Date post: | 10-Oct-2015 |
Category: |
Documents |
Upload: | parmeshwar-nath-tripathi |
View: | 274 times |
Download: | 41 times |
of 15
MW95A Belt Weigher System Setup Summary
MW95A_Setup_Summary_SV3.60a EMC INDUSTRIAL GROUP LTD
Applies to transmitter software version number 3.60 onwards
TYPE SERIAL No.
COMPANY TAG No.
PLANT DATE
Quick Key
Service Setting (password 9713) Field Setting Default/ Group
Address
Basic Settings Engineering units 2111 units metric/imperial [0=any, 1=metric, 2=imperial] 1 0 8042 2112 weight units (WU) 1 101 (kg) 0 8044 2113 belt speed units (BSU) 2 80 (m/s) 0 8046 2114 flowrate units (FU) 3 164 (t/h) 0 8048 2115 totaliser units (TU) 4 102 (t) 0 8050 2116 length units (LU) 5 20 (m) 0 8052
Measuring range 2121 weight capacity [0.001 to 1,000,000] WU 1000 8060 2122 belt speed capacity [0.001 to 1,000,000] BSU 2.00 8062 2123 flowrate capacity [0.001 to 1,000,000] FU 100 8064
Display resolution 2131 weight divisions [100 to 100,000] 500 0 8070 2132 belt speed divisions [100 to 100,000] 500 0 8072 2133 flowrate divisions [100 to 100,000] 500 0 8074
Inputs Digital inputs 2211 IN1 function (& state6) 7 pulse input 0 3 8170 6/8xx 2212 IN2 function (& state) acquire zero 16 3 8172 6/8xx 2213 IN3 function (& state) run 2 3 8174 6/8xx 2214 IN4 function (& state) reset total 32 3 8176 8xx8 2215 IN5 function (& state) print 40 3 8178 8xx 2216 IN6 function (& state) print total 41 3 8180 8xx 2217 IN7 function (& state) stop 1 3 8182 8xx 2218 IN8 function (& state) pause 3 3 8184
Tacho & Belt lengths / Direct belt calibration 22211 tacho constant (belt travel for 1000 tacho pulses) [0 to 100] 1.000 8160 22212 platform length LU 1.000 8080 22213 belt unload length LU 0.0 4 8082 22214 belt calibration length LU 10.0 8084 22216 internal belt speed (set to 0 when using tacho) BSU 0.00 4 8272
1 Metric: 100=g, 101=kg, 102=t, Imperial: 110=oz, 111=lb, 112=tons 2 Metric: 80=m/s, 81=mm/s, 82=cm/s, 83=m/min, Imperial: 90=ft/s, 91=in/s, 92=yd/s, 93=ft/min 3 Metric: 160=kg/s, 161=kg/min, 162=kg/h, 163=t/min, 164=t/h, Imperial: 170=lb/s, 171=lb/min, 172=lb/h, 173=ton/min,
174=ton/h 4 Metric: 100=g, 101=kg, 102=t, Imperial: 110=oz, 111=lb, 112=tons 5 Metric: 20=m, 21=mm, 22=cm, Imperial: 30=in, 31=ft, 32=yd 6 Hint line shows state as (on) or (off) 7 See I/O Function & Alarm Table page 8. Use negative numbers to reverse the signal sense eg 1=stop (stop when input is on), -
1=NOT stop (stop when input is off). 8 Only for MW8xx transmitters
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 2 of 15
Quick Key
Service Setting (password 9713) Field Setting Default/ Group
Address
Tacho & Belt lengths / Tacho cal at known speed 22421 belt speed 9 shows belt speed BSU 8908
Tacho & Belt lengths / Measured belt calibration 22231 known belt length 10 LU 0.000 4 8924 22232 measure tacho constant 11 4 8760 22233 measure unload length 11 4 8926 22234 measure calibration length 11 4 8928 22235 measure reload length 11 4 8930
Loadcell input (platform weight) 2231 AI1 response time [0.04 to 32] s 2.00 1 8120
Loadcell input / Calibration with weights 22321 AI1 zero (remove all weight and set to zero) 12 shows platform weight WU 8910 22322 AI1 span (apply span weight and enter weight value) 12 shows platform weight WU 8912
Loadcell input / Direct loadcell calibration 22331 loadcell capacity (sum of capacity of all loadcells) 13 14 WU 1000 1 8122 22332 system sensitivity (average sensitivity of all loadcells) [-20 to 20] mV/V 2.00000 1 8124 22333 deadload (dead weight on loadcells) [-1,000,000 to 1,000,000] WU 0 1 8126
Loadcell input / Dynamic loadcell calibration 22341 dynamic zero (set to 0 to start dynamic zero) 12 shows platform weight WU 1 8914 22342 dynamic span by weight 12 shows platform weight WU 1 8916 22343 dynamic span by belt loading 12 shows belt loading WU/LU 1 8918
