+ All Categories
Home > Documents > Maintenance.pdf

Maintenance.pdf

Date post: 12-Oct-2015
Category:
Upload: deltasierracharlie
View: 108 times
Download: 1 times
Share this document with a friend
Popular Tags:

of 256

Transcript
  • Maintenance NWD-107462-05E October, 2011

    - 1 -

    iPASOLINK 100/200 SECTION III MAINTENANCE

    CONTENTS

    CONTENTS............................................................................................................................- 1 - 1. General..........................................................................................................................1-1 2. Precaution ....................................................................................................................2-1

    2.1 Maintenance and Operation Manual....................................................................................... 2-4 2.1.1 Wrist Strap Connection.................................................................................................... 2-4 2.1.2 Maintenance Mode Setting (for the LCT Operation)........................................................ 2-4 2.1.3 Manual Switch Operation ................................................................................................ 2-5 2.1.4 XPIC Configuration........................................................................................................ 2-18

    3. Test Sets and Accessories .........................................................................................3-1 4. Current Status..............................................................................................................4-1

    4.1 Current Status......................................................................................................................... 4-1 5. Routine Maintenance...................................................................................................5-1

    5.1 Meter Reading ........................................................................................................................ 5-1 5.2 Performance Monitoring .........................................................................................................5-3

    5.2.1 PM Parameters ............................................................................................................... 5-3 6. Corrective Maintenance ..............................................................................................6-1

    6.1 Alarm/Status ........................................................................................................................... 6-2 6.1.1 Alarm Management ......................................................................................................... 6-4 6.1.2 Alarm and Status Indication Detail .................................................................................. 6-4

    7. Control Items................................................................................................................7-1 7.1 Loopback ................................................................................................................................ 7-2

    7.1.1 IF Loopback..................................................................................................................... 7-2 7.1.2 TDM Loopback Control.................................................................................................... 7-9

    7.2 Equipment Maintenance ....................................................................................................... 7-22 7.2.1 Equipment Utility ........................................................................................................... 7-22 7.2.2 Equipment Reset...........................................................................................................7-67 7.2.3 Radio Control ................................................................................................................ 7-74 7.2.4 Laser Management .......................................................................................................7-86 7.2.5 Cluster Alarm Setting .................................................................................................... 7-91 7.2.6 Inventory........................................................................................................................ 7-95

  • NWD-107462-05E Maintenance

    - 2 -/END

    7.2.7 Software License Key Information............................................................................... 7-102 7.3 Performance Monitor .......................................................................................................... 7-106

    7.3.1 Link Performance Monitor ........................................................................................... 7-106 7.3.2 Monitor Report.............................................................................................................7-106

    7.4 Offline Maintenance............................................................................................................7-131 7.4.1 DADE Adjust ............................................................................................................... 7-131 7.4.2 RF Sub Band Select .................................................................................................... 7-133

    7.5 Maintenance Test ...............................................................................................................7-136 7.6 Software License Setup...................................................................................................... 7-141

    8. Trouble Shooting .........................................................................................................8-1 8.1 Trouble Shooting Flow............................................................................................................ 8-1 8.2 Replacement for Radio Portion............................................................................................... 8-6

    8.2.1 ODU Replacement ..........................................................................................................8-6 8.2.2 IDU Replacement ..........................................................................................................8-12 8.2.3 Fuse Replacement ........................................................................................................8-15

    8.3 Trouble Clearing Details .......................................................................................................8-15 8.3.1 Making Contact with NEC.............................................................................................. 8-15 8.3.2 Categories of Condition Types ...................................................................................... 8-15 8.3.3 Retrieve Alarm Information............................................................................................8-15 8.3.4 ODU Alarm.................................................................................................................... 8-16 8.3.5 IDU Alarm......................................................................................................................8-18 8.3.6 Modem Alarm ................................................................................................................ 8-29 8.3.7 STM1-S Alarm...............................................................................................................8-32 8.3.8 16E1-S Alarm ................................................................................................................ 8-41 8.3.9 AUX-S Alarm ................................................................................................................. 8-43 8.3.10 MSE-S Alarm................................................................................................................. 8-43 8.3.11 Radio GRP Alarm..........................................................................................................8-45 8.3.12 Alarm Action Table ........................................................................................................ 8-46

    9. Abbreviations...............................................................................................................9-1

  • General

    Maintenance NWD-107462-05E

    1-1

    1. GENERAL

    This section provides information on routine and corrective maintenance for the iPASOLINK used for 6 to 42 GHz PDH/SDH/Packet digital radio system.

    This information includes followings with its instructions and procedures:

    Precautions for maintenance Materials for maintenance (test sets and accessories) Performing routine maintenance tasks Performing corrective maintenance tasks

  • General

    NWD-107462-05E Maintenance

    1-2/END

    This page is intentionally left blank.

  • Precaution

    Maintenance NWD-107462-05E

    2-1

    2. PRECAUTION

    The maintenance personnel should report arrival and departure from a station to the relevant station. The following precaution must be carefully observed during maintenance.

    Warning

    1. The -48V DC power is superimposed on the centre conductor of the coaxial cable between the IDU and the ODU. Connecting test equipment directly to this terminal may damage it and touching the coaxial cable core may cause electrical shock.

    2. Persons performing maintenance must take necessary steps to avoid Electrostatic Discharge (ESD) which may damage the cards on the IDU or cause error. Wear a conductive wrist strap connected to the grounded (G) jack on the front of the equipment shelf. This will minimize static build-up during maintenance.

    3. Turn off the "ODU PWR" switch on the IDU before connecting/disconnecting the IF cable to avoid the equipment damaged.

    4. After turning ON the equipment, wait at least 1 minute before turning it OFF again. Repeatedly turning the power ON and OFF within a short interval may cause the equipment damaged.

    5. Do not allow open or short circuit ODU TX output with the TX power on conditions. Perform the TX Mute control in the Maintenance mode or turn the ODU PWR switch off at the IDU before disconnecting cable or feeder from the ODU TX output.

    6. Contact NEC before program download on the LCT is performed. Equipment may not function correctly with improper operation.

    Caution

    1. In a system using the OPTICAL STM-1 interface, do not stare at the laser beam or look at it directly with optical instruments. Otherwise, it may hurt your eyes (Class 1 laser product)

    2. The top surface of the IDU above MODEM is hot in operation.

    3. When replacing the IDU, turn off the ODU PWR switch and disconnected all cables.

    4. During maintenance, the IDU should be set to maintenance ON by the LCT.

    5. To prevent traffic interruption, under the maintenance, perform TX/RX SW manual switching in 1+1 system.

  • Precaution

    NWD-107462-05E Maintenance

    2-2

    6. While the CPU is initialized by the CPU RESET switch, alarm(s) status is reset to normal. After initialized, the alarm information is properly provided through relay contacts.

    7. Information on the maintenance and the control such as Mute, CW, LB etc. is released if the power is turned off.

    8. If each setup item of NE SETUP or SYSTEM OPERATION is changed during in operation, traffic will be momentarily interrupted.

    9. When the TX SW is activated, momentary traffic interruption may occur.

    10. After completing maintenance, restore all connections, manual control settings to normal and confirm that all alarm LEDs are unlit.

    11. After equipment start-up, allow the equipment to warm up at least 30 minutes.

  • Precaution

    Maintenance NWD-107462-05E

    2-3

    Straight Type

    Tighten the TNC-male connector of IF cable to the IDU with engage connector nut only using fingers and holding the cable with another hand.

    L-angle Type

    Tighten the engage connector nut only for the L-angle connector also. (Tightening Torque: 0.3 to 0.5 N-m (3 to 5kg. Cm))

    If rotate other parts of the L-angle connector as illustrated left, it can cause connector damage.

  • Precaution

    NWD-107462-05E Maintenance

    2-4

    2.1 Maintenance and Operation Manual

    2.1.1 Wrist Strap Connection

    Procedure 2-1

    1. Connect the Wrist Strap to the ESD ground terminal (G).

    G

    Figure 2-1 ESD Ground Terminal Location

    2.1.2 Maintenance Mode Setting (for the LCT Operation)

    Procedure 2-2

    1. Click Maintenance button on the top of the LCT window.

    2. Confirm that the MAINT on the top of the LCT window becomes yellow.

    Maintenance Button

    Figure 2-2 LCT Main Window

  • Precaution

    Maintenance NWD-107462-05E

    2-5

    3. And also confirm that the MAINT LED at the front of the equipment becomes yellow.

    Figure 2-3 LED Location

    2.1.3 Manual Switch Operation iPASOLINK 200 supports the following 3 kinds of Manual Switch.

    TX Switch Manual Control (Only 1+1 Hot Standby Configuration) RX Switch Manual Control (Only 1+1 (Twin Path/Hot Standby) Configuration) SNCP Switch Control (Only SNCP Mode (E1) Configuration) Timing Source Switch Control

    (1) TX Switch Manual Control

    Note: This item is supported when the configuration is set to 1+1 Hot Standby mode only. Ex: MODEM No.1 and No.2 constructed as 1+1 Hot Standby mode and MODEM No.1 act as working side. MODEM No.2 is act as standby side.

    The switching procedure is as follows.

    Procedure 2-3

    1. Click the Maintenance button on the top of the LCT window to turn on the maintenance mode.

    2. Expand Maintenance Control from the LCT menu.

    3. Expand Protection Control from the Maintenance Control sub menu.

    4. Select MODEM TX / RX Switch Control from the Protection Control sub menu.

  • Precaution

    NWD-107462-05E Maintenance

    2-6

    5. The MODEM TX / RX Switch Control window appears. Click Clear in the TX SW Manual Control field.

    Figure 2-4 MODEM TX / RX Switch Control Window

    6. The MODEM TX / RX Switch Control box appears. Select Forced No.1/2 from the TX SW Manual Control drop-down list.

    Figure 2-5 MODEM TX / RX Switch Control Box

    7. Click OK button.

    8. The Warning box appears. Click OK button.

    Figure 2-6 Warning Box

    9. The Information box appears. Click OK button.

  • Precaution

    Maintenance NWD-107462-05E

    2-7

    Figure 2-7 Information Box

    10. The MODEM TX / RX Switch Control window appears again. Confirm the parameters displayed.

    Figure 2-8 MODEM TX / RX Switch Control Window

    11. Click Maintenance button on the top of the LCT window to exit the maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

    (2) RX Switch Manual Control

    Note: This item is supported when the configuration is set to 1+1 Twin Path/Hot Standby mode only. Ex: MODEM No.1 and No.2 constructed as 1+1 Twin Path mode and MODEM No.1 act as working side. MODEM No.2 is act as standby side.

