GE Energy Connections Grid Solutions MiCOM P40 Agile P14N Address Assignment List Feeder Management IED Hardware version: A Software version: 57 Publication reference: P14NB-ADL-EN-7
Transcript
Page 1: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

GE Energy Connections Grid Solutions

MiCOM P40 Agile P14N

Address Assignment List Feeder Management IED

Hardware version: A Software version: 57 Publication reference: P14NB-ADL-EN-7

Page 2: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 1 1. IEC 61850 ADDRESS ASSIGNMENT LIST (ADL)

1.1 OBJECTIVE

This section of the document is the IEC 61850 Address Assignment List (ADL) and presents the relationships between Data Attributes of the IEC61850 data model and Courier Cells / Digital Data Bus signals in the settings database of the P141.

The reader is expected to be conversant with the terminology presented within the IEC 61850 standards, namely parts 6 and 7 of the series.

1.2 LOGICAL CONTROL

This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data Attributes within Logical Nodes contained in the Control Logical Device.

1.2.1 Logical Node: CILO1

Description: XCBR Interlocking

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [06 00] - CB CONDITION

EnaOpn.stVal ST Other internal source

EnaOpn.q ST Other internal source

EnaOpn.t ST Other internal source

EnaCls.stVal ST Other internal source

EnaCls.q ST Other internal source

EnaCls.t ST Other internal source

1.2.2 Logical Node: LLN0

Description: Controls Logical Device

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Page 3: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 2 MiCOM P40Agile P14NB

Attribute FC Source Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

NamPlt.configRev DC Other internal source

NamPlt.ldNs EX Other internal source

1.2.3 Logical Node: LPHD1

Description: Physical Device Information

Attribute FC Source PhyNam.vendor DC Other internal source

PhyNam.hwRev DC Other internal source

PhyNam.swRev DC [00 11] - Software Ref. 1

PhyNam.serNum DC [00 08] - Serial Number

PhyNam.model DC [00 06] - Model Number

PhyNam.location DC [00 05] - Plant Reference

PhyHealth.stVal ST Other internal source

PhyHealth.q ST Other internal source

PhyHealth.t ST Other internal source

Proxy.stVal ST Other internal source

Proxy.q ST Other internal source

Proxy.t ST Other internal source

Proxy.d DC Other internal source

PwrUp.stVal ST Other internal source

PwrUp.q ST Other internal source

PwrUp.t ST Other internal source

PwrUp.d DC Other internal source

1.2.4 Logical Node: XCBR1

Description: Circuit Breaker Monitoring

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [06 00] - CB CONDITION

Loc.stVal ST [07 01] - CB Control by

Page 4: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 3

Attribute FC Source Loc.q ST Other internal source

Loc.t ST Other internal source

EEHealth.stVal ST Other internal source

EEHealth.q ST Other internal source

EEHealth.t ST Other internal source

OpCnt.stVal ST [06 01] - CB Operations

OpCnt.q ST Other internal source

OpCnt.t ST Other internal source

Lock.ctlVal CO Other internal source

Pos.ctlVal CO [00 10] - CB Trip/Close

Lock.origin.orCat ST Other internal source

Pos.origin.orCat ST Other internal source

Lock.origin.orIdent ST Other internal source

Pos.origin.orIdent ST Other internal source

Lock.stVal ST Other internal source

Pos.stVal ST Other internal source

Lock.q ST Other internal source

Lock.t ST Other internal source

Pos.q ST Other internal source

Lock.ctlModel CF Other internal source

Pos.t ST Other internal source

Lock.sboTimeout CF Other internal source

Pos.ctlModel CF Other internal source

Pos.sboTimeout CF Other internal source

Pos.cdcNs EX Other internal source

Pos.cdcName EX Other internal source

Lock.cdcNs EX Other internal source

Lock.cdcName EX Other internal source

Lock.dataNs EX Other internal source

BlkOpn.stVal ST Other internal source

BlkOpn.q ST Other internal source

BlkOpn.t ST Other internal source

BlkOpn.ctlModel CF Other internal source

BlkCls.stVal ST Other internal source

BlkCls.q ST Other internal source

BlkCls.t ST Other internal source

BlkCls.ctlModel CF Other internal source

CBOpCap.stVal ST Other internal source

CBOpCap.q ST Other internal source

CBOpCap.t ST Other internal source

1.3 LOGICAL MEASUREMENTS

This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data Attributes within Logical Nodes contained in the Measurements Logical Device.

Page 5: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 4 MiCOM P40Agile P14NB 1.3.1 Logical Node: LLN0

Description: Measurements Logical Device

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

NamPlt.configRev DC Other internal source

NamPlt.ldNs EX Other internal source

1.3.2 Logical Node: LPHD1

Description: Physical Device Information

Attribute FC Source PhyNam.vendor DC Other internal source

PhyNam.hwRev DC Other internal source

PhyNam.swRev DC [00 11] - Software Ref. 1

PhyNam.serNum DC [00 08] - Serial Number

PhyNam.model DC [00 06] - Model Number

PhyNam.location DC [00 05] - Plant Reference

PhyHealth.stVal ST Other internal source

PhyHealth.q ST Other internal source

PhyHealth.t ST Other internal source

Proxy.stVal ST Other internal source

Proxy.q ST Other internal source

Proxy.t ST Other internal source

Proxy.d DC Other internal source

PwrUp.stVal ST Other internal source

PwrUp.q ST Other internal source

PwrUp.t ST Other internal source

PwrUp.d DC Other internal source

1.3.3 Logical Node: PriFouMMXU1

Description: Primary Fourier Measurements (No Volts)

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Page 6: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 5

Attribute FC Source Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

Hz.mag.f MX [02 2D] - Frequency

Hz.q MX Other internal source

Hz.t MX Other internal source

Hz.units.SIUnit CF [02 2D] - Frequency

Hz.units.multiplier CF Other internal source

Hz.db CF Other internal source

Hz.rangeC.hhLim.f CF Other internal source

Hz.rangeC.hLim.f CF Other internal source

Hz.rangeC.lLim.f CF Other internal source

Hz.rangeC.llLim.f CF Other internal source

Hz.rangeC.min.f CF Other internal source

Hz.rangeC.max.f CF Other internal source

A1.phsA.cVal.mag.f MX [02 01] - IA Magnitude

A1.phsA.cVal.ang.f MX [02 02] - IA Phase Angle

A1.phsA.q MX Other internal source

A1.phsA.t MX Other internal source

A1.phsA.units.SIUnit CF [02 01] - IA Magnitude

A1.phsA.units.multiplier CF Other internal source

A1.phsA.db CF Other internal source

A1.phsA.rangeC.hhLim.f CF Other internal source

A1.phsA.rangeC.hLim.f CF Other internal source

A1.phsA.rangeC.lLim.f CF Other internal source

A1.phsA.rangeC.llLim.f CF Other internal source

A1.phsA.rangeC.min.f CF Other internal source

A1.phsA.rangeC.max.f CF Other internal source

A1.phsB.cVal.mag.f MX [02 03] - IB Magnitude

A1.phsB.cVal.ang.f MX [02 04] - IB Phase Angle

A1.phsB.q MX Other internal source

A1.phsB.t MX Other internal source

A1.phsB.units.SIUnit CF [02 03] - IB Magnitude

A1.phsB.units.multiplier CF Other internal source

A1.phsB.db CF Other internal source

A1.phsB.rangeC.hhLim.f CF Other internal source

A1.phsB.rangeC.hLim.f CF Other internal source

A1.phsB.rangeC.lLim.f CF Other internal source

A1.phsB.rangeC.llLim.f CF Other internal source

Page 7: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 6 MiCOM P40Agile P14NB

Attribute FC Source A1.phsB.rangeC.min.f CF Other internal source

A1.phsB.rangeC.max.f CF Other internal source

A1.phsC.cVal.mag.f MX [02 05] - IC Magnitude

A1.phsC.cVal.ang.f MX [02 06] - IC Phase Angle

A1.phsC.q MX Other internal source

A1.phsC.t MX Other internal source

A1.phsC.units.SIUnit CF [02 05] - IC Magnitude

A1.phsC.units.multiplier CF Other internal source

A1.phsC.db CF Other internal source

A1.phsC.rangeC.hhLim.f CF Other internal source

A1.phsC.rangeC.hLim.f CF Other internal source

A1.phsC.rangeC.lLim.f CF Other internal source

A1.phsC.rangeC.llLim.f CF Other internal source

A1.phsC.rangeC.min.f CF Other internal source

A1.phsC.rangeC.max.f CF Other internal source

A1.neut.cVal.mag.f MX [02 09] - IN Derived Mag

A1.neut.cVal.ang.f MX [02 0A] - IN Derived Angle

A1.neut.q MX Other internal source

A1.neut.t MX Other internal source

A1.neut.units.SIUnit CF [02 09] - IN Derived Mag

A1.neut.units.multiplier CF Other internal source

A1.neut.db CF Other internal source

A1.neut.rangeC.hhLim.f CF Other internal source

A1.neut.rangeC.hLim.f CF Other internal source

A1.neut.rangeC.lLim.f CF Other internal source

A1.neut.rangeC.llLim.f CF Other internal source

A1.neut.rangeC.min.f CF Other internal source

A1.neut.rangeC.max.f CF Other internal source

A1.d DC Other internal source

A2.res.cVal.mag.f MX [02 07] - IN Measured Mag

A2.res.cVal.ang.f MX [02 08] - IN Measured Ang

A2.res.q MX Other internal source

A2.res.t MX Other internal source

A2.res.units.SIUnit CF [02 07] - IN Measured Mag

A2.res.units.multiplier CF Other internal source

A2.res.db CF Other internal source

A2.res.rangeC.hhLim.f CF Other internal source

A2.res.rangeC.hLim.f CF Other internal source

A2.res.rangeC.lLim.f CF Other internal source

A2.res.rangeC.llLim.f CF Other internal source

A2.res.rangeC.min.f CF Other internal source

A2.res.rangeC.max.f CF Other internal source

A2.d DC Other internal source

A3.res.cVal.mag.f MX [02 0B] - ISEF Magnitude

A3.res.cVal.ang.f MX [02 0C] - ISEF Angle

A3.res.q MX Other internal source

Page 8: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 7

Attribute FC Source A3.res.t MX Other internal source

A3.res.units.SIUnit CF [02 0B] - ISEF Magnitude

A3.res.units.multiplier CF Other internal source

A3.res.db CF Other internal source

A3.res.rangeC.hhLim.f CF Other internal source

A3.res.rangeC.hLim.f CF Other internal source

A3.res.rangeC.lLim.f CF Other internal source

A3.res.rangeC.llLim.f CF Other internal source

A3.res.rangeC.min.f CF Other internal source

A3.res.rangeC.max.f CF Other internal source

A3.d DC Other internal source

1.3.4 Logical Node: PriMSQI1

Description: Primary Sequence Measurements (No Volts)

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

SeqA.c1.cVal.mag.f MX [02 40] - I1 Magnitude

SeqA.c1.cVal.ang.f MX [02 41] - I1 Phase Angle

SeqA.c1.q MX Other internal source

SeqA.c1.t MX Other internal source

SeqA.c1.units.SIUnit CF [02 40] - I1 Magnitude

SeqA.c1.units.multiplier CF Other internal source

SeqA.c1.db CF Other internal source

SeqA.c1.rangeC.hhLim.f CF Other internal source

SeqA.c1.rangeC.hLim.f CF Other internal source

SeqA.c1.rangeC.lLim.f CF Other internal source

SeqA.c1.rangeC.llLim.f CF Other internal source

SeqA.c1.rangeC.min.f CF Other internal source

SeqA.c1.rangeC.max.f CF Other internal source

SeqA.c2.cVal.mag.f MX [02 42] - I2 Magnitude

SeqA.c2.cVal.ang.f MX [02 43] - I2 Phase Angle

SeqA.c2.q MX Other internal source

SeqA.c2.t MX Other internal source

SeqA.c2.units.SIUnit CF [02 42] - I2 Magnitude

Page 9: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 8 MiCOM P40Agile P14NB

Attribute FC Source SeqA.c2.units.multiplier CF Other internal source

SeqA.c2.db CF Other internal source

SeqA.c2.rangeC.hhLim.f CF Other internal source

SeqA.c2.rangeC.hLim.f CF Other internal source

SeqA.c2.rangeC.lLim.f CF Other internal source

SeqA.c2.rangeC.llLim.f CF Other internal source

SeqA.c2.rangeC.min.f CF Other internal source

SeqA.c2.rangeC.max.f CF Other internal source

SeqA.c3.cVal.mag.f MX [02 44] - I0 Magnitude

SeqA.c3.cVal.ang.f MX [02 45] - I0 Phase Angle

SeqA.c3.q MX Other internal source

SeqA.c3.t MX Other internal source

SeqA.c3.units.SIUnit CF [02 44] - I0 Magnitude

SeqA.c3.units.multiplier CF Other internal source

SeqA.c3.db CF Other internal source

SeqA.c3.rangeC.hhLim.f CF Other internal source

SeqA.c3.rangeC.hLim.f CF Other internal source

SeqA.c3.rangeC.lLim.f CF Other internal source

SeqA.c3.rangeC.llLim.f CF Other internal source

SeqA.c3.rangeC.min.f CF Other internal source

SeqA.c3.rangeC.max.f CF Other internal source

SeqA.seqT MX Other internal source

ImbNgA.mag.f MX [04 0C] - I2/I1 Ratio

ImbNgA.q MX Other internal source

ImbNgA.t MX Other internal source

ImbNgA.units.SIUnit CF [04 0C] - I2/I1 Ratio

ImbNgA.units.multiplier CF Other internal source

ImbNgA.db CF Other internal source

ImbNgA.rangeC.hhLim.f CF Other internal source

ImbNgA.rangeC.hLim.f CF Other internal source

ImbNgA.rangeC.lLim.f CF Other internal source

ImbNgA.rangeC.llLim.f CF Other internal source

ImbNgA.rangeC.min.f CF Other internal source

ImbNgA.rangeC.max.f CF Other internal source

1.3.5 Logical Node: PriMSTA1

Description: Primary Metering Statistics (No Volts)

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Page 10: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 9

Attribute FC Source Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

AvAmps1.mag.f MX [03 18] - IA Fixed Demand

AvAmps1.q MX Other internal source

AvAmps1.t MX Other internal source

AvAmps1.units.SIUnit CF [03 18] - IA Fixed Demand

AvAmps1.units.multiplier CF Other internal source

AvAmps1.db CF Other internal source

AvAmps1.rangeC.hhLim.f CF Other internal source

AvAmps1.rangeC.hLim.f CF Other internal source

AvAmps1.rangeC.lLim.f CF Other internal source

AvAmps1.rangeC.llLim.f CF Other internal source

AvAmps1.rangeC.min.f CF Other internal source

AvAmps1.rangeC.max.f CF Other internal source

AvAmps1.d DC [03 18] - IA Fixed Demand

AvAmps2.mag.f MX [03 19] - IB Fixed Demand

AvAmps2.q MX Other internal source

AvAmps2.t MX Other internal source

AvAmps2.units.SIUnit CF [03 19] - IB Fixed Demand

AvAmps2.units.multiplier CF Other internal source

AvAmps2.db CF Other internal source

AvAmps2.rangeC.hhLim.f CF Other internal source

AvAmps2.rangeC.hLim.f CF Other internal source

AvAmps2.rangeC.lLim.f CF Other internal source

AvAmps2.rangeC.llLim.f CF Other internal source

AvAmps2.rangeC.min.f CF Other internal source

AvAmps2.rangeC.max.f CF Other internal source

AvAmps2.d DC [03 19] - IB Fixed Demand

AvAmps3.mag.f MX [03 1A] - IC Fixed Demand

AvAmps3.q MX Other internal source

AvAmps3.t MX Other internal source

AvAmps3.units.SIUnit CF [03 1A] - IC Fixed Demand

AvAmps3.units.multiplier CF Other internal source

AvAmps3.db CF Other internal source

AvAmps3.rangeC.hhLim.f CF Other internal source

AvAmps3.rangeC.hLim.f CF Other internal source

AvAmps3.rangeC.lLim.f CF Other internal source

AvAmps3.rangeC.llLim.f CF Other internal source

AvAmps3.rangeC.min.f CF Other internal source

AvAmps3.rangeC.max.f CF Other internal source

AvAmps3.d DC [03 1A] - IC Fixed Demand

AvAmps4.mag.f MX [03 1D] - IA Roll Demand

AvAmps4.q MX Other internal source

Page 11: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 10 MiCOM P40Agile P14NB

Attribute FC Source AvAmps4.t MX Other internal source

AvAmps4.units.SIUnit CF [03 1D] - IA Roll Demand

AvAmps4.units.multiplier CF Other internal source

AvAmps4.db CF Other internal source

AvAmps4.rangeC.hhLim.f CF Other internal source

AvAmps4.rangeC.hLim.f CF Other internal source

AvAmps4.rangeC.lLim.f CF Other internal source

AvAmps4.rangeC.llLim.f CF Other internal source

AvAmps4.rangeC.min.f CF Other internal source

AvAmps4.rangeC.max.f CF Other internal source

AvAmps4.d DC [03 1D] - IA Roll Demand

AvAmps5.mag.f MX [03 1E] - IB Roll Demand

AvAmps5.q MX Other internal source

AvAmps5.t MX Other internal source

AvAmps5.units.SIUnit CF [03 1E] - IB Roll Demand

AvAmps5.units.multiplier CF Other internal source

AvAmps5.db CF Other internal source

AvAmps5.rangeC.hhLim.f CF Other internal source

AvAmps5.rangeC.hLim.f CF Other internal source

AvAmps5.rangeC.lLim.f CF Other internal source

AvAmps5.rangeC.llLim.f CF Other internal source

AvAmps5.rangeC.min.f CF Other internal source

AvAmps5.rangeC.max.f CF Other internal source

AvAmps5.d DC [03 1E] - IB Roll Demand

AvAmps6.mag.f MX [03 1F] - IC Roll Demand

AvAmps6.q MX Other internal source

AvAmps6.t MX Other internal source

AvAmps6.units.SIUnit CF [03 1F] - IC Roll Demand

AvAmps6.units.multiplier CF Other internal source

AvAmps6.db CF Other internal source

AvAmps6.rangeC.hhLim.f CF Other internal source

AvAmps6.rangeC.hLim.f CF Other internal source

AvAmps6.rangeC.lLim.f CF Other internal source

AvAmps6.rangeC.llLim.f CF Other internal source

AvAmps6.rangeC.min.f CF Other internal source

AvAmps6.rangeC.max.f CF Other internal source

AvAmps6.d DC [03 1F] - IC Roll Demand

MaxAmps1.mag.f MX [03 22] - IA Peak Demand

MaxAmps1.q MX Other internal source

MaxAmps1.t MX Other internal source

MaxAmps1.units.SIUnit CF [03 22] - IA Peak Demand

MaxAmps1.units.multiplier CF Other internal source

MaxAmps1.db CF Other internal source

MaxAmps1.rangeC.hhLim.f CF Other internal source

MaxAmps1.rangeC.hLim.f CF Other internal source

MaxAmps1.rangeC.lLim.f CF Other internal source

Page 12: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 11

Attribute FC Source MaxAmps1.rangeC.llLim.f CF Other internal source

MaxAmps1.rangeC.min.f CF Other internal source

MaxAmps1.rangeC.max.f CF Other internal source

MaxAmps1.d DC [03 22] - IA Peak Demand

MaxAmps2.mag.f MX [03 23] - IB Peak Demand

MaxAmps2.q MX Other internal source

MaxAmps2.t MX Other internal source

MaxAmps2.units.SIUnit CF [03 23] - IB Peak Demand

MaxAmps2.units.multiplier CF Other internal source

MaxAmps2.db CF Other internal source

MaxAmps2.rangeC.hhLim.f CF Other internal source

MaxAmps2.rangeC.hLim.f CF Other internal source

MaxAmps2.rangeC.lLim.f CF Other internal source

MaxAmps2.rangeC.llLim.f CF Other internal source

MaxAmps2.rangeC.min.f CF Other internal source

MaxAmps2.rangeC.max.f CF Other internal source

MaxAmps2.d DC [03 23] - IB Peak Demand

MaxAmps3.mag.f MX [03 24] - IC Peak Demand

MaxAmps3.q MX Other internal source

MaxAmps3.t MX Other internal source

MaxAmps3.units.SIUnit CF [03 24] - IC Peak Demand

MaxAmps3.units.multiplier CF Other internal source

MaxAmps3.db CF Other internal source

MaxAmps3.rangeC.hhLim.f CF Other internal source

MaxAmps3.rangeC.hLim.f CF Other internal source

MaxAmps3.rangeC.lLim.f CF Other internal source

MaxAmps3.rangeC.llLim.f CF Other internal source

MaxAmps3.rangeC.min.f CF Other internal source

MaxAmps3.rangeC.max.f CF Other internal source

MaxAmps3.d DC [03 24] - IC Peak Demand

1.3.6 Logical Node: PriRmsMMXU1

Description: Primary RMS Measurements (No Volts)

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

Page 13: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 12 MiCOM P40Agile P14NB

Attribute FC Source NamPlt.d DC Other internal source

A.phsA.cVal.mag.f MX [02 10] - IA RMS

A.phsA.q MX Other internal source

A.phsA.t MX Other internal source

A.phsA.units.SIUnit CF [02 10] - IA RMS

A.phsA.units.multiplier CF Other internal source

A.phsA.db CF Other internal source

A.phsA.rangeC.hhLim.f CF Other internal source

A.phsA.rangeC.hLim.f CF Other internal source

A.phsA.rangeC.lLim.f CF Other internal source

A.phsA.rangeC.llLim.f CF Other internal source

A.phsA.rangeC.min.f CF Other internal source

A.phsA.rangeC.max.f CF Other internal source

A.phsB.cVal.mag.f MX [02 11] - IB RMS

A.phsB.q MX Other internal source

A.phsB.t MX Other internal source

A.phsB.units.SIUnit CF [02 11] - IB RMS

A.phsB.units.multiplier CF Other internal source

A.phsB.db CF Other internal source

A.phsB.rangeC.hhLim.f CF Other internal source

A.phsB.rangeC.hLim.f CF Other internal source

A.phsB.rangeC.lLim.f CF Other internal source

A.phsB.rangeC.llLim.f CF Other internal source

A.phsB.rangeC.min.f CF Other internal source

A.phsB.rangeC.max.f CF Other internal source

A.phsC.cVal.mag.f MX [02 12] - IC RMS

A.phsC.q MX Other internal source

A.phsC.t MX Other internal source

A.phsC.units.SIUnit CF [02 11] - IB RMS

A.phsC.units.multiplier CF Other internal source

A.phsC.db CF Other internal source

A.phsC.rangeC.hhLim.f CF Other internal source

A.phsC.rangeC.hLim.f CF Other internal source

A.phsC.rangeC.lLim.f CF Other internal source

A.phsC.rangeC.llLim.f CF Other internal source

A.phsC.rangeC.min.f CF Other internal source

A.phsC.rangeC.max.f CF Other internal source

A.d DC Other internal source

1.3.7 Logical Node: SecFouMMXU1

Description: Secondary Fourier Measurements (No Volts)

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Page 14: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 13

Attribute FC Source Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

Hz.mag.f MX [02 2D] - Frequency

Hz.q MX Other internal source

Hz.t MX Other internal source

Hz.units.SIUnit CF [02 2D] - Frequency

Hz.units.multiplier CF Other internal source

Hz.db CF Other internal source

Hz.rangeC.hhLim.f CF Other internal source

Hz.rangeC.hLim.f CF Other internal source

Hz.rangeC.lLim.f CF Other internal source

Hz.rangeC.llLim.f CF Other internal source

Hz.rangeC.min.f CF Other internal source

Hz.rangeC.max.f CF Other internal source

A1.phsA.cVal.mag.f MX [02 01] - IA Magnitude

A1.phsA.cVal.ang.f MX [02 02] - IA Phase Angle

A1.phsA.q MX Other internal source

A1.phsA.t MX Other internal source

A1.phsA.units.SIUnit CF [02 01] - IA Magnitude

A1.phsA.units.multiplier CF Other internal source

A1.phsA.db CF Other internal source

A1.phsA.rangeC.hhLim.f CF Other internal source

A1.phsA.rangeC.hLim.f CF Other internal source

A1.phsA.rangeC.lLim.f CF Other internal source

A1.phsA.rangeC.llLim.f CF Other internal source

A1.phsA.rangeC.min.f CF Other internal source

A1.phsA.rangeC.max.f CF Other internal source

A1.phsB.cVal.mag.f MX [02 03] - IB Magnitude

A1.phsB.cVal.ang.f MX [02 04] - IB Phase Angle

A1.phsB.q MX Other internal source

A1.phsB.t MX Other internal source

A1.phsB.units.SIUnit CF [02 03] - IB Magnitude

A1.phsB.units.multiplier CF Other internal source

A1.phsB.db CF Other internal source

A1.phsB.rangeC.hhLim.f CF Other internal source

A1.phsB.rangeC.hLim.f CF Other internal source

A1.phsB.rangeC.lLim.f CF Other internal source

A1.phsB.rangeC.llLim.f CF Other internal source

A1.phsB.rangeC.min.f CF Other internal source

Page 15: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 14 MiCOM P40Agile P14NB

Attribute FC Source A1.phsB.rangeC.max.f CF Other internal source

A1.phsC.cVal.mag.f MX [02 05] - IC Magnitude

A1.phsC.cVal.ang.f MX [02 06] - IC Phase Angle

A1.phsC.q MX Other internal source

A1.phsC.t MX Other internal source

A1.phsC.units.SIUnit CF [02 05] - IC Magnitude

A1.phsC.units.multiplier CF Other internal source

A1.phsC.db CF Other internal source

A1.phsC.rangeC.hhLim.f CF Other internal source

A1.phsC.rangeC.hLim.f CF Other internal source

A1.phsC.rangeC.lLim.f CF Other internal source

A1.phsC.rangeC.llLim.f CF Other internal source

A1.phsC.rangeC.min.f CF Other internal source

A1.phsC.rangeC.max.f CF Other internal source

A1.neut.cVal.mag.f MX [02 09] - IN Derived Mag

A1.neut.cVal.ang.f MX [02 0A] - IN Derived Angle

A1.neut.q MX Other internal source

A1.neut.t MX Other internal source

A1.neut.units.SIUnit CF [02 09] - IN Derived Mag

A1.neut.units.multiplier CF Other internal source

A1.neut.db CF Other internal source

A1.neut.rangeC.hhLim.f CF Other internal source

A1.neut.rangeC.hLim.f CF Other internal source

A1.neut.rangeC.lLim.f CF Other internal source

A1.neut.rangeC.llLim.f CF Other internal source

A1.neut.rangeC.min.f CF Other internal source

A1.neut.rangeC.max.f CF Other internal source

A1.d DC Other internal source

A2.res.cVal.mag.f MX [02 07] - IN Measured Mag

A2.res.cVal.ang.f MX [02 08] - IN Measured Ang

A2.res.q MX Other internal source

A2.res.t MX Other internal source

A2.res.units.SIUnit CF [02 07] - IN Measured Mag

A2.res.units.multiplier CF Other internal source

A2.res.db CF Other internal source

A2.res.rangeC.hhLim.f CF Other internal source

A2.res.rangeC.hLim.f CF Other internal source

A2.res.rangeC.lLim.f CF Other internal source

A2.res.rangeC.llLim.f CF Other internal source

A2.res.rangeC.min.f CF Other internal source

A2.res.rangeC.max.f CF Other internal source

A2.d DC Other internal source

A3.res.cVal.mag.f MX [02 0B] - ISEF Magnitude

A3.res.cVal.ang.f MX [02 0C] - ISEF Angle

A3.res.q MX Other internal source

A3.res.t MX Other internal source

Page 16: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 15

Attribute FC Source A3.res.units.SIUnit CF [02 0B] - ISEF Magnitude

A3.res.units.multiplier CF Other internal source

A3.res.db CF Other internal source

A3.res.rangeC.hhLim.f CF Other internal source

A3.res.rangeC.hLim.f CF Other internal source

A3.res.rangeC.lLim.f CF Other internal source

A3.res.rangeC.llLim.f CF Other internal source

A3.res.rangeC.min.f CF Other internal source

A3.res.rangeC.max.f CF Other internal source

A3.d DC Other internal source

1.3.8 Logical Node: SecMSQI1

Description: Secondary based metering quantities (No Volts)

