Date post: | 09-Sep-2018 |
Category: |
Documents |
Upload: | trinhduong |
View: | 514 times |
Download: | 12 times |
29
M E M S H I E L D 2 0 0 : I N C O M E R S U P T O 6 3 0 A , O U T G O I N G M C C B S U P T O 2 0 0 A
Memshield 200 panelboards are supplied with designated
incomer and ready for installation. Required single pole or
triple pole outgoing MCCBs should be specified separately
from the table. Main busbar short circuit rating 50kA for
1 second. Accessories including meter packs are listed on
page 31.
Complete panelboards listed below are supplied with a full
length door to prevent unauthorised access to main
incomer as well as outgoing MCCBs.
For details of larger pan-assemblies please contact
technical services.
TPN FACTORY FITTED WITH NO. OF WAYS PANELBOARD LIST NO. PAN ASSEMBLY LIST NO.INCOMING DEVICES630A LUGS 6 662PBLF 662PBLINT
12 1262PBLF 1262PBLINT18 1862PBLF 1862PBLINT
250A MCCB INCOMER 6 622PBBF 622PBBINT12 1222PBBF 1222PBBINT18 1822PBBF 1822PBBINT
400A MCCB INCOMER 6 642PBBF 642PBBINT12 1242PBBF 1242PBBINT18 1842PBBF 1842PBBINT
630A MCCB INCOMER 6 662PBBF 662PBBINT12 1262PBBF 1262PBBINT18 1862PBBF 1862PBBINT
250A CIRCUIT BREAKER SWITCH INCOMER 6 622PBMF 622PBMINT12 1222PBMF 1222PBMINT18 1822PBMF 1822PBMINT
400A CIRCUIT BREAKER SWITCH INCOMER 6 642PBMF 642PBMINT12 1242PBMF 1242PBMINT18 1842PBMF 1842PBMINT
630A CIRCUIT BREAKER SWITCH INCOMER 6 662PBMF 662PBMINT12 1262PBMF 1262PBMINT18 1862PBMF 1862PBMINT
250A FUSED COMBINATION SWITCH INCOMER 6 622PBS -SUITABLE MEM HRC FUSELINKS; SF4 TO SF6 12 1222PBS -
18 1822PBS -400A FUSED COMBINATION SWITCH INCOMER 6 642PBS -SUITABLE MEM HRC FUSELINKS; SF4 TO SF8 12 1242PBS -
18 1842PBS -630A FUSED COMBINATION SWITCH INCOMER 6 662PBS -SUITABLE MEM HRC FUSELINKS; SH8, SH9, 12 1262PBS -SH10 18 1862PBS -COVER PLATES WITH APERTURES FOR 6 - 62FPOUTGOING DEVICES 12 - 122FP
18 - 182FP
Memshield 2 P1-46 31/7/02 15:59 Page 32
OUTGOING MCCBS
Suitable for use in Memshield 200 panelboards. See page 8 for the complete
range of ‘F’ frame MCCBs and accessories.
TERMINAL CAPACITIES
The incoming copper cable sizes are recommended and not restricted to
the figures stated except where tunnel clamps are used.
All cable sizes refer to multi stranded cable.
M E M S H I E L D 2 M C C B P A N E L B O A R D S & P A N A S S E M B L I E SM E M S H I E L D 2 0 0 : I N C O M E R S U P T O 6 3 0 A , O U T G O I N G M C C B S U P T O 2 0 0 A
30
‘F FRAME THERMAL SHORT SHORTMCCBS RATING, A CIRCUIT CIRCUIT
BREAKING BREAKING CAPACITY CAPACITY25KA (Icu) 25KA (Icu)
SINGLE POLE TRIPLE POLELIST NO. LIST NO.
16 MFL161 MFL16320 MFL201 MFL20332 MFL321 MFL32340 MFL401 MFL40350 MFL501 MFL50363 MFL631 MFL63380 MFL801 MFL803100 MFL1001 MFL1003125 MFL1251 MFL1253160 MFL1601 MFL1603200 - MFL2003
Terminal shields MFTS1 MFTS3Blanking plates 32PBBP 32PBBPMoulded triple pole
blanking plates for
unused outgoing
ways. They are
moulded in three
sections to be
easily adapted to
fill single or double
pole spaces.
PANELBOARDS & PAN ASSEMBLIESRecommended Outgoing Incomer
incoming copper cables max (mm2) bolt size
cables (mm2)
Neutral up to 2 x 240 95 M14
Earth up to 185 25 M12
250A MCCB incomer 150 (max) - Tunnel clamp
400A MCCB incomer 240 (max) - Tunnel clamp
630A MCCB incomer 2 x 240 - M14
250A FCS incomer 185 - M10
400A FCS incomer 240 - M14
630A FCS incomer 2 x 240 - M20
630A lugs 2 x 240 - M14
OUTGOING MCCBsRecommended incoming Outgoing copper
copper cables (mm2) cables max (mm2)
16-200A - 120
Memshield 2 P1-46 31/7/02 15:59 Page 33
31
A C C E S S O R I E S
METER PACKS
Standard meter packs can be fitted at the top of each board and are available
across the range to enable monitoring of both current and voltage levels. Each
pack includes:- suitably calibrated ammeter and voltmeter allied to rotary,
phase selection switches, red/yellow/blue phase indicator lamps, drilled
replacement front plate to carry instrumentation, strenghtening cross piece to
take meter pack and rear cable cover for meter pack. Packs are supplied fully
wired with cable ties and loom to enable connection to circuit fuses and CTs,
which are part of the pack, and are fitted below the main incomer. A
replacement incoming cable shield is also supplied which has cable entries on
both left and right and will shroud the CTs and circuit fuses.
The ammeter allows the user to monitor current through the red, yellow or
blue phases.
It should be noted that, unless otherwise advised, a meter pack will be
supplied/fitted to match the full rating of the incomer. This may mean that the
ammeter scale is inappropriate if the incomer is derated. Contact the
customer services department for further information.
The voltmeter can monitor voltage across phases as follows:- blue/red,
yellow/blue, red/yellow, red/neutral, yellow/neutral, blue/neutral.
For information on alternative configurations of meter packs, such as digital
multi-function metering, the factory will be pleased to advise.
EXTENSION BOXES
Top or bottom mounting, each extension box is fitted with an adjustable depth,equipment mounting plate.
SUITABLE FOR PANELBOARDS WITH MEMSHIELD 200FOLLOWING INCOMER ARRANGEMENTS METER PACK LIST NO.250A MCCB/non auto MCCB incomer 22PBBMP250A FCS incomer 22PBSMP400A MCCB/non auto MCCB incomer 42PBBMP400A lugs -400A FCS incomer 42PBSMP630A MCCB/non auto MCCB incomer 62PBBMP630A lugs 62PBLMP630A FCS incomer 62PBSMP
EXTENSION BOX SUITABLE FORMEMSHIELD 200 PANELBOARDS
HEIGHT (mm) LIST No.
315 2PBEXS
630 2PBEXL
Memshield 2 P1-46 31/7/02 16:00 Page 34
M P S - M A K I N G P A N ET Y P I C A L A P P L I C A T I O N SThe Memshield 2 Modular Panelboard Systemcomplements our successful Memshield 2 - 125 and 200MCCB Panelboard ranges and fulfils the requirement forhigher rated more intricate systems.
Memshield 2 MPS provides the choice of creating asimple panelboard consisting only of an incoming moduleand outgoing module or a comprehensive panelboardsystem. This could incorporate horizontal busbar modulesthat allow you to extend the system with a wide variety ofoutgoing modules, ancillary devices, accessories and evenenables you to extend the system furtherin the future.
Memshield 2 MPS is essentially a
panelboard or switchboard in modular form.
By choosing from the wide variety of modules
you are able to create the ideal panelboard
system for your application. Memshield 2
will provide far more flexibility than
conventional panelboards and provide a
lower cost alternative to an equivalent
cubicle switchboard. Individual modules can
be conveniently delivered and easily handled
on site obviating the need for special access
arrangements or handling equipment.
Site assembly of modules is uncomplicated and
a panelboard system can be quickly produced.
Memshield 2 MPS can also be extended to
accommodate any future requirements.
In simple terms Memshield 2 MPS provides a
choice of:
■ Incoming modules, MCCB, fused
combination switch (FCS) and direct
connection options
■ Outgoing modules, MCCB, MCB and
FCS options
■ Horizontal busbar modules
■ Incoming / outgoing module accessories
■ Plinth modules
■ Ancillary modules including DIN - rail
enclosures and meter packs
■ Side cableway boxes
■ Connection kits
Modules offer IP3X protection and are formed of rust
protected sheet steel finished in light grey BS4800
Shade 00A07.
Completed systems can be wall / floor or frame mounted.
FORMS OF SEPARATION:
Form 2 Type 2 - All modules as standard.
Form 3B Type 2 - All modules when shields are fitted to
outgoing terminals of MCCB's.
Form 4 Type 2 - On selected modules as indicated in tables
from page 35.
MODULAR CONVENIENCE
■ All modules are 250mm deep.
■ All modules are 750mm wide.
■ Side cableway boxes are 250mm wide.
■ All module heights increase in increments of 150mm.
APPLICATIONMemshield 2 MPS has been designed with inherent flexibility and
installer convenience to accommodate the requirements of modern
commercial and industrial applications.
UNIQUE SOFTWARE ASSISTANCE
Memshield 2 MPS offers a simple and
effective software selection system -
Memshield 2 MPS Advantage. This
software can be used to produce layout
drawings, establish pricing, identify
dimensions and weights and also to
output a completed order form.
Memshield 2 MPS Advantage is
available on request.
5
2
9
32
Memshield 2 P1-46 1/8/02 9:35 Page 35
333
N E L B O A R D S S I M P L E
1
3
8
10
7
4
6
STANDARD MEMSHIELD 2 MPS CONFIGURATION
Front access, wall / floor mounting. Top or bottom
cable entry.
INCOMING MODULES
Choice of incoming devices up to 1250A; MCCB, fused
combination switch (FCS), direct connection. Contact us
for details of 1600/2000A ACB options.
HORIZONTAL BUSBAR MODULES
Enabling horizontal extension of the panelboard system.
OUTGOING MODULES
Choice of outgoing devices; MCCB, FCS, MCB.
TYPE B MCB DISTRIBUTION MODULE
ANCILLARY MODULES
MCB distribution modules.
Service centre modules.
Empty general purpose (filler) modules.
Meter pack modules (analogue or digital).
