONT OF PREP.TABLE PER MANUFACTURES RECOMMENDATIONS.COORDINATE EXACT REQUIREMENTS

5 DOORBELL PUSH BUTTON. MOUNT AT 42 IN. A.F.F.PROVIDE SQUARE D MODEL KR1RH13 WITH STAINLESSSTELL FACEPLATE.

6 DOOR BELL, EDWARDS MODEL 340-4N5 120 VOLT GRAY BELL IN #348 EDWARDS BACKBOX. MOUNT AT 80 IN. A.F.F

7 PROVIDE SERVICE OUT OF WALL FOR FLY FAN. COORDINATE EXACT MOUNTING HEIGHT. INTERLOCK FAN

WITH LIMIT SWITCH PROVIDED WITH UNIT SO THAT FAN WILL TURN ON WHEN DOOR IS OPEN AND TURN OFF WHEN

DOOR IS CLOSED. LOCATE 30A/2P DISCONNECT ABOVEACCESSIBLE CEILING.

8 PROVIDE PASS & SEYMORE PS60SS-NON FUSIBLE, NONMETALLIC DISCONNECT. MAKE ALL FINAL CONNECTIONSTO EQUIPMENT.

9 MAKE CONNECTION TO FREEZER/COOLER LIGHTS ANDDOOR HEATERS AS REQUIRED BY UNIT MANUFACTURER.

10 EYS SEAL OFF FITTING.

11 MOUNT OUTLET ON WALL ABOVE OPENING.(AT 88" A.F.F.)COORDINATE EXACT LOCATION. PROVIDE 3#10.

12 MOUNT OUTLET ON WALL ABOVE OPENING (AT 88" A.F.F.).COORDINATE EXACT LOCATION.

13 MAKE FINAL CONNECTION TO UDS/UTILITY WALL.COORDINATE EXACT ELECTRICAL REQUIREMENTS WITHEQUIPMENT BEING INSTALLED.

F ALL EXPOSED CONDUITS SHALL BE GALVANIZED RIGIDSTEEL.

G COORDINATE EXACT LOCATIONS OF WALK IN COOLER &FREEZER COMPRESSOR LOCATIONS WITH ARCHITECT.

H PROVIDE CORD AND PLUG FOR EACH PIECE OF KITCHENEQUIPMENT LOCATED BENEATH HOOD.

I OUTLETS IN KITCHEN LOW WALLS SHALL BE MOUNTEDHORIZONTAL.

J INTERLOCK RANGE HOOD FIRE SUPPRESSION SYSTEMWITH GAS SOLENOID VALVE AND SHUNT TRIPBREAKERS SERVING EQUIPMENT UNDER THE HOOD,SUCH THAT UPON SYSTEM ACTIVATION ALL POWER ISSHUT OFF. RANGE HOOD EXHAUST FAN SHALL REMAINON AND MAKE-UP AIR SHALL BE SHUT OFF. ALSOINTERLOCK WITH FIRE ALARM SYSTEM SUCH THAT AGENERAL ALARM IS SOUNDED UPON SYSTEMACTIVATION.

A ALL EXPOSED OUTLETS IN KITCHEN AND SERVING AREASHALL BE CAST METAL AND WATER PROOF.

B ALL FLEXIBLE CONDUIT SHALL BE WATERPROOF.

C WHERE KITCHEN EQUIPMENT SHOP DRAWINGS CALLFOR DIRECT CONNECTION AND A RECEPTACLE ISSHOWN ON THE DRAWING, PROVIDE RECEPTACLE,PLUG, AND CORDSET.

D PROVIDE EYS SEAL OFF FITTINGS AT ALL FREEZER ANDCOOLER PENETRATIONS.

E BEFORE ROUGHING IN ANY OUTLETS OR ORDERING ANYRECEPTACLES, PLUGS, CORD SETS, DISCONNECTS, ORANY ITEMS NECESSARY FOR THE CONNECTION OFKITCHEN EQUIPMENT. THE CONTRACTOR SHALLCONSULT THE SHOP DRAWINGS FOR THE EQUIPMENTACTUALLY BEING FURNISHED (UNDER THE CONTRACTOR BY THE OWNER) FOR THE PROJECT AND SHALLPROVIDE AND INSTALL DEVICES. CIRCUITS AND ANYOTHER APPURTENANCES COMPATIBLE WITH THEEQUIPMENT FURNISHED SHALL BE PROVIDED AT NOCOST TO THE OWNER.

(THIS SHEET ONLY)GENERAL NOTES:

D ALL KITCHEN ELECTRICAL REQUIREMENTS SHALL BEVERIFIED WITH EQUIPMENT PURCHASED AND INSTALLEDPRIOR TO ROUGH IN OF ANY OUTLET.

E ALL 5-15R AND 5-20R RECEPTACLES SHALL BE GFCI TYPE.

A REFER TO SECTION 260120 FOR THE COORDINATIONAFFIDAVIT THAT MUST BE SUBMITTED AND APPROVEDBEFORE MATERIALS MAY BE ORDERED.

B THE DESIGN IS BASED ON SINGLE POINT CONNECTIONS TOALL EQUIPMENT, UNLESS NOTED OTHERWISE.

C DISCONNECTS ARE SHOWN AS 30A/3P/3R ETC. IF ARECEPTACLE IS INDICATED, COORDINATE NEMACONFIGURATION WITH EQUIPMENT INSTALLED.

