+ All Categories
Home > Documents > Manual Eagle Quantum

Manual Eagle Quantum

Date post: 02-Jun-2018
Category:
Upload: manuelmartinez
View: 224 times
Download: 0 times
Share this document with a friend
128
Instructions 95-8470-05 Eagle Quantum Fire and Gas Detection/Releasing System Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.3473 • Fax: 952.829.8750 10/01 95-8470-05
Transcript
Page 1: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 1/128

Instructions 95-8470-05

Eagle Quantum™

Fire and Gas Detection/Releasing System

Detector Electronics Corporation6901 West 110th Street • Minneapolis, Minnesota 55438 USATel: 952.941.5665 or 800.765.3473 • Fax: 952.829.8750

10/01 95-8470-05

Page 2: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 2/128

Section I - System Overview

SYSTEM DESCRIPTION.......................................................I-1

SYSTEM FEATURES ............................................................I-2

MAJOR COMPONENT DESCRIPTIONS ..............................I-2

Intelligent Field Devices on Local Operating

Network/Signaling Line Circuit (LON™/SLC) .......I-2

Local Control Unit (LCU) ..............................................I-2

Local Output Unit (LIOU)..............................................I-3

THEORY OF OPERATION....................................................I-3NETWORK OPERATION DURING A FAULT CONDITION...I-3

Multiple Wiring Faults...................................................I-4

LON/SLC Ground Fault Detection and LCU

Protection..............................................................I-4

Field Devices without Power ........................................I-4

Section II - Local Control Unit and Power Supplies

OVERVIEW...........................................................................II-1

Logic Controller ...........................................................II-1

Communication Gateway............................................II-1

Isolation Module ..........................................................II-1

Optional LCU Versions................................................II-1

EQ2100CG COMMUNICATION GATEWAY ........................II-1

Features......................................................................II-1Description ..................................................................II-1

EQ2100LC LOGIC CONTROLLER.......................................II-5

Features......................................................................II-5

Description ..................................................................II-5

EQ2100IM ISOLATION MODULE ........................................II-7

Features......................................................................II-7

Description ..................................................................II-7

EQ21XXPS SERIES POWER SUPPLIES AND

EQ2100PSM POWER SUPPLY MONITOR .........................II-8

Features......................................................................II-8

Description ..................................................................II-8

EQ2100PSM...............................................................II-8

EQ2200IDCGF ............................................................II-8

Section III - Local Output Unit

OVERVIEW..........................................................................III-1

Enclosure ...................................................................III-1

Fault LED and Reset Switch ......................................III-1

RELAY MODULE .................................................................III-1

Features.....................................................................III-1

Description .................................................................III-1

RELEASE MODULE ............................................................III-2

Features.....................................................................III-2

Description .................................................................III-2

SIGNAL AUDIBLE MODULE ...............................................III-3

Features.....................................................................III-3

Description .................................................................III-3

Section IV - Addressable Field Devices

EQ2200IDC SERIES INITIATING DEVICE CIRCUIT .........IV-1

Description.................................................................IV-1

EQ2200UV UV FLAME DETECTOR...................................IV-1

Description.................................................................IV-1

Software Selectable Options .....................................IV-2

EQ2200UVHT (Hi Temp) UV FLAME DETECTOR .............IV-4

Description.................................................................IV-4

EQ2200UVIR FLAME DETECTOR .....................................IV-4Description.................................................................IV-4

Software Selectable Options .....................................IV-5

EQ2200DCU AND EQ2200DCUEX DIGITAL

COMMUNICATION UNIT ...........................................IV-7

Description..................................................................IV-7

EQ2500ARM AGENT RELEASE MODULE.........................IV-9

Description..................................................................IV-9

EQ2500SAM SIGNAL AUDIBLE MODULE........................IV-10

Description................................................................IV-10

EQ2400NE NETWORK EXTENDER .................................IV-10

Description................................................................IV-10

General Application Information ...............................IV-11

Section V - Detector Application InformationUV DETECTORS..................................................................V-1

Windows .....................................................................V-1

Obstructions................................................................V-1

Smoke.........................................................................V-1

Arc Welding ................................................................V-1

Common Environmental Conditions ...........................V-1

UV DETECTOR POSITIONING ...........................................V-2

UV/IR DETECTORS.............................................................V-2

False Alarm Sources ..................................................V-2

Factors Inhibiting Detector Response.........................V-3

UV/IR DETECTOR POSITIONING.......................................V-3

GAS DETECTOR POSITIONING.........................................V-3

CATALYTIC GAS SENSORS...............................................V-4

Catalytic Sensor Operation .........................................V-4Sensitivity Loss in Catalytic Combustible Gas

Sensors ...............................................................V-6

Calibration Gas ...........................................................V-7

Section VI - General Wiring Requirements

GENERAL INFORMATION .................................................VI-1

Power Wiring .............................................................VI-1

Network Wiring ..........................................................VI-2

Shield Grounding.......................................................VI-2

Junction Box Grounding ............................................VI-3

RS-485 Link Wiring....................................................VI-3

Protection Against Moisture Damage ........................VI-3

Electrostatic Discharge ..............................................VI-3

DETERMINING POWER REQUIREMENTS .......................VI-3EQ2110PS, EQ2130PS AND EQ2175PS .................VI-4

Backup Battery ..........................................................VI-4

Battery Charger .........................................................VI-5

Table of Contents

Page 3: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 3/128

Section VII – System Wiring

EQ2100PSM POWER SUPPLY MONITOR USED WITH

EQ2110PS, EQ2130PS AND EQ2175PS

POWER SUPPLIES............................................................VII-1

Wiring........................................................................VII-1

Startup ......................................................................VII-3

Measuring Battery Voltage and Charging Current....VII-3

EQ2100LCU SERIES LOCAL CONTROL UNIT ................VII-4

EQ2100LIOU LOCAL OUTPUT UNIT ................................VII-7Backplane Wiring......................................................VII-7

RS485 Link Wiring ....................................................VII-7

Power Wiring ............................................................VII-7

RELAY MODULE................................................................VII-8

Wiring........................................................................VII-8

Switch Setting ...........................................................VII-8

RELEASE MODULE...........................................................VII-9

Wiring........................................................................VII-9

Jumpers ....................................................................VII-9

Switch Setting ...........................................................VII-9

SIGNAL AUDIBLE MODULE............................................VII-11

Wiring......................................................................VII-11

Jumpers/Switches...................................................VII-11

Address Switch Setting...........................................VII-11FIELD DEVICES...............................................................VII-13

EQ2200IDC Series Initiating Device Circuit............VII-13

EQ2200IDCGF Series Initiating Device Circuit

Ground Fault ...................................................VII-14

EQ2200IDCSC Series Initiating Device

Circuit Short Circuit .........................................VII-14

EQ2200UV UV Flame Detector ..............................VII-15

EQ2200UVHT High Temperature UV Detector.......VII-17

EQ2200UVIR UV/IR Flame Detector ......................VII-19

EQ2200DCU Digital Communication Unit

used with Det-Tronics H2S/O2 Sensors

or other Two-Wire 4 to 20 ma Devices............VII-22

Sensor Separation for DCU with H2S and

O2 Sensors .....................................................VII-22EQ2200DCU Digital Communication Unit

used with PointWatch......................................VII-23

EQ2200DCUEX Digital Communication Unit

used with Det-Tronics

Combustible Gas Sensors...............................VII-24

EQ2500ARM Series Agent Release Module ..........VII-27

EQ2500SAM Series Signal Audible Module ...........VII-29

EQ2400NE Series Network Extender .....................VII-30

TYPICAL APPLICATIONS................................................VII-31

INSTALLATION CHECKLIST...........................................VII-32

Section VIII – Switch Setting

GATEWAY.........................................................................VIII-1

LOGIC CONTROLLER......................................................VIII-3ISOLATION MODULE .......................................................VIII-3

LON/SLC DEVICE ADDRESS SWITCH SETTING...........VIII-3

Section IX – System Startup

PRE-COMMISSIONING CHECKLIST .................................IX-1

STARTUP PROCEDURE....................................................IX-2

CALIBRATION.....................................................................IX-2

Calibration Algorithm A For Manual Calibration

of Universal DCU................................................IX-2

Calibration Algorithm C For Combustible Gas DCUs

and Automatic Calibration of Universal DCUs....IX-4

Calibration Algorithm D For Universal DCUswith O2 Sensor...................................................IX-5

Calibration Algorithm G For DCUs with PointWatch..IX-6

UV DETECTOR TEST.........................................................IX-7

Fire Alarm Test ..........................................................IX-7

False Alarm Test........................................................IX-7

UV/IR DETECTOR TEST ....................................................IX-7

Manual oi...................................................................IX-8

Automatic oi ..............................................................IX-8

Section X – Specifications

CERTIFICATIONS................................................................X-1

EQ2100LCU LOCAL CONTROL UNIT.................................X-1

EQ2200IDC/IDCGF/IDCSC INITIATING DEVICE CIRCUIT X-3

EQ2200UV and EQ2200UVHT UV FLAME DETECTORS ..X-3EQ2200UVIR UV/IR DETECTOR.........................................X-6

EQ2200DCU AND EQ2200DCUEX

DIGITAL COMMUNICATION UNIT ......................................X-9

EQ2500ARM AGENT RELEASE MODULE.........................X-9

EQ2500SAM SIGNAL AUDIBLE MODULE ........................X-10

EQ2400NE NETWORK EXTENDER..................................X-10

EQ2100PSM POWER SUPPLY MONITOR.......................X-11

EQ2110PS, EQ2130PS AND EQ2175PS

POWER SUPPLIES............................................................X-11

LIOU Local Output Unit .......................................................X-12

LIOU RELAY MODULE ......................................................X-12

LIOU RELEASE MODULE .................................................X-12

LIOU SIGNAL AUDIBLE MODULE ....................................X-12

COMBUSTIBLE GAS SENSOR .........................................X-13ELECTROCHEMICAL SENSORS......................................X-13

POINTWATCH....................................................................X-13

Section XI – System Maintenance

ROUTINE MAINTENANCE .................................................XI-1

Manual Check of Output Devices ..............................XI-1

O-Ring Maintenance..................................................XI-1

Flame Detector Maintenance.....................................XI-1

Gas Sensor Maintenance ..........................................XI-1

Batteries.....................................................................XI-2

TROUBLESHOOTING.........................................................XI-2

REPLACEMENT PARTS.....................................................XI-2

DEVICE REPAIR AND RETURN ........................................XI-3

ORDERING INFORMATION ...............................................XI-3

Table of Contents – Continued

Page 4: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 4/128

IMPORTANT Be sure to read and understand the entire

instruction manual before installing or operating the Eagle Quantum System. Only qualified personnel should install, maintain or operate the Eagle

Quantum System.

WARNING The hazardous area must be de-classified prior to

removing a junction box cover or opening a detector assembly with power applied.

CAUTION 1. The wir ing procedures in this manual are

intended to ensure proper functioning of the devices under normal conditions. However,

because of the many variations in wiring codes and regulations, total compliance to these

ordinances cannot be guaranteed. Be certain that all wiring complies with the NEC as well as all local ordinances. If in doubt, consult a

qualified official before wiring the system.

2. Some Eagle Quantum devices contain semiconductor devices that are susceptible to

damage by electrostat ic discharge. An electrostatic charge can build up on the skin and discharge when an object is touched. Always

observe the normal precautions for handling electrostatic sensitive devices, i.e. use of a wrist

strap (if available) and proper grounding.

3. To prevent unwanted actuation, alarms and extinguishing devices must be secured prior to performing system tests.

Section ISystem Overview

SYSTEM DESCRIPTION

The Eagle Quantum System serves multiple roles in the

monitoring and protection of hazardous areas. It is a“fire detection and extinguishing agent release system”

combined with a “hazardous gas monitoring system,”integrated on a fault tolerant digital communication

network. The Eagle Quantum system utilizes anadvanced distributed architecture that is equally adeptat monitoring analog process signals like combustible

or toxic gas concentrations, and discrete “contactclosure” type devices such as manual fire alarm “call

boxes” and heat detectors, as well as Det-Tronicsoptical flame detection. This sensor information is then

transmitted to the control unit to execute the firesuppression logic, to control agent release, signaling,

and annunciation outputs, and to communicate withexternal operator interface systems for configurationand monitoring.

INSTRUCTIONS

Eagle Quantum

Fire and Gas

Detection/Releasing System

© Detector Electronics Corporation 2001 10/01 95-8470-05

DET-TRONICS®

*oi is Detector Electronics' Trademark for its patented OpticalIntegrity Systems, U.S. Patent 3,952,196, United Kingdom Patent1,534,969, Canada Patent 1,059,598.

Page 5: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 5/128

I–2

SYSTEM FEATURES

• Deluge and pre-action release capability for fire

suppression.

• Agent release capability for fire suppression.

• Up to 244 addressable field devices and 32,500 feet

(10,000 meters) of wiring on the network.

• Supports up to 6 network extenders.

• Compatible with Det-Tronics flame and gas detectors.

• Accommodates a variety of third-party devices with 4to 20 ma or “dry contact” type inputs.

• Fault tolerant communication loop.

• Non-volatile memory for alarm and calibration logging.

• Built in diagnostics.

• Programmable logic.

• Modbus RTU Master/Slave and Allen Bradley DF1

communication capability through two electrically

isolated RS-232 serial ports.

• Up to 4 gateways and 4 logic controllers.

• Up to 75 amperes of alarm current per power supply.

• FM Approved to ANSI/NFPA-72-1996 National FireAlarm Code. See Figure A1 in Appendix A for

installation requirements.

• FM, CSA, CENELEC and CE Mark Certifications. See

Appendix A, B and C respectively for details andspecific installation requirements.

MAJOR COMPONENT DESCRIPTIONS

The system consists of three basic components (seeFigure I-1):

INTELLIGENT FIELD DEVICES ON LOCAL OPERATINGNETWORK/SIGNALING LINE CIRCUIT (LON™/SLC)

The LON/SLC is a fault tolerant, two wire, digitalcommunication network, arranged in a loop starting andending at the Local Control Unit. The LON/SLC

supports up to 244 intelligent field devices spread overa distance of up to 32,500 feet (10,000 meters). The

LON/SLC serves as the Signaling Line Circuit (SLC) for

the fire detection/suppression aspects of the system.

LOCAL CONTROL UNIT (LCU)

The LCU functions as the “heart” of the Eagle Quantumsystem. The LCU contains three replaceable modules

FIRE DETECTION

C1899

PLC/DCS

OIS

LOCALOUTPUT

UNIT(LIOU)

AUDIBLEINDICATORS

VISUALINDICATORS

FIRESUPPRESSION

GATEWAYLOGIC

CONTROLLERISOLATIONMODULE

LOCAL CONTROL UNIT (LCU)

FLAME

DETECTORSIDCs DCUs

AGENTRELEASEMODULES

FIRE

SUPRESSION

SIGNALAUDIBLE

MODULES

VISUAL/AUDIBLE

INDICATORS

FIRE/GAS RESPONSEGAS DETECTION

CONTACTCLOSURE

DEVICE

GAS SENSOROR OTHER

4 TO 20 MA INPUT

NETWORK

EXTENDERS

POWER

MONITORS

LON/SLC LON/SLC

Figure I – 1 —Block Diagram of Eagle Quantum System

Page 6: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 6/128

that perform all the communication, command, andcontrol functions for the system. It includes all the

required operator interface controls for a fire alarmsystem (silence, acknowledge, reset, isolate),annunciation relays, a local information display, and

communication interfaces for computer basedconfiguration and monitoring of the system.

LOCAL OUTPUT UNIT (LIOU)

The LIOU consists of a rack controlled by the LCU thatcan hold up to six FenwalNet 2000 modules. These

modules allow the control of Notification ApplianceCircuits (NACs), fire suppression agent release (CO2,

Halon, FM200) using supervised relays, as well asunsupervised relays for other needs.

THEORY OF OPERATION

During normal operation, each node on the networkmonitors its attached sensor or other input, determines if

it has an alarm condition, analyzes its own health,

checks network integrity, and then packages up thisinformation for transmission to the communicationgateway, located in the LCU. This Standard Periodic

Report (SPR) contains 16 pieces of “discrete”information on the status of the node and, whereapplicable, also contains the analog value of its sensor.

At the time of node configuration, the report rate of theSPR can be set to anywhere between 1 and 10

seconds.

In the LCU the Communication Gateway collects all ofthe incoming SPRs from the field devices and puts theinformation into “datatables.” Datatables are organized

areas of memory in the gateway that can be “read” byexternal “host devices” using one of the gateway’s serial

ports. If any of the SPRs indicate an out of tolerancecondition, the gateway will display this information on its

integrated faceplate display. The gateway also has fourprogrammable relays whose action can beprogrammed to events in the SPRs of the monitored

nodes.

In addition to SPRs, nodes used as a part of the firedetection and suppression system, such as fire

detectors or Initiating Device Circuits (IDCs) interfacedwith heat detectors, manual call points, etc. send aseparate Standard Supervisory Report (SSR) to the

Logic Controller, located in the Local Control Unit. TheLogic Controller, which manages the fire suppression

logic, uses these SSR messages to verify that the nodesused in the fire alarm and suppression logic are active

and able to communicate. If the Logic Controller doesnot receive SSRs from a required node, it willannunciate a “trouble” condition.

If a “Fire Alarm” is detected by a Flame Detector orInitiating Device Circuit (IDC), the affected node will

send a special Acknowledged Exception Report (AER)directly to the Logic Controller. The AER is transmittedas soon as an alarm is detected to maximize system

performance. When the Logic Controller receives theAER, it sends the originating node a message

acknowledging its receipt. If the node originating theAER does not receive an acknowledgement, it will re-

transmit the AER until it receives an acknowledgement.This exchange of messages is used to ensure thatcritical messages are received at all appropriate

registers throughout the system.

Once the Logic Controller receives a Fire Alarmmessage from a field device, “fixed logic” will activate

built-in annunciation circuits, which consist of both avisible and audible alarm. The “programmable logic”will execute any specified voting, timing, and/or zone

logic and subsequently activate the appropriate outputcircuits for Notification Appliance Circuits (NACs), agent

release circuits, and unsupervised relay outputs.

The faceplate of the Logic Controller has twopushbuttons. “ACKNOWLEDGE” will silence the built in

audible alarm and illuminate the “Acknowledge LED”located on the faceplate next to the “Acknowledge”pushbutton. “SILENCE” will silence selected NACs in

the field and illuminate the “Silence LED” located on thefaceplate next to the “Silence” pushbutton. The Logic

Controller also features a keyswitch to reset the systemafter the event is over.

NETWORK OPERATION DURING AFAULT CONDITION

The Eagle Quantum system utilizes a unique patented

technique for detecting problems in the communicationnetwork wiring. This state-of-the-art feature minimizes

the possibility of a communication breakdown in theevent of a wiring fault in the communication loop andcan also serve as an aid in troubleshooting.

The communication network is constructed as a loop

that starts and ends at a pair of communication portslocated at the LCU. The nodes communicate with the

LCU over the LON/SLC as shown in Figure I-2.

Each field device node contains both the hardware and

software necessary to isolate and re-routecommunication in the event of a network wiring fault.

When a problem occurs somewhere within the networkwiring, the communication gateway located in the LCU

annunciates the fault, while the fault isolation circuitry inthe affected nodes isolates the section of the networkwhere the fault has occurred. Communication is

I – 3 95-8470

Page 7: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 7/128

thereby ensured and will continue over the network.See Figure I-3.

A single open or short on the LON/SLC will not affectsystem communication between the field devices and

the gateway. System communication will continue untilthe wiring problem can be repaired.

MULTIPLE WIRING FAULTS

In the event of multiple wiring faults on the LON/SLC,the nodes between the faults will continue to function,

but the faults will prevent them from communicating withthe gateway. See Figure I-4. In this example, nodes 1

to 4 communicate using one gateway port (path A) andnodes 7 and 8 use the other gateway port (path B).

Nodes 5 and 6 are unable to report to the gatewaybecause they are isolated by the two wiring faults.

LON/SLC GROUND FAULT DETECTION AND LCUPROTECTION

The LCU contains an isolation module that checks theLON/SLC for ground faults. Should a ground fault bedetected, it is indicated by an LED on the isolation

module’s faceplate. The isolation module also ensurescommunication with the field devices even if there is aLON/SLC short circuit directly adjacent to the LCU.

FIELD DEVICES WITHOUT POWER

All Eagle Quantum field devices are designed so that a

“pass-through” circuit is created for the network wiringon a loss of power to the node. This ensures networkintegrity even when a node is down for service or has

been damaged. The Communication Gateway in theLCU will report powered-down nodes as “not-

communicating.”

IMPORTANT

Since it is impossible to predict where a network fault might occur or exactly what effect it will have

on actual system operation, it is important to diagnose and repair any fault as soon as possible after it is detected to ensure reliable system

operation.

I – 4

A1851

NODE 1 NODE 8

NODE 3 NODE 6

NODE 2 NODE 7

NODE 4 NODE 5

LCU

Figure I – 2 —Normal Communication over the Digital Highway

A1852

LCUNODE 1 NODE 8

NODE 3 NODE 6

NODE 2 NODE 7

NODE 4 NODE 5

PATH A PATH B

WIRING FAULT

Figure I – 3 —Communication with a Single Wiring Faulton the Network

A1853

LCUNODE 1 NODE 8

NODE 3 NODE 6

NODE 2 NODE 7

NODE 4 NODE 5

PATH A PATH B

WIRING FAULTS

Figure I – 4 —Communication with Multiple Wiring Faultson the Network

Page 8: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 8/128

II–1 95-8470

Section IILocal Control Unit (LCU) and

Power Supplies

OVERVIEW

The Local Control Unit (LCU) is the “heart” of the Eagle

Quantum system. External host devices such as PLC’s

or DCS’s interface through the LCU, the fire detectionand releasing logic resides in the LCU, control of thereleasing, signaling, and annunciation outputs are

handled by the LCU, and the Local OperatingNetwork/Signaling Line Circuit (LON/SLC), through

which all field devices communicate, starts and ends itsloop at the LCU. Physically, the LCU consists of a threeslot rack style enclosure that houses the Communication

Gateway, Logic Controller, and Isolation Module. Thesethree modules plug into the backplane and are secured

with thumb screws. All external wiring is routed throughconduit entries at the bottom and sides of the unit. The

wiring terminals are protected by a removable cover.

The LCU can be installed in Class I, Division 2hazardous locations. Refer to Appendix A (FMRC) and

Appendix B (CSA) for details.

LOGIC CONTROLLER

The Eagle Quantum Logic Controller uses sevenmicroprocessors and parallel processing techniques toexecute the logic used for fire suppression. Its wealth

of logical operators allow for the easy development ofnearly any imaginable type of cross-zone monitoring,

voting, and timed operations that might be needed in afire suppression system. The Logic Controller supports

ANSI/NFPA 72 Class A, Style 7 communication with fielddevices.

COMMUNICATION GATEWAY

The Eagle Quantum Communication Gatewaycommunicates through two serial links for configuration

and monitoring. This allows for device configurationusing a comprehensive set of Det-Tronics authoredsoftware tools. The monitoring is provided to the

Operator Interface Station(s) (OIS) through Modbus orAllen-Bradley compatible protocols. The gateway also

provides four programmable relays that can be used toannunciate conditions being monitored by the devices

on the LON/SLC.

ISOLATION MODULE

The Isolation Module protects the integrity of the

LON/SLC wiring by isolating shorts and monitoring forground faults. It also provides electrical isolation for the

two serial communication ports between the gatewayand host devices.

OPTIONAL LCU VERSIONS

An optional EQ2101LCU is available with provisions for

two 24 vdc power inputs. Two reliable and independent24 vdc supplies, in accordance with ANSI/NFPA 72

section 1-5.2, must be supplied. If either of the suppliesis missing or a wiring problem occurs, a troublecondition will be annunciated.

Logic controllers can be added to the communicationnetwork to segment it into logical groups. Up to fourlogic controllers can be used on each network.

Auxiliary gateways can be added to provide additionalrelays or serial port connections to PLCs or DCSs. Up to

three auxiliary gateways can be added to the Quantumnetwork. Gateways located outside the LCU can be

turned off without disrupting LON/SLC communicationwith the LCU.

EQ2100CG COMMUNICATION

GATEWAY

FEATURES

• Utilizes Modbus or Allen Bradley protocols

• Transformer isolation of network ports

• Four programmable relay outputs

• Three digit display and bar graph

• LEDs indicate relay status

• EMI/RFI hardened

DESCRIPTION

The Eagle Quantum Communication Gateway is used inconjunction with Det-Tronics software to configure the

system as well as to provide information on an ongoingbasis to external systems such as PLCs and DCSs. It

also provides local display and four programmablerelay outputs. In addition, the gateway provides a

heartbeat signal used to test for LON/SLC integrity, toprovide time and date information to field devices, andto monitor for the continued presence of all configured

field devices.

The gateway receives and stores the current status andprocess variable information from all devices on the

“Local Operating Network/Signaling Line Circuit”(LON/SLC) communication loop. It services all validrequests by Modbus RTU masters and/or Allen-Bradley

DF1 masters that are received through its two hostinterface serial ports. When acting as a Modbus RTU

master, the gateway will automatically transfer keyprocess variable and status information to a default or

user selected Modbus RTU slave address and registeroffset.

Page 9: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 9/128

II–2

During normal operation the gateway produces aperiodic (250 millisecond) “heartbeat” signal on the

network, which is used by all field devices as a part oftheir network fault isolation routine. Every fourth“heartbeat” (1 second intervals) also includes a time

and date message that is used by the field devices forlogging calibration, alarm, and other events.

The gateway has sufficient non-volatile memory to store

configuration data for all networked field devices, whichis downloaded to the gateway from the OIS.

Faceplate Description

The faceplate provides four relay LEDs and one faultLED, a digital display, a bar graph, and a reset

pushbutton. See Figure II-1.

DIGITAL DISPLAY

The digital display is a three digit “seven segment”

display. During normal operating conditions, thedisplay indicates “000.” When a system event occurs

(alarm, fault or calibration) the display sequentially

shows the device address, followed by deviceidentification code, followed by device percent fullscale/fault code/calibrate signal.

Each indication is shown for 3/4 second, followed by a1/4 second delay before going to the next indication.

If more than one event should occur, the entire display

(digital display and bar graph) will track the status ofeach address where activity is occurring by sequencingthrough each event by order of address.

DEVICE ADDRESS

All three digits are on and the decimal point for each

digit is also on. Up to 250 addresses are available(displayed 0.0.1. to 2.5.0.).

DEVICE IDENTIFICATION CODE

See Table II-1 for device identification codes.

DEVICE PERCENT FULL SCALE/FAULT

CODE/CALIBRATE

The display follows the sensor input in percent of fullscale up to 100% full scale. A negative sign is used to

indicate a negative zero drift condition. See Table II-2for the status codes used by the gateway display.

A fault condition is indicated as “FXX,” with F indicating

that a fault has occurred and XX identifying the type offault that is detected.

If a detector is being calibrated, the display will show“CAL.”

BAR GRAPH

The 20 segment bar graph tracks the input signal fromthe sensor, providing a 0 to 100% full scale reading of

sensor input.

RELAY 1 LED

RELAY 2 LED

RELAY 3 LED

RESET PUSHBUTTON

DIGITAL DISPLAY

BAR GRAPH DISPLAY

RELAY 4 LED

FAULT LED

B1884

RELAY 1100

90

80

70

60

50

40

30

20

10

RELAY 2

RELAY 3

RELAY 4

FAULT

RESET

EAGLE QUANTUM™GATEWAY

DET-TRONICS®

Figure II–1—Gateway Faceplate

Table II–1—Device Identification Codesused by Gateway Digital Display

DISPLAY READING DEVICE

Gateway

IDC

UV Detector

UV/IR Detector

Logic Controller

DCU

ARM

SAM

Power Supply Monitor

T0026B

Page 10: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 10/128

II–3 95-8470

Table II–2—Status Codes used by Gateway Digital Display

F10 Gateway FaultF20 Not CommunicatingF30 LON FaultF32 Right Heartbeat Fault (Net Test Fault)F40 Stuck Reset SwitchF50 Upper Transceiver FaultF51 Lower Transceiver FaultF60 Invalid Configuration or Unable to ConfigureALA Output Relay ActiveBytes Bytes Remaining for Non-volatile Memory Write

F10 Fault

F11 Low Voltage FaultF13 Input 1 OpenF14 Input 2 OpenF20 Not Communicating, Com 1 or Com 2 faultF60 Invalid Configuration or Unable to ConfigureA10 Input 1 is ActiveA01 Input 2 is ActiveA11 Both Inputs are Active

F10 FaultF11 Low Voltage FaultF13 Input 1 Open or ShortF14 Input 2 Open or ShortF20 Not Communicating, Com 1 or Com 2 faultF60 Invalid Configuration or Unable to ConfigureA10 Input 1 is ActiveA01 Input 2 is Active

A11 Both Inputs are Active

F10 FaultF11 Low Voltage FaultF13 Ground Fault “–”F14 Input OpenF20 Not Communicating, Com 1 or Com 2 faultF60 Invalid Configuration or Unable to ConfigureA10 Ground Fault “+”A01 Input is ActiveA11 Input Active and Ground Fault “+”

F10 FaultF11 Low Voltage FaultF12 oi FaultF13 290 Volt FaultF20 Not Communicating, Com 1 or Com 2 fault

F60 Invalid Configuration or Unable to Configurecps Counts Per Second, Displayed During Alarm and Pre-Alarm

F10 FaultF11 Low Voltage FaultF20 Not Communicating, Com 1 or Com 2 faultF60 Invalid Configuration or Unable to Configurecps* Counts Per Second, Displayed During Alarm

* Can be either UV counts or IR counts, depending on the mode selected at the OIS.

F10 TroubleF17 Ground faultF20 Not Communicating, Upper Transceiver Fault or Lower Transceiver FaultF60 Invalid Configuration or Unable to ConfigureALA AlarmBytes Bytes Remaining for Non-volatile Memory Write

F10 Sensor Fault or Calibration FaultF11 Low Voltage FaultF20 Not Communicating, Com 1 or Com 2 faultF60 Unconfigured, Invalid Configuration or Unable to ConfigureCAL Calibration in Progressnnn Process variable displayed as a % of the Calibrated Full Scale Reading

Sol Release display codeF10 Open OutputF11 Low Voltage FaultF12 Low Auxiliary Voltage FaultF20 Not Communicating, Com 1 or Com 2 faultF21 Network Variable Input FaultF60 Invalid Configuration or Unable to Configure

Gateway

IDC

IDCSC

IDCGF

UV Detector

UV/IR Detector

LogicController

DCU

ARM

Page 11: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 11/128

Page 12: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 12/128

II–5 95-8470

EQ2100LC LOGIC CONTROLLER

FEATURES

• Programmable logic

• LEDs indicate status conditions

• Alarm, Trouble and Supervisory SPDT relays

• EMI/RFI hardened

DESCRIPTION

The logic controller provides the control function for the

fire detection portion of the Eagle Quantum fire and gassafety system. It monitors messages from the devices

on the loop that are configured to report to thatcontroller (up to 120 in combination) and generates the

appropriate output(s) in response to the inputconditions. The logic controller supports ANSI/NFPA 72Class A, Style 7 communication with the field devices.

The logic controller uses fixed logic to control the

faceplate display and onboard alarm, trouble andsupervisory outputs per ANSI/NFPA 72.

The logic controller also has programmable logic, whichallows it to be customized to perform complex logic

operations including voting and timing. It alsocommunicates with the output modules located in the

LIOU, controlling system functions such as alarmsignaling, agent release and relay actuation.

The logic controller receives configuration informationthrough the gateway by means of its serial connection

to the operator interface system.

Faceplate Description

The faceplate has a key switch, two pushbutton

switches, and nine LEDs. See Figure II-2.

KEY SWITCH

The key switch on the front panel of the logic controller

is used to select from four operating modes — Normal,Acknowledge & Silence Enable, Reset or Isolate. The

key may be removed in the Normal or Isolate position.

NOTE Always rotate the key switch slowly when selecting operating modes.

Normal

In the normal mode, the controller’s program is runningand the outputs are enabled.

Acknowledge & Silence Enable

This mode enables the Acknowledge and Silence

pushbuttons.

NOTE

The Acknowledge and Silence pushbuttons are inhibited when the key switch is in the Normal

position.

Reset

In the reset mode, normal operation is inhibited and areset signal is sent to the LIOU and field output devices.

This mode is also used for programming. In theprogram mode, normal operation is inhibited. This is

the only mode that allows configuration information tobe downloaded to the logic controller from the gateway.

When the program mode is exited, configurationinformation is sent to the LIOU.

NOTE If the key switch is left in the RESET position for

more than a second or if the logic controller is in the Program mode, a Trouble condition will be indicated.

C1854

POWER

ALARM

TROUBLE

POWER FAULT

SUPERVISORY

EAGLE QUANTUM™LOGIC CONTROLLER

ACKNOWLEGDE

SILENCE

PROGRAM

ISOLATE

NORMAL

ACKNOWLEDGE& SILENCE

ENABLE

ISOLATE

RESET

KEY SWITCH

PUSHBUTTONSWITCHES

DET-TRONICS®

Figure II–2—Logic Controller Faceplate

Page 13: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 13/128

II–6

Isolate

In the isolate mode, normal operation continues while

the logic controller sends an isolate command to all theagent release outputs in the LIOU. The Isolate LED

turns on in a steady state if all release outputs areisolated. The LED is off when none of the outputs areisolated and blinks if only some of the outputs are

isolated.

NOTE User logic is required to isolate LON based agent release modules.

PUSHBUTTON SWITCHES

Acknowledge

Pressing the acknowledge pushbutton with

Acknowledge/Silence enabled acknowledges thecurrent status condition(s) and turns off the internalbuzzer.

Silence

Pressing the silence pushbutton silences the selected

signaling outputs in the LIOU. (The specific LIOUoutputs that are affected by the silence button areselected at the time of system configuration.)

NOTE

Signaling devices connected to LON based Signal Audible Modules must be silenced via user logic.

LEDS

Nine faceplate LEDs are provided for indicating systemstatus conditions.

POWER (Green)

Indicates that power is applied to the device.

ALARM (Red)

Indicates that the Fire Alarm relay is actuated.

TROUBLE (Yellow)

Illuminated when a trouble condition occurs in the wiring

or devices associated with the fire system. (Troublerelay is active). All logic controller faults are latching

and must be cleared by resetting with the key switch.Det-Tronics configuration software should be used to

determine the specific problem.

POWER FAULT (Yellow)

Indicates that a power supply fault has been detected.

This could involve any of the following:

— ground fault

— low or missing AC input voltage— 24 vdc power supply

— battery related fault— power supply monitor

— IDCGF.

SUPERVISORY (Yellow)

Follows the status of the Supervisory relay.

ACKNOWLEDGE (Yellow)

Illuminated when the acknowledge switch is pressedand remains lit until the unit is reset.

SILENCE (Yellow)

Illuminated when the silence switch is pressed and

remains on until the unit is reset.

PROGRAM (Yellow)

Indicates that the logic controller is in the

Reset/Program mode.