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

SeqA.c1.cVal.mag.f MX [02 40] - I1 Magnitude

SeqA.c1.cVal.ang.f MX [02 41] - I1 Phase Angle

SeqA.c1.q MX Other internal source

SeqA.c1.t MX Other internal source

SeqA.c1.units.SIUnit CF [02 40] - I1 Magnitude

SeqA.c1.units.multiplier CF Other internal source

SeqA.c1.db CF Other internal source

SeqA.c1.rangeC.hhLim.f CF Other internal source

SeqA.c1.rangeC.hLim.f CF Other internal source

SeqA.c1.rangeC.lLim.f CF Other internal source

SeqA.c1.rangeC.llLim.f CF Other internal source

SeqA.c1.rangeC.min.f CF Other internal source

SeqA.c1.rangeC.max.f CF Other internal source

SeqA.c2.cVal.mag.f MX [02 42] - I2 Magnitude

SeqA.c2.cVal.ang.f MX [02 43] - I2 Phase Angle

SeqA.c2.q MX Other internal source

SeqA.c2.t MX Other internal source

SeqA.c2.units.SIUnit CF [02 42] - I2 Magnitude

SeqA.c2.units.multiplier CF Other internal source

Page 17: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 16 MiCOM P40Agile P14NB

Attribute FC Source SeqA.c2.db CF Other internal source

SeqA.c2.rangeC.hhLim.f CF Other internal source

SeqA.c2.rangeC.hLim.f CF Other internal source

SeqA.c2.rangeC.lLim.f CF Other internal source

SeqA.c2.rangeC.llLim.f CF Other internal source

SeqA.c2.rangeC.min.f CF Other internal source

SeqA.c2.rangeC.max.f CF Other internal source

SeqA.c3.cVal.mag.f MX [02 44] - I0 Magnitude

SeqA.c3.cVal.ang.f MX [02 45] - I0 Phase Angle

SeqA.c3.q MX Other internal source

SeqA.c3.t MX Other internal source

SeqA.c3.units.SIUnit CF [02 44] - I0 Magnitude

SeqA.c3.units.multiplier CF Other internal source

SeqA.c3.db CF Other internal source

SeqA.c3.rangeC.hhLim.f CF Other internal source

SeqA.c3.rangeC.hLim.f CF Other internal source

SeqA.c3.rangeC.lLim.f CF Other internal source

SeqA.c3.rangeC.llLim.f CF Other internal source

SeqA.c3.rangeC.min.f CF Other internal source

SeqA.c3.rangeC.max.f CF Other internal source

SeqA.seqT MX Other internal source

ImbNgA.mag.f MX [04 0C] - I2/I1 Ratio

ImbNgA.q MX Other internal source

ImbNgA.t MX Other internal source

ImbNgA.units.SIUnit CF [04 0C] - I2/I1 Ratio

ImbNgA.units.multiplier CF Other internal source

ImbNgA.db CF Other internal source

ImbNgA.rangeC.hhLim.f CF Other internal source

ImbNgA.rangeC.hLim.f CF Other internal source

ImbNgA.rangeC.lLim.f CF Other internal source

ImbNgA.rangeC.llLim.f CF Other internal source

ImbNgA.rangeC.min.f CF Other internal source

ImbNgA.rangeC.max.f CF Other internal source

Page 18: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 17 1.3.9 Logical Node: SecMSTA1

Description: Secondary Metering Statistics (No Volts)

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

AvAmps1.mag.f MX [03 18] - IA Fixed Demand

AvAmps1.q MX Other internal source

AvAmps1.t MX Other internal source

AvAmps1.units.SIUnit CF [03 18] - IA Fixed Demand

AvAmps1.units.multiplier CF Other internal source

AvAmps1.db CF Other internal source

AvAmps1.rangeC.hhLim.f CF Other internal source

AvAmps1.rangeC.hLim.f CF Other internal source

AvAmps1.rangeC.lLim.f CF Other internal source

AvAmps1.rangeC.llLim.f CF Other internal source

AvAmps1.rangeC.min.f CF Other internal source

AvAmps1.rangeC.max.f CF Other internal source

AvAmps1.d DC [03 18] - IA Fixed Demand

AvAmps2.mag.f MX [03 19] - IB Fixed Demand

AvAmps2.q MX Other internal source

AvAmps2.t MX Other internal source

AvAmps2.units.SIUnit CF [03 19] - IB Fixed Demand

AvAmps2.units.multiplier CF Other internal source

AvAmps2.db CF Other internal source

AvAmps2.rangeC.hhLim.f CF Other internal source

AvAmps2.rangeC.hLim.f CF Other internal source

AvAmps2.rangeC.lLim.f CF Other internal source

AvAmps2.rangeC.llLim.f CF Other internal source

AvAmps2.rangeC.min.f CF Other internal source

AvAmps2.rangeC.max.f CF Other internal source

AvAmps2.d DC [03 19] - IB Fixed Demand

AvAmps3.mag.f MX [03 1A] - IC Fixed Demand

AvAmps3.q MX Other internal source

AvAmps3.t MX Other internal source

AvAmps3.units.SIUnit CF [03 1A] - IC Fixed Demand

Page 19: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 18 MiCOM P40Agile P14NB

Attribute FC Source AvAmps3.units.multiplier CF Other internal source

AvAmps3.db CF Other internal source

AvAmps3.rangeC.hhLim.f CF Other internal source

AvAmps3.rangeC.hLim.f CF Other internal source

AvAmps3.rangeC.lLim.f CF Other internal source

AvAmps3.rangeC.llLim.f CF Other internal source

AvAmps3.rangeC.min.f CF Other internal source

AvAmps3.rangeC.max.f CF Other internal source

AvAmps3.d DC [03 1A] - IC Fixed Demand

AvAmps4.mag.f MX [03 1D] - IA Roll Demand

AvAmps4.q MX Other internal source

AvAmps4.t MX Other internal source

AvAmps4.units.SIUnit CF [03 1D] - IA Roll Demand

AvAmps4.units.multiplier CF Other internal source

AvAmps4.db CF Other internal source

AvAmps4.rangeC.hhLim.f CF Other internal source

AvAmps4.rangeC.hLim.f CF Other internal source

AvAmps4.rangeC.lLim.f CF Other internal source

AvAmps4.rangeC.llLim.f CF Other internal source

AvAmps4.rangeC.min.f CF Other internal source

AvAmps4.rangeC.max.f CF Other internal source

AvAmps4.d DC [03 1D] - IA Roll Demand

AvAmps5.mag.f MX [03 1E] - IB Roll Demand

AvAmps5.q MX Other internal source

AvAmps5.t MX Other internal source

AvAmps5.units.SIUnit CF [03 1E] - IB Roll Demand

AvAmps5.units.multiplier CF Other internal source

AvAmps5.db CF Other internal source

AvAmps5.rangeC.hhLim.f CF Other internal source

AvAmps5.rangeC.hLim.f CF Other internal source

AvAmps5.rangeC.lLim.f CF Other internal source

AvAmps5.rangeC.llLim.f CF Other internal source

AvAmps5.rangeC.min.f CF Other internal source

AvAmps5.rangeC.max.f CF Other internal source

AvAmps5.d DC [03 1E] - IB Roll Demand

AvAmps6.mag.f MX [03 1F] - IC Roll Demand

AvAmps6.q MX Other internal source

AvAmps6.t MX Other internal source

AvAmps6.units.SIUnit CF [03 1F] - IC Roll Demand

AvAmps6.units.multiplier CF Other internal source

AvAmps6.db CF Other internal source

AvAmps6.rangeC.hhLim.f CF Other internal source

AvAmps6.rangeC.hLim.f CF Other internal source

AvAmps6.rangeC.lLim.f CF Other internal source

AvAmps6.rangeC.llLim.f CF Other internal source

AvAmps6.rangeC.min.f CF Other internal source

Page 20: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 19

Attribute FC Source AvAmps6.rangeC.max.f CF Other internal source

AvAmps6.d DC [03 1F] - IC Roll Demand

MaxAmps1.mag.f MX [03 22] - IA Peak Demand

MaxAmps1.q MX Other internal source

MaxAmps1.t MX Other internal source

MaxAmps1.units.SIUnit CF [03 22] - IA Peak Demand

MaxAmps1.units.multiplier CF Other internal source

MaxAmps1.db CF Other internal source

MaxAmps1.rangeC.hhLim.f CF Other internal source

MaxAmps1.rangeC.hLim.f CF Other internal source

MaxAmps1.rangeC.lLim.f CF Other internal source

MaxAmps1.rangeC.llLim.f CF Other internal source

MaxAmps1.rangeC.min.f CF Other internal source

MaxAmps1.rangeC.max.f CF Other internal source

MaxAmps1.d DC [03 22] - IA Peak Demand

MaxAmps2.mag.f MX [03 23] - IB Peak Demand

MaxAmps2.q MX Other internal source

MaxAmps2.t MX Other internal source

MaxAmps2.units.SIUnit CF [03 23] - IB Peak Demand

MaxAmps2.units.multiplier CF Other internal source

MaxAmps2.db CF Other internal source

MaxAmps2.rangeC.hhLim.f CF Other internal source

MaxAmps2.rangeC.hLim.f CF Other internal source

MaxAmps2.rangeC.lLim.f CF Other internal source

MaxAmps2.rangeC.llLim.f CF Other internal source

MaxAmps2.rangeC.min.f CF Other internal source

MaxAmps2.rangeC.max.f CF Other internal source

MaxAmps2.d DC [03 23] - IB Peak Demand

MaxAmps3.mag.f MX [03 24] - IC Peak Demand

MaxAmps3.q MX Other internal source

MaxAmps3.t MX Other internal source

MaxAmps3.units.SIUnit CF [03 24] - IC Peak Demand

MaxAmps3.units.multiplier CF Other internal source

MaxAmps3.db CF Other internal source

MaxAmps3.rangeC.hhLim.f CF Other internal source

MaxAmps3.rangeC.hLim.f CF Other internal source

MaxAmps3.rangeC.lLim.f CF Other internal source

MaxAmps3.rangeC.llLim.f CF Other internal source

MaxAmps3.rangeC.min.f CF Other internal source

MaxAmps3.rangeC.max.f CF Other internal source

MaxAmps3.d DC [03 24] - IC Peak Demand

Page 21: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 20 MiCOM P40Agile P14NB 1.3.10 Logical Node: SecRmsMMXU1

Description: Secondary RMS Measurements (No Volts)

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

A.phsA.cVal.mag.f MX [02 10] - IA RMS

A.phsA.q MX Other internal source

A.phsA.t MX Other internal source

A.phsA.units.SIUnit CF [02 10] - IA RMS

A.phsA.units.multiplier CF Other internal source

A.phsA.db CF Other internal source

A.phsA.rangeC.hhLim.f CF Other internal source

A.phsA.rangeC.hLim.f CF Other internal source

A.phsA.rangeC.lLim.f CF Other internal source

A.phsA.rangeC.llLim.f CF Other internal source

A.phsA.rangeC.min.f CF Other internal source

A.phsA.rangeC.max.f CF Other internal source

A.phsB.cVal.mag.f MX [02 11] - IB RMS

A.phsB.q MX Other internal source

A.phsB.t MX Other internal source

A.phsB.units.SIUnit CF [02 11] - IB RMS

A.phsB.units.multiplier CF Other internal source

A.phsB.db CF Other internal source

A.phsB.rangeC.hhLim.f CF Other internal source

A.phsB.rangeC.hLim.f CF Other internal source

A.phsB.rangeC.lLim.f CF Other internal source

A.phsB.rangeC.llLim.f CF Other internal source

A.phsB.rangeC.min.f CF Other internal source

A.phsB.rangeC.max.f CF Other internal source

A.phsC.cVal.mag.f MX [02 12] - IC RMS

A.phsC.q MX Other internal source

A.phsC.t MX Other internal source

A.phsC.units.SIUnit CF [02 11] - IB RMS

A.phsC.units.multiplier CF Other internal source

A.phsC.db CF Other internal source

Page 22: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 21

Attribute FC Source A.phsC.rangeC.hhLim.f CF Other internal source

A.phsC.rangeC.hLim.f CF Other internal source

A.phsC.rangeC.lLim.f CF Other internal source

A.phsC.rangeC.llLim.f CF Other internal source

A.phsC.rangeC.min.f CF Other internal source

A.phsC.rangeC.max.f CF Other internal source

A.d DC Other internal source

1.4 LOGICAL PROTECTION

This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data Attributes within Logical Nodes contained in the Protection Logical Device.

1.4.1 Logical Node: CbfRBRF1

Description: CB Fail 1

Attribute FC Source Mod.stVal ST [45 02] - CB Fail 1 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [45 02] - CB Fail 1 Status

OpEx.general ST DDB_CBF1_TRIP_3PH (353)

OpEx.q ST Other internal source

OpEx.t ST Other internal source

1.4.2 Logical Node: CbfRBRF2

Description: CB Fail 2

Attribute FC Source Mod.stVal ST [45 04] - CB Fail 2 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

Page 23: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 22 MiCOM P40Agile P14NB

Attribute FC Source NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [45 04] - CB Fail 2 Status

OpEx.general ST DDB_CBF2_TRIP_3PH (354)

OpEx.q ST Other internal source

OpEx.t ST Other internal source

1.4.3 Logical Node: EfdPTOC1

Description: IN2> 1 Earth Fault (Derived)

Attribute FC Source Mod.stVal ST [39 25] - IN2>1 Function

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [39 25] - IN2>1 Function

Str.general ST DDB_EF2_1_START (319)

Str.dirGeneral ST [39 26] - IN2>1 Direction

Str.neut ST DDB_EF2_1_START (319)

Str.dirNeut ST [39 26] - IN2>1 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_EF2_1_TRIP (265)

Op.neut ST DDB_EF2_1_TRIP (265)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.4 Logical Node: EfdPTOC2

Description: IN2> 2 Earth Fault (Derived)

Attribute FC Source Mod.stVal ST [39 36] - IN2>2 Function

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

Page 24: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 23

Attribute FC Source NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [39 36] - IN2>2 Function

Str.general ST DDB_EF2_2_START (320)

Str.dirGeneral ST [39 37] - IN2>2 Direction

Str.neut ST DDB_EF2_2_START (320)

Str.dirNeut ST [39 37] - IN2>2 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_EF2_2_TRIP (266)

Op.neut ST DDB_EF2_2_TRIP (266)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.5 Logical Node: EfdPTOC3

Description: IN2> 3 Earth Fault (Derived)

Attribute FC Source Mod.stVal ST [39 46] - IN2>3 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [39 46] - IN2>3 Status

Str.general ST DDB_EF2_3_START (321)

Str.dirGeneral ST [39 47] - IN2>3 Direction

Str.neut ST DDB_EF2_3_START (321)

Str.dirNeut ST [39 47] - IN2>3 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_EF2_3_TRIP (267)

Op.neut ST DDB_EF2_3_TRIP (267)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.6 Logical Node: EfdPTOC4

Description: IN2> 4 Earth Fault (Derived)

Attribute FC Source Mod.stVal ST [39 4D] - IN2>4 Status

Mod.q ST Other internal source

Page 25: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 24 MiCOM P40Agile P14NB

Attribute FC Source Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [39 4D] - IN2>4 Status

Str.general ST DDB_EF2_4_START (322)

Str.dirGeneral ST [39 4E] - IN2>4 Direction

Str.neut ST DDB_EF2_4_START (322)

Str.dirNeut ST [39 4E] - IN2>4 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_EF2_4_TRIP (268)

Op.neut ST DDB_EF2_4_TRIP (268)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.7 Logical Node: EfmPTOC1

Description: IN1> 1 Earth Fault (Measured)

Attribute FC Source Mod.stVal ST [38 25] - IN1>1 Function

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [38 25] - IN1>1 Function

Str.general ST DDB_EF1_1_START (315)

Str.dirGeneral ST [38 26] - IN1>1 Direction

Str.neut ST DDB_EF1_1_START (315)

Str.dirNeut ST [38 26] - IN1>1 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_EF1_1_TRIP (261)

Op.neut ST DDB_EF1_1_TRIP (261)

Page 26: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 25

Attribute FC Source Op.q ST Other internal source

Op.t ST Other internal source

1.4.8 Logical Node: EfmPTOC2

Description: IN1> 2 Earth Fault (Measured)

Attribute FC Source Mod.stVal ST [38 36] - IN1>2 Function

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [38 36] - IN1>2 Function

Str.general ST DDB_EF1_2_START (316)

Str.dirGeneral ST [38 37] - IN1>2 Direction

Str.neut ST DDB_EF1_2_START (316)

Str.dirNeut ST [38 37] - IN1>2 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_EF1_2_TRIP (262)

Op.neut ST DDB_EF1_2_TRIP (262)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.9 Logical Node: EfmPTOC3

Description: IN1> 3 Earth Fault (Measured)

Attribute FC Source Mod.stVal ST [38 46] - IN1>3 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [38 46] - IN1>3 Status

Page 27: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 26 MiCOM P40Agile P14NB

Attribute FC Source Str.general ST DDB_EF1_3_START (317)

Str.dirGeneral ST [38 47] - IN1>3 Direction

Str.neut ST DDB_EF1_3_START (317)

Str.dirNeut ST [38 47] - IN1>3 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_EF1_3_TRIP (263)

Op.neut ST DDB_EF1_3_TRIP (263)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.10 Logical Node: EfmPTOC4

Description: IN1> 4 Earth Fault (Measured)

Attribute FC Source Mod.stVal ST [38 4D] - IN1>4 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [38 4D] - IN1>4 Status

Str.general ST DDB_EF1_4_START (318)

Str.dirGeneral ST [38 4E] - IN1>4 Direction

Str.neut ST DDB_EF1_4_START (318)

Str.dirNeut ST [38 4E] - IN1>4 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_EF1_4_TRIP (264)

Op.neut ST DDB_EF1_4_TRIP (264)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.11 Logical Node: LLN0

Description: Protection Logical device

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Page 28: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 27

Attribute FC Source Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

NamPlt.configRev DC Other internal source

NamPlt.ldNs EX Other internal source

OcpMod.ctlVal CO [09 10] - Overcurrent

OcpMod.stVal ST [09 10] - Overcurrent

OcpMod.q ST Other internal source

OcpMod.t ST Other internal source

OcpMod.ctlModel CF Other internal source

OcpMod.cdcNs EX Other internal source

OcpMod.cdcName EX Other internal source

OcpMod.dataNs EX Other internal source

OcpBeh.stVal ST [09 10] - Overcurrent

OcpBeh.q ST Other internal source

OcpBeh.t ST Other internal source

OcpBeh.d DC [09 10] - Overcurrent

OcpBeh.dataNs EX Other internal source

NgcMod.ctlVal CO [09 11] - Neg Sequence O/C

NgcMod.stVal ST [09 11] - Neg Sequence O/C

NgcMod.q ST Other internal source

NgcMod.t ST Other internal source

NgcMod.ctlModel CF Other internal source

NgcMod.cdcNs EX Other internal source

NgcMod.cdcName EX Other internal source

NgcMod.dataNs EX Other internal source

NgcBeh.stVal ST [09 11] - Neg Sequence O/C

NgcBeh.q ST Other internal source

NgcBeh.t ST Other internal source

NgcBeh.d DC [09 11] - Neg Sequence O/C

NgcBeh.dataNs EX Other internal source

EfmMod.ctlVal CO [09 13] - Earth Fault 1

EfmMod.stVal ST [09 13] - Earth Fault 1

EfmMod.q ST Other internal source

EfmMod.t ST Other internal source

EfmMod.ctlModel CF Other internal source

EfmMod.cdcNs EX Other internal source

EfmMod.cdcName EX Other internal source

EfmMod.dataNs EX Other internal source

EfmBeh.stVal ST [09 13] - Earth Fault 1

EfmBeh.q ST Other internal source

Page 29: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 28 MiCOM P40Agile P14NB

Attribute FC Source EfmBeh.t ST Other internal source

EfmBeh.d DC [09 13] - Earth Fault 1

EfmBeh.dataNs EX Other internal source

EfdMod.ctlVal CO [09 14] - Earth Fault 2

EfdMod.stVal ST [09 14] - Earth Fault 2

EfdMod.q ST Other internal source

EfdMod.t ST Other internal source

EfdMod.ctlModel CF Other internal source

EfdMod.cdcNs EX Other internal source

EfdMod.cdcName EX Other internal source

EfdMod.dataNs EX Other internal source

EfdBeh.stVal ST [09 14] - Earth Fault 2

EfdBeh.q ST Other internal source

EfdBeh.t ST Other internal source

EfdBeh.d DC [09 14] - Earth Fault 2

EfdBeh.dataNs EX Other internal source

SenMod.ctlVal CO [09 15] - SEF/REF Prot'n

SenMod.stVal ST [09 15] - SEF/REF Prot'n

SenMod.q ST Other internal source

SenMod.t ST Other internal source

SenMod.ctlModel CF Other internal source

SenMod.cdcNs EX Other internal source

SenMod.cdcName EX Other internal source

SenMod.dataNs EX Other internal source

SenBeh.stVal ST [09 15] - SEF/REF Prot'n

SenBeh.q ST Other internal source

SenBeh.t ST Other internal source

SenBeh.d DC [09 15] - SEF/REF Prot'n

SenBeh.dataNs EX Other internal source

ThmMod.ctlVal CO [09 17] - Thermal Overload

ThmMod.stVal ST [09 17] - Thermal Overload

ThmMod.q ST Other internal source

ThmMod.t ST Other internal source

ThmMod.ctlModel CF Other internal source

ThmMod.cdcNs EX Other internal source

ThmMod.cdcName EX Other internal source

ThmMod.dataNs EX Other internal source

ThmBeh.stVal ST [09 17] - Thermal Overload

ThmBeh.q ST Other internal source

ThmBeh.t ST Other internal source

ThmBeh.d DC [09 17] - Thermal Overload

ThmBeh.dataNs EX Other internal source

CbfMod.ctlVal CO [09 20] - CB Fail

CbfMod.stVal ST [09 20] - CB Fail

CbfMod.q ST Other internal source

CbfMod.t ST Other internal source

Page 30: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 29

Attribute FC Source CbfMod.ctlModel CF Other internal source

CbfMod.cdcNs EX Other internal source

CbfMod.cdcName EX Other internal source

CbfMod.dataNs EX Other internal source

CbfBeh.stVal ST [09 20] - CB Fail

CbfBeh.q ST Other internal source

CbfBeh.t ST Other internal source

CbfBeh.d DC [09 20] - CB Fail

CbfBeh.dataNs EX Other internal source

1.4.12 Logical Node: LPHD1

Description: Physical Device Information

Attribute FC Source PhyNam.vendor DC Other internal source

PhyNam.hwRev DC Other internal source

PhyNam.swRev DC [00 11] - Software Ref. 1

PhyNam.serNum DC [00 08] - Serial Number

PhyNam.model DC [00 06] - Model Number

PhyNam.location DC [00 05] - Plant Reference

PhyHealth.stVal ST Other internal source

PhyHealth.q ST Other internal source

PhyHealth.t ST Other internal source

Proxy.stVal ST Other internal source

Proxy.q ST Other internal source

Proxy.t ST Other internal source

Proxy.d DC Other internal source

PwrUp.stVal ST Other internal source

PwrUp.q ST Other internal source

PwrUp.t ST Other internal source

PwrUp.d DC Other internal source

1.4.13 Logical Node: NgcPTOC1

Description: I2> 1 Negative Sequence

Attribute FC Source Mod.stVal ST [36 10] - I2>1 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

Page 31: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 30 MiCOM P40Agile P14NB

Attribute FC Source NamPlt.d DC [36 10] - I2>1 Status

Str.general ST DDB_NPSOC_1_START (509)

Str.dirGeneral ST [36 12] - I2>1 Directional

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_NPSOC_1_TRIP (513)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.14 Logical Node: NgcPTOC2

Description: I2> 2 Negative Sequence

Attribute FC Source Mod.stVal ST [36 20] - I2>2 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [36 20] - I2>2 Status

Str.general ST DDB_NPSOC_2_START (510)

Str.dirGeneral ST [36 22] - I2>2 Directional

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_NPSOC_2_TRIP (514)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.15 Logical Node: NgcPTOC3

Description: I2> 3 Negative Sequence

Attribute FC Source Mod.stVal ST [36 30] - I2>3 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

Page 32: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 31

Attribute FC Source NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [36 30] - I2>3 Status

Str.general ST DDB_NPSOC_3_START (511)

Str.dirGeneral ST [36 32] - I2>3 Directional

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_NPSOC_3_TRIP (515)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.16 Logical Node: NgcPTOC4

Description: I2> 4 Negative Sequence

Attribute FC Source Mod.stVal ST [36 40] - I2>4 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [36 40] - I2>4 Status

Str.general ST DDB_NPSOC_4_START (512)

Str.dirGeneral ST [36 42] - I2>4 Directional

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_NPSOC_4_TRIP (516)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.17 Logical Node: OcpPTOC1

Description: I> 1 Overcurrent

Attribute FC Source Mod.stVal ST [35 23] - I>1 Function

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Page 33: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 32 MiCOM P40Agile P14NB

Attribute FC Source Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [35 23] - I>1 Function

Str.general ST DDB_POC_1_3PH_START (295)

Str.dirGeneral ST [35 24] - I>1 Direction

Str.phsA ST DDB_POC_1_PH_A_START (296)

Str.dirPhsA ST [35 24] - I>1 Direction

Str.phsB ST DDB_POC_1_PH_B_START (297)

Str.dirPhsB ST [35 24] - I>1 Direction

Str.phsC ST DDB_POC_1_PH_C_START (298)

Str.dirPhsC ST [35 24] - I>1 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_POC_1_3PH_TRIP (243)

Op.phsA ST DDB_POC_1_PH_A_TRIP (244)

Op.phsB ST DDB_POC_1_PH_B_TRIP (245)

Op.phsC ST DDB_POC_1_PH_C_TRIP (246)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.18 Logical Node: OcpPTOC2

Description: I> 2 Overcurrent

Attribute FC Source Mod.stVal ST [35 32] - I>2 Function

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [35 32] - I>2 Function

Str.general ST DDB_POC_2_3PH_START (299)

Str.dirGeneral ST [35 33] - I>2 Direction

Str.phsA ST DDB_POC_2_PH_A_START (300)

Str.dirPhsA ST [35 33] - I>2 Direction

Str.phsB ST DDB_POC_2_PH_B_START (301)

Str.dirPhsB ST [35 33] - I>2 Direction

Str.phsC ST DDB_POC_2_PH_C_START (302)

Str.dirPhsC ST [35 33] - I>2 Direction

Page 34: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 33

Attribute FC Source Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_POC_2_3PH_TRIP (247)

Op.phsA ST DDB_POC_2_PH_A_TRIP (248)

Op.phsB ST DDB_POC_2_PH_B_TRIP (249)

Op.phsC ST DDB_POC_2_PH_C_TRIP (250)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.19 Logical Node: OcpPTOC3

Description: I> 3 Overcurrent

Attribute FC Source Mod.stVal ST [35 40] - I>3 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [35 40] - I>3 Status

Str.general ST DDB_POC_3_3PH_START (303)

Str.dirGeneral ST [35 41] - I>3 Direction

Str.phsA ST DDB_POC_3_PH_A_START (304)

Str.dirPhsA ST [35 41] - I>3 Direction

Str.phsB ST DDB_POC_3_PH_B_START (305)

Str.dirPhsB ST [35 41] - I>3 Direction

Str.phsC ST DDB_POC_3_PH_C_START (306)

Str.dirPhsC ST [35 41] - I>3 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_POC_3_3PH_TRIP (251)

Op.phsA ST DDB_POC_3_PH_A_TRIP (252)

Op.phsB ST DDB_POC_3_PH_B_TRIP (253)

Op.phsC ST DDB_POC_3_PH_C_TRIP (254)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.20 Logical Node: OcpPTOC4

Description: I> 4 Overcurrent

Attribute FC Source Mod.stVal ST [35 47] - I>4 Status

Page 35: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 34 MiCOM P40Agile P14NB

Attribute FC Source Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [35 47] - I>4 Status

Str.general ST DDB_POC_4_3PH_START (307)

Str.dirGeneral ST [35 48] - I>4 Direction

Str.phsA ST DDB_POC_4_PH_A_START (308)

Str.dirPhsA ST [35 48] - I>4 Direction

Str.phsB ST DDB_POC_4_PH_B_START (309)

Str.dirPhsB ST [35 48] - I>4 Direction

Str.phsC ST DDB_POC_4_PH_C_START (310)

Str.dirPhsC ST [35 48] - I>4 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_POC_4_3PH_TRIP (255)

Op.phsA ST DDB_POC_4_PH_A_TRIP (256)

Op.phsB ST DDB_POC_4_PH_B_TRIP (257)

Op.phsC ST DDB_POC_4_PH_C_TRIP (258)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.21 Logical Node: OcpPTOC5

