M-SERIES
Specifications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
Job Name:
System Reference: Date:
SUBMITTAL DATA: MSZ-HM09NA-U1 & MUZ-HM09NA2-U1 9,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM
Indoor Unit: MSZ-HM09NA-U1
Outdoor Unit: MUZ-HM09NA2-U1Wireless Remote Controller
ACCESSORIES:Indoor Unit
□ Condensate Pump (BlueDiamond X87-711/721; 115/230V) □ Condensate Pump (Sauermann SI30-115/230; 115/230V) □ Anti-Allergy Enzyme Filter (MAC-408FT-E) □ Drain Pan Level Sensor (DPLS2)
Outdoor Unit
□ Outdoor Mounting Pad (ULTRILITE1) □ Drain Pan Heater (MAC-640BH-U) □ 3-1/4” Mounting Base [Pair] (DSD-400P) □ Drain Pan Socket (MAC-860DS) □ Air Outlet Guide (MAC-889SG) □ Wall Mounting Bracket (QSWB2000M-1)
SPECIFICATIONS:
Rated Conditions (Capacity / Input)
Cooling1 Btu/h / W 9,000 / 750
Heating at 47º F2 Btu/h / W 10,900 / 900
Capacity Range Minimum Maximum
Cooling1 Btu/h 3,800 10,000
Heating at 47º F2 Btu/h 4,500 11,800
Heating at 17º F3 Btu/h - 7,200
Heating at 5º F4 Btu/h - 6,0001 Cooling | Indoor: 80º F(27º C)DB / 67º F(19º C)WB; Outdoor: 95º F(35º C)DB / 75º F(24º C)WB* 2 Heating at 47ºF | Indoor: 70º F (21º C)DB / 60º F (16º C)WB; Outdoor: 47º F (8º C)DB / 43º F (6º C)WB* 3 Heating at 17º F | Indoor: 70º F(21º C)DB / 60º F(16º C)WB; Outdoor: 17º F(-8º C)DB / 15º F(-9º C)WB* 4 Heating at 5º F | Indoor: 70º F (21º C)DB / 60º F(16º C)WB; Outdoor: 5º F(-15º C) DB / 5º F(-15º C)WB * Rating Conditions per AHRI Standard:
Operating Conditons (Indoor Intake Air Temp.) (Max./ Min.)
Cooling 90º F (32º C) DB / 67º F (19º C) DB
Heating 80º F (27º C) DB / 70º F (21º C) DB
Operating Conditons (Outdoor Intake Air Temp.) (Max./ Min.)
Cooling5 115 F (46º C) DB / 14º F (-10º C) DB
Heating 75º F (24º C) DB / 5º F (-15º C) DB**
5 Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.** System cuts out at -9º F (-27º C) to avoid thermistor error and automatically restarts at -4º F (-20º C).
AHRI Efficiency Ratings
SEER / HSPF 18 / 8.5
COP at 47o F / 17o F 3.55 / 2.8
Electrical Power Requirements 208 / 230V, 1-Phase, 60 Hz
Minimum Circuit Ampacity (MCA)
Indoor / Outdoor A 1.0 / 9
Indoor Unit
Blower Motor (ECM) F.L.A. 0.76
Blower Motor Output W 30
SHF / Moisture Removal 0.82 / 1.5 pt./h
Field Drainpipe Size O.D. In.(mm) 5/8 (15)
Outdoor Unit
Compressor DC INVERTER-driven Twin Rotary
Fan Motor (ECM) F.L.A. 0.5
Airflow Rate (Lo - Med - Hi - Super Hi)
Indoor (Cooling)
DRY
CFM
170-237-321-399
WET 134-201-286-364
Indoor (Heating) DRY 170-237-321-406
Outdoor 1,151 /1 ,225
Sound Pressure Level (Lo - Med - Hi - Super Hi)
IndoorCooling
dB(A)
22-30-37-43
Heating 22-30-37-43
OutdoorCooling 46
Heating 50
External Dimensions
Indoor (H x W x D)
In.(mm)
11-5/8 x 31-7/16 x 9-1/8 (295 x 798 x 232)
Outdoor (H x W x D) 21-5/8 x 31-1/2 x 11-1/4 (550 x 800 x 285)
Net Weight
IndoorLbs.(kg)
22 (10)
Outdoor 73 (33)
External Finish
Indoor Munsell 1.0Y 9.2 / 0.2
Outdoor Munsell No. 3Y 7.8 / 1.1
Refrigerant R410A; 1 lb. 12 oz.
Refrigerant Piping (Flared)
Liquid (High Pressure)In.(mm)
1/4 (6.35)
Gas (Low Pressure) 3/8 (9.52)
Max. Total Refrigerant Pipe Length (Height Diff.)