SCHEDULE NOTES: (THIS SHEET ONLY)

REVISION SCHEDULE

DATE DESCRIPTION

9-18-2015 Addendum No. 6

6

6

6

6

AV

C

C

C

C

C

AV

C

X 26' - 8"28' - 8"

AV

C

AV

C

AV

AV

C

C

C

C

CC

C

C

C

C

C

C

AV

AV

C

1ST GRADE INCLUSION CLASSROOM

1502

KINDERGARTEN INCLUSION CLASSROOM

1506

TLT

1504.1

HALL

1504TLT

1504.2

NOTE 1

NOTE 1

PANEL - ØAØB ØC

ØA

ØB

ØA ØA

ØA

ØC

ØA

ØC

ØAØA

ØB

ØC

ØA

ØB

ØC

ØB

ØB

ØA

PANEL - ØAØB ØC

HOMERUN DIFFERENTIATION LINE

ØC

ØA

ØA

ØA

ØB

ØC

ØA

ØA

ØC

ELL CLASSROOM

1430

C

ØB

ØB

ØAØA ØA

ØC

ØC

ØC

PANEL - ØAØB ØC

NOTE 1

ØA

ØA

ØA

ØB

ØA

ØC

COMPUTER LAB

1102

NOTE 1

ØA1

ØB1

ØC1

PANEL-ØA1,ØB1, ØC1

ØA1

ØA1

ØA2 ØC2 ØB3

ØB2

PANEL-ØA2,ØB2, ØC2

ØC3

ØC6

ØC6

ØC6

ØC6

ØC6

PANEL-ØA6,ØB6, ØC6

ØC5ØB5ØC4

PANEL-ØA4,ØB4, ØC4 PANEL-ØA5,ØB5, ØC5

PROJECTOR

ØA4ØB4

ØA3

PANEL-ØA3,ØB3, ØC3

ØA5ØA6

ØB6

2ND GRADE CLASSROOM

1609

TLT

1611.1

HALL

1611

TLT

1611.2

2ND GRADE CLASSROOM

1613

PROJECTOR

ØA ØA

ØC

ØC

ØA

ØA

ØA

ØB

ØA

ØC

ØB

ØB

PROJECTOR

NOTE 1

PANEL - ØAØB ØC

PANEL - ØAØB ØC

ØA

ØA

ØA

ØC

ØB

ØB

ØA

ØB

ØC

ØC

ØA ØA

NOTE 1

ØA

HOMERUN DIFFERENTIATION LINE

ØA

ØC

ØC

PSI CLASSROOM

1601

TLT

1603.1

DRESSING

1603

TLT

1603.2

STOR.

1605

SID/PID CLASSROOM

1607

C

NOTE 1

NOTE 1

ØA

ØB

PROJECTOR

ØA

ØA

ØC

ØA

ØB

ØC

ØA

ØC

ØA

ØB

PANEL - ØAØB ØC

PANEL - ØAØB ØC

HOMERUN DIFFERENTIATION LINE

ØB

ØA

PROJECTOR

ØA ØA

ØB

ØC

ØC

ØC

ØA

ØAØA

ØA

ØA

PANEL - ØA, ØBPANEL - ØC

ØB

ØA

ØC

ØC

ØA

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

1/4" = 1'-0"8/7

/2015 3

:29:0

2 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

E5.02

ELECTRICALLARGE SCALEPLANS

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/4" = 1'-0"E5.02

LARGE SCALE - CLASSROOM TYPE B - POWER & SYSTEM2

1/4" = 1'-0"E5.02

LARGE SCALE - CLASSROOM TYPE A - POWER & SYSTEMS3

1/4" = 1'-0"E5.02

LARGE SCALE - COMPUTER CLASSROOM - POWER & SYSTEMS4

1/4" = 1'-0"E5.02

LARGE SCALE - CLASSROOM TYPE C - POWER & SYSTEMS11

1. MOUNT BOX FOR AUDIO VISUAL CONNECTIONS AT 48" AFF.SEE DETAIL FOR BOX SIZE, CONFIGURATION AND CONDUITREQUIREMENTS.

(THIS SHEET ONLY)NOTES:

1/4" = 1'-0"E5.02

LARGE SCALE - CLASSROOM TYPE D - POWER & SYSTEMS5

A COORDINATE LOCATIONS OF OUTLETS WITH ARCHITECT, SEEDETAIL. 2/E7.01.

(THIS SHEET ONLY)GENERAL NOTES:

REVISION SCHEDULE

DATE DESCRIPTION

x1

x4 x4 x4 x4

x4 x4 x4 x4

x1 x4

x1

x4

x4

x1

x1

x4

x1

x4

x4

x1

x1

x4

X 13' - 11"11' - 11"

X 12' - 0"10' - 0"

P

P

P

P FACPP

X 12' - 0"10' - 0"

CC

C

C

AV

DATA

1113

NOTE 1

NOTE 2

NOTE 2

NOTE 2

NOTE 3

TGB

24

6

8

10

12 14,16 22

20

1824

26

28

L1A- 1820 22

L1A- 24 6

L1A- 14,16

L1A- 810 12

L1A- 2426 28

DATA

1418

NOTE 1

NOTE 3

NOTE 2

NOTE 2

NOTE 2

TGB66

54

56

58

60

62

64

72

70

68

74,7652

L1C- 5254 56

L1C- 6466

L1C- 5860 62L1C- 68

70 72

L1C- 74,76

MDF

1303

TB

NOTE 4

NOTE 2

NOTE 2

NOTE 2

NOTE 2

SERVERS

FIBER

COPPER

INTERCOM

FACPIACP

NOTE 3

NOTE 3

NOTE 1

NOTE 3

TMGB

CABINET FOR INTERCOMSHALL BE PROVIDED BYINTERCOM SYSTEM VENDORBUT SHALL MATCH OTHERTHREE CABINETS.

26

28,30242220

18

16

14

12

10

32

34

36

5452

50

48

4644

4038

L1B- 1012 14

L1B- 1618 20

L1B- 2224 26

L1B- 28,30

L1B- 3234 36

40L1B- 38

L1B- 4446

L1B- 4850

L1B- 5254

CEILING

WHITEBOARD

QUADRUPLEX RECEPTACLE(18"AFF)

TURN OUT ABOVE CEILING WITH 90DEGREE ELBOW. TERMINATE WITHARLINGTON BUSHING.(TYPICAL)

SPEAKER CABLEPROVIDED BY OWNER

FRONT LEFTSPEAKER

OWNER PROVIDED

FRONT RIGHTSPEAKER

OWNER PROVIDED

SPEAKER CABLEPROVIDED BY OWNER

BACK LEFTSPEAKER

OWNER PROVIDED

FRONT BACKSPEAKER

OWNER PROVIDED

POWER BELOWWHITEBOARD

DOUBLE DUPLEX RECEPTACLE FORPROJECTOR, MOUNTED IN KNOCKOUT OF THE

PROJECTOR MOUNT PLATE. (WALL MOUNTED INMUSIC ROOM FOR SHORT THROW PROJECTOR)

TWO 1-1/2"C. STUBBED ABOVEACCESSIBLE CEILING FORCABLES

CEILING MOUNTED DATA PROJECTOR,FURNISHED BY OWNER. INSTALLED,CONNECTED, PROGRAMMED AND SET UPBY CONTRACTOR. COORDINATE EXACTLOCATION OF PROJECTOR WITH OWNERSREPRESENTATIVE.

