METAL ENCLOSEDMODULAR SWITCHGEARS24 kV 630A - 1250A 20kA36kV 630A - 1250A 16kA
MONOBLOCK CONCRETE SUBSTATIONS UP TO 36kV 1600kVA
www.evaelektromekanik.comEVA-Cat.ENG R1
EVA ELEKTROMEKANİK SAN. VE TİC. LTD. ŞTİ. DAĞYAKA MAH. 2008. CAD. NO:5 KAHRAMANKAZAN, ANKARA, TÜRKİYETel: +90 312 811 27 27 Fax: +90 312 811 27 28www.evaelektromekanik.com
All rights reserved. Any part of this catalogue can not be copied without the permission of the rightholder. It can only be copiedand augmented with the written permission of EVA ELEKTROMEKANİK SAN. VE TİC. LTD. ŞTİ.
Switching The Future
COMPANY PROFILE 2
MISSION 2
VISION 2
QUALITY POLICY 3
METAL ENCLOSED MODULAR SWITCHGEAR 4
ADVANTAGES OF EVA AIR INSULATED METAL ENCLOSED SWITCHGEARS 4
QUALITY MANAGEMENT AND STANDARDS 6
USAGE AREAS 7
STRUCTURAL FEATURES 8
STRUCTURAL PARTS AND SWITCHING DEVICES 8
INTERLOCKING SYTEM 11
INTERLOCKING SYTEM 11
EVA AIR INSULATED METAL ENCLOSED SWITCHGEAR TYPES AND 12
TECHNICAL SPECIFICATIONS 16
TECHNICAL SPECIFICATIONS 17
CONCRETE SUBSTATION 18
ADVANTAGES OF EVA MONOBLOCK CONCRETE TRANSFORMER AND DISTRIBUTION SUBSTATIONS 18
USAGE AREAS 20
STRUCTURAL FEATURES 21
STRUCTURAL PARTS 21
SYSTEM FEATURES 21
EVA MONOBLOCK CONCRETE TRANSFORMER AND DISTRIBUTION SUBSTATIONS TYPES AND TECHNICAL DETAILS 22
TRANSFORMER SUBSTATIONS 22
RMU SUBSTATIONS 25
DISTRIBUTION SUBSTATIONS 26
TECHNICAL SPECIFICATIONS 29
LIFTING INSTRUCTIONS FOR CONCRETE SUBSTATION 29
LIFTING INSTRUCTIONS FOR CONCRETE SUBSTATION 29
LIFTING INSTRUCTIONS FOR ROOF 29
CIVIL WORKS AND INSTALLATION 30
CON
TEN
TS
COMPANY PROFILE
EVA Elektromekanik company was established in
Ankara-Kahramankazan-Akıncılar area in April 2017 to
manufacture, market and sell Metal Enclosed Modular
Switchgears, Concrete Substations, Sheet Metal
Substations, Mobile Transformer Substations and LV
Distribution Panels by a team that each member has more
than 18 years experience in Transformer Distribution
Substations and MV Switchnig Devices. Our facility
consists of a total area of 10.400m², including 2.000m²
closed area for Electromechanical Production, 3.000m²
for Concrete Substation / Metal Sheet Substation and
Mobile Transformer Substation Manufacturing and open
stock area, 400m² for technical and administrative office
area and 5.000m² suitable area for future extention .
As EVA Elektromekanik, our mission is to provide high quality customer service to both domestic and international markets by developing and producing switchgear products such as Metal Enclosed Modular Switchgears, Monoblock Concrete Substations, Metal Sheet Substations and Mobile Transformer Substations.
As EVA Elektromekanik, our vision is to be a firm that provides switchgear products to customers in economical, fast, high quality and solution focused way.
MISSION
VISION
EVA Elektromekanik company was established in Ankara-Kahramankazan-Akıncılar area in April 2017 to manufacture, market and sell Metal Enclosed Modular Switchgears, Concrete Substations, Sheet Metal Substations, Mobile Transformer Substations and LV Distribution Panels by a team that each member has more than 18 years experience in Transformer Distribution Substations and MV Switchnig Devices.
www.evaelektromekanik.com2
QUALITY POLICY
In line with this goal;
We are giving importance to produce our products in a smooth and quality manner.