ACCESSORIES
Spare gland plates.
Spare side plates.
Fire barrier kits.
PLINTH MODULES
To form base of modular panelboard system.
SIDE CABLE WAY BOXES
Reducing the need for cable trunking.
CONNECTION KITS
To electrically connect all required modules.
6
7
8
9
10
2
3
4
5
1
Empty general purpose module
Busbar system, fully extendable
Outgoing modules, MCB, MCCB or FCS
Incoming modules, MCCB or FCS
Memshield 2 P1-46 1/8/02 9:36 Page 36
4
13 IP3X PROTECTION
High integrity protection against ingress of foreign bodies
when mounted against a wall
14 COMPLIANCE IEC/BSEN 60439-1
Full compliance with the latest British and
International standards.
15 ANALOGUE OR DIGITAL METERING MODULES
CAN BE MOUNTED ON THE LINE OR LOAD SIDE
OF THE INCOMING CIRCUIT
Enables monitoring of both voltage and current levels.
16 STANDARD MECHANICALLY INTERLOCKED
DUAL INCOMER OPTION
Ideal for applications with mains and standby supplies.
17 GENERAL PURPOSE MODULES TO HOUSE
ANCILLARY DEVICES
Sub - distribution equipment such as MCB’s and modular
devices can be incorporated within the Memshield 2
MPS system.
18 FULLY SHROUDED PAN ASSEMBLIES
To prevent contact with live parts.
19 REMOVABLE PAN ASSEMBLIES
For easier installation and wiring.
20 REMOVABLE GLAND PLATES
Prevents any chance of foreign bodies entering into
device sections.
21 BLANKING MODULES
Prevents access to unused live busbar stabs and blanks
off apertures in front plates.
22 ALL SWITCHED DEVICES HAVE POSITIVE
CONTACT INDICATION
True indication of device contact status.
23 C O V E R S A N D D O O R S F I T W I T H I N
ENCLOSURE DIMENSIONS
Allows adjacent mounting.
24 D O O R S C O V E R A L L D E V I C E S A N D
F R O N T COVER SCREWS
Device sections can be locked to prevent unwanted access.
25 REMOVABLE DOORS
Aid access in restricted working areas.
26 ROBUST CONSTRUCTION
Will provide many years of service in industrial and
commercial applications.
27 MODERN AESTHETIC APPEARANCE
Blends well with modern building design and existing
Memshield 2 products providing a complete circuit
protection solution.
MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE Technical Support: 0121 685 2001
M P S - M A K I N G A P P L I C A T I O N C L E A RF E A T U R E S A N D B E N E F I T S
34
1 UNIQUE ‘MEMSHIELD 2 MPS ADVANTAGE’
SOFTWARE PACKAGE
Aids layout designs, produces price, dimensions,
weights and parts list for ordering. Speeds up and
simplifies the process from conception to ordering with
high accuracy.
2 FCS OR MCCB INCOMERS AND OUTGOERS
To suit fusegear or circuit breaker applications.
3 INCOMERS UP TO 1250A
An alternative to switchboards where the main
incoming supply is up to 1250A. For larger incomer
ratings up to 2000A contact Technical Support.
4 OUTGOERS UP TO 800A
Standard Memshield 2 MPS can cope with large loads.
5 CHOICE OF 3 OR 4 POLE INCOMING AND
OUTGOING CIRCUITS
Standard 3 pole switching or 4 pole where switching of
neutral circuits is required.
6 S T A N D A R D S I D E , T O P A N D B O T T O M
CABLE ENTRY
To suit cabling requirements of any application
7 CHOICE OF SELF ASSEMBLY OR FACTORY
BUILT ASSEMBLIES
Memshield 2 MPS modules available via MEM
Preferred Stockists on a quick lead-time for
site assembly. Optional factory assembled unit
when required.
8 FORM 2 TYPE 2 AS STANDARD, FORM 3B TYPE 2
OR FORM 4 TYPE 2 OPTIONS
To meet high degrees of device separation required by
the installation.
9 HORIZONTAL BUSBAR MODULE EXTENSION
Enables many modules to be assembled meeting
applications traditionally met by distribution
switchboards. Also allows future expansion.
10 UP TO 50KA FOR 1 SECOND RATED BUSBARS
Matches many standard switchboard specification
requirements in a panelboard design.
Busbar ratings below 630A-35kA for 1 second, 630A
and above - 50kA for 1 second.
11 CHOICE OF 1 TO AN ALMOST INFINITE NUMBER
OF OUTGOING WAYS
Can meet the needs of small to large installations.
12 MODULAR CONVENIENCE
All modules are 250mm deep. All modules are 750mm
wide. Side cableway boxes are 250mm wide. All
module heights increase in increments of 150mm.
Memshield 2 P1-46 31/7/02 16:01 Page 37
5
1. SELECT INCOMING MODULE
2. SELECT OPTIONAL HORIZONTAL BUSBAR MODULE
INCOMING POLES No. OF SUITABLE SELECT HEIGHT OF MODULE+ LIST No. DEVICE WAYS INCOMING DEVICE HEIGHT OF RATING Ie When used DEVICE FROM PAGE CABLE BOX MM
as outgoing Cable box includedmodule with incoming module
INCOMING OR OUTGOING MCCB MODULES - FORM 4 TYPE 2250A/400A TPN/4P 1 250A J frame MCCB, 39 300+300 MS1JK4✝
400A K frame MCCB
630A/800A TPN/4P 1 L frame MCCB 39 450+300 MS1L4✝
1000A/1250A TPN/4P 1 M frame MCCB 39 600+450 MS1M4✝
1600/2000A TP/4P incoming ACB - contact us for details
DUAL MCCB INCOMING MODULE c/w MECHANICAL INTERLOCK250A 4P N/A J frame MCCB x 2 Supplied fitted 450+300 MSDJ4400A 4P N/A K frame MCCB x 2 Supplied fitted 450+300 MSDK4INCOMING OR OUTGOING FUSED COMBINATION SWITCH MODULES - FORM 4 TYPE 2 250A 4P 1 250A FCS Supplied fitted* 300+300 MS1S2004400A 4P 1 400A FCS Supplied fitted* 300+300 MS1S4004 630A 4P 1 630A FCS Supplied fitted* 450+300 MS1S6304800A 4P 1 800A FCS Supplied fitted* 450+300 MS1S8004INCOMING DIRECT CONNECTION MODULES 400A/800A TPN N/A 800A direct connection lugs Supplied fitted 300+300 MS800DC 1250A TPN N/A 1250A direct connection lugs Supplied fitted 300+450 MS1250DC
RATING Ie POLES WIDTH MM HEIGHT OF MODULE MM LIST NoHORIZONTAL BUSBAR MODULES400A 4P 750 150 MS4HC800A 4P 750 150 MS8HC1250A 4P 750 150 MS12HC
35
M P S - M A K I N G S E L E C T I O N S T R A I G H T F O R W A R DC R E A T E Y O U R I D E A L P A N E L B O A R D
SIMPLE SELECTION STEPS....
1 Select incoming module.
2 Select optional horizontal busbar module for future extension.
3 Select outgoing module or modules.
4 Select optional ancillary module or modules.
5 Select optional accessories.
6 Select optional plinth module or modules.
7 Select optional side cableway boxes.
8 Select circuit breaker incoming / outgoing devices.
9 Select fused combination switch incoming /outgoing devices.
10 Select connection sets for your choice of modules.
AVAILABLE AUGUST 2001.
* Select fuses from page 41.
✝ This module should not be used as an outgoing unit when installed below any
horizontal busbar module.
Memshield 2 P1-46 31/7/02 16:01 Page 38
36
M P S - M A K I N G S E L E C T I O N S T R A I G H T F O R W A R DC R E A T E Y O U R I D E A L P A N E L B O A R D
3. SELECT OUTGOING MODULE OR MODULES Module list nos. MS683K and MS1283KThese can accept J and K frame outgoing MCCB’s on the left hand side of thebusbars and F frame outgoing MCCB’s on the right. Coupling devices allow Fframe MCCB’s to be fitted on the left instead of J or K frame MCCB’s. Seediagram below table. These modules MUST be fitted with a side cableway boxwhen installing J and K frame MCCB’s or when using cables of 50mm2 and above.
Module list nos. MS2S2004, MS68F4 and MS108F4To provide cabling space on these modules a side cableway box must be fitted on both sides.
MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE
Technical Support: 0121 685 2001
MODULE POLES No OF SUITABLE SELECT HEIGHT OF LIST NORATING Ie WAYS OUTGOING DEVICE DEVICE MODULE+ HEIGHT
FROM OF CABLE BOX MMPAGE Cable box included
with outgoing module
OUTGOING MCCB PANELBOARD MODULES400A busbar system TPN 6 G frame MCCB up to 125A 39 600 MS643G400A busbar system TPN 12 G frame MCCB up to 125A 39 900 MS1243G630A busbar system TPN 6 F frame MCCB up to 200A 39 750 MS663F630A busbar system TPN 12 F frame MCCB up to 200A 39 1050 MS1263F800A busbar system TPN 6 F frame MCCB up to 200A 39 900 MS683K
J frame MCCB up to 250A 39
K frame MCCB up to 400A 39
800A busbar system TPN 12 F frame MCCB up to 200A 39 1200 MS1283KJ frame MCCB up to 250A 39
K frame MCCB up to 400A 39
OUTGOING MCCB PANELBOARD MODULES - FORM 4 TYPE 2400A busbar system TPN/4P 6 G frame MCCB up to 125A 39 750 MS64G4400A busbar system TPN/4P 10 G frame MCCB up to 125A 39 1200 MS104G4800A busbar system TPN/4P 6 F Frame MCCB up to 200A 39 750 MS68F4800A busbar system TPN/4P 10 F Frame MCCB up to 200A 39 1200 MS108F4200A per way TPN/4P 3 F frame MCCB up to 200A 39 300+150 MS3F4✝
250A per way TPN/4P 3 J frame MCCB up to 250A 39 300+300 MS3J4✝
400A per way TPN/4P 2 K frame MCCB up to 400A 39 300+300 MS2K4✝
OUTGOING FUSED COMBINATION SWITCH PANELBOARD MODULES - FORM 4 TYPE 2400A busbar system TPN/4P 6 100A FCS 41 750 MS64S1004400A busbar system TPN/4P 10 100A FCS 41 1200 MS104S1004800A busbar system TPN/4P 6 100A FCS 41 750 MS68S1004800A busbar system TPN/4P 10 100A FCS 41 1200 MS108S1004125A per way TPN/4P 2 125A FCS 41 450 MS2S1254250A per way TPN/4P 2 250A FCS 41 600 MS2S2004
Description List No.
