3.1.0.18 Edition 04.10 Technical Information · GB www.kromschroeder.com For use as a measuring or restricting orifice Can be combined with valVario valves and regulators Air and gas flow rate diagrams to facilitate configuration Easy installation thanks to flanges with internal thread Replaceable aluminium washers for optimal adjustment to local operating conditions Measuring orifice VMO
Transcript
Page 1: Measuring orifice VMO - Docuthek

3.1.0.18 Edition 04.10Technical Information · GB

www.kromschroeder.com

• For use as a measuring or restricting orifice• Can be combined with valVario valves and regulators• Air and gas flow rate diagrams to facilitate configuration• Easy installation thanks to flanges with internal thread• Replaceable aluminium washers for optimal adjustment to local operating

conditions

Measuring orifice VMO

Page 2: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

2

t = To be continued

Table of contentsMeasuring orifice VMO . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31.1 Examples of application. . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.1.1 Self recuperative burner for direct heating systems . . . . . . 41.1.2 Continuous control with pneumatic ratio control system . . 4

2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Flow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63.1 VMO 110, VMO 115, VMO 120, VMO 125. . . . . . . . . . . . . 63.2 VMO 232, VMO 240, VMO 250 . . . . . . . . . . . . . . . . . . . 73.3 kV value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

4 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94.1 Type code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

5 Project planning information . . . . . . . . . . . . . . . . . . . . . 105.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105.2 Gas line connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116.1 Seal set VA 1 – 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116.2 Washer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

7 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127.1 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

7.1.1 VMO..R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137.1.2 VMO..N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137.1.3 VMO 240F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

8 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Page 3: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

3

1 Application

The valVario measuring orifice VMO is installed in gas control and safety systems, as well as in air systems used in indus-trial and commercial gas heat generation. It can serve as a restricting orifice when used in conjunction with valVario gas solenoid valves and gas control valves.The test points are located in the measuring orifice housing. The measuring orifice VMO is a good-value alternative in areas where no standardized measuring orifice is required. The replaceable washers with different hole sizes allow the orifice to be adjusted perfectly to the local operating conditions.

Shaft melting furnace

Incineration installation for thermal regenerative flue air purification

Page 4: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

4

1 .1 Examples of application1 .1 .1 Self recuperative burner for direct heating systems

EKOVAS..L EKOVMO

BVA+IC

M

LEH LEH

VMO VMO

GEH

Self recuperative burner in a direct heating system with an inductor for evacuating the flue gases from the furnace. The inductor generates a vacuum with a centrally positioned noz-zle and thus draws the flue gases out of the furnace chamber through the burner’s heat exchanger. The measuring orifices VMO are designed to record the gas and air flow rates.

1 .1 .2 Continuous control with pneumatic ratio control system

IC 20 + BVA

VAG

M

BVA

VAS ZIO VMO

EKO

With this type of control, the mixture setting can be maintained over a wide control range while at the same time preventing air deficiency. This type of control is used in melting furnaces in the aluminium industry or in regenerative incineration in-stallations in the environment industry, for example. Here, the measuring orifice VMO is designed to record the gas flow rate.

Application

Page 5: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

5

2 Function

Base plate

Plate bracket

WasherHousing

A plate bracket with a washer is placed in the VMO housing. There is a hole in the washer through which gas can flow. For replacing the washer, the base plate of the housing can be removed in order to pull the plate bracket and washer together out of the housing.

Page 6: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

6

3 Flow rateThe characteristic curves are measured at the test points at 15°C (59°F) for the individual washers.

3 .1 VMO 110, VMO 115, VMO 120, VMO 125

10 20 30 40 60 1001 2 3 5 81

2

3

4568

10

20

30

40506080

100

∆p [m

bar]

VMO 110, VMO 115

V' [m3/h (n)]1 2 3 4 6 10 20 30

0,8 1 2 3 4 6 10 20

60

30

1

2

3

0.8

1.2

1.62

2.53

4

8

10

16

2432

0.4

40

∆p [i

nch

WC

]

20

70 100 200 300 700 1000 200050 500V' [SCFH]

30001

4 m

m

6 m

m

5 m

m

10 20 30 40 60 1001 2 3 5 81

2

3

4568

10

20

30

40506080

100

∆p [m

bar]

V' [m3/h (n)]1 2 3 4 6 10 20 30

0,8 1 2 3 4 6 10 20

60

30

1

2

3

VMO 120

0.8

1.2

1.62

2.53

4

8

10

16

2432

0.4

40

∆p [i

nch

WC

]

20

70 100 200 300 700 1000 200050 500V' [SCFH]

30001

6 m

m8

mm

10 m

m12

mm

10 20 30 40 60 1001 2 3 5 81

2

3

4568

10

20

30

40506080

100

∆p [m

bar]