ISOLATE (Yellow)

Indicates that the logic controller is in the Isolate mode.

Relays

The Logic Controller has three relay outputs,responding to the following status conditions:

— Fire alarm (Activated when any device that is

configured as a fire alarm input is active. Thisincludes all flame detectors and IDCs that areconfigured as alarm type inputs.)

— Supervisory (Activated when a supervisory faultoccurs at any LON device that is configured to

report to the Logic Controller as a supervisoryinput.)

— Trouble (Normally energized). Activated when anyof the following occurs:

LIOU communication, wiring or other faultAC input failure

Battery faultPower supply fault

Invalid configurationLON faultLON device communication fault

Gateway LON faultRAM fault.

Page 14: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 14/128

The relays latch until the Logic Controller is reset.

The relays have SPDT (Form C) contacts, rated 5

amperes resistive at 30 vdc. Terminals are provided onthe LCU backplane for connecting EOL resistors.

Buzzer

The Logic Controller is furnished with an internal buzzer

for signaling a change in status. The buzzer has fourmodes of operation:

— Off— Alarm

— Trouble— Supervisory.

In the normal mode with no events occurring, the buzzeris off. If an alarm, trouble or supervisory event occurs,

the appropriate tone is generated. In the event ofmultiple events, the order of priority is alarm,

supervisory, then trouble. Refer to Figure II-3 for thetone patterns that identify each type of event.

The buzzer can be silenced by pressing theACKNOWLEDGE switch on the front panel (the key

switch must be in the “Acknowledge & Silence Enable”position). If a second event occurs or if the original event

stops and then returns, the buzzer will again turn on.

NOTE

If a trouble condition has been acknowledged and the condition exists for more than 24 hours, the

buzzer will again sound.

EQ2100IM ISOLATION MODULE

FEATURES

• Ground fault detection

• RS-232 isolation for data rates up to 19.2 Kbaud

• LEDs indicate status conditions

• EMI/RFI hardened

DESCRIPTION

The Eagle Quantum Isolation Module (LON Isolator)protects the integrity of the communication network

wiring by isolating shorts and monitoring for groundfaults. The Isolation Module also provides electrical

isolation for the two serial communication ports betweenthe gateway and host devices.

Visual Indicators

LEDs on the front panel are provided for indicatingstatus conditions. See Figure II-4 for LED locations and

Table II-3A and II-3B for possible fault conditions.

II–7 95-8470

B1856

LON ISOLATOR

EAGLE QUANTUM™LON ISOLATOR

GROUND FAULT

GROUND FAULT

POWER –

POWER +

COM 2

COM 1

DET-TRONICS®

Figure II–4—Isolation Module Faceplate

0.5 SEC

0.5 SEC 0.5 SEC 1.5 SEC

0.1 SEC0.1 SEC

5.0 SEC

2.0 SEC

ALARM

TROUBLE

SUPERVISORY

A1855

Figure II–3—Tone Pattern for Logic Controller Buzzer

Page 15: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 15/128

EQ21XXPS SERIES POWERSUPPLIES AND EQ2100PSM POWERSUPPLY MONITOR

FEATURES

• Monitors primary AC supply and battery integrity.

• Power supplies available with 10, 30 or 75 ampereoutput.

• Field addressable.

• Unique patented fault isolation.

• Utilizes state-of-the-art communication technology.

• Pass through communication circuitry on power loss.

• EMI hardened.

• FMRC approved and CSA certified for use in Eagle

Quantum systems.

DESCRIPTION

These power supplies are available with 10, 30 or 75ampere outputs. Input voltage is selectable for 120, 208

or 240 vac. Refer to Section X or Table VI-5 (Section VI)for power supply specifications.

EQ2100PSM

The EQ2100PSM Power Supply Monitor is used inconjunction with an EQ21xxPS power supply andbackup batteries to provide power for the Eagle

Quantum system. Since the power supply monitor

resides on the communication loop (LON), any troublecondition related to system power will immediately be

reported through the Local Control Unit. Statusconditions being monitored include power supplyfailure, loss of AC power, loss of battery power, power

ground fault, AC voltage, DC voltage and batterycharging current levels.

The output of the power supply monitor is a status

message that is sent along the communication loop tothe gateway and logic controller in the Local ControlUnit (LCU). System response to the message is

determined at the time of configuration. The powersupply monitor supports ANSI/NFPA 72 Class A, Style 7

communication with the LCU.

Enclosure

The power supply monitor must be located in acontrolled non-hazardous area and must be mounted in

a suitable metallic nationally recognized test laboratory(NRTL) labeled NEMA rated enclosure.

Fault Tolerant Network

Like other Eagle Quantum network devices, the powersupply monitor utilizes a unique patented technique for

detecting network wiring problems. This featureminimizes the possibility of a communication breakdownin the event of a wiring fault and can also serve as an

aid in troubleshooting.

A single open or short on the network will not affectsystem communication between the field devices and

the LCU. System communication will continue until thewiring problem can be repaired.

Status LEDs

The power supply monitor has three LEDs to provide avisual indication of status conditions:

Green — On when power is applied to the device.

Red — On (flashing) indicates a troublecondition.

Yellow — Used for factory diagnostic purposes.

EQ2200IDCGF

The available EQ2200IDCGF Initiating Device Circuit

Ground Fault Monitor responds to the presence of aground fault within the power circuitry of the Eagle

Quantum system. It provides a supervised dry contactinput and ground fault monitoring circuitry for indicatinga power supply trouble condition. It is intended for use

with a third party power supply.

II–8

“Power +” ground fault occurs if:- Resistance of “Power +” to earth is <136K ohms.

- DC voltage is below +19.0 vdc (with 26 vdc supply voltage).

- Current >0.14 ma between “+” wire and earth.

“Power –” ground fault occurs if:- Resistance of “Power –” to earth is <15K ohms.

- DC voltage is below –4.9 vdc (with 26 vdc supply voltage).- Current >0.1 ma between “–” wire and earth.

“COM 1 / COM 2” ground fault occurs if:

- “LON B” wire resistance to earth is <4K ohms.- “LON B” wire DC voltage is below –4.0 vdc.

- Current >1.0 ma between “LON B” wire and earth.

—OR—

- “LON A” wire resistance to earth is <2K ohms.

- “LON A” wire DC voltage is below +2.0 vdc.

- Current >1.0 ma between “LON A” wire and earth.

Note: Voltages are nominal and may vary slightly (voltages referenced toearth).

Resistance/voltage levels between sides are different — samereadings indicate they are shorted together.

Table II-3A—Power Supply Ground Fault

Table II-3B—LON Ground Fault

Page 16: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 16/128

Section IIIEQ2100LIOU

Local Output Unit

OVERVIEW

The Local Output Unit (LIOU) consists of a six position

card rack. Available modules include:

Relay Module — four independently programmableunsupervised relay contacts.

Release Module — one release circuit and threesignaling circuits.

Signal Audible Module — four independentlyprogrammable signaling circuits.

These modules can be installed in the rack in anyposition. The Local Control Unit (LCU) automatically

reads the output module’s type and address on power-up. It is recommended that modules performing like

functions be inserted adjacent to each other to facilitateidentification and field wiring runs.

The assembly is controlled and supervised by the localcontrol unit (using an RS-485 serial communication link)

and must be mounted nearby (less than 20 feet). Up tofour LIOUs can be controlled by the LCU, adding a

maximum of 24 output modules to the system. Whenmultiple LIOUs are used, the last one in the chain must

be no more than 20 cable feet from the LCU.

NOTE

Input modules are not currently available for the

LIOU.

ENCLOSURE

The LIOU must be located in a controlled non-

hazardous area and must be mounted in a suitablemetallic nationally recognized test laboratory (NRTL)labeled NEMA rated enclosure.

FAULT LED AND RESET SWITCH

Each card in the LIOU is furnished with a yellow fault

LED and a Reset switch. During Normal operation, the

LED is off. The yellow LED turns on when the Resetbutton is pressed or a fault occurs. Pressing the Reset

button resets the microprocessor on the card, causing itto re-initialize. At this time, the Trouble light on the LCU

is also turned on.

If the Reset button is pressed with an output energized,the output is de-energized until the event that triggeredthe output re-occurs. (Outputs are “event driven.”)

The yellow LED also turns on if:

– An output fault occurs (signal audible and agent

release modules only). The LED is reset automaticallywhen the fault clears.

– A microprocessor fault occurs.

– The card is not configured.

– A loss of communication with the LCU occurs (RS-

485). If an output is on during a loss ofcommunication, the output will remain in the currentstate and can only be reset using the reset switch on

the Logic Controller.

RELAY MODULE

FEATURES

• Four independently programmable relays

• SPDT dry contacts

• Supervised module

DESCRIPTION

The relay module is a convenient and economical

means of providing “unsupervised” output capability forthe Eagle Quantum System. The module is located inthe LIOU and provides four independently

programmable relays for control of auxiliary functionssuch as fan shutdown and damper control. Each relay

has SPDT contacts, rated 2 amperes at 30 vdc.

The connection of the relay module to the system issupervised by the LCU. In the event of module removal,the system will display a trouble condition at the LCU.

The relay module is housed and secured in the LIOU. A

maximum of 8 relay modules can be installed in thesystem.

NOTE It is not recommended to configure relay outputs

as Normally Energized/Open on Alarm.

III-1 95-8470

Page 17: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 17/128

III-2

RELEASE MODULE

FEATURES

• One programmable releasing output

• Three independently programmable signal circuitoutputs (style “Y” wiring)

• FM200, FE-13, CO2, Halon, water mist, dry and wet

chemical compatible, deluge and pre-action• Programmable for initiators or solenoid type releasing

devices for 90 sec., 10 min., 15 min., continuous.

DESCRIPTION

The release module is a convenient and economicalmeans of providing signaling and agent releasecapability for the Eagle Quantum System. The release

module is located in the LIOU and provides oneprogrammable release circuit and three Style “Y”

signaling circuits. The release circuit is compatible with

all solenoid or initiator based Fenwal suppressionsystems.

Used in conjunction with the Eagle Quantum’s

programmable logic, each release circuit can beprogrammed for “Single,” “Cross” or “Counting” Zone

Style initiation. Optional time delay, abort and manualrelease sequences allow the output to be programmed

for use in unique applications.

Each signal circuit delivers up to 2 amperes at 24 vdc— enough to meet the power requirements of today’s

ADA/UL 1971 Signaling Appliances. The three signaloutputs are individually programmable to allowsignaling of each phase of the release sequence.

The agent release output circuit is rated for 24 vdc

control devices. Each release output can supervise andactivate up to two solenoid control heads. Tables III-1

and III-2 identify the devices that can be controlled bythe releasing output. Refer to Section VII for specificwiring information.

Each circuit on the release module is furnished with a

self-restoring fuse to provide protection from shortcircuit conditions. The three signaling circuits are

supervised for open and short circuit conditions. Therelease circuit is supervised for open circuit conditions.If a trouble condition occurs, it will be indicated at the

LCU.

The connection of the release module to the system is

supervised by the LCU. In the event of module removal,the system will display a trouble condition at the LCU.

The release module is housed and secured in the LIOU.A maximum of 8 release modules can be installed in thesystem.

Manufacturer Model

Skinner LV2LBX25

ASCO 8210A107

ASCO 8210G207

Skinner 73218BN4UNLVNOC111C2

Skinner 73212BN4TNLVNOC322C2

Skinner 71395SN2ENJ1NOH111C2

T0037B

Table III-2—Solenoid Compatibility with Release Module for Delugeand Pre-Action Applications

Table III–1—Solenoid Compatibility with Release Module forReleasing Applications

Solenoids

Fenwal part no. 486500-001

Fenwal part no. 890181

Fenwal part no. 897494

Fenwal part no. 899175

Fenwal part no. 895630-000

Fenwal part no. 31-199932-004

Page 18: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 18/128

SIGNAL AUDIBLE MODULE

FEATURES

• Four independently programmable indicating circuits

• NFPA Style “Y” or “Z” wiring

• 24 vdc power limited outputs

• Self-restoring output design

• Four optional coded outputs per circuit.

DESCRIPTION

The signal audible module provides four indicatingcircuits for controlling UL Listed 24 vdc polarized

audible/visual indicating appliances. Each outputcircuit is independently programmable to allow

annunciation of separate events.

The outputs are UL Listed for power limited

applications. The advanced circuitry design usesresettable fuses, eliminating the need to replace

modules or components if the circuits are shorted oroverloaded. As a result, downtime and maintenance

costs are reduced.

The signal audible module can support four NFPA Style

“Y” or two Style “Z” field wiring circuits. Each outputcircuit is supervised for open and short circuit

conditions. The outputs operate in the reverse polarityfashion when activated. Each output delivers up to 2

amperes at 24 vdc — enough to meet the powerrequirements of today’s ADA/UL 1971 signaling

appliances.

The Signal Audible Module is located in the LIOU and issupervised by the LCU. In the event of module removal,

the system displays a trouble condition at the LCU.

The Eagle Quantum system supports up to eight signal

audible modules, providing a maximum of 32 signaloutputs per system. Each module provides auxiliary

input terminals for additional 24 vdc signaling powerwhere required. All four module outputs are

synchronized for accurate activation of visual signalingappliances.

The signal outputs are programmable for activation bythe Eagle Quantum’s Logic Controller. Time delay and

stepped signaling functions can also beaccommodated. In release applications, signal outputs

can be programmed to provide pre-release, releaseand post-release signaling.

Each circuit is individually programmable for any one ofthe following coded outputs:

1. Continuous sounding

2. 60 Beats per minute

3. 120 Beats per minute

4. Temporal pattern.

The signal audible module is housed and secured in the

LIOU. A maximum of eight signal audible modules canbe installed in the system.

III-3 95-8470

Page 19: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 19/128

IV-1 95-8470

Section IVAddressable Field Devices

EQ2200IDC SERIES

INITIATING DEVICE CIRCUIT (IDC)

DESCRIPTION

Three IDC models are available:

The EQ2200IDC allows discrete inputs from smoke/heat

detectors, manual call stations or other contact devices.

The EQ2200IDCGF Initiating Device Circuit GroundFault Monitor responds to the presence of a ground fault

within the power circuitry of the Eagle Quantum system.It provides a supervised dry contact input and groundfault monitoring circuitry for indicating a power supply

trouble condition. It is intended for use with a third partypower supply.

The EQ2200IDCSC Initiating Device Circuit Short Circuit(IDCSC) provides two supervised digital inputs formonitoring the system for shorts circuits. The IDCSC

supports ANSI/NFPA 72 Class B Style C (3 state,open/short circuit) supervised input circuits.

Inputs

Each IDC accepts two dry contact inputs for use withdevices such as relays, pushbuttons, key switches, etc.

The IDC supports ANSI/NFPA 72 Class B Style Bsupervised input circuits (Class B Style C for IDCSC).

Each circuit requires its own end of line (EOL) resistorfor monitoring circuit continuity. Nominal resistance of

the resistor is 10 k ohms.

Inputs are software selectable in EagleVision NT toactuate the alarm, trouble, or supervisory relays on theLCU.

Outputs

The output of the device is a status message that is sent

to the gateway and logic controller in the Local ControlUnit along the LON/SLC. System response to the

message is determined at the time of configuration. TheIDC supports ANSI/NFPA 72 Class A, Style 7communication with the LCU.

A Standard Periodic Report (SPR) is sent to the gateway

at the rate determined at the time of configuration.When programmed for response to a fire alarmcondition, a special Acknowledged Exception Report

(AER) is immediately sent to the Logic Controller.

Addressability

Device identification is accomplished by setting

switches on an eight position DIP switch (valid addressrange is 5 to 250).

Status LEDs

Three LEDs are located at the center of the

communication module circuit board and are visiblewhen the cover is removed.

The green LED serves as a power-on indicator and isthe only LED illuminated during normal operation (nofaults or alarms occurring).

The red LED is used to indicate an alarm or fault

condition. The flashing rate of the red LED indicates thefollowing conditions:

On steady = one of the inputs is activeBlinking = fault condition such as an open input

circuit or not configured.

The amber LED is provided for factory diagnosticpurposes and is not used by the customer. Illumination

of the amber LED normally indicates a failure in thecommunication chip. Replacement of the communicationmodule circuit board is required.

Alarm Log

The module tracks when either of its input circuits are

activated and will store these changes in non-volatilememory. The time, date, and circuit number is stored

for the last eight events.

Enclosure

The explosion-proof, water-tight NEMA/Type 4X

enclosure is designed for use in a variety of hazardouslocations.

EQ2200UV UV FLAME DETECTOR

DESCRIPTION

The EQ2200UV Series UV Flame Detector contains a UVsensor module and control circuitry in an explosion-proof, watertight enclosure. The detector is equippedwith both automatic and manual optical integrity (oi) test

capability.

Detector status is indicated by red LEDs visible throughthe detector’s viewing window. Table IV-1 indicates the

condition of the LEDs for each detector status.

Page 20: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 20/128

IV-2

Output

The output of the device is a status message that is sent

to the gateway and logic controller in the Local ControlUnit along the communication loop. System response

to the message is determined at the time ofconfiguration. The UV detector supports ANSI/NFPA 72Class A, Style 7 communication with the LCU.

A Standard Periodic Report (SPR) is sent to the gateway

at the rate determined at the time of configuration.When programmed for response to a fire alarm

condition, a special Acknowledged Exception Report(AER) is immediately sent to the Logic Controller.

Addressability

Device identification is accomplished by settingswitches on an eight position DIP switch (valid address

range is 5 to 250).

Alarm Log

Each detector maintains an alarm log in non-volatile

memory. The time and date for the last eight alarms arelogged.

Terminal Wiring Board

All external wiring is connected to screw terminalconnectors on the terminal wiring board located inside

the detector housing.

Enclosure

The explosion-proof NEMA/Type 4X enclosure isdesigned for use in a variety of hazardous locations.

SOFTWARE SELECTABLE OPTIONS

The following software selectable options are availablethrough a PC running Det-Tronics configuration

software.

Operating Mode

The operating mode determines the type of logic that

the UV flame detector will use for processing fire signals(either standard or arc rejection).

ARC REJECTION MODE

The arc rejection mode (recommended) enables thedetector to prevent nuisance fire alarms caused by UV

from short-duration electrical arcs or electrostaticdischarge, while maintaining the ability to reliably detect

the UV given off by a flame. The arc rejection mode isnot recommended unless these false alarm sources arepresent within the application to be protected. Typical

applications that benefit from arc rejection logic includeelectrostatic coating processes and uncontrolled

environments where transient UV sources can bepresent, such as many typical outdoor applications.

STANDARD MODE

In the standard processing mode, the detector output(measured in counts per second) is compared to the

fire threshold (the “sensitivity” setting as describedbelow). If the radiant energy level from the fire exceeds

the selected alarm threshold level, the time delaybegins (if a time delay is selected). If the radiant energy

level from the fire remains above the selected sensitivitylevel for the duration of the time delay, the fire alarmoutput is activated. In every application, it is crucial to

ensure that the radiant ultraviolet energy level from theexpected fire at the required distance from the detector

will exceed the selected sensitivity level.

Standard signal processing is recommended forcontrolled indoor applications only.

The arc rejection algorithm examines the radiant energylevel detected within a specified unit of time (timed

gate). Detector output is determined by three variables:— sensitivity level

— gate length— number of consecutive gates required.

T0005A

Status LEDs

Normal with automatic oi selected Blink every 5 seconds

Normal with manual oi selected Blink every 10 seconds

Fault (General) Off

Power supply fault Off

oi fault Off

UV being detected, but time delay not yet satisfied LEDs continue blinkingFire On

Table IV–1—EQ2200UV Detector Status/Indications

Page 21: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 21/128

IV-3 95-8470

Different combinations of these variables allow forvarious levels of transient arc rejection capability. There

are four arc rejection levels (very high, high, medium,and low) that are selectable for each detector throughthe PC. Refer to Table IV-2.

The proper arc rejection setting for a given application

must be determined through testing. For indoorapplications with known electrostatic energy fields

within 15 feet of the detector, an arc rejection setting of“very high” or “high” is typical. For outdoorapplications, “medium” or “low” arc rejection settings

are typical.

It is recommended that each detector be thoroughlytested at the programmed arc rejection setting within

the ambient conditions that will be present duringnormal operation. This will help to ensure that theselected arc rejection setting is proper for the

application.

Sensitivity

Whether the Standard or Arc Rejection mode isselected, the sensitivity setting must always be

programmed. The selected sensitivity level determinesthe fire alarm threshold setpoint. The higher thesensitivity level, the greater the detection range, but the

possibility of false alarms will be increased. Foursensitivity levels are selectable. Refer to Table IV-3.

The sensitivity setting must be appropriate for the

anticipated fire size at the required distance from thedetector.

Time Delay

Arc rejection mode — If the fire signal meets the

programmed arc rejection requirements, the time delaybegins. A fire output is generated if the fire signal

continues for the duration of the time delay.

Standard mode — A fire output is generated only if the

fire signal exceeds the sensitivity setting for the entire

duration of the programmed time delay.

Automatic or Manual oi

The oi system uses an internally generated UV testsignal to determine the relative condition of the detector

and its optical surfaces.

If automatic oi testing is selected, the oi test isautomatically performed once every minute. The

automatic oi test does not generate an alarm output orinterfere with normal detector operation.

The manual oi test is initiated using a button on thepoint display screen at the PC. The manual oi test can

be used in addition to automatic oi to verify correctsystem operation.

Fire Output Latching

When latching operation is selected, the fire alarmsignal is cleared by removing input power for a

minimum of 0.1 second.

Arc Rejection Level Consecutive Gates Gate Length Sensitivity* Min. Processing Time

Very High 8 1/16 Second Very High (8 CPS) 0.5 Second

High 4 1/16 Second Very High (8 CPS) 0.25 Second

Medium 4 1/8 Second Very High (8 CPS) 0.5 Second

Low 4 1/4 Second Very High (8 CPS) 1.0 Second

T0006A* CPS = counts er second

Table IV–2—Arc Rejection Levels for UV Detector

Sensitivity Level Equivalents

Sensitivity Level Selected Nominal Fire Alarm Threshold

In Counts per Second (CPS)

Very High 8

High 24

Medium 48

Low 96

T0007A

Table IV–3—Sensitivity Levels for UV Detector

Page 22: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 22/128

Fault Latching

If the fault output is set for latching, the fault will not

clear until it is corrected and the unit is reset. If a fireoccurs, the unit will indicate a fire, over-riding the fault

condition, i.e., the fault signal will clear if not latched. Ifa fault is stil l present after the fire has beenextinguished, the unit will again indicate a fault until the

problem has been corrected and the unit is reset.

EQ2200UVHT HIGH TEMPERATUREUV FLAME DETECTOR

DESCRIPTION

The EQ2200UVHT UV Flame Detector provides UV

flame protection in continuous duty high temperatureapplications, such as turbine compartments,

enclosures, generator rooms, etc. where ambienttemperatures can continuously exceed +75°C (+167°F).

The EQ2200UVHT is an electronic module assemblythat is used in conjunction with a high temperature rated

C7050B UV detector (with DE1888K3 high temperaturerated UV sensor tube). The two devices are mounted in

separate explosion-proof, watertight enclosures.

The UV detector is rated for continuous duty in

environments up to +125°C (+257°F). The electronic

module is rated up to +75°C (+167°F).

NOTE

The electronic module cannot be located in the high temperature area.

The UV detector and electronic module assembly canbe separated up to 165 feet (50 meters) using high

temperature rated 4 core shielded cable.

NOTE In accordance with NFPA 72, the maximum separation distance is 20 feet (6 meters) using

conduit or equivalent protection against mechanical damage.

LED

Detector status is indicated by a red LED that is visible

through the viewing window on the cover of theelectronic module junction box.

Refer to the “EQ2200UV UV Flame Detector” sectionabove for a description of features, operating

characteristics and software selectable options of Det-Tronics Eagle Quantum UV detectors.

EQ2200UVIR FLAME DETECTOR

DESCRIPTION

The EQ2200UVIR Series Flame Detector is designed toprovide reliable fire protection in applications where the

use of either ultraviolet (UV) or infrared (IR) detectorsalone can result in false alarms. When used alone, a UV

detector can respond to sources of ultraviolet radiation

besides fire, such as lightning, x-rays or arc welding.Likewise, an IR detector can respond to various hotobjects, such as flickering or chopped radiation from

electric heaters or exhaust manifolds. Themicroprocessor based EQ2200UVIR combines both aUV and a single frequency IR sensor in a single

detector and requires simultaneous response of bothsensors to generate a fire alarm. These two detecting

elements monitor different portions of the radiationspectrum and have virtually no common sources of

false alarms. This enables the detector to respond to areal fire while ignoring potential false alarm sourcessuch as arc welding, x-rays, or hot vibrating objects.

Microprocessor based circuitry located inside the

detector junction box continuously monitors the twosensors, evaluating the signal(s) with fire and fault

algorithms to determine the current status of thedetector. When both sensors simultaneously detect thepresence of fire, the microprocessor generates a fire

signal, which is immediately sent over the LON/SLC tothe logic controller in the Local Control Unit (LCU). The

LEDs, visible through the UV sensor viewing window,are also immediately il luminated. In addition, a

watchdog timer assures that the detector’s operatingprogram is running properly.

Detector Output

The output of the device is a status message that is sentto the gateway and logic controller in the LCU along thecommunication loop. System response to the message

is determined at the time of configuration. The detectorsupports ANSI/NFPA 72 Class A, Style 7 communication

with the LCU.

Status Conditions

Detector status conditions include normal operation,fire, fault, UV only, and IR only. A fire alarm signal isgenerated when both UV and IR sensors are active.

The fire alarm status has the highest priority and willoverride a fault condition.

IV-4

Page 23: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 23/128

Addressability

Device identification is accomplished by setting rocker

switches on an eight position DIP switch (valid addressrange is 5 to 250).

Alarm Log

Each detector maintains an alarm log in non-volatile

memory. The time and date for the last 8 alarms arelogged.

Enclosure

The explosion-proof NEMA/Type 4X enclosure is

available in either aluminum or stainless steel and isdesigned for use in a variety of hazardous locations.

LEDs

Detector status is indicated by a pair of red LEDs(illuminated simultaneously) that are visible through the

viewing window of the UV sensor.

Table IV-4 indicates the condition of the LEDs for eachdetector status.

Automatic Diagnostics

The microprocessor based detector is equipped withadvanced fault detection and diagnostic capabilities.

The LED indicators on the UV sensor module providethe user with visual annunciation of the problem area.

In addition, the point display screen at the OIS providesa variety of information regarding detector status as well

as the actual UV and IR signal levels present at thedetector. Refer to Table IV-5 for a list of statusconditions.

SOFTWARE SELECTABLE OPTIONS

The following options are selectable through a PC

running Det-Tronics configuration software:

Processing Mode

The UV portion of the detector offers a choice of two

different types of logic that can be used for processing

fire signals — either standard or arc rejection.

ARC REJECTION MODE

The arc rejection mode (recommended) enables thedetector to prevent nuisance fire alarms caused by

short-duration electrical arcs or electrostatic discharge,while maintaining the ability to reliably detect a flame.

The arc rejection mode is not recommended unlessthese false alarm sources are present within the

application to be protected. Typical applications thatbenefit from arc rejection logic include any uncontrolledenvironments where transient radiation sources can be

present, such as many typical outdoor applications.

The arc rejection algorithm examines the radiant energylevel detected within a specified unit of time (timed

gate). The output of the detector is determined by threevariables:— sensitivity level

— gate length— number of consecutive gates required.

Different combinations of these variables allow for

various levels of transient arc rejection capability. Thereare two arc rejection levels (medium and high) that are

selectable for the detector through the OIS. The properarc rejection setting for a given application must bedetermined through testing.

IV-5 95-8470

Detector Status LED

Fault Off

Automatic oi On for 0.25 second every 5 seconds

Manual oi On for 0.25 second every 10 seconds

UV only On for 50 mill iseconds — off for 500 milliseconds

IR only On for 200 milliseconds — off for 500 milliseconds

Alarm On steady

T0030

Table IV–4—EQ2200UVIR Detector Status/Indications

Page 24: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 24/128

IV-6

Status Indication Possible Cause

Low Voltage Power supply.Detector power wiring.

COM 1 LON wiring on COM 1 side of detector.Detector communication circuitry problem.

COM 2 LON wiring on COM 2 side of detector.Detector communication circuitry problem.

IR Alarm IR radiation source within view of detector.

UV Alarm UV radiation source within view of detector.

Not communicating Power supply or power wiring problem.LON wiring problem.Detector communication circuitry problem.Wrong DIP switch address setting.

Inhibit active Inhibit activated at OIS.

Unable to configure Configuration problem. Repeat configuration.

Invalid Configuration Configuration problem. Repeat configuration.

UV fault Defect in UV module. (See extended status.)

IR fault Defect in IR module. (See extended status.)

Power-up Detector in power-up time delay.Solution: Wait for detector to exit delay. Replace detector.

Auto configuration fault Configuration problem. Repeat configuration.

General fault Power supply failure.Power or LON wiring problem.Electronic failure in detector.

Fire alarm UV and IR radiation detected.

UV oi fault UV viewing window or oi ring dirty.UV oi ring missing.

UV tube missing Module missing. Install module.Dirty or broken contacts on module.

UV 290 volt fault Internal power problem. Replace detector terminal board.

IR oi fault IR viewing window or oi ring dirty.IR oi ring missing.

IR missing module Module missing. Install module.Dirty or broken contacts on module.

T0031B

Table IV–5—Status Conditions of UV/IR Detector

Page 25: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 25/128

It is recommended that each detector be thoroughlytested at the programmed arc rejection setting within

the ambient conditions that will be present duringnormal operation. This will help to ensure that theselected arc rejection setting is proper for the

application.

STANDARD MODE

In the standard processing mode, the UV sensor output(measured in counts per second) is compared to thefire threshold (the “sensitivity” setting as described

below). If the radiant energy level from the fire exceedsthe selected alarm threshold level, the time delay

begins (if a time delay is selected). If the radiant energylevel from the fire remains above the selected sensitivity

level for the duration of the time delay, a fire alarmsignal is generated. In every application, it is crucial toensure that the radiant energy level from the expected

fire at the required distance from the detector willexceed the selected sensitivity level.

Standard signal processing is recommended forcontrolled indoor applications only.

Sensitivity

Whether Arc Rejection or Standard mode is selected,

the sensitivity setting must always be programmed. Theselected sensitivity level determines the fire alarm

threshold setpoint. The higher the sensitivity level, thegreater the detection range, but the possibility of false

alarms will be increased. Four sensitivity levels areselectable. (Sensitivity levels for UV and IR are selectedseparately.)

The sensitivity setting must be appropriate for the

anticipated fire size at the required distance from thedetector. Refer to the “Specifications” section of this

manual for additional information.

Time Delay

A time delay from 0 to 7 seconds is selectable.

STANDARD MODE

A fire output is generated only if the fire signal exceedsthe sensitivity setting for the entire duration of the

programmed time delay.

ARC REJECTION MODE

If the fire signal meets the programmed arc rejectionrequirements, the time delay begins. A fire output isgenerated if the fire signal continues for the duration of

the time delay.

Automatic or Manual oi

The EQ2200UVIR is equipped with the Optical Integrity(oi) feature. The oi test is performed on both the UV

and IR sensors to check the cleanliness of the detectoroptics, as well as the proper functioning of the sensors

and electronic components of the detector. If aproblem should occur, it is quickly detected.

The detector is user programmable (from a PC runningDet-Tronics configuration software) for automatic oi

testing. If automatic testing is selected, the oi test isautomatically performed on each sensor. The rate for

the UV sensor test is once per minute. The rate for theIR sensor is field selectable from once a minute to onceevery four hours. If a fault is detected, a trouble signal

is sent to the LCU over the LON/SLC. A fault conditionis indicated at the logic controller and the gateway and

also by the LEDs on the detector’s UV sensor. Theautomatic oi test does not generate an alarm output or

interfere with normal detector operation.

The manual oi test is initiated using a button on thepoint display screen at the OIS. A successful test issignaled by the OIS. The manual oi test can be used in

addition to automatic oi to verify correct detectoroperation.

NOTE The manual oi test does not generate an alarm

output or actuate any system outputs.

Fire Output Latching

When latching operation is selected, the fire alarm

signal is present until cleared by a reset command fromthe PC.

EQ2200DCU AND EQ2200DCUEX

DIGITAL COMMUNICATION UNIT

DESCRIPTION

The EQ2200 Series Digital Communication Unit (DCU)digitizes a 4 to 20 ma analog signal and transmits the

value as the process variable portion of its Standard

Periodic Report (SPR) to the Communication Gatewaylocated in the LCU. All circuitry is housed in a single

explosion-proof/watertight enclosure for use in the areaof detection.

Designed for use with the Eagle Quantum system, the

DCU provides a unique technique for detecting andisolating opens or shorts in the Local OperatingNetwork/Signaling Line Circuit (LON/SLC) wiring. This

IV-7 95-8470

Page 26: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 26/128

fault isolation method allows for communication integrityin the event of a single wiring fault in the LON/SLC

wiring.

The DCU is approved for use with a variety of Detector

Electronics sensors including catalytic combustible gassensors, the PointWatch IR gas detector, as well as

electrochemical sensors (hydrogen sulfide, carbonmonoxide, chlorine, sulfur dioxide, and nitrogen

dioxide). It will also accept any sensor with a linear 4 to20 ma output signal and allows for one person non-intrusive calibration.

Inputs

The DCU features one 4 to 20 ma non-isolated input,

with an input impedance of 200 ohms in series with aprotection diode. (When used with a Det-Tronicscatalytic combustible gas sensor, a separate transmitter

board converts the millivolt output to a 4 to 20 masignal.) The DCU also monitors its 24 vdc supply

voltage and reports to the PC when requested.

Output

The Standard Periodic Report (SPR) is sent to thegateway at the rate determined at the time ofconfiguration (from one to ten seconds).

Calibration

A magnetic reed switch, located on the terminal board,

enables calibration of the sensor without opening theenclosure. The switch is activated by placing acalibration magnet at a specified location on the side of

the enclosure. Once the calibration mode has beenentered, the DCU steps the user through the process.

For details, refer to the “Calibration” section of thismanual.

Addressability

Device identification is accomplished by settingswitches on an eight position DIP switch (valid address

range is 5 to 250).

Status LEDs

Three LEDs are located at the center of the

communication module circuit board and are visiblethrough the window on the enclosure cover.

The green LED serves as a power-on indicator and is

illuminated whenever power is applied. During normaloperation, only the green LED is illuminated.

The red LED is used to indicate a calibration, power-up,fault or alarm condition. The flashing rate of the red

LED indicates the following conditions:

Power-up = Pulsed at a 0.5 Hz rateCalibration = Pulsed at a 1 Hz rate or on steady

Fault = Pulsed at a 4 Hz rateAlarm = Illuminated continuously.

NOTE If the communication module has not been configured, the red LED blinks at the 4 Hz rate.

The amber LED is provided for factory diagnosticpurposes and is not used in the system. Illumination ofthe amber LED normally indicates a failure in the

communication chip. Replacement of thecommunication module circuit board is required.