Coupler to allow fitment of ‘F’ frame MCCB in ‘K’ frame MCCB space 4PBCUK
Coupler to allow fitment of ‘F’ frame MCCB in ‘J’ frame MCCB space 4PBCUJ
COUPLERSRequired when fitting ‘F’ frame MCCBs on the left side of module list nos. MS683Kand MS1283K - see diagram below. There are two types of coupler: the first allowsfitment of an ‘F’ frame MCCB in the ‘K’ frame space, the second allows fitment of an‘F’ frame into any ‘J’ frame space.
This arrangement allows outgoing devices to be fitted covering a range from 16A up to 400A.
‘J’ frame160 - 250A
‘K’ frame250 - 400A
(1 max)
F-frame
16 - 200A TP16 - 200A SP
To fit an ‘F’ frameMCCB use coupler
List No 4PBCUJ
To fit an ‘F’ frameMCCB use coupler
List No 4PBCUK
AVAILABLE AUGUST 2001
✝ Only suitable for mounting above horizontal busbar modules.
Memshield 2 P1-46 31/7/02 16:01 Page 39
37
C R E A T E Y O U R I D E A L P A N E L B O A R D
4. SELECT OPTIONAL ANCILLARY MODULE OR MODULES
TYPE OF POLES No OF SUITABLE OUTGOING SELECT HEIGHT OF LIST NoMODULE WAYS DEVICE DEVICE MODULE
FROM PAGE MM MCB DISTRIBUTION MODULES100A busbar system c/w 100A DP main lugs incomer
Type A SPN 10 Type B, C & D MCB’s & RCBO’s 40 300 MS10AType A SPN 16 Type B, C & D MCB’s & RCBO’s 40 300 MS16AType A SPN 2 x 10 Type B, C & D MCB’s & RCBO’s 40 300 MS10A2200A busbar system c/w 200A TP main lugs incomer
Type B TPN 8 Type B, C & D MCB’s & RCBO’s 40 600 MS8BType B TPN 16 Type B, C & D MCB’s & RCBO’s 40 900 MS16BType B TPN 2 x 8 Type B, C & D MCB’s & RCBO’s 40 600 MS8B2Type B TPN 2 x 12 Type B, C & D MCB’s & RCBO’s 40 750 MS12B2SERVICE CENTRE MODULES DIN - rail N/A 2 x 12 MCB’s & RCBO’s+DIN mounting devices 40 300 MS12D2DIN - rail N/A 12 MCB’s & RCBO’s+DIN mounting devices 40 300 MS12DDIN - rail N/A 18 MCB’s & RCBO’s+DIN mounting devices 40 300 MS18DType A + DIN - rail N/A 10+15 MCB’s & RCBO’s+DIN mounting devices 40 300 MS10A15DType A + DIN - rail N/A 16+9 MCB’s & RCBO’s+DIN mounting devices 40 300 MS16A9DMODULE HEIGHT OF LIST NoDESCRIPTION MODULE MMEMPTY GENERAL PURPOSE MODULESTo house equipment or use as filler box 150 MSEM1To house equipment or use as filler box 300 MSEM2To house equipment or use as filler box 450 MSEM3To house equipment or use as filler box 600 MSEM4TYPE OF DESCRIPTION OF HEIGHT OF LIST NoMODULE MEASUREMENT / RATING MODULE MMMETER PACK MODULES Require CT module of corresponding ratingAnalogue Vm+SS, Amm+SS / 250A 150 MSMA250Analogue Vm+SS, Amm + SS / 400A 150 MSMA400Analogue Vm+SS, Amm + SS / 800A 150 MSMA800Analogue Vm+SS, Amm + SS / 1250A 150 MSMA1250Analogue Vm+SS, 3 Amm / 400A 150 MSM3A400Analogue Vm+SS, 3 Amm / 800A 150 MSM3A800Analogue Vm+SS, 3 Amm / 1250A 150 MSM3A1250Digital Up to 1250A, phase Amps, phase Volts, line Volts, per phase PF, 150 MSMD
per phase kW, 3-phase PF, 3-phase kW, frequency, import kWH.
CURRENT TRANSFORMER MODULES Required for meter pack module of corresponding rating250A CT module 150 MS250CT400A CT module 150 MS400CT800A CT module 150 MS800CT1250A CT module 150 MS1250CT
Memshield 2 P1-46 31/7/02 16:02 Page 40
38
DESCRIPTION TO SUIT MODULE TO SUIT MODULE LIST No WIDTH MM HEIGHT MM
INCOMING / OUTGOING MODULE ACCESSORIESFire barrier kit 750 MSHIK Spare steel gland plate, gauge 2.5mm 750 MSGPSReplacement aluminium gland plate, gauge 5mm 750 MSGPASpare steel side plate 150 MSSP1Spare steel side plate 300 MSSP2Spare steel side plate 450 MSSP3Spare steel side plate 600 MSSP4Spare steel side plate 750 MSSP5Spare steel side plate 900 MSSP6Spare steel side plate 1050 MSSP7Spare steel side plate 1200 MSSP8Door cylinder lock AMDLIP3X kit; required to plug fixing holes
when freestanding. One kit per MSIP3Kmodule/cableway box of 300mm
high & above.
DESCRIPTION TO SUIT MODULE TO SUIT MODULE LIST No WIDTH MM HEIGHT MM
PLINTH MODULES150mm high plinth 750 MSMP150mm high plinth 250 MSCP
5. SELECT OPTIONAL ACCESSORIES
6. SELECT OPTIONAL PLINTH MODULE OR MODULES
7. SELECT OPTIONAL SIDE CABLEWAY BOXES
DESCRIPTION TO SUIT MODULE HEIGHT OF LIST NoWIDTH MM MODULE MM
SIDE CABLEWAY BOXESReplaces cable trunking 150 MSVCB1 and increases cabling space 300 MSVCB2
450 MSVCB3600 MSVCB4750 MSVCB5900 MSVCB61050 MSVCB7 1200 MSVCB8
SIDE CABLEWAY ACCESSORIESFire barrier kit, top or bottom 250 MSCBIKFire barrier kit, side 150 MSVIK1Fire barrier kit, side 300 MSVIK2 Fire barrier kit, side 450 MSVIK3Fire barrier kit, side 600 MSVIK4Fire barrier kit, side 750 MSVIK5Fire barrier kit, side 900 MSVIK6Fire barrier kit, side 1050 MSVIK7Fire barrier kit, side 1200 MSVIK8 Spare steel gland plate, gauge 2.5mm 250 MSCBGPSReplacement aluminium gland plate, gauge 5mm 250 MSCBGPA
MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE
Technical Support: 0121 685 2001
M P S - M A K I N G S E L E C T I O N S T R A I G H T F O R W A R DC R E A T E Y O U R I D E A L P A N E L B O A R D
Memshield 2 P1-46 31/7/02 16:02 Page 41
39
M P S - M A K I N G P R O T E C T I O N E L E M E N T A R YS E L E C T I N C O M I N G A N D O U T G O I N G D E V I C E S
BREAKING CAP. Icu (400/440V AC) CONDITIONAL SHORT CIRCUIT RATING, Icc36kA 36kA 65kA 65kA 35kA 35kA
RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.TP (Adj) TPSN (Adj) TP (Hi Adj) TPSN (Hi Adj) TP SWITCH 4P SWITCH
250 MKLA2503 MKLA2504 MKHA2503 MKHA2504320 MKLA3203 MKLA3204 MKHA3203 MKHA3204 MKN3203400 MKLA4003 MKLA4004 MKHA4003 MKHA4004 MKN4003 MKN4004
BREAKING CAP. Icu (400/440V AC) SHORT CIRCUIT MAKING CAPACITY, Icm50kA 50kA 50kA 50kA 15kA 15kA
RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.TP (Adj) TPSN (Adj) TP (Elec) TPSN (Elec) TP SWITCH 4P SWITCH
400 MLLA4003 MLLA4004630 MLLA6303 MLLA6304 MLLS6303 MLLS6304 MLN6303 MLN6304800 MLLA8003 MLLA8004 MLLS8003 MLLS8004 MLN8003 MLN8004
BREAKING CAP. Icu (440V AC) SHORT CIRCUIT MAKING CAPACITY, Icm65kA 65kA 32kA 32kA
LIST NO. LIST NO. LIST NO. LIST NO.TP (Elec) TPSN (Elec) TP SWITCH 4P SWITCH
1000 MMLS10003 MMLS100041250 MMLS12503 MMLS12504 MMN12503 MMN12504
FRAME SIZE LIST NO. NO. OF POLESG Frame PBGBP1 SP
F Frame 32PBBPJ Frame 34PBBJK Frame 34PBBPK
TP (Adjustableto fit SP, DP, TP)
J FRAME MCCB’s INCOMING / OUTGOING, CIRCUIT BREAKER SWITCHES INCOMING, 160A-250A
K FRAME MCCB’s INCOMING / OUTGOING, CIRCUIT BREAKER SWITCHES INCOMING, 250A-400A
L FRAME MCCB’s INCOMING / OUTGOING, CIRCUIT BREAKER SWITCHES INCOMING, 400A-800A
For information on the full range of MCCB’s please refer to page 4.