Description: I> 5 Overcurrent

Attribute FC Source Mod.stVal ST [35 63] - I>5 Function

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [35 63] - I>5 Function

Str.general ST DDB_POC_5_3PH_START (579)

Page 36: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 35

Attribute FC Source Str.dirGeneral ST [35 64] - I>5 Direction

Str.phsA ST DDB_POC_5_PH_A_START (580)

Str.dirPhsA ST [35 64] - I>5 Direction

Str.phsB ST DDB_POC_5_PH_B_START (581)

Str.dirPhsB ST [35 64] - I>5 Direction

Str.phsC ST DDB_POC_5_PH_C_START (582)

Str.dirPhsC ST [35 64] - I>5 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_POC_5_3PH_TRIP (570)

Op.phsA ST DDB_POC_5_PH_A_TRIP (571)

Op.phsB ST DDB_POC_5_PH_B_TRIP (572)

Op.phsC ST DDB_POC_5_PH_C_TRIP (573)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.22 Logical Node: OcpPTOC6

Description: I> 6 Overcurrent

Attribute FC Source Mod.stVal ST [35 71] - I>6 Status

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [35 71] - I>6 Status

Str.general ST DDB_POC_6_3PH_START (583)

Str.dirGeneral ST [35 72] - I>6 Direction

Str.phsA ST DDB_POC_6_PH_A_START (584)

Str.dirPhsA ST [35 72] - I>6 Direction

Str.phsB ST DDB_POC_6_PH_B_START (585)

Str.dirPhsB ST [35 72] - I>6 Direction

Str.phsC ST DDB_POC_6_PH_C_START (586)

Str.dirPhsC ST [35 72] - I>6 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_POC_6_3PH_TRIP (574)

Op.phsA ST DDB_POC_6_PH_A_TRIP (575)

Op.phsB ST DDB_POC_6_PH_B_TRIP (576)

Op.phsC ST DDB_POC_6_PH_C_TRIP (577)

Page 37: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 36 MiCOM P40Agile P14NB

Attribute FC Source Op.q ST Other internal source

Op.t ST Other internal source

1.4.23 Logical Node: PTRC1

Description: Protection Trip Conditioning

Attribute FC Source Mod.stVal ST [0F 0D] - Test Mode

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST [0F 0D] - Test Mode

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

Tr.general ST DDB_ANY_TRIP (536)

Tr.q ST Other internal source

Tr.t ST Other internal source

Str.general ST DDB_ANY_START (294)

Str.dirGeneral ST Other internal source

Str.q ST Other internal source

Str.t ST Other internal source

1.4.24 Logical Node: SenEftPTOC1

Description: ISEF> 1 Sensitive Earth Fault

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [3A 2A] - ISEF>1 Function

Str.general ST DDB_SEF_1_START (323)

Str.dirGeneral ST [3A 2B] - ISEF>1 Direction

Str.neut ST DDB_SEF_1_START (323)

Page 38: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 37

Attribute FC Source Str.dirNeut ST [3A 2B] - ISEF>1 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_SEF_1_TRIP (269)

Op.neut ST DDB_SEF_1_TRIP (269)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.25 Logical Node: SenEftPTOC2

Description: ISEF> 2 Sensitive Earth Fault

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [3A 3A] - ISEF>2 Function

Str.general ST DDB_SEF_2_START (324)

Str.dirGeneral ST [3A 3B] - ISEF>2 Direction

Str.neut ST DDB_SEF_2_START (324)

Str.dirNeut ST [3A 3B] - ISEF>2 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_SEF_2_TRIP (270)

Op.neut ST DDB_SEF_2_TRIP (270)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.26 Logical Node: SenEftPTOC3

Description: ISEF> 3 Sensitive Earth Fault

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Page 39: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 38 MiCOM P40Agile P14NB

Attribute FC Source Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [3A 49] - ISEF>3 Status

Str.general ST DDB_SEF_3_START (325)

Str.dirGeneral ST [3A 4A] - ISEF>3 Direction

Str.neut ST DDB_SEF_3_START (325)

Str.dirNeut ST [3A 4A] - ISEF>3 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_SEF_3_TRIP (271)

Op.neut ST DDB_SEF_3_TRIP (271)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.27 Logical Node: SenEftPTOC4

Description: ISEF> 4 Sensitive Earth Fault

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [3A 50] - ISEF>4 Status

Str.general ST DDB_SEF_4_START (326)

Str.dirGeneral ST [3A 51] - ISEF>4 Direction

Str.neut ST DDB_SEF_4_START (326)

Str.dirNeut ST [3A 51] - ISEF>4 Direction

Str.q ST Other internal source

Str.t ST Other internal source

Op.general ST DDB_SEF_4_TRIP (272)

Op.neut ST DDB_SEF_4_TRIP (272)

Op.q ST Other internal source

Op.t ST Other internal source

1.4.28 Logical Node: ThmPTTR1

Description: Thermal Overload

Attribute FC Source

Page 40: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 39

Attribute FC Source Mod.stVal ST [3C 01] - Characteristic

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [09 17] - Thermal Overload

Amp.mag.f MX [04 01] - Highest Phase I

Amp.q MX Other internal source

Amp.t MX Other internal source

Amp.units.SIUnit CF [04 01] - Highest Phase I

Amp.units.multiplier CF Other internal source

Amp.db CF Other internal source

Amp.rangeC.hhLim.f CF Other internal source

Amp.rangeC.hLim.f CF Other internal source

Amp.rangeC.lLim.f CF Other internal source

Amp.rangeC.llLim.f CF Other internal source

Amp.rangeC.min.f CF Other internal source

Amp.rangeC.max.f CF Other internal source

TmpRl.mag.f MX [04 02] - Thermal State

TmpRl.q MX Other internal source

TmpRl.t MX Other internal source

TmpRl.units.SIUnit CF [04 02] - Thermal State

TmpRl.units.multiplier CF Other internal source

TmpRl.db CF Other internal source

TmpRl.rangeC.hhLim.f CF Other internal source

TmpRl.rangeC.hLim.f CF Other internal source

TmpRl.rangeC.lLim.f CF Other internal source

TmpRl.rangeC.llLim.f CF Other internal source

TmpRl.rangeC.min.f CF Other internal source

TmpRl.rangeC.max.f CF Other internal source

Op.general ST DDB_THERMAL_TRIP (276)

Op.q ST Other internal source

Op.t ST Other internal source

AlmThm.general ST DDB_THERMAL_ALARM (329)

AlmThm.q ST Other internal source

AlmThm.t ST Other internal source

MTRRs.ctlVal CO [04 03] - Reset Thermal

MTRRs.origin.orCat ST Other internal source

MTRRs.origin.orIdent ST Other internal source

Page 41: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 40 MiCOM P40Agile P14NB

Attribute FC Source MTRRs.stVal ST [04 03] - Reset Thermal

MTRRs.q ST Other internal source

MTRRs.t ST Other internal source

MTRRs.ctlModel CF Other internal source

MTRRs.sboTimeout CF Other internal source

MTRRs.cdcNs EX Other internal source

MTRRs.cdcName EX Other internal source

MTRRs.dataNs EX Other internal source

1.5 LOGICAL RECORDS

This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data Attributes within Logical Nodes contained in the Records Logical Device.

1.5.1 Logical Node: LLN0

Description: Records Logical Device

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

NamPlt.configRev DC Other internal source

NamPlt.ldNs EX Other internal source

1.5.2 Logical Node: LPHD1

Description: Physical Device Information

Attribute FC Source PhyNam.vendor DC Other internal source

PhyNam.hwRev DC Other internal source

PhyNam.swRev DC [00 11] - Software Ref. 1

PhyNam.serNum DC [00 08] - Serial Number

PhyNam.model DC [00 06] - Model Number

PhyNam.location DC [00 05] - Plant Reference

PhyHealth.stVal ST Other internal source

PhyHealth.q ST Other internal source

PhyHealth.t ST Other internal source

Proxy.stVal ST Other internal source

Proxy.q ST Other internal source

Page 42: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 41

Attribute FC Source Proxy.t ST Other internal source

Proxy.d DC Other internal source

PwrUp.stVal ST Other internal source

PwrUp.q ST Other internal source

PwrUp.t ST Other internal source

PwrUp.d DC Other internal source

1.5.3 Logical Node: RDRE1

Description: Disturbance Recorder

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

RcdMade.stVal ST Other internal source

RcdMade.q ST Other internal source

RcdMade.t ST Other internal source

FltNum.stVal ST Other internal source

FltNum.q ST Other internal source

FltNum.t ST Other internal source

1.6 LOGICAL SYSTEM

This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data Attributes within Logical Nodes contained in the System Logical Device.

Page 43: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 42 MiCOM P40Agile P14NB 1.6.1 Logical Node: AlmGGIO1

Description: Alarms

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

Alm1.stVal ST Other internal source

Alm1.q ST Other internal source

Alm1.t ST Other internal source

Alm1.d DC Other internal source

Alm2.stVal ST Other internal source

Alm2.q ST Other internal source

Alm2.t ST Other internal source

Alm2.d DC Other internal source

Alm3.stVal ST DDB_ILLEGAL_OPTO_SETTINGS_GROUP (145)

Alm3.q ST Other internal source

Alm3.t ST Other internal source

Alm3.d DC DDB_ILLEGAL_OPTO_SETTINGS_GROUP (145)

Alm4.stVal ST DDB_OOS_ALARM (146)

Alm4.q ST Other internal source

Alm4.t ST Other internal source

Alm4.d DC DDB_OOS_ALARM (146)

Alm5.stVal ST DDB_FREQ_ALARM (147)

Alm5.q ST Other internal source

Alm5.t ST Other internal source

Alm5.d DC DDB_FREQ_ALARM (147)

Alm6.stVal ST Other internal source

Alm6.q ST Other internal source

Alm6.t ST Other internal source

Alm6.d DC Other internal source

Alm7.stVal ST Other internal source

Alm7.q ST Other internal source

Alm7.t ST Other internal source

Alm7.d DC Other internal source

Alm8.stVal ST DDB_BREAKER_FAIL_ALARM (150)

Alm8.q ST Other internal source

Page 44: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 43

Attribute FC Source Alm8.t ST Other internal source

Alm8.d DC DDB_BREAKER_FAIL_ALARM (150)

Alm9.stVal ST DDB_BROKEN_CURRENT_ALARM (151)

Alm9.q ST Other internal source

Alm9.t ST Other internal source

Alm9.d DC DDB_BROKEN_CURRENT_ALARM (151)

Alm10.stVal ST DDB_BROKEN_CURRENT_LOCKOUT (152)

Alm10.q ST Other internal source

Alm10.t ST Other internal source

Alm10.d DC DDB_BROKEN_CURRENT_LOCKOUT (152)

Alm11.stVal ST DDB_MAINTENANCE_ALARM (153)

Alm11.q ST Other internal source

Alm11.t ST Other internal source

Alm11.d DC DDB_MAINTENANCE_ALARM (153)

Alm12.stVal ST DDB_MAINTENANCE_LOCKOUT (154)

Alm12.q ST Other internal source

Alm12.t ST Other internal source

Alm12.d DC DDB_MAINTENANCE_LOCKOUT (154)

Alm13.stVal ST DDB_EXCESSIVE_OP_TIME_ALARM (155)

Alm13.q ST Other internal source

Alm13.t ST Other internal source

Alm13.d DC DDB_EXCESSIVE_OP_TIME_ALARM (155)

Alm14.stVal ST DDB_EXCESSIVE_OP_TIME_LOCKOUT (156)

Alm14.q ST Other internal source

Alm14.t ST Other internal source

Alm14.d DC DDB_EXCESSIVE_OP_TIME_LOCKOUT (156)

Alm15.stVal ST DDB_EFF_LOCKOUT (157)

Alm15.q ST Other internal source

Alm15.t ST Other internal source

Alm15.d DC DDB_EFF_LOCKOUT (157)

Alm16.stVal ST DDB_CB_STATUS_ALARM (158)

Alm16.q ST Other internal source

Alm16.t ST Other internal source

Alm16.d DC DDB_CB_STATUS_ALARM (158)

Alm17.stVal ST DDB_CB_FAILED_TO_TRIP (159)

Alm17.q ST Other internal source

Alm17.t ST Other internal source

Alm17.d DC DDB_CB_FAILED_TO_TRIP (159)

Alm18.stVal ST DDB_CB_FAILED_TO_CLOSE (160)

Alm18.q ST Other internal source

Alm18.t ST Other internal source

Alm18.d DC DDB_CB_FAILED_TO_CLOSE (160)

Alm19.stVal ST DDB_CONTROL_CB_UNHEALTHY (161)

Alm19.q ST Other internal source

Alm19.t ST Other internal source

Alm19.d DC DDB_CONTROL_CB_UNHEALTHY (161)

Page 45: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 44 MiCOM P40Agile P14NB

Attribute FC Source Alm20.stVal ST Other internal source

Alm20.q ST Other internal source

Alm20.t ST Other internal source

Alm20.d DC Other internal source

Alm21.stVal ST Other internal source

Alm21.q ST Other internal source

Alm21.t ST Other internal source

Alm21.d DC Other internal source

Alm22.stVal ST Other internal source

Alm22.q ST Other internal source

Alm22.t ST Other internal source

Alm22.d DC Other internal source

Alm23.stVal ST Other internal source

Alm23.q ST Other internal source

Alm23.t ST Other internal source

Alm23.d DC Other internal source

Alm24.stVal ST Other internal source

Alm24.q ST Other internal source

Alm24.t ST Other internal source

Alm24.d DC Other internal source

Alm25.stVal ST Other internal source

Alm25.q ST Other internal source

Alm25.t ST Other internal source

Alm25.d DC Other internal source

Alm26.stVal ST DDB_USER_ALARM_1 (168)

Alm26.q ST Other internal source

Alm26.t ST Other internal source

Alm26.d DC DDB_USER_ALARM_1 (168)

Alm27.stVal ST DDB_USER_ALARM_2 (169)

Alm27.q ST Other internal source

Alm27.t ST Other internal source

Alm27.d DC DDB_USER_ALARM_2 (169)

Alm28.stVal ST DDB_USER_ALARM_3 (170)

Alm28.q ST Other internal source

Alm28.t ST Other internal source

Alm28.d DC DDB_USER_ALARM_3 (170)

Alm29.stVal ST DDB_USER_ALARM_4 (171)

Alm29.q ST Other internal source

Alm29.t ST Other internal source

Alm29.d DC DDB_USER_ALARM_4 (171)

Alm30.stVal ST DDB_USER_ALARM_5 (172)

Alm30.q ST Other internal source

Alm30.t ST Other internal source

Alm30.d DC DDB_USER_ALARM_5 (172)

Alm31.stVal ST DDB_USER_ALARM_6 (173)

Alm31.q ST Other internal source

Page 46: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 45

Attribute FC Source Alm31.t ST Other internal source

Alm31.d DC DDB_USER_ALARM_6 (173)

Alm32.stVal ST DDB_USER_ALARM_7 (174)

Alm32.q ST Other internal source

Alm32.t ST Other internal source

Alm32.d DC DDB_USER_ALARM_7 (174)

Alm33.stVal ST Other internal source

Alm33.q ST Other internal source

Alm33.t ST Other internal source

Alm33.d DC Other internal source

Alm34.stVal ST Other internal source

Alm34.q ST Other internal source

Alm34.t ST Other internal source

Alm34.d DC Other internal source

Alm35.stVal ST Other internal source

Alm35.q ST Other internal source

Alm35.t ST Other internal source

Alm35.d DC Other internal source

Alm36.stVal ST Other internal source

Alm36.q ST Other internal source

Alm36.t ST Other internal source

Alm36.d DC Other internal source

Alm37.stVal ST DDB_USER_ALARM_8 (175)

Alm37.q ST Other internal source

Alm37.t ST Other internal source

Alm37.d DC DDB_USER_ALARM_8 (175)

Alm38.stVal ST DDB_USER_ALARM_9 (176)

Alm38.q ST Other internal source

Alm38.t ST Other internal source

Alm38.d DC DDB_USER_ALARM_9 (176)

Alm39.stVal ST DDB_USER_ALARM_10 (177)

Alm39.q ST Other internal source

Alm39.t ST Other internal source

Alm39.d DC DDB_USER_ALARM_10 (177)

Alm40.stVal ST DDB_USER_ALARM_11 (178)

Alm40.q ST Other internal source

Alm40.t ST Other internal source

Alm40.d DC DDB_USER_ALARM_11 (178)

Alm41.stVal ST DDB_USER_ALARM_12 (179)

Alm41.q ST Other internal source

Alm41.t ST Other internal source

Alm41.d DC DDB_USER_ALARM_12 (179)

Alm42.stVal ST DDB_USER_ALARM_13 (180)

Alm42.q ST Other internal source

Alm42.t ST Other internal source

Alm42.d DC DDB_USER_ALARM_13 (180)

Page 47: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 46 MiCOM P40Agile P14NB

Attribute FC Source Alm43.stVal ST DDB_USER_ALARM_14 (181)

Alm43.q ST Other internal source

Alm43.t ST Other internal source

Alm43.d DC DDB_USER_ALARM_14 (181)

Alm44.stVal ST DDB_USER_ALARM_15 (182)

Alm44.q ST Other internal source

Alm44.t ST Other internal source

Alm44.d DC DDB_USER_ALARM_15 (182)

Alm45.stVal ST DDB_USER_ALARM_16 (183)

Alm45.q ST Other internal source

Alm45.t ST Other internal source

Alm45.d DC DDB_USER_ALARM_16 (183)

Alm46.stVal ST DDB_USER_ALARM_17 (184)

Alm46.q ST Other internal source

Alm46.t ST Other internal source

Alm46.d DC DDB_USER_ALARM_17 (184)

Alm47.stVal ST DDB_USER_ALARM_18 (185)

Alm47.q ST Other internal source

Alm47.t ST Other internal source

Alm47.d DC DDB_USER_ALARM_18 (185)

Alm48.stVal ST DDB_USER_ALARM_19 (186)

Alm48.q ST Other internal source

Alm48.t ST Other internal source

Alm48.d DC DDB_USER_ALARM_19 (186)

Alm49.stVal ST DDB_USER_ALARM_20 (187)

Alm49.q ST Other internal source

Alm49.t ST Other internal source

Alm49.d DC DDB_USER_ALARM_20 (187)

Alm50.stVal ST DDB_USER_ALARM_21 (188)

Alm50.q ST Other internal source

Alm50.t ST Other internal source

Alm50.d DC DDB_USER_ALARM_21 (188)

Alm51.stVal ST DDB_USER_ALARM_22 (189)

Alm51.q ST Other internal source

Alm51.t ST Other internal source

Alm51.d DC DDB_USER_ALARM_22 (189)

Alm52.stVal ST DDB_USER_ALARM_23 (190)

Alm52.q ST Other internal source

Alm52.t ST Other internal source

Alm52.d DC DDB_USER_ALARM_23 (190)

Alm53.stVal ST DDB_USER_ALARM_24 (191)

Alm53.q ST Other internal source

Alm53.t ST Other internal source

Alm53.d DC DDB_USER_ALARM_24 (191)

Alm54.stVal ST DDB_USER_ALARM_25 (192)

Alm54.q ST Other internal source

Page 48: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 47

Attribute FC Source Alm54.t ST Other internal source

Alm54.d DC DDB_USER_ALARM_25 (192)

Alm55.stVal ST DDB_USER_ALARM_26 (193)

Alm55.q ST Other internal source

Alm55.t ST Other internal source

Alm55.d DC DDB_USER_ALARM_26 (193)

Alm56.stVal ST DDB_USER_ALARM_27 (194)

Alm56.q ST Other internal source

Alm56.t ST Other internal source

Alm56.d DC DDB_USER_ALARM_27 (194)

Alm57.stVal ST DDB_USER_ALARM_28 (195)

Alm57.q ST Other internal source

Alm57.t ST Other internal source

Alm57.d DC DDB_USER_ALARM_28 (195)

Alm58.stVal ST DDB_USER_ALARM_29 (196)

Alm58.q ST Other internal source

Alm58.t ST Other internal source

Alm58.d DC DDB_USER_ALARM_29 (196)

Alm59.stVal ST DDB_USER_ALARM_30 (197)

Alm59.q ST Other internal source

Alm59.t ST Other internal source

Alm59.d DC DDB_USER_ALARM_30 (197)

Alm60.stVal ST DDB_USER_ALARM_31 (198)

Alm60.q ST Other internal source

Alm60.t ST Other internal source

Alm60.d DC DDB_USER_ALARM_31 (198)

Alm61.stVal ST DDB_USER_ALARM_32 (199)

Alm61.q ST Other internal source

Alm61.t ST Other internal source

Alm61.d DC DDB_USER_ALARM_32 (199)

Alm62.stVal ST DDB_USER_ALARM_33 (200)

Alm62.q ST Other internal source

Alm62.t ST Other internal source

Alm62.d DC DDB_USER_ALARM_33 (200)

Alm63.stVal ST DDB_USER_ALARM_34 (201)

Alm63.q ST Other internal source

Alm63.t ST Other internal source

Alm63.d DC DDB_USER_ALARM_34 (201)

Alm64.stVal ST DDB_USER_ALARM_35 (202)

Alm64.q ST Other internal source

Alm64.t ST Other internal source

Alm64.d DC DDB_USER_ALARM_35 (202)

Alm65.stVal ST DDB_DC_SUPPLY_MON_ALARM (769)

Alm65.q ST Other internal source

Alm65.t ST Other internal source

Alm65.d DC DDB_DC_SUPPLY_MON_ALARM (769)

Page 49: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 48 MiCOM P40Agile P14NB

Attribute FC Source Alm66.stVal ST Other internal source

Alm66.q ST Other internal source

Alm66.t ST Other internal source

Alm66.d DC Other internal source

Alm67.stVal ST Other internal source

Alm67.q ST Other internal source

Alm67.t ST Other internal source

Alm67.d DC Other internal source

Alm68.stVal ST DDB_GOOSE_MISSING_IED_ALARM (771)

Alm68.q ST Other internal source

Alm68.t ST Other internal source

Alm68.d DC DDB_GOOSE_MISSING_IED_ALARM (771)

Alm69.stVal ST DDB_ECARD_NOT_FITTED_ALARM (772)

Alm69.q ST Other internal source

Alm69.t ST Other internal source

Alm69.d DC DDB_ECARD_NOT_FITTED_ALARM (772)

Alm70.stVal ST DDB_NIC_NOT_RESPONDING_ALARM (773)

Alm70.q ST Other internal source

Alm70.t ST Other internal source

Alm70.d DC DDB_NIC_NOT_RESPONDING_ALARM (773)

Alm71.stVal ST DDB_NIC_FATAL_ERROR_ALARM (774)

Alm71.q ST Other internal source

Alm71.t ST Other internal source

Alm71.d DC DDB_NIC_FATAL_ERROR_ALARM (774)

Alm72.stVal ST Other internal source

Alm72.q ST Other internal source

Alm72.t ST Other internal source

Alm72.d DC Other internal source

Alm73.stVal ST DDB_INVALID_TCP_IP_CONFIG_ALARM (776)

Alm73.q ST Other internal source

Alm73.t ST Other internal source

Alm73.d DC DDB_INVALID_TCP_IP_CONFIG_ALARM (776)

Alm74.stVal ST Other internal source

Alm74.q ST Other internal source

Alm74.t ST Other internal source

Alm74.d DC Other internal source

Alm75.stVal ST DDB_NIC_LINK_FAIL_ALARM (778)

Alm75.q ST Other internal source

Alm75.t ST Other internal source

Alm75.d DC DDB_NIC_LINK_FAIL_ALARM (778)

Alm76.stVal ST DDB_SW_MISMATCH_ALARM (779)

Alm76.q ST Other internal source

Alm76.t ST Other internal source

Alm76.d DC DDB_SW_MISMATCH_ALARM (779)

Alm77.stVal ST DDB_IP_ADDRESS_CONFLICT_ALARM (780)

Alm77.q ST Other internal source

Page 50: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 49

Attribute FC Source Alm77.t ST Other internal source

Alm77.d DC DDB_IP_ADDRESS_CONFLICT_ALARM (780)

Alm78.stVal ST Other internal source

Alm78.q ST Other internal source

Alm78.t ST Other internal source

Alm78.d DC Other internal source

Alm79.stVal ST Other internal source

Alm79.q ST Other internal source

Alm79.t ST Other internal source

Alm79.d DC Other internal source

Alm80.stVal ST Other internal source

Alm80.q ST Other internal source

Alm80.t ST Other internal source

Alm80.d DC Other internal source

Alm81.stVal ST Other internal source

Alm81.q ST Other internal source

Alm81.t ST Other internal source

Alm81.d DC Other internal source

Alm82.stVal ST Other internal source

Alm82.q ST Other internal source

Alm82.t ST Other internal source

Alm82.d DC Other internal source

Alm83.stVal ST Other internal source

Alm83.q ST Other internal source

Alm83.t ST Other internal source

Alm83.d DC Other internal source

Alm84.stVal ST Other internal source

Alm84.q ST Other internal source

Alm84.t ST Other internal source

Alm84.d DC Other internal source

Alm85.stVal ST Other internal source

Alm85.q ST Other internal source

Alm85.t ST Other internal source

Alm85.d DC Other internal source

Alm86.stVal ST Other internal source

Alm86.q ST Other internal source

Alm86.t ST Other internal source

Alm86.d DC Other internal source

Alm87.stVal ST Other internal source

Alm87.q ST Other internal source

Alm87.t ST Other internal source

Alm87.d DC Other internal source

Alm88.stVal ST Other internal source

Alm88.q ST Other internal source

Alm88.t ST Other internal source

Alm88.d DC Other internal source

Page 51: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 50 MiCOM P40Agile P14NB

Attribute FC Source Alm89.stVal ST Other internal source

Alm89.q ST Other internal source

Alm89.t ST Other internal source

Alm89.d DC Other internal source

Alm90.stVal ST Other internal source

Alm90.q ST Other internal source

Alm90.t ST Other internal source

Alm90.d DC Other internal source

Alm91.stVal ST Other internal source

Alm91.q ST Other internal source

Alm91.t ST Other internal source

Alm91.d DC Other internal source

Alm92.stVal ST Other internal source

Alm92.q ST Other internal source

Alm92.t ST Other internal source

Alm92.d DC Other internal source

Alm93.stVal ST Other internal source

Alm93.q ST Other internal source

Alm93.t ST Other internal source

Alm93.d DC Other internal source

Alm94.stVal ST Other internal source

Alm94.q ST Other internal source

Alm94.t ST Other internal source

Alm94.d DC Other internal source

Alm95.stVal ST Other internal source

Alm95.q ST Other internal source

Alm95.t ST Other internal source

Alm95.d DC Other internal source

Alm96.stVal ST Other internal source

Alm96.q ST Other internal source

Alm96.t ST Other internal source

Alm96.d DC Other internal source

Page 52: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 51 1.6.2 Logical Node: FnkGGIO1

Description: Function Keys

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [17 01] - Fn Key Status

Ind1.stVal ST DDB_FN_KEY_1 (712)

Ind1.q ST Other internal source

Ind1.t ST Other internal source

Ind1.d DC [17 04] - Fn Key 1 Label

Ind2.stVal ST DDB_FN_KEY_2 (713)

Ind2.q ST Other internal source

Ind2.t ST Other internal source

Ind2.d DC [17 07] - Fn Key 2 Label

Ind3.stVal ST DDB_FN_KEY_3 (714)

Ind3.q ST Other internal source

Ind3.t ST Other internal source

Ind3.d DC [17 0A] - Fn Key 3 Label

1.6.3 Logical Node: GosGGIO1

Description: GOOSE Input Signals

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

Ind1.stVal ST DDB_GOOSEIN_1 (832)

Page 53: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 52 MiCOM P40Agile P14NB

Attribute FC Source Ind1.q ST Other internal source

Ind1.t ST Other internal source

Ind1.d DC Other internal source

Ind2.stVal ST DDB_GOOSEIN_2 (833)

Ind2.q ST Other internal source

Ind2.t ST Other internal source

Ind2.d DC Other internal source

Ind3.stVal ST DDB_GOOSEIN_3 (834)

Ind3.q ST Other internal source

Ind3.t ST Other internal source

Ind3.d DC Other internal source

Ind4.stVal ST DDB_GOOSEIN_4 (835)

Ind4.q ST Other internal source

Ind4.t ST Other internal source

Ind4.d DC Other internal source

Ind5.stVal ST DDB_GOOSEIN_5 (836)

Ind5.q ST Other internal source

Ind5.t ST Other internal source

Ind5.d DC Other internal source

Ind6.stVal ST DDB_GOOSEIN_6 (837)