Loadcell input / Loadcell signals 22351 AI1 signal mV/V 8700 6/8xx15 22352 loadcell 4/6 wire connection 4 wire or 6 wire 8702 22356 calibration sequence no. 8714
Loadcell input / Excitation adjustment 22361 excitation 1 [-250 to 251] 251 (disabled) 1 8132 22362 excitation 2 [-250 to 251] 251 (disabled) 1 8134 22363 excitation 3 [-250 to 251] 251 (disabled) 1 8136 22364 excitation 4 [-250 to 251] 251 (disabled) 1 8138
Current/Voltage input16 6/8xx 2241 AI2 current low mA 4.000 2 8140 6/8xx 2242 AI2 current high mA 20.000 2 8142 6/8xx 2243 AI2 voltage low V 0.000 2 8144 6/8xx 2244 AI2 voltage high V 10.000 2 8146 6/8xx 2245 AI2 signal type 17 3 2 8148 6/8xx 2246 AI2 signal low 18 FU 0 2 8150 6/8xx 2247 AI2 signal high 18 FU 100 2 8152 6/8xx 2248 AI2 current/voltage mA or V 2 8720 6/8xx 2249 AI2 signal FU 2 8722
9 Entering a value changes the tacho constant to display the entered belt speed. 10 Not retained when power is turned off. 11 When in EDIT mode, the 1 key starts & stops the belt measurement. 12 Entering a value initiates a calibration 13 WARNING: Altering loadcell capacity will NOT change the loadcell calibration, but will re-scale the system sensitivity and deadload
values. Altering the system sensitivity or deadload values WILL change the loadcell calibration 14 [-1,000,000 to 1,000,000] 15 Only for MT6x and MT8x transmitters 16 Only if option MO-2 fitted 17 0=general, 1=weight, 2=belt speed, 3=flowrate, 4=total, 5=belt loading, 6=length, 7=short length, 8=current, 9=voltage 18 Signal units are determined by units of AI2 signal type
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 3 of 15
Quick Key
Service Setting (password 9713) Field Setting Default/ Group
Address
Internal Signals Weight / Basic weight 23111 platform weight WU 8740 23115 belt loading WU/LU 8746
Weight / Weight zeroing 23121 zero range % 2.00 8212 23123 zero tracking band (set to 0 to disable) 19 div 0.0 5 8216 23124 un-zeroed weight WU 8750 23125 zeroing progress 8752 23126 zero weight WU 0 8220 23127 zero deviation WU 8756
Flowrate 2331 flowrate correction (increases measured flowrate) % 0.00 8290 2333 flowrate FU 8762 2336 dynamic filter [0=off,1=low,2=medium,3=high] 0 6 8298 2337 flowrate raw FU 6 8764
Totaliser 2341 low flow cutout % 2.0 8310 2342 totaliser max. count rate [0.1 to 1000] Hz 10.0 8312 2343 OUT1 max. count rate (for external counter) [0.1 to 100] Hz 10.0 8314 2344 total weight TU 0.00 8316 2345 running total TU 0.00 6 8318 2346 totaliser digits 6 8320
Limits/Batching / Limit setpoints 23511 setpoint 1 high limit 20 FU 90 7 8330 23512 setpoint 2 low limit 20 FU 10 7 8332
Limits/Batching / Limit sources 23521 setpoint 1 source (modbus address of signal) flowrate 8762 7 8350 23522 setpoint 2 source (modbus address of signal) flowrate 8762 7 8360
Limits/Batching / Batching 23541 batch setpoint TU 0.00 7 8400 23542 batch preact (stop this amount before batch setpoint) TU 0.00 7 8402
Events 2361 event ID 8 8780 2362 event value 8 8782 2364 alarm list (press EDIT to view list of all possible alarms) 8 8920 2365 delay time [0.00 to 300.00] s 0.00 8 8458
Control / Speed demand 23731 speed demand (flow control speed signal) % 8792
19 Set in divisions of weight, the smallest weight increment as displayed when setting the weight capacity or weight divisions. [0.0 to 12] 20 Signal units are determined by units of setpoint 1 source or setpoint 2 source
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 4 of 15
Quick Key
Service Setting (password 9713) Field Setting Default/ Group
Address
