OREGON OREGON OREGON 12/31/20 EXPIRES: 84929 J U N E 5 , 2 0 1 1 J A M E S M . M c C L E L L A N D E N G I N E E R R E G I S T E R E D P R O F E S S I O N A L COPYRIGHT 2019 STEELE ASSOCIATES ARCHITECTS All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution. ASSOCIATES ARCHITECTS LLC 686 NW YORK DRIVE SUITE 150 BEND, OR 97703 541.382.9867 FAX 541.385.8816 [email protected] COOS BAY OREGON JOB NO. DATE DRAWN BY CHECKED BY SHEET NO. 2/11/2020 9:44:28 AM M001 JMM JK 18113.01 BID SET - FEBRUARY 13, 2020 SYMBOLS LIST AND GENERAL NOTES - MECHANICAL SYMBOLS LIST AND GENERAL NOTES - MECHANICAL 04/19/2019 755 S 7TH ST. Marshfield Jr. High School GENERAL MECHANICAL NOTES M001 SYMBOLS LIST AND GENERAL NOTES - MECHANICAL M002 SCHEDULES - MECHANICAL M003 SCHEDULES - MECHANICAL M101 FIRST FLOOR ZONING PLAN - MECHANICAL M102 SECOND FLOOR ZONING PLANS - MECHANICAL M103 THIRD FLOOR ZONING PLANS - MECHANICAL M201 FIRST FLOOR PLAN - MECHANICAL M202 SECOND FLOOR PLAN - MECHANICAL M203 THIRD FLOOR PLAN - MECHANICAL M205 ROOF PLAN - MECHANICAL M401 MECHANICAL SECTIONS AND ISOMETRICS M402 MECHANICAL SECTIONS AND ISOMETRICS M701 DETAILS - MECHANICAL M702 DETAILS - MECHANICAL M703 AHU DETAILS - MECHANICAL M801 CONTROL DIAGRAMS - MECHANICAL M802 CONTROL DIAGRAMS - MECHANICAL M803 CONTROL DIAGRAMS - MECHANICAL M804 CONTROL DIAGRAMS - MECHANICAL SHEET INDEX MECHANICAL SYMBOL LIST NOTE: This is a standard symbol list and not all items listed may be used. Abbreviations AFF ABOVE FINISHED FLOOR AD ACCESS DOOR A/C AIR CONDITION(ED) AHU AIR HANDLING UNIT BDD BACKDRAFT DAMPER BFP BACKFLOW PREVENTER BFF BELOW FINISHED FLOOR B BOILER BHP BRAKE HORSEPOWER CD CEILING DIFFUSER CH CEILING HEATER CL CENTERLINE CV CHECK VALVE COP COEFFICIENT OF PERFORMANCE CW COLD WATER CD CONDENSATE DRAIN CU CONDENSING UNIT CONT. CONTINUATION DB DECIBEL DP DEW POINT, DIFFERENTIAL PRESSURE DIA DIAMETER DX DIRECT EXPANSION DG DOOR GRILLE D DROP DB DRY BULB EFF EFFICIENT ELECT ELECTRICAL EL ELEVATION EER ENERGY EFFICIENCY RATING EAT ENTERING AIR TEMPERATURE EWT ENTERING WATER TEMPERATURE EXH EXHAUST EF EXHAUST FAN FA FACE AREA F FAHRENHEIT FC FAN COIL FT FEET FPM FEET PER MINUTE FPS FEET PER SECOND FPI FINS PER INCH FD FIRE DAMPER FC FLEXIBLE CONNECTOR FLA FULL LOAD AMPS GAL GALLONS GPH GALLONS PER HOUR GPM GALLONS PER MINUTE HD HEAD HP HEAT PUMP HTR HEATER HTG HEATING HP HORSEPOWER IN INCHES ID INSIDE DIAMETER IE INVERT ELEVATION KW KILOWATT LH LATENT HEAT LAT LEAVING AIR TEMPERATURE MAX MAXIMUM MIN MINIMUM MA MIXED AIR MS MOTOR STARTER MD MOTORIZED DAMPER MH MOUNTING HEIGHT (N) NEW NC NOISE CRITERIA N/A NOT APPLICABLE NIC NOT IN CONTRACT NTS NOT TO SCALE NO. NUMBER OC ON CENTER OBD OPPOSED BLADE DAMPER OA OUTSIDE AIR OD OUTSIDE DIAMETER PH PHASE LBS. POUNDS PSI POUNDS PER SQUARE INCH PD PRESSURE DROP PRV PRESSURE REDUCING VALVE P PUMP QTY QUANTITY REF REFRIGERANT RL REFRIGERANT LIQUID RS REFRIGERANT SUCTION RH RELATIVE HUMIDITY RLD RELIEF DAMPER (R) RELOCATE/RELOCATED LOCATION RET RETURN RA RETURN AIR RPM REVOLUTIONS PER MINUTE R RISE SEER SEASONAL ENERGY EFFICIENCY RATING SH SENSIBLE HEAT SOV SHUT OFF VALVE SF SQUARE FEET SP STATIC PRESSURE SA SUPPLY AIR T, TEMP TEMPERATURE TD TEMPERATURE DIFFERENCE MBH THOUSAND BTU'S PER HOUR TH TOTAL HEAT TP TOTAL PRESSURE TYP TYPICAL UD UNDERCUT DOOR VAV VARIABLE AIR VOLUME VEL VELOCITY V VOLT VD VOLUME DAMPER (HAND OPERATOR) WC WATER COLUMN W WATT WB WET BULB W/ WITH PROJECT CONTACT www.interfaceengineering.com John Kotas 2018-0244 100 SW Main Street, Suite 1600 Portland, OR 97204 TEL 503.382.2266 A. CONSULT ALL DRAWINGS AND SPECIFICATIONS IN THIS PROJECT AND BECOME FAMILIAR WITH ALL EQUIPMENT TO BE INSTALLED. COORDINATE ALL ASPECTS OF THE CONSTRUCTION WITH THE OTHER TRADES ON THE JOB TO ENSURE THAT ALL WORK AND MATERIALS REQUIRED TO PROVIDE A COMPLETE AND OPERATIONAL FACILITY ARE INCLUDED IN THE BID. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. B. COORDINATE INSTALLATION OF DUCTWORK, PIPING, FIXTURES, EQUIPMENT, ETC. WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL AND FIRE PROTECTION SYSTEMS PRIOR TO INSTALLATION. C. PROVIDE CEILING ACCESS PANELS FOR ALL DUCT DAMPERS OR CONCEALED VOLUME DAMPER REGULATORS LOCATED ABOVE INACCESSIBLE CEILING SYSTEMS. MAINTAIN FIRE RATINGS WHERE REQUIRED. D. INSTALL THERMOSTATS AT 4' - 0" A.F.F. PER ADA REQUIREMENTS UNLESS OTHERWISE NOTED ON DRAWINGS. 4' - 0" DIMENSION TO BE TO THE TOP OF THE THERMOSTAT. E. COORDINATE EXACT LOCATION OF ALL CEILING GRILLES AND DIFFUSERS WITH ARCHITECTURAL REFLECTED CEILING PLAN, ARCHITECTURAL INTERIOR ELEVATIONS, LIGHTING, AND STRUCTURAL CONDITIONS.ARCHITECTURAL PLANS TO PROVIDE FINAL GRILLE AND DIFFUSER LOCATIONS IN THE EVENT OF A CONFLICT. F. ALL WORK PERFORMED AND MATERIAL SUPPLIED SHALL CONFORM TO ALL STATE AND LOCAL CODES AND ALL OTHER APPLICABLE LAWS AND STATE REGULATIONS INCLUDING APPLICABLE SEISMIC ZONE REQUIREMENTS. G. MAINTAIN ALL OUTSIDE AIR INTAKE OPENINGS MINIMUM 10' - 0" FROM ALL MECHANICAL VENTS, PLUMBING VENTS AND EXHAUST FANS. H. CONTRACTOR TO TEMPORARILY INSTALL 2" THICK 60% EFFICIENT FILTERS AT ALL RETURN AIR GRILLE LOCATIONS. FILTERS TO BE REMOVED AT CONCLUSION OF CONSTRUCTION. I. PAINT ALL DIFFUSERS, REGISTERS AND GRILLES PER ARCHITECTURAL INSTRUCTIONS. ANY GRILLES INSTALLED IN GYPSUM BOARD WALLS AND CEILINGS ARE TO BE FURNISHED WITH FACTORY MILL OR PRIMER FINISH, READY FOR PAINTING IN THE FIELD. J. DIFFUSER/GRILLE RUNOUTS ARE SAME SIZE AS DIFFUSER/GRILLE NECK SIZE UNLESS OTHERWISE NOTED ON PLANS. K. MAINTAIN REQUIRED CLEARANCES TO COMBUSTIBLE CONSTRUCTION AS SPECIFIED IN THE LISTING AND MANUFACTURER'S INSTRUCTIONS. L. EQUIPMENT TO BE ACCESSIBLE FOR INSPECTION, SERVICE, REPAIR AND REPLACEMENT WITHOUT REMOVING WITHOUT REMOVING PERMANENT CONSTRUCTION, OTHER EQUIPMENT, VENTING SYSTEMS, PIPING, OR DUCTS CONNECTED TO THE EQUIPMENT BEING SERVICED. M. MAINTAIN MINIMUM DISTANCE OF 3' - 0" BETWEEN ALL EXHAUST OUTLETS AND DOORS/OPERABLE WINDOWS. N. PROVIDE ONE BALANCING DAMPER FOR EACH AIR INLET/ OUTLET SHOWN ON PLAN. WHERE DAMPER IS LOCATED ABOVE A HARD LID CEILING, PROVIDE REMOTE CABLE CONTROL FOR DAMPER. O. FOR ALL DUCT CONNECTIONS TO MECHANICAL EQUIPMENT, PROVIDE TRANSITION FROM DUCT SIZE SHOWN TO EQUIPMENT CONNECTION SIZE. P. PROVIDE WALL MOUNTED THERMOSTAT FOR ALL MECHANICAL EQUIPMENT EXCEPT ELECTRIC WALL HEATERS. Q. ADJUST THROW OF ALL AIR DEVICES TO NOT INTERFERE WITH LIGHTING. R. FAN COIL UNITS (FC - X) IN MDF, IDF, TELE, AND ELEVATOR MACHINE ROOMS ARE NOT TO BE LOCATED DIRECTLY OVER EQUIPMENT IN THE SPACE. S. INSTALL ALL EQUIPMENT SUCH THAT MANUFACTURER RECOMMENDED CLEARANCES ARE MAINTAINED. T. PROVIDE ALUMINUM DUCT IN ANY WET OR MOIST LOCATIONS. U. PROVIDE CO2 SENSOR ADJACENT TO ROOM TEMPERATURE SENSOR FOR ALL SPACES WITH DEMAND CONTROLLED VENTILATION. INSTALL SENSORS BETWEEN 3 FT AND 6 FT AFF. DCV CONTROLS MAINTAIN SYSTEM VENTILATION RATE. V. DETAILS APPLY WHETHER REFERENCED ON THE DRAWINGS OR NOT. W. ALL REVIEWED DOCUMENTS SHALL BE KEPT AT THE SITE OF WORK AND AVAILABLE AT THE TIME OF EACH INSPECTION. OSSC SECTION 107.3.1 X. ALL FIRESTOPPING ASSEMBLY PENETRATIONS SHALL COMPLY WITH 2014 OSSC SECTIONS 714, 715, AND 717. REFER TO SPEC BOOK DIVISION 07 8400 "FIRESTOPPING" FOR APPROVED LISTED PENETRATION SYSTEMS. AT THE TIME OF INSPECTION PROVIDE CUTSHEETS TO THE AHJ OF SYSTEMS USED FOR EACH TYPE OF PENETRATION. Y. MAINTAIN DISTANCE OF 10' MINIMUM FROM EDGE OF ROOF FOR ALL ROOF MOUNTED EQUIPMENT. Z. PROVIDE ESCUTCHEONS FOR ALL CONDUIT, PIPE, AND DUCT PENETRATIONS THROUGH CONCRETE AND FRAMED WALLS TO CONCEAL ROUGH OPENINGS. SYMMETRICAL WYE MITERED ELBOW WITH TURNING VANES RADIUSED ELBOW General NEW WORK RECTANGULAR DUCT SIZING ROUND DUCT SIZING Piping Fittings, Appurtenances and Equipment CAP CONTINUATION EXPANSION JOINT HOSE BIBB PIPE DROP PIPE RISE PIPE TO DRAIN PRESSURE GAUGE WITH COCK PRESSURE RELIEF VALVE PRESSURE SENSOR SHOCK ABSORBER T&P RELIEF VALVE WITH PIPE TO DRAIN TEE DOWN ON PIPE TEE UP ON PIPE TEMPERATURE SENSOR TEST PORT (PETE'S PLUG OR EQUAL) THERMOMETER VENT TO ATMOSPHERE Piping Systems REFRIGERANT LIQUID REFRIGERANT SUCTION Piping Valves VALVE, GENERAL Control Symbols CARBON DIOXIDE SENSOR ROOM THERMOSTAT TEMPERATURE SENSOR Dampers FIRE DAMPER FIRE/SMOKE DAMPER MOTORIZED DAMPER SMOKE DAMPER VOLUME DAMPER Diffusers and Grilles DIFFUSER OR GRILLE IDENTIFICATION EXHAUST AIR RETURN AIR SUPPLY AIR Ductwork Fittings ACOUSTICALLY LINED DUCT (SIZES SHOWN ARE NET INSIDE) BELLMOUTH CONCENTRIC SQUARE TO ROUND CONCENTRIC TRANSITION, RECTANGULAR OR ROUND ECCENTRIC TRANSITION, RECTANGULAR OR ROUND FLEXIBLE CONNECTION NON-SYMMETRICAL WYE RECTANGULAR DUCT DROP RECTANGULAR DUCT RISER RECTANGULAR MAIN WITH RECTANGULAR BRANCH RECTANGULAR MAIN WITH ROUND BRANCH RECTANGULAR OFFSET LESS THAN 15%%d RECTANGULAR OFFSET MORE THAN 15%%d ROUND DUCT DROP ROUND DUCT RISER ROUND DUCT WITH ROUND BRANCH ROUND WYE REV. DATE DESCRIPTION
Transcript
Page 1: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:2

8 A

M

M001

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

SY

MB

OLS

LIS

T A

ND

GE

NE

RA

L N

OT

ES

-M

EC

HA

NIC

AL

SYMBOLS LIST ANDGENERAL NOTES -MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

GENERAL MECHANICAL NOTES

M001 SYMBOLS LIST AND GENERAL NOTES - MECHANICAL

M002 SCHEDULES - MECHANICAL

M003 SCHEDULES - MECHANICAL

M101 FIRST FLOOR ZONING PLAN - MECHANICAL

M102 SECOND FLOOR ZONING PLANS - MECHANICAL

M103 THIRD FLOOR ZONING PLANS - MECHANICAL

M201 FIRST FLOOR PLAN - MECHANICAL

M202 SECOND FLOOR PLAN - MECHANICAL

M203 THIRD FLOOR PLAN - MECHANICAL

M205 ROOF PLAN - MECHANICAL

M401 MECHANICAL SECTIONS AND ISOMETRICS

M402 MECHANICAL SECTIONS AND ISOMETRICS

M701 DETAILS - MECHANICAL

M702 DETAILS - MECHANICAL

M703 AHU DETAILS - MECHANICAL

M801 CONTROL DIAGRAMS - MECHANICAL

M802 CONTROL DIAGRAMS - MECHANICAL

M803 CONTROL DIAGRAMS - MECHANICAL

M804 CONTROL DIAGRAMS - MECHANICAL

SHEET INDEX

MECHANICAL SYMBOL LISTNOTE: This is a standard symbol list and not all items listed may be used.

AbbreviationsAFF ABOVE FINISHED FLOOR

AD ACCESS DOOR

A/C AIR CONDITION(ED)

AHU AIR HANDLING UNIT

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BFF BELOW FINISHED FLOOR

B BOILER

BHP BRAKE HORSEPOWER

CD CEILING DIFFUSER

CH CEILING HEATER

CL CENTERLINE

CV CHECK VALVE

COP COEFFICIENT OF PERFORMANCE

CW COLD WATER

CD CONDENSATE DRAIN

CU CONDENSING UNIT

CONT. CONTINUATION

DB DECIBEL

DP DEW POINT, DIFFERENTIAL PRESSURE

DIA DIAMETER

DX DIRECT EXPANSION

DG DOOR GRILLE

D DROP

DB DRY BULB

EFF EFFICIENT

ELECT ELECTRICAL

EL ELEVATION

EER ENERGY EFFICIENCY RATING

EAT ENTERING AIR TEMPERATURE

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EF EXHAUST FAN

FA FACE AREA

F FAHRENHEIT

FC FAN COIL

FT FEET

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPI FINS PER INCH

FD FIRE DAMPER

FC FLEXIBLE CONNECTOR

FLA FULL LOAD AMPS

GAL GALLONS

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HD HEAD

HP HEAT PUMP

HTR HEATER

HTG HEATING

HP HORSEPOWER

IN INCHES

ID INSIDE DIAMETER

IE INVERT ELEVATION

KW KILOWATT

LH LATENT HEAT

LAT LEAVING AIR TEMPERATURE

MAX MAXIMUM

MIN MINIMUM

MA MIXED AIR

MS MOTOR STARTER

MD MOTORIZED DAMPER

MH MOUNTING HEIGHT

(N) NEW

NC NOISE CRITERIA

N/A NOT APPLICABLE

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NO. NUMBER

OC ON CENTER

OBD OPPOSED BLADE DAMPER

OA OUTSIDE AIR

OD OUTSIDE DIAMETER

PH PHASE

LBS. POUNDS

PSI POUNDS PER SQUARE INCH

PD PRESSURE DROP

PRV PRESSURE REDUCING VALVE

P PUMP

QTY QUANTITY

REF REFRIGERANT

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

RH RELATIVE HUMIDITY

RLD RELIEF DAMPER

(R) RELOCATE/RELOCATED LOCATION

RET RETURN

RA RETURN AIR

RPM REVOLUTIONS PER MINUTE

R RISE

SEER SEASONAL ENERGY EFFICIENCY RATING

SH SENSIBLE HEAT

SOV SHUT OFF VALVE

SF SQUARE FEET

SP STATIC PRESSURE

SA SUPPLY AIR

T, TEMP TEMPERATURE

TD TEMPERATURE DIFFERENCE

MBH THOUSAND BTU'S PER HOUR

TH TOTAL HEAT

TP TOTAL PRESSURE

TYP TYPICAL

UD UNDERCUT DOOR

VAV VARIABLE AIR VOLUME

VEL VELOCITY

V VOLT

VD VOLUME DAMPER (HAND OPERATOR)

WC WATER COLUMN

W WATT

WB WET BULB

W/ WITH

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

A. CONSULT ALL DRAWINGS AND SPECIFICATIONS IN THIS PROJECT AND BECOME FAMILIAR WITH ALL EQUIPMENT TO BE INSTALLED. COORDINATE ALL ASPECTS OF THE CONSTRUCTION WITH THE OTHER TRADES ON THE JOB TO ENSURE THAT ALL WORK AND MATERIALS REQUIRED TO PROVIDE A COMPLETE AND OPERATIONAL FACILITY ARE INCLUDED IN THE BID. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS.

B. COORDINATE INSTALLATION OF DUCTWORK, PIPING, FIXTURES, EQUIPMENT, ETC. WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL AND FIRE PROTECTION SYSTEMS PRIOR TO INSTALLATION.

C. PROVIDE CEILING ACCESS PANELS FOR ALL DUCT DAMPERS OR CONCEALED VOLUME DAMPER REGULATORS LOCATED ABOVE INACCESSIBLE CEILING SYSTEMS. MAINTAIN FIRE RATINGS WHERE REQUIRED.

D. INSTALL THERMOSTATS AT 4'-0" A.F.F. PER ADA REQUIREMENTS UNLESS OTHERWISE NOTED ON DRAWINGS. 4'-0" DIMENSION TO BE TO THE TOP OF THE THERMOSTAT.