Ft. (m)
40 (12)
Max. Total Refrigerant Pipe Length (Length.) 65 (20)
Specifications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
1340 Satellite Boulevard. Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com
FORM# MSZ-HM09NA-U1 / MUZ-HM09NA2-U1 - 201611
DIMENSIONS: MSZ-HM09NA-U1 & MUZ-HM09NA2-U1MSZ-HM09NA-U1
MUZ-HM09NA2-U1
Unit: in. (mm)
Unit: in. (mm)
9
OUTLINES AND DIMENSIONS4
Unit: inchMUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
clea
r *1
*1 4 in. (100 mm) or more when front and sides of the unit are clear
*2 When any 2 sides of left, right and rear of the unit are clear
holes
REQUIRED SPACE
Liquid refrigerant pipe jointRefrigerant pipe (flared) Ø 1/4
Gas refrigerant pipe jointRefrigerant pipe (flared) Ø 3/8 (HM09/12) Ø 1/2 (HM15/18)
4 in. (100 mm)
or more
14 in. (350 mm)or more8 in. (200 mm)
or more *2
4 in. (100 mm)or more
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
OBH747A
7
Unit: inchMSZ-HM09NA MSZ-HM12NA MSZ-HM15NA
MSZ-HM18NA MSZ-HM24NA
4 OUTLINES AND DIMENSIONS
Pipi
ng InsulationMSZ-HM24NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø3/8)
Gas line Ø15/32 13-3/8 (Flared connection Ø5/8)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
Pipi
ng InsulationMSZ-HM18NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø1/4)
Gas line Ø15/32 13-3/8 (Flared connection Ø1/2)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
11/16
5-1/2
2-1/4
2-1/4 2-1/2
9-13/163/16
35-13/1636-5/16
1/4
27-15/16 6-5/162-1/16
12
2-9/16
2-13
/16
2-1/2
2-9/163-11/16
2-1/1
6
9-7/1
610
-5/16
1/8
8-7/8 8-7/83-11/16
8-3/410
-3/8
2-5/16 15-7/8
8-11/16
3-11/16
7/8
1×7/16 Oblong hole
7/16×13/16Oblong holeInstallation plate
Indoor unit
Wall hole Ø3Air in
Installation plate
8-1/16
15-3/161-5/8
8-11
/16
3 1-11
/16
2-9/16
2-9/1
6
4-1/25-3/4
1/4
Air out
Piping
Drain hose
3-15
/16
11/16
5-1/2
2-1/4
Pip
ing
Insulation ø1 - 3/8 O.DLiquid line ø1/4 19 - 11/16 (Flared connection ø1/4)Gas line ø3/8 16 - 15/16
(Flared connection: ø3/8 (HM09/12NA), ø1/2 (HM15NA))Drain hose Insulation ø1-1/8 O.D Connected part ø5/8 O.D
OBH746A
M-SERIES
Specifications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
Job Name:
System Reference: Date:
SUBMITTAL DATA: MSZ-HM12NA-U1 & MUZ-HM12NA2-U1 12,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM
Indoor Unit: MSZ-HM12NA-U1
Outdoor Unit: MUZ-HM12NA2-U1Wireless Remote Controller
ACCESSORIES:Indoor Unit
□ Condensate Pump (BlueDiamond X87-711/721; 115/230V) □ Condensate Pump (Sauermann SI30-115/230; 115/230V) □ Anti-Allergy Enzyme Filter (MAC-408FT-E) □ Drain Pan Level Sensor (DPLS2)
Outdoor Unit
□ Outdoor Mounting Pad (ULTRILITE1) □ Drain Pan Heater (MAC-640BH-U) □ 3-1/4” Mounting Base [Pair] (DSD-400P) □ Drain Pan Socket (MAC-860DS) □ Air Outlet Guide (MAC-889SG) □ Wall Mounting Bracket (QSWB2000M-1)
SPECIFICATIONS:
Rated Conditions (Capacity / Input)
Cooling1 Btu/h / W 12,000 / 1,210
Heating at 47º F2 Btu/h / W 12,200 / 990
Capacity Range Minimum Maximum
Cooling1 Btu/h 3,800 12,200
Heating at 47º F2 Btu/h 4,500 14,500
Heating at 17º F3 Btu/h - 9,000
Heating at 5º F4 Btu/h - 7,5001 Cooling | Indoor: 80º F(27º C)DB / 67º F(19º C)WB; Outdoor: 95º F(35º C)DB / 75º F(24º C)WB* 2 Heating at 47ºF | Indoor: 70º F (21º C)DB / 60º F (16º C)WB; Outdoor: 47º F (8º C)DB / 43º F (6º C)WB* 3 Heating at 17º F | Indoor: 70º F(21º C)DB / 60º F(16º C)WB; Outdoor: 17º F(-8º C)DB / 15º F(-9º C)WB* 4 Heating at 5º F | Indoor: 70º F (21º C)DB / 60º F(16º C)WB; Outdoor: 5º F(-15º C) DB / 5º F(-15º C)WB * Rating Conditions per AHRI Standard:
Operating Conditons (Indoor Intake Air Temp.) (Max./ Min.)
