MDB-1402
MAR. 18, 2014
REVISIONS
DATE
DRAWN BY
SHEET TITLE
PROJECT NO.
SHEET
MARLIN DESIGN BUILD
OF
1405 HILLSBOROUGH STRALEIGH, NC 27605
mapleENGINEERING, pllc
plumbing mechanical electrical
LIC.#: P-0990P:919-341-4247 F:919-890-3797
PO Box 1852Cary, NC 27512Phone: (919) 291-6736
3/18/14
P0.11 2
RDG
PLUMBINGSCHEDULES
DETAILS& NOTES
VALVE SCHEDULETAG
BV-1
CV-1
CV-2
TV-1
PRV-1
FULL-PORT BALL VALVE
DESCRIPTION
PRESS. RED. VALVE
BRONZE CHECK VALVE
IND. TEMP. VALVE
DBL CHECK VALVE
TV-2 MASTER TEMP. VALVE
WATTS SD-2-MF (<1/2"), WATTS 9D (1/2"+)
WATTS CV
WATTS USG-B
WATTS 223-S
WATTS LFB6081
GBV-1 GAS BALL VALVE APOLLO 80 SERIES
NOTES:1. SEE PLAN FOR SIZE. VALVE SIZE TO EQUAL LINE SIZE.2. BALL VALVES TO INCLUDE REMOVABLE HANDLES.3. IF AVAILABLE, VALVES MAY BE THREADED OR SWEATED CONNECTIONS. USE EXTREME
CARE AND LOW TEMP SOLDER TO PROTECT VALVE SEATS IF SWEATED CONNECTIONSARE USED.
4. VERIFY SOLENOID VALVE DETAILS W/ E.C. & KITCHEN EQUIPMENT/HOOD MFG.
(SET TO 40 PSI)
MFG & MODEL (OR EQUAL)
N170-M3 CSUT(SET TO 110°F DISCHARGE)
GSV-1 GAS SOLENOID VALVE
BV-2 BALANCING VALVE BELL & GOSSETT CB(CIRCUIT SETTER PLUS, W/ TEST PORTS)
BY OTHERS
(ASSE 1022 APPROVED)
SHOCK ARRESTOR SCHEDULEFIXTURE UNITS
IND. FIXTURE
12 - 32
33-60
114-154
61-113
SEE FIXTURE SCHEDULE
UNIT SIZE (CONN. SIZE)
D (1")
C (1")
E (1")
B (3/4")
SIOUX CHIEF "MINI-RESTER"
MFG & MODEL (OR EQUAL)
1-11 A (1/2") SIOUX CHIEF "HYDRA-RESTER"
SIOUX CHIEF "HYDRA-RESTER"
SIOUX CHIEF "HYDRA-RESTER"
SIOUX CHIEF "HYDRA-RESTER"
SIOUX CHIEF "HYDRA-RESTER"
NOTES:1. LOCATED SHOCK ARRESTORS IN ACCESSIBLE LOCATION OR PROVIDE SIOUX CHIEF
BRAND ARRESTORS ONLY.2. SEE PLAN, RISERS, SCHEDULES FOR ARRESTER LOCATIONS. IF LOCATION NOT INDICATED
INSTALL IN ACCORDNCE W/ MFG GUIDELINES.
PLUMBING LEGEND
PIPE DOWN
FLOOR DRAIN
VENT PIPING
VALVE
PIPE UP
CHECK VALVE
DOMESTIC HOT WATER PIPING
WASTE (SANITARY SEWER)
DOMESTIC COLD WATER PIPING
CONNECT TO EXISTING POINT
GAS PIPINGG
EXISTING PIPING/EQUIPMENT
VALVE
DEMO TO POINT
CLEANOUT
G.C.
M.C.P.C.
VW
HB
HW
FS
FDFR
VENTWASTE
GENERAL CONTRACTOR
MECHANICAL SUB-CONTRACTORPLUMBING SUB-CONTRACTOR
HOSE BIBB
HOT WATER
FLOOR DRAIN
FLOOR SINKFROM
AAV
AFF
FCO
ABV
DNE.C.
CW
AIR ADMITTANCE VALVE
ABOVE FINISHED FLOOR
FLOOR CLEAN OUTELECTRICAL SUB-CONTRACTOR
COLD WATERDOWN
ABOVE
HUB DRAINHD
BV BALL OR BALANCING VALVE (SEE SCHED)CV CHECK VALVE
PRV PRESSURE REDUCING VALVE
TV TEMPERING VALVE
GBV GAS BALL VALVE
GSV GAS SOLENOID VALVE
BFP BACK FLOW PREVENTER
WH WATER HEATERWHD WALL HYDRANT
WF WALL FAUCET
SS SANITARY SEWER
AHJ AUTHORITY HAVING JURISDICTION
DEMO PIPING/EQUIPMENT
PLUMBING GENERAL NOTESI. GENERAL REQUIREMENTS:
1. PLUMBING CONTRACTOR IS TO FURNISH AND PAY FOR ALL LABOR, MATERIAL,EQUIPMENT, PERMITS & FEES REQUIRED FOR THE COMPLETE INSTALLATION OF ALLSYSTEMS IN THIS SECTION OF WORK.
2. ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH NC PLUMBING CODEAND ALL OTHER APPLICABLE CODES. PC IS TO COORDINATE W/ G.C. INREGARDS TO PROJECT TIMELINE, WORK HOURS, AS WELL AS ANY BONDING ORINSURANCE REQUIREMENTS.
3. ALL PLUMBING FIXTURES AND PLUMBING SYSTEM EQUIPMENT SHALL BE PROVIDEDCOMPLETE WITH ALL ACCESSORIES, HANGERS, VALVES, STOPS, TAILPIECES, TRAPS,FAUCETS, STRAINERS, ETC REGARDLESS OF PRESENCE ON PLANS. SEE FIXTURESCHEDULE.
4. ALL EQUIPMENT, MATERIALS AND INSTALLATION SHALL BE GUARANTEED TO BEFREE OF DEFECTS FOR A PERIOD OF ONE (1) YEAR AFTER FINAL ACCEPTANCE OFWORK OR IN ACCORDANCE WITH THE MANUFACTURER'S STANDARDGUARANTEE, IF LONGER. EXISTING EQUIPMENT IS EXCLUDED FROM WARRANTYREQUIREMENT.
5. THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL LOCATION ANDARRANGEMENT OF ALL MATERIALS AND EQUIPMENT. THE DRAWINGS SHALL BEFOLLOWED AS CLOSELY AS BUILDING CONSTRUCTION AND ALL OTHER WORKWILL PERMIT.
6. DO NO SCALE DRAWINGS FOR MEASUREMENT.
7. INFORMATION GIVEN IN SCHEDULES INCLUDES BOTH DESCRIPTION OF PRODUCTAND MANUFACTURER'S MODEL #. IF CONFLICT IS PRESENT BETWEEN DESCRIPTIONAND MODEL #, EQUIPMENT DESCRIPTION SHALL TAKE PRECEDENT. IN CASE OFCONFLICT BETWEEN THE PLANS AND NOTES/SPECIFICATIONS OR CONFLICTBETWEEN INFORMATION PRESENTED ON THE PLANS OR IN THENOTES/SPECIFICATIONS, THEN THE MOST RESTRICTIVE SHALL TAKE PRECEDENT.
8. BEFORE BID PC IS RESPONSIBLE FOR CLARIFYING W/ G.C. ANY CONFUSION INREGARDS TO RESPONSIBILITY OF WORK TO BE PERFORMED OR MATERIALS TO BEPROVIDED. THE SUBMITTAL OF THE BID BY THE CONTRACTOR WILL BE HELD ASPROOF THAT THE CONTRACTOR UNDERSTANDS THOROUGHLY AND COMPLETELYTHE SCOPE OF THE WORK INVOLVED, AND HAS INCLUDED ON THE BID ALL THENECESSARY ITEMS TO CARRY OUT THIS SECTION OF WORK.
9. ALL EXISTING EQUIPMENT AND SYSTEMS ARE ASSUMED BY ENGINEER TO BE INGOOD WORKING ORDER. BEFORE BEGINNING WORK P.C. IS TO ENSURE ANYEQUIPMENT & SYSTEMS TO REMAIN ARE PROPERLY FUNCTIONING. NOTIFY G.C.IMMEDIATELY IF PROBLEMS ARE DISCOVERED.
10. ALL QUESTIONS MUST BE SUBMITTED IN RFI FORMAT TO THE ARCHITECT AND MUSTBE ADDRESSED BY THE APPROPRIATE DESIGNER OF RECORD PROIR TO BECOMINGA PROPOSED CHANGE ORDER.
11. P.C. IS TO REVIEW COMPLETE DRAWING SET. P.C. IS RESPONSIBLE FOR WORKEXPLICITLY SHOWN AND WORK IMPLIED. UNLESS OTHERWISE NOTED FINALPLUMBING CONNECTION TO ALL EQUIPMENT, FIXTURES, ETC IS THE RESPONSIBILITYOF THE P.C..
II. DIVISION OF WORK:
1. ALL ROOF PENETRATIONS, FLASHING, ETC ARE TO BE PERFORMED BY ROOFINGCONTRACTOR.
2. ALL LOW VOLTAGE WIRING RELATED TO PLUMBING EQUIPMENT AND SYSTEMS ISTHE RESPONSIBILITY OF THE PLUMBING CONTRACTOR. ALL HIGH VOLTAGECONNECTIONS TO PLUMBING EQUIPMENT, INCLUDING DISCONNECTS TO BEPROVIDED AND INSTALLED BY E.C.
3. G.C. TO BE RESPONSIBLE FOR PROVIDING AND INSTALLING ANY ACCESS DOORSRELATED TO PLUMBING SYSTEM (W/ EXCEPTION OF CLEANOUT COVERS, BY P.C.).P.C. RESPONSIBLE FOR COMMUNICATING TO G.C. SIZE AND LOCATION OF REQ'DACCESS DOOR(S).
4. PLUMBING CONTRACTOR IS TO EMPLOY THE SERVICES OF THE G.C. FOR CUTTINGAND PATCHING OF WALLS, FLOORS & CEILINGS RELATED TO THE INSTALLATION OFPLUMBING EQUIPMENT & SYSTEMS.
5. G.C. TO BE RESPONSIBLE FOR PROVIDING AND INSTALLING ANY WATER HEATERPLATFORMS, EITHER FLOOR/WALL MOUNTED OR SUSPENDED. P.C. TOCOMMUNICATE REQ'S TO G.C.
6. ALL GAS PIPING IS BY MECHANICAL CONTRACTOR.
III. MATERIALS:
1. ALL MATERIALS SHALL BE NEW UNLESS OTHERWISE SHOWN OR SPECIFIED.
2. ALL MATERIALS INSTALLED IN RETURN PLENUM ARE TO BE PLENUM RATED.
3. PIPING MATERIALS AND FITTINGS SHALL BE AS FOLLOWS:WASTE & VENT (ABOVE & BELOW SLAB):
PVC PIPE, PVC SOCKET FITTINGS, AND SOLVENT-CEMENTEDFITTINGS.
DOMESTIC WATER (BELOW SLAB):TYPE 'K' COPPER.
DOMESTIC WATER (ABOVE SLAB):TYPE 'L' COPPER WITH SWEATED SOCKET FITTINGS. THREADEDFITTINGS MAY BE USED AT VALVES, FIXTURES & SIMILAR.ORCPVC PIPING WITH SOLVENT-CEMENTED FITTINGS. THREADEDFITTINGS MAY BE USED AT VALVES, FIXTURES & SIMILARORPEX PIPING WITH FLARED OR MECHANICAL JOINTS/FITTINGS.
4. INSULATION IS REQUIRED ON THE FIRST 8 FEET OF HOT WATER PIPING FROM WATERHEATERS ON NON-CIRCULATING SYSTEMS. INSULATION IS REQUIRED ON ALL HOTWATER PIPING THAT IS PART OF A HOT WATER CIRCULATION LOOP & THE FIRST 8FEET OF BRANCH LINES FROM CIRCULATION LOOP. INSULATION TO BE EQUAL TO"ARMAFLEX" PIPE INSULATION W/ SEALED OR TAPED SEAMS. INSULATION TO BEMIN. 12" THICK FOR NON CIRCULATING SYSTEMS AND MIN. 1" THICK FORCIRCULATING SYSTEMS. INSULATION TO HAVE A CONDUCTIVITY NOT EXCEEDING0.27 (BTU-INCH)/(HR-FT^2-°F) OR IN ACCORDANCE W/ LOCAL CODESWHICHEVER IS MORE STRINGENT.
5. PROVIDE HANGERS & SUPPORTS APPROVED FOR USE BY 2012 NC PLUMBINGCODE.
IV. COORDINATION:
1. BEFORE BEGINNING WORK INVERT ELEVATIONS SHALL BE ESTABLISHED. PC IS TOENSURE PROPER SLOPES OF ALL WASTE AND STORM PIPING CAN BE MAINTAINED,CONTACT ENGINEER IMMEDIATELY IF PROBLEM/ISSUE IS DISCOVERED.
2. P.C. TO COORDINATE LOCATION OF ALL ROOF PENETRATIONS W/ ROOFINGCONTRACTOR & MECHANICAL CONTRACTOR. P.C. & M.C. TO COORDINATE TOENSURE NO PLUMBING VENTS ARE LOCATED WITHIN 10' OF ANY OUTSIDE AIRINTAKES.
3. P.C. TO COORDINATE W/ G.C. AND ARCH PLANS TO ENSURE NECESSARYBACKING/SUPPORTS ARE INSTALLED TO ALLOW INSTALLATION OF PLUMBINGFIXTURES.
