MCS-MAGNUM EXV LOGICTraining Presentation

www.mcscontrols.com

Revision - 04/21/23

Page 2: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV CONTROL PRESENTATIONMCS EXV CONTROL PRESENTATION

1. EXV CONTROLLER & VALVEa. Controller Descriptionb. Wiringc. Specifications

2. BASIC CONTROLS (INFINITE CAPACITY)a. Set Pointsb. Control Zones

3. BASIC CONTROLS (STEP CAPACITY)a. Set Pointsb. Relay Outputs for steps

4. EXV ADAPTIVE CONTROLa. Rate of Changeb. Load Adjustc. Low Suction Control

Page 3: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

6. EXV MODES, STATES & LOGIC CHART

5. LIQUID LEVEL CONTROL

MCS EXV CONTROL PRESENTATIONMCS EXV CONTROL PRESENTATIONContinued

7. FINE TUNING YOUR MCS-EXV-DRIVER

Page 4: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

EXV CONTROLLER & VALVEEXV CONTROLLER & VALVE

- DESCRIPTION

- WIRING DIAGRAM

- SPECIFICATIONS

Page 5: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV-DRIVERMCS-EXV-DRIVER

•Standard 110 to 240 VAC ±10% (50/60 Hz)

• Option 24 VAC ± 10% (50/60 Hz)

•2 position led display

•Auto / Manual operation

•Closes valve on power failure

•Eliminates need for Liquid Line Solenoid

•33% faster valve operation

•CSA / UL approved

Page 6: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV-DRIVER WIRINGMCS-EXV-DRIVER WIRINGSporlanSporlan

BLACK

WHITE

WHITE WIRE TO ANALOG OUTPUT

BLACK & SHIELD TO ANALOG OUTPUT GROUND

BLACK TO LINE 120/240 VAC

WHITE TO NETURAL 120/240

RED

GREEN

WHITE

BLACK

ELECTRIC EXPANSION

VALVE

Page 7: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV-DRIVER WIRINGMCS-EXV-DRIVER WIRINGAlcoAlco

BLACK

WHITE

WHITE WIRE TO ANALOG OUTPUT

BLACK & SHIELD TO ANALOG OUTPUT GROUND

BLACK TO LINE 120/240 VAC

WHITE TO NETURAL 120/240

BROWN

BLUE

WHITE

BLACK

ELECTRIC EXPANSION

VALVE

Page 8: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV-DRIVER WIRINGMCS-EXV-DRIVER WIRINGDanfossDanfoss

BLACK

WHITE

WHITE WIRE TO ANALOG OUTPUT

BLACK & SHIELD TO ANALOG OUTPUT GROUND

BLACK TO LINE 120/240 VAC

WHITE TO NETURAL 120/240

RED

GREEN

WHITE

BLACK

ELECTRIC EXPANSION

VALVE

Page 9: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV-DRIVER WIRINGMCS-EXV-DRIVER WIRINGCarelCarel

BLACK

WHITE

WHITE WIRE TO ANALOG OUTPUT

BLACK & SHIELD TO ANALOG OUTPUT GROUND

BLACK TO LINE 120/240 VAC

WHITE TO NETURAL 120/240

GREEN

YELLOW

BROWN

WHITE

ELECTRIC EXPANSION

VALVE

Page 10: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

SpecificationsSpecifications

Display # of Steps SPORLANS1 1596 SEI 0.5 to 11

S2 1596 SER 1.5 to 20

S3 3193 SEI 30; SDR –3, SDR-3x

S4 2500Sporlan SERI-G, -J, -K, -LSporan SER-B, -C, -D, -FCDS -2, -4, -7

S5 6388 SEI-50, SHE (I)-100, -175, -400; CDS –9, -16, -17; SDR –4

Display # of Steps ALCOA1 750 EX4 & EX5

A2 1660 EX7

A3 2600 EX8

Display # of Steps DANFOSSD1 2625 ETS-12/25/50

D2 3530 ETS-100

D3 3810 ETS-250/400

Display # of Steps CARELCL 500 E2V, E3V, E4V, E5V, E6V, E7V

Page 11: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV BASIC CONTROL(Infinite Capacity Control)

- SET POINTS

- CONTROL ZONES

Page 12: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV-DRIVER SET POINTS(MCS CHILLER)