8a. SELECT CIRCUIT BREAKER INCOMING / OUTGOING DEVICES
BREAKING CAP. Icu (SP 220/240V AC, TP, TPSN 380/415V AC)16kA 16kA 22kA 25kA 25kA 25kA
RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.SP TP SP TP TP(Hi Adj) TPSN (Hi Adj)
16 MGL161 MGL163 MGH161 MGH163 20 MGL201 MGL203 MGH201 MGH203 MGHAT253 MGHAT25432 MGL321 MGL323 MGH321 MGH323 MGHAT323 MGHAT32440 MGL401 MGL403 MGH401 MGH403 MGHAT453 MGHAT45450 MGL501 MGL503 MGH501 MGH50363 MGL631 MGL633 MGH631 MGH633 MGHAT633 MGHAT63480 MGL801 MGL803 MGH801 MGH803 MGHAT853 MGHAT854100 MGL1001 MGL1003 MGH1001 MGH1003125 MGL1251 MGL1253 MGH1253 MGHAT1253 MGHAT1254
G FRAME MCCB’s 16A-125A OUTGOING
M FRAME MCCB’s INCOMING / OUTGOING, CIRCUIT BREAKER SWITCHES INCOMING, 1000A-1250A
MCCB BLANKING PLATE
BREAKING CAP. Icu (SP 220/240V AC, TP, TPSN 400/440V AC)25kA 25kA 25kA 25kA 45kA 65kA 65kA
RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. SP TP TP(Adj) FP(Adj) TP(Hi Break) TP(Hi Adj) TPSN (Hi Adj)
16 MFL161 MFL163 MFH16320 MFL201 MFL203 MFH20332 MFL321 MFL323 MFH32340 MFL401 MFL403 MFH40350 MFL501 MFL503 MFLA503 MFLA504 MFH503 MFHA503 MFHA50463 MFL631 MFL633 MFLA633 MFLA634 MFH633 MFHA633 MFHA63480 MFL801 MFL803 MFLA803 MFLA804 MFH803 MFHA803 MFHA804100 MFL1001 MFL1003 MFLA1003 MFLA1004 MFH1003 MFHA1003 MFHA1004125 MFL1251 MFL1253 MFLA1253 MFLA1254 MFH1253 MFHA1253 MFHA1254160 MFL1601 MFL1603 MFLA1603 MFLA1604 MFH1603 MFHA1603 MFHA1604200 MFL2003 MFH2003
F FRAME MCCB’s 16A-200A OUTGOING
BREAKING CAP. Icu (400/440V AC) CONDITIONAL SHORT CIRCUIT RATING, Icc36kA 36kA 65kA 65kA 35kA 35kA
RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.TP (Adj) TPSN (Adj) TP (Hi Adj) TPSN (Hi Adj) TP SWITCH 4P SWITCH
160 MJLA1603 MJLA1604 MJHA1603 MJHA1604200 MJLA2003 MJLA2004 MJHA2003 MJHA2004250 MJLA2503 MJLA2504 MJHA2503 MJHA2504 MJN2503 MJN2504
RATING A
Memshield 2 P1-46 31/7/02 16:03 Page 42
M P S - M A K I N G P R O T E C T I O N E L E M E N T A R YS E L E C T I N C O M I N G A N D O U T G O I N G D E V I C E S
40
RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.SP SPSN* DP TP 4P*
1 MBH101 MBH101N MBH201 MBH301 MBH4012 MBH102 MBH102N MBH202 MBH302 MBH4024 MBH104 MBH104N MBH204 MBH304 MBH4046 MBH106 MBH106N MBH206 MBH306 MBH4068 MBH108 MBH108N MBH208 MBH308 MBH40810 MBH110 MBH110N MBH210 MBH310 MBH41013 MBH113 MBH113N MBH213 MBH313 MBH41316 MBH116 MBH116N MBH216 MBH316 MBH41620 MBH120 MBH120N MBH220 MBH320 MBH42025 MBH125 MBH125N MBH225 MBH325 MBH42532 MBH132 MBH132N MBH232 MBH332 MBH43240 MBH140 MBH140N MBH240 MBH340 MBH44050 MBH150 MBH150N MBH250 MBH350 MBH45063 MBH163 MBH163N MBH263 MBH363 MBH463
RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.SP SPSN* DP TP 4P*
1 MCH101 MCH101N MCH201 MCH301 MCH4012 MCH102 MCH102N MCH202 MCH302 MCH4024 MCH104 MCH104N MCH204 MCH304 MCH4046 MCH106 MCH106N MCH206 MCH306 MCH4068 MCH108 MCH108N MCH208 MCH308 MCH40810 MCH110 MCH110N MCH210 MCH310 MCH41013 MCH113 MCH113N MCH213 MCH313 MCH41316 MCH116 MCH116N MCH216 MCH316 MCH41620 MCH120 MCH120N MCH220 MCH320 MCH42025 MCH125 MCH125N MCH225 MCH325 MCH42532 MCH132 MCH132N MCH232 MCH332 MCH43240 MCH140 MCH140N MCH240 MCH340 MCH44050 MCH150 MCH150N MCH250 MCH350 MCH45063 MCH163 MCH163N MCH263 MCH363 MCH463
RATING A LIST NO. LIST NO. LIST NO. LIST NO. LIST NO.SP SPSN* DP TP 4P*
1 MDH101 MDH101N MDH201 MDH301 MDH4012 MDH102 MDH102N MDH202 MDH302 MDH4024 MDH104 MDH104N MDH204 MDH304 MDH4046 MDH106 MDH106N MDH206 MDH306 MDH4068 MDH108 MDH108N MDH208 MDH308 MDH40810 MDH110 MDH110N MDH210 MDH310 MDH41013 MDH113 MDH113N MDH213 MDH313 MDH41316 MDH116 MDH116N MDH216 MDH316 MDH41620 MDH120 MDH120N MDH220 MDH320 MDH42025 MDH125 MDH125N MDH225 MDH325 MDH42532 MDH132 MDH132N MDH232 MDH332 MDH43240 MDL140** MDL140N** MDL240** MDL340** MDL440**50 MDL150** MDL150N** MDL250** MDL350** MDL450**63 MDL163** MDL163N** MDL263** MDL363** MDL463**
MCB BLANKING PLATE LIST No. MBP
MINIATURE CIRCUIT BREAKERS TYPE B 10kA
MINIATURE CIRCUIT BREAKERS TYPE C 10kA
MINIATURE CIRCUIT BREAKERS TYPE D 10kA
MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE
Technical Support: 0121 685 2001
8b. SELECT CIRCUIT BREAKER INCOMING / OUTGOING DEVICES/RCBO’s
RATING A SENSITIVITY COMPLETE FIELD FITTABLEmA RCBO SUFFIX RC POD LIST NO.
1 - 63 A 30mA R30 MR301 - 63 A 100mA R100 MR1001 - 63 A 100mA time delayed R100D MR100D1 - 63 A 300mA time delayed R300D MR300D
RCBO’s
For complete factory assembled RCBO's add one of the following suffixes to any standard
SP or SPSN MCB or choose a field fittable RC pod to add to your MCB on site.
For information on the full range of
MCB's and accessories please refer to
page 48.
*Suitable for DIN Modules Only. ** 6kA breaking capacity
Memshield 2 P1-46 31/7/02 16:03 Page 43
41
S E L E C T I N C O M I N G A N D O U T G O I N G D E V I C E S
MAX. FCS SUITABLE HRC MOTOR SUITABLE NO. OF POLES FCS LIST NO.RATING A FUSE CURRENT RATING A HRC FUSE
RATING A LIST NO.100 16 16SB3
20 20SB325 25SB332 32SB340 40SB450 50SB4
TPN 100S3N100
63 63SB4 TPSN 100S3SN100
80 80SO100 100SO100 125 100SOM125100 160 100SOM160
125 80 80SD5100 100SD5125 125SD6
TPN 125S3N125
100 160 100SD5M160TPSN 125S3SN125
100 200 100SD5M200250 125 125SF6
160 160SF6TPN 250S3N250
200 200SF6250 250SF7 TPSN 250S3SN250
200 315 200SF6M315400 250 250SF7 FCS
315 315SF7 TPSN SUPPLIED
400 400SF8 FITTED630 250 250SG7
315 315SG7
FCS400 400SH8SUPPLIED450 450SH9
500 500SH9TPSN
FITTED
560 560SH9630 630SH9
800 250 250SG7315 315SG7400 400SH8
FCS450 450SH9SUPPLIED500 500SH9 TPSN
560 560SH9 FITTED630 630SH9710 710SH10800 800SH10
9. SELECT FUSED COMBINATION SWITCHINCOMING / OUTGOING DEVICES
FUSED COMBINATION SWITCHES (FCS) 100 - 800A
INCOMING/OUTGOING
FCS modules of 400A, 630A and 800A are supplied with FCS devices
already fitted as standard.
Fuselinks must be ordered separately in each case by selecting from the table below.
Memshield 2 P1-46 31/7/02 16:04 Page 44
M P S - M A K I N G I N S T A L L A T I O N E A S I E RC O N N E C T I N G M O D U L E S
42
10. SELECT CONNECTION SETS FOR YOUR CHOICE OF MODULES
TO CONNECT MCCB / FCS / DIRECT CONNECTION INCOMING
MODULE TO MCCB / FCS OUTGOING MODULE
MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE
Technical Support: 0121 685 2001
MCC
B / F
CSOU
TGOI
NG
MOD
ULE
LIS
T N
O.
FCS INCOMING MODULE LIST NO.
MS2S1254 MS2S2004 MS1S2004 MS1S4004 MS1S6304 MS1S8004INCOMINGMODULE TOP OR TOP OR
BOTTOM TOP BOTTOM TOP BOTTOM TOP BOTTOMMOUNTING BOTTOM BOTTOMPOSITIONMS643G MSCLS2003G MSCLS2004G MSCLS4003G MSCLS4004GMS1243G MSCLS2003G MSCLS2004G MSCLS4003G MSCLS4004GMS663F MSCLS2003F MSCLS2004F MSCLS4003F MSCLS4004F MSCLS8003F MSCLS8004FMS1263F MSCLS2003F MSCLS2004F MSCLS4003F MSCLS4004F MSCLS8003F MSCLS8004FMS683K MSCLS4003F MSCLS8003F MSCLS8003FMS1283K MSCLS4003F MSCLS8003F MSCLS8003F
TOP OR BOTTOM TOP OR BOTTOM TOP OR BOTTOM TOP OR BOTTOMMS64S1004 MSCL400BB MSCL400BB MSCLS200S100 MSCLS400S100MS104S1004 MSCL400BB MSCL400BB MSCLS200S100 MSCLS400S100MS68S1004 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS108S1004 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS2S1254 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS2S2004 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS64G4 MSCL400BB MSCL400BB MSCLS200S100 MSCLS400S100MS104G4 MSCL400BB MSCL400BB MSCLS200S100 MSCLS400S100MS68F4 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100MS108F4 Qty 2 MSCL400BB Qty 2 MSCL400BB MSCLS200S100 MSCLS400S100 MSCLS800S100 MSCLS800S100
MCC
B / F
CSOU
TGOI
NG
MOD
ULE
LIS
T N
O.
MCCB / DIRECT CONNECTION INCOMING MODULE LIST NO.