4. THE PLUMBING CONTRACTOR SHALL COORDINATE CLOSELY WITH ALL OTHERTRADES TO AVOID CONFLICT AND ENSURE OTHER TRADES PROVIDE MEASURES TOACCOMMODATE PLUMBING WORK (I.E. ACCESS DOORS, SLAB/WALL/ROOFOPENINGS, ELECTRICAL CONNECTIONS, ETC)
5. PIPING SHOULD BE COORDINATED WITH ALL STRUCTURAL FOOTINGS ANDFOUNDATIONS. PIPE SHOULD BE OFFSET TO AVOID CONTACT WITH FOOTINGSAND FOUNDATION WALLS. IF PIPING MUST RUN UNDERNEATH A FOOTING ORTHROUGH A FOUNDATION WALL, THE PIPE MUST BE INSTALLED WITH A RELIEVINGARCH OR IN A PIPE SLEEVE.
6. P.C. TO REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS OFPLUMBING FIXTURES.
V. EXECUTION:
1. P.C. TO FOLLOW MANUFACTURER'S INSTRUCTIONS WHEN INSTALLING PLUMBINGEQUIPMENT. ENSURE REQUIRED MAINTENANCE ACCESS AND CLEARANCES AREMAINTAINED. IF CONFLICT EXISTS BETWEEN THESE PLANS AND MFG INSTRUCTIONSCONTACT ENGINEER.
2. P.C. RESPONSIBLE FOR EXECUTING ALL CODE REQUIRED TESTS AND INSPECTIONS,INCLUDING BUT NOT LIMITED TO, LEAK & PRESSURE TESTING OF GAS, WASTE, VENT& WATER PIPING AND SANITIZING OF WATER PIPING.
3. ENSURE PIPING LOCATED ON EXTERIOR WALLS (OR OTHER WALLS EXPOSED TOFREEZING CONDITIONS) IS INSTALLED ON WARM-SIDE OF WALL INSULATION.
4. ANY NOTCHING, DRILLING, BORING OR OTHER ALTERATION TO BUILDINGSTRUCTURE SHALL BE PERFORMED IN A CODE APPROVED METHOD AND NOTTHREATEN THE INTEGRITY OF THE BUILDING STRUCTURE.
5. SUPPORT ALL PIPING IN ACCORDANCE W/ 2012 NC PLUMBING CODE. ANYSUSPENDED MATERIALS SHALL BE DIRECTLY SUPPORTED BY THE BUILDINGSTRUCTURE.
6. PROVIDE A U.L. LISTED ASSEMBLY FOR ALL PENETRATIONS THRU FIRE RATED WALLS,FLOORS & CEILINGS.
7. PENETRATIONS OF ALL EXTERIOR WALLS, FLOORS AND CEILINGS SHALL BE SEALEDIN AN AIR TIGHT MANNER AND IN ACCORDANCE W/ 2012 NCECC APPENDIX 2DETAILS.
8. CLEANOUT PLUGS SHALL BE INSTALLED IN ACCORDANCE WITH PLUMBING CODEREQUIREMENTS. PROVIDE CLEANOUTS AS PLANS INDICATED AND AT THE BASE OFALL WASTE STACKS, AT EVERY FOUR 45 DEGREE TURNS, AT EVERY 100 FEET, AND ATTHE BASE OF ALL ROOF LEADERS. CLEANOUTS SHALL BE PLACED IN READILYACCESSIBLE LOCATIONS.
9. SUPPLY BRANCH LINES SERVING MORE THAN (1) FIXTURE SHALL INCLUDE SHUT-OFFVALVE. LABEL VALVE AND LOCATE AS CLOSE TO RISER/MAIN AS POSSIBLE. (NCPC606.2.1)
10. VALVES NOT DIRECTLY AT EQUIPMENT SHALL BE LABELED INDICATING THE FIXTUREOR AREA SERVED. (NCPC 606.4)
11. WATER HEATER SHALL BE FILLED WITH WATER AND PURGED AS SOON AS INSTALLEDOR IN NO EVENT LATER THAN GAS/ELECTRIC HOOK-UP.
12. COPPER PIPING SHALL BE PROTECTED AGAINST CONTACT WITH MASONRY ORDISSIMILAR METALS. ALL HANGERS, SUPPORTS, ANCHORS, AND CLIPS SHALL BECOPPER OR COPPER PLATED. WHERE COPPER PIPING IS CARRIED ON IRONTRAPEZE HANGERS WITH OTHER PIPING, SATISFACTORY AND PERMANENTELECTROLYTIC ISOLATION MATERIAL SHALL PROTECT THE COPPER AGAINSTCONTACT WITH OTHER METALS.
13. WHERE COPPER PIPING IS SLEEVED THROUGH MASONRY, SLEEVES SHALL BECOPPER OR RED BRASS. WHERE COPPER MUST BE CONCEALED IN A MASONRYPARTITION OR AGAINST MASONRY, CONTACT SHALL BE PREVENTED BY COATINGTHE COPPER HEAVILY WITH ASPHALTIC ENAMEL AND PROVIDING 15# ASPHALTSATURATED FELT BETWEEN THE PIPE AND MASONRY.
14. ALL PIPE INSULATION SHALL RUN CONTINUOUSLY THROUGH FLOORS, WALLS, ANDPARTITIONS. PIPE INSULATION SHALL BE MITERED AT ELBOWS AND TEES TO ENSURECOMPLETE COVERAGE OF PIPING.
15. PROVIDE SHUT OFF VALVES ON THE FIXTURE SUPPLY TO EACH PLUMBING FIXTURE,APPLIANCE, OR MECHANICAL EQUIPMENT.
16. VACUUM BREAKERS SHALL BE PROVIDED FOR ALL FIXTURES TO WHICH HOSES MAYBE ATTACHED. VACUUM BREAKERS SHALL BE PERMANENTLY ATTACHED.
17. THE PLUMBING CONTRACTOR SHALL PROVIDE WATER HAMMER PROTECTION ONALL WATER DISTRIBUTION PIPING SERVING EQUIPMENT W/ QUICK CLOSINGVALVES (ICE MAKERS, DISHWASHERS, FLUSH VALVES, WASHING MACHINES, WATERCOOLERS, ETC.) SEE SHOCK ARRESTOR SCHEDULE.
18. ACCESS DOORS TO BE PROVIDED FOR ALL VALVES AND DEVICES REQUIRINGACCESS WHEN LOCATED IN WALLS OR ABOVE INACCESSIBLE CEILINGCONSTRUCTION. ACCESS DOORS TO BE RATED WHERE INSTALLED IN RATEDASSEMBLIES.
19. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALLPLUMBING EQUIPMENT FROM FOREIGN MATERIAL DURING CONSTRUCTION(PAINT, SPACKLE, ETC.). UPON COMPLETION OF WORK THE PLUMBINGCONTRACTOR SHALL CLEAN, WASH, ETC ALL ITEMS AND EQUIPMENT WITHIN HISSCOPE OF WORK AND LEAVE ALL ITEMS BRIGHT AND CLEAN.
20. PROVIDE PRESSURE REDUCING VALVE IF INCOMING WATER PRESSURE EXCEEDS 80PSI.
21. NO INSULATION PERMITTED ON BACKFLOW PREVENTOR ASSEMBLY.
TYPEFIXTUREMARK REMARKSHWCW
MOUNTINGTYPE WASTE
SUPPLIESAND STOPSSIZE
DRAIN
HANDLESSPOUT
FAUCET/VALVE
CENTERS VENT
PIPE SIZESSTYLEMATERIALMANUFACTURER MODEL NO.
PLUMBING FIXTURE SPECIFICATIONS AND CONNECTION SCHEDULE
MODEL NO.MANUFACT.
WATERCLOSET FLOORVITREOUS
CHINA2835.128 - - - - - -Q894AC12
FLUSHTANK
AMERICANSTANDARD
WATTS WITH NO LID.PROVIDE OPEN FRONT SEAT
ELONGATEDADAP-1
WALLVITREOUSCHINA0355.012 CENTER LEVER GRID Q894AB20
WALLMOUNT
AMERICANSTANDARD
WATTS MOUNT AT ADA HEIGHT.W/ WALL BRACKET. 0.5 GPM.
D-SHAPEADAP-2 LAVATORY 407171H
CFG3-HOLE
4"
COUNTERCENTER LEVER GRID Q894AB20WATTS 0.5 GPM.
P-3 407171HCFG
3-HOLE4"VITREOUS
CHINA0467.028DROPIN
AMERICANSTANDARD COUNTER TOP
ADALAVATORY BARRIER FREE.
WASHERBOX WALL- - - - - -
W/ QTR TURN VALVES & SHOCKP-4 OATEY 38980 RECESSED -METAL STEEL ARRESTORS. W/ FACEPLATE.
W/ TAIL PIECE. REVERSIBLE BOX.
WALLCASTBRONZE009 - - - - - -RED. PRESS.
ZONE DISCHARGE TO DRAIN W/ AIR GAP.PROVIDE REQ'D CLEARANCE.BFP-1 BACK FLOW
PREVENTER WATTS HORIZONTAL -FOLLOW MFG'S INSTRUCTIONS.
NOTES:1. ALL FIXTURE COLORS & FINISHES TO BE APPROVED BY OWNER & ARCHITECT BEFORE PURCHASING.2. PROVIDE P-TRAP AND SUPPLY LINE SAFETY COVERS FOR ALL ADA SINK AND LAVATORY INSTALLATIONS.3. WATER CLOSET HANDLES TO BE LOCATED ON "WIDE SIDE" OF STALL FOR ADA FIXTURES.4. SEE DETAIL SHEET FOR ADDITIONAL ITEMS TO BE PROVIDED/INSTALLED W/ FIXTURES LISTED ABOVE.
PLATFORMGLASSLINEDES6 40 DOLNS - - - -STATE
WATER HEATERS
38 GALLON, 6.0KW, 208V/1Ø.WH-1 WATER
HEATER ELECTRIC LOWBOY --- 30GPH @ 80°F RISE.SET TO 110°F. SEE DETAIL.
FLOOR-- - - - PEDICURE CHAIR, SELECTED BY -
P-5 FLOOR - OWNER. INSTALLED BY P.C. PEDICURECHAIR
- - -W/ VACUUM BREAKER.
AIR ADM.VALVE PIPEABS,
PVC- - - - - -
W/ ACCESS COVER (IF REQ'D).AAV STUDOR 20301 MINI-VENT PLN
SEE-THREADED
FLOORCLEANOUT FLOORCO-2450 - - - - -
FLOORFINISHEDFCO -ADJUSTABLE ZURN NICKEL CVR.
PVC BODY, -PLANSEE
C.W. TO FIXTURES
HEATERWATER
1" DRAIN LINETO EXTERIOR.
HBPLATFORM
EXPANSION TANK
H.W. TO FIXTURES
DISCHARGE FULL SIZEOF VALVE DISCHARGE.SPILL INTO DRAIN PAN
TEMPERATURE ANDPRESSURE RELIEF VALVE
VACUUMBREAKER
CONBRACO 78-RV SERIESBRONZE SHUT-OFF VALVEWITH THERMAL EXPANSIONCONTROL VALVE.
APPROVED TYPERELIEF VALVE, NEXTLOWER RATING ASVALVE
1-1/2" DEEP GALV.DRAIN PAN
BALLVALVE
NOTE:1. INSTALL WATER HEATER PER MANUFACTURER REQUIREMENTS2. PROVIDE HEAT TRAP ON CW AND HW LINES PER ENERGY CODE3. ELEVATE DRAIN PAN AS NECESSARY TO ALLOW PROPER FLOW TO HUB DRAIN
CW SUPPLY
REMOTE READ SUB METER BYOWNER OR INDEPENDENTCONTRACTOR, COORDINATEDIMENSIONS, EXACT LOCATIONAND ELECTRICAL REQ.
WATER HEATER ON PLATFORM BYG.C. SIZE PER LOCAL SIESMICREQUIREMTNS AND TOTAL WEIGHTOF WATER HEATER FULL OFWATER.
CHECKVALVE
UNION
1 NO SCALE
WATER HEATER DETAIL (PLATFORM)
SOIL PIPE
TILE, CARPET, CONC., ETC.
TOP SUITABLE FORFINISHED FLOOR,
FINISH FLOOR LEVEL
2 NO SCALE
FLOOR CLEANOUT DETAIL
NOTE:CONFIRM FIXTURESELECTIONS WITH OWNERPRIOR TO BID.
MDB-1402
MAR. 18, 2014
REVISIONS
DATE
DRAWN BY
SHEET TITLE
PROJECT NO.
SHEET
MARLIN DESIGN BUILD
OF
1405 HILLSBOROUGH STRALEIGH, NC 27605
mapleENGINEERING, pllc
plumbing mechanical electrical
LIC.#: P-0990P:919-341-4247 F:919-890-3797
PO Box 1852Cary, NC 27512Phone: (919) 291-6736
3/18/14
FIRE RATING LEGEND1-HR WALL2-HR WALL
P1.12 2
RDG
PLUMBINGPLAN
& RISERS
1 SCALE: 1/4" = 1'-0"
PLUMBING PLAN
RestrmPassage
OfficeWaxing
Waxing
Pedicure Area
Manicure Area
Reception
P-2
P-2 P-1
P-2
P-4
P-3
EXIST CW OVERHEADFR METER & BLDG RPZ
EXIST. S.S.
2
1
NOTE:P.C. TO VERIFY EXISTINGLINES. P.C. TO TAKE ALLMEASURES POSSIBLE TOENSURE GREASY WASTEAND SANITARY SEWERSYSTEMS DO NOT BECOMEINTERCONNECTED. P.C.RESPONSIBLE FOR ANYINTERCONNECTION THATOCCURS.
