+ All Categories
Home > Documents > MEA 2017 NEC Grounding and Bonding Part 4

MEA 2017 NEC Grounding and Bonding Part 4

Date post: 01-Dec-2021
Category:
Upload: others
View: 3 times
Download: 1 times
Share this document with a friend
60
11/13/2018 1 MEA 2017 NEC Grounding and Bonding Part 4 2-hour class presented by Minnesota Electrical Association This seminar will satisfy the 2-hour electrical code training for electricians required by the State of Minnesota. Minnesota Electrical Association 1 Acknowledgements Some material and illustrations presented are with permission of Cengage Learning from: Electrical Grounding and Bonding 2014 by Phil Simmons The National Electrical Code (NEC) ® is: Document 70 from the National Fire Protection Association (NFPA)
Transcript
Page 1: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

1

MEA 2017 NECGrounding and Bonding

Part 4

2-hour class presented by

Minnesota Electrical Association

This seminar will satisfy the 2-hour electrical code training for electricians required by the State of Minnesota.

Minnesota Electrical Association 1

Acknowledgements

Some material and illustrations presented are with permission of Cengage Learning from: Electrical Grounding and Bonding 2014 by Phil Simmons

The National Electrical Code (NEC)® is: Document 70 from the National Fire Protection

Association (NFPA)

Page 2: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

2

Objectives:

Equipment required to be grounded that is fastened in place or connected by permanent wiring methods that is connected to an equipment grounding conductor

Types of acceptable equipment grounding conductors

Identification requirements for equipment grounding conductors

3

Objectives:

Installation requirements for equipment grounding conductors

The minimum size of equipment grounding conductors

Rules for continuity of equipment grounding conductors

Means of identification of wiring device terminals

4

Page 3: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

3

Part VI: Equipment grounding and Grounding Conductors

250.110 Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods

Exposed normally non–current-carrying metal parts of fixed equipment supplied by or enclosing conductors or components that are likely to become energized are required to be connected to the equipment grounding conductor under any of the following conditions:

(1) If within 8 ft (2.5 m) vertically or 5 ft (1.5 m) horizontally of ground or grounded metal objects and subject to contact by persons

(2) If located in a wet or damp location and not isolated ----Continued---

5

250.110 Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods

(3) If in electrical contact with metal(4) If in a hazardous (classified) location as covered

by Articles 500 through 517(5) If supplied by a wiring method that provides an

equipment grounding conductor, except as permitted by 250.86 Exception No. 2 for short sections of metal enclosures

(6) If equipment operates with any terminal at over 150 volts to ground

6

Page 4: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

4

250.110 Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods

• Exception No. 1: If exempted by special permission, the metal frame of electrically heated appliances that have the frame permanently and effectively insulated from ground shall not be required to be grounded.

• Exception No. 2: Distribution apparatus, such as transformer and capacitor cases, mounted on wooden poles at a height exceeding 2.5 m (8 ft) above ground or grade level shall not be required to be grounded.

• Exception No. 3: Listed equipment protected by a system of double insulation, or its equivalent, shall not be required to be connected to the equipment grounding conductor. Where such a system is employed, the equipment shall be distinctively marked.

7

250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods

Except as permitted in 250.112(F) and (I) (as follows) , (following sections)) exposed, normally non–current-carrying metal parts of equipment described in 250.112(A) through (K) (as follows) , and normally non–current-carrying metal parts of equipment and enclosures described in 250.112(L) and (M) (as follows), shall be connected to an equipment grounding conductor, regardless of voltage.

(A) Switchgear and Switchboard Frames and Structures. Switchgear and Switchboard frames and structures supporting switching equipment, except frames of 2-wire dc switchgear or switchboards where effectively insulated from ground.

8

Page 5: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

5

250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods

(B) Pipe Organs. Generator and motor frames in an electrically operated pipe organ, unless effectively insulated from ground and the motor driving it.

(C) Motor Frames. Motor frames, as provided by 430.242. (grounding of stationary motors )

Specific requirements for grounding motors and related equipment can be found in Article 430, Part XIII.