V' [m3/h (n)]1 2 3 4 6 10 20 30

0,8 1 2 3 4 6 10 20

60

30

1

2

3

VMO 125

0.8

1.2

1.62

2.53

4

8

10

16

2432

0.4

40

∆p [i

nch

WC

]

20

70 100 200 300 700 1000 200050 500V' [SCFH]

30001

10 m

m

16 m

m

14 m

m

12 m

m20

mm

18 m

m

Legend = natural gas (ρ = 0.80 kg/m3) = propane (ρ = 2.01 kg/m3) = air (ρ = 1.29 kg/m3)

Page 7: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

7

3 .2 VMO 232, VMO 240, VMO 250

100 200 300400 600 100010 20 30 50 801

2

3

4568

10

20

30

40506080

100

∆p [m

bar]

V' [m3/h (n)]10 20 30 40 60 100 200 300

8 10 20 30 40 60 100 200

600

300

1

2

3

VMO 232

0.8

1.2

1.62

2.53

4

8

10

16

2432

0.4

40

∆p [i

nch

WC

]

20

70 100 200 300 700 1000 200050 500V' [SCFH]

30001

16 m

m

24 m

m

20 m

m

100 200 300400 600 100010 20 30 50 801

2

3

4568

10

20

30

40506080

100

∆p [m

bar]

V' [m3/h (n)]10 20 30 40 60 100 200 300

8 10 20 30 40 60 100 200

600

300

1

2

3

VMO 240

0.8

1.2

1.62

2.53

4

8

10

16

2432

0.4

40

∆p [i

nch

WC

]

20

70 100 200 300 700 1000 200050 500V' [SCFH]

30001

24 m

m

20 m

m

32 m

m

28 m

m

16 m

m

100 200 300400 600 100010 20 30 50 801

2

3

4568

10

20

30

40506080

100

∆p [m

bar]

V' [m3/h (n)]10 20 30 40 60 100 200 300

8 10 20 30 40 60 100 200

600

300

1

2

3

VMO 250

0.8

1.2

1.62

2.53

4

8

10

16

2432

0.4

40

∆p [i

nch

WC

]

20

70 100 200 300 700 1000 200050 500V' [SCFH]

30001

34 m

m38

mm

32 m

m

Legend = natural gas (ρ = 0.80 kg/m3) = propane (ρ = 2.01 kg/m3) = air (ρ = 1.29 kg/m3)

Flow rate

Page 8: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

8

3 .3 kV valueThe measuring orifice is determined using the flow rate dia-gram or by calculation using the kv value.

Measuring orifi ce

Nominalfl ange size

Hole diameterWasher [mm] kV [m3/h]

VMO 110 DN 104 1.45 2.16 3.0

VMO 115 DN 154 1.45 2.16 3.0

VMO 120 DN 20

6 1.08 1.710 2.612 3.8

VMO 125 DN 25

10 2.512 3.714 5.216 6.918 9.020 12.2

VMO 232 DN 3216 7.220 10.524 12.5

VMO 240 DN 40

16 7.120 10.524 15.528 21.732 30.6

VMO 250 DN 5032 28.734 34.338 50.7

V· (n) = Flow rate (standard state) [m3/h]kV = Valve coefficient (see table)∆p = Pressure loss [bar]pa = Outlet pressure (absolute) [bar]

ρn = Density [kg/m3] (air 1.29/natural gas 0.80/propane 2.01/butane 2.71)

T = Medium temperature (absolute) [K]

ExampleWe want to find the hole diameter for the washer and the nominal flange diameter for a measuring orifice VMO.We have the maximum flow rate V· (n) max, the outlet pres-sure pa and the temperature T for the medium of natural gas.V· (n) max. = 37 m3/hpa = 30 mbar = 0.03 bar ⇒pa absolute = 0.03 bar + 1 bar = 1.03 bar∆pmax. = 0.01 bar (desired)T = 20°C ⇒ Tabsolute = 20 + 273 K = 293 K

kv = = 11.1 m3/h· 0.83 · 2930.01 · 1.03

37514

The measuring orifice with the next higher kv value is to be selected (see table): e.g. VMO 125 with a washer hole diam-eter of 20 mm.

Flow rate

Page 9: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

9

4 SelectionType R N F 05 M 04 05 06 08 10 12 14 16 18 20 24 28 32 34 38VMO 110 – – – – – – – – – – – – –VMO 115 – – – – – – – – – – – – –VMO 120 – – – – – – – – – – – –VMO 125 – – – – – – – – – –VMO 232 – – – – – – – – – – – – –VMO 240 – – – – – – – – – –VMO 250 – – – – – – – – – – – – –

= standard, = available

Order exampleVMO 115R05P05

4 .1 Type codeCode DescriptionVMO Measuring orifi ce1–2 Size–10–50

Without inlet and outlet fl angeNominal inlet and outlet diameter in DN

RNF

Rp internal threadNPT internal threadFlange to ISO 7005

05 pe max 500 mbarM With pressure test points04 – 38 Orifi ce diameter* in mm

* Delivery of washers with individual orifi ce diameter on request.