    The switching procedure is as follows.

    Procedure 2-4

    1. Click Maintenance button on the top of the LCT window to turn on maintenance mode.

    2. Expand Maintenance Control from the LCT menu.

  • Precaution

    NWD-107462-05E Maintenance

    2-8

    3. Expand Protection Control from the Maintenance Control sub menu.

    4. Select MODEM TX / RX Switch Control from the Protection Control sub menu.

    5. The MODEM TX / RX Switch Control window appears. Click Clear in the RX SW Manual Control field.

    Figure 2-9 MODEM TX / RX Switch Control Window

    6. The MODEM TX / RX Switch Control box appears. Select Forced No.1/2 from the RX SW Manual Control drop-down list.

    Figure 2-10 MODEM TX / RX Switch Control Box

    7. Click OK button.

    8. The Warning box appears. Click OK button.

    Figure 2-11 Warning Box

    9. The Information box appears. Click OK button.

  • Precaution

    Maintenance NWD-107462-05E

    2-9

    Figure 2-12 Information Box

    10. The MODEM TX / RX Switch Control window appears again. Confirm the parameters displayed.

    Figure 2-13 MODEM TX/RX Switch Control Window

    11. Click Maintenance button on the top of the LCT window to exit maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

    (3) RSTP Control

    Procedure 2-5

    1. Click Maintenance button on the top of the LCT window to turn on maintenance mode.

    2. Expand Maintenance Control from the LCT menu.

    3. Expand Protection Control from the Maintenance Control sub menu.

    4. Select RSTP Control from the Protection Control sub menu.

    5. The RSTP Control window appears. Click RSTP Clear button.

  • Precaution

    NWD-107462-05E Maintenance

    2-10

    Figure 2-14 RSTP Control Window

    6. The Warning box appears. Click OK button.

    Figure 2-15 Warning Box

    7. The Information box appears. Click OK button.

    Figure 2-16 Information Box

    8. The RSTP Control window appears again. Confirm the parameters displayed.

  • Precaution

    Maintenance NWD-107462-05E

    2-11

    Figure 2-17 RSTP Control Window

    9. After finishing RSTP Control, click Maintenance button on the top of the LCT window to exit maintenance mode.

    10. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

    (4) SNCP Switch Control (Only SNCP Mode (E1) Configuration)

    Procedure 2-6

    1. Click Maintenance button on the top of the LCT window to turn on maintenance mode.

    2. Expand Maintenance Control from the LCT menu.

    3. Expand Protection Control from the Maintenance Control sub menu.

    4. Select SNCP Switch Control from the Protection Control sub menu.

    5. The SNCP Switch Control window appears. Click the desired number to configure.

  • Precaution

    NWD-107462-05E Maintenance

    2-12

    Figure 2-18 SNCP Switch Control Window

    6. The SNCP Switch Control box appears. Select Manual SW to Protection or Forced SW to Protection from the SNCP Manual SW Control drop-down list.

    Figure 2-19 SNCP Switch Control Box

    7. Click OK button.

    8. The Warning box appears. Click OK button.

    Figure 2-20 Warning Box

    9. The Information box appears. Click OK button.

  • Precaution

    Maintenance NWD-107462-05E

    2-13

    Figure 2-21 Information Box

    10. The SNCP Switch Control window appears again. Confirm the parameters displayed.

    Figure 2-22 SNCP Switch Control Window

    11. Click Maintenance button on the top of the LCT window to exit maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

  • Precaution

    NWD-107462-05E Maintenance

    2-14

    (5) Timing Source Switch Control (This mode available when the Lock Out is Off only)

    In case that Lock Out Status is set to On, follow the Procedure 2-7 to change the setting to Off and then follow the Procedure 2-8 to configure Timing Source Switching.

    (a) Lock Out Setting

    Procedure 2-7

    1. Click Maintenance button on the top of the LCT window to turn on maintenance mode.

    2. Expand Maintenance Control from the LCT menu.

    3. Expand Protection Control from the Maintenance Control sub menu.

    4. Select Timing Source Switch Control from the Protection Control sub menu.

    5. The Timing Source Switch Control window appears. Click desired Lock Out to configure.

    Figure 2-23 Timing Source Switch Control Window

    6. The Timing Source Switch Control box appears. Select Off from Lock Out.

  • Precaution

    Maintenance NWD-107462-05E

    2-15

    Figure 2-24 Timing Source Switch Control Box

    7. Click OK button.

    8. The Information box appears. Click OK button.

    Figure 2-25 Warning Box

    9. The Timing Source Switch Control window appears again. Confirm the parameters displayed.

    Figure 2-26 Timing Source Switch Control Window

    10. After finishing Lock Out Setting, click Maintenance button on the top of the LCT window to exit maintenance mode.

    11. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

  • Precaution

    NWD-107462-05E Maintenance

    2-16

    (b) Timing Source Switch

    Procedure 2-8

    1. Click Maintenance button on the top of the LCT window to turn on maintenance mode.

    2. Expand Maintenance Control from the LCT menu.

    3. Expand Protection Control from the Maintenance Control sub menu.

    4. Select Timing Source Switch Control from the Protection Control sub menu.

    5. The Timing Source Switch Control window appears. Click the desired Timing Source Switch Control to configure.

    Figure 2-27 Timing Source Switch Control Window

    6. The Timing Source Switch Control box appears. Select specify switching mode (Manual SW or Forced SW).

    Figure 2-28 Timing Source Switch Control Box

    7. Click OK button.

    8. The Warning box appears. Click OK button.

    Click.

  • Precaution

    Maintenance NWD-107462-05E

    2-17

    Figure 2-29 Warning Box

    9. The Information box appears. Click OK button.

    Figure 2-30 Information Box

    10. The Timing Source Switch Control window appears again. Confirm the parameters displayed.

    Figure 2-31 Timing Source Switch Control Window

    11. Click Maintenance button on the top of the LCT window to exit maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

  • Precaution

    NWD-107462-05E Maintenance

    2-18/END

    2.1.4 XPIC Configuration

    2.1.4.1 X-DEM Delay Adjust

    Cable Length Adjustment between IDU and ODU

    When the cable length difference between Master and Slave MODEMs is eight meters or more, adjust length by LCT operation, Maintenance Offline Maintenance Control.

    Figure 2-32 X-DEM Delay Adjust Window

    2.1.4.2 XPIC Reset

    When executing Mute or CW, perform after executing XPIC Reset (for both local and remote stations). For this, select Forced Reset of the XPIC Reset radio button.

    Figure 2-33 XPIC Reset Window

    Default: -8 m to +8 m

    e.g. If the Master side is 16-meters longer than the Slave side, select +8 to +16[m].

  • Test Sets and Accessories

    Maintenance NWD-107462-05E

    3-1

    3. TEST SETS AND ACCESSORIES

    The test sets and special accessories listed in Table 3-1 are required for maintenance. If recommended test sets and accessories are not available, equivalents may be used.

    Table 3-1 Test Sets and Accessories

    No. Model Type Model Number Manufacture

    1 PASOLINK Monitor X0818 NEC

  • Test Sets and Accessories

    NWD-107462-05E Maintenance

    3-2/END

    This page is intentionally left blank.

  • Current Status

    Maintenance NWD-107462-05E

    4-1

    4. CURRENT STATUS

    4.1 Current Status The Current Status window on the LCT window is for displaying Equipment status, Line card status, Event log and all alarms detected on the equipments side.

    But it is just for viewing system status only you can not make any changes of all items displayed on this window. (Such as modify, adding, masking alarms or items)

    (1) Active Alarm Tab

    The Active Alarm tab displays all current alarms detected on the equipment side.

    You can download the current alarm list to LCT PC by clicking Save button on the top left of the Active Alarm tab.

    Figure 4-1 Active Alarm Tab

    (2) Event Log Tab

    The Event Log tab displays all alarms and status detected when there is any changed on the line card and configuration on equipment.

  • Current Status

    NWD-107462-05E Maintenance

    4-2

    You can download the Event Status list to the LCT PC by clicking Save button on the top left of the Event Log tab.

    Figure 4-2 Event Log Tab

    Note: To Save log list, follow the procedure below.

    1. Click Save button of the Active Alarm tab or the Event Log tab.

    Figure 4-3 Active Alarm (or Event Log) Tab

    2. The File Download window appears. Click Save button.

  • Current Status

    Maintenance NWD-107462-05E

    4-3

    Figure 4-4 File Download Window

    3. The Save As window appears. Select the proper folder of the Local PC, and then click Save button. Default file name: Event Status: EventLog_YYYYMMDDhhmmss.csv Active Alarm Status: ActiveAlarm_YYYYMMDDhhmmss.csv

    Figure 4-5 Save As Window

    4. After finishing the export of log file, the Download Complete window appears. Click Close button.

  • Current Status

    NWD-107462-05E Maintenance

    4-4

    Figure 4-6 Download Complete Window

    5. Confirm the log file was saved in the selected folder.

    Figure 4-7 Log File Folder

  • Current Status

    Maintenance NWD-107462-05E

    4-5

    (3) ODU Tab

    The ODU tab displays all alarm and status detected on ODU.

    Figure 4-8 ODU Tab

  • Current Status

    NWD-107462-05E Maintenance

    4-6

    (4) IDU Tab

    The IDU tab displays all alarms and status detected on IDU.

    Figure 4-9 IDU Tab

  • Current Status

    Maintenance NWD-107462-05E

    4-7

    (5) AUX Tab

    The AUX tab displays all alarms and status of AUX.

    Figure 4-10 AUX Tab

  • Current Status

    NWD-107462-05E Maintenance

    4-8/END

    This page is intentionally left blank.