Ind6.q ST Other internal source

Ind6.t ST Other internal source

Ind6.d DC Other internal source

Ind7.stVal ST DDB_GOOSEIN_7 (838)

Ind7.q ST Other internal source

Ind7.t ST Other internal source

Ind7.d DC Other internal source

Ind8.stVal ST DDB_GOOSEIN_8 (839)

Ind8.q ST Other internal source

Ind8.t ST Other internal source

Ind8.d DC Other internal source

Ind9.stVal ST DDB_GOOSEIN_9 (840)

Ind9.q ST Other internal source

Ind9.t ST Other internal source

Ind9.d DC Other internal source

Ind10.stVal ST DDB_GOOSEIN_10 (841)

Ind10.q ST Other internal source

Ind10.t ST Other internal source

Ind10.d DC Other internal source

Ind11.stVal ST DDB_GOOSEIN_11 (842)

Ind11.q ST Other internal source

Ind11.t ST Other internal source

Ind11.d DC Other internal source

Ind12.stVal ST DDB_GOOSEIN_12 (843)

Ind12.q ST Other internal source

Ind12.t ST Other internal source

Page 54: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 53

Attribute FC Source Ind12.d DC Other internal source

Ind13.stVal ST DDB_GOOSEIN_13 (844)

Ind13.q ST Other internal source

Ind13.t ST Other internal source

Ind13.d DC Other internal source

Ind14.stVal ST DDB_GOOSEIN_14 (845)

Ind14.q ST Other internal source

Ind14.t ST Other internal source

Ind14.d DC Other internal source

Ind15.stVal ST DDB_GOOSEIN_15 (846)

Ind15.q ST Other internal source

Ind15.t ST Other internal source

Ind15.d DC Other internal source

Ind16.stVal ST DDB_GOOSEIN_16 (847)

Ind16.q ST Other internal source

Ind16.t ST Other internal source

Ind16.d DC Other internal source

Ind17.stVal ST DDB_GOOSEIN_17 (848)

Ind17.q ST Other internal source

Ind17.t ST Other internal source

Ind17.d DC Other internal source

Ind18.stVal ST DDB_GOOSEIN_18 (849)

Ind18.q ST Other internal source

Ind18.t ST Other internal source

Ind18.d DC Other internal source

Ind19.stVal ST DDB_GOOSEIN_19 (850)

Ind19.q ST Other internal source

Ind19.t ST Other internal source

Ind19.d DC Other internal source

Ind20.stVal ST DDB_GOOSEIN_20 (851)

Ind20.q ST Other internal source

Ind20.t ST Other internal source

Ind20.d DC Other internal source

Ind21.stVal ST DDB_GOOSEIN_21 (852)

Ind21.q ST Other internal source

Ind21.t ST Other internal source

Ind21.d DC Other internal source

Ind22.stVal ST DDB_GOOSEIN_22 (853)

Ind22.q ST Other internal source

Ind22.t ST Other internal source

Ind22.d DC Other internal source

Ind23.stVal ST DDB_GOOSEIN_23 (854)

Ind23.q ST Other internal source

Ind23.t ST Other internal source

Ind23.d DC Other internal source

Ind24.stVal ST DDB_GOOSEIN_24 (855)

Page 55: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 54 MiCOM P40Agile P14NB

Attribute FC Source Ind24.q ST Other internal source

Ind24.t ST Other internal source

Ind24.d DC Other internal source

Ind25.stVal ST DDB_GOOSEIN_25 (856)

Ind25.q ST Other internal source

Ind25.t ST Other internal source

Ind25.d DC Other internal source

Ind26.stVal ST DDB_GOOSEIN_26 (857)

Ind26.q ST Other internal source

Ind26.t ST Other internal source

Ind26.d DC Other internal source

Ind27.stVal ST DDB_GOOSEIN_27 (858)

Ind27.q ST Other internal source

Ind27.t ST Other internal source

Ind27.d DC Other internal source

Ind28.stVal ST DDB_GOOSEIN_28 (859)

Ind28.q ST Other internal source

Ind28.t ST Other internal source

Ind28.d DC Other internal source

Ind29.stVal ST DDB_GOOSEIN_29 (860)

Ind29.q ST Other internal source

Ind29.t ST Other internal source

Ind29.d DC Other internal source

Ind30.stVal ST DDB_GOOSEIN_30 (861)

Ind30.q ST Other internal source

Ind30.t ST Other internal source

Ind30.d DC Other internal source

Ind31.stVal ST DDB_GOOSEIN_31 (862)

Ind31.q ST Other internal source

Ind31.t ST Other internal source

Ind31.d DC Other internal source

Ind32.stVal ST DDB_GOOSEIN_32 (863)

Ind32.q ST Other internal source

Ind32.t ST Other internal source

Ind32.d DC Other internal source

1.6.4 Logical Node: GosGGIO2

Description: GOOSE Output Signals

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Page 56: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 55

Attribute FC Source Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

Ind1.stVal ST DDB_GOOSEOUT_1 (1024)

Ind1.q ST Other internal source

Ind1.t ST Other internal source

Ind1.d DC DDB_GOOSEOUT_1 (1024)

Ind2.stVal ST DDB_GOOSEOUT_2 (1025)

Ind2.q ST Other internal source

Ind2.t ST Other internal source

Ind2.d DC DDB_GOOSEOUT_2 (1025)

Ind3.stVal ST DDB_GOOSEOUT_3 (1026)

Ind3.q ST Other internal source

Ind3.t ST Other internal source

Ind3.d DC DDB_GOOSEOUT_3 (1026)

Ind4.stVal ST DDB_GOOSEOUT_4 (1027)

Ind4.q ST Other internal source

Ind4.t ST Other internal source

Ind4.d DC DDB_GOOSEOUT_4 (1027)

Ind5.stVal ST DDB_GOOSEOUT_5 (1028)

Ind5.q ST Other internal source

Ind5.t ST Other internal source

Ind5.d DC DDB_GOOSEOUT_5 (1028)

Ind6.stVal ST DDB_GOOSEOUT_6 (1029)

Ind6.q ST Other internal source

Ind6.t ST Other internal source

Ind6.d DC DDB_GOOSEOUT_6 (1029)

Ind7.stVal ST DDB_GOOSEOUT_7 (1030)

Ind7.q ST Other internal source

Ind7.t ST Other internal source

Ind7.d DC DDB_GOOSEOUT_7 (1030)

Ind8.stVal ST DDB_GOOSEOUT_8 (1031)

Ind8.q ST Other internal source

Ind8.t ST Other internal source

Ind8.d DC DDB_GOOSEOUT_8 (1031)

Ind9.stVal ST DDB_GOOSEOUT_9 (1032)

Ind9.q ST Other internal source

Ind9.t ST Other internal source

Ind9.d DC DDB_GOOSEOUT_9 (1032)

Ind10.stVal ST DDB_GOOSEOUT_10 (1033)

Ind10.q ST Other internal source

Ind10.t ST Other internal source

Ind10.d DC DDB_GOOSEOUT_10 (1033)

Page 57: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 56 MiCOM P40Agile P14NB

Attribute FC Source Ind11.stVal ST DDB_GOOSEOUT_11 (1034)

Ind11.q ST Other internal source

Ind11.t ST Other internal source

Ind11.d DC DDB_GOOSEOUT_11 (1034)

Ind12.stVal ST DDB_GOOSEOUT_12 (1035)

Ind12.q ST Other internal source

Ind12.t ST Other internal source

Ind12.d DC DDB_GOOSEOUT_12 (1035)

Ind13.stVal ST DDB_GOOSEOUT_13 (1036)

Ind13.q ST Other internal source

Ind13.t ST Other internal source

Ind13.d DC DDB_GOOSEOUT_13 (1036)

Ind14.stVal ST DDB_GOOSEOUT_14 (1037)

Ind14.q ST Other internal source

Ind14.t ST Other internal source

Ind14.d DC DDB_GOOSEOUT_14 (1037)

Ind15.stVal ST DDB_GOOSEOUT_15 (1038)

Ind15.q ST Other internal source

Ind15.t ST Other internal source

Ind15.d DC DDB_GOOSEOUT_15 (1038)

Ind16.stVal ST DDB_GOOSEOUT_16 (1039)

Ind16.q ST Other internal source

Ind16.t ST Other internal source

Ind16.d DC DDB_GOOSEOUT_16 (1039)

Ind17.stVal ST DDB_GOOSEOUT_17 (1040)

Ind17.q ST Other internal source

Ind17.t ST Other internal source

Ind17.d DC DDB_GOOSEOUT_17 (1040)

Ind18.stVal ST DDB_GOOSEOUT_18 (1041)

Ind18.q ST Other internal source

Ind18.t ST Other internal source

Ind18.d DC DDB_GOOSEOUT_18 (1041)

Ind19.stVal ST DDB_GOOSEOUT_19 (1042)

Ind19.q ST Other internal source

Ind19.t ST Other internal source

Ind19.d DC DDB_GOOSEOUT_19 (1042)

Ind20.stVal ST DDB_GOOSEOUT_20 (1043)

Ind20.q ST Other internal source

Ind20.t ST Other internal source

Ind20.d DC DDB_GOOSEOUT_20 (1043)

Ind21.stVal ST DDB_GOOSEOUT_21 (1044)

Ind21.q ST Other internal source

Ind21.t ST Other internal source

Ind21.d DC DDB_GOOSEOUT_21 (1044)

Ind22.stVal ST DDB_GOOSEOUT_22 (1045)

Ind22.q ST Other internal source

Page 58: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 57

Attribute FC Source Ind22.t ST Other internal source

Ind22.d DC DDB_GOOSEOUT_22 (1045)

Ind23.stVal ST DDB_GOOSEOUT_23 (1046)

Ind23.q ST Other internal source

Ind23.t ST Other internal source

Ind23.d DC DDB_GOOSEOUT_23 (1046)

Ind24.stVal ST DDB_GOOSEOUT_24 (1047)

Ind24.q ST Other internal source

Ind24.t ST Other internal source

Ind24.d DC DDB_GOOSEOUT_24 (1047)

Ind25.stVal ST DDB_GOOSEOUT_25 (1048)

Ind25.q ST Other internal source

Ind25.t ST Other internal source

Ind25.d DC DDB_GOOSEOUT_25 (1048)

Ind26.stVal ST DDB_GOOSEOUT_26 (1049)

Ind26.q ST Other internal source

Ind26.t ST Other internal source

Ind26.d DC DDB_GOOSEOUT_26 (1049)

Ind27.stVal ST DDB_GOOSEOUT_27 (1050)

Ind27.q ST Other internal source

Ind27.t ST Other internal source

Ind27.d DC DDB_GOOSEOUT_27 (1050)

Ind28.stVal ST DDB_GOOSEOUT_28 (1051)

Ind28.q ST Other internal source

Ind28.t ST Other internal source

Ind28.d DC DDB_GOOSEOUT_28 (1051)

Ind29.stVal ST DDB_GOOSEOUT_29 (1052)

Ind29.q ST Other internal source

Ind29.t ST Other internal source

Ind29.d DC DDB_GOOSEOUT_29 (1052)

Ind30.stVal ST DDB_GOOSEOUT_30 (1053)

Ind30.q ST Other internal source

Ind30.t ST Other internal source

Ind30.d DC DDB_GOOSEOUT_30 (1053)

Ind31.stVal ST DDB_GOOSEOUT_31 (1054)

Ind31.q ST Other internal source

Ind31.t ST Other internal source

Ind31.d DC DDB_GOOSEOUT_31 (1054)

Ind32.stVal ST DDB_GOOSEOUT_32 (1055)

Ind32.q ST Other internal source

Ind32.t ST Other internal source

Ind32.d DC DDB_GOOSEOUT_32 (1055)

1.6.5 Logical Node: LedGGIO1

Description: Red LED Signals

Attribute FC Source

Page 59: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 58 MiCOM P40Agile P14NB

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

Ind1.stVal ST DDB_OUTPUT_TRI_LED_1_RED (640)

Ind1.q ST Other internal source

Ind1.t ST Other internal source

Ind1.d DC DDB_OUTPUT_TRI_LED_1_RED (640)

Ind2.stVal ST DDB_OUTPUT_TRI_LED_2_RED (642)

Ind2.q ST Other internal source

Ind2.t ST Other internal source

Ind2.d DC DDB_OUTPUT_TRI_LED_2_RED (642)

Ind3.stVal ST DDB_OUTPUT_TRI_LED_3_RED (644)

Ind3.q ST Other internal source

Ind3.t ST Other internal source

Ind3.d DC DDB_OUTPUT_TRI_LED_3_RED (644)

Ind4.stVal ST DDB_OUTPUT_TRI_LED_4_RED (646)

Ind4.q ST Other internal source

Ind4.t ST Other internal source

Ind4.d DC DDB_OUTPUT_TRI_LED_4_RED (646)

Ind5.stVal ST DDB_OUTPUT_TRI_LED_5_RED (648)

Ind5.q ST Other internal source

Ind5.t ST Other internal source

Ind5.d DC DDB_OUTPUT_TRI_LED_5_RED (648)

Ind6.stVal ST DDB_OUTPUT_TRI_LED_6_RED (650)

Ind6.q ST Other internal source

Ind6.t ST Other internal source

Ind6.d DC DDB_OUTPUT_TRI_LED_6_RED (650)

Ind7.stVal ST DDB_OUTPUT_TRI_LED_7_RED (652)

Ind7.q ST Other internal source

Ind7.t ST Other internal source

Ind7.d DC DDB_OUTPUT_TRI_LED_7_RED (652)

Ind8.stVal ST DDB_OUTPUT_TRI_LED_8_RED (654)

Ind8.q ST Other internal source

Ind8.t ST Other internal source

Ind8.d DC DDB_OUTPUT_TRI_LED_8_RED (654)

Ind9.stVal ST DDB_OUTPUT_TRI_LED_9_RED (656)

Page 60: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 59

Attribute FC Source Ind9.q ST Other internal source

Ind9.t ST Other internal source

Ind9.d DC DDB_OUTPUT_TRI_LED_9_RED (656)

Ind10.stVal ST DDB_OUTPUT_TRI_LED_10_RED (658)

Ind10.q ST Other internal source

Ind10.t ST Other internal source

Ind10.d DC DDB_OUTPUT_TRI_LED_10_RED (658)

Ind11.stVal ST DDB_OUTPUT_TRI_LED_11_RED (660)

Ind11.q ST Other internal source

Ind11.t ST Other internal source

Ind11.d DC DDB_OUTPUT_TRI_LED_11_RED (660)

1.6.6 Logical Node: LedGGIO2

Description: Green LED Signals

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

Ind1.stVal ST DDB_OUTPUT_TRI_LED_1_GRN (641)

Ind1.q ST Other internal source

Ind1.t ST Other internal source

Ind1.d DC DDB_OUTPUT_TRI_LED_1_GRN (641)

Ind2.stVal ST DDB_OUTPUT_TRI_LED_2_GRN (643)

Ind2.q ST Other internal source

Ind2.t ST Other internal source

Ind2.d DC DDB_OUTPUT_TRI_LED_2_GRN (643)

Ind3.stVal ST DDB_OUTPUT_TRI_LED_3_GRN (645)

Ind3.q ST Other internal source

Ind3.t ST Other internal source

Ind3.d DC DDB_OUTPUT_TRI_LED_3_GRN (645)

Ind4.stVal ST DDB_OUTPUT_TRI_LED_4_GRN (647)

Ind4.q ST Other internal source

Ind4.t ST Other internal source

Ind4.d DC DDB_OUTPUT_TRI_LED_4_GRN (647)

Ind5.stVal ST DDB_OUTPUT_TRI_LED_5_GRN (649)

Ind5.q ST Other internal source

Page 61: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 60 MiCOM P40Agile P14NB

Attribute FC Source Ind5.t ST Other internal source

Ind5.d DC DDB_OUTPUT_TRI_LED_5_GRN (649)

Ind6.stVal ST DDB_OUTPUT_TRI_LED_6_GRN (651)

Ind6.q ST Other internal source

Ind6.t ST Other internal source

Ind6.d DC DDB_OUTPUT_TRI_LED_6_GRN (651)

Ind7.stVal ST DDB_OUTPUT_TRI_LED_7_GRN (653)

Ind7.q ST Other internal source

Ind7.t ST Other internal source

Ind7.d DC DDB_OUTPUT_TRI_LED_7_GRN (653)

Ind8.stVal ST DDB_OUTPUT_TRI_LED_8_GRN (655)

Ind8.q ST Other internal source

Ind8.t ST Other internal source

Ind8.d DC DDB_OUTPUT_TRI_LED_8_GRN (655)

Ind9.stVal ST DDB_OUTPUT_TRI_LED_9_GRN (657)

Ind9.q ST Other internal source

Ind9.t ST Other internal source

Ind9.d DC DDB_OUTPUT_TRI_LED_9_GRN (657)

Ind10.stVal ST DDB_OUTPUT_TRI_LED_10_GRN (659)

Ind10.q ST Other internal source

Ind10.t ST Other internal source

Ind10.d DC DDB_OUTPUT_TRI_LED_10_GRN (659)

Ind11.stVal ST DDB_OUTPUT_TRI_LED_11_GRN (661)

Ind11.q ST Other internal source

Ind11.t ST Other internal source

Ind11.d DC DDB_OUTPUT_TRI_LED_11_GRN (661)

1.6.7 Logical Node: LLN0

Description: System Logical Device

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

NamPlt.configRev DC Other internal source

NamPlt.ldNs EX Other internal source

LEDRs.ctlVal CO [01 FF] - Reset Indication

Page 62: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 61

Attribute FC Source LEDRs.origin.orCat ST Other internal source

LEDRs.origin.orIdent ST Other internal source

LEDRs.stVal ST [01 FF] - Reset Indication

LEDRs.q ST Other internal source

LEDRs.t ST Other internal source

LEDRs.ctlModel CF Other internal source

LEDRs.sboTimeout CF Other internal source

LEDRs.cdcNs EX Other internal source

LEDRs.cdcName EX Other internal source

OrdRun.stVal ST Other internal source

OrdRun.q ST Other internal source

OrdRun.t ST Other internal source

OrdRun.dataNs EX Other internal source

SyncSt.stVal ST Other internal source

SyncSt.q ST Other internal source

SyncSt.t ST Other internal source

SyncSt.dataNs EX Other internal source

1.6.8 Logical Node: LPHD1

Description: Physical Device Information

Attribute FC Source PhyNam.vendor DC Other internal source

PhyNam.hwRev DC Other internal source

PhyNam.swRev DC [00 11] - Software Ref. 1

PhyNam.serNum DC [00 08] - Serial Number

PhyNam.model DC [00 06] - Model Number

PhyNam.location DC [00 05] - Plant Reference

PhyHealth.stVal ST Other internal source

PhyHealth.q ST Other internal source

PhyHealth.t ST Other internal source

Proxy.stVal ST Other internal source

Proxy.q ST Other internal source

Proxy.t ST Other internal source

Proxy.d DC Other internal source

PwrUp.stVal ST Other internal source

PwrUp.q ST Other internal source

PwrUp.t ST Other internal source

PwrUp.d DC Other internal source

1.6.9 Logical Node: OptGGIO1

Description: Opto Inputs

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Page 63: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 62 MiCOM P40Agile P14NB

Attribute FC Source Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [0F 01] - Opto I/P Status

Ind1.stVal ST DDB_OPTO_ISOLATOR_1 (32)

Ind1.q ST Other internal source

Ind1.t ST Other internal source

Ind1.d DC [4A 01] - Opto Input 1

Ind2.stVal ST DDB_OPTO_ISOLATOR_2 (33)

Ind2.q ST Other internal source

Ind2.t ST Other internal source

Ind2.d DC [4A 02] - Opto Input 2

Ind3.stVal ST DDB_OPTO_ISOLATOR_3 (34)

Ind3.q ST Other internal source

Ind3.t ST Other internal source

Ind3.d DC [4A 03] - Opto Input 3

Ind4.stVal ST DDB_OPTO_ISOLATOR_4 (35)

Ind4.q ST Other internal source

Ind4.t ST Other internal source

Ind4.d DC [4A 04] - Opto Input 4

Ind5.stVal ST DDB_OPTO_ISOLATOR_5 (36)

Ind5.q ST Other internal source

Ind5.t ST Other internal source

Ind5.d DC [4A 05] - Opto Input 5

Ind6.stVal ST DDB_OPTO_ISOLATOR_6 (37)

Ind6.q ST Other internal source

Ind6.t ST Other internal source

Ind6.d DC [4A 06] - Opto Input 6

Ind7.stVal ST DDB_OPTO_ISOLATOR_7 (38)

Ind7.q ST Other internal source

Ind7.t ST Other internal source

Ind7.d DC [4A 07] - Opto Input 7

Ind8.stVal ST DDB_OPTO_ISOLATOR_8 (39)

Ind8.q ST Other internal source

Ind8.t ST Other internal source

Ind8.d DC [4A 08] - Opto Input 8

1.6.10 Logical Node: OrdRunGGIO1

Description: Uniqueness of control "Order Running" indications for Control operations

Attribute FC Source Mod.stVal ST Other internal source

Page 64: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 63

Attribute FC Source Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC Other internal source

Ind1.stVal ST Other internal source

Ind1.q ST Other internal source

Ind1.t ST Other internal source

Ind1.d DC Other internal source

Ind2.stVal ST Other internal source

Ind2.q ST Other internal source

Ind2.t ST Other internal source

Ind2.d DC Other internal source

Ind3.stVal ST Other internal source

Ind3.q ST Other internal source

Ind3.t ST Other internal source

Ind3.d DC Other internal source

Ind4.stVal ST Other internal source

Ind4.q ST Other internal source

Ind4.t ST Other internal source

Ind4.d DC Other internal source

Ind5.stVal ST Other internal source

Ind5.q ST Other internal source

Ind5.t ST Other internal source

Ind5.d DC Other internal source

Ind6.stVal ST Other internal source

Ind6.q ST Other internal source

Ind6.t ST Other internal source

Ind6.d DC Other internal source

Ind7.stVal ST Other internal source

Ind7.q ST Other internal source

Ind7.t ST Other internal source

Ind7.d DC Other internal source

Ind8.stVal ST Other internal source

Ind8.q ST Other internal source

Ind8.t ST Other internal source

Ind8.d DC Other internal source

Ind9.stVal ST Other internal source

Ind9.q ST Other internal source

Page 65: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 64 MiCOM P40Agile P14NB

Attribute FC Source Ind9.t ST Other internal source

Ind9.d DC Other internal source

Ind10.stVal ST Other internal source

Ind10.q ST Other internal source

Ind10.t ST Other internal source

Ind10.d DC Other internal source

Ind11.stVal ST Other internal source

Ind11.q ST Other internal source

Ind11.t ST Other internal source

Ind11.d DC Other internal source

Ind12.stVal ST Other internal source

Ind12.q ST Other internal source

Ind12.t ST Other internal source

Ind12.d DC Other internal source

Ind13.stVal ST Other internal source

Ind13.q ST Other internal source

Ind13.t ST Other internal source

Ind13.d DC Other internal source

Ind14.stVal ST Other internal source

Ind14.q ST Other internal source

Ind14.t ST Other internal source

Ind14.d DC Other internal source

Ind15.stVal ST Other internal source

Ind15.q ST Other internal source

Ind15.t ST Other internal source

Ind15.d DC Other internal source

Ind16.stVal ST Other internal source

Ind16.q ST Other internal source

Ind16.t ST Other internal source

Ind16.d DC Other internal source

Ind17.stVal ST Other internal source

Ind17.q ST Other internal source

Ind17.t ST Other internal source

Ind17.d DC Other internal source

Ind18.stVal ST Other internal source

Ind18.q ST Other internal source

Ind18.t ST Other internal source

Ind18.d DC Other internal source

Ind19.stVal ST Other internal source

Ind19.q ST Other internal source

Ind19.t ST Other internal source

Ind19.d DC Other internal source

Ind20.stVal ST Other internal source

Ind20.q ST Other internal source

Ind20.t ST Other internal source

Ind20.d DC Other internal source

Page 66: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 65

Attribute FC Source Ind21.stVal ST Other internal source

Ind21.q ST Other internal source

Ind21.t ST Other internal source

Ind21.d DC Other internal source

Ind22.stVal ST Other internal source

Ind22.q ST Other internal source

Ind22.t ST Other internal source

Ind22.d DC Other internal source

Ind23.stVal ST Other internal source

Ind23.q ST Other internal source

Ind23.t ST Other internal source

Ind23.d DC Other internal source

Ind24.stVal ST Other internal source

Ind24.q ST Other internal source

Ind24.t ST Other internal source

Ind24.d DC Other internal source

Ind25.stVal ST Other internal source

Ind25.q ST Other internal source

Ind25.t ST Other internal source

Ind25.d DC Other internal source

Ind26.stVal ST Other internal source

Ind26.q ST Other internal source

Ind26.t ST Other internal source

Ind26.d DC Other internal source

Ind27.stVal ST Other internal source

Ind27.q ST Other internal source

Ind27.t ST Other internal source

Ind27.d DC Other internal source

Ind28.stVal ST Other internal source

Ind28.q ST Other internal source

Ind28.t ST Other internal source

Ind28.d DC Other internal source

Ind29.stVal ST Other internal source

Ind29.q ST Other internal source

Ind29.t ST Other internal source

Ind29.d DC Other internal source

Ind30.stVal ST Other internal source

Ind30.q ST Other internal source

Ind30.t ST Other internal source

Ind30.d DC Other internal source

Ind31.stVal ST Other internal source

Ind31.q ST Other internal source

Ind31.t ST Other internal source

Ind31.d DC Other internal source

Ind32.stVal ST Other internal source

Ind32.q ST Other internal source

Page 67: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 66 MiCOM P40Agile P14NB

Attribute FC Source Ind32.t ST Other internal source

Ind32.d DC Other internal source

Ind33.stVal ST Other internal source

Ind33.q ST Other internal source

Ind33.t ST Other internal source

Ind33.d DC Other internal source

Ind34.stVal ST Other internal source

Ind34.q ST Other internal source

Ind34.t ST Other internal source

Ind34.d DC Other internal source

Ind35.stVal ST Other internal source

Ind35.q ST Other internal source

Ind35.t ST Other internal source

Ind35.d DC Other internal source

Ind36.stVal ST Other internal source

Ind36.q ST Other internal source

Ind36.t ST Other internal source

Ind36.d DC Other internal source

Ind37.stVal ST Other internal source

Ind37.q ST Other internal source

Ind37.t ST Other internal source

Ind37.d DC Other internal source

Ind38.stVal ST Other internal source

Ind38.q ST Other internal source

Ind38.t ST Other internal source

Ind38.d DC Other internal source

Ind39.stVal ST Other internal source

Ind39.q ST Other internal source

Ind39.t ST Other internal source

Ind39.d DC Other internal source

Ind40.stVal ST Other internal source

Ind40.q ST Other internal source

Ind40.t ST Other internal source

Ind40.d DC Other internal source

Ind41.stVal ST Other internal source

Ind41.q ST Other internal source

Ind41.t ST Other internal source

Ind41.d DC Other internal source

Ind42.stVal ST Other internal source

Ind42.q ST Other internal source

Ind42.t ST Other internal source

Ind42.d DC Other internal source

Ind43.stVal ST Other internal source

Ind43.q ST Other internal source

Ind43.t ST Other internal source

Ind43.d DC Other internal source

Page 68: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 67

Attribute FC Source Ind44.stVal ST Other internal source

Ind44.q ST Other internal source

Ind44.t ST Other internal source

Ind44.d DC Other internal source

Ind45.stVal ST Other internal source

Ind45.q ST Other internal source

Ind45.t ST Other internal source

Ind45.d DC Other internal source

Ind46.stVal ST Other internal source

Ind46.q ST Other internal source

Ind46.t ST Other internal source

Ind46.d DC Other internal source

Ind47.stVal ST Other internal source

Ind47.q ST Other internal source

Ind47.t ST Other internal source

Ind47.d DC Other internal source

Ind48.stVal ST Other internal source

Ind48.q ST Other internal source

Ind48.t ST Other internal source

Ind48.d DC Other internal source

Ind49.stVal ST Other internal source

Ind49.q ST Other internal source

Ind49.t ST Other internal source

Ind49.d DC Other internal source

Ind50.stVal ST Other internal source

Ind50.q ST Other internal source

Ind50.t ST Other internal source

Ind50.d DC Other internal source

Ind51.stVal ST Other internal source

Ind51.q ST Other internal source

Ind51.t ST Other internal source

Ind51.d DC Other internal source

Ind52.stVal ST Other internal source

Ind52.q ST Other internal source

Ind52.t ST Other internal source

Ind52.d DC Other internal source

Ind53.stVal ST Other internal source

Ind53.q ST Other internal source

Ind53.t ST Other internal source

Ind53.d DC Other internal source

Ind54.stVal ST Other internal source

Ind54.q ST Other internal source

Ind54.t ST Other internal source

Ind54.d DC Other internal source

Ind55.stVal ST Other internal source

Ind55.q ST Other internal source

Page 69: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 68 MiCOM P40Agile P14NB