E. COORDINATE EXACT LOCATION OF ALL CEILING GRILLES AND DIFFUSERS WITH ARCHITECTURAL REFLECTED CEILING PLAN, ARCHITECTURAL INTERIOR ELEVATIONS, LIGHTING, AND STRUCTURAL CONDITIONS.ARCHITECTURAL PLANS TO PROVIDE FINAL GRILLE AND DIFFUSER LOCATIONS IN THE EVENT OF A CONFLICT.

F. ALL WORK PERFORMED AND MATERIAL SUPPLIED SHALL CONFORM TO ALL STATE AND LOCAL CODES AND ALL OTHER APPLICABLE LAWS AND STATE REGULATIONS INCLUDING APPLICABLE SEISMIC ZONE REQUIREMENTS.

G. MAINTAIN ALL OUTSIDE AIR INTAKE OPENINGS MINIMUM 10'-0" FROM ALL MECHANICAL VENTS, PLUMBING VENTS AND EXHAUST FANS.

H. CONTRACTOR TO TEMPORARILY INSTALL 2" THICK 60% EFFICIENT FILTERS AT ALL RETURN AIR GRILLE LOCATIONS. FILTERS TO BE REMOVED AT CONCLUSION OF CONSTRUCTION.

I. PAINT ALL DIFFUSERS, REGISTERS AND GRILLES PER ARCHITECTURAL INSTRUCTIONS. ANY GRILLES INSTALLED IN GYPSUM BOARD WALLS AND CEILINGS ARE TO BE FURNISHED WITH FACTORY MILL OR PRIMER FINISH, READY FOR PAINTING IN THE FIELD.

J. DIFFUSER/GRILLE RUNOUTS ARE SAME SIZE AS DIFFUSER/GRILLE NECK SIZE UNLESS OTHERWISE NOTED ON PLANS.

K. MAINTAIN REQUIRED CLEARANCES TO COMBUSTIBLE CONSTRUCTION AS SPECIFIED IN THE LISTING AND MANUFACTURER'S INSTRUCTIONS.

L. EQUIPMENT TO BE ACCESSIBLE FOR INSPECTION, SERVICE, REPAIR AND REPLACEMENT WITHOUT REMOVING WITHOUT REMOVING PERMANENT CONSTRUCTION, OTHER EQUIPMENT, VENTING SYSTEMS, PIPING, OR DUCTS CONNECTED TO THE EQUIPMENT BEING SERVICED.

M. MAINTAIN MINIMUM DISTANCE OF 3'-0" BETWEEN ALL EXHAUST OUTLETS AND DOORS/OPERABLE WINDOWS.

N. PROVIDE ONE BALANCING DAMPER FOR EACH AIR INLET/ OUTLET SHOWN ON PLAN. WHERE DAMPER IS LOCATED ABOVE A HARD LID CEILING, PROVIDE REMOTE CABLE CONTROL FOR DAMPER.

O. FOR ALL DUCT CONNECTIONS TO MECHANICAL EQUIPMENT, PROVIDE TRANSITION FROM DUCT SIZE SHOWN TO EQUIPMENT CONNECTION SIZE.

P. PROVIDE WALL MOUNTED THERMOSTAT FOR ALL MECHANICAL EQUIPMENT EXCEPT ELECTRIC WALL HEATERS.

Q. ADJUST THROW OF ALL AIR DEVICES TO NOT INTERFERE WITH LIGHTING.

R. FAN COIL UNITS (FC-X) IN MDF, IDF, TELE, AND ELEVATOR MACHINE ROOMS ARE NOT TO BE LOCATED DIRECTLY OVER EQUIPMENT IN THE SPACE.

S. INSTALL ALL EQUIPMENT SUCH THAT MANUFACTURER RECOMMENDED CLEARANCES ARE MAINTAINED.

T. PROVIDE ALUMINUM DUCT IN ANY WET OR MOIST LOCATIONS.

U. PROVIDE CO2 SENSOR ADJACENT TO ROOM TEMPERATURE SENSOR FOR ALL SPACES WITH DEMAND CONTROLLED VENTILATION. INSTALL SENSORS BETWEEN 3 FT AND 6 FT AFF. DCV CONTROLS MAINTAIN SYSTEM VENTILATION RATE.

V. DETAILS APPLY WHETHER REFERENCED ON THE DRAWINGS OR NOT.

W. ALL REVIEWED DOCUMENTS SHALL BE KEPT AT THE SITE OF WORK AND AVAILABLE AT THE TIME OF EACH INSPECTION. OSSC SECTION 107.3.1

X. ALL FIRESTOPPING ASSEMBLY PENETRATIONS SHALL COMPLY WITH 2014 OSSC SECTIONS 714, 715, AND 717. REFER TO SPEC BOOK DIVISION 07 8400 "FIRESTOPPING" FOR APPROVED LISTED PENETRATION SYSTEMS. AT THE TIME OF INSPECTION PROVIDE CUTSHEETS TO THE AHJ OF SYSTEMS USED FOR EACH TYPE OF PENETRATION.

Y. MAINTAIN DISTANCE OF 10' MINIMUM FROM EDGE OF ROOF FOR ALL ROOF MOUNTED EQUIPMENT.

Z. PROVIDE ESCUTCHEONS FOR ALL CONDUIT, PIPE, AND DUCT PENETRATIONS THROUGH CONCRETE AND FRAMED WALLS TO CONCEAL ROUGH OPENINGS.

SYMMETRICAL WYE

MITERED ELBOW WITH TURNING VANES

RADIUSED ELBOW

General

NEW WORK

RECTANGULAR DUCT SIZING

ROUND DUCT SIZING

Piping Fittings, Appurtenances and Equipment

CAP

CONTINUATION

EXPANSION JOINT

HOSE BIBB

PIPE DROP

PIPE RISE

PIPE TO DRAIN

PRESSURE GAUGE WITH COCK

PRESSURE RELIEF VALVE

PRESSURE SENSOR

SHOCK ABSORBER

T&P RELIEF VALVE WITH PIPE TO DRAIN

TEE DOWN ON PIPE

TEE UP ON PIPE

TEMPERATURE SENSOR

TEST PORT (PETE'S PLUG OR EQUAL)

THERMOMETER

VENT TO ATMOSPHERE

Piping Systems

REFRIGERANT LIQUID

REFRIGERANT SUCTION

Piping Valves

VALVE, GENERAL

Control Symbols

CARBON DIOXIDE SENSOR

ROOM THERMOSTAT

TEMPERATURE SENSOR

Dampers

FIRE DAMPER

FIRE/SMOKE DAMPER

MOTORIZED DAMPER

SMOKE DAMPER

VOLUME DAMPER

Diffusers and Grilles

DIFFUSER OR GRILLE IDENTIFICATION

EXHAUST AIR

RETURN AIR

SUPPLY AIR

Ductwork Fittings

ACOUSTICALLY LINED DUCT (SIZES SHOWN ARE NET INSIDE)

BELLMOUTH

CONCENTRIC SQUARE TO ROUND

CONCENTRIC TRANSITION, RECTANGULAR OR ROUND

ECCENTRIC TRANSITION, RECTANGULAR OR ROUND

FLEXIBLE CONNECTION

NON-SYMMETRICAL WYE

RECTANGULAR DUCT DROP

RECTANGULAR DUCT RISER

RECTANGULAR MAIN WITH RECTANGULAR BRANCH

RECTANGULAR MAIN WITH ROUND BRANCH

RECTANGULAR OFFSET LESS THAN 15%%d

RECTANGULAR OFFSET MORE THAN 15%%d

ROUND DUCT DROP

ROUND DUCT RISER

ROUND DUCT WITH ROUND BRANCH

ROUND WYE

REV. DATE DESCRIPTION

Page 2: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

AIR OUTPUT INPUT AIR MAX TOTAL SENS

FLOW CAP CAP TURNDOWN EAT LAT APD FLOW WIDTH HEIGHT # APD CAP CAP EDB EWB LDB LWB

SYMBOL UNIT SERVED MFR MODEL (CFM) (MBH) (MBH) (°F) (°F) (FT H2O) (CFM) (IN) (IN) ROWS FPI (IN H2O) (MBH) (MBH) (°F) (°F) (°F) (°F) NOTES

AHU-1 CLASSROOMS DAIKIN CAH034GDCM 9525 373 466 10:1 30 65 0.12 15550 95 24 6 10 0.82 448 355 73 61 52 51 1, 2, 3, 4

AHU-2 ADMIN DAIKIN CAH005GDCM 905 50 63 5:1 42 66 0.01 1810 31 18 6 9 0.71 51 42 74 61 53 51 1, 2, 3, 4

AHU-3 GYMNASIUM DAIKIN CAH011GDCM 5000 160 201 10:1 56 85 0.29 5000 31 48 6 11 0.85 148 116 73 61 52 50 1, 4

AHU-4 COMMONS DAIKIN CAH011GDCM 4665 197 246 10:1 61 85 0.25 4665 31 48 8 10 0.92 187 129 78 65 52 51 1, 2, 3, 4

NOTES:

2. FOR MULTI-ZONE VAV SYSTEMS, HEAT PUMP CAPACITY IS SIZED BASED ON MORNING WARMUP AT FULL AIRFLOW. HEAT PUMP TO BE DISABLED DURING OCCUPIED OPERATION.

3. FOR MULTI-ZONE VAV SYSTEMS, ELECTRIC HEAT SHALL BE PRIMARY FORM OF HEAT DURING OCCUPIED MODE.

AIR HANDLING UNIT COIL SCHEDULEBASIS OF DESIGN GAS FIRED HEATING DATA DX COIL DATA

1. DX COOLING COILS SHALL BE STAINLESS STEEL CASING WITH ELECTROFIN DIP

4. ELECTRIC HEATERS SHALL BE STAINLESS STEEL FRAME WITH STAINLESS STEEL TUBULAR HEATING ELEMENTS

QTY APPROX. MAX

ASSOC NOM OF CAP AMBIENT DIMS WT

SYMBOL MFR MODEL FAN TONS COMPRESSORS (MBH) DB (°F) EER VOLTS PH MCA MOCP (LxWxH) (LBS) NOTES

CU-1 DAIKIN RCS040D AHU-1 40 4 441 80 11.3 460 3 78.2 90 80x99x55.5 2,596 1,2

CU-2 DAIKIN DXS13SA0484 AHU-2 4 1 46 80 11 460 3 8.4 15 37x29x29 189 1,2

CU-3 DAIKIN RCS12F150D AHU-3 12 2 149 80 12 460 3 27 35 74x38x45 650 1,2

CU-4 DAIKIN RCS15F180D AHU-4 15 2 200 80 12.8 460 3 26 40 89x38x45 746 1,2

HP-1 DAIKIN RX36NMVJU AC-1 3 1 34.4 80 9.1 208 1 17 20 34.25X12.6X29 200 1,2

HP-2 DAIKIN RX36NMVJU AC-2 3 1 34.4 80 9.1 208 1 17 20 34.25X12.6X29 200 1,2

HP-3 DAIKIN RX36NMVJU AC-3 3 1 34.4 80 9.1 208 1 17 20 34.25X12.6X29 200 1,2

HP-4 DAIKIN RX36NMVJU AC-4 3 1 34.4 80 9.1 208 1 17 20 34.25X12.6X29 200 1,2

NOTES:

1. PROVIDE WIND BAFFLE FOR LOW AMBIENT OPERATION.

2. PROVIDE ANTI CORROSION COATING TO WITHSTAND 1,000 HOUR SALT SPRAY TEST.

CONDENSING UNIT / HEAT PUMP SCHEDULEBASIS OF DESIGN AIR SOURCE CONDENSER ELECTRICAL

MAX

HEAT WT

SYMBOL AREA SERVED MFR MODEL VOLTS PH KW STAGES (LBS) NOTES

CH-1 100 VESTIBULE QMARK EFF1500 120 1 1.5 1 23 1, 2

CH-2 129 STAIR #1 QMARK EFF1500 120 1 1.5 1 23 1, 2

CH-3 118 STAIR #2 QMARK EFF1500 120 1 1.5 1 23 1, 2

CH-4 200 STAIR #1 QMARK EFF1500 120 1 1.5 1 23 1, 2

CH-5 212 STAIR #2 QMARK EFF1500 120 1 1.5 1 23 1, 2

CH-6 300 STAIR #1 QMARK EFF1500 120 1 1.5 1 23 1, 2

CH-7 311 STAIR #2 QMARK EFF1500 120 1 1.5 1 23 1, 2

NOTES:

ELECTRIC CEILING HEATER SCHEDULEBASIS OF DESIGN ELECTRICAL

1. CEILING HEATERS SHALL BE VANDAL PROOF

2. LINE VOLTAGE TEMPERATURE SENSORS

APPROX. MAX

TOTAL ESP FAN # OF VFD INPUT OUTPUT EAT LAT EFF DIMS WT

SYMBOL AREA SERVED MFR MODEL CFM (IN H2O) TYPE FANS BHP MHP FRPM (Y/N) (MBH) (MBH) (°F) (°F) MERV VOLTS PH FLA (LxWxH) (LBS) NOTES

MAU-1 KITCHEN CAPTIVEAIRE A1-D.250-15D 1890 0.5 SWSI 1 1.25 2 1996 Y 140 129 30 75 8 460 3 2.7 118x28x30 518 1

NOTES:

1. PROVIDE MODULATING DIRECT FIRED BURNER

MAKEUP AIR UNIT SCHEDULEBASIS OF DESIGN SUPPLY FAN NATURAL GAS HEATING FILTER ELECTRICAL

AIR APPROX. MAX

FLOW TSP FAN SOUND VFD DIMS WT

SYMBOL AREA SERVED MFR MODEL TYPE DRIVE (CFM) (IN H2O) RPM (SONES) VOLTS PH BHP MHP (Y/N) (LxWxH) (LBS) NOTES

EF-1 MAIN TOILET ROOMS GREENHECK SQ-140-VG INLINE DIRECT 2400 1 1628 16.3 120 1 0.87 1 ECM 22x23x23 121 1,3

EF-2 GIRLS & BOYS LOCKER GREENHECK CUE-161-VG UPBLAST DIRECT 2420 0.5 1143 14.1 120 1 0.58 0.75 ECM 22x22x42 94 1,3

EF-3 KITCHEN TYPE 1 CAPTIVE AIRE DU180HFA UPBLAST DIRECT 2100 1 1040 12 460 3 0.54 1 ECM 40x28x34 200 1,2,4

EF-4 KITCHEN DISHWASHER CAPTIVE AIRE DU33HFA UPBLAST DIRECT 525 0.5 1253 10.8 120 1 0.12 0.33 ECM 25x21x25 86 1,3,5

EF-5 SCIENCE 317 GREENHECK CUE-099-VG UPBLAST DIRECT 915 0.5 1584 10 120 1 0.19 0.25 ECM 19x19x40 44 1,3

EF-6 SCIENCE 319 GREENHECK CUE-099-VG UPBLAST DIRECT 915 0.5 1584 10 120 1 0.19 0.25 ECM 19x19x40 44 1,3

EF-7 ELEC RM. 128 GREENHECK CUE-90-VG UPBLAST DIRECT 515 0.25 1293 5.4 120 1 0.05 0.1 ECM 22x22x25 37 1,3

NOTES:

1

2 UNIT TO BE LISTED TO UL-762 FOR GREASE EXHAUST. FAN OUTLET TO BE NO LOWER THAN 42" ABOVE WALKING SURFACE OF ROOF.

3 PROVIDE CLASS I, LOW-LEAK MOTORIZED DAMPER

4 PROVIDE WITH GREASE CAPTURE AND CONTAINMENT SYSTEM AND HINGED BASE FOR CLEANING.

5 FAN AND ALL ASSOCIATED DUCTWORK TO BE ALUMINUM CONSTRUCTION.

FAN SCHEDULEBASIS OF DESIGN ELECTRICAL

PROVIDE WITH VARIABLE SPEED CONTROLLER

SYMBOL TYPE FACE FRAME DAMPER FINISH BASIS OF DESIGN NOTES

CD-1 CEILING DIFFUSER LOUVERED LAY-IN NONE COORDINATE WITH ARCH. PRICE SMD 1,2

CD-2 SECURITY CEILING DIFFUSER W' BLADE SURFACE NONE COORDINATE WITH ARCH. PRICE MSRRCD 1

CRG-1 CEILING RETURN GRILLE PERFORATED LAY-IN NONE COORDINATE WITH ARCH. PRICE PDDR 1,2

CEG-1 CEILING EXHAUST GRILLE PERFORATED SURFACE NONE COORDINATE WITH ARCH. PRICE PDDR 1,2

SG-1 HEAVY DUTY SUPPLY GRILLE DOUBLE DEFLECTION DUCT DIRECT NONE COORDINATE WITH ARCH. PRICE 920 1

RG-1 HEAVY DUTY RETURN GRILLE 3/4IN. BLADES 0° DEFLECTION IN-WALL NONE COORDINATE WITH ARCH. PRICE 93 1,3

SG-2 LOUVERED SUPPLY GRILLE DOUBLE DEFLECTION IN-WALL NONE COORDINATE WITH ARCH. PRICE 500 1

RG-2 LOUVERED RETURN GRILLE DOUBLE DEFLECTION IN-WALL NONE COORDINATE WITH ARCH. PRICE 500 1

NOTES: 1. ARCHITECT TO VERIFY FINISH

DIFFUSER, REGISTER AND GRILLE SCHEDULE

2. INSTALL IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS

3. PROVIDE INTEGRAL FIRE DAMPER

INLET MAX

SIZE MAX MIN HTG EAT LAT

SYMBOL AREA SERVED MFR MODEL (IN) CFM CFM CFM (°F) (°F) (KW) STAGES VOLTS PH NOTES

TU-1-101 LIFE SKILLS 130 NAILOR D30RE 9 1090 275 545 55 81.0 4.5 SCR 277 1

TU-1-102 CALM 130A, 132A NAILOR D30RE 5 200 60 100 55 86.5 1 SCR 277 1

TU-1-103 STRUCTURED LEARN. 132 NAILOR D30RE 9 1090 275 545 55 78.1 4 SCR 277 1

TU-1-104 R.R. 136, 137 NAILOR D30RE 5 200 60 100 55 86.5 1 SCR 277 1

TU-1-105 MEDIA CENTER 139 NAILOR D30RE 9 1150 275 575 55 79.6 4.5 SCR 277 1

TU-1-106 HALL 140 NAILOR D30RE 6 300 120 165 55 93.1 2 SCR 277 1

TU-1-201 CLASSROOM 201 NAILOR D30RE 9 940 200 470 55 81.8 4 SCR 277 1

TU-1-202 CLASSROOM 202 NAILOR D30RE 9 940 200 470 55 81.8 4 SCR 277 1

TU-1-203 R.R. 206, 207 NAILOR D30RE 5 200 60 100 55 86.5 1 SCR 277 1

TU-1-204 CLASSROOM 209 NAILOR D30RE 9 930 190 465 55 82.1 4 SCR 277 1

TU-1-205 MAKER SPACE 210 NAILOR D30RE 9 920 185 460 55 82.4 4 SCR 277 1

TU-1-206 CLASSROOM 211 NAILOR D30RE 9 950 210 475 55 81.5 4 SCR 277 1

TU-1-207 ACADEMIC RES. 213 NAILOR D30RE 8 700 175 350 55 82.0 3 SCR 277 1

TU-1-208 HALL 214 NAILOR D30RE 5 150 90 115 55 96.0 1.5 SCR 277 1

TU-1-209 HALL 214 NAILOR D30RE 5 150 90 115 55 96.0 1.5 SCR 277 1

TU-1-301 CLASSROOM 301 NAILOR D30RE 9 940 200 470 55 81.8 4 SCR 277 1

TU-1-302 CLASSROOM 302 NAILOR D30RE 9 950 200 475 55 81.5 4 SCR 277 1

TU-1-303 R.R. 306, 307 NAILOR D30RE 5 200 60 100 55 86.5 1 SCR 277 1

TU-1-304 CLASSROOM 309 NAILOR D30RE 9 920 185 460 55 82.4 4 SCR 277 1

TU-1-305 CLASSROOM 310 NAILOR D30RE 9 950 200 475 55 81.5 4 SCR 277 1

TU-1-306 CLASSROOM 313 NAILOR D30RE 8 900 200 450 55 83.0 4 SCR 277 1

TU-1-307 CLASSROOM 314 NAILOR D30RE 8 900 180 450 55 83.0 4 SCR 277 1

TU-1-308 CLASSROOM 315 NAILOR D30RE 8 900 180 450 55 83.0 4 SCR 277 1

TU-1-309 CLASSROOM 316 NAILOR D30RE 8 900 180 450 55 83.0 4 SCR 277 1

TU-1-310 CLASSROOM 317 NAILOR D30RE 8 900 180 450 55 83.0 4 SCR 277 1

TU-1-311 PREP. 318 NAILOR D30RE 6 400 100 200 55 78.6 1.5 SCR 277 1

TU-1-312 CLASSROOM 319 NAILOR D30RE 8 900 200 450 55 83.0 4 SCR 277 1

TU-1-313 HALL 312 NAILOR D30RE 5 150 90 120 55 94.3 1.5 SCR 277 1

TU-1-314 HALL 312 NAILOR D30RE 5 150 90 115 55 96.0 1.5 SCR 277 1

NOTES:

AHU-1 TERMINAL UNIT SCHEDULEBASIS OF DESIGN COOLING ELECT. RESISTANCE HTG. ELECTRICAL

AIRFLOW

INLET MAX

SIZE MAX MIN HTG EAT LAT

SYMBOL AREA SERVED MFR MODEL (IN) CFM CFM CFM (°F) (°F) (KW) STAGES VOLTS PH NOTES

TU-2-101 PRINCIPAL 102 NAILOR D30RE 5 270 90 135 55 90.0 1.5 SCR 277 1

TU-2-102 VP 106 NAILOR D30RE 5 200 60 100 55 86.5 1 SCR 277 1

TU-2-103 CONFERENCE 112 NAILOR D30RE 6 450 115 225 55 83.0 2 SCR 277 1

TU-2-104 LOUNGE 116 NAILOR D30RE 7 650 175 325 55 84.0 3 SCR 277 1

TU-2-105 WORK RM/RECORDS NAILOR D30RE 5 130 60 65 55 79.2 0.5 SCR 277 1

TU-2-106 RECPT/LOBBY NAILOR D30RE 4 115 45 60 55 81.2 0.5 SCR 277 1

TU-2-107 HALL/CALM NAILOR D30RE 5 170 60 85 55 92.0 1 SCR 277 1

TU-2-108 ELL/SP/CO NAILOR D30RE 4 120 45 60 55 81.2 0.5 SCR 277 1

TU-2-109 SICK/HEALTH NAILOR D30RE 4 100 45 50 55 86.5 0.5 SCR 277 1

TU-2-110 HALL119 NAILOR D30RE 4 100 45 50 55 86.5 0.5 SCR 277 1

NOTES:

AHU-2 TERMINAL UNIT SCHEDULEBASIS OF DESIGN COOLING ELECT. RESISTANCE HTG. ELECTRICAL

AIRFLOW

AIR THROAT THROAT MAX

FLOW TSP VELOCITY AREA WT

SYMBOL AREA SERVED MFR MODEL (CFM) (IN H2O) (FPM) (SQ FT) (LBS) NOTES

RC-1 AHU-1 & AHU-2 OA INTAKE GREENHECK FGI 60x84 17360 0.057 500 35.0 672 1

RC-2 AHU-1, AHU-2, EF-1 EXHAUST GREENHECK FGR 66x86 19760 0.059 500 39.0 772 1

NOTES:

1

ROOF HOOD SCHEDULEBASIS OF DESIGN

INSTALL PER MANUFACTURERS INSTALLATION INSTRUCTIONS.

MIN

AIR MAX FREE OVERALL OVERALL

FLOW APD AREA WIDTH HEIGHT

SYMBOL AREA SERVED MFR MODEL TYPE (CFM) (IN H2O) (SQ FT) (FT) (FT) NOTES

L-1 AHUs-3,4 INTAKE GREENHECK EHH-401 HORIZONTAL WIND-DRIVEN RAIN RESISTANT 9665 0.043 20 7 6'-6" 1, 2, 3, 4, 5, 6

L-2 AHUs-3,4 EXHAUST GREENHECK EHH-401 HORIZONTAL WIND-DRIVEN RAIN RESISTANT 9665 0.043 20 7 6'-6" 1, 2, 3, 4, 5, 6

L-3 ELEC. RM. INTAKE GREENHECK EHH-701 HORIZONTAL WIND-DRIVEN RAIN RESISTANT 515 0.06 1.1 2 1'-8" 1, 2, 3, 4, 5, 6

NOTES:

1. SEE PLANS FOR DIMENSIONS. REFER TO ARCHITECTURAL FOR ELEVATION.

2. LOUVERS TO BE SUITABLE FOR MARINE ENVIRONMENT.

3. LOUVERS SHALL BEAR THE AMCA SEAL FOR WATER PENETRATION, AIR PERFORMANCE, AND WIND DRIVEN RAIN.

4. COLOR TO BE SELECTED BY ARCHITECT.

5. BEGINNING POINT OF WATER PENETRATION = 1,043 FEET PER MINUTE

6. PROVIDE BIRD SCREEN AND EXTENDED SILL.

LOUVER SCHEDULEBASIS OF DESIGN

HEAT

TOTAL SENS PUMP APPROX. MAX

ASSOC TOTAL NOM CAP CAP EDB EWB LDB LWB HTG DIMS WT

SYMBOL AREA SERVED MFR MODEL CU CFM TONS (MBH) (MBH) (°F) (°F) (°F) (°F) (MBH) VOLTS PH MCA (LxWxH) (LBS) NOTES

AC-1 BOYS LOCKER DAIKIN FTX36NVJU HP-1 915 3 34.4 22.1 75 64 55 55 25.9 208 1 2.8 47x10x13 49 1, 2

AC-2 GIRLS LOCKER DAIKIN FTX36NVJU HP-2 915 3 34.4 22.1 75 64 55 55 25.9 208 1 2.8 47x10x13 49 1, 2

AC-3 119 MDF DAIKIN FTX36NVJU HP-3 915 3 34.4 22.1 75 64 55 55 25.9 208 1 2.8 47x10x13 49 1, 2

AC-4 KITCHEN DAIKIN FTX36NVJU HP-4 915 3 34.4 22.1 75 64 55 55 25.9 208 1 2.8 47x10x13 49 1, 2

NOTES:

1

2

DUCTLESS AIR CONDITIONING UNIT SCHEDULEBASIS OF DESIGN SUPPLY FAN DX COOLING COIL ELECTRICAL

PROVIDE WITH INTEGRAL CONDENSATE PUMP

RECEIVES POWER FROM OUTDOOR UNIT

MAX

AIRFLOW HEAT WT

SYMBOL AREA SERVED MFR MODEL (CFM) TYPE VOLTS PH KW STAGES (LBS) NOTES

UH-1 128 ELECTRICAL QMARK MUH0321 350 SUSPENDED IN SPACE 208 3 2.2 1 27 1

UH-2 215 MECH QMARK MUH0321 350 SUSPENDED IN SPACE 208 3 2.2 1 27 1

UH-3 308 MECH QMARK MUH0321 350 SUSPENDED IN SPACE 208 3 2.2 1 27 1

UH-4 141 FIRE RISER QMARK MUH0321 350 SUSPENDED IN SPACE 208 3 2.2 1 27 1

NOTES:

ELECTRIC UNIT HEATER SCHEDULEBASIS OF DESIGN ELECTRICAL

1. LINE VOLTAGE THERMOSTAT

MIN DCV THICK- FACE THICK- FACE APPROX. MAX

TOTAL HEATING OSA OSA TSP ESP FAN # OF FAN MAX VFD/ TOTAL TSP ESP FAN # OF FAN MAX VFD/ EFF NESS VEL EFF NESS VEL DIMS (FT) WT

SYMBOL AREA SERVED MFR MODEL CFM CFM CFM CFM (IN H2O) (IN H2O) TYPE FANS BHP MHP RPM RPM MCA MOCP ECM CFM (IN H2O) (IN H2O) TYPE FANS BHP MHP RPM RPM MCA MOCP ECM MERV (INCH) (FPM) MERV (INCH) (FPM) VOLTS PH (LxWxH) (LBS) NOTES

AHU-1 CLASSROOMS DAIKIN CAH034GDCM 15550 9525 9525 - 5.26 2 PLENUM 6 3.1 3.3 3213 3230 25.6 30 ECM 15550 1.12 1 PLENUM 5 1.07 2.3 2502 3230 15.8 20 ECM 8 2 468 13 12 468 480 3 27x10x6 7195 1, 2, 3, 4, 5, 6

AHU-2 ADMIN DAIKIN CAH005GDCM 1810 905 625 - 4.3 2 PLENUM 1 1.83 3.3 2711 3230 5.1 15 ECM 1810 1.08 1 PLENUM 1 0.47 2.3 1755 3230 3.8 15 ECM 8 2 347 13 12 347 480 3 21x6x3 2057 1, 2, 3, 4, 5, 7, 8

AHU-3 GYM DAIKIN CAH011GDCM 5000 5000 2905 2420 3.93 1 PLENUM 2 2.24 3.3 2889 3230 9.2 15 ECM 5000 0.62 0.5 PLENUM 2 0.51 2.3 1976 3230 6.8 15 ECM 8 2 443 13 12 443 480 3 25x6x6 3442 1, 2, 3, 4, 5, 9

AHU-4 COMMONS DAIKIN CAH011GDCM 4665 4665 2830 645 3.89 1 PLENUM 2 2.01 3.3 2782 3230 9.2 15 ECM 4665 0.61 0.5 PLENUM 2 0.44 2.3 1867 3230 6.8 15 ECM 8 2 404 13 12 404 480 3 26x6x6 3565 1, 2, 3, 4, 5

NOTES:

1. REFER TO AHU COIL SHEDULE FOR COIL PROPERTIES

2. PROVIDE STAINLESS STEEL LINER FOR CORROSION RESISTANCE.

3. ALL DAMPERS SHALL BE TAMCO 1000 SERIES SW, SUITABLE FOR MARINE ENVIRONMENT

4. PROVIDE WITH 100% OSA ECONOMIZER.

5. PROVIDE WITH SMOKE DETECTOR ON RETURN DUCT.

6. DEMAND LIMIT RETURN FANS ECM TO 10 HP TOTAL.

7. DEMAND LIMIT RETURN FANS ECM TO 1 HP TOTAL.

8. DEMAND LIMIT SUPPLY FANS ECM TO 3 HP TOTAL.

9. DEMAND LIMIT RETURN FANS ECM TO 2 HP TOTAL.

10. DEMAND LIMIT RETURN FANS ECM TO 1.5 HP TOTAL.

AIR HANDLING UNIT SCHEDULEBASIS OF DESIGN SUPPLY FAN RETURN FAN PRE-FILTER FINAL FILTER ELECTRICAL

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:2

9 A

M

M002

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

SC

HE

DU

LE

S -

ME

CH

AN

ICA

L

SCHEDULES -MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

REV. DATE DESCRIPTION

Page 3: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

NET NET AIR EXHAUST EXHAUST REQUIRED PROVIDED

OCCUPIABLE OCCUPIABLE CHANGES AIRFLOW AIRFLOW EXHAUST EXHAUST

HVAC FLOOR AREA VOLUME PER RATE RATE # OF AIRFLOW AIRFLOW

UNIT ROOM (SF) (CF) HOUR (CFM/SF) (CFM/FIXTURE) FIXTURES (CFM) (CFM)

EF-1 109 SICK 86 693 - 1 - - 86 90

EF-1 109A R.R. 51 413 - - 75 1 75 80

EF-1 110 HEALTH 121 974 - 1 - - 121 130

EF-1 113 R.R. 54 433 - - 75 1 75 80

EF-1 114 R.R. 48 386 - - 75 1 75 80

EF-1 131 R.R. 91 735 - - 75 1 75 80

EF-1 133 JAN. 57 457 - - 75 1 75 80

EF-1 135 R.R. 48 384 - - 75 1 75 80

EF-1 136 GIRLS R.R. 178 1,427 10 - - - 238 240

EF-1 137 BOYS R.R. 179 1,433 10 - - - 239 240

EF-1 203 JAN. 46 371 - - 75 1 75 80

EF-1 205 R.R. 48 384 - - 75 1 75 80

EF-1 206 GIRLS R.R. 181 1,448 10 - - - 241 250

EF-1 207 GIRLS R.R. 179 1,436 10 - - - 239 240

EF-1 303 JAN. 46 371 - - 75 1 75 80

EF-1 305 R.R. 48 384 - - 75 1 75 80

EF-1 306 GIRLS R.R. 182 1,457 10 - - - 243 250

EF-1 307 BOYS R.R. 179 1,438 10 - - - 240 240

TOTAL 2397 2400

EF-2 125 BOYS LOCKER 856 6,822 10 - - - 1137 1140

EF-2 125C R.R. 56 448 - - 75 1 75 80

EF-2 127 GRILS LOCKER 840 6,708 10 - - - 1118 1120

EF-2 127C R.R. 58 466 - - 75 1 75 80

TOTAL 2405 2420

NOTES:

EXHAUST VENTILATION SCHEDULE

SUM OF ZONE POPULATION (ƩPz) 589 PEOPLE UNCORRECTED OA INTAKE (Vou) 8,187 CFM AVE UNCORRECTED OA FRACTION (Xs) 50.7% CFM/CFM OA INTAKE REQUIRED (Vot) 9,521 CFM

DIVERSITY (D = Ps/ƩPz) 0.99 SUM OF PRIMARY AIR AT MIN (ƩVpz=Vps) 19,213 CFM SYSTEM VENTILATION EFF. (Ev) 86.0% OA INTAKE PROVIDED 9,525 CFM

(Er) (Evz) (Az) (Pz) (Ez) (Rp) (Ra) (Vbzp) (Vbza) (Vbz) (Voz) (Vdz) (Ep) (Vpz) (Pz) (Zpz)

ZONE SECOND ROOM ZONE FLOOR PEAK OCC DEFAULT ACTUAL PEOPLE SPACE AIR PEOPLE AREA Rp*Pz RA*Az Rp*Pz + OUTDOOR PRIMARY PRIMARY ZONE PEAK OUTDOOR

EQUIP RECIRC NUMER VENT AREA CLG DENSITY NO. NO. DIVERSITY DISTRI- OUTDOOR OUTDOOR RA*Az AIR FLOW + AIR PRIMARY NO. AIR

TAG FRAC EFF. (Az) DEFAULT PEOPLE PEOPLE BUTION AIR RATE AIR RATE (DISTRIBUTION SECONDARY FRACTION AIR PEOPLE FRACTION

EFFECT- CORRECTED) AIR (Ep) FLOW (AT MIN)

IVENESS

(PERSON/ (CFM/

(SQ. FT.) (CFM) 1000 SF) (PEOPLE) (PEOPLE) (%) PERSON) (CFM/SF) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (PEOPLE) Voz/Vpz

134 LIFE SKILLS 1.04 790 1090 35 28 31 0% 0.80 10.0 0.12 310.0 95 405 506 1090 1.0000 1,090 31 0.464

TU-1-101

135 CALM 0.88 85 100 5 0 1 0% 0.80 5.0 0.06 5.0 5 10 13 20 1.0000 20 1 0.631

136 CALM 0.88 85 100 5 0 1 0% 0.80 5.0 0.06 5.0 5 10 13 20 1.00 20 1 0.631

TU-1-102

138 STRUCTURED LEARNING CENTER 1.04 785 1090 35 27 31 0% 0.80 10.0 0.12 310.0 94 404 505 1090 1.0000 1,090 31 0.464

TU-1-103

142 BOYS RR 1.36 190 100 0 0 0 0% 0.80 0.0 0.06 0.0 11 11 14 100 1.0000 100 0 0.143

143 GIRLS RR 1.36 190 100 0 0 0 0% 0.80 0.0 0.06 0.0 11 11 14 100 1.00 100 0 0.143

TU-1-104

145 LIBRARY 1.09 575 1150 35 20 31 0% 0.80 10.0 0.12 310.0 69 379 474 1150 1.0000 1,150 31 0.412

TU-1-105

146 SOUTH HALL 0.88 1,380 300 0 0 0 0% 0.80 0.0 0.06 0.0 83 83 104 165 1.0000 165 0 0.627

TU-1-106

201 CLASSROOM 0.95 900 940 35 32 31 0% 0.80 10.0 0.12 310.0 108 418 523 940 1.0000 940 31 0.556

TU-1-201

202 CLASSROOM 0.95 900 940 35 32 31 0% 0.80 10.0 0.12 310.0 108 418 523 940 1.0000 940 31 0.556

TU-1-202

242 BOYS RR 1.37 185 100 0 0 0 0% 0.80 0.0 0.06 0.0 11 11 14 100 1.0000 100 0 0.139

243 GIRLS RR 1.37 180 100 0 0 0 0% 0.80 0.0 0.06 0.0 11 11 14 100 1.00 100 0 0.135

TU-1-203

210 CLASSROOM 0.96 820 930 35 29 31 0% 0.80 10.0 0.12 310.0 98 408 511 930 1.0000 930 31 0.549

TU-1-204

211 MAKER SPACE 0.95 805 920 35 28 31 0% 0.80 10.0 0.12 310.0 97 407 508 920 1.0000 920 31 0.552

TU-1-205

212 CLASSROOM 0.95 915 950 35 32 31 0% 0.80 10.0 0.12 310.0 110 420 525 950 1.0000 950 31 0.552

TU-1-206

215 ACADEMIC RESOURCES 0.91 715 700 35 25 25 0% 0.80 10.0 0.12 250.0 86 336 420 700 1.0000 700 25 0.600

TU-1-207

213-2 HALL-2 0.93 870 150 0 0 0 0% 0.80 0.0 0.06 0.0 52 52 65 113 1.0000 113 0 0.580

TU-1-208

213-1 HALL-1 0.95 840 150 0 0 0 0% 0.80 0.0 0.06 0.0 50 50 63 113 1.0000 113 0 0.560

TU-1-209

301 CLASSROOM 0.95 930 940 35 33 31 0% 0.80 10.0 0.12 310.0 112 422 527 940 1.0000 940 31 0.561

TU-1-301

302 CLASSROOM 0.95 935 950 35 33 31 0% 0.80 10.0 0.12 310.0 112 422 528 950 1.0000 950 31 0.556

TU-1-302

342 BOYS RR 1.36 190 100 0 0 0 0% 0.80 0.0 0.06 0.0 11 11 14 100 1.0000 100 0 0.143

343 GIRLS RR 1.38 175 100 0 0 0 0% 0.80 0.0 0.06 0.0 11 11 13 100 1.00 100 0 0.131

TU-1-303

310 CLASSROOM 0.95 820 920 35 29 31 0% 0.80 10.0 0.12 310.0 98 408 511 920 1.0000 920 31 0.555

TU-1-304

311 CLASSROOM 0.95 930 950 35 33 31 0% 0.80 10.0 0.12 310.0 112 422 527 950 1.0000 950 31 0.555

TU-1-305

314 CLASSROOM 0.92 945 900 35 33 31 0% 0.80 10.0 0.12 310.0 113 423 529 900 1.0000 900 31 0.588

TU-1-306

315 CLASSROOM 0.93 885 900 35 31 31 0% 0.80 10.0 0.12 310.0 106 416 520 900 1.0000 900 31 0.578

TU-1-307

316 CLASSROOM 0.93 885 900 35 31 31 0% 0.80 10.0 0.12 310.0 106 416 520 900 1.0000 900 31 0.578

TU-1-308

317 CLASSROOM 0.93 885 900 35 31 31 0% 0.80 10.0 0.12 310.0 106 416 520 900 1.0000 900 31 0.578

TU-1-309

318 SCIENCE 0.92 925 900 35 32 31 0% 0.80 10.0 0.12 310.0 111 421 526 900 1.0000 900 31 0.585

TU-1-310

319 PREP 0.88 330 400 2 1 4 25% 0.80 5.0 0.06 20.0 20 40 50 80 1.0000 80 4 0.622

TU-1-311

320 SCIENCE 0.92 945 900 35 33 31 0% 0.80 10.0 0.12 310.0 113 423 529 900 1.0000 900 31 0.588

TU-1-312

312-2 HALL-2 0.86 1,035 150 0 0 0 0% 0.80 0.0 0.06 0.0 62 62 78 120 1.0000 120 0 0.647

TU-1-313

312-1 HALL-1 0.87 960 150 0 0 0 0% 0.80 0.0 0.06 0.0 58 58 72 113 1.0000 113 0 0.640

TU-1-314

ASHRAE 62.1-2010 VENTILATION CALCULATION:AHU-# 1

SPACE DESCRIPTION

SUM OF ZONE POPULATION (ƩPz) 49 PEOPLE UNCORRECTED OA INTAKE (Vou) 299 CFM AVE UNCORRECTED OA FRACTION (Xs) 15.1% CFM/CFM OA INTAKE REQUIRED (Vot) 622 CFM