  • Routine Maintenance

    Maintenance NWD-107462-05E

    5-1

    5. ROUTINE MAINTENANCE

    This chapter provides the routine (annually) maintenance procedures to ensure the satisfactory operation of the equipment. During routine maintenance, carefully observe the precautions given in Chapter 2.

    5.1 Meter Reading

    Table 5-1 Metering Item

    Item Description

    TX Power Indicates the transmit power of the ODU

    RX Level Indicates the RF reception level of the ODU

    ODU Power Supply Indicates the Power Supply voltage of the ODU

    BER Indicates the value of the BER measurement

    Procedure 5-1

    1. Expand Metering from the LCT menu.

    2. Select Current Metering from the Metering sub menu.

    3. The Current Metering window appears. Confirm the parameters displayed.

    Figure 5-1 Current Metering Window

  • Routine Maintenance

    NWD-107462-05E Maintenance

    5-2

    Notes

    1. If an abnormal indication appears, check Alarm/Status, performance monitor and perform loopback test to distinguish sections of normal and alarmed.

    2. RX LEVEL varies depending on received RF signal level.

    3. Power Supply voltage at ODU varies depending of IF cable length between the IDU and ODU.

    4. Click the desired MODEM to configure.

    5. The Current Metering box appears. Modify the parameter accordingly.

    Figure 5-2 Current Metering Box

    Table 5-2 Refresh Cycle

    Parameter Description

    Normal Speed Refreshed automatically every 10 seconds.

    High Speed Refreshed automatically every 3 seconds

    6. Click Close button on the top of the Current Metering box.

    This step ends the procedure.

  • Routine Maintenance

    Maintenance NWD-107462-05E

    5-3

    5.2 Performance Monitoring The Performance Monitoring (PM) is used to identify and isolate the problem if occurring at a particular line or path. It also monitors the quality of lines and paths. All Performance Monitoring parameters are collected every minute and accumulated to 15-minute and 24-hour (1 day) statistics.

    5.2.1 PM Parameters Performance Monitor Parameters can be measured from iPASOLINK.

    5.2.1.1 PM Status Monitor Types

    Table 5-3 MODEM Performance Monitor Items

    Item Description Spec.

    RF BBE Background Block

    Error

    The sum of the background block error ITU-T G.826

    RF ES Errored Second The cumulative time in which more than

    one block error per second was detected.

    ITU-T G.826

    RF SES Severely Errored

    Second

    The cumulative time in which the BER of a

    one second period exceeded a set

    percentage (30%).

    ITU-T G.826

    RF SEP Severely Errored

    Period

    The cumulative time in which the BER of a

    one second period exceeded 10E-3.

    ITU-T G.826

    RF UAS Unavailable Second The cumulative time in which the unit

    remained inoperative

    ITU-T G.826

    RF OFS Out of Frame Second The total number of seconds the out of

    frame condition is generated in 15

    minute-blocks. (OFS is applied to the Total

    only)

    ITU-T G.826

    RX LEV RX Level The minimum and maximum reception level

    (when there are two routes it does so for

    No. 1 and 2 respectively)

  • Routine Maintenance

    NWD-107462-05E Maintenance

    5-4

    Table 5-4 SDH/PDH Performance Monitor Items

    Monitor Types Definition Spec.

    BBE Near end background block error ITU-T G.826 G.784

    ES Near end errored seconds ITU-T G.826 G.784

    SES Near end severely errored seconds ITU-T G.826 G.784

    SEP Near end severely error period -

    UAS Unavailable seconds ITU-T G.826 G.784

    RS

    OFS Out of frame seconds ITU-T G.784

    BBE Near end background block error ITU-T G.826 G.784

    ES Near end errored seconds ITU-T G.826 G.784

    SES Near end severely errored seconds ITU-T G.826 G.784

    SEP Near end severely error period -

    UAS Unavailable seconds ITU-T G.826 G.784

    DMR-RS

    OFS Out of frame seconds ITU-T G.784

    BBE Near end background block error ITU-T G.826 G.784

    ES Near end errored seconds ITU-T G.826 G.784

    SES Near end severely errored seconds ITU-T G.826 G.784

    SEP Near end severely error period -

    MS

    UAS Unavailable seconds ITU-T G.826 G.784

    E1 E1 CV Near end Code violation

  • Routine Maintenance

    Maintenance NWD-107462-05E

    5-5

    Table 5-5 LAN Performance Monitor Items

    Monitor Types Description Spec.

    RX Octs The total number of octets received on the interface, including

    framing characters.

    RFC2819

    TX Octs The total number of octets transmitted out of the interface,

    including framing characters.

    RFC2819

    RX Pkts Number of packets received (including bad packets, all Unicast,

    Broadcast packets, and Multicast packets).

    RFC2819

    TX Pkts The total number of packets transmitted. RFC2819

    RX Drop Events A count of drop packets RFC2819

    RX Undersize Pkts Number of packets received that were less than 64 octets long

    and were otherwise well formed.

    RFC2819

    RX Fragments Number of packets received that were less than

    64 octets in length and had either a bad Frame Check Sequence

    (FCS) with an integral number of octets (FCS Error) or a bad FCS

    with a non-integral number of octets (Alignment Error).

    RFC2819

    RX 64Octs Number of packets received 64 octets in length.

    (including error packets)

    RFC2819

    TX 64Octs Number of packets transmitted 64 octets in length.

    (including error packets)

    RFC2819

    RX 65 to 127Octs Number of packets received that were between 65 and 127 octets

    in length. (including error packets)

    RFC2819

    TX 65 to 127Octs Number of packets transmitted and received that were between

    65 and 127 octets in length. (including error packets)

    RFC2819

    RX 128 to 255Octs Number of packets received that were between 128 and 255

    octets in length. (including error packets)

    RFC2819

    TX 128 to 255Octs Number of packets transmitted and received that were between

    128 and 255 octets in length. (including error packets)

    RFC2819

    RX 256 to 511Octs Number of packets received that were between 256 and 511

    octets in length. (including error packets)

    RFC2819

    TX 256 to 511Octs Number of packets transmitted and received that were between

    256 and 511 octets in length. (including error packets)

    RFC2819

    RX 512 to 1023Octs Number of packets received that were between 512 and 1023

    octets in length. (including error packets)

    RFC2819

    TX 512 to 1023Octs Number of packets transmitted and received that were between

    512 and 1023 octets in length. (including error packets)

    RFC2819

    RX 1024 to 1518Octs Number of packets received that were between 1024 and 1518

    octets in length. (including error packets)

    RFC2819

  • Routine Maintenance

    NWD-107462-05E Maintenance

    5-6

    Monitor Types Description Spec.

    TX 1024 to 1518Octs Number of packets transmitted and received that were between

    1024 and 1518 octets in length (including error packets)

    RFC2819

    RX CRC Alignment

    Errors

    Number of reception alignments of FCS error frames RFC2819

    RX Oversize Pkts A count of frames received on a particular interface that

    exceeds1518 bytes.

    RFC2819

    RX Jabbers Number of error frames more than 1519 octets in receive data

    length.

    RFC2819

    RX Multicast Pkts Number of good multicast packets received. (excluding broadcast

    packets)

    RFC2819

    TX Multicast Pkts The total number packets that higher-level protocols requested to

    be transmitted to a multicast address.

    RFC2819

    RX Broadcast Pkts Number of good broadcast packets received. RFC2819

    TX Broadcast Pkts The total number packets that higher-level protocols requested to

    be transmitted to a broadcast address.

    RFC2819

    TX Collisions Number of collisions on this Ethernet segment RFC2819

    RX Unknown TPID Number of abandoned frames included in unsetting TPID frames

    received.

    RX Unknown VID Number of abandoned frames included in unsetting VID frames

    received.

    RX MAC Limit Number of frames discarded due to exceeding MAC learning Limit

    RX Filter Discard Number of frames abandoned by input filtering function.

    RX QoS Discard Number of frames abandoned by Policing function of input port.

    TX Queue0 Discard Number of QoS frames discard by transmission Queue0.

    TX Queue1 Discard Number of QoS frames discard by transmission Queue1.

    TX Queue2 Discard Number of QoS frames discard by transmission Queue2.

    TX Queue3 Discard Number of QoS frames discard by transmission Queue3.

    Per VLAN Rx Frames Number of frames received as particular VLAN.

    Per VLAN Tx Frames Number of frames transmitted as particular VLAN.

    Per VLAN Rx QoS

    Discard

    Number of discarded frames per VLAN basis.

  • Routine Maintenance

    Maintenance NWD-107462-05E

    5-7

    Table 5-6 MODEM PM Counter Range

    PM Types 15M PM Counter Range 24h PM Counter Range

    RF OFS 0 to 900 0 to 86400

    RF BBE It depends on radio setting (CS

    and Modulation)

    It depends on radio setting (CS

    and Modulation)

