LOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The term of validity is one year from the issued date. Nameplate FOR DEALERS LGH-150RX4-E LGH-200RX4-E Nameplate Repair work should be performed by the manufacturer, its service agent or similarly qualified person in order to avoid a hazard. March 2006 No. U111 (Revised to RoHS)
Transcript
Page 1: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

LOSSNAYHAND BOOK(For HONG KONG)

Model: LGH-15RX4-ELGH-25RX4-ELGH-35RX4-ELGH-50RX4-ELGH-65RX4-ELGH-80RX4-ELGH-100RX4-E

Notice:The term of validity is one year from the issued date.

Nameplate

FOR DEALERS

LGH-150RX4-ELGH-200RX4-E

Nameplate

Repair work should be performed by the manufacturer, its service agent orsimilarly qualified person in order toavoid a hazard.

March 2006 No. U111(Revised to RoHS)

Page 2: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Contents

Safety precautions........................................................................3

1. Specifications ....................................................................... 4-8

2. Dimensions ........................................................................ 9-17

3. Wiring diagrams ............................................................... 18-19

4. Troubleshooting ............................................................... 20-34

4-1 Service Flow.............................................................. 20-21

4-2 Items to Check .......................................................... 22-33

4-3 Circuit Test Point............................................................. 34

5. Overhaul procedures........................................................ 35-39

5-1 Blower Parts .............................................................. 35-36

5-2 Damper Movement Motor Part (All units available) ........ 37

5-3 Circuit Board Part ...................................................... 37-39

6. Parts list ........................................................................... 40-76

LGH-15RX4-E ............................................................... 41-44

LGH-25RX4-E ............................................................... 45-48

LGH-35RX4-E ............................................................... 49-52

LGH-50RX4-E ............................................................... 53-56

LGH-65RX4-E ............................................................... 57-60

LGH-80RX4-E ............................................................... 61-64

LGH-100RX4-E ............................................................. 65-68

LGH-150RX4-E ............................................................. 69-72

LGH-200RX4-E ............................................................. 73-76

Page 3: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

♦♦Turn off the power supplyBe sure to shut off the breaker before dis-assembling the unit for repair.

(Failure to heed this warning may result in elec-tric shock.)

♦♦Use proper parts and toolsFor repair, be sure to use the parts listed in the serviceparts list of the applicable unit model anduse the proper tools.

(Failure to heed this warning may result in elec-tric shock, fire and/or bodily injury.)

♦♦Proper electric workUse the electric wires designated for electric work, andconduct electric work in accordance with the "ElectricInstallation Engineering Standard," the "Indoor WiringRegulations," and the Installation WorkGuide.

(Incomplete connection or wiring installation mayresult in electric shock and/or fire.)

♦♦Replace damaged and/or degraded partsBe sure to replace the power-supply cord and lead wirein the event that they are damaged and/ordegraded.

(Failure to heed this warning may result in elec-tric shock and/or fire.)

♦♦Check insulationBe sure to measure the insulation resistance once therepair work is complete, and turn on the power supplyafter verifying that an insulation resistanceof at least 10MΩ is obtained.

(If an insulation problem exists, it may result inelectric shock.)

Be sure to follow this instruction.

Be sure to follow this instruction.

Be sure to follow this instruction.

Be sure to follow this instruction.

Be sure to follow this instruction.

♦♦Electric shockIf you must inspect the circuitry while thepower is on, do not touch the live parts.

(Failure to heed this warning may result in elec-tric shock.) Caution for

electric shock

♦♦Modification is prohibitedDo not modify the unit.

(Failure to heed this warning may result in elec-tric shock, fire and/or bodily injury.)

Prohibited

Incorrect handling of the product may result in serious injuryor death.Warning

♦♦Caution for bodily injuryDo not conduct any work at a locationwhere you do not have a sure footing.

(Failure to heed this caution may result in a fall.)Prohibited

Be sure to follow this instruction.

♦♦Wear glovesWear gloves when conducting work.

(Failure to heed this caution may result in injuryto your hands from sharp metal or other edges.)

•Inspect the grounding, and repair it if incomplete.

●Make sure that the product operates correctly upon completion of repair. Clean the product as well as the sur-rounding area, and then notify the customer of the completion of repair.

Incorrect handling of the product may result in serious injuryor damage to properties including buildings and equipment.Caution

Request during repair

—3—

Safety precautions●Please be sure to read the following safety precautions thoroughly before commencing with the maintenance

work, and conduct the inspection and repair of the product in a safe manner.●The types and levels of danger that may arise if the product is handled incorrectly are described by using the

warning symbols shown below.

Page 4: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—4—

1. Specifications

Page 5: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—5—

Page 6: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—6—

Page 7: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—7—

Page 8: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—8—

Page 9: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Unit (mm)

LGH-15RX4-E

2. Dimensions

—9—

Page 10: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Unit (mm)

LGH-25RX4-E

—10—

Page 11: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Unit (mm)

LGH-35RX4-E

—11—

Page 12: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—12—

Unit (mm)

LGH-50RX4-E

Page 13: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Unit (mm)

LGH-65RX4-E

—13—

Page 14: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—14—

Unit (mm)

LGH-80RX4-E

Page 15: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Unit (mm)

LGH-100RX4-E

—15—

Page 16: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—16—

Unit (mm)

LGH-150RX4-E

Page 17: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Unit (mm)

LGH-200RX4-E

—17—

Page 18: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

50/60Hz

3. Wiring diagramsLGH-15RX4-E,LGH-25RX4-E,LGH-35RX4-E,LGH-50RX4-E,LGH-65RX4-E,LGH-80RX4-E,LGH-100RX4-E

—18—

Page 19: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

50/60Hz

LGH-150RX4-E,LGH-200RX4-E

—19—

Page 20: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

4. Troubleshooting4-1 Service Flow

Confirmation items1 Condition of trouble – remote controller dis-

play, etc.2 Frequency of trouble – date of start of opera-

tion and occurrence3 Occurrence timing 4 Existence of drawings, equipment (including

controllers and equipment sold separately),cables, wiring, and settings.

Applicable modelsLossnayLGH-15 to 200RX4-E

Remote controllerPZ-41SLB-EPZ-52SF-E

Trouble Mode 1 The system will not start properly.

• The check code display appears on the remote controller.

• The LED of the Lossnay circuit board is blinking.

Check with the check code list (table 2).

Trouble Mode 3 The remote controller does not operate or operates irregularly.

The Lossnay does not operate or operates irregularly.

Trouble Mode 4

Check with the remote controller checklist (table 3).

Check with the Lossnay checklist (table 4).

Precautions when diagnosing malfunctions● When removing a transistor or printed circuit board, make sure the breaker is thrown.● When removing the circuit board, always hold it at both ends and remove carefully so as not to apply force to the surface

mounted parts.● When removing the circuit board, be careful of the metal edges on the board.● When removing or inserting the connectors for the circuit board, hold the entire housing section. Never pull on the lead

wires.● When servicing, be sure to recreate the malfunction 2 to 3 times before starting repairs.● If a malfunction of the printed circuit board is suspected, check for disconnected wires in the print pattern, burnt parts or dis-

coloration.● If the printed circuit board is replaced, make sure that the switch settings on the new board are the same as the old board.

—20—

• Check the initialization checklist from installation to operation (table 1-1).

• Check the system checklist (table 1-2).

Trouble Mode 2

Page 21: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Error ListU

nit e

rror

— —

Error item

— «

« « «

« «

«

« « «

«

«

«—

«««

— — — ——

—« « « «

« « «

« « «

—« « ««

—« « «

—« « «

«

« « «

2 times

3 times

4 times

8 times

9 times

6 times

8 times

1 - 5times

LED 6turn off

4000/4116

*1)

3602

*2)

5101

3126

0900

6600

6607

6608

6607/6608

6602/6603/6604

6608

• Cancellation

• Cancel damper operation• Other controls as normal

• Lossnay ventilationfixed (for “Auto” modes)

• Other controls as normal

• The Pre-heat output(X8) turns OFF

• Fan: High speed• Lossnay ventilation fixed

• Cancellation

• Cancellation

Fan motor operationdevice error

Damper motorerror

OA temperaturesensor error

Pre-heat error

«« «—«5 times —5102• Lossnay ventilation

fixed (for “Auto” modes)• Other controls as normal

RA temperaturesensor error

Test operation

Dual address

No ACK

No response

Controller communicationerror

Communicationcircuit error

«« « ««9 times —6801

*3)• Restricted to ON/OFF

Local transmis-sion cable com-municationerror

Polarity not set

PZ-41SLB-Ecommunica-tion error

Cla

ssifi

catio

nC

omm

unic

atio

n er

ror

Measures taken byLossnay

Remotecontrollerdisplayerrorcode

LED 1(green)Display(No. ofblinks)

LED 2(red)

Display(No. ofblinks)

Errormonitoroutput

*4)

Resetpowersupply

Changeaddress

Stop↓

Start

Errordelete

Cancellation measures

*1) “4000” is displayed on PZ-41SLB-E only.*2) This error is not generated in the LGH-150RX4, LGH-200RX4 model.*3) “6801” is displayed on the M-NET controllers only.*4) Since the error monitor output will turn into the preheat output if SW5-6 is turned ON, it becomes impossible to use it.

—21—

Page 22: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Do the capacity of the main power supply on/off unit and wiring span meet specification?

Checkpoint

1

No.