Cooling 90º F (32º C) DB / 67º F (19º C) DB
Heating 80º F (27º C) DB / 70º F (21º C) DB
Operating Conditons (Outdoor Intake Air Temp.) (Max./ Min.)
Cooling5 115 F (46º C) DB / 14º F (-10º C) DB
Heating 75º F (24º C) DB / 5º F (-15º C) DB**
5 Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.** System cuts out at -9º F (-27º C) to avoid thermistor error and automatically restarts at -4º F (-20º C).
AHRI Efficiency Ratings
SEER / HSPF 18 / 8.5
COP at 47o F / 17o F 3.61 / 2.78
Electrical Power Requirements 208 / 230V, 1-Phase, 60 Hz
Minimum Circuit Ampacity (MCA)
Indoor / Outdoor A 1.0 / 9
Indoor Unit
Blower Motor (ECM) F.L.A. 0.76
Blower Motor Output W 30
SHF / Moisture Removal 0.77 / 2.5 pt./h
Field Drainpipe Size O.D. In.(mm) 5/8 (15)
Outdoor Unit
Compressor DC INVERTER-driven Twin Rotary
Fan Motor (ECM) F.L.A. 0.5
Airflow Rate (Lo - Med - Hi - Super Hi)
Indoor (Cooling)
DRY
CFM
170-237-321-399
WET 134-201-286-364
Indoor (Heating) DRY 170-237-321-406
Outdoor 1,243 / 1,229
Sound Pressure Level (Lo - Med - Hi - Super Hi)
IndoorCooling
dB(A)
22-30-37-45
Heating 22-30-37-43
OutdoorCooling 49
Heating 51
External Dimensions
Indoor (H x W x D)
In.(mm)
11-5/8 x 31-7/16 x 9-1/8 (295 x 798 x 232)
Outdoor (H x W x D) 21-5/8 x 31-1/2 x 11-1/4 (550 x 800 x 285)
Net Weight
IndoorLbs.(kg)
22 (10)
Outdoor 73 (33)
External Finish
Indoor Munsell 1.0Y 9.2 / 0.2
Outdoor Munsell No. 3Y 7.8 / 1.1
Refrigerant R410A; 1 lb. 12 oz.
Refrigerant Piping (Flared)
Liquid (High Pressure)In.(mm)
1/4 (6.35)
Gas (Low Pressure) 3/8 (9.52)
Max. Total Refrigerant Pipe Length (Height Diff.)
Ft. (m)
40 (12)
Max. Total Refrigerant Pipe Length (Length.) 65 (20)
Specifications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
1340 Satellite Boulevard. Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com
FORM# MSZ-HM12NA-U1 / MUZ-HM12NA2-U1 - 201611
DIMENSIONS: MSZ-HM12NA-U1 & MUZ-HM12NA2-U1MSZ-HM12NA-U1
MUZ-HM12NA2-U1
Unit: in. (mm)
Unit: in. (mm)
9
OUTLINES AND DIMENSIONS4
Unit: inchMUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
clea
r *1
*1 4 in. (100 mm) or more when front and sides of the unit are clear
*2 When any 2 sides of left, right and rear of the unit are clear
holes
REQUIRED SPACE
Liquid refrigerant pipe jointRefrigerant pipe (flared) Ø 1/4
Gas refrigerant pipe jointRefrigerant pipe (flared) Ø 3/8 (HM09/12) Ø 1/2 (HM15/18)
4 in. (100 mm)
or more
14 in. (350 mm)or more8 in. (200 mm)
or more *2
4 in. (100 mm)or more
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
OBH747A
7
Unit: inchMSZ-HM09NA MSZ-HM12NA MSZ-HM15NA
MSZ-HM18NA MSZ-HM24NA
4 OUTLINES AND DIMENSIONS
Pipi
ng InsulationMSZ-HM24NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø3/8)
Gas line Ø15/32 13-3/8 (Flared connection Ø5/8)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
Pipi
ng InsulationMSZ-HM18NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø1/4)
Gas line Ø15/32 13-3/8 (Flared connection Ø1/2)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
11/16
5-1/2
2-1/4
2-1/4 2-1/2
9-13/163/16
35-13/1636-5/16
1/4
27-15/16 6-5/162-1/16
12
2-9/16
2-13
/16
2-1/2
2-9/163-11/16
2-1/1
6
9-7/1
610
-5/16
1/8
8-7/8 8-7/83-11/16
8-3/410
-3/8
2-5/16 15-7/8
8-11/16
3-11/16
7/8
1×7/16 Oblong hole
7/16×13/16Oblong holeInstallation plate
Indoor unit
Wall hole Ø3Air in
Installation plate