# NAME VALUE TIME MAX TIME ALLOWED

9 SUPERHT TRGT 10.5 4 8

10 SPRHT + - 1.5 - -

11 EXV LOAD ADJ 0.6 - -

12 EXV FINE ADJ 0.2 - -

13 EXV COURSE ADJ 0.5 2 4

15 EXV MIN% 20.5 - -

16 EXV MAX% 100 - -

17 LO SUPERHEAT 1 - -

18 LOSUCTPSIDLY 4 - -

19 EXV DELAY 60 - -

20 EXV STRT TME 5 - -

SH Target ± Ctl Zone

SH Fine & Course Adj

EXV Min & MAX %

Timing CtlSet Points

Page 13: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV-DRIVER SET POINTS(MCS CHILLER)

# NAME VALUE TIME MAX TIME ALLOWED

65 EXV ZONE X1 1.5 - -

66 EXV ZONE X2 1.5 - -

67 EXV rocZONE1 0.2 4 10

69 EXV rocZONE2 0.3 5 10

70 EXV rocZONE3 0.4 5 10

71 EXV roc FAST 1 10 15

72 EXV roc CHG 0.8 10 15

IndividualZone Ctl

IndividualROC Ctl

Zone 1 Speed Ctl

Page 14: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

EXV ABOVE & BELOW ZONES

BELOW ZONES < 6.0CLOSING 4X

COURSE ADJ * 2 @ QUARTER STEP DELAY

18

16

15

14

13

12

11

10

9

8

7

6

5

4

SUPERHEAT

CONTROL ZONESPT 9 = 10.5SP 10 = 1.5

9.0 TO 12.0 EXV IS HOLDING ROC CONTROL

ZONE 1 ABOVESPT 65 = 1.5

12.0 TO 13.5EXV IS OPENING

FINE ADJ @ STEP DELAY TIME

ZONE 1 BELOWSP 65 = 1.5

7.5 TO 9.0EXV IS CLOSING

FINE ADJ @ STEP DELAY TIME

ZONE 2 ABOVESPT 66 = 1.5

13.5 TO 15.0OPENING 2X

COURSE ADJ @ HALF STEP DELAY

ABOVE ZONES > 15.0OPENING 4X

COURSE ADJ * 2 @ QUARTER STEP DELAY

ZONE 2 BELOWSPT 66 = 1.5

6.0 TO 7.5CLOSING 2X

COURSE ADJ @ HALF STEP DELAY

Page 15: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV BASIC CONTROL(Step Capacity Control)

- SET POINTS

- RELAY OUTPUT SETUP FOR STEPS

Page 16: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV-DRIVER SET POINTS# NAME VALUE TIME MAX TIME

ALLOWED

9 SUPERHT TRGT 10.5 4 8

10 SPRHT + - 1.5 - -

12 EXV FINE ADJ 0.2 - -

13 EXV COURSE ADJ 0.5 - -

14 EXV LOAD DIV 3 - -

With EXV Step Control the following Set Points are changed:• SP 11, ‘EXV LOAD ADJUST’ is deleted• SP 14, ‘EXV LOAD DIV’ is added• As the Amp draw % changes this divides the EXV % change

calculated as the ratio of slide movement to valve movement[(Max slide% – min slide%) / (Max vlv% - min vlv%)] +1

No Change

Page 17: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

15 EXV MIN% 10 - -

16 EXV MAX% 100 - -

17 LO SUPERHEAT 2 120 120

18 LOSUCTPSIDLY 4 - -

19 EXV DELAY 60 - -

20 EXV STRT TME 5 10 10

MCS-EXV-DRIVER SET POINTS

The remaining set points remain active with the following changes:• SP 17 TIME & MAX TIME ALLOWED are setup

# NAME VALUE TIME MAX TIME ALLOWED

No Change

No Change

Page 18: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS RELAY OUTPUT CFG SETUP (Step Capacity Control)

- Cfg RO screen when Type = Step w\ EXV setup following:• EXV Starting % when this compressor is the lead• EXV Load Adjust %, the % increase to apply to the current EXV opening

when this compressor is not the lead and is started• EXV Unld adjust %, the % decrease to apply to the current EXV opening

when this compressor is not the last compressor and is turned off

Page 19: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS RELAY OUTPUT MCS-CONNECT

EXV START WHEN LEAD

COMPRESSOR STARTING %

COMPRESSOR TIME IN STARTUP

Page 20: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

EXV ADAPTIVE CONTROL

- LOAD ADJUSTMENT

- RATE of CHANGE

- LOW SUCTION CONTROL

Page 21: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV ROC FUNCTION(MCS CHILLER)

# NAME VALUE TIME MAX TIME ALLOWED

9 SUPERHT TRGT 10.5 4 8

- TIME field in set point 9 is the number of seconds to look at the slope of the superheat (ROC).