    RF ES 0 to 900 0 to 86400

    RF SES 0 to 900 0 to 86400

    RF SEP 0 to 900 0 to 86400

    RF UAS 0 to 900 0 to 86400

    Table 5-7 SDH/PDH PM Counter Range

    PM Types 15M PM Counter Range 24h PM Counter Range

    OFS 0 to 900 0 to 86400

    BBE 0 to 16777215 0 to 1610612640

    ES 0 to 900 0 to 86400

    SES 0 to 900 0 to 86400

    SEP 0 to 900 0 to 86400

    UAS 0 to 900 0 to 86400

    E1 CV 0 to 4294967295 0 to 4294967295

  • Routine Maintenance

    NWD-107462-05E Maintenance

    5-8

    Table 5-8 LAN PM Counter Range

    PM Types 15M PM Counter Range 24h PM Counter Range

    RX Octs 0 to 18446744073709551615 0 to 18446744073709551615

    TX Octs 0 to 18446744073709551615 0 to 18446744073709551615

    RX Pkts 0 to 4294967295 0 to 4294967295

    TX Pkts 0 to 4294967295 0 to 4294967295

    RX Drop Events 0 to 4294967295 0 to 4294967295

    RX Undersize Pkts 0 to 4294967295 0 to 4294967295

    RX Fragments 0 to 4294967295 0 to 4294967295

    RX 64Octs 0 to 4294967295 0 to 4294967295

    TX 64Octs 0 to 4294967295 0 to 4294967295

    RX 65 to 127Octs 0 to 4294967295 0 to 4294967295

    TX 65 to 127Octs 0 to 4294967295 0 to 4294967295

    RX 128 to 255Octs 0 to 4294967295 0 to 4294967295

    TX 128 to 255Octs 0 to 4294967295 0 to 4294967295

    RX 256 to 511Octs 0 to 4294967295 0 to 4294967295

    TX 256 to 511Octs 0 to 4294967295 0 to 4294967295

    RX 512 to 1023Octs 0 to 4294967295 0 to 4294967295

    TX 512 to 1023Octs 0 to 4294967295 0 to 4294967295

    RX 1024 to 1518Octs 0 to 4294967295 0 to 4294967295

    TX 1024 to 1518Octs 0 to 4294967295 0 to 4294967295

    RX CRC Alignment Errors 0 to 4294967295 0 to 4294967295

    RX Oversize Pkts 0 to 4294967295 0 to 4294967295

    RX Jabbers 0 to 4294967295 0 to 4294967295

    RX Multicast Pkts 0 to 4294967295 0 to 4294967295

    TX Multicast Pkts 0 to 4294967295 0 to 4294967295

    RX Broadcast Pkts 0 to 4294967295 0 to 4294967295

    TX Broadcast Pkts 0 to 4294967295 0 to 4294967295

    TX Collisions 0 to 4294967295 0 to 4294967295

    RX Unknown TPID 0 to 18446744073709551615 0 to 18446744073709551615

    RX Unknown VID 0 to 18446744073709551615 0 to 18446744073709551615

    RX MAC Limit 0 to 18446744073709551615 0 to 18446744073709551615

    RX Filter Discard 0 to 18446744073709551615 0 to 18446744073709551615

    RX QoS Discard 0 to 18446744073709551615 0 to 18446744073709551615

    TX Queue0 Discard 0 to 18446744073709551615 0 to 18446744073709551615

    TX Queue1 Discard 0 to 18446744073709551615 0 to 18446744073709551615

    TX Queue2 Discard 0 to 18446744073709551615 0 to 18446744073709551615

    TX Queue3 Discard 0 to 18446744073709551615 0 to 18446744073709551615

  • Routine Maintenance

    Maintenance NWD-107462-05E

    5-9

    PM Types 15M PM Counter Range 24h PM Counter Range

    Per VLAN Rx Frames 0 to 18446744073709551615 0 to 18446744073709551615

    Per VLAN Tx Frames 0 to 18446744073709551615 0 to 18446744073709551615

    Per VLAN Rx QoS Discard 0 to 18446744073709551615 0 to 18446744073709551615

    Table 5-9 MODEM TCA Threshold

    15min TCA Threshold 24h TCA Threshold

    Default threshold Default threshold

    PM

    Types Range

    Occur Recovery

    Range

    Occur Recovery

    RF OFS 1 to 900 900 90 1 to 86400 65534 650

    RF BBE It depends on radio setting (CS and

    Modulation)

    It depends on radio setting (CS and

    Modulation)

    RF ES 1 to 900 900 90 1 to 86400 65534 650

    RF SES 1 to 900 900 90 1 to 86400 65534 650

    RF SEP 1 to 900 900 90 1 to 86400 65534 650

    RF UAS 1 to 900 900 90 1 to 86400 65534 650

    RX LEV -99 to -30 It depends on radio setting

    (CS and Modulation)

    -99 to -30 It depends on radio setting

    (CS and Modulation)

    Table 5-10 MODEM RX LEV TCA default Threshold

    Modulati

    on Type

    CS=7MHz CS=14MHz CS=28MHz CS=56MHz

    QPSK -98dBm -95dBm -92dBm -89dBm

    16QAM -92dBm -89dBm -86dBm -83dBm

    32QAM -89dBm -86dBm -83dBm -80dBm

    64QAM -86dBm -83dBm -80dBm -77dBm

    128QAM -83dBm -80dBm -77dBm -74dBm

    256QAM -80dBm -77dBm -74dBm -71dBm

  • Routine Maintenance

    NWD-107462-05E Maintenance

    5-10

    Table 5-11 MODEM RF BBE TCA Threshold

    Modulation

    Types

    15min TCA Threshold 24h TCA Threshold

    Default threshold Default threshold CS Modulation Range

    Occur Recovery

    Range

    Occur Recovery

    QPSK 1-805000 8,050 805 1-77280000 772,800 77,280

    16QAM 1-1611000 16,110 1,611 1-154656000 1,546,560 154,656

    32QAM 1-2014000 20,140 2,014 1-193344000 1,933,440 193,344

    64QAM 1-2417000 24,170 2,417 1-232032000 2,320,320 232,032

    128QAM 1-2820000 28,200 2,820 1-270720000 2,707,200 270,720

    7M

    256QAM 1-3223000 32,230 3,223 1-309408000 3,094,080 309,408

    QPSK 1-805000 8,050 805 1-77280000 772,800 77,280

    16QAM 1-1611000 16,110 1,611 1-154656000 1,546,560 154,656

    32QAM 1-2014000 20,140 2,014 1-193344000 1,933,440 193,344

    64QAM 1-2417000 24,170 2,417 1-232032000 2,320,320 232,032

    128QAM 1-2820000 28,200 2,820 1-270720000 2,707,200 270,720

    14M

    256QAM 1-3223000 32,230 3,223 1-309408000 3,094,080 309,408

    QPSK 1-805000 8,050 805 1-77280000 772,800 77,280

    16QAM 1-1611000 16,110 1,611 1-154656000 1,546,560 154,656

    32QAM 1-2014000 20,140 2,014 1-193344000 1,933,440 193,344

    64QAM 1-2417000 24,170 2,417 1-232032000 2,320,320 232,032

    128QAM 1-2820000 28,200 2,820 1-270720000 2,707,200 270,720

    28M

    256QAM 1-3223000 32,230 3,223 1-309408000 3,094,080 309,408

    QPSK 1-1611000 16,110 1,611 1-154656000 1,546,560 154,656

    16QAM 1-3223000 32,230 3,223 1-309408000 3,094,080 309,408

    32QAM 1-4028000 40,280 4,028 1-386688000 3,866,880 386,688

    64QAM 1-4834000 48,340 4,834 1-464064000 4,640,640 464,064

    128QAM 1-5640000 56,400 5,640 1-541440000 5,414,400 541,440

    56M

    256QAM 1-6446000 64,460 6,446 1-618816000 6,188,160 618,816

  • Routine Maintenance

    Maintenance NWD-107462-05E

    5-11

    Table 5-12 SDH/PDH TCA Threshold

    15min TCA Threshold 24h TCA Threshold

    Default threshold Default threshold

    PM

    Types Range

    Occur Recovery

    Range

    Occur Recovery

    RS OFS 1 to 900 900 90 1 to 86400 65534 650

    RS BBE 1 to 16777215 65534 6560 1 to 1610612640 6291260 629130

    RS ES 1 to 900 900 90 1 to 86400 65534 650

    RS SES 1 to 900 900 90 1 to 86400 65534 650

    RS SEP 1 to 900 900 90 1 to 86400 65534 650

    RS UAS 1 to 900 900 90 1 to 86400 65534 650

    DMR RS

    OFS

    1 to 900 900 90 1 to 86400 65534 650

    DMR RS

    BBE

    1 to 16777215 65534 6560 1 to 1610612640 6291260 629130

    DMR RS

    ES

    1 to 900 900 90 1 to 86400 65534 650

    DMR RS

    SES

    1 to 900 900 90 1 to 86400 65534 650

    DMR RS

    SEP

    1 to 900 900 90 1 to 86400 65534 650

    DMR RS

    UAS

    1 to 900 900 90 1 to 86400 65534 650

    MS BBE 1 to 16777215 65534 6560 1 to 1610612640 6291260 629130

    MS ES 1 to 900 900 90 1 to 86400 65534 650

    MS SES 1 to 900 900 90 1 to 86400 65534 650

    MS SEP 1 to 900 900 90 1 to 86400 65534 650

    MS UAS 1 to 900 900 90 1 to 86400 65534 650

    E1 CV 1 to

    4294967295

    65534 650 1 to 4294967295 6291260 629130

  • Routine Maintenance

    NWD-107462-05E Maintenance

    5-12/END

    Table 5-13 LAN TCA Threshold

    15min TCA Threshold 24h TCA Threshold PM Types

    Range Default threshold Range Default threshold

    Drop Event 1 to 133929000 133929000 1 to 4294967295 4294967295

    Undersize Packets 1 to 133929000 133929000 1 to 4294967295 4294967295

    Fragment Packets 1 to 133929000 133929000 1 to 4294967295 4294967295

    CRC Alignment

    Error

    1 to 133929000 133929000 1 to 4294967295 4294967295

    Oversize Packets 1 to 133929000 133929000 1 to 4294967295 4294967295

    Collisions 1 to 133929000 133929000 1 to 4294967295 4294967295

  • Corrective Maintenance

    Maintenance NWD-107462-05E

    6-1

    6. CORRECTIVE MAINTENANCE

    Corrective maintenance to be done in the field is described in this chapter. Corrective maintenance in the field covers fault isolation, card/unit replacement and alignment. The fault location procedures describe how to isolate card-level/unit-level faults.

    Faults can be classified in to those that cause deterioration of the transmission quality and those that interrupt the traffic due to a malfunction of the equipment. This chapter explains the troubleshooting procedures for equipment faults and the corresponding remedial methods. The purpose of troubleshooting malfunctioning equipment is to restart the service by locating the faulty part and replacing it with a spare.

    The faults that cause deterioration quality are primarily originated by changes occurred in the state of propagation. Therefore, if a decline in the transmission quality or similar fakes place frequently, the link design will have to be reviewed.

    During the corrective maintenance, carefully observe the precautions given in Chapter2, until the alignment is completed.

  • Corrective Maintenance

    NWD-107462-05E Maintenance

    6-2

    6.1 Alarm/Status When an alarm event has occurred, at first, check alarm indication on the front of the IDU. Continuously, connect the PC to the LOCAL jack on the LCT port mounted on the IDU and check alarm/status indication.