1-1/2"C. STUBBED ABOVEACCESSIBLE CEILING FORCABLES

A/V OUTLET AT TEACHER'S DESK. (48"AFF). 6"SQUARE, 3-1/2" DEEP OUTLET WITH THREE GANGPLASTER RING. FACEPLATE SHALL BE CABLES TOGO 60039. SEE SPECIFICATIONS PROVIDE USBEXTENDER AND PATCH CORDS PER SPECS.

NOTE:CONTRACTOR SHALL PROVIDE RECEPTACLES, OUTLETBOXES AND RACEWAYS. IT DEPARTMENT TO PROVIDECABLING, FACEPLATES, CONTROLLERS, PROJECTOR ANDMOUNT. CONTRACTOR SHALL INSTALL ONE CLASSROOMCOMPLETE AS A MOCK UP FOR THE OWNER TO REVIEWAND APPROVE PRIOR TO ROUGH IN OF ANY ADDITIONALCLASSROOMS.

THREE(3) CAT 6 CABLES TODATA RACK (18" AFF)

LADDER

1st LEVEL

48"

6"

1st LEVEL

TO PANELBOARD

NOTE 1:

ADJACENT TO SPRINKLER HEAD PER N.F.P.A.

SUMP PUMP

SUMP PUMP PIT

12" GRATE ELEVATOR SHAFTFINISHED FLOOR

NOTE 1

GFI RECEPTACLEIN FS BOX -UNSWITCHED

LIGHT FIXTURE, SEE PLANSFOR MARK & LOCATION

SWITCH IN FS BOX, LOCATEADJACENT TO LADDER ACCESS.

LOCATE HEAT DETECTOR ON WALL

NON-GFI RECEPTACLEIN FS BOX. UNSWITCHEDON DEDICATED CIRCUIT

(ELEVATOR ELEVATION - FIRE ALARM)

C

B

A

NOTES:

ELEVATOR LOBBY-FIRST FLOOR

ELEV. PIT

ELEV. SHAFT

ELEVATOR LOBBY - 2ND FLOOR

MACHINE ROOM

COORDINATE INSTALLATION OF DETECTORS WITH ELEVATOR EQUIPMENT

THE EXACT PLACEMENT OF DETECTORS SHALL BE FIELD DETERMINED INACCORDANCE WITH ASME A17.1, NFPA 72, AND THE ELEVATORMANUFACTURER.

ESR

SMOKE DETECTORTO INITIATEFIREMAN'SEMERGENCY RETURN

SMOKE DETECTORTO INITIATE FIREMAN'SEMERGENCY RETURN.(PROVIDE HEATDETECTORIF IN DAMP LOCATION).

HEAT DETECTOR. MOUNTWITHIN 2 FT. OFSPRINKLERHEAD.

SMOKE DETECTOR AT TOP

HEAT DETECTOR. MOUNTWITHIN 2 FT. OFSPRINKLERHEAD. OMIT IF SHAFT ISNOT SPRINKLED.

OF ELEVATOR SHAFT. SHALLINITIATE FIREMAN'SEMERGENCYRETURN AND FLASH FIRE HATIN ELEVATOR.

SMOKE DETECTOR TO INITIATEFIREMAN'S EMERGENCY RETURNAND FLASH FIRE HAT INELEVATOR.

HEAT DETECTOR. MOUNTWITHIN 2 FT. OFSPRINKLERHEAD. OMIT IF MACHINEROOM IS NOT SPRINKLED.

PROVIDE FIRE ALARMSYSTEM CONNECTION TOALL ELEVATOR CONTROL/MONITOR RELAYS PERELEVATORMANUFACTURER'SREQUIREMENTS. PROVIDEALL NECESSARY MODULES.

INTERLOCK HEAT DETECTORS WITH SHUNT TRIP BREAKER SERVINGELEVATOR TO INITIATE ELEVATOR POWER SHUTOFF UPONACTIVATION.

NOTES:ARRANGE EQUIPMENT IN ROOM AS RECOMMENDED BY ELEVATOR SUPPLIER ANDACCORDING TO N.E.C.

FUSE DISCONNECTS ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.

PROVIDE ITEMS NOT SHOWN BUT REQUIRED BY THE ELEVATOR MANUFACTURER.

PROVIDE AS A MINIMUM THE ELEVATOR POWER CIRCUIT SHOWN. COORDINATEEXACT FEEDER SIZE WITH THE ELEVATOR MANUFACTURER FOR THE EQUIPMENTACTUALLY PROVIDED.

(ELEVATOR EQUIPMENT ROOM)

B

D

C

A

E

A

F

F

1T

30A/2P

100A/3P

CAB LIGHTS

3#2,#8G,1-1/4 IN.C

3/4IN.C

ELEVATORCONTROL PANEL

#10'S

120/1

208/1

480/3

A

B

C

D

E

100A/3P/3R SHUNT TRIP ENCLOSEDCIRCUIT BREAKER.

M

HEAT DETECTOR IN ELEVATOR EQUIPMENT ROOM, TOP OF ELEVATOR SHAFT,AND ELEVATOR PIT SHALL SHUNT BREAKER WHEN ACTIVATED.

F

F SEE ELEVATOR ELEVATION - FIRE ALARM DETAIL FOR MORE INFORMATION.