2 Is the specified power supplied to the Lossnay power terminal (TM1)?

3 Is the wiring length of the transmission cable within specifications?

When using PZ-41SLB-E: Overall extension within 500 m

When using M-NET: Maximum power supply length within 200 m, maximum distance between ends within 500 m

4 Does the transmission cable meet regulations? (Type, diameter)

5 Is the transmission cable wired at least 5 cm away from the power supply cable?

6 Are multiple transmission or signal cables wired to the same power cable duct?

7 Are multiple transmission cables wired with multi core cables?

8 Is the transmission cable connected to the terminal unit?

(PZ-41SLB-E to TM4 1, 2; M-NET to TB5 A , B )

9 Is the transmission cable securely connected to the Lossnay terminal unit?

10 When not using M-NET

If using 1 Lossnay unit, is the Main/Sub change switch (SW1) on the Lossnay circuit board set to “Main”?

If using 2 or more Lossnay units, is the Main/Sub switch set to “Main” on only one unit, and the other units are setto “Sub”?

11 When using M-NET

Is the address switch on the Lossnay circuit board (SA1, SA2) set to the correct number?

12 When using external control input

Do the specifications of the external signal match specifications of signals that can be input to the Lossnay?

13 When the external input signal is a pulse signal

Is the pulse input switch (SW2-2) on the Lossnay circuit board set to ON?

14 When the external signal is 12V DC, 24V DC, or Mr. Slim (A-control or K-control) signal

Is it connected to 1, 2 on the Lossnay external control input terminal unit (TM2)?

15 When the external signal is an uncharged a-contact signal

Is it connected to 1, 3 on the Lossnay external control input terminal unit (TM2)?

16 When M-NET is not being used

Is the external input signal connected to the Lossnay set to “Main”?

17 Is the signal cable length within wiring specifications?

12V DC, 24V DC signal: Within limitation of the external device

Uncharged a-contact signal: Within 500 m

Mr. Slim (A-control or K-control) signal: Within 500 m

18 Is the signal cable wired at least 5 cm away from the power supply cable?

19 Is the output capacity of the Lossnay operation monitor/malfunction monitor (pre-heat output) within specifications?

Operation monitor output: Maximum 240V AC/24V DC 2A, minimum 220V AC/5V DC 100 mA

Maifunction monitor output/pre-heat output:Maximum 240V AC/24V DC 2A, minimum 220V AC/5V DC100 mA

20 Are the power supply cable, transmission cable, signal cable, etc., securely connected to the proper terminals?

21 Are the settings for the Mai/Sub switch, address switch, and function select switch correct?

4-2 Items to Check(1)Trouble Mode 1: The system will not start properly.

Initialization checklist from installation to operation (Table 1-1)

After checking the system, check the points below up to operation.

—22—

Page 23: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

22 When pre-heat output output is used, turn the SW5-6 ON.

There is no method of turning ON the pre-heat output without changing OA temperature.

The first check of the installation

(1) Make the power supply of the heater turned off.

(2) Short-circuit the pre-heater output with a lead etc.

(3) Check weather the relay contact by the side of the heate rturns on.

The pre-heat output is never closed even if abnormalities, such as drawing out the OA/RA thermistor connector,occur.

« Check the power supply to theLossnay.

« Set the Main/Sub (SW1) switchto “Main.”

« Check the length of the trans-mission cable wiring.

« Connect the transmission cableto TM4 12.

« Change to the PZ-41SLB-Eremote controller.

1

No.

Remote controllerdisplay does notappear.

« Power is not supplied to the Lossnay, or poweroutside specifications is connected.

« When using only 1 Lossnay, the Main/Sub switch(SW1) on the Lossnay circuit board is set to “Sub.”

« The overall wiring length of the transmission cableis longer than specifications (longer than 500 m).

« The remote controller is connected to TB5 (M-NETtransmission cable).

« PZ-52SF-E is connected to the Lossnay localremote controller.

2 Remote controllerdoes not operate(Communication errordisplay)

« When using multiple Lossnay units, the Main/Subswitch (SW1) on the Lossnay circuit board of thesecond or following unit is set to “Main.”

« The overall wiring length of the transmission cableis longer than specifications (longer than 500 m).

« Multiple transmission cables are wired with multicore cables.

« Set the Main/Sub switch (SW1) ofthe second and following Lossnayunits to “Sub.”

« Check the length of the trans-mission cable wiring.

« For the applied transmissioncable, wire the transmissioncables away from the othertransmission cable.

3 Interlocked operationwith external devicedoes not occur.

« The type of external signal does not match theconnected terminal unit (charged, uncharged, Mr.Slim signal).

« The type of external signal does not match thepulse input switch (SW2-2) setting (level signal,pulse signal).

« The external device signal is not being input.

« The external device and signal cable wiring islonger than specifications

12V DC, 24V DC: Longer than limitations ofexternal device

Uncharged a-contact: Longer than 500 mMr. Slim signal: Longer than 500 m

« The Delayed Start mode is set at the remote con-troller (PZ-41SLB-E).

« The ON Interlocked Operation mode or OFFInterlocked Operation mode is set at the remotecontroller (PZ-41SLB-E).

« When using multiple Lossnay units, the externalcontrol input signal is connected to a unit with the“Sub” setting made.

« Check the connection to the exter-nal control input terminal (TM2) forthe type of external signal.

« Check the type of external signaland the setting of the pulse inputswitch (SW2-2).

« Check the external device.

« Check the length of the signalcable wiring.

« Check the Delayed Start modesetting at the remote controller(PZ-41SLB-E).

« Check the Interlocked Operationmode setting at the remote con-troller (PZ-41SLB-E).

« Connect the external controlinput signal to the Lossnay unitset to “Main.”

Symptom Cause Corrective action

System checklist

1Use this checklist when using a PZ-41SLB-E or an external device (Table 1-2-1)

—23—

CheckpointNo.

Page 24: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

« Turn the SW5-6 ON.

« Operate onry below -5˚C.

4

No.

Pre-heat control doesnot work.

« SW5-6 is OFF.

« OA temprature is larger than -5˚C.

Symptom Cause Corrective action

2System checklist when using the M-NET (Table 1-2-2)

« Check the Lossnay address, andset for an address correspond-ing to interlocked operation.

« Check the length of the trans-mission cable wiring.

« Change to the PZ-52SF-E remotecontroller (PZ-41SLB-E can notbe used with the M-NET).

1

No.

Does not interlock withCity Multi. (The Lossnaycannot be operated bythe ventilation switch onthe ME remote controller,MA remote controller, orMELANS.)

« The Lossnay is not set for interlocked opera-tion, or is set for interlocked operation at thewrong address.

« The length of the M-NET transmission cablewiring from the outdoor unit or the system’soverall wiring length is longer than specifica-tions. (Longer than 200 m from the outdoorunit, longer than 500 m between ends.)

« PZ-41LSB-E is connected to the Lossnay localremote controller.

Symptom Cause Corrective action

2 Cannot operate using theMELANS or Lossnayremote controller.

« The address that has been set for the group inMELANS and the address for the Lossnay aredifferent.

« The length of the M-NET transmission cablewiring from the power supply unit or the sys-tem’s overall wiring length is longer than speci-fications. (Longer than 200 m from the powersupply unit, longer than 500 m between ends.)

« PZ-41LSB-E is connected to the Lossnay localremote controller.

« Check the registered address inMELANS.

« Check the length of the trans-mission cable wiring.

« Change to the PZ-52SF-E remotecontroller (PZ-41SLB-E can not beused with a M-NET system).

3 A unit should operateindependently byMELANS or the Lossnayremote controller, but itinterlocks with anotherCity Multi unit.

« It has been set for interlocked operation withthe City Multi unit.

« Cancel the interlocked operationsetting.

4 Cannot perform groupsettings for the Lossnayusing MELANS, MEremote controller, or MAremote controller. (Theremote controller shows“88” at the time of regis-tration.)

« Power is not supplied to the Lossnay, or poweroutside specifications is connected.

« The M-NET transmission cable is connected toTM4 12.

« The transmission cable is not properly con-nected to the MELANS or the City Multi.

« The length of the transmission cable wiring is longer thanspecifications (longer than maximum 200 m from thepower supply unit, longer than 500 m between ends.)

« Check the power for the Lossnayand perform the registration again.

« Connect the transmission cableto TB5 A , B .

« Check the transmission cableconnection.

« Check the length of the trans-mission cable wiring.

—24—

5 When power is suppliedto the system, theLossnay remote con-troller continues to dis-play “HO” and does notstart. (Group registrationinformation disappears.)

« The Group setting was made on a Lossnayremote controller in a system connected to asystem controller.

« The length of the transmission cable wiring islonger than specifications (longer than maxi-mum 200 m from the power supply unit, longerthan 500 m between ends.)

« In a system connected to MELANS,make the group setting with theMELANS (Do not make the group set-ting with the Lossnay remote controller).

« Check the length of the trans-mission cable wiring.

Page 25: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

« Check remote control unit numberlimitations when using a powersupply unit.

« Check the length of the trans-mission cable wiring.

6 When power is suppliedto the system, theremote control displaygoes blank and the sys-tem does not start.

« Over the number of units that can be controlledwith the Lossnay remote controller.

« The length of the transmission cable wiring islonger than specifications (longer than maxi-mum 200 m from the power supply unit, longerthan 500 m between ends.)

No. Symptom Cause Corrective action

—25—

7 The power display “ ”does not display whenpower is supplied to thesystem.

1 When using City Multi and Lossnay interlockedsystem (connected to the indoor unit system)

« The transmission cable is not correctly con-nected to the Lossnay remote controller.