8-1/16
15-3/161-5/8
8-11
/16
3 1-11
/16
2-9/16
2-9/1
6
4-1/25-3/4
1/4
Air out
Piping
Drain hose
3-15
/16
11/16
5-1/2
2-1/4
Pip
ing
Insulation ø1 - 3/8 O.DLiquid line ø1/4 19 - 11/16 (Flared connection ø1/4)Gas line ø3/8 16 - 15/16
(Flared connection: ø3/8 (HM09/12NA), ø1/2 (HM15NA))Drain hose Insulation ø1-1/8 O.D Connected part ø5/8 O.D
OBH746A
M-SERIES
Specifications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
Job Name:
System Reference: Date:
SUBMITTAL DATA: MSZ-HM15NA-U1 & MUZ-HM15NA2-U1 15,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM
Indoor Unit: MSZ-HM15NA-U1
Outdoor Unit: MUZ-HM15NA2-U1Wireless Remote Controller
ACCESSORIES:Indoor Unit
□ Condensate Pump (BlueDiamond X87-711/721; 115/230V) □ Condensate Pump (Sauermann SI30-115/230; 115/230V) □ Anti-Allergy Enzyme Filter (MAC-408FT-E) □ Drain Pan Level Sensor (DPLS2)
Outdoor Unit
□ Outdoor Mounting Pad (ULTRILITE1) □ Drain Pan Heater (MAC-640BH-U) □ 3-1/4” Mounting Base [Pair] (DSD-400P) □ Drain Pan Socket (MAC-860DS) □ Air Outlet Guide (MAC-889SG) □ Wall Mounting Bracket (QSWB2000M-1)
SPECIFICATIONS:
Rated Conditions (Capacity / Input)
Cooling1 Btu/h / W 14,000 / 1,170
Heating at 47º F2 Btu/h / W 18,000 / 1,600
Capacity Range Minimum Maximum
Cooling1 Btu/h 3,100 16,000
Heating at 47º F2 Btu/h 4,800 18,500
Heating at 17º F3 Btu/h - 14,000
Heating at 5º F4 Btu/h - 11,8001 Cooling | Indoor: 80º F(27º C)DB / 67º F(19º C)WB; Outdoor: 95º F(35º C)DB / 75º F(24º C)WB* 2 Heating at 47ºF | Indoor: 70º F (21º C)DB / 60º F (16º C)WB; Outdoor: 47º F (8º C)DB / 43º F (6º C)WB* 3 Heating at 17º F | Indoor: 70º F(21º C)DB / 60º F(16º C)WB; Outdoor: 17º F(-8º C)DB / 15º F(-9º C)WB* 4 Heating at 5º F | Indoor: 70º F (21º C)DB / 60º F(16º C)WB; Outdoor: 5º F(-15º C) DB / 5º F(-15º C)WB * Rating Conditions per AHRI Standard:
Operating Conditons (Indoor Intake Air Temp.) (Max./ Min.)
Cooling 90º F (32º C) DB / 67º F (19º C) DB
Heating 80º F (27º C) DB / 70º F (21º C) DB
Operating Conditons (Outdoor Intake Air Temp.) (Max./ Min.)
Cooling5 115 F (46º C) DB / 14º F (-10º C) DB
Heating 75º F (24º C) DB / 5º F (-15º C) DB**
5 Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.** System cuts out at -9º F (-27º C) to avoid thermistor error and automatically restarts at -4º F (-20º C).
AHRI Efficiency Ratings
SEER / HSPF 18 / 8.5
COP at 47o F / 17o F 3.30 / 2.55
Electrical Power Requirements 208 / 230V, 1-Phase, 60 Hz
Minimum Circuit Ampacity (MCA)
Indoor / Outdoor A 1 / 10
Indoor Unit
Blower Motor (ECM) F.L.A. 0.76
Blower Motor Output W 30
SHF / Moisture Removal 0.78 / 2.7 pt./h
Field Drainpipe Size O.D. In.(mm) 5/8 (15)
Outdoor Unit
Compressor DC INVERTER-driven Twin Rotary
Fan Motor (ECM) F.L.A. 0.5
Airflow Rate (Lo - Med - Hi - Super Hi)
Indoor (Cooling)
DRY
CFM
272-335-420-533
WET 237-300-385-498
Indoor (Heating) DRY 247-304-367-463
Outdoor 1,243 / 1,229
Sound Pressure Level (Lo - Med - Hi - Super Hi)
IndoorCooling
dB(A)
32-38-44-49
Heating 30-35-40-46
OutdoorCooling 49
Heating 51
External Dimensions
Indoor (H x W x D)
In.(mm)
11-5/8 x 31-7/16 x 9-1/8 (295 x 798 x 232)
Outdoor (H x W x D) 21-5/8 x 31-1/2 x 11-1/4 (550 x 800 x 285)
Net Weight
IndoorLbs.(kg)
22 (10)
Outdoor 81 (37)
External Finish
Indoor Munsell 1.0Y 9.2 / 0.2
Outdoor Munsell No. 3Y 7.8 / 1.1
Refrigerant R410A; 2 lb. 9 oz.