SEE PLANFOR CIRCUITNUMBERS

DATA

2419

NOTE 1

NOTE 2

NOTE 2

NOTE 2

NOTE 3

NOTE 3

TGB

8

10

12

14

16

18

20

2230,32

24

26

28

L2C- 2426 28

L2C- 1416 18

L2C- 2022

L2C- 30,32

L2C- 810 12

SCIENCE CLASSROOM

2409

NOTE 5

NOTE 7

NOTE 8

PROJECTOR

ØA1

ØA1

ØA1

ØB1

ØB1

ØB1

ØB1

ØB2

ØB2

ØC2 ØC2 ØC2

ØA2

ØA2

ØA2

ØC1 ØB2ØC1

PANEL-ØA1,ØB1,ØC1

PANEL-ØA2,ØB2,ØC2

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

As indicated8/7

/2015 3

:29:0

7 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

E5.03

ELECTRICALLARGE SCALEPLANS

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/4" = 1'-0"E5.03

LARGE SCALE - DATA 1113 POWER & SYSTEMS1 1/4" = 1'-0"E5.03

LARGE SCALE - DATA 1418 POWER & SYSTEMS2 1/4" = 1'-0"E5.03

LARGE SCALE - MDF 1309 POWER & SYSTEMS4

1/8" = 1'-0"E5.03

TYPICAL WALL FIELD DETAIL FOR DEVICE LAYOUT FOR CLASSROOMS5

1/8" = 1'-0"E5.03

ELEVATOR ELEVATION - ELECTRICAL6 1/8" = 1'-0"E5.03

ELEVATOR ELEVATION - FIRE ALARM7 1/8" = 1'-0"E5.03

ELEVATOR EQUIPMENT ROOM DETAIL8

1/4" = 1'-0"E5.03

LARGE SCALE - DATA 2419-1 POWER & SYSTEMS9

1/4" = 1'-0"E5.03

LARGE SCALE - LAB POWER & SYSTEMS10

1. PROVIDE 4#10 HOMERUN, 3/4"C. FOR FUTURE UPS POWER.

2. RECEPTACLE SHALL BE LOCATED AT TOP OF TELECOMMUNICATIONSRACK. COORDINATE EXACT LOCATION WITH TELECOMUNICATIONSINSTALLER.

3. PLYWOOD BACKBOARD: PROVIDE 3/4" THICK, FIRE RETARDANT PLYWOODBACKBOARD, COAT PLYWOOD WITH TWO COATS LIGHT GRAY FIRERETARDANT PAINT. PROVIDE 3/4" X 3/4" ALUMINUM ANGLE FRAME AFTERPAINTING.

4. TELEPHONE DEMARK: PROVIDE TELEPHONE CABLING FOR THE FOLLOWING:EMERGENCY 911 BACKUP LINES (2), FIRE ALARM (1), BURGLAR ALARM (1),ELEVATOR (2).

5. MOUNT BOX FOR AUDIO VISUAL CONNECTIONS AT 48" A.F.F. SEE DETAIL FORBOX SIZE, CONFIGURATION AND CONDUIT REQUIREMENTS.

6. NOT USED.

7. MOUNT OUTLETS IN KNEE SPACE OF CASEWORK IN AN ACCESSIBLE LOCATION.ALL CONDUIT SHALL BE CONCEALED.

8. PROVIDE 1 1/4" CONDUIT FROM DATA OUTLET TO NEAREAST WALL, THENTO ABOVE ACCESSIBLE CEILING.

(THIS SHEET ONLY)NOTES:

A COORDINATE LOCATIONS OF OUTLETS WITH ARCHITECT, SEEDETAIL. 2/E7.01.

(THIS SHEET ONLY)GENERAL NOTES:

REVISION SCHEDULE

DATE DESCRIPTION

GROUND CONNECTION FOR EQUIPMENT.COMPRESSION LUG BOLTS AND WIRE.

MOUNTING BRACKET,STAINLESS STEEL

POLYESTER/FIBERGLASS.RED STANDOFF INSULATOR,

FRONT ELEVATION

A

WALL CONSTRUCTION(TYPICAL).

SUITABLE FORWALL ANCHOR SECTION "A-A"

A

19" x 6" x 1/4" THICK COPPER GROUND BUS

3/8" MOUNTING BOLT.

1" OFFSET.2"

1/4"

NOTE: LOCATION INDICATEDAS "TMGB" IN MDF ROOMAND "TGB" IN IDF ROOMS.

STK

STK

CORE12X4

APOGEECA-4000

CD PLAYER

1-WIRELESS MIC

2-WIRELESS MIC

1- MIC

2- MIC

3- MIC

INPUTS

AFI-3SPEAKER

AFI-3SPEAKER

WILLIAMS SOUND

ASSISTED LISTENING SYSTEM

AFI-3SPEAKER

AFI-3SPEAKER

SCHOOL WIDE INTERCOM

4

TO NEAREST 120 VOLT, 20 AMPUNSWITCHED RECEPTACLECIRCUIT

MOTOR RATEDSWITCH

3#12, 1 / 2 IN. C

INTERIOR VIEW

1 1

22

3

1/2" C. 1/2" C.

5 5

THIS DRAWING IS INTENDED TO INDICATE CONDUIT INFRASTRUCTUREREQUIREMENT ONLY. COORDINATE EXACT REQUIRED COMPONENTSWITH ARCHITECTURAL DOOR SPECIFICATIONS. PROVIDE ALL CONDUITAND BOXES FOR COMPLETE ACCESS CONTROL INSTALLATION.

3#12, 1/2"C.(FLEXIBLECONDUIT)

NOTES:1

2

4

(ACCESS CONTROL CONNECTIONS)

DOOR POSITION SWITCH.

CURRENT TRANSFER HINGE

POWER SUPPLY.

CARD READER.

DELAYED EGRESS SYSTEM - NORMALLY CLOSED FIRE ALARMRELAY REQUIRED, PLUGNPLAY. NORMALLY CLOSED FIRE ALARMRELAY REQUIRED FOR THE DELAYED EGRESS APPLICATION.