P-5
1
2 NO SCALE
WASTE/VENT RISER
3 NO SCALE
WATER RISER
P-5
P-5
P-5
P-5
P-5
FCO
FCO
HW/CWIN FURROUT
HW/CWIN FURROUT
WH-1ABV CLG
HW/CWIN FURROUT
3
3
COLUMN
4
4
4
FINISH FLOOR2" TO S.S. FLEXIBLE CONNECTION
1 1/2"1-1/2" AAV
2" P-TRAP
4 NO SCALE
CHAIR DETAIL
BV-1
GENERAL NOTES - THIS SHEET1. ITEMS SHOWN IN FAINT & HATCHED ARE TO BE DEMO'D OR
RELOCATED. ITEMS SHOWN IN FAINT ARE EXISTING TOREMAIN. NEW OR RELOCATED ITEMS ARE SHOWN IN BOLD.SEE LEGEND.
2. P.C. TO VERIFY EXACT SIZE, LOCATION, INVERT & DIRECTIONOF EXISTING LINES BEFORE BEGINNING WORK.
3. P.C. TO VERIFY THAT NO FIXTURES ARE CONNECTEDUPSTREAM OF BACK FLOW PREVENTER.
4. P.C. TO CONFIRM EXACT LOCATION, SIZE & METHOD OFPLUM. CONNECTIONS TO PEDICURE CHAIRS W/ OWNERBEFORE BEGINNING WORK.
TAGGED NOTES - THIS SHEET1 CLEARLY LABEL ALL PORTIONS OF CW LINE UPSTREAM
OF BFP "DO NOT TAP".2 BACK FLOW PREVENTER BFP-1 LOCATED ON BACK
WALL. DRAIN TO EXTERIOR. ENSURE REQ'DCLEARANCES CAN BE MAINTAINED. CONFIRMLOCATION WITH OWNER & G.C.
3 HW/CW CONNECTIONS TO CHAIR W/ CV-1'S &DOUBLE CHECK VALVES. CONFIRM EXACT CHAIRLOCATION & CONNECTIONS WITH OWNER. TYPICAL.
4 HW/CW DN W/ VALVES & ACCESS PANEL.
MDB-1402
MAR. 18, 2014
REVISIONS
DATE
DRAWN BY
SHEET TITLE
PROJECT NO.
SHEET
MARLIN DESIGN BUILD
OF
1405 HILLSBOROUGH STRALEIGH, NC 27605
mapleENGINEERING, pllc
plumbing mechanical electrical
LIC.#: P-0990P:919-341-4247 F:919-890-3797
PO Box 1852Cary, NC 27512Phone: (919) 291-6736
3/18/14
M0.11 3
BTM
MECHANICAL SCHEDULES
& NOTES
HVAC GENERAL NOTES
I. GENERAL REQUIREMENTS:
1. MECHANICAL CONTRACTOR IS TO FURNISH AND PAY FOR ALL LABOR, MATERIAL,EQUIPMENT, PERMITS & FEES REQUIRED FOR THE COMPLETE INSTALLATION OF ALLSYSTEMS IN THIS SECTION OF WORK.
2. ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH NC MECHANICAL CODESAND ALL OTHER APPLICABLE CODES. MC IS TO COORDINATE W/ G.C. IN REGARDSTO PROJECT TIMELINE, WORK HOURS, AS WELL AS ANY BONDING OR INSURANCEREQUIREMENTS.
3. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED COMPLETE WITH ALLACCESSORIES, HANGERS, SUPPORTS, CONTROLS, ETC FOR A FULLY FUNCTIONINGSYSTEM REGARDLESS OF PRESENCE ON PLANS.
4. ALL EQUIPMENT, MATERIALS AND INSTALLATION SHALL BE GUARANTEED TO BE FREEOF DEFECTS FOR A PERIOD OF ONE (1) YEAR AFTER FINAL ACCEPTANCE OF WORKOR IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD GUARANTEE, IFLONGER. ALL COMPRESSORS ARE TO INCLUDE FIVE (5) YEAR WARRANTY. EXISTINGEQUIPMENT IS EXCLUDED FROM WARRANTY REQUIREMENT.
5. THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL LOCATION ANDARRANGEMENT OF ALL MATERIALS AND EQUIPMENT. THE DRAWINGS SHALL BEFOLLOWED AS CLOSELY AS BUILDING CONSTRUCTION AND ALL OTHER WORK WILLPERMIT.
6. ALL DUCT DIMENSIONS SHOWN ARE INTERIOR DUCT DIMENSIONS.
7. INFORMATION GIVEN IN SCHEDULES INCLUDES BOTH DESCRIPTION OF PRODUCTAND MANUFACTURER'S MODEL #. IF CONFLICT IS PRESENT BETWEEN DESCRIPTIONAND MODEL #, EQUIPMENT DESCRIPTION SHALL TAKE PRECEDENT. IN CASE OFCONFLICT BETWEEN THE PLANS AND NOTES/SPECIFICATIONS OR CONFLICT BETWEENINFORMATION PRESENTED ON THE PLANS OR IN THE NOTES/SPECIFICATIONS, THENTHE MOST RESTRICTIVE SHALL TAKE PRECEDENT.
8. BEFORE BID MC IS RESPONSIBLE FOR CLARIFYING W/ G.C. ANY CONFUSION INREGARDS TO RESPONSIBILITY OF WORK TO BE PERFORMED OR MATERIALS TO BEPROVIDED. THE SUBMITTAL OF THE BID BY THE CONTRACTOR WILL BE HELD ASPROOF THAT THE CONTRACTOR UNDERSTANDS THOROUGHLY AND COMPLETELYTHE SCOPE OF THE WORK INVOLVED, AND HAS INCLUDED ON THE BID ALL THENECESSARY ITEMS TO CARRY OUT THIS SECTION OF WORK.
9. AS SOON AS POSSIBLE (AND NOT MORE THAN 30 DAYS) AFTER CONTRACT ISSIGNED, THE MC SHALL PROVIDE SUBMITTALS OF MECHANICAL EQUIPMENT HE/SHEINTENDS TO PURCHASE FOR REVIEW AND COMMENT BY THE ENGINEER. ENGINEER ISTO APPROVE SUBMITTALS BEFORE EQUIPMENT IS ORDERED.
10. ALL QUESTIONS MUST BE SUBMITTED IN RFI FORMAT TO THE ARCHITECT AND MUST BEADDRESSED BY THE APPROPRIATE DESIGNER OF RECORD PROIR TO BECOMING APROPOSED CHANGE ORDER.
11. UPON COMPLETION OF WORK M.C. IS TO PROVIDE OWNER W/ COMPLETE BOUNDSET OF ALL EQUIPMENT OPERATION & MAINTENANCE MANUALS. PACKAGE IS ALSOTO INCLUDE AND WARRANTY & GUARANTEE INFORMATION.
12. M.C. IS TO PROVIDE TRAINING TO OWNER OR OWNER'S REPRESENTATIVE INREGARDS TO OPERATION, FUNCTION, AND MAINTENANCE OF ALL MECHANICALEQUIPMENT, CONTROLS, ETC.
13. M.C. IS TO REVIEW COMPLETE DRAWING SET. M.C. IS RESPONSIBLE FOR WORKEXPLICITLY SHOWN AND WORK IMPLIED.
II. DIVISION OF WORK:
1. ALL ROOF WORK INCLUDING PENETRATIONS, OPENINGS, FLASHING, CURB INSTALLS,ETC ARE TO BE PERFORMED BY ROOFING CONTRACTOR. M.C. RESPONSIBLE FORPROVIDING ANY ROOF CURBS, EQUIPMENT RAILS, VENTS, ETC ANDCOMMUNICATING ALL REQ'S WITH G.C. & ROOFING CONTRACTOR.
2. ALL LOW VOLTAGE WIRING RELATED TO MECHANICAL EQUIPMENT AND SYSTEMS ISTHE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR (ANY LOW VOLTAGE FIREALARM WIRING TO BE BY E.C.). ALL HIGH VOLTAGE CONNECTIONS TOMECHANICAL EQUIPMENT, TO BE PROVIDED AND INSTALLED BY E.C. (SEEEQUIPMENT SCHEDULE FOR DISCONNECT RESPONSIBILITY).
3. G.C. TO BE RESPONSIBLE FOR PROVIDING AND INSTALLING ANY ACCESS DOORS(WALL, FLOOR, CEILING) RELATED TO MECHANICAL SYSTEM. M.C. RESPONSIBLE FORCOMMUNICATING TO G.C. SIZE AND LOCATION OF REQ'D ACCESS DOOR(S).
4. MECHANICAL CONTRACTOR IS TO EMPLOY THE SERVICES OF THE G.C. FOR CUTTINGAND PATCHING OF WALLS, FLOORS & CEILINGS RELATED TO THE INSTALLATION OFMECHANICAL EQUIPMENT & SYSTEMS.
5. G.C. RESPONSIBLE FOR PAINTING OF ANY EXPOSED DUCT, PIPING, GRILLES, ETC.M.C. RESPONSIBLE FOR CLEANING AND PREPARING ITEMS FOR PAINT, COORDINATEW/ G.C.
6. G.C. TO BE RESPONSIBLE FOR PROVIDING AND INSTALLING ANY ACCESSPLATFORMS, GUARD RAILS, LADDERS, CONCRETE PADS. M.C. TO COMMUNICATEREQ'S TO G.C.
7. G.C. TO BE RESPONSIBLE FOR PROVIDING AND INSTALLING ANY WALL LOUVERSBRICK VENTS OR SIMILAR. M.C. TO PROVIDE AND INSTALL ANY WALL CAPS.
8. ALL GAS PIPING IS BY MECHANICAL CONTRACTOR.
III. MATERIALS:
1. ALL MATERIALS SHALL BE NEW UNLESS OTHERWISE SHOWN OR SPECIFIED.
2. PROVIDE HANGERS & SUPPORTS APPROVED FOR USE BY 2012 NC MECHANICALCODE.
3. ALL MAIN DUCTWORK (SUPPLY, RETURN, EXHAUST, OUTSIDE AIR) SHALL BEGALVANIZED SHEET METAL CONSTRUCTED IN ACCORDANCE WITH SMACNASTANDARDS. RUNOUTS FROM MAIN/BRANCH DUCTS MAY BE FLEXIBLE DUCTCONFORMING TO THE REQUIREMENTS OF UL 181 FOR CLASS 1 FLEXIBLE AIR DUCTS.MAX. LENGTH OF FLEX PER RUNOUT TO BE 6'-0" UNLESS SHOWN OTHERWISE.
4. NO FLEXIBLE DUCT ALLOWED FOR NEGATIVE PRESSURE EXHAUST APPLICATIONS.
5. ALL SUPPLY AND RETURN DUCTWORK AND PLENUMS SHALL BE INSULATED.INSULATION OF DUCTWORK IN UNCONDITIONED SPACE SHALL BE MINIMUM R-5 PER2012 NCECC. INSULATION OF DUCTWORK OUTSIDE BUILDING THERMAL ENVELOPE(I.E. ROOF, ATTIC, CRAWLSPACE) SPACE SHALL BE MINIMUM R-8 PER 2012 NCECC.
6. CONCEALED SHEET METAL SUPPLY & RETURN DUCT MAY BE EXTERNALLY INSULATEDWITH MINERAL FIBER BOARD OR BLANKET OR MAY BE INTERNALLY INSULATED WITHACOUSTICAL DUCT LINER. EXPOSED SPIRAL DUCTWORK DOES NOT REQUIREINSULATION UNLESS OTHERWISE NOTED (WHEN INSTALLED IN CONDITIONED SPACE).
7. ALL MAIN DUCTWORK (INCLUDING EXHAUST) TO BE SEALED ACCORDING TO 2012NCECC AND AT A MINIMUM INCLUDE SEALING OF ALL DUCT SEAMS W/NON-HARDENING MASTIC. SEALING BY TAPE ALONE NOT ALLOWED.
8. CONDENSATE DRAIN PIPING AND FITTINGS SHALL BE SCHEDULE 40 PVC.
9. ALL DAMPERS TO INCLUDE SET SCREW OR SIMILAR FEATURE FOR LOCKING INPOSITION.
10. ALL REFRIGERANT LINE MATERIAL AS PER MFG'S REQUIREMENTS. SIZE PER MFGINSTRUCTIONS. SUCTION LINE TO BE INSULATED W/ MIN. 1-1/2" ARMAFLEX W/ TAPEDOR SEALED SEAMS.
11. ALL FIRE, SMOKE AND RADIATION DAMPERS TO BE U.L. LISTED AND APPROVED FORCORRECT PRESSURE CLASS, APPLICATION (STATIC, DYNAMIC), ORIENTATION(HORIZONTAL/VERTICAL), AND INSTALLATION (WALL, FLOOR CEILING U.L.ASSEMBLY). TO INCLUDE 165° FUSIBLE LINK UNLESS OTHERWISE NOTED.
12. ALL FIRE SEALANTS TO BE U.L. LISTED AND APPROVED FOR USE W/ APPROPRIATE U.L.PENETRATION DETAIL.
13. ALL PROGRAMMABLE THERMOSTATS TO INCLUDE BATTERY BACK-UP AND HAVECAPABILITY TO SETBACK TO 55°F (HEATING) & 85°F (COOLING).AUTO-CHANGEOVER THERMOSTATS TO HAVE A MIN. 5°F DEADBAND.
14. GAS PIPING TO BE SCHEDULE 40 BLACK STEEL PIPE W/ THREADED FITTINGS.APPROVED FLEXIBLE GAS PIPING MAY BE USED AT CONNECTION TO EQUIPMENT.
IV. COORDINATION:
1. THE MECHANICAL CONTRACTOR SHALL COORDINATE CLOSELY WITH ALL OTHERTRADES TO AVOID CONFLICT AND ENSURE OTHER TRADES PROVIDE MEASURES TOACCOMMODATE MECHANICAL WORK (I.E. ACCESS DOORS, SLAB/WALL/ROOFOPENINGS, ELECTRICAL CONNECTIONS, ETC).