Refrigerant Piping (Flared)
Liquid (High Pressure)In.(mm)
1/4 (6.35)
Gas (Low Pressure) 1/2 (12.7)
Max. Total Refrigerant Pipe Length (Height Diff.)
Ft. (m)
40 (12)
Max. Total Refrigerant Pipe Length (Length.) 65 (20)
Specifications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
1340 Satellite Boulevard. Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com
FORM# MSZ-HM15NA-U1 / MUZ-HM15NA2-U1 - 201607
DIMENSIONS: MSZ-HM15NA-U1 & MUZ-HM15NA2-U1MSZ-HM15NA-U1
MUZ-HM15NA2-U1
Unit: in. (mm)
7
Unit: inchMSZ-HM09NA MSZ-HM12NA MSZ-HM15NA
MSZ-HM18NA MSZ-HM24NA
4 OUTLINES AND DIMENSIONS
Pipi
ng InsulationMSZ-HM24NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø3/8)
Gas line Ø15/32 13-3/8 (Flared connection Ø5/8)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
Pipi
ng InsulationMSZ-HM18NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø1/4)
Gas line Ø15/32 13-3/8 (Flared connection Ø1/2)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
11/16
5-1/2
2-1/4
2-1/4 2-1/2
9-13/163/16
35-13/1636-5/16
1/4
27-15/16 6-5/162-1/16
12
2-9/16
2-13
/16
2-1/2
2-9/163-11/16
2-1/1
6
9-7/1
610
-5/16
1/8
8-7/8 8-7/83-11/16
8-3/410
-3/8
2-5/16 15-7/8
8-11/16
3-11/16
7/8
1×7/16 Oblong hole
7/16×13/16Oblong holeInstallation plate
Indoor unit
Wall hole Ø3Air in
Installation plate
8-1/16
15-3/161-5/8
8-11
/16
3 1-11
/16
2-9/16
2-9/1
6
4-1/25-3/4
1/4
Air out
Piping
Drain hose
3-15
/16
11/16
5-1/2
2-1/4
Pip
ing
Insulation ø1 - 3/8 O.DLiquid line ø1/4 19 - 11/16 (Flared connection ø1/4)Gas line ø3/8 16 - 15/16
(Flared connection: ø3/8 (HM09/12NA), ø1/2 (HM15NA))Drain hose Insulation ø1-1/8 O.D Connected part ø5/8 O.D
OBH746A
Unit: in. (mm)
9
OUTLINES AND DIMENSIONS4
Unit: inchMUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
clea
r *1
*1 4 in. (100 mm) or more when front and sides of the unit are clear
*2 When any 2 sides of left, right and rear of the unit are clear
holes
REQUIRED SPACE
Liquid refrigerant pipe jointRefrigerant pipe (flared) Ø 1/4
Gas refrigerant pipe jointRefrigerant pipe (flared) Ø 3/8 (HM09/12) Ø 1/2 (HM15/18)
4 in. (100 mm)
or more
14 in. (350 mm)or more8 in. (200 mm)
or more *2
4 in. (100 mm)or more
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
OBH747A
M-SERIES
Specifications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
Job Name:
System Reference: Date:
SUBMITTAL DATA: MSZ-HM18NA-U1 & MUZ-HM18NA2-U1 18,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM
Indoor Unit: MSZ-HM18NA-U1
Outdoor Unit: MUZ-HM18NA2-U1Wireless Remote Controller
ACCESSORIES:Indoor Unit
□ Condensate Pump (BlueDiamond X87-711/721; 115/230V) □ Condensate Pump (Sauermann SI30-115/230; 115/230V) □ Anti-Allergy Enzyme Filter (MAC-408FT-E) □ Drain Pan Level Sensor (DPLS2)
Outdoor Unit
□ Outdoor Mounting Pad (ULTRILITE1) □ Drain Pan Heater (MAC-640BH-U) □ 3-1/4” Mounting Base [Pair] (DSD-400P) □ Drain Pan Socket (MAC-860DS) □ Air Outlet Guide (MAC-889SG) □ Wall Mounting Bracket (QSWB2000M-1)
SPECIFICATIONS:
Rated Conditions (Capacity / Input)
Cooling1 Btu/h / W 17,200 / 1,640
Heating at 47º F2 Btu/h / W 18,000 / 1,590
Capacity Range Minimum Maximum
Cooling1 Btu/h 5,800 18,000
Heating at 47º F2 Btu/h 5,400 20,900
Heating at 17º F3 Btu/h - 15,000
Heating at 5º F4 Btu/h - 12,7001 Cooling | Indoor: 80º F(27º C)DB / 67º F(19º C)WB; Outdoor: 95º F(35º C)DB / 75º F(24º C)WB* 2 Heating at 47ºF | Indoor: 70º F (21º C)DB / 60º F (16º C)WB; Outdoor: 47º F (8º C)DB / 43º F (6º C)WB* 3 Heating at 17º F | Indoor: 70º F(21º C)DB / 60º F(16º C)WB; Outdoor: 17º F(-8º C)DB / 15º F(-9º C)WB* 4 Heating at 5º F | Indoor: 70º F (21º C)DB / 60º F(16º C)WB; Outdoor: 5º F(-15º C) DB / 5º F(-15º C)WB * Rating Conditions per AHRI Standard:
Operating Conditons (Indoor Intake Air Temp.) (Max./ Min.)