9

250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods

(D) Enclosures for Motor Controllers. Enclosures for motor controllers unless attached to ungrounded portable equipment.

(E) Elevators and Cranes. Electric equipment for elevators and cranes.

(F) Garages, Theaters, and Motion Picture Studios. Electric equipment in commercial garages, theaters, and motion picture studios, except pendant lampholders supplied by circuits not over 150 volts to ground.

(G) Electric Signs. Electric signs, outline lighting, and associated equipment as provided in Article 600.

10

Page 6: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

6

250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods

(H) Motion Picture Projection Equipment. Motion picture projection equipment.

(I) Power-Limited Remote-Control, Signaling, and Fire Alarm Circuits. Equipment supplied by Class 1 circuits is required to be grounded unless operating at less than 50 volts. Equipment supplied by Class 1 power-limited circuits, Class 2, and Class 3 remote-control and signaling circuits, and by fire alarm circuits, are required to be grounded if the system is to be grounding by Part II or Part VIII of Article 250.

11

250.112(J) Grounding Luminaires

Luminaires with exposed conductive parts are generally required to be grounded in accordance with Part V of Article 410

See 410.42

12

Copyright © Cengage Learning

Page 7: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

7

410.42 Exposed Conductive Parts

Luminaires: Exposed metal parts are required to be connected to an equipment grounding conductor or be insulated from the equipment grounding conductor and other conducting surfaces or be inaccessible to unqualified personnel.

13

410.44 General

Luminaires and lighting equipment are required to be mechanically connected to an equipment grounding conductor as specified in 250.118 that is sized in accordance with 250.122 if of the wire type.

14

Page 8: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

8

410.44 Ex. No. 1 Made of Insulating Material

Luminaires directly wired or attached to outlets supplied by a wiring method that does not provide a ready means for grounding attachment to an equipment grounding conductor are required to be made of insulating materials and have no exposed conductive surfaces.

15

410.44 Ex. No. 2 Replacement Luminaires

Replacement luminaires (fixtures) are permitted to be grounded in accordance with 250.130(C)

External equipment grounding conductor installed

Copyright © Cengage Learning16

Page 9: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

9

410.44 Ex. No. 3 GFCI Protected

If no equipment grounding conductor exists at the outlet, replacement luminaires are permitted to be GFCI protected rather than being connected to an equipment grounding conductor

Listing requirements may mandate connecting to equipment grounding conductor. 110.3(B)

Copyright © Cengage Learning17

250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods

(K) Skid Mounted Equipment. Permanently mounted electrical equipment and skids shall be grounded with an equipment bonding jumper sized as required by 250.122.

(L) Motor-Operated Water Pumps. Motor-operated water pumps, including the submersible type are required to be connected to the equipment grounding conductor.

18

Page 10: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

10

250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods

(M) Metal Well Casings. If a submersible pump is used in a metal well casing, the well casing must be bonded to the pump circuit equipment grounding conductor.

19Copyright © Cengage Learning

250.114 Equipment connected by cord and plug

Conditions as in items 1-4 the exposed non-current carrying parts of equipment will be connected to an equipment grounding conductor

1) Hazardous locations2) Operating over 150 Volts to ground - with

exceptions 3) In residential occupancies - see list4) Other than residential occupancies - see list

20

Page 11: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

11

250.116 Non-electrical equipment

The metal parts of equipment shall be connected to ground

1) Frames and tracks of electrically operated hoists and cranes

2) Frames of elevators that have electrical conductors to the cars (hydraulic elevators)

3) Hand operated metal ropes or cables of electric elevators

21

250.118 Types of Equipment Grounding Conductors

• A copper, aluminum, or copper-clad aluminum conductor. This conductor is generally permitted to be solid or stranded; insulated, covered, or bare; and in the form of a wire or a busbar of any shape.