2. MECHANICAL CONTRACTOR SHALL VERIFY LOCATION OF ALL PENETRATIONS FORRELIEF HOODS, OUTSIDE AIR HOODS, LOUVERS, AND WALL CAPS WITH ARCHITECT &OWNER PRIOR TO INSTALLATION.
3. M.C. TO COORDINATE LOCATION OF ALL ROOF PENETRATIONS W/ ROOFINGCONTRACTOR. P.C. & M.C. TO COORDINATE TO ENSURE NO PLUMBING VENTS ORANY OTHER SOURCES OF BUILDING EXHAUST ARE LOCATED WITHIN 10' OF ANYOUTSIDE AIR INTAKES.
4. LOCATE CEILING DIFFUSERS IN ACCORDANCE WITH ARCHITECTURAL REFLECTEDCEILING PLANS (IF PROVIDED).
V. EXECUTION:
1. M.C. TO FOLLOW MANUFACTURER'S INSTRUCTIONS WHEN INSTALLING MECHANICALEQUIPMENT. ENSURE REQUIRED MAINTENANCE ACCESS AND CLEARANCES AREMAINTAINED. IF CONFLICT EXISTS BETWEEN THESE PLANS AND MFG INSTRUCTIONSCONTACT ENGINEER.
2. ALL PENETRATIONS THROUGH EXTERIOR WALLS & ROOF SHALL BE FLASHED &COUNTER-FLASHED IN A WATERPROOF MANNER.
3. SEAL ALL PENETRATIONS OF RATED WALLS, CEILING, FLOORS IN ACCORDANCE W/APPROPRIATE U.L. PENETRATION DETAIL.
4. INSTALL ALL CONTROL DEVICES, INCLUDING THERMOSTATS AND SWITCHES, 4'-0"ABOVE FINISHED FLOOR.
5. INDEPENDENT CERTIFIED TEST AND BALANCE CONTRACTOR SHALL BALANCE SYSTEMTO AIR QUANTITIES INDICATED ON PLANS AND IN ACCORDANCE W/ 2012 NCECCSEC. 503.2.9. M.C. TO PROVIDE OWNER'S REPRESENTATIVE & ENGINEER WITHCOMPLETE BALANCE REPORT. MC RESPONSIBLE FOR PROVIDING ANY DAMPERS,VALVES, PORTS, ETC. NECESSARY FOR A COMPLETE SYSTEM BALANCE.
6. ALL REFRIGERANT PIPING SHALL BE INSTALLED PER MFG'S INSTRUCTIONS IN REGARDSTO SUPPORTS, BENDS, FITTINGS, OIL TRAPS, ETC.
7. PENETRATIONS OF NON-RATED WALLS, PARTITIONS AND FLOOR OF COMBUSTIBLECONSTRUCTION SHALL BE FIRESTOPPED WITH MATERIALS EQUIVALENT TO TWOINCHES OF WOOD. FIRESTOPPING SHALL COMPLY WITH ASTM E-814.
8. SUPPORT ALL DUCTWORK AND PIPING IN ACCORDANCE W/ 2012 NC MECHANICALCODE. ANY SUSPENDED MATERIALS SHALL BE DIRECTLY SUPPORTED BY THE BUILDINGSTRUCTURE.
9. PENETRATIONS OF ALL EXTERIOR WALLS, FLOORS AND CEILINGS SHALL BE SEALED INAN AIR TIGHT MANNER AND IN ACCORDANCE W/ 2012 NCECC APPENDIX 2DETAILS. ALL PENETRATIONS OF WALLS, FLOORS & CEILINGS IN RETURN OR EXHAUSTPLENUMS SHALL BE SEALED IN AN AIR TIGHT MANNER.
10. DUCT ACCESS DOORS TO BE PROVIDED AT ALL FIRE, RADIATION & SMOKEDAMPERS, SMOKE DETECTORS, CLEANOUTS AND ANY OTHER CODE REQUIREDLOCATIONS.
11. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALLMECHANICAL EQUIPMENT FROM FOREIGN MATERIAL DURING CONSTRUCTION(PAINT, SPACKLE, ETC.). UPON COMPLETION OF WORK THE MECHANICALCONTRACTOR SHALL CLEAN, WASH, ETC ALL ITEMS AND EQUIPMENT WITHIN HISSCOPE OF WORK AND LEAVE ALL ITEMS BRIGHT AND CLEAN.
UNITARY
RELATIVE HUMIDITY
BOILER
CHILLER
LIST EQUIPMENT EFFICIENCIES
DESIGNER'S STATEMENT:
SIGNED:
NAME:
TITLE:
REQUIREMENTS OF THE N.C.S. ENERGY CODE.
BUILDING HEATING LOAD (MBH)
BUILDING COOLING LOAD (MBH)
MECHANICAL SPACING CONDITIONING SYSTEM
TO THE BEST OF MY KNOWLEDGE AND BELIEF, THE DESIGN OF THIS BUILDINGCOMPLIES WITH THE MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
SUMMER DRY BULB
COOLING EFFICIENCYHEATING EFFICIENCY
TOTAL BOILER OUTPUT
HEAT OUTPUT OF UNIT
DESCRIPTION OF UNIT
TOTAL CHILLER OUTPUT
COOLING OUTPUT OF UNIT
ZACK L. TOMLIN, PE
MECHANICAL ENGINEER
50%
43.2 MBH
53.8 MBH
NA
NA
SEE SCHEDULES
SEE SCHEDULES
SEE SCHEDULESSEE SCHEDULESSEE SCHEDULES
SEE SCHEDULES
75
METHOD OF COMPLIANCE
EXTERIOR DESIGN CONDITIONS
INTERIOR DESIGN CONDITIONS
SUMMER DRY BULB
WINTER DRY BULB
WINTER DRY BULB
THERMAL ZONE
PRESCRIPTIVE
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENTENERGY REQUIREMENTS:
ENERGY COST BUDGET
9314
4A
70
CONTROL OPTIONS:
4. INTEGRAL DISCONNECT SWITCH1.
3.2.
COLOR BY ARCHITECTBACKDRAFT DAMPERW/ SCREEN
NOTES:
A. CONTROL W/ ROOM LIGHTS
NOTESCONTROL SCHEME& MODEL NO. DRIVEMANUFACTURER
& VOLTAGERPMS.P. ARRANGEMENTMIN. MOTOR HPTYPE &
FAN SCHEDULESERVEDNO. SERVICE
UNIT AREACFM
120V/1Ø SPA-190113 WATTS
EXHAUST BATHROOM MFG.75 0.35" DIRECTGREENHECK
120V/1ØAEF-1
CEILING,CENTRIFUGAL
1,2,3,4
1/6 HPEXHAUST MANICURE MFG400 0.4" DOWNBLAST DIRECT
GREENHECK120V/1Ø G-085
B 1,2,3,4,5,6EF-2 CENTRIFUGAL
5. SPEED CONTROLLER6. W/ INSULATED MFG. ROOF CURB
B. CONTROL W/ SPEED CONTROLLER
NOTESMANUFACTURER
& MODEL NO.FINISHSERVICEMATERIALDAMPERPATTERNTYPEFRAME
SIZENECK
CFMSYMBOLMODULE
SIZE
DIFFUSER SCHEDULE
24x24AS NOTED AS NOTED LAY-IN PLAQUE NO STEEL SUPPLY NOTE 2 TITUS OMNIA 1,2,3
12x24AS NOTED LAY-IN PERF. STEEL SUPPLY NOTE 2 TITUS PASB NOAS NOTED
3.
A758x4
2. FINISH TO MATCH / BE ABLE MATCH CEILING OR WALL OR DOOR.
1. DIFFUSER DESIGNATIONS ON PLANS AS FOLLOWS:
AS NOTED ABOVEDIFFUSER TYPE
DIFFUSER ORNECK SIZE.
AIR QUANTITY
FACTORY INSULATION BACKING ON GRILLES EXPOSED TO NON-CONDITIONED AREAS.ALTERNATELY, FIELD SUPPLY AND INSTALL.
GENERAL - MC RESPONSIBLE FOR VERIFYING QTY, COLOR & FRAME TYPEOF DIFFUSERS/GRILLES BEFORE ORDERING. PROVIDE SQR TO RNDTRANSTIONS & PLENUMS AS NECESSARY.
1,2,3
ELBOW WITH TURNING VANES
FLEX/RIGID ROUND DUCT
RECTANGULAR DUCT
ROUND METAL DUCT
MECHANICAL LEGEND
T-STAT
SUPPLY DIFFUSER/GRILLE OR RISER
RETURN REGISTER/GRILLE OR RISER
SIDEWALL DIFFUSER/GRILLE
3/4" DOOR UNDER CUT
6Ø
18x14
6Ø
T
SUPPLY TAP WITH VOLUME DAMPER
VOLUME DAMPER
SUPPLY TAP
EXHAUST REGISTER/GRILLE OR RISER
CEILING EXHAUST FAN
REMOTE AVERAGING TEMP SENSORS
3.
4.
COMPRESSOR CYCLE DELAY AND WINTER START TIME DELAY (IF AVAILABLE).
NOTES:
COOLING CAPACITIES ARE RATED IN ACCORDANCE WITH AT LEAST ONE OF THE FOLLOWING ARISTANDARDS;; 210-94, 270-95, OR 360-93 AT 95°F AMBIENT OUTDOOR AIR TEMP., 80°F DRY BULB, 67° WET BULBENTRANCE AIR TEMP., AND AIR QUANTITY LISTED BY MFG.
PROVIDE FACTORY ROOF CURB AND AIR SIDE DIFFERENTIAL ENTHALPY ECONOMIZER SECTION WITH BAROMETRICRELIEF DAMPER FOR EACH UNIT.
5.
PROVIDE 3 SETS OF NEW FILTERS FOR EACH UNIT. PROVIDE ONE AT INSTALLATION, ONEPRIOR TO AIR BALANCE AND ONE AT TURNOVER TO OWNER.
PROVIDE MANUFACTURER'S 7 DAY PROGRAMMABLE THERMOSTAT W/ MANUAL OVERRIDE & REMOTEAVERAGING SENSOR. (T-STAT & SENSOR TO MEASURE TEMPERATURE IN (2) LOCATIONS)
2.
1.
EF-3
E
(LBS)WT.
TON.NOM.REHEAT
(MBH)STAGES# OF
(MBH)OUTPUTENT. AIR
DB/WB (°F)DB/WB (°F)AMBIENTFAN
RPMESP
(" OF WG)AREA
SERVED NOTESEER(SEER)MODEL
MANUF.(A)
MOCP
GENERAL DATA
(A)MCAVOLTAGE
(V/PH)# OF
STAGES
HEATING SECTION
INPUT(MBH)
SENS.
COOLING SECTION
(MBH)(CFM)OA, MAX
(MBH)TOTAL
PACKAGED DX COOLING/GAS-ELEC HEATING ROOF TOP UNIT SCHEDULEELECTRICAL DATAEVAPORATOR FAN DATA
CFMFANUNIT
TAG (HP)MOTOROA, MIN
(CFM) (KW)ELEC HEAT
8415.0N/A1 48.093/76MFG.0.75 YHC060RTU-1 48.1 160.0 30.0208V/3Ø 45 TRANE 12.9 1,2,3,4,5,6,71.01990 62.3-SALON 500 N/A80/67
24x24AS NOTED N/A LAY-IN PERF. STEEL NOTE 2 TITUS 8RFNOFILTER
1,2,3RETURN
AS NOTEDAS NOTED N/A SURFACE LOUVERED STEEL EXHAUST NOTE 2 TITUS 350RL 1,2D NO
EXHAUST PEDICURE MFG600 0.65" DIRECT120V/1Ø
B 1,2,3,4,5,6CENTRIFUGAL1/6 HP GREENHECKDOWNBLAST
G-095
1,2,3,4C AS NOTEDAS NOTED SURFACE SNG. DEFL. STEEL SUPPLY NOTE 2 TITUS 301FSNON/A
6.
PROVIDE WITH FACTORY MOUNTED DISCONNECT AND FACTORY POWERED GFI RECEPTICAL.7.
PROVIDE WITH THROUGH THE BASE ELECTRICAL CONNECTION.
4. SET BLADE ANGLE TO 0°.
MDB-1402
MAR. 18, 2014
REVISIONS
DATE
DRAWN BY
SHEET TITLE
PROJECT NO.
SHEET
MARLIN DESIGN BUILD
OF
1405 HILLSBOROUGH STRALEIGH, NC 27605
mapleENGINEERING, pllc
plumbing mechanical electrical
LIC.#: P-0990P:919-341-4247 F:919-890-3797
PO Box 1852Cary, NC 27512Phone: (919) 291-6736
3/18/14
FIRE RATING LEGEND1-HR WALL2-HR WALL
M1.12 3
BTM
MECHANICALPLAN
& DETAILS
1 SCALE: 1/4" = 1'-0"
MECHANICAL PLAN
RestrmPassage
Office
Waxing
Waxing
Pedicure Area
Manicure Area
ReceptionEXHAUST DUCT
FAN
HANGER
EXHAUST GRILLE
NOTES:1. IF FAN IS EQUIPPED W/ INTERNAL BDD ENSURE BDD IS NOT
TAPED SHUT.2. ENSURE NO PORTION OF TAPE, SEALING, ETC EXTENDS PAST
EDGE OF EXHAUST GRILLE.3. INSTALLATION IN HARD-CEILING SIMILAR. FAN TO BE
FASTENED TO RAFTER/JOIST. SEE MFG INSTRUCTIONS.
CEILING
SEAL GAP BETWEENFAN HOUSING & CEILING
EXHAUST FAN (CEILING) DETAIL4 NO SCALE 2 NO SCALE
EF-1
3 NO SCALE
GAS/ELEC ROOFTOP UNIT
TAGGED NOTES - THIS SHEET1
REDUCER ORSQUARE TO ROUNDTRANSITION(IF NECESSARY)TYP.
