11/13/2018
1
MEA 2017 NECGrounding and Bonding
Part 4
2-hour class presented by
Minnesota Electrical Association
This seminar will satisfy the 2-hour electrical code training for electricians required by the State of Minnesota.
Minnesota Electrical Association 1
Acknowledgements
Some material and illustrations presented are with permission of Cengage Learning from: Electrical Grounding and Bonding 2014 by Phil Simmons
The National Electrical Code (NEC)® is: Document 70 from the National Fire Protection
Association (NFPA)
11/13/2018
2
Objectives:
Equipment required to be grounded that is fastened in place or connected by permanent wiring methods that is connected to an equipment grounding conductor
Types of acceptable equipment grounding conductors
Identification requirements for equipment grounding conductors
3
Objectives:
Installation requirements for equipment grounding conductors
The minimum size of equipment grounding conductors
Rules for continuity of equipment grounding conductors
Means of identification of wiring device terminals
4
11/13/2018
3
Part VI: Equipment grounding and Grounding Conductors
250.110 Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods
Exposed normally non–current-carrying metal parts of fixed equipment supplied by or enclosing conductors or components that are likely to become energized are required to be connected to the equipment grounding conductor under any of the following conditions:
(1) If within 8 ft (2.5 m) vertically or 5 ft (1.5 m) horizontally of ground or grounded metal objects and subject to contact by persons
(2) If located in a wet or damp location and not isolated ----Continued---
5
250.110 Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods
(3) If in electrical contact with metal(4) If in a hazardous (classified) location as covered
by Articles 500 through 517(5) If supplied by a wiring method that provides an
equipment grounding conductor, except as permitted by 250.86 Exception No. 2 for short sections of metal enclosures
(6) If equipment operates with any terminal at over 150 volts to ground
6
11/13/2018
4
250.110 Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods
• Exception No. 1: If exempted by special permission, the metal frame of electrically heated appliances that have the frame permanently and effectively insulated from ground shall not be required to be grounded.
• Exception No. 2: Distribution apparatus, such as transformer and capacitor cases, mounted on wooden poles at a height exceeding 2.5 m (8 ft) above ground or grade level shall not be required to be grounded.
• Exception No. 3: Listed equipment protected by a system of double insulation, or its equivalent, shall not be required to be connected to the equipment grounding conductor. Where such a system is employed, the equipment shall be distinctively marked.
7
250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods
Except as permitted in 250.112(F) and (I) (as follows) , (following sections)) exposed, normally non–current-carrying metal parts of equipment described in 250.112(A) through (K) (as follows) , and normally non–current-carrying metal parts of equipment and enclosures described in 250.112(L) and (M) (as follows), shall be connected to an equipment grounding conductor, regardless of voltage.
(A) Switchgear and Switchboard Frames and Structures. Switchgear and Switchboard frames and structures supporting switching equipment, except frames of 2-wire dc switchgear or switchboards where effectively insulated from ground.
8
11/13/2018
5
250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods
(B) Pipe Organs. Generator and motor frames in an electrically operated pipe organ, unless effectively insulated from ground and the motor driving it.
(C) Motor Frames. Motor frames, as provided by 430.242. (grounding of stationary motors )
Specific requirements for grounding motors and related equipment can be found in Article 430, Part XIII.
9
250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods
(D) Enclosures for Motor Controllers. Enclosures for motor controllers unless attached to ungrounded portable equipment.
(E) Elevators and Cranes. Electric equipment for elevators and cranes.
(F) Garages, Theaters, and Motion Picture Studios. Electric equipment in commercial garages, theaters, and motion picture studios, except pendant lampholders supplied by circuits not over 150 volts to ground.
(G) Electric Signs. Electric signs, outline lighting, and associated equipment as provided in Article 600.
10
11/13/2018
6
250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods
(H) Motion Picture Projection Equipment. Motion picture projection equipment.