• An insulated equipment grounding conductor is required by several NEC sections

22

Page 12: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

12

250.118 Types of Equipment Grounding Conductors

(2) Rigid metal conduit

(3) Intermediate metal conduit

(4) Electrical metallic tubing

◦ Good workmanship is essential in providing an effective fault-current path◦ The conduit or tubing carry fault current◦ Loose connections can interrupt the fault path

or cause arcing or sparking

23

RMC, IMC and EMT

No maximum length to function as an equipment grounding conductor is given in the NEC

Maximum “effective” length can be calculated using GEMI™ software o Set up software using values for fault clearing

characteristics of overcurrent device

Table 6-1 (next slide) has effective lengths for circuit breaker and fuse OCP

24

Page 13: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

13

TABLE 6-1

If Overcurrent trips at: 5 X rated current for fault then use 5X, if 2 times rated current then 2X

2525

250.118(5) Listed FMC

Conduit is terminated in listed fittings

Circuit conductors have OCP max 20A

Combined length not more than 6 ft

The size of the conduit does not exceed 1-1/4” trade size

EGC required if installed for flexibility to minimize transmission of vibration

1951

Copyright © Cengage Learning26

Page 14: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

14

250.118(6) Listed LFMC

Conduit is terminated in listed fittings

For trade sizes through ½ in. circuit conductors have OCP max 20A

For circuit conductors trade sizes ¾ through 1 ¼, OCP maximum 60 A

Listed LFMC required

2727

250.118(6) Listed LFMC

For circuit conductors trade sizes ¾ through 1¼, OCP maximum 60 A with no smaller LFMC in the path

Combined length not more than 6 ft

Where installed for flexibility, EGC required

Unlisted type LFMC is not suitable for grounding

350.6 requires LFMC to be listed

28

Page 15: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

15

250.118(7) Flexible Metallic Tubing

Fittings must be listed

Circuit conductors to have not more than 20 A overcurrent protection

Combined length of ground-fault path with FMC and LFMC is not more than 6 ft

2929

250.118(8) Type AC Cable

Armor of Type AC cable as per 320.108

Listed AC cable has a bonding conductor under armor

Armor and bonding conductor equals ground path

3030

Page 16: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

16

250.118(9) Type MI Cable

The copper sheath of mineral-insulated, metal sheathed cable

31

250.118(9) Terminating Single-Conductor Type MI Cable

32

Page 17: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

17

250.118(10) Type MC Cable

Type MC cable that provides an effective ground-fault current path by:◦ An insulated or bare equipment grounding

conductor in compliance with 250.118(1), or◦ The combined metallic sheath and uninsulated

grounding/bonding conductor of interlocked metal tape-type MC cable, or◦ The metallic sheath or combined sheath and

grounding conductor of smooth or corrugated tube Type MC cable

33

250.118(10) Type MC Cable

Interlocked and corrugated tube Type MC cables

Three types of Type MC cable is made:

Interlocked armor

Smooth tube

Corrugated tube

34

Copyright © Cengage Learning34

Page 18: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

18

250.118(10) Type MC Cable

“Traditional” interlocked armor Type MC cable –the armor is not suitable as an equipment grounding conductor

35

250.118(10) Type MC Cable

Interlocked armor Type MC cable with a 10 AWG aluminum grounding/bonding conductor in continuous contact with the armor

Combination is suitable as EGC

3636

Page 19: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

19

Fittings for Type MC Cable

Use fitting listed and appropriate for variation of Type MC cable being installed

Size and type of Type MC Cable Use in concrete Grounding (all listed fittings are) Dry and Wet Locations Use with Armored Cable

37

Product Markings for Fittings for Type MC Cable

The range of cable diameters and the type of cable sheath (corrugated, interlocking or smooth)

The material of the sheath (aluminum, copper or steel)

“Concrete-tight” if suitable for that use

38

Type of Metal-Clad Cable Abbreviation

Metal-clad interlocking armor cable MCI

Metal-clad interlocking armor ground cable MCI-A

Metal-clad continuous smooth sheath armor cable MCS

Page 20: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

20

Terminating Type MC Cable Having an Aluminum Equipment Grounding/Bonding Conductor

39Copyright © Cengage Learning

250.118(10) Type MC Cable

This construction of corrugated tube Type MC cable is suitable as an equipment grounding conductor, as a bare equipment grounding conductor if listed and identified.