Attribute FC Source Ind55.t ST Other internal source

Ind55.d DC Other internal source

Ind56.stVal ST Other internal source

Ind56.q ST Other internal source

Ind56.t ST Other internal source

Ind56.d DC Other internal source

Ind57.stVal ST Other internal source

Ind57.q ST Other internal source

Ind57.t ST Other internal source

Ind57.d DC Other internal source

Ind58.stVal ST Other internal source

Ind58.q ST Other internal source

Ind58.t ST Other internal source

Ind58.d DC Other internal source

Ind59.stVal ST Other internal source

Ind59.q ST Other internal source

Ind59.t ST Other internal source

Ind59.d DC Other internal source

Ind60.stVal ST Other internal source

Ind60.q ST Other internal source

Ind60.t ST Other internal source

Ind60.d DC Other internal source

Ind61.stVal ST Other internal source

Ind61.q ST Other internal source

Ind61.t ST Other internal source

Ind61.d DC Other internal source

Ind62.stVal ST Other internal source

Ind62.q ST Other internal source

Ind62.t ST Other internal source

Ind62.d DC Other internal source

Ind63.stVal ST Other internal source

Ind63.q ST Other internal source

Ind63.t ST Other internal source

Ind63.d DC Other internal source

Ind64.stVal ST Other internal source

Ind64.q ST Other internal source

Ind64.t ST Other internal source

Ind64.d DC Other internal source

1.6.11 Logical Node: PloGGIO1

Description: Controllable Inputs

Attribute FC Source Mod.stVal ST Other internal source

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Page 70: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 69

Attribute FC Source Beh.stVal ST Other internal source

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [12 01] - Ctrl I/P Status

SPCSO1.ctlVal CO [12 10] - Control Input 1

SPCSO1.origin.orCat ST Other internal source

SPCSO1.origin.orIdent ST Other internal source

SPCSO1.stVal ST DDB_CONTROL_1 (800)

SPCSO1.q ST Other internal source

SPCSO1.t ST Other internal source

SPCSO1.ctlModel CF Other internal source

SPCSO1.sboTimeout CF Other internal source

SPCSO1.cdcNs EX Other internal source

SPCSO1.cdcName EX Other internal source

SPCSO2.ctlVal CO [12 11] - Control Input 2

SPCSO2.origin.orCat ST Other internal source

SPCSO2.origin.orIdent ST Other internal source

SPCSO2.stVal ST DDB_CONTROL_2 (801)

SPCSO2.q ST Other internal source

SPCSO2.t ST Other internal source

SPCSO2.ctlModel CF Other internal source

SPCSO2.sboTimeout CF Other internal source

SPCSO2.cdcNs EX Other internal source

SPCSO2.cdcName EX Other internal source

SPCSO3.ctlVal CO [12 12] - Control Input 3

SPCSO3.origin.orCat ST Other internal source

SPCSO3.origin.orIdent ST Other internal source

SPCSO3.stVal ST DDB_CONTROL_3 (802)

SPCSO3.q ST Other internal source

SPCSO3.t ST Other internal source

SPCSO3.ctlModel CF Other internal source

SPCSO3.sboTimeout CF Other internal source

SPCSO3.cdcNs EX Other internal source

SPCSO3.cdcName EX Other internal source

SPCSO4.ctlVal CO [12 13] - Control Input 4

SPCSO4.origin.orCat ST Other internal source

SPCSO4.origin.orIdent ST Other internal source

SPCSO4.stVal ST DDB_CONTROL_4 (803)

SPCSO4.q ST Other internal source

SPCSO4.t ST Other internal source

SPCSO4.ctlModel CF Other internal source

Page 71: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 70 MiCOM P40Agile P14NB

Attribute FC Source SPCSO4.sboTimeout CF Other internal source

SPCSO4.cdcNs EX Other internal source

SPCSO4.cdcName EX Other internal source

SPCSO5.ctlVal CO [12 14] - Control Input 5

SPCSO5.origin.orCat ST Other internal source

SPCSO5.origin.orIdent ST Other internal source

SPCSO5.stVal ST DDB_CONTROL_5 (804)

SPCSO5.q ST Other internal source

SPCSO5.t ST Other internal source

SPCSO5.ctlModel CF Other internal source

SPCSO5.sboTimeout CF Other internal source

SPCSO5.cdcNs EX Other internal source

SPCSO5.cdcName EX Other internal source

SPCSO6.ctlVal CO [12 15] - Control Input 6

SPCSO6.origin.orCat ST Other internal source

SPCSO6.origin.orIdent ST Other internal source

SPCSO6.stVal ST DDB_CONTROL_6 (805)

SPCSO6.q ST Other internal source

SPCSO6.t ST Other internal source

SPCSO6.ctlModel CF Other internal source

SPCSO6.sboTimeout CF Other internal source

SPCSO6.cdcNs EX Other internal source

SPCSO6.cdcName EX Other internal source

SPCSO7.ctlVal CO [12 16] - Control Input 7

SPCSO7.origin.orCat ST Other internal source

SPCSO7.origin.orIdent ST Other internal source

SPCSO7.stVal ST DDB_CONTROL_7 (806)

SPCSO7.q ST Other internal source

SPCSO7.t ST Other internal source

SPCSO7.ctlModel CF Other internal source

SPCSO7.sboTimeout CF Other internal source

SPCSO7.cdcNs EX Other internal source

SPCSO7.cdcName EX Other internal source

SPCSO8.ctlVal CO [12 17] - Control Input 8

SPCSO8.origin.orCat ST Other internal source

SPCSO8.origin.orIdent ST Other internal source

SPCSO8.stVal ST DDB_CONTROL_8 (807)

SPCSO8.q ST Other internal source

SPCSO8.t ST Other internal source

SPCSO8.ctlModel CF Other internal source

SPCSO8.sboTimeout CF Other internal source

SPCSO8.cdcNs EX Other internal source

SPCSO8.cdcName EX Other internal source

SPCSO9.ctlVal CO [12 18] - Control Input 9

SPCSO9.origin.orCat ST Other internal source

SPCSO9.origin.orIdent ST Other internal source

Page 72: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 71

Attribute FC Source SPCSO9.stVal ST DDB_CONTROL_9 (808)

SPCSO9.q ST Other internal source

SPCSO9.t ST Other internal source

SPCSO9.ctlModel CF Other internal source

SPCSO9.sboTimeout CF Other internal source

SPCSO9.cdcNs EX Other internal source

SPCSO9.cdcName EX Other internal source

SPCSO10.ctlVal CO [12 19] - Control Input 10

SPCSO10.origin.orCat ST Other internal source

SPCSO10.origin.orIdent ST Other internal source

SPCSO10.stVal ST DDB_CONTROL_10 (809)

SPCSO10.q ST Other internal source

SPCSO10.t ST Other internal source

SPCSO10.ctlModel CF Other internal source

SPCSO10.sboTimeout CF Other internal source

SPCSO10.cdcNs EX Other internal source

SPCSO10.cdcName EX Other internal source

SPCSO11.ctlVal CO [12 1A] - Control Input 11

SPCSO11.origin.orCat ST Other internal source

SPCSO11.origin.orIdent ST Other internal source

SPCSO11.stVal ST DDB_CONTROL_11 (810)

SPCSO11.q ST Other internal source

SPCSO11.t ST Other internal source

SPCSO11.ctlModel CF Other internal source

SPCSO11.sboTimeout CF Other internal source

SPCSO11.cdcNs EX Other internal source

SPCSO11.cdcName EX Other internal source

SPCSO12.ctlVal CO [12 1B] - Control Input 12

SPCSO12.origin.orCat ST Other internal source

SPCSO12.origin.orIdent ST Other internal source

SPCSO12.stVal ST DDB_CONTROL_12 (811)

SPCSO12.q ST Other internal source

SPCSO12.t ST Other internal source

SPCSO12.ctlModel CF Other internal source

SPCSO12.sboTimeout CF Other internal source

SPCSO12.cdcNs EX Other internal source

SPCSO12.cdcName EX Other internal source

SPCSO13.ctlVal CO [12 1C] - Control Input 13

SPCSO13.origin.orCat ST Other internal source

SPCSO13.origin.orIdent ST Other internal source

SPCSO13.stVal ST DDB_CONTROL_13 (812)

SPCSO13.q ST Other internal source

SPCSO13.t ST Other internal source

SPCSO13.ctlModel CF Other internal source

SPCSO13.sboTimeout CF Other internal source

SPCSO13.cdcNs EX Other internal source

Page 73: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 72 MiCOM P40Agile P14NB

Attribute FC Source SPCSO13.cdcName EX Other internal source

SPCSO14.ctlVal CO [12 1D] - Control Input 14

SPCSO14.origin.orCat ST Other internal source

SPCSO14.origin.orIdent ST Other internal source

SPCSO14.stVal ST DDB_CONTROL_14 (813)

SPCSO14.q ST Other internal source

SPCSO14.t ST Other internal source

SPCSO14.ctlModel CF Other internal source

SPCSO14.sboTimeout CF Other internal source

SPCSO14.cdcNs EX Other internal source

SPCSO14.cdcName EX Other internal source

SPCSO15.ctlVal CO [12 1E] - Control Input 15

SPCSO15.origin.orCat ST Other internal source

SPCSO15.origin.orIdent ST Other internal source

SPCSO15.stVal ST DDB_CONTROL_15 (814)

SPCSO15.q ST Other internal source

SPCSO15.t ST Other internal source

SPCSO15.ctlModel CF Other internal source

SPCSO15.sboTimeout CF Other internal source

SPCSO15.cdcNs EX Other internal source

SPCSO15.cdcName EX Other internal source

SPCSO16.ctlVal CO [12 1F] - Control Input 16

SPCSO16.origin.orCat ST Other internal source

SPCSO16.origin.orIdent ST Other internal source

SPCSO16.stVal ST DDB_CONTROL_16 (815)

SPCSO16.q ST Other internal source

SPCSO16.t ST Other internal source

SPCSO16.ctlModel CF Other internal source

SPCSO16.sboTimeout CF Other internal source

SPCSO16.cdcNs EX Other internal source

SPCSO16.cdcName EX Other internal source

SPCSO17.ctlVal CO [12 20] - Control Input 17

SPCSO17.origin.orCat ST Other internal source

SPCSO17.origin.orIdent ST Other internal source

SPCSO17.stVal ST DDB_CONTROL_17 (816)

SPCSO17.q ST Other internal source

SPCSO17.t ST Other internal source

SPCSO17.ctlModel CF Other internal source

SPCSO17.sboTimeout CF Other internal source

SPCSO17.cdcNs EX Other internal source

SPCSO17.cdcName EX Other internal source

SPCSO18.ctlVal CO [12 21] - Control Input 18

SPCSO18.origin.orCat ST Other internal source

SPCSO18.origin.orIdent ST Other internal source

SPCSO18.stVal ST DDB_CONTROL_18 (817)

SPCSO18.q ST Other internal source

Page 74: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 73

Attribute FC Source SPCSO18.t ST Other internal source

SPCSO18.ctlModel CF Other internal source

SPCSO18.sboTimeout CF Other internal source

SPCSO18.cdcNs EX Other internal source

SPCSO18.cdcName EX Other internal source

SPCSO19.ctlVal CO [12 22] - Control Input 19

SPCSO19.origin.orCat ST Other internal source

SPCSO19.origin.orIdent ST Other internal source

SPCSO19.stVal ST DDB_CONTROL_19 (818)

SPCSO19.q ST Other internal source

SPCSO19.t ST Other internal source

SPCSO19.ctlModel CF Other internal source

SPCSO19.sboTimeout CF Other internal source

SPCSO19.cdcNs EX Other internal source

SPCSO19.cdcName EX Other internal source

SPCSO20.ctlVal CO [12 23] - Control Input 20

SPCSO20.origin.orCat ST Other internal source

SPCSO20.origin.orIdent ST Other internal source

SPCSO20.stVal ST DDB_CONTROL_20 (819)

SPCSO20.q ST Other internal source

SPCSO20.t ST Other internal source

SPCSO20.ctlModel CF Other internal source

SPCSO20.sboTimeout CF Other internal source

SPCSO20.cdcNs EX Other internal source

SPCSO20.cdcName EX Other internal source

SPCSO21.ctlVal CO [12 24] - Control Input 21

SPCSO21.origin.orCat ST Other internal source

SPCSO21.origin.orIdent ST Other internal source

SPCSO21.stVal ST DDB_CONTROL_21 (820)

SPCSO21.q ST Other internal source

SPCSO21.t ST Other internal source

SPCSO21.ctlModel CF Other internal source

SPCSO21.sboTimeout CF Other internal source

SPCSO21.cdcNs EX Other internal source

SPCSO21.cdcName EX Other internal source

SPCSO22.ctlVal CO [12 25] - Control Input 22

SPCSO22.origin.orCat ST Other internal source

SPCSO22.origin.orIdent ST Other internal source

SPCSO22.stVal ST DDB_CONTROL_22 (821)

SPCSO22.q ST Other internal source

SPCSO22.t ST Other internal source

SPCSO22.ctlModel CF Other internal source

SPCSO22.sboTimeout CF Other internal source

SPCSO22.cdcNs EX Other internal source

SPCSO22.cdcName EX Other internal source

SPCSO23.ctlVal CO [12 26] - Control Input 23

Page 75: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 74 MiCOM P40Agile P14NB

Attribute FC Source SPCSO23.origin.orCat ST Other internal source

SPCSO23.origin.orIdent ST Other internal source

SPCSO23.stVal ST DDB_CONTROL_23 (822)

SPCSO23.q ST Other internal source

SPCSO23.t ST Other internal source

SPCSO23.ctlModel CF Other internal source

SPCSO23.sboTimeout CF Other internal source

SPCSO23.cdcNs EX Other internal source

SPCSO23.cdcName EX Other internal source

SPCSO24.ctlVal CO [12 27] - Control Input 24

SPCSO24.origin.orCat ST Other internal source

SPCSO24.origin.orIdent ST Other internal source

SPCSO24.stVal ST DDB_CONTROL_24 (823)

SPCSO24.q ST Other internal source

SPCSO24.t ST Other internal source

SPCSO24.ctlModel CF Other internal source

SPCSO24.sboTimeout CF Other internal source

SPCSO24.cdcNs EX Other internal source

SPCSO24.cdcName EX Other internal source

SPCSO25.ctlVal CO [12 28] - Control Input 25

SPCSO25.origin.orCat ST Other internal source

SPCSO25.origin.orIdent ST Other internal source

SPCSO25.stVal ST DDB_CONTROL_25 (824)

SPCSO25.q ST Other internal source

SPCSO25.t ST Other internal source

SPCSO25.ctlModel CF Other internal source

SPCSO25.sboTimeout CF Other internal source

SPCSO25.cdcNs EX Other internal source

SPCSO25.cdcName EX Other internal source

SPCSO26.ctlVal CO [12 29] - Control Input 26

SPCSO26.origin.orCat ST Other internal source

SPCSO26.origin.orIdent ST Other internal source

SPCSO26.stVal ST DDB_CONTROL_26 (825)

SPCSO26.q ST Other internal source

SPCSO26.t ST Other internal source

SPCSO26.ctlModel CF Other internal source

SPCSO26.sboTimeout CF Other internal source

SPCSO26.cdcNs EX Other internal source

SPCSO26.cdcName EX Other internal source

SPCSO27.ctlVal CO [12 2A] - Control Input 27

SPCSO27.origin.orCat ST Other internal source

SPCSO27.origin.orIdent ST Other internal source

SPCSO27.stVal ST DDB_CONTROL_27 (826)

SPCSO27.q ST Other internal source

SPCSO27.t ST Other internal source

SPCSO27.ctlModel CF Other internal source

Page 76: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 75

Attribute FC Source SPCSO27.sboTimeout CF Other internal source

SPCSO27.cdcNs EX Other internal source

SPCSO27.cdcName EX Other internal source

SPCSO28.ctlVal CO [12 2B] - Control Input 28

SPCSO28.origin.orCat ST Other internal source

SPCSO28.origin.orIdent ST Other internal source

SPCSO28.stVal ST DDB_CONTROL_28 (827)

SPCSO28.q ST Other internal source

SPCSO28.t ST Other internal source

SPCSO28.ctlModel CF Other internal source

SPCSO28.sboTimeout CF Other internal source

SPCSO28.cdcNs EX Other internal source

SPCSO28.cdcName EX Other internal source

SPCSO29.ctlVal CO [12 2C] - Control Input 29

SPCSO29.origin.orCat ST Other internal source

SPCSO29.origin.orIdent ST Other internal source

SPCSO29.stVal ST DDB_CONTROL_29 (828)

SPCSO29.q ST Other internal source

SPCSO29.t ST Other internal source

SPCSO29.ctlModel CF Other internal source

SPCSO29.sboTimeout CF Other internal source

SPCSO29.cdcNs EX Other internal source

SPCSO29.cdcName EX Other internal source

SPCSO30.ctlVal CO [12 2D] - Control Input 30

SPCSO30.origin.orCat ST Other internal source

SPCSO30.origin.orIdent ST Other internal source

SPCSO30.stVal ST DDB_CONTROL_30 (829)

SPCSO30.q ST Other internal source

SPCSO30.t ST Other internal source

SPCSO30.ctlModel CF Other internal source

SPCSO30.sboTimeout CF Other internal source

SPCSO30.cdcNs EX Other internal source

SPCSO30.cdcName EX Other internal source

SPCSO31.ctlVal CO [12 2E] - Control Input 31

SPCSO31.origin.orCat ST Other internal source

SPCSO31.origin.orIdent ST Other internal source

SPCSO31.stVal ST DDB_CONTROL_31 (830)

SPCSO31.q ST Other internal source

SPCSO31.t ST Other internal source

SPCSO31.ctlModel CF Other internal source

SPCSO31.sboTimeout CF Other internal source

SPCSO31.cdcNs EX Other internal source

SPCSO31.cdcName EX Other internal source

SPCSO32.ctlVal CO [12 2F] - Control Input 32

SPCSO32.origin.orCat ST Other internal source

SPCSO32.origin.orIdent ST Other internal source

Page 77: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 76 MiCOM P40Agile P14NB

Attribute FC Source SPCSO32.stVal ST DDB_CONTROL_32 (831)

SPCSO32.q ST Other internal source

SPCSO32.t ST Other internal source

SPCSO32.ctlModel CF Other internal source

SPCSO32.sboTimeout CF Other internal source

SPCSO32.cdcNs EX Other internal source

SPCSO32.cdcName EX Other internal source

SPCSO33.ctlVal CO [12 30] - Control Input 33

SPCSO33.origin.orCat ST Other internal source

SPCSO33.origin.orIdent ST Other internal source

SPCSO33.stVal ST DDB_CONTROL_33 (1248)

SPCSO33.q ST Other internal source

SPCSO33.t ST Other internal source

SPCSO33.ctlModel CF Other internal source

SPCSO33.sboTimeout CF Other internal source

SPCSO33.cdcNs EX Other internal source

SPCSO33.cdcName EX Other internal source

SPCSO34.ctlVal CO [12 31] - Control Input 34

SPCSO34.origin.orCat ST Other internal source

SPCSO34.origin.orIdent ST Other internal source

SPCSO34.stVal ST DDB_CONTROL_34 (1249)

SPCSO34.q ST Other internal source

SPCSO34.t ST Other internal source

SPCSO34.ctlModel CF Other internal source

SPCSO34.sboTimeout CF Other internal source

SPCSO34.cdcNs EX Other internal source

SPCSO34.cdcName EX Other internal source

SPCSO35.ctlVal CO [12 32] - Control Input 35

SPCSO35.origin.orCat ST Other internal source

SPCSO35.origin.orIdent ST Other internal source

SPCSO35.stVal ST DDB_CONTROL_35 (1250)

SPCSO35.q ST Other internal source

SPCSO35.t ST Other internal source

SPCSO35.ctlModel CF Other internal source

SPCSO35.sboTimeout CF Other internal source

SPCSO35.cdcNs EX Other internal source

SPCSO35.cdcName EX Other internal source

SPCSO36.ctlVal CO [12 33] - Control Input 36

SPCSO36.origin.orCat ST Other internal source

SPCSO36.origin.orIdent ST Other internal source

SPCSO36.stVal ST DDB_CONTROL_36 (1251)

SPCSO36.q ST Other internal source

SPCSO36.t ST Other internal source

SPCSO36.ctlModel CF Other internal source

SPCSO36.sboTimeout CF Other internal source

SPCSO36.cdcNs EX Other internal source

Page 78: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 77

Attribute FC Source SPCSO36.cdcName EX Other internal source

SPCSO37.ctlVal CO [12 34] - Control Input 37

SPCSO37.origin.orCat ST Other internal source

SPCSO37.origin.orIdent ST Other internal source

SPCSO37.stVal ST DDB_CONTROL_37 (1252)

SPCSO37.q ST Other internal source

SPCSO37.t ST Other internal source

SPCSO37.ctlModel CF Other internal source

SPCSO37.sboTimeout CF Other internal source

SPCSO37.cdcNs EX Other internal source

SPCSO37.cdcName EX Other internal source

SPCSO38.ctlVal CO [12 35] - Control Input 38

SPCSO38.origin.orCat ST Other internal source

SPCSO38.origin.orIdent ST Other internal source

SPCSO38.stVal ST DDB_CONTROL_38 (1253)

SPCSO38.q ST Other internal source

SPCSO38.t ST Other internal source

SPCSO38.ctlModel CF Other internal source

SPCSO38.sboTimeout CF Other internal source

SPCSO38.cdcNs EX Other internal source

SPCSO38.cdcName EX Other internal source

SPCSO39.ctlVal CO [12 36] - Control Input 39

SPCSO39.origin.orCat ST Other internal source

SPCSO39.origin.orIdent ST Other internal source

SPCSO39.stVal ST DDB_CONTROL_39 (1254)

SPCSO39.q ST Other internal source

SPCSO39.t ST Other internal source

SPCSO39.ctlModel CF Other internal source

SPCSO39.sboTimeout CF Other internal source

SPCSO39.cdcNs EX Other internal source

SPCSO39.cdcName EX Other internal source

SPCSO40.ctlVal CO [12 37] - Control Input 40

SPCSO40.origin.orCat ST Other internal source

SPCSO40.origin.orIdent ST Other internal source

SPCSO40.stVal ST DDB_CONTROL_40 (1255)

SPCSO40.q ST Other internal source

SPCSO40.t ST Other internal source

SPCSO40.ctlModel CF Other internal source

SPCSO40.sboTimeout CF Other internal source

SPCSO40.cdcNs EX Other internal source

SPCSO40.cdcName EX Other internal source

SPCSO41.ctlVal CO [12 38] - Control Input 41

SPCSO41.origin.orCat ST Other internal source

SPCSO41.origin.orIdent ST Other internal source

SPCSO41.stVal ST DDB_CONTROL_41 (1256)

SPCSO41.q ST Other internal source

Page 79: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 78 MiCOM P40Agile P14NB

Attribute FC Source SPCSO41.t ST Other internal source

SPCSO41.ctlModel CF Other internal source

SPCSO41.sboTimeout CF Other internal source

SPCSO41.cdcNs EX Other internal source

SPCSO41.cdcName EX Other internal source

SPCSO42.ctlVal CO [12 39] - Control Input 42

SPCSO42.origin.orCat ST Other internal source

SPCSO42.origin.orIdent ST Other internal source

SPCSO42.stVal ST DDB_CONTROL_42 (1257)

SPCSO42.q ST Other internal source

SPCSO42.t ST Other internal source

SPCSO42.ctlModel CF Other internal source

SPCSO42.sboTimeout CF Other internal source

SPCSO42.cdcNs EX Other internal source

SPCSO42.cdcName EX Other internal source

SPCSO43.ctlVal CO [12 3A] - Control Input 43

SPCSO43.origin.orCat ST Other internal source

SPCSO43.origin.orIdent ST Other internal source

SPCSO43.stVal ST DDB_CONTROL_43 (1258)

SPCSO43.q ST Other internal source

SPCSO43.t ST Other internal source

SPCSO43.ctlModel CF Other internal source

SPCSO43.sboTimeout CF Other internal source

SPCSO43.cdcNs EX Other internal source

SPCSO43.cdcName EX Other internal source

SPCSO44.ctlVal CO [12 3B] - Control Input 44

SPCSO44.origin.orCat ST Other internal source

SPCSO44.origin.orIdent ST Other internal source

SPCSO44.stVal ST DDB_CONTROL_44 (1259)

SPCSO44.q ST Other internal source

SPCSO44.t ST Other internal source

SPCSO44.ctlModel CF Other internal source

SPCSO44.sboTimeout CF Other internal source

SPCSO44.cdcNs EX Other internal source

SPCSO44.cdcName EX Other internal source

SPCSO45.ctlVal CO [12 3C] - Control Input 45

SPCSO45.origin.orCat ST Other internal source

SPCSO45.origin.orIdent ST Other internal source

SPCSO45.stVal ST DDB_CONTROL_45 (1260)

SPCSO45.q ST Other internal source

SPCSO45.t ST Other internal source

SPCSO45.ctlModel CF Other internal source

SPCSO45.sboTimeout CF Other internal source

SPCSO45.cdcNs EX Other internal source

SPCSO45.cdcName EX Other internal source

SPCSO46.ctlVal CO [12 3D] - Control Input 46

Page 80: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 79

Attribute FC Source SPCSO46.origin.orCat ST Other internal source

SPCSO46.origin.orIdent ST Other internal source

SPCSO46.stVal ST DDB_CONTROL_46 (1261)

SPCSO46.q ST Other internal source

SPCSO46.t ST Other internal source

SPCSO46.ctlModel CF Other internal source

SPCSO46.sboTimeout CF Other internal source

SPCSO46.cdcNs EX Other internal source

SPCSO46.cdcName EX Other internal source

SPCSO47.ctlVal CO [12 3E] - Control Input 47

SPCSO47.origin.orCat ST Other internal source

SPCSO47.origin.orIdent ST Other internal source

SPCSO47.stVal ST DDB_CONTROL_47 (1262)

SPCSO47.q ST Other internal source

SPCSO47.t ST Other internal source

SPCSO47.ctlModel CF Other internal source

SPCSO47.sboTimeout CF Other internal source

SPCSO47.cdcNs EX Other internal source

SPCSO47.cdcName EX Other internal source

SPCSO48.ctlVal CO [12 3F] - Control Input 48

SPCSO48.origin.orCat ST Other internal source

SPCSO48.origin.orIdent ST Other internal source

SPCSO48.stVal ST DDB_CONTROL_48 (1263)

SPCSO48.q ST Other internal source

SPCSO48.t ST Other internal source

SPCSO48.ctlModel CF Other internal source

SPCSO48.sboTimeout CF Other internal source

SPCSO48.cdcNs EX Other internal source

SPCSO48.cdcName EX Other internal source

SPCSO49.ctlVal CO [12 40] - Control Input 49

SPCSO49.origin.orCat ST Other internal source

SPCSO49.origin.orIdent ST Other internal source

SPCSO49.stVal ST DDB_CONTROL_49 (1264)

SPCSO49.q ST Other internal source

SPCSO49.t ST Other internal source

SPCSO49.ctlModel CF Other internal source

SPCSO49.sboTimeout CF Other internal source

SPCSO49.cdcNs EX Other internal source

SPCSO49.cdcName EX Other internal source

SPCSO50.ctlVal CO [12 41] - Control Input 50

SPCSO50.origin.orCat ST Other internal source

SPCSO50.origin.orIdent ST Other internal source

SPCSO50.stVal ST DDB_CONTROL_50 (1265)

SPCSO50.q ST Other internal source

SPCSO50.t ST Other internal source

SPCSO50.ctlModel CF Other internal source

Page 81: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 80 MiCOM P40Agile P14NB

Attribute FC Source SPCSO50.sboTimeout CF Other internal source

SPCSO50.cdcNs EX Other internal source

SPCSO50.cdcName EX Other internal source

SPCSO51.ctlVal CO [12 42] - Control Input 51

SPCSO51.origin.orCat ST Other internal source

SPCSO51.origin.orIdent ST Other internal source

SPCSO51.stVal ST DDB_CONTROL_51 (1266)