We are always cooperating with our suppliers in order to ensure the continuity of our quality.
We are providing solutions to our customers’ after-sales service requests as soon as possible.
We are constantly following technological innovations.
We are taking account of feedbacks from our customers.
As a solution oriented company with a high level of communication, we are giving importance to good relationships with customers.
To ensure that our customers choose us again;
To make a difference with our superior product and service quality;
1
2
In line with its quality policy, EVA Elektromekanik
aims to be able to supply high quality and
competitive products to its customers with 100%
customer satisfaction and timely delivery.
www.evaelektromekanik.com 3
ADVANTAGES OF EVA AIR INSULATED METAL ENCLOSED SWITCHGEARS
METAL ENCLOSED SWITCHGEARS
EVA Air Insulated Metal Enclosed Switchgears are medium
voltage switchgear equipment used for reliable distribution of
electricity in 36 kV secondary distribution systems according
to the customer’s different requirements. EVA Air Insulated
Metal Enclosed Switchgears are highly suitable for use in indoor
environments, industrial production facilities and compact type
substation buildings. Thanks to modular construction for easy
installation, EVA Air Insulated Metal Enclosed Switchgears can
easily meet all the requirements of clients; they can be quickly
installed. In these cells, the output busbars are air insulated and
the electrical insulation and breaking operations are performed
in SF6 gas environment. In this way, a maximum safety operation
can be achieved in minimum distances. EVA Air Insulated Metal
Enclosed Switchgears are also preferred by customers in kiosk
type transformer substations with their reliable construction
and compact dimensions.’
COMPACT DESIGN
EASY INSTALLATION AND CHANGEABILITY
THANKS TO MODULAR CONSTRUCTION
COMPATIBILITY WITH RIGHT-LEFT EXTENSION
WHEN NEEDED INTELLIGENT LOCKING SYSTEMS FOR
MAXIMUM OPERATOR SAFETY
RELIABLE SWITCHING WITHIN SF6 GAS ENVIRONMENT COMPATIBILITY WITH
SCADA SYSTEMS
SUITABLE FOR EASY TRANSPORT AND
STORAGE
DIFFERENT COMBINATIONS OF
FEEDERS ACCORDING TO
THE CUSTOMER’S REQUEST
www.evaelektromekanik.com4
DIFFERENT COMBINATIONS OF
FEEDERS ACCORDING TO
THE CUSTOMER’S REQUEST
EVA AIR INSULATED SWITCHGEARS CAN EASILY RESPOND
TO ANY KIND OF REQUIREMENT OF A SUBSTATION AND
CAN EASILY BE ENERGIZED.
www.evaelektromekanik.com 5
QUALITY MANAGEMENT AND STANDARDS
EVA Air Insulated Metal Enclosed Switchgears are produced according to IEC 62271-200, 60265, 60129, 60694, 62271-
100, 62271-102, 62271-105 standards.
The quality of EVA Air Insulated Metal Enclosed Switchgears are also certified in international accredited laboratories.
***EVA Air Insulated Metal Enclosed Switchgears are manufactured by applying an integrated quality
management system. in all departments of our production facility At each stage of production, it is checked
whether EVA Air Insulated Metal Enclosed Switchgears are produced according to the relevant standards and
customer requirements or not. Also related documents and test reports are recorded in terms of traceability.
www.evaelektromekanik.com6
USAGE AREAS
ENERGY
Wind power plants, solar energy plants,
hydroelectric power plants, MV distribution
systems, transformer substations etc.
VARIOUS INDUSTRIES
Water, iron and steel, automotive, oil etc.