Cooling 90º F (32º C) DB / 67º F (19º C) DB
Heating 80º F (27º C) DB / 70º F (21º C) DB
Operating Conditons (Outdoor Intake Air Temp.) (Max./ Min.)
Cooling5 115 F (46º C) DB / 14º F (-10º C) DB
Heating 75º F (24º C) DB / 5º F (-15º C) DB**
5 Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.** System cuts out at -9º F (-27º C) to avoid thermistor error and automatically restarts at -4º F (-20º C).
AHRI Efficiency Ratings
SEER / HSPF 18.0 / 8.5
COP at 47o F / 17o F 3.32 / 2.59
Electrical Power Requirements 208 / 230V, 1-Phase, 60 Hz
Minimum Circuit Ampacity (MCA)
Indoor / Outdoor A 1 / 10
Indoor Unit
Blower Motor (ECM) F.L.A. 0.67
Blower Motor Output W 30
SHF / Moisture Removal 0.86 / 2.1 pt./h
Field Drainpipe Size O.D. In.(mm) 5/8 (15)
Outdoor Unit
Compressor DC INVERTER-driven Twin Rotary
Fan Motor (ECM) F.L.A. 0.5
Airflow Rate (Lo - Med - Hi - Super Hi)
Indoor (Cooling)
DRY
CFM
328-431-530-625
WET 295-388-477-562
Indoor (Heating) DRY 307-431-530-625
Outdoor 1,243 / 1,229
Sound Pressure Level (Lo - Med - Hi - Super Hi)
IndoorCooling
dB(A)
30-37-42-47
Heating 30-37-42-47
OutdoorCooling 49
Heating 51
External Dimensions
Indoor (H x W x D)
In.(mm)
12 x 36-5/16 x 9-13/16 (305 x 923 x 250)
Outdoor (H x W x D) 21-5/8 x 31-1/2 x 11-1/4 (550 x 500 x 285)
Net Weight
IndoorLbs.(kg)
28 (13)
Outdoor 81 (37)
External Finish
Indoor Munsell 1.0Y 9.2 / 0.2
Outdoor Munsell No. 3Y 7.8 / 1.1
Refrigerant R410A; 2 lb. 10 oz.
Refrigerant Piping (Flared)
Liquid (High Pressure)In.(mm)
1/4 (6.35)
Gas (Low Pressure) 1/2 (12.7)
Max. Total Refrigerant Pipe Length (Height Diff.)