    A faulty part can be located by checking the ALARM LED indications and LCT Alarm indications.

    Alarm Report When an alarm is detected, alarm notification is made to the user by lighting up the LEDs on the rack, and reporting the alarm to user interface. The alarm notification is also made to the user by an Office alarm, such as the station alarm bell and lamps.

    ALARM LED indication LED at the front of the rack lights up/turns off when alarm is generated/cleared to report the alarm to the user.

    Figure 6-1 LED Location

    Web-LCT indication

    The alarm LED indications faulty part can be located by checking the ALM LED indicators and Web-LCT Alarm indications.

  • Corrective Maintenance

    Maintenance NWD-107462-05E

    6-3

    Figure 6-2 Active Status (Current Status) Window

    Meter Reading

    Based on the meter readings during periodical inspection with LCT in Chapter 5, a faulty part can be located by checking if the reading values exceed the permissible ranges.

    Loopback

    In case of an abnormal BER measurement result among the meter reading items, try to distinguish the faulty part by Loopback procedure.

  • Corrective Maintenance

    NWD-107462-05E Maintenance

    6-4

    6.1.1 Alarm Management The alarm severity of each failure is indicated by the following alarm level and alarm class. Alarm classes can be modified. Modification is done by Alarm Severity Setting.

    6.1.1.1 Alarm Class

    Critical (CR) : The Critical severity level indicates that a service affecting condition has occurred and an immediate corrective action is required. Such a severity can be reported, for example, when a managed object becomes totally out of service and its capability must be restored.

    Major (MJ): The Major severity level indicates that a service affecting condition has developed and an urgent corrective action is required. Such a severity can be reported, for example, when there is a severe degradation in the capability of the managed object and its full capability must be restored.

    Minor (MN): The Minor severity level indicates the existence of a non-service affecting fault condition and that corrective action should be taken in order to prevent a more serious (for example, service affecting) fault. Such a severity can be reported, for example, when the detected alarm condition is not currently degrading the capacity of the managed object.

    Warning (WR): The Warning severity level indicates the detection of a potential or impending service affecting fault, before any significant effects have been felt. Action should be taken to further diagnose (if necessary) and correct the problem in order to prevent it from becoming a more serious service affecting fault.

    6.1.2 Alarm and Status Indication Detail

    6.1.2.1 ODU Alarms & Status

    Indication Category Descriptions Severity

    ODU Alarm Alarm ODU hardware failure. MJ

    TX Power Alarm The TX PWR is lower than 3 dB. MJ

    TX Input Alarm The TX IF signal become out of range from

    -29 dBm 5 dB.

    MJ

  • Corrective Maintenance

    Maintenance NWD-107462-05E

    6-5

    Indication Category Descriptions Severity

    RX Level Alarm The reception level become lower than -72dBm ~

    -94dBm level. (It depends on the modulation system

    and bit rates).

    MJ

    ODU CPU / Cable Open Alarm CPU of ODU is faulty or IF CABLE between IDU -

    ODU of ODU is broken or is not connected.

    MJ

    Mute Status Status Indicates the control status of the ODU TX power

    output. When the TX power is set to Mute, Status is

    issued.

    -

    LO REF Alarm Loss of Ref LO signal of ODU. MN

    ODU TYPE MISMATCH Alarm Indicates connected ODU type is not supported at

    iPASOLINK system, or ODU type cannot use in

    provisioned modulation setting.

    MJ

    ODU Power Supply Alarm ALM in a case of Power supply interruption to ODU. MJ

  • Corrective Maintenance

    NWD-107462-05E Maintenance

    6-6

    6.1.2.2 MODEM Alarms & Status

    Indication Category Descriptions Severity

    RX SW Status Status Radio interface RX SW usage state in Redundant

    configuration

    -

    TX SW Status Status Radio interface TX SW usage state in 1+1 HOT

    STANDBY Redundant configuration

    -

    LOF Alarm Loss of Frame at radio side. MJ

    Frame ID Alarm Frame ID (route differentiation ID) MJ

    High BER Alarm Radio signal degradation (High BER threshold detection). (Threshold :1E-3/1E-4/1E-5)

    MJ

    Low BER Alarm Radio signal degradation (Low BER threshold detection). (Threshold. :1E-6/1E-7/1E-8/1E-9)

    MN

    Early Warning Alarm Radio signal degradation (Early Warning threshold detection). (Threshold :1E-9)

    MN

    MOD Alarm Indicates the operating status of the MOD. When any failure occurs in the modulator section, Alarm is issued.

    MJ

    IF Cable Short Alarm IF cable between IDU - ODU is in short condition. MJ

    InPhase. Status In - Phase indicates the received signal DADE status between No.1 and No.2 MODEM interfaces are in Phase condition. In this condition, hitless switch over is available.

    -

    L2SYNC Loss Alarm Loss of frame synchronization of GFP frames on MODEM port.

    MJ

    RDI Alarm RDI indication reception alarm on MODEM port MJ

    UAE. Alarm UAE alarm. Indicates the occurrence of an Unavailable state.

    WR

    XPIC Mode Mismatch Alarm XPIC configuration of two MODEMs is not Master-Slave. MJ

    Communication FAIL Alarm Communication failure of equipment internal control communication.

    MJ

    TDM / AMR Range

    Mismatch

    Alarm Mismatch condition when the mapping number of E1 channels are different between TX and RX modem ports OR detection of mismatch of selected RX AMR modulation and TX AMR modulation

    MJ

    ATPC Power Mode Status ATPC control signal fault (90sec) as well as MAX Power continuation 90sec

    -

    TX SW Reverse

    Request

    Status TXSW request signal receiving condition from the opposite station:

    -

    TX SW Lock-in

    Status

    Status TXSW Lockin state -

    Unlocked Alarm Wireless synchronization status of the local side. MJ

  • Corrective Maintenance

    Maintenance NWD-107462-05E

    6-7

    6.1.2.3 STM-1-S Option Card Alarms & Status

    Indication Category Descriptions Severity

    Unequipped Alarm Reserved and installed optional card is removed from

    optional slot.

    MJ

    Communication FAIL Alarm Equipment internal control-plane communication

    failure.

    MJ

    SNCP Protection Status Status SNCP Path Protection Status indication which

    indicates [FS, SF, SD, MS, NR] condition.

    -

    SFP Type Mismatch Alarm Mismatch between SFP on LCT and installed SFP. MJ

    SFP Removed Alarm A SFP is removed. MJ

    STM-1 LOS Alarm LOS detection on STM1 Optical port. MJ

    TF Alarm Transmit Failure detection on STM1 Optical port. MJ

    RS LOF Alarm SDH Frame synchronization lost in RS (Regenerator

    Section) on STM1 port.

    MJ

    RS TIM Alarm Trace Identifier Mismatch detected in RS

    (Regenerator Section) on STM1 port.

    MJ

    RS EXC Alarm B1 Byte error occurrence in RS (Regenerator

    Section) on STM1 port.

    MJ

    RS DEG Alarm B1 byte error in RS (Regenerator Section) (RS -

    Degraded) on STM1 port.

    MN

    MS AIS Alarm AIS detection in MS (Multiplex Section) on STM1

    port.

    MJ

    MS RDI Alarm Remote Defect Indication reception in MS (Multiplex

    Section) on STM1 port.

    MJ

    AU AIS Alarm AIS detection in AU (Administrative Unit) on STM1

    port.

    MJ

    AU LOP Alarm Loss of AU pointer happens on STM1 port. MJ

    HP UNEQ Alarm HOP (Higher Order Path) Unequipped occurrence on

    STM1 port.

    MJ

    HP TIM Alarm HOP (Higher Order Path) Trace Identifier mismatch

    occurrence on STM1 port.

    MJ

    HP PLM Alarm Payload Label Mismatch occurrence in HOP (Higher

    Order Path) on STM1 port.

    MJ

    HP RDI Alarm RDI (Remote Defect Indication) reception in HOP

    (Higher Order Path) on STM1 port.

    MJ

  • Corrective Maintenance

    NWD-107462-05E Maintenance

    6-8

    Indication Category Descriptions Severity

    LOM Alarm Loss of Multi-Frame on STM1 port. MJ

    TU AIS Alarm In TU (Tributary Unit), AIS detection on STM1 port. MJ

    TU LOP Alarm Loss of TU Pointer on STM1 port. MJ

    LP UNEQ. Alarm LP (Lower Order Path) Unequipment occurrence on

    STM1 port.

    MJ

    LP RDI Alarm Remote Defect Indicate reception by a LP (Lower

    Order Path) on STM1 port.

    MJ

    LP PLM Alarm Payload Label Mismatch Failure occurrence by a LP

    (Lower Order Path) on STM1 port.

    MJ

    ALS Status Indication of automatic laser shutdown condition at

    STM-1 optical port.

    -

    RS UAS Status Status UAS status indication on STM port (Repeater

    Section)

    -

    STM-1 AIS Generated Status AIS generation condition on STM port. -

    PJE Status Pointer justification Event indication at STM port. -

  • Corrective Maintenance

    Maintenance NWD-107462-05E

    6-9

    6.1.2.4 16E1-S Option Card Alarms & Status

    Indication Category Descriptions Severity

    Unequipped Alarm Reserved and installed optional card is removed from

    optional slot.

    MJ

    Communication FAIL Alarm Communication failure of equipment internal control

    communication.

    MJ

    E1 LOS Alarm No signal input on E1 port MJ

    E1 AIS Alarm /

    Status

    PDH AIS

    Alarm/Status category can change according to " AIS

    Received Condition Setting

    MJ / -

    Usage Error Alarm Unused E1 CH input signal detection. MN

    E1 AIS Generated Status AIS generation condition on every E1 Channels. -

    6.1.2.5 AUX-S Option Card Alarms & Status

    Indication Category Descriptions Severity

    Unequipped Alarm Reserved and installed optional card is removed from

    optional slot.

    MJ

    Communication FAIL Alarm Communication failure of equipment internal control

    communication.

    MJ

    6.1.2.6 MSE-S Option Card Alarms & Status

    Indication Category Descriptions Severity

    Unequipped Alarm Reserved and installed optional card is removed from

    optional slot.