3

5

TO MDF/IDF

PROVIDE 12 CONDUCTOR20 GAUGE WIRE WITH THEFOLLOWING COLORS: BLACK,RED, WHITE, GREEN, ORANGE,BLUE, BROWN, YELLOW, PINK,GRAY, TAN AND VIOLET.

STK

STK

CORE

12X4

BOGEN

M-CLASS

CD PLAYER

1-WIRELESS MIC

2-WIRELESS MIC

1- MIC

2- MIC

3- MIC

INPUTS

WILLIAMS SOUND

ASSISTED LISTENING SYSTEM

s

s

ALL SPEAKERS IN CAFETERIA SHALLBE BOGEN "HFCS1" OR EQUALSPEAKERS. SEE PLAN FOR QUANTITYOF SPEAKERS

SCHOOL WIDE INTERCOM

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

NOT TO SCALE8/7

/2015 3

:29:1

8 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

T0.01

TELECOMDETAILS

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

NOT TO SCALET0.01

2 TELECOMMUNICATIONS EQUIPMENT GROUND BUS

NOT TO SCALET0.01

3 GYM / MULTIPURPOSE P.A. SYSTEM SIGNAL FLOW DIAGRAM

NOT TO SCALET0.01

1 ACCESS CONTROL DOOR DETAILNOT TO SCALET0.01

4 CAFETERIA P.A. SYSTEM SIGNAL FLOW DIAGRAM

REVISION SCHEDULE

DATE DESCRIPTION

DN

AC

AC

AC AC

AC

AC

AC

AC AC

AC

AC

AC

AC

AC

AC

AC

AC

AC

AC

ACAC

ACAC

AC

KP

AC

KP

AC

AC

AC

CAFETERIA

1304

ELEC

1301

EQUIPMENT

1103STORAGE

1429

OFFICE

1407

?

?

OFFICE

1408

OFFICE

1409

CORR

1300

KILN

1413

STAIR

2402-14

STORAGE

1412

CHASE

1022.1JAN

1022

MEN

1021

WOMEN

1023

ELEC

1208

STOR

1211

STOR

1210

STORAGE

1204

STORAGE

1205

CHASE

1213.1

GYM

1201

OFFICE

1207

STOR

1206

LOBBY

1200

DATA

1113

JAN

1306

TRASH VEST

1305

OFFICE

1314

CHEM STOR

1313

SERVERY

1307

ELECTRICAL

1318

TLT

1317

DISH WASH

1308

COOLER/FREEZER

1312

RECEIVING

1315

KITCHEN

1311

JAN

1420

DATA

1418ELEC

1416

OFFICE

1414

OFFICE

1410

CONF

1433

CORR

1500

ELL CLASSROOM

1430

WORKROOM

1434

STORAGE

1514

HALL

1504

STAIR

2402-65

HALL

1510

RESOURCE ROOM

1421

ART

1411

ELEVATOR EQUIPMENT

1415

CORR

1600

STORAGE

1614

STAIR

2402-72

DRY STORAGE

1310

TABLE/CHAIR STORAGE

1309

OFFICE

1419

ELEV

1417

JAN

1213

LEARNING CENTER

1111

LEARNING CENTER

1112

WORKROOM

1104

BROADCAST

1109

OFFICE

1105

CIRCULATION

1101.1

CORRIDOR

1004

CORRIDOR

1001.1

CORRIDOR

1001.2

LOCKER

1316

WAITING

1405

CORR

1405.2

VESTIBULE

1000

STAIR

1401

RECORDS

1011

STORAGE

1020

MAILROOM

1005

CORRIDOR

1001

MEN

1212

MUSIC

1209

CORR

1200.1

WOMEN

1214

CLOS

1012.2

LEAD TEACHER

1016ASSIST. PRINCIPAL

1018

TESTING

1014

CORRIDOR

1400

HEAD CUSTODIAN

1402

JAN

1403

SCRUBBER STORAGE

1302

MDF

1303

SUPPLIES

1304.1

MECHANICAL-1

1319-1

MECHANICAL-2

1319-2

JAN

1015

TLT

1017

SITTING AREA

1004.1

SUPPLY

1007

CLINIC

1019

COTS

1019.1CORR

1004.2

CORR

1004.3

TLT

1012.1

CONFERENCE

1010

PRINCIPAL

1012

STORAGE

1106

TLT

1104.1

TLT

1107

TLT

1108

STAFF

1110

TLT

1019.2

TLT

1013

TLT

1431

TLT

1432

TLT

1510.2

TLT

1510.1

KINDERGARTEN CLASSROOM

1508

KINDERGARTEN CLASSROOM

1512

HALL

1509

TLT

1509.2

TLT

1509.1

KINDERGARTEN CLASSROOM

1507

KINDERGARTEN CLASSROOM

1511

HALL

1503

TLT

1503.2

TLT

1503.1

KINDERGARTEN CLASSROOM

1501

KINDERGARTEN CLASSROOM

1505

TLT

1504.1

1ST GRADE INCLUSION CLASSROOM

1502

TLT

1504.2

KINDERGARTEN INCLUSION CLASSROOM

1506

HALL

1604

TLT

1604.2

TLT

1604.1

2ND GRADE CLASSROOM

1606

SPANISH

1602

HALL

1610

TLT

1610.2

TLT

1610.1

2ND GRADE CLASSROOM

1612

2ND GRADE CLASSROOM

1608

HALL

1611

TLT

1611.2

TLT

1611.1

2ND GRADE CLASSROOM

1613

2ND GRADE CLASSROOM

1609

HALL

1424

TLT

1424.2

TLT

1424.1

1ST GRADE CLASSROOM

1426

1ST GRADE CLASSROOM

1422

HALL

1425

TLT

1425.2

TLT

1425.1

1ST GRADE CLASSROOM

1427

1ST GRADE CLASSROOM

1423

SID/PID CLASSROOM

1607

PSI CLASSROOM

1601

TLT

1603.2

STOR.