Ft. (m)
40 (12)
Max. Total Refrigerant Pipe Length (Length.) 65 (20)
Specifications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
1340 Satellite Boulevard. Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com
FORM# MSZ-HM18NA-U1 ~ MUZ-HM18NA2-U1 - 201603
DIMENSIONS: MSZ-HM18NA-U1 & MUZ-HM18NA2-U1MSZ-HM18NA-U1 Unit: in. (mm)
MUZ-HM18NA2-U1Unit: in. (mm)
7
Unit: inchMSZ-HM09NA MSZ-HM12NA MSZ-HM15NA
MSZ-HM18NA MSZ-HM24NA
4 OUTLINES AND DIMENSIONS
Pipi
ng InsulationMSZ-HM24NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø3/8)
Gas line Ø15/32 13-3/8 (Flared connection Ø5/8)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
Pipi
ng InsulationMSZ-HM18NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø1/4)
Gas line Ø15/32 13-3/8 (Flared connection Ø1/2)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
11/16
5-1/2
2-1/4
2-1/4 2-1/2
9-13/163/16
35-13/1636-5/16
1/4
27-15/16 6-5/162-1/16
12
2-9/162-
13/16
2-1/2
2-9/163-11/16
2-1/1
6
9-7/1
610
-5/16
1/8
8-7/8 8-7/83-11/16
8-3/410
-3/8
2-5/16 15-7/8
8-11/16
3-11/16
7/8
1×7/16 Oblong hole
7/16×13/16Oblong holeInstallation plate
Indoor unit
Wall hole Ø3Air in
Installation plate
8-1/16
15-3/161-5/8
8-11
/16
3 1-11
/16
2-9/16
2-9/1
6
4-1/25-3/4
1/4
Air out
Piping
Drain hose
3-15
/16
11/16
5-1/2
2-1/4
Pip
ing
Insulation ø1 - 3/8 O.DLiquid line ø1/4 19 - 11/16 (Flared connection ø1/4)Gas line ø3/8 16 - 15/16
(Flared connection: ø3/8 (HM09/12NA), ø1/2 (HM15NA))Drain hose Insulation ø1-1/8 O.D Connected part ø5/8 O.D
OBH746A
9
OUTLINES AND DIMENSIONS4
Unit: inchMUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
clea
r *1
*1 4 in. (100 mm) or more when front and sides of the unit are clear
*2 When any 2 sides of left, right and rear of the unit are clear
holes
REQUIRED SPACE
Liquid refrigerant pipe jointRefrigerant pipe (flared) Ø 1/4
Gas refrigerant pipe jointRefrigerant pipe (flared) Ø 3/8 (HM09/12) Ø 1/2 (HM15/18)
4 in. (100 mm)
or more
14 in. (350 mm)or more8 in. (200 mm)
or more *2
4 in. (100 mm)or more
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
OBH747A
M-SERIES
Specifications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
Job Name:
System Reference: Date:
SUBMITTAL DATA: MSZ-HM24NA-U1 & MUZ-HM24NA-U1 24,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM
Indoor Unit: MSZ-HM24NA-U1
Outdoor Unit: MUZ-HM24NA-U1Wireless Remote Controller
ACCESSORIES:Indoor Unit
□ Condensate Pump (BlueDiamond X87-711/721; 115/230V) □ Condensate Pump (Sauermann SI30-115/230; 115/230V) □ Anti-Allergy Enzyme Filter (MAC-408FT-E) □ Drain Pan Level Sensor (DPLS2)
Outdoor Unit
□ Outdoor Mounting Pad (ULTRILITE1) □ Drain Pan Heater (MAC-642BH-U) □ 3-1/4” Mounting Base [Pair] (DSD-400P) □ Drain Pan Socket (MAC-851DS) □ Air Outlet Guide (MAC-886SG-E) □ Wall Mounting Bracket (QSWB2000M-1)
SPECIFICATIONS:
Rated Conditions (Capacity / Input)
Cooling1 Btu/h / W 22,500 / 2,630
Heating at 47º F2 Btu/h / W 26,000 / 2,500
Capacity Range Minimum Maximum
Cooling1 Btu/h 5,800 22,500
Heating at 47º F2 Btu/h 5,400 26,000
Heating at 17º F3 Btu/h - 18,500
Heating at 5º F4 Btu/h - 15,0001 Cooling | Indoor: 80º F(27º C)DB / 67º F(19º C)WB; Outdoor: 95º F(35º C)DB / 75º F(24º C)WB* 2 Heating at 47ºF | Indoor: 70º F (21º C)DB / 60º F (16º C)WB; Outdoor: 47º F (8º C)DB / 43º F (6º C)WB* 3 Heating at 17º F | Indoor: 70º F(21º C)DB / 60º F(16º C)WB; Outdoor: 17º F(-8º C)DB / 15º F(-9º C)WB* 4 Heating at 5º F | Indoor: 70º F (21º C)DB / 60º F(16º C)WB; Outdoor: 5º F(-15º C) DB / 5º F(-15º C)WB * Rating Conditions per AHRI Standard:
Operating Conditons (Indoor Intake Air Temp.) (Max./ Min.)
Cooling 90º F (32º C) DB / 67º F (19º C) DB
Heating 80º F (27º C) DB / 70º F (21º C) DB
Operating Conditons (Outdoor Intake Air Temp.) (Max./ Min.)
Cooling5 115 F (46º C) DB / 14º F (-10º C) DB
Heating 75º F (24º C) DB / -4º F (-20º C) DB**
5 Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.** System cuts out at -9º F (-27º C) to avoid thermistor error and automatically restarts at -4º F (-20º C).