(I) Power-Limited Remote-Control, Signaling, and Fire Alarm Circuits. Equipment supplied by Class 1 circuits is required to be grounded unless operating at less than 50 volts. Equipment supplied by Class 1 power-limited circuits, Class 2, and Class 3 remote-control and signaling circuits, and by fire alarm circuits, are required to be grounded if the system is to be grounding by Part II or Part VIII of Article 250.
11
250.112(J) Grounding Luminaires
Luminaires with exposed conductive parts are generally required to be grounded in accordance with Part V of Article 410
See 410.42
12
Copyright © Cengage Learning
11/13/2018
7
410.42 Exposed Conductive Parts
Luminaires: Exposed metal parts are required to be connected to an equipment grounding conductor or be insulated from the equipment grounding conductor and other conducting surfaces or be inaccessible to unqualified personnel.
13
410.44 General
Luminaires and lighting equipment are required to be mechanically connected to an equipment grounding conductor as specified in 250.118 that is sized in accordance with 250.122 if of the wire type.
14
11/13/2018
8
410.44 Ex. No. 1 Made of Insulating Material
Luminaires directly wired or attached to outlets supplied by a wiring method that does not provide a ready means for grounding attachment to an equipment grounding conductor are required to be made of insulating materials and have no exposed conductive surfaces.
15
410.44 Ex. No. 2 Replacement Luminaires
Replacement luminaires (fixtures) are permitted to be grounded in accordance with 250.130(C)
External equipment grounding conductor installed
Copyright © Cengage Learning16
11/13/2018
9
410.44 Ex. No. 3 GFCI Protected
If no equipment grounding conductor exists at the outlet, replacement luminaires are permitted to be GFCI protected rather than being connected to an equipment grounding conductor
Listing requirements may mandate connecting to equipment grounding conductor. 110.3(B)
Copyright © Cengage Learning17
250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods
(K) Skid Mounted Equipment. Permanently mounted electrical equipment and skids shall be grounded with an equipment bonding jumper sized as required by 250.122.
(L) Motor-Operated Water Pumps. Motor-operated water pumps, including the submersible type are required to be connected to the equipment grounding conductor.
18
11/13/2018
10
250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods
(M) Metal Well Casings. If a submersible pump is used in a metal well casing, the well casing must be bonded to the pump circuit equipment grounding conductor.
19Copyright © Cengage Learning
250.114 Equipment connected by cord and plug
Conditions as in items 1-4 the exposed non-current carrying parts of equipment will be connected to an equipment grounding conductor
1) Hazardous locations2) Operating over 150 Volts to ground - with
exceptions 3) In residential occupancies - see list4) Other than residential occupancies - see list
20
11/13/2018
11
250.116 Non-electrical equipment
The metal parts of equipment shall be connected to ground
1) Frames and tracks of electrically operated hoists and cranes
2) Frames of elevators that have electrical conductors to the cars (hydraulic elevators)
3) Hand operated metal ropes or cables of electric elevators
21
250.118 Types of Equipment Grounding Conductors
• A copper, aluminum, or copper-clad aluminum conductor. This conductor is generally permitted to be solid or stranded; insulated, covered, or bare; and in the form of a wire or a busbar of any shape.