SPCSO51.q ST Other internal source

SPCSO51.t ST Other internal source

SPCSO51.ctlModel CF Other internal source

SPCSO51.sboTimeout CF Other internal source

SPCSO51.cdcNs EX Other internal source

SPCSO51.cdcName EX Other internal source

SPCSO52.ctlVal CO [12 43] - Control Input 52

SPCSO52.origin.orCat ST Other internal source

SPCSO52.origin.orIdent ST Other internal source

SPCSO52.stVal ST DDB_CONTROL_52 (1267)

SPCSO52.q ST Other internal source

SPCSO52.t ST Other internal source

SPCSO52.ctlModel CF Other internal source

SPCSO52.sboTimeout CF Other internal source

SPCSO52.cdcNs EX Other internal source

SPCSO52.cdcName EX Other internal source

SPCSO53.ctlVal CO [12 44] - Control Input 53

SPCSO53.origin.orCat ST Other internal source

SPCSO53.origin.orIdent ST Other internal source

SPCSO53.stVal ST DDB_CONTROL_53 (1268)

SPCSO53.q ST Other internal source

SPCSO53.t ST Other internal source

SPCSO53.ctlModel CF Other internal source

SPCSO53.sboTimeout CF Other internal source

SPCSO53.cdcNs EX Other internal source

SPCSO53.cdcName EX Other internal source

SPCSO54.ctlVal CO [12 45] - Control Input 54

SPCSO54.origin.orCat ST Other internal source

SPCSO54.origin.orIdent ST Other internal source

SPCSO54.stVal ST DDB_CONTROL_54 (1269)

SPCSO54.q ST Other internal source

SPCSO54.t ST Other internal source

SPCSO54.ctlModel CF Other internal source

SPCSO54.sboTimeout CF Other internal source

SPCSO54.cdcNs EX Other internal source

SPCSO54.cdcName EX Other internal source

SPCSO55.ctlVal CO [12 46] - Control Input 55

SPCSO55.origin.orCat ST Other internal source

SPCSO55.origin.orIdent ST Other internal source

Page 82: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 81

Attribute FC Source SPCSO55.stVal ST DDB_CONTROL_55 (1270)

SPCSO55.q ST Other internal source

SPCSO55.t ST Other internal source

SPCSO55.ctlModel CF Other internal source

SPCSO55.sboTimeout CF Other internal source

SPCSO55.cdcNs EX Other internal source

SPCSO55.cdcName EX Other internal source

SPCSO56.ctlVal CO [12 47] - Control Input 56

SPCSO56.origin.orCat ST Other internal source

SPCSO56.origin.orIdent ST Other internal source

SPCSO56.stVal ST DDB_CONTROL_56 (1271)

SPCSO56.q ST Other internal source

SPCSO56.t ST Other internal source

SPCSO56.ctlModel CF Other internal source

SPCSO56.sboTimeout CF Other internal source

SPCSO56.cdcNs EX Other internal source

SPCSO56.cdcName EX Other internal source

SPCSO57.ctlVal CO [12 48] - Control Input 57

SPCSO57.origin.orCat ST Other internal source

SPCSO57.origin.orIdent ST Other internal source

SPCSO57.stVal ST DDB_CONTROL_57 (1272)

SPCSO57.q ST Other internal source

SPCSO57.t ST Other internal source

SPCSO57.ctlModel CF Other internal source

SPCSO57.sboTimeout CF Other internal source

SPCSO57.cdcNs EX Other internal source

SPCSO57.cdcName EX Other internal source

SPCSO58.ctlVal CO [12 49] - Control Input 58

SPCSO58.origin.orCat ST Other internal source

SPCSO58.origin.orIdent ST Other internal source

SPCSO58.stVal ST DDB_CONTROL_58 (1273)

SPCSO58.q ST Other internal source

SPCSO58.t ST Other internal source

SPCSO58.ctlModel CF Other internal source

SPCSO58.sboTimeout CF Other internal source

SPCSO58.cdcNs EX Other internal source

SPCSO58.cdcName EX Other internal source

SPCSO59.ctlVal CO [12 4A] - Control Input 59

SPCSO59.origin.orCat ST Other internal source

SPCSO59.origin.orIdent ST Other internal source

SPCSO59.stVal ST DDB_CONTROL_59 (1274)

SPCSO59.q ST Other internal source

SPCSO59.t ST Other internal source

SPCSO59.ctlModel CF Other internal source

SPCSO59.sboTimeout CF Other internal source

SPCSO59.cdcNs EX Other internal source

Page 83: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 82 MiCOM P40Agile P14NB

Attribute FC Source SPCSO59.cdcName EX Other internal source

SPCSO60.ctlVal CO [12 4B] - Control Input 60

SPCSO60.origin.orCat ST Other internal source

SPCSO60.origin.orIdent ST Other internal source

SPCSO60.stVal ST DDB_CONTROL_60 (1275)

SPCSO60.q ST Other internal source

SPCSO60.t ST Other internal source

SPCSO60.ctlModel CF Other internal source

SPCSO60.sboTimeout CF Other internal source

SPCSO60.cdcNs EX Other internal source

SPCSO60.cdcName EX Other internal source

SPCSO61.ctlVal CO [12 4C] - Control Input 61

SPCSO61.origin.orCat ST Other internal source

SPCSO61.origin.orIdent ST Other internal source

SPCSO61.stVal ST DDB_CONTROL_61 (1276)

SPCSO61.q ST Other internal source

SPCSO61.t ST Other internal source

SPCSO61.ctlModel CF Other internal source

SPCSO61.sboTimeout CF Other internal source

SPCSO61.cdcNs EX Other internal source

SPCSO61.cdcName EX Other internal source

SPCSO62.ctlVal CO [12 4D] - Control Input 62

SPCSO62.origin.orCat ST Other internal source

SPCSO62.origin.orIdent ST Other internal source

SPCSO62.stVal ST DDB_CONTROL_62 (1277)

SPCSO62.q ST Other internal source

SPCSO62.t ST Other internal source

SPCSO62.ctlModel CF Other internal source

SPCSO62.sboTimeout CF Other internal source

SPCSO62.cdcNs EX Other internal source

SPCSO62.cdcName EX Other internal source

SPCSO63.ctlVal CO [12 4E] - Control Input 63

SPCSO63.origin.orCat ST Other internal source

SPCSO63.origin.orIdent ST Other internal source

SPCSO63.stVal ST DDB_CONTROL_63 (1278)

SPCSO63.q ST Other internal source

SPCSO63.t ST Other internal source

SPCSO63.ctlModel CF Other internal source

SPCSO63.sboTimeout CF Other internal source

SPCSO63.cdcNs EX Other internal source

SPCSO63.cdcName EX Other internal source

SPCSO64.ctlVal CO [12 4F] - Control Input 64

SPCSO64.origin.orCat ST Other internal source

SPCSO64.origin.orIdent ST Other internal source

SPCSO64.stVal ST DDB_CONTROL_64 (1279)

SPCSO64.q ST Other internal source

Page 84: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 83

Attribute FC Source SPCSO64.t ST Other internal source

SPCSO64.ctlModel CF Other internal source

SPCSO64.sboTimeout CF Other internal source

SPCSO64.cdcNs EX Other internal source

SPCSO64.cdcName EX Other internal source

1.6.12 Logical Node: RlyGGIO1

Description: Output Contacts

Attribute FC Source Mod.stVal ST [0F 0D] - Test Mode

Mod.q ST Other internal source

Mod.t ST Other internal source

Mod.ctlModel CF Other internal source

Beh.stVal ST [0F 0D] - Test Mode

Beh.q ST Other internal source

Beh.t ST Other internal source

Health.stVal ST Other internal source

Health.q ST Other internal source

Health.t ST Other internal source

NamPlt.vendor DC Other internal source

NamPlt.swRev DC [00 11] - Software Ref. 1

NamPlt.d DC [0F 02] - Relay O/P Status

Ind1.stVal ST DDB_OUTPUT_RELAY_1 (0)

Ind1.q ST Other internal source

Ind1.t ST Other internal source

Ind1.d DC [4B 01] - Relay 1

Ind2.stVal ST DDB_OUTPUT_RELAY_2 (1)

Ind2.q ST Other internal source

Ind2.t ST Other internal source

Ind2.d DC [4B 02] - Relay 2

Ind3.stVal ST DDB_OUTPUT_RELAY_3 (2)

Ind3.q ST Other internal source

Ind3.t ST Other internal source

Ind3.d DC [4B 03] - Relay 3

Ind4.stVal ST DDB_OUTPUT_RELAY_4 (3)

Ind4.q ST Other internal source

Ind4.t ST Other internal source

Ind4.d DC [4B 04] - Relay 4

Ind5.stVal ST DDB_OUTPUT_RELAY_5 (4)

Ind5.q ST Other internal source

Ind5.t ST Other internal source

Ind5.d DC [4B 05] - Relay 5

Ind6.stVal ST DDB_OUTPUT_RELAY_6 (5)

Ind6.q ST Other internal source

Ind6.t ST Other internal source

Ind6.d DC [4B 06] - Relay 6

Page 85: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 84 MiCOM P40Agile P14NB

Attribute FC Source Ind7.stVal ST DDB_OUTPUT_RELAY_7 (6)

Ind7.q ST Other internal source

Ind7.t ST Other internal source

Ind7.d DC [4B 07] - Relay 7

Ind8.stVal ST DDB_OUTPUT_RELAY_8 (7)

Ind8.q ST Other internal source

Ind8.t ST Other internal source

Ind8.d DC [4B 08] - Relay 8

Page 86: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 85 2. PX40 ADDRESS ASSIGNMENT LIST (ADL)

2.1 OBJECTIVE

This section of the document is the MiCOM Px40 Address Assignment List (ADL) and presents the relationships between Courier Cells / Digital Data Bus signals in the settings database of the P141 and Data Attributes of the IEC 61850 data model.

2.2 COURIER CELL

The following table presents the Courier Cell mappings.

Courier Cell Attribute Reference [00 05] Plant Reference

Control/LPHD1.DC.PhyNam.location

Measurements/LPHD1.DC.PhyNam.location

Protection/LPHD1.DC.PhyNam.location

Records/LPHD1.DC.PhyNam.location

System/LPHD1.DC.PhyNam.location

[00 06] Model Number

Control/LPHD1.DC.PhyNam.model

Measurements/LPHD1.DC.PhyNam.model

Protection/LPHD1.DC.PhyNam.model

Records/LPHD1.DC.PhyNam.model

System/LPHD1.DC.PhyNam.model

[00 08] Serial Number

Control/LPHD1.DC.PhyNam.serNum

Measurements/LPHD1.DC.PhyNam.serNum

Protection/LPHD1.DC.PhyNam.serNum

Records/LPHD1.DC.PhyNam.serNum

System/LPHD1.DC.PhyNam.serNum

[00 10] CB Trip/Close

Control/XCBR1.CO.Pos.ctlVal

[00 11] Software Ref. 1

Control/XCBR1.DC.NamPlt.swRev

Control/CILO1.DC.NamPlt.swRev

Control/LLN0.DC.NamPlt.swRev

Control/LPHD1.DC.PhyNam.swRev

Measurements/PriFouMMXU1.DC.NamPlt.swRev

Measurements/SecMSTA1.DC.NamPlt.swRev

Measurements/SecMSQI1.DC.NamPlt.swRev

Measurements/PriRmsMMXU1.DC.NamPlt.swRev

Measurements/SecFouMMXU1.DC.NamPlt.swRev

Measurements/LPHD1.DC.PhyNam.swRev

Measurements/PriMSTA1.DC.NamPlt.swRev

Measurements/PriMSQI1.DC.NamPlt.swRev

Measurements/SecRmsMMXU1.DC.NamPlt.swRev

Measurements/LLN0.DC.NamPlt.swRev

Protection/SenEftPTOC4.DC.NamPlt.swRev

Protection/OcpPTOC3.DC.NamPlt.swRev

Page 87: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 86 MiCOM P40Agile P14NB

Courier Cell Attribute Reference Protection/SenEftPTOC3.DC.NamPlt.swRev

Protection/OcpPTOC5.DC.NamPlt.swRev

Protection/EfmPTOC3.DC.NamPlt.swRev

Protection/EfmPTOC1.DC.NamPlt.swRev

Protection/EfmPTOC2.DC.NamPlt.swRev

Protection/SenEftPTOC1.DC.NamPlt.swRev

Protection/ThmPTTR1.DC.NamPlt.swRev

Protection/NgcPTOC2.DC.NamPlt.swRev

Protection/NgcPTOC1.DC.NamPlt.swRev

Protection/OcpPTOC4.DC.NamPlt.swRev

Protection/LPHD1.DC.PhyNam.swRev

Protection/SenEftPTOC2.DC.NamPlt.swRev

Protection/PTRC1.DC.NamPlt.swRev

Protection/LLN0.DC.NamPlt.swRev

Protection/OcpPTOC2.DC.NamPlt.swRev

Protection/EfmPTOC4.DC.NamPlt.swRev

Protection/NgcPTOC3.DC.NamPlt.swRev

Protection/NgcPTOC4.DC.NamPlt.swRev

Protection/OcpPTOC6.DC.NamPlt.swRev

Protection/EfdPTOC4.DC.NamPlt.swRev

Protection/EfdPTOC3.DC.NamPlt.swRev

Protection/EfdPTOC2.DC.NamPlt.swRev

Protection/EfdPTOC1.DC.NamPlt.swRev

Protection/OcpPTOC1.DC.NamPlt.swRev

Protection/CbfRBRF2.DC.NamPlt.swRev

Protection/CbfRBRF1.DC.NamPlt.swRev

Records/LLN0.DC.NamPlt.swRev

Records/LPHD1.DC.PhyNam.swRev

Records/RDRE1.DC.NamPlt.swRev

System/LedGGIO1.DC.NamPlt.swRev

System/OptGGIO1.DC.NamPlt.swRev

System/OrdRunGGIO1.DC.NamPlt.swRev

System/AlmGGIO1.DC.NamPlt.swRev

System/GosGGIO2.DC.NamPlt.swRev

System/RlyGGIO1.DC.NamPlt.swRev

System/LLN0.DC.NamPlt.swRev

System/LedGGIO2.DC.NamPlt.swRev

System/LPHD1.DC.PhyNam.swRev

System/PloGGIO1.DC.NamPlt.swRev

System/GosGGIO1.DC.NamPlt.swRev

System/FnkGGIO1.DC.NamPlt.swRev

[01 FF] Reset Indication

System/LLN0.CO.LEDRs.ctlVal

System/LLN0.ST.LEDRs.stVal

[02 01] IA Magnitude

Measurements/PriFouMMXU1.MX.A1.phsA.cVal.mag.f

Page 88: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 87

Courier Cell Attribute Reference Measurements/SecFouMMXU1.CF.A1.phsA.units.SIUnit

Measurements/SecFouMMXU1.MX.A1.phsA.cVal.mag.f

Measurements/PriFouMMXU1.CF.A1.phsA.units.SIUnit

[02 02] IA Phase Angle

Measurements/PriFouMMXU1.MX.A1.phsA.cVal.ang.f

Measurements/SecFouMMXU1.MX.A1.phsA.cVal.ang.f

[02 03] IB Magnitude

Measurements/SecFouMMXU1.MX.A1.phsB.cVal.mag.f

Measurements/PriFouMMXU1.MX.A1.phsB.cVal.mag.f

Measurements/SecFouMMXU1.CF.A1.phsB.units.SIUnit

Measurements/PriFouMMXU1.CF.A1.phsB.units.SIUnit

[02 04] IB Phase Angle

Measurements/PriFouMMXU1.MX.A1.phsB.cVal.ang.f

Measurements/SecFouMMXU1.MX.A1.phsB.cVal.ang.f

[02 05] IC Magnitude

Measurements/PriFouMMXU1.CF.A1.phsC.units.SIUnit

Measurements/SecFouMMXU1.CF.A1.phsC.units.SIUnit

Measurements/PriFouMMXU1.MX.A1.phsC.cVal.mag.f

Measurements/SecFouMMXU1.MX.A1.phsC.cVal.mag.f

[02 06] IC Phase Angle

Measurements/SecFouMMXU1.MX.A1.phsC.cVal.ang.f

Measurements/PriFouMMXU1.MX.A1.phsC.cVal.ang.f

[02 07] IN Measured Mag

Measurements/SecFouMMXU1.CF.A2.res.units.SIUnit

Measurements/SecFouMMXU1.MX.A2.res.cVal.mag.f

Measurements/PriFouMMXU1.MX.A2.res.cVal.mag.f

Measurements/PriFouMMXU1.CF.A2.res.units.SIUnit

[02 08] IN Measured Ang

Measurements/PriFouMMXU1.MX.A2.res.cVal.ang.f

Measurements/SecFouMMXU1.MX.A2.res.cVal.ang.f

[02 09] IN Derived Mag

Measurements/PriFouMMXU1.CF.A1.neut.units.SIUnit

Measurements/SecFouMMXU1.CF.A1.neut.units.SIUnit

Measurements/PriFouMMXU1.MX.A1.neut.cVal.mag.f

Measurements/SecFouMMXU1.MX.A1.neut.cVal.mag.f

[02 0A] IN Derived Angle

Measurements/PriFouMMXU1.MX.A1.neut.cVal.ang.f

Measurements/SecFouMMXU1.MX.A1.neut.cVal.ang.f

[02 0B] ISEF Magnitude

Measurements/SecFouMMXU1.CF.A3.res.units.SIUnit

Measurements/PriFouMMXU1.MX.A3.res.cVal.mag.f

Measurements/SecFouMMXU1.MX.A3.res.cVal.mag.f

Measurements/PriFouMMXU1.CF.A3.res.units.SIUnit

[02 0C] ISEF Angle

Measurements/SecFouMMXU1.MX.A3.res.cVal.ang.f

Measurements/PriFouMMXU1.MX.A3.res.cVal.ang.f

Page 89: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 88 MiCOM P40Agile P14NB

Courier Cell Attribute Reference [02 10] IA RMS

Measurements/SecRmsMMXU1.MX.A.phsA.cVal.mag.f

Measurements/SecRmsMMXU1.CF.A.phsA.units.SIUnit

Measurements/PriRmsMMXU1.CF.A.phsA.units.SIUnit

Measurements/PriRmsMMXU1.MX.A.phsA.cVal.mag.f

[02 11] IB RMS

Measurements/PriRmsMMXU1.CF.A.phsC.units.SIUnit

Measurements/PriRmsMMXU1.CF.A.phsB.units.SIUnit

Measurements/PriRmsMMXU1.MX.A.phsB.cVal.mag.f

Measurements/SecRmsMMXU1.CF.A.phsC.units.SIUnit

Measurements/SecRmsMMXU1.CF.A.phsB.units.SIUnit

Measurements/SecRmsMMXU1.MX.A.phsB.cVal.mag.f

[02 12] IC RMS

Measurements/PriRmsMMXU1.MX.A.phsC.cVal.mag.f

Measurements/SecRmsMMXU1.MX.A.phsC.cVal.mag.f

[02 2D] Frequency

Measurements/SecFouMMXU1.MX.Hz.mag.f

Measurements/PriFouMMXU1.CF.Hz.units.SIUnit

Measurements/PriFouMMXU1.MX.Hz.mag.f

Measurements/SecFouMMXU1.CF.Hz.units.SIUnit

[02 40] I1 Magnitude

Measurements/SecMSQI1.CF.SeqA.c1.units.SIUnit

Measurements/SecMSQI1.MX.SeqA.c1.cVal.mag.f

Measurements/PriMSQI1.MX.SeqA.c1.cVal.mag.f

Measurements/PriMSQI1.CF.SeqA.c1.units.SIUnit

[02 41] I1 Phase Angle

Measurements/PriMSQI1.MX.SeqA.c1.cVal.ang.f

Measurements/SecMSQI1.MX.SeqA.c1.cVal.ang.f

[02 42] I2 Magnitude

Measurements/SecMSQI1.CF.SeqA.c2.units.SIUnit

Measurements/SecMSQI1.MX.SeqA.c2.cVal.mag.f

Measurements/PriMSQI1.MX.SeqA.c2.cVal.mag.f

Measurements/PriMSQI1.CF.SeqA.c2.units.SIUnit

[02 43] I2 Phase Angle

Measurements/SecMSQI1.MX.SeqA.c2.cVal.ang.f

Measurements/PriMSQI1.MX.SeqA.c2.cVal.ang.f

[02 44] I0 Magnitude

Measurements/PriMSQI1.MX.SeqA.c3.cVal.mag.f

Measurements/PriMSQI1.CF.SeqA.c3.units.SIUnit

Measurements/SecMSQI1.CF.SeqA.c3.units.SIUnit

Measurements/SecMSQI1.MX.SeqA.c3.cVal.mag.f

[02 45] I0 Phase Angle

Measurements/SecMSQI1.MX.SeqA.c3.cVal.ang.f

Measurements/PriMSQI1.MX.SeqA.c3.cVal.ang.f

[03 18] IA Fixed Demand

Measurements/PriMSTA1.MX.AvAmps1.mag.f

Page 90: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 89

Courier Cell Attribute Reference Measurements/PriMSTA1.CF.AvAmps1.units.SIUnit

Measurements/SecMSTA1.DC.AvAmps1.d

Measurements/SecMSTA1.CF.AvAmps1.units.SIUnit

Measurements/SecMSTA1.MX.AvAmps1.mag.f

Measurements/PriMSTA1.DC.AvAmps1.d

[03 19] IB Fixed Demand

Measurements/PriMSTA1.DC.AvAmps2.d

Measurements/PriMSTA1.CF.AvAmps2.units.SIUnit

Measurements/PriMSTA1.MX.AvAmps2.mag.f

Measurements/SecMSTA1.MX.AvAmps2.mag.f

Measurements/SecMSTA1.CF.AvAmps2.units.SIUnit

Measurements/SecMSTA1.DC.AvAmps2.d

[03 1A] IC Fixed Demand

Measurements/PriMSTA1.DC.AvAmps3.d

Measurements/SecMSTA1.DC.AvAmps3.d

Measurements/SecMSTA1.MX.AvAmps3.mag.f

Measurements/PriMSTA1.CF.AvAmps3.units.SIUnit

Measurements/PriMSTA1.MX.AvAmps3.mag.f

Measurements/SecMSTA1.CF.AvAmps3.units.SIUnit

[03 1D] IA Roll Demand

Measurements/PriMSTA1.CF.AvAmps4.units.SIUnit

Measurements/SecMSTA1.CF.AvAmps4.units.SIUnit

Measurements/SecMSTA1.MX.AvAmps4.mag.f

Measurements/PriMSTA1.DC.AvAmps4.d

Measurements/SecMSTA1.DC.AvAmps4.d

Measurements/PriMSTA1.MX.AvAmps4.mag.f

[03 1E] IB Roll Demand

Measurements/SecMSTA1.DC.AvAmps5.d

Measurements/SecMSTA1.CF.AvAmps5.units.SIUnit

Measurements/PriMSTA1.CF.AvAmps5.units.SIUnit

Measurements/PriMSTA1.DC.AvAmps5.d

Measurements/PriMSTA1.MX.AvAmps5.mag.f

Measurements/SecMSTA1.MX.AvAmps5.mag.f

[03 1F] IC Roll Demand

Measurements/PriMSTA1.CF.AvAmps6.units.SIUnit

Measurements/SecMSTA1.CF.AvAmps6.units.SIUnit

Measurements/SecMSTA1.DC.AvAmps6.d

Measurements/SecMSTA1.MX.AvAmps6.mag.f

Measurements/PriMSTA1.DC.AvAmps6.d

Measurements/PriMSTA1.MX.AvAmps6.mag.f

[03 22] IA Peak Demand

Measurements/PriMSTA1.MX.MaxAmps1.mag.f

Measurements/SecMSTA1.MX.MaxAmps1.mag.f

Measurements/PriMSTA1.DC.MaxAmps1.d

Measurements/SecMSTA1.CF.MaxAmps1.units.SIUnit

Measurements/SecMSTA1.DC.MaxAmps1.d

Page 91: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 90 MiCOM P40Agile P14NB

Courier Cell Attribute Reference Measurements/PriMSTA1.CF.MaxAmps1.units.SIUnit

[03 23] IB Peak Demand

Measurements/PriMSTA1.CF.MaxAmps2.units.SIUnit

Measurements/PriMSTA1.DC.MaxAmps2.d

Measurements/PriMSTA1.MX.MaxAmps2.mag.f

Measurements/SecMSTA1.MX.MaxAmps2.mag.f

Measurements/SecMSTA1.CF.MaxAmps2.units.SIUnit

Measurements/SecMSTA1.DC.MaxAmps2.d

[03 24] IC Peak Demand

Measurements/SecMSTA1.CF.MaxAmps3.units.SIUnit

Measurements/SecMSTA1.MX.MaxAmps3.mag.f

Measurements/PriMSTA1.MX.MaxAmps3.mag.f

Measurements/PriMSTA1.CF.MaxAmps3.units.SIUnit

Measurements/PriMSTA1.DC.MaxAmps3.d

Measurements/SecMSTA1.DC.MaxAmps3.d

[04 01] Highest Phase I

Protection/ThmPTTR1.MX.Amp.mag.f

Protection/ThmPTTR1.CF.Amp.units.SIUnit

[04 02] Thermal State

Protection/ThmPTTR1.MX.TmpRl.mag.f

Protection/ThmPTTR1.CF.TmpRl.units.SIUnit

[04 03] Reset Thermal

Protection/ThmPTTR1.CO.MTRRs.ctlVal

Protection/ThmPTTR1.ST.MTRRs.stVal

[04 0C] I2/I1 Ratio

Measurements/PriMSQI1.MX.ImbNgA.mag.f

Measurements/SecMSQI1.MX.ImbNgA.mag.f

Measurements/PriMSQI1.CF.ImbNgA.units.SIUnit

Measurements/SecMSQI1.CF.ImbNgA.units.SIUnit

[06 00] CB CONDITION

Control/CILO1.DC.NamPlt.d

Control/XCBR1.DC.NamPlt.d

[06 01] CB Operations

Control/XCBR1.ST.OpCnt.stVal

[07 01] CB Control by

Control/XCBR1.ST.Loc.stVal

[09 10] Overcurrent

Protection/LLN0.DC.OcpBeh.d

Protection/LLN0.CO.OcpMod.ctlVal

Protection/LLN0.ST.OcpBeh.stVal

Protection/LLN0.ST.OcpMod.stVal

[09 11] Neg Sequence O/C

Protection/LLN0.ST.NgcMod.stVal

Protection/LLN0.ST.NgcBeh.stVal

Protection/LLN0.CO.NgcMod.ctlVal

Protection/LLN0.DC.NgcBeh.d

Page 92: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 91

Courier Cell Attribute Reference [09 13] Earth Fault 1

Protection/LLN0.CO.EfmMod.ctlVal

Protection/LLN0.DC.EfmBeh.d

Protection/LLN0.ST.EfmBeh.stVal

Protection/LLN0.ST.EfmMod.stVal

[09 14] Earth Fault 2

Protection/LLN0.DC.EfdBeh.d

Protection/LLN0.CO.EfdMod.ctlVal

Protection/LLN0.ST.EfdMod.stVal

Protection/LLN0.ST.EfdBeh.stVal

[09 15] SEF/REF Prot'n

Protection/LLN0.DC.SenBeh.d

Protection/LLN0.ST.SenBeh.stVal

Protection/LLN0.ST.SenMod.stVal

Protection/LLN0.CO.SenMod.ctlVal

[09 17] Thermal Overload

Protection/LLN0.CO.ThmMod.ctlVal

Protection/LLN0.ST.ThmMod.stVal

Protection/LLN0.ST.ThmBeh.stVal

Protection/LLN0.DC.ThmBeh.d

Protection/ThmPTTR1.DC.NamPlt.d

[09 20] CB Fail

Protection/LLN0.ST.CbfMod.stVal

Protection/LLN0.ST.CbfBeh.stVal

Protection/LLN0.CO.CbfMod.ctlVal

Protection/LLN0.DC.CbfBeh.d

[0F 01] Opto I/P Status

System/OptGGIO1.DC.NamPlt.d

[0F 02] Relay O/P Status

System/RlyGGIO1.DC.NamPlt.d

[0F 0D] Test Mode

Protection/PTRC1.ST.Beh.stVal

Protection/PTRC1.ST.Mod.stVal

System/RlyGGIO1.ST.Beh.stVal

System/RlyGGIO1.ST.Mod.stVal

[12 01] Ctrl I/P Status

System/PloGGIO1.DC.NamPlt.d

[12 10] Control Input 1

System/PloGGIO1.CO.SPCSO1.ctlVal

[12 11] Control Input 2

System/PloGGIO1.CO.SPCSO2.ctlVal

[12 12] Control Input 3

System/PloGGIO1.CO.SPCSO3.ctlVal

[12 13] Control Input 4

System/PloGGIO1.CO.SPCSO4.ctlVal

[12 14] Control Input 5

Page 93: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 92 MiCOM P40Agile P14NB