40

Copyright © Cengage Learning40

Page 21: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

21

250.118(11) Cable Trays

Cable trays as permitted in 392.10 and 392.60

392.60 Grounding and Bonding. Metallic cable trays are permitted to be used as equipment grounding conductors if continuous maintenance and supervision ensure that qualified persons service the installed cable tray system and the cable tray complies with provisions of this section.

41

250.118(12) Cablebus

Cablebus framework as permitted in 370.60(1). “Cablebus framework, where bonded as required by Article 250, shall be permitted as the equipment grounding conductor for branch circuits and feeders.”

42

Page 22: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

22

Cable Tray

Page 23: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

23

250.118(13) Other Raceways

Other listed electrically continuous metal raceways and listed auxiliary gutters

4545

250.118(14) Surface Metal Raceways

Surface metal raceways is listed for grounding ---As per UL when installed per specifications

46

Page 24: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

24

250.119 Identification of Equipment Grounding Conductors

Permitted to be bare, covered or insulated

Covered or insulated conductors to have continuous finish that is either green or green with a yellow stripe

Not permitted to be used as grounded or ungrounded conductor

47

250.119 Exception # 1

Power limited Class 2 or Class 3 cables, power-limited fire alarm cables, or communications cables containing only circuits operating at less than 50 volts are permitted to use a conductor with green insulation for other than equipment grounding purposes

48

Page 25: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

25

250.119 Exception # 2

Flexible cords having an integral insulation and jacket without an equipment grounding conductor shall be permitted to have a continuous outer finish that is green. (Christmas Tree wire, extension cords)

Informational Note: An example of a flexible cord with Integral-type insulation is Type SPT-2, 2 conductor.

When looking at the two numbers for the zip cord, SPT-1 wire has an insulation thickness of 0.030″ and 18/2, SPT-2 has insulation that is 0.045″ thick.

49

250.119 Exception #3

Conductors with green insulation shall be permitted to be used as ungrounded signal conductors where installed between the output terminations of traffıc signal control and traffıc signal indicating heads.

Signaling circuits installed in accordance with this exception shall include an equipment grounding conductor in accordance with 250.118.

Wire-type equipment grounding conductors shall be bare or have insulation or covering that is green with one or more yellow stripes.

50

Page 26: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

26

250.119(A) Conductors 4 AWG and Larger

51

Copyright © Cengage Learning51

250.119(B) Multiconductor Cable

Mark at each end and at every point where the conductor is accessible. Identification of conductor by:

• Stripping the insulation or covering from the entire exposed length

• Coloring the exposed insulation or covering green

• Marking the exposed insulation green (tape) that encircles the conductor

52

Copyright © Cengage Learning52

Page 27: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

27

250.120(A) Raceway, Cable Trays, Cable Armor, Etc.

Use fittings for joints and terminations approved for use with the type of raceway or cable used

Make all connections and joints tight using suitable tools

53

Copyright © Cengage Learning53

250.120(B) Aluminum and Copper-Clad Aluminum Conductors

Bare or insulated are permitted

Bare conductors are not permitted in direct contact with masonry or the earth or where subject to corrosive conditions

Aluminum or copper-clad aluminum conductors are not permitted to be terminated within 18 in. of the earth

54

Page 28: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

28

250.120(C) EGCs Smaller Than #6 AWG

Protect from physical damage by a raceway or cable armor except where run in hollow spaces of walls or partitions where not subject to physical damage or protected from physical damage

55

Copyright © Cengage Learning55

250.121 Use of Equipment Grounding Conductor

An equipment grounding conductor (EGC) shall not be used as a grounding electrode conductor (GEC).

Except: See next slide

Sizing and installation requirements differ significantly.

56

Page 29: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

29

250.121 Use of Equipment Grounding Conductor

Exception: A wire-type equipment grounding conductor installed in compliance with 250.6 A (no objectionable currents) and the applicable requirements for both the equipment grounding conductor and the grounding electrode conductor in Parts II, III, and VI of this article shall be permitted to serve as both an equipment grounding Conductor and a grounding electrode conductor.