    MJ

    Communication FAIL Alarm Communication failure of equipment internal control

    communication.

    MJ

    TDM Buffer Underrun Alarm When packets at Ether side of the PWE path are not

    received or a problem occurs with received packets.

    MJ

    Adaptive CLK Status Status Outputs when the adaptive clock state has changed.

    (Acquired, Acquiring, Holdover)

    -

  • Corrective Maintenance

    NWD-107462-05E Maintenance

    6-10

    6.1.2.7 Radio Traffic Aggregation Link Alarm

    Indication Category Descriptions Severity

    Radio Traffic

    Aggregation Link

    Alarm All of member ports belong to the radio group are

    down.

    MJ

    6.1.2.8 IDU Alarms & Status

    Indication Category Descriptions Severity

    Module Alarm Equipment fault MJ

    Bus Error Alarm Data communication BUS failure condition. MJ

    Unequipped (PS) Alarm Installed Power Supply Module is removed from PS

    slot.

    MJ

    Power Supply (PS) Alarm Alarm in case of power failure. MJ

    FAN FAIL Alarm FAN failure MJ

    Unequipped (FAN) Alarm Installed FAN Unit is removed from FAN slot. MJ

    IDU CPU Alarm Alarm. IDU CPU Alarm MN

    Memory FAIL Alarm Detection of memory failure MJ

    USB FAIL Alarm USB memory failure indication WR

    Maintenance Status Maintenance declaration. -

    CLK FAIL Alarm Reference Clock Failed. MN

    CLK Drift Alarm Reference Clock source Frequency drift condition MN

    LTI Alarm Loss of all incoming timing source MJ

    CLK Status Changed Status Reference clock change status

    (1) (Locked Ref1)

    (2) (Locked Ref2)

    (3) (Locked Ref3)

    (4) Holdover

    (5) Freerun

    -

    EXT CLK Unequipped Alarm Installed CLK2M Card is removed from Mainboard. MJ

    EXT CLK LOS Alarm Loss of Signal condition of External clock input. MN

    EXT CLK AIS Alarm AIS (Alarm Indication Signal) condition of External

    Clock input.

    MN

    EXT CLK LOF Alarm Loss of frame condition of External Clock input. MN

    EXT CLK Loop Alarm Indication of EXTERNAL clock input is used as

    EXTERNAL clock output.

    MJ

    E1 LOS Alarm No signal input on E1 port MJ

  • Corrective Maintenance

    Maintenance NWD-107462-05E

    6-11

    Indication Category Descriptions Severity

    E1 AIS Alarm /

    Status

    PDH AIS

    ALARM/Status category can change according to "

    AIS Received Condition Setting

    MJ / -

    PPS FAIL Alarm E1 SNCP Path Protection Switch failed MJ

    Usage Error Alarm Unused E1 CH input signal detection. MN

    SSM FAIL Alarm Received Sync Status Message value is in unstable

    condition.

    MN

    ETH LOS Alarm LOS detection at Optical ETH port. MJ

    ETH TF Alarm Transmit Fail detection at Optical ETH port. MJ

    SFP Type Mismatch

    (ETH)

    Alarm Mismatch between SFP on LCT and installed SFP. MJ

    SFP Removed(ETH) Alarm A SFP is removed. MJ

    LAN LINK Alarm LINK of the LAN Port is disconnected. MJ

    Speed & Duplex Status LAN Port setting (Speed&Duplex) -

    ETH-OAM LOC Alarm ETH OAM LOC ( Loss of connectivity) is detected on

    the indicated MEP

    MJ

    ETH-OAM Mismerge Alarm ETH OAM Mismatch detection notice. MN

    ETH-OAM Unexpected

    MEP

    Alarm ETH OAM Unexpected MEP and Ether OAM

    Unexpected Period detection notice

    MN

    ETH-OAM RDI Alarm ETH OAM RDI reception detection notice MJ

    LLF Message Timeout Status Loss of a conditional signaling in which the LLF

    control signal should be received continuously from

    the opposite radio equipment.

    LLF Status LLF force a LINKDOWN status. The ETH port under

    "edge" mode becomes LINKDOWN.

    -

    Temperature Alarm The temperature is over the threshold MJ

    IDU TOTAL ALM Alarm IDU TOTAL ALM The highest

    Severity will

    be reported

  • Corrective Maintenance

    NWD-107462-05E Maintenance

    6-12/END

    6.1.2.9 TCN Alarms

    Indication Category Descriptions Severity

    RF OFS Alarm Threshold Crossing Notification MN

    RF BBE Alarm Threshold Crossing Notification MN

    RF ES Alarm Threshold Crossing Notification MN

    RF SES Alarm Threshold Crossing Notification MN

    RF SEP Alarm Threshold Crossing Notification MN

    RF UAS Alarm Threshold Crossing Notification MN

    RS OFS Alarm Threshold Crossing Notification MN

    RS BBE Alarm Threshold Crossing Notification MN

    RS ES Alarm Threshold Crossing Notification MN

    RS SES Alarm Threshold Crossing Notification MN

    RS SEP Alarm Threshold Crossing Notification MN

    RS UAS Alarm Threshold Crossing Notification MN

    DMR RS OFS Alarm Threshold Crossing Notification MN

    DMR RS BBE Alarm Threshold Crossing Notification MN

    DMR RS ES Alarm Threshold Crossing Notification MN

    DMR RS SES Alarm Threshold Crossing Notification MN

    DMR RS SEP Alarm Threshold Crossing Notification MN

    DMR RS UAS Alarm Threshold Crossing Notification MN

    MS BBE Alarm Threshold Crossing Notification MN

    MS ES Alarm Threshold Crossing Notification MN

    MS SES Alarm Threshold Crossing Notification MN

    MS SEP Alarm Threshold Crossing Notification MN

    MS UAS Alarm Threshold Crossing Notification MN

    E1 CV Alarm Threshold Crossing Notification MN

    RX Level (MIN) Alarm Threshold Crossing Notification MN

    RX Drop Events Alarm Threshold Crossing Notification MN

    RX Undersize Pkts Alarm Threshold Crossing Notification MN

    RX Fragments Alarm Threshold Crossing Notification MN

    RX CRC Alignment

    Errors

    Alarm Threshold Crossing Notification MN

    RX Oversize Pkts Alarm Threshold Crossing Notification MN

    TX Collisions Alarm Threshold Crossing Notification MN

  • Control Items

    Maintenance NWD-107462-05E

    7-1

    7. CONTROL ITEMS

    Following is the control items list that available on the LCT.

    Following is the control items list that relate to traffic.

    Following control items is available when the maintenance mode is on only. And be careful during the operation on these control items. Because there is possibility to be traffic affected during operation.

    z Loopback Control - IF Loopback Control - TDM Loopback Control (E1 LB1/LB2) - TDM Loopback Control (STM1 LB1/LB2)

    z Database Upload/Download - Data File Upload (Configuration Data) - Data File Download (Program / FPGA / Configuration / MODEM Parameter) - Program ROM Switching

    z H/W F/W Reset - HW Reset Control - FW Reset Control

    z Radio Control - ATPC Manual Control - TX Mute Control - CW Control - TX Modulation Manual Control

    z Laser Management (STM-1 only) - Laser Shutdown Control - ALS Manual Switch Control

    z License Management - Import License Key - Radio Capacity Setting

  • Control Items

    NWD-107462-05E Maintenance

    7-2

    Following is the control items list that is not relate to traffic.

    z Inventory Information - Equipment Inventory Information - Software Inventory Information

    z Performance Monitor - MODEM PMON Report - E1 PMON Report - STM-1 PMON Report - PMON/RMON/FDB Clear

    z Offline Maintenance - Data Adjust - RF Sub Band Select

    7.1 Loopback When there is an interruption of signals, use the SDH/SONET/PDH analyzers and isolate the faulty section by checking the traffic signal by loopback. Setup the test equipment according to the following diagrams for PDH or SDH configuration.

    The facility loopback is toward the baseband interface direction and terminal loopback is toward the CS card direction. They are performed at the STM-1/4 (SDH) or E1 (PDH) interfaces. (Note 1, 2)

    When executing the loopback control, set Maintenance Mode to ON and do not release Maintenance Modes while controlling loopback.

    7.1.1 IF Loopback Execute the MODEM Loopback control for checking the incoming of traffic signal inside MODEM interface (The traffic signal from E1 interfaces to wireless direction).

  • Control Items

    Maintenance NWD-107462-05E

    7-3

    Notes

    1. Turn on the TX Mute Control before executing IF Loopback. While IF Loopback is being executed, the TX INPUT ALM of ODU will occur because the MOD output is determinate. So, the MOD ALM and TX INPUT ALM will be masked while IF Loopback is executed.

    2. The MOD ALM and TX INPUT ALM will be un-masked as soon as the IF Loopback is off.

    3. If the remote control connected at opposite side, the remote control will be disconnect while the IF Loopback is executed and does not restore in default. So, it is necessary to set the IF Loopback Release Time to release IF Loopback automatically before executing the IF Loopback.

    Figure 7-1 IF Loopback

    7.1.1.1 IF Loopback (for 1+1 Twin Path)

    Importance:

    1. Turn ON the TX Mute control before executing IF Loopback.

    2. When executing the Loopback control, set Maintenance Mode to ON and do not release Maintenance Modes during controlling loopback.

    Procedure 7-1

    1. Click Maintenance button on the top of the LCT window to enter maintenance mode.

    2. Expand the Maintenance Control from the LCT menu.

    3. Expand the Loopback Control from the Maintenance Control sub menu.

    4. Select the MODEM Loopback Control from the Loopback Control sub menu.

    5. The MODEM Loopback Control window appears. Click Off at the specify MODEM No. (or SW GRP) of IF Loopback field.

  • Control Items

    NWD-107462-05E Maintenance

    7-4

    Figure 7-2 MODEM Loopback Control Window

    6. The MODEM Loopback Control box appears. Click On for IF Loopback.

    Figure 7-3 MODEM Loopback Control Box

    Table 7-1 IF Loopback

    Parameter Description

    IF Loopback

    Off Turn on the IF Loopback function (Default)

    On Turn off IF Loopback function

    Release Time

    not release Not set automatic restore

    90sec(Default)

    180sec

    300sec

    3600sec(60min)

    43200sec(12h)

    Set automatic restore time

    * Available when executing IF Loopback from remote NE.