MS1JK4 MS1L4 MS800DCTOP OR BOTTOM TOP OR BOTTOMTOP OR BOTTOM *Bottom mounted only *Bottom mounted only**Top mounted only
TP J FRAME MCCB 4P J FRAME MCCB TP K FRAME MCCB 4P K FRAME MCCB TP L FRAME MCCB 4P L FRAME MCCBINCOMER INCOMER INCOMER INCOMER INCOMER INCOMER
MS643G MSCL3JG MSCL4JG MSCL3KG MSCL4KG MSCLDCGMS1243G MSCL3JG MSCL4JG MSCL3KG MSCL4KG MSCLDCGMS663F MSCL3JF MSCL4JF MSCL3KF MSCL4KF MSCLLF MSCLLF MSCLLFMS1263F MSCL3JF MSCL4JF MSCL3KF MSCL4KF MSCLLF MSCLLF MSCLLFMS683K MSCLLF * MSCLLF ** MSCLLF *MS1283K MSCLLF * MSCLLF ** MSCLLF *
TP OR 4P TP OR 4P TP OR 4PMS64S1004 MSCLJS100 MSCLKS100 MSCL8CDS100MS104S1004 MSCLJS100 MSCLKS100 MSCL8CDS100MS68S1004 MSCLLS100 MSCL8CDS100MS108S1004 MSCLLS100 MSCL8CDS100MS2S1254 MSCLLS100 MSCL8CDS100MS2S2004 MSCLLS100 MSCL8CDS100MS64G4 MSCLJS100 MSCLKS100 MSCL8CDS100MS104G4 MSCLJS100 MSCLKS100 MSCL8CDS100MS68F4 MSCLLS100 MSCL8CDS100MS108F4 MSCLLS100 MSCL8CDS100
INCOMINGMODULE
MOUNTINGPOSITION
Memshield 2 P1-46 31/7/02 16:04 Page 45
C O N N E C T I N G M O D U L E S
43
TO CONNECT MCCB INCOMING / OUTGOING MODULE TO
HORIZONTAL BUSBAR MODULE
HORI
ZONT
AL B
USBA
R M
ODUL
E LI
ST N
O
INCOMING / OUTGOING MCCB MODULE LIST NO.
MS643G MS1243G MS663F MS1263F MS3F4 MS3J4ONE ONE
CONNECTION CONNECTIONSET REQUIRED SET REQUIREDPER OUTGOING PER OUTGOING
WAY WAY
MS4HC MSCLHCG MSCLHCG MSCLHCF MSCLHCF MSCLHCF4 MSCLHCJ4
MS8HC MSCLHCG MSCLHCG MSCLHCF MSCLHCF MSCLHCF4 MSCLHCJ4
MS12HC MSCLHCG MSCLHCG MSCLHCF MSCLHCF MSCLHCF4 MSCLHCJ4
HORI
ZONT
AL B
USBA
R M
ODUL
E LI
ST N
O
INCOMING / OUTGOING MCCB MODULE LIST NO.
MS2K4 MS64G4 MS104G4 MS68F4 MS108F4ONE
CONNECTIONSET REQUIREDPER OUTGOING
WAY
MS4HC MSCLHCK4 MSCLHCS100 MSCLHCS100 MSCLHCS100 MSCLHCS100
MS8HC MSCLHCK4 MSCLHCS100 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100
MS12HC MSCLHCK4 MSCLHCS100 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100
HORI
ZONT
AL B
USBA
R M
ODUL
E LI
ST N
O
INCOMING / OUTGOING MCCB MODULE LIST NO.
MS683K MS1283K MS1JK4 MS1L4 MS1M4
WHERE J WHERE KFRAME FRAME
MCCB TO MCCB TOBE FITTED BE FITTED
MS4HC MSCLHCF MSCLHCF MSCLHCJ4 MSCLHCK4 MSCLHCL4 MSCLHCM4
MS8HC MSCLHCF MSCLHCF MSCLHCJ4 MSCLHCK4 MSCLHCL4 MSCLHCM4
MS12HC MSCLHCF MSCLHCF MSCLHCJ4 MSCLHCK4 MSCLHCL4 MSCLHCM4
Memshield 2 P1-46 1/8/02 10:19 Page 46
M P S - M A K I N G I N S T A L L A T I O N E A S I E RC O N N E C T I N G M O D U L E S
44
TO CONNECT FCS INCOMING / OUTGOING MODULE
TO HORIZONTAL BUSBAR MODULE
TO CONNECT INCOMING DIRECT CONNECTION MODULE
TO HORIZONTAL BUSBAR MODULE
TO CONNECT CT MODULE TO HORIZONTAL BUSBAR MODULE
INCOMING / OUTGOING FCS MODULE LIST No.
MS64S1004 MS104S1004 MS68S1004 MS108S1004 MS2S1254
MS4HC MSCLHCS100 MSCLHCS100 MSCLHCS100
MS8HC MSCLHCS100 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100
MS12HC MSCLHCS100 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100 Qty 2 MSCLHCS100HORI
ZONT
AL B
USBA
RM
ODUL
E LI
ST N
O.
MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE
Technical Support: 0121 685 2001
INCOMING / OUTGOING FCS MODULE LIST No.
MS2S2004 MS1S2004 MS1S4004 MS1S6304 MS1S8004
MS4HC MSCLHCS100 MSCLHCS200 MSCLHCS400
MS8HC Qty 2 MSCLHCS100 MSCLHCS200 MSCLHCS400 MSCLHCS800 MSCLHCS800
MS12HC Qty 2 MSCLHCS100 MSCLHCS200 MSCLHCS400 MSCLHCS800 MSCLHCS800HORI
ZONT
AL B
USBA
RM
ODUL
E LI
ST N
O.
CT MODULE LIST NO.
MS250CT MS400CT MS800CT MS1250CT
MS4HC MSCLCT400HC MSCLCT400HC
MS8HC MSCLCT400HC MSCLCT400HC MSCLCT800HC
MS12HC MSCLCT400HC MSCLCT400HC MSCLCT800HC MSCLCT1250HCHORI
ZONT
AL B
USBA
RM
ODUL
E LI
ST N
O.
DIRECT CONNECTION MODULE
MS800DC MS1250DC
MS4HC MSCLHC8DC MSCLHC12DC
MS8HC MSCLHC8DC MSCLHC12DC
MS12HC MSCLHC8DC MSCLHC12DCHORI
ZONT
AL B
USBA
RM
ODUL
E LI
ST N
O.
Memshield 2 P47-91 1/8/02 10:00 Page 1
45
C O N N E C T I N G M O D U L E S
CT MODULE LIST NO.MS250CT MS400CT MS800CT MS1250CT
MS643G MSCLCT400G MSCLCT400GMS1243G MSCLCT400G MSCLCT400GMS663F MSCLCT400F MSCLCT800FMS1263F MSCLCT400F MSCLCT800FMS683K MSCLCT800FMS1283K MSCLCT800FMS64S1004 MSCLCT400S100 MSCLCT400S100MS104S1004 MSCLCT400S100 MSCLCT400S100MS68S1004 MSCLCT800S1008MS108S1004 MSCLCT800S1008MS2S1254 MSCLCT400S100 MSCLCT400S100 MSCLCT800S1008MS2S2004 MSCLCT800S1008MS64G4 MSCLCT400S100 MSCLCT400S100MS104G4 MSCLCT400S100 MSCLCT400S100MS68F4 MSCLCT800S1008MS108F4 MSCLCT800S1008MS1S2004 MSCLS200CT250MS1S4004 MSCLS400CT400MS1S6304 MSCLS800CT800MS1S8004 MSCLS800CT800MS1JK4 TP MCCB = MSCL3JCT250 TP MCCB = MSCL3KCT400MS1JK4 4P MCCB = MSCL4JCT250 4P MCCB = MSCL4KCT400MS1L4 MSCLLCT800MS1M4 3P MCCB = MSCL3MCT1250MS1M4 4P MCCB = MSCL4MCT1250MS800DC MSCL8DCCT800 MSCL8DCCT800MS1250DC MSCL3MCT1250
MCC
B / F
CS /
DIRE
CT C
ONN
ECTI
ON IN
COM
ING
/ OU
TGOI
NG
MOD
ULE
LIS
T N
O.
TO CONNECT MCCB / FCS / DIRECT CONNECTION INCOMING / OUTGOING
MODULE TO CT MODULE
TO CONNECT HORIZONTAL BUSBAR MODULE TO HORIZONTAL BUSBAR MODULE
To connect horizontal busbar modules across a side cableway space between modules add
suffix VCB1 to the connection set list number from the table, e.g. MSCL400BBVCB1.
This provides additional connections to bridge the space.
400A horizontal busbar modules require 1 off MSCL400BBVCB1.
800/1250A horizontal busbar modules require 2 off MSCL400BBVCB1.
In each case a 150mm high side cableway box is required list no MSVCB1 which must
be fitted between appropriate height side cableway boxes.
Cabling cannot pass vertically through this connection.
HORIZONTAL BUSBAR MODULE LIST NO.
MS4HC MS8HC MS12HC
MS4HC MSCL400BB
MS8HC QTY 2 MSCL400BB
MS12HC QTY 2 MSCL400BBHORI
ZONT
AL B
USBA
RM
ODUL
E LI
ST N
O.
Memshield 2 P47-91 1/8/02 10:01 Page 2
46
M P S - M A K I N G L A Y O U T S U N C O M P L I C A T E DL A Y O U T G R I D
LAYOUT GRID SCALE 1/16 OF ACTUAL SIZE
The Grid below will help you plan a Memshield 2 Modular Panelboard System up to three
modules wide including a side cable way box at each end and up to 2400mm high.
All modules are 250mm deep.
All modules are 750mm wide.
Side cableway boxes are 250mm wide.
All module heights increase in increments of 150mm.