Courier Cell Attribute Reference System/PloGGIO1.CO.SPCSO5.ctlVal

[12 15] Control Input 6

System/PloGGIO1.CO.SPCSO6.ctlVal

[12 16] Control Input 7

System/PloGGIO1.CO.SPCSO7.ctlVal

[12 17] Control Input 8

System/PloGGIO1.CO.SPCSO8.ctlVal

[12 18] Control Input 9

System/PloGGIO1.CO.SPCSO9.ctlVal

[12 19] Control Input 10

System/PloGGIO1.CO.SPCSO10.ctlVal

[12 1A] Control Input 11

System/PloGGIO1.CO.SPCSO11.ctlVal

[12 1B] Control Input 12

System/PloGGIO1.CO.SPCSO12.ctlVal

[12 1C] Control Input 13

System/PloGGIO1.CO.SPCSO13.ctlVal

[12 1D] Control Input 14

System/PloGGIO1.CO.SPCSO14.ctlVal

[12 1E] Control Input 15

System/PloGGIO1.CO.SPCSO15.ctlVal

[12 1F] Control Input 16

System/PloGGIO1.CO.SPCSO16.ctlVal

[12 20] Control Input 17

System/PloGGIO1.CO.SPCSO17.ctlVal

[12 21] Control Input 18

System/PloGGIO1.CO.SPCSO18.ctlVal

[12 22] Control Input 19

System/PloGGIO1.CO.SPCSO19.ctlVal

[12 23] Control Input 20

System/PloGGIO1.CO.SPCSO20.ctlVal

[12 24] Control Input 21

System/PloGGIO1.CO.SPCSO21.ctlVal

[12 25] Control Input 22

System/PloGGIO1.CO.SPCSO22.ctlVal

[12 26] Control Input 23

System/PloGGIO1.CO.SPCSO23.ctlVal

[12 27] Control Input 24

System/PloGGIO1.CO.SPCSO24.ctlVal

[12 28] Control Input 25

System/PloGGIO1.CO.SPCSO25.ctlVal

[12 29] Control Input 26

System/PloGGIO1.CO.SPCSO26.ctlVal

[12 2A] Control Input 27

System/PloGGIO1.CO.SPCSO27.ctlVal

[12 2B] Control Input 28

Page 94: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 93

Courier Cell Attribute Reference System/PloGGIO1.CO.SPCSO28.ctlVal

[12 2C] Control Input 29

System/PloGGIO1.CO.SPCSO29.ctlVal

[12 2D] Control Input 30

System/PloGGIO1.CO.SPCSO30.ctlVal

[12 2E] Control Input 31

System/PloGGIO1.CO.SPCSO31.ctlVal

[12 2F] Control Input 32

System/PloGGIO1.CO.SPCSO32.ctlVal

[12 30] Control Input 33

System/PloGGIO1.CO.SPCSO33.ctlVal

[12 31] Control Input 34

System/PloGGIO1.CO.SPCSO34.ctlVal

[12 32] Control Input 35

System/PloGGIO1.CO.SPCSO35.ctlVal

[12 33] Control Input 36

System/PloGGIO1.CO.SPCSO36.ctlVal

[12 34] Control Input 37

System/PloGGIO1.CO.SPCSO37.ctlVal

[12 35] Control Input 38

System/PloGGIO1.CO.SPCSO38.ctlVal

[12 36] Control Input 39

System/PloGGIO1.CO.SPCSO39.ctlVal

[12 37] Control Input 40

System/PloGGIO1.CO.SPCSO40.ctlVal

[12 38] Control Input 41

System/PloGGIO1.CO.SPCSO41.ctlVal

[12 39] Control Input 42

System/PloGGIO1.CO.SPCSO42.ctlVal

[12 3A] Control Input 43

System/PloGGIO1.CO.SPCSO43.ctlVal

[12 3B] Control Input 44

System/PloGGIO1.CO.SPCSO44.ctlVal

[12 3C] Control Input 45

System/PloGGIO1.CO.SPCSO45.ctlVal

[12 3D] Control Input 46

System/PloGGIO1.CO.SPCSO46.ctlVal

[12 3E] Control Input 47

System/PloGGIO1.CO.SPCSO47.ctlVal

[12 3F] Control Input 48

System/PloGGIO1.CO.SPCSO48.ctlVal

[12 40] Control Input 49

System/PloGGIO1.CO.SPCSO49.ctlVal

[12 41] Control Input 50

System/PloGGIO1.CO.SPCSO50.ctlVal

[12 42] Control Input 51

Page 95: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 94 MiCOM P40Agile P14NB

Courier Cell Attribute Reference System/PloGGIO1.CO.SPCSO51.ctlVal

[12 43] Control Input 52

System/PloGGIO1.CO.SPCSO52.ctlVal

[12 44] Control Input 53

System/PloGGIO1.CO.SPCSO53.ctlVal

[12 45] Control Input 54

System/PloGGIO1.CO.SPCSO54.ctlVal

[12 46] Control Input 55

System/PloGGIO1.CO.SPCSO55.ctlVal

[12 47] Control Input 56

System/PloGGIO1.CO.SPCSO56.ctlVal

[12 48] Control Input 57

System/PloGGIO1.CO.SPCSO57.ctlVal

[12 49] Control Input 58

System/PloGGIO1.CO.SPCSO58.ctlVal

[12 4A] Control Input 59

System/PloGGIO1.CO.SPCSO59.ctlVal

[12 4B] Control Input 60

System/PloGGIO1.CO.SPCSO60.ctlVal

[12 4C] Control Input 61

System/PloGGIO1.CO.SPCSO61.ctlVal

[12 4D] Control Input 62

System/PloGGIO1.CO.SPCSO62.ctlVal

[12 4E] Control Input 63

System/PloGGIO1.CO.SPCSO63.ctlVal

[12 4F] Control Input 64

System/PloGGIO1.CO.SPCSO64.ctlVal

[17 01] Fn Key Status

System/FnkGGIO1.DC.NamPlt.d

[17 04] Fn Key 1 Label

System/FnkGGIO1.DC.Ind1.d

[17 07] Fn Key 2 Label

System/FnkGGIO1.DC.Ind2.d

[17 0A] Fn Key 3 Label

System/FnkGGIO1.DC.Ind3.d

[35 23] I>1 Function

Protection/OcpPTOC1.ST.Mod.stVal

Protection/OcpPTOC1.DC.NamPlt.d

[35 24] I>1 Direction

Protection/OcpPTOC1.ST.Str.dirPhsC

Protection/OcpPTOC1.ST.Str.dirPhsB

Protection/OcpPTOC1.ST.Str.dirPhsA

Protection/OcpPTOC1.ST.Str.dirGeneral

[35 32] I>2 Function

Protection/OcpPTOC2.ST.Mod.stVal

Protection/OcpPTOC2.DC.NamPlt.d

Page 96: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 95

Courier Cell Attribute Reference [35 33] I>2 Direction

Protection/OcpPTOC2.ST.Str.dirPhsB

Protection/OcpPTOC2.ST.Str.dirPhsA

Protection/OcpPTOC2.ST.Str.dirGeneral

Protection/OcpPTOC2.ST.Str.dirPhsC

[35 40] I>3 Status

Protection/OcpPTOC3.ST.Mod.stVal

Protection/OcpPTOC3.DC.NamPlt.d

[35 41] I>3 Direction

Protection/OcpPTOC3.ST.Str.dirPhsA

Protection/OcpPTOC3.ST.Str.dirGeneral

Protection/OcpPTOC3.ST.Str.dirPhsC

Protection/OcpPTOC3.ST.Str.dirPhsB

[35 47] I>4 Status

Protection/OcpPTOC4.ST.Mod.stVal

Protection/OcpPTOC4.DC.NamPlt.d

[35 48] I>4 Direction

Protection/OcpPTOC4.ST.Str.dirPhsC

Protection/OcpPTOC4.ST.Str.dirPhsB

Protection/OcpPTOC4.ST.Str.dirPhsA

Protection/OcpPTOC4.ST.Str.dirGeneral

[35 63] I>5 Function

Protection/OcpPTOC5.ST.Mod.stVal

Protection/OcpPTOC5.DC.NamPlt.d

[35 64] I>5 Direction

Protection/OcpPTOC5.ST.Str.dirPhsB

Protection/OcpPTOC5.ST.Str.dirGeneral

Protection/OcpPTOC5.ST.Str.dirPhsA

Protection/OcpPTOC5.ST.Str.dirPhsC

[35 71] I>6 Status

Protection/OcpPTOC6.DC.NamPlt.d

Protection/OcpPTOC6.ST.Mod.stVal

[35 72] I>6 Direction

Protection/OcpPTOC6.ST.Str.dirGeneral

Protection/OcpPTOC6.ST.Str.dirPhsC

Protection/OcpPTOC6.ST.Str.dirPhsA

Protection/OcpPTOC6.ST.Str.dirPhsB

[36 10] I2>1 Status

Protection/NgcPTOC1.DC.NamPlt.d

Protection/NgcPTOC1.ST.Mod.stVal

[36 12] I2>1 Directional

Protection/NgcPTOC1.ST.Str.dirGeneral

[36 20] I2>2 Status

Protection/NgcPTOC2.DC.NamPlt.d

Protection/NgcPTOC2.ST.Mod.stVal

[36 22] I2>2 Directional

Page 97: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 96 MiCOM P40Agile P14NB

Courier Cell Attribute Reference Protection/NgcPTOC2.ST.Str.dirGeneral

[36 30] I2>3 Status

Protection/NgcPTOC3.ST.Mod.stVal

Protection/NgcPTOC3.DC.NamPlt.d

[36 32] I2>3 Directional

Protection/NgcPTOC3.ST.Str.dirGeneral

[36 40] I2>4 Status

Protection/NgcPTOC4.ST.Mod.stVal

Protection/NgcPTOC4.DC.NamPlt.d

[36 42] I2>4 Directional

Protection/NgcPTOC4.ST.Str.dirGeneral

[38 25] IN1>1 Function

Protection/EfmPTOC1.DC.NamPlt.d

Protection/EfmPTOC1.ST.Mod.stVal

[38 26] IN1>1 Direction

Protection/EfmPTOC1.ST.Str.dirGeneral

Protection/EfmPTOC1.ST.Str.dirNeut

[38 36] IN1>2 Function

Protection/EfmPTOC2.ST.Mod.stVal

Protection/EfmPTOC2.DC.NamPlt.d

[38 37] IN1>2 Direction

Protection/EfmPTOC2.ST.Str.dirGeneral

Protection/EfmPTOC2.ST.Str.dirNeut

[38 46] IN1>3 Status

Protection/EfmPTOC3.ST.Mod.stVal

Protection/EfmPTOC3.DC.NamPlt.d

[38 47] IN1>3 Direction

Protection/EfmPTOC3.ST.Str.dirNeut

Protection/EfmPTOC3.ST.Str.dirGeneral

[38 4D] IN1>4 Status

Protection/EfmPTOC4.ST.Mod.stVal

Protection/EfmPTOC4.DC.NamPlt.d

[38 4E] IN1>4 Direction

Protection/EfmPTOC4.ST.Str.dirGeneral

Protection/EfmPTOC4.ST.Str.dirNeut

[39 25] IN2>1 Function

Protection/EfdPTOC1.DC.NamPlt.d

Protection/EfdPTOC1.ST.Mod.stVal

[39 26] IN2>1 Direction

Protection/EfdPTOC1.ST.Str.dirNeut

Protection/EfdPTOC1.ST.Str.dirGeneral

[39 36] IN2>2 Function

Protection/EfdPTOC2.ST.Mod.stVal

Protection/EfdPTOC2.DC.NamPlt.d

[39 37] IN2>2 Direction

Protection/EfdPTOC2.ST.Str.dirGeneral

Page 98: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 97

Courier Cell Attribute Reference Protection/EfdPTOC2.ST.Str.dirNeut

[39 46] IN2>3 Status

Protection/EfdPTOC3.DC.NamPlt.d

Protection/EfdPTOC3.ST.Mod.stVal

[39 47] IN2>3 Direction

Protection/EfdPTOC3.ST.Str.dirGeneral

Protection/EfdPTOC3.ST.Str.dirNeut

[39 4D] IN2>4 Status

Protection/EfdPTOC4.ST.Mod.stVal

Protection/EfdPTOC4.DC.NamPlt.d

[39 4E] IN2>4 Direction

Protection/EfdPTOC4.ST.Str.dirGeneral

Protection/EfdPTOC4.ST.Str.dirNeut

[3A 2A] ISEF>1 Function

Protection/SenEftPTOC1.DC.NamPlt.d

[3A 2B] ISEF>1 Direction

Protection/SenEftPTOC1.ST.Str.dirGeneral

Protection/SenEftPTOC1.ST.Str.dirNeut

[3A 3A] ISEF>2 Function

Protection/SenEftPTOC2.DC.NamPlt.d

[3A 3B] ISEF>2 Direction

Protection/SenEftPTOC2.ST.Str.dirNeut

Protection/SenEftPTOC2.ST.Str.dirGeneral

[3A 49] ISEF>3 Status

Protection/SenEftPTOC3.DC.NamPlt.d

[3A 4A] ISEF>3 Direction

Protection/SenEftPTOC3.ST.Str.dirNeut

Protection/SenEftPTOC3.ST.Str.dirGeneral

[3A 50] ISEF>4 Status

Protection/SenEftPTOC4.DC.NamPlt.d

[3A 51] ISEF>4 Direction

Protection/SenEftPTOC4.ST.Str.dirNeut

Protection/SenEftPTOC4.ST.Str.dirGeneral

[3C 01] Characteristic

Protection/ThmPTTR1.ST.Mod.stVal

[45 02] CB Fail 1 Status

Protection/CbfRBRF1.DC.NamPlt.d

Protection/CbfRBRF1.ST.Mod.stVal

[45 04] CB Fail 2 Status

Protection/CbfRBRF2.ST.Mod.stVal

Protection/CbfRBRF2.DC.NamPlt.d

[4A 01] Opto Input 1

System/OptGGIO1.DC.Ind1.d

[4A 02] Opto Input 2

System/OptGGIO1.DC.Ind2.d

[4A 03] Opto Input 3

Page 99: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 98 MiCOM P40Agile P14NB

Courier Cell Attribute Reference System/OptGGIO1.DC.Ind3.d

[4A 04] Opto Input 4

System/OptGGIO1.DC.Ind4.d

[4A 05] Opto Input 5

System/OptGGIO1.DC.Ind5.d

[4A 06] Opto Input 6

System/OptGGIO1.DC.Ind6.d

[4A 07] Opto Input 7

System/OptGGIO1.DC.Ind7.d

[4A 08] Opto Input 8

System/OptGGIO1.DC.Ind8.d

[4B 01] Relay 1

System/RlyGGIO1.DC.Ind1.d

[4B 02] Relay 2

System/RlyGGIO1.DC.Ind2.d

[4B 03] Relay 3

System/RlyGGIO1.DC.Ind3.d

[4B 04] Relay 4

System/RlyGGIO1.DC.Ind4.d

[4B 05] Relay 5

System/RlyGGIO1.DC.Ind5.d

[4B 06] Relay 6

System/RlyGGIO1.DC.Ind6.d

[4B 07] Relay 7

System/RlyGGIO1.DC.Ind7.d

[4B 08] Relay 8

System/RlyGGIO1.DC.Ind8.d

[FE 01] OcpPTOC1.ST.Beh.stVal

Protection/OcpPTOC1.ST.Beh.stVal

[FE 02] OcpPTOC2.ST.Beh.stVal

Protection/OcpPTOC2.ST.Beh.stVal

[FE 03] OcpPTOC3.ST.Beh.stVal

Protection/OcpPTOC3.ST.Beh.stVal

[FE 04] OcpPTOC4.ST.Beh.stVal

Protection/OcpPTOC4.ST.Beh.stVal

[FE 07] CbfRBRF1.ST.Beh.stVal

Protection/CbfRBRF1.ST.Beh.stVal

[FE 08] CbfRBRF2.ST.Beh.stVal

Protection/CbfRBRF2.ST.Beh.stVal

[FE 0D] EfdPTOC1.ST.Beh.stVal

Protection/EfdPTOC1.ST.Beh.stVal

[FE 0E] EfdPTOC2.ST.Beh.stVal

Protection/EfdPTOC2.ST.Beh.stVal

[FE 0F] EfdPTOC3.ST.Beh.stVal

Protection/EfdPTOC3.ST.Beh.stVal

[FE 10] EfdPTOC4.ST.Beh.stVal

Page 100: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 99

Courier Cell Attribute Reference Protection/EfdPTOC4.ST.Beh.stVal

[FE 11] EfmPTOC1.ST.Beh.stVal

Protection/EfmPTOC1.ST.Beh.stVal

[FE 12] EfmPTOC2.ST.Beh.stVal

Protection/EfmPTOC2.ST.Beh.stVal

[FE 13] EfmPTOC3.ST.Beh.stVal

Protection/EfmPTOC3.ST.Beh.stVal

[FE 14] EfmPTOC4.ST.Beh.stVal

Protection/EfmPTOC4.ST.Beh.stVal

[FE 1B] NgcPTOC1.ST.Beh.stVal

Protection/NgcPTOC1.ST.Beh.stVal

[FE 1C] NgcPTOC2.ST.Beh.stVal

Protection/NgcPTOC2.ST.Beh.stVal

[FE 1D] NgcPTOC3.ST.Beh.stVal

Protection/NgcPTOC3.ST.Beh.stVal

[FE 1E] NgcPTOC4.ST.Beh.stVal

Protection/NgcPTOC4.ST.Beh.stVal

[FE 27] SenSefPTOC1.ST.Mod.stVal

Protection/SenEftPTOC1.ST.Mod.stVal

[FE 28] SenSefPTOC2.ST.Mod.stVal

Protection/SenEftPTOC2.ST.Mod.stVal

[FE 29] SenSefPTOC3.ST.Mod.stVal

Protection/SenEftPTOC3.ST.Mod.stVal

[FE 2A] SenSefPTOC4.ST.Mod.stVal

Protection/SenEftPTOC4.ST.Mod.stVal

[FE 2B] SenSefPTOC1.ST.Beh.stVal

Protection/SenEftPTOC1.ST.Beh.stVal

[FE 2C] SenSefPTOC2.ST.Beh.stVal

Protection/SenEftPTOC2.ST.Beh.stVal

[FE 2D] SenSefPTOC3.ST.Beh.stVal

Protection/SenEftPTOC3.ST.Beh.stVal

[FE 2E] SenSefPTOC4.ST.Beh.stVal

Protection/SenEftPTOC4.ST.Beh.stVal

[FE 2F] ThmPTTR1.Beh.stVal

Protection/ThmPTTR1.ST.Beh.stVal

[FE 39] OcpPTOC5.ST.Beh.stVal

Protection/OcpPTOC5.ST.Beh.stVal

[FE 3A] OcpPTOC6.ST.Beh.stVal

Protection/OcpPTOC6.ST.Beh.stVal

2.3 DIGITAL DATABUS (DDB) MAPPING

The following table presents the DDB signal mappings.

DDB Name Attribute Reference DDB_OUTPUT_RELAY_1

System/RlyGGIO1.ST.Ind1.stVal

DDB_OUTPUT_RELAY_2

Page 101: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 100 MiCOM P40Agile P14NB

DDB Name Attribute Reference System/RlyGGIO1.ST.Ind2.stVal

DDB_OUTPUT_RELAY_3

System/RlyGGIO1.ST.Ind3.stVal

DDB_OUTPUT_RELAY_4

System/RlyGGIO1.ST.Ind4.stVal

DDB_OUTPUT_RELAY_5

System/RlyGGIO1.ST.Ind5.stVal

DDB_OUTPUT_RELAY_6

System/RlyGGIO1.ST.Ind6.stVal

DDB_OUTPUT_RELAY_7

System/RlyGGIO1.ST.Ind7.stVal

DDB_OUTPUT_RELAY_8

System/RlyGGIO1.ST.Ind8.stVal

DDB_OPTO_ISOLATOR_1

System/OptGGIO1.ST.Ind1.stVal

DDB_OPTO_ISOLATOR_2

System/OptGGIO1.ST.Ind2.stVal

DDB_OPTO_ISOLATOR_3

System/OptGGIO1.ST.Ind3.stVal

DDB_OPTO_ISOLATOR_4

System/OptGGIO1.ST.Ind4.stVal

DDB_OPTO_ISOLATOR_5

System/OptGGIO1.ST.Ind5.stVal

DDB_OPTO_ISOLATOR_6

System/OptGGIO1.ST.Ind6.stVal

DDB_OPTO_ISOLATOR_7

System/OptGGIO1.ST.Ind7.stVal

DDB_OPTO_ISOLATOR_8

System/OptGGIO1.ST.Ind8.stVal

DDB_ILLEGAL_OPTO_SETTINGS_GROUP

System/AlmGGIO1.DC.Alm3.d

System/AlmGGIO1.ST.Alm3.stVal

DDB_OOS_ALARM

System/AlmGGIO1.DC.Alm4.d

System/AlmGGIO1.ST.Alm4.stVal

DDB_FREQ_ALARM

System/AlmGGIO1.DC.Alm5.d

System/AlmGGIO1.ST.Alm5.stVal

DDB_BREAKER_FAIL_ALARM

System/AlmGGIO1.DC.Alm8.d

System/AlmGGIO1.ST.Alm8.stVal

DDB_BROKEN_CURRENT_ALARM

System/AlmGGIO1.DC.Alm9.d

System/AlmGGIO1.ST.Alm9.stVal

DDB_BROKEN_CURRENT_LOCKOUT

System/AlmGGIO1.DC.Alm10.d

Page 102: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 101

DDB Name Attribute Reference System/AlmGGIO1.ST.Alm10.stVal

DDB_MAINTENANCE_ALARM

System/AlmGGIO1.DC.Alm11.d

System/AlmGGIO1.ST.Alm11.stVal

DDB_MAINTENANCE_LOCKOUT

System/AlmGGIO1.DC.Alm12.d

System/AlmGGIO1.ST.Alm12.stVal

DDB_EXCESSIVE_OP_TIME_ALARM

System/AlmGGIO1.DC.Alm13.d

System/AlmGGIO1.ST.Alm13.stVal

DDB_EXCESSIVE_OP_TIME_LOCKOUT

System/AlmGGIO1.DC.Alm14.d

System/AlmGGIO1.ST.Alm14.stVal

DDB_EFF_LOCKOUT

System/AlmGGIO1.DC.Alm15.d

System/AlmGGIO1.ST.Alm15.stVal

DDB_CB_STATUS_ALARM

System/AlmGGIO1.DC.Alm16.d

System/AlmGGIO1.ST.Alm16.stVal

DDB_CB_FAILED_TO_TRIP

System/AlmGGIO1.DC.Alm17.d

System/AlmGGIO1.ST.Alm17.stVal

DDB_CB_FAILED_TO_CLOSE

System/AlmGGIO1.DC.Alm18.d

System/AlmGGIO1.ST.Alm18.stVal

DDB_CONTROL_CB_UNHEALTHY

System/AlmGGIO1.ST.Alm19.stVal

System/AlmGGIO1.DC.Alm19.d

DDB_USER_ALARM_1

System/AlmGGIO1.DC.Alm26.d

System/AlmGGIO1.ST.Alm26.stVal

DDB_USER_ALARM_2

System/AlmGGIO1.DC.Alm27.d

System/AlmGGIO1.ST.Alm27.stVal

DDB_USER_ALARM_3

System/AlmGGIO1.DC.Alm28.d

System/AlmGGIO1.ST.Alm28.stVal

DDB_USER_ALARM_4

System/AlmGGIO1.DC.Alm29.d

System/AlmGGIO1.ST.Alm29.stVal

DDB_USER_ALARM_5

System/AlmGGIO1.DC.Alm30.d

System/AlmGGIO1.ST.Alm30.stVal

DDB_USER_ALARM_6

System/AlmGGIO1.DC.Alm31.d

System/AlmGGIO1.ST.Alm31.stVal

Page 103: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 102 MiCOM P40Agile P14NB

DDB Name Attribute Reference DDB_USER_ALARM_7

System/AlmGGIO1.ST.Alm32.stVal

System/AlmGGIO1.DC.Alm32.d

DDB_USER_ALARM_8

System/AlmGGIO1.DC.Alm37.d

System/AlmGGIO1.ST.Alm37.stVal

DDB_USER_ALARM_9

System/AlmGGIO1.ST.Alm38.stVal

System/AlmGGIO1.DC.Alm38.d

DDB_USER_ALARM_10

System/AlmGGIO1.ST.Alm39.stVal

System/AlmGGIO1.DC.Alm39.d

DDB_USER_ALARM_11

System/AlmGGIO1.DC.Alm40.d

System/AlmGGIO1.ST.Alm40.stVal

DDB_USER_ALARM_12

System/AlmGGIO1.DC.Alm41.d

System/AlmGGIO1.ST.Alm41.stVal

DDB_USER_ALARM_13

System/AlmGGIO1.DC.Alm42.d

System/AlmGGIO1.ST.Alm42.stVal

DDB_USER_ALARM_14

System/AlmGGIO1.ST.Alm43.stVal

System/AlmGGIO1.DC.Alm43.d

DDB_USER_ALARM_15

System/AlmGGIO1.DC.Alm44.d

System/AlmGGIO1.ST.Alm44.stVal

DDB_USER_ALARM_16

System/AlmGGIO1.DC.Alm45.d

System/AlmGGIO1.ST.Alm45.stVal

DDB_USER_ALARM_17

System/AlmGGIO1.ST.Alm46.stVal

System/AlmGGIO1.DC.Alm46.d

DDB_USER_ALARM_18

System/AlmGGIO1.DC.Alm47.d

System/AlmGGIO1.ST.Alm47.stVal

DDB_USER_ALARM_19

System/AlmGGIO1.DC.Alm48.d

System/AlmGGIO1.ST.Alm48.stVal

DDB_USER_ALARM_20

System/AlmGGIO1.ST.Alm49.stVal

System/AlmGGIO1.DC.Alm49.d

DDB_USER_ALARM_21

System/AlmGGIO1.ST.Alm50.stVal

System/AlmGGIO1.DC.Alm50.d

DDB_USER_ALARM_22

Page 104: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 103

DDB Name Attribute Reference System/AlmGGIO1.DC.Alm51.d

System/AlmGGIO1.ST.Alm51.stVal

DDB_USER_ALARM_23

System/AlmGGIO1.DC.Alm52.d

System/AlmGGIO1.ST.Alm52.stVal

DDB_USER_ALARM_24

System/AlmGGIO1.DC.Alm53.d

System/AlmGGIO1.ST.Alm53.stVal

DDB_USER_ALARM_25

System/AlmGGIO1.ST.Alm54.stVal

System/AlmGGIO1.DC.Alm54.d

DDB_USER_ALARM_26

System/AlmGGIO1.DC.Alm55.d

System/AlmGGIO1.ST.Alm55.stVal

DDB_USER_ALARM_27

System/AlmGGIO1.DC.Alm56.d

System/AlmGGIO1.ST.Alm56.stVal

DDB_USER_ALARM_28

System/AlmGGIO1.ST.Alm57.stVal

System/AlmGGIO1.DC.Alm57.d

DDB_USER_ALARM_29

System/AlmGGIO1.DC.Alm58.d

System/AlmGGIO1.ST.Alm58.stVal

DDB_USER_ALARM_30

System/AlmGGIO1.DC.Alm59.d

System/AlmGGIO1.ST.Alm59.stVal

DDB_USER_ALARM_31

System/AlmGGIO1.ST.Alm60.stVal

System/AlmGGIO1.DC.Alm60.d

DDB_USER_ALARM_32

System/AlmGGIO1.ST.Alm61.stVal

System/AlmGGIO1.DC.Alm61.d

DDB_USER_ALARM_33

System/AlmGGIO1.DC.Alm62.d

System/AlmGGIO1.ST.Alm62.stVal

DDB_USER_ALARM_34

System/AlmGGIO1.DC.Alm63.d

System/AlmGGIO1.ST.Alm63.stVal

DDB_USER_ALARM_35

System/AlmGGIO1.ST.Alm64.stVal

System/AlmGGIO1.DC.Alm64.d

DDB_POC_1_3PH_TRIP

Protection/OcpPTOC1.ST.Op.general

DDB_POC_1_PH_A_TRIP

Protection/OcpPTOC1.ST.Op.phsA

DDB_POC_1_PH_B_TRIP

Page 105: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 104 MiCOM P40Agile P14NB