    7. Click OK button.

  • Control Items

    Maintenance NWD-107462-05E

    7-5

    8. The Warning box appears. Click OK button.

    Figure 7-4 Warning Box

    9. The Information box appears. Click OK button.

    Figure 7-5 Information Box

    10. The MODEM Loopback Control window appears again. Confirm that the status of IF Loopback of specified MODEM is displayed On.

    Figure 7-6 MODEM Loopback Control Window

    11. After finishing loopback test, click Maintenance button on the top of the LCT window to exit maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

  • Control Items

    NWD-107462-05E Maintenance

    7-6

    7.1.1.2 IF Loopback (for 1+1 Hot Standby)

    Importance:

    1. Turn ON the TX Mute control before executes IF Loopback.

    2. When executing the Loopback control, set Maintenance Mode to ON and do not release Maintenance Modes during controlling loopback.

    Procedure 7-2

    1. Click Maintenance button on the top of the LCT window to enter maintenance mode.

    2. Expand the Maintenance Control from the LCT menu.

    3. Expand the Loopback Control from the Maintenance Control sub menu.

    4. Select the MODEM Loopback Control from the Loopback Control sub menu.

    5. The MODEM Loopback Control window appears. Click Off at the specify MODEM (No.1/No.2) of IF Loopback field.

    Figure 7-7 MODEM Loopback Control Window

    6. The MODEM Loopback Control box appears. Click On for IF Loopback.

  • Control Items

    Maintenance NWD-107462-05E

    7-7

    Figure 7-8 MODEM Loopback Control Box

    Table 7-2 IF Loopback

    Parameter Description

    IF Loopback

    Off Turn on the IF Loopback function (Default)

    On Turn off IF Loopback function

    Release Time

    not release Not set automatic restore

    90sec(Default)

    180sec

    300sec

    3600sec(60min)

    43200sec(12h)

    Set automatic restore time

    * Available when executing IF Loopback from remote NE.

    7. Click OK button.

    8. The Warning box appears. Click OK button.

    Figure 7-9 Warning Box

    9. The Information box appears. Click OK button.

  • Control Items

    NWD-107462-05E Maintenance

    7-8

    Figure 7-10 Information Box

    10. The MODEM Loopback Control window appears again. Confirm that the status of IF Loopback of specified MODEM is displayed On.

    Figure 7-11 MODEM Loopback Control Window

    11. After finishing loopback test, click Maintenance button on the top of the LCT window to exit maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

  • Control Items

    Maintenance NWD-107462-05E

    7-9

    7.1.2 TDM Loopback Control

    7.1.2.1 TDM Loopback Control (E1 Loopback1)

    Execute the TDM Loopback Control (E1 Loopback1) for checking the incoming of E1 traffic signal inside E1 interfaces. (The traffic signal from outside to E1 interfaces direction).

    Note: During executing Loopback, the AIS will be detected at down stream of the specified channel (Loopback channel).

    Figure 7-12 TDM Loopback Control (E1 Loopback1)

    Importance:

    1. When executing the Loopback control, set Maintenance Mode to ON and do not release Maintenance Modes while controlling loopback.

    Procedure 7-3

    1. Click Maintenance button on the top of the LCT window to enter maintenance mode.

    2. Expand the Maintenance Control from the LCT menu.

    3. Expand the Loopback Control from the Maintenance Control sub menu.

    4. Select the TDM Loopback Control (E1 Loopback1) from the Loopback Control sub menu.

    5. The TDM Loopback Control (E1 Loopback1) window appears. Click Off at the specified E1 Loopback1 channel from the Main Board field.

  • Control Items

    NWD-107462-05E Maintenance

    7-10

    Figure 7-13 TDM Loopback Control (E1 Loopback1) Window

    6. The TDM Loopback Control (E1 Loopback) box appears. Click On for specified E1 Loopback1 CH**.

    Figure 7-14 TDM Loopback Control (E1 Loopback1) Box

    Table 7-3 TDM Loopback Control (E1 Loopback1)

    Parameter Description

    Off Turn off E1 Loopback1 function

    On Turn on E1 Loopback1 function

  • Control Items

    Maintenance NWD-107462-05E

    7-11

    7. Click OK button.

    8. The Warning box appears. Click OK button.

    Figure 7-15 Warning Box

    9. The Information box appears. Click OK button.

    Figure 7-16 Information Box

    10. The TDM Loopback Control (E1 Loopback1) window appears again. Confirm that the status of specified CH is displayed On.

  • Control Items

    NWD-107462-05E Maintenance

    7-12

    Figure 7-17 TDM Loopback Control (E1 Loopbak1) Window

    11. After finishing loopback test, click Maintenance button on the top of the LCT window to exit maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

  • Control Items

    Maintenance NWD-107462-05E

    7-13

    7.1.2.2 TDM Loopback Control (E1 Loopback2)

    Execute the TDM Loopback Control (E1 Loopback2) for checking the incoming of E1 traffic signal through MODEM IF. (The traffic signal from wireless to E1 interfaces direction).

    Remote login to the opposite site NE and execute LB2 at opposite site NE.

    Note: During executing Loopback, the AIS alarm will be detected at down stream of the specified channel (Loopback channel).

    Figure 7-18 TDM Loopback Control (E1 Loopback2)

    Importance:

    1. When executing the Loopback control, set Maintenance Mode to ON and do not release Maintenance Modes during controlling loopback.

    Procedure 7-4

    1. Click Maintenance button on the top of the LCT window to enter maintenance mode.

    2. Expand the Maintenance Control from the LCT menu.

    3. Expand the Loopback Control from the Maintenance Control sub menu.

    4. Select the TDM Loopback Control (E1 Loopback2) from the Loopback Control sub menu.

    5. The TDM Loopback Control (E1 Loopback2) window appears. Click Off at the specified E1 Loopback2 Channel from the Main Board field.

  • Control Items

    NWD-107462-05E Maintenance

    7-14

    Figure 7-19 TDM Loopback Control (E1 Loopback2) Window

    6. The TDM Loopback Control (E1 Loopback2) box appears. Click On for specified E1 Loopback2 CH**.

    Figure 7-20 TDM Loopback Control (E1 Loopback2) Box

    Table 7-4 TDM Loopback Control (E1 Loopback2)

    Parameter Description

    Off Turn off E1 Loopback2 function

    On Turn on E1 Loopback2 function

  • Control Items

    Maintenance NWD-107462-05E

    7-15

    7. Click OK button.

    8. The Warning box appears. Click OK button.

    Figure 7-21 Warning Box

    9. The Information box appears. Click OK button.

    Figure 7-22 Information Box

    10. The TDM Loopback Control (E1 Loopback2) window appears again. Confirm that the status of specified CH is displayed On.

  • Control Items

    NWD-107462-05E Maintenance

    7-16

    Figure 7-23 TDM Loopback Control (E1 Loopback2) Window

    11. After finishing loopback test, click Maintenance button on the top of the LCT window to exit maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

    7.1.2.3 TDM Loopback Control (STM-1 Loopback1)

    Execute the TDM Loopback Control (STM-1 Loopback1) for checking the incoming of TDM traffic signal inside STM-1 interfaces. (The traffic signal from outside to STM-1 interfaces direction).

    Note: During executing Loopback, the AIS will be detected at down stream of the specified channel (Loopback channel).

  • Control Items

    Maintenance NWD-107462-05E

    7-17

    Figure 7-24 TDM Loopback Control (STM-1 Loopback 1)

    Importance:

    1. When executing the Loopback control, set Maintenance Mode to on and do not release Maintenance Modes while controlling loopback.

    Procedure 7-5

    1. Click Maintenance button on the top of the LCT window to enter maintenance mode.

    2. Expand the Maintenance Control from the LCT menu.

    3. Expand the Loopback Control from the Maintenance Control sub menu.

    4. Select the TDM Loopback Control (STM-1 Loopback1) from the Loopback Control sub menu.

    5. The TDM Loopback Control (STM-1 Loopback1) window appears. Click Off at the STM1-S field.

    Figure 7-25 TDM Loopback Control (STM-1 Loopback1) Window

    6. The TDM Loopback Control (STM-1 Loopback1) box appears. Click On for specified STM-1 Loopback1 Port**.

  • Control Items

    NWD-107462-05E Maintenance

    7-18

    Figure 7-26 TDM Loopback Control (STM-1 Loopback1) Box

    Table 7-5 TDM Loopback Control (STM-1 Loopback1)

    Parameter Description

    Off Turn off STM-1 Loopback1 function

    On Turn on STM-1 Loopback1 function

    7. Click OK button.

    8. The Warning box appears. Click OK button.

    Figure 7-27 Warning Box

    9. The Information box appears. Click OK button.

    Figure 7-28 Information Box

    10. The TDM Loopback Control (STM-1 Loopback1) window appears again. Confirm that the status of STM-1 Loopback1 Port** is displayed On.

  • Control Items

    Maintenance NWD-107462-05E

    7-19

    Figure 7-29 TDM Loopback Control (STM-1 Loopback1) Window

    11. After finishing loopback test, click Maintenance button on the top of the LCT window to exit maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

    7.1.2.4 TDM Loopback Control (STM-1 Loopback 2)

    Execute the TDM Loopback Control (STM-1 Loopback2) for checking the incoming of TDM traffic signal through MODEM IF. (The traffic signal from wireless to STM-1 interfaces direction).

    Remote login to the opposite site NE and execute STM-1 Loopback2 at opposite site NE.

    Note: During executing Loopback, the AIS will be detected at down stream of the specified channel (Loopback channel).

    Figure 7-30 TDM Loopback Control (STM-1 Loopback 2)

    Importance:

    1. When executing the Loopback control, set Maintenance Mode to ON and do not release Maintenance Modes during controlling loopback.