AHRI Efficiency Ratings
SEER / EER / HSPF 18.0 / 8.6 / 9.5
COP at 47o F / 17o F 3.05 / 2.36
Electrical Power Requirements 208 / 230V, 1-Phase, 60 Hz
Minimum Circuit Ampacity (MCA)
Indoor / Outdoor A 1 / 14
Indoor Unit
Blower Motor (ECM) F.L.A. 0.67
Blower Motor Output W 30
SHF / Moisture Removal 0.87 / 2.3 pt./h
Field Drainpipe Size O.D. In.(mm) 5/8 (15)
Outdoor Unit
Compressor DC INVERTER-driven Twin Rotary
Fan Motor (ECM) F.L.A. 0.93
Airflow Rate (Lo - Med - Hi - Super Hi)
Indoor (Cooling)
DRY
CFM
353-431-530-702
WET 318-388-477-632
Indoor (Heating) DRY 346-448-579-702
Outdoor 1,691 / 1,691
Sound Pressure Level (Lo - Med - Hi - Super Hi)
IndoorCooling
dB(A)
33-38-44-50
Heating 32-38-44-50
OutdoorCooling 54
Heating 55
External Dimensions
Indoor (H x W x D)
In.(mm)
12 x 36-5/16 x 9-13/16 (305 x 923 x 250)
Outdoor (H x W x D) 34-5/8 x 33-1/16 x 13 (880 x 840 x 330)
Net Weight
IndoorLbs.(kg)
28 (13)
Outdoor 121 (55)
External Finish
Indoor Munsell 1.0Y 9.2 / 0.2
Outdoor Munsell No. 3Y 7.8 / 1.1
Refrigerant R410A; 3 lb. 9 oz.
Refrigerant Piping (Flared)
Liquid (High Pressure)In.(mm)
3/8 (9.52)
Gas (Low Pressure) 5/8 (15.88)
Max. Total Refrigerant Pipe Length (Height Diff.)
Ft. (m)
50 (15)
Max. Total Refrigerant Pipe Length (Length.) 100 (30)
Specifications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
1340 Satellite Boulevard. Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com
FORM# MSZ-HM24NA-U1 / MUZ-HM24NA-U1 - 201705
DIMENSIONS: MSZ-HM24NA-U1 & MUZ-HM24NA-U1MSZ-HM24NA-U1
MUZ-HM24NA-U1
Unit: in. (mm)
10
MUZ-HM24NA MUZ-HM24NA2 Unit: inch
16-7/16
1-9/161-5/8Drain hole
6-7/8 19-11/16
13
2
Air in
Air in
Air out2-holes 13/32 13/16
14-3
/16
33-1/164-5/16
3-3/16
34-5
/8
17-2
5/32
Service panel
3-29
/32
6-1/
2
7-11/16
35
44
Liquid refrigerant pipe jointRefrigerant pipe (flared) Ø 3/8
Gas refrigerant pipe jointRefrigerant pipe (flared) Ø 5/8
*1 20 in. (500 mm) or more when front and sides of the unit are clear
14 in. (350 mm)
or more
4 in. (100 mm)
or more
REQUIRED SPACE
Cle
ar *
1
4 in. (100 mm)
or more
20 in. (500 mm)
or more *2
*2 When any 2 sides of left, right and rear of the unit are clear
OBH747A
7
Unit: inchMSZ-HM09NA MSZ-HM12NA MSZ-HM15NA
MSZ-HM18NA MSZ-HM24NA
4 OUTLINES AND DIMENSIONS
Pipi
ng InsulationMSZ-HM24NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø3/8)
Gas line Ø15/32 13-3/8 (Flared connection Ø5/8)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
Pipi
ng InsulationMSZ-HM18NA
Ø2 O.DLiquid line Ø5/16 15-3/8 (Flared connection Ø1/4)
Gas line Ø15/32 13-3/8 (Flared connection Ø1/2)Drain hose Insulation Ø1-1/8 Connected part Ø5/8 O.D
11/16
5-1/2
2-1/4
2-1/4 2-1/2
9-13/163/16
35-13/1636-5/16
1/4
27-15/16 6-5/162-1/16
12
2-9/162-
13/16
2-1/2
2-9/163-11/16
2-1/1
6
9-7/1
610
-5/16
1/8
8-7/8 8-7/83-11/16
8-3/410
-3/8
2-5/16 15-7/8
8-11/16
3-11/16
7/8
1×7/16 Oblong hole
7/16×13/16Oblong holeInstallation plate
Indoor unit
Wall hole Ø3Air in
Installation plate
8-1/16
15-3/161-5/8
8-11
/16
3 1-11
/16
2-9/16
2-9/1
6
4-1/25-3/4
1/4
Air out
Piping
Drain hose
3-15
/16
11/16
5-1/2
2-1/4
Pip
ing
Insulation ø1 - 3/8 O.DLiquid line ø1/4 19 - 11/16 (Flared connection ø1/4)Gas line ø3/8 16 - 15/16
(Flared connection: ø3/8 (HM09/12NA), ø1/2 (HM15NA))Drain hose Insulation ø1-1/8 O.D Connected part ø5/8 O.D
OBH746AUnit: in. (mm)