FINISHED
FLEX DUCTDIAMETER "D"
CEILING SURFACE
CIRCULAR CLAMP
DIFFUSER/GRILLE
NOTES:1. PROVIDE INSULATED REGISTER BOOT/PLENUM BOX IF NECESSARY.2. RETURN APPLICATION IS SIMILAR. ALL ELBOWS IN RETURN APPLICATION
TO BE INSULATED SHEET METAL (NO FLEX ELBOWS).
(COORD. FRAME TYPE)
SUPPLY AIR DUCT.
FLARED SHOULDER &
INTEGRAL SCOOP.SPIN IN COLLAR W/
(WHERE ACCESIBLE)
VOLUME DAMPER WITH3/8" LOCKING QUADRANTAND END BEARING.
ROUND SHEETMETAL DUCT.
NOTE:FLEX DUCT TURN INTO DIFFUSER TO BE REPLACEDBY INSULATED SHEET METAL ELBOW FOR (3)FARTHEST CEILING DIFFUSERS FROM AIRHANDLER. THERMAFLEX "FLEX FLOW ELBOW"SUPPORT MAY BE USED IN LIEU OF SHEET METALELBOW.
5 NO SCALE
DIFFUSER DETAIL
2 PROVIDE AND INSTALL ROOFTOP UNIT AND CURBMAINTAINING ALL MANUFACTURER'S CLEARANCES.MAINTAIN 10' CLEARANCE FROM ALL BUILDING EXHAUST.SEE DETAIL.
3 PROVIDE 4Ø DRYER VENT UP TO ROOF JACK W/ BDD.INSTALL ABOVE EMERGENCY DRAIN LEVELS. MAINTAIN 10'CLEARANCE FROM ALL BUILDING AIR INTAKES.
FRESH AIR INLET
TO SPLASH BLOCK1" CONDENSATE
ECONOMIZER HOOD WITHFILTER ACCESS PANEL.
ROOF TOP MOUNTEDAIR HANDLING UNIT.
HIGH DENSITYGASKET 2" WIDE.
PREFABRICATED
FLASHING
ROOF CURB.
2" RIGID INSUL.
HARDENING MASTIC.
SEAL ALL DUCTWORKOPENINGS WITH NON-
PROVIDE 3 ALT. LAYERS OF 5/8" G.W.B. & 1" RIGID INSULATION. SEAL AND STAGGER ALL SEAMS.
FLEX CONN.
PROVIDE ACOUSTICDUCT LINER FIRST 10' FROMDISCHARGE AND INTAKE.
4
5Ø25B
8Ø175A
7Ø115B
6Ø75B
6Ø100B
6Ø75B
(RTU-1)
5
SUPPLY GRILLE IN BULKHEAD. CENTER VERTICALLY INBULKHEAD.
6
PROVIDE 6Ø EXHAUST TAP W/ DAMPER OVER TO 9x3EXHAUST DUCT IN STUD CAVITY. DUCT NOT TO BE INRATED WALL. PROVIDE 6x6 TYPE "D" GRILLE, BOTTOMOF GRILLE TO BE 12" AFF. BALANCE TO 75 CFMEXHAUST. COORDINATE INSTALLATION W/ G.C.BEFORE BEGINNING WORK.
4Ø EXHAUST DUCT UP TO MFG ROOF JACK WITH BDDAND INSECT SCREEN. INSTALL ROOF JACK ABOVEEMERGENCY ROOF DRAIN HEIGHT. MAINTAIN 10'CLEARANCE FROM ALL BUILDING AIR INTAKES.
8Ø
8Ø
7
6x6 EXHAUST DUCT DOWN TO NAIL STATION TABLE.G.C. TO PROVIDE CHASE.
RTU-1
2
1
8
MAIN SUPPORT GIRDER. PROVIDE AND INSTALLROOFTOP UNIT AND CURB IN THIS LOCATION FORMAXIMUM SUPPORT. ROUTE SUPPLY/RETURN DUCTDOWN INBETWEEN BAR JOISTS.
20x1
4
FLASHING
EXHAUST FAN
W/ 1" INSUL. & NAILORMFG. ROOF CURB
EXHAUST DUCT
EXHAUST DUCT FLANGEFASTENED TO NAILOR
BACK DRAFT DAMPER
NO SCALE
EXH. FAN DETAIL (ROOF)
EF-2
EF-3
10Ø10Ø
710Ø8Ø
6Ø
6Ø
9
12X10 DOWN FROM EF ON ROOF.
8X8 DOWN FROM EF ON ROOF.
8
14Ø745 E
6Ø
7Ø
8Ø
5Ø
14Ø
14Ø
(RTU-1)
14Ø745E
GGAS PIPING ON ROOF
GAS SHUT-OFF VALVEBY MECHANICAL CONTR.
6x8
8Ø175A
8Ø175A
8Ø175A
12x1
2
10Ø
10 DUCT TO RUN BETWEEN NAIL STATION TABLE FRAMING.COORDINATE W/ G.C.. PROVIDE EXHAUST GRILLE ASSHOWN. INSTALL GRILLE AS HIGH AS POSSIBLE.
10Ø
6Ø
8Ø
6Ø
12x10300C12x10
300C
12x10300C
DRYER VENT LENGTH
BREAK ROOM:LENGTH = 15' (V) + 0' (H) = 15' < 35'
1. INSTALLED DRYER MUST BE RATED BY MFG FOR VENT LENGTH OF15' OR GREATER.
2012 NCMC SEC 504.6
5
5
3
10x1
0 5
5
5
8Ø
5
5
5 6Ø
4 4
4
6x10
12x6200D
12x6200D
6x8
6x8
6x86x10
10
6
6
10
9
MDB-1402
MAR. 18, 2014
REVISIONS
DATE
DRAWN BY
SHEET TITLE
PROJECT NO.
SHEET
MARLIN DESIGN BUILD
OF
1405 HILLSBOROUGH STRALEIGH, NC 27605
mapleENGINEERING, pllc
plumbing mechanical electrical
LIC.#: P-0990P:919-341-4247 F:919-890-3797
PO Box 1852Cary, NC 27512Phone: (919) 291-6736
3/18/14
FIRE RATING LEGEND1-HR WALL2-HR WALL
M1.23 3
RSA
MECHANICAL GAS PLAN
1 SCALE: 1/4" = 1'-0"
MECHANICAL PLAN- GAS
RTU-1
TABLE 402.4(2)
1"
3/4"
1/2"
PIPE SIZE (IN.)
157 MBH
MAX CAPACITY OF PIPE IN MBH
40 MBH
83 MBH
EQUIV. LENGTH = 150 FT
NATURAL GAS CALCULATIONS
?? MBH
?? MBH
?? MBH
?? FT ?? FT
?? MBH
?? MBH
?? MBH
BASED UPON CHAPTER 4 OF THE 2012 NORTH CAROLINA FUEL GAS CODE,LESS THAN 2.0 PSI INLET PRESSURE, 0.5 IN. W.C. PRESSURE DROP.
2 NO SCALE
GAS RISER
BY M.C.BY P.C.
SHUT-OFF VALVE
ROOF
GAS PIPE SUPPORT
ROOF TOP UNIT
NOTE:
REQUIRED BY UNIT MANUFACTURER
12" M
AX.
PIPE CLAMPS: "UNISTRUT"#P2600 WITH CUSHION
CLAMP. SIZE TO MATCHPIPING SIZE
BETWEEN PIPING & TO PROVIDE GAS PRESSURE AND CAPACITY AS PROVIDE REGULATOR AT EACH ROOF TOP UNIT
PITCH BACK TO SOURCE
4 NO SCALE
GAS PIPING DETAIL
GENERAL NOTES - THIS SHEET1. ITEMS SHOWN IN FAINT & HATCHED ARE TO BE DEMO'D OR
RELOCATED. ITEMS SHOWN IN FAINT ARE EXISTING TOREMAIN. NEW OR RELOCATED ITEMS ARE SHOWN IN BOLD.
2. VERIFY EXISTING CONDITIONS BEFORE BEGINNING WORK.3. M.C. IS TO PROVIDE REGULATOR, FLEX CONNECTION &
SHUT-OFF VALVE AT EACH EQUIPMENT CONNECTION.COORDINATE AND VERIFY EXACT SIZE AND LOCATION OFEQUIPMENT GAS CONNECTION(S) BEFORE BEGINNINGWORK.
4. PROVIDE LABELING ON GAS PIPING AS REQUIRED BY 2012NCFGC SEC. 401.5 & 401.7.
GAS LINE FROM BELOWGRADE UP TO HEADER.
~28F
T
GAS METERLOCATION
3 NO SCALE
BUILDING PLAN
AREA OFWORK
NORTH
(60 MBH)
MDB-1402
MAR. 18, 2014
REVISIONS
DATE
DRAWN BY
SHEET TITLE
PROJECT NO.
SHEET
MARLIN DESIGN BUILD
OF
1405 HILLSBOROUGH STRALEIGH, NC 27605
mapleENGINEERING, pllc
plumbing mechanical electrical
LIC.#: P-0990P:919-341-4247 F:919-890-3797
PO Box 1852Cary, NC 27512Phone: (919) 291-6736
3/18/14
E0.11 3
MJL
ELECTRICALSCHEDULESDETAILS &
NOTES
7. METAL CONDUIT COUPLINGS TO BE COMPRESSION TYPE OR THREADED WHEN ACCESSIBLE TO BUILDING OCCUPANTS. METALCOUNDUIT COUPLINGS MAY BE SET-SCREW TYPE WHEN CONCEALED IN BUILDING STRUCTURE OR LOCATED MORE THAN 10' AFF. PLASTIC CONDUIT COUPLINGS TO BE SOCKET GLUED TYPE.
8. FUSES 0 - 600 AMPS SHALL BE UL CLASS "RK-1" LOW PEAK DUALELEMENT TIME DELAY WITH 200,000 AMPERE INTERRUPTINGRATING AS MANUFACTURED BY BUSSMANN, UNLESS NOTEDOTHERWISE.
9. ALL TERMINALS/LUGS SHALL BE 60/75° RATED. ALL TERMINALS,SPLICING CONNECTORS, LUGS, ETC SHALL BE IDENTIFIED FOR USEWITH THE MATERIAL (CU/AL) OF THE CONDUCTOR AND SHALL BEPROPERLY INSTALLED.
10. RECEPTACLES IN COMMERCIAL AREAS SHALL BE 20 AMPCOMMERCIAL SPECIFICATION GRADE EQUAL TO HUBBELL SERIES.GROUND FAULT RECEPTACLES SHALL BE EQUAL TO COOPER VGFSERIES.
11. LIGHTING SWITCHES SHALL BE 20 AMP COMMERCIALSPECIFICATION GRADE EQUAL TO HUBBELL SERIES.
12. ALL EXTERIOR FIXTURES AND DEVICES SHALL BE RATED FOROPERATION AT 0° F AND SHALL BE DAMP OR WET LABELED ASREQUIRED.
13. ANY RECESSED LIGHT FIXTURES INSTALLED IN INSULATED CEILINGSOR WALLS TO BE "IC RATED" AND MEET REQUIREMENTS OF ASTME283 AND 2012 NCECC SEC. 502.4.8.
IV. COORDINATION:
1. THE ELECTRICAL CONTRACTOR SHALL COORDINATE CLOSELYWITH ALL OTHER TRADES TO AVOID CONFLICT AND ENSUREOTHER TRADES PROVIDE MEASURES TO ACCOMMODATEELECTRICAL WORK (I.E. ACCESS DOORS, SLAB/WALL/ROOFOPENINGS, ETC).
2. E.C. TO COORDINATE ELEVATION OF WALL MOUNTED LIGHTS(INTERIOR & EXTERIOR) W/ ARCHITECT/ARCH PLANS.
3. E.C. TO COORDINATE W/ P.C. & M.C. REGARDING POWER ANDFIRE ALARM CONNECTIONS TO MECHANICAL AND PLUMBINGEQUIPMENT.
4. E.C. TO VERIFY ALL REQUIREMENTS AND COORDINATE EXACTLOCATION OF INCOMING ELECTRICAL SERVICE WITH LOCALPOWER COMPANY PRIOR TO PROJECT START-UP. NOTIFYENGINEER OF ANY CHANGES AS MAY BE REQUIRED.
V. EXECUTION:
1. E.C. TO FOLLOW MANUFACTURER'S INSTRUCTIONS WHENINSTALLING ELECTRICAL EQUIPMENT. ENSURE REQUIREDMAINTENANCE ACCESS AND CLEARANCES ARE MAINTAINED. IFCONFLICT EXISTS BETWEEN THESE PLANS AND MFG INSTRUCTIONSCONTACT ENGINEER.
2. A COMPLETE GROUNDING SYSTEM SHALL BE PROVIDED ANDINSTALLED IN ACCORDANCE WITH ARTICLE 250 OF THE NEC,AND AS SHOWN ON THE DRAWINGS.
3. PROVIDE A PULLWIRE IN ALL EMPTY CONDUITS.
4. PROVIDE A TYPED DIRECTORY IN ALL PANELBOARDS CLEARLYDESCRIBING THE LOCATION OF AND TYPE OF LOAD BEINGSERVED FOR ALL CIRCUITS. PROVIDE ENGRAVED PHENOLICNAMEPLATES FOR ALL PANELBOARDS AND DISCONNECTSWITCHES, WHITE LETTERS ON BLACK BACKGROUND.
5. ALL PENETRATIONS THROUGH EXTERIOR WALLS & ROOF SHALL BEFLASHED & COUNTER-FLASHED IN A WATERPROOF MANNER.
6. SEAL ALL PENETRATIONS OF SMOKE PARTITIONS OR FIRE RATEDWALLS, CEILING, FLOORS IN ACCORDANCE W/ APPROPRIATEU.L. PENETRATION DETAIL AND NC BUILDING CODE.