• An insulated equipment grounding conductor is required by several NEC sections
22
11/13/2018
12
250.118 Types of Equipment Grounding Conductors
(2) Rigid metal conduit
(3) Intermediate metal conduit
(4) Electrical metallic tubing
◦ Good workmanship is essential in providing an effective fault-current path◦ The conduit or tubing carry fault current◦ Loose connections can interrupt the fault path
or cause arcing or sparking
23
RMC, IMC and EMT
No maximum length to function as an equipment grounding conductor is given in the NEC
Maximum “effective” length can be calculated using GEMI™ software o Set up software using values for fault clearing
characteristics of overcurrent device
Table 6-1 (next slide) has effective lengths for circuit breaker and fuse OCP
24
11/13/2018
13
TABLE 6-1
If Overcurrent trips at: 5 X rated current for fault then use 5X, if 2 times rated current then 2X
2525
250.118(5) Listed FMC
Conduit is terminated in listed fittings
Circuit conductors have OCP max 20A
Combined length not more than 6 ft
The size of the conduit does not exceed 1-1/4” trade size
EGC required if installed for flexibility to minimize transmission of vibration
1951
Copyright © Cengage Learning26
11/13/2018
14
250.118(6) Listed LFMC
Conduit is terminated in listed fittings
For trade sizes through ½ in. circuit conductors have OCP max 20A
For circuit conductors trade sizes ¾ through 1 ¼, OCP maximum 60 A
Listed LFMC required
2727
250.118(6) Listed LFMC
For circuit conductors trade sizes ¾ through 1¼, OCP maximum 60 A with no smaller LFMC in the path
Combined length not more than 6 ft
Where installed for flexibility, EGC required
Unlisted type LFMC is not suitable for grounding
350.6 requires LFMC to be listed
28
11/13/2018
15
250.118(7) Flexible Metallic Tubing
Fittings must be listed
Circuit conductors to have not more than 20 A overcurrent protection
Combined length of ground-fault path with FMC and LFMC is not more than 6 ft
2929
250.118(8) Type AC Cable
Armor of Type AC cable as per 320.108
Listed AC cable has a bonding conductor under armor
Armor and bonding conductor equals ground path
3030
11/13/2018
16
250.118(9) Type MI Cable
The copper sheath of mineral-insulated, metal sheathed cable
31
250.118(9) Terminating Single-Conductor Type MI Cable
32
11/13/2018
17
250.118(10) Type MC Cable
Type MC cable that provides an effective ground-fault current path by:◦ An insulated or bare equipment grounding
conductor in compliance with 250.118(1), or◦ The combined metallic sheath and uninsulated
grounding/bonding conductor of interlocked metal tape-type MC cable, or◦ The metallic sheath or combined sheath and
grounding conductor of smooth or corrugated tube Type MC cable
33
250.118(10) Type MC Cable
Interlocked and corrugated tube Type MC cables
Three types of Type MC cable is made:
Interlocked armor
Smooth tube
Corrugated tube
34
Copyright © Cengage Learning34
11/13/2018
18
250.118(10) Type MC Cable
“Traditional” interlocked armor Type MC cable –the armor is not suitable as an equipment grounding conductor
35
250.118(10) Type MC Cable
Interlocked armor Type MC cable with a 10 AWG aluminum grounding/bonding conductor in continuous contact with the armor
Combination is suitable as EGC
3636
11/13/2018
19
Fittings for Type MC Cable
Use fitting listed and appropriate for variation of Type MC cable being installed
Size and type of Type MC Cable Use in concrete Grounding (all listed fittings are) Dry and Wet Locations Use with Armored Cable
37
Product Markings for Fittings for Type MC Cable
The range of cable diameters and the type of cable sheath (corrugated, interlocking or smooth)
The material of the sheath (aluminum, copper or steel)
“Concrete-tight” if suitable for that use
38
Type of Metal-Clad Cable Abbreviation
Metal-clad interlocking armor cable MCI
Metal-clad interlocking armor ground cable MCI-A
Metal-clad continuous smooth sheath armor cable MCS
11/13/2018
20
Terminating Type MC Cable Having an Aluminum Equipment Grounding/Bonding Conductor
39Copyright © Cengage Learning
250.118(10) Type MC Cable
This construction of corrugated tube Type MC cable is suitable as an equipment grounding conductor, as a bare equipment grounding conductor if listed and identified.
40
Copyright © Cengage Learning40
11/13/2018
21
250.118(11) Cable Trays
Cable trays as permitted in 392.10 and 392.60
392.60 Grounding and Bonding. Metallic cable trays are permitted to be used as equipment grounding conductors if continuous maintenance and supervision ensure that qualified persons service the installed cable tray system and the cable tray complies with provisions of this section.