57

250.122 Size of Equipment Grounding Conductors

Size in accordance with Table 250.122

Not required to be larger than the circuit conductors

If cable tray, raceway or cable armor or sheath is used as the equipment grounding conductor, it must be installed to provide an effective ground-fault return path as provided in 250.4(A)(4) or (B)(5)

58

Page 30: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

30

Table 250.122 Minimum Size of Equipment Grounding Conductor for Grounding Raceway and Equipment

Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of Equipment, Conduit,

etc., Not Exceeding (Amperes)

Size (AWG or kcmil)

Copper Aluminum or Copper-Clad Aluminum

15 14 1220 12 1060 10 8100 8 6200 6 4400 3 1600 1 2/0800 1/0 3/0

5959

Increasing Size of EGC for Available Short-Circuit Current

The size of the equipment grounding conductor in Table 250.122 is shown to be the “Minimum Size.”

It may need to be increased in size using data such as Table P-32-382 from the Insulated Cable Engineers Association

Do not exceed thermal damage curve for equipment grounding conductor

The equipment grounding conductor must be large enough so it can carry the fault current delivered by the system until the overcurrent device opens

60

Page 31: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

31

Insulated Cable Engineers Association (ICEA) P-32-382

61

250.122(B) Increased in Size

If ungrounded conductors are increased in size, wire type equipment grounding conductors, where used, must be increased proportionately by circular mil area

62

Copyright © Cengage Learning62

Page 32: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

32

Common Applications

The phase conductors are typically increased in size for:◦ Excessive voltage drop◦ High ambient temperatures◦ More than 3 current-carrying conductors in a

raceway or cable

63

Example

200-ampere feeder installation◦ Normal size – 3/0 AWG copper◦ Installed size 300 kcmil for losses

300,000 ÷ 167,800 = 1.788 × bigger ◦ (167,800 = cm area of 3/0 conductor)

Required EGC Table 250.122 = 6 AWG Cm area of 6 AWG in Table 8, Chapter 9 = 26,240 26,240 × 1.788 = 46,917 cm Next standard size in Table 8 of Chapter 9 = 3 AWG

64

Page 33: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

33

250.122(C) Multiple Circuits

Size single equipment grounding conductor for multiple circuits based on the largest overcurrent device for contained conductors

6565

250.122(D) Motor Circuits

Equipment grounding conductors must be installed in accordance with (D)(1) or (D)(2)

(D)(1) The equipment grounding conductor is required to be not smaller than the size determined from Table 250.122 based on the rating of the branch circuit, short circuit and ground fault protection

BUT : The equipment grounding conductor is not required to be larger than the circuit conductors

66

Page 34: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

34

Motor Circuits

Size per Table 250.122 for the rating of branch-circuit, short-circuit, and ground-fault protective device

5 hp, 208-V 3-ph motor, Table 250.250 FLA = 16.7 amperes

16.7 A × 1.25 = 20.9 amperes (minimum conductor size)

Table 310.15(B)(16) = 12 AWG (25 amperes)

67

Example: Motor Circuits

Circuit breaker used as BC, SC and GF protection permitted to be 250% of FLA or 16.7 x 2.5 = 41.8 A

Next standard OC device is 45 A

Table 250.122, EGC required to be 10 AWG- BUT:

EGC permitted to be same as circuit conductors or 12 AWG

68

Page 35: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

35

250.122(D)(2) Motor Circuits

If the overcurrent device consists of an instantaneous trip circuit breaker or a motor short-circuit protector, the equipment grounding conductor is required to be sized not smaller than given by 250.122(A) using the maximum permitted rating of a dual-element time-delay fuse selected for branch-circuit short-circuit and ground-fault protection in accordance with 430.52(C)(1) Exception No. 1. (Next higher size)

69

Here’s How50 HP, 460-Volt, 3-Phase Motor

FLA from Table 430.250 = 65 A

Conductor minimum 125 % = 65 × 1.25 = 81 A

Select 4 AWG (85 A) Table 310.15(B)(16)

FLA × 175 % for BC, SC & GF = 65 × 1.75 = 113.8 A

Round up to 125 A overcurrent device

Select 6 AWG EGC from Table 250.122

70# 6 EGC with #4 ungrounded conductors 70

Page 36: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

36

250.112(F) Conductors in Parallel

If conductors are installed in parallel in multiple raceways as permitted in 310.10(H), equipment grounding conductors where used, are required to be installed as per 1-2 below.