« The power is not turned on for the outdoor unit.

« The length of wiring for the outdoor unit’s M-NET transmission cable is longer than specifi-cation (longer than 200 m).

« Check the transmission cableconnection.

« Check the power to the outdoor unit.

« Check the length of the trans-mission cable wiring.

2 When using a Lossnay individual system orCity Multi and Lossnay interlocked system con-nected to the central system.

« The power supply unit is not connected to thetransmission cable.

« The power to the power supply unit is notturned on.

« The length of wiring of the M-NET transmissioncable from the power supply unit is longer thanspecification (longer than 200 m).

« Connect to the power supplyunit.

« Check the power to the powersupply unit.

« Check the length of the trans-mission cable wiring.

« Check the power to the Lossnay.

« Check the Lossnay remote con-troller address registration withthe MELANS (“HO displays for 3– 10 minute when electricity issupplied to the system).

« Connect the transmission cableto TB5 A , B .

« Check the Lossnay registrationwith the Lossnay remote con-troller.

8 The “HO” on the remotecontroller continues toflash when the power issupplied to the system.

« Lossnay is Not supplied with specified power.

« The address for the Lossnay remote controllerdoes not have a group setting at the MELANS.

« The M-NET transmission cable is connected toTM2 56.

« For a Lossnay individual system with noMELANS, Lossnay registration has not beenperformed by the Lossnay remote controller.

9 “LC 6608” displays onthe remote controller andthe Lossnay does notoperate.

« The remote controller is PZ-41LSB-E and con-nected to the TB5 A , B .

« Change to the PZ-52SF-Eremote controller (PZ-41SLB-Ecan not be used with a M-NETsystem).

10 The operation specifiedby the system controllerdiffers from the operationof the Lossnay.

« The remote controller is PZ-41SLB-E and con-nected to the TM4 1-2.

« Change to the PZ-52SF-Eremote controller (PZ-41SLB-Ecan not be used with a M-NETsystem).

Page 26: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

0.25S 0.25S 0.25S

5SOFF

ON

Error display example: Fan motor operation device error

1Checklist of error codes displayed on the PZ-41SLB-E and LED displays(Table2-1)

(2)Trouble Mode 2

●An error code displays on the remote controller.

●Lossnay circuit board LED is flashing or lit up.

An error code displayed on the remote controller (PZ-41SLB-E, PZ-52SF-E) or the M-NET controller and blinkingor illumination of LED1 (green) or LED2 (red) on the circuit board shows the type of error. The LED blink intervalis 0.25 seconds for both on and off. The display duration is approximately 5 seconds.

LC 6608

Error code*1

LED1(green)

LED 2(red)

Lossnaycommuni-cationerror

« When using multiple Lossnay units, themain/sub setting has not been madefor the second unit and following units.

« Multiple transmission cables havebeen wired using multi core wires.

« Transmission cable and power cableare too close.

« Transmission cable is not securelyconnected.

« The length of wiring of the transmis-sion cable is longer than specifica-tion (longer than 500 m).

« Turn off the main power supply and setthe Main/Sub switch (SW1) (first unit tomain, second and following units to sub).

« Wire the transmission cable awayfrom the other transmission cable.

« Wire the transmission cable at least 5cm away from the power supply cable.

« Check the transmission cable con-nection.

« Check the length of the transmissioncable wiring.

Symptom Cause Corrective action

RC6608

SRC 6608

— — Communication errorbetweenremote con-trollers(when 2remote con-trollers areconnected)

« Multiple transmission cables havebeen wired using multi core wires.

« Transmission cable and power sup-ply cable are too close.

« Transmission cable is not securelyconnected.

« The length of wiring of the transmis-sion cable is longer than specifica-tion (longer than 500 m).

« Wire the transmission cable awayfrom the other transmission cable.

« Wire the transmission cable at least 5cm away from the power supply cable.

« Check the transmission cable con-nection.

« Check the length of the transmissioncable wiring.

LC 0900

SLC 0900

— — Lossnaytrial opera-tion

« Trial operation switch on theLossnay circuit board (SW 2-1 orSW 2-3) is set to ON board.

« Check the test operation switch.

LC 4000

SLC 4000

2blinks

— Fan motoroperationdevice error

« Lossnay fan will not stop. « Replace the table.

LC 3602

SLC 3602

3blinks

— Damperrelatederror

« Damper board operation is not cor-rect.

« Connectors for the damper unit arenot correctly connected.

« Remove the load and check ormove the damper board by hand.

« Check the connection of the lead wire’sconnectors and the circuit connector.

LC 5101

SLC 5101

4blinks

— OA thermis-tor relatederror

« Connectors for the thermistor arenot correctly connected.

« Check the connection of the leadwires connectors and the circuitconnector.

LC 5102

SLC 5102

5blinks

— RA thermis-tor relatederror

« Connectors for the thermistor arenot correctly connected.

« Check the connection of the leadwires connectors and the circuitconnector.

—26—

Page 27: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Error code*1

LED1(green)

LED 2(red)

———

*2

8blinks

— Pre-heaterror

« In order that the OA temperaturemight not rise up, intermittent opera-tion started.

« After turnig ON the pre-heat output(X8), when the OA temperaturebecomes larger than 15˚C within15 minutes.

« SW5-6 ON without preheatinginstallation

« Check whether the heater power issupplied. Check whether the wiringis correct. If not above-mentioned,the heater capacity is too small. Theheater capacity needs to be lookedagain.

« Since the heater capacity is too large,the OA temperature rises up toomuch. The heater capacity needs tobe looked again.

« Turn SW5-6 OFF, when no preheat-ing installation.

——— 9blinks

— Remotecontrollercommuni-cationerror

« Multiple transmission cables havebeen wired using multi core wires.

« Transmission cable and power sup-ply cable are too close.

« Transmission cable is not securelyconnected.

« The length of wiring of the transmis-sion cable is longer than specifica-tion (longer than 500 m).

« Wire the transmission cable awayfrom the other transmission cable.

« Wire the transmission cable at least 5cm away from the power supply cable.

« Check the transmission cable con-nection.

« Check the length of the transmissioncable wiring.

“Filter” blink-ing

— — Warning to clean airfilter by comulativeoperation time

« Interval for cleaning Lossnay air fil-ter has elapsed.

« After cleaning the air filter press the“Filter” button on the remote con-troller 2 times.

“HO” blinking blink-ing

— System isstarting

« LED1 blinks at 1 second intervals duringstarting operation (maximum of 45 seconds.)

« There is no error.

Symptom Cause Corrective action

*1 LC: Lossnay set to Main SLC: Lossnay set to Sub RC, SRC: remote controller (PZ-41SLB-E)*2 The errror message is NOT displayed for the PZ-41SLB-E Lossnay remote controller.

—27—

2Checklist of error codes displayed on the PZ-52SF-E, M-NET controllers, and LED displays(Table2-2)

Error code*1

LED1(green)

LED 2(red)

Symptom Cause Corrective action

6600 — 6blinks

Multipleaddress error

« There is another unit with the sameaddress setting.

« Check the addresses of devices inthe system.

6607

6608

— 8blinks

No ACK error

No answererror (M-NET com-municationerror)

« Power supply to Lossnay is not turned on.

« Lossnay address was changed.

« Multiple transmission cables havebeen wired using multi core wires.

« Transmission cable is not securelyconnected.

« The length of wiring of the transmissioncable is longer than specifications (longerthan maximum 200 m from the power sup-ply unit, longer than 500 m between ends).

« Check the power to the Lossnay.

« Check the Lossnay address.

« Wire the transmission cable awayfrom the other transmission cable.

« Check the transmission cable con-nection.

« Check the length of the transmissioncable wiring.

0900 — — Lossnaytrial opera-tion

« Trial operation switch on theLossnay circuit board (SW 2-1 orSW 2-3) is set to ON.

« Check the trial operation switch.

4116 2blinks

— Fan motoroperationdevice error

« Lossnay fan will not stop. « Replace the table.

3602 3blinks

— Damperrelatederror

« Damper board operation is not cor-rect.

« Connectors for the damper unit arenot correctly connected.

« Remove the load and check ormove the damper board by hand.

« Check the connection of the lead wiresconnectors and the circuit connector.

Page 28: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

5101 4blinks

— OA thermis-tor relatederror

« Connectors for the thermistor arenot correctly connected.

« Check the connection of the leadwires connectors and the circuitconnector.

5102 5blinks

— RA thermis-tor relatederror

« Connectors for the thermistor arenot correctly connected.

« Check the connection of the leadwires connectors and the circuitconnector.

3126 8blinks

— Pre-heaterror

« In order that the OA temperaturemight not rise up, intermittent opera-tion started.

« After turnig ON the pre-heat output(X8), when the temprature becomelarger than 15˚C within 15 min-utes.

« SW5-6 ON without preheatinginstallation

« Check whether the heater power issupplied. Check whether the wiringis correct. If not above-mentioned,the heater capacity is too small. Theheater capacity needs too be lookedagain.

« Since the heater capacity is too large,the OA temperature rises up toomuch. The heater capacity needs tobe looked again.

« Turn SW5-6 OFF, when no preheat-ing installation.

6602

6603

6604

— 1 - 5blinks

Communication cir-cuit sectionerror

« Error with transmission cable.

« Controller where error originallyoccurred is defective.

« Lossnay board is defective.

« Check transmission cable relations.

« Check the controller where the erroroccurred.

« Replace the circuit board.

——— — Lit No M-NETconnectioninformation

« Lossnay does not have Group set-ting (registration) made.