41
250.118(12) Cablebus
Cablebus framework as permitted in 370.60(1). “Cablebus framework, where bonded as required by Article 250, shall be permitted as the equipment grounding conductor for branch circuits and feeders.”
42
11/13/2018
22
Cable Tray
11/13/2018
23
250.118(13) Other Raceways
Other listed electrically continuous metal raceways and listed auxiliary gutters
4545
250.118(14) Surface Metal Raceways
Surface metal raceways is listed for grounding ---As per UL when installed per specifications
46
11/13/2018
24
250.119 Identification of Equipment Grounding Conductors
Permitted to be bare, covered or insulated
Covered or insulated conductors to have continuous finish that is either green or green with a yellow stripe
Not permitted to be used as grounded or ungrounded conductor
47
250.119 Exception # 1
Power limited Class 2 or Class 3 cables, power-limited fire alarm cables, or communications cables containing only circuits operating at less than 50 volts are permitted to use a conductor with green insulation for other than equipment grounding purposes
48
11/13/2018
25
250.119 Exception # 2
Flexible cords having an integral insulation and jacket without an equipment grounding conductor shall be permitted to have a continuous outer finish that is green. (Christmas Tree wire, extension cords)
Informational Note: An example of a flexible cord with Integral-type insulation is Type SPT-2, 2 conductor.
When looking at the two numbers for the zip cord, SPT-1 wire has an insulation thickness of 0.030″ and 18/2, SPT-2 has insulation that is 0.045″ thick.
49
250.119 Exception #3
Conductors with green insulation shall be permitted to be used as ungrounded signal conductors where installed between the output terminations of traffıc signal control and traffıc signal indicating heads.
Signaling circuits installed in accordance with this exception shall include an equipment grounding conductor in accordance with 250.118.
Wire-type equipment grounding conductors shall be bare or have insulation or covering that is green with one or more yellow stripes.
50
11/13/2018
26
250.119(A) Conductors 4 AWG and Larger
51
Copyright © Cengage Learning51
250.119(B) Multiconductor Cable
Mark at each end and at every point where the conductor is accessible. Identification of conductor by:
• Stripping the insulation or covering from the entire exposed length
• Coloring the exposed insulation or covering green
• Marking the exposed insulation green (tape) that encircles the conductor
52
Copyright © Cengage Learning52
11/13/2018
27
250.120(A) Raceway, Cable Trays, Cable Armor, Etc.
Use fittings for joints and terminations approved for use with the type of raceway or cable used
Make all connections and joints tight using suitable tools
53
Copyright © Cengage Learning53
250.120(B) Aluminum and Copper-Clad Aluminum Conductors
Bare or insulated are permitted
Bare conductors are not permitted in direct contact with masonry or the earth or where subject to corrosive conditions
Aluminum or copper-clad aluminum conductors are not permitted to be terminated within 18 in. of the earth
54
11/13/2018
28
250.120(C) EGCs Smaller Than #6 AWG
Protect from physical damage by a raceway or cable armor except where run in hollow spaces of walls or partitions where not subject to physical damage or protected from physical damage
55
Copyright © Cengage Learning55
250.121 Use of Equipment Grounding Conductor
An equipment grounding conductor (EGC) shall not be used as a grounding electrode conductor (GEC).
Except: See next slide
Sizing and installation requirements differ significantly.
56
11/13/2018
29
250.121 Use of Equipment Grounding Conductor
Exception: A wire-type equipment grounding conductor installed in compliance with 250.6 A (no objectionable currents) and the applicable requirements for both the equipment grounding conductor and the grounding electrode conductor in Parts II, III, and VI of this article shall be permitted to serve as both an equipment grounding Conductor and a grounding electrode conductor.