Calibration Log

The DCU keeps a calibration log in non-volatile memory

that can be used by the operator to evaluate theremaining life of some sensors. This log includes thezero, span, date and time for each successful

calibration. An aborted calibration is indicated by zerosin the zero and span values. The calibration log iscleared when the sensor replacement switch is pressed

and the calibration is successfully completed.

The initial calibration is logged in position one, where itremains for the life of the sensor. If more than 8

calibrations are performed without the sensorreplacement switch being pressed, the newest

calibration data will replace the second oldest so thatthe initial calibration data can be saved. The oldcalibration data will be lost. This feature enables sensor

sensitivity trending to aid in maintenance ortroubleshooting.

The analog value for the sensor is represented in raw

analog to digital counts 0 to 4095, where 0 represents 0ma and 4095 represents 24 ma.

Alarm Log

A log of low and high alarms is stored in each DCU.

Time, date and alarm type are logged for each alarmevent. A maximum of eight events can be stored. Ifmore than eight events are logged, the oldest event willbe overwritten.

IV-8

Page 27: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 27/128

Enclosure

The explosion-proof, watertight NEMA/Type 4X

enclosure is designed for use in a variety of hazardouslocations. The cover is furnished with a window to allow

the operator to view the three status indicator LEDs onthe communication module PC board.

Terminal Wiring Board

All external wiring is connected to screw terminalconnectors on the terminal wiring board located inside

the junction box.

EQ2500ARM AGENT RELEASEMODULE

DESCRIPTION

The EQ2500ARM Series Agent Release Module (ARM)is located on the LON/SLC and provides agent releasecapability for the Eagle Quantum system. The device is

controlled by programmable logic in the LogicController and can be programmed for “Single,” “Cross”

or “Counting” Zone Style initiation. Optional time delay,abort and manual release sequences allow the output to

be programmed for use in unique applications.

The Agent Release Module can monitor and control two

output devices (rated for 24 vdc), which areprogrammed and energized together. The release

circuits are compatible with a variety of solenoid orinitiator (squib) based suppression systems.

The release circuit is supervised for open circuit

conditions. If a trouble condition occurs (open circuit orsolenoid supply voltage less than 19 volts), it will beindicated at the LCU.

Each output is rated at 2 amperes. Auxiliary inputterminals are provided for additional 24 vdc output

power where needed.

Solenoids/Initiators

The releasing output devices listed in Table IV-6 are

recommended for use with the Agent Release Module.

The solenoids listed in Table IV-7 are compatible withthe Agent Release Module for deluge and pre-actionapplications.

Addressability

Device identification is accomplished by setting

switches on an eight position DIP switch (valid addressrange is 5 to 250).

Status LEDs

Three LEDs located at the center of the circuit board

provide a visual indication of device status conditions.

Green — On steady when power is applied to the

device.

Red — Blinking at a 4 Hz rate with the LED on 50%,

off 50% of the time indicates a local troublecondition such as an open output circuit or

low solenoid supply voltage.

Blinking at a 1 Hz rate with the LED on 5%,

off 95% of the time indicates an isolatecondition.

Blinking at a 1 Hz rate with the LED on 95%,off 5% of the time indicates release and

isolate.

Yellow — On indicates a malfunction in the electroniccircuitry. Replace the module.

IV-9 95-8470

Manufacturer Model

Skinner LV2LBX25

ASCO 8210A107

ASCO 8210G207

Skinner 73218BN4UNLVNOC111C2

Skinner 73212BN4TNLVNOC322C2

Skinner 71395SN2ENJ1NOH111C2

T0037B

Table IV-7—Solenoid Compatibility with Agent Release Module forDeluge and Pre-Action Applications

Manufacturer Model

Fenwal 890181(2.4 A. max., 10 Ω, momentary)

Fenwal 899175

(2.4 A. max., 10.8 Ω, momentary)

Fenwal 895630-000(2 A. max., 12 Ω, momentary)

Fenwal 897494(1.5 A. max., 15.9 Ω, continuous)

Fenwal 486500-001(240 ma max., 103 Ω, momentary)

Fenwal 31-199932-004(2.4 A. max., 10 Ω, momentary)

Table IV-6—Recommended Releasing Output Devicesfor Agent Release Module

Page 28: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 28/128

Alarm Log

Time and date are logged each time that a release

occurs. Data for the last eight events is stored in non-volatile memory.

Terminal Wiring Board

All external wiring is connected to screw terminal

connectors on the terminal wiring board located insidethe device enclosure.

EQ2500SAM SIGNAL AUDIBLEMODULE

DESCRIPTION

The EQ2500SAM Series Signal Audible Module (SAM)

provides two indicating circuits for controlling UL Listed24 vdc polarized audible/visual indicating appliances.The device is located on the LON/SLC and is controlled

by programmable logic in the Eagle Quantum’s LogicController.

Each output circuit is independently programmable to

allow annunciation of separate events. In releaseapplications, signal outputs can be programmed toprovide signaling for pre-release, release or post-

release. Each output can be individually activated forany one of the following pre-defined coded outputs:

1. Continuous until reset

2. 60 beats per minute

3. 120 beats per minute

4. Temporal pattern.

The outputs operate in the reverse polarity fashion when

activated. Each output is rated at 2 amperes. Auxiliaryinput terminals are provided for additional 24 vdc

signaling power where required.

The output circuits are supervised for open and shortcircuit conditions. If a wiring fault occurs, a troublecondition will be indicated at the LCU.

Addressability

Device identification is accomplished by setting

switches on an eight position DIP switch (valid addressrange is 5 to 250).

Status LEDs

Three LEDs located at the center of the circuit board

provide a visual indication of device status conditions.

Green — On when power is applied to the device.

Red — On steady indicates an active condition.

Blinking indicates a local trouble condition

such as an open or shorted output circuit orlow output supply voltage.

Yellow — On indicates a malfunction in the electroniccircuitry. Replace the module.

Alarm Log

Time and date are logged each time that a fire alarmoccurs. Data for the last eight events is stored in non-

volatile memory.

Terminal Wiring Board

All external wiring is connected to screw terminalconnectors on the terminal wiring board located insidethe device enclosure.

EQ2400NE NETWORK EXTENDER

DESCRIPTION

The EQ2400NE Series Network Extender expands the

capabilities of the Eagle Quantum system by allowingadditional nodes as well as additional wiring to beadded to the LON/SLC (communication loop). Without a

network extender, the communication network is limitedto 60 nodes on a 2000 meter loop. Each networkextender, however, increases the capacity of the loop

by up to 40 nodes and 2000 meters of wiring, up to amaximum of 244 field nodes and 10,000 meters of

wiring.

Network extender circuitry supports communication inboth directions. If a network wiring fault should occur,

uninterrupted communication can continue in theopposite direction.

LEDs

The network extender’s electronic module is furnishedwith three LEDs (one green and two yellow) for

indicating device status.

IV-10

Page 29: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 29/128

The green LED indicates that power is applied andflashes to indicate that messages are being transferred

over the network.

The two yellow LEDs correspond to the two

communication transceivers and are illuminated toindicate that an internal fault has been detected.

Enclosure

The network extender’s electronic circuitry is mountedinside an explosion-proof, water-tight enclosure for

installation in hazardous locations. The enclosure isavailable with up to six 3/4 inch NPT or 25 mm conduit

entries.

GENERAL APPLICATION INFORMATION

System Capacity

The basic Eagle Quantum system supports a

communication loop consisting of up to 60 detection

nodes and up to 2000 meters of connecting wiring.Adding a network extender to the loop allows it to beexpanded by up to 40 nodes with an additional 2000meters of wiring. Up to 6 network extenders can be

utilized in a single system, supporting up to 244 fieldnodes and up to 10,000 meters of wiring.

To ensure optimum performance, it is important to

distribute the network extenders along the loop so thatthere are no more than 40 detection nodes or 2000

meters of wiring on either side of a network extender.See Figure IV-1.

Response Time vs. System Size

When designing a system, it is important to realize thatincreasing the number of nodes on the communication

loop can result in an increase in the amount of timerequired for a status change message from a detection

node to reach the host computer.

The gateway requires a finite length of time to processeach bit of information that is transferred along thecommunication network. As the number of nodes

increases, so does the amount of data that is being

processed as well as the time required for processingthe data. As a result, the update time for each nodeshould be increased to accommodate the extra traffic

for a large system (one second minimum for each 50nodes).

If the fastest possible communication response time isan important criteria for a large system, it is

recommended that the number of nodes on anindividual loop be kept as small as practical. Considerusing multiple loops with fewer nodes per loop rather

than one large loop.

IV-11 95-8470

LCU

60 NODE LOOP

RIGHT

RIGHT

LCU

100 NODE LOOP

NE

50 NODES 50 NODESWRONG

LCU

100 NODE LOOP

NE NE40 NODES

30 NODES30 NODES

NOTES: 1. BASIC LOOP WITHOUT A NETWORK EXTENDER

CANNOT EXCEED 60 NODES AND 2000 METERSOF WIRE.

2. NO MORE THAN 40 NODES AND 2000 METERS OFWIRE BETWEEN NETWORK EXTENDERS ORBETWEEN A NETWORK EXTENDER AND THE LCU.

3. NO MORE THAN 244 FIELD NODES AND 10,000METERS OF WIRE ON THE LOOP.

A1946

Figure IV-1—Eagle Quantum Communication Loops

Page 30: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 30/128

V-1 95-8470

Section VDetector Application

Information

UV DETECTORS

In applying any type of sensing device as a fire

detector, it is important to know of any conditions that

can prevent the device from responding to a fire, andalso to know what other sources besides fire will causethe device to respond.

WINDOWS

Glass and plexiglas windows significantly attenuate UVradiation and must not be located between the detector

and a potential flame source. If the window cannot beeliminated or the detector location changed, contact

Detector Electronics for recommendations regardingwindow materials that will not attenuate UV radiation.

OBSTRUCTIONS

For an ultraviolet detector, dust, dirt and other films, UVabsorbing gases or vapors as well as physical

obstructions must not be allowed to come between thedetector and the protected hazard (see Table V-1).

SMOKE

Smoke will absorb UV radiation, and if accumulations ofdense smoke can be expected to precede the

presence of flame, then ultraviolet detectors that areused in enclosed areas should be mounted on the wall

approximately 3 feet (1 meter) from the ceiling wherethe accumulation of smoke is reduced.

ARC WELDING

Electric arc welding is a source of intense ultravioletradiation, and care must be taken to ensure that arc

welding is not performed in the protected area withoutsecuring the fire detection system. UV radiation fromarc welding readily scatters and can deflect across

significant distances, even when direct obstructionsexist. Any open door or window can allow nuisance UV

radiation from arc welding to enter an enclosed area.

When x-rays or radioactive substances are present inthe area being protected, the UV system must bedisabled until those sources are removed.

COMMON ENVIRONMENTAL CONDITIONS

The detector is not affected by environmental conditions

such as wind, rain or extremes of temperature and

pressure. It is also insensitive to the ultravioletcomponent of solar radiation.

UV radiation generated by periodic lightning or sparksin the area can be effectively ignored by the detector

using the arc rejection feature or time delay.

UV detectors should not be positioned so that their coneof vision can scan the horizon. Rather, they should be

directed down over the designated hazardous area toreduce the likelihood of picking up UV radiation fromdistant sources.

The following is a partial list of compounds that exhibit

significant UV absorption characteristics. These are also

usually hazardous vapors. While generally of little

consequence in small amounts, these gases can restrict

UV detection if they are in the atmosphere in heavy

concentrations. It should also be determined whether or

not large amounts of these gases may be released as aresult of a fire-causing occurrence.

Acetaldehyde Methyl Methacrylate

Acetone Alpha-Methylstyrene

Acrylonitrile Naphthalene

Ethyl Acrylate Nitroethane

Methyl Acrylate Nitrobenzene

Ethanol Nitromethane

Ammonia 1-Nitropropane

Aniline 2-Nitropropane

Benzene 2-Pentanone

1,3 Butadiene Phenol

2—Butanone Phenyl Clycide Ether

Butylamine PyridineChlorobenzene Hydrogen Sulfide

1-Chloro-1-Nitropropane Styrene

Chloroprene Tetrachloroethylene

Cumene Toluene

Cyclopentadiene Trichloroethylene

O-Dichlorobenzene Vinyl Toluene

P-Dichlorobenzene Xylene

If UV-absorbing gases may be a factor in a given

application, precautionary measures should be taken.

Detectors can be placed closer to the potential hazard

area, and/or the sensitivity of the detection system can be

increased. Contact the factory for further details.

Substances such as methane, propane, butane, hexane,camphor and octane are not UV absorbing.

Absorption of infrared radiation in the range of 4.2 to 4.7

microns is not a significant problem with most organic

vapors, with the exception of those compounds that have

triple bonds such as acetylene, nitriles, silane, or

isocyanates. Carbon dioxide concentrations higher than

normally present in the atmosphere can also cause

substantial loss of fire detection sensitivity.

Table V-1—UV and IR Absorbing Gases and Vapors

Page 31: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 31/128

V-2

UV DETECTOR POSITIONING

Detectors should be positioned to provide the best

unobstructed view of the area to be protected. Thefollowing factors should be taken into consideration:

• Identify all high risk fire ignition sources.

• Be sure that enough detectors are used to adequatelycover the hazardous area.

• For fastest response time, locate the detector as closeas possible to the anticipated fire source. The central

axis of the detector’s cone of vision provides thehighest sensitivity.

• Be sure that the unit is easily accessible for cleaningand other periodic servicing.

• Particular attention should be paid to potential falsealarm sources within the cone of vision of the detector.

• For outdoor applications, the detector should beaimed downward at least 10 to 20 degrees to prevent

it from scanning the horizon. This minimizes response

to distant UV sources outside the protected area. SeeFigure 1.

• Dense fog, rain or ice will absorb UV radiation and

reduce the sensitivity of the detector.

• If smoke is expected before flame, it is recommended

that smoke or other additional detectors be used inconjunction with the UV detector.

If possible, fire tests should be conducted to verifycorrect detector positioning and coverage.

UV/IR DETECTORS

FALSE ALARM SOURCES

UV: The UV sensor is insensitive to the ultraviolet

component of solar radiation. However, it willrespond to sources of UV besides fire, such as

electric arc welding, lightning, high voltage corona,x-rays and gamma radiation.

IR: The detector has been designed to ignore steadystate infrared sources that do not have a flicker

frequency characteristic of a fire, however, it shouldbe noted that if these steady state infrared sources

are hot enough to emit adequate amounts ofinfrared radiation in the response range of the IR

sensor and if this radiation becomes interruptedfrom the view of the detector in a patterncharacteristic of a flickering flame, the IR sensor

can respond.

Any object having a temperature greater than 0°Kelvin (–273°C) emits infrared radiation. The hotter

the object, the greater the intensity of the emittedradiation. The closer the infrared source is to thedetector, the greater the potential for a false alarm.

The IR sensor can respond to IR radiation sourcesthat can meet the amplitude and flicker

requirements of the detector such as vibrating hotobjects.

Although the detector is designed to reduce false

actuations, certain combinations of ambientradiation must be avoided. For example, if IRradiation with an intensity that exceeds the fire

threshold of the IR sensor should reach the detectoras a flickering signal, and if at the same time an

electric arc welding signal also reaches thedetector, an alarm output will be generated.

NOTE Radiation generated by false alarm sources such

as periodic lightning or sparks in the area can be effectively ignored by the detector using the arc rejection feature or time delay.

Arc Welding

Electric arc welding is a source of intense ultraviolet

radiation. UV radiation from arc welding readily scattersand can deflect across significant distances, even when

direct obstructions exist. Any open door or window canallow nuisance UV radiation from arc welding to enter

an enclosed area.

CENTER AXISOF DETECTOR

FIELD OF VIEW

CENTER AXISOF DETECTORFIELD OF VIEW

INCORRECT

CORRECT

NOTE: DETECTOR MUST ALWAYS BE AIMED

DOWNWARD AT LEAST 10 TO 20 DEGREES.

B1974

Figure 1—Detector Orientation Relative to Horizon

Page 32: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 32/128

The UV/IR detector does not respond to arc weldingbeyond 10 feet from the detector. However, a UV only

signal will be generated in response to the intense UVradiation generated by the arc welding, and atdistances closer than 10 feet the heated metal from the

welding can become a false alarm source for the IRsensor.

FACTORS INHIBITING DETECTOR RESPONSE

Windows

Glass and Plexiglas windows significantly attenuateradiation and must not be located between the detector

and a potential flame source. If the window cannot beeliminated or the detector location changed, contact

Detector Electronics for recommendations regardingwindow materials that will not attenuate radiation.

Obstructions

Radiation must be able to reach the detector in order for

it to respond. Care must be taken to keep physicalobstructions out of the line of view of the detector. Inaddition, UV or IR absorbing gases or vapors must not

be allowed to accumulate between the detector and theprotected hazard. See Table V-1 for a list of thesesubstances.

Smoke

Smoke will absorb radiation. If accumulations of dense

smoke can be expected to precede the presence of aflame, then detectors that are used in enclosed areasshould be mounted on the wall approximately 3 feet (1

meter) from the ceiling where the accumulation ofsmoke is reduced.

Detector Viewing Windows

It is important to keep the detector viewing windows asfree of contaminants as possible in order to maintain

maximum sensitivity. Commonly encounteredsubstances that can significantly attenuate UV and/or IR

radiation include, but are certainly not limited to, thefollowing:

Silicones

Oils and greasesIce buildupDust and dirt buildup

Paint overspray.

UV/IR DETECTOR POSITIONING

IMPORTANT

Detectors should not be positioned so that their cone of vision can scan the horizon. Rather, they should be directed down over the designated

hazardous area to reduce the likelihood of picking up radiation from distant sources. See Figure 1.

Detectors should be located in positions best suited forcovering the area to be protected. Whenever practical,they should be placed where they will be easily

accessible for cleaning and other periodic servicing.Particular attention should also be paid to potential false

alarm sources within the cone of vision of the detector,such as distant arc welding, or the rotating blades of a

fan or surface vibration of an IR source, which couldallow a flickering IR signal to reach the detector. Rainor ice can absorb radiation, which can reduce the

capability of the detector. For outdoor applications, aimthe detector downward to minimize the buildup of water

or ice on the detector viewing windows and to prevent

the cone of vision from scanning the horizon. Thisminimizes response to distant radiation sources outsidethe protected area.

GAS DETECTOR POSITIONING

The sensor must be properly located to enable it to

provide maximum protection. The formula fordetermining the most effective number and placementof sensors varies depending on the conditions at the job

site. The individual performing the installation must relyon experience and common sense to determine the

quantity of sensors and the best sensor locations toadequately protect the area.

The following factors should be considered for everyinstallation:

1. What kind of gas is to be detected? If it is lighter

than air (acetylene, hydrogen, methane, etc.), placethe sensor above the potential source. Place the

sensor close to the floor for gases that are heavierthan air (benzene, butane, butylene, propane,hexane, pentane, etc.) or for vapors resulting from

flammable liquid spills. However, note that aircurrents can cause a gas that is heavier than air to

rise. In addition, if the gas is hotter than ambientair, it could also rise.

2. How rapidly will the gas diffuse into the air? Selecta location for the sensor as close as practical to the

anticipated source of a gas leak.

V-3 95-8470

Page 33: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 33/128

V-4

3. Ventilation characteristics of the immediate areamust also be considered. Movement of air will

cause gas to accumulate more heavily in one areathan another. The sensor should be placed in thearea where the most concentrated accumulation of

gas is anticipated. Also consider the fact that manyventilation systems do not operate continuously.

4. The sensor should be pointed down to prevent the

buildup of moisture or contaminants on the filter andto ensure proper operation. For PointWatch, refer toinstruction manual 95-8440.

5. The sensor must be accessible for testing and

calibration. The use of the Sensor Separation Kitwill be required in some installations.

6. Catalytic sensors should be located where they aresafe from potential sources of contamination that

can poison the sensing element.

7. Exposure to excessive heat or vibration can result in

premature failure of any electronic device andshould be avoided if possible. Shielding the devicefrom intense sunlight will reduce solar heating and

can increase the life of the unit.

For additional information on determining quantity and

placement for sensors in a specific application, refer toInstrument Society of America (ISA) Transaction Volume

20, Number 2, titled “The Use of Combustible Detectorsin Protecting Facilities from Flammable Hazards.”

CATALYTIC GAS SENSORS

CAUTION Exposure to a high level of gas can have an

adverse effect on the sensitivity of catalytic sensing elements. If the level of gas at the sensor should

reach 100% LFL, it is important that it be tested and recalibrated if required. In some cases, it may

be necessary to replace the sensor.

If an over-range condition should occur, the user

must exercise caution, since a highly explosive condition could exist. The hazardous area should

be checked with a portable detection instrument to determine the actual level of combustible gas

present.

For best calibration results, allow a new sensor tooperate for several hours to ensure a stable output

before performing calibration. For the highest degree ofaccuracy, perform a second calibration after 24 hours.

When a sensor is exposed to a different or newenvironment, calibration should be checked frequently

to determine the proper interval between periodiccalibrations.

Before performing calibration, the operator shouldexamine the sensor filter (flame arrester) to be sure that

it is not missing or damaged. If the filter is defective ormissing, it must be replaced. In some cases, an

exposed sensing element can act as an ignition source.It should also be noted that a dirty cover cansignificantly reduce the sensitivity of the sensor.

CATALYTIC SENSOR OPERATION

The sensing element used in the combustible gas

sensor consists of a pair of elements. One is an activecatalytic sensing element, and the other is inactive andacts as a temperature compensating reference element.

Both elements are composed of a wire coil encased inceramic. The active element has a catalytic coating

applied to its surface, however, the reference element is

glazed so that it does not react to the presence of acombustible gas/air mixture. The pair is computermatched to have the same electrical resistance.

In the presence of a combustible gas/air mixture, theresistance of the active sensing element increases in

proportion to the concentration of gas at the sensor.The change in resistance of the active sensing element,

relative to that of the reference element, is used todetermine the actual level of combustible gas present at

the sensor.

Both elements operate at a high temperature and are

enclosed by a porous stainless steel cup (flamearrester). See Figure V-2. This cup allows the diffusion

of gas to and from the sensing element, but preventsthe ignition of the atmosphere outside the sensor should

the combustible gas concentration exceed its LFL.

A barrier is placed between the element pair to prevent

thermal interaction and to prevent the transfer ofcatalytic material from the active element to the surface

of the reference element.

All catalytic type sensors require oxygen to detectcombustible gases. The sensor response will decreaseif enough combustible gas displaces the normal oxygen

present in air. The sensor should not be used where theoxygen level is less than 10%. See Figure V-3.

Figure V-4 shows the response of a typical sensor to

various levels of combustible gas. Note that a reading of40% LFL will be given at 2.0% methane (40% LFL) and

Page 34: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 34/128

also at 80.0% methane, well above the upper flammablelimit of methane. Although gas levels above the upper

flammable limit will not propagate a flame, it stands toreason that somewhere between the leak and clear airthere will be a flammable mixture.

CAUTION It is possible for the display to drop to a low % LFL

reading after going into high alarm and still have an

unsafe level of combustible gas present.Therefore, precautions should be taken to ensure that the combustible gas has been cleared before

classifying the area as safe.

V-5 95-8470

ACTIVE ELEMENT REFERENCE ELEMENT

THERMAL BARRIERFLAME ARRESTER

R E D

W H T

B L K

B1124

Figure V–2—Catalytic Combustible Gas Sensor

0 905 10 15 20 30 40 50 60 70 80 100

100

90

80

70

60

50

40

30

20

10

0

CONTROLLERDISPLAYREADING

(%LFL)

PERCENT OF OXYGEN IN MIXTURE (BY VOLUME)B1126

50% LFL METHANE IN STANDARD AIR

4.5% METHANE

2.5% METHANE

90% LFL METHANE IN STANDARD AIR

Figure V–3—Effect of Oxygen Enriched and Deficient Atmosphere on the Response of a Typical Catalytic Sensor

Page 35: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 35/128

SENSITIVITY LOSS IN CATALYTIC COMBUSTIBLEGAS SENSORS

There are a variety of factors that can cause a decrease

in the sensitivity of catalytic type combustible gassensors. Interfering or contaminating substances that

can adversely affect the response of the sensor tocombustible gases are as follows:

A. Materials that can clog the pores of the sintered

metal flame arrestor and reduce the gas diffusionrate to the sensor are:

1. Dirt and oil.

A dust cover should be installed to protect the

flame arrester whenever these conditions exist.

The dust cover can be cleaned as part of routinemaintenance. This can be accomplished using

an organic solvent and an ultrasonic bath.

2. Corrosive products.

This occurs when substances such as Cl2(Chlorine) or HCl are present. A dust coverprovides some protection. The dust cover

should be replaced as part of routinemaintenance.

3. Flame arrester clogged as a result of paintingor house cleaning.

The routine maintenance procedure should

include covering the sensor with a plastic bagwhen painting or cleaning. The bag should be

removed as soon as possible when theprocedure is complete.

4. Polymer formation in the flame arrester.

This can occur where monomer vapors such as1-3 butadiene, styrene, isoprene, etc. are

present.

B. Substances that cover or tie up the active sites on

the catalytic surface of the active sensing element.

This occurs in the presence of volatile metalorganics, gases, or vapors of hydrides, and volatile

compounds containing phosphorous, boron,silicone, etc.

Examples:RTV silicone sealants

Silicone oils and greases

Tetraethyl leadPhosphineDiborane

SilaneTrimethyl chlorsilaneHydrogen fluoride

Boron trifluoridePhosphate esters

V-6

0 905 10 15 20 30 40 50 60 70 80 100

180

160

140

120

100

80

60

40

20

0

DISPLAY

READING(%LFL)

PERCENT OF METHANE (BY VOLUME)

LOWER FLAMMABLE LIMIT(100% LFL)

UPPER FLAMMABLE LIMIT

B1125

Figure V–4—Typical Response of Catalytic Sensor to All Possible Mixtures of Methane and Air

Page 36: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 36/128

C. Materials that remove the catalytic metals from theactive element of the sensor.

Some substances react with the catalytic metalforming a volatile compound. This erodes the metal

from the surface. With sufficient exposure, most orall of the metal catalyst can be removed from the

surface of the active element of the sensor.

Halogens and compounds containing halogen arematerials of this nature.

Examples:Chlorine

BromineIodine

Hydrogen Chloride, Bromide or IodideOrganic halides:

Trichloroethylene

DichlorobenzeneVinyl chloride

Freons

Halon 1301(Bromotrifluoromethane).

A brief exposure to one of these materials cantemporarily increase the sensitivity of the sensor.This results because the surface of the active

element is increased due to etching. Prolongedexposure continues the etching process until the

sensitivity of the sensor is degraded, resulting inshortened sensor life.

D. Exposure to high concentrations of combustiblegases.

Exposure of the sensor to high concentrations of

combustible gases for extended periods of timecan introduce stress to the sensing element and

seriously affect its performance. After exposure toa high concentration of combustible gas,recalibration should be performed and, if

necessary, the sensor should be replaced.

The degree of damage to the sensor is determinedby a combination of the type of contaminant, its

concentration in the atmosphere, and the length oftime the sensor is exposed. When a sensor hasbeen exposed to a contaminant or a high level of

combustible gas, it should be calibrated at the time,followed by an additional calibration a few days

later to determine whether a significant shift insensitivity has occurred.

E. A combination of accessories such as rain shieldsand dust covers is not recommended and can

result in slow response to a gas leak.

CALIBRATION GAS

Before calibrating a sensor, check the label on the

calibration gas cylinder to ensure that the correct gastype and concentration are being used. If a different

gas type is being used for calibration, refer to Det-Tronics Technical Note No. GTN01 for “K-Factor”information (Det-Tronics form number 99-1068-02).

V-7 95-8470

Page 37: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 37/128

Section VIGeneral Wiring Requirements

GENERAL INFORMATION

WARNING

Do not open any junction box or device enclosure when power is applied without first de-classifying

the hazardous area.

CAUTION Any deviation from the recommended wiring practices can compromise system operation.

Consult the factory if different wire types or methods are being considered.

NOTE

All wiring must be marked per NFPA 70 Article 760.

NOTE Specific installation requirements may differ

depending on local installation practices and compliance with third party certifications. For local

installation practices, consult the local authority having jurisdiction. For compliance with third party certifications, consult the appropriate appendix in

this manual for additional specific installation requirements.

POWER WIRING

The input voltage at the field devices must be 18 vdc

minimum to ensure proper operation of the devices.Therefore, it is important to consider both the size

(gauge) of the power wiring and the wiring distancefrom the power supply. As the wiring distanceincreases, larger diameter wire is required to maintain a

minimum of 18 vdc at the device.

Refer to Table VI-1 to determine the minimum wire sizeneeded to prevent excessive voltage drop from power

supply to device for a given current load.

To use Table VI-1, first determine the total current load

for the circuit and the maximum allowable voltage drop.Then look under the appropriate Amp Load column to

determine the minimum wire size that will not allow thevoltage drop to exceed the maximum allowable.

For example:

What wire size is required to power ten DCUs at adistance of 100 feet from the power supply, assuming a

24 VDC power supply and a minimum of 18 VDCneeded to power the DCUs?

Maximum allowable voltage drop is 6 VDC.(24 – 18 = 6)

VI-1 95-8470

AWG 1 AMP LOAD 2 AMP LOAD 3 AMP LOAD 4 AMP LOAD 5 AMP LOAD

22 3.3 6.6 9.9 13.2 16.5

20 2.1 4.1 6.2 8.3 10.4

18 1.5 3.1 4.6 6.2 7.7

16 1.0 2.0 2.9 3.9 4.9

14 0.6 1.2 1.9 2.5 3.1

12 0.4 0.8 1.2 1.5 1.9

10 0.2 0.5 0.7 1.0 1.2

8 0.2 0.3 0.5 0.6 0.8

6 0.1 0.2 0.3 0.4 0.5

4 0.1 0.1 0.2 0.2 0.31 0.0 0.1 0.1 0.1 0.2

1/0 0.0 0.0 0.1 0.1 0.1

Table VI-1—Voltage Drop Per Pair in Volts DC per 100 Feet from Power Supply to Device

NOTES: This table is for reference only and does not replace good engineering practice.Use Ohms Law when designing the power distribution system.

Voltage drop and wiring distance are proportional.Consult factory for assistance with system wiring requirements.

Page 38: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 38/128

A combustible gas DCU draws approximately 500 mAat startup, therefore, the total current load is 5 amps.

(10 units x 500 mA = 5 amps)

Refer to the 5 Amp Load column in the table. Since the

maximum allowable voltage drop is 6 volts, 16 AWG (orlarger) wire is required.

IMPORTANT

To ensure proper operation of field devices, the voltage input to the device (measured at the device) must be within the range indicated for that

device in the “Specifications” section of this manual.

NETWORK WIRING

All devices on the LON/SLC are wired in a loop that

starts and ends at the LCU. To ensure properoperation, the LON/SLC should be wired using high

speed communication grade cable. Cable meeting the

specifications listed in Table VI-2 is suitable fordistances up to 2000 meters. Any of the cable typeslisted in Table VI-3 can be used for wiring the LON/SLC

for the distances indicated. If no network extenders areused, the distances listed are for the entire loop. Ifnetwork extenders are used, the distances listed are for

the wiring length between network extenders or

between a network extender and the LCU. The use ofother cable types can degrade system operation. For

optimum fault isolation performance, the maximumLON/SLC wiring length should not exceed 1600 feet

(500 meters).

SHIELD GROUNDING

Two shield ground terminals are provided inside the

junction box of each field device and also at the LCU.Connect the shield ends to the terminals provided (not

to each other) inside the junction box.

CAUTION

Insulate the shields to prevent shorting to the device housing or to any other conductor.

VI-2

Table VI–3—Communication Loop Wiring Cable

Minimum Typical Maximum Units Condition

DC Resistance, each conductor 14 14.7 15.5 ohm/km 20 C per ASTM D 4566

DC Resistance Unbalanced 5% 20 C per ASTM D 4566

Mutual Capacitance 55.9 nF/km per ASTM D 4566

Characteristic Impedance 92 100 108 ohm 64 kHz to 1 MHz, per ASTM D 4566

Attenuation 20 kHz 1.3 dB/km 20 C per ASTM D 4566

64 kHz 1.9

78 kHz 2.2

156 kHz 3

256 kHz 4.8

512 kHz 8.1

772 kHz 11.3

1000 kHz 13.7

Propagation Delay 5.6 nsec/m 78 kHz

Length: 6,500 feet/2000 meters maximum (basic loop or between Network Extenders).Type: Single twisted pair.

Wire Gauge: 16 AWG, stranded (19 x 29), tinned copper with overall shield.Cables meeting these specifications are good for up to 2000 meters.

T0049B

Table VI-2—Specifications for LON Wiring Cable

Cable Type Maximum Length

Feet Meters

Belden 8719 6500 2000Belden 85231 6500 2000

Level IV, 22 AWG 4500 1370JY (St) 2x2x0.8 3000 900

Be sure that selected cable meets all job specifications.

If necessary, consult factory for further suggested cable types.

Page 39: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 39/128

JUNCTION BOX GROUNDING

Junction boxes should be electrically connected to

earth ground.

RS-485 LINK WIRING

The RS-485 link connecting the LCU and LIOU requires

termination at both ends. The LCU provides termination

for the beginning of the RS-485 link. All other devices,except for the device at the end of the line, shall havetheir termination resistor removed. The LIOU uses a

termination resistor that must be removed if it is not atthe end of the line.

All devices sharing a common RS-485 link must have acommon power return.

PROTECTION AGAINST MOISTURE DAMAGE

Moisture can have a detrimental effect on theperformance of electronic devices. Therefore, it is

important to take proper precautions during installationto ensure that moisture will not come in contact with the

electrical connections or components of the system.

In applications where the wiring cable is installed inconduit, the use of watertight conduit seals, drains,

breathers, or equivalent is recommended to preventdamage to electrical connections caused bycondensation within the conduit.

ELECTROSTATIC DISCHARGE

Many system electronic modules contain semiconductor

devices that are susceptible to damage by electrostaticdischarge. An electrostatic charge can build up on theskin and discharge when an object is touched.

Therefore, use caution when handling, taking care not totouch the terminals or electronic components. For more

information on proper handling, refer to Service Memoform 75-1005.

DETERMINING POWERREQUIREMENTS

Tables VI-4 and VI-5 are provided for calculating the

total current requirements for those parts of the systemrequiring battery backup.

VI-3 95-8470

Device Type Number of Devices Standby Current Total Current for Device Type

LCU 1 X 0.300 = 0.300

Release Module X 0.070 =

Signal Audible X 0.033 =

Relay Module X 0.020 =

P. S. Monitor X 0.060 =

IDC/IDCGF/IDCSC X 0.055 =

UV Detector X 0.100 =

UV/IR Detector X 0.100 =

DCUEX X 0.145 =

DCU with H2S X 0.060 =

DCU with PointWatch X 0.300 =

ARM X 0.075 =

SAM X 0.060 =

Network Extender X 0.090 =

Power Supply X 0.300 =

Other X =

TOTAL STANDBY CURRENT FOR SYSTEM (IN AMPERES) =

T0012B

Table VI–4—Standby Current Requirements at 24 vdc

Page 40: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 40/128

EQ2110PS, EQ2130PS AND EQ2175PS

Refer to Table VI-6 for Power Supply ratings.