1605

TLT

1603.1

DRESSING

1603

WORKROOM

1006

OFFICE

1009

DATA CLERK

1008

CLERICAL

1003

RECEPTION

1002

COMPUTER LAB

1102

MEDIA CENTER-2

1101-2

CORRIDOR-2

1100-2

@20' AFF

@20' AFF

INTRUSION ALARMCONTROL PANEL

CARDREADER(ELR|DPS)

DPS ONLY,EXIT ONLY

CARDREADER(ELR|DPS)

DPS ONLY,EXIT ONLY

CARDREADER(ELR|DPS)

DPS ONLY

DPS ONLYEXIT ONLY

CARD READER(ELR|DPS)

DPS ONLYEXIT ONLY

DPS ONLYEXIT ONLY

DPS ONLY

DPS ONLYCARDREADER(ELR|DPS)

DPS ONLYEXIT ONLY

DPS ONLYDPS ONLY

CARD READER(ELR|DPS)

CARD READER(ELR|DPS)

CARD READER(ELR|DPS)

ELR|DPS

CARD READER(ELR|DPS)

CARD READER(ELR|DPS)

DPS ONLYEXIT ONLY

DPS ONLY

CARD READER(ELR|DPS) CARD READER

(ELR|DPS)

CARD READER(ELR|DPS)

AIPHONE SYSTEMREQUIREMENTSINDICATED ONSHEET E2.11

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

1/16" = 1'-0"8/7

/2015 3

:29:5

3 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

T2.11

FIRST FLOORPLAN -SECURITYSYSTEMS

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/16" = 1'-0"T2.11

FIRST FLOOR PLAN - SECURITY SYSTEMS1

REVISION SCHEDULE

DATE DESCRIPTION

DN

s s

CAFETERIA

1304

ELEC

1301

EQUIPMENT

1103STORAGE

1429

OFFICE

1407

?

?

OFFICE

1408

OFFICE

1409

CORR

1300

KILN

1413

STAIR

2402-14

STORAGE

1412

CHASE

1022.1

JAN

1022

MEN

1021

WOMEN

1023

ELEC

1208

STOR

1211

STOR

1210

STORAGE

1204

STORAGE

1205

CHASE

1213.1

GYM

1201

OFFICE

1207

STOR

1206 LOBBY

1200

DATA

1113

JAN

1306

TRASH VEST

1305

OFFICE

1314

CHEM STOR

1313

SERVERY

1307

ELECTRICAL

1318

TLT

1317

DISH WASH

1308

COOLER/FREEZER

1312

RECEIVING

1315

KITCHEN

1311

JAN

1420

DATA

1418ELEC

1416

OFFICE

1414

OFFICE

1410

CONF

1433

CORR

1500

ELL CLASSROOM

1430

WORKROOM

1434

STORAGE

1514

HALL

1504

STAIR

2402-65

HALL

1510

RESOURCE ROOM

1421

ART

1411

ELEVATOR EQUIPMENT

1415

CORR

1600

STORAGE

1614

STAIR

2402-72

DRY STORAGE

1310

TABLE/CHAIR STORAGE

1309

OFFICE

1419

ELEV

1417

JAN

1213

LEARNING CENTER

1111

LEARNING CENTER

1112

WORKROOM

1104

BROADCAST

1109

OFFICE

1105

CIRCULATION

1101.1

CORRIDOR

1004

CORRIDOR

1001.1

CORRIDOR

1001.2

LOCKER

1316

WAITING

1405

CORR

1405.2

VESTIBULE

1000

STAIR

1401

RECORDS

1011

STORAGE

1020

MAILROOM

1005

CORRIDOR

1001

MEN

1212

MUSIC

1209

CORR

1200.1

WOMEN

1214

CLOS

1012.2

LEAD TEACHER

1016ASSIST. PRINCIPAL

1018

TESTING

1014

CORRIDOR

1400

HEAD CUSTODIAN

1402

JAN

1403

SCRUBBER STORAGE

1302

MDF

1303SUPPLIES

1304.1

MECHANICAL-1

1319-1

MECHANICAL-2

1319-2

JAN

1015

TLT

1017

SITTING AREA

1004.1

SUPPLY

1007

CLINIC

1019

COTS

1019.1

CORR

1004.2

CORR

1004.3

TLT

1012.1

CONFERENCE

1010

PRINCIPAL

1012

STORAGE

1106

TLT

1104.1

TLT

1107

TLT

1108

STAFF

1110

TLT

1019.2

TLT

1013

TLT

1431

TLT

1432

TLT

1510.2

TLT

1510.1

KINDERGARTEN CLASSROOM

1508

KINDERGARTEN CLASSROOM

1512

HALL

1509

TLT

1509.2

TLT

1509.1

KINDERGARTEN CLASSROOM

1507

KINDERGARTEN CLASSROOM

1511

HALL

1503

TLT

1503.2

TLT

1503.1

KINDERGARTEN CLASSROOM

1501

KINDERGARTEN CLASSROOM

1505

TLT

1504.1

1ST GRADE INCLUSION CLASSROOM

1502

TLT

1504.2

KINDERGARTEN INCLUSION CLASSROOM

1506

HALL

1604

TLT

1604.2

TLT

1604.1

2ND GRADE CLASSROOM

1606

SPANISH

1602

HALL

1610

TLT

1610.2

TLT

1610.1

2ND GRADE CLASSROOM

1612

2ND GRADE CLASSROOM

1608

HALL

1611

TLT

1611.2

TLT

1611.1

2ND GRADE CLASSROOM

1613

2ND GRADE CLASSROOM

1609

HALL

1424

TLT

1424.2

TLT

1424.1

1ST GRADE CLASSROOM

1426

1ST GRADE CLASSROOM

1422

HALL

1425

TLT

1425.2

TLT

1425.1

1ST GRADE CLASSROOM

1427

1ST GRADE CLASSROOM

1423

SID/PID CLASSROOM

1607

PSI CLASSROOM

1601

TLT

1603.2

STOR.

