Mechanical Design of Transmission Lines
Transcript
Page 1: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Mechanical Design of Transmission Lines

Page 2: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

General Considerations

Electrical Considerations for T.L. Design:• Low voltage drop • Minimum power loss for high efficiency of

power transmission.• The line should have sufficient current

carrying capacity so that the power can be transmitted without excessive voltage drop or overheating.

Page 3: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

• Conductivity of Conductor:R = ρ.L/A , orR = L/Ϭ. A

Where:L: Conductor length.A: Conductor cross sectional area.ρ: resistivityϬ: Conductivity (Ϭ= 1/ρ)

Page 4: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

• The conductor conductivity must be very highto reduce Conductor resistance R and hence

reduce losses

PL= 3 I2 .R

Page 5: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Mechanical Considerations for T.L. Design:

• The conductors and line supports should have sufficient mechanical strength:

- to withstand conductor weight, Conductor Tension and weather conditions (wind, ice).

- The Spans between the towers can be long.- Sag will be small.- Reducing the number and height of towers

and the number of insulators.

Page 6: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 7: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

• Heat expansion coefficient must be very small.

Rt = R0. (1 + α0 .t)

αt = α0/(1+ α0.t)

α t is the heat expansion coefficient at t.

Page 8: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

TYPES OF CONDUCTORS MATERIALS

Page 9: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

1- All Aluminum Conductors (AAC)

lowest cost – low mechanical strengthUsed for small span

Page 10: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 11: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 12: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

2- Aluminum Conductor Steel Reinforced (ACSR)

1- Steel strands2- Aluminum strands ACSR (26/7)

Page 13: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 14: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 15: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 16: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 17: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Advantages of ACSR

• High mechanical strength can be utilized by using spans of larger lengths.

• A reduction in the number of supports also include reduction in insulators and the risk of lines outage due to flash over or faults is reduced.

• losses are reduced due to larger diameter of conductor.

• High current carrying capacity.

Page 18: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

3- All Aluminum Alloy Conductor (AAAC)

األلمونيوم من سبيكة عن عبارة وهىحراريا المعالجة والسيليكون والماغنسيوم

- – ) الوزن ) مع متانة نسبة أكبر عالية متانة لهمما االبراج بين المسافة زيادة يمكن وبالتالى

التكلفة من يقللفى - الفقد من يقلل وبالتالى أقل مقاومة له

القدرةالسابق - النوع فى كما الجلفنة تآكل معرض غير

Page 19: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 20: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

4-Aluminum Conductor Alloy Reinforced (ACAR)

الصلب أسالك من المكون القلب استبدل وفيهااللمونيوم من سبيكة من أسالك من بقلب

Page 21: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Types of Supports

• Wooden Poles

• Reinforced Concrete Poles

• Steel Poles

• Lattice Structure Steel Towers

Page 22: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Wooden Poles

Page 23: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 24: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 25: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 26: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 27: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Reinforced Concrete Poles

Page 28: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 29: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 30: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Steel Poles

Page 31: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 32: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Lattice Structure Steel Towers

العالى الجهد فى استخداما :األكثر / الوزن متانة نسبة األعلى

عمرا األطولوالتجميع التركيب سهولة

عالية ميكانيكية قوى تتحمل

:يعيبهاآلخر - وقت من دهانها وجوب

خرسانية - اساسات تحتاجعالية – نقلها تكاليف

Page 33: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Types of Towers1- Suspension Tower

2- Tension Tower

3- Angle Tower

4- End Tower

Page 34: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

1- Suspension Tower

Page 35: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 36: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

2- Tension Tower

Page 37: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 38: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

3- Angle Tower

Page 39: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

4- End Tower

This type of towers exists in the beginning and at the end of the line which exposed to tension in one side.

Page 40: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

SAG AND TENSION CALCULATIONS

Page 41: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Sag of Transmission Lines

Sag of T.L depends on:

- Conductor weight.- Span length, - Tension in the conductor, T- Weather conditions (wind , ice).- Temperature.

Page 42: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Minimum Clearance between the ground and the conductor

kV C (m)0.4 5.511 5.533 6.066 6.2

132 6.2220 7.0400 8.4

Page 43: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.

Conductor Spacing

Spacing = (S )0.5 + V/150Where:S: Sag in meters.V: Line voltage in kV.

Page 44: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 45: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.
Page 46: Mechanical Design of Transmission Lines. General Considerations Electrical Considerations for T.L. Design: Low voltage drop Minimum power loss for high.