Outputs Analog output 1 (flowrate) 2411 AO1 source (modbus address of signal) flowrate 8762 10 8520 2412 AO1 signal low FU 0.0 10 8522 2413 AO1 signal high FU FCAP 10 8524 2414 AO1 current low mA 4.000 10 8526 2415 AO1 current high mA 20.000 10 8528 2416 AO1 current (can override output signal) mA 10 8800 2417 AO1 signal (can override output signal) FU 10 8804
Analog output 2 (platform weight) 6/8xx21 2421 AO2 source (modbus address of signal) platform weight 8744 10 8530 6/8xx 2422 AO2 signal low WU 0 10 8532 6/8xx 2423 AO2 signal high WU WCAP 10 8534 6/8xx 2424 AO2 current low mA 4.000 10 8536 6/8xx 2425 AO2 current high mA 20.000 10 8538 6/8xx 2426 AO2 current (can override output signal) mA 10 8802 2427 AO2 signal (can override output signal) WU 10 8806
Digital outputs 2431 OUT1 function (& state22) 23 pulse output 48 11 8550 6/8xx 2432 OUT2 function (& state) running 57 11 8552 6/8xx 2433 OUT3 function (& state) run motor 56 11 8554 6/8xx 2434 OUT4 function (& state) healthy 60 11 8556 8xx24 2435 OUT5 function (& state) weight fault 112 11 8558 8xx 2436 OUT6 function (& state) belt speed fault 113 11 8560 8xx 2437 OUT7 function (& state) material feed 59 11 8562 8xx 2438 OUT8 function (& state) alarm alert 63 11 8564
Communications & Display Comms port 1 RS232 2511 COM1 baud rate (8 data, no parity, 2 stop) 19200 12 8580 2512 COM1 modbus address [1 to 30] 1 12 8582 2513 COM1 handshake enable [0=disable, 1=enable] 0 12 8584 2514 COM1 error count 12 8810
Comms port 2 RS485 2521 COM2 baud rate (8 data, no parity, 2 stop) 115200 12 8590 2522 COM2 modbus address[1 to 30] 1 12 8592 2523 COM2 error count 12 8812
Interface registers / Registers 1 25411 platform weight 12 8000 25412 belt speed 12 8002 25413 speed demand 12 8004 25414 no function no function 12 8006 25415 total weight 12 8008 25416 flowrate 12 8010 25417 control1 & control2 12 8012 25418 control3 & status1 12 8014 25419 status2 & status3 12 8016 25410 IOx & faults 12 8018
21 Only for MT6x and MT8x transmitters 22 Hint line shows state as (on) or (off) 23 See I/O Function & Alarm Table page 8. Use negative numbers to reverse the signal sense eg 16=motion (output on when weight is
in motion), -16=NOT motion (output off when weight is in motion) 24 Only for MW8xx transmitters
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 5 of 15
Quick Key
Service Setting (password 9713) Field Setting Default/ Group
Address
Interface registers / Registers 2 25421 no function 12 8020 25422 no function 12 8022 25423 no function 12 8024 25424 no function 12 8026 25425 speedC 12 8028 25426 ratioC 12 8030 25427 setpointC 12 8032 25428 control2 & control3 12 8034 25429 control1C & control1G 12 8036 25420 no function 12 8038
Printing & Design 2551 print settings and designs25 0 13 8922
Printing & Design / Print options 25521 print continuous rate26 0 13 8610 25522 disable designs [0=off, 1=on] 0 13 8616
Printing & Design / Designs 25531 print key design 13 1000 25532 print total key design 13 1100 25533 print remote design 13 1200 25534 print total remote design 13 1300 25535 times to print 13 1400 25536 print at times design 13 1500 25537 print settings design 13 1600 25538 print continuous design 13 1700
Printing & Design / Design subroutines 25541 system name design 13 2000 25542 print key sub design 13 2100 25543 print total key sub design 13 2200 25544 settings sub design 13 2300 25545 designs sub design 13 2400 25546 heading sub design 13 2500 25547 information sub design 13 2600 25548 user 1 sub design 13 2700 25549 user 2 sub design 13 2800
Printing & Design / Event Designs 25551 capture weight design 13 3000 25552 event design 13 3100 25553 temp 1 0 13 8612 25554 temp 2 0 13 8614 25555 perm 1 0 13 8596 25556 perm 2 0 13 8598 25557 date 13 8830 25558 time 13 8832