BACKUP BATTERY

Refer to Table VI-7 or VI-8 to calculate the minimum sizeof the backup battery (in amp hours). Select a sealed

lead-acid battery with an adequate amp hour rating.

NOTE

Connect two batteries in series for 24 volts. Be sure that the battery enclosure is adequately

ventilated.

VI-4

Table VI-6—EQ21xxPS Power Supply Specifications

Device Type Number of Devices Alarm Current Total Current for Device Type

LCU 1 X 0.340 = 0.340

Release Module X 0.165 =

Signal Audible X 0.120 =

Relay Module X 0.090 =

P. S. Monitor X 0.060 =

IDC/IDCGF/IDCSC X 0.090 =

UV Detector X 0.120 =

UV/IR Detector X 0.120 =

DCUEX X 0.160 =

DCU with H2S X 0.075 =

DCU with PointWatch X 0.320 =

ARM X 0.120 =

SAM X 0.120 =

Network Extender X 0.090 =

Power Supply X 0.300 =

Other X =

Total Solenoid Load +

Total Signaling Load +

TOTAL ALARM CURRENT FOR SYSTEM (IN AMPERES) =

T0013B

Table VI–5—Alarm Current Requirements at 24 vdc

CharacteristicPower Supply

EQ2110PS EQ2130PS EQ2175PS

Input Voltage 120 vac 120/208/240 vac 120/208/240 vac

Input Current 4 Amps 11/6/6 Amps 24/15/12 Amps

Input Frequency 60 Hz 60 or 50 Hz 60 or 50 Hz

Supply Rating 10 Amps 30 Amps 75 Amps

Maximum Alarm Current 10 Amps 30 Amps 75 Amps

Maximum Standby Current 3.33 Amps 10 Amps 25 Amps

Recharge Current 6.67 Amps 20 Amps 50 Amps

Maximum Battery Capacity 100 AmpHours 300 AmpHours 750 AmpHours

Maximum Deluge Standby Current 1 Amp 3 Amps 7.5 Amps

Page 41: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 41/128

BATTERY CHARGER

Use the following formula to calculate the minimum

battery charger size:

CAUTION

Care should be taken when considering the final voltage at the device during AC power loss. With loss of AC power, the device voltage will drop over

time as the batteries lose their charge. If extended periods of AC power loss are to be expected,

either consider a heavier wire gauge than indicated in Table VI-1, or specify batteries with higher amp-

hour ratings.

VI-5 95-8470

Standby Current Standby Time* Standby Amp HoursX =

24 Hours

Alarm Current 5 Minute Alarm Time* Alarm Amp Hours

X =0.083 Hours

Sum of Standby and Alarm Amp Hours =

Multiply by 1.1 (10% Safety Factor) X

Total Battery Amp Hour Requirement

T0014A

* FM MINIMUM REQUIREMENT FOR EXTINGUISHING SYSTEMSIS 24 HOURS STANDBY TIME AND 5 MINUTES ALARM TIME.

Table VI–7—Backup Battery Requirements for Automatic Release of Extinguishing Systems Except Deluge

Standby Current Standby Time* Standby Amp HoursX =

90 Hours

Alarm Current 10 Minute Alarm Time* Alarm Amp Hours

X =0.166 Hours

Sum of Standby and Alarm Amp Hours =

Multiply by 1.1 (10% Safety Factor) X

Total Battery Amp Hour Requirement

T0040A

* FM MINIMUM REQUIREMENT FOR DELUGE SYSTEMS IS90 HOURS STANDBY TIME AND 10 MINUTES ALARM TIME.

Table VI-8—Backup Battery Requirements for Deluge and Pre-Action Applications

Minimum= Alarm Current +

Total Amp HoursCharge Rate 48

Page 42: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 42/128

Section VIISystem Wiring

NOTE Specific installation requirements may differ

depending on local installation practices and compliance with third party certifications. For local

installation practices, consult the local authority

having jurisdiction. For compliance with third party certifications, consult the appropriate appendix in

this manual for additional specific installation requirements.

EQ2100PSM POWER SUPPLYMONITOR USED WITH EQ2110PS,EQ2130PS AND EQ2175PS POWERSUPPLIES

WIRING

1. Mount the power supply monitor in a Nationally

Recognized Test Laboratory (NRTL) labeledenclosure. Refer to the “Specifications” section formounting dimensions.

NOTE

Power supplies require unrestricted air flow for

proper cooling.

2. Securely mount the cabinet. The cabinet should beelectrically connected to earth ground.

3. Connect the external wiring to the appropriate

points as described below. Refer to Figure VII-1 for

terminal block locations and Figures VII-2 and VII-3for terminal identification.

95-8470VII-1

+ +

+

++

+

+

+

+

+

+

+

+

+

++

J1: POWER AND LON WIRING LON ADDRESS SWITCHES J3: AC INPUT

TERMINAL NO. 1

YELLOW LED

RED LED

GREEN LED

TERMINAL NO. 1

TERMINAL "B"

TERMINAL "C"

J2: CURRENT TEST POINTS

TERMINAL NO. 1

SWITCH NO. 1

1

1

1

1

A1949

Figure VII-1—Location of Terminals, LEDs and Switches on the Power Supply Monitor

Page 43: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 43/128

WARNING

Do not connect or disconnect wires with power applied.

4. Connect the 24 vdc power wires and the LON

network cable to the appropriate points on J1, thePower & LON Wiring terminal block. See Figure VII-

2.

COM 1 - Communication network connect ions:Connect to COM 2 terminals of the nextdevice on the loop, A to A and B to B.

COM 2 - Communication network connect ions:

Connect to COM 1 terminals of theprevious device on the loop, A to A and B

to B.

24 VDC - Connect the "+" terminal to the positive

side of the 24 vdc power source. (Both "+"terminals are connected internally.)

Connect the "-" terminal to the negative

side of the 24 vdc power source. (Both "-"terminals are connected internally.)

Connect the shield to the designated"shield" terminal. (The two shield terminals

are connected internally.) Do not groundany shield at the monitor / powerdistribution cabinet. Insulate the shields

to prevent shorting to the device housingor any other conductor.

5. Connect a two wire cable between the AC input of

the power supply and terminals 1 and 4 on J3, theAC input terminal block on the power supplymonitor. See Figure VII-3.

6. Connect the “B” terminal on the power supply

monitor to the negative (–) side of the backupbattery. Connect a correctly sized circuit breaker or

disconnect switch in the battery circuit as shown inFigure VII-4. If a circuit breaker is used, it must berated between 150% and 250% of the total load.

7. Connect the “C” terminal on the power supply

monitor to the negative (–) side of the power supply.

8. Wire the power distribution circuit breakers to theoutput of the power supply. Circuit breaker ratings

must be between 150% and 250% of the full loadrating.

9. Check all field wiring to ensure that the properconnections have been made.

10. Set the LON address for the power supply monitor.

Refer to Figure VII-1 for rocker switch location.Refer to “LON/SLC Device Address Switch Setting”in the “Switch Setting” section (Section VIII) of the

Eagle Quantum system manual (form number 95-8470) for complete information regarding the switch

setting procedure.

11. Connect the mounting frame to chassis (earth)ground.

VII-2

1

2

3

4

5

6

7

8

9

10

A1947

11

12

SHIELD

SHIELD

SHIELD

SHIELD

A

B

A

B

+

+

COM 2

24 VDC

COM 1

Figure VII-2 —J1: Power and LON Wiring Terminal

A1950

1

2

3

4

AC INPUT 120 / 240 VAC

AC INPUT 120 / 240 VAC

NOT USED

NOT USED

Figure VII-3 —J3: AC Input Terminal

Page 44: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 44/128

STARTUP

Turn on the power supply and allow the voltage to

stabilize at 27 volts before closing the circuit to thebattery.

MEASURING BATTERY VOLTAGE ANDCHARGING CURRENT

Measure the battery voltage at terminals 3 and 4 of

terminal block J2.

To measure the battery charging current, connect a

digital voltmeter to terminals 1 and 2 of terminal blockJ2. See Figure VII-5. The voltmeter will read 1 millivolt(0.001 volt) for each 2 amperes of current.

Current in Amperes = Meter reading in millivolts x 2

Example: A reading of 50 millivolts indicates a chargingcurrent of 100 amperes.

95-8470VII-3

1

4

C

B

AC BREAKER DC BREAKER

H

N

G

+

24 VDC

OUTPUT

POWER SUPPLY MONITOR 12

11

10

9

8

7

6

5

4

3

2

1

POWER SUPPLY

– +

12 VDC

– +

12 VDC

NRTL CABINET

BATTERY

CIRCUIT

BREAKER

+ –

+

+

+

+

POWER DIST CKT #1

POWER DIST CKT #2

POWER DIST CKT #3

POWER DIST CKT #4

NOTES

1. AC INPUT SELECTABLE (THROUGH THE OIS)

FOR 120 / 208 / 240 VAC.

2. BATTERY SIZE CALCULATED BASED ON

SYSTEM LOAD.

3. CIRCUIT BREAKER RATINGS MUST BE BETWEEN

150% AND 250% OF FULL LOAD RATING.

4. REMOVAL OF TERMINAL PLUG WITH POWER

APPLIED TO TERMINALS B AND C WILL DAMAGE

THE POWER SUPPLY MONITOR.C1951

AC MONITOR

BACKUP BATTERIES

Figure VII-4 —A Typical Application — Wiring Connections for a Power Supply Monitor, Power Supply and Backup Batteries

A 952

1

2

3

4

CURRENT SENSE +

BATTERY +

CURRENT SENSE –

BATTERY –

Figure VII-5 —J2: Current Test Points

Page 45: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 45/128

Page 46: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 46/128

95-8470VII-5

Terminal 7 — System power.

When used with the standard

LCU rack (EQ2100LCU),terminals A7 and B7 are powerinput terminals for supplying

the 24 vdc power from thepower supply to the LCU.

When used with the optional

LCU rack (EQ2101LCU),terminals A7 and B7 are poweroutput terminals for supplying

isolated power with groundfault monitoring from the LCU

to the main power terminals onthe LIOU and field devices.Output current must not

exceed 2.8 amperes.

A7 terminal = (–)

B7 terminal = (+)

Terminal 8 — Ground fault monitor.

Terminal B8 (ground faultmonitor) must be connected toA8 (chassis ground) to ensure

proper functioning of theground fault monitoring

circuitry.

IMPORTANT

The chassis ground stud must be connected to earth ground.

Terminal 9 — RS-485 link.

Connect to the power supply

or LIOU rack RS485 terminals.Be sure to observe polarity:

Connect A9 terminal to the RS-485 “A” terminal of the next

device on the link. ConnectB9 terminal to the RS-485 “B”terminal of the next device on

the link.

All devices sharing a common

RS-485 link must have acommon system power return.

Terminals 10 to 12 — Three unsupervised inputsto the Logic Controller.

These inputs are typically usedfor contact inputs such asswitches, pushbuttons, relay

contacts etc. Wire thecontacts between the “A” and

“B” terminals. These inputscan be used in theprogrammable logic.

Terminal 13 — Remote reset.

Connect a normally open,

momentary closure switchbetween terminals A13 andB13 to reset the gateway

relays from a remote locationwhen the relays are

programmed for latchingoperation.

Terminals 14 to 18 — Gateway relay contacts.

Terminals A14 (NO), =B14 (COM), =

C14 (NC), = Relay K1

Terminals A15 (NO), =

B15 (COM), =C15 (NC), = Relay K2

Terminals A16 (NO), =B16 (COM), =

C16 (NC), = Relay K3

Terminals A17 (NO), =

B17 (COM), =C17 (NC), = Relay K4

Terminals A18 (NO), =B18 (COM), =

C18 (NC), = Fault relay

Terminals 19 to 22 — RS-232 serial

communication ports.

These two serial ports areelectrically isolated from each

other and from the system.

A19 = Port 2 common (COM).

Connects to “common” of theother device.

B19 = Port 2 transmit (TXD).Connects to “receive” of the

other device.

B20 = Port 2 receive (RXD).Connects to “transmit” of theother device.

Page 47: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 47/128

NOTE

Connection to Port 2 can also be made using the 9-pin (DB9) connector P7.

Pin 2 = TXD = B19

Pin 3 = RXD = B20 Pin 5 = COM = A19

WARNING

Do not plug or unplug the connector unless the

area is known to be non-hazardous.

A20 = (T+) Not used.

A21 = Port 1 common (COM).

Connects to “common” of theother device.

B21 = Port 1 transmit (TXD).Connects to “receive” of the

other device.

B22 = Port 1 receive (RXD).

Connects to “transmit” of theother device.

A22 = (R+) Not used.

Terminals 23 to 25 —LON/SLC signaling circuit

terminals, with separateshield connections.

The LON/SLC is polarity

sensitive due to ground faultmonitoring.

A23 = shield connection for COM 1

A24 = B side of signaling circuit forCOM 1

A25 = A side of signaling circuit forCOM 1

B23 = shield connection for COM 2

B24 = B side of signaling circuit forCOM 2

B25 = A side of signaling circuit forCOM 2

NOTE

B23 is connected directly to chassis ground. A23 is connected to chassis ground through a filter network.

IMPORTANT

When installing the three modules in the LCU rack,the Logic Controller must be in the left hand

position, the Gateway in the center position, and

the LON Isolator in the right hand position.

VII-6

Page 48: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 48/128

95-8470VII-7

EQ2100LIOU LOCAL OUTPUT UNIT

CAUTION

All personnel installing or servicing the LIOU must wear a grounding strap to avoid generating static electricity that can destroy or damage integrated

circuits. The circuit boards are shipped in anti- static plastic bags and should be kept in these

bags until the time of installation. If the circuit

boards are removed from the rack, they should be replaced in the appropriate bags. Never pack the boards in styrofoam or plastic pellets.

CAUTION LIOU modules must not be installed or removed in

a powered-up system. Always disconnect both AC and battery power before installing the modules.

BACKPLANE WIRING

Power and communication wiring to the LIOU is

connected to the terminal block on the LIOU backplane.

See Figure VII-7.

RS-485 LINK WIRING

The assembly is controlled and supervised by the LocalControl Unit (LCU) using an RS-485 serial

communication link. Up to four LIOU’s can becontrolled by the LCU adding a maximum of 24 output

modules to the system.

The RS-485 link connecting the LCU and LIOU requires

termination at both ends. The LCU provides terminationfor the beginning of the RS-485 link. If the LIOU is not

the last unit in the line, termination resistor R1 must beremoved. See Figure VII-7 for location.

Two sets of RS-485 terminals are provided to allowdaisy-chained wiring. “A” terminals are connected to

“A” terminals and “B” terminals to “B” terminals of thenext device on the link.

RS-485 A — Connect one terminal to “A” of

the previous device on the linkand the other terminal to “A” ofthe next device on the link.

RS-485 B — Connect one terminal to “B” of

the previous device on the linkand the other terminal to “B” of

the next device on the link.

All devices sharing a common RS-485 link must have a

common power return.

POWER WIRING

Main Power ( –) — Connect to the (–) terminal of

the system power terminals onthe EQ2101LCU (terminal A7).

CAUTION

Do not connect a breaker or other disconnect

device to power minus (–) with RS-485

connected. Doing so will damage the RS-485 circuitry.

Main Power (+): Connect to the (+) terminal ofthe system power terminals onthe EQ2101LCU (terminal B7).

Auxiliary Power Input ( –): Connect to the (–) auxiliary

terminal of the EQ2101LCU(terminal A6).

Auxiliary Power Input (+): Connect to the (+) auxiliaryterminal of the EQ2101LCU

(terminal B6).

Auxiliary Power Output: These terminals are providedJ3, J4, J5 to distribute 24 vdc auxiliary

power to the auxiliary powerterminals on the release andsignal audible modules.

Maximum total current mustnot exceed 8 amperes.

Chassis Ground: Connect to earth ground.

Module Wiring

Wiring to the external devices that are controlled by theLIOU modules is connected to the terminal strip on the

corresponding module.

P2

J3 J4 J5

P1 P3 P4 P5 P6

+

+

B

A

RS-485 TERMINATION RESISTOR

RS-485 MAIN AUX

AUX POWER

B1860

Figure VII-7 —Wiring Terminals on LIOU Backplane

Page 49: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 49/128

RELAY MODULE

WIRING

Refer to Figure VII-8 for identification of relay wiringterminals.

SWITCH SETTING

Each relay module must be assigned a unique address(1 to 8) using switch assemblies S1 and S2 on the relaymodule circuit board. See Figure VII-9 for the location

of switches on the circuit board. Refer to Table VII-1 todetermine the correct switch positions for the desiredaddress. Note that switch S1-1 is not used.

VII-8

S3

S2

S1

DS1

R E L A Y M O D U L E

MODULE ADDRESS SWITCHES

RESET SWITCH

TROUBLE LEDON

1 2

1 2

A1862

1

TB1

12

Figure VII – 9 —Location of Switches on Relay Module

Module Switch PositionAddress S1 –2 S2 –1 S2 –2

1 ON ON ON

2 ON ON OFF

3 ON OFF ON

4 ON OFF OFF

5 OFF ON ON

6 OFF ON OFF

7 OFF OFF ON

8 OFF OFF OFF

T0016A

Table VII – 1 —Switch Positions for Relay Module Addresses

K1

NOTES:

1. ALL RELAY OUTPUTS ARE SHOWN IN NORMAL STANDBY CONDITION.

2. ALL CONTACTS ARE THE DRY CONTACT TYPE.

3. OUTPUTS OF ALL RELAYS ARE NOT SUPERVISED.

4. RATINGS ARE 2A MAXIMUM AT 24 VDC; 1A AT 120 VAC.

5. THE MAXIMUM NUMBER OF BOARDS PER SYSTEM IS EIGHT.

6. THE MAXIMUM WIRE SIZE IS 12 AWG, ONE WIRE PER TERMINAL.

K2

K3

K4

1

2

3

4

5

6

7

8

9

10

11

12

B1861

Figure VII – 8 —Wiring Terminals for Relay Module

Page 50: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 50/128

95-8470VII-9

RELEASE MODULE

WIRING

Refer to Figure VII-10 for identification of wiring

terminals.

To ensure adequate operating voltage for the outputdevice, the maximum wiring length from the power

source to the output device must not exceed the valuesshown in Table VII-2 for automatic release applicationsor Table VII-3 for deluge and pre-action applications.

(For solenoids, this wire length includes both the wiringfrom the power supply to the agent release module and

the wiring from the module to the solenoid. For squibs,use only the wire length from the power supply to the

module, since the resistance of the wire from themodule to the squib is included when determining thevalue of the compensating resistor.)

JUMPERS

When the auxiliary power input is used, jumpers W1 andW2 must be cut. See Figure VII-11 for the locations ofjumpers and switches on the circuit board.

SWITCH SETTING

Each release module in the LIOU must be assigned a

unique address (1 to 8). This is accomplished usingswitches S3-2, S4-1 and S4-2 on the release module

circuit board. Refer to Table VII-4 to determine thecorrect switch positions for the desired address.

Switches S1 and S3-1 must be set for solenoid or

explosive initiator (squib). Refer to Table VII-5 for switchpositions.

RELEASE SOLENOIDS

CKT #2

CKT #3

10K EOL

10K EOL

10K EOL

1

2

3

4

5

6

7

8

9

10

11

12

+

+

+

+

+

+

RELEASE CIRCUITS

SIGNAL CIRCUITS

AUXILIARY POWER3

4

5

6

3

4

5

6

+

+

+

+

ONE SOLENOID

SOLENOID ONE

SOLENOID TWO

7

8

9

10

11

12

+

+

+

CKT #1

SIGNAL CIRCUITS

TB1 TB1

TB1

TB1

3

4

5

6

+

+

SEE NOTE 1.

INITIATOR RELEASE NOTES:1. USED TO COMPENSATE FOR 10 OHMS MAXIMUM

CIRCUIT RESISTANCE.

1. RESISTOR MUST BE RATED AT 1 WATT MINIMUM.

2. MAXIMUM NUMBER OF INITIATORS PER CIRCUIT IS 12.2. EACH CIRCUIT MUST NOT EXCEED 10 OHMS

INCLUDING CABLE RESISTANCE.

3. USE A 1200 OHM RESISTOR AS A LOAD FOR TEST PURPOSES.

4. POLARITY SHOWN IS FOR ACTIVATED CONDITION.POLARITY IS REVERSED DURING MONITORING CONDITION.

SEE NOTE 2.

B1863

SEE NOTE 3.

SEE NOTE 3.

Figure VII-10 —Wiring Terminals for Release Module

Page 51: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 51/128

Page 52: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 52/128

95-8470VII-11

SIGNAL AUDIBLE MODULE

WIRING

The signal audible module can support NFPA style Y or

style Z field wiring. Refer to Figures VII-12 through VII-15 and determine which of the wiring styles will beused. EOL resistor value is 10K ohms.

NOTE

Polarity shown is for activated condition. Polarity is reversed for monitoring condition.

To ensure adequate operating voltage for the signalingdevice, the maximum wiring length from the power

source to the output device must not exceed the valuesshown in Table VII-6. (This wire length includes both the

wiring from the power supply to the signal audible moduleand the wiring from the module to the signaling device.)

JUMPERS/SWITCHES

Note that each wiring diagram is accompanied by its

corresponding jumper/switch setting table. This tableshows the correct positions for jumper plugs W1through W8 and switches SW2-1 and SW3-2. Forjumper plugs W1 through W8, ON = jumper installed,

OFF = jumper removed.

When the auxiliary power input is used, jumpers W9 andW10 must be cut. See Figure VII-16 for the locations of

jumpers and switches on the circuit board.

ADDRESS SWITCH SETTING

Each signal audible module must be assigned a unique

address (1 to 8). This is accomplished using switchesSW2-2, SW1-1 and SW1-2 on the signal audible modulecircuit board. Refer to Table VII-7 to determine the

correct switch positions for the desired address.

10K EOL10K EOL

AUXILIARY POWER

+24VDC

RET

10K EOL

CIRCUIT 4

CIRCUIT 1

CIRCUIT 3

TB1

1

2

5

6

7

8

9

10

11

12

C1865

W1

OFF

W2

OFF

W1

OFF

W3

OFF

W4

ON

JUMPERS

W5

ON

W6

ON

W7

ON

W8

OFF

SW2 –1

OFF

SW3 –2

ON

SWITCHES

+

+

+

+

Figure VII – 12 —One Style “Z” and Two Style “Y” Circuitsfor Signal Audible Module

10K EOL10K EOL

AUXILIARY POWER

+24VDC

RET

10K EOL CIRCUIT 3

CIRCUIT 2

CIRCUIT 1

TB1

1

2

5

6

7

8

9

10

11

12

C1866

W1

OFF

W2

ON

W1

ON

W3

ON

W4

OFF

JUMPERS

W5

OFF

W6

OFF

W7

OFF

W8

ON

SW2 –1

ON

SW3 –2

OFF

SWITCHES

+

+

+

+

Figure VII – 13 —Two Style “Y” and One Style “Z” Circuitsfor Signal Audible Module

AUXILIARY POWER

+24VDC

RET

10K EOL CIRCUIT 3

10K EOL CIRCUIT 1

1

2

5

6

7

8

9

10

11

12

C1867

W1

OFF

W2

OFF

W1

OFF

W3

OFF

W4

ON

JUMPERS

W5

OFF

W6

OFF

W7

OFF

W8

ON

SW2 –1

OFF

SW3 –2

OFF

SWITCHES

+

+

+

+

Figure VII – 14 —Two Style “Z” Circuits for Signal Audible Module

10K EOL10K EOL

AUXILIARY POWER

+24VDC

RET

CIRCUIT 2

CIRCUIT 1

10K EOL10K EOL CIRCUIT 4

CIRCUIT 3

TB1

1

2

5

6

7

8

9

10

11

12

C1868

W1

OFF

W2

ON

W1

ON

W3

ON

W4

OFF

JUMPERS

W5

ON

W6

ON

W7

ON

W8

OFF

SW2 –1

ON

SW3 –2

ON

SWITCHES

+

+

+

+

Figure VII – 15 —Four Style “Y” Circuits for Signal Audible Module

Page 53: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 53/128

VII-12

W3

W1

W2

W5

W6

W7

W4

W8

1

TB1

SW1

SW2

SW3

SW4

DS1

M I C R O C O N T R O L L E R

W I T H E P R O M

W9

W10

12

MODULE ADDRESS ASSIGNMENT

RESET SWITCH

TROUBLE LED

W11

U1

ON

J1

SIGNAL AUDIBLE MODULE

1 2

1 2

1 2

A1869

Figure VII – 16 —Location of Switches and Jumperson Signal Audible Module

Module Switch PositionAddress SW2 –2 SW1 –1 SW1 –2

1 ON ON ON2 ON ON OFF

3 ON OFF ON

4 ON OFF OFF

5 OFF ON ON

6 OFF ON OFF

7 OFF OFF ON

8 OFF OFF OFF

T0019A

Table VII – 7 —Switch Positions for Signal Audible ModuleAddresses

Table VII – 6 —Maximum Wiring Lengthfrom Nominal 24 VDC Power Source to Signaling Device

Maximum Wire Length in Feet (Meters)

12 AWG 14 AWG 16 AWG(4 mm2)* (2.5 mm2)* (1.5 mm2)*

One 2 Ampere Load 190 (58) 120 (37) 75 (23)

Two 2 Ampere Loads 95 (29) 60 (18) 35 (11)

T0029A* Approximate Metric Equivalent.

Page 54: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 54/128

95-8470VII-13

FIELD DEVICES

EQ2200IDC SERIES INITIATING DEVICE CIRCUIT

WARNING The hazardous area must be de-classified prior to

removing a junction box cover with power applied.

1. Remove the cover from the junction box.

2. Connect external system wiring to the appropriateterminals on the terminal block inside the junction

box. See Figure VII-17 for terminal block locationand Figure VII-18 for terminal identification. The

input to the IDC consists of one or more normallyopen switches (momentary pushbuttons are not

recommended), with a 10K ohm, 1/4 watt EOLresistor in parallel across the last switch. An EOLresistor must be installed on both IDC inputs

(including unused inputs). Wiring impedance mustnot exceed 500 ohms.

3. Check the wiring to ensure proper connections.

4. Set the node address for the device. Refer to“Device Address Switch Setting” in the “Switch

Setting” section (Section VIII) of this manual forcomplete information regarding the switch setting

procedure.

5. Instal l the communicat ion module inside thejunction box. Be sure that the keyed ribbon cable isproperly connected.

6. Inspect the junction box O-ring to be sure that it is

in good condition and properly installed. Lubricatethe O-ring and the threads of the junction box cover

with a thin coat of an appropriate grease to easeinstallation and ensure a watertight enclosure. Therecommended lubricant is a silicone free grease,

available from Det-Tronics. Place the cover on thejunction box. Tighten only until snug. Do not over

tighten.

GND

9 1 0

7 8

5 6

3

4

1 2

1 3 1 4

1 1 1 2

A1870

Figure VII – 17 —IDC Terminal Wiring Board Mountedin Six-Port Junction Box

1

2

3

4

5

6

7

8

9

10

IDC MANUAL PULL STATION

OR OTHER CONTACT DEVICE

14

13

12

11

+

+

24 VDC

+

+

A

B

A

B

CIRCUIT 1

CIRCUIT 2

COM 2

COM SHIELD

COM 1

EOL (10K)

EOL (10K)

A1871

Figure VII – 18 —Terminal Configuration for Initiating Device Circuit

Page 55: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 55/128

VII-14

EQ2200IDCGF SERIES INITIATING DEVICE

CIRCUIT GROUND FAULT

1. Securely mount the aluminum enclosure. Theenclosure should be electrically connected to earth

ground.

2. Connect the external wiring to the appropriate

points on the terminal block. See Figure VII-17 for

terminal block location and Figure VII-19A forterminal identification.

3. Check all field wiring to ensure that the properconnections have been made.

4. Instal l the communication module inside thejunction box. Be sure that the keyed ribbon cable is

properly connected.

5. Set the node address for the device. Refer to“LON/SLC Device Address Switch Setting” in the“Switch Setting” section (Section VIII).

6. Inspect the enclosure O-ring to be sure that it is in

good condition and properly installed. Lubricatethe O-ring and the threads of the enclosure cover to

ease both installation and future removal of thecover. The recommended lubricant is a siliconefree grease available from Detector Electronics. If

the installation uses catalytic type combustible gassensors, it is imperative that lubricants containing

silicone not be used, since they will causeirreversible damage to the sensor. Place the cover

on the enclosure. Tighten only until snug. Do not

over tighten.

Device Configuration

When configuring the EQ2200IDCGF, its “device type”should be configured as an initiating device circuit

(IDC).

Both inputs must be configured for a trouble condition.

Circuit 1 – “Open” indicates a –24 VDC ground faultcondition. “Active” indicates a +24 VDC

ground fault condition.

Circuit 2 – “Active” indicates a loss of AC inputpower.“Open” indicates a loss of battery power.

EQ2200IDCSC SERIES INITIATING DEVICECIRCUIT SHORT CIRCUIT

The EQ2200IDCSC Initiating Device Circuit Short Circuit

(IDCSC) provides two supervised digital inputs for usewith dry contact inputs from devices such as relays,

pushbuttons, key switches, etc. The IDCSC supportsANSI/NFPA 72 Class B Style C (3 state, open/shortcircuit) supervised input circuits. Each circuit uses its

own end of line (EOL) resistor for monitoring circuitcontinuity and a series resistor for each contact.

1. Remove the cover from the junction box.

2. Remove the communicat ion module f rom thejunction box. Connect external system wiring to the

appropriate terminals on the terminal block insidethe junction box. See Figure VII-17 for terminal

block location and Figure VII-19B for terminalidentification. The input to the IDCSC consists of

one or more normally open switches, with a 10Kohm, 1/4 watt EOL resistor in parallel across the lastswitch. An EOL resistor must be installed on both

IDCSC inputs (including unused inputs). Wiringimpedance must not exceed 500 ohms. A 3.3K

ohm resistor must be installed in series with eachswitch.

3. Check the wiring to ensure proper connections.

3

4

5

6

7

8

9

10

14

13

12

11

+

+

24 VDC

+

A

B

A

B

INPUT

COM 2

COM SHIELD

COM 1

68K OHMRESISTOR

RELAY CONTACTFOR MONITORING BATTERY.CONTACT OPENSWITH BATTERY TROUBLE CONDITION.

RELAY CONTACTFOR MONITORING AC POWER.CONTACT CLOSESON LOSS OF AC POWER.

B1922

NOTE: ENCLOSURE AND/OR MOUNTING BRACKETMUST BE CONNECTED TO EARTH GROUND.

Figure VII-19A —EQ2200IDCGF Wiring Terminal

Page 56: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 56/128

4. Set the node address for the device. Refer to“Device Address Switch Setting” in the “Switch

Setting” section (Section VIII) of this manual forcomplete information regarding the switch settingprocedure.

5. Instal l the communicat ion module inside the

junction box. Be sure that the keyed ribbon cable isproperly connected.

6. Inspect the junction box O-ring to be sure that it isin good condition and properly installed. Lubricate

the O-ring and the threads of the junction box coverwith a thin coat of an appropriate grease to ease

installation and ensure a watertight enclosure. Therecommended lubricant is a silicone free grease,

available from Det-Tronics. Place the cover on thejunction box. Tighten only until snug. Do not overtighten.

EQ2200UV UV FLAME DETECTOR

1. Remove the sensor housing from the bulkhead (turn

counterclockwise). Install the sensor module andreplace the sensor housing. See Figure VII-20.

NOTE If the detector is equipped with a cover locking

device, i t must be loosened using a 5/32

hexagonal (Allen) wrench (see Figure VII-21).

2. Mount the swivel mounting bracket using 1/4 inch

(M6) screws with a length of at least 1 inch (25mm). The mounting surface should be free ofvibration. Allow adequate space around the swivel

to facilitate aiming and wiring of the detector.Armored flexible conduit should be used for the

final 3 feet (one meter) of the cable run to allow foraiming and alignment of the detector.

3. Attach the detector to the swivel mounting bracket.

4. Remove the rear housing from the bulkhead.

5. Connect the wires to the appropriate screwterminals on the terminal block. See Figure VII-22.

Connect the cable shields to the terminalsprovided.

6. Set the rocker switches on the DIP switch assemblyon the electronic module for the desired address.

Refer to “Device Address Switch Setting” in the“Switch Setting” section of this manual for complete

information regarding the switch setting procedure.

7. Install the electronic module, ensuring that theconnector is aligned correctly. Tighten the threecaptive screws that hold the electronic module in

place. See Figures VII-20 and VII-23.

8. Replace the rear housing and hand tighten to ensureproper sealing. See Figures VII-20 and VII-21.

9. Aim the detector at the potential hazard and tightenthe nut.

10. Check the viewing window surface (Figure VII-24)

and ensure that:A) the oi source (UV test lamp opening) is located

on top

B) the split in the oi reflective ring is not alignedwith the UV test lamp opening on the detector

module

C) the split in the oi ring is directed downward to

prevent a buildup of contaminants between the

oi ring and the viewing window.

95-8470VII-15

1

2

3

4

5

6

7

8

9

10

IDCSC

MANUAL PULL STATIONOR OTHER CONTACT DEVICE

14

13

12

11

+

+

24 VDC

+

+

A

B

A

B

CIRCUIT 1

CIRCUIT 2

COM 2

COM SHIELDS

COM 1

A2076

EOL (10K)

EOL (10K)

3.3 K

3.3 K 3.3 K

Figure VII-19B —Terminal Identification for EQ2200IDCSC

Page 57: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 57/128

VII-16

ELECTRONIC MODULE

REAR HOUSING

CONDUIT ENTRY

SENSOR MODULE

DETECTOR WINDOW

SENSOR HOUSING

BULKHEAD

CONDUIT ENTRY

oi RING

O-RING

O-RING

A1840

A1841

STRAP

COVERLOCKING

ASSEMBLY

BARREL LENS CAP

CATCH SCREW

CATCHBLIND HOLE SCREW COVER LOCKING CLAMPREAR HOUSING

Figure VII – 20 —EQ2200UV Detector Assembly

Figure VII – 21 —Optional Cover Locking Devices on UV Detector

Page 58: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 58/128

11. Clean the viewing window and oi ring using theprocedure described in the “Maintenance” section.

12. Install any optional accessories (such as air

shields).

EQ2200UVHT HIGH TEMPERATURE UV FLAMEDETECTOR

WARNING Do not open any junction box or device enclosure

when power is applied without first de-classifying the hazardous area.

Electronic Module Assembly

1. Mount the device on a solid surface that is free of

vibration.

2. Remove the cover from the junction box.

3. Loosen the three captive screws that hold theelectronic module to the terminal wiring board andremove the module. See Figure VII-25.

4. Loosen (do not remove) the two captive screws that

secure the terminal wiring board inside the junctionbox, and remove the terminal wiring board. SeeFigure VII-26. (The terminal blocks are located on

the bottom side of the terminal wiring board.)