DIVERSITY (D = Ps/ƩPz) 0.47 SUM OF PRIMARY AIR AT MIN (ƩVpz=Vps) 1,409 CFM SYSTEM VENTILATION EFF. (Ev) 48.0% OA INTAKE PROVIDED 625 CFM

(Er) (Evz) (Az) (Pz) (Ez) (Rp) (Ra) (Vbzp) (Vbza) (Vbz) (Voz) (Vdz) (Ep) (Vpz) (Pz) (Zpz)

ZONE SECOND ROOM ZONE FLOOR PEAK OCC DEFAULT ACTUAL PEOPLE SPACE AIR PEOPLE AREA Rp*Pz RA*Az Rp*Pz + OUTDOOR PRIMARY PRIMARY ZONE PEAK OUTDOOR

EQUIP RECIRC NUMER VENT AREA CLG DENSITY NO. NO. DIVERSITY DISTRI- OUTDOOR OUTDOOR RA*Az AIR FLOW + AIR PRIMARY NO. AIR

TAG FRAC EFF. (Az) DEFAULT PEOPLE PEOPLE BUTION AIR RATE AIR RATE (DISTRIBUTION SECONDARY FRACTION AIR PEOPLE FRACTION

EFFECT- CORRECTED) AIR (Ep) FLOW (AT MIN)

IVENESS

(PERSON/ (CFM/

(SQ. FT.) (CFM) 1000 SF) (PEOPLE) (PEOPLE) (%) PERSON) (CFM/SF) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (PEOPLE) Voz/Vpz

102 PRINCIPAL 0.66 190 270 5 1 2 50% 0.80 5.0 0.06 10.0 11 21 27 54 1.0000 54 2 0.495

TU-2-101

106 VP 0.57 145 200 5 1 2 50% 0.80 5.0 0.06 10.0 9 19 23 40 1.0000 40 2 0.584

TU-2-102

112 CONFERENCE 0.97 245 450 50 12 10 0% 0.80 5.0 0.06 50.0 15 65 81 450 1.0000 450 10 0.180

TU-2-103

117 LOUNGE 0.48 330 650 25 8 10 0% 0.80 5.0 0.06 50.0 20 70 87 130 1.0000 130 10 0.671

TU-2-104

116 WORK RM 0.72 235 70 2 0 2 0% 0.80 5.0 0.06 10.0 14 24 30 70 1.0000 70 2 0.430

118 RECORDS 0.79 125 60 2 0 2 0% 0.80 5.0 0.06 10.0 8 18 22 60 1.00 60 2 0.365

TU-2-105

111 HALL 0.86 295 75 0 0 0 0% 0.80 0.0 0.06 0.0 18 18 22 75 1.0000 75 0 0.295

107 CALM 0.69 80 40 5 0 2 0% 0.80 5.0 0.06 10.0 5 15 19 40 1.00 40 2 0.463

TU-2-106

103-1 LOBBY-1 0.67 220 100 10 2 5 50% 0.80 5.0 0.06 25.0 13 38 48 100 1.0000 100 5 0.478

103-2 LOBBY-2 0.65 220 70 10 2 3 100% 0.80 5.0 0.06 15.0 13 28 35 70 1.00 70 3 0.504

TU-2-107

104 ELL 0.67 90 40 5 0 2 50% 0.80 5.0 0.06 10.0 5 15 19 40 1.0000 40 2 0.481

105 SP 0.67 90 40 5 0 2 50% 0.80 5.0 0.06 10.0 5 15 19 40 1.00 40 2 0.481

108 CO 0.67 90 40 5 0 2 50% 0.80 5.0 0.06 10.0 5 15 19 40 1.00 40 2 0.481

TU-2-108

109 SICK 0.64 90 50 5 0 3 50% 0.80 5.0 0.06 15.0 5 20 26 50 1.0000 50 3 0.510

110 HEALTH 0.71 125 50 5 1 2 50% 0.80 5.0 0.06 10.0 8 18 22 50 1.00 50 2 0.438

TU-2-109

120 NORTH HALL 0.78 490 100 0 0 0 0% 0.80 0.0 0.06 0.0 29 29 37 100 1.0000 100 0 0.368

TU-2-110

ASHRAE 62.1-2010 VENTILATION CALCULATION:AHU-# 2

SPACE DESCRIPTION

Az Rp Ra Pz Vbz EZ Voz

NET DEFAULT PEOPLE AREA BREATHING ZONE ZONE

OCCUPIABLE OCCUPANT OUTDOOR AIR OUTDOOR AIR DEFAULT ACTUAL ZONE OUTDOOR AIR OUTDOOR

HVAC FLOOR AREA DENSITY RATE FLOW RATE ZONE ZONE AIRFLOW DISTRIBUTION AIRFLOW

UNIT ROOM (SF) (#/1000SF) (CFM / PERSON) (CFM/SQ FT) POPULATION POPULATION (CFM) EFFECTIVENESS (CFM)

AHU-4 COMMONS 3,562 100 7.50 0.18 357 216 2,261 0.8 2,826

NOTES:

OUTSIDE AIR VENTILATION SCHEDULE - AHU-4

Az Rp Ra Pz Vbz EZ Voz

NET DEFAULT PEOPLE AREA BREATHING ZONE ZONE

OCCUPIABLE OCCUPANT OUTDOOR AIR OUTDOOR AIR DEFAULT ACTUAL ZONE OUTDOOR AIR OUTDOOR

HVAC FLOOR AREA DENSITY RATE FLOW RATE ZONE ZONE AIRFLOW DISTRIBUTION AIRFLOW

UNIT ROOM (SF) (#/1000SF) (CFM / PERSON) (CFM/SQ FT) POPULATION POPULATION (CFM) EFFECTIVENESS (CFM)

AHU-3 GYM 7,740 0 0.00 0.3 0 100 2,322 0.8 2,903

NOTES:

OUTSIDE AIR VENTILATION SCHEDULE - AHU-3

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:3

0 A

M

M003

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

SC

HE

DU

LE

S -

ME

CH

AN

ICA

L

SCHEDULES -MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

REV. DATE DESCRIPTION

Page 4: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

21x48533x1219

21x48533x1219

21x36

533x914

21x48533x1219

21x48533x1219

21x48533x1219

21x48533x1219

21x48

533x1219

CLEARANCE -

FORCOMBUSTIBLE

SURFACES

ONLY

MAX

Q

21x60533x1524

MAX

Q

21x60533x1524

MAX

Q

21x60533x1524

MAX

Q

21x36

533x914

MAX

Q

21x48

533x1219

AA

1

1

FF

2

2

GG

20

20

EE

BB

14

14

8

8

HH

TU-2-101 TU-2-102

TU-2-103

TU-2-104

TU-2-105

TU-2-106

TU-2-107

TU-2-108

TU-2-110

TU-2-109

CH-3

JAN.

133

CALM

130A

ELL

104SP

105

CO

108

SICK

109

R.R.

113

HEALTH

110

CALM

107

MEDIA CENTER

139

CALM

132A

R.R.

131

R.R.

109A

ELEV.

138

GIRLS R.R.

136

BOYS R.R.

137

R.R.

125C

OFFICE

127A

HALL

134

HALL

111

VP

106

CONFERENCE

112

STAIR #2

118

HALL

126

LOUNGE

116

RECORDS

117

STRUCTURED LEARNINGCENTER

132

OFFICE

125A

LIFE SKILLS

130

HALL

140

ELEC. RM.

128

STAIR #1

129

KITCHEN

121COMMONS

122

GYM STORAGE

120

WORK RM

115

VESTIBULE

100

HALL

119

GYMNASIUM

123

R.R.

127C

PRINCIPAL

102

ENTRY HALL

101

CH-2

STORAGE

127B

STORAGE

125B

CO2TTT

TU-1-101

TU-1-102

TU-1-103TU-1-104

TU-1-105

TU-1-106

UH-1

AHU-3

T T

T

T

T

T

T

TCO2

T

CO2

T

CO2

T

T

T

T

TT

T T

AC-2 AC-1

AHU-4

AC-4

CC

7

7

3

3

4

4

5

5

6

6

9

9

10

10

11

11

12

12

15

15

18

18

16

16

17

17

13

13 19

19

DD

T

S S

CH-1

S

GIRLS LOCKER RM

127 BOYS LOCKER RM

125

FIRE RISER ROOM

141

UH-4

UH-5

CO2

CO2

T

T

4

M402

21

21

I I

AHU-3

AHU-3

R.R.

135

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:3

4 A

M

M101

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

FIR

ST

FL

OO

R Z

ON

ING

PL

AN

-M

EC

HA

NIC

AL

FIRST FLOOR ZONINGPLAN - MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

0' 4' 8' 16'

1/8" = 1'-0"

1 FIRST FLOOR - HVAC ZONES PLAN - MECHANICAL

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

N O R T H

REV. DATE DESCRIPTION

Page 5: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

AA

1

1

FF

2

2

GG

20

20

EE

BB

14

14

8

8

HH

MECHANICAL

215

HALL

204

CLASSROOM

202MDF

208BOYS R.R.

207

GIRLS R.R.

206

MAKER SPACE

210

CLASSROOM

211

STAIR #2

212STAIR #1

200

ACADEMIC RESOURCES

213

HALL

214

CLASSROOM

201

CH-4

CH-5

UH-2

TU-1-201 TU-1-202

TU-1-203 TU-1-204

TU-1-205 TU-1-206

TU-1-207

TU-1-208TU-1-209

AC-3

T

CO2

T

CO2

T

CO2

T

CO2

T

CO2

T

T T

T

T

CO2

CC

7

7

3

3

4

4

5

5

6

6

9

9

10

10

11

11

12

12

15

15

18

18

16

16

17

17

13

13 19

19

DD

T

S S

4

M402

21

21

I I

HALL

214

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:3

7 A

M

M102

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

SE

CO

ND

FL

OO

R Z

ON

ING

PLA

NS

-M

EC

HA

NIC

AL

SECOND FLOOR ZONINGPLANS - MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

0' 4' 8' 16'

1/8" = 1'-0"

1 SECOND FLOOR - HVAC ZONES PLAN - MECHANICAL

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

N O R T H

REV. DATE DESCRIPTION

Page 6: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

AA

1

1

FF

2

2

GG

20

20

EE

BB

14

14

8

8

HH

BOYS R.R.

307

SCIENCE

317

PREP.

318

SCIENCE

319

ELEV.

320

CLASSROOM

309

HALL

304

STAIR #2

311STAIR #1

300

CLASSROOM

301

CLASSROOM

310

CLASSROOM

313

CLASSROOM

314

CLASSROOM

315

CLASSROOM

316

CLASSROOM

302GIRLS R.R.

306

MECHANICAL ROOM

308

HALL

312

TU-1-301 TU-1-302

TU-1-303TU-1-304

TU-1-305

TU-1-306TU-1-307TU-1-308TU-1-309TU-1-310

TU-1-311

TU-1-312

TU-1-313TU-1-314

CH-7CH-6

T

CO2

T

CO2

T

CO2

T

CO2

T CO2 TCO2T

T

CO2

T

CO2

T

CO2

T

CO2

T

T T

CC

7

7

3

3

4

4

5

5

6

6

9

9

10

10

11

11

12

12

15

15

18

18

16

16

17

17

13

13 19

19

DD

UH-3

T

SS

1

M402

3

M402

4

M402

21

21

I I

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:3

9 A

M

M103

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

TH

IRD

FLO

OR

ZO

NIN

G P

LA

NS

-M

EC

HA

NIC

AL

THIRD FLOOR ZONINGPLANS - MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

0' 4' 8' 16'

1/8" = 1'-0"

1 THIRD FLOOR - HVAC ZONES PLAN - MECHANICAL

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

N O R T H

REV. DATE DESCRIPTION

Page 7: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

SH

OW

ER

SH

OW

ER

MAX

Q

21x48533x1219

MAX

Q

21x48533x1219

MAX

Q

21x36

533x914

MAX

Q

21x48533x1219

MAX

Q

21x48533x1219

MAX

Q

21x48533x1219

MAX

Q

MAX

Q

21x48

533x1219

CLEARANCE -

FORCOMBUSTIBLE

SURFACES

ONLY

MAX

Q

21x60533x1524

MAX

Q

21x60533x1524

MAX

Q

21x60533x1524

MAX

Q

21x36

533x914

MAX

Q

21x48

533x1219

AA

1

1

FF

2

2

GG

20

20

EE

BB

14

14

8

8

HH

JAN.

133

CALM

130A

ELL

104

SP

105

CO

108

SICK

109

R.R.

113

HEALTH

110

CALM

107MEDIA CENTER

139

CALM

132A

R.R.

131

R.R.

109A

ELEV.

138

GIRLS R.R.

136

BOYS R.R.

137

R.R.

125C

OFFICE

127A

HALL

134

HALL

111

VP

106

CONFERENCE

112

STAIR #2

118

HALL

126

LOUNGE

116

RECORDS

117STRUCTURED LEARNING

CENTER

132

OFFICE

125A

LIFE SKILLS

130

HALL

140

ELEC. RM.

128

STAIR #1

129

KITCHEN

121COMMONS

122

GYM STORAGE

120

WORK RM

115

VESTIBULE

100

HALL

119

GYMNASIUM

123

R.R.

127C

PRINCIPAL

102

ENTRY HALL

101

STORAGE

127B

STORAGE

125B

20x14

28x18

10"ø

20x10

22x14

16x10

10x10

R.R.

114

R.R.

135

AC-2

AC-1

AC-4

UP TO EF-2

16x16 TYPE 1 UP TO EF-3PROVIDE 2 LAYERS 3M FIRE BARRIERDUCT WRAP OVER ENTIRE EXHAUST DUCT.PROVIDE CLEANOUTS AS REQUIRED BYNFPA 96.

16x16 TYPE 2 UP TO EF-4

UP TO MUA-1

20x16

16x12

CC

7

7

3

3

4

4

5

5

6

6

9

9

10

10

11

11

12

12

15

15

18

18

16

16

17

17

13

13 19

19

DD

TU-1-101

TU-1-102

TU-1-103

TU-2-101

TU-2-102

TU-2-107

TU-2-106

TU-2-103

TU-2-104

TU-2-105

TU-2-1094665

18x48 RG-1

5000

30x30 RG-1

CH-2CH-3

CH-1

BOYS LOCKER RM

125

12"ø

20x12

14"ø12"ø

TU-1-104TU-1-106

TU-2-108 TU-2-110

TU-1-105

30x20

10"ø 10"ø

20x10

740

24x16 RG-1

370CRG-1(TYP. 2)

14"ø

FSD TYP.

FSD

GIRLS LOCKER RM

127

FIRE RISER ROOM

141

UH-4

UH-1

50CD-18"ø

50CD-18"ø

UH-5

34x18

275CD-1(TYP 2)

10"ø

545CRG-1(TYP 2)

12"ø270

CD-1(TYP 2)

10"ø

100CD-2(TYP 2)

6"ø

545CRG-1(TYP 2)

12"ø

275CD-1(TYP 2)

10"ø

270CD-1(TYP 2)

10"ø

12"ø12"ø

8"ø

100CD-1(TYP 2)

8"ø

12"ø

290CD-1(TYP 2)

10"ø

285CD-1(TYP 2)

10"ø

575

CRG-1(TYP 2)

12"ø

300CD-18"ø

270CD-110"ø

200CD-18"ø

270CRG-110"ø

200CRG-18"ø

225CD-1(TYP 2)

10"ø

450CRG-112"ø

325CD-1(TYP 2)

10"ø

650CRG-112"ø

60CD-16"ø

70CD-18"ø

75CD-18"ø

50CD-18"ø

85CD-1(TYP 2)

8"ø

50

CD-1(TYP 3)

8"ø

50CD-18"ø

50

CD-18"ø

100CD-18"ø

26x8

KIT. STG.

121A

170CRG-18"ø

250

CRG-18"ø

115CRG-18"ø

75CEG-1(TYP 5)

8"ø

10"ø

10"ø

10"ø

10"ø

12"ø

8"ø

16x16

250CEG-1(TYP 2)

10"ø

80CEG-1(TYP 2)

6"ø

24x20

515

L-3

10x10

MD

MD

PUMP RM.

128A

80

CEG-16x6

570

CEG-1

(TYP 2)

10x10

560

CEG-1

(TYP 2)

10x10

80

CEG-16x6

UP TO SUPPLY MAINFROM AHU-3

1" UNDERCUTDOOR (TYP)

1" UNDERCUTDOOR (TYP)

SEE CONTINUATIONON M202

16x16

UP TOHP-4

8"ø

---CRG-1

(TYP 4)

16x16

CONCENTRICVENTTERMINATIONKIT (TYP.2)

4"COMBUSTION AIR AND VENTDN TO WATER HEATER(TYP.2)

SLOPE HORIZONTAL SECTIONSOF DUCTWORK AT A MINIMUMOF 1 PERCENT, SLOPED DOWNWARDTOWARD HOOD.

20x30

UP TO AHU-3

50

CEG-16x6

MOUNT AT 24" AFFTO MIDDLE OF GRILLE

LOBBY

103

RECEPT

103A

21

21

I I

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:4

6 A

M

M201

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

FIR

ST

FL

OO

R P

LA

N -

ME

CH

AN

ICA

L

FIRST FLOOR PLAN -MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

0' 4' 8' 16'

1/8" = 1'-0"

1 FIRST FLOOR PLAN - MECHANICAL

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

N O R T H

A. UNLESS OTHERWISE NOTED, BRANCH DUCTS TO TU TO BE THE SAMESIZE AS INLET.

GENERAL SHEET NOTES

B. UNLESS OTHERWISE NOTES, BRANCH DUCTS TO DIFFUSERS/GRILLES TOBE THE SAME SIZE AS DIFFUSER/GRILLE NECK.

C. ALL MATERIAL AND EQUIPMENT EXPOSED TO THE EXTERIOR AIR SHALLBE RATED FOR USE IN A COASTAL ENVIRONMENT VIA A 1,000 HOUR SALTSPRAY TEST, MINIMUM, UNLESS SCHEDULES OR SPECIFICATIONSDICTATE A LONGER SALF SPRAY TEST (E.G. AIR HANDLING UNITS,EXTERIOR HEAT PUMPS). OUTSIDE AIR DUCTWORK AND ALL OUTSIDE,RELIEF, AND EXHAUST AIR PLENUMS SHALL BE 316L STAINLESS STEEL INTHEIR ENTIRETY.

REV. DATE DESCRIPTION

Page 8: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

AA

1

1

FF

2

2

GG

20

20

EE

BB

14

14

8

8

HH

MECHANICAL

215

HALL

204

CLASSROOM

202

MDF

208

BOYS R.R.

207

GIRLS R.R.

206

MAKER SPACE

210

CLASSROOM

211

STAIR #2

212STAIR #1

200

ACADEMIC RESOURCES

213

HALL

214

CLASSROOM

201

AHU-4

20x14

16x12

28x20

JAN.