DDB Name Attribute Reference Protection/OcpPTOC1.ST.Op.phsB

DDB_POC_1_PH_C_TRIP

Protection/OcpPTOC1.ST.Op.phsC

DDB_POC_2_3PH_TRIP

Protection/OcpPTOC2.ST.Op.general

DDB_POC_2_PH_A_TRIP

Protection/OcpPTOC2.ST.Op.phsA

DDB_POC_2_PH_B_TRIP

Protection/OcpPTOC2.ST.Op.phsB

DDB_POC_2_PH_C_TRIP

Protection/OcpPTOC2.ST.Op.phsC

DDB_POC_3_3PH_TRIP

Protection/OcpPTOC3.ST.Op.general

DDB_POC_3_PH_A_TRIP

Protection/OcpPTOC3.ST.Op.phsA

DDB_POC_3_PH_B_TRIP

Protection/OcpPTOC3.ST.Op.phsB

DDB_POC_3_PH_C_TRIP

Protection/OcpPTOC3.ST.Op.phsC

DDB_POC_4_3PH_TRIP

Protection/OcpPTOC4.ST.Op.general

DDB_POC_4_PH_A_TRIP

Protection/OcpPTOC4.ST.Op.phsA

DDB_POC_4_PH_B_TRIP

Protection/OcpPTOC4.ST.Op.phsB

DDB_POC_4_PH_C_TRIP

Protection/OcpPTOC4.ST.Op.phsC

DDB_EF1_1_TRIP

Protection/EfmPTOC1.ST.Op.general

Protection/EfmPTOC1.ST.Op.neut

DDB_EF1_2_TRIP

Protection/EfmPTOC2.ST.Op.neut

Protection/EfmPTOC2.ST.Op.general

DDB_EF1_3_TRIP

Protection/EfmPTOC3.ST.Op.general

Protection/EfmPTOC3.ST.Op.neut

DDB_EF1_4_TRIP

Protection/EfmPTOC4.ST.Op.neut

Protection/EfmPTOC4.ST.Op.general

DDB_EF2_1_TRIP

Protection/EfdPTOC1.ST.Op.neut

Protection/EfdPTOC1.ST.Op.general

DDB_EF2_2_TRIP

Protection/EfdPTOC2.ST.Op.neut

Protection/EfdPTOC2.ST.Op.general

DDB_EF2_3_TRIP

Page 106: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 105

DDB Name Attribute Reference Protection/EfdPTOC3.ST.Op.general

Protection/EfdPTOC3.ST.Op.neut

DDB_EF2_4_TRIP

Protection/EfdPTOC4.ST.Op.neut

Protection/EfdPTOC4.ST.Op.general

DDB_SEF_1_TRIP

Protection/SenEftPTOC1.ST.Op.general

Protection/SenEftPTOC1.ST.Op.neut

DDB_SEF_2_TRIP

Protection/SenEftPTOC2.ST.Op.neut

Protection/SenEftPTOC2.ST.Op.general

DDB_SEF_3_TRIP

Protection/SenEftPTOC3.ST.Op.neut

Protection/SenEftPTOC3.ST.Op.general

DDB_SEF_4_TRIP

Protection/SenEftPTOC4.ST.Op.neut

Protection/SenEftPTOC4.ST.Op.general

DDB_THERMAL_TRIP

Protection/ThmPTTR1.ST.Op.general

DDB_ANY_START

Protection/PTRC1.ST.Str.general

DDB_POC_1_3PH_START

Protection/OcpPTOC1.ST.Str.general

DDB_POC_1_PH_A_START

Protection/OcpPTOC1.ST.Str.phsA

DDB_POC_1_PH_B_START

Protection/OcpPTOC1.ST.Str.phsB

DDB_POC_1_PH_C_START

Protection/OcpPTOC1.ST.Str.phsC

DDB_POC_2_3PH_START

Protection/OcpPTOC2.ST.Str.general

DDB_POC_2_PH_A_START

Protection/OcpPTOC2.ST.Str.phsA

DDB_POC_2_PH_B_START

Protection/OcpPTOC2.ST.Str.phsB

DDB_POC_2_PH_C_START

Protection/OcpPTOC2.ST.Str.phsC

DDB_POC_3_3PH_START

Protection/OcpPTOC3.ST.Str.general

DDB_POC_3_PH_A_START

Protection/OcpPTOC3.ST.Str.phsA

DDB_POC_3_PH_B_START

Protection/OcpPTOC3.ST.Str.phsB

DDB_POC_3_PH_C_START

Protection/OcpPTOC3.ST.Str.phsC

DDB_POC_4_3PH_START

Page 107: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 106 MiCOM P40Agile P14NB

DDB Name Attribute Reference Protection/OcpPTOC4.ST.Str.general

DDB_POC_4_PH_A_START

Protection/OcpPTOC4.ST.Str.phsA

DDB_POC_4_PH_B_START

Protection/OcpPTOC4.ST.Str.phsB

DDB_POC_4_PH_C_START

Protection/OcpPTOC4.ST.Str.phsC

DDB_EF1_1_START

Protection/EfmPTOC1.ST.Str.neut

Protection/EfmPTOC1.ST.Str.general

DDB_EF1_2_START

Protection/EfmPTOC2.ST.Str.general

Protection/EfmPTOC2.ST.Str.neut

DDB_EF1_3_START

Protection/EfmPTOC3.ST.Str.neut

Protection/EfmPTOC3.ST.Str.general

DDB_EF1_4_START

Protection/EfmPTOC4.ST.Str.neut

Protection/EfmPTOC4.ST.Str.general

DDB_EF2_1_START

Protection/EfdPTOC1.ST.Str.neut

Protection/EfdPTOC1.ST.Str.general

DDB_EF2_2_START

Protection/EfdPTOC2.ST.Str.general

Protection/EfdPTOC2.ST.Str.neut

DDB_EF2_3_START

Protection/EfdPTOC3.ST.Str.general

Protection/EfdPTOC3.ST.Str.neut

DDB_EF2_4_START

Protection/EfdPTOC4.ST.Str.general

Protection/EfdPTOC4.ST.Str.neut

DDB_SEF_1_START

Protection/SenEftPTOC1.ST.Str.general

Protection/SenEftPTOC1.ST.Str.neut

DDB_SEF_2_START

Protection/SenEftPTOC2.ST.Str.general

Protection/SenEftPTOC2.ST.Str.neut

DDB_SEF_3_START

Protection/SenEftPTOC3.ST.Str.general

Protection/SenEftPTOC3.ST.Str.neut

DDB_SEF_4_START

Protection/SenEftPTOC4.ST.Str.general

Protection/SenEftPTOC4.ST.Str.neut

DDB_THERMAL_ALARM

Protection/ThmPTTR1.ST.AlmThm.general

DDB_CBF1_TRIP_3PH

Page 108: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 107

DDB Name Attribute Reference Protection/CbfRBRF1.ST.OpEx.general

DDB_CBF2_TRIP_3PH

Protection/CbfRBRF2.ST.OpEx.general

DDB_NPSOC_1_START

Protection/NgcPTOC1.ST.Str.general

DDB_NPSOC_2_START

Protection/NgcPTOC2.ST.Str.general

DDB_NPSOC_3_START

Protection/NgcPTOC3.ST.Str.general

DDB_NPSOC_4_START

Protection/NgcPTOC4.ST.Str.general

DDB_NPSOC_1_TRIP

Protection/NgcPTOC1.ST.Op.general

DDB_NPSOC_2_TRIP

Protection/NgcPTOC2.ST.Op.general

DDB_NPSOC_3_TRIP

Protection/NgcPTOC3.ST.Op.general

DDB_NPSOC_4_TRIP

Protection/NgcPTOC4.ST.Op.general

DDB_ANY_TRIP

Protection/PTRC1.ST.Tr.general

DDB_POC_5_3PH_TRIP

Protection/OcpPTOC5.ST.Op.general

DDB_POC_5_PH_A_TRIP

Protection/OcpPTOC5.ST.Op.phsA

DDB_POC_5_PH_B_TRIP

Protection/OcpPTOC5.ST.Op.phsB

DDB_POC_5_PH_C_TRIP

Protection/OcpPTOC5.ST.Op.phsC

DDB_POC_6_3PH_TRIP

Protection/OcpPTOC6.ST.Op.general

DDB_POC_6_PH_A_TRIP

Protection/OcpPTOC6.ST.Op.phsA

DDB_POC_6_PH_B_TRIP

Protection/OcpPTOC6.ST.Op.phsB

DDB_POC_6_PH_C_TRIP

Protection/OcpPTOC6.ST.Op.phsC

DDB_POC_5_3PH_START

Protection/OcpPTOC5.ST.Str.general

DDB_POC_5_PH_A_START

Protection/OcpPTOC5.ST.Str.phsA

DDB_POC_5_PH_B_START

Protection/OcpPTOC5.ST.Str.phsB

DDB_POC_5_PH_C_START

Protection/OcpPTOC5.ST.Str.phsC

DDB_POC_6_3PH_START

Page 109: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 108 MiCOM P40Agile P14NB

DDB Name Attribute Reference Protection/OcpPTOC6.ST.Str.general

DDB_POC_6_PH_A_START

Protection/OcpPTOC6.ST.Str.phsA

DDB_POC_6_PH_B_START

Protection/OcpPTOC6.ST.Str.phsB

DDB_POC_6_PH_C_START

Protection/OcpPTOC6.ST.Str.phsC

DDB_OUTPUT_TRI_LED_1_RED

System/LedGGIO1.ST.Ind1.stVal

System/LedGGIO1.DC.Ind1.d

DDB_OUTPUT_TRI_LED_1_GRN

System/LedGGIO2.ST.Ind1.stVal

System/LedGGIO2.DC.Ind1.d

DDB_OUTPUT_TRI_LED_2_RED

System/LedGGIO1.ST.Ind2.stVal

System/LedGGIO1.DC.Ind2.d

DDB_OUTPUT_TRI_LED_2_GRN

System/LedGGIO2.DC.Ind2.d

System/LedGGIO2.ST.Ind2.stVal

DDB_OUTPUT_TRI_LED_3_RED

System/LedGGIO1.DC.Ind3.d

System/LedGGIO1.ST.Ind3.stVal

DDB_OUTPUT_TRI_LED_3_GRN

System/LedGGIO2.ST.Ind3.stVal

System/LedGGIO2.DC.Ind3.d

DDB_OUTPUT_TRI_LED_4_RED

System/LedGGIO1.ST.Ind4.stVal

System/LedGGIO1.DC.Ind4.d

DDB_OUTPUT_TRI_LED_4_GRN

System/LedGGIO2.ST.Ind4.stVal

System/LedGGIO2.DC.Ind4.d

DDB_OUTPUT_TRI_LED_5_RED

System/LedGGIO1.DC.Ind5.d

System/LedGGIO1.ST.Ind5.stVal

DDB_OUTPUT_TRI_LED_5_GRN

System/LedGGIO2.DC.Ind5.d

System/LedGGIO2.ST.Ind5.stVal

DDB_OUTPUT_TRI_LED_6_RED

System/LedGGIO1.ST.Ind6.stVal

System/LedGGIO1.DC.Ind6.d

DDB_OUTPUT_TRI_LED_6_GRN

System/LedGGIO2.ST.Ind6.stVal

System/LedGGIO2.DC.Ind6.d

DDB_OUTPUT_TRI_LED_7_RED

System/LedGGIO1.ST.Ind7.stVal

System/LedGGIO1.DC.Ind7.d

Page 110: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 109

DDB Name Attribute Reference DDB_OUTPUT_TRI_LED_7_GRN

System/LedGGIO2.DC.Ind7.d

System/LedGGIO2.ST.Ind7.stVal

DDB_OUTPUT_TRI_LED_8_RED

System/LedGGIO1.ST.Ind8.stVal

System/LedGGIO1.DC.Ind8.d

DDB_OUTPUT_TRI_LED_8_GRN

System/LedGGIO2.DC.Ind8.d

System/LedGGIO2.ST.Ind8.stVal

DDB_OUTPUT_TRI_LED_9_RED

System/LedGGIO1.ST.Ind9.stVal

System/LedGGIO1.DC.Ind9.d

DDB_OUTPUT_TRI_LED_9_GRN

System/LedGGIO2.ST.Ind9.stVal

System/LedGGIO2.DC.Ind9.d

DDB_OUTPUT_TRI_LED_10_RED

System/LedGGIO1.DC.Ind10.d

System/LedGGIO1.ST.Ind10.stVal

DDB_OUTPUT_TRI_LED_10_GRN

System/LedGGIO2.ST.Ind10.stVal

System/LedGGIO2.DC.Ind10.d

DDB_OUTPUT_TRI_LED_11_RED

System/LedGGIO1.ST.Ind11.stVal

System/LedGGIO1.DC.Ind11.d

DDB_OUTPUT_TRI_LED_11_GRN

System/LedGGIO2.ST.Ind11.stVal

System/LedGGIO2.DC.Ind11.d

DDB_FN_KEY_1

System/FnkGGIO1.ST.Ind1.stVal

DDB_FN_KEY_2

System/FnkGGIO1.ST.Ind2.stVal

DDB_FN_KEY_3

System/FnkGGIO1.ST.Ind3.stVal

DDB_DC_SUPPLY_MON_ALARM

System/AlmGGIO1.ST.Alm65.stVal

System/AlmGGIO1.DC.Alm65.d

DDB_GOOSE_MISSING_IED_ALARM

System/AlmGGIO1.ST.Alm68.stVal

System/AlmGGIO1.DC.Alm68.d

DDB_ECARD_NOT_FITTED_ALARM

System/AlmGGIO1.ST.Alm69.stVal

System/AlmGGIO1.DC.Alm69.d

DDB_NIC_NOT_RESPONDING_ALARM

System/AlmGGIO1.DC.Alm70.d

System/AlmGGIO1.ST.Alm70.stVal

DDB_NIC_FATAL_ERROR_ALARM

Page 111: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 110 MiCOM P40Agile P14NB

DDB Name Attribute Reference System/AlmGGIO1.ST.Alm71.stVal

System/AlmGGIO1.DC.Alm71.d

DDB_INVALID_TCP_IP_CONFIG_ALARM

System/AlmGGIO1.ST.Alm73.stVal

System/AlmGGIO1.DC.Alm73.d

DDB_NIC_LINK_FAIL_ALARM

System/AlmGGIO1.ST.Alm75.stVal

System/AlmGGIO1.DC.Alm75.d

DDB_SW_MISMATCH_ALARM

System/AlmGGIO1.DC.Alm76.d

System/AlmGGIO1.ST.Alm76.stVal

DDB_IP_ADDRESS_CONFLICT_ALARM

System/AlmGGIO1.ST.Alm77.stVal

System/AlmGGIO1.DC.Alm77.d

DDB_CONTROL_1

System/PloGGIO1.ST.SPCSO1.stVal

DDB_CONTROL_2

System/PloGGIO1.ST.SPCSO2.stVal

DDB_CONTROL_3

System/PloGGIO1.ST.SPCSO3.stVal

DDB_CONTROL_4

System/PloGGIO1.ST.SPCSO4.stVal

DDB_CONTROL_5

System/PloGGIO1.ST.SPCSO5.stVal

DDB_CONTROL_6

System/PloGGIO1.ST.SPCSO6.stVal

DDB_CONTROL_7

System/PloGGIO1.ST.SPCSO7.stVal

DDB_CONTROL_8

System/PloGGIO1.ST.SPCSO8.stVal

DDB_CONTROL_9

System/PloGGIO1.ST.SPCSO9.stVal

DDB_CONTROL_10

System/PloGGIO1.ST.SPCSO10.stVal

DDB_CONTROL_11

System/PloGGIO1.ST.SPCSO11.stVal

DDB_CONTROL_12

System/PloGGIO1.ST.SPCSO12.stVal

DDB_CONTROL_13

System/PloGGIO1.ST.SPCSO13.stVal

DDB_CONTROL_14

System/PloGGIO1.ST.SPCSO14.stVal

DDB_CONTROL_15

System/PloGGIO1.ST.SPCSO15.stVal

DDB_CONTROL_16

System/PloGGIO1.ST.SPCSO16.stVal

Page 112: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 111

DDB Name Attribute Reference DDB_CONTROL_17

System/PloGGIO1.ST.SPCSO17.stVal

DDB_CONTROL_18

System/PloGGIO1.ST.SPCSO18.stVal

DDB_CONTROL_19

System/PloGGIO1.ST.SPCSO19.stVal

DDB_CONTROL_20

System/PloGGIO1.ST.SPCSO20.stVal

DDB_CONTROL_21

System/PloGGIO1.ST.SPCSO21.stVal

DDB_CONTROL_22

System/PloGGIO1.ST.SPCSO22.stVal

DDB_CONTROL_23

System/PloGGIO1.ST.SPCSO23.stVal

DDB_CONTROL_24

System/PloGGIO1.ST.SPCSO24.stVal

DDB_CONTROL_25

System/PloGGIO1.ST.SPCSO25.stVal

DDB_CONTROL_26

System/PloGGIO1.ST.SPCSO26.stVal

DDB_CONTROL_27

System/PloGGIO1.ST.SPCSO27.stVal

DDB_CONTROL_28

System/PloGGIO1.ST.SPCSO28.stVal

DDB_CONTROL_29

System/PloGGIO1.ST.SPCSO29.stVal

DDB_CONTROL_30

System/PloGGIO1.ST.SPCSO30.stVal

DDB_CONTROL_31

System/PloGGIO1.ST.SPCSO31.stVal

DDB_CONTROL_32

System/PloGGIO1.ST.SPCSO32.stVal

DDB_GOOSEIN_1

System/GosGGIO1.ST.Ind1.stVal

DDB_GOOSEIN_2

System/GosGGIO1.ST.Ind2.stVal

DDB_GOOSEIN_3

System/GosGGIO1.ST.Ind3.stVal

DDB_GOOSEIN_4

System/GosGGIO1.ST.Ind4.stVal

DDB_GOOSEIN_5

System/GosGGIO1.ST.Ind5.stVal

DDB_GOOSEIN_6

System/GosGGIO1.ST.Ind6.stVal

DDB_GOOSEIN_7

System/GosGGIO1.ST.Ind7.stVal

Page 113: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 112 MiCOM P40Agile P14NB

DDB Name Attribute Reference DDB_GOOSEIN_8

System/GosGGIO1.ST.Ind8.stVal

DDB_GOOSEIN_9

System/GosGGIO1.ST.Ind9.stVal

DDB_GOOSEIN_10

System/GosGGIO1.ST.Ind10.stVal

DDB_GOOSEIN_11

System/GosGGIO1.ST.Ind11.stVal

DDB_GOOSEIN_12

System/GosGGIO1.ST.Ind12.stVal

DDB_GOOSEIN_13

System/GosGGIO1.ST.Ind13.stVal

DDB_GOOSEIN_14

System/GosGGIO1.ST.Ind14.stVal

DDB_GOOSEIN_15

System/GosGGIO1.ST.Ind15.stVal

DDB_GOOSEIN_16

System/GosGGIO1.ST.Ind16.stVal

DDB_GOOSEIN_17

System/GosGGIO1.ST.Ind17.stVal

DDB_GOOSEIN_18

System/GosGGIO1.ST.Ind18.stVal

DDB_GOOSEIN_19

System/GosGGIO1.ST.Ind19.stVal

DDB_GOOSEIN_20

System/GosGGIO1.ST.Ind20.stVal

DDB_GOOSEIN_21

System/GosGGIO1.ST.Ind21.stVal

DDB_GOOSEIN_22

System/GosGGIO1.ST.Ind22.stVal

DDB_GOOSEIN_23

System/GosGGIO1.ST.Ind23.stVal

DDB_GOOSEIN_24

System/GosGGIO1.ST.Ind24.stVal

DDB_GOOSEIN_25

System/GosGGIO1.ST.Ind25.stVal

DDB_GOOSEIN_26

System/GosGGIO1.ST.Ind26.stVal

DDB_GOOSEIN_27

System/GosGGIO1.ST.Ind27.stVal

DDB_GOOSEIN_28

System/GosGGIO1.ST.Ind28.stVal

DDB_GOOSEIN_29

System/GosGGIO1.ST.Ind29.stVal

DDB_GOOSEIN_30

System/GosGGIO1.ST.Ind30.stVal

Page 114: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 113

DDB Name Attribute Reference DDB_GOOSEIN_31

System/GosGGIO1.ST.Ind31.stVal

DDB_GOOSEIN_32

System/GosGGIO1.ST.Ind32.stVal

DDB_GOOSEOUT_1

System/GosGGIO2.ST.Ind1.stVal

System/GosGGIO2.DC.Ind1.d

DDB_GOOSEOUT_2

System/GosGGIO2.DC.Ind2.d

System/GosGGIO2.ST.Ind2.stVal

DDB_GOOSEOUT_3

System/GosGGIO2.DC.Ind3.d

System/GosGGIO2.ST.Ind3.stVal

DDB_GOOSEOUT_4

System/GosGGIO2.DC.Ind4.d

System/GosGGIO2.ST.Ind4.stVal

DDB_GOOSEOUT_5

System/GosGGIO2.ST.Ind5.stVal

System/GosGGIO2.DC.Ind5.d

DDB_GOOSEOUT_6

System/GosGGIO2.DC.Ind6.d

System/GosGGIO2.ST.Ind6.stVal

DDB_GOOSEOUT_7

System/GosGGIO2.ST.Ind7.stVal

System/GosGGIO2.DC.Ind7.d

DDB_GOOSEOUT_8

System/GosGGIO2.DC.Ind8.d

System/GosGGIO2.ST.Ind8.stVal

DDB_GOOSEOUT_9

System/GosGGIO2.DC.Ind9.d

System/GosGGIO2.ST.Ind9.stVal

DDB_GOOSEOUT_10

System/GosGGIO2.ST.Ind10.stVal

System/GosGGIO2.DC.Ind10.d

DDB_GOOSEOUT_11

System/GosGGIO2.DC.Ind11.d

System/GosGGIO2.ST.Ind11.stVal

DDB_GOOSEOUT_12

System/GosGGIO2.DC.Ind12.d

System/GosGGIO2.ST.Ind12.stVal

DDB_GOOSEOUT_13

System/GosGGIO2.DC.Ind13.d

System/GosGGIO2.ST.Ind13.stVal

DDB_GOOSEOUT_14

System/GosGGIO2.DC.Ind14.d

System/GosGGIO2.ST.Ind14.stVal

Page 115: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 114 MiCOM P40Agile P14NB

DDB Name Attribute Reference DDB_GOOSEOUT_15

System/GosGGIO2.DC.Ind15.d

System/GosGGIO2.ST.Ind15.stVal

DDB_GOOSEOUT_16

System/GosGGIO2.ST.Ind16.stVal

System/GosGGIO2.DC.Ind16.d

DDB_GOOSEOUT_17

System/GosGGIO2.ST.Ind17.stVal

System/GosGGIO2.DC.Ind17.d

DDB_GOOSEOUT_18

System/GosGGIO2.DC.Ind18.d

System/GosGGIO2.ST.Ind18.stVal

DDB_GOOSEOUT_19

System/GosGGIO2.DC.Ind19.d

System/GosGGIO2.ST.Ind19.stVal

DDB_GOOSEOUT_20

System/GosGGIO2.DC.Ind20.d

System/GosGGIO2.ST.Ind20.stVal

DDB_GOOSEOUT_21

System/GosGGIO2.ST.Ind21.stVal

System/GosGGIO2.DC.Ind21.d

DDB_GOOSEOUT_22

System/GosGGIO2.ST.Ind22.stVal

System/GosGGIO2.DC.Ind22.d

DDB_GOOSEOUT_23

System/GosGGIO2.DC.Ind23.d

System/GosGGIO2.ST.Ind23.stVal

DDB_GOOSEOUT_24

System/GosGGIO2.DC.Ind24.d

System/GosGGIO2.ST.Ind24.stVal

DDB_GOOSEOUT_25

System/GosGGIO2.ST.Ind25.stVal

System/GosGGIO2.DC.Ind25.d

DDB_GOOSEOUT_26

System/GosGGIO2.DC.Ind26.d

System/GosGGIO2.ST.Ind26.stVal

DDB_GOOSEOUT_27

System/GosGGIO2.DC.Ind27.d

System/GosGGIO2.ST.Ind27.stVal

DDB_GOOSEOUT_28

System/GosGGIO2.DC.Ind28.d

System/GosGGIO2.ST.Ind28.stVal

DDB_GOOSEOUT_29

System/GosGGIO2.ST.Ind29.stVal

System/GosGGIO2.DC.Ind29.d

DDB_GOOSEOUT_30

Page 116: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Address Assignment List

P14NB-ADL-EN-7 MiCOM P40Agile P14NB (ADL) 115

DDB Name Attribute Reference System/GosGGIO2.DC.Ind30.d

System/GosGGIO2.ST.Ind30.stVal

DDB_GOOSEOUT_31

System/GosGGIO2.DC.Ind31.d

System/GosGGIO2.ST.Ind31.stVal

DDB_GOOSEOUT_32

System/GosGGIO2.DC.Ind32.d

System/GosGGIO2.ST.Ind32.stVal

DDB_CONTROL_33

System/PloGGIO1.ST.SPCSO33.stVal

DDB_CONTROL_34

System/PloGGIO1.ST.SPCSO34.stVal

DDB_CONTROL_35

System/PloGGIO1.ST.SPCSO35.stVal

DDB_CONTROL_36

System/PloGGIO1.ST.SPCSO36.stVal

DDB_CONTROL_37

System/PloGGIO1.ST.SPCSO37.stVal

DDB_CONTROL_38

System/PloGGIO1.ST.SPCSO38.stVal

DDB_CONTROL_39

System/PloGGIO1.ST.SPCSO39.stVal

DDB_CONTROL_40

System/PloGGIO1.ST.SPCSO40.stVal

DDB_CONTROL_41

System/PloGGIO1.ST.SPCSO41.stVal

DDB_CONTROL_42

System/PloGGIO1.ST.SPCSO42.stVal

DDB_CONTROL_43

System/PloGGIO1.ST.SPCSO43.stVal

DDB_CONTROL_44

System/PloGGIO1.ST.SPCSO44.stVal

DDB_CONTROL_45

System/PloGGIO1.ST.SPCSO45.stVal

DDB_CONTROL_46

System/PloGGIO1.ST.SPCSO46.stVal

DDB_CONTROL_47

System/PloGGIO1.ST.SPCSO47.stVal

DDB_CONTROL_48

System/PloGGIO1.ST.SPCSO48.stVal

DDB_CONTROL_49

System/PloGGIO1.ST.SPCSO49.stVal

DDB_CONTROL_50

System/PloGGIO1.ST.SPCSO50.stVal

DDB_CONTROL_51

System/PloGGIO1.ST.SPCSO51.stVal

Page 117: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

P14NB-ADL-EN-7

Address Assignment List (ADL) 116 MiCOM P40Agile P14NB

DDB Name Attribute Reference DDB_CONTROL_52

System/PloGGIO1.ST.SPCSO52.stVal

DDB_CONTROL_53

System/PloGGIO1.ST.SPCSO53.stVal

DDB_CONTROL_54

System/PloGGIO1.ST.SPCSO54.stVal

DDB_CONTROL_55

System/PloGGIO1.ST.SPCSO55.stVal

DDB_CONTROL_56

System/PloGGIO1.ST.SPCSO56.stVal

DDB_CONTROL_57

System/PloGGIO1.ST.SPCSO57.stVal

DDB_CONTROL_58

System/PloGGIO1.ST.SPCSO58.stVal

DDB_CONTROL_59

System/PloGGIO1.ST.SPCSO59.stVal

DDB_CONTROL_60

System/PloGGIO1.ST.SPCSO60.stVal

DDB_CONTROL_61

System/PloGGIO1.ST.SPCSO61.stVal

DDB_CONTROL_62

System/PloGGIO1.ST.SPCSO62.stVal

DDB_CONTROL_63

System/PloGGIO1.ST.SPCSO63.stVal

DDB_CONTROL_64

System/PloGGIO1.ST.SPCSO64.stVal

Page 118: MiCOM P40 Agile - GE Grid Solutions · MiCOM P40 Agile P14N Address ... This section details Courier Cell and Digital Data Bus assignments to IEC 61850 Data ... [02 07] - IN Measured

Imagination at work

Grid Solutions St Leonards Building Redhill Business Park Stafford, ST16 1WT, UK +44 (0) 1785 250 070 www.gegridsolutions.com/contact

© 2016 General Electric. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.