« Check the Lossnay address andconfirm that the group setting ismade.

Filter blinking — — Warning to clean airfilter by comulativeoperation time

« Interval for cleaning Lossnay air fil-ter has elapsed.

« After cleaning the air filter press the“Filter” button on the remote con-troller 2 times.

——— Lit — In delayedstart oper-ation

« Delayed start operation is set at thefunction select switch (SW 5-1) onthe Lossnay circuit board.

« There is no error.

——— LED6 (red)

off

No powerto M-NETtransmis-sion cable

« Power supply is not supplied to theM-NET transmission cable.

« Wiring length of the transmissioncable is from the power supply unitor the outdoor unit is longer thanspecification (maximum extension200 m).

« Check the connection of the powersupply unit, outdoor unit and trans-mission cable.

« Check the length of the transmissioncable wiring.

Error code*1

LED1(green)

LED 2(red)

Symptom Cause Corrective action

*1 The letters “LC” that display with the error code show a Lossnay unit type, and the number in the third column shows theaddress.

—28—

Page 29: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

(3)Trouble Mode 3: The remote controller does not operate or operates irregularly.1Checklist for when using the PZ-41SLB-E (Table 3-1)

1

No.

Nothing displays on theLCD.

« Transmission cable is connected to the wrongterminal

« No Lossnay is set to “Main.”

« Power supply to the Lossnay is not turned on.

« Lossnay is connected to a power supply with arating outside specification.

« Transmission cable is not securely connected.

« The length of wiring of the transmission cable islonger than specification (longer than 500 m).

« Check the transmission cableconnection (connected to TM4on the Lossnay board).

« Turn off the main power supplyand set the Main/Sub switch(SW1) (first unit to main, secondand following units to sub).

« Check the power supply to the Lossnay.

« Check the power supply.

« Check the transmission cableconnection.

« Check the length of the trans-mission cable wiring.

2 Starts or stops, or thedisplay changes, byitself.

« Multiple transmission cables have been wiredusing multi core wires.

« Transmission cable and power supply cableare too close.

« Wire the transmission cable away fromthe other transmission cable.

« Wire the transmission cable at least 5cm away from the power supply cable.

3 Displays a error codethat is not in the checklist.

« Letters on the remote controller LCD are dim.

« The release of the Delay Start button or theFilter Reset button is not good.

« Replace the remote control.

« Replace the remote control.

4 Cannot stop the Lossnaywith the remote controller(display shows “Interlocked”).

« External priority ON/OFF setting is made. « Check the interlocked operationmode setting.

5 Cannot switch fan speedwith the remote con-troller.

« High/Low change input (CN16) is ON.

« The function select switch (SW2-4.5) on theLossnay circuit has the fixed high or fixed lowspeed set.

« Check the High/Low changeinput (CN16).

« Check the function select switch(SW 2-4.5)

6 Lossnay operates whenthe main power supplyturns on and the remotecontroller displays.

« Main power supply was cut during Lossnayoperation.

« Stop the Lossnay with theremote controller, then wait atleast 10 second and turn off themain power supply .

Symptom Cause Corrective action

—29—

2Checklist for when using PZ-52SF-E (Table 3-2)

1

No.

Nothing displays on theLCD.

« Transmission cable is connected to the wrongterminal

« There is no power supply unit (for Lossnayonly systems).

« The power supply unit is not turned on.

« Transmission cable is not securely connected.

« Wiring length of the transmission cable is fromthe power supply unit or the outdoor unit islonger than specifications (maximum extension200 m).

« Check the transmission cableconnection (connected to A , Bof terminal unit TB5 on theLossnay board).

« Install the power supply unit.

« Check the power to the powersupply unit.

« Check the transmission cableconnection.

« Check the length of the trans-mission cable wiring.

Symptom Cause Corrective action

Page 30: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

« After supplying power to the sys-tem, HO blinks for a maximum ofabout 10 minutes. (This is not an error.)

« Make the group setting (registra-tion). If using a system with a sys-tem controller, register at the sys-tem controller. If there is only theLossnay remote controller, registerat the remote controller.

« Check the group setting at theMELANS.

« Check the power supply to theLossnay.

« Check the power supply.

« Check the transmission cableconnection (connected to A , Bof terminal unit TB5 on theLossnay board).

« Check the Lossnay address.

« If the board has been replaced,reset the group settings.

« Check the length of the trans-mission cable wiring.

2

No.

Displays “HO” and doesnot start.

« It is less than 10 minutes since the power wassupplied to the system.

« Group setting (registration) has not beenmade.

« Remote control address has not been registeredin the group setting by the system controller.

« Power supply to the Lossnay is not turned on.

« Lossnay is connected to a power supply with arating outside specification.

« Lossnay transmission cable connection termi-nal is wrong.

« Lossnay address was changed.

« Lossnay board was changed.

« The length of wiring of the transmission cable is longerthan specifications (longer than maximum 200 m fromthe power supply unit, longer than 500 m between ends).

3 Cannot register theLossnay from the remotecontroller or the con-troller.

« Power supply to the Lossnay is not turned on.

« Lossnay is connected to a power supply with arating outside specification.

« Transmission cable to the Lossnay is not con-nected.

« Lossnay transmission cable connection termi-nal is wrong.

« Lossnay address is wrong.

« The length of wiring of the transmission cable is longerthan specifications (longer than maximum 200 m fromthe power supply unit, longer than 500 m between ends).

« Check the power supply to theLossnay.

« Check the power supply.

« Check the transmission cableconnection.

« Check the transmission cableconnection (connected to A , Bof terminal unit TB5 on theLossnay table).

« Check the Lossnay address.

« Check the length of the trans-mission cable wiring.

4 Starts or stops, or the dis-play changes, by itself.

« Set for interlocked operation with City Multi. « Cancel interlocked operation set-ting.

5 Displays a error code thatis not in the checklist.

« Letters on the remote controller LCD are dim. « Replace the remote controller.

6 Cannot stop the Lossnaywith the remote controller(display shows “Central”).

« “Cancel Operation” setting is made from theMELANS.

« External priority ON/OFF setting is made.

« Remote/nearby switch input (CN32) is set to“Remote.”

« Check the settings of theMELANS.

« Check the interlocked operationmode setting.

« Check the remote/nearbychange input (CN32).

Symptom Cause Corrective action

—30—

Page 31: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

(4)Trouble Mode 4: The Lossnay does not operate or operates irregularly.1Lossnay checklist (Table 4).

1

No.

The fan does not operate.

The fan does not operatenormally.

« Connectors for the fan connection or connec-tors for the control circuit section connectionare not secure.

« Power supply is not supplied to the Lossnay, orpower outside specifications is connected.

« Lossnay group setting is not made by using theM-NET. (LED2 lights)

« Check the lead wire connectorsand the control circuit sectionconnectors.

« Check the power supply.

« Check the Lossnay address andthe group setting (LED2 lightswhen not using M-NET. This isno error.)

3 Fan will not stop. « The trial operation switch (SW 2-1) is ON. « Check the test operation switch (SW2-1).

2 Interlocked operationwith external device (air conditioner) does notoccur.

« The type of external signal does not match theconnected terminal unit (charged, uncharged,Mr. Slim signal).

« The type of external signal does not match thepulse input switch (SW2-2) setting (level sig-nal, pulse signal).

« The external device signal is not being input.

« The external device and signal cable wiring islonger than specifications

(12V DC, 24V DC: Longer than limitationsof external device

Uncharged a-contact: Longer than 500 mMr. Slim signal: Longer than 500 m)

« The Delayed Start mode is set at the remotecontroller (PZ-41SLB-E) or the function selectswitch (SW 5-1) on the Lossnay circuit board.

« The ON Interlocked Operation mode or OFFInterlocked Operation mode is set at theremote controller (PZ-41SLB-E) or the functionselect switch (SW 5-7,8) on the Lossnay circuitboard.

« When using multiple Lossnay units, the exter-nal control input signal is connected to a unitwith the “Sub” setting made.

« In a group of multiple Lossnay units with the M-NET, the external control input signal is con-nected to a Lossnay unit other than the onewith the smallest address.

« There is a communication error with theremote controller or controller.

« Check the external signal type and theexternal control input terminal (TM2)connection.

« Check the external signal type andthe pulse input switch (SW2-2)setting.

« Check the external device.

« Check the wiring length of thesignal cable.

« Check the delayed start settings ofthe remote controller (PZ41SLB-E)and the function select switch(SW5-1).

« Check the interlocked operation modesettings of the remote controller(PZ41SLB-E) and the functionselect switch (SW5-7, 8)

« Connect the external controlinput signal to the Lossnay set to“Main.”

« Connect the external controlinput signal to the Lossnay in thegroup with the lowest address.

« Check the remote controller orcontroller.

Symptom Cause Corrective action

—31—

4 Lossnay operates whenmain power is turned on.

« The PZ-41SLB-E is being used.

« By using the M-NET, the power supply ON/OFFsetting is set to ON at the function select switch(SW 2-6) on the Lossnay circuit board.

« By using the M-NET, the automatic recoveryfollowing power supply interruption (refer topage 61) setting is made at the function selectswitch (SW 5-4) on the Lossnay circuit board.

« When the main power supply isturned off while the Lossnay isoperating from the remote con-troller, the Lossnay will resumeoperation when the main power isturned back on (this is no error).

« Check the power supply ON/OFFsetting of the function selectswitch (SW2-6).

« Check the automatic recovery fol-lowing power supply interruptionsetting of the function selectswitch (SW5-4).

Page 32: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

5

No.