INFRASTRUCTURE AND CONSTRUCTION SECTOR
Ports, train stations, airports, hospitals, schools,
hotels, shopping malls, commercial centers,
holiday complexes etc.
www.evaelektromekanik.com 7
STRUCTURAL FEATURESSTRUCTURAL PARTS AND SWITCHING DEVICES
14
2
3
EVA Air Insulated Metal Enclosed Switchgears are made up of four main compartments separated by a metal partition:
1. Busbar connection compartments
2. Switching and cable connection compartments
3. Mechanism compartments
4. Low voltage compartments Access to this compartment is provided from the
closure on the cell. Side-by-side installation of EVA
Air Insulated Metal Enclosed Switchgears is carried
out through three busbars located in this section.
This compartment consists of switching elements
such as switch disconnector, disconnector, circuit
breaker and earthing switch according to the
customer’s request. If the cell is a fuse-load break
switch combination, then the pin mechanism and
MV fuses are also in this compartment. The electrical
cabling from the network is connected to the cell at
the connection points below the earthing switch in
this section.
With the help of the sheet metal partitions between
the bar connection part and the cable connection
part, disconnector with the epoxy body or the load
break switch is securely separated from the bus
bar. The earthing switch must be closed in the
ground position so that the cable connection can
be reached safely from the front.
. 1 BUSBAR CONNECTION COMPARTMENT
2. SWITCHING AND CABLE CONNECTION COMPARTMENT
www.evaelektromekanik.com8
BATEL SF6 insulated load break switches provide
“switching-disconnecting” characteristics. LBS
main circuit contacts are housed in an epoxy cast
housing that is filled with 1.5 bar SF6 gas and
guaranteed for a lifetime of gas tightness.
The main circuit contacts can be found in only one
of the two positions “On” and “Off”.
The earthing switch is located outside the
epoxy body and earthing switch position can be
monitored directly, safely and reliably by the user.
There is a mechanical locking mechanism that
ensures safe operation between the earthing switch and the main circuit contacts. The explosion-proof reliability of
the gas-filled epoxy seal is provided by the safety membrane at the rear.
There are auxiliary contact options that indicate the positions of the main circuit contacts and the earthing switch.
The control mechanism can be set by hand or by motor when required by using the lever. The installed mechanism
has accumulated energy for closing and opening. Closing and opening operations can be done with pushbuttons or
remote coils. If required, a protective fuse throwing pin and opening system can be applied.
BATEL SF6 gas insulated circuit breakers provide
high reliability with applied SF6 gas arc breaking
technique. With these features, BATEL SF6 gas
insulated circuit breakers guarantee the continuity
of energy in electric distribution systems.
Epoxy-insulated 3 pole housings are filled with
SF6 gas and their sealings are guaranteed for a
lifetime. The explosion-proof reliability of gas-filled
pole epoxy housings is provided by the safety
membrane on the bottom cover.
The control mechanism can be set by hand or
by motor when required by using the lever.
The installed mechanism has accumulated energy for closing and opening. Closing and opening can be done with
pushbutton or remote coil. BGK type circuit breakers have front and side mechanism options.
4NO + 4 NC or 6NO + 6 NC auxiliary contact options are available for OPEN and CLOSED positions.
BATEL SF6 INSULATED LOAD BREAK SWITCHES
BATEL SF6 INSULATED CIRCUIT BREAKERS
www.evaelektromekanik.com 9
In this compartment, there are mechanisms of
switching elements such as load break switch,
disconnector, circuit breaker and earthing switch.
According to the customer’s request motor or
earthing disconnector can be added to this section.
This compartment contains the LV fuses, protection relays, measuring instruments and connection terminals.
3. MECHANISM COMPARTMENT
4. LOW VOLTAGE COMPARTMENT
www.evaelektromekanik.com10
INTERLOCKING SYTEM
EARTHING SYSTEM
EVA Air Insulated Metal Enclosed Switchgears provide maximum safety of operation thanks to the following interlocking
mechanisms:
1. The load break switch can not be closed when the cell door is open.
2. Only when the earthing switch is off, the cell door can be opened.
3. The load break switch can be closed only when the earting switch is opened and the cell door is closed.
4. The earthing switch can only be closed when the load break switch is opened.
5. According to the customer’s request, it is possible to put an earthing lock on the cell. With this interlocking, closing
on to energized cable, which leads to a three phase short circuit current, will be prevented .