- MAX TIME ALLOWED field is the maximum value the TIME field can be set to.

Page 22: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV ROC FUNCTION(MCS CHILLER)

- VALUE field in set points is the ROC allowed for that zone

- TIME field is the minimum time the EXV is kept in the HOLDING state.

# NAME VALUE TIME MAX TIME ALLOWED

67 EXV rocZONE1 0.2 4 10

69 EXV rocZONE2 0.3 5 10

70 EXV rocZONE3 0.4 5 10

Page 23: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV ROC FUNCTION(Special Action)

Super Heat Below Control Zone- If in Zone 1 and the EXV ROC is positive and > then SP 67 then

hold for number of seconds in time field. If in Zone 2 and the EXV ROC is positive and > then SP 69 then

hold for number of seconds in time field. If in Zone 3 and the EXV ROC is positive and > then SP 70 then

hold for number of seconds in time field.

Super Heat Above Control Zone- If above zones and the EXV ROC is negative and < then SP 70

then hold for number of seconds in time field. If in Zone 2 and the EXV ROC is negative and < then SP 69 then

hold for number of seconds in time field. If in Zone 1 and the EXV ROC is negative and < then SP 67 then

hold for number of seconds in time field.

Page 24: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV ROC FUNCTION(Special Action)

EXV ROC FAST- If we are opening or closing at 2x, if the absolute value of the

super heat ROC is > than the value in SP 71 we will hold for the time in SP 71.

EXV ROC CHG- If the super heat state is ‘EXV is HOLDING’ this value

specifies the maximum value of the change % that can be made.

Page 25: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV LOAD ADJ FUNCTION(MCS CHILLER)

# NAME VALUE TIME MAX TIME ALLOWED

9 SUPERHT TRGT 10.5 4 8

- VALUE field, in EXV LOAD ADJ, is the value the EXV will be adjusted each time the compressor capacity is adjusted. Used on modulating compressors.

11 EXV LOAD ADJ 0.6 - -

Page 26: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV LOW SUCTION ADJUSTMENT

HOW IT NORMALLY OCCURS Condenser is sized for high ambient We have a low ambient condition Usually when the last stage of condensing is turned on

WHAT NORMALLY HAPPENS Because of the pressure drop some of the liquid boils off before it gets to

the EXV Now you have liquid and vapor mixed requiring the EXV to open This occurs within 1 minute and system returns to normal in about 3

minutes.

Page 27: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

GRAPH OF LOW SUCTION OCCURING

Notice the 3rd stage of condensing comes on

15 seconds later the suction psi crashes

Page 28: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV LOW SUCTION ADJUSTMENT(MCS CHILLER)

# NAME VALUE TIME MAX TIME ALLOWED

13 EXV COURSE ADJ 0.5 4 5

18 LOSUCTPSIDLY 2 - -

19 EXV DELAY 60 - -

Once the Magnum has determined it is in a LOW SUCTION situation it will take the EXV COURSE ADJ and multiply it by the value in the TIME field of SP 13. It will continue to make this adjustment, based on the value in Set Point 56 ‘PULSE or CMP LOAD DELAY’ until the situation is cleared.

Page 29: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV FLOODED LEVEL CONTROL# NAME VALUE TIME MAX TIME

ALLOWED

9 REFR LVL TRG 41.5 2 0

10 REFR ZONE + - 1 0 0

12 EXV FINE ADJ 0.2 - -

13 EXV COURSE ADJ 0.5 - -

15 EXV MIN% 10 - -

16 EXV MAX% 100 - -

18 LOSUCTPSIDLY 4 - -

19 EXV DELAY 60 - -

20 EXV STRT TME 5 10 10

- EXV set points 9 & 10 now reflect refrigerant level- EXV other set points remain same

No Change

Page 30: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS-EXV FLOODED LEVEL CONTROLNew Set Points

# NAME VALUE TIME MAX TIME ALLOWED

109 HI REFR LEVEL 50.0 - -

217 LOW REFR LEVEL 32.5 - -

- Set point 9 & 217 specify the range that will be used to maintain and even refrigeration level when required.

- Set point 109 specifies the upper limit and will cause a safety shutdown.

9 REFR LVL TRG 41.5 2 0

Page 31: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

EXV UNIT MODES & STATES

- EXV STATES

- EXV DRIVER MODES

- EXV LOGIC CHART

Page 32: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV Unit ModesMCS EXV Unit Modes Auto Mode – The unit defaults to this mode after every power up.