Supply air fan periodical-ly stops operating.

« When the outdoor air temperature is -10°C orless, operation stops after a fixed period ofabout 10 minutes to keep the Lossnay Corefrom freezing. (Cold weather area spec)

« When connected to a Mr. Slim or a City Multiby a duct, operation stops when the air condi-tioner is defrosting.

« This is no error.

« This is no error.

6 Takes in air from out-doors during interlockedoperation with a Mr. Slimor a City Multi, but supplyair fan doesn’t stop oper-ating when defrosting.

« The indoor unit’s outside air intake selection isinvalid.

« Set the outdoor air intake selec-tion of a indoor unit to “ON.”

7 The supply air fan andexhaust fan both periodi-cally stop operating.

« When connected to Mr. Slim or City Multi by aduct and the function select switch (SW 5-3)on the Lossnay circuit board is ON, operationstops when the air conditioner is defrosting.

« Check the function select switch(SW5-3).

8 Fan speed will notchange.

« The High/Low switching extermary input(CN16) is set to ON.

« The function select switch (SW2-4.5) on the Lossnay cir-cuit board is set to the high fixed or low fixed fan speed.

« The trial operation switch (SW2-1) is turnedON.

« Check the High/Low changeinput (CN16).

« Check the function select switch(SW2-4,5).

« Check the trial operation switch(SW2-1).

9 Damper board does notoperate.

« The outside air temperature is less than 8°C.

« The damper board operation is defective.

« The thermistor related connectors are notsecurely connected.

« The damper related connectors are notsecurely connected.

« The trial operation switch (SW2-1 or SW2-3) isturned ON.

« When using the remote controller to changeventilation mode, there may be a delayed startof up to 30 seconds depending on the timing.

« Check the outdoor air temperature.

« Remove the load and check ormove the damper board by hand.

« Check the connections of thelead wire connectors and the cir-cuit connectors.

« Check the connections of thelead wire connectors and thecontrol circuit connectors.

« Check the trial operation switch(SW2-1 or SW2-3).

« This is no error.

10 Operation monitor outputis late with regard to exter-nal control input ON/OFF.

« When using the PZ-41SLB-E there is a maxi-mum delay of 7 seconds, or without usingthere is a maximum delay of 3 seconds.

« This is no error.

11 Operation monitor outputis OFF during operation.

« When the function select switch (SW 5-2) onthe Lossnay circuit board is ON, for operationmonitor output for interlocked operation withthe supply air fan, it turns OFF when the out-side air is -10°C or less or when the air condi-tioner is defrosting.

« Check the function select switch(SW5-2)

12 Delayed start operationdoes not work whenDelayed start is set.

« When using the PZ-41SLB-E, the circuit func-tion select switch is set for delayed start.

« Set delayed start at the remote con-troller (the circuit board switch is not ineffect when using the PZ-41SLB-E).

13 Lossnay does not operate whenpower is on even when thepower on/off setting is made.

« Using the PZ-41SLB-E. « The power supply ON/OFF set-ting is not in effect when usingPZ-41SLB-E.

14 Interlocked operation isdifferent from the set-tings.

« When using the PZ-41SLB-E, the circuit func-tion select switch is set for interlocked opera-tion.

« Set interlocked operation at theremote controller (the circuitboard switch is not in effect whenusing the PZ-41SLB-E).

Symptom Cause Corrective action

—32—

Page 33: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

2Temperature vs. themistor resistance table

Temperature(°C)

Resistancevalue (kΩ)

Temperature(°C)

Resistancevalue (kΩ)

Temperature(°C)

Resistancevalue (kΩ)

Temperature(°C)

Resistancevalue (kΩ)

Temperature(°C)

Resistancevalue (kΩ)

-40 88.85 - ∞ -7 17.92 8 9.57 23 5.38 38 3.17

. . .

. . .

. . .

. . .

-6 17.16 9 9.20 24 5.19 39 3.06

-20 32.43 -5 16.43 10 8.84 25 5.00 40 2.96

-19 30.92 -4 15.74 11 8.49 26 4.82 41 2.86

-18 29.50 -3 15.08 12 8.17 27 4.65 42 2.77

-17 28.14 -2 14.45 13 7.85 28 4.49 43 2.68

-16 26.87 -1 13.86 14 7.55 29 4.33 44 2.59

-15 25.65 0 13.29 15 7.27 30 4.18 45 2.51

-14 24.51 1 12.74 16 6.99 31 4.03 46 2.43

-13 23.42 2 12.22 17 6.73 32 3.89 47 2.35

-12 22.39 3 11.72 18 6.48 33 3.76 48 2.28

-11 21.41 4 11.25 19 6.24 34 3.63 49 2.21

-10 20.48 5 10.80 20 6.01 35 3.51 50 2.14

-9 19.58 6 10.37 21 5.79 36 3.39

-8 18.73 7 9.96 22 5.58 37 3.28 87.5 - 0.72 - 0

—33—

Page 34: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—34—

LED1 (green)• When blinking, there is an error with the Lossnay unit (number of blinks indicates the type of error).• Blinks at 1 second intervals when starting.• Lit during delayed start, normally off at other times.

LED2 (red)• Blinking indicates M-NET communication error (number of blinks indicated the type of error).• Lit when not connected to other M-NET units (registered).

Exhaust fan operation unit (combined)

Fuse (6.3 A/250 V)

Supply fan operation unit (combined)

Power supply220 V to 240 V AC: up to 50 Hz220 V AC: up to 60 Hz(60 Hz is not used in EU)

Transformer input

Damper motoroperation unit220 V - 240 V AC

5 V DC12 V DC

Transformer output11 V to 20 V AC

GND

LED4 (red)• lit when power is supplied to circuit

Thermistor (outdoor air)Thermistor (return air)

Damper positiondetector• during Lossnay

ventilation: 12 V DC• during by-passventilation: 0 V

M-NET transmission cable (shielded)

M-NET transmission cable (PZ-52SF-E, MELANS, power supply unitor City Multi)

For external device connection

During operation: 0ΩWhen stopped: OPEN

During error/pre-heat: 0ΩNormal: OPEN

Remote control switch (PZ-41SLB-E) andLossnay spanning transmission cable

9 V to 15 V DC

Exhaust fan operation unit220 V to 240 V AC: up to 50 Hz220 V AC: up to 60 Hz

Supply fan operation unit220 V to 240 V AC: up to 50 Hz220 V AC: up to 60 Hz

Extrahigh

High Low

Extrahigh

High Low

4-3 Circuit Test Point

In the case of LGH-150RX4-E and LGH-200RX4-E, CN6 isunconnected.

Page 35: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

5. Overhaul procedures5-1 Blower Parts1Remove the cover fixing screw.2Pull back the hinged clip.2Open the door and lift off of the hinge brackets.

3Remove Filters from the unit.4Remove Cores from the unit.

LGH-15RX4-E~LGH-100RX4-EHinge Maintenance Cover

LGH-15RX4-E~LGH-100RX4-ECore

Screw Screw

Filter Filter

LGH-150RX4-E,LGH-200RX4-EHinge Maintenance Cover

LGH-150RX4-E,LGH-200RX4-ECore

—35—

Page 36: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

5Remove screw from the core-guide,Remove core-guide.

6Remove separator from the blower portion.

7Remove screws from the motor base.

—36—

Core Guide

Separator

Motor Base Motor

Pre-assembled Blower

8Remove the pre-assembled blower.

Page 37: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—37—

5-2 Damper Movement Motor Part (All units available)1Remove (2) screws out from the damper motor cover.

2Take the damper movement motor out of the cover.

Damper Motor Cover

Damper Movement Motor

Control Cover

1Remove (3) screws from the control cover and openthe control cover.

5-3 Circuit Board Part(1)LGH-15RX4-E~LGH-100RX4-E

Page 38: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

2Remove (2) screws from capacitors.

3Remove all harnesses connected to the circuit board.

—38—

Capacitors

Circuit Board

4Take the circiuit board out.

Page 39: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

1Remove (2) screws from the control cover and open thecontrol cover.

(2)LGH-150RX4-E,LGH-200RX4-E

—39—

2Remove all harnesses connected to the circuit board.3Take the circuit board out.

Page 40: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—40—

6. Parts list

Please note the following when using the parts list.

1. When ordering parts, always indicate the part number, part name, and number of partsrequired.

2. Parts are not always available, and it may take time for you to receive them.3. There may be specification improvements or prices changes.4. Specifications and prices are as of March 2006.5. Parts marked are critical for safety. To maintain safety and performance, always

replace these parts with the parts prescribed.6. The numbers that are circled in the exploded view are the same as the reference

number for the part being indicated.