Switching elements such as earth conductors of energy cables, blades of earting switch, breaker, disconnector, load
break switch and shunt of current and voltage transformers, metal parts of cell parts firstly connect to each other and
then to the main earthing busbar located at the front of the cell. This ensures safe grounding of the system.
www.evaelektromekanik.com 11
INCOMING-OUTGOING FEEDER WITH LOAD BREAK SWITCH
EVA AIR INSULATED METAL ENCLOSED SWITCHGEAR TYPES AND TECHNICAL DETAILS EVA AIS Switchgears can be classified according to usage areas as follows:
SWITCH-FUSE COMBINATION TRANSFORMER PROTECTION FEEDER
INCOMING-OUTGOING FEEDER WITH DISCONNECTOR
BUS TIE (COUPLER) CUBICLE WITH LOAD BREAK SWITCH
HEIGHT (mm)
DEPTH(mm)
WIDTH(mm)
RATED VOLTAGE
PRODUCTCODE
eva-36-Seva-24-S
36kV24kV
750500
14001000
22501935
HEIGHT (mm)
DEPTH(mm)
WIDTH(mm)
RATED VOLTAGE
PRODUCTCODE
eva-36-S (a)eva-24-S (a)
36kV24kV
750500
14001000
22501935
HEIGHT (mm)
DEPTH(mm)
WIDTH(mm)
RATED VOLTAGE
PRODUCTCODE
eva-36-Feva-24-F
36kV24kV
750500
14001000
22501935
HEIGHT (mm)
DEPTH(mm)
WIDTH(mm)
RATED VOLTAGE
PRODUCTCODE
eva-36-DSeva-24-DS
36kV24kV
1000750
14001000
22501935
www.evaelektromekanik.com12
CABLE CONNECTION CUBICLE
INCOMING-OUTGOING & TRANSFORMER PROTECTION FEEDER WITH CIRCUIT BREAKER
BUS TIE (COUPLER) CUBICLE WITH CIRCUIT BREAKER
OUTGOING FEEDER WITH CIRCUIT BREAKER AND VOLTAGE TRANSFORMER
HEIGHT (mm)
DEPTH(mm)
WIDTH(mm)
RATED VOLTAGE
PRODUCTCODE
eva-36-Beva-24-B
36kV24kV
1000750
14001000
22501935
HEIGHT (mm)
DEPTH(mm)
WIDTH(mm)
RATED VOLTAGE
PRODUCTCODE
eva-36-Otop
eva-24-Otop
36kV24kV
14001100
14001000
22501935
HEIGHT (mm)
DEPTH(mm)
WIDTH(mm)
RATED VOLTAGE
PRODUCTCODE
eva-36-CBeva-24-CB
36kV24kV
15001250
14001000
22501935
HEIGHT (mm)
DEPTH(mm)
WIDTH(mm)
RATED VOLTAGE
PRODUCTCODE
eva-36-CReva-24-CR
36kV24kV
750500
14001000
22501935
www.evaelektromekanik.com 13
CURRENT & VOLTAGE MEASUREMENT CUBICLE WITH LOAD BREAK SWITCH
CURRENT MEASUREMENT
CURRENT & VOLTAGE MEASUREMENT CUBICLE
AUXILIARY TRANSFORMER CUBICLE
HEIGHT (mm)
HEIGHT (mm)
HEIGHT (mm)
HEIGHT (mm)
DEPTH(mm)
DEPTH(mm)
DEPTH(mm)
DEPTH(mm)
WIDTH(mm)
WIDTH(mm)
WIDTH(mm)
WIDTH(mm)
RATED VOLTAGE
RATED VOLTAGE