750mm
250mm
2400m
m
150m
m
Memshield 2 P47-91 1/8/02 10:01 Page 3
47
T E R M I N A L C A P A C I T I E S
MEMSHIELD 2 MPS - MAKING PANELBOARDS SIMPLE
Technical Support: 0121 685 2001
R/Y/B Phase Neutral Phase EarthTunnel Clamp Stud Tunnel Clamp Stud Stud
G frame 16A - 125A 70mm2 side fed - 70mm2 - M8/M10F frame 16A - 200A 120mm2 side fed - - M8 M8/M10J frame 160A - 250A 150mm2 - 150mm2 - M10K frame 250A - 400A 240mm2 - 240mm2 - M10L frame 400A - 800A - M12 - M12 M10M frame 1000A - 1250A - M12 - M12 M10
R/Y/B Phase Neutral Phase EarthFCS Tunnel Clamp Stud Tunnel Clamp Stud StudSize 2 100A - M6 - M6 M10Size 3 160A - M8 - M8 M10Size 4 200/250A - M10 - M10 M10Size 5 400A - M14 - M14 M10Size 6 630/800A - M12 - M12 M10DIRECT CABLE R/Y/B Phase Neutral Phase EarthCONNECTION Tunnel Clamp Stud Tunnel Clamp Stud Stud400A lugs - M16 - M16 M10800A lugs - M16 - M16 M101250A lugs - M16 - M16 M10
INCOMING CABLE TERMINATION SIZE (MAX)
R/Y/B Phase Neutral Phase EarthTunnel Clamp Stud Tunnel Clamp Stud Tunnel Clamp Stud
G frame 16A - 125A 70mm2 - 70mm2 - 70mm2 -F frame 16A - 200A 120mm2 - 70mm2 M8 70mm2 -J frame 160A - 250A 150mm2 - 150mm2 - - M8/M10K frame 250A - 400A 240mm2 - 240mm2 - - M8/M10L frame 400A - 800A - M12 - - - M10M frame 1000A - 1250A - - - - - -
R/Y/B Phase Neutral Phase EarthFCS Tunnel Clamp Stud Tunnel Clamp Stud Tunnel Clamp StudSizes 2 100A - M6 - M6 - M6Sizes 3 160A - M8 - M8 - M8Sizes 4 200/250A - M10 - M10 - M8Sizes 5 400A - M14 - M14 - M10Sizes 6 630/800A - M12 - M12 - M10DIRECT CABLE R/Y/B Phase Neutral Phase EarthCONNECTION Tunnel Clamp Stud Tunnel Clamp Stud Tunnel Clamp Stud400A lugs - - - - - -800A lugs - - - - - -1250A lugs - - - - - -
OUTGOING CABLE TERMINATION SIZE (MAX)
DEVICE TYPEMCCB
DEVICE TYPEMCCB
NOTES
G and F frame distribution modules have the following Earth and Neutral Tunnel
Terminations - 6 x 25mm2, 25 x 50mm2, 6 x 70mm2 (plus 2 M8 stud adapters for larger
cable F frame only).
K frame distribution Modules have the following Earth and Neutral Tunnel
Terminations - 6 x 25mm2, 25 x 50mm2, 6 x 70mm2, 4 x 150mm2 and a M12 stud
for 240mm2.
Memshield 2 P47-91 1/8/02 10:01 Page 4
2
T H E U L T I M A T E M C B
48
■ Technologically advanced range of
MCB based distribution equipment
■ Incorporates many unique features
of benefit to all of our customers
■ Satisfies the diverse requirements of
the user, contractor, specifier, OEM
and distributor
■ Incorporates the revolutionary
RCBO
■ Distribution boards accept both
MCBs to BSEN60898 & BS1361
HRC fuses
■ Memshield 2 MCBs and ancillary
devices can be DIN-rail mounted and
connected with comb busbar
Memshield 2 type A and type B
distribution boards of equal width can be
vertically stacked and interlinked to
provide additional outgoing ways.
SP HRC fuse carriers can be fitted to
any Memshield 2 distribution board and
incorporate an MEM BS1361 HRC
fuse fitted plus facility for a spare fuse
contained in the carrier.
Memshield 2 devices are suitable
for DIN-rail mounting and can be
inter-connected with comb busbar.
Memshield 2 MCBs are rated at 10kA
Icn to BSEN60898 & BSEN60947-2.
MCBs comply with Lloyds Register of
Shipping. MCBs and RCCBs have
positive contact indication.REVOLUTIONARY...
The unique RCBO pod can be
fitted to any SP or SPSN MCB
offering hundreds of possible
combinations of circuit and
earth fault protection.
A wide choice of incoming
devices are available including
direct connection, switch-
disconnector, MCB, MCCB,
RCCB or fused combination
switch.Top or bottom cable entry.
Memshield 2 P47-91 1/8/02 10:01 Page 5
49
D I S T R I B U T I O N S Y S T E M
11129
5
4
1613
10
8
36
7
2
1
15
14
9
6
5
4
2
1
8
7
11
3
12
10
THE FEATURE PACKED, REVOLUTIONARY MEMSHIELD 2 RCBO
1 Earth fault sensitivity pod can be fitted to any standard SP or SPSN
Memshield MCB
2 Unique revolutionary design means that an RCBO within a SP (18mm) module
can be achieved
3 SP configuration allows a far greater number of devices to be fitted in a
distribution board
4 Use of the standard Memshield 2 MCB means that there are hundreds of possible
RCBO combinations providing an incredible choice
5 Standard features of the MCB are retained but with the added flexibility of earth
fault protection
6 Memshield 2 RCBOs are suitable for use in any Memshield 2 distribution board
or ideally suited to OEM applications
7 Four choices of sensitivity to meet the requirements of any installation
8 Time delay versions available to allow correct function of any downstream
residual current devices
9 The Memshield 2 RCBO complies with BSEN61009
10 An RCBO can be ordered simply by selecting the most suitable MCB for an
application and then adding the appropriate sensitivity suffix
11 The all new British design developed using state-of-the-art CAD equipment gives
you the assurance of quality, safety and performance
12 Earth fault protection is maintained even if the neutral connection is lost
13 Version suitable for use on 110V 50/60Hz systems
THE FEATURE PACKED MEMSHIELD 2 MCB
1 Any SP or SPSN MCB can be factory or site fitted with an RCBO pod providing
hundreds of possible combinations allowing you even more flexibility
2 Magnetic Type characteristics to BSEN60898 B, C, D for wide choice
of applications
3 Foolproof positive contact indication gives you the assurance of isolation function
4 Breaking capacities of up to 10kA (BSEN60898) allow increased
installation opportunities
5 Five pole configurations (SP, SPSN, DP, TP, with FP) and 14 current ratings (1,
2, 4, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63A) for increased flexibility
6 Quality trip free mechanism prevents MCBs from being held ‘ON’
7 Optional padlock dolly for positive locking ‘ON’ or ‘OFF’
8 High performance current limiting design for safer installations
9 Optional screw and terminal shields for full shrouding of MCBs
10 All new ‘easy fit’ British design using state-of-the-art CAD equipment gives you
the assurance of quality, safety and performance
11 Generous, wire-in, wire-out, box type terminals for cables up to 25mm2, and fork
type comb busbar facilities on line and load side for OEM installations
12 Terminals clamp cable and fork type comb busbar simultaneously
13 Mounting on standard 35mm DIN-rail to BS5584/EN50 022 for individual and
OEM installations
14 Finger protected combination head screws to increase safety and allow
easier installation
15 Optional rear connectors to allow cables up to 50mm2 to be terminated where
space is limited
16 Thermally calibrated to 40ºC with 50ºC option to cover a wider range of
ambient temperatures
Memshield 2 P47-91 1/8/02 10:02 Page 6
1 Easy fit, DIN-rail mounting, incoming devices simply slot
into place easing installation
2 HRC fuse modules can be fitted in place of outgoing MCBs
increasing flexibility
3 Attractive two-tone grey finish over rust protected steel
enclosure for lasting durability
4 Main earth stud allows earth to be terminated inside or
outside the enclosure
5 Type A distribution boards comply with BS5486:Pt 12 & 13
and BSEN60439-3; type B with BS5486:Pt 12 and
BSEN60439-3
6 Heavy guage removable gland plates are provided top and
bottom for ease of installation
7 Shrouded neutral bar for increased safety
8 Fully shrouded busbar for increased safety
9 Busbar design eliminates risk of ‘hot spots’
10 Earth and neutral bars can accommodate up to
25mm2
cables
11 Modular sizes and removable gland plates allow distribution
boards to be stacked vertically
12 Optional connecting kits can be used to electrically connect
two distribution boards together vertically. TPN boards can
also be linked horizontally (not shown)
13 Covers fit within enclosure dimensions allowing
adjacent mounting
50
M E M S H I E L D 2 M C B D I S T R I B U T I O N S Y S T E MM E M S H I E L D 2 F E A T U R E S A N D B E N E F I T S
4
1011
18
15
8
2
24
23
26
16
7
21
20
9
125
3
27
65
THE FEATURE PACKED MEMSHIELD 2 TYPE A SPN DISTRIBUTION BOARD
13
14
Memshield 2 P47-91 1/8/02 10:02 Page 7
14 The door can be closed when MCBs are padlocked ‘ON’
or ‘OFF’ to increase safety (not shown)
15 Unique blanking modules can be used to blank off
unused outgoing ways. The blanking module is the
profile of an MCB, so that it shrouds the busbar stab as
well for increased safety
16 Generous cable space is provided. Space behind the pan
assembly, on type A boards, allows bottom entry/exit
of cables
17 Optional adjustable flush mounting kits provide the
solution even where the mounting surface is uneven;
non-adjustable on type A (not shown)
18 All distribution boards have dished keyhole mounting
slots for easy surface installation even when the
mounting surface is uneven
19 Optional busbar connecting blocks for type A boards
allow the installer to fit DIN-rail mounted control
devices onto the pan assembly providing protection and
control for additional flexibility with economy and
compact size (not shown)
20 Pan assembles are fully removable to ease installation
21 Neutral links can be removed
for testing purposes
22 An optional clean earth kit can
be site installed for computer
installations - standard on TPN
distribution boards (not shown)
23 The door, when locked, covers
all devices and front cover
screws to prevent unwanted
access (not shown)
24 Doors can be site fitted with
either door barrel lock kits or
padlocking kits. Padlocking
kits allow the user to
standardise on all padlocking
arrangements for an
installation (not shown)
25 All incomers (except direct
connection) have positive
contact indication
26 Distribution boards can be fitted
with a wide range of extension
boxes including glazed door
types so the user can easily
identify the status of the fitted
control devices (not shown)
27 Modern styling allows the
range to discreetly blend in
with both industrial and
commercial premises
28 Dual earth and neutral bars on TPN distribution boards
for ease of installation
29 TPN and TPSN incoming device options include a 125A
fuse combination switch to give a compact solution to
discrimination problems at high current levels
30 TPN incomer options allow the fitting of MCCBs from
16A up to 200A
31 Split load, dual tariff and double pole distribution
boards are available as standard
32 Double pole boards can be fitted with SPSN MCBs
and SPSN RCBOs
33 Top entry distribution boards available.
51
THE FEATURE PACKED MEMSHIELD 2 TYPE B TPN DISTRIBUTION BOARD
23 14
13
27
7
5
21125
4
2
3
266
1831
11
20915
8
2810
2930
24
Memshield 2 P47-91 1/8/02 10:02 Page 8
52
M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SS T A N D A R D S P N T Y P E A A N D D P V E R S I O N S - T Y P E A F O R M A T
Standard SPN type A distribution boards are available in six
sizes with a choice of 2, 4, 7, 10, 13, or 16 outgoing ways. DP
versions of type A distribution boards are also available having
5 or 8 DP outgoing ways. A wide range of incomers can be
fitted to allow for the flexibility needed in modern installations.