5. Connect the UV detector wires to the appropriatepoints on the P3 terminal. Connect the 24 vdc

power wires and the communication network cable

to the appropriate points on the P2 terminal. SeeFigure VII-27 for terminal identification. Note that theplug-in terminals can be removed to facilitate wiring.

95-8470VII-17

TERMINALS 1 AND 2 — 24 VDC POWER SUPPLY (+)TERMINALS 3 AND 4 — POWER SUPPLY ( –)

TERMINAL 5 — COM 1 ATERMINAL 6 — COM 1 BTERMINAL 7 — SHIELD

TERMINAL 8 — COM 2 ATERMINAL 9 — COM 2 BTERMINAL 10 — SHIELD

1 2

3 4

5 6

8 9

7

10

24 VDC

COM 1

COM 2

A1873

+

Figure VII – 22 —EQ2200UV Detector Wiring Terminals

A1895

MOUNTING SCREWS

BULKHEAD

ADDRESS

SWITCHES

Figure VII – 23 —Electronic Module Mounted Inside Bulkhead

SPLIT IN oi RING(MUST BE POSITIONEDON THE DOWNWARD SIDEOF UNIT WHEN MOUNTED)

LEDs

UV TEST LAMP* OPENING

B1891

oi RING

* UV TEST LAMP OPENING MUST NOT BE ALIGNED WITH SPLIT IN oi RING

Figure VII – 24 —Viewing Window of UV Detector

LOOSEN THREE SCREWSTO REMOVE ELECTRONIC MODULE

ELECTRONIC MODULE

TERMINAL WIRING BOARD

A1992

Figure VII-25 —Electronic Module Installed on Terminal Wiring Board

Page 59: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 59/128

VII-18

NOTE Terminals 4 and 9 (shield) are connected

internally, as are terminals 5 and 8 (24 vdc +) and terminals 6 and 7 (24 vdc –).

6. Re-install the terminal wiring board inside the

junction box.

7. Set the rocker switches on the DIP switch assembly

on the electronic module for the desired address.Refer to “LON/SLC Device Address Switch Setting”

in the “Switch Setting” section of this manual forcomplete information regarding the switch setting

procedure.

8. Re-install the electronic module, ensuring that theconnector is aligned correctly. Tighten the three

captive screws that hold the electronic module inplace.

9. Replace the junction box cover and hand tighten toensure proper sealing.

UV Flame Detector

WIRING REQUIREMENTS

Wiring to the UV detector must be between 12 and 18AWG with a minimum voltage rating of 600 volts rms

and a minimum temperature rating of 125°C. The use of

shielded cable is highly recommended to providemaximum protection from RFI/EMI interference.

1. Mount the Swivel Mounting Bracket using 1/4 inch

(M6) screws with a length of at least 1 inch (25 mm).The mounting surface should be free of vibration.

Allow adequate space around the swivel to facilitate

aiming and wiring of the detector. Armored flexible

conduit should be used for the final 3 feet (onemeter) of the cable run to allow for aiming andalignment of the detector.

2. Attach the detector to the Swivel Mounting Bracket.

3. Disassemble the detector enclosure by turning the

housing cover counterclockwise. See Figure VII-28.

NOTE

If the detector is equipped with a cover locking device, it must be loosened using a hexagonal (Allen) wrench.

4. Connect the wires to the appropriate screw terminalson the detector terminal block. See Figure VII-27 forterminal identification. Do not ground the shield to

the detector housing. (Tape off the shield and leaveit disconnected.)

5. Remove the UV sensor tube module from its

shipping package. When handling the sensor tubemodule, be careful not to touch the sensor tube,since oil from the skin can attenuate UV radiation,

reducing the sensitivity of the tube.

6. Using the index pin as a guide, install the sensormodule on the detector terminal block.

Figure VII-26 — Terminal Wiring Board with Electronic Module

Removed

LOOSEN TWO SCREWS TOREMOVE TERMINAL WIRING BOARD

A1993

Figure VII-27 — EQ2200UVHT Wiring Terminal

1

2

3

4

5

6

7

8

9

10

A1989

11

12

SHIELD

SHIELD

SHIELD

SHIELD

A

B

B

A

+

+

COM 2

24 VDC

COM 1

1

2

3

4

5

A

B

C

D

P2

P3

UV FLAME DETECTORTERMINAL BLOCK

Page 60: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 60/128

95-8470VII-19

7. Re-assemble the detector housing. If the detectorsare equipped with cover locking devices, loosen the

clamp sufficiently so that the “catch” can be seatedin the blind hole provided on the terminal cap. Theclamp must then be fastened securely around the

detector barrel by tightening with the proper tool.

8. Clean the viewing window and oi ring using theprocedure described in the “Maintenance” section.

9. Check the viewing window surface (Figure VII-24)and ensure that:

A) The oi source (UV test lamp opening) is located

on top.

B) The split in the oi reflective ring is not alignedwith the UV test lamp opening on the detector

module.

C) The split in the oi ring is directed downward to

prevent a buildup of contaminants between the

oi ring and the viewing window.

10. Aim the detector at the potential hazard and tighten

the nut on the swivel mounting bracket.

11. Install any optional accessories (such as air shields).

EQ2200UVIR UV/IR FLAME DETECTOR

1. Mount and wire the detector.

A. Mount the detector and mounting bracketassembly on the wall or ceiling. Observe the

following guidelines:

— The mounting surface should be free of

excessive heat and vibration.

— Allow adequate space around the swivel tofacilitate aiming and wiring of the detector.

— Armored flexible conduit should be used

for the final 3 feet (one meter) of the cablerun to allow for aiming and alignment of the

detector.

— Position the conduit below the detector and

orient the detector with the conduit entry atthe bottom or either side of the detector(never at the top). This will prevent

condensation in the conduit from enteringthe detector junction box.

B. Remove the junction box cover.

C. Connect the leadwires to the appropriate screwterminals on the terminal block inside thejunction box. See Figures VII-29 and VII-30 for

location of the terminal block and Figure VII-31for terminal identification. Connect the shield of

the power cable to earth ground at the powersource. Connect the shields for the LON/SLC

cable as indicated. Do not ground the shieldsat the detector housing.

TERMINAL BLOCK

INDEX PIN

HOUSING COVER

UV SENSOR TUBE MODULE

A1994

Figure VII-28 —High Temperature UV Detector

Page 61: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 61/128

VII-20

A1912

TERMINAL BLOCK LON/SLC ADDRESS SWITCHES

LED **

SERVICE SWITCH *

"D" CONNECTORGROUND SCREW

NOTES: ** SERVICE SWITCH NOT FOR USE IN THE FIELD.NOTES: ** ILLUMINATION OF LED INDICATES AN ELECTRONIC MALFUNCTION.

Figure VII – 30 —UV/IR Detector Junction Box with Cover Removed

A1913

JUNCTION BOX

oi TEST LAMP (2)

O-RING

IR SENSOR HOUSING

IR oi RING

UV SENSOR MODULE

O-RING

oi TEST LAMP

UV SENSOR HOUSING

UV oi RING

IR SENSOR MODULE

UV TERMINAL BLOCK

BANANA PLUG

LED (2)

JUNCTION BOX COVER

IR CONNECTOR PLUG

Figure VII – 29 —UV/IR Detector Parts Identification

Page 62: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 62/128

95-8470VII-21

2. Set the rocker switches.

A. Set the rocker switches on the DIP switch

assembly for the desired LON/SLC address.Refer to “LON/SLC Device Address Switch

Setting” in Section VIII — Switch Setting.

B. Re-install the junction box cover. The six

screws must be tight to ensure the explosion-proof and watertight integrity of the junction

box.3. Complete the installation.

A. Aim the detector at the potential hazard.

B. Inspect and clean (if necessary) the detectorviewing windows and oi rings by following theinstructions in the Maintenance section of this

manual.

C. Check the detector viewing windows (Figure

VII-32) and ensure that:

— the oi test lamps are located at the top or

side of the sensor module (when viewed

from the front)

— the opening in the oi ring is at the bottom.This will ensure proper operation of the oi

system and also minimize the accumulationof moisture and contaminants between the

oi ring and the viewing window.

D. Install any optional accessories (such as air

shields).

oi RINGOPENINGDOWN

DETECTOR MUSTBE ORIENTED WITHCABLE/CONDUIT ENTRYAT BOTTOM (PREFERRED)OR SIDE TO ELIMINATEDRAINAGE INTOJUNCTION BOX.

*oi TEST LAMPS AT TOP OR SIDE

LED (2)

oi TEST LAMP

*oi TEST LAMP(2)

LED (2)

IR SENSOR HOUSING

UV SENSOR HOUSING

H1327

Figure VII – 32 —Front View of the UV/IR Detector

1

2

3

4

5

6

7

8

9

10

+

+

A

B

SHIELD

A

B

SHIELD

POWER

COM 1

COM 2

A1914

Figure VII – 31 —EQ2200UVIR Detector Wiring Terminals

Page 63: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 63/128

VII-22

EQ2200DCU DIGITAL COMMUNICATION UNIT USED

WITH DET-TRONICS H2S/O2 SENSORS OR OTHERTWO-WIRE 4 TO 20 MA DEVICES

Determine the best mounting locations for the detectors.

Whenever practical, detectors should be placed wherethey are easily accessible for calibration.

WARNING

Do not apply power to the system with the cover removed unless the area has been verified to be

free of combustible gases or vapors.

The DCU utilizes the following:

1. A terminal wiring board mounted at the bottom ofthe junction box.

2. A communication module mounted above the

terminal wiring board using the standoffs provided.See Figure VII-33.

Assembly and Wiring Procedure

Attach the sensor to the DCU enclosure. Do not over-tighten. If a sensor separation kit is being used, attach

the sensor to the separation kit junction box and wirethe device as described in the “Sensor Separation”section.

CAUTION

The sensor threads can be coated with an appropriate grease to ease installation. Also lubricate the cover threads. (See “Ordering

Information” for part number).

Connect the external wiring to the appropriate terminalson the DCU terminal wiring board. Refer to Figure VII-

34 for terminal identification. See Figure VII-35 for anexample of a Det-Tronics electrochemical sensor

connected to a DCU.

Attach the communication module to the standoffs asshown in Figure VII-33. Connect the ribbon cable fromthe terminal wiring board to the communication module.

Set the address for the device. Refer to “Device

Address Switch Setting” in the “Switch Setting” sectionof this manual for complete information regarding the

switch setting procedure.

Check the wiring to ensure proper connections, then

pour the conduit seals and allow them to dry (if conduitis being used).

NOTE Before placing the cover back on the enclosure

following completion of assembly and wiring,inspect the enclosure O-ring to be sure that it is in good condition and properly installed. Lubricate

the O-ring and the threads of the cover with a thin coat of an appropriate grease to ease installation.

Refer to the “Ordering Information” section for the part number of the recommended grease

(available from Detector Electronics). If the installation uses catalytic type combustible gas sensors, it is imperative that lubricants containing

sil icone NOT be used, since they will cause irreversible damage to the sensor. Place the cover

on the enclosure. Tighten only until snug. Do not over tighten.

SENSOR SEPARATION FOR DCU WITH H2S AND O2SENSORS

Since the transmitter for the electrochemical sensor isalready mounted within the sensor housing, simply

mount the entire sensor assembly to the sensorseparation kit junction box and wire it to terminals 2 and

4 inside the DCU, the same as a regular (without sensorseparation) installation. Connect the shield to the

ground terminal in the DCU junction box.

Refer to Table VII-8 for separation distance limitations

for H2S and O2 sensors.

A1571

COMMUNICATION MODULE

STANDOFFS (4)

TERMINAL WIRING BOARD

Figure VII – 33 —Printed Circuit Boards in Universal DCU

Page 64: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 64/128

95-8470VII-23

EQ2200DCU DIGITAL COMMUNICATION UNIT USED

WITH POINTWATCH

Determine the best mounting locations for the detectors.Whenever practical, detectors should be placed wherethey are easily accessible for calibration.

WARNING Do not apply power to the system with the cover

removed unless the area has been verified to be free of combustible gases and vapors.

The DCU utilizes the following:

1. A terminal wiring board mounted at the bottom of

the junction box.

2. A communication module mounted above theterminal wiring board using the standoffs provided.See Figure VII-33.

Assembly and Wiring Procedure

Attach the PointWatch to the DCU enclosure. Do not

over-tighten. If a sensor separation kit is being used,attach the sensor to the separation kit junction box andwire the device as described in the “Sensor Separation”

section.

Refer to the PointWatch instruction manual (formnumber 95-8440) for complete installation and

application information.

Refer to Figure VII-36 when wiring a PointWatch IR gasdetector and a DCU. The wiring code for PointWatch is:

Red = + (24 vdc)Black = – (common)

White = 4 to 20 ma signalYellow = Calibration input

Green = Chassis ground

Set the address for the device. Refer to “Device

Address Switch Setting” in the “Switch Setting” sectionof this manual for complete information regarding the

switch setting procedure.

T0020A

Wire Size Maximum Wiring Distance

(AWG) Feet Meters

18 5700 1750

16 9000 2800

Table VII – 8 —Maximum Separation Distances — Electrochemical Sensor to DCU

1

2

3

4

5

6

7

8

9

10

BLACK

RED

GREEN

DCU H2S/TOXIC/O2

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

A1875

Figure VII – 35 —Electrochemical Sensor Connected to DCU

1

2

3

4

5

6

7

8

9

10

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

A1726

Figure VII – 34 —Wiring Configuration for DCU

Page 65: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 65/128

Sensor Separation for DCU with PointWatch

Shielded four wire cable is recommended for

connecting the detector junction box to the DCU. Cablewith a foil shield is recommended. The shield of the

cable should be open at the detector junction box andconnected to earth ground at the DCU junction box.

Refer to Table VI-1 to determine the maximum allowablewiring from the PointWatch to the power supply (through

the DCU).

NOTE

To ensure proper operation, it is essential to maintain a minimum of 18 vdc (including ripple) at

the PointWatch detector.

EQ2200DCUEX DIGITAL COMMUNICATION UNIT

USED WITH DET-TRONICS COMBUSTIBLE GASSENSORS

Determine the best mounting locations for the detectors.

Whenever practical, detectors should be placed wherethey are easily accessible for calibration. Always orientthe junction box with the sensor pointing down.

WARNING Do not apply power to the system with the cover

removed unless the area has been verified to be free of combustible gases or vapors.

The DCUEX uses the following:

1. The terminal wiring board is mounted at the bottom

of the junction box.

2. The transmit ter board is mounted above the

terminal wiring board.

3. The communication module is mounted above thetransmitter board.

The boards are connected to each other using thestandoffs provided. See Figure VII-37.

NOTE Be sure to note correct orientation of the

transmitter board. If the transmitter board is rotated 180° from proper orientation, the device

will not operate correctly — a LON communication fault will result. See Figure VII-

37.

Assembly and Wiring Procedure

Connect the external wiring to the appropriate terminalson the DCU terminal wiring board. See Figure VII-38.

Attach the sensor to the DCU enclosure. Do not over-tighten. If a sensor separation kit is being used, attach

the sensor to the separation kit junction box and wirethe device as described below.

VII-24

1

2

3

4

5

6

7

8

9

10

YELLOW

WHITE

BLACK

RED

GREEN

DCU POINTWATCH

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

A1876

Figure VII – 36 —PointWatch Connected to DCU

Page 66: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 66/128

CAUTION

The sensor threads can be coated with an appropriate grease to ease both the init ial installation and future replacement of the sensor.

Detector Electronics offers a silicone free grease that is especially suited for use with catalytic type

combustible gas sensors (see “Ordering Information” for part number). The use of other

lubricants is not recommended, since some

materials can cause irreversible damage to the sensing element. SILICONE based lubricants or

compounds must NEVER be used.

Screw the transmitter board to the standoffs as shown inFigure VII-37. Connect the sensor plug to the

transmitter board.

Attach the communication module to the standoffsmounted on the transmitter board. Connect the ribbon

cable from the terminal wiring board to thecommunication module.

Set the address for the device. Refer to “DeviceAddress Switch Setting” in the “Switch Setting” section

of this manual for complete information regarding theswitch setting procedure.

95-8470VII-25

1

2

3

4

5

6

7

8

9

10

SIG

+

DCU TERMINAL BOARD DCU TRANSMITTER BOARD1

(MIDDLE BOARD)

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

B1877

NOTES: 1 Catalytic Combustible Gas SensorPlugs into Connector Pins on theMiddle Board inside the Junction Box.

2 Connections Wired at the Factory.

2

2

2

Figure VII – 38 —DCU Transmitter Board Connectedto Terminal Wiring Board

W R O N G

COMMUNICATION MODULE

TRANSMITTER BOARD

STANDOFFS (4)

TERMINAL WIRING BOARD

COMMUNICATION MODULE

SWITCHES ON SAME SIDE(RIGHT)

TRANSMITTER BOARD

TERMINAL WIRING BOARD

CORRECT ORIENTATION OF TRANSMITTER BOARD

COMMUNICATION MODULE

SWITCHES ON OPPOSITE SIDES(WRONG)

TRANSMITTER BOARD

TERMINAL WIRING BOARD

INCORRECT ORIENTATION OF TRANSMITTER BOARD

B1570

Figure VII – 37 —Printed Circuit Boards in Combustible Gas DCU

Page 67: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 67/128

VII-26

Sensor Separation with DCUEX

If the installation requires mounting the sensor in a

different location than the DCUEX, observe the followingguidelines.

When separating a combustible gas sensor from theDCUEX, two options exist:

1. Preferred MethodMount the transmitter PC board inside the sensorseparation junction box. This assembly can be

separated from the DCUEX by up to 1000 feet usingthree conductor 18 AWG shielded cable.

(Regardless of separation distance, operatingvoltage at the transmitter MUST be at least 18 vdc

to ensure proper operation.) See Figure VII-39.

Assemble the DCUEX without the transmitter board

similar to the DCU as shown in Figure VII-33. Plugthe sensor into P2 on the transmitter board. Use athree conductor 18 AWG shielded cable to connect

P1 on the transmitter board to terminals 2, 3 and 4on the DCU terminal board (see Figure VII-39).

Connect the shield to the ground terminal in theDCUEX junction box.

2. Alternate Method.

If the transmitter board must be mounted separatefrom the sensor (high temperature applications,

etc.), separate the sensor only, leaving thetransmitter PC board inside the DCUEX enclosure.When using this installation option, see Table VII-9

for maximum wiring distances.

Mount the sensor directly to the separation kitjunction box. Use three conductor shielded cablefor the connection between the terminal block in the

separation kit junction box and P1 on the transmitterboard. A plug with screw terminals is provided for

connecting the cable to P1 on the transmitter board.Observe the wiring color code. Connect the shield

to the ground terminal in the DCUEX junction box.SENSOR

CATALYTIC SENSOR

ELECTROCHEMICAL SENSOR

TRANSMITTER BOARD

P1

P2

+

–4 TO 20

B1878

POINTWATCH

GN D

SPARE

CAL

4-20

RET

+24

CHASSIS

CAL

4-20

RET

+24

+

G R N

+

G R N

NOTE:ALWAYS ORIENTJUNCTION BOX WITHCATALYTIC SENSORPOINTING DOWN.

Figure VII – 39 —Sensor Separation KitsTable VII – 9 —Maximum Separation Distances —

Combustible Gas Sensor to DCU (Alternate Method)

Wire SizeMaximum Separation Distance

Feet Meters

18 AWG (1.0 mm2)* 40 12

16 AWG (1.5 mm2)* 60 18

14 AWG (2.5 mm2)* 100 30

12 AWG (4.0 mm2)* 150 45

*Approximate Metric Equivalent.

Page 68: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 68/128

EQ2500ARM SERIES AGENT RELEASE MODULE

Wiring

To ensure adequate operating voltage for the output

device, the maximum wiring length from the powersource to the output device must not exceed the valuesshown in Table VII-10 for automatic release applications

or Table VII-11 for deluge and pre-action applications.

(For solenoids, this wire length includes both the wiringfrom the power supply to the agent release module andthe wiring from the module to the solenoid. For squibs,

use only the wire length from the power supply to themodule, since the resistance of the wire from themodule to the squib is included when determining the

value of the compensating resistor.)

Refer to Figure VII-40 for identification of wiringterminals.

Terminals 1 to 4 — Output terminals

Connect a single solenoidbetween terminals 1 and 4.

Connect dual solenoidsbetween terminals 1 and 2, and

between terminals 3 and 4.

NOTE

For testing purposes, a load resistor of 1200 to 1500 ohms @ 1 watt can be placed across

terminals 1 and 4.

When using an explosiveinitiator, connect the resistor

between terminals 1 and 2 andthe initiator between terminals3 and 4, as shown in Figure

VII-40.

CAUTION Do not intermix different types of initiators in the release circuit.

Terminals 5 to 10 — LON/SLC signaling circuit

terminals

Be sure to observe polarity

when wiring the LON/SLC.

5 — “A” side of signaling circuit for

COM 2

6 — “B” side of signaling circuit forCOM 2

7 and 8 — shield connection

9 — “A” side of signaling circuit forCOM 1

10 — “B” side of signaling circuit forCOM 1

95-8470VII-27

Solenoids Maximum Wire Length in Feet (Meters)

Manufacturer Model 12 AWG 14 AWG 16 AWG 18 AWG

Skinner LV2LBX25 800 (244) 500 (152) 310 (94) 200 (61)

ASCO 8210A107 520 (158) 325 (99) 200 (61) 130 (40)

ASCO 8210G207 825 (251) 520 (158) 325 (99) 205 (62)

Skinner 73218BN4UNLVNOC111C2 860 (262) 540 (165) 340 (104) 215 (66)

Skinner 73212BN4TNLVNOC322C2 400 (122) 250 (76) 160 (49) 100 (30)

Skinner 71395SN2ENJ1NOH111C2 860 (262) 540 (165) 340 (104) 215 (66)

T0041B

Table VII-11 —Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications

Device Maximum Wire Length in Feet

12 AWG 14 AWG 16 AWG 18 AWG

890181* 150 100 60

899175* 150 100 60

895630-000* 150 100 60

897494* 190 120 75

486500-001* 1500 1000 600 40031-199932-004* 150 100 60

Squib 190 120 75

2 Amp Load 190 120 75

T0028B*Fenwal Solenoid

Table VII – 10 —Maximum Wiring Length for Release Applications

Page 69: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 69/128

Terminals 11 to 14 — 24 vdc power input

Connect the module power

supply to terminals 12 and 13.If an auxiliary output supply is

used for powering solenoids, itshould be connected toterminals 11 and 14.

Jumpers

Terminals 13 and 14 are connected by jumper JP2 and

terminals 11 and 12 are connected by jumper JP3.These two jumpers (JP2 and JP3) must be cut if an

auxiliary output power supply is being used. See FigureVII-41 for the locations of jumpers on the circuit board.

When an explosive initiator is being used, jumper JP1

must be cut. If a solenoid is used, the jumper mustremain in.

Address Switch Setting

Each device on the LON/SLC must be assigned a

unique address. This is accomplished by setting DIPswitches on the release module circuit board. The valid

address range is from 5 to 250. For completeinformation on address switch setting, refer to

“LON/SLC Device Address Switch Setting” in SectionVIII. For convenience in determining the correctpositions for address switches, refer to the table

“Address Switch Settings” at the back of this manual.

VII-28

9 107 85 63 41 2

1 3 1 4 1 1 1 2

JP1

JP2

JP3

A1902

Figure VII – 41 —Agent Release Module Wiring Terminals and Jumpers

1

2

3

4

5

6

7

8

9

10

1

2

3

4

EXPLOSIVE INITIATOR OPTION

DUALSOLENOIDS

14

13

12

11

+

+

24 VDC

+

+

A

B

A

B

SINGLESOLENOID

COM 2

COM SHIELD

COM 1

NOTE:TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY.TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY.JUMPERS JP2 AND JP3 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED.

NOTES:1. JUMPER JP1 MUST BE REMOVED IF EXPLOSIVE INITIATOR IS USED.

2. RESISTOR IS USED TO COMPENSATE FOR 10 OHMS CIRCUIT RESISTANCE. RESISTOR MUST BE RATED 1 WATT MINIMUM (WIRE-WOUND RESISTOR PREFERRED).

WHEN MEASURING THE TOTAL RELEASE CIRCUIT RESISTANCE, USE AN OHM METER WITH A CURRENT OUTPUT OF 10 MA MAXIMUM.

3. MAXIMUM NUMBER OF EXPLOSIVE INITIATORS PER CIRCUIT IS 12. EACH CIRCUIT MUST NOT EXCEED 10 OHMS INCLUDING CABLE RESISTANCE. B1900

SEE NOTE 2.

Figure VII – 40 —Wiring Configuration for Agent Release Module

Page 70: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 70/128

95-8470VII-29

EQ2500SAM SERIES SIGNAL AUDIBLE MODULE

Wiring

To ensure adequate operating voltage for the signaling

device, the maximum wiring length from the powersource to the output device must not exceed the valuesshown in Table VII-12. (This wire length includes both the

wiring from the power supply to the signal audible module

and the wiring from the module to the signaling device.)

Refer to Figure VII-42 for identification of wiring

terminals.

Terminals 1 to 4 — Output terminals

Connect the first output device

between terminals 1 and 2,and the second between

terminals 3 and 4.

Polarity shown in Figure VII-42

is for monitoring condition,polarity is reversed when

activated.

Each circuit must have a 10

kohm EOL resistor.

Terminals 5 to 10 — LON/SLC signaling circuit

terminals

Be sure to observe polaritywhen wiring the LON/SLC.

5 — “A” side of signaling circuit for

COM 2

6 — “B” side of signaling circuit for

COM 2

7 and 8 — shield connection

9 — “A” side of signaling circuit forCOM 1

10 — “B” side of signaling circuit forCOM 1

Terminals 11 to 14 — 24 vdc power input

Connect the module powersupply to terminals 12 and 13.

If an auxiliary output supply isused for powering signaling

devices, it should be connectedto terminals 11 and 14.

Jumpers

Terminals 13 and 14 are connected by jumper JP2 andterminals 11 and 12 are connected by jumper JP1.

These two jumpers (JP1 and JP2) must be cut if an

auxiliary output power supply is being used. See FigureVII-43 for the locations of jumpers on the circuit board.

1

2

3

4

5

6

7

8

9

10

14

13

12

11

+

+

24 VDC

+

+

A

B

A

B

OUTPUT 1*

OUTPUT 2*

COM 2

COM SHIELD

COM 1

* POLARITY SHOWN IS FOR MONITORING CONDITION,POLARITY IS REVERSED WHEN ACTIVATED.

NOTE:TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY.TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY.JUMPERS JP1 AND JP2 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED.

B1901

10K EOL

10K EOL

Figure VII – 42 —Wiring Configuration for Signal Audible Module

Maximum Wire Length in Feet (Meters)

12 AWG 14 AWG 16 AWG

(4 mm2)* (2.5 mm2)* (1.5 mm2)*

One 2 Ampere Load 190 (58) 120 (37) 75 (23)

Two 2 Ampere Loads 95 (29) 60 (18) 35 (11)

T0029A* Approximate Metric Equivalent.

Table VII – 12 —Maximum Wiring Lengthfrom Nominal 24 VDC Power Source to Signaling Device

Page 71: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 71/128

Address Switch Setting

Each device on the LON/SLC must be assigned aunique address. This is accomplished by setting DIP

switches on the module’s circuit board. The validaddress range is from 5 to 250. For complete

information on address switch setting, refer to“LON/SLC Device Address Switch Setting” in SectionVIII. For convenience in determining the correct

positions for address switches, refer to the table“Address Switch Settings” at the back of this manual.

EQ2400NE SERIES NETWORK EXTENDER

1. Securely mount the aluminum enclosure.

2. Remove the cover from the network extender

enclosure.

3. Connect the 24 vdc power lead wires and thecommunication network cable to the appropriate

points on the terminal block. See Figure VII-44A forterminal location within the junction box and FigureVII-44B for terminal identification. Refer to Table VII-

13 to determine maximum wiring length.

VII-30

1

2

3

4

5

6

7

8

9

10

A1947

11

12

SHIELD

SHIELD

SHIELD

SHIELD

A

B

A

B

+

+

COM 2

24 VDC

COM 1

Figure VII-44B —Network Extender Wiring Terminal Identification

TERMINAL NO. 1

1 12

A2021

Figure VII-44A —Network Extender Wiring Terminal Location

9 107 85 63 41 2

1 3 1 4 1 1 1 2JP1

JP2

B1903

Figure VII – 43 —Signal Audible Module Wiring Terminals and Jumpers

Page 72: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 72/128

COM 1 - Communication network connect ions:Connect to COM 2 terminals of the next

device on the loop, A to A and B to B.

COM 2 - Communication network connect ions:

Connect to COM 1 terminals of theprevious device on the loop, A to A and B

to B.

24 VDC - Connect the "+" terminal to the positiveside of the 24 vdc power source. (Both "+"terminals are connected internally.)

Connect the "-" terminal to the negative

side of the 24 vdc power source. (Both "-"terminals are connected internally.)

4. Connect the shields to the two designated "shield"terminals. The two shield terminals are connected

internally to ensure shield continuity. Do not groundeither shield at the network extender enclosure.

Insulate the shields to prevent shorting to the

device housing or any other conductor.

5. Check all field wiring to ensure that the proper

connections have been made.

6. Inspect the enclosure O-ring to be sure that it is in

good condition and properly installed. Lubricate theO-ring and the threads of the enclosure cover to

ease both installation and future removal of thecover. The recommended lubricant is a silicone free

grease available from Detector Electronics. If theinstallation uses catalytic type combustible gassensors, it is imperative that lubricants containing

silicone not be used, since they will causeirreversible damage to the sensor. Place the cover

on the enclosure. Tighten only until snug. Do not

over tighten.

TYPICAL APPLICATIONS

Figure VII-45 shows a power supply monitor wired on a

LON between a UV detector and a DCU.

Figure VII-46 illustrates the power and communicationwiring for a UV detector, an IDC and a DCU, connected

to a standard LCU (EQ2100LCU) and an LIOU.

Figure VII-47 illustrates the power and communicationwiring for a UV detector, an IDC and a DCU, connectedto the optional LCU (EQ2101LCU) and an LIOU.

Figure VII-48 shows the power and communication

wiring for a UV/IR detector, an EQ2500SAM and anEQ2500ARM, connected to a standard LCU

(EQ2100LCU) and an LIOU.

Figure VII-49 shows a network extender wired between

a UV detector and a DCU.

Figure VII-50 shows a high temperature UV detector

wired between a standard UV detector and a DCU.

95-8470VII-31

Table VII-13 —Maximum Wiring Length from Nominal 24 vdcPower Source to Network Extender

Wire SizeMaximum Wiring Distance

Feet Meters

18 AWG (1.0 mm2)* 2200 650

16 AWG (1.5 mm2)* 3500 75014 AWG (2.5 mm2)* 5600 1700

* Approximate Metric Equivalent.

Page 73: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 73/128

INSTALLATION CHECKLIST

The following checklist is provided as a means of

double checking the system to be sure that all phasesof system installation are complete and have been

performed correctly.

1. Junction boxes are mounted securely and detectorsare pointing in the proper direction.

2. Al l cable shields are proper ly insulated andgrounded.

3. All junction box covers are tightly installed.

4. Explosion-proof and watertight electrical fittings

have been installed at all junction box entries asrequired for the hazardous location.

5. Sensor and LON/SLC wiring is correct.

6. Power wiring is installed and power source isoperational.

7. External loads are properly connected and EOLresistors are installed.

8. DIP switches are set correctly. Record th is

information for future reference.

9. Devices are properly installed in the mounting

racks.

10. Proper ventilation is provided (if needed) to preventequipment over-heating.

Proceed to System Startup.