RATED VOLTAGE
RATED VOLTAGE
PRODUCTCODE
PRODUCTCODE
PRODUCTCODE
PRODUCTCODE
eva-36-McvLeva-24-McvL
eva-36-McvReva-24-McvR
eva-36-Mceva-24-Mc
eva-36-Mvieva-24-Mvi
36kV24kV
36kV24kV
36kV24kV
36kV24kV
1000750
1000750
1000750
750500
14001000
14001000
14001000
14001000
22501935
22501935
22501935
22501935
www.evaelektromekanik.com14
BUS SECTION CUBICLE WITH CIRCUIT BREAKER
CURRENT & VOLTAGE MEASUREMENT CUBICLE WITH DISCONNECTOR
VOLTAGE MEASUREMENT CUBICLE
M
E
HEIGHT (mm)
HEIGHT (mm)
HEIGHT (mm)
DEPTH(mm)
DEPTH(mm)
DEPTH(mm)
WIDTH(mm)
WIDTH(mm)
WIDTH(mm)
RATED VOLTAGE
RATED VOLTAGE
RATED VOLTAGE
PRODUCTCODE
PRODUCTCODE
PRODUCTCODE
eva-36-Mcvs (a)eva-24-Mcvs (a)
eva-36-Mveva-24-Mv
eva-36-DBeva-24-DB
36kV24kV
36kV24kV
36kV24kV
1000750
750500
17501250
14001000
14001000
14001000
22501935
22501935
22501935
www.evaelektromekanik.com 15
eva-36
Rated voltage 36 kV70 kV80 kV170 kV195 kV50 Hz630 -1250 A40-63 kA-peak16 kA
630 A630 A20 A2 A40 A35 A 630 A40 kA-peakM1-E3IP3X
LSC2A-PIAFL
Rated power frequency withstand voltage (phase-to-phase) (1min)
Rated power frequency withstand voltage (across isolating distance) (1 min)Rated lightning impulse withstand voltage (phase-to-phase)Rated lightning impulse withstand voltage (across isolating istance)Rated frequencyRated currentRated peak withstand currentRated short time withstand current (1 s) (3s)Rated mainly active load breaking currentRated breaking currentRated cable charging currentRated line charging currentRated earth fault currentRated cable and line charging current under earth faultRated transfer currentRated short circuit making currentElectrical and mechanical endurance classProtection classInternal arc classificationLoss of service continuity class
TECHNICAL SPECIFICATIONS
BUS RISER CUBICLE
HEIGHT (mm)
DEPTH(mm)
WIDTH(mm)
RATED VOLTAGE
PRODUCTCODE
eva-36-BReva-24-BR
36kV24kV
750500
14001000
22501935
www.evaelektromekanik.com16
PLACEMENT AND INSTALLATION
EVA Air Insulated Metal Enclosed Switchgears should be placed on
a cable duct in the building, taking into account the drawings and
measurements given below.
In addition, the cells should be
installed with M10 x 30 steel
bolts as shown below.