57
250.122 Size of Equipment Grounding Conductors
Size in accordance with Table 250.122
Not required to be larger than the circuit conductors
If cable tray, raceway or cable armor or sheath is used as the equipment grounding conductor, it must be installed to provide an effective ground-fault return path as provided in 250.4(A)(4) or (B)(5)
58
11/13/2018
30
Table 250.122 Minimum Size of Equipment Grounding Conductor for Grounding Raceway and Equipment
Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of Equipment, Conduit,
etc., Not Exceeding (Amperes)
Size (AWG or kcmil)
Copper Aluminum or Copper-Clad Aluminum
15 14 1220 12 1060 10 8100 8 6200 6 4400 3 1600 1 2/0800 1/0 3/0
5959
Increasing Size of EGC for Available Short-Circuit Current
The size of the equipment grounding conductor in Table 250.122 is shown to be the “Minimum Size.”
It may need to be increased in size using data such as Table P-32-382 from the Insulated Cable Engineers Association
Do not exceed thermal damage curve for equipment grounding conductor
The equipment grounding conductor must be large enough so it can carry the fault current delivered by the system until the overcurrent device opens
60
11/13/2018
31
Insulated Cable Engineers Association (ICEA) P-32-382
61
250.122(B) Increased in Size
If ungrounded conductors are increased in size, wire type equipment grounding conductors, where used, must be increased proportionately by circular mil area
62
Copyright © Cengage Learning62
11/13/2018
32
Common Applications
The phase conductors are typically increased in size for:◦ Excessive voltage drop◦ High ambient temperatures◦ More than 3 current-carrying conductors in a
raceway or cable
63
Example
200-ampere feeder installation◦ Normal size – 3/0 AWG copper◦ Installed size 300 kcmil for losses
300,000 ÷ 167,800 = 1.788 × bigger ◦ (167,800 = cm area of 3/0 conductor)
Required EGC Table 250.122 = 6 AWG Cm area of 6 AWG in Table 8, Chapter 9 = 26,240 26,240 × 1.788 = 46,917 cm Next standard size in Table 8 of Chapter 9 = 3 AWG
64
11/13/2018
33
250.122(C) Multiple Circuits
Size single equipment grounding conductor for multiple circuits based on the largest overcurrent device for contained conductors
6565
250.122(D) Motor Circuits
Equipment grounding conductors must be installed in accordance with (D)(1) or (D)(2)
(D)(1) The equipment grounding conductor is required to be not smaller than the size determined from Table 250.122 based on the rating of the branch circuit, short circuit and ground fault protection
BUT : The equipment grounding conductor is not required to be larger than the circuit conductors
66
11/13/2018
34
Motor Circuits
Size per Table 250.122 for the rating of branch-circuit, short-circuit, and ground-fault protective device
5 hp, 208-V 3-ph motor, Table 250.250 FLA = 16.7 amperes
16.7 A × 1.25 = 20.9 amperes (minimum conductor size)
Table 310.15(B)(16) = 12 AWG (25 amperes)
67
Example: Motor Circuits
Circuit breaker used as BC, SC and GF protection permitted to be 250% of FLA or 16.7 x 2.5 = 41.8 A
Next standard OC device is 45 A
Table 250.122, EGC required to be 10 AWG- BUT:
EGC permitted to be same as circuit conductors or 12 AWG
68
11/13/2018
35
250.122(D)(2) Motor Circuits
If the overcurrent device consists of an instantaneous trip circuit breaker or a motor short-circuit protector, the equipment grounding conductor is required to be sized not smaller than given by 250.122(A) using the maximum permitted rating of a dual-element time-delay fuse selected for branch-circuit short-circuit and ground-fault protection in accordance with 430.52(C)(1) Exception No. 1. (Next higher size)
69
Here’s How50 HP, 460-Volt, 3-Phase Motor
FLA from Table 430.250 = 65 A
Conductor minimum 125 % = 65 × 1.25 = 81 A
Select 4 AWG (85 A) Table 310.15(B)(16)
FLA × 175 % for BC, SC & GF = 65 × 1.75 = 113.8 A
Round up to 125 A overcurrent device
Select 6 AWG EGC from Table 250.122
70# 6 EGC with #4 ungrounded conductors 70
11/13/2018
36
250.112(F) Conductors in Parallel
If conductors are installed in parallel in multiple raceways as permitted in 310.10(H), equipment grounding conductors where used, are required to be installed as per 1-2 below.