1605

TLT

1603.1

DRESSING

1603

WORKROOM

1006

OFFICE

1009

DATA CLERK

1008

CLERICAL

1003

RECEPTION

1002

COMPUTER LAB

1102

MEDIA CENTER-2

1101-2

CORRIDOR-2

1100-2

TYPICAL FOR ALL FLOOR BOXES:PROVIDE 1 1/4" CONDUIT FROM BOXTO NEAREST BLOCK WALL, THENTURN CONDUIT OUT ABOVE ACCESSIBLECEILING AT BASKET TRAY.

PROVIDE 4-4"CFROM IDF TOMDF ROOM.

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

1/16" = 1'-0"8/7

/2015 3

:30:0

8 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

T3.11

FIRST FLOORPLAN - WIREMANAGEMENT

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/16" = 1'-0"T3.11

FIRST FLOOR PLAN - WIRE MANAGEMENT1

IN OPEN STRUCTURE AREASAND IN SPACES WITH HARDCEILILNGS, LOW VOLTAGECABLING SHALL BE ROUTEDIN CONDUIT TO CABLE TRAY.

REVISION SCHEDULE

DATE DESCRIPTION

A

B

C

D

E

F

G

H

I

K

J

NOTES: (J-HOOK DETAIL)RESOURCE ROOM-1

2405-1

RESOURCE ROOM-1

2401-1

STAIR

1120

STORAGE-1

2427-1 STORAGE-1

2407-1

STORAGE

2410

JAN-1

2420-1

DATA

2419

ELEC-1

2418-1

CONF-1

2433-1

CORRIDOR

2500

DATA CONF ROOM-1

2429-1

WORKROOM-1

2430-1

?

?

STORAGE-1

2514-1

RESOURCE ROOM-1

2417-1

STOR-1

2411-1

STAIR

1135

CORRIDOR-1

2600-1

STORAGE

2614

CORRIDOR-1

2402-1

OFFICE-1

2416-1

OFFICE-1

2414-1

STOR-1

2412-1

SCIENCE CLASSROOM

2409

GIFTED/STEM LAB

2408

CORRIDOR

2400

STAIR-1

2406-1

OFFICE-1

2415-1

ELEV-1

2413-1

TLT-1

2431-1

TLT-1

2432-1

HALL-1

2510-1

TLT-1

2510.2-1

5TH GRADE CLASSROOM

2512

5TH GRADE CLASSROOM-1

2508-1

HALL-1

2509-1

TLT-1

2509.2-1

5TH GRADE CLASSROOM

2511

5TH GRADE CLASSROOM-1

2507-1

HALL-1

2503-1

TLT-1

2503.2-1

5TH GRADE CLASSROOM

2505

4TH GRADE CLASSROOM-1

2501-1

HALL-1

2604-1

TLT-1

2604.2-1

3RD GRADE CLASSROOM

2602

3RD GRADE CLASSROOM-1

2606-1

TLT-1

2604.1-1

HALL-1

2610-1

TLT-1

2610.2-1

GIFTED CLASSROOM

2608

GIFTED CLASSROOM

2612

TLT-1

2610.1-1

HALL-1

2609-1

TLT-1

2609.2-1

GIFTED CLASSROOM

2607

GIFTED CLASSROOM-1

2611-1

TLT-1

2609.1-1

HALL-1

2423-1

TLT-1

2423.2-1

3RD GRADE CLASSROOM

2421

3RD GRADE CLASSROOM-1

2425-1

TLT-1

2423.1-1

HALL-1

2424-1

TLT-1

2424.2-1

4TH GRADE CLASSROOM

2422

4TH GRADE CLASSROOM-1

2426-1

TLT-1

2424.1-1

HALL-1

2504-1

TLT-1

2504.2-1

5TH GRADE INCLUSION CLASSROOM

2506

4TH GRADE INCULSION CLASSROOM-1

2502-1

TLT-1

2504.1-1

HALL-1

2603-1

TLT-1

2603.2-1

3RD GRADE INCLUSION CLASSROOM

2601

TLT-1

2603.1-1

ESL CLASSROOM-1

2605-1

TLT

2403

TLT

2404

PROVIDE 6-4"SLEEVES TODATA ROOMBELOW.

UP TO 4" CONDUIT

NOTE:WHERE CONDUIT IS USED AS A SLEEVE FOR ROUTING LOW VOLTAGE CABLESTHROUGH A RATED WALL, LOCATE CONDUCTORS IN CENTER OF SLEEVE ANDFILL OPENING WITH NON HARDENING FIRE RATED PUTTY AT EACH END.

WHERE USED AS SLEEVEFOR LOW VOLTAGECABLING,EXTEND CONDUIT 6"BEYONDWALL AND PROVIDE NYLONBUSHINGS ON BOTH ENDS.

FOAM BACKING RODS

WALL

WIRE MESH/STEEL SLEEVE3/4" METACAULK FIRERATED PUTTY

STEEL MATERIALMINIMUM 1"WIDE

ALL J- HOOKS SHALL BE SPACED NO MORE THAN 48 INCHES APART AND NOMORE THAN 12 INCHES FROM THE CORNER OF ANY SPACE.

PROVIDE J-HOOKS NO MORE THAN 12 INCHES AWAY FROM CONDUIT SLEEVES.

WHERE J-HOOKS ARE 2 OR MORE ROWS: SPACING BETWEEN THE ROWS SHALLBE 12 INCHES.

CONDUIT SLEEVES SHALL BE AT THE SAME LEVEL AS THE ROWS OF J-HOOKS.

FIRE SEAL AROUND ALL CONDUIT SLEEVES AS SHOWN IN CONDUIT PENTRATIONDETAILS. SEE ARCHITECTURAL SHEET FOR REQUIRED RATINGS.

COORDINATE THE EXACT LEVEL OF J-HOOKS AND CONDUIT SLEEVES WITH OTHERTRADES PRIOR TO ROUGHING.

J-HOOKS SHALL NOT BE SUPPORTED BY GYPSUM WALL BOARD. J-HOOKS SHALL BESUPPORTED BY BLOCK WALL OR STUD. SEE ARCHITECTURAL PLAN FOR WALLMATERIALS.