Note: eva-36-CB cubicle is composed of 2 units of cubicles, having 750mm width..eva-36-DB cubicle is composed of 1 unit of cubicle, having 750mm width and 1 unit of cubicle, having 1000mm width
Note: eva-24-CB cubicle is composed of 2 units of cubicles, having 500mm width..eva-24-DB cubicle is composed of 1 unit of cubicle, having 500mm width and 1 unit of cubicle, having 750mm width
Where the cells are to be placed, the distance to the ceiling and back wall of the cell;A≥ 400 mm and B = 100 mmCable duct dimensions (XLPE insulated, according to 1 x 240/25 mm2 cable);C (Cable channel width) = 900 mm and D (Cable channel depth) = minimum 690 mm
FIXING SWITCHGEARS TO THE GROUND
CABLE TRENCHD
IN F
RON
T O
F CU
BICL
E
E
F
H
G
G
eva-36-S
MODELE
(mm)F
(mm)G
(mm)H
(mm)DELİK SAYISI
eva-36-McvL
eva-36-B
eva-36-McvS (a)
eva-36-F
eva-36-Mc
eva-36-CB
eva-36-DB
eva-36-S (a)
eva-36-McvR
eva-36-Otop
eva-36-Mv
eva-36-DS
eva-36-MVİ
eva-36-CR
eva-36-BR
750
1000
1000
1000
750
1000
1500
1750
750
1000
1400
750
1000
750
750
750
4
4
4
4
4
4
8
8
4
4
6
4
4
4
4
4
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
550
800
800
800
550
800
550
800/550
550
800
600
550
800
550
550
550
1270
1270
1270
1270
1270
1270
1270
1270
1270
1270
1270
1270
1270
1270
1270
1270
eva-24-S
MODELE
(mm)F
(mm)G
(mm)H
(mm)DELİK SAYISI
eva-24-McvL
eva-24-B
eva-24-McvS (a)
eva-24-F
eva-24-Mc
eva-24-CB
eva-24-DB
eva-24-S (a)
eva-24-McvR
eva-24-Otop
eva-24-Mv
eva-24-DS
eva-24-MVİ
eva-24-CR
eva-24-BR
500
750
750
750
500
750
1000
1250
500
750
1100
500
1000
500
500
500
4
4
4
4
4
4
8
8
4
4
6
4
4
4
4
4
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
370
620
620
620
370
620
370/370
620/370
370
620
485
370
620
370
370
370
870
870
870
870
870
870
870
870
870
870
870
870
870
870
870
870
www.evaelektromekanik.com 17
ADVANTAGES OF EVA MONOBLOCK CONCRETE TRANSFORMER AND DISTRIBUTION SUBSTATIONS
CONCRETE SUBSTATION
EVA monoblock concrete transformer and distribution substations; environment friendly, aesthetic and reliable
centers designed to protect metal enclosed switchgears, transformers and LV panels from the harsh environmental
conditions. EVA monoblock concrete transformer and distribution substations, which are produced in different colors
and sizes according to all international standards and without any extra installation, have also proven their reliability
from international accredited laboratories.
EVA Monoblock Concrete Transformer and Distribution Substations offer customers the following advantages:
COMPACT DESIGN
TRANSPORTABILITY EASY SETUP
FLEXIBLE SOLUTION FOR DIFFERENT
PROJECTS
MAXIMUM OPERATOR SAFETY DURING INTERNAL ARC
www.evaelektromekanik.com18
EVA MONOBLOCK CONCRETE KIOSKS ARE DESIGNED ECO-
FRIENDLY, COMPACT, AESTHETIC AND RELIABLE IN ORDER
TO ISOLATE SWITCHGEAR EQUIPMENTS, TRANSFORMERS
AND LV PANELS FROM TOUGH ENVIRONMENTAL
CONDITIONS.
www.evaelektromekanik.com 19
USAGE AREASEVA Monoblock Concrete Transformer and Distribution Substations are used in the following areas:
Transformer Substations
Organized Industrial Zones
Medium Voltage Distribution Systems
Generator Supply Units
Power Plants
Industrial Plants
www.evaelektromekanik.com20
STRUCTURAL FEATURESSTRUCTURAL PARTS
SYSTEM FEATURES
EVA Monoblock Concrete Transformer and Distribution Substations consist of three main sections separated from
each other:
1. Medium voltage switching equipment section
2. Medium voltage distribution transformer section
3. Low voltage distribution panel section
11 2 3
The main bodies of the EVA Monoblock Concrete Transformer and Distribution Substations are designed by taking into consideration the most difficult conditions in the operation and making the corresponding strength and seismic calculations. The safety distances required for each part are determined according to the information received from the manufacturers of the products such as transformers and LV panels and specified distance values in relevant specifications.When producing concrete substations, IEC 60529 standard is taken into consideration in terms of access to the sections under energy and resistance to dust and water in moving parts. C 35 quality cement according to TS 500 standard is used in the production of concrete substations. Concrete substations are water-resistant. The ventilation panels on the walls of the substation are manufactured in accordance with the IP 23 protection class. EVA Monoblok Concrete Transformer and Distribution Substations can be carried safely thanks to the lifting irons at four corners. From the attenuated cable entry sections at the bottom of the body, the desired number of cables can safely enter and exit the substation. The parts of the substation that are under the floor are insulated.Ventilation panels and doors are manufactured to withstand stroke, which can occur from inside and outside. The doors are designed for easy operation of the operating personnel.The switchgear, compartments, doors, ventilation panels, fittings and all metal parts in the concrete substation are connected to the earthing busbar.