203

R.R.

205

HP-1 HP-2

HP-3

HP-4

20"ø

AC-3

60x60

9665

L-1

9665

60x60 L-2

CU-3

CU-2

CU-1

EF-4

EF-3

MAU-1

EF-2

CC

7

7

3

3

4

4

5

5

6

6

9

9

10

10

11

11

12

12

15

15

18

18

16

16

17

17

13

13 19

19

DD

TU-1-201

TU-1-202

TU-1-204

TU-1-205 TU-1-206

TU-1-207

CU-4

28"ø20"ø

24"ø28"ø

20"ø

CH-4 CH-5

30"ø

38x2

628x20

30x20

38x26

30x2

0

10"ø14x10

TU-1-209

TU-1-203

TU-1-208

MECHANICAL CONTRACTOR TO COORDINATE THE ROUTING AND INSTALLATION OF DUCTWORK IN THE GYM WITH THE INSTALLER OF THE BASKETBALL BACKBOARDS

FSD TYP.

FSD

UH-2

REFRIGERATION CONDENSERSR1 AND R2. REFER TO FOOD SERVICE CONSULTANTDRAWINGS FOR MORE INFORMATION.

RS/RL PIPING

RS/RL PIPING

28x16

20x14

20x14

16x12

AHU-3

585

10x8 SG-1

(TYP 8)

625

12x8 SG-1

(TYP 3)

625

12x8 SG-1

(TYP 5)

235CD-1(TYP 4)

10"ø

470CRG-1(TYP 2)

12"ø

12"ø

235CD-1(TYP 4)

10"ø470

CRG-1(TYP 2)

12"ø

12"ø

100CD-1(TYP 2)

8"ø

235CD-1(TYP 2)

10"ø

230CD-1(TYP 2)

10"ø465

CRG-1(TYP 2)

12"ø

12"ø

230CD-1(TYP 4)

10"ø460

CRG-1(TYP 2)

12"ø475

CRG-1(TYP 2)

12"ø

240CD-1(TYP 2)

10"ø

235CD-1(TYP 2)

10"ø

12"ø 12"ø

175CD-1(TYP 4)

10"ø

12"ø

350CRG-1(TYP 2)

12"ø

150

CD-18"ø150

CD-18"ø

EF-7

240CEG-1(TYP 2)

10"ø

80CEG-1(TYP 2)

6"ø

8Ø NATURAL GAS BURNERCOMBUSTION VENTING UP TO ROOF

8Ø NATURAL GAS BURNEROUTSIDE AIR INTAKE UP TO ROOF

SEE CONTINUATION ON M2.01

SLOPE BOTTOM EDGE OF PLENUM TOWARDSEXTERIOR FOR DRAINAGE.

SLOPE BOTTOM EDGE OF PLENUM TOWARDSEXTERIOR FOR DRAINAGE.

16x10

16x10

16x1016x10

CLASSROOM

209

10x10

30x20

30x20

MD

AFMS

MD

28x20

AFMS

MD

MD

21

21

I I

28x20

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:5

0 A

M

M202

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

SE

CO

ND

FL

OO

R P

LA

N -

ME

CH

AN

ICA

L

SECOND FLOOR PLAN -MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

0' 4' 8' 16'

1/8" = 1'-0"

1 SECOND FLOOR PLAN - MECHANICAL

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

N O R T H

A. UNLESS OTHERWISE NOTED, BRANCH DUCTS TO TU TO BE THE SAMESIZE AS INLET.

GENERAL SHEET NOTES

B. UNLESS OTHERWISE NOTES, BRANCH DUCTS TO DIFFUSERS/GRILLES TOBE THE SAME SIZE AS DIFFUSER/GRILLE NECK.

C. ALL MATERIAL AND EQUIPMENT EXPOSED TO THE EXTERIOR AIR SHALLBE RATED FOR USE IN A COASTAL ENVIRONMENT VIA A 1,000 HOUR SALTSPRAY TEST, MINIMUM, UNLESS SCHEDULES OR SPECIFICATIONSDICTATE A LONGER SALF SPRAY TEST (E.G. AIR HANDLING UNITS,EXTERIOR HEAT PUMPS). OUTSIDE AIR DUCTWORK AND ALL OUTSIDE,RELIEF, AND EXHAUST AIR PLENUMS SHALL BE 316L STAINLESS STEEL INTHEIR ENTIRETY.

REV. DATE DESCRIPTION

Page 9: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

AA

1

1

FF

2

2

GG

20

20

EE

BB

14

14

8

8

HH

BOYS R.R.

307

SCIENCE

317

PREP.

318SCIENCE

319

ELEV.

320

CLASSROOM

309

HALL

304

STAIR #2

311

STAIR #1

300

CLASSROOM

301

CLASSROOM

310

CLASSROOM

313

CLASSROOM

314

CLASSROOM

315CLASSROOM

316

CLASSROOM

302

GIRLS R.R.

306

MECHANICAL ROOM

308

HALL

312

20x16

JAN.

303

R.R.

305

EF-1

FSD

UP TO EF-7

UP TO EF-6

CC

7

7

3

3

4

4

5

5

6

6

9

9

10

10

11

11

12

12

15

15

18

18

16

16

17

17

13

13 19

19

DD

TU-1-301

TU-1-302

TU-1-304TU-1-305

TU-1-306

TU-1-307

TU-1-308

TU-1-309TU-1-310

TU-1-311

TU-1-312

CH-6 CH-7

TU-1-303TU-1-313

TU-1-314

UH-3

36x18

32x12

26x18

28x12

470CRG-1(TYP 2)

12"ø

235CD-1(TYP 4)

10"ø

12"ø

475CRG-1(TYP 2)

12"ø

240CD-1(TYP 2)

10"ø

235CD-1(TYP 2)

10"ø

12"ø

100CD-1(TYP 2)

8"ø

460CRG-1(TYP 2)

12"ø

230

CD-1(TYP 4)

10"ø

12"ø

475CRG-1(TYP 2)

12"ø

240CD-1(TYP 2)

10"ø

235CD-1(TYP 2)

10"ø

12"ø

450CRG-1(TYP 2)

12"ø225

CD-1(TYP 4)

10"ø

12"ø

450CRG-1(TYP 2)

12"ø

12"ø

225CD-1(TYP 4)

10"ø450

CRG-1(TYP 2)

12"ø225

CD-1(TYP 4)

10"ø

450CRG-1(TYP 2)

12"ø225

CD-1(TYP 4)

10"ø

12"ø12"ø

450CRG-1(TYP 2)

12"ø

225CD-1(TYP 4)

10"ø

400

CD-110"ø

12"ø

450CRG-1(TYP 2)

12"ø

225CD-1(TYP 4)

10"ø

150CD-18"ø

200CD-18"ø

NATURAL GAS BURNERVENTING UP TO ROOF (TYP)

NATURAL GAS BURNEROUTSIDE COMBUSTIONAIR INTAKE UP TO ROOF (TYP)

1

M402

3

M402

4

M402

AHU-1

44x32

38x22

36x2624x22

24x22

30x24

56x4056x40

10"ø 10"øAFMS

AFMS

8"ø38x22

16x1016x10 16x10

16x10

16x10

16x10

16x10

16x10

16x10

16x10

AFMS

AFMS

FSD TYP.

10x10

80CEG-1(TYP 2)

6"ø

240CEG-1(TYP 2)

10"ø

RS/RL PIPING

MD

21

21

I I

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:5

5 A

M

M203

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

TH

IRD

FLO

OR

PL

AN

-M

EC

HA

NIC

AL

THIRD FLOOR PLAN -MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

0' 4' 8' 16'

1/8" = 1'-0"

1 THIRD FLOOR PLAN - MECHANICAL

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

N O R T H

A. UNLESS OTHERWISE NOTED, BRANCH DUCTS TO TU TO BE THE SAMESIZE AS INLET.

GENERAL SHEET NOTES

B. UNLESS OTHERWISE NOTES, BRANCH DUCTS TO DIFFUSERS/GRILLES TOBE THE SAME SIZE AS DIFFUSER/GRILLE NECK.

C. ALL MATERIAL AND EQUIPMENT EXPOSED TO THE EXTERIOR AIR SHALLBE RATED FOR USE IN A COASTAL ENVIRONMENT VIA A 1,000 HOUR SALTSPRAY TEST, MINIMUM, UNLESS SCHEDULES OR SPECIFICATIONSDICTATE A LONGER SALF SPRAY TEST (E.G. AIR HANDLING UNITS,EXTERIOR HEAT PUMPS). OUTSIDE AIR DUCTWORK AND ALL OUTSIDE,RELIEF, AND EXHAUST AIR PLENUMS SHALL BE 316L STAINLESS STEEL INTHEIR ENTIRETY.

REV. DATE DESCRIPTION

Page 10: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

AA

1

1

FF

2

2

GG

20

20

EE

BB

14

14

8

8

HH

RC-2 RC-1

EF-6 EF-5

CC

7

7

3

3

4

4

5

5

6

6

9

9

10

10

11

11

12

12

15

15

18

18

16

16

17

17

13

13 19

19

DD

1

M402

21

21

I I

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:44:5

6 A

M

M205

JMMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

RO

OF

PL

AN

-M

EC

HA

NIC

AL

ROOF PLAN -MECHANICAL

04/19/2019

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

0' 4' 8' 16'

1/8" = 1'-0"

1 ROOF PLAN - MECHANICAL

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

N O R T H

REV. DATE DESCRIPTION

Page 11: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:45:1

2 A

M

M401

CheckerAuthor

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

ME

CH

AN

ICA

L S

EC

TIO

NS

AN

D I

SO

ME

TR

ICS

MECHANICAL SECTIONSAND ISOMETRICS

01/10/20

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

NO SCALE

1 MECHANICAL ROOM 215 ISOMETRIC

NO SCALE

2 MECHANICAL ROOM 308 ISOMETRIC

REV. DATE DESCRIPTION

Page 12: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

LEVEL 3128' - 0"

UPPER ROOF142' - 0"

ROOF156' - 0"

1411 12 13

40x56 40x56

RC-2 RC-1

24x38

MD

24x38

MD 10"ø

10"ø

26x36

22x3832x44

AHU-1

AFMS

LEVEL 3128' - 0"

UPPER ROOF142' - 0"

1112

10x16

AFMS

8"ø

8"ø

30x2424x22

14x22

10x1210x12

MDMDAFMS

AHU-2

AFMS

LEVEL 1100' - 0"

LEVEL 2114' - 0"

LEVEL 3128' - 0"

UPPER ROOF142' - 0"

F

28x30RETURN

22x24SUPPLY

18x28

14x20

RETURN

SUPPLY

8x26

575CRG-112"ø

FSD

FSD

18x3016x24

FSD

FSD

24x30

FSD

FSD

10x16 36x18

32x12

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:45:2

3 A

M

M402

CheckerAuthor

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

ME

CH

AN

ICA

L S

EC

TIO

NS

AN

D I

SO

ME

TR

ICS

MECHANICAL SECTIONSAND ISOMETRICS

01/10/20

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

0' 2' 4' 6'

3/8" = 1'-0"

1 AHU-1 SECTION

0' 2' 4' 6'

3/8" = 1'-0"

3 AHU-2 SECTION

0' 2' 4' 6'

3/8" = 1'-0"

4 SHAFT SECTION

NO SCALE

2 LEVEL 3 DUCT MAINS ISOMETRIC

REV. DATE DESCRIPTION

Page 13: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

SEAL WATERTIGHT

HOT MOP

AGA APPROVEDVENT TOP

STORM COLLAR

ROOFING

ROOF DECK

GAS VENT

CONE ROOFFLASHING

SEE FLOOR PLAN FOR SIZE.

MOTORIZED DAMPER.

ROOF DECK.

CANT STRIP.

FLASHING.

2x.

COUNTER FLASHING.

BIRD SCREEN.

8" MIN.

SEE FLOOR PLAN FOR

TYPE AND SIZE.

PENTHOUSE LOUVER.

CURB TIES.

GENERAL NOTES:

NOTES:

DUCT DUCT

"S" TYPE DUCT CONNECTION. DO NOT SCREW OR BOLT.

FIRE RATED PARTITION. COORDINATE WITH

ARCHITECTURAL FOR FRAMING AND FIRE RATED

LINING REQUIREMENTS.

COORDINATE PARTITION OPENING, 1/8" LARGER

THAN FIRE DAMPER SLEEVE PER FOOT OF WIDTH

OR HEIGHT.

PROVIDE SLEEVE 3" BEYOND EDGE OF PARTITION,

EACH SIDE.

FIRE DAMPER FRAME ATTACHED TO SLEEVE BY

MANUFACTURER.

ANGLE ALL AROUND SLEEVE MINIMUM 1" OVERLAP

WITH WALL FRAMING. ONE INCH FILLET WELDS 5"

MAX. ON CENTER, OR 1/4" BOLTS 5" MAX. ON

CENTER. DO NOT ATTACH ANGLES TO WALL.

COORDINATE WITH DAMPER MANUFACTURER FOR

APPROVED ANGLE SIZE AND GAUGE.

PROVIDE DUCT ACCESS DOOR. COORDINATE LOCATION

AND TYPE OF ARCHITECTURAL SERVICE ACCESS WITH

ARCHITECTURAL.

DETAIL INDICATES REQUIREMENTS FOR STANDARD

FRAME INSTALLATION. REFERENCE "SMACNA FIRE,

SMOKE AND RADIATION DAMPER INSTALLATION GUIDE"

FOR OTHER CONFIGURATION REQUIREMENTS. COMPLY

FULLY WITH ABOVE MENTIONED AND ALSO AHJ

REQUIREMENTS IN ALL CASES.

ASSEMBLY.

DAMPER

CAULKING

MATERIAL (TYP.).

DAMPER ACTUATOR. MOUNT EXTERNAL OF DUCT ON

DAMPER SLEEVE. BY DAMPER MANUFACTURER.

AIR FLOW

FUSIBLE LINK

ASSEMBLY.

1

2

3

4

5

6

7

8

1

2

3

6

5

7

8

4

6

CONNECT TO STRUCTURE.

CABLES IN EACH OF 4 DIRECTIONS.

PROVIDE SEISMIC RESTRAINT

45° MAX.

FAN.

IN-LINE

__"Ø STEEL THREADED ROD.

ENTIRE CONTACT AREA (TYP.).

NEOPRENE PAD OVER

SPRING VIBRATION

ISOLATORS (4 REQ'D.).

HANGER ROD (4 REQ'D.)

DUCT TRANSITION AS

REQUIRED.

SUPPORT FROM

STRUCTURE AS

REQUIRED.

FLEXIBLE CONN.

(TYP.).

MOUNTING

BRACKETS (TYP.).

.

SEE DETAIL [_/M_.__].

PIPE COVER.

ALUMINUM

FILL CAVITY WITH SPRAY FOAM INSULATION AIRTIGHT.

TO FAN/COIL UNIT.ROUTE REFRIGERATION PIPES

18 GA. SHEETMETAL CAP.

FLASHING.ROOFING AND

SILICONE SEAL.

ROOF.

GALV OR ZINC-A-LUME COVER.

INSULATED REFRIGERANT PIPES.

CONDENSING UNIT. MAINTAIN CLEARANCES AS SPECIFIED BY MANUFACTURER.

CURB (HEIGHT AS REQUIRED) SEE STRUCTURAL FOR ATTACHMENT TO ROOF.

[1/8"] AIRCRAFT CABLE. SEISMIC GUY WIRE TYP. OF FOUR SIDES. SECURELY FASTEN TO UNIT CURB.

METAL STUDS.

[5/8"] EYE BOLT ATTACHED WITH NUT AND WASHER BOTH SIDES.

[5/8"] EYE BOLT ATTACHED WITH NUT AND WASHER BOTH SIDES.

AIRCRAFT CABLE ATTACHMENT CAPABLE OF WITHSTANDING [80 LBS OF FORCE].

FILL VOID WITH RIGID FOAM INSULATIONTO MINIMIZE SOUND TRANSMISSION TO OCCUPIED SPACE.

SEE MIN. STRAIGHTRUN REQM'T. NOTE 3

NOTES:

INLET

UNIT CONTROLLER

REHEAT COIL SECTION

5"±TERMINAL UNIT

SLIP AND DRIVE CLEATCONNECTION, TYP

1. BRANCH DUCT SIZE TO MATCH UNIT INLET CONNECTION. FOR BRANCH DUCTS OVERFIVE FEET IN LENGTH, INCREASE BRANCH DUCT ONE SIZE AND PROVIDE TRANSITIONIMMEDIATELY UPSTREAM OF MINIMUM STRAIGHT DUCT RUN.

MINIMUM 5'-0" LONG LINED PLENUM EQUAL TO TERMINAL BOX OUTLET SIZE. PROVIDE WITH MYLAR LINING FOR OSHPD PROJECTS.

MINIMUM STRAIGHT DUCT RUN SHALL BE EQUAL TO 4 TIMES THE INLET DIAMETER OF TERMINAL UNIT.

FIRST BRANCH DUCT DOWNSTREAM OF TERMINAL MUST BE A MINIMUM OF 3 FEETDOWNSTEAM OF TERMINAL UNIT.

2.

3.

TRANSITION FITTING,MAX. 15°, WHEREREQUIRED

BRANCH DUCT,SEE NOTE 1

DISCHARGE LINEDPLENUM, SEE NOTE 2

TRANSVERSE AND LONGITUDINALSEISMIC BRACING (EACH SIDE)

3'-0" MINIMUM

FIRST BRANCH DUCT

4.

MEDIUMPRESSURE

DUCT

ATTACH HANGERS AND SEISMIC SUPPORTSTO STRUCTURE ABOVE PER CBCREQUIREMENTS

POSSIBLE AT UNDERSIDE OF ROOF

UNIT HEATER. MOUNT AS HIGH AS

(TYP.).

(SHEET METAL NOT ALLOWED)

IRON BRACING

[1-1/2"x1-1/2"x1/8"] ANGLE

SEISMIC RESTRAINT: PROVIDE

DOWNWARD ANGLE.

VANES AT 30°

SET AIR DEFLECTION

ROOF TRUSS.

3" PIPE.

[--] THREADED

ROD. 45°MAX.

45°

MAX. WELD 8" LONG (MIN) STEEL

STRUCTURE, UNLESS NOTED

OTHERWISE ON FLOOR PLANS.

BAR TO PIPE SUPPORT AT

EACH END OF PIPE.

NOTE:

ROOF DECK.

LAP SEALANT.

CLAMPING STRAP.

STAINLESS STEEL

MEMBRANE.

ROOFING

SPLICE ADHESIVE.

INSULATION.

RIGID

ALUMINUM

PIPE COVER.

USE ROOF MEMBRANE

MANUFACTURER'S

MATERIALS. PATCH

AND REPAIR ROOF TO

COMPLY WITH ALL

ROOF WARRANTIES.

PRE-FAB

PIPE FLASHING.

LAP SEALANT.

INSULATION

DAMPERBACKDRAFT(LEVEL)

PRE-FAB INSULATED

ROOFING MIN

.

12"

TRANSITION

SQUARE TO ROUND

ROOF CURB

WOOD NAILER

ON TOP OF CURBFOAM GASKET

EXHAUST DUCT

EXHAUST FAN

NOTE: SEE ARCH. AND STRUCT. DWGS FOR ROOF PENETRATION, FLASHING & ROOFING DETAILS.