VII-32

3456 12101112 78

1 2

3 4

COM 1

COM 2

+

BA24 VDC

1098

76SHIELD

5

1 2 3 109874 65 S H I E L D

A B S H I E L D

+–– + S H I E L D

A B S H I E L D B A S

H I E L D

S H I E L D

B A + S E N S OR

P OWE R

4 T O2 0 MA I N

P O I N T WA T C H

C A L I B R A T E

C OM1

C OM2

C OM1

2 4 V D C

C OM2

24 VOLTS DC + + – –

EQ2200UV EQ2200DCUEQ2100PSM

14 13 12 11

9

TO PREVIOUS LON DEVICE

TO NEXT LON DEVICE

TO POWER DISTRIBUTION

TERMINALS

B1953

G

Figure VII-45 —A Typical Application — LON Connections for a Power Supply Monitor Wired Between a UV Detector and a DCU

Page 74: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 74/128

95-8470VII-33

C O M 2

N O

F A U L T

K 4

K 3

K 2

K 1

3 E

3 D

2 E

2 D

1 E

1 D

T R O U B L E

S U P E R

A L A R M

C O M 1

C O M

2 5

2 4

2 3

2 2

2 1

2 0

1 9

1 8

1 7

1 6

1 5

1 4

1 3

1 2

1 1

1 0 9 8 7 3 2 1

R X D +

C O M

T X D +

C O M A

C H A S S I S – – – –

P 1

P 2

R S - 4 8 5

G N D F L T

M A I N 2 4 V

A U X 2 4 V

D C 1

D C 2

A B

S H I E L D

R E S E T

I N P U T 1

I N P U T 2

I N P U T 3

R X D –

T X D –

R X D

T X D B

E A R T H + + + +

N C

N O

C O M

N C

G A T E W A Y R E L A Y S

R O W

C

R O W

B R

O W

A

C 1 8 7 9

1

2

3

1 0

9

8

7

4

6

5

1

2

3

4

C O M 1

C O M 2

+ –

B

A

2 4 V D C

1 0

9

8

7

6

S H I E L D

5

1

2

3

1 0

9

8

7

4

6

5

B

A

SHIELD

SHIELD

B

A

+

+

B

A

SHIELD

SHIELD

B

A

+ SENSOR

– POWER

4 TO 20 MA IN

POINTWATCH CALIBRATE

COM 1

COM 2

2 4 V O L T S D C

+

+

2 4 V O L T S D C

T O G A S D E T E C T O R

P O W E R S U P P L Y

+

+

J3 J4

AUX POWER

J5

A

B

J1 J2

+

+

RS-485 MAIN AUX

E Q 2 1 0 0 L C U

E Q 2 2 0 0 U V

E Q 2 2 0 0 D C U

E Q 2 1 0 0 L I O U

E Q 2

2 0 0 I D C

1 4

1 3

1 2

1 1

1 4

1 3

1 2

1 1

3

4 5

6

1

2

1 0

1 1

1 2

7

8

SHIELD

A

B

SHIELD+

+

SHIELD

A

B

SHIELD

COM 1

24 VDC

COM 2

9

S Y S T E M

P O W E R

S U P P L Y

+

+

2 4 V O L T

B A T T E R Y

B A C K U P

COM 1

COM 2

CIRCUIT 2

CIRCUIT 1

A C L I N E

H

N

J 1

J 3 1 2 3 4 C B

P O W E R S U P P L Y M O N I T

O R

B A T T E R Y

C K T B R E A K E R

B U S

B A R

G

G

S

C

Q C S

Page 75: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 75/128

VII-34

A

B

C O M 2

N O

F A U L T

K 4

K 3

K 2

K 1

3 E

3 D

2 E

2 D

1 E

1 D

T R O U B L E

S U P E R

A L A R M

C O M 1

C O M

2 5

2 4

2 3

2 2

2 1

2 0

1 9

1 8

1 7

1 6

1 5

1 4

1 3

1 2

1 1

1 0 9 8 7 6 5 4 3 2 1

R X D +

C O M

T X D +

C O M A

C H A S S I S – – – –

P 1

P 2

R S - 4 8 5

G N D F L T

M A I N 2 4 V

A U X 2 4 V

D C 1

D C 2

A B

S H I E L D

R E S E T

I N P U T 1

I N P U T 2

I N P U T 3

R X D –

T X D –

R X D

T X D B

E A R T H + + + +

N C

G A T E W A Y R E L A Y S

R O W

C

R O W

B R

O W

A

B 1 8 8 0

1

2

3

1 0

9

8

7

4

6

5

1

2

3

4

C O M 1

C O M 2

+ –

B

A

2 4 V D C

1 0

9

8

7

6

S H I E L D

5

1

2

3

1 0

9

8

7

4

6

5

B

A

SHIELD

SHIELD

B

A

+

+

COM 1

COM 2

CIRCUIT 2

CIRCUIT 1

B

A

SHIELD

SHIELD

B

A

+ SENSOR

– POWER

4 TO 20 MA IN

POINTWATCH CALIBRATE

COM 1

COM 2

2 4 V O L T S D C

+

+

2 4 V O L T S D C

T O G A S D E T E C T O R

P O W E R S U P P L Y

+

+

J3 J4

AUX POWER

J5

J1 J2

+

+

RS-485

E Q 2 1 0 1 L C U

E Q 2 2 0 0 U V

E Q 2 2 0 0 D C U

E Q 2 1 0 0 L I O U

E Q 2

2 0 0 I D C

MAIN AUX

T W O 2 4 V O L T D C

P O W E R S U P P L I E S

P E R N F P A 7 2

+ – + –

N O

C O M

N C

1 4

1 3

1 2

1 1

1 4

1 3

1 2

1 1

G

G

F i g u r e V I I – 4 7 — A T y p i c

a l S y s t e m — F i e l d D e v i c e s C o n n e c t e d t o E

Q 2 1 0 1 L C U ( O p t i o n a l )

Page 76: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 76/128

95-8470VII-35

C O M 2

N O

F A U L T

K 4

K 3

K 2

K 1

3 E

3 D

2 E

2 D

1 E

1 D

T R O U B L E

S U P E R

A L A R M

C O M 1

C O M

2 5

2 4

2 3

2 2

2 1

2 0

1 9

1 8

1 7

1 6

1 5

1 4

1 3

1 2

1 1

1 0 9 8 7 3 2 1

R X D +

C O M

T X D +

C O M A

C H A S S I S – – – –

P 1

P 2

R S - 4 8 5

G N D F L T

M A I N 2 4 V

A U X 2 4 V

D C 1

D C 2

A B

S H I E L D

R E S E T

I N P U T 1

I N P U T 2

I N P U T 3

R X D –

T X D –

R X D

T X D B

E A R T H + + + +

N C

N O

C O M

N C

G A T E W A Y R E L A Y S

R O W

C

R O W

B

R O W

A

C 1 9 1 0

1

2

3

1 0

9

8

7

4

6

5

1

2

3

1 0

9

8

7

4

6

5

1

2

3

1 0

9

8

7

4

6

5

B

A

SHIELD

SHIELD

B

A

+

+

SHIELD

B

A

SHIELD

B

A

+

+

COM 1

COM 2

OUTPUT 2

OUTPUT 1

B

A

SHIELD

SHIELD

B

A

+

+

COM 1

COM 2

2 4 V O L T S D C

+

+

J3 J4

AUX POWER

J5

A

B

J1 J2

+

+

RS-485 MAIN AUX

E Q 2 1 0 0 L C U

E Q 2 2 0 0 U V I R

E Q 2 5 0 0 A R M

E Q 2 1 0 0 L I O U

E Q 2 5 0 0 S A M

1 4

1 3

1 2

1 1

1 4

1 3

1 2

1 1

C O M 1

C O M 2

+

+

– 2 4 V O L T S D C

D U A L S O L E N O I D S

S I N G L E S O L E N O I D

3

4

5

6

1

2

1 0

1 1

1 2

7

8

SHIELD

A

B

SHIELD

+

– –

+

SHIELD

A

B

SHIELD

COM 1

24 VDC

COM 2

9

S Y S T E M

P O W

E R

S U P

P L Y

+

+

2 4 V O L T

B A T T E R Y

B A C K U P

A

C L I N E

H

N

J 3 1 2 3 4 C B

P O W E R S U P P L Y M O N I T O R

B A T T E R Y

C K T B R E A K E R

B U S

B A R

G

G

F i g u r e V I I 4 8 A T y p i c a l S y s t e m U V / I R

D e t e c t o r E Q 2 5 0 0 S A M a n d E Q 2 5 0 0 A R M C o n n e c t e d t o a S t a n d a r d E Q 2 1 0 0 L C U

Page 77: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 77/128

VII-36

C O M 2

N O

F A U L T

K 4

K 3

K 2

K 1

3 E

3 D

2 E

2 D

1 E

1 D

T R O U B L E

S U P E R

A L A R M

C O M 1

C O M

2 5

2 4

2 3

2 2

2 1

2 0

1 9

1 8

1 7

1 6

1 5

1 4

1 3

1 2

1 1

1 0 9 8 7 3 2 1

R X D +

C O M

T X D +

C O M A

C H A S S I S – – – –

P 1

P 2

R S - 4 8 5

G N D F L T

M A I N 2 4 V

A U X 2 4 V

D C 1

D C 2

A B

S H I E L D

R E S E T

I N P U T 1

I N P U T 2

I N P U T 3

R X D –

T X D –

R X D

T X D B

E A R T H + + + +

N C

N O

C O M

N C

G A T E W A Y R E L A Y S

R O W

C

R O W

B R

O W

A

C 1 9 4 0

3

4

5

6

1

2

1 0

1 1

1 2

7

8

1

2

3

4

C O M 1

C O M 2

+ –

B

A

2 4 V D C

1 0

9

8

7

6

S H I E L D

5

1

2

3

1 0

9

8

7

4

6

5

SHIELD

A

B

SHIELD

+

+

SHIELD

A

B

SHIELD

B

A

SHIELD

SHIELD

B

A

+ SENSOR

– POWER

4 TO 20 MA IN

POINTWATCH CALIBRATE

COM 1

COM 2

COM 1

24 VDC

COM 2

2 4 V O L T S D C

T O G A S D E T E C T O R

P O W E R S U P P L Y

+

+

J3 J4

AUX POWER

J5

A

B

J1 J2

+

+

RS-485 MAIN AUX

E Q 2 1 0 0 L C U

E Q 2 2 0 0 U V

E Q 2 2 0 0 D C U

E Q 2 1 0 0 L I O U

E Q 2 4 0 1 N E

1 4

1 3

1 2

1 1

9

3 4

5

6

1

2

1 0

1 1

1 2

7

8

SHIELD

A

BSHIELD

+

+

SHIELD

A

B

SHIELD

COM 1

24 VDC

COM 2

9

S Y S T E M

P O W E R

S U P P L Y

+

+

2 4 V O L T

B A T T E R Y

B A C K U P

A C L I N E

H

N

J 3 1 2 3 4 C B

P O W E R S U P P L Y M O N I T O R

B A T T E R Y

C K T B R E A K E R

B U S

B A R

G

G

F i g u r e V I I - 4 9 — A T y p i c a l S y s t e m - N e t w o r k E x t e n d e r W i r e d B e t w e e n U V D e t e c t o r a n d D C U

Page 78: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 78/128

95-8470VII-37

F i g u r e 5 0 — A T y p i c a l S y s t e

m – E Q 2 2 0 0 U V H T W i r e d B e t w e e n a S t a n d

a r d U V D e t e c t o r a n d a D C U

C O M 2

N O

F A U L T

K 4

K 3

K 2

K 1

3 E

3 D

2 E

2 D

1 E

1 D

T R O U B L E

S U P E R

A L A R M

C O M 1

C O M

2 5

2 4

2 3

2 2

2 1

2 0

1 9

1 8

1 7

1 6

1 5

1 4

1 3

1 2

1 1

1 0 9 8 7 3 2 1

R X D +

C O M

T X D +

C O M A

C H A S S I S – – – –

P 1

P 2

R S - 4

8 5

G N D F L T

M A I N 2 4 V

A U X 2 4 V

D C 1

D C 2

A B

S H I E L D

R E S E T

I N P U T 1

I N P U T 2

I N P U T 3

R X D –

T X D –

R X D

T X D B

E A R T H + + + +

N C

N O

C O M

N C

G A T E W A Y R E L A Y S

R O W

C

R O W B

R O W

A

B 1 9 9 0

3

4

5

6

1

2

1 0

1 1

1 2

7

8

1

2

3

4

C O M 1

C O M 2

+ –

B

A

2 4 V D C

1 0

9

8

7

6 S H I E L D

5

1

2

3

1 0

9

8

7

4

6

5

SHIELD

A

B

SHIELD

+

+

SHIELD

A

B

SHIELD

B

A

SHIELD

SHIELD

B

A

+ SENSOR

– POWER

4 TO 20 MA IN

POINTWATCH CALIBRATE

COM 1

COM 2

COM 1

24 VDC

COM 2

2 4 V O L T S D C

T O G A S D E T E C T O R

P O W E R S U P P L Y

+

+

J3 J4

AUX POWER

J5

A

B

J1 J2

+

+

RS-485 MAIN AUX

E Q 2 1 0 0 L C U

E Q 2 2 0 0 U V

E Q 2 2 0 0 D C U

E Q 2 1 0 0 L I O U

E Q

2 2 0 0 U V H T

1 4

1 3

1 2

1 1

9

3

4

5

1

2

C

D

A

B

3

4

5

6

1

2

1 0

1 1

1 2

7

8

SHIELD

A

B

SHIELD

+

+

SHIELD

A

B

SHIELD

COM 1

24 VDC

COM 2

9

S Y S T E M

P O W E R

S U P P L Y

+

+

2 4 V O L T

B A T T E R Y

B A C K U P

A C L I N E

H

N

J 3 1 2 3 4 C B

P O W E R S U P P L Y M O N I T O R

B A T T E R

Y

C K T B R E A

K E R

B U S

B A R

G

G

Page 79: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 79/128

VIII-1 95-8470

Section VIIISwitch Setting

GATEWAY

The gateway contains four 8-position DIP switchassemblies that are used for:

— Selecting serial port 1 software parameters

— Setting the gateway Modbus/Allen Bradley address— Selecting gateway relay operation (latching/non-

latching)— Setting the gateway type and address.

Refer to Figure VIII-1 to identify the function of the DIP

switches. Refer to Figure VIII-2 to locate the DIP switchassemblies on the side of the gateway.

S5 — Hardware Serial Port Configuration

Verify that S5 switches are set as follows:

1 — Open

2 — Closed

3 — Closed

4 — Open

5 and 6 — Closed

7 and 8 — Open.

S6 — Software Serial Port Configuration for Port 1

1, 2, and 3 — Determine the desired baud

rate, then refer to Table VIII-1for the proper switch settings.

(19,200 is recommended andcannot be exceeded in the

LCU.)

4 — Parity enable.Open = no parity.Closed = parity enabled.

5 — Parity type.

Open = odd.Closed = even.

6 — Stop bits.

Open = 1 stop bit.Closed = 2 stop bits.

PARITY ENABLE (OFF = NO PARITY, ON = PARITY ENABLED)

BAUD RATE BIT 2 (MSB)

BAUD RATE BIT 1

BAUD RATE BIT 0 (LSB)

PARITY TYPE (OFF = ODD, ON = EVEN)

NUMBER OF STOP BITS (OFF = 1, ON = 2)

OPENNUMBER OF DATA BITS (OFF = 7, ON = 8)

1 2 3 4 5 6 7 8

S6 SOFTWARE SERIAL PORT CONFIGURATION (CHANNEL 1 ONLY)

0 = 1200

1 = 2400

2 = 96003 = 19200

C1888

OPEN

CLOSEDCLOSED

OPEN

CLOSED

CLOSED

OPENOPEN

1 2 3 4 5 6 7 8

S5 HARDWARE SERIAL PORT CONFIGURATION

CLOSED = ONOPEN = OFF

MODBUS ADDRESS BIT 3

MODBUS ADDRESS BIT 2

MODBUS ADDRESS BIT 1

MODBUS ADDRESS BIT 0 (LSB)

MODBUS ADDRESS BIT 4

MODBUS ADDRESS BIT 5

MODBUS ADDRESS BIT 7 (MSB)MODBUS ADDRESS BIT 6

1 2 3 4 5 6 7 8

S7 MODBUS ADDRESS

PORT 2 OPERATION

PORT 1 OPERATION

GATEWAY ADDRESS BIT 1 (MSB)

GATEWAY ADDRESS BIT 0 (LSB)

SELECT CONFIGURATION PORT

NON-LATCHING GATEWAY RELAYS

CLOSED

OPEN

1 2 3 4 5 6 7 8

S8 LON CONFIGURATION

Figure VIII–1—Gateway DIP Switch AssignmentsS8S7S6S5

A1546

Figure VIII–2—Gateway DIP Switch Location

Page 80: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 80/128

VIII-2

7 — Data bits.

Closed = 8 data bits

(required forModbus or Allen

Bradleycommunication).

Open = 7 data bits (notrecommended).

8 — Open.

NOTE Serial port 2 is fixed at 9600 baud, one stop bit and

even parity.

S7 — Port 1: Modbus/Allen Bradley Address

Set switches to match the

required slave address. “0” isnot a valid address. Refer to

“Address Switch Settings” in

the Appendix.

S8 — Network Configuration

1 and 2 — Gateway LON/SLC address.See Table VIII-2. Gateway

address 1 is recommended.

3 — Port 1 operation:

Open = Modbus RTU Slave

Closed = Allen Bradley DF1Slave

4 — Port 2 operation:

Open = Modbus RTU SlaveClosed = Modbus RTU

Master (to PLC)

5 — Select configuration port:

Open = Port 1Closed = Port 2

6 — Relay Operation.

Open = LatchingClosed = Non-latching.

7 — Reserved. Leave switch Open

8 — Gateway type.

Open = ReservedClosed = Main gateway.

BAUD RATE SWITCH POSITIONS

1 2 3

1,200 Op Op Op

2,400 Cl Op Op

9,600 Op Cl Op

19,200 Cl Cl Op

Op = Open

Cl = Closed

T0022B

Table VIII–1—Baud Rate Selection - Switches S6-1, S6-2, S6-3

Gateway Address S8-1 S8-2

1 Op Op

2 Cl Op

3 Op Cl

4 Cl Cl

Op = Open

Cl = Closed

T0023A

Table VIII–2—Gateway Address Switch Settings

Page 81: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 81/128

LOGIC CONTROLLER

The logic controller contains three 8-position DIP switch

assemblies that are used for:

— Serial port configuration— Communication parameters

— Setting the LON/SLC address.

S5 — Hardware Serial Port Configuration

Verify that S5 switches are set as follows:

1 — Closed

2 — Open

3 — Open

4 — Closed

5 — Open

6 — Open

7 — Closed

8 — Open.

S6 — Diagnostic Serial Port Configuration

Diagnostic serial port is

intended for factory use only.Switch settings will not affect

normal operation.

S7 — LON/SLC Address

Set switches for the LON/SLC

address. Valid addresses arefrom 5 to 247, and must be an

odd number. If an addressoutside this range is selected,the address will default to 5.

S7-1 = LSB, S7-8 = MSB.

ISOLATION MODULE

A slide switch (SW1), located on the top edge of themodule, controls the 24 volt ground fault monitor

function.

On = EnabledOff = Disabled

Determine the type of LCU being used (Refer to thelabel on the LCU mounting cage.) Set SW1 as follows:

Off — EQ2100LCUOn — EQ2101LCU

LON/SLC DEVICE ADDRESS SWITCHSETTING

Each individual device on the LON/SLC must beassigned a unique address. Addresses 1 to 4 are

reserved for gateway use. Address 1 is for the maingateway. Valid addresses for field devices are from 5 to

250. If the address is set to zero or an address above250, the communication module will ignore the switch

setting. Duplicated addresses are not automaticallydetected. All modules with the same address will reporton that address. The status word will show the latest

update, which could be from any of the reportingmodules at that address.

NOTE Logic controllers utilize two consecutive LON/SLC

addresses, the first of which must be an odd number, i. e. a Logic Controller with an address of

7 will occupy both 7 and 8 on the LON/SLC.

Selection of the node address for field devices is

accomplished by setting rocker switches on a DIPswitch assembly. (Note that only the first eight of the 12switches are used for selecting the address.) Theaddress number is binary encoded with rocker switch

No. 1 on the 8 position switch assembly being the LSB(least significant bit). Each rocker switch has a specific

binary value, as shown in Figure VIII-3. The nodeaddress is equal to the added value of all closed rocker

switches. All open switches are ignored. For example:for node No. 5, close rocker switches 1 and 3 (binaryvalues 1 + 4); for node No. 25, close rocker switches 1,

4 and 5 (binary values 1 + 8 + 16).

Power must be cycled before the new address will takeeffect.

For your convenience in setting the address switches,refer to the table “Address Switch Settings” at the back

of this manual.

After setting the address switches, record the addressnumber and device type on the “Address Identification

Chart” provided with this manual. Post the chart in aconvenient location near the LCU.

VIII-3 95-8470

1 2 3 4 5 6 7 8 1 2 3 4

1 2 4 8 16 32 64 128

OPEN OPEN

LEAVE INOPEN POSITION

NODE ADDRESS EQUALS THE ADDED VALUEOF ALL CLOSED ROCKER SWITCHES

A1557

BINARYVALUE

CLOSED = ON

OPEN = OFF

Figure VIII–3—Field Device Address Switches

Page 82: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 82/128

IX-1 95-8470

Section IXSystem Startup

PRE-COMMISSIONING CHECKLIST

GENERAL

Insulate all shields to prevent shorting to the device

housing or to any other conductor.

Place alarm/release output in “Bypass/Isolate” whenservicing devices.

Maintain a log book containing the type and serialnumbers of devices as well as the location and date ofinstallation.

Maintain a log of maintenance activities.

Observe normal precautions for handling electrostaticsensitive devices.

LON

Rocker switches for each LON device must be set to the

desired address prior to power-up.

Test the loop with no power applied and all

communication modules removed. DC resistanceshould be equal on A and B.

Check polarity on A and B (no rolls). COM 1 connectsto COM 2 ; COM 2 connects to COM 1. A connects to

A and B to B.

Measure voltage. A to chassis ground measures

approximately +7.5 vdc. B to ground measures

approximately –7.5 vdc.Measure signal (400 mv P-P min.).

Check fault tolerance by introducing a short and an

open.

LCU

Verify correct switch positions.

All configuration data must be downloaded to thedevice and written to the EPROM after any change ismade. Changes to the logic controller also require

downloading via the key switch.

Chassis ground stud must be connected to earthground.

Check RS-485 connections and polarity.

The last device requires an EOL resistor.

All devices sharing a common RS-485 link must have a

common system power return.

LIOU

Verify correct jumper positions and switch settings.

Never disconnect the circuit ground between the LIOUand the LCU.

Check signal circuits for correct polarity.

Check for correct installation of EOL resistors.

POWER SUPPLIES AND POWER MONITORS

Verify all earth ground connections as specified in the

wiring instructions.

Verify correct ac power to supply.

Check power distribution to ensure that all devices arereceiving power.

Check power trouble indicator by introducing a short

and an open.

FLAME DETECTORS

Check for potential false alarm sources.

Check detector aiming and ensure that mountingbrackets are tight.

Check for objects that can block the detector’s view.Detectors can be checked for proper response using

the test described in this manual.

DCUs

Check modules for correct orientation.

Check for the presence of contaminants or poisoning

agents.

Device should be oriented with the sensor pointingdown.

IDCs

Check for correct installation of EOL resistors.

Page 83: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 83/128

ARMs

Check jumpers.

SAMs

Check signal circuits for correct polarity.

Check for correct installation of EOL resistors.

Check jumpers.

STARTUP PROCEDURE

1. Output loads that are controlled by the systemshould be secured (remove power from all outputdevices) to prevent actuation.

2. Check all system wiring for proper connection.

3. Before installing devices in the mounting racks,

inspect them to verify that they have not beenphysically damaged in shipment. Check the rockerswitches for proper programming, then slide the

device fully into the mounting rack.

4. Apply power to the system.

NOTE

To prevent the network modules from going into a fault isolation condition, apply power to the LCU

prior to applying power to the network devices.

5. Program the system for the desired operation usingDet-Tronics configuration software. Refer to

software manual, form number 95-8479-02.Download configuration data to all devices.

NOTE After system configuration has been completed,the entire system should be tested for proper

operation to ensure that configuration was performed properly.

6. Calibrate the sensors.

7. Ensure that all trouble and alarm conditions have

been cleared and the LCU reset, then removemechanical blocking devices (if used) and restore

power to the output loads.

CALIBRATION

To ensure optimum performance, calibration must be

performed on a regularly scheduled basis. Since eachapplication is different, the length of time between

regularly scheduled recalibrations can vary from oneinstallation to the next. In general, the more frequently a

system is checked, the greater the reliability.

IMPORTANT 4 to 20 ma devices not manufactured by Det- Tronics must be pre-cal ibrated. To ensure

adequate protection, calibration must be performed on a regularly scheduled basis.

NOTE The calibration will be aborted and the detector will

revert back to the previous calibration values if the calibration is not completed within 12 minutes. The

red LED will blink. The calibration will be logged as aborted.

NOTE The “Sensor Replacement” calibration procedure

must be used for the initial calibration of a new sensor. The “Routine Calibration” procedure can

then be used for all subsequent calibrations.

NOTE

Some calibration procedures require the operator to activate the reed switch located on a circuit

board inside the junction box. See Figure IX-1 for the location of the reed switch. To activate the

reed switch, hold the calibration magnet against the side of the junction box near the switch location

approximately one inch above the mounting surface. (Do not open the junction box.) Hold the calibration magnet in place for about 4 seconds to

initiate steps of the calibration procedure.

CALIBRATION ALGORITHM A

FOR MANUAL CALIBRATION OF UNIVERSAL DCU

Normal Calibration

1. Activate the reed switch. The red LED blinks at a 2Hz rate while the reed switch is closed.

2. After the reed switch has been closed for 3

seconds, the calibrate LED on the communicationmodule flashes at a 1 Hz rate, indicating that it isready for the zero input.

3. Apply the zero input (4 ma).

IX-2

Page 84: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 84/128

IX-3 95-8470

4. Activate the reed switch. The red LED will blink at a2 Hz rate for 3 seconds while the reed switch is

closed.

5. After the reed switch has been closed for 3

seconds, the communication module records theuncalibrated value in the calibration log and

calibrates the zero value. The calibrate LED goeson steady.

6. Apply the calibration gas.

7. The calibrate LED blinks at a 1 Hz rate when theinput increases.

8. Activate the reed switch. The red LED blinks at a 2

Hz rate while the reed switch is closed.

9. The communicat ion module records the

uncalibrated value in the calibration log andcalibrates the span value after the reed switch is on

for 3 seconds.

10. The calibrate LED goes on steady.

11. Remove the span gas and return the analog input to

normal.

12. Activate the reed switch. The red LED blinks at a 2Hz rate for 3 seconds while the reed switch is

closed.

13. The calibration is complete. The calibrate LEDturns off.

If the calibration is not completed within 12 minutes, theprevious calibration values are restored and the

calibration is logged as aborted. The calibrate LEDflashes at a 4 Hz rate.

Sensor Replacement

WARNING The hazardous area must be de-classified prior to

removing a junction box cover with power applied.

1. Open the junction box cover and press the sensorreplacement switch.

2. The calibrate LED on the communication moduleflashes at a 1 Hz rate, indicating it is ready for the

zero input.

3. Replace the sensor and apply the zero input (4 ma).

4. Activate the reed switch. The red LED blinks at a 2Hz rate for 3 seconds while the reed switch is

closed.

5. The communicat ion module records the

uncalibrated value in position one of the calibrationlog and calibrates the zero value. The calibrate

LED goes on steady.

6. Apply the calibration gas.

7. The calibrate LED blinks at a 1 Hz rate when the

input increases.

8. Activate the reed switch. The red LED blinks at a 2Hz rate for 3 seconds while the reed switch is

closed.

9. The communicat ion module records the

uncalibrated value in the first register of thecalibration log and calibrates the span value.

10. The calibrate LED goes on steady.

11. Remove the span gas and return the analog input tonormal.

12. Activate the reed switch. The red LED blinks at a 2

Hz rate for 3 seconds while the reed switch isclosed.

13. The calibration is complete. The calibrate LEDturns off.

GND

9 1 0

7 8

5 6

3 4

1 2

1 3 1 4

1 1 1 2

A1881

MAGNETIC REED SWITCH *

* TO ACTIVATE THE MAGNETIC REED SWITCH,HOLD THE CALIBRATION MAGNET AGAINST THE SIDE OF THE ENCLOSUREAT THE LOCATION OF THE REED SWITCH,APPROXIMATELY ONE INCH ABOVE THE MOUNTING SURFACE.

S W

1

Figure IX–1—DCU Terminal Wiring Board Mounted

in Six-Port Junction Box

Page 85: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 85/128

IX-4

Pressing the sensor replacement switch aborts thecalibration and starts over. Resetting the

communication module will abort sensor replacement.

CALIBRATION ALGORITHM C

FOR COMBUSTIBLE GAS DCUs AND

AUTOMATIC CALIBRATION OF UNIVERSAL DCUs

NOTE After exposure of the H 2 S sensor to high concentrations of gas, it is recommended that it be

exposed to fresh air for at least 30 minutes and then re-calibrated.

Routine Calibration

1. Apply the zero gas.

2. Activate the reed switch for at least 4 seconds. The

red LED blinks at a 2 Hz rate for 3 seconds whilethe reed switch is activated.

3. The calibrate LED on the communication moduleblinks at a 1 Hz rate, indicating it is ready for the

zero input.

4. Wait unt il the cal ibrate LED goes on steady(approximately 4 seconds). The communicationmodule records the uncalibrated value in the

calibration log and calibrates the zero value duringthis time.

5. Apply the calibration gas. The calibrate LED blinks

at a 1 Hz rate when the sensor detects gas.

6. When the sensor input has been stable for 30

seconds, the communication module records theuncalibrated value in the calibration log and

calibrates the span value.

7. The calibrate LED goes on steady.

8. Remove the calibration gas.

9. The communication module waits until the sensor

input drops below 4% full scale.

10. The calibration is complete. The calibrate LEDturns off.

NOTE If the cal ibrat ion is not completed within 12

minutes, the calibration will be aborted and the detector will revert back to the previous calibration values. The red LED will blink at a 4 Hz rate. The

calibration will be logged as aborted.

Sensor Replacement — Combustible Gas

NOTE When replacing a sensor, compare part numbers

to be sure that the correct replacement sensor is being used.

WARNING

The hazardous area must be de-classified prior to

removing a junction box cover with power applied.

1. Remove the cover from the DCU enclosure.

2. Press the sensor replacement switch on thecommunication module for about 1 second. The

calibrate LED on the communication module blinksat a 1 Hz rate, indicating that it is ready for the zero

input.

NOTE

Pressing the sensor replacement switch prevents the communication module from generating a fault

signal when the input drops to zero due to removing the sensor. In addition, the calibration will not be aborted if the calibration procedure is

not completed within 12 minutes.

3. Place the calibration switch on the transmitter boardin the “calibrate” position.

4. Replace the sensor.

5. Connect a volt meter to the test points on the

transmitter board. Connect the “+” lead to TP1(red). Connect the “–” lead to TP2 (black).

6. Wait at least 5 minutes for the sensor output tostabilize, then adjust R2 for a reading of 0.40 vdc (4

ma) on the meter.

NOTE

Do not make adjustments to R1 when calibrating the sensor.

7. Place the calibrate switch on the transmitter board

in the “normal” position.

8. Activate the reed switch for 4 seconds. The redLED blinks at a 2 Hz rate for 3 seconds while the

reed switch is activated. The communicationmodule records the uncalibrated value in positionone of the calibration log and calibrates the zero

value. The calibrate LED goes on steady.

9. Place the calibration switch on the transmitter boardin the “calibrate” position.

Page 86: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 86/128

10. Apply the calibration gas and wait for the output tostabilize.

11. With 50% LFL calibration gas applied to the sensor,adjust R3 for a reading of 1.2 vdc (12 ma) on the

meter.

12. Place the calibrate switch on the transmitter boardin the “normal” position. The red LED blinks at a 1

Hz rate.

13. Activate the reed switch. The red LED blinks at a 2

Hz rate for 3 seconds while the reed switch isactivated.

14. The communication module records the

uncalibrated value in the first register of thecalibration log and calibrates the span value. Thecalibrate LED goes on steady.

15. Remove the calibration gas and place the cover

back on the DCU enclosure.

16. The communication module waits until the analogvalue drops below 4% full scale. The calibration is

complete. The calibrate LED turns off.

Pressing the sensor replacement switch aborts the

calibration and starts over.

Sensor Replacement — Toxic Gas

NOTE

When replacing a sensor, compare part numbers to be sure that the correct replacement sensor is

being used.

WARNING The hazardous area must be de-classified prior to removing a junction box cover with power applied.

1. Remove the cover from the DCU enclosure.

2. Press the sensor replacement switch on the

communication module for about 1 second. Thecalibrate LED on the communication module blinks

at a 1 Hz rate, indicating that it is ready for the zeroinput.

NOTE Pressing the sensor replacement switch prevents the communication module from generating a fault

signal when the input drops to zero due to removing the sensor. In addition, the calibration

will not be aborted if the calibration procedure is not completed within 12 minutes.

3. Replace the sensor.

4. Wait at least 5 minutes for the sensor output tostabilize.

5. Activate the reed switch. The red LED blinks at a 2Hz rate for 3 seconds while the reed switch is

activated. The communication module records theuncalibrated value in position one of the calibration

log and calibrates the zero value. The calibrateLED goes on steady.

6. Apply the calibration gas. The calibrate LED blinksat a 1 Hz rate when the input increases.

7. Activate the reed switch. The red LED blinks at a 2

Hz rate for 3 seconds while the reed switch isactivated.

8. The communicat ion module records theuncalibrated value in the first register of the

calibration log and calibrates the span value. The

calibrate LED goes on steady.

9. Remove the calibration gas and place the cover

back on the DCU enclosure.

10. The communication module waits until the analog

value drops below 4% full scale. The calibration iscomplete. The calibrate LED turns off.

Pressing the sensor replacement switch aborts the

calibration and starts over.

CALIBRATION ALGORITHM D

FOR UNIVERSAL DCUs WITH O2 SENSOR

Normal Calibration

1. Apply clean air (20.9% oxygen).

2. Activate the reed switch for at least 4 seconds. Thered LED blinks at a 2 Hz rate for 3 seconds while

the reed switch is closed.

3. The calibrate LED blinks at a 1 Hz rate, indicating

that calibration has begun.

4. The communication module waits 3 seconds.

5. The communicat ion module records theuncalibrated value in the calibration log and

calibrates the span value.

6. The calibrate LED goes on steady.

IX-5 95-8470

Page 87: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 87/128

7. The communication module waits 3 seconds.

8. The calibration is complete. The calibrate LEDturns off.

Sensor Replacement

WARNING The hazardous area must be de-classified prior to

removing a junction box cover with power applied.

1. Open the junction box cover and press the sensor

replacement switch.

2. The calibrate LED on the communication moduleblinks at a 1 Hz rate, indicating that it is ready for

the zero input.

3. Replace the sensor and set the sensor switch

(located on the sensor cell) to zero.

4. Activate the reed switch. The red LED blinks at a 2

Hz rate for 3 seconds while the reed switch isclosed.

5. The communicat ion module records theuncalibrated value in position one of the calibrationlog and calibrates the zero value. The calibrate

LED is on steady.

6. Set the zero switch on the sensor to normal. Applyclean air (20.9% oxygen) to set the sensor analog

span value.

7. The calibrate LED blinks at a 1 Hz rate when the

input goes high.

8. Activate the reed switch. The red LED blinks at a 2Hz rate for 3 seconds while the reed switch is

closed.

9. The communicat ion module records the

uncalibrated value in the first register of thecalibration log and calibrates the span value.

10. The calibration is complete. The calibrate LED

turns off.

Pressing the sensor replacement switch aborts the

calibration and starts over.

CALIBRATION ALGORITHM G

FOR DCUs WITH POINTWATCH

Routine Calibration

1. Apply the zero gas.

2. Activate the reed switch for at least 4 seconds. Thered LED blinks at a 2 Hz rate for 3 seconds while

the reed switch is activated.

3. The calibrate LED on the communication module

blinks at a 1 Hz rate, indicating it is ready for thezero input.

4. When a steady zero reading is obtained, thecommunication module records the uncalibrated

value in the calibration log and calibrates the zerovalue during this time. The LED turns on steady.

5. Apply the calibration gas. The calibrate LED blinks

at a 1 Hz rate when the sensor detects gas.

6. When the sensor input has been stable for 30

seconds, the communication module records theuncalibrated value in the calibration log and

calibrates the span value.

7. The calibrate LED goes on steady.

8. Remove the calibration gas.

9. The communication module waits until the sensor

input drops below 4% full scale.

10. The calibration is complete. The calibrate LEDturns off.

NOTE If the cal ibrat ion is not completed within 12 minutes, the calibration will be aborted and the

detector will revert back to the previous calibration values. The red LED will blink at a 4 Hz rate. The

calibration will be logged as aborted.

Sensor Replacement

WARNING The hazardous area must be de-classified prior to removing a junction box cover with power applied.

1. Remove power from the DCU and the PointWatch

unit. Replace the PointWatch. Apply power, thenpress the sensor replacement switch on the

communication module for about 1 second. Allowat least 10 minutes for the sensor to warm up.

IX-6

Page 88: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 88/128

NOTE

Pressing the sensor replacement switch prevents the communication module from generating a fault signal when the input drops to zero. In addition,

the calibration will not be aborted if the calibration procedure is not completed within 12 minutes.

2. Apply zero gas.

3. The calibrate LED on the communication moduleblinks at a 1 Hz rate, indicating that it is ready forthe zero input.

4. Continue from step 4 of the PointWatch routinecalibration procedure described above.

UV DETECTOR TEST

CAUTION

To prevent unwanted actuation, alarm and extinguishing devices must be disconnected prior

to performing detection system tests.

FIRE ALARM TEST

1. Disable any ext inguishing equipment that isconnected to the system.

2. Apply input power to the system. Allow a one

second power-up delay.

3. Hold a UV source (W8066) within the cone of visionof the detector at a distance relative to the selected

detection range. Verify that an alarm condition isindicated at the LCU. Reset the alarm indicationusing the key switch on the LCU.