Split load and dual tariff SPN type A distribution boards are
available with up to 19 outgoing ways.
They comply fully with BS5486:Pt 12 & 13 and BSEN60439-3.
INCOMING DEVICES
100A lugs; 100A SPSN switch-disconnector; 100A SPSN
RCCB. For full range of SPSN RCCBs suitable for use as
incoming devices see page 65.
Please consult our Technical Services department for details of
an even wider choice of incoming devices.
OUTGOING DEVICES
For type A distribution boards: 1-63A Memshield 2 SP MCBs.
Types B, C, D, 10kA to BSEN60898; 5-45A fuse carriers,
16kA to BS1361; 1-63A 18mm SP RCBOs
For double pole distribution boards: 1-63A Memshield 2 SPSN
or DP MCBs. Types B, C, D, 10kA to BSEN60898; 1-63A
36mm SPSN RCBOs.
FEATURES
Distribution boards of equal width can be stacked vertically
without any other accessories. They can be electrically
connected to give more outgoing ways by using a connector kit
(see page 60).
Memshield modular control devices can be fitted by using a
busbar block kit to adapt the busbar (see page 60). AM13,
AMSL64/37 and AMDT74 distribution boards can be mounted
on top of any type B distribution board. A clean earth kit can
be used for computer installations (see page 60).
DOUBLE POLE DISTRIBUTION BOARDS
Memshield 2 double pole distribution boards have been
developed for specialist applications.
They allow for single pole and switched neutral MCBs to be
fitted on all outgoing circuits which is necessary for the control
of circuits situated in hazardous areas.
SPSN or DP MCBs and SPSN RCBOs can be fitted.
For 3 phase, 4 wire systems please contact us for details of our
four pole range of Memshield 2 distribution boards.
A-SELECT DISTRIBUTION BOARD:
DESCRIPTION LIST NO.
2 way SPN type A AM2
4 way SPN type A AM4
7 way SPN type A AM7
10 way SPN type A AM10
13 way SPN type A AM13
16 way SPN type A AM16
5 way DP type A format AM5D
8 way DP type A format AM8D
B-SELECT 100A INCOMING DEVICE:
Incoming device supplied separately to distribution board.
DESCRIPTION LIST NO.
SPSN switch-disconnector (isolator) MS1001N
DP lugs (direct connection) MBT1002
SPSN 30mA RCCB AM100HE
SPSN 100mA RCCB AM100ME
SPSN 300mA RCCB AM100LE
SPSN 100mA time delayed RCCB AM100MET
SPSN 300mA time delayed RCCB AM100LET
C-EXAMPLE:
AM4 + MS1001N = 4 way SPN distribution board with 100A
switch-disconnector.
Use pages 61-64 to select outgoing devices and accessories.
Memshield 2 P47-91 1/8/02 10:02 Page 9
SPLIT LOAD DISTRIBUTION BOARDS FITTED WITH MAIN 100A
SWITCH-DISCONNECTOR, AND 80A, 30MA RCCB.
DESCRIPTION LIST NO.
10 way; 4 ways RCCB protected AMSL64
10 way; 7 ways RCCB protected AMSL37
13 way; 4 ways RCCB protected AMSL94
13 way; 7 ways RCCB protected AMSL67
13 way; 10 ways RCCB protected AMSL310
19 way; 10 ways RCCB protected AMSL910
N.B. AMSL910 = 2 row unit
DUAL TARIFF DISTRIBUTION BOARDS FITTED WITH 2
INCOMING SWITCH-DISCONNECTORS*
DESCRIPTION LIST NO.
7 + 4 way AMDT74
10 + 4 way AMDT104
7 + 7 way AMDT77
*Please consult our Technical Services department for other incomer
types, or configurations.
Example:
AMSL37 = 10 way SPN distribution board with main 100A switch
disconnector, and 7 RCCB protected ways.
CABLE CAPACITIES mm2
LUGS 50
SWITCH-DISCONNECTOR 50
RCCB 50
MCBs 25
EARTH BARS 25
NEUTRAL BARS 25
53
S P L I T L O A D & D U A L T A R I F F S P N T Y P E A
■ Clean earth kit available for all type Adistribution boards.
■ Any number of type A distribution boardscan be vertically stacked and electricallyinter-connected with a connector kit.
■ Consult us for even more incomer options.
■ Modular control/command devices can befitted into any SPN type A distributionboard by using the unique busbar block kit.See page 60 for details.
Memshield 2 P47-91 1/8/02 10:03 Page 10
54
M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SS T A N D A R D 1 2 5 A T P N T Y P E B
A - SELECT 125A DISTRIBUTION BOARD:
DESCRIPTION LIST NO.
4 way TPN type B BM41
6 way TPN type B BM61
8 way TPN type B BM81
12 way TPN type B BM121
16 way TPN type B BM161
24 way TPN type B BM242
B - SELECT 100/125A INCOMING DEVICE:
Incoming device supplied separately to distribution board.
DESCRIPTION LIST NO.
100A TP switch-disconnector (isolator) BMS1003
100A SPSN switch-disconnector (isolator) BMS1001N4*
125A TP switch-disconnector (isolator) BMS1253
100A TPSN switch-disconnector (isolator) BMS1004
100A TP lugs (direct connection) BMBT1003
100A TPSN 30mA RCCB BMR30
100A TPSN 100mA RCCB BMR100**
100A TPSN 300mA RCCB BMR300
100A TPSN 300mA RCCB BMR300Twith time delay
63A TP Type C MCB BMCH363
100A TP switch-disconnector BMCC1003feeding 100A TP AC1 contactor c/w
control circuit fuse & terminal block,
housed in extension box.
Top entry distribution boards with factory fitted 125A TP switch-
disconnector- add suffix T125 to list no. e.g. BM41T125.Not applicable to 24 way board; BM242.
*TPN to SPN conversion kit included.
**Not suitable for BM242.
C - EXAMPLE:
BM61 + BMS1003 = 6 way TPN distribution board with 100A
switch-disconnector.
Use pages 61 - 64 to select outgoing devices & accessories.
Standard 125A and 200A TPN type B distribution boards are
available with a choice of 4, 6, 8, 12, 16 or 24 outgoing ways.
A wide range of incomers can be fitted to allow for the
flexibility needed in modern installations. They comply fully
with BS5486 : Pt 12 and BSEN60439-3.
INCOMING DEVICES, 125A MAX
100A lugs; 100A SPSN, TP, or TPSN switch-disconnectors,
125A TP switch-disconnectors, 100A TPSN RCCBs; 63A TP
MCB. Please consult our Technical Services department for
details of other incoming device types.
INCOMING DEVICES, 200A
200A lugs; 200A SPSN, or TP switch-disconnectors; and any
TP ‘F’ frame MCCB up to 200A. All standard 100A
distribution board incomers can also be fitted.
OUTGOING DEVICES
1-63A Memshield 2 SP, DP and TP MCBs Types B, C, D, 10kA
to BSEN60898; 5-45A fuse carriers, 16kA to BS1361; 1-
63A SP 18mm RCBOs.
FEATURES
Distribution boards of equal width can be stacked vertically
without any other accessories. They can be electrically
connected vertically or horizontally to give more outgoing ways
by using a connector kit (see page 60). Memshield modular
control devices can be fitted by using an extension box (see
page 60). Many SPN type A distribution boards can be
mounted on top of any type B distribution board.
A clean earth facility is standard for computer installations.
Memshield 2 P47-91 1/8/02 10:03 Page 11
55
S T A N D A R D 2 0 0 A T P N T Y P E B
■ Two type B distribution boards can bepositioned side by side and electricallyinter-connected with a connector kit.
■ Any number of type B distribution boardscan be vertically stacked and electricallyinter-connected with a connector kit.
■ Clean earth facility standard within alltype B distribution boards.
■ Any TPN (type B) distribution board can
be simply converted to SPN by fitting
a conversion kit and SPSN switch-
disconnector incoming device.
■ Consult us for even more incoming options.
A - SELECT 200A DISTRIBUTION BOARD:
DESCRIPTION LIST NO.
4 way TPN type B BM42
6 way TPN type B BM62
8 way TPN type B BM82
12 way TPN type B BM122
16 way TPN type B BM162
24 way TPN type B BM242
B - SELECT INCOMING DEVICE UP TO 200A:
Incoming device supplied separately to distribution board. 200A
switch-disconnector and MCCB incoming devices are supplied with
cable entry boxes. (100A incomers from page 54 can also be used).
DESCRIPTION LIST NO.
200A TP switch-disconnector (isolator) BMS2003†
160A TP switch-disconnector (isolator) BMS1603
200A SPSN switch-disconnector (isolator) BMS2001N*
TP kit for ‘F’ frame MCCB** BMIK2003†
TP lugs (direct connection) BMBT2003
Top entry distribution boards with factory fitted 160A TP switch -
disconnector - Add suffix T160 to list no. e.g. BM42T160.Not applicable to 24 way board BM242.
*Not suitable for BM242. TPN to SPN conversion kit included.
**Select ‘F’ frame MCCB for use with BMIK2003 from following table.
† Add suffix ‘P’ when these are to be fitted to BM242.
F FRAME MCCBS
DESCRIPTION Icu Ics LIST NO.
TP 100A 25kA 100% MFL1003
TP 125A 25kA 100% MFL1253
TP 160A 25kA 100% MFL1603
TP 200A 25kA 100% MFL2003
CABLE CAPACITIES mm2
LUGS (100A) 50
SWITCH-DISCONNECTOR (100A) 50
RCCB 50
LUGS (200A) 120
SWITCH-DISCONNECTOR (125A & 160A) 70
SWITCH-DISCONNECTOR (200A) 120
MCCB (‘F’ Frame type) 120
MCBs 25
EARTH BARS 25
NEUTRAL BARS 25
Memshield 2 P47-91 1/8/02 10:03 Page 12
56
M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SF C S I N C O M E R S T P N T Y P E B , D P V E R S I O N S - T Y P E B F O R M A T
FUSED COMBINATION SWITCH INCOMERS
TPN type B distribution boards are also available with a choice of
fitted TP or TPSN FCS incomers. The FCS incomer uses MEM BS88
fuses, which allow the unit to be fused from 2-125A. This is a benefit
for applications where the load may increase in the future, as the FCS
can be re-fused accordingly.