DUCT TO BE SAME

AS DAMPER SIZE

1/4"ø HILTI W/2" EMBED @ 12"OCMIN. 3 PER SIDE

FASTEN TO STRUCTURE#10 SMS @ 8"OC MIN.4 PER SIDE

S.A.D #6 & #18 A431FOR FLASHING DETAIL

CONCRETE FILLOVER METAL DECK(SSD)

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:45:2

5 A

M

M701

CheckerAuthor

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

DE

TA

ILS

-M

EC

HA

NIC

AL

DETAILS - MECHANICAL

05/29/19

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

NO SCALE

1 GAS VENT BUILT-UP ROOF PENETRATION

NO SCALE

2 ROOF VENT CURB

NO SCALE

3 FIRE DAMPER

NO SCALE

4 IN-LINE FAN

NO SCALE

5 ROOFTOP CONDENSING UNIT CURB

NO SCALE

6 TYPICAL TERMINAL UNIT DUCTING (VAV OR CAV)

NO SCALE

7 UNIT HEATER INSTALLATION

NO SCALE

8 REFRIGERANT PIPING COVER PENETRATION

NO SCALE

9 EXHAUST FAN MOUNTING DETAIL1

REV. DATE DESCRIPTION

Page 14: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

DISCHARGE

LAG BOLT. TYPICALONE PER SIDE

NO SCALE

DETAIL A

3"

AIR INLET/OUTLET

EXHAUST DUCT,TYPE 1

2"

AIR SPACEMIN. 3 [6] INCHES

FIRE RATED ENCLOSURE

LEVELING CURB

FLASHING

1-1/2"x1-1/2"x1/8" ANGLEIRON FRAME. ALL WELDEDCONSTRUCTION

1/2" BIRDSCREENWELDED TO FRAME

SEALANT (TYP.)

3"x1-1/2" IRON TUBEWELDED TO FRAME

EXHAUST FAN

3"

NOTE:SEE ARCHITECTURALDRAWINGS FOR LEVELINGCURB CONSTRUCTION

ROOF

LEVELING CURB, CANT STRIP ANDFLASHING BY OTHERS

FIRE RATED ENCLOSURE BYGENERAL CONTRACTOR.

AIR SPACE PER CODE

SEE DETAIL AFOR ENLARGED VIEW.

CONSTRUCT GREASE HOODEXHAUST DUCT OF 16GAUGE GALVANIZED STEELWITH CONTINUOUS WELDEDSEAMS AND JOINTS

UPBLAST TYPEEXHAUST FAN

18 GAUGE GALVANIZEDCOUNTERFLASHING TOPROTECT AIRSPACE

GREASE WATERDRAIN

.

.

.

DIS

CH

AR

GE

HE

IGH

T T

O B

E D

IRE

CT

ED

BY

LO

CA

L C

OD

ES

AIR SPACE PER CODE

RATED ENCLOSURE

ROOF CURB

RAIN SKIRT

BIRD SCREEN.

EXHAUST DUCT

ROOFING

ROOF DECK

CONTINUOUS WELD LIQUIDTIGHT ALL AROUND

3" OPENING

FLASHING

1-1/2"x1-1/2" ANGLE TOP,BOTTOM AND CORNERS,WELDED CONSTRUCTION

DOWN TO TYPE 1 HOOD

.

SLOPE DUCTFOR DRAINAGE

SLOPE FOR DRAINAGE

WALL

CAULK JOINTS(TYP.)

SEAL WATERTIGHT WITH FLEXIBLE NON-HARDENING SEALER

LOUVERED EXHAUSTGRILLE

PACK ANNULAR SPACE WITH FIBERGLASS OR MINERAL WOOL

DUCT HANGER EACH SIDE OF OPENING (ONLYONE SHOWN) 1' MAX. FROM FACE OF WALL

FLEXIBLE DUCT - MAX 5'-0".

CEILING.CONNECT AIR INLET OR OUTLET TO ELBOW

PER MANUFACTURER'S INSTRUCTIONS.

SHEET METAL DUCT.

VOLUME DAMPER PER

SPECIFICATIONS (NOT

FURNISHED W/SPIN-IN).

DUCT SMOKE DETECTOR

SEQUENCEa. FSD SHALL CLOSE AT ANY OF THE FOLLOWING CONDITIONS:b. DETECTION OF SMOKE BY LOCAL DUCT SMOKE DETECTOR.c. LOSS OF POWER.d. SIGNED FROM FACP.

RATED WALL OPENING TO

EXCEED NET O.D. OF SLEEVE

BY 1/8" FOR EACH FT. OF

WIDTH & HEIGHT OF DAMPER

ASSEMBLY.

STATE FIRE MARSHALL/U.L.

APPROVED FIRE DAMPER.

SHT. MTL. SLEEVE

10 GA. ANGLE FRAMEBOLTED TO ALL FOUR SIDESOF SLEEVE W/ 1/4" BOLTSAT 4"O.C.,FRAME SHALL LAPWALL OPN'G BY 1" (MIN).

STUD WALL

10x10 HINGEDINSPECTION DOOR

NOTES:

1. USE "UNITED DUCT SEALER" OR EQUAL WHERE DUCTS CONNECT TO SLEEVE.

2. IF ROUND DUCT, PROVIDE WELDED ROUND DUCT COLLAR ON BOTH SIDES. SIMILAR TO HIGH VELOCITY FIRE DAMPER. OPENING SIZE = DUCT SIZE + 1".

FLEXIBLE DUCT - MAX 5'-0".

CEILING.

DUCT DIA.PLUS 2".

STRAP HANGERSTO STRUCTURE.

NECK WIDTHPLUS 2".

SPIN IN FITTING.

CONNECT AIR INLET OR OUTLET TO PLENUM

PER MANUFACTURER'S INSTRUCTIONS.

VOLUME DAMPER PER

SPECIFICATIONS (NOT

FURNISHED W/SPIN-IN).

SHEET METAL PLENUM WITH

1" FIBERGLASS LINING.

MINIMUM

CONNECTION. SUPPORT FLEXPROVIDE SMOOTH RADIUS

1.5 x RADIUS

HANGER STRAP

FLEX DUCT WHEREAPPLICABLE. SEE PLAN FOR SIZE

SECURE TO STRUCTURE

PROVIDE 2 ANGLECLIPS ON OPPOSITESIDES OF DIFFUSER

SCREW TO T-BAR

FLOW TO DIFFUSERDUCT FOR SMOOTH AIR

FACTORY MOUNTED SHEET METAL END COLLAR SECURE WITH 3 SHEET METAL SCREWS & SEAL

2. SIMILAR FOR GYP BOARD CEILING.

SHEET METAL BOOT

2"MIN.

MIN.2"

FACTORY MOUNTED SHEET

PLAN FOR SIZE

CEILINGSUSPENDED

CEILING DIFFUSERLAY-IN T-BAR

DIFFUSER FACE

EACH SIDE (TYP.)2 SHEET METAL SCREWS

SCREW TO T-BARSIDES OF DIFFUSERCLIPS ON OPPOSITE

PROVIDE 2 ANGLE

TO STRUCTURE (2)HANGER STRAP SECURE

1. USE THIS DETAIL WHERE 1.5 x RADIUS ON FLEXIBLE DUCT IS NOT POSSIBLE.

METAL SCREWS & SEALSECURE WITH 3 SHEET

METAL END COLLAR

NOTES:

FLEX DUCT. SEESHEET METAL SCREW

(2 PER HANGER)

CEILING DIFFUSERLAY-IN T-BAR

DIFFUSER FACE

CEILINGSUSPENDED

NOTES:

FOLLOW DETAIL ABOVE.

2. SIMILAR FOR GYP BOARD, SPLINE CEILING.

1. USE MOUNTING DETAIL WHERE SPACE PERMITS. WHERE SPACE DOES NOT PERMIT

BEHIND).

ADJUSTABLE EXTRACTOR

SUPPLY GRILLE (WITH

CEILING STRUCTURE.

SPIRAL WOUND

SUPPLY DUCT.

6"

30° OFFSET FROM

HORIZONTAL.

SUSPEND DUCTS WITH

THREADED HANGER

RODS AND CONNECT

TO SHEET METAL

HANGER STRAP.

TAKE-OFF BOX SHALL

BE SIZED SUCH THAT

FACE GRILLE FITS

FLUSH WITH EDGES OF

TAKE-OFF BOX.

MANUAL VOLUME DAMPER

NOTE:SEE ARCHITECTURAL OR

STRUCTURAL DRAWINGS.

STRUCTURAL DRAWINGS.

ARCHITECTURAL OR

AS INDICATED ON

LEVELING CURB.

CONCRETE SLAB/TUB

HVAC UNIT

RUBBER GASKET.

NAILER STRIP.

SOUND CONTROL THRU

BOTTOM OF UNIT.

DETAIL UTILIZED FOR

ROOF DECK.

INSULATION.

ROOFING.

RIGID INSULATION.

COUNTER FLASHING.

ROOF

CANT STRIP.

PREMANUFACTURED

AC UNIT CURB.

CURB.

ROOF DECK.

SOLDER WATERTIGHT

COUNTER FLASHING,

ROOFING.

FLASHING.

TO DUCT.

1/4"x1/4" MESH.

BIRD SCREEN

VERIFY DISCHARGE

HEIGHT WITH LOCAL

CODE REQUIREMENTS.

18" MINIMUM HEIGHT.

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:45:2

7 A

M

M702

CheckerAuthor

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

DE

TA

ILS

-M

EC

HA

NIC

AL

DETAILS - MECHANICAL

01/28/20

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

NO SCALE

1 GREASE HOOD ROOF EXHAUST FAN

NO SCALE

2 GREASE EXHAUST DUCT ROOF PENETRATION

NO SCALE

3 LOUVERED EXHAUST GRILLE WALL PENETRATION

NO SCALE

4 AIR INLET OR OUTLET ROUND NECK

NO SCALE

6 FIRE & SMOKE DAMPER

NO SCALE

5 AIR INLET OR OUTLET SQUARE NECK

NO SCALE

7 CEILING DEFFUSER CONNECTION DETAIL

NO SCALE

8 SUPPLY DUCT TAKE-OFF

NO SCALE

9 AC UNIT CURB

NO SCALE

10 GOOSENECK - RECTANGULAR DUCT

REV. DATE DESCRIPTION

Page 15: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

VFD VFD

8"

5'-0"

26'-8"

13'-2" 13'-6"

1'-8" 2'-0" 2'-8" 2'-8" 1'-10" 3'-8" 2'-0" 2'-4" 3'-2" 2'-2" 2"2"

RETURNPLENUM

RETURNFAN ARRAY

FILTERS INDIRECT GAS HEATER

DX COOLINGCOIL

SUPPLYFAN ARRAY

SUPPLYPLENUM

2'-2"

CONTROL BOX CONTROL BOX

9'-0"9'-8"

2"

8"

GAS VENT

VFD VFD

VFD VFD

6"

2'-4"

20'-8"

10'-0" 10'-8"

1'-10" 2'-0" 1'-8" 1'-8" 1'-10" 2'-10" 2'-0" 2'-0" 2'-4" 1'-4" 2"2" 10"

CONTROL BOX CONTROL BOX

3'-8"4'-4"

2"

8"

GAS VENT

RETURNPLENUM

RETURNFAN ARRAY

FILTERS INDIRECT GAS HEATER

DX COOLINGCOIL

SUPPLYFAN ARRAY

SUPPLYPLENUM

VFD VFD

6"

5'-0"

25'-2"

12'-8" 12'-6"

1'-6" 2'-0" 2'-8" 2'-8" 1'-10" 3'-0" 2'-0" 2'-8" 2'-8" 2'-0" 2"2" 1'-10"

CONTROL BOX CONTROL BOX

3'-8"4'-4"

2"

RETURNPLENUM

RETURNFAN ARRAY

FILTERS INDIRECT GAS HEATER

DX COOLINGCOIL

SUPPLYFAN ARRAY

SUPPLYPLENUM

8"

GAS VENT

VFD VFD

6"

5'-0"

CONTROL BOX CONTROL BOX

3'-8"4'-4"

2"

25'-6"

12'-6" 13'-0"

1'-6" 2'-0" 2'-8" 2'-6" 1'-10" 3'-6" 2'-0" 2'-8" 2'-8" 2'-0" 2"2" 1'-10"

8"

GAS VENT

RETURNPLENUM

RETURNFAN ARRAY

FILTERS INDIRECT GAS HEATER

DX COOLINGCOIL

SUPPLYFAN ARRAY

SUPPLYPLENUM

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:45:3

0 A

M

M703

CheckerAuthor

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

AH

U D

ET

AIL

S -

ME

CH

AN

ICA

L

AHU DETAILS -MECHANICAL

01/28/20

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

NO SCALE

1 AHU-1 DIAGRAM

NO SCALE

2 AHU-2 DIAGRAM

NO SCALE

3 AHU-3 DIAGRAM

NO SCALE

4 AHU-4 DIAGRAM

REV. DATE DESCRIPTION

Page 16: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

DX

T

SP

25

31

SUPPLY AIRTO SPACE

SUPPLY FAN ARRAYSEE PLANS FOR NUMBER OF FANS

DX COOLING COIL

RELIEFTO OUTSIDE

12

SF

8

7

CT6

9

11 MD

POINTS LIST

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

VAV AIR HANDLER X DIAGRAMMATIC SYSTEM GRAPHIC

OUTSIDE AIR TEMPERATURE

RETURN AIR TEMPERATURE

RELIEF AIR DAMPER

RETURN AIR DAMPER POSITION FEEDBACK

1

OUTSIDE AIRFLOW MEASURING STATION

FILTER DIFFERENTIAL PRESSURE SENSOR

MIXED AIR TEMPERATURE

SUPPLY FAN START/STOP

SUPPLY FAN ECM SPEED

SUPPLY AIR TEMPERATURE

DUCT SUPPLY AIR STATIC PRESSURE

ZONE TEMPERATURE

RELIEF AIR DAMPER POSITION FEEDBACK

RETURN AIR DAMPER

SUPPLY FAN ECM ALARM STATUS

X

X

X

X

X

X

X

X

X

X X

X

X

X

X

OUTSIDE AIR DAMPER

OUTSIDE AIR DAMPER POSITION FEEDBACK X

X

SUPPLY FAN STATUS (CT SWITCH)

X

T

28

FILTERV-BANK

NATURAL GASFURNACE

RETURN FAN ARRAY

MD

OA FROMLOUVER

CONDENSING UNITFACTORY CONTROLLER CO2

30

ZONE CO2SENSOR

29

ZONETEMPERATURE

T

SD

SMOKE DETECTORBY DIVISION 28

T

26

24 AF

DP

2113 14

15

16 MD

27

EXTERIORWALL

T

MIXED AIRTEMPERATURE

X ALARM, FAIL

RF

3

2

CT1

4

RETURN FAN STATUS (CT SWITCH)

RETURN FAN ECM ALARM STATUS

RETURN FAN START/STOP

RETURN FAN ECM SPEED

X

X X ALARM, FAIL

X

X

DISCHARGE AIRTEMPERATURE

OUTSIDE AIR TEMP

ECM

NOTE: CONTROLS CONTRACTOR SHALL COORDINATE WITH THE AIR HANDLING UNIT / CONDENSING UNIT MANUFACTURER TO ENSURE CONTROLS ARE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

GENERAL OPERATION:

THE AIR HANDLING UNIT SHALL OPERATE CONTINUOUSLY TO PROVIDE A VARIABLE VOLUME OF CONDITIONED SUPPLY AIR TO MULTIPLE INDEPENDENTLY CONTROLLED TEMPERATURE ZONES. OPERATION OF THE AIR HANDLING UNIT SHALL BE VIA THE BUILDING AUTOMATION SYSTEM WITH FACTORY CONTROL OF NATURAL GAS HEATING AND DX COOLING OPERATION.

OCCUPIED MODE - DAMPER AND FAN OPERATION

THE AIR HANDLING UNIT SHALL BE CONSIDERED IN OCCUPIED MODE ONLY DURING NORMAL DAYTIME SCHOOL HOURS OR AS SCHEDULED BY FACILITIES MAINTENANCE STAFF. A START SIGNAL SHALL BE SENT FROM THE BAS TO THE AIR HANDLING UNIT PLACING IT IN OCCUPIED MODE. UPON RECEIPT OF THE “START” SIGNAL, THE FOLLOWING STARTUP SEQUENCE OF EVENTS SHALL OCCUR:

2-POSITION MOTORIZED DAMPERS AT RESPECTIVE OUTSIDE AIR INTAKE AND EXHAUST LOUVERS TO OPEN. DAMPERS SHALL BE PROVEN OPEN BY END SWITCH. A START SIGNAL SHALL NOT BE SENT IF DAMPERS FAIL TO OPEN.

AIR HANDING UNIT OUTSIDE AND RELIEF AIR DAMPERS SHALL OPEN TO MINIMUM POSITIONS AS DETERMINED BY THE AIRSIDE BALANCING CONTRACTOR. AIR HANDLING UNIT RETURN AIR DAMPER TO OPEN TO ITS MAXIMUM POSITION. PROVIDE SUFFICIENT DELAY IN FAN START/STOP TO ALLOW DAMPERS TO OPEN/CLOSE WITHOUT CAUSING DUCT DAMAGE. PROVIDE SUFFICIENT DELAY IN FAN START/STOP TO ALLOW DAMPERS TO OPEN/CLOSE WITHOUT CAUSING DUCT DAMAGE.

NORMALLY CLOSED FIRE SMOKE DAMPERS IN DISTRIBUTION DUCTWORK OPEN. PROVIDE SUFFICIENT DELAY IN FAN START/STOP TO ALLOW FIRE SMOKE DAMPERS TO OPEN/CLOSE WITHOUT CAUSING DUCT DAMAGE.

ALARM BAS IF DAMPERS FAIL TO OPEN OR CLOSE WHEN COMMANDED.

OCCUPED MODE - SUPPLY FAN OPERATION

THE UNIT CONTROLLER SHALL SEND A “START” COMMAND TO THE ZONE-AHU SUPPLY FAN ARRAY. THE SUPPLY FANS SHALL RAMP UP SLOWLY UNTIL THE FAN STABILIZES AT THE ESTABLISHED MOTOR SPEED SETPOINT AS DETERMINED BY THE AIRSIDE BALANCING CONTRACTOR.

REMOTE DUCT STATIC PRESSURE SENSOR SIGNALS CONTROLLER WHICH MODULATES SUPPLY FAN SPEED TO MAINTAIN REQUIRED STATIC PRESSURE SETPOINT AS DETERMINED BY THE AIRSIDE BALANCING CONTRACTOR. STATIC PRESSURE SETPOINTS CONTINUOUSLY RESET TO MAINTAIN AT LEAST TWO TERMINAL UNITS WITH 100% DAMPER POSITION WHILE MAINTAINING SPACE TEMPERATURE SETPOINTS.

ALARM BAS SYSTEM IF COMMAND TO ENERGIZE SUPPLY FAN IS GIVEN BUT CURRENT IS NOT SENSED THROUGH THE DIGITAL CURRENT SENSING DEVICE. ALARM BAS AT HIGH SUPPLY FAN DISCHARGE PRESSURE CONDITION.

OCCUPIED MODE - RETURN FAN OPERATION

THE UNIT CONTROLLER SHALL SEND A “START” COMMAND TO THE AHU RETURN FAN ARRAY. THE RETURN FANS SHALL RAMP UP SLOWLY UNTIL THE FAN-GENERATED STATIC PRESSURE STABILIZES AT THE ESTABLISHED MOTOR SPEED AS DETERMINED BY THE AIRSIDE BALANCING CONTRACTOR.

AIRFLOW MEASURING STATIONS LOCATED IN SUPPLY AND RETURN FANS SIGNAL CONTROLLER WHICH MODULATES RETURN FAN AIRFLOW ACCORDING TO THE FOLLOWING EQUATION: RETURN FAN CFM = SUPPLY FAN CFM - BUILDING EXHAUST FAN CFM - BUILDING PRESSURIZATION. EXHAUST FAN CFM IS BASED ON SUM OF EXHAUST AIRFLOWS. BUILDING PRESSURIZATION AIRFLOW IS 5% OF MAXIMUM SUPPLY FAN CAPACITY.

ALARM BAS SYSTEM IF COMMAND TO ENERGIZE RETURN FAN ARRAY IS GIVEN BUT CURRENT IS NOT SENSED THROUGH THE DIGITAL CURRENT SENSING DEVICE. ALARM BAS AT LOW PRESSURE CONDITION AT RETURN FAN INLET.

OCCUPIED MODE - DX COOLING COIL AND NATURAL GAS BURNER OPERATION

FACTORY CONTROLS OF THE CONDENSING UNIT AND NATURAL GAS BURNER SHALL MODULATE COOLING AND HEATING AS REQIURED TO MAINTAIN THE SUPPLY AIR TEMPERATURE BASED ON A HEATING OR COOLING DEMAND SIGNAL BY THE BAS.