ALL CABLING SHALL BE NEATLY BUNDLED UTILIZING VELCRO TIE WRAPS ATMINIMUM 5' INTERVALS.

J-HOOKS SHALL SUPPORT CABLING FOR: FIRE ALARM, INTERCOM, DATA, TELEPHONE,CCTV, INTRUSION AND TELEVISION DISTRIBUTION.

J-HOOKS SHALL SUPPORT A SINGLE SYSTEM - CABLING SHALL NOT BE INTERMINGLED.

PROVIDE QUANTITY OF J-HOOKS AS REQUIRED FOR CABLING NOTED ON DRAWINGS,DO NOT EXCEED J-HOOK CAPACITY.

4"

6"

UP TO 4" EMT OR STEEL PIPE

NOTE:WHERE CONDUIT IS USED AS A SLEEVE FOR ROUTING LOW VOLTAGE CABLESTHROUGH A RATED WALL, LOCATE CONDUCTORS IN CENTER OF SLEEVE ANDFILL OPENING WITH NON HARDENING FIRE RATED PUTTY AT EACH END OFSLEEVE.

WHERE USED AS SLEEVEFOR LOW VOLTAGECABLING,EXTEND CONDUIT 6"BEYONDWALL AND PROVIDE NYLONBUSHINGS ON BOTH ENDS.

3/4" METACAULK FIRE RATED

PUTTY

FOAM BACKING RODS

CONCRETE BLOCK (CMU)

OR CONCRETE WALL

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

As indicated8/7

/2015 3

:30:1

5 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

7-2

0-2

015.r

vt

T3.22

SECOND FLOORPLAN - WIREMANAGEMENT

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

1/16" = 1'-0"T3.22

SECOND FLOOR PLAN - WIRE MANAGEMENT1

NOT TO SCALET3.22

2 GYPSUM WALLBOARD PENETRATION

NOT TO SCALET3.22

3 J-HOOK DETAIL

NOT TO SCALET3.22

4 CONCRETE WALL PENETRATION

REVISION SCHEDULE

DATE DESCRIPTION

1000.1

12

2

1400.3

1500

1600

2

12

PS

J

J

1000.2

J

12 12

PS

120V INPUT

120V INPUT

J

12

PS

120V INPUT

12

1000.4 1000.3

2 2

J

2 2

1200.11200.2

2 2 2 2

12 12

2 2

J

PS

120V INPUT

12 12

2 2

J

PS

120V INPUT

J

12

PS

120V INPUT

1002.2

J

2 2

J

4

1001.1

J

12

PS

120V INPUT

12

2 2

1201.1

1300

1201.2

1203

1315

12

J

PS

120V INPUT

1318

1319

1320

1401.1

1428.1

1513.1

1615.1

1411.1

1304.31200.3

1101.1

J

12

PS

120V INPUT

2

1101.2

J

2

J

12

PS

120V INPUT

2

T

PROFESSIONAL

NEER

IGNE

SIGER

ERED

No. 26308

IGROEG

A

A

W

R.L

NERRA

W

NORTH

517 EAST CONGRESS STREETSAVANNAH, GEORGIA 31401

tel 912.234.6318fax 912.236.8414

cogdellmendrala.com

PROJECT CONSULTANTS:

SEAL:

SHEET TITLE:

ARCH. PROJECT NO:

DRAWN BY:DATE:

SCALE:

SHEET:

KEY PLAN:

COGDELL & MENDRALA ARCHITECTS, PC

STRUCTURAL ENGINEER:

MECHANICAL & PLUMBING ENGINEER:

DULOHERY WEEKS, INC.333 COMMERICAL DRIVESAVANNAH, GA. 31406

SAUSSY ENGINEERING400 E. JOHNNY MERCER BOULEVARDSAVANNAH, GA 31410

CIVIL ENGINEERS:

COASTLINE CONSULTINGSERVICES138 CANAL STREETPOOLER, GA 31322

FTE: 750 / 900 CORE

1500

Cogdell MendralaArchitects

WOLVERTON & ASSOCIATES, INC.7 CONGRESS STREETSAVANNAH, GA 31401

ELECTRICAL & COMMUNICATIONS ENGINEER:

SUSTAINABLE DESIGNCONSULTANTS

415 BONAVENTURE DRIVETHUNDERBOLT, GA. 31404

1400

1600

1100

1300

1200

1000

FACILITY CODE: 625-0122

NOT TO SCALE9/2

/2015 7

:37:4

9 P

ME

:\$A

CT

IVE

JO

BS

\2014 1

017 -

MA

Y H

OW

AR

D\R

EV

IT M

OD

ELS

\20141017 E

LE

C-G

clark

9-2

-2015.r

vt

T4.11

ACCESSCONTROLDETAILS

GJCAUGUST 2015

1402

MA

Y H

OW

AR

D E

LE

ME

NT

AR

Y

RE

PL

AC

EM

EN

T S

CH

OO

L

115 W

ILM

ING

TO

N IS

LA

ND

RO

AD

SA

VA

NN

AH

, G

EO

RG

IA 3

1410

REVISION SCHEDULE

DATE DESCRIPTION

9-04-2015 Addendum No. 1

NOT TO SCALET4.11

1 ACCESS CONTROL DETAILS

1

COORDINATE CABLING WITH SECTION 087100. EXTEND ALL PREWIREDCABLES IN HOLLOW METAL FRAMES, INCLUDING CONDUIT, TO THEJUNCTION BOX LOCATIONS SHOWN. DO NOT CUT ANY EXCESS CABLING.SIMPLY COIL IT AND TIE WRAP TO JUNCTION BOX FOR TERMINATION BYOTHERS.

ELECTRICAL CONTRACTOR RESPONSIBLE FOR ALL 120VAC CONNECTIONSTO THE POWER SUPPLIES.

SEE ARCHITECTURAL FLOOR PLAN SHEETS FOR ALL DOOR NUMBERS.

SEE DETAIL 1/T0.01 FOR ADDITIONAL REQUIREMENT FOR ALL ACCESSCONTROL DOORS.

(THIS SHEET ONLY)GENERAL NOTES:A.

B.

C.

D.