Description of screw abbreviations

Screw 4 × 16

Abbreviation

PC screwPRC screwPP screwSW · PP screwPPT screwPCT screwPTT screwPT screwSET screwSQ · SET screwP · SET screwPMT screwHS · SET screwP · R · W screwP · C · W screwP · R · C · W screwR · W screwPW · PP screwSW-PW · PP screw

Description

Cross recess flat head machine screwCross recess oval head machine screwCross recess pan head machine screwCross recess pan head screw with spring washerCross recess tapping screwCross recess flat head tapping screwCross recess truss head tapping screwCross recess truss head machine screwSlotted head stop screwSquare head stop screwPan head stop screwPrimer truss head screwHexagon head stop screwCross recess round wood screwCross recess flat head wood screwCross recess round and flat wood screwSlotted round wood screwCross recess pan head screw with small washerCross recess pan head machine screw with spring washer and flat washer

Screw diameter Length

Page 41: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

1

1 2 3 4

5 6 7 8 9 10 11 12 13 14 15 16 17

1

1

17

2

3

7

3

3

—41—

Model LGH-15RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

1. H00 000 487 PTT screw 4×8 182. K82 163 617 Flange 23. R50 476 380 Hanger 44. H00 189 007 PTT screw 5×10 45. Y50 075 707 Maintenance cover 16. R50 395 381 Core guide 17. Y50 061 717 Filter 28. R50 476 710 Lossnay core 19. R50 476 381 Core guide 110. R50 384 712 Cover 211. R50 466 344 Hinge 112. M34 074 017 Special screw 4×11 113. Y50 029 712 Fix plate 114. Y50 061 704 Hanger cover 415. R50 483 704 Lead support 116. R50 361 717 Sound absorbing material 1 SA17. R50 384 617 Flange 2

Q'typcs/unit

Page 42: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

31 32 33 34 35 36 37 38 39

3638

38

31

33

38

32

34

36

38

3536

39

38

37

—42—

Model LGH-15RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

31. R50 331 067 Special nut 232. M34 398 077 Tab washer 233. R50 354 480 Centrifugal fan 2 φ18034. R50 028 465 Special washer 235. Y50 116 451 Motor 236. H00 312 007 PTT screw 4×6 2237. R50 214 708 Motor plate 438. H00 000 332 PTT screw 4×10 1239. Y50 029 708 Motor base 2

Q'typcs/unit

Page 43: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-15RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

51. Y50 061 693 Damper motor cover 152. R50 213 715 Damper support 153. M31 234 089 Special bush 254. R50 095 156 Pull spring 155. R50 213 713 Damper 156. Y50 061 260 Damper motor 1 220-240V57. R50 054 225 Bush 258. R50 228 150 Rod 159. Y50 061 706 Control cover 160. K83 170 228 Cord band 161. M45 017 228 Cord band 162. Y50 047 216 Transformer 1 230VAC63. Y50 116 235 Capacitor 2 1.5μF・440VAC64. H00 011 008 PT screw 4×8(BS) 265. H00 013 076 Lock washer 366. Y50 116 706 Earth fix plate 167. H00 154 005 PPT screw 4×12 268. K81 432 236 Terminal block 1 3P ML-2069. Y50 108 226 Insulation plate 170. Y50 116 707 Circuit fix plate 171. Y50 116 368 Wiring diagram 172. H00 000 003 PP screw 4×8 273. Y50 116 171 Circuit board 1 LG-X02-E74. X40 139 095 Spacer 475. R50 477 167 Thermistor 176. D42 019 095 Spacer 477. M35 164 224 Cord clip 178. K82 163 225 Cord bush 279. K83 223 225 Bush 1

43

Q'typcs/unit

Page 44: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

59 60 61 62 63 64 65 66 67

1

68 69 70

1

65

1

71 72 73 74 75 76 77 78 79

51 52 53 54 55

56 57 58

57

36

36

1

—44—

Page 45: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-25RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

1. H00 000 487 PTT screw 4×8 182. R50 323 609 Flange 23. R50 476 380 Hanger 44. H00 189 007 PTT screw 5×10 45. Y50 075 707 Maintenance cover 16. R50 395 382 Core guide 17. Y50 061 718 Filter 28. R50 476 711 Lossnay core 29. R50 476 382 Core guide 110. R50 476 708 Cover 211. R50 466 344 Hinge 112. M34 074 017 Special screw 4×11 113. Y50 029 712 Fix plate 114. Y50 061 704 Hanger cover 415. R50 483 704 Lead support 116. R50 354 718 Sound absorbing material 1 SA17. Y50 075 609 Flange 2

Q'typcs/unit

1

1 2 3 4

5 6 7 8 9 10 11 12 13 14

1

1

17

2

3

7

3

3

15 16 17—45—

Page 46: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

31 32 33 34 35 36 37 38 39

3638

38

31

33

38

32

34

36

38

3536

39

38

37

—46—

Model LGH-25RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

31. R50 331 067 Special nut 232. M34 398 077 Tab washer 233. R50 354 480 Centrifugal fan 2 φ18034. R50 028 465 Special washer 235. Y50 117 451 Motor 236. H00 312 007 PTT screw 4×6 2237. R50 214 708 Motor plate 438. H00 000 332 PTT screw 4×10 1239. Y50 030 707 Motor base 2

Q'typcs/unit

Page 47: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-25RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

51. Y50 061 693 Damper motor cover 152. R50 213 715 Damper support 153. M31 234 089 Special bush 254. R50 095 156 Pull spring 155. R50 213 713 Damper 156. Y50 061 260 Damper motor 1 220-240V57. R50 054 225 Bush 258. R50 230 150 Rod 159. Y50 061 706 Control cover 160. K83 170 228 Cord band 161. M45 017 228 Cord band 162. Y50 047 216 Transformer 1 230VAC63. Y50 116 235 Capacitor 2 1.5μF・440VAC64. H00 011 008 PT screw 4×8(BS) 265. H00 013 076 Lock washer 366. Y50 116 706 Earth fix plate 167. H00 154 005 PPT screw 4×12 268. K81 432 236 Terminal block 1 3P ML-2069. Y50 108 226 Insulation plate 170. Y50 116 707 Circuit fix plate 171. Y50 116 368 Wiring diagram 172. H00 000 003 PP screw 4×8 273. Y50 116 171 Circuit board 1 LG-X02-E74. X40 139 095 Spacer 475. R50 477 167 Thermistor 176. D42 019 095 Spacer 477. M35 164 224 Cord clip 178. K82 163 225 Cord bush 279. K83 223 225 Bush 1

47

Q'typcs/unit

Page 48: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

59 60 61 62 63 64 65 66 67

1

68 69 70

1

65

1

71 72 73 74 75 76 77 78 79

51 52 53 54 55

56 57 58

57

36

36

1

—48—

Page 49: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

14

1 2 3 4 5

6 7 8 9 10 11 12 13 14 15 1716

42

14

5

5

8

5

14

14

14 1

2 4

14

17

2

4

3

—49—

Model LGH-35RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

1. R50 323 609 Flange 22. R50 476 380 Hanger 43. H00 189 007 PTT screw 5×10 44. R50 483 705 Hanger support 45. Y50 061 704 Hanger cover 46. X50 002 707 Maintenance cover 17. R50 396 381 Core guide 18. Y50 062 717 Filter 29. R50 478 710 Lossnay core 210. R50 478 381 Core guide 111. R50 476 708 Cover 212. R50 466 344 Hinge 113. M34 074 017 Special screw 4×11 114. H00 000 487 PTT screw 4×8 2015. Y50 029 712 Fix plate 116. R50 483 704 Lead support 117. Y50 075 609 Flange 2

Q'typcs/unit

Page 50: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

31 32 33 34 35 36 37 38

38

31

33

38

32

34

36

38

35

37

—50—

Model LGH-35RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

31. R50 331 067 Special nut 232. M34 398 077 Tab washer 233. R50 351 480 Centrifugal fan 2 φ22034. R50 478 707 Motor base 235. M34 706 465 Special washer 236. Y50 062 451 Motor 237. R50 351 713 Motor fix plate 238. H00 189 007 PTT screw 5x10 16

Q'typcs/unit

Page 51: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-35RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

51. Y50 061 693 Damper motor cover 152. H00 312 007 PTT screw 4×6 2353. R50 069 156 Pull spring 154. R50 472 716 Damper support 155. M31 234 089 Special bush 256. R50 472 715 Damper 157. Y50 061 260 Damper motor 1 220-240V58. R50 054 225 Bush 259. R50 231 150 Rod 160. Y50 061 706 Control cover 161. K83 170 228 Cord band 162. M45 017 228 Cord band 163. Y50 047 216 Transformer 1 230VAC64. Y50 088 235 Capacitor 2 2.5μF・440VAC65. H00 011 008 PT screw 4×8(BS) 266. H00 013 076 Lock washer 367. Y50 116 706 Earth fix plate 168. H00 154 005 PPT screw 4×12 269. K81 432 236 Terminal block 1 3P ML-2070. Y50 108 226 Insulation plate 171. Y50 116 707 Circuit fix plate 172. Y50 116 368 Wiring diagram 173. H00 000 003 PP screw 4×8 274. Y50 116 171 Circuit board 1 LG-X02-E75. X40 139 095 Spacer 476. R50 477 167 Thermistor 177. D42 019 095 Spacer 478. M35 164 224 Cord clip 179. K82 163 225 Cord bush 280. K83 223 225 Bush 1

51

Q'typcs/unit

Page 52: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

60 61 62 63 64 65 66 67 68

14

69 70 71

14

66

14

72 73 74 75 76 77 78 79 80

51 52 54 55 56

57 58 59

58

52

53

—52—

Page 53: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

1716

1714

1 2 3 4 5

6 7 8 9 10 11 12 13 14 15

42

14

5

5

8

5

14

14

14 1

2 4

14

2

4

3

—53—

Model LGH-50RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

1. R50 028 610 Flange 22. R50 476 380 Hanger 43. H00 189 007 PTT screw 5×10 44. R50 483 705 Hanger support 45. Y50 061 704 Hanger cover 46. X50 002 707 Maintenance cover 17. R50 216 381 Core guide 18. Y50 062 718 Filter 29. R50 478 711 Lossnay core 210. R50 478 382 Core guide 111. R50 351 708 Cover 212. R50 466 344 Hinge 113. M34 074 017 Special screw 4×11 114. H00 000 487 PTT screw 4×8 2015. Y50 029 712 Fix plate 116. R50 483 704 Lead support 117. R50 429 609 Flange 2