71
250.122 (F) NEW (1) Parallel Conductors in Raceways….
If EGC conductors are installed in parallel in raceway or cable tray, a single wire type EGC may be installed based on 250.122. (raceways and cable trays may serve as the EGC as per 250.118 or 392.60(B)
If EGC conductors are installed in parallel in multiple raceways, the conductors are based on 250.122 and the full size is installed in each raceway. Raceways and cable trays may be used for the EGC.
72
11/13/2018
37
250.122 (F) NEW (2) Multiconductor Cables
(a) If multi-conductor cables are installed in parallel, the EGC conductors are also installed in parallel
(b) If multi-conductor cables are installed in a common raceway, a single EGC per .122 is permitted and connected in parallel with the cable EGC.
(c) EGC conductors in cable trays meet 392.(d) Where multi-conductor cables installed in
parallel, the EGC in each cable shall be based on .122 for the OCP of the total circuit
73
74Copyright © Cengage Learning
11/13/2018
38
Table 6-2
Overcurrent Protection
Number of 200-A Cables
in Parallel
Minimum Size of
Equipment Grounding
Conductor in Each Cable
Typical Size of Equipment
Grounding Conductor on Listed Cable
200 A 1 6 4
400 A 2 3 4
600 A 3 1 4
800 A 4 1/0 4
7575
250.122(G) Feeder Taps
Equipment grounding conductor for feeder taps sized from Table 250.122 based on supply OC protection
Not required to be larger than tap circuit conductors
76
Copyright © Cengage Learning76
11/13/2018
39
250.124 Equipment Grounding Conductor Continuity
First-make, last-break of equipment grounding conductor required for separable connectors
Not required for interlocked equipment
7777
250.126 Identification of Wiring Device Terminals
Green, not readily removable terminal screw with hex head
Green, hexagon terminal nut, not readily removable
Green pressure wire connector
78
Copyright © Cengage Learning78
11/13/2018
40
250.126 Identification of Wiring Device Terminals
FPN: One example of a symbol used to identify the termination point for an equipment grounding conductor
7979
80
Art 250 Part VII Methods of Equipment
Grounding
11/13/2018
41
Objectives:
Equipment grounding conductor connections
Methods permitted for non-grounding receptacle replacement and branch circuit extensions
Rules for equipment fastened in place or connected by permanent wiring methods
81
Objectives:
Grounding frames of ranges, dryers and associated equipment
Use of grounded circuit conductor for grounding equipment
Connecting receptacle grounding terminals Bonding of general-use snap switches Continuity and attachment of equipment
grounding conductors to boxes
82
11/13/2018
42
250.130 Equipment Grounding Conductor Connections
Equipment grounding conductor connections at separately derived systems made per 250.30(A)(1)
Equipment grounding conductor connections at service equipment made per 250.130(A) or (B)
Replacement of receptacles and branch-circuit extensions that do not have equipment grounding conductors permitted as in250.130(C) (this article)
83
250.130(A) For Grounded Systems
Bond the equipment grounding conductor to the grounded service conductor and the grounding electrode conductor
8484
11/13/2018
43
250.130(B) For Ungrounded Systems
Bond the equipment grounding conductor to the grounding electrode conductor
8585
250.130(C) Non-grounding Receptacle Replacement or Branch-Circuit Extensions
The equipment grounding conductor of a grounding-type receptacle or a branch-circuit extension is permitted to be connected to any of the following:
86
For ungrounded systems, the grounding terminal bar at the service
86
11/13/2018
44
250.130(C) Non-grounding Receptacle Replacement or Branch-Circuit Extensions
The equipment grounding conductor of a grounding-type receptacle or a branch-circuit extension is permitted to be connected to any of the following:
(1) Any accessible point on the grounding electrode system as described in 250.50
(2) Any accessible point on the grounding electrode conductor
(3) The equipment grounding terminal bar within the enclosure where the branch circuit for the receptacle or branch circuit originates