7. PENETRATIONS OF NON-RATED WALLS, PARTITIONS AND FLOOROF COMBUSTIBLE CONSTRUCTION SHALL BE FIRESTOPPED WITHMATERIALS EQUIVALENT TO TWO INCHES OF WOOD.FIRESTOPPING SHALL COMPLY WITH ASTM E-814.
8. ANY NOTCHING, DRILLING, BORING OR OTHER ALTERATION TOBUILDING STRUCTURE SHALL BE PERFORMED IN A CODEAPPROVED METHOD AND NOT THREATEN THE INTEGRITY OF THEBUILDING STRUCTURE.
9. SUPPORT ALL CONDUIT AND EQUIPMENT IN ACCORDANCE W/NEC. ANY SUSPENDED MATERIALS SHALL BE DIRECTLY SUPPORTEDBY THE BUILDING STRUCTURE.
10. PENETRATIONS OF ALL EXTERIOR WALLS, FLOORS AND CEILINGSSHALL BE SEALED IN AN AIR TIGHT MANNER AND INACCORDANCE W/ 2012 NCECC APPENDIX 2 DETAILS.
11. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FORPROTECTING ALL ELECTRICAL EQUIPMENT FROM FOREIGNMATERIAL DURING CONSTRUCTION (PAINT, SPACKLE, ETC.).UPON COMPLETION OF WORK THE ELECTRICAL CONTRACTORSHALL CLEAN, WASH, ETC ALL ITEMS AND EQUIPMENT WITHIN HISSCOPE OF WORK AND LEAVE ALL ITEMS BRIGHT AND CLEAN.
12. IN REQUIRED FIRE RATED WALLS AND PARTITIONS, OPENINGS FORINSTALLATION OF BOXES THAT ARE GREATER THAN 16 SQUAREINCHES SHALL BE PROTECTED AS REQUIRED BY U.L.
13. UNLESS OTHERWISE INDICATED THE ELECTRICAL CONTRACTOR ATHIS/HER DISCRETION MAY COMBINE MULTIPLE CIRCUITS INTO ASINGLE CONDUIT AND DE-RATE WIRE. COMBINING ANDDE-RATING IS TO BE DONE IN STRICT ACCORDANCE W/ NEC.
14. DEVICES INCLUDING GFCI PROTECTION MUST HAVE THEIRTESTING MEANS READILY ACCESSIBLE. PROVIDE REMOTE TESTINGMEANS OR GFCI BREAKER FOR GFCI RECEPTACLES AND SIMILARDEVICES WHICH ARE NOT READILY ACCESSIBLE (I.E. BEHINDEQUIPMENT, AT CEILING, ETC). (NEC 210.8).
15. ALL EXIT & EMERGENCY LIGHTS ARE TO BE CIRCUITED TOUN-SWITCHED LEG OF LOCAL NORMALLY ON LIGHTING CIRCUIT.
16. RECEPTACLE, LIGHT SWITCHES AND OTHER CONTROL DEVICESARE TO BE INSTALLED IN ACCORDANCE W/ ANSI A117.1 ANDADA REQ'S CONCERNING HEIGHT AND ACCESSIBILITY. FHA REQ'STO BE FOLLOWED FOR MULTI-FAMILY AND RESIDENTIALPROJECTS.
17. E.C. IS TO CONFIRM EXACT ELECTRICAL NAMEPLATE DATA OFALL PLUMBING, MECHANICAL AND ELECTRICAL EQUIPMENTINCLUDING, BUT NOT LIMITED TO, MCA, MOCP, VOLTAGE &PHASE BEFORE BEGINNING WORK.
GENERAL ELECTRICAL NOTESI. GENERAL REQUIREMENTS:
1. ELECTRICAL CONTRACTOR IS TO FURNISH AND PAY FOR ALL LABOR,MATERIAL, EQUIPMENT, PERMITS & FEES REQUIRED FOR THECOMPLETE INSTALLATION OF ALL SYSTEMS IN THIS SECTION OFWORK.
2. ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH NEC ANDALL OTHER APPLICABLE CODES. EC IS TO COORDINATE W/ G.C. INREGARDS TO PROJECT TIMELINE, WORK HOURS, AS WELL AS ANYBONDING OR INSURANCE REQUIREMENTS.
3. ALL ELECTRICAL & LIGHTING EQUIPMENT SHALL BE PROVIDEDCOMPLETE WITH ALL ACCESSORIES, HANGERS, SUPPORTS,CONTROLS, ETC FOR A FULLY FUNCTIONING SYSTEM REGARDLESS OFPRESENCE ON PLANS.
4. ALL EQUIPMENT, MATERIALS AND INSTALLATION SHALL BEGUARANTEED TO BE FREE OF DEFECTS FOR A PERIOD OF ONE (1)YEAR AFTER FINAL ACCEPTANCE OF WORK OR IN ACCORDANCEWITH THE MANUFACTURER'S STANDARD GUARANTEE, IF LONGER.EXISTING EQUIPMENT IS EXCLUDED FROM WARRANTY REQUIREMENT.
5. THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERALLOCATION AND ARRANGEMENT OF ALL MATERIALS ANDEQUIPMENT. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY ASBUILDING CONSTRUCTION AND ALL OTHER WORK WILL PERMIT.
6. DO NO SCALE DRAWINGS FOR MEASUREMENT.
7. INFORMATION GIVEN IN SCHEDULES INCLUDES BOTH DESCRIPTIONOF PRODUCT AND MANUFACTURER'S MODEL #. IF CONFLICT ISPRESENT BETWEEN DESCRIPTION AND MODEL #, EQUIPMENTDESCRIPTION SHALL TAKE PRECEDENT. IN CASE OF CONFLICTBETWEEN THE PLANS AND NOTES/SPECIFICATIONS OR CONFLICTBETWEEN INFORMATION PRESENTED ON THE PLANS OR IN THENOTES/SPECIFICATIONS, THEN THE MOST RESTRICTIVE SHALL TAKEPRECEDENT.
8. BEFORE BID EC IS RESPONSIBLE FOR CLARIFYING W/ G.C. ANYCONFUSION IN REGARDS TO RESPONSIBILITY OF WORK TO BEPERFORMED OR MATERIALS TO BE PROVIDED. THE SUBMITTAL OF THEBID BY THE CONTRACTOR WILL BE HELD AS PROOF THAT THECONTRACTOR UNDERSTANDS THOROUGHLY AND COMPLETELY THESCOPE OF THE WORK INVOLVED, AND HAS INCLUDED ON THE BIDALL THE NECESSARY ITEMS TO CARRY OUT THIS SECTION OF WORK.
9. ALL EXISTING EQUIPMENT AND SYSTEMS ARE ASSUMED BY ENGINEERTO BE IN GOOD WORKING ORDER. BEFORE BEGINNING WORK E.C.IS TO ENSURE ANY EQUIPMENT & SYSTEMS TO REMAIN ARE PROPERLYFUNCTIONING. NOTIFY G.C. IMMEDIATELY IF PROBLEMS AREDISCOVERED.
10. ALL QUESTIONS MUST BE SUBMITTED IN RFI FORMAT TO THEARCHITECT AND MUST BE ADDRESSED BY THE APPROPRIATEDESIGNER OF RECORD PRIOR TO BECOMING A PROPOSED CHANGEORDER.
11. E.C. IS TO REVIEW COMPLETE DRAWING SET. E.C. IS RESPONSIBLE FORWORK EXPLICITLY SHOWN AND WORK IMPLIED. UNLESS OTHERWISENOTED FINAL ELECTRICAL CONNECTION TO ALL EQUIPMENT,FURNITURE (I.E. CUBICLES, WORKSTATIONS, ETC) IS THE RESPONSIBILITYOF THE E.C..
II. DIVISION OF WORK:
1. ALL ROOF WORK INCLUDING PENETRATIONS, OPENINGS, FLASHING,CURB INSTALLS, ETC ARE TO BE PERFORMED BY ROOFINGCONTRACTOR. E.C. RESPONSIBLE FOR PROVIDING ANY ROOFCURBS, EQUIPMENT RAILS, VENTS, ETC AND COMMUNICATING ALLREQ'S WITH G.C. & ROOFING CONTRACTOR.
2. ALL LOW VOLTAGE WIRING RELATED TO MECHANICAL EQUIPMENTAND SYSTEMS IS THE RESPONSIBILITY OF THE MECHANICALCONTRACTOR (ANY LOW VOLTAGE FIRE ALARM WIRING TO BE BYE.C.). ALL HIGH VOLTAGE CONNECTIONS TO MECHANICALEQUIPMENT, TO BE PROVIDED AND INSTALLED BY E.C. (SEEEQUIPMENT SCHEDULE FOR DISCONNECT RESPONSIBILITY).
3. G.C. TO BE RESPONSIBLE FOR PROVIDING AND INSTALLING ANYACCESS DOORS (WALL, FLOOR, CEILING) RELATED TO ELECTRICALSYSTEM. E.C. RESPONSIBLE FOR COMMUNICATING TO G.C. SIZE ANDLOCATION OF REQ'D ACCESS DOOR(S).
4. ELECTRICAL CONTRACTOR IS TO EMPLOY THE SERVICES OF THE G.C.FOR CUTTING AND PATCHING OF WALLS, FLOORS & CEILINGSRELATED TO THE INSTALLATION OF ELECTRICAL EQUIPMENT &SYSTEMS.
5. G.C. RESPONSIBLE FOR PAINTING OF ANY EXPOSED CONDUIT, WIRE,BOXES ETC. E.C. RESPONSIBLE FOR CLEANING AND PREPARINGITEMS FOR PAINT, COORDINATE W/ G.C.
6. E.C. TO COORDINATE W/ G.C. PRIOR TO BID REGARDING HIRING OFFIRE ALARM, DATA/TELE & SECURITY SUB-CONTRACTORS (IFAPPLICABLE).
III. MATERIALS:
1. ALL MATERIAL, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BENEW UNLESS OTHERWISE NOTED AND SHALL CONFORM TO THESTANDARDS OF THE UNDERWRITER'S LABORATORIES, INC., AND THENATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION.
2. ALL MATERIALS INSTALLED IN RETURN PLENUM ARE TO BE PLENUMRATED.
3. PROVIDE HANGERS & SUPPORTS APPROVED FOR USE BY NEC.
4. ALL FIRE SEALANTS TO BE U.L. LISTED AND APPROVED FOR USE W/APPROPRIATE U.L. PENETRATION DETAIL.
5. CONDUCTORS SHALL BE COPPER RATED AT NOT LESS THAN 600VOLTS.MINIMUM SIZE SHALL BE #12 AWG UNLESS OTHERWISE NOTEDON THE DRAWINGS. ALL WIRE #8 AWG AND LARGER SHALL BESTRANDED. ALL CONDUCTORS #10 AND SMALLER MAY BE SOLID ORSTRANDED, UNLESS OTHERWISE NOTED. CONDUCTOR INSULATIONSHALL BE TYPE THHN UNLESS OTHERWISE NOTED. ALL EXTERIOR CABLEOR OTHER WIRE EXPOSED TO SUNLIGHT SHALL BE RATED FOREXTERIOR USE & SUNLIGHT RESISTANT.
6. ALL WIRING SHALL BE INSTALLED IN GALVANIZED RIGID CONDUIT,INTERMEDIATE METAL CONDUIT, OR EMT, EXCEPT AS ALLOWEDBELOW. EMT SHALL NOT BE USED IN OR UNDER CONCRETE SLABS,OR IN MASONRY WALLS. USE SCHEDULE 40 PVC OUTDOORS WHERENOT SUBJECT TO PHYSICAL DAMAGE OR BELOW FLOOR SLAB.MINIMUM CONDUIT SIZE TO BE 1/2". TYPE MC AND AC CABLE MAYBE USED WHERE PERMISSIBLE BY NEC. FLEXIBLE CONDUIT SHALL BEUSED FOR CONNECTIONS TO VIBRATING EQUIPMENT ANDLUMINAIRES, BUT SHALL NOT EXCEED 6' IN LENGTH.
BALLAST DATA
LIGHTING FIXTURE SCHEDULEMANUF.MARK NUMBER
CATALOG LAMP DATANO. TYPE
VOLTSNO. TYPE WATTS
INPUT MOUNTING DESCRIPTION
NOTES:1. UNLESS OTHERWISE NOTED COLOR & FINISH OF FIXTURE HOUSING, BAFFLE, OR SIMILAR EXPOSED ELEMENTS TO BE BY ARCHITECT.2. WHERE MASTER SLAVE WIRING CONFIGURATIONS IS INDICATED THE CONTRACTOR SHALL VERIFY THE QUANTITY AND TYPE OF BALLASTS REQUIRED TO PERMIT BI-LEVEL SWITCHING. WHERE
BI-LEVEL LIGHTING IS INDICATED INBOARD AND OUTBOARD LAMPS SHALL BE SWITCHED SEPARATELY.3. EXIT AND EMERGENCY LIGHTING FIXTURES SHALL BE CIRCUITED TO AN UNSWITCHED LEG OF A NORMALLY ON LOCAL LIGHTING CIRCUIT (UNLESS NOTED OTHERWISE),INCLUDE 90 MINUTE BATTERY
BACKUP & TESTING MEANS.4. PROVIDE DISCONNECT FOR LUMINAIRES WITH LINEAR FLUORESCENT LAMPS AND/OR SERVICEABLE BALLASTS PER NEC 410.130(G).5. FIXTURES WITH A STANDARD FACTORY INSTALLED EMERGENCY OPTION SHOULD USE THAT WHERE "EMC" IS SHOWN.6. ALL LAMPS OF A SINGLE FIXTURE TYPE INSTALLED IN EACH AREA/ROOM/SPACE ARE TO BE OF SAME TEMPERATURE/COLOR.