Q'typcs/unit

Page 54: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

31 32 33 34 35 36 37 38

38

31

33

38

32

34

36

38

35

37

—54—

Model LGH-50RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

31. R50 331 067 Special nut 232. M34 398 077 Tab washer 233. R50 351 480 Centrifugal fan 2 φ22034. R50 478 707 Motor base 235. M34 706 465 Special washer 236. Y50 062 452 Motor 237. R50 351 713 Motor fix plate 238. H00 189 007 PTT screw 5×10 16

Q'typcs/unit

Page 55: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-50RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

51. Y50 061 693 Damper motor cover 152. H00 312 007 PTT screw 4×6 2353. R50 069 156 Pull spring 154. R50 472 716 Damper support 155. M31 234 089 Special bush 256. R50 472 715 Damper 157. Y50 061 260 Damper motor 1 220-240V58. R50 054 225 Bush 259. R50 232 150 Rod 160. Y50 061 706 Control cover 161. K83 170 228 Cord band 162. M45 017 228 Cord band 163. Y50 047 216 Transformer 1 230VAC64. Y50 091 235 Capacitor 2 4μF・440VAC65. H00 011 008 PT screw 4×8(BS) 266. H00 013 076 Lock washer 367. Y50 116 706 Earth fix plate 168. H00 154 005 PPT screw 4×12 269. K81 432 236 Terminal block 1 3P ML-2070. Y50 108 226 Insulation plate 171. Y50 116 707 Circuit fix plate 172. Y50 116 368 Wiring diagram 173. H00 000 003 PP screw 4×8 274. Y50 116 171 Circuit board 1 LG-X02-E75. X40 139 095 Spacer 476. R50 477 167 Thermistor 177. D42 019 095 Spacer 478. M35 164 224 Cord clip 179. K82 163 225 Cord bush 280. K83 223 225 Bush 1

55

Q'typcs/unit

Page 56: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

60 61 62 63 64 65 66 67 68

14

69 70 71

14

66

14

72 73 74 75 76 77 78 79 80

51 52 54 55 56

57 58 59

58

52

53

—56—

Page 57: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

1716

17

1 2 3 4 5

6 7 8 9 10 11 12 13 14 15

2

5

5

8

5

1

2 3

3

2

3

2

2

2

—57—

Model LGH-65RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

1. R50 028 610 Flange 22. H00 000 487 PTT screw 4×8 183. R50 479 380 Hanger 44. H00 189 007 PTT screw 5×10 45. R50 479 704 Hanger cover 46. R50 217 708 Maintenance cover 17. R50 217 381 Core guide 18. Y50 120 717 Filter 29. R50 479 710 Lossnay core 210. R50 479 381 Core guige 111. R50 351 708 Cover 212. R50 466 344 Hinge 113. M34 074 017 Special screw 4×11 114. Y50 029 712 Fix plate 115. R50 483 704 Lead support 216. R50 357 717 Sound absorbing material 1 SA17. R50 429 609 Flange 2

Q'typcs/unit

Page 58: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

31 32 33 34 35 36 3837

40

31

33

39

32

34

3637

3538

39 40 41 42 43

41

4243

—58—

Model LGH-65RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

31. R50 218 067 Special nut(12) 232. K83 466 113 Washer(12) 233. R50 479 480 Centrifugal fan 2 φ24534. R50 357 707 Fan base 235. Y50 033 104 Key 2 5×5×11.536. R50 217 711 Inlet ring 237. H00 189 007 PTT screw 5×10 1638. Y50 120 451 Motor 239. R50 263 712 Motor fix leg 440. R50 217 225 Bush 841. D40 135 095 Spacer 842. M34 043 080 Special washer 843. H00 000 606 PT screw 5×14 8

Q'typcs/unit

Page 59: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-65RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

51. Y50 061 693 Damper motor cover 152. R50 099 156 Pull spring 153. R50 472 716 Damper support 154. M31 234 089 Special bush 255. R50 472 715 Damper 156. Y50 061 260 Damper motor 1 220-240V57. H00 312 007 PTT screw 4×6 258. R50 054 225 Bush 259. R50 233 150 Rod 160. Y50 061 706 Control cover 161. K83 170 228 Cord band 162. M45 017 228 Cord band 163. Y50 047 216 Transformer 1 230VAC64. Y50 120 235 Capacitor 2 5μF・440VAC65. H00 011 008 PT screw 4×8(BS) 266. H00 013 076 Lock washer 367. Y50 116 706 Earth fix plate 168. H00 154 005 PPT screw 4×12 269. K81 432 236 Terminal block 1 3P ML-2070. Y50 108 226 Insulation plate 171. Y50 116 707 Circuit fix plate 172. Y50 116 368 Wiring diagram 173. H00 000 003 PP screw 4×8 274. Y50 116 171 Circuit board 1 LG-X02-E75. X40 139 095 Spacer 476. R50 477 167 Thermistor 177. D42 019 095 Spacer 478. M35 164 224 Cord clip 179. K82 163 225 Cord bush 280. K83 223 225 Bush 1

59

Q'typcs/unit

Page 60: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

60 61 62 63 64 65 66 67 68

14

69 70 71

14

66

14

72 73 74 75 76 77 78 79 80

51 53 54 55

56 58 59

58

52

57

2

—60—

Page 61: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

15 16 17

17

1 2 3 4 5

6 7 8 9 10 11 12 13 14

4

8

2

44

3

3

3

14

—61—

Model LGH-80RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

1. H00 000 488 PTT screw 4×12 102. R50 430 609 Flange 23. H00 000 487 PTT screw 4×8 184. R50 095 380 Hanger 45. H00 000 244 PT screw 6×12 166. X50 004 707 Maintenance cover 17. R50 218 381 Core guide 18. Y50 063 717 Filter 29. R50 480 710 Lossnay core 210. R50 480 381 Core guide 111. R50 358 704 Cover 212. R50 466 344 Hinge 113. M34 074 017 Special screw 4×11 114. Y50 029 712 Fix plate 215. R50 483 704 Lead support 216. Y50 126 718 Sound absorbing material 117. Y50 021 609 Flange 2

Q'typcs/unit

Page 62: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

31 32 33 34 35 36 3837

40

31

33

39

32

34

3638

35

37

39 40 41 42 43

4142

43

44

44

—62—

Model LGH-80RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

31. R50 218 067 Special nut(12) 232. K83 466 113 Washer(12) 233. R50 479 480 Centrifugal fan 2 φ24534. H00 157 008 PT screw 6×20 835. M34 043 080 Special washer 836. D40 135 095 Spacer 837. R50 217 225 Bush 838. R50 480 707 Fan base 239. Y50 033 104 Key 2 5×5×11.540. R50 264 711 Inlet plate 241. R50 264 712 Motor fix leg 242. H00 189 007 PTT screw 5×10 1643. Y50 121 451 Motor 244. H00 061 050 Nut(6) 8

Q'typcs/unit

Page 63: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-80RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

51. Y50 061 693 Damper motor cover 152. R50 074 156 Pull spring 153. R50 473 715 Damper support 154. M31 234 089 Special bush 255. R50 473 716 Damper 156. Y50 061 260 Damper motor 1 220-240V57. H00 312 007 PTT screw 4×6 258. R50 054 225 Bush 259. R50 265 150 Rod 160. Y50 061 706 Control cover 161. K83 170 228 Cord band 162. M45 017 228 Cord band 163. Y50 047 216 Transformer 1 230VAC64. Y50 092 235 Capacitor 2 7μF・440VAC65. H00 011 008 PT screw 4×8(BS) 266. H00 013 076 Lock washer 367. Y50 116 706 Earth fix plate 168. H00 154 005 PPT screw 4×12 269. K81 432 236 Terminal block 1 3P ML-2070. Y50 108 226 Insulation plate 171. Y50 116 707 Circuit fix plate 172. Y50 116 368 Wiring diagram 173. H00 000 003 PP screw 4×8 274. Y50 116 171 Circuit board 1 LG-X02-E75. X40 139 095 Spacer 476. Y50 121 215 Thermistor 177. D42 019 095 Spacer 478. M35 164 224 Cord clip 179. K82 163 225 Cord bush 280. K83 223 225 Bush 1

63

Q'typcs/unit

Page 64: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

60 61 62 63 64 65 66 67 68

3

69 70 71

3

66

3

72 73 74 75 76 77 78 79 80

51 53 54 55

56 58 59

58

52

57

3

—64—

Page 65: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

15 16 17

1 2 3 4 5

6 7 8 9 10 11 12 13 14

4

8

2

4

17

4

3

3

3

14

—65—

Model LGH-100RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

1. H00 000 488 PTT screw 4×12 102. R50 430 609 Flange 23. H00 000 487 PTT screw 4×8 184. R50 095 380 Hanger 45. H00 000 244 PT screw 6×12 166. X50 004 707 Maintenance cover 17. R50 219 381 Core guide 18. Y50 063 718 Filter 29. R50 481 710 Lossnay core 210. R50 481 381 Core guide 111. R50 358 704 Cover 212. R50 466 344 Hinge 113. M34 074 017 Special screw 4×11 114. Y50 029 712 Fix plate 215. R50 483 704 Lead support 216. Y50 126 718 Sound absorbing material 117. Y50 021 609 Flange 2