Lack of response may indicate reduced sensitivitydue to contamination on the viewing window, a

damaged sensor, or electronic circuitry or wiringproblems. Refer to “Troubleshooting” for additional

information.

4. Repeat this test for each fire detector in the system.

5. Verify that all detectors are properly aimed at the

area to be protected.

6. Enable extinguishing equipment when the test iscomplete.

FALSE ALARM TEST

1. Disable all alarm response equipment.

2. Allow the system to monitor the protected area for a

period of time with all the normal operations in thearea taking place. If the detector responds(indicating a fire when no fire has occurred), check

the area to see if UV sources are present. If

possible, remove the sources, or reposition thedetectors so that the sources fall outside of thedetector’s cone of vision. If problems still occur,

adjust the time delay, sensitivity or arc rejectionsettings.

The model U7656 Hand-Held UV Monitor isavailable from Detector Electronics for conveniently

scanning the protected area and pin-pointing theexact source of UV radiation.

3. Recycle power and test again as described above.

4. Once the correct settings are obtained, turn on allalarm and extinguishing equipment that is

connected to the system. Record all switch settingsfor future reference.

UV/IR DETECTOR TEST

IMPORTANT Disable any extinguishing equipment that is

connected to the system to prevent unwanted actuation.

The detector can be tested by shining a UV/IR test lamp(W867 or W8067) into the detector viewing windows orby a live fire. (Refer to the test lamp manual for specific

instructions regarding proper use of the device.) Thiswill cause the detector to go into an alarm condition —the LEDs on the UV sensor will be on steady and the

LCU will indicate an alarm condition. If latchingoperation is selected, the detector will remain in this

condition until it is reset at the OIS. If non-latchingoperation is selected, the detector will return to normal

operation as soon as the test is terminated (the testlamp or fire source is removed).

If a fire signal was not generated and the LEDs indicateresponse by only one sensor, the other sensor has

failed to respond.— Check the cleanliness of the viewing window and

repeat the test.— If the sensor fails to respond again, replace the

sensor module.

— If the sensor still does not respond, replace thedetector.

IX-7 95-8470

Page 89: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 89/128

If a fire signal was not generated and the LEDs indicateresponse by neither sensor, both sensors have failed to

respond.— Check input power and external wiring.— Check the cleanliness of both viewing windows.

— If the detector still does not respond:— If using a test lamp, check the battery, window, etc.

to be sure that the test lamp is working properly.— If the detector still does not respond, replace the

detector.

MANUAL oi

When manual oi is selected, the automatically initiated

oi test is disabled.

Regardless of the oi selection, internal diagnosticcircuitry will respond to failures such as a loss of inputpower or to certain electronic failures. These failures

will be indicated at the LCU and also by the detector’sLEDs. If such a failure occurs, check the operation of

the power source and the continuity of the detector

wiring. If the detector appears to be “dead” with powerapplied, it must be returned to the factory for repair.

AUTOMATIC oi

The Automatic oi feature (if selected) tests the detector

at the selected interval (once per minute for UV andfrom once a minute to once every four hours for IR),

checking the cleanliness of the optical surfaces, sensorsensitivity, and proper functioning of the electronic

circuitry. If a problem is detected for three consecutiveautomatic oi tests, a fault signal is generated at theLCU (also indicated by the UV sensor LEDs). If the

detector passes three subsequent automatic oi tests,the fault signal will be cleared

UV Fault

To correct a UV oi fault, clean the viewing window and

oi ring of the UV sensor, and also check the oi ring

opening for proper orientation. If the fault does notclear (or fault reoccurs), a faulty sensor or electrical

problem is indicated. First replace the UV sensormodule. If the problem persists, replace the detector.

IR Fault

To correct an IR oi fault, clean the viewing window and

oi ring of the IR sensor, and also check the module and

oi ring opening for proper orientation. If the fault does

not clear (fault reoccurs), a faulty sensor or electricalproblem is indicated. Check the connection of theconnector plug on the IR module. Also check the

condition of the wires. Repair or replace if needed. If

the problem persists, replace the IR sensor module. Ifthe problem still persists, replace the detector.

General Fault

If a general fault is indicated, check input power to the

detector as well as continuity of system wiring. Alsocheck the detector viewing windows for contamination

such as paint overspray, snow, etc. that couldsimultaneously affect both sensors. Since simultaneous

failure of both sensor modules is unlikely, the problem ismost likely caused by loss of input power or failure ofthe detector’s electronic circuitry.

Background Radiation

Background radiation as such does not cause a

problem with the detector in most applications, unlessboth UV and flickering IR non-fire radiation sourcesoccur simultaneously. If a UV or IR background

radiation indication occurs:— Determine its cause. The presence of background

radiation could indicate a problem in the protectedarea. For example, background IR could be

caused by overheating equipment.— Determine whether or not repositioning the detector

could eliminate response to the backgroundradiation without reducing coverage of thehazardous area.

IX-8

Page 90: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 90/128

Section XSpecifications

CERTIFICATIONSFMRC Approval – See Appendix A.

CSA Certification – See Appendix B.CENELEC and CE Mark – See Appendix C.

EQ2100LCU LOCAL CONTROL UNITINPUT VOLTAGE—18 to 30 vdc. 10% overvoltage will not cause damage

to the equipment.

INPUT CURRENT—

EQ2100LCU: 0.4 ampere maximum.EQ2101LCU: 12 amperes maximum.

OUTPUT CURRENT (EQ2101LCU ONLY)—

System: 2.8 amperes maximum(ground fault monitored)

1.8 amperes standby current2.8 amperes alarm current

Auxiliary: 8.0 amperes maximum(input power to LIOU auxiliary).

RELAY OUTPUT RATING—5 amperes resistive at 30 vdc.

I/O PORTS—

The LCU provides two electrically isolated RS-232 serialports, port “1” and port “2,” both of which can be active

simultaneously. Port “1” can be configured as either aModbus RTU slave, or an Allen Bradley DF1 slave. Port

“2” can be either a Modbus RTU slave or master.

Two 78.5 kb LON/SLC ports provide the start and end of

the communication loop for the detection devices. Thewiring is transformer coupled to protect thetransceivers. The LON/SLC is monitored for ground

faults.

TEMPERATURE RANGE—

Operating: +32°F to +140°F (0°C to +60°C).

Storage: –67°F to +185°F (–55°C to +85°C).

HUMIDITY RANGE—

0 to 95% RH, non-condensing.

VIBRATION—

Meets MIL SPEC 810C, method 514.2, curve AW.

DIMENSIONS—See Figure X-1A for dimensions of the standard LCU

mounting configuration. The LCU can also be housedin a 19 inch mounting rack (000840-xxx), with any

combination of up to 4 logic controllers, 4 gateways andone isolation module. See Figure X-1B for dimensions.

X-1 95-8470

A1882

9.24 (23.5) 1.48 (3.8) 10.86 (27.6)

10.26 (26.1)

8.68 (22.0)

4.00(10.2)

6.97(17.7)

6.50(16.5)

12.25(31.1)

Figure X–1A—Dimensions of LCU in Inches (Centimeters)

Page 91: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 91/128

X-2

POWER

ALARM

TROUBLE

POWER FAULT

SUPERVISORY

EAGLE QUANTUM™LOGIC CONTROLLER

ACKNOWLEGDE

SILENCE

PROGRAM

ISOLATE

NORMAL

ACKNOWLEDGE& SILENCE

ENABLE

ISOLATE

RESET

DET-TRONICS®

RELAY 1100

90

80

70

60

50

40

30

20

10

RELAY 2

RELAY 3

RELAY 4

FAULT

RESET

EAGLE QUANTUM™GATEWAY

DET-TRONICS®

LON INSOLATOR

EAGLE QUANTUM™LON ISOLATOR

GROUND FAULT

GROUND FAULT

POWER –

POWER +

COM 2

COM 1

DET-TRONICS®

SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8

13.2(33.5)

4.0(10.2)

7.0(17.7)

19.0(48.3)

B2044

FRONT

FRONT

REAR

TERMINALSTRIP

Figure X–1B—Dimensions of Model 000840-XXX LCU in Inches (Centimeters)

Page 92: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 92/128

EQ2200IDC/IDCGF/IDCSC

INITIATING DEVICE CIRCUIT

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 vdc. 10% overvoltage will notcause damage to the equipment.

INPUT POWER—

4.0 watts maximum.

INPUTS—

Two supervised non-incendive digital inputs (sealed or

unsealed switch or relay contacts). 10 kohm EOLresistors are required.

OUTPUTS—Digital communication, transformer isolated (78.5 kbps).

TEMPERATURE RANGE—

Operating: –40°F to +167°F (–40°C to +75°C).Storage: –-67°F to +185°F (–55°C to +85°C).

HUMIDITY RANGE—0 to 95% RH, non-condensing.

VIBRATION—

Meets MIL SPEC 810C, method 514.2, curve AW.

DIMENSIONS—

See Figure X-2.

EQ2200UV and EQ2200UVHT UVFLAME DETECTORS

INPUT VOLTAGE—24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not

cause damage to the equipment.

INPUT POWER—

2.0 watts typical, 4.0 watts maximum during oi test.

TEMPERATURE RANGE—

EQ2200UVOperating: –40°F to +167°F (–40°C to +75°C).

Storage: –67°F to +185°F (–55°C to +85°C).

EQ2200UVHT

Electronic Module: –40°F to +167°F (–40°C to +75°C).UV Detector: –40°F to +257°F (–40°C to +125°C).

Storage: –67°F to +185°F (–55°C to +85°C).

HUMIDITY RANGE—

0 to 95% relative humidity, can withstand 100%

condensing humidity for short periods of time.

SPECTRAL SENSITIVITY RANGE—

UV radiation over the wavelength of 1850 to 2450angstroms (solar blind).

CONE OF VISION—

The detector has a 90 degree cone of vision with thehighest sensitivity lying along its central axis. SeeFigure X-3.

X-3 95-8470

0.32 (0.81) OVAL SLOT MOUNTING(TYPICAL FOUR PLACES)

3.4(8.6)

4.7(11.8)

5.2(13.2)

0.28(0.71)

2.7(6.8)

B2045

6.6(16.8)

1.28(3.25)

Figure X–2—Dimensions of Tall Cover Junction Boxin Inches (Centimeters)

0°15°

30°

45°

15°

30°

45°

D573

100

90

80

70

60

50

40

30

20

10

DETECTIONDISTANCE(PERCENT)

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE.THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES.

Figure X–3—Cone of Vision of UV Detector

Page 93: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 93/128

X-4

FLAME SENSITIVITY—

The detector has four adjustable sensitivity settings plustransient arc rejection capabilities.

RESPONSE TIME—

The detector is selectable for a 0 to 7 second timedelay.

OUTPUTS—

Digital communication, transformer isolated (78.5 kbps).

SEPARATION DISTANCE (EQ2200UVHT only)—

Maximum separation distance between the UV detectorand the electronic module is 165 feet (50 meters).

VIBRATION—Meets MIL SPEC 810C, method 514.2, curve AW.

DIMENSIONS—

See Figures X-4A and X–4B for the standard UVdetector. For the high temperature UV detector, seeFigures X-5A and X-5B (UV detector) and Figure X-6

(electronic module).

5.25 (13.3)

2.5 (6.4)

MOUNTING BASE

1/2 INCH NUT USED TO ADJUSTELBOW TO DESIRED ANGLE

1-3/8 INCH NUT USED TO ROTATESWIVEL/DETECTOR ASSEMBLYTO DESIRED POSITION

3/4 INCH NUT USED TO SECUREDETECTOR TO SWIVEL MOUNT

DETECTOR SCREWS ONTOSWIVEL MOUNT HERE

A1886 2.5 (6.4) DIA.

0.25 (.64) (3)

120° ± 2° (2)

2.0 (5.0) DIA.

Figure X–4A—Dimensions of Optional Swivel Assemblyin Inches (Centimeters)

Figure X–5A—Q9001B Swivel Mounting Bracket Dimensions

in Inches (Centimeters)

5/16-18 UNC

1 3/8 INCH GLAND NUTUSED TO ROTATESWIVEL/DETECTOR ASSEMBLYTO DESIRED POSITION

MOUNTING BASE

DETECTOR LOCK NUT

120° ±2° (2)

2.0 (5.08) DIA.

2.5 (6.4) DIA. 0.25 (0.64) DIA. (3)

2.5(6.4)

2.5(6.4)

A1986

Figure X–5B—UV Detector Dimensions

in Inches (Centimeters)

4.75 (12.06)

2.5(6.35)

1/2 INCH NPTOR 20 MM

A1987

Page 94: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 94/128

X-5 95-8470

COVER LOCKING CLAMPS (BASEEFA)

4.5 (114.3)

4.375(111.1)

4(101.6)

5(127)

2.5(63.5)

9 (228.6)

A1844

CONDUIT/CABLE ENTRY (2)

Figure X–4B—Dimensions of EQ2200UV Detector in Inches (Millimeters)

0.32 (0.81) OVAL SLOT MOUNTING(TYPICAL FOUR PLACES)

3.39(8.6)

4.66(11.8)

5.20(13.21)

0.28(0.71)

2.69(6.83)

A1887

6.62(16.8)

1.28(3.25)

Figure X–6— EQ2200UVHT Junction Box Dimensions

in Inches (Centimeters)

Page 95: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 95/128

X-6

EQ2200UVIR UV/IR DETECTOR

INPUT VOLTAGE—

24 vdc nominal, 18 to 30 Vdc. 10% overvoltage will notcause damage to the equipment.

INPUT POWER—

2.0 watts nominal, 5.0 watts maximum during oi test.

TEMPERATURE RANGE—Operating: –40°F to +167°F (–40°C to +75°C).Storage: –40°F to +185°F (–40°C to +85°C).

HUMIDITY RANGE—

0 to 95% RH. Can withstand 100% condensinghumidity for short periods of time.

SPECTRAL SENSITIVITY RANGE—UV: 0.185 to 0.245 microns (solar blind).

IR: 4.45 microns (solar blind).

Figure X-7 illustrates the spectral response range of the

UV and IR sensors.

CONE OF VISION—

90 degree cone of vision using gasoline fuel (1 sq. ft).

80 degree cone of vision using methane fuel (30 inch).See Figure X-8.

FLAME SENSITIVITY—Refer to Tables X-1 and X-2 for typical detector

response characteristics.

CAUTION

The detector is extremely sensitive when the very

high setting is util ized. While this setting is required to reliably detect certain types of fires,care must be taken to minimize the possibility of

false alarms.

RESPONSE TIME—

Selectable for a 0 to 7 second time delay. Fastestresponse time is 0.5 second.

OUTPUTS—

Digital communication, transformer isolated (78.5 kbps).

VIBRATION—Meets MIL SPEC 810C, method 514.2, curve AW.

ENCLOSURE MATERIAL—

Copper-free aluminum (red) or 316 stainless steel, withstainless steel mounting bracket.

DIMENSIONS—See Figures X-9 and X-10.

5.04.03.02.01.51.00.90.80.70.60.50.40.30.20.1

ATMOSPHERICTRANSMISSION

WAVELENGTH (MICRONS)

SOLARRADIATIONREACHINGTHE EARTH

INFRAREDSENSOR

RESPONSE

VISIBLE INFRARED

ULTRAVIOLETSENSOR

RESPONSE

ULTRAVIOLET

100

75

50

25

0

A1070

Figure X–7—Sensitivity Range of UV/IR Detector

0°15°

30°

45°

15°

30°

45°

D573

100

90

80

70

60

50

40

30

20

10

DETECTIONDISTANCE(PERCENT)

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE.THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES.

Figure X–8—Cone of Vision of UV/IR Detector

Page 96: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 96/128

X-7 95-8470

Table X–1—UV/IR Detector Maximum Response Distances in Feet

Table X–2—Recommended Settings for JP-4, 5, 8 Fires

Sensitivity Arc Rejection 30 inch Methane 1 Ft x 1 Ft Gasoline 1 Ft x 1 Ft Methanol

UV Standard Low 40 30 15

Medium 60 45 20

High 80 65 35

Very High 100 100 55

UV Arc Low Medium 35 30 10

Rejection Low High 35 30 10

Medium Medium 55 40 15

Medium High 55 40 15

High Medium 60 50 25

High High 65 50 25

Very High Medium 85 65 50

Very High High 85 65 50

IR Low 40 65 40

Medium 55 75 45

High 65 90 55Very High 90 100 60

Typical response time less than 5 seconds.

NOTE: Sensitivity level determines maximum response distance and is selected for UV and IR sensors individually (selectedthrough the configuration software). The maximum response distance for the UV/IR detector is the lesser of the two.

Fuel Size Distance UV IR

JP4 3 Ft x 3 Ft 150 Ft. Very High High

JP5 3 Ft x 3 Ft 150 Ft. High High

JP8 3 Ft x 3 Ft 150 Ft. Very High Medium

JP4 2 Ft x 2 Ft 100 Ft. High Medium

JP5 2 Ft x 2 Ft 100 Ft. High Medium

JP8 2 Ft x 2 Ft 100 Ft. High Medium

Typical response time less than 5 seconds.

Page 97: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 97/128

X-8

5-1/4 INCHES

(133 MM)

2-1/2 INCHES(64 MM)

MOUNTING BASE

1/2 INCH NUT USED TO ADJUSTELBOW TO DESIRED ANGLE

1-3/8 INCH NUT USED TO ROTATESWIVEL/DETECTOR ASSEMBLYTO DESIRED POSITION

3/4 INCH NUT USED TOSECURE DETECTORBRACKET TO SWIVEL MOUNT

JUNCTION BOX MOUNTINGBRACKET (ATTACHESWITH TWO ENCLOSEDFLATHEAD SCREWS)

2 –1/2 (64 MM) DIA.

0.25 (6.4 MM)DIA. (3)

120° ± 2° (2)

2.00 (50.8 MM) DIA.

B1303

B1303

Figure X–9—Q9001G Swivel Mounting Bracket Dimensions

C1047

3.38 (85.8 MM) 7.11 (181 MM)

7.81(198 MM)

2.5 DIA.(64 MM)

5.25(133 MM)

CONDUIT ENTRY 3/4 NPT OR 25 MM

Figure X–10—UV/IR Detector Dimensions in Inches (Millimeters)

Page 98: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 98/128

EQ2200DCU AND EQ2200DCUEXDIGITAL COMMUNICATION UNIT

INPUT VOLTAGE—24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not

cause damage to the equipment.

POWER CONSUMPTION—

DCU with toxic gas sensor/transmitter:

95 ma maximum.

DCU with transmitter and combustible gas sensor:

180 ma maximum during normal operation, 500 maduring startup.

INPUTS—

4 to 20 ma analog signal.Non-intrusive calibration.

OUTPUTS—Digital communication, transformer isolated (78.5 kbps).

TEMPERATURE RANGE—Operating: –40°F to +167°F (–40°C to +75°C).Storage: –67°F to +185°F (–55°C to +85°C).

HUMIDITY RANGE—0 to 95% RH, non-condensing.

VIBRATION—

Meets MIL SPEC 810C, method 514.2, curve AW.

DIMENSIONS—

See Figure X-2.

EQ2500ARM AGENT RELEASEMODULE

RELEASE OUTPUT RATING—2 amperes at 30 vdc maximum.

SUPERVISORY CURRENT—

2.0 ma, ±1.0 ma each circuit.

INPUT VOLTAGE—24 vdc nominal.

INPUT CURRENT—Standby: 75 ma maximum at 24 vdc.

Alarm: 120 ma maximum at 24 vdc.

STATUS OUTPUTS—

Digital communication, transformer isolated (78.5 kbps).

TEMPERATURE RANGE—Operating: –40°F to +167°F (–40°C to +75°C).

Storage: –67°F to +185°F (–55°C to +85°C).

HUMIDITY RANGE—

5 to 95% RH, non-condensing.

VIBRATION—Meets MIL SPEC 810C, method 514.2, curve AW.

DIMENSIONS—

See Figure X-2.

X-9 95-8470

Page 99: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 99/128

EQ2500SAM SIGNAL AUDIBLEMODULE

OUTPUT RATING—

2 amperes at 30 vdc maximum.

RESPONSE TIME—Output relay actuates in <0.1 second after

acknowledging an alarm command message.

SUPERVISORY CURRENT—

3.0 ma ± 2.0ma, each circuit.

EOL RESISTORS —10 kohm ± 2 kohm. Each circuit must have an EOL

resistor.

INPUT VOLTAGE—

24 vdc nominal.

INPUT CURRENT (Excluding Output Current)—Standby: 60 ma maximum at 24 vdc.

Alarm: 120 ma maximum at 24 vdc.

STATUS OUTPUT—

Digital communication, transformer isolated (78.5 kbps).

TEMPERATURE RANGE—Operating: –40°F to +167°F (–40°C to +75°C).

Storage: –67°F to +185°F (–55°C to +85°C).

HUMIDITY RANGE—

5 to 95% RH, non-condensing.

VIBRATION—

Meets MIL SPEC 810C, method 514.2, curve AW.

DIMENSIONS—

See Figure X-2.

EQ2400NE NETWORK EXTENDER

INPUT VOLTAGE—

18 to 30 Vdc.

POWER CONSUMPTION—

2.2 watts nominal at 24 vdc, 2.7 watts maximum.

INPUTS/OUTPUTS—

Digital, transformer isolated (78.5k Baud).

TEMPERATURE RANGE—

Operating: -40°F to +167°F (-40°C to +75°C)Storage: -67°F to +185°F (-55°C to +85°C).

HUMIDITY—

5 to 95% RH at 70°C.

DIMENSIONS—

See Figure X-11.

X-10

A1883

0.32 (0.81) OVAL SLOT MOUNTING(TYPICAL FOUR PLACES)

3.39(8.6)

4.66

(11.8)

3.7(9.4)

5.20(13.21)

0.28

(0.71)

2.69(6.83)

1.28(3.25)

Figure X–11—Dimensions of Short Cover Junction Boxin Inches (Centimeters)

Page 100: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 100/128

EQ2100PSM POWER SUPPLYMONITOR

INPUT VOLTAGE—24 vdc nominal, 18 to 30 Vdc.

POWER CONSUMPTION—

2.0 watts maximum.

MEASUREMENT RANGE—AC Voltage: 240 vac maximum.

DC Battery Charging Current: 75 amperes maximum.

OUTPUT—

Digital communication, transformer isolated (78.5 kbps).

TEMPERATURE RANGE—

Operating: +32°F to +122°F (0°C to +50°C)Storage: -67°F to +185°F (-55°C to +85°C).

HUMIDITY RANGE—5 to 95% RH, non-condensing.

DIMENSIONS—

See Figure X-12.

EQ2110PS, EQ2130PS ANDEQ2175PS POWER SUPPLIES

INPUT VOLTAGE—Selectable for 120, 208 or 240 vac input power, ±10%.

INPUT FREQUENCY—

60 Hz ±5% standard, 50 Hz ±5% optional.

INPUT CURRENT—EQ2110PS: 4 amps at 120 VAC (60 Hz)EQ2130PS: 11 / 6 / 6 amps at 120 / 208 / 240 VAC*

EQ2175PS: 24 / 15 / 12 amps at 120 / 208 / 240 VAC*.*Specify 50 Hz or 60 Hz.

OUTPUT CURRENT—

EQ2110PS: 10 amperes at 24 VDCEQ2130PS: 30 amperes at 24 VDCEQ2175PS: 75 amperes at 24 VDC.

POWER CONSUMPTION—

EQ2110PS: 46 Watts

EQ2130PS: 140 WattsEQ2175PS: 349 Watts.

TEMPERATURE RANGE—

Operating: +32°F to +122°F (0°C to +50°C)Storage: -40°F to +185°F (-40°C to +85°C).

HUMIDITY RANGE—

5 to 95% RH, non-condensing.

DIMENSIONS—

in Inches (Centimeters)Width Height Depth

EQ2110PS: 19 (48.3) 7 (17.8) 15 (38.1)EQ2130PS: 19 (48.3) 14 (35.6) 15 (38.1)

EQ2175PS: 19 (48.3) 14 (35.6) 15 (38.1)

NOTE

Power supplies are designed for mounting in a standard 19 inch rack. Optional mounting hardware is available for floor or wall mount applications.

X-11 95-8470

B C

J1 J3

4(10.2)

8.5(21.6)

9(22.9)

2.5(6.4)

2.25

(5.7)

A2038

Figure X–12—Dimensions of Power Supply Monitor

in Inches (Centimeters)

Page 101: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 101/128

LIOU (Local Output Unit)

INPUT VOLTAGE—

24 vdc nominal.

INPUT POWER—

30 watts maximum.

MODULES PER SYSTEM—

24 maximum.

TEMPERATURE RATING—

Operating: +32°F to +120°F (0°C to +50°C).Storage: –67°F to +185°F (–55°C to +85°C).

HUMIDITY RANGE—

0 to 95% RH, non-condensing.

VIBRATION—

Meets FMRC Class number 3260 requirements.

DIMENSIONS—

See Figures X-13 and X-14.

LIOU RELAY MODULE

CONTACT RATING—

2 amperes at 24 vdc.

MODULES PER SYSTEM—

8 maximum.

OUTPUTS PER SYSTEM—32 maximum.

LIOU RELEASE MODULE

RELEASE OUTPUT RATING—

2 amperes at 24 vdc.

SUPERVISORY CURRENT—

2.5 ma, each circuit.

SIGNAL OUTPUT RATING—

2 amperes at 24 vdc.

MODULES PER SYSTEM—

8 maximum.

OUTPUTS PER SYSTEM—

32 maximum.

LIOU SIGNAL AUDIBLE MODULE

OUTPUT RATING—

2 amperes at 24 vdc

WIRING STYLES—

NFPA Four Style “Y” or Two Style “Z” circuits.

MODULES PER SYSTEM—8 maximum.

OUTPUTS PER SYSTEM—

32 maximum.

X-12

12.0(30.5)

16.0(40.6)

6.0(15.2)

A1695

9.6(24.4)

10.25(26)

13.6(34.6)

14.25(36.2)

A2037

Figure X–13—Dimensions of LIOU Enclosure in Inches

Figure X–14—Dimensions of LIOU Mounting Platein Inches (Centimeters)

Page 102: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 102/128

X-13 95-8470

COMBUSTIBLE GAS SENSOR

Refer to the Combustible Gas Sensor Specification Data

sheet, form 90-1041, for specifications.

ELECTROCHEMICAL SENSORS

Refer to the Electrochemical Gas Sensor Specification

Data sheet, form 90-1079, for specifications.Electrochemical sensors available from Det-Tronicsinclude Hydrogen Sulfide, Oxygen, Carbon Monoxide,

Chlorine, Sulfur Dioxide, and Nitrogen Dioxide.

POINTWATCH

Refer to the PointWatch manual, form 95-8440, forPointWatch specifications.

Page 103: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 103/128

XI-1 95-8470

Section XISystem Maintenance

ROUTINE MAINTENANCE

To ensure reliable protection, it is important to checkand calibrate the system on a regularly scheduledbasis. The frequency of these checks is determined by

the requirements of the particular installation.

MANUAL CHECK OF OUTPUT DEVICES

It is important that response devices be checked initiallywhen the system is installed, as well as periodicallyduring the on-going maintenance program.

CAUTION

Be sure to secure all output devices that are actuated by the system to prevent unwanted activation of this equipment, and remember to

place these same output devices back into service when the checkout is complete.

O-RING MAINTENANCE

WARNING The hazardous area must be de-classified prior to

removing a junction box cover with power applied.

A rubber O-ring is used to ensure that the junction boxcover will seal tightly and provide protection against

water ingress. Periodically the enclosure should beopened and the O-ring should be inspected for breaks,

cracks and dryness. To test the ring, remove it from the

enclosure and stretch it slightly. If cracks are visible, itshould be replaced. If it feels dry, a thin coating oflubricant should be applied. When re-installing the ring,be sure that it is properly seated in the groove on the

housing. It is imperative that this O-ring be properlyinstalled and in good condition. Failure to properly

maintain it can allow water to enter the enclosure andcause premature failure. A coating of lubricant should

also be applied to the threads on the cover before re-assembling the enclosure. This will both lubricate thethreads and help to prevent moisture from entering the

enclosure.

CAUTION The O-rings should be lubricated with a silicone free grease. The use of other lubricants is not

recommended, since they can adversely affect the performance of some sensors. Under no

circumstances should a lubricant or compound containing silicone be used on systems using catalytic type combustible gas sensors.

FLAME DETECTOR MAINTENANCE

The flame detector requires no periodic calibration.

However, to maintain maximum sensitivity, the viewingwindow must be kept clean at all times.

To clean the optical surfaces, remove the oi ring fromthe detector by gently squeezing the tabs together and

then pulling out. Clean the viewing window and the

back side of theoi ring using a clean cloth or tissueand Det-Tronics window cleaning solution. Avoid the

use of commercial glass cleaners, since many of them

can leave a UV absorbing residue on the surface.Avoid leaving fingerprints on the reflective surface of the

oi ring. Re-install the ring so that the opening is

positioned downward.

NOTE

If corrosive contaminants in the atmosphere cause the reflective rings to deteriorate to the extent that

it is no longer possible to restore them to their original condition, they must be replaced.

To ensure the watertight integrity of the detector, the O-

rings must be maintained following the guidelinesdescribed above.

GAS SENSOR MAINTENANCE

All gas sensors must be calibrated on a regularlyscheduled basis, typically every 90 days for catalytic

and electrochemical sensors and annually forPointWatch.

Catalytic sensors have a finite lifespan. If a successful

calibration cannot be performed, replace the sensorand recalibrate following the procedure described in the“Calibration” section. Exposure of the sensor to high

concentrations of combustible gases for extendedperiods of time can introduce stress to the sensing

element and seriously affect its performance. Afterexposure to a high concentration of combustible gas,

recalibration should be performed and, if necessary, thesensor should be replaced.

Electrochemical sensors have a finite lifespan. If asuccessful calibration cannot be performed, inspect the

hydrophobic filter. If the filter is plugged, replace it andrecalibrate the sensor. If the filter is in good condition,

replace the sensor. Recalibrate following the proceduredescribed in the “Calibration” section.

If the PointWatch fails calibration, refer to thePointWatch manual.

NOTE Compare part numbers to be sure that the correct

replacement sensor is being used.

Page 104: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 104/128

XI-2

BATTERIES

Batteries must be replaced every 48 months, or soonerif required by local codes. Only sealed batteries are to

be used.

TROUBLESHOOTING

Table XI-1 is intended to serve as an aid in locating the

cause of a system malfunction. If the problem cannot

be corrected, contact the factory for assistance.

REPLACEMENT PARTS

Eagle devices are not designed to be repaired in the

field. If a problem should develop, first carefully check

for proper wiring, programming and calibration. If it isdetermined that the problem is caused by an electronic

defect, the device must be returned to the factory forrepair.

NOTE When replacing a device, be sure that the rocker switches on the replacement are set the same as

the original. Remove power before removing or

plugging in the replacement unit. When a DCU,IDC or flame detector is replaced, the point must be re-configured. If the auto-configure feature is

enabled, configuration is done automatically.

T0025B

Symptom Possible Cause

Gateway Green Power LED is off. Power wiring is wrong.

Gateway Fault LED is on and F30 is displayed. An open in the LON wiring.This can also be caused by

a device that has isolated a short on the LON. Pressthe Gateway reset switch after the LON is repaired toclear the fault.

Gateway Fault LED is on and F40 is displayed. The external or faceplate reset switch is held closed.

Gateway Fault LED is on and F50 or F51 is displayed. A fault was detected on one of the LON communication

boards. Replace the gateway.

Gateway Fault LED is on and F60 is displayed. The gateway was not configured using the OIS

software.

No communication with the host computer. Wrong communication parameters (check the gatewayDIP switches), or communication wiring.

Logic Controller Fault LED is on. See Logic Controller table (Table II-3).

Logic Controller Power Fault LED is on. Power related fault.

Logic Controller Supervisory LED is on. A field device programmed as a supervisory input isactive.

The Gateway displays F10 for a field device. This is caused by a problem with the field device input.

Check for wiring or sensor faults.

The Gateway displays F20 for a field device. The field device is not repor ting or communication fault.Check power and LON wiring. Check that the device

address is set properly.

The Gateway displays F60 for a field device. The device configuration needs to be downloadedusing the OIS software.

UV Detector LEDs not blinking. Dirty viewing window.

oi ring dirty, misaligned or missing.Input voltage too low.

Internal high voltage out of tolerance.

Open, shorted or incorrect wiring.Device not configured.

UV Detector does not respond to fire stimuli or to manual oi test. Dirty viewing window.Insufficient supply voltage.Open, shorted or incorrect wiring.

Defect in UV module.Defect in electronic module.

Table XI-1—Troubleshooting Guide

Page 105: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 105/128

XI-3 95-8470

DEVICE REPAIR AND RETURN

Prior to returning devices or components, contact the

nearest local Detector Electronics office so that aService Order number can be assigned. A written

statement describing the malfunction must accompanythe returned device or component to expedite finding

the cause of the failure.

Pack the unit or component properly. Use sufficientpacking material in addition to an antistatic bag oraluminum-backed cardboard as protection from

electrostatic discharge.

Return all equipment transportation prepaid to thefactory in Minneapolis.

ORDERING INFORMATION

When ordering, please specify:

LCU

Part Number Description006814-001 EQ2100LCU Local Control Unit for

use with EQ21XXPS Series PowerSupplies.

LCU Replacement Parts:006570-001 EQ2100CG Communication Gateway

006566-001 EQ2100LC Logic Controller006558-001 EQ2100IM Isolation Module006668-001 EQ2100MR Mounting Rack

LIOU

Part Number Description

006641-xxx EQ2100LIOU Local Input/Output Unit102844-001 Relay Module102843-001 Release Module

102842-001 Signal Audible Module

LON DEVICES

Part Number Description

006608-xxx EQ22XXIDC Initiating Device Circuit006943-xxx EQ22XXIDCGF Ground Fault Monitor

007257-xxx EQ22XXIDCSC Ini ti at ing Dev iceCircuit Short Circuit

006600-xxx EQ22XXUV UV Flame Detector007082-xxx EQ22XXUVHT High Temperature UV

Flame Detector006861-xxx EQ22XXUVIR UV/IR Flame Detector006607-xxx EQ22XXDCU Digital Communication

Unit (specify gas)006733-xxx EQ25XXARM Agent Release Module

006738-xxx EQ25XXSAM Signal Audible Module006941-xxx EQ24XXNE Network Extender

POWER SUPPLIES

Part Number Description

006979-001 EQ2100PSM Power Supply Monitor000604-013 EQ2110PS Power Supply (10 amps)000604-014 EQ2130PS Power Supply (30 amps)

000604-015 EQ2175PS Power Supply (75 amps)

COMBUSTIBLE GAS SENSORS

See Table XI-2.

H2S SENSOR

Part Number Description

004539-009 Explosion-Proof H2S Sensor Housing

005434-001 Electrochemical H2S SensingElement Assembly

Other toxic gas sensors available. Consult the factory.