71

250.122 (F) NEW (1) Parallel Conductors in Raceways….

If EGC conductors are installed in parallel in raceway or cable tray, a single wire type EGC may be installed based on 250.122. (raceways and cable trays may serve as the EGC as per 250.118 or 392.60(B)

If EGC conductors are installed in parallel in multiple raceways, the conductors are based on 250.122 and the full size is installed in each raceway. Raceways and cable trays may be used for the EGC.

72

Page 37: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

37

250.122 (F) NEW (2) Multiconductor Cables

(a) If multi-conductor cables are installed in parallel, the EGC conductors are also installed in parallel

(b) If multi-conductor cables are installed in a common raceway, a single EGC per .122 is permitted and connected in parallel with the cable EGC.

(c) EGC conductors in cable trays meet 392.(d) Where multi-conductor cables installed in

parallel, the EGC in each cable shall be based on .122 for the OCP of the total circuit

73

74Copyright © Cengage Learning

Page 38: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

38

Table 6-2

Overcurrent Protection

Number of 200-A Cables

in Parallel

Minimum Size of

Equipment Grounding

Conductor in Each Cable

Typical Size of Equipment

Grounding Conductor on Listed Cable

200 A 1 6 4

400 A 2 3 4

600 A 3 1 4

800 A 4 1/0 4

7575

250.122(G) Feeder Taps

Equipment grounding conductor for feeder taps sized from Table 250.122 based on supply OC protection

Not required to be larger than tap circuit conductors

76

Copyright © Cengage Learning76

Page 39: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

39

250.124 Equipment Grounding Conductor Continuity

First-make, last-break of equipment grounding conductor required for separable connectors

Not required for interlocked equipment

7777

250.126 Identification of Wiring Device Terminals

Green, not readily removable terminal screw with hex head

Green, hexagon terminal nut, not readily removable

Green pressure wire connector

78

Copyright © Cengage Learning78

Page 40: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

40

250.126 Identification of Wiring Device Terminals

FPN: One example of a symbol used to identify the termination point for an equipment grounding conductor

7979

80

Art 250 Part VII Methods of Equipment

Grounding

Page 41: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

41

Objectives:

Equipment grounding conductor connections

Methods permitted for non-grounding receptacle replacement and branch circuit extensions

Rules for equipment fastened in place or connected by permanent wiring methods

81

Objectives:

Grounding frames of ranges, dryers and associated equipment

Use of grounded circuit conductor for grounding equipment

Connecting receptacle grounding terminals Bonding of general-use snap switches Continuity and attachment of equipment

grounding conductors to boxes

82

Page 42: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

42

250.130 Equipment Grounding Conductor Connections

Equipment grounding conductor connections at separately derived systems made per 250.30(A)(1)

Equipment grounding conductor connections at service equipment made per 250.130(A) or (B)

Replacement of receptacles and branch-circuit extensions that do not have equipment grounding conductors permitted as in250.130(C) (this article)

83

250.130(A) For Grounded Systems

Bond the equipment grounding conductor to the grounded service conductor and the grounding electrode conductor

8484

Page 43: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

43

250.130(B) For Ungrounded Systems

Bond the equipment grounding conductor to the grounding electrode conductor

8585

250.130(C) Non-grounding Receptacle Replacement or Branch-Circuit Extensions

The equipment grounding conductor of a grounding-type receptacle or a branch-circuit extension is permitted to be connected to any of the following:

86

For ungrounded systems, the grounding terminal bar at the service

86

Page 44: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

44

250.130(C) Non-grounding Receptacle Replacement or Branch-Circuit Extensions

The equipment grounding conductor of a grounding-type receptacle or a branch-circuit extension is permitted to be connected to any of the following:

(1) Any accessible point on the grounding electrode system as described in 250.50

(2) Any accessible point on the grounding electrode conductor

(3) The equipment grounding terminal bar within the enclosure where the branch circuit for the receptacle or branch circuit originates

(4) An equipment grounding conductor that is part of another branch circuit that originates from the enclosure where the branch circuit for the receptacle or branch circuit originates

(5) For grounded systems, the grounded service conductor within the service equipment enclosure

(6) For ungrounded systems, the grounding terminal bar within the service equipment enclosure

87

88Copyright © Cengage Learning

Page 45: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

45

406.3(D) Replacement of Receptacles

Caution: Many types of equipment are required to be grounded by NEC rules or by manufacturer product listing

If equipment or appliance is required to be grounded, GFCI protection is not permitted in lieu of grounding

Must comply with NEC 110.3(B)

89

250.130(C) Branch-Circuit Extensions

Applies where the existing branch circuit does not contain an equipment grounding conductor

An equipment grounding conductor is installed back to point permitted in 250.130(C)

9090

Page 46: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

46

250.134 Equipment Fastened in Place

Unless grounded by connection to the grounded circuit conductor as permitted by 250.32, 250.140 and 250.142, the non-current-carrying parts of equipment, raceways and other enclosures, if grounded, must be grounded by one of the following methods.

91

250.134(A) Equipment Grounding Conductor Types

By connection to any of the equipment grounding conductors recognized by 250.118

92

Page 47: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

47

250.134(B) With Circuit Conductors

By connection to the equipment grounding conductor contained within the same raceway, cable or otherwise run with the circuit conductors

Exception: The equipment grounding conductor is permitted to be run separately as provided in 250.130(C).

93

250.136 Equipment Considered Effectively Grounded

Under the conditions specified in 250.136(A) and (B), the non-current-carrying metal parts of equipment is considered to be effectively grounded.

94

Page 48: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

48

250.136(A) Equipment Secured to Grounded Metal Supports

Electrical equipment secured to and in electrical contact with metal rack that is grounded by one of the means provided in 250.134

The structural metal frame of a building shall not be used as the required EGC.

95

250.140 Frames of Ranges and Clothes Dryers (New circuits)

Required to be grounded in accordance with 250.134 or 250.138

For appliances requiring a neutral or grounded conductor, a four-wire circuit is required

9696

Page 49: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

49

250.140 Frames of Ranges and Clothes Dryers (Existing circuits)

Permitted to ground to grounded circuit conductor if:

◦ The supply circuit is 120/240-V, 1-Ph, 3-wire or 208Y/120-V from a 3-Ph, 4-wire system

◦ (continued)

9797

250.140 Frames of Ranges and Clothes Dryers ( Exception- Existing circuits)

If no equipment grounding conductor is present in the in the outlet box, the frame of the appliance can be connected to the grounded conductor, if all of the following:

The grounded conductor is not smaller than 10 AWG copper or 8 AWG aluminum

The grounded conductor is insulated, or the grounded conductor is uninsulated and part of a Type SE cable and the branch circuit originates at the service (not a subpanel)

Grounding contacts of receptacles are bonded to the equipment

98

Page 50: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

50

250.140 Frames of Ranges and Clothes Dryers (Existing circuits)

Caution on relocating ranges or dryers where the circuit and receptacle is different from the appliance

A connection from the neutral to the frame is required for 3-wire branch circuits

• Isolate the neutral and connect the equipment grounding conductor to the frame if a 4-wire branch circuit is available

99

250.142 Use of Grounded Circuit Conductor for Grounding Equipment

Supply side Service / derived system – grounded circuit conductor permitted to ground equipment:

• On the supply side or within the enclosure of the ac service disconnecting means

• On the supply side, or within the enclosure, of the main disconnecting means for separate buildings as provided in 250.32(B)

• For separately derived systems as provided in 250.30(A)(1)

100

Page 51: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

51

250.142 Use of Grounded Circuit Conductor for Grounding Equipment

Load side: Not generally permitted to ground equipment by the grounded conductor. Except as permitted:

• 250.30(A)(1) for separately derived systems• 250.32(B) Exception at building or structure• The frames of ranges and dryers as provided in

250.140

101

250.142 Use of Grounded Circuit Conductor for Grounding Equipment

Exception No. 2 for meter enclosures:

• GFPE is not installed• Located immediately

adjacent to service• Grounded circuit

conductor not smaller than specified in 250.122

102

Copyright © Cengage Learning102

Page 52: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

52

250.146 Connecting Receptacle Grounding Terminal to Box

Generally required to connect bonding jumper from grounded box to receptacle

Size per 250.122

103

Copyright © Cengage Learning103

250.146(A) Surface-Mounted Box

Direct metal-to-metal contact and self-grounding type receptacles do not require a bonding jumper

At least one insulating washer must be removed

104

Copyright © Cengage Learning104

Page 53: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

53

250.146(A) Cover-Mounted Receptacles

Bonding jumper required unless the box and cover combination are listed for application

So far as can be determined, no such combinations are listed

105

Copyright © Cengage Learning105

250.146(A) Cover-Mounted Receptacles

A listed exposed work cover is permitted to be the grounding and bonding means when:

• The device is attached to the cover with at least two fasteners that are permanent (such as a rivet) or have a thread locking or screw locking meansand

• The cover mounting holes are located on a flat non-raised portion of the cover

106

Page 54: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

54

107Copyright © Cengage Learning

250.146(B) Contact Devices or Yokes

Bonding jumper not required for listed self-grounding devices

108

Copyright © Cengage Learning108

Page 55: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

55

250.146(C) Floor Boxes

Bonding jumper not required if the assembly is listed as providing satisfactory ground continuity

109

Copyright © Cengage Learning109

Copyright © Cengage Learning110

Page 56: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

56

250.146(D) Isolated Ground Receptacles

The isolated equipment grounding conductor is permitted to pass through one or more panelboards, boxes, wireways, or other enclosures without being connected to the enclosure. It must be terminated at nearest:

• Separately derived system (if the source)• Building disconnecting means• Service equipment

111

250.146(D) Isolated Receptacles

Identified by an orange triangle on its face

Equipment grounding terminal is isolated fromany metal yoke as well asfrom the center terminalfor the cover plate

IN: Use of an isolated ground does NOT dismiss the requirement for the grounding of the raceway or the outlet box

112

Copyright © Cengage Learning112

Page 57: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

57

250.148 Continuity and Attachment of Equipment Grounding Conductor to Boxes

If circuit conductors are spliced within a box or terminated on equipment within, or supported by a box, any equipment grounding conductor associated with the conductors must be spliced or joined in the box or to the box

113

Copyright © Cengage Learning113

250.148 Continuity and Attachment of Equipment Grounding Conductor to Boxes

Equipment grounding conductors associated with feeder conductors are permitted to pass through a pull box unbroken if the circuit conductors are not spliced within the box

114

Copyright © Cengage Learning114

Page 58: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

58

250.148(A) Connections

Connections and splices are required to comply with all the rules in 110.14(B) except that insulation is not required

The rules in 250.8 must also be complied with

115

250.148(B) Grounding Continuity

The removal of a wiring device or luminaire must not interfere with - or interrupt downstream grounding continuity

116

Copyright © Cengage Learning116

Page 59: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

59

250.148(C) Metal Boxes

A connection is required to the equipment grounding conductor by a ground screw that is used for no other purpose or by a listed grounding device

117

Copyright © Cengage Learning117

250.148(D) Nonmetallic Boxes

One or more equipment grounding conductor brought into the box must be arranged so a connection can be made to any fitting or device in the box that requires grounding

118

Copyright © Cengage Learning118

Page 60: MEA 2017 NEC Grounding and Bonding Part 4

11/13/2018

60

250.148(E) Solder

Connections depending on solder alone are not permitted

Make connections mechanically secure then solder

Equipment grounding conductors get hot when carrying current and can melt solder

119

Copyright © Cengage Learning119

End of Part 4 Grounding and Bonding

Questions ???

120


Recommended