WALL SWITCH MICROPHONIC OCCUPANCY SENSOR EQUAL TO SENSOR SWITCH MODEL WSPDT. TIME DELAYS 10 MINUTES FOR ON/OFF.
NOTE:THE CONTRACTOR IS TO PROVIDE AND INSTALL ALL RELAYS, CONTROLS, SWITCHES, ETC FORA FULLY FUNCTIONING SYSTEM REGARDLESS OF PRESENCE OR ABSENCE ON PLANS.
NOTE:THE MOTION SENSOR LAYOUT SHALL BE REVIEWED AND ADJUSTED BY THE ACTUAL DEVICEMANUFACTURER WHICH THE CONTRACTOR SELECTS. THE CONTRACTOR SHALL PROVIDESHOP DRAWINGS FOR THE SYSTEM TO THE ENGINEER FOR REVIEW, PRIOR TO PURCHASE ANDINSTALLATION.
MOTION SENSOR LEGENDM0
ELECTRICAL ABBREVIATIONS
18"
AFF
AFG
E.C.
FPN
G.C.
M.C.
P.C.
WP
UON
FACP
SMP
DIMENSION INDICATES HEIGHT ABOVE FINISHED FLOOR AT WHICH CENTER OF DEVICE IS TO BE MOUNTED.
ABOVE FINISHED FLOOR.
ABOVE FINISHED GRADE.
ELECTRICAL CONTRACTOR.
FUSE PER EQUIPMENT NAMEPLATE REQUIREMENTS.
GENERAL CONTRACTOR.
MECHANICAL CONTRACTOR.
PLUMBING CONTRACTOR.
INDICATES DEVICE TO HAVE WEATHERPROOF COVER.
UNLESS OTHERWISE NOTED.
FIRE ALARM CONTROL PANEL.
SPRINKLER MONITORING PANEL.
NIGHT LIGHT, LIGHT NOT SWITCHED.NL
WEATHER PROOFWP
ELECTRICAL SYMBOL LEGEND
J
EF
CIRCUIT CONDUCTORS CONCEALED IN FLOOR, WALL OR CEILING.
ARROWHEAD INDICATES HOMERUN TO PANEL NOTED.
INDICATES HOT LEG OF CIRCUIT TO BE CARRIED OVER TO NEXT DEVICE. SEE PLANS FORCONTROL SCHEME.
JUNCTION BOX CEILING MOUNTED.
JUNCTION BOX FLOOR MOUNTED.
JUNCTION BOX WALL MOUNTED AT HEIGHT INDICATED ON DRAWINGS.
SINGLE POLE SWITCH, 20A, 120/277 VOLT, 48" A.F.F. TO CENTER. "3" INDICATES 3-WAY SWITCH. "4" INDICATES 4-WAY SWITCH. "D" INDICATES DIMMER SWITCH OF TYPE TO SUIT LOAD. "M" INDICATES 120V, 20A MOTOR RATED TOGGLE SWITCH. "DP" INDICATES DOUBLE POLE
INDICATES FLUORESCENT FIXTURES DUAL SWITCHED, INBOARD/OUTBOARD SWITCHEDSEPARATELY.
SINGLE RECEPTACLE, 20 AMP, 120 VOLT, 18" A.F.F. TO CENTER.
DUPLEX RECEPTACLE, 20 AMP (15 AMP RESIDENTIAL, UON), 120 VOLT, 18" A.F.F. TO CENTER. "GFI" INDICATES GROUND FAULT CIRCUIT INTERRUPTER TYPE. "WP" INDICATES WEATHERPROOF. "EWC" INDICATES RECEPTACLE INSIDE ENCLOSURE OF ELECTRIC WATER COOLER PROVIDE
GFI BREAKER FOR CIRCUIT. "ASW" INDICATES ABOVE SHOW WINDOW, PER NEC SHOW WINDOW REQ'S.
QUADRUPLEX RECEPTACLE, AS ABOVE, 18" A.F.F.
DUPLEX RECEPTACLE, AS ABOVE, SPLIT WIRED, TOP HALF SWITCHED, 18" A.F.F.
DUPLEX RECEPTACLE, AS ABOVE, MOUNTED 6" ABOVE COUNTER TOP OR 4" ABOVEBACKSPLASH, AS APPROPRIATE, OR AT HEIGHT INDICATED.
DUPLEX RECEPTACLE, AS ABOVE, MOUNTED 6" ABOVE COUNTER TOP OR 4" ABOVEBACKSPLASH, AS APPROPRIATE, OR AT HEIGHT INDICATED, WITH GFI PROTECTION.
RECESSED FLUSH FLOOR DUPLEX RECEPTACLE WITH BRASS COVERPLATE. COORDINATEEXACT FINISH WITH ARCHITECT AND OWNER.
208V RECEPTACLE, SEE PLANS FOR NEMA CONFIGURATION.
TELEPHONE/DATA OUTLET, 18" A.F.F. TO CENTER OR ALIGN MOUNTING HEIGHT WITHADJACENT DEVICE, UNLESS OTHERWISE NOTED. COORDINATE EXACT DEVICE TYPE ANDREQUIRED FACEPLATE W/ OWNER/TENANT.
HEAVY DUTY FUSIBLE/NON-FUSIBLE DISCONNECT SWITCH, NUMBERS INDICATE FRAME SIZE,NUMBER OF POLES AND FUSING. PROVIDE NEMA 1 ENCLOSURE INSIDE. PROVIDE NEMA 3ENCLOSURE FOR ALL SWITCHES LOCATED OUTSIDE. "FPN" INDICATES FUSE PER EQUIPMENT NAMEPLATE "NF" INDICATES NON-FUSED. "MS" INDICATES MOTOR STARTER OF TYPE TO SUIT LOAD.
208Y/120V PANEL, SURFACE OR RECESS MOUNTED, SEE SCHEDULE FOR DETAILS.
480Y/277V PANEL, SURFACE OR RECESS MOUNTED, SEE SCHEDULE FOR DETAILS.
FAN, PROVIDED AND INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICALCONTRACTOR. PROVIDE DISCONNECTING MEANS AS REQUIRED.
RECESSED MOUNTED 2x4 FLUORESCENT TROFFER, SEE FIXTURE SCHEDULE FOR DETAILS.
TRACK LIGHTING FIXTURE, SEE FIXTURE SCHEDULE FOR DETAILS.
SURFACE MOUNTED FLUORESCENT STRIP, SEE FIXTURE SCHEDULE FOR DETAILS.
WALL MOUNTED LIGHTING FIXTURE, SEE FIXTURE SCHEDULE FOR DETAILS.
SURFACE, RECESSED OR GROUND MOUNTED LIGHTING FIXTURE, SEE FIXTURE SCHEDULE FORDETAILS.
ELECTRIC UTILITY METER LOCATION.
KITCHEN EQUIPMENT TAG.
DEMO'D LIGHT FIXTURE OR SIMILAR.
DEMO'D RECEPTACLE OR SIMILAR.
CABLE TV OUTLET, 18" A.F.F. TO CENTER, UNLESS OTHERWISE NOTED.
M
30/3/FPN
###
TV
VS.NONTRADABLE EXTERIOR WATTAGE SPECIFIED VS. ALLOWED
EXTERIOR LIGHTING POWER DENSITY CALCULATION PER TABLE 505.6.2. SEE LIGHTINGFIXTURE SCHEDULE FOR FIXTURE INFORMATION.
INTERIOR LIGHTING POWER DENSITY CALCULATION PER TABLE 505.5.2. SEE LIGHTINGFIXTURE SCHEDULE FOR FIXTURE INFORMATION.
TRADABLE EXTERIOR WATTAGE SPECIFIED VS. ALLOWED VS.
SIGNED:
TITLE:NAME:
ELECTRICAL ENGINEER
VS.INTERIOR WATTAGE SPECIFIED VS. ALLOWED
LIGHTING POWER DENSITY CALCULATION COMPLIANCE DESIGNER STATEMENT:TO THE BEST OF MY KNOWLEDGE AND BELIEF, THE DESIGN OF THIS BUILDING COMPLIESWITH THE LIGHTING SYSTEMS REQUIREMENTS OF THE NORTH CAROLINA ENERGYCONSERVATION CODE, SECTION 505 & 506 AND ANY LOCAL AMENDMENTS THEREOF.
LIGHTING SYSTEMSNCECC SECTION 505 & 506
ZACK L. TOMLIN, PE
ADDITIONAL PRESCRIPTIVE COMPLIANCENOT APPLICABLE (RENOVATION PROJECT)506.2.1 MORE EFFICIENT MECHANICAL EQUIPMENT506.2.2 REDUCED LIGHTING POWER DENSITY506.2.3 ENERGY RECOVERY VENTILATION SYSTEM
506.2.4 HIGHER EFFICIENCY SERVICE WATER HEATING506.2.5 ON-SITE SUPPLY OF RENEWABLE ENERGY506.2.6 AUTOMATIC DAYLIGHTING CONTROL SYSTEMS
1,683 1,692
EXIST. EXIST.NA NA
X
WALLMOUNTEDTELEPHONE
48"
FLOOR
TOP OF COUNTER
CEILING
FIRE ALARM HORN,HORN/STROBE ORSTROBE.
18"
TELEPHONE ORDATA JACK
46"
46"
FIRE ALARMPULL STATION
LIGHT SWITCHOR DIMMER
RECEPTACLE
80"
FIRE
ALIGN DEVICES WHENMOUNTED CLOSE ON
SAME WALL
42"
36" M
AX
MAX COUNTERDEPTH = 24"
NOTE:DEVICE HEIGHTS ARE TOBE AS INDICATED UNLESSOTHERWISE NOTED.
SWITCHTELE/DATA
RECEPTACLE
1 NO SCALE
TYPICAL DEVICE MOUNTING HEIGHTS
NOTE:MOUNTING LOCATIONS OF RECEPTACLES, SWITCHES AND ALLOTHER CONTROL DEVICES SHALL BE IN ACCORDANCE WITHANSI A117.1 AND ADA REQUIREMENTS (FHA REQ'S FORMULTI-FAMILY AND RESIDENTIAL PROJECTS)
A LITHONIA 2SP8 G 2 32W T8 MVOLT GEB10RS1 64 LAY-IN 2x4 2-LAMP ACRYLIC LENSED LAY-IN RECESSEDTROFFER
C LITHONIA ZL1 1 32W LED MVOLT DRIVER1 32W SURFACE 48" LED STRIP LIGHT. INSTALL IN COVE, COORD W/ARCH. DIMMABLE.
D LITHONIA ZL1 1 32W LED MVOLT DRIVER1 32W SURFACE 24" LED STRIP LIGHT. INSTALL IN COVE, COORD W/ARCH. DIMMABLE.
E - - - - 120 -- 20W WALLWALL SCONCE LIGHT. SELECTED BY OTHERS.PROVIDED & INSTALLED BY E.C.. INCLUDE$100/FIXTURE MAT'L ALLOWANCE IN BID.MAX
F - - - - 120 -- 30W/FT TRACKTRACK LIGHT. SELECTED BY OTHERS. PROVIDED &INSTALLED BY E.C.. INCLUDE $75/TRACK HEAD MAT'LALLOWANCE IN BID.
MAX
LITHONIA LQC 1 LED 120, - 1.2 CEILING EXIT LIGHT W/ BATTERY BACK-UP. RED ILLUMINATEDEXIT SIGN. ALUM. FACE. HOUSING COLOR BY ARCH.-277
- - - - - MFG CONCEALED EMERGENCY BATTERY PACK. COORDINATE W/FIXTURE TYPE/MFG. PROVIDE TEST SWITCH/LIGHT.-120,
277EMG
B GOTHAM AFV 1 13W TRT MVOLT ELECTRONIC1 13W RECESSED 4" RECESSED CAN/DOWNLIGHT. NO LENS
G - - - - 120 -- 50W CHANDELIERCHANDELIER LIGHT. SELECTED BY OTHERS.PROVIDED & INSTALLED BY E.C.. INCLUDE$300/FIXTURE MAT'L ALLOWANCE IN BID.MAX
LITHONIA LHQM 2 5.4 W T-5 120, - 3.3 CEILINGEXIT-EMERGENCY LIGHT COMBO. (2) ADJ. HEADS.BATTERY BACK-UP. RED ILLUMINATED EXIT SIGN.HOUSING COLOR BY ARCH.
-277
LITHONIA ELM2 2 5.4 W - 1.2 SEE PLAN GEN. PURPOSE EMERGENCY LIGHT. (2) ADJ. HEADS.BATTERY BACK-UP.-120,
277
LITHONIA ELAT QWP 2 1.5W LED - - SEE PLANREMOTE EXTERIOR EMERGENCY LIGHT. TWIN HEAD.BATTERY BACK-UP (CAN BE WIRED TO EXIT UNIT).WET LOCATION LISTED.
-120,277E
MDB-1402
MAR. 18, 2014
REVISIONS
DATE
DRAWN BY
SHEET TITLE
PROJECT NO.
SHEET
MARLIN DESIGN BUILD
OF
1405 HILLSBOROUGH STRALEIGH, NC 27605
mapleENGINEERING, pllc
plumbing mechanical electrical
LIC.#: P-0990P:919-341-4247 F:919-890-3797
PO Box 1852Cary, NC 27512Phone: (919) 291-6736
3/18/14
FIRE RATING LEGEND1-HR WALL2-HR WALL
E1.12 3
MJL
ELECTRICALLIGHTING& POWER
PLAN
1 SCALE: 1/4" = 1'-0"
ELEC. POWER PLAN2 SCALE: 1/4" = 1'-0"
ELEC. LIGHTING PLAN
RestrmPassage
Office
Waxing
Waxing
Pedicure Area
Manicure Area
Reception
Restrm
Passage
Office
Waxing
Waxing
Pedicure Area
Manicure Area
Reception
A
A
A
A
A
AB
B
B
B
B
B
B
B
B
B
B
B
B
B
B
G
G
E
E
E
E
E
F
F
F
F
F
F
G
G
SOLID COPPERMIN. 8 AWG
PUMPRECIRCULATING
HW LINE
CW LINE
WASTE LINE
M
RECEPTACLE PROTECTED BY GFIBREAKER. SEE PANEL SCHEDULE.