Q'typcs/unit

Page 66: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

31 32 33 34 35 36 3837

40

31

33

39

32

34

3638

35

37

39 40 41 42 43

4142

43

44

44

—66—

Model LGH-100RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

31. R50 218 067 Special nut(12) 232. K83 466 113 Washer(12) 233. R50 479 480 Centrifugal fan 2 φ24534. H00 157 008 PT screw 6×20 835. M34 043 080 Special washer 836. D40 135 095 Spacer 837. R50 217 225 Bush 838. R50 480 707 Fan base 239. Y50 033 104 Key 2 5×5×11.540. R50 264 711 Inlet plate 241. R50 264 712 Motor fix leg 242. H00 189 007 PTT screw 5×10 1643. Y50 122 451 Motor 244. H00 061 050 Nut(6) 8

Q'typcs/unit

Page 67: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-100RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

51. Y50 061 693 Damper motor cover 152. R50 074 156 Pull spring 153. R50 473 715 Damper support 154. M31 234 089 Special bush 255. R50 473 716 Damper 156. Y50 061 260 Damper motor 1 220-240V57. H00 312 007 PTT screw 4×6 258. R50 054 225 Bush 259. R50 265 150 Rod 160. Y50 061 706 Control cover 161. K83 170 228 Cord band 162. M45 017 228 Cord band 163. Y50 047 216 Transformer 1 230VAC64. Y50 092 235 Capacitor 2 7μF・440VAC65. H00 011 008 PT screw 4×8(BS) 266. H00 013 076 Lock washer 367. Y50 116 706 Earth fix plate 168. H00 154 005 PPT screw 4×12 269. K81 432 236 Terminal block 1 3P ML-2070. Y50 108 226 Insulation plate 171. Y50 116 707 Circuit fix plate 172. Y50 116 368 Wiring diagram 173. H00 000 003 PP screw 4×8 274. Y50 116 171 Circuit board 1 LG-X02-E75. X40 139 095 Spacer 476. Y50 122 215 Thermister 177. D42 019 095 Spacer 478. M35 164 224 Cord clip 179. K82 163 225 Cord bush 280. K83 223 225 Bush 1

67

pcs/unit Q'ty

Page 68: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

—68—

60 61 62 63 64 65 66 67 68

3

69 70 71

3

66

3

72 73 74 75 76 77 78 79 80

51 53 54 55

56 58 59

58

52

57

3

Page 69: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

1 2 3 4 5

6 7 8 9 10 11 12 14 1513

2

5

5

8

5

1

15

2

12

13

2

2

2

15

54

4

4

15

—69—

Model LGH-150RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

1. Y50 123 704 Flange 22. H00 000 487 PTT screw 4×8 403. R50 466 344 Hinge 24. R50 111 381 Hanger 85. H00 000 244 PT screw 6×12 406. X50 004 707 Maintenance cover 27. R50 218 381 Core guide 28. Y50 063 717 Filter 49. R50 480 710 Lossnay core 410. R50 480 381 Core guide 211. M34 074 017 Special screw 4×11 212. Y50 029 712 Fix plate 413. R50 483 704 Lead support 414. Y50 126 718 Sound absorbing material 215. Y50 021 609 Flange 4

Q'typcs/unit

Page 70: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

31 32 33 34 35 36 3837

40

31

33

39

32

34

3638

35

37

39 40 41 42 43

4142

43

44

44

—70—

Model LGH-150RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

31. R50 218 067 Special nut(12) 432. K83 466 113 Washer(12) 433. R50 479 480 Centrifugal fan 4 φ24534. H00 157 008 PT screw 6×20 1635. M34 043 080 Special washer 1636. D40 135 095 Spacer 1637. R50 217 225 Bush 1638. R50 480 707 Fan base 439. Y50 033 104 Key 4 5×5×11.540. R50 264 711 Inlet plate 441. R50 264 712 Motor fix leg 442. H00 189 007 PTT screw 5×10 3243. Y50 121 451 Motor 444. H00 061 050 Nut(6) 16

Q'typcs/unit

Page 71: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-150RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

51. Y50 061 693 Damper motor cover 252. R50 074 156 Pull spring 253. R50 473 715 Damper support 254. M31 234 089 Special bush 455. R50 473 716 Damper 256. Y50 123 260 Damper motor 257. H00 000 007 PPT screw 4×25 458. R50 271 150 Rod 259. H00 000 003 PP screw 4×8 660. H00 013 076 Lock washer 761. Y50 075 216 Transformer 2 AC220-240V62. H00 000 487 P screw 4×8 863. Y50 092 235 Capacitor 4 7μF・440VAC64. Y50 047 216 Transformer 1 230VAC65. Y50 009 268 Relay 666. Y50 123 707 Control base 167. D41 093 223 Cord clip 368. Y50 123 171 Circuit board 1 LG-X02-E269. X40 139 095 Spacer 470. D42 019 095 Spacer 471. Y50 123 706 Earth fix plate 172. Y50 123 368 Wiring diagram 173. Y50 123 705 Control cover 174. M34 721 045 Special screw 4×10 275. H00 231 005 PPT screw 4×16 276. Y45 608 236 Teaminal block 1 ML-20-A37-3P77. Y50 108 226 Insulation plate 178. H00 000 384 PPT screw 3×6 1279. H00 011 008 PT screw 4×8(BS) 380. Y50 116 706 Earth fix plate 181. M35 698 223 Cord clip 282. Y50 123 215 Thermistor 183. R50 351 225 Bush 284. K82 163 225 Cord bush 1

71

Q'typcs/unit

Page 72: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

2

8160

83

62

62

62

74

67

78

63

67

60 61 62 63 64 65 66 67 68 69 70 71

72 73 74 75 76 77 78 79 80

51 53 54 55

56 58

52

57

59

81 82 83 84—72—

Page 73: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

14 1513

15

13

15

1 2 3 4 5

6 7 8 9 10 11 12

2

5

5

8

5

1

2

12

2

2

2

54

4

4

15

—73—

Model LGH-200RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

1. Y50 123 704 Flange 22. H00 000 487 PTT screw 4×8 403. R50 466 344 Hinge 24. R50 111 381 Hanger 85. H00 000 244 PT screw 6×12 406. X50 004 707 Maintenance cover 27. R50 219 381 Core guide 28. Y50 063 718 Filter 49. R50 481 710 Lossnay core 410. R50 481 381 Core guide 211. M34 074 017 Special screw 4×11 212. Y50 029 712 Fix plate 413. R50 483 704 Lead support 414. Y50 126 718 Sound absorbing material 215. Y50 021 609 Flange 4

Q'typcs/unit

Page 74: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

31 32 33 34 35 36 3837

40

31

33

39

32

34

3638

35

37

39 40 41 42 43

4142

43

44

44

—74—

Model LGH-200RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

31. R50 218 067 Special nut(12) 432. K83 466 113 Washer(12) 433. R50 479 480 Centrifugal fan 4 φ24534. H00 157 008 PT screw 6×20 1635. M34 043 080 Special washer 1636. D40 135 095 Spacer 1637. R50 217 225 Bush 1638. R50 480 707 Fan base 439. Y50 033 104 Key 4 5×5×11.540. R50 264 711 Inlet plate 441. R50 264 712 Motor fix leg 442. H00 189 007 PTT screw 5×10 3243. Y50 122 451 Motor 444. H00 061 050 Nut(6) 16

Q'typcs/unit

Page 75: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Model LGH-200RX4-E

No. Parts No. Name of part Critical Remarks Pricefor safety

51. Y50 061 693 Damper motor cover 252. R50 074 156 Pull spring 253. R50 473 715 Damper support 254. M31 234 089 Special bush 455. R50 473 716 Damper 256. Y50 123 260 Damper motor 257. H00 000 007 PPT screw 4×25 458. R50 271 150 Rod 259. H00 000 003 PP screw 4×8 660. H00 013 076 Lock washer 761. Y50 075 216 Transformer 2 AC220-240V62. H00 000 487 PTT screw 4×8 863. Y50 092 235 Capacitor 4 7μF・440VAC64. Y50 047 216 Transformer 1 230VAC65. Y50 009 268 Relay 666. Y50 123 707 Control base 167. D41 093 223 Cord clip 368. Y50 123 171 Circuit board 1 LG-X02-E269. X40 139 095 Spacer 470. D42 019 095 Spacer 471. Y50 123 706 Earth fix plate 172. Y50 123 368 Wiring diagram 173. Y50 123 705 Control cover 174. M34 721 045 Special screw 4×10 275. H00 231 005 PPT screw 4×16 276. Y45 608 236 Teaminal block 1 ML-20-A37-3P77. Y50 108 226 Insulation plate 178. H00 000 384 PPT screw 3×6 1279. H00 011 008 PT screw 4×8(BS) 380. Y50 116 706 Earth fix plate 181. M35 698 223 Cord clip 282. Y50 124 215 Thermistor 183. R50 351 225 Bush 284. K82 163 225 Cord bush 1

Q'typcs/unit

75

Page 76: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

2

8160

83

62

62

62

74

67

78

63

67

60 61 62 63 64 65 66 67 68 69 70 71

72 73 74 75 76 77 78 79 80

51 53 54 55

56 58

52

57

59

81 82 83 84—76—

Page 77: March 2006 No. U111 (Revised to RoHS) LOSSNAYLOSSNAY HAND BOOK (For HONG KONG) Model: LGH-15RX4-E LGH-25RX4-E LGH-35RX4-E LGH-50RX4-E LGH-65RX4-E LGH-80RX4-E LGH-100RX4-E Notice: The

Printed in Japan

March, 2006

35 <MEE>