(4) An equipment grounding conductor that is part of another branch circuit that originates from the enclosure where the branch circuit for the receptacle or branch circuit originates
(5) For grounded systems, the grounded service conductor within the service equipment enclosure
(6) For ungrounded systems, the grounding terminal bar within the service equipment enclosure
87
88Copyright © Cengage Learning
11/13/2018
45
406.3(D) Replacement of Receptacles
Caution: Many types of equipment are required to be grounded by NEC rules or by manufacturer product listing
If equipment or appliance is required to be grounded, GFCI protection is not permitted in lieu of grounding
Must comply with NEC 110.3(B)
89
250.130(C) Branch-Circuit Extensions
Applies where the existing branch circuit does not contain an equipment grounding conductor
An equipment grounding conductor is installed back to point permitted in 250.130(C)
9090
11/13/2018
46
250.134 Equipment Fastened in Place
Unless grounded by connection to the grounded circuit conductor as permitted by 250.32, 250.140 and 250.142, the non-current-carrying parts of equipment, raceways and other enclosures, if grounded, must be grounded by one of the following methods.
91
250.134(A) Equipment Grounding Conductor Types
By connection to any of the equipment grounding conductors recognized by 250.118
92
11/13/2018
47
250.134(B) With Circuit Conductors
By connection to the equipment grounding conductor contained within the same raceway, cable or otherwise run with the circuit conductors
Exception: The equipment grounding conductor is permitted to be run separately as provided in 250.130(C).
93
250.136 Equipment Considered Effectively Grounded
Under the conditions specified in 250.136(A) and (B), the non-current-carrying metal parts of equipment is considered to be effectively grounded.
94
11/13/2018
48
250.136(A) Equipment Secured to Grounded Metal Supports
Electrical equipment secured to and in electrical contact with metal rack that is grounded by one of the means provided in 250.134
The structural metal frame of a building shall not be used as the required EGC.
95
250.140 Frames of Ranges and Clothes Dryers (New circuits)
Required to be grounded in accordance with 250.134 or 250.138
For appliances requiring a neutral or grounded conductor, a four-wire circuit is required
9696
11/13/2018
49
250.140 Frames of Ranges and Clothes Dryers (Existing circuits)
Permitted to ground to grounded circuit conductor if:
◦ The supply circuit is 120/240-V, 1-Ph, 3-wire or 208Y/120-V from a 3-Ph, 4-wire system
◦ (continued)
9797
250.140 Frames of Ranges and Clothes Dryers ( Exception- Existing circuits)
If no equipment grounding conductor is present in the in the outlet box, the frame of the appliance can be connected to the grounded conductor, if all of the following:
The grounded conductor is not smaller than 10 AWG copper or 8 AWG aluminum
The grounded conductor is insulated, or the grounded conductor is uninsulated and part of a Type SE cable and the branch circuit originates at the service (not a subpanel)
Grounding contacts of receptacles are bonded to the equipment
98
11/13/2018
50
250.140 Frames of Ranges and Clothes Dryers (Existing circuits)
Caution on relocating ranges or dryers where the circuit and receptacle is different from the appliance
A connection from the neutral to the frame is required for 3-wire branch circuits
• Isolate the neutral and connect the equipment grounding conductor to the frame if a 4-wire branch circuit is available
99
250.142 Use of Grounded Circuit Conductor for Grounding Equipment
Supply side Service / derived system – grounded circuit conductor permitted to ground equipment:
• On the supply side or within the enclosure of the ac service disconnecting means
• On the supply side, or within the enclosure, of the main disconnecting means for separate buildings as provided in 250.32(B)
• For separately derived systems as provided in 250.30(A)(1)
100
11/13/2018
51
250.142 Use of Grounded Circuit Conductor for Grounding Equipment
Load side: Not generally permitted to ground equipment by the grounded conductor. Except as permitted:
• 250.30(A)(1) for separately derived systems• 250.32(B) Exception at building or structure• The frames of ranges and dryers as provided in