  • Control Items

    NWD-107462-05E Maintenance

    7-20

    Procedure 7-6

    1. Click Maintenance button on the top of the LCT window to enter maintenance mode.

    2. Expand the Maintenance Control from the LCT menu.

    3. Expand the Loopback Control from the Maintenance Control sub menu.

    4. Select the TDM Loopback Control (STM-1 Loopback2) from the Loopback Control sub menu.

    5. The TDM Loopback Control (STM-1 Loopback2) window appears. Click Off at the STM1-S field.

    Figure 7-31 TDM Loopback Control (STM-1 Loopback2) Window

    6. The TDM Loopback Control (STM-1 Loopback2) box appears. Click On for specified STM-1 Loopback2 Port**.

    Figure 7-32 TDM Loopback Control (STM-1 Loopback2) Box

  • Control Items

    Maintenance NWD-107462-05E

    7-21

    Table 7-6 TDM Loopback Control (STM-1 Loopback2)

    Parameter Description

    Off Turn off STM-1 Loopback2 function

    On Turn on STM-1 Loopback2 function

    7. Click OK button.

    8. The Warning box appears. Click OK button.

    Figure 7-33 Warning box

    9. The Information box appears. Click OK button.

    Figure 7-34 Information Box

    10. The TDM Loopback Control (STM-1 Loopback2) window appears again. Confirm that the status of STM-1 Loopback2 Port** is displayed On.

  • Control Items

    NWD-107462-05E Maintenance

    7-22

    Figure 7-35 TDM Loopback Control (STM-1 Loopback2) Window

    11. After finishing loopback test, click Maintenance button on the top of the LCT window to exit maintenance mode.

    12. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

    7.2 Equipment Maintenance This section provides the maintenance information and procedures related to the equipment and equipment configuration.

    7.2.1 Equipment Utility Following is the list of Data Upload/Download function

    Database Upload (Export (NE->Storage) Utility) Use this function to export the Equipment Config Data, Network Config Data and User Config Data from NE to storage (local PC or USB memory)

    Database Download (Update (Storage->NE) Utility) Use this function to update NE by downloading Program File, FPGA Data and Config Data from storage (local PC or USB memory) to NE.

    Program ROM Switching Use this function to switch running F/W version of IDU and ODU.

    USB Memory Utility Use this function to format USB memory.

  • Control Items

    Maintenance NWD-107462-05E

    7-23

    Log Clear Function Use this function to clear Alarm/Event/Command Log from NE.

    Provisioning Clear Use this function to clear Provisioning setting from Main Board and STM-1 (option).

    Current Time Setting Use this function to time setting of NE.

    7.2.1.1 Database Upload (Export (NE->Storage) Utility)

    Procedure 7-7

    1. Expand the Equipment Utility from the LCT menu.

    2. Select the Export (NE->Storage) Utility from the Equipment Utility sub menu.

    3. The Export (NE->Storage) Utility window appears. Select the specified Config Data and storage (local PC or USB memory), then click Execute button.

    Figure 7-36 Export (NE->Storage) Utility Window

    4. The File Download window appears. Click Save button.

  • Control Items

    NWD-107462-05E Maintenance

    7-24

    Figure 7-37 File Download Window

    5. The Save As window appears. Select the specified directory on the specified device (local PC/USB memory) and then click Save button.

    Figure 7-38 Save As Window

    Table 7-7 Upload Configuration Data

    Data Type Default File Name

    Equipment Configuration Data iPASOLINK-equip.cfg

    Network Configuration Data iPASOLINK-network.cfg

    User Configuration Data iPASOLINK-user.cfg

    Inventory Data Invent_200_********_YYYYMMDD.csv

    6. The Download Complete window appears. Click Close button.

  • Control Items

    Maintenance NWD-107462-05E

    7-25

    Figure 7-39 Download Complete Window

    7. After the upload progress is finished, go to export destination on specified device (local PC or USB memory) to confirm whether the data has been uploaded correctly or not.

    Figure 7-40 Data Folder

    This step ends the procedure.

    7.2.1.2 Database Download (Update (Storage->NE) Utility)

    This function is for downloading iPASOLINK software, firmware (Program File (*.php)/FPGA) and equipment configuration file (*.cnf) from storage (local PC or USB memory *1) to NE.

    Connect USB memory to the USB port at the front of iPASOLINK and the operation is on LCT.

    Following is the items list available on Update (Storage->NE) Utility.

  • Control Items

    NWD-107462-05E Maintenance

    7-26

    Program File Download This function is used for downloading F/Ws from Local PC or USB Memory to the targets. (Main Board, ODU)

    FPGA Data File Download This function is used for downloading FPGA from Local PC or USB Memory to the target cards.

    Configuration Data File Download This function is used for downloading configuration file (Equipment, Network, User) from Local PC or USB Memory to iPASOLINK.

    MODEM Parameter File Download This function is used to update the MODEM parameter file on the MODEM module.

    SSL Server Certificate File Download

    (1) Program File Download

    Importance:

    1. Confirm that you have IDU Main Board Program File that is provided from NEC.

    2. Confirm the current version of IDU Main Board Program File from the IDU tab of Equipment Inventory Information window.

    3. Turn on the Maintenance Mode before downloading IDU Main Board Program File. And do not release Maintenance Mode while downloading.

    (a) Main Board

    Procedure 7-8

    1. Click Maintenance button on the top of the LCT window to turn maintenance mode on.

    2. Expand the Equipment Utility from the LCT menu.

    3. Select the Update (Storage->NE) Utility from the Equipment Utility sub menu.

  • Control Items

    Maintenance NWD-107462-05E

    7-27

    4. The Update (Storage->NE) Utility window appears. Click the Program File radio button and then click Execute button.

    Figure 7-41 Update (Storage->NE) Utility Window

    5. The Update (Storage->NE) Utility box appears. Select the Main Board from drop-down list and then click Next button.

    Figure 7-42 Update (Storage->NE) Utility Box

    6. The source selection window appears. Select destination storage (Local PC/USB Memory) from the Import File field and then click File icon button.

    Figure 7-43 Source Selection Window

  • Control Items

    NWD-107462-05E Maintenance

    7-28

    7. The file selection window appears. Select the Main Board firmware file and then click Open (or OK) button.

    Main Board firmware name: iPASOLINK200- idufw-vx.xx.xx.xx.bin

    Local PC

    Figure 7-44 File Selection Window (1/2)

    USB Memory

    Figure 7-45 File Selection Window (2/2)

    8. The source selection window appears again. Click OK button.

  • Control Items

    Maintenance NWD-107462-05E

    7-29

    Figure 7-46 Source Selection Window

    9. The Warning box appears. Click OK button.

    Figure 7-47 Warning Box

    10. The download progress box appears.

    Figure 7-48 Download Progress Box

    11. After the download is completed, the Update Complete! window appears. Check the Program ROM Switching check box and then click OK button.

  • Control Items

    NWD-107462-05E Maintenance

    7-30

    Figure 7-49 Update Complete! Window

    Table 7-8 Program ROM Switching

    Check Box Description

    ON Executes Program ROM Switching to new version now

    (after click Close button)

    OFF Executes Program ROM Switching later by manually.

    Note: If the check box of Program ROM Switching is not checked, you have to execute Program ROM Switching later by manually. (For more detail refer to 7.2.1.3 Program ROM Switching)

    And use in the following case.

    1. When suppose to download Program File data to NE only and update NE in other days.

    2. When suppose to update multiple NEs in one time.

    3. When suppose to continue downloads another data and then executes the update one time.

    4. Program ROM will be switched to new version after equipment restart. You can confirm running version in Equipment Inventory Information Window.

    12. The Warning box appears. Click OK button. iPASOLINK will be restarted automatically.

    Figure 7-50 Warning Box

    13. The Information box appears. Click OK button. The WebLCT will shutdown automatically.

  • Control Items

    Maintenance NWD-107462-05E

    7-31

    Figure 7-51 Information Box

    14. After iPASOLINK restarts, log in again.

    15. Select the Inventory (Equipment Inventory Information) from the LCT menu.

    16. The Equipment Inventory Information (IDU) window appears. Confirm the Current version (new program running version) of Main Board.

  • Control Items

    NWD-107462-05E Maintenance

    7-32

    Figure 7-52 Equipment Inventory Information Window

    17. After finishing Program File download, click Maintenance button on the top of the LCT window to exit maintenance mode.

    18. Confirm that the MAINT changes from yellow to white.

    This step ends the procedure.

  • Control Items

    Maintenance NWD-107462-05E

    7-33

    (b) ODU

    Importance:

    1. Confirm that you have ODU Program File that is provided from NEC.

    2. Confirm the current version of ODU Program File from the ODU tab of the Equipment Inventory Information window.

    3. Turn on the Maintenance Mode before download ODU Program File. And do not release Maintenance Mode while downloading.

    Procedure 7-9

    1. Click Maintenance button on the top of the LCT window to turn maintenance mode ON.

    2. Expand the Equipment Utility from the LCT menu.

    3. Select the Update (Storage->NE) Utility from the Equipment Utility sub menu.

    4. The Update (Storage->NE) Utility window appears. Check the Program File radio button and then click Execute button.

    Figure 7-53 Update (Storage->NE) Utility Window

    5. The Update (Storage->NE) Utility box (1/2) appears. Select the ODU from drop-down list and then click Next button.

  • Control Items

    NWD-107462-05E Maintenance

    7-34

    Figure 7-54 Update (Storage->NE) Utility Box (1/2)

    6. The Update (Storage->NE) Utility box (2/2) appears. Select the MODEM from drop-down list and then click Next button.

    Figure 7-55 Update (Storage->NE) Utility Box (2/2)

    7. The source selection window appears. Select destination storage (Local PC/USB Memory) from the Import File field and then click File icon button.

    Figure 7-56 Source Selection Window

  • Control Items

    Maintenance NWD-107462-05E

    7-35

    8. The file selection window appears. Select the ODU firmware file and then click Open (or OK) button.

    ODU firmware name:

    Local PC

    Figure 7-57 File Selection Window (1/2)

    USB Memory

    Figure 7-58 File Selection Window (2/2)

    9. The source selection window appears again. Click OK button.

  • Control Items

    NWD-107462-05E Maintenance

    7-36

    Figure 7-59 Source Selection Window

    10. The Warning box appears. Click OK button.

    Figure 7-60 Warning Box

    11. The download progress box appears.


Recommended