SUPPLY AIR TEMPERATURE SHALL BE RESET AS PER THE BELOW TABLE:

SUPPLY AIR TEMPERATURE RESET:

SAT SETPOINT TEMPERATURE SHALL BE AS FOLLOWS:

*IF OUTSIDE AIR TEMPERATURE (OAT) >=70 °F:* “SA TEMP SETPOINT” SHALL DEFAULT TO T-MIN = 55°F (ADJ).

*IF 55°F < OAT < 70 °F:“SAT SETPOINT” SHALL VARY INVERSELY PROPORTIONAL WITH OAT SUCH THAT:

* “SAT SETPOINT” AT [55 °F OAT] = 65 °F (T-MAX) * “SAT SETPOINT” AT [85 °F OAT] = 55° F (T-MIN)

ECM

17

DX COOLING DEMAND X

SP

10

SUPPLY FAN HIGH PRESSURE SWITCH

SP

5

RETURN FAN LOW PRESSURE SWITCH(LOW PRESSURE ALARM)

SUPPLY FAN HIGH PRESSURE SWITCH X X

RETURN FAN LOW PRESSURE SWITCH X X

ALARM, HIGH

ALARM, LOW

18

X

RETURN AIRTEMPERATURE

N.C.

OUTSIDE AIR

OUTSIDE AIR FLOW WILL BE MONITORED AND CONTROLLED BY AN AIR FLOW STATION AND MOTORIZED DAMPER AT THE AIR HANDLER. WHEN THE ZONE AHU IS ACTIVATED, THE VENTILATION OSA DAMPER WILL MODULATE TO MAINTAIN THE SPECIFIED MINIMUM OUTSIDE AIRFLOW. THE BAS WILL MONITOR CO2 CONCENTRATIONS IN THE ZONES IN REFERENCE TO A PRE-DETERMINED SITE-SPECIFIC CO2 LEVEL. IF A ZONE CO2 LEVEL EXCEEDS 900 PPM, THE VENTILATION OSA FLOW SHALL MODULATE UP TO A MAXIMUM OF 125% OF SPECIFIED MINIMUM OCCUPIED AIRFLOW. SEE PRESSURIZATION CONTROL FOR OTHER CONSTRAINTS ON VENTILATION OSA TURNDOWN.

THE CONTROLLER SHALL CONTINUOUSLY MONITOR THE OUTSIDE AIR TEMPERATURE IN REFERENCE TO THE RETURN AIR TEMPERATURE. IF IT IS DETERMINED THAT THE COOLING DEMAND CAN BE MET FULLY OR PARTIALLY USING THE OUTSIDE AIR, THE UNIT SHALL MODULATE THE OUTSIDE AND RELIEF AIR DAMPERS TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. DX COOLING SHALL MODULATE TO TRIM THE SUPPLY AIR TEMPERATURE TO MEET SETPOINT.

UNOCCUPIED MODE

OPTIMUM START: THE AIR HANDLING UNIT SHALL BE PROGRAMMED WITH AN "OPTIMUM START" TIMING ALGORITHM TO EFFFECTIVELY BRING THE SPACES FROM AN UNOCCUPIED-SETBACK OCCUPANCY SUITABLE CONDITIONS PRIOR TO SCHEDULED OCCUPIED PERIODS. HISTORICAL RUNTIME START-UP DATA SHALL BE UTILIZED TO INITIATE AN ANTICIPITAORY PRE-CONDITIONING OF THE ZONE, PRIOR TO THE SCHEDULED OCCUPIED MODE SUCH THAT SETPO0INT CONDTIIONS ARE MET NO SOONER THAN 10 MIN. PRIOR TO SCHEDULED OCCUPANCY.

NIGHT SETBACK AND SETUP: SUPPLY AND RETURN FANS OPERATE WHEN ANY SPACE TEMPERATURE DROPS TO 60 DEGREES F OR BELOW OR RISES TO 85 DEGREES F OR ABOVE IN DESIGNATED ZONES. MAINTAIN FAN OPERATION UNTIL SPACE TEMPERATURE RISES TO 63 DEGREES F (HEATING) OR DROPS TO 82 DEGREES F (COOLING). ASSOCIATED EXHAUST FANS TO REMAIN OFF DURING UNOCCUPIED OPERATION. WHEN FANS OPERATE, OUTDOOR AND RELIEF AIR DAMPERS ARE CLOSED, AND RETURN AIR DAMPER OPEN.

NIGHT PURGE: NIGHT PURGE SHALL BE INITIATED WHENEVER OUTDOOR AIR TEMPERATURE IS 65 DEGREES F OR BELOW AND ANY SPACE TEMPERATURE IS 75 DEGREES F OR ABOVE. SUPPLY AND RETURN FANS OPERATE DURING NIGHT PURGE. DURING NIGHT PURGE OUTSIDE AIR DAMPER OPENS, RELIEF AIR DAMPER OPENS, RETURN AIR DAMPER CLOSES, AND HEATING/COOLING DISABLED. WHEN SPACES ARE 70 DEGREES F OR BELOW FOR 30 MINUTES, SWITCH TO SHUTDOWN MODE.

WARM-UP CONTROL: OPTIMAL START PROGRAM INITIATES WARM-UP CONTROL. SUPPLY AND RETURN FANS OPERATE DURING WARM-UP. DURING WARM-UP MODE OUTDOOR AND RELIEF AIR DAMPERS CLOSED, RETURN AIR DAMPERS OPEN, NATURAL GAS HEATING TO MAINTAIN 90 DEG. F (adj.) DISCHARGE AIR TEMPERATURE. WHEN RETURN AIR TEMPERATURE REACHES 70 F, SWITCH TO OCCUPIED MODE.

UNOCCUPIED MODE OVERRIDE: UPON RECEIVING AN 'OVERIDE' SIGNAL FROM DESIGNATED SPACE TEMPERATURE SENSORS, CONTROLLER CHANGES BUILDING TO WARM-UP CONTROL, AND THEN TO OCCUPIED MODE FOR A PERIOD OF 2 HOURS (ADJ.). COORDINATE LOCATION OF (2) SENSORS WITH OWNER.

FIRE ALARM SHUTDOWN

WHEN THE FIRE ALARM SENSES A SMOKE CONDITION AT A DUCT OR AREA SMOKE DETECTOR, ALL FANS WILL BE STOPPED. FAN SYSTEMS MAY BE MANUALLY RESTARTED WHEN PERMITTED BY THE FIRE ALARM SYSTEM.

N.O.

N.C.

EXTERIORWALL

ES

MDN.C.

34

35

OUTDOOR AIRINTAKE ISOLATIONDAMPER AT PLENUM

ES

MD N.C.

32

33

RELIEF AIRDISCHARGE ISOLATIONDAMPER AT PLENUM

RELIEF AIR ISOLATION DAMPER POSITION

OUTSIDE AIR DAMPER END SWITCH

ALARM, FAIL

ALARM, FAIL

RELIEF AIR DAMPER END SWITCH

OUTSIDE AIR ISOLATION DAMPER POSITION

X X

X

X

X

X

DUCT PRESSURE SENSORLOCATE 2/3 OF THE LENGTHOF THE SUPPLY DUCT.

FIELD VERIFY EXACT LOCATION.

UNIT RETURN AIRDAMPER

AF

22

OUTDOOR AIRMEASURING STATION

SUPPLY AIRMEASURING STATION

SUPPLY AIRFLOW MEASURING STATION

RETURN AIRFLOW MEASURING STATION

INTERIORWALL

INTERIORWALL

23

AF

19

CONDENSING UNIT STATUS

20

BURNER CONTROLMODULE BY AHU MANUFACTURER

NG BURNER STATUS ALARM, FAILX X

NATURAL GAS HEATING DEMAND

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

2122

23

24

25

26

27

28

29

31

32

33

34

35

X

X

X

X

X

X

ZONE CO2 LEVEL30 X

X ALARM, FAIL

X

ALARM, FAIL

ALARM, FAIL

ALARM, FAIL

X ALARM, FAIL

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:45:3

2 A

M

M801

CheckerAuthor

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

CO

NT

RO

L D

IAG

RA

MS

-M

EC

HA

NIC

AL

CONTROL DIAGRAMS -MECHANICAL

09/18/19

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

NO SCALE

1 VARIABLE-VOLUME AHU CONTROL DIAGRAM (AHUs-1,2)

REV. DATE DESCRIPTION

Page 17: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

POINTS LIST

NOTE: CONTROLS CONTRACTOR SHALL COORDINATE WITH THE AIR HANDLING UNIT/CONDENSING UNIT MANUFACTURER TO ENSURE CONTROLS ARE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS.

GENERAL OPERATION:

THE AIR HANDLING UNIT SHALL OPERATE CONTINUOUSLY TO PROVIDE A CONSTANT VOLUME OF CONDITIONED SUPPLY AIR TO A SINGLE TEMPERATURE CONTROL ZONE. OPERATION OF THE AIR HANDLING UNIT SHALL BE VIA THE BUILDING AUTOMATION SYSTEM WITH FACTORY CONTROL OF NATURAL GAS HEAT AND DX COOLING OPERATION.

OCCUPIED MODE - DAMPER AND FAN OPERATION

THE AIR HANDLING UNIT SHALL BE CONSIDERED IN OCCUPIED MODE ONLY DURING NORMAL DAYTIME SCHOOL HOURS OR AS SCHEDULED BY FACILITIES MAINTENANCE STAFF. A START SIGNAL SHALL BE SENT FROM THE BAS TO THE AIR HANDLING UNIT PLACING IT IN OCCUPIED MODE. UPON RECEIPT OF THE “START” SIGNAL, THE FOLLOWING STARTUP SEQUENCE OF EVENTS SHALL OCCUR:

2-POSITION MOTORIZED DAMPERS AT RESPECTIVE OUTSIDE AIR INTAKE AND EXHAUST LOUVERS TO OPEN. DAMPERS SHALL BE PROVEN OPEN BY END SWITCH. A START SIGNAL SHALL NOT BE SENT IF DAMPERS FAIL TO OPEN. PROVIDE SUFFICIENT DELAY IN FAN START/STOP TO ALLOW DAMPERS TO OPEN/CLOSE WITHOUT CAUSING DUCT DAMAGE.

AIR HANDING UNIT OUTSIDE AND RELIEF DAMPERS SHALL OPEN TO MINIMUM POSITIONS AS DETERMINED BY T&B. AIR HANDLING UNIT RETURN AIR DAMPER TO OPEN TO ITS MAXIMUM POSITION. DAMPERS TO BE PROVEN OPEN VIA END SWITCHES. A START COMMAND SHALL NOT BE SENT IF DAMPERS FAIL TO OPEN. PROVIDE SUFFICIENT DELAY IN FAN START/STOP TO ALLOW DAMPERS TO OPEN/CLOSE WITHOUT CAUSING DUCT DAMAGE.

NORMALLY CLOSED FIRE SMOKE DAMPERS IN DISTRIBUTION DUCTWORK OPEN. PROVIDE SUFFICIENT DELAY IN FAN START/STOP TO ALLOW FIRE SMOKE DAMPERS TO OPEN/CLOSE WITHOUT CAUSING DUCT DAMAGE.

ALARM BAS IF DAMPERS FAIL TO OPEN OR CLOSE WHEN COMMANDED.

OCCUPED MODE - SUPPLY FAN OPERATION

THE UNIT CONTROLLER SHALL SEND A “START” COMMAND TO THE ZONE-AHU SUPPLY FAN ARRAY. THE SUPPLY FANS SHALL RAMP UP SLOWLY UNTIL THE FAN REACHES THE ESTABLISHED MOTOR SPEED AS DETERMINED BY THE AIRSIDE BALANCING CONTRACTOR.

THE SUPPLY FAN SPEED SHALL MODULATE TO MAINTAIN ZONE TEMPERATURE SETPOINT. THE FAN SPEED SHALL INCREASE AS THE ZONE TEMPERATURE RISES ABOVE COOLING SETPOINT, OR AS THE ZONE TEMPERATURE DROPS BELOW THE HEATING SETPOINT. THE SUPPLY FAN SPEED SHALL NOT DROP BELOW 60% OF THE SCHEDULED AIRFLOW FOR BOTH AIR HANDLING UNITS TO MAINTAIN MINIMUM OUTSIDE AIR REQUIREMENTS. COORDINATE WITH TESTING AND BALANCING CONTRACTOR.

ALARM BAS SYSTEM IF COMMAND TO ENERGIZE SUPPLY FAN IS GIVEN BUT CURRENT IS NOT SENSED THROUGH THE DIGITAL CURRENT SENSING DEVICE. ALARM BAS AT HIGH SUPPLY FAN DISCHARGE PRESSURE CONDITION.

OCCUPIED MODE - RETURN FAN OPERATION

THE UNIT CONTROLLER SHALL SEND A “START” COMMAND TO THE AHU RETURN FAN ARRAY. THE RETURN FANS SHALL RAMP UP SLOWLY UNTIL THE FAN REACHED AT THE ESTABLISHED MOTOR SPEED AS DETERMINED BY THE AIRSIDE BALANCING CONTRACTOR.

AIRFLOW MEASURING STATIONS LOCATED IN SUPPLY AND RETURN FANS SIGNAL CONTROLLER WHICH MODULATES RETURN FAN AIRFLOW ACCORDING TO THE FOLLOWING EQUATION: RETURN FAN CFM = SUPPLY FAN CFM - BUILDING EXHAUST FAN CFM - BUILDING PRESSURIZATION. EXHAUST FAN CFM IS BASED ON SUM OF EXHAUST AIRFLOWS. BUILDING PRESSURIZATION AIRFLOW IS 5% OF MAXIMUM SUPPLY FAN CAPACITY.

ALARM BAS SYSTEM IF COMMAND TO ENERGIZE RETURN FAN ARRAY IS GIVEN BUT CURRENT IS NOT SENSED THROUGH THE DIGITAL CURRENT SENSING DEVICE. ALARM BAS AT LOW PRESSURE CONDITION AT RETURN FAN INLET.

OCCUPIED MODE - DX COOLING COIL AND NATURAL GAS BURNER OPERATION

FACTORY CONTROLS OF THE CONDENSING UNIT AND NATURAL GAS BURNER SHALL MODULATE COOLING AND HEATING AS REQUIREDTO MAINTAIN THE SUPPLY AIR TEMPERATURE BASED ON A HEATING OR COOLING DEMAND SIGNAL BY THE BAS.

OUTSIDE AIR

OUTSIDE AIR FLOW WILL BE MONITORED AND CONTROLLED BY AN AIR FLOW STATION AND MOTORIZED DAMPER AT THE AIR HANDLER. WHEN THE ZONE AHU IS ACTIVATED, THE VENTILATION OSA DAMPER WILL MODULATE TO MAINTAIN THE SPECIFIED MINIMUM OUTSIDE AIRFLOW. THE BAS WILL MONITOR CO2 CONCENTRATIONS IN THE ZONES IN REFERENCE TO A PRE-DETERMINED SITE-SPECIFIC CO2 LEVEL. IF A ZONE CO2 LEVEL EXCEEDS 900 PPM, THE VENTILATION OSA FLOW SHALL MODULATE TO MINIMUM SCHEDULED OUTSIDE AIR VALUE. IF ZONE CO2 LEVEL FALLS BELOW 900 PPM, THE OUTSIDE AIR DAMPER SHALL MODULATE CLOSED TO THE SCHEDULED DCV MIN. VALUE.

THE CONTROLLER SHALL CONTINUOUSLY MONITOR THE OUTSIDE AIR TEMPERATURE IN REFERENCE TO THE RETURN AIR TEMPERATURE. IF IT IS DETERMINED THAT THE COOLING DEMAND CAN BE MET FULLY OR PARTIALLY USING THE OUTSIDE AIR, THE UNIT SHALL MODULATE THE OUTSIDE AND RELIEF AIR DAMPERS TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. DX COOLING SHALL MODULATE TO TRIM THE SUPPLY AIR TEMPERATURE TO MEET SETPOINT.

UNOCCUPIED MODE

OPTIMUM START: THE AIR HANDLING UNIT SHALL BE PROGRAMMED WITH AN "OPTIMUM START" TIMING ALGORITHM TO EFFFECTIVELY BRING THE SPACES FROM AN UNOCCUPIED-SETBACK OCCUPANCY SUITABLE CONDITIONS PRIOR TO SCHEDULED OCCUPIED PERIODS. HISTORICAL RUNTIME START-UP DATA SHALL BE UTILIZED TO INITIATE AN ANTICIPITAORY PRE-CONDITIONING OF THE ZONE, PRIOR TO THE SCHEDULED OCCUPIED MODE SUCH THAT SETPO0INT CONDTIIONS ARE MET NO SOONER THAN 10 MIN. PRIOR TO SCHEDULED OCCUPANCY.

NIGHT SETBACK AND SETUP: SUPPLY AND RETURN FANS OPERATE WHEN ANY SPACE TEMPERATURE DROPS TO 60 DEGREES F OR BELOW OR RISES TO 85 DEGREES F OR ABOVE IN DESIGNATED ZONES. MAINTAIN FAN OPERATION UNTIL SPACE TEMPERATURE RISES TO 63 DEGREES F (HEATING) OR DROPS TO 82 DEGREES F (COOLING). ASSOCIATED EXHAUST FANS TO REMAIN OFF DURING UNOCCUPIED OPERATION. WHEN FANS OPERATE, OUTDOOR AND RELIEF AIR DAMPERS ARE CLOSED, AND RETURN AIR DAMPER OPEN.

NIGHT PURGE: NIGHT PURGE SHALL BE INITIATED WHENEVER OUTDOOR AIR TEMPERATURE IS 65 DEGREES F OR BELOW AND SPACE TEMPERATURE IS 75 DEGREES F OR ABOVE. SUPPLY AND RETURN FANS OPERATE DURING NIGHT PURGE. DURING NIGHT PURGE OUTSIDE AIR DAMPER OPENS, RELIEF AIR DAMPER OPENS, RETURN AIR DAMPER CLOSES, AND HEATING/COOLING DISABLED. WHEN SPACES ARE 70 DEGREES F OR BELOW FOR 30 MINUTES, SWITCH TO SHUTDOWN MODE.

WARM-UP CONTROL: OPTIMAL START PROGRAM INITIATES WARM-UP CONTROL. SUPPLY AND RETURN FANS OPERATE DURING WARM-UP. DURING WARM-UP MODE OUTDOOR AND RELIEF AIR DAMPERS CLOSED, RETURN AIR DAMPERS OPEN, HEAT PUMP HEATING TO MAINTAIN 90 DEG. F (adj.) DISCHARGE AIR TEMPERATURE. MODULATE THE ELECTRIC HEATING COIL OUTPUT TO ENSURE A TEMPERATURE OF 50 F MIN. TO THE DX COIL DURING MORNING WARMUP. WHEN RETURN AIR TEMPERATURE REACHES 70 F, SWITCH TO OCCUPIED MODE.

UNOCCUPIED MODE OVERRIDE: UPON RECEIVING AN 'OVERIDE' SIGNAL FROM SPACE TEMPERATURE SENSORS, CONTROLLER CHANGES BUILDING TO WARM-UP CONTROL, AND THEN TO OCCUPIED MODE FOR A PERIOD OF 2 HOURS (ADJ.).

FIRE ALARM SHUTDOWN

WHEN THE FIRE ALARM SENSES A SMOKE CONDITION AT A DUCT OR AREA SMOKE DETECTOR, ALL FANS WILL BE STOPPED. FAN SYSTEMS MAY BE MANUALLY RESTARTED WHEN PERMITTED BY THE FIRE ALARM SYSTEM.