Page 10: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

10

5 Project planning information5 .1 Installation

Installation position: VMO can be installed as required.

When fitting to pressure regulator VAD, VAG or VAV, the base plate must be facing the same direction as the regulator body.

Installation position when using other valVario controls: VMO can be installed downstream of the valVario control or can be fitted as a standalone device in the pipe.

5 .2 Gas line connectionIn order to take accurate measurements of the pressure dif-ferential on the measuring orifice VMO, it must be ensured that there is an undisturbed flow of gas at the inlet and outlet for a distance of ≥ 5 × DN.

≥ 5 DN ≥ 5 DN

Page 11: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

11

6 Accessories6 .1 Seal set VA 1 – 3

A B

D

C

Scope of delivery:A 1 x double block seal,B 2 x O-rings (flange),C 2 x O-rings (pressure switch),D 2 x sealing rings (test point).

6 .2 WasherFor installing in the plate bracket of measuring orifice VMO. The hole diameter is engraved on the washer. Supply includ-ing the new seal for the base plate.

Hole diameter Order No.[mm] Suitable for VMO 1 Suitable for VMO 2

4 35457454 –5 35457455 –6 35457456 –8 35457457 –10 35457458 –12 35457459 –14 35457460 –16 35457461 3545746418 35457462 –20 35457463 3545746524 – 3545746628 – 3545746732 – 3545746834 – 3545746938 – 35457470xx* 34339103 34339104

* Hole diameter on request.

Page 12: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

12

7 Technical dataGas types: natural gas, LPG (gaseous), biologically pro-duced methane (max. 0.1 %-by-vol. H2S) or air; other gases on request.The gas must be dry in all conditions and must not contain condensate.Max. inlet pressure pe: max. 500 mbar (7.25 psig).Ambient temperature: -20 to +60°C (-4 to +140°F), no condensation permitted.Storage temperature: 0 to +40°C (-4 to +104°F).Housing: aluminium.Connection flanges with internal thread: Rp to ISO 7-1, NPT to ANSI/ASME.

Page 13: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

13

L1

D

H1

F

F

VMO..R, VMO..N

Technical data

7 .1 Dimensions

7 .1 .1 VMO . .R

TypeConnection

DimensionsWeight*

L1 F D H1Rp DN mm mm mm mm kg

VMO 110 3/8 10 30 15 62.7 66 0.245VMO 115 1/2 15 30 15 62.7 66 0.245VMO 120 3/4 20 30 23 62.7 66 0.245VMO 125 1 25 30 23 62.7 66 0.245VMO 225 1 25 34 29 88 82 0.505VMO 232 11/4 32 34 29 88 82 0.505VMO 240 11/2 40 34 29 88 82 0.505VMO 250 2 50 34 29 88 82 0.505

* Without fl anges and connection parts.

7 .1 .2 VMO . .N

TypeConnection

DimensionsWeight*

L1 F D H1Rp DN mm mm mm mm kg

VMO 110 3/8 10 30 15 62.7 66 0.245VMO 115 1/2 15 30 15 62.7 66 0.245VMO 120 3/4 20 30 23 62.7 66 0.245VMO 125 1 25 30 23 62.7 66 0.245VMO 225 1 25 34 29 88 82 0.505VMO 232 11/4 32 34 29 88 82 0.505VMO 240 11/2 40 34 29 88 82 0.505VMO 250 2 50 34 29 88 82 0.505

* Without fl anges and connection parts.

Page 14: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

14

L1

F

F

D

H1

VMO 240F

Technical data > Dimensions

7 .1 .3 VMO 240F

TypeConnection

DimensionsWeight*

L1 F D H1DN mm mm mm mm kg

VMO 240 40 34 66 88 82 0.505

* Without fl anges and connection parts.

Page 15: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

15

8 MaintenanceCheck for external tightness at least once per annum, at least twice per annum for operation with biologically produced methane.

Page 16: Measuring orifice VMO - Docuthek

VMO · Edition 04.10

16

Kromschröder, a product brand of the Elster Group

FeedbackFinally, we are offering you the opportunity to assess this “Technical Information (TI)” and to give us your opinion, so that we can improve our documents further and suit them to your needs.

ClarityFound information quicklySearched for a long timeDidn’t find informationWhat is missing?

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got “lost”No answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required)

Elster GmbH Postfach 2809 · 49018 Osnabrück Strotheweg 1 · 49504 Lotte (Büren) GermanyT +49 541 1214-0 F +49 541 1214-370 [email protected] www.elster.com

The current addresses of our international agents are available on the Internet:

www.kromschroeder.com SalesWe reserve the right to make technical modifications in the interests of progress.Copyright © 2007 – 2009 Elster Group All rights reserved.