In this mode, the MCS-EVX-DRIVER-XX positions the valve according to the analog input control voltage.

Manual Mode – When in auto mode, holding the ‘Auto/Manual’ key for 5 seconds, then entering the authorization number switches the unit into Manual mode. In this mode, the valve position is controlled with the keypad’s directional arrows.

Power Down Mode – If the main power is disconnected, the controller switches to the power down mode. In this mode, the controller uses internal power to close the expansion valve.

Page 33: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

MCS EXV Controller StatesSTATE DESCRIPTION

LOCKED OUT The compressor is in a Lockout state.

EXV IS CLOSED The associated compressor is OFF and the valve is closed.

PRE-PMPDWN The valve has been in a closed state while the system goes through a pump down.

EXV IN STARTUP At startup the valve will remain in this state for the time in Set Point #20. At that time the state will be changed to holding, at this point the valve control logic will position the valve.

EXV AT 100% This state will be entered when the valve opening reaches 100%.

EXV IS HOLDING Refer to EXV Logic Chart, superheat is in control zone and ROC is acceptable.

EXV IS OPENING Refer to EXV Logic Chart, superheat is in control zone but rising too fast, ROC less than 1.0.

EXV IS CLOSING Refer to EXV Logic Chart, superheat is in the control zone and the rate of change is acceptable, ROC greater than -0.5.

LOW SPRHT Refer to EXV Logic Chart, force a course valve adjustment.

Page 34: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

EXV State Controller States (Continued)

STATE DESCRIPTION

OPENING 4x Refer to EXV Logic Chart, superheat is above control zone.

OPENING 2x Refer to EXV Logic Chart, superheat is in control zone but rising too fast, the ROC is greater than 1.0.

LO PSI OPN Refer to EXV Logic Chart, state indicates that a low suction pressure condition exists. The suction pressure is less than Set point #77 “LOW SUCTION” plus twice the value of Set point #79 “LOW SUCT RELOAD” and the superheat is greater than Set point #9 “SUPERHT TRGT” plus twice the value of Set point #10 “SPRHT ZONE+-.”

CLOSING 2x Refer to EXV Logic Chart, superheat is in the control zone and the rate of change is acceptable, the ROC is less than -0.5 and greater than -1.0.

CLOSING 4x Refer to EXV Logic Chart, superheat is in control zone but falling too fast, ROC less than -1.0.

Page 35: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

EXV State Controller States (Continued)

STATE DESCRIPTION

HI LVL CLS This state indicates that a high refrigerant level. This state is entered if Set point #109 “HiRefLevel” is active and the superheat is greater than the value of this Set point.

EXV MOP CLS Refer to EXV Logic Chart. Maximum operating pressure option is active and it is forcing the EXV to close. In this state the EXV valve’s opening will be reduced.

EXV MOP HLD Refer to EXV Logic Chart. Maximum operating pressure option is active and it is forcing the EXV to hold.

Kelly Mitchell
space??
Kelly Mitchell
space
Page 36: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

EXV LOGIC CHART

Page 37: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

FINE TUNING YOUR MCS-EXV-DRIVERPart 1

Verify what has been done.1.Completed the MCS EXV DRIVER setup specifying valve type.2.Completed the setup for starting valve position in cfg.3.If a modulating compressor verify starting % is set.

Using MCS-Connect, review start up.1.Set history sample rate at 1 sec2.Place RUN/STOP switch to RUN

Page 38: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

FINE TUNING YOUR MCS-EXV-DRIVERPart 2

Normal MCS CONTROLLER start up.1.At 2 to 3 minutes from compressor starting, suction superheat should be between ± Control Zone 1.

a. If above Control Zone 1 increase starting valve opening %.b. If below Control Zone 1 decrease starting valve opening %.

2.At end of startup Discharge temperature should be 110°F or higher.a. If less than 105°F and we have a modulating compressor and the load

is adequate increase the startup speed.b. Otherwise increase the startup time.

3.Watch changing capacity, if superheat is moving too much as capacity changes, lower LOAD ADJUST set point.4.Pull Graph at about 15 minutes after starting, this will allow you to review startup results.5.If Unit is stable but EXV is hunting check time in superheat target. The length of time to calculate superheat ROC should be no less then 3 and no higher than 8. If hunting lower by 1 and watch results.

Page 39: MCS-MAGNUM EXV LOGIC Training Presentation  Revision - 12/12/2015.

For additional information please visit our website www.mcscontrols.com

Or call MCS at 239-694-0089