www.evaelektromekanik.com 21
EVA MONOBLOCK CONCRETE TRANSFORMER AND DISTRIBUTION SUBSTATIONS TYPES AND TECHNICAL DETAILS
eva-MB-2550 TR
eva-MB-3200 TR
TRANSFORMER SUBSTATIONS
PANJUR
25002550
35503550
2550
2000 2500
1720 570
1500
2280
1000 kVATR
AG
AG
2000
6702270
25002000
3200
2280
3550 3550
3200 2500
FRONT VIEW
FRONT VIEW
SIDE VIEW
SIDE VIEW
www.evaelektromekanik.com22
eva-MB-3800 TR
eva-MB-4350 TR
eva-MB-4800 TR
eva-MB-5450 TR
KOMP.
AG
1500
18401700
25002000
3800
2280
1000 kVATR
3550 3550
3800 2500
h=2400h=2400
25004350
3550
4350
2280 25002000
5701700
1500
1780
1500
h=2400h=2400
25004800
35503550
4800
2280 25002000
5701700
1500
2230
1500
h=2400 h=2400
h=24
00
25005450
35503550
2280 25002000
5702880
2000
5230
5450
1700
1500
FRONT VIEW
FRONT VIEW
FRONT VIEW
FRONT VIEW
SIDE VIEW
SIDE VIEW
SIDE VIEW
SIDE VIEW
3550
www.evaelektromekanik.com 23
eva-MB-6500 TR
eva-MB-7500 TR
eva-MB-6000 TR
h=2400
h=24
00
h=2400
25006000
355035502280
1700
2000
6000
2000 2500
3430 570
1500
h=2400
h=24
00
h=2400h=2400
25006500
35503550
1500 1500
6500
2000 2500
3930 570
1500
2280
1700
h=2400 h=2400
h=24
00
h=2400
25007500
35503550
2500
1500
2000
5704930
2000
1700
1500
7500
FRONT VIEW
FRONT VIEW
FRONT VIEW
SIDE VIEW
SIDE VIEW
SIDE VIEW
www.evaelektromekanik.com24
RMU SUBSTATIONSeva-MB-3800 RMU EK 1A EXTERNAL OPERATED
eva-MB-4350 RMU EK 1B INTERNAL OPERATED
eva-MB-5450 RMU EK 1C INTERNAL OPERATED
eva-MB-4350 RMU EK 1D EXTERNAL OPERATED
eva-MB-4800 RMU EK 1E INTERNAL OPERATED
100
0 k
VA
100
0 k
VA
AG
AG
100
0 k
VA
100
0 k
VA
AG
AG
100
0 k
VA
100
0 k
VA
AG
AG
160
0 k
VA
AG
AG
160
0 k
VA
AG
160
0 k
VA
AG
160
0 k
VA
www.evaelektromekanik.com 25
eva-MB-2550 SINGLE SECTION TYPE
eva-MB-3200 SINGLE SECTION TYPE
eva-MB-3800 SINGLE SECTION TYPE
DISTRIBUTION SUBSTATIONS
h=2400
3550
2550
3550
2500
2330
2500
2550
2000
2280
3200 2500
h=2400
2980
2500
3200
2000
2280
3550 3550
3800
3550
2500
2500
3800
2000
2280
3580
3550
FRONT VIEW
FRONT VIEW
FRONT VIEW
SIDE VIEW
SIDE VIEW
SIDE VIEW
www.evaelektromekanik.com26
eva-MB-4350 SINGLE SECTION TYPE
eva-MB-4800 SINGLE SECTION TYPE
eva-MB-5450 SINGLE SECTION TYPE
4350
3550
2500
h=2400 h=2400
1500
25002280
4350
1500
3550
4130
4800
3550
2500
h=2400h=2400
1500 2000
2000 25002280
4800
4580
3550
3550
5450 2500
5230
2280 2500 3550
h=2400 h=2400
2000
5450
2000
FRONT VIEW
FRONT VIEW
FRONT VIEW
SIDE VIEW
SIDE VIEW
SIDE VIEW
www.evaelektromekanik.com 27
eva-MB-6000 SINGLE SECTION TYPE
eva-MB-6500 SINGLE SECTION TYPE
eva-MB-7500 SINGLE SECTION TYPE
3550
6000 2500
h=2400 h=2400 h=2400
2500
6000
1500
2280
5780
1500 1500
h=2400 h=2400 h=2400
6500
25002280
6280