ACCESSORIES

Part Number Description

102868-001 Silicone Free Grease102740-001 Calibration Magnet226365-113 Sensor Separation Kit for Catalytic

Sensors226365-104 Sensor Separation Kit for

Electrochemical Sensors006414-001 Sensor Separation Kit for PointWatch

226349-001 Sensor Rain Shield225312-001 Sensor Dust Cover (Stainless Steel)226190-001 Sensor Dust Cover (Porex)

226354-001 Splash Guard

Other accessories are available. Consult the factory.

OS Number Wire LengthThreads

225006-004 3/4 inch 6 inch

225957-002

226530-003226531-003

226931-005

226931-006

226999-011

226999-012

CGSS1A6C2R1X 006824-001

Part Number Replaces

CGSS1A3C2R1X 006824-005 225006-003

226530-005

226531-004

226931-007

226931-008

3/4 inch 30 inch

CGSS1C6C2R1X 006824-003 226999-008

226999-020

226999-014

226999-021

20 mm 6 inch

CGSS1C3C2R1X 006824-007 226999-015 20 mm 30 inch

T0043A

Table XI-2—Combustible Gas Sensors

Page 106: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 106/128

CALIBRATION KITS — COMBUSTIBLE GAS

Part Number Gas

225130-001 Methane (50% LFL)225130-002 Ethane (50% LFL)

225130-003 Ethylene (50% LFL)225130-004 Propane (50% LFL)225130-005 Hydrogen (50% LFL)

225130-006 Methane (20% LFL)

225130-007 Methane (25% LFL)225130-008 Methane (35% LFL)

REPLACEMENT CYLINDERS

Part Number Gas

226166-001 Methane (50% LFL)226166-002 Ethane (50% LFL)

226166-003 Ethylene (50% LFL)226166-004 Propane (50% LFL)

226166-005 Hydrogen (50% LFL)226166-006 Air (0% LFL)226166-007 Methane (20% LFL)

226166-008 Methane (25% LFL)226166-009 Methane (35% LFL)

REPLACEMENT PARTS FOR CALIBRATION KIT

Part Number Description162552-001 Regulator

101678-007 3 foot hose004976-001 Standard calibration cup

225777-001 Modified calibration cup (for sensorseparation)

H2S CALIBRATION KIT

227115-001 H2S Calibration Kit (for electro-chemical sensors only) includes

regulator, hose, calibration cup, andtwo cylinders of calibration gas.

REPLACEMENT PARTS — H2S

Part Number Description005434-001 Elect rochemical Sens ing E lement

Assembly for H2S Sensor004532-002 Hydrophobic Filter for H2S Sensor

107427-034 O-ring (for Hydrophobic Filter)107427-004 O-ring (for Sensor Housing)

227117-001 Gas Bottle for 227115-001 CalibrationKit - 50 ppm

UV DETECTOR

006600-xxx EQ22XXUV UV Flame Detector

Accessories and Replacement Parts

Part Number Description

004273-002 Q1113 Air Shield Assembly004483-001 W8066 UV Test Lamp

004404-005 Swivel Mount003240-202 Sensor Module006598-001 Electronic Module

002507-001 Window cleaner kit

002519-001 o

i Ring107427-040 O-Ring (large)107427-004 O-Ring (small)

UV DETECTOR — High Temperature

007082-xxx EQ22XXUVHT H i Temp UV F lameDetector Electronic Module Assembly

006899-xxx C7050B Hi Temp UV Detector

One electronic module assembly and one hightemperature UV detector are required for eachdetection point. Both units must be ordered separately.

Specify material (aluminum or stainless steel) andconduit entry size (3/4 inch NPT or 25/20 MM) for each.

Accessories and Replacement Parts

Part Number Description006598-002 Electronic Module

003240-221 DE1888K3 UV Sensor Module107427-004 O-Ring for UV Detector

002099-003 Mounting Bracket (Aluminum)004404-002 Mounting Bracket (Stainless Steel)

UV/IR DETECTOR

006861-xxx EQ22XXUVIR UV/IR Flame Detector

Accessories and Replacement Parts

Part Number Description

004404-001 Q9001G Swivel Mount Assembly

004273-002 Q1113 Air Shield Assembly (two perdetector)

004000-003 W867 Explosion-proof UV/IR Test

Lamp002519-001 oi ring for UV detector

003525-001 oi ring for IR detector107427-004 O-rings for UV and IR detectors (two

O-rings per detector)DE1888B2 UV sensor module with LEDsDE5600-002 IR modu le wi th LEDs (s tandard

sensitivity)001680-001 Window Cleaner (six bottles)

003996-001 UV/ IR W indow Maintenance K it ,consisting of 2 bottles of

cleaner, 4 UV rings, 4 IR rings102868-001 Silicone Free Grease

XI-4

Page 107: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 107/128

A-1 95-8470

APPENDIX A

FACTORY MUTUAL RESEARCH CORPORATION (FMRC)

APPROVAL DESCRIPTION

The Eagle Quantum Fire and Gas Detection/Releasing System (reference Figure A1) has the following FMRCapproved configurations:

MODEL EQ2100LCU SERIES LOCAL CONTROL UNIT(Up to four EQ2100LC, four EQ2100CG and one EQ2100IM for maximum system.)

• Nonincendive for Class I, Division 2, Groups A, B, C, and D; temperature code T4A Hazardous (Classified)Locations per FM 3611.

• Operating Temperature Limits 0°C to +60°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

• Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6320.

• H2S Toxic Gas Performance verified 0 to 20, 50 or 100 ppm per FMRC requirements.

NOTE FMRC Approval allows the presence and operation of serial communications software in the LCU Gateway

(MODBUS or Allen Bradley protocols, etc.), however, the communications functions are not included in the Approval.

MODEL EQ2100LCUPS LOCAL CONTROL UNIT POWER SUPPLY ANDMODEL EQ2175PS, EQ2130PS, AND EQ2110PS POWER SUPPLIES WITH MODEL EQ2100PSM SERIESPOWER SUPPLY MONITOR

• Ordinary Locations verified per FM 3820.

• Operating Temperature Limits 0°C to +50°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

Page 108: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 108/128

A-2

MODEL EQ2100LIOU LOCAL INPUT/OUTPUT UNIT

• Ordinary Locations verified per FM 3820.

• Operating Temperature Limits 0°C to +50°C.

• Storage Temperature Limits –55°C to +85°C.

• Humidity Range: 5 to 95% RH.

• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

• Approved for use with the following automatic deluge and pre-action solenoids:

Manufacturer Model

Skinner LV2LBX25

ASCO 8210A107ASCO 8210G207Skinner 73218BN4UNLVNOC111C2

Skinner 73212BN4TNLVNOC322C2Skinner 71395SN2ENJ1NOH111C2

MODEL EQ2200IDC SERIES INITIATING DEVICE CIRCUIT AND

MODEL EQ2200IDCGF SERIES INITIATING DEVICE CIRCUIT GROUND FAULT

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.

• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM3615.

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; TemperatureCode T4A Hazardous (Classified) Locations per FM 3611.

• EQ22EMIDC and EQ22EMIDCGF non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4AHazardous (Classified) Locations per FM 3611.

• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

• The Model EQ2200IDC Series must be used in conjunction with any FMRC Approved device providing relay

contact closure.

Page 109: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 109/128

A-3 95-8470

MODEL EQ2200UV & EQ2200UVHT with C7050B SERIES UV FLAME DETECTORS

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.

• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM3615.

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature

Code T4A Hazardous (Classified) Locations per FM 3611.

• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.

• Operating Temperature Limits –40°C to +75°C for EQ2200UV and EQ2200UVHT; -40°C to +125°C for C7050B.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

• Automatic Fire Alarm Signaling Performance verified per FM 3260. A Model EQ2200UV with B2 Module was

verified to comply with the following performance criteria:

Response Characteristics

SENSITIVITY FUEL SIZE DISTANCE

Very High Gasoline 1 ft x 1 ft (0.3 m x 0.3 m) 90 ft (27.4 m)Very High Diesel 1 ft x 1 ft (0.3 m x 0.3 m) 65 ft (19.8 m)Very High Natural Gas 30 inch plume 80 ft (24.4 m)

Response Time

Typical 5 seconds maximum.

Field of View

–45° to +45° off centerline in vertical and horizontal planes.

False Alarm Immunity

Detector does not respond to the following:Direct sunlight

Indirect (reflected) sunlightTwo 34 watt fluorescent lights at 3 feet (0.9 m)100 watt incandescent light at 3 feet (0.9 m)

75 watt Phillips Far Spot incandescent light at 3 feet (0.9 m)250 watt infrared heat lamp at 3 feet (0.9 m)

300 watt incandescent clear light at 3 feet (0.9 m)500 watt Phillips quartz halogen light at 3 feet (0.9 m)

6000 watt infrared heater at 3 feet (0.9 m).

Page 110: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 110/128

A-4

UV Arc Rejection

Short duration electrical arcs

Mounting

Q9001L swivel mount for EQ2200UV; Q9001B swivel mount for C7050B.

MODEL EQ2200UVIR SERIES UV/IR FLAME DETECTOR

• Explosionproof for Class I, Division 1, Groups B, C, & D Hazardous (Classified) Locations per FM 3615.

• Dust-ignitionproof for Class II, Division 1, Groups E, F, & G, Class III Hazardous (Classified) Locations per FM3615.

• Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III;Temperature Code T4A Hazardous (Classified) Locations per FM 3611.

• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

• Automatic Fire Alarm Signaling Performance verified per FM 3260. A Model EQ2200UVIR with UV Module

DE1888B2 and IR Module DE5600-002 was verified to comply with the following performance criteria:

Page 111: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 111/128

A-5 95-8470

Response Characteristics

Fuel Size Distance UV Setting IR Setting

Gasoline 1 Sq. Ft. 100 Ft. Very High (Standard) Very High

Gasoline 1 Sq. Ft. 80 Ft. Very High (Arc Rej.) Very High

Gasoline 1 Sq. Ft. 65 Ft. High (Standard) Medium

Gasoline 1 Sq. Ft. 65 Ft. Very High (Arc Rej.) Medium

Methane 30 inch 90 Ft. Very High (Standard) Very High

Methane 30 inch 90 Ft. Very High (Arc Rej.) Very High

Methane 30 inch 40 Ft. Low (Standard) Low

Methane 30 inch 40 Ft. Medium (Arc Rej.) Low

Propane 30 inch 30 Ft. Medium (Standard) Medium

Propane 30 inch 30 Ft. Medium (Arc Rej.) Medium

Methanol 1 Sq. Ft. 40 Ft. High (Standard) Low

Methanol 1 Sq. Ft. 40 Ft. Very High (Arc Rej.) Low

JP4 4 Sq. Ft. 100 Ft. High (Standard) Medium

JP5 4 Sq. Ft. 100 Ft. High (Standard) Medium

JP8 4 Sq. Ft. 100 Ft. High (Standard) Medium

Response Time

Typical 5 seconds maximum.

Field of View

–45° to +45° off centerline in vertical and horizontal planes using gasoline fuel (1 sq. ft.).–40° to +40° off centerline in vertical and horizontal planes using methane fuel (30 inch).

Page 112: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 112/128

A-6

False Alarm Immunity

Detector does not respond to the following:

• Direct sunlight

• A 150 watt incandescent light at 2 feet (0.6 m)

• Two 60 watt fluorescent bulbs at 2 feet (0.6 m)

• A 500 watt halogen lamp at 4 feet (1.2 m)

• The radiation produced by a Miller Dial-Arc 250-P arcwelder at 10 feet (3m), set at 50 amperes with 1/8 inch Type

601 welding rod.

• Vibration immunity for vertical displacement of 0.02 inch (0.5 mm) at a frequency of 10 to 30 Hz for 4 hours.

• Radio frequency interference (RFI) immunity at 12 inches to 155 MHz and 450 MHz with radiation power levels of5.0 watts.

Mounting

Model Q9001G Swivel Mounting Bracket.

MODEL EQ2200DCU SERIES DIGITAL COMMUNICATION UNITS

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.

• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM3615 (For use with Sensor Separation Kit).

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous (Classified) Locationsper FM 3611.

• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified)Locations per FM 3611. (For use with sensor separation kit.)

• EQ22EMDCU non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous(Classified) Locations per FM 3611.

• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250 (For use with Sensor Separation Kit).

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• Combustible gas performance verified with any FMRC Approved stand alone linear 4 to 20 mA device per FM

6310/6320. Accuracy: ±3% LFL from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL.

• Toxic gas performance verified 0 to 100 ppm per FMRC requirements. Accuracy: ±2 ppm from 0 to 20 ppm,±10% of concentration from 21 to 100 ppm. Models C7064E4012 and C7064E5012 Hydrogen Sulfide (H2S)Sensors Explosion-proof for Class I, Div. 1, Groups C and D Hazardous (Classified) Locations per FM 3615. Model

C7064E5014 Hydrogen Sulfide (H2S) Sensors Explosion-proof for Class I, Div. 1, Groups B, C and D Hazardous(Classified) Locations per FM 3615. Operating temperature limits are –40°C to +40°C.

Page 113: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 113/128

NOTE

Sensor cross sensitivity has not been verified by FMRC.

NOTE FMRC Approval of the 4 to 20 ma input does not include or imply approval of the gas detection apparatus such

as sensors, transmitters, or devices connected to the system. In order to maintain FMRC Approval of the system, all 4 to 20 ma gas detection instruments connected to the input must also be FMRC Approved.

MODEL EQ2200DCUEX SERIES DIGITAL COMMUNICATION UNITWITH MODEL CGS SERIES COMBUSTIBLE GAS SENSOR

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.

• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM

3615. (For use with Sensor Separation Kit)

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous (Classified) Locations

per FM 3611.

• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified)

Locations per FM 3611. (For use with sensor separation kit.)

• EQ22EMDCUEX non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous

(Classified) Locations per FM 3611.

• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250 (For use with Sensor Separation Kit).

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6310/6320. Accuracy: ±3% LFL from0 to 50% LFL, ±5% LFL from 51% to 100% LFL.

NOTE

The high temperature characteristic has NOT been FMRC verified above 75°C.

NOTE Detector Electronics combustible gas detection K factors are not FMRC verified.

SENSOR SEPARATION KIT

226365-106 Combustible, Aluminum, 3/4 inch NPT, 4 Position Connector226365-113 Combustible, Aluminum, 3/4 inch NPT, Wiring Harness226365-104 Toxic, Aluminum, 3/4 inch NPT

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.

NOTE

Ensure sensor hazardous (classified) location rating is applicable for the intended use.

95-8470A-7

Page 114: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 114/128

A-8

MODEL EQ2500ARM SERIES AGENT RELEASE MODULE

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.

• Dust ignition-proof for Class II, Div. 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615.

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; TemperatureCode T4A Hazardous (Classified) Locations per FM 3611.

• EQ25EMARM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous(Classified) Locations per FM 3611.

• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

• Approved for use with the following automatic deluge and pre-action solenoids:

Manufacturer Model

Skinner LV2LBX25

ASCO 8210A107ASCO 8210G207Skinner 73218BN4UNLVNOC111C2Skinner 73212BN4TNLVNOC322C2

Skinner 71395SN2ENJ1NOH111C2

MODEL EQ2500SAM SERIES SIGNAL AUDIBLE MODULE

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.

• Dust ignition-proof for Class II, Div. 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615.

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; TemperatureCode T4A Hazardous (Classified) Locations per FM 3611.

• EQ25EMSAM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous(Classified) Locations per FM 3611.

• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

Page 115: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 115/128

A-9 95-8470

MODEL EQ2400NE SERIES NETWORK EXTENDER

• Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous (Classified) Locations per FM 3615.

• Dust ignition-proof for Class II, Div. 1, Groups E, F, & G, Class III Hazardous (Classified) Locations per FM 3615.

• Non-incendive for Class I, Div. 2, Groups A, B, C and D; Class II, Div. 2, Groups F and G; Class III; TemperatureCode T4A Hazardous (Classified) Locations per FM 3611.

• EQ24EMNE non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous

(Classified) Locations per FM 3611.• Enclosure Rating NEMA / Type 4X per ANSI/NEMA 250.

• Operating Temperature Limits -40°C to +75°C.

• Storage Temperature Limits -55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996 and gas performance verified per FM6310/6320.

OPTIONS

• An optional EQ2101LCU with EQ2101MR Mounting Rack is available with provisions for two 24 vdc power inputs.

The customer must supply two reliable and independent 24 vdc supplies in accordance with ANSI/NFPA 72-1996section 1-5.2. If either of the supplies is missing due to a broken wire, a trouble condition will be annunciated.

• Operator Interface Station (OIS)

NOTE Metric straight thread types are for use in non-North American applications.

CALIBRATION

• Calibration of the above listed sensors has been FMRC verified using the respective EQ2200DCU andEQ2200DCUEX Series with the Det-Tronics 225130-001 (50% LFL methane) and 227115-001 H2S Calibration Kits.

• The EQ2200DCU Series can be used with any FMRC Approved 4 to 20 ma device.

Page 116: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 116/128

F i g u r e A 1

A-10

Page 117: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 117/128

B-1 95-8470

APPENDIX B

CANADIAN STANDARDS ASSOCIATION (CSA)

APPROVAL DESCRIPTION]

The Eagle Quantum Fire and Gas Detection/Suppression System (reference Figure B1) has the following CSAapproved configurations:

MODEL EQ2100LCU SERIES LOCAL CONTROL UNIT(Up to four EQ2100LCU, four EQ2100CG and one EQ2100IM for maximum system.)

• Class I, Division 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213.

• Operating Temperature Limits 0°C to +60°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152.

MODEL EQ2100LCUPS LOCAL CONTROL UNIT POWER SUPPLY ANDMODEL EQ2175PS, EQ2130PS AND EQ2110PS POWER SUPPLIES WITH MODEL EQ2100PSM SERIES

POWER SUPPLY MONITOR

• Ordinary Locations verified per CSA C22.2 #142.

• Operating Temperature Limits 0°C to +50°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

MODEL EQ2100LIOU LOCAL INPUT/OUTPUT UNIT

• Ordinary Locations verified per CSA C22.2 #142.

• Operating Temperature Limits 0°C to +50°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

Page 118: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 118/128

B-2

MODEL EQ2200IDC SERIES INITIATING DEVICE CIRCUIT AND

MODEL EQ2200IDCGF SERIES INITIATING DEVICE CIRCUIT GROUND FAULT

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.

• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; TemperatureCode T4A Hazardous Locations per CSA C22.2 #213.

• EQ22EMIDC AND EQ22EMIDCGF non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code

T4A Hazardous Locations per CSA C22.2 #213.

• Enclosure Rating Type 4X per CSA C22.2 #94.

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• The Model EQ2200IDC Series must be used in conjunction with any CSA certified device providing relay contactclosure.

MODEL EQ2200UV SERIES UV FLAME DETECTOR:

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.

• Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; TemperatureCode T4A Hazardous Locations per CSA C22.2 #213.

• Enclosure Rating Type 4X per CSA C22.2 #94.

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• Optional Q9001L Swivel Mount.

MODEL EQ2200UVHT SERIES HIGH TEMPERATURE UV FLAME DETECTOR

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.

• Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; TemperatureCode T4A Hazardous Locations per CSA C22.2 #213.

• Enclosure Rating Type 4X per CSA C22.2 #94.

• Operating Temperature Limits –40°C to +75°C for electronic module, –40°C to +125°C for UV detector.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• Optional Q9001B Swivel Mount for UV detector.

Page 119: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 119/128

B-3 95-8470

MODEL EQ2200UVIR SERIES UV/IR FLAME DETECTOR

• Explosionproof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.

• Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.

• Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III;Temperature Code T4A Hazardous Locations per CSA C22.2 #213.

• Enclosure Rating Type 4X per CSA C22.2 #94.

• Operating Temperature Limits –40°C to +75°C.• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• Optional Q9001G Swivel Mount.

MODEL EQ2200DCU SERIES DIGITAL COMMUNICATION UNITS

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.

• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25

(For use with Sensor Separation Kit).

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA

C22.2 #213.

• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per

CSA C22.2 #213 (For use with sensor separation kit.)

• EQ22EMDCU non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous

Locations per CSA C22.2 #213.

• Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit).

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• Combustible gas performance verified with any CSA Certified stand alone linear 4 to 20 mA device per CSA C22.2

#152. Accuracy ±3% LFL from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL.

Page 120: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 120/128

B-4

MODEL EQ2200DCUEX SERIES DIGITAL COMMUNICATION UNIT

WITH MODEL CGS SERIES COMBUSTIBLE GAS SENSOR

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.

• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25(For use with Sensor Separation Kit).

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSAC22.2 #213.

• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations perCSA C22.2 #213 (For use with sensor separation kit.)

• EQ22EMDCUEX non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A HazardousLocations per CSA C22.2 #213.

• Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit).

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• Verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152. Accuracy: ±3% LFL from 0 to 50%

LFL, ±5% LFL from 51% to 100% LFL.

NOTE The high temperature characteristic has NOT been CSA verified above 75°C.

SENSOR SEPARATION KITS

226365-106 Combustible, Aluminum, 3/4 inch NPT, 4 Position Connector226365-113 Combustible, Aluminum, 3/4 inch NPT, Wiring Harness

226365-104 Toxic, Aluminum, 3/4 inch NPT

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.

NOTE

Ensure sensor hazardous (classified) location rating is applicable for the intended use.

MODEL EQ2500ARM SERIES AGENT RELEASE MODULE

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.

• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature

Code T4A Hazardous Locations per CSA C22.2 #213.• EQ25EMARM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous

Locations per CSA C22.2 #213.

• Enclosure Rating NEMA Type 4X per CSA C22.2 #94.

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

Page 121: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 121/128

B-5 95-8470

MODEL EQ2500SAM SERIES SIGNAL AUDIBLE MODULE

• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.

• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.

• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; TemperatureCode T4A Hazardous Locations per CSA C22.2 #213.

• EQ25EMSAM non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A HazardousLocations per CSA C22.2 #213.

• Enclosure Rating NEMA Type 4X per CSA C22.2 #94.

• Operating Temperature Limits –40°C to +75°C.

• Storage Temperature Limits –55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

MODEL EQ2400NE SERIES NETWORK EXTENDER

• Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous Locations per CSA C22.2 #30.

• Dust ignition-proof for Class II, Div. 1, Groups E, F, & G, Class III Hazardous Locations per CSA C22.2 #25.

• Non-incendive for Class I, Div.2, Groups A, B, C and D; Class II, Div. 2, Groups F and G; Class III; Temperature

Code T4A Hazardous Locations per CSA C22.2 #213.

• EQ24EMNE non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations

per CSA C22.2 #213.

• Enclosure Rating NEMA / Type 4X per CSA C22.2 #94.

• Operating Temperature Limits -40°C to +75°C.

• Storage Temperature Limits -55°C to +85°C.

• Relative Humidity Range: 5 to 95% RH.

• Gas performance verified per CSA C22.2 #152.

OPTIONS

• Operator Interface Station (OIS)

NOTE Metric straight thread types are for use in non-North American applications.

CALIBRATION

• Calibration of the above listed sensors has been CSA verified using the respective EQ2200DCU andEQ2200DCUEX Series with Det-Tronics 225130-001 (50% LFL methane) and 227115-001 H2S Calibration Kits.

• The Model EQ2200DCU Series can be used with any CSA certified stand alone 4 to 20 ma linear device.

Page 122: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 122/128

F i g u r e B 1

B-6

Page 123: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 123/128

C-1 95-8470

APPENDIX C

CE MARK

The Eagle Quantum Fire and Gas Detection/Suppression System was tested and found to be compliant with

EN50081-2 and EN50082-2 when wired in conduit or with armoured instrument cable with individual screenedtwisted pairs and galvanized steel wire armour. All screen drains shall be terminated to the chassis except for theLON/SLC screen drains, which are terminated at LCU terminals 23 A and B and the LON/SLC screen termination in

each field device.

Communication wiring between the Local Control Unit (LCU), Local Input/Output Unit (LIOU) and Local Control UnitPower Supply (LCUPS) shall be limited to a maximum of 3 meters for each section.

CENELEC CERTIFICATION

INITIATING DEVICE CIRCUIT (IDC and IDCGF),DIGITAL COMMUNICATION UNIT (DCU)

AGENT RELEASE MODULE (ARM),SIGNAL AUDIBLE MODULE (SAM),

NETWORK EXTENDER (NE):

EEx d IIC T4 (Tamb = –60°C to +75°C)EEx d IIC T5 (Tamb = –60°C to +65°C)

EEx d IIC T6 (Tamb = –60°C to +50°C)IP66.

Special Conditions for Safe Use

To obviate the risk of hotspots and capacitor energy storage, the enclosure must not be opened, even when isolated,when a flammable atmosphere is present.

Cable glands or the conduit entries to be used with this apparatus shall be EEx d approved by a notified body,

relevant to the threads found with the enclosure where they are to be fixed. As guards do not protect the transparentwindows of the devices, care shall be exercised during installation, positioning the face of the apparatus in order toprevent damage.

UV FLAME DETECTOR:

Standard Temperature Version —

EEx d IIB +H2 T6 (Tamb = –40°C to +75°C).IP66.

Extended Temperature Version —EEx d IIB +H2 T6 (Tamb = –40°C to +75°C)

EEx d IIB +H2 T4 (Tamb = –40°C to +125°C)

IP66.

Special Conditions for Safe Use of UV Detector —

The detector contains capacitors that could be an ignition source if the enclosure is opened within a hazardous area.The enclosure must not be opened, even when isolated, when a flammable atmosphere is present. The cable must

only be connected to the enclosure by a flameproof cable entry device certified to EN 50 018. If only one cable entryis used, any other entries must be closed by a certified flameproof stopping plug. The flame detector can be

delivered in two versions, one for ambient temperatures up to +75°C, and one for temperatures up to +125°C. Thelabel will indicate the actual maximum allowable ambient temperature.

Page 124: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 124/128

C-2

EQ2200UVHT SERIES UV FLAME DETECTOR

Electronic Module —

EEx d IIC T4 (Tamb = –60°C to +75°C)EEx d IIC T5 (Tamb = –60°C to +65°C)

EEx d IIC T6 (Tamb = –60°C to +50°C)IP66.

UV Detector —

EEx d IIB +H2 T4 (Tamb = –55°C to +125°C)EEx d IIB +H2 T5 (Tamb = –55°C to +90°C)EEx d IIB +H2 T6 (Tamb = –55°C to +75°C)

IP66.

Special Conditions for Safe Use of UV Detector —

The cable entry temperature may rise 10°C above the ambient temperature and cable shall be suitable for that

temperature. The flame detector shall be electrically connected by means of a flame-proof cable gland or stoppingbox certified to EN 50018. The fused silica lens in this unit is liable to be damabed by impact. The unit should be

installed in such a manner as to protect the lens from mechanical damage.

UV/IR FLAME DETECTOR:

Standard Temperature Version —

EEx d IIB +H2 T6 (Tamb = –40°C to +75°C).EEx d IIB +H2 T5 (Tamb = –40°C to +90°C).

IP66.

Extended Temperature Version —

EEx d IIB +H2 T6 (Tamb = –55°C to +75°C)EEx d IIB +H2 T5 (Tamb = –55°C to +90°C)

EEx d IIB +H2 T4 (Tamb = –55°C to +125°C)IP66.

Special Conditions for Safe Use of UV/IR Detector —

The UV detector module contains a fused silica window, which can be damaged by impact. The detector should beinstalled in such a manner as to prevent the window from receiving mechanical damage.

CATALYTIC COMBUSTIBLE GAS SENSOR

EEx d IIC T4 (Tamb = –55°C to +105°C).

Special Conditions for Safe Use of Catalytic Gas Sensor —

The sensor can withstand repeated exposures to +125°C for periods up to 12 hours. It is recommended that thesensor be replaced after a maximum of 500 hours of exposure to the +125°C temperature conditions.

Page 125: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 125/128

APPENDIX D

D-1 95-8470

Page 126: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 126/128

D-2

Node Rocker Switch

Address 1 2 3 4 5 6 7 8

1 X O O O O O O O

2 O X O O O O O O

3 X X O O O O O O

4 O O X O O O O O

5 X O X O O O O O

6 O X X O O O O O

7 X X X O O O O O

8 O O O X O O O O

9 X O O X O O O O

10 O X O X O O O O

11 X X O X O O O O

12 O O X X O O O O

13 X O X X O O O O

14 O X X X O O O O

15 X X X X O O O O

16 O O O O X O O O

17 X O O O X O O O

18 O X O O X O O O

19 X X O O X O O O

20 O O X O X O O O

21 X O X O X O O O

22 O X X O X O O O

23 X X X O X O O O

24 O O O X X O O O

25 X O O X X O O O26 O X O X X O O O

27 X X O X X O O O

28 O O X X X O O O

29 X O X X X O O O

30 O X X X X O O O

31 X X X X X O O O

32 O O O O O X O O

33 X O O O O X O O

34 O X O O O X O O

35 X X O O O X O O

36 O O X O O X O O

37 X O X O O X O O

38 O X X O O X O O

39 X X X O O X O O

40 O O O X O X O O

41 X O O X O X O O

42 O X O X O X O O

43 X X O X O X O O

44 O O X X O X O O

45 X O X X O X O O

46 O X X X O X O O

47 X X X X O X O O

48 O O O O X X O O

49 X O O O X X O O

50 O X O O X X O O

51 X X O O X X O O

52 O O X O X X O O

53 X O X O X X O O

54 O X X O X X O O

55 X X X O X X O O

56 O O O X X X O O

57 X O O X X X O O58 O X O X X X O O

59 X X O X X X O O

60 O O X X X X O O

61 X O X X X X O O

62 O X X X X X O O

63 X X X X X X O O

64 O O O O O O X O

65 X O O O O O X O

66 O X O O O O X O

67 X X O O O O X O

68 O O X O O O X O

69 X O X O O O X O

70 O X X O O O X O

Node Rocker Switch

Address 1 2 3 4 5 6 7 8

71 X X X O O O X O

72 O O O X O O X O

73 X O O X O O X O

74 O X O X O O X O

75 X X O X O O X O

76 O O X X O O X O

77 X O X X O O X O

78 O X X X O O X O

79 X X X X O O X O

80 O O O O X O X O

81 X O O O X O X O

82 O X O O X O X O

83 X X O O X O X O

84 O O X O X O X O

85 X O X O X O X O

86 O X X O X O X O

87 X X X O X O X O

88 O O O X X O X O

89 X O O X X O X O

90 O X O X X O X O

91 X X O X X O X O

92 O O X X X O X O

93 X O X X X O X O

94 O X X X X O X O

95 X X X X X O X O96 O O O O O X X O

97 X O O O O X X O

98 O X O O O X X O

99 X X O O O X X O

100 O O X O O X X O

101 X O X O O X X O

102 O X X O O X X O

103 X X X O O X X O

104 O O O X O X X O

105 X O O X O X X O

106 O X O X O X X O

107 X X O X O X X O

108 O O X X O X X O

109 X O X X O X X O

110 O X X X O X X O

111 X X X X O X X O

112 O O O O X X X O

113 X O O O X X X O

114 O X O O X X X O

115 X X O O X X X O

116 O O X O X X X O

117 X O X O X X X O

118 O X X O X X X O

119 X X X O X X X O

120 O O O X X X X O

121 X O O X X X X O

122 O X O X X X X O

123 X X O X X X X O

124 O O X X X X X O

125 X O X X X X X O

126 O X X X X X X O

127 X X X X X X X O128 O O O O O O O X

129 X O O O O O O X

130 O X O O O O O X

131 X X O O O O O X

132 O O X O O O O X

133 X O X O O O O X

134 O X X O O O O X

135 X X X O O O O X

136 O O O X O O O X

137 X O O X O O O X

138 O X O X O O O X

139 X X O X O O O X

140 O O X X O O O X

Rocker Switch Table

Page 127: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 127/128

95-8470D-3

Node Rocker Switch

Address 1 2 3 4 5 6 7 8

141 X O X X O O O X

142 O X X X O O O X

143 X X X X O O O X

144 O O O O X O O X

145 X O O O X O O X

146 O X O O X O O X

147 X X O O X O O X

148 O O X O X O O X

149 X O X O X O O X

150 O X X O X O O X

151 X X X O X O O X

152 O O O X X O O X

153 X O O X X O O X

154 O X O X X O O X

155 X X O X X O O X

156 O O X X X O O X

157 X O X X X O O X

158 O X X X X O O X

159 X X X X X O O X

160 O O O O O X O X

161 X O O O O X O X

162 O X O O O X O X

163 X X O O O X O X

164 O O X O O X O X

165 X O X O O X O X166 O X X O O X O X

167 X X X O O X O X

168 O O O X O X O X

169 X O O X O X O X

170 O X O X O X O X

171 X X O X O X O X

172 O O X X O X O X

173 X O X X O X O X

174 O X X X O X O X

175 X X X X O X O X

176 O O O O X X O X

177 X O O O X X O X

178 O X O O X X O X

179 X X O O X X O X

180 O O X O X X O X

181 X O X O X X O X

182 O X X O X X O X

183 X X X O X X O X

184 O O O X X X O X

185 X O O X X X O X

186 O X O X X X O X

187 X X O X X X O X

188 O O X X X X O X

189 X O X X X X O X

190 O X X X X X O X

191 X X X X X X O X

192 O O O O O O X X

193 X O O O O O X X

194 O X O O O O X X

195 X X O O O O X X

196 O O X O O O X X

197 X O X O O O X X198 O X X O O O X X

199 X X X O O O X X

200 O O O X O O X X

201 X O O X O O X X

202 O X O X O O X X

203 X X O X O O X X

204 O O X X O O X X

205 X O X X O O X X

206 O X X X O O X X

207 X X X X O O X X

208 O O O O X O X X

209 X O O O X O X X

210 O X O O X O X X

Node Rocker Switch

Address 1 2 3 4 5 6 7 8

211 X X O O X O X X

212 O O X O X O X X

213 X O X O X O X X

214 O X X O X O X X

215 X X X O X O X X

216 O O O X X O X X

217 X O O X X O X X

218 O X O X X O X X

219 X X O X X O X X

220 O O X X X O X X

221 X O X X X O X X

222 O X X X X O X X

223 X X X X X O X X

224 O O O O O X X X

225 X O O O O X X X

226 O X O O O X X X

227 X X O O O X X X

228 O O X O O X X X

229 X O X O O X X X

230 O X X O O X X X

231 X X X O O X X X

232 O O O X O X X X

233 X O O X O X X X

234 O X O X O X X X

235 X X O X O X X X236 O O X X O X X X

237 X O X X O X X X

238 O X X X O X X X

239 X X X X O X X X

240 O O O O X X X X

241 X O O O X X X X

242 O X O O X X X X

243 X X O O X X X X

244 O O X O X X X X

245 X O X O X X X X

246 O X X O X X X X

247 X X X O X X X X

248 O O O X X X X X

249 X O O X X X X X

250 O X O X X X X X

O = OPEN

X = CLOSED

Rocker Switch Table

Page 128: Manual Eagle Quantum

8/10/2019 Manual Eagle Quantum

http://slidepdf.com/reader/full/manual-eagle-quantum 128/128

LON® is a registered trademark of Echelon Corporation.Modbus® is a registered trademark of Modicon Inc.


Recommended