The exclusive use of MEM fuselinks in this equipment will extend thewarranty period to 3 years.
These distribution boards comply fully with BS5486 : Pt 12 and
BSEN60439-3.
125A TP DISTRIBUTION BOARDS WITH FITTED FUSE
COMBINATION SWITCH INCOMERS.
DESCRIPTION INCOMER LIST NO.
4 way TPN type B TP FCS BMFCS4
6 way TPN type B TP FCS BMFCS6
8 way TPN type B TP FCS BMFCS8
12 way TPN type B TP FCS BMFCS12
16 way TPN type B TP FCS BMFCS16
4 way TPN type B TPSN FCS BMFCSN4
6 way TPN type B TPSN FCS BMFCSN6
8 way TPN type B TPSN FCS BMFCSN8
12 way TPN type B TPSN FCS BMFCSN12
16 way TPN type B TPSN FCS BMFCSN16
N.B. All distribution boards with FCS type incomer are supplied with
125A fuses.
DOUBLE POLE DISTRIBUTION BOARDS
Memshield 2 double pole distribution boards have been developed for
specialist applications.
Double pole distribution boards have a single pole and switched neutral
incoming circuit. They allow for single pole and switched neutral
MCBs to be fitted on all outgoing circuits which is necessary for the
control of circuits situated in hazardous areas.
SPSN or DP MCBs and SPSN RCBOs can be fitted.
For 3 phase, 4 wire systems please contact us for details of our four
pole range of Memshield 2 distribution boards.
DP DISTRIBUTION BOARDS TYPE B FORMAT WITH FITTED
100A SPSN MAIN SWITCH-DISCONNECTOR.
DESCRIPTION LIST NO.
6 way DP (5 way SPSN) type B format BM61D
12 way DP (11 way SPSN) type B format BM121D
18 way DP (17 way SPSN) type B format BM181D
24 way DP (23 way SPSN) type B format BM241D
Memshield 2 P47-91 1/8/02 10:03 Page 13
SPLIT LOAD BOARDS
Split load TPN type B distribution boards are factory fitted with a
main 100A switch-disconnector and a 30mA RCCB. Please consult
our Technical Services department for details of other incoming
device options.
MODULAR ENCLOSURES
Memshield 2 modular enclosures can be used to house Memshield
2 protective and command devices. Enclosures are available to
house from 2 to 45 x 18mm modules in moulded or metal
construction up to IP55.
Up to three Memshield 2 type A pan assemblies can be fitted into
an enclosure.
To select a suitable enclosure, select the devices required and
calculate the amount of 18mm modules required, then select the
enclosure that can accommodate at least that many 18mm modules.
BMX 15 module enclosures can be mounted onto AM13 or any
Memshield 2 TPN distribution board. Distribution board accessories
e.g. door lock kit are suitable for use with BMX type enclosures.
BMXDC enclosures are fitted with earth and neutral bars as
standard. Additional earth and neutral bars for 30 and 45 way
enclosures are available for specific applications.
Metal enclosures will accommodate all modular devices, ie;
MCBs, RCCBs, RCBOs, fuse modules and command devices.
Moulded enclosures 4/6 QEL, 4EME and AM1SL will not
accept RCBOs.
4EME will accept command devices and TPSN RCCBs only.
CABLE EXTENSION BOXES
Cable extension boxes are for use with larger cables or for special
applications e.g. metering, etc. They can be fitted top and/or
bottom. All 200A type incomers include a cable extension box
where necessary.
All enclosures and extension boxes can be fitted top and/or bottom
of distribution boards in any quantity.
100A SPLIT LOAD DISTRIBUTION BOARDS WITH FITTED
100A MAIN SWITCH-DISCONNECTOR, AND 80A, 30MA RCCB.
DESCRIPTION LIST NO.12 way; 8 ways RCCB protected BMSL4812 way; 6 ways RCCB protected BMSL6612 way; 4 ways RCCB protected BMSL8416 way; 8 ways RCCB protected BMSL88
MEMSHIELD 2 ENCLOSURES - FOR MODULAR DEVICES
EARTH CAPACITYWITH DOOR TERMINAL IP RATING IN 18MM LIST NO.
PROVIDED MODULES
MOULDED ENCLOSURESNo yes IP30 2 AM1SLNo yes IP30 4 4EMEYes yes IP55 4 4QELYes yes IP55 6 6QEL
METAL ENCLOSURESYes yes IP4X 4 BMXDC4Yes yes IP4X 6 BMXDC6Yes yes IP4X 9 BMXDC9Yes yes IP4X 15 BMXDC15Yes yes IP4X 18 BMXDC18Yes yes IP4X 30 BMXDC30Yes yes IP4X 45 BMXDC45
Yes-glazed yes IP4X 6 BMXDCG6Yes-glazed yes IP4X 9 BMXDCG9Yes-glazed yes IP4X 15 BMXDCG15Yes-glazed yes IP4X 18 BMXDCG18Yes-glazed yes IP4X 30 BMXDCG30Yes-glazed yes IP4X 45 BMXDCG45
N.B. AM1SL, 4QEL, 6QEL, can be wire sealed.
ENCLOSURE ACCESSORIES
DESCRIPTION LIST NO.Blanking module for unused MBPways-metal enclosures
Additional earth bar for 30 & 45 BMXE15way BMXDC enclosures
Additional neutral bar for 30 & 45 BMXN15way BMXDC enclosures
Door barrel lock for 4, 6, 9, 15 way AMDLBMXDC enclosures
Door barrel lock for 30 & 45 way BMDLBMXDC enclosures
Padlocking kit for 4, 6, 9, 15 way AMPLBMXDC enclosures
Padlocking kit for 30 & 45 way BMPLBMXDC enclosures
Padlock for AMPL/BMPL PD1EXTENSION BOXES FOR TPN AND AM13 DISTRIBUTION BOARDS.
DESCRIPTION LIST NO.Cable spreader extension box, 162mm high BMXPC1Cable spreader extension box, 250mm high BMXPC2
57
S P L I T L O A D B O A R D S , E X T E N S I O N B O X E S A N D M O D U L A R E N C L O S U R E S
Memshield 2 P47-91 1/8/02 10:03 Page 14
58
M E M S H I E L D 2 M C B D I S T R I B U T I O N B O A R D SF L U S H M O U N T I N G K I T S & P A N A S S E M B L I E S
FLUSH KITS
Type A and type B distribution boards are suitable for flush mounting
applications by using the appropriate kit except 24 way TPN.
FEATURES
Memshield 2 type B flush mounting kits can be adjusted to
accommodate slightly uneven mounting surfaces.
Please contact our Technical Services department for other
flush mounting possibilities.
MEMSHIELD 2 FLUSH MOUNTING KITS
DISTRIBUTION BOARD TYPE LIST NO.
AM4, BMXDC6, BMXDCG6 AMFK4
AM7, BMXDC9, BMXDCG9 AMFK7
AM10, AM5D AMFK10
AM13, AMSL37, AMSL64, AMDT74, AMFK13BMXDC15, BMXDCG15
AM8D, AM16, AMDT77, AMDT104, AMFK16AMSL67, AMSL94, AMSL310
BM41, BM61D BMFK1
BM61, BM42 BMFK2
BM81, BM62, BM121D BMFK3
BM82 BMFK4
BM121, BM122, BM181D, BMFK5BMXDC45, BMXDCG45
BM161, BM162, BM241D BMFK6
BMSL48, BMSL66, BMSL84 BMFK7
BM42* BMFK21
BM62* BMFK22
BM82* BMFK23
BM122* BMFK24
BM162* BMFK25
*When fitted with BMIK2003, BMS2003, BMS2001N,or BMXPC1
PAN ASSEMBLIES
Memshield pan assemblies offer a high degree of flexibility for
custom applications.
SPN types are available with 4, 7, 10, 13, and 16 ways. DP types
with 5, 6, 8, 12, 18 and 24 ways. TPN types with 4, 6, 8, 12,16
and 24 TP ways.
Where the switching of outgoing neutrals on 3 phase pan
assemblies is required, eg: for switching circuits in hazardous
areas, please contact us.
Refer to pages 52, 54 and 55 for incoming devices.
Add suffix ‘P’ to incomer kits BMS2001N, BMS2003 and
BMIK2003 to order kit without cable box.
Refer to pages 61 and 68 for outgoing devices.
FEATURES
Memshield 2 pan assemblies are suitable for inclusion in other
factory built assemblies and as replacements for distribution board
interiors. Pan assemblies feature fully shrouded busbars. The
busbars can be connected by using a busbar connector kit. SPN
distribution boards can be adapted to take modular control devices
using a busbar kit to adapt the busbar, see page 60.
Please contact our Technical Services department for other pan
assembly types.
MEMSHIELD 2 PAN ASSEMBLIES (INTERIORS)
DESCRIPTION LIST NO.
100A 4 way SPN without incomer AMP4
100A 7 way SPN without incomer AMP7
100A 10 way SPN without incomer AMP10
100A 13 way SPN without incomer AMP13
100A 16 way SPN without incomer AMP16
100A 5 way DP without incomer AMP5D
100A 8 way DP without incomer AMP8D
200A 6 way DP main lugs fitted BMP61D
200A 12 way DP main lugs fitted BMP121D
200A 18 way DP main lugs fitted BMP181D
200A 24 way DP main lugs fitted BMP241D
125A 4 way TPN without incomer BMP41
125A 6 way TPN without incomer BMP61
125A 8 way TPN without incomer BMP81
200A 4 way TPN without incomer BMP42
200A 6 way TPN without incomer BMP62
200A 8 way TPN without incomer BMP82
200A 12 way TPN without incomer BMP122
200A 16 way TPN without incomer BMP162
200A 24 way TPN main lugs fitted BMP242L
MEMSHIELD 2 PAN ASSEMBLIES (WITHOUT EARTH AND
NEUTRAL BARS)
DESCRIPTION LIST NO.
200A 4 way TPN main lugs fitted BMPS42
200A 6 way TPN main lugs fitted BMPS62
200A 8 way TPN main lugs fitted BMPS82
200A 12 way TPN main lugs fitted BMPS122
200A 16 way TPN main lugs fitted BMPS162
200A 24 way TPN main lugs fitted BMP242LWEN