1500 1500 1500
6500 2500
h=2400 h=2400h=2400
1500 2000
7500
2000
7280
25003550 3550
7500 2500
FRONT VIEW
FRONT VIEW
FRONT VIEW
SIDE VIEW
SIDE VIEW
SIDE VIEW
3550
3550 3550
www.evaelektromekanik.com28
Rated voltage Up to 36 kVeva-MB16001016kA-1 sec.IEC 62271 - 202IP 23 D
Type
Rated power (max) (kVA)Protection class (accordig to iec 62271-202)Internal arc withstand (according to accessibility A & B)Applied standardProtection degree
TECHNICAL SPECIFICATIONS
LIFTING INSTRUCTIONS FOR CONCRETE SUBSTATION
1. Be sure that the capacity of the crane shall be at least three tımes of weıght of the concrete substation.
2. Be sure that lifting pins are placed and screwed properly3. Be sure that the lenght of the ropes are 8 meters and the
capacity of each rope is 10 tons.4. Be sure that the ropes are fixed to the pins during the
lifting. 5. Lift the concrete substation securely and place it on the
place which shall be prepared before.
EVA Monoblock Concrete Transformer and Distribution Substations should be located at the appropriate location in accordance with the drawing and measurements given below, in accordance with the instruction supplied with the product during delivery:
1. Be sure that the lenght of the ropes are 4 meters, the capacıty of each rope is 3 tons and having hooks wıth 3 tons capacity. Hang the hooks to the lifting eyes on the roof and lift.
2. Bring the roof down securely on a flat ground.3. Protect the lifthing eyes on the roof from any kind of damage made by
hammer, etc.
LIFTING INSTRUCTIONS FOR CONCRETE SUBSTATION
LIFTING INSTRUCTIONS FOR ROOF
LIFTING EYES
LIFTING PIN
LIFTING PIN
LIFTING PIN
www.evaelektromekanik.com 29
1. Excavate accordıng to drawıngs below. Check lenght of concrete substatıon, protectıve earthıng system, elevatıon dıfference for the excavatıng dımensıons.
2. Prepare the floor for concrete. Make foundatıon earthıng. Pour at least 15cm concrete. Use at least Q131*131 mattıng steel and C20 concrete.
3. Wait 2-3 days for full drying of pitched concrete.4. Cover the concrete with 3-4 cm height of 0.3 Sand as shown in detail.5. Brıng the concrete substatıon securely on the ground concrete covered by sand. 6. Connect floor earthıng and concrete substatıon earthıng.7. Fill the excavated perimeter of the concrete substation with soil and/or filling material.
CIVIL WORKS AND INSTALLATION
www.evaelektromekanik.com30
Switching The Future
EVA ELEKTROMEKANİK SAN. VE TİC. LTD. ŞTİ.DAĞYAKA MAH. 2008. CAD. NO:5 KAHRAMANKAZAN, ANKARA, TÜRKİYE
Tel: +90 312 811 27 27 Fax: +90 312 811 27 28www.evaelektromekanik.com [email protected]