PEDICURE CHAIR
FINISH FLOOR
WATER BASIN
TO OTHERCHAIRS
RECIRCULATING
=BONDING POINT
ALL PEDICURE CHAIRS TO BE U.L. LISTED.
4 NO SCALE
PEDICURE CHAIR BONDING DETAIL
NOTE: ANY OTHER GROUNDEDMETAL COMPONENTS NOTSHOWN THAT MAKE CONTACTWITH RECIRCULATING WATERMUST BE BONDED AS WELL.
+48"
+48"
1
TAGGED NOTES - THIS SHEET1 PROPOSED SWITCH BANK LOCATION. CONFIRM W/
OWNER.
GENERAL NOTES - THIS SHEET1. ITEMS SHOWN IN FAINT & HATCHED ARE TO BE DEMO'D OR
RELOCATED. ITEMS SHOWN IN FAINT ARE EXISTING TOREMAIN. NEW OR RELOCATED ITEMS ARE SHOWN IN BOLD.SEE LEGEND.
2. ENSURE THAT ALL EXIT AND EMERGENCY LIGHTS ARECONNECTED TO LOCAL NORMALLY ON LIGHTING CIRCUITAND ARE WIRED UPSTREAM OF ALL SWITCHES,CONTACTORS, AND SIMILAR.
3. "C" & "D" FIXTURES TO BE INSTALLED IN RECESSED CEILINGFIXTURE. COORDINATE EXACT LOCATION OF FIXTURES W/ARCH. & OWNER.
M0
M0
M0
EF
L
N
O
P
R
S
UN
DIMMER SWITCH
L O
DIMMER SWITCH
P
DIMMER SWITCH
RFRNT TRACKFRNT TRACK FRNT TRACK FRNT TRACK MANI. WALL
A-1A-1 A-3 A-3 A-5
SWITCH BANK NOTES:1. COORDINATE EXACT SWITCH TYPE W/ OWNER AND FIXTURES & BALLAST(S) BEING CONTROLLED.2. LABEL SWITCHES W/ DESIGNATION SHOWN (I.E. "A", "AN", "W", ETC) & CIRCUIT #.3. PROVIDE PLACARD AT EACH SWITCH INDICATING AREA CONTROLLED.4. DIMMER SWITCH TO INCLUDE ON-OFF SWITCH AT BOTTOM TO ALLOW FOR ONE-TIME ADJUSTMENT OF
LIGHT LEVELS.5. HIGHEST POSITION OF HIGHEST SWITCH TO BE NO GREATER THAN 48" AFF (ANSI A117.1)
3 NO SCALE
SWITCH BANK DETAIL
SMANI. WALL
A-5
DIMMER SWITCH
A-3
A-1
OFF
SINGLE SWITCH
OFF
SINGLE SWITCH
UPEDI. CANS
A-7
OFF
SINGLE SWITCH
A-7
A-9
A-5
A-20
A-22
A-24
A-26
A-28
A-30
A-32
A-34
A-36
A-38
A-40
A-42
2
2 RECEPTACLE FOR PEDICURE CHAIR. CONFIRMLOCATION OF RECEPTACLE W/ OWNER. SEE PEDICURECHAIR DETAIL.
EMG
A-2
A-2
A-4
A-4
A-4
A-6
A-6
A-6
A-8
A-8A-10
A-10
A-12
A-12
A-8
RTU-1
A-37,39,41
A-13,15
A-17 A
WH-160/2/FPN
3 COORDINATE EXACT LOCATION OF RECEPTACLE W/OWNER & CASEWORK.
3
ABV. CEIL.
C
C
C
C
C
C
C
C
DD
DD
X
X
DIMMER SWITCH
LED STRIP LTSA-7
EMG
EMG
EMG
EMG
EMG
D
A-11
ASWA-14
EF4 RTU TO INCLUDE FACTORY MOUNTED DISCONNECT.
AND FACTORY POWERED GFI CONVENIENCE OUTLET.COORDINATE W/ M.C..
4
EF
Y
A-16
A-18
5 EXHAUST FAN LOCATED ON ROOF. CONTROLLED VIAWALL SPEED CONTROLLER SWITCH PROVIDED BYM.C.. SWITCH LOCATED IN SWITCH BANK.
5
5
Y
FAN SWITCH
EF-MANICUREA-16
Z
FAN SWITCH
EF-PEDICUREA-18
(IF METAL)
(IF METAL)
(IF METAL)
E
E
6
6 COORDINATE EXACT LOCATION OF JUNCTION BOXSIGN CIRCUIT W/ OWNER.
A-33,35
Z
MDB-1402
MAR. 18, 2014
REVISIONS
DATE
DRAWN BY
SHEET TITLE
PROJECT NO.
SHEET
MARLIN DESIGN BUILD
OF
1405 HILLSBOROUGH STRALEIGH, NC 27605
mapleENGINEERING, pllc
plumbing mechanical electrical
LIC.#: P-0990P:919-341-4247 F:919-890-3797
PO Box 1852Cary, NC 27512Phone: (919) 291-6736
3/18/14
E2.13 3
MJL
PANELSCHEDULE
& RISER
1. PANEL SHALL BE EQUAL TO SQUARE D NQ.2. PROVIDE HACR BREAKERS FOR HVAC EQUIPMENT.3. GFI - PROVIDE GFCI BREAKER FOR CIRCUIT. GFCI RECEPTACLES MAY BE USED IN LIEU OF GFCI
BREAKERS SO LONG AS THE DEVICE(S) CONFORM TO NEC CODE REQUIREMENTS FOR GFCIPROTECTION & ACCESSIBILITY.
4. TC - CIRCUIT THROUGH 7-DAY PROGRAMMABLE TIME SWITCH WITH AUTO-DUSK, AUTO-DAWNFEATURE. SWITCH TO INCLUDE MANUAL OVERRIDE.
XFMRUTILITY
kVA300MAIN SERVICEDISCONNECT
1,600AMCB
3Ø/4W208Y/120V
200A
MLO1,600A
208Y/120V3Ø/4W
M
150A
M
150A
M
100A
M
200A
M
200A
M
200A
MEXIST.
400A
FROM UTILITY
PANEL
A
A
200 MLO208Y/120VNOTE 10
1 NO SCALE
ELECTRICAL POWER RISER
RISER DIAGRAM NOTES:1. ALL EXISTING ITEMS ARE SHOWN IN FAINT. NEW ITEMS ARE SHOWN IN BOLD.2. E.C. TO CONFIRM RISER BEFORE BEGINNING WORK. CONTACT ENGINEER IF SIGNIFICANT
DISCREPANCIES ARE FOUND.3. (4)#3/0 CU, #6 CU GND, 2" CONDUIT.4. E.C. TO CONFIRM PRESENCE OF GROUNDING/BONDING SYSTEM (NEC 250).5. EXISTING 1,600 AMP MAIN DISCONNECT. E.C. TO CONFIRM. CONTACT ENGINEER IF OF LESSER
AMPACITY.6. EXISTING EMPTY METER/DISCONNECT BASE.7. EXISTING METER BASE. NEW METER BY UTILITY. E.C. TO VERIFY LOCATION OF METER/DISCONNECT
FRAME THAT SERVES CORRESPONDING TENANT SPACE.8. PROVIDE PLACARD AT PANEL(S)/DISCONNECT(S) INDICATING SUITE/TENANT & PANEL SERVED.9. PROVIDE PLACARD INDICATING AVAILABLE AIC FAULT CURRENT (NEC 110.24)10. MAIN BREAKER, PANEL AND BRANCH CIRCUIT BREAKERS TO BE PAIRED TO ENSURE 42,000 AIC
RATING IS MAINTAINED THROUGHOUT. COORDINATE W/ EQUIPMENT MFG.
NEXT TO BACK DOOR 3 PHASE, 4 WIRE
VOLTAGE: 208Y/120V PANEL: A FLUSH MOUNTED
AMPS: 200-MLO LOAD PER PHASE NEMA 1
NOTES -DESCRIPTION- POLE WIRESIZE
BRKSIZE
CKT# A B C CKT# BRK
SIZEWIRESIZE POLE -DESCRIPTION- NOTES
LTS: FRONT TRACKS 1 12 20 1 1.0 0.6 2 20 12 1 REC: RECEPT/WAITINGLTS: MANICURE TRACKS 1 12 20 3 1.5 0.6 4 20 12 1 REC: MANI. AREA RIGHTLTS:CHANDLRS,WALL SCON. 1 12 20 5 0.6 0.6 6 20 12 1 REC: MANI. AREA LEFTLTS: PEDI. AREA 1 12 20 7 1.0 0.6 8 20 12 1 REC: WAXING 103/RESTRMLTS: BACK OFF,WAX, HALL 1 12 20 9 0.8 0.4 10 20 12 1 REC: WAXING 105
TC SIGN 1 12 20 11 1.2 0.4 12 20 12 1 REC: OFFICE
DRYER 2 10 3013 2.5 0.2 14 20 12 1 REC: SHOW WINDOW15 2.5 0.5 16 20 12 1 EF-1
GFI WASHER 1 12 20 17 1.0 0.5 18 20 12 1 EF-2SPARE 1 - 20 19 0 1.5 20 20 12 1 PEDICURE STATION CHAIR GFISPARE 1 - 20 21 0 1.5 22 20 12 1 PEDICURE STATION CHAIR GFISPARE 1 - 20 23 0 1.5 24 20 12 1 PEDICURE STATION CHAIR GFISPACE 1 - - 25 0 1.5 26 20 12 1 PEDICURE STATION CHAIR GFISPACE 1 - - 27 0 1.5 28 20 12 1 PEDICURE STATION CHAIR GFISPACE 1 - - 29 0 1.5 30 20 12 1 PEDICURE STATION CHAIR GFISPACE 1 - - 31 0 1.5 32 20 12 1 PEDICURE STATION CHAIR GFI
WH-1 2 8 4033 3.0 1.5 34 20 12 1 PEDICURE STATION CHAIR GFI35 3.0 1.5 36 20 12 1 PEDICURE STATION CHAIR GFI
RTU-1 3 8 45
37 2.8 1.5 38 20 12 1 PEDICURE STATION CHAIR GFI39 2.8 1.5 40 20 12 1 PEDICURE STATION CHAIR GFI41 2.9 1.5 42 20 12 1 PEDICURE STATION CHAIR GFI
14.7 18.1 16.2TOTAL CONNECTED kVA: 49.0 DEMAND kVA: 55.9
PANEL RMS SYM. AMPS: SEE RISER DEMAND AMPS: 155.2
SHORT CIRCUIT CALCULATIONMAXIMUM AVAILABLE FAULT CURRENT IS BASED ON A THE TX KVA, IMPEDANCE (%Z),WIRE SIZE & LENGTH SHOWN BELOW. CONTRACTOR SHALL NOTIFY ENGINEERIMMEDIATELY IF TRANSFORMER CHARACTERISTIC INDICATE A HIGHER FAULT CURRENTIS POSSIBLE (HIGHER KVA, LOWER IMPEDANCE, LARGER SECONDARY WIRE, SHORTERSECONDARY LENGTH, ETC).
TX KVA TX %Z VOLTAGE PHASE # COND.PER Ø WIRE SIZE
WIRE L.(FEET) WIRE "C"
300 2.5 208 3 2 500 kcmil 30 26706
CURRENT(L TO L)
MULT.(ISC) TX ISC f M ISC (AMPS)
833 40.00 33309 0.1558 0.8652 28819
PANEL "A" LOAD SUMMARYLOAD TYPE kVA
CONN.DEM.FACT.
kVADEM.
LOADS ON 200AMP MCB @ METER
LIGHTS (1,200 SQ FT @ 3W/SQ FT > CONN. LOAD) 3.6 1.25 4.5
TRACK LIGHTS (28 FT) 2.1 1.25 2.6
RECEPTACLES
1st 10 kVA 2.8 1.0 2.8
REMAINDER 0.0 0.5 0.0
SHOW-WINDOW (7 FT @ 125%) 0.2 8.75 1.8
HVAC & R
ELEC HEAT 0.0 1.0 0.0
LARGEST MOTOR 6.0 1.25 7.5
REMAINDER 2.5 1.0 2.5
WATER HEATER (ELECTRIC) 6.0 1.25 7.5
LAUNDRY EQUIPMENTWASHERS 1.0 1.0 1.0
DRYERS5.0 1.0 5.0
# OF ELECTRIC DRYERS: 1
PEDICURE CHAIR 18.0 1.0 18.0
SIGN 1.2 1.25 1.5
EF-1,EF-2 1.0 1.25 1.3
TOTALS 49.4 55.9
TOTAL AMPS @ 208 V 3 PHASE 155.2
M
NOTE 3
NOTE 5
ELECTRICAL POWER RISER
NOTE 4
NOTE 6
NOTE 6
NOTE 7
GRADE NAIL SALON
EXISTING ELECTRICAL SERVICE/METER CENTER. SEE. RISER.
AREA OFWORK
2 NO SCALE
BUILDING PLAN
METER CENTER MAIN BUS - LOAD SUMMARYSUM OF EXISTING TENANT DISCONNECTS = 1,000A + 153.8A NEWTENANT LOAD = 1,153.8A < 1,600A MLO.
MAIN SERVICE DISC. - LOAD SUMMARYSUM OF EXISTING TENANT DISCONNECTS = 1,400A + 153.8A NEWTENANT LOAD = 1,553.8A < 1,600A MCB.
N