250.140
101
250.142 Use of Grounded Circuit Conductor for Grounding Equipment
Exception No. 2 for meter enclosures:
• GFPE is not installed• Located immediately
adjacent to service• Grounded circuit
conductor not smaller than specified in 250.122
102
Copyright © Cengage Learning102
11/13/2018
52
250.146 Connecting Receptacle Grounding Terminal to Box
Generally required to connect bonding jumper from grounded box to receptacle
Size per 250.122
103
Copyright © Cengage Learning103
250.146(A) Surface-Mounted Box
Direct metal-to-metal contact and self-grounding type receptacles do not require a bonding jumper
At least one insulating washer must be removed
104
Copyright © Cengage Learning104
11/13/2018
53
250.146(A) Cover-Mounted Receptacles
Bonding jumper required unless the box and cover combination are listed for application
So far as can be determined, no such combinations are listed
105
Copyright © Cengage Learning105
250.146(A) Cover-Mounted Receptacles
A listed exposed work cover is permitted to be the grounding and bonding means when:
• The device is attached to the cover with at least two fasteners that are permanent (such as a rivet) or have a thread locking or screw locking meansand
• The cover mounting holes are located on a flat non-raised portion of the cover
106
11/13/2018
54
107Copyright © Cengage Learning
250.146(B) Contact Devices or Yokes
Bonding jumper not required for listed self-grounding devices
108
Copyright © Cengage Learning108
11/13/2018
55
250.146(C) Floor Boxes
Bonding jumper not required if the assembly is listed as providing satisfactory ground continuity
109
Copyright © Cengage Learning109
Copyright © Cengage Learning110
11/13/2018
56
250.146(D) Isolated Ground Receptacles
The isolated equipment grounding conductor is permitted to pass through one or more panelboards, boxes, wireways, or other enclosures without being connected to the enclosure. It must be terminated at nearest:
• Separately derived system (if the source)• Building disconnecting means• Service equipment
111
250.146(D) Isolated Receptacles
Identified by an orange triangle on its face
Equipment grounding terminal is isolated fromany metal yoke as well asfrom the center terminalfor the cover plate
IN: Use of an isolated ground does NOT dismiss the requirement for the grounding of the raceway or the outlet box
112
Copyright © Cengage Learning112
11/13/2018
57
250.148 Continuity and Attachment of Equipment Grounding Conductor to Boxes
If circuit conductors are spliced within a box or terminated on equipment within, or supported by a box, any equipment grounding conductor associated with the conductors must be spliced or joined in the box or to the box
113
Copyright © Cengage Learning113
250.148 Continuity and Attachment of Equipment Grounding Conductor to Boxes
Equipment grounding conductors associated with feeder conductors are permitted to pass through a pull box unbroken if the circuit conductors are not spliced within the box
114
Copyright © Cengage Learning114
11/13/2018
58
250.148(A) Connections
Connections and splices are required to comply with all the rules in 110.14(B) except that insulation is not required
The rules in 250.8 must also be complied with
115
250.148(B) Grounding Continuity
The removal of a wiring device or luminaire must not interfere with - or interrupt downstream grounding continuity
116
Copyright © Cengage Learning116
11/13/2018
59
250.148(C) Metal Boxes
A connection is required to the equipment grounding conductor by a ground screw that is used for no other purpose or by a listed grounding device
117
Copyright © Cengage Learning117
250.148(D) Nonmetallic Boxes
One or more equipment grounding conductor brought into the box must be arranged so a connection can be made to any fitting or device in the box that requires grounding
118
Copyright © Cengage Learning118
11/13/2018
60
250.148(E) Solder
Connections depending on solder alone are not permitted
Make connections mechanically secure then solder
Equipment grounding conductors get hot when carrying current and can melt solder
119
Copyright © Cengage Learning119
End of Part 4 Grounding and Bonding
Questions ???
120