25 0=press EDIT then use up & down keys to select printout, 1=print quick settings, 2=print main settings, 3=print service settings,
4=print altered settings, 5=print altered designs, 6=print all designs 26 0=off, 1=100Hz, 2=50Hz, 3=20Hz, 4=10Hz, 5=5Hz, 6=2Hz, 7=1Hz, 8=2s, 9=5s, 10=10s, 11=30s, 12=1min, 13=2min, 14=5min,
15=10min
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 6 of 15
Quick Key
Service Setting (password 9713) Field Setting Default/ Group
Address
Display (MW99) / keys 0 to 9 locks 25611 key 1 lock.(start) 27 2 14 8620 25612 key 2 lock.(volumetric) 27 0 14 8622 25613 key 3 lock.(remote) 27 0 14 8624 25614 key 4 lock.(stop) 27 0 14 8626 25615 key 5 lock.(speed demand) 27 0 14 8628 25616 key 6 lock.(flow) 27 0 14 8630 25617 key 7 lock.(print total) 27 0 14 8632 25618 key 8 lock.(reset total) 27 0 14 8634 25619 key 9 lock.(batch weight) 27 0 14 8636 25610 key 0 lock.(zero) 27 0 14 8638
Display (MW99) / other key locks 25621 decimal point key lock.(print) 27 0 14 8640 25622 back key lock.(-) back key lock (-) 27 0 14 8642 25623 display key lock.(display) 27 0 14 8644 25624 alarm key lock (alarm) 27 0 14 8646
Display (MW99) / menu item locks 25631 menu item 1 lock 27 0 14 8650 25632 menu item 2 lock 27 0 14 8652 25633 menu item 3 lock 27 0 14 8654 25634 menu item 4 lock 27 0 14 8656 25635 menu item 5 lock 27 0 14 8658 25636 menu item 6 lock 27 0 14 8660 25637 menu item 7 lock 27 0 14 8662 25638 menu item 8 lock 27 0 14 8664 25639 menu item 9 lock 27 0 14 8666
Display (MW99) / Display customisation 25641 identification line [0=off to 1=on] 1 14 8608 25642 main line bar graph [0=off to 1=on] 1 14 8668 25643 secondary line options 28 1t95 14 8648 25644 display select sourceA 0 14 8600 25645 display select sourceB 0 14 8602 25646 menu sourceA 0 14 8604 25647 menu sourceB 0 14 8606
Information & Resets Transmitter Information 2611 system name 29 Belt Weigher 1 8844 2612 transmitter serial number 8852 2613 software version number 8854 2614 CPU type 8858 2615 CPU circuit number 8856 2616 terminal circuit number 8866
P-Module Information 2621 P-Module serial number 8860 2622 Last version used 8862
Reset settings 2631 reset loadcell calibration (1=reset to defaults) 0 8950 2632 reset comms settings (1= reset to defaults) 0 8952 2633 reset other settings (1= reset to defaults) 0 8954
27 0=never locked, 1=locked with pass code access, 2=always locked (pass code = 99) 28 1=hide current setpoint, 2=hide total/batch weight, 4=hide material feed stopped icon, 8=hide speed demand bar graph & icons,
32=hide setpoint units, 64=hide total/batch weight units, 128=include total name, 256=include limit icons (For multiple options, add together the numbers)
29 Defined by the system name design at Quick Key 35541
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 7 of 15
Quick Key
Service Setting (password 9713) Field Setting Default/ Group
Address
Reset designs 2641 reset all designs (1=reset to defaults) 0 8956
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 8 of 15
I/O Function & Alarm Table Input & Output Functions Description 0 no function/pulse input 0 1 stop 1 2 run 2 3 pause 3 4 4 5 volumetric mode 5 6 remote flowrate mode 6 7 7 8 hold flowrate 8 9 hold control 9 10 10 11 11 12 timer enable 12 13 13 14 14 15
inpu
t fu
nctio
n (le
vel s
ensi
tive
)
15
Cont
rol1
=
cont
rol1
_inp
uts
or
cont
rol1
_int
erna
l
or
cont
rol1
C
or
cont
rol1
G
16 acquire zero 0 17 1 18 2 19 3 20 4 21 set volumetric mode 5 22 reset volumetric mode 6 NOTES 23 toggle volumetric mode 7 24 set remote flowrate mode 8 25 reset remote flowrate mode 9
26 toggle remote flowrate mode 10
To invert signal, use negative value. e.g. for NOT run, use -2. IN1 is pulse input, other inputs are no function. OUT1 only. Other outputs are no function.
27 start 11 28 timer start 12 29 13 30 14 31
inpu
t fu
nctio
n (e
dge
sens
itive
)
15
Cont
rol2
32 reset total 0 33 totalise 1 34 2 35 3 36 4 37 5 38 6 39 7 40 print 8 41 print total 9 42 print remote 10 43 print total remote 11 44 12 45 13 46 14 47
inpu
t fu
nctio
n (e
dge
sens
itive
)
capture weight 15
Cono
trol
3
48 pulse output 0 49 1 50 2 51 3 52 4 53 5 54 in volumetric mode 6 55 7 56 run motor 8 57 running 9 58 paused 10 59 material feed 11 60 healthy 12 61 fault 13 62 alarm 14 63
outp
ut f
unct
ion
alarm alert 15
Stat
us1
64 0 65 holding flowrate 1 66 holding control 2 67 3 68 low flow cutout 4 69 5 70 6 71 7 72 8 73 9 74 10 75 11 76 timer output 12 77 13 78 clock active 14 79
outp
ut f
unct
ion
daylight saving time 15
Stat
us2
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 9 of 15
Output Functions & Alarms Description 80 limit 1 output 0 81 limit 2 output 1 82 2 83 3 84 4 85 5 86 6 87 7 88 8 89 9 90 10 91 11 92 12 93 13 94 disable designs 14 95
outp
ut f
unct
ion
MO2 fitted 15
Stat
us3
96 IN1 0 97 IN2 1 98 IN3 2 99 IN4 3 100 IN5 4 101 IN6 5 102 IN7 6 103 IN8 7 104 OUT1 8 105 OUT2 9 106 OUT3 10 107 OUT4 11 108 OUT5 12 109 OUT6 13 110 OUT7 14 111
outp
ut f
unct
ion
OUT8 15
IOx
Alarm Comments
112 weight fault 0 AI1 out of range: faulty loadcell or wiring weight too low or too high
113 belt speed fault 1 belt speed too high belt speed too low NAMUR sensor fault
114 flowrate fault 2 flowrate too high 115 not filling or discharging 3 material flow may be blocked 116 low flow 4 flowrate setpoint cannot be achieved 117 5 118 6 119 7 120 8 121 9 122 10 123 11 124 12 125 13 126 14 127
outp
ut f
unct
ion
& a
larm
no P-Module fitted 15
Faul
ts
fit P-Module 128 can't start stop input is on 129 130 unable to zero belt is not empty or requires recalibration 131 zero limited signal > 3mV/V 132 span limited signal too low to span 133 belt track error check belt lateral alignment 144 power supply brown out check power supply 145 error at power down totaliser and other data may be invalid 146 setting error at address ####
147 design error at address #### excess recursion at address ####
150 processor card alarm
FRAM error: unit requires servicing COP error: unit requires servicing RAM error: cycle power and check alarms controller fault: contact EMC
151 P-Module alarm FRAM error: unit requires servicing replace F-Chip with a P-Module 152 terminal card alarm cycle power and check alarms 153 MO1/MO2 card alarm FRAM error: unit requires servicing
alar
m
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 10 of 15
Connections MW95 Connection Diagram
+
0V
Belt Speed Tacho
output
Totaliserinput
0V
acquire zerorunreset total
running
healthy
+24V0V
Power Supply
MAD r1DB9F
To PC/PLC
optional sense(if used, then all -ve
excitations must connect to -EX1)
MAC
LOADCELL
2ndLOADCELL if
used
Power supply fuse less than 5A
23RXD
TXD
4
78
DTRCTSRTS
65SG
DSR
printprint totalstoppause
weight fault
material feedalarm alert
belt speed fault
flowrate outputplatform weight output
run motor
MAPDB25M
To Printer
23TXD
RXD
20
4DSRCTS
67SG
DTR
MD99d and transmitter can alternatively be connected COM1 to COM1 using an
MAC cable.
+12/24VPower CN1A1A2A3A4A7
0V+D-D0V/SCREEN
+EXL/C 1/3 CN2B1B2B3B4
B6B7
-EX1+SIG-SIG
+SEN-SEN
+EXC1C2C3C4
C6C7
-EX2+SIG-SIG
-EX3-EX4
L/C 2/4 CN3
D1D2D3D4D5D6
+12/24V+12/24V
IN1IN2IN3IN4
F1F2F3F4F5F6F7
+V1OUT1OUT2OUT3OUT4
0V0V
H1H2H3H4H5
A7
+5EX10V20mA0V20mA0V
CN4 Digital InputsModWeigh MW95 & MT6X or MT8X
MO2 option CN5
AI2
AO2
SUPPLY
A5A6
20mA0V
AO1
CN1 I/O
H6
+V2
COM2
0V/SCREEN
AI1
B5
C5 0V/SCREEN
RJ11RTS 0VTXD RXD0V CTS
COM1
E1E2E3E4E5E6
IN5IN6IN7IN8
MT8X
G1G2G3G4G5G6G7
OUT5OUT6OUT7OUT8
0V0V
MT8X
+12/24V+12/24V
0V/SCREEN
Digital InputsCN5
CN5/6 Digital Outputs
DigitalOutputsCN7
Input & output functions are
programmable
+12/24VPower12345
0V+D-D
IN7d
MD99d Display
COM2
SUPPLY
76 +S
0V
COM1
RJ11RTS 0VTXD RXD0V CTS
98
0VIN8d
515253545556
+12/24V+12/24V
IN3dIN4dIN5dIN6d
57585960616263
+V1OUT5dOUT6dOUT7dOUT8d
0V0V
35363738
33
+5EX10V
20mA0V
20mA0V
MO6
MO4/MO5
AI2d
AO2d34
3120mA0V
AO1d 32
640V
DigitalI/O option
Analogoption
Input & output functions are
programmable
MW95A only
Belt Speed Tacho
NAMUR+-
or
3 WIRE PNP
Keep all wiring separated from mains wiring Use shielded cable where indicated All 0V terminals internally connected
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 11 of 15
Motor VSD integration The following diagrams show various methods to connect a ModWeigh to a VSD drive or motor contactor.
VSD Drive, keypad run/stop
VSD Drive, VSD run/stop
VSD drive, start/stop buttons
Motor Contactor, keypad run/stop
Motor Contactor, run/stop buttons
Key
ModWeigh digital output
+
AOx
[INx, input function] ModWeigh digital input
ModWeigh analog output
[OUTx, output function]
motor contactor (mc)
mc
+24V 0V overload
run [INx, 2]
START STOP
mc disable RUN key do not use start function
motor contactor
run motor [OUTx, 56]
+24V 0V
NOT stop [INx, -1] overload
overload
VSD run input run motor [OUTx, 56]
+
AOx
+
VSD speed input 4-20mA
+24V 0V
NOT stop [INx, -1] VSD OK
start [INx, 27] START
STOP
run [INx,2] VSD running signal
+
AOx
+
VSD speed input 4-20mA
+24V 0V
disable RUN key do not use start function
4-20mA
VSD run input run motor [OUTx, 56]
+
AOx
+
VSD speed input 4-20mA
+24V 0V
NOT stop [INx, -1] VSD OK
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 12 of 15
Run/Stop/Pause Logic The following table describes how the status is affected by the inputs.
Inputs (Control1) Outputs (Status)
stop run pause start running paused run motor
1 X X X 0 0 0
0 1 0 X 1 0 1
0 0 0 0 0 0 0 0 X 1 X NC 1 0
0 0 0 1 0 1 0 0 1 1 1 0
Setpoint & Speed Demand Signals
Flowrate Calculation
06.0100
[%]1][
min]/[][]/[
+
=
correctionflowratemlengthplatform
mspeedbeltkgweightplatformhtflowrate
AI2 %
AI2d %
set local flowrate [8470]
greater of
slewrate limit
setpointC [8032]
current flowrate setpoint [8790]
>=0
ratio [8472]
ratioC [8030] >=0
X
multiply
remote flowrate [6]
speed demand [8792]
speedC [8028]
AI2 signal [8722]
set local flowrate [8470]
set local flowrate [8470]
calculate flowrate
% to signal
PI Control
Feed forward
>=0
volumetric mode [5]
manual speed set [120]
+
-
+
+
error [8798]
KEY
Entry Description
0 input or output off
1 input or output on
X dont care (either on or off)
NC no change
rising edge (input turns on) remains off since last stop
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 13 of 15
ModWeigh Design Codes Code Description
0 end of design ASCII
1 - 127 standard ASCII characters 128 - 191 reserved
Register Instructions 192 NOP no operation 193 RECALL register register is an ASCII Modbus address (8000 to 8992). It may take the form PpSsRrrrr where p is the port number,
s is the slave address and rrrr is the Modbus register. e.g. P2S3R8074 retrieves data on COM2, slave address 3 at register 8074. If either the port or slave_address are not specified, the values in the port and slave_address registers are used (see RECALL ).
194 RECALL register register 1 weight 17 temp 1 2 platform weight 18 temp 2 3 net weight 19 perm 1 4 zero weight 20 perm 2 5 tare weight 21 P_Module serial number 6 total weight 22-100 invalid argument 7 running total 101 with address in VALUE 8 peak weight 102 default_value 9 flow rate 103 minimum_value 10 belt speed 104 maximum_value 11 current flowrate setpoint 105 column 12 speed demand 106 memory 13 COM 2 modbus address 107 register_number 14 print settings & designs 108 port 15 transmitter serial number 109 slave_address 16 flowrate raw 110-225 invalid argument
195 STORE register register is an ASCII Modbus register (8000 to 8992). 196 STORE selects register. See RECALL instruction. 197 MENU action action
1 start_menu 5 next_service 2 next_operator 6 next_factory 3 next_quick 7 next_altered
198 DESIGN action 1 start_design 2 next_design 3 next_ altered _design
Print Instructions 200 PRINT_VALUE 201 PRINT_NAME 202 PRINT_UNITS 203 PRINT_HINT 204 PRINT_DATE 205 PRINT_TIME 207 PRINT_MENU_HEADING 208 PRINT_MENU_PATH 209 PRINT_QUICK_KEY 212 FORMAT format format is an ASCII format code of the form CcDdBb. c is the column width, d is the number of decimal places and
b is the count by. Any one or combination of the three parts can be included. (e.g. C10d2b5 sets the column width to 10, the decimal places to 2 and the count by to 5; C10 sets column width to 10). The default is 0.
213 NEWLINE 214 NEWPAGE 215 TAB is a number 1 to 99. Columns are numbered from 0. 218 LIST is number 1 to 99. If = 101, lists design number in VALUE. 219 DUMP is number 1 to 99. If = 101, lists design number in VALUE.
belt speed [m/s]
speed demand [%]
belt speed capacity
100% 20%
10capacityspeedbelt
belt speed fault after 10 sec-
Belt Speed Fault Detection
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 14 of 15
Calculation Instructions 220 VALUE number number is an ASCII number (e.g. 123.4) If there
is no number, then the stack is pushed up. 221 ADD VALUE = VALUE + Y 222 SUB VALUE = VALUE + Y 223 MUL VALUE = VALUE + Y 224 DIV VALUE = VALUE + Y 225 MOD VALUE = VALUE + Y 226 SWAP_VALUE_Y VALUE and Y swapped 227 ROLL stack rolled down 230 CLEAR_VALUE VALUE is set to zero 231 CLEAR_ALL VALUE, Y, Z and T all set to 0 232 INC_ VALUE VALUE = VALUE + 1
Calculations are done on a stack in RPN (reverse polish notation). When a value is entered onto the stack with a RECALL or VALUE instruction, the other values on the stack are moved up first. An instruction like ADD or MUL operates on the values in VALUE and Y and places the result in VALUE. Z is moved to Y and T is copied to Z. The operation follows the values. e.g RECALL VALUE 2 MUL., this multiplies the weight by 2. e.g. 2 + 3 x weight = VALUE 2 VALUE 3 RECALL MUL ADD
233 DEC_ VALUE VALUE = VALUE 1
235 CHANGE_SIGN sign of VALUE changed, plus and minus
STACK
RECALL or VALUE
ROLL ADD, SUB, MUL, DIV, MOD
236 ABS absolute value of VALUE T T lost / copied 237 INT integer value of VALUE (e.g. INT(12.54) = 12) Z 238 FIX fixed value of VALUE (e.g. INT(12.54) = 13) Y
VALUE 0 RESULT
Looping and Control Instructions 240 IF is a logical expression made up of one or more values and operators evaluated from left
to right. e.g. IN3 OR NOT IN4 = value [NOT] [operator] [value] [NOT] [operator] NOT reverses the sense of the value, (e.g. true becomes false).
value test value test 1-127 See I/O Function & Alarm Table 181 end_of_design 182 end_of_menus 151 VALUE>=0 183 new_menu_heading 152 VALUE>0 184 new_menu_path 153 VALUE=0 185 design_altered 154 VALUE0 186 clock_active 155 VALUEVALUE 159 Y=VALUE operator result 160 YVALUE AND true if both values are true 161 Y
EMC INDUSTRIAL GROUP LTD Setup Summary
MW95A_Setup_Summary_SV3.60a Page 15 of 15
To Adjust A Setting Press the EDIT key to allow changes to the selected setting. If editing is locked, a password will be requested. For Quick setup and Main setup, the password is 111. For Service setup the password is 9713. For Altered setup there is no password as settings are display only.
Use the keypad and/or UP and DOWN arrow keys to increase or decrease the displayed setting. Some settings allow only one method, and some are display only.
Holding either key down will automatically continually increase or decrease the value.
Alarms An alarm is indicated by the light above the ALARM key flashing. An alarm number will flash in the display while a fault is active or until it is acknowledged. 30
Press the ALARM key to see the Alarms menu and acknowledge the alarms. The menu shows a list of the previous alarms.
For details on an alarm in the list, use the UP, DOWN and ENTER keys, or key in the number next to the alarm.
Press BACK to exit the Alarms menu, or press 6 to clear the alarms and exit the menu.
Modbus Access The Modbus protocol supported is RTU. (ASCII mode is not supported). Transmission is with 8 data bits, no parity and 2 stop bits. The following function codes are supported;
3 - read holding registers
4 - read input registers
6 - preset single register
16 - preset multiple registers (10 hex)
23 - read/write multiple registers (17 hex)
Data can be accessed as floats (4 bytes) or integers (2 or 4 bytes). Floats are preferred as the data is stored in engineering units. The following table shows how the addresses shown in the setup sum-mary are translated into Modbus register addresses. (Note with Modbus protocol, the actual address transmitted is one less than the register address. With some systems, you must specify an address one less than expected).
The interface registers starting at address 8000 contain the most common data required for Modbus access.
Modbus registers are 2 bytes, so 4 byte floats or 4 byte integers are stored in two consecutive regis-ters.
The following tables provide information for Modbus access to the transmitter. Address Data description
1000 to 4999 Design strings (contains printouts and programs) 8000 to 8029 Interface registers (PLC access) 8030 to 8699 Configuration settings (full instrument calibration) 8700 to 8899 Data outputs (values produced by the instrument) 8900 to 8999 Activations (when set, a process is activated)
Address Modbus Register Address Data description 1000 to 4999 Address 1000 to 4999 Design strings 8000 to 8999 6000 + (Address - 8000) / 2 6000 to 6599 Integer (16 bit) (limited by integer range) 8000 to 8999 7000 + (Address - 8000) 7000 to 7999 Long integers (32 bit words) 8000 to 8999 Address 8000 to 8999 Float (IEEE 4 byte reals)
COPYRIGHT 2006 by EMC Industrial Group Ltd.. P.O. Box 101 444, North Shore, Auckland 0745, New Zealand.
56 Tarndale Grove, Albany, North Shore, Auckland 0632.
Telephone +64-9-415 5110. Facsimile +64-9-415 5115.
E-mail [email protected] Web www.emc.co.nz
Re-distribution of this information is prohibited
30 Refer to the ALARM list for the alarm numbers, page 9.