DX

T

23

SUPPLY FAN ARRAYSEE PLANS FOR NUMBER OF FANS

DX COOLING COIL

RELIEFTO OUTSIDE

12

SF

8

7

CT611 MD

T

26

FILTERV-BANK

NATURAL GASFURNACE

RETURN FAN ARRAY

MD

OA FROMLOUVER

CONDENSING UNITFACTORY CONTROLLER CO2

28

ZONE CO2SENSOR

27

ZONETEMPERATURE

T

SD

SMOKE DETECTORBY DIVISION 28

T

24

22 AF

DP

2113 14

15

16 MD

25

EXTERIORWALL

T

POST ELECTRIC HEAT COIL TEMPERATURE

MIXED AIRTEMPERATURE

RF

3

2

CT1

SUPPLY AIRTEMPERATURE

OUTSIDE AIR TEMP

ECM

ECM

18

SP

10

SUPPLY FAN HIGH PRESSURE SWITCH

SP

5

RETURN FAN LOW PRESSURE SWITCH(LOW PRESSURE ALARM)

17

RETURN AIRTEMPERATURE

N.C.

N.O.

N.C.

EXTERIORWALL

ES

MDN.C.

31

32

OUTDOOR AIRINTAKE ISOLATIONDAMPER AT PLENUM

ES

MD N.C.

29

30

RELIEF AIRDISCHARGE ISOLATIONDAMPER AT PLENUM

UNIT RETURN AIRDAMPER

OUTDOOR AIRMEASURING STATION

INTERIORWALL

INTERIORWALL

19 20

BURNER CONTROLMODULE BY AHU MANUFACTURER

4

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

SINGLE ZONE VAV AIR HANDLER X DIAGRAMMATIC SYSTEM GRAPHIC

OUTSIDE AIR TEMPERATURE

RETURN AIR TEMPERATURE

RELIEF AIR DAMPER POSITION

RETURN AIR DAMPER POSITION FEEDBACK

1

OUTSIDE AIRFLOW MEASURING STATION

FILTER DIFFERENTIAL PRESSURE SENSOR

MIXED AIR TEMPERATURE

SUPPLY FAN START/STOP

SUPPLY FAN ECM SPEED

SUPPLY AIR TEMPERATURE

ZONE TEMPERATURE

RELIEF AIR DAMPER POSITION FEEDBACK

RETURN AIR DAMPER POSITION

SUPPLY FAN ECM ALARM STATUS

X

X

X

X

X

X

X

X

X

X X

X

X

X

X

OUTSIDE AIR DAMPER POSITION

OUTSIDE AIR DAMPER POSITION FEEDBACK X

X

SUPPLY FAN STATUS (CURRENT TRANSFORMER)

X

X ALARM, FAIL

RETURN FAN STATUS (CURRENT TRANSFORMER)

RETURN FAN ECM ALARM STATUS

RETURN FAN START/STOP

RETURN FAN ECM SPEED

X

X X ALARM, FAIL

X

X

DX COOLING DEMAND X

SUPPLY FAN HIGH PRESSURE SWITCH X X

RETURN FAN LOW PRESSURE SWITCH X X

ALARM, HIGH

ALARM, LOW

RELIEF AIR ISOLATION DAMPER POSITION

OUTSIDE AIR DAMPER END SWITCH

ALARM, FAIL

ALARM, FAIL

RELIEF AIR DAMPER END SWITCH

OUTSIDE AIR ISOLATION DAMPER POSITION

X X

X

X

X

X

CONDENSING UNIT STATUS

NG BURNER STATUS ALARM, FAILX X

NATURAL GAS HEATING DEMAND

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

2122

23

24

25

26

27

28

29

31

32

X

X

X

X

XZONE CO2 LEVEL

30

X ALARM, FAIL

X

ALARM, FAIL

ALARM, FAIL

ALARM, FAIL

X ALARM, FAIL

9

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:45:3

3 A

M

M802

CheckerAuthor

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

CO

NT

RO

L D

IAG

RA

MS

-M

EC

HA

NIC

AL

CONTROL DIAGRAMS -MECHANICAL

09/18/19

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

NO SCALE

1 SINGLE ZONE CAV AHU CONTROL DIAGRAM (AHUs-3,4)

REV. DATE DESCRIPTION

Page 18: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

EA

EA

EF

CT2 1

POINTS LIST

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

SCIENCE CLASSROOM EXHAUST EF-5,6 X DIAGRAMMATIC SYSTEM GRAPHIC

1

2

EXHAUST FAN START/STOP X

3

FAN STATUS (CURRENT TRANSFORMER) X

EXHAUST FAN MOTORIZED DAMPER X

ALARM, FAIL

MD

RA FROMSCIENCE CLASSROOM

RA

MD4

3

X

4 XRETURN DUCT MOTORIZED DAMPER

SEQUENCE OF OPERATION

A LOW-VOLTAGE PUSHBUTTON SWITCH SHALL ENABLE OR DISABLE THE FAN VIA THE BUILDING AUTOMATION SYSTEM WHEN PUSHED.

WHEN FAN IS STARTED, OPEN EXHAUST FAN ISOLATION DAMPER AND CLOSE ASSOCIATED RETURN AIR MOTORIZED DAMPER. CLOSE EXHAUST FAN ISOLATION DAMPER AND OPEN ASSOCIATED RETURN AIR DAMPER WHEN FAN IS TURNED OFF.

FAN STATUS SHALL BE MONITORED VIA A CT TRANSMITTER. IF FAN FAILS TO OPERATE WHEN COMMANDED, ALARM THE BAS.

VIA PUSHBUTTON

EA EA

EF

CT2 1

POINTS LIST

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

EXHAUST FANS EF-1,2 X DIAGRAMMATIC SYSTEM GRAPHIC

1

2

EXHAUST FAN START/STOP X

3

FAN STATUS (CURRENT TRANSFORMER) X

EXHAUST FAN MOTORIZED DAMPER X

ALARM, FAIL

MD

X

SEQUENCE OF OPERATION

FAN TO BE STARTED AND STOPPED BASED ON A USER-DEFINED ADJUSTABLE OPERATION SCHEDULE OR BY A MANUALLY INITIATED COMMAND AT THE BAS WORKSTATION.

UPON CALL TO START FAN, OPEN ISOLATION DAMPER. START FAN AFTER 15 SECOND (adj.) DELAY. DAMPER TO CLOSE WHEN FAN IS OFF.

FAN STATUS SHALL BE MONITORED VIA A CURRENT TRANSMITTER. IF FAN FAILS TO OPERATE WHEN COMMANDED, ALARM THE BAS.

3

PRIMARY AIR

SUPPLY AIR

M

2

AIRFLOW MEASURING RING

1

AF

TU CONTROL DAMPER

ZONETEMPERATURE

T

SCR REHEAT COIL

EH T

TEMPERATURE SENSOR

ZONECARBON DIOXIDE

CO2

3 4

5

6

POINTS LIST

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

TERMINAL UNITS WITH ELECTRIC REHEAT X DIAGRAMMATIC SYSTEM GRAPHIC

1

2

SUPPLY AIRFLOW MEASUREMENT X

3

DAMPER POSITION X

4

ELECTRIC REHEAT COIL OUTPUT

XSUPPLY AIR TEMPERATURE

X

5 XZONE TEMPERATURE

X

6 ZONE CARBON DIOXIDE

X

X

SEQUENCE OF OPERATION

TERMINAL UNIT CONTROLLER RECEIVES SIGNAL FROM BUILDING CONTROLLER WHICH INITIATES OCCUPIED OR UNOCCUPIED MODE. DURING UNOCCUPIED MODE SPACE TEMPERATURE RESET TO UNOCCUPIED SETPOINTS AND DURING OCCUPIED MODE SPACE TEMPERATURE RESET TO OCCUPIED SETPOINTS. WHEN ENTERING OCCUPIED MODE, USE AN OPTIMAL START ALGORITHM FOR WARM-UP OR COOL-DOWN. MINIMIZE THE WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF SCHEDULED OCCUPIED PERIOD.

UNOCCUPIED MODE:

CLOSE DAMPER, SHUT OFF FAN, AND DISABLE ELECTRIC HEATER. IGNORE ANY SIGNALS FROM SPACE CARBON DIOXIDE SENSORS.

IF SPACE TEMPERATURE IS GREATER THAN UNOCCUPIED COOLING SETPOINT, AND IF CENTRAL AIR HANDLING UNIT SUPPLY FAN IS RUNNING, MODULATE DAMPER BETWEEN MINIMUM AND MAXIMUM COOLING AIRFLOW SETPOINTS TO MAINTAIN SPACE TEMPERATURE AT UNOCCUPIED COOLING SETPOINT.

IF SPACE TEMPERATURE IS LESS THAN UNOCCUPIED HEATING SETPOINT, MODULATE DAMPER BETWEEN MINIMUM AND MAXIMUM HEATING AIRFLOW SETPOINTS AND MODULATE ELECTRIC HEAT TO MAINTAIN SPACE TEMPERATURE AT UNOCCUPIED HEATING SETPOINT.

OCCUPIED MODE:

MODULATE DAMPER TO MAINTAIN MINIMUM AIRFLOW SETPOINT AND DISABLE ELECTRIC HEATER.

IF SPACE TEMPERATURE IS GREATER THAN OCCUPIED COOLING SETPOINT, MODULATE DAMPER BETWEEN MINIMUM AND MAXIMUM COOLING AIRFLOW SETPOINTS TO MAINTAIN SPACE TEMPERATURE AT OCCUPIED COOLING SETPOINT.

IF SPACE TEMPERATURE IS LESS THAN OCCUPIED HEATING SETPOINT, MODULATE DAMPER BETWEEN MINIMUM AND MAXIMUM HEATING AIRFLOW SETPOINTS AND MODULATE ELECTRIC HEAT TO MAINTAIN SPACE TEMPERATURE AT OCCUPIED HEATING SETPOINT.

FOR ZONES EQUIPPED WITH CO2 SENSORS (SEE PLANS): IF SPACE CO2 CONCENTRATION IS GREATER THAN 900 PPM (ADJ.) MODULATE DAMPER BETWEEN MINIMUM AND MAXIMUM COOLING AIRFLOW SETPOINTS TO MAINTAIN CONCENTRATION AT SETPOINT. MODULATE ELECTRIC HEAT AS NECESSARY TO MAINTAIN SPACE TEMPERATURE. WHEN ZONE CO2 CONCENTRATION DROPS BELOW 800 PPM, RESUME NORMAL TEMPERATURE MAINTENANCE OPERATION. ALARM THE BAS IF CO2 LEVELS EXCEED 1300 PPM (adj.).

WARM-UP MODE:

TERMINAL UNIT RECEIVES GLOBAL SIGNAL FROM BUILDING CONTROLLER TO INITIATE WARM-UP MODE. DURING WARM-UP MODE DISABLE ELECTRIC HEATER AND MODULATE DAMPER BETWEEN MINIMUM AND MAXIMUM AIRFLOW SETPOINTS TO MAINTAIN SPACE TEMPERATURE AT OCCUPIED HEATING SETPOINT.

WHERE INDICATED ON PLANS

ALARM, HIGH (1300 PPM, ADJ.)

RA SA

POINTS LIST

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

SPLIT SYSTEMS X DIAGRAMMATIC SYSTEM GRAPHIC

1 ZONE TEMP X ALARM, HIGH

SEQUENCE OF OPERATION

SPLIT SYSTEM SHALL BE EQUIPPED WITH FACTORY CONTROLS. SPLIT SYSTEMS SHALL CYCLE TO MAINTAIN SPACE TEMPERATURE SETPOINT AS SENSED BY PACKAGED THERMOSTAT.

THE BAS SHALL MONITOR SPACE TEMPERATURE AND ALARM IF SPACE TEMPERATURE RISES ABOVE 78 F (adj.)

ZONETEMPERATURE

S1

FAN COIL UNIT

X

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:45:3

5 A

M

M803

CheckerAuthor

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

CO

NT

RO

L D

IAG

RA

MS

-M

EC

HA

NIC

AL

CONTROL DIAGRAMS -MECHANICAL

09/18/19

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

NO SCALE

1 SCIENCE CLASSROOM EXHAUST SYSTEMS (EF-5,6)

NO SCALE

2 EXHAUST FANS (EF-1,2)

NO SCALE

3 TERMINAL UNIT CONTROL DIAGRAM

NO SCALE

4 SPLIT SYSTEMSREV. DATE DESCRIPTION

Page 19: M001 · bid set -february 13, 2020 symbols list and general notes -mechanical symbols list and general notes - ... a. consult all drawings and specifications in this project and become

TYPE I EXHAUST FAN TO BE STARTED AND STOPPED VIA THE HOOD CONTROL PANEL SWTICH. FAN STATUS TO BE MONITORED VIA A CT SWITCH. IF THE FAN FAILS TO OPERATE WHEN COMMANDED, ALARM THE BAS.

MAKEUP AIR UNIT SHALL BE COMMANDED TO RUN WHEN THE TYPE 1 HOOD EXHAUST FAN RUNS. UPON A CALL TO START THE MAKEUP AIR UNIT, OPEN OUTSIDE AIR ISOLATION DAMPER. START AFTER A 15 SECOND (adj.) DELAY. OUTSIDE AIR DAMPER TO CLOSE WHEN MAKEUP AIR UNIT IS OFF. MAKEUP AIR UNIT TO BE INTERLOCKED WITH DAMPER END SWITCH. IF END SWITCH INDICATES DAMPER IS CLOSED, MAKEUP AIR UNIT SHALL RECEIVE NO POWER AND ALARM BAS.

THE MAKEUP AIR UNIT SHALL BE PROVIDED WITH FACTORY-MOUNTED DISCHARGE AIR TEMPERATURE CONTROLS. THE BAS SHALL HAVE THE CAPABILITY TO START, STOP, AND MONITOR THE MAKEUP AIR UNIT.

TYPE 2 EXHAUST FAN TO RUN CONTINUOUSLY DURING OCCUPIED HOURS TO PROVIDE CODE-REQUIRED VENTILATION TO THE KITCHEN. THE FAN STATUS SHALL BE MONITORED VIA A CT SWITCH. IF THE FAN FAILS TO OPERATE WHEN COMMANDED, ALARM THE BAS. UPON A CALL TO START FAN, OPEN ISOLATION DAMPER. START FAN AFTER END SWITCH PROVES THE DAMPER IS OPEN. DAMPER TO CLOSE WHEN FAN IS COMMANDED OFF. FAN TO BE INTERLOCKED WITH DAMPER END SWITCH. IF END SWITCH INDICATES DAMPER IS CLOSED, FAN SHALL RECEIVE NO POWER.

SEQUENCE OF OPERATION

EA

TYPE II EXHAUST

FAN

EA

EF

CT5

3

HOOD CONTROL

PANEL

4

POINTS LIST

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

KITCHEN EXHAUST/MAKEUP AIR X DIAGRAMMATIC SYSTEM GRAPHIC

1

2

TYPE I FAN START/STOP X

3

TYPE I FAN STATUS (CURRENT TRANSFORMER) X

4

TYPE I HOOD CONTROL PANEL SWITCH

5

6

XTYPE II EXHAUST FAN START/STOP

X

XTYPE II EXHAUST FAN STATUS (CURRENT TRANSFORMER)

MAKEUP AIR UNIT START STOP

X

X

OA OA

3

MAKEUP AIR UNIT

1

NATURAL GAS HEAT

ALARM, FAIL

EA

TYPE I EXHAUST

FAN

EF

CT2

1

MES 8 9

SF

CT2

X

7

8

MAKEUP AIR UNIT STATUS (CURRENT TRANSFORMER) X

9

ISOLATION DAMPER OPEN/CLOSE X

ISOLATION DAMPER END SWITCH X ALARM, FAIL

X

X

DISCHARGE AIR TEMPERATURECONTROLLER BY MAU MANUFACTURER

M

ES

8 9

RA SA

POINTS LIST

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

UNIT HEATER X DIAGRAMMATIC SYSTEM GRAPHIC

1 ZONE TEMP X ALARM, LOW

SEQUENCE OF OPERATION

UNIT HEATER SHALL BE EQUIPPED WITH FACTORY CONTROLS. UNIT HEATER SHALL CYCLE TO MAINTAIN SPACE TEMPERATURE SETPOINT AS SENSED BY INTEGRAL THERMOSTAT.

THE BAS SHALL MONITOR SPACE TEMPERATURE AND ALARM IF SPACE TEMPERATURE FALLS BELOW 40 F (adj.)

ZONETEMPERATURE

S1

POINTS LIST

ELECTRIC UNIT HEATER WITH PACKAGED CONTROLS

X

EA EA

EF

CT2 1

POINTS LIST

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

EXHAUST FAN EF-7 X DIAGRAMMATIC SYSTEM GRAPHIC

1

2

EXHAUST FAN START/STOP X

3

FAN STATUS (CURRENT TRANSFORMER) X

EXHAUST FAN MOTORIZED DAMPER X

ALARM, FAIL

MD

X

SEQUENCE OF OPERATION

FAN TO RUN CONTINUOUSLY TO CONTROL HYDROGEN BUILDUP FROM BATTERIES.

WHEN FAN IS STARTED, OPEN EXHAUST AND OUTSIDE AIR ISOLATION DAMPERS. CLOSE ASSOCIATED RETURN AIR MOTORIZED DAMPER. CLOSE EXHAUST FAN AND INTAKE ISOLATION DAMPERS WHEN FAN IS OFF.

FAN STATUS SHALL BE MONITORED VIA A CT TRANSMITTER. IF FAN FAILS TO OPERATE WHEN COMMANDED, ALARM THE BAS.

3

4 OUTSIDE AIR INTAKE MOTORIZED DAMPER X

OA FROMLOUVER OA

MD4

CP

CT2 1

POINTS LIST

TAG DESCRIPTION GR

AP

HIC

AI

AO

DI

DO

AL

AR

M A

T B

AS

NOTES

HOT WATER RECIRC PUMP (CP-1,CP-2) X DIAGRAMMATIC SYSTEM GRAPHIC

1

2

PUMP START/STOP X

PUMP STATUS (CURRENT TRANSFORMER) X ALARM, FAILX

SEQUENCE OF OPERATION

PUMP CONTROLLER RECEIVES SIGNAL FROM BUILDING CONTROLLER, WHICH INITIATES OCCUPIED OR UNOCCUPIED MODE. DURING OCCUPIED MODE PUMP WILL RUN CONTINUOUSLY. DURING UNOCCUPIED MODE PUMP WILL BE OFF.

CURRENT TRANSFORMER SIGNALS CONTROLLER WHICH GENERATES ALARM WHEN PUMP/CONTROLLER FAILS TO OPERATE.

HWR HWR

OREGONOREGONOREGON

12/31/20EXPIRES:

84929

JUNE5, 2011

JA

M

ESM. McCLELLA

ND

E

NGINEER

REGIS

TEREDPROFESSIONA

L

COPYRIGHT 2019STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

AS

SO

CIA

TE

S A

RC

HIT

EC

TS

LLC

686 N

W Y

OR

K D

RIV

E S

UIT

E 1

50

BE

ND

, O

R 9

7703

541.3

82.9

867

FA

X 5

41.3

85.8

816

info

@ste

ele

-arc

h.c

om

CO

OS

BA

Y

OR

EG

ON

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

2/1

1/2

02

0 9

:45:3

6 A

M

M804

JMJK

18113.01

BID

SE

T -

FE

BR

UA

RY

13,

202

0

CO

NT

RO

L D

IAG

RA

MS

-M

EC

HA

NIC

AL

CONTROL DIAGRAMS -MECHANICAL

12/06/19

755

S 7

TH

ST

.

Mars

hfie

ld J

r. H

igh S

choo

l

NO SCALE

1 KITCHEN HOOD EXHAUST AND MAKEUP CONTROLS DIAGRAM, POINTS LIST & SEQUENCES

PROJECT

CONTACT

www.interfaceengineering.com

John Kotas

2018-0244

100 SW Main Street, Suite 1600Portland, OR 97204

TEL 503.382.2266

NO SCALE

2 UNIT HEATER CONTROLS DIAGRAM, POINTS LIST, AND SEQUENCES

NO SCALE

3 EXHAUST FAN (EF-7)

NO SCALE

4 HOT WATER RECIRCULATING PUMPS (CP-1,CP-2)